Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 08:35:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1785.51 | 358.38 | 358.38 |
Net Site Energy | 1785.51 | 358.38 | 358.38 |
Total Source Energy | 4914.08 | 986.33 | 986.33 |
Net Source Energy | 4914.08 | 986.33 | 986.33 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 255.17 | 243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 118.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 86.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 112.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1429.95 | 355.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 255.17 | 243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 118.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 86.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 112.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 255.17 | 243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 118.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 203.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 86.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 112.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 92.23 | 71.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 287.01 | 71.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 92.23 | 71.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 287.01 | 71.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1429.954 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1429.954 | 100.00 |
Total On-Site and Utility Electric Sources | 1429.954 | 100.00 |
Total Electricity End Uses | 1429.954 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 552.33 |
Time Setpoint Not Met During Occupied Cooling | 64.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2861.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.9322 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.9322 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.9322 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 07-FEB-07:49 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 193928.18 | 104611.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7126.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6938.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8184.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 234893.06 | 112796.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 193928.18 | 104611.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 7126.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6938.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8184.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 808.13 | 263.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 373.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 643.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 159.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 273.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 121.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4528.67 | 385.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 162.20 | 52.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 75.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 54.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 908.97 | 77.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 162.20 | 52.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 75.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 54.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 908.97 | 77.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.77 | 0.270961 | 0.278000 | 0.768925 | 0.722561 | 0.500000 | 0.001406 |
CORE_MID VAV BOX COMPONENT | 1.99 | 0.376182 | 0.371000 | 0.739131 | 1.00 | 0.500000 | 0.001013 |
CORE_TOP VAV BOX COMPONENT | 2.11 | 0.355176 | 0.366000 | 0.772294 | 0.947136 | 0.500000 | 0.001073 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.647683 | 0.243934 | 0.251000 | 0.162568 | 0.650490 | 0.500000 | 0.001562 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.759113 | 0.131761 | 0.200000 | 0.151823 | 0.351364 | 0.500000 | 0.002892 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.942659 | 0.167602 | 0.200000 | 0.188532 | 0.446939 | 0.500000 | 0.002273 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.832772 | 0.120099 | 0.200000 | 0.166554 | 0.320264 | 0.500000 | 0.003172 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.502324 | 0.314521 | 0.322000 | 0.161748 | 0.838724 | 0.500000 | 0.001211 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.617249 | 0.162045 | 0.200000 | 0.123450 | 0.432119 | 0.500000 | 0.002351 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.745653 | 0.211884 | 0.217000 | 0.161807 | 0.565023 | 0.500000 | 0.001798 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.647034 | 0.154575 | 0.200000 | 0.129407 | 0.412200 | 0.500000 | 0.002465 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.560132 | 0.282061 | 0.278000 | 0.155717 | 0.752164 | 0.500000 | 0.001351 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.738217 | 0.135491 | 0.200000 | 0.147643 | 0.361309 | 0.500000 | 0.002812 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.848784 | 0.186139 | 0.200000 | 0.169757 | 0.496370 | 0.500000 | 0.002047 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.762053 | 0.131245 | 0.200000 | 0.152411 | 0.349985 | 0.500000 | 0.002903 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25036.35 |
CORE_MID VAV BOX REHEAT COIL | 24066.25 |
CORE_TOP VAV BOX REHEAT COIL | 40897.16 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18840.46 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12215.34 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18825.92 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12321.56 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14326.19 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9367.55 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14326.17 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9456.90 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 14500.68 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9450.48 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 14483.21 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9541.62 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.64 | 1.35 | 5.28 | 1.88 | 4.68 | 4.68 | 0.300000 | 0.402223 | 4.68 |
PACU_VAV_MID | 2.45 | 1.36 | 4.90 | 2.19 | 4.12 | 4.12 | 0.300000 | 0.530839 | 4.12 |
PACU_VAV_TOP | 2.65 | 1.44 | 5.29 | 3.17 | 4.79 | 4.79 | 0.300000 | 0.660761 | 4.79 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.68 |
PACU_VAV_MID_OA_CONTROLLER | 4.12 |
PACU_VAV_TOP_OA_CONTROLLER | 4.79 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.68 | 98149.37 | 0.758259 | 1.56 | 32713.19 | 0.758259 |
PACU_VAV_MID COOLING COIL | 4.12 | 89324.62 | 0.745897 | 1.37 | 29771.90 | 0.745897 |
PACU_VAV_TOP COOLING COIL | 4.79 | 100140.87 | 0.759239 | 1.60 | 33376.95 | 0.759239 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 39474.25 |
PACU_VAV_MID HEATING COIL | 40727.19 |
PACU_VAV_TOP HEATING COIL | 39797.62 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.68 |
PACU_VAV_MID FAN | 4.12 |
PACU_VAV_TOP FAN | 4.79 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 30.766 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8662 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.8508 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9205 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9413 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6010 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29361301E-12 | 0.14012854E-14 | -0.85605344E-13 | 0.14800367E-15 |
43 | 6 | 0.27604353E-07 | 0.24091625E-09 | 0.63325015E-08 | -0.12947724E-12 |
44 | 5 | -0.18467641E-03 | 0.20758097E-05 | -0.95060042E-04 | 0.62631763E-08 |
45 | 4 | 0.28577214 | 0.10163362E-02 | 0.97391765E-01 | -0.32673590E-04 |
46 | 3 | -7.1400386 | 0.31651635E-01 | -2.3014419 | 0.28390242E-01 |
47 | 2 | 40.454589 | 0.11303679 | 15.111294 | -0.32870127 |
48 | 1 | -80.226531 | 0.51206543E-01 | -29.003760 | 1.0718159 |
49 | 0 | 46.824341 | 0.10340301E-02 | 16.294559 | |
50 | 7 | -0.29611882E-12 | 0.13865371E-14 | -0.86632775E-13 | 0.14828224E-15 |
51 | 6 | 0.27787793E-07 | 0.23712375E-09 | 0.63729895E-08 | -0.13045931E-12 |
52 | 5 | -0.18561242E-03 | 0.20406469E-05 | -0.95529752E-04 | 0.63026795E-08 |
53 | 4 | 0.28687424 | 0.99804250E-03 | 0.97787795E-01 | -0.32828381E-04 |
54 | 3 | -7.1618810 | 0.31052249E-01 | -2.3079221 | 0.28497237E-01 |
55 | 2 | 40.526644 | 0.11080299 | 15.137914 | -0.32950368 |
56 | 1 | -80.281767 | 0.50157931E-01 | -29.027638 | 1.0729929 |
57 | 0 | 46.824340 | 0.10121278E-02 | 16.293979 | |
58 | 7 | -0.28014218E-12 | 0.13884632E-14 | -0.87393674E-13 | 0.18804395E-15 |
59 | 6 | 0.23616586E-07 | 0.31618784E-09 | 0.54522364E-08 | -0.10828607E-12 |
60 | 5 | -0.16407885E-03 | 0.28046874E-05 | -0.84685207E-04 | 0.54024401E-08 |
61 | 4 | 0.26115148 | 0.14088028E-02 | 0.88562665E-01 | -0.29253652E-04 |
62 | 3 | -6.6512012 | 0.44876491E-01 | -2.1564742 | 0.25998182E-01 |
63 | 2 | 38.840966 | 0.16346293 | 14.513591 | -0.31073734 |
64 | 1 | -78.988481 | 0.75323239E-01 | -28.467021 | 1.0454353 |
65 | 0 | 46.824349 | 0.15467291E-02 | 16.308047 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3628_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.3628_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.215E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.231E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.215E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.231E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.278E-004 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.278E-004 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.480E-005 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0218E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0276E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1321E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1370E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8734E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9132E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6395E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6611E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1448 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8205E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1654 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.8925E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1020 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3739E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2271E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5852E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0220E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0288E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1323E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1383E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8751E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9219E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6393E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6609E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6385E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8828E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3759E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6483E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4773E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2595E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9184E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3003E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8423E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8656E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6031E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6199E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2277E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.2336E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2478E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2552E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8896E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9409E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2519E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2934E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8254E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8565E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6393E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6609E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.7074E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1830E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8685E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6668E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7493E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1641E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2271E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5852E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8893E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9412E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2511E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2919E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8238E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8503E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6395E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6611E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5275E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3403E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9829E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9653E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5804E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8359E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9184E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3003E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1573E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2221E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7391E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8103E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7008E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7275E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2479E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2553E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1430 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.3457E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1606 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1058 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1079 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4558E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7521E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.2047E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.3811E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7385E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.1391E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.5161E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2850E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1552E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8008E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2370E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.1928E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8098E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3033E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2075E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1825E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6626E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7521E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2047E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.3124E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2226E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.7995E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8668E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.4201E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7511E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8008E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2371E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1430 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.3449E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1606 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1058 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1079 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4552E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7517E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.2044E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3811E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7383E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.1391E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.5158E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.2847E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1549E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8004E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2368E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.1931E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8097E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3034E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2074E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1823E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6624E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7517E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2044E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.3125E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2224E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.7996E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8667E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.4199E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7508E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8005E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2369E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37426.61154 | 37426.61154 | 2.76592 | 2.76592 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8437.90620 | 8437.90620 | 0.36430 | 0.42469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 26993.82978 | 26993.82978 | 1.99227 | 1.99227 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 16453.75696 | 16453.75696 | 0.71506 | 0.71506 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28312.84303 | 28312.84303 | 2.11009 | 2.11009 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 30.11400 | 1.33666E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 28788.16230 | 28788.16230 | 1.25605 | 1.25605 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8690.26974 | 8690.26974 | 0.64768 | 0.64768 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 13227.60750 | 13227.60750 | 0.57864 | 0.57864 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10185.45818 | 10185.45818 | 0.75911 | 0.75911 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 8575.77238 | 8575.77238 | 0.37516 | 0.37516 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12648.16948 | 12648.16948 | 0.94266 | 0.94266 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 13217.42395 | 13217.42395 | 0.57819 | 0.57819 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11173.80963 | 11173.80963 | 0.83277 | 0.83277 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 8650.16757 | 8650.16757 | 0.37842 | 0.37842 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6740.01583 | 6740.01583 | 0.50232 | 0.50232 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 10064.53551 | 10064.53551 | 0.43999 | 0.43999 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8282.10640 | 8282.10640 | 0.61725 | 0.61725 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.23900 | 1.33598E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6580.34455 | 6580.34455 | 0.28770 | 0.28770 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10004.97593 | 10004.97593 | 0.74565 | 0.74565 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 10064.52453 | 10064.52453 | 0.43999 | 0.43999 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8681.77176 | 8681.77176 | 0.64703 | 0.64703 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 28.22300 | 1.33633E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6642.91407 | 6642.91407 | 0.29044 | 0.29044 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7515.59060 | 7515.59060 | 0.56013 | 0.56013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 10187.49814 | 10187.49814 | 0.44535 | 0.44535 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9905.15384 | 9905.15384 | 0.73822 | 0.73822 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71200 | 1.33588E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6638.91343 | 6638.91343 | 0.29025 | 0.29025 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11388.65468 | 11388.65468 | 0.84878 | 0.84878 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 10175.25691 | 10175.25691 | 0.44481 | 0.44481 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10224.96917 | 10224.96917 | 0.76205 | 0.76205 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6702.74248 | 6702.74248 | 0.29305 | 0.29305 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 70711.19 | 4.68103 | 4.68103 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 40763.86 | 1.88282 | 1.88282 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 63264.39 | 4.12274 | 4.12274 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 40660.97 | 2.18851 | 2.18851 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 71993.34 | 4.79214 | 4.79214 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 40817.59 | 3.16646 | 3.16646 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.76592 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27096 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27800 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76893 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72256 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40611E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25036.34560 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.99227 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37618 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.37100 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73913 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01281E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24066.24880 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11009 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35518 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77229 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94714 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07271E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 40897.16497 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64768 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24393 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16257 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65049 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.56190E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18840.46160 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75911 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13176 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15182 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35136 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.89159E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12215.34132 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94266 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16760 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18853 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44694 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27324E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18825.92374 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83277 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12010 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16655 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32026 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17238E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12321.55831 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50232 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31452 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32200 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16175 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83872 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21136E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14326.18932 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61725 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16204 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12345 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43212 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35120E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9367.55472 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74565 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21188 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21700 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16181 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56502 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79816E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14326.17365 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64703 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15457 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12941 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41220 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.46482E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9456.89772 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56013 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28206 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27800 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15572 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75216 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35077E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14500.68406 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73822 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13549 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14764 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36131 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81199E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9450.48439 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84878 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18614 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16976 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49637 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.04686E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14483.20707 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76205 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13124 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15241 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34999 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90298E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9541.62282 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.63909 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34534 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.27818 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.88282 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.68103 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.68103 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.40222 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.45073 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36466 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.90145 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.18851 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.12274 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.12274 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.53084 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.64616 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44177 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.29232 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.16646 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.79214 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.79214 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.66076 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.68103 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.12274 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.79214 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.68103 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.68103 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 98149.37491 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75826 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.56019 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32713.18666 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75826 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 39474.24636 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.68103 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.12274 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.12274 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 89324.61809 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74590 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.37411 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 29771.89521 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74590 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 40727.18919 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.12274 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.79214 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.79214 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 100140.86640 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.75924 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.59722 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 33376.95077 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.75924 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 39797.61714 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.79214 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 97425.68 | 332430.22 | 12.32 | 3.16 | 3.53 | 3.71 | 3.90 | 10.79 | 12.03 | 12.66 | 13.30 | 5.2782 | 4.2128 | 2.8369 | 1.1557 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 88772.25 | 302903.49 | 12.39 | 3.18 | 3.55 | 3.74 | 3.91 | 10.84 | 12.11 | 12.75 | 13.35 | 4.6487 | 3.7041 | 2.4935 | 1.0288 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 99390.02 | 339132.81 | 12.31 | 3.16 | 3.52 | 3.71 | 3.90 | 10.78 | 12.03 | 12.65 | 13.29 | 5.4034 | 4.3110 | 2.9025 | 1.1825 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.2496920074E-002 | 2.8718535121E-002 | Pass | Pass | 0.5098043470 | 0.4932224846 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1367260566 | 9.1045103020E-002 | Pass | Pass | 0.4935038211 | 0.4706119546 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.1399350318E-002 | 3.4645929288E-002 | Pass | Pass | 0.4677333006 | 0.4596517432 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.2988797486E-002 | 3.7241742546E-002 | Pass | Pass | 0.4940221095 | 0.4544661915 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.0122362648E-002 | 8.1522300855E-003 | Pass | Pass | 0.5166083701 | 0.5488590993 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 7.7534117381E-002 | 7.9475426344E-002 | Pass | Pass | 26.9409626023 | 51.5924103360 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3513037185 | 0.3493425116 | Pass | Pass | 42.6768069441 | 219.7544430400 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3800326281 | 0.3654877671 | Pass | Pass | 37.9038163472 | 81.4078072206 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3509434009 | 0.3461571545 | Pass | Pass | 38.0101217072 | 79.1888323358 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3819211210 | 0.3697358465 | Pass | Pass | 36.2972487066 | 78.8361935907 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2547626738 | 0.2352235293 | Pass | Pass | 20.5315407336 | 44.0972178274 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2625961969 | 0.2439008019 | Pass | Pass | 18.0386117671 | 38.7500054272 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2258138538 | 0.2192631604 | Pass | Pass | 31.4617668724 | 157.7819404495 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2638319478 | 0.2463225852 | Pass | Pass | 17.2992922073 | 37.0019384625 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2668834059 | 0.2447782200 | Pass | Pass | 25.2572221553 | 59.1472256391 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2716362344 | 0.2515592668 | Pass | Pass | 19.0357105661 | 45.1448722013 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2390459084 | 0.2308888338 | Pass | Pass | 23.9651620070 | 54.4634503283 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2732482319 | 0.2543313214 | Pass | Pass | 18.5170711889 | 44.3261937310 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3564.50 | 115.70 | 0.00 | 1645.05 | 697.43 | 6022.70 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3628_SHGC_EAST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3628_SHGC_EAST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3628_SHGC_WEST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3628_SHGC_WEST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.061 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 177.99 | 2.061 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.061 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.92 | 0.0000 | Y | 5.99 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.71 | 0.0000 | Y | 3.76 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.50 | 0.0000 | Y | 5.89 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.70 | 0.0000 | Y | 3.76 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.84 | 0.0000 | Y | 5.97 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.66 | 0.0000 | Y | 3.75 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.46 | 0.0000 | Y | 5.88 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.64 | 0.0000 | Y | 3.75 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.92 | 0.0000 | Y | 5.99 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.71 | 0.0000 | Y | 3.76 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.50 | 0.0000 | Y | 5.89 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.70 | 0.0000 | Y | 3.76 |
Interior Lighting Total | 5.9322 | 4982.19 | 29555.08 | 203.12 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.04 | 42.04 | 3.35 | |
EXTERIOR_LIGHTS_B | 408.47 | AstronomicalClock | - | 83.67 | 62.85 | 4.82 | |
EXTERIOR_LIGHTS_C | 4724.13 | AstronomicalClock | - | 83.67 | 47.45 | 42.08 | |
Exterior Lighting Total | 5557.43 | 50.25 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 98149.37 | 74422.65 | 23726.72 | 0.76 | 3.74 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 89324.62 | 66626.97 | 22697.65 | 0.75 | 3.74 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 100140.87 | 76030.88 | 24109.98 | 0.76 | 3.74 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 97425.7 | 3.16 | 10.79 | N/A | N/A | 12.32 | |
PACU_VAV_MID COOLING COIL | 88772.3 | 3.18 | 10.84 | N/A | N/A | 12.39 | |
PACU_VAV_TOP COOLING COIL | 99390.0 | 3.16 | 10.78 | N/A | N/A | 12.31 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25036.35 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24066.25 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 40897.16 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18840.46 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12215.34 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18825.92 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12321.56 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14326.19 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9367.55 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14326.17 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9456.90 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14500.68 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9450.48 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14483.21 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9541.62 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 39474.25 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 40727.19 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 39797.62 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.68 | 10829.03 | 2313.39 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.12 | 9537.50 | 2313.39 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.79 | 11014.55 | 2298.46 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 97425.68 | 3.16 | 10.79 | 12.32 | 5.2782 | 3.53 | 12.03 | 4.2128 | 3.71 | 12.66 | 2.8369 | 3.90 | 13.30 | 1.1557 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 88772.25 | 3.18 | 10.84 | 12.39 | 4.6487 | 3.55 | 12.11 | 3.7041 | 3.74 | 12.75 | 2.4935 | 3.91 | 13.35 | 1.0288 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 99390.02 | 3.16 | 10.78 | 12.31 | 5.4034 | 3.52 | 12.03 | 4.3110 | 3.71 | 12.65 | 2.9025 | 3.90 | 13.29 | 1.1825 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37426.61 | 37426.61 | 38.05 | 2.766 | 2.766 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_MID | 26993.83 | 26993.83 | 27.45 | 1.992 | 1.992 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 23.42 | 0.01335 | 0.425 | 0.00 |
CORE_TOP | 28312.84 | 28312.84 | 28.79 | 2.110 | 2.110 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00892 | 30.11 | 0.01337 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8690.27 | 8690.27 | 41.91 | 0.648 | 0.648 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00890 | 30.21 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10185.46 | 10185.46 | 77.60 | 0.759 | 0.759 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00872 | 25.98 | 0.01336 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12648.17 | 12648.17 | 61.00 | 0.943 | 0.943 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00878 | 30.14 | 0.01337 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11173.81 | 11173.81 | 85.13 | 0.833 | 0.833 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00870 | 28.84 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6740.02 | 6740.02 | 32.51 | 0.502 | 0.502 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00895 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8282.11 | 8282.11 | 63.10 | 0.617 | 0.617 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00874 | 26.24 | 0.01336 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10004.98 | 10004.98 | 48.25 | 0.746 | 0.746 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00881 | 30.22 | 0.01337 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8681.77 | 8681.77 | 66.15 | 0.647 | 0.647 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 24.00 | 24.00 | 0.00873 | 28.22 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7515.59 | 7515.59 | 36.25 | 0.560 | 0.560 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00894 | 30.30 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9905.15 | 9905.15 | 75.46 | 0.738 | 0.738 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00872 | 25.71 | 0.01336 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11388.65 | 11388.65 | 54.93 | 0.849 | 0.849 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00880 | 30.07 | 0.01337 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10224.97 | 10224.97 | 77.90 | 0.762 | 0.762 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00871 | 28.84 | 0.01336 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8437.91 | 8437.91 | 8.58 | 0.364 | 0.425 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_MID | 16453.76 | 16453.76 | 16.73 | 0.715 | 0.715 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
CORE_TOP | 28788.16 | 28788.16 | 29.27 | 1.256 | 1.256 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 13227.61 | 13227.61 | 63.80 | 0.579 | 0.579 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8575.77 | 8575.77 | 65.33 | 0.375 | 0.375 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 13217.42 | 13217.42 | 63.75 | 0.578 | 0.578 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 8650.17 | 8650.17 | 65.90 | 0.378 | 0.378 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 10064.54 | 10064.54 | 48.54 | 0.440 | 0.440 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6580.34 | 6580.34 | 50.13 | 0.288 | 0.288 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10064.52 | 10064.52 | 48.54 | 0.440 | 0.440 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6642.91 | 6642.91 | 50.61 | 0.290 | 0.290 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 10187.50 | 10187.50 | 49.13 | 0.445 | 0.445 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6638.91 | 6638.91 | 50.58 | 0.290 | 0.290 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -16.30 | 0.00092 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 10175.26 | 10175.26 | 49.08 | 0.445 | 0.445 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -16.30 | 0.00092 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6702.74 | 6702.74 | 51.07 | 0.293 | 0.293 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | -16.30 | 0.00092 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.68 | 4.68 | 1.88 | 1.88 | 4.6810 | 1.8828 | 4.6810 | 0.4022 | 0.3000 |
PACU_VAV_MID | 4.12 | 4.12 | 2.19 | 2.19 | 4.1227 | 2.1885 | 4.1227 | 0.5308 | 0.3000 |
PACU_VAV_TOP | 4.79 | 4.79 | 3.17 | 3.17 | 4.7921 | 3.1665 | 4.7921 | 0.6608 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25036.346 | 25036.346 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25036.35 | 13828.02 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 8437.91 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24066.249 | 24066.249 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24066.25 | 23282.34 | 0.715056 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 16453.76 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 40897.165 | 40897.165 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40897.16 | 40897.16 | 1.256049 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 28788.16 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 18840.462 | 18840.462 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18840.46 | 18840.46 | 0.578635 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00778479 | 49.0824 | 13227.61 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12215.341 | 12215.341 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12215.34 | 12215.34 | 0.375162 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00777918 | 49.0476 | 8575.77 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 18825.924 | 18825.924 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18825.92 | 18825.92 | 0.578189 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00778462 | 49.0813 | 13217.42 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12321.558 | 12321.558 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12321.56 | 12321.56 | 0.378424 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00778112 | 49.0596 | 8650.17 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 14326.189 | 14326.189 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14326.19 | 14326.19 | 0.439991 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00783281 | 49.3802 | 10064.54 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9367.555 | 9367.555 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9367.55 | 9367.55 | 0.287700 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00783259 | 49.3789 | 6580.34 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 14326.174 | 14326.174 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14326.17 | 14326.17 | 0.439991 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00783281 | 49.3802 | 10064.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9456.898 | 9456.898 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9456.90 | 9456.90 | 0.290444 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00783502 | 49.3940 | 6642.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 14500.684 | 14500.684 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14500.68 | 14500.68 | 0.445350 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00775591 | 48.9023 | 10187.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 9450.484 | 9450.484 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9450.48 | 9450.48 | 0.290247 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00775278 | 48.8829 | 6638.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 14483.207 | 14483.207 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14483.21 | 14483.21 | 0.444814 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00775553 | 48.9000 | 10175.26 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 9541.623 | 9541.623 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9541.62 | 9541.62 | 0.293046 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00775579 | 48.9016 | 6702.74 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 98149.375 | 74422.652 | 4.681029 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 100538.28 | 79736.22 | 4.681029 | 25.61 | 17.92 | 0.01000380 | 10.87 | 10.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 25.5322 | 24.00 | 0.00885044 | 46.4240 | 62798.30 | 0.00 | 101205.18 | 74662.16 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 39474.246 | 39474.246 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39474.25 | 39474.25 | 1.404309 | -11.03 | -11.03 | 0.00193565 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 85.1073 | 19.60 | 0.00758007 | 52.1231 | 21198.74 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 89324.618 | 66626.966 | 4.122744 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 91950.93 | 71171.88 | 4.122744 | 25.83 | 18.15 | 0.01020838 | 10.88 | 10.88 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 28.9897 | 24.00 | 0.00891616 | 46.7642 | 55234.40 | 0.00 | 92105.67 | 66886.17 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 40727.189 | 40727.189 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 40727.19 | 40727.19 | 1.236823 | -15.11 | -15.11 | 0.00115054 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 96.6322 | 19.60 | 0.00753586 | 51.8254 | 24667.36 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 100140.866 | 76030.884 | 4.792139 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 102537.76 | 81401.24 | 4.792139 | 25.58 | 17.90 | 0.00999335 | 10.89 | 10.89 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 24.9402 | 24.00 | 0.00886776 | 46.5139 | 64100.44 | 0.00 | 103258.68 | 76256.30 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 39797.617 | 39797.617 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 39797.62 | 39797.62 | 1.437642 | -10.67 | -10.67 | 0.00205706 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 83.1341 | 17.67 | 0.00757277 | 58.7765 | 28977.74 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25036.346 | 25036.346 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25036.35 | 13828.02 | 1.0000 | 0.49855562 | 0.424691 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25036.35 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.90 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 8437.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24066.249 | 24066.249 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24066.25 | 23282.34 | 1.0000 | 0.83942208 | 0.715056 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24066.25 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 16453.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 40897.165 | 40897.165 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40897.16 | 40897.16 | 1.0000 | 1.47450734 | 1.256049 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40897.16 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 28788.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18840.462 | 18840.462 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18840.46 | 18840.46 | 1.0000 | 0.67927444 | 0.578635 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18840.46 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00778479 | 21.00 | 0.00778479 | 49.0824 | 13227.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12215.341 | 12215.341 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12215.34 | 12215.34 | 1.0000 | 0.44041220 | 0.375162 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12215.34 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00777918 | 21.00 | 0.00777918 | 49.0476 | 8575.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18825.924 | 18825.924 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18825.92 | 18825.92 | 1.0000 | 0.67875029 | 0.578189 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18825.92 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00778462 | 21.00 | 0.00778462 | 49.0813 | 13217.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12321.558 | 12321.558 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12321.56 | 12321.56 | 1.0000 | 0.44424175 | 0.378424 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12321.56 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00778112 | 21.00 | 0.00778112 | 49.0596 | 8650.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14326.189 | 14326.189 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14326.19 | 14326.19 | 1.0000 | 0.51651677 | 0.439991 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14326.19 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783281 | 21.00 | 0.00783281 | 49.3802 | 10064.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9367.555 | 9367.555 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9367.55 | 9367.55 | 1.0000 | 0.33773804 | 0.287700 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9367.55 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783259 | 21.00 | 0.00783259 | 49.3789 | 6580.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14326.174 | 14326.174 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14326.17 | 14326.17 | 1.0000 | 0.51651620 | 0.439991 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14326.17 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783281 | 21.00 | 0.00783281 | 49.3802 | 10064.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9456.898 | 9456.898 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9456.90 | 9456.90 | 1.0000 | 0.34095921 | 0.290444 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9456.90 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00783502 | 21.00 | 0.00783502 | 49.3940 | 6642.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14500.684 | 14500.684 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14500.68 | 14500.68 | 1.0000 | 0.52280800 | 0.445350 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14500.68 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775591 | 21.00 | 0.00775591 | 48.9023 | 10187.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9450.484 | 9450.484 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9450.48 | 9450.48 | 1.0000 | 0.34072799 | 0.290247 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9450.48 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775278 | 21.00 | 0.00775278 | 48.8829 | 6638.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14483.207 | 14483.207 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14483.21 | 14483.21 | 1.0000 | 0.52217789 | 0.444814 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14483.21 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775553 | 21.00 | 0.00775553 | 48.9000 | 10175.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9541.623 | 9541.623 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9541.62 | 9541.62 | 1.0000 | 0.34401389 | 0.293046 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9541.62 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775579 | 21.00 | 0.00775579 | 48.9016 | 6702.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 98149.375 | 74422.652 | 4.681029 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4366 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.681029 | 5.49517890 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 100538.28 | 79736.22 | 1.0243 | 5.49517890 | 4.681029 | 25.61 | 17.92 | 0.01000380 | 51226.9 | 10.87 | 10.87 | 0.00850000 | 32356.9 | -999.0 | -999.00 | -999.00 | -999.00 | 10829.031 | 89709.25 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 25.5322 | 24.00 | 0.00885044 | 24.00 | 0.00885044 | 46.4240 | 62798.30 | 0.00 | 101205.18 | 74662.16 | 5.27816087 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.83 | 12.81 | 0.00921297 | 36148.1 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39474.246 | 39474.246 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.681029 | 5.49517890 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39474.25 | 39474.25 | 1.0000 | 1.64855367 | 1.404309 | -11.03 | -11.03 | 0.00193565 | -6281.1 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39474.25 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 85.1073 | 19.09 | 0.00771644 | 19.60 | 0.00758007 | 52.1231 | 21198.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 89324.618 | 66626.966 | 4.122744 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8169 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.122744 | 4.83979336 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 91950.93 | 71171.88 | 1.0294 | 4.83979336 | 4.122744 | 25.83 | 18.15 | 0.01020838 | 51973.8 | 10.88 | 10.88 | 0.00850000 | 32357.7 | -999.0 | -999.00 | -999.00 | -999.00 | 9537.500 | 82413.43 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 28.9897 | 24.00 | 0.00891616 | 24.00 | 0.00891616 | 46.7642 | 55234.40 | 0.00 | 92105.67 | 66886.17 | 4.64865810 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.58 | 12.56 | 0.00905759 | 35509.0 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 40727.189 | 40727.189 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.122744 | 4.83979336 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 40727.19 | 40727.19 | 1.0000 | 1.45193801 | 1.236823 | -15.11 | -15.11 | 0.00115054 | -12342.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40727.19 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 96.6322 | 18.90 | 0.00764799 | 19.60 | 0.00753586 | 51.8254 | 24667.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 100140.866 | 76030.884 | 4.792139 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4171 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.792139 | 5.62561341 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 102537.76 | 81401.24 | 1.0239 | 5.62561341 | 4.792139 | 25.58 | 17.90 | 0.00999335 | 51166.7 | 10.89 | 10.89 | 0.00850000 | 32369.6 | -999.0 | -999.00 | -999.00 | -999.00 | 11014.547 | 91523.21 | 30.30 | 0.01336696 | 21.83 | 1.19517000 | 24.9402 | 24.00 | 0.00886776 | 24.00 | 0.00886776 | 46.5139 | 64100.44 | 0.00 | 103258.68 | 76256.30 | 5.40344420 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.86 | 12.84 | 0.00922535 | 36212.6 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39797.617 | 39797.617 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.792139 | 5.62561341 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 39797.62 | 39797.62 | 1.0000 | 1.68768402 | 1.437642 | -10.67 | -10.67 | 0.00205706 | -5615.0 | 12.80 | 11.37 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39797.62 | -16.30 | 0.00092409 | -16.30 | 1.19517000 | 83.1341 | 17.10 | 0.00764157 | 17.67 | 0.00757277 | 58.7765 | 28977.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.68 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.12 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1941.00 | 3103.00 | 152.17 |
CORE_MID | 2487.17 | 3751.33 | 1127.17 |
CORE_TOP | 3019.00 | 4044.00 | 1784.50 |
PERIMETER_TOP_ZN_3 | 3646.33 | 4238.33 | 2456.83 |
PERIMETER_TOP_ZN_2 | 3809.17 | 4003.50 | 2344.67 |
PERIMETER_TOP_ZN_1 | 3505.67 | 3950.67 | 2069.67 |
PERIMETER_TOP_ZN_4 | 3716.67 | 4233.50 | 2392.67 |
PERIMETER_BOT_ZN_3 | 3273.33 | 4312.67 | 2161.50 |
PERIMETER_BOT_ZN_2 | 3531.83 | 3867.17 | 1982.83 |
PERIMETER_BOT_ZN_1 | 3410.33 | 4294.17 | 2171.67 |
PERIMETER_BOT_ZN_4 | 3458.17 | 3981.33 | 2005.17 |
PERIMETER_MID_ZN_3 | 3373.50 | 4021.83 | 2075.83 |
PERIMETER_MID_ZN_2 | 3028.33 | 3342.17 | 1780.67 |
PERIMETER_MID_ZN_1 | 3223.33 | 3650.50 | 1636.67 |
PERIMETER_MID_ZN_4 | 3496.67 | 3991.83 | 2021.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4829.50 | 4856.33 | 2861.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.50 | 0.33 | 0.50 | 0.00 |
CORE_MID | 2.83 | 0.00 | 2.50 | 0.00 |
CORE_TOP | 9.00 | 0.17 | 5.83 | 0.17 |
PERIMETER_TOP_ZN_3 | 113.17 | 2.00 | 58.50 | 1.67 |
PERIMETER_TOP_ZN_2 | 61.00 | 13.67 | 7.67 | 13.50 |
PERIMETER_TOP_ZN_1 | 52.50 | 18.00 | 8.83 | 17.50 |
PERIMETER_TOP_ZN_4 | 62.83 | 23.67 | 10.33 | 13.83 |
PERIMETER_BOT_ZN_3 | 35.50 | 0.00 | 29.50 | 0.00 |
PERIMETER_BOT_ZN_2 | 6.00 | 3.50 | 0.17 | 3.50 |
PERIMETER_BOT_ZN_1 | 540.17 | 10.00 | 536.67 | 10.00 |
PERIMETER_BOT_ZN_4 | 6.17 | 13.17 | 0.17 | 6.67 |
PERIMETER_MID_ZN_3 | 34.17 | 0.00 | 21.33 | 0.00 |
PERIMETER_MID_ZN_2 | 14.50 | 11.33 | 0.50 | 11.33 |
PERIMETER_MID_ZN_1 | 8.83 | 13.67 | 1.00 | 13.67 |
PERIMETER_MID_ZN_4 | 14.00 | 20.50 | 0.50 | 11.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 620.83 | 82.50 | 552.33 | 64.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.70 | 52.94 | 2698.04 | 0.894 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.70 | 52.94 | 2698.04 | 0.659 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.70 | 52.94 | 2698.04 | 0.668 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.57 | 11.16 | 568.77 | 0.760 | 0.046 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 1.208 | 0.048 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.57 | 11.16 | 568.77 | 1.053 | 0.046 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 1.230 | 0.048 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.57 | 11.16 | 568.77 | 0.659 | 0.024 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.980 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.57 | 11.16 | 568.77 | 0.846 | 1.313 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.956 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.57 | 11.16 | 568.77 | 0.733 | 0.038 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 1.083 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.57 | 11.16 | 568.77 | 1.000 | 0.038 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 1.151 | 0.040 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.70 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.57 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.70 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.54 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.57 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.56 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14252145.87 | 0.00 | 14252145.87 | 0.00 | 14252145.87 | 13393058.27 | 5590.55 | 386.31 | 2783.14 | 131.57 |
CORE_MID | 10518502.60 | 0.00 | 10518502.60 | 0.00 | 10518502.60 | 13393058.27 | 6460.47 | 31.60 | 2267.93 | 136.81 |
CORE_TOP | 10672130.69 | 0.00 | 10672130.69 | 0.00 | 10672130.69 | 13393058.27 | 6377.37 | 22.23 | 2360.39 | 95.28 |
PERIMETER_TOP_ZN_3 | 2554689.78 | 0.00 | 2554689.78 | 300174.51 | 2854864.28 | 2823374.22 | 5790.30 | 40.31 | 2929.40 | 95.28 |
PERIMETER_TOP_ZN_2 | 2567554.26 | 0.00 | 2567554.26 | 200115.14 | 2767669.39 | 1787429.43 | 4077.03 | 2.48 | 4680.50 | 95.28 |
PERIMETER_TOP_ZN_1 | 3529015.58 | 0.00 | 3529015.58 | 300174.51 | 3829190.09 | 2823374.22 | 4101.02 | 4.00 | 4654.98 | 95.28 |
PERIMETER_TOP_ZN_4 | 2628472.01 | 0.00 | 2628472.01 | 200115.14 | 2828587.15 | 1787312.18 | 4075.39 | 1.35 | 4683.26 | 95.28 |
PERIMETER_BOT_ZN_3 | 2231481.44 | 0.00 | 2231481.44 | 159600.83 | 2391082.27 | 2823374.22 | 5955.16 | 253.25 | 2551.59 | 131.57 |
PERIMETER_BOT_ZN_2 | 2090568.16 | 0.00 | 2090568.16 | 106399.91 | 2196968.08 | 1787429.43 | 4135.59 | 26.22 | 4598.20 | 131.57 |
PERIMETER_BOT_ZN_1 | 2862519.98 | 0.00 | 2862519.98 | 4489791.06 | 7352311.04 | 2823374.22 | 4932.05 | 257.85 | 3570.10 | 131.57 |
PERIMETER_BOT_ZN_4 | 2046743.29 | 0.00 | 2046743.29 | 106399.91 | 2153143.21 | 1787312.18 | 4159.14 | 13.75 | 4587.11 | 131.57 |
PERIMETER_MID_ZN_3 | 2462889.43 | 0.00 | 2462889.43 | 249871.94 | 2712761.37 | 2823374.22 | 6005.04 | 40.48 | 2714.48 | 136.81 |
PERIMETER_MID_ZN_2 | 2495851.17 | 0.00 | 2495851.17 | 166580.29 | 2662431.46 | 1787429.43 | 4078.56 | 1.92 | 4679.52 | 1045.81 |
PERIMETER_MID_ZN_1 | 3349759.04 | 0.00 | 3349759.04 | 249871.94 | 3599630.99 | 2823374.22 | 4120.73 | 10.99 | 4628.28 | 136.81 |
PERIMETER_MID_ZN_4 | 2454120.57 | 0.00 | 2454120.57 | 166580.29 | 2620700.86 | 1787312.18 | 4078.76 | 2.22 | 4679.03 | 136.81 |
Total Facility | 66716443.86 | 0.00 | 66716443.86 | 6695675.48 | 73412119.35 | 67843644.98 | 6610.08 | 560.33 | 4797.84 | 1156.57 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6557 | 0.0000 | 0.6557 | 0.0000 | 0.6557 | 0.4247 | 2844.06 | 386.31 | 2712.63 |
CORE_MID | 0.4849 | 0.0000 | 0.4849 | 0.0000 | 0.4849 | 0.4247 | 3689.41 | 31.60 | 2221.99 |
CORE_TOP | 0.4916 | 0.0000 | 0.4916 | 0.0000 | 0.4916 | 0.4247 | 3613.79 | 22.23 | 2306.98 |
PERIMETER_TOP_ZN_3 | 0.1179 | 0.0000 | 0.1179 | 0.0071 | 0.1250 | 0.0895 | 3026.71 | 40.31 | 2875.98 |
PERIMETER_TOP_ZN_2 | 0.1186 | 0.0000 | 0.1186 | 0.0047 | 0.1233 | 0.0567 | 1313.44 | 2.48 | 4627.08 |
PERIMETER_TOP_ZN_1 | 0.1632 | 0.0000 | 0.1632 | 0.0071 | 0.1703 | 0.0895 | 1337.44 | 4.00 | 4601.56 |
PERIMETER_TOP_ZN_4 | 0.1208 | 0.0000 | 0.1208 | 0.0047 | 0.1256 | 0.0567 | 1311.80 | 1.35 | 4629.84 |
PERIMETER_BOT_ZN_3 | 0.1023 | 0.0000 | 0.1023 | 0.0038 | 0.1061 | 0.0895 | 3208.62 | 253.25 | 2481.13 |
PERIMETER_BOT_ZN_2 | 0.0962 | 0.0000 | 0.0962 | 0.0025 | 0.0987 | 0.0567 | 1389.55 | 26.22 | 4527.23 |
PERIMETER_BOT_ZN_1 | 0.1318 | 0.0000 | 0.1318 | 0.2062 | 0.3379 | 0.0895 | 2185.51 | 257.85 | 3499.64 |
PERIMETER_BOT_ZN_4 | 0.0939 | 0.0000 | 0.0939 | 0.0025 | 0.0964 | 0.0567 | 1413.10 | 13.75 | 4516.15 |
PERIMETER_MID_ZN_3 | 0.1137 | 0.0000 | 0.1137 | 0.0059 | 0.1196 | 0.0895 | 3233.98 | 40.48 | 2668.54 |
PERIMETER_MID_ZN_2 | 0.1063 | 0.0000 | 0.1063 | 0.0042 | 0.1105 | 0.0567 | 1307.54 | 1.92 | 3724.54 |
PERIMETER_MID_ZN_1 | 0.1550 | 0.0000 | 0.1550 | 0.0059 | 0.1610 | 0.0895 | 1349.68 | 10.99 | 4582.34 |
PERIMETER_MID_ZN_4 | 0.1130 | 0.0000 | 0.1130 | 0.0040 | 0.1170 | 0.0567 | 1307.72 | 2.22 | 4633.07 |
Total Facility | 3.0649 | 0.0000 | 3.0649 | 0.2587 | 3.3237 | 2.1513 | 3814.76 | 560.33 | 4695.21 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 32362539.92 | 0.00 | 32362539.92 | 22614548.33 | 4080.82 | 3.88 | 4675.30 | 131.57 |
PACU_VAV_MID | 29327556.57 | 0.00 | 29327556.57 | 22614548.33 | 4079.62 | 2.12 | 4678.26 | 136.70 |
PACU_VAV_TOP | 30251889.09 | 0.00 | 30251889.09 | 22614548.33 | 4075.05 | 0.76 | 4684.18 | 94.70 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4881 | 0.0000 | 1.4881 | 0.7171 | 1334.78 | 3.88 | 4604.34 |
PACU_VAV_MID | 1.3534 | 0.0000 | 1.3534 | 0.7171 | 1308.56 | 2.12 | 4632.32 |
PACU_VAV_TOP | 1.3947 | 0.0000 | 1.3947 | 0.7171 | 1311.47 | 0.76 | 4630.77 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.39 | 2789.28 | 0.00 | 0.00 | 0.00 | 2073.91 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.10 | 2614.66 | 0.00 | 0.00 | 0.00 | 2285.43 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.17 | 2668.11 | 0.00 | 0.00 | 0.00 | 2214.01 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.5018 | 0.0000 | 0.0000 | 0.0000 | 1.0584 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.2650 | 0.0000 | 0.0000 | 0.0000 | 1.0635 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.3091 | 0.0000 | 0.0000 | 0.0000 | 1.0598 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 825 |
Defaulted Fields | 545 |
Fields with Defaults | 2230 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1429.95 | 12344.18 | 16-APR-17:10 | 234893.06 | 02-JAN-07:10 |
Electricity:Building | 908.55 | 12175.61 | 16-APR-17:10 | 66980.32 | 02-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 284.50 | 4029.56 | 01-JAN-00:10 | 22405.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 908.55 | 12175.61 | 16-APR-17:10 | 66980.32 | 02-NOV-07:10 |
InteriorLights:Electricity | 203.12 | 934.27 | 01-JAN-11:30 | 21377.78 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 203.12 | 934.27 | 01-JAN-11:30 | 21377.78 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 203.12 | 934.27 | 01-JAN-11:30 | 21377.78 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 203.12 | 934.27 | 01-JAN-11:30 | 21377.78 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.32 | 409.68 | 26-MAR-17:10 | 2324.90 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.99 | 23.57 | 01-JAN-11:30 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.99 | 23.57 | 01-JAN-11:30 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.16 | 259.34 | 16-APR-17:10 | 1471.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.76 | 14.92 | 01-JAN-09:30 | 563.23 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.76 | 14.92 | 01-JAN-09:30 | 563.23 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.22 | 409.67 | 12-MAR-17:10 | 2324.89 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.89 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.89 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.16 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.76 | 14.92 | 01-JAN-10:40 | 563.19 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.76 | 14.92 | 01-JAN-10:40 | 563.19 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.30 | 409.68 | 26-MAR-17:10 | 2324.90 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.97 | 23.57 | 01-JAN-11:10 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.97 | 23.57 | 01-JAN-11:10 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.15 | 259.34 | 09-APR-17:10 | 1471.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.75 | 14.92 | 01-JAN-09:20 | 563.23 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.75 | 14.92 | 01-JAN-09:20 | 563.23 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.21 | 409.67 | 12-MAR-17:10 | 2324.89 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.88 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.88 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.15 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.75 | 14.92 | 01-JAN-10:30 | 563.19 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.75 | 14.92 | 01-JAN-10:30 | 563.19 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.32 | 409.68 | 26-MAR-17:10 | 2324.90 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.99 | 23.57 | 01-JAN-11:30 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.99 | 23.57 | 01-JAN-11:30 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.16 | 259.34 | 16-APR-17:10 | 1471.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.76 | 14.92 | 01-JAN-09:30 | 563.23 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.76 | 14.92 | 01-JAN-09:30 | 563.23 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.22 | 409.67 | 12-MAR-17:10 | 2324.89 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.89 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.89 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.16 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.76 | 14.92 | 01-JAN-10:40 | 563.19 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.76 | 14.92 | 01-JAN-10:40 | 563.19 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 471.14 | 168.57 | 14-MAY-17:50 | 201110.07 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 834.98 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 834.98 | 02-NOV-07:20 |
ElectricityPurchased:Facility | 1429.95 | 12344.18 | 16-APR-17:10 | 234893.06 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1429.95 | 12344.18 | 16-APR-17:10 | 234893.06 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1429.95 | 12344.18 | 16-APR-17:10 | 234893.06 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1429.95 | 12344.18 | 16-APR-17:10 | 234893.06 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1429.95 | 12344.18 | 16-APR-17:10 | 234893.06 | 02-JAN-07:10 |
ElectricityNet:Plant | 1429.95 | 12344.18 | 16-APR-17:10 | 234893.06 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1429.95 | 12344.18 | 16-APR-17:10 | 234893.06 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1429.95 | 12344.18 | 16-APR-17:10 | 234893.06 | 02-JAN-07:10 |
Heating:Electricity | 255.17 | 0.00 | 01-JAN-00:40 | 193928.18 | 02-JAN-07:10 |
General:Heating:Electricity | 255.17 | 0.00 | 01-JAN-00:40 | 193928.18 | 02-JAN-07:10 |
Fans:Electricity | 86.29 | 0.00 | 01-JAN-00:40 | 25839.59 | 17-JUL-12:10 |
General:Fans:Electricity | 86.29 | 0.00 | 01-JAN-00:40 | 25839.59 | 17-JUL-12:10 |
ExteriorLights:Electricity | 50.25 | 0.00 | 01-JAN-08:00 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.25 | 0.00 | 01-JAN-08:00 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 118.02 | 0.00 | 01-JAN-00:10 | 66359.60 | 15-AUG-14:30 |
General:Cooling:Electricity | 118.02 | 0.00 | 01-JAN-00:10 | 66359.60 | 15-AUG-14:30 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 5.71 | 0.00 | 01-JAN-00:10 | 600.72 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 355.55 | 1156.00 | 21-JAN-06:10 | 112796.50 | 07-FEB-07:50 |
NaturalGas:HVAC | 243.22 | 0.00 | 01-JAN-00:40 | 108107.29 | 07-FEB-07:20 |
Heating:NaturalGas | 243.22 | 0.00 | 01-JAN-00:40 | 108107.29 | 07-FEB-07:20 |
General:Heating:NaturalGas | 243.22 | 0.00 | 01-JAN-00:40 | 108107.29 | 07-FEB-07:20 |
NaturalGas:Plant | 112.33 | 1156.00 | 02-JAN-17:20 | 10479.93 | 21-FEB-12:30 |
WaterSystems:NaturalGas | 112.33 | 1156.00 | 02-JAN-17:20 | 10479.93 | 21-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 112.33 | 1156.00 | 02-JAN-17:20 | 10479.93 | 21-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2050.37 | 0.00 | 01-JAN-00:40 | 453822.73 | 15-AUG-14:30 |
EnergyTransfer:Building | 1016.98 | 0.00 | 01-JAN-00:40 | 189104.67 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 193.63 | 0.00 | 01-JAN-00:40 | 25353.00 | 17-JUL-08:00 |
Heating:EnergyTransfer | 212.60 | 0.00 | 01-JAN-00:40 | 189104.67 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.37 | 0.00 | 01-JAN-00:10 | 19584.48 | 02-JAN-06:30 |
General:Heating:EnergyTransfer | 212.60 | 0.00 | 01-JAN-00:40 | 189104.67 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.37 | 0.00 | 01-JAN-00:10 | 19584.48 | 02-JAN-06:30 |
Cooling:EnergyTransfer | 804.37 | 0.00 | 01-JAN-00:40 | 149825.36 | 09-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 193.27 | 0.00 | 01-JAN-00:40 | 25353.00 | 17-JUL-08:00 |
General:Cooling:EnergyTransfer | 804.37 | 0.00 | 01-JAN-00:40 | 149825.36 | 09-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 193.27 | 0.00 | 01-JAN-00:40 | 25353.00 | 17-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 51.35 | 0.00 | 01-JAN-00:40 | 14840.59 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.16 | 0.00 | 01-JAN-00:40 | 14840.59 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.16 | 0.00 | 01-JAN-00:40 | 14840.59 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.20 | 0.00 | 01-JAN-00:10 | 9806.40 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.20 | 0.00 | 01-JAN-00:10 | 9806.40 | 21-JUL-13:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.19 | 0.00 | 01-JAN-00:40 | 8938.59 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.88 | 0.00 | 01-JAN-00:40 | 8938.59 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.88 | 0.00 | 01-JAN-00:40 | 8938.59 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.31 | 0.00 | 01-JAN-00:10 | 4757.70 | 17-JUL-07:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.31 | 0.00 | 01-JAN-00:10 | 4757.70 | 17-JUL-07:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 25.06 | 0.00 | 01-JAN-00:40 | 7595.88 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 9.18 | 0.00 | 01-JAN-00:40 | 7595.88 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 9.18 | 0.00 | 01-JAN-00:40 | 7595.88 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.88 | 0.00 | 01-JAN-00:10 | 4931.88 | 17-JUL-07:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.88 | 0.00 | 01-JAN-00:10 | 4931.88 | 17-JUL-07:10 |
EnergyTransfer:Zone:CORE_MID | 127.86 | 0.00 | 01-JAN-00:40 | 20683.15 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 2.58 | 0.00 | 01-JAN-00:20 | 20683.15 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 2.58 | 0.00 | 01-JAN-00:20 | 20683.15 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 125.28 | 0.00 | 01-JAN-00:10 | 17665.58 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 125.28 | 0.00 | 01-JAN-00:10 | 17665.58 | 17-JUL-07:40 |
EnergyTransfer:Zone:CORE_TOP | 127.37 | 0.00 | 01-JAN-00:40 | 26924.36 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 12.36 | 0.00 | 01-JAN-00:40 | 26924.36 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 12.36 | 0.00 | 01-JAN-00:40 | 26924.36 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 115.02 | 0.00 | 01-JAN-00:10 | 19359.92 | 27-JUN-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 115.02 | 0.00 | 01-JAN-00:10 | 19359.92 | 27-JUN-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.56 | 0.00 | 01-JAN-00:40 | 9164.75 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.67 | 0.00 | 01-JAN-00:40 | 9164.75 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.67 | 0.00 | 01-JAN-00:40 | 9164.75 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.89 | 0.00 | 01-JAN-00:10 | 6704.29 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.89 | 0.00 | 01-JAN-00:10 | 6704.29 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 36.36 | 0.00 | 01-JAN-00:40 | 9364.98 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 11.22 | 0.00 | 01-JAN-00:40 | 9364.98 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 11.22 | 0.00 | 01-JAN-00:40 | 9364.98 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.14 | 0.00 | 01-JAN-00:10 | 8207.91 | 17-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.14 | 0.00 | 01-JAN-00:10 | 8207.91 | 17-JUL-07:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 52.32 | 0.00 | 01-JAN-00:40 | 11981.19 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 14.23 | 0.00 | 01-JAN-00:40 | 11981.19 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 14.23 | 0.00 | 01-JAN-00:40 | 11981.19 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.09 | 0.00 | 01-JAN-00:10 | 11714.33 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.09 | 0.00 | 01-JAN-00:10 | 11714.33 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.48 | 0.00 | 01-JAN-00:40 | 9879.52 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 12.22 | 0.00 | 01-JAN-00:40 | 9879.52 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 12.22 | 0.00 | 01-JAN-00:40 | 9879.52 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.26 | 0.00 | 01-JAN-00:10 | 8618.31 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.26 | 0.00 | 01-JAN-00:10 | 8618.31 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 32.56 | 0.00 | 01-JAN-00:40 | 6766.43 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 11.22 | 0.00 | 01-JAN-00:40 | 6766.43 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 11.22 | 0.00 | 01-JAN-00:40 | 6766.43 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 21.34 | 0.00 | 01-JAN-00:10 | 5135.85 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 21.34 | 0.00 | 01-JAN-00:10 | 5135.85 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 28.14 | 0.00 | 01-JAN-00:40 | 7061.18 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.01 | 0.00 | 01-JAN-00:40 | 7061.18 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 6.01 | 0.00 | 01-JAN-00:40 | 7061.18 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.13 | 0.00 | 01-JAN-00:10 | 6509.35 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.13 | 0.00 | 01-JAN-00:10 | 6509.35 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 62.88 | 0.00 | 01-JAN-00:40 | 14615.41 | 07-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 36.97 | 0.00 | 01-JAN-00:40 | 14615.41 | 07-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 36.97 | 0.00 | 01-JAN-00:40 | 14615.41 | 07-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.91 | 0.00 | 01-JAN-00:10 | 11013.41 | 10-AUG-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.91 | 0.00 | 01-JAN-00:10 | 11013.41 | 10-AUG-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.26 | 0.00 | 01-JAN-00:40 | 7160.78 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 6.60 | 0.00 | 01-JAN-00:40 | 7160.78 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 6.60 | 0.00 | 01-JAN-00:40 | 7160.78 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.66 | 0.00 | 01-JAN-00:10 | 6821.62 | 04-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.66 | 0.00 | 01-JAN-00:10 | 6821.62 | 04-AUG-17:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 35.35 | 0.00 | 01-JAN-00:40 | 7725.50 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 10.19 | 0.00 | 01-JAN-00:40 | 7725.50 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 10.19 | 0.00 | 01-JAN-00:40 | 7725.50 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.16 | 0.00 | 01-JAN-00:10 | 5997.97 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.16 | 0.00 | 01-JAN-00:10 | 5997.97 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 31.64 | 0.00 | 01-JAN-00:40 | 8124.15 | 17-JUL-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 5.87 | 0.00 | 01-JAN-00:40 | 6997.53 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 5.87 | 0.00 | 01-JAN-00:40 | 6997.53 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 25.77 | 0.00 | 01-JAN-00:10 | 8124.15 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 25.77 | 0.00 | 01-JAN-00:10 | 8124.15 | 17-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 45.94 | 0.00 | 01-JAN-00:40 | 11212.90 | 21-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 6.65 | 0.00 | 01-JAN-00:40 | 10225.01 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 6.65 | 0.00 | 01-JAN-00:40 | 10225.01 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 39.28 | 0.00 | 01-JAN-00:10 | 11212.90 | 21-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 39.28 | 0.00 | 01-JAN-00:10 | 11212.90 | 21-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 32.00 | 0.00 | 01-JAN-00:40 | 8121.64 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.24 | 0.00 | 01-JAN-00:40 | 6969.26 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 6.24 | 0.00 | 01-JAN-00:40 | 6969.26 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.77 | 0.00 | 01-JAN-00:10 | 8121.64 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 25.77 | 0.00 | 01-JAN-00:10 | 8121.64 | 10-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 52.88 | 0.00 | 01-JAN-00:10 | 6712.43 | 16-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6712.43 | 16-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6712.43 | 16-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 52.88 | 0.00 | 01-JAN-00:10 | 6712.43 | 16-FEB-12:30 |
EnergyTransfer:HVAC | 980.52 | 0.00 | 01-JAN-00:40 | 320602.47 | 15-AUG-14:30 |
HeatingCoils:EnergyTransfer | 449.75 | 0.00 | 01-JAN-00:40 | 255855.09 | 11-DEC-07:10 |
CoolingCoils:EnergyTransfer | 530.77 | 0.00 | 01-JAN-00:10 | 320602.47 | 15-AUG-14:30 |
EnergyTransfer:Plant | 52.88 | 0.00 | 01-JAN-00:10 | 6712.43 | 16-FEB-12:30 |
WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6712.43 | 16-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 52.88 | 0.00 | 01-JAN-00:10 | 6712.43 | 16-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.366 | -193.268 | 0.000 | 0.000 | 33.451 | 48.333 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -125.048 |
CORE_MID | 0.000 | 0.000 | 2.582 | -125.281 | 0.000 | 0.000 | 35.065 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -76.125 |
CORE_TOP | 0.000 | 0.000 | 12.355 | -115.017 | 0.000 | 0.000 | 35.730 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -96.826 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 19.669 | -23.892 | 0.000 | 0.000 | 7.652 | 5.985 | 24.333 | 15.609 | 0.000 | 0.025 | 0.001 | 0.000 | -30.547 | 0.000 | -4.693 | -14.142 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 11.224 | -25.140 | 0.000 | 0.000 | 4.804 | 3.759 | 15.404 | 28.516 | 0.000 | 0.016 | 0.000 | 0.000 | -19.229 | 0.000 | -3.159 | -16.195 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 14.230 | -38.090 | 0.000 | 0.000 | 7.509 | 5.889 | 24.332 | 52.968 | 0.000 | 0.024 | 0.001 | 0.000 | -28.938 | 0.000 | -4.843 | -33.082 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 12.219 | -25.261 | 0.000 | 0.000 | 4.860 | 3.757 | 15.403 | 28.679 | 0.000 | 0.017 | 0.000 | 0.000 | -19.964 | 0.000 | -3.173 | -16.538 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 11.219 | -21.345 | 0.000 | 0.000 | 7.633 | 5.966 | 24.333 | 15.914 | 0.000 | 0.017 | 0.000 | 0.000 | -31.569 | 0.000 | -2.606 | -9.563 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 6.007 | -22.134 | 0.000 | 0.000 | 4.766 | 3.751 | 15.404 | 28.647 | 0.000 | 0.009 | 0.000 | 0.000 | -20.148 | 0.000 | -1.775 | -14.525 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 36.969 | -25.914 | 0.000 | 0.000 | 7.800 | 5.877 | 24.332 | 53.903 | 0.000 | 1.187 | 0.000 | 0.000 | -29.722 | 0.000 | -58.356 | -16.076 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 6.601 | -21.662 | 0.000 | 0.000 | 4.806 | 3.748 | 15.403 | 28.862 | 0.000 | 0.009 | 0.000 | 0.000 | -20.902 | 0.000 | -1.782 | -15.084 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 10.192 | -25.157 | 0.000 | 0.000 | 7.570 | 5.985 | 24.333 | 15.374 | 0.000 | 0.022 | 0.000 | 0.000 | -32.158 | 0.000 | -4.103 | -2.059 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 5.869 | -25.769 | 0.000 | 0.000 | 3.528 | 3.759 | 15.404 | 28.336 | 0.000 | 0.014 | 0.000 | 0.000 | -20.200 | 0.000 | -2.756 | -8.185 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 6.652 | -39.284 | 0.000 | 0.000 | 7.410 | 5.888 | 24.332 | 52.667 | 0.000 | 0.020 | 0.000 | 0.000 | -30.504 | 0.000 | -4.242 | -22.939 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 6.236 | -25.768 | 0.000 | 0.000 | 4.804 | 3.757 | 15.403 | 28.523 | 0.000 | 0.014 | 0.000 | 0.000 | -21.007 | 0.000 | -2.772 | -9.191 |
TOPFLOOR_PLENUM | 28.156 | -23.197 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.019 | 2.147 | 0.000 | 0.000 | 0.000 | -7.126 | -0.002 |
MIDFLOOR_PLENUM | 12.877 | -12.314 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.031 | 6.382 | 0.000 | 0.000 | 0.000 | -6.976 | -0.001 |
FIRSTFLOOR_PLENUM | 9.181 | -15.877 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.024 | 12.321 | 0.000 | 0.000 | 0.000 | -5.649 | -0.000 |
Total Facility | 50.215 | -51.387 | 162.390 | -752.981 | 0.000 | 0.000 | 177.387 | 203.119 | 705.434 | 377.998 | 0.000 | 1.449 | 20.854 | 0.000 | -304.887 | 0.000 | -114.009 | -475.580 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 18-SEP-04:03 | 0.00 | 0.00 | 0.00 | -41740.71 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 36866.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-JUL-04:03 | 0.00 | 0.00 | 0.00 | -29857.45 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 26946.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-04:03 | 0.00 | 0.00 | 0.00 | -32003.59 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 29092.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-13:32 | 0.00 | 0.00 | 0.00 | -10504.16 | 0.00 | 0.00 | 28.01 | 23.57 | 478.42 | 3821.09 | 0.00 | 23.82 | 6129.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:02 | 0.00 | 0.00 | 0.00 | -12932.32 | 0.00 | 0.00 | 13.89 | 14.92 | 302.86 | 9958.63 | 0.00 | 0.00 | 2706.46 | 0.00 | -0.00 | 0.00 | -64.44 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:42 | 0.00 | 0.00 | 0.00 | -16751.68 | 0.00 | 0.00 | 24.15 | 23.57 | 478.41 | 12135.29 | 0.00 | 0.00 | 4270.49 | 0.00 | -0.00 | 0.00 | -180.24 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-16:52 | 0.00 | 0.00 | 0.00 | -14812.14 | 0.00 | 0.00 | 12.01 | 14.92 | 302.86 | 11088.88 | 0.00 | 0.00 | 3433.90 | 0.00 | -0.00 | 0.00 | -40.42 | 0.00 |
PERIMETER_BOT_ZN_3 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 | -5136.01 | 0.00 | 0.00 | 757.18 | 424.37 | 1435.25 | 3975.87 | 0.00 | 18.72 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1475.37 |
PERIMETER_BOT_ZN_2 | 04-JUL-10:12 | 0.00 | 0.00 | 0.00 | -10574.07 | 0.00 | 0.00 | 16.44 | 14.92 | 302.86 | 5978.00 | 0.00 | 0.00 | 4289.40 | 0.00 | -0.00 | 0.00 | -27.55 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-14:13 | 0.00 | 0.00 | 0.00 | -12715.35 | 0.00 | 0.00 | 26.48 | 23.57 | 478.41 | 10594.67 | 0.00 | 0.00 | 1689.50 | 0.00 | -0.00 | 0.00 | -97.30 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-18:01 | 0.00 | 0.00 | 0.00 | -11312.37 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 9107.20 | 0.00 | 0.00 | 1964.37 | 0.00 | -0.00 | 0.00 | -18.54 | 0.00 |
PERIMETER_MID_ZN_3 | 10-JUL-06:02 | 0.00 | 0.00 | 0.00 | -7087.70 | 0.00 | 0.00 | 150.52 | 141.46 | 637.89 | 2176.24 | 0.00 | 0.00 | 3998.81 | 0.00 | -0.00 | 0.00 | -17.21 | 0.00 |
PERIMETER_MID_ZN_2 | 11-JUN-09:42 | 0.00 | 0.00 | 0.00 | -12776.11 | 0.00 | 0.00 | 15.53 | 14.92 | 302.86 | 7719.25 | 0.00 | 0.00 | 4779.23 | 0.00 | -0.00 | 0.00 | -55.68 | 0.00 |
PERIMETER_MID_ZN_1 | 30-JUL-12:32 | 0.00 | 0.00 | 0.00 | -14890.20 | 0.00 | 0.00 | 25.16 | 23.57 | 478.41 | 10533.27 | 0.00 | 0.00 | 3873.28 | 0.00 | -0.00 | 0.00 | -43.49 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-18:22 | 0.00 | 0.00 | 0.00 | -13670.36 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 7647.01 | 0.00 | 0.00 | 5801.05 | 0.00 | -0.00 | 0.00 | -37.05 | 0.00 |
TOPFLOOR_PLENUM | 27-JUN-14:55 | 0.00 | -10042.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10044.83 | 0.00 | -0.00 | 0.00 | -2.36 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-07:10 | 0.00 | -4757.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4768.87 | 0.00 | -0.00 | 0.00 | -11.34 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-07:10 | 0.00 | -4932.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4940.29 | 0.00 | -0.00 | 0.00 | -8.13 | 0.00 |
Total Facility | 17-JUL-04:03 | 0.00 | 7135.05 | 0.00 | -154678.06 | 0.00 | 0.00 | 0.00 | 2375.34 | 14333.92 | 0.00 | 0.00 | 0.00 | 135040.53 | 0.00 | -3681.55 | 0.00 | -525.24 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 22704.79 | 0.00 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27579.35 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 23586.65 | 0.00 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26497.62 |
CORE_TOP | 26-DEC-05:11 | 0.00 | 0.00 | 30234.34 | 0.00 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33145.32 |
PERIMETER_TOP_ZN_3 | 06-FEB-04:32 | 0.00 | 0.00 | 10007.97 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3175.13 | 0.00 | -902.26 | -6494.81 |
PERIMETER_TOP_ZN_2 | 06-FEB-04:32 | 0.00 | 0.00 | 11439.42 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2054.08 | 0.00 | -614.97 | -9127.55 |
PERIMETER_TOP_ZN_1 | 06-FEB-04:32 | 0.00 | 0.00 | 14311.54 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3188.53 | 0.00 | -916.51 | -10770.72 |
PERIMETER_TOP_ZN_4 | 06-FEB-04:32 | 0.00 | 0.00 | 12507.58 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2115.22 | 0.00 | -616.75 | -10132.79 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 7316.52 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3277.30 | 0.00 | -511.49 | -4141.39 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 8858.85 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2134.58 | 0.00 | -345.06 | -6767.69 |
PERIMETER_BOT_ZN_1 | 11-DEC-07:10 | 0.00 | 0.00 | 15053.51 | 0.00 | 0.00 | 0.00 | 209.00 | 296.56 | 637.88 | 0.00 | 0.00 | 0.00 | 19180.53 | 0.00 | -3539.53 | 0.00 | -31837.96 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 9295.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2187.14 | 0.00 | -344.80 | -7151.77 |
PERIMETER_MID_ZN_3 | 11-DEC-04:22 | 0.00 | 0.00 | 8243.89 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3358.05 | 0.00 | -232.23 | -5217.83 |
PERIMETER_MID_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 9525.98 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2118.22 | 0.00 | -536.24 | -7259.99 |
PERIMETER_MID_ZN_1 | 06-FEB-05:01 | 0.00 | 0.00 | 12321.70 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3291.20 | 0.00 | -803.44 | -8840.72 |
PERIMETER_MID_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 9633.96 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2179.40 | 0.00 | -535.68 | -7307.35 |
TOPFLOOR_PLENUM | 11-DEC-06:09 | 15451.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -114.87 | -15336.57 |
MIDFLOOR_PLENUM | 02-JAN-07:11 | 9606.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -106.85 | -9500.07 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 8511.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -84.09 | -8427.82 |
Total Facility | 02-JAN-05:01 | 11508.76 | 0.00 | 194996.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.34 | 14333.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16781.17 | 0.00 | -3413.56 | -203019.50 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.2782 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6810 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.9015 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.1227 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.2923 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7921 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.6391 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3453 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4507 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3647 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6462 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4418 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7659 | 2.7659 | 0.7689 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9923 | 1.9923 | 0.7391 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1101 | 2.1101 | 0.7723 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6477 | 0.6477 | 0.1626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7591 | 0.7591 | 0.1518 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9427 | 0.9427 | 0.1885 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8328 | 0.8328 | 0.1666 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5023 | 0.5023 | 0.1617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6172 | 0.6172 | 0.1234 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7457 | 0.7457 | 0.1618 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6470 | 0.6470 | 0.1294 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5601 | 0.5601 | 0.1557 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7382 | 0.7382 | 0.1476 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8488 | 0.8488 | 0.1698 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7621 | 0.7621 | 0.1524 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.2782 | 4.6810 | 5.2782 | 1.3453 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.9015 | 4.1227 | 4.9015 | 1.3647 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.2923 | 4.7921 | 5.2923 | 1.4418 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3830 | 1.3830 | 0.7689 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9961 | 0.9961 | 0.7391 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0550 | 1.0550 | 0.7723 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3238 | 0.3238 | 0.1626 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3796 | 0.3796 | 0.1518 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4713 | 0.4713 | 0.1885 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4164 | 0.4164 | 0.1666 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2512 | 0.2512 | 0.1617 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3086 | 0.3086 | 0.1234 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3728 | 0.3728 | 0.1618 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3235 | 0.3235 | 0.1294 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2801 | 0.2801 | 0.1557 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3691 | 0.3691 | 0.1476 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4244 | 0.4244 | 0.1698 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3810 | 0.3810 | 0.1524 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.6391 | 1.3453 | 1.3453 | 1.3453 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4507 | 1.3647 | 1.3647 | 1.3647 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6462 | 1.4418 | 1.4418 | 1.4418 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 552.33 |
Number of hours cooling loads not met | 64.83 |
Number of hours not met | 617.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 255.17 | 193928.18 | 243.22 | 108107.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 118.02 | 66359.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 203.12 | 21377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.25 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.66 | 834.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 86.29 | 25839.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 112.33 | 10479.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1429.95 |
Natural Gas | 0.00 | 355.55 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1785.51 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 40.77 |
Space Heating | 51.22 |
Space Cooling | 23.69 |
Fans (All) | 17.32 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 287.01 |
Subtotal | 287.01 |
Natural Gas [MJ/m2] | |
Space Heating | 48.82 |
Service Water Heating | 22.55 |
Miscellaneous (All) | 71.36 |
Subtotal | 71.36 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.38 |
Space Heating | 27.91 |
Space Cooling | 6.61 |
Fans (All) | 4.83 |
Service Water Heating | 6.29 |
Receptacle Equipment | 39.51 |
Miscellaneous | 3.47 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8738.33 | 21.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8709.83 | 50.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8703.50 | 56.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8670.50 | 89.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8731.00 | 29.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8697.33 | 62.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8716.67 | 43.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8710.67 | 49.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8677.33 | 82.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8667.33 | 92.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8667.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 92.67 | 0.00 | 0.00 | 0.00 |
Average | 8725.04 | 34.96 | 0.00 | 0.00 | 0.00 |
Sum | 157050.67 | 629.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128299.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 5.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.06 | 0.28 | 0.00 | 0.00 | 0.00 |
Sum | 614575.00 | 5.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8284.00 | 476.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8400.83 | 359.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8470.83 | 289.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8377.67 | 382.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8370.50 | 389.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8344.50 | 415.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8341.50 | 418.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8471.67 | 288.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8373.83 | 386.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8255.33 | 504.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8324.67 | 435.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8338.67 | 421.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8337.00 | 423.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8303.83 | 456.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8309.00 | 451.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8093.00 | 667.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8380.33 | 379.67 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8388.17 | 371.83 | 0.00 | 0.00 | 0.00 |
Min | 8093.00 | 288.33 | 0.00 | 0.00 | 0.00 |
Max | 8471.67 | 667.00 | 0.00 | 0.00 | 0.00 |
Average | 8342.52 | 417.48 | 0.00 | 0.00 | 0.00 |
Sum | 150165.33 | 7514.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128070.33 | 233.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128157.50 | 146.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128141.83 | 162.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24884.17 | 24.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14012.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24891.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14012.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24193.17 | 715.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24900.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24901.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128157.50 | 715.83 | 0.00 | 0.00 | 0.00 |
Average | 34069.58 | 73.75 | 0.00 | 0.00 | 0.00 |
Sum | 613252.50 | 1327.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.822031E+10 | 7653.75 | 20-JAN-17:00 | -1.1 | -3.7 | 0.173188E+10 | 2564.75 | 20-JAN-14:09 | -1.1 | -3.7 |
February | 0.805833E+10 | 8038.47 | 17-FEB-17:00 | 1.10 | 0.20 | 0.160044E+10 | 2588.98 | 17-FEB-14:09 | 1.10 | 0.20 |
March | 0.119651E+11 | 16181.67 | 17-MAR-08:00 | 9.40 | 9.07 | 0.209012E+10 | 2606.63 | 09-MAR-14:09 | 9.40 | 9.07 |
April | 0.133631E+11 | 17390.35 | 21-APR-07:04 | 3.95 | 2.35 | 0.189460E+10 | 2606.66 | 12-APR-13:09 | 3.95 | 2.35 |
May | 0.188482E+11 | 39107.53 | 24-MAY-05:03 | 18.80 | 15.75 | 0.207336E+10 | 2606.68 | 05-MAY-13:09 | 18.80 | 15.75 |
June | 0.237477E+11 | 39307.70 | 01-JUN-05:03 | 15.60 | 14.32 | 0.206935E+10 | 2606.81 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.246828E+11 | 41305.40 | 24-JUL-04:03 | 16.10 | 15.07 | 0.192447E+10 | 2606.68 | 12-JUL-09:00 | 16.10 | 15.07 |
August | 0.261732E+11 | 41060.91 | 21-AUG-04:03 | 14.90 | 13.34 | 0.215981E+10 | 2611.33 | 14-AUG-09:00 | 14.90 | 13.34 |
September | 0.215788E+11 | 41753.93 | 18-SEP-04:03 | 10.40 | 9.46 | 0.191679E+10 | 2606.78 | 12-SEP-13:09 | 10.40 | 9.46 |
October | 0.158614E+11 | 31667.51 | 13-OCT-05:03 | 10.50 | 10.16 | 0.198311E+10 | 2608.74 | 18-OCT-09:09 | 6.88 | 4.39 |
November | 0.117623E+11 | 17847.71 | 01-NOV-07:04 | 5.50 | 2.90 | 0.194106E+10 | 2606.71 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.900741E+10 | 11403.01 | 01-DEC-08:40 | 12.57 | 10.73 | 0.175845E+10 | 2608.37 | 01-DEC-14:39 | 7.57 | 6.05 |
Annual Sum or Average | 0.193269E+12 | 0.231434E+11 | ||||||||
Minimum of Months | 0.805833E+10 | 7653.75 | -1.1 | -3.7 | 0.160044E+10 | 2564.75 | -1.1 | -3.7 | ||
Maximum of Months | 0.261732E+11 | 41753.93 | 18.80 | 15.75 | 0.215981E+10 | 2611.33 | 20.60 | 15.75 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 761021.16 | 298.03 | 18-FEB-16:30 | 1.65 | -0.3 | 0.00 | 0.00 | 01-FEB-00:10 | 1.65 | -0.3 |
March | 0.312646E+09 | 4671.34 | 15-MAR-14:20 | 25.93 | 16.12 | 0.00 | 0.00 | 01-MAR-00:10 | 25.93 | 16.12 |
April | 0.911957E+09 | 3958.52 | 21-APR-14:50 | 14.90 | 8.32 | 0.00 | 0.00 | 01-APR-00:10 | 14.90 | 8.32 |
May | 0.247601E+10 | 6728.31 | 31-MAY-14:30 | 21.70 | 14.07 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.07 |
June | 0.486989E+10 | 10042.47 | 27-JUN-14:55 | 25.60 | 22.78 | 0.00 | 0.00 | 01-JUN-00:10 | 25.60 | 22.78 |
July | 0.607464E+10 | 9806.40 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
August | 0.528828E+10 | 9752.26 | 09-AUG-15:00 | 29.40 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.10 |
September | 0.265724E+10 | 7584.54 | 21-SEP-15:30 | 26.10 | 16.91 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 16.91 |
October | 0.553961E+09 | 3804.94 | 11-OCT-15:20 | 22.03 | 14.58 | 0.00 | 0.00 | 01-OCT-00:10 | 22.03 | 14.58 |
November | 51605463.09 | 999.60 | 04-NOV-15:30 | 18.30 | 13.61 | 0.00 | 0.00 | 01-NOV-00:10 | 18.30 | 13.61 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.231970E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -1.0 | -1.6 | 0.00 | 0.00 | -1.0 | -1.6 | ||
Maximum of Months | 0.607464E+10 | 10042.47 | 31.15 | 22.78 | 0.00 | 0.00 | 31.15 | 22.78 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5107530.36 | 1978.11 | 04-JAN-05:01 | -12.2 | -12.8 | 0.00 | 0.00 | 01-JAN-00:10 | -12.2 | -12.8 |
February | 3938189.51 | 1734.52 | 09-FEB-05:01 | -11.0 | -11.7 | 0.00 | 0.00 | 01-FEB-00:10 | -11.0 | -11.7 |
March | 0.128545E+09 | 1871.86 | 04-MAR-06:01 | -10.6 | -11.5 | 0.00 | 0.00 | 01-MAR-00:10 | -10.6 | -11.5 |
April | 0.267959E+09 | 2090.30 | 11-APR-06:01 | 3.30 | 2.15 | 0.00 | 0.00 | 01-APR-00:10 | 3.30 | 2.15 |
May | 0.945705E+09 | 2083.73 | 31-MAY-16:00 | 22.20 | 14.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 14.47 |
June | 0.254297E+10 | 3982.08 | 12-JUN-15:30 | 29.15 | 20.10 | 0.00 | 0.00 | 01-JUN-00:10 | 29.15 | 20.10 |
July | 0.341568E+10 | 4757.70 | 17-JUL-07:10 | 23.40 | 20.98 | 0.00 | 0.00 | 01-JUL-00:10 | 23.40 | 20.98 |
August | 0.311802E+10 | 4347.09 | 07-AUG-06:15 | 20.77 | 18.75 | 0.00 | 0.00 | 01-AUG-00:10 | 20.77 | 18.75 |
September | 0.151762E+10 | 3016.79 | 18-SEP-12:50 | 18.80 | 12.41 | 0.00 | 0.00 | 01-SEP-00:10 | 18.80 | 12.41 |
October | 0.307165E+09 | 2161.71 | 24-OCT-06:01 | 1.70 | 0.40 | 0.00 | 0.00 | 01-OCT-00:10 | 1.70 | 0.40 |
November | 55387645.31 | 1272.16 | 02-NOV-06:02 | 4.40 | 3.64 | 0.00 | 0.00 | 01-NOV-00:10 | 4.40 | 3.64 |
December | 5775599.76 | 1621.83 | 28-DEC-05:01 | -11.8 | -12.1 | 0.00 | 0.00 | 01-DEC-00:10 | -11.8 | -12.1 |
Annual Sum or Average | 0.123139E+11 | 0.00 | ||||||||
Minimum of Months | 3938189.51 | 1272.16 | -12.2 | -12.8 | 0.00 | 0.00 | -12.2 | -12.8 | ||
Maximum of Months | 0.341568E+10 | 4757.70 | 29.15 | 20.98 | 0.00 | 0.00 | 29.15 | 20.98 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64464340.10 | 1951.71 | 12-JAN-17:10 | -6.9 | -8.5 | 0.00 | 0.00 | 01-JAN-00:10 | -6.9 | -8.5 |
February | 66292046.91 | 1939.20 | 10-FEB-17:10 | -7.4 | -8.0 | 0.00 | 0.00 | 01-FEB-00:10 | -7.4 | -8.0 |
March | 0.276170E+09 | 2459.14 | 24-MAR-06:10 | -5.1 | -6.3 | 0.00 | 0.00 | 01-MAR-00:10 | -5.1 | -6.3 |
April | 0.516255E+09 | 2493.45 | 11-APR-06:01 | 3.30 | 2.15 | 0.00 | 0.00 | 01-APR-00:10 | 3.30 | 2.15 |
May | 0.142647E+10 | 2381.09 | 30-MAY-06:10 | 12.20 | 11.93 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 11.93 |
June | 0.296252E+10 | 4290.13 | 12-JUN-12:10 | 29.40 | 20.05 | 0.00 | 0.00 | 01-JUN-00:10 | 29.40 | 20.05 |
July | 0.378202E+10 | 4931.88 | 17-JUL-07:10 | 23.40 | 20.98 | 0.00 | 0.00 | 01-JUL-00:10 | 23.40 | 20.98 |
August | 0.373234E+10 | 4845.71 | 07-AUG-06:15 | 20.77 | 18.75 | 0.00 | 0.00 | 01-AUG-00:10 | 20.77 | 18.75 |
September | 0.223936E+10 | 4082.55 | 18-SEP-12:10 | 18.40 | 12.35 | 0.00 | 0.00 | 01-SEP-00:10 | 18.40 | 12.35 |
October | 0.593312E+09 | 2089.73 | 24-OCT-06:09 | 1.70 | 0.40 | 0.00 | 0.00 | 01-OCT-00:10 | 1.70 | 0.40 |
November | 0.162025E+09 | 1888.90 | 03-NOV-06:01 | 1.70 | 0.39 | 0.00 | 0.00 | 01-NOV-00:10 | 1.70 | 0.39 |
December | 55922534.18 | 1718.09 | 08-DEC-07:10 | -10.4 | -10.8 | 0.00 | 0.00 | 01-DEC-00:10 | -10.4 | -10.8 |
Annual Sum or Average | 0.158772E+11 | 0.00 | ||||||||
Minimum of Months | 55922534.18 | 1718.09 | -10.4 | -10.8 | 0.00 | 0.00 | -10.4 | -10.8 | ||
Maximum of Months | 0.378202E+10 | 4931.88 | 29.40 | 20.98 | 0.00 | 0.00 | 29.40 | 20.98 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.433694E+10 | 5838.99 | 12-JAN-16:50 | -6.6 | -8.3 | 0.149811E+10 | 2152.00 | 12-JAN-14:00 | -6.6 | -8.3 |
February | 0.430574E+10 | 5889.01 | 17-FEB-17:00 | 1.10 | 0.20 | 0.137238E+10 | 2182.13 | 17-FEB-14:00 | 1.10 | 0.20 |
March | 0.811488E+10 | 10032.71 | 16-MAR-16:00 | 15.60 | 13.95 | 0.182100E+10 | 2606.61 | 16-MAR-09:00 | 15.60 | 13.95 |
April | 0.877533E+10 | 9153.44 | 21-APR-16:00 | 13.30 | 8.77 | 0.175064E+10 | 2606.61 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.123907E+11 | 20358.43 | 24-MAY-05:03 | 18.80 | 15.75 | 0.204005E+10 | 2606.64 | 05-MAY-13:09 | 18.80 | 15.75 |
June | 0.163801E+11 | 28890.22 | 19-JUN-05:03 | 16.70 | 15.97 | 0.206226E+10 | 2606.78 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.176008E+11 | 29854.71 | 05-JUL-04:03 | 18.48 | 16.54 | 0.192021E+10 | 2606.66 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.178152E+11 | 29824.05 | 07-AUG-04:03 | 20.00 | 18.50 | 0.215525E+10 | 2606.80 | 02-AUG-13:09 | 20.00 | 18.50 |
September | 0.137223E+11 | 29018.64 | 18-SEP-05:03 | 9.50 | 8.65 | 0.190309E+10 | 2606.75 | 12-SEP-13:09 | 9.50 | 8.65 |
October | 0.943278E+10 | 11200.80 | 12-OCT-16:00 | 18.30 | 14.87 | 0.185892E+10 | 2606.60 | 06-OCT-13:00 | 18.30 | 14.87 |
November | 0.738324E+10 | 7220.10 | 01-NOV-16:00 | 9.40 | 6.91 | 0.167808E+10 | 2532.03 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.502317E+10 | 6188.06 | 01-DEC-17:00 | 7.20 | 4.89 | 0.146868E+10 | 2260.66 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.125281E+12 | 0.215287E+11 | ||||||||
Minimum of Months | 0.430574E+10 | 5838.99 | -6.6 | -8.3 | 0.137238E+10 | 2152.00 | -6.6 | -8.3 | ||
Maximum of Months | 0.178152E+11 | 29854.71 | 20.00 | 18.50 | 0.215525E+10 | 2606.80 | 20.60 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255217E+10 | 5548.98 | 12-JAN-16:30 | -6.4 | -8.3 | 0.145911E+10 | 2029.21 | 12-JAN-14:00 | -6.4 | -8.3 |
February | 0.286427E+10 | 5727.07 | 28-FEB-17:00 | -0.6 | -3.0 | 0.133351E+10 | 2070.41 | 17-FEB-14:00 | -0.6 | -3.0 |
March | 0.671911E+10 | 10167.38 | 16-MAR-16:00 | 15.60 | 13.95 | 0.173158E+10 | 2606.60 | 15-MAR-13:39 | 15.60 | 13.95 |
April | 0.811279E+10 | 9930.14 | 21-APR-16:00 | 13.30 | 8.77 | 0.165590E+10 | 2606.61 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.121481E+11 | 14729.88 | 31-MAY-16:00 | 22.20 | 14.47 | 0.199410E+10 | 2606.64 | 05-MAY-13:09 | 22.20 | 14.47 |
June | 0.166641E+11 | 31046.56 | 19-JUN-05:03 | 16.70 | 15.97 | 0.205367E+10 | 2673.14 | 27-JUN-15:30 | 25.85 | 22.66 |
July | 0.182487E+11 | 30443.38 | 19-JUL-05:03 | 22.20 | 19.60 | 0.191742E+10 | 2606.66 | 12-JUL-09:00 | 22.20 | 19.60 |
August | 0.178508E+11 | 32003.82 | 07-AUG-04:03 | 20.00 | 18.50 | 0.214836E+10 | 2606.81 | 02-AUG-13:09 | 20.00 | 18.50 |
September | 0.128504E+11 | 16791.21 | 18-SEP-05:03 | 9.50 | 8.65 | 0.187381E+10 | 2606.75 | 12-SEP-13:09 | 9.50 | 8.65 |
October | 0.841385E+10 | 10758.53 | 12-OCT-16:00 | 18.30 | 14.87 | 0.173592E+10 | 2606.58 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.572153E+10 | 6981.13 | 01-NOV-16:00 | 9.40 | 6.91 | 0.154941E+10 | 2396.57 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.287161E+10 | 5863.58 | 01-DEC-15:00 | 7.20 | 5.63 | 0.141148E+10 | 2128.01 | 01-DEC-14:00 | 7.20 | 5.63 |
Annual Sum or Average | 0.115017E+12 | 0.208643E+11 | ||||||||
Minimum of Months | 0.255217E+10 | 5548.98 | -6.4 | -8.3 | 0.133351E+10 | 2029.21 | -6.4 | -8.3 | ||
Maximum of Months | 0.182487E+11 | 32003.82 | 22.20 | 19.60 | 0.214836E+10 | 2673.14 | 25.85 | 22.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19444582.88 | 986.31 | 14-JAN-16:03 | 3.30 | 2.84 | 0.303959E+09 | 406.70 | 12-JAN-10:09 | 3.30 | 2.84 |
February | 28596862.59 | 986.63 | 18-FEB-16:03 | 2.02 | -0.3 | 0.275596E+09 | 406.69 | 06-FEB-14:00 | 2.02 | -0.3 |
March | 0.686539E+09 | 3245.79 | 15-MAR-15:20 | 25.40 | 16.14 | 0.348545E+09 | 549.49 | 15-MAR-13:39 | 25.40 | 16.14 |
April | 0.127192E+10 | 2153.34 | 21-APR-15:30 | 14.15 | 8.57 | 0.327552E+09 | 549.49 | 21-APR-13:00 | 14.15 | 8.57 |
May | 0.261342E+10 | 4451.36 | 23-MAY-14:40 | 23.90 | 13.32 | 0.408852E+09 | 549.50 | 10-MAY-13:00 | 23.90 | 13.32 |
June | 0.451970E+10 | 6984.82 | 27-JUN-15:47 | 26.02 | 22.57 | 0.431536E+09 | 577.45 | 27-JUN-15:30 | 26.02 | 22.57 |
July | 0.534467E+10 | 10508.57 | 16-JUL-13:32 | 27.93 | 21.28 | 0.404669E+09 | 549.57 | 21-JUL-13:39 | 31.33 | 21.85 |
August | 0.485596E+10 | 6873.22 | 06-AUG-14:02 | 26.97 | 18.51 | 0.450751E+09 | 549.54 | 02-AUG-13:09 | 26.97 | 18.51 |
September | 0.283121E+10 | 4471.88 | 15-SEP-14:00 | 25.60 | 21.03 | 0.384526E+09 | 549.52 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.128878E+10 | 2290.47 | 12-OCT-15:20 | 18.30 | 15.11 | 0.342575E+09 | 549.48 | 12-OCT-13:00 | 18.30 | 15.11 |
November | 0.393458E+09 | 1332.06 | 16-NOV-16:40 | 17.93 | 13.54 | 0.307187E+09 | 470.27 | 16-NOV-14:00 | 17.93 | 13.54 |
December | 38743668.99 | 1068.01 | 01-DEC-13:50 | 9.23 | 7.80 | 0.293062E+09 | 406.70 | 26-DEC-14:30 | -9.4 | -11.0 |
Annual Sum or Average | 0.238925E+11 | 0.427881E+10 | ||||||||
Minimum of Months | 19444582.88 | 986.31 | 2.02 | -0.3 | 0.275596E+09 | 406.69 | -9.4 | -11.0 | ||
Maximum of Months | 0.534467E+10 | 10508.57 | 27.93 | 22.57 | 0.450751E+09 | 577.45 | 31.33 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 19304727.06 | 912.66 | 14-JAN-16:03 | 3.30 | 2.84 | 0.192870E+09 | 257.47 | 03-JAN-10:09 | 3.30 | 2.84 |
February | 0.111727E+09 | 1168.52 | 28-FEB-10:10 | -3.6 | -5.3 | 0.175490E+09 | 288.74 | 28-FEB-10:20 | -3.3 | -5.1 |
March | 0.869450E+09 | 2553.23 | 15-MAR-14:00 | 26.10 | 16.06 | 0.226564E+09 | 347.88 | 15-MAR-13:39 | 26.10 | 16.06 |
April | 0.158978E+10 | 4857.77 | 24-APR-09:20 | 6.47 | 3.13 | 0.221226E+09 | 347.88 | 21-APR-13:00 | 6.47 | 3.13 |
May | 0.304574E+10 | 7131.46 | 31-MAY-09:00 | 17.80 | 13.21 | 0.264084E+09 | 347.88 | 26-MAY-09:00 | 17.80 | 13.21 |
June | 0.458542E+10 | 11597.57 | 11-JUN-10:32 | 24.80 | 17.18 | 0.274004E+09 | 348.31 | 12-JUN-09:00 | 27.80 | 19.41 |
July | 0.523309E+10 | 12934.32 | 04-JUL-09:02 | 21.28 | 17.22 | 0.256486E+09 | 348.47 | 17-JUL-09:09 | 25.10 | 20.50 |
August | 0.481256E+10 | 12257.81 | 06-AUG-08:43 | 23.53 | 17.08 | 0.285889E+09 | 348.26 | 10-AUG-09:00 | 27.80 | 20.31 |
September | 0.308660E+10 | 6005.42 | 18-SEP-09:30 | 16.15 | 11.54 | 0.246186E+09 | 347.89 | 12-SEP-13:09 | 16.15 | 11.54 |
October | 0.134414E+10 | 3617.39 | 11-OCT-09:40 | 16.13 | 11.96 | 0.224573E+09 | 347.87 | 10-OCT-09:50 | 16.13 | 11.96 |
November | 0.408622E+09 | 1346.10 | 03-NOV-09:30 | 4.75 | 2.42 | 0.196015E+09 | 317.75 | 03-NOV-09:39 | 5.03 | 2.61 |
December | 33484126.35 | 911.19 | 16-DEC-16:03 | 4.22 | 2.19 | 0.186052E+09 | 257.47 | 26-DEC-14:30 | -9.4 | -11.0 |
Annual Sum or Average | 0.251399E+11 | 0.274944E+10 | ||||||||
Minimum of Months | 19304727.06 | 911.19 | -3.6 | -5.3 | 0.175490E+09 | 257.47 | -9.4 | -11.0 | ||
Maximum of Months | 0.523309E+10 | 12934.32 | 26.10 | 17.22 | 0.285889E+09 | 348.47 | 27.80 | 20.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389579E+09 | 3425.99 | 12-JAN-13:40 | -6.5 | -9.0 | 0.315902E+09 | 549.49 | 12-JAN-14:00 | -5.6 | -8.1 |
February | 0.514117E+09 | 5352.43 | 28-FEB-13:50 | 0.00 | -3.0 | 0.290307E+09 | 549.49 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.184469E+10 | 9117.84 | 15-MAR-13:30 | 25.55 | 15.84 | 0.381713E+09 | 549.53 | 15-MAR-13:30 | 25.55 | 15.84 |
April | 0.237203E+10 | 7466.30 | 24-APR-13:10 | 11.38 | 6.04 | 0.348640E+09 | 549.52 | 21-APR-13:00 | 11.38 | 6.04 |
May | 0.394356E+10 | 7587.67 | 26-MAY-13:30 | 20.85 | 13.56 | 0.410956E+09 | 549.51 | 10-MAY-13:00 | 20.85 | 13.56 |
June | 0.564785E+10 | 14395.60 | 18-JUN-13:53 | 25.60 | 21.03 | 0.429432E+09 | 567.08 | 27-JUN-15:20 | 25.77 | 22.70 |
July | 0.672733E+10 | 15812.84 | 30-JUL-14:02 | 25.40 | 19.72 | 0.403812E+09 | 550.03 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.700524E+10 | 15989.52 | 13-AUG-13:13 | 30.00 | 22.88 | 0.450440E+09 | 550.01 | 03-AUG-13:00 | 30.00 | 22.88 |
September | 0.540800E+10 | 16750.99 | 10-SEP-13:42 | 17.20 | 10.65 | 0.389691E+09 | 550.12 | 22-SEP-13:50 | 23.72 | 15.13 |
October | 0.285716E+10 | 11106.07 | 11-OCT-12:30 | 21.95 | 13.79 | 0.371957E+09 | 549.51 | 30-OCT-13:00 | 15.00 | 8.94 |
November | 0.108185E+10 | 6654.16 | 03-NOV-12:35 | 8.53 | 4.68 | 0.329256E+09 | 549.50 | 01-NOV-13:00 | 8.53 | 4.68 |
December | 0.298632E+09 | 3158.03 | 16-DEC-13:30 | 5.60 | 3.03 | 0.299484E+09 | 549.48 | 04-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.380900E+11 | 0.442159E+10 | ||||||||
Minimum of Months | 0.298632E+09 | 3158.03 | -6.5 | -9.0 | 0.290307E+09 | 549.48 | -5.6 | -8.1 | ||
Maximum of Months | 0.700524E+10 | 16750.99 | 30.00 | 22.88 | 0.450440E+09 | 567.08 | 30.00 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49313747.40 | 1165.83 | 12-JAN-16:10 | -6.2 | -8.3 | 0.192920E+09 | 264.59 | 12-JAN-16:19 | -6.3 | -8.3 |
February | 0.117750E+09 | 1613.30 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176141E+09 | 330.98 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.874393E+09 | 3276.54 | 15-MAR-14:20 | 25.93 | 16.12 | 0.223612E+09 | 347.85 | 15-MAR-13:39 | 25.93 | 16.12 |
April | 0.156552E+10 | 5849.22 | 24-APR-16:00 | 13.30 | 7.63 | 0.207421E+09 | 347.85 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.310754E+10 | 11622.01 | 27-MAY-17:06 | 20.32 | 11.21 | 0.251353E+09 | 347.86 | 10-MAY-13:00 | 20.32 | 11.21 |
June | 0.473908E+10 | 14128.41 | 11-JUN-16:32 | 25.60 | 17.82 | 0.269401E+09 | 371.76 | 27-JUN-15:50 | 26.02 | 22.57 |
July | 0.510039E+10 | 14811.92 | 02-JUL-16:52 | 25.00 | 17.00 | 0.254415E+09 | 347.86 | 24-JUL-13:39 | 25.93 | 17.98 |
August | 0.480198E+10 | 13543.24 | 12-AUG-17:05 | 24.72 | 16.93 | 0.282229E+09 | 347.88 | 02-AUG-13:09 | 24.72 | 16.93 |
September | 0.303056E+10 | 14313.46 | 04-SEP-16:42 | 18.30 | 12.93 | 0.237948E+09 | 347.86 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.138675E+10 | 5539.98 | 11-OCT-16:00 | 21.70 | 14.52 | 0.215282E+09 | 347.84 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.430899E+09 | 1575.79 | 03-NOV-15:40 | 9.27 | 5.12 | 0.195719E+09 | 324.33 | 03-NOV-15:50 | 9.08 | 5.02 |
December | 57414172.29 | 1164.72 | 04-DEC-15:50 | -0.5 | -3.2 | 0.186062E+09 | 264.09 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.252616E+11 | 0.269250E+10 | ||||||||
Minimum of Months | 49313747.40 | 1164.72 | -6.2 | -8.3 | 0.176141E+09 | 264.09 | -6.3 | -8.3 | ||
Maximum of Months | 0.510039E+10 | 14811.92 | 25.93 | 17.82 | 0.282229E+09 | 371.76 | 26.02 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21826653.99 | 988.54 | 14-JAN-16:03 | 3.30 | 2.84 | 0.304674E+09 | 406.70 | 03-JAN-10:00 | 3.30 | 2.84 |
February | 24651327.58 | 984.16 | 17-FEB-21:03 | 0.60 | -0.2 | 0.276715E+09 | 406.70 | 06-FEB-14:00 | 0.60 | -0.2 |
March | 0.574772E+09 | 1537.41 | 15-MAR-15:30 | 25.30 | 16.10 | 0.343180E+09 | 519.75 | 15-MAR-13:00 | 25.30 | 16.10 |
April | 0.115847E+10 | 1426.50 | 21-APR-15:40 | 13.87 | 8.65 | 0.317079E+09 | 497.35 | 27-APR-13:00 | 13.30 | 8.09 |
May | 0.201763E+10 | 2521.15 | 23-MAY-14:40 | 23.90 | 13.32 | 0.395987E+09 | 549.48 | 23-MAY-13:09 | 23.90 | 13.32 |
June | 0.339203E+10 | 4416.61 | 27-JUN-13:30 | 28.90 | 23.32 | 0.431001E+09 | 549.52 | 22-JUN-13:09 | 28.90 | 23.32 |
July | 0.426723E+10 | 5135.85 | 21-JUL-13:50 | 31.52 | 21.79 | 0.404172E+09 | 549.50 | 12-JUL-09:00 | 31.52 | 21.79 |
August | 0.426099E+10 | 5120.74 | 14-AUG-12:20 | 26.50 | 21.48 | 0.452601E+09 | 554.06 | 14-AUG-09:00 | 26.50 | 21.48 |
September | 0.280030E+10 | 3788.19 | 18-SEP-13:40 | 18.17 | 12.62 | 0.394345E+09 | 549.52 | 12-SEP-13:09 | 18.17 | 12.62 |
October | 0.174638E+10 | 2020.59 | 05-OCT-14:40 | 18.90 | 12.59 | 0.364139E+09 | 549.48 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.982055E+09 | 1365.87 | 01-NOV-13:10 | 11.52 | 6.96 | 0.317980E+09 | 483.99 | 01-NOV-13:39 | 10.97 | 6.90 |
December | 98488054.53 | 1170.99 | 01-DEC-13:30 | 11.10 | 9.57 | 0.295307E+09 | 430.76 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.213448E+11 | 0.429718E+10 | ||||||||
Minimum of Months | 21826653.99 | 984.16 | 0.60 | -0.2 | 0.276715E+09 | 406.70 | 0.60 | -0.2 | ||
Maximum of Months | 0.426723E+10 | 5135.85 | 31.52 | 23.32 | 0.452601E+09 | 554.06 | 31.52 | 23.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20262258.11 | 808.51 | 14-JAN-07:05 | 3.30 | 2.57 | 0.193490E+09 | 257.49 | 02-JAN-14:30 | 3.30 | 2.57 |
February | 85303776.21 | 877.96 | 28-FEB-10:10 | -3.6 | -5.3 | 0.175933E+09 | 274.35 | 28-FEB-10:20 | -3.3 | -5.1 |
March | 0.713962E+09 | 1240.05 | 15-MAR-14:10 | 26.02 | 16.09 | 0.224735E+09 | 346.43 | 15-MAR-13:00 | 26.02 | 16.09 |
April | 0.127315E+10 | 3408.84 | 24-APR-09:20 | 6.47 | 3.13 | 0.221875E+09 | 347.87 | 21-APR-13:00 | 6.47 | 3.13 |
May | 0.216456E+10 | 4668.37 | 31-MAY-09:20 | 17.97 | 13.39 | 0.264608E+09 | 347.88 | 26-MAY-09:00 | 17.97 | 13.39 |
June | 0.365422E+10 | 6551.59 | 23-JUN-06:03 | 13.90 | 11.85 | 0.274933E+09 | 347.89 | 22-JUN-13:09 | 13.90 | 11.85 |
July | 0.443258E+10 | 10574.50 | 04-JUL-10:12 | 22.77 | 17.60 | 0.256746E+09 | 348.28 | 17-JUL-09:09 | 25.10 | 20.50 |
August | 0.436710E+10 | 7627.97 | 06-AUG-08:43 | 23.53 | 17.08 | 0.287399E+09 | 348.50 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.299210E+10 | 5038.18 | 18-SEP-09:30 | 16.15 | 11.54 | 0.252173E+09 | 347.89 | 12-SEP-13:09 | 16.15 | 11.54 |
October | 0.154223E+10 | 3350.67 | 11-OCT-09:40 | 16.13 | 11.96 | 0.243236E+09 | 347.88 | 10-OCT-09:09 | 16.13 | 11.96 |
November | 0.814066E+09 | 1216.98 | 03-NOV-09:00 | 3.90 | 1.83 | 0.205253E+09 | 344.07 | 03-NOV-09:09 | 4.18 | 2.03 |
December | 75047970.91 | 866.44 | 01-DEC-13:30 | 11.10 | 9.57 | 0.187114E+09 | 267.24 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.221346E+11 | 0.278750E+10 | ||||||||
Minimum of Months | 20262258.11 | 808.51 | -3.6 | -5.3 | 0.175933E+09 | 257.49 | -3.3 | -5.1 | ||
Maximum of Months | 0.443258E+10 | 10574.50 | 26.02 | 17.60 | 0.287399E+09 | 348.50 | 26.02 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45889204.32 | 1178.22 | 21-JAN-12:30 | -0.6 | -3.1 | 0.274515E+09 | 406.64 | 26-JAN-10:00 | -4.4 | -6.5 |
February | 66953571.79 | 1373.40 | 18-FEB-14:40 | 2.80 | 0.63 | 0.249180E+09 | 416.02 | 22-FEB-14:00 | 10.60 | 4.92 |
March | 0.606858E+09 | 5479.23 | 15-MAR-13:30 | 25.55 | 15.84 | 0.331495E+09 | 549.50 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.902156E+09 | 3127.61 | 22-APR-13:40 | 15.20 | 6.94 | 0.310367E+09 | 549.51 | 21-APR-13:00 | 15.20 | 6.94 |
May | 0.189035E+10 | 4438.34 | 23-MAY-14:30 | 23.90 | 13.29 | 0.376955E+09 | 549.50 | 10-MAY-13:00 | 23.90 | 13.29 |
June | 0.371719E+10 | 10704.35 | 27-JUN-12:00 | 30.00 | 22.87 | 0.415752E+09 | 570.13 | 27-JUN-12:09 | 30.10 | 23.02 |
July | 0.565279E+10 | 10971.60 | 21-JUL-12:00 | 30.00 | 21.57 | 0.401131E+09 | 586.87 | 21-JUL-12:09 | 30.10 | 21.65 |
August | 0.607893E+10 | 12110.57 | 06-AUG-14:02 | 26.97 | 18.51 | 0.446587E+09 | 588.68 | 10-AUG-12:09 | 29.82 | 22.08 |
September | 0.427391E+10 | 12716.72 | 04-SEP-14:13 | 18.17 | 13.03 | 0.387304E+09 | 549.80 | 22-SEP-13:30 | 23.35 | 14.79 |
October | 0.194597E+10 | 9035.39 | 11-OCT-12:40 | 22.03 | 13.91 | 0.356332E+09 | 549.75 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.636740E+09 | 2118.00 | 18-NOV-13:30 | 5.30 | 1.94 | 0.310199E+09 | 547.44 | 03-NOV-13:00 | 5.30 | 1.94 |
December | 96543209.13 | 1580.95 | 16-DEC-13:40 | 5.60 | 2.97 | 0.270842E+09 | 406.65 | 22-DEC-10:09 | -2.0 | -2.8 |
Annual Sum or Average | 0.259143E+11 | 0.413066E+10 | ||||||||
Minimum of Months | 45889204.32 | 1178.22 | -0.6 | -3.1 | 0.249180E+09 | 406.64 | -4.4 | -6.5 | ||
Maximum of Months | 0.607893E+10 | 12716.72 | 30.00 | 22.87 | 0.446587E+09 | 588.68 | 30.10 | 23.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 41359309.97 | 942.39 | 12-JAN-16:10 | -6.2 | -8.3 | 0.193508E+09 | 271.22 | 12-JAN-16:19 | -6.3 | -8.3 |
February | 83386377.51 | 1145.87 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176263E+09 | 309.48 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.690386E+09 | 1418.80 | 15-MAR-14:20 | 25.93 | 16.12 | 0.221172E+09 | 346.76 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.120736E+10 | 3531.35 | 24-APR-17:30 | 11.70 | 7.64 | 0.209590E+09 | 347.55 | 21-APR-13:00 | 11.70 | 7.64 |
May | 0.212631E+10 | 5678.24 | 27-MAY-17:08 | 20.32 | 11.21 | 0.255264E+09 | 347.84 | 23-MAY-13:09 | 20.32 | 11.21 |
June | 0.375077E+10 | 11060.84 | 25-JUN-17:42 | 26.78 | 18.33 | 0.273595E+09 | 347.87 | 22-JUN-13:09 | 26.78 | 18.33 |
July | 0.423413E+10 | 11312.54 | 02-JUL-18:01 | 23.72 | 16.60 | 0.256360E+09 | 347.86 | 03-JUL-13:39 | 25.20 | 16.81 |
August | 0.428633E+10 | 9536.18 | 12-AUG-17:05 | 24.72 | 16.93 | 0.286968E+09 | 348.50 | 14-AUG-09:00 | 23.90 | 22.00 |
September | 0.278965E+10 | 7185.92 | 04-SEP-16:53 | 18.30 | 12.88 | 0.250561E+09 | 347.87 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.155363E+10 | 4657.21 | 11-OCT-16:00 | 21.70 | 14.52 | 0.233295E+09 | 347.84 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.806089E+09 | 1277.14 | 03-NOV-15:50 | 9.08 | 5.02 | 0.202914E+09 | 335.08 | 03-NOV-15:00 | 8.90 | 4.93 |
December | 92483062.99 | 963.66 | 04-DEC-15:50 | -0.5 | -3.2 | 0.187121E+09 | 274.78 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.216619E+11 | 0.274661E+10 | ||||||||
Minimum of Months | 41359309.97 | 942.39 | -6.2 | -8.3 | 0.176263E+09 | 271.22 | -6.3 | -8.3 | ||
Maximum of Months | 0.428633E+10 | 11312.54 | 26.78 | 18.33 | 0.286968E+09 | 348.50 | 26.78 | 22.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40009078.60 | 958.63 | 14-JAN-16:03 | 3.30 | 2.84 | 0.305020E+09 | 406.69 | 23-JAN-10:09 | -7.0 | -8.8 |
February | 75305232.90 | 955.83 | 18-FEB-16:03 | 2.02 | -0.3 | 0.276967E+09 | 406.69 | 06-FEB-14:00 | 2.02 | -0.3 |
March | 0.924010E+09 | 2771.40 | 15-MAR-15:20 | 25.40 | 16.14 | 0.355209E+09 | 549.48 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.151906E+10 | 2015.31 | 21-APR-15:30 | 14.15 | 8.57 | 0.341607E+09 | 549.49 | 21-APR-13:00 | 14.15 | 8.57 |
May | 0.267272E+10 | 4177.54 | 23-MAY-14:40 | 23.90 | 13.32 | 0.420839E+09 | 549.50 | 17-MAY-09:00 | 23.90 | 13.32 |
June | 0.444210E+10 | 6334.99 | 21-JUN-06:03 | 18.48 | 16.25 | 0.434302E+09 | 549.52 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.514594E+10 | 7088.36 | 10-JUL-06:02 | 14.78 | 13.59 | 0.405262E+09 | 549.60 | 20-JUL-13:30 | 30.00 | 23.60 |
August | 0.479382E+10 | 6686.62 | 07-AUG-06:03 | 20.68 | 18.73 | 0.453456E+09 | 549.56 | 14-AUG-13:09 | 26.47 | 20.73 |
September | 0.298060E+10 | 4210.04 | 13-SEP-13:30 | 22.20 | 19.01 | 0.394886E+09 | 549.52 | 12-SEP-13:09 | 22.20 | 19.01 |
October | 0.164938E+10 | 2431.33 | 12-OCT-15:20 | 18.30 | 15.11 | 0.361720E+09 | 549.49 | 12-OCT-13:00 | 18.30 | 15.11 |
November | 0.817187E+09 | 1353.42 | 01-NOV-13:40 | 10.97 | 6.90 | 0.316295E+09 | 493.81 | 01-NOV-13:50 | 10.78 | 6.88 |
December | 97276640.20 | 1122.41 | 01-DEC-13:30 | 11.10 | 9.57 | 0.294827E+09 | 429.25 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.251574E+11 | 0.436039E+10 | ||||||||
Minimum of Months | 40009078.60 | 955.83 | 2.02 | -0.3 | 0.276967E+09 | 406.69 | -7.0 | -8.8 | ||
Maximum of Months | 0.514594E+10 | 7088.36 | 25.40 | 19.01 | 0.453456E+09 | 549.60 | 30.00 | 23.60 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44373192.64 | 989.83 | 14-JAN-07:05 | 3.30 | 2.57 | 0.142247E+09 | 250.68 | 02-JAN-09:00 | 3.30 | 2.57 |
February | 0.156947E+09 | 1253.48 | 28-FEB-10:00 | -3.9 | -5.5 | 0.129763E+09 | 300.71 | 28-FEB-09:00 | -3.9 | -5.5 |
March | 0.104345E+10 | 2347.59 | 14-MAR-10:30 | 20.80 | 17.14 | 0.169357E+09 | 338.72 | 21-MAR-10:09 | 2.88 | 0.57 |
April | 0.181626E+10 | 5633.55 | 24-APR-08:50 | 5.92 | 2.67 | 0.166232E+09 | 338.73 | 21-APR-14:09 | 5.92 | 2.67 |
May | 0.307853E+10 | 7268.71 | 31-MAY-08:40 | 17.60 | 13.16 | 0.197072E+09 | 338.73 | 26-MAY-10:09 | 17.60 | 13.16 |
June | 0.443226E+10 | 12776.76 | 11-JUN-09:42 | 24.22 | 16.74 | 0.202742E+09 | 338.82 | 23-JUN-08:00 | 15.60 | 11.53 |
July | 0.496883E+10 | 12598.93 | 04-JUL-08:42 | 21.10 | 17.25 | 0.190164E+09 | 342.42 | 17-JUL-07:19 | 23.50 | 20.94 |
August | 0.465897E+10 | 12690.08 | 06-AUG-09:12 | 24.47 | 17.45 | 0.211528E+09 | 339.15 | 15-AUG-14:39 | 24.23 | 21.18 |
September | 0.316518E+10 | 6432.98 | 10-SEP-10:33 | 15.93 | 10.61 | 0.183955E+09 | 338.74 | 12-SEP-12:20 | 20.77 | 15.37 |
October | 0.162824E+10 | 4264.31 | 11-OCT-09:00 | 15.00 | 11.35 | 0.171424E+09 | 338.72 | 03-OCT-10:09 | 15.00 | 11.35 |
November | 0.703539E+09 | 1463.80 | 03-NOV-09:00 | 3.90 | 1.83 | 0.147396E+09 | 332.60 | 03-NOV-08:00 | 3.90 | 1.83 |
December | 72154080.77 | 1004.38 | 01-DEC-07:05 | 10.68 | 9.22 | 0.137426E+09 | 255.46 | 01-DEC-13:39 | 10.17 | 8.68 |
Annual Sum or Average | 0.257687E+11 | 0.204931E+10 | ||||||||
Minimum of Months | 44373192.64 | 989.83 | -3.9 | -5.5 | 0.129763E+09 | 250.68 | -3.9 | -5.5 | ||
Maximum of Months | 0.496883E+10 | 12776.76 | 24.47 | 17.45 | 0.211528E+09 | 342.42 | 24.23 | 21.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.510240E+09 | 4352.26 | 12-JAN-13:25 | -6.7 | -9.2 | 0.320856E+09 | 549.49 | 12-JAN-14:00 | -5.6 | -8.1 |
February | 0.666773E+09 | 5540.69 | 28-FEB-13:40 | 0.00 | -2.9 | 0.295652E+09 | 549.49 | 28-FEB-14:00 | 0.00 | -2.8 |
March | 0.213940E+10 | 8521.15 | 15-MAR-13:30 | 25.55 | 15.84 | 0.393482E+09 | 549.72 | 15-MAR-13:39 | 25.73 | 15.91 |
April | 0.259816E+10 | 7468.05 | 24-APR-13:10 | 11.38 | 6.04 | 0.362697E+09 | 549.52 | 21-APR-13:00 | 11.38 | 6.04 |
May | 0.393787E+10 | 7014.62 | 26-MAY-13:30 | 20.85 | 13.56 | 0.422681E+09 | 549.51 | 05-MAY-13:09 | 20.85 | 13.56 |
June | 0.545549E+10 | 11356.87 | 18-JUN-13:53 | 25.60 | 21.03 | 0.433419E+09 | 549.53 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.639600E+10 | 14894.96 | 30-JUL-12:32 | 25.60 | 19.52 | 0.405311E+09 | 550.05 | 17-JUL-13:50 | 25.60 | 19.52 |
August | 0.680454E+10 | 14384.37 | 13-AUG-13:13 | 30.00 | 22.88 | 0.453796E+09 | 549.98 | 03-AUG-13:00 | 30.00 | 22.88 |
September | 0.550815E+10 | 14611.07 | 04-SEP-14:13 | 18.17 | 13.03 | 0.397897E+09 | 550.17 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.327959E+10 | 11129.15 | 11-OCT-12:30 | 21.95 | 13.79 | 0.389121E+09 | 549.78 | 11-OCT-13:50 | 22.20 | 14.14 |
November | 0.154876E+10 | 7527.25 | 03-NOV-12:25 | 8.35 | 4.56 | 0.342023E+09 | 549.50 | 01-NOV-13:00 | 8.35 | 4.56 |
December | 0.439683E+09 | 3638.47 | 16-DEC-13:30 | 5.60 | 3.03 | 0.303505E+09 | 549.48 | 04-DEC-14:09 | 5.60 | 3.03 |
Annual Sum or Average | 0.392847E+11 | 0.452044E+10 | ||||||||
Minimum of Months | 0.439683E+09 | 3638.47 | -6.7 | -9.2 | 0.295652E+09 | 549.48 | -5.6 | -8.1 | ||
Maximum of Months | 0.680454E+10 | 14894.96 | 30.00 | 22.88 | 0.453796E+09 | 550.17 | 30.00 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 84301196.63 | 1174.46 | 12-JAN-16:10 | -6.2 | -8.3 | 0.193561E+09 | 281.46 | 12-JAN-16:19 | -6.3 | -8.3 |
February | 0.170140E+09 | 1550.16 | 28-FEB-16:40 | -0.2 | -2.7 | 0.176997E+09 | 338.47 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.105442E+10 | 2947.35 | 15-MAR-14:20 | 25.93 | 16.12 | 0.228142E+09 | 347.84 | 15-MAR-13:00 | 25.93 | 16.12 |
April | 0.175032E+10 | 5755.49 | 24-APR-16:00 | 13.30 | 7.63 | 0.215145E+09 | 347.85 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.306365E+10 | 10823.37 | 07-MAY-17:53 | 13.90 | 5.26 | 0.260667E+09 | 347.85 | 17-MAY-09:00 | 18.90 | 14.77 |
June | 0.456498E+10 | 13671.02 | 11-JUN-18:22 | 24.45 | 17.38 | 0.272999E+09 | 347.87 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.484460E+10 | 13491.03 | 02-JUL-16:52 | 25.00 | 17.00 | 0.255993E+09 | 347.86 | 03-JUL-13:30 | 25.00 | 16.74 |
August | 0.464023E+10 | 13068.50 | 06-AUG-16:31 | 27.80 | 18.98 | 0.285733E+09 | 347.88 | 02-AUG-13:09 | 27.80 | 18.98 |
September | 0.304364E+10 | 8969.61 | 03-SEP-16:23 | 18.60 | 12.27 | 0.246460E+09 | 347.86 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.168563E+10 | 5441.14 | 11-OCT-16:00 | 21.70 | 14.52 | 0.225699E+09 | 347.84 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.753555E+09 | 1607.10 | 03-NOV-15:00 | 10.00 | 5.48 | 0.200154E+09 | 339.25 | 15-NOV-14:00 | 11.70 | 6.59 |
December | 0.112810E+09 | 1159.05 | 04-DEC-15:50 | -0.5 | -3.2 | 0.186818E+09 | 278.64 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.257683E+11 | 0.274837E+10 | ||||||||
Minimum of Months | 84301196.63 | 1159.05 | -6.2 | -8.3 | 0.176997E+09 | 278.64 | -6.3 | -8.3 | ||
Maximum of Months | 0.484460E+10 | 13671.02 | 27.80 | 18.98 | 0.285733E+09 | 347.88 | 27.80 | 18.98 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342890E+09 | 22704.82 | 02-JAN-05:01 | -0.7 |
February | 15599485.80 | 19270.92 | 06-FEB-07:03 | -14.1 |
March | 297395.30 | 4956.59 | 06-MAR-07:01 | -10.8 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 6845209.53 | 18292.14 | 26-DEC-07:02 | -12.3 |
Annual Sum or Average | 0.365632E+09 | |||
Minimum of Months | 0.00 | 0.00 | -14.1 | |
Maximum of Months | 0.342890E+09 | 22704.82 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.700205E+10 | 14406.70 | 30-JAN-06:12 | -10.2 |
February | 0.593978E+10 | 15433.63 | 06-FEB-06:08 | -13.9 |
March | 0.299324E+10 | 14582.67 | 06-MAR-06:12 | -11.1 |
April | 0.117122E+10 | 11044.24 | 17-APR-05:13 | -4.1 |
May | 0.441588E+09 | 4236.07 | 08-MAY-05:03 | 3.40 |
June | 0.149351E+09 | 4302.46 | 19-JUN-05:03 | 16.70 |
July | 80169897.18 | 5354.72 | 24-JUL-05:03 | 16.10 |
August | 0.131765E+09 | 4891.78 | 01-AUG-05:03 | 11.10 |
September | 0.347269E+09 | 5304.00 | 18-SEP-05:03 | 9.50 |
October | 0.113712E+10 | 8939.02 | 30-OCT-06:02 | -0.4 |
November | 0.247976E+10 | 11509.86 | 24-NOV-06:13 | -3.7 |
December | 0.628287E+10 | 15451.43 | 11-DEC-06:09 | -18.5 |
Annual Sum or Average | 0.281562E+11 | |||
Minimum of Months | 80169897.18 | 4236.07 | -18.5 | |
Maximum of Months | 0.700205E+10 | 15451.43 | 16.70 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324106E+10 | 9606.93 | 02-JAN-07:11 | -1.1 |
February | 0.272352E+10 | 8404.98 | 06-FEB-07:04 | -14.1 |
March | 0.148036E+10 | 6183.14 | 06-MAR-07:11 | -10.5 |
April | 0.659026E+09 | 2994.72 | 17-APR-06:11 | -4.0 |
May | 0.125794E+09 | 2854.39 | 07-MAY-13:28 | 14.70 |
June | 21005755.39 | 2245.04 | 11-JUN-09:02 | 23.48 |
July | 24934426.86 | 2174.18 | 21-JUL-04:03 | 26.52 |
August | 19327627.06 | 3120.40 | 13-AUG-15:12 | 29.80 |
September | 39342658.27 | 3619.16 | 04-SEP-10:53 | 18.90 |
October | 0.637773E+09 | 3867.52 | 09-OCT-11:53 | 11.70 |
November | 0.117284E+10 | 4167.27 | 24-NOV-07:02 | -3.2 |
December | 0.273197E+10 | 8553.20 | 11-DEC-07:11 | -16.1 |
Annual Sum or Average | 0.128770E+11 | |||
Minimum of Months | 19327627.06 | 2174.18 | -16.1 | |
Maximum of Months | 0.324106E+10 | 9606.93 | 29.80 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247621E+10 | 8511.90 | 02-JAN-07:01 | -1.1 |
February | 0.198059E+10 | 4497.55 | 06-FEB-07:01 | -14.1 |
March | 0.106750E+10 | 3656.64 | 06-MAR-09:00 | -8.3 |
April | 0.373889E+09 | 2947.69 | 06-APR-07:17 | 2.60 |
May | 34156077.93 | 3805.73 | 22-MAY-05:03 | 9.08 |
June | 23246881.08 | 4146.21 | 14-JUN-05:03 | 6.78 |
July | 25753060.87 | 2941.28 | 08-JUL-05:03 | 18.30 |
August | 23987892.60 | 3829.89 | 31-AUG-05:03 | 11.20 |
September | 26095699.53 | 4305.68 | 28-SEP-05:03 | 11.78 |
October | 0.293815E+09 | 4458.46 | 06-OCT-05:03 | 10.50 |
November | 0.866319E+09 | 3200.93 | 08-NOV-08:07 | 5.50 |
December | 0.198928E+10 | 4449.10 | 26-DEC-07:01 | -12.3 |
Annual Sum or Average | 0.918085E+10 | |||
Minimum of Months | 23246881.08 | 2941.28 | -14.1 | |
Maximum of Months | 0.247621E+10 | 8511.90 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117004E+10 | 23586.66 | 02-JAN-05:01 | -0.7 |
February | 0.735694E+09 | 21192.87 | 06-FEB-06:01 | -13.9 |
March | 93730385.50 | 20448.50 | 06-MAR-06:01 | -11.1 |
April | 8033635.76 | 18978.05 | 17-APR-06:01 | -4.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 1094216.35 | 18236.94 | 30-OCT-06:01 | -0.4 |
November | 33313776.51 | 19343.83 | 24-NOV-06:01 | -3.8 |
December | 0.540343E+09 | 21193.00 | 26-DEC-06:01 | -12.2 |
Annual Sum or Average | 0.258225E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 0.117004E+10 | 23586.66 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.406369E+10 | 30112.36 | 02-JAN-05:01 | -0.7 |
February | 0.333241E+10 | 30214.23 | 06-FEB-05:11 | -14.6 |
March | 0.101468E+10 | 29000.73 | 06-MAR-05:01 | -11.1 |
April | 0.155551E+09 | 27427.58 | 17-APR-05:01 | -4.0 |
May | 819041.54 | 12285.62 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.120674E+09 | 26625.42 | 30-OCT-05:01 | -0.1 |
November | 0.559924E+09 | 28020.15 | 24-NOV-05:11 | -3.2 |
December | 0.310777E+10 | 30234.49 | 26-DEC-05:11 | -12.2 |
Annual Sum or Average | 0.123555E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.6 | |
Maximum of Months | 0.406369E+10 | 30234.49 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.576630E+10 | 9729.70 | 30-JAN-04:42 | -9.5 |
February | 0.480419E+10 | 10008.11 | 06-FEB-04:32 | -15.0 |
March | 0.209658E+10 | 9507.55 | 06-MAR-03:23 | -10.8 |
April | 0.403694E+09 | 9307.23 | 17-APR-04:01 | -3.4 |
May | 9301268.49 | 7589.24 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 4235419.90 | 7405.91 | 30-SEP-06:03 | 7.30 |
October | 0.334012E+09 | 8917.68 | 30-OCT-04:02 | -0.5 |
November | 0.127030E+10 | 9314.25 | 24-NOV-05:11 | -3.2 |
December | 0.498033E+10 | 9964.52 | 26-DEC-04:32 | -12.0 |
Annual Sum or Average | 0.196689E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.576630E+10 | 10008.11 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335479E+10 | 11103.69 | 09-JAN-05:01 | -9.4 |
February | 0.275213E+10 | 11439.49 | 06-FEB-04:32 | -15.0 |
March | 0.948865E+09 | 10821.50 | 20-MAR-04:01 | -2.8 |
April | 0.164358E+09 | 10724.94 | 17-APR-04:01 | -3.4 |
May | 3594805.10 | 5987.88 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 2478981.97 | 5587.72 | 30-SEP-06:03 | 7.30 |
October | 0.173172E+09 | 10277.85 | 30-OCT-04:02 | -0.5 |
November | 0.728464E+09 | 10751.40 | 24-NOV-05:11 | -3.2 |
December | 0.309592E+10 | 11410.85 | 26-DEC-04:32 | -12.0 |
Annual Sum or Average | 0.112238E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.335479E+10 | 11439.49 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.416049E+10 | 13870.79 | 30-JAN-04:42 | -9.5 |
February | 0.353525E+10 | 14311.67 | 06-FEB-04:32 | -15.0 |
March | 0.123756E+10 | 13429.80 | 20-MAR-04:01 | -2.8 |
April | 0.338053E+09 | 13207.38 | 17-APR-04:01 | -3.4 |
May | 14279030.94 | 10962.48 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 3494142.76 | 8484.25 | 30-SEP-06:03 | 7.30 |
October | 0.224044E+09 | 12688.58 | 30-OCT-04:02 | -0.5 |
November | 0.924559E+09 | 13414.28 | 24-NOV-05:11 | -3.2 |
December | 0.379258E+10 | 14289.36 | 26-DEC-04:32 | -12.0 |
Annual Sum or Average | 0.142303E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.416049E+10 | 14311.67 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363404E+10 | 12161.60 | 09-JAN-05:01 | -9.4 |
February | 0.300135E+10 | 12507.64 | 06-FEB-04:32 | -15.0 |
March | 0.113669E+10 | 11836.55 | 20-MAR-04:01 | -2.8 |
April | 0.249155E+09 | 11512.00 | 17-APR-04:01 | -3.4 |
May | 9833566.61 | 9574.76 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 3525649.18 | 5461.28 | 30-SEP-06:03 | 7.30 |
October | 0.208062E+09 | 11125.55 | 30-OCT-04:02 | -0.5 |
November | 0.807160E+09 | 11736.87 | 24-NOV-05:11 | -3.2 |
December | 0.316903E+10 | 12466.09 | 26-DEC-04:32 | -12.0 |
Annual Sum or Average | 0.122188E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.363404E+10 | 12507.64 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.384924E+10 | 7288.49 | 02-JAN-02:63 | -1.7 |
February | 0.312624E+10 | 7316.52 | 06-FEB-05:01 | -14.8 |
March | 0.140044E+10 | 7227.05 | 06-MAR-05:01 | -11.1 |
April | 0.187404E+09 | 6551.51 | 17-APR-05:01 | -4.0 |
May | 2950360.58 | 5852.69 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 18148720.63 | 5902.35 | 30-OCT-06:01 | -0.4 |
November | 0.200322E+09 | 6391.43 | 24-NOV-06:01 | -3.8 |
December | 0.243433E+10 | 7239.39 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.112191E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.384924E+10 | 7316.52 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219727E+10 | 8735.93 | 09-JAN-05:01 | -9.4 |
February | 0.168775E+10 | 8858.85 | 06-FEB-05:01 | -14.8 |
March | 0.470785E+09 | 8507.54 | 06-MAR-05:01 | -11.1 |
April | 46212095.08 | 7900.70 | 17-APR-05:01 | -4.0 |
May | 344532.94 | 1707.80 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 8729517.10 | 7164.19 | 30-OCT-06:01 | -0.4 |
November | 0.109980E+09 | 7800.15 | 24-NOV-06:01 | -3.8 |
December | 0.148606E+10 | 8810.51 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.600713E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.219727E+10 | 8858.85 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.862408E+10 | 14101.61 | 04-JAN-08:00 | -13.3 |
February | 0.748504E+10 | 15037.67 | 07-FEB-07:10 | -16.5 |
March | 0.448932E+10 | 14070.00 | 07-MAR-07:10 | -12.9 |
April | 0.241112E+10 | 12166.45 | 17-APR-06:10 | -4.2 |
May | 0.105575E+10 | 10596.15 | 01-MAY-06:10 | 2.35 |
June | 0.287326E+09 | 9203.35 | 14-JUN-06:10 | 7.67 |
July | 55453102.55 | 7565.95 | 03-JUL-06:06 | 12.77 |
August | 0.134142E+09 | 8556.88 | 03-AUG-06:05 | 11.57 |
September | 0.413946E+09 | 9091.27 | 06-SEP-06:10 | 6.28 |
October | 0.150020E+10 | 11489.76 | 17-OCT-06:10 | -2.8 |
November | 0.316367E+10 | 11982.36 | 24-NOV-07:10 | -3.2 |
December | 0.734918E+10 | 15054.32 | 11-DEC-07:10 | -16.4 |
Annual Sum or Average | 0.369692E+11 | |||
Minimum of Months | 55453102.55 | 7565.95 | -16.5 | |
Maximum of Months | 0.862408E+10 | 15054.32 | 12.77 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242762E+10 | 9263.80 | 09-JAN-05:01 | -9.4 |
February | 0.188786E+10 | 9295.25 | 06-FEB-05:01 | -14.8 |
March | 0.545581E+09 | 8925.66 | 06-MAR-05:01 | -11.1 |
April | 73524165.09 | 8101.36 | 17-APR-05:01 | -4.0 |
May | 1292330.98 | 7393.89 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 9269455.51 | 7497.95 | 30-OCT-06:01 | -0.4 |
November | 0.118998E+09 | 8101.67 | 24-NOV-06:01 | -3.8 |
December | 0.153669E+10 | 9242.62 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.660083E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.242762E+10 | 9295.25 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342719E+10 | 8109.65 | 30-JAN-04:42 | -9.5 |
February | 0.270415E+10 | 8226.39 | 06-FEB-05:01 | -14.8 |
March | 0.893391E+09 | 8027.84 | 06-MAR-05:11 | -11.1 |
April | 92741634.98 | 7296.87 | 17-APR-05:01 | -4.0 |
May | 155938.95 | 2339.08 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 55153129.79 | 7012.00 | 30-OCT-05:01 | -0.1 |
November | 0.356160E+09 | 7256.76 | 24-NOV-06:01 | -3.8 |
December | 0.266354E+10 | 8243.91 | 11-DEC-04:22 | -17.2 |
Annual Sum or Average | 0.101925E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.342719E+10 | 8243.91 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199295E+10 | 9346.09 | 24-JAN-05:01 | -11.8 |
February | 0.153541E+10 | 9525.96 | 06-FEB-05:01 | -14.8 |
March | 0.362138E+09 | 9262.43 | 06-MAR-05:11 | -11.1 |
April | 34450786.70 | 8335.08 | 17-APR-05:01 | -4.0 |
May | 57555.77 | 383.71 | 02-MAY-06:03 | 7.98 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 170953.87 | 1139.69 | 30-SEP-06:03 | 7.30 |
October | 34791502.68 | 7980.78 | 30-OCT-05:01 | -0.1 |
November | 0.216155E+09 | 8297.66 | 24-NOV-06:01 | -3.8 |
December | 0.169244E+10 | 9511.12 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.586856E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.199295E+10 | 9525.96 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227408E+10 | 12033.24 | 24-JAN-05:01 | -11.8 |
February | 0.180154E+10 | 12321.68 | 06-FEB-05:01 | -14.8 |
March | 0.416541E+09 | 11773.26 | 06-MAR-05:11 | -11.1 |
April | 74609484.83 | 10782.21 | 17-APR-05:01 | -4.0 |
May | 529858.78 | 7947.88 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 36425654.42 | 10407.74 | 30-OCT-05:01 | -0.1 |
November | 0.237489E+09 | 10890.35 | 24-NOV-06:01 | -3.8 |
December | 0.181052E+10 | 12296.67 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.665174E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.227408E+10 | 12321.68 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213516E+10 | 9466.81 | 24-JAN-05:01 | -11.8 |
February | 0.165385E+10 | 9633.94 | 06-FEB-05:01 | -14.8 |
March | 0.442276E+09 | 9317.02 | 06-MAR-05:11 | -11.1 |
April | 55874286.01 | 8206.32 | 17-APR-05:01 | -4.0 |
May | 501916.27 | 5701.68 | 01-MAY-06:01 | 2.35 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
September | 52041.26 | 346.94 | 30-SEP-06:03 | 7.30 |
October | 38189261.01 | 7940.52 | 30-OCT-05:01 | -0.1 |
November | 0.233337E+09 | 8346.75 | 24-NOV-06:01 | -3.8 |
December | 0.167684E+10 | 9590.89 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.623608E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.213516E+10 | 9633.94 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.562632E+09 | 889.66 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.474709E+09 | 793.58 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.526049E+09 | 670.92 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.451395E+09 | 587.89 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.473419E+09 | 481.23 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.462737E+09 | 444.55 | 19-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.437261E+09 | 475.31 | 11-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.493727E+09 | 480.74 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.463958E+09 | 649.16 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.511790E+09 | 864.03 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.562918E+09 | 889.66 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.564674E+09 | 889.66 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.598527E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.437261E+09 | 444.55 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.564674E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.347377E+09 | 563.23 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.297662E+09 | 506.06 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330962E+09 | 381.31 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.286070E+09 | 309.81 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.301538E+09 | 291.74 | 11-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.295021E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.278475E+09 | 289.28 | 17-JUL-15:39 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.314135E+09 | 301.64 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.292560E+09 | 365.91 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.318961E+09 | 495.14 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.348351E+09 | 563.23 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.347522E+09 | 563.23 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.375863E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.278475E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.348351E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.535474E+09 | 889.66 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.463458E+09 | 778.70 | 01-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.519980E+09 | 654.68 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.452319E+09 | 583.38 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.476984E+09 | 483.26 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.466835E+09 | 453.23 | 19-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.441043E+09 | 477.64 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.496180E+09 | 482.15 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.461575E+09 | 636.88 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.498781E+09 | 775.50 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.538051E+09 | 889.66 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.537849E+09 | 889.66 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.588853E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.441043E+09 | 453.23 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.538051E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.346510E+09 | 563.19 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.296398E+09 | 500.18 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.331284E+09 | 443.25 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.286400E+09 | 394.34 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.300577E+09 | 311.22 | 11-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.293962E+09 | 300.34 | 21-JUN-08:09 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.277949E+09 | 308.37 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.313197E+09 | 312.86 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293547E+09 | 429.60 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.321620E+09 | 546.99 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.347254E+09 | 563.19 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.348143E+09 | 563.19 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.375684E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.277949E+09 | 300.34 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.348143E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.559258E+09 | 889.66 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.472950E+09 | 789.22 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.524436E+09 | 660.80 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.450798E+09 | 574.17 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.472679E+09 | 477.75 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.462407E+09 | 424.37 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.436874E+09 | 471.53 | 11-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.493099E+09 | 477.23 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.462784E+09 | 638.17 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.509737E+09 | 862.46 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.559891E+09 | 889.66 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.561316E+09 | 889.66 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.596623E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.436874E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.561316E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.346161E+09 | 563.23 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.296927E+09 | 504.01 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330353E+09 | 373.87 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.285746E+09 | 307.98 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.301075E+09 | 289.05 | 11-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.294722E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.278184E+09 | 287.17 | 17-JUL-15:39 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.313740E+09 | 299.56 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.292053E+09 | 357.91 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.318183E+09 | 489.95 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.347083E+09 | 563.23 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.346432E+09 | 563.23 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.375066E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.278184E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.347083E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.534011E+09 | 889.66 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.462613E+09 | 773.47 | 01-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.519222E+09 | 643.63 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.451682E+09 | 569.43 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.476119E+09 | 479.90 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.466273E+09 | 448.37 | 19-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.440409E+09 | 474.02 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.495440E+09 | 478.72 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.460661E+09 | 625.21 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.497940E+09 | 769.36 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.536706E+09 | 889.66 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.536230E+09 | 889.66 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.587731E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.440409E+09 | 448.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.536706E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.345121E+09 | 563.19 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.295684E+09 | 497.93 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330608E+09 | 438.96 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.285925E+09 | 388.35 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.300127E+09 | 309.57 | 11-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.293659E+09 | 298.65 | 21-JUN-08:09 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.277654E+09 | 306.62 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.312695E+09 | 311.30 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.292954E+09 | 424.85 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.320699E+09 | 546.14 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.346044E+09 | 563.19 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.346760E+09 | 563.19 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.374793E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.277654E+09 | 298.65 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.346760E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.562629E+09 | 889.66 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.474707E+09 | 793.57 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.526048E+09 | 670.90 | 17-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.451395E+09 | 587.87 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.473418E+09 | 481.22 | 11-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.462736E+09 | 444.54 | 19-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.437257E+09 | 475.30 | 11-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.493726E+09 | 480.74 | 24-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.463946E+09 | 649.14 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.511788E+09 | 864.03 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.562914E+09 | 889.66 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.564648E+09 | 889.66 | 01-DEC-16:40 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.598521E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.437257E+09 | 444.54 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.564648E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.347375E+09 | 563.23 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.297661E+09 | 506.06 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330962E+09 | 381.30 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.286070E+09 | 309.81 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.301538E+09 | 291.74 | 11-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.295021E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.278475E+09 | 289.28 | 17-JUL-15:39 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.314134E+09 | 301.63 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.292559E+09 | 365.90 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.318953E+09 | 495.14 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.348350E+09 | 563.23 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.347520E+09 | 563.23 | 01-DEC-16:40 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.375862E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.278475E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.348350E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.535473E+09 | 889.66 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.463458E+09 | 778.70 | 01-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.519979E+09 | 654.66 | 17-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.452318E+09 | 583.36 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.476983E+09 | 483.25 | 11-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.466834E+09 | 453.22 | 19-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.441042E+09 | 477.64 | 11-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.496180E+09 | 482.14 | 24-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.461574E+09 | 636.86 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.498781E+09 | 775.50 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.538019E+09 | 889.66 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.537847E+09 | 889.66 | 01-DEC-16:40 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.588849E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.441042E+09 | 453.22 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.538019E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.346509E+09 | 563.19 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.296397E+09 | 500.18 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.331283E+09 | 443.24 | 17-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.286399E+09 | 394.33 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.300576E+09 | 311.22 | 11-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.293962E+09 | 300.34 | 21-JUN-08:09 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.277949E+09 | 308.36 | 11-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.313196E+09 | 312.86 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293547E+09 | 429.59 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.321619E+09 | 546.99 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.347253E+09 | 563.19 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.348142E+09 | 563.19 | 01-DEC-16:40 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.375683E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.277949E+09 | 300.34 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.348142E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.562632E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757622E+09 |
February | 0.901968E+09 | 0.474709E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806154E+09 |
March | 0.107774E+10 | 0.526049E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 204597.00 | 0.494970E+09 |
April | 0.956342E+09 | 0.451395E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401647E+09 |
May | 0.103597E+10 | 0.473419E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198238.91 | 0.247512E+09 |
June | 0.103308E+10 | 0.462737E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4507675.39 | 0.145562E+09 |
July | 0.959235E+09 | 0.437261E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10816381.61 | 86454936.42 |
August | 0.107774E+10 | 0.493727E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8826287.99 | 99026740.24 |
September | 0.956342E+09 | 0.463958E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 600827.55 | 0.143360E+09 |
October | 0.994195E+09 | 0.511790E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302785E+09 |
November | 0.984487E+09 | 0.562918E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406848E+09 |
December | 0.959235E+09 | 0.564674E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.800693E+09 |
Annual Sum or Average | 0.119305E+11 | 0.598527E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25154008.45 | 0.469263E+10 |
Minimum of Months | 0.901968E+09 | 0.437261E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86454936.42 |
Maximum of Months | 0.107774E+10 | 0.564674E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10816381.61 | 0.806154E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.347377E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506182E+09 |
February | 0.571020E+09 | 0.297662E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538515E+09 |
March | 0.682301E+09 | 0.330962E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 118051.98 | 0.333156E+09 |
April | 0.605444E+09 | 0.286070E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273162E+09 |
May | 0.655854E+09 | 0.301538E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138018.16 | 0.170352E+09 |
June | 0.654023E+09 | 0.295021E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2950323.19 | 98904771.53 |
July | 0.607275E+09 | 0.278475E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7082708.25 | 58608856.31 |
August | 0.682301E+09 | 0.314135E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5693360.81 | 67292202.04 |
September | 0.605444E+09 | 0.292560E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 422092.87 | 97822074.85 |
October | 0.629407E+09 | 0.318961E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207044E+09 |
November | 0.623262E+09 | 0.348351E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273139E+09 |
December | 0.607275E+09 | 0.347522E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534675E+09 |
Annual Sum or Average | 0.755301E+10 | 0.375863E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16404555.27 | 0.315885E+10 |
Minimum of Months | 0.571020E+09 | 0.278475E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58608856.31 |
Maximum of Months | 0.682301E+09 | 0.348351E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7082708.25 | 0.538515E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.535474E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773124E+09 |
February | 0.901968E+09 | 0.463458E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817200E+09 |
March | 0.107774E+10 | 0.519980E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 175017.32 | 0.520520E+09 |
April | 0.956342E+09 | 0.452319E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417740E+09 |
May | 0.103597E+10 | 0.476984E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80755.50 | 0.255750E+09 |
June | 0.103308E+10 | 0.466835E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4297302.55 | 0.146775E+09 |
July | 0.959235E+09 | 0.441043E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10474708.51 | 88391315.98 |
August | 0.107774E+10 | 0.496180E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7965590.07 | 0.103217E+09 |
September | 0.956342E+09 | 0.461575E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 531859.77 | 0.152922E+09 |
October | 0.994195E+09 | 0.498781E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326347E+09 |
November | 0.984487E+09 | 0.538051E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423308E+09 |
December | 0.959235E+09 | 0.537849E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817404E+09 |
Annual Sum or Average | 0.119305E+11 | 0.588853E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23525233.72 | 0.484270E+10 |
Minimum of Months | 0.901968E+09 | 0.441043E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88391315.98 |
Maximum of Months | 0.107774E+10 | 0.538051E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10474708.51 | 0.817404E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.346510E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505975E+09 |
February | 0.570983E+09 | 0.296398E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539314E+09 |
March | 0.682256E+09 | 0.331284E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171156.12 | 0.338671E+09 |
April | 0.605404E+09 | 0.286400E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276201E+09 |
May | 0.655811E+09 | 0.300577E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53843.48 | 0.171657E+09 |
June | 0.653980E+09 | 0.293962E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3074885.98 | 0.100937E+09 |
July | 0.607235E+09 | 0.277949E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7260770.33 | 60798009.25 |
August | 0.682256E+09 | 0.313197E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5926285.06 | 69525476.39 |
September | 0.605404E+09 | 0.293547E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 358694.62 | 98258163.41 |
October | 0.629366E+09 | 0.321620E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204964E+09 |
November | 0.623221E+09 | 0.347254E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271863E+09 |
December | 0.607235E+09 | 0.348143E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534399E+09 |
Annual Sum or Average | 0.755252E+10 | 0.375684E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16845635.57 | 0.317256E+10 |
Minimum of Months | 0.570983E+09 | 0.277949E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60798009.25 |
Maximum of Months | 0.682256E+09 | 0.348143E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7260770.33 | 0.539314E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.559258E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420997E+09 |
February | 0.901968E+09 | 0.472950E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445691E+09 |
March | 0.107774E+10 | 0.524436E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 246712.96 | 0.271748E+09 |
April | 0.956342E+09 | 0.450798E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216155E+09 |
May | 0.103597E+10 | 0.472679E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 213109.88 | 0.125714E+09 |
June | 0.103308E+10 | 0.462407E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3455381.43 | 74411087.09 |
July | 0.959235E+09 | 0.436874E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6808605.37 | 42750294.82 |
August | 0.107774E+10 | 0.493099E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5762094.63 | 51962058.19 |
September | 0.956342E+09 | 0.462784E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 365134.48 | 80639007.02 |
October | 0.994195E+09 | 0.509737E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180920E+09 |
November | 0.984487E+09 | 0.559891E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240134E+09 |
December | 0.959235E+09 | 0.561316E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454746E+09 |
Annual Sum or Average | 0.119305E+11 | 0.596623E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16851038.75 | 0.260587E+10 |
Minimum of Months | 0.901968E+09 | 0.436874E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42750294.82 |
Maximum of Months | 0.107774E+10 | 0.561316E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6808605.37 | 0.454746E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.346161E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281995E+09 |
February | 0.571020E+09 | 0.296927E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298084E+09 |
March | 0.682301E+09 | 0.330353E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103941.44 | 0.184275E+09 |
April | 0.605444E+09 | 0.285746E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150782E+09 |
May | 0.655854E+09 | 0.301075E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73983.45 | 91149627.84 |
June | 0.654023E+09 | 0.294722E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1704769.91 | 52991088.24 |
July | 0.607275E+09 | 0.278184E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4012289.50 | 31052572.58 |
August | 0.682301E+09 | 0.313740E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3253854.51 | 37123044.62 |
September | 0.605444E+09 | 0.292053E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 231625.49 | 56562687.89 |
October | 0.629407E+09 | 0.318183E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125476E+09 |
November | 0.623262E+09 | 0.347083E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162112E+09 |
December | 0.607275E+09 | 0.346432E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303648E+09 |
Annual Sum or Average | 0.755301E+10 | 0.375066E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9380464.30 | 0.177525E+10 |
Minimum of Months | 0.571020E+09 | 0.278184E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31052572.58 |
Maximum of Months | 0.682301E+09 | 0.347083E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4012289.50 | 0.303648E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.534011E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938154E+10 |
February | 0.901968E+09 | 0.462613E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858384E+10 |
March | 0.107774E+10 | 0.519222E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12250391.62 | 0.734611E+10 |
April | 0.956342E+09 | 0.451682E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497711E+10 |
May | 0.103597E+10 | 0.476119E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3831964.04 | 0.322812E+10 |
June | 0.103308E+10 | 0.466273E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193817E+09 | 0.170401E+10 |
July | 0.959235E+09 | 0.440409E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541166E+09 | 0.672533E+09 |
August | 0.107774E+10 | 0.495440E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415316E+09 | 0.121517E+10 |
September | 0.956342E+09 | 0.460661E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20873827.38 | 0.214219E+10 |
October | 0.994195E+09 | 0.497940E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461704E+10 |
November | 0.984487E+09 | 0.536706E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593076E+10 |
December | 0.959235E+09 | 0.536230E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855719E+10 |
Annual Sum or Average | 0.119305E+11 | 0.587731E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118726E+10 | 0.583556E+11 |
Minimum of Months | 0.901968E+09 | 0.440409E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672533E+09 |
Maximum of Months | 0.107774E+10 | 0.536706E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541166E+09 | 0.938154E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.345121E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281028E+09 |
February | 0.570983E+09 | 0.295684E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298329E+09 |
March | 0.682256E+09 | 0.330608E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 144190.77 | 0.186849E+09 |
April | 0.605404E+09 | 0.285925E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151052E+09 |
May | 0.655811E+09 | 0.300127E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33639.10 | 92489878.05 |
June | 0.653980E+09 | 0.293659E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1690732.29 | 54980530.28 |
July | 0.607235E+09 | 0.277654E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4089675.94 | 32899884.17 |
August | 0.682256E+09 | 0.312695E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3213147.06 | 38771246.76 |
September | 0.605404E+09 | 0.292954E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 192638.71 | 57197258.74 |
October | 0.629366E+09 | 0.320699E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123733E+09 |
November | 0.623221E+09 | 0.346044E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161209E+09 |
December | 0.607235E+09 | 0.346760E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303383E+09 |
Annual Sum or Average | 0.755252E+10 | 0.374793E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9364023.89 | 0.178192E+10 |
Minimum of Months | 0.570983E+09 | 0.277654E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32899884.17 |
Maximum of Months | 0.682256E+09 | 0.346760E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4089675.94 | 0.303383E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.562629E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653633E+09 |
February | 0.901968E+09 | 0.474707E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694273E+09 |
March | 0.107774E+10 | 0.526048E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 177363.70 | 0.433760E+09 |
April | 0.956342E+09 | 0.451395E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354722E+09 |
May | 0.103597E+10 | 0.473418E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 252389.07 | 0.215802E+09 |
June | 0.103308E+10 | 0.462736E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4161362.34 | 0.124802E+09 |
July | 0.959235E+09 | 0.437257E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9421196.22 | 73400842.84 |
August | 0.107774E+10 | 0.493726E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7753123.41 | 85165556.51 |
September | 0.956342E+09 | 0.463946E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 525430.42 | 0.127224E+09 |
October | 0.994195E+09 | 0.511788E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275795E+09 |
November | 0.984487E+09 | 0.562914E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366580E+09 |
December | 0.959235E+09 | 0.564648E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697695E+09 |
Annual Sum or Average | 0.119305E+11 | 0.598521E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22290865.16 | 0.410285E+10 |
Minimum of Months | 0.901968E+09 | 0.437257E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73400842.84 |
Maximum of Months | 0.107774E+10 | 0.564648E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9421196.22 | 0.697695E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.347375E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437122E+09 |
February | 0.421807E+09 | 0.297661E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463517E+09 |
March | 0.502994E+09 | 0.330962E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107381.81 | 0.292070E+09 |
April | 0.447140E+09 | 0.286070E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239986E+09 |
May | 0.484071E+09 | 0.301538E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170693.52 | 0.147612E+09 |
June | 0.482240E+09 | 0.295021E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2636140.75 | 84423735.72 |
July | 0.448971E+09 | 0.278475E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6132527.25 | 49669943.79 |
August | 0.502994E+09 | 0.314134E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5007890.66 | 57627612.41 |
September | 0.447140E+09 | 0.292559E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 369588.25 | 86009799.38 |
October | 0.465148E+09 | 0.318953E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187087E+09 |
November | 0.460569E+09 | 0.348350E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245176E+09 |
December | 0.448971E+09 | 0.347520E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465727E+09 |
Annual Sum or Average | 0.557719E+10 | 0.375862E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14424222.24 | 0.275603E+10 |
Minimum of Months | 0.421807E+09 | 0.278475E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49669943.79 |
Maximum of Months | 0.502994E+09 | 0.348350E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6132527.25 | 0.465727E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.535473E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670938E+09 |
February | 0.901968E+09 | 0.463458E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706188E+09 |
March | 0.107774E+10 | 0.519979E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 149804.67 | 0.457117E+09 |
April | 0.956342E+09 | 0.452318E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368041E+09 |
May | 0.103597E+10 | 0.476983E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68669.03 | 0.222886E+09 |
June | 0.103308E+10 | 0.466834E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3682517.47 | 0.126443E+09 |
July | 0.959235E+09 | 0.441042E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8931650.94 | 75685826.55 |
August | 0.107774E+10 | 0.496180E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6761683.93 | 89053705.98 |
September | 0.956342E+09 | 0.461574E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 453075.54 | 0.134734E+09 |
October | 0.994195E+09 | 0.498781E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294688E+09 |
November | 0.984487E+09 | 0.538019E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381101E+09 |
December | 0.959235E+09 | 0.537847E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714916E+09 |
Annual Sum or Average | 0.119305E+11 | 0.588849E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20047401.58 | 0.424179E+10 |
Minimum of Months | 0.901968E+09 | 0.441042E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75685826.55 |
Maximum of Months | 0.107774E+10 | 0.538019E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8931650.94 | 0.714916E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.346509E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436071E+09 |
February | 0.570983E+09 | 0.296397E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464094E+09 |
March | 0.682256E+09 | 0.331283E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139532.82 | 0.296746E+09 |
April | 0.605404E+09 | 0.286399E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243034E+09 |
May | 0.655811E+09 | 0.300576E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45785.01 | 0.149766E+09 |
June | 0.653980E+09 | 0.293962E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2630546.00 | 87067091.78 |
July | 0.607235E+09 | 0.277949E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6202128.40 | 52264317.95 |
August | 0.682256E+09 | 0.313196E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4961627.38 | 60082046.09 |
September | 0.605404E+09 | 0.293547E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 295241.79 | 87204965.04 |
October | 0.629366E+09 | 0.321619E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185867E+09 |
November | 0.623221E+09 | 0.347253E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244330E+09 |
December | 0.607235E+09 | 0.348142E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465368E+09 |
Annual Sum or Average | 0.755252E+10 | 0.375683E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14274861.39 | 0.277189E+10 |
Minimum of Months | 0.570983E+09 | 0.277949E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52264317.95 |
Maximum of Months | 0.682256E+09 | 0.348142E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6202128.40 | 0.465368E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892302E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944637E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278624.10 | 0.600052E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489046E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245603.76 | 0.289641E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4112499.06 | 0.166950E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10076075.92 | 96707234.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8422936.72 | 0.115475E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421967.85 | 0.177408E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392195E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520225E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964176E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23557707.41 | 0.564881E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96707234.11 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10076075.92 | 0.964176E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110544E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116980E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418000.19 | 0.744020E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608891E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404915.15 | 0.367028E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5434939.82 | 0.213954E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12772275.85 | 0.124364E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10960351.65 | 0.146895E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588377.78 | 0.220215E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470882E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622473E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118179E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30578860.44 | 0.697576E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124364E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12772275.85 | 0.118179E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112560E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119908E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19720.58 | 0.757917E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624640E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10074.46 | 0.392274E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2989967.92 | 0.231773E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9344240.76 | 0.137788E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6541780.30 | 0.155661E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270220.78 | 0.227492E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468376E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613454E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119231E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19176004.80 | 0.712636E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137788E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9344240.76 | 0.119908E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1435.78 | 12-JAN-05:57 |
February | 1306.65 | 01-FEB-10:09 | 793.58 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1501.88 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 670.92 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 | 15-MAR-14:00 | 809.26 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 587.89 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 749.83 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 481.23 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 14-MAY-15:00 | 501.57 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 444.55 | 19-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.78 | 17-JUN-17:03 | 432.16 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 475.31 | 11-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.31 | 21-JUL-03:00 | 311.12 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 480.74 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.30 | 13-AUG-12:55 | 195.66 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 649.16 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 | 16-SEP-17:03 | 339.54 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 864.03 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 408.97 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 749.27 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1362.88 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 444.55 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.66 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 155.30 | 1501.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 957.18 | 12-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 506.06 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1001.25 | 13-FEB-06:00 |
March | 827.22 | 01-MAR-10:09 | 381.31 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 15-MAR-14:00 | 543.51 | 02-MAR-01:00 |
April | 827.22 | 03-APR-09:09 | 309.81 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 500.20 | 16-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 291.74 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.41 | 14-MAY-15:00 | 366.60 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.59 | 17-JUN-17:20 | 289.39 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 289.28 | 17-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.65 | 15-JUL-15:00 | 206.56 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 301.64 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.56 | 13-AUG-13:20 | 127.23 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 365.91 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 | 16-SEP-17:03 | 223.56 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 495.14 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 285.26 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 496.29 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 904.21 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.23 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 107.56 | 1001.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1435.78 | 12-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 778.70 | 01-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1501.89 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 654.68 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 | 15-MAR-14:00 | 895.72 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 583.38 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 751.96 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 483.26 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 10-MAY-14:00 | 545.71 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 453.23 | 19-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.08 | 17-JUN-17:03 | 435.45 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 477.64 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.97 | 15-JUL-15:00 | 312.33 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 482.15 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.34 | 13-AUG-13:18 | 195.35 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 636.88 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 | 16-SEP-13:00 | 341.06 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 775.50 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 429.08 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 759.87 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1372.12 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 453.23 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.35 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 138.34 | 1501.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 957.18 | 12-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 500.18 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1001.25 | 13-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 443.25 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 15-MAR-14:00 | 594.41 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 394.34 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 495.78 | 16-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 311.22 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | 10-MAY-14:00 | 378.57 | 29-MAY-15:00 |
June | 827.17 | 01-JUN-09:09 | 300.34 | 21-JUN-08:09 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.86 | 12-JUN-13:00 | 290.90 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 308.37 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.92 | 16-JUL-10:20 | 210.28 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 312.86 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.66 | 13-AUG-12:43 | 153.27 | 27-AUG-16:40 |
September | 827.17 | 01-SEP-09:09 | 429.60 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.37 | 16-SEP-13:00 | 222.55 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 546.99 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 273.05 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 494.69 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 905.30 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 300.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.27 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 115.66 | 1001.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 761.83 | 12-JAN-05:53 |
February | 1306.65 | 01-FEB-10:09 | 789.22 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 797.02 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 660.80 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.25 | 14-MAR-14:00 | 454.83 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 574.17 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 438.94 | 16-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 477.75 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.52 | 14-MAY-15:00 | 234.81 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.00 | 17-JUN-17:03 | 231.97 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 471.53 | 11-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.98 | 21-JUL-03:00 | 169.46 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 477.23 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.78 | 13-AUG-13:00 | 108.52 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 638.17 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 16-SEP-17:03 | 206.63 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 862.46 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 261.17 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 444.98 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 758.17 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.52 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 97.78 | 797.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 507.88 | 12-JAN-05:55 |
February | 827.22 | 01-FEB-10:09 | 504.01 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 531.35 | 13-FEB-05:53 |
March | 827.22 | 01-MAR-10:09 | 373.87 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 14-MAR-14:00 | 311.24 | 02-MAR-01:00 |
April | 827.22 | 03-APR-09:09 | 307.98 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 293.86 | 16-APR-07:00 |
May | 827.22 | 01-MAY-09:09 | 289.05 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.85 | 14-MAY-15:10 | 176.94 | 29-MAY-14:00 |
June | 827.22 | 01-JUN-09:09 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 | 17-JUN-17:03 | 160.97 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 287.17 | 17-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 | 21-JUL-03:00 | 116.35 | 06-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 299.56 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.92 | 13-AUG-13:00 | 72.04 | 30-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 357.91 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 16-SEP-17:03 | 137.14 | 29-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 489.95 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 180.64 | 08-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 298.76 | 17-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 503.96 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.04 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 55.92 | 531.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 43134.15 | 31-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 773.47 | 01-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 46010.11 | 07-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 643.63 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1220.22 | 15-MAR-12:00 | 43755.59 | 07-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 569.43 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 31483.69 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 479.90 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.24 | 10-MAY-16:10 | 22407.94 | 01-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 448.37 | 19-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6352.41 | 27-JUN-12:00 | 16420.92 | 06-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 474.02 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6596.86 | 19-JUL-16:10 | 11368.52 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 478.72 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6110.31 | 18-AUG-16:05 | 12719.23 | 01-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 625.21 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2563.90 | 15-SEP-12:00 | 19155.73 | 05-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 769.36 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 29801.04 | 17-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 29938.71 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 46858.43 | 11-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 448.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11368.52 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6596.86 | 46858.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 507.88 | 12-JAN-05:55 |
February | 827.17 | 01-FEB-10:09 | 497.93 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 531.35 | 13-FEB-05:53 |
March | 827.17 | 01-MAR-10:09 | 438.96 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 | 15-MAR-12:00 | 315.22 | 02-MAR-01:00 |
April | 827.17 | 03-APR-09:09 | 388.35 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 291.25 | 16-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 309.57 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.15 | 14-MAY-15:10 | 178.09 | 29-MAY-15:00 |
June | 827.17 | 01-JUN-09:09 | 298.65 | 21-JUN-08:09 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 | 17-JUN-17:03 | 162.65 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 306.62 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.01 | 21-JUL-03:00 | 118.92 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 311.30 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.15 | 13-AUG-13:00 | 71.99 | 19-AUG-17:40 |
September | 827.17 | 01-SEP-09:09 | 424.85 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 16-SEP-13:00 | 136.74 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 546.14 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 175.69 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 298.72 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 504.25 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 298.65 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.99 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 57.15 | 531.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1193.96 | 12-JAN-05:53 |
February | 1306.65 | 01-FEB-10:09 | 793.57 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1249.01 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 670.90 | 17-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 | 15-MAR-14:00 | 727.43 | 02-MAR-01:00 |
April | 1306.65 | 03-APR-09:09 | 587.87 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 685.33 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 481.22 | 11-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.91 | 14-MAY-15:00 | 419.62 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 444.54 | 19-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.02 | 17-JUN-17:03 | 372.81 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 475.30 | 11-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.22 | 21-JUL-03:00 | 271.37 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 480.74 | 24-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.54 | 13-AUG-12:55 | 169.34 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 649.14 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 | 16-SEP-17:03 | 313.17 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 864.03 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 388.52 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 680.50 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:40 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1172.91 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 444.54 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.34 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 137.54 | 1249.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 563.23 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 795.97 | 12-JAN-05:53 |
February | 805.43 | 01-FEB-08:09 | 506.06 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 832.67 | 13-FEB-06:00 |
March | 805.43 | 01-MAR-08:09 | 381.30 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | 15-MAR-14:00 | 488.92 | 02-MAR-01:00 |
April | 805.43 | 03-APR-07:10 | 309.81 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 457.37 | 16-APR-07:00 |
May | 805.43 | 01-MAY-07:10 | 291.74 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.98 | 14-MAY-15:00 | 305.96 | 29-MAY-14:00 |
June | 805.43 | 01-JUN-07:10 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.08 | 17-JUN-17:20 | 249.53 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 289.28 | 17-JUL-15:39 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.81 | 21-JUL-03:00 | 180.21 | 06-JUL-02:00 |
August | 805.43 | 01-AUG-07:10 | 301.63 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.99 | 13-AUG-13:20 | 109.89 | 30-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 365.90 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.13 | 16-SEP-17:03 | 206.14 | 29-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 495.14 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 269.24 | 08-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 563.23 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 449.75 | 17-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 563.23 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 777.47 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.89 | |||||
Maximum of Months | 805.43 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 87.99 | 832.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1193.96 | 12-JAN-05:53 |
February | 1306.65 | 01-FEB-10:09 | 778.70 | 01-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1249.01 | 13-FEB-06:00 |
March | 1306.65 | 01-MAR-10:09 | 654.66 | 17-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.27 | 15-MAR-14:00 | 786.72 | 26-MAR-13:00 |
April | 1306.65 | 03-APR-09:09 | 583.36 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 687.02 | 16-APR-02:00 |
May | 1306.65 | 01-MAY-09:09 | 483.25 | 11-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 | 10-MAY-14:00 | 456.86 | 29-MAY-14:00 |
June | 1306.65 | 01-JUN-09:09 | 453.22 | 19-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.26 | 17-JUN-17:03 | 375.49 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 477.64 | 11-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.43 | 21-JUL-03:00 | 272.51 | 06-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 482.14 | 24-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.93 | 13-AUG-13:18 | 169.41 | 30-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 636.86 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 | 16-SEP-13:00 | 314.28 | 29-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 775.50 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 405.16 | 08-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 690.28 | 17-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:40 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1181.85 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 453.22 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.41 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 114.93 | 1249.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 795.97 | 12-JAN-05:53 |
February | 827.17 | 01-FEB-10:09 | 500.18 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 832.67 | 13-FEB-06:00 |
March | 827.17 | 01-MAR-10:09 | 443.24 | 17-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.85 | 15-MAR-14:00 | 504.75 | 25-MAR-17:10 |
April | 827.17 | 03-APR-09:09 | 394.33 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 453.18 | 16-APR-02:00 |
May | 827.17 | 01-MAY-09:09 | 311.22 | 11-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 | 10-MAY-14:00 | 316.47 | 29-MAY-15:00 |
June | 827.17 | 01-JUN-09:09 | 300.34 | 21-JUN-08:09 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 12-JUN-13:00 | 251.00 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 308.36 | 11-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.76 | 16-JUL-11:40 | 183.45 | 06-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 312.86 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.20 | 13-AUG-12:55 | 122.47 | 27-AUG-16:40 |
September | 827.17 | 01-SEP-09:09 | 429.59 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 16-SEP-13:00 | 205.71 | 29-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 546.99 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 259.07 | 08-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 449.11 | 17-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:40 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 778.86 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 300.34 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.47 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 97.20 | 832.67 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1627.63 | 12-JAN-05:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1600.96 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.24 | 15-MAR-14:00 | 1043.35 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 980.77 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.43 | 14-MAY-14:53 | 495.14 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.27 | 17-JUN-17:03 | 502.14 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.97 | 21-JUL-03:00 | 365.52 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.07 | 13-AUG-13:00 | 230.09 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 | 16-SEP-13:00 | 443.30 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 551.18 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 971.24 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1620.15 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.07 | 1627.63 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2033.30 | 12-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1950.11 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 14-MAR-14:00 | 1304.09 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1203.39 | 16-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.70 | 14-MAY-14:53 | 622.65 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.04 | 17-JUN-17:03 | 646.10 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.60 | 21-JUL-03:00 | 466.10 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.25 | 13-AUG-13:00 | 293.48 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.80 | 16-SEP-17:03 | 543.53 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 657.24 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1183.83 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2022.82 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.48 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.25 | 2033.30 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2028.38 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2042.89 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 | 15-MAR-14:00 | 1210.37 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1141.95 | 16-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 | 10-MAY-15:00 | 842.10 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.05 | 17-JUN-17:03 | 654.87 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.87 | 21-JUL-02:00 | 462.05 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.17 | 13-AUG-12:55 | 298.68 | 30-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 | 16-SEP-13:00 | 510.68 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 609.79 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1132.64 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2153.88 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.68 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.17 | 2153.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7653.75 | 20-JAN-17:00 | 6035.01 | 4220.20 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8038.47 | 17-FEB-17:00 | 6035.01 | 4220.20 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16181.67 | 17-MAR-08:00 | 6035.01 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17390.35 | 21-APR-07:04 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39107.53 | 24-MAY-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39307.70 | 01-JUN-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41305.40 | 24-JUL-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41060.91 | 21-AUG-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41753.93 | 18-SEP-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31667.51 | 13-OCT-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17847.71 | 01-NOV-07:04 | 48280.06 | 33761.62 | 145481.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11403.01 | 01-DEC-08:40 | 6035.01 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7653.75 | 0.00 | 1875.67 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41753.93 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.17 |
February | 298.03 | 18-FEB-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.79 |
March | 4671.34 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 0.00 |
April | 3958.52 | 21-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.52 |
May | 6728.31 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.70 |
June | 10042.47 | 27-JUN-14:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.36 |
July | 9806.40 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.08 | 0.00 |
August | 9752.26 | 09-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.31 | 0.00 |
September | 7584.54 | 21-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 0.00 |
October | 3804.94 | 11-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.19 |
November | 999.60 | 04-NOV-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.88 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10042.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.08 | 455.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1978.11 | 04-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.61 |
February | 1734.52 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.45 |
March | 1871.86 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.38 |
April | 2090.30 | 11-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.52 |
May | 2083.73 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.77 |
June | 3982.08 | 12-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.56 | 0.00 |
July | 4757.70 | 17-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 |
August | 4347.09 | 07-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 |
September | 3016.79 | 18-SEP-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.64 |
October | 2161.71 | 24-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.19 |
November | 1272.16 | 02-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.57 |
December | 1621.83 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 752.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1272.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4757.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.56 | 752.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1951.71 | 12-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.40 |
February | 1939.20 | 10-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.46 |
March | 2459.14 | 24-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 |
April | 2493.45 | 11-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.07 |
May | 2381.09 | 30-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.24 |
June | 4290.13 | 12-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.11 | 0.00 |
July | 4931.88 | 17-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 |
August | 4845.71 | 07-AUG-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.79 |
September | 4082.55 | 18-SEP-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 |
October | 2089.73 | 24-OCT-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.79 |
November | 1888.90 | 03-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.70 |
December | 1718.09 | 08-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1718.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4931.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.11 | 293.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5838.99 | 12-JAN-16:50 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5889.01 | 17-FEB-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10032.71 | 16-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9153.44 | 21-APR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20358.43 | 24-MAY-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28890.22 | 19-JUN-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29854.71 | 05-JUL-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29824.05 | 07-AUG-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29018.64 | 18-SEP-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11200.80 | 12-OCT-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7220.10 | 01-NOV-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6188.06 | 01-DEC-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5838.99 | 0.00 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29854.71 | 6035.01 | 4220.20 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5548.98 | 12-JAN-16:30 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5727.07 | 28-FEB-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10167.38 | 16-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9930.14 | 21-APR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14729.88 | 31-MAY-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31046.56 | 19-JUN-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30443.38 | 19-JUL-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32003.82 | 07-AUG-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16791.21 | 18-SEP-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10758.53 | 12-OCT-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6981.13 | 01-NOV-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5863.58 | 01-DEC-15:00 | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5548.98 | 0.00 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32003.82 | 6198.29 | 4220.20 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 986.31 | 14-JAN-16:03 | 535.68 | 461.42 | 2232.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.68 |
February | 986.63 | 18-FEB-16:03 | 401.76 | 212.18 | 1674.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.08 |
March | 3245.79 | 15-MAR-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.92 | 0.00 |
April | 2153.34 | 21-APR-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.34 |
May | 4451.36 | 23-MAY-14:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
June | 6984.82 | 27-JUN-15:47 | 3816.70 | 1273.10 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 0.00 |
July | 10508.57 | 16-JUL-13:32 | 267.84 | 94.29 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 23.82 | 0.00 |
August | 6873.22 | 06-AUG-14:02 | 267.84 | 94.29 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 4.42 | 0.00 |
September | 4471.88 | 15-SEP-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | 0.00 |
October | 2290.47 | 12-OCT-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.20 |
November | 1332.06 | 16-NOV-16:40 | 1272.23 | 850.62 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.27 |
December | 1068.01 | 01-DEC-13:50 | 1272.23 | 451.43 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 986.31 | 267.84 | 94.29 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10508.57 | 3816.70 | 1273.10 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 23.82 | 158.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 912.66 | 14-JAN-16:03 | 339.13 | 293.65 | 1413.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.39 |
February | 1168.52 | 28-FEB-10:10 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.02 |
March | 2553.23 | 15-MAR-14:00 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 0.00 |
April | 4857.77 | 24-APR-09:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 |
May | 7131.46 | 31-MAY-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.55 |
June | 11597.57 | 11-JUN-10:32 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.47 |
July | 12934.32 | 04-JUL-09:02 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.44 |
August | 12257.81 | 06-AUG-08:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.10 |
September | 6005.42 | 18-SEP-09:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 |
October | 3617.39 | 11-OCT-09:40 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.08 |
November | 1346.10 | 03-NOV-09:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.21 |
December | 911.19 | 16-DEC-16:03 | 254.35 | 234.99 | 1060.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 911.19 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12934.32 | 827.22 | 293.65 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 8.13 | 78.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3425.99 | 12-JAN-13:40 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.55 |
February | 5352.43 | 28-FEB-13:50 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.85 |
March | 9117.84 | 15-MAR-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 | 0.00 |
April | 7466.30 | 24-APR-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.05 |
May | 7587.67 | 26-MAY-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.21 |
June | 14395.60 | 18-JUN-13:53 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.43 |
July | 15812.84 | 30-JUL-14:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 |
August | 15989.52 | 13-AUG-13:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 103.56 | 0.00 |
September | 16750.99 | 10-SEP-13:42 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.24 |
October | 11106.07 | 11-OCT-12:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.68 |
November | 6654.16 | 03-NOV-12:35 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.31 |
December | 3158.03 | 16-DEC-13:30 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3158.03 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16750.99 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 103.56 | 362.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1165.83 | 12-JAN-16:10 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.66 |
February | 1613.30 | 28-FEB-16:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.17 |
March | 3276.54 | 15-MAR-14:20 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 0.00 |
April | 5849.22 | 24-APR-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.18 |
May | 11622.01 | 27-MAY-17:06 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.13 |
June | 14128.41 | 11-JUN-16:32 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.48 |
July | 14811.92 | 02-JUL-16:52 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.42 |
August | 13543.24 | 12-AUG-17:05 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 |
September | 14313.46 | 04-SEP-16:42 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.12 |
October | 5539.98 | 11-OCT-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 |
November | 1575.79 | 03-NOV-15:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.73 |
December | 1164.72 | 04-DEC-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1164.72 | 211.94 | 74.61 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14811.92 | 805.38 | 268.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 197.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 988.54 | 14-JAN-16:03 | 535.68 | 455.48 | 2232.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 |
February | 984.16 | 17-FEB-21:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.23 |
March | 1537.41 | 15-MAR-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 | 0.00 |
April | 1426.50 | 21-APR-15:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 |
May | 2521.15 | 23-MAY-14:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 4416.61 | 27-JUN-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 | 0.00 |
July | 5135.85 | 21-JUL-13:50 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 18.72 | 0.00 |
August | 5120.74 | 14-AUG-12:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 | 0.00 |
September | 3788.19 | 18-SEP-13:40 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.98 |
October | 2020.59 | 05-OCT-14:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 |
November | 1365.87 | 01-NOV-13:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.53 |
December | 1170.99 | 01-DEC-13:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 984.16 | 535.68 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5135.85 | 1306.65 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 | 65.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 808.51 | 14-JAN-07:05 | 339.13 | 250.33 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.05 |
February | 877.96 | 28-FEB-10:10 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.32 |
March | 1240.05 | 15-MAR-14:10 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 | 0.00 |
April | 3408.84 | 24-APR-09:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 |
May | 4668.37 | 31-MAY-09:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 |
June | 6551.59 | 23-JUN-06:03 | 678.26 | 358.22 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.86 |
July | 10574.50 | 04-JUL-10:12 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 |
August | 7627.97 | 06-AUG-08:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.98 |
September | 5038.18 | 18-SEP-09:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 |
October | 3350.67 | 11-OCT-09:40 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 |
November | 1216.98 | 03-NOV-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.79 |
December | 866.44 | 01-DEC-13:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 808.51 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10574.50 | 827.22 | 358.22 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 | 48.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1178.22 | 21-JAN-12:30 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.45 |
February | 1373.40 | 18-FEB-14:40 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.75 |
March | 5479.23 | 15-MAR-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 276.09 | 0.00 |
April | 3127.61 | 22-APR-13:40 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 |
May | 4438.34 | 23-MAY-14:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 |
June | 10704.35 | 27-JUN-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6352.41 | 0.00 |
July | 10971.60 | 21-JUL-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5975.95 | 0.00 |
August | 12110.57 | 06-AUG-14:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 | 0.00 |
September | 12716.72 | 04-SEP-14:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.30 |
October | 9035.39 | 11-OCT-12:40 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.85 |
November | 2118.00 | 18-NOV-13:30 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.02 |
December | 1580.95 | 16-DEC-13:40 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1178.22 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12716.72 | 1306.65 | 424.37 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 6352.41 | 353.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 942.39 | 12-JAN-16:10 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.79 |
February | 1145.87 | 28-FEB-16:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.95 |
March | 1418.80 | 15-MAR-14:20 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 | 0.00 |
April | 3531.35 | 24-APR-17:30 | 84.78 | 89.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.95 |
May | 5678.24 | 27-MAY-17:08 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.82 |
June | 11060.84 | 25-JUN-17:42 | 0.00 | 74.61 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.22 |
July | 11312.54 | 02-JUL-18:01 | 0.00 | 119.38 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 |
August | 9536.18 | 12-AUG-17:05 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 |
September | 7185.92 | 04-SEP-16:53 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.23 |
October | 4657.21 | 11-OCT-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 |
November | 1277.14 | 03-NOV-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.01 |
December | 963.66 | 04-DEC-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 942.39 | 0.00 | 59.69 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11312.54 | 805.38 | 268.64 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 | 105.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 958.63 | 14-JAN-16:03 | 535.68 | 461.41 | 2232.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.11 |
February | 955.83 | 18-FEB-16:03 | 401.76 | 212.18 | 1674.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 |
March | 2771.40 | 15-MAR-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 0.00 |
April | 2015.31 | 21-APR-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 |
May | 4177.54 | 23-MAY-14:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
June | 6334.99 | 21-JUN-06:03 | 1071.35 | 565.83 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 |
July | 7088.36 | 10-JUL-06:02 | 1607.03 | 848.74 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.21 |
August | 6686.62 | 07-AUG-06:03 | 803.52 | 478.91 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 |
September | 4210.04 | 13-SEP-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
October | 2431.33 | 12-OCT-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.77 |
November | 1353.42 | 01-NOV-13:40 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.03 |
December | 1122.41 | 01-DEC-13:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 955.83 | 401.76 | 212.18 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7088.36 | 1607.03 | 848.74 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 114.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 989.83 | 14-JAN-07:05 | 339.13 | 250.33 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.65 |
February | 1253.48 | 28-FEB-10:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.83 |
March | 2347.59 | 14-MAR-10:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 |
April | 5633.55 | 24-APR-08:50 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.60 |
May | 7268.71 | 31-MAY-08:40 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 |
June | 12776.76 | 11-JUN-09:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 |
July | 12598.93 | 04-JUL-08:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.70 |
August | 12690.08 | 06-AUG-09:12 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.74 |
September | 6432.98 | 10-SEP-10:33 | 127.17 | 44.77 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.57 |
October | 4264.31 | 11-OCT-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 |
November | 1463.80 | 03-NOV-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.66 |
December | 1004.38 | 01-DEC-07:05 | 678.26 | 750.98 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 989.83 | 127.17 | 44.77 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 | |
Maximum of Months | 12776.76 | 805.43 | 750.98 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4352.26 | 12-JAN-13:25 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.35 |
February | 5540.69 | 28-FEB-13:40 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.16 |
March | 8521.15 | 15-MAR-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 | 0.00 |
April | 7468.05 | 24-APR-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 |
May | 7014.62 | 26-MAY-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.25 |
June | 11356.87 | 18-JUN-13:53 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.18 |
July | 14894.96 | 30-JUL-12:32 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.49 |
August | 14384.37 | 13-AUG-13:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 89.02 | 0.00 |
September | 14611.07 | 04-SEP-14:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.81 |
October | 11129.15 | 11-OCT-12:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
November | 7527.25 | 03-NOV-12:25 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.93 |
December | 3638.47 | 16-DEC-13:30 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3638.47 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14894.96 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 89.02 | 310.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1174.46 | 12-JAN-16:10 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.91 |
February | 1550.16 | 28-FEB-16:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.56 |
March | 2947.35 | 15-MAR-14:20 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 0.00 |
April | 5755.49 | 24-APR-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.38 |
May | 10823.37 | 07-MAY-17:53 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.35 |
June | 13671.02 | 11-JUN-18:22 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.05 |
July | 13491.03 | 02-JUL-16:52 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.40 |
August | 13068.50 | 06-AUG-16:31 | 296.72 | 104.46 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 | 0.00 |
September | 8969.61 | 03-SEP-16:23 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.35 |
October | 5441.14 | 11-OCT-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 |
November | 1607.10 | 03-NOV-15:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.81 |
December | 1159.05 | 04-DEC-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1159.05 | 0.00 | 59.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13671.02 | 805.38 | 268.64 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 | 167.91 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.161687E+12 | 234893.06 | 02-JAN-07:10 | 0.745789E+11 | 100696.22 | 04-JAN-07:19 |
February | 0.139173E+12 | 219339.65 | 06-FEB-07:10 | 0.687469E+11 | 112796.50 | 07-FEB-07:49 |
March | 0.117697E+12 | 175747.11 | 06-MAR-07:10 | 0.437515E+11 | 96945.68 | 07-MAR-07:10 |
April | 0.905911E+11 | 136641.33 | 17-APR-06:10 | 0.180295E+11 | 61955.39 | 17-APR-06:19 |
May | 0.948799E+11 | 93375.62 | 23-MAY-15:09 | 0.992756E+10 | 32797.70 | 01-MAY-06:10 |
June | 0.115045E+12 | 139929.73 | 27-JUN-15:20 | 0.913797E+10 | 10418.44 | 14-JUN-06:10 |
July | 0.132390E+12 | 147986.50 | 17-JUL-07:10 | 0.869966E+10 | 9138.88 | 03-JUL-11:39 |
August | 0.130915E+12 | 150336.80 | 15-AUG-14:30 | 0.911051E+10 | 9092.18 | 31-AUG-11:09 |
September | 0.101319E+12 | 116449.13 | 15-SEP-10:00 | 0.862161E+10 | 14668.83 | 30-SEP-06:19 |
October | 0.937754E+11 | 123590.68 | 30-OCT-06:10 | 0.136041E+11 | 54737.66 | 17-OCT-06:30 |
November | 0.104643E+12 | 158010.74 | 24-NOV-07:10 | 0.260129E+11 | 59277.21 | 24-NOV-07:30 |
December | 0.147839E+12 | 215473.83 | 11-DEC-07:10 | 0.653313E+11 | 111342.27 | 11-DEC-07:19 |
Annual Sum or Average | 0.142995E+13 | 0.355552E+12 | ||||
Minimum of Months | 0.905911E+11 | 93375.62 | 0.862161E+10 | 9092.18 | ||
Maximum of Months | 0.161687E+12 | 234893.06 | 0.745789E+11 | 112796.50 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.174669E+11 | 0.584553E+10 | 0.593559E+11 | 0.980150E+09 | 0.480674E+10 | 1312252.65 | 0.732299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155668E+11 | 0.464973E+10 | 0.537310E+11 | 0.886794E+09 | 0.428083E+10 | 1186778.30 | 0.600571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181615E+11 | 0.432936E+10 | 0.617796E+11 | 0.102606E+10 | 0.460097E+10 | 1343621.24 | 0.265501E+11 | 0.124791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160742E+11 | 0.345875E+10 | 0.572952E+11 | 0.943584E+09 | 0.441251E+10 | 1267813.82 | 0.793348E+10 | 0.472114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172244E+11 | 0.299770E+10 | 0.605677E+11 | 0.100269E+10 | 0.649490E+10 | 1327936.95 | 0.154089E+10 | 0.505026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170628E+11 | 0.269407E+10 | 0.594895E+11 | 0.987008E+09 | 0.115069E+11 | 1296568.36 | 0.371943E+09 | 0.229317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160110E+11 | 0.285704E+10 | 0.583622E+11 | 0.959044E+09 | 0.145255E+11 | 1299182.41 | 81016479.56 | 0.395925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178898E+11 | 0.331937E+10 | 0.617796E+11 | 0.102591E+10 | 0.139016E+11 | 1343621.24 | 0.189416E+09 | 0.328083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161794E+11 | 0.383703E+10 | 0.572729E+11 | 0.943412E+09 | 0.850125E+10 | 1267813.82 | 0.595258E+09 | 0.139883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170473E+11 | 0.478851E+10 | 0.593671E+11 | 0.979887E+09 | 0.482217E+10 | 1312252.65 | 0.514116E+10 | 0.162805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173394E+11 | 0.541581E+10 | 0.580818E+11 | 0.962064E+09 | 0.399433E+10 | 1278270.02 | 0.185506E+11 | 0.297953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170955E+11 | 0.605560E+10 | 0.583511E+11 | 0.959821E+09 | 0.444565E+10 | 1299182.41 | 0.609297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203119E+12 | 0.502485E+11 | 0.705434E+12 | 0.116564E+11 | 0.862933E+11 | 15535293.87 | 0.255171E+12 | 0.118017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155668E+11 | 0.269407E+10 | 0.537310E+11 | 0.886794E+09 | 0.399433E+10 | 1186778.30 | 81016479.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181615E+11 | 0.605560E+10 | 0.617796E+11 | 0.102606E+10 | 0.145255E+11 | 1343621.24 | 0.732299E+11 | 0.395925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.645088E+11 | 0.00 | 0.100701E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.595447E+11 | 0.00 | 0.920216E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.332542E+11 | 0.00 | 0.104973E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.856133E+10 | 0.00 | 0.946815E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.282366E+09 | 0.00 | 0.964520E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6183129.17 | 0.00 | 0.913178E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.869966E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.911051E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 69837346.71 | 0.00 | 0.855177E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.451127E+10 | 0.00 | 0.909287E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.167921E+11 | 0.00 | 0.922080E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.556896E+11 | 0.00 | 0.964165E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.243220E+12 | 0.00 | 0.112332E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.855177E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.645088E+11 | 0.00 | 0.104973E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21377.78 | 02-JAN-16:49 | 5557.43 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 834.09 | 11-JAN-08:20 | 6938.37 | 02-JAN-07:10 | 0.73 | 02-JAN-06:10 | 193928.18 | 02-JAN-07:10 |
February | 20335.96 | 01-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 833.89 | 01-FEB-08:20 | 6264.90 | 06-FEB-07:10 | 0.73 | 01-FEB-08:09 | 179048.25 | 06-FEB-07:10 |
March | 19078.12 | 17-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 832.28 | 17-MAR-07:19 | 6337.85 | 15-MAR-13:50 | 0.73 | 01-MAR-07:10 | 143484.45 | 06-MAR-07:10 |
April | 18251.32 | 12-APR-07:10 | 5557.43 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 831.19 | 12-APR-07:19 | 6387.62 | 21-APR-15:30 | 0.73 | 03-APR-06:10 | 105628.00 | 17-APR-06:10 |
May | 17351.76 | 11-MAY-07:10 | 5557.43 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 830.00 | 11-MAY-07:19 | 13137.56 | 31-MAY-15:00 | 0.73 | 01-MAY-07:10 | 29581.78 | 01-MAY-06:10 |
June | 17023.88 | 19-JUN-07:10 | 3195.36 | 01-JUN-19:49 | 45864.70 | 01-JUN-07:10 | 829.57 | 19-JUN-07:19 | 25368.31 | 27-JUN-15:20 | 0.73 | 01-JUN-05:10 | 11244.08 | 14-JUN-06:10 |
July | 17265.23 | 11-JUL-07:30 | 3195.36 | 01-JUL-19:00 | 45864.70 | 03-JUL-07:10 | 829.89 | 11-JUL-07:40 | 25839.59 | 17-JUL-12:09 | 0.73 | 01-JUL-05:10 | 7048.44 | 13-JUL-06:19 |
August | 17337.52 | 24-AUG-07:10 | 5557.43 | 02-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 829.98 | 24-AUG-07:19 | 25741.89 | 15-AUG-14:30 | 0.73 | 01-AUG-05:10 | 9547.63 | 31-AUG-06:40 |
September | 18869.79 | 26-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 832.01 | 26-SEP-07:19 | 18221.08 | 21-SEP-15:00 | 0.73 | 01-SEP-05:10 | 17355.14 | 29-SEP-06:10 |
October | 20672.49 | 31-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 834.40 | 31-OCT-07:19 | 9622.23 | 11-OCT-15:50 | 0.73 | 03-OCT-07:10 | 85906.57 | 30-OCT-06:10 |
November | 21377.78 | 06-NOV-16:00 | 5557.43 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 834.98 | 02-NOV-07:19 | 4368.52 | 03-NOV-12:39 | 0.73 | 02-NOV-07:10 | 119795.18 | 24-NOV-07:10 |
December | 21377.78 | 01-DEC-16:40 | 5557.43 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 834.29 | 18-DEC-08:20 | 6176.74 | 11-DEC-07:10 | 0.73 | 04-DEC-07:10 | 175270.58 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 17023.88 | 3195.36 | 45864.70 | 829.57 | 4368.52 | 0.73 | 7048.44 | |||||||
Maximum of Months | 21377.78 | 5557.43 | 45864.70 | 834.98 | 25839.59 | 0.73 | 193928.18 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19550.84 | 15-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9221.64 | 08-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23719.88 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 54841.64 | 27-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 60611.26 | 17-JUL-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 66359.60 | 15-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 43096.47 | 15-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16645.21 | 11-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6956.62 | 16-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 66359.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 234893.06 | 02-JAN-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 6938.37 | 0.73 | 193928.18 | 0.00 | 0.00 |
February | 219339.65 | 06-FEB-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 6264.90 | 0.73 | 179048.25 | 0.00 | 0.00 |
March | 175747.11 | 06-MAR-07:10 | 6117.89 | 21098.80 | 0.00 | 243.41 | 4801.84 | 0.73 | 143484.45 | 0.00 | 0.00 |
April | 136641.33 | 17-APR-06:10 | 5784.08 | 21098.80 | 0.00 | 243.35 | 3886.36 | 0.73 | 105628.00 | 0.00 | 0.00 |
May | 93375.62 | 23-MAY-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 11865.74 | 0.73 | 0.00 | 21790.10 | 0.00 |
June | 139929.73 | 27-JUN-15:20 | 16818.70 | 42072.41 | 0.00 | 827.95 | 25368.31 | 0.73 | 0.00 | 54841.64 | 0.00 |
July | 147986.50 | 17-JUL-07:10 | 16818.70 | 45864.70 | 0.00 | 814.60 | 24580.43 | 0.73 | 0.00 | 59907.34 | 0.00 |
August | 150336.80 | 15-AUG-14:30 | 16818.70 | 40588.47 | 0.00 | 827.42 | 25741.89 | 0.73 | 0.00 | 66359.60 | 0.00 |
September | 116449.13 | 15-SEP-10:00 | 16818.70 | 41577.77 | 0.00 | 827.77 | 14196.36 | 0.73 | 0.00 | 43027.80 | 0.00 |
October | 123590.68 | 30-OCT-06:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 3657.61 | 0.73 | 85906.57 | 0.00 | 0.00 |
November | 158010.74 | 24-NOV-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 4189.06 | 0.73 | 119795.18 | 0.00 | 0.00 |
December | 215473.83 | 11-DEC-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 6176.74 | 0.73 | 175270.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 93375.62 | 5784.08 | 21098.80 | 0.00 | 243.35 | 3657.61 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 234893.06 | 16818.70 | 45864.70 | 5557.43 | 827.95 | 25741.89 | 0.73 | 193928.18 | 66359.60 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 92489.37 | 04-JAN-07:19 | 0.00 | 10304.96 | 26-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 108107.29 | 07-FEB-07:19 | 0.00 | 10479.93 | 21-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 89117.81 | 07-MAR-07:19 | 0.00 | 10105.72 | 14-MAR-11:00 | 0.00 |
April | 0.00 | 0.00 | 53770.55 | 17-APR-06:19 | 0.00 | 9523.55 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 24625.75 | 01-MAY-06:10 | 0.00 | 9402.29 | 02-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 2315.58 | 14-JUN-06:10 | 0.00 | 9260.85 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9138.88 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9092.18 | 31-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 6822.77 | 30-SEP-06:10 | 0.00 | 9148.75 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 46806.42 | 17-OCT-06:19 | 0.00 | 9263.81 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 51125.16 | 24-NOV-07:30 | 0.00 | 9401.64 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 103622.79 | 11-DEC-07:30 | 0.00 | 9523.71 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9092.18 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 108107.29 | 0.00 | 10479.93 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.57 | 0.50 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.57 | 0.50 | 19.57 | 0.33 | 21.22 | 0.00 | 21.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.57 | 0.50 | 19.57 | 0.17 | 26.17 | 0.00 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.21 | 1.83 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
February | 0.33 | 19.37 | 0.33 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.32 | 0.33 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 2.83 | 19.24 | 2.50 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.37 | 1.83 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.60 | 2.50 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 2.50 | 18.09 | 1.33 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
March | 0.33 | 18.15 | 0.17 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.56 | 0.17 | 24.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
December | 2.33 | 18.65 | 1.67 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
Annual Sum or Average | 9.00 | 18.47 | 5.83 | 18.82 | 0.17 | 18.89 | 0.17 | 18.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.42 | 2.50 | 19.42 | 0.17 | 24.56 | 0.17 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.33 | 16.98 | 20.33 | 17.49 | 0.00 | 17.49 | 0.00 | 17.49 |
February | 34.00 | 17.07 | 17.67 | 17.66 | 0.00 | 17.66 | 0.00 | 17.66 |
March | 9.00 | 17.50 | 4.67 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
April | 0.33 | 18.00 | 0.17 | 18.39 | 0.00 | 18.39 | 0.00 | 18.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.80 | 0.67 | 24.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.37 | 1.00 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
November | 1.00 | 17.90 | 0.50 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
December | 30.33 | 16.89 | 15.17 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
Annual Sum or Average | 113.17 | 17.03 | 58.50 | 17.58 | 2.00 | 17.68 | 1.67 | 17.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 38.33 | 18.00 | 20.33 | 18.42 | 1.33 | 27.37 | 1.00 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.17 | 15.20 | 3.17 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
February | 17.83 | 15.13 | 2.00 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
March | 4.50 | 15.96 | 0.67 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
April | 0.17 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.44 | 0.33 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.68 | 2.50 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.76 | 7.17 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.55 | 2.83 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.40 | 0.67 | 27.40 |
October | 0.17 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
November | 1.00 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
December | 16.17 | 15.25 | 1.83 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
Annual Sum or Average | 61.00 | 15.27 | 7.67 | 15.34 | 13.67 | 17.39 | 13.50 | 18.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 0.00 | 15.22 |
Maximum of Months | 21.17 | 17.07 | 3.17 | 17.07 | 7.33 | 27.76 | 7.17 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.67 | 15.49 | 3.50 | 15.63 | 0.00 | 15.63 | 0.00 | 15.63 |
February | 16.67 | 15.61 | 2.67 | 15.93 | 0.00 | 15.93 | 0.00 | 15.93 |
March | 2.83 | 16.57 | 0.33 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
April | 0.17 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.39 | 0.67 | 27.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.20 | 3.17 | 27.20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.64 | 6.50 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.76 | 3.83 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.75 | 3.33 | 27.75 |
October | 0.17 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
November | 0.50 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
December | 13.50 | 15.72 | 2.33 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
Annual Sum or Average | 52.50 | 15.67 | 8.83 | 15.90 | 18.00 | 18.56 | 17.50 | 20.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 | 0.00 | 15.63 |
Maximum of Months | 18.67 | 17.23 | 3.50 | 17.23 | 6.67 | 27.76 | 6.50 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.17 | 15.16 | 5.00 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
February | 17.67 | 15.04 | 2.33 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
March | 4.00 | 15.95 | 0.50 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
April | 0.17 | 16.95 | 0.00 | 16.95 | 0.17 | 22.12 | 0.17 | 23.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.73 | 1.17 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.75 | 3.83 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.14 | 4.17 | 28.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.00 | 2.67 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.74 | 1.83 | 27.73 |
October | 0.17 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
November | 0.67 | 16.53 | 0.00 | 16.53 | 0.00 | 16.53 | 0.00 | 16.53 |
December | 16.00 | 15.15 | 2.50 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
Annual Sum or Average | 62.83 | 15.20 | 10.33 | 15.22 | 23.67 | 18.32 | 13.83 | 19.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 | 0.00 | 15.06 |
Maximum of Months | 24.17 | 17.16 | 5.00 | 17.16 | 7.83 | 28.14 | 4.17 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.33 | 19.07 | 11.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 12.33 | 19.16 | 10.33 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
March | 3.17 | 19.25 | 2.67 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
April | 0.17 | 19.41 | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.50 | 19.08 | 5.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Annual Sum or Average | 35.50 | 19.12 | 29.50 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.33 | 19.41 | 11.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 16.00 | 0.17 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
February | 1.33 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
March | 0.33 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.45 | 0.50 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.68 | 2.17 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.50 | 0.67 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
Annual Sum or Average | 6.00 | 16.33 | 0.17 | 16.41 | 3.50 | 20.46 | 3.50 | 22.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 17.11 | 0.17 | 17.11 | 2.17 | 27.68 | 2.17 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 120.83 | 16.12 | 119.17 | 16.12 | 0.00 | 16.12 | 0.00 | 16.12 |
February | 107.83 | 16.08 | 106.50 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
March | 69.67 | 17.01 | 69.67 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
April | 44.50 | 18.27 | 44.50 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
May | 13.67 | 19.18 | 13.67 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
June | 3.00 | 20.01 | 3.00 | 20.01 | 0.67 | 20.47 | 0.67 | 20.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.35 | 2.17 | 25.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 26.42 | 4.33 | 26.42 |
September | 3.00 | 20.10 | 3.00 | 20.10 | 2.83 | 22.49 | 2.83 | 23.72 |
October | 25.17 | 18.78 | 25.17 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
November | 55.17 | 18.01 | 55.17 | 18.01 | 0.00 | 18.01 | 0.00 | 18.01 |
December | 97.33 | 16.09 | 96.83 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
Annual Sum or Average | 540.17 | 16.84 | 536.67 | 16.84 | 10.00 | 16.92 | 10.00 | 17.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.07 | 0.00 | 16.07 |
Maximum of Months | 120.83 | 20.10 | 119.17 | 20.10 | 4.33 | 26.42 | 4.33 | 26.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 15.90 | 0.17 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
February | 1.50 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
March | 0.17 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.36 | 0.17 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.66 | 1.83 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.82 | 2.17 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.63 | 1.83 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.65 | 0.67 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
Annual Sum or Average | 6.17 | 16.23 | 0.17 | 16.31 | 13.17 | 24.00 | 6.67 | 24.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.83 | 17.01 | 0.17 | 17.01 | 4.67 | 27.82 | 2.17 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.33 | 18.27 | 7.50 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
February | 12.33 | 18.12 | 7.50 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
March | 1.83 | 18.49 | 1.17 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8.67 | 17.93 | 5.17 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
Annual Sum or Average | 34.17 | 18.14 | 21.33 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.33 | 18.49 | 7.50 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.00 | 16.00 | 0.50 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
February | 4.50 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
March | 0.50 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 | 0.00 | 16.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.83 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.63 | 2.50 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.86 | 4.67 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.68 | 1.50 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.56 | 1.67 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.50 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
Annual Sum or Average | 14.50 | 15.79 | 0.50 | 15.86 | 11.33 | 20.96 | 11.33 | 22.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.00 | 16.45 | 0.50 | 16.45 | 4.67 | 27.86 | 4.67 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 16.55 | 0.33 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
February | 3.67 | 16.35 | 0.50 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
March | 0.33 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.39 | 1.33 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.51 | 4.67 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.63 | 3.83 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.75 | 3.50 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.83 | 16.21 | 0.17 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
Annual Sum or Average | 8.83 | 16.39 | 1.00 | 16.69 | 13.67 | 23.03 | 13.67 | 24.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 16.55 | 0.50 | 16.81 | 4.67 | 27.75 | 4.67 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 15.92 | 0.50 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
February | 4.50 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
March | 0.33 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.62 | 1.50 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.02 | 2.67 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.11 | 3.17 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.84 | 2.67 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.74 | 1.83 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.50 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
Annual Sum or Average | 14.00 | 15.73 | 0.50 | 15.81 | 20.50 | 22.91 | 11.83 | 24.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 16.15 | 0.50 | 16.15 | 6.17 | 28.11 | 3.17 | 28.12 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.03 | 93.83 | 21.78 | 93.83 | 21.61 |
February | 454.00 | 22.28 | 37.50 | 22.18 | 37.50 | 22.09 |
March | 463.67 | 23.28 | 7.83 | 23.28 | 3.00 | 23.26 |
April | 374.17 | 23.69 | 6.50 | 23.71 | 0.00 | 23.71 |
May | 132.67 | 23.91 | 135.50 | 24.42 | 0.00 | 24.42 |
June | 0.67 | 24.00 | 327.50 | 24.46 | 0.00 | 24.46 |
July | 0.00 | 0.00 | 482.50 | 24.43 | 0.00 | 24.43 |
August | 0.00 | 0.00 | 466.67 | 24.39 | 0.00 | 24.39 |
September | 9.33 | 23.83 | 309.33 | 24.51 | 0.00 | 24.51 |
October | 211.00 | 23.82 | 56.00 | 24.03 | 0.00 | 24.03 |
November | 460.17 | 23.61 | 0.00 | 23.61 | 0.00 | 23.61 |
December | 495.33 | 22.60 | 17.83 | 22.54 | 17.83 | 22.49 |
Annual Sum or Average | 3103.00 | 22.99 | 1941.00 | 23.45 | 152.17 | 23.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.78 | 0.00 | 21.61 |
Maximum of Months | 502.00 | 24.00 | 482.50 | 24.51 | 93.83 | 24.51 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.74 | 388.33 | 20.65 | 388.33 | 20.61 |
February | 454.00 | 20.90 | 315.83 | 20.79 | 315.83 | 20.75 |
March | 489.67 | 21.83 | 94.00 | 21.68 | 92.67 | 21.56 |
April | 476.17 | 22.78 | 3.50 | 22.76 | 3.50 | 22.75 |
May | 274.17 | 23.47 | 48.17 | 23.61 | 0.00 | 23.61 |
June | 59.50 | 23.76 | 257.50 | 24.15 | 0.00 | 24.15 |
July | 0.00 | 0.00 | 460.83 | 24.28 | 0.00 | 24.28 |
August | 1.33 | 23.53 | 395.17 | 24.29 | 0.00 | 24.29 |
September | 85.67 | 23.43 | 192.67 | 24.09 | 0.00 | 24.09 |
October | 422.83 | 22.88 | 4.33 | 22.90 | 0.00 | 22.90 |
November | 489.00 | 22.02 | 28.00 | 21.96 | 28.00 | 21.90 |
December | 497.00 | 20.96 | 298.83 | 20.84 | 298.83 | 20.78 |
Annual Sum or Average | 3751.33 | 21.91 | 2487.17 | 22.20 | 1127.17 | 21.96 |
Minimum of Months | 0.00 | 0.00 | 3.50 | 20.65 | 0.00 | 20.61 |
Maximum of Months | 502.00 | 23.76 | 460.83 | 24.29 | 388.33 | 24.29 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.28 | 468.50 | 20.25 | 468.50 | 20.23 |
February | 454.00 | 20.39 | 395.33 | 20.33 | 395.33 | 20.30 |
March | 501.00 | 21.26 | 223.50 | 21.03 | 222.17 | 20.91 |
April | 481.17 | 22.16 | 48.50 | 21.99 | 48.50 | 21.85 |
May | 334.67 | 23.19 | 38.00 | 23.30 | 0.00 | 23.30 |
June | 90.50 | 23.51 | 244.67 | 24.03 | 0.67 | 24.03 |
July | 8.17 | 23.46 | 443.50 | 24.26 | 0.00 | 24.26 |
August | 27.83 | 23.37 | 369.33 | 24.19 | 0.00 | 24.19 |
September | 184.50 | 23.13 | 136.33 | 23.62 | 0.00 | 23.62 |
October | 474.17 | 22.11 | 44.33 | 21.98 | 42.33 | 21.86 |
November | 489.00 | 21.14 | 176.33 | 20.94 | 176.33 | 20.82 |
December | 497.00 | 20.38 | 430.67 | 20.32 | 430.67 | 20.30 |
Annual Sum or Average | 4044.00 | 21.44 | 3019.00 | 21.64 | 1784.50 | 21.37 |
Minimum of Months | 8.17 | 20.28 | 38.00 | 20.25 | 0.00 | 20.23 |
Maximum of Months | 502.00 | 23.51 | 468.50 | 24.26 | 468.50 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.76 | 494.67 | 19.75 | 494.67 | 19.75 |
February | 454.00 | 19.81 | 453.83 | 19.81 | 453.83 | 19.81 |
March | 499.17 | 20.58 | 348.67 | 20.41 | 343.50 | 20.32 |
April | 479.17 | 21.42 | 146.17 | 21.12 | 146.17 | 20.94 |
May | 351.00 | 22.72 | 56.17 | 22.85 | 9.83 | 22.79 |
June | 105.33 | 23.47 | 260.50 | 24.05 | 11.33 | 24.10 |
July | 37.67 | 24.77 | 442.67 | 24.42 | 24.00 | 24.48 |
August | 79.33 | 23.40 | 358.67 | 24.12 | 10.17 | 24.15 |
September | 259.17 | 22.82 | 130.50 | 23.29 | 11.00 | 23.35 |
October | 485.50 | 21.33 | 140.67 | 21.05 | 138.50 | 20.87 |
November | 489.00 | 20.43 | 332.83 | 20.28 | 332.83 | 20.21 |
December | 497.00 | 19.79 | 481.00 | 19.77 | 481.00 | 19.76 |
Annual Sum or Average | 4238.33 | 20.95 | 3646.33 | 21.16 | 2456.83 | 20.89 |
Minimum of Months | 37.67 | 19.76 | 56.17 | 19.75 | 9.83 | 19.75 |
Maximum of Months | 502.00 | 24.77 | 494.67 | 24.42 | 494.67 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 495.00 | 19.83 | 495.00 | 19.82 |
February | 454.00 | 19.90 | 444.33 | 19.88 | 444.33 | 19.87 |
March | 492.50 | 20.74 | 304.00 | 20.56 | 289.83 | 20.43 |
April | 406.17 | 21.46 | 113.50 | 21.25 | 101.33 | 21.03 |
May | 273.17 | 22.63 | 125.50 | 23.16 | 8.17 | 23.13 |
June | 95.50 | 23.77 | 334.17 | 24.25 | 21.17 | 24.35 |
July | 57.83 | 25.91 | 460.83 | 24.63 | 48.33 | 24.78 |
August | 77.33 | 23.78 | 397.00 | 24.24 | 19.50 | 24.32 |
September | 203.83 | 22.68 | 221.17 | 23.55 | 11.50 | 23.60 |
October | 455.17 | 21.45 | 114.00 | 21.21 | 105.83 | 21.02 |
November | 489.00 | 20.53 | 317.00 | 20.36 | 317.00 | 20.29 |
December | 497.00 | 19.86 | 482.67 | 19.84 | 482.67 | 19.83 |
Annual Sum or Average | 4003.50 | 20.98 | 3809.17 | 21.36 | 2344.67 | 21.09 |
Minimum of Months | 57.83 | 19.84 | 113.50 | 19.83 | 8.17 | 19.82 |
Maximum of Months | 502.00 | 25.91 | 495.00 | 24.63 | 495.00 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.67 | 20.16 | 438.50 | 20.01 | 438.50 | 19.96 |
February | 450.33 | 20.18 | 379.83 | 20.00 | 379.83 | 19.93 |
March | 471.50 | 21.21 | 246.17 | 20.92 | 229.67 | 20.73 |
April | 393.83 | 21.53 | 137.17 | 21.40 | 114.33 | 21.18 |
May | 290.33 | 22.59 | 113.00 | 23.02 | 14.17 | 22.98 |
June | 126.33 | 23.47 | 292.00 | 24.09 | 20.17 | 24.18 |
July | 73.67 | 25.12 | 435.17 | 24.55 | 47.83 | 24.70 |
August | 93.50 | 23.86 | 385.50 | 24.27 | 24.17 | 24.37 |
September | 192.33 | 23.01 | 240.00 | 23.81 | 20.00 | 23.92 |
October | 391.50 | 21.65 | 147.67 | 21.68 | 90.33 | 21.45 |
November | 470.00 | 20.91 | 247.50 | 20.63 | 247.50 | 20.50 |
December | 495.67 | 20.13 | 443.17 | 20.03 | 443.17 | 19.99 |
Annual Sum or Average | 3950.67 | 21.26 | 3505.67 | 21.57 | 2069.67 | 21.30 |
Minimum of Months | 73.67 | 20.13 | 113.00 | 20.00 | 14.17 | 19.93 |
Maximum of Months | 501.67 | 25.12 | 443.17 | 24.55 | 443.17 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 492.50 | 19.82 | 492.50 | 19.81 |
February | 454.00 | 19.92 | 436.00 | 19.88 | 436.00 | 19.87 |
March | 495.50 | 20.80 | 300.17 | 20.58 | 293.00 | 20.46 |
April | 422.17 | 21.28 | 160.67 | 21.21 | 131.33 | 21.02 |
May | 325.33 | 22.45 | 116.17 | 22.90 | 17.67 | 22.89 |
June | 139.67 | 23.40 | 302.00 | 24.07 | 23.33 | 24.18 |
July | 72.33 | 24.63 | 427.67 | 24.47 | 38.67 | 24.59 |
August | 107.50 | 23.40 | 368.00 | 24.14 | 19.50 | 24.22 |
September | 263.83 | 22.66 | 175.33 | 23.35 | 18.33 | 23.46 |
October | 465.17 | 21.26 | 143.67 | 21.08 | 127.83 | 20.89 |
November | 489.00 | 20.49 | 315.83 | 20.32 | 315.83 | 20.25 |
December | 497.00 | 19.84 | 478.67 | 19.82 | 478.67 | 19.81 |
Annual Sum or Average | 4233.50 | 21.00 | 3716.67 | 21.31 | 2392.67 | 21.05 |
Minimum of Months | 72.33 | 19.83 | 116.17 | 19.82 | 17.67 | 19.81 |
Maximum of Months | 502.00 | 24.63 | 492.50 | 24.47 | 492.50 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.05 | 494.67 | 20.04 | 494.67 | 20.04 |
February | 454.00 | 20.13 | 454.00 | 20.13 | 454.00 | 20.13 |
March | 514.00 | 20.72 | 359.83 | 20.58 | 359.83 | 20.52 |
April | 485.00 | 21.26 | 139.33 | 21.07 | 139.33 | 20.95 |
May | 462.00 | 22.62 | 11.83 | 22.63 | 4.67 | 22.61 |
June | 148.33 | 23.51 | 204.17 | 23.89 | 7.50 | 23.91 |
July | 20.33 | 24.41 | 435.00 | 24.29 | 10.83 | 24.31 |
August | 43.33 | 23.46 | 357.33 | 24.15 | 2.17 | 24.16 |
September | 217.50 | 23.28 | 134.00 | 23.66 | 6.50 | 23.70 |
October | 480.17 | 22.17 | 22.33 | 22.11 | 21.17 | 22.05 |
November | 489.00 | 21.02 | 190.83 | 20.87 | 190.83 | 20.78 |
December | 497.00 | 20.24 | 470.00 | 20.22 | 470.00 | 20.21 |
Annual Sum or Average | 4312.67 | 21.26 | 3273.33 | 21.41 | 2161.50 | 21.16 |
Minimum of Months | 20.33 | 20.05 | 11.83 | 20.04 | 2.17 | 20.04 |
Maximum of Months | 514.00 | 24.41 | 494.67 | 24.29 | 494.67 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 494.33 | 20.13 | 494.33 | 20.13 |
February | 454.00 | 20.22 | 449.33 | 20.22 | 449.33 | 20.21 |
March | 509.83 | 20.96 | 289.17 | 20.76 | 289.17 | 20.66 |
April | 450.00 | 21.85 | 72.50 | 21.67 | 69.17 | 21.50 |
May | 317.33 | 22.88 | 74.83 | 23.23 | 0.83 | 23.22 |
June | 71.00 | 23.66 | 314.17 | 24.26 | 7.67 | 24.29 |
July | 23.33 | 26.37 | 476.83 | 24.55 | 22.83 | 24.63 |
August | 28.00 | 24.07 | 428.50 | 24.35 | 6.33 | 24.38 |
September | 119.33 | 23.32 | 276.83 | 24.07 | 7.50 | 24.11 |
October | 406.33 | 22.39 | 27.50 | 22.45 | 7.83 | 22.41 |
November | 489.00 | 21.19 | 155.67 | 21.01 | 155.67 | 20.90 |
December | 497.00 | 20.30 | 472.17 | 20.28 | 472.17 | 20.27 |
Annual Sum or Average | 3867.17 | 21.30 | 3531.83 | 21.70 | 1982.83 | 21.42 |
Minimum of Months | 23.33 | 20.14 | 27.50 | 20.13 | 0.83 | 20.13 |
Maximum of Months | 509.83 | 26.37 | 494.33 | 24.55 | 494.33 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.16 | 476.17 | 19.09 | 476.17 | 19.07 |
February | 454.00 | 19.18 | 435.50 | 19.14 | 435.50 | 19.12 |
March | 502.00 | 20.43 | 287.33 | 20.16 | 280.83 | 20.00 |
April | 459.17 | 21.08 | 132.33 | 20.85 | 122.83 | 20.64 |
May | 422.50 | 22.16 | 51.33 | 22.28 | 16.50 | 22.18 |
June | 220.17 | 22.89 | 215.33 | 23.57 | 40.33 | 23.59 |
July | 103.67 | 23.77 | 434.17 | 24.29 | 73.83 | 24.30 |
August | 112.50 | 23.32 | 397.33 | 24.15 | 54.50 | 24.18 |
September | 149.00 | 22.89 | 276.50 | 23.94 | 26.67 | 24.01 |
October | 392.17 | 21.83 | 82.50 | 22.05 | 22.67 | 21.90 |
November | 480.50 | 20.97 | 171.67 | 20.64 | 171.67 | 20.44 |
December | 496.50 | 19.55 | 450.17 | 19.44 | 450.17 | 19.40 |
Annual Sum or Average | 4294.17 | 20.84 | 3410.33 | 21.11 | 2171.67 | 20.81 |
Minimum of Months | 103.67 | 19.16 | 51.33 | 19.09 | 16.50 | 19.07 |
Maximum of Months | 502.00 | 23.77 | 476.17 | 24.29 | 476.17 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 491.00 | 20.09 | 491.00 | 20.09 |
February | 454.00 | 20.22 | 440.33 | 20.20 | 440.33 | 20.19 |
March | 510.33 | 20.97 | 282.83 | 20.77 | 282.83 | 20.67 |
April | 450.00 | 21.62 | 93.33 | 21.44 | 88.83 | 21.29 |
May | 345.00 | 22.73 | 71.50 | 23.07 | 0.67 | 23.07 |
June | 87.17 | 23.63 | 304.17 | 24.22 | 12.17 | 24.27 |
July | 28.67 | 25.52 | 461.33 | 24.52 | 22.33 | 24.59 |
August | 40.33 | 24.27 | 418.83 | 24.39 | 12.33 | 24.44 |
September | 139.00 | 23.32 | 229.67 | 24.01 | 8.83 | 24.07 |
October | 438.83 | 22.23 | 31.50 | 22.27 | 12.17 | 22.23 |
November | 489.00 | 21.12 | 166.33 | 20.95 | 166.33 | 20.86 |
December | 497.00 | 20.28 | 467.33 | 20.26 | 467.33 | 20.25 |
Annual Sum or Average | 3981.33 | 21.28 | 3458.17 | 21.65 | 2005.17 | 21.38 |
Minimum of Months | 28.67 | 20.10 | 31.50 | 20.09 | 0.67 | 20.09 |
Maximum of Months | 510.33 | 25.52 | 491.00 | 24.52 | 491.00 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.00 | 491.17 | 19.99 | 491.17 | 19.99 |
February | 454.00 | 20.11 | 442.50 | 20.09 | 442.50 | 20.09 |
March | 497.17 | 20.91 | 291.67 | 20.72 | 287.83 | 20.61 |
April | 478.67 | 21.89 | 70.17 | 21.68 | 70.17 | 21.52 |
May | 323.67 | 23.12 | 51.17 | 23.29 | 0.00 | 23.29 |
June | 70.67 | 23.80 | 268.83 | 24.18 | 5.67 | 24.21 |
July | 16.83 | 25.36 | 461.33 | 24.43 | 15.83 | 24.46 |
August | 32.67 | 23.58 | 393.67 | 24.24 | 4.00 | 24.25 |
September | 194.17 | 23.26 | 150.33 | 23.70 | 9.17 | 23.77 |
October | 466.00 | 21.93 | 53.50 | 21.80 | 50.33 | 21.68 |
November | 489.00 | 20.88 | 231.83 | 20.70 | 231.83 | 20.61 |
December | 497.00 | 20.11 | 467.33 | 20.08 | 467.33 | 20.07 |
Annual Sum or Average | 4021.83 | 21.22 | 3373.50 | 21.48 | 2075.83 | 21.20 |
Minimum of Months | 16.83 | 20.00 | 51.17 | 19.99 | 0.00 | 19.99 |
Maximum of Months | 502.00 | 25.36 | 491.17 | 24.43 | 491.17 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.92 | 419.67 | 19.91 | 419.67 | 19.91 |
February | 385.00 | 20.05 | 367.67 | 20.02 | 367.67 | 20.01 |
March | 417.00 | 20.98 | 220.17 | 20.79 | 212.67 | 20.66 |
April | 352.00 | 21.79 | 69.17 | 21.72 | 53.83 | 21.54 |
May | 233.33 | 22.93 | 95.50 | 23.46 | 2.50 | 23.49 |
June | 72.00 | 23.97 | 275.67 | 24.36 | 14.17 | 24.45 |
July | 39.33 | 26.35 | 398.17 | 24.71 | 37.83 | 24.85 |
August | 44.83 | 24.05 | 337.50 | 24.38 | 11.83 | 24.44 |
September | 160.17 | 23.16 | 185.17 | 23.88 | 13.33 | 23.98 |
October | 372.50 | 21.85 | 53.00 | 21.78 | 40.50 | 21.66 |
November | 417.00 | 20.86 | 203.67 | 20.67 | 203.67 | 20.58 |
December | 422.00 | 20.01 | 403.00 | 19.99 | 403.00 | 19.98 |
Annual Sum or Average | 3342.17 | 21.19 | 3028.33 | 21.58 | 1780.67 | 21.31 |
Minimum of Months | 39.33 | 19.92 | 53.00 | 19.91 | 2.50 | 19.91 |
Maximum of Months | 427.00 | 26.35 | 419.67 | 24.71 | 419.67 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.17 | 20.46 | 408.17 | 20.29 | 406.67 | 20.22 |
February | 450.33 | 20.56 | 351.17 | 20.35 | 351.17 | 20.27 |
March | 453.00 | 21.57 | 180.83 | 21.33 | 162.83 | 21.13 |
April | 380.67 | 22.04 | 68.50 | 22.02 | 47.33 | 21.85 |
May | 253.17 | 23.01 | 108.00 | 23.49 | 1.00 | 23.49 |
June | 83.17 | 23.76 | 305.00 | 24.22 | 11.17 | 24.27 |
July | 50.83 | 25.70 | 458.50 | 24.59 | 40.67 | 24.72 |
August | 48.50 | 24.70 | 417.67 | 24.42 | 20.83 | 24.51 |
September | 137.50 | 23.60 | 275.17 | 24.18 | 19.67 | 24.30 |
October | 345.50 | 22.23 | 100.17 | 22.48 | 27.83 | 22.36 |
November | 456.83 | 21.40 | 149.83 | 21.15 | 147.17 | 20.99 |
December | 492.83 | 20.50 | 400.33 | 20.36 | 400.33 | 20.31 |
Annual Sum or Average | 3650.50 | 21.57 | 3223.33 | 21.96 | 1636.67 | 21.68 |
Minimum of Months | 48.50 | 20.46 | 68.50 | 20.29 | 1.00 | 20.22 |
Maximum of Months | 498.17 | 25.70 | 458.50 | 24.59 | 406.67 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.05 | 484.67 | 20.03 | 484.67 | 20.02 |
February | 454.00 | 20.20 | 420.67 | 20.15 | 420.67 | 20.13 |
March | 493.67 | 21.14 | 245.83 | 20.92 | 238.33 | 20.79 |
April | 416.33 | 21.74 | 87.17 | 21.74 | 59.17 | 21.58 |
May | 281.00 | 22.81 | 121.00 | 23.35 | 3.17 | 23.38 |
June | 97.33 | 23.84 | 321.33 | 24.25 | 20.50 | 24.36 |
July | 47.33 | 25.34 | 456.83 | 24.53 | 33.00 | 24.63 |
August | 65.00 | 23.97 | 405.83 | 24.31 | 16.83 | 24.38 |
September | 200.00 | 23.13 | 203.67 | 23.79 | 16.17 | 23.90 |
October | 449.17 | 21.82 | 64.83 | 21.79 | 44.50 | 21.68 |
November | 489.00 | 20.91 | 221.00 | 20.72 | 221.00 | 20.63 |
December | 497.00 | 20.15 | 463.83 | 20.12 | 463.83 | 20.11 |
Annual Sum or Average | 3991.83 | 21.26 | 3496.67 | 21.63 | 2021.83 | 21.38 |
Minimum of Months | 47.33 | 20.05 | 64.83 | 20.03 | 3.17 | 20.02 |
Maximum of Months | 502.00 | 25.34 | 484.67 | 24.53 | 484.67 | 24.63 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.03089 | 19.46790 | -0.3675 | 9.28261 |
February | 454.00000 | 22.28256 | 18.83800 | -0.3037 | 7.60002 |
March | 514.00000 | 23.35903 | 25.42578 | 0.02199 | 5.90882 |
April | 485.00000 | 23.85966 | 28.89800 | 0.19313 | 6.14297 |
May | 508.00000 | 24.30290 | 32.47523 | -0.5186 | 11.18853 |
June | 496.00000 | 24.32157 | 43.39771 | -0.3792 | 8.44726 |
July | 497.00000 | 24.41692 | 51.29041 | -0.2793 | 7.09543 |
August | 514.00000 | 24.35496 | 47.96024 | -0.3216 | 7.57951 |
September | 485.00000 | 24.35859 | 43.61060 | -0.3783 | 8.53774 |
October | 502.00000 | 24.13219 | 33.93773 | 0.31223 | 7.31138 |
November | 489.00000 | 23.65536 | 28.80934 | 0.12357 | 5.73811 |
December | 497.00000 | 22.60307 | 22.31939 | -0.1998 | 6.63436 |
Annual Sum or Average | 5943.00000 | 23.64913 | 33.13877 | -0.1748 | 7.62864 |
Minimum of Months | 454.00000 | 22.03089 | 18.83800 | -0.5186 | 5.73811 |
Maximum of Months | 514.00000 | 24.41692 | 51.29041 | 0.31223 | 11.18853 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.74261 | 20.81279 | -0.6640 | 15.23446 |
February | 454.00000 | 20.90239 | 20.10624 | -0.6238 | 13.79191 |
March | 514.00000 | 21.93323 | 27.64710 | -0.2925 | 8.35967 |
April | 485.00000 | 22.80282 | 31.54937 | -0.0431 | 5.98711 |
May | 508.00000 | 23.81634 | 34.46661 | -0.6823 | 15.57566 |
June | 496.00000 | 24.11865 | 44.57081 | -0.4617 | 9.88139 |
July | 497.00000 | 24.25956 | 52.42820 | -0.3450 | 7.78846 |
August | 514.00000 | 24.21573 | 49.13692 | -0.3886 | 8.44212 |
September | 485.00000 | 24.04261 | 45.16675 | -0.5073 | 11.04900 |
October | 502.00000 | 23.06824 | 37.15428 | 0.06160 | 5.93881 |
November | 489.00000 | 22.02148 | 32.14380 | -0.2461 | 7.02498 |
December | 497.00000 | 20.95967 | 24.11515 | -0.5797 | 12.72409 |
Annual Sum or Average | 5943.00000 | 22.75405 | 35.04603 | -0.3968 | 10.13507 |
Minimum of Months | 454.00000 | 20.74261 | 20.10624 | -0.6823 | 5.93881 |
Maximum of Months | 514.00000 | 24.25956 | 52.42820 | 0.06160 | 15.57566 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.27750 | 20.93475 | -0.8079 | 20.34119 |
February | 454.00000 | 20.39230 | 20.55087 | -0.7749 | 19.12748 |
March | 514.00000 | 21.32619 | 28.32390 | -0.4537 | 11.62429 |
April | 485.00000 | 22.17126 | 32.52348 | -0.1962 | 7.28806 |
May | 508.00000 | 23.50917 | 34.99603 | -0.7841 | 19.30685 |
June | 496.00000 | 24.02285 | 44.84533 | -0.4875 | 10.65164 |
July | 497.00000 | 24.23024 | 52.39169 | -0.3459 | 7.87178 |
August | 514.00000 | 24.12999 | 49.20203 | -0.4153 | 8.98350 |
September | 485.00000 | 23.73587 | 45.90101 | -0.6161 | 14.25667 |
October | 502.00000 | 22.20774 | 38.84738 | -0.1476 | 7.10373 |
November | 489.00000 | 21.14230 | 33.49948 | -0.4725 | 10.73863 |
December | 497.00000 | 20.37758 | 24.85294 | -0.7521 | 18.30526 |
Annual Sum or Average | 5943.00000 | 22.30890 | 35.67525 | -0.5198 | 12.93204 |
Minimum of Months | 454.00000 | 20.27750 | 20.55087 | -0.8079 | 7.10373 |
Maximum of Months | 514.00000 | 24.23024 | 52.39169 | -0.1476 | 20.34119 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76253 | 21.99247 | -1.0026 | 28.42032 |
February | 454.00000 | 19.81173 | 21.87631 | -0.9745 | 27.32850 |
March | 514.00000 | 20.67988 | 30.12470 | -0.6411 | 17.21903 |
April | 485.00000 | 21.45569 | 34.24488 | -0.3727 | 10.36187 |
May | 508.00000 | 23.14902 | 36.96280 | -0.8942 | 24.47818 |
June | 496.00000 | 24.01667 | 45.52818 | -0.4646 | 11.04539 |
July | 497.00000 | 24.32987 | 53.06429 | -0.2739 | 7.52846 |
August | 514.00000 | 24.08167 | 49.97564 | -0.4074 | 9.64095 |
September | 485.00000 | 23.38226 | 47.85785 | -0.7295 | 19.03713 |
October | 502.00000 | 21.41652 | 41.07990 | -0.3427 | 10.06421 |
November | 489.00000 | 20.42514 | 34.91881 | -0.6767 | 16.36785 |
December | 497.00000 | 19.79043 | 26.01199 | -0.9568 | 26.71803 |
Annual Sum or Average | 5943.00000 | 21.87580 | 37.07233 | -0.6425 | 17.28567 |
Minimum of Months | 454.00000 | 19.76253 | 21.87631 | -1.0026 | 7.52846 |
Maximum of Months | 514.00000 | 24.32987 | 53.06429 | -0.2739 | 28.42032 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83591 | 21.56532 | -0.9737 | 27.18800 |
February | 454.00000 | 19.89546 | 21.48004 | -0.9360 | 25.85444 |
March | 514.00000 | 20.87231 | 29.44532 | -0.5629 | 15.19241 |
April | 485.00000 | 21.91195 | 32.92016 | -0.2309 | 9.68869 |
May | 508.00000 | 23.38373 | 35.72704 | -0.7476 | 20.57535 |
June | 496.00000 | 24.10155 | 44.86065 | -0.3556 | 9.90634 |
July | 497.00000 | 24.40912 | 52.41372 | -0.1638 | 7.30923 |
August | 514.00000 | 24.11992 | 49.45350 | -0.3156 | 8.89166 |
September | 485.00000 | 23.54513 | 46.78423 | -0.6086 | 16.42961 |
October | 502.00000 | 21.68891 | 40.02753 | -0.2563 | 9.29924 |
November | 489.00000 | 20.52700 | 34.29491 | -0.6429 | 15.47399 |
December | 497.00000 | 19.85606 | 25.61346 | -0.9378 | 25.82610 |
Annual Sum or Average | 5943.00000 | 22.02953 | 36.31703 | -0.5585 | 15.90139 |
Minimum of Months | 454.00000 | 19.83591 | 21.48004 | -0.9737 | 7.30923 |
Maximum of Months | 514.00000 | 24.40912 | 52.41372 | -0.1638 | 27.18800 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.16192 | 21.21453 | -0.8640 | 24.02530 |
February | 454.00000 | 20.20889 | 21.08189 | -0.8335 | 23.38580 |
March | 514.00000 | 21.43991 | 28.55822 | -0.4167 | 13.25848 |
April | 485.00000 | 22.05907 | 32.41518 | -0.2058 | 9.85544 |
May | 508.00000 | 23.30060 | 35.87966 | -0.8033 | 22.62208 |
June | 496.00000 | 23.97927 | 45.27214 | -0.4423 | 11.61727 |
July | 497.00000 | 24.34206 | 52.73435 | -0.2290 | 7.96274 |
August | 514.00000 | 24.13477 | 49.32740 | -0.3276 | 9.29256 |
September | 485.00000 | 23.72138 | 46.03731 | -0.5373 | 15.30130 |
October | 502.00000 | 22.22090 | 38.47391 | -0.1190 | 9.33141 |
November | 489.00000 | 21.03294 | 33.31023 | -0.5084 | 13.58061 |
December | 497.00000 | 20.14390 | 25.24155 | -0.8424 | 22.78480 |
Annual Sum or Average | 5943.00000 | 22.24550 | 35.89803 | -0.5087 | 15.19958 |
Minimum of Months | 454.00000 | 20.14390 | 21.08189 | -0.8640 | 7.96274 |
Maximum of Months | 514.00000 | 24.34206 | 52.73435 | -0.1190 | 24.02530 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82985 | 21.33290 | -0.9840 | 27.65568 |
February | 454.00000 | 19.92122 | 21.19959 | -0.9399 | 26.14228 |
March | 514.00000 | 20.91683 | 29.20105 | -0.5620 | 15.35965 |
April | 485.00000 | 21.68532 | 33.02877 | -0.2907 | 10.47389 |
May | 508.00000 | 23.09715 | 36.36977 | -0.8406 | 24.75352 |
June | 496.00000 | 23.93296 | 45.42868 | -0.4068 | 11.80930 |
July | 497.00000 | 24.27409 | 53.00486 | -0.2185 | 8.20652 |
August | 514.00000 | 24.01044 | 49.92918 | -0.3542 | 10.11734 |
September | 485.00000 | 23.30757 | 47.54546 | -0.6902 | 19.50788 |
October | 502.00000 | 21.46660 | 40.22464 | -0.3097 | 9.98515 |
November | 489.00000 | 20.49110 | 34.12048 | -0.6544 | 15.88248 |
December | 497.00000 | 19.84444 | 25.40442 | -0.9424 | 26.06788 |
Annual Sum or Average | 5943.00000 | 21.91492 | 36.50357 | -0.5971 | 17.10142 |
Minimum of Months | 454.00000 | 19.82985 | 21.19959 | -0.9840 | 8.20652 |
Maximum of Months | 514.00000 | 24.27409 | 53.00486 | -0.2185 | 27.65568 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04616 | 21.72870 | -0.9156 | 24.17179 |
February | 454.00000 | 20.13200 | 21.67724 | -0.8856 | 22.86140 |
March | 514.00000 | 20.72091 | 30.33599 | -0.6339 | 15.41393 |
April | 485.00000 | 21.26202 | 34.71891 | -0.4248 | 9.80567 |
May | 508.00000 | 22.75084 | 38.22036 | -1.0577 | 30.17463 |
June | 496.00000 | 23.91238 | 46.16060 | -0.5451 | 12.05516 |
July | 497.00000 | 24.22940 | 53.30746 | -0.3507 | 7.96792 |
August | 514.00000 | 24.10813 | 49.93259 | -0.4227 | 9.20517 |
September | 485.00000 | 23.70680 | 47.15556 | -0.6250 | 14.48473 |
October | 502.00000 | 22.24633 | 39.28890 | -0.1286 | 6.68884 |
November | 489.00000 | 21.01879 | 34.08248 | -0.4889 | 10.77713 |
December | 497.00000 | 20.24388 | 25.72382 | -0.8086 | 20.02584 |
Annual Sum or Average | 5943.00000 | 22.04646 | 36.96718 | -0.6060 | 15.27800 |
Minimum of Months | 454.00000 | 20.04616 | 21.67724 | -1.0577 | 6.68884 |
Maximum of Months | 514.00000 | 24.22940 | 53.30746 | -0.1286 | 30.17463 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13611 | 21.84468 | -0.8831 | 22.83640 |
February | 454.00000 | 20.22224 | 21.83767 | -0.8460 | 21.33217 |
March | 514.00000 | 20.98246 | 30.13103 | -0.5370 | 13.05882 |
April | 485.00000 | 22.04675 | 33.44767 | -0.2116 | 8.16168 |
May | 508.00000 | 23.41899 | 36.40336 | -0.7878 | 20.73035 |
June | 496.00000 | 24.17263 | 44.84115 | -0.3838 | 9.36561 |
July | 497.00000 | 24.43636 | 52.20091 | -0.2007 | 6.87807 |
August | 514.00000 | 24.26136 | 49.04454 | -0.2947 | 7.78968 |
September | 485.00000 | 24.01122 | 45.79132 | -0.4621 | 11.13996 |
October | 502.00000 | 22.72488 | 38.26391 | 0.00079 | 6.63371 |
November | 489.00000 | 21.19173 | 33.94528 | -0.4373 | 10.08148 |
December | 497.00000 | 20.29569 | 25.86481 | -0.7923 | 19.33990 |
Annual Sum or Average | 5943.00000 | 22.34084 | 36.23557 | -0.4845 | 13.07299 |
Minimum of Months | 454.00000 | 20.13611 | 21.83767 | -0.8831 | 6.63371 |
Maximum of Months | 514.00000 | 24.43636 | 52.20091 | 0.00079 | 22.83640 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.15559 | 19.47350 | -1.0325 | 29.92321 |
February | 454.00000 | 19.18460 | 19.72925 | -1.0122 | 28.69434 |
March | 514.00000 | 20.50978 | 27.65013 | -0.5886 | 15.49386 |
April | 485.00000 | 21.27987 | 32.40759 | -0.3642 | 10.39442 |
May | 508.00000 | 22.55318 | 36.80798 | -1.0556 | 31.49652 |
June | 496.00000 | 23.63502 | 46.88743 | -0.5811 | 14.48392 |
July | 497.00000 | 24.24683 | 54.53302 | -0.2890 | 8.23052 |
August | 514.00000 | 24.08891 | 50.24593 | -0.3479 | 9.39722 |
September | 485.00000 | 23.86034 | 45.92466 | -0.4701 | 12.73679 |
October | 502.00000 | 22.39368 | 36.56509 | -0.0275 | 7.81911 |
November | 489.00000 | 21.02466 | 31.17492 | -0.4366 | 11.37497 |
December | 497.00000 | 19.55396 | 23.72324 | -0.9045 | 24.81545 |
Annual Sum or Average | 5943.00000 | 21.80958 | 35.53941 | -0.5904 | 17.02120 |
Minimum of Months | 454.00000 | 19.15559 | 19.47350 | -1.0556 | 7.81911 |
Maximum of Months | 514.00000 | 24.24683 | 54.53302 | -0.0275 | 31.49652 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10499 | 21.70874 | -0.8979 | 23.51679 |
February | 454.00000 | 20.22067 | 21.65613 | -0.8548 | 21.77175 |
March | 514.00000 | 20.99400 | 29.97695 | -0.5395 | 13.10175 |
April | 485.00000 | 21.81097 | 33.62025 | -0.2718 | 8.62260 |
May | 508.00000 | 23.25411 | 36.81381 | -0.8449 | 23.03509 |
June | 496.00000 | 24.13694 | 45.08211 | -0.3920 | 9.72540 |
July | 497.00000 | 24.40034 | 52.50013 | -0.2240 | 7.14911 |
August | 514.00000 | 24.26272 | 49.21330 | -0.2994 | 7.99355 |
September | 485.00000 | 23.94231 | 46.22146 | -0.4955 | 11.99431 |
October | 502.00000 | 22.46592 | 38.61783 | -0.0593 | 6.71638 |
November | 489.00000 | 21.11600 | 33.91578 | -0.4564 | 10.29092 |
December | 497.00000 | 20.28083 | 25.72702 | -0.7972 | 19.54922 |
Annual Sum or Average | 5943.00000 | 22.26491 | 36.35684 | -0.5092 | 13.58414 |
Minimum of Months | 454.00000 | 20.10499 | 21.65613 | -0.8979 | 6.71638 |
Maximum of Months | 514.00000 | 24.40034 | 52.50013 | -0.0593 | 23.51679 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.00352 | 21.72882 | -0.9046 | 24.05811 |
February | 454.00000 | 20.10634 | 21.62543 | -0.8661 | 22.43787 |
March | 514.00000 | 21.00788 | 29.75580 | -0.5312 | 13.74615 |
April | 485.00000 | 21.92375 | 33.56031 | -0.2464 | 8.07821 |
May | 508.00000 | 23.49415 | 36.26208 | -0.7793 | 19.46811 |
June | 496.00000 | 24.12693 | 45.11663 | -0.4333 | 9.70388 |
July | 497.00000 | 24.36708 | 52.93527 | -0.2709 | 7.15843 |
August | 514.00000 | 24.19080 | 49.72398 | -0.3744 | 8.55678 |
September | 485.00000 | 23.74075 | 46.94409 | -0.6058 | 14.28907 |
October | 502.00000 | 22.07480 | 39.77448 | -0.1694 | 7.45557 |
November | 489.00000 | 20.88297 | 34.26562 | -0.5282 | 11.93583 |
December | 497.00000 | 20.10682 | 25.67625 | -0.8376 | 21.49848 |
Annual Sum or Average | 5943.00000 | 22.18548 | 36.54966 | -0.5437 | 13.98292 |
Minimum of Months | 454.00000 | 20.00352 | 21.62543 | -0.9046 | 7.15843 |
Maximum of Months | 514.00000 | 24.36708 | 52.93527 | -0.1694 | 24.05811 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.91860 | 20.71411 | -0.9170 | 24.48661 |
February | 385.00000 | 20.04643 | 20.63895 | -0.8676 | 22.50904 |
March | 433.00000 | 21.08771 | 28.56888 | -0.4909 | 12.64381 |
April | 410.00000 | 22.16053 | 32.05359 | -0.1630 | 8.22661 |
May | 430.00000 | 23.58563 | 34.94306 | -0.6934 | 18.22781 |
June | 418.00000 | 24.20847 | 44.32697 | -0.3471 | 9.35997 |
July | 422.00000 | 24.51209 | 52.03563 | -0.1656 | 7.21796 |
August | 433.00000 | 24.23760 | 48.95861 | -0.3052 | 8.41873 |
September | 410.00000 | 23.79702 | 46.07584 | -0.5356 | 13.76131 |
October | 427.00000 | 22.14453 | 38.48160 | -0.1368 | 7.54979 |
November | 417.00000 | 20.86173 | 32.97668 | -0.5301 | 12.09223 |
December | 422.00000 | 20.01346 | 24.67605 | -0.8584 | 22.12956 |
Annual Sum or Average | 5034.00000 | 22.22832 | 35.45944 | -0.4989 | 13.83754 |
Minimum of Months | 385.00000 | 19.91860 | 20.63895 | -0.9170 | 7.21796 |
Maximum of Months | 433.00000 | 24.51209 | 52.03563 | -0.1368 | 24.48661 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.49834 | 20.94825 | -0.7486 | 19.72613 |
February | 454.00000 | 20.58937 | 20.82168 | -0.7094 | 18.47972 |
March | 514.00000 | 21.86967 | 28.09558 | -0.2901 | 10.40110 |
April | 485.00000 | 22.53645 | 31.70714 | -0.0800 | 7.97239 |
May | 508.00000 | 23.64980 | 35.17815 | -0.6893 | 17.64115 |
June | 496.00000 | 24.13245 | 44.78457 | -0.4010 | 9.80918 |
July | 497.00000 | 24.41916 | 52.49243 | -0.2169 | 7.28789 |
August | 514.00000 | 24.26795 | 49.02937 | -0.2907 | 8.06665 |
September | 485.00000 | 24.03897 | 45.27761 | -0.4286 | 11.41213 |
October | 502.00000 | 22.85931 | 37.20628 | 0.04700 | 7.79996 |
November | 489.00000 | 21.57319 | 32.61189 | -0.3464 | 10.02748 |
December | 497.00000 | 20.53230 | 24.91869 | -0.7100 | 17.79472 |
Annual Sum or Average | 5943.00000 | 22.59648 | 35.35767 | -0.4036 | 12.16530 |
Minimum of Months | 454.00000 | 20.49834 | 20.82168 | -0.7486 | 7.28789 |
Maximum of Months | 514.00000 | 24.41916 | 52.49243 | 0.04700 | 19.72613 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05297 | 21.06158 | -0.8899 | 23.55665 |
February | 454.00000 | 20.20016 | 20.96744 | -0.8349 | 21.53761 |
March | 514.00000 | 21.25407 | 28.86959 | -0.4511 | 12.24426 |
April | 485.00000 | 22.11294 | 32.42758 | -0.1730 | 8.42594 |
May | 508.00000 | 23.47927 | 35.66303 | -0.7174 | 19.29580 |
June | 496.00000 | 24.10627 | 44.92379 | -0.3604 | 9.79929 |
July | 497.00000 | 24.37005 | 52.71860 | -0.2013 | 7.39475 |
August | 514.00000 | 24.17462 | 49.57647 | -0.3085 | 8.56952 |
September | 485.00000 | 23.71065 | 46.66966 | -0.5562 | 14.35311 |
October | 502.00000 | 22.05828 | 39.09527 | -0.1497 | 7.62795 |
November | 489.00000 | 20.90796 | 33.61341 | -0.5139 | 11.73735 |
December | 497.00000 | 20.14814 | 25.08444 | -0.8263 | 20.99958 |
Annual Sum or Average | 5943.00000 | 22.23107 | 35.99284 | -0.4964 | 13.74611 |
Minimum of Months | 454.00000 | 20.05297 | 20.96744 | -0.8899 | 7.39475 |
Maximum of Months | 514.00000 | 24.37005 | 52.71860 | -0.1497 | 23.55665 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.177792E+10 | 0.416558E+09 | 33.50 | 0.143688E+10 | 0.341047E+09 | 0.00 | 0.82 | 15-MAR-14:00 | 0.00 | 01-MAR-00:10 | 26119.74 | 15-MAR-14:00 | 26119.74 | 15-MAR-14:00 | 7990.62 | 14-MAR-11:00 | 6035.63 | 15-MAR-14:00 | 0.00 |
April | 0.609139E+09 | 0.154114E+09 | 34.17 | 0.540531E+09 | 68608528.40 | 0.00 | 0.42 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 11949.39 | 08-APR-13:30 | 11508.78 | 07-APR-13:00 | 2683.02 | 08-APR-14:00 | 2911.67 | 08-APR-13:30 | 0.00 |
May | 0.694770E+10 | 0.164441E+10 | 185.43 | 0.623800E+10 | 0.709702E+09 | 0.00 | 1.00 | 23-MAY-14:00 | 0.00 | 01-MAY-00:10 | 38280.80 | 24-MAY-05:03 | 35164.97 | 23-MAY-15:10 | 11819.52 | 24-MAY-05:03 | 7945.64 | 24-MAY-05:03 | 0.00 |
June | 0.348096E+11 | 0.774618E+10 | 373.29 | 0.261821E+11 | 0.862753E+10 | 0.00 | 1.00 | 01-JUN-14:20 | 0.00 | 01-JUN-00:10 | 93420.84 | 27-JUN-07:40 | 58271.45 | 12-JUN-15:10 | 53063.31 | 27-JUN-07:40 | 19169.87 | 27-JUN-07:40 | 0.00 |
July | 0.621910E+11 | 0.136533E+11 | 427.98 | 0.437522E+11 | 0.184387E+11 | 0.00 | 1.00 | 03-JUL-10:10 | 0.00 | 01-JUL-00:10 | 115026.51 | 20-JUL-06:03 | 61288.75 | 19-JUL-15:30 | 69350.09 | 20-JUL-05:03 | 23404.92 | 20-JUL-06:03 | 0.00 |
August | 0.528586E+11 | 0.116655E+11 | 422.75 | 0.405549E+11 | 0.123038E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 115059.47 | 14-AUG-08:00 | 61146.01 | 09-AUG-15:50 | 72248.36 | 14-AUG-04:03 | 23482.01 | 14-AUG-08:00 | 0.00 |
September | 0.231162E+11 | 0.512127E+10 | 303.99 | 0.172927E+11 | 0.582344E+10 | 0.00 | 1.00 | 08-SEP-12:10 | 0.00 | 01-SEP-00:10 | 80474.23 | 16-SEP-05:03 | 51911.49 | 21-SEP-16:00 | 44321.68 | 16-SEP-05:03 | 16789.18 | 16-SEP-05:03 | 0.00 |
October | 0.243859E+10 | 0.590281E+09 | 83.08 | 0.205086E+10 | 0.387728E+09 | 0.00 | 0.90 | 11-OCT-15:10 | 0.00 | 01-OCT-00:10 | 29443.72 | 11-OCT-15:10 | 29443.72 | 11-OCT-15:10 | 5502.69 | 12-OCT-15:00 | 6297.81 | 11-OCT-15:10 | 0.00 |
November | 0.410095E+09 | 0.103931E+09 | 18.83 | 0.289668E+09 | 0.120427E+09 | 0.00 | 0.35 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 10030.06 | 16-NOV-18:00 | 8033.59 | 16-NOV-13:00 | 2723.99 | 04-NOV-15:00 | 2481.89 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.185159E+12 | 0.410956E+11 | 1883.02 | 0.138338E+12 | 0.468210E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.621910E+11 | 0.136533E+11 | 427.98 | 0.437522E+11 | 0.184387E+11 | 0.00 | 1.00 | 0.00 | 115059.47 | 61288.75 | 72248.36 | 23482.01 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.169693E+10 | 0.394272E+09 | 33.50 | 0.138854E+10 | 0.308385E+09 | 0.00 | 0.91 | 15-MAR-13:50 | 0.00 | 01-MAR-00:10 | 26983.14 | 15-MAR-13:50 | 26983.14 | 15-MAR-13:50 | 7526.33 | 14-MAR-10:40 | 6073.73 | 15-MAR-14:00 | 0.00 |
April | 0.614316E+09 | 0.154936E+09 | 37.22 | 0.556160E+09 | 58156326.57 | 0.00 | 0.48 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 12678.71 | 08-APR-13:30 | 11163.13 | 08-APR-13:20 | 1987.94 | 08-APR-14:30 | 3041.42 | 08-APR-13:30 | 0.00 |
May | 0.702397E+10 | 0.165415E+10 | 197.03 | 0.631329E+10 | 0.710675E+09 | 0.00 | 1.00 | 10-MAY-14:00 | 0.00 | 01-MAY-00:10 | 35361.65 | 23-MAY-14:30 | 35361.65 | 23-MAY-14:30 | 6345.80 | 14-MAY-13:00 | 7519.39 | 10-MAY-15:00 | 0.00 |
June | 0.329140E+11 | 0.731018E+10 | 378.71 | 0.248822E+11 | 0.803178E+10 | 0.00 | 1.00 | 01-JUN-14:00 | 0.00 | 01-JUN-00:10 | 80061.28 | 27-JUN-07:40 | 55924.48 | 12-JUN-14:10 | 45456.39 | 27-JUN-07:40 | 17375.60 | 27-JUN-13:00 | 0.00 |
July | 0.568858E+11 | 0.124728E+11 | 431.70 | 0.400106E+11 | 0.168752E+11 | 0.00 | 1.00 | 02-JUL-15:32 | 0.00 | 01-JUL-00:10 | 104684.31 | 20-JUL-06:03 | 56930.03 | 21-JUL-13:40 | 62770.40 | 20-JUL-05:03 | 21636.61 | 21-JUL-05:03 | 0.00 |
August | 0.463431E+11 | 0.102427E+11 | 418.19 | 0.357314E+11 | 0.106117E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 104578.83 | 14-AUG-04:03 | 58610.69 | 09-AUG-15:20 | 65735.86 | 14-AUG-04:03 | 21264.68 | 15-AUG-14:30 | 0.00 |
September | 0.196575E+11 | 0.438301E+10 | 301.08 | 0.146531E+11 | 0.500435E+10 | 0.00 | 1.00 | 08-SEP-12:10 | 0.00 | 01-SEP-00:10 | 66938.75 | 15-SEP-11:00 | 47394.90 | 21-SEP-15:40 | 30047.76 | 15-SEP-11:00 | 13933.16 | 15-SEP-11:00 | 0.00 |
October | 0.214685E+10 | 0.523985E+09 | 83.89 | 0.177432E+10 | 0.372530E+09 | 0.00 | 0.81 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 23723.62 | 11-OCT-15:00 | 23723.62 | 11-OCT-15:00 | 5164.11 | 12-OCT-15:00 | 5196.87 | 11-OCT-15:00 | 0.00 |
November | 0.369972E+09 | 93869584.74 | 18.83 | 0.258440E+09 | 0.111532E+09 | 0.00 | 0.34 | 16-NOV-18:00 | 0.00 | 01-NOV-00:10 | 8676.55 | 16-NOV-18:00 | 6515.66 | 16-NOV-13:00 | 2559.82 | 04-NOV-15:00 | 2155.62 | 16-NOV-18:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.167652E+12 | 0.372300E+11 | 1900.15 | 0.125568E+12 | 0.420843E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.568858E+11 | 0.124728E+11 | 431.70 | 0.400106E+11 | 0.168752E+11 | 0.00 | 1.00 | 0.00 | 104684.31 | 58610.69 | 65735.86 | 21636.61 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.188565E+10 | 0.437083E+09 | 33.50 | 0.156272E+10 | 0.322921E+09 | 0.00 | 0.99 | 15-MAR-14:00 | 0.00 | 01-MAR-00:10 | 33839.39 | 15-MAR-14:00 | 33839.39 | 15-MAR-14:00 | 8297.98 | 14-MAR-10:50 | 7441.49 | 15-MAR-14:00 | 0.00 |
April | 0.644254E+09 | 0.163064E+09 | 37.08 | 0.571368E+09 | 72886520.45 | 0.00 | 0.46 | 08-APR-13:30 | 0.00 | 01-APR-00:10 | 13556.86 | 08-APR-13:30 | 11557.93 | 08-APR-13:20 | 2414.76 | 08-APR-14:00 | 3268.56 | 08-APR-13:30 | 0.00 |
May | 0.740420E+10 | 0.175170E+10 | 198.28 | 0.656933E+10 | 0.834877E+09 | 0.00 | 1.00 | 10-MAY-13:20 | 0.00 | 01-MAY-00:10 | 40225.11 | 10-MAY-14:30 | 40225.11 | 10-MAY-14:30 | 7231.66 | 14-MAY-13:40 | 8821.15 | 10-MAY-14:30 | 0.00 |
June | 0.353442E+11 | 0.787534E+10 | 377.14 | 0.265247E+11 | 0.881949E+10 | 0.00 | 1.00 | 01-JUN-14:00 | 0.00 | 01-JUN-00:10 | 117184.99 | 27-JUN-14:55 | 69932.83 | 27-JUN-15:43 | 65735.92 | 27-JUN-14:55 | 24344.28 | 27-JUN-15:40 | 0.00 |
July | 0.612064E+11 | 0.134664E+11 | 431.77 | 0.431509E+11 | 0.180556E+11 | 0.00 | 1.00 | 02-JUL-15:32 | 0.00 | 01-JUL-00:10 | 117258.77 | 20-JUL-05:03 | 68483.18 | 21-JUL-13:30 | 69997.28 | 20-JUL-05:03 | 24550.13 | 16-JUL-13:32 | 0.00 |
August | 0.490663E+11 | 0.109000E+11 | 416.69 | 0.377407E+11 | 0.113256E+11 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 117242.20 | 14-AUG-04:03 | 67731.71 | 09-AUG-15:10 | 73806.82 | 14-AUG-04:03 | 24039.09 | 15-AUG-14:20 | 0.00 |
September | 0.199311E+11 | 0.448402E+10 | 298.68 | 0.144910E+11 | 0.544014E+10 | 0.00 | 1.00 | 08-SEP-12:50 | 0.00 | 01-SEP-00:10 | 79019.18 | 15-SEP-12:30 | 53825.86 | 21-SEP-15:30 | 34989.98 | 15-SEP-12:30 | 16693.34 | 15-SEP-12:30 | 0.00 |
October | 0.208244E+10 | 0.513788E+09 | 82.28 | 0.166805E+10 | 0.414390E+09 | 0.00 | 0.73 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 | 23197.38 | 11-OCT-15:00 | 23197.38 | 11-OCT-15:00 | 5467.01 | 12-OCT-15:00 | 5205.64 | 11-OCT-15:00 | 0.00 |
November | 0.393591E+09 | 0.100152E+09 | 18.83 | 0.270347E+09 | 0.123244E+09 | 0.00 | 0.33 | 27-NOV-07:03 | 0.00 | 01-NOV-00:10 | 9369.53 | 27-NOV-07:03 | 7990.10 | 27-NOV-07:03 | 2820.70 | 04-NOV-15:00 | 2334.42 | 27-NOV-07:03 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.177958E+12 | 0.396916E+11 | 1894.26 | 0.132549E+12 | 0.454091E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.612064E+11 | 0.134664E+11 | 431.77 | 0.431509E+11 | 0.180556E+11 | 0.00 | 1.00 | 0.00 | 117258.77 | 69932.83 | 73806.82 | 24550.13 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 330.08 | 0.00 | 330.08 | 6.71 | 1866.40 | 0.00 | 0.00 | 0.00 |
February | 502.92 | 0.00 | 502.92 | 41.41 | 1741.62 | 0.00 | 0.00 | 0.00 |
March | 609.91 | 0.00 | 609.91 | 218.29 | 1245.88 | 0.00 | 0.00 | 0.00 |
April | 777.14 | 3.10 | 774.04 | 453.02 | 883.28 | 0.00 | 0.00 | 0.00 |
May | 903.00 | 38.29 | 864.71 | 733.69 | 580.84 | 0.00 | 0.00 | 0.00 |
June | 1086.12 | 92.46 | 993.67 | 1181.96 | 386.97 | 0.00 | 0.00 | 0.00 |
July | 1007.52 | 65.04 | 942.49 | 1259.80 | 273.43 | 0.00 | 0.00 | 0.00 |
August | 871.79 | 13.26 | 858.53 | 1032.90 | 358.71 | 0.00 | 0.00 | 0.00 |
September | 663.45 | 0.14 | 663.31 | 615.22 | 570.41 | 0.00 | 0.00 | 0.00 |
October | 495.96 | 0.00 | 495.96 | 269.82 | 869.93 | 0.00 | 0.00 | 0.00 |
November | 333.27 | 0.00 | 333.27 | 86.88 | 1122.09 | 0.00 | 0.00 | 0.00 |
December | 308.95 | 0.00 | 308.95 | 7.51 | 1769.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 658.15 | 17.77 | 640.38 | 494.97 | 968.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.95 | 0.00 | 308.95 | 6.71 | 273.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1086.12 | 92.46 | 993.67 | 1259.80 | 1866.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 402.70 | 129.85 | 272.85 | 165.90 | 1131.22 | 0.00 | 0.00 | 0.00 |
February | 590.88 | 177.31 | 413.57 | 297.65 | 1069.46 | 0.00 | 0.00 | 0.00 |
March | 847.90 | 355.09 | 492.81 | 687.76 | 765.95 | 0.00 | 0.00 | 0.00 |
April | 1122.25 | 495.87 | 626.38 | 1081.82 | 561.87 | 0.00 | 0.00 | 0.00 |
May | 1257.32 | 556.18 | 701.14 | 1379.79 | 393.45 | 0.00 | 0.00 | 0.00 |
June | 1404.21 | 620.59 | 783.62 | 1711.94 | 261.90 | 0.00 | 0.00 | 0.00 |
July | 1348.41 | 593.69 | 754.73 | 1762.02 | 183.54 | 0.00 | 0.00 | 0.00 |
August | 1217.77 | 511.15 | 706.62 | 1559.15 | 237.69 | 0.00 | 0.00 | 0.00 |
September | 1013.39 | 449.50 | 563.89 | 1180.11 | 365.36 | 0.00 | 0.00 | 0.00 |
October | 687.67 | 284.44 | 403.23 | 639.21 | 550.31 | 0.00 | 0.00 | 0.00 |
November | 390.06 | 125.13 | 264.93 | 258.31 | 715.16 | 0.00 | 0.00 | 0.00 |
December | 314.02 | 64.88 | 249.13 | 88.26 | 1108.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 884.36 | 364.52 | 519.84 | 904.23 | 609.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 314.02 | 64.88 | 249.13 | 88.26 | 183.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1404.21 | 620.59 | 783.62 | 1762.02 | 1131.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1419.34 | 828.51 | 590.83 | 1178.49 | 1597.09 | 0.00 | 0.00 | 0.00 |
February | 1620.54 | 781.41 | 839.13 | 1330.06 | 1567.76 | 0.00 | 0.00 | 0.00 |
March | 1977.97 | 1111.41 | 866.56 | 1980.61 | 1159.43 | 0.00 | 0.00 | 0.00 |
April | 1638.07 | 654.58 | 983.50 | 1710.53 | 920.00 | 0.00 | 0.00 | 0.00 |
May | 1433.46 | 416.34 | 1017.13 | 1613.09 | 639.73 | 0.00 | 0.00 | 0.00 |
June | 1392.86 | 295.15 | 1097.71 | 1738.76 | 423.66 | 0.00 | 0.00 | 0.00 |
July | 1421.89 | 344.99 | 1076.89 | 1957.30 | 295.89 | 0.00 | 0.00 | 0.00 |
August | 1596.30 | 517.56 | 1078.74 | 2164.42 | 379.82 | 0.00 | 0.00 | 0.00 |
September | 1856.02 | 904.02 | 952.00 | 2330.37 | 586.77 | 0.00 | 0.00 | 0.00 |
October | 1775.94 | 1014.45 | 761.49 | 1953.55 | 850.41 | 0.00 | 0.00 | 0.00 |
November | 1271.89 | 718.02 | 553.87 | 1238.40 | 1067.27 | 0.00 | 0.00 | 0.00 |
December | 1186.85 | 614.25 | 572.60 | 935.66 | 1564.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1548.78 | 683.03 | 865.75 | 1679.62 | 917.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1186.85 | 295.15 | 553.87 | 935.66 | 295.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1977.97 | 1111.41 | 1097.71 | 2330.37 | 1597.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 345.51 | 81.11 | 264.40 | 103.35 | 1174.50 | 0.00 | 0.00 | 0.00 |
February | 559.98 | 143.92 | 416.06 | 257.69 | 1104.93 | 0.00 | 0.00 | 0.00 |
March | 877.66 | 375.79 | 501.87 | 726.48 | 787.96 | 0.00 | 0.00 | 0.00 |
April | 1074.58 | 440.62 | 633.96 | 1037.40 | 588.30 | 0.00 | 0.00 | 0.00 |
May | 1267.64 | 572.89 | 694.75 | 1406.37 | 416.94 | 0.00 | 0.00 | 0.00 |
June | 1529.44 | 719.38 | 810.06 | 1889.76 | 285.49 | 0.00 | 0.00 | 0.00 |
July | 1367.38 | 599.50 | 767.87 | 1797.01 | 202.96 | 0.00 | 0.00 | 0.00 |
August | 1236.71 | 525.86 | 710.85 | 1601.56 | 254.54 | 0.00 | 0.00 | 0.00 |
September | 971.20 | 419.42 | 551.78 | 1136.76 | 384.21 | 0.00 | 0.00 | 0.00 |
October | 629.58 | 221.77 | 407.81 | 575.69 | 569.46 | 0.00 | 0.00 | 0.00 |
November | 373.09 | 107.51 | 265.58 | 239.36 | 729.57 | 0.00 | 0.00 | 0.00 |
December | 323.44 | 70.47 | 252.96 | 99.81 | 1125.80 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 881.13 | 357.55 | 523.58 | 909.40 | 633.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 323.44 | 70.47 | 252.96 | 99.81 | 202.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1529.44 | 719.38 | 810.06 | 1889.76 | 1174.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.02 | 0.00 | 110.02 | 1.40 | 637.31 | 0.00 | 0.00 | 0.00 |
February | 167.63 | 0.00 | 167.63 | 12.91 | 594.96 | 0.00 | 0.00 | 0.00 |
March | 203.29 | 0.00 | 203.29 | 76.79 | 421.47 | 0.00 | 0.00 | 0.00 |
April | 259.04 | 1.03 | 258.00 | 159.30 | 294.25 | 0.00 | 0.00 | 0.00 |
May | 300.99 | 12.76 | 288.22 | 259.08 | 186.57 | 0.00 | 0.00 | 0.00 |
June | 362.02 | 30.82 | 331.21 | 404.74 | 125.26 | 0.00 | 0.00 | 0.00 |
July | 335.83 | 21.68 | 314.15 | 429.29 | 87.69 | 0.00 | 0.00 | 0.00 |
August | 290.58 | 4.42 | 286.16 | 348.96 | 119.97 | 0.00 | 0.00 | 0.00 |
September | 221.14 | 0.05 | 221.09 | 204.63 | 201.33 | 0.00 | 0.00 | 0.00 |
October | 165.31 | 0.00 | 165.31 | 83.15 | 321.91 | 0.00 | 0.00 | 0.00 |
November | 111.08 | 0.00 | 111.08 | 25.22 | 409.43 | 0.00 | 0.00 | 0.00 |
December | 102.98 | 0.00 | 102.98 | 1.81 | 619.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 219.37 | 5.92 | 213.45 | 168.20 | 333.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 1.40 | 87.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.02 | 30.82 | 331.21 | 429.29 | 637.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.03 | 0.00 | 110.03 | 1.40 | 637.35 | 0.00 | 0.00 | 0.00 |
February | 167.64 | 0.00 | 167.64 | 12.91 | 594.99 | 0.00 | 0.00 | 0.00 |
March | 203.30 | 0.00 | 203.30 | 76.80 | 421.49 | 0.00 | 0.00 | 0.00 |
April | 259.05 | 1.03 | 258.02 | 159.31 | 294.27 | 0.00 | 0.00 | 0.00 |
May | 301.01 | 12.76 | 288.24 | 259.10 | 186.58 | 0.00 | 0.00 | 0.00 |
June | 362.05 | 30.82 | 331.23 | 404.77 | 125.27 | 0.00 | 0.00 | 0.00 |
July | 335.85 | 21.68 | 314.17 | 429.32 | 87.70 | 0.00 | 0.00 | 0.00 |
August | 290.60 | 4.42 | 286.18 | 348.99 | 119.98 | 0.00 | 0.00 | 0.00 |
September | 221.15 | 0.05 | 221.11 | 204.64 | 201.35 | 0.00 | 0.00 | 0.00 |
October | 165.32 | 0.00 | 165.32 | 83.16 | 321.93 | 0.00 | 0.00 | 0.00 |
November | 111.09 | 0.00 | 111.09 | 25.22 | 409.46 | 0.00 | 0.00 | 0.00 |
December | 102.98 | 0.00 | 102.98 | 1.81 | 619.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 219.39 | 5.92 | 213.46 | 168.21 | 333.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 1.40 | 87.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.05 | 30.82 | 331.23 | 429.32 | 637.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.03 | 0.00 | 110.03 | 1.40 | 637.35 | 0.00 | 0.00 | 0.00 |
February | 167.64 | 0.00 | 167.64 | 12.91 | 594.99 | 0.00 | 0.00 | 0.00 |
March | 203.30 | 0.00 | 203.30 | 76.80 | 421.49 | 0.00 | 0.00 | 0.00 |
April | 259.05 | 1.03 | 258.02 | 159.31 | 294.27 | 0.00 | 0.00 | 0.00 |
May | 301.01 | 12.76 | 288.24 | 259.10 | 186.58 | 0.00 | 0.00 | 0.00 |
June | 362.05 | 30.82 | 331.23 | 404.77 | 125.27 | 0.00 | 0.00 | 0.00 |
July | 335.85 | 21.68 | 314.17 | 429.32 | 87.70 | 0.00 | 0.00 | 0.00 |
August | 290.60 | 4.42 | 286.18 | 348.99 | 119.98 | 0.00 | 0.00 | 0.00 |
September | 221.15 | 0.05 | 221.11 | 204.64 | 201.35 | 0.00 | 0.00 | 0.00 |
October | 165.32 | 0.00 | 165.32 | 83.16 | 321.93 | 0.00 | 0.00 | 0.00 |
November | 111.09 | 0.00 | 111.09 | 25.22 | 409.46 | 0.00 | 0.00 | 0.00 |
December | 102.98 | 0.00 | 102.98 | 1.81 | 619.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 219.39 | 5.92 | 213.46 | 168.21 | 333.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.98 | 0.00 | 102.98 | 1.40 | 87.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 362.05 | 30.82 | 331.23 | 429.32 | 637.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 387.38 | 124.91 | 262.47 | 158.57 | 1120.26 | 0.00 | 0.00 | 0.00 |
February | 568.40 | 170.56 | 397.84 | 286.10 | 1058.53 | 0.00 | 0.00 | 0.00 |
March | 815.64 | 341.58 | 474.06 | 671.66 | 757.12 | 0.00 | 0.00 | 0.00 |
April | 1079.55 | 477.00 | 602.55 | 1052.99 | 555.96 | 0.00 | 0.00 | 0.00 |
May | 1209.49 | 535.02 | 674.47 | 1346.52 | 380.29 | 0.00 | 0.00 | 0.00 |
June | 1350.80 | 596.98 | 753.81 | 1663.45 | 254.82 | 0.00 | 0.00 | 0.00 |
July | 1297.12 | 571.10 | 726.02 | 1710.03 | 178.10 | 0.00 | 0.00 | 0.00 |
August | 1171.44 | 491.70 | 679.74 | 1508.32 | 238.13 | 0.00 | 0.00 | 0.00 |
September | 974.84 | 432.40 | 542.44 | 1133.25 | 382.69 | 0.00 | 0.00 | 0.00 |
October | 661.51 | 273.62 | 387.89 | 597.32 | 597.88 | 0.00 | 0.00 | 0.00 |
November | 375.22 | 120.37 | 254.85 | 238.01 | 758.12 | 0.00 | 0.00 | 0.00 |
December | 302.07 | 62.41 | 239.66 | 82.15 | 1119.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 850.72 | 350.66 | 500.06 | 873.84 | 614.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 302.07 | 62.41 | 239.66 | 82.15 | 178.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1350.80 | 596.98 | 753.81 | 1710.03 | 1120.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.32 | 4.94 | 10.38 | 6.27 | 44.29 | 0.00 | 0.00 | 0.00 |
February | 22.47 | 6.74 | 15.73 | 11.31 | 41.85 | 0.00 | 0.00 | 0.00 |
March | 32.25 | 13.51 | 18.74 | 26.56 | 29.94 | 0.00 | 0.00 | 0.00 |
April | 42.68 | 18.86 | 23.82 | 41.63 | 21.98 | 0.00 | 0.00 | 0.00 |
May | 47.82 | 21.15 | 26.67 | 53.24 | 15.04 | 0.00 | 0.00 | 0.00 |
June | 53.41 | 23.60 | 29.81 | 65.77 | 10.08 | 0.00 | 0.00 | 0.00 |
July | 51.29 | 22.58 | 28.71 | 67.61 | 7.04 | 0.00 | 0.00 | 0.00 |
August | 46.32 | 19.44 | 26.88 | 59.64 | 9.42 | 0.00 | 0.00 | 0.00 |
September | 38.54 | 17.10 | 21.45 | 44.81 | 15.13 | 0.00 | 0.00 | 0.00 |
October | 26.16 | 10.82 | 15.34 | 23.62 | 23.64 | 0.00 | 0.00 | 0.00 |
November | 14.84 | 4.76 | 10.08 | 9.41 | 29.98 | 0.00 | 0.00 | 0.00 |
December | 11.94 | 2.47 | 9.48 | 3.25 | 44.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.64 | 13.86 | 19.77 | 34.55 | 24.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.94 | 2.47 | 9.48 | 3.25 | 7.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.41 | 23.60 | 29.81 | 67.61 | 44.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 473.13 | 276.18 | 196.95 | 402.95 | 535.46 | 0.00 | 0.00 | 0.00 |
February | 540.20 | 260.48 | 279.72 | 457.20 | 524.57 | 0.00 | 0.00 | 0.00 |
March | 659.34 | 370.48 | 288.86 | 678.99 | 393.95 | 0.00 | 0.00 | 0.00 |
April | 546.04 | 218.20 | 327.84 | 586.77 | 307.22 | 0.00 | 0.00 | 0.00 |
May | 477.83 | 138.78 | 339.05 | 556.52 | 206.26 | 0.00 | 0.00 | 0.00 |
June | 464.30 | 98.39 | 365.91 | 594.34 | 137.75 | 0.00 | 0.00 | 0.00 |
July | 473.98 | 115.00 | 358.97 | 662.62 | 97.43 | 0.00 | 0.00 | 0.00 |
August | 532.12 | 172.53 | 359.59 | 728.28 | 130.59 | 0.00 | 0.00 | 0.00 |
September | 618.69 | 301.35 | 317.34 | 780.16 | 211.42 | 0.00 | 0.00 | 0.00 |
October | 592.00 | 338.16 | 253.84 | 652.02 | 314.95 | 0.00 | 0.00 | 0.00 |
November | 423.98 | 239.35 | 184.63 | 412.79 | 388.04 | 0.00 | 0.00 | 0.00 |
December | 395.63 | 204.76 | 190.87 | 316.62 | 535.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 516.28 | 227.68 | 288.59 | 569.76 | 314.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 395.63 | 98.39 | 184.63 | 316.62 | 97.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 659.34 | 370.48 | 365.91 | 780.16 | 535.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 473.13 | 276.18 | 196.95 | 402.95 | 535.46 | 0.00 | 0.00 | 0.00 |
February | 540.20 | 260.48 | 279.72 | 457.20 | 524.57 | 0.00 | 0.00 | 0.00 |
March | 659.34 | 370.48 | 288.86 | 678.99 | 393.95 | 0.00 | 0.00 | 0.00 |
April | 546.04 | 218.20 | 327.84 | 586.77 | 307.22 | 0.00 | 0.00 | 0.00 |
May | 477.83 | 138.78 | 339.05 | 556.52 | 206.26 | 0.00 | 0.00 | 0.00 |
June | 464.30 | 98.39 | 365.91 | 594.34 | 137.75 | 0.00 | 0.00 | 0.00 |
July | 473.98 | 115.00 | 358.97 | 662.62 | 97.43 | 0.00 | 0.00 | 0.00 |
August | 532.12 | 172.53 | 359.59 | 728.28 | 130.59 | 0.00 | 0.00 | 0.00 |
September | 618.69 | 301.35 | 317.34 | 780.16 | 211.42 | 0.00 | 0.00 | 0.00 |
October | 592.00 | 338.16 | 253.84 | 652.02 | 314.95 | 0.00 | 0.00 | 0.00 |
November | 423.98 | 239.35 | 184.63 | 412.79 | 388.04 | 0.00 | 0.00 | 0.00 |
December | 395.63 | 204.76 | 190.87 | 316.62 | 535.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 516.28 | 227.68 | 288.59 | 569.76 | 314.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 395.63 | 98.39 | 184.63 | 316.62 | 97.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 659.34 | 370.48 | 365.91 | 780.16 | 535.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 473.10 | 276.16 | 196.94 | 402.93 | 535.43 | 0.00 | 0.00 | 0.00 |
February | 540.16 | 260.46 | 279.70 | 457.17 | 524.54 | 0.00 | 0.00 | 0.00 |
March | 659.30 | 370.46 | 288.84 | 678.95 | 393.92 | 0.00 | 0.00 | 0.00 |
April | 546.01 | 218.19 | 327.82 | 586.73 | 307.20 | 0.00 | 0.00 | 0.00 |
May | 477.80 | 138.77 | 339.03 | 556.49 | 206.24 | 0.00 | 0.00 | 0.00 |
June | 464.27 | 98.38 | 365.89 | 594.30 | 137.74 | 0.00 | 0.00 | 0.00 |
July | 473.95 | 114.99 | 358.95 | 662.58 | 97.43 | 0.00 | 0.00 | 0.00 |
August | 532.08 | 172.51 | 359.57 | 728.24 | 130.58 | 0.00 | 0.00 | 0.00 |
September | 618.65 | 301.33 | 317.32 | 780.12 | 211.41 | 0.00 | 0.00 | 0.00 |
October | 591.96 | 338.14 | 253.82 | 651.98 | 314.93 | 0.00 | 0.00 | 0.00 |
November | 423.95 | 239.33 | 184.62 | 412.76 | 388.02 | 0.00 | 0.00 | 0.00 |
December | 395.61 | 204.74 | 190.86 | 316.60 | 535.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 516.24 | 227.67 | 288.57 | 569.72 | 314.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 395.61 | 98.38 | 184.62 | 316.60 | 97.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 659.30 | 370.46 | 365.89 | 780.12 | 535.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 332.37 | 78.03 | 254.34 | 99.65 | 1158.52 | 0.00 | 0.00 | 0.00 |
February | 538.67 | 138.44 | 400.23 | 251.27 | 1091.23 | 0.00 | 0.00 | 0.00 |
March | 844.27 | 361.50 | 482.78 | 713.66 | 780.14 | 0.00 | 0.00 | 0.00 |
April | 1033.70 | 423.86 | 609.84 | 1014.52 | 580.30 | 0.00 | 0.00 | 0.00 |
May | 1219.41 | 551.09 | 668.32 | 1372.49 | 405.07 | 0.00 | 0.00 | 0.00 |
June | 1471.26 | 692.02 | 779.24 | 1835.00 | 281.31 | 0.00 | 0.00 | 0.00 |
July | 1315.36 | 576.70 | 738.66 | 1743.76 | 198.85 | 0.00 | 0.00 | 0.00 |
August | 1189.67 | 505.85 | 683.81 | 1547.77 | 257.09 | 0.00 | 0.00 | 0.00 |
September | 934.26 | 403.46 | 530.79 | 1090.17 | 403.38 | 0.00 | 0.00 | 0.00 |
October | 605.63 | 213.34 | 392.29 | 539.57 | 615.41 | 0.00 | 0.00 | 0.00 |
November | 358.90 | 103.42 | 255.48 | 221.97 | 771.12 | 0.00 | 0.00 | 0.00 |
December | 311.13 | 67.79 | 243.34 | 94.63 | 1135.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 847.61 | 343.95 | 503.66 | 880.39 | 637.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 311.13 | 67.79 | 243.34 | 94.63 | 198.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1471.26 | 692.02 | 779.24 | 1835.00 | 1158.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 13.14 | 3.09 | 10.06 | 3.94 | 45.81 | 0.00 | 0.00 | 0.00 |
February | 21.30 | 5.47 | 15.82 | 9.93 | 43.15 | 0.00 | 0.00 | 0.00 |
March | 33.38 | 14.29 | 19.09 | 28.22 | 30.85 | 0.00 | 0.00 | 0.00 |
April | 40.87 | 16.76 | 24.11 | 40.11 | 22.94 | 0.00 | 0.00 | 0.00 |
May | 48.21 | 21.79 | 26.42 | 54.27 | 16.02 | 0.00 | 0.00 | 0.00 |
June | 58.17 | 27.36 | 30.81 | 72.55 | 11.12 | 0.00 | 0.00 | 0.00 |
July | 52.01 | 22.80 | 29.21 | 68.95 | 7.86 | 0.00 | 0.00 | 0.00 |
August | 47.04 | 20.00 | 27.04 | 61.20 | 10.17 | 0.00 | 0.00 | 0.00 |
September | 36.94 | 15.95 | 20.99 | 43.10 | 15.95 | 0.00 | 0.00 | 0.00 |
October | 23.95 | 8.44 | 15.51 | 21.33 | 24.33 | 0.00 | 0.00 | 0.00 |
November | 14.19 | 4.09 | 10.10 | 8.78 | 30.49 | 0.00 | 0.00 | 0.00 |
December | 12.30 | 2.68 | 9.62 | 3.74 | 44.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.51 | 13.60 | 19.91 | 34.81 | 25.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.30 | 2.68 | 9.62 | 3.74 | 7.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.17 | 27.36 | 30.81 | 72.55 | 45.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 330.08 | 0.00 | 330.08 | 4.00 | 1934.98 | 0.00 | 0.00 | 0.00 |
February | 502.92 | 0.00 | 502.92 | 34.79 | 1810.37 | 0.00 | 0.00 | 0.00 |
March | 609.91 | 0.00 | 609.91 | 208.86 | 1314.06 | 0.00 | 0.00 | 0.00 |
April | 777.14 | 3.10 | 774.04 | 436.28 | 941.04 | 0.00 | 0.00 | 0.00 |
May | 903.00 | 38.29 | 864.71 | 720.85 | 612.35 | 0.00 | 0.00 | 0.00 |
June | 1086.12 | 92.46 | 993.67 | 1180.71 | 400.11 | 0.00 | 0.00 | 0.00 |
July | 1007.52 | 65.04 | 942.49 | 1263.79 | 280.19 | 0.00 | 0.00 | 0.00 |
August | 871.79 | 13.26 | 858.53 | 1032.51 | 371.97 | 0.00 | 0.00 | 0.00 |
September | 663.45 | 0.14 | 663.31 | 605.25 | 608.16 | 0.00 | 0.00 | 0.00 |
October | 495.96 | 0.00 | 495.96 | 249.30 | 947.67 | 0.00 | 0.00 | 0.00 |
November | 333.27 | 0.00 | 333.27 | 75.78 | 1210.38 | 0.00 | 0.00 | 0.00 |
December | 308.95 | 0.00 | 308.95 | 5.36 | 1852.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 658.15 | 17.77 | 640.38 | 487.51 | 1019.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.95 | 0.00 | 308.95 | 4.00 | 280.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1086.12 | 92.46 | 993.67 | 1263.79 | 1934.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 402.70 | 129.85 | 272.85 | 161.08 | 1174.06 | 0.00 | 0.00 | 0.00 |
February | 590.88 | 177.31 | 413.57 | 289.17 | 1111.25 | 0.00 | 0.00 | 0.00 |
March | 847.90 | 355.09 | 492.81 | 677.75 | 807.62 | 0.00 | 0.00 | 0.00 |
April | 1122.25 | 495.87 | 626.38 | 1070.40 | 594.79 | 0.00 | 0.00 | 0.00 |
May | 1257.32 | 556.18 | 701.14 | 1374.56 | 412.42 | 0.00 | 0.00 | 0.00 |
June | 1404.21 | 620.59 | 783.62 | 1713.14 | 270.09 | 0.00 | 0.00 | 0.00 |
July | 1348.41 | 593.69 | 754.73 | 1765.94 | 187.78 | 0.00 | 0.00 | 0.00 |
August | 1217.77 | 511.15 | 706.62 | 1560.53 | 245.73 | 0.00 | 0.00 | 0.00 |
September | 1013.39 | 449.50 | 563.89 | 1174.62 | 386.41 | 0.00 | 0.00 | 0.00 |
October | 687.67 | 284.44 | 403.23 | 623.87 | 595.45 | 0.00 | 0.00 | 0.00 |
November | 390.06 | 125.13 | 264.93 | 248.02 | 769.12 | 0.00 | 0.00 | 0.00 |
December | 314.02 | 64.88 | 249.13 | 84.16 | 1159.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 884.36 | 364.52 | 519.84 | 898.54 | 640.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 314.02 | 64.88 | 249.13 | 84.16 | 187.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1404.21 | 620.59 | 783.62 | 1765.94 | 1174.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1419.34 | 828.51 | 590.83 | 1166.58 | 1662.80 | 0.00 | 0.00 | 0.00 |
February | 1620.54 | 781.41 | 839.13 | 1315.57 | 1633.25 | 0.00 | 0.00 | 0.00 |
March | 1977.97 | 1111.41 | 866.56 | 1965.32 | 1226.00 | 0.00 | 0.00 | 0.00 |
April | 1638.07 | 654.58 | 983.50 | 1695.47 | 976.94 | 0.00 | 0.00 | 0.00 |
May | 1433.46 | 416.34 | 1017.13 | 1605.80 | 675.04 | 0.00 | 0.00 | 0.00 |
June | 1392.86 | 295.15 | 1097.71 | 1740.37 | 440.71 | 0.00 | 0.00 | 0.00 |
July | 1421.89 | 344.99 | 1076.89 | 1962.88 | 305.00 | 0.00 | 0.00 | 0.00 |
August | 1596.30 | 517.56 | 1078.74 | 2166.69 | 394.75 | 0.00 | 0.00 | 0.00 |
September | 1856.02 | 904.02 | 952.00 | 2324.19 | 622.41 | 0.00 | 0.00 | 0.00 |
October | 1775.94 | 1014.45 | 761.49 | 1931.48 | 921.90 | 0.00 | 0.00 | 0.00 |
November | 1271.89 | 718.02 | 553.87 | 1219.08 | 1150.47 | 0.00 | 0.00 | 0.00 |
December | 1186.85 | 614.25 | 572.60 | 922.51 | 1640.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1548.78 | 683.03 | 865.75 | 1670.05 | 967.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1186.85 | 295.15 | 553.87 | 922.51 | 305.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1977.97 | 1111.41 | 1097.71 | 2324.19 | 1662.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 345.51 | 81.11 | 264.40 | 100.20 | 1217.51 | 0.00 | 0.00 | 0.00 |
February | 559.98 | 143.92 | 416.06 | 251.98 | 1147.93 | 0.00 | 0.00 | 0.00 |
March | 877.66 | 375.79 | 501.87 | 719.10 | 832.04 | 0.00 | 0.00 | 0.00 |
April | 1074.58 | 440.62 | 633.96 | 1027.66 | 625.02 | 0.00 | 0.00 | 0.00 |
May | 1267.64 | 572.89 | 694.75 | 1400.19 | 439.90 | 0.00 | 0.00 | 0.00 |
June | 1529.44 | 719.38 | 810.06 | 1890.98 | 296.61 | 0.00 | 0.00 | 0.00 |
July | 1367.38 | 599.50 | 767.87 | 1800.62 | 209.14 | 0.00 | 0.00 | 0.00 |
August | 1236.71 | 525.86 | 710.85 | 1602.04 | 264.41 | 0.00 | 0.00 | 0.00 |
September | 971.20 | 419.42 | 551.78 | 1130.06 | 408.98 | 0.00 | 0.00 | 0.00 |
October | 629.58 | 221.77 | 407.81 | 562.05 | 618.15 | 0.00 | 0.00 | 0.00 |
November | 373.09 | 107.51 | 265.58 | 230.43 | 785.12 | 0.00 | 0.00 | 0.00 |
December | 323.44 | 70.47 | 252.96 | 96.33 | 1177.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 881.13 | 357.55 | 523.58 | 904.45 | 666.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 323.44 | 70.47 | 252.96 | 96.33 | 209.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1529.44 | 719.38 | 810.06 | 1890.98 | 1217.51 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.884097E+09 | 0.00 | 0.884097E+09 | 17978040.71 | 0.499897E+10 |
February | 0.121667E+10 | 0.00 | 0.121667E+10 | 0.100178E+09 | 0.421333E+10 |
March | 0.163357E+10 | 0.00 | 0.163357E+10 | 0.584677E+09 | 0.333698E+10 |
April | 0.201436E+10 | 8038086.86 | 0.200632E+10 | 0.117423E+10 | 0.228945E+10 |
May | 0.241860E+10 | 0.102563E+09 | 0.231604E+10 | 0.196513E+10 | 0.155573E+10 |
June | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.306363E+10 | 0.100302E+10 |
July | 0.269855E+10 | 0.174197E+09 | 0.252435E+10 | 0.337426E+10 | 0.732354E+09 |
August | 0.233500E+10 | 35521897.19 | 0.229947E+10 | 0.276651E+10 | 0.960776E+09 |
September | 0.171966E+10 | 357270.95 | 0.171930E+10 | 0.159465E+10 | 0.147851E+10 |
October | 0.132837E+10 | 0.00 | 0.132837E+10 | 0.722675E+09 | 0.233001E+10 |
November | 0.863837E+09 | 0.00 | 0.863837E+09 | 0.225196E+09 | 0.290846E+10 |
December | 0.827489E+09 | 0.00 | 0.827489E+09 | 20126936.61 | 0.473898E+10 |
Annual Sum or Average | 0.207554E+11 | 0.560324E+09 | 0.201951E+11 | 0.156092E+11 | 0.305466E+11 |
Minimum of Months | 0.827489E+09 | 0.00 | 0.827489E+09 | 17978040.71 | 0.732354E+09 |
Maximum of Months | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.337426E+10 | 0.499897E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107859E+10 | 0.347796E+09 | 0.730792E+09 | 0.444334E+09 | 0.302986E+10 |
February | 0.142946E+10 | 0.428945E+09 | 0.100052E+10 | 0.720066E+09 | 0.258725E+10 |
March | 0.227101E+10 | 0.951083E+09 | 0.131993E+10 | 0.184209E+10 | 0.205151E+10 |
April | 0.290887E+10 | 0.128529E+10 | 0.162358E+10 | 0.280409E+10 | 0.145636E+10 |
May | 0.336761E+10 | 0.148967E+10 | 0.187794E+10 | 0.369562E+10 | 0.105383E+10 |
June | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.443735E+10 | 0.678850E+09 |
July | 0.361159E+10 | 0.159013E+10 | 0.202146E+10 | 0.471939E+10 | 0.491590E+09 |
August | 0.326166E+10 | 0.136907E+10 | 0.189260E+10 | 0.417603E+10 | 0.636634E+09 |
September | 0.262671E+10 | 0.116511E+10 | 0.146161E+10 | 0.305884E+10 | 0.947024E+09 |
October | 0.184186E+10 | 0.761840E+09 | 0.108002E+10 | 0.171206E+10 | 0.147394E+10 |
November | 0.101103E+10 | 0.324327E+09 | 0.686706E+09 | 0.669528E+09 | 0.185369E+10 |
December | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.236405E+09 | 0.296803E+10 |
Annual Sum or Average | 0.278892E+11 | 0.114956E+11 | 0.163936E+11 | 0.285158E+11 | 0.192285E+11 |
Minimum of Months | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.236405E+09 | 0.491590E+09 |
Maximum of Months | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.471939E+10 | 0.302986E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380157E+10 | 0.221909E+10 | 0.158248E+10 | 0.315646E+10 | 0.427766E+10 |
February | 0.392040E+10 | 0.189038E+10 | 0.203002E+10 | 0.321768E+10 | 0.379272E+10 |
March | 0.529780E+10 | 0.297679E+10 | 0.232100E+10 | 0.530486E+10 | 0.310542E+10 |
April | 0.424589E+10 | 0.169666E+10 | 0.254922E+10 | 0.443371E+10 | 0.238465E+10 |
May | 0.383938E+10 | 0.111511E+10 | 0.272427E+10 | 0.432051E+10 | 0.171345E+10 |
June | 0.361030E+10 | 0.765037E+09 | 0.284527E+10 | 0.450688E+10 | 0.109812E+10 |
July | 0.380838E+10 | 0.924034E+09 | 0.288435E+10 | 0.524244E+10 | 0.792511E+09 |
August | 0.427553E+10 | 0.138623E+10 | 0.288930E+10 | 0.579718E+10 | 0.101731E+10 |
September | 0.481081E+10 | 0.234322E+10 | 0.246759E+10 | 0.604031E+10 | 0.152090E+10 |
October | 0.475667E+10 | 0.271710E+10 | 0.203957E+10 | 0.523238E+10 | 0.227774E+10 |
November | 0.329673E+10 | 0.186112E+10 | 0.143562E+10 | 0.320993E+10 | 0.276636E+10 |
December | 0.317887E+10 | 0.164521E+10 | 0.153366E+10 | 0.250607E+10 | 0.419140E+10 |
Annual Sum or Average | 0.488423E+11 | 0.215400E+11 | 0.273024E+11 | 0.529684E+11 | 0.289382E+11 |
Minimum of Months | 0.317887E+10 | 0.765037E+09 | 0.143562E+10 | 0.250607E+10 | 0.792511E+09 |
Maximum of Months | 0.529780E+10 | 0.297679E+10 | 0.288930E+10 | 0.604031E+10 | 0.427766E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.925412E+09 | 0.217250E+09 | 0.708162E+09 | 0.276804E+09 | 0.314577E+10 |
February | 0.135469E+10 | 0.348165E+09 | 0.100653E+10 | 0.623408E+09 | 0.267304E+10 |
March | 0.235073E+10 | 0.100652E+10 | 0.134420E+10 | 0.194581E+10 | 0.211047E+10 |
April | 0.278531E+10 | 0.114208E+10 | 0.164322E+10 | 0.268895E+10 | 0.152488E+10 |
May | 0.339524E+10 | 0.153442E+10 | 0.186081E+10 | 0.376683E+10 | 0.111672E+10 |
June | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.489826E+10 | 0.739984E+09 |
July | 0.366239E+10 | 0.160571E+10 | 0.205667E+10 | 0.481310E+10 | 0.543615E+09 |
August | 0.331241E+10 | 0.140847E+10 | 0.190395E+10 | 0.428963E+10 | 0.681764E+09 |
September | 0.251736E+10 | 0.108713E+10 | 0.143022E+10 | 0.294647E+10 | 0.995878E+09 |
October | 0.168627E+10 | 0.593999E+09 | 0.109227E+10 | 0.154194E+10 | 0.152525E+10 |
November | 0.967054E+09 | 0.278670E+09 | 0.688384E+09 | 0.620411E+09 | 0.189105E+10 |
December | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.267343E+09 | 0.301534E+10 |
Annual Sum or Average | 0.277875E+11 | 0.112758E+11 | 0.165116E+11 | 0.286790E+11 | 0.199638E+11 |
Minimum of Months | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.267343E+09 | 0.543615E+09 |
Maximum of Months | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.489826E+10 | 0.314577E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294685E+09 | 0.00 | 0.294685E+09 | 3746719.88 | 0.170697E+10 |
February | 0.405539E+09 | 0.00 | 0.405539E+09 | 31224462.00 | 0.143932E+10 |
March | 0.544498E+09 | 0.00 | 0.544498E+09 | 0.205682E+09 | 0.112885E+10 |
April | 0.671421E+09 | 2679235.52 | 0.668742E+09 | 0.412904E+09 | 0.762700E+09 |
May | 0.806163E+09 | 34185907.45 | 0.771977E+09 | 0.693916E+09 | 0.499700E+09 |
June | 0.938366E+09 | 79878478.38 | 0.858487E+09 | 0.104909E+10 | 0.324676E+09 |
July | 0.899474E+09 | 58063085.82 | 0.841411E+09 | 0.114982E+10 | 0.234869E+09 |
August | 0.778295E+09 | 11840072.19 | 0.766455E+09 | 0.934667E+09 | 0.321335E+09 |
September | 0.573193E+09 | 119084.68 | 0.573074E+09 | 0.530404E+09 | 0.521856E+09 |
October | 0.442769E+09 | 0.00 | 0.442769E+09 | 0.222719E+09 | 0.862199E+09 |
November | 0.287932E+09 | 0.00 | 0.287932E+09 | 65365401.11 | 0.106125E+10 |
December | 0.275817E+09 | 0.00 | 0.275817E+09 | 4850618.53 | 0.165868E+10 |
Annual Sum or Average | 0.691815E+10 | 0.186766E+09 | 0.673139E+10 | 0.530439E+10 | 0.105224E+11 |
Minimum of Months | 0.275817E+09 | 0.00 | 0.275817E+09 | 3746719.88 | 0.234869E+09 |
Maximum of Months | 0.938366E+09 | 79878478.38 | 0.858487E+09 | 0.114982E+10 | 0.170697E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294704E+09 | 0.00 | 0.294704E+09 | 3746956.67 | 0.170708E+10 |
February | 0.405565E+09 | 0.00 | 0.405565E+09 | 31226435.34 | 0.143941E+10 |
March | 0.544532E+09 | 0.00 | 0.544532E+09 | 0.205695E+09 | 0.112892E+10 |
April | 0.671463E+09 | 2679404.84 | 0.668784E+09 | 0.412930E+09 | 0.762748E+09 |
May | 0.806214E+09 | 34188067.94 | 0.772026E+09 | 0.693960E+09 | 0.499731E+09 |
June | 0.938425E+09 | 79883526.57 | 0.858542E+09 | 0.104916E+10 | 0.324696E+09 |
July | 0.899531E+09 | 58066755.31 | 0.841464E+09 | 0.114989E+10 | 0.234883E+09 |
August | 0.778344E+09 | 11840820.47 | 0.766504E+09 | 0.934726E+09 | 0.321356E+09 |
September | 0.573229E+09 | 119092.21 | 0.573110E+09 | 0.530438E+09 | 0.521889E+09 |
October | 0.442797E+09 | 0.00 | 0.442797E+09 | 0.222733E+09 | 0.862253E+09 |
November | 0.287950E+09 | 0.00 | 0.287950E+09 | 65369532.09 | 0.106131E+10 |
December | 0.275834E+09 | 0.00 | 0.275834E+09 | 4850925.08 | 0.165878E+10 |
Annual Sum or Average | 0.691859E+10 | 0.186778E+09 | 0.673181E+10 | 0.530472E+10 | 0.105231E+11 |
Minimum of Months | 0.275834E+09 | 0.00 | 0.275834E+09 | 3746956.67 | 0.234883E+09 |
Maximum of Months | 0.938425E+09 | 79883526.57 | 0.858542E+09 | 0.114989E+10 | 0.170708E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.294704E+09 | 0.00 | 0.294704E+09 | 3746956.67 | 0.170708E+10 |
February | 0.405565E+09 | 0.00 | 0.405565E+09 | 31226435.34 | 0.143941E+10 |
March | 0.544532E+09 | 0.00 | 0.544532E+09 | 0.205695E+09 | 0.112892E+10 |
April | 0.671463E+09 | 2679404.84 | 0.668784E+09 | 0.412930E+09 | 0.762748E+09 |
May | 0.806214E+09 | 34188067.94 | 0.772026E+09 | 0.693960E+09 | 0.499731E+09 |
June | 0.938425E+09 | 79883526.57 | 0.858542E+09 | 0.104916E+10 | 0.324696E+09 |
July | 0.899531E+09 | 58066755.31 | 0.841464E+09 | 0.114989E+10 | 0.234883E+09 |
August | 0.778344E+09 | 11840820.47 | 0.766504E+09 | 0.934726E+09 | 0.321356E+09 |
September | 0.573229E+09 | 119092.21 | 0.573110E+09 | 0.530438E+09 | 0.521889E+09 |
October | 0.442797E+09 | 0.00 | 0.442797E+09 | 0.222733E+09 | 0.862253E+09 |
November | 0.287950E+09 | 0.00 | 0.287950E+09 | 65369532.09 | 0.106131E+10 |
December | 0.275834E+09 | 0.00 | 0.275834E+09 | 4850925.08 | 0.165878E+10 |
Annual Sum or Average | 0.691859E+10 | 0.186778E+09 | 0.673181E+10 | 0.530472E+10 | 0.105231E+11 |
Minimum of Months | 0.275834E+09 | 0.00 | 0.275834E+09 | 3746956.67 | 0.234883E+09 |
Maximum of Months | 0.938425E+09 | 79883526.57 | 0.858542E+09 | 0.114989E+10 | 0.170708E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.103756E+10 | 0.334564E+09 | 0.702991E+09 | 0.424717E+09 | 0.300051E+10 |
February | 0.137508E+10 | 0.412626E+09 | 0.962454E+09 | 0.692124E+09 | 0.256079E+10 |
March | 0.218462E+10 | 0.914899E+09 | 0.126972E+10 | 0.179897E+10 | 0.202786E+10 |
April | 0.279820E+10 | 0.123639E+10 | 0.156181E+10 | 0.272934E+10 | 0.144106E+10 |
May | 0.323949E+10 | 0.143299E+10 | 0.180650E+10 | 0.360651E+10 | 0.101856E+10 |
June | 0.350126E+10 | 0.154738E+10 | 0.195388E+10 | 0.431167E+10 | 0.660503E+09 |
July | 0.347420E+10 | 0.152963E+10 | 0.194457E+10 | 0.458014E+10 | 0.477018E+09 |
August | 0.313758E+10 | 0.131698E+10 | 0.182060E+10 | 0.403987E+10 | 0.637806E+09 |
September | 0.252679E+10 | 0.112078E+10 | 0.140601E+10 | 0.293739E+10 | 0.991936E+09 |
October | 0.177179E+10 | 0.732856E+09 | 0.103893E+10 | 0.159985E+10 | 0.160137E+10 |
November | 0.972571E+09 | 0.311988E+09 | 0.660583E+09 | 0.616925E+09 | 0.196503E+10 |
December | 0.809068E+09 | 0.167170E+09 | 0.641898E+09 | 0.220038E+09 | 0.299965E+10 |
Annual Sum or Average | 0.268282E+11 | 0.110583E+11 | 0.157699E+11 | 0.275576E+11 | 0.193821E+11 |
Minimum of Months | 0.809068E+09 | 0.167170E+09 | 0.641898E+09 | 0.220038E+09 | 0.477018E+09 |
Maximum of Months | 0.350126E+10 | 0.154738E+10 | 0.195388E+10 | 0.458014E+10 | 0.300051E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41024007.43 | 13228371.45 | 27795635.98 | 16792936.19 | 0.118637E+09 |
February | 54369427.35 | 16314846.49 | 38054580.86 | 27365949.52 | 0.101251E+09 |
March | 86377782.88 | 36174296.78 | 50203486.10 | 71129586.34 | 80179672.46 |
April | 0.110638E+09 | 48885792.30 | 61752691.01 | 0.107916E+09 | 56978221.31 |
May | 0.128087E+09 | 56659274.04 | 71427368.49 | 0.142598E+09 | 40272889.66 |
June | 0.138437E+09 | 61181866.60 | 77254827.74 | 0.170480E+09 | 26115674.96 |
July | 0.137367E+09 | 60480322.99 | 76886380.32 | 0.181095E+09 | 18860845.65 |
August | 0.124057E+09 | 52072164.91 | 71985038.67 | 0.159733E+09 | 25218270.13 |
September | 99906859.06 | 44314631.90 | 55592227.15 | 0.116142E+09 | 39220273.19 |
October | 70054905.41 | 28976462.07 | 41078443.35 | 63256705.78 | 63316772.32 |
November | 38454578.54 | 12335725.91 | 26118852.63 | 24392652.36 | 77695686.24 |
December | 31989832.31 | 6609754.45 | 25380077.86 | 8700113.64 | 0.118603E+09 |
Annual Sum or Average | 0.106076E+10 | 0.437234E+09 | 0.623530E+09 | 0.108960E+10 | 0.766350E+09 |
Minimum of Months | 31989832.31 | 6609754.45 | 25380077.86 | 8700113.64 | 18860845.65 |
Maximum of Months | 0.138437E+09 | 61181866.60 | 77254827.74 | 0.181095E+09 | 0.118637E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126723E+10 | 0.739720E+09 | 0.527511E+09 | 0.107926E+10 | 0.143418E+10 |
February | 0.130684E+10 | 0.630147E+09 | 0.676693E+09 | 0.110606E+10 | 0.126905E+10 |
March | 0.176599E+10 | 0.992297E+09 | 0.773690E+09 | 0.181860E+10 | 0.105515E+10 |
April | 0.141534E+10 | 0.565573E+09 | 0.849765E+09 | 0.152091E+10 | 0.796313E+09 |
May | 0.127983E+10 | 0.371717E+09 | 0.908114E+09 | 0.149060E+10 | 0.552434E+09 |
June | 0.120347E+10 | 0.255021E+09 | 0.948447E+09 | 0.154052E+10 | 0.357049E+09 |
July | 0.126950E+10 | 0.308022E+09 | 0.961475E+09 | 0.177476E+10 | 0.260963E+09 |
August | 0.142522E+10 | 0.462092E+09 | 0.963127E+09 | 0.195063E+10 | 0.349766E+09 |
September | 0.160365E+10 | 0.781097E+09 | 0.822554E+09 | 0.202219E+10 | 0.548001E+09 |
October | 0.158561E+10 | 0.905728E+09 | 0.679877E+09 | 0.174638E+10 | 0.843571E+09 |
November | 0.109895E+10 | 0.620392E+09 | 0.478554E+09 | 0.106995E+10 | 0.100580E+10 |
December | 0.105966E+10 | 0.548420E+09 | 0.511236E+09 | 0.848043E+09 | 0.143535E+10 |
Annual Sum or Average | 0.162813E+11 | 0.718023E+10 | 0.910104E+10 | 0.179679E+11 | 0.990763E+10 |
Minimum of Months | 0.105966E+10 | 0.255021E+09 | 0.478554E+09 | 0.848043E+09 | 0.260963E+09 |
Maximum of Months | 0.176599E+10 | 0.992297E+09 | 0.963127E+09 | 0.202219E+10 | 0.143535E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126723E+10 | 0.739720E+09 | 0.527511E+09 | 0.107926E+10 | 0.143418E+10 |
February | 0.130684E+10 | 0.630147E+09 | 0.676693E+09 | 0.110606E+10 | 0.126905E+10 |
March | 0.176599E+10 | 0.992297E+09 | 0.773690E+09 | 0.181860E+10 | 0.105515E+10 |
April | 0.141534E+10 | 0.565573E+09 | 0.849765E+09 | 0.152091E+10 | 0.796313E+09 |
May | 0.127983E+10 | 0.371717E+09 | 0.908114E+09 | 0.149060E+10 | 0.552434E+09 |
June | 0.120347E+10 | 0.255021E+09 | 0.948447E+09 | 0.154052E+10 | 0.357049E+09 |
July | 0.126950E+10 | 0.308022E+09 | 0.961475E+09 | 0.177476E+10 | 0.260963E+09 |
August | 0.142522E+10 | 0.462092E+09 | 0.963127E+09 | 0.195063E+10 | 0.349766E+09 |
September | 0.160365E+10 | 0.781097E+09 | 0.822554E+09 | 0.202219E+10 | 0.548001E+09 |
October | 0.158561E+10 | 0.905728E+09 | 0.679877E+09 | 0.174638E+10 | 0.843571E+09 |
November | 0.109895E+10 | 0.620392E+09 | 0.478554E+09 | 0.106995E+10 | 0.100580E+10 |
December | 0.105966E+10 | 0.548420E+09 | 0.511236E+09 | 0.848043E+09 | 0.143535E+10 |
Annual Sum or Average | 0.162813E+11 | 0.718023E+10 | 0.910104E+10 | 0.179679E+11 | 0.990763E+10 |
Minimum of Months | 0.105966E+10 | 0.255021E+09 | 0.478554E+09 | 0.848043E+09 | 0.260963E+09 |
Maximum of Months | 0.176599E+10 | 0.992297E+09 | 0.963127E+09 | 0.202219E+10 | 0.143535E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126715E+10 | 0.739673E+09 | 0.527477E+09 | 0.107920E+10 | 0.143409E+10 |
February | 0.130676E+10 | 0.630107E+09 | 0.676651E+09 | 0.110599E+10 | 0.126897E+10 |
March | 0.176588E+10 | 0.992235E+09 | 0.773641E+09 | 0.181849E+10 | 0.105508E+10 |
April | 0.141525E+10 | 0.565538E+09 | 0.849711E+09 | 0.152082E+10 | 0.796263E+09 |
May | 0.127975E+10 | 0.371693E+09 | 0.908057E+09 | 0.149050E+10 | 0.552399E+09 |
June | 0.120339E+10 | 0.255005E+09 | 0.948387E+09 | 0.154042E+10 | 0.357026E+09 |
July | 0.126942E+10 | 0.308002E+09 | 0.961415E+09 | 0.177465E+10 | 0.260947E+09 |
August | 0.142513E+10 | 0.462063E+09 | 0.963067E+09 | 0.195050E+10 | 0.349744E+09 |
September | 0.160355E+10 | 0.781048E+09 | 0.822502E+09 | 0.202206E+10 | 0.547966E+09 |
October | 0.158550E+10 | 0.905671E+09 | 0.679834E+09 | 0.174626E+10 | 0.843518E+09 |
November | 0.109888E+10 | 0.620353E+09 | 0.478524E+09 | 0.106988E+10 | 0.100574E+10 |
December | 0.105959E+10 | 0.548385E+09 | 0.511204E+09 | 0.847990E+09 | 0.143526E+10 |
Annual Sum or Average | 0.162802E+11 | 0.717977E+10 | 0.910047E+10 | 0.179668E+11 | 0.990700E+10 |
Minimum of Months | 0.105959E+10 | 0.255005E+09 | 0.478524E+09 | 0.847990E+09 | 0.260947E+09 |
Maximum of Months | 0.176588E+10 | 0.992235E+09 | 0.963067E+09 | 0.202206E+10 | 0.143526E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.890207E+09 | 0.208985E+09 | 0.681222E+09 | 0.266913E+09 | 0.310297E+10 |
February | 0.130316E+10 | 0.334919E+09 | 0.968237E+09 | 0.607863E+09 | 0.263990E+10 |
March | 0.226130E+10 | 0.968232E+09 | 0.129307E+10 | 0.191146E+10 | 0.208953E+10 |
April | 0.267935E+10 | 0.109863E+10 | 0.158071E+10 | 0.262963E+10 | 0.150414E+10 |
May | 0.326607E+10 | 0.147605E+10 | 0.179003E+10 | 0.367608E+10 | 0.108494E+10 |
June | 0.381350E+10 | 0.179370E+10 | 0.201980E+10 | 0.475633E+10 | 0.729167E+09 |
July | 0.352306E+10 | 0.154462E+10 | 0.197844E+10 | 0.467049E+10 | 0.532596E+09 |
August | 0.318640E+10 | 0.135488E+10 | 0.183152E+10 | 0.414554E+10 | 0.688588E+09 |
September | 0.242159E+10 | 0.104578E+10 | 0.137582E+10 | 0.282573E+10 | 0.104556E+10 |
October | 0.162212E+10 | 0.571400E+09 | 0.105072E+10 | 0.144517E+10 | 0.164831E+10 |
November | 0.930264E+09 | 0.268068E+09 | 0.662197E+09 | 0.575340E+09 | 0.199874E+10 |
December | 0.833338E+09 | 0.181574E+09 | 0.651764E+09 | 0.253453E+09 | 0.304253E+10 |
Annual Sum or Average | 0.267304E+11 | 0.108468E+11 | 0.158835E+11 | 0.277640E+11 | 0.201070E+11 |
Minimum of Months | 0.833338E+09 | 0.181574E+09 | 0.651764E+09 | 0.253453E+09 | 0.532596E+09 |
Maximum of Months | 0.381350E+10 | 0.179370E+10 | 0.201980E+10 | 0.475633E+10 | 0.310297E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 35197892.37 | 8263041.20 | 26934851.18 | 10553422.09 | 0.122689E+09 |
February | 51525504.54 | 13242363.98 | 38283140.56 | 24034194.62 | 0.104379E+09 |
March | 89409537.00 | 38282891.65 | 51126645.34 | 75576925.54 | 82618287.95 |
April | 0.105939E+09 | 43438881.87 | 62499741.07 | 0.103973E+09 | 59472393.42 |
May | 0.129137E+09 | 58361382.25 | 70775868.59 | 0.145349E+09 | 42897583.96 |
June | 0.150782E+09 | 70921213.46 | 79860709.65 | 0.188060E+09 | 28830613.73 |
July | 0.139298E+09 | 61072813.34 | 78225453.51 | 0.184666E+09 | 21058338.44 |
August | 0.125987E+09 | 53570612.27 | 72416404.57 | 0.163911E+09 | 27226148.07 |
September | 95747289.72 | 41348869.00 | 54398420.71 | 0.111726E+09 | 41340546.86 |
October | 64136911.94 | 22592577.70 | 41544334.24 | 57140622.42 | 65172695.94 |
November | 36781718.95 | 10599125.91 | 26182593.04 | 22748336.74 | 79028288.39 |
December | 32949350.07 | 7179259.31 | 25770090.76 | 10021241.24 | 0.120299E+09 |
Annual Sum or Average | 0.105689E+10 | 0.428873E+09 | 0.628018E+09 | 0.109776E+10 | 0.795012E+09 |
Minimum of Months | 32949350.07 | 7179259.31 | 25770090.76 | 10021241.24 | 21058338.44 |
Maximum of Months | 0.150782E+09 | 70921213.46 | 79860709.65 | 0.188060E+09 | 0.122689E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.884097E+09 | 0.00 | 0.884097E+09 | 10700665.16 | 0.518265E+10 |
February | 0.121667E+10 | 0.00 | 0.121667E+10 | 84172289.82 | 0.437964E+10 |
March | 0.163357E+10 | 0.00 | 0.163357E+10 | 0.559411E+09 | 0.351958E+10 |
April | 0.201436E+10 | 8038086.86 | 0.200632E+10 | 0.113084E+10 | 0.243918E+10 |
May | 0.241860E+10 | 0.102563E+09 | 0.231604E+10 | 0.193073E+10 | 0.164011E+10 |
June | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.306040E+10 | 0.103709E+10 |
July | 0.269855E+10 | 0.174197E+09 | 0.252435E+10 | 0.338494E+10 | 0.750458E+09 |
August | 0.233500E+10 | 35521897.19 | 0.229947E+10 | 0.276547E+10 | 0.996289E+09 |
September | 0.171966E+10 | 357270.95 | 0.171930E+10 | 0.156881E+10 | 0.157634E+10 |
October | 0.132837E+10 | 0.00 | 0.132837E+10 | 0.667736E+09 | 0.253825E+10 |
November | 0.863837E+09 | 0.00 | 0.863837E+09 | 0.196414E+09 | 0.313730E+10 |
December | 0.827489E+09 | 0.00 | 0.827489E+09 | 14361210.58 | 0.496072E+10 |
Annual Sum or Average | 0.207554E+11 | 0.560324E+09 | 0.201951E+11 | 0.153740E+11 | 0.321576E+11 |
Minimum of Months | 0.827489E+09 | 0.00 | 0.827489E+09 | 10700665.16 | 0.750458E+09 |
Maximum of Months | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.338494E+10 | 0.518265E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107859E+10 | 0.347796E+09 | 0.730792E+09 | 0.431432E+09 | 0.314459E+10 |
February | 0.142946E+10 | 0.428945E+09 | 0.100052E+10 | 0.699549E+09 | 0.268834E+10 |
March | 0.227101E+10 | 0.951083E+09 | 0.131993E+10 | 0.181528E+10 | 0.216313E+10 |
April | 0.290887E+10 | 0.128529E+10 | 0.162358E+10 | 0.277447E+10 | 0.154170E+10 |
May | 0.336761E+10 | 0.148967E+10 | 0.187794E+10 | 0.368163E+10 | 0.110463E+10 |
June | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.444045E+10 | 0.700065E+09 |
July | 0.361159E+10 | 0.159013E+10 | 0.202146E+10 | 0.472988E+10 | 0.502959E+09 |
August | 0.326166E+10 | 0.136907E+10 | 0.189260E+10 | 0.417972E+10 | 0.658170E+09 |
September | 0.262671E+10 | 0.116511E+10 | 0.146161E+10 | 0.304462E+10 | 0.100157E+10 |
October | 0.184186E+10 | 0.761840E+09 | 0.108002E+10 | 0.167099E+10 | 0.159486E+10 |
November | 0.101103E+10 | 0.324327E+09 | 0.686706E+09 | 0.642856E+09 | 0.199357E+10 |
December | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.225410E+09 | 0.310620E+10 |
Annual Sum or Average | 0.278892E+11 | 0.114956E+11 | 0.163936E+11 | 0.283363E+11 | 0.201998E+11 |
Minimum of Months | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.225410E+09 | 0.502959E+09 |
Maximum of Months | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.472988E+10 | 0.314459E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.380157E+10 | 0.221909E+10 | 0.158248E+10 | 0.312457E+10 | 0.445366E+10 |
February | 0.392040E+10 | 0.189038E+10 | 0.203002E+10 | 0.318263E+10 | 0.395115E+10 |
March | 0.529780E+10 | 0.297679E+10 | 0.232100E+10 | 0.526393E+10 | 0.328373E+10 |
April | 0.424589E+10 | 0.169666E+10 | 0.254922E+10 | 0.439465E+10 | 0.253223E+10 |
May | 0.383938E+10 | 0.111511E+10 | 0.272427E+10 | 0.430098E+10 | 0.180803E+10 |
June | 0.361030E+10 | 0.765037E+09 | 0.284527E+10 | 0.451104E+10 | 0.114233E+10 |
July | 0.380838E+10 | 0.924034E+09 | 0.288435E+10 | 0.525738E+10 | 0.816925E+09 |
August | 0.427553E+10 | 0.138623E+10 | 0.288930E+10 | 0.580327E+10 | 0.105731E+10 |
September | 0.481081E+10 | 0.234322E+10 | 0.246759E+10 | 0.602429E+10 | 0.161328E+10 |
October | 0.475667E+10 | 0.271710E+10 | 0.203957E+10 | 0.517327E+10 | 0.246923E+10 |
November | 0.329673E+10 | 0.186112E+10 | 0.143562E+10 | 0.315985E+10 | 0.298201E+10 |
December | 0.317887E+10 | 0.164521E+10 | 0.153366E+10 | 0.247086E+10 | 0.439450E+10 |
Annual Sum or Average | 0.488423E+11 | 0.215400E+11 | 0.273024E+11 | 0.526667E+11 | 0.305044E+11 |
Minimum of Months | 0.317887E+10 | 0.765037E+09 | 0.143562E+10 | 0.247086E+10 | 0.816925E+09 |
Maximum of Months | 0.529780E+10 | 0.297679E+10 | 0.288930E+10 | 0.602429E+10 | 0.445366E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.925412E+09 | 0.217250E+09 | 0.708162E+09 | 0.268382E+09 | 0.326098E+10 |
February | 0.135469E+10 | 0.348165E+09 | 0.100653E+10 | 0.609580E+09 | 0.277707E+10 |
March | 0.235073E+10 | 0.100652E+10 | 0.134420E+10 | 0.192603E+10 | 0.222853E+10 |
April | 0.278531E+10 | 0.114208E+10 | 0.164322E+10 | 0.266369E+10 | 0.162004E+10 |
May | 0.339524E+10 | 0.153442E+10 | 0.186081E+10 | 0.375026E+10 | 0.117823E+10 |
June | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.490142E+10 | 0.768806E+09 |
July | 0.366239E+10 | 0.160571E+10 | 0.205667E+10 | 0.482278E+10 | 0.560169E+09 |
August | 0.331241E+10 | 0.140847E+10 | 0.190395E+10 | 0.429091E+10 | 0.708190E+09 |
September | 0.251736E+10 | 0.108713E+10 | 0.143022E+10 | 0.292912E+10 | 0.106008E+10 |
October | 0.168627E+10 | 0.593999E+09 | 0.109227E+10 | 0.150540E+10 | 0.165564E+10 |
November | 0.967054E+09 | 0.278670E+09 | 0.688384E+09 | 0.597287E+09 | 0.203504E+10 |
December | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.258012E+09 | 0.315379E+10 |
Annual Sum or Average | 0.277875E+11 | 0.112758E+11 | 0.165116E+11 | 0.285229E+11 | 0.210066E+11 |
Minimum of Months | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.258012E+09 | 0.560169E+09 |
Maximum of Months | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.490142E+10 | 0.326098E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6.71 | 1866.40 | 330.08 | 0.00 | 330.08 | 0.00 | 0.00 |
February | 41.41 | 1741.62 | 502.92 | 0.00 | 502.92 | 0.00 | 0.00 |
March | 218.29 | 1245.88 | 609.91 | 0.00 | 609.91 | 0.00 | 0.00 |
April | 453.02 | 883.28 | 777.14 | 3.10 | 774.04 | 0.00 | 0.00 |
May | 733.69 | 580.84 | 903.00 | 38.29 | 864.71 | 0.00 | 0.00 |
June | 1181.96 | 386.97 | 1086.12 | 92.46 | 993.67 | 0.00 | 0.00 |
July | 1259.80 | 273.43 | 1007.52 | 65.04 | 942.49 | 0.00 | 0.00 |
August | 1032.90 | 358.71 | 871.79 | 13.26 | 858.53 | 0.00 | 0.00 |
September | 615.22 | 570.41 | 663.45 | 0.14 | 663.31 | 0.00 | 0.00 |
October | 269.82 | 869.93 | 495.96 | 0.00 | 495.96 | 0.00 | 0.00 |
November | 86.88 | 1122.09 | 333.27 | 0.00 | 333.27 | 0.00 | 0.00 |
December | 7.51 | 1769.33 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Annual Sum or Average | 494.97 | 968.63 | 658.15 | 17.77 | 640.38 | 0.00 | 0.00 |
Minimum of Months | 6.71 | 273.43 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Maximum of Months | 1259.80 | 1866.40 | 1086.12 | 92.46 | 993.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 165.90 | 1131.22 | 402.70 | 129.85 | 272.85 | 0.00 | 0.00 |
February | 297.65 | 1069.46 | 590.88 | 177.31 | 413.57 | 0.00 | 0.00 |
March | 687.76 | 765.95 | 847.90 | 355.09 | 492.81 | 0.00 | 0.00 |
April | 1081.82 | 561.87 | 1122.25 | 495.87 | 626.38 | 0.00 | 0.00 |
May | 1379.79 | 393.45 | 1257.32 | 556.18 | 701.14 | 0.00 | 0.00 |
June | 1711.94 | 261.90 | 1404.21 | 620.59 | 783.62 | 0.00 | 0.00 |
July | 1762.02 | 183.54 | 1348.41 | 593.69 | 754.73 | 0.00 | 0.00 |
August | 1559.15 | 237.69 | 1217.77 | 511.15 | 706.62 | 0.00 | 0.00 |
September | 1180.11 | 365.36 | 1013.39 | 449.50 | 563.89 | 0.00 | 0.00 |
October | 639.21 | 550.31 | 687.67 | 284.44 | 403.23 | 0.00 | 0.00 |
November | 258.31 | 715.16 | 390.06 | 125.13 | 264.93 | 0.00 | 0.00 |
December | 88.26 | 1108.13 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Annual Sum or Average | 904.23 | 609.73 | 884.36 | 364.52 | 519.84 | 0.00 | 0.00 |
Minimum of Months | 88.26 | 183.54 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Maximum of Months | 1762.02 | 1131.22 | 1404.21 | 620.59 | 783.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1178.49 | 1597.09 | 1419.34 | 828.51 | 590.83 | 0.00 | 0.00 |
February | 1330.06 | 1567.76 | 1620.54 | 781.41 | 839.13 | 0.00 | 0.00 |
March | 1980.61 | 1159.43 | 1977.97 | 1111.41 | 866.56 | 0.00 | 0.00 |
April | 1710.53 | 920.00 | 1638.07 | 654.58 | 983.50 | 0.00 | 0.00 |
May | 1613.09 | 639.73 | 1433.46 | 416.34 | 1017.13 | 0.00 | 0.00 |
June | 1738.76 | 423.66 | 1392.86 | 295.15 | 1097.71 | 0.00 | 0.00 |
July | 1957.30 | 295.89 | 1421.89 | 344.99 | 1076.89 | 0.00 | 0.00 |
August | 2164.42 | 379.82 | 1596.30 | 517.56 | 1078.74 | 0.00 | 0.00 |
September | 2330.37 | 586.77 | 1856.02 | 904.02 | 952.00 | 0.00 | 0.00 |
October | 1953.55 | 850.41 | 1775.94 | 1014.45 | 761.49 | 0.00 | 0.00 |
November | 1238.40 | 1067.27 | 1271.89 | 718.02 | 553.87 | 0.00 | 0.00 |
December | 935.66 | 1564.89 | 1186.85 | 614.25 | 572.60 | 0.00 | 0.00 |
Annual Sum or Average | 1679.62 | 917.63 | 1548.78 | 683.03 | 865.75 | 0.00 | 0.00 |
Minimum of Months | 935.66 | 295.89 | 1186.85 | 295.15 | 553.87 | 0.00 | 0.00 |
Maximum of Months | 2330.37 | 1597.09 | 1977.97 | 1111.41 | 1097.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 103.35 | 1174.50 | 345.51 | 81.11 | 264.40 | 0.00 | 0.00 |
February | 257.69 | 1104.93 | 559.98 | 143.92 | 416.06 | 0.00 | 0.00 |
March | 726.48 | 787.96 | 877.66 | 375.79 | 501.87 | 0.00 | 0.00 |
April | 1037.40 | 588.30 | 1074.58 | 440.62 | 633.96 | 0.00 | 0.00 |
May | 1406.37 | 416.94 | 1267.64 | 572.89 | 694.75 | 0.00 | 0.00 |
June | 1889.76 | 285.49 | 1529.44 | 719.38 | 810.06 | 0.00 | 0.00 |
July | 1797.01 | 202.96 | 1367.38 | 599.50 | 767.87 | 0.00 | 0.00 |
August | 1601.56 | 254.54 | 1236.71 | 525.86 | 710.85 | 0.00 | 0.00 |
September | 1136.76 | 384.21 | 971.20 | 419.42 | 551.78 | 0.00 | 0.00 |
October | 575.69 | 569.46 | 629.58 | 221.77 | 407.81 | 0.00 | 0.00 |
November | 239.36 | 729.57 | 373.09 | 107.51 | 265.58 | 0.00 | 0.00 |
December | 99.81 | 1125.80 | 323.44 | 70.47 | 252.96 | 0.00 | 0.00 |
Annual Sum or Average | 909.40 | 633.05 | 881.13 | 357.55 | 523.58 | 0.00 | 0.00 |
Minimum of Months | 99.81 | 202.96 | 323.44 | 70.47 | 252.96 | 0.00 | 0.00 |
Maximum of Months | 1889.76 | 1174.50 | 1529.44 | 719.38 | 810.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.20 | 1912.01 | 330.08 | 0.00 | 330.08 | 0.00 | 0.00 |
February | 38.72 | 1784.94 | 502.92 | 0.00 | 502.92 | 0.00 | 0.00 |
March | 230.39 | 1264.45 | 609.90 | 0.00 | 609.90 | 0.00 | 0.00 |
April | 477.92 | 882.79 | 777.14 | 3.10 | 774.04 | 0.00 | 0.00 |
May | 777.27 | 559.72 | 903.00 | 38.29 | 864.71 | 0.00 | 0.00 |
June | 1214.28 | 375.80 | 1086.12 | 92.46 | 993.66 | 0.00 | 0.00 |
July | 1287.93 | 263.08 | 1007.52 | 65.04 | 942.48 | 0.00 | 0.00 |
August | 1046.94 | 359.93 | 871.78 | 13.26 | 858.52 | 0.00 | 0.00 |
September | 613.92 | 604.03 | 663.45 | 0.14 | 663.31 | 0.00 | 0.00 |
October | 249.47 | 965.77 | 495.95 | 0.00 | 495.95 | 0.00 | 0.00 |
November | 75.66 | 1228.35 | 333.27 | 0.00 | 333.27 | 0.00 | 0.00 |
December | 5.43 | 1857.92 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Annual Sum or Average | 504.62 | 1001.03 | 658.15 | 17.77 | 640.38 | 0.00 | 0.00 |
Minimum of Months | 4.20 | 263.08 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Maximum of Months | 1287.93 | 1912.01 | 1086.12 | 92.46 | 993.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 164.84 | 1164.55 | 402.70 | 129.85 | 272.84 | 0.00 | 0.00 |
February | 297.41 | 1100.38 | 590.88 | 177.31 | 413.57 | 0.00 | 0.00 |
March | 698.21 | 787.05 | 847.89 | 355.09 | 492.80 | 0.00 | 0.00 |
April | 1094.62 | 577.95 | 1122.24 | 495.86 | 626.38 | 0.00 | 0.00 |
May | 1399.76 | 395.32 | 1257.31 | 556.17 | 701.14 | 0.00 | 0.00 |
June | 1729.22 | 264.90 | 1404.20 | 620.59 | 783.62 | 0.00 | 0.00 |
July | 1777.64 | 185.14 | 1348.40 | 593.68 | 754.72 | 0.00 | 0.00 |
August | 1567.95 | 247.54 | 1217.76 | 511.15 | 706.61 | 0.00 | 0.00 |
September | 1178.06 | 397.82 | 1013.38 | 449.50 | 563.89 | 0.00 | 0.00 |
October | 620.93 | 621.52 | 687.67 | 284.44 | 403.23 | 0.00 | 0.00 |
November | 247.42 | 788.09 | 390.06 | 125.12 | 264.93 | 0.00 | 0.00 |
December | 85.40 | 1164.22 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Annual Sum or Average | 908.40 | 638.90 | 884.35 | 364.52 | 519.83 | 0.00 | 0.00 |
Minimum of Months | 85.40 | 185.14 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Maximum of Months | 1777.64 | 1164.55 | 1404.20 | 620.59 | 783.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1208.83 | 1606.35 | 1419.36 | 828.52 | 590.84 | 0.00 | 0.00 |
February | 1371.57 | 1573.69 | 1620.55 | 781.42 | 839.14 | 0.00 | 0.00 |
March | 2036.92 | 1181.82 | 1977.99 | 1111.42 | 866.57 | 0.00 | 0.00 |
April | 1760.28 | 921.64 | 1638.09 | 654.58 | 983.50 | 0.00 | 0.00 |
May | 1669.54 | 618.75 | 1433.47 | 416.34 | 1017.13 | 0.00 | 0.00 |
June | 1782.97 | 413.24 | 1392.87 | 295.16 | 1097.72 | 0.00 | 0.00 |
July | 1987.82 | 292.29 | 1421.90 | 345.00 | 1076.90 | 0.00 | 0.00 |
August | 2184.80 | 391.75 | 1596.31 | 517.57 | 1078.75 | 0.00 | 0.00 |
September | 2340.45 | 634.25 | 1856.04 | 904.03 | 952.01 | 0.00 | 0.00 |
October | 1956.02 | 944.84 | 1775.95 | 1014.46 | 761.49 | 0.00 | 0.00 |
November | 1238.34 | 1164.10 | 1271.90 | 718.03 | 553.87 | 0.00 | 0.00 |
December | 949.85 | 1607.66 | 1186.87 | 614.26 | 572.61 | 0.00 | 0.00 |
Annual Sum or Average | 1709.24 | 942.49 | 1548.79 | 683.04 | 865.76 | 0.00 | 0.00 |
Minimum of Months | 949.85 | 292.29 | 1186.87 | 295.16 | 553.87 | 0.00 | 0.00 |
Maximum of Months | 2340.45 | 1607.66 | 1977.99 | 1111.42 | 1097.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 103.59 | 1204.32 | 345.51 | 81.11 | 264.40 | 0.00 | 0.00 |
February | 261.20 | 1134.37 | 559.97 | 143.92 | 416.06 | 0.00 | 0.00 |
March | 741.87 | 810.99 | 877.65 | 375.79 | 501.86 | 0.00 | 0.00 |
April | 1054.63 | 603.25 | 1074.57 | 440.61 | 633.95 | 0.00 | 0.00 |
May | 1426.76 | 421.09 | 1267.63 | 572.88 | 694.74 | 0.00 | 0.00 |
June | 1907.56 | 292.44 | 1529.43 | 719.38 | 810.05 | 0.00 | 0.00 |
July | 1812.71 | 206.71 | 1367.37 | 599.50 | 767.87 | 0.00 | 0.00 |
August | 1608.97 | 267.25 | 1236.70 | 525.86 | 710.85 | 0.00 | 0.00 |
September | 1133.28 | 419.33 | 971.20 | 419.42 | 551.78 | 0.00 | 0.00 |
October | 560.90 | 639.74 | 629.58 | 221.77 | 407.80 | 0.00 | 0.00 |
November | 230.74 | 801.61 | 373.09 | 107.51 | 265.58 | 0.00 | 0.00 |
December | 98.37 | 1180.86 | 323.43 | 70.47 | 252.96 | 0.00 | 0.00 |
Annual Sum or Average | 915.20 | 662.80 | 881.13 | 357.55 | 523.58 | 0.00 | 0.00 |
Minimum of Months | 98.37 | 206.71 | 323.43 | 70.47 | 252.96 | 0.00 | 0.00 |
Maximum of Months | 1907.56 | 1204.32 | 1529.43 | 719.38 | 810.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.00 | 1934.98 | 330.08 | 0.00 | 330.08 | 0.00 | 0.00 |
February | 34.79 | 1810.37 | 502.92 | 0.00 | 502.92 | 0.00 | 0.00 |
March | 208.86 | 1314.06 | 609.91 | 0.00 | 609.91 | 0.00 | 0.00 |
April | 436.28 | 941.04 | 777.14 | 3.10 | 774.04 | 0.00 | 0.00 |
May | 720.85 | 612.35 | 903.00 | 38.29 | 864.71 | 0.00 | 0.00 |
June | 1180.71 | 400.11 | 1086.12 | 92.46 | 993.67 | 0.00 | 0.00 |
July | 1263.79 | 280.19 | 1007.52 | 65.04 | 942.49 | 0.00 | 0.00 |
August | 1032.51 | 371.97 | 871.79 | 13.26 | 858.53 | 0.00 | 0.00 |
September | 605.25 | 608.16 | 663.45 | 0.14 | 663.31 | 0.00 | 0.00 |
October | 249.30 | 947.67 | 495.96 | 0.00 | 495.96 | 0.00 | 0.00 |
November | 75.78 | 1210.38 | 333.27 | 0.00 | 333.27 | 0.00 | 0.00 |
December | 5.36 | 1852.12 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Annual Sum or Average | 487.51 | 1019.71 | 658.15 | 17.77 | 640.38 | 0.00 | 0.00 |
Minimum of Months | 4.00 | 280.19 | 308.95 | 0.00 | 308.95 | 0.00 | 0.00 |
Maximum of Months | 1263.79 | 1934.98 | 1086.12 | 92.46 | 993.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 161.08 | 1174.06 | 402.70 | 129.85 | 272.85 | 0.00 | 0.00 |
February | 289.17 | 1111.25 | 590.88 | 177.31 | 413.57 | 0.00 | 0.00 |
March | 677.75 | 807.62 | 847.90 | 355.09 | 492.81 | 0.00 | 0.00 |
April | 1070.40 | 594.79 | 1122.25 | 495.87 | 626.38 | 0.00 | 0.00 |
May | 1374.56 | 412.42 | 1257.32 | 556.18 | 701.14 | 0.00 | 0.00 |
June | 1713.14 | 270.09 | 1404.21 | 620.59 | 783.62 | 0.00 | 0.00 |
July | 1765.94 | 187.78 | 1348.41 | 593.69 | 754.73 | 0.00 | 0.00 |
August | 1560.53 | 245.73 | 1217.77 | 511.15 | 706.62 | 0.00 | 0.00 |
September | 1174.62 | 386.41 | 1013.39 | 449.50 | 563.89 | 0.00 | 0.00 |
October | 623.87 | 595.45 | 687.67 | 284.44 | 403.23 | 0.00 | 0.00 |
November | 248.02 | 769.12 | 390.06 | 125.13 | 264.93 | 0.00 | 0.00 |
December | 84.16 | 1159.72 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Annual Sum or Average | 898.54 | 640.53 | 884.36 | 364.52 | 519.84 | 0.00 | 0.00 |
Minimum of Months | 84.16 | 187.78 | 314.02 | 64.88 | 249.13 | 0.00 | 0.00 |
Maximum of Months | 1765.94 | 1174.06 | 1404.21 | 620.59 | 783.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1166.58 | 1662.80 | 1419.34 | 828.51 | 590.83 | 0.00 | 0.00 |
February | 1315.57 | 1633.25 | 1620.54 | 781.41 | 839.13 | 0.00 | 0.00 |
March | 1965.32 | 1226.00 | 1977.97 | 1111.41 | 866.56 | 0.00 | 0.00 |
April | 1695.47 | 976.94 | 1638.07 | 654.58 | 983.50 | 0.00 | 0.00 |
May | 1605.80 | 675.04 | 1433.46 | 416.34 | 1017.13 | 0.00 | 0.00 |
June | 1740.37 | 440.71 | 1392.86 | 295.15 | 1097.71 | 0.00 | 0.00 |
July | 1962.88 | 305.00 | 1421.89 | 344.99 | 1076.89 | 0.00 | 0.00 |
August | 2166.69 | 394.75 | 1596.30 | 517.56 | 1078.74 | 0.00 | 0.00 |
September | 2324.19 | 622.41 | 1856.02 | 904.02 | 952.00 | 0.00 | 0.00 |
October | 1931.48 | 921.90 | 1775.94 | 1014.45 | 761.49 | 0.00 | 0.00 |
November | 1219.08 | 1150.47 | 1271.89 | 718.02 | 553.87 | 0.00 | 0.00 |
December | 922.51 | 1640.72 | 1186.85 | 614.25 | 572.60 | 0.00 | 0.00 |
Annual Sum or Average | 1670.05 | 967.29 | 1548.78 | 683.03 | 865.75 | 0.00 | 0.00 |
Minimum of Months | 922.51 | 305.00 | 1186.85 | 295.15 | 553.87 | 0.00 | 0.00 |
Maximum of Months | 2324.19 | 1662.80 | 1977.97 | 1111.41 | 1097.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 100.20 | 1217.51 | 345.51 | 81.11 | 264.40 | 0.00 | 0.00 |
February | 251.98 | 1147.93 | 559.98 | 143.92 | 416.06 | 0.00 | 0.00 |
March | 719.10 | 832.04 | 877.66 | 375.79 | 501.87 | 0.00 | 0.00 |
April | 1027.66 | 625.02 | 1074.58 | 440.62 | 633.96 | 0.00 | 0.00 |
May | 1400.19 | 439.90 | 1267.64 | 572.89 | 694.75 | 0.00 | 0.00 |
June | 1890.98 | 296.61 | 1529.44 | 719.38 | 810.06 | 0.00 | 0.00 |
July | 1800.62 | 209.14 | 1367.38 | 599.50 | 767.87 | 0.00 | 0.00 |
August | 1602.04 | 264.41 | 1236.71 | 525.86 | 710.85 | 0.00 | 0.00 |
September | 1130.06 | 408.98 | 971.20 | 419.42 | 551.78 | 0.00 | 0.00 |
October | 562.05 | 618.15 | 629.58 | 221.77 | 407.81 | 0.00 | 0.00 |
November | 230.43 | 785.12 | 373.09 | 107.51 | 265.58 | 0.00 | 0.00 |
December | 96.33 | 1177.49 | 323.44 | 70.47 | 252.96 | 0.00 | 0.00 |
Annual Sum or Average | 904.45 | 666.11 | 881.13 | 357.55 | 523.58 | 0.00 | 0.00 |
Minimum of Months | 96.33 | 209.14 | 323.44 | 70.47 | 252.96 | 0.00 | 0.00 |
Maximum of Months | 1890.98 | 1217.51 | 1529.44 | 719.38 | 810.06 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 17978040.71 | 0.499897E+10 | 0.884097E+09 | 0.00 | 0.884097E+09 | 0.00 | 0.00 |
February | 0.100178E+09 | 0.421333E+10 | 0.121667E+10 | 0.00 | 0.121667E+10 | 0.00 | 0.00 |
March | 0.584677E+09 | 0.333698E+10 | 0.163357E+10 | 0.00 | 0.163357E+10 | 0.00 | 0.00 |
April | 0.117423E+10 | 0.228945E+10 | 0.201436E+10 | 8038086.86 | 0.200632E+10 | 0.00 | 0.00 |
May | 0.196513E+10 | 0.155573E+10 | 0.241860E+10 | 0.102563E+09 | 0.231604E+10 | 0.00 | 0.00 |
June | 0.306363E+10 | 0.100302E+10 | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.00 | 0.00 |
July | 0.337426E+10 | 0.732354E+09 | 0.269855E+10 | 0.174197E+09 | 0.252435E+10 | 0.00 | 0.00 |
August | 0.276651E+10 | 0.960776E+09 | 0.233500E+10 | 35521897.19 | 0.229947E+10 | 0.00 | 0.00 |
September | 0.159465E+10 | 0.147851E+10 | 0.171966E+10 | 357270.95 | 0.171930E+10 | 0.00 | 0.00 |
October | 0.722675E+09 | 0.233001E+10 | 0.132837E+10 | 0.00 | 0.132837E+10 | 0.00 | 0.00 |
November | 0.225196E+09 | 0.290846E+10 | 0.863837E+09 | 0.00 | 0.863837E+09 | 0.00 | 0.00 |
December | 20126936.61 | 0.473898E+10 | 0.827489E+09 | 0.00 | 0.827489E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.156092E+11 | 0.305466E+11 | 0.207554E+11 | 0.560324E+09 | 0.201951E+11 | 0.00 | 0.00 |
Minimum of Months | 17978040.71 | 0.732354E+09 | 0.827489E+09 | 0.00 | 0.827489E+09 | 0.00 | 0.00 |
Maximum of Months | 0.337426E+10 | 0.499897E+10 | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.444334E+09 | 0.302986E+10 | 0.107859E+10 | 0.347796E+09 | 0.730792E+09 | 0.00 | 0.00 |
February | 0.720066E+09 | 0.258725E+10 | 0.142946E+10 | 0.428945E+09 | 0.100052E+10 | 0.00 | 0.00 |
March | 0.184209E+10 | 0.205151E+10 | 0.227101E+10 | 0.951083E+09 | 0.131993E+10 | 0.00 | 0.00 |
April | 0.280409E+10 | 0.145636E+10 | 0.290887E+10 | 0.128529E+10 | 0.162358E+10 | 0.00 | 0.00 |
May | 0.369562E+10 | 0.105383E+10 | 0.336761E+10 | 0.148967E+10 | 0.187794E+10 | 0.00 | 0.00 |
June | 0.443735E+10 | 0.678850E+09 | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.00 | 0.00 |
July | 0.471939E+10 | 0.491590E+09 | 0.361159E+10 | 0.159013E+10 | 0.202146E+10 | 0.00 | 0.00 |
August | 0.417603E+10 | 0.636634E+09 | 0.326166E+10 | 0.136907E+10 | 0.189260E+10 | 0.00 | 0.00 |
September | 0.305884E+10 | 0.947024E+09 | 0.262671E+10 | 0.116511E+10 | 0.146161E+10 | 0.00 | 0.00 |
October | 0.171206E+10 | 0.147394E+10 | 0.184186E+10 | 0.761840E+09 | 0.108002E+10 | 0.00 | 0.00 |
November | 0.669528E+09 | 0.185369E+10 | 0.101103E+10 | 0.324327E+09 | 0.686706E+09 | 0.00 | 0.00 |
December | 0.236405E+09 | 0.296803E+10 | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.285158E+11 | 0.192285E+11 | 0.278892E+11 | 0.114956E+11 | 0.163936E+11 | 0.00 | 0.00 |
Minimum of Months | 0.236405E+09 | 0.491590E+09 | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.00 | 0.00 |
Maximum of Months | 0.471939E+10 | 0.302986E+10 | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.315646E+10 | 0.427766E+10 | 0.380157E+10 | 0.221909E+10 | 0.158248E+10 | 0.00 | 0.00 |
February | 0.321768E+10 | 0.379272E+10 | 0.392040E+10 | 0.189038E+10 | 0.203002E+10 | 0.00 | 0.00 |
March | 0.530486E+10 | 0.310542E+10 | 0.529780E+10 | 0.297679E+10 | 0.232100E+10 | 0.00 | 0.00 |
April | 0.443371E+10 | 0.238465E+10 | 0.424589E+10 | 0.169666E+10 | 0.254922E+10 | 0.00 | 0.00 |
May | 0.432051E+10 | 0.171345E+10 | 0.383938E+10 | 0.111511E+10 | 0.272427E+10 | 0.00 | 0.00 |
June | 0.450688E+10 | 0.109812E+10 | 0.361030E+10 | 0.765037E+09 | 0.284527E+10 | 0.00 | 0.00 |
July | 0.524244E+10 | 0.792511E+09 | 0.380838E+10 | 0.924034E+09 | 0.288435E+10 | 0.00 | 0.00 |
August | 0.579718E+10 | 0.101731E+10 | 0.427553E+10 | 0.138623E+10 | 0.288930E+10 | 0.00 | 0.00 |
September | 0.604031E+10 | 0.152090E+10 | 0.481081E+10 | 0.234322E+10 | 0.246759E+10 | 0.00 | 0.00 |
October | 0.523238E+10 | 0.227774E+10 | 0.475667E+10 | 0.271710E+10 | 0.203957E+10 | 0.00 | 0.00 |
November | 0.320993E+10 | 0.276636E+10 | 0.329673E+10 | 0.186112E+10 | 0.143562E+10 | 0.00 | 0.00 |
December | 0.250607E+10 | 0.419140E+10 | 0.317887E+10 | 0.164521E+10 | 0.153366E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.529684E+11 | 0.289382E+11 | 0.488423E+11 | 0.215400E+11 | 0.273024E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250607E+10 | 0.792511E+09 | 0.317887E+10 | 0.765037E+09 | 0.143562E+10 | 0.00 | 0.00 |
Maximum of Months | 0.604031E+10 | 0.427766E+10 | 0.529780E+10 | 0.297679E+10 | 0.288930E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.276804E+09 | 0.314577E+10 | 0.925412E+09 | 0.217250E+09 | 0.708162E+09 | 0.00 | 0.00 |
February | 0.623408E+09 | 0.267304E+10 | 0.135469E+10 | 0.348165E+09 | 0.100653E+10 | 0.00 | 0.00 |
March | 0.194581E+10 | 0.211047E+10 | 0.235073E+10 | 0.100652E+10 | 0.134420E+10 | 0.00 | 0.00 |
April | 0.268895E+10 | 0.152488E+10 | 0.278531E+10 | 0.114208E+10 | 0.164322E+10 | 0.00 | 0.00 |
May | 0.376683E+10 | 0.111672E+10 | 0.339524E+10 | 0.153442E+10 | 0.186081E+10 | 0.00 | 0.00 |
June | 0.489826E+10 | 0.739984E+09 | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.00 | 0.00 |
July | 0.481310E+10 | 0.543615E+09 | 0.366239E+10 | 0.160571E+10 | 0.205667E+10 | 0.00 | 0.00 |
August | 0.428963E+10 | 0.681764E+09 | 0.331241E+10 | 0.140847E+10 | 0.190395E+10 | 0.00 | 0.00 |
September | 0.294647E+10 | 0.995878E+09 | 0.251736E+10 | 0.108713E+10 | 0.143022E+10 | 0.00 | 0.00 |
October | 0.154194E+10 | 0.152525E+10 | 0.168627E+10 | 0.593999E+09 | 0.109227E+10 | 0.00 | 0.00 |
November | 0.620411E+09 | 0.189105E+10 | 0.967054E+09 | 0.278670E+09 | 0.688384E+09 | 0.00 | 0.00 |
December | 0.267343E+09 | 0.301534E+10 | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.286790E+11 | 0.199638E+11 | 0.277875E+11 | 0.112758E+11 | 0.165116E+11 | 0.00 | 0.00 |
Minimum of Months | 0.267343E+09 | 0.543615E+09 | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.00 | 0.00 |
Maximum of Months | 0.489826E+10 | 0.314577E+10 | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 11240633.22 | 0.512114E+10 | 0.884093E+09 | 0.00 | 0.884093E+09 | 0.00 | 0.00 |
February | 93677332.68 | 0.431814E+10 | 0.121667E+10 | 0.00 | 0.121667E+10 | 0.00 | 0.00 |
March | 0.617071E+09 | 0.338670E+10 | 0.163356E+10 | 0.00 | 0.163356E+10 | 0.00 | 0.00 |
April | 0.123876E+10 | 0.228820E+10 | 0.201435E+10 | 8038045.20 | 0.200631E+10 | 0.00 | 0.00 |
May | 0.208184E+10 | 0.149916E+10 | 0.241859E+10 | 0.102562E+09 | 0.231603E+10 | 0.00 | 0.00 |
June | 0.314740E+10 | 0.974068E+09 | 0.281522E+10 | 0.239646E+09 | 0.257557E+10 | 0.00 | 0.00 |
July | 0.344960E+10 | 0.704635E+09 | 0.269854E+10 | 0.174197E+09 | 0.252434E+10 | 0.00 | 0.00 |
August | 0.280412E+10 | 0.964047E+09 | 0.233498E+10 | 35521713.12 | 0.229946E+10 | 0.00 | 0.00 |
September | 0.159128E+10 | 0.156563E+10 | 0.171965E+10 | 357269.10 | 0.171929E+10 | 0.00 | 0.00 |
October | 0.668186E+09 | 0.258671E+10 | 0.132836E+10 | 0.00 | 0.132836E+10 | 0.00 | 0.00 |
November | 0.196104E+09 | 0.318387E+10 | 0.863833E+09 | 0.00 | 0.863833E+09 | 0.00 | 0.00 |
December | 14552468.68 | 0.497625E+10 | 0.827484E+09 | 0.00 | 0.827484E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.159138E+11 | 0.315686E+11 | 0.207553E+11 | 0.560321E+09 | 0.201950E+11 | 0.00 | 0.00 |
Minimum of Months | 11240633.22 | 0.704635E+09 | 0.827484E+09 | 0.00 | 0.827484E+09 | 0.00 | 0.00 |
Maximum of Months | 0.344960E+10 | 0.512114E+10 | 0.281522E+10 | 0.239646E+09 | 0.257557E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.441510E+09 | 0.311914E+10 | 0.107858E+10 | 0.347793E+09 | 0.730787E+09 | 0.00 | 0.00 |
February | 0.719490E+09 | 0.266204E+10 | 0.142945E+10 | 0.428940E+09 | 0.100051E+10 | 0.00 | 0.00 |
March | 0.187010E+10 | 0.210804E+10 | 0.227099E+10 | 0.951074E+09 | 0.131992E+10 | 0.00 | 0.00 |
April | 0.283726E+10 | 0.149804E+10 | 0.290884E+10 | 0.128528E+10 | 0.162357E+10 | 0.00 | 0.00 |
May | 0.374910E+10 | 0.105883E+10 | 0.336758E+10 | 0.148965E+10 | 0.187793E+10 | 0.00 | 0.00 |
June | 0.448215E+10 | 0.686618E+09 | 0.363970E+10 | 0.160856E+10 | 0.203114E+10 | 0.00 | 0.00 |
July | 0.476124E+10 | 0.495878E+09 | 0.361157E+10 | 0.159011E+10 | 0.202145E+10 | 0.00 | 0.00 |
August | 0.419961E+10 | 0.663024E+09 | 0.326164E+10 | 0.136905E+10 | 0.189259E+10 | 0.00 | 0.00 |
September | 0.305353E+10 | 0.103116E+10 | 0.262669E+10 | 0.116509E+10 | 0.146160E+10 | 0.00 | 0.00 |
October | 0.166311E+10 | 0.166469E+10 | 0.184184E+10 | 0.761832E+09 | 0.108001E+10 | 0.00 | 0.00 |
November | 0.641317E+09 | 0.204273E+10 | 0.101103E+10 | 0.324324E+09 | 0.686702E+09 | 0.00 | 0.00 |
December | 0.228738E+09 | 0.311825E+10 | 0.841058E+09 | 0.173780E+09 | 0.667278E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.286472E+11 | 0.201484E+11 | 0.278890E+11 | 0.114955E+11 | 0.163935E+11 | 0.00 | 0.00 |
Minimum of Months | 0.228738E+09 | 0.495878E+09 | 0.841058E+09 | 0.173780E+09 | 0.667278E+09 | 0.00 | 0.00 |
Maximum of Months | 0.476124E+10 | 0.311914E+10 | 0.363970E+10 | 0.160856E+10 | 0.203114E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.323772E+10 | 0.430246E+10 | 0.380161E+10 | 0.221911E+10 | 0.158250E+10 | 0.00 | 0.00 |
February | 0.331811E+10 | 0.380707E+10 | 0.392044E+10 | 0.189040E+10 | 0.203004E+10 | 0.00 | 0.00 |
March | 0.545570E+10 | 0.316538E+10 | 0.529785E+10 | 0.297683E+10 | 0.232102E+10 | 0.00 | 0.00 |
April | 0.456264E+10 | 0.238889E+10 | 0.424592E+10 | 0.169668E+10 | 0.254924E+10 | 0.00 | 0.00 |
May | 0.447169E+10 | 0.165727E+10 | 0.383941E+10 | 0.111513E+10 | 0.272429E+10 | 0.00 | 0.00 |
June | 0.462146E+10 | 0.107112E+10 | 0.361033E+10 | 0.765046E+09 | 0.284528E+10 | 0.00 | 0.00 |
July | 0.532417E+10 | 0.782873E+09 | 0.380841E+10 | 0.924045E+09 | 0.288437E+10 | 0.00 | 0.00 |
August | 0.585176E+10 | 0.104928E+10 | 0.427557E+10 | 0.138625E+10 | 0.288932E+10 | 0.00 | 0.00 |
September | 0.606643E+10 | 0.164397E+10 | 0.481085E+10 | 0.234324E+10 | 0.246761E+10 | 0.00 | 0.00 |
October | 0.523902E+10 | 0.253066E+10 | 0.475672E+10 | 0.271713E+10 | 0.203959E+10 | 0.00 | 0.00 |
November | 0.320978E+10 | 0.301734E+10 | 0.329677E+10 | 0.186114E+10 | 0.143563E+10 | 0.00 | 0.00 |
December | 0.254408E+10 | 0.430595E+10 | 0.317890E+10 | 0.164523E+10 | 0.153368E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.539026E+11 | 0.297223E+11 | 0.488428E+11 | 0.215402E+11 | 0.273026E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254408E+10 | 0.782873E+09 | 0.317890E+10 | 0.765046E+09 | 0.143563E+10 | 0.00 | 0.00 |
Maximum of Months | 0.606643E+10 | 0.430595E+10 | 0.529785E+10 | 0.297683E+10 | 0.288932E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.277466E+09 | 0.322566E+10 | 0.925405E+09 | 0.217248E+09 | 0.708157E+09 | 0.00 | 0.00 |
February | 0.631897E+09 | 0.274428E+10 | 0.135468E+10 | 0.348162E+09 | 0.100652E+10 | 0.00 | 0.00 |
March | 0.198703E+10 | 0.217215E+10 | 0.235071E+10 | 0.100651E+10 | 0.134420E+10 | 0.00 | 0.00 |
April | 0.273360E+10 | 0.156361E+10 | 0.278528E+10 | 0.114207E+10 | 0.164321E+10 | 0.00 | 0.00 |
May | 0.382143E+10 | 0.112784E+10 | 0.339521E+10 | 0.153441E+10 | 0.186080E+10 | 0.00 | 0.00 |
June | 0.494439E+10 | 0.757998E+09 | 0.396428E+10 | 0.186463E+10 | 0.209966E+10 | 0.00 | 0.00 |
July | 0.485516E+10 | 0.553654E+09 | 0.366236E+10 | 0.160570E+10 | 0.205666E+10 | 0.00 | 0.00 |
August | 0.430945E+10 | 0.715814E+09 | 0.331239E+10 | 0.140845E+10 | 0.190393E+10 | 0.00 | 0.00 |
September | 0.293745E+10 | 0.108690E+10 | 0.251734E+10 | 0.108712E+10 | 0.143021E+10 | 0.00 | 0.00 |
October | 0.150231E+10 | 0.171348E+10 | 0.168625E+10 | 0.593993E+09 | 0.109226E+10 | 0.00 | 0.00 |
November | 0.598089E+09 | 0.207777E+10 | 0.967046E+09 | 0.278667E+09 | 0.688379E+09 | 0.00 | 0.00 |
December | 0.263474E+09 | 0.316283E+10 | 0.866287E+09 | 0.188754E+09 | 0.677534E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.288618E+11 | 0.209020E+11 | 0.277872E+11 | 0.112757E+11 | 0.165115E+11 | 0.00 | 0.00 |
Minimum of Months | 0.263474E+09 | 0.553654E+09 | 0.866287E+09 | 0.188754E+09 | 0.677534E+09 | 0.00 | 0.00 |
Maximum of Months | 0.494439E+10 | 0.322566E+10 | 0.396428E+10 | 0.186463E+10 | 0.209966E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 10700665.16 | 0.518265E+10 | 0.884097E+09 | 0.00 | 0.884097E+09 | 0.00 | 0.00 |
February | 84172289.82 | 0.437964E+10 | 0.121667E+10 | 0.00 | 0.121667E+10 | 0.00 | 0.00 |
March | 0.559411E+09 | 0.351958E+10 | 0.163357E+10 | 0.00 | 0.163357E+10 | 0.00 | 0.00 |
April | 0.113084E+10 | 0.243918E+10 | 0.201436E+10 | 8038086.86 | 0.200632E+10 | 0.00 | 0.00 |
May | 0.193073E+10 | 0.164011E+10 | 0.241860E+10 | 0.102563E+09 | 0.231604E+10 | 0.00 | 0.00 |
June | 0.306040E+10 | 0.103709E+10 | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.00 | 0.00 |
July | 0.338494E+10 | 0.750458E+09 | 0.269855E+10 | 0.174197E+09 | 0.252435E+10 | 0.00 | 0.00 |
August | 0.276547E+10 | 0.996289E+09 | 0.233500E+10 | 35521897.19 | 0.229947E+10 | 0.00 | 0.00 |
September | 0.156881E+10 | 0.157634E+10 | 0.171966E+10 | 357270.95 | 0.171930E+10 | 0.00 | 0.00 |
October | 0.667736E+09 | 0.253825E+10 | 0.132837E+10 | 0.00 | 0.132837E+10 | 0.00 | 0.00 |
November | 0.196414E+09 | 0.313730E+10 | 0.863837E+09 | 0.00 | 0.863837E+09 | 0.00 | 0.00 |
December | 14361210.58 | 0.496072E+10 | 0.827489E+09 | 0.00 | 0.827489E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.153740E+11 | 0.321576E+11 | 0.207554E+11 | 0.560324E+09 | 0.201951E+11 | 0.00 | 0.00 |
Minimum of Months | 10700665.16 | 0.750458E+09 | 0.827489E+09 | 0.00 | 0.827489E+09 | 0.00 | 0.00 |
Maximum of Months | 0.338494E+10 | 0.518265E+10 | 0.281523E+10 | 0.239647E+09 | 0.257558E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.431432E+09 | 0.314459E+10 | 0.107859E+10 | 0.347796E+09 | 0.730792E+09 | 0.00 | 0.00 |
February | 0.699549E+09 | 0.268834E+10 | 0.142946E+10 | 0.428945E+09 | 0.100052E+10 | 0.00 | 0.00 |
March | 0.181528E+10 | 0.216313E+10 | 0.227101E+10 | 0.951083E+09 | 0.131993E+10 | 0.00 | 0.00 |
April | 0.277447E+10 | 0.154170E+10 | 0.290887E+10 | 0.128529E+10 | 0.162358E+10 | 0.00 | 0.00 |
May | 0.368163E+10 | 0.110463E+10 | 0.336761E+10 | 0.148967E+10 | 0.187794E+10 | 0.00 | 0.00 |
June | 0.444045E+10 | 0.700065E+09 | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.00 | 0.00 |
July | 0.472988E+10 | 0.502959E+09 | 0.361159E+10 | 0.159013E+10 | 0.202146E+10 | 0.00 | 0.00 |
August | 0.417972E+10 | 0.658170E+09 | 0.326166E+10 | 0.136907E+10 | 0.189260E+10 | 0.00 | 0.00 |
September | 0.304462E+10 | 0.100157E+10 | 0.262671E+10 | 0.116511E+10 | 0.146161E+10 | 0.00 | 0.00 |
October | 0.167099E+10 | 0.159486E+10 | 0.184186E+10 | 0.761840E+09 | 0.108002E+10 | 0.00 | 0.00 |
November | 0.642856E+09 | 0.199357E+10 | 0.101103E+10 | 0.324327E+09 | 0.686706E+09 | 0.00 | 0.00 |
December | 0.225410E+09 | 0.310620E+10 | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.283363E+11 | 0.201998E+11 | 0.278892E+11 | 0.114956E+11 | 0.163936E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225410E+09 | 0.502959E+09 | 0.841065E+09 | 0.173782E+09 | 0.667283E+09 | 0.00 | 0.00 |
Maximum of Months | 0.472988E+10 | 0.314459E+10 | 0.363972E+10 | 0.160857E+10 | 0.203115E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.312457E+10 | 0.445366E+10 | 0.380157E+10 | 0.221909E+10 | 0.158248E+10 | 0.00 | 0.00 |
February | 0.318263E+10 | 0.395115E+10 | 0.392040E+10 | 0.189038E+10 | 0.203002E+10 | 0.00 | 0.00 |
March | 0.526393E+10 | 0.328373E+10 | 0.529780E+10 | 0.297679E+10 | 0.232100E+10 | 0.00 | 0.00 |
April | 0.439465E+10 | 0.253223E+10 | 0.424589E+10 | 0.169666E+10 | 0.254922E+10 | 0.00 | 0.00 |
May | 0.430098E+10 | 0.180803E+10 | 0.383938E+10 | 0.111511E+10 | 0.272427E+10 | 0.00 | 0.00 |
June | 0.451104E+10 | 0.114233E+10 | 0.361030E+10 | 0.765037E+09 | 0.284527E+10 | 0.00 | 0.00 |
July | 0.525738E+10 | 0.816925E+09 | 0.380838E+10 | 0.924034E+09 | 0.288435E+10 | 0.00 | 0.00 |
August | 0.580327E+10 | 0.105731E+10 | 0.427553E+10 | 0.138623E+10 | 0.288930E+10 | 0.00 | 0.00 |
September | 0.602429E+10 | 0.161328E+10 | 0.481081E+10 | 0.234322E+10 | 0.246759E+10 | 0.00 | 0.00 |
October | 0.517327E+10 | 0.246923E+10 | 0.475667E+10 | 0.271710E+10 | 0.203957E+10 | 0.00 | 0.00 |
November | 0.315985E+10 | 0.298201E+10 | 0.329673E+10 | 0.186112E+10 | 0.143562E+10 | 0.00 | 0.00 |
December | 0.247086E+10 | 0.439450E+10 | 0.317887E+10 | 0.164521E+10 | 0.153366E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.526667E+11 | 0.305044E+11 | 0.488423E+11 | 0.215400E+11 | 0.273024E+11 | 0.00 | 0.00 |
Minimum of Months | 0.247086E+10 | 0.816925E+09 | 0.317887E+10 | 0.765037E+09 | 0.143562E+10 | 0.00 | 0.00 |
Maximum of Months | 0.602429E+10 | 0.445366E+10 | 0.529780E+10 | 0.297679E+10 | 0.288930E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.268382E+09 | 0.326098E+10 | 0.925412E+09 | 0.217250E+09 | 0.708162E+09 | 0.00 | 0.00 |
February | 0.609580E+09 | 0.277707E+10 | 0.135469E+10 | 0.348165E+09 | 0.100653E+10 | 0.00 | 0.00 |
March | 0.192603E+10 | 0.222853E+10 | 0.235073E+10 | 0.100652E+10 | 0.134420E+10 | 0.00 | 0.00 |
April | 0.266369E+10 | 0.162004E+10 | 0.278531E+10 | 0.114208E+10 | 0.164322E+10 | 0.00 | 0.00 |
May | 0.375026E+10 | 0.117823E+10 | 0.339524E+10 | 0.153442E+10 | 0.186081E+10 | 0.00 | 0.00 |
June | 0.490142E+10 | 0.768806E+09 | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.00 | 0.00 |
July | 0.482278E+10 | 0.560169E+09 | 0.366239E+10 | 0.160571E+10 | 0.205667E+10 | 0.00 | 0.00 |
August | 0.429091E+10 | 0.708190E+09 | 0.331241E+10 | 0.140847E+10 | 0.190395E+10 | 0.00 | 0.00 |
September | 0.292912E+10 | 0.106008E+10 | 0.251736E+10 | 0.108713E+10 | 0.143022E+10 | 0.00 | 0.00 |
October | 0.150540E+10 | 0.165564E+10 | 0.168627E+10 | 0.593999E+09 | 0.109227E+10 | 0.00 | 0.00 |
November | 0.597287E+09 | 0.203504E+10 | 0.967054E+09 | 0.278670E+09 | 0.688384E+09 | 0.00 | 0.00 |
December | 0.258012E+09 | 0.315379E+10 | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.285229E+11 | 0.210066E+11 | 0.277875E+11 | 0.112758E+11 | 0.165116E+11 | 0.00 | 0.00 |
Minimum of Months | 0.258012E+09 | 0.560169E+09 | 0.866294E+09 | 0.188755E+09 | 0.677539E+09 | 0.00 | 0.00 |
Maximum of Months | 0.490142E+10 | 0.326098E+10 | 0.396431E+10 | 0.186464E+10 | 0.209967E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.563535E+10 | -0.488351E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -751839525.9 | 58.99 | 0.00 | 0.00 |
February | 0.517584E+10 | -0.450243E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -673403137.5 | 58.98 | 0.00 | 0.00 |
March | 0.597783E+10 | -0.525692E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -720906504.5 | 58.99 | 0.00 | 0.00 |
April | 0.522875E+10 | -0.454425E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -684496434.4 | 58.98 | 0.00 | 0.00 |
May | 0.529344E+10 | -0.459888E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694561945.4 | 58.98 | 0.00 | 0.00 |
June | 0.495480E+10 | -0.428515E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669656103.2 | 58.98 | 0.00 | 0.00 |
July | 0.452917E+10 | -0.384044E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688730618.8 | 58.98 | 0.00 | 0.00 |
August | 0.485786E+10 | -0.416743E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690436119.1 | 58.98 | 0.00 | 0.00 |
September | 0.448902E+10 | -0.382039E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668629891.1 | 58.98 | 0.00 | 0.00 |
October | 0.484282E+10 | -0.414283E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -699985979.5 | 58.98 | 0.00 | 0.00 |
November | 0.502832E+10 | -0.433785E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -690466996.2 | 58.98 | 0.00 | 0.00 |
December | 0.529068E+10 | -0.455277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -737901849.0 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.613039E+11 | -0.529328E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.837102E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.448902E+10 | -0.525692E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -751839525.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.597783E+10 | -0.382039E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -668629891.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:20 | 3900.36 | 32.07 | 234.00 | 243.83 | 3167.71 | 33.40 | 241.50 | 217.17 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:00 | 4915.76 | 32.29 | 243.33 | 251.50 | 1616.01 | 26.55 | 232.33 | 232.50 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 7091.69 | 29.11 | 246.33 | 321.50 | 1288.21 | 21.15 | 159.83 | 285.00 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1783.40 | 17.51 | 0.00 | 338.17 | 997.47 | 20.26 | 153.00 | 297.50 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-06:49 | 1608.00 | 17.56 | 0.00 | 374.17 | 945.63 | 20.38 | 123.83 | 322.17 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:19 | 1450.25 | 17.35 | 0.00 | 383.67 | 833.33 | 20.13 | 149.67 | 339.50 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:40 | 1523.42 | 17.39 | 0.00 | 390.00 | 862.87 | 20.16 | 168.33 | 340.00 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:30 | 1810.58 | 17.90 | 0.00 | 368.67 | 1003.12 | 20.66 | 204.17 | 325.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2597.07 | 19.46 | 17.00 | 318.00 | 1321.95 | 21.32 | 178.83 | 281.67 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:30 | 5715.51 | 31.67 | 272.33 | 294.33 | 1363.49 | 21.76 | 164.67 | 271.17 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:49 | 3678.51 | 31.90 | 237.67 | 236.50 | 1476.29 | 27.36 | 198.83 | 209.67 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:20 | 3258.68 | 29.83 | 197.00 | 231.83 | 2588.04 | 32.32 | 216.50 | 199.00 |
Annual Sum or Average | 3928.50 | 0.50 | 3096.88 | 23.40 | 1447.67 | 3752.17 | 1346.09 | 23.01 | 2191.50 | 3320.83 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1450.25 | 17.35 | 0.00 | 231.83 | 833.33 | 20.13 | 123.83 | 199.00 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 7091.69 | 32.29 | 272.33 | 390.00 | 3167.71 | 33.40 | 241.50 | 340.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:20 | 1317.75 | 19.66 | 68.83 | 227.17 | 656.45 | 20.82 | 70.67 | 171.33 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-09:00 | 1792.06 | 19.62 | 68.33 | 240.83 | 946.13 | 22.19 | 81.83 | 206.17 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 2471.45 | 20.49 | 101.83 | 311.17 | 1050.46 | 20.87 | 53.33 | 268.17 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 2690.23 | 20.04 | 103.67 | 342.83 | 1504.82 | 21.72 | 77.83 | 300.67 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 3543.52 | 20.25 | 86.67 | 381.67 | 1508.85 | 21.70 | 56.33 | 332.50 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3275.78 | 20.73 | 131.00 | 393.83 | 1424.56 | 21.44 | 75.83 | 359.83 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:10 | 3032.51 | 19.73 | 113.83 | 399.67 | 1346.36 | 21.45 | 75.50 | 358.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:49 | 2832.84 | 20.13 | 106.50 | 370.67 | 1252.23 | 21.69 | 67.33 | 334.33 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2777.88 | 20.00 | 67.17 | 315.17 | 1587.39 | 23.07 | 67.17 | 275.83 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:10 | 1807.87 | 19.41 | 77.67 | 280.33 | 961.16 | 21.06 | 60.00 | 237.33 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-07:40 | 1282.70 | 18.46 | 69.33 | 220.67 | 730.95 | 21.26 | 77.83 | 159.17 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-08:09 | 1133.08 | 18.96 | 59.00 | 217.17 | 566.95 | 20.30 | 55.33 | 156.67 |
Annual Sum or Average | 3928.50 | 0.51 | 2463.36 | 19.87 | 1053.83 | 3701.17 | 1177.49 | 21.49 | 819.00 | 3160.17 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1133.08 | 18.46 | 59.00 | 217.17 | 566.95 | 20.30 | 53.33 | 156.67 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 3543.52 | 20.73 | 131.00 | 399.67 | 1587.39 | 23.07 | 81.83 | 359.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.53 | 0.48 | 01-JAN-11:09 | 559.79 | 14.37 | 0.00 | 207.00 | 314.44 | 17.20 | 0.00 | 89.50 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-12:50 | 736.53 | 15.54 | 0.00 | 233.50 | 410.74 | 18.24 | 0.00 | 169.50 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:30 | 775.52 | 16.10 | 0.00 | 303.83 | 455.97 | 18.91 | 0.00 | 243.50 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 895.05 | 16.75 | 0.00 | 342.00 | 528.82 | 19.43 | 1.17 | 297.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:10 | 1063.36 | 17.90 | 3.33 | 393.67 | 652.41 | 21.74 | 79.50 | 350.50 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1205.42 | 20.68 | 74.33 | 408.67 | 708.20 | 22.03 | 152.67 | 381.67 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:30 | 1146.77 | 20.32 | 71.00 | 414.00 | 672.27 | 21.76 | 134.67 | 380.83 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 1012.83 | 17.50 | 0.00 | 380.83 | 604.51 | 20.22 | 44.33 | 341.67 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:49 | 841.13 | 16.96 | 0.00 | 312.33 | 524.61 | 19.75 | 1.00 | 252.83 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-08:09 | 681.50 | 15.26 | 0.00 | 269.83 | 393.70 | 18.06 | 0.00 | 189.33 |
November | 258.33 | 0.55 | 0.48 | 01-NOV-08:39 | 543.34 | 13.88 | 0.00 | 204.00 | 303.49 | 16.60 | 0.00 | 88.00 |
December | 230.67 | 0.53 | 0.48 | 01-DEC-12:09 | 564.93 | 14.31 | 0.00 | 192.17 | 309.94 | 17.06 | 0.00 | 82.50 |
Annual Sum or Average | 3928.50 | 0.51 | 877.35 | 17.03 | 148.67 | 3661.83 | 515.89 | 19.57 | 413.33 | 2867.50 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 543.34 | 13.88 | 0.00 | 192.17 | 303.49 | 16.60 | 0.00 | 82.50 | |
Maximum of Months | 439.00 | 0.55 | 0.48 | 1205.42 | 20.68 | 74.33 | 414.00 | 708.20 | 22.03 | 152.67 | 381.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-10:30 | 1199.93 | 18.60 | 63.50 | 224.00 | 674.41 | 21.50 | 74.17 | 167.17 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:39 | 1666.63 | 19.28 | 67.17 | 241.83 | 900.99 | 22.05 | 75.67 | 204.83 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:30 | 2431.55 | 20.43 | 99.67 | 313.83 | 1372.62 | 22.08 | 78.17 | 272.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:30 | 2834.15 | 19.77 | 103.67 | 337.33 | 1207.71 | 20.19 | 49.33 | 299.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:00 | 3073.23 | 16.93 | 43.00 | 381.17 | 1681.74 | 18.17 | 0.00 | 335.83 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:49 | 3221.99 | 16.70 | 52.33 | 391.83 | 1383.22 | 18.14 | 0.00 | 356.67 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:40 | 2873.09 | 16.76 | 54.50 | 396.83 | 1303.72 | 18.32 | 3.67 | 359.67 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:49 | 2712.23 | 18.78 | 84.33 | 373.50 | 1467.67 | 20.60 | 53.50 | 330.83 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:00 | 2974.26 | 21.29 | 83.50 | 313.83 | 1261.28 | 21.50 | 42.33 | 278.33 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-08:20 | 1695.80 | 18.98 | 73.67 | 278.17 | 916.92 | 21.73 | 65.17 | 238.00 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:39 | 1241.14 | 18.30 | 71.33 | 218.67 | 677.69 | 20.83 | 67.17 | 163.00 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-11:50 | 1170.18 | 18.41 | 50.33 | 210.83 | 629.58 | 20.97 | 63.50 | 154.50 |
Annual Sum or Average | 3928.50 | 0.51 | 2386.47 | 18.57 | 847.00 | 3681.83 | 1175.61 | 20.31 | 572.67 | 3161.50 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1170.18 | 16.70 | 43.00 | 210.83 | 629.58 | 18.14 | 0.00 | 154.50 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 3221.99 | 21.29 | 103.67 | 396.83 | 1681.74 | 22.08 | 78.17 | 359.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:20 | 3771.68 | 31.70 | 231.50 | 242.17 | 3080.39 | 32.94 | 231.50 | 214.33 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:00 | 4775.20 | 32.00 | 240.17 | 250.50 | 1524.03 | 24.54 | 105.83 | 230.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 6959.58 | 28.10 | 226.33 | 319.67 | 1196.63 | 18.37 | 9.00 | 281.67 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1687.57 | 13.79 | 0.00 | 336.83 | 933.65 | 17.70 | 0.17 | 293.67 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-06:49 | 1525.85 | 14.06 | 0.00 | 370.67 | 892.34 | 18.07 | 0.00 | 316.00 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:30 | 1381.16 | 13.88 | 0.00 | 380.67 | 791.08 | 17.82 | 0.00 | 334.33 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:40 | 1449.51 | 13.84 | 0.00 | 386.67 | 817.03 | 17.77 | 0.00 | 336.17 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:30 | 1717.77 | 14.29 | 0.00 | 365.17 | 943.68 | 18.21 | 0.00 | 321.83 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2462.47 | 16.05 | 17.00 | 315.83 | 1229.02 | 18.87 | 3.50 | 278.17 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:30 | 5587.85 | 31.16 | 267.67 | 293.00 | 1272.86 | 18.86 | 20.67 | 268.83 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:49 | 3563.43 | 31.65 | 234.67 | 234.33 | 1400.94 | 25.66 | 132.83 | 207.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:20 | 3130.70 | 28.93 | 190.67 | 229.17 | 2509.10 | 31.87 | 210.67 | 195.00 |
Annual Sum or Average | 3928.50 | 0.51 | 2991.09 | 21.12 | 1408.00 | 3724.67 | 1276.25 | 20.84 | 714.17 | 3277.50 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1381.16 | 13.79 | 0.00 | 229.17 | 791.08 | 17.70 | 0.00 | 195.00 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 6959.58 | 32.00 | 267.67 | 386.67 | 3080.39 | 32.94 | 231.50 | 336.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:30 | 1273.63 | 19.21 | 68.67 | 224.83 | 625.20 | 20.56 | 65.17 | 167.00 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-09:00 | 1733.60 | 19.19 | 67.67 | 239.67 | 904.88 | 21.96 | 73.00 | 203.00 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 2403.66 | 20.09 | 101.67 | 308.83 | 1000.17 | 20.65 | 49.33 | 263.67 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 2612.67 | 19.64 | 103.17 | 339.33 | 1446.26 | 21.53 | 77.83 | 297.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 3441.03 | 19.75 | 85.67 | 378.17 | 1441.59 | 21.53 | 56.00 | 328.50 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-05:00 | 3108.57 | 19.01 | 107.17 | 390.83 | 1364.10 | 21.27 | 75.83 | 357.00 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-05:10 | 2948.19 | 19.33 | 113.67 | 395.17 | 1282.03 | 21.21 | 74.67 | 354.50 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-05:00 | 2749.94 | 19.73 | 106.33 | 368.50 | 1162.72 | 20.63 | 54.33 | 328.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2689.90 | 19.57 | 67.17 | 312.00 | 1520.96 | 22.88 | 63.67 | 270.00 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:19 | 1748.10 | 18.98 | 77.67 | 278.00 | 917.23 | 20.83 | 55.50 | 231.67 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-07:40 | 1240.62 | 18.03 | 69.00 | 218.17 | 701.73 | 21.03 | 70.67 | 153.50 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-08:09 | 1086.87 | 18.19 | 54.67 | 213.83 | 540.20 | 20.04 | 52.17 | 150.83 |
Annual Sum or Average | 3928.50 | 0.51 | 2381.68 | 19.29 | 1022.50 | 3667.33 | 1122.17 | 21.19 | 768.17 | 3105.83 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1086.87 | 18.03 | 54.67 | 213.83 | 540.20 | 20.04 | 49.33 | 150.83 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 3441.03 | 20.09 | 113.67 | 395.17 | 1520.96 | 22.88 | 77.83 | 357.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.54 | 0.48 | 01-JAN-11:30 | 535.35 | 10.44 | 0.00 | 201.83 | 301.27 | 14.50 | 0.00 | 74.33 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-12:50 | 705.38 | 11.88 | 0.00 | 231.50 | 393.99 | 15.76 | 0.00 | 162.00 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:39 | 743.06 | 12.66 | 0.00 | 300.50 | 438.85 | 16.64 | 0.00 | 234.50 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 862.66 | 13.40 | 0.00 | 342.67 | 509.17 | 17.30 | 0.00 | 292.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:10 | 1019.39 | 14.64 | 3.33 | 390.50 | 629.00 | 19.88 | 24.67 | 344.67 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1155.64 | 17.99 | 73.67 | 406.00 | 680.90 | 20.02 | 37.00 | 379.00 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:40 | 1099.26 | 17.57 | 70.50 | 412.00 | 646.41 | 19.74 | 36.67 | 377.50 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 970.10 | 14.19 | 0.00 | 377.83 | 581.79 | 18.15 | 0.00 | 336.83 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:49 | 804.82 | 13.96 | 0.00 | 308.17 | 505.70 | 17.92 | 0.00 | 246.67 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-08:09 | 652.48 | 11.65 | 0.00 | 264.83 | 378.27 | 15.62 | 0.00 | 178.00 |
November | 258.33 | 0.55 | 0.48 | 01-NOV-08:50 | 519.83 | 10.02 | 0.00 | 198.50 | 290.83 | 13.92 | 0.00 | 74.50 |
December | 230.67 | 0.54 | 0.48 | 01-DEC-12:20 | 540.47 | 10.35 | 0.00 | 187.00 | 296.70 | 14.33 | 0.00 | 72.83 |
Annual Sum or Average | 3928.50 | 0.51 | 840.94 | 13.70 | 147.50 | 3621.33 | 496.13 | 17.35 | 98.33 | 2773.50 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 519.83 | 10.02 | 0.00 | 187.00 | 290.83 | 13.92 | 0.00 | 72.83 | |
Maximum of Months | 439.00 | 0.55 | 0.48 | 1155.64 | 17.99 | 73.67 | 412.00 | 680.90 | 20.02 | 37.00 | 379.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:39 | 1161.21 | 18.24 | 63.17 | 221.83 | 647.98 | 21.39 | 73.50 | 162.00 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-11:09 | 1610.15 | 18.92 | 66.83 | 240.17 | 861.56 | 21.94 | 74.50 | 200.50 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:30 | 2360.73 | 20.08 | 99.50 | 310.17 | 1319.37 | 21.95 | 77.67 | 269.50 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:40 | 2761.97 | 19.40 | 103.50 | 335.33 | 1153.41 | 20.03 | 49.33 | 295.67 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-07:10 | 2978.95 | 16.51 | 43.00 | 379.33 | 1612.26 | 18.01 | 0.00 | 331.00 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:49 | 3127.71 | 16.27 | 52.33 | 389.33 | 1314.73 | 17.96 | 0.00 | 352.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:40 | 2773.66 | 16.33 | 54.50 | 394.50 | 1241.64 | 18.14 | 3.67 | 356.00 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:49 | 2530.55 | 18.39 | 84.33 | 371.00 | 1407.03 | 20.45 | 53.50 | 325.00 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:00 | 2891.94 | 20.93 | 83.50 | 311.33 | 1193.70 | 21.24 | 41.17 | 274.33 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-08:30 | 1639.06 | 18.61 | 73.50 | 276.17 | 855.31 | 20.69 | 54.33 | 231.50 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:50 | 1201.17 | 17.96 | 71.17 | 216.50 | 650.21 | 20.69 | 66.17 | 157.67 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 1130.09 | 18.06 | 50.17 | 208.17 | 586.73 | 20.01 | 52.83 | 149.00 |
Annual Sum or Average | 3928.50 | 0.51 | 2303.47 | 18.19 | 845.50 | 3653.83 | 1120.72 | 20.03 | 546.67 | 3105.00 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1130.09 | 16.27 | 43.00 | 208.17 | 586.73 | 17.96 | 0.00 | 149.00 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 3127.71 | 20.93 | 103.50 | 394.50 | 1612.26 | 21.95 | 77.67 | 356.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:20 | 3771.69 | 31.70 | 231.50 | 242.17 | 3080.32 | 32.94 | 231.50 | 214.33 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:00 | 4775.17 | 32.00 | 240.17 | 250.50 | 1523.93 | 24.54 | 105.83 | 230.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 6959.51 | 28.10 | 226.33 | 319.67 | 1196.55 | 18.37 | 9.00 | 281.67 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1687.50 | 13.79 | 0.00 | 336.83 | 933.58 | 17.70 | 0.17 | 293.67 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-06:49 | 1525.79 | 14.06 | 0.00 | 370.67 | 892.28 | 18.07 | 0.00 | 316.00 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:30 | 1381.11 | 13.89 | 0.00 | 380.67 | 791.03 | 17.82 | 0.00 | 334.33 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:40 | 1449.45 | 13.84 | 0.00 | 386.67 | 816.98 | 17.77 | 0.00 | 336.17 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:30 | 1717.70 | 14.29 | 0.00 | 365.17 | 943.61 | 18.21 | 0.00 | 321.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2462.39 | 16.05 | 17.00 | 315.83 | 1228.93 | 18.87 | 3.50 | 278.17 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:30 | 5587.81 | 31.16 | 267.67 | 293.00 | 1272.78 | 18.86 | 20.67 | 268.83 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:49 | 3563.43 | 31.65 | 234.67 | 234.33 | 1400.86 | 25.66 | 132.83 | 207.17 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:20 | 3130.71 | 28.93 | 190.67 | 229.17 | 2509.02 | 31.87 | 210.67 | 195.00 |
Annual Sum or Average | 3928.50 | 0.51 | 2991.04 | 21.12 | 1408.00 | 3724.67 | 1276.18 | 20.84 | 714.17 | 3277.33 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1381.11 | 13.79 | 0.00 | 229.17 | 791.03 | 17.70 | 0.00 | 195.00 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 6959.51 | 32.00 | 267.67 | 386.67 | 3080.32 | 32.94 | 231.50 | 336.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:30 | 1273.62 | 19.21 | 68.67 | 224.83 | 625.16 | 20.56 | 65.17 | 167.00 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-09:00 | 1733.57 | 19.19 | 67.67 | 239.67 | 904.83 | 21.96 | 73.00 | 203.00 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 2403.65 | 20.09 | 101.67 | 308.83 | 1000.12 | 20.65 | 49.33 | 263.67 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 2612.65 | 19.64 | 103.17 | 339.33 | 1446.20 | 21.53 | 77.83 | 297.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 3441.01 | 19.75 | 85.67 | 378.17 | 1441.53 | 21.53 | 56.00 | 328.50 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-05:00 | 3108.55 | 19.02 | 107.17 | 390.83 | 1364.04 | 21.27 | 75.83 | 357.00 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-05:10 | 2948.16 | 19.33 | 113.67 | 395.17 | 1281.97 | 21.21 | 74.67 | 354.50 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-05:00 | 2749.91 | 19.73 | 106.33 | 368.50 | 1162.66 | 20.63 | 54.33 | 328.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2689.89 | 19.57 | 67.17 | 312.00 | 1520.91 | 22.88 | 63.67 | 270.00 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:19 | 1748.08 | 18.98 | 77.67 | 278.00 | 917.18 | 20.83 | 55.50 | 231.67 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-07:40 | 1240.60 | 18.03 | 69.00 | 218.17 | 701.69 | 21.03 | 70.67 | 153.50 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-08:09 | 1086.85 | 18.19 | 54.67 | 213.83 | 540.16 | 20.04 | 52.17 | 150.83 |
Annual Sum or Average | 3928.50 | 0.51 | 2381.66 | 19.29 | 1022.50 | 3667.33 | 1122.12 | 21.19 | 768.17 | 3105.83 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1086.85 | 18.03 | 54.67 | 213.83 | 540.16 | 20.04 | 49.33 | 150.83 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 3441.01 | 20.09 | 113.67 | 395.17 | 1520.91 | 22.88 | 77.83 | 357.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.54 | 0.48 | 01-JAN-11:30 | 535.33 | 10.44 | 0.00 | 201.83 | 301.25 | 14.50 | 0.00 | 74.33 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-12:50 | 705.36 | 11.88 | 0.00 | 231.50 | 393.96 | 15.76 | 0.00 | 162.00 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:39 | 743.04 | 12.66 | 0.00 | 300.50 | 438.82 | 16.65 | 0.00 | 234.50 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 862.64 | 13.40 | 0.00 | 342.67 | 509.14 | 17.30 | 0.00 | 292.67 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:10 | 1019.38 | 14.64 | 3.33 | 390.50 | 628.97 | 19.88 | 24.67 | 344.67 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1155.62 | 17.99 | 73.67 | 406.00 | 680.86 | 20.02 | 37.00 | 379.00 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:40 | 1099.24 | 17.58 | 70.50 | 412.00 | 646.37 | 19.74 | 36.67 | 377.50 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 970.09 | 14.19 | 0.00 | 377.83 | 581.75 | 18.15 | 0.00 | 336.83 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:49 | 804.82 | 13.96 | 0.00 | 308.17 | 505.68 | 17.92 | 0.00 | 246.67 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-08:09 | 652.47 | 11.65 | 0.00 | 264.83 | 378.24 | 15.62 | 0.00 | 178.00 |
November | 258.33 | 0.55 | 0.48 | 01-NOV-08:50 | 519.81 | 10.02 | 0.00 | 198.50 | 290.80 | 13.92 | 0.00 | 74.50 |
December | 230.67 | 0.54 | 0.48 | 01-DEC-12:20 | 540.46 | 10.35 | 0.00 | 187.00 | 296.67 | 14.33 | 0.00 | 72.83 |
Annual Sum or Average | 3928.50 | 0.51 | 840.92 | 13.70 | 147.50 | 3621.33 | 496.10 | 17.35 | 98.33 | 2773.50 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 519.81 | 10.02 | 0.00 | 187.00 | 290.80 | 13.92 | 0.00 | 72.83 | |
Maximum of Months | 439.00 | 0.55 | 0.48 | 1155.62 | 17.99 | 73.67 | 412.00 | 680.86 | 20.02 | 37.00 | 379.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:39 | 1161.19 | 18.24 | 63.17 | 221.83 | 647.94 | 21.39 | 73.50 | 162.00 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-11:09 | 1610.12 | 18.92 | 67.00 | 240.17 | 861.51 | 21.94 | 74.50 | 200.50 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:30 | 2360.71 | 20.08 | 99.50 | 310.33 | 1319.32 | 21.95 | 77.67 | 269.50 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:40 | 2761.94 | 19.40 | 103.50 | 335.33 | 1153.35 | 20.03 | 49.33 | 295.67 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-07:10 | 2978.94 | 16.51 | 43.00 | 379.33 | 1612.21 | 18.01 | 0.00 | 331.00 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:49 | 3127.69 | 16.28 | 52.33 | 389.33 | 1314.67 | 17.96 | 0.00 | 352.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:40 | 2773.63 | 16.33 | 54.50 | 394.50 | 1241.58 | 18.15 | 3.67 | 356.00 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:49 | 2530.52 | 18.39 | 84.33 | 371.00 | 1406.97 | 20.45 | 53.50 | 325.00 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:00 | 2891.94 | 20.93 | 83.50 | 311.33 | 1193.64 | 21.24 | 41.17 | 274.33 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-08:30 | 1639.04 | 18.61 | 73.50 | 276.17 | 855.26 | 20.69 | 54.33 | 231.50 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:50 | 1201.15 | 17.96 | 71.17 | 216.50 | 650.18 | 20.69 | 66.17 | 157.67 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:00 | 1130.07 | 18.06 | 50.17 | 208.17 | 586.69 | 20.01 | 52.83 | 149.00 |
Annual Sum or Average | 3928.50 | 0.51 | 2303.45 | 18.19 | 845.67 | 3654.00 | 1120.66 | 20.03 | 546.67 | 3105.00 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1130.07 | 16.28 | 43.00 | 208.17 | 586.69 | 17.96 | 0.00 | 149.00 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 3127.69 | 20.93 | 103.50 | 394.50 | 1612.21 | 21.95 | 77.67 | 356.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.770190E+09 | 25036.35 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69643510.61 | 25036.35 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 589713.03 | 9828.55 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21701868.66 | 25036.35 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.862125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.770190E+09 | 25036.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.998381E+10 | 10891.60 | 11-JAN-17:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.866736E+10 | 10860.37 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.556369E+10 | 10922.33 | 14-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.313497E+10 | 10888.37 | 21-APR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136601E+10 | 11031.94 | 30-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.371448E+09 | 11079.51 | 13-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81016479.56 | 9824.07 | 13-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189416E+09 | 11115.15 | 03-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.532092E+09 | 11137.63 | 06-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188737E+10 | 10919.28 | 13-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.405535E+10 | 10881.89 | 10-NOV-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.863880E+10 | 10871.08 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444713E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 81016479.56 | 9824.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.998381E+10 | 11137.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.329752E+10 | 8990.75 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262661E+10 | 8990.07 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101436E+10 | 8976.01 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167632E+09 | 8945.46 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2211515.74 | 2496.60 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 27846423.54 | 8938.66 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.416757E+09 | 8949.27 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249255E+10 | 8984.65 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.329752E+10 | 8990.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.531989E+10 | 7325.05 | 03-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.446178E+10 | 7315.95 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242855E+10 | 7336.34 | 14-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.545637E+09 | 7314.34 | 13-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12040024.60 | 7302.11 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 67061690.95 | 7308.19 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.653062E+09 | 7313.31 | 21-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376248E+10 | 7321.52 | 14-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.531989E+10 | 7336.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.355912E+10 | 9424.60 | 02-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288367E+10 | 9423.85 | 27-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116934E+10 | 9389.26 | 31-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.261324E+09 | 9370.51 | 13-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7104272.99 | 9405.53 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40945400.11 | 9369.84 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.475360E+09 | 9380.99 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.257634E+10 | 9418.22 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.355912E+10 | 9424.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.370448E+10 | 24066.25 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284466E+10 | 24066.25 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.477117E+09 | 24066.25 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31669221.08 | 24066.25 | 17-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7625716.48 | 24066.25 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238311E+09 | 24066.25 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.244173E+10 | 24066.25 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.974560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.370448E+10 | 24066.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342647E+10 | 12386.64 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273222E+10 | 12360.54 | 14-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.791441E+09 | 12333.42 | 21-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181725E+09 | 12347.71 | 17-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2272557.38 | 10158.48 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86465408.53 | 12261.12 | 20-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.627080E+09 | 12342.75 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296326E+10 | 12396.63 | 04-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342647E+10 | 12396.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.326260E+10 | 9450.48 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258818E+10 | 9450.48 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.893740E+09 | 9450.48 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130276E+09 | 9450.48 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 528340.52 | 1329.46 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 778481.34 | 2088.13 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.118183E+09 | 9450.48 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.810397E+09 | 9450.48 | 03-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.291273E+10 | 9450.48 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.326260E+10 | 9450.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.482326E+10 | 8204.14 | 17-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.394529E+10 | 8197.93 | 15-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160636E+10 | 8229.53 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237958E+09 | 8197.09 | 18-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 221869.20 | 3328.04 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146407E+09 | 8199.27 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.915955E+09 | 8209.49 | 20-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.396497E+10 | 8223.29 | 14-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.482326E+10 | 8229.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.340749E+10 | 9541.62 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.274231E+10 | 9541.62 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103262E+10 | 9541.62 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.219149E+09 | 9541.62 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3072350.72 | 7288.29 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1204764.87 | 1326.81 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145252E+09 | 9541.62 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.825368E+09 | 9541.62 | 03-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289914E+10 | 9541.62 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.340749E+10 | 9541.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.879828E+10 | 30772.82 | 18-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.719979E+10 | 30791.13 | 15-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.272058E+10 | 30846.48 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.513954E+09 | 30836.36 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3134233.92 | 17124.77 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.353053E+09 | 30862.12 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199818E+10 | 30910.92 | 09-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.740177E+10 | 30904.09 | 14-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.879828E+10 | 30910.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.565749E+10 | 13749.30 | 23-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.481658E+10 | 13752.52 | 23-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197499E+10 | 13776.43 | 10-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.668603E+09 | 13754.31 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48524764.41 | 13661.94 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44066.36 | 220.33 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12097180.94 | 10843.37 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.487809E+09 | 13737.19 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178016E+10 | 13762.87 | 15-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.530706E+10 | 13768.99 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.565749E+10 | 13776.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.473521E+10 | 11017.53 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.392738E+10 | 11022.75 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169583E+10 | 11040.75 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.407581E+09 | 11010.97 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14137095.44 | 7631.41 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10698588.27 | 7140.71 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.452253E+09 | 11062.69 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163817E+10 | 11053.66 | 14-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.443323E+10 | 11072.37 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173145E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.473521E+10 | 11072.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.738019E+10 | 9477.47 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.625689E+10 | 9474.18 | 02-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.314958E+10 | 9491.28 | 23-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.783501E+09 | 9488.41 | 13-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30425232.18 | 9387.25 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16903883.47 | 9399.12 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.708877E+09 | 9478.30 | 24-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229442E+10 | 9493.36 | 28-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.650992E+10 | 9486.24 | 14-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.738019E+10 | 9493.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.510396E+10 | 12068.06 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.429478E+10 | 12072.11 | 14-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203132E+10 | 12058.33 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.649494E+09 | 12079.33 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51207776.78 | 12068.57 | 01-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 451449.46 | 990.77 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21483112.76 | 6979.58 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.612007E+09 | 12136.14 | 16-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182201E+10 | 12126.20 | 14-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.460401E+10 | 12146.67 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.191907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.510396E+10 | 12146.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163353E+11 | 24651.67 | 04-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150913E+11 | 28734.22 | 07-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.808166E+10 | 24343.71 | 07-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169104E+10 | 13556.46 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32831300.92 | 5451.43 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2195452.90 | 816.49 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.669132E+09 | 11218.08 | 17-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.335340E+10 | 12683.12 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138094E+11 | 29081.58 | 11-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.590662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163353E+11 | 29081.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171285E+11 | 24853.73 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158512E+11 | 28534.35 | 07-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.918137E+10 | 24265.54 | 07-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.250449E+10 | 14694.94 | 17-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66466183.25 | 6538.85 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92052.28 | 277.71 | 06-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15392302.77 | 1775.25 | 06-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133616E+10 | 12561.96 | 17-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.486351E+10 | 14104.05 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149059E+11 | 29274.12 | 11-DEC-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.658531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171285E+11 | 29274.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.181432E+11 | 26562.70 | 04-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166933E+11 | 30996.71 | 07-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.934032E+10 | 26751.36 | 07-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.265353E+10 | 16983.86 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126595E+09 | 8153.47 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4854451.06 | 1816.07 | 14-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38282121.69 | 3303.39 | 06-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160373E+10 | 15106.60 | 17-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.521676E+10 | 15689.07 | 24-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158364E+11 | 28293.90 | 11-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.696570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181432E+11 | 30996.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.177792E+10 | 0.143688E+10 | 26119.74 | 15-MAR-14:00 | 26119.74 | 0.00 |
April | 0.00 | 0.00 | 0.609139E+09 | 0.540531E+09 | 11949.39 | 08-APR-13:30 | 9528.70 | 0.00 |
May | 0.00 | 0.00 | 0.694770E+10 | 0.623800E+10 | 38280.80 | 24-MAY-05:03 | 26461.27 | 0.00 |
June | 0.00 | 0.00 | 0.348096E+11 | 0.261821E+11 | 93420.84 | 27-JUN-07:40 | 40357.53 | 0.00 |
July | 0.00 | 0.00 | 0.621910E+11 | 0.437522E+11 | 115026.51 | 20-JUL-06:03 | 47092.33 | 0.00 |
August | 0.00 | 0.00 | 0.528586E+11 | 0.405549E+11 | 115059.47 | 14-AUG-08:00 | 48684.61 | 0.00 |
September | 0.00 | 0.00 | 0.231162E+11 | 0.172927E+11 | 80474.23 | 16-SEP-05:03 | 36152.56 | 0.00 |
October | 0.00 | 0.00 | 0.243859E+10 | 0.205086E+10 | 29443.72 | 11-OCT-15:10 | 29443.72 | 0.00 |
November | 0.00 | 0.00 | 0.410095E+09 | 0.289668E+09 | 10030.06 | 16-NOV-18:00 | 7464.36 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185159E+12 | 0.138338E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.621910E+11 | 0.437522E+11 | 115059.47 | 48684.61 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.169693E+10 | 0.138854E+10 | 26983.14 | 15-MAR-13:50 | 26983.14 | 0.00 |
April | 0.00 | 0.00 | 0.614316E+09 | 0.556160E+09 | 12678.71 | 08-APR-13:30 | 11144.38 | 0.00 |
May | 0.00 | 0.00 | 0.702397E+10 | 0.631329E+10 | 35361.65 | 23-MAY-14:30 | 35361.65 | 0.00 |
June | 0.00 | 0.00 | 0.329140E+11 | 0.248822E+11 | 80061.28 | 27-JUN-07:40 | 34604.88 | 0.00 |
July | 0.00 | 0.00 | 0.568858E+11 | 0.400106E+11 | 104684.31 | 20-JUL-06:03 | 42591.43 | 0.00 |
August | 0.00 | 0.00 | 0.463431E+11 | 0.357314E+11 | 104578.83 | 14-AUG-04:03 | 38842.97 | 0.00 |
September | 0.00 | 0.00 | 0.196575E+11 | 0.146531E+11 | 66938.75 | 15-SEP-11:00 | 36890.99 | 0.00 |
October | 0.00 | 0.00 | 0.214685E+10 | 0.177432E+10 | 23723.62 | 11-OCT-15:00 | 23723.62 | 0.00 |
November | 0.00 | 0.00 | 0.369972E+09 | 0.258440E+09 | 8676.55 | 16-NOV-18:00 | 6299.54 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.167652E+12 | 0.125568E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.568858E+11 | 0.400106E+11 | 104684.31 | 42591.43 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.188565E+10 | 0.156272E+10 | 33839.39 | 15-MAR-14:00 | 33839.39 | 0.00 |
April | 0.00 | 0.00 | 0.644254E+09 | 0.571368E+09 | 13556.86 | 08-APR-13:30 | 11547.37 | 0.00 |
May | 0.00 | 0.00 | 0.740420E+10 | 0.656933E+10 | 40225.11 | 10-MAY-14:30 | 40225.11 | 0.00 |
June | 0.00 | 0.00 | 0.353442E+11 | 0.265247E+11 | 117184.99 | 27-JUN-14:55 | 51449.06 | 0.00 |
July | 0.00 | 0.00 | 0.612064E+11 | 0.431509E+11 | 117258.77 | 20-JUL-05:03 | 47261.49 | 0.00 |
August | 0.00 | 0.00 | 0.490663E+11 | 0.377407E+11 | 117242.20 | 14-AUG-04:03 | 43435.38 | 0.00 |
September | 0.00 | 0.00 | 0.199311E+11 | 0.144910E+11 | 79019.18 | 15-SEP-12:30 | 44029.20 | 0.00 |
October | 0.00 | 0.00 | 0.208244E+10 | 0.166805E+10 | 23197.38 | 11-OCT-15:00 | 23197.38 | 0.00 |
November | 0.00 | 0.00 | 0.393591E+09 | 0.270347E+09 | 9369.53 | 27-NOV-07:03 | 7990.10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177958E+12 | 0.132549E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.612064E+11 | 0.431509E+11 | 117258.77 | 51449.06 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 1975.99 | 6957.06 | 31-JAN-12:14 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2014.02 | 6981.90 | 16-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2119.18 | 6959.22 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1905.89 | 6724.90 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1871.88 | 6422.98 | 02-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1809.36 | 6019.45 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1585.85 | 5668.54 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1712.95 | 5528.32 | 31-AUG-11:09 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1627.17 | 5693.05 | 28-SEP-11:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1699.94 | 6035.07 | 30-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1827.79 | 6406.13 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1850.94 | 6741.51 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1832.38 | ||||
Minimum of Months | 0.00 | 0.00 | 1585.85 | 5528.32 | ||
Maximum of Months | 0.00 | 0.00 | 2119.18 | 6981.90 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149038E+10 | 0.32 | 2559.47 | 02-JAN-05:01 | 0.82 |
February | 0.131212E+10 | 0.31 | 2559.47 | 06-FEB-07:01 | 0.82 |
March | 0.152607E+10 | 0.32 | 1821.19 | 17-MAR-07:02 | 0.68 |
April | 0.156799E+10 | 0.31 | 2425.24 | 11-APR-07:04 | 0.79 |
May | 0.233095E+10 | 0.36 | 4439.82 | 15-MAY-05:03 | 1.11 |
June | 0.402543E+10 | 0.49 | 7937.20 | 12-JUN-15:10 | 1.58 |
July | 0.517509E+10 | 0.54 | 10824.70 | 17-JUL-06:03 | 1.92 |
August | 0.519822E+10 | 0.55 | 10824.70 | 14-AUG-06:03 | 1.92 |
September | 0.346122E+10 | 0.44 | 8002.87 | 18-SEP-12:10 | 1.60 |
October | 0.189153E+10 | 0.32 | 4439.82 | 06-OCT-05:03 | 1.11 |
November | 0.140080E+10 | 0.29 | 2177.38 | 03-NOV-07:05 | 0.75 |
December | 0.135349E+10 | 0.29 | 2559.47 | 11-DEC-07:01 | 0.82 |
Annual Sum or Average | 0.307333E+11 | 0.38 | |||
Minimum of Months | 0.131212E+10 | 0.29 | 1821.19 | 0.68 | |
Maximum of Months | 0.519822E+10 | 0.55 | 10824.70 | 1.92 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147637E+10 | 0.33 | 2532.94 | 05-JAN-06:01 | 0.87 |
February | 0.131796E+10 | 0.33 | 2532.94 | 27-FEB-06:03 | 0.87 |
March | 0.146682E+10 | 0.32 | 2532.94 | 01-MAR-07:01 | 0.87 |
April | 0.141673E+10 | 0.31 | 2532.94 | 17-APR-06:01 | 0.87 |
May | 0.214128E+10 | 0.37 | 4578.58 | 31-MAY-16:00 | 1.22 |
June | 0.387473E+10 | 0.51 | 8112.30 | 12-JUN-15:30 | 1.74 |
July | 0.482623E+10 | 0.55 | 9533.69 | 17-JUL-06:03 | 1.92 |
August | 0.456182E+10 | 0.54 | 9533.69 | 14-AUG-04:03 | 1.92 |
September | 0.269945E+10 | 0.41 | 6638.65 | 21-SEP-15:40 | 1.53 |
October | 0.148431E+10 | 0.31 | 3064.68 | 11-OCT-15:20 | 0.96 |
November | 0.126163E+10 | 0.29 | 2532.94 | 20-NOV-07:01 | 0.87 |
December | 0.138542E+10 | 0.31 | 2532.94 | 18-DEC-06:01 | 0.87 |
Annual Sum or Average | 0.279128E+11 | 0.38 | |||
Minimum of Months | 0.126163E+10 | 0.29 | 2532.94 | 0.87 | |
Maximum of Months | 0.482623E+10 | 0.55 | 9533.69 | 1.92 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183999E+10 | 0.38 | 2489.88 | 02-JAN-05:01 | 0.79 |
February | 0.165075E+10 | 0.38 | 2489.88 | 01-FEB-06:01 | 0.79 |
March | 0.160808E+10 | 0.34 | 2489.88 | 01-MAR-06:01 | 0.79 |
April | 0.142780E+10 | 0.30 | 2489.88 | 03-APR-06:01 | 0.79 |
May | 0.202267E+10 | 0.34 | 4567.27 | 31-MAY-16:00 | 1.11 |
June | 0.360670E+10 | 0.46 | 11010.14 | 27-JUN-14:55 | 1.90 |
July | 0.452418E+10 | 0.49 | 11010.14 | 21-JUL-05:03 | 1.90 |
August | 0.414159E+10 | 0.48 | 11010.14 | 15-AUG-14:20 | 1.91 |
September | 0.234058E+10 | 0.37 | 6290.21 | 21-SEP-15:40 | 1.35 |
October | 0.144632E+10 | 0.29 | 2513.29 | 11-OCT-15:20 | 0.79 |
November | 0.133190E+10 | 0.29 | 2489.88 | 03-NOV-06:01 | 0.79 |
December | 0.170674E+10 | 0.36 | 2489.88 | 04-DEC-05:01 | 0.79 |
Annual Sum or Average | 0.276473E+11 | 0.37 | |||
Minimum of Months | 0.133190E+10 | 0.29 | 2489.88 | 0.79 | |
Maximum of Months | 0.452418E+10 | 0.49 | 11010.14 | 1.91 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:03 | 0.22 | 0.22 | 56.84 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 56.38 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 55.93 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:02 | 0.22 | 0.22 | 55.67 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 55.50 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.29 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 55.78 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 56.44 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 57.09 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.35 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:02 | 0.22 | 0.22 | 55.56 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:02 | 0.22 | 0.22 | 56.15 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.50 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.35 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 56.17 | 56.17 | 1975.99 | 6957.06 | 31-JAN-12:14 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.86 | 56.86 | 2014.02 | 6981.90 | 16-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.43 | 56.43 | 2119.18 | 6959.22 | 01-MAR-12:08 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.15 | 56.15 | 1905.89 | 6724.90 | 03-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.19 | 56.19 | 1871.88 | 6422.98 | 02-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.73 | 56.73 | 1809.36 | 6019.45 | 01-JUN-11:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.17 | 56.17 | 1585.85 | 5668.54 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.82 | 56.82 | 1712.95 | 5528.32 | 31-AUG-11:09 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.49 | 57.49 | 1627.17 | 5693.05 | 28-SEP-11:07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.95 | 55.95 | 1699.94 | 6035.07 | 30-OCT-11:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.00 | 56.00 | 1827.79 | 6406.13 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.94 | 56.94 | 1850.94 | 6741.51 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1832.38 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.95 | 55.95 | 1585.85 | 5528.32 | ||
Maximum of Months | 0.00 | 0.00 | 57.49 | 57.49 | 2119.18 | 6981.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.244209E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.200212E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.121192E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.583167E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.536272E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.121431E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.189094E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.170532E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.911458E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.450504E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.710526E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.188454E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.155432E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.450504E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.244209E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.201007E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.161706E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.666237E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.237244E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.380153E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.111849E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.172991E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.148046E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.708445E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.251223E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.477261E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.165673E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.123333E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.237244E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.201007E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.335151E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.281462E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.136175E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.461399E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.392180E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.114825E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.179906E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.150416E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.688578E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.457411E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.109650E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.299627E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.180717E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.392180E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.335151E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149038E+10 | 0.00 | 0.392658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131212E+10 | 0.00 | 0.338003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152607E+10 | 0.177792E+10 | 0.182582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156799E+10 | 0.609139E+09 | 0.580061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233095E+10 | 0.694770E+10 | 0.142019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.402543E+10 | 0.348096E+11 | 0.371448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.517509E+10 | 0.621910E+11 | 81016479.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.519822E+10 | 0.528586E+11 | 0.189416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346122E+10 | 0.231162E+11 | 0.534288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189153E+10 | 0.243859E+10 | 0.269236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140080E+10 | 0.410095E+09 | 0.895393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135349E+10 | 0.00 | 0.313012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307333E+11 | 0.185159E+12 | 0.142669E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131212E+10 | 0.00 | 81016479.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.519822E+10 | 0.621910E+11 | 0.392658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147637E+10 | 0.00 | 0.357528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131796E+10 | 0.00 | 0.307038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146682E+10 | 0.169693E+10 | 0.139826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141673E+10 | 0.614316E+09 | 0.330527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214128E+10 | 0.702397E+10 | 72561301.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387473E+10 | 0.329140E+11 | 92052.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.482623E+10 | 0.568858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.456182E+10 | 0.463431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.269945E+10 | 0.196575E+11 | 17375548.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148431E+10 | 0.214685E+10 | 0.184009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126163E+10 | 0.369972E+09 | 0.828062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138542E+10 | 0.00 | 0.300878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279128E+11 | 0.167652E+12 | 0.124043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.482623E+10 | 0.568858E+11 | 0.357528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.183999E+10 | 0.00 | 0.498184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165075E+10 | 0.00 | 0.431887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160808E+10 | 0.188565E+10 | 0.209126E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142780E+10 | 0.644254E+09 | 0.567666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202267E+10 | 0.740420E+10 | 0.274024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.360670E+10 | 0.353442E+11 | 5349966.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.452418E+10 | 0.612064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414159E+10 | 0.490663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234058E+10 | 0.199311E+11 | 99464887.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144632E+10 | 0.208244E+10 | 0.421773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133190E+10 | 0.393591E+09 | 0.147497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170674E+10 | 0.00 | 0.440924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276473E+11 | 0.177958E+12 | 0.183035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.452418E+10 | 0.612064E+11 | 0.498184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152607E+10 | 0.00 | 0.00 | 0.00 | 0.416558E+09 | 0.101765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156799E+10 | 0.00 | 0.00 | 0.00 | 0.154114E+09 | 0.410957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233095E+10 | 0.00 | 0.00 | 0.00 | 0.164441E+10 | 0.138736E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.402543E+10 | 0.00 | 0.00 | 0.00 | 0.774618E+10 | 0.371448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.517509E+10 | 0.00 | 0.00 | 0.00 | 0.136533E+11 | 81016479.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.519822E+10 | 0.00 | 0.00 | 0.00 | 0.116655E+11 | 0.189416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346122E+10 | 0.00 | 0.00 | 0.00 | 0.512127E+10 | 0.532092E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189153E+10 | 0.00 | 0.00 | 0.00 | 0.590281E+09 | 0.202323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140080E+10 | 0.00 | 0.00 | 0.00 | 0.103931E+09 | 0.560053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307333E+11 | 0.00 | 0.00 | 0.00 | 0.410956E+11 | 0.836026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81016479.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.519822E+10 | 0.00 | 0.00 | 0.00 | 0.136533E+11 | 0.229305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146682E+10 | 0.00 | 0.00 | 0.00 | 0.394272E+09 | 0.480128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141673E+10 | 0.00 | 0.00 | 0.00 | 0.154936E+09 | 0.800776E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.214128E+10 | 0.00 | 0.00 | 0.00 | 0.165415E+10 | 6095117.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387473E+10 | 0.00 | 0.00 | 0.00 | 0.731018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.482623E+10 | 0.00 | 0.00 | 0.00 | 0.124728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.456182E+10 | 0.00 | 0.00 | 0.00 | 0.102427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.269945E+10 | 0.00 | 0.00 | 0.00 | 0.438301E+10 | 1983246.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148431E+10 | 0.00 | 0.00 | 0.00 | 0.523985E+09 | 0.503934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126163E+10 | 0.00 | 0.00 | 0.00 | 93869584.74 | 0.341711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.279128E+11 | 0.00 | 0.00 | 0.00 | 0.372300E+11 | 0.581900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.482623E+10 | 0.00 | 0.00 | 0.00 | 0.124728E+11 | 0.186243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.183999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160808E+10 | 0.00 | 0.00 | 0.00 | 0.437083E+09 | 0.115723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142780E+10 | 0.00 | 0.00 | 0.00 | 0.163064E+09 | 0.302313E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202267E+10 | 0.00 | 0.00 | 0.00 | 0.175170E+10 | 0.147429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.360670E+10 | 0.00 | 0.00 | 0.00 | 0.787534E+10 | 495515.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.452418E+10 | 0.00 | 0.00 | 0.00 | 0.134664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.414159E+10 | 0.00 | 0.00 | 0.00 | 0.109000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234058E+10 | 0.00 | 0.00 | 0.00 | 0.448402E+10 | 61182765.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144632E+10 | 0.00 | 0.00 | 0.00 | 0.513788E+09 | 0.261400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133190E+10 | 0.00 | 0.00 | 0.00 | 0.100152E+09 | 0.953295E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276473E+11 | 0.00 | 0.00 | 0.00 | 0.396916E+11 | 0.113378E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.452418E+10 | 0.00 | 0.00 | 0.00 | 0.134664E+11 | 0.316751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154835E+11 | 0.00 | 0.00 | 321378.95 | 0.00 | 0.512770E+09 | 0.969839E+09 | 0.00 | 0.27 |
February | 0.147154E+11 | 0.00 | 0.00 | 394982.56 | 0.00 | 14659271.23 | 0.111801E+10 | 0.00 | 0.28 |
March | 0.789106E+10 | 9468711.86 | 0.00 | 14263637.99 | 0.00 | 779347.16 | 0.837183E+10 | 0.00 | 0.37 |
April | 0.367136E+10 | 0.00 | 0.00 | 22177874.77 | 0.00 | 0.00 | 0.120384E+11 | 0.00 | 0.46 |
May | 0.113735E+10 | 6422471.50 | 0.00 | 36148192.07 | 9143831.96 | 0.00 | 0.175391E+11 | 0.00 | 0.84 |
June | 0.659709E+09 | 0.164247E+10 | 0.00 | 32833787.44 | 0.220808E+09 | 0.00 | 0.113586E+11 | 0.00 | 1.04 |
July | 0.347278E+09 | 0.569862E+10 | 0.00 | 17324347.38 | 0.560354E+09 | 0.00 | 0.345235E+10 | 0.00 | 0.84 |
August | 0.631406E+09 | 0.322879E+10 | 0.00 | 31396672.38 | 0.200152E+09 | 0.00 | 0.739045E+10 | 0.00 | 1.00 |
September | 0.140952E+10 | 0.107380E+10 | 0.00 | 33858294.25 | 39762061.51 | 0.00 | 0.133532E+11 | 0.00 | 1.03 |
October | 0.193880E+10 | 0.00 | 0.00 | 30276641.98 | 779459.23 | 0.00 | 0.156494E+11 | 0.00 | 0.59 |
November | 0.477741E+10 | 0.00 | 0.00 | 18675134.44 | 8245825.95 | 0.00 | 0.959274E+10 | 0.00 | 0.36 |
December | 0.128102E+11 | 0.00 | 0.00 | 2093325.87 | 0.00 | 7497492.19 | 0.338410E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.654729E+11 | 0.116596E+11 | 0.00 | 0.239764E+09 | 0.103924E+10 | 0.535706E+09 | 0.104218E+12 | 0.00 | 0.62 |
Minimum of Months | 0.347278E+09 | 0.00 | 0.00 | 321378.95 | 0.00 | 0.00 | 0.969839E+09 | 0.00 | 0.27 |
Maximum of Months | 0.154835E+11 | 0.569862E+10 | 0.00 | 36148192.07 | 0.560354E+09 | 0.512770E+09 | 0.175391E+11 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282889E+10 | 0.00 | 0.00 | 0.27 |
February | 0.131331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235099E+10 | 0.00 | 0.00 | 0.28 |
March | 0.135510E+11 | 0.00 | 0.00 | 1133421.24 | 8717290.53 | 0.185476E+09 | 0.705835E+09 | 0.00 | 0.32 |
April | 0.914914E+10 | 0.00 | 0.00 | 2422813.88 | 0.00 | 18422635.58 | 0.272791E+10 | 0.00 | 0.35 |
May | 0.444549E+10 | 2484763.62 | 0.00 | 14189180.88 | 25344950.71 | 0.00 | 0.826781E+10 | 0.00 | 0.56 |
June | 0.900172E+09 | 0.123889E+10 | 0.00 | 18879452.28 | 0.221973E+09 | 0.00 | 0.722507E+10 | 0.00 | 0.72 |
July | 0.423187E+09 | 0.422609E+10 | 0.00 | 11413019.24 | 0.593434E+09 | 0.00 | 0.216626E+10 | 0.00 | 0.62 |
August | 0.682903E+09 | 0.233124E+10 | 0.00 | 19384313.72 | 0.204226E+09 | 0.00 | 0.462770E+10 | 0.00 | 0.69 |
September | 0.232359E+10 | 0.712303E+09 | 0.00 | 15847745.47 | 39035112.74 | 0.00 | 0.701921E+10 | 0.00 | 0.66 |
October | 0.786201E+10 | 0.00 | 0.00 | 4626420.60 | 2623187.29 | 582989.44 | 0.358939E+10 | 0.00 | 0.38 |
November | 0.113087E+11 | 0.00 | 225946.75 | 72582.30 | 11474534.70 | 67331922.91 | 0.176175E+09 | 4515.31 | 0.30 |
December | 0.137508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188331E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.913937E+11 | 0.851101E+10 | 225946.75 | 87968949.62 | 0.110683E+10 | 0.733500E+10 | 0.365053E+11 | 4515.31 | 0.45 |
Minimum of Months | 0.423187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.138635E+11 | 0.422609E+10 | 225946.75 | 19384313.72 | 0.593434E+09 | 0.282889E+10 | 0.826781E+10 | 4515.31 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.780959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.771551E+10 | 0.00 | 0.00 | 0.26 |
February | 0.816807E+10 | 0.00 | 0.00 | 0.00 | 443344.36 | 0.627949E+10 | 0.00 | 23357.28 | 0.27 |
March | 0.114122E+11 | 0.00 | 0.00 | 745347.04 | 1281195.85 | 0.172918E+10 | 0.531391E+09 | 0.00 | 0.32 |
April | 0.101233E+11 | 0.00 | 0.00 | 1015386.32 | 0.00 | 0.242071E+09 | 0.129988E+10 | 0.00 | 0.35 |
May | 0.563473E+10 | 524389.43 | 0.00 | 11512150.71 | 34987806.07 | 596104.15 | 0.707346E+10 | 0.00 | 0.57 |
June | 0.164138E+10 | 0.128681E+10 | 0.00 | 17399103.65 | 0.305304E+09 | 0.00 | 0.663639E+10 | 0.00 | 0.77 |
July | 0.496960E+09 | 0.432471E+10 | 0.00 | 10181509.37 | 0.625192E+09 | 0.00 | 0.205250E+10 | 0.00 | 0.67 |
August | 0.112001E+10 | 0.232642E+10 | 0.00 | 16392563.50 | 0.318119E+09 | 0.00 | 0.385752E+10 | 0.00 | 0.72 |
September | 0.347600E+10 | 0.688223E+09 | 0.00 | 11091359.38 | 0.100353E+09 | 0.00 | 0.504017E+10 | 0.00 | 0.65 |
October | 0.889709E+10 | 0.00 | 0.00 | 1557525.61 | 174215.10 | 0.149957E+09 | 0.159337E+10 | 0.00 | 0.37 |
November | 0.992092E+10 | 0.00 | 1477477.04 | 0.00 | 15002055.70 | 0.830203E+09 | 0.00 | 40810.47 | 0.30 |
December | 0.833529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610754E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.770356E+11 | 0.862668E+10 | 1477477.04 | 69894945.58 | 0.140086E+10 | 0.230545E+11 | 0.280847E+11 | 64167.75 | 0.46 |
Minimum of Months | 0.496960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.114122E+11 | 0.432471E+10 | 1477477.04 | 17399103.65 | 0.625192E+09 | 0.771551E+10 | 0.707346E+10 | 40810.47 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 65686708.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364497E+10 | 0.00 | 0.00 | 0.29 |
February | 0.139581E+09 | 0.00 | 59899.85 | 0.00 | 12707.79 | 0.330669E+10 | 0.00 | 31837.20 | 0.30 |
March | 0.111312E+10 | 91452.30 | 0.00 | 186818.43 | 178240.15 | 0.184118E+10 | 55102839.51 | 0.00 | 0.33 |
April | 0.186836E+10 | 0.00 | 0.00 | 162478.79 | 0.00 | 0.422834E+09 | 0.179483E+09 | 0.00 | 0.35 |
May | 0.143461E+10 | 0.00 | 0.00 | 2511287.42 | 7475337.35 | 15875042.65 | 0.131346E+10 | 0.00 | 0.60 |
June | 0.383360E+09 | 0.428081E+09 | 0.00 | 4670137.83 | 57805879.24 | 0.00 | 0.158616E+10 | 0.00 | 0.96 |
July | 0.121168E+09 | 0.137301E+10 | 0.00 | 2792427.19 | 0.112331E+09 | 0.00 | 0.527579E+09 | 0.00 | 0.88 |
August | 0.315564E+09 | 0.694461E+09 | 0.00 | 4182060.86 | 60545784.62 | 0.00 | 0.875857E+09 | 0.00 | 0.88 |
September | 0.963890E+09 | 0.176353E+09 | 0.00 | 2171038.92 | 24889108.64 | 6959345.68 | 0.849500E+09 | 0.00 | 0.69 |
October | 0.173612E+10 | 0.00 | 0.00 | 197729.84 | 36672.38 | 0.344493E+09 | 0.166832E+09 | 0.00 | 0.37 |
November | 0.884167E+09 | 0.00 | 745150.05 | 0.00 | 2764833.54 | 0.140850E+10 | 0.00 | 12553.15 | 0.30 |
December | 0.138989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325261E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.916461E+10 | 0.267200E+10 | 805049.90 | 16873979.28 | 0.266039E+09 | 0.142441E+11 | 0.555397E+10 | 44390.34 | 0.52 |
Minimum of Months | 65686708.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.186836E+10 | 0.137301E+10 | 745150.05 | 4670137.83 | 0.112331E+09 | 0.364497E+10 | 0.158616E+10 | 31837.20 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 79168274.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305067E+10 | 0.00 | 0.00 | 0.39 |
February | 0.519493E+09 | 0.00 | 58658.16 | 0.00 | 16393.57 | 0.239823E+10 | 0.00 | 22996.50 | 0.40 |
March | 0.155998E+10 | 307083.41 | 0.00 | 222102.87 | 0.00 | 0.105288E+10 | 88233808.24 | 0.00 | 0.48 |
April | 0.150184E+10 | 0.00 | 0.00 | 1245187.30 | 0.00 | 0.189736E+09 | 0.816406E+09 | 0.00 | 0.57 |
May | 0.103029E+10 | 0.00 | 0.00 | 4030927.49 | 6981215.44 | 4833281.53 | 0.214935E+10 | 0.00 | 1.08 |
June | 0.315525E+09 | 0.403606E+09 | 0.00 | 5324889.18 | 33433005.29 | 0.00 | 0.206511E+10 | 0.00 | 1.55 |
July | 79323520.36 | 0.116625E+10 | 0.00 | 4210655.89 | 0.105963E+09 | 0.00 | 0.806402E+09 | 0.00 | 1.45 |
August | 0.240545E+09 | 0.555254E+09 | 0.00 | 4864449.53 | 62848574.73 | 0.00 | 0.107529E+10 | 0.00 | 1.42 |
September | 0.752799E+09 | 0.153384E+09 | 0.00 | 3160093.38 | 29541455.86 | 3242305.04 | 0.133656E+10 | 0.00 | 1.18 |
October | 0.157851E+10 | 0.00 | 0.00 | 459959.34 | 34248.32 | 0.217263E+09 | 0.319165E+09 | 0.00 | 0.56 |
November | 0.992788E+09 | 0.00 | 424461.01 | 0.00 | 2823478.02 | 0.112733E+10 | 0.00 | 7564.39 | 0.44 |
December | 0.146153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276199E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.879641E+10 | 0.227880E+10 | 483119.18 | 23518264.99 | 0.241641E+09 | 0.108062E+11 | 0.865651E+10 | 30560.89 | 0.83 |
Minimum of Months | 79168274.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.157851E+10 | 0.116625E+10 | 424461.01 | 5324889.18 | 0.105963E+09 | 0.305067E+10 | 0.214935E+10 | 22996.50 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.891279E+09 | 0.00 | 0.00 | 190481.01 | 0.00 | 0.298761E+10 | 0.135898E+09 | 0.00 | 0.32 |
February | 0.105187E+10 | 0.00 | 71400.75 | 428058.98 | 19869.14 | 0.251937E+10 | 0.244907E+09 | 31112.12 | 0.33 |
March | 0.171795E+10 | 1059424.21 | 0.00 | 1952247.44 | 0.00 | 0.104188E+10 | 0.967279E+09 | 0.00 | 0.44 |
April | 0.165530E+10 | 0.00 | 0.00 | 2771580.29 | 0.00 | 0.347170E+09 | 0.165428E+10 | 0.00 | 0.54 |
May | 0.135868E+10 | 4857488.58 | 0.00 | 5448758.24 | 4316509.09 | 27477910.84 | 0.272369E+10 | 0.00 | 0.91 |
June | 0.511072E+09 | 0.503539E+09 | 0.00 | 6077573.53 | 53936938.73 | 0.00 | 0.209878E+10 | 0.00 | 1.20 |
July | 0.169079E+09 | 0.165530E+10 | 0.00 | 3720640.34 | 0.123114E+09 | 0.00 | 0.666338E+09 | 0.00 | 1.08 |
August | 0.363396E+09 | 0.882438E+09 | 0.00 | 6595431.05 | 51628848.95 | 0.00 | 0.131076E+10 | 0.00 | 1.22 |
September | 0.799457E+09 | 0.275133E+09 | 0.00 | 7076320.38 | 23756462.83 | 4521573.01 | 0.256289E+10 | 0.00 | 1.27 |
October | 0.157556E+10 | 0.00 | 0.00 | 3581085.55 | 42529.22 | 0.211609E+09 | 0.174668E+10 | 0.00 | 0.65 |
November | 0.131161E+10 | 0.00 | 558178.73 | 882244.40 | 3506166.72 | 0.104981E+10 | 0.458403E+09 | 9637.07 | 0.37 |
December | 0.712466E+09 | 0.00 | 0.00 | 107873.65 | 0.00 | 0.289847E+10 | 78662373.50 | 0.00 | 0.32 |
Annual Sum or Average | 0.121177E+11 | 0.332232E+10 | 629579.48 | 38832294.86 | 0.260321E+09 | 0.110879E+11 | 0.146486E+11 | 40749.18 | 0.72 |
Minimum of Months | 0.169079E+09 | 0.00 | 0.00 | 107873.65 | 0.00 | 0.00 | 78662373.50 | 0.00 | 0.32 |
Maximum of Months | 0.171795E+10 | 0.165530E+10 | 558178.73 | 7076320.38 | 0.123114E+09 | 0.298761E+10 | 0.272369E+10 | 31112.12 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318639E+10 | 0.00 | 0.00 | 0.43 |
February | 0.426110E+09 | 0.00 | 65269.24 | 5274.26 | 17984.30 | 0.275720E+10 | 10976198.58 | 23699.14 | 0.44 |
March | 0.143878E+10 | 10363.33 | 0.00 | 352454.07 | 265941.77 | 0.136702E+10 | 0.175901E+09 | 0.00 | 0.53 |
April | 0.165209E+10 | 0.00 | 0.00 | 1296749.93 | 0.00 | 0.380393E+09 | 0.799976E+09 | 0.00 | 0.65 |
May | 0.137507E+10 | 1321359.95 | 0.00 | 3819704.75 | 6383710.74 | 20858596.40 | 0.196592E+10 | 0.00 | 1.15 |
June | 0.486687E+09 | 0.399567E+09 | 0.00 | 5524466.98 | 54062767.49 | 0.00 | 0.172228E+10 | 0.00 | 1.60 |
July | 0.156635E+09 | 0.119794E+10 | 0.00 | 2918282.80 | 0.109910E+09 | 0.00 | 0.449415E+09 | 0.00 | 1.30 |
August | 0.378333E+09 | 0.596993E+09 | 0.00 | 4213832.04 | 55862095.54 | 0.00 | 0.754274E+09 | 0.00 | 1.33 |
September | 0.989603E+09 | 0.134181E+09 | 0.00 | 2910277.91 | 39763406.45 | 7367196.29 | 0.103792E+10 | 0.00 | 1.17 |
October | 0.174258E+10 | 0.00 | 0.00 | 616933.87 | 37571.56 | 0.304509E+09 | 0.325315E+09 | 0.00 | 0.64 |
November | 0.102987E+10 | 0.00 | 456165.64 | 7381.89 | 3097449.78 | 0.127131E+10 | 22643210.72 | 7993.94 | 0.48 |
December | 0.246071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292687E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.101518E+11 | 0.233001E+10 | 521434.88 | 21665358.50 | 0.269401E+09 | 0.122219E+11 | 0.726462E+10 | 31693.08 | 0.85 |
Minimum of Months | 0.156635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.174258E+10 | 0.119794E+10 | 456165.64 | 5524466.98 | 0.109910E+09 | 0.318639E+10 | 0.196592E+10 | 23699.14 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369671E+10 | 0.00 | 0.00 | 0.29 |
February | 0.152507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340190E+10 | 0.00 | 0.00 | 0.29 |
March | 0.117937E+10 | 0.00 | 0.00 | 353.27 | 1524853.79 | 0.201877E+10 | 644505.21 | 0.00 | 0.33 |
April | 0.211887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411298E+09 | 0.00 | 0.00 | 0.35 |
May | 0.204590E+10 | 10223.67 | 0.00 | 504704.29 | 2825902.34 | 4898937.52 | 0.323284E+09 | 0.00 | 0.49 |
June | 0.484989E+09 | 0.265128E+09 | 0.00 | 2860605.90 | 61433832.92 | 0.00 | 0.102604E+10 | 0.00 | 0.69 |
July | 0.147031E+09 | 0.983827E+09 | 0.00 | 2046795.80 | 0.149517E+09 | 0.00 | 0.400695E+09 | 0.00 | 0.65 |
August | 0.357724E+09 | 0.563320E+09 | 0.00 | 3521772.63 | 61214851.04 | 0.00 | 0.759166E+09 | 0.00 | 0.74 |
September | 0.970781E+09 | 0.159989E+09 | 0.00 | 2198429.72 | 14554422.94 | 0.00 | 0.923961E+09 | 0.00 | 0.66 |
October | 0.217686E+10 | 0.00 | 0.00 | 292832.59 | 163964.25 | 39305422.56 | 0.251635E+09 | 0.00 | 0.38 |
November | 0.202371E+10 | 0.00 | 25591.25 | 0.00 | 1710264.73 | 0.518280E+09 | 0.00 | 4727.74 | 0.30 |
December | 0.413611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310062E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.121788E+11 | 0.197227E+10 | 25591.25 | 11425494.20 | 0.292945E+09 | 0.131918E+11 | 0.368542E+10 | 4727.74 | 0.46 |
Minimum of Months | 0.107450E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.217686E+10 | 0.983827E+09 | 25591.25 | 3521772.63 | 0.149517E+09 | 0.369671E+10 | 0.102604E+10 | 4727.74 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268591E+10 | 0.00 | 0.00 | 0.34 |
February | 0.434950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219663E+10 | 0.00 | 0.00 | 0.34 |
March | 0.148236E+10 | 205069.21 | 0.00 | 40817.75 | 958730.63 | 0.917001E+09 | 6890703.62 | 0.00 | 0.39 |
April | 0.145873E+10 | 0.00 | 0.00 | 661971.12 | 0.00 | 0.113542E+09 | 0.456704E+09 | 0.00 | 0.44 |
May | 0.951929E+09 | 10793.89 | 0.00 | 2513722.50 | 2156786.91 | 669259.28 | 0.132750E+10 | 0.00 | 0.78 |
June | 0.252027E+09 | 0.277301E+09 | 0.00 | 4229134.60 | 32143489.97 | 0.00 | 0.157420E+10 | 0.00 | 1.18 |
July | 87477200.06 | 0.922805E+09 | 0.00 | 3324553.53 | 0.100741E+09 | 0.00 | 0.662496E+09 | 0.00 | 1.12 |
August | 0.213631E+09 | 0.489726E+09 | 0.00 | 4590074.25 | 37800933.07 | 0.00 | 0.100582E+10 | 0.00 | 1.20 |
September | 0.536156E+09 | 0.146013E+09 | 0.00 | 3605794.77 | 7616238.05 | 0.00 | 0.149715E+10 | 0.00 | 1.09 |
October | 0.141226E+10 | 0.00 | 0.00 | 944365.19 | 125140.89 | 20735816.27 | 0.549125E+09 | 0.00 | 0.50 |
November | 0.160406E+10 | 0.00 | 16328.23 | 11672.96 | 1305309.30 | 0.313163E+09 | 23705077.99 | 2216.21 | 0.36 |
December | 0.347905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229495E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.890962E+10 | 0.183606E+10 | 16328.23 | 19922106.68 | 0.182848E+09 | 0.854261E+10 | 0.710359E+10 | 2216.21 | 0.68 |
Minimum of Months | 87477200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.160406E+10 | 0.922805E+09 | 16328.23 | 4590074.25 | 0.100741E+09 | 0.268591E+10 | 0.157420E+10 | 2216.21 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.171622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569757E+10 | 0.00 | 0.00 | 0.43 |
February | 0.211685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510213E+10 | 0.00 | 0.00 | 0.43 |
March | 0.952939E+09 | 2852904.71 | 0.00 | 180967.27 | 154328.06 | 0.313325E+10 | 9069241.87 | 0.00 | 0.41 |
April | 0.138255E+10 | 0.00 | 0.00 | 233931.82 | 0.00 | 0.148404E+10 | 0.168060E+09 | 0.00 | 0.41 |
May | 0.170487E+10 | 24367.08 | 4708.14 | 926977.29 | 2821960.16 | 0.580193E+09 | 0.406803E+09 | 253.88 | 0.57 |
June | 0.827983E+09 | 0.324750E+09 | 0.00 | 2164812.68 | 73683055.36 | 0.152526E+09 | 0.596179E+09 | 0.00 | 0.75 |
July | 0.199483E+09 | 0.128390E+10 | 0.00 | 2164419.60 | 0.142478E+09 | 38889143.91 | 0.331459E+09 | 0.00 | 0.75 |
August | 0.428720E+09 | 0.792726E+09 | 0.00 | 4661613.93 | 50707547.26 | 92199953.81 | 0.737543E+09 | 0.00 | 0.94 |
September | 0.814450E+09 | 0.233823E+09 | 0.00 | 4893464.96 | 13905565.94 | 0.229069E+09 | 0.161739E+10 | 0.00 | 1.01 |
October | 0.156542E+10 | 88895.02 | 0.00 | 1425949.16 | 118830.47 | 0.864251E+09 | 0.742718E+09 | 0.00 | 0.53 |
November | 0.990291E+09 | 0.00 | 104994.17 | 83691.40 | 1619991.00 | 0.208325E+10 | 82499341.42 | 10203.16 | 0.37 |
December | 0.227523E+09 | 0.00 | 0.00 | 5963.29 | 0.00 | 0.499922E+10 | 10556449.55 | 0.00 | 0.41 |
Annual Sum or Average | 0.947753E+10 | 0.263817E+10 | 109702.31 | 16741791.39 | 0.285489E+09 | 0.244566E+11 | 0.470228E+10 | 10457.04 | 0.58 |
Minimum of Months | 0.171622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38889143.91 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.170487E+10 | 0.128390E+10 | 104994.17 | 4893464.96 | 0.142478E+09 | 0.569757E+10 | 0.161739E+10 | 10203.16 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223512E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272367E+10 | 0.00 | 0.00 | 0.35 |
February | 0.329165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243372E+10 | 0.00 | 0.00 | 0.36 |
March | 0.146262E+10 | 0.00 | 0.00 | 29565.71 | 1219959.23 | 0.104875E+10 | 16195918.89 | 0.00 | 0.41 |
April | 0.158308E+10 | 0.00 | 0.00 | 555796.00 | 0.00 | 0.191777E+09 | 0.339537E+09 | 0.00 | 0.46 |
May | 0.121308E+10 | 143624.95 | 0.00 | 2044840.34 | 2144668.73 | 2496559.79 | 0.104197E+10 | 0.00 | 0.78 |
June | 0.318316E+09 | 0.290349E+09 | 0.00 | 4064696.25 | 36292438.51 | 0.00 | 0.131394E+10 | 0.00 | 1.19 |
July | 0.120519E+09 | 0.955005E+09 | 0.00 | 2480884.61 | 78385886.48 | 0.00 | 0.378120E+09 | 0.00 | 0.97 |
August | 0.256400E+09 | 0.553173E+09 | 0.00 | 3768500.75 | 26612812.85 | 0.00 | 0.724967E+09 | 0.00 | 1.11 |
September | 0.618903E+09 | 0.131674E+09 | 0.00 | 3203797.60 | 9050528.23 | 0.00 | 0.118211E+10 | 0.00 | 1.02 |
October | 0.159863E+10 | 0.00 | 0.00 | 744344.10 | 131179.59 | 25840614.67 | 0.436855E+09 | 0.00 | 0.52 |
November | 0.164815E+10 | 0.00 | 17096.89 | 11460.19 | 1368297.25 | 0.368129E+09 | 17984365.67 | 2342.41 | 0.38 |
December | 0.411485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235349E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.978386E+10 | 0.193034E+10 | 17096.89 | 16903885.55 | 0.155206E+09 | 0.914787E+10 | 0.545168E+10 | 2342.41 | 0.66 |
Minimum of Months | 0.120519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.164815E+10 | 0.955005E+09 | 17096.89 | 4064696.25 | 78385886.48 | 0.272367E+10 | 0.131394E+10 | 2342.41 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348903E+10 | 0.00 | 0.00 | 0.28 |
February | 0.452472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300771E+10 | 0.00 | 0.00 | 0.29 |
March | 0.161506E+10 | 817802.10 | 0.00 | 197476.16 | 1018715.27 | 0.136928E+10 | 94981777.20 | 0.00 | 0.32 |
April | 0.214547E+10 | 0.00 | 0.00 | 194975.89 | 0.00 | 0.182181E+09 | 0.176368E+09 | 0.00 | 0.35 |
May | 0.119920E+10 | 123556.90 | 0.00 | 2879718.12 | 5623658.59 | 169723.35 | 0.151343E+10 | 0.00 | 0.59 |
June | 0.304534E+09 | 0.415077E+09 | 0.00 | 4769684.28 | 40957693.31 | 0.00 | 0.160113E+10 | 0.00 | 0.90 |
July | 0.103435E+09 | 0.133989E+10 | 0.00 | 2894152.15 | 0.111629E+09 | 0.00 | 0.530153E+09 | 0.00 | 0.80 |
August | 0.254742E+09 | 0.694393E+09 | 0.00 | 4381562.79 | 41640640.10 | 0.00 | 0.943793E+09 | 0.00 | 0.84 |
September | 0.834948E+09 | 0.185371E+09 | 0.00 | 2693927.22 | 9670069.86 | 0.00 | 0.105922E+10 | 0.00 | 0.69 |
October | 0.196442E+10 | 0.00 | 0.00 | 424463.14 | 552640.64 | 0.107478E+09 | 0.297969E+09 | 0.00 | 0.38 |
November | 0.172976E+10 | 0.00 | 68544.34 | 0.00 | 2417400.49 | 0.711832E+09 | 0.00 | 5596.47 | 0.30 |
December | 0.402421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303976E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.112212E+11 | 0.263567E+10 | 68544.34 | 18435959.75 | 0.213510E+09 | 0.119074E+11 | 0.621705E+10 | 5596.47 | 0.50 |
Minimum of Months | 0.103435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.214547E+10 | 0.133989E+10 | 68544.34 | 4769684.28 | 0.111629E+09 | 0.348903E+10 | 0.160113E+10 | 5596.47 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.348315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302442E+10 | 0.00 | 0.00 | 0.41 |
February | 0.746532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238592E+10 | 0.00 | 0.00 | 0.42 |
March | 0.195832E+10 | 1939383.35 | 0.00 | 230484.00 | 0.00 | 0.813340E+09 | 0.114268E+09 | 0.00 | 0.48 |
April | 0.165873E+10 | 0.00 | 0.00 | 1479614.34 | 0.00 | 83810836.88 | 0.924889E+09 | 0.00 | 0.59 |
May | 0.100819E+10 | 73058.83 | 0.00 | 4239371.74 | 5374023.92 | 216422.97 | 0.216957E+10 | 0.00 | 1.07 |
June | 0.280219E+09 | 0.370607E+09 | 0.00 | 5212026.87 | 28435375.74 | 0.00 | 0.202139E+10 | 0.00 | 1.44 |
July | 78687490.60 | 0.110665E+10 | 0.00 | 4011008.75 | 0.107812E+09 | 0.00 | 0.791379E+09 | 0.00 | 1.30 |
August | 0.228334E+09 | 0.534885E+09 | 0.00 | 4855436.03 | 45410084.33 | 0.00 | 0.111391E+10 | 0.00 | 1.33 |
September | 0.755661E+09 | 0.155385E+09 | 0.00 | 3492174.95 | 14062034.51 | 232006.94 | 0.144552E+10 | 0.00 | 1.17 |
October | 0.175101E+10 | 0.00 | 0.00 | 746681.99 | 523988.55 | 67649127.07 | 0.474196E+09 | 0.00 | 0.58 |
November | 0.164475E+10 | 0.00 | 57402.43 | 10897.43 | 2292068.44 | 0.648392E+09 | 18855278.07 | 4746.31 | 0.45 |
December | 0.333451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282445E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.107922E+11 | 0.216954E+10 | 57402.43 | 24277696.09 | 0.203910E+09 | 0.984843E+10 | 0.907397E+10 | 4746.31 | 0.81 |
Minimum of Months | 78687490.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.195832E+10 | 0.110665E+10 | 57402.43 | 5212026.87 | 0.107812E+09 | 0.302442E+10 | 0.216957E+10 | 4746.31 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118855E+10 | 0.00 | 0.00 | 367120.86 | 0.00 | 0.260020E+10 | 0.231148E+09 | 0.00 | 0.31 |
February | 0.140410E+10 | 0.00 | 0.00 | 575809.24 | 0.00 | 0.205262E+10 | 0.338953E+09 | 0.00 | 0.32 |
March | 0.197974E+10 | 7281427.20 | 0.00 | 2454929.96 | 0.00 | 0.596460E+09 | 0.123532E+10 | 0.00 | 0.42 |
April | 0.176545E+10 | 0.00 | 0.00 | 3078492.55 | 0.00 | 0.144824E+09 | 0.166312E+10 | 0.00 | 0.53 |
May | 0.114486E+10 | 3547416.84 | 0.00 | 5787283.56 | 3122522.23 | 380910.01 | 0.271024E+10 | 0.00 | 0.88 |
June | 0.395667E+09 | 0.469660E+09 | 0.00 | 6029396.55 | 43482689.00 | 0.00 | 0.198965E+10 | 0.00 | 1.10 |
July | 0.143142E+09 | 0.160541E+10 | 0.00 | 3424599.24 | 0.106319E+09 | 0.00 | 0.597822E+09 | 0.00 | 0.94 |
August | 0.290295E+09 | 0.872620E+09 | 0.00 | 6540777.05 | 36397940.92 | 0.00 | 0.127321E+10 | 0.00 | 1.12 |
September | 0.670924E+09 | 0.276853E+09 | 0.00 | 7537312.93 | 9349072.81 | 0.00 | 0.262927E+10 | 0.00 | 1.24 |
October | 0.152542E+10 | 224902.94 | 0.00 | 4537380.84 | 491789.11 | 63804175.85 | 0.210056E+10 | 0.00 | 0.67 |
November | 0.180281E+10 | 0.00 | 49804.41 | 1350910.26 | 2635364.43 | 0.503855E+09 | 0.658462E+09 | 3125.97 | 0.37 |
December | 0.113599E+10 | 0.00 | 0.00 | 201174.36 | 0.00 | 0.244104E+10 | 0.134471E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.134470E+11 | 0.323560E+10 | 49804.41 | 41885187.40 | 0.201798E+09 | 0.840318E+10 | 0.155622E+11 | 3125.97 | 0.69 |
Minimum of Months | 0.143142E+09 | 0.00 | 0.00 | 201174.36 | 0.00 | 0.00 | 0.134471E+09 | 0.00 | 0.31 |
Maximum of Months | 0.197974E+10 | 0.160541E+10 | 49804.41 | 7537312.93 | 0.106319E+09 | 0.260020E+10 | 0.271024E+10 | 3125.97 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.446073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303326E+10 | 0.00 | 0.00 | 0.42 |
February | 0.746201E+09 | 0.00 | 0.00 | 8673.89 | 0.00 | 0.247894E+10 | 12819393.33 | 0.00 | 0.43 |
March | 0.189967E+10 | 456721.42 | 0.00 | 381189.52 | 1344716.09 | 0.902900E+09 | 0.197984E+09 | 0.00 | 0.50 |
April | 0.179833E+10 | 0.00 | 0.00 | 1356583.52 | 0.00 | 0.163551E+09 | 0.794810E+09 | 0.00 | 0.62 |
May | 0.121451E+10 | 330554.39 | 0.00 | 4025519.36 | 5289580.35 | 630736.20 | 0.190041E+10 | 0.00 | 1.09 |
June | 0.380143E+09 | 0.382476E+09 | 0.00 | 5153567.38 | 32582865.29 | 0.00 | 0.162833E+10 | 0.00 | 1.45 |
July | 0.146407E+09 | 0.117764E+10 | 0.00 | 2798824.26 | 82956767.34 | 0.00 | 0.400633E+09 | 0.00 | 1.14 |
August | 0.319623E+09 | 0.591314E+09 | 0.00 | 4052946.72 | 31546504.33 | 0.00 | 0.745871E+09 | 0.00 | 1.21 |
September | 0.825830E+09 | 0.146702E+09 | 0.00 | 3264328.16 | 18151385.87 | 239497.94 | 0.113965E+10 | 0.00 | 1.12 |
October | 0.187564E+10 | 0.00 | 0.00 | 767042.33 | 540906.99 | 96676613.28 | 0.429606E+09 | 0.00 | 0.62 |
November | 0.171260E+10 | 0.00 | 157260.75 | 28624.86 | 2267774.53 | 0.647304E+09 | 26739769.94 | 4887.78 | 0.46 |
December | 0.533315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272580E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.118983E+11 | 0.229891E+10 | 157260.75 | 21837300.01 | 0.174681E+09 | 0.100493E+11 | 0.727686E+10 | 4887.78 | 0.79 |
Minimum of Months | 0.146407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.189967E+10 | 0.117764E+10 | 157260.75 | 5153567.38 | 82956767.34 | 0.303326E+10 | 0.190041E+10 | 4887.78 | 1.45 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.140486E+12 | 0.194031E+11 | 0.00 | 0.139357E+12 | 0.129018E+11 |
February | 0.214890E+12 | 0.190091E+11 | 0.00 | 0.129238E+12 | 0.119089E+11 |
March | 0.315968E+12 | 0.141824E+11 | 0.00 | 0.159024E+12 | 0.132592E+11 |
April | 0.372556E+12 | 0.106746E+11 | 0.00 | 0.189779E+12 | 0.405209E+10 |
May | 0.452701E+12 | 0.643391E+10 | 0.00 | 0.201846E+12 | 0.264826E+11 |
June | 0.486317E+12 | 0.237319E+10 | 0.00 | 0.109574E+12 | 0.126001E+12 |
July | 0.451916E+12 | -0.113762E+10 | 0.00 | -0.545283E+10 | 0.219876E+12 |
August | 0.387786E+12 | 0.716640E+09 | 0.00 | 0.690302E+11 | 0.181076E+12 |
September | 0.299419E+12 | 0.373374E+10 | 0.00 | 0.160301E+12 | 0.767070E+11 |
October | 0.206354E+12 | 0.911557E+10 | 0.00 | 0.193899E+12 | 0.919819E+10 |
November | 0.110161E+12 | 0.120090E+11 | 0.00 | 0.155611E+12 | 0.483003E+10 |
December | 0.125947E+12 | 0.191914E+11 | 0.00 | 0.142848E+12 | 0.111379E+11 |
Annual Sum or Average | 0.356450E+13 | 0.115705E+12 | 0.00 | 0.164505E+13 | 0.697431E+12 |
Minimum of Months | 0.110161E+12 | -0.113762E+10 | 0.00 | -0.545283E+10 | 0.405209E+10 |
Maximum of Months | 0.486317E+12 | 0.194031E+11 | 0.00 | 0.201846E+12 | 0.219876E+12 |