Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:35:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1423.82 | 285.78 | 285.78 |
Net Site Energy | 1423.82 | 285.78 | 285.78 |
Total Source Energy | 4070.18 | 816.95 | 816.95 |
Net Source Energy | 4070.18 | 816.95 | 816.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 135.11 | 98.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 35.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 204.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 70.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 111.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1213.04 | 210.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 135.11 | 98.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 35.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 204.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 70.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 111.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 135.11 | 98.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 35.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 204.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 70.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 111.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 51.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 48.28 | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 243.48 | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 51.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 48.28 | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 243.48 | 42.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1213.043 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1213.043 | 100.00 |
Total On-Site and Utility Electric Sources | 1213.043 | 100.00 |
Total Electricity End Uses | 1213.043 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 474.50 |
Time Setpoint Not Met During Occupied Cooling | 63.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2219.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.9322 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.9322 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.9322 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 10-JAN-07:40 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 153761.42 | 59135.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7126.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5531.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8144.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 193319.41 | 67280.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 153761.42 | 59135.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 7126.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5531.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8144.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 427.88 | 107.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 111.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 648.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 160.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 222.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 121.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3841.71 | 228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 85.88 | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 130.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 44.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 771.09 | 45.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 85.88 | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 130.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 44.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 771.09 | 45.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.71 | 0.276717 | 0.282000 | 0.763764 | 0.737912 | 0.500000 | 0.001377 |
CORE_MID VAV BOX COMPONENT | 1.92 | 0.389815 | 0.382000 | 0.734430 | 1.00 | 0.500000 | 0.000977 |
CORE_TOP VAV BOX COMPONENT | 1.98 | 0.379046 | 0.385000 | 0.761228 | 1.00 | 0.500000 | 0.001005 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.535334 | 0.295127 | 0.300000 | 0.160600 | 0.787006 | 0.500000 | 0.001291 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.716340 | 0.139629 | 0.200000 | 0.143268 | 0.372344 | 0.500000 | 0.002729 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.09 | 0.144904 | 0.200000 | 0.218064 | 0.386410 | 0.500000 | 0.002629 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.805185 | 0.124214 | 0.200000 | 0.161037 | 0.331237 | 0.500000 | 0.003067 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.420006 | 0.376165 | 0.383000 | 0.160862 | 1.00 | 0.500000 | 0.001013 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.584384 | 0.171158 | 0.200000 | 0.116877 | 0.456420 | 0.500000 | 0.002226 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.879432 | 0.179652 | 0.200000 | 0.175886 | 0.479072 | 0.500000 | 0.002121 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.665342 | 0.150321 | 0.200000 | 0.133068 | 0.400857 | 0.500000 | 0.002535 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.472104 | 0.334654 | 0.328000 | 0.154850 | 0.892411 | 0.500000 | 0.001138 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.718109 | 0.139285 | 0.200000 | 0.143622 | 0.371427 | 0.500000 | 0.002735 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.01 | 0.156683 | 0.200000 | 0.201670 | 0.417822 | 0.500000 | 0.002432 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.745029 | 0.134243 | 0.200000 | 0.149006 | 0.357982 | 0.500000 | 0.002838 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25237.86 |
CORE_MID VAV BOX REHEAT COIL | 24268.57 |
CORE_TOP VAV BOX REHEAT COIL | 30409.51 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 13137.19 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8612.94 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 13171.29 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 8582.93 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9898.34 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6600.71 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9940.50 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6572.98 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 9759.06 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 6465.47 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 9786.29 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 6437.77 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.63 | 1.35 | 5.26 | 1.42 | 4.60 | 4.60 | 0.300000 | 0.309451 | 4.60 |
PACU_VAV_MID | 2.43 | 1.38 | 4.87 | 1.48 | 4.03 | 4.03 | 0.300000 | 0.366669 | 4.03 |
PACU_VAV_TOP | 2.56 | 1.44 | 5.12 | 2.24 | 4.56 | 4.56 | 0.300000 | 0.490905 | 4.56 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.60 |
PACU_VAV_MID_OA_CONTROLLER | 4.03 |
PACU_VAV_TOP_OA_CONTROLLER | 4.56 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.60 | 76160.40 | 0.800655 | 1.53 | 25384.26 | 0.800655 |
PACU_VAV_MID COOLING COIL | 4.03 | 67136.52 | 0.800296 | 1.34 | 22376.60 | 0.800296 |
PACU_VAV_TOP COOLING COIL | 4.56 | 75426.77 | 0.800655 | 1.52 | 25139.74 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 22649.94 |
PACU_VAV_MID HEATING COIL | 24331.99 |
PACU_VAV_TOP HEATING COIL | 23302.43 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.60 |
PACU_VAV_MID FAN | 4.03 |
PACU_VAV_TOP FAN | 4.56 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 30.766 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8662 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.8508 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9205 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9413 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6010 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29361301E-12 | 0.14012854E-14 | -0.85605344E-13 | 0.14800367E-15 |
43 | 6 | 0.27604353E-07 | 0.24091625E-09 | 0.63325015E-08 | -0.12947724E-12 |
44 | 5 | -0.18467641E-03 | 0.20758097E-05 | -0.95060042E-04 | 0.62631763E-08 |
45 | 4 | 0.28577214 | 0.10163362E-02 | 0.97391765E-01 | -0.32673590E-04 |
46 | 3 | -7.1400386 | 0.31651635E-01 | -2.3014419 | 0.28390242E-01 |
47 | 2 | 40.454589 | 0.11303679 | 15.111294 | -0.32870127 |
48 | 1 | -80.226531 | 0.51206543E-01 | -29.003760 | 1.0718159 |
49 | 0 | 46.824341 | 0.10340301E-02 | 16.294559 | |
50 | 7 | -0.29611882E-12 | 0.13865371E-14 | -0.86632775E-13 | 0.14828224E-15 |
51 | 6 | 0.27787793E-07 | 0.23712375E-09 | 0.63729895E-08 | -0.13045931E-12 |
52 | 5 | -0.18561242E-03 | 0.20406469E-05 | -0.95529752E-04 | 0.63026795E-08 |
53 | 4 | 0.28687424 | 0.99804250E-03 | 0.97787795E-01 | -0.32828381E-04 |
54 | 3 | -7.1618810 | 0.31052249E-01 | -2.3079221 | 0.28497237E-01 |
55 | 2 | 40.526644 | 0.11080299 | 15.137914 | -0.32950368 |
56 | 1 | -80.281767 | 0.50157931E-01 | -29.027638 | 1.0729929 |
57 | 0 | 46.824340 | 0.10121278E-02 | 16.293979 | |
58 | 7 | -0.28014218E-12 | 0.13884632E-14 | -0.87393674E-13 | 0.18804395E-15 |
59 | 6 | 0.23616586E-07 | 0.31618784E-09 | 0.54522364E-08 | -0.10828607E-12 |
60 | 5 | -0.16407885E-03 | 0.28046874E-05 | -0.84685207E-04 | 0.54024401E-08 |
61 | 4 | 0.26115148 | 0.14088028E-02 | 0.88562665E-01 | -0.29253652E-04 |
62 | 3 | -6.6512012 | 0.44876491E-01 | -2.1564742 | 0.25998182E-01 |
63 | 2 | 38.840966 | 0.16346293 | 14.513591 | -0.31073734 |
64 | 1 | -78.988481 | 0.75323239E-01 | -28.467021 | 1.0454353 |
65 | 0 | 46.824349 | 0.15467291E-02 | 16.308047 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3628_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.3628_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.384E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.394E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.384E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.394E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.424E-004 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.424E-004 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.550E-005 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0793E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0853E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2133E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2185E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7928E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.8344E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6395E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6611E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1449 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6997E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1665 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1011 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.8859E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3808E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2271E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5852E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0795E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0865E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2135E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2199E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7944E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.8424E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6393E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6609E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8279E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0417E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.6090E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8388E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5465E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3141E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9184E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3003E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9886E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0134E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7778E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7959E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2748E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.2811E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2478E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2552E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0536E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1069E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3822E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4257E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9107E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9430E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6393E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6609E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9386E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3218E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0512E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7763E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8979E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2218E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2271E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5852E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0533E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.1076E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3815E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4245E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9092E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9373E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6395E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6611E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7442E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4913E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2220E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1308E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7475E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9289E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9184E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3003E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3223E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4001E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9210E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0093E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8052E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8329E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2479E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2553E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1439 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1029 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1628 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1188 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1051 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4479E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7521E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.2047E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.5569E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8901E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.3561E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6978E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.3497E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2076E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8008E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2370E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4363E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9706E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4960E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3347E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3405E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7331E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7521E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2047E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5165E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3668E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0249E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0250E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5800E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8401E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8008E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2371E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1439 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1028 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1628 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1188 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1051 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4473E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7517E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.2044E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.5570E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8899E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3562E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6976E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3495E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2072E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8004E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2368E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4366E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9705E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4962E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3346E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3404E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7329E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7517E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2044E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5167E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3667E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0250E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0248E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5798E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8398E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8005E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2369E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37194.89399 | 37194.89399 | 2.70838 | 2.70838 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5604.75342 | 5604.75342 | 0.23838 | 0.42469 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 26440.81908 | 26440.81908 | 1.92259 | 1.92259 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 11620.52528 | 11620.52528 | 0.49559 | 0.49559 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 26924.18624 | 26924.18624 | 1.97721 | 1.97721 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 26.21800 | 8.40679E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 21446.46816 | 21446.46816 | 0.92027 | 0.92027 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 7289.85715 | 7289.85715 | 0.53533 | 0.53533 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 26.30900 | 8.40693E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 9232.90729 | 9232.90729 | 0.39757 | 0.39757 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 9754.79680 | 9754.79680 | 0.71634 | 0.71634 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 21.91067 | 8.40008E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6052.53029 | 6052.53029 | 0.26065 | 0.26065 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 14847.49379 | 14847.49379 | 1.09032 | 1.09032 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 9256.78906 | 9256.78906 | 0.39860 | 0.39860 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10964.65265 | 10964.65265 | 0.80518 | 0.80518 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6031.50955 | 6031.50955 | 0.25974 | 0.25974 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 5719.36656 | 5719.36656 | 0.42001 | 0.42001 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 6963.16902 | 6963.16902 | 0.29955 | 0.29955 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7957.85808 | 7957.85808 | 0.58438 | 0.58438 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 21.91067 | 8.40008E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4642.62196 | 4642.62196 | 0.19975 | 0.19975 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 11975.64672 | 11975.64672 | 0.87943 | 0.87943 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40000 | 8.40708E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 6992.72549 | 6992.72549 | 0.30083 | 0.30083 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9060.30375 | 9060.30375 | 0.66534 | 0.66534 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.21600 | 8.40365E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4623.18320 | 4623.18320 | 0.19892 | 0.19892 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 6428.82342 | 6428.82342 | 0.47210 | 0.47210 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 6866.30556 | 6866.30556 | 0.29533 | 0.29533 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9778.87426 | 9778.87426 | 0.71811 | 0.71811 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 4548.27589 | 4548.27589 | 0.19566 | 0.19566 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 13731.23061 | 13731.23061 | 1.00835 | 1.00835 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 6885.39219 | 6885.39219 | 0.29616 | 0.29616 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10145.46556 | 10145.46556 | 0.74503 | 0.74503 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 4528.86936 | 4528.86936 | 0.19482 | 0.19482 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 65101.78 | 4.60085 | 4.60085 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 24459.43 | 1.42374 | 1.42374 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 18:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 57439.23 | 4.02969 | 4.02969 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 24459.47 | 1.47757 | 1.47757 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:40:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 64409.61 | 4.55653 | 4.55653 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 24325.17 | 2.23683 | 2.23683 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.70838 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27672 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76376 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73791 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37686E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25237.86421 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.92259 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38981 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.38200 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73443 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.77387E-004 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24268.57062 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.97721 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37905 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.38500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76123 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00516E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 30409.51300 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.53533 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29513 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16060 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78701 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29097E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13137.18797 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71634 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13963 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14327 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37234 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.72866E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8612.94152 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.09032 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14490 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21806 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38641 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.62933E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13171.29005 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80518 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12421 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16104 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33124 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.06729E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8582.92790 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.42001 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37617 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.38300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16086 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01285E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9898.33748 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58438 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17116 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11688 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45642 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.22602E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6600.70760 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87943 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17965 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17589 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47907 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.12077E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9940.50105 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66534 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15032 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13307 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40086 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.53457E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6572.98383 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.47210 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33465 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32800 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15485 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89241 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13849E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9759.06167 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71811 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13928 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14362 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37143 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73540E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6465.47382 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00835 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15668 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20167 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41782 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43166E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9786.28892 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74503 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13424 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14901 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35798 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.83813E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6437.76559 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.62877 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35046 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.25755 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.42374 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.60085 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.60085 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.30945 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.43309 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.38358 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.86619 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.47757 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.02969 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.02969 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.36667 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.56220 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.44420 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.12440 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.23683 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.55653 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.55653 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.49091 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.60085 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.02969 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.55653 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.60085 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.60085 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 76160.40287 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.53346 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 25384.26228 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 22649.93852 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.60085 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.02969 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.02969 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 67136.52408 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80030 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.34310 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 22376.60348 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80030 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 24331.99245 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.02969 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.55653 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.55653 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 75426.77192 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.51869 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 25139.74308 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 23302.43280 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.55653 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 74849.87 | 255398.36 | 11.24 | 2.92 | 3.22 | 3.38 | 3.57 | 9.95 | 10.97 | 11.54 | 12.17 | 5.2649 | 4.1642 | 2.7912 | 1.1626 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 66001.40 | 225206.11 | 12.14 | 3.16 | 3.47 | 3.65 | 3.86 | 10.79 | 11.85 | 12.45 | 13.18 | 4.6113 | 3.6479 | 2.4448 | 1.0167 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 74128.86 | 252938.19 | 11.24 | 2.92 | 3.22 | 3.38 | 3.57 | 9.95 | 10.97 | 11.54 | 12.17 | 5.2141 | 4.1240 | 2.7643 | 1.1514 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.9532446011E-003 | 6.1642404119E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1217963564 | 6.9570912026E-002 | Pass | Pass | 0.1866155883 | 0.3853388542 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.6801164715E-003 | 7.6120000492E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.1744987136E-003 | 6.8256084777E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.5096493738E-003 | 7.3140090442E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.8440431916E-002 | 2.1229997924E-002 | Pass | Pass | 0.2357560851 | 0.5571508264 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1465430001 | 0.1837107961 | Pass | Pass | 0.8485209148 | 3.0166743246 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1334674818 | 0.1455512570 | Pass | Pass | 0.7287306693 | 3.1088099744 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1038468265 | 0.1009266103 | Pass | Pass | 0.7134786755 | 4.1987823771 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1431898025 | 0.1478174000 | Pass | Pass | 0.7047331149 | 3.0098553083 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.3124454610E-002 | 1.1097443395E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.4607721855E-002 | 5.8780257072E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.5523181438E-002 | 7.6324924337E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.1881237702E-002 | 3.9061033253E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.4390801685E-002 | 1.1969829637E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.2961780781E-002 | 6.7498528928E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.2525263153E-002 | 9.3370054675E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.7777589481E-002 | 4.5353963390E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3143.58 | 73.46 | 0.00 | 2375.11 | 208.01 | 5800.18 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3628_SHGC_EAST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3628_SHGC_EAST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3628_SHGC_WEST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3628_SHGC_WEST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.061 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 177.99 | 2.061 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.061 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.73 | 0.0000 | Y | 6.17 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.33 | 0.0000 | Y | 3.85 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.11 | 0.0000 | Y | 6.03 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.46 | 0.0000 | Y | 3.87 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.63 | 0.0000 | Y | 6.15 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.26 | 0.0000 | Y | 3.84 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.06 | 0.0000 | Y | 6.02 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.39 | 0.0000 | Y | 3.86 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.73 | 0.0000 | Y | 6.17 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.33 | 0.0000 | Y | 3.85 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.11 | 0.0000 | Y | 6.03 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.46 | 0.0000 | Y | 3.87 |
Interior Lighting Total | 5.9322 | 4982.19 | 29555.08 | 204.69 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.50 | 42.50 | 3.39 | |
EXTERIOR_LIGHTS_B | 408.47 | AstronomicalClock | - | 83.54 | 63.02 | 4.83 | |
EXTERIOR_LIGHTS_C | 4724.13 | AstronomicalClock | - | 83.54 | 47.95 | 42.52 | |
Exterior Lighting Total | 5557.43 | 50.74 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 76160.40 | 60978.23 | 15182.18 | 0.80 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 67136.52 | 53729.10 | 13407.42 | 0.80 | 3.92 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 75426.77 | 60390.84 | 15035.93 | 0.80 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 74849.9 | 2.92 | 9.95 | N/A | N/A | 11.24 | |
PACU_VAV_MID COOLING COIL | 66001.4 | 3.16 | 10.79 | N/A | N/A | 12.14 | |
PACU_VAV_TOP COOLING COIL | 74128.9 | 2.92 | 9.95 | N/A | N/A | 11.24 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25237.86 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24268.57 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 30409.51 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13137.19 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8612.94 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13171.29 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8582.93 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9898.34 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6600.71 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9940.50 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6572.98 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9759.06 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6465.47 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9786.29 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6437.77 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 22649.94 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 24331.99 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 23302.43 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.60 | 10071.31 | 2189.01 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.03 | 9322.24 | 2313.39 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.56 | 9974.30 | 2189.01 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 74849.87 | 2.92 | 9.95 | 11.24 | 5.2649 | 3.22 | 10.97 | 4.1642 | 3.38 | 11.54 | 2.7912 | 3.57 | 12.17 | 1.1626 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 66001.40 | 3.16 | 10.79 | 12.14 | 4.6113 | 3.47 | 11.85 | 3.6479 | 3.65 | 12.45 | 2.4448 | 3.86 | 13.18 | 1.0167 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 74128.86 | 2.92 | 9.95 | 11.24 | 5.2141 | 3.22 | 10.97 | 4.1240 | 3.38 | 11.54 | 2.7643 | 3.57 | 12.17 | 1.1514 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37194.89 | 37194.89 | 37.82 | 2.708 | 2.708 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 19.67 | 0.00840 | 0.425 | 0.00 |
CORE_MID | 26440.82 | 26440.82 | 26.88 | 1.923 | 1.923 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 19.67 | 0.00840 | 0.425 | 0.00 |
CORE_TOP | 26924.19 | 26924.19 | 27.37 | 1.977 | 1.977 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00895 | 26.22 | 0.00841 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 7289.86 | 7289.86 | 35.16 | 0.535 | 0.535 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00884 | 26.31 | 0.00841 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 9754.80 | 9754.80 | 74.32 | 0.716 | 0.716 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00866 | 21.91 | 0.00840 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 14847.49 | 14847.49 | 71.61 | 1.090 | 1.090 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00867 | 26.25 | 0.00841 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10964.65 | 10964.65 | 83.54 | 0.805 | 0.805 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00865 | 24.97 | 0.00840 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 5719.37 | 5719.37 | 27.58 | 0.420 | 0.420 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00894 | 26.40 | 0.00841 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7957.86 | 7957.86 | 60.63 | 0.584 | 0.584 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00870 | 21.91 | 0.00840 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11975.65 | 11975.65 | 57.76 | 0.879 | 0.879 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00871 | 26.40 | 0.00841 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9060.30 | 9060.30 | 69.03 | 0.665 | 0.665 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00867 | 24.22 | 0.00840 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6428.82 | 6428.82 | 31.01 | 0.472 | 0.472 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00889 | 26.40 | 0.00841 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9778.87 | 9778.87 | 74.50 | 0.718 | 0.718 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00866 | 21.39 | 0.00840 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 13731.23 | 13731.23 | 66.23 | 1.008 | 1.008 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00868 | 26.17 | 0.00841 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10145.47 | 10145.47 | 77.30 | 0.745 | 0.745 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00866 | 24.97 | 0.00840 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5604.75 | 5604.75 | 5.70 | 0.238 | 0.425 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
CORE_MID | 11620.53 | 11620.53 | 11.82 | 0.496 | 0.496 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
CORE_TOP | 21446.47 | 21446.47 | 21.81 | 0.920 | 0.920 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9232.91 | 9232.91 | 44.53 | 0.398 | 0.398 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6052.53 | 6052.53 | 46.11 | 0.261 | 0.261 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9256.79 | 9256.79 | 44.65 | 0.399 | 0.399 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6031.51 | 6031.51 | 45.95 | 0.260 | 0.260 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00796 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6963.17 | 6963.17 | 33.58 | 0.300 | 0.300 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4642.62 | 4642.62 | 35.37 | 0.200 | 0.200 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 6992.73 | 6992.73 | 33.73 | 0.301 | 0.301 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4623.18 | 4623.18 | 35.22 | 0.199 | 0.199 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 6866.31 | 6866.31 | 33.12 | 0.295 | 0.295 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 4548.28 | 4548.28 | 34.65 | 0.196 | 0.196 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 6885.39 | 6885.39 | 33.21 | 0.296 | 0.296 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 4528.87 | 4528.87 | 34.50 | 0.195 | 0.195 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.60 | 4.60 | 1.42 | 1.42 | 4.6008 | 1.4237 | 4.6008 | 0.3095 | 0.3000 |
PACU_VAV_MID | 4.03 | 4.03 | 1.48 | 1.48 | 4.0297 | 1.4776 | 4.0297 | 0.3667 | 0.3000 |
PACU_VAV_TOP | 4.56 | 4.56 | 2.24 | 2.24 | 4.5565 | 2.2368 | 4.5565 | 0.4909 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25237.864 | 25237.864 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25237.86 | 14033.53 | 0.424691 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 5604.75 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24268.571 | 24268.571 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24268.57 | 16376.19 | 0.495586 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 11620.53 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 30409.513 | 30409.513 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 30409.51 | 30409.51 | 0.920271 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 21446.47 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 13137.188 | 13137.188 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13137.19 | 13137.19 | 0.397566 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00795558 | 50.8879 | 9232.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8612.942 | 8612.942 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8612.94 | 8612.94 | 0.260650 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00795645 | 50.8934 | 6052.53 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 13171.290 | 13171.290 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13171.29 | 13171.29 | 0.398598 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00795587 | 50.8897 | 9256.79 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 8582.928 | 8582.928 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8582.93 | 8582.93 | 0.259742 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00795611 | 50.8912 | 6031.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9898.337 | 9898.337 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9898.34 | 9898.34 | 0.299550 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00794199 | 50.8021 | 6963.17 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6600.708 | 6600.708 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6600.71 | 6600.71 | 0.199755 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00794542 | 50.8238 | 4642.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9940.501 | 9940.501 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9940.50 | 9940.50 | 0.300825 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00794255 | 50.8057 | 6992.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6572.984 | 6572.984 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6572.98 | 6572.98 | 0.198916 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00794488 | 50.8204 | 4623.18 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 9759.062 | 9759.062 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9759.06 | 9759.06 | 0.295335 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00791599 | 50.6382 | 6866.31 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 6465.474 | 6465.474 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6465.47 | 6465.47 | 0.195662 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00791990 | 50.6628 | 4548.28 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 9786.289 | 9786.289 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9786.29 | 9786.29 | 0.296159 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00791655 | 50.6417 | 6885.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 6437.766 | 6437.766 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6437.77 | 6437.77 | 0.194824 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00791909 | 50.6577 | 4528.87 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 76160.403 | 60978.227 | 4.600850 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 77895.38 | 74854.52 | 4.600850 | 24.62 | 16.68 | 0.00871467 | 11.00 | 11.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 25.9772 | 24.00 | 0.00882265 | 46.9678 | 62634.66 | 0.00 | 78531.60 | 61476.86 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 22649.939 | 22649.939 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 18:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22649.94 | 22649.94 | 1.380255 | -0.91 | -1.16 | 0.00337136 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 86.5905 | 21.00 | 0.00797461 | 51.0077 | 21221.00 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 67136.524 | 53729.104 | 4.029694 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 68712.96 | 65851.25 | 4.029694 | 24.71 | 16.73 | 0.00873117 | 10.90 | 10.90 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 29.6591 | 24.00 | 0.00886790 | 47.2053 | 54851.78 | 0.00 | 69226.77 | 54173.63 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 24331.992 | 24331.992 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24331.99 | 24331.99 | 1.208908 | -4.01 | -4.02 | 0.00271796 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 98.8636 | 21.00 | 0.00796851 | 50.9692 | 26586.97 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 75426.772 | 60390.842 | 4.556531 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 77149.16 | 74122.34 | 4.556531 | 24.63 | 16.68 | 0.00871591 | 11.00 | 11.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 26.2298 | 24.00 | 0.00882599 | 46.9852 | 61931.66 | 0.00 | 77775.13 | 60884.67 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 23302.433 | 23302.433 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23302.43 | 23302.43 | 1.366959 | -1.44 | -1.54 | 0.00332059 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 87.4327 | 19.60 | 0.00792913 | 55.2929 | 29797.68 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25237.864 | 25237.864 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25237.86 | 14033.53 | 1.0000 | 0.50596508 | 0.424691 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25237.86 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.66 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 5604.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24268.571 | 24268.571 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24268.57 | 16376.19 | 1.0000 | 0.59042769 | 0.495586 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24268.57 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 11620.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 30409.513 | 30409.513 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 30409.51 | 30409.51 | 1.0000 | 1.09638529 | 0.920271 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30409.51 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 21446.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13137.188 | 13137.188 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13137.19 | 13137.19 | 1.0000 | 0.47364848 | 0.397566 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13137.19 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00795558 | 21.00 | 0.00795558 | 50.8879 | 9232.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8612.942 | 8612.942 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8612.94 | 8612.94 | 1.0000 | 0.31053120 | 0.260650 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8612.94 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00795645 | 21.00 | 0.00795645 | 50.8934 | 6052.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13171.290 | 13171.290 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13171.29 | 13171.29 | 1.0000 | 0.47487800 | 0.398598 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13171.29 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00795587 | 21.00 | 0.00795587 | 50.8897 | 9256.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8582.928 | 8582.928 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8582.93 | 8582.93 | 1.0000 | 0.30944908 | 0.259742 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8582.93 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00795611 | 21.00 | 0.00795611 | 50.8912 | 6031.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9898.337 | 9898.337 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9898.34 | 9898.34 | 1.0000 | 0.35687489 | 0.299550 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9898.34 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00794199 | 21.00 | 0.00794199 | 50.8021 | 6963.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6600.708 | 6600.708 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6600.71 | 6600.71 | 1.0000 | 0.23798207 | 0.199755 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6600.71 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00794542 | 21.00 | 0.00794542 | 50.8238 | 4642.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9940.501 | 9940.501 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9940.50 | 9940.50 | 1.0000 | 0.35839506 | 0.300825 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9940.50 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00794255 | 21.00 | 0.00794255 | 50.8057 | 6992.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6572.984 | 6572.984 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6572.98 | 6572.98 | 1.0000 | 0.23698251 | 0.198916 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6572.98 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00794488 | 21.00 | 0.00794488 | 50.8204 | 4623.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9759.062 | 9759.062 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9759.06 | 9759.06 | 1.0000 | 0.35185344 | 0.295335 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9759.06 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00791599 | 21.00 | 0.00791599 | 50.6382 | 6866.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6465.474 | 6465.474 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6465.47 | 6465.47 | 1.0000 | 0.23310634 | 0.195662 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6465.47 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00791990 | 21.00 | 0.00791990 | 50.6628 | 4548.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9786.289 | 9786.289 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9786.29 | 9786.29 | 1.0000 | 0.35283509 | 0.296159 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9786.29 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00791655 | 21.00 | 0.00791655 | 50.6417 | 6885.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6437.766 | 6437.766 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6437.77 | 6437.77 | 1.0000 | 0.23210735 | 0.194824 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6437.77 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00791909 | 21.00 | 0.00791909 | 50.6577 | 4528.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 76160.403 | 60978.227 | 4.600850 | -999.0 | -999.000 | -999.0000 | 1.00905 | 1.00000 | 1021.0401 | 1004.8586 | 1.1914 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.600850 | 5.48132384 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 77895.38 | 74854.52 | 1.0228 | 5.48132384 | 4.600850 | 24.62 | 16.68 | 0.00871467 | 46935.7 | 11.00 | 11.00 | 0.00850000 | 32485.5 | -999.0 | -999.00 | -999.00 | -999.00 | 10071.311 | 67824.07 | 26.40 | 0.00840708 | 17.04 | 1.19517000 | 25.9772 | 24.00 | 0.00882265 | 24.00 | 0.00882265 | 46.9678 | 62634.66 | 0.00 | 78531.60 | 61476.86 | 5.26485299 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.43 | 0.00991458 | 40406.2 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22649.939 | 22649.939 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.600850 | 5.48132384 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 18:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22649.94 | 22649.94 | 1.0000 | 1.64439715 | 1.380255 | -0.91 | -1.16 | 0.00337136 | 7514.1 | 12.80 | 11.50 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22649.94 | -4.30 | 0.00265759 | -4.30 | 1.19517000 | 86.5905 | 21.00 | 0.00798048 | 21.00 | 0.00797461 | 51.0077 | 21221.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 67136.524 | 53729.104 | 4.029694 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0708 | 1004.8586 | 1.1914 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.029694 | 4.80086428 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 68712.96 | 65851.25 | 1.0235 | 4.80086428 | 4.029694 | 24.71 | 16.73 | 0.00873117 | 47068.1 | 10.90 | 10.90 | 0.00850000 | 32381.2 | -999.0 | -999.00 | -999.00 | -999.00 | 9322.239 | 59390.72 | 26.40 | 0.00840708 | 17.04 | 1.19517000 | 29.6591 | 24.00 | 0.00886790 | 24.00 | 0.00886790 | 47.2053 | 54851.78 | 0.00 | 69226.77 | 54173.63 | 4.61126644 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.19 | 14.39 | 0.00990475 | 40309.9 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24331.992 | 24331.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.029694 | 4.80086428 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 12:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24331.99 | 24331.99 | 1.0000 | 1.44025928 | 1.208908 | -4.01 | -4.02 | 0.00271796 | 2745.3 | 12.80 | 11.50 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24331.99 | -4.30 | 0.00265759 | -4.30 | 1.19517000 | 98.8636 | 21.00 | 0.00796967 | 21.00 | 0.00796851 | 50.9692 | 26586.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 75426.772 | 60390.842 | 4.556531 | -999.0 | -999.000 | -999.0000 | 1.00840 | 1.00000 | 1021.0424 | 1004.8586 | 1.1914 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.556531 | 5.42852385 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | Sensible | 77149.16 | 74122.34 | 1.0228 | 5.42852385 | 4.556531 | 24.63 | 16.68 | 0.00871591 | 46946.1 | 11.00 | 11.00 | 0.00850000 | 32485.5 | -999.0 | -999.00 | -999.00 | -999.00 | 9974.297 | 67174.86 | 26.40 | 0.00840708 | 17.04 | 1.19517000 | 26.2298 | 24.00 | 0.00882599 | 24.00 | 0.00882599 | 46.9852 | 61931.66 | 0.00 | 77775.13 | 60884.67 | 5.21413819 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.26 | 14.43 | 0.00991458 | 40406.2 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 23302.433 | 23302.433 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.556531 | 5.42852385 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23302.43 | 23302.43 | 1.0000 | 1.62855715 | 1.366959 | -1.44 | -1.54 | 0.00332059 | 6849.3 | 12.80 | 11.50 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23302.43 | -4.30 | 0.00265759 | -4.30 | 1.19517000 | 87.4327 | 18.46 | 0.00793323 | 19.60 | 0.00792913 | 55.2929 | 29797.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.60 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.03 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.56 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1382.17 | 2925.17 | 18.33 |
CORE_MID | 786.67 | 4071.33 | 185.17 |
CORE_TOP | 1405.33 | 4613.33 | 934.33 |
PERIMETER_TOP_ZN_3 | 2372.67 | 4833.33 | 1875.33 |
PERIMETER_TOP_ZN_2 | 2790.33 | 4292.00 | 1728.50 |
PERIMETER_TOP_ZN_1 | 2603.50 | 4291.00 | 1524.50 |
PERIMETER_TOP_ZN_4 | 2681.00 | 4679.17 | 1840.50 |
PERIMETER_BOT_ZN_3 | 1633.33 | 5060.50 | 1396.50 |
PERIMETER_BOT_ZN_2 | 2291.67 | 4036.00 | 1203.83 |
PERIMETER_BOT_ZN_1 | 2183.33 | 4602.50 | 1374.83 |
PERIMETER_BOT_ZN_4 | 2221.33 | 4386.33 | 1292.33 |
PERIMETER_MID_ZN_3 | 1764.83 | 4541.17 | 1231.67 |
PERIMETER_MID_ZN_2 | 1948.67 | 3600.83 | 1100.50 |
PERIMETER_MID_ZN_1 | 2096.00 | 3968.33 | 897.67 |
PERIMETER_MID_ZN_4 | 2193.50 | 4405.00 | 1215.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4246.83 | 5358.33 | 2219.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.17 | 0.00 |
CORE_TOP | 1.00 | 0.00 | 0.83 | 0.00 |
PERIMETER_TOP_ZN_3 | 14.17 | 0.00 | 10.50 | 0.00 |
PERIMETER_TOP_ZN_2 | 3.83 | 8.00 | 0.50 | 8.00 |
PERIMETER_TOP_ZN_1 | 1.83 | 12.67 | 0.33 | 12.67 |
PERIMETER_TOP_ZN_4 | 3.83 | 16.67 | 0.50 | 9.33 |
PERIMETER_BOT_ZN_3 | 2.50 | 0.00 | 2.33 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 3.33 | 0.00 | 3.33 |
PERIMETER_BOT_ZN_1 | 467.00 | 6.50 | 467.00 | 6.50 |
PERIMETER_BOT_ZN_4 | 0.17 | 8.50 | 0.00 | 3.67 |
PERIMETER_MID_ZN_3 | 1.67 | 0.00 | 1.50 | 0.00 |
PERIMETER_MID_ZN_2 | 0.67 | 10.83 | 0.50 | 10.83 |
PERIMETER_MID_ZN_1 | 0.00 | 14.00 | 0.00 | 14.00 |
PERIMETER_MID_ZN_4 | 0.50 | 15.00 | 0.33 | 8.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 479.33 | 78.50 | 474.50 | 63.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.52 | 52.94 | 2698.04 | 0.906 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.52 | 52.94 | 2698.04 | 0.648 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.52 | 52.94 | 2698.04 | 0.630 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.54 | 11.16 | 568.77 | 0.664 | 0.012 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 1.109 | 0.013 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.54 | 11.16 | 568.77 | 1.167 | 0.012 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 1.190 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.54 | 11.16 | 568.77 | 0.614 | 0.006 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.949 | 0.007 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.54 | 11.16 | 568.77 | 0.872 | 1.293 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.978 | 0.007 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.54 | 11.16 | 568.77 | 0.674 | 0.010 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 1.044 | 0.011 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.54 | 11.16 | 568.77 | 1.162 | 0.010 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 1.160 | 0.011 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.52 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.87 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.51 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.54 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.87 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.52 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.87 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.51 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.54 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.87 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 108.66 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 14346843.37 | 0.00 | 14346843.37 | 0.00 | 14346843.37 | 13393058.27 | 5356.46 | 123.35 | 3280.19 | 38.92 |
CORE_MID | 10292932.62 | 0.00 | 10292932.62 | 0.00 | 10292932.62 | 13393058.27 | 6175.04 | 53.25 | 2531.71 | 36.56 |
CORE_TOP | 10039909.65 | 0.00 | 10039909.65 | 0.00 | 10039909.65 | 13393058.27 | 6223.49 | 51.59 | 2484.92 | 61.69 |
PERIMETER_TOP_ZN_3 | 2231463.52 | 0.00 | 2231463.52 | 81865.87 | 2313329.39 | 2823374.22 | 6145.66 | 55.56 | 2558.78 | 61.69 |
PERIMETER_TOP_ZN_2 | 2352335.23 | 0.00 | 2352335.23 | 54576.92 | 2406912.15 | 1787429.43 | 4122.43 | 2.53 | 4635.04 | 61.69 |
PERIMETER_TOP_ZN_1 | 3907875.91 | 0.00 | 3907875.91 | 81865.87 | 3989741.78 | 2823374.22 | 4128.22 | 2.81 | 4628.97 | 61.69 |
PERIMETER_TOP_ZN_4 | 2533698.79 | 0.00 | 2533698.79 | 54576.92 | 2588275.71 | 1787312.18 | 4109.72 | 4.27 | 4646.00 | 61.69 |
PERIMETER_BOT_ZN_3 | 2062897.69 | 0.00 | 2062897.69 | 43527.62 | 2106425.31 | 2823374.22 | 5920.75 | 120.64 | 2718.61 | 38.92 |
PERIMETER_BOT_ZN_2 | 2010542.06 | 0.00 | 2010542.06 | 29018.24 | 2039560.30 | 1787429.43 | 4159.71 | 42.59 | 4557.70 | 38.92 |
PERIMETER_BOT_ZN_1 | 2930968.98 | 0.00 | 2930968.98 | 4367211.55 | 7298180.54 | 2823374.22 | 4202.00 | 71.83 | 4486.17 | 38.92 |
PERIMETER_BOT_ZN_4 | 2077469.44 | 0.00 | 2077469.44 | 29018.24 | 2106487.68 | 1787312.18 | 4092.76 | 5.50 | 4661.74 | 38.92 |
PERIMETER_MID_ZN_3 | 2259468.83 | 0.00 | 2259468.83 | 68147.03 | 2327615.86 | 2823374.22 | 6145.95 | 56.48 | 2557.57 | 36.56 |
PERIMETER_MID_ZN_2 | 2423235.94 | 0.00 | 2423235.94 | 45431.08 | 2468667.02 | 1787429.43 | 4051.04 | 4.24 | 4704.72 | 945.56 |
PERIMETER_MID_ZN_1 | 3883787.51 | 0.00 | 3883787.51 | 68147.03 | 3951934.54 | 2823374.22 | 4083.64 | 6.61 | 4669.75 | 36.56 |
PERIMETER_MID_ZN_4 | 2464933.73 | 0.00 | 2464933.73 | 45431.08 | 2510364.81 | 1787312.18 | 4043.99 | 2.64 | 4713.37 | 36.56 |
Total Facility | 65818363.27 | 0.00 | 65818363.27 | 4968817.45 | 70787180.72 | 67843644.98 | 6377.48 | 412.67 | 4780.99 | 995.41 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6660 | 0.0000 | 0.6660 | 0.0000 | 0.6660 | 0.4247 | 2577.37 | 123.19 | 3242.44 |
CORE_MID | 0.4771 | 0.0000 | 0.4771 | 0.0000 | 0.4771 | 0.4247 | 3392.60 | 53.25 | 2497.15 |
CORE_TOP | 0.4647 | 0.0000 | 0.4647 | 0.0000 | 0.4647 | 0.4247 | 3442.88 | 51.59 | 2448.53 |
PERIMETER_TOP_ZN_3 | 0.1033 | 0.0000 | 0.1033 | 0.0019 | 0.1052 | 0.0895 | 3365.05 | 55.56 | 2522.39 |
PERIMETER_TOP_ZN_2 | 0.1091 | 0.0000 | 0.1091 | 0.0013 | 0.1103 | 0.0567 | 1341.82 | 2.53 | 4598.65 |
PERIMETER_TOP_ZN_1 | 0.1813 | 0.0000 | 0.1813 | 0.0019 | 0.1832 | 0.0895 | 1347.61 | 2.81 | 4592.58 |
PERIMETER_TOP_ZN_4 | 0.1172 | 0.0000 | 0.1172 | 0.0013 | 0.1184 | 0.0567 | 1329.11 | 4.27 | 4609.62 |
PERIMETER_BOT_ZN_3 | 0.0955 | 0.0000 | 0.0955 | 0.0010 | 0.0965 | 0.0895 | 3141.66 | 120.47 | 2680.86 |
PERIMETER_BOT_ZN_2 | 0.0933 | 0.0000 | 0.0933 | 0.0007 | 0.0940 | 0.0567 | 1380.80 | 42.59 | 4519.62 |
PERIMETER_BOT_ZN_1 | 0.1360 | 0.0000 | 0.1360 | 0.2031 | 0.3391 | 0.0895 | 1423.08 | 71.83 | 4448.09 |
PERIMETER_BOT_ZN_4 | 0.0962 | 0.0000 | 0.0962 | 0.0007 | 0.0969 | 0.0567 | 1313.84 | 5.50 | 4623.66 |
PERIMETER_MID_ZN_3 | 0.1048 | 0.0000 | 0.1048 | 0.0016 | 0.1063 | 0.0895 | 3363.51 | 56.48 | 2523.01 |
PERIMETER_MID_ZN_2 | 0.1027 | 0.0000 | 0.1027 | 0.0011 | 0.1038 | 0.0567 | 1268.60 | 4.24 | 3761.16 |
PERIMETER_MID_ZN_1 | 0.1804 | 0.0000 | 0.1804 | 0.0016 | 0.1820 | 0.0895 | 1301.20 | 6.61 | 4635.19 |
PERIMETER_MID_ZN_4 | 0.1141 | 0.0000 | 0.1141 | 0.0011 | 0.1152 | 0.0567 | 1261.54 | 2.64 | 4678.82 |
Total Facility | 3.0417 | 0.0000 | 3.0417 | 0.2171 | 3.2588 | 2.1513 | 3572.78 | 412.51 | 4721.49 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 33253954.60 | 0.00 | 33253954.60 | 22614548.33 | 4056.60 | 4.55 | 4698.85 | 38.92 |
PACU_VAV_MID | 30267132.43 | 0.00 | 30267132.43 | 22614548.33 | 4035.72 | 4.11 | 4720.17 | 36.56 |
PACU_VAV_TOP | 29899380.84 | 0.00 | 29899380.84 | 22614548.33 | 4110.18 | 4.62 | 4645.20 | 61.61 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.5429 | 0.0000 | 1.5429 | 0.7171 | 1277.69 | 4.55 | 4660.76 |
PACU_VAV_MID | 1.4036 | 0.0000 | 1.4036 | 0.7171 | 1253.28 | 4.11 | 4685.62 |
PACU_VAV_TOP | 1.3847 | 0.0000 | 1.3847 | 0.7171 | 1329.57 | 4.62 | 4608.81 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 3283.12 | 0.00 | 0.00 | 0.00 | 1501.56 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2919.94 | 0.00 | 0.00 | 0.00 | 1904.48 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2902.15 | 0.00 | 0.00 | 0.00 | 1932.44 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.3255 | 0.0000 | 0.0000 | 0.0000 | 1.0829 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.1711 | 0.0000 | 0.0000 | 0.0000 | 1.0937 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.1555 | 0.0000 | 0.0000 | 0.0000 | 1.0909 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 825 |
Defaulted Fields | 545 |
Fields with Defaults | 2230 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1213.04 | 12344.18 | 16-APR-17:10 | 193319.41 | 02-JAN-07:10 |
Electricity:Building | 910.13 | 12175.61 | 16-APR-17:10 | 67242.49 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 284.50 | 4029.56 | 01-JAN-00:10 | 22405.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 910.13 | 12175.61 | 16-APR-17:10 | 67242.49 | 02-JAN-08:10 |
InteriorLights:Electricity | 204.69 | 934.27 | 01-JAN-11:00 | 21377.78 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 204.69 | 934.27 | 01-JAN-11:00 | 21377.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 204.69 | 934.27 | 01-JAN-11:00 | 21377.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 204.69 | 934.27 | 01-JAN-11:00 | 21377.78 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.50 | 409.68 | 02-APR-17:10 | 2324.90 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.17 | 23.57 | 01-JAN-11:00 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.17 | 23.57 | 01-JAN-11:00 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.25 | 259.34 | 16-APR-17:10 | 1471.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.85 | 14.92 | 01-JAN-08:50 | 563.23 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.85 | 14.92 | 01-JAN-08:50 | 563.23 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.36 | 409.67 | 02-APR-17:10 | 2324.89 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.03 | 23.57 | 01-JAN-08:50 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.03 | 23.57 | 01-JAN-08:50 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.27 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.87 | 14.92 | 01-JAN-10:30 | 563.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.87 | 14.92 | 01-JAN-10:30 | 563.19 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.48 | 409.68 | 02-APR-17:10 | 2324.90 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.15 | 23.57 | 01-JAN-10:40 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.15 | 23.57 | 01-JAN-10:40 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.24 | 259.34 | 16-APR-17:10 | 1471.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.84 | 14.92 | 01-JAN-08:50 | 563.23 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.84 | 14.92 | 01-JAN-08:50 | 563.23 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.35 | 409.67 | 02-APR-17:10 | 2324.89 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.02 | 23.57 | 01-JAN-08:50 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.02 | 23.57 | 01-JAN-08:50 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.26 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.86 | 14.92 | 01-JAN-10:30 | 563.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.86 | 14.92 | 01-JAN-10:30 | 563.19 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.50 | 409.68 | 02-APR-17:10 | 2324.90 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.17 | 23.57 | 01-JAN-11:00 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.17 | 23.57 | 01-JAN-11:00 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.25 | 259.34 | 16-APR-17:10 | 1471.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.85 | 14.92 | 01-JAN-08:50 | 563.23 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.85 | 14.92 | 01-JAN-08:50 | 563.23 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.36 | 409.67 | 02-APR-17:10 | 2324.89 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.03 | 23.57 | 01-JAN-08:50 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.03 | 23.57 | 01-JAN-08:50 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.27 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.87 | 14.92 | 01-JAN-10:30 | 563.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.87 | 14.92 | 01-JAN-10:30 | 563.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 252.16 | 168.57 | 22-JUL-18:20 | 159536.42 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 835.33 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 835.33 | 02-JAN-08:20 |
ElectricityPurchased:Facility | 1213.04 | 12344.18 | 16-APR-17:10 | 193319.41 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1213.04 | 12344.18 | 16-APR-17:10 | 193319.41 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1213.04 | 12344.18 | 16-APR-17:10 | 193319.41 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1213.04 | 12344.18 | 16-APR-17:10 | 193319.41 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1213.04 | 12344.18 | 16-APR-17:10 | 193319.41 | 02-JAN-07:10 |
ElectricityNet:Plant | 1213.04 | 12344.18 | 16-APR-17:10 | 193319.41 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1213.04 | 12344.18 | 16-APR-17:10 | 193319.41 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1213.04 | 12344.18 | 16-APR-17:10 | 193319.41 | 02-JAN-07:10 |
Heating:Electricity | 135.11 | 0.00 | 01-JAN-00:40 | 153761.42 | 02-JAN-07:10 |
General:Heating:Electricity | 135.11 | 0.00 | 01-JAN-00:40 | 153761.42 | 02-JAN-07:10 |
Fans:Electricity | 70.28 | 0.00 | 01-JAN-00:40 | 20533.14 | 13-JUN-15:30 |
General:Fans:Electricity | 70.28 | 0.00 | 01-JAN-00:40 | 20533.14 | 13-JUN-15:30 |
ExteriorLights:Electricity | 50.74 | 0.00 | 01-JAN-08:20 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.74 | 0.00 | 01-JAN-08:20 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 35.12 | 0.00 | 01-JAN-00:10 | 38915.93 | 13-JUN-16:00 |
General:Cooling:Electricity | 35.12 | 0.00 | 01-JAN-00:10 | 38915.93 | 13-JUN-16:00 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 5.75 | 0.00 | 01-JAN-00:10 | 600.72 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 210.77 | 1156.00 | 17-JAN-06:10 | 67280.15 | 10-JAN-07:40 |
NaturalGas:HVAC | 98.87 | 0.00 | 01-JAN-00:40 | 61168.50 | 10-JAN-08:00 |
Heating:NaturalGas | 98.87 | 0.00 | 01-JAN-00:40 | 61168.50 | 10-JAN-08:00 |
General:Heating:NaturalGas | 98.87 | 0.00 | 01-JAN-00:40 | 61168.50 | 10-JAN-08:00 |
NaturalGas:Plant | 111.90 | 1156.00 | 03-JAN-18:20 | 9443.92 | 17-FEB-12:10 |
WaterSystems:NaturalGas | 111.90 | 1156.00 | 03-JAN-18:20 | 9443.92 | 17-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 111.90 | 1156.00 | 03-JAN-18:20 | 9443.92 | 17-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1276.71 | 0.00 | 01-JAN-00:40 | 315021.32 | 02-JAN-07:10 |
EnergyTransfer:Building | 856.80 | 0.00 | 01-JAN-00:40 | 135353.67 | 02-JAN-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 190.34 | 0.00 | 01-JAN-00:10 | 22960.25 | 24-JUL-08:00 |
Heating:EnergyTransfer | 96.16 | 0.00 | 01-JAN-00:40 | 135070.52 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.02 | 0.00 | 01-JAN-00:10 | 5773.61 | 02-JAN-07:10 |
General:Heating:EnergyTransfer | 96.16 | 0.00 | 01-JAN-00:40 | 135070.52 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.02 | 0.00 | 01-JAN-00:10 | 5773.61 | 02-JAN-07:10 |
Cooling:EnergyTransfer | 760.64 | 0.00 | 01-JAN-00:40 | 133219.54 | 13-JUN-15:40 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 190.32 | 0.00 | 01-JAN-00:10 | 22960.25 | 24-JUL-08:00 |
General:Cooling:EnergyTransfer | 760.64 | 0.00 | 01-JAN-00:40 | 133219.54 | 13-JUN-15:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 190.32 | 0.00 | 01-JAN-00:10 | 22960.25 | 24-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.97 | 0.00 | 01-JAN-00:40 | 9237.47 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.38 | 0.00 | 01-JAN-00:40 | 9237.47 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.38 | 0.00 | 01-JAN-00:40 | 9237.47 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.59 | 0.00 | 01-JAN-00:10 | 8527.63 | 13-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 17.59 | 0.00 | 01-JAN-00:10 | 8527.63 | 13-JUN-14:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.90 | 0.00 | 01-JAN-00:10 | 6510.65 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.70 | 0.00 | 01-JAN-00:10 | 6510.65 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 7.70 | 0.00 | 01-JAN-00:10 | 6510.65 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.21 | 0.00 | 01-JAN-00:10 | 3397.57 | 24-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.21 | 0.00 | 01-JAN-00:10 | 3397.57 | 24-JUL-15:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.64 | 0.00 | 01-JAN-00:10 | 4027.20 | 02-JAN-08:40 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.63 | 0.00 | 01-JAN-00:10 | 4027.20 | 02-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 5.63 | 0.00 | 01-JAN-00:10 | 4027.20 | 02-JAN-08:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.01 | 0.00 | 01-JAN-00:10 | 3677.46 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 13.01 | 0.00 | 01-JAN-00:10 | 3677.46 | 24-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 124.33 | 0.00 | 01-JAN-00:10 | 16770.81 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.39 | 0.00 | 01-JAN-00:10 | 16770.81 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.39 | 0.00 | 01-JAN-00:10 | 16770.81 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 123.94 | 0.00 | 01-JAN-00:10 | 15330.35 | 24-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 123.94 | 0.00 | 01-JAN-00:10 | 15330.35 | 24-JUL-16:00 |
EnergyTransfer:Zone:CORE_TOP | 113.12 | 0.00 | 01-JAN-00:40 | 24443.59 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.56 | 0.00 | 01-JAN-00:10 | 24443.59 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.56 | 0.00 | 01-JAN-00:10 | 24443.59 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 109.56 | 0.00 | 01-JAN-00:40 | 16766.19 | 24-JUL-15:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 109.56 | 0.00 | 01-JAN-00:40 | 16766.19 | 24-JUL-15:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 27.12 | 0.00 | 01-JAN-00:40 | 6947.34 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.84 | 0.00 | 01-JAN-00:40 | 6947.34 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.84 | 0.00 | 01-JAN-00:40 | 6947.34 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.28 | 0.00 | 01-JAN-00:20 | 5132.70 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 19.28 | 0.00 | 01-JAN-00:20 | 5132.70 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 26.77 | 0.00 | 01-JAN-00:40 | 7563.40 | 13-JUN-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.48 | 0.00 | 01-JAN-00:40 | 6176.63 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.48 | 0.00 | 01-JAN-00:40 | 6176.63 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.28 | 0.00 | 01-JAN-00:20 | 7563.40 | 13-JUN-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.28 | 0.00 | 01-JAN-00:20 | 7563.40 | 13-JUN-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 44.95 | 0.00 | 01-JAN-00:40 | 11954.15 | 11-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.70 | 0.00 | 01-JAN-00:40 | 8909.79 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.70 | 0.00 | 01-JAN-00:40 | 8909.79 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.25 | 0.00 | 01-JAN-00:20 | 11954.15 | 11-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.25 | 0.00 | 01-JAN-00:20 | 11954.15 | 11-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.62 | 0.00 | 01-JAN-00:40 | 8893.41 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.90 | 0.00 | 01-JAN-00:40 | 6161.71 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.90 | 0.00 | 01-JAN-00:40 | 6161.71 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.72 | 0.00 | 01-JAN-00:20 | 8893.41 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.72 | 0.00 | 01-JAN-00:20 | 8893.41 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 21.72 | 0.00 | 01-JAN-00:10 | 5400.81 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.98 | 0.00 | 01-JAN-00:10 | 5400.81 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.98 | 0.00 | 01-JAN-00:10 | 5400.81 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.74 | 0.00 | 01-JAN-00:10 | 3558.61 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 18.74 | 0.00 | 01-JAN-00:10 | 3558.61 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 22.17 | 0.00 | 01-JAN-00:10 | 5764.66 | 13-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.63 | 0.00 | 01-JAN-00:10 | 4541.01 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.63 | 0.00 | 01-JAN-00:10 | 4541.01 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.54 | 0.00 | 01-JAN-00:10 | 5764.66 | 13-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 20.54 | 0.00 | 01-JAN-00:10 | 5764.66 | 13-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 46.60 | 0.00 | 01-JAN-00:10 | 11932.91 | 10-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.00 | 0.00 | 01-JAN-00:10 | 11932.91 | 10-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 25.00 | 0.00 | 01-JAN-00:10 | 11932.91 | 10-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 21.60 | 0.00 | 01-JAN-00:10 | 10224.52 | 21-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 21.60 | 0.00 | 01-JAN-00:10 | 10224.52 | 21-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 22.00 | 0.00 | 01-JAN-00:10 | 6535.45 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.75 | 0.00 | 01-JAN-00:10 | 4577.11 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 1.75 | 0.00 | 01-JAN-00:10 | 4577.11 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.24 | 0.00 | 01-JAN-00:10 | 6535.45 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 20.24 | 0.00 | 01-JAN-00:10 | 6535.45 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.64 | 0.00 | 01-JAN-00:10 | 6006.24 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.47 | 0.00 | 01-JAN-00:10 | 6006.24 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.47 | 0.00 | 01-JAN-00:10 | 6006.24 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 22.18 | 0.00 | 01-JAN-00:10 | 4634.80 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 22.18 | 0.00 | 01-JAN-00:10 | 4634.80 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 25.97 | 0.00 | 01-JAN-00:10 | 7533.87 | 13-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.52 | 0.00 | 01-JAN-00:10 | 4480.54 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.52 | 0.00 | 01-JAN-00:10 | 4480.54 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 24.44 | 0.00 | 01-JAN-00:10 | 7533.87 | 13-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 24.44 | 0.00 | 01-JAN-00:10 | 7533.87 | 13-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 43.92 | 0.00 | 01-JAN-00:10 | 11538.99 | 11-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.64 | 0.00 | 01-JAN-00:10 | 6390.15 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1.64 | 0.00 | 01-JAN-00:10 | 6390.15 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 42.28 | 0.00 | 01-JAN-00:10 | 11538.99 | 11-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 42.28 | 0.00 | 01-JAN-00:10 | 11538.99 | 11-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.03 | 0.00 | 01-JAN-00:10 | 8318.48 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.57 | 0.00 | 01-JAN-00:10 | 4478.02 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.57 | 0.00 | 01-JAN-00:10 | 4478.02 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.46 | 0.00 | 01-JAN-00:10 | 8318.48 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 24.46 | 0.00 | 01-JAN-00:10 | 8318.48 | 13-JUN-17:00 |
PlantLoopHeatingDemand:Facility | 52.59 | 0.00 | 01-JAN-00:10 | 6273.87 | 15-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 52.59 | 0.00 | 01-JAN-00:10 | 6273.87 | 15-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 52.59 | 0.00 | 01-JAN-00:10 | 6273.87 | 15-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 52.59 | 0.00 | 01-JAN-00:10 | 6273.87 | 15-FEB-12:10 |
EnergyTransfer:HVAC | 367.32 | 0.00 | 01-JAN-00:40 | 177611.53 | 02-JAN-07:10 |
HeatingCoils:EnergyTransfer | 214.20 | 0.00 | 01-JAN-00:40 | 177611.53 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 153.12 | 0.00 | 01-JAN-00:10 | 173127.48 | 13-JUN-15:30 |
EnergyTransfer:Plant | 52.59 | 0.00 | 01-JAN-00:10 | 6273.87 | 15-FEB-12:10 |
WaterSystems:EnergyTransfer | 52.59 | 0.00 | 01-JAN-00:10 | 6273.87 | 15-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 52.59 | 0.00 | 01-JAN-00:10 | 6273.87 | 15-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.015 | -190.323 | 0.000 | 0.000 | 33.029 | 48.333 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -127.221 |
CORE_MID | 0.000 | 0.000 | 0.388 | -123.937 | 0.000 | 0.000 | 34.786 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -74.995 |
CORE_TOP | 0.000 | 0.000 | 3.559 | -109.563 | 0.000 | 0.000 | 35.696 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -93.449 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 7.841 | -19.279 | 0.000 | 0.000 | 7.691 | 6.172 | 24.333 | 13.317 | 0.000 | 0.000 | 0.000 | 0.000 | -28.284 | 0.000 | -1.166 | -10.626 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.481 | -22.285 | 0.000 | 0.000 | 4.811 | 3.848 | 15.404 | 28.181 | 0.000 | 0.000 | 0.000 | 0.000 | -18.290 | 0.000 | -0.793 | -15.356 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.698 | -39.248 | 0.000 | 0.000 | 7.555 | 6.029 | 24.332 | 56.269 | 0.000 | 0.000 | 0.001 | 0.000 | -28.315 | 0.000 | -1.214 | -31.105 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.904 | -22.717 | 0.000 | 0.000 | 4.894 | 3.868 | 15.403 | 27.605 | 0.000 | 0.000 | 0.000 | 0.000 | -19.015 | 0.000 | -0.795 | -14.148 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.984 | -18.741 | 0.000 | 0.000 | 7.656 | 6.149 | 24.333 | 13.505 | 0.000 | 0.000 | 0.003 | 0.000 | -29.551 | 0.000 | -0.648 | -5.686 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.635 | -20.537 | 0.000 | 0.000 | 4.762 | 3.839 | 15.404 | 28.180 | 0.000 | 0.000 | 0.000 | 0.000 | -19.400 | 0.000 | -0.449 | -13.434 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 24.997 | -21.598 | 0.000 | 0.000 | 7.814 | 6.016 | 24.332 | 56.898 | 0.000 | 0.067 | 0.001 | 0.000 | -29.619 | 0.000 | -53.431 | -15.476 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 1.755 | -20.244 | 0.000 | 0.000 | 4.823 | 3.857 | 15.403 | 27.660 | 0.000 | 0.000 | 0.000 | 0.000 | -20.140 | 0.000 | -0.450 | -12.664 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.465 | -22.177 | 0.000 | 0.000 | 7.570 | 6.172 | 24.333 | 12.923 | 0.000 | 0.000 | 0.000 | 0.000 | -30.158 | 0.000 | -1.032 | -0.096 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.525 | -24.442 | 0.000 | 0.000 | 3.530 | 3.848 | 15.404 | 27.925 | 0.000 | 0.000 | 0.000 | 0.000 | -19.404 | 0.000 | -0.697 | -7.689 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 1.638 | -42.280 | 0.000 | 0.000 | 7.429 | 6.029 | 24.332 | 55.854 | 0.000 | 0.000 | 0.000 | 0.000 | -30.112 | 0.000 | -1.071 | -21.819 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.567 | -24.465 | 0.000 | 0.000 | 4.817 | 3.868 | 15.403 | 27.360 | 0.000 | 0.000 | 0.001 | 0.000 | -20.234 | 0.000 | -0.702 | -7.615 |
TOPFLOOR_PLENUM | 17.380 | -17.593 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.011 | 0.000 | 0.000 | 0.000 | -1.799 | -0.001 |
MIDFLOOR_PLENUM | 7.697 | -8.205 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 2.276 | 0.000 | 0.000 | 0.000 | -1.768 | -0.000 |
FIRSTFLOOR_PLENUM | 5.633 | -13.006 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.800 | 0.000 | 0.000 | 0.000 | -1.428 | -0.001 |
Total Facility | 30.709 | -38.803 | 65.450 | -721.836 | 0.000 | 0.000 | 176.860 | 204.694 | 705.434 | 375.678 | 0.000 | 0.072 | 13.095 | 0.000 | -292.521 | 0.000 | -67.445 | -451.383 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 29-AUG-05:02 | 0.00 | 0.00 | 0.00 | -39627.23 | 0.00 | 0.00 | 314.81 | 468.92 | 4989.51 | 0.00 | 0.00 | 0.00 | 33854.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | -25236.83 | 0.00 | 0.00 | 329.36 | 468.92 | 3025.92 | 0.00 | 0.00 | 0.00 | 21412.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-05:03 | 0.00 | 0.00 | 0.00 | -20906.19 | 0.00 | 0.00 | 329.40 | 468.92 | 3025.92 | 0.00 | 0.00 | 0.00 | 17081.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -5132.47 | 0.00 | 0.00 | 737.23 | 424.37 | 1435.25 | 2514.74 | 0.00 | 5.64 | 15.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 30-APR-09:22 | 0.00 | 0.00 | 0.00 | -12476.34 | 0.00 | 0.00 | 15.85 | 14.92 | 302.86 | 8866.70 | 0.00 | 0.00 | 3324.63 | 0.00 | -0.00 | 0.00 | -48.63 | 0.00 |
PERIMETER_TOP_ZN_1 | 30-APR-13:22 | 0.00 | 0.00 | 0.00 | -20198.98 | 0.00 | 0.00 | 22.65 | 23.57 | 478.41 | 13377.80 | 0.00 | 0.00 | 6330.53 | 0.00 | -0.00 | 0.00 | -33.98 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-JUN-16:42 | 0.00 | 0.00 | 0.00 | -14823.30 | 0.00 | 0.00 | 14.03 | 14.92 | 302.86 | 9773.08 | 0.00 | 0.00 | 4738.26 | 0.00 | -0.00 | 0.00 | -19.85 | 0.00 |
PERIMETER_BOT_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -3558.59 | 0.00 | 0.00 | 737.23 | 424.37 | 1435.25 | 2568.27 | 0.00 | 3.06 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1609.57 |
PERIMETER_BOT_ZN_2 | 16-JUL-10:02 | 0.00 | 0.00 | 0.00 | -8065.12 | 0.00 | 0.00 | 17.35 | 14.92 | 302.86 | 6664.21 | 0.00 | 0.00 | 1099.73 | 0.00 | -0.00 | 0.00 | -33.96 | 0.00 |
PERIMETER_BOT_ZN_1 | 24-SEP-13:22 | 0.00 | 0.00 | 0.00 | -15151.95 | 0.00 | 0.00 | 26.71 | 23.57 | 478.41 | 13458.63 | 0.00 | 0.00 | 1191.42 | 0.00 | -0.00 | 0.00 | -26.80 | 0.00 |
PERIMETER_BOT_ZN_4 | 25-JUN-17:11 | 0.00 | 0.00 | 0.00 | -10202.89 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 9707.44 | 0.00 | 0.00 | 242.31 | 0.00 | -0.00 | 0.00 | -6.20 | 0.00 |
PERIMETER_MID_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -4634.60 | 0.00 | 0.00 | 737.23 | 424.37 | 1435.25 | 2532.45 | 0.00 | 4.74 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -499.44 |
PERIMETER_MID_ZN_2 | 23-JUL-08:52 | 0.00 | 0.00 | 0.00 | -13332.99 | 0.00 | 0.00 | 14.35 | 14.92 | 302.86 | 9449.20 | 0.00 | 0.00 | 3583.94 | 0.00 | -0.00 | 0.00 | -32.28 | 0.00 |
PERIMETER_MID_ZN_1 | 24-SEP-13:22 | 0.00 | 0.00 | 0.00 | -17820.40 | 0.00 | 0.00 | 24.84 | 23.57 | 478.41 | 13352.25 | 0.00 | 0.00 | 3985.97 | 0.00 | -0.00 | 0.00 | -44.65 | 0.00 |
PERIMETER_MID_ZN_4 | 09-JUL-16:32 | 0.00 | 0.00 | 0.00 | -13656.65 | 0.00 | 0.00 | 14.68 | 14.92 | 302.86 | 11158.06 | 0.00 | 0.00 | 2198.36 | 0.00 | -0.00 | 0.00 | -32.23 | 0.00 |
TOPFLOOR_PLENUM | 13-JUN-14:40 | 0.00 | -8527.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8528.23 | 0.00 | -0.00 | 0.00 | -0.56 | 0.00 |
MIDFLOOR_PLENUM | 24-JUL-15:50 | 0.00 | -3397.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3412.04 | 0.00 | -0.00 | 0.00 | -14.50 | 0.00 |
FIRSTFLOOR_PLENUM | 24-JUL-16:00 | 0.00 | -3677.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3687.90 | 0.00 | -0.00 | 0.00 | -10.54 | 0.00 |
Total Facility | 13-JUN-15:40 | 0.00 | -14954.43 | 0.00 | -118264.19 | 0.00 | 0.00 | 17714.93 | 16818.70 | 42072.41 | 57927.86 | 0.00 | 469.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1784.35 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-06:02 | 0.00 | 0.00 | 20551.37 | 0.00 | 0.00 | 0.00 | 471.64 | 468.92 | 4989.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26481.43 |
CORE_MID | 02-JAN-06:01 | 0.00 | 0.00 | 21791.04 | 0.00 | 0.00 | 0.00 | 500.42 | 468.92 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25786.30 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 27987.78 | 0.00 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30898.75 |
PERIMETER_TOP_ZN_3 | 18-DEC-05:01 | 0.00 | 0.00 | 7888.85 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1616.60 | 0.00 | -92.61 | -6793.29 |
PERIMETER_TOP_ZN_2 | 18-DEC-05:01 | 0.00 | 0.00 | 8549.13 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1094.69 | 0.00 | -62.85 | -7780.07 |
PERIMETER_TOP_ZN_1 | 11-DEC-05:01 | 0.00 | 0.00 | 12827.17 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1296.09 | 0.00 | 0.00 | -12144.73 |
PERIMETER_TOP_ZN_4 | 18-DEC-05:01 | 0.00 | 0.00 | 8507.07 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1077.25 | 0.00 | -62.87 | -7755.41 |
PERIMETER_BOT_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 6060.62 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1530.71 | 0.00 | 0.00 | -5143.57 |
PERIMETER_BOT_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 6171.08 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1055.56 | 0.00 | 0.00 | -5503.99 |
PERIMETER_BOT_ZN_1 | 10-JAN-08:00 | 0.00 | 0.00 | 11932.24 | 0.00 | 0.00 | 0.00 | 246.76 | 296.56 | 637.88 | 0.00 | 0.00 | 0.00 | 13454.68 | 0.00 | -2230.87 | 0.00 | -24337.25 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 6150.15 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1043.62 | 0.00 | 0.00 | -5495.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 6789.60 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1530.39 | 0.00 | 0.00 | -5872.87 |
PERIMETER_MID_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 6172.89 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1028.39 | 0.00 | 0.00 | -5532.97 |
PERIMETER_MID_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 9045.50 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1600.92 | 0.00 | 0.00 | -8058.22 |
PERIMETER_MID_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 6144.65 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1026.92 | 0.00 | 0.00 | -5506.20 |
TOPFLOOR_PLENUM | 02-JAN-06:12 | 10853.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10853.53 |
MIDFLOOR_PLENUM | 02-JAN-07:11 | 7361.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7361.26 |
FIRSTFLOOR_PLENUM | 05-OCT-05:02 | 4652.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -27.06 | -4625.64 |
Total Facility | 02-JAN-06:01 | 10886.68 | 0.00 | 154139.33 | 0.00 | 0.00 | 0.00 | 2537.03 | 2375.34 | 17291.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16093.77 | 0.00 | -3286.69 | -167849.43 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.2575 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6008 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.8662 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.0297 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.1244 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5565 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.6288 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3505 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.4331 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3836 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.5622 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4442 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7084 | 2.7084 | 0.7638 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9226 | 1.9226 | 0.7344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9772 | 1.9772 | 0.7612 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5353 | 0.5353 | 0.1606 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7163 | 0.7163 | 0.1433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0903 | 1.0903 | 0.2181 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8052 | 0.8052 | 0.1610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4200 | 0.4200 | 0.1609 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5844 | 0.5844 | 0.1169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8794 | 0.8794 | 0.1759 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6653 | 0.6653 | 0.1331 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4721 | 0.4721 | 0.1549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7181 | 0.7181 | 0.1436 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0084 | 1.0084 | 0.2017 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7450 | 0.7450 | 0.1490 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.2575 | 4.6008 | 5.2575 | 1.3505 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.8662 | 4.0297 | 4.8662 | 1.3836 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.1244 | 4.5565 | 5.1244 | 1.4442 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3542 | 1.3542 | 0.7638 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9613 | 0.9613 | 0.7344 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9886 | 0.9886 | 0.7612 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2677 | 0.2677 | 0.1606 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3582 | 0.3582 | 0.1433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5452 | 0.5452 | 0.2181 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4026 | 0.4026 | 0.1610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2100 | 0.2100 | 0.1609 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2922 | 0.2922 | 0.1169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4397 | 0.4397 | 0.1759 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3327 | 0.3327 | 0.1331 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2361 | 0.2361 | 0.1549 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3591 | 0.3591 | 0.1436 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5042 | 0.5042 | 0.2017 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3725 | 0.3725 | 0.1490 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.6288 | 1.3505 | 1.3505 | 1.3505 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.4331 | 1.3836 | 1.3836 | 1.3836 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.5622 | 1.4442 | 1.4442 | 1.4442 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 474.50 |
Number of hours cooling loads not met | 63.50 |
Number of hours not met | 538.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 135.11 | 153761.42 | 98.87 | 61168.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 35.12 | 38915.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 204.69 | 21377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.74 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.66 | 835.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 70.28 | 20533.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 111.90 | 9443.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1213.04 |
Natural Gas | 0.00 | 210.77 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1423.82 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 41.09 |
Space Heating | 27.12 |
Space Cooling | 7.05 |
Fans (All) | 14.11 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 243.48 |
Subtotal | 243.48 |
Natural Gas [MJ/m2] | |
Space Heating | 19.85 |
Service Water Heating | 22.46 |
Miscellaneous (All) | 42.31 |
Subtotal | 42.31 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 14.38 |
Space Heating | 16.43 |
Space Cooling | 2.47 |
Fans (All) | 4.94 |
Service Water Heating | 7.86 |
Receptacle Equipment | 49.55 |
Miscellaneous | 4.38 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8740.50 | 19.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8742.33 | 17.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8745.00 | 15.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8740.67 | 19.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8740.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 19.50 | 0.00 | 0.00 | 0.00 |
Average | 8751.42 | 8.58 | 0.00 | 0.00 | 0.00 |
Sum | 157525.50 | 154.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8722.00 | 38.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8750.17 | 9.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8740.17 | 19.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8749.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8751.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8744.33 | 15.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8722.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 38.00 | 0.00 | 0.00 | 0.00 |
Average | 8750.79 | 9.21 | 0.00 | 0.00 | 0.00 |
Sum | 157514.17 | 165.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128280.33 | 23.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128302.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 23.67 | 0.00 | 0.00 | 0.00 |
Average | 34141.91 | 1.43 | 0.00 | 0.00 | 0.00 |
Sum | 614554.33 | 25.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.991558E+10 | 12462.36 | 26-JAN-08:20 | 4.53 | 4.01 | 0.188375E+10 | 2608.38 | 26-JAN-10:39 | 8.67 | 7.29 |
February | 0.986393E+10 | 12492.62 | 10-FEB-08:20 | 4.67 | 4.37 | 0.176450E+10 | 2606.65 | 17-FEB-10:20 | 4.00 | 2.99 |
March | 0.121275E+11 | 13878.50 | 31-MAR-07:17 | 3.00 | 2.55 | 0.211578E+10 | 2608.35 | 01-MAR-14:09 | 3.00 | 2.55 |
April | 0.161359E+11 | 33817.18 | 28-APR-05:02 | 6.17 | 4.37 | 0.190730E+10 | 2606.74 | 14-APR-13:00 | 6.17 | 4.37 |
May | 0.191007E+11 | 39419.47 | 01-MAY-05:02 | 4.33 | 3.72 | 0.207281E+10 | 2606.64 | 05-MAY-13:00 | 8.00 | 6.98 |
June | 0.216255E+11 | 39208.35 | 23-JUN-05:03 | 11.17 | 10.64 | 0.206882E+10 | 2606.76 | 08-JUN-13:09 | 11.17 | 10.64 |
July | 0.217294E+11 | 39434.57 | 22-JUL-05:03 | 16.33 | 11.78 | 0.192280E+10 | 2606.67 | 03-JUL-09:09 | 16.33 | 11.78 |
August | 0.237099E+11 | 39633.69 | 29-AUG-05:02 | 10.17 | 8.99 | 0.215759E+10 | 2606.69 | 08-AUG-13:09 | 10.17 | 8.99 |
September | 0.200017E+11 | 39494.94 | 05-SEP-05:02 | 6.33 | 5.74 | 0.191513E+10 | 2606.77 | 19-SEP-13:39 | 14.67 | 13.92 |
October | 0.149324E+11 | 34997.88 | 02-OCT-05:02 | 9.17 | 7.09 | 0.197704E+10 | 2606.70 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.113966E+11 | 14827.29 | 02-NOV-07:08 | 7.90 | 6.38 | 0.193954E+10 | 2606.63 | 10-NOV-10:20 | 11.00 | 9.41 |
December | 0.978369E+10 | 10835.83 | 22-DEC-08:50 | 3.83 | 3.03 | 0.184052E+10 | 2608.15 | 20-DEC-14:20 | 3.83 | 3.03 |
Annual Sum or Average | 0.190323E+12 | 0.235656E+11 | ||||||||
Minimum of Months | 0.978369E+10 | 10835.83 | 3.00 | 2.55 | 0.176450E+10 | 2606.63 | 3.00 | 2.55 | ||
Maximum of Months | 0.237099E+11 | 39633.69 | 16.33 | 11.78 | 0.215759E+10 | 2608.38 | 16.33 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12164062.97 | 492.82 | 19-JAN-17:10 | 5.83 | 5.75 | 0.00 | 0.00 | 01-JAN-00:10 | 5.83 | 5.75 |
February | 48593013.53 | 1156.97 | 04-FEB-16:20 | 7.00 | 5.54 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 5.54 |
March | 0.135094E+09 | 1945.97 | 25-MAR-12:50 | 13.67 | 10.83 | 0.00 | 0.00 | 01-MAR-00:10 | 13.67 | 10.83 |
April | 0.178709E+10 | 6924.82 | 28-APR-15:00 | 20.10 | 13.70 | 0.00 | 0.00 | 01-APR-00:10 | 20.10 | 13.70 |
May | 0.215274E+10 | 7522.13 | 22-MAY-14:50 | 23.83 | 16.03 | 0.00 | 0.00 | 01-MAY-00:10 | 23.83 | 16.03 |
June | 0.322384E+10 | 8527.63 | 13-JUN-14:40 | 25.70 | 17.71 | 0.00 | 0.00 | 01-JUN-00:10 | 25.70 | 17.71 |
July | 0.383370E+10 | 8522.94 | 21-JUL-14:50 | 27.00 | 15.89 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 15.89 |
August | 0.364567E+10 | 7709.09 | 14-AUG-15:10 | 25.17 | 16.00 | 0.00 | 0.00 | 01-AUG-00:10 | 25.17 | 16.00 |
September | 0.223823E+10 | 6421.77 | 12-SEP-14:40 | 21.67 | 15.81 | 0.00 | 0.00 | 01-SEP-00:10 | 21.67 | 15.81 |
October | 0.497743E+09 | 2831.04 | 03-OCT-14:40 | 14.00 | 9.11 | 0.00 | 0.00 | 01-OCT-00:10 | 14.00 | 9.11 |
November | 17974681.58 | 867.02 | 11-NOV-13:40 | 9.00 | 7.15 | 0.00 | 0.00 | 01-NOV-00:10 | 9.00 | 7.15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.175928E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.00 | 0.00 | 4.00 | 3.53 | ||
Maximum of Months | 0.383370E+10 | 8527.63 | 27.00 | 17.71 | 0.00 | 0.00 | 27.00 | 17.71 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30262791.79 | 1061.51 | 26-JAN-07:01 | 4.83 | 4.35 | 0.00 | 0.00 | 01-JAN-00:10 | 4.83 | 4.35 |
February | 43884890.00 | 1049.93 | 10-FEB-07:01 | 4.83 | 4.43 | 0.00 | 0.00 | 01-FEB-00:10 | 4.83 | 4.43 |
March | 96639172.63 | 1585.66 | 24-MAR-06:01 | 4.00 | 3.12 | 0.00 | 0.00 | 01-MAR-00:10 | 4.00 | 3.12 |
April | 0.539553E+09 | 1997.93 | 28-APR-16:00 | 20.00 | 12.32 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 12.32 |
May | 0.844286E+09 | 2369.82 | 23-MAY-16:00 | 18.00 | 14.38 | 0.00 | 0.00 | 01-MAY-00:10 | 18.00 | 14.38 |
June | 0.150774E+10 | 3150.86 | 13-JUN-15:30 | 26.25 | 17.77 | 0.00 | 0.00 | 01-JUN-00:10 | 26.25 | 17.77 |
July | 0.187396E+10 | 3397.57 | 24-JUL-15:50 | 19.83 | 16.14 | 0.00 | 0.00 | 01-JUL-00:10 | 19.83 | 16.14 |
August | 0.184180E+10 | 2768.88 | 14-AUG-16:00 | 26.00 | 15.86 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 15.86 |
September | 0.110553E+10 | 2514.88 | 13-SEP-16:00 | 23.00 | 16.22 | 0.00 | 0.00 | 01-SEP-00:10 | 23.00 | 16.22 |
October | 0.250201E+09 | 1527.61 | 19-OCT-06:01 | 5.33 | 4.70 | 0.00 | 0.00 | 01-OCT-00:10 | 5.33 | 4.70 |
November | 58797881.90 | 1555.47 | 01-NOV-06:01 | 5.00 | 4.51 | 0.00 | 0.00 | 01-NOV-00:10 | 5.00 | 4.51 |
December | 12540437.83 | 895.54 | 30-DEC-06:01 | -1.0 | -2.5 | 0.00 | 0.00 | 01-DEC-00:10 | -1.0 | -2.5 |
Annual Sum or Average | 0.820520E+10 | 0.00 | ||||||||
Minimum of Months | 12540437.83 | 895.54 | -1.0 | -2.5 | 0.00 | 0.00 | -1.0 | -2.5 | ||
Maximum of Months | 0.187396E+10 | 3397.57 | 26.25 | 17.77 | 0.00 | 0.00 | 26.25 | 17.77 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152984E+09 | 2285.26 | 11-JAN-17:10 | -3.2 | -4.7 | 0.00 | 0.00 | 01-JAN-00:10 | -3.2 | -4.7 |
February | 0.177462E+09 | 2645.69 | 24-FEB-07:10 | -1.7 | -1.7 | 0.00 | 0.00 | 01-FEB-00:10 | -1.7 | -1.7 |
March | 0.276335E+09 | 2244.57 | 21-MAR-06:10 | 1.00 | 0.24 | 0.00 | 0.00 | 01-MAR-00:10 | 1.00 | 0.24 |
April | 0.102734E+10 | 2782.31 | 20-APR-06:07 | 2.83 | 1.33 | 0.00 | 0.00 | 01-APR-00:10 | 2.83 | 1.33 |
May | 0.147362E+10 | 3382.45 | 01-MAY-16:05 | 8.17 | 7.39 | 0.00 | 0.00 | 01-MAY-00:10 | 8.17 | 7.39 |
June | 0.215515E+10 | 3545.49 | 13-JUN-16:00 | 26.50 | 17.70 | 0.00 | 0.00 | 01-JUN-00:10 | 26.50 | 17.70 |
July | 0.245996E+10 | 3677.46 | 24-JUL-16:00 | 20.00 | 16.18 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 16.18 |
August | 0.253968E+10 | 3315.44 | 14-AUG-16:00 | 26.00 | 15.86 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 15.86 |
September | 0.183113E+10 | 3147.34 | 13-SEP-16:00 | 23.00 | 16.22 | 0.00 | 0.00 | 01-SEP-00:10 | 23.00 | 16.22 |
October | 0.595122E+09 | 2794.96 | 04-OCT-06:09 | 3.17 | 3.17 | 0.00 | 0.00 | 01-OCT-00:10 | 3.17 | 3.17 |
November | 0.207062E+09 | 2255.83 | 01-NOV-06:01 | 5.00 | 4.51 | 0.00 | 0.00 | 01-NOV-00:10 | 5.00 | 4.51 |
December | 0.110032E+09 | 2501.89 | 29-DEC-17:10 | -2.0 | -2.8 | 0.00 | 0.00 | 01-DEC-00:10 | -2.0 | -2.8 |
Annual Sum or Average | 0.130059E+11 | 0.00 | ||||||||
Minimum of Months | 0.110032E+09 | 2244.57 | -3.2 | -4.7 | 0.00 | 0.00 | -3.2 | -4.7 | ||
Maximum of Months | 0.253968E+10 | 3677.46 | 26.50 | 17.70 | 0.00 | 0.00 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.663323E+10 | 6766.31 | 20-JAN-17:00 | 5.00 | 4.51 | 0.160477E+10 | 2388.09 | 20-JAN-14:00 | 5.00 | 4.51 |
February | 0.680254E+10 | 6755.33 | 24-FEB-17:00 | 6.00 | 4.60 | 0.149621E+10 | 2357.06 | 24-FEB-14:00 | 6.00 | 4.60 |
March | 0.831842E+10 | 6904.62 | 31-MAR-15:40 | 8.33 | 4.78 | 0.181978E+10 | 2394.59 | 31-MAR-13:00 | 8.33 | 4.78 |
April | 0.101940E+11 | 12435.86 | 28-APR-16:00 | 20.00 | 12.32 | 0.183425E+10 | 2606.67 | 14-APR-13:00 | 20.00 | 12.32 |
May | 0.121880E+11 | 25237.37 | 01-MAY-05:02 | 4.33 | 3.72 | 0.203277E+10 | 2606.62 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.141165E+11 | 24268.24 | 26-JUN-05:03 | 14.33 | 11.96 | 0.205428E+10 | 2606.66 | 08-JUN-13:09 | 14.33 | 11.96 |
July | 0.145715E+11 | 24319.47 | 24-JUL-06:02 | 13.17 | 13.07 | 0.191066E+10 | 2606.64 | 03-JUL-09:09 | 13.17 | 13.07 |
August | 0.154618E+11 | 22338.43 | 07-AUG-05:03 | 10.17 | 9.06 | 0.214612E+10 | 2606.67 | 08-AUG-13:09 | 17.83 | 16.43 |
September | 0.127052E+11 | 16168.11 | 13-SEP-05:03 | 9.33 | 9.25 | 0.189370E+10 | 2606.71 | 19-SEP-13:50 | 14.33 | 13.96 |
October | 0.911172E+10 | 10875.78 | 03-OCT-16:00 | 14.00 | 8.96 | 0.181753E+10 | 2606.64 | 04-OCT-09:20 | 12.33 | 9.48 |
November | 0.747770E+10 | 6960.78 | 10-NOV-16:50 | 7.67 | 6.84 | 0.166367E+10 | 2435.10 | 10-NOV-14:00 | 7.67 | 6.84 |
December | 0.635658E+10 | 6380.79 | 21-DEC-15:10 | 7.83 | 6.90 | 0.153414E+10 | 2309.10 | 21-DEC-14:00 | 7.83 | 6.90 |
Annual Sum or Average | 0.123937E+12 | 0.218079E+11 | ||||||||
Minimum of Months | 0.635658E+10 | 6380.79 | 4.33 | 3.72 | 0.149621E+10 | 2309.10 | 5.00 | 4.51 | ||
Maximum of Months | 0.154618E+11 | 25237.37 | 20.00 | 13.07 | 0.214612E+10 | 2606.71 | 23.00 | 16.43 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469947E+10 | 6607.71 | 19-JAN-16:40 | 6.67 | 6.49 | 0.151456E+10 | 2281.12 | 20-JAN-14:00 | 8.00 | 6.49 |
February | 0.506200E+10 | 6626.47 | 09-FEB-17:00 | 6.00 | 4.60 | 0.139998E+10 | 2256.41 | 09-FEB-16:00 | 6.00 | 4.60 |
March | 0.675551E+10 | 6795.90 | 31-MAR-16:00 | 9.00 | 4.96 | 0.170481E+10 | 2296.49 | 10-MAR-14:00 | 9.00 | 4.96 |
April | 0.965942E+10 | 13564.88 | 28-APR-16:00 | 20.00 | 12.32 | 0.175134E+10 | 2606.67 | 14-APR-13:00 | 20.00 | 12.32 |
May | 0.115456E+11 | 14827.06 | 23-MAY-15:50 | 18.00 | 14.38 | 0.196365E+10 | 2606.62 | 22-MAY-13:00 | 18.00 | 14.38 |
June | 0.136564E+11 | 16369.07 | 13-JUN-16:00 | 26.50 | 17.70 | 0.203012E+10 | 2606.66 | 09-JUN-13:00 | 26.50 | 17.70 |
July | 0.142296E+11 | 20905.31 | 24-JUL-05:03 | 13.00 | 13.00 | 0.189461E+10 | 2606.63 | 21-JUL-13:09 | 13.00 | 13.00 |
August | 0.147459E+11 | 15145.35 | 14-AUG-16:00 | 26.00 | 15.86 | 0.212436E+10 | 2606.67 | 15-AUG-09:09 | 16.00 | 13.59 |
September | 0.115878E+11 | 14346.39 | 13-SEP-16:00 | 23.00 | 16.22 | 0.184436E+10 | 2606.70 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.791251E+10 | 9706.79 | 03-OCT-16:00 | 14.00 | 8.96 | 0.168618E+10 | 2606.56 | 02-OCT-13:00 | 14.00 | 8.96 |
November | 0.571137E+10 | 6842.69 | 10-NOV-16:30 | 9.00 | 7.52 | 0.154144E+10 | 2344.90 | 10-NOV-14:00 | 9.00 | 7.52 |
December | 0.399784E+10 | 6167.89 | 21-DEC-15:35 | 7.33 | 6.65 | 0.144297E+10 | 2194.93 | 21-DEC-14:00 | 7.33 | 6.65 |
Annual Sum or Average | 0.109563E+12 | 0.208984E+11 | ||||||||
Minimum of Months | 0.399784E+10 | 6167.89 | 6.00 | 4.60 | 0.139998E+10 | 2194.93 | 6.00 | 4.60 | ||
Maximum of Months | 0.147459E+11 | 20905.31 | 26.50 | 17.70 | 0.212436E+10 | 2606.70 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237140E+09 | 1172.33 | 19-JAN-16:00 | 8.00 | 7.45 | 0.306590E+09 | 428.90 | 19-JAN-14:00 | 8.00 | 7.45 |
February | 0.344782E+09 | 1148.90 | 09-FEB-16:00 | 8.00 | 5.66 | 0.279062E+09 | 426.39 | 03-FEB-14:00 | 8.00 | 5.66 |
March | 0.706736E+09 | 1323.35 | 30-MAR-15:50 | 12.00 | 5.94 | 0.341006E+09 | 464.67 | 30-MAR-13:00 | 12.00 | 5.94 |
April | 0.177497E+10 | 3446.58 | 28-APR-15:40 | 20.03 | 12.78 | 0.351153E+09 | 549.49 | 21-APR-13:09 | 20.03 | 12.78 |
May | 0.235426E+10 | 3984.16 | 22-MAY-15:40 | 23.33 | 15.55 | 0.398425E+09 | 549.50 | 22-MAY-13:00 | 23.33 | 15.55 |
June | 0.320243E+10 | 5132.70 | 13-JUN-16:00 | 26.50 | 17.70 | 0.422484E+09 | 549.50 | 09-JUN-13:00 | 26.50 | 17.70 |
July | 0.346263E+10 | 4908.14 | 10-JUL-15:00 | 23.00 | 16.69 | 0.396022E+09 | 549.50 | 21-JUL-13:09 | 26.17 | 16.40 |
August | 0.332444E+10 | 4413.43 | 14-AUG-16:00 | 26.00 | 15.86 | 0.440015E+09 | 549.50 | 11-AUG-13:00 | 26.00 | 15.86 |
September | 0.228961E+10 | 3734.39 | 13-SEP-15:30 | 23.00 | 16.22 | 0.373157E+09 | 549.49 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.109078E+10 | 1606.19 | 06-OCT-16:00 | 17.00 | 9.21 | 0.330751E+09 | 527.79 | 06-OCT-15:00 | 17.00 | 9.21 |
November | 0.398363E+09 | 1255.58 | 10-NOV-15:30 | 11.50 | 8.42 | 0.306065E+09 | 452.30 | 10-NOV-14:00 | 11.50 | 8.42 |
December | 92685123.92 | 996.03 | 05-DEC-21:03 | 6.50 | 5.97 | 0.294538E+09 | 406.69 | 04-DEC-10:09 | 6.50 | 5.97 |
Annual Sum or Average | 0.192788E+11 | 0.423927E+10 | ||||||||
Minimum of Months | 92685123.92 | 996.03 | 6.50 | 5.66 | 0.279062E+09 | 406.69 | 6.50 | 5.66 | ||
Maximum of Months | 0.346263E+10 | 5132.70 | 26.50 | 17.70 | 0.440015E+09 | 549.50 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282412E+09 | 1157.21 | 20-JAN-10:40 | 5.33 | 4.86 | 0.194652E+09 | 294.17 | 20-JAN-10:50 | 5.67 | 5.18 |
February | 0.410583E+09 | 1245.04 | 24-FEB-10:35 | 5.67 | 4.28 | 0.179326E+09 | 309.50 | 24-FEB-10:39 | 5.67 | 4.28 |
March | 0.677819E+09 | 1204.76 | 30-MAR-10:30 | 9.50 | 6.81 | 0.216488E+09 | 300.34 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.235302E+10 | 12475.80 | 30-APR-09:22 | 19.00 | 12.37 | 0.239617E+09 | 347.89 | 14-APR-13:00 | 19.00 | 12.37 |
May | 0.283150E+10 | 6992.93 | 23-MAY-09:10 | 19.17 | 14.75 | 0.261718E+09 | 347.88 | 22-MAY-13:00 | 19.17 | 14.75 |
June | 0.352983E+10 | 11085.57 | 25-JUN-10:02 | 18.50 | 13.17 | 0.269994E+09 | 348.23 | 13-JUN-09:50 | 18.50 | 13.17 |
July | 0.377456E+10 | 12289.69 | 23-JUL-09:02 | 20.17 | 15.71 | 0.253458E+09 | 348.07 | 10-JUL-09:30 | 20.17 | 15.71 |
August | 0.393809E+10 | 11350.38 | 20-AUG-09:32 | 16.33 | 13.20 | 0.282245E+09 | 347.89 | 14-AUG-09:50 | 16.33 | 13.20 |
September | 0.284704E+10 | 5978.24 | 12-SEP-09:30 | 17.50 | 14.46 | 0.246774E+09 | 347.89 | 06-SEP-09:09 | 17.50 | 14.46 |
October | 0.110938E+10 | 2832.03 | 04-OCT-10:00 | 13.00 | 9.81 | 0.217027E+09 | 347.87 | 04-OCT-09:20 | 13.00 | 9.81 |
November | 0.394007E+09 | 1156.23 | 03-NOV-10:00 | 7.00 | 5.17 | 0.194333E+09 | 293.94 | 03-NOV-09:00 | 7.00 | 5.17 |
December | 0.136357E+09 | 1008.22 | 06-DEC-10:20 | 5.00 | 3.82 | 0.186725E+09 | 269.14 | 06-DEC-10:30 | 5.50 | 4.16 |
Annual Sum or Average | 0.222846E+11 | 0.274236E+10 | ||||||||
Minimum of Months | 0.136357E+09 | 1008.22 | 5.00 | 3.82 | 0.179326E+09 | 269.14 | 5.50 | 4.16 | ||
Maximum of Months | 0.393809E+10 | 12475.80 | 20.17 | 15.71 | 0.282245E+09 | 348.23 | 20.17 | 15.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101839E+10 | 5053.24 | 20-JAN-12:00 | 8.00 | 6.08 | 0.328196E+09 | 549.49 | 20-JAN-14:00 | 8.00 | 6.49 |
February | 0.129668E+10 | 6728.37 | 17-FEB-14:10 | 6.00 | 3.06 | 0.306347E+09 | 549.49 | 24-FEB-14:20 | 6.00 | 4.60 |
March | 0.127226E+10 | 3098.26 | 28-MAR-12:15 | 11.33 | 7.17 | 0.354524E+09 | 549.50 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.416154E+10 | 20195.05 | 30-APR-13:22 | 22.50 | 12.93 | 0.367195E+09 | 549.52 | 14-APR-13:00 | 22.50 | 12.93 |
May | 0.417483E+10 | 9467.60 | 23-MAY-13:10 | 18.17 | 14.45 | 0.400315E+09 | 549.51 | 22-MAY-13:50 | 18.17 | 14.45 |
June | 0.484815E+10 | 10547.91 | 11-JUN-14:02 | 17.83 | 14.32 | 0.417011E+09 | 549.53 | 08-JUN-13:09 | 17.83 | 14.32 |
July | 0.551792E+10 | 18289.87 | 23-JUL-13:43 | 21.17 | 16.07 | 0.393084E+09 | 549.52 | 21-JUL-13:09 | 21.17 | 16.07 |
August | 0.651174E+10 | 18582.68 | 06-AUG-13:43 | 17.83 | 13.83 | 0.439642E+09 | 549.50 | 11-AUG-13:00 | 16.00 | 14.77 |
September | 0.587373E+10 | 19438.55 | 10-SEP-13:32 | 21.00 | 15.82 | 0.383892E+09 | 549.92 | 11-SEP-13:00 | 21.00 | 15.99 |
October | 0.284362E+10 | 10464.33 | 03-OCT-13:30 | 13.50 | 9.36 | 0.352780E+09 | 549.51 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.112919E+10 | 5740.36 | 03-NOV-12:40 | 9.00 | 5.48 | 0.325133E+09 | 549.49 | 03-NOV-13:00 | 9.00 | 5.72 |
December | 0.600582E+09 | 4409.16 | 18-DEC-13:30 | 8.00 | 5.46 | 0.307907E+09 | 549.49 | 18-DEC-14:00 | 8.00 | 5.66 |
Annual Sum or Average | 0.392486E+11 | 0.437602E+10 | ||||||||
Minimum of Months | 0.600582E+09 | 3098.26 | 6.00 | 3.06 | 0.306347E+09 | 549.49 | 6.00 | 4.60 | ||
Maximum of Months | 0.651174E+10 | 20195.05 | 22.50 | 16.07 | 0.439642E+09 | 549.92 | 22.50 | 16.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286625E+09 | 1500.16 | 19-JAN-16:00 | 8.00 | 7.45 | 0.195802E+09 | 315.13 | 19-JAN-16:10 | 7.67 | 7.22 |
February | 0.461482E+09 | 2152.74 | 27-FEB-16:30 | 8.00 | 6.72 | 0.182275E+09 | 338.68 | 27-FEB-16:00 | 8.00 | 6.97 |
March | 0.694701E+09 | 2182.50 | 23-MAR-17:00 | 10.00 | 6.65 | 0.215631E+09 | 338.21 | 23-MAR-15:00 | 10.00 | 6.65 |
April | 0.231832E+10 | 14645.56 | 30-APR-16:02 | 24.00 | 13.04 | 0.218577E+09 | 347.85 | 28-APR-13:00 | 24.00 | 13.04 |
May | 0.292944E+10 | 9756.94 | 21-MAY-16:53 | 20.00 | 12.79 | 0.245454E+09 | 347.85 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.375872E+10 | 14823.44 | 25-JUN-16:42 | 21.67 | 14.18 | 0.260714E+09 | 347.86 | 09-JUN-13:00 | 21.67 | 14.18 |
July | 0.405042E+10 | 14107.78 | 30-JUL-16:42 | 14.33 | 10.92 | 0.246361E+09 | 347.85 | 21-JUL-13:09 | 14.33 | 10.92 |
August | 0.380419E+10 | 14468.19 | 20-AUG-16:12 | 23.33 | 14.80 | 0.272876E+09 | 347.85 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.274021E+10 | 10527.11 | 10-SEP-16:12 | 20.33 | 16.35 | 0.230757E+09 | 347.85 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.115591E+10 | 4688.82 | 03-OCT-16:00 | 14.00 | 8.96 | 0.208611E+09 | 347.81 | 03-OCT-13:00 | 14.00 | 8.96 |
November | 0.394643E+09 | 1524.53 | 10-NOV-15:50 | 11.17 | 8.40 | 0.195022E+09 | 320.19 | 10-NOV-15:00 | 11.00 | 8.40 |
December | 0.122510E+09 | 1218.67 | 21-DEC-14:50 | 8.00 | 6.98 | 0.186717E+09 | 281.33 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.227172E+11 | 0.265880E+10 | ||||||||
Minimum of Months | 0.122510E+09 | 1218.67 | 8.00 | 6.65 | 0.182275E+09 | 281.33 | 7.67 | 6.65 | ||
Maximum of Months | 0.405042E+10 | 14823.44 | 24.00 | 16.35 | 0.272876E+09 | 347.86 | 24.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357219E+09 | 1143.88 | 25-JAN-15:10 | 10.67 | 9.25 | 0.308099E+09 | 426.36 | 25-JAN-14:00 | 10.67 | 9.25 |
February | 0.467940E+09 | 1135.70 | 10-FEB-16:30 | 6.50 | 4.88 | 0.279895E+09 | 421.72 | 10-FEB-14:00 | 6.50 | 4.88 |
March | 0.846467E+09 | 1255.60 | 30-MAR-14:00 | 13.00 | 7.37 | 0.340746E+09 | 453.77 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.171864E+10 | 1874.75 | 28-APR-16:00 | 20.00 | 12.32 | 0.345426E+09 | 549.48 | 28-APR-13:00 | 20.00 | 12.32 |
May | 0.208473E+10 | 2339.24 | 23-MAY-14:00 | 19.00 | 14.77 | 0.398336E+09 | 549.49 | 22-MAY-13:00 | 19.00 | 14.77 |
June | 0.263894E+10 | 3558.61 | 13-JUN-16:00 | 26.50 | 17.70 | 0.424333E+09 | 549.50 | 09-JUN-13:00 | 26.50 | 17.70 |
July | 0.289369E+10 | 3502.25 | 21-JUL-16:00 | 28.00 | 16.11 | 0.398368E+09 | 549.49 | 06-JUL-09:09 | 28.00 | 16.11 |
August | 0.285910E+10 | 3002.98 | 14-AUG-16:00 | 26.00 | 15.86 | 0.443903E+09 | 549.50 | 08-AUG-13:09 | 26.00 | 15.86 |
September | 0.219587E+10 | 2687.21 | 13-SEP-15:30 | 23.00 | 16.22 | 0.381372E+09 | 549.49 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.153790E+10 | 1558.98 | 02-OCT-15:00 | 14.00 | 10.70 | 0.344857E+09 | 523.68 | 02-OCT-13:20 | 14.00 | 10.70 |
November | 0.862713E+09 | 1287.75 | 10-NOV-15:10 | 11.83 | 8.42 | 0.313362E+09 | 460.72 | 10-NOV-14:00 | 11.83 | 8.42 |
December | 0.277437E+09 | 1087.41 | 21-DEC-14:00 | 8.00 | 6.98 | 0.296071E+09 | 413.56 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.187407E+11 | 0.427477E+10 | ||||||||
Minimum of Months | 0.277437E+09 | 1087.41 | 6.50 | 4.88 | 0.279895E+09 | 413.56 | 6.50 | 4.88 | ||
Maximum of Months | 0.289369E+10 | 3558.61 | 28.00 | 17.70 | 0.443903E+09 | 549.50 | 28.00 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353924E+09 | 978.06 | 20-JAN-10:30 | 5.00 | 4.55 | 0.196592E+09 | 301.37 | 20-JAN-10:39 | 5.33 | 4.86 |
February | 0.464442E+09 | 1027.79 | 24-FEB-10:30 | 5.50 | 4.13 | 0.181605E+09 | 312.17 | 24-FEB-10:39 | 5.67 | 4.28 |
March | 0.692020E+09 | 981.14 | 31-MAR-09:50 | 8.33 | 5.01 | 0.218497E+09 | 302.13 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.197645E+10 | 4375.67 | 28-APR-09:50 | 17.67 | 11.49 | 0.242841E+09 | 347.88 | 14-APR-13:00 | 17.67 | 11.49 |
May | 0.236598E+10 | 5392.07 | 23-MAY-09:20 | 19.33 | 14.73 | 0.267188E+09 | 347.88 | 22-MAY-13:00 | 19.33 | 14.73 |
June | 0.295116E+10 | 7092.15 | 26-JUN-06:03 | 16.67 | 13.34 | 0.272963E+09 | 347.88 | 20-JUN-09:09 | 16.67 | 13.34 |
July | 0.325460E+10 | 8065.59 | 16-JUL-10:02 | 16.33 | 13.83 | 0.255399E+09 | 347.88 | 03-JUL-09:09 | 16.33 | 13.83 |
August | 0.348685E+10 | 5451.75 | 21-AUG-09:30 | 18.00 | 13.89 | 0.285957E+09 | 347.88 | 23-AUG-09:09 | 16.17 | 12.09 |
September | 0.268892E+10 | 4886.20 | 12-SEP-09:20 | 17.67 | 14.44 | 0.252237E+09 | 347.89 | 06-SEP-09:09 | 17.67 | 14.44 |
October | 0.132495E+10 | 2677.96 | 04-OCT-10:00 | 13.00 | 9.81 | 0.228336E+09 | 347.88 | 04-OCT-09:20 | 13.00 | 9.81 |
November | 0.697812E+09 | 1019.79 | 03-NOV-09:40 | 6.67 | 4.83 | 0.200653E+09 | 310.40 | 03-NOV-09:50 | 6.83 | 5.00 |
December | 0.279782E+09 | 892.15 | 08-DEC-10:30 | 5.00 | 3.66 | 0.188281E+09 | 283.38 | 08-DEC-10:39 | 5.33 | 3.83 |
Annual Sum or Average | 0.205369E+11 | 0.279055E+10 | ||||||||
Minimum of Months | 0.279782E+09 | 892.15 | 5.00 | 3.66 | 0.181605E+09 | 283.38 | 5.33 | 3.83 | ||
Maximum of Months | 0.348685E+10 | 8065.59 | 19.33 | 14.73 | 0.285957E+09 | 347.89 | 19.33 | 14.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345669E+09 | 2261.82 | 21-JAN-11:30 | 6.00 | 5.05 | 0.298444E+09 | 498.35 | 17-JAN-14:09 | 6.00 | 5.05 |
February | 0.438870E+09 | 2902.63 | 04-FEB-14:00 | 9.00 | 6.13 | 0.274740E+09 | 484.50 | 03-FEB-14:39 | 9.00 | 6.13 |
March | 0.331145E+09 | 1561.21 | 25-MAR-11:50 | 11.92 | 8.82 | 0.323011E+09 | 447.36 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.192715E+10 | 7988.49 | 30-APR-13:43 | 22.83 | 12.83 | 0.337041E+09 | 549.51 | 21-APR-13:09 | 22.83 | 12.83 |
May | 0.196962E+10 | 6462.00 | 22-MAY-14:00 | 23.00 | 15.76 | 0.367657E+09 | 549.51 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.264697E+10 | 7855.95 | 13-JUN-16:10 | 26.58 | 17.67 | 0.391558E+09 | 549.51 | 09-JUN-13:00 | 26.58 | 17.67 |
July | 0.336250E+10 | 11362.03 | 23-JUL-13:43 | 21.17 | 16.07 | 0.381053E+09 | 549.51 | 21-JUL-13:00 | 21.17 | 16.07 |
August | 0.421223E+10 | 10598.55 | 20-AUG-13:53 | 23.00 | 14.82 | 0.434046E+09 | 549.50 | 21-AUG-13:30 | 21.00 | 14.72 |
September | 0.395781E+10 | 15152.46 | 24-SEP-13:22 | 20.00 | 15.13 | 0.381300E+09 | 549.71 | 25-SEP-13:30 | 21.50 | 13.34 |
October | 0.172516E+10 | 7332.13 | 02-OCT-12:20 | 14.00 | 10.70 | 0.339424E+09 | 549.51 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.533843E+09 | 1950.79 | 25-NOV-12:40 | 10.00 | 5.90 | 0.303682E+09 | 519.71 | 15-NOV-14:39 | 10.00 | 5.90 |
December | 0.147378E+09 | 1533.50 | 18-DEC-14:00 | 8.00 | 5.67 | 0.284953E+09 | 490.38 | 18-DEC-14:09 | 8.00 | 5.67 |
Annual Sum or Average | 0.215983E+11 | 0.411691E+10 | ||||||||
Minimum of Months | 0.147378E+09 | 1533.50 | 6.00 | 5.05 | 0.274740E+09 | 447.36 | 6.00 | 5.05 | ||
Maximum of Months | 0.421223E+10 | 15152.46 | 26.58 | 17.67 | 0.434046E+09 | 549.71 | 26.58 | 17.67 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348255E+09 | 1200.27 | 19-JAN-15:50 | 8.17 | 7.46 | 0.196791E+09 | 308.92 | 19-JAN-15:00 | 8.00 | 7.45 |
February | 0.513892E+09 | 1336.41 | 27-FEB-16:40 | 8.00 | 6.81 | 0.182360E+09 | 334.66 | 27-FEB-16:49 | 8.00 | 6.89 |
March | 0.721747E+09 | 1336.52 | 23-MAR-17:00 | 10.00 | 6.65 | 0.216061E+09 | 316.48 | 23-MAR-15:00 | 10.00 | 6.65 |
April | 0.185149E+10 | 7511.74 | 30-APR-17:42 | 24.00 | 13.04 | 0.223996E+09 | 347.84 | 28-APR-13:00 | 24.00 | 13.04 |
May | 0.237762E+10 | 5855.85 | 22-MAY-16:00 | 23.00 | 15.28 | 0.255855E+09 | 347.85 | 22-MAY-13:00 | 23.00 | 15.28 |
June | 0.307546E+10 | 10200.51 | 25-JUN-17:11 | 21.33 | 16.05 | 0.269062E+09 | 347.85 | 09-JUN-13:00 | 21.33 | 16.05 |
July | 0.342837E+10 | 9171.95 | 22-JUL-18:22 | 29.50 | 16.91 | 0.252909E+09 | 347.85 | 12-JUL-13:00 | 29.50 | 16.91 |
August | 0.321469E+10 | 6845.67 | 19-AUG-17:06 | 18.00 | 14.38 | 0.282971E+09 | 347.86 | 15-AUG-09:09 | 18.00 | 14.38 |
September | 0.240230E+10 | 5571.57 | 12-SEP-16:00 | 21.00 | 15.99 | 0.244068E+09 | 347.85 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.138592E+10 | 3993.72 | 03-OCT-16:00 | 14.00 | 8.96 | 0.219470E+09 | 347.83 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.713842E+09 | 1263.78 | 10-NOV-15:50 | 11.17 | 8.40 | 0.198573E+09 | 320.99 | 10-NOV-15:00 | 11.00 | 8.40 |
December | 0.210636E+09 | 1029.60 | 21-DEC-14:50 | 8.00 | 6.98 | 0.187749E+09 | 285.44 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.202442E+11 | 0.272986E+10 | ||||||||
Minimum of Months | 0.210636E+09 | 1029.60 | 8.00 | 6.65 | 0.182360E+09 | 285.44 | 8.00 | 6.65 | ||
Maximum of Months | 0.342837E+10 | 10200.51 | 29.50 | 16.91 | 0.282971E+09 | 347.86 | 29.50 | 16.91 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473214E+09 | 1205.73 | 19-JAN-15:30 | 8.50 | 7.46 | 0.310914E+09 | 447.43 | 19-JAN-14:00 | 8.50 | 7.46 |
February | 0.640822E+09 | 1186.66 | 09-FEB-15:50 | 8.00 | 5.73 | 0.284826E+09 | 444.18 | 24-FEB-14:09 | 6.00 | 4.60 |
March | 0.111690E+10 | 1349.52 | 31-MAR-15:40 | 8.33 | 4.78 | 0.351634E+09 | 484.56 | 30-MAR-13:00 | 8.33 | 4.78 |
April | 0.196842E+10 | 3217.64 | 28-APR-15:40 | 20.03 | 12.78 | 0.367149E+09 | 549.50 | 14-APR-13:00 | 20.03 | 12.78 |
May | 0.250258E+10 | 3566.87 | 22-MAY-15:40 | 23.33 | 15.55 | 0.415747E+09 | 549.49 | 22-MAY-13:00 | 23.33 | 15.55 |
June | 0.329907E+10 | 4634.80 | 13-JUN-16:00 | 26.50 | 17.70 | 0.430594E+09 | 549.50 | 08-JUN-13:09 | 26.50 | 17.70 |
July | 0.353593E+10 | 4456.57 | 10-JUL-15:00 | 23.00 | 16.69 | 0.401266E+09 | 549.50 | 03-JUL-09:09 | 23.00 | 16.69 |
August | 0.345316E+10 | 4069.79 | 14-AUG-16:00 | 26.00 | 15.86 | 0.448687E+09 | 549.50 | 15-AUG-09:09 | 16.00 | 13.59 |
September | 0.249067E+10 | 3599.12 | 13-SEP-15:30 | 23.00 | 16.22 | 0.388154E+09 | 549.51 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.151965E+10 | 1799.11 | 02-OCT-15:00 | 14.00 | 10.70 | 0.350739E+09 | 549.48 | 02-OCT-13:20 | 14.00 | 10.70 |
November | 0.844956E+09 | 1285.88 | 10-NOV-15:30 | 11.50 | 8.42 | 0.314822E+09 | 471.41 | 10-NOV-14:00 | 11.50 | 8.42 |
December | 0.331983E+09 | 1087.99 | 21-DEC-14:50 | 8.00 | 6.98 | 0.296322E+09 | 423.81 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.221774E+11 | 0.436085E+10 | ||||||||
Minimum of Months | 0.331983E+09 | 1087.99 | 8.00 | 4.78 | 0.284826E+09 | 423.81 | 6.00 | 4.60 | ||
Maximum of Months | 0.353593E+10 | 4634.80 | 26.50 | 17.70 | 0.448687E+09 | 549.51 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449391E+09 | 1260.86 | 20-JAN-10:00 | 4.00 | 3.60 | 0.144836E+09 | 299.93 | 20-JAN-09:00 | 4.00 | 3.60 |
February | 0.603462E+09 | 1362.09 | 17-FEB-10:00 | 3.00 | 2.16 | 0.134279E+09 | 319.55 | 17-FEB-09:00 | 3.00 | 2.16 |
March | 0.948874E+09 | 1293.40 | 25-MAR-09:50 | 10.67 | 7.61 | 0.162167E+09 | 308.10 | 30-MAR-10:39 | 9.67 | 6.89 |
April | 0.257574E+10 | 11788.57 | 30-APR-10:13 | 19.67 | 12.19 | 0.178635E+09 | 338.78 | 28-APR-07:00 | 19.67 | 12.19 |
May | 0.300090E+10 | 7139.55 | 23-MAY-08:40 | 18.33 | 14.52 | 0.196028E+09 | 338.72 | 22-MAY-14:09 | 18.33 | 14.52 |
June | 0.355463E+10 | 7630.89 | 26-JUN-06:03 | 16.67 | 13.34 | 0.200616E+09 | 338.90 | 13-JUN-08:00 | 16.67 | 13.34 |
July | 0.379336E+10 | 13335.00 | 23-JUL-08:52 | 20.00 | 15.65 | 0.188424E+09 | 338.73 | 31-JUL-08:09 | 14.83 | 10.71 |
August | 0.398207E+10 | 12190.63 | 20-AUG-08:23 | 16.50 | 13.27 | 0.209506E+09 | 338.73 | 21-AUG-07:10 | 14.33 | 12.39 |
September | 0.306151E+10 | 7441.89 | 04-SEP-09:03 | 14.08 | 10.77 | 0.184119E+09 | 338.73 | 21-SEP-08:09 | 13.00 | 11.30 |
October | 0.148179E+10 | 3620.67 | 03-OCT-09:00 | 12.00 | 9.31 | 0.164182E+09 | 338.72 | 03-OCT-12:20 | 13.00 | 9.64 |
November | 0.701234E+09 | 1258.03 | 03-NOV-10:30 | 8.00 | 5.31 | 0.145822E+09 | 303.21 | 03-NOV-10:39 | 8.33 | 5.34 |
December | 0.289181E+09 | 1119.24 | 06-DEC-10:00 | 4.00 | 3.12 | 0.138415E+09 | 277.66 | 06-DEC-09:00 | 4.00 | 3.12 |
Annual Sum or Average | 0.244422E+11 | 0.204703E+10 | ||||||||
Minimum of Months | 0.289181E+09 | 1119.24 | 3.00 | 2.16 | 0.134279E+09 | 277.66 | 3.00 | 2.16 | ||
Maximum of Months | 0.398207E+10 | 13335.00 | 20.00 | 15.65 | 0.209506E+09 | 338.90 | 19.67 | 14.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137068E+10 | 5928.88 | 20-JAN-12:00 | 8.00 | 6.08 | 0.336524E+09 | 549.50 | 20-JAN-10:50 | 8.00 | 6.08 |
February | 0.169258E+10 | 7173.88 | 17-FEB-13:35 | 6.00 | 3.25 | 0.315741E+09 | 550.14 | 27-FEB-14:30 | 8.50 | 7.45 |
March | 0.169253E+10 | 3587.99 | 28-MAR-12:10 | 11.67 | 7.18 | 0.367056E+09 | 549.50 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.438124E+10 | 17194.77 | 30-APR-11:32 | 21.00 | 13.03 | 0.379044E+09 | 549.82 | 28-APR-13:09 | 21.00 | 13.03 |
May | 0.431257E+10 | 8886.74 | 23-MAY-13:10 | 18.17 | 14.45 | 0.415429E+09 | 549.51 | 22-MAY-13:00 | 18.17 | 14.45 |
June | 0.481540E+10 | 8734.43 | 13-JUN-13:10 | 24.18 | 17.12 | 0.426854E+09 | 549.53 | 08-JUN-13:09 | 24.18 | 17.12 |
July | 0.545151E+10 | 16336.35 | 23-JUL-13:32 | 21.33 | 16.14 | 0.399826E+09 | 549.50 | 12-JUL-13:50 | 21.33 | 16.14 |
August | 0.647676E+10 | 17198.76 | 06-AUG-13:13 | 17.33 | 13.63 | 0.448421E+09 | 549.50 | 15-AUG-09:09 | 16.00 | 13.59 |
September | 0.610602E+10 | 17821.99 | 24-SEP-13:22 | 20.00 | 15.13 | 0.393779E+09 | 549.98 | 27-SEP-13:00 | 22.00 | 13.55 |
October | 0.341794E+10 | 11305.34 | 01-OCT-12:13 | 13.33 | 9.85 | 0.367537E+09 | 549.74 | 03-OCT-13:00 | 14.00 | 9.41 |
November | 0.166196E+10 | 6684.83 | 11-NOV-13:33 | 9.00 | 7.15 | 0.336623E+09 | 549.49 | 03-NOV-13:00 | 9.00 | 7.15 |
December | 0.901113E+09 | 4916.00 | 18-DEC-13:30 | 8.00 | 5.46 | 0.315100E+09 | 549.49 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.422803E+11 | 0.450193E+10 | ||||||||
Minimum of Months | 0.901113E+09 | 3587.99 | 6.00 | 3.25 | 0.315100E+09 | 549.49 | 6.00 | 3.37 | ||
Maximum of Months | 0.647676E+10 | 17821.99 | 24.18 | 17.12 | 0.448421E+09 | 550.14 | 24.18 | 17.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479106E+09 | 1442.85 | 19-JAN-16:00 | 8.00 | 7.45 | 0.198235E+09 | 325.41 | 19-JAN-16:10 | 7.67 | 7.22 |
February | 0.696242E+09 | 2226.23 | 27-FEB-16:30 | 8.00 | 6.72 | 0.185407E+09 | 338.68 | 17-FEB-16:00 | 8.00 | 6.72 |
March | 0.100878E+10 | 2400.85 | 23-MAR-17:00 | 10.00 | 6.65 | 0.220520E+09 | 338.67 | 23-MAR-15:50 | 10.00 | 6.65 |
April | 0.244490E+10 | 12195.81 | 30-APR-16:12 | 24.00 | 12.95 | 0.227784E+09 | 347.86 | 14-APR-13:00 | 24.00 | 12.95 |
May | 0.300398E+10 | 11181.10 | 28-MAY-16:42 | 12.17 | 7.68 | 0.256710E+09 | 347.85 | 22-MAY-13:00 | 12.17 | 7.68 |
June | 0.370857E+10 | 12027.70 | 25-JUN-16:52 | 21.00 | 14.00 | 0.268400E+09 | 347.86 | 09-JUN-13:00 | 21.00 | 14.00 |
July | 0.398196E+10 | 13656.74 | 09-JUL-16:32 | 21.00 | 15.03 | 0.251945E+09 | 347.85 | 12-JUL-13:00 | 21.00 | 15.44 |
August | 0.376511E+10 | 12169.10 | 06-AUG-15:53 | 17.00 | 13.49 | 0.281080E+09 | 347.85 | 08-AUG-13:09 | 17.83 | 16.43 |
September | 0.282742E+10 | 9867.61 | 24-SEP-16:03 | 21.83 | 15.35 | 0.241348E+09 | 347.85 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.153074E+10 | 4822.44 | 03-OCT-15:40 | 14.00 | 8.96 | 0.217624E+09 | 347.83 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.744857E+09 | 1481.36 | 10-NOV-15:50 | 11.17 | 8.40 | 0.198661E+09 | 332.18 | 10-NOV-15:00 | 11.00 | 8.40 |
December | 0.273203E+09 | 1215.96 | 21-DEC-14:40 | 8.00 | 6.98 | 0.187934E+09 | 295.65 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.244649E+11 | 0.273565E+10 | ||||||||
Minimum of Months | 0.273203E+09 | 1215.96 | 8.00 | 6.65 | 0.185407E+09 | 295.65 | 7.67 | 6.65 | ||
Maximum of Months | 0.398196E+10 | 13656.74 | 24.00 | 15.35 | 0.281080E+09 | 347.86 | 24.00 | 16.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15212793.65 | 20555.34 | 02-JAN-06:02 | 1.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 15212793.65 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 15212793.65 | 20555.34 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325660E+10 | 10853.53 | 02-JAN-06:12 | 1.33 |
February | 0.224587E+10 | 9075.42 | 17-FEB-07:02 | -3.8 |
March | 0.199879E+10 | 8047.65 | 27-MAR-06:02 | 0.33 |
April | 0.790611E+09 | 4731.09 | 20-APR-05:02 | 1.17 |
May | 0.536099E+09 | 4145.31 | 03-MAY-05:02 | 3.50 |
June | 0.266288E+09 | 4056.14 | 01-JUN-05:03 | 6.50 |
July | 0.216232E+09 | 5141.85 | 24-JUL-05:03 | 13.00 |
August | 0.334762E+09 | 4003.99 | 20-AUG-08:13 | 16.33 |
September | 0.525804E+09 | 3986.21 | 20-SEP-05:02 | 6.00 |
October | 0.135943E+10 | 6460.30 | 23-OCT-06:01 | 4.00 |
November | 0.228764E+10 | 8621.94 | 20-NOV-07:02 | 1.00 |
December | 0.356136E+10 | 10397.33 | 26-DEC-06:12 | 1.93 |
Annual Sum or Average | 0.173795E+11 | |||
Minimum of Months | 0.216232E+09 | 3986.21 | -3.8 | |
Maximum of Months | 0.356136E+10 | 10853.53 | 16.33 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160691E+10 | 7361.37 | 02-JAN-07:11 | 1.67 |
February | 0.113053E+10 | 2853.20 | 27-FEB-14:30 | 8.50 |
March | 0.100816E+10 | 2735.20 | 06-MAR-07:02 | 4.33 |
April | 0.331234E+09 | 3874.31 | 30-APR-14:53 | 24.00 |
May | 0.180484E+09 | 3548.15 | 21-MAY-14:55 | 19.00 |
June | 20304518.64 | 2323.01 | 11-JUN-15:32 | 16.33 |
July | 28744487.10 | 3065.82 | 09-JUL-16:32 | 21.00 |
August | 22684322.32 | 3852.46 | 13-AUG-15:32 | 21.00 |
September | 72344620.13 | 4387.06 | 24-SEP-16:03 | 21.83 |
October | 0.585950E+09 | 3404.75 | 01-OCT-12:13 | 13.33 |
November | 0.106071E+10 | 3642.98 | 11-NOV-12:57 | 9.00 |
December | 0.164834E+10 | 5243.94 | 26-DEC-07:03 | 1.83 |
Annual Sum or Average | 0.769639E+10 | |||
Minimum of Months | 20304518.64 | 2323.01 | 1.67 | |
Maximum of Months | 0.164834E+10 | 7361.37 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123597E+10 | 4418.14 | 02-JAN-07:01 | 1.83 |
February | 0.841898E+09 | 2893.26 | 24-FEB-08:30 | 1.50 |
March | 0.846385E+09 | 3011.89 | 31-MAR-07:17 | 3.00 |
April | 0.112345E+09 | 3817.46 | 28-APR-05:02 | 6.17 |
May | 34271860.25 | 4361.79 | 30-MAY-05:03 | 8.17 |
June | 24655066.10 | 4193.66 | 06-JUN-05:03 | 8.42 |
July | 25868155.86 | 4077.01 | 03-JUL-05:03 | 9.17 |
August | 26416257.60 | 3860.39 | 28-AUG-05:02 | 9.17 |
September | 32847364.23 | 4416.96 | 20-SEP-05:02 | 6.00 |
October | 0.351670E+09 | 4652.58 | 05-OCT-05:02 | 4.00 |
November | 0.814165E+09 | 3209.94 | 17-NOV-08:09 | 2.17 |
December | 0.128646E+10 | 3136.34 | 26-DEC-08:20 | 1.33 |
Annual Sum or Average | 0.563295E+10 | |||
Minimum of Months | 24655066.10 | 2893.26 | 1.33 | |
Maximum of Months | 0.128646E+10 | 4652.58 | 9.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206440E+09 | 21792.30 | 02-JAN-06:01 | 1.17 |
February | 28325459.91 | 19182.75 | 27-FEB-07:01 | 6.00 |
March | 18198859.19 | 19255.38 | 06-MAR-07:01 | 4.33 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 443684.08 | 4436.84 | 30-OCT-06:02 | 6.83 |
November | 21324042.26 | 19264.13 | 27-NOV-07:01 | 4.00 |
December | 0.113585E+09 | 20121.92 | 26-DEC-06:01 | 1.92 |
Annual Sum or Average | 0.388317E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 0.206440E+09 | 21792.30 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109622E+10 | 27987.78 | 02-JAN-05:01 | 1.00 |
February | 0.472679E+09 | 25603.67 | 13-FEB-06:01 | -1.0 |
March | 0.347399E+09 | 25676.13 | 06-MAR-06:01 | 4.00 |
April | 13590566.91 | 23295.79 | 03-APR-06:01 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 83785946.02 | 23589.18 | 23-OCT-06:01 | 4.00 |
November | 0.405114E+09 | 25779.77 | 27-NOV-06:01 | 4.00 |
December | 0.114013E+10 | 27026.77 | 26-DEC-05:01 | 1.98 |
Annual Sum or Average | 0.355891E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.114013E+10 | 27987.78 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203105E+10 | 7768.58 | 02-JAN-05:01 | 1.00 |
February | 0.124234E+10 | 7579.46 | 13-FEB-05:02 | -1.0 |
March | 0.867412E+09 | 7320.10 | 06-MAR-05:03 | 3.83 |
April | 0.104194E+09 | 6686.29 | 01-APR-05:02 | 2.17 |
May | 12913057.03 | 6315.26 | 17-MAY-06:02 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 5528620.65 | 6291.59 | 21-SEP-06:02 | 5.33 |
October | 0.309444E+09 | 7038.04 | 23-OCT-05:01 | 3.17 |
November | 0.103458E+10 | 7484.28 | 20-NOV-05:02 | 0.67 |
December | 0.223315E+10 | 7888.92 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.784061E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.223315E+10 | 7888.92 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115011E+10 | 8396.45 | 09-JAN-05:01 | -2.1 |
February | 0.680844E+09 | 8072.41 | 13-FEB-05:02 | -1.0 |
March | 0.505578E+09 | 7545.08 | 04-MAR-06:01 | 3.00 |
April | 30983428.23 | 6929.27 | 01-APR-05:02 | 2.17 |
May | 5404476.23 | 6515.67 | 17-MAY-06:02 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 2981352.21 | 6615.20 | 21-SEP-06:02 | 5.33 |
October | 0.181473E+09 | 7399.35 | 23-OCT-05:01 | 3.17 |
November | 0.592430E+09 | 7956.01 | 20-NOV-05:02 | 0.67 |
December | 0.133096E+10 | 8549.39 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.448077E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.133096E+10 | 8549.39 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135646E+10 | 12818.32 | 09-JAN-05:01 | -2.1 |
February | 0.811321E+09 | 12096.03 | 13-FEB-05:02 | -1.0 |
March | 0.716518E+09 | 11489.95 | 13-MAR-05:01 | 2.08 |
April | 88255498.95 | 10786.04 | 01-APR-05:02 | 2.17 |
May | 24809464.61 | 9893.55 | 17-MAY-06:02 | 6.17 |
June | 508606.60 | 3390.71 | 08-JUN-06:03 | 7.50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 5106559.70 | 9721.02 | 21-SEP-06:02 | 5.33 |
October | 0.238017E+09 | 11064.97 | 23-OCT-05:01 | 3.17 |
November | 0.721447E+09 | 12059.25 | 20-NOV-05:02 | 0.67 |
December | 0.173514E+10 | 12827.94 | 11-DEC-05:01 | 3.00 |
Annual Sum or Average | 0.569758E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.173514E+10 | 12827.94 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122489E+10 | 8334.34 | 09-JAN-05:01 | -2.1 |
February | 0.714922E+09 | 8033.43 | 13-FEB-05:02 | -1.0 |
March | 0.548292E+09 | 7396.33 | 13-MAR-05:01 | 2.08 |
April | 67470503.03 | 6921.20 | 01-APR-05:02 | 2.17 |
May | 17491569.88 | 6499.22 | 17-MAY-06:02 | 6.17 |
June | 272262.04 | 1815.08 | 08-JUN-06:03 | 7.50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 6143356.26 | 6511.67 | 20-SEP-06:02 | 6.17 |
October | 0.206521E+09 | 7178.40 | 23-OCT-05:01 | 3.17 |
November | 0.653925E+09 | 7852.21 | 27-NOV-05:02 | 4.00 |
December | 0.146430E+10 | 8507.34 | 18-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.490423E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.146430E+10 | 8507.34 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110588E+10 | 6061.07 | 02-JAN-05:01 | 1.00 |
February | 0.493278E+09 | 5424.41 | 13-FEB-06:01 | -1.0 |
March | 0.304516E+09 | 5349.67 | 06-MAR-06:01 | 4.00 |
April | 19738539.81 | 5013.74 | 03-APR-06:01 | 3.17 |
May | 19000.92 | 190.01 | 17-MAY-06:02 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 24118012.86 | 5013.22 | 23-OCT-06:01 | 4.00 |
November | 0.194451E+09 | 5257.45 | 20-NOV-06:01 | -0.7 |
December | 0.841928E+09 | 5558.79 | 26-DEC-06:01 | 1.92 |
Annual Sum or Average | 0.298392E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.110588E+10 | 6061.07 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.586709E+09 | 6172.43 | 02-JAN-05:01 | 1.00 |
February | 0.235736E+09 | 5413.62 | 03-FEB-06:02 | 2.83 |
March | 0.170783E+09 | 5432.69 | 06-MAR-06:01 | 4.00 |
April | 2928947.15 | 5152.23 | 01-APR-06:03 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 16000717.47 | 5134.67 | 28-OCT-06:03 | 6.50 |
November | 0.111070E+09 | 5322.73 | 30-NOV-06:01 | 4.00 |
December | 0.511524E+09 | 5677.31 | 26-DEC-06:01 | 1.92 |
Annual Sum or Average | 0.163475E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.586709E+09 | 6172.43 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.433557E+10 | 11932.91 | 10-JAN-08:00 | -6.0 |
February | 0.310189E+10 | 11715.17 | 17-FEB-07:10 | -3.8 |
March | 0.380578E+10 | 11044.54 | 08-MAR-07:10 | -0.5 |
April | 0.146961E+10 | 9598.43 | 03-APR-06:10 | 3.17 |
May | 0.142601E+10 | 8964.13 | 05-MAY-06:10 | 6.17 |
June | 0.769116E+09 | 8359.58 | 08-JUN-06:10 | 7.50 |
July | 0.350186E+09 | 7756.20 | 05-JUL-06:10 | 9.50 |
August | 0.333588E+09 | 7816.44 | 24-AUG-06:10 | 8.83 |
September | 0.557851E+09 | 8536.55 | 21-SEP-06:10 | 5.33 |
October | 0.165501E+10 | 9302.55 | 23-OCT-06:10 | 4.00 |
November | 0.290618E+10 | 11151.66 | 29-NOV-07:10 | -1.0 |
December | 0.428704E+10 | 11291.49 | 29-DEC-17:10 | -2.0 |
Annual Sum or Average | 0.249978E+11 | |||
Minimum of Months | 0.333588E+09 | 7756.20 | -6.0 | |
Maximum of Months | 0.433557E+10 | 11932.91 | 9.50 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.625531E+09 | 6151.65 | 02-JAN-05:01 | 1.00 |
February | 0.216353E+09 | 5370.36 | 21-FEB-06:01 | 4.75 |
March | 0.179598E+09 | 5377.00 | 20-MAR-05:02 | 5.00 |
April | 9006233.12 | 5046.20 | 01-APR-06:03 | 3.17 |
May | 807259.66 | 2494.47 | 05-MAY-06:02 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 18540906.47 | 5108.64 | 28-OCT-06:03 | 6.50 |
November | 0.125233E+09 | 5236.31 | 30-NOV-06:01 | 4.00 |
December | 0.579916E+09 | 5538.05 | 26-DEC-06:01 | 1.92 |
Annual Sum or Average | 0.175499E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.625531E+09 | 6151.65 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.813300E+09 | 6789.95 | 02-JAN-05:01 | 1.00 |
February | 0.325322E+09 | 6125.81 | 13-FEB-06:01 | -1.0 |
March | 0.192299E+09 | 6024.44 | 06-MAR-06:01 | 4.00 |
April | 7968570.40 | 5620.40 | 03-APR-06:01 | 3.17 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 35544017.35 | 5627.89 | 23-OCT-06:01 | 4.00 |
November | 0.243353E+09 | 6064.34 | 27-NOV-06:01 | 4.00 |
December | 0.847234E+09 | 6411.69 | 26-DEC-05:01 | 1.98 |
Annual Sum or Average | 0.246502E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.847234E+09 | 6789.95 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485009E+09 | 6173.88 | 02-JAN-05:01 | 1.00 |
February | 0.189303E+09 | 5291.98 | 09-FEB-06:01 | 2.17 |
March | 0.118262E+09 | 5176.93 | 14-MAR-05:01 | 2.00 |
April | 3800103.87 | 5056.38 | 01-APR-06:03 | 3.17 |
May | 83782.16 | 837.82 | 17-MAY-06:02 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 27198443.83 | 5050.94 | 20-OCT-06:03 | 11.17 |
November | 0.153179E+09 | 5184.36 | 29-NOV-06:03 | -1.0 |
December | 0.547829E+09 | 5850.34 | 26-DEC-05:01 | 1.98 |
Annual Sum or Average | 0.152466E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.547829E+09 | 6173.88 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.496202E+09 | 9046.64 | 02-JAN-05:01 | 1.00 |
February | 0.184212E+09 | 8057.08 | 18-FEB-06:01 | -1.2 |
March | 0.151641E+09 | 7883.13 | 13-MAR-05:01 | 2.08 |
April | 8147966.74 | 7506.61 | 12-APR-06:01 | 3.17 |
May | 395145.70 | 3135.80 | 05-MAY-06:02 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 31269530.68 | 7637.53 | 20-OCT-06:03 | 11.17 |
November | 0.160592E+09 | 7961.90 | 13-NOV-06:01 | 4.17 |
December | 0.605267E+09 | 8375.36 | 26-DEC-06:01 | 1.92 |
Annual Sum or Average | 0.163773E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.2 | |
Maximum of Months | 0.605267E+09 | 9046.64 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.489189E+09 | 6145.66 | 02-JAN-05:01 | 1.00 |
February | 0.184564E+09 | 5187.20 | 27-FEB-06:03 | 6.00 |
March | 0.124855E+09 | 5066.32 | 04-MAR-06:01 | 3.00 |
April | 7093550.89 | 4945.35 | 01-APR-06:03 | 3.17 |
May | 590342.47 | 3456.97 | 05-MAY-06:02 | 6.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 27823124.70 | 5024.88 | 20-OCT-06:03 | 11.17 |
November | 0.163698E+09 | 5123.25 | 27-NOV-06:01 | 4.00 |
December | 0.569543E+09 | 5819.30 | 26-DEC-05:01 | 1.98 |
Annual Sum or Average | 0.156736E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.569543E+09 | 6145.66 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.608519E+09 | 889.66 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.493993E+09 | 845.33 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.537010E+09 | 769.99 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.449817E+09 | 673.83 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.467050E+09 | 464.83 | 04-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.458077E+09 | 424.37 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.432314E+09 | 462.72 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.494140E+09 | 572.81 | 22-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.463456E+09 | 623.31 | 08-SEP-07:30 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.535635E+09 | 885.62 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.598767E+09 | 889.66 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.633193E+09 | 889.66 | 01-DEC-15:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.617197E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.432314E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.633193E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370683E+09 | 563.23 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.304826E+09 | 532.77 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.336670E+09 | 473.37 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.284443E+09 | 403.29 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.296938E+09 | 290.96 | 15-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.291461E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.275045E+09 | 291.06 | 07-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.313096E+09 | 310.73 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.290870E+09 | 358.67 | 08-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.332694E+09 | 560.50 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.367554E+09 | 563.23 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.383904E+09 | 563.23 | 01-DEC-15:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.384818E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.275045E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.383904E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.572578E+09 | 889.66 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.473521E+09 | 843.21 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.527942E+09 | 764.44 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.450417E+09 | 670.26 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.469832E+09 | 466.37 | 04-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.461032E+09 | 424.37 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.435362E+09 | 464.11 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.496007E+09 | 567.03 | 22-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.460425E+09 | 607.40 | 08-SEP-07:30 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.519892E+09 | 885.45 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.568189E+09 | 889.66 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.594025E+09 | 889.66 | 01-DEC-15:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.602922E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.435362E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.594025E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.373600E+09 | 563.19 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.306535E+09 | 535.28 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.338259E+09 | 492.87 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.285268E+09 | 436.01 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.296737E+09 | 305.15 | 04-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.290853E+09 | 292.40 | 14-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.274665E+09 | 302.19 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.314237E+09 | 383.29 | 22-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293595E+09 | 438.50 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.335493E+09 | 560.63 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.369009E+09 | 563.19 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.389820E+09 | 563.19 | 01-DEC-15:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.386807E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.274665E+09 | 292.40 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.389820E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.604664E+09 | 889.66 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.491187E+09 | 843.37 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.534691E+09 | 764.57 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.449241E+09 | 664.13 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.466623E+09 | 460.50 | 04-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.457735E+09 | 424.37 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.431971E+09 | 458.29 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.493534E+09 | 558.57 | 22-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.462342E+09 | 611.36 | 08-SEP-07:30 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.533215E+09 | 885.44 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.594604E+09 | 889.66 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.628714E+09 | 889.66 | 01-DEC-15:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.614852E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.431971E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.628714E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.369345E+09 | 563.23 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.303766E+09 | 531.64 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.335787E+09 | 469.87 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.284190E+09 | 397.01 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.296650E+09 | 288.42 | 15-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.291184E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.274828E+09 | 288.50 | 07-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.312787E+09 | 308.94 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.290489E+09 | 350.95 | 08-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.331636E+09 | 560.40 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.365881E+09 | 563.23 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.382311E+09 | 563.23 | 01-DEC-15:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.383885E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.274828E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.382311E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.571017E+09 | 889.66 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.472278E+09 | 841.12 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.526796E+09 | 758.69 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.449897E+09 | 660.37 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.469320E+09 | 462.13 | 04-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.460574E+09 | 424.37 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.434920E+09 | 459.77 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.495350E+09 | 552.49 | 22-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.459747E+09 | 594.58 | 08-SEP-07:30 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.518656E+09 | 885.27 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.565995E+09 | 889.66 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.591688E+09 | 889.66 | 01-DEC-15:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.601624E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.434920E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.591688E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.372149E+09 | 563.19 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.305379E+09 | 534.28 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.337295E+09 | 490.36 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.284856E+09 | 431.50 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.296450E+09 | 303.25 | 04-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.290564E+09 | 289.96 | 14-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.274424E+09 | 300.15 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.313837E+09 | 376.98 | 22-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.292961E+09 | 434.13 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.334415E+09 | 560.54 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.367151E+09 | 563.19 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.387869E+09 | 563.19 | 01-DEC-15:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.385735E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.274424E+09 | 289.96 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.387869E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.608516E+09 | 889.66 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.493979E+09 | 845.33 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.537008E+09 | 769.99 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.449817E+09 | 673.81 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.467050E+09 | 464.83 | 04-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.458077E+09 | 424.37 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.432314E+09 | 462.71 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.494139E+09 | 572.79 | 22-AUG-07:30 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.463455E+09 | 623.29 | 08-SEP-07:30 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.535632E+09 | 885.62 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.598762E+09 | 889.66 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.633189E+09 | 889.66 | 01-DEC-15:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.617194E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.432314E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.633189E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.370682E+09 | 563.23 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.304825E+09 | 532.76 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.336669E+09 | 473.37 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.284442E+09 | 403.28 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.296938E+09 | 290.96 | 15-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.291461E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.275045E+09 | 291.05 | 07-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.313095E+09 | 310.72 | 22-AUG-07:30 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.290869E+09 | 358.66 | 08-SEP-07:30 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.332692E+09 | 560.50 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.367552E+09 | 563.23 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.383902E+09 | 563.23 | 01-DEC-15:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.384817E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.275045E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.383902E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.572577E+09 | 889.66 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.473520E+09 | 843.21 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.527941E+09 | 764.43 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.450417E+09 | 670.25 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.469832E+09 | 466.36 | 04-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.461032E+09 | 424.37 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.435361E+09 | 464.10 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.496006E+09 | 567.01 | 22-AUG-07:30 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.460425E+09 | 607.38 | 08-SEP-07:30 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.519890E+09 | 885.45 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.568186E+09 | 889.66 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.594024E+09 | 889.66 | 01-DEC-15:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.602921E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.435361E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.594024E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.373599E+09 | 563.19 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.306534E+09 | 535.28 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.338257E+09 | 492.86 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.285268E+09 | 436.00 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.296737E+09 | 305.14 | 04-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.290853E+09 | 292.40 | 14-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.274664E+09 | 302.19 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.314236E+09 | 383.28 | 22-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293595E+09 | 438.49 | 08-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.335492E+09 | 560.63 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.369007E+09 | 563.19 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.389818E+09 | 563.19 | 01-DEC-15:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.386806E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.274664E+09 | 292.40 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.389818E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.608519E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56372841.75 |
February | 0.901968E+09 | 0.493993E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80779500.85 |
March | 0.107774E+10 | 0.537010E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48037080.24 |
April | 0.956342E+09 | 0.449817E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64476689.21 |
May | 0.103597E+10 | 0.467050E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160234E+09 |
June | 0.103308E+10 | 0.458077E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77582.02 | 0.126830E+09 |
July | 0.959235E+09 | 0.432314E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 358453.02 | 0.121231E+09 |
August | 0.107774E+10 | 0.494140E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50485.17 | 86220654.89 |
September | 0.956342E+09 | 0.463456E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87483129.90 |
October | 0.994195E+09 | 0.535635E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87514750.26 |
November | 0.984487E+09 | 0.598767E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104502E+09 |
December | 0.959235E+09 | 0.633193E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141931E+09 |
Annual Sum or Average | 0.119305E+11 | 0.617197E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 486520.21 | 0.116561E+10 |
Minimum of Months | 0.901968E+09 | 0.432314E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48037080.24 |
Maximum of Months | 0.107774E+10 | 0.633193E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 358453.02 | 0.160234E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.370683E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37970220.92 |
February | 0.571020E+09 | 0.304826E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54480579.24 |
March | 0.682301E+09 | 0.336670E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32327337.82 |
April | 0.605444E+09 | 0.284443E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44841658.54 |
May | 0.655854E+09 | 0.296938E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109423E+09 |
June | 0.654023E+09 | 0.291461E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51722.10 | 85678210.46 |
July | 0.607275E+09 | 0.275045E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 253532.54 | 83129186.03 |
August | 0.682301E+09 | 0.313096E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33657.35 | 59335569.59 |
September | 0.605444E+09 | 0.290870E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61356911.67 |
October | 0.629407E+09 | 0.332694E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59507012.18 |
November | 0.623262E+09 | 0.367554E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70117227.49 |
December | 0.607275E+09 | 0.383904E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94807843.96 |
Annual Sum or Average | 0.755301E+10 | 0.384818E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 338911.99 | 0.792975E+09 |
Minimum of Months | 0.571020E+09 | 0.275045E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32327337.82 |
Maximum of Months | 0.682301E+09 | 0.383904E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 253532.54 | 0.109423E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.572578E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59751701.10 |
February | 0.901968E+09 | 0.473521E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85444106.65 |
March | 0.107774E+10 | 0.527942E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49487400.87 |
April | 0.956342E+09 | 0.450417E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68472870.71 |
May | 0.103597E+10 | 0.469832E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164491E+09 |
June | 0.103308E+10 | 0.461032E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77579.38 | 0.128030E+09 |
July | 0.959235E+09 | 0.435362E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 369000.71 | 0.124446E+09 |
August | 0.107774E+10 | 0.496007E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50484.58 | 90367436.14 |
September | 0.956342E+09 | 0.460425E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94535301.96 |
October | 0.994195E+09 | 0.519892E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93656454.44 |
November | 0.984487E+09 | 0.568189E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109481E+09 |
December | 0.959235E+09 | 0.594025E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146069E+09 |
Annual Sum or Average | 0.119305E+11 | 0.602922E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 497064.67 | 0.121423E+10 |
Minimum of Months | 0.901968E+09 | 0.435362E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49487400.87 |
Maximum of Months | 0.107774E+10 | 0.594025E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 369000.71 | 0.164491E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.373600E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37909110.90 |
February | 0.570983E+09 | 0.306535E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54801202.69 |
March | 0.682256E+09 | 0.338259E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32144622.41 |
April | 0.605404E+09 | 0.285268E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44184073.66 |
May | 0.655811E+09 | 0.296737E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110314E+09 |
June | 0.653980E+09 | 0.290853E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51718.07 | 86972102.68 |
July | 0.607235E+09 | 0.274665E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 213359.77 | 84300776.69 |
August | 0.682256E+09 | 0.314237E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33659.06 | 59911684.00 |
September | 0.605404E+09 | 0.293595E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60318477.61 |
October | 0.629366E+09 | 0.335493E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59596471.65 |
November | 0.623221E+09 | 0.369009E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70091417.19 |
December | 0.607235E+09 | 0.389820E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94577361.77 |
Annual Sum or Average | 0.755252E+10 | 0.386807E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 298736.90 | 0.795121E+09 |
Minimum of Months | 0.570983E+09 | 0.274665E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32144622.41 |
Maximum of Months | 0.682256E+09 | 0.389820E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 213359.77 | 0.110314E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.604664E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31803013.47 |
February | 0.901968E+09 | 0.491187E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45727536.50 |
March | 0.107774E+10 | 0.534691E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26469518.55 |
April | 0.956342E+09 | 0.449241E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8726.46 | 34476099.70 |
May | 0.103597E+10 | 0.466623E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 86756468.67 |
June | 0.103308E+10 | 0.457735E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43164.58 | 68111518.63 |
July | 0.959235E+09 | 0.431971E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 224142.70 | 65170488.48 |
August | 0.107774E+10 | 0.493534E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28098.08 | 46361929.06 |
September | 0.956342E+09 | 0.462342E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49004374.42 |
October | 0.994195E+09 | 0.533215E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50527911.05 |
November | 0.984487E+09 | 0.594604E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61100394.65 |
December | 0.959235E+09 | 0.628714E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82502951.20 |
Annual Sum or Average | 0.119305E+11 | 0.614852E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 304132.51 | 0.648012E+09 |
Minimum of Months | 0.901968E+09 | 0.431971E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26469518.55 |
Maximum of Months | 0.107774E+10 | 0.628714E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 224142.70 | 86756468.67 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.369345E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21490428.32 |
February | 0.571020E+09 | 0.303766E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30946158.69 |
March | 0.682301E+09 | 0.335787E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17871115.42 |
April | 0.605444E+09 | 0.284190E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24815332.63 |
May | 0.655854E+09 | 0.296650E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | 61242082.79 |
June | 0.654023E+09 | 0.291184E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28407.29 | 47253567.83 |
July | 0.607275E+09 | 0.274828E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 141114.38 | 46143189.53 |
August | 0.682301E+09 | 0.312787E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18422.24 | 33238243.50 |
September | 0.605444E+09 | 0.290489E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35408452.63 |
October | 0.629407E+09 | 0.331636E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34835418.59 |
November | 0.623262E+09 | 0.365881E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41128708.01 |
December | 0.607275E+09 | 0.382311E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55056582.15 |
Annual Sum or Average | 0.755301E+10 | 0.383885E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 187944.37 | 0.449429E+09 |
Minimum of Months | 0.571020E+09 | 0.274828E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17871115.42 |
Maximum of Months | 0.682301E+09 | 0.382311E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 141114.38 | 61242082.79 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.571017E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622276E+10 |
February | 0.901968E+09 | 0.472278E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534323E+10 |
March | 0.107774E+10 | 0.526796E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597054E+10 |
April | 0.956342E+09 | 0.449897E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442608E+10 |
May | 0.103597E+10 | 0.469320E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.11 | 0.454812E+10 |
June | 0.103308E+10 | 0.460574E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19633816.45 | 0.326498E+10 |
July | 0.959235E+09 | 0.434920E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32911810.35 | 0.243370E+10 |
August | 0.107774E+10 | 0.495350E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14742465.69 | 0.255531E+10 |
September | 0.956342E+09 | 0.459747E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302800E+10 |
October | 0.994195E+09 | 0.518656E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446247E+10 |
November | 0.984487E+09 | 0.565995E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536421E+10 |
December | 0.959235E+09 | 0.591688E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581196E+10 |
Annual Sum or Average | 0.119305E+11 | 0.601624E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67288227.60 | 0.534314E+11 |
Minimum of Months | 0.901968E+09 | 0.434920E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243370E+10 |
Maximum of Months | 0.107774E+10 | 0.591688E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32911810.35 | 0.622276E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.372149E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21419448.19 |
February | 0.570983E+09 | 0.305379E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31145149.94 |
March | 0.682256E+09 | 0.337295E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17726213.43 |
April | 0.605404E+09 | 0.284856E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24427855.67 |
May | 0.655811E+09 | 0.296450E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 | 61601894.82 |
June | 0.653980E+09 | 0.290564E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28407.81 | 48285588.83 |
July | 0.607235E+09 | 0.274424E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114389.92 | 46806400.57 |
August | 0.682256E+09 | 0.313837E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18423.54 | 33599142.72 |
September | 0.605404E+09 | 0.292961E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34767577.26 |
October | 0.629366E+09 | 0.334415E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34694906.95 |
November | 0.623221E+09 | 0.367151E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41004034.23 |
December | 0.607235E+09 | 0.387869E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54873492.55 |
Annual Sum or Average | 0.755252E+10 | 0.385735E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 161221.74 | 0.450352E+09 |
Minimum of Months | 0.570983E+09 | 0.274424E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17726213.43 |
Maximum of Months | 0.682256E+09 | 0.387869E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114389.92 | 61601894.82 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.608516E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50014838.26 |
February | 0.901968E+09 | 0.493979E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72273600.72 |
March | 0.107774E+10 | 0.537008E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42365080.12 |
April | 0.956342E+09 | 0.449817E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56741227.54 |
May | 0.103597E+10 | 0.467050E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140643E+09 |
June | 0.103308E+10 | 0.458077E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65640.62 | 0.109819E+09 |
July | 0.959235E+09 | 0.432314E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 318538.40 | 0.105018E+09 |
August | 0.107774E+10 | 0.494139E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42635.59 | 75206184.10 |
September | 0.956342E+09 | 0.463455E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78158447.71 |
October | 0.994195E+09 | 0.535632E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79388174.70 |
November | 0.984487E+09 | 0.598762E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94502455.05 |
December | 0.959235E+09 | 0.633189E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127513E+09 |
Annual Sum or Average | 0.119305E+11 | 0.617194E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 426814.61 | 0.103164E+10 |
Minimum of Months | 0.901968E+09 | 0.432314E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42365080.12 |
Maximum of Months | 0.107774E+10 | 0.633189E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 318538.40 | 0.140643E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.370682E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33655038.00 |
February | 0.421807E+09 | 0.304825E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48646057.88 |
March | 0.502994E+09 | 0.336669E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28367824.25 |
April | 0.447140E+09 | 0.284442E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39033815.00 |
May | 0.484071E+09 | 0.296938E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95276802.14 |
June | 0.482240E+09 | 0.291461E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43759.16 | 73812871.91 |
July | 0.448971E+09 | 0.275045E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 225580.41 | 71510189.67 |
August | 0.502994E+09 | 0.313095E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28423.55 | 51301731.82 |
September | 0.447140E+09 | 0.290869E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54043141.14 |
October | 0.465148E+09 | 0.332692E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53519232.56 |
November | 0.460569E+09 | 0.367552E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63225485.82 |
December | 0.448971E+09 | 0.383902E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85098724.90 |
Annual Sum or Average | 0.557719E+10 | 0.384817E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 297763.12 | 0.697491E+09 |
Minimum of Months | 0.421807E+09 | 0.275045E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28367824.25 |
Maximum of Months | 0.502994E+09 | 0.383902E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 225580.41 | 95276802.14 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.572577E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53077418.60 |
February | 0.901968E+09 | 0.473520E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76232223.81 |
March | 0.107774E+10 | 0.527941E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43618741.89 |
April | 0.956342E+09 | 0.450417E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59770463.64 |
May | 0.103597E+10 | 0.469832E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143855E+09 |
June | 0.103308E+10 | 0.461032E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65638.29 | 0.110931E+09 |
July | 0.959235E+09 | 0.435361E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 320580.90 | 0.107795E+09 |
August | 0.107774E+10 | 0.496006E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42634.75 | 78709961.32 |
September | 0.956342E+09 | 0.460425E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83436967.79 |
October | 0.994195E+09 | 0.519890E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84053270.29 |
November | 0.984487E+09 | 0.568186E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98794809.38 |
December | 0.959235E+09 | 0.594024E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131116E+09 |
Annual Sum or Average | 0.119305E+11 | 0.602921E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 428853.94 | 0.107139E+10 |
Minimum of Months | 0.901968E+09 | 0.435361E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43618741.89 |
Maximum of Months | 0.107774E+10 | 0.594024E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 320580.90 | 0.143855E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.373599E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33622302.05 |
February | 0.570983E+09 | 0.306534E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48927846.96 |
March | 0.682256E+09 | 0.338257E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28287513.72 |
April | 0.605404E+09 | 0.285268E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38758503.92 |
May | 0.655811E+09 | 0.296737E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96530856.24 |
June | 0.653980E+09 | 0.290853E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43754.62 | 75354939.59 |
July | 0.607235E+09 | 0.274664E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 176252.67 | 73047002.52 |
August | 0.682256E+09 | 0.314236E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28425.56 | 52309238.55 |
September | 0.605404E+09 | 0.293595E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53691182.34 |
October | 0.629366E+09 | 0.335492E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53729371.76 |
November | 0.623221E+09 | 0.369007E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63224151.55 |
December | 0.607235E+09 | 0.389818E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84919907.25 |
Annual Sum or Average | 0.755252E+10 | 0.386806E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 248432.85 | 0.702403E+09 |
Minimum of Months | 0.570983E+09 | 0.274664E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28287513.72 |
Maximum of Months | 0.682256E+09 | 0.389818E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 176252.67 | 96530856.24 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69370670.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101247E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58081475.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77388196.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191350E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48094.36 | 0.147638E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332806.05 | 0.142349E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33824.59 | 0.104131E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109892E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112469E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134395E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179332E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414725.01 | 0.142764E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58081475.65 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332806.05 | 0.191350E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84559513.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123509E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71185745.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96863381.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240863E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61724.88 | 0.187411E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439471.33 | 0.180144E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44273.03 | 0.131463E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136340E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136598E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162211E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217077E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 545469.24 | 0.176822E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71185745.01 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439471.33 | 0.240863E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85085787.83 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122682E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73461999.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102803E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249801E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19872.65 | 0.197582E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253558.13 | 0.190781E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22591.95 | 0.136320E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137901E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134160E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156855E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211409E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296022.72 | 0.179884E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73461999.22 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253558.13 | 0.249801E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 178.13 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 845.33 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 184.18 | 08-FEB-22:05 |
March | 1306.65 | 01-MAR-10:09 | 769.99 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 184.12 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 673.83 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 197.08 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 464.83 | 04-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 308.21 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 | 13-JUN-15:30 | 224.97 | 05-JUN-21:50 |
July | 1306.65 | 03-JUL-09:09 | 462.72 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 | 22-JUL-19:10 | 208.98 | 30-JUL-18:43 |
August | 1306.65 | 01-AUG-09:09 | 572.81 | 22-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 14-AUG-16:50 | 147.92 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 623.31 | 08-SEP-07:30 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 186.03 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 885.62 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 217.92 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 206.73 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-15:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 348.66 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.92 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 | 348.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 118.51 | 08-JAN-08:00 |
February | 827.22 | 01-FEB-10:09 | 532.77 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 122.68 | 08-FEB-22:05 |
March | 827.22 | 01-MAR-10:09 | 473.37 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 122.67 | 27-MAR-21:05 |
April | 827.22 | 03-APR-09:09 | 403.29 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 131.23 | 23-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 290.96 | 15-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 203.35 | 04-MAY-23:00 |
June | 827.22 | 01-JUN-09:09 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 13-JUN-15:30 | 175.14 | 18-JUN-10:13 |
July | 827.22 | 03-JUL-09:09 | 291.06 | 07-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.25 | 22-JUL-19:10 | 140.51 | 30-JUL-18:43 |
August | 827.22 | 01-AUG-09:09 | 310.73 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 | 14-AUG-16:50 | 96.31 | 22-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 358.67 | 08-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 124.79 | 06-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 560.50 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 144.41 | 20-OCT-22:00 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 136.72 | 25-NOV-05:00 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 231.11 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.31 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.25 | 231.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 183.00 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 843.21 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 185.26 | 05-FEB-14:00 |
March | 1306.65 | 01-MAR-10:09 | 764.44 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 184.15 | 27-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 670.26 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 215.73 | 16-APR-12:00 |
May | 1306.65 | 01-MAY-09:09 | 466.37 | 04-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 307.45 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 | 13-JUN-15:30 | 246.68 | 18-JUN-16:00 |
July | 1306.65 | 03-JUL-09:09 | 464.11 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 | 22-JUL-19:10 | 224.88 | 30-JUL-18:43 |
August | 1306.65 | 01-AUG-09:09 | 567.03 | 22-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 14-AUG-16:50 | 150.62 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 607.40 | 08-SEP-07:30 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 188.96 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 885.45 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 230.90 | 01-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 209.54 | 26-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-15:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 353.61 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.62 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 | 353.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 118.44 | 08-JAN-08:00 |
February | 827.17 | 01-FEB-10:09 | 535.28 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 123.10 | 08-FEB-22:05 |
March | 827.17 | 01-MAR-10:09 | 492.87 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 122.71 | 27-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 436.01 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 130.67 | 23-APR-22:00 |
May | 827.17 | 01-MAY-09:09 | 305.15 | 04-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 204.48 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 292.40 | 14-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 13-JUN-15:30 | 179.95 | 18-JUN-16:00 |
July | 827.17 | 03-JUL-09:09 | 302.19 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | 22-JUL-19:08 | 182.32 | 30-JUL-18:40 |
August | 827.17 | 01-AUG-09:09 | 383.29 | 22-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 | 14-AUG-16:50 | 102.64 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 438.50 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 124.48 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 560.63 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 146.89 | 20-OCT-22:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 136.69 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 230.49 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 292.40 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.64 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 | 230.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 107.88 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 843.37 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 98.52 | 08-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 764.57 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 99.06 | 27-MAR-21:30 |
April | 1306.65 | 03-APR-09:09 | 664.13 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.16 | 30-APR-17:50 | 110.72 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 460.50 | 04-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 173.31 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.09 | 13-JUN-15:30 | 121.04 | 05-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 458.29 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 22-JUL-19:10 | 107.80 | 11-JUL-02:00 |
August | 1306.65 | 01-AUG-09:09 | 558.57 | 22-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 14-AUG-16:50 | 79.77 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 611.36 | 08-SEP-07:30 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 108.24 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 885.44 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 126.45 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 125.55 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-15:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 196.25 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.77 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 196.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 72.41 | 08-JAN-08:00 |
February | 827.22 | 01-FEB-10:09 | 531.64 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 65.65 | 08-FEB-22:05 |
March | 827.22 | 01-MAR-10:09 | 469.87 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 66.08 | 27-MAR-21:30 |
April | 827.22 | 03-APR-09:09 | 397.01 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 76.01 | 23-APR-22:00 |
May | 827.22 | 01-MAY-09:09 | 288.42 | 15-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 115.66 | 04-MAY-23:00 |
June | 827.22 | 01-JUN-09:09 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 | 13-JUN-15:30 | 90.97 | 18-JUN-10:53 |
July | 827.22 | 03-JUL-09:09 | 288.50 | 07-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 | 22-JUL-19:10 | 75.06 | 11-JUL-02:00 |
August | 827.22 | 01-AUG-09:09 | 308.94 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 14-AUG-16:50 | 54.88 | 22-AUG-21:10 |
September | 827.22 | 01-SEP-09:09 | 350.95 | 08-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 76.37 | 06-SEP-04:00 |
October | 827.22 | 02-OCT-09:09 | 560.40 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 86.55 | 01-OCT-24:00 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 83.16 | 26-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 130.29 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.88 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 | 130.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 31502.47 | 10-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 841.12 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 31207.36 | 17-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 758.69 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 26511.16 | 08-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 660.37 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 21890.38 | 20-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 462.13 | 04-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 | 22-MAY-15:00 | 19686.06 | 01-MAY-06:02 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3672.51 | 13-JUN-17:00 | 15926.55 | 08-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 459.77 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6097.97 | 21-JUL-17:00 | 14451.73 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 552.49 | 22-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3678.24 | 14-AUG-17:00 | 15440.18 | 24-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 594.58 | 08-SEP-07:30 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 19571.09 | 21-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 885.27 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 22445.96 | 04-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 27496.20 | 29-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-15:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 29751.16 | 29-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14451.73 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6097.97 | 31502.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 71.92 | 08-JAN-08:00 |
February | 827.17 | 01-FEB-10:09 | 534.28 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 66.22 | 08-FEB-22:10 |
March | 827.17 | 01-MAR-10:09 | 490.36 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 65.86 | 27-MAR-21:30 |
April | 827.17 | 03-APR-09:09 | 431.50 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 75.12 | 23-APR-22:00 |
May | 827.17 | 01-MAY-09:09 | 303.25 | 04-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 116.78 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 289.96 | 14-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 | 13-JUN-15:30 | 93.54 | 18-JUN-16:00 |
July | 827.17 | 03-JUL-09:09 | 300.15 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 | 22-JUL-19:08 | 92.08 | 30-JUL-18:30 |
August | 827.17 | 01-AUG-09:09 | 376.98 | 22-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 14-AUG-16:50 | 59.01 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 434.13 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 74.35 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 560.54 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 87.48 | 01-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 82.78 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 129.84 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 289.96 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.01 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 | 129.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 167.85 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 845.33 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 156.18 | 08-FEB-22:10 |
March | 1306.65 | 01-MAR-10:09 | 769.99 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 157.72 | 27-MAR-21:30 |
April | 1306.65 | 03-APR-09:09 | 673.81 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 179.05 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 464.83 | 04-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 276.13 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 13-JUN-15:30 | 194.65 | 05-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 462.71 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 | 22-JUL-19:10 | 175.88 | 30-JUL-18:50 |
August | 1306.65 | 01-AUG-09:09 | 572.79 | 22-AUG-07:30 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 14-AUG-16:50 | 128.85 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 623.29 | 08-SEP-07:30 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 170.59 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 885.62 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 196.86 | 20-OCT-22:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 191.80 | 25-NOV-05:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-15:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 304.90 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.85 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 | 304.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 563.23 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 111.68 | 08-JAN-08:00 |
February | 805.43 | 01-FEB-08:09 | 532.76 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 103.70 | 08-FEB-22:10 |
March | 805.43 | 01-MAR-08:09 | 473.37 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 104.61 | 27-MAR-21:30 |
April | 805.43 | 03-APR-07:10 | 403.28 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 119.16 | 23-APR-22:00 |
May | 805.43 | 01-MAY-07:10 | 290.96 | 15-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 181.65 | 04-MAY-23:00 |
June | 805.43 | 01-JUN-07:10 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 13-JUN-15:30 | 146.48 | 18-JUN-10:23 |
July | 805.43 | 03-JUL-07:10 | 291.05 | 07-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 22-JUL-19:10 | 117.76 | 30-JUL-18:50 |
August | 805.43 | 01-AUG-07:10 | 310.72 | 22-AUG-07:30 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | 14-AUG-16:50 | 83.48 | 22-AUG-21:10 |
September | 805.43 | 01-SEP-07:10 | 358.66 | 08-SEP-07:30 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 114.05 | 06-SEP-04:00 |
October | 805.43 | 02-OCT-07:10 | 560.50 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 131.55 | 01-OCT-24:00 |
November | 805.43 | 01-NOV-07:10 | 563.23 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 126.73 | 25-NOV-05:00 |
December | 805.43 | 01-DEC-08:09 | 563.23 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 201.79 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.48 | |||||
Maximum of Months | 805.43 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.38 | 201.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 172.11 | 08-JAN-08:00 |
February | 1306.65 | 01-FEB-10:09 | 843.21 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 166.70 | 05-FEB-14:00 |
March | 1306.65 | 01-MAR-10:09 | 764.43 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 157.72 | 27-MAR-21:30 |
April | 1306.65 | 03-APR-09:09 | 670.25 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 179.86 | 23-APR-22:00 |
May | 1306.65 | 01-MAY-09:09 | 466.36 | 04-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 275.45 | 04-MAY-23:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 13-JUN-15:30 | 206.02 | 18-JUN-15:40 |
July | 1306.65 | 03-JUL-09:09 | 464.10 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 | 22-JUL-19:10 | 189.05 | 30-JUL-18:50 |
August | 1306.65 | 01-AUG-09:09 | 567.01 | 22-AUG-07:30 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 | 14-AUG-16:50 | 131.03 | 22-AUG-21:10 |
September | 1306.65 | 01-SEP-09:09 | 607.38 | 08-SEP-07:30 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 172.77 | 06-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 885.45 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 209.99 | 01-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 195.14 | 26-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-15:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 309.12 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.03 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 | 309.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 111.63 | 08-JAN-08:00 |
February | 827.17 | 01-FEB-10:09 | 535.28 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 104.62 | 08-FEB-22:10 |
March | 827.17 | 01-MAR-10:09 | 492.86 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 104.76 | 27-MAR-21:30 |
April | 827.17 | 03-APR-09:09 | 436.00 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 118.78 | 23-APR-22:00 |
May | 827.17 | 01-MAY-09:09 | 305.14 | 04-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 183.24 | 04-MAY-23:00 |
June | 827.17 | 01-JUN-09:09 | 292.40 | 14-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.19 | 13-JUN-15:30 | 149.30 | 18-JUN-16:20 |
July | 827.17 | 03-JUL-09:09 | 302.19 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | 22-JUL-19:08 | 151.60 | 30-JUL-18:50 |
August | 827.17 | 01-AUG-09:09 | 383.28 | 22-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | 14-AUG-16:50 | 89.17 | 22-AUG-21:10 |
September | 827.17 | 01-SEP-09:09 | 438.49 | 08-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 114.02 | 06-SEP-04:00 |
October | 827.17 | 02-OCT-09:09 | 560.63 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 134.06 | 01-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 126.71 | 25-NOV-05:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-15:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 201.50 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 292.40 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.17 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.04 | 201.50 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 241.65 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 221.03 | 08-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 217.23 | 27-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 249.61 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 383.36 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 13-JUN-16:00 | 261.27 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 | 22-JUL-18:52 | 240.53 | 30-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 14-AUG-17:00 | 179.59 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 240.06 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 278.19 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 279.47 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 434.85 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.59 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 | 434.85 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 294.67 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 272.09 | 08-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 265.92 | 27-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 308.82 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 479.12 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 13-JUN-16:00 | 332.35 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 22-JUL-18:52 | 304.18 | 30-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 14-AUG-17:00 | 227.99 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 297.97 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 339.16 | 01-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 332.84 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 530.36 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.99 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 530.36 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 259.57 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 278.73 | 08-FEB-22:05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 281.83 | 27-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 295.60 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 465.34 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 | 13-JUN-17:00 | 391.74 | 18-JUN-16:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 | 22-JUL-18:52 | 362.20 | 30-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 14-AUG-18:00 | 227.14 | 22-AUG-21:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 270.62 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 319.49 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 307.57 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 559.51 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.14 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 | 559.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 12462.36 | 26-JAN-08:20 | 30175.04 | 21101.01 | 90925.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12492.62 | 10-FEB-08:20 | 24140.03 | 16880.81 | 72740.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13878.50 | 31-MAR-07:17 | 36210.05 | 25321.21 | 109111.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33817.18 | 28-APR-05:02 | 3176.32 | 2344.59 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39419.47 | 01-MAY-05:02 | 3176.32 | 2344.59 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39208.35 | 23-JUN-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 39434.57 | 22-JUL-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39633.69 | 29-AUG-05:02 | 3176.32 | 2344.59 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39494.94 | 05-SEP-05:02 | 3176.32 | 2344.59 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34997.88 | 02-OCT-05:02 | 3176.32 | 2344.59 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14827.29 | 02-NOV-07:08 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10835.83 | 22-DEC-08:50 | 6035.01 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10835.83 | 2541.06 | 1875.67 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39633.69 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 492.82 | 19-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1156.97 | 04-FEB-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 |
March | 1945.97 | 25-MAR-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 |
April | 6924.82 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 |
May | 7522.13 | 22-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.65 |
June | 8527.63 | 13-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 8522.94 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 0.00 |
August | 7709.09 | 14-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 |
September | 6421.77 | 12-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 |
October | 2831.04 | 03-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 |
November | 867.02 | 11-NOV-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.04 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8527.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 128.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1061.51 | 26-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1049.93 | 10-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 |
March | 1585.66 | 24-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1997.93 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
May | 2369.82 | 23-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.58 |
June | 3150.86 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 0.00 |
July | 3397.57 | 24-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 |
August | 2768.88 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 0.00 |
September | 2514.88 | 13-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 |
October | 1527.61 | 19-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 |
November | 1555.47 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 |
December | 895.54 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 895.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3397.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 41.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2285.26 | 11-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.07 |
February | 2645.69 | 24-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
March | 2244.57 | 21-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2782.31 | 20-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3382.45 | 01-MAY-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 |
June | 3545.49 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 0.00 |
July | 3677.46 | 24-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 |
August | 3315.44 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 0.00 |
September | 3147.34 | 13-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
October | 2794.96 | 04-OCT-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.72 |
November | 2255.83 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 |
December | 2501.89 | 29-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2244.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3677.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 81.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6766.31 | 20-JAN-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6755.33 | 24-FEB-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6904.62 | 31-MAR-15:40 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12435.86 | 28-APR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25237.37 | 01-MAY-05:02 | 3176.32 | 2344.59 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 24268.24 | 26-JUN-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 24319.47 | 24-JUL-06:02 | 7623.17 | 8440.52 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 22338.43 | 07-AUG-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16168.11 | 13-SEP-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10875.78 | 03-OCT-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6960.78 | 10-NOV-16:50 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6380.79 | 21-DEC-15:10 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6380.79 | 2541.06 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25237.37 | 7623.17 | 8440.52 | 18155.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6607.71 | 19-JAN-16:40 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6626.47 | 09-FEB-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6795.90 | 31-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13564.88 | 28-APR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14827.06 | 23-MAY-15:50 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16369.07 | 13-JUN-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 20905.31 | 24-JUL-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15145.35 | 14-AUG-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14346.39 | 13-SEP-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9706.79 | 03-OCT-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6842.69 | 10-NOV-16:30 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6167.89 | 21-DEC-15:35 | 12070.02 | 8440.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6167.89 | 2541.06 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20905.31 | 12070.02 | 8440.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1172.33 | 19-JAN-16:00 | 1272.23 | 569.48 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1148.90 | 09-FEB-16:00 | 1272.23 | 450.55 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 |
March | 1323.35 | 30-MAR-15:50 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.47 |
April | 3446.58 | 28-APR-15:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 |
May | 3984.16 | 22-MAY-15:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 |
June | 5132.70 | 13-JUN-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 0.00 |
July | 4908.14 | 10-JUL-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 |
August | 4413.43 | 14-AUG-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 | 0.00 |
September | 3734.39 | 13-SEP-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
October | 1606.19 | 06-OCT-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 |
November | 1255.58 | 10-NOV-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 |
December | 996.03 | 05-DEC-21:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 996.03 | 535.68 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5132.70 | 1272.23 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 52.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1157.21 | 20-JAN-10:40 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1245.04 | 24-FEB-10:35 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
March | 1204.76 | 30-MAR-10:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 |
April | 12475.80 | 30-APR-09:22 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.63 |
May | 6992.93 | 23-MAY-09:10 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 |
June | 11085.57 | 25-JUN-10:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 |
July | 12289.69 | 23-JUL-09:02 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.72 |
August | 11350.38 | 20-AUG-09:32 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.41 |
September | 5978.24 | 12-SEP-09:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
October | 2832.03 | 04-OCT-10:00 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1156.23 | 03-NOV-10:00 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 |
December | 1008.22 | 06-DEC-10:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1008.22 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12475.80 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5053.24 | 20-JAN-12:00 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6728.37 | 17-FEB-14:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.93 |
March | 3098.26 | 28-MAR-12:15 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.51 |
April | 20195.05 | 30-APR-13:22 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.98 |
May | 9467.60 | 23-MAY-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.84 |
June | 10547.91 | 11-JUN-14:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.61 |
July | 18289.87 | 23-JUL-13:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 |
August | 18582.68 | 06-AUG-13:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.18 |
September | 19438.55 | 10-SEP-13:32 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.02 |
October | 10464.33 | 03-OCT-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.82 |
November | 5740.36 | 03-NOV-12:40 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.61 |
December | 4409.16 | 18-DEC-13:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3098.26 | 267.84 | 94.29 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20195.05 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1500.16 | 19-JAN-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2152.74 | 27-FEB-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2182.50 | 23-MAR-17:00 | 254.33 | 149.24 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 |
April | 14645.56 | 30-APR-16:02 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 |
May | 9756.94 | 21-MAY-16:53 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.30 |
June | 14823.44 | 25-JUN-16:42 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.85 |
July | 14107.78 | 30-JUL-16:42 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.75 |
August | 14468.19 | 20-AUG-16:12 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.99 |
September | 10527.11 | 10-SEP-16:12 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 |
October | 4688.82 | 03-OCT-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.30 |
November | 1524.53 | 10-NOV-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.29 |
December | 1218.67 | 21-DEC-14:50 | 827.17 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1218.67 | 169.55 | 59.69 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14823.44 | 827.17 | 268.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1143.88 | 25-JAN-15:10 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 |
February | 1135.70 | 10-FEB-16:30 | 1272.23 | 450.20 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 |
March | 1255.60 | 30-MAR-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 |
April | 1874.75 | 28-APR-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 |
May | 2339.24 | 23-MAY-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
June | 3558.61 | 13-JUN-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 0.00 |
July | 3502.25 | 21-JUL-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3002.98 | 14-AUG-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 0.00 |
September | 2687.21 | 13-SEP-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
October | 1558.98 | 02-OCT-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 |
November | 1287.75 | 10-NOV-15:10 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 |
December | 1087.41 | 21-DEC-14:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1087.41 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3558.61 | 1306.65 | 450.20 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 15.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 978.06 | 20-JAN-10:30 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1027.79 | 24-FEB-10:30 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 |
March | 981.14 | 31-MAR-09:50 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.06 |
April | 4375.67 | 28-APR-09:50 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 |
May | 5392.07 | 23-MAY-09:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
June | 7092.15 | 26-JUN-06:03 | 678.26 | 358.22 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 |
July | 8065.59 | 16-JUL-10:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 |
August | 5451.75 | 21-AUG-09:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.20 |
September | 4886.20 | 12-SEP-09:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.73 |
October | 2677.96 | 04-OCT-10:00 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1019.79 | 03-NOV-09:40 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 |
December | 892.15 | 08-DEC-10:30 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 892.15 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8065.59 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2261.82 | 21-JAN-11:30 | 401.76 | 141.46 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2902.63 | 04-FEB-14:00 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 |
March | 1561.21 | 25-MAR-11:50 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7988.49 | 30-APR-13:43 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 |
May | 6462.00 | 22-MAY-14:00 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.24 |
June | 7855.95 | 13-JUN-16:10 | 401.76 | 235.76 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3168.39 | 0.00 |
July | 11362.03 | 23-JUL-13:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 |
August | 10598.55 | 20-AUG-13:53 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 |
September | 15152.46 | 24-SEP-13:22 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.80 |
October | 7332.13 | 02-OCT-12:20 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1866.47 |
November | 1950.79 | 25-NOV-12:40 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.08 |
December | 1533.50 | 18-DEC-14:00 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2815.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1533.50 | 133.92 | 70.72 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15152.46 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 3168.39 | 2815.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1200.27 | 19-JAN-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1336.41 | 27-FEB-16:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1336.52 | 23-MAR-17:00 | 254.33 | 149.24 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 |
April | 7511.74 | 30-APR-17:42 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 |
May | 5855.85 | 22-MAY-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
June | 10200.51 | 25-JUN-17:11 | 0.00 | 104.46 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.20 |
July | 9171.95 | 22-JUL-18:22 | 0.00 | 74.61 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 0.00 |
August | 6845.67 | 19-AUG-17:06 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.91 |
September | 5571.57 | 12-SEP-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.19 |
October | 3993.72 | 03-OCT-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 |
November | 1263.78 | 10-NOV-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.52 |
December | 1029.60 | 21-DEC-14:50 | 827.17 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1029.60 | 0.00 | 59.69 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10200.51 | 827.17 | 268.64 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 28.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1205.73 | 19-JAN-15:30 | 1272.23 | 450.06 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1186.66 | 09-FEB-15:50 | 1272.23 | 445.85 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.86 |
March | 1349.52 | 31-MAR-15:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.44 |
April | 3217.64 | 28-APR-15:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 |
May | 3566.87 | 22-MAY-15:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 |
June | 4634.80 | 13-JUN-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 0.00 |
July | 4456.57 | 10-JUL-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 |
August | 4069.79 | 14-AUG-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 | 0.00 |
September | 3599.12 | 13-SEP-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 |
October | 1799.11 | 02-OCT-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 |
November | 1285.88 | 10-NOV-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 |
December | 1087.99 | 21-DEC-14:50 | 1306.65 | 470.05 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1087.99 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4634.80 | 1306.65 | 470.05 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 36.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1260.86 | 20-JAN-10:00 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1362.09 | 17-FEB-10:00 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1293.40 | 25-MAR-09:50 | 0.00 | 89.55 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11788.57 | 30-APR-10:13 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.97 |
May | 7139.55 | 23-MAY-08:40 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 |
June | 7630.89 | 26-JUN-06:03 | 678.26 | 358.22 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 |
July | 13335.00 | 23-JUL-08:52 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 |
August | 12190.63 | 20-AUG-08:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 |
September | 7441.89 | 04-SEP-09:03 | 127.17 | 44.77 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.73 |
October | 3620.67 | 03-OCT-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.34 |
November | 1258.03 | 03-NOV-10:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 |
December | 1119.24 | 06-DEC-10:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1119.24 | 0.00 | 44.77 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13335.00 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5928.88 | 20-JAN-12:00 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7173.88 | 17-FEB-13:35 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.75 |
March | 3587.99 | 28-MAR-12:10 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.06 |
April | 17194.77 | 30-APR-11:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.28 |
May | 8886.74 | 23-MAY-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 |
June | 8734.43 | 13-JUN-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 0.00 |
July | 16336.35 | 23-JUL-13:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.59 |
August | 17198.76 | 06-AUG-13:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.80 |
September | 17821.99 | 24-SEP-13:22 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.65 |
October | 11305.34 | 01-OCT-12:13 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.88 |
November | 6684.83 | 11-NOV-13:33 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.26 |
December | 4916.00 | 18-DEC-13:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3587.99 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17821.99 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 112.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1442.85 | 19-JAN-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2226.23 | 27-FEB-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2400.85 | 23-MAR-17:00 | 254.33 | 149.24 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.03 |
April | 12195.81 | 30-APR-16:12 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
May | 11181.10 | 28-MAY-16:42 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.44 |
June | 12027.70 | 25-JUN-16:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 |
July | 13656.74 | 09-JUL-16:32 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.23 |
August | 12169.10 | 06-AUG-15:53 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 |
September | 9867.61 | 24-SEP-16:03 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.81 |
October | 4822.44 | 03-OCT-15:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 |
November | 1481.36 | 10-NOV-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.53 |
December | 1215.96 | 21-DEC-14:40 | 827.17 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1215.96 | 169.55 | 59.69 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13656.74 | 827.17 | 268.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.44 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.119435E+12 | 193319.41 | 02-JAN-07:10 | 0.346591E+11 | 67280.15 | 10-JAN-07:40 |
February | 0.982783E+11 | 133615.39 | 13-FEB-07:10 | 0.266926E+11 | 59514.58 | 17-FEB-07:10 |
March | 0.107670E+12 | 126788.55 | 06-MAR-07:10 | 0.246139E+11 | 46462.28 | 08-MAR-07:10 |
April | 0.873699E+11 | 89426.73 | 28-APR-15:20 | 0.116973E+11 | 37087.60 | 08-APR-06:40 |
May | 0.918183E+11 | 98321.20 | 22-MAY-15:09 | 0.103126E+11 | 23727.70 | 06-MAY-06:40 |
June | 0.946216E+11 | 119052.96 | 13-JUN-15:30 | 0.929645E+10 | 12009.35 | 08-JUN-06:10 |
July | 0.968368E+11 | 116165.12 | 21-JUL-15:39 | 0.898700E+10 | 9238.60 | 05-JUL-11:09 |
August | 0.105565E+12 | 112698.94 | 14-AUG-15:50 | 0.947627E+10 | 9212.52 | 01-AUG-11:09 |
September | 0.922045E+11 | 103196.11 | 13-SEP-15:09 | 0.895445E+10 | 17722.76 | 21-SEP-06:19 |
October | 0.942421E+11 | 98811.98 | 23-OCT-06:10 | 0.120015E+11 | 30778.78 | 23-OCT-06:40 |
November | 0.103766E+12 | 134539.72 | 27-NOV-07:10 | 0.207943E+11 | 50614.94 | 29-NOV-07:30 |
December | 0.121236E+12 | 157793.60 | 26-DEC-07:10 | 0.332879E+11 | 54884.86 | 29-DEC-20:00 |
Annual Sum or Average | 0.121304E+13 | 0.210773E+12 | ||||
Minimum of Months | 0.873699E+11 | 89426.73 | 0.895445E+10 | 9212.52 | ||
Maximum of Months | 0.121236E+12 | 193319.41 | 0.346591E+11 | 67280.15 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.178663E+11 | 0.620565E+10 | 0.593559E+11 | 0.980641E+09 | 0.396368E+10 | 1312252.65 | 0.310611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157045E+11 | 0.483979E+10 | 0.537310E+11 | 0.886946E+09 | 0.360447E+10 | 1186778.30 | 0.195104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182547E+11 | 0.435653E+10 | 0.617796E+11 | 0.102615E+10 | 0.421305E+10 | 1343621.24 | 0.180388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160558E+11 | 0.333512E+10 | 0.572952E+11 | 0.943577E+09 | 0.538354E+10 | 1267813.82 | 0.325496E+10 | 0.110052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171595E+11 | 0.282726E+10 | 0.605677E+11 | 0.100266E+10 | 0.643670E+10 | 1327936.95 | 0.218242E+10 | 0.164067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170115E+11 | 0.247392E+10 | 0.594895E+11 | 0.986985E+09 | 0.815455E+10 | 1296568.36 | 0.103324E+10 | 0.547055E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159594E+11 | 0.266458E+10 | 0.583622E+11 | 0.959020E+09 | 0.909288E+10 | 1299182.41 | 0.474196E+09 | 0.932318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178908E+11 | 0.314553E+10 | 0.617796E+11 | 0.102592E+10 | 0.963275E+10 | 1343621.24 | 0.452781E+09 | 0.116360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161699E+11 | 0.379218E+10 | 0.572729E+11 | 0.943400E+09 | 0.746966E+10 | 1267813.82 | 0.829390E+09 | 0.572575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.172637E+11 | 0.492189E+10 | 0.593671E+11 | 0.980117E+09 | 0.464555E+10 | 1312252.65 | 0.684422E+10 | 0.218245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176573E+11 | 0.571591E+10 | 0.580818E+11 | 0.962459E+09 | 0.384042E+10 | 1278270.02 | 0.175041E+11 | 2510716.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.177009E+11 | 0.646241E+10 | 0.583511E+11 | 0.960558E+09 | 0.383847E+10 | 1299182.41 | 0.339210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204694E+12 | 0.507408E+11 | 0.705434E+12 | 0.116584E+11 | 0.702757E+11 | 15535293.87 | 0.135107E+12 | 0.351174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157045E+11 | 0.247392E+10 | 0.537310E+11 | 0.886946E+09 | 0.360447E+10 | 1186778.30 | 0.452781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182547E+11 | 0.646241E+10 | 0.617796E+11 | 0.102615E+10 | 0.963275E+10 | 1343621.24 | 0.339210E+11 | 0.116360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.249696E+11 | 0.00 | 0.968948E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.178819E+11 | 0.00 | 0.881067E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.145070E+11 | 0.00 | 0.101069E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245706E+10 | 0.00 | 0.924026E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.711139E+09 | 0.00 | 0.960147E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 13301766.94 | 0.00 | 0.928315E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.898700E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 604507.00 | 0.00 | 0.947566E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.119828E+09 | 0.00 | 0.883462E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.275188E+10 | 0.00 | 0.924957E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.116008E+11 | 0.00 | 0.919348E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.238597E+11 | 0.00 | 0.942820E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.988728E+11 | 0.00 | 0.111900E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.881067E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.249696E+11 | 0.00 | 0.101069E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21377.78 | 02-JAN-08:09 | 5557.43 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 835.33 | 02-JAN-08:20 | 5531.48 | 02-JAN-07:10 | 0.73 | 02-JAN-06:10 | 153761.42 | 02-JAN-07:10 |
February | 20924.19 | 01-FEB-08:09 | 5557.43 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 834.73 | 01-FEB-08:20 | 3870.46 | 17-FEB-13:39 | 0.73 | 02-FEB-07:10 | 95775.19 | 13-FEB-07:10 |
March | 20145.41 | 15-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 833.70 | 15-MAR-07:19 | 3759.47 | 06-MAR-07:10 | 0.73 | 01-MAR-07:10 | 95001.71 | 06-MAR-07:10 |
April | 19180.36 | 10-APR-07:10 | 5557.43 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 832.42 | 10-APR-07:19 | 14750.45 | 28-APR-15:30 | 0.73 | 03-APR-07:10 | 47698.95 | 03-APR-06:10 |
May | 17165.16 | 04-MAY-07:10 | 3195.36 | 01-MAY-19:19 | 45864.70 | 01-MAY-07:10 | 829.76 | 04-MAY-07:19 | 14735.36 | 23-MAY-15:09 | 0.73 | 05-MAY-07:10 | 21524.55 | 17-MAY-06:10 |
June | 16887.53 | 14-JUN-07:10 | 3195.36 | 01-JUN-19:00 | 45864.70 | 01-JUN-07:10 | 829.39 | 14-JUN-07:19 | 20533.14 | 13-JUN-15:30 | 0.73 | 01-JUN-05:10 | 12108.75 | 08-JUN-06:10 |
July | 17141.41 | 07-JUL-07:30 | 3195.36 | 01-JUL-20:19 | 45864.70 | 03-JUL-07:10 | 829.72 | 07-JUL-07:40 | 19706.43 | 21-JUL-15:39 | 0.73 | 01-JUL-05:10 | 9940.50 | 03-JUL-06:10 |
August | 18115.99 | 22-AUG-07:30 | 5557.43 | 14-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 831.01 | 22-AUG-07:40 | 19271.52 | 14-AUG-15:30 | 0.73 | 01-AUG-05:10 | 10066.92 | 24-AUG-06:10 |
September | 18606.45 | 08-SEP-07:30 | 5557.43 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 831.66 | 08-SEP-07:40 | 17503.60 | 12-SEP-15:09 | 0.73 | 01-SEP-05:10 | 19188.76 | 20-SEP-06:10 |
October | 21336.67 | 31-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 835.28 | 31-OCT-07:19 | 8739.06 | 03-OCT-15:09 | 0.73 | 04-OCT-07:10 | 61393.60 | 23-OCT-06:10 |
November | 21377.78 | 06-NOV-16:49 | 5557.43 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 835.29 | 02-NOV-07:19 | 3845.85 | 03-NOV-12:39 | 0.73 | 01-NOV-07:10 | 96672.58 | 27-NOV-07:10 |
December | 21377.78 | 01-DEC-15:30 | 5557.43 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 835.33 | 29-DEC-08:20 | 4304.28 | 26-DEC-07:10 | 0.73 | 01-DEC-07:10 | 119462.82 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 16887.53 | 3195.36 | 45864.70 | 829.39 | 3759.47 | 0.73 | 9940.50 | |||||||
Maximum of Months | 21377.78 | 5557.43 | 45864.70 | 835.33 | 20533.14 | 0.73 | 153761.42 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14968.76 | 28-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24490.33 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 38915.93 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 36962.65 | 21-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33884.97 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26413.73 | 13-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6945.26 | 07-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1838.96 | 24-NOV-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38915.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 193319.41 | 02-JAN-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 5531.48 | 0.73 | 153761.42 | 0.00 | 0.00 |
February | 133615.39 | 13-FEB-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 3813.69 | 0.73 | 95775.19 | 0.00 | 0.00 |
March | 126788.55 | 06-MAR-07:10 | 6684.37 | 21098.80 | 0.00 | 243.47 | 3759.47 | 0.73 | 95001.71 | 0.00 | 0.00 |
April | 89426.73 | 28-APR-15:20 | 16818.70 | 42072.41 | 0.00 | 827.95 | 14738.19 | 0.73 | 0.00 | 14968.76 | 0.00 |
May | 98321.20 | 22-MAY-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 14322.63 | 0.73 | 0.00 | 24278.79 | 0.00 |
June | 119052.96 | 13-JUN-15:30 | 16818.70 | 42072.41 | 0.00 | 827.95 | 20533.14 | 0.73 | 0.00 | 38800.03 | 0.00 |
July | 116165.12 | 21-JUL-15:39 | 16818.70 | 42072.41 | 0.00 | 827.95 | 19706.43 | 0.73 | 0.00 | 36738.91 | 0.00 |
August | 112698.94 | 14-AUG-15:50 | 16818.70 | 42072.41 | 0.00 | 827.95 | 19143.17 | 0.73 | 0.00 | 33835.97 | 0.00 |
September | 103196.11 | 13-SEP-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 17110.77 | 0.73 | 0.00 | 26365.56 | 0.00 |
October | 98811.98 | 23-OCT-06:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 3391.88 | 0.73 | 61393.60 | 0.00 | 0.00 |
November | 134539.72 | 27-NOV-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 3840.63 | 0.73 | 96672.58 | 0.00 | 0.00 |
December | 157793.60 | 26-DEC-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 4304.28 | 0.73 | 119462.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 89426.73 | 6684.37 | 21098.80 | 0.00 | 243.47 | 3391.88 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 193319.41 | 16818.70 | 42072.41 | 5557.43 | 827.95 | 20533.14 | 0.73 | 153761.42 | 38800.03 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 61168.50 | 10-JAN-07:00 | 0.00 | 9437.22 | 25-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 52143.83 | 17-FEB-07:19 | 0.00 | 9443.92 | 17-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 38283.45 | 08-MAR-07:10 | 0.00 | 9437.28 | 08-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 32866.91 | 08-APR-06:10 | 0.00 | 9396.73 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 21326.87 | 06-MAY-06:10 | 0.00 | 9356.00 | 02-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 3990.75 | 08-JUN-06:10 | 0.00 | 9288.56 | 02-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9238.60 | 05-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 1007.51 | 24-AUG-06:10 | 0.00 | 9212.52 | 01-AUG-11:09 | 0.00 |
September | 0.00 | 0.00 | 10477.56 | 21-SEP-06:10 | 0.00 | 9238.30 | 26-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 22763.16 | 23-OCT-06:19 | 0.00 | 9294.11 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 42701.20 | 29-NOV-07:19 | 0.00 | 9351.02 | 28-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 46789.47 | 29-DEC-20:00 | 0.00 | 9406.33 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9212.52 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 61168.50 | 0.00 | 9443.92 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.35 | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.35 | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.35 | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.49 | 0.33 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.38 | 0.50 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Annual Sum or Average | 1.00 | 18.93 | 0.83 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.38 | 0.50 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 18.49 | 4.50 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
February | 1.33 | 19.10 | 1.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
March | 0.33 | 19.41 | 0.33 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 19.00 | 0.83 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
December | 5.33 | 18.63 | 3.67 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Annual Sum or Average | 14.17 | 18.66 | 10.50 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 19.41 | 4.50 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 16.76 | 0.33 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 |
February | 0.17 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.79 | 1.00 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.55 | 1.67 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.93 | 2.83 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.53 | 1.83 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
December | 1.83 | 16.81 | 0.17 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
Annual Sum or Average | 3.83 | 16.82 | 0.50 | 16.94 | 8.00 | 23.92 | 8.00 | 25.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 17.18 | 0.33 | 17.18 | 2.83 | 27.93 | 2.83 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 17.31 | 0.17 | 17.65 | 0.00 | 17.65 | 0.00 | 17.65 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.19 | 1.50 | 28.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.60 | 3.00 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.71 | 4.00 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.79 | 3.17 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.51 | 0.67 | 27.51 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 17.35 | 0.17 | 17.65 | 0.00 | 17.65 | 0.00 | 17.65 |
Annual Sum or Average | 1.83 | 17.33 | 0.33 | 17.65 | 12.67 | 26.27 | 12.67 | 26.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 17.35 | 0.17 | 17.65 | 4.00 | 28.19 | 4.00 | 28.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 16.71 | 0.33 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
February | 0.17 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.33 | 0.83 | 28.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.85 | 1.17 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.01 | 1.33 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.07 | 2.50 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.88 | 2.67 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.83 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
December | 1.83 | 16.81 | 0.17 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
Annual Sum or Average | 3.83 | 16.82 | 0.50 | 16.94 | 16.67 | 25.71 | 9.33 | 26.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 17.22 | 0.33 | 17.22 | 5.67 | 28.33 | 2.67 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.45 | 2.17 | 19.54 | 0.00 | 19.54 | 0.00 | 19.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.43 | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Annual Sum or Average | 2.50 | 19.45 | 2.33 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.45 | 2.17 | 19.54 | 0.00 | 19.54 | 0.00 | 19.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.61 | 2.00 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 27.52 | 3.33 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.61 | 2.00 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 72.50 | 17.29 | 72.50 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
February | 64.33 | 17.90 | 64.33 | 17.90 | 0.00 | 17.90 | 0.00 | 17.90 |
March | 75.83 | 18.02 | 75.83 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
April | 31.50 | 18.80 | 31.50 | 18.80 | 1.33 | 18.98 | 1.33 | 19.16 |
May | 32.00 | 19.39 | 32.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
June | 7.17 | 19.91 | 7.17 | 19.91 | 0.00 | 19.91 | 0.00 | 19.91 |
July | 0.83 | 20.15 | 0.83 | 20.15 | 0.17 | 20.81 | 0.17 | 21.36 |
August | 0.83 | 20.18 | 0.83 | 20.18 | 1.67 | 23.80 | 1.67 | 25.00 |
September | 9.00 | 19.66 | 9.00 | 19.66 | 2.33 | 20.56 | 2.33 | 21.28 |
October | 37.33 | 18.97 | 37.33 | 18.97 | 1.00 | 19.08 | 1.00 | 19.19 |
November | 65.00 | 18.35 | 65.00 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
December | 70.67 | 17.42 | 70.67 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
Annual Sum or Average | 467.00 | 18.13 | 467.00 | 18.13 | 6.50 | 18.20 | 6.50 | 18.26 |
Minimum of Months | 0.83 | 17.29 | 0.83 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
Maximum of Months | 75.83 | 20.18 | 75.83 | 20.18 | 2.33 | 23.80 | 2.33 | 25.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.78 | 0.50 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.57 | 0.17 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.60 | 0.67 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.66 | 1.33 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.58 | 1.00 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 17.22 | 0.00 | 17.22 | 8.50 | 27.44 | 3.67 | 27.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 17.22 | 0.00 | 17.22 | 3.67 | 27.78 | 1.33 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.26 | 1.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.32 | 0.33 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 1.67 | 19.27 | 1.50 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.32 | 1.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.67 | 0.33 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.90 | 1.00 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.61 | 0.67 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.63 | 2.00 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.87 | 3.17 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.58 | 2.67 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.38 | 1.33 | 27.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Annual Sum or Average | 0.67 | 18.86 | 0.50 | 19.11 | 10.83 | 26.85 | 10.83 | 27.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.44 | 0.33 | 19.44 | 3.17 | 27.90 | 3.17 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.91 | 1.83 | 27.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.58 | 2.33 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.67 | 3.83 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.69 | 4.17 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.55 | 1.17 | 27.55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.00 | 27.66 | 14.00 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.91 | 4.17 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.26 | 0.17 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.15 | 0.83 | 28.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.79 | 1.17 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.96 | 1.33 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.01 | 2.50 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.88 | 2.33 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.66 | 0.67 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Annual Sum or Average | 0.50 | 18.66 | 0.33 | 18.96 | 15.00 | 27.47 | 8.83 | 27.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.44 | 0.17 | 19.44 | 5.17 | 28.15 | 2.50 | 28.15 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 23.01 | 18.33 | 22.92 | 18.33 | 22.83 |
February | 454.00 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
March | 514.00 | 23.51 | 0.00 | 23.51 | 0.00 | 23.51 |
April | 225.17 | 23.83 | 34.83 | 24.06 | 0.00 | 24.06 |
May | 66.33 | 23.80 | 104.17 | 24.57 | 0.00 | 24.57 |
June | 0.00 | 0.00 | 266.67 | 24.55 | 0.00 | 24.55 |
July | 0.00 | 0.00 | 354.33 | 24.50 | 0.00 | 24.50 |
August | 0.00 | 0.00 | 343.50 | 24.40 | 0.00 | 24.40 |
September | 0.00 | 0.00 | 227.33 | 24.61 | 0.00 | 24.61 |
October | 221.17 | 23.64 | 33.00 | 23.86 | 0.00 | 23.86 |
November | 445.50 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
December | 497.00 | 23.10 | 0.00 | 23.10 | 0.00 | 23.10 |
Annual Sum or Average | 2925.17 | 23.39 | 1382.17 | 23.76 | 18.33 | 23.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.92 | 0.00 | 22.83 |
Maximum of Months | 514.00 | 23.83 | 354.33 | 24.61 | 18.33 | 24.61 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.45 | 82.00 | 21.31 | 82.00 | 21.20 |
February | 454.00 | 21.75 | 4.17 | 21.73 | 4.17 | 21.72 |
March | 514.00 | 21.95 | 3.67 | 21.94 | 3.67 | 21.93 |
April | 413.50 | 23.27 | 1.00 | 23.27 | 0.00 | 23.27 |
May | 303.50 | 23.41 | 15.83 | 23.47 | 0.00 | 23.47 |
June | 119.17 | 23.48 | 127.83 | 23.94 | 0.00 | 23.94 |
July | 75.17 | 23.40 | 213.00 | 24.09 | 0.00 | 24.09 |
August | 61.17 | 23.50 | 169.67 | 24.12 | 0.00 | 24.12 |
September | 174.33 | 23.36 | 74.17 | 23.64 | 0.00 | 23.64 |
October | 468.50 | 22.76 | 0.00 | 22.76 | 0.00 | 22.76 |
November | 489.00 | 21.98 | 4.50 | 21.96 | 4.50 | 21.95 |
December | 497.00 | 21.34 | 90.83 | 21.23 | 90.83 | 21.14 |
Annual Sum or Average | 4071.33 | 22.29 | 786.67 | 22.47 | 185.17 | 22.40 |
Minimum of Months | 61.17 | 21.34 | 0.00 | 21.23 | 0.00 | 21.14 |
Maximum of Months | 514.00 | 23.50 | 213.00 | 24.12 | 90.83 | 24.12 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.79 | 249.83 | 20.61 | 249.83 | 20.52 |
February | 454.00 | 21.00 | 155.50 | 20.80 | 155.50 | 20.69 |
March | 514.00 | 21.26 | 106.00 | 21.12 | 106.00 | 21.02 |
April | 445.67 | 22.74 | 6.50 | 22.71 | 6.50 | 22.68 |
May | 383.67 | 22.96 | 18.83 | 23.02 | 0.00 | 23.02 |
June | 201.50 | 23.26 | 95.67 | 23.55 | 0.00 | 23.55 |
July | 154.00 | 23.20 | 183.50 | 23.77 | 0.00 | 23.77 |
August | 172.17 | 23.29 | 127.50 | 23.64 | 0.00 | 23.64 |
September | 307.33 | 23.03 | 45.50 | 23.16 | 0.00 | 23.16 |
October | 493.00 | 21.93 | 20.50 | 21.87 | 20.50 | 21.81 |
November | 489.00 | 21.13 | 124.67 | 20.97 | 124.67 | 20.87 |
December | 497.00 | 20.66 | 271.33 | 20.49 | 271.33 | 20.40 |
Annual Sum or Average | 4613.33 | 21.81 | 1405.33 | 21.75 | 934.33 | 21.55 |
Minimum of Months | 154.00 | 20.66 | 6.50 | 20.49 | 0.00 | 20.40 |
Maximum of Months | 514.00 | 23.29 | 271.33 | 23.77 | 271.33 | 23.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.20 | 381.00 | 20.09 | 381.00 | 20.04 |
February | 454.00 | 20.32 | 301.17 | 20.18 | 301.17 | 20.11 |
March | 514.00 | 20.70 | 273.00 | 20.54 | 273.00 | 20.47 |
April | 448.33 | 22.06 | 63.50 | 21.88 | 60.00 | 21.72 |
May | 414.83 | 22.43 | 33.17 | 22.47 | 9.83 | 22.42 |
June | 223.67 | 22.94 | 117.83 | 23.36 | 0.00 | 23.36 |
July | 187.17 | 23.02 | 180.83 | 23.60 | 0.00 | 23.60 |
August | 235.33 | 22.97 | 137.17 | 23.37 | 0.00 | 23.37 |
September | 366.00 | 22.45 | 35.83 | 22.58 | 1.17 | 22.57 |
October | 502.00 | 21.18 | 127.67 | 20.96 | 127.67 | 20.81 |
November | 489.00 | 20.44 | 288.83 | 20.28 | 288.83 | 20.20 |
December | 497.00 | 20.08 | 432.67 | 20.01 | 432.67 | 19.99 |
Annual Sum or Average | 4833.33 | 21.28 | 2372.67 | 21.15 | 1875.33 | 20.92 |
Minimum of Months | 187.17 | 20.08 | 33.17 | 20.01 | 0.00 | 19.99 |
Maximum of Months | 514.00 | 23.02 | 432.67 | 23.60 | 432.67 | 23.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.30 | 359.83 | 20.18 | 359.83 | 20.12 |
February | 454.00 | 20.50 | 277.67 | 20.34 | 277.67 | 20.26 |
March | 514.00 | 20.76 | 247.00 | 20.60 | 247.00 | 20.51 |
April | 334.67 | 22.25 | 75.00 | 22.31 | 37.00 | 22.18 |
May | 295.00 | 22.40 | 111.50 | 22.89 | 6.00 | 22.86 |
June | 187.00 | 22.95 | 223.17 | 23.71 | 6.00 | 23.75 |
July | 146.00 | 23.28 | 287.00 | 24.07 | 12.17 | 24.15 |
August | 175.00 | 23.06 | 270.33 | 23.81 | 6.33 | 23.85 |
September | 233.17 | 22.36 | 161.33 | 23.18 | 1.33 | 23.17 |
October | 465.17 | 21.25 | 108.50 | 21.06 | 106.17 | 20.90 |
November | 489.00 | 20.52 | 256.17 | 20.34 | 256.17 | 20.26 |
December | 497.00 | 20.13 | 412.83 | 20.05 | 412.83 | 20.02 |
Annual Sum or Average | 4292.00 | 21.22 | 2790.33 | 21.43 | 1728.50 | 21.18 |
Minimum of Months | 146.00 | 20.13 | 75.00 | 20.05 | 1.33 | 20.02 |
Maximum of Months | 514.00 | 23.28 | 412.83 | 24.07 | 412.83 | 24.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.67 | 20.69 | 298.83 | 20.49 | 295.50 | 20.38 |
February | 419.33 | 20.90 | 217.67 | 20.66 | 213.33 | 20.52 |
March | 509.00 | 20.96 | 238.33 | 20.75 | 238.33 | 20.64 |
April | 322.00 | 22.10 | 125.33 | 22.32 | 54.17 | 22.18 |
May | 330.17 | 22.18 | 117.83 | 22.64 | 15.50 | 22.56 |
June | 228.67 | 22.67 | 196.17 | 23.42 | 1.67 | 23.43 |
July | 191.50 | 22.97 | 236.83 | 23.78 | 11.67 | 23.86 |
August | 206.33 | 23.07 | 243.50 | 23.75 | 14.83 | 23.85 |
September | 241.50 | 22.55 | 204.67 | 23.42 | 13.00 | 23.51 |
October | 409.33 | 21.34 | 141.83 | 21.44 | 89.67 | 21.26 |
November | 463.67 | 20.83 | 222.17 | 20.63 | 216.50 | 20.49 |
December | 489.83 | 20.44 | 360.33 | 20.27 | 360.33 | 20.20 |
Annual Sum or Average | 4291.00 | 21.44 | 2603.50 | 21.64 | 1524.50 | 21.40 |
Minimum of Months | 191.50 | 20.44 | 117.83 | 20.27 | 1.67 | 20.20 |
Maximum of Months | 509.00 | 23.07 | 360.33 | 23.78 | 360.33 | 23.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.31 | 365.67 | 20.18 | 365.67 | 20.12 |
February | 451.17 | 20.58 | 273.00 | 20.37 | 273.00 | 20.27 |
March | 511.83 | 20.72 | 267.83 | 20.57 | 267.83 | 20.49 |
April | 386.00 | 21.88 | 106.33 | 21.96 | 61.00 | 21.82 |
May | 364.00 | 22.16 | 108.67 | 22.55 | 19.67 | 22.52 |
June | 240.50 | 22.74 | 195.00 | 23.44 | 7.00 | 23.49 |
July | 192.33 | 22.85 | 239.33 | 23.69 | 12.83 | 23.79 |
August | 247.17 | 22.89 | 189.50 | 23.49 | 12.00 | 23.58 |
September | 328.33 | 22.22 | 105.83 | 22.73 | 5.17 | 22.75 |
October | 469.83 | 21.09 | 129.67 | 20.97 | 116.17 | 20.83 |
November | 489.00 | 20.52 | 269.33 | 20.34 | 269.33 | 20.25 |
December | 497.00 | 20.10 | 430.83 | 20.04 | 430.83 | 20.01 |
Annual Sum or Average | 4679.17 | 21.23 | 2681.00 | 21.32 | 1840.50 | 21.10 |
Minimum of Months | 192.33 | 20.10 | 105.83 | 20.04 | 5.17 | 20.01 |
Maximum of Months | 511.83 | 22.89 | 430.83 | 23.69 | 430.83 | 23.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.49 | 347.17 | 20.38 | 347.17 | 20.34 |
February | 454.00 | 20.60 | 269.67 | 20.48 | 269.67 | 20.43 |
March | 514.00 | 20.84 | 225.50 | 20.72 | 225.50 | 20.66 |
April | 482.83 | 22.08 | 23.50 | 22.01 | 23.50 | 21.93 |
May | 468.33 | 22.66 | 0.00 | 22.66 | 0.00 | 22.66 |
June | 281.00 | 23.23 | 60.67 | 23.38 | 0.00 | 23.38 |
July | 197.00 | 23.31 | 114.67 | 23.61 | 0.00 | 23.61 |
August | 281.50 | 23.27 | 52.67 | 23.39 | 0.00 | 23.39 |
September | 391.83 | 22.91 | 8.83 | 22.94 | 0.00 | 22.94 |
October | 502.00 | 21.71 | 16.50 | 21.66 | 16.50 | 21.62 |
November | 489.00 | 20.90 | 149.83 | 20.78 | 149.83 | 20.71 |
December | 497.00 | 20.48 | 364.33 | 20.40 | 364.33 | 20.37 |
Annual Sum or Average | 5060.50 | 21.65 | 1633.33 | 21.46 | 1396.50 | 21.26 |
Minimum of Months | 197.00 | 20.48 | 0.00 | 20.38 | 0.00 | 20.34 |
Maximum of Months | 514.00 | 23.31 | 364.33 | 23.61 | 364.33 | 23.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.61 | 315.50 | 20.50 | 315.50 | 20.45 |
February | 454.00 | 20.81 | 212.17 | 20.67 | 212.17 | 20.59 |
March | 514.00 | 20.94 | 192.83 | 20.80 | 192.83 | 20.71 |
April | 349.00 | 22.70 | 29.83 | 22.81 | 5.83 | 22.79 |
May | 276.33 | 22.92 | 97.50 | 23.36 | 0.00 | 23.36 |
June | 144.17 | 23.24 | 210.33 | 23.92 | 0.33 | 23.93 |
July | 84.67 | 23.63 | 296.17 | 24.31 | 6.83 | 24.36 |
August | 95.17 | 23.36 | 286.50 | 24.07 | 0.67 | 24.08 |
September | 177.50 | 23.14 | 177.33 | 23.81 | 0.00 | 23.81 |
October | 453.17 | 21.93 | 15.00 | 21.92 | 11.17 | 21.88 |
November | 489.00 | 21.02 | 118.00 | 20.90 | 118.00 | 20.82 |
December | 497.00 | 20.53 | 340.50 | 20.43 | 340.50 | 20.39 |
Annual Sum or Average | 4036.00 | 21.54 | 2291.67 | 21.81 | 1203.83 | 21.59 |
Minimum of Months | 84.67 | 20.53 | 15.00 | 20.43 | 0.00 | 20.39 |
Maximum of Months | 514.00 | 23.63 | 340.50 | 24.31 | 340.50 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.17 | 20.36 | 288.50 | 20.09 | 287.50 | 19.96 |
February | 445.50 | 20.59 | 200.67 | 20.31 | 198.67 | 20.15 |
March | 514.00 | 20.40 | 277.67 | 20.20 | 277.67 | 20.10 |
April | 401.17 | 21.81 | 71.00 | 21.83 | 39.50 | 21.66 |
May | 411.50 | 21.86 | 68.33 | 22.08 | 17.83 | 21.97 |
June | 325.17 | 22.33 | 103.33 | 22.83 | 1.83 | 22.81 |
July | 219.50 | 22.65 | 167.50 | 23.46 | 0.83 | 23.47 |
August | 177.50 | 22.72 | 216.33 | 23.64 | 3.33 | 23.67 |
September | 207.50 | 22.60 | 204.83 | 23.55 | 8.67 | 23.58 |
October | 426.67 | 21.53 | 76.50 | 21.59 | 37.00 | 21.43 |
November | 478.83 | 20.77 | 141.33 | 20.55 | 134.67 | 20.36 |
December | 497.00 | 20.18 | 367.33 | 20.02 | 367.33 | 19.95 |
Annual Sum or Average | 4602.50 | 21.22 | 2183.33 | 21.31 | 1374.83 | 21.04 |
Minimum of Months | 177.50 | 20.18 | 68.33 | 20.02 | 0.83 | 19.95 |
Maximum of Months | 514.00 | 22.72 | 367.33 | 23.64 | 367.33 | 23.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.60 | 325.83 | 20.48 | 325.83 | 20.43 |
February | 454.00 | 20.87 | 216.17 | 20.70 | 216.17 | 20.61 |
March | 514.00 | 20.89 | 206.67 | 20.76 | 206.67 | 20.69 |
April | 401.50 | 22.30 | 39.00 | 22.38 | 14.67 | 22.32 |
May | 343.67 | 22.68 | 73.67 | 23.02 | 0.17 | 23.02 |
June | 182.50 | 23.23 | 194.83 | 23.80 | 2.00 | 23.82 |
July | 123.83 | 23.31 | 289.50 | 24.05 | 6.00 | 24.09 |
August | 140.50 | 23.30 | 227.33 | 23.90 | 3.67 | 23.93 |
September | 269.50 | 22.96 | 124.00 | 23.40 | 0.00 | 23.40 |
October | 468.83 | 21.76 | 21.00 | 21.75 | 13.83 | 21.71 |
November | 489.00 | 20.96 | 134.33 | 20.84 | 134.33 | 20.76 |
December | 497.00 | 20.49 | 369.00 | 20.41 | 369.00 | 20.38 |
Annual Sum or Average | 4386.33 | 21.55 | 2221.33 | 21.72 | 1292.33 | 21.50 |
Minimum of Months | 123.83 | 20.49 | 21.00 | 20.41 | 0.00 | 20.38 |
Maximum of Months | 514.00 | 23.31 | 369.00 | 24.05 | 369.00 | 24.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.55 | 316.67 | 20.42 | 316.67 | 20.36 |
February | 454.00 | 20.71 | 217.17 | 20.55 | 217.17 | 20.47 |
March | 514.00 | 21.07 | 154.83 | 20.92 | 154.83 | 20.82 |
April | 436.50 | 22.57 | 11.17 | 22.52 | 10.67 | 22.48 |
May | 389.17 | 22.99 | 18.33 | 23.04 | 0.00 | 23.04 |
June | 163.83 | 23.38 | 123.00 | 23.73 | 0.00 | 23.73 |
July | 123.33 | 23.39 | 200.67 | 23.90 | 0.00 | 23.90 |
August | 157.67 | 23.32 | 144.00 | 23.66 | 0.00 | 23.66 |
September | 317.00 | 22.98 | 46.67 | 23.11 | 0.00 | 23.11 |
October | 497.67 | 21.80 | 25.17 | 21.72 | 25.17 | 21.65 |
November | 489.00 | 20.88 | 160.50 | 20.74 | 160.50 | 20.65 |
December | 497.00 | 20.43 | 346.67 | 20.32 | 346.67 | 20.27 |
Annual Sum or Average | 4541.17 | 21.63 | 1764.83 | 21.57 | 1231.67 | 21.35 |
Minimum of Months | 123.33 | 20.43 | 11.17 | 20.32 | 0.00 | 20.27 |
Maximum of Months | 514.00 | 23.39 | 346.67 | 23.90 | 346.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.54 | 265.83 | 20.41 | 265.83 | 20.35 |
February | 385.00 | 20.80 | 173.50 | 20.63 | 173.50 | 20.55 |
March | 433.00 | 20.99 | 142.17 | 20.83 | 142.17 | 20.74 |
April | 287.50 | 22.58 | 45.17 | 22.78 | 10.50 | 22.77 |
May | 247.50 | 22.78 | 94.00 | 23.29 | 1.17 | 23.30 |
June | 150.50 | 23.33 | 175.17 | 23.94 | 7.83 | 24.01 |
July | 103.33 | 23.64 | 230.83 | 24.32 | 11.67 | 24.42 |
August | 134.33 | 23.43 | 208.83 | 24.01 | 9.17 | 24.08 |
September | 199.83 | 22.87 | 130.67 | 23.55 | 2.33 | 23.57 |
October | 393.83 | 21.65 | 31.67 | 21.61 | 25.50 | 21.53 |
November | 417.00 | 20.85 | 144.00 | 20.71 | 144.00 | 20.62 |
December | 422.00 | 20.38 | 306.83 | 20.27 | 306.83 | 20.23 |
Annual Sum or Average | 3600.83 | 21.52 | 1948.67 | 21.75 | 1100.50 | 21.53 |
Minimum of Months | 103.33 | 20.38 | 31.67 | 20.27 | 1.17 | 20.23 |
Maximum of Months | 433.00 | 23.64 | 306.83 | 24.32 | 306.83 | 24.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 469.17 | 21.05 | 220.00 | 20.87 | 214.50 | 20.75 |
February | 404.50 | 21.27 | 137.50 | 21.12 | 128.33 | 20.97 |
March | 504.17 | 21.35 | 120.83 | 21.16 | 120.83 | 21.04 |
April | 295.83 | 22.58 | 89.67 | 22.98 | 11.83 | 22.99 |
May | 299.17 | 22.74 | 106.17 | 23.20 | 0.00 | 23.20 |
June | 183.17 | 23.14 | 210.67 | 23.76 | 0.50 | 23.76 |
July | 137.00 | 23.36 | 261.50 | 24.06 | 8.67 | 24.12 |
August | 141.33 | 23.55 | 270.00 | 24.06 | 15.33 | 24.17 |
September | 201.67 | 23.16 | 222.17 | 23.85 | 13.33 | 23.94 |
October | 393.83 | 21.93 | 77.33 | 22.20 | 17.50 | 22.17 |
November | 453.67 | 21.27 | 108.67 | 21.21 | 95.33 | 21.09 |
December | 484.83 | 20.83 | 271.50 | 20.62 | 271.50 | 20.52 |
Annual Sum or Average | 3968.33 | 21.81 | 2096.00 | 22.14 | 897.67 | 21.95 |
Minimum of Months | 137.00 | 20.83 | 77.33 | 20.62 | 0.00 | 20.52 |
Maximum of Months | 504.17 | 23.55 | 271.50 | 24.06 | 271.50 | 24.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.64 | 294.33 | 20.49 | 294.33 | 20.42 |
February | 446.50 | 20.92 | 185.00 | 20.72 | 185.00 | 20.62 |
March | 509.67 | 21.03 | 153.00 | 20.89 | 153.00 | 20.79 |
April | 374.83 | 22.40 | 61.00 | 22.58 | 14.83 | 22.55 |
May | 336.33 | 22.71 | 97.17 | 23.10 | 2.67 | 23.13 |
June | 184.33 | 23.19 | 217.67 | 23.80 | 6.33 | 23.85 |
July | 145.00 | 23.32 | 279.17 | 24.02 | 12.00 | 24.10 |
August | 172.67 | 23.32 | 233.17 | 23.87 | 12.17 | 23.96 |
September | 283.50 | 22.78 | 125.00 | 23.27 | 3.33 | 23.30 |
October | 464.17 | 21.62 | 43.17 | 21.63 | 27.00 | 21.56 |
November | 489.00 | 20.91 | 157.17 | 20.76 | 157.17 | 20.67 |
December | 497.00 | 20.44 | 347.67 | 20.34 | 347.67 | 20.29 |
Annual Sum or Average | 4405.00 | 21.57 | 2193.50 | 21.77 | 1215.50 | 21.56 |
Minimum of Months | 145.00 | 20.44 | 43.17 | 20.34 | 2.67 | 20.29 |
Maximum of Months | 509.67 | 23.32 | 347.67 | 24.02 | 347.67 | 24.10 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.01111 | 34.09080 | -0.0212 | 5.85686 |
February | 454.00000 | 23.42024 | 32.61232 | 0.08015 | 5.47441 |
March | 514.00000 | 23.50581 | 31.91699 | 0.10217 | 5.51714 |
April | 485.00000 | 24.12455 | 29.84485 | 0.28971 | 6.99383 |
May | 508.00000 | 24.27394 | 35.10263 | -0.5076 | 10.76863 |
June | 496.00000 | 24.30896 | 42.01819 | -0.4140 | 8.92089 |
July | 497.00000 | 24.36349 | 43.50399 | -0.3816 | 8.40672 |
August | 514.00000 | 24.27554 | 43.36146 | -0.4010 | 8.63434 |
September | 485.00000 | 24.29521 | 41.48775 | -0.4291 | 9.18928 |
October | 502.00000 | 24.00946 | 37.14440 | 0.29489 | 7.07545 |
November | 489.00000 | 23.63640 | 35.69564 | 0.16154 | 5.89278 |
December | 497.00000 | 23.10242 | 31.69862 | -0.0118 | 5.47970 |
Annual Sum or Average | 5943.00000 | 23.86294 | 36.57404 | -0.1055 | 7.36638 |
Minimum of Months | 454.00000 | 23.01111 | 29.84485 | -0.5076 | 5.47441 |
Maximum of Months | 514.00000 | 24.36349 | 43.50399 | 0.29489 | 10.76863 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.45045 | 37.02494 | -0.3678 | 8.51617 |
February | 454.00000 | 21.74695 | 35.99366 | -0.2896 | 7.18506 |
March | 514.00000 | 21.95329 | 35.30976 | -0.2396 | 6.61465 |
April | 485.00000 | 23.41266 | 32.24757 | 0.12314 | 5.88563 |
May | 508.00000 | 23.69867 | 37.32833 | -0.7064 | 16.20412 |
June | 496.00000 | 23.97869 | 43.69566 | -0.5398 | 11.44023 |
July | 497.00000 | 24.04691 | 44.90038 | -0.5025 | 10.66250 |
August | 514.00000 | 24.01290 | 44.81989 | -0.5109 | 10.70700 |
September | 485.00000 | 23.82833 | 43.26418 | -0.6042 | 13.09466 |
October | 502.00000 | 22.84756 | 40.91155 | 0.02662 | 5.71683 |
November | 489.00000 | 21.97711 | 39.70467 | -0.2097 | 6.44442 |
December | 497.00000 | 21.34007 | 34.90987 | -0.4060 | 8.94141 |
Annual Sum or Average | 5943.00000 | 22.86483 | 39.20447 | -0.3538 | 9.30780 |
Minimum of Months | 454.00000 | 21.34007 | 32.24757 | -0.7064 | 5.71683 |
Maximum of Months | 514.00000 | 24.04691 | 44.90038 | 0.12314 | 16.20412 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.78877 | 36.90633 | -0.5542 | 12.59514 |
February | 454.00000 | 20.99603 | 37.41576 | -0.4870 | 10.81982 |
March | 514.00000 | 21.26314 | 36.59316 | -0.4177 | 9.28223 |
April | 485.00000 | 22.84562 | 33.19392 | -0.0118 | 6.13083 |
May | 508.00000 | 23.22992 | 38.32390 | -0.8649 | 22.23565 |
June | 496.00000 | 23.74380 | 44.38721 | -0.6195 | 13.79401 |
July | 497.00000 | 23.83883 | 45.48362 | -0.5708 | 12.59238 |
August | 514.00000 | 23.79329 | 45.42570 | -0.5889 | 12.80065 |
September | 485.00000 | 23.38579 | 44.68929 | -0.7582 | 18.17755 |
October | 502.00000 | 21.96744 | 42.92809 | -0.1887 | 6.76725 |
November | 489.00000 | 21.13423 | 41.50338 | -0.4270 | 9.56297 |
December | 497.00000 | 20.65574 | 36.23134 | -0.5965 | 13.43255 |
Annual Sum or Average | 5943.00000 | 22.31250 | 40.28046 | -0.5082 | 12.37094 |
Minimum of Months | 454.00000 | 20.65574 | 33.19392 | -0.8649 | 6.13083 |
Maximum of Months | 514.00000 | 23.83883 | 45.48362 | -0.0118 | 22.23565 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.20269 | 39.37219 | -0.7367 | 18.15639 |
February | 454.00000 | 20.32454 | 39.82496 | -0.6832 | 16.24660 |
March | 514.00000 | 20.69977 | 38.95606 | -0.5759 | 12.88556 |
April | 485.00000 | 22.21838 | 35.37632 | -0.1618 | 7.61133 |
May | 508.00000 | 22.72181 | 40.19819 | -1.0322 | 29.84485 |
June | 496.00000 | 23.55506 | 45.38594 | -0.6754 | 16.20037 |
July | 497.00000 | 23.70267 | 46.21229 | -0.6074 | 14.24337 |
August | 514.00000 | 23.52924 | 46.69595 | -0.6761 | 16.05208 |
September | 485.00000 | 22.82340 | 46.74911 | -0.9522 | 26.41613 |
October | 502.00000 | 21.17900 | 46.10227 | -0.3863 | 9.42873 |
November | 489.00000 | 20.43802 | 44.01582 | -0.6250 | 14.39565 |
December | 497.00000 | 20.07710 | 38.23787 | -0.7838 | 19.77433 |
Annual Sum or Average | 5943.00000 | 21.80021 | 42.28037 | -0.6586 | 16.78341 |
Minimum of Months | 454.00000 | 20.07710 | 35.37632 | -1.0322 | 7.61133 |
Maximum of Months | 514.00000 | 23.70267 | 46.74911 | -0.1618 | 29.84485 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.30190 | 38.79667 | -0.7029 | 16.92788 |
February | 454.00000 | 20.50233 | 39.10812 | -0.6278 | 14.56415 |
March | 514.00000 | 20.75923 | 38.39716 | -0.5497 | 12.30381 |
April | 485.00000 | 22.83092 | 33.35331 | 0.02800 | 7.84600 |
May | 508.00000 | 23.15831 | 38.51598 | -0.8220 | 23.07177 |
June | 496.00000 | 23.69921 | 44.37803 | -0.5536 | 14.17920 |
July | 497.00000 | 23.97841 | 45.02229 | -0.4394 | 11.75126 |
August | 514.00000 | 23.78212 | 45.21957 | -0.5057 | 12.90546 |
September | 485.00000 | 23.33315 | 44.42724 | -0.7118 | 19.45214 |
October | 502.00000 | 21.46530 | 45.06997 | -0.3018 | 9.04731 |
November | 489.00000 | 20.52117 | 43.48752 | -0.5971 | 13.56409 |
December | 497.00000 | 20.13487 | 37.79846 | -0.7644 | 18.99324 |
Annual Sum or Average | 5943.00000 | 22.04903 | 41.15155 | -0.5462 | 14.55747 |
Minimum of Months | 454.00000 | 20.13487 | 33.35331 | -0.8220 | 7.84600 |
Maximum of Months | 514.00000 | 23.97841 | 45.21957 | 0.02800 | 23.07177 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.85618 | 36.91830 | -0.5511 | 14.45383 |
February | 454.00000 | 21.14798 | 37.04160 | -0.4550 | 12.67500 |
March | 514.00000 | 20.98872 | 37.30841 | -0.4913 | 11.69759 |
April | 485.00000 | 22.80007 | 32.75277 | 0.02510 | 8.60585 |
May | 508.00000 | 22.91545 | 38.61360 | -0.9130 | 27.26916 |
June | 496.00000 | 23.47581 | 44.71563 | -0.6489 | 17.04533 |
July | 497.00000 | 23.73404 | 45.41828 | -0.5333 | 14.43390 |
August | 514.00000 | 23.68860 | 45.14191 | -0.5283 | 14.39008 |
September | 485.00000 | 23.39050 | 43.69385 | -0.6532 | 19.56581 |
October | 502.00000 | 21.87167 | 43.13285 | -0.1866 | 9.15995 |
November | 489.00000 | 21.02181 | 41.70992 | -0.4638 | 12.09532 |
December | 497.00000 | 20.49363 | 36.37497 | -0.6647 | 16.71233 |
Annual Sum or Average | 5943.00000 | 22.20478 | 40.26598 | -0.5070 | 14.87168 |
Minimum of Months | 454.00000 | 20.49363 | 32.75277 | -0.9130 | 8.60585 |
Maximum of Months | 514.00000 | 23.73404 | 45.41828 | 0.02510 | 27.26916 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.31153 | 38.41846 | -0.7050 | 17.26572 |
February | 454.00000 | 20.59770 | 38.55379 | -0.6063 | 14.87356 |
March | 514.00000 | 20.73588 | 38.06323 | -0.5584 | 12.73014 |
April | 485.00000 | 22.34571 | 34.15374 | -0.0900 | 8.38891 |
May | 508.00000 | 22.73579 | 39.35415 | -0.9584 | 29.28422 |
June | 496.00000 | 23.44898 | 45.10436 | -0.6274 | 17.04620 |
July | 497.00000 | 23.64594 | 46.05022 | -0.5389 | 14.93022 |
August | 514.00000 | 23.48426 | 46.27975 | -0.6104 | 16.27213 |
September | 485.00000 | 22.84132 | 45.82252 | -0.8788 | 25.73837 |
October | 502.00000 | 21.28906 | 45.08808 | -0.3447 | 9.44336 |
November | 489.00000 | 20.52393 | 43.09939 | -0.6006 | 13.93610 |
December | 497.00000 | 20.10432 | 37.52212 | -0.7789 | 19.55393 |
Annual Sum or Average | 5943.00000 | 21.84760 | 41.48397 | -0.6090 | 16.64212 |
Minimum of Months | 454.00000 | 20.10432 | 34.15374 | -0.9584 | 8.38891 |
Maximum of Months | 514.00000 | 23.64594 | 46.27975 | -0.0900 | 29.28422 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.48752 | 38.90929 | -0.6484 | 14.74896 |
February | 454.00000 | 20.59550 | 39.33974 | -0.5991 | 13.03386 |
March | 514.00000 | 20.83853 | 38.44558 | -0.5301 | 11.28955 |
April | 485.00000 | 22.09085 | 35.55761 | -0.1950 | 6.78389 |
May | 508.00000 | 22.75631 | 40.33634 | -1.0364 | 28.94432 |
June | 496.00000 | 23.57412 | 45.80292 | -0.6936 | 15.88019 |
July | 497.00000 | 23.76361 | 46.55555 | -0.6103 | 13.42926 |
August | 514.00000 | 23.58446 | 47.03939 | -0.6752 | 15.19090 |
September | 485.00000 | 23.11690 | 46.36898 | -0.8605 | 21.64465 |
October | 502.00000 | 21.70669 | 44.40520 | -0.2422 | 6.94166 |
November | 489.00000 | 20.90178 | 42.89706 | -0.4775 | 10.24525 |
December | 497.00000 | 20.48064 | 37.52128 | -0.6515 | 14.48668 |
Annual Sum or Average | 5943.00000 | 22.00141 | 41.95352 | -0.6027 | 14.41516 |
Minimum of Months | 454.00000 | 20.48064 | 35.55761 | -1.0364 | 6.78389 |
Maximum of Months | 514.00000 | 23.76361 | 47.03939 | -0.1950 | 28.94432 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.61015 | 39.20418 | -0.6057 | 13.48654 |
February | 454.00000 | 20.81408 | 39.32332 | -0.5322 | 11.51598 |
March | 514.00000 | 20.94382 | 38.60111 | -0.4940 | 10.63301 |
April | 485.00000 | 23.12496 | 33.26160 | 0.08274 | 6.86956 |
May | 508.00000 | 23.54309 | 38.12853 | -0.7217 | 18.25680 |
June | 496.00000 | 23.92550 | 44.18356 | -0.5110 | 11.91126 |
July | 497.00000 | 24.19382 | 44.79457 | -0.3971 | 9.73536 |
August | 514.00000 | 24.04994 | 44.84368 | -0.4393 | 10.18018 |
September | 485.00000 | 23.85313 | 43.46748 | -0.5492 | 13.03143 |
October | 502.00000 | 22.14532 | 43.63423 | -0.1240 | 6.81627 |
November | 489.00000 | 21.02047 | 43.09941 | -0.4390 | 9.57056 |
December | 497.00000 | 20.53166 | 37.82928 | -0.6316 | 13.95348 |
Annual Sum or Average | 5943.00000 | 22.40594 | 40.88270 | -0.4476 | 11.34209 |
Minimum of Months | 454.00000 | 20.53166 | 33.26160 | -0.7217 | 6.81627 |
Maximum of Months | 514.00000 | 24.19382 | 44.84368 | 0.08274 | 18.25680 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.39196 | 35.82814 | -0.6042 | 15.15273 |
February | 454.00000 | 20.66389 | 36.20221 | -0.5111 | 12.54566 |
March | 514.00000 | 20.40476 | 35.93787 | -0.5904 | 13.46178 |
April | 485.00000 | 22.25900 | 32.63883 | -0.0820 | 8.04880 |
May | 508.00000 | 22.35668 | 39.02809 | -1.0688 | 32.55901 |
June | 496.00000 | 22.97714 | 45.70032 | -0.8058 | 21.43913 |
July | 497.00000 | 23.52760 | 46.20610 | -0.6065 | 15.14662 |
August | 514.00000 | 23.66159 | 45.57027 | -0.5370 | 13.46377 |
September | 485.00000 | 23.57253 | 43.11979 | -0.5740 | 15.55960 |
October | 502.00000 | 21.95687 | 41.43800 | -0.1207 | 8.04018 |
November | 489.00000 | 20.86706 | 40.10720 | -0.4347 | 10.83805 |
December | 497.00000 | 20.17950 | 35.01486 | -0.6759 | 16.19519 |
Annual Sum or Average | 5943.00000 | 21.90799 | 39.76685 | -0.5529 | 15.25809 |
Minimum of Months | 454.00000 | 20.17950 | 32.63883 | -1.0688 | 8.04018 |
Maximum of Months | 514.00000 | 23.66159 | 46.20610 | -0.0820 | 32.55901 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.59508 | 38.72083 | -0.6134 | 13.82605 |
February | 454.00000 | 20.86829 | 38.69510 | -0.5181 | 11.51889 |
March | 514.00000 | 20.88625 | 38.17854 | -0.5089 | 10.98088 |
April | 485.00000 | 22.63713 | 34.04907 | -0.0371 | 6.93907 |
May | 508.00000 | 23.20455 | 38.73555 | -0.8328 | 22.62259 |
June | 496.00000 | 23.83575 | 44.45232 | -0.5350 | 12.59834 |
July | 497.00000 | 23.99696 | 45.38968 | -0.4548 | 10.97102 |
August | 514.00000 | 23.90033 | 45.53020 | -0.5013 | 11.50199 |
September | 485.00000 | 23.50292 | 44.63947 | -0.6781 | 16.59287 |
October | 502.00000 | 21.91258 | 43.76086 | -0.1769 | 6.97969 |
November | 489.00000 | 20.96043 | 42.69764 | -0.4549 | 9.93896 |
December | 497.00000 | 20.48987 | 37.42152 | -0.6501 | 14.46620 |
Annual Sum or Average | 5943.00000 | 22.24151 | 41.04424 | -0.4977 | 12.43257 |
Minimum of Months | 454.00000 | 20.48987 | 34.04907 | -0.8328 | 6.93907 |
Maximum of Months | 514.00000 | 23.99696 | 45.53020 | -0.0371 | 22.62259 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.54757 | 38.68967 | -0.6171 | 14.07503 |
February | 454.00000 | 20.71056 | 39.10199 | -0.5529 | 12.06234 |
March | 514.00000 | 21.06754 | 38.24895 | -0.4558 | 9.97650 |
April | 485.00000 | 22.72034 | 34.51277 | -0.0352 | 6.31837 |
May | 508.00000 | 23.23113 | 39.10605 | -0.8589 | 22.01886 |
June | 496.00000 | 23.83553 | 44.54869 | -0.5807 | 12.73177 |
July | 497.00000 | 23.94247 | 45.49745 | -0.5278 | 11.44678 |
August | 514.00000 | 23.80137 | 45.90674 | -0.5820 | 12.63219 |
September | 485.00000 | 23.32870 | 45.27830 | -0.7790 | 18.98879 |
October | 502.00000 | 21.81807 | 44.60779 | -0.2132 | 7.00698 |
November | 489.00000 | 20.88021 | 43.05749 | -0.4812 | 10.49885 |
December | 497.00000 | 20.42577 | 37.53556 | -0.6586 | 14.94518 |
Annual Sum or Average | 5943.00000 | 22.20290 | 41.36074 | -0.5293 | 12.73862 |
Minimum of Months | 454.00000 | 20.42577 | 34.51277 | -0.8589 | 6.31837 |
Maximum of Months | 514.00000 | 23.94247 | 45.90674 | -0.0352 | 22.01886 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.53827 | 37.68454 | -0.6149 | 13.88615 |
February | 385.00000 | 20.79548 | 37.64741 | -0.5283 | 11.54892 |
March | 433.00000 | 20.98829 | 37.21049 | -0.4687 | 10.25686 |
April | 410.00000 | 23.06073 | 32.59076 | 0.08331 | 7.20034 |
May | 430.00000 | 23.43753 | 37.37315 | -0.7335 | 19.30008 |
June | 418.00000 | 23.87726 | 43.50631 | -0.5071 | 12.45269 |
July | 422.00000 | 24.15915 | 44.27816 | -0.3976 | 10.53327 |
August | 433.00000 | 23.93530 | 44.60025 | -0.4693 | 11.49600 |
September | 410.00000 | 23.60207 | 43.34509 | -0.6262 | 16.06638 |
October | 427.00000 | 21.85261 | 43.26348 | -0.1925 | 7.40039 |
November | 417.00000 | 20.84622 | 41.96605 | -0.4865 | 10.56955 |
December | 422.00000 | 20.37562 | 36.56910 | -0.6693 | 15.19435 |
Annual Sum or Average | 5034.00000 | 22.29563 | 40.02588 | -0.4683 | 12.16982 |
Minimum of Months | 385.00000 | 20.37562 | 32.59076 | -0.7335 | 7.20034 |
Maximum of Months | 433.00000 | 24.15915 | 44.60025 | 0.08331 | 19.30008 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.26501 | 36.22855 | -0.4210 | 11.26904 |
February | 454.00000 | 21.59976 | 36.24398 | -0.3151 | 9.79354 |
March | 514.00000 | 21.39627 | 36.60107 | -0.3652 | 9.14584 |
April | 485.00000 | 23.21731 | 32.01350 | 0.13160 | 7.74518 |
May | 508.00000 | 23.37048 | 37.65133 | -0.7574 | 20.23179 |
June | 496.00000 | 23.78747 | 43.90544 | -0.5484 | 13.06628 |
July | 497.00000 | 23.99920 | 44.69949 | -0.4503 | 11.24666 |
August | 514.00000 | 23.96621 | 44.45049 | -0.4377 | 11.07082 |
September | 485.00000 | 23.78343 | 42.56892 | -0.5161 | 14.03020 |
October | 502.00000 | 22.41763 | 41.83081 | -0.0349 | 7.65050 |
November | 489.00000 | 21.51286 | 40.73769 | -0.3130 | 9.21828 |
December | 497.00000 | 20.90480 | 35.62869 | -0.5282 | 12.66196 |
Annual Sum or Average | 5943.00000 | 22.60719 | 39.41130 | -0.3815 | 11.44965 |
Minimum of Months | 454.00000 | 20.90480 | 32.01350 | -0.7574 | 7.65050 |
Maximum of Months | 514.00000 | 23.99920 | 44.69949 | 0.13160 | 20.23179 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.64066 | 37.93633 | -0.5880 | 13.43110 |
February | 454.00000 | 20.97167 | 37.93475 | -0.4791 | 11.21688 |
March | 514.00000 | 21.05800 | 37.51277 | -0.4469 | 10.03821 |
April | 485.00000 | 22.80673 | 33.41368 | 0.02698 | 7.21616 |
May | 508.00000 | 23.22289 | 38.35375 | -0.7930 | 21.69522 |
June | 496.00000 | 23.78693 | 44.25849 | -0.5191 | 12.84955 |
July | 497.00000 | 23.93903 | 45.27118 | -0.4473 | 11.48081 |
August | 514.00000 | 23.81485 | 45.49322 | -0.5028 | 12.26821 |
September | 485.00000 | 23.35115 | 44.47484 | -0.7067 | 18.38984 |
October | 502.00000 | 21.81353 | 43.90167 | -0.1937 | 7.36108 |
November | 489.00000 | 20.90813 | 42.36138 | -0.4675 | 10.40531 |
December | 497.00000 | 20.44491 | 36.89316 | -0.6552 | 14.85082 |
Annual Sum or Average | 5943.00000 | 22.23840 | 40.67514 | -0.4820 | 12.61721 |
Minimum of Months | 454.00000 | 20.44491 | 33.41368 | -0.7930 | 7.21616 |
Maximum of Months | 514.00000 | 23.93903 | 45.49322 | 0.02698 | 21.69522 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.145744E+10 | 0.365058E+09 | 49.56 | 0.137963E+10 | 77806425.17 | 0.00 | 0.88 | 28-APR-15:20 | 0.00 | 01-APR-00:10 | 22414.54 | 28-APR-15:20 | 22414.54 | 28-APR-15:20 | 5032.90 | 28-APR-08:00 | 5042.26 | 28-APR-15:20 | 0.00 |
May | 0.236826E+10 | 0.563812E+09 | 58.92 | 0.200455E+10 | 0.363706E+09 | 0.00 | 1.00 | 22-MAY-12:50 | 0.00 | 01-MAY-00:10 | 37945.30 | 22-MAY-15:10 | 37945.30 | 22-MAY-15:10 | 5053.55 | 23-MAY-15:20 | 8257.34 | 22-MAY-15:10 | 0.00 |
June | 0.819228E+10 | 0.190259E+10 | 149.89 | 0.677310E+10 | 0.141918E+10 | 0.00 | 1.00 | 12-JUN-12:10 | 0.00 | 01-JUN-00:10 | 56899.14 | 13-JUN-16:00 | 51727.21 | 13-JUN-16:00 | 19246.51 | 25-JUN-17:52 | 13198.91 | 13-JUN-16:00 | 0.00 |
July | 0.138704E+11 | 0.328507E+10 | 272.09 | 0.112450E+11 | 0.262533E+10 | 0.00 | 1.00 | 06-JUL-15:10 | 0.00 | 01-JUL-00:10 | 52994.31 | 21-JUL-16:00 | 52994.31 | 21-JUL-16:00 | 11352.17 | 24-JUL-15:40 | 12878.35 | 21-JUL-17:00 | 0.00 |
August | 0.179454E+11 | 0.424005E+10 | 355.93 | 0.141279E+11 | 0.381750E+10 | 0.00 | 1.00 | 14-AUG-09:10 | 0.00 | 01-AUG-00:10 | 51745.81 | 14-AUG-15:50 | 50787.40 | 14-AUG-16:00 | 10835.38 | 08-AUG-13:00 | 11838.84 | 14-AUG-16:00 | 0.00 |
September | 0.894291E+10 | 0.210331E+10 | 193.99 | 0.734793E+10 | 0.159499E+10 | 0.00 | 1.00 | 11-SEP-12:30 | 0.00 | 01-SEP-00:10 | 43944.24 | 13-SEP-15:30 | 39984.18 | 13-SEP-15:30 | 10531.66 | 12-SEP-14:00 | 9547.28 | 13-SEP-15:30 | 0.00 |
October | 0.301617E+09 | 80778555.25 | 22.08 | 0.286731E+09 | 14886473.40 | 0.00 | 0.40 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 8801.15 | 07-OCT-15:00 | 8801.15 | 07-OCT-15:00 | 1383.87 | 17-OCT-15:00 | 2257.58 | 07-OCT-15:00 | 0.00 |
November | 3123919.91 | 865012.61 | 0.67 | 2141851.30 | 982068.61 | 0.00 | 0.11 | 24-NOV-12:00 | 0.00 | 01-NOV-00:10 | 2325.27 | 24-NOV-12:00 | 1625.30 | 24-NOV-12:00 | 699.96 | 24-NOV-12:00 | 639.10 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.530814E+11 | 0.125415E+11 | 1103.13 | 0.431671E+11 | 0.991437E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.179454E+11 | 0.424005E+10 | 355.93 | 0.141279E+11 | 0.381750E+10 | 0.00 | 1.00 | 0.00 | 56899.14 | 52994.31 | 19246.51 | 13198.91 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.154594E+10 | 0.344660E+09 | 50.17 | 0.149612E+10 | 49817488.45 | 0.00 | 1.00 | 28-APR-15:00 | 0.00 | 01-APR-00:10 | 33435.52 | 30-APR-16:12 | 33435.52 | 30-APR-16:12 | 3183.30 | 28-APR-08:00 | 6652.12 | 30-APR-16:12 | 0.00 |
May | 0.233469E+10 | 0.502097E+09 | 62.71 | 0.200194E+10 | 0.332746E+09 | 0.00 | 1.00 | 22-MAY-12:40 | 0.00 | 01-MAY-00:10 | 37159.07 | 22-MAY-15:00 | 37159.07 | 22-MAY-15:00 | 4887.43 | 23-MAY-15:20 | 7391.05 | 22-MAY-15:00 | 0.00 |
June | 0.788224E+10 | 0.166094E+10 | 155.18 | 0.654491E+10 | 0.133732E+10 | 0.00 | 1.00 | 12-JUN-12:00 | 0.00 | 01-JUN-00:10 | 53990.96 | 13-JUN-15:30 | 48728.53 | 13-JUN-15:30 | 15532.54 | 25-JUN-17:53 | 11351.29 | 13-JUN-16:00 | 0.00 |
July | 0.131745E+11 | 0.282533E+10 | 275.82 | 0.107253E+11 | 0.244918E+10 | 0.00 | 1.00 | 06-JUL-13:50 | 0.00 | 01-JUL-00:10 | 48699.74 | 21-JUL-15:40 | 48699.74 | 21-JUL-15:40 | 13164.29 | 23-JUL-16:12 | 10624.41 | 21-JUL-16:00 | 0.00 |
August | 0.164400E+11 | 0.352230E+10 | 360.74 | 0.130090E+11 | 0.343108E+10 | 0.00 | 1.00 | 07-AUG-15:00 | 0.00 | 01-AUG-00:10 | 47896.41 | 14-AUG-15:30 | 46448.00 | 14-AUG-15:50 | 10510.89 | 18-AUG-15:30 | 9905.38 | 14-AUG-15:50 | 0.00 |
September | 0.824656E+10 | 0.176113E+10 | 199.32 | 0.678102E+10 | 0.146554E+10 | 0.00 | 1.00 | 11-SEP-12:20 | 0.00 | 01-SEP-00:10 | 40348.55 | 13-SEP-14:50 | 36649.49 | 13-SEP-14:50 | 10675.64 | 12-SEP-14:00 | 7983.18 | 13-SEP-14:50 | 0.00 |
October | 0.283178E+09 | 68746470.92 | 22.17 | 0.270699E+09 | 12478674.45 | 0.00 | 0.49 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 9839.41 | 07-OCT-15:00 | 9839.41 | 07-OCT-15:00 | 1154.19 | 17-OCT-15:00 | 2244.15 | 07-OCT-15:00 | 0.00 |
November | 3142264.78 | 790873.31 | 0.67 | 2181662.52 | 960602.27 | 0.00 | 0.12 | 24-NOV-12:00 | 0.00 | 01-NOV-00:10 | 2267.67 | 24-NOV-12:00 | 1608.87 | 24-NOV-12:00 | 658.80 | 24-NOV-12:00 | 566.12 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.499103E+11 | 0.106860E+11 | 1126.76 | 0.408312E+11 | 0.907912E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.164400E+11 | 0.352230E+10 | 360.74 | 0.130090E+11 | 0.343108E+10 | 0.00 | 1.00 | 0.00 | 53990.96 | 48728.53 | 15532.54 | 11351.29 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 |
April | 0.158367E+10 | 0.390802E+09 | 49.75 | 0.151904E+10 | 64634947.86 | 0.00 | 1.00 | 30-APR-12:02 | 0.00 | 01-APR-00:10 | 42221.93 | 30-APR-15:22 | 42221.93 | 30-APR-15:22 | 2556.09 | 28-APR-08:00 | 9220.37 | 30-APR-15:22 | 0.00 |
May | 0.241670E+10 | 0.574758E+09 | 61.17 | 0.205291E+10 | 0.363785E+09 | 0.00 | 1.00 | 22-MAY-12:50 | 0.00 | 01-MAY-00:10 | 40846.45 | 22-MAY-15:00 | 40846.45 | 22-MAY-15:00 | 5299.86 | 23-MAY-15:20 | 8920.74 | 22-MAY-15:00 | 0.00 |
June | 0.820481E+10 | 0.190702E+10 | 151.05 | 0.678305E+10 | 0.142176E+10 | 0.00 | 1.00 | 12-JUN-12:10 | 0.00 | 01-JUN-00:10 | 62776.84 | 13-JUN-14:40 | 57137.26 | 13-JUN-15:30 | 18533.94 | 25-JUN-18:02 | 14430.93 | 13-JUN-15:40 | 0.00 |
July | 0.135442E+11 | 0.321278E+10 | 270.77 | 0.110139E+11 | 0.253029E+10 | 0.00 | 1.00 | 06-JUL-14:20 | 0.00 | 01-JUL-00:10 | 57005.92 | 21-JUL-15:40 | 57005.92 | 21-JUL-15:40 | 11605.56 | 24-JUL-15:30 | 13645.29 | 21-JUL-15:50 | 0.00 |
August | 0.162737E+11 | 0.387363E+10 | 357.78 | 0.127273E+11 | 0.354641E+10 | 0.00 | 1.00 | 13-AUG-13:23 | 0.00 | 01-AUG-00:10 | 53173.56 | 14-AUG-15:50 | 53173.56 | 14-AUG-15:50 | 10767.58 | 18-AUG-15:30 | 12146.00 | 14-AUG-16:00 | 0.00 |
September | 0.784204E+10 | 0.186130E+10 | 190.57 | 0.637490E+10 | 0.146713E+10 | 0.00 | 1.00 | 10-SEP-12:52 | 0.00 | 01-SEP-00:10 | 40923.78 | 13-SEP-15:20 | 37402.88 | 13-SEP-15:20 | 10314.22 | 12-SEP-14:00 | 8892.47 | 13-SEP-15:20 | 0.00 |
October | 0.255554E+09 | 68720467.00 | 21.50 | 0.240651E+09 | 14902849.47 | 0.00 | 0.43 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 9615.21 | 07-OCT-15:00 | 9615.21 | 07-OCT-15:00 | 1181.91 | 17-OCT-15:00 | 2443.54 | 07-OCT-15:00 | 0.00 |
November | 3087308.20 | 854830.40 | 0.67 | 2115878.55 | 971429.65 | 0.00 | 0.11 | 24-NOV-12:00 | 0.00 | 01-NOV-00:10 | 2305.88 | 24-NOV-12:00 | 1612.10 | 24-NOV-12:00 | 693.77 | 24-NOV-12:00 | 633.75 | 24-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.501237E+11 | 0.118899E+11 | 1103.25 | 0.407138E+11 | 0.940989E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.162737E+11 | 0.387363E+10 | 357.78 | 0.127273E+11 | 0.354641E+10 | 0.00 | 1.00 | 0.00 | 62776.84 | 57137.26 | 18533.94 | 14430.93 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.37 | 0.00 | 235.37 | 26.86 | 1274.65 | 0.00 | 0.00 | 0.00 |
February | 367.54 | 0.00 | 367.54 | 76.98 | 1196.43 | 0.00 | 0.00 | 0.00 |
March | 508.61 | 0.00 | 508.61 | 206.94 | 981.82 | 0.00 | 0.00 | 0.00 |
April | 828.09 | 3.71 | 824.39 | 559.98 | 838.10 | 0.00 | 0.00 | 0.00 |
May | 1035.33 | 49.95 | 985.38 | 704.05 | 686.90 | 0.00 | 0.00 | 0.00 |
June | 1144.49 | 71.77 | 1072.72 | 974.47 | 553.12 | 0.00 | 0.00 | 0.00 |
July | 1085.61 | 61.90 | 1023.71 | 984.21 | 513.57 | 0.00 | 0.00 | 0.00 |
August | 853.35 | 13.37 | 839.98 | 758.98 | 569.83 | 0.00 | 0.00 | 0.00 |
September | 649.51 | 0.14 | 649.37 | 507.03 | 745.63 | 0.00 | 0.00 | 0.00 |
October | 416.20 | 0.00 | 416.20 | 201.86 | 929.87 | 0.00 | 0.00 | 0.00 |
November | 250.08 | 0.00 | 250.08 | 40.94 | 1117.77 | 0.00 | 0.00 | 0.00 |
December | 170.30 | 0.00 | 170.30 | 4.46 | 1372.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 629.87 | 16.85 | 613.02 | 422.29 | 896.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 170.30 | 0.00 | 170.30 | 4.46 | 513.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1144.49 | 71.77 | 1072.72 | 984.21 | 1372.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 320.72 | 128.83 | 191.89 | 202.76 | 800.61 | 0.00 | 0.00 | 0.00 |
February | 478.25 | 176.67 | 301.58 | 333.38 | 759.70 | 0.00 | 0.00 | 0.00 |
March | 499.78 | 98.49 | 401.29 | 334.36 | 624.43 | 0.00 | 0.00 | 0.00 |
April | 1341.96 | 630.59 | 711.36 | 1421.22 | 539.11 | 0.00 | 0.00 | 0.00 |
May | 1411.03 | 615.32 | 795.70 | 1451.02 | 471.91 | 0.00 | 0.00 | 0.00 |
June | 1396.66 | 557.81 | 838.85 | 1521.45 | 377.42 | 0.00 | 0.00 | 0.00 |
July | 1425.71 | 605.93 | 819.79 | 1618.28 | 351.64 | 0.00 | 0.00 | 0.00 |
August | 1350.55 | 645.28 | 705.27 | 1579.00 | 379.87 | 0.00 | 0.00 | 0.00 |
September | 1216.22 | 646.73 | 569.49 | 1380.90 | 477.12 | 0.00 | 0.00 | 0.00 |
October | 587.08 | 243.30 | 343.78 | 539.59 | 601.24 | 0.00 | 0.00 | 0.00 |
November | 306.06 | 104.31 | 201.75 | 192.29 | 713.18 | 0.00 | 0.00 | 0.00 |
December | 226.83 | 84.33 | 142.50 | 125.25 | 874.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 881.35 | 378.62 | 502.73 | 893.61 | 579.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.83 | 84.33 | 142.50 | 125.25 | 351.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1425.71 | 646.73 | 838.85 | 1618.28 | 874.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1336.25 | 865.01 | 471.24 | 1357.65 | 1163.48 | 0.00 | 0.00 | 0.00 |
February | 1631.98 | 995.86 | 636.12 | 1695.65 | 1148.62 | 0.00 | 0.00 | 0.00 |
March | 1009.00 | 293.77 | 715.22 | 861.52 | 956.85 | 0.00 | 0.00 | 0.00 |
April | 2095.27 | 947.03 | 1148.23 | 2409.15 | 879.46 | 0.00 | 0.00 | 0.00 |
May | 1732.98 | 564.20 | 1168.78 | 1843.98 | 771.47 | 0.00 | 0.00 | 0.00 |
June | 1596.45 | 386.43 | 1210.02 | 1761.27 | 607.97 | 0.00 | 0.00 | 0.00 |
July | 1729.72 | 541.68 | 1188.04 | 2049.41 | 568.43 | 0.00 | 0.00 | 0.00 |
August | 2026.85 | 911.75 | 1115.10 | 2539.80 | 614.93 | 0.00 | 0.00 | 0.00 |
September | 2395.21 | 1403.15 | 992.06 | 2976.21 | 768.25 | 0.00 | 0.00 | 0.00 |
October | 1645.61 | 961.78 | 683.82 | 1844.55 | 927.51 | 0.00 | 0.00 | 0.00 |
November | 1166.73 | 709.75 | 456.98 | 1189.72 | 1075.14 | 0.00 | 0.00 | 0.00 |
December | 924.74 | 592.49 | 332.26 | 912.44 | 1308.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1605.11 | 761.44 | 843.67 | 1784.27 | 897.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 924.74 | 293.77 | 332.26 | 861.52 | 568.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2395.21 | 1403.15 | 1210.02 | 2976.21 | 1308.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 311.89 | 103.05 | 208.84 | 201.44 | 815.71 | 0.00 | 0.00 | 0.00 |
February | 552.21 | 233.16 | 319.05 | 457.08 | 784.82 | 0.00 | 0.00 | 0.00 |
March | 499.32 | 95.52 | 403.80 | 333.45 | 634.13 | 0.00 | 0.00 | 0.00 |
April | 1178.16 | 467.97 | 710.18 | 1233.22 | 569.95 | 0.00 | 0.00 | 0.00 |
May | 1382.25 | 562.07 | 820.18 | 1430.65 | 497.62 | 0.00 | 0.00 | 0.00 |
June | 1492.68 | 614.48 | 878.20 | 1657.31 | 399.51 | 0.00 | 0.00 | 0.00 |
July | 1520.23 | 670.27 | 849.96 | 1759.41 | 374.29 | 0.00 | 0.00 | 0.00 |
August | 1276.89 | 552.86 | 724.03 | 1494.78 | 405.27 | 0.00 | 0.00 | 0.00 |
September | 1024.41 | 459.37 | 565.04 | 1158.59 | 505.37 | 0.00 | 0.00 | 0.00 |
October | 546.48 | 196.51 | 349.97 | 500.47 | 619.38 | 0.00 | 0.00 | 0.00 |
November | 295.74 | 86.33 | 209.41 | 193.67 | 734.39 | 0.00 | 0.00 | 0.00 |
December | 167.40 | 35.32 | 132.07 | 67.58 | 906.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.87 | 339.88 | 514.99 | 875.35 | 602.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 167.40 | 35.32 | 132.07 | 67.58 | 374.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1520.23 | 670.27 | 878.20 | 1759.41 | 906.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.45 | 0.00 | 78.45 | 8.20 | 444.54 | 0.00 | 0.00 | 0.00 |
February | 122.51 | 0.00 | 122.51 | 24.34 | 417.32 | 0.00 | 0.00 | 0.00 |
March | 169.53 | 0.00 | 169.53 | 69.39 | 339.90 | 0.00 | 0.00 | 0.00 |
April | 276.02 | 1.24 | 274.78 | 194.19 | 282.71 | 0.00 | 0.00 | 0.00 |
May | 345.09 | 16.65 | 328.44 | 241.15 | 232.67 | 0.00 | 0.00 | 0.00 |
June | 381.48 | 23.92 | 357.56 | 332.38 | 185.92 | 0.00 | 0.00 | 0.00 |
July | 361.85 | 20.63 | 341.22 | 333.78 | 173.21 | 0.00 | 0.00 | 0.00 |
August | 284.44 | 4.46 | 279.98 | 257.55 | 192.98 | 0.00 | 0.00 | 0.00 |
September | 216.49 | 0.05 | 216.45 | 169.12 | 259.25 | 0.00 | 0.00 | 0.00 |
October | 138.73 | 0.00 | 138.73 | 63.64 | 334.69 | 0.00 | 0.00 | 0.00 |
November | 83.35 | 0.00 | 83.35 | 11.46 | 403.11 | 0.00 | 0.00 | 0.00 |
December | 56.76 | 0.00 | 56.76 | 0.67 | 488.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 209.95 | 5.62 | 204.33 | 142.75 | 312.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.76 | 0.00 | 56.76 | 0.67 | 173.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 381.48 | 23.92 | 357.56 | 333.78 | 488.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.46 | 0.00 | 78.46 | 8.20 | 444.57 | 0.00 | 0.00 | 0.00 |
February | 122.51 | 0.00 | 122.51 | 24.34 | 417.35 | 0.00 | 0.00 | 0.00 |
March | 169.54 | 0.00 | 169.54 | 69.40 | 339.92 | 0.00 | 0.00 | 0.00 |
April | 276.04 | 1.24 | 274.80 | 194.20 | 282.73 | 0.00 | 0.00 | 0.00 |
May | 345.11 | 16.65 | 328.46 | 241.17 | 232.69 | 0.00 | 0.00 | 0.00 |
June | 381.50 | 23.92 | 357.58 | 332.40 | 185.93 | 0.00 | 0.00 | 0.00 |
July | 361.88 | 20.63 | 341.24 | 333.80 | 173.22 | 0.00 | 0.00 | 0.00 |
August | 284.45 | 4.46 | 280.00 | 257.57 | 193.00 | 0.00 | 0.00 | 0.00 |
September | 216.51 | 0.05 | 216.46 | 169.13 | 259.26 | 0.00 | 0.00 | 0.00 |
October | 138.74 | 0.00 | 138.74 | 63.65 | 334.71 | 0.00 | 0.00 | 0.00 |
November | 83.36 | 0.00 | 83.36 | 11.46 | 403.14 | 0.00 | 0.00 | 0.00 |
December | 56.77 | 0.00 | 56.77 | 0.67 | 488.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 209.96 | 5.62 | 204.34 | 142.75 | 312.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.77 | 0.00 | 56.77 | 0.67 | 173.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 381.50 | 23.92 | 357.58 | 333.80 | 488.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.46 | 0.00 | 78.46 | 8.20 | 444.57 | 0.00 | 0.00 | 0.00 |
February | 122.51 | 0.00 | 122.51 | 24.34 | 417.35 | 0.00 | 0.00 | 0.00 |
March | 169.54 | 0.00 | 169.54 | 69.40 | 339.92 | 0.00 | 0.00 | 0.00 |
April | 276.04 | 1.24 | 274.80 | 194.20 | 282.73 | 0.00 | 0.00 | 0.00 |
May | 345.11 | 16.65 | 328.46 | 241.17 | 232.69 | 0.00 | 0.00 | 0.00 |
June | 381.50 | 23.92 | 357.58 | 332.40 | 185.93 | 0.00 | 0.00 | 0.00 |
July | 361.88 | 20.63 | 341.24 | 333.80 | 173.22 | 0.00 | 0.00 | 0.00 |
August | 284.45 | 4.46 | 280.00 | 257.57 | 193.00 | 0.00 | 0.00 | 0.00 |
September | 216.51 | 0.05 | 216.46 | 169.13 | 259.26 | 0.00 | 0.00 | 0.00 |
October | 138.74 | 0.00 | 138.74 | 63.65 | 334.71 | 0.00 | 0.00 | 0.00 |
November | 83.36 | 0.00 | 83.36 | 11.46 | 403.14 | 0.00 | 0.00 | 0.00 |
December | 56.77 | 0.00 | 56.77 | 0.67 | 488.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 209.96 | 5.62 | 204.34 | 142.75 | 312.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 56.77 | 0.00 | 56.77 | 0.67 | 173.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 381.50 | 23.92 | 357.58 | 333.80 | 488.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 308.52 | 123.93 | 184.59 | 192.20 | 809.31 | 0.00 | 0.00 | 0.00 |
February | 460.06 | 169.95 | 290.11 | 316.80 | 768.45 | 0.00 | 0.00 | 0.00 |
March | 480.77 | 94.74 | 386.03 | 321.61 | 626.13 | 0.00 | 0.00 | 0.00 |
April | 1290.91 | 606.60 | 684.30 | 1372.93 | 543.40 | 0.00 | 0.00 | 0.00 |
May | 1357.35 | 591.91 | 765.43 | 1399.82 | 478.03 | 0.00 | 0.00 | 0.00 |
June | 1343.53 | 536.59 | 806.94 | 1472.05 | 377.19 | 0.00 | 0.00 | 0.00 |
July | 1371.48 | 582.87 | 788.60 | 1563.86 | 353.55 | 0.00 | 0.00 | 0.00 |
August | 1299.17 | 620.73 | 678.44 | 1523.62 | 385.75 | 0.00 | 0.00 | 0.00 |
September | 1169.95 | 622.12 | 547.83 | 1325.44 | 495.16 | 0.00 | 0.00 | 0.00 |
October | 564.75 | 234.05 | 330.70 | 509.39 | 633.72 | 0.00 | 0.00 | 0.00 |
November | 294.42 | 100.34 | 194.08 | 178.02 | 744.76 | 0.00 | 0.00 | 0.00 |
December | 218.20 | 81.12 | 137.08 | 116.22 | 896.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 847.82 | 364.21 | 483.60 | 859.59 | 591.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 218.20 | 81.12 | 137.08 | 116.22 | 353.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1371.48 | 622.12 | 806.94 | 1563.86 | 896.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.20 | 4.90 | 7.30 | 7.60 | 32.00 | 0.00 | 0.00 | 0.00 |
February | 18.19 | 6.72 | 11.47 | 12.53 | 30.38 | 0.00 | 0.00 | 0.00 |
March | 19.01 | 3.75 | 15.26 | 12.72 | 24.76 | 0.00 | 0.00 | 0.00 |
April | 51.04 | 23.98 | 27.06 | 54.28 | 21.49 | 0.00 | 0.00 | 0.00 |
May | 53.67 | 23.40 | 30.26 | 55.35 | 18.90 | 0.00 | 0.00 | 0.00 |
June | 53.12 | 21.22 | 31.91 | 58.20 | 14.91 | 0.00 | 0.00 | 0.00 |
July | 54.23 | 23.05 | 31.18 | 61.83 | 13.98 | 0.00 | 0.00 | 0.00 |
August | 51.37 | 24.54 | 26.83 | 60.24 | 15.25 | 0.00 | 0.00 | 0.00 |
September | 46.26 | 24.60 | 21.66 | 52.41 | 19.58 | 0.00 | 0.00 | 0.00 |
October | 22.33 | 9.25 | 13.08 | 20.14 | 25.06 | 0.00 | 0.00 | 0.00 |
November | 11.64 | 3.97 | 7.67 | 7.04 | 29.45 | 0.00 | 0.00 | 0.00 |
December | 8.63 | 3.21 | 5.42 | 4.60 | 35.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 33.52 | 14.40 | 19.12 | 33.99 | 23.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.63 | 3.21 | 5.42 | 4.60 | 13.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.23 | 24.60 | 31.91 | 61.83 | 35.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 445.43 | 288.34 | 157.08 | 456.31 | 403.96 | 0.00 | 0.00 | 0.00 |
February | 544.01 | 331.96 | 212.05 | 570.77 | 400.95 | 0.00 | 0.00 | 0.00 |
March | 336.34 | 97.93 | 238.42 | 294.34 | 326.60 | 0.00 | 0.00 | 0.00 |
April | 698.44 | 315.69 | 382.76 | 815.74 | 301.47 | 0.00 | 0.00 | 0.00 |
May | 577.68 | 188.07 | 389.60 | 628.01 | 262.10 | 0.00 | 0.00 | 0.00 |
June | 532.16 | 128.81 | 403.35 | 600.97 | 203.75 | 0.00 | 0.00 | 0.00 |
July | 576.59 | 180.57 | 396.02 | 693.10 | 193.70 | 0.00 | 0.00 | 0.00 |
August | 675.64 | 303.93 | 371.71 | 853.52 | 215.12 | 0.00 | 0.00 | 0.00 |
September | 798.43 | 467.73 | 330.70 | 995.38 | 276.31 | 0.00 | 0.00 | 0.00 |
October | 548.55 | 320.60 | 227.95 | 615.46 | 337.20 | 0.00 | 0.00 | 0.00 |
November | 388.92 | 236.59 | 152.33 | 397.80 | 385.31 | 0.00 | 0.00 | 0.00 |
December | 308.26 | 197.50 | 110.76 | 305.71 | 456.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 535.05 | 253.82 | 281.23 | 601.42 | 313.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.26 | 97.93 | 110.76 | 294.34 | 193.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 798.43 | 467.73 | 403.35 | 995.38 | 456.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 445.43 | 288.34 | 157.08 | 456.31 | 403.96 | 0.00 | 0.00 | 0.00 |
February | 544.01 | 331.96 | 212.05 | 570.77 | 400.95 | 0.00 | 0.00 | 0.00 |
March | 336.34 | 97.93 | 238.42 | 294.34 | 326.60 | 0.00 | 0.00 | 0.00 |
April | 698.44 | 315.69 | 382.76 | 815.74 | 301.47 | 0.00 | 0.00 | 0.00 |
May | 577.68 | 188.07 | 389.60 | 628.01 | 262.10 | 0.00 | 0.00 | 0.00 |
June | 532.16 | 128.81 | 403.35 | 600.97 | 203.75 | 0.00 | 0.00 | 0.00 |
July | 576.59 | 180.57 | 396.02 | 693.10 | 193.70 | 0.00 | 0.00 | 0.00 |
August | 675.64 | 303.93 | 371.71 | 853.52 | 215.12 | 0.00 | 0.00 | 0.00 |
September | 798.43 | 467.73 | 330.70 | 995.38 | 276.31 | 0.00 | 0.00 | 0.00 |
October | 548.55 | 320.60 | 227.95 | 615.46 | 337.20 | 0.00 | 0.00 | 0.00 |
November | 388.92 | 236.59 | 152.33 | 397.80 | 385.31 | 0.00 | 0.00 | 0.00 |
December | 308.26 | 197.50 | 110.76 | 305.71 | 456.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 535.05 | 253.82 | 281.23 | 601.42 | 313.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.26 | 97.93 | 110.76 | 294.34 | 193.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 798.43 | 467.73 | 403.35 | 995.38 | 456.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 445.40 | 288.33 | 157.07 | 456.28 | 403.93 | 0.00 | 0.00 | 0.00 |
February | 543.98 | 331.94 | 212.03 | 570.73 | 400.93 | 0.00 | 0.00 | 0.00 |
March | 336.32 | 97.92 | 238.40 | 294.32 | 326.58 | 0.00 | 0.00 | 0.00 |
April | 698.40 | 315.67 | 382.73 | 815.69 | 301.46 | 0.00 | 0.00 | 0.00 |
May | 577.64 | 188.06 | 389.58 | 627.97 | 262.09 | 0.00 | 0.00 | 0.00 |
June | 532.13 | 128.81 | 403.32 | 600.94 | 203.74 | 0.00 | 0.00 | 0.00 |
July | 576.55 | 180.55 | 396.00 | 693.06 | 193.69 | 0.00 | 0.00 | 0.00 |
August | 675.59 | 303.91 | 371.69 | 853.47 | 215.10 | 0.00 | 0.00 | 0.00 |
September | 798.38 | 467.70 | 330.67 | 995.32 | 276.29 | 0.00 | 0.00 | 0.00 |
October | 548.52 | 320.58 | 227.93 | 615.42 | 337.17 | 0.00 | 0.00 | 0.00 |
November | 388.90 | 236.58 | 152.32 | 397.78 | 385.28 | 0.00 | 0.00 | 0.00 |
December | 308.24 | 197.49 | 110.75 | 305.69 | 456.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 535.02 | 253.81 | 281.21 | 601.38 | 313.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.24 | 97.92 | 110.75 | 294.32 | 193.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 798.38 | 467.70 | 403.32 | 995.32 | 456.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 300.02 | 99.13 | 200.89 | 193.00 | 824.30 | 0.00 | 0.00 | 0.00 |
February | 531.20 | 224.29 | 306.91 | 439.22 | 795.45 | 0.00 | 0.00 | 0.00 |
March | 480.32 | 91.89 | 388.44 | 323.75 | 636.11 | 0.00 | 0.00 | 0.00 |
April | 1133.34 | 450.17 | 683.17 | 1194.97 | 569.99 | 0.00 | 0.00 | 0.00 |
May | 1329.66 | 540.69 | 788.98 | 1382.19 | 502.97 | 0.00 | 0.00 | 0.00 |
June | 1435.90 | 591.10 | 844.79 | 1602.79 | 402.07 | 0.00 | 0.00 | 0.00 |
July | 1462.40 | 644.77 | 817.62 | 1700.37 | 376.99 | 0.00 | 0.00 | 0.00 |
August | 1228.32 | 531.82 | 696.49 | 1442.71 | 411.72 | 0.00 | 0.00 | 0.00 |
September | 985.44 | 441.89 | 543.55 | 1110.71 | 521.79 | 0.00 | 0.00 | 0.00 |
October | 525.69 | 189.04 | 336.66 | 473.73 | 649.33 | 0.00 | 0.00 | 0.00 |
November | 284.49 | 83.04 | 201.44 | 182.33 | 765.34 | 0.00 | 0.00 | 0.00 |
December | 161.03 | 33.98 | 127.05 | 62.94 | 927.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 822.35 | 326.95 | 495.40 | 843.73 | 614.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 161.03 | 33.98 | 127.05 | 62.94 | 376.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1462.40 | 644.77 | 844.79 | 1700.37 | 927.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.86 | 3.92 | 7.94 | 7.63 | 32.59 | 0.00 | 0.00 | 0.00 |
February | 21.00 | 8.87 | 12.14 | 17.37 | 31.45 | 0.00 | 0.00 | 0.00 |
March | 18.99 | 3.63 | 15.36 | 12.80 | 25.15 | 0.00 | 0.00 | 0.00 |
April | 44.81 | 17.80 | 27.01 | 47.25 | 22.54 | 0.00 | 0.00 | 0.00 |
May | 52.57 | 21.38 | 31.20 | 54.65 | 19.89 | 0.00 | 0.00 | 0.00 |
June | 56.77 | 23.37 | 33.40 | 63.37 | 15.90 | 0.00 | 0.00 | 0.00 |
July | 57.82 | 25.49 | 32.33 | 67.23 | 14.91 | 0.00 | 0.00 | 0.00 |
August | 48.57 | 21.03 | 27.54 | 57.04 | 16.28 | 0.00 | 0.00 | 0.00 |
September | 38.96 | 17.47 | 21.49 | 43.92 | 20.63 | 0.00 | 0.00 | 0.00 |
October | 20.79 | 7.47 | 13.31 | 18.73 | 25.67 | 0.00 | 0.00 | 0.00 |
November | 11.25 | 3.28 | 7.96 | 7.21 | 30.26 | 0.00 | 0.00 | 0.00 |
December | 6.37 | 1.34 | 5.02 | 2.49 | 36.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.52 | 12.93 | 19.59 | 33.36 | 24.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.37 | 1.34 | 5.02 | 2.49 | 14.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.82 | 25.49 | 33.40 | 67.23 | 36.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 235.37 | 0.00 | 235.37 | 21.86 | 1354.88 | 0.00 | 0.00 | 0.00 |
February | 367.54 | 0.00 | 367.54 | 65.45 | 1278.48 | 0.00 | 0.00 | 0.00 |
March | 508.61 | 0.00 | 508.61 | 192.30 | 1048.25 | 0.00 | 0.00 | 0.00 |
April | 828.09 | 3.71 | 824.39 | 542.65 | 891.09 | 0.00 | 0.00 | 0.00 |
May | 1035.33 | 49.95 | 985.38 | 680.41 | 728.77 | 0.00 | 0.00 | 0.00 |
June | 1144.49 | 71.77 | 1072.72 | 962.35 | 579.40 | 0.00 | 0.00 | 0.00 |
July | 1085.61 | 61.90 | 1023.71 | 974.00 | 536.39 | 0.00 | 0.00 | 0.00 |
August | 853.35 | 13.37 | 839.98 | 748.96 | 599.14 | 0.00 | 0.00 | 0.00 |
September | 649.51 | 0.14 | 649.37 | 490.73 | 795.95 | 0.00 | 0.00 | 0.00 |
October | 416.20 | 0.00 | 416.20 | 183.09 | 1010.81 | 0.00 | 0.00 | 0.00 |
November | 250.08 | 0.00 | 250.08 | 33.10 | 1207.80 | 0.00 | 0.00 | 0.00 |
December | 170.30 | 0.00 | 170.30 | 1.95 | 1464.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 629.87 | 16.85 | 613.02 | 409.80 | 956.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 170.30 | 0.00 | 170.30 | 1.95 | 536.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1144.49 | 71.77 | 1072.72 | 974.00 | 1464.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 320.72 | 128.83 | 191.89 | 195.77 | 849.86 | 0.00 | 0.00 | 0.00 |
February | 478.25 | 176.67 | 301.58 | 321.86 | 809.77 | 0.00 | 0.00 | 0.00 |
March | 499.78 | 98.49 | 401.29 | 323.23 | 664.60 | 0.00 | 0.00 | 0.00 |
April | 1341.96 | 630.59 | 711.36 | 1411.21 | 567.82 | 0.00 | 0.00 | 0.00 |
May | 1411.03 | 615.32 | 795.70 | 1440.48 | 496.78 | 0.00 | 0.00 | 0.00 |
June | 1396.66 | 557.81 | 838.85 | 1516.43 | 393.43 | 0.00 | 0.00 | 0.00 |
July | 1425.71 | 605.93 | 819.79 | 1614.75 | 365.49 | 0.00 | 0.00 | 0.00 |
August | 1350.55 | 645.28 | 705.27 | 1575.28 | 396.36 | 0.00 | 0.00 | 0.00 |
September | 1216.22 | 646.73 | 569.49 | 1372.32 | 503.78 | 0.00 | 0.00 | 0.00 |
October | 587.08 | 243.30 | 343.78 | 527.22 | 648.49 | 0.00 | 0.00 | 0.00 |
November | 306.06 | 104.31 | 201.75 | 183.75 | 767.53 | 0.00 | 0.00 | 0.00 |
December | 226.83 | 84.33 | 142.50 | 119.62 | 930.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 881.35 | 378.62 | 502.73 | 885.51 | 615.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.83 | 84.33 | 142.50 | 119.62 | 365.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1425.71 | 646.73 | 838.85 | 1614.75 | 930.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1336.25 | 865.01 | 471.24 | 1342.32 | 1236.95 | 0.00 | 0.00 | 0.00 |
February | 1631.98 | 995.86 | 636.12 | 1676.13 | 1224.24 | 0.00 | 0.00 | 0.00 |
March | 1009.00 | 293.77 | 715.22 | 843.12 | 1020.43 | 0.00 | 0.00 | 0.00 |
April | 2095.27 | 947.03 | 1148.23 | 2396.22 | 929.61 | 0.00 | 0.00 | 0.00 |
May | 1732.98 | 564.20 | 1168.78 | 1829.57 | 818.04 | 0.00 | 0.00 | 0.00 |
June | 1596.45 | 386.43 | 1210.02 | 1752.63 | 638.36 | 0.00 | 0.00 | 0.00 |
July | 1729.72 | 541.68 | 1188.04 | 2043.23 | 595.20 | 0.00 | 0.00 | 0.00 |
August | 2026.85 | 911.75 | 1115.10 | 2534.37 | 646.01 | 0.00 | 0.00 | 0.00 |
September | 2395.21 | 1403.15 | 992.06 | 2965.55 | 813.93 | 0.00 | 0.00 | 0.00 |
October | 1645.61 | 961.78 | 683.82 | 1826.57 | 1001.30 | 0.00 | 0.00 | 0.00 |
November | 1166.73 | 709.75 | 456.98 | 1173.47 | 1158.25 | 0.00 | 0.00 | 0.00 |
December | 924.74 | 592.49 | 332.26 | 899.92 | 1393.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1605.11 | 761.44 | 843.67 | 1771.12 | 954.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 924.74 | 293.77 | 332.26 | 843.12 | 595.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2395.21 | 1403.15 | 1210.02 | 2965.55 | 1393.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 311.89 | 103.05 | 208.84 | 196.00 | 866.46 | 0.00 | 0.00 | 0.00 |
February | 552.21 | 233.16 | 319.05 | 447.96 | 837.07 | 0.00 | 0.00 | 0.00 |
March | 499.32 | 95.52 | 403.80 | 323.62 | 676.29 | 0.00 | 0.00 | 0.00 |
April | 1178.16 | 467.97 | 710.18 | 1222.83 | 603.26 | 0.00 | 0.00 | 0.00 |
May | 1382.25 | 562.07 | 820.18 | 1419.30 | 527.28 | 0.00 | 0.00 | 0.00 |
June | 1492.68 | 614.48 | 878.20 | 1651.39 | 419.32 | 0.00 | 0.00 | 0.00 |
July | 1520.23 | 670.27 | 849.96 | 1754.90 | 391.83 | 0.00 | 0.00 | 0.00 |
August | 1276.89 | 552.86 | 724.03 | 1489.45 | 426.24 | 0.00 | 0.00 | 0.00 |
September | 1024.41 | 459.37 | 565.04 | 1148.26 | 537.71 | 0.00 | 0.00 | 0.00 |
October | 546.48 | 196.51 | 349.97 | 488.69 | 669.36 | 0.00 | 0.00 | 0.00 |
November | 295.74 | 86.33 | 209.41 | 187.33 | 791.21 | 0.00 | 0.00 | 0.00 |
December | 167.40 | 35.32 | 132.07 | 64.30 | 965.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.87 | 339.88 | 514.99 | 867.56 | 641.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 167.40 | 35.32 | 132.07 | 64.30 | 391.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1520.23 | 670.27 | 878.20 | 1754.90 | 965.24 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.630413E+09 | 0.00 | 0.630413E+09 | 71953525.13 | 0.341403E+10 |
February | 0.889150E+09 | 0.00 | 0.889150E+09 | 0.186229E+09 | 0.289441E+10 |
March | 0.136226E+10 | 0.00 | 0.136226E+10 | 0.554280E+09 | 0.262969E+10 |
April | 0.214642E+10 | 9606474.10 | 0.213681E+10 | 0.145147E+10 | 0.217235E+10 |
May | 0.277302E+10 | 0.133785E+09 | 0.263924E+10 | 0.188573E+10 | 0.183980E+10 |
June | 0.296652E+10 | 0.186020E+09 | 0.278050E+10 | 0.252582E+10 | 0.143368E+10 |
July | 0.290770E+10 | 0.165783E+09 | 0.274192E+10 | 0.263610E+10 | 0.137555E+10 |
August | 0.228560E+10 | 35809728.31 | 0.224979E+10 | 0.203286E+10 | 0.152624E+10 |
September | 0.168354E+10 | 372533.47 | 0.168317E+10 | 0.131422E+10 | 0.193267E+10 |
October | 0.111476E+10 | 0.00 | 0.111476E+10 | 0.540672E+09 | 0.249057E+10 |
November | 0.648199E+09 | 0.00 | 0.648199E+09 | 0.106127E+09 | 0.289725E+10 |
December | 0.456136E+09 | 0.00 | 0.456136E+09 | 11950736.84 | 0.367730E+10 |
Annual Sum or Average | 0.198637E+11 | 0.531377E+09 | 0.193323E+11 | 0.133174E+11 | 0.282835E+11 |
Minimum of Months | 0.456136E+09 | 0.00 | 0.456136E+09 | 11950736.84 | 0.137555E+10 |
Maximum of Months | 0.296652E+10 | 0.186020E+09 | 0.278050E+10 | 0.263610E+10 | 0.367730E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.859020E+09 | 0.345069E+09 | 0.513951E+09 | 0.543072E+09 | 0.214435E+10 |
February | 0.115699E+10 | 0.427398E+09 | 0.729587E+09 | 0.806525E+09 | 0.183787E+10 |
March | 0.133862E+10 | 0.263792E+09 | 0.107483E+10 | 0.895547E+09 | 0.167247E+10 |
April | 0.347836E+10 | 0.163450E+10 | 0.184386E+10 | 0.368381E+10 | 0.139738E+10 |
May | 0.377930E+10 | 0.164808E+10 | 0.213121E+10 | 0.388642E+10 | 0.126396E+10 |
June | 0.362014E+10 | 0.144584E+10 | 0.217430E+10 | 0.394361E+10 | 0.978262E+09 |
July | 0.381863E+10 | 0.162291E+10 | 0.219572E+10 | 0.433440E+10 | 0.941832E+09 |
August | 0.361732E+10 | 0.172832E+10 | 0.188900E+10 | 0.422919E+10 | 0.101744E+10 |
September | 0.315243E+10 | 0.167632E+10 | 0.147612E+10 | 0.357929E+10 | 0.123670E+10 |
October | 0.157245E+10 | 0.651660E+09 | 0.920785E+09 | 0.144525E+10 | 0.161035E+10 |
November | 0.793319E+09 | 0.270374E+09 | 0.522945E+09 | 0.498417E+09 | 0.184855E+10 |
December | 0.607544E+09 | 0.225876E+09 | 0.381668E+09 | 0.335468E+09 | 0.234122E+10 |
Annual Sum or Average | 0.277941E+11 | 0.119401E+11 | 0.158540E+11 | 0.281810E+11 | 0.182904E+11 |
Minimum of Months | 0.607544E+09 | 0.225876E+09 | 0.381668E+09 | 0.335468E+09 | 0.941832E+09 |
Maximum of Months | 0.381863E+10 | 0.172832E+10 | 0.219572E+10 | 0.433440E+10 | 0.234122E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.357900E+10 | 0.231683E+10 | 0.126217E+10 | 0.363633E+10 | 0.311626E+10 |
February | 0.394808E+10 | 0.240917E+10 | 0.153891E+10 | 0.410213E+10 | 0.277875E+10 |
March | 0.270250E+10 | 0.786845E+09 | 0.191566E+10 | 0.230750E+10 | 0.256284E+10 |
April | 0.543093E+10 | 0.245471E+10 | 0.297622E+10 | 0.624452E+10 | 0.227956E+10 |
May | 0.464162E+10 | 0.151116E+10 | 0.313046E+10 | 0.493892E+10 | 0.206631E+10 |
June | 0.413799E+10 | 0.100163E+10 | 0.313636E+10 | 0.456522E+10 | 0.157585E+10 |
July | 0.463288E+10 | 0.145083E+10 | 0.318205E+10 | 0.548914E+10 | 0.152247E+10 |
August | 0.542872E+10 | 0.244203E+10 | 0.298669E+10 | 0.680260E+10 | 0.164702E+10 |
September | 0.620838E+10 | 0.363696E+10 | 0.257141E+10 | 0.771433E+10 | 0.199131E+10 |
October | 0.440759E+10 | 0.257603E+10 | 0.183156E+10 | 0.494045E+10 | 0.248424E+10 |
November | 0.302417E+10 | 0.183968E+10 | 0.118449E+10 | 0.308374E+10 | 0.278675E+10 |
December | 0.247683E+10 | 0.158692E+10 | 0.889915E+09 | 0.244388E+10 | 0.350352E+10 |
Annual Sum or Average | 0.506187E+11 | 0.240128E+11 | 0.266059E+11 | 0.562688E+11 | 0.283149E+11 |
Minimum of Months | 0.247683E+10 | 0.786845E+09 | 0.889915E+09 | 0.230750E+10 | 0.152247E+10 |
Maximum of Months | 0.620838E+10 | 0.363696E+10 | 0.318205E+10 | 0.771433E+10 | 0.350352E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.835357E+09 | 0.276005E+09 | 0.559352E+09 | 0.539541E+09 | 0.218481E+10 |
February | 0.133591E+10 | 0.564062E+09 | 0.771846E+09 | 0.110578E+10 | 0.189864E+10 |
March | 0.133737E+10 | 0.255838E+09 | 0.108153E+10 | 0.893113E+09 | 0.169846E+10 |
April | 0.305378E+10 | 0.121298E+10 | 0.184079E+10 | 0.319650E+10 | 0.147731E+10 |
May | 0.370222E+10 | 0.150545E+10 | 0.219677E+10 | 0.383185E+10 | 0.133282E+10 |
June | 0.386903E+10 | 0.159273E+10 | 0.227630E+10 | 0.429574E+10 | 0.103553E+10 |
July | 0.407178E+10 | 0.179526E+10 | 0.227653E+10 | 0.471239E+10 | 0.100250E+10 |
August | 0.342003E+10 | 0.148077E+10 | 0.193925E+10 | 0.400362E+10 | 0.108547E+10 |
September | 0.265526E+10 | 0.119068E+10 | 0.146458E+10 | 0.300306E+10 | 0.130991E+10 |
October | 0.146369E+10 | 0.526337E+09 | 0.937357E+09 | 0.134047E+10 | 0.165896E+10 |
November | 0.766549E+09 | 0.223765E+09 | 0.542784E+09 | 0.501986E+09 | 0.190353E+10 |
December | 0.448353E+09 | 94611958.57 | 0.353741E+09 | 0.181006E+09 | 0.242692E+10 |
Annual Sum or Average | 0.269593E+11 | 0.107185E+11 | 0.162408E+11 | 0.276051E+11 | 0.190149E+11 |
Minimum of Months | 0.448353E+09 | 94611958.57 | 0.353741E+09 | 0.181006E+09 | 0.100250E+10 |
Maximum of Months | 0.407178E+10 | 0.179526E+10 | 0.227653E+10 | 0.471239E+10 | 0.242692E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210128E+09 | 0.00 | 0.210128E+09 | 21961142.19 | 0.119066E+10 |
February | 0.296369E+09 | 0.00 | 0.296369E+09 | 58871786.65 | 0.100958E+10 |
March | 0.454065E+09 | 0.00 | 0.454065E+09 | 0.185863E+09 | 0.910378E+09 |
April | 0.715439E+09 | 3202006.53 | 0.712237E+09 | 0.503331E+09 | 0.732797E+09 |
May | 0.924297E+09 | 44592900.60 | 0.879705E+09 | 0.645909E+09 | 0.623185E+09 |
June | 0.988793E+09 | 62003728.10 | 0.926789E+09 | 0.861529E+09 | 0.481893E+09 |
July | 0.969188E+09 | 55258540.58 | 0.913929E+09 | 0.894006E+09 | 0.463919E+09 |
August | 0.761831E+09 | 11936011.36 | 0.749895E+09 | 0.689820E+09 | 0.516889E+09 |
September | 0.561153E+09 | 124171.95 | 0.561029E+09 | 0.438369E+09 | 0.671972E+09 |
October | 0.371569E+09 | 0.00 | 0.371569E+09 | 0.170464E+09 | 0.896430E+09 |
November | 0.216056E+09 | 0.00 | 0.216056E+09 | 29710930.52 | 0.104487E+10 |
December | 0.152038E+09 | 0.00 | 0.152038E+09 | 1782387.39 | 0.130741E+10 |
Annual Sum or Average | 0.662093E+10 | 0.177117E+09 | 0.644381E+10 | 0.450162E+10 | 0.984999E+10 |
Minimum of Months | 0.152038E+09 | 0.00 | 0.152038E+09 | 1782387.39 | 0.463919E+09 |
Maximum of Months | 0.988793E+09 | 62003728.10 | 0.926789E+09 | 0.894006E+09 | 0.130741E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210141E+09 | 0.00 | 0.210141E+09 | 21962530.09 | 0.119074E+10 |
February | 0.296388E+09 | 0.00 | 0.296388E+09 | 58875507.25 | 0.100965E+10 |
March | 0.454094E+09 | 0.00 | 0.454094E+09 | 0.185875E+09 | 0.910435E+09 |
April | 0.715484E+09 | 3202208.89 | 0.712282E+09 | 0.503362E+09 | 0.732843E+09 |
May | 0.924356E+09 | 44595718.80 | 0.879760E+09 | 0.645950E+09 | 0.623224E+09 |
June | 0.988856E+09 | 62007646.64 | 0.926848E+09 | 0.861583E+09 | 0.481924E+09 |
July | 0.969249E+09 | 55262032.83 | 0.913987E+09 | 0.894062E+09 | 0.463949E+09 |
August | 0.761880E+09 | 11936765.70 | 0.749943E+09 | 0.689864E+09 | 0.516922E+09 |
September | 0.561189E+09 | 124179.80 | 0.561065E+09 | 0.438397E+09 | 0.672014E+09 |
October | 0.371593E+09 | 0.00 | 0.371593E+09 | 0.170475E+09 | 0.896487E+09 |
November | 0.216070E+09 | 0.00 | 0.216070E+09 | 29712808.20 | 0.104494E+10 |
December | 0.152048E+09 | 0.00 | 0.152048E+09 | 1782500.03 | 0.130749E+10 |
Annual Sum or Average | 0.662135E+10 | 0.177129E+09 | 0.644422E+10 | 0.450190E+10 | 0.985061E+10 |
Minimum of Months | 0.152048E+09 | 0.00 | 0.152048E+09 | 1782500.03 | 0.463949E+09 |
Maximum of Months | 0.988856E+09 | 62007646.64 | 0.926848E+09 | 0.894062E+09 | 0.130749E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210141E+09 | 0.00 | 0.210141E+09 | 21962530.09 | 0.119074E+10 |
February | 0.296388E+09 | 0.00 | 0.296388E+09 | 58875507.25 | 0.100965E+10 |
March | 0.454094E+09 | 0.00 | 0.454094E+09 | 0.185875E+09 | 0.910435E+09 |
April | 0.715484E+09 | 3202208.89 | 0.712282E+09 | 0.503362E+09 | 0.732843E+09 |
May | 0.924356E+09 | 44595718.80 | 0.879760E+09 | 0.645950E+09 | 0.623224E+09 |
June | 0.988856E+09 | 62007646.64 | 0.926848E+09 | 0.861583E+09 | 0.481924E+09 |
July | 0.969249E+09 | 55262032.83 | 0.913987E+09 | 0.894062E+09 | 0.463949E+09 |
August | 0.761880E+09 | 11936765.70 | 0.749943E+09 | 0.689864E+09 | 0.516922E+09 |
September | 0.561189E+09 | 124179.80 | 0.561065E+09 | 0.438397E+09 | 0.672014E+09 |
October | 0.371593E+09 | 0.00 | 0.371593E+09 | 0.170475E+09 | 0.896487E+09 |
November | 0.216070E+09 | 0.00 | 0.216070E+09 | 29712808.20 | 0.104494E+10 |
December | 0.152048E+09 | 0.00 | 0.152048E+09 | 1782500.03 | 0.130749E+10 |
Annual Sum or Average | 0.662135E+10 | 0.177129E+09 | 0.644422E+10 | 0.450190E+10 | 0.985061E+10 |
Minimum of Months | 0.152048E+09 | 0.00 | 0.152048E+09 | 1782500.03 | 0.463949E+09 |
Maximum of Months | 0.988856E+09 | 62007646.64 | 0.926848E+09 | 0.894062E+09 | 0.130749E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.826340E+09 | 0.331941E+09 | 0.494399E+09 | 0.514796E+09 | 0.216767E+10 |
February | 0.111297E+10 | 0.411138E+09 | 0.701833E+09 | 0.766398E+09 | 0.185904E+10 |
March | 0.128769E+10 | 0.253756E+09 | 0.103394E+10 | 0.861387E+09 | 0.167702E+10 |
April | 0.334603E+10 | 0.157231E+10 | 0.177371E+10 | 0.355862E+10 | 0.140849E+10 |
May | 0.363552E+10 | 0.158538E+10 | 0.205014E+10 | 0.374927E+10 | 0.128034E+10 |
June | 0.348242E+10 | 0.139084E+10 | 0.209158E+10 | 0.381556E+10 | 0.977672E+09 |
July | 0.367336E+10 | 0.156117E+10 | 0.211219E+10 | 0.418864E+10 | 0.946957E+09 |
August | 0.347970E+10 | 0.166256E+10 | 0.181714E+10 | 0.408086E+10 | 0.103319E+10 |
September | 0.303251E+10 | 0.161254E+10 | 0.141996E+10 | 0.343553E+10 | 0.128346E+10 |
October | 0.151262E+10 | 0.626868E+09 | 0.885757E+09 | 0.136435E+10 | 0.169735E+10 |
November | 0.763139E+09 | 0.260087E+09 | 0.503051E+09 | 0.461433E+09 | 0.193043E+10 |
December | 0.584431E+09 | 0.217282E+09 | 0.367149E+09 | 0.311273E+09 | 0.240022E+10 |
Annual Sum or Average | 0.267367E+11 | 0.114859E+11 | 0.152509E+11 | 0.271081E+11 | 0.186618E+11 |
Minimum of Months | 0.584431E+09 | 0.217282E+09 | 0.367149E+09 | 0.311273E+09 | 0.946957E+09 |
Maximum of Months | 0.367336E+10 | 0.166256E+10 | 0.211219E+10 | 0.418864E+10 | 0.240022E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32672735.61 | 13124635.02 | 19548100.59 | 20354584.04 | 85707681.48 |
February | 44005843.45 | 16256011.84 | 27749831.61 | 30302690.43 | 73504792.62 |
March | 50914284.97 | 10033292.01 | 40880992.97 | 34058475.39 | 66308014.32 |
April | 0.132299E+09 | 62167873.40 | 70131091.74 | 0.140705E+09 | 55690434.52 |
May | 0.143745E+09 | 62684506.14 | 81060720.12 | 0.148243E+09 | 50623617.68 |
June | 0.137692E+09 | 54992446.60 | 82699369.46 | 0.150864E+09 | 38656285.53 |
July | 0.145241E+09 | 61727191.25 | 83514126.73 | 0.165615E+09 | 37441816.79 |
August | 0.137584E+09 | 65736184.88 | 71848172.75 | 0.161354E+09 | 40851306.83 |
September | 0.119903E+09 | 63758445.71 | 56144125.04 | 0.135838E+09 | 50746708.55 |
October | 59807827.80 | 24785789.35 | 35022038.45 | 53945162.36 | 67111720.38 |
November | 30173811.90 | 10283624.36 | 19890187.54 | 18244664.13 | 76327413.48 |
December | 23107873.57 | 8591148.34 | 14516725.23 | 12307463.40 | 94902634.04 |
Annual Sum or Average | 0.105715E+10 | 0.454141E+09 | 0.603005E+09 | 0.107183E+10 | 0.737872E+09 |
Minimum of Months | 23107873.57 | 8591148.34 | 14516725.23 | 12307463.40 | 37441816.79 |
Maximum of Months | 0.145241E+09 | 65736184.88 | 83514126.73 | 0.165615E+09 | 94902634.04 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119304E+10 | 0.772303E+09 | 0.420736E+09 | 0.122218E+10 | 0.108195E+10 |
February | 0.131607E+10 | 0.803084E+09 | 0.512986E+09 | 0.138080E+10 | 0.969990E+09 |
March | 0.900861E+09 | 0.262290E+09 | 0.638571E+09 | 0.788347E+09 | 0.874755E+09 |
April | 0.181037E+10 | 0.818264E+09 | 0.992102E+09 | 0.211439E+10 | 0.781422E+09 |
May | 0.154725E+10 | 0.503735E+09 | 0.104352E+10 | 0.168207E+10 | 0.702020E+09 |
June | 0.137937E+10 | 0.333888E+09 | 0.104548E+10 | 0.155772E+10 | 0.528123E+09 |
July | 0.154434E+10 | 0.483627E+09 | 0.106071E+10 | 0.185640E+10 | 0.518814E+09 |
August | 0.180963E+10 | 0.814037E+09 | 0.995590E+09 | 0.228608E+10 | 0.576170E+09 |
September | 0.206952E+10 | 0.121236E+10 | 0.857162E+09 | 0.258002E+10 | 0.716193E+09 |
October | 0.146924E+10 | 0.858706E+09 | 0.610536E+09 | 0.164846E+10 | 0.903144E+09 |
November | 0.100809E+10 | 0.613246E+09 | 0.394843E+09 | 0.103110E+10 | 0.998721E+09 |
December | 0.825637E+09 | 0.528989E+09 | 0.296647E+09 | 0.818806E+09 | 0.122182E+10 |
Annual Sum or Average | 0.168734E+11 | 0.800453E+10 | 0.886888E+10 | 0.189664E+11 | 0.987313E+10 |
Minimum of Months | 0.825637E+09 | 0.262290E+09 | 0.296647E+09 | 0.788347E+09 | 0.518814E+09 |
Maximum of Months | 0.206952E+10 | 0.121236E+10 | 0.106071E+10 | 0.258002E+10 | 0.122182E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119304E+10 | 0.772303E+09 | 0.420736E+09 | 0.122218E+10 | 0.108195E+10 |
February | 0.131607E+10 | 0.803084E+09 | 0.512986E+09 | 0.138080E+10 | 0.969990E+09 |
March | 0.900861E+09 | 0.262290E+09 | 0.638571E+09 | 0.788347E+09 | 0.874755E+09 |
April | 0.181037E+10 | 0.818264E+09 | 0.992102E+09 | 0.211439E+10 | 0.781422E+09 |
May | 0.154725E+10 | 0.503735E+09 | 0.104352E+10 | 0.168207E+10 | 0.702020E+09 |
June | 0.137937E+10 | 0.333888E+09 | 0.104548E+10 | 0.155772E+10 | 0.528123E+09 |
July | 0.154434E+10 | 0.483627E+09 | 0.106071E+10 | 0.185640E+10 | 0.518814E+09 |
August | 0.180963E+10 | 0.814037E+09 | 0.995590E+09 | 0.228608E+10 | 0.576170E+09 |
September | 0.206952E+10 | 0.121236E+10 | 0.857162E+09 | 0.258002E+10 | 0.716193E+09 |
October | 0.146924E+10 | 0.858706E+09 | 0.610536E+09 | 0.164846E+10 | 0.903144E+09 |
November | 0.100809E+10 | 0.613246E+09 | 0.394843E+09 | 0.103110E+10 | 0.998721E+09 |
December | 0.825637E+09 | 0.528989E+09 | 0.296647E+09 | 0.818806E+09 | 0.122182E+10 |
Annual Sum or Average | 0.168734E+11 | 0.800453E+10 | 0.886888E+10 | 0.189664E+11 | 0.987313E+10 |
Minimum of Months | 0.825637E+09 | 0.262290E+09 | 0.296647E+09 | 0.788347E+09 | 0.518814E+09 |
Maximum of Months | 0.206952E+10 | 0.121236E+10 | 0.106071E+10 | 0.258002E+10 | 0.122182E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.119296E+10 | 0.772254E+09 | 0.420709E+09 | 0.122210E+10 | 0.108188E+10 |
February | 0.131599E+10 | 0.803033E+09 | 0.512954E+09 | 0.138071E+10 | 0.969929E+09 |
March | 0.900804E+09 | 0.262274E+09 | 0.638530E+09 | 0.788298E+09 | 0.874700E+09 |
April | 0.181025E+10 | 0.818213E+09 | 0.992039E+09 | 0.211426E+10 | 0.781372E+09 |
May | 0.154715E+10 | 0.503703E+09 | 0.104345E+10 | 0.168196E+10 | 0.701976E+09 |
June | 0.137928E+10 | 0.333867E+09 | 0.104542E+10 | 0.155762E+10 | 0.528090E+09 |
July | 0.154424E+10 | 0.483597E+09 | 0.106065E+10 | 0.185628E+10 | 0.518781E+09 |
August | 0.180951E+10 | 0.813986E+09 | 0.995527E+09 | 0.228593E+10 | 0.576134E+09 |
September | 0.206939E+10 | 0.121228E+10 | 0.857108E+09 | 0.257986E+10 | 0.716148E+09 |
October | 0.146915E+10 | 0.858652E+09 | 0.610498E+09 | 0.164835E+10 | 0.903087E+09 |
November | 0.100803E+10 | 0.613208E+09 | 0.394818E+09 | 0.103103E+10 | 0.998658E+09 |
December | 0.825585E+09 | 0.528956E+09 | 0.296629E+09 | 0.818754E+09 | 0.122174E+10 |
Annual Sum or Average | 0.168723E+11 | 0.800403E+10 | 0.886832E+10 | 0.189652E+11 | 0.987250E+10 |
Minimum of Months | 0.825585E+09 | 0.262274E+09 | 0.296629E+09 | 0.788298E+09 | 0.518781E+09 |
Maximum of Months | 0.206939E+10 | 0.121228E+10 | 0.106065E+10 | 0.257986E+10 | 0.122174E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.803578E+09 | 0.265504E+09 | 0.538074E+09 | 0.516930E+09 | 0.220781E+10 |
February | 0.128509E+10 | 0.542603E+09 | 0.742483E+09 | 0.106255E+10 | 0.192436E+10 |
March | 0.128649E+10 | 0.246105E+09 | 0.104039E+10 | 0.867122E+09 | 0.170375E+10 |
April | 0.293761E+10 | 0.116684E+10 | 0.177077E+10 | 0.309736E+10 | 0.147740E+10 |
May | 0.356137E+10 | 0.144817E+10 | 0.211320E+10 | 0.370206E+10 | 0.134715E+10 |
June | 0.372184E+10 | 0.153213E+10 | 0.218971E+10 | 0.415444E+10 | 0.104215E+10 |
July | 0.391688E+10 | 0.172696E+10 | 0.218993E+10 | 0.455426E+10 | 0.100972E+10 |
August | 0.328992E+10 | 0.142444E+10 | 0.186548E+10 | 0.386415E+10 | 0.110275E+10 |
September | 0.255425E+10 | 0.114538E+10 | 0.140887E+10 | 0.287897E+10 | 0.135248E+10 |
October | 0.140801E+10 | 0.506313E+09 | 0.901699E+09 | 0.126884E+10 | 0.173916E+10 |
November | 0.737388E+09 | 0.215252E+09 | 0.522136E+09 | 0.472604E+09 | 0.198375E+10 |
December | 0.431296E+09 | 91012473.82 | 0.340284E+09 | 0.168577E+09 | 0.248353E+10 |
Annual Sum or Average | 0.259337E+11 | 0.103107E+11 | 0.156230E+11 | 0.266079E+11 | 0.193740E+11 |
Minimum of Months | 0.431296E+09 | 91012473.82 | 0.340284E+09 | 0.168577E+09 | 0.100972E+10 |
Maximum of Months | 0.391688E+10 | 0.172696E+10 | 0.218993E+10 | 0.455426E+10 | 0.248353E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31772654.88 | 10497767.09 | 21274887.79 | 20438839.59 | 87294916.80 |
February | 50810996.68 | 21453945.80 | 29357050.88 | 42012098.25 | 76087617.39 |
March | 50866677.49 | 9730743.29 | 41135934.20 | 34285066.32 | 67364889.58 |
April | 0.116150E+09 | 46135533.96 | 70014443.38 | 0.122466E+09 | 58415141.30 |
May | 0.140813E+09 | 57259192.47 | 83553949.68 | 0.146376E+09 | 53265215.82 |
June | 0.147158E+09 | 60578959.32 | 86578837.92 | 0.164262E+09 | 41205850.97 |
July | 0.154870E+09 | 68282068.25 | 86587473.74 | 0.180071E+09 | 39923306.97 |
August | 0.130080E+09 | 56320755.30 | 73759364.59 | 0.152784E+09 | 43601648.44 |
September | 0.100992E+09 | 45287033.34 | 55705339.08 | 0.113831E+09 | 53475883.39 |
October | 55671370.91 | 20019086.76 | 35652284.15 | 50168669.44 | 68764952.33 |
November | 29155561.76 | 8510831.40 | 20644730.36 | 18686248.08 | 78435671.98 |
December | 17053019.85 | 3598539.60 | 13454480.25 | 6665361.99 | 98196576.70 |
Annual Sum or Average | 0.102539E+10 | 0.407674E+09 | 0.617719E+09 | 0.105205E+10 | 0.766032E+09 |
Minimum of Months | 17053019.85 | 3598539.60 | 13454480.25 | 6665361.99 | 39923306.97 |
Maximum of Months | 0.154870E+09 | 68282068.25 | 86587473.74 | 0.180071E+09 | 98196576.70 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.630413E+09 | 0.00 | 0.630413E+09 | 58545994.77 | 0.362891E+10 |
February | 0.889150E+09 | 0.00 | 0.889150E+09 | 0.158325E+09 | 0.309291E+10 |
March | 0.136226E+10 | 0.00 | 0.136226E+10 | 0.515055E+09 | 0.280764E+10 |
April | 0.214642E+10 | 9606474.10 | 0.213681E+10 | 0.140656E+10 | 0.230971E+10 |
May | 0.277302E+10 | 0.133785E+09 | 0.263924E+10 | 0.182242E+10 | 0.195194E+10 |
June | 0.296652E+10 | 0.186020E+09 | 0.278050E+10 | 0.249441E+10 | 0.150180E+10 |
July | 0.290770E+10 | 0.165783E+09 | 0.274192E+10 | 0.260877E+10 | 0.143666E+10 |
August | 0.228560E+10 | 35809728.31 | 0.224979E+10 | 0.200601E+10 | 0.160475E+10 |
September | 0.168354E+10 | 372533.47 | 0.168317E+10 | 0.127198E+10 | 0.206310E+10 |
October | 0.111476E+10 | 0.00 | 0.111476E+10 | 0.490384E+09 | 0.270735E+10 |
November | 0.648199E+09 | 0.00 | 0.648199E+09 | 85790339.84 | 0.313061E+10 |
December | 0.456136E+09 | 0.00 | 0.456136E+09 | 5229567.38 | 0.392239E+10 |
Annual Sum or Average | 0.198637E+11 | 0.531377E+09 | 0.193323E+11 | 0.129235E+11 | 0.301578E+11 |
Minimum of Months | 0.456136E+09 | 0.00 | 0.456136E+09 | 5229567.38 | 0.143666E+10 |
Maximum of Months | 0.296652E+10 | 0.186020E+09 | 0.278050E+10 | 0.260877E+10 | 0.392239E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.859020E+09 | 0.345069E+09 | 0.513951E+09 | 0.524348E+09 | 0.227627E+10 |
February | 0.115699E+10 | 0.427398E+09 | 0.729587E+09 | 0.778634E+09 | 0.195900E+10 |
March | 0.133862E+10 | 0.263792E+09 | 0.107483E+10 | 0.865729E+09 | 0.178006E+10 |
April | 0.347836E+10 | 0.163450E+10 | 0.184386E+10 | 0.365785E+10 | 0.147178E+10 |
May | 0.377930E+10 | 0.164808E+10 | 0.213121E+10 | 0.385818E+10 | 0.133057E+10 |
June | 0.362014E+10 | 0.144584E+10 | 0.217430E+10 | 0.393059E+10 | 0.101978E+10 |
July | 0.381863E+10 | 0.162291E+10 | 0.219572E+10 | 0.432494E+10 | 0.978927E+09 |
August | 0.361732E+10 | 0.172832E+10 | 0.188900E+10 | 0.421924E+10 | 0.106160E+10 |
September | 0.315243E+10 | 0.167632E+10 | 0.147612E+10 | 0.355705E+10 | 0.130579E+10 |
October | 0.157245E+10 | 0.651660E+09 | 0.920785E+09 | 0.141210E+10 | 0.173691E+10 |
November | 0.793319E+09 | 0.270374E+09 | 0.522945E+09 | 0.476281E+09 | 0.198943E+10 |
December | 0.607544E+09 | 0.225876E+09 | 0.381668E+09 | 0.320400E+09 | 0.249344E+10 |
Annual Sum or Average | 0.277941E+11 | 0.119401E+11 | 0.158540E+11 | 0.279254E+11 | 0.194036E+11 |
Minimum of Months | 0.607544E+09 | 0.225876E+09 | 0.381668E+09 | 0.320400E+09 | 0.978927E+09 |
Maximum of Months | 0.381863E+10 | 0.172832E+10 | 0.219572E+10 | 0.432494E+10 | 0.249344E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.357900E+10 | 0.231683E+10 | 0.126217E+10 | 0.359528E+10 | 0.331305E+10 |
February | 0.394808E+10 | 0.240917E+10 | 0.153891E+10 | 0.405489E+10 | 0.296167E+10 |
March | 0.270250E+10 | 0.786845E+09 | 0.191566E+10 | 0.225820E+10 | 0.273313E+10 |
April | 0.543093E+10 | 0.245471E+10 | 0.297622E+10 | 0.621101E+10 | 0.240955E+10 |
May | 0.464162E+10 | 0.151116E+10 | 0.313046E+10 | 0.490032E+10 | 0.219104E+10 |
June | 0.413799E+10 | 0.100163E+10 | 0.313636E+10 | 0.454281E+10 | 0.165462E+10 |
July | 0.463288E+10 | 0.145083E+10 | 0.318205E+10 | 0.547260E+10 | 0.159418E+10 |
August | 0.542872E+10 | 0.244203E+10 | 0.298669E+10 | 0.678807E+10 | 0.173028E+10 |
September | 0.620838E+10 | 0.363696E+10 | 0.257141E+10 | 0.768671E+10 | 0.210970E+10 |
October | 0.440759E+10 | 0.257603E+10 | 0.183156E+10 | 0.489227E+10 | 0.268189E+10 |
November | 0.302417E+10 | 0.183968E+10 | 0.118449E+10 | 0.304163E+10 | 0.300217E+10 |
December | 0.247683E+10 | 0.158692E+10 | 0.889915E+09 | 0.241036E+10 | 0.373118E+10 |
Annual Sum or Average | 0.506187E+11 | 0.240128E+11 | 0.266059E+11 | 0.558542E+11 | 0.301125E+11 |
Minimum of Months | 0.247683E+10 | 0.786845E+09 | 0.889915E+09 | 0.225820E+10 | 0.159418E+10 |
Maximum of Months | 0.620838E+10 | 0.363696E+10 | 0.318205E+10 | 0.768671E+10 | 0.373118E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.835357E+09 | 0.276005E+09 | 0.559352E+09 | 0.524975E+09 | 0.232072E+10 |
February | 0.133591E+10 | 0.564062E+09 | 0.771846E+09 | 0.108371E+10 | 0.202503E+10 |
March | 0.133737E+10 | 0.255838E+09 | 0.108153E+10 | 0.866788E+09 | 0.181137E+10 |
April | 0.305378E+10 | 0.121298E+10 | 0.184079E+10 | 0.316957E+10 | 0.156366E+10 |
May | 0.370222E+10 | 0.150545E+10 | 0.219677E+10 | 0.380144E+10 | 0.141226E+10 |
June | 0.386903E+10 | 0.159273E+10 | 0.227630E+10 | 0.428041E+10 | 0.108688E+10 |
July | 0.407178E+10 | 0.179526E+10 | 0.227653E+10 | 0.470031E+10 | 0.104947E+10 |
August | 0.342003E+10 | 0.148077E+10 | 0.193925E+10 | 0.398933E+10 | 0.114163E+10 |
September | 0.265526E+10 | 0.119068E+10 | 0.146458E+10 | 0.297630E+10 | 0.139375E+10 |
October | 0.146369E+10 | 0.526337E+09 | 0.937357E+09 | 0.130891E+10 | 0.179282E+10 |
November | 0.766549E+09 | 0.223765E+09 | 0.542784E+09 | 0.485559E+09 | 0.205082E+10 |
December | 0.448353E+09 | 94611958.57 | 0.353741E+09 | 0.172212E+09 | 0.258530E+10 |
Annual Sum or Average | 0.269593E+11 | 0.107185E+11 | 0.162408E+11 | 0.273595E+11 | 0.202337E+11 |
Minimum of Months | 0.448353E+09 | 94611958.57 | 0.353741E+09 | 0.172212E+09 | 0.104947E+10 |
Maximum of Months | 0.407178E+10 | 0.179526E+10 | 0.227653E+10 | 0.470031E+10 | 0.258530E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.86 | 1274.65 | 235.37 | 0.00 | 235.37 | 0.00 | 0.00 |
February | 76.98 | 1196.43 | 367.54 | 0.00 | 367.54 | 0.00 | 0.00 |
March | 206.94 | 981.82 | 508.61 | 0.00 | 508.61 | 0.00 | 0.00 |
April | 559.98 | 838.10 | 828.09 | 3.71 | 824.39 | 0.00 | 0.00 |
May | 704.05 | 686.90 | 1035.33 | 49.95 | 985.38 | 0.00 | 0.00 |
June | 974.47 | 553.12 | 1144.49 | 71.77 | 1072.72 | 0.00 | 0.00 |
July | 984.21 | 513.57 | 1085.61 | 61.90 | 1023.71 | 0.00 | 0.00 |
August | 758.98 | 569.83 | 853.35 | 13.37 | 839.98 | 0.00 | 0.00 |
September | 507.03 | 745.63 | 649.51 | 0.14 | 649.37 | 0.00 | 0.00 |
October | 201.86 | 929.87 | 416.20 | 0.00 | 416.20 | 0.00 | 0.00 |
November | 40.94 | 1117.77 | 250.08 | 0.00 | 250.08 | 0.00 | 0.00 |
December | 4.46 | 1372.95 | 170.30 | 0.00 | 170.30 | 0.00 | 0.00 |
Annual Sum or Average | 422.29 | 896.87 | 629.87 | 16.85 | 613.02 | 0.00 | 0.00 |
Minimum of Months | 4.46 | 513.57 | 170.30 | 0.00 | 170.30 | 0.00 | 0.00 |
Maximum of Months | 984.21 | 1372.95 | 1144.49 | 71.77 | 1072.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 202.76 | 800.61 | 320.72 | 128.83 | 191.89 | 0.00 | 0.00 |
February | 333.38 | 759.70 | 478.25 | 176.67 | 301.58 | 0.00 | 0.00 |
March | 334.36 | 624.43 | 499.78 | 98.49 | 401.29 | 0.00 | 0.00 |
April | 1421.22 | 539.11 | 1341.96 | 630.59 | 711.36 | 0.00 | 0.00 |
May | 1451.02 | 471.91 | 1411.03 | 615.32 | 795.70 | 0.00 | 0.00 |
June | 1521.45 | 377.42 | 1396.66 | 557.81 | 838.85 | 0.00 | 0.00 |
July | 1618.28 | 351.64 | 1425.71 | 605.93 | 819.79 | 0.00 | 0.00 |
August | 1579.00 | 379.87 | 1350.55 | 645.28 | 705.27 | 0.00 | 0.00 |
September | 1380.90 | 477.12 | 1216.22 | 646.73 | 569.49 | 0.00 | 0.00 |
October | 539.59 | 601.24 | 587.08 | 243.30 | 343.78 | 0.00 | 0.00 |
November | 192.29 | 713.18 | 306.06 | 104.31 | 201.75 | 0.00 | 0.00 |
December | 125.25 | 874.11 | 226.83 | 84.33 | 142.50 | 0.00 | 0.00 |
Annual Sum or Average | 893.61 | 579.98 | 881.35 | 378.62 | 502.73 | 0.00 | 0.00 |
Minimum of Months | 125.25 | 351.64 | 226.83 | 84.33 | 142.50 | 0.00 | 0.00 |
Maximum of Months | 1618.28 | 874.11 | 1425.71 | 646.73 | 838.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1357.65 | 1163.48 | 1336.25 | 865.01 | 471.24 | 0.00 | 0.00 |
February | 1695.65 | 1148.62 | 1631.98 | 995.86 | 636.12 | 0.00 | 0.00 |
March | 861.52 | 956.85 | 1009.00 | 293.77 | 715.22 | 0.00 | 0.00 |
April | 2409.15 | 879.46 | 2095.27 | 947.03 | 1148.23 | 0.00 | 0.00 |
May | 1843.98 | 771.47 | 1732.98 | 564.20 | 1168.78 | 0.00 | 0.00 |
June | 1761.27 | 607.97 | 1596.45 | 386.43 | 1210.02 | 0.00 | 0.00 |
July | 2049.41 | 568.43 | 1729.72 | 541.68 | 1188.04 | 0.00 | 0.00 |
August | 2539.80 | 614.93 | 2026.85 | 911.75 | 1115.10 | 0.00 | 0.00 |
September | 2976.21 | 768.25 | 2395.21 | 1403.15 | 992.06 | 0.00 | 0.00 |
October | 1844.55 | 927.51 | 1645.61 | 961.78 | 683.82 | 0.00 | 0.00 |
November | 1189.72 | 1075.14 | 1166.73 | 709.75 | 456.98 | 0.00 | 0.00 |
December | 912.44 | 1308.07 | 924.74 | 592.49 | 332.26 | 0.00 | 0.00 |
Annual Sum or Average | 1784.27 | 897.86 | 1605.11 | 761.44 | 843.67 | 0.00 | 0.00 |
Minimum of Months | 861.52 | 568.43 | 924.74 | 293.77 | 332.26 | 0.00 | 0.00 |
Maximum of Months | 2976.21 | 1308.07 | 2395.21 | 1403.15 | 1210.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 201.44 | 815.71 | 311.89 | 103.05 | 208.84 | 0.00 | 0.00 |
February | 457.08 | 784.82 | 552.21 | 233.16 | 319.05 | 0.00 | 0.00 |
March | 333.45 | 634.13 | 499.32 | 95.52 | 403.80 | 0.00 | 0.00 |
April | 1233.22 | 569.95 | 1178.16 | 467.97 | 710.18 | 0.00 | 0.00 |
May | 1430.65 | 497.62 | 1382.25 | 562.07 | 820.18 | 0.00 | 0.00 |
June | 1657.31 | 399.51 | 1492.68 | 614.48 | 878.20 | 0.00 | 0.00 |
July | 1759.41 | 374.29 | 1520.23 | 670.27 | 849.96 | 0.00 | 0.00 |
August | 1494.78 | 405.27 | 1276.89 | 552.86 | 724.03 | 0.00 | 0.00 |
September | 1158.59 | 505.37 | 1024.41 | 459.37 | 565.04 | 0.00 | 0.00 |
October | 500.47 | 619.38 | 546.48 | 196.51 | 349.97 | 0.00 | 0.00 |
November | 193.67 | 734.39 | 295.74 | 86.33 | 209.41 | 0.00 | 0.00 |
December | 67.58 | 906.11 | 167.40 | 35.32 | 132.07 | 0.00 | 0.00 |
Annual Sum or Average | 875.35 | 602.96 | 854.87 | 339.88 | 514.99 | 0.00 | 0.00 |
Minimum of Months | 67.58 | 374.29 | 167.40 | 35.32 | 132.07 | 0.00 | 0.00 |
Maximum of Months | 1759.41 | 906.11 | 1520.23 | 670.27 | 878.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24.60 | 1333.68 | 235.37 | 0.00 | 235.37 | 0.00 | 0.00 |
February | 73.01 | 1252.02 | 367.54 | 0.00 | 367.54 | 0.00 | 0.00 |
March | 208.19 | 1019.73 | 508.61 | 0.00 | 508.61 | 0.00 | 0.00 |
April | 582.58 | 848.18 | 828.09 | 3.71 | 824.38 | 0.00 | 0.00 |
May | 723.49 | 698.04 | 1035.32 | 49.95 | 985.37 | 0.00 | 0.00 |
June | 997.18 | 557.77 | 1144.48 | 71.77 | 1072.72 | 0.00 | 0.00 |
July | 1001.39 | 519.64 | 1085.61 | 61.90 | 1023.71 | 0.00 | 0.00 |
August | 772.68 | 578.98 | 853.34 | 13.37 | 839.97 | 0.00 | 0.00 |
September | 507.39 | 777.78 | 649.51 | 0.14 | 649.37 | 0.00 | 0.00 |
October | 190.94 | 1004.11 | 416.20 | 0.00 | 416.20 | 0.00 | 0.00 |
November | 34.39 | 1209.39 | 250.08 | 0.00 | 250.08 | 0.00 | 0.00 |
December | 2.00 | 1464.46 | 170.30 | 0.00 | 170.30 | 0.00 | 0.00 |
Annual Sum or Average | 428.25 | 937.06 | 629.87 | 16.85 | 613.02 | 0.00 | 0.00 |
Minimum of Months | 2.00 | 519.64 | 170.30 | 0.00 | 170.30 | 0.00 | 0.00 |
Maximum of Months | 1001.39 | 1464.46 | 1144.48 | 71.77 | 1072.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 199.80 | 841.31 | 320.72 | 128.83 | 191.89 | 0.00 | 0.00 |
February | 329.32 | 798.84 | 478.25 | 176.67 | 301.58 | 0.00 | 0.00 |
March | 334.32 | 650.89 | 499.78 | 98.49 | 401.29 | 0.00 | 0.00 |
April | 1427.21 | 564.88 | 1341.95 | 630.59 | 711.36 | 0.00 | 0.00 |
May | 1455.16 | 496.93 | 1411.02 | 615.32 | 795.70 | 0.00 | 0.00 |
June | 1530.25 | 392.10 | 1396.65 | 557.80 | 838.84 | 0.00 | 0.00 |
July | 1625.69 | 367.53 | 1425.70 | 605.92 | 819.78 | 0.00 | 0.00 |
August | 1583.86 | 401.00 | 1350.54 | 645.27 | 705.27 | 0.00 | 0.00 |
September | 1377.84 | 514.74 | 1216.21 | 646.72 | 569.49 | 0.00 | 0.00 |
October | 529.53 | 658.77 | 587.08 | 243.30 | 343.78 | 0.00 | 0.00 |
November | 185.06 | 774.21 | 306.06 | 104.31 | 201.75 | 0.00 | 0.00 |
December | 120.81 | 931.57 | 226.83 | 84.33 | 142.50 | 0.00 | 0.00 |
Annual Sum or Average | 893.58 | 615.16 | 881.34 | 378.62 | 502.72 | 0.00 | 0.00 |
Minimum of Months | 120.81 | 367.53 | 226.83 | 84.33 | 142.50 | 0.00 | 0.00 |
Maximum of Months | 1625.69 | 931.57 | 1425.70 | 646.72 | 838.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1368.90 | 1211.84 | 1336.26 | 865.02 | 471.24 | 0.00 | 0.00 |
February | 1712.26 | 1202.84 | 1632.00 | 995.87 | 636.13 | 0.00 | 0.00 |
March | 882.99 | 979.77 | 1009.01 | 293.78 | 715.23 | 0.00 | 0.00 |
April | 2447.16 | 904.40 | 2095.29 | 947.05 | 1148.24 | 0.00 | 0.00 |
May | 1884.00 | 786.30 | 1733.00 | 564.21 | 1168.79 | 0.00 | 0.00 |
June | 1802.88 | 611.24 | 1596.46 | 386.44 | 1210.02 | 0.00 | 0.00 |
July | 2079.26 | 581.10 | 1729.73 | 541.69 | 1188.05 | 0.00 | 0.00 |
August | 2560.51 | 645.34 | 2026.87 | 911.76 | 1115.11 | 0.00 | 0.00 |
September | 2986.08 | 828.91 | 2395.23 | 1403.17 | 992.06 | 0.00 | 0.00 |
October | 1846.35 | 1011.57 | 1645.62 | 961.79 | 683.83 | 0.00 | 0.00 |
November | 1193.38 | 1155.90 | 1166.75 | 709.76 | 456.98 | 0.00 | 0.00 |
December | 917.10 | 1368.49 | 924.75 | 592.49 | 332.26 | 0.00 | 0.00 |
Annual Sum or Average | 1804.22 | 939.20 | 1605.12 | 761.45 | 843.67 | 0.00 | 0.00 |
Minimum of Months | 882.99 | 581.10 | 924.75 | 293.78 | 332.26 | 0.00 | 0.00 |
Maximum of Months | 2986.08 | 1368.49 | 2395.23 | 1403.17 | 1210.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 200.63 | 856.89 | 311.88 | 103.05 | 208.84 | 0.00 | 0.00 |
February | 456.58 | 826.91 | 552.21 | 233.16 | 319.05 | 0.00 | 0.00 |
March | 336.55 | 661.26 | 499.31 | 95.52 | 403.80 | 0.00 | 0.00 |
April | 1242.22 | 592.52 | 1178.15 | 467.97 | 710.18 | 0.00 | 0.00 |
May | 1436.84 | 522.86 | 1382.24 | 562.06 | 820.18 | 0.00 | 0.00 |
June | 1666.17 | 417.96 | 1492.67 | 614.47 | 878.20 | 0.00 | 0.00 |
July | 1767.60 | 391.89 | 1520.22 | 670.27 | 849.95 | 0.00 | 0.00 |
August | 1499.75 | 428.00 | 1276.88 | 552.85 | 724.03 | 0.00 | 0.00 |
September | 1154.63 | 542.42 | 1024.40 | 459.36 | 565.04 | 0.00 | 0.00 |
October | 492.46 | 675.00 | 546.48 | 196.51 | 349.97 | 0.00 | 0.00 |
November | 189.54 | 795.60 | 295.73 | 86.33 | 209.41 | 0.00 | 0.00 |
December | 65.43 | 963.91 | 167.39 | 35.32 | 132.07 | 0.00 | 0.00 |
Annual Sum or Average | 877.09 | 638.64 | 854.87 | 339.88 | 514.99 | 0.00 | 0.00 |
Minimum of Months | 65.43 | 391.89 | 167.39 | 35.32 | 132.07 | 0.00 | 0.00 |
Maximum of Months | 1767.60 | 963.91 | 1520.22 | 670.27 | 878.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 21.86 | 1354.88 | 235.37 | 0.00 | 235.37 | 0.00 | 0.00 |
February | 65.45 | 1278.48 | 367.54 | 0.00 | 367.54 | 0.00 | 0.00 |
March | 192.30 | 1048.25 | 508.61 | 0.00 | 508.61 | 0.00 | 0.00 |
April | 542.65 | 891.09 | 828.09 | 3.71 | 824.39 | 0.00 | 0.00 |
May | 680.41 | 728.77 | 1035.33 | 49.95 | 985.38 | 0.00 | 0.00 |
June | 962.35 | 579.40 | 1144.49 | 71.77 | 1072.72 | 0.00 | 0.00 |
July | 974.00 | 536.39 | 1085.61 | 61.90 | 1023.71 | 0.00 | 0.00 |
August | 748.96 | 599.14 | 853.35 | 13.37 | 839.98 | 0.00 | 0.00 |
September | 490.73 | 795.95 | 649.51 | 0.14 | 649.37 | 0.00 | 0.00 |
October | 183.09 | 1010.81 | 416.20 | 0.00 | 416.20 | 0.00 | 0.00 |
November | 33.10 | 1207.80 | 250.08 | 0.00 | 250.08 | 0.00 | 0.00 |
December | 1.95 | 1464.45 | 170.30 | 0.00 | 170.30 | 0.00 | 0.00 |
Annual Sum or Average | 409.80 | 956.30 | 629.87 | 16.85 | 613.02 | 0.00 | 0.00 |
Minimum of Months | 1.95 | 536.39 | 170.30 | 0.00 | 170.30 | 0.00 | 0.00 |
Maximum of Months | 974.00 | 1464.45 | 1144.49 | 71.77 | 1072.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 195.77 | 849.86 | 320.72 | 128.83 | 191.89 | 0.00 | 0.00 |
February | 321.86 | 809.77 | 478.25 | 176.67 | 301.58 | 0.00 | 0.00 |
March | 323.23 | 664.60 | 499.78 | 98.49 | 401.29 | 0.00 | 0.00 |
April | 1411.21 | 567.82 | 1341.96 | 630.59 | 711.36 | 0.00 | 0.00 |
May | 1440.48 | 496.78 | 1411.03 | 615.32 | 795.70 | 0.00 | 0.00 |
June | 1516.43 | 393.43 | 1396.66 | 557.81 | 838.85 | 0.00 | 0.00 |
July | 1614.75 | 365.49 | 1425.71 | 605.93 | 819.79 | 0.00 | 0.00 |
August | 1575.28 | 396.36 | 1350.55 | 645.28 | 705.27 | 0.00 | 0.00 |
September | 1372.32 | 503.78 | 1216.22 | 646.73 | 569.49 | 0.00 | 0.00 |
October | 527.22 | 648.49 | 587.08 | 243.30 | 343.78 | 0.00 | 0.00 |
November | 183.75 | 767.53 | 306.06 | 104.31 | 201.75 | 0.00 | 0.00 |
December | 119.62 | 930.95 | 226.83 | 84.33 | 142.50 | 0.00 | 0.00 |
Annual Sum or Average | 885.51 | 615.28 | 881.35 | 378.62 | 502.73 | 0.00 | 0.00 |
Minimum of Months | 119.62 | 365.49 | 226.83 | 84.33 | 142.50 | 0.00 | 0.00 |
Maximum of Months | 1614.75 | 930.95 | 1425.71 | 646.73 | 838.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1342.32 | 1236.95 | 1336.25 | 865.01 | 471.24 | 0.00 | 0.00 |
February | 1676.13 | 1224.24 | 1631.98 | 995.86 | 636.12 | 0.00 | 0.00 |
March | 843.12 | 1020.43 | 1009.00 | 293.77 | 715.22 | 0.00 | 0.00 |
April | 2396.22 | 929.61 | 2095.27 | 947.03 | 1148.23 | 0.00 | 0.00 |
May | 1829.57 | 818.04 | 1732.98 | 564.20 | 1168.78 | 0.00 | 0.00 |
June | 1752.63 | 638.36 | 1596.45 | 386.43 | 1210.02 | 0.00 | 0.00 |
July | 2043.23 | 595.20 | 1729.72 | 541.68 | 1188.04 | 0.00 | 0.00 |
August | 2534.37 | 646.01 | 2026.85 | 911.75 | 1115.10 | 0.00 | 0.00 |
September | 2965.55 | 813.93 | 2395.21 | 1403.15 | 992.06 | 0.00 | 0.00 |
October | 1826.57 | 1001.30 | 1645.61 | 961.78 | 683.82 | 0.00 | 0.00 |
November | 1173.47 | 1158.25 | 1166.73 | 709.75 | 456.98 | 0.00 | 0.00 |
December | 899.92 | 1393.06 | 924.74 | 592.49 | 332.26 | 0.00 | 0.00 |
Annual Sum or Average | 1771.12 | 954.86 | 1605.11 | 761.44 | 843.67 | 0.00 | 0.00 |
Minimum of Months | 843.12 | 595.20 | 924.74 | 293.77 | 332.26 | 0.00 | 0.00 |
Maximum of Months | 2965.55 | 1393.06 | 2395.21 | 1403.15 | 1210.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 196.00 | 866.46 | 311.89 | 103.05 | 208.84 | 0.00 | 0.00 |
February | 447.96 | 837.07 | 552.21 | 233.16 | 319.05 | 0.00 | 0.00 |
March | 323.62 | 676.29 | 499.32 | 95.52 | 403.80 | 0.00 | 0.00 |
April | 1222.83 | 603.26 | 1178.16 | 467.97 | 710.18 | 0.00 | 0.00 |
May | 1419.30 | 527.28 | 1382.25 | 562.07 | 820.18 | 0.00 | 0.00 |
June | 1651.39 | 419.32 | 1492.68 | 614.48 | 878.20 | 0.00 | 0.00 |
July | 1754.90 | 391.83 | 1520.23 | 670.27 | 849.96 | 0.00 | 0.00 |
August | 1489.45 | 426.24 | 1276.89 | 552.86 | 724.03 | 0.00 | 0.00 |
September | 1148.26 | 537.71 | 1024.41 | 459.37 | 565.04 | 0.00 | 0.00 |
October | 488.69 | 669.36 | 546.48 | 196.51 | 349.97 | 0.00 | 0.00 |
November | 187.33 | 791.21 | 295.74 | 86.33 | 209.41 | 0.00 | 0.00 |
December | 64.30 | 965.24 | 167.40 | 35.32 | 132.07 | 0.00 | 0.00 |
Annual Sum or Average | 867.56 | 641.61 | 854.87 | 339.88 | 514.99 | 0.00 | 0.00 |
Minimum of Months | 64.30 | 391.83 | 167.40 | 35.32 | 132.07 | 0.00 | 0.00 |
Maximum of Months | 1754.90 | 965.24 | 1520.23 | 670.27 | 878.20 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 71953525.13 | 0.341403E+10 | 0.630413E+09 | 0.00 | 0.630413E+09 | 0.00 | 0.00 |
February | 0.186229E+09 | 0.289441E+10 | 0.889150E+09 | 0.00 | 0.889150E+09 | 0.00 | 0.00 |
March | 0.554280E+09 | 0.262969E+10 | 0.136226E+10 | 0.00 | 0.136226E+10 | 0.00 | 0.00 |
April | 0.145147E+10 | 0.217235E+10 | 0.214642E+10 | 9606474.10 | 0.213681E+10 | 0.00 | 0.00 |
May | 0.188573E+10 | 0.183980E+10 | 0.277302E+10 | 0.133785E+09 | 0.263924E+10 | 0.00 | 0.00 |
June | 0.252582E+10 | 0.143368E+10 | 0.296652E+10 | 0.186020E+09 | 0.278050E+10 | 0.00 | 0.00 |
July | 0.263610E+10 | 0.137555E+10 | 0.290770E+10 | 0.165783E+09 | 0.274192E+10 | 0.00 | 0.00 |
August | 0.203286E+10 | 0.152624E+10 | 0.228560E+10 | 35809728.31 | 0.224979E+10 | 0.00 | 0.00 |
September | 0.131422E+10 | 0.193267E+10 | 0.168354E+10 | 372533.47 | 0.168317E+10 | 0.00 | 0.00 |
October | 0.540672E+09 | 0.249057E+10 | 0.111476E+10 | 0.00 | 0.111476E+10 | 0.00 | 0.00 |
November | 0.106127E+09 | 0.289725E+10 | 0.648199E+09 | 0.00 | 0.648199E+09 | 0.00 | 0.00 |
December | 11950736.84 | 0.367730E+10 | 0.456136E+09 | 0.00 | 0.456136E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.133174E+11 | 0.282835E+11 | 0.198637E+11 | 0.531377E+09 | 0.193323E+11 | 0.00 | 0.00 |
Minimum of Months | 11950736.84 | 0.137555E+10 | 0.456136E+09 | 0.00 | 0.456136E+09 | 0.00 | 0.00 |
Maximum of Months | 0.263610E+10 | 0.367730E+10 | 0.296652E+10 | 0.186020E+09 | 0.278050E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.543072E+09 | 0.214435E+10 | 0.859020E+09 | 0.345069E+09 | 0.513951E+09 | 0.00 | 0.00 |
February | 0.806525E+09 | 0.183787E+10 | 0.115699E+10 | 0.427398E+09 | 0.729587E+09 | 0.00 | 0.00 |
March | 0.895547E+09 | 0.167247E+10 | 0.133862E+10 | 0.263792E+09 | 0.107483E+10 | 0.00 | 0.00 |
April | 0.368381E+10 | 0.139738E+10 | 0.347836E+10 | 0.163450E+10 | 0.184386E+10 | 0.00 | 0.00 |
May | 0.388642E+10 | 0.126396E+10 | 0.377930E+10 | 0.164808E+10 | 0.213121E+10 | 0.00 | 0.00 |
June | 0.394361E+10 | 0.978262E+09 | 0.362014E+10 | 0.144584E+10 | 0.217430E+10 | 0.00 | 0.00 |
July | 0.433440E+10 | 0.941832E+09 | 0.381863E+10 | 0.162291E+10 | 0.219572E+10 | 0.00 | 0.00 |
August | 0.422919E+10 | 0.101744E+10 | 0.361732E+10 | 0.172832E+10 | 0.188900E+10 | 0.00 | 0.00 |
September | 0.357929E+10 | 0.123670E+10 | 0.315243E+10 | 0.167632E+10 | 0.147612E+10 | 0.00 | 0.00 |
October | 0.144525E+10 | 0.161035E+10 | 0.157245E+10 | 0.651660E+09 | 0.920785E+09 | 0.00 | 0.00 |
November | 0.498417E+09 | 0.184855E+10 | 0.793319E+09 | 0.270374E+09 | 0.522945E+09 | 0.00 | 0.00 |
December | 0.335468E+09 | 0.234122E+10 | 0.607544E+09 | 0.225876E+09 | 0.381668E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.281810E+11 | 0.182904E+11 | 0.277941E+11 | 0.119401E+11 | 0.158540E+11 | 0.00 | 0.00 |
Minimum of Months | 0.335468E+09 | 0.941832E+09 | 0.607544E+09 | 0.225876E+09 | 0.381668E+09 | 0.00 | 0.00 |
Maximum of Months | 0.433440E+10 | 0.234122E+10 | 0.381863E+10 | 0.172832E+10 | 0.219572E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.363633E+10 | 0.311626E+10 | 0.357900E+10 | 0.231683E+10 | 0.126217E+10 | 0.00 | 0.00 |
February | 0.410213E+10 | 0.277875E+10 | 0.394808E+10 | 0.240917E+10 | 0.153891E+10 | 0.00 | 0.00 |
March | 0.230750E+10 | 0.256284E+10 | 0.270250E+10 | 0.786845E+09 | 0.191566E+10 | 0.00 | 0.00 |
April | 0.624452E+10 | 0.227956E+10 | 0.543093E+10 | 0.245471E+10 | 0.297622E+10 | 0.00 | 0.00 |
May | 0.493892E+10 | 0.206631E+10 | 0.464162E+10 | 0.151116E+10 | 0.313046E+10 | 0.00 | 0.00 |
June | 0.456522E+10 | 0.157585E+10 | 0.413799E+10 | 0.100163E+10 | 0.313636E+10 | 0.00 | 0.00 |
July | 0.548914E+10 | 0.152247E+10 | 0.463288E+10 | 0.145083E+10 | 0.318205E+10 | 0.00 | 0.00 |
August | 0.680260E+10 | 0.164702E+10 | 0.542872E+10 | 0.244203E+10 | 0.298669E+10 | 0.00 | 0.00 |
September | 0.771433E+10 | 0.199131E+10 | 0.620838E+10 | 0.363696E+10 | 0.257141E+10 | 0.00 | 0.00 |
October | 0.494045E+10 | 0.248424E+10 | 0.440759E+10 | 0.257603E+10 | 0.183156E+10 | 0.00 | 0.00 |
November | 0.308374E+10 | 0.278675E+10 | 0.302417E+10 | 0.183968E+10 | 0.118449E+10 | 0.00 | 0.00 |
December | 0.244388E+10 | 0.350352E+10 | 0.247683E+10 | 0.158692E+10 | 0.889915E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.562688E+11 | 0.283149E+11 | 0.506187E+11 | 0.240128E+11 | 0.266059E+11 | 0.00 | 0.00 |
Minimum of Months | 0.230750E+10 | 0.152247E+10 | 0.247683E+10 | 0.786845E+09 | 0.889915E+09 | 0.00 | 0.00 |
Maximum of Months | 0.771433E+10 | 0.350352E+10 | 0.620838E+10 | 0.363696E+10 | 0.318205E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.539541E+09 | 0.218481E+10 | 0.835357E+09 | 0.276005E+09 | 0.559352E+09 | 0.00 | 0.00 |
February | 0.110578E+10 | 0.189864E+10 | 0.133591E+10 | 0.564062E+09 | 0.771846E+09 | 0.00 | 0.00 |
March | 0.893113E+09 | 0.169846E+10 | 0.133737E+10 | 0.255838E+09 | 0.108153E+10 | 0.00 | 0.00 |
April | 0.319650E+10 | 0.147731E+10 | 0.305378E+10 | 0.121298E+10 | 0.184079E+10 | 0.00 | 0.00 |
May | 0.383185E+10 | 0.133282E+10 | 0.370222E+10 | 0.150545E+10 | 0.219677E+10 | 0.00 | 0.00 |
June | 0.429574E+10 | 0.103553E+10 | 0.386903E+10 | 0.159273E+10 | 0.227630E+10 | 0.00 | 0.00 |
July | 0.471239E+10 | 0.100250E+10 | 0.407178E+10 | 0.179526E+10 | 0.227653E+10 | 0.00 | 0.00 |
August | 0.400362E+10 | 0.108547E+10 | 0.342003E+10 | 0.148077E+10 | 0.193925E+10 | 0.00 | 0.00 |
September | 0.300306E+10 | 0.130991E+10 | 0.265526E+10 | 0.119068E+10 | 0.146458E+10 | 0.00 | 0.00 |
October | 0.134047E+10 | 0.165896E+10 | 0.146369E+10 | 0.526337E+09 | 0.937357E+09 | 0.00 | 0.00 |
November | 0.501986E+09 | 0.190353E+10 | 0.766549E+09 | 0.223765E+09 | 0.542784E+09 | 0.00 | 0.00 |
December | 0.181006E+09 | 0.242692E+10 | 0.448353E+09 | 94611958.57 | 0.353741E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.276051E+11 | 0.190149E+11 | 0.269593E+11 | 0.107185E+11 | 0.162408E+11 | 0.00 | 0.00 |
Minimum of Months | 0.181006E+09 | 0.100250E+10 | 0.448353E+09 | 94611958.57 | 0.353741E+09 | 0.00 | 0.00 |
Maximum of Months | 0.471239E+10 | 0.242692E+10 | 0.407178E+10 | 0.179526E+10 | 0.227653E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 65886202.38 | 0.357213E+10 | 0.630410E+09 | 0.00 | 0.630410E+09 | 0.00 | 0.00 |
February | 0.176623E+09 | 0.302888E+10 | 0.889146E+09 | 0.00 | 0.889146E+09 | 0.00 | 0.00 |
March | 0.557614E+09 | 0.273125E+10 | 0.136225E+10 | 0.00 | 0.136225E+10 | 0.00 | 0.00 |
April | 0.151006E+10 | 0.219848E+10 | 0.214641E+10 | 9606424.32 | 0.213680E+10 | 0.00 | 0.00 |
May | 0.193781E+10 | 0.186963E+10 | 0.277301E+10 | 0.133784E+09 | 0.263922E+10 | 0.00 | 0.00 |
June | 0.258470E+10 | 0.144574E+10 | 0.296650E+10 | 0.186019E+09 | 0.278049E+10 | 0.00 | 0.00 |
July | 0.268213E+10 | 0.139182E+10 | 0.290769E+10 | 0.165783E+09 | 0.274190E+10 | 0.00 | 0.00 |
August | 0.206955E+10 | 0.155073E+10 | 0.228559E+10 | 35809542.75 | 0.224978E+10 | 0.00 | 0.00 |
September | 0.131516E+10 | 0.201600E+10 | 0.168353E+10 | 372531.54 | 0.168316E+10 | 0.00 | 0.00 |
October | 0.511414E+09 | 0.268940E+10 | 0.111475E+10 | 0.00 | 0.111475E+10 | 0.00 | 0.00 |
November | 89136546.93 | 0.313474E+10 | 0.648195E+09 | 0.00 | 0.648195E+09 | 0.00 | 0.00 |
December | 5347387.46 | 0.392240E+10 | 0.456133E+09 | 0.00 | 0.456133E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.135054E+11 | 0.295512E+11 | 0.198636E+11 | 0.531374E+09 | 0.193322E+11 | 0.00 | 0.00 |
Minimum of Months | 5347387.46 | 0.139182E+10 | 0.456133E+09 | 0.00 | 0.456133E+09 | 0.00 | 0.00 |
Maximum of Months | 0.268213E+10 | 0.392240E+10 | 0.296650E+10 | 0.186019E+09 | 0.278049E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.535151E+09 | 0.225338E+10 | 0.859013E+09 | 0.345065E+09 | 0.513947E+09 | 0.00 | 0.00 |
February | 0.796701E+09 | 0.193255E+10 | 0.115698E+10 | 0.427394E+09 | 0.729582E+09 | 0.00 | 0.00 |
March | 0.895446E+09 | 0.174333E+10 | 0.133861E+10 | 0.263790E+09 | 0.107482E+10 | 0.00 | 0.00 |
April | 0.369933E+10 | 0.146418E+10 | 0.347833E+10 | 0.163448E+10 | 0.184385E+10 | 0.00 | 0.00 |
May | 0.389751E+10 | 0.133097E+10 | 0.377927E+10 | 0.164806E+10 | 0.213120E+10 | 0.00 | 0.00 |
June | 0.396642E+10 | 0.101633E+10 | 0.362011E+10 | 0.144583E+10 | 0.217428E+10 | 0.00 | 0.00 |
July | 0.435426E+10 | 0.984399E+09 | 0.381860E+10 | 0.162290E+10 | 0.219571E+10 | 0.00 | 0.00 |
August | 0.424221E+10 | 0.107404E+10 | 0.361729E+10 | 0.172830E+10 | 0.188899E+10 | 0.00 | 0.00 |
September | 0.357137E+10 | 0.133420E+10 | 0.315241E+10 | 0.167630E+10 | 0.147611E+10 | 0.00 | 0.00 |
October | 0.141829E+10 | 0.176446E+10 | 0.157243E+10 | 0.651654E+09 | 0.920779E+09 | 0.00 | 0.00 |
November | 0.479678E+09 | 0.200676E+10 | 0.793312E+09 | 0.270371E+09 | 0.522941E+09 | 0.00 | 0.00 |
December | 0.323581E+09 | 0.249513E+10 | 0.607539E+09 | 0.225873E+09 | 0.381665E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.281800E+11 | 0.193997E+11 | 0.277939E+11 | 0.119400E+11 | 0.158539E+11 | 0.00 | 0.00 |
Minimum of Months | 0.323581E+09 | 0.984399E+09 | 0.607539E+09 | 0.225873E+09 | 0.381665E+09 | 0.00 | 0.00 |
Maximum of Months | 0.435426E+10 | 0.249513E+10 | 0.381860E+10 | 0.172830E+10 | 0.219571E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.366646E+10 | 0.324579E+10 | 0.357904E+10 | 0.231686E+10 | 0.126218E+10 | 0.00 | 0.00 |
February | 0.414230E+10 | 0.290991E+10 | 0.394813E+10 | 0.240920E+10 | 0.153893E+10 | 0.00 | 0.00 |
March | 0.236499E+10 | 0.262421E+10 | 0.270253E+10 | 0.786854E+09 | 0.191567E+10 | 0.00 | 0.00 |
April | 0.634305E+10 | 0.234422E+10 | 0.543098E+10 | 0.245474E+10 | 0.297624E+10 | 0.00 | 0.00 |
May | 0.504610E+10 | 0.210602E+10 | 0.464166E+10 | 0.151117E+10 | 0.313049E+10 | 0.00 | 0.00 |
June | 0.467307E+10 | 0.158434E+10 | 0.413802E+10 | 0.100164E+10 | 0.313638E+10 | 0.00 | 0.00 |
July | 0.556908E+10 | 0.155641E+10 | 0.463292E+10 | 0.145085E+10 | 0.318207E+10 | 0.00 | 0.00 |
August | 0.685808E+10 | 0.172848E+10 | 0.542877E+10 | 0.244206E+10 | 0.298671E+10 | 0.00 | 0.00 |
September | 0.773991E+10 | 0.214853E+10 | 0.620844E+10 | 0.363701E+10 | 0.257143E+10 | 0.00 | 0.00 |
October | 0.494526E+10 | 0.270938E+10 | 0.440763E+10 | 0.257606E+10 | 0.183157E+10 | 0.00 | 0.00 |
November | 0.309323E+10 | 0.299610E+10 | 0.302420E+10 | 0.183970E+10 | 0.118450E+10 | 0.00 | 0.00 |
December | 0.245637E+10 | 0.366538E+10 | 0.247686E+10 | 0.158693E+10 | 0.889923E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.568979E+11 | 0.296188E+11 | 0.506192E+11 | 0.240131E+11 | 0.266061E+11 | 0.00 | 0.00 |
Minimum of Months | 0.236499E+10 | 0.155641E+10 | 0.247686E+10 | 0.786854E+09 | 0.889923E+09 | 0.00 | 0.00 |
Maximum of Months | 0.773991E+10 | 0.366538E+10 | 0.620844E+10 | 0.363701E+10 | 0.318207E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.537369E+09 | 0.229511E+10 | 0.835350E+09 | 0.276002E+09 | 0.559348E+09 | 0.00 | 0.00 |
February | 0.110456E+10 | 0.200045E+10 | 0.133590E+10 | 0.564056E+09 | 0.771840E+09 | 0.00 | 0.00 |
March | 0.901407E+09 | 0.177112E+10 | 0.133736E+10 | 0.255836E+09 | 0.108152E+10 | 0.00 | 0.00 |
April | 0.321983E+10 | 0.153582E+10 | 0.305376E+10 | 0.121297E+10 | 0.184078E+10 | 0.00 | 0.00 |
May | 0.384844E+10 | 0.140042E+10 | 0.370219E+10 | 0.150543E+10 | 0.219676E+10 | 0.00 | 0.00 |
June | 0.431870E+10 | 0.108336E+10 | 0.386900E+10 | 0.159271E+10 | 0.227629E+10 | 0.00 | 0.00 |
July | 0.473433E+10 | 0.104964E+10 | 0.407175E+10 | 0.179524E+10 | 0.227651E+10 | 0.00 | 0.00 |
August | 0.401693E+10 | 0.114635E+10 | 0.342000E+10 | 0.148076E+10 | 0.193924E+10 | 0.00 | 0.00 |
September | 0.299280E+10 | 0.140596E+10 | 0.265524E+10 | 0.119066E+10 | 0.146458E+10 | 0.00 | 0.00 |
October | 0.131901E+10 | 0.180793E+10 | 0.146368E+10 | 0.526332E+09 | 0.937351E+09 | 0.00 | 0.00 |
November | 0.491290E+09 | 0.206219E+10 | 0.766543E+09 | 0.223763E+09 | 0.542781E+09 | 0.00 | 0.00 |
December | 0.175243E+09 | 0.258173E+10 | 0.448349E+09 | 94611013.42 | 0.353738E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.276599E+11 | 0.201401E+11 | 0.269591E+11 | 0.107184E+11 | 0.162407E+11 | 0.00 | 0.00 |
Minimum of Months | 0.175243E+09 | 0.104964E+10 | 0.448349E+09 | 94611013.42 | 0.353738E+09 | 0.00 | 0.00 |
Maximum of Months | 0.473433E+10 | 0.258173E+10 | 0.407175E+10 | 0.179524E+10 | 0.227651E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 58545994.77 | 0.362891E+10 | 0.630413E+09 | 0.00 | 0.630413E+09 | 0.00 | 0.00 |
February | 0.158325E+09 | 0.309291E+10 | 0.889150E+09 | 0.00 | 0.889150E+09 | 0.00 | 0.00 |
March | 0.515055E+09 | 0.280764E+10 | 0.136226E+10 | 0.00 | 0.136226E+10 | 0.00 | 0.00 |
April | 0.140656E+10 | 0.230971E+10 | 0.214642E+10 | 9606474.10 | 0.213681E+10 | 0.00 | 0.00 |
May | 0.182242E+10 | 0.195194E+10 | 0.277302E+10 | 0.133785E+09 | 0.263924E+10 | 0.00 | 0.00 |
June | 0.249441E+10 | 0.150180E+10 | 0.296652E+10 | 0.186020E+09 | 0.278050E+10 | 0.00 | 0.00 |
July | 0.260877E+10 | 0.143666E+10 | 0.290770E+10 | 0.165783E+09 | 0.274192E+10 | 0.00 | 0.00 |
August | 0.200601E+10 | 0.160475E+10 | 0.228560E+10 | 35809728.31 | 0.224979E+10 | 0.00 | 0.00 |
September | 0.127198E+10 | 0.206310E+10 | 0.168354E+10 | 372533.47 | 0.168317E+10 | 0.00 | 0.00 |
October | 0.490384E+09 | 0.270735E+10 | 0.111476E+10 | 0.00 | 0.111476E+10 | 0.00 | 0.00 |
November | 85790339.84 | 0.313061E+10 | 0.648199E+09 | 0.00 | 0.648199E+09 | 0.00 | 0.00 |
December | 5229567.38 | 0.392239E+10 | 0.456136E+09 | 0.00 | 0.456136E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.129235E+11 | 0.301578E+11 | 0.198637E+11 | 0.531377E+09 | 0.193323E+11 | 0.00 | 0.00 |
Minimum of Months | 5229567.38 | 0.143666E+10 | 0.456136E+09 | 0.00 | 0.456136E+09 | 0.00 | 0.00 |
Maximum of Months | 0.260877E+10 | 0.392239E+10 | 0.296652E+10 | 0.186020E+09 | 0.278050E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.524348E+09 | 0.227627E+10 | 0.859020E+09 | 0.345069E+09 | 0.513951E+09 | 0.00 | 0.00 |
February | 0.778634E+09 | 0.195900E+10 | 0.115699E+10 | 0.427398E+09 | 0.729587E+09 | 0.00 | 0.00 |
March | 0.865729E+09 | 0.178006E+10 | 0.133862E+10 | 0.263792E+09 | 0.107483E+10 | 0.00 | 0.00 |
April | 0.365785E+10 | 0.147178E+10 | 0.347836E+10 | 0.163450E+10 | 0.184386E+10 | 0.00 | 0.00 |
May | 0.385818E+10 | 0.133057E+10 | 0.377930E+10 | 0.164808E+10 | 0.213121E+10 | 0.00 | 0.00 |
June | 0.393059E+10 | 0.101978E+10 | 0.362014E+10 | 0.144584E+10 | 0.217430E+10 | 0.00 | 0.00 |
July | 0.432494E+10 | 0.978927E+09 | 0.381863E+10 | 0.162291E+10 | 0.219572E+10 | 0.00 | 0.00 |
August | 0.421924E+10 | 0.106160E+10 | 0.361732E+10 | 0.172832E+10 | 0.188900E+10 | 0.00 | 0.00 |
September | 0.355705E+10 | 0.130579E+10 | 0.315243E+10 | 0.167632E+10 | 0.147612E+10 | 0.00 | 0.00 |
October | 0.141210E+10 | 0.173691E+10 | 0.157245E+10 | 0.651660E+09 | 0.920785E+09 | 0.00 | 0.00 |
November | 0.476281E+09 | 0.198943E+10 | 0.793319E+09 | 0.270374E+09 | 0.522945E+09 | 0.00 | 0.00 |
December | 0.320400E+09 | 0.249344E+10 | 0.607544E+09 | 0.225876E+09 | 0.381668E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.279254E+11 | 0.194036E+11 | 0.277941E+11 | 0.119401E+11 | 0.158540E+11 | 0.00 | 0.00 |
Minimum of Months | 0.320400E+09 | 0.978927E+09 | 0.607544E+09 | 0.225876E+09 | 0.381668E+09 | 0.00 | 0.00 |
Maximum of Months | 0.432494E+10 | 0.249344E+10 | 0.381863E+10 | 0.172832E+10 | 0.219572E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.359528E+10 | 0.331305E+10 | 0.357900E+10 | 0.231683E+10 | 0.126217E+10 | 0.00 | 0.00 |
February | 0.405489E+10 | 0.296167E+10 | 0.394808E+10 | 0.240917E+10 | 0.153891E+10 | 0.00 | 0.00 |
March | 0.225820E+10 | 0.273313E+10 | 0.270250E+10 | 0.786845E+09 | 0.191566E+10 | 0.00 | 0.00 |
April | 0.621101E+10 | 0.240955E+10 | 0.543093E+10 | 0.245471E+10 | 0.297622E+10 | 0.00 | 0.00 |
May | 0.490032E+10 | 0.219104E+10 | 0.464162E+10 | 0.151116E+10 | 0.313046E+10 | 0.00 | 0.00 |
June | 0.454281E+10 | 0.165462E+10 | 0.413799E+10 | 0.100163E+10 | 0.313636E+10 | 0.00 | 0.00 |
July | 0.547260E+10 | 0.159418E+10 | 0.463288E+10 | 0.145083E+10 | 0.318205E+10 | 0.00 | 0.00 |
August | 0.678807E+10 | 0.173028E+10 | 0.542872E+10 | 0.244203E+10 | 0.298669E+10 | 0.00 | 0.00 |
September | 0.768671E+10 | 0.210970E+10 | 0.620838E+10 | 0.363696E+10 | 0.257141E+10 | 0.00 | 0.00 |
October | 0.489227E+10 | 0.268189E+10 | 0.440759E+10 | 0.257603E+10 | 0.183156E+10 | 0.00 | 0.00 |
November | 0.304163E+10 | 0.300217E+10 | 0.302417E+10 | 0.183968E+10 | 0.118449E+10 | 0.00 | 0.00 |
December | 0.241036E+10 | 0.373118E+10 | 0.247683E+10 | 0.158692E+10 | 0.889915E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.558542E+11 | 0.301125E+11 | 0.506187E+11 | 0.240128E+11 | 0.266059E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225820E+10 | 0.159418E+10 | 0.247683E+10 | 0.786845E+09 | 0.889915E+09 | 0.00 | 0.00 |
Maximum of Months | 0.768671E+10 | 0.373118E+10 | 0.620838E+10 | 0.363696E+10 | 0.318205E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.524975E+09 | 0.232072E+10 | 0.835357E+09 | 0.276005E+09 | 0.559352E+09 | 0.00 | 0.00 |
February | 0.108371E+10 | 0.202503E+10 | 0.133591E+10 | 0.564062E+09 | 0.771846E+09 | 0.00 | 0.00 |
March | 0.866788E+09 | 0.181137E+10 | 0.133737E+10 | 0.255838E+09 | 0.108153E+10 | 0.00 | 0.00 |
April | 0.316957E+10 | 0.156366E+10 | 0.305378E+10 | 0.121298E+10 | 0.184079E+10 | 0.00 | 0.00 |
May | 0.380144E+10 | 0.141226E+10 | 0.370222E+10 | 0.150545E+10 | 0.219677E+10 | 0.00 | 0.00 |
June | 0.428041E+10 | 0.108688E+10 | 0.386903E+10 | 0.159273E+10 | 0.227630E+10 | 0.00 | 0.00 |
July | 0.470031E+10 | 0.104947E+10 | 0.407178E+10 | 0.179526E+10 | 0.227653E+10 | 0.00 | 0.00 |
August | 0.398933E+10 | 0.114163E+10 | 0.342003E+10 | 0.148077E+10 | 0.193925E+10 | 0.00 | 0.00 |
September | 0.297630E+10 | 0.139375E+10 | 0.265526E+10 | 0.119068E+10 | 0.146458E+10 | 0.00 | 0.00 |
October | 0.130891E+10 | 0.179282E+10 | 0.146369E+10 | 0.526337E+09 | 0.937357E+09 | 0.00 | 0.00 |
November | 0.485559E+09 | 0.205082E+10 | 0.766549E+09 | 0.223765E+09 | 0.542784E+09 | 0.00 | 0.00 |
December | 0.172212E+09 | 0.258530E+10 | 0.448353E+09 | 94611958.57 | 0.353741E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.273595E+11 | 0.202337E+11 | 0.269593E+11 | 0.107185E+11 | 0.162408E+11 | 0.00 | 0.00 |
Minimum of Months | 0.172212E+09 | 0.104947E+10 | 0.448353E+09 | 94611958.57 | 0.353741E+09 | 0.00 | 0.00 |
Maximum of Months | 0.470031E+10 | 0.258530E+10 | 0.407178E+10 | 0.179526E+10 | 0.227653E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.532838E+10 | -0.459924E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -729136255.8 | 58.99 | 0.00 | 0.00 |
February | 0.485760E+10 | -0.420775E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -649847798.9 | 58.98 | 0.00 | 0.00 |
March | 0.566510E+10 | -0.494791E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -717192645.6 | 58.98 | 0.00 | 0.00 |
April | 0.504493E+10 | -0.436808E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -676850770.6 | 58.98 | 0.00 | 0.00 |
May | 0.525598E+10 | -0.456065E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -695328544.3 | 58.98 | 0.00 | 0.00 |
June | 0.507891E+10 | -0.440831E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -670598943.0 | 58.98 | 0.00 | 0.00 |
July | 0.475735E+10 | -0.406598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691369368.1 | 58.98 | 0.00 | 0.00 |
August | 0.515425E+10 | -0.446137E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692876773.6 | 58.98 | 0.00 | 0.00 |
September | 0.471727E+10 | -0.404683E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -670439498.6 | 58.98 | 0.00 | 0.00 |
October | 0.497159E+10 | -0.426859E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -703007820.9 | 58.98 | 0.00 | 0.00 |
November | 0.500758E+10 | -0.431664E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -690935275.2 | 58.98 | 0.00 | 0.00 |
December | 0.511436E+10 | -0.438744E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -726917712.7 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.609533E+11 | -0.526388E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.831450E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.471727E+10 | -0.494791E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -729136255.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.566510E+10 | -0.404683E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -649847798.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:50 | 3397.06 | 31.56 | 158.33 | 214.50 | 2976.06 | 37.19 | 189.83 | 185.00 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 5014.98 | 33.23 | 193.50 | 238.00 | 2402.28 | 31.40 | 186.67 | 210.50 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 3727.55 | 30.25 | 180.33 | 302.17 | 1037.25 | 20.81 | 127.50 | 254.50 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:10 | 2271.62 | 18.33 | 0.00 | 348.83 | 1285.44 | 21.11 | 216.67 | 318.67 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 1802.10 | 17.92 | 0.00 | 402.17 | 1011.93 | 20.69 | 197.33 | 357.67 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:00 | 1751.38 | 18.24 | 0.00 | 404.00 | 972.14 | 20.99 | 202.33 | 359.50 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:00 | 1744.67 | 17.98 | 0.00 | 413.83 | 993.82 | 20.76 | 195.83 | 368.83 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 2024.99 | 17.97 | 0.00 | 375.33 | 1169.91 | 20.76 | 199.00 | 337.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 3039.16 | 20.07 | 29.50 | 324.67 | 1424.67 | 21.32 | 192.17 | 293.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 6417.95 | 34.01 | 212.00 | 274.67 | 1866.71 | 23.92 | 163.17 | 230.67 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 3988.36 | 32.97 | 149.33 | 207.00 | 3414.68 | 37.10 | 167.17 | 164.00 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3294.74 | 33.74 | 111.67 | 172.83 | 2885.16 | 38.15 | 128.67 | 123.17 |
Annual Sum or Average | 3515.67 | 0.51 | 2855.92 | 23.08 | 1034.67 | 3678.00 | 1531.33 | 24.10 | 2166.33 | 3202.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1744.67 | 17.92 | 0.00 | 172.83 | 972.14 | 20.69 | 127.50 | 123.17 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 6417.95 | 34.01 | 212.00 | 413.83 | 3414.68 | 38.15 | 216.67 | 368.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:50 | 1191.61 | 19.31 | 62.67 | 197.00 | 756.63 | 23.08 | 70.83 | 122.50 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1489.91 | 20.10 | 62.17 | 228.17 | 815.47 | 21.48 | 62.50 | 171.83 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1728.84 | 20.75 | 71.33 | 294.83 | 760.52 | 20.71 | 42.17 | 228.67 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3219.89 | 21.77 | 107.17 | 357.83 | 1852.59 | 23.21 | 79.17 | 322.00 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3350.31 | 21.82 | 133.33 | 414.50 | 1491.81 | 22.10 | 72.17 | 363.83 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3363.98 | 21.72 | 129.50 | 411.50 | 1527.21 | 22.90 | 81.00 | 376.00 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3282.08 | 21.82 | 137.67 | 424.33 | 1475.60 | 22.35 | 78.00 | 386.17 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3118.24 | 20.72 | 106.83 | 382.67 | 1383.04 | 22.43 | 72.50 | 347.33 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 2853.42 | 20.52 | 84.17 | 329.33 | 1647.64 | 23.65 | 97.33 | 294.50 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:49 | 2335.62 | 22.00 | 82.33 | 263.50 | 1034.15 | 22.05 | 72.00 | 195.50 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:50 | 1244.39 | 19.95 | 53.17 | 189.83 | 740.20 | 23.04 | 68.00 | 114.17 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 997.30 | 19.38 | 36.17 | 147.33 | 764.84 | 25.26 | 62.50 | 88.33 |
Annual Sum or Average | 3515.67 | 0.50 | 2663.69 | 21.07 | 1066.50 | 3640.83 | 1311.78 | 22.61 | 858.17 | 3010.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 997.30 | 19.31 | 36.17 | 147.33 | 740.20 | 20.71 | 42.17 | 88.33 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3363.98 | 22.00 | 137.67 | 424.33 | 1852.59 | 25.26 | 97.33 | 386.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.58 | 0.48 | 01-JAN-10:39 | 446.98 | 12.90 | 0.00 | 166.33 | 261.71 | 15.85 | 0.00 | 28.50 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-12:09 | 592.67 | 14.69 | 0.00 | 211.83 | 348.88 | 17.56 | 0.00 | 106.50 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 739.40 | 15.54 | 0.00 | 288.50 | 401.47 | 18.16 | 0.00 | 173.83 |
April | 359.67 | 0.50 | 0.48 | 01-APR-07:19 | 968.49 | 17.43 | 0.00 | 355.17 | 579.87 | 20.12 | 14.33 | 312.67 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:00 | 1153.71 | 19.39 | 36.50 | 419.67 | 665.56 | 22.11 | 130.33 | 388.67 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1307.75 | 19.58 | 32.83 | 422.00 | 758.94 | 23.25 | 163.33 | 396.33 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:00 | 1215.61 | 19.34 | 34.00 | 433.33 | 720.50 | 23.03 | 170.83 | 407.83 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 983.66 | 17.48 | 0.00 | 387.00 | 597.72 | 20.23 | 38.83 | 347.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:00 | 787.43 | 16.70 | 0.00 | 317.17 | 497.22 | 19.55 | 0.33 | 262.50 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:49 | 670.03 | 15.42 | 0.00 | 247.00 | 403.85 | 18.28 | 0.00 | 145.83 |
November | 171.33 | 0.56 | 0.48 | 01-NOV-12:20 | 495.43 | 13.69 | 0.00 | 159.17 | 291.84 | 16.60 | 0.00 | 51.33 |
December | 131.67 | 0.58 | 0.48 | 02-DEC-10:00 | 418.54 | 13.00 | 0.00 | 103.33 | 248.75 | 16.09 | 0.00 | 13.50 |
Annual Sum or Average | 3515.67 | 0.51 | 914.79 | 17.06 | 103.33 | 3510.50 | 541.14 | 20.07 | 518.00 | 2634.50 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 418.54 | 12.90 | 0.00 | 103.33 | 248.75 | 15.85 | 0.00 | 13.50 | |
Maximum of Months | 429.00 | 0.58 | 0.48 | 1307.75 | 19.58 | 36.50 | 433.33 | 758.94 | 23.25 | 170.83 | 407.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-10:30 | 1094.77 | 19.11 | 64.00 | 190.17 | 654.29 | 22.19 | 64.83 | 121.00 |
February | 217.00 | 0.52 | 0.48 | 01-FEB-11:39 | 1742.75 | 19.69 | 58.33 | 224.00 | 927.04 | 20.83 | 53.17 | 163.83 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1631.30 | 20.66 | 72.17 | 293.50 | 886.39 | 21.93 | 54.33 | 231.00 |
April | 359.67 | 0.51 | 0.48 | 01-APR-08:09 | 3046.88 | 20.66 | 101.83 | 346.17 | 1398.83 | 21.15 | 50.00 | 313.83 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-07:19 | 2786.68 | 18.36 | 73.83 | 403.67 | 1558.90 | 20.48 | 45.50 | 371.33 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-06:10 | 3222.38 | 17.43 | 50.33 | 406.50 | 1444.05 | 18.88 | 0.00 | 367.33 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3197.32 | 17.29 | 52.83 | 416.83 | 1466.59 | 18.82 | 3.67 | 380.67 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2863.03 | 19.31 | 86.67 | 373.17 | 1594.52 | 21.09 | 59.17 | 336.17 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:20 | 2781.31 | 20.96 | 96.83 | 314.83 | 1514.55 | 22.44 | 75.67 | 278.33 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2199.29 | 21.37 | 79.83 | 257.67 | 971.12 | 21.44 | 62.17 | 192.00 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:00 | 1224.01 | 19.45 | 51.67 | 181.33 | 670.60 | 21.86 | 59.67 | 115.83 |
December | 131.67 | 0.55 | 0.48 | 02-DEC-10:20 | 889.25 | 18.94 | 37.67 | 136.00 | 466.74 | 19.84 | 31.83 | 66.83 |
Annual Sum or Average | 3515.67 | 0.51 | 2506.66 | 19.25 | 826.00 | 3543.83 | 1263.71 | 20.73 | 560.00 | 2938.17 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 889.25 | 17.29 | 37.67 | 136.00 | 466.74 | 18.82 | 0.00 | 66.83 | |
Maximum of Months | 429.00 | 0.55 | 0.48 | 3222.38 | 21.37 | 101.83 | 416.83 | 1594.52 | 22.44 | 75.67 | 380.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:50 | 3267.03 | 30.63 | 158.33 | 212.50 | 2883.03 | 36.97 | 189.83 | 179.50 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 4868.30 | 32.66 | 193.50 | 236.33 | 2297.29 | 30.05 | 141.83 | 207.83 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 3621.46 | 29.53 | 180.00 | 300.50 | 971.59 | 17.83 | 4.50 | 250.00 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:19 | 2143.60 | 14.76 | 0.00 | 348.17 | 1198.31 | 18.71 | 11.50 | 315.17 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 1709.24 | 14.39 | 0.00 | 400.17 | 951.90 | 18.29 | 0.00 | 351.83 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1665.78 | 14.71 | 0.00 | 401.50 | 918.88 | 18.60 | 0.00 | 354.33 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1655.29 | 14.49 | 0.00 | 411.33 | 936.36 | 18.42 | 1.33 | 365.17 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 1911.20 | 14.43 | 0.00 | 372.00 | 1092.43 | 18.37 | 5.83 | 332.50 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 2890.72 | 16.69 | 29.50 | 321.83 | 1317.91 | 18.82 | 11.17 | 289.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:00 | 6254.60 | 33.57 | 211.67 | 272.50 | 1753.16 | 21.34 | 34.83 | 227.00 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 3834.72 | 32.15 | 148.33 | 203.00 | 3317.35 | 36.89 | 167.17 | 160.50 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3093.38 | 31.24 | 104.17 | 165.50 | 2788.62 | 37.92 | 128.67 | 120.33 |
Annual Sum or Average | 3515.67 | 0.51 | 2735.12 | 20.44 | 1025.50 | 3645.33 | 1451.48 | 22.03 | 696.67 | 3153.50 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 1655.29 | 14.39 | 0.00 | 165.50 | 918.88 | 17.83 | 0.00 | 120.33 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 6254.60 | 33.57 | 211.67 | 411.33 | 3317.35 | 37.92 | 189.83 | 365.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:50 | 1152.52 | 18.89 | 62.67 | 195.00 | 728.61 | 22.86 | 67.33 | 116.67 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1437.36 | 19.66 | 62.00 | 225.50 | 777.02 | 21.22 | 57.67 | 165.00 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1673.96 | 20.34 | 71.33 | 291.83 | 723.11 | 20.48 | 38.83 | 222.17 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:19 | 3119.57 | 21.38 | 107.17 | 356.67 | 1777.03 | 23.03 | 79.17 | 315.83 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3173.62 | 20.04 | 111.00 | 412.67 | 1424.21 | 21.87 | 71.50 | 358.67 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:00 | 3272.47 | 21.28 | 128.50 | 409.67 | 1449.19 | 22.07 | 71.33 | 370.50 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-04:49 | 3115.98 | 20.11 | 115.33 | 422.00 | 1410.61 | 22.17 | 78.00 | 381.50 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3027.31 | 20.32 | 106.83 | 380.33 | 1315.34 | 22.25 | 71.83 | 341.83 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 2764.05 | 20.09 | 84.17 | 326.67 | 1578.91 | 23.45 | 88.50 | 290.83 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:49 | 2266.66 | 21.60 | 82.33 | 260.67 | 982.69 | 21.81 | 61.50 | 190.67 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:00 | 1199.88 | 19.51 | 53.00 | 186.50 | 709.26 | 22.81 | 63.17 | 107.00 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 957.37 | 18.88 | 36.17 | 143.33 | 736.68 | 25.05 | 58.83 | 85.17 |
Annual Sum or Average | 3515.67 | 0.51 | 2565.64 | 20.33 | 1020.50 | 3610.83 | 1252.53 | 22.34 | 807.67 | 2945.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 957.37 | 18.88 | 36.17 | 143.33 | 709.26 | 20.48 | 38.83 | 85.17 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3272.47 | 21.60 | 128.50 | 422.00 | 1777.03 | 25.05 | 88.50 | 381.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.58 | 0.48 | 01-JAN-10:00 | 426.12 | 9.30 | 0.00 | 160.17 | 250.49 | 13.32 | 0.00 | 20.17 |
February | 217.00 | 0.54 | 0.48 | 01-FEB-12:09 | 565.93 | 11.17 | 0.00 | 207.67 | 334.61 | 15.18 | 0.00 | 93.50 |
March | 215.50 | 0.53 | 0.48 | 01-MAR-11:39 | 708.45 | 11.81 | 0.00 | 285.50 | 384.72 | 15.63 | 0.00 | 158.50 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:30 | 927.37 | 14.39 | 0.00 | 354.00 | 558.26 | 18.30 | 0.00 | 307.00 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:00 | 1105.74 | 16.39 | 36.50 | 419.17 | 639.76 | 20.19 | 44.33 | 383.17 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1253.38 | 16.48 | 32.83 | 420.17 | 729.02 | 21.38 | 71.50 | 393.17 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:00 | 1163.31 | 16.31 | 34.00 | 431.33 | 692.81 | 21.24 | 66.17 | 404.50 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 937.87 | 14.34 | 0.00 | 384.00 | 575.62 | 18.34 | 0.00 | 342.17 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:09 | 752.64 | 13.73 | 0.00 | 314.00 | 479.16 | 17.73 | 0.00 | 256.17 |
October | 234.00 | 0.53 | 0.48 | 01-OCT-07:00 | 639.96 | 12.09 | 0.00 | 241.67 | 387.93 | 16.08 | 0.00 | 135.83 |
November | 171.33 | 0.56 | 0.48 | 01-NOV-12:20 | 472.46 | 10.03 | 0.00 | 152.83 | 279.53 | 14.09 | 0.00 | 45.17 |
December | 131.67 | 0.58 | 0.48 | 02-DEC-11:09 | 398.52 | 9.18 | 0.00 | 96.17 | 237.98 | 13.44 | 0.00 | 7.83 |
Annual Sum or Average | 3515.67 | 0.52 | 875.08 | 13.84 | 103.33 | 3466.67 | 520.17 | 18.02 | 182.00 | 2547.17 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 398.52 | 9.18 | 0.00 | 96.17 | 237.98 | 13.32 | 0.00 | 7.83 | |
Maximum of Months | 429.00 | 0.58 | 0.48 | 1253.38 | 16.48 | 36.50 | 431.33 | 729.02 | 21.38 | 71.50 | 404.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-10:30 | 1056.05 | 18.79 | 64.00 | 186.83 | 627.05 | 22.10 | 63.83 | 116.17 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 1682.09 | 19.34 | 58.33 | 221.67 | 881.86 | 20.71 | 52.33 | 157.67 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1523.39 | 18.41 | 55.67 | 290.83 | 849.71 | 21.82 | 54.00 | 223.17 |
April | 359.67 | 0.51 | 0.48 | 01-APR-08:20 | 2962.79 | 20.30 | 101.83 | 343.83 | 1336.55 | 21.01 | 50.00 | 310.50 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-07:19 | 2698.45 | 17.95 | 73.83 | 400.83 | 1473.07 | 20.32 | 45.50 | 364.50 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-06:19 | 3125.39 | 17.01 | 50.33 | 404.50 | 1374.19 | 18.72 | 0.00 | 364.17 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-06:19 | 3100.95 | 16.88 | 52.83 | 414.17 | 1396.97 | 18.66 | 3.67 | 376.83 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2774.89 | 18.93 | 86.67 | 370.00 | 1529.36 | 20.95 | 58.17 | 332.83 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:20 | 2701.38 | 20.59 | 96.83 | 313.00 | 1455.53 | 22.31 | 74.67 | 274.33 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2133.77 | 21.04 | 79.83 | 255.67 | 917.08 | 21.09 | 59.17 | 186.83 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:00 | 1180.79 | 19.12 | 51.67 | 177.67 | 621.90 | 20.49 | 51.00 | 108.50 |
December | 131.67 | 0.55 | 0.48 | 02-DEC-10:30 | 857.51 | 18.61 | 37.67 | 131.67 | 445.25 | 19.74 | 31.00 | 63.67 |
Annual Sum or Average | 3515.67 | 0.51 | 2426.71 | 18.76 | 809.50 | 3510.67 | 1204.16 | 20.52 | 543.33 | 2879.17 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 857.51 | 16.88 | 37.67 | 131.67 | 445.25 | 18.66 | 0.00 | 63.67 | |
Maximum of Months | 429.00 | 0.55 | 0.48 | 3125.39 | 21.04 | 101.83 | 414.17 | 1529.36 | 22.31 | 74.67 | 376.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:50 | 3267.08 | 30.64 | 158.33 | 212.50 | 2882.98 | 36.97 | 189.83 | 179.50 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 4868.33 | 32.66 | 193.50 | 236.33 | 2297.20 | 30.05 | 141.83 | 207.83 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 3621.39 | 29.53 | 180.00 | 300.50 | 971.50 | 17.83 | 4.50 | 250.00 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:19 | 2143.52 | 14.76 | 0.00 | 348.17 | 1198.23 | 18.71 | 11.67 | 315.17 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 1709.17 | 14.39 | 0.00 | 400.17 | 951.83 | 18.29 | 0.00 | 351.83 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1665.70 | 14.72 | 0.00 | 401.50 | 918.82 | 18.60 | 0.00 | 354.33 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-06:10 | 1655.23 | 14.50 | 0.00 | 411.33 | 936.29 | 18.42 | 1.33 | 365.17 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 1911.13 | 14.43 | 0.00 | 372.00 | 1092.36 | 18.37 | 5.83 | 332.50 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 2890.66 | 16.69 | 29.50 | 321.83 | 1317.83 | 18.82 | 11.17 | 289.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:00 | 6254.60 | 33.57 | 211.67 | 272.50 | 1753.07 | 21.35 | 34.83 | 227.00 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 3834.77 | 32.15 | 148.33 | 203.00 | 3317.28 | 36.89 | 167.17 | 160.50 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3093.46 | 31.24 | 104.17 | 165.50 | 2788.57 | 37.92 | 128.67 | 120.33 |
Annual Sum or Average | 3515.67 | 0.51 | 2735.08 | 20.44 | 1025.50 | 3645.33 | 1451.40 | 22.03 | 696.83 | 3153.50 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 1655.23 | 14.39 | 0.00 | 165.50 | 918.82 | 17.83 | 0.00 | 120.33 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 6254.60 | 33.57 | 211.67 | 411.33 | 3317.28 | 37.92 | 189.83 | 365.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:50 | 1152.52 | 18.89 | 62.67 | 195.00 | 728.59 | 22.86 | 67.33 | 116.67 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1437.36 | 19.66 | 62.00 | 225.50 | 776.98 | 21.22 | 57.67 | 165.00 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1673.93 | 20.35 | 71.33 | 291.83 | 723.05 | 20.48 | 38.83 | 222.17 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:19 | 3119.56 | 21.39 | 107.17 | 356.67 | 1776.97 | 23.03 | 79.17 | 315.83 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3173.60 | 20.05 | 111.00 | 412.67 | 1424.14 | 21.88 | 71.50 | 358.67 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:00 | 3272.44 | 21.29 | 128.50 | 409.67 | 1449.12 | 22.07 | 71.33 | 370.50 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-04:49 | 3115.96 | 20.11 | 115.33 | 422.00 | 1410.55 | 22.17 | 78.00 | 381.50 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3027.30 | 20.32 | 106.83 | 380.33 | 1315.28 | 22.25 | 71.83 | 341.83 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 2764.06 | 20.09 | 84.17 | 326.67 | 1578.86 | 23.45 | 88.50 | 290.83 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:49 | 2266.66 | 21.60 | 82.33 | 260.67 | 982.65 | 21.81 | 61.67 | 190.67 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:00 | 1199.88 | 19.52 | 53.00 | 186.50 | 709.23 | 22.81 | 63.17 | 107.00 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 957.37 | 18.89 | 36.17 | 143.33 | 736.65 | 25.05 | 58.83 | 85.17 |
Annual Sum or Average | 3515.67 | 0.51 | 2565.62 | 20.33 | 1020.50 | 3610.83 | 1252.48 | 22.34 | 807.83 | 2945.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 957.37 | 18.89 | 36.17 | 143.33 | 709.23 | 20.48 | 38.83 | 85.17 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3272.44 | 21.60 | 128.50 | 422.00 | 1776.97 | 25.05 | 88.50 | 381.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.58 | 0.48 | 01-JAN-10:00 | 426.11 | 9.30 | 0.00 | 160.17 | 250.47 | 13.33 | 0.00 | 20.17 |
February | 217.00 | 0.54 | 0.48 | 01-FEB-12:09 | 565.92 | 11.17 | 0.00 | 207.67 | 334.59 | 15.18 | 0.00 | 93.50 |
March | 215.50 | 0.53 | 0.48 | 01-MAR-11:39 | 708.42 | 11.81 | 0.00 | 285.50 | 384.69 | 15.63 | 0.00 | 158.50 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:30 | 927.36 | 14.39 | 0.00 | 354.00 | 558.23 | 18.30 | 0.00 | 307.00 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:00 | 1105.72 | 16.39 | 36.50 | 419.17 | 639.73 | 20.19 | 44.50 | 383.17 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1253.35 | 16.48 | 32.83 | 420.17 | 728.98 | 21.38 | 71.50 | 393.17 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:00 | 1163.29 | 16.31 | 34.00 | 431.33 | 692.77 | 21.25 | 66.17 | 404.33 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 937.87 | 14.34 | 0.00 | 384.00 | 575.59 | 18.34 | 0.00 | 342.17 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:09 | 752.64 | 13.73 | 0.00 | 314.00 | 479.14 | 17.73 | 0.00 | 256.17 |
October | 234.00 | 0.53 | 0.48 | 01-OCT-07:00 | 639.96 | 12.09 | 0.00 | 241.67 | 387.91 | 16.08 | 0.00 | 135.83 |
November | 171.33 | 0.56 | 0.48 | 01-NOV-12:20 | 472.46 | 10.03 | 0.00 | 152.83 | 279.51 | 14.09 | 0.00 | 45.00 |
December | 131.67 | 0.58 | 0.48 | 02-DEC-11:09 | 398.51 | 9.19 | 0.00 | 96.17 | 237.96 | 13.44 | 0.00 | 7.83 |
Annual Sum or Average | 3515.67 | 0.52 | 875.06 | 13.84 | 103.33 | 3466.67 | 520.14 | 18.03 | 182.17 | 2546.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 398.51 | 9.19 | 0.00 | 96.17 | 237.96 | 13.33 | 0.00 | 7.83 | |
Maximum of Months | 429.00 | 0.58 | 0.48 | 1253.35 | 16.48 | 36.50 | 431.33 | 728.98 | 21.38 | 71.50 | 404.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-10:30 | 1056.05 | 18.79 | 64.00 | 186.83 | 627.02 | 22.10 | 63.83 | 116.17 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 1682.09 | 19.34 | 58.33 | 221.67 | 881.82 | 20.71 | 52.50 | 157.67 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1523.35 | 18.41 | 55.67 | 290.83 | 849.65 | 21.82 | 54.00 | 223.17 |
April | 359.67 | 0.51 | 0.48 | 01-APR-08:20 | 2962.77 | 20.30 | 101.83 | 344.00 | 1336.49 | 21.01 | 50.00 | 310.50 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-07:19 | 2698.43 | 17.95 | 73.83 | 400.83 | 1473.00 | 20.32 | 45.50 | 364.50 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-06:19 | 3125.35 | 17.02 | 50.33 | 404.50 | 1374.12 | 18.72 | 0.00 | 364.00 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-06:19 | 3100.93 | 16.88 | 52.83 | 414.17 | 1396.90 | 18.66 | 3.67 | 376.83 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2774.88 | 18.93 | 86.67 | 370.00 | 1529.30 | 20.95 | 58.17 | 332.83 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:20 | 2701.38 | 20.59 | 96.83 | 313.00 | 1455.48 | 22.31 | 74.67 | 274.33 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:00 | 2133.77 | 21.04 | 79.83 | 255.67 | 917.04 | 21.09 | 59.17 | 186.83 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:00 | 1180.79 | 19.12 | 51.67 | 177.67 | 621.87 | 20.49 | 51.00 | 108.50 |
December | 131.67 | 0.55 | 0.48 | 02-DEC-10:30 | 857.51 | 18.61 | 37.67 | 131.67 | 445.22 | 19.74 | 31.00 | 63.67 |
Annual Sum or Average | 3515.67 | 0.51 | 2426.70 | 18.76 | 809.50 | 3510.83 | 1204.10 | 20.52 | 543.50 | 2879.00 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 857.51 | 16.88 | 37.67 | 131.67 | 445.22 | 18.66 | 0.00 | 63.67 | |
Maximum of Months | 429.00 | 0.55 | 0.48 | 3125.35 | 21.04 | 101.83 | 414.17 | 1529.30 | 22.31 | 74.67 | 376.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 72914705.95 | 25237.86 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72914705.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72914705.95 | 25237.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.559744E+10 | 9940.50 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417404E+10 | 9940.50 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.522908E+10 | 9940.50 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197244E+10 | 9940.50 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.191052E+10 | 9940.50 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102977E+10 | 9940.50 | 01-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.473718E+09 | 9940.50 | 03-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.452690E+09 | 9940.50 | 02-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.731773E+09 | 9940.50 | 05-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234413E+10 | 9940.50 | 02-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.403202E+10 | 9940.50 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.567378E+10 | 9940.50 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.452690E+09 | 9940.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.567378E+10 | 9940.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128029E+10 | 6600.71 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744088E+09 | 6600.71 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.640682E+09 | 6600.71 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12649117.02 | 6600.71 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2003.64 | 20.04 | 17-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94648818.17 | 6600.71 | 17-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.459100E+09 | 6600.71 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125557E+10 | 6600.71 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128029E+10 | 6600.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217521E+10 | 6251.68 | 02-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132928E+10 | 6225.72 | 08-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102942E+10 | 6227.75 | 09-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88246698.74 | 6210.48 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 438951.06 | 1240.48 | 17-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157277E+09 | 6226.74 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753045E+09 | 6229.38 | 08-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196362E+10 | 6216.27 | 06-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.749654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.217521E+10 | 6251.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147050E+10 | 6572.98 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.821537E+09 | 6572.98 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.769774E+09 | 6572.98 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 49016626.69 | 6572.98 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5382823.01 | 3359.63 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144121E+09 | 6572.98 | 17-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.589379E+09 | 6572.98 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153116E+10 | 6572.98 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.538087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153116E+10 | 6572.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.881463E+09 | 24268.57 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160710E+09 | 24268.57 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123933E+09 | 24268.57 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2749936.61 | 9053.39 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122979E+09 | 24268.57 | 13-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.848850E+09 | 24268.57 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.881463E+09 | 24268.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128431E+10 | 9786.29 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.702253E+09 | 9786.29 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.652902E+09 | 9786.29 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42655331.87 | 9786.29 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2301086.16 | 4447.67 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161795E+09 | 9786.29 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.638031E+09 | 9786.29 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164309E+10 | 9786.29 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.512734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164309E+10 | 9786.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132219E+10 | 6465.47 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.786687E+09 | 6465.47 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.612962E+09 | 6465.47 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16857880.76 | 6465.47 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1041494.74 | 1774.77 | 17-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193849E+09 | 6465.47 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.720656E+09 | 6465.47 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151515E+10 | 6465.47 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151515E+10 | 6465.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173079E+10 | 7059.63 | 30-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.965148E+09 | 7058.61 | 22-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.648877E+09 | 7049.43 | 20-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36637934.89 | 7015.58 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166122E+09 | 7019.55 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.780781E+09 | 7051.36 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186923E+10 | 7043.10 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.619758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.186923E+10 | 7059.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.135712E+10 | 6437.77 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.773327E+09 | 6437.77 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.630698E+09 | 6437.77 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43906816.56 | 6437.77 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4364514.85 | 4432.19 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216549E+09 | 6437.77 | 16-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.743505E+09 | 6437.77 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160048E+10 | 6437.77 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160048E+10 | 6437.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.353447E+10 | 29457.05 | 24-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.202520E+10 | 29475.48 | 08-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156073E+10 | 29445.14 | 27-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88611435.97 | 29391.76 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.451160E+09 | 29369.26 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.177292E+10 | 29495.32 | 08-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.404711E+10 | 29402.17 | 12-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.404711E+10 | 29495.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.254906E+10 | 13171.29 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172680E+10 | 13171.29 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170305E+10 | 13171.29 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.280547E+09 | 13171.29 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103916E+09 | 13171.29 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2061328.18 | 4807.45 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26042992.10 | 12404.07 | 21-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.756829E+09 | 13171.29 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173630E+10 | 13171.29 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.317064E+10 | 13171.29 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.317064E+10 | 13171.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.215839E+10 | 8612.94 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145845E+10 | 8612.94 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124402E+10 | 8612.94 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112405E+09 | 8612.94 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22447684.48 | 8612.94 | 17-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8406795.05 | 8612.94 | 21-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.591318E+09 | 8612.94 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144744E+10 | 8612.94 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.246210E+10 | 8612.94 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.950499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.246210E+10 | 8612.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.325342E+10 | 7990.35 | 30-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.222096E+10 | 7980.85 | 08-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174533E+10 | 7975.54 | 20-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.259639E+09 | 7974.59 | 11-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45477284.91 | 7896.30 | 19-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23898768.64 | 7895.74 | 20-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.797290E+09 | 7986.89 | 19-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204014E+10 | 7986.35 | 08-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357822E+10 | 7962.50 | 15-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.357822E+10 | 7990.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.239352E+10 | 8582.93 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162190E+10 | 8582.93 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144730E+10 | 8582.93 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251353E+09 | 8582.93 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86528388.37 | 8582.93 | 05-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1402147.42 | 2861.74 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 477476.57 | 652.90 | 01-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91084.61 | 505.67 | 24-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39268615.75 | 8582.93 | 21-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.766380E+09 | 8582.93 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166783E+10 | 8582.93 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276199E+10 | 8582.93 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 91084.61 | 505.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.276199E+10 | 8582.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.578482E+10 | 16048.50 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.383653E+10 | 13063.09 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.291801E+10 | 9629.43 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.338606E+09 | 7486.09 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 60402062.52 | 4588.18 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 397843.87 | 468.39 | 07-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 184358.50 | 458.62 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.333275E+09 | 4726.54 | 07-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215285E+10 | 10541.14 | 29-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.532998E+10 | 11610.74 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.578482E+10 | 16048.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.689000E+10 | 15670.56 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.509739E+10 | 13789.00 | 17-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.421362E+10 | 10460.46 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.674151E+09 | 8314.41 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.163809E+09 | 5331.25 | 06-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1752162.00 | 1015.48 | 07-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 23252139.21 | 3269.45 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.749676E+09 | 6134.93 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.335598E+10 | 11301.26 | 29-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.664915E+10 | 12514.56 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.278188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.689000E+10 | 15670.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.730084E+10 | 17215.74 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.537162E+10 | 16044.54 | 17-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.447395E+10 | 12496.00 | 08-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.952894E+09 | 10891.14 | 08-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.344701E+09 | 7186.01 | 06-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8491407.67 | 2432.96 | 08-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 483605.60 | 817.34 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72425702.90 | 5066.95 | 21-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111855E+10 | 7816.27 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.377181E+10 | 13185.82 | 29-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.710867E+10 | 14263.09 | 27-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.730084E+10 | 17215.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.145744E+10 | 0.137963E+10 | 22414.54 | 28-APR-15:20 | 22414.54 | 0.00 |
May | 0.00 | 0.00 | 0.236826E+10 | 0.200455E+10 | 37945.30 | 22-MAY-15:10 | 37945.30 | 0.00 |
June | 0.00 | 0.00 | 0.819228E+10 | 0.677310E+10 | 56899.14 | 13-JUN-16:00 | 51727.21 | 0.00 |
July | 0.00 | 0.00 | 0.138704E+11 | 0.112450E+11 | 52994.31 | 21-JUL-16:00 | 52994.31 | 0.00 |
August | 0.00 | 0.00 | 0.179454E+11 | 0.141279E+11 | 51745.81 | 14-AUG-15:50 | 50630.21 | 0.00 |
September | 0.00 | 0.00 | 0.894291E+10 | 0.734793E+10 | 43944.24 | 13-SEP-15:30 | 39984.18 | 0.00 |
October | 0.00 | 0.00 | 0.301617E+09 | 0.286731E+09 | 8801.15 | 07-OCT-15:00 | 8801.15 | 0.00 |
November | 0.00 | 0.00 | 3123919.91 | 2141851.30 | 2325.27 | 24-NOV-12:00 | 1625.30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.530814E+11 | 0.431671E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.179454E+11 | 0.141279E+11 | 56899.14 | 52994.31 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.154594E+10 | 0.149612E+10 | 33435.52 | 30-APR-16:12 | 33435.52 | 0.00 |
May | 0.00 | 0.00 | 0.233469E+10 | 0.200194E+10 | 37159.07 | 22-MAY-15:00 | 37159.07 | 0.00 |
June | 0.00 | 0.00 | 0.788224E+10 | 0.654491E+10 | 53990.96 | 13-JUN-15:30 | 48728.53 | 0.00 |
July | 0.00 | 0.00 | 0.131745E+11 | 0.107253E+11 | 48699.74 | 21-JUL-15:40 | 48699.74 | 0.00 |
August | 0.00 | 0.00 | 0.164400E+11 | 0.130090E+11 | 47896.41 | 14-AUG-15:30 | 46299.35 | 0.00 |
September | 0.00 | 0.00 | 0.824656E+10 | 0.678102E+10 | 40348.55 | 13-SEP-14:50 | 36649.49 | 0.00 |
October | 0.00 | 0.00 | 0.283178E+09 | 0.270699E+09 | 9839.41 | 07-OCT-15:00 | 9839.41 | 0.00 |
November | 0.00 | 0.00 | 3142264.78 | 2181662.52 | 2267.67 | 24-NOV-12:00 | 1608.87 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.499103E+11 | 0.408312E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.164400E+11 | 0.130090E+11 | 53990.96 | 48728.53 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.158367E+10 | 0.151904E+10 | 42221.93 | 30-APR-15:22 | 42221.93 | 0.00 |
May | 0.00 | 0.00 | 0.241670E+10 | 0.205291E+10 | 40846.45 | 22-MAY-15:00 | 40846.45 | 0.00 |
June | 0.00 | 0.00 | 0.820481E+10 | 0.678305E+10 | 62776.84 | 13-JUN-14:40 | 55344.90 | 0.00 |
July | 0.00 | 0.00 | 0.135442E+11 | 0.110139E+11 | 57005.92 | 21-JUL-15:40 | 57005.92 | 0.00 |
August | 0.00 | 0.00 | 0.162737E+11 | 0.127273E+11 | 53173.56 | 14-AUG-15:50 | 53173.56 | 0.00 |
September | 0.00 | 0.00 | 0.784204E+10 | 0.637490E+10 | 40923.78 | 13-SEP-15:20 | 37402.88 | 0.00 |
October | 0.00 | 0.00 | 0.255554E+09 | 0.240651E+09 | 9615.21 | 07-OCT-15:00 | 9615.21 | 0.00 |
November | 0.00 | 0.00 | 3087308.20 | 2115878.55 | 2305.88 | 24-NOV-12:00 | 1612.10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.501237E+11 | 0.407138E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.162737E+11 | 0.127273E+11 | 62776.84 | 57005.92 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1870.20 | 6517.66 | 31-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1892.38 | 6541.98 | 16-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2003.70 | 6516.42 | 08-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1837.89 | 6405.19 | 07-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1857.37 | 6291.83 | 02-MAY-11:09 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1856.55 | 6103.87 | 02-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1669.52 | 5966.32 | 03-JUL-11:09 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1822.30 | 5879.81 | 01-AUG-11:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1714.08 | 5956.86 | 26-SEP-11:09 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1746.62 | 6117.16 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1819.29 | 6290.76 | 30-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1789.39 | 6430.09 | 28-DEC-12:06 |
Annual Sum or Average | 0.00 | 1822.89 | ||||
Minimum of Months | 0.00 | 0.00 | 1669.52 | 5879.81 | ||
Maximum of Months | 0.00 | 0.00 | 2003.70 | 6541.98 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.127248E+10 | 0.27 | 2450.43 | 02-JAN-06:01 | 0.77 |
February | 0.117805E+10 | 0.28 | 1485.95 | 01-FEB-07:01 | 0.60 |
March | 0.142094E+10 | 0.30 | 1672.53 | 31-MAR-07:09 | 0.64 |
April | 0.189552E+10 | 0.32 | 4340.97 | 28-APR-15:30 | 1.07 |
May | 0.234446E+10 | 0.35 | 4407.52 | 22-MAY-15:10 | 1.08 |
June | 0.293927E+10 | 0.40 | 6504.93 | 13-JUN-16:00 | 1.36 |
July | 0.322031E+10 | 0.40 | 6511.55 | 21-JUL-16:00 | 1.37 |
August | 0.350475E+10 | 0.43 | 6415.06 | 14-AUG-15:50 | 1.35 |
September | 0.282360E+10 | 0.38 | 5997.06 | 13-SEP-15:10 | 1.30 |
October | 0.171823E+10 | 0.30 | 4160.48 | 02-OCT-05:02 | 1.04 |
November | 0.130584E+10 | 0.27 | 1520.89 | 17-NOV-08:09 | 0.61 |
December | 0.123738E+10 | 0.27 | 1485.95 | 01-DEC-07:01 | 0.60 |
Annual Sum or Average | 0.248608E+11 | 0.33 | |||
Minimum of Months | 0.117805E+10 | 0.27 | 1485.95 | 0.60 | |
Maximum of Months | 0.350475E+10 | 0.43 | 6511.55 | 1.37 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132739E+10 | 0.29 | 2564.40 | 02-JAN-06:01 | 0.87 |
February | 0.122644E+10 | 0.30 | 2564.40 | 01-FEB-07:01 | 0.87 |
March | 0.141148E+10 | 0.31 | 2564.40 | 06-MAR-07:01 | 0.87 |
April | 0.183521E+10 | 0.34 | 5383.34 | 28-APR-15:20 | 1.35 |
May | 0.216952E+10 | 0.37 | 5253.72 | 23-MAY-15:20 | 1.33 |
June | 0.278249E+10 | 0.43 | 7003.18 | 13-JUN-15:30 | 1.59 |
July | 0.314120E+10 | 0.44 | 6733.61 | 24-JUL-15:30 | 1.55 |
August | 0.333188E+10 | 0.46 | 6560.08 | 14-AUG-15:30 | 1.52 |
September | 0.255761E+10 | 0.40 | 6194.76 | 12-SEP-14:50 | 1.47 |
October | 0.153407E+10 | 0.31 | 3191.36 | 03-OCT-14:40 | 0.99 |
November | 0.128193E+10 | 0.29 | 2564.40 | 20-NOV-07:01 | 0.87 |
December | 0.130048E+10 | 0.29 | 2564.40 | 01-DEC-07:01 | 0.87 |
Annual Sum or Average | 0.238997E+11 | 0.35 | |||
Minimum of Months | 0.122644E+10 | 0.29 | 2564.40 | 0.87 | |
Maximum of Months | 0.333188E+10 | 0.46 | 7003.18 | 1.59 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136381E+10 | 0.29 | 2344.20 | 02-JAN-05:01 | 0.76 |
February | 0.119998E+10 | 0.28 | 2344.20 | 01-FEB-07:01 | 0.76 |
March | 0.138063E+10 | 0.29 | 2344.20 | 01-MAR-07:01 | 0.76 |
April | 0.165281E+10 | 0.31 | 5043.25 | 28-APR-15:20 | 1.18 |
May | 0.192272E+10 | 0.33 | 5118.44 | 23-MAY-15:20 | 1.18 |
June | 0.243278E+10 | 0.37 | 7087.79 | 13-JUN-15:30 | 1.45 |
July | 0.273137E+10 | 0.37 | 6649.39 | 21-JUL-15:40 | 1.39 |
August | 0.279613E+10 | 0.39 | 6303.45 | 14-AUG-15:30 | 1.35 |
September | 0.208845E+10 | 0.34 | 5385.32 | 12-SEP-15:20 | 1.22 |
October | 0.139325E+10 | 0.28 | 2344.20 | 19-OCT-06:01 | 0.76 |
November | 0.125265E+10 | 0.27 | 2344.20 | 01-NOV-06:01 | 0.76 |
December | 0.130061E+10 | 0.27 | 2344.20 | 01-DEC-07:01 | 0.76 |
Annual Sum or Average | 0.215152E+11 | 0.32 | |||
Minimum of Months | 0.119998E+10 | 0.27 | 2344.20 | 0.76 | |
Maximum of Months | 0.279613E+10 | 0.39 | 7087.79 | 1.45 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:10 | 0.22 | 0.22 | 57.61 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:02 | 0.22 | 0.22 | 56.19 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:02 | 0.22 | 0.22 | 56.26 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:02 | 0.22 | 0.22 | 56.48 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:02 | 0.22 | 0.22 | 56.46 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.46 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:05 | 0.22 | 0.22 | 56.55 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 55.89 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 55.71 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 56.42 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 56.46 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 55.86 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.71 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.61 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.66 | 56.66 | 1870.20 | 6517.66 | 31-JAN-12:13 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.68 | 56.68 | 1892.38 | 6541.98 | 16-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.10 | 57.10 | 2003.70 | 6516.42 | 08-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.20 | 57.20 | 1837.89 | 6405.19 | 07-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.97 | 56.97 | 1857.37 | 6291.83 | 02-MAY-11:09 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.92 | 56.92 | 1856.55 | 6103.87 | 02-JUN-11:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.11 | 57.11 | 1669.52 | 5966.32 | 03-JUL-11:09 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.31 | 56.31 | 1822.30 | 5879.81 | 01-AUG-11:08 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.13 | 56.13 | 1714.08 | 5956.86 | 26-SEP-11:09 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.77 | 55.77 | 1746.62 | 6117.16 | 31-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.33 | 57.33 | 1819.29 | 6290.76 | 30-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.28 | 56.28 | 1789.39 | 6430.09 | 28-DEC-12:06 |
Annual Sum or Average | 0.00 | 1822.89 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.77 | 55.77 | 1669.52 | 5879.81 | ||
Maximum of Months | 0.00 | 0.00 | 57.33 | 57.33 | 2003.70 | 6541.98 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.118688E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.824700E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.908990E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.438293E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.482462E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.587164E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.697910E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.819749E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.565868E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.453919E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.714025E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.116615E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.884611E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.438293E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.118688E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.790327E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.461457E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.408085E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.231993E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.267933E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.444344E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.596653E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.685418E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.431875E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.234388E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.428867E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.877728E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.585907E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.231993E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.877728E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.152527E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.102533E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.908106E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.303617E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.275584E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.434327E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.594463E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.666985E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.404737E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.482495E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.991815E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.173207E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.934479E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.275584E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.173207E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.127248E+10 | 0.00 | 0.163812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117805E+10 | 0.00 | 0.109055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142094E+10 | 0.00 | 0.105870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189552E+10 | 0.145744E+10 | 0.246096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234446E+10 | 0.236826E+10 | 0.197675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.293927E+10 | 0.819228E+10 | 0.103017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.322031E+10 | 0.138704E+11 | 0.473718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350475E+10 | 0.179454E+11 | 0.452690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.282360E+10 | 0.894291E+10 | 0.731957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171823E+10 | 0.301617E+09 | 0.307346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130584E+10 | 3123919.91 | 0.798639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123738E+10 | 0.00 | 0.157541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248608E+11 | 0.530814E+11 | 0.718138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117805E+10 | 0.00 | 0.452690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350475E+10 | 0.179454E+11 | 0.163812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132739E+10 | 0.00 | 0.134659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122644E+10 | 0.00 | 0.848552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141148E+10 | 0.00 | 0.688299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183521E+10 | 0.154594E+10 | 0.814209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.216952E+10 | 0.233469E+10 | 0.171516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.278249E+10 | 0.788224E+10 | 1752162.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.314120E+10 | 0.131745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.333188E+10 | 0.164400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.255761E+10 | 0.824656E+10 | 23252139.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153407E+10 | 0.283178E+09 | 0.149074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128193E+10 | 3142264.78 | 0.636193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130048E+10 | 0.00 | 0.141260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238997E+11 | 0.499103E+11 | 0.518237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.333188E+10 | 0.164400E+11 | 0.141260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136381E+10 | 0.00 | 0.211897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119998E+10 | 0.00 | 0.144249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138063E+10 | 0.00 | 0.121744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165281E+10 | 0.158367E+10 | 0.194545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192272E+10 | 0.241670E+10 | 0.603070E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.243278E+10 | 0.820481E+10 | 11954883.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.273137E+10 | 0.135442E+11 | 477476.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.279613E+10 | 0.162737E+11 | 574690.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208845E+10 | 0.784204E+10 | 0.170043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139325E+10 | 0.255554E+09 | 0.448153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125265E+10 | 3087308.20 | 0.124364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130061E+10 | 0.00 | 0.231287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215152E+11 | 0.501237E+11 | 0.905673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119998E+10 | 0.00 | 477476.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.279613E+10 | 0.162737E+11 | 0.231287E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.127248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189552E+10 | 0.00 | 0.00 | 0.00 | 0.365058E+09 | 0.212235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.234446E+10 | 0.00 | 0.00 | 0.00 | 0.563812E+09 | 0.191635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.293927E+10 | 0.00 | 0.00 | 0.00 | 0.190259E+10 | 0.102977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.322031E+10 | 0.00 | 0.00 | 0.00 | 0.328507E+10 | 0.473718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350475E+10 | 0.00 | 0.00 | 0.00 | 0.424005E+10 | 0.452690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.282360E+10 | 0.00 | 0.00 | 0.00 | 0.210331E+10 | 0.731773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171823E+10 | 0.00 | 0.00 | 0.00 | 80778555.25 | 0.274018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130584E+10 | 0.00 | 0.00 | 0.00 | 865012.61 | 0.583354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248608E+11 | 0.00 | 0.00 | 0.00 | 0.125415E+11 | 0.510588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350475E+10 | 0.00 | 0.00 | 0.00 | 0.424005E+10 | 0.105964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183521E+10 | 0.00 | 0.00 | 0.00 | 0.344660E+09 | 0.140058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.216952E+10 | 0.00 | 0.00 | 0.00 | 0.502097E+09 | 7707095.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.278249E+10 | 0.00 | 0.00 | 0.00 | 0.166094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.314120E+10 | 0.00 | 0.00 | 0.00 | 0.282533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.333188E+10 | 0.00 | 0.00 | 0.00 | 0.352230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.255761E+10 | 0.00 | 0.00 | 0.00 | 0.176113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153407E+10 | 0.00 | 0.00 | 0.00 | 68746470.92 | 0.741065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128193E+10 | 0.00 | 0.00 | 0.00 | 790873.31 | 0.300595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.238997E+11 | 0.00 | 0.00 | 0.00 | 0.106860E+11 | 0.240050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.333188E+10 | 0.00 | 0.00 | 0.00 | 0.352230E+10 | 0.747680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165281E+10 | 0.00 | 0.00 | 0.00 | 0.390802E+09 | 0.992555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.192272E+10 | 0.00 | 0.00 | 0.00 | 0.574758E+09 | 0.258369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.243278E+10 | 0.00 | 0.00 | 0.00 | 0.190702E+10 | 3463475.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.273137E+10 | 0.00 | 0.00 | 0.00 | 0.321278E+10 | 477476.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.279613E+10 | 0.00 | 0.00 | 0.00 | 0.387363E+10 | 91084.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.208845E+10 | 0.00 | 0.00 | 0.00 | 0.186130E+10 | 97617171.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139325E+10 | 0.00 | 0.00 | 0.00 | 68720467.00 | 0.336298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.125265E+10 | 0.00 | 0.00 | 0.00 | 854830.40 | 0.866464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.215152E+11 | 0.00 | 0.00 | 0.00 | 0.118899E+11 | 0.600428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91084.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.279613E+10 | 0.00 | 0.00 | 0.00 | 0.387363E+10 | 0.160201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.808762E+10 | 0.00 | 0.00 | 8588176.69 | 0.00 | 47137108.54 | 0.546118E+10 | 0.00 | 0.29 |
February | 0.575905E+10 | 0.00 | 0.00 | 14057926.74 | 0.00 | 0.00 | 0.675667E+10 | 0.00 | 0.30 |
March | 0.601847E+10 | 0.00 | 0.00 | 17104031.92 | 0.00 | 0.00 | 0.851402E+10 | 0.00 | 0.34 |
April | 0.215844E+10 | 0.00 | 0.00 | 32380698.27 | 0.00 | 0.00 | 0.163371E+11 | 0.00 | 0.59 |
May | 0.129776E+10 | 0.00 | 0.00 | 40034603.92 | 0.00 | 0.00 | 0.203859E+11 | 0.00 | 0.69 |
June | 0.142464E+10 | 14417075.15 | 0.00 | 42922036.09 | 34850560.37 | 0.00 | 0.209163E+11 | 0.00 | 0.97 |
July | 0.155662E+10 | 15155513.16 | 0.00 | 41493350.84 | 5264636.65 | 0.00 | 0.178138E+11 | 0.00 | 1.00 |
August | 0.154719E+10 | 0.00 | 0.00 | 45049406.64 | 0.00 | 0.00 | 0.174866E+11 | 0.00 | 1.14 |
September | 0.150855E+10 | 0.00 | 0.00 | 40485087.29 | 1054663.10 | 0.00 | 0.181047E+11 | 0.00 | 0.94 |
October | 0.342067E+10 | 0.00 | 0.00 | 27375724.04 | 0.00 | 0.00 | 0.137308E+11 | 0.00 | 0.52 |
November | 0.513428E+10 | 0.00 | 0.00 | 16528508.05 | 0.00 | 0.00 | 0.819389E+10 | 0.00 | 0.34 |
December | 0.721553E+10 | 0.00 | 0.00 | 8537928.70 | 0.00 | 0.00 | 0.574332E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.451288E+11 | 29572588.30 | 0.00 | 0.334557E+09 | 41169860.12 | 47137108.54 | 0.159444E+12 | 0.00 | 0.62 |
Minimum of Months | 0.129776E+10 | 0.00 | 0.00 | 8537928.70 | 0.00 | 0.00 | 0.546118E+10 | 0.00 | 0.28 |
Maximum of Months | 0.808762E+10 | 15155513.16 | 0.00 | 45049406.64 | 34850560.37 | 47137108.54 | 0.209163E+11 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501843E+09 | 0.00 | 0.00 | 0.27 |
February | 0.111295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30373516.47 | 0.00 | 0.00 | 0.28 |
March | 0.125987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32314701.96 | 0.00 | 0.00 | 0.30 |
April | 0.695329E+10 | 701639.33 | 0.00 | 7321718.77 | 0.00 | 0.00 | 0.555063E+10 | 0.00 | 0.39 |
May | 0.545766E+10 | 0.00 | 0.00 | 13975652.60 | 0.00 | 0.00 | 0.903024E+10 | 0.00 | 0.46 |
June | 0.316723E+10 | 12102227.89 | 0.00 | 20695656.43 | 31385992.66 | 0.00 | 0.117267E+11 | 0.00 | 0.64 |
July | 0.258606E+10 | 12689565.75 | 0.00 | 22281408.90 | 6401289.56 | 0.00 | 0.105535E+11 | 0.00 | 0.68 |
August | 0.226487E+10 | 0.00 | 0.00 | 22822584.12 | 0.00 | 0.00 | 0.103384E+11 | 0.00 | 0.75 |
September | 0.420728E+10 | 0.00 | 0.00 | 15904946.00 | 990449.77 | 0.00 | 0.847476E+10 | 0.00 | 0.61 |
October | 0.888167E+10 | 0.00 | 0.00 | 3691273.37 | 0.00 | 699708.78 | 0.262645E+10 | 0.00 | 0.35 |
November | 0.109418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28103622.51 | 0.00 | 0.00 | 0.29 |
December | 0.117514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209648E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.919135E+11 | 25493432.96 | 0.00 | 0.106693E+09 | 38777731.99 | 0.802983E+09 | 0.583007E+11 | 0.00 | 0.44 |
Minimum of Months | 0.226487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.125987E+11 | 12689565.75 | 0.00 | 22822584.12 | 31385992.66 | 0.501843E+09 | 0.117267E+11 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.992025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178302E+10 | 0.00 | 0.00 | 0.27 |
February | 0.976410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733751E+09 | 0.00 | 0.00 | 0.27 |
March | 0.112660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652090E+09 | 0.00 | 0.00 | 0.30 |
April | 0.834408E+10 | 0.00 | 0.00 | 4353896.27 | 2734275.55 | 15332348.69 | 0.401506E+10 | 0.00 | 0.39 |
May | 0.717939E+10 | 0.00 | 0.00 | 9908442.89 | 0.00 | 0.00 | 0.690545E+10 | 0.00 | 0.45 |
June | 0.419206E+10 | 4691282.87 | 0.00 | 17797247.62 | 24341199.96 | 0.00 | 0.104368E+11 | 0.00 | 0.63 |
July | 0.343514E+10 | 8293906.54 | 0.00 | 19851110.61 | 8380706.85 | 0.00 | 0.969049E+10 | 0.00 | 0.67 |
August | 0.347096E+10 | 0.00 | 0.00 | 18485111.82 | 0.00 | 0.00 | 0.884003E+10 | 0.00 | 0.73 |
September | 0.552982E+10 | 0.00 | 0.00 | 10329330.49 | 0.00 | 0.00 | 0.617181E+10 | 0.00 | 0.57 |
October | 0.940673E+10 | 0.00 | 0.00 | 989530.91 | 0.00 | 0.133408E+09 | 0.107267E+10 | 0.00 | 0.34 |
November | 0.957839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581463E+09 | 0.00 | 0.00 | 0.28 |
December | 0.884613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225453E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.909331E+11 | 12985189.41 | 0.00 | 81714670.61 | 35456182.37 | 0.615359E+10 | 0.471323E+11 | 0.00 | 0.43 |
Minimum of Months | 0.343514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.112660E+11 | 8293906.54 | 0.00 | 19851110.61 | 24341199.96 | 0.225453E+10 | 0.104368E+11 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.601970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191811E+10 | 0.00 | 0.00 | 0.27 |
February | 0.885516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135284E+10 | 0.00 | 0.00 | 0.28 |
March | 0.151303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101504E+10 | 0.00 | 0.00 | 0.30 |
April | 0.184781E+10 | 0.00 | 0.00 | 739340.15 | 576864.25 | 0.151360E+09 | 0.615586E+09 | 0.00 | 0.39 |
May | 0.184039E+10 | 0.00 | 0.00 | 1833096.24 | 0.00 | 24940718.73 | 0.115094E+10 | 0.00 | 0.47 |
June | 0.102622E+10 | 1679225.30 | 0.00 | 4324126.86 | 5135388.78 | 0.00 | 0.230198E+10 | 0.00 | 0.71 |
July | 0.831269E+09 | 2817117.74 | 0.00 | 4984397.76 | 1006318.71 | 0.00 | 0.226659E+10 | 0.00 | 0.78 |
August | 0.938516E+09 | 0.00 | 0.00 | 4183352.22 | 0.00 | 0.00 | 0.183892E+10 | 0.00 | 0.79 |
September | 0.150822E+10 | 0.00 | 0.00 | 1618978.79 | 0.00 | 12162092.47 | 0.919093E+09 | 0.00 | 0.57 |
October | 0.170169E+10 | 0.00 | 0.00 | 37089.86 | 0.00 | 0.429564E+09 | 99947560.07 | 0.00 | 0.34 |
November | 0.963617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119841E+10 | 0.00 | 0.00 | 0.28 |
December | 0.362713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202817E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.140210E+11 | 4496343.04 | 0.00 | 17720381.88 | 6718571.74 | 0.813060E+10 | 0.919306E+10 | 0.00 | 0.45 |
Minimum of Months | 0.362713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.184781E+10 | 2817117.74 | 0.00 | 4984397.76 | 5135388.78 | 0.202817E+10 | 0.230198E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.771341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144662E+10 | 0.00 | 0.00 | 0.38 |
February | 0.964931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101742E+10 | 0.00 | 0.00 | 0.39 |
March | 0.146408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784521E+09 | 0.00 | 0.00 | 0.42 |
April | 0.106005E+10 | 1519918.39 | 0.00 | 3194246.88 | 0.00 | 56054058.75 | 0.185606E+10 | 0.00 | 0.73 |
May | 0.120958E+10 | 0.00 | 0.00 | 3862712.55 | 0.00 | 10430426.81 | 0.216211E+10 | 0.00 | 0.84 |
June | 0.806233E+09 | 1197077.84 | 0.00 | 5604528.18 | 4581174.66 | 0.00 | 0.281234E+10 | 0.00 | 1.23 |
July | 0.605172E+09 | 9864602.12 | 0.00 | 6312664.39 | 361087.98 | 0.00 | 0.273568E+10 | 0.00 | 1.31 |
August | 0.663551E+09 | 0.00 | 0.00 | 6048717.89 | 0.00 | 0.00 | 0.257994E+10 | 0.00 | 1.45 |
September | 0.977872E+09 | 0.00 | 0.00 | 3732116.52 | 0.00 | 2741721.89 | 0.182973E+10 | 0.00 | 1.06 |
October | 0.136184E+10 | 0.00 | 0.00 | 622757.50 | 0.00 | 0.309153E+09 | 0.372857E+09 | 0.00 | 0.49 |
November | 0.100383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914346E+09 | 0.00 | 0.00 | 0.40 |
December | 0.494538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160925E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.113830E+11 | 12581598.35 | 0.00 | 29377743.91 | 4942262.64 | 0.615054E+10 | 0.143487E+11 | 0.00 | 0.76 |
Minimum of Months | 0.494538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.146408E+10 | 9864602.12 | 0.00 | 6312664.39 | 4581174.66 | 0.160925E+10 | 0.281234E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138965E+10 | 0.00 | 0.00 | 795825.23 | 0.00 | 0.165488E+10 | 0.448980E+09 | 0.00 | 0.38 |
February | 0.150664E+10 | 0.00 | 0.00 | 1171530.70 | 0.00 | 0.109929E+10 | 0.663696E+09 | 0.00 | 0.40 |
March | 0.223627E+10 | 0.00 | 0.00 | 168102.05 | 0.00 | 0.104183E+10 | 0.152536E+09 | 0.00 | 0.41 |
April | 0.149535E+10 | 0.00 | 0.00 | 7177058.98 | 783271.87 | 0.170773E+09 | 0.382272E+10 | 0.00 | 0.86 |
May | 0.199991E+10 | 0.00 | 0.00 | 5779147.21 | 0.00 | 45742671.99 | 0.326765E+10 | 0.00 | 0.83 |
June | 0.150750E+10 | 2286632.51 | 0.00 | 7003087.93 | 6972880.66 | 361957.17 | 0.358717E+10 | 0.00 | 1.10 |
July | 0.111699E+10 | 1725893.49 | 0.00 | 8839167.28 | 3712550.22 | 0.00 | 0.377481E+10 | 0.00 | 1.23 |
August | 0.107716E+10 | 0.00 | 0.00 | 10404649.54 | 0.00 | 0.00 | 0.416570E+10 | 0.00 | 1.53 |
September | 0.130386E+10 | 0.00 | 0.00 | 9742473.95 | 0.00 | 7696527.01 | 0.433796E+10 | 0.00 | 1.39 |
October | 0.171919E+10 | 0.00 | 0.00 | 4018232.56 | 0.00 | 0.396880E+09 | 0.218329E+10 | 0.00 | 0.67 |
November | 0.162986E+10 | 0.00 | 0.00 | 656103.47 | 0.00 | 0.103707E+10 | 0.372802E+09 | 0.00 | 0.40 |
December | 0.102149E+10 | 0.00 | 0.00 | 352055.53 | 0.00 | 0.204687E+10 | 0.162205E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.180039E+11 | 4012525.99 | 0.00 | 56107434.44 | 11468702.74 | 0.750139E+10 | 0.269395E+11 | 0.00 | 0.80 |
Minimum of Months | 0.102149E+10 | 0.00 | 0.00 | 168102.05 | 0.00 | 0.00 | 0.152536E+09 | 0.00 | 0.37 |
Maximum of Months | 0.223627E+10 | 2286632.51 | 0.00 | 10404649.54 | 6972880.66 | 0.204687E+10 | 0.433796E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.806933E+09 | 0.00 | 0.00 | 19.92 | 0.00 | 0.167858E+10 | 1066866.68 | 0.00 | 0.43 |
February | 0.102840E+10 | 0.00 | 0.00 | 64384.48 | 0.00 | 0.112162E+10 | 78508897.29 | 0.00 | 0.43 |
March | 0.157329E+10 | 0.00 | 0.00 | 52870.98 | 0.00 | 0.911382E+09 | 44457910.07 | 0.00 | 0.47 |
April | 0.157231E+10 | 0.00 | 0.00 | 3084176.24 | 578433.30 | 0.148632E+09 | 0.156075E+10 | 0.00 | 0.80 |
May | 0.165585E+10 | 0.00 | 0.00 | 3730614.46 | 0.00 | 37343987.64 | 0.204242E+10 | 0.00 | 0.93 |
June | 0.112903E+10 | 12104972.23 | 0.00 | 5638510.50 | 857168.73 | 267299.38 | 0.272223E+10 | 0.00 | 1.33 |
July | 0.825003E+09 | 1169646.58 | 0.00 | 6925217.16 | 2793234.52 | 0.00 | 0.271992E+10 | 0.00 | 1.43 |
August | 0.926158E+09 | 0.00 | 0.00 | 5635252.00 | 0.00 | 0.00 | 0.221576E+10 | 0.00 | 1.42 |
September | 0.143018E+10 | 0.00 | 0.00 | 2907738.17 | 0.00 | 14320160.17 | 0.139298E+10 | 0.00 | 1.08 |
October | 0.157913E+10 | 0.00 | 0.00 | 707235.34 | 0.00 | 0.400584E+09 | 0.414954E+09 | 0.00 | 0.58 |
November | 0.105915E+10 | 0.00 | 0.00 | 1075.74 | 0.00 | 0.108654E+10 | 8498143.28 | 0.00 | 0.44 |
December | 0.449604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190956E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.140350E+11 | 13274618.81 | 0.00 | 28747094.98 | 4228836.55 | 0.730883E+10 | 0.132015E+11 | 0.00 | 0.82 |
Minimum of Months | 0.449604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.165585E+10 | 12104972.23 | 0.00 | 6925217.16 | 2793234.52 | 0.190956E+10 | 0.272223E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.927159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185009E+10 | 0.00 | 0.00 | 0.28 |
February | 0.124702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121391E+10 | 0.00 | 0.00 | 0.28 |
March | 0.198733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779171E+09 | 0.00 | 0.00 | 0.31 |
April | 0.240511E+10 | 0.00 | 0.00 | 78482.85 | 0.00 | 53213424.14 | 0.117768E+09 | 0.00 | 0.38 |
May | 0.225174E+10 | 0.00 | 0.00 | 611464.54 | 0.00 | 189936.82 | 0.506274E+09 | 0.00 | 0.41 |
June | 0.129718E+10 | 2447442.68 | 0.00 | 2521167.17 | 7340150.60 | 0.00 | 0.149791E+10 | 0.00 | 0.59 |
July | 0.963411E+09 | 2681055.21 | 0.00 | 3638630.56 | 931179.37 | 0.00 | 0.162092E+10 | 0.00 | 0.65 |
August | 0.113921E+10 | 0.00 | 0.00 | 2910978.32 | 0.00 | 0.00 | 0.127786E+10 | 0.00 | 0.68 |
September | 0.170915E+10 | 0.00 | 0.00 | 1120096.92 | 222130.89 | 0.00 | 0.719264E+09 | 0.00 | 0.54 |
October | 0.246291E+10 | 0.00 | 0.00 | 3824.95 | 0.00 | 58522636.33 | 26212482.66 | 0.00 | 0.36 |
November | 0.190694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539276E+09 | 0.00 | 0.00 | 0.29 |
December | 0.981218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168735E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.192784E+11 | 5128497.89 | 0.00 | 10884645.30 | 8493460.87 | 0.618172E+10 | 0.576620E+10 | 0.00 | 0.42 |
Minimum of Months | 0.927159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.246291E+10 | 2681055.21 | 0.00 | 3638630.56 | 7340150.60 | 0.185009E+10 | 0.162092E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.898532E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112086E+10 | 0.00 | 0.00 | 0.32 |
February | 0.108732E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704805E+09 | 0.00 | 0.00 | 0.32 |
March | 0.152231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492046E+09 | 0.00 | 0.00 | 0.35 |
April | 0.954427E+09 | 0.00 | 0.00 | 2610249.10 | 0.00 | 2231880.01 | 0.146490E+10 | 0.00 | 0.59 |
May | 0.911283E+09 | 0.00 | 0.00 | 3396969.53 | 0.00 | 0.00 | 0.184957E+10 | 0.00 | 0.69 |
June | 0.566236E+09 | 2412485.77 | 0.00 | 4787181.63 | 5333096.89 | 0.00 | 0.234422E+10 | 0.00 | 1.02 |
July | 0.434489E+09 | 5733542.58 | 0.00 | 5551439.78 | 501289.89 | 0.00 | 0.235565E+10 | 0.00 | 1.11 |
August | 0.438660E+09 | 0.00 | 0.00 | 5771055.95 | 0.00 | 0.00 | 0.234686E+10 | 0.00 | 1.27 |
September | 0.715744E+09 | 0.00 | 0.00 | 4108014.36 | 161392.54 | 0.00 | 0.192637E+10 | 0.00 | 0.98 |
October | 0.147880E+10 | 0.00 | 0.00 | 799550.88 | 0.00 | 37228075.85 | 0.468605E+09 | 0.00 | 0.45 |
November | 0.146847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312134E+09 | 0.00 | 0.00 | 0.33 |
December | 0.890819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105311E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.113671E+11 | 8146028.35 | 0.00 | 27024461.23 | 5995779.32 | 0.372241E+10 | 0.127562E+11 | 0.00 | 0.65 |
Minimum of Months | 0.434489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.152231E+10 | 5733542.58 | 0.00 | 5771055.95 | 5333096.89 | 0.112086E+10 | 0.235565E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.713822E+09 | 0.00 | 0.00 | 40481.39 | 0.00 | 0.328966E+10 | 41136597.58 | 0.00 | 0.40 |
February | 0.101172E+10 | 0.00 | 0.00 | 60680.04 | 0.00 | 0.239789E+10 | 35919906.13 | 0.00 | 0.39 |
March | 0.864892E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303276E+10 | 0.00 | 0.00 | 0.43 |
April | 0.171253E+10 | 0.00 | 0.00 | 1524244.99 | 0.00 | 0.106035E+10 | 0.793966E+09 | 0.00 | 0.55 |
May | 0.204439E+10 | 0.00 | 0.00 | 971911.31 | 0.00 | 0.965759E+09 | 0.615457E+09 | 0.00 | 0.55 |
June | 0.200995E+10 | 4486930.59 | 0.00 | 1633721.24 | 8102736.88 | 0.502403E+09 | 0.721759E+09 | 0.00 | 0.70 |
July | 0.147587E+10 | 4853251.90 | 0.00 | 3126364.81 | 719790.41 | 0.219678E+09 | 0.131853E+10 | 0.00 | 0.78 |
August | 0.112750E+10 | 0.00 | 0.00 | 5223754.99 | 0.00 | 0.195543E+09 | 0.205335E+10 | 0.00 | 1.02 |
September | 0.125051E+10 | 315879.86 | 0.00 | 5229006.37 | 22723.58 | 0.361235E+09 | 0.235789E+10 | 0.00 | 0.99 |
October | 0.155824E+10 | 0.00 | 0.00 | 1436593.53 | 0.00 | 0.124984E+10 | 0.961917E+09 | 0.00 | 0.54 |
November | 0.109102E+10 | 0.00 | 0.00 | 18389.42 | 0.00 | 0.230770E+10 | 15751504.82 | 0.00 | 0.40 |
December | 0.373275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344697E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.152337E+11 | 9656062.34 | 0.00 | 19265148.09 | 8845250.87 | 0.190298E+11 | 0.891568E+10 | 0.00 | 0.60 |
Minimum of Months | 0.373275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195543E+09 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.204439E+10 | 4853251.90 | 0.00 | 5229006.37 | 8102736.88 | 0.344697E+10 | 0.235789E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.998769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129812E+10 | 0.00 | 0.00 | 0.37 |
February | 0.128314E+10 | 0.00 | 0.00 | 13396.67 | 0.00 | 0.728062E+09 | 27827258.59 | 0.00 | 0.37 |
March | 0.170641E+10 | 0.00 | 0.00 | 7161.55 | 0.00 | 0.577330E+09 | 8967995.55 | 0.00 | 0.40 |
April | 0.153679E+10 | 0.00 | 0.00 | 1805121.43 | 0.00 | 29633736.00 | 0.889156E+09 | 0.00 | 0.60 |
May | 0.134764E+10 | 0.00 | 0.00 | 2827288.45 | 0.00 | 961718.28 | 0.152193E+10 | 0.00 | 0.73 |
June | 0.783640E+09 | 11416869.81 | 0.00 | 4478720.65 | 2017012.58 | 0.00 | 0.220345E+10 | 0.00 | 1.06 |
July | 0.602315E+09 | 3723246.30 | 0.00 | 5718191.40 | 302563.91 | 0.00 | 0.226456E+10 | 0.00 | 1.19 |
August | 0.603682E+09 | 0.00 | 0.00 | 4899249.75 | 0.00 | 0.00 | 0.192679E+10 | 0.00 | 1.17 |
September | 0.108203E+10 | 32930.61 | 0.00 | 2699857.04 | 150820.49 | 0.00 | 0.130790E+10 | 0.00 | 0.90 |
October | 0.182877E+10 | 0.00 | 0.00 | 616515.61 | 0.00 | 56603772.81 | 0.344363E+09 | 0.00 | 0.50 |
November | 0.160452E+10 | 0.00 | 0.00 | 298.68 | 0.00 | 0.417228E+09 | 4967550.72 | 0.00 | 0.38 |
December | 0.808358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140408E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.141860E+11 | 15173046.72 | 0.00 | 23065801.24 | 2470396.98 | 0.451202E+10 | 0.104999E+11 | 0.00 | 0.67 |
Minimum of Months | 0.602315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.182877E+10 | 11416869.81 | 0.00 | 5718191.40 | 2017012.58 | 0.140408E+10 | 0.226456E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145492E+10 | 0.00 | 0.00 | 0.28 |
February | 0.151429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843571E+09 | 0.00 | 0.00 | 0.28 |
March | 0.219193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475390E+09 | 0.00 | 0.00 | 0.30 |
April | 0.182418E+10 | 0.00 | 0.00 | 997174.19 | 119917.49 | 18110265.79 | 0.779166E+09 | 0.00 | 0.39 |
May | 0.157348E+10 | 0.00 | 0.00 | 2364928.12 | 0.00 | 0.00 | 0.147691E+10 | 0.00 | 0.47 |
June | 0.750484E+09 | 4382809.79 | 0.00 | 4971479.82 | 6617547.28 | 0.00 | 0.259080E+10 | 0.00 | 0.72 |
July | 0.708769E+09 | 4580104.63 | 0.00 | 5366940.88 | 943670.81 | 0.00 | 0.234334E+10 | 0.00 | 0.78 |
August | 0.788860E+09 | 0.00 | 0.00 | 4837976.51 | 0.00 | 0.00 | 0.197288E+10 | 0.00 | 0.81 |
September | 0.138774E+10 | 0.00 | 0.00 | 2335837.58 | 208830.36 | 0.00 | 0.116879E+10 | 0.00 | 0.59 |
October | 0.213538E+10 | 0.00 | 0.00 | 157792.54 | 0.00 | 75603771.01 | 0.163724E+09 | 0.00 | 0.34 |
November | 0.176741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.549485E+09 | 0.00 | 0.00 | 0.29 |
December | 0.103226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150097E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.168667E+11 | 8962914.42 | 0.00 | 21032129.64 | 7889965.94 | 0.491805E+10 | 0.104956E+11 | 0.00 | 0.46 |
Minimum of Months | 0.708769E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.219193E+10 | 4580104.63 | 0.00 | 5366940.88 | 6617547.28 | 0.150097E+10 | 0.259080E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119753E+10 | 0.00 | 0.00 | 0.40 |
February | 0.149065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697991E+09 | 0.00 | 0.00 | 0.41 |
March | 0.206999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406274E+09 | 0.00 | 0.00 | 0.44 |
April | 0.111696E+10 | 413043.30 | 0.00 | 3671297.38 | 0.00 | 3377543.84 | 0.203097E+10 | 0.00 | 0.77 |
May | 0.117900E+10 | 0.00 | 0.00 | 4332721.02 | 0.00 | 183506.74 | 0.235288E+10 | 0.00 | 0.87 |
June | 0.695680E+09 | 3142540.51 | 0.00 | 5806668.64 | 6137699.75 | 0.00 | 0.290081E+10 | 0.00 | 1.23 |
July | 0.587383E+09 | 8629246.84 | 0.00 | 6515440.47 | 783944.11 | 0.00 | 0.269736E+10 | 0.00 | 1.30 |
August | 0.622009E+09 | 0.00 | 0.00 | 6366823.66 | 0.00 | 0.00 | 0.260747E+10 | 0.00 | 1.46 |
September | 0.101759E+10 | 0.00 | 0.00 | 4292140.37 | 193687.78 | 0.00 | 0.202490E+10 | 0.00 | 1.12 |
October | 0.175360E+10 | 0.00 | 0.00 | 879022.20 | 0.00 | 71683591.24 | 0.501409E+09 | 0.00 | 0.53 |
November | 0.168454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465920E+09 | 0.00 | 0.00 | 0.42 |
December | 0.101832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132989E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.144887E+11 | 12184830.65 | 0.00 | 31864113.73 | 7115331.65 | 0.417285E+10 | 0.151158E+11 | 0.00 | 0.78 |
Minimum of Months | 0.587383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.206999E+10 | 8629246.84 | 0.00 | 6515440.47 | 6137699.75 | 0.132989E+10 | 0.290081E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198562E+10 | 0.00 | 0.00 | 1120750.69 | 0.00 | 0.107323E+10 | 0.597502E+09 | 0.00 | 0.38 |
February | 0.209482E+10 | 0.00 | 0.00 | 1568068.45 | 0.00 | 0.520455E+09 | 0.808548E+09 | 0.00 | 0.41 |
March | 0.288882E+10 | 0.00 | 0.00 | 296238.69 | 0.00 | 0.409916E+09 | 0.208098E+09 | 0.00 | 0.40 |
April | 0.152199E+10 | 156175.34 | 0.00 | 7524007.10 | 0.00 | 18287269.46 | 0.378954E+10 | 0.00 | 0.85 |
May | 0.177190E+10 | 0.00 | 0.00 | 6217049.85 | 0.00 | 727771.97 | 0.337134E+10 | 0.00 | 0.82 |
June | 0.115944E+10 | 6026494.81 | 0.00 | 7352080.46 | 8618407.05 | 0.00 | 0.366363E+10 | 0.00 | 1.07 |
July | 0.946870E+09 | 7808905.74 | 0.00 | 8922519.10 | 1058888.72 | 0.00 | 0.360374E+10 | 0.00 | 1.20 |
August | 0.864170E+09 | 0.00 | 0.00 | 10757386.63 | 0.00 | 0.00 | 0.399187E+10 | 0.00 | 1.50 |
September | 0.123852E+10 | 357965.56 | 0.00 | 10368034.72 | 23092.49 | 0.00 | 0.434128E+10 | 0.00 | 1.42 |
October | 0.204029E+10 | 0.00 | 0.00 | 4734226.07 | 0.00 | 87531719.57 | 0.244187E+10 | 0.00 | 0.70 |
November | 0.224600E+10 | 0.00 | 0.00 | 1013568.57 | 0.00 | 0.440738E+09 | 0.527968E+09 | 0.00 | 0.40 |
December | 0.170917E+10 | 0.00 | 0.00 | 527718.42 | 0.00 | 0.142465E+10 | 0.235914E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.204676E+11 | 14349541.45 | 0.00 | 60401648.76 | 9700388.26 | 0.397553E+10 | 0.275813E+11 | 0.00 | 0.79 |
Minimum of Months | 0.864170E+09 | 0.00 | 0.00 | 296238.69 | 0.00 | 0.00 | 0.208098E+09 | 0.00 | 0.36 |
Maximum of Months | 0.288882E+10 | 7808905.74 | 0.00 | 10757386.63 | 8618407.05 | 0.142465E+10 | 0.434128E+10 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130845E+10 | 0.00 | 0.00 | 3044.36 | 0.00 | 0.122549E+10 | 8038022.60 | 0.00 | 0.42 |
February | 0.158107E+10 | 0.00 | 0.00 | 117425.36 | 0.00 | 0.589447E+09 | 0.107292E+09 | 0.00 | 0.42 |
March | 0.210532E+10 | 0.00 | 0.00 | 82866.96 | 0.00 | 0.408439E+09 | 62303922.91 | 0.00 | 0.46 |
April | 0.160687E+10 | 0.00 | 0.00 | 3102176.79 | 115391.57 | 22259396.78 | 0.150532E+10 | 0.00 | 0.78 |
May | 0.147721E+10 | 0.00 | 0.00 | 4016567.26 | 0.00 | 1221806.40 | 0.211148E+10 | 0.00 | 0.91 |
June | 0.836379E+09 | 18236731.16 | 0.00 | 5860208.87 | 1165259.08 | 0.00 | 0.278776E+10 | 0.00 | 1.28 |
July | 0.685370E+09 | 5858174.15 | 0.00 | 7143740.82 | 519538.94 | 0.00 | 0.260340E+10 | 0.00 | 1.38 |
August | 0.704214E+09 | 0.00 | 0.00 | 6012323.53 | 0.00 | 0.00 | 0.222261E+10 | 0.00 | 1.37 |
September | 0.126862E+10 | 196768.78 | 0.00 | 3302109.08 | 23152.76 | 0.00 | 0.150761E+10 | 0.00 | 1.06 |
October | 0.192389E+10 | 0.00 | 0.00 | 824879.84 | 0.00 | 82817100.79 | 0.468271E+09 | 0.00 | 0.57 |
November | 0.167308E+10 | 0.00 | 0.00 | 15152.66 | 0.00 | 0.527477E+09 | 30290585.73 | 0.00 | 0.43 |
December | 0.987205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144883E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.161577E+11 | 24291674.08 | 0.00 | 30480495.51 | 1823342.36 | 0.430598E+10 | 0.134144E+11 | 0.00 | 0.79 |
Minimum of Months | 0.685370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.210532E+10 | 18236731.16 | 0.00 | 7143740.82 | 1165259.08 | 0.144883E+10 | 0.278776E+10 | 0.00 | 1.38 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.874139E+11 | 0.750900E+10 | 0.00 | 0.153930E+12 | 0.499383E+10 |
February | 0.133682E+12 | 0.690546E+10 | 0.00 | 0.145977E+12 | 0.357638E+10 |
March | 0.154818E+12 | 0.720537E+10 | 0.00 | 0.169116E+12 | 0.290139E+10 |
April | 0.397291E+12 | 0.567081E+10 | 0.00 | 0.217362E+12 | 0.617898E+10 |
May | 0.474014E+12 | 0.700357E+10 | 0.00 | 0.236775E+12 | 0.890254E+10 |
June | 0.474569E+12 | 0.515798E+10 | 0.00 | 0.241312E+12 | 0.297525E+11 |
July | 0.480881E+12 | 0.411253E+10 | 0.00 | 0.242621E+12 | 0.499122E+11 |
August | 0.397863E+12 | 0.375740E+10 | 0.00 | 0.224087E+12 | 0.622953E+11 |
September | 0.302888E+12 | 0.448061E+10 | 0.00 | 0.243025E+12 | 0.307812E+11 |
October | 0.142980E+12 | 0.605161E+10 | 0.00 | 0.190197E+12 | 0.160897E+10 |
November | 0.641086E+11 | 0.730742E+10 | 0.00 | 0.163838E+12 | 0.233202E+10 |
December | 0.330741E+11 | 0.830224E+10 | 0.00 | 0.146865E+12 | 0.477195E+10 |
Annual Sum or Average | 0.314358E+13 | 0.734640E+11 | 0.00 | 0.237511E+13 | 0.208007E+12 |
Minimum of Months | 0.330741E+11 | 0.375740E+10 | 0.00 | 0.145977E+12 | 0.160897E+10 |
Maximum of Months | 0.480881E+12 | 0.830224E+10 | 0.00 | 0.243025E+12 | 0.622953E+11 |