Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 08:35:22
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1666.76 | 334.54 | 334.54 |
Net Site Energy | 1666.76 | 334.54 | 334.54 |
Total Source Energy | 4765.95 | 956.60 | 956.60 |
Net Source Energy | 4765.95 | 956.60 | 956.60 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 154.61 | 138.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 199.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 203.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 96.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1420.64 | 246.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 154.61 | 138.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 199.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 203.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 49.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 96.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 154.61 | 138.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 199.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 203.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 49.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 96.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 90.38 | 49.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 285.14 | 49.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 90.38 | 49.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 285.14 | 49.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1420.637 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1420.637 | 100.00 |
Total On-Site and Utility Electric Sources | 1420.637 | 100.00 |
Total Electricity End Uses | 1420.637 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 364.33 |
Time Setpoint Not Met During Occupied Cooling | 120.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2701.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.9322 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.9322 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.9322 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 06-FEB-07:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 200569.99 | 92566.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7126.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7164.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8164.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 241761.03 | 100730.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 200569.99 | 92566.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 7126.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7164.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8164.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 489.65 | 150.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 631.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 644.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 157.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 304.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 116.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4499.16 | 266.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 98.28 | 30.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 126.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 903.05 | 53.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 98.28 | 30.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 126.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 61.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 23.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 903.05 | 53.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.72 | 0.275911 | 0.282000 | 0.765994 | 0.735763 | 0.500000 | 0.001381 |
CORE_MID VAV BOX COMPONENT | 1.97 | 0.379854 | 0.374000 | 0.737906 | 1.00 | 0.500000 | 0.001003 |
CORE_TOP VAV BOX COMPONENT | 2.11 | 0.354459 | 0.365000 | 0.771743 | 0.945223 | 0.500000 | 0.001075 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.668434 | 0.236361 | 0.244000 | 0.163098 | 0.630295 | 0.500000 | 0.001612 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.728729 | 0.137255 | 0.200000 | 0.145746 | 0.366014 | 0.500000 | 0.002776 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.907874 | 0.174024 | 0.200000 | 0.181575 | 0.464063 | 0.500000 | 0.002189 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.789702 | 0.126649 | 0.200000 | 0.157940 | 0.337732 | 0.500000 | 0.003008 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.527870 | 0.299300 | 0.306000 | 0.161528 | 0.798135 | 0.500000 | 0.001273 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.601613 | 0.166256 | 0.200000 | 0.120323 | 0.443349 | 0.500000 | 0.002292 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.729316 | 0.216630 | 0.222000 | 0.161908 | 0.577680 | 0.500000 | 0.001759 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.617176 | 0.162053 | 0.200000 | 0.123435 | 0.432142 | 0.500000 | 0.002351 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.574767 | 0.274880 | 0.271000 | 0.155762 | 0.733013 | 0.500000 | 0.001386 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.699110 | 0.143070 | 0.200000 | 0.139822 | 0.381521 | 0.500000 | 0.002663 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.809435 | 0.195188 | 0.200000 | 0.161887 | 0.520500 | 0.500000 | 0.001952 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.716360 | 0.139616 | 0.200000 | 0.143272 | 0.372309 | 0.500000 | 0.002729 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25571.27 |
CORE_MID VAV BOX REHEAT COIL | 24633.57 |
CORE_TOP VAV BOX REHEAT COIL | 37500.50 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17464.22 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11333.36 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17315.72 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11423.18 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13002.67 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8508.46 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12882.25 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8586.54 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 13531.99 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 8825.12 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 13401.61 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 8901.61 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.60 | 1.33 | 5.19 | 1.71 | 4.66 | 4.66 | 0.300000 | 0.367392 | 4.66 |
PACU_VAV_MID | 2.39 | 1.34 | 4.77 | 1.99 | 4.09 | 4.09 | 0.300000 | 0.486002 | 4.09 |
PACU_VAV_TOP | 2.60 | 1.42 | 5.21 | 2.85 | 4.79 | 4.79 | 0.300000 | 0.594259 | 4.79 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.66 |
PACU_VAV_MID_OA_CONTROLLER | 4.09 |
PACU_VAV_TOP_OA_CONTROLLER | 4.79 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.66 | 104743.89 | 0.733782 | 1.55 | 34911.14 | 0.733782 |
PACU_VAV_MID COOLING COIL | 4.09 | 95354.13 | 0.721079 | 1.36 | 31781.53 | 0.721079 |
PACU_VAV_TOP COOLING COIL | 4.79 | 106581.75 | 0.736552 | 1.60 | 35523.70 | 0.736552 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 31956.64 |
PACU_VAV_MID HEATING COIL | 33731.10 |
PACU_VAV_TOP HEATING COIL | 32614.53 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.66 |
PACU_VAV_MID FAN | 4.09 |
PACU_VAV_TOP FAN | 4.79 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 30.766 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
66 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
67 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
68 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
69 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
70 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
71 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
72 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
73 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
74 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
75 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
76 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
77 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
78 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
79 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
80 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
81 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
82 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
83 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
84 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
85 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
86 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
87 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
88 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
89 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
90 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
91 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
92 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
93 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
94 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
95 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
96 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3628_SHGC_EAST_0.36 | 35 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 | ||
2 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 36 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 | ||
3 | WINDOW_U_0.3628_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 | ||
4 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 38 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62909E-002 | 0.27318 | 0.51969 | 0.51969 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.215E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.231E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.215E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.231E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.278E-004 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.278E-004 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.480E-005 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.2828E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.3386E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0175E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0224E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5182E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5574E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4493E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4697E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1333 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9495E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1510 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7972E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.7367E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1131E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.0047E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5019E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.2827E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.3409E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0175E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0226E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.5183E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5592E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4490E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4695E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6904E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3586E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2991E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0648E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7194E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8825E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6599E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1796E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1464E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1678E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8288E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8442E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7054E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7107E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0258E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0328E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6021E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6494E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0121E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0497E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6306E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6576E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4490E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4695E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3948E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9984E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6206E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5220E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5234E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0704E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0047E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5019E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6022E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6496E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0121E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0495E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6304E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6563E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4493E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4697E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4403E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2375E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9893E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9143E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5058E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7822E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6599E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1796E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0033E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0647E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6509E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7181E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5852E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.6108E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0259E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0329E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1303 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 8.2511E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1449 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.2006E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1025 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.1280E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.5023E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.0890E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.4717E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2368E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1056E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9578E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.5527E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7926E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.5485E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1197E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8483E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.5809E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0272E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0248E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.9290E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5358E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.5023E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0890E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2314E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1227E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8079E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8160E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.3469E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6974E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5485E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1197E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1303 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 8.2503E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1449 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.1997E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1025 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.1274E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.5020E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.0887E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.4718E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2366E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1056E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9576E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.5524E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7923E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.5481E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1194E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8485E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.5808E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0273E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0248E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.9289E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5356E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.5020E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0887E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2314E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1225E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8079E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8159E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.3467E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6972E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5482E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1195E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37686.22856 | 37686.22856 | 2.71629 | 2.71629 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 7606.10900 | 7606.10900 | 0.31966 | 0.42469 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27409.82248 | 27409.82248 | 1.97301 | 1.97301 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 15351.10246 | 15351.10246 | 0.65019 | 0.65019 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29087.24200 | 29087.24200 | 2.11436 | 2.11436 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 26411.83442 | 26411.83442 | 1.12334 | 1.12334 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9195.34522 | 9195.34522 | 0.66843 | 0.66843 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 12264.57295 | 12264.57295 | 0.52315 | 0.52315 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10024.85289 | 10024.85289 | 0.72873 | 0.72873 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44933 | 1.41131E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 7958.59275 | 7958.59275 | 0.33949 | 0.33949 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12489.25590 | 12489.25590 | 0.90787 | 0.90787 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 12160.56456 | 12160.56456 | 0.51870 | 0.51870 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 10863.65476 | 10863.65476 | 0.78970 | 0.78970 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 8021.49934 | 8021.49934 | 0.34218 | 0.34218 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7261.78195 | 7261.78195 | 0.52787 | 0.52787 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 9138.56750 | 9138.56750 | 0.38950 | 0.38950 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8276.31559 | 8276.31559 | 0.60161 | 0.60161 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 28.65900 | 1.41134E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5979.27328 | 5979.27328 | 0.25487 | 0.25487 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10033.06457 | 10033.06457 | 0.72932 | 0.72932 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 9054.24531 | 9054.24531 | 0.38589 | 0.38589 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8490.41362 | 8490.41362 | 0.61718 | 0.61718 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.06400 | 1.41178E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6033.95501 | 6033.95501 | 0.25721 | 0.25721 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7906.83834 | 7906.83834 | 0.57477 | 0.57477 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 9509.97463 | 9509.97463 | 0.40535 | 0.40535 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 9617.46032 | 9617.46032 | 0.69911 | 0.69911 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6201.50889 | 6201.50889 | 0.26436 | 0.26436 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11135.13354 | 11135.13354 | 0.80944 | 0.80944 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 9418.66469 | 9418.66469 | 0.40145 | 0.40145 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 9854.77118 | 9854.77118 | 0.71636 | 0.71636 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6255.07666 | 6255.07666 | 0.26665 | 0.26665 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 74830.54 | 4.66032 | 4.66032 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 33562.05 | 1.71217 | 1.71217 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 67107.43 | 4.09053 | 4.09053 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 33912.92 | 1.98801 | 1.98801 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 76569.36 | 4.79060 | 4.79060 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 33751.94 | 2.84686 | 2.84686 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.71629 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27591 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76599 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73576 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38088E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25571.26620 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.97301 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37985 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.37400 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73791 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.00302E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24633.57392 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11436 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35446 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77174 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94522 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07488E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 37500.50189 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66843 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23636 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24400 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16310 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63030 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61194E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17464.22127 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72873 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13726 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14575 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36601 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77585E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11333.35878 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90787 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17402 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18157 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46406 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18936E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17315.72348 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78970 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12665 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15794 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33773 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00831E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11423.17545 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52787 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29930 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16153 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79813 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27297E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13002.66622 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60161 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16626 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12032 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44335 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29165E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8508.45506 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72932 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21663 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16191 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57768 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.75876E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12882.25047 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61718 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16205 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12344 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43214 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35108E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8586.54352 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57477 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27488 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27100 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15576 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73301 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38606E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13531.98734 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69911 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14307 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13982 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38152 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66303E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8825.11938 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80944 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19519 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16189 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52050 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95197E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13401.60613 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71636 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13962 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14327 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37231 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.72892E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8901.60996 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.59613 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33319 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.19227 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.71217 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.66032 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.66032 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.36739 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.38634 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.33865 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.77268 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.98801 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.09053 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.09053 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.48600 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.60455 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.42010 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.20910 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.84686 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.79060 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.79060 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.59426 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.66032 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.09053 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.79060 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.66032 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.66032 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 104743.89027 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73378 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.55329 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 34911.13863 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73378 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 31956.64329 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.66032 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.09053 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.09053 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 95354.12891 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72108 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.36337 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31781.53117 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72108 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 33731.10096 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.09053 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.79060 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.79060 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 106581.74840 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73655 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.59671 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35523.69674 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73655 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 32614.53488 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.79060 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 104230.80 | 355650.25 | 11.94 | 3.07 | 3.42 | 3.60 | 3.76 | 10.46 | 11.67 | 12.30 | 12.83 | 5.3876 | 4.2832 | 2.8841 | 1.2012 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 95004.59 | 324169.10 | 12.02 | 3.08 | 3.44 | 3.63 | 3.78 | 10.51 | 11.75 | 12.39 | 12.88 | 4.7289 | 3.7526 | 2.5259 | 1.0669 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 106022.14 | 361762.56 | 11.92 | 3.06 | 3.41 | 3.60 | 3.76 | 10.44 | 11.65 | 12.27 | 12.81 | 5.5382 | 4.3988 | 2.9659 | 1.2327 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.36 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.36 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.36 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.8721869304E-002 | 2.8706035486E-002 | Pass | Pass | 0.4849952955 | 0.4906181076 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1728118570 | 0.1282512270 | Pass | Pass | 0.4890161906 | 0.4831313511 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.1532497693E-002 | 4.8635802405E-002 | Pass | Pass | 0.4885456550 | 0.4753338980 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.8015497074E-002 | 4.6856383259E-002 | Pass | Pass | 0.4892671876 | 0.4728594076 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 9.0735940593E-003 | 8.1940322651E-003 | Pass | Pass | 0.5290878022 | 0.5600485703 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1106748571 | 0.1269847100 | Pass | Pass | 10.3578229545 | 41.5985179309 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5351117211 | 0.4880907972 | Pass | Pass | 9.3911330715 | 58.8064339413 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4599207004 | 0.5360208849 | Pass | Pass | 5.7796916333 | 41.9428850841 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3993708133 | 0.4511918113 | Pass | Pass | 11.1330410823 | 123.5743655567 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5360316788 | 0.5573486040 | Pass | Pass | 4.2485582783 | 16.3019652246 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3408854383 | 0.3154070432 | Pass | Pass | 8.7021928586 | 40.3620531908 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2771974465 | 0.3220434114 | Pass | Pass | 10.4001010238 | 71.5477710827 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1994275004 | 0.2103873360 | Pass | Pass | 3.6014863144 | 22.8741789898 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3483382407 | 0.3503706793 | Pass | Pass | 13.1502971412 | 77.5171635096 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3799220312 | 0.3547369449 | Pass | Pass | 7.5916246209 | 31.2149581055 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3399016716 | 0.3888484864 | Pass | Pass | 2.7325729755 | 12.9506940344 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2931673523 | 0.3145601621 | Pass | Pass | 1.4698540482 | 5.1517542964 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3887268715 | 0.4021194950 | Pass | Pass | 5.8615862262 | 28.6690798748 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3617.96 | 79.11 | 0.00 | 1426.60 | 1072.21 | 6195.90 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3628_SHGC_EAST_0.36 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3628_SHGC_EAST_0.36 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3628_SHGC_WEST_0.36 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3628_SHGC_WEST_0.36 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.061 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.36 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.36 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.061 | 0.361 | 0.361 | |||||||||||||||||
North Total or Average | 177.99 | 2.061 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.061 | 0.361 | 0.361 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.09 | 0.0000 | Y | 6.02 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.96 | 0.0000 | Y | 3.79 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.64 | 0.0000 | Y | 5.92 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.75 | 0.0000 | Y | 3.76 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.01 | 0.0000 | Y | 6.00 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.90 | 0.0000 | Y | 3.79 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.59 | 0.0000 | Y | 5.91 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.69 | 0.0000 | Y | 3.75 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.09 | 0.0000 | Y | 6.02 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.96 | 0.0000 | Y | 3.79 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.64 | 0.0000 | Y | 5.92 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.75 | 0.0000 | Y | 3.76 |
Interior Lighting Total | 5.9322 | 4982.19 | 29555.08 | 203.45 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.43 | 42.43 | 3.38 | |
EXTERIOR_LIGHTS_B | 408.47 | AstronomicalClock | - | 83.64 | 63.04 | 4.83 | |
EXTERIOR_LIGHTS_C | 4724.13 | AstronomicalClock | - | 83.64 | 46.90 | 41.59 | |
Exterior Lighting Total | 5557.43 | 49.81 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 104743.89 | 76859.14 | 27884.75 | 0.73 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 95354.13 | 68757.88 | 26596.25 | 0.72 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 106581.75 | 78502.96 | 28078.79 | 0.74 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 104230.8 | 3.07 | 10.46 | N/A | N/A | 11.94 | |
PACU_VAV_MID COOLING COIL | 95004.6 | 3.08 | 10.51 | N/A | N/A | 12.02 | |
PACU_VAV_TOP COOLING COIL | 106022.1 | 3.06 | 10.44 | N/A | N/A | 11.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25571.27 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24633.57 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 37500.50 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17464.22 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11333.36 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17315.72 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11423.18 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13002.67 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8508.46 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12882.25 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8586.54 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13531.99 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8825.12 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13401.61 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8901.61 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 31956.64 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 33731.10 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 32614.53 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.66 | 10781.12 | 2313.39 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.09 | 9462.98 | 2313.39 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.79 | 10486.68 | 2189.01 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 104230.80 | 3.07 | 10.46 | 11.94 | 5.3876 | 3.42 | 11.67 | 4.2832 | 3.60 | 12.30 | 2.8841 | 3.76 | 12.83 | 1.2012 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 95004.59 | 3.08 | 10.51 | 12.02 | 4.7289 | 3.44 | 11.75 | 3.7526 | 3.63 | 12.39 | 2.5259 | 3.78 | 12.88 | 1.0669 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 106022.14 | 3.06 | 10.44 | 11.92 | 5.5382 | 3.41 | 11.65 | 4.3988 | 3.60 | 12.27 | 2.9659 | 3.76 | 12.81 | 1.2327 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37686.23 | 37686.23 | 38.32 | 2.716 | 2.716 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_MID | 27409.82 | 27409.82 | 27.87 | 1.973 | 1.973 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 26.62 | 0.01411 | 0.425 | 0.00 |
CORE_TOP | 29087.24 | 29087.24 | 29.57 | 2.114 | 2.114 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00891 | 32.10 | 0.01412 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9195.35 | 9195.35 | 44.35 | 0.668 | 0.668 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00890 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10024.85 | 10024.85 | 76.37 | 0.729 | 0.729 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00874 | 28.45 | 0.01411 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12489.26 | 12489.26 | 60.24 | 0.908 | 0.908 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00880 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10863.65 | 10863.65 | 82.77 | 0.790 | 0.790 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00872 | 31.26 | 0.01412 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7261.78 | 7261.78 | 35.02 | 0.528 | 0.528 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00893 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8276.32 | 8276.32 | 63.05 | 0.602 | 0.602 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00874 | 28.66 | 0.01411 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10033.06 | 10033.06 | 48.39 | 0.729 | 0.729 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00881 | 31.85 | 0.01412 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8490.41 | 8490.41 | 64.69 | 0.617 | 0.617 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00874 | 31.06 | 0.01412 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7906.84 | 7906.84 | 38.13 | 0.575 | 0.575 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00894 | 32.10 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 9617.46 | 9617.46 | 73.27 | 0.699 | 0.699 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00874 | 28.24 | 0.01411 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11135.13 | 11135.13 | 53.71 | 0.809 | 0.809 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00881 | 31.79 | 0.01412 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 9854.77 | 9854.77 | 75.08 | 0.716 | 0.716 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00873 | 31.26 | 0.01412 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 7606.11 | 7606.11 | 7.73 | 0.320 | 0.425 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_MID | 15351.10 | 15351.10 | 15.61 | 0.650 | 0.650 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
CORE_TOP | 26411.83 | 26411.83 | 26.85 | 1.123 | 1.123 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12264.57 | 12264.57 | 59.15 | 0.523 | 0.523 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 7958.59 | 7958.59 | 60.63 | 0.339 | 0.339 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12160.56 | 12160.56 | 58.65 | 0.519 | 0.519 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 8021.50 | 8021.50 | 61.11 | 0.342 | 0.342 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9138.57 | 9138.57 | 44.08 | 0.389 | 0.389 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 5979.27 | 5979.27 | 45.55 | 0.255 | 0.255 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9054.25 | 9054.25 | 43.67 | 0.386 | 0.386 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6033.96 | 6033.96 | 45.97 | 0.257 | 0.257 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9509.97 | 9509.97 | 45.87 | 0.405 | 0.405 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6201.51 | 6201.51 | 47.25 | 0.264 | 0.264 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -10.70 | 0.00150 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9418.66 | 9418.66 | 45.43 | 0.401 | 0.401 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -10.70 | 0.00150 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6255.08 | 6255.08 | 47.66 | 0.267 | 0.267 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -10.70 | 0.00150 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.66 | 4.66 | 1.71 | 1.71 | 4.6603 | 1.7122 | 4.6603 | 0.3674 | 0.3000 |
PACU_VAV_MID | 4.09 | 4.09 | 1.99 | 1.99 | 4.0905 | 1.9880 | 4.0905 | 0.4860 | 0.3000 |
PACU_VAV_TOP | 4.79 | 4.79 | 2.85 | 2.85 | 4.7906 | 2.8469 | 4.7906 | 0.5943 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25571.266 | 25571.266 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25571.27 | 14177.50 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 7606.11 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24633.574 | 24633.574 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24633.57 | 21705.45 | 0.650193 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 15351.10 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 37500.502 | 37500.502 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37500.50 | 37500.50 | 1.123338 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 26411.83 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17464.221 | 17464.221 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17464.22 | 17464.22 | 0.523146 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00768846 | 49.7090 | 12264.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11333.359 | 11333.359 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11333.36 | 11333.36 | 0.339494 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00768120 | 49.6627 | 7958.59 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17315.723 | 17315.723 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17315.72 | 17315.72 | 0.518697 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00768562 | 49.6908 | 12160.56 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11423.175 | 11423.175 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11423.18 | 11423.18 | 0.342184 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00768381 | 49.6794 | 8021.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13002.666 | 13002.666 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13002.67 | 13002.67 | 0.389498 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00772158 | 49.9195 | 9138.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8508.455 | 8508.455 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8508.46 | 8508.46 | 0.254873 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00772658 | 49.9514 | 5979.27 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12882.250 | 12882.250 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12882.25 | 12882.25 | 0.385891 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00771541 | 49.8802 | 9054.25 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8586.544 | 8586.544 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8586.54 | 8586.54 | 0.257212 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00773194 | 49.9855 | 6033.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 13531.987 | 13531.987 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13531.99 | 13531.99 | 0.405354 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00763782 | 49.3855 | 9509.97 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 8825.119 | 8825.119 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8825.12 | 8825.12 | 0.264359 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00763565 | 49.3717 | 6201.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 13401.606 | 13401.606 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13401.61 | 13401.61 | 0.401449 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00763241 | 49.3509 | 9418.66 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 8901.610 | 8901.610 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8901.61 | 8901.61 | 0.266650 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00764012 | 49.4002 | 6255.08 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 104743.890 | 76859.137 | 4.660321 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 107473.66 | 83111.40 | 4.660321 | 26.08 | 18.50 | 0.01019984 | 10.92 | 10.92 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 25.6457 | 24.00 | 0.00884786 | 47.5837 | 64111.55 | 0.00 | 108005.01 | 78080.02 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 31956.643 | 31956.643 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31956.64 | 31956.64 | 1.398096 | -6.10 | -6.10 | 0.00241597 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 85.4855 | 19.73 | 0.00773101 | 54.0619 | 22744.69 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 95354.129 | 68757.878 | 4.090532 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 98490.75 | 74189.96 | 4.090532 | 26.37 | 18.78 | 0.01043701 | 10.92 | 10.92 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 29.2180 | 24.00 | 0.00891666 | 47.9487 | 56266.99 | 0.00 | 98322.91 | 69872.03 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 33731.101 | 33731.101 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 33731.10 | 33731.10 | 1.227160 | -9.93 | -9.93 | 0.00165878 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 97.3932 | 19.64 | 0.00729256 | 51.3036 | 24734.28 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 106581.748 | 78502.955 | 4.790602 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 109268.10 | 84680.51 | 4.790602 | 26.02 | 18.46 | 0.01017736 | 11.02 | 11.02 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 24.9482 | 24.00 | 0.00886622 | 47.6813 | 65877.50 | 0.00 | 109900.09 | 79727.36 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 32614.535 | 32614.535 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 32614.53 | 32614.53 | 1.437181 | -5.96 | -5.96 | 0.00250887 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 83.1607 | 17.60 | 0.00740041 | 59.1602 | 30481.77 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25571.266 | 25571.266 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25571.27 | 14177.50 | 1.0000 | 0.51115607 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25571.27 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.59 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 7606.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24633.574 | 24633.574 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24633.57 | 21705.45 | 1.0000 | 0.78256893 | 0.650193 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24633.57 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 15351.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 37500.502 | 37500.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37500.50 | 37500.50 | 1.0000 | 1.35204397 | 1.123338 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37500.50 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 26411.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17464.221 | 17464.221 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17464.22 | 17464.22 | 1.0000 | 0.62965544 | 0.523146 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17464.22 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00768846 | 21.00 | 0.00768846 | 49.7090 | 12264.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11333.359 | 11333.359 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11333.36 | 11333.36 | 1.0000 | 0.40861318 | 0.339494 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11333.36 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00768120 | 21.00 | 0.00768120 | 49.6627 | 7958.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17315.723 | 17315.723 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17315.72 | 17315.72 | 1.0000 | 0.62430150 | 0.518697 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17315.72 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00768562 | 21.00 | 0.00768562 | 49.6908 | 12160.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11423.175 | 11423.175 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11423.18 | 11423.18 | 1.0000 | 0.41185143 | 0.342184 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11423.18 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00768381 | 21.00 | 0.00768381 | 49.6794 | 8021.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13002.666 | 13002.666 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13002.67 | 13002.67 | 1.0000 | 0.46879843 | 0.389498 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13002.67 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00772158 | 21.00 | 0.00772158 | 49.9195 | 9138.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8508.455 | 8508.455 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8508.46 | 8508.46 | 1.0000 | 0.30676404 | 0.254873 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8508.46 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00772658 | 21.00 | 0.00772658 | 49.9514 | 5979.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12882.250 | 12882.250 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12882.25 | 12882.25 | 1.0000 | 0.46445696 | 0.385891 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12882.25 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00771541 | 21.00 | 0.00771541 | 49.8802 | 9054.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8586.544 | 8586.544 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8586.54 | 8586.54 | 1.0000 | 0.30957944 | 0.257212 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8586.54 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00773194 | 21.00 | 0.00773194 | 49.9855 | 6033.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13531.987 | 13531.987 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13531.99 | 13531.99 | 1.0000 | 0.48788259 | 0.405354 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13531.99 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00763782 | 21.00 | 0.00763782 | 49.3855 | 9509.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8825.119 | 8825.119 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8825.12 | 8825.12 | 1.0000 | 0.31818106 | 0.264359 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8825.12 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00763565 | 21.00 | 0.00763565 | 49.3717 | 6201.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13401.606 | 13401.606 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13401.61 | 13401.61 | 1.0000 | 0.48318182 | 0.401449 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13401.61 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00763241 | 21.00 | 0.00763241 | 49.3509 | 9418.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8901.610 | 8901.610 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8901.61 | 8901.61 | 1.0000 | 0.32093885 | 0.266650 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8901.61 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00764012 | 21.00 | 0.00764012 | 49.4002 | 6255.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 104743.890 | 76859.137 | 4.660321 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8010 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.660321 | 5.60913935 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 107473.66 | 83111.40 | 1.0261 | 5.60913935 | 4.660321 | 26.08 | 18.50 | 0.01019984 | 52206.2 | 10.92 | 10.92 | 0.00850000 | 32406.1 | -999.0 | -999.00 | -999.00 | -999.00 | 10781.125 | 96692.53 | 32.10 | 0.01411964 | 23.13 | 1.19517000 | 25.6457 | 24.00 | 0.00884786 | 24.00 | 0.00884786 | 47.5837 | 64111.55 | 0.00 | 108005.01 | 78080.02 | 5.38762075 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.48 | 12.47 | 0.00900691 | 35275.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31956.643 | 31956.643 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.660321 | 5.60913935 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 31956.64 | 31956.64 | 1.0000 | 1.68274181 | 1.398096 | -6.10 | -6.10 | 0.00241597 | -113.7 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31956.64 | -10.70 | 0.00150390 | -10.70 | 1.19517000 | 85.4855 | 21.00 | 0.00778777 | 19.73 | 0.00773101 | 54.0619 | 22744.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 95354.129 | 68757.878 | 4.090532 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2419 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.090532 | 4.92334400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 98490.75 | 74189.96 | 1.0329 | 4.92334400 | 4.090532 | 26.37 | 18.78 | 0.01043701 | 53107.4 | 10.92 | 10.92 | 0.00850000 | 32406.9 | -999.0 | -999.00 | -999.00 | -999.00 | 9462.982 | 89027.77 | 32.10 | 0.01411964 | 23.13 | 1.19517000 | 29.2180 | 24.00 | 0.00891666 | 24.00 | 0.00891666 | 47.9487 | 56266.99 | 0.00 | 98322.91 | 69872.03 | 4.72890913 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.20 | 12.18 | 0.00882578 | 34530.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33731.101 | 33731.101 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.090532 | 4.92334400 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 33731.10 | 33731.10 | 1.0000 | 1.47700320 | 1.227160 | -9.93 | -9.93 | 0.00165878 | -5857.2 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33731.10 | -10.70 | 0.00150390 | -10.70 | 1.19517000 | 97.3932 | 18.95 | 0.00744550 | 19.64 | 0.00729256 | 51.3036 | 24734.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 106581.748 | 78502.955 | 4.790602 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7592 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.790602 | 5.76594493 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 109268.10 | 84680.51 | 1.0252 | 5.76594493 | 4.790602 | 26.02 | 18.46 | 0.01017736 | 52091.7 | 11.02 | 11.02 | 0.00850000 | 32509.0 | -999.0 | -999.00 | -999.00 | -999.00 | 10486.681 | 98781.42 | 32.10 | 0.01411964 | 23.13 | 1.19517000 | 24.9482 | 24.00 | 0.00886622 | 24.00 | 0.00886622 | 47.6813 | 65877.50 | 0.00 | 109900.09 | 79727.36 | 5.53823369 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.58 | 12.55 | 0.00904859 | 35478.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32614.535 | 32614.535 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.790602 | 5.76594493 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 32614.53 | 32614.53 | 1.0000 | 1.72978348 | 1.437181 | -5.96 | -5.96 | 0.00250887 | 254.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32614.53 | -10.70 | 0.00150390 | -10.70 | 1.19517000 | 83.1607 | 17.43 | 0.00747193 | 17.60 | 0.00740041 | 59.1602 | 30481.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.66 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.09 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2404.17 | 2639.17 | 64.67 |
CORE_MID | 2484.50 | 3353.00 | 575.83 |
CORE_TOP | 3022.50 | 3606.83 | 1314.00 |
PERIMETER_TOP_ZN_3 | 3823.33 | 3811.50 | 2146.83 |
PERIMETER_TOP_ZN_2 | 3818.83 | 3688.17 | 1953.50 |
PERIMETER_TOP_ZN_1 | 3544.33 | 3412.50 | 1578.67 |
PERIMETER_TOP_ZN_4 | 3746.17 | 3764.83 | 1989.50 |
PERIMETER_BOT_ZN_3 | 3505.00 | 3783.33 | 1833.17 |
PERIMETER_BOT_ZN_2 | 3498.17 | 3396.50 | 1467.00 |
PERIMETER_BOT_ZN_1 | 3447.33 | 3775.67 | 1714.00 |
PERIMETER_BOT_ZN_4 | 3564.33 | 3459.17 | 1553.67 |
PERIMETER_MID_ZN_3 | 3528.83 | 3586.17 | 1705.33 |
PERIMETER_MID_ZN_2 | 3014.00 | 3038.50 | 1409.00 |
PERIMETER_MID_ZN_1 | 3327.50 | 3114.83 | 1142.17 |
PERIMETER_MID_ZN_4 | 3523.50 | 3502.00 | 1576.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4983.83 | 4544.17 | 2701.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.50 | 0.67 | 0.50 | 0.00 |
CORE_MID | 2.33 | 0.17 | 1.83 | 0.00 |
CORE_TOP | 3.83 | 0.00 | 2.50 | 0.00 |
PERIMETER_TOP_ZN_3 | 38.67 | 3.33 | 16.67 | 3.00 |
PERIMETER_TOP_ZN_2 | 23.83 | 27.00 | 2.33 | 26.50 |
PERIMETER_TOP_ZN_1 | 19.33 | 26.50 | 3.17 | 25.67 |
PERIMETER_TOP_ZN_4 | 23.17 | 25.00 | 3.83 | 18.00 |
PERIMETER_BOT_ZN_3 | 15.17 | 0.00 | 9.50 | 0.00 |
PERIMETER_BOT_ZN_2 | 6.17 | 13.17 | 1.00 | 13.17 |
PERIMETER_BOT_ZN_1 | 358.83 | 51.33 | 356.50 | 51.17 |
PERIMETER_BOT_ZN_4 | 7.17 | 13.50 | 2.00 | 10.33 |
PERIMETER_MID_ZN_3 | 13.50 | 0.00 | 7.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7.83 | 21.00 | 1.50 | 21.00 |
PERIMETER_MID_ZN_1 | 6.50 | 22.17 | 1.33 | 22.00 |
PERIMETER_MID_ZN_4 | 8.50 | 20.67 | 2.00 | 15.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 390.33 | 131.17 | 364.33 | 120.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.768 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.572 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.573 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.654 | 0.043 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.992 | 0.045 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.959 | 0.043 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 1.041 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.581 | 0.023 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.832 | 0.024 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.796 | 1.298 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.830 | 0.024 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.643 | 0.035 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.902 | 0.040 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.936 | 0.036 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.995 | 0.037 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.88 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.88 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.49 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 12165903.79 | 0.00 | 12165903.79 | 0.00 | 12165903.79 | 13393058.27 | 5546.73 | 564.70 | 2648.58 | 52.36 |
CORE_MID | 9051808.71 | 0.00 | 9051808.71 | 0.00 | 9051808.71 | 13393058.27 | 6992.06 | 49.56 | 1718.39 | 36.85 |
CORE_TOP | 9073071.00 | 0.00 | 9073071.00 | 0.00 | 9073071.00 | 13393058.27 | 6996.86 | 27.05 | 1736.09 | 61.71 |
PERIMETER_TOP_ZN_3 | 2182887.29 | 0.00 | 2182887.29 | 278735.79 | 2461623.08 | 2823374.22 | 5953.42 | 48.99 | 2757.60 | 61.61 |
PERIMETER_TOP_ZN_2 | 2095283.28 | 0.00 | 2095283.28 | 185822.74 | 2281106.02 | 1787429.43 | 4224.04 | 2.79 | 4533.17 | 61.61 |
PERIMETER_TOP_ZN_1 | 3192222.55 | 0.00 | 3192222.55 | 278735.79 | 3470958.34 | 2823374.22 | 4254.68 | 13.80 | 4491.52 | 61.61 |
PERIMETER_TOP_ZN_4 | 2200720.45 | 0.00 | 2200720.45 | 185822.74 | 2386543.19 | 1787312.18 | 4240.23 | 9.13 | 4510.63 | 61.61 |
PERIMETER_BOT_ZN_3 | 1948928.28 | 0.00 | 1948928.28 | 148202.29 | 2097130.57 | 2823374.22 | 6209.65 | 577.09 | 1973.26 | 52.36 |
PERIMETER_BOT_ZN_2 | 1762511.92 | 0.00 | 1762511.92 | 98800.93 | 1861312.85 | 1787429.43 | 4331.18 | 45.26 | 4383.55 | 52.36 |
PERIMETER_BOT_ZN_1 | 2665775.36 | 0.00 | 2665775.36 | 4413538.54 | 7079313.90 | 2823374.22 | 5012.45 | 651.13 | 3096.42 | 52.36 |
PERIMETER_BOT_ZN_4 | 1757338.61 | 0.00 | 1757338.61 | 98800.93 | 1856139.55 | 1787312.18 | 4406.75 | 49.73 | 4303.52 | 52.36 |
PERIMETER_MID_ZN_3 | 2145203.01 | 0.00 | 2145203.01 | 232026.10 | 2377229.11 | 2823374.22 | 5998.53 | 72.16 | 2689.31 | 36.85 |
PERIMETER_MID_ZN_2 | 2061022.52 | 0.00 | 2061022.52 | 154683.14 | 2215705.65 | 1787429.43 | 4212.03 | 6.66 | 4541.31 | 945.85 |
PERIMETER_MID_ZN_1 | 3115833.09 | 0.00 | 3115833.09 | 232026.10 | 3347859.19 | 2823374.22 | 4272.33 | 418.87 | 4068.79 | 36.85 |
PERIMETER_MID_ZN_4 | 2100130.33 | 0.00 | 2100130.33 | 154683.14 | 2254813.46 | 1787312.18 | 4217.44 | 13.76 | 4528.79 | 36.85 |
Total Facility | 57518640.18 | 0.00 | 57518640.18 | 6461878.22 | 63980518.39 | 67843644.98 | 7165.06 | 1342.27 | 4633.41 | 1030.12 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5643 | 0.0000 | 0.5643 | 0.0000 | 0.5643 | 0.4247 | 2758.70 | 564.70 | 2619.61 |
CORE_MID | 0.4211 | 0.0000 | 0.4211 | 0.0000 | 0.4211 | 0.4247 | 4187.76 | 49.56 | 1705.68 |
CORE_TOP | 0.4219 | 0.0000 | 0.4219 | 0.0000 | 0.4219 | 0.4247 | 4193.83 | 27.05 | 1722.12 |
PERIMETER_TOP_ZN_3 | 0.1016 | 0.0000 | 0.1016 | 0.0066 | 0.1082 | 0.0895 | 3150.39 | 48.99 | 2743.63 |
PERIMETER_TOP_ZN_2 | 0.0975 | 0.0000 | 0.0975 | 0.0044 | 0.1019 | 0.0567 | 1421.02 | 2.79 | 4519.19 |
PERIMETER_TOP_ZN_1 | 0.1487 | 0.0000 | 0.1487 | 0.0066 | 0.1553 | 0.0895 | 1451.65 | 13.80 | 4477.55 |
PERIMETER_TOP_ZN_4 | 0.1024 | 0.0000 | 0.1024 | 0.0044 | 0.1068 | 0.0567 | 1437.21 | 9.13 | 4496.66 |
PERIMETER_BOT_ZN_3 | 0.0903 | 0.0000 | 0.0903 | 0.0035 | 0.0938 | 0.0895 | 3421.62 | 577.09 | 1944.29 |
PERIMETER_BOT_ZN_2 | 0.0818 | 0.0000 | 0.0818 | 0.0024 | 0.0841 | 0.0567 | 1543.18 | 45.26 | 4354.55 |
PERIMETER_BOT_ZN_1 | 0.1238 | 0.0000 | 0.1238 | 0.2029 | 0.3267 | 0.0895 | 2224.43 | 651.13 | 3067.44 |
PERIMETER_BOT_ZN_4 | 0.0815 | 0.0000 | 0.0815 | 0.0024 | 0.0839 | 0.0567 | 1618.77 | 49.70 | 4274.52 |
PERIMETER_MID_ZN_3 | 0.0999 | 0.0000 | 0.0999 | 0.0055 | 0.1054 | 0.0895 | 3194.24 | 72.16 | 2676.60 |
PERIMETER_MID_ZN_2 | 0.0886 | 0.0000 | 0.0886 | 0.0039 | 0.0925 | 0.0567 | 1399.42 | 5.64 | 3628.94 |
PERIMETER_MID_ZN_1 | 0.1452 | 0.0000 | 0.1452 | 0.0055 | 0.1507 | 0.0895 | 1468.04 | 418.87 | 4056.08 |
PERIMETER_MID_ZN_4 | 0.0978 | 0.0000 | 0.0978 | 0.0037 | 0.1015 | 0.0567 | 1413.19 | 13.74 | 4516.06 |
Total Facility | 2.6663 | 0.0000 | 2.6663 | 0.2519 | 2.9182 | 2.1513 | 4353.33 | 1342.21 | 4594.71 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 29408066.06 | 0.00 | 29408066.06 | 22614548.33 | 4181.53 | 4.57 | 4573.90 | 52.14 |
PACU_VAV_MID | 26762203.80 | 0.00 | 26762203.80 | 22614548.33 | 4191.05 | 1.72 | 4567.23 | 36.85 |
PACU_VAV_TOP | 27153596.79 | 0.00 | 27153596.79 | 22614548.33 | 4213.83 | 2.63 | 4543.54 | 61.34 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.3641 | 0.0000 | 1.3641 | 0.7171 | 1393.50 | 4.57 | 4544.93 |
PACU_VAV_MID | 1.2458 | 0.0000 | 1.2458 | 0.7171 | 1386.76 | 1.72 | 4554.53 |
PACU_VAV_TOP | 1.2632 | 0.0000 | 1.2632 | 0.7171 | 1410.80 | 2.63 | 4529.57 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.06 | 2150.69 | 0.00 | 0.00 | 0.00 | 2547.75 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 1944.86 | 0.00 | 0.00 | 0.00 | 2753.67 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 1993.39 | 0.00 | 0.00 | 0.00 | 2733.45 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.5093 | 0.0000 | 0.0000 | 0.0000 | 1.1158 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.2627 | 0.0000 | 0.0000 | 0.0000 | 1.1211 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.3069 | 0.0000 | 0.0000 | 0.0000 | 1.1162 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 825 |
Defaulted Fields | 545 |
Fields with Defaults | 2230 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1420.64 | 12347.50 | 30-APR-17:10 | 241761.03 | 02-JAN-07:10 |
Electricity:Building | 908.89 | 12175.61 | 14-MAY-17:10 | 66194.72 | 03-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 284.50 | 4029.56 | 01-JAN-00:10 | 22405.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 908.89 | 12175.61 | 14-MAY-17:10 | 66194.72 | 03-JAN-08:10 |
InteriorLights:Electricity | 203.45 | 934.27 | 01-JAN-09:20 | 21377.78 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 203.45 | 934.27 | 01-JAN-09:20 | 21377.78 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 203.45 | 934.27 | 01-JAN-09:20 | 21377.78 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 203.45 | 934.27 | 01-JAN-09:20 | 21377.78 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.36 | 409.68 | 09-APR-17:10 | 2324.90 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.02 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.02 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.20 | 259.34 | 14-MAY-17:10 | 1471.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.79 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.79 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.25 | 409.67 | 26-MAR-17:10 | 2324.89 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.92 | 23.57 | 01-JAN-07:50 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.92 | 23.57 | 01-JAN-07:50 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.17 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.76 | 14.92 | 01-JAN-09:20 | 563.19 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.76 | 14.92 | 01-JAN-09:20 | 563.19 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.34 | 409.68 | 02-APR-17:10 | 2324.90 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.00 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.00 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.19 | 259.34 | 14-MAY-17:10 | 1471.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.79 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.79 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.24 | 409.67 | 26-MAR-17:10 | 2324.89 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.91 | 23.57 | 01-JAN-07:50 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.91 | 23.57 | 01-JAN-07:50 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.16 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.76 | 14.92 | 01-JAN-09:10 | 563.19 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.76 | 14.92 | 01-JAN-09:10 | 563.19 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.36 | 409.68 | 09-APR-17:10 | 2324.90 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.02 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.02 | 23.57 | 01-JAN-09:20 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.20 | 259.34 | 14-MAY-17:10 | 1471.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.79 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.79 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.25 | 409.67 | 26-MAR-17:10 | 2324.89 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.92 | 23.57 | 01-JAN-07:50 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.92 | 23.57 | 01-JAN-07:50 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.17 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.76 | 14.92 | 01-JAN-09:20 | 563.19 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.76 | 14.92 | 01-JAN-09:20 | 563.19 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 461.93 | 168.57 | 30-APR-17:10 | 208196.91 | 02-JAN-06:20 |
ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 833.98 | 02-JAN-16:50 |
Transformer:ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 833.98 | 02-JAN-16:50 |
ElectricityPurchased:Facility | 1420.64 | 12347.50 | 30-APR-17:10 | 241761.03 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1420.64 | 12347.50 | 30-APR-17:10 | 241761.03 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1420.64 | 12347.50 | 30-APR-17:10 | 241761.03 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1420.64 | 12347.50 | 30-APR-17:10 | 241761.03 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1420.64 | 12347.50 | 30-APR-17:10 | 241761.03 | 02-JAN-07:10 |
ElectricityNet:Plant | 1420.64 | 12347.50 | 30-APR-17:10 | 241761.03 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1420.64 | 12347.50 | 30-APR-17:10 | 241761.03 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1420.64 | 12347.50 | 30-APR-17:10 | 241761.03 | 02-JAN-07:10 |
Heating:Electricity | 154.61 | 0.00 | 01-JAN-00:40 | 200766.58 | 02-JAN-06:20 |
General:Heating:Electricity | 154.61 | 0.00 | 01-JAN-00:40 | 200766.58 | 02-JAN-06:20 |
Fans:Electricity | 96.14 | 0.00 | 01-JAN-00:40 | 25644.99 | 30-MAY-14:40 |
General:Fans:Electricity | 96.14 | 0.00 | 01-JAN-00:40 | 25644.99 | 30-MAY-14:40 |
ExteriorLights:Electricity | 49.81 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 49.81 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 199.52 | 0.00 | 01-JAN-00:10 | 75494.26 | 19-JUN-12:20 |
General:Cooling:Electricity | 199.52 | 0.00 | 01-JAN-00:10 | 75494.26 | 19-JUN-12:20 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 5.72 | 0.00 | 01-JAN-00:10 | 600.72 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 246.12 | 1156.00 | 11-MAR-06:10 | 100730.93 | 06-FEB-07:30 |
NaturalGas:HVAC | 138.80 | 0.00 | 01-JAN-00:40 | 92594.63 | 06-FEB-07:40 |
Heating:NaturalGas | 138.80 | 0.00 | 01-JAN-00:40 | 92594.63 | 06-FEB-07:40 |
General:Heating:NaturalGas | 138.80 | 0.00 | 01-JAN-00:40 | 92594.63 | 06-FEB-07:40 |
NaturalGas:Plant | 107.33 | 1156.00 | 03-JAN-07:10 | 9472.57 | 09-FEB-12:10 |
WaterSystems:NaturalGas | 107.33 | 1156.00 | 03-JAN-07:10 | 9472.57 | 09-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 107.33 | 1156.00 | 03-JAN-07:10 | 9472.57 | 09-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2249.98 | 0.00 | 01-JAN-00:40 | 462105.30 | 02-JAN-07:10 |
EnergyTransfer:Building | 1090.49 | 0.00 | 01-JAN-00:40 | 202385.82 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 213.51 | 0.00 | 01-JAN-00:40 | 27027.10 | 07-AUG-08:00 |
Heating:EnergyTransfer | 123.21 | 0.00 | 01-JAN-00:40 | 202385.82 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.34 | 0.00 | 01-JAN-00:10 | 20056.29 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 123.21 | 0.00 | 01-JAN-00:40 | 202385.82 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.34 | 0.00 | 01-JAN-00:10 | 20056.29 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 967.29 | 0.00 | 01-JAN-00:40 | 163309.26 | 10-JUL-14:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 213.17 | 0.00 | 01-JAN-00:40 | 27027.10 | 07-AUG-08:00 |
General:Cooling:EnergyTransfer | 967.29 | 0.00 | 01-JAN-00:40 | 163309.26 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 213.17 | 0.00 | 01-JAN-00:40 | 27027.10 | 07-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.50 | 0.00 | 01-JAN-00:40 | 14647.23 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 18.67 | 0.00 | 01-JAN-00:40 | 14647.23 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 18.67 | 0.00 | 01-JAN-00:40 | 14647.23 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.83 | 0.00 | 01-JAN-00:10 | 12017.36 | 19-JUN-13:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 31.83 | 0.00 | 01-JAN-00:10 | 12017.36 | 19-JUN-13:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.38 | 0.00 | 01-JAN-00:40 | 9514.32 | 02-JAN-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.14 | 0.00 | 01-JAN-00:40 | 9514.32 | 02-JAN-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 9.14 | 0.00 | 01-JAN-00:40 | 9514.32 | 02-JAN-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.24 | 0.00 | 01-JAN-00:10 | 5309.25 | 14-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.24 | 0.00 | 01-JAN-00:10 | 5309.25 | 14-AUG-14:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.60 | 0.00 | 01-JAN-00:40 | 7768.17 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 6.45 | 0.00 | 01-JAN-00:40 | 7768.17 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 6.45 | 0.00 | 01-JAN-00:40 | 7768.17 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.15 | 0.00 | 01-JAN-00:10 | 5380.14 | 10-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 21.15 | 0.00 | 01-JAN-00:10 | 5380.14 | 10-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 143.87 | 0.00 | 01-JAN-00:40 | 21315.05 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.25 | 0.00 | 01-JAN-00:20 | 21315.05 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.25 | 0.00 | 01-JAN-00:20 | 21315.05 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 142.62 | 0.00 | 01-JAN-00:40 | 18225.36 | 14-AUG-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 142.62 | 0.00 | 01-JAN-00:40 | 18225.36 | 14-AUG-07:40 |
EnergyTransfer:Zone:CORE_TOP | 141.62 | 0.00 | 01-JAN-00:40 | 27871.40 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 6.52 | 0.00 | 01-JAN-00:40 | 27871.40 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 6.52 | 0.00 | 01-JAN-00:40 | 27871.40 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 135.10 | 0.00 | 01-JAN-00:20 | 20216.26 | 10-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 135.10 | 0.00 | 01-JAN-00:20 | 20216.26 | 10-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.64 | 0.00 | 01-JAN-00:40 | 9574.26 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 12.02 | 0.00 | 01-JAN-00:40 | 9574.26 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 12.02 | 0.00 | 01-JAN-00:40 | 9574.26 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.62 | 0.00 | 01-JAN-00:10 | 7623.93 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.62 | 0.00 | 01-JAN-00:10 | 7623.93 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 36.48 | 0.00 | 01-JAN-00:40 | 9084.59 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 6.21 | 0.00 | 01-JAN-00:40 | 9084.59 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 6.21 | 0.00 | 01-JAN-00:40 | 9084.59 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.27 | 0.00 | 01-JAN-00:10 | 8890.28 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.27 | 0.00 | 01-JAN-00:10 | 8890.28 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 57.08 | 0.00 | 01-JAN-00:40 | 12619.24 | 28-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 7.65 | 0.00 | 01-JAN-00:40 | 11642.13 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 7.65 | 0.00 | 01-JAN-00:40 | 11642.13 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 49.43 | 0.00 | 01-JAN-00:10 | 12619.24 | 28-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 49.43 | 0.00 | 01-JAN-00:10 | 12619.24 | 28-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 38.07 | 0.00 | 01-JAN-00:40 | 9523.96 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 7.20 | 0.00 | 01-JAN-00:40 | 9523.96 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 7.20 | 0.00 | 01-JAN-00:40 | 9523.96 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.87 | 0.00 | 01-JAN-00:10 | 9367.18 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 30.87 | 0.00 | 01-JAN-00:10 | 9367.18 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 33.35 | 0.00 | 01-JAN-00:40 | 7431.48 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.48 | 0.00 | 01-JAN-00:40 | 7431.48 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.48 | 0.00 | 01-JAN-00:40 | 7431.48 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.87 | 0.00 | 01-JAN-00:10 | 5884.23 | 10-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 27.87 | 0.00 | 01-JAN-00:10 | 5884.23 | 10-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.14 | 0.00 | 01-JAN-00:40 | 7186.35 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.46 | 0.00 | 01-JAN-00:40 | 7186.35 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.46 | 0.00 | 01-JAN-00:40 | 7186.35 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.68 | 0.00 | 01-JAN-00:20 | 7061.07 | 22-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 27.68 | 0.00 | 01-JAN-00:20 | 7061.07 | 22-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 62.03 | 0.00 | 01-JAN-00:40 | 14149.55 | 02-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 22.77 | 0.00 | 01-JAN-00:40 | 14149.55 | 02-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 22.77 | 0.00 | 01-JAN-00:40 | 14149.55 | 02-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 39.26 | 0.00 | 01-JAN-00:20 | 13137.95 | 19-JUN-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 39.26 | 0.00 | 01-JAN-00:20 | 13137.95 | 19-JUN-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 30.33 | 0.00 | 01-JAN-00:40 | 7331.79 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.88 | 0.00 | 01-JAN-00:40 | 7255.95 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.88 | 0.00 | 01-JAN-00:40 | 7255.95 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 27.45 | 0.00 | 01-JAN-00:20 | 7331.79 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 27.45 | 0.00 | 01-JAN-00:20 | 7331.79 | 21-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 36.63 | 0.00 | 01-JAN-00:40 | 8071.45 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 5.28 | 0.00 | 01-JAN-00:40 | 8071.45 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 5.28 | 0.00 | 01-JAN-00:40 | 8071.45 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 31.35 | 0.00 | 01-JAN-00:10 | 6716.63 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 31.35 | 0.00 | 01-JAN-00:10 | 6716.63 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 33.11 | 0.00 | 01-JAN-00:40 | 8570.80 | 26-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.75 | 0.00 | 01-JAN-00:40 | 7282.30 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.75 | 0.00 | 01-JAN-00:40 | 7282.30 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.36 | 0.00 | 01-JAN-00:20 | 8570.80 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 30.36 | 0.00 | 01-JAN-00:20 | 8570.80 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.11 | 0.00 | 01-JAN-00:40 | 11514.87 | 28-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.01 | 0.00 | 01-JAN-00:40 | 10266.87 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.01 | 0.00 | 01-JAN-00:40 | 10266.87 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.11 | 0.00 | 01-JAN-00:20 | 11514.87 | 28-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 50.11 | 0.00 | 01-JAN-00:20 | 11514.87 | 28-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 34.02 | 0.00 | 01-JAN-00:40 | 8772.67 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.13 | 0.00 | 01-JAN-00:40 | 7326.59 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 3.13 | 0.00 | 01-JAN-00:40 | 7326.59 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 30.90 | 0.00 | 01-JAN-00:20 | 8772.67 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 30.90 | 0.00 | 01-JAN-00:20 | 8772.67 | 15-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 48.91 | 0.00 | 01-JAN-00:10 | 6337.56 | 08-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 48.91 | 0.00 | 01-JAN-00:10 | 6337.56 | 08-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 48.91 | 0.00 | 01-JAN-00:10 | 6337.56 | 08-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 48.91 | 0.00 | 01-JAN-00:10 | 6337.56 | 08-FEB-12:30 |
EnergyTransfer:HVAC | 1110.58 | 0.00 | 01-JAN-00:40 | 278635.05 | 16-AUG-12:30 |
HeatingCoils:EnergyTransfer | 265.65 | 0.00 | 01-JAN-00:40 | 266606.98 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 844.93 | 0.00 | 01-JAN-00:10 | 278635.05 | 16-AUG-12:30 |
EnergyTransfer:Plant | 48.91 | 0.00 | 01-JAN-00:10 | 6337.56 | 08-FEB-12:30 |
WaterSystems:EnergyTransfer | 48.91 | 0.00 | 01-JAN-00:10 | 6337.56 | 08-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 48.91 | 0.00 | 01-JAN-00:10 | 6337.56 | 08-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.342 | -213.173 | 0.000 | 0.000 | 33.123 | 48.333 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -104.793 |
CORE_MID | 0.000 | 0.000 | 1.250 | -142.621 | 0.000 | 0.000 | 34.594 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -56.981 |
CORE_TOP | 0.000 | 0.000 | 6.516 | -135.100 | 0.000 | 0.000 | 35.252 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -70.427 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 12.025 | -30.617 | 0.000 | 0.000 | 7.551 | 6.024 | 24.333 | 17.333 | 0.000 | 0.056 | 0.001 | 0.000 | -24.974 | 0.000 | -3.676 | -8.053 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 6.206 | -30.273 | 0.000 | 0.000 | 4.734 | 3.794 | 15.404 | 30.646 | 0.000 | 0.036 | 0.000 | 0.000 | -15.800 | 0.000 | -2.486 | -12.260 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 7.650 | -49.433 | 0.000 | 0.000 | 7.344 | 5.920 | 24.332 | 62.317 | 0.000 | 0.054 | 0.001 | 0.000 | -23.791 | 0.000 | -3.856 | -30.537 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 7.202 | -30.866 | 0.000 | 0.000 | 4.778 | 3.763 | 15.403 | 31.244 | 0.000 | 0.037 | 0.001 | 0.000 | -16.298 | 0.000 | -2.500 | -12.764 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 5.478 | -27.874 | 0.000 | 0.000 | 7.521 | 6.005 | 24.333 | 17.575 | 0.000 | 0.034 | 0.000 | 0.000 | -26.170 | 0.000 | -2.074 | -4.828 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.458 | -27.679 | 0.000 | 0.000 | 4.691 | 3.785 | 15.404 | 30.748 | 0.000 | 0.020 | 0.000 | 0.000 | -16.853 | 0.000 | -1.423 | -11.150 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 22.770 | -39.260 | 0.000 | 0.000 | 7.580 | 5.908 | 24.332 | 63.094 | 0.000 | 3.004 | 0.000 | 0.000 | -25.133 | 0.000 | -45.571 | -16.723 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 2.885 | -27.447 | 0.000 | 0.000 | 4.722 | 3.755 | 15.403 | 31.375 | 0.000 | 0.020 | 0.000 | 0.000 | -17.390 | 0.000 | -1.432 | -11.892 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 5.281 | -31.351 | 0.000 | 0.000 | 7.478 | 6.024 | 24.333 | 17.154 | 0.000 | 0.048 | 0.803 | 0.000 | -26.520 | 0.000 | -3.248 | -0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.749 | -30.364 | 0.000 | 0.000 | 3.475 | 3.794 | 15.404 | 30.495 | 0.000 | 0.031 | 0.000 | 0.000 | -16.734 | 0.000 | -2.192 | -6.658 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 3.006 | -50.109 | 0.000 | 0.000 | 7.249 | 5.920 | 24.332 | 62.077 | 0.000 | 0.045 | 0.000 | 0.000 | -25.265 | 0.000 | -3.409 | -23.846 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 3.127 | -30.897 | 0.000 | 0.000 | 4.725 | 3.763 | 15.403 | 31.115 | 0.000 | 0.031 | 0.000 | 0.000 | -17.298 | 0.000 | -2.208 | -7.763 |
TOPFLOOR_PLENUM | 18.669 | -31.829 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.054 | 18.720 | 0.000 | 0.000 | 0.000 | -5.615 | -0.000 |
MIDFLOOR_PLENUM | 9.140 | -17.242 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.065 | 13.610 | 0.000 | 0.000 | 0.000 | -5.573 | -0.000 |
FIRSTFLOOR_PLENUM | 6.454 | -21.149 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.051 | 19.185 | 0.000 | 0.000 | 0.000 | -4.540 | -0.000 |
Total Facility | 34.263 | -70.220 | 88.944 | -897.064 | 0.000 | 0.000 | 174.817 | 203.453 | 705.434 | 425.171 | 0.000 | 3.587 | 52.321 | 0.000 | -252.225 | 0.000 | -89.802 | -378.676 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 07-AUG-04:02 | 0.00 | 0.00 | 0.00 | -44032.30 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 39157.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 07-AUG-04:02 | 0.00 | 0.00 | 0.00 | -31887.60 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 28976.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-04:02 | 0.00 | 0.00 | 0.00 | -33403.96 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 30492.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-15:52 | 0.00 | 0.00 | 0.00 | -10801.01 | 0.00 | 0.00 | 27.26 | 23.57 | 478.42 | 2263.43 | 0.00 | 47.01 | 7961.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 28-MAY-08:52 | 0.00 | 0.00 | 0.00 | -12937.26 | 0.00 | 0.00 | 15.52 | 14.92 | 302.86 | 8327.70 | 0.00 | 0.00 | 4363.93 | 0.00 | -0.00 | 0.00 | -87.67 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-13:12 | 0.00 | 0.00 | 0.00 | -16175.54 | 0.00 | 0.00 | 21.61 | 23.57 | 478.41 | 10971.90 | 0.00 | 0.00 | 4701.84 | 0.00 | -0.00 | 0.00 | -21.81 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-JUN-16:32 | 0.00 | 0.00 | 0.00 | -14051.50 | 0.00 | 0.00 | 14.95 | 14.92 | 302.86 | 6502.14 | 0.00 | 0.00 | 7303.48 | 0.00 | -0.00 | 0.00 | -86.86 | 0.00 |
PERIMETER_BOT_ZN_3 | 10-JUL-06:03 | 0.00 | 0.00 | 0.00 | -7058.06 | 0.00 | 0.00 | 146.46 | 152.99 | 637.89 | 952.48 | 0.00 | 4.07 | 5164.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-09:42 | 0.00 | 0.00 | 0.00 | -10944.50 | 0.00 | 0.00 | 15.55 | 14.92 | 302.86 | 7027.62 | 0.00 | 0.00 | 3590.59 | 0.00 | -0.00 | 0.00 | -7.05 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-11:42 | 0.00 | 0.00 | 0.00 | -13568.91 | 0.00 | 0.00 | 24.42 | 23.57 | 478.41 | 12509.58 | 0.00 | 0.00 | 547.66 | 0.00 | -0.00 | 0.00 | -14.73 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-SEP-17:02 | 0.00 | 0.00 | 0.00 | -10898.51 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 4997.32 | 0.00 | 0.00 | 5667.21 | 0.00 | -0.00 | 0.00 | -25.36 | 0.00 |
PERIMETER_MID_ZN_3 | 26-JUN-06:03 | 0.00 | 0.00 | 0.00 | -8004.08 | 0.00 | 0.00 | 144.48 | 141.46 | 637.89 | 2600.11 | 0.00 | 0.00 | 4486.91 | 0.00 | -0.00 | 0.00 | -6.76 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-07:52 | 0.00 | 0.00 | 0.00 | -13138.50 | 0.00 | 0.00 | 14.45 | 14.92 | 302.86 | 10429.31 | 0.00 | 0.00 | 2396.98 | 0.00 | -0.00 | 0.00 | -20.03 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-11:42 | 0.00 | 0.00 | 0.00 | -15371.48 | 0.00 | 0.00 | 22.91 | 23.57 | 478.41 | 12428.22 | 0.00 | 0.00 | 2445.90 | 0.00 | -0.00 | 0.00 | -27.54 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-16:31 | 0.00 | 0.00 | 0.00 | -13736.48 | 0.00 | 0.00 | 13.89 | 14.92 | 302.86 | 8730.35 | 0.00 | 0.00 | 4734.55 | 0.00 | -0.00 | 0.00 | -60.09 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:40 | 0.00 | -12016.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.09 | 11962.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 14-AUG-14:50 | 0.00 | -5309.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 5283.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 19-JUN-12:09 | 0.00 | -6323.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.15 | 6268.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-JUL-04:02 | 0.00 | 7871.78 | 0.00 | -202832.33 | 0.00 | 0.00 | 0.00 | 2375.34 | 14333.92 | 0.00 | 0.00 | 22.05 | 179525.11 | 0.00 | -1253.84 | 0.00 | -42.03 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 23221.47 | 0.00 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28096.03 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 24275.06 | 0.00 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27186.04 |
CORE_TOP | 02-JAN-04:42 | 0.00 | 0.00 | 31346.20 | 0.00 | 0.00 | 0.00 | 0.00 | 234.43 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -34022.68 |
PERIMETER_TOP_ZN_3 | 02-JAN-00:02 | 0.00 | 0.00 | 10574.85 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2752.89 | 0.00 | -896.29 | -7489.89 |
PERIMETER_TOP_ZN_2 | 02-JAN-00:02 | 0.00 | 0.00 | 11268.29 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1790.70 | 0.00 | -611.85 | -9222.92 |
PERIMETER_TOP_ZN_1 | 02-JAN-00:02 | 0.00 | 0.00 | 14086.78 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2708.08 | 0.00 | -914.57 | -11028.36 |
PERIMETER_TOP_ZN_4 | 02-JAN-00:02 | 0.00 | 0.00 | 12023.62 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1835.76 | 0.00 | -612.94 | -9932.10 |
PERIMETER_BOT_ZN_3 | 02-JAN-00:02 | 0.00 | 0.00 | 8132.49 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2798.26 | 0.00 | -488.95 | -5409.51 |
PERIMETER_BOT_ZN_2 | 02-JAN-00:02 | 0.00 | 0.00 | 8699.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1833.92 | 0.00 | -333.28 | -6889.23 |
PERIMETER_BOT_ZN_1 | 06-FEB-07:10 | 0.00 | 0.00 | 14209.12 | 0.00 | 0.00 | 0.00 | 203.04 | 227.87 | 637.88 | 0.00 | 0.00 | 0.00 | 16978.08 | 0.00 | -2381.28 | 0.00 | -29874.71 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-00:02 | 0.00 | 0.00 | 8819.16 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1870.02 | 0.00 | -332.01 | -6974.31 |
PERIMETER_MID_ZN_3 | 02-JAN-00:02 | 0.00 | 0.00 | 8910.50 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2811.38 | 0.00 | -761.28 | -5902.07 |
PERIMETER_MID_ZN_2 | 02-JAN-00:02 | 0.00 | 0.00 | 9199.14 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1830.18 | 0.00 | -516.87 | -7209.27 |
PERIMETER_MID_ZN_1 | 02-JAN-00:02 | 0.00 | 0.00 | 12299.69 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2766.21 | 0.00 | -776.65 | -9321.05 |
PERIMETER_MID_ZN_4 | 02-JAN-00:02 | 0.00 | 0.00 | 9301.54 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1874.88 | 0.00 | -516.10 | -7267.73 |
TOPFLOOR_PLENUM | 02-JAN-06:12 | 15446.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -131.71 | -15314.55 |
MIDFLOOR_PLENUM | 02-JAN-07:17 | 9559.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -100.14 | -9459.60 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 8632.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -72.07 | -8560.77 |
Total Facility | 02-JAN-05:01 | 17614.10 | 0.00 | 195469.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.34 | 14333.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29035.32 | 0.00 | -3834.56 | -196923.17 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.1923 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6603 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.7727 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.0905 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.2091 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7906 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.5961 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3332 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.3863 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3386 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.6046 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4201 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7163 | 2.7163 | 0.7660 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9730 | 1.9730 | 0.7379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1144 | 2.1144 | 0.7717 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6684 | 0.6684 | 0.1631 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7287 | 0.7287 | 0.1457 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9079 | 0.9079 | 0.1816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7897 | 0.7897 | 0.1579 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5279 | 0.5279 | 0.1615 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6016 | 0.6016 | 0.1203 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7293 | 0.7293 | 0.1619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6172 | 0.6172 | 0.1234 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5748 | 0.5748 | 0.1558 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6991 | 0.6991 | 0.1398 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8094 | 0.8094 | 0.1619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7164 | 0.7164 | 0.1433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.1923 | 4.6603 | 5.1923 | 1.3332 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.7727 | 4.0905 | 4.7727 | 1.3386 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.2091 | 4.7906 | 5.2091 | 1.4201 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3581 | 1.3581 | 0.7660 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9865 | 0.9865 | 0.7379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0572 | 1.0572 | 0.7717 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3342 | 0.3342 | 0.1631 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3644 | 0.3644 | 0.1457 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4539 | 0.4539 | 0.1816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3949 | 0.3949 | 0.1579 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2639 | 0.2639 | 0.1615 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3008 | 0.3008 | 0.1203 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3647 | 0.3647 | 0.1619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3086 | 0.3086 | 0.1234 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2874 | 0.2874 | 0.1558 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3496 | 0.3496 | 0.1398 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4047 | 0.4047 | 0.1619 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3582 | 0.3582 | 0.1433 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.5961 | 1.3332 | 1.3332 | 1.3332 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.3863 | 1.3386 | 1.3386 | 1.3386 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.6046 | 1.4201 | 1.4201 | 1.4201 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 364.33 |
Number of hours cooling loads not met | 120.33 |
Number of hours not met | 484.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 154.61 | 200766.58 | 138.80 | 92594.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 199.52 | 75494.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 203.45 | 21377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 49.81 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.66 | 833.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 96.14 | 25644.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 107.33 | 9472.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1420.64 |
Natural Gas | 0.00 | 246.12 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1666.76 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 40.84 |
Space Heating | 31.03 |
Space Cooling | 40.05 |
Fans (All) | 19.30 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 285.14 |
Subtotal | 285.14 |
Natural Gas [MJ/m2] | |
Space Heating | 27.86 |
Service Water Heating | 21.54 |
Miscellaneous (All) | 49.40 |
Subtotal | 49.40 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.21 |
Space Heating | 17.60 |
Space Cooling | 11.97 |
Fans (All) | 5.77 |
Service Water Heating | 6.44 |
Receptacle Equipment | 42.32 |
Miscellaneous | 3.69 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8715.83 | 44.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8749.50 | 10.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8723.00 | 37.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8672.67 | 87.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8674.50 | 85.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8640.17 | 119.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8708.83 | 51.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8714.83 | 45.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8686.67 | 73.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8733.33 | 26.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8680.33 | 79.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8687.00 | 73.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8649.33 | 110.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8631.17 | 128.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8631.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 128.83 | 0.00 | 0.00 | 0.00 |
Average | 8705.10 | 54.90 | 0.00 | 0.00 | 0.00 |
Sum | 156691.83 | 988.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128275.33 | 28.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128300.33 | 3.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24905.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 28.67 | 0.00 | 0.00 | 0.00 |
Average | 34141.35 | 1.98 | 0.00 | 0.00 | 0.00 |
Sum | 614544.33 | 35.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8080.67 | 679.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8283.33 | 476.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8411.33 | 348.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8106.67 | 653.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8126.00 | 634.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8095.67 | 664.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8101.17 | 658.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8283.17 | 476.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8200.83 | 559.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7816.67 | 943.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8118.50 | 641.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8081.17 | 678.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8096.50 | 663.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8041.17 | 718.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8046.00 | 714.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7625.17 | 1134.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8153.83 | 606.17 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8115.00 | 645.00 | 0.00 | 0.00 | 0.00 |
Min | 7625.17 | 348.67 | 0.00 | 0.00 | 0.00 |
Max | 8411.33 | 1134.83 | 0.00 | 0.00 | 0.00 |
Average | 8099.05 | 660.95 | 0.00 | 0.00 | 0.00 |
Sum | 145782.83 | 11897.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 127969.00 | 335.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128093.67 | 210.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128044.00 | 260.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24844.33 | 64.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14005.50 | 10.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24869.00 | 40.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14015.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24862.17 | 46.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14000.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 22824.67 | 2084.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14007.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24841.67 | 67.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10130.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24847.17 | 61.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14006.50 | 9.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128093.67 | 2084.33 | 0.00 | 0.00 | 0.00 |
Average | 33964.43 | 178.91 | 0.00 | 0.00 | 0.00 |
Sum | 611359.67 | 3220.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.887619E+10 | 10511.27 | 27-JAN-08:40 | 2.57 | 0.54 | 0.179851E+10 | 2606.62 | 26-JAN-14:39 | 2.57 | 0.54 |
February | 0.905625E+10 | 10921.33 | 24-FEB-08:50 | 5.00 | 4.05 | 0.170424E+10 | 2606.62 | 23-FEB-10:09 | 5.00 | 4.05 |
March | 0.131126E+11 | 17823.59 | 31-MAR-07:05 | 5.68 | 5.68 | 0.212293E+10 | 2608.37 | 29-MAR-09:30 | 5.68 | 5.68 |
April | 0.149401E+11 | 33540.89 | 11-APR-05:03 | 6.10 | 1.72 | 0.190094E+10 | 2606.66 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.205960E+11 | 39697.19 | 23-MAY-05:03 | 15.60 | 14.95 | 0.207307E+10 | 2606.77 | 15-MAY-13:00 | 15.60 | 14.95 |
June | 0.247921E+11 | 41596.24 | 26-JUN-04:03 | 20.60 | 16.77 | 0.207022E+10 | 2606.67 | 23-JUN-09:09 | 20.60 | 16.77 |
July | 0.254910E+11 | 43316.07 | 24-JUL-04:02 | 21.02 | 20.27 | 0.192444E+10 | 2606.66 | 12-JUL-13:00 | 21.02 | 20.27 |
August | 0.278342E+11 | 44043.04 | 07-AUG-04:02 | 18.48 | 17.13 | 0.216068E+10 | 2606.67 | 08-AUG-13:20 | 26.50 | 16.97 |
September | 0.232152E+11 | 41397.60 | 06-SEP-04:03 | 21.20 | 18.83 | 0.191749E+10 | 2606.72 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.211400E+11 | 39745.58 | 14-OCT-05:03 | 14.40 | 13.43 | 0.199177E+10 | 2606.73 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.135785E+11 | 20872.11 | 03-NOV-05:03 | 9.22 | 6.42 | 0.194635E+10 | 2607.78 | 15-NOV-10:39 | 6.83 | 3.77 |
December | 0.105399E+11 | 13104.27 | 20-DEC-08:20 | 3.50 | 2.24 | 0.186027E+10 | 2606.64 | 15-DEC-10:20 | 3.50 | 2.24 |
Annual Sum or Average | 0.213172E+12 | 0.234709E+11 | ||||||||
Minimum of Months | 0.887619E+10 | 10511.27 | 2.57 | 0.54 | 0.170424E+10 | 2606.62 | 2.57 | 0.54 | ||
Maximum of Months | 0.278342E+11 | 44043.04 | 21.20 | 20.27 | 0.216068E+10 | 2608.37 | 26.50 | 20.27 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5719262.44 | 452.10 | 17-JAN-14:50 | 10.68 | 5.08 | 0.00 | 0.00 | 01-JAN-00:10 | 10.68 | 5.08 |
February | 29026492.48 | 812.57 | 18-FEB-16:20 | 6.33 | 2.83 | 0.00 | 0.00 | 01-FEB-00:10 | 6.33 | 2.83 |
March | 0.544961E+09 | 2637.24 | 03-MAR-14:30 | 15.00 | 8.51 | 0.00 | 0.00 | 01-MAR-00:10 | 15.00 | 8.51 |
April | 0.142367E+10 | 6882.96 | 07-APR-14:30 | 25.85 | 15.95 | 0.00 | 0.00 | 01-APR-00:10 | 25.85 | 15.95 |
May | 0.330328E+10 | 10708.46 | 30-MAY-14:10 | 29.22 | 16.98 | 0.00 | 0.00 | 01-MAY-00:10 | 29.22 | 16.98 |
June | 0.571959E+10 | 12017.36 | 19-JUN-13:40 | 34.60 | 23.77 | 0.00 | 0.00 | 01-JUN-00:10 | 34.60 | 23.77 |
July | 0.711521E+10 | 11198.86 | 10-JUL-13:50 | 32.70 | 20.82 | 0.00 | 0.00 | 01-JUL-00:10 | 32.70 | 20.82 |
August | 0.763269E+10 | 10708.50 | 01-AUG-14:50 | 30.78 | 22.82 | 0.00 | 0.00 | 01-AUG-00:10 | 30.78 | 22.82 |
September | 0.378156E+10 | 9476.90 | 01-SEP-14:50 | 30.68 | 17.45 | 0.00 | 0.00 | 01-SEP-00:10 | 30.68 | 17.45 |
October | 0.204745E+10 | 6588.01 | 04-OCT-14:50 | 23.98 | 19.09 | 0.00 | 0.00 | 01-OCT-00:10 | 23.98 | 19.09 |
November | 0.222778E+09 | 2383.85 | 04-NOV-13:10 | 17.62 | 12.77 | 0.00 | 0.00 | 01-NOV-00:10 | 17.62 | 12.77 |
December | 2891517.82 | 392.39 | 20-DEC-13:03 | 9.50 | 5.64 | 0.00 | 0.00 | 01-DEC-00:10 | 9.50 | 5.64 |
Annual Sum or Average | 0.318288E+11 | 0.00 | ||||||||
Minimum of Months | 2891517.82 | 392.39 | 6.33 | 2.83 | 0.00 | 0.00 | 6.33 | 2.83 | ||
Maximum of Months | 0.763269E+10 | 12017.36 | 34.60 | 23.77 | 0.00 | 0.00 | 34.60 | 23.77 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9722454.81 | 1558.63 | 05-JAN-05:01 | -7.8 | -9.6 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -9.6 |
February | 13573044.34 | 1297.00 | 03-FEB-06:01 | -7.8 | -9.5 | 0.00 | 0.00 | 01-FEB-00:10 | -7.8 | -9.5 |
March | 0.154891E+09 | 2386.66 | 29-MAR-06:01 | 1.88 | 0.26 | 0.00 | 0.00 | 01-MAR-00:10 | 1.88 | 0.26 |
April | 0.517583E+09 | 2010.87 | 10-APR-16:00 | 20.00 | 11.13 | 0.00 | 0.00 | 01-APR-00:10 | 20.00 | 11.13 |
May | 0.144515E+10 | 4593.01 | 30-MAY-14:40 | 28.67 | 17.12 | 0.00 | 0.00 | 01-MAY-00:10 | 28.67 | 17.12 |
June | 0.313997E+10 | 4745.97 | 19-JUN-15:10 | 32.93 | 23.30 | 0.00 | 0.00 | 01-JUN-00:10 | 32.93 | 23.30 |
July | 0.402536E+10 | 5211.14 | 10-JUL-15:10 | 32.93 | 20.87 | 0.00 | 0.00 | 01-JUL-00:10 | 32.93 | 20.87 |
August | 0.438511E+10 | 5309.25 | 14-AUG-14:50 | 28.58 | 23.14 | 0.00 | 0.00 | 01-AUG-00:10 | 28.58 | 23.14 |
September | 0.233644E+10 | 4795.57 | 05-SEP-15:20 | 25.93 | 21.57 | 0.00 | 0.00 | 01-SEP-00:10 | 25.93 | 21.57 |
October | 0.107026E+10 | 2823.11 | 04-OCT-15:50 | 22.98 | 19.12 | 0.00 | 0.00 | 01-OCT-00:10 | 22.98 | 19.12 |
November | 0.130778E+09 | 848.37 | 04-NOV-06:03 | 9.90 | 8.72 | 0.00 | 0.00 | 01-NOV-00:10 | 9.90 | 8.72 |
December | 13125313.00 | 827.57 | 15-DEC-06:01 | -3.4 | -5.5 | 0.00 | 0.00 | 01-DEC-00:10 | -3.4 | -5.5 |
Annual Sum or Average | 0.172420E+11 | 0.00 | ||||||||
Minimum of Months | 9722454.81 | 827.57 | -7.8 | -9.6 | 0.00 | 0.00 | -7.8 | -9.6 | ||
Maximum of Months | 0.438511E+10 | 5309.25 | 32.93 | 23.30 | 0.00 | 0.00 | 32.93 | 23.30 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60797790.11 | 1946.30 | 11-JAN-17:10 | -5.1 | -8.2 | 0.00 | 0.00 | 01-JAN-00:10 | -5.1 | -8.2 |
February | 77069540.10 | 2464.66 | 03-FEB-07:10 | -7.7 | -9.4 | 0.00 | 0.00 | 01-FEB-00:10 | -7.7 | -9.4 |
March | 0.315719E+09 | 2740.15 | 29-MAR-06:01 | 1.88 | 0.26 | 0.00 | 0.00 | 01-MAR-00:10 | 1.88 | 0.26 |
April | 0.792160E+09 | 2410.85 | 14-APR-06:01 | 5.00 | 4.24 | 0.00 | 0.00 | 01-APR-00:10 | 5.00 | 4.24 |
May | 0.185999E+10 | 4686.75 | 30-MAY-12:07 | 29.50 | 17.65 | 0.00 | 0.00 | 01-MAY-00:10 | 29.50 | 17.65 |
June | 0.350819E+10 | 6324.35 | 19-JUN-12:09 | 36.42 | 24.23 | 0.00 | 0.00 | 01-JUN-00:10 | 36.42 | 24.23 |
July | 0.433482E+10 | 5576.94 | 13-JUL-12:08 | 32.43 | 22.59 | 0.00 | 0.00 | 01-JUL-00:10 | 32.43 | 22.59 |
August | 0.489283E+10 | 5339.39 | 14-AUG-16:00 | 27.80 | 22.71 | 0.00 | 0.00 | 01-AUG-00:10 | 27.80 | 22.71 |
September | 0.303800E+10 | 5089.00 | 05-SEP-07:10 | 21.88 | 18.77 | 0.00 | 0.00 | 01-SEP-00:10 | 21.88 | 18.77 |
October | 0.188450E+10 | 3528.34 | 04-OCT-16:00 | 22.80 | 19.11 | 0.00 | 0.00 | 01-OCT-00:10 | 22.80 | 19.11 |
November | 0.301347E+09 | 1665.45 | 16-NOV-07:01 | 3.98 | 2.32 | 0.00 | 0.00 | 01-NOV-00:10 | 3.98 | 2.32 |
December | 83967505.67 | 2126.71 | 22-DEC-07:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-DEC-00:10 | -4.9 | -6.9 |
Annual Sum or Average | 0.211494E+11 | 0.00 | ||||||||
Minimum of Months | 60797790.11 | 1665.45 | -7.7 | -9.4 | 0.00 | 0.00 | -7.7 | -9.4 | ||
Maximum of Months | 0.489283E+10 | 6324.35 | 36.42 | 24.23 | 0.00 | 0.00 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.556311E+10 | 6582.58 | 20-JAN-16:55 | 5.60 | 3.19 | 0.154455E+10 | 2293.72 | 20-JAN-14:00 | 5.60 | 3.19 |
February | 0.581234E+10 | 6585.71 | 02-FEB-17:00 | 2.80 | -3.1 | 0.142792E+10 | 2303.77 | 02-FEB-14:00 | 2.80 | -3.1 |
March | 0.885443E+10 | 7832.28 | 29-MAR-16:00 | 7.20 | 4.88 | 0.187127E+10 | 2574.11 | 29-MAR-13:00 | 7.20 | 4.88 |
April | 0.985333E+10 | 13029.86 | 10-APR-16:00 | 20.00 | 11.13 | 0.179259E+10 | 2606.63 | 07-APR-13:09 | 20.00 | 11.13 |
May | 0.138599E+11 | 29944.46 | 30-MAY-04:03 | 17.80 | 14.10 | 0.204570E+10 | 2606.72 | 15-MAY-13:00 | 17.80 | 14.10 |
June | 0.172279E+11 | 30417.35 | 26-JUN-04:03 | 20.60 | 16.77 | 0.206569E+10 | 2606.67 | 12-JUN-09:09 | 20.60 | 16.77 |
July | 0.185866E+11 | 30633.24 | 24-JUL-04:02 | 21.02 | 20.27 | 0.192101E+10 | 2606.65 | 17-JUL-09:20 | 21.02 | 20.27 |
August | 0.197276E+11 | 31893.05 | 07-AUG-04:02 | 18.48 | 17.13 | 0.215781E+10 | 2606.66 | 23-AUG-13:09 | 25.60 | 17.07 |
September | 0.154028E+11 | 30911.86 | 05-SEP-04:02 | 20.52 | 17.93 | 0.190842E+10 | 2606.69 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.128258E+11 | 19245.81 | 06-OCT-05:03 | 19.40 | 18.22 | 0.196494E+10 | 2606.71 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.802198E+10 | 9882.48 | 03-NOV-16:00 | 15.00 | 10.26 | 0.174009E+10 | 2606.58 | 03-NOV-13:09 | 15.00 | 10.26 |
December | 0.688487E+10 | 6748.51 | 21-DEC-16:20 | 2.43 | -2.4 | 0.156026E+10 | 2366.62 | 21-DEC-14:00 | 2.43 | -2.4 |
Annual Sum or Average | 0.142621E+12 | 0.220002E+11 | ||||||||
Minimum of Months | 0.556311E+10 | 6582.58 | 2.43 | -3.1 | 0.142792E+10 | 2293.72 | 2.43 | -3.1 | ||
Maximum of Months | 0.197276E+11 | 31893.05 | 21.02 | 20.27 | 0.215781E+10 | 2606.72 | 25.60 | 20.27 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387781E+10 | 6465.29 | 20-JAN-16:40 | 6.13 | 3.40 | 0.148412E+10 | 2187.67 | 20-JAN-16:49 | 5.87 | 3.30 |
February | 0.397765E+10 | 6545.76 | 02-FEB-17:00 | 2.80 | -3.1 | 0.136270E+10 | 2228.00 | 02-FEB-14:00 | 2.80 | -3.1 |
March | 0.774190E+10 | 7836.97 | 29-MAR-16:00 | 7.20 | 4.88 | 0.176314E+10 | 2537.14 | 28-MAR-13:00 | 7.20 | 4.88 |
April | 0.929165E+10 | 13936.96 | 10-APR-15:50 | 20.00 | 11.21 | 0.171788E+10 | 2606.63 | 07-APR-13:09 | 20.00 | 11.21 |
May | 0.139088E+11 | 30326.11 | 30-MAY-05:03 | 18.17 | 14.31 | 0.201148E+10 | 2606.73 | 15-MAY-13:00 | 18.17 | 14.31 |
June | 0.179573E+11 | 31157.76 | 23-JUN-05:03 | 20.68 | 16.42 | 0.206170E+10 | 2606.67 | 23-JUN-09:09 | 27.25 | 18.76 |
July | 0.197798E+11 | 33251.03 | 24-JUL-04:02 | 21.02 | 20.27 | 0.192095E+10 | 2606.65 | 11-JUL-13:50 | 21.02 | 20.27 |
August | 0.206181E+11 | 33409.29 | 07-AUG-04:02 | 18.48 | 17.13 | 0.215586E+10 | 2606.69 | 29-AUG-09:20 | 24.23 | 18.51 |
September | 0.150338E+11 | 32667.05 | 05-SEP-04:02 | 20.52 | 17.93 | 0.189252E+10 | 2606.68 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.116728E+11 | 14836.43 | 04-OCT-15:50 | 22.98 | 19.12 | 0.190150E+10 | 2606.69 | 06-OCT-09:30 | 18.05 | 16.75 |
November | 0.659849E+10 | 8390.28 | 03-NOV-16:00 | 15.00 | 10.26 | 0.161209E+10 | 2561.37 | 03-NOV-13:00 | 15.00 | 10.26 |
December | 0.464143E+10 | 6460.70 | 21-DEC-16:00 | 2.80 | -2.2 | 0.145806E+10 | 2224.20 | 21-DEC-14:00 | 2.80 | -2.2 |
Annual Sum or Average | 0.135100E+12 | 0.213420E+11 | ||||||||
Minimum of Months | 0.387781E+10 | 6460.70 | 2.80 | -3.1 | 0.136270E+10 | 2187.67 | 2.80 | -3.1 | ||
Maximum of Months | 0.206181E+11 | 33409.29 | 22.98 | 20.27 | 0.215586E+10 | 2606.73 | 27.25 | 20.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102711E+09 | 1090.80 | 19-JAN-15:00 | 8.90 | 3.60 | 0.304617E+09 | 409.83 | 19-JAN-14:00 | 8.90 | 3.60 |
February | 0.132090E+09 | 1122.90 | 24-FEB-15:50 | 7.88 | 1.88 | 0.276969E+09 | 414.76 | 24-FEB-14:00 | 7.88 | 1.88 |
March | 0.832326E+09 | 1600.20 | 28-MAR-14:10 | 13.22 | 8.42 | 0.347951E+09 | 529.23 | 28-MAR-13:00 | 13.22 | 8.42 |
April | 0.166783E+10 | 3728.48 | 07-APR-15:20 | 25.60 | 16.01 | 0.344842E+09 | 549.50 | 07-APR-13:09 | 25.60 | 16.01 |
May | 0.336149E+10 | 7291.59 | 29-MAY-14:23 | 25.85 | 17.23 | 0.418280E+09 | 549.52 | 15-MAY-13:00 | 25.85 | 17.23 |
June | 0.527196E+10 | 9022.33 | 26-JUN-06:03 | 21.97 | 17.81 | 0.434834E+09 | 549.67 | 19-JUN-13:50 | 21.97 | 17.81 |
July | 0.621995E+10 | 9675.17 | 10-JUL-04:02 | 26.10 | 21.38 | 0.405900E+09 | 549.51 | 11-JUL-13:50 | 28.72 | 17.86 |
August | 0.619438E+10 | 10801.61 | 13-AUG-15:52 | 30.00 | 20.46 | 0.454548E+09 | 549.51 | 08-AUG-13:39 | 30.00 | 20.46 |
September | 0.366569E+10 | 5904.03 | 01-SEP-14:30 | 30.85 | 17.41 | 0.394711E+09 | 549.50 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.231094E+10 | 3940.79 | 04-OCT-14:00 | 24.40 | 18.95 | 0.383917E+09 | 549.49 | 12-OCT-13:00 | 20.60 | 17.37 |
November | 0.745106E+09 | 1589.90 | 03-NOV-15:00 | 17.20 | 10.98 | 0.318417E+09 | 523.47 | 03-NOV-13:00 | 17.20 | 10.98 |
December | 0.113255E+09 | 1119.21 | 20-DEC-14:00 | 10.00 | 5.91 | 0.294597E+09 | 416.11 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.306177E+11 | 0.437958E+10 | ||||||||
Minimum of Months | 0.102711E+09 | 1090.80 | 7.88 | 1.88 | 0.276969E+09 | 409.83 | 7.88 | 1.88 | ||
Maximum of Months | 0.621995E+10 | 10801.61 | 30.85 | 21.38 | 0.454548E+09 | 549.67 | 30.00 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184045E+09 | 1166.07 | 19-JAN-10:20 | 7.80 | 4.36 | 0.193939E+09 | 290.49 | 19-JAN-10:30 | 7.80 | 4.48 |
February | 0.285370E+09 | 1218.65 | 22-FEB-10:10 | 0.87 | -3.0 | 0.177140E+09 | 300.14 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.103678E+10 | 2970.25 | 29-MAR-09:40 | 6.33 | 3.26 | 0.234002E+09 | 347.87 | 29-MAR-09:00 | 6.70 | 3.39 |
April | 0.188951E+10 | 5628.73 | 28-APR-09:00 | 16.10 | 8.85 | 0.229026E+09 | 347.89 | 26-APR-09:00 | 16.10 | 8.85 |
May | 0.357940E+10 | 12937.26 | 28-MAY-08:52 | 20.60 | 12.82 | 0.266661E+09 | 348.35 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.469337E+10 | 12797.33 | 04-JUN-09:12 | 23.67 | 12.90 | 0.275213E+09 | 348.34 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.544853E+10 | 12774.79 | 02-JUL-08:42 | 25.40 | 21.60 | 0.257060E+09 | 348.81 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.601181E+10 | 12190.42 | 27-AUG-09:23 | 25.25 | 21.77 | 0.288076E+09 | 348.48 | 18-AUG-09:39 | 25.25 | 21.77 |
September | 0.360952E+10 | 12625.49 | 04-SEP-09:12 | 24.47 | 18.42 | 0.251032E+09 | 348.49 | 06-SEP-09:50 | 26.52 | 19.55 |
October | 0.244977E+10 | 5058.13 | 05-OCT-09:20 | 19.27 | 16.99 | 0.252162E+09 | 347.88 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.809241E+09 | 1566.06 | 02-NOV-09:40 | 11.83 | 6.09 | 0.206806E+09 | 347.86 | 03-NOV-09:00 | 13.30 | 8.39 |
December | 0.276182E+09 | 1192.97 | 20-DEC-09:50 | 7.93 | 4.87 | 0.187450E+09 | 294.95 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.302735E+11 | 0.281856E+10 | ||||||||
Minimum of Months | 0.184045E+09 | 1166.07 | 0.87 | -3.0 | 0.177140E+09 | 290.49 | 1.13 | -2.8 | ||
Maximum of Months | 0.601181E+10 | 12937.26 | 25.40 | 21.77 | 0.288076E+09 | 348.81 | 30.60 | 21.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.826425E+09 | 5222.06 | 19-JAN-13:30 | 9.40 | 3.94 | 0.333497E+09 | 549.49 | 30-JAN-14:20 | 2.80 | -1.2 |
February | 0.107821E+10 | 5614.27 | 02-FEB-14:10 | 5.50 | -1.1 | 0.308500E+09 | 550.14 | 17-FEB-14:20 | 6.50 | 2.07 |
March | 0.236378E+10 | 8058.60 | 03-MAR-13:25 | 14.70 | 8.33 | 0.388177E+09 | 549.50 | 01-MAR-14:00 | 14.70 | 8.33 |
April | 0.297723E+10 | 9286.44 | 07-APR-12:30 | 26.15 | 15.90 | 0.359503E+09 | 549.51 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.445244E+10 | 15581.82 | 29-MAY-13:43 | 26.28 | 17.36 | 0.417915E+09 | 549.99 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.610161E+10 | 12249.53 | 04-JUN-13:13 | 24.40 | 13.83 | 0.434193E+09 | 549.80 | 19-JUN-13:39 | 34.60 | 23.77 |
July | 0.730028E+10 | 15636.17 | 04-JUL-12:53 | 27.80 | 18.77 | 0.405886E+09 | 549.97 | 10-JUL-13:00 | 32.80 | 20.89 |
August | 0.889384E+10 | 15866.53 | 13-AUG-12:32 | 30.93 | 19.36 | 0.454818E+09 | 549.97 | 17-AUG-13:50 | 31.10 | 24.82 |
September | 0.651263E+10 | 16175.65 | 04-SEP-13:12 | 26.10 | 18.36 | 0.397763E+09 | 558.38 | 28-SEP-13:20 | 23.17 | 13.55 |
October | 0.582739E+10 | 15936.95 | 22-OCT-12:43 | 22.02 | 16.80 | 0.403107E+09 | 549.88 | 13-OCT-13:39 | 22.02 | 16.80 |
November | 0.203000E+10 | 9823.95 | 02-NOV-13:10 | 15.68 | 8.29 | 0.355798E+09 | 549.58 | 02-NOV-13:00 | 16.10 | 8.71 |
December | 0.106996E+10 | 5229.57 | 21-DEC-13:30 | 3.05 | -1.7 | 0.327381E+09 | 549.49 | 14-DEC-14:09 | 3.05 | -1.7 |
Annual Sum or Average | 0.494338E+11 | 0.458654E+10 | ||||||||
Minimum of Months | 0.826425E+09 | 5222.06 | 3.05 | -1.7 | 0.308500E+09 | 549.49 | 2.80 | -1.7 | ||
Maximum of Months | 0.889384E+10 | 16175.65 | 30.93 | 19.36 | 0.454818E+09 | 558.38 | 34.60 | 24.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219844E+09 | 1461.02 | 19-JAN-15:50 | 8.40 | 3.05 | 0.195453E+09 | 313.46 | 19-JAN-15:00 | 8.30 | 2.94 |
February | 0.297221E+09 | 1604.27 | 22-FEB-16:30 | 3.85 | -0.7 | 0.179876E+09 | 336.99 | 22-FEB-16:40 | 3.67 | -0.7 |
March | 0.112013E+10 | 4784.64 | 29-MAR-16:00 | 7.20 | 4.88 | 0.227577E+09 | 347.84 | 03-MAR-14:00 | 7.20 | 4.88 |
April | 0.201206E+10 | 11177.31 | 09-APR-17:03 | 15.92 | 13.68 | 0.216493E+09 | 347.85 | 26-APR-13:00 | 18.30 | 12.92 |
May | 0.351437E+10 | 11910.66 | 21-MAY-15:13 | 20.37 | 13.43 | 0.258991E+09 | 347.87 | 15-MAY-13:00 | 20.37 | 13.43 |
June | 0.490507E+10 | 14052.56 | 04-JUN-16:32 | 21.47 | 14.55 | 0.273894E+09 | 347.86 | 22-JUN-13:30 | 29.15 | 17.46 |
July | 0.544357E+10 | 13854.31 | 02-JUL-16:02 | 24.90 | 20.78 | 0.256553E+09 | 347.87 | 11-JUL-13:50 | 28.72 | 17.86 |
August | 0.603179E+10 | 13780.70 | 13-AUG-15:52 | 30.00 | 20.46 | 0.287207E+09 | 347.86 | 08-AUG-13:39 | 30.00 | 20.46 |
September | 0.365126E+10 | 13502.20 | 10-SEP-15:32 | 23.67 | 13.25 | 0.246828E+09 | 347.86 | 15-SEP-13:00 | 22.80 | 15.50 |
October | 0.266666E+10 | 6983.11 | 04-OCT-15:30 | 23.35 | 19.12 | 0.240194E+09 | 347.85 | 12-OCT-13:00 | 20.60 | 17.37 |
November | 0.755748E+09 | 3140.66 | 03-NOV-15:30 | 16.10 | 10.65 | 0.202662E+09 | 347.80 | 03-NOV-13:00 | 16.10 | 10.65 |
December | 0.249041E+09 | 1413.55 | 08-DEC-15:40 | 6.30 | 2.04 | 0.188800E+09 | 306.06 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.308667E+11 | 0.277453E+10 | ||||||||
Minimum of Months | 0.219844E+09 | 1413.55 | 3.85 | -0.7 | 0.179876E+09 | 306.06 | 3.67 | -0.7 | ||
Maximum of Months | 0.603179E+10 | 14052.56 | 30.00 | 20.78 | 0.287207E+09 | 347.87 | 30.00 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183804E+09 | 1098.03 | 20-JAN-14:50 | 7.70 | 3.92 | 0.305310E+09 | 414.16 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.156506E+09 | 1106.75 | 24-FEB-14:10 | 9.22 | 3.12 | 0.277990E+09 | 415.81 | 24-FEB-14:20 | 9.03 | 2.95 |
March | 0.876356E+09 | 1416.78 | 28-MAR-14:00 | 13.30 | 8.41 | 0.343602E+09 | 488.19 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.149191E+10 | 1987.66 | 10-APR-14:00 | 20.60 | 10.45 | 0.337413E+09 | 549.48 | 10-APR-13:00 | 20.60 | 10.45 |
May | 0.255585E+10 | 4182.29 | 30-MAY-14:00 | 29.40 | 16.93 | 0.412847E+09 | 549.51 | 15-MAY-13:00 | 29.40 | 16.93 |
June | 0.410072E+10 | 5814.29 | 26-JUN-06:03 | 21.97 | 17.81 | 0.434177E+09 | 549.50 | 23-JUN-09:09 | 21.97 | 17.81 |
July | 0.513313E+10 | 7057.72 | 10-JUL-06:03 | 26.20 | 20.78 | 0.405181E+09 | 549.50 | 12-JUL-13:00 | 28.30 | 19.52 |
August | 0.543692E+10 | 6508.55 | 14-AUG-06:03 | 23.48 | 21.76 | 0.454637E+09 | 549.50 | 23-AUG-13:09 | 25.60 | 17.07 |
September | 0.364497E+10 | 4833.46 | 05-SEP-13:10 | 26.60 | 21.00 | 0.400192E+09 | 549.51 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.259569E+10 | 3516.50 | 05-OCT-14:00 | 23.30 | 18.86 | 0.402857E+09 | 549.50 | 16-OCT-09:30 | 17.25 | 14.25 |
November | 0.128353E+10 | 1608.03 | 03-NOV-14:10 | 17.70 | 10.72 | 0.337723E+09 | 535.47 | 03-NOV-13:00 | 17.70 | 10.72 |
December | 0.414378E+09 | 1188.32 | 20-DEC-14:10 | 9.72 | 5.77 | 0.297147E+09 | 434.16 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.278737E+11 | 0.440908E+10 | ||||||||
Minimum of Months | 0.156506E+09 | 1098.03 | 7.70 | 3.12 | 0.277990E+09 | 414.16 | 7.80 | 2.95 | ||
Maximum of Months | 0.543692E+10 | 7057.72 | 29.40 | 21.76 | 0.454637E+09 | 549.51 | 29.40 | 19.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237879E+09 | 974.76 | 27-JAN-10:20 | 4.60 | 1.51 | 0.195617E+09 | 293.28 | 27-JAN-10:30 | 4.70 | 1.53 |
February | 0.311507E+09 | 990.02 | 22-FEB-10:20 | 1.13 | -2.8 | 0.178567E+09 | 296.78 | 22-FEB-10:30 | 1.40 | -2.7 |
March | 0.100451E+10 | 1888.46 | 29-MAR-09:30 | 6.15 | 3.19 | 0.234476E+09 | 348.11 | 29-MAR-09:30 | 6.15 | 3.19 |
April | 0.154431E+10 | 3755.82 | 28-APR-09:20 | 16.47 | 9.08 | 0.231210E+09 | 347.88 | 26-APR-09:00 | 16.47 | 9.08 |
May | 0.271207E+10 | 8396.63 | 29-MAY-09:02 | 26.20 | 16.88 | 0.267624E+09 | 348.12 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.382233E+10 | 10269.26 | 04-JUN-09:52 | 24.40 | 12.91 | 0.275551E+09 | 348.13 | 26-JUN-09:00 | 26.10 | 20.11 |
July | 0.463271E+10 | 8897.27 | 02-JUL-09:22 | 25.85 | 21.74 | 0.257094E+09 | 348.46 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.550052E+10 | 8388.35 | 27-AUG-10:02 | 26.28 | 21.80 | 0.288418E+09 | 348.31 | 18-AUG-09:30 | 26.28 | 21.80 |
September | 0.358426E+10 | 10944.79 | 04-SEP-09:42 | 25.32 | 18.17 | 0.254710E+09 | 348.10 | 06-SEP-09:30 | 26.15 | 19.35 |
October | 0.267949E+10 | 4624.32 | 05-OCT-09:30 | 19.45 | 17.11 | 0.261585E+09 | 347.89 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.112401E+10 | 2051.93 | 03-NOV-09:30 | 13.05 | 8.24 | 0.224270E+09 | 347.87 | 02-NOV-09:09 | 13.05 | 8.24 |
December | 0.525794E+09 | 1091.53 | 20-DEC-09:50 | 7.93 | 4.87 | 0.193175E+09 | 314.83 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.276794E+11 | 0.286230E+10 | ||||||||
Minimum of Months | 0.237879E+09 | 974.76 | 1.13 | -2.8 | 0.178567E+09 | 293.28 | 1.40 | -2.7 | ||
Maximum of Months | 0.550052E+10 | 10944.79 | 26.28 | 21.80 | 0.288418E+09 | 348.46 | 30.60 | 21.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237865E+09 | 1485.14 | 07-JAN-14:20 | 0.60 | -4.4 | 0.291685E+09 | 490.42 | 19-JAN-14:39 | 9.07 | 3.63 |
February | 0.297197E+09 | 1710.95 | 25-FEB-13:20 | 2.97 | -1.8 | 0.266422E+09 | 476.28 | 02-FEB-14:39 | 2.97 | -1.8 |
March | 0.857038E+09 | 2579.30 | 03-MAR-14:10 | 15.00 | 8.59 | 0.344873E+09 | 549.50 | 03-MAR-14:09 | 15.00 | 8.59 |
April | 0.145938E+10 | 6840.18 | 07-APR-12:00 | 25.60 | 15.40 | 0.331393E+09 | 549.51 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.260426E+10 | 10801.27 | 30-MAY-12:00 | 29.40 | 17.58 | 0.392247E+09 | 579.12 | 30-MAY-12:09 | 29.50 | 17.65 |
June | 0.483966E+10 | 13137.95 | 19-JUN-12:00 | 36.70 | 24.28 | 0.429558E+09 | 716.59 | 19-JUN-12:09 | 36.42 | 24.23 |
July | 0.703814E+10 | 12266.81 | 07-JUL-12:00 | 33.90 | 23.31 | 0.406799E+09 | 662.13 | 07-JUL-12:09 | 33.72 | 23.31 |
August | 0.907236E+10 | 12596.84 | 20-AUG-12:02 | 26.88 | 15.51 | 0.457485E+09 | 656.15 | 18-AUG-12:09 | 26.88 | 15.51 |
September | 0.605417E+10 | 13568.70 | 04-SEP-11:42 | 26.02 | 17.75 | 0.399036E+09 | 620.91 | 01-SEP-12:09 | 26.02 | 17.75 |
October | 0.493629E+10 | 12809.30 | 22-OCT-12:13 | 21.47 | 16.46 | 0.404091E+09 | 564.82 | 04-OCT-13:20 | 21.47 | 16.46 |
November | 0.133223E+10 | 7195.23 | 02-NOV-12:07 | 15.10 | 8.04 | 0.333197E+09 | 549.51 | 08-NOV-14:50 | 13.68 | 11.16 |
December | 0.532408E+09 | 2818.32 | 02-DEC-14:00 | 6.70 | 1.42 | 0.294156E+09 | 522.64 | 18-DEC-14:50 | 6.38 | 2.66 |
Annual Sum or Average | 0.392610E+11 | 0.435094E+10 | ||||||||
Minimum of Months | 0.237865E+09 | 1485.14 | 0.60 | -4.4 | 0.266422E+09 | 476.28 | 2.97 | -1.8 | ||
Maximum of Months | 0.907236E+10 | 13568.70 | 36.70 | 24.28 | 0.457485E+09 | 716.59 | 36.42 | 24.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242408E+09 | 1143.97 | 20-JAN-16:00 | 7.20 | 3.80 | 0.196154E+09 | 313.67 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.280490E+09 | 1202.42 | 22-FEB-16:30 | 3.85 | -0.7 | 0.179775E+09 | 326.27 | 22-FEB-16:40 | 3.67 | -0.7 |
March | 0.102726E+10 | 2889.62 | 27-MAR-16:50 | 21.28 | 15.57 | 0.228591E+09 | 346.45 | 03-MAR-14:00 | 21.28 | 15.57 |
April | 0.155330E+10 | 5141.09 | 10-APR-16:00 | 20.00 | 11.13 | 0.221650E+09 | 347.84 | 07-APR-13:09 | 20.00 | 11.13 |
May | 0.253550E+10 | 6376.23 | 30-MAY-16:00 | 28.30 | 17.60 | 0.262679E+09 | 347.87 | 15-MAY-13:00 | 28.30 | 17.60 |
June | 0.398591E+10 | 10822.33 | 18-JUN-17:52 | 23.30 | 21.43 | 0.275469E+09 | 347.86 | 23-JUN-09:09 | 27.25 | 18.76 |
July | 0.461083E+10 | 8996.44 | 02-JUL-16:42 | 24.50 | 20.61 | 0.256943E+09 | 347.86 | 12-JUL-13:00 | 28.30 | 19.52 |
August | 0.548027E+10 | 8052.19 | 20-AUG-16:02 | 25.50 | 16.89 | 0.288373E+09 | 347.86 | 25-AUG-13:00 | 26.70 | 15.26 |
September | 0.351253E+10 | 10898.59 | 04-SEP-17:02 | 24.32 | 18.74 | 0.253856E+09 | 347.86 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.273400E+10 | 6688.87 | 15-OCT-16:13 | 19.03 | 12.04 | 0.258695E+09 | 347.86 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.105007E+10 | 3031.11 | 03-NOV-15:30 | 16.10 | 10.65 | 0.216613E+09 | 347.85 | 08-NOV-14:00 | 13.30 | 11.09 |
December | 0.434970E+09 | 1157.21 | 08-DEC-15:40 | 6.30 | 2.04 | 0.192123E+09 | 316.53 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.274475E+11 | 0.283092E+10 | ||||||||
Minimum of Months | 0.242408E+09 | 1143.97 | 3.85 | -0.7 | 0.179775E+09 | 313.67 | 3.67 | -0.7 | ||
Maximum of Months | 0.548027E+10 | 10898.59 | 28.30 | 21.43 | 0.288373E+09 | 347.87 | 28.30 | 19.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229510E+09 | 1124.79 | 20-JAN-15:00 | 7.80 | 3.97 | 0.305976E+09 | 429.53 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.259140E+09 | 1148.41 | 24-FEB-14:30 | 8.85 | 2.78 | 0.278993E+09 | 433.03 | 24-FEB-14:00 | 8.30 | 2.27 |
March | 0.118853E+10 | 1545.68 | 28-MAR-14:10 | 13.22 | 8.42 | 0.357009E+09 | 534.07 | 28-MAR-13:00 | 13.22 | 8.42 |
April | 0.185255E+10 | 3311.53 | 10-APR-14:00 | 20.60 | 10.45 | 0.357728E+09 | 549.49 | 07-APR-13:09 | 20.60 | 10.45 |
May | 0.333670E+10 | 6692.24 | 30-MAY-06:03 | 20.47 | 15.45 | 0.426838E+09 | 549.52 | 15-MAY-13:00 | 20.47 | 15.45 |
June | 0.505765E+10 | 8004.52 | 26-JUN-06:03 | 21.97 | 17.81 | 0.435678E+09 | 549.72 | 19-JUN-13:30 | 21.97 | 17.81 |
July | 0.584023E+10 | 8004.33 | 10-JUL-06:03 | 26.20 | 20.78 | 0.405922E+09 | 549.83 | 10-JUL-13:50 | 32.70 | 20.82 |
August | 0.588925E+10 | 7944.35 | 05-AUG-05:03 | 26.20 | 23.65 | 0.455106E+09 | 549.50 | 08-AUG-13:20 | 26.50 | 16.97 |
September | 0.371601E+10 | 5784.50 | 02-SEP-05:03 | 22.12 | 16.30 | 0.399747E+09 | 549.50 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.253700E+10 | 3779.10 | 05-OCT-14:00 | 23.30 | 18.86 | 0.399974E+09 | 549.50 | 16-OCT-09:30 | 17.25 | 14.25 |
November | 0.108609E+10 | 1755.81 | 02-NOV-13:10 | 15.68 | 8.29 | 0.332680E+09 | 544.57 | 03-NOV-13:00 | 17.80 | 10.67 |
December | 0.358174E+09 | 1170.29 | 20-DEC-14:00 | 10.00 | 5.91 | 0.296782E+09 | 440.17 | 20-DEC-14:09 | 9.72 | 5.77 |
Annual Sum or Average | 0.313508E+11 | 0.445243E+10 | ||||||||
Minimum of Months | 0.229510E+09 | 1124.79 | 7.80 | 2.78 | 0.278993E+09 | 429.53 | 7.80 | 2.27 | ||
Maximum of Months | 0.588925E+10 | 8004.52 | 26.20 | 23.65 | 0.455106E+09 | 549.83 | 32.70 | 20.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281007E+09 | 1217.63 | 19-JAN-10:00 | 7.80 | 4.14 | 0.143821E+09 | 299.12 | 19-JAN-09:00 | 7.80 | 4.14 |
February | 0.407998E+09 | 1297.00 | 22-FEB-09:50 | 0.50 | -3.2 | 0.132157E+09 | 314.67 | 22-FEB-09:00 | 0.60 | -3.2 |
March | 0.128301E+10 | 3588.37 | 29-MAR-09:00 | 5.60 | 2.98 | 0.174966E+09 | 338.72 | 29-MAR-10:20 | 7.43 | 3.94 |
April | 0.202880E+10 | 5945.96 | 28-APR-08:40 | 15.53 | 8.75 | 0.171301E+09 | 338.73 | 26-APR-10:09 | 15.53 | 8.75 |
May | 0.349567E+10 | 12117.13 | 29-MAY-08:42 | 25.73 | 16.73 | 0.198907E+09 | 338.94 | 31-MAY-08:00 | 25.00 | 19.48 |
June | 0.441548E+10 | 9305.01 | 25-JUN-08:53 | 25.60 | 23.63 | 0.203495E+09 | 341.27 | 26-JUN-07:19 | 23.50 | 18.22 |
July | 0.506038E+10 | 13138.03 | 02-JUL-07:52 | 24.40 | 21.27 | 0.190565E+09 | 342.93 | 17-JUL-07:19 | 24.63 | 20.35 |
August | 0.565550E+10 | 11708.67 | 27-AUG-09:53 | 26.10 | 21.81 | 0.212861E+09 | 339.87 | 22-AUG-07:19 | 26.10 | 21.81 |
September | 0.357967E+10 | 13081.43 | 04-SEP-08:22 | 23.35 | 18.64 | 0.186758E+09 | 338.98 | 06-SEP-08:00 | 25.60 | 19.05 |
October | 0.263553E+10 | 5360.22 | 05-OCT-09:00 | 18.90 | 16.77 | 0.189080E+09 | 338.73 | 16-OCT-08:39 | 15.77 | 13.14 |
November | 0.105735E+10 | 2287.60 | 02-NOV-09:00 | 11.10 | 5.86 | 0.157755E+09 | 338.71 | 03-NOV-10:09 | 13.58 | 8.52 |
December | 0.463906E+09 | 1295.27 | 20-DEC-09:40 | 7.57 | 4.72 | 0.140440E+09 | 313.60 | 20-DEC-09:50 | 7.93 | 4.87 |
Annual Sum or Average | 0.303643E+11 | 0.210211E+10 | ||||||||
Minimum of Months | 0.281007E+09 | 1217.63 | 0.50 | -3.2 | 0.132157E+09 | 299.12 | 0.60 | -3.2 | ||
Maximum of Months | 0.565550E+10 | 13138.03 | 26.10 | 23.63 | 0.212861E+09 | 342.93 | 26.10 | 21.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105916E+10 | 5423.17 | 19-JAN-13:30 | 9.40 | 3.94 | 0.340805E+09 | 549.50 | 30-JAN-14:30 | 2.80 | -1.1 |
February | 0.132410E+10 | 5917.93 | 02-FEB-13:50 | 5.78 | -0.8 | 0.316990E+09 | 549.49 | 03-FEB-14:00 | -1.7 | -5.1 |
March | 0.273422E+10 | 7953.43 | 29-MAR-13:10 | 7.80 | 5.30 | 0.400320E+09 | 549.50 | 23-MAR-13:00 | 7.80 | 5.30 |
April | 0.310373E+10 | 8573.71 | 07-APR-12:30 | 26.15 | 15.90 | 0.371988E+09 | 549.77 | 07-APR-13:09 | 26.60 | 16.32 |
May | 0.430904E+10 | 9245.30 | 28-MAY-12:23 | 24.70 | 14.58 | 0.427359E+09 | 550.13 | 30-MAY-13:50 | 29.50 | 17.11 |
June | 0.578901E+10 | 9813.46 | 18-JUN-13:13 | 26.50 | 22.53 | 0.435621E+09 | 549.81 | 19-JUN-13:30 | 34.70 | 23.81 |
July | 0.681063E+10 | 13850.38 | 04-JUL-12:53 | 27.80 | 18.77 | 0.406148E+09 | 549.97 | 10-JUL-13:50 | 32.70 | 20.82 |
August | 0.842899E+10 | 14102.86 | 20-AUG-11:53 | 26.70 | 15.45 | 0.455603E+09 | 557.24 | 30-AUG-13:09 | 27.48 | 15.59 |
September | 0.646421E+10 | 15371.16 | 04-SEP-11:42 | 26.02 | 17.75 | 0.402155E+09 | 571.82 | 28-SEP-13:09 | 22.98 | 13.55 |
October | 0.617287E+10 | 14462.95 | 22-OCT-12:23 | 21.65 | 16.58 | 0.412539E+09 | 563.83 | 04-OCT-13:20 | 21.65 | 16.58 |
November | 0.248196E+10 | 10093.29 | 02-NOV-12:50 | 15.50 | 8.17 | 0.372560E+09 | 549.56 | 02-NOV-13:50 | 16.02 | 8.62 |
December | 0.143132E+10 | 6133.36 | 21-DEC-13:13 | 2.97 | -1.7 | 0.339644E+09 | 550.06 | 20-DEC-10:50 | 2.97 | -1.7 |
Annual Sum or Average | 0.501092E+11 | 0.468173E+10 | ||||||||
Minimum of Months | 0.105916E+10 | 5423.17 | 2.97 | -1.7 | 0.316990E+09 | 549.49 | -1.7 | -5.1 | ||
Maximum of Months | 0.842899E+10 | 15371.16 | 27.80 | 22.53 | 0.455603E+09 | 571.82 | 34.70 | 23.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316295E+09 | 1392.14 | 20-JAN-16:00 | 7.20 | 3.80 | 0.197293E+09 | 324.91 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.398633E+09 | 1875.91 | 24-FEB-15:30 | 8.05 | 2.04 | 0.182069E+09 | 338.68 | 22-FEB-16:00 | 8.05 | 2.04 |
March | 0.138202E+10 | 4785.83 | 29-MAR-16:00 | 7.20 | 4.88 | 0.232688E+09 | 347.84 | 02-MAR-14:00 | 7.20 | 4.88 |
April | 0.211815E+10 | 10440.52 | 09-APR-17:03 | 15.92 | 13.68 | 0.224306E+09 | 347.85 | 26-APR-13:00 | 18.30 | 12.92 |
May | 0.338434E+10 | 11398.32 | 28-MAY-15:02 | 26.23 | 15.49 | 0.266118E+09 | 347.87 | 15-MAY-13:00 | 26.23 | 15.49 |
June | 0.465745E+10 | 12828.18 | 18-JUN-15:51 | 25.60 | 22.09 | 0.275355E+09 | 347.86 | 12-JUN-09:09 | 25.60 | 22.09 |
July | 0.509338E+10 | 13735.34 | 02-JUL-16:31 | 24.60 | 20.65 | 0.256878E+09 | 347.86 | 17-JUL-09:20 | 27.97 | 21.33 |
August | 0.572064E+10 | 12397.70 | 13-AUG-15:52 | 30.00 | 20.46 | 0.288021E+09 | 347.86 | 25-AUG-13:00 | 26.70 | 15.26 |
September | 0.358713E+10 | 12755.19 | 04-SEP-14:22 | 25.55 | 18.53 | 0.251540E+09 | 347.85 | 15-SEP-13:00 | 22.80 | 15.50 |
October | 0.279851E+10 | 6717.10 | 04-OCT-15:30 | 23.35 | 19.12 | 0.250726E+09 | 347.85 | 12-OCT-13:00 | 20.60 | 17.37 |
November | 0.102253E+10 | 3340.04 | 03-NOV-15:30 | 16.10 | 10.65 | 0.210543E+09 | 347.85 | 08-NOV-14:00 | 13.30 | 11.09 |
December | 0.418273E+09 | 1371.33 | 08-DEC-15:40 | 6.30 | 2.04 | 0.191595E+09 | 321.40 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.308973E+11 | 0.282713E+10 | ||||||||
Minimum of Months | 0.316295E+09 | 1371.33 | 6.30 | 2.04 | 0.182069E+09 | 321.40 | 6.20 | 1.96 | ||
Maximum of Months | 0.572064E+10 | 13735.34 | 30.00 | 22.09 | 0.288021E+09 | 347.87 | 27.97 | 22.09 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341419E+09 | 23221.49 | 02-JAN-05:01 | -12.1 |
February | 663443.06 | 11057.38 | 06-FEB-07:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.342082E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.341419E+09 | 23221.49 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.507094E+10 | 15446.25 | 02-JAN-06:12 | -11.7 |
February | 0.412379E+10 | 15279.89 | 06-FEB-06:06 | -12.9 |
March | 0.193457E+10 | 9796.56 | 20-MAR-06:02 | -0.6 |
April | 0.917372E+09 | 7449.50 | 03-APR-06:01 | 2.38 |
May | 0.220740E+09 | 4894.42 | 30-MAY-05:03 | 18.17 |
June | 42679015.65 | 4115.34 | 21-JUN-05:03 | 20.10 |
July | 22636733.79 | 4506.44 | 11-JUL-05:03 | 19.60 |
August | 38387895.01 | 4639.86 | 21-AUG-05:03 | 20.60 |
September | 0.152070E+09 | 4637.45 | 05-SEP-04:02 | 20.52 |
October | 0.535086E+09 | 4353.38 | 19-OCT-05:02 | 5.37 |
November | 0.202772E+10 | 11362.65 | 24-NOV-06:13 | -4.4 |
December | 0.358299E+10 | 9708.18 | 15-DEC-07:02 | -3.6 |
Annual Sum or Average | 0.186690E+11 | |||
Minimum of Months | 22636733.79 | 4115.34 | -12.9 | |
Maximum of Months | 0.507094E+10 | 15446.25 | 20.60 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257224E+10 | 9559.76 | 02-JAN-07:17 | -11.5 |
February | 0.193581E+10 | 7681.50 | 06-FEB-07:11 | -13.1 |
March | 0.113454E+10 | 2683.52 | 20-MAR-06:12 | -0.6 |
April | 0.420586E+09 | 2898.46 | 16-APR-15:23 | 21.40 |
May | 0.100670E+09 | 2454.10 | 14-MAY-12:32 | 15.93 |
June | 15940290.77 | 1897.62 | 22-JUN-05:03 | 22.88 |
July | 20808093.14 | 2223.87 | 09-JUL-14:52 | 27.20 |
August | 18422257.71 | 2577.96 | 20-AUG-14:32 | 28.17 |
September | 26050562.14 | 3011.46 | 10-SEP-15:13 | 24.03 |
October | 0.142222E+09 | 3954.96 | 09-OCT-13:23 | 13.60 |
November | 0.109202E+10 | 3920.91 | 24-NOV-07:02 | -4.3 |
December | 0.166038E+10 | 4470.56 | 11-DEC-07:02 | 1.70 |
Annual Sum or Average | 0.913970E+10 | |||
Minimum of Months | 15940290.77 | 1897.62 | -13.1 | |
Maximum of Months | 0.257224E+10 | 9559.76 | 28.17 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201891E+10 | 8632.83 | 02-JAN-07:01 | -11.6 |
February | 0.139405E+10 | 4052.60 | 06-FEB-08:55 | -12.2 |
March | 0.783692E+09 | 3227.66 | 17-MAR-07:27 | -1.1 |
April | 0.240235E+09 | 4347.99 | 11-APR-05:03 | 6.10 |
May | 26700721.28 | 4194.99 | 15-MAY-05:03 | 8.07 |
June | 20168577.04 | 3683.23 | 07-JUN-05:03 | 16.70 |
July | 22051402.64 | 3033.29 | 01-JUL-05:03 | 20.10 |
August | 22069425.99 | 3426.63 | 08-AUG-04:03 | 15.50 |
September | 29868865.54 | 4466.26 | 25-SEP-05:03 | 14.40 |
October | 44621938.53 | 5212.23 | 10-OCT-05:03 | 9.72 |
November | 0.641765E+09 | 3561.32 | 16-NOV-08:06 | 4.60 |
December | 0.120978E+10 | 3233.94 | 22-DEC-08:18 | -3.9 |
Annual Sum or Average | 0.645391E+10 | |||
Minimum of Months | 20168577.04 | 3033.29 | -12.2 | |
Maximum of Months | 0.201891E+10 | 8632.83 | 20.10 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.883203E+09 | 24275.08 | 02-JAN-05:01 | -12.1 |
February | 0.229886E+09 | 21163.33 | 06-FEB-06:01 | -12.9 |
March | 17160028.21 | 19408.66 | 20-MAR-06:01 | -0.6 |
April | 1650319.74 | 18821.14 | 03-APR-06:01 | 2.38 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 35148153.76 | 19422.22 | 24-NOV-07:01 | -4.3 |
December | 82481779.60 | 19723.38 | 26-DEC-06:01 | 6.20 |
Annual Sum or Average | 0.124953E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.883203E+09 | 24275.08 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273429E+10 | 31346.14 | 02-JAN-04:42 | -12.1 |
February | 0.174743E+10 | 30531.78 | 06-FEB-05:01 | -13.2 |
March | 0.349185E+09 | 27715.30 | 20-MAR-05:01 | -1.5 |
April | 59749722.83 | 26507.07 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.578820E+09 | 28076.24 | 20-NOV-06:01 | 0.00 |
December | 0.104683E+10 | 28701.17 | 26-DEC-05:01 | 5.68 |
Annual Sum or Average | 0.651630E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.273429E+10 | 31346.14 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395407E+10 | 10574.95 | 02-JAN-00:02 | -10.7 |
February | 0.327081E+10 | 10484.75 | 06-FEB-04:22 | -13.3 |
March | 0.975316E+09 | 9493.50 | 20-MAR-04:02 | -0.8 |
April | 0.229187E+09 | 8835.54 | 03-APR-05:01 | 2.70 |
May | 2457050.03 | 7835.42 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 31903234.74 | 7868.36 | 31-OCT-06:02 | 5.68 |
November | 0.110362E+10 | 9782.41 | 20-NOV-05:01 | 0.50 |
December | 0.245737E+10 | 10050.55 | 31-DEC-23:03 | -7.9 |
Annual Sum or Average | 0.120247E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.395407E+10 | 10574.95 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216691E+10 | 11268.35 | 02-JAN-00:02 | -10.7 |
February | 0.160578E+10 | 11171.28 | 06-FEB-04:22 | -13.3 |
March | 0.450005E+09 | 10191.09 | 20-MAR-04:02 | -0.8 |
April | 0.119665E+09 | 9465.26 | 03-APR-05:01 | 2.70 |
May | 864551.02 | 3695.64 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 16754218.29 | 7271.24 | 31-OCT-06:02 | 5.68 |
November | 0.554557E+09 | 10504.46 | 20-NOV-05:01 | 0.50 |
December | 0.129099E+10 | 10518.06 | 26-DEC-05:01 | 5.68 |
Annual Sum or Average | 0.620553E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.216691E+10 | 11268.35 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263709E+10 | 14086.88 | 02-JAN-00:02 | -10.7 |
February | 0.195516E+10 | 13950.13 | 06-FEB-04:22 | -13.3 |
March | 0.637791E+09 | 12546.01 | 20-MAR-04:02 | -0.8 |
April | 0.199776E+09 | 11872.27 | 03-APR-05:01 | 2.70 |
May | 3657383.15 | 8760.01 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 16211852.96 | 10542.31 | 31-OCT-06:02 | 5.68 |
November | 0.644458E+09 | 13040.81 | 24-NOV-05:01 | -4.0 |
December | 0.155616E+10 | 13071.76 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.765031E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.263709E+10 | 14086.88 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239987E+10 | 12023.67 | 02-JAN-00:02 | -10.7 |
February | 0.192232E+10 | 11879.81 | 06-FEB-04:22 | -13.3 |
March | 0.542595E+09 | 10664.58 | 13-MAR-04:02 | -0.1 |
April | 0.145244E+09 | 10005.62 | 03-APR-05:01 | 2.70 |
May | 3312651.82 | 5510.51 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 19907761.35 | 7221.98 | 31-OCT-06:02 | 5.68 |
November | 0.681826E+09 | 11148.78 | 20-NOV-05:01 | 0.50 |
December | 0.148688E+10 | 11037.34 | 26-DEC-05:01 | 5.68 |
Annual Sum or Average | 0.720196E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.239987E+10 | 12023.67 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232189E+10 | 8132.52 | 02-JAN-00:02 | -10.7 |
February | 0.186629E+10 | 7826.31 | 06-FEB-05:01 | -13.2 |
March | 0.403915E+09 | 6925.06 | 20-MAR-05:01 | -1.5 |
April | 60189195.75 | 6659.89 | 03-APR-05:01 | 2.70 |
May | 206637.93 | 1377.59 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.186359E+09 | 6844.02 | 24-NOV-06:01 | -4.4 |
December | 0.639293E+09 | 6847.81 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.547815E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.232189E+10 | 8132.52 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118013E+10 | 8699.25 | 02-JAN-00:02 | -10.7 |
February | 0.749233E+09 | 8379.71 | 06-FEB-05:01 | -13.2 |
March | 0.130267E+09 | 7371.20 | 20-MAR-05:01 | -1.5 |
April | 21328509.16 | 6995.41 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 72979940.58 | 7206.18 | 24-NOV-06:01 | -4.4 |
December | 0.303843E+09 | 7316.25 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.245778E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.118013E+10 | 8699.25 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.560370E+10 | 14149.55 | 02-JAN-08:00 | -11.1 |
February | 0.488862E+10 | 14210.00 | 06-FEB-07:10 | -13.2 |
March | 0.339425E+10 | 12433.66 | 23-MAR-06:10 | -4.7 |
April | 0.169537E+10 | 11157.13 | 03-APR-06:10 | 2.38 |
May | 0.648794E+09 | 9565.18 | 01-MAY-06:10 | 7.67 |
June | 17644603.11 | 6797.63 | 02-JUN-06:06 | 13.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 82438763.97 | 8502.70 | 20-SEP-06:05 | 12.48 |
October | 0.475796E+09 | 9369.43 | 27-OCT-06:10 | 5.68 |
November | 0.217424E+10 | 12140.29 | 24-NOV-07:10 | -4.3 |
December | 0.378978E+10 | 12213.30 | 15-DEC-07:10 | -3.6 |
Annual Sum or Average | 0.227706E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.560370E+10 | 14210.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132975E+10 | 8819.16 | 02-JAN-00:02 | -10.7 |
February | 0.935576E+09 | 8517.64 | 06-FEB-05:01 | -13.2 |
March | 0.141817E+09 | 7232.64 | 01-MAR-06:01 | 3.98 |
April | 27549646.36 | 6785.60 | 03-APR-06:01 | 2.38 |
May | 161233.54 | 1074.89 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 99440883.50 | 7243.56 | 24-NOV-06:01 | -4.4 |
December | 0.350691E+09 | 7364.19 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.288498E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.132975E+10 | 8819.16 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216587E+10 | 8910.57 | 02-JAN-00:02 | -10.7 |
February | 0.156941E+10 | 8462.23 | 13-FEB-05:01 | -9.0 |
March | 0.266436E+09 | 7527.88 | 20-MAR-05:01 | -1.5 |
April | 35473579.04 | 7211.82 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 326454.52 | 1378.48 | 28-OCT-06:03 | 3.90 |
November | 0.350867E+09 | 7874.71 | 24-NOV-05:01 | -4.0 |
December | 0.892116E+09 | 7794.31 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.528050E+10 | |||
Minimum of Months | 0.00 | 0.00 | -10.7 | |
Maximum of Months | 0.216587E+10 | 8910.57 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118619E+10 | 9199.15 | 02-JAN-00:02 | -10.7 |
February | 0.744660E+09 | 8681.59 | 13-FEB-05:01 | -9.0 |
March | 0.124259E+09 | 7600.93 | 20-MAR-05:01 | -1.5 |
April | 16758544.73 | 7150.24 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 587218.07 | 2270.38 | 31-OCT-06:02 | 5.68 |
November | 0.180295E+09 | 8054.42 | 24-NOV-05:01 | -4.0 |
December | 0.496354E+09 | 7910.15 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.274910E+10 | |||
Minimum of Months | 0.00 | 0.00 | -10.7 | |
Maximum of Months | 0.118619E+10 | 9199.15 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132022E+10 | 12299.73 | 02-JAN-00:02 | -10.7 |
February | 0.796412E+09 | 11754.26 | 06-FEB-05:01 | -13.2 |
March | 0.161613E+09 | 10329.90 | 20-MAR-05:01 | -1.5 |
April | 29293786.66 | 9894.75 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.170186E+09 | 10587.78 | 24-NOV-06:01 | -4.4 |
December | 0.527824E+09 | 10864.36 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.300555E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.132022E+10 | 12299.73 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129990E+10 | 9301.55 | 02-JAN-00:02 | -10.7 |
February | 0.894832E+09 | 8724.86 | 06-FEB-05:01 | -13.2 |
March | 0.147977E+09 | 7581.30 | 13-MAR-05:01 | -0.6 |
April | 24053218.30 | 7332.40 | 03-APR-05:01 | 2.70 |
May | 94207.25 | 628.05 | 01-MAY-06:03 | 7.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 466498.12 | 1833.41 | 28-OCT-06:03 | 3.90 |
November | 0.216632E+09 | 7732.18 | 25-NOV-06:01 | -3.1 |
December | 0.542695E+09 | 7950.37 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.312665E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.129990E+10 | 9301.55 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.576754E+09 | 889.66 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.484166E+09 | 818.72 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.534215E+09 | 678.03 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.454588E+09 | 484.53 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.477115E+09 | 484.05 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.466790E+09 | 474.55 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.441225E+09 | 471.67 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.497907E+09 | 491.15 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.464734E+09 | 613.82 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.504356E+09 | 731.22 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.549574E+09 | 889.66 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.572290E+09 | 889.66 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.602371E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.441225E+09 | 471.67 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.576754E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.358763E+09 | 563.23 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.302389E+09 | 523.21 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.336975E+09 | 469.98 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.288325E+09 | 299.91 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.303931E+09 | 306.98 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.298000E+09 | 286.80 | 29-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.281296E+09 | 281.29 | 24-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.316690E+09 | 299.77 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293719E+09 | 312.81 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.317616E+09 | 466.18 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.344303E+09 | 563.23 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.351938E+09 | 563.23 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.379394E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.281296E+09 | 281.29 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.358763E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.550981E+09 | 889.66 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.466350E+09 | 814.16 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.526933E+09 | 620.39 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.455020E+09 | 482.14 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.479742E+09 | 484.99 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.470877E+09 | 478.02 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.444615E+09 | 475.48 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.499963E+09 | 491.13 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.462202E+09 | 594.25 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.494545E+09 | 708.59 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.531637E+09 | 889.66 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.537064E+09 | 889.66 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.591993E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.444615E+09 | 475.48 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.550981E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.353612E+09 | 563.19 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.298454E+09 | 512.07 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.334213E+09 | 423.83 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.288026E+09 | 360.53 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.301865E+09 | 311.93 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.296285E+09 | 307.83 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.280121E+09 | 307.56 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.315246E+09 | 351.15 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293412E+09 | 407.87 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.314758E+09 | 451.73 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.339269E+09 | 563.19 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.348135E+09 | 563.19 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.376340E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.280121E+09 | 307.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.353612E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.573382E+09 | 889.66 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.481576E+09 | 815.44 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.532707E+09 | 667.85 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.453798E+09 | 481.24 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.476554E+09 | 480.72 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.466316E+09 | 470.72 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.440688E+09 | 467.68 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.497530E+09 | 488.19 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.463642E+09 | 601.30 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.502857E+09 | 724.10 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.547167E+09 | 889.66 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.568334E+09 | 889.66 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.600455E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.440688E+09 | 467.68 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.573382E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.357430E+09 | 563.23 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.301341E+09 | 521.76 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.336217E+09 | 466.65 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287889E+09 | 297.77 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.303595E+09 | 305.12 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.297632E+09 | 283.83 | 29-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.280972E+09 | 268.66 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.316396E+09 | 297.39 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293207E+09 | 311.25 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.316875E+09 | 462.70 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.343438E+09 | 563.23 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.350372E+09 | 563.23 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.378536E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.280972E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.357430E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.548296E+09 | 889.66 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.465534E+09 | 810.71 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.526087E+09 | 607.85 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.454322E+09 | 478.69 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.479130E+09 | 481.72 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.470176E+09 | 474.41 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.443992E+09 | 471.73 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.499448E+09 | 488.17 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.461424E+09 | 580.66 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.493881E+09 | 700.12 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.530181E+09 | 889.66 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.535290E+09 | 889.66 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.590776E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.443992E+09 | 471.73 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.548296E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.352243E+09 | 563.19 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.297533E+09 | 510.13 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.333477E+09 | 418.86 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287563E+09 | 353.56 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.301502E+09 | 310.31 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.295917E+09 | 306.04 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.279763E+09 | 305.76 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.314925E+09 | 314.34 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.292805E+09 | 402.35 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.314273E+09 | 447.76 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.338356E+09 | 563.19 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.346653E+09 | 563.19 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.375501E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.279763E+09 | 305.76 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.352243E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.576751E+09 | 889.66 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.484164E+09 | 818.72 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.534213E+09 | 678.02 | 02-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.454587E+09 | 484.52 | 21-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.477115E+09 | 484.04 | 08-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.466786E+09 | 474.54 | 29-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.441225E+09 | 471.66 | 24-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.497907E+09 | 491.14 | 16-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.464733E+09 | 613.80 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.504355E+09 | 731.21 | 31-OCT-15:00 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.549572E+09 | 889.66 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.572288E+09 | 889.66 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.602370E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.441225E+09 | 471.66 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.576751E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.358762E+09 | 563.23 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.302388E+09 | 523.21 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.336974E+09 | 469.98 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.288324E+09 | 299.91 | 21-APR-15:00 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.303930E+09 | 306.97 | 19-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.298000E+09 | 286.79 | 29-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.281295E+09 | 281.28 | 24-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.316690E+09 | 299.76 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293719E+09 | 312.81 | 26-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.317616E+09 | 466.17 | 31-OCT-15:00 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.344302E+09 | 563.23 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.351929E+09 | 563.23 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.379393E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.281295E+09 | 281.28 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.358762E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.550980E+09 | 889.66 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.466349E+09 | 814.15 | 15-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.526932E+09 | 620.37 | 16-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.455015E+09 | 482.13 | 21-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.479741E+09 | 484.98 | 08-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.470877E+09 | 478.02 | 29-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.444614E+09 | 475.47 | 24-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.499963E+09 | 491.13 | 16-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.462201E+09 | 594.23 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.494544E+09 | 708.58 | 31-OCT-15:00 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.531637E+09 | 889.66 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.537063E+09 | 889.66 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.591992E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.444614E+09 | 475.47 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.550980E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.353611E+09 | 563.19 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.298454E+09 | 512.06 | 15-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.334205E+09 | 423.82 | 16-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.288025E+09 | 360.52 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.301864E+09 | 311.93 | 08-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.296285E+09 | 307.83 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.280121E+09 | 307.56 | 24-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.315246E+09 | 351.13 | 16-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293411E+09 | 407.86 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.314758E+09 | 451.72 | 06-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.339261E+09 | 563.19 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.348134E+09 | 563.19 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.376337E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.280121E+09 | 307.56 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.353611E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.576754E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642128E+09 |
February | 0.901968E+09 | 0.484166E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.570930E+09 |
March | 0.107774E+10 | 0.534215E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459309E+09 |
April | 0.956342E+09 | 0.454588E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 257633.76 | 0.305865E+09 |
May | 0.103597E+10 | 0.477115E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1264639.61 | 0.187533E+09 |
June | 0.103308E+10 | 0.466790E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8305775.10 | 0.100852E+09 |
July | 0.959235E+09 | 0.441225E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19350780.65 | 36367921.18 |
August | 0.107774E+10 | 0.497907E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23571500.47 | 45316322.87 |
September | 0.956342E+09 | 0.464734E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2971249.70 | 0.101315E+09 |
October | 0.994195E+09 | 0.504356E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43434.33 | 0.248777E+09 |
November | 0.984487E+09 | 0.549574E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443346E+09 |
December | 0.959235E+09 | 0.572290E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534495E+09 |
Annual Sum or Average | 0.119305E+11 | 0.602371E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55765013.63 | 0.367623E+10 |
Minimum of Months | 0.901968E+09 | 0.441225E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36367921.18 |
Maximum of Months | 0.107774E+10 | 0.576754E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23571500.47 | 0.642128E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.358763E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428464E+09 |
February | 0.571020E+09 | 0.302389E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384553E+09 |
March | 0.682301E+09 | 0.336975E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310594E+09 |
April | 0.605444E+09 | 0.288325E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167395.68 | 0.211340E+09 |
May | 0.655854E+09 | 0.303931E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 635404.00 | 0.127445E+09 |
June | 0.654023E+09 | 0.298000E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5448057.70 | 67557084.29 |
July | 0.607275E+09 | 0.281296E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12705574.65 | 24452500.39 |
August | 0.682301E+09 | 0.316690E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15323399.49 | 31174882.39 |
September | 0.605444E+09 | 0.293719E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1930306.57 | 70459752.38 |
October | 0.629407E+09 | 0.317616E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28954.66 | 0.171429E+09 |
November | 0.623262E+09 | 0.344303E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299774E+09 |
December | 0.607275E+09 | 0.351938E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358448E+09 |
Annual Sum or Average | 0.755301E+10 | 0.379394E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36239092.77 | 0.248569E+10 |
Minimum of Months | 0.571020E+09 | 0.281296E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24452500.39 |
Maximum of Months | 0.682301E+09 | 0.358763E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15323399.49 | 0.428464E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.550981E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658949E+09 |
February | 0.901968E+09 | 0.466350E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599090E+09 |
March | 0.107774E+10 | 0.526933E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482602E+09 |
April | 0.956342E+09 | 0.455020E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250455.11 | 0.320754E+09 |
May | 0.103597E+10 | 0.479742E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 999092.14 | 0.190492E+09 |
June | 0.103308E+10 | 0.470877E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8075389.58 | 0.101056E+09 |
July | 0.959235E+09 | 0.444615E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18908224.30 | 37152181.08 |
August | 0.107774E+10 | 0.499963E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22699689.09 | 47640321.00 |
September | 0.956342E+09 | 0.462202E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2867716.97 | 0.110143E+09 |
October | 0.994195E+09 | 0.494545E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43265.37 | 0.276464E+09 |
November | 0.984487E+09 | 0.531637E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469052E+09 |
December | 0.959235E+09 | 0.537064E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562187E+09 |
Annual Sum or Average | 0.119305E+11 | 0.591993E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53843832.56 | 0.385558E+10 |
Minimum of Months | 0.901968E+09 | 0.444615E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37152181.08 |
Maximum of Months | 0.107774E+10 | 0.550981E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22699689.09 | 0.658949E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.353612E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430257E+09 |
February | 0.570983E+09 | 0.298454E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385428E+09 |
March | 0.682256E+09 | 0.334213E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315505E+09 |
April | 0.605404E+09 | 0.288026E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 181010.32 | 0.211086E+09 |
May | 0.655811E+09 | 0.301865E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 935850.06 | 0.128205E+09 |
June | 0.653980E+09 | 0.296285E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5580276.21 | 70204056.41 |
July | 0.607235E+09 | 0.280121E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13160154.31 | 26820488.52 |
August | 0.682256E+09 | 0.315246E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15520830.13 | 32572235.52 |
September | 0.605404E+09 | 0.293412E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2018845.19 | 70330097.49 |
October | 0.629366E+09 | 0.314758E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29016.82 | 0.172861E+09 |
November | 0.623221E+09 | 0.339269E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296978E+09 |
December | 0.607235E+09 | 0.348135E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359683E+09 |
Annual Sum or Average | 0.755252E+10 | 0.376340E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37425983.03 | 0.249993E+10 |
Minimum of Months | 0.570983E+09 | 0.280121E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26820488.52 |
Maximum of Months | 0.682256E+09 | 0.353612E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15520830.13 | 0.430257E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.573382E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361357E+09 |
February | 0.901968E+09 | 0.481576E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319326E+09 |
March | 0.107774E+10 | 0.532707E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253863E+09 |
April | 0.956342E+09 | 0.453798E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 199316.85 | 0.166517E+09 |
May | 0.103597E+10 | 0.476554E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1146407.94 | 97400684.47 |
June | 0.103308E+10 | 0.466316E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5179273.20 | 50600321.23 |
July | 0.959235E+09 | 0.440688E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12116752.26 | 16820517.49 |
August | 0.107774E+10 | 0.497530E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13575035.43 | 23380728.30 |
September | 0.956342E+09 | 0.463642E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1659108.47 | 57354728.07 |
October | 0.994195E+09 | 0.502857E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26059.29 | 0.147266E+09 |
November | 0.984487E+09 | 0.547167E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267268E+09 |
December | 0.959235E+09 | 0.568334E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312865E+09 |
Annual Sum or Average | 0.119305E+11 | 0.600455E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33901953.43 | 0.207402E+10 |
Minimum of Months | 0.901968E+09 | 0.440688E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16820517.49 |
Maximum of Months | 0.107774E+10 | 0.573382E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13575035.43 | 0.361357E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.357430E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241690E+09 |
February | 0.571020E+09 | 0.301341E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216752E+09 |
March | 0.682301E+09 | 0.336217E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174064E+09 |
April | 0.605444E+09 | 0.287889E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93412.95 | 0.117422E+09 |
May | 0.655854E+09 | 0.303595E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 374220.65 | 68917765.11 |
June | 0.654023E+09 | 0.297632E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3105428.87 | 35655347.24 |
July | 0.607275E+09 | 0.280972E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7073997.07 | 12516145.73 |
August | 0.682301E+09 | 0.316396E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8327293.87 | 17360082.34 |
September | 0.605444E+09 | 0.293207E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1038675.34 | 41340289.14 |
October | 0.629407E+09 | 0.316875E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17371.81 | 0.103234E+09 |
November | 0.623262E+09 | 0.343438E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182879E+09 |
December | 0.607275E+09 | 0.350372E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211059E+09 |
Annual Sum or Average | 0.755301E+10 | 0.378536E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20030400.55 | 0.142289E+10 |
Minimum of Months | 0.571020E+09 | 0.280972E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12516145.73 |
Maximum of Months | 0.682301E+09 | 0.357430E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8327293.87 | 0.241690E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.548296E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744314E+10 |
February | 0.901968E+09 | 0.465534E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.741956E+10 |
March | 0.107774E+10 | 0.526087E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673180E+10 |
April | 0.956342E+09 | 0.454322E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17113333.32 | 0.398609E+10 |
May | 0.103597E+10 | 0.479130E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68434053.08 | 0.239086E+10 |
June | 0.103308E+10 | 0.470176E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482834E+09 | 0.759544E+09 |
July | 0.959235E+09 | 0.443992E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101645E+10 | 93502661.50 |
August | 0.107774E+10 | 0.499448E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121478E+10 | 0.242308E+09 |
September | 0.956342E+09 | 0.461424E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201696E+09 | 0.113668E+10 |
October | 0.994195E+09 | 0.493881E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2913622.71 | 0.308684E+10 |
November | 0.984487E+09 | 0.530181E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557697E+10 |
December | 0.959235E+09 | 0.535290E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670390E+10 |
Annual Sum or Average | 0.119305E+11 | 0.590776E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300423E+10 | 0.455712E+11 |
Minimum of Months | 0.901968E+09 | 0.443992E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93502661.50 |
Maximum of Months | 0.107774E+10 | 0.548296E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121478E+10 | 0.744314E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.352243E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242515E+09 |
February | 0.570983E+09 | 0.297533E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216591E+09 |
March | 0.682256E+09 | 0.333477E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176894E+09 |
April | 0.605404E+09 | 0.287563E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103939.67 | 0.117717E+09 |
May | 0.655811E+09 | 0.301502E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 576319.11 | 69699327.72 |
June | 0.653980E+09 | 0.295917E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2995471.67 | 37848253.07 |
July | 0.607235E+09 | 0.279763E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7182248.33 | 14288640.34 |
August | 0.682256E+09 | 0.314925E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8369767.66 | 18341388.78 |
September | 0.605404E+09 | 0.292805E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1048595.32 | 41461881.45 |
October | 0.629366E+09 | 0.314273E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17381.76 | 0.104815E+09 |
November | 0.623221E+09 | 0.338356E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180118E+09 |
December | 0.607235E+09 | 0.346653E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211242E+09 |
Annual Sum or Average | 0.755252E+10 | 0.375501E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20293723.52 | 0.143153E+10 |
Minimum of Months | 0.570983E+09 | 0.279763E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14288640.34 |
Maximum of Months | 0.682256E+09 | 0.352243E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8369767.66 | 0.242515E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.576751E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558467E+09 |
February | 0.901968E+09 | 0.484164E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498072E+09 |
March | 0.107774E+10 | 0.534213E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405892E+09 |
April | 0.956342E+09 | 0.454587E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 214239.18 | 0.272136E+09 |
May | 0.103597E+10 | 0.477115E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1189548.32 | 0.163741E+09 |
June | 0.103308E+10 | 0.466786E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7284847.28 | 86375657.35 |
July | 0.959235E+09 | 0.441225E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16796151.51 | 30442701.42 |
August | 0.107774E+10 | 0.497907E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20057030.71 | 39081578.05 |
September | 0.956342E+09 | 0.464733E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2479703.17 | 89994513.96 |
October | 0.994195E+09 | 0.504355E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38394.84 | 0.224913E+09 |
November | 0.984487E+09 | 0.549572E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402684E+09 |
December | 0.959235E+09 | 0.572288E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476356E+09 |
Annual Sum or Average | 0.119305E+11 | 0.602370E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48059915.01 | 0.324815E+10 |
Minimum of Months | 0.901968E+09 | 0.441225E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30442701.42 |
Maximum of Months | 0.107774E+10 | 0.576751E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20057030.71 | 0.558467E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.358762E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372687E+09 |
February | 0.421807E+09 | 0.302388E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336275E+09 |
March | 0.502994E+09 | 0.336974E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274009E+09 |
April | 0.447140E+09 | 0.288324E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142080.40 | 0.186647E+09 |
May | 0.484071E+09 | 0.303930E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 544727.25 | 0.110769E+09 |
June | 0.482240E+09 | 0.298000E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4719915.62 | 57897198.13 |
July | 0.448971E+09 | 0.281295E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10871522.74 | 20522987.28 |
August | 0.502994E+09 | 0.316690E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12961003.70 | 26792004.08 |
September | 0.447140E+09 | 0.293719E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1618886.47 | 62097355.10 |
October | 0.465148E+09 | 0.317616E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25579.82 | 0.153320E+09 |
November | 0.460569E+09 | 0.344302E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271506E+09 |
December | 0.448971E+09 | 0.351929E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319520E+09 |
Annual Sum or Average | 0.557719E+10 | 0.379393E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30883716.00 | 0.219204E+10 |
Minimum of Months | 0.421807E+09 | 0.281295E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20522987.28 |
Maximum of Months | 0.502994E+09 | 0.358762E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12961003.70 | 0.372687E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.550980E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575573E+09 |
February | 0.901968E+09 | 0.466349E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525945E+09 |
March | 0.107774E+10 | 0.526932E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426154E+09 |
April | 0.956342E+09 | 0.455015E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 211785.11 | 0.284409E+09 |
May | 0.103597E+10 | 0.479741E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 835195.24 | 0.166829E+09 |
June | 0.103308E+10 | 0.470877E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6810583.33 | 87177321.23 |
July | 0.959235E+09 | 0.444614E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15875338.42 | 31564222.18 |
August | 0.107774E+10 | 0.499963E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19083263.32 | 41208193.03 |
September | 0.956342E+09 | 0.462201E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2401154.90 | 97449232.26 |
October | 0.994195E+09 | 0.494544E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31161.17 | 0.245547E+09 |
November | 0.984487E+09 | 0.531637E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424868E+09 |
December | 0.959235E+09 | 0.537063E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502316E+09 |
Annual Sum or Average | 0.119305E+11 | 0.591992E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45248481.49 | 0.340904E+10 |
Minimum of Months | 0.901968E+09 | 0.444614E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31564222.18 |
Maximum of Months | 0.107774E+10 | 0.550980E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19083263.32 | 0.575573E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.353611E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374269E+09 |
February | 0.570983E+09 | 0.298454E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336422E+09 |
March | 0.682256E+09 | 0.334205E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278285E+09 |
April | 0.605404E+09 | 0.288025E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147856.52 | 0.187220E+09 |
May | 0.655811E+09 | 0.301864E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 800100.45 | 0.112333E+09 |
June | 0.653980E+09 | 0.296285E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4704994.88 | 60645584.58 |
July | 0.607235E+09 | 0.280121E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11048659.09 | 22881945.72 |
August | 0.682256E+09 | 0.315246E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13058421.88 | 28154241.36 |
September | 0.605404E+09 | 0.293411E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1656824.33 | 62642493.36 |
October | 0.629366E+09 | 0.314758E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25614.75 | 0.155344E+09 |
November | 0.623221E+09 | 0.339261E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269328E+09 |
December | 0.607235E+09 | 0.348134E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320548E+09 |
Annual Sum or Average | 0.755252E+10 | 0.376337E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31442471.89 | 0.220807E+10 |
Minimum of Months | 0.570983E+09 | 0.280121E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22881945.72 |
Maximum of Months | 0.682256E+09 | 0.353611E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13058421.88 | 0.374269E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767682E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.694765E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567622E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212580.90 | 0.378761E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1308502.15 | 0.222303E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7433870.67 | 0.114889E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18388560.33 | 37836401.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21465432.52 | 51727859.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2073955.47 | 0.127012E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4182.61 | 0.322488E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576852E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678203E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50887084.65 | 0.454014E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37836401.36 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21465432.52 | 0.767682E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944071E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855320E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699935E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283592.01 | 0.467778E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1602781.32 | 0.280916E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9486080.63 | 0.147543E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23234815.42 | 49081647.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27724716.69 | 65996724.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2710466.58 | 0.157175E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8795.98 | 0.394833E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691702E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818589E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65051248.63 | 0.557294E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49081647.68 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27724716.69 | 0.944071E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951797E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863325E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708710E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56744.14 | 0.479086E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564687.67 | 0.297174E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7559782.95 | 0.158382E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18730607.32 | 55226912.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25012132.79 | 66133650.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2250692.09 | 0.160656E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394984E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674268E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805286E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54174646.97 | 0.561503E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55226912.17 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25012132.79 | 0.951797E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1082.90 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 818.72 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1165.47 | 06-FEB-00:50 |
March | 1306.65 | 01-MAR-10:09 | 678.03 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 847.13 | 21-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 484.53 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 07-APR-13:00 | 699.05 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 484.05 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.74 | 29-MAY-11:55 | 400.05 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 474.55 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.01 | 19-JUN-21:03 | 248.47 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 471.67 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.91 | 09-JUL-14:00 | 116.39 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 491.15 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.73 | 04-AUG-21:03 | 157.57 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 613.82 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.23 | 14-SEP-14:00 | 205.78 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 731.22 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.60 | 25-OCT-11:00 | 575.79 | 17-OCT-24:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 876.19 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1167.61 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 471.67 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.39 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 139.73 | 1167.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 721.47 | 31-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 523.21 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 776.97 | 06-FEB-00:50 |
March | 827.22 | 01-MAR-10:09 | 469.98 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 595.51 | 12-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 299.91 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 | 07-APR-13:00 | 464.86 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 306.98 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.76 | 29-MAY-11:50 | 267.12 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 286.80 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.50 | 19-JUN-21:03 | 164.06 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 281.29 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.27 | 09-JUL-14:00 | 79.30 | 11-JUL-05:00 |
August | 827.22 | 01-AUG-09:09 | 299.77 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.41 | 12-AUG-19:00 | 109.76 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 312.81 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.15 | 14-SEP-14:00 | 147.46 | 10-SEP-08:10 |
October | 827.22 | 02-OCT-09:09 | 466.18 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 | 25-OCT-11:00 | 419.40 | 08-OCT-08:00 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 584.11 | 23-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 778.43 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 281.29 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.30 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 96.41 | 778.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1119.67 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 814.16 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1165.47 | 06-FEB-00:50 |
March | 1306.65 | 01-MAR-10:09 | 620.39 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 893.90 | 12-MAR-10:00 |
April | 1306.65 | 03-APR-09:09 | 482.14 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 07-APR-13:00 | 709.58 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 484.99 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.43 | 29-MAY-11:53 | 405.63 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 478.02 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.96 | 19-JUN-21:03 | 247.80 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 475.48 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.91 | 09-JUL-14:00 | 116.05 | 02-JUL-18:40 |
August | 1306.65 | 01-AUG-09:09 | 491.13 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.30 | 04-AUG-21:03 | 158.72 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 594.25 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 14-SEP-14:00 | 216.50 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 708.59 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 | 25-OCT-11:00 | 602.52 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 897.33 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1167.64 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 475.48 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.05 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 139.30 | 1167.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 723.31 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 512.07 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 776.98 | 06-FEB-00:50 |
March | 827.17 | 01-MAR-10:09 | 423.83 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 569.17 | 21-MAR-21:05 |
April | 827.17 | 03-APR-09:09 | 360.53 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 | 07-APR-13:00 | 472.43 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 311.93 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.99 | 29-MAY-11:50 | 273.01 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 307.83 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.44 | 19-JUN-21:03 | 186.32 | 03-JUN-17:40 |
July | 827.17 | 03-JUL-09:09 | 307.56 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.27 | 09-JUL-14:00 | 109.55 | 02-JUL-18:00 |
August | 827.17 | 01-AUG-09:09 | 351.15 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.40 | 04-AUG-21:03 | 107.40 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 407.87 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.15 | 14-SEP-14:00 | 148.66 | 10-SEP-20:00 |
October | 827.17 | 02-OCT-09:09 | 451.73 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 | 25-OCT-11:00 | 389.69 | 17-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 583.25 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 778.43 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 307.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.40 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 92.40 | 778.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 628.76 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 815.44 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 620.16 | 06-FEB-00:52 |
March | 1306.65 | 01-MAR-10:09 | 667.85 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 452.10 | 21-MAR-21:05 |
April | 1306.65 | 03-APR-09:09 | 481.24 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 | 07-APR-17:00 | 390.15 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 480.72 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.84 | 29-MAY-12:00 | 217.04 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 470.72 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.68 | 19-JUN-21:03 | 132.97 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 467.68 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.04 | 09-JUL-14:00 | 57.43 | 11-JUL-04:50 |
August | 1306.65 | 01-AUG-09:09 | 488.19 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.12 | 04-AUG-21:03 | 89.74 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 601.30 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 14-SEP-14:00 | 120.78 | 23-SEP-04:00 |
October | 1306.65 | 02-OCT-09:09 | 724.10 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 | 25-OCT-11:00 | 353.08 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 528.20 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 652.63 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 467.68 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.43 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 75.12 | 652.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 422.73 | 31-JAN-01:00 |
February | 827.22 | 01-FEB-10:09 | 521.76 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 436.48 | 05-FEB-08:40 |
March | 827.22 | 01-MAR-10:09 | 466.65 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 335.15 | 12-MAR-10:00 |
April | 827.22 | 03-APR-09:09 | 297.77 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 | 07-APR-13:00 | 266.84 | 11-APR-04:00 |
May | 827.22 | 01-MAY-09:09 | 305.12 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 | 29-MAY-12:00 | 152.51 | 03-MAY-04:00 |
June | 827.22 | 01-JUN-09:09 | 283.83 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.06 | 19-JUN-21:03 | 92.00 | 02-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 268.66 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.22 | 09-JUL-14:00 | 43.41 | 02-JUL-18:55 |
August | 827.22 | 01-AUG-09:09 | 297.39 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 | 04-AUG-21:03 | 64.54 | 20-AUG-06:00 |
September | 827.22 | 01-SEP-09:09 | 311.25 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 14-SEP-14:00 | 82.29 | 17-SEP-10:00 |
October | 827.22 | 02-OCT-09:09 | 462.70 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 25-OCT-11:00 | 260.00 | 08-OCT-08:00 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 357.42 | 23-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 438.72 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.41 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 49.58 | 438.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 39761.09 | 02-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 810.71 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 43221.94 | 06-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 607.85 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 33168.88 | 23-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 478.69 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2600.42 | 07-APR-17:00 | 23253.49 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 481.72 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5792.27 | 30-MAY-11:05 | 15884.85 | 01-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 474.41 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13859.81 | 19-JUN-11:02 | 9911.28 | 02-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 471.73 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10742.99 | 07-JUL-11:02 | 3470.29 | 11-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 488.17 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11156.08 | 24-AUG-16:02 | 6520.16 | 25-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 580.66 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6329.29 | 14-SEP-16:05 | 13680.57 | 11-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 700.12 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1007.88 | 25-OCT-11:10 | 20178.24 | 31-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 32622.13 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 33444.72 | 22-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 471.73 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3470.29 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13859.81 | 43221.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 423.56 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 510.13 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 415.56 | 06-FEB-00:52 |
March | 827.17 | 01-MAR-10:09 | 418.86 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 312.12 | 21-MAR-21:10 |
April | 827.17 | 03-APR-09:09 | 353.56 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.38 | 07-APR-13:00 | 275.45 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 310.31 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.99 | 29-MAY-12:00 | 153.68 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 306.04 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.23 | 19-JUN-21:03 | 97.26 | 02-JUN-22:00 |
July | 827.17 | 03-JUL-09:09 | 305.76 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.86 | 09-JUL-14:00 | 53.15 | 02-JUL-18:55 |
August | 827.17 | 01-AUG-09:09 | 314.34 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 04-AUG-21:03 | 64.60 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 402.35 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 14-SEP-14:00 | 85.18 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 447.76 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.46 | 25-OCT-11:00 | 242.12 | 08-OCT-08:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 353.91 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 440.13 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 305.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.15 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 49.37 | 440.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 966.69 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 818.72 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 977.61 | 06-FEB-00:52 |
March | 1306.65 | 01-MAR-10:09 | 678.02 | 02-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 713.59 | 21-MAR-21:10 |
April | 1306.65 | 03-APR-09:09 | 484.52 | 21-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 07-APR-13:00 | 624.96 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 484.04 | 08-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.46 | 29-MAY-12:10 | 360.17 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 474.54 | 29-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.09 | 19-JUN-21:03 | 215.00 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 471.66 | 24-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.71 | 09-JUL-14:00 | 99.09 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 491.14 | 16-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.99 | 04-AUG-21:03 | 141.85 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 613.80 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.78 | 14-SEP-14:00 | 184.19 | 17-SEP-10:00 |
October | 1306.65 | 02-OCT-09:09 | 731.21 | 31-OCT-15:00 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 25-OCT-11:00 | 523.81 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 793.92 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 960.35 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 471.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.09 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 116.99 | 977.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 563.23 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 644.46 | 31-JAN-01:00 |
February | 805.43 | 01-FEB-08:09 | 523.21 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 675.20 | 05-FEB-08:50 |
March | 805.43 | 01-MAR-08:09 | 469.98 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 543.10 | 12-MAR-10:00 |
April | 805.43 | 03-APR-07:10 | 299.91 | 21-APR-15:00 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 07-APR-13:00 | 415.41 | 11-APR-04:00 |
May | 805.43 | 01-MAY-07:10 | 306.97 | 19-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.34 | 29-MAY-12:10 | 240.19 | 03-MAY-04:00 |
June | 805.43 | 01-JUN-07:10 | 286.79 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.91 | 19-JUN-21:03 | 141.93 | 02-JUN-22:00 |
July | 805.43 | 03-JUL-07:10 | 281.28 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.34 | 09-JUL-13:38 | 66.98 | 11-JUL-05:00 |
August | 805.43 | 01-AUG-07:10 | 299.76 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.76 | 04-AUG-21:03 | 98.55 | 20-AUG-06:00 |
September | 805.43 | 01-SEP-07:10 | 312.81 | 26-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.85 | 14-SEP-14:00 | 122.96 | 17-SEP-10:00 |
October | 805.43 | 02-OCT-07:10 | 466.17 | 31-OCT-15:00 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | 25-OCT-11:00 | 390.62 | 08-OCT-08:00 |
November | 805.43 | 01-NOV-07:10 | 563.23 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 529.62 | 23-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 563.23 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 644.06 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 281.28 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.98 | |||||
Maximum of Months | 805.43 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 77.76 | 675.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 999.26 | 31-JAN-01:00 |
February | 1306.65 | 01-FEB-10:09 | 814.15 | 15-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 990.46 | 05-FEB-10:00 |
March | 1306.65 | 01-MAR-10:09 | 620.37 | 16-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 815.43 | 12-MAR-10:00 |
April | 1306.65 | 03-APR-09:09 | 482.13 | 21-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.48 | 07-APR-13:00 | 633.42 | 11-APR-04:00 |
May | 1306.65 | 01-MAY-09:09 | 484.98 | 08-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.29 | 29-MAY-12:07 | 364.80 | 03-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 478.02 | 29-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.03 | 19-JUN-21:03 | 214.92 | 02-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 475.47 | 24-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.44 | 09-JUL-14:00 | 97.28 | 11-JUL-05:00 |
August | 1306.65 | 01-AUG-09:09 | 491.13 | 16-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.64 | 04-AUG-21:03 | 142.88 | 20-AUG-06:00 |
September | 1306.65 | 01-SEP-09:09 | 594.23 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 14-SEP-14:00 | 193.04 | 30-SEP-24:00 |
October | 1306.65 | 02-OCT-09:09 | 708.58 | 31-OCT-15:00 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.62 | 25-OCT-11:00 | 563.86 | 08-OCT-08:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 814.19 | 23-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1013.56 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 475.47 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.28 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 116.64 | 1013.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 645.89 | 31-JAN-01:00 |
February | 827.17 | 01-FEB-10:09 | 512.06 | 15-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 651.74 | 06-FEB-00:52 |
March | 827.17 | 01-MAR-10:09 | 423.82 | 16-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 488.10 | 21-MAR-21:10 |
April | 827.17 | 03-APR-09:09 | 360.52 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 07-APR-13:00 | 421.89 | 11-APR-04:00 |
May | 827.17 | 01-MAY-09:09 | 311.93 | 08-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.80 | 29-MAY-12:10 | 245.25 | 03-MAY-04:00 |
June | 827.17 | 01-JUN-09:09 | 307.83 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.10 | 19-JUN-21:03 | 152.45 | 03-JUN-17:40 |
July | 827.17 | 03-JUL-09:09 | 307.56 | 24-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.30 | 09-JUL-14:00 | 84.34 | 02-JUL-17:50 |
August | 827.17 | 01-AUG-09:09 | 351.13 | 16-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.40 | 04-AUG-21:03 | 96.64 | 20-AUG-06:00 |
September | 827.17 | 01-SEP-09:09 | 407.86 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.86 | 14-SEP-14:00 | 126.80 | 30-SEP-24:00 |
October | 827.17 | 02-OCT-09:09 | 451.72 | 06-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | 25-OCT-11:00 | 350.97 | 17-OCT-24:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 529.01 | 23-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 648.01 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 307.56 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.34 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 77.40 | 651.74 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1379.84 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1370.70 | 06-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 997.95 | 21-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.16 | 07-APR-13:00 | 875.99 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.41 | 29-MAY-12:00 | 501.61 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.15 | 19-JUN-21:03 | 287.09 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.18 | 09-JUL-14:00 | 129.10 | 11-JUL-04:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.50 | 12-AUG-18:53 | 191.18 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.16 | 14-SEP-14:00 | 255.22 | 30-SEP-24:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 | 25-OCT-11:00 | 751.02 | 08-OCT-08:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1150.64 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1423.63 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.10 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.50 | 1423.63 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1704.41 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1674.89 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1250.98 | 21-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 | 07-APR-13:00 | 1108.91 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.76 | 29-MAY-11:53 | 629.23 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.57 | 19-JUN-21:03 | 368.34 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.19 | 09-JUL-14:00 | 165.19 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.75 | 12-AUG-18:53 | 242.77 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.07 | 14-SEP-14:00 | 318.03 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 25-OCT-11:00 | 919.42 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1409.38 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1711.50 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.19 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.75 | 1711.50 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1638.01 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1673.10 | 06-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1303.85 | 21-MAR-21:05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 08-APR-10:00 | 1045.96 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.78 | 30-MAY-13:00 | 596.75 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.92 | 19-JUN-21:03 | 362.09 | 03-JUN-18:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.59 | 07-JUL-22:00 | 204.52 | 02-JUL-18:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.56 | 04-AUG-21:03 | 215.80 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.21 | 14-SEP-14:00 | 305.67 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 863.67 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1317.82 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1692.22 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.56 | 1692.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 10511.27 | 27-JAN-08:40 | 12070.02 | 8440.40 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10921.33 | 24-FEB-08:50 | 6035.01 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17823.59 | 31-MAR-07:05 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33540.89 | 11-APR-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39697.19 | 23-MAY-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41596.24 | 26-JUN-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 43316.07 | 24-JUL-04:02 | 0.00 | 2344.59 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44043.04 | 07-AUG-04:02 | 0.00 | 2344.59 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41397.60 | 06-SEP-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39745.58 | 14-OCT-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20872.11 | 03-NOV-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13104.27 | 20-DEC-08:20 | 24140.03 | 16880.81 | 72740.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 10511.27 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44043.04 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 452.10 | 17-JAN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 |
February | 812.57 | 18-FEB-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.49 |
March | 2637.24 | 03-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.06 |
April | 6882.96 | 07-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 | 0.00 |
May | 10708.46 | 30-MAY-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 | 0.00 |
June | 12017.36 | 19-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.09 | 0.00 |
July | 11198.86 | 10-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.65 | 0.00 |
August | 10708.50 | 01-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.12 | 0.00 |
September | 9476.90 | 01-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.15 | 0.00 |
October | 6588.01 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 |
November | 2383.85 | 04-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 |
December | 392.39 | 20-DEC-13:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 392.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12017.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.65 | 125.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1558.63 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.72 |
February | 1297.00 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.22 |
March | 2386.66 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.73 |
April | 2010.87 | 10-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.33 |
May | 4593.01 | 30-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.94 | 0.00 |
June | 4745.97 | 19-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.15 | 0.00 |
July | 5211.14 | 10-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.63 | 0.00 |
August | 5309.25 | 14-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 0.00 |
September | 4795.57 | 05-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.14 | 0.00 |
October | 2823.11 | 04-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.24 |
November | 848.37 | 04-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 |
December | 827.57 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 827.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5309.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.63 | 788.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1946.30 | 11-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.41 |
February | 2464.66 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.42 |
March | 2740.15 | 29-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.28 |
April | 2410.85 | 14-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.30 |
May | 4686.75 | 30-MAY-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.47 | 0.00 |
June | 6324.35 | 19-JUN-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.15 | 0.00 |
July | 5576.94 | 13-JUL-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 | 0.00 |
August | 5339.39 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 0.00 |
September | 5089.00 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.51 |
October | 3528.34 | 04-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 |
November | 1665.45 | 16-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.65 |
December | 2126.71 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1665.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6324.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.15 | 213.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6582.58 | 20-JAN-16:55 | 12070.02 | 8440.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6585.71 | 02-FEB-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7832.28 | 29-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13029.86 | 10-APR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29944.46 | 30-MAY-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30417.35 | 26-JUN-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30633.24 | 24-JUL-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31893.05 | 07-AUG-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30911.86 | 05-SEP-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19245.81 | 06-OCT-05:03 | 1905.79 | 1406.75 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9882.48 | 03-NOV-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6748.51 | 21-DEC-16:20 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6582.58 | 0.00 | 1406.75 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31893.05 | 12070.02 | 8440.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6465.29 | 20-JAN-16:40 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6545.76 | 02-FEB-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7836.97 | 29-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13936.96 | 10-APR-15:50 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30326.11 | 30-MAY-05:03 | 1905.79 | 1406.75 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31157.76 | 23-JUN-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 33251.03 | 24-JUL-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 33409.29 | 07-AUG-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32667.05 | 05-SEP-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14836.43 | 04-OCT-15:50 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8390.28 | 03-NOV-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6460.70 | 21-DEC-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6460.70 | 0.00 | 1406.75 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33409.29 | 6035.01 | 4220.20 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1090.80 | 19-JAN-15:00 | 1306.65 | 443.74 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.47 |
February | 1122.90 | 24-FEB-15:50 | 1272.23 | 445.32 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.95 |
March | 1600.20 | 28-MAR-14:10 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.18 |
April | 3728.48 | 07-APR-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 | 0.00 |
May | 7291.59 | 29-MAY-14:23 | 267.84 | 94.29 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 |
June | 9022.33 | 26-JUN-06:03 | 803.52 | 424.37 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 |
July | 9675.17 | 10-JUL-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.32 |
August | 10801.61 | 13-AUG-15:52 | 401.76 | 141.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 47.01 | 0.00 |
September | 5904.03 | 01-SEP-14:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 | 0.00 |
October | 3940.79 | 04-OCT-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.31 | 0.00 |
November | 1589.90 | 03-NOV-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 |
December | 1119.21 | 20-DEC-14:00 | 1272.23 | 462.18 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1090.80 | 0.00 | 94.29 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10801.61 | 1306.65 | 494.26 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 47.01 | 119.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1166.07 | 19-JAN-10:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.88 |
February | 1218.65 | 22-FEB-10:10 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.99 |
March | 2970.25 | 29-MAR-09:40 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.92 |
April | 5628.73 | 28-APR-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.04 |
May | 12937.26 | 28-MAY-08:52 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.67 |
June | 12797.33 | 04-JUN-09:12 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.01 |
July | 12774.79 | 02-JUL-08:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.75 |
August | 12190.42 | 27-AUG-09:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 |
September | 12625.49 | 04-SEP-09:12 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 |
October | 5058.13 | 05-OCT-09:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 |
November | 1566.06 | 02-NOV-09:40 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.68 |
December | 1192.97 | 20-DEC-09:50 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1166.07 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 | |
Maximum of Months | 12937.26 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5222.06 | 19-JAN-13:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.02 |
February | 5614.27 | 02-FEB-14:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.65 |
March | 8058.60 | 03-MAR-13:25 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.27 |
April | 9286.44 | 07-APR-12:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 | 0.00 |
May | 15581.82 | 29-MAY-13:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.19 |
June | 12249.53 | 04-JUN-13:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.75 |
July | 15636.17 | 04-JUL-12:53 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 12.98 | 0.00 |
August | 15866.53 | 13-AUG-12:32 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 55.89 | 0.00 |
September | 16175.65 | 04-SEP-13:12 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.81 |
October | 15936.95 | 22-OCT-12:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 |
November | 9823.95 | 02-NOV-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.61 |
December | 5229.57 | 21-DEC-13:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5222.06 | 267.84 | 94.29 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16175.65 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 55.89 | 123.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1461.02 | 19-JAN-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.86 |
February | 1604.27 | 22-FEB-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.71 |
March | 4784.64 | 29-MAR-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.52 |
April | 11177.31 | 09-APR-17:03 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.39 |
May | 11910.66 | 21-MAY-15:13 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.89 |
June | 14052.56 | 04-JUN-16:32 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.86 |
July | 13854.31 | 02-JUL-16:02 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.73 |
August | 13780.70 | 13-AUG-15:52 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 | 0.00 |
September | 13502.20 | 10-SEP-15:32 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.55 |
October | 6983.11 | 04-OCT-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 |
November | 3140.66 | 03-NOV-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.48 |
December | 1413.55 | 08-DEC-15:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1413.55 | 0.00 | 59.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14052.56 | 805.38 | 268.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 | 100.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1098.03 | 20-JAN-14:50 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.28 |
February | 1106.75 | 24-FEB-14:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.20 |
March | 1416.78 | 28-MAR-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.92 |
April | 1987.66 | 10-APR-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 |
May | 4182.29 | 30-MAY-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 | 0.00 |
June | 5814.29 | 26-JUN-06:03 | 803.52 | 424.37 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
July | 7057.72 | 10-JUL-06:03 | 803.52 | 458.96 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 4.07 | 0.00 |
August | 6508.55 | 14-AUG-06:03 | 803.52 | 424.37 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 4833.46 | 05-SEP-13:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.53 | 0.00 |
October | 3516.50 | 05-OCT-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.77 |
November | 1608.03 | 03-NOV-14:10 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 |
December | 1188.32 | 20-DEC-14:10 | 1306.65 | 466.23 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1098.03 | 803.52 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7057.72 | 1306.65 | 466.23 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 11.96 | 59.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 974.76 | 27-JAN-10:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 |
February | 990.02 | 22-FEB-10:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 |
March | 1888.46 | 29-MAR-09:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 |
April | 3755.82 | 28-APR-09:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.34 |
May | 8396.63 | 29-MAY-09:02 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
June | 10269.26 | 04-JUN-09:52 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 |
July | 8897.27 | 02-JUL-09:22 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 |
August | 8388.35 | 27-AUG-10:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.48 |
September | 10944.79 | 04-SEP-09:42 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.05 |
October | 4624.32 | 05-OCT-09:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.91 |
November | 2051.93 | 03-NOV-09:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.28 |
December | 1091.53 | 20-DEC-09:50 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 974.76 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | |
Maximum of Months | 10944.79 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1485.14 | 07-JAN-14:20 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.47 |
February | 1710.95 | 25-FEB-13:20 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.41 |
March | 2579.30 | 03-MAR-14:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1716.42 |
April | 6840.18 | 07-APR-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1988.00 | 0.00 |
May | 10801.27 | 30-MAY-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5609.24 | 0.00 |
June | 13137.95 | 19-JUN-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 11181.94 | 0.00 |
July | 12266.81 | 07-JUL-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9073.69 | 0.00 |
August | 12596.84 | 20-AUG-12:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
September | 13568.70 | 04-SEP-11:42 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.73 |
October | 12809.30 | 22-OCT-12:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.78 |
November | 7195.23 | 02-NOV-12:07 | 7633.40 | 2546.19 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1685.21 |
December | 2818.32 | 02-DEC-14:00 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1485.14 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13568.70 | 7633.40 | 2546.19 | 8611.42 | 0.00 | 0.00 | 0.00 | 0.00 | 11181.94 | 1716.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1143.97 | 20-JAN-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.10 |
February | 1202.42 | 22-FEB-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 |
March | 2889.62 | 27-MAR-16:50 | 254.33 | 149.24 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 |
April | 5141.09 | 10-APR-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.42 |
May | 6376.23 | 30-MAY-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 | 0.00 |
June | 10822.33 | 18-JUN-17:52 | 0.00 | 74.61 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.84 |
July | 8996.44 | 02-JUL-16:42 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.99 |
August | 8052.19 | 20-AUG-16:02 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 |
September | 10898.59 | 04-SEP-17:02 | 0.00 | 74.61 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.36 |
October | 6688.87 | 15-OCT-16:13 | 127.16 | 44.77 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.86 |
November | 3031.11 | 03-NOV-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.18 |
December | 1157.21 | 08-DEC-15:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1143.97 | 0.00 | 44.77 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10898.59 | 805.38 | 268.64 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 | 68.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1124.79 | 20-JAN-15:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.10 |
February | 1148.41 | 24-FEB-14:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.05 |
March | 1545.68 | 28-MAR-14:10 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.12 |
April | 3311.53 | 10-APR-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.13 |
May | 6692.24 | 30-MAY-06:03 | 803.52 | 424.37 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 |
June | 8004.52 | 26-JUN-06:03 | 803.52 | 424.37 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 |
July | 8004.33 | 10-JUL-06:03 | 803.52 | 463.56 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 0.00 |
August | 7944.35 | 05-AUG-05:03 | 535.68 | 384.31 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 0.00 |
September | 5784.50 | 02-SEP-05:03 | 535.68 | 395.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
October | 3779.10 | 05-OCT-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 |
November | 1755.81 | 02-NOV-13:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.35 |
December | 1170.29 | 20-DEC-14:00 | 1272.23 | 462.17 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1124.79 | 535.68 | 384.31 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8004.52 | 1306.65 | 463.56 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 97.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1217.63 | 19-JAN-10:00 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.73 |
February | 1297.00 | 22-FEB-09:50 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.01 |
March | 3588.37 | 29-MAR-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.59 |
April | 5945.96 | 28-APR-08:40 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.90 |
May | 12117.13 | 29-MAY-08:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 |
June | 9305.01 | 25-JUN-08:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 |
July | 13138.03 | 02-JUL-07:52 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 |
August | 11708.67 | 27-AUG-09:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 |
September | 13081.43 | 04-SEP-08:22 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.84 |
October | 5360.22 | 05-OCT-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 |
November | 2287.60 | 02-NOV-09:00 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.64 |
December | 1295.27 | 20-DEC-09:40 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1217.63 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 | |
Maximum of Months | 13138.03 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5423.17 | 19-JAN-13:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.23 |
February | 5917.93 | 02-FEB-13:50 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.75 |
March | 7953.43 | 29-MAR-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.46 |
April | 8573.71 | 07-APR-12:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 | 0.00 |
May | 9245.30 | 28-MAY-12:23 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.36 |
June | 9813.46 | 18-JUN-13:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 |
July | 13850.38 | 04-JUL-12:53 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 0.00 |
August | 14102.86 | 20-AUG-11:53 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 |
September | 15371.16 | 04-SEP-11:42 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 |
October | 14462.95 | 22-OCT-12:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.07 |
November | 10093.29 | 02-NOV-12:50 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.67 |
December | 6133.36 | 21-DEC-13:13 | 5088.93 | 1697.46 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5423.17 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15371.16 | 5088.93 | 1697.46 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 102.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1392.14 | 20-JAN-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.43 |
February | 1875.91 | 24-FEB-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.20 |
March | 4785.83 | 29-MAR-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.95 |
April | 10440.52 | 09-APR-17:03 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.37 |
May | 11398.32 | 28-MAY-15:02 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 |
June | 12828.18 | 18-JUN-15:51 | 296.72 | 104.46 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 |
July | 13735.34 | 02-JUL-16:31 | 296.72 | 104.46 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.09 |
August | 12397.70 | 13-AUG-15:52 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 0.00 |
September | 12755.19 | 04-SEP-14:22 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 |
October | 6717.10 | 04-OCT-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.69 |
November | 3340.04 | 03-NOV-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
December | 1371.33 | 08-DEC-15:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1371.33 | 0.00 | 59.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13735.34 | 805.38 | 268.64 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 21.65 | 79.20 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.138479E+12 | 241761.03 | 02-JAN-07:10 | 0.481076E+11 | 96772.94 | 02-JAN-08:39 |
February | 0.116739E+12 | 195622.51 | 06-FEB-07:10 | 0.472626E+11 | 100730.93 | 06-FEB-07:30 |
March | 0.105135E+12 | 135302.75 | 20-MAR-06:10 | 0.287890E+11 | 63016.73 | 23-MAR-06:19 |
April | 0.912203E+11 | 104120.62 | 03-APR-06:10 | 0.125433E+11 | 36923.26 | 03-APR-06:30 |
May | 0.101820E+12 | 139859.74 | 30-MAY-13:00 | 0.915621E+10 | 13257.24 | 01-MAY-06:19 |
June | 0.130402E+12 | 155245.74 | 19-JUN-12:09 | 0.860168E+10 | 9071.49 | 01-JUN-11:00 |
July | 0.147781E+12 | 146373.74 | 07-JUL-14:30 | 0.821340E+10 | 8955.81 | 03-JUL-11:00 |
August | 0.156400E+12 | 150868.36 | 16-AUG-15:09 | 0.859647E+10 | 8919.17 | 31-AUG-11:50 |
September | 0.115223E+12 | 130605.47 | 07-SEP-15:20 | 0.814190E+10 | 8992.25 | 29-SEP-11:39 |
October | 0.101658E+12 | 108902.96 | 04-OCT-15:39 | 0.918578E+10 | 27826.40 | 28-OCT-06:00 |
November | 0.998748E+11 | 145775.06 | 24-NOV-07:10 | 0.204935E+11 | 64510.89 | 24-NOV-07:30 |
December | 0.115904E+12 | 154667.83 | 11-DEC-07:10 | 0.370318E+11 | 64638.87 | 22-DEC-07:19 |
Annual Sum or Average | 0.142064E+13 | 0.246123E+12 | ||||
Minimum of Months | 0.912203E+11 | 104120.62 | 0.814190E+10 | 8919.17 | ||
Maximum of Months | 0.156400E+12 | 241761.03 | 0.481076E+11 | 100730.93 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.176100E+11 | 0.570882E+10 | 0.593559E+11 | 0.980331E+09 | 0.440062E+10 | 1312252.65 | 0.504222E+11 | 47150.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156228E+11 | 0.457304E+10 | 0.537310E+11 | 0.886868E+09 | 0.380748E+10 | 1186778.30 | 0.381167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182335E+11 | 0.426592E+10 | 0.617796E+11 | 0.102610E+10 | 0.443228E+10 | 1343621.24 | 0.150724E+11 | 0.323386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161032E+11 | 0.342381E+10 | 0.572952E+11 | 0.943595E+09 | 0.493675E+10 | 1267813.82 | 0.557285E+10 | 0.294367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172555E+11 | 0.307731E+10 | 0.605677E+11 | 0.100271E+10 | 0.761312E+10 | 1327936.95 | 0.906509E+09 | 0.113961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171026E+11 | 0.277966E+10 | 0.594895E+11 | 0.987027E+09 | 0.124567E+11 | 1296568.36 | 29671192.42 | 0.375556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160484E+11 | 0.295229E+10 | 0.583622E+11 | 0.959060E+09 | 0.155990E+11 | 1299182.41 | 0.00 | 0.538588E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179283E+11 | 0.330683E+10 | 0.617796E+11 | 0.102592E+10 | 0.172922E+11 | 1343621.24 | 0.00 | 0.550655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161869E+11 | 0.379176E+10 | 0.572729E+11 | 0.943409E+09 | 0.100857E+11 | 1267813.82 | 0.111402E+09 | 0.268300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169888E+11 | 0.473182E+10 | 0.593671E+11 | 0.979813E+09 | 0.741747E+10 | 1312252.65 | 0.914675E+09 | 0.112572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172453E+11 | 0.531244E+10 | 0.580818E+11 | 0.961980E+09 | 0.417327E+10 | 1278270.02 | 0.138065E+11 | 0.292198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.171279E+11 | 0.588555E+10 | 0.583511E+11 | 0.959872E+09 | 0.392102E+10 | 1299182.41 | 0.296577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203453E+12 | 0.498092E+11 | 0.705434E+12 | 0.116567E+11 | 0.961355E+11 | 15535293.87 | 0.154611E+12 | 0.199523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156228E+11 | 0.277966E+10 | 0.537310E+11 | 0.886868E+09 | 0.380748E+10 | 1186778.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182335E+11 | 0.588555E+10 | 0.617796E+11 | 0.102610E+10 | 0.172922E+11 | 1343621.24 | 0.504222E+11 | 0.550655E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.383640E+11 | 0.00 | 0.974359E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.383940E+11 | 0.00 | 0.886860E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.187249E+11 | 0.00 | 0.100640E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.351313E+10 | 0.00 | 0.903015E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 13511851.64 | 0.00 | 0.914269E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.860168E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.821340E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.859647E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.814190E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.476327E+09 | 0.00 | 0.870946E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.116037E+11 | 0.00 | 0.888976E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.277066E+11 | 0.00 | 0.932522E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138796E+12 | 0.00 | 0.107327E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.814190E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.383940E+11 | 0.00 | 0.100640E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21377.78 | 02-JAN-16:40 | 5557.43 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 833.98 | 02-JAN-16:49 | 7187.50 | 02-JAN-06:19 | 0.73 | 02-JAN-06:10 | 200766.58 | 02-JAN-06:19 |
February | 20643.55 | 15-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 832.72 | 15-FEB-16:00 | 5340.47 | 06-FEB-06:10 | 0.73 | 01-FEB-07:10 | 162408.88 | 06-FEB-07:10 |
March | 18759.98 | 16-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 831.86 | 16-MAR-07:19 | 4932.36 | 29-MAR-15:39 | 0.73 | 01-MAR-08:09 | 103121.47 | 20-MAR-06:10 |
April | 17363.11 | 21-APR-07:10 | 5557.43 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 830.02 | 21-APR-07:19 | 12585.06 | 10-APR-15:20 | 0.73 | 03-APR-06:10 | 73298.83 | 03-APR-06:10 |
May | 17375.89 | 08-MAY-07:10 | 3195.36 | 01-MAY-18:49 | 45864.70 | 01-MAY-07:10 | 830.03 | 08-MAY-07:19 | 25644.99 | 30-MAY-14:39 | 0.73 | 01-MAY-05:10 | 22784.05 | 01-MAY-06:10 |
June | 17290.00 | 29-JUN-07:10 | 3195.36 | 01-JUN-19:19 | 45864.70 | 01-JUN-07:10 | 829.92 | 29-JUN-07:19 | 25295.81 | 19-JUN-15:50 | 0.73 | 01-JUN-05:30 | 5689.48 | 02-JUN-06:19 |
July | 17246.40 | 24-JUL-07:10 | 3195.36 | 01-JUL-19:30 | 45864.70 | 03-JUL-07:10 | 829.86 | 24-JUL-07:19 | 25621.75 | 17-JUL-15:09 | 0.73 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 17515.05 | 16-AUG-07:10 | 5557.43 | 16-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 830.22 | 16-AUG-07:19 | 25339.78 | 14-AUG-15:09 | 0.73 | 01-AUG-05:30 | 0.00 | 01-AUG-00:10 |
September | 18412.32 | 27-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 831.40 | 27-SEP-07:19 | 21299.96 | 05-SEP-15:30 | 0.73 | 01-SEP-05:10 | 6901.07 | 19-SEP-06:19 |
October | 19674.99 | 31-OCT-15:00 | 5557.43 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 832.79 | 06-OCT-07:19 | 15719.67 | 04-OCT-15:50 | 0.73 | 27-OCT-16:10 | 25681.65 | 31-OCT-06:10 |
November | 21377.78 | 06-NOV-16:49 | 5557.43 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 833.98 | 06-NOV-16:00 | 6313.07 | 02-NOV-14:30 | 0.73 | 15-NOV-08:09 | 114304.20 | 24-NOV-07:10 |
December | 21377.78 | 01-DEC-16:30 | 5557.43 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 833.98 | 01-DEC-16:40 | 3911.50 | 11-DEC-07:10 | 0.73 | 01-DEC-08:09 | 116729.82 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 17246.40 | 3195.36 | 45864.70 | 829.86 | 3911.50 | 0.73 | 0.00 | |||||||
Maximum of Months | 21377.78 | 5557.43 | 45864.70 | 833.98 | 25644.99 | 0.73 | 200766.58 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 78.58 | 15-JAN-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15325.54 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 27874.21 | 07-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 58476.96 | 30-MAY-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75494.26 | 19-JUN-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 65864.00 | 07-JUL-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70429.57 | 16-AUG-12:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54813.94 | 07-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 37709.54 | 04-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6486.07 | 03-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 75494.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 241761.03 | 02-JAN-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 7164.53 | 0.73 | 200569.99 | 0.00 | 0.00 |
February | 195622.51 | 06-FEB-07:10 | 6542.40 | 21098.80 | 0.00 | 243.52 | 5328.19 | 0.73 | 162408.88 | 0.00 | 0.00 |
March | 135302.75 | 20-MAR-06:10 | 7126.03 | 21098.80 | 0.00 | 243.52 | 3712.20 | 0.73 | 103121.47 | 0.00 | 0.00 |
April | 104120.62 | 03-APR-06:10 | 6129.44 | 21098.80 | 0.00 | 243.40 | 3349.43 | 0.73 | 73298.83 | 0.00 | 0.00 |
May | 139859.74 | 30-MAY-13:00 | 16818.70 | 40588.47 | 0.00 | 827.42 | 23147.47 | 0.73 | 0.00 | 58476.96 | 0.00 |
June | 155245.74 | 19-JUN-12:09 | 16818.70 | 42402.18 | 0.00 | 828.07 | 20298.99 | 0.73 | 0.00 | 74897.07 | 0.00 |
July | 146373.74 | 07-JUL-14:30 | 16818.70 | 40588.47 | 0.00 | 827.42 | 22793.96 | 0.73 | 0.00 | 65344.46 | 0.00 |
August | 150868.36 | 16-AUG-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 22871.02 | 0.73 | 0.00 | 68277.55 | 0.00 |
September | 130605.47 | 07-SEP-15:20 | 16818.70 | 42072.41 | 0.00 | 827.95 | 20093.79 | 0.73 | 0.00 | 50791.90 | 0.00 |
October | 108902.96 | 04-OCT-15:39 | 16818.70 | 42072.41 | 0.00 | 827.95 | 15353.56 | 0.73 | 0.00 | 33829.62 | 0.00 |
November | 145775.06 | 24-NOV-07:10 | 6229.66 | 21098.80 | 0.00 | 243.43 | 3898.24 | 0.73 | 114304.20 | 0.00 | 0.00 |
December | 154667.83 | 11-DEC-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 3911.50 | 0.73 | 116729.82 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 104120.62 | 6129.44 | 21098.80 | 0.00 | 243.40 | 3349.43 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 241761.03 | 16818.70 | 42402.18 | 5557.43 | 828.07 | 23147.47 | 0.73 | 200569.99 | 74897.07 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 88145.52 | 02-JAN-08:39 | 0.00 | 9468.98 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 92594.63 | 06-FEB-07:40 | 0.00 | 9472.57 | 09-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 55405.97 | 23-MAR-06:10 | 0.00 | 9436.28 | 03-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 29589.03 | 03-APR-06:19 | 0.00 | 9344.80 | 05-APR-11:09 | 0.00 |
May | 0.00 | 0.00 | 6136.66 | 01-MAY-06:10 | 0.00 | 9226.69 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9071.49 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8955.81 | 03-JUL-11:00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8919.17 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8992.25 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 20086.77 | 28-OCT-06:49 | 0.00 | 9131.26 | 31-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 56472.37 | 24-NOV-07:19 | 0.00 | 9272.18 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 56480.23 | 22-DEC-07:19 | 0.00 | 9390.29 | 28-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8919.17 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 92594.63 | 0.00 | 9472.57 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.56 | 0.50 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.17 | 0.00 | 26.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 19.56 | 0.50 | 19.56 | 0.67 | 22.21 | 0.00 | 22.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.56 | 0.50 | 19.56 | 0.50 | 26.17 | 0.00 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.00 | 1.83 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 26.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 19.00 | 1.83 | 19.24 | 0.17 | 19.51 | 0.00 | 19.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.00 | 1.83 | 19.24 | 0.17 | 26.16 | 0.00 | 26.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 18.62 | 1.83 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
February | 1.00 | 18.09 | 0.50 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.44 | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 18.52 | 2.50 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.67 | 19.44 | 1.83 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.50 | 16.22 | 9.50 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 |
February | 14.83 | 17.02 | 6.33 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
March | 0.50 | 17.87 | 0.17 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.43 | 1.67 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.48 | 1.33 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.50 | 17.03 | 0.33 | 17.43 | 0.00 | 17.43 | 0.00 | 17.43 |
December | 2.33 | 16.25 | 0.33 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
Annual Sum or Average | 38.67 | 16.59 | 16.67 | 17.05 | 3.33 | 17.64 | 3.00 | 18.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.50 | 17.87 | 9.50 | 18.26 | 1.83 | 27.48 | 1.67 | 27.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.50 | 15.16 | 2.33 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
February | 7.83 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
March | 0.33 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.84 | 4.67 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.70 | 3.17 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.80 | 10.00 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.84 | 4.50 | 27.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.87 | 4.17 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
December | 2.17 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
Annual Sum or Average | 23.83 | 15.32 | 2.33 | 15.33 | 27.00 | 21.67 | 26.50 | 23.71 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.50 | 17.07 | 2.33 | 17.07 | 10.17 | 27.87 | 10.00 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.17 | 15.60 | 2.50 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
February | 6.17 | 15.96 | 0.67 | 16.28 | 0.00 | 16.28 | 0.00 | 16.28 |
March | 0.33 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.63 | 2.83 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.50 | 2.50 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.70 | 7.67 | 27.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.90 | 5.00 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.11 | 5.50 | 28.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.82 | 2.17 | 27.82 |
November | 0.67 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
December | 1.00 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
Annual Sum or Average | 19.33 | 15.81 | 3.17 | 16.05 | 26.50 | 22.41 | 25.67 | 24.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.17 | 17.21 | 2.50 | 17.21 | 7.83 | 28.11 | 7.67 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.67 | 15.07 | 3.50 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
February | 7.50 | 15.30 | 0.17 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
March | 0.17 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.76 | 0.50 | 27.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.67 | 3.67 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.03 | 3.00 | 28.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.12 | 5.00 | 28.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.13 | 2.67 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.13 | 2.67 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.47 | 0.50 | 27.47 |
November | 0.83 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
December | 2.00 | 15.75 | 0.17 | 15.69 | 0.00 | 15.69 | 0.00 | 15.69 |
Annual Sum or Average | 23.17 | 15.29 | 3.83 | 15.24 | 25.00 | 21.38 | 18.00 | 23.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 0.00 | 15.05 |
Maximum of Months | 12.67 | 17.07 | 3.50 | 17.07 | 7.67 | 28.13 | 5.00 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.33 | 17.05 | 7.33 | 17.56 | 0.00 | 17.56 | 0.00 | 17.56 |
February | 2.83 | 19.07 | 2.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 15.17 | 17.43 | 9.50 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.33 | 19.07 | 7.33 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 15.38 | 1.00 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
February | 0.50 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.62 | 1.50 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.45 | 1.33 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.65 | 3.67 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.53 | 2.67 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.63 | 4.00 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 6.17 | 15.52 | 1.00 | 15.75 | 13.17 | 23.42 | 13.17 | 25.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 17.06 | 1.00 | 17.06 | 4.00 | 27.65 | 4.00 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 81.33 | 16.77 | 79.17 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
February | 73.67 | 16.64 | 73.50 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
March | 58.17 | 17.73 | 58.17 | 17.73 | 0.00 | 17.73 | 0.00 | 17.73 |
April | 29.33 | 18.89 | 29.33 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
May | 3.50 | 19.68 | 3.50 | 19.68 | 0.83 | 20.22 | 0.83 | 20.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.76 | 2.67 | 25.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 25.57 | 9.83 | 25.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 25.51 | 21.67 | 25.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.08 | 12.50 | 26.07 |
October | 4.17 | 19.37 | 4.17 | 19.37 | 3.67 | 21.87 | 3.67 | 23.19 |
November | 43.83 | 18.44 | 43.83 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
December | 64.83 | 17.54 | 64.83 | 17.54 | 0.00 | 17.54 | 0.00 | 17.54 |
Annual Sum or Average | 358.83 | 17.47 | 356.50 | 17.48 | 51.33 | 18.04 | 51.17 | 18.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 | 0.00 | 16.64 |
Maximum of Months | 81.33 | 19.68 | 79.17 | 19.68 | 21.67 | 26.08 | 21.67 | 26.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.67 | 15.54 | 2.00 | 15.87 | 0.00 | 15.87 | 0.00 | 15.87 |
February | 0.50 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.59 | 2.33 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.69 | 3.50 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.78 | 1.83 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.83 | 2.17 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.41 | 0.33 | 27.41 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7.17 | 15.64 | 2.00 | 15.93 | 13.50 | 22.94 | 10.33 | 24.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.67 | 17.01 | 2.00 | 17.01 | 4.83 | 27.83 | 3.50 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.17 | 16.34 | 5.00 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
February | 3.00 | 18.41 | 1.83 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
December | 0.17 | 19.39 | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Annual Sum or Average | 13.50 | 16.85 | 7.00 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.17 | 19.39 | 5.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.50 | 15.37 | 1.33 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
February | 1.00 | 16.77 | 0.17 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.81 | 4.17 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.78 | 2.17 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.83 | 6.50 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.74 | 4.33 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.95 | 3.67 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
December | 0.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
Annual Sum or Average | 7.83 | 15.63 | 1.50 | 15.83 | 21.00 | 24.13 | 21.00 | 25.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.50 | 17.24 | 1.33 | 17.24 | 6.50 | 27.95 | 6.50 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 15.56 | 1.17 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
February | 0.83 | 17.27 | 0.17 | 17.58 | 0.00 | 17.58 | 0.00 | 17.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.55 | 1.67 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.35 | 0.83 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.57 | 5.50 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.83 | 4.00 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.02 | 5.33 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.63 | 4.17 | 27.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.33 | 27.26 |
Annual Sum or Average | 6.50 | 15.77 | 1.33 | 16.21 | 22.17 | 24.71 | 22.00 | 25.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.67 | 17.27 | 1.17 | 17.58 | 5.50 | 28.02 | 5.50 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 15.32 | 1.83 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
February | 1.50 | 16.17 | 0.17 | 16.48 | 0.00 | 16.48 | 0.00 | 16.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.68 | 0.50 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.62 | 2.67 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.92 | 2.50 | 27.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.97 | 4.33 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.98 | 2.33 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.04 | 2.67 | 28.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.50 | 0.50 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.50 | 15.47 | 2.00 | 15.64 | 20.67 | 23.77 | 15.50 | 25.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 16.17 | 1.83 | 16.48 | 6.33 | 28.04 | 4.33 | 28.05 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.41 | 60.33 | 22.16 | 60.33 | 21.96 |
February | 454.00 | 23.00 | 4.33 | 22.98 | 4.33 | 22.96 |
March | 485.33 | 23.59 | 0.00 | 23.59 | 0.00 | 23.59 |
April | 277.83 | 23.71 | 40.33 | 23.88 | 0.00 | 23.88 |
May | 43.00 | 23.93 | 204.67 | 24.45 | 0.00 | 24.45 |
June | 0.00 | 0.00 | 429.50 | 24.39 | 0.00 | 24.39 |
July | 0.00 | 0.00 | 497.00 | 24.41 | 0.00 | 24.41 |
August | 0.00 | 0.00 | 477.67 | 24.42 | 0.00 | 24.42 |
September | 6.00 | 23.99 | 374.50 | 24.47 | 0.00 | 24.47 |
October | 65.00 | 24.01 | 264.00 | 24.35 | 0.00 | 24.35 |
November | 309.00 | 23.54 | 51.83 | 23.76 | 0.00 | 23.76 |
December | 497.00 | 23.28 | 0.00 | 23.28 | 0.00 | 23.28 |
Annual Sum or Average | 2639.17 | 23.23 | 2404.17 | 23.76 | 64.67 | 23.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.16 | 0.00 | 21.96 |
Maximum of Months | 502.00 | 24.01 | 497.00 | 24.47 | 60.33 | 24.47 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.97 | 226.50 | 20.76 | 226.50 | 20.66 |
February | 454.00 | 21.34 | 179.33 | 21.20 | 179.33 | 21.12 |
March | 514.00 | 22.25 | 8.00 | 22.22 | 8.00 | 22.20 |
April | 418.33 | 22.89 | 11.83 | 22.94 | 0.33 | 22.94 |
May | 202.67 | 23.48 | 105.50 | 23.74 | 0.00 | 23.74 |
June | 13.83 | 23.73 | 402.00 | 24.24 | 0.00 | 24.24 |
July | 0.00 | 0.00 | 490.83 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 451.83 | 24.32 | 0.00 | 24.32 |
September | 55.83 | 23.57 | 287.50 | 24.21 | 0.00 | 24.21 |
October | 221.00 | 23.51 | 159.50 | 23.78 | 0.00 | 23.78 |
November | 474.33 | 22.41 | 46.00 | 22.27 | 46.00 | 22.15 |
December | 497.00 | 21.48 | 115.67 | 21.33 | 115.67 | 21.23 |
Annual Sum or Average | 3353.00 | 22.11 | 2484.50 | 22.67 | 575.83 | 22.48 |
Minimum of Months | 0.00 | 0.00 | 8.00 | 20.76 | 0.00 | 20.66 |
Maximum of Months | 514.00 | 23.73 | 490.83 | 24.32 | 226.50 | 24.32 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.43 | 357.50 | 20.29 | 357.50 | 20.23 |
February | 454.00 | 20.72 | 337.17 | 20.60 | 337.17 | 20.55 |
March | 514.00 | 21.56 | 120.00 | 21.38 | 120.00 | 21.26 |
April | 429.67 | 22.33 | 28.67 | 22.25 | 23.67 | 22.16 |
May | 263.00 | 23.19 | 92.17 | 23.46 | 0.00 | 23.46 |
June | 21.67 | 23.51 | 369.67 | 24.21 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 482.33 | 24.32 | 0.00 | 24.32 |
August | 3.33 | 23.54 | 429.50 | 24.32 | 0.00 | 24.32 |
September | 111.33 | 23.24 | 226.00 | 23.92 | 0.00 | 23.92 |
October | 321.83 | 22.91 | 108.17 | 23.17 | 4.33 | 23.15 |
November | 489.00 | 21.57 | 133.33 | 21.30 | 133.33 | 21.13 |
December | 497.00 | 20.73 | 338.00 | 20.58 | 338.00 | 20.52 |
Annual Sum or Average | 3606.83 | 21.58 | 3022.50 | 22.03 | 1314.00 | 21.75 |
Minimum of Months | 0.00 | 0.00 | 28.67 | 20.29 | 0.00 | 20.23 |
Maximum of Months | 514.00 | 23.54 | 482.33 | 24.32 | 357.50 | 24.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.89 | 452.83 | 19.84 | 452.83 | 19.82 |
February | 454.00 | 20.03 | 434.33 | 20.01 | 434.33 | 20.00 |
March | 514.00 | 20.81 | 290.67 | 20.60 | 290.67 | 20.51 |
April | 425.67 | 21.63 | 123.33 | 21.45 | 104.67 | 21.26 |
May | 277.50 | 22.87 | 111.50 | 23.27 | 9.00 | 23.26 |
June | 39.17 | 24.02 | 390.33 | 24.28 | 10.83 | 24.31 |
July | 37.50 | 26.13 | 494.67 | 24.59 | 37.50 | 24.69 |
August | 41.00 | 25.09 | 440.50 | 24.44 | 23.33 | 24.53 |
September | 158.67 | 23.02 | 232.00 | 23.75 | 5.00 | 23.77 |
October | 376.00 | 22.20 | 117.67 | 22.30 | 43.17 | 22.14 |
November | 489.00 | 20.74 | 262.67 | 20.50 | 262.67 | 20.38 |
December | 497.00 | 20.05 | 472.83 | 20.03 | 472.83 | 20.02 |
Annual Sum or Average | 3811.50 | 21.09 | 3823.33 | 21.55 | 2146.83 | 21.26 |
Minimum of Months | 37.50 | 19.89 | 111.50 | 19.84 | 5.00 | 19.82 |
Maximum of Months | 514.00 | 26.13 | 494.67 | 24.59 | 472.83 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.94 | 432.33 | 19.86 | 432.33 | 19.82 |
February | 454.00 | 20.22 | 394.67 | 20.14 | 394.67 | 20.12 |
March | 505.17 | 21.10 | 212.17 | 20.79 | 212.17 | 20.62 |
April | 369.83 | 21.73 | 143.00 | 21.87 | 77.33 | 21.67 |
May | 244.50 | 22.90 | 190.50 | 23.61 | 17.50 | 23.71 |
June | 51.83 | 24.42 | 404.50 | 24.37 | 19.67 | 24.46 |
July | 63.67 | 26.54 | 485.83 | 24.77 | 63.67 | 24.96 |
August | 46.17 | 25.92 | 467.83 | 24.55 | 36.33 | 24.69 |
September | 149.50 | 23.30 | 288.17 | 24.04 | 20.67 | 24.15 |
October | 315.83 | 22.34 | 143.00 | 22.71 | 22.33 | 22.60 |
November | 488.67 | 20.94 | 220.17 | 20.64 | 220.17 | 20.48 |
December | 497.00 | 20.17 | 436.67 | 20.11 | 436.67 | 20.08 |
Annual Sum or Average | 3688.17 | 21.27 | 3818.83 | 21.81 | 1953.50 | 21.54 |
Minimum of Months | 46.17 | 19.94 | 143.00 | 19.86 | 17.50 | 19.82 |
Maximum of Months | 505.17 | 26.54 | 485.83 | 24.77 | 436.67 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.33 | 20.45 | 341.67 | 20.13 | 341.67 | 19.99 |
February | 434.67 | 20.87 | 296.83 | 20.54 | 296.83 | 20.41 |
March | 437.50 | 21.21 | 208.00 | 20.99 | 190.00 | 20.80 |
April | 360.67 | 21.70 | 147.00 | 21.86 | 80.83 | 21.64 |
May | 263.83 | 22.84 | 161.83 | 23.44 | 12.83 | 23.49 |
June | 59.67 | 24.17 | 386.83 | 24.32 | 18.83 | 24.39 |
July | 56.50 | 26.31 | 483.67 | 24.69 | 55.00 | 24.85 |
August | 53.83 | 25.56 | 458.67 | 24.55 | 36.17 | 24.69 |
September | 133.67 | 23.67 | 310.50 | 24.20 | 26.50 | 24.35 |
October | 220.67 | 22.53 | 233.67 | 23.32 | 30.83 | 23.26 |
November | 423.83 | 21.24 | 187.83 | 20.99 | 167.50 | 20.78 |
December | 473.33 | 20.76 | 327.83 | 20.49 | 321.67 | 20.35 |
Annual Sum or Average | 3412.50 | 21.56 | 3544.33 | 22.12 | 1578.67 | 21.84 |
Minimum of Months | 53.83 | 20.45 | 147.00 | 20.13 | 12.83 | 19.99 |
Maximum of Months | 494.33 | 26.31 | 483.67 | 24.69 | 341.67 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.02 | 426.00 | 19.91 | 426.00 | 19.87 |
February | 454.00 | 20.28 | 386.50 | 20.16 | 386.50 | 20.11 |
March | 481.33 | 20.98 | 242.33 | 20.77 | 236.00 | 20.63 |
April | 388.50 | 21.50 | 142.00 | 21.57 | 93.00 | 21.39 |
May | 281.83 | 22.74 | 161.67 | 23.34 | 16.00 | 23.43 |
June | 73.00 | 24.09 | 391.50 | 24.32 | 22.67 | 24.41 |
July | 50.00 | 26.23 | 471.67 | 24.66 | 47.00 | 24.81 |
August | 54.83 | 24.98 | 451.17 | 24.48 | 29.83 | 24.60 |
September | 174.67 | 23.06 | 245.17 | 23.81 | 17.67 | 23.92 |
October | 328.67 | 22.07 | 149.50 | 22.44 | 36.17 | 22.30 |
November | 479.00 | 20.74 | 247.17 | 20.50 | 247.17 | 20.38 |
December | 497.00 | 20.20 | 431.50 | 20.11 | 431.50 | 20.08 |
Annual Sum or Average | 3764.83 | 21.20 | 3746.17 | 21.71 | 1989.50 | 21.45 |
Minimum of Months | 50.00 | 20.02 | 142.00 | 19.91 | 16.00 | 19.87 |
Maximum of Months | 502.00 | 26.23 | 471.67 | 24.66 | 431.50 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.20 | 442.00 | 20.15 | 442.00 | 20.13 |
February | 454.00 | 20.35 | 433.67 | 20.33 | 433.67 | 20.33 |
March | 514.00 | 20.87 | 283.17 | 20.74 | 283.17 | 20.68 |
April | 477.50 | 21.78 | 69.17 | 21.61 | 69.17 | 21.48 |
May | 375.83 | 22.93 | 53.50 | 23.07 | 3.00 | 23.08 |
June | 43.67 | 23.67 | 343.00 | 24.16 | 3.50 | 24.17 |
July | 12.83 | 25.88 | 488.50 | 24.40 | 12.83 | 24.44 |
August | 16.50 | 25.80 | 442.50 | 24.39 | 13.17 | 24.44 |
September | 97.33 | 23.37 | 266.33 | 24.02 | 0.00 | 24.02 |
October | 303.67 | 22.96 | 110.50 | 23.25 | 0.00 | 23.25 |
November | 489.00 | 21.57 | 140.00 | 21.31 | 140.00 | 21.14 |
December | 497.00 | 20.54 | 432.67 | 20.50 | 432.67 | 20.49 |
Annual Sum or Average | 3783.33 | 21.39 | 3505.00 | 21.80 | 1833.17 | 21.53 |
Minimum of Months | 12.83 | 20.20 | 53.50 | 20.15 | 0.00 | 20.13 |
Maximum of Months | 514.00 | 25.88 | 488.50 | 24.40 | 442.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.29 | 410.17 | 20.20 | 410.17 | 20.17 |
February | 454.00 | 20.58 | 357.83 | 20.49 | 357.83 | 20.46 |
March | 514.00 | 21.34 | 157.67 | 21.11 | 157.67 | 20.96 |
April | 383.83 | 22.07 | 56.50 | 22.11 | 31.17 | 21.99 |
May | 247.50 | 22.89 | 136.33 | 23.56 | 5.17 | 23.58 |
June | 23.33 | 24.30 | 408.00 | 24.35 | 6.50 | 24.38 |
July | 31.50 | 26.58 | 495.67 | 24.64 | 31.50 | 24.75 |
August | 23.50 | 26.72 | 492.00 | 24.55 | 23.50 | 24.64 |
September | 65.50 | 24.01 | 350.67 | 24.39 | 12.33 | 24.47 |
October | 194.33 | 23.26 | 199.00 | 23.74 | 0.33 | 23.75 |
November | 460.00 | 21.82 | 108.83 | 21.58 | 105.33 | 21.40 |
December | 497.00 | 20.75 | 325.50 | 20.62 | 325.50 | 20.56 |
Annual Sum or Average | 3396.50 | 21.53 | 3498.17 | 22.17 | 1467.00 | 21.91 |
Minimum of Months | 23.33 | 20.29 | 56.50 | 20.20 | 0.33 | 20.17 |
Maximum of Months | 514.00 | 26.72 | 495.67 | 24.64 | 410.17 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 372.17 | 19.62 | 372.17 | 19.53 |
February | 447.67 | 20.18 | 317.33 | 19.93 | 317.33 | 19.82 |
March | 500.17 | 20.85 | 178.00 | 20.53 | 176.83 | 20.33 |
April | 417.83 | 21.45 | 93.50 | 21.42 | 64.67 | 21.22 |
May | 369.17 | 22.35 | 74.33 | 22.68 | 17.67 | 22.66 |
June | 147.17 | 23.49 | 361.67 | 24.01 | 95.00 | 23.98 |
July | 125.17 | 24.38 | 489.50 | 24.45 | 124.33 | 24.44 |
August | 82.17 | 24.83 | 481.50 | 24.55 | 75.50 | 24.61 |
September | 118.00 | 23.74 | 366.50 | 24.33 | 56.33 | 24.39 |
October | 157.67 | 22.84 | 284.83 | 23.90 | 18.33 | 23.92 |
November | 424.33 | 21.29 | 126.83 | 21.12 | 104.00 | 20.88 |
December | 484.33 | 20.54 | 301.17 | 20.35 | 291.83 | 20.21 |
Annual Sum or Average | 3775.67 | 21.34 | 3447.33 | 21.93 | 1714.00 | 21.68 |
Minimum of Months | 82.17 | 19.84 | 74.33 | 19.62 | 17.67 | 19.53 |
Maximum of Months | 502.00 | 24.83 | 489.50 | 24.55 | 372.17 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 406.00 | 20.23 | 406.00 | 20.19 |
February | 454.00 | 20.59 | 372.17 | 20.49 | 372.17 | 20.45 |
March | 504.50 | 21.35 | 177.17 | 21.15 | 174.67 | 21.03 |
April | 410.17 | 21.97 | 67.67 | 22.01 | 37.33 | 21.89 |
May | 274.83 | 22.86 | 127.17 | 23.39 | 1.50 | 23.39 |
June | 26.67 | 24.65 | 407.17 | 24.40 | 11.17 | 24.45 |
July | 30.83 | 26.64 | 488.83 | 24.63 | 30.67 | 24.74 |
August | 21.33 | 26.73 | 489.00 | 24.54 | 21.33 | 24.63 |
September | 71.33 | 23.75 | 327.67 | 24.29 | 9.17 | 24.35 |
October | 194.33 | 23.13 | 212.17 | 23.72 | 0.33 | 23.72 |
November | 472.17 | 21.62 | 128.17 | 21.37 | 128.17 | 21.20 |
December | 497.00 | 20.73 | 361.17 | 20.61 | 361.17 | 20.57 |
Annual Sum or Average | 3459.17 | 21.50 | 3564.33 | 22.12 | 1553.67 | 21.86 |
Minimum of Months | 21.33 | 20.33 | 67.67 | 20.23 | 0.33 | 20.19 |
Maximum of Months | 504.50 | 26.73 | 489.00 | 24.63 | 406.00 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 417.33 | 20.06 | 417.33 | 20.03 |
February | 454.00 | 20.35 | 400.33 | 20.30 | 400.33 | 20.29 |
March | 514.00 | 21.16 | 196.00 | 20.96 | 196.00 | 20.85 |
April | 422.83 | 22.10 | 51.50 | 22.02 | 38.67 | 21.90 |
May | 230.33 | 23.22 | 116.50 | 23.57 | 1.33 | 23.57 |
June | 16.17 | 24.58 | 414.00 | 24.31 | 7.33 | 24.33 |
July | 20.17 | 25.97 | 496.67 | 24.52 | 20.17 | 24.58 |
August | 17.83 | 26.15 | 460.67 | 24.45 | 16.17 | 24.51 |
September | 112.00 | 23.36 | 269.00 | 24.01 | 4.00 | 24.02 |
October | 310.83 | 22.75 | 106.50 | 23.04 | 3.67 | 23.02 |
November | 489.00 | 21.32 | 165.33 | 21.04 | 165.33 | 20.87 |
December | 497.00 | 20.41 | 435.00 | 20.36 | 435.00 | 20.34 |
Annual Sum or Average | 3586.17 | 21.35 | 3528.83 | 21.87 | 1705.33 | 21.58 |
Minimum of Months | 16.17 | 20.14 | 51.50 | 20.06 | 1.33 | 20.03 |
Maximum of Months | 514.00 | 26.15 | 496.67 | 24.52 | 435.00 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.06 | 353.17 | 19.95 | 353.17 | 19.91 |
February | 385.00 | 20.48 | 298.50 | 20.36 | 298.50 | 20.31 |
March | 423.67 | 21.30 | 136.17 | 21.05 | 135.67 | 20.89 |
April | 317.17 | 22.05 | 76.50 | 22.30 | 25.17 | 22.19 |
May | 196.17 | 23.20 | 149.50 | 23.85 | 11.33 | 23.95 |
June | 25.33 | 25.30 | 347.00 | 24.51 | 15.00 | 24.58 |
July | 48.33 | 26.61 | 419.50 | 24.83 | 48.33 | 24.99 |
August | 32.83 | 26.58 | 399.67 | 24.67 | 31.83 | 24.80 |
September | 109.50 | 23.68 | 253.67 | 24.28 | 18.33 | 24.39 |
October | 243.67 | 22.73 | 111.17 | 23.19 | 4.00 | 23.18 |
November | 407.83 | 21.32 | 139.83 | 21.04 | 138.33 | 20.86 |
December | 422.00 | 20.45 | 329.33 | 20.34 | 329.33 | 20.30 |
Annual Sum or Average | 3038.50 | 21.48 | 3014.00 | 22.07 | 1409.00 | 21.81 |
Minimum of Months | 25.33 | 20.06 | 76.50 | 19.95 | 4.00 | 19.91 |
Maximum of Months | 427.00 | 26.61 | 419.50 | 24.83 | 353.17 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.67 | 20.77 | 297.83 | 20.44 | 297.00 | 20.28 |
February | 425.50 | 21.27 | 240.67 | 20.97 | 235.00 | 20.80 |
March | 429.33 | 21.67 | 122.67 | 21.53 | 103.50 | 21.35 |
April | 347.00 | 22.22 | 89.50 | 22.49 | 23.17 | 22.38 |
May | 206.67 | 23.19 | 169.50 | 23.75 | 5.50 | 23.79 |
June | 27.33 | 24.79 | 423.50 | 24.37 | 13.17 | 24.42 |
July | 45.17 | 26.46 | 495.50 | 24.67 | 45.17 | 24.81 |
August | 33.50 | 26.56 | 477.50 | 24.59 | 32.00 | 24.71 |
September | 87.00 | 24.29 | 355.17 | 24.42 | 25.00 | 24.55 |
October | 174.00 | 23.22 | 262.00 | 23.98 | 9.50 | 24.04 |
November | 394.17 | 21.78 | 128.00 | 21.63 | 97.17 | 21.41 |
December | 457.50 | 21.18 | 265.67 | 20.94 | 256.00 | 20.78 |
Annual Sum or Average | 3114.83 | 21.89 | 3327.50 | 22.54 | 1142.17 | 22.30 |
Minimum of Months | 27.33 | 20.77 | 89.50 | 20.44 | 5.50 | 20.28 |
Maximum of Months | 487.67 | 26.56 | 495.50 | 24.67 | 297.00 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.28 | 380.83 | 20.13 | 380.83 | 20.07 |
February | 454.00 | 20.63 | 343.83 | 20.47 | 343.83 | 20.40 |
March | 477.50 | 21.34 | 166.00 | 21.16 | 159.17 | 21.03 |
April | 377.33 | 21.95 | 86.33 | 22.13 | 35.00 | 22.02 |
May | 226.83 | 23.07 | 175.50 | 23.66 | 8.33 | 23.73 |
June | 36.33 | 25.00 | 414.67 | 24.42 | 19.50 | 24.51 |
July | 41.00 | 26.53 | 489.83 | 24.65 | 41.00 | 24.78 |
August | 30.83 | 26.05 | 472.17 | 24.53 | 25.17 | 24.63 |
September | 119.50 | 23.47 | 291.33 | 24.11 | 16.33 | 24.21 |
October | 266.33 | 22.64 | 160.67 | 23.20 | 4.83 | 23.19 |
November | 473.33 | 21.26 | 160.83 | 20.99 | 160.83 | 20.84 |
December | 497.00 | 20.58 | 381.50 | 20.46 | 381.50 | 20.41 |
Annual Sum or Average | 3502.00 | 21.46 | 3523.50 | 22.07 | 1576.33 | 21.81 |
Minimum of Months | 30.83 | 20.28 | 86.33 | 20.13 | 4.83 | 20.07 |
Maximum of Months | 502.00 | 26.53 | 489.83 | 24.65 | 381.50 | 24.78 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.40559 | 24.33400 | -0.2393 | 8.38129 |
February | 454.00000 | 22.99876 | 20.23292 | -0.1131 | 5.83328 |
March | 514.00000 | 23.62234 | 27.64272 | 0.11255 | 5.63920 |
April | 485.00000 | 23.98226 | 32.93096 | 0.26523 | 6.88220 |
May | 508.00000 | 24.26563 | 40.02493 | -0.4570 | 9.77486 |
June | 496.00000 | 24.35506 | 49.09179 | -0.3177 | 7.53504 |
July | 497.00000 | 24.41038 | 52.35471 | -0.2645 | 6.90903 |
August | 514.00000 | 24.38601 | 49.19089 | -0.2865 | 7.27174 |
September | 485.00000 | 24.38123 | 44.97894 | -0.3448 | 7.96120 |
October | 502.00000 | 24.33572 | 38.80235 | 0.43855 | 9.45286 |
November | 489.00000 | 23.85895 | 30.23476 | 0.20032 | 6.71847 |
December | 497.00000 | 23.28257 | 23.18884 | -0.0164 | 5.40189 |
Annual Sum or Average | 5943.00000 | 23.86263 | 36.20581 | -0.0859 | 7.32680 |
Minimum of Months | 454.00000 | 22.40559 | 20.23292 | -0.4570 | 5.40189 |
Maximum of Months | 514.00000 | 24.41038 | 52.35471 | 0.43855 | 9.77486 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.96669 | 26.21098 | -0.5609 | 13.25115 |
February | 454.00000 | 21.33703 | 21.99774 | -0.4866 | 10.49544 |
March | 514.00000 | 22.24627 | 30.38150 | -0.1930 | 6.48559 |
April | 485.00000 | 23.06897 | 35.72686 | 0.05878 | 6.13691 |
May | 508.00000 | 23.85593 | 41.95275 | -0.6005 | 13.22094 |
June | 496.00000 | 24.20126 | 50.07590 | -0.3853 | 8.43145 |
July | 497.00000 | 24.28522 | 53.76229 | -0.3169 | 7.40463 |
August | 514.00000 | 24.28443 | 50.54474 | -0.3364 | 7.76927 |
September | 485.00000 | 24.13783 | 46.25259 | -0.4475 | 9.70684 |
October | 502.00000 | 23.84924 | 40.45552 | 0.30720 | 7.66420 |
November | 489.00000 | 22.45472 | 33.53481 | -0.1241 | 7.03392 |
December | 497.00000 | 21.48454 | 25.63097 | -0.4202 | 9.23617 |
Annual Sum or Average | 5943.00000 | 23.02663 | 38.16529 | -0.2915 | 8.89853 |
Minimum of Months | 454.00000 | 20.96669 | 21.99774 | -0.6005 | 6.13691 |
Maximum of Months | 514.00000 | 24.28522 | 53.76229 | 0.30720 | 13.25115 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.42978 | 26.96905 | -0.7138 | 17.81504 |
February | 454.00000 | 20.71691 | 22.15450 | -0.6648 | 15.39104 |
March | 514.00000 | 21.56226 | 31.33340 | -0.3651 | 8.90926 |
April | 485.00000 | 22.52840 | 36.62470 | -0.0720 | 6.88151 |
May | 508.00000 | 23.62463 | 42.57515 | -0.6735 | 15.73682 |
June | 496.00000 | 24.15536 | 50.05939 | -0.3918 | 8.61008 |
July | 497.00000 | 24.30346 | 53.65721 | -0.2970 | 7.17986 |
August | 514.00000 | 24.26335 | 50.39143 | -0.3335 | 7.79090 |
September | 485.00000 | 23.94474 | 46.47134 | -0.5144 | 11.42848 |
October | 502.00000 | 23.29166 | 41.74933 | 0.17156 | 7.10784 |
November | 489.00000 | 21.56539 | 35.05076 | -0.3495 | 9.56530 |
December | 497.00000 | 20.72628 | 26.42815 | -0.6287 | 14.36165 |
Annual Sum or Average | 5943.00000 | 22.60729 | 38.74521 | -0.4013 | 10.87187 |
Minimum of Months | 454.00000 | 20.42978 | 22.15450 | -0.7138 | 6.88151 |
Maximum of Months | 514.00000 | 24.30346 | 53.65721 | 0.17156 | 17.81504 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.89277 | 28.40392 | -0.8990 | 24.63866 |
February | 454.00000 | 20.02876 | 23.28872 | -0.8848 | 23.59113 |
March | 514.00000 | 20.80516 | 33.25196 | -0.5689 | 13.50825 |
April | 485.00000 | 21.92695 | 38.33114 | -0.2191 | 8.92589 |
May | 508.00000 | 23.45473 | 43.58304 | -0.7189 | 18.36741 |
June | 496.00000 | 24.20168 | 51.05800 | -0.3360 | 8.22492 |
July | 497.00000 | 24.47186 | 55.05019 | -0.1822 | 6.69414 |
August | 514.00000 | 24.31019 | 51.47659 | -0.2722 | 7.56813 |
September | 485.00000 | 23.77785 | 48.22894 | -0.5570 | 13.43677 |
October | 502.00000 | 22.62990 | 44.00549 | 0.01720 | 7.93645 |
November | 489.00000 | 20.74325 | 36.85604 | -0.5688 | 14.31541 |
December | 497.00000 | 20.05484 | 28.21808 | -0.8386 | 21.66885 |
Annual Sum or Average | 5943.00000 | 22.20895 | 40.27033 | -0.4998 | 14.00792 |
Minimum of Months | 454.00000 | 19.89277 | 23.28872 | -0.8990 | 6.69414 |
Maximum of Months | 514.00000 | 24.47186 | 55.05019 | 0.01720 | 24.63866 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.94432 | 28.02843 | -0.8671 | 23.57286 |
February | 454.00000 | 20.21809 | 22.82967 | -0.8099 | 20.87558 |
March | 514.00000 | 21.14736 | 32.39686 | -0.4596 | 12.02167 |
April | 485.00000 | 22.34255 | 36.89572 | -0.0909 | 8.89195 |
May | 508.00000 | 23.58725 | 42.82851 | -0.6045 | 16.75249 |
June | 496.00000 | 24.22722 | 50.71950 | -0.2665 | 7.96556 |
July | 497.00000 | 24.51902 | 54.47549 | -0.1018 | 6.90486 |
August | 514.00000 | 24.36029 | 50.88298 | -0.1660 | 6.99787 |
September | 485.00000 | 23.91235 | 47.44099 | -0.4481 | 12.29948 |
October | 502.00000 | 22.97391 | 42.70508 | 0.13197 | 8.27466 |
November | 489.00000 | 20.94553 | 36.17825 | -0.5001 | 13.16164 |
December | 497.00000 | 20.16869 | 27.79311 | -0.7913 | 20.01605 |
Annual Sum or Average | 5943.00000 | 22.37922 | 39.55485 | -0.4118 | 13.09032 |
Minimum of Months | 454.00000 | 19.94432 | 22.82967 | -0.8671 | 6.90486 |
Maximum of Months | 514.00000 | 24.51902 | 54.47549 | 0.13197 | 23.57286 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.50390 | 27.27854 | -0.7057 | 20.22592 |
February | 454.00000 | 21.01137 | 21.81326 | -0.5967 | 16.96116 |
March | 514.00000 | 21.63752 | 31.12569 | -0.3315 | 11.27969 |
April | 485.00000 | 22.37513 | 36.64253 | -0.0863 | 9.21823 |
May | 508.00000 | 23.49815 | 43.05765 | -0.6712 | 18.04706 |
June | 496.00000 | 24.18838 | 50.87477 | -0.3162 | 8.45818 |
July | 497.00000 | 24.48335 | 54.71799 | -0.1477 | 6.89904 |
August | 514.00000 | 24.36343 | 50.81467 | -0.1799 | 7.21651 |
September | 485.00000 | 24.03025 | 46.81459 | -0.3864 | 11.38534 |
October | 502.00000 | 23.49072 | 40.83730 | 0.28767 | 10.19641 |
November | 489.00000 | 21.61709 | 34.63949 | -0.3223 | 11.51183 |
December | 497.00000 | 20.94886 | 26.64449 | -0.5821 | 16.46698 |
Annual Sum or Average | 5943.00000 | 22.69235 | 38.89861 | -0.3350 | 12.29640 |
Minimum of Months | 454.00000 | 20.50390 | 21.81326 | -0.7057 | 6.89904 |
Maximum of Months | 514.00000 | 24.48335 | 54.71799 | 0.28767 | 20.22592 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.01738 | 27.68861 | -0.8588 | 23.35220 |
February | 454.00000 | 20.28463 | 22.55822 | -0.8082 | 21.49087 |
March | 514.00000 | 21.17964 | 31.96490 | -0.4565 | 12.39443 |
April | 485.00000 | 22.04204 | 37.43230 | -0.1579 | 9.51997 |
May | 508.00000 | 23.35997 | 43.46608 | -0.6827 | 19.11660 |
June | 496.00000 | 24.16425 | 50.83200 | -0.2787 | 8.56722 |
July | 497.00000 | 24.44242 | 54.70264 | -0.1297 | 7.12603 |
August | 514.00000 | 24.31657 | 51.08931 | -0.1822 | 7.38065 |
September | 485.00000 | 23.72464 | 47.92450 | -0.5087 | 13.83682 |
October | 502.00000 | 22.76174 | 43.06443 | 0.08911 | 8.67069 |
November | 489.00000 | 20.80599 | 36.20466 | -0.5419 | 13.93642 |
December | 497.00000 | 20.20004 | 27.51415 | -0.7942 | 20.30088 |
Annual Sum or Average | 5943.00000 | 22.29177 | 39.66122 | -0.4399 | 13.75256 |
Minimum of Months | 454.00000 | 20.01738 | 22.55822 | -0.8588 | 7.12603 |
Maximum of Months | 514.00000 | 24.44242 | 54.70264 | 0.08911 | 23.35220 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.20027 | 28.12320 | -0.8009 | 20.27312 |
February | 454.00000 | 20.34728 | 23.23825 | -0.7906 | 19.21169 |
March | 514.00000 | 20.86862 | 33.33393 | -0.5465 | 12.03062 |
April | 485.00000 | 21.81718 | 38.88446 | -0.2500 | 7.82914 |
May | 508.00000 | 23.21952 | 44.53941 | -0.8335 | 21.19089 |
June | 496.00000 | 24.10566 | 51.46557 | -0.4138 | 9.03584 |
July | 497.00000 | 24.35181 | 54.30664 | -0.2700 | 6.95591 |
August | 514.00000 | 24.28358 | 50.86648 | -0.3141 | 7.60965 |
September | 485.00000 | 24.01312 | 47.55074 | -0.4843 | 10.68207 |
October | 502.00000 | 23.34719 | 42.54664 | 0.19153 | 7.06094 |
November | 489.00000 | 21.56512 | 35.28620 | -0.3364 | 9.26725 |
December | 497.00000 | 20.53839 | 27.57087 | -0.6745 | 15.12617 |
Annual Sum or Average | 5943.00000 | 22.40318 | 39.93396 | -0.4587 | 12.16054 |
Minimum of Months | 454.00000 | 20.20027 | 23.23825 | -0.8335 | 6.95591 |
Maximum of Months | 514.00000 | 24.35181 | 54.30664 | 0.19153 | 21.19089 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29240 | 28.30951 | -0.7588 | 18.92968 |
February | 454.00000 | 20.57839 | 23.28050 | -0.7033 | 16.39051 |
March | 514.00000 | 21.34279 | 32.85800 | -0.4048 | 9.83116 |
April | 485.00000 | 22.52969 | 37.20003 | -0.0574 | 7.52552 |
May | 508.00000 | 23.64830 | 43.11069 | -0.6345 | 16.34435 |
June | 496.00000 | 24.24761 | 50.80634 | -0.3085 | 7.87710 |
July | 497.00000 | 24.51229 | 53.53134 | -0.1545 | 6.53709 |
August | 514.00000 | 24.42333 | 50.03874 | -0.1764 | 6.56588 |
September | 485.00000 | 24.25697 | 46.58301 | -0.3417 | 8.96415 |
October | 502.00000 | 23.79036 | 40.99747 | 0.32949 | 8.42633 |
November | 489.00000 | 21.95897 | 34.75428 | -0.2268 | 8.52461 |
December | 497.00000 | 20.75038 | 27.59080 | -0.6043 | 13.41226 |
Annual Sum or Average | 5943.00000 | 22.70925 | 39.20880 | -0.3349 | 10.75095 |
Minimum of Months | 454.00000 | 20.29240 | 23.28050 | -0.7588 | 6.53709 |
Maximum of Months | 514.00000 | 24.51229 | 53.53134 | 0.32949 | 18.92968 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83773 | 25.63076 | -0.7953 | 21.21878 |
February | 454.00000 | 20.25288 | 20.41954 | -0.7019 | 18.48717 |
March | 514.00000 | 20.93257 | 30.41886 | -0.4479 | 11.66682 |
April | 485.00000 | 21.85672 | 36.54480 | -0.1903 | 8.69915 |
May | 508.00000 | 22.91012 | 44.50090 | -0.8768 | 24.20344 |
June | 496.00000 | 24.02672 | 54.41788 | -0.3888 | 9.34987 |
July | 497.00000 | 24.45957 | 58.37849 | -0.1739 | 6.43096 |
August | 514.00000 | 24.44058 | 52.99287 | -0.1634 | 6.70705 |
September | 485.00000 | 24.21062 | 48.12631 | -0.3050 | 9.18586 |
October | 502.00000 | 23.89757 | 40.42029 | 0.42340 | 10.77668 |
November | 489.00000 | 21.68967 | 32.40129 | -0.2319 | 9.59935 |
December | 497.00000 | 20.68548 | 24.60724 | -0.5613 | 14.47039 |
Annual Sum or Average | 5943.00000 | 22.44882 | 39.21472 | -0.3663 | 12.55060 |
Minimum of Months | 454.00000 | 19.83773 | 20.41954 | -0.8768 | 6.43096 |
Maximum of Months | 514.00000 | 24.45957 | 58.37849 | 0.42340 | 24.20344 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.32627 | 28.14456 | -0.7573 | 18.97413 |
February | 454.00000 | 20.59469 | 23.15916 | -0.7098 | 16.93342 |
March | 514.00000 | 21.39622 | 32.51288 | -0.3945 | 9.88596 |
April | 485.00000 | 22.32336 | 37.65743 | -0.1054 | 7.71510 |
May | 508.00000 | 23.51931 | 43.59313 | -0.6859 | 17.51528 |
June | 496.00000 | 24.27949 | 50.62386 | -0.2909 | 7.77342 |
July | 497.00000 | 24.48891 | 53.63714 | -0.1637 | 6.63704 |
August | 514.00000 | 24.42422 | 50.15753 | -0.1781 | 6.61131 |
September | 485.00000 | 24.17999 | 46.85171 | -0.3710 | 9.29086 |
October | 502.00000 | 23.76843 | 41.11713 | 0.32621 | 8.56583 |
November | 489.00000 | 21.70615 | 35.08671 | -0.2913 | 8.98986 |
December | 497.00000 | 20.72754 | 27.50209 | -0.6175 | 13.81174 |
Annual Sum or Average | 5943.00000 | 22.66005 | 39.29017 | -0.3513 | 11.03025 |
Minimum of Months | 454.00000 | 20.32627 | 23.15916 | -0.7573 | 6.61131 |
Maximum of Months | 514.00000 | 24.48891 | 53.63714 | 0.32621 | 18.97413 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.14124 | 28.12722 | -0.8011 | 20.62688 |
February | 454.00000 | 20.35184 | 22.91886 | -0.7680 | 18.76137 |
March | 514.00000 | 21.16039 | 32.78733 | -0.4545 | 10.53653 |
April | 485.00000 | 22.35855 | 37.66428 | -0.1054 | 7.33833 |
May | 508.00000 | 23.71150 | 42.87730 | -0.6368 | 14.86393 |
June | 496.00000 | 24.25312 | 50.88886 | -0.3282 | 7.76488 |
July | 497.00000 | 24.46529 | 54.82535 | -0.2013 | 6.60210 |
August | 514.00000 | 24.34296 | 51.38070 | -0.2736 | 7.29904 |
September | 485.00000 | 23.99152 | 47.78957 | -0.4850 | 10.98107 |
October | 502.00000 | 23.20192 | 42.64287 | 0.15655 | 7.21564 |
November | 489.00000 | 21.32101 | 35.84295 | -0.4017 | 10.57411 |
December | 497.00000 | 20.40719 | 27.63723 | -0.7099 | 16.56233 |
Annual Sum or Average | 5943.00000 | 22.49185 | 39.73967 | -0.4154 | 11.54850 |
Minimum of Months | 454.00000 | 20.14124 | 22.91886 | -0.8011 | 6.60210 |
Maximum of Months | 514.00000 | 24.46529 | 54.82535 | 0.15655 | 20.62688 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.06116 | 27.02548 | -0.8076 | 21.01224 |
February | 385.00000 | 20.47937 | 21.71708 | -0.7185 | 17.30835 |
March | 433.00000 | 21.35765 | 31.47421 | -0.3896 | 10.04206 |
April | 410.00000 | 22.59898 | 36.21192 | -0.0244 | 7.97683 |
May | 430.00000 | 23.79114 | 41.95624 | -0.5545 | 14.62827 |
June | 418.00000 | 24.32875 | 50.06717 | -0.2669 | 7.77708 |
July | 422.00000 | 24.61528 | 53.91117 | -0.1137 | 6.92073 |
August | 433.00000 | 24.46176 | 50.63686 | -0.1749 | 6.99573 |
September | 410.00000 | 24.10730 | 46.95653 | -0.4008 | 10.79935 |
October | 427.00000 | 23.33009 | 41.25205 | 0.21133 | 7.83948 |
November | 417.00000 | 21.38666 | 34.76570 | -0.3728 | 10.41422 |
December | 422.00000 | 20.45459 | 26.57444 | -0.6870 | 16.03801 |
Annual Sum or Average | 5034.00000 | 22.59423 | 38.65718 | -0.3562 | 11.44841 |
Minimum of Months | 385.00000 | 20.06116 | 21.71708 | -0.8076 | 6.92073 |
Maximum of Months | 433.00000 | 24.61528 | 53.91117 | 0.21133 | 21.01224 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.86665 | 26.99717 | -0.5876 | 16.39012 |
February | 454.00000 | 21.47039 | 21.40341 | -0.4569 | 13.04891 |
March | 514.00000 | 22.06921 | 30.57807 | -0.2066 | 8.81991 |
April | 485.00000 | 22.81379 | 35.96121 | 0.02672 | 7.90027 |
May | 508.00000 | 23.79528 | 42.28041 | -0.5800 | 14.18360 |
June | 496.00000 | 24.27716 | 50.64405 | -0.2993 | 7.74113 |
July | 497.00000 | 24.50889 | 54.45279 | -0.1589 | 6.70509 |
August | 514.00000 | 24.41288 | 50.67797 | -0.1796 | 6.83480 |
September | 485.00000 | 24.23842 | 46.42301 | -0.3201 | 9.23810 |
October | 502.00000 | 23.92184 | 39.74150 | 0.39601 | 10.32368 |
November | 489.00000 | 22.23726 | 33.59061 | -0.1509 | 9.01446 |
December | 497.00000 | 21.46100 | 25.98344 | -0.4262 | 12.37788 |
Annual Sum or Average | 5943.00000 | 23.01767 | 38.35477 | -0.2443 | 10.20198 |
Minimum of Months | 454.00000 | 20.86665 | 21.40341 | -0.5876 | 6.70509 |
Maximum of Months | 514.00000 | 24.50889 | 54.45279 | 0.39601 | 16.39012 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.27744 | 27.53052 | -0.7587 | 19.49089 |
February | 454.00000 | 20.62531 | 22.22291 | -0.6889 | 16.99532 |
March | 514.00000 | 21.53409 | 31.56303 | -0.3440 | 9.77725 |
April | 485.00000 | 22.46057 | 36.80266 | -0.0480 | 8.03427 |
May | 508.00000 | 23.67398 | 42.68657 | -0.5872 | 15.00566 |
June | 496.00000 | 24.26567 | 50.56446 | -0.2590 | 7.72646 |
July | 497.00000 | 24.47812 | 54.42085 | -0.1385 | 6.80655 |
August | 514.00000 | 24.37520 | 50.98078 | -0.1790 | 6.89893 |
September | 485.00000 | 23.99070 | 47.46526 | -0.4249 | 10.92892 |
October | 502.00000 | 23.31527 | 41.80581 | 0.22358 | 8.19657 |
November | 489.00000 | 21.34319 | 35.32476 | -0.3829 | 10.42146 |
December | 497.00000 | 20.57835 | 26.98136 | -0.6613 | 15.42359 |
Annual Sum or Average | 5943.00000 | 22.59225 | 39.15345 | -0.3519 | 11.27097 |
Minimum of Months | 454.00000 | 20.27744 | 22.22291 | -0.7587 | 6.80655 |
Maximum of Months | 514.00000 | 24.47812 | 54.42085 | 0.22358 | 19.49089 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.436525E+09 | 0.109833E+09 | 13.17 | 0.287914E+09 | 0.148611E+09 | 0.00 | 0.67 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 21949.60 | 27-MAR-16:00 | 17196.58 | 27-MAR-16:00 | 7846.55 | 27-MAR-13:00 | 5243.50 | 27-MAR-16:00 | 0.00 |
April | 0.386519E+10 | 0.959600E+09 | 88.22 | 0.339501E+10 | 0.470181E+09 | 0.00 | 1.00 | 07-APR-13:50 | 0.00 | 01-APR-00:10 | 38379.90 | 07-APR-15:50 | 38379.90 | 07-APR-15:50 | 5696.27 | 10-APR-08:70 | 8750.61 | 07-APR-13:50 | 0.00 |
May | 0.157491E+11 | 0.385821E+10 | 285.83 | 0.130900E+11 | 0.265902E+10 | 0.00 | 1.00 | 30-MAY-07:10 | 0.00 | 01-MAY-00:10 | 74742.72 | 30-MAY-14:00 | 74742.72 | 30-MAY-14:00 | 19383.72 | 31-MAY-06:03 | 18713.06 | 30-MAY-13:40 | 0.00 |
June | 0.558415E+11 | 0.130246E+11 | 432.36 | 0.429341E+11 | 0.129074E+11 | 0.00 | 1.00 | 01-JUN-06:02 | 0.00 | 01-JUN-00:10 | 90798.67 | 19-JUN-12:03 | 71979.11 | 19-JUN-06:03 | 35405.57 | 15-JUN-12:03 | 26443.53 | 19-JUN-12:03 | 0.00 |
July | 0.796705E+11 | 0.187326E+11 | 445.82 | 0.585887E+11 | 0.210818E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 96578.47 | 10-JUL-06:03 | 85118.52 | 10-JUL-06:03 | 40715.83 | 20-JUL-11:10 | 23467.79 | 07-JUL-12:03 | 0.00 |
August | 0.820188E+11 | 0.195328E+11 | 461.63 | 0.648440E+11 | 0.171748E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 114769.66 | 17-AUG-06:03 | 81739.55 | 22-AUG-15:50 | 42941.69 | 17-AUG-06:03 | 25927.47 | 03-AUG-06:03 | 0.00 |
September | 0.426499E+11 | 0.989047E+10 | 393.76 | 0.340507E+11 | 0.859913E+10 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 81978.76 | 07-SEP-11:10 | 77322.50 | 05-SEP-04:02 | 40533.52 | 06-SEP-04:03 | 19189.47 | 14-SEP-12:05 | 0.00 |
October | 0.182158E+11 | 0.422014E+10 | 229.00 | 0.128625E+11 | 0.535327E+10 | 0.00 | 1.00 | 02-OCT-15:00 | 0.00 | 01-OCT-00:10 | 64491.88 | 05-OCT-12:30 | 48842.87 | 04-OCT-15:30 | 23486.33 | 24-OCT-08:50 | 14124.95 | 05-OCT-12:30 | 0.00 |
November | 0.397543E+09 | 0.107100E+09 | 25.00 | 0.316894E+09 | 80648601.83 | 0.00 | 0.33 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 9857.36 | 03-NOV-14:00 | 9857.36 | 03-NOV-14:00 | 4033.24 | 10-NOV-10:00 | 2571.79 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.298845E+12 | 0.704353E+11 | 2374.78 | 0.230370E+12 | 0.684748E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.820188E+11 | 0.195328E+11 | 461.63 | 0.648440E+11 | 0.210818E+11 | 0.00 | 1.00 | 0.00 | 114769.66 | 85118.52 | 42941.69 | 26443.53 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.416154E+09 | 0.104184E+09 | 13.17 | 0.279718E+09 | 0.136436E+09 | 0.00 | 0.68 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 20527.93 | 27-MAR-16:00 | 16217.10 | 27-MAR-16:00 | 7342.15 | 27-MAR-13:00 | 4883.45 | 27-MAR-16:00 | 0.00 |
April | 0.387728E+10 | 0.959115E+09 | 93.72 | 0.342537E+10 | 0.451915E+09 | 0.00 | 1.00 | 07-APR-13:00 | 0.00 | 01-APR-00:10 | 39458.79 | 07-APR-14:30 | 39458.79 | 07-APR-14:30 | 6034.40 | 09-APR-12:13 | 9013.15 | 07-APR-14:30 | 0.00 |
May | 0.149752E+11 | 0.365969E+10 | 292.82 | 0.126970E+11 | 0.227816E+10 | 0.00 | 1.00 | 28-MAY-15:02 | 0.00 | 01-MAY-00:10 | 74561.11 | 30-MAY-14:00 | 74561.11 | 30-MAY-14:00 | 14682.60 | 18-MAY-15:00 | 18649.19 | 30-MAY-14:00 | 0.00 |
June | 0.508910E+11 | 0.118638E+11 | 430.76 | 0.390071E+11 | 0.118839E+11 | 0.00 | 1.00 | 01-JUN-09:40 | 0.00 | 01-JUN-00:10 | 92690.00 | 19-JUN-06:03 | 66867.72 | 01-JUN-15:00 | 27995.35 | 19-JUN-06:03 | 23190.88 | 19-JUN-12:04 | 0.00 |
July | 0.722691E+11 | 0.169533E+11 | 447.39 | 0.525940E+11 | 0.196751E+11 | 0.00 | 1.00 | 01-JUL-08:50 | 0.00 | 01-JUL-00:10 | 107336.91 | 22-JUL-05:03 | 74355.52 | 10-JUL-06:03 | 45983.04 | 22-JUL-05:03 | 23455.51 | 22-JUL-05:03 | 0.00 |
August | 0.723638E+11 | 0.172094E+11 | 455.99 | 0.568283E+11 | 0.155355E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 99435.75 | 05-AUG-05:03 | 79999.10 | 22-AUG-14:50 | 33927.62 | 05-AUG-05:03 | 22637.26 | 05-AUG-05:03 | 0.00 |
September | 0.358543E+11 | 0.835215E+10 | 386.14 | 0.282340E+11 | 0.762032E+10 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 79293.46 | 01-SEP-05:03 | 57645.54 | 01-SEP-14:30 | 25331.81 | 07-SEP-13:00 | 17439.44 | 01-SEP-05:03 | 0.00 |
October | 0.152092E+11 | 0.354913E+10 | 227.44 | 0.104587E+11 | 0.475056E+10 | 0.00 | 1.00 | 03-OCT-10:20 | 0.00 | 01-OCT-00:10 | 54424.39 | 04-OCT-14:30 | 43014.20 | 04-OCT-15:00 | 20212.02 | 24-OCT-09:10 | 12008.95 | 04-OCT-14:20 | 0.00 |
November | 0.361919E+09 | 97439673.12 | 25.00 | 0.295846E+09 | 66072580.02 | 0.00 | 0.30 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 | 8232.99 | 04-NOV-12:30 | 7688.46 | 03-NOV-14:00 | 2783.11 | 10-NOV-10:00 | 2161.40 | 04-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.266218E+12 | 0.627482E+11 | 2372.43 | 0.203820E+12 | 0.623981E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.723638E+11 | 0.172094E+11 | 455.99 | 0.568283E+11 | 0.196751E+11 | 0.00 | 1.00 | 0.00 | 107336.91 | 79999.10 | 45983.04 | 23455.51 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 167525.54 | 47150.77 | 0.17 | 160876.38 | 6649.16 | 0.00 | 0.01 | 15-JAN-10:20 | 0.00 | 01-JAN-00:02 | 279.21 | 15-JAN-10:20 | 268.13 | 15-JAN-10:20 | 11.08 | 15-JAN-10:20 | 78.58 | 15-JAN-10:20 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.433811E+09 | 0.109370E+09 | 13.17 | 0.285913E+09 | 0.147898E+09 | 0.00 | 0.65 | 27-MAR-16:00 | 0.00 | 01-MAR-00:10 | 21661.08 | 27-MAR-16:00 | 16549.92 | 27-MAR-16:00 | 7812.17 | 27-MAR-13:00 | 5198.59 | 27-MAR-16:00 | 0.00 |
April | 0.412568E+10 | 0.102496E+10 | 92.83 | 0.360746E+10 | 0.518218E+09 | 0.00 | 1.00 | 07-APR-12:10 | 0.00 | 01-APR-00:10 | 44796.47 | 07-APR-14:30 | 44796.47 | 07-APR-14:30 | 7181.04 | 09-APR-12:02 | 10232.07 | 07-APR-14:30 | 0.00 |
May | 0.157941E+11 | 0.387819E+10 | 290.24 | 0.134559E+11 | 0.233819E+10 | 0.00 | 1.00 | 28-MAY-13:32 | 0.00 | 01-MAY-00:10 | 84470.95 | 30-MAY-14:00 | 84470.95 | 30-MAY-14:00 | 13677.38 | 18-MAY-15:00 | 21127.01 | 30-MAY-14:00 | 0.00 |
June | 0.539758E+11 | 0.126672E+11 | 430.48 | 0.418584E+11 | 0.121174E+11 | 0.00 | 1.00 | 01-JUN-09:50 | 0.00 | 01-JUN-00:10 | 94112.66 | 19-JUN-13:50 | 78083.92 | 19-JUN-13:40 | 24499.77 | 19-JUN-08:30 | 26516.65 | 19-JUN-12:04 | 0.00 |
July | 0.772098E+11 | 0.181729E+11 | 447.07 | 0.575168E+11 | 0.196930E+11 | 0.00 | 1.00 | 01-JUL-09:40 | 0.00 | 01-JUL-00:10 | 115567.43 | 22-JUL-05:03 | 83661.29 | 10-JUL-04:02 | 53461.89 | 22-JUL-05:03 | 25230.76 | 22-JUL-05:03 | 0.00 |
August | 0.767431E+11 | 0.183233E+11 | 453.82 | 0.613340E+11 | 0.154091E+11 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 105652.78 | 05-AUG-05:03 | 88609.51 | 22-AUG-14:50 | 37975.74 | 04-AUG-05:03 | 24442.30 | 04-AUG-14:00 | 0.00 |
September | 0.365133E+11 | 0.858738E+10 | 383.42 | 0.286243E+11 | 0.788897E+10 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 83012.98 | 01-SEP-14:10 | 83012.98 | 01-SEP-14:10 | 24952.37 | 07-SEP-12:40 | 21638.36 | 01-SEP-14:10 | 0.00 |
October | 0.147499E+11 | 0.348794E+10 | 222.72 | 0.100349E+11 | 0.471501E+10 | 0.00 | 1.00 | 03-OCT-12:00 | 0.00 | 01-OCT-00:10 | 57511.05 | 04-OCT-14:00 | 48314.15 | 04-OCT-15:00 | 19896.78 | 24-OCT-10:00 | 12764.48 | 04-OCT-13:50 | 0.00 |
November | 0.323565E+09 | 87658511.53 | 23.83 | 0.251285E+09 | 72279665.17 | 0.00 | 0.28 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 | 8313.02 | 04-NOV-12:30 | 6775.42 | 03-NOV-14:00 | 2609.09 | 10-NOV-08:00 | 2197.13 | 04-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.279869E+12 | 0.663390E+11 | 2357.75 | 0.216969E+12 | 0.629001E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.772098E+11 | 0.183233E+11 | 453.82 | 0.613340E+11 | 0.196930E+11 | 0.00 | 1.00 | 0.00 | 115567.43 | 88609.51 | 53461.89 | 26516.65 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 299.04 | 0.00 | 299.04 | 26.01 | 1525.58 | 0.00 | 0.00 | 0.00 |
February | 409.23 | 0.00 | 409.23 | 48.08 | 1580.94 | 0.00 | 0.00 | 0.00 |
March | 567.49 | 0.00 | 567.49 | 230.13 | 1043.50 | 0.00 | 0.00 | 0.00 |
April | 681.64 | 1.94 | 679.70 | 459.95 | 746.19 | 0.00 | 0.00 | 0.00 |
May | 904.31 | 30.13 | 874.18 | 872.94 | 473.71 | 0.00 | 0.00 | 0.00 |
June | 959.01 | 51.53 | 907.48 | 1197.25 | 264.83 | 0.00 | 0.00 | 0.00 |
July | 926.79 | 33.52 | 893.28 | 1323.13 | 148.98 | 0.00 | 0.00 | 0.00 |
August | 821.09 | 9.77 | 811.32 | 1160.08 | 201.17 | 0.00 | 0.00 | 0.00 |
September | 618.97 | 0.12 | 618.85 | 675.50 | 394.32 | 0.00 | 0.00 | 0.00 |
October | 535.67 | 0.00 | 535.67 | 417.92 | 714.64 | 0.00 | 0.00 | 0.00 |
November | 375.72 | 0.00 | 375.72 | 126.45 | 1059.32 | 0.00 | 0.00 | 0.00 |
December | 260.84 | 0.00 | 260.84 | 17.91 | 1403.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 614.50 | 10.64 | 603.86 | 549.62 | 791.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 260.84 | 0.00 | 260.84 | 17.91 | 148.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 959.01 | 51.53 | 907.48 | 1323.13 | 1580.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.44 | 166.96 | 249.48 | 270.06 | 946.64 | 0.00 | 0.00 | 0.00 |
February | 645.81 | 301.27 | 344.54 | 472.60 | 951.02 | 0.00 | 0.00 | 0.00 |
March | 823.85 | 350.39 | 473.46 | 744.11 | 672.81 | 0.00 | 0.00 | 0.00 |
April | 988.68 | 433.07 | 555.61 | 1026.19 | 485.26 | 0.00 | 0.00 | 0.00 |
May | 1199.06 | 479.21 | 719.84 | 1407.69 | 321.48 | 0.00 | 0.00 | 0.00 |
June | 1111.27 | 402.27 | 709.00 | 1459.80 | 179.73 | 0.00 | 0.00 | 0.00 |
July | 1116.14 | 402.78 | 713.35 | 1585.23 | 100.13 | 0.00 | 0.00 | 0.00 |
August | 1256.80 | 566.69 | 690.11 | 1776.96 | 134.85 | 0.00 | 0.00 | 0.00 |
September | 937.33 | 420.54 | 516.79 | 1180.98 | 255.41 | 0.00 | 0.00 | 0.00 |
October | 849.76 | 385.14 | 464.62 | 960.89 | 463.83 | 0.00 | 0.00 | 0.00 |
November | 525.51 | 201.80 | 323.71 | 444.85 | 667.10 | 0.00 | 0.00 | 0.00 |
December | 409.40 | 192.23 | 217.17 | 290.80 | 864.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 858.03 | 358.94 | 499.09 | 971.77 | 501.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 409.40 | 166.96 | 217.17 | 270.06 | 100.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1256.80 | 566.69 | 719.84 | 1776.96 | 951.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1546.98 | 1012.97 | 534.01 | 1556.68 | 1368.01 | 0.00 | 0.00 | 0.00 |
February | 2040.41 | 1350.59 | 689.83 | 2085.79 | 1387.49 | 0.00 | 0.00 | 0.00 |
March | 1840.84 | 1021.70 | 819.14 | 1989.94 | 1023.50 | 0.00 | 0.00 | 0.00 |
April | 1428.43 | 564.84 | 863.59 | 1597.44 | 773.68 | 0.00 | 0.00 | 0.00 |
May | 1251.81 | 261.11 | 990.70 | 1479.74 | 508.34 | 0.00 | 0.00 | 0.00 |
June | 1174.78 | 179.58 | 995.21 | 1592.11 | 282.58 | 0.00 | 0.00 | 0.00 |
July | 1231.41 | 213.89 | 1017.51 | 1846.06 | 152.62 | 0.00 | 0.00 | 0.00 |
August | 1644.41 | 609.94 | 1034.47 | 2486.14 | 213.49 | 0.00 | 0.00 | 0.00 |
September | 1784.21 | 922.87 | 861.35 | 2399.15 | 407.34 | 0.00 | 0.00 | 0.00 |
October | 2444.22 | 1532.70 | 911.52 | 3070.46 | 724.74 | 0.00 | 0.00 | 0.00 |
November | 1694.86 | 1017.84 | 677.02 | 1846.96 | 1004.57 | 0.00 | 0.00 | 0.00 |
December | 1676.69 | 1190.34 | 486.35 | 1757.64 | 1250.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1644.73 | 820.53 | 824.21 | 1976.05 | 754.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1174.78 | 179.58 | 486.35 | 1479.74 | 152.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2444.22 | 1532.70 | 1034.47 | 3070.46 | 1387.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 411.12 | 168.40 | 242.72 | 266.66 | 967.99 | 0.00 | 0.00 | 0.00 |
February | 606.25 | 266.27 | 339.99 | 434.10 | 993.85 | 0.00 | 0.00 | 0.00 |
March | 895.21 | 413.29 | 481.92 | 833.78 | 672.81 | 0.00 | 0.00 | 0.00 |
April | 978.42 | 418.64 | 559.78 | 1027.96 | 500.43 | 0.00 | 0.00 | 0.00 |
May | 1139.76 | 432.84 | 706.93 | 1346.16 | 333.70 | 0.00 | 0.00 | 0.00 |
June | 1247.44 | 503.13 | 744.31 | 1651.45 | 190.90 | 0.00 | 0.00 | 0.00 |
July | 1168.29 | 439.94 | 728.35 | 1658.32 | 106.98 | 0.00 | 0.00 | 0.00 |
August | 1292.45 | 598.32 | 694.13 | 1836.88 | 145.77 | 0.00 | 0.00 | 0.00 |
September | 917.53 | 400.96 | 516.57 | 1170.81 | 267.99 | 0.00 | 0.00 | 0.00 |
October | 909.67 | 442.35 | 467.32 | 1049.73 | 478.99 | 0.00 | 0.00 | 0.00 |
November | 427.18 | 123.46 | 303.72 | 311.27 | 685.00 | 0.00 | 0.00 | 0.00 |
December | 379.96 | 164.41 | 215.55 | 254.18 | 889.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 866.25 | 365.17 | 501.08 | 990.73 | 516.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.96 | 123.46 | 215.55 | 254.18 | 106.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1292.45 | 598.32 | 744.31 | 1836.88 | 993.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.68 | 0.00 | 99.68 | 8.10 | 530.06 | 0.00 | 0.00 | 0.00 |
February | 136.40 | 0.00 | 136.40 | 15.88 | 546.26 | 0.00 | 0.00 | 0.00 |
March | 189.16 | 0.00 | 189.16 | 79.90 | 356.91 | 0.00 | 0.00 | 0.00 |
April | 227.20 | 0.65 | 226.55 | 159.78 | 251.42 | 0.00 | 0.00 | 0.00 |
May | 301.42 | 10.04 | 291.38 | 303.26 | 153.46 | 0.00 | 0.00 | 0.00 |
June | 319.66 | 17.18 | 302.48 | 408.49 | 84.75 | 0.00 | 0.00 | 0.00 |
July | 308.92 | 11.17 | 297.75 | 449.91 | 46.40 | 0.00 | 0.00 | 0.00 |
August | 273.69 | 3.26 | 270.43 | 391.27 | 66.61 | 0.00 | 0.00 | 0.00 |
September | 206.31 | 0.04 | 206.27 | 224.78 | 140.06 | 0.00 | 0.00 | 0.00 |
October | 178.55 | 0.00 | 178.55 | 133.27 | 262.46 | 0.00 | 0.00 | 0.00 |
November | 125.24 | 0.00 | 125.24 | 36.19 | 394.18 | 0.00 | 0.00 | 0.00 |
December | 86.94 | 0.00 | 86.94 | 4.63 | 505.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.82 | 3.55 | 201.28 | 185.76 | 276.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.94 | 0.00 | 86.94 | 4.63 | 46.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 319.66 | 17.18 | 302.48 | 449.91 | 546.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.68 | 0.00 | 99.68 | 8.10 | 530.10 | 0.00 | 0.00 | 0.00 |
February | 136.41 | 0.00 | 136.41 | 15.88 | 546.29 | 0.00 | 0.00 | 0.00 |
March | 189.17 | 0.00 | 189.17 | 79.91 | 356.93 | 0.00 | 0.00 | 0.00 |
April | 227.22 | 0.65 | 226.57 | 159.79 | 251.43 | 0.00 | 0.00 | 0.00 |
May | 301.44 | 10.04 | 291.40 | 303.28 | 153.47 | 0.00 | 0.00 | 0.00 |
June | 319.68 | 17.18 | 302.50 | 408.51 | 84.75 | 0.00 | 0.00 | 0.00 |
July | 308.94 | 11.17 | 297.76 | 449.94 | 46.40 | 0.00 | 0.00 | 0.00 |
August | 273.70 | 3.26 | 270.45 | 391.29 | 66.62 | 0.00 | 0.00 | 0.00 |
September | 206.33 | 0.04 | 206.29 | 224.80 | 140.07 | 0.00 | 0.00 | 0.00 |
October | 178.56 | 0.00 | 178.56 | 133.28 | 262.48 | 0.00 | 0.00 | 0.00 |
November | 125.24 | 0.00 | 125.24 | 36.19 | 394.21 | 0.00 | 0.00 | 0.00 |
December | 86.95 | 0.00 | 86.95 | 4.63 | 505.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.84 | 3.55 | 201.29 | 185.77 | 276.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.95 | 0.00 | 86.95 | 4.63 | 46.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 319.68 | 17.18 | 302.50 | 449.94 | 546.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 99.68 | 0.00 | 99.68 | 8.10 | 530.10 | 0.00 | 0.00 | 0.00 |
February | 136.41 | 0.00 | 136.41 | 15.88 | 546.29 | 0.00 | 0.00 | 0.00 |
March | 189.17 | 0.00 | 189.17 | 79.91 | 356.93 | 0.00 | 0.00 | 0.00 |
April | 227.22 | 0.65 | 226.57 | 159.79 | 251.43 | 0.00 | 0.00 | 0.00 |
May | 301.44 | 10.04 | 291.40 | 303.28 | 153.47 | 0.00 | 0.00 | 0.00 |
June | 319.68 | 17.18 | 302.50 | 408.51 | 84.75 | 0.00 | 0.00 | 0.00 |
July | 308.94 | 11.17 | 297.76 | 449.94 | 46.40 | 0.00 | 0.00 | 0.00 |
August | 273.70 | 3.26 | 270.45 | 391.29 | 66.62 | 0.00 | 0.00 | 0.00 |
September | 206.33 | 0.04 | 206.29 | 224.80 | 140.07 | 0.00 | 0.00 | 0.00 |
October | 178.56 | 0.00 | 178.56 | 133.28 | 262.48 | 0.00 | 0.00 | 0.00 |
November | 125.24 | 0.00 | 125.24 | 36.19 | 394.21 | 0.00 | 0.00 | 0.00 |
December | 86.95 | 0.00 | 86.95 | 4.63 | 505.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.84 | 3.55 | 201.29 | 185.77 | 276.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.95 | 0.00 | 86.95 | 4.63 | 46.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 319.68 | 17.18 | 302.50 | 449.94 | 546.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 400.60 | 160.61 | 239.99 | 258.83 | 955.62 | 0.00 | 0.00 | 0.00 |
February | 621.24 | 289.81 | 331.43 | 453.89 | 959.22 | 0.00 | 0.00 | 0.00 |
March | 792.51 | 337.06 | 455.45 | 723.24 | 675.78 | 0.00 | 0.00 | 0.00 |
April | 951.06 | 416.59 | 534.47 | 996.84 | 485.78 | 0.00 | 0.00 | 0.00 |
May | 1153.44 | 460.98 | 692.46 | 1372.68 | 311.91 | 0.00 | 0.00 | 0.00 |
June | 1069.00 | 386.97 | 682.03 | 1420.50 | 172.62 | 0.00 | 0.00 | 0.00 |
July | 1073.68 | 387.46 | 686.22 | 1539.61 | 96.27 | 0.00 | 0.00 | 0.00 |
August | 1208.99 | 545.13 | 663.86 | 1718.46 | 136.68 | 0.00 | 0.00 | 0.00 |
September | 901.67 | 404.54 | 497.13 | 1135.78 | 270.48 | 0.00 | 0.00 | 0.00 |
October | 817.43 | 370.48 | 446.94 | 912.93 | 503.51 | 0.00 | 0.00 | 0.00 |
November | 505.52 | 194.12 | 311.39 | 409.93 | 725.48 | 0.00 | 0.00 | 0.00 |
December | 393.83 | 184.92 | 208.91 | 272.29 | 905.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 825.39 | 345.28 | 480.11 | 937.92 | 514.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 393.83 | 160.61 | 208.91 | 258.83 | 96.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1208.99 | 545.13 | 692.46 | 1718.46 | 959.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.84 | 6.35 | 9.49 | 10.23 | 37.78 | 0.00 | 0.00 | 0.00 |
February | 24.56 | 11.46 | 13.10 | 17.95 | 37.93 | 0.00 | 0.00 | 0.00 |
March | 31.34 | 13.33 | 18.01 | 28.60 | 26.72 | 0.00 | 0.00 | 0.00 |
April | 37.60 | 16.47 | 21.13 | 39.41 | 19.21 | 0.00 | 0.00 | 0.00 |
May | 45.61 | 18.23 | 27.38 | 54.27 | 12.33 | 0.00 | 0.00 | 0.00 |
June | 42.27 | 15.30 | 26.97 | 56.17 | 6.83 | 0.00 | 0.00 | 0.00 |
July | 42.45 | 15.32 | 27.13 | 60.87 | 3.81 | 0.00 | 0.00 | 0.00 |
August | 47.80 | 21.55 | 26.25 | 67.95 | 5.40 | 0.00 | 0.00 | 0.00 |
September | 35.65 | 16.00 | 19.66 | 44.91 | 10.69 | 0.00 | 0.00 | 0.00 |
October | 32.32 | 14.65 | 17.67 | 36.10 | 19.91 | 0.00 | 0.00 | 0.00 |
November | 19.99 | 7.68 | 12.31 | 16.21 | 28.68 | 0.00 | 0.00 | 0.00 |
December | 15.57 | 7.31 | 8.26 | 10.77 | 35.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.64 | 13.65 | 18.98 | 37.08 | 20.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.57 | 6.35 | 8.26 | 10.23 | 3.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 47.80 | 21.55 | 27.38 | 67.95 | 37.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.68 | 337.67 | 178.01 | 529.71 | 474.78 | 0.00 | 0.00 | 0.00 |
February | 680.16 | 450.21 | 229.95 | 708.28 | 484.25 | 0.00 | 0.00 | 0.00 |
March | 613.63 | 340.58 | 273.06 | 678.37 | 353.15 | 0.00 | 0.00 | 0.00 |
April | 476.16 | 188.29 | 287.87 | 545.02 | 261.73 | 0.00 | 0.00 | 0.00 |
May | 417.28 | 87.04 | 330.24 | 510.07 | 164.43 | 0.00 | 0.00 | 0.00 |
June | 391.61 | 59.86 | 331.74 | 541.74 | 91.37 | 0.00 | 0.00 | 0.00 |
July | 410.48 | 71.30 | 339.18 | 623.49 | 49.47 | 0.00 | 0.00 | 0.00 |
August | 548.15 | 203.32 | 344.83 | 833.38 | 75.00 | 0.00 | 0.00 | 0.00 |
September | 594.76 | 307.63 | 287.12 | 801.99 | 149.62 | 0.00 | 0.00 | 0.00 |
October | 814.77 | 510.92 | 303.85 | 1023.87 | 274.32 | 0.00 | 0.00 | 0.00 |
November | 564.97 | 339.29 | 225.68 | 615.93 | 373.46 | 0.00 | 0.00 | 0.00 |
December | 558.92 | 396.79 | 162.12 | 589.83 | 451.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 548.26 | 273.52 | 274.74 | 666.91 | 265.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 391.61 | 59.86 | 162.12 | 510.07 | 49.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 814.77 | 510.92 | 344.83 | 1023.87 | 484.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.68 | 337.67 | 178.01 | 529.71 | 474.78 | 0.00 | 0.00 | 0.00 |
February | 680.16 | 450.21 | 229.95 | 708.28 | 484.25 | 0.00 | 0.00 | 0.00 |
March | 613.63 | 340.58 | 273.06 | 678.37 | 353.15 | 0.00 | 0.00 | 0.00 |
April | 476.16 | 188.29 | 287.87 | 545.02 | 261.73 | 0.00 | 0.00 | 0.00 |
May | 417.28 | 87.04 | 330.24 | 510.07 | 164.43 | 0.00 | 0.00 | 0.00 |
June | 391.61 | 59.86 | 331.74 | 541.74 | 91.37 | 0.00 | 0.00 | 0.00 |
July | 410.48 | 71.30 | 339.18 | 623.49 | 49.47 | 0.00 | 0.00 | 0.00 |
August | 548.15 | 203.32 | 344.83 | 833.38 | 75.00 | 0.00 | 0.00 | 0.00 |
September | 594.76 | 307.63 | 287.12 | 801.99 | 149.62 | 0.00 | 0.00 | 0.00 |
October | 814.77 | 510.92 | 303.85 | 1023.87 | 274.32 | 0.00 | 0.00 | 0.00 |
November | 564.97 | 339.29 | 225.68 | 615.93 | 373.46 | 0.00 | 0.00 | 0.00 |
December | 558.92 | 396.79 | 162.12 | 589.83 | 451.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 548.26 | 273.52 | 274.74 | 666.91 | 265.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 391.61 | 59.86 | 162.12 | 510.07 | 49.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 814.77 | 510.92 | 344.83 | 1023.87 | 484.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.64 | 337.65 | 178.00 | 529.68 | 474.75 | 0.00 | 0.00 | 0.00 |
February | 680.12 | 450.18 | 229.93 | 708.24 | 484.22 | 0.00 | 0.00 | 0.00 |
March | 613.59 | 340.55 | 273.04 | 678.33 | 353.13 | 0.00 | 0.00 | 0.00 |
April | 476.13 | 188.27 | 287.85 | 544.99 | 261.71 | 0.00 | 0.00 | 0.00 |
May | 417.25 | 87.03 | 330.22 | 510.04 | 164.42 | 0.00 | 0.00 | 0.00 |
June | 391.58 | 59.86 | 331.72 | 541.70 | 91.37 | 0.00 | 0.00 | 0.00 |
July | 410.46 | 71.30 | 339.16 | 623.45 | 49.46 | 0.00 | 0.00 | 0.00 |
August | 548.12 | 203.31 | 344.81 | 833.32 | 75.00 | 0.00 | 0.00 | 0.00 |
September | 594.72 | 307.61 | 287.11 | 801.94 | 149.61 | 0.00 | 0.00 | 0.00 |
October | 814.71 | 510.88 | 303.83 | 1023.80 | 274.30 | 0.00 | 0.00 | 0.00 |
November | 564.93 | 339.27 | 225.66 | 615.89 | 373.44 | 0.00 | 0.00 | 0.00 |
December | 558.88 | 396.77 | 162.11 | 589.80 | 451.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 548.23 | 273.50 | 274.73 | 666.87 | 265.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 391.58 | 59.86 | 162.11 | 510.04 | 49.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 814.71 | 510.88 | 344.81 | 1023.80 | 484.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 395.48 | 161.99 | 233.49 | 258.22 | 975.72 | 0.00 | 0.00 | 0.00 |
February | 583.19 | 256.14 | 327.05 | 422.39 | 1000.89 | 0.00 | 0.00 | 0.00 |
March | 861.15 | 397.57 | 463.58 | 811.57 | 678.70 | 0.00 | 0.00 | 0.00 |
April | 941.20 | 402.71 | 538.49 | 999.07 | 502.35 | 0.00 | 0.00 | 0.00 |
May | 1096.40 | 416.37 | 680.03 | 1311.35 | 324.94 | 0.00 | 0.00 | 0.00 |
June | 1199.98 | 483.98 | 716.00 | 1603.97 | 186.22 | 0.00 | 0.00 | 0.00 |
July | 1123.85 | 423.20 | 700.64 | 1609.38 | 104.31 | 0.00 | 0.00 | 0.00 |
August | 1243.28 | 575.55 | 667.73 | 1775.13 | 148.47 | 0.00 | 0.00 | 0.00 |
September | 882.63 | 385.71 | 496.92 | 1123.91 | 283.60 | 0.00 | 0.00 | 0.00 |
October | 875.06 | 425.52 | 449.54 | 996.56 | 521.87 | 0.00 | 0.00 | 0.00 |
November | 410.93 | 118.76 | 292.17 | 286.15 | 740.19 | 0.00 | 0.00 | 0.00 |
December | 365.51 | 158.16 | 207.35 | 241.20 | 930.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 833.30 | 351.28 | 482.02 | 957.06 | 530.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 365.51 | 118.76 | 207.35 | 241.20 | 104.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1243.28 | 575.55 | 716.00 | 1775.13 | 1000.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 15.64 | 6.40 | 9.23 | 10.21 | 38.58 | 0.00 | 0.00 | 0.00 |
February | 23.06 | 10.13 | 12.93 | 16.70 | 39.57 | 0.00 | 0.00 | 0.00 |
March | 34.05 | 15.72 | 18.33 | 32.09 | 26.84 | 0.00 | 0.00 | 0.00 |
April | 37.21 | 15.92 | 21.29 | 39.50 | 19.86 | 0.00 | 0.00 | 0.00 |
May | 43.35 | 16.46 | 26.89 | 51.85 | 12.85 | 0.00 | 0.00 | 0.00 |
June | 47.45 | 19.14 | 28.31 | 63.42 | 7.36 | 0.00 | 0.00 | 0.00 |
July | 44.44 | 16.73 | 27.70 | 63.63 | 4.12 | 0.00 | 0.00 | 0.00 |
August | 49.16 | 22.76 | 26.40 | 70.19 | 5.87 | 0.00 | 0.00 | 0.00 |
September | 34.90 | 15.25 | 19.65 | 44.44 | 11.21 | 0.00 | 0.00 | 0.00 |
October | 34.60 | 16.82 | 17.77 | 39.40 | 20.63 | 0.00 | 0.00 | 0.00 |
November | 16.25 | 4.70 | 11.55 | 11.31 | 29.27 | 0.00 | 0.00 | 0.00 |
December | 14.45 | 6.25 | 8.20 | 9.54 | 36.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.95 | 13.89 | 19.06 | 37.84 | 20.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.45 | 4.70 | 8.20 | 9.54 | 4.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 49.16 | 22.76 | 28.31 | 70.19 | 39.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 299.04 | 0.00 | 299.04 | 22.81 | 1597.88 | 0.00 | 0.00 | 0.00 |
February | 409.23 | 0.00 | 409.23 | 43.36 | 1664.67 | 0.00 | 0.00 | 0.00 |
March | 567.49 | 0.00 | 567.49 | 219.63 | 1112.40 | 0.00 | 0.00 | 0.00 |
April | 681.64 | 1.94 | 679.70 | 446.03 | 799.48 | 0.00 | 0.00 | 0.00 |
May | 904.31 | 30.13 | 874.18 | 864.23 | 497.79 | 0.00 | 0.00 | 0.00 |
June | 959.01 | 51.53 | 907.48 | 1200.30 | 273.60 | 0.00 | 0.00 | 0.00 |
July | 926.79 | 33.52 | 893.28 | 1331.13 | 151.94 | 0.00 | 0.00 | 0.00 |
August | 821.09 | 9.77 | 811.32 | 1164.27 | 207.71 | 0.00 | 0.00 | 0.00 |
September | 618.97 | 0.12 | 618.85 | 670.48 | 419.33 | 0.00 | 0.00 | 0.00 |
October | 535.67 | 0.00 | 535.67 | 399.96 | 773.52 | 0.00 | 0.00 | 0.00 |
November | 375.72 | 0.00 | 375.72 | 110.79 | 1150.70 | 0.00 | 0.00 | 0.00 |
December | 260.84 | 0.00 | 260.84 | 13.91 | 1498.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 614.50 | 10.64 | 603.86 | 543.93 | 840.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 260.84 | 0.00 | 260.84 | 13.91 | 151.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 959.01 | 51.53 | 907.48 | 1331.13 | 1664.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.44 | 166.96 | 249.48 | 264.78 | 992.26 | 0.00 | 0.00 | 0.00 |
February | 645.81 | 301.27 | 344.54 | 463.22 | 1001.89 | 0.00 | 0.00 | 0.00 |
March | 823.85 | 350.39 | 473.46 | 735.41 | 715.20 | 0.00 | 0.00 | 0.00 |
April | 988.68 | 433.07 | 555.61 | 1017.53 | 515.82 | 0.00 | 0.00 | 0.00 |
May | 1199.06 | 479.21 | 719.84 | 1404.43 | 336.33 | 0.00 | 0.00 | 0.00 |
June | 1111.27 | 402.27 | 709.00 | 1462.67 | 185.37 | 0.00 | 0.00 | 0.00 |
July | 1116.14 | 402.78 | 713.35 | 1591.07 | 102.18 | 0.00 | 0.00 | 0.00 |
August | 1256.80 | 566.69 | 690.11 | 1781.25 | 138.86 | 0.00 | 0.00 | 0.00 |
September | 937.33 | 420.54 | 516.79 | 1178.84 | 269.89 | 0.00 | 0.00 | 0.00 |
October | 849.76 | 385.14 | 464.62 | 950.64 | 497.93 | 0.00 | 0.00 | 0.00 |
November | 525.51 | 201.80 | 323.71 | 430.38 | 720.92 | 0.00 | 0.00 | 0.00 |
December | 409.40 | 192.23 | 217.17 | 282.23 | 922.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 858.03 | 358.94 | 499.09 | 967.01 | 530.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 409.40 | 166.96 | 217.17 | 264.78 | 102.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1256.80 | 566.69 | 719.84 | 1781.25 | 1001.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1546.98 | 1012.97 | 534.01 | 1546.12 | 1438.84 | 0.00 | 0.00 | 0.00 |
February | 2040.41 | 1350.59 | 689.83 | 2069.06 | 1466.05 | 0.00 | 0.00 | 0.00 |
March | 1840.84 | 1021.70 | 819.14 | 1978.32 | 1091.04 | 0.00 | 0.00 | 0.00 |
April | 1428.43 | 564.84 | 863.59 | 1585.80 | 826.60 | 0.00 | 0.00 | 0.00 |
May | 1251.81 | 261.11 | 990.70 | 1473.95 | 535.63 | 0.00 | 0.00 | 0.00 |
June | 1174.78 | 179.58 | 995.21 | 1596.02 | 293.02 | 0.00 | 0.00 | 0.00 |
July | 1231.41 | 213.89 | 1017.51 | 1854.08 | 156.39 | 0.00 | 0.00 | 0.00 |
August | 1644.41 | 609.94 | 1034.47 | 2492.67 | 220.57 | 0.00 | 0.00 | 0.00 |
September | 1784.21 | 922.87 | 861.35 | 2397.24 | 431.04 | 0.00 | 0.00 | 0.00 |
October | 2444.22 | 1532.70 | 911.52 | 3059.59 | 776.45 | 0.00 | 0.00 | 0.00 |
November | 1694.86 | 1017.84 | 677.02 | 1824.07 | 1086.87 | 0.00 | 0.00 | 0.00 |
December | 1676.69 | 1190.34 | 486.35 | 1738.90 | 1337.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1644.73 | 820.53 | 824.21 | 1968.44 | 801.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1174.78 | 179.58 | 486.35 | 1473.95 | 156.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2444.22 | 1532.70 | 1034.47 | 3059.59 | 1466.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 411.12 | 168.40 | 242.72 | 263.18 | 1014.77 | 0.00 | 0.00 | 0.00 |
February | 606.25 | 266.27 | 339.99 | 428.70 | 1047.19 | 0.00 | 0.00 | 0.00 |
March | 895.21 | 413.29 | 481.92 | 826.53 | 716.58 | 0.00 | 0.00 | 0.00 |
April | 978.42 | 418.64 | 559.78 | 1019.63 | 534.64 | 0.00 | 0.00 | 0.00 |
May | 1139.76 | 432.84 | 706.93 | 1341.36 | 351.33 | 0.00 | 0.00 | 0.00 |
June | 1247.44 | 503.13 | 744.31 | 1654.23 | 197.85 | 0.00 | 0.00 | 0.00 |
July | 1168.29 | 439.94 | 728.35 | 1663.81 | 109.71 | 0.00 | 0.00 | 0.00 |
August | 1292.45 | 598.32 | 694.13 | 1840.71 | 150.35 | 0.00 | 0.00 | 0.00 |
September | 917.53 | 400.96 | 516.57 | 1167.41 | 284.57 | 0.00 | 0.00 | 0.00 |
October | 909.67 | 442.35 | 467.32 | 1038.61 | 516.31 | 0.00 | 0.00 | 0.00 |
November | 427.18 | 123.46 | 303.72 | 299.36 | 742.28 | 0.00 | 0.00 | 0.00 |
December | 379.96 | 164.41 | 215.55 | 248.52 | 950.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 866.25 | 365.17 | 501.08 | 986.65 | 548.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.96 | 123.46 | 215.55 | 248.52 | 109.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1292.45 | 598.32 | 744.31 | 1840.71 | 1047.19 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.800952E+09 | 0.00 | 0.800952E+09 | 69661842.76 | 0.408610E+10 |
February | 0.989997E+09 | 0.00 | 0.989997E+09 | 0.116316E+09 | 0.382461E+10 |
March | 0.151997E+10 | 0.00 | 0.151997E+10 | 0.616379E+09 | 0.279491E+10 |
April | 0.176680E+10 | 5025323.02 | 0.176177E+10 | 0.119219E+10 | 0.193411E+10 |
May | 0.242211E+10 | 80706178.30 | 0.234141E+10 | 0.233808E+10 | 0.126878E+10 |
June | 0.248576E+10 | 0.133570E+09 | 0.235219E+10 | 0.310326E+10 | 0.686431E+09 |
July | 0.248232E+10 | 89769122.78 | 0.239255E+10 | 0.354387E+10 | 0.399025E+09 |
August | 0.219922E+10 | 26173819.73 | 0.217305E+10 | 0.310716E+10 | 0.538801E+09 |
September | 0.160437E+10 | 300432.95 | 0.160407E+10 | 0.175089E+10 | 0.102209E+10 |
October | 0.143475E+10 | 0.00 | 0.143475E+10 | 0.111934E+10 | 0.191409E+10 |
November | 0.973875E+09 | 0.00 | 0.973875E+09 | 0.327760E+09 | 0.274576E+10 |
December | 0.698643E+09 | 0.00 | 0.698643E+09 | 47971650.87 | 0.375898E+10 |
Annual Sum or Average | 0.193788E+11 | 0.335545E+09 | 0.190432E+11 | 0.173329E+11 | 0.249737E+11 |
Minimum of Months | 0.698643E+09 | 0.00 | 0.698643E+09 | 47971650.87 | 0.399025E+09 |
Maximum of Months | 0.248576E+10 | 0.133570E+09 | 0.239255E+10 | 0.354387E+10 | 0.408610E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111539E+10 | 0.447180E+09 | 0.668210E+09 | 0.723319E+09 | 0.253549E+10 |
February | 0.156234E+10 | 0.728829E+09 | 0.833507E+09 | 0.114332E+10 | 0.230072E+10 |
March | 0.220660E+10 | 0.938479E+09 | 0.126812E+10 | 0.199302E+10 | 0.180204E+10 |
April | 0.256265E+10 | 0.112252E+10 | 0.144013E+10 | 0.265987E+10 | 0.125779E+10 |
May | 0.321155E+10 | 0.128353E+10 | 0.192803E+10 | 0.377035E+10 | 0.861046E+09 |
June | 0.288042E+10 | 0.104269E+10 | 0.183773E+10 | 0.378381E+10 | 0.465848E+09 |
July | 0.298946E+10 | 0.107882E+10 | 0.191064E+10 | 0.424587E+10 | 0.268184E+09 |
August | 0.336621E+10 | 0.151782E+10 | 0.184839E+10 | 0.475941E+10 | 0.361172E+09 |
September | 0.242955E+10 | 0.109004E+10 | 0.133951E+10 | 0.306110E+10 | 0.662027E+09 |
October | 0.227598E+10 | 0.103155E+10 | 0.124443E+10 | 0.257364E+10 | 0.124232E+10 |
November | 0.136212E+10 | 0.523065E+09 | 0.839051E+09 | 0.115306E+10 | 0.172912E+10 |
December | 0.109654E+10 | 0.514866E+09 | 0.581672E+09 | 0.778879E+09 | 0.231454E+10 |
Annual Sum or Average | 0.270588E+11 | 0.113194E+11 | 0.157394E+11 | 0.306457E+11 | 0.158003E+11 |
Minimum of Months | 0.109654E+10 | 0.447180E+09 | 0.581672E+09 | 0.723319E+09 | 0.268184E+09 |
Maximum of Months | 0.336621E+10 | 0.151782E+10 | 0.192803E+10 | 0.475941E+10 | 0.253549E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.414343E+10 | 0.271314E+10 | 0.143029E+10 | 0.416941E+10 | 0.366407E+10 |
February | 0.493617E+10 | 0.326734E+10 | 0.166883E+10 | 0.504595E+10 | 0.335662E+10 |
March | 0.493050E+10 | 0.273651E+10 | 0.219399E+10 | 0.532985E+10 | 0.274134E+10 |
April | 0.370248E+10 | 0.146407E+10 | 0.223842E+10 | 0.414057E+10 | 0.200537E+10 |
May | 0.335284E+10 | 0.699346E+09 | 0.265349E+10 | 0.396334E+10 | 0.136153E+10 |
June | 0.304504E+10 | 0.465464E+09 | 0.257958E+10 | 0.412675E+10 | 0.732439E+09 |
July | 0.329820E+10 | 0.572895E+09 | 0.272531E+10 | 0.494449E+10 | 0.408777E+09 |
August | 0.440438E+10 | 0.163365E+10 | 0.277073E+10 | 0.665888E+10 | 0.571810E+09 |
September | 0.462468E+10 | 0.239207E+10 | 0.223261E+10 | 0.621860E+10 | 0.105584E+10 |
October | 0.654660E+10 | 0.410518E+10 | 0.244142E+10 | 0.822393E+10 | 0.194114E+10 |
November | 0.439307E+10 | 0.263825E+10 | 0.175482E+10 | 0.478732E+10 | 0.260384E+10 |
December | 0.449086E+10 | 0.318821E+10 | 0.130265E+10 | 0.470767E+10 | 0.334857E+10 |
Annual Sum or Average | 0.518683E+11 | 0.258761E+11 | 0.259921E+11 | 0.623168E+11 | 0.237913E+11 |
Minimum of Months | 0.304504E+10 | 0.465464E+09 | 0.130265E+10 | 0.396334E+10 | 0.408777E+09 |
Maximum of Months | 0.654660E+10 | 0.410518E+10 | 0.277073E+10 | 0.822393E+10 | 0.366407E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110114E+10 | 0.451030E+09 | 0.650111E+09 | 0.714229E+09 | 0.259266E+10 |
February | 0.146665E+10 | 0.644157E+09 | 0.822493E+09 | 0.105017E+10 | 0.240432E+10 |
March | 0.239773E+10 | 0.110696E+10 | 0.129076E+10 | 0.223321E+10 | 0.180204E+10 |
April | 0.253607E+10 | 0.108512E+10 | 0.145095E+10 | 0.266446E+10 | 0.129711E+10 |
May | 0.305274E+10 | 0.115931E+10 | 0.189343E+10 | 0.360555E+10 | 0.893770E+09 |
June | 0.323335E+10 | 0.130410E+10 | 0.192925E+10 | 0.428056E+10 | 0.494815E+09 |
July | 0.312915E+10 | 0.117834E+10 | 0.195081E+10 | 0.444165E+10 | 0.286544E+09 |
August | 0.346169E+10 | 0.160253E+10 | 0.185916E+10 | 0.491991E+10 | 0.390433E+09 |
September | 0.237825E+10 | 0.103929E+10 | 0.133896E+10 | 0.303473E+10 | 0.694621E+09 |
October | 0.243645E+10 | 0.118478E+10 | 0.125167E+10 | 0.281161E+10 | 0.128292E+10 |
November | 0.110724E+10 | 0.320000E+09 | 0.787241E+09 | 0.806813E+09 | 0.177553E+10 |
December | 0.101770E+10 | 0.440359E+09 | 0.577337E+09 | 0.680799E+09 | 0.238282E+10 |
Annual Sum or Average | 0.273181E+11 | 0.115160E+11 | 0.158022E+11 | 0.312437E+11 | 0.162976E+11 |
Minimum of Months | 0.101770E+10 | 0.320000E+09 | 0.577337E+09 | 0.680799E+09 | 0.286544E+09 |
Maximum of Months | 0.346169E+10 | 0.160253E+10 | 0.195081E+10 | 0.491991E+10 | 0.259266E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.266971E+09 | 0.00 | 0.266971E+09 | 21692076.37 | 0.141973E+10 |
February | 0.329983E+09 | 0.00 | 0.329983E+09 | 38419021.55 | 0.132151E+10 |
March | 0.506633E+09 | 0.00 | 0.506633E+09 | 0.214017E+09 | 0.955944E+09 |
April | 0.588905E+09 | 1675028.42 | 0.587230E+09 | 0.414155E+09 | 0.651673E+09 |
May | 0.807333E+09 | 26900786.64 | 0.780432E+09 | 0.812262E+09 | 0.411029E+09 |
June | 0.828548E+09 | 44521364.70 | 0.784027E+09 | 0.105880E+10 | 0.219663E+09 |
July | 0.827402E+09 | 29921625.21 | 0.797480E+09 | 0.120505E+10 | 0.124268E+09 |
August | 0.733039E+09 | 8724193.80 | 0.724315E+09 | 0.104798E+10 | 0.178414E+09 |
September | 0.534764E+09 | 100139.58 | 0.534664E+09 | 0.582639E+09 | 0.363045E+09 |
October | 0.478227E+09 | 0.00 | 0.478227E+09 | 0.356957E+09 | 0.702971E+09 |
November | 0.324610E+09 | 0.00 | 0.324610E+09 | 93810390.41 | 0.102172E+10 |
December | 0.232870E+09 | 0.00 | 0.232870E+09 | 12411230.85 | 0.135305E+10 |
Annual Sum or Average | 0.645929E+10 | 0.111843E+09 | 0.634744E+10 | 0.585818E+10 | 0.872302E+10 |
Minimum of Months | 0.232870E+09 | 0.00 | 0.232870E+09 | 12411230.85 | 0.124268E+09 |
Maximum of Months | 0.828548E+09 | 44521364.70 | 0.797480E+09 | 0.120505E+10 | 0.141973E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.266988E+09 | 0.00 | 0.266988E+09 | 21693447.27 | 0.141982E+10 |
February | 0.330004E+09 | 0.00 | 0.330004E+09 | 38421449.57 | 0.132159E+10 |
March | 0.506665E+09 | 0.00 | 0.506665E+09 | 0.214030E+09 | 0.956004E+09 |
April | 0.588943E+09 | 1675134.28 | 0.587267E+09 | 0.414181E+09 | 0.651715E+09 |
May | 0.807384E+09 | 26902486.73 | 0.780481E+09 | 0.812313E+09 | 0.411055E+09 |
June | 0.828600E+09 | 44524178.37 | 0.784076E+09 | 0.105886E+10 | 0.219677E+09 |
July | 0.827454E+09 | 29923516.20 | 0.797531E+09 | 0.120512E+10 | 0.124276E+09 |
August | 0.733085E+09 | 8724745.15 | 0.724360E+09 | 0.104804E+10 | 0.178425E+09 |
September | 0.534798E+09 | 100145.91 | 0.534698E+09 | 0.582676E+09 | 0.363068E+09 |
October | 0.478257E+09 | 0.00 | 0.478257E+09 | 0.356980E+09 | 0.703016E+09 |
November | 0.324630E+09 | 0.00 | 0.324630E+09 | 93816319.07 | 0.102179E+10 |
December | 0.232885E+09 | 0.00 | 0.232885E+09 | 12412015.22 | 0.135314E+10 |
Annual Sum or Average | 0.645969E+10 | 0.111850E+09 | 0.634784E+10 | 0.585855E+10 | 0.872357E+10 |
Minimum of Months | 0.232885E+09 | 0.00 | 0.232885E+09 | 12412015.22 | 0.124276E+09 |
Maximum of Months | 0.828600E+09 | 44524178.37 | 0.797531E+09 | 0.120512E+10 | 0.141982E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.266988E+09 | 0.00 | 0.266988E+09 | 21693447.27 | 0.141982E+10 |
February | 0.330004E+09 | 0.00 | 0.330004E+09 | 38421449.57 | 0.132159E+10 |
March | 0.506665E+09 | 0.00 | 0.506665E+09 | 0.214030E+09 | 0.956004E+09 |
April | 0.588943E+09 | 1675134.28 | 0.587267E+09 | 0.414181E+09 | 0.651715E+09 |
May | 0.807384E+09 | 26902486.73 | 0.780481E+09 | 0.812313E+09 | 0.411055E+09 |
June | 0.828600E+09 | 44524178.37 | 0.784076E+09 | 0.105886E+10 | 0.219677E+09 |
July | 0.827454E+09 | 29923516.20 | 0.797531E+09 | 0.120512E+10 | 0.124276E+09 |
August | 0.733085E+09 | 8724745.15 | 0.724360E+09 | 0.104804E+10 | 0.178425E+09 |
September | 0.534798E+09 | 100145.91 | 0.534698E+09 | 0.582676E+09 | 0.363068E+09 |
October | 0.478257E+09 | 0.00 | 0.478257E+09 | 0.356980E+09 | 0.703016E+09 |
November | 0.324630E+09 | 0.00 | 0.324630E+09 | 93816319.07 | 0.102179E+10 |
December | 0.232885E+09 | 0.00 | 0.232885E+09 | 12412015.22 | 0.135314E+10 |
Annual Sum or Average | 0.645969E+10 | 0.111850E+09 | 0.634784E+10 | 0.585855E+10 | 0.872357E+10 |
Minimum of Months | 0.232885E+09 | 0.00 | 0.232885E+09 | 12412015.22 | 0.124276E+09 |
Maximum of Months | 0.828600E+09 | 44524178.37 | 0.797531E+09 | 0.120512E+10 | 0.141982E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.107296E+10 | 0.430167E+09 | 0.642790E+09 | 0.693241E+09 | 0.255953E+10 |
February | 0.150290E+10 | 0.701101E+09 | 0.801800E+09 | 0.109804E+10 | 0.232054E+10 |
March | 0.212265E+10 | 0.902774E+09 | 0.121988E+10 | 0.193713E+10 | 0.181000E+10 |
April | 0.246516E+10 | 0.107981E+10 | 0.138535E+10 | 0.258381E+10 | 0.125913E+10 |
May | 0.308938E+10 | 0.123469E+10 | 0.185468E+10 | 0.367658E+10 | 0.835429E+09 |
June | 0.277084E+10 | 0.100302E+10 | 0.176782E+10 | 0.368193E+10 | 0.447440E+09 |
July | 0.287574E+10 | 0.103778E+10 | 0.183796E+10 | 0.412368E+10 | 0.257858E+09 |
August | 0.323815E+10 | 0.146007E+10 | 0.177807E+10 | 0.460273E+10 | 0.366085E+09 |
September | 0.233712E+10 | 0.104857E+10 | 0.128855E+10 | 0.294393E+10 | 0.701089E+09 |
October | 0.218940E+10 | 0.992306E+09 | 0.119709E+10 | 0.244520E+10 | 0.134859E+10 |
November | 0.131030E+10 | 0.503165E+09 | 0.807132E+09 | 0.106253E+10 | 0.188043E+10 |
December | 0.105482E+10 | 0.495278E+09 | 0.559545E+09 | 0.729312E+09 | 0.242563E+10 |
Annual Sum or Average | 0.260294E+11 | 0.108887E+11 | 0.151407E+11 | 0.295781E+11 | 0.162118E+11 |
Minimum of Months | 0.105482E+10 | 0.430167E+09 | 0.559545E+09 | 0.693241E+09 | 0.257858E+09 |
Maximum of Months | 0.323815E+10 | 0.146007E+10 | 0.185468E+10 | 0.460273E+10 | 0.255953E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 42423779.60 | 17008434.29 | 25415345.31 | 27410112.04 | 0.101201E+09 |
February | 59423351.52 | 27720902.05 | 31702449.46 | 43415619.60 | 91752167.34 |
March | 83927777.31 | 35694885.87 | 48232891.44 | 76592552.08 | 71565723.77 |
April | 97470154.82 | 42694718.37 | 54775436.45 | 0.102161E+09 | 49784991.82 |
May | 0.122151E+09 | 48818725.42 | 73332505.75 | 0.145369E+09 | 33032091.12 |
June | 0.109557E+09 | 39658437.19 | 69898088.15 | 0.145580E+09 | 17691391.07 |
July | 0.113704E+09 | 41032713.71 | 72671289.02 | 0.163047E+09 | 10195491.12 |
August | 0.128033E+09 | 57729954.46 | 70303454.55 | 0.181988E+09 | 14474664.82 |
September | 92407707.83 | 41459503.73 | 50948204.10 | 0.116400E+09 | 27720418.72 |
October | 86566907.50 | 39234872.02 | 47332035.48 | 96680821.22 | 53322007.97 |
November | 51807968.92 | 19894701.90 | 31913267.02 | 42011517.88 | 74350694.33 |
December | 41706729.51 | 19582843.72 | 22123885.79 | 28836321.08 | 95907300.75 |
Annual Sum or Average | 0.102918E+10 | 0.430531E+09 | 0.598649E+09 | 0.116949E+10 | 0.640998E+09 |
Minimum of Months | 41706729.51 | 17008434.29 | 22123885.79 | 27410112.04 | 10195491.12 |
Maximum of Months | 0.128033E+09 | 57729954.46 | 73332505.75 | 0.181988E+09 | 0.101201E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138119E+10 | 0.904410E+09 | 0.476777E+09 | 0.141877E+10 | 0.127166E+10 |
February | 0.164544E+10 | 0.108915E+10 | 0.556293E+09 | 0.171348E+10 | 0.117150E+10 |
March | 0.164355E+10 | 0.912200E+09 | 0.731352E+09 | 0.181694E+10 | 0.945872E+09 |
April | 0.123420E+10 | 0.488039E+09 | 0.746159E+09 | 0.141269E+10 | 0.678407E+09 |
May | 0.111765E+10 | 0.233123E+09 | 0.884522E+09 | 0.136618E+10 | 0.440407E+09 |
June | 0.101504E+10 | 0.155160E+09 | 0.859882E+09 | 0.140418E+10 | 0.236834E+09 |
July | 0.109943E+10 | 0.190971E+09 | 0.908462E+09 | 0.166995E+10 | 0.132489E+09 |
August | 0.146817E+10 | 0.544569E+09 | 0.923602E+09 | 0.223212E+10 | 0.200891E+09 |
September | 0.154161E+10 | 0.797383E+09 | 0.744225E+09 | 0.207875E+10 | 0.387815E+09 |
October | 0.218227E+10 | 0.136844E+10 | 0.813829E+09 | 0.274232E+10 | 0.734744E+09 |
November | 0.146440E+10 | 0.879444E+09 | 0.584959E+09 | 0.159649E+10 | 0.968009E+09 |
December | 0.149700E+10 | 0.106277E+10 | 0.434230E+09 | 0.157981E+10 | 0.120927E+10 |
Annual Sum or Average | 0.172899E+11 | 0.862566E+10 | 0.866429E+10 | 0.210317E+11 | 0.837790E+10 |
Minimum of Months | 0.101504E+10 | 0.155160E+09 | 0.434230E+09 | 0.136618E+10 | 0.132489E+09 |
Maximum of Months | 0.218227E+10 | 0.136844E+10 | 0.923602E+09 | 0.274232E+10 | 0.127166E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138119E+10 | 0.904410E+09 | 0.476777E+09 | 0.141877E+10 | 0.127166E+10 |
February | 0.164544E+10 | 0.108915E+10 | 0.556293E+09 | 0.171348E+10 | 0.117150E+10 |
March | 0.164355E+10 | 0.912200E+09 | 0.731352E+09 | 0.181694E+10 | 0.945872E+09 |
April | 0.123420E+10 | 0.488039E+09 | 0.746159E+09 | 0.141269E+10 | 0.678407E+09 |
May | 0.111765E+10 | 0.233123E+09 | 0.884522E+09 | 0.136618E+10 | 0.440407E+09 |
June | 0.101504E+10 | 0.155160E+09 | 0.859882E+09 | 0.140418E+10 | 0.236834E+09 |
July | 0.109943E+10 | 0.190971E+09 | 0.908462E+09 | 0.166995E+10 | 0.132489E+09 |
August | 0.146817E+10 | 0.544569E+09 | 0.923602E+09 | 0.223212E+10 | 0.200891E+09 |
September | 0.154161E+10 | 0.797383E+09 | 0.744225E+09 | 0.207875E+10 | 0.387815E+09 |
October | 0.218227E+10 | 0.136844E+10 | 0.813829E+09 | 0.274232E+10 | 0.734744E+09 |
November | 0.146440E+10 | 0.879444E+09 | 0.584959E+09 | 0.159649E+10 | 0.968009E+09 |
December | 0.149700E+10 | 0.106277E+10 | 0.434230E+09 | 0.157981E+10 | 0.120927E+10 |
Annual Sum or Average | 0.172899E+11 | 0.862566E+10 | 0.866429E+10 | 0.210317E+11 | 0.837790E+10 |
Minimum of Months | 0.101504E+10 | 0.155160E+09 | 0.434230E+09 | 0.136618E+10 | 0.132489E+09 |
Maximum of Months | 0.218227E+10 | 0.136844E+10 | 0.923602E+09 | 0.274232E+10 | 0.127166E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138110E+10 | 0.904353E+09 | 0.476747E+09 | 0.141868E+10 | 0.127158E+10 |
February | 0.164534E+10 | 0.108908E+10 | 0.556258E+09 | 0.171337E+10 | 0.117142E+10 |
March | 0.164345E+10 | 0.912142E+09 | 0.731306E+09 | 0.181683E+10 | 0.945812E+09 |
April | 0.123412E+10 | 0.488008E+09 | 0.746112E+09 | 0.141260E+10 | 0.678364E+09 |
May | 0.111757E+10 | 0.233108E+09 | 0.884466E+09 | 0.136609E+10 | 0.440379E+09 |
June | 0.101498E+10 | 0.155150E+09 | 0.859828E+09 | 0.140409E+10 | 0.236819E+09 |
July | 0.109936E+10 | 0.190959E+09 | 0.908404E+09 | 0.166984E+10 | 0.132480E+09 |
August | 0.146808E+10 | 0.544535E+09 | 0.923544E+09 | 0.223198E+10 | 0.200878E+09 |
September | 0.154151E+10 | 0.797333E+09 | 0.744178E+09 | 0.207862E+10 | 0.387790E+09 |
October | 0.218213E+10 | 0.136835E+10 | 0.813778E+09 | 0.274215E+10 | 0.734698E+09 |
November | 0.146431E+10 | 0.879388E+09 | 0.584922E+09 | 0.159639E+10 | 0.967947E+09 |
December | 0.149691E+10 | 0.106270E+10 | 0.434203E+09 | 0.157971E+10 | 0.120920E+10 |
Annual Sum or Average | 0.172889E+11 | 0.862511E+10 | 0.866374E+10 | 0.210304E+11 | 0.837737E+10 |
Minimum of Months | 0.101498E+10 | 0.155150E+09 | 0.434203E+09 | 0.136609E+10 | 0.132480E+09 |
Maximum of Months | 0.218213E+10 | 0.136835E+10 | 0.923544E+09 | 0.274215E+10 | 0.127158E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105925E+10 | 0.433871E+09 | 0.625380E+09 | 0.691618E+09 | 0.261336E+10 |
February | 0.141085E+10 | 0.619650E+09 | 0.791205E+09 | 0.102185E+10 | 0.242136E+10 |
March | 0.230651E+10 | 0.106485E+10 | 0.124166E+10 | 0.217371E+10 | 0.181784E+10 |
April | 0.243959E+10 | 0.104383E+10 | 0.139576E+10 | 0.258959E+10 | 0.130210E+10 |
May | 0.293660E+10 | 0.111520E+10 | 0.182140E+10 | 0.351233E+10 | 0.870324E+09 |
June | 0.311035E+10 | 0.125449E+10 | 0.185586E+10 | 0.415749E+10 | 0.482684E+09 |
July | 0.301011E+10 | 0.113351E+10 | 0.187660E+10 | 0.431057E+10 | 0.279396E+09 |
August | 0.333000E+10 | 0.154156E+10 | 0.178843E+10 | 0.475450E+10 | 0.397664E+09 |
September | 0.228777E+10 | 0.999747E+09 | 0.128803E+10 | 0.291319E+10 | 0.735101E+09 |
October | 0.234376E+10 | 0.113971E+10 | 0.120405E+10 | 0.266919E+10 | 0.139777E+10 |
November | 0.106512E+10 | 0.307825E+09 | 0.757293E+09 | 0.741701E+09 | 0.191856E+10 |
December | 0.978981E+09 | 0.423606E+09 | 0.555375E+09 | 0.646019E+09 | 0.249203E+10 |
Annual Sum or Average | 0.262789E+11 | 0.110779E+11 | 0.152010E+11 | 0.301818E+11 | 0.167282E+11 |
Minimum of Months | 0.978981E+09 | 0.307825E+09 | 0.555375E+09 | 0.646019E+09 | 0.279396E+09 |
Maximum of Months | 0.333000E+10 | 0.154156E+10 | 0.187660E+10 | 0.475450E+10 | 0.261336E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 41881722.35 | 17154805.50 | 24726916.85 | 27345821.09 | 0.103330E+09 |
February | 55783778.15 | 24500333.57 | 31283444.58 | 40402945.69 | 95738385.17 |
March | 91197099.77 | 42103006.45 | 49094093.32 | 85946129.75 | 71875764.02 |
April | 96458942.92 | 41272093.29 | 55186849.63 | 0.102390E+09 | 51483763.11 |
May | 0.116110E+09 | 44093983.43 | 72016417.29 | 0.138874E+09 | 34411826.58 |
June | 0.122980E+09 | 49601099.07 | 73378927.75 | 0.164383E+09 | 19084877.74 |
July | 0.119017E+09 | 44817757.63 | 74198901.55 | 0.170436E+09 | 11047065.60 |
August | 0.131665E+09 | 60951800.67 | 70712945.73 | 0.187988E+09 | 15723257.54 |
September | 90456295.00 | 39528985.56 | 50927309.44 | 0.115184E+09 | 29065198.23 |
October | 92669939.05 | 45062924.06 | 47607014.99 | 0.105537E+09 | 55266568.39 |
November | 42113711.60 | 12171094.35 | 29942617.25 | 29326063.72 | 75858200.55 |
December | 38707902.22 | 16748947.55 | 21958954.68 | 25542892.78 | 98532478.30 |
Annual Sum or Average | 0.103904E+10 | 0.438007E+09 | 0.601034E+09 | 0.119336E+10 | 0.661417E+09 |
Minimum of Months | 38707902.22 | 12171094.35 | 21958954.68 | 25542892.78 | 11047065.60 |
Maximum of Months | 0.131665E+09 | 60951800.67 | 74198901.55 | 0.187988E+09 | 0.103330E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.800952E+09 | 0.00 | 0.800952E+09 | 61082339.12 | 0.427975E+10 |
February | 0.989997E+09 | 0.00 | 0.989997E+09 | 0.104889E+09 | 0.402716E+10 |
March | 0.151997E+10 | 0.00 | 0.151997E+10 | 0.588268E+09 | 0.297944E+10 |
April | 0.176680E+10 | 5025323.02 | 0.176177E+10 | 0.115610E+10 | 0.207224E+10 |
May | 0.242211E+10 | 80706178.30 | 0.234141E+10 | 0.231475E+10 | 0.133328E+10 |
June | 0.248576E+10 | 0.133570E+09 | 0.235219E+10 | 0.311118E+10 | 0.709182E+09 |
July | 0.248232E+10 | 89769122.78 | 0.239255E+10 | 0.356531E+10 | 0.406949E+09 |
August | 0.219922E+10 | 26173819.73 | 0.217305E+10 | 0.311838E+10 | 0.556340E+09 |
September | 0.160437E+10 | 300432.95 | 0.160407E+10 | 0.173790E+10 | 0.108691E+10 |
October | 0.143475E+10 | 0.00 | 0.143475E+10 | 0.107126E+10 | 0.207180E+10 |
November | 0.973875E+09 | 0.00 | 0.973875E+09 | 0.287155E+09 | 0.298262E+10 |
December | 0.698643E+09 | 0.00 | 0.698643E+09 | 37261507.10 | 0.401452E+10 |
Annual Sum or Average | 0.193788E+11 | 0.335545E+09 | 0.190432E+11 | 0.171535E+11 | 0.265202E+11 |
Minimum of Months | 0.698643E+09 | 0.00 | 0.698643E+09 | 37261507.10 | 0.406949E+09 |
Maximum of Months | 0.248576E+10 | 0.133570E+09 | 0.239255E+10 | 0.356531E+10 | 0.427975E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111539E+10 | 0.447180E+09 | 0.668210E+09 | 0.709176E+09 | 0.265767E+10 |
February | 0.156234E+10 | 0.728829E+09 | 0.833507E+09 | 0.112062E+10 | 0.242376E+10 |
March | 0.220660E+10 | 0.938479E+09 | 0.126812E+10 | 0.196971E+10 | 0.191558E+10 |
April | 0.256265E+10 | 0.112252E+10 | 0.144013E+10 | 0.263744E+10 | 0.133700E+10 |
May | 0.321155E+10 | 0.128353E+10 | 0.192803E+10 | 0.376162E+10 | 0.900835E+09 |
June | 0.288042E+10 | 0.104269E+10 | 0.183773E+10 | 0.379124E+10 | 0.480491E+09 |
July | 0.298946E+10 | 0.107882E+10 | 0.191064E+10 | 0.426152E+10 | 0.273678E+09 |
August | 0.336621E+10 | 0.151782E+10 | 0.184839E+10 | 0.477091E+10 | 0.371917E+09 |
September | 0.242955E+10 | 0.109004E+10 | 0.133951E+10 | 0.305557E+10 | 0.699566E+09 |
October | 0.227598E+10 | 0.103155E+10 | 0.124443E+10 | 0.254620E+10 | 0.133364E+10 |
November | 0.136212E+10 | 0.523065E+09 | 0.839051E+09 | 0.111555E+10 | 0.186863E+10 |
December | 0.109654E+10 | 0.514866E+09 | 0.581672E+09 | 0.755928E+09 | 0.247101E+10 |
Annual Sum or Average | 0.270588E+11 | 0.113194E+11 | 0.157394E+11 | 0.304955E+11 | 0.167338E+11 |
Minimum of Months | 0.109654E+10 | 0.447180E+09 | 0.581672E+09 | 0.709176E+09 | 0.273678E+09 |
Maximum of Months | 0.336621E+10 | 0.151782E+10 | 0.192803E+10 | 0.477091E+10 | 0.265767E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.414343E+10 | 0.271314E+10 | 0.143029E+10 | 0.414112E+10 | 0.385378E+10 |
February | 0.493617E+10 | 0.326734E+10 | 0.166883E+10 | 0.500547E+10 | 0.354667E+10 |
March | 0.493050E+10 | 0.273651E+10 | 0.219399E+10 | 0.529875E+10 | 0.292225E+10 |
April | 0.370248E+10 | 0.146407E+10 | 0.223842E+10 | 0.411040E+10 | 0.214254E+10 |
May | 0.335284E+10 | 0.699346E+09 | 0.265349E+10 | 0.394782E+10 | 0.143462E+10 |
June | 0.304504E+10 | 0.465464E+09 | 0.257958E+10 | 0.413688E+10 | 0.759516E+09 |
July | 0.329820E+10 | 0.572895E+09 | 0.272531E+10 | 0.496596E+10 | 0.418879E+09 |
August | 0.440438E+10 | 0.163365E+10 | 0.277073E+10 | 0.667636E+10 | 0.590777E+09 |
September | 0.462468E+10 | 0.239207E+10 | 0.223261E+10 | 0.621366E+10 | 0.111725E+10 |
October | 0.654660E+10 | 0.410518E+10 | 0.244142E+10 | 0.819481E+10 | 0.207964E+10 |
November | 0.439307E+10 | 0.263825E+10 | 0.175482E+10 | 0.472799E+10 | 0.281718E+10 |
December | 0.449086E+10 | 0.318821E+10 | 0.130265E+10 | 0.465748E+10 | 0.358190E+10 |
Annual Sum or Average | 0.518683E+11 | 0.258761E+11 | 0.259921E+11 | 0.620767E+11 | 0.252650E+11 |
Minimum of Months | 0.304504E+10 | 0.465464E+09 | 0.130265E+10 | 0.394782E+10 | 0.418879E+09 |
Maximum of Months | 0.654660E+10 | 0.410518E+10 | 0.277073E+10 | 0.819481E+10 | 0.385378E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110114E+10 | 0.451030E+09 | 0.650111E+09 | 0.704899E+09 | 0.271795E+10 |
February | 0.146665E+10 | 0.644157E+09 | 0.822493E+09 | 0.103712E+10 | 0.253337E+10 |
March | 0.239773E+10 | 0.110696E+10 | 0.129076E+10 | 0.221378E+10 | 0.191929E+10 |
April | 0.253607E+10 | 0.108512E+10 | 0.145095E+10 | 0.264287E+10 | 0.138579E+10 |
May | 0.305274E+10 | 0.115931E+10 | 0.189343E+10 | 0.359269E+10 | 0.940990E+09 |
June | 0.323335E+10 | 0.130410E+10 | 0.192925E+10 | 0.428776E+10 | 0.512839E+09 |
July | 0.312915E+10 | 0.117834E+10 | 0.195081E+10 | 0.445635E+10 | 0.293834E+09 |
August | 0.346169E+10 | 0.160253E+10 | 0.185916E+10 | 0.493015E+10 | 0.402704E+09 |
September | 0.237825E+10 | 0.103929E+10 | 0.133896E+10 | 0.302594E+10 | 0.737608E+09 |
October | 0.243645E+10 | 0.118478E+10 | 0.125167E+10 | 0.278182E+10 | 0.138288E+10 |
November | 0.110724E+10 | 0.320000E+09 | 0.787241E+09 | 0.775934E+09 | 0.192400E+10 |
December | 0.101770E+10 | 0.440359E+09 | 0.577337E+09 | 0.665629E+09 | 0.254643E+10 |
Annual Sum or Average | 0.273181E+11 | 0.115160E+11 | 0.158022E+11 | 0.311149E+11 | 0.172977E+11 |
Minimum of Months | 0.101770E+10 | 0.320000E+09 | 0.577337E+09 | 0.665629E+09 | 0.293834E+09 |
Maximum of Months | 0.346169E+10 | 0.160253E+10 | 0.195081E+10 | 0.493015E+10 | 0.271795E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 26.01 | 1525.58 | 299.04 | 0.00 | 299.04 | 0.00 | 0.00 |
February | 48.08 | 1580.94 | 409.23 | 0.00 | 409.23 | 0.00 | 0.00 |
March | 230.13 | 1043.50 | 567.49 | 0.00 | 567.49 | 0.00 | 0.00 |
April | 459.95 | 746.19 | 681.64 | 1.94 | 679.70 | 0.00 | 0.00 |
May | 872.94 | 473.71 | 904.31 | 30.13 | 874.18 | 0.00 | 0.00 |
June | 1197.25 | 264.83 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
July | 1323.13 | 148.98 | 926.79 | 33.52 | 893.28 | 0.00 | 0.00 |
August | 1160.08 | 201.17 | 821.09 | 9.77 | 811.32 | 0.00 | 0.00 |
September | 675.50 | 394.32 | 618.97 | 0.12 | 618.85 | 0.00 | 0.00 |
October | 417.92 | 714.64 | 535.67 | 0.00 | 535.67 | 0.00 | 0.00 |
November | 126.45 | 1059.32 | 375.72 | 0.00 | 375.72 | 0.00 | 0.00 |
December | 17.91 | 1403.44 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Annual Sum or Average | 549.62 | 791.91 | 614.50 | 10.64 | 603.86 | 0.00 | 0.00 |
Minimum of Months | 17.91 | 148.98 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Maximum of Months | 1323.13 | 1580.94 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 270.06 | 946.64 | 416.44 | 166.96 | 249.48 | 0.00 | 0.00 |
February | 472.60 | 951.02 | 645.81 | 301.27 | 344.54 | 0.00 | 0.00 |
March | 744.11 | 672.81 | 823.85 | 350.39 | 473.46 | 0.00 | 0.00 |
April | 1026.19 | 485.26 | 988.68 | 433.07 | 555.61 | 0.00 | 0.00 |
May | 1407.69 | 321.48 | 1199.06 | 479.21 | 719.84 | 0.00 | 0.00 |
June | 1459.80 | 179.73 | 1111.27 | 402.27 | 709.00 | 0.00 | 0.00 |
July | 1585.23 | 100.13 | 1116.14 | 402.78 | 713.35 | 0.00 | 0.00 |
August | 1776.96 | 134.85 | 1256.80 | 566.69 | 690.11 | 0.00 | 0.00 |
September | 1180.98 | 255.41 | 937.33 | 420.54 | 516.79 | 0.00 | 0.00 |
October | 960.89 | 463.83 | 849.76 | 385.14 | 464.62 | 0.00 | 0.00 |
November | 444.85 | 667.10 | 525.51 | 201.80 | 323.71 | 0.00 | 0.00 |
December | 290.80 | 864.15 | 409.40 | 192.23 | 217.17 | 0.00 | 0.00 |
Annual Sum or Average | 971.77 | 501.02 | 858.03 | 358.94 | 499.09 | 0.00 | 0.00 |
Minimum of Months | 270.06 | 100.13 | 409.40 | 166.96 | 217.17 | 0.00 | 0.00 |
Maximum of Months | 1776.96 | 951.02 | 1256.80 | 566.69 | 719.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1556.68 | 1368.01 | 1546.98 | 1012.97 | 534.01 | 0.00 | 0.00 |
February | 2085.79 | 1387.49 | 2040.41 | 1350.59 | 689.83 | 0.00 | 0.00 |
March | 1989.94 | 1023.50 | 1840.84 | 1021.70 | 819.14 | 0.00 | 0.00 |
April | 1597.44 | 773.68 | 1428.43 | 564.84 | 863.59 | 0.00 | 0.00 |
May | 1479.74 | 508.34 | 1251.81 | 261.11 | 990.70 | 0.00 | 0.00 |
June | 1592.11 | 282.58 | 1174.78 | 179.58 | 995.21 | 0.00 | 0.00 |
July | 1846.06 | 152.62 | 1231.41 | 213.89 | 1017.51 | 0.00 | 0.00 |
August | 2486.14 | 213.49 | 1644.41 | 609.94 | 1034.47 | 0.00 | 0.00 |
September | 2399.15 | 407.34 | 1784.21 | 922.87 | 861.35 | 0.00 | 0.00 |
October | 3070.46 | 724.74 | 2444.22 | 1532.70 | 911.52 | 0.00 | 0.00 |
November | 1846.96 | 1004.57 | 1694.86 | 1017.84 | 677.02 | 0.00 | 0.00 |
December | 1757.64 | 1250.21 | 1676.69 | 1190.34 | 486.35 | 0.00 | 0.00 |
Annual Sum or Average | 1976.05 | 754.42 | 1644.73 | 820.53 | 824.21 | 0.00 | 0.00 |
Minimum of Months | 1479.74 | 152.62 | 1174.78 | 179.58 | 486.35 | 0.00 | 0.00 |
Maximum of Months | 3070.46 | 1387.49 | 2444.22 | 1532.70 | 1034.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 266.66 | 967.99 | 411.12 | 168.40 | 242.72 | 0.00 | 0.00 |
February | 434.10 | 993.85 | 606.25 | 266.27 | 339.99 | 0.00 | 0.00 |
March | 833.78 | 672.81 | 895.21 | 413.29 | 481.92 | 0.00 | 0.00 |
April | 1027.96 | 500.43 | 978.42 | 418.64 | 559.78 | 0.00 | 0.00 |
May | 1346.16 | 333.70 | 1139.76 | 432.84 | 706.93 | 0.00 | 0.00 |
June | 1651.45 | 190.90 | 1247.44 | 503.13 | 744.31 | 0.00 | 0.00 |
July | 1658.32 | 106.98 | 1168.29 | 439.94 | 728.35 | 0.00 | 0.00 |
August | 1836.88 | 145.77 | 1292.45 | 598.32 | 694.13 | 0.00 | 0.00 |
September | 1170.81 | 267.99 | 917.53 | 400.96 | 516.57 | 0.00 | 0.00 |
October | 1049.73 | 478.99 | 909.67 | 442.35 | 467.32 | 0.00 | 0.00 |
November | 311.27 | 685.00 | 427.18 | 123.46 | 303.72 | 0.00 | 0.00 |
December | 254.18 | 889.64 | 379.96 | 164.41 | 215.55 | 0.00 | 0.00 |
Annual Sum or Average | 990.73 | 516.79 | 866.25 | 365.17 | 501.08 | 0.00 | 0.00 |
Minimum of Months | 254.18 | 106.98 | 379.96 | 123.46 | 215.55 | 0.00 | 0.00 |
Maximum of Months | 1836.88 | 993.85 | 1292.45 | 598.32 | 744.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 24.30 | 1590.26 | 299.04 | 0.00 | 299.04 | 0.00 | 0.00 |
February | 47.64 | 1638.85 | 409.22 | 0.00 | 409.22 | 0.00 | 0.00 |
March | 239.72 | 1070.77 | 567.49 | 0.00 | 567.49 | 0.00 | 0.00 |
April | 479.37 | 754.28 | 681.63 | 1.94 | 679.69 | 0.00 | 0.00 |
May | 909.83 | 460.40 | 904.31 | 30.13 | 874.18 | 0.00 | 0.00 |
June | 1225.51 | 254.25 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
July | 1349.79 | 139.20 | 926.79 | 33.52 | 893.27 | 0.00 | 0.00 |
August | 1173.86 | 199.84 | 821.09 | 9.77 | 811.32 | 0.00 | 0.00 |
September | 674.38 | 420.21 | 618.97 | 0.12 | 618.85 | 0.00 | 0.00 |
October | 399.83 | 787.41 | 535.67 | 0.00 | 535.67 | 0.00 | 0.00 |
November | 108.58 | 1182.60 | 375.72 | 0.00 | 375.72 | 0.00 | 0.00 |
December | 13.90 | 1515.58 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Annual Sum or Average | 557.31 | 829.85 | 614.49 | 10.64 | 603.85 | 0.00 | 0.00 |
Minimum of Months | 13.90 | 139.20 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Maximum of Months | 1349.79 | 1638.85 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 269.06 | 993.40 | 416.44 | 166.96 | 249.48 | 0.00 | 0.00 |
February | 471.83 | 997.15 | 645.80 | 301.27 | 344.54 | 0.00 | 0.00 |
March | 751.84 | 702.50 | 823.84 | 350.38 | 473.46 | 0.00 | 0.00 |
April | 1036.25 | 504.98 | 988.67 | 433.07 | 555.60 | 0.00 | 0.00 |
May | 1426.95 | 324.25 | 1199.05 | 479.21 | 719.84 | 0.00 | 0.00 |
June | 1476.66 | 179.45 | 1111.26 | 402.27 | 709.00 | 0.00 | 0.00 |
July | 1600.48 | 100.08 | 1116.13 | 402.78 | 713.35 | 0.00 | 0.00 |
August | 1786.41 | 142.08 | 1256.79 | 566.68 | 690.11 | 0.00 | 0.00 |
September | 1180.68 | 281.18 | 937.32 | 420.54 | 516.78 | 0.00 | 0.00 |
October | 949.03 | 523.41 | 849.75 | 385.13 | 464.62 | 0.00 | 0.00 |
November | 426.14 | 754.16 | 525.50 | 201.80 | 323.71 | 0.00 | 0.00 |
December | 283.06 | 941.43 | 409.40 | 192.23 | 217.17 | 0.00 | 0.00 |
Annual Sum or Average | 975.00 | 534.40 | 858.02 | 358.93 | 499.09 | 0.00 | 0.00 |
Minimum of Months | 269.06 | 100.08 | 409.40 | 166.96 | 217.17 | 0.00 | 0.00 |
Maximum of Months | 1786.41 | 997.15 | 1256.79 | 566.68 | 719.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1589.09 | 1424.32 | 1547.00 | 1012.98 | 534.01 | 0.00 | 0.00 |
February | 2124.81 | 1452.72 | 2040.43 | 1350.60 | 689.83 | 0.00 | 0.00 |
March | 2035.06 | 1059.42 | 1840.86 | 1021.71 | 819.15 | 0.00 | 0.00 |
April | 1635.03 | 785.18 | 1428.44 | 564.85 | 863.59 | 0.00 | 0.00 |
May | 1530.18 | 493.28 | 1251.82 | 261.11 | 990.71 | 0.00 | 0.00 |
June | 1625.18 | 274.11 | 1174.79 | 179.58 | 995.21 | 0.00 | 0.00 |
July | 1870.42 | 148.39 | 1231.42 | 213.90 | 1017.52 | 0.00 | 0.00 |
August | 2500.08 | 225.01 | 1644.42 | 609.94 | 1034.48 | 0.00 | 0.00 |
September | 2405.92 | 448.85 | 1784.23 | 922.88 | 861.35 | 0.00 | 0.00 |
October | 3071.53 | 822.95 | 2444.25 | 1532.72 | 911.53 | 0.00 | 0.00 |
November | 1847.75 | 1120.36 | 1694.88 | 1017.85 | 677.02 | 0.00 | 0.00 |
December | 1769.46 | 1354.44 | 1676.71 | 1190.35 | 486.36 | 0.00 | 0.00 |
Annual Sum or Average | 2000.69 | 796.97 | 1644.75 | 820.54 | 824.21 | 0.00 | 0.00 |
Minimum of Months | 1530.18 | 148.39 | 1174.79 | 179.58 | 486.36 | 0.00 | 0.00 |
Maximum of Months | 3071.53 | 1452.72 | 2444.25 | 1532.72 | 1034.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 268.43 | 1014.30 | 411.12 | 168.39 | 242.72 | 0.00 | 0.00 |
February | 439.09 | 1040.47 | 606.25 | 266.27 | 339.98 | 0.00 | 0.00 |
March | 843.66 | 705.54 | 895.20 | 413.29 | 481.91 | 0.00 | 0.00 |
April | 1038.57 | 522.22 | 978.41 | 418.64 | 559.78 | 0.00 | 0.00 |
May | 1363.20 | 337.79 | 1139.75 | 432.83 | 706.92 | 0.00 | 0.00 |
June | 1667.39 | 193.58 | 1247.43 | 503.12 | 744.31 | 0.00 | 0.00 |
July | 1673.02 | 108.44 | 1168.28 | 439.94 | 728.34 | 0.00 | 0.00 |
August | 1845.31 | 154.34 | 1292.44 | 598.31 | 694.13 | 0.00 | 0.00 |
September | 1168.35 | 294.82 | 917.53 | 400.96 | 516.57 | 0.00 | 0.00 |
October | 1035.96 | 542.50 | 909.66 | 442.34 | 467.32 | 0.00 | 0.00 |
November | 297.46 | 769.45 | 427.17 | 123.46 | 303.72 | 0.00 | 0.00 |
December | 250.73 | 967.20 | 379.96 | 164.41 | 215.55 | 0.00 | 0.00 |
Annual Sum or Average | 994.90 | 551.42 | 866.25 | 365.17 | 501.08 | 0.00 | 0.00 |
Minimum of Months | 250.73 | 108.44 | 379.96 | 123.46 | 215.55 | 0.00 | 0.00 |
Maximum of Months | 1845.31 | 1040.47 | 1292.44 | 598.31 | 744.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.81 | 1597.88 | 299.04 | 0.00 | 299.04 | 0.00 | 0.00 |
February | 43.36 | 1664.67 | 409.23 | 0.00 | 409.23 | 0.00 | 0.00 |
March | 219.63 | 1112.40 | 567.49 | 0.00 | 567.49 | 0.00 | 0.00 |
April | 446.03 | 799.48 | 681.64 | 1.94 | 679.70 | 0.00 | 0.00 |
May | 864.23 | 497.79 | 904.31 | 30.13 | 874.18 | 0.00 | 0.00 |
June | 1200.30 | 273.60 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
July | 1331.13 | 151.94 | 926.79 | 33.52 | 893.28 | 0.00 | 0.00 |
August | 1164.27 | 207.71 | 821.09 | 9.77 | 811.32 | 0.00 | 0.00 |
September | 670.48 | 419.33 | 618.97 | 0.12 | 618.85 | 0.00 | 0.00 |
October | 399.96 | 773.52 | 535.67 | 0.00 | 535.67 | 0.00 | 0.00 |
November | 110.79 | 1150.70 | 375.72 | 0.00 | 375.72 | 0.00 | 0.00 |
December | 13.91 | 1498.85 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Annual Sum or Average | 543.93 | 840.95 | 614.50 | 10.64 | 603.86 | 0.00 | 0.00 |
Minimum of Months | 13.91 | 151.94 | 260.84 | 0.00 | 260.84 | 0.00 | 0.00 |
Maximum of Months | 1331.13 | 1664.67 | 959.01 | 51.53 | 907.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 264.78 | 992.26 | 416.44 | 166.96 | 249.48 | 0.00 | 0.00 |
February | 463.22 | 1001.89 | 645.81 | 301.27 | 344.54 | 0.00 | 0.00 |
March | 735.41 | 715.20 | 823.85 | 350.39 | 473.46 | 0.00 | 0.00 |
April | 1017.53 | 515.82 | 988.68 | 433.07 | 555.61 | 0.00 | 0.00 |
May | 1404.43 | 336.33 | 1199.06 | 479.21 | 719.84 | 0.00 | 0.00 |
June | 1462.67 | 185.37 | 1111.27 | 402.27 | 709.00 | 0.00 | 0.00 |
July | 1591.07 | 102.18 | 1116.14 | 402.78 | 713.35 | 0.00 | 0.00 |
August | 1781.25 | 138.86 | 1256.80 | 566.69 | 690.11 | 0.00 | 0.00 |
September | 1178.84 | 269.89 | 937.33 | 420.54 | 516.79 | 0.00 | 0.00 |
October | 950.64 | 497.93 | 849.76 | 385.14 | 464.62 | 0.00 | 0.00 |
November | 430.38 | 720.92 | 525.51 | 201.80 | 323.71 | 0.00 | 0.00 |
December | 282.23 | 922.57 | 409.40 | 192.23 | 217.17 | 0.00 | 0.00 |
Annual Sum or Average | 967.01 | 530.62 | 858.03 | 358.94 | 499.09 | 0.00 | 0.00 |
Minimum of Months | 264.78 | 102.18 | 409.40 | 166.96 | 217.17 | 0.00 | 0.00 |
Maximum of Months | 1781.25 | 1001.89 | 1256.80 | 566.69 | 719.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1546.12 | 1438.84 | 1546.98 | 1012.97 | 534.01 | 0.00 | 0.00 |
February | 2069.06 | 1466.05 | 2040.41 | 1350.59 | 689.83 | 0.00 | 0.00 |
March | 1978.32 | 1091.04 | 1840.84 | 1021.70 | 819.14 | 0.00 | 0.00 |
April | 1585.80 | 826.60 | 1428.43 | 564.84 | 863.59 | 0.00 | 0.00 |
May | 1473.95 | 535.63 | 1251.81 | 261.11 | 990.70 | 0.00 | 0.00 |
June | 1596.02 | 293.02 | 1174.78 | 179.58 | 995.21 | 0.00 | 0.00 |
July | 1854.08 | 156.39 | 1231.41 | 213.89 | 1017.51 | 0.00 | 0.00 |
August | 2492.67 | 220.57 | 1644.41 | 609.94 | 1034.47 | 0.00 | 0.00 |
September | 2397.24 | 431.04 | 1784.21 | 922.87 | 861.35 | 0.00 | 0.00 |
October | 3059.59 | 776.45 | 2444.22 | 1532.70 | 911.52 | 0.00 | 0.00 |
November | 1824.07 | 1086.87 | 1694.86 | 1017.84 | 677.02 | 0.00 | 0.00 |
December | 1738.90 | 1337.33 | 1676.69 | 1190.34 | 486.35 | 0.00 | 0.00 |
Annual Sum or Average | 1968.44 | 801.15 | 1644.73 | 820.53 | 824.21 | 0.00 | 0.00 |
Minimum of Months | 1473.95 | 156.39 | 1174.78 | 179.58 | 486.35 | 0.00 | 0.00 |
Maximum of Months | 3059.59 | 1466.05 | 2444.22 | 1532.70 | 1034.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 263.18 | 1014.77 | 411.12 | 168.40 | 242.72 | 0.00 | 0.00 |
February | 428.70 | 1047.19 | 606.25 | 266.27 | 339.99 | 0.00 | 0.00 |
March | 826.53 | 716.58 | 895.21 | 413.29 | 481.92 | 0.00 | 0.00 |
April | 1019.63 | 534.64 | 978.42 | 418.64 | 559.78 | 0.00 | 0.00 |
May | 1341.36 | 351.33 | 1139.76 | 432.84 | 706.93 | 0.00 | 0.00 |
June | 1654.23 | 197.85 | 1247.44 | 503.13 | 744.31 | 0.00 | 0.00 |
July | 1663.81 | 109.71 | 1168.29 | 439.94 | 728.35 | 0.00 | 0.00 |
August | 1840.71 | 150.35 | 1292.45 | 598.32 | 694.13 | 0.00 | 0.00 |
September | 1167.41 | 284.57 | 917.53 | 400.96 | 516.57 | 0.00 | 0.00 |
October | 1038.61 | 516.31 | 909.67 | 442.35 | 467.32 | 0.00 | 0.00 |
November | 299.36 | 742.28 | 427.18 | 123.46 | 303.72 | 0.00 | 0.00 |
December | 248.52 | 950.73 | 379.96 | 164.41 | 215.55 | 0.00 | 0.00 |
Annual Sum or Average | 986.65 | 548.51 | 866.25 | 365.17 | 501.08 | 0.00 | 0.00 |
Minimum of Months | 248.52 | 109.71 | 379.96 | 123.46 | 215.55 | 0.00 | 0.00 |
Maximum of Months | 1840.71 | 1047.19 | 1292.45 | 598.32 | 744.31 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 69661842.76 | 0.408610E+10 | 0.800952E+09 | 0.00 | 0.800952E+09 | 0.00 | 0.00 |
February | 0.116316E+09 | 0.382461E+10 | 0.989997E+09 | 0.00 | 0.989997E+09 | 0.00 | 0.00 |
March | 0.616379E+09 | 0.279491E+10 | 0.151997E+10 | 0.00 | 0.151997E+10 | 0.00 | 0.00 |
April | 0.119219E+10 | 0.193411E+10 | 0.176680E+10 | 5025323.02 | 0.176177E+10 | 0.00 | 0.00 |
May | 0.233808E+10 | 0.126878E+10 | 0.242211E+10 | 80706178.30 | 0.234141E+10 | 0.00 | 0.00 |
June | 0.310326E+10 | 0.686431E+09 | 0.248576E+10 | 0.133570E+09 | 0.235219E+10 | 0.00 | 0.00 |
July | 0.354387E+10 | 0.399025E+09 | 0.248232E+10 | 89769122.78 | 0.239255E+10 | 0.00 | 0.00 |
August | 0.310716E+10 | 0.538801E+09 | 0.219922E+10 | 26173819.73 | 0.217305E+10 | 0.00 | 0.00 |
September | 0.175089E+10 | 0.102209E+10 | 0.160437E+10 | 300432.95 | 0.160407E+10 | 0.00 | 0.00 |
October | 0.111934E+10 | 0.191409E+10 | 0.143475E+10 | 0.00 | 0.143475E+10 | 0.00 | 0.00 |
November | 0.327760E+09 | 0.274576E+10 | 0.973875E+09 | 0.00 | 0.973875E+09 | 0.00 | 0.00 |
December | 47971650.87 | 0.375898E+10 | 0.698643E+09 | 0.00 | 0.698643E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.173329E+11 | 0.249737E+11 | 0.193788E+11 | 0.335545E+09 | 0.190432E+11 | 0.00 | 0.00 |
Minimum of Months | 47971650.87 | 0.399025E+09 | 0.698643E+09 | 0.00 | 0.698643E+09 | 0.00 | 0.00 |
Maximum of Months | 0.354387E+10 | 0.408610E+10 | 0.248576E+10 | 0.133570E+09 | 0.239255E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.723319E+09 | 0.253549E+10 | 0.111539E+10 | 0.447180E+09 | 0.668210E+09 | 0.00 | 0.00 |
February | 0.114332E+10 | 0.230072E+10 | 0.156234E+10 | 0.728829E+09 | 0.833507E+09 | 0.00 | 0.00 |
March | 0.199302E+10 | 0.180204E+10 | 0.220660E+10 | 0.938479E+09 | 0.126812E+10 | 0.00 | 0.00 |
April | 0.265987E+10 | 0.125779E+10 | 0.256265E+10 | 0.112252E+10 | 0.144013E+10 | 0.00 | 0.00 |
May | 0.377035E+10 | 0.861046E+09 | 0.321155E+10 | 0.128353E+10 | 0.192803E+10 | 0.00 | 0.00 |
June | 0.378381E+10 | 0.465848E+09 | 0.288042E+10 | 0.104269E+10 | 0.183773E+10 | 0.00 | 0.00 |
July | 0.424587E+10 | 0.268184E+09 | 0.298946E+10 | 0.107882E+10 | 0.191064E+10 | 0.00 | 0.00 |
August | 0.475941E+10 | 0.361172E+09 | 0.336621E+10 | 0.151782E+10 | 0.184839E+10 | 0.00 | 0.00 |
September | 0.306110E+10 | 0.662027E+09 | 0.242955E+10 | 0.109004E+10 | 0.133951E+10 | 0.00 | 0.00 |
October | 0.257364E+10 | 0.124232E+10 | 0.227598E+10 | 0.103155E+10 | 0.124443E+10 | 0.00 | 0.00 |
November | 0.115306E+10 | 0.172912E+10 | 0.136212E+10 | 0.523065E+09 | 0.839051E+09 | 0.00 | 0.00 |
December | 0.778879E+09 | 0.231454E+10 | 0.109654E+10 | 0.514866E+09 | 0.581672E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.306457E+11 | 0.158003E+11 | 0.270588E+11 | 0.113194E+11 | 0.157394E+11 | 0.00 | 0.00 |
Minimum of Months | 0.723319E+09 | 0.268184E+09 | 0.109654E+10 | 0.447180E+09 | 0.581672E+09 | 0.00 | 0.00 |
Maximum of Months | 0.475941E+10 | 0.253549E+10 | 0.336621E+10 | 0.151782E+10 | 0.192803E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.416941E+10 | 0.366407E+10 | 0.414343E+10 | 0.271314E+10 | 0.143029E+10 | 0.00 | 0.00 |
February | 0.504595E+10 | 0.335662E+10 | 0.493617E+10 | 0.326734E+10 | 0.166883E+10 | 0.00 | 0.00 |
March | 0.532985E+10 | 0.274134E+10 | 0.493050E+10 | 0.273651E+10 | 0.219399E+10 | 0.00 | 0.00 |
April | 0.414057E+10 | 0.200537E+10 | 0.370248E+10 | 0.146407E+10 | 0.223842E+10 | 0.00 | 0.00 |
May | 0.396334E+10 | 0.136153E+10 | 0.335284E+10 | 0.699346E+09 | 0.265349E+10 | 0.00 | 0.00 |
June | 0.412675E+10 | 0.732439E+09 | 0.304504E+10 | 0.465464E+09 | 0.257958E+10 | 0.00 | 0.00 |
July | 0.494449E+10 | 0.408777E+09 | 0.329820E+10 | 0.572895E+09 | 0.272531E+10 | 0.00 | 0.00 |
August | 0.665888E+10 | 0.571810E+09 | 0.440438E+10 | 0.163365E+10 | 0.277073E+10 | 0.00 | 0.00 |
September | 0.621860E+10 | 0.105584E+10 | 0.462468E+10 | 0.239207E+10 | 0.223261E+10 | 0.00 | 0.00 |
October | 0.822393E+10 | 0.194114E+10 | 0.654660E+10 | 0.410518E+10 | 0.244142E+10 | 0.00 | 0.00 |
November | 0.478732E+10 | 0.260384E+10 | 0.439307E+10 | 0.263825E+10 | 0.175482E+10 | 0.00 | 0.00 |
December | 0.470767E+10 | 0.334857E+10 | 0.449086E+10 | 0.318821E+10 | 0.130265E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.623168E+11 | 0.237913E+11 | 0.518683E+11 | 0.258761E+11 | 0.259921E+11 | 0.00 | 0.00 |
Minimum of Months | 0.396334E+10 | 0.408777E+09 | 0.304504E+10 | 0.465464E+09 | 0.130265E+10 | 0.00 | 0.00 |
Maximum of Months | 0.822393E+10 | 0.366407E+10 | 0.654660E+10 | 0.410518E+10 | 0.277073E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.714229E+09 | 0.259266E+10 | 0.110114E+10 | 0.451030E+09 | 0.650111E+09 | 0.00 | 0.00 |
February | 0.105017E+10 | 0.240432E+10 | 0.146665E+10 | 0.644157E+09 | 0.822493E+09 | 0.00 | 0.00 |
March | 0.223321E+10 | 0.180204E+10 | 0.239773E+10 | 0.110696E+10 | 0.129076E+10 | 0.00 | 0.00 |
April | 0.266446E+10 | 0.129711E+10 | 0.253607E+10 | 0.108512E+10 | 0.145095E+10 | 0.00 | 0.00 |
May | 0.360555E+10 | 0.893770E+09 | 0.305274E+10 | 0.115931E+10 | 0.189343E+10 | 0.00 | 0.00 |
June | 0.428056E+10 | 0.494815E+09 | 0.323335E+10 | 0.130410E+10 | 0.192925E+10 | 0.00 | 0.00 |
July | 0.444165E+10 | 0.286544E+09 | 0.312915E+10 | 0.117834E+10 | 0.195081E+10 | 0.00 | 0.00 |
August | 0.491991E+10 | 0.390433E+09 | 0.346169E+10 | 0.160253E+10 | 0.185916E+10 | 0.00 | 0.00 |
September | 0.303473E+10 | 0.694621E+09 | 0.237825E+10 | 0.103929E+10 | 0.133896E+10 | 0.00 | 0.00 |
October | 0.281161E+10 | 0.128292E+10 | 0.243645E+10 | 0.118478E+10 | 0.125167E+10 | 0.00 | 0.00 |
November | 0.806813E+09 | 0.177553E+10 | 0.110724E+10 | 0.320000E+09 | 0.787241E+09 | 0.00 | 0.00 |
December | 0.680799E+09 | 0.238282E+10 | 0.101770E+10 | 0.440359E+09 | 0.577337E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.312437E+11 | 0.162976E+11 | 0.273181E+11 | 0.115160E+11 | 0.158022E+11 | 0.00 | 0.00 |
Minimum of Months | 0.680799E+09 | 0.286544E+09 | 0.101770E+10 | 0.320000E+09 | 0.577337E+09 | 0.00 | 0.00 |
Maximum of Months | 0.491991E+10 | 0.259266E+10 | 0.346169E+10 | 0.160253E+10 | 0.195081E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 65078970.90 | 0.425936E+10 | 0.800948E+09 | 0.00 | 0.800948E+09 | 0.00 | 0.00 |
February | 0.115262E+09 | 0.396470E+10 | 0.989992E+09 | 0.00 | 0.989992E+09 | 0.00 | 0.00 |
March | 0.642077E+09 | 0.286795E+10 | 0.151996E+10 | 0.00 | 0.151996E+10 | 0.00 | 0.00 |
April | 0.124252E+10 | 0.195510E+10 | 0.176679E+10 | 5025296.98 | 0.176176E+10 | 0.00 | 0.00 |
May | 0.243689E+10 | 0.123314E+10 | 0.242210E+10 | 80705760.09 | 0.234139E+10 | 0.00 | 0.00 |
June | 0.317653E+10 | 0.659018E+09 | 0.248575E+10 | 0.133570E+09 | 0.235218E+10 | 0.00 | 0.00 |
July | 0.361529E+10 | 0.372821E+09 | 0.248231E+10 | 89768657.61 | 0.239254E+10 | 0.00 | 0.00 |
August | 0.314406E+10 | 0.535263E+09 | 0.219921E+10 | 26173684.10 | 0.217304E+10 | 0.00 | 0.00 |
September | 0.174799E+10 | 0.108918E+10 | 0.160436E+10 | 300431.40 | 0.160406E+10 | 0.00 | 0.00 |
October | 0.107092E+10 | 0.210900E+10 | 0.143474E+10 | 0.00 | 0.143474E+10 | 0.00 | 0.00 |
November | 0.281443E+09 | 0.306530E+10 | 0.973870E+09 | 0.00 | 0.973870E+09 | 0.00 | 0.00 |
December | 37235261.28 | 0.405932E+10 | 0.698639E+09 | 0.00 | 0.698639E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.175753E+11 | 0.261702E+11 | 0.193787E+11 | 0.335544E+09 | 0.190431E+11 | 0.00 | 0.00 |
Minimum of Months | 37235261.28 | 0.372821E+09 | 0.698639E+09 | 0.00 | 0.698639E+09 | 0.00 | 0.00 |
Maximum of Months | 0.361529E+10 | 0.425936E+10 | 0.248575E+10 | 0.133570E+09 | 0.239254E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.720651E+09 | 0.266073E+10 | 0.111538E+10 | 0.447176E+09 | 0.668206E+09 | 0.00 | 0.00 |
February | 0.114146E+10 | 0.241229E+10 | 0.156232E+10 | 0.728822E+09 | 0.833502E+09 | 0.00 | 0.00 |
March | 0.201373E+10 | 0.188156E+10 | 0.220658E+10 | 0.938469E+09 | 0.126811E+10 | 0.00 | 0.00 |
April | 0.268597E+10 | 0.130892E+10 | 0.256263E+10 | 0.112250E+10 | 0.144012E+10 | 0.00 | 0.00 |
May | 0.382195E+10 | 0.868461E+09 | 0.321153E+10 | 0.128351E+10 | 0.192802E+10 | 0.00 | 0.00 |
June | 0.382751E+10 | 0.465132E+09 | 0.288040E+10 | 0.104268E+10 | 0.183772E+10 | 0.00 | 0.00 |
July | 0.428673E+10 | 0.268054E+09 | 0.298944E+10 | 0.107881E+10 | 0.191063E+10 | 0.00 | 0.00 |
August | 0.478472E+10 | 0.380560E+09 | 0.336618E+10 | 0.151780E+10 | 0.184838E+10 | 0.00 | 0.00 |
September | 0.306033E+10 | 0.728809E+09 | 0.242953E+10 | 0.109003E+10 | 0.133950E+10 | 0.00 | 0.00 |
October | 0.254188E+10 | 0.140191E+10 | 0.227597E+10 | 0.103154E+10 | 0.124443E+10 | 0.00 | 0.00 |
November | 0.110454E+10 | 0.195479E+10 | 0.136211E+10 | 0.523060E+09 | 0.839045E+09 | 0.00 | 0.00 |
December | 0.758148E+09 | 0.252154E+10 | 0.109653E+10 | 0.514861E+09 | 0.581668E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.307476E+11 | 0.168528E+11 | 0.270586E+11 | 0.113193E+11 | 0.157393E+11 | 0.00 | 0.00 |
Minimum of Months | 0.720651E+09 | 0.268054E+09 | 0.109653E+10 | 0.447176E+09 | 0.581668E+09 | 0.00 | 0.00 |
Maximum of Months | 0.478472E+10 | 0.266073E+10 | 0.336618E+10 | 0.151780E+10 | 0.192802E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.425623E+10 | 0.381491E+10 | 0.414347E+10 | 0.271317E+10 | 0.143030E+10 | 0.00 | 0.00 |
February | 0.514034E+10 | 0.351442E+10 | 0.493622E+10 | 0.326738E+10 | 0.166884E+10 | 0.00 | 0.00 |
March | 0.545071E+10 | 0.283756E+10 | 0.493055E+10 | 0.273654E+10 | 0.219401E+10 | 0.00 | 0.00 |
April | 0.423799E+10 | 0.203518E+10 | 0.370252E+10 | 0.146409E+10 | 0.223843E+10 | 0.00 | 0.00 |
May | 0.409844E+10 | 0.132119E+10 | 0.335286E+10 | 0.699355E+09 | 0.265351E+10 | 0.00 | 0.00 |
June | 0.421246E+10 | 0.710486E+09 | 0.304506E+10 | 0.465469E+09 | 0.257959E+10 | 0.00 | 0.00 |
July | 0.500973E+10 | 0.397457E+09 | 0.329823E+10 | 0.572901E+09 | 0.272533E+10 | 0.00 | 0.00 |
August | 0.669621E+10 | 0.602661E+09 | 0.440442E+10 | 0.163367E+10 | 0.277075E+10 | 0.00 | 0.00 |
September | 0.623613E+10 | 0.116342E+10 | 0.462473E+10 | 0.239210E+10 | 0.223263E+10 | 0.00 | 0.00 |
October | 0.822680E+10 | 0.220419E+10 | 0.654667E+10 | 0.410523E+10 | 0.244144E+10 | 0.00 | 0.00 |
November | 0.478936E+10 | 0.290396E+10 | 0.439312E+10 | 0.263828E+10 | 0.175484E+10 | 0.00 | 0.00 |
December | 0.473933E+10 | 0.362774E+10 | 0.449091E+10 | 0.318824E+10 | 0.130266E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.630937E+11 | 0.251332E+11 | 0.518688E+11 | 0.258764E+11 | 0.259923E+11 | 0.00 | 0.00 |
Minimum of Months | 0.409844E+10 | 0.397457E+09 | 0.304506E+10 | 0.465469E+09 | 0.130266E+10 | 0.00 | 0.00 |
Maximum of Months | 0.822680E+10 | 0.381491E+10 | 0.654667E+10 | 0.410523E+10 | 0.277075E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.718964E+09 | 0.271669E+10 | 0.110113E+10 | 0.451026E+09 | 0.650107E+09 | 0.00 | 0.00 |
February | 0.106226E+10 | 0.251710E+10 | 0.146664E+10 | 0.644151E+09 | 0.822488E+09 | 0.00 | 0.00 |
March | 0.225965E+10 | 0.188972E+10 | 0.239771E+10 | 0.110695E+10 | 0.129076E+10 | 0.00 | 0.00 |
April | 0.269198E+10 | 0.135358E+10 | 0.253605E+10 | 0.108511E+10 | 0.145094E+10 | 0.00 | 0.00 |
May | 0.365120E+10 | 0.904736E+09 | 0.305272E+10 | 0.115930E+10 | 0.189342E+10 | 0.00 | 0.00 |
June | 0.432187E+10 | 0.501769E+09 | 0.323333E+10 | 0.130409E+10 | 0.192924E+10 | 0.00 | 0.00 |
July | 0.448101E+10 | 0.290443E+09 | 0.312913E+10 | 0.117833E+10 | 0.195080E+10 | 0.00 | 0.00 |
August | 0.494249E+10 | 0.413387E+09 | 0.346166E+10 | 0.160251E+10 | 0.185915E+10 | 0.00 | 0.00 |
September | 0.302837E+10 | 0.764166E+09 | 0.237823E+10 | 0.103928E+10 | 0.133895E+10 | 0.00 | 0.00 |
October | 0.277473E+10 | 0.145304E+10 | 0.243643E+10 | 0.118477E+10 | 0.125166E+10 | 0.00 | 0.00 |
November | 0.771027E+09 | 0.199442E+10 | 0.110723E+10 | 0.319996E+09 | 0.787236E+09 | 0.00 | 0.00 |
December | 0.671562E+09 | 0.259056E+10 | 0.101769E+10 | 0.440355E+09 | 0.577333E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.313751E+11 | 0.173896E+11 | 0.273179E+11 | 0.115159E+11 | 0.158021E+11 | 0.00 | 0.00 |
Minimum of Months | 0.671562E+09 | 0.290443E+09 | 0.101769E+10 | 0.319996E+09 | 0.577333E+09 | 0.00 | 0.00 |
Maximum of Months | 0.494249E+10 | 0.271669E+10 | 0.346166E+10 | 0.160251E+10 | 0.195080E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 61082339.12 | 0.427975E+10 | 0.800952E+09 | 0.00 | 0.800952E+09 | 0.00 | 0.00 |
February | 0.104889E+09 | 0.402716E+10 | 0.989997E+09 | 0.00 | 0.989997E+09 | 0.00 | 0.00 |
March | 0.588268E+09 | 0.297944E+10 | 0.151997E+10 | 0.00 | 0.151997E+10 | 0.00 | 0.00 |
April | 0.115610E+10 | 0.207224E+10 | 0.176680E+10 | 5025323.02 | 0.176177E+10 | 0.00 | 0.00 |
May | 0.231475E+10 | 0.133328E+10 | 0.242211E+10 | 80706178.30 | 0.234141E+10 | 0.00 | 0.00 |
June | 0.311118E+10 | 0.709182E+09 | 0.248576E+10 | 0.133570E+09 | 0.235219E+10 | 0.00 | 0.00 |
July | 0.356531E+10 | 0.406949E+09 | 0.248232E+10 | 89769122.78 | 0.239255E+10 | 0.00 | 0.00 |
August | 0.311838E+10 | 0.556340E+09 | 0.219922E+10 | 26173819.73 | 0.217305E+10 | 0.00 | 0.00 |
September | 0.173790E+10 | 0.108691E+10 | 0.160437E+10 | 300432.95 | 0.160407E+10 | 0.00 | 0.00 |
October | 0.107126E+10 | 0.207180E+10 | 0.143475E+10 | 0.00 | 0.143475E+10 | 0.00 | 0.00 |
November | 0.287155E+09 | 0.298262E+10 | 0.973875E+09 | 0.00 | 0.973875E+09 | 0.00 | 0.00 |
December | 37261507.10 | 0.401452E+10 | 0.698643E+09 | 0.00 | 0.698643E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.171535E+11 | 0.265202E+11 | 0.193788E+11 | 0.335545E+09 | 0.190432E+11 | 0.00 | 0.00 |
Minimum of Months | 37261507.10 | 0.406949E+09 | 0.698643E+09 | 0.00 | 0.698643E+09 | 0.00 | 0.00 |
Maximum of Months | 0.356531E+10 | 0.427975E+10 | 0.248576E+10 | 0.133570E+09 | 0.239255E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.709176E+09 | 0.265767E+10 | 0.111539E+10 | 0.447180E+09 | 0.668210E+09 | 0.00 | 0.00 |
February | 0.112062E+10 | 0.242376E+10 | 0.156234E+10 | 0.728829E+09 | 0.833507E+09 | 0.00 | 0.00 |
March | 0.196971E+10 | 0.191558E+10 | 0.220660E+10 | 0.938479E+09 | 0.126812E+10 | 0.00 | 0.00 |
April | 0.263744E+10 | 0.133700E+10 | 0.256265E+10 | 0.112252E+10 | 0.144013E+10 | 0.00 | 0.00 |
May | 0.376162E+10 | 0.900835E+09 | 0.321155E+10 | 0.128353E+10 | 0.192803E+10 | 0.00 | 0.00 |
June | 0.379124E+10 | 0.480491E+09 | 0.288042E+10 | 0.104269E+10 | 0.183773E+10 | 0.00 | 0.00 |
July | 0.426152E+10 | 0.273678E+09 | 0.298946E+10 | 0.107882E+10 | 0.191064E+10 | 0.00 | 0.00 |
August | 0.477091E+10 | 0.371917E+09 | 0.336621E+10 | 0.151782E+10 | 0.184839E+10 | 0.00 | 0.00 |
September | 0.305557E+10 | 0.699566E+09 | 0.242955E+10 | 0.109004E+10 | 0.133951E+10 | 0.00 | 0.00 |
October | 0.254620E+10 | 0.133364E+10 | 0.227598E+10 | 0.103155E+10 | 0.124443E+10 | 0.00 | 0.00 |
November | 0.111555E+10 | 0.186863E+10 | 0.136212E+10 | 0.523065E+09 | 0.839051E+09 | 0.00 | 0.00 |
December | 0.755928E+09 | 0.247101E+10 | 0.109654E+10 | 0.514866E+09 | 0.581672E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.304955E+11 | 0.167338E+11 | 0.270588E+11 | 0.113194E+11 | 0.157394E+11 | 0.00 | 0.00 |
Minimum of Months | 0.709176E+09 | 0.273678E+09 | 0.109654E+10 | 0.447180E+09 | 0.581672E+09 | 0.00 | 0.00 |
Maximum of Months | 0.477091E+10 | 0.265767E+10 | 0.336621E+10 | 0.151782E+10 | 0.192803E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.414112E+10 | 0.385378E+10 | 0.414343E+10 | 0.271314E+10 | 0.143029E+10 | 0.00 | 0.00 |
February | 0.500547E+10 | 0.354667E+10 | 0.493617E+10 | 0.326734E+10 | 0.166883E+10 | 0.00 | 0.00 |
March | 0.529875E+10 | 0.292225E+10 | 0.493050E+10 | 0.273651E+10 | 0.219399E+10 | 0.00 | 0.00 |
April | 0.411040E+10 | 0.214254E+10 | 0.370248E+10 | 0.146407E+10 | 0.223842E+10 | 0.00 | 0.00 |
May | 0.394782E+10 | 0.143462E+10 | 0.335284E+10 | 0.699346E+09 | 0.265349E+10 | 0.00 | 0.00 |
June | 0.413688E+10 | 0.759516E+09 | 0.304504E+10 | 0.465464E+09 | 0.257958E+10 | 0.00 | 0.00 |
July | 0.496596E+10 | 0.418879E+09 | 0.329820E+10 | 0.572895E+09 | 0.272531E+10 | 0.00 | 0.00 |
August | 0.667636E+10 | 0.590777E+09 | 0.440438E+10 | 0.163365E+10 | 0.277073E+10 | 0.00 | 0.00 |
September | 0.621366E+10 | 0.111725E+10 | 0.462468E+10 | 0.239207E+10 | 0.223261E+10 | 0.00 | 0.00 |
October | 0.819481E+10 | 0.207964E+10 | 0.654660E+10 | 0.410518E+10 | 0.244142E+10 | 0.00 | 0.00 |
November | 0.472799E+10 | 0.281718E+10 | 0.439307E+10 | 0.263825E+10 | 0.175482E+10 | 0.00 | 0.00 |
December | 0.465748E+10 | 0.358190E+10 | 0.449086E+10 | 0.318821E+10 | 0.130265E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.620767E+11 | 0.252650E+11 | 0.518683E+11 | 0.258761E+11 | 0.259921E+11 | 0.00 | 0.00 |
Minimum of Months | 0.394782E+10 | 0.418879E+09 | 0.304504E+10 | 0.465464E+09 | 0.130265E+10 | 0.00 | 0.00 |
Maximum of Months | 0.819481E+10 | 0.385378E+10 | 0.654660E+10 | 0.410518E+10 | 0.277073E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.704899E+09 | 0.271795E+10 | 0.110114E+10 | 0.451030E+09 | 0.650111E+09 | 0.00 | 0.00 |
February | 0.103712E+10 | 0.253337E+10 | 0.146665E+10 | 0.644157E+09 | 0.822493E+09 | 0.00 | 0.00 |
March | 0.221378E+10 | 0.191929E+10 | 0.239773E+10 | 0.110696E+10 | 0.129076E+10 | 0.00 | 0.00 |
April | 0.264287E+10 | 0.138579E+10 | 0.253607E+10 | 0.108512E+10 | 0.145095E+10 | 0.00 | 0.00 |
May | 0.359269E+10 | 0.940990E+09 | 0.305274E+10 | 0.115931E+10 | 0.189343E+10 | 0.00 | 0.00 |
June | 0.428776E+10 | 0.512839E+09 | 0.323335E+10 | 0.130410E+10 | 0.192925E+10 | 0.00 | 0.00 |
July | 0.445635E+10 | 0.293834E+09 | 0.312915E+10 | 0.117834E+10 | 0.195081E+10 | 0.00 | 0.00 |
August | 0.493015E+10 | 0.402704E+09 | 0.346169E+10 | 0.160253E+10 | 0.185916E+10 | 0.00 | 0.00 |
September | 0.302594E+10 | 0.737608E+09 | 0.237825E+10 | 0.103929E+10 | 0.133896E+10 | 0.00 | 0.00 |
October | 0.278182E+10 | 0.138288E+10 | 0.243645E+10 | 0.118478E+10 | 0.125167E+10 | 0.00 | 0.00 |
November | 0.775934E+09 | 0.192400E+10 | 0.110724E+10 | 0.320000E+09 | 0.787241E+09 | 0.00 | 0.00 |
December | 0.665629E+09 | 0.254643E+10 | 0.101770E+10 | 0.440359E+09 | 0.577337E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.311149E+11 | 0.172977E+11 | 0.273181E+11 | 0.115160E+11 | 0.158022E+11 | 0.00 | 0.00 |
Minimum of Months | 0.665629E+09 | 0.293834E+09 | 0.101770E+10 | 0.320000E+09 | 0.577337E+09 | 0.00 | 0.00 |
Maximum of Months | 0.493015E+10 | 0.271795E+10 | 0.346169E+10 | 0.160253E+10 | 0.195081E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.537131E+10 | -0.462774E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -743570215.7 | 58.98 | 0.00 | 0.00 |
February | 0.490648E+10 | -0.424802E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -658459944.9 | 58.98 | 0.00 | 0.00 |
March | 0.562858E+10 | -0.491448E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -714103117.8 | 58.98 | 0.00 | 0.00 |
April | 0.487660E+10 | -0.419566E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -680940625.4 | 58.98 | 0.00 | 0.00 |
May | 0.488457E+10 | -0.419041E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694162315.7 | 58.98 | 0.00 | 0.00 |
June | 0.452829E+10 | -0.385995E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668336059.7 | 58.98 | 0.00 | 0.00 |
July | 0.413264E+10 | -0.344452E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688123870.0 | 58.98 | 0.00 | 0.00 |
August | 0.444562E+10 | -0.375691E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688709087.3 | 58.98 | 0.00 | 0.00 |
September | 0.415693E+10 | -0.348961E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667318987.8 | 58.98 | 0.00 | 0.00 |
October | 0.453457E+10 | -0.384247E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -692105325.8 | 58.99 | 0.00 | 0.00 |
November | 0.476008E+10 | -0.407525E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -684825573.4 | 58.98 | 0.00 | 0.00 |
December | 0.503160E+10 | -0.430909E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -722516097.3 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.572573E+11 | -0.489541E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.830317E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.413264E+10 | -0.491448E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -743570215.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.562858E+10 | -0.344452E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -658459944.9 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-07:49 | 5719.27 | 34.81 | 184.50 | 232.00 | 2991.37 | 32.96 | 174.67 | 189.17 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8255.58 | 36.30 | 203.17 | 252.67 | 1832.08 | 26.07 | 150.50 | 226.83 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:10 | 2839.50 | 20.43 | 45.17 | 314.17 | 1359.02 | 21.06 | 144.50 | 267.50 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 1774.32 | 17.69 | 0.00 | 331.17 | 1046.77 | 20.48 | 101.83 | 285.17 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-06:10 | 1546.71 | 17.59 | 0.00 | 383.83 | 866.91 | 20.31 | 151.00 | 331.50 |
June | 351.83 | 0.51 | 0.48 | 01-JUN-05:00 | 1470.79 | 17.55 | 0.00 | 372.83 | 836.00 | 20.34 | 135.67 | 326.67 |
July | 365.17 | 0.51 | 0.48 | 01-JUL-06:10 | 1625.91 | 17.82 | 0.00 | 380.83 | 904.24 | 20.60 | 168.67 | 331.33 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-06:10 | 1803.41 | 17.82 | 0.00 | 363.67 | 1043.81 | 20.58 | 181.83 | 328.50 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:30 | 3332.57 | 20.14 | 29.50 | 316.33 | 1250.72 | 20.81 | 140.67 | 279.17 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 9044.28 | 35.39 | 281.00 | 302.50 | 1758.24 | 22.99 | 235.83 | 281.50 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:00 | 5705.62 | 35.04 | 227.17 | 253.17 | 1980.35 | 29.04 | 213.67 | 227.83 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 5291.30 | 33.80 | 178.83 | 233.67 | 4837.57 | 38.79 | 207.83 | 206.67 |
Annual Sum or Average | 3472.67 | 0.51 | 3675.05 | 23.99 | 1149.33 | 3736.83 | 1550.72 | 23.54 | 2006.67 | 3281.83 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1470.79 | 17.55 | 0.00 | 232.00 | 836.00 | 20.31 | 101.83 | 189.17 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 9044.28 | 36.30 | 281.00 | 383.83 | 4837.57 | 38.79 | 235.83 | 331.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-07:49 | 1724.32 | 20.20 | 60.83 | 209.17 | 980.12 | 23.01 | 72.00 | 146.17 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2471.33 | 22.95 | 80.67 | 236.17 | 1426.28 | 23.98 | 69.50 | 189.83 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:00 | 2460.06 | 18.92 | 58.67 | 305.83 | 1423.12 | 21.91 | 54.67 | 237.17 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:19 | 3365.83 | 21.21 | 80.67 | 332.17 | 1343.86 | 22.28 | 50.17 | 285.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 2773.47 | 20.09 | 98.83 | 387.67 | 1498.06 | 21.78 | 72.33 | 336.67 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-04:00 | 2466.97 | 19.34 | 80.50 | 378.83 | 1365.52 | 21.46 | 60.83 | 340.67 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 2546.80 | 19.95 | 89.00 | 387.33 | 1374.85 | 21.85 | 64.50 | 343.50 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:40 | 3391.46 | 20.79 | 111.67 | 365.17 | 1405.01 | 22.09 | 68.50 | 335.00 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-05:49 | 2954.42 | 20.75 | 79.67 | 312.83 | 1267.40 | 21.22 | 43.83 | 269.33 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 2572.12 | 20.68 | 78.33 | 285.50 | 1388.01 | 23.21 | 91.67 | 250.17 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-06:49 | 1771.83 | 20.76 | 71.67 | 235.00 | 907.77 | 21.86 | 81.83 | 183.83 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-07:40 | 1580.61 | 19.72 | 64.00 | 204.67 | 966.25 | 23.38 | 80.83 | 136.00 |
Annual Sum or Average | 3472.67 | 0.51 | 2583.66 | 20.38 | 954.50 | 3640.33 | 1307.59 | 22.23 | 810.67 | 3053.33 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1580.61 | 18.92 | 58.67 | 204.67 | 907.77 | 21.22 | 43.83 | 136.00 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 3391.46 | 22.95 | 111.67 | 387.67 | 1498.06 | 23.98 | 91.67 | 343.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.55 | 0.48 | 01-JAN-09:20 | 538.53 | 14.03 | 0.00 | 188.00 | 328.99 | 17.01 | 0.00 | 88.67 |
February | 216.00 | 0.53 | 0.48 | 01-FEB-08:00 | 580.87 | 14.92 | 0.00 | 216.50 | 376.73 | 18.05 | 0.00 | 134.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:40 | 772.74 | 15.99 | 0.00 | 300.83 | 480.81 | 18.80 | 0.33 | 211.67 |
April | 261.17 | 0.50 | 0.48 | 01-APR-14:39 | 869.54 | 17.02 | 0.00 | 336.00 | 542.98 | 19.79 | 6.83 | 273.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1128.48 | 17.81 | 1.83 | 397.33 | 648.40 | 20.56 | 99.33 | 344.83 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1264.33 | 19.60 | 41.00 | 393.83 | 715.29 | 23.05 | 162.00 | 365.17 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1252.10 | 18.01 | 0.00 | 399.33 | 708.18 | 22.59 | 159.33 | 360.17 |
August | 389.17 | 0.50 | 0.48 | 01-AUG-05:00 | 1027.02 | 17.48 | 0.00 | 373.83 | 618.86 | 20.22 | 54.17 | 339.67 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:30 | 796.42 | 16.54 | 0.00 | 310.83 | 502.44 | 19.39 | 0.83 | 247.00 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 720.64 | 16.11 | 0.00 | 281.00 | 465.84 | 19.11 | 0.00 | 220.83 |
November | 240.83 | 0.53 | 0.48 | 01-NOV-07:49 | 602.02 | 14.74 | 0.00 | 220.83 | 359.86 | 17.64 | 0.00 | 124.83 |
December | 211.17 | 0.58 | 0.48 | 01-DEC-09:20 | 433.20 | 12.94 | 0.00 | 171.17 | 273.34 | 16.12 | 0.00 | 55.17 |
Annual Sum or Average | 3472.67 | 0.51 | 886.32 | 16.61 | 42.83 | 3589.50 | 530.84 | 19.74 | 482.83 | 2766.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 433.20 | 12.94 | 0.00 | 171.17 | 273.34 | 16.12 | 0.00 | 55.17 | |
Maximum of Months | 389.17 | 0.58 | 0.48 | 1264.33 | 19.60 | 41.00 | 399.33 | 715.29 | 23.05 | 162.00 | 365.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-09:09 | 1643.95 | 19.84 | 57.17 | 213.83 | 969.79 | 23.12 | 64.83 | 146.83 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:00 | 1910.38 | 20.24 | 57.00 | 235.17 | 995.46 | 21.55 | 40.33 | 185.67 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:49 | 2634.34 | 19.90 | 70.83 | 308.83 | 1567.61 | 23.90 | 75.83 | 247.67 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 3174.74 | 20.87 | 76.83 | 330.83 | 1267.75 | 20.83 | 37.00 | 285.33 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:30 | 2937.14 | 18.07 | 69.00 | 387.67 | 1310.93 | 18.28 | 0.00 | 339.67 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-06:10 | 2877.16 | 14.59 | 1.83 | 383.33 | 1549.59 | 18.47 | 0.00 | 333.00 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-06:10 | 2700.41 | 17.34 | 49.00 | 387.33 | 1441.86 | 18.59 | 0.00 | 340.17 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-06:30 | 3458.70 | 19.20 | 86.33 | 364.33 | 1505.67 | 18.74 | 8.50 | 334.00 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-07:10 | 2817.56 | 21.33 | 85.17 | 313.00 | 1462.58 | 22.49 | 61.17 | 270.83 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3023.30 | 23.08 | 109.33 | 296.50 | 1263.05 | 22.79 | 68.83 | 264.33 |
November | 240.83 | 0.51 | 0.48 | 01-NOV-07:49 | 1445.98 | 19.91 | 68.50 | 238.17 | 788.21 | 22.53 | 70.67 | 183.33 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-09:09 | 1358.35 | 20.01 | 67.50 | 206.83 | 737.35 | 20.97 | 54.83 | 139.50 |
Annual Sum or Average | 3472.67 | 0.51 | 2618.69 | 19.31 | 798.50 | 3665.83 | 1285.68 | 20.70 | 482.00 | 3070.33 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1358.35 | 14.59 | 1.83 | 206.83 | 737.35 | 18.28 | 0.00 | 139.50 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 3458.70 | 23.08 | 109.33 | 387.67 | 1567.61 | 23.90 | 75.83 | 340.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-07:49 | 5485.31 | 32.27 | 169.00 | 227.33 | 2874.91 | 31.86 | 144.00 | 186.83 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8084.23 | 35.95 | 202.83 | 251.00 | 1721.40 | 24.52 | 80.00 | 226.33 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:10 | 2722.90 | 17.14 | 44.83 | 313.67 | 1257.97 | 18.55 | 18.50 | 259.00 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 1674.98 | 14.12 | 0.00 | 329.17 | 978.36 | 18.13 | 0.00 | 281.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-06:10 | 1471.89 | 14.09 | 0.00 | 381.17 | 820.86 | 17.95 | 0.00 | 326.67 |
June | 351.83 | 0.51 | 0.48 | 01-JUN-05:00 | 1401.99 | 14.07 | 0.00 | 370.17 | 794.81 | 18.01 | 0.00 | 323.17 |
July | 365.17 | 0.51 | 0.48 | 01-JUL-06:10 | 1548.73 | 14.28 | 0.00 | 377.50 | 857.66 | 18.20 | 0.00 | 326.50 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-06:19 | 1707.59 | 14.42 | 0.00 | 362.17 | 980.59 | 18.33 | 1.83 | 323.17 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:30 | 3205.04 | 16.84 | 29.50 | 313.33 | 1159.67 | 18.32 | 1.50 | 275.50 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 8852.70 | 34.74 | 278.33 | 301.00 | 1628.41 | 20.27 | 24.00 | 278.67 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:00 | 5528.29 | 33.43 | 217.00 | 249.50 | 1868.30 | 27.01 | 119.67 | 225.33 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 5133.04 | 32.98 | 178.83 | 231.67 | 4693.38 | 37.35 | 198.50 | 200.33 |
Annual Sum or Average | 3472.67 | 0.51 | 3551.16 | 21.32 | 1120.33 | 3707.67 | 1467.47 | 21.34 | 588.00 | 3232.50 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1401.99 | 14.07 | 0.00 | 227.33 | 794.81 | 17.95 | 0.00 | 186.83 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 8852.70 | 35.95 | 278.33 | 381.17 | 4693.38 | 37.35 | 198.50 | 326.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-07:49 | 1662.75 | 19.69 | 60.33 | 205.67 | 940.58 | 22.78 | 66.00 | 141.67 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2242.81 | 20.11 | 61.33 | 233.00 | 1376.98 | 23.77 | 60.50 | 184.33 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:00 | 2370.95 | 18.40 | 57.50 | 303.00 | 1366.53 | 21.71 | 52.00 | 233.17 |
April | 261.17 | 0.51 | 0.48 | 01-APR-06:19 | 3279.92 | 20.81 | 80.67 | 329.17 | 1278.83 | 22.10 | 50.17 | 279.67 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 2591.49 | 18.18 | 75.00 | 385.83 | 1435.43 | 21.61 | 72.33 | 331.17 |
June | 351.83 | 0.51 | 0.48 | 01-JUN-05:10 | 2386.33 | 18.93 | 80.50 | 375.83 | 1309.60 | 21.28 | 60.83 | 337.50 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 2458.96 | 19.56 | 88.83 | 384.67 | 1316.10 | 21.68 | 64.50 | 339.50 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:40 | 3300.83 | 20.40 | 111.67 | 362.67 | 1338.80 | 21.92 | 68.50 | 331.17 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-05:49 | 2873.84 | 20.33 | 79.67 | 310.83 | 1205.80 | 21.02 | 41.50 | 265.17 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 2491.59 | 20.25 | 78.33 | 282.83 | 1328.82 | 23.00 | 75.67 | 244.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-06:49 | 1711.09 | 20.33 | 71.67 | 232.33 | 864.08 | 21.62 | 71.83 | 179.33 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-07:40 | 1533.49 | 19.27 | 64.00 | 201.83 | 931.16 | 23.16 | 76.67 | 130.50 |
Annual Sum or Average | 3472.67 | 0.51 | 2484.55 | 19.65 | 909.50 | 3607.67 | 1251.47 | 22.04 | 760.50 | 2998.00 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1533.49 | 18.18 | 57.50 | 201.83 | 864.08 | 21.02 | 41.50 | 130.50 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 3300.83 | 20.81 | 111.67 | 385.83 | 1435.43 | 23.77 | 76.67 | 339.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.55 | 0.48 | 01-JAN-09:20 | 513.96 | 10.56 | 0.00 | 179.83 | 315.99 | 14.64 | 0.00 | 80.00 |
February | 216.00 | 0.54 | 0.48 | 01-FEB-09:09 | 554.83 | 11.60 | 0.00 | 211.83 | 363.26 | 15.87 | 0.00 | 126.00 |
March | 275.00 | 0.53 | 0.48 | 01-MAR-07:49 | 739.75 | 12.87 | 0.00 | 298.00 | 463.68 | 16.81 | 0.00 | 204.33 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 833.17 | 13.92 | 0.00 | 334.33 | 524.14 | 17.93 | 0.00 | 265.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:00 | 1080.74 | 14.45 | 1.67 | 395.33 | 622.69 | 18.43 | 3.33 | 337.50 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1212.24 | 16.62 | 40.67 | 392.33 | 686.64 | 21.23 | 50.17 | 362.00 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1199.79 | 14.59 | 0.00 | 397.17 | 679.53 | 20.70 | 42.50 | 356.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 983.89 | 14.43 | 0.00 | 372.67 | 596.17 | 18.37 | 0.00 | 334.83 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:40 | 762.56 | 13.48 | 0.00 | 307.00 | 484.92 | 17.50 | 0.00 | 237.17 |
October | 305.50 | 0.52 | 0.48 | 01-OCT-14:39 | 687.79 | 13.03 | 0.00 | 277.67 | 448.76 | 17.13 | 0.00 | 213.83 |
November | 240.83 | 0.54 | 0.48 | 01-NOV-07:49 | 575.08 | 11.16 | 0.00 | 216.67 | 345.55 | 15.22 | 0.00 | 115.50 |
December | 211.17 | 0.58 | 0.48 | 01-DEC-09:20 | 412.92 | 9.39 | 0.00 | 161.33 | 262.67 | 13.65 | 0.00 | 47.67 |
Annual Sum or Average | 3472.67 | 0.52 | 848.44 | 13.38 | 42.33 | 3544.17 | 510.68 | 17.70 | 96.00 | 2680.67 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 412.92 | 9.39 | 0.00 | 161.33 | 262.67 | 13.65 | 0.00 | 47.67 | |
Maximum of Months | 389.17 | 0.58 | 0.48 | 1212.24 | 16.62 | 40.67 | 397.17 | 686.64 | 21.23 | 50.17 | 362.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-09:20 | 1592.00 | 19.50 | 57.17 | 210.00 | 932.20 | 23.02 | 64.33 | 143.33 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-09:09 | 1845.48 | 19.88 | 57.00 | 232.17 | 947.58 | 21.44 | 39.83 | 179.50 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:49 | 2553.37 | 19.54 | 70.83 | 306.50 | 1506.74 | 23.80 | 75.33 | 242.00 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 3090.09 | 20.50 | 76.83 | 327.83 | 1203.02 | 20.69 | 37.00 | 280.50 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-06:30 | 2853.70 | 17.66 | 69.00 | 385.00 | 1252.57 | 18.10 | 0.00 | 332.33 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-06:10 | 2778.63 | 14.15 | 1.83 | 380.50 | 1483.59 | 18.30 | 0.00 | 328.00 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-06:19 | 2608.83 | 16.92 | 49.00 | 384.50 | 1379.32 | 18.42 | 0.00 | 335.50 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-06:40 | 3337.95 | 18.59 | 83.33 | 363.33 | 1437.24 | 18.59 | 8.50 | 331.50 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-07:10 | 2640.54 | 19.27 | 67.50 | 310.67 | 1401.29 | 22.36 | 60.67 | 266.33 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 2936.59 | 22.76 | 109.33 | 295.50 | 1200.36 | 22.68 | 66.67 | 260.67 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:00 | 1398.08 | 19.56 | 68.50 | 236.00 | 754.13 | 22.42 | 70.00 | 178.00 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-09:20 | 1312.59 | 19.68 | 67.50 | 203.33 | 703.98 | 20.87 | 54.33 | 131.67 |
Annual Sum or Average | 3472.67 | 0.51 | 2528.53 | 18.77 | 777.83 | 3635.33 | 1228.73 | 20.57 | 476.67 | 3009.33 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1312.59 | 14.15 | 1.83 | 203.33 | 703.98 | 18.10 | 0.00 | 131.67 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 3337.95 | 22.76 | 109.33 | 385.00 | 1506.74 | 23.80 | 75.33 | 335.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-07:49 | 5485.35 | 32.27 | 169.00 | 227.33 | 2874.83 | 31.86 | 144.00 | 186.83 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:49 | 8084.23 | 35.95 | 202.83 | 251.00 | 1721.31 | 24.52 | 80.00 | 226.33 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:10 | 2722.83 | 17.14 | 44.83 | 313.67 | 1257.89 | 18.55 | 18.67 | 259.00 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 1674.92 | 14.12 | 0.00 | 329.17 | 978.30 | 18.13 | 0.00 | 281.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-06:10 | 1471.83 | 14.09 | 0.00 | 381.17 | 820.80 | 17.95 | 0.00 | 326.67 |
June | 351.83 | 0.51 | 0.48 | 01-JUN-05:00 | 1401.93 | 14.08 | 0.00 | 370.17 | 794.76 | 18.01 | 0.00 | 323.17 |
July | 365.17 | 0.51 | 0.48 | 01-JUL-06:10 | 1548.67 | 14.28 | 0.00 | 377.50 | 857.60 | 18.20 | 0.00 | 326.50 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-06:19 | 1707.52 | 14.42 | 0.00 | 362.17 | 980.53 | 18.33 | 1.83 | 323.17 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:30 | 3204.97 | 16.84 | 29.50 | 313.33 | 1159.59 | 18.32 | 1.50 | 275.50 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 8852.67 | 34.74 | 278.33 | 301.00 | 1628.31 | 20.27 | 24.00 | 278.67 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:00 | 5528.30 | 33.43 | 217.00 | 249.50 | 1868.20 | 27.01 | 119.67 | 225.33 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 5133.09 | 32.99 | 178.83 | 231.67 | 4693.32 | 37.35 | 198.50 | 200.33 |
Annual Sum or Average | 3472.67 | 0.51 | 3551.12 | 21.33 | 1120.33 | 3707.67 | 1467.40 | 21.34 | 588.17 | 3232.50 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1401.93 | 14.08 | 0.00 | 227.33 | 794.76 | 17.95 | 0.00 | 186.83 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 8852.67 | 35.95 | 278.33 | 381.17 | 4693.32 | 37.35 | 198.50 | 326.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-07:49 | 1662.75 | 19.69 | 60.33 | 205.67 | 940.55 | 22.78 | 66.00 | 141.67 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2242.82 | 20.11 | 61.33 | 233.00 | 1376.95 | 23.77 | 60.50 | 184.33 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:00 | 2370.95 | 18.40 | 57.50 | 303.00 | 1366.48 | 21.71 | 52.00 | 233.17 |
April | 261.17 | 0.51 | 0.48 | 01-APR-06:19 | 3279.91 | 20.81 | 80.67 | 329.17 | 1278.77 | 22.10 | 50.17 | 279.67 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 2591.46 | 18.18 | 75.00 | 385.83 | 1435.36 | 21.61 | 72.33 | 331.17 |
June | 351.83 | 0.51 | 0.48 | 01-JUN-05:10 | 2386.31 | 18.94 | 80.50 | 375.83 | 1309.54 | 21.28 | 60.83 | 337.50 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 2458.92 | 19.56 | 88.83 | 384.67 | 1316.04 | 21.69 | 64.50 | 339.50 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:40 | 3300.81 | 20.41 | 111.67 | 362.67 | 1338.74 | 21.92 | 68.50 | 331.17 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-05:49 | 2873.84 | 20.33 | 79.67 | 310.83 | 1205.75 | 21.02 | 41.50 | 265.17 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 2491.60 | 20.25 | 78.33 | 282.83 | 1328.78 | 23.00 | 75.67 | 244.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-06:49 | 1711.08 | 20.33 | 71.67 | 232.33 | 864.04 | 21.62 | 71.83 | 179.33 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-07:40 | 1533.50 | 19.27 | 64.00 | 201.83 | 931.13 | 23.16 | 76.67 | 130.50 |
Annual Sum or Average | 3472.67 | 0.51 | 2484.54 | 19.65 | 909.50 | 3607.67 | 1251.42 | 22.04 | 760.50 | 2998.00 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1533.50 | 18.18 | 57.50 | 201.83 | 864.04 | 21.02 | 41.50 | 130.50 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 3300.81 | 20.81 | 111.67 | 385.83 | 1435.36 | 23.77 | 76.67 | 339.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.55 | 0.48 | 01-JAN-09:20 | 513.95 | 10.56 | 0.00 | 179.83 | 315.97 | 14.64 | 0.00 | 80.00 |
February | 216.00 | 0.54 | 0.48 | 01-FEB-09:09 | 554.83 | 11.60 | 0.00 | 211.83 | 363.24 | 15.87 | 0.00 | 126.00 |
March | 275.00 | 0.53 | 0.48 | 01-MAR-07:49 | 739.74 | 12.87 | 0.00 | 298.00 | 463.65 | 16.81 | 0.00 | 204.33 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 833.17 | 13.93 | 0.00 | 334.33 | 524.11 | 17.93 | 0.00 | 265.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:00 | 1080.72 | 14.45 | 1.67 | 395.33 | 622.65 | 18.43 | 3.33 | 337.50 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1212.22 | 16.63 | 40.67 | 392.33 | 686.60 | 21.23 | 50.17 | 362.00 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1199.77 | 14.59 | 0.00 | 397.17 | 679.49 | 20.70 | 42.50 | 356.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 983.88 | 14.43 | 0.00 | 372.67 | 596.13 | 18.37 | 0.00 | 334.83 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:40 | 762.55 | 13.48 | 0.00 | 307.00 | 484.90 | 17.50 | 0.00 | 237.17 |
October | 305.50 | 0.52 | 0.48 | 01-OCT-14:39 | 687.80 | 13.03 | 0.00 | 277.67 | 448.74 | 17.13 | 0.00 | 213.83 |
November | 240.83 | 0.54 | 0.48 | 01-NOV-07:49 | 575.07 | 11.16 | 0.00 | 216.67 | 345.53 | 15.22 | 0.00 | 115.50 |
December | 211.17 | 0.58 | 0.48 | 01-DEC-09:20 | 412.93 | 9.39 | 0.00 | 161.33 | 262.65 | 13.65 | 0.00 | 47.67 |
Annual Sum or Average | 3472.67 | 0.52 | 848.44 | 13.38 | 42.33 | 3544.17 | 510.65 | 17.70 | 96.00 | 2680.67 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 412.93 | 9.39 | 0.00 | 161.33 | 262.65 | 13.65 | 0.00 | 47.67 | |
Maximum of Months | 389.17 | 0.58 | 0.48 | 1212.22 | 16.63 | 40.67 | 397.17 | 686.60 | 21.23 | 50.17 | 362.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-09:20 | 1592.00 | 19.50 | 57.17 | 210.00 | 932.16 | 23.02 | 64.33 | 143.33 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-09:09 | 1845.48 | 19.88 | 57.00 | 232.17 | 947.54 | 21.44 | 39.83 | 179.50 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:49 | 2553.37 | 19.54 | 70.83 | 306.50 | 1506.69 | 23.80 | 75.33 | 242.00 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 3090.08 | 20.50 | 76.83 | 327.83 | 1202.96 | 20.69 | 37.00 | 280.50 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-06:30 | 2853.67 | 17.66 | 69.00 | 385.00 | 1252.51 | 18.10 | 0.00 | 332.33 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-06:10 | 2778.59 | 14.15 | 1.83 | 380.50 | 1483.53 | 18.30 | 0.00 | 328.00 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-06:19 | 2608.79 | 16.92 | 49.00 | 384.50 | 1379.25 | 18.42 | 0.00 | 335.50 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-06:40 | 3337.94 | 18.59 | 83.33 | 363.33 | 1437.18 | 18.59 | 8.50 | 331.50 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-07:10 | 2640.53 | 19.27 | 67.50 | 310.67 | 1401.24 | 22.37 | 60.67 | 266.33 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 2936.60 | 22.76 | 109.33 | 295.50 | 1200.31 | 22.68 | 66.67 | 260.50 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:00 | 1398.07 | 19.56 | 68.50 | 236.00 | 754.09 | 22.42 | 70.00 | 178.00 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-09:20 | 1312.59 | 19.68 | 67.50 | 203.33 | 703.95 | 20.87 | 54.33 | 131.67 |
Annual Sum or Average | 3472.67 | 0.51 | 2528.52 | 18.77 | 777.83 | 3635.33 | 1228.67 | 20.57 | 476.67 | 3009.17 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1312.59 | 14.15 | 1.83 | 203.33 | 703.95 | 18.10 | 0.00 | 131.67 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 3337.94 | 22.76 | 109.33 | 385.00 | 1506.69 | 23.80 | 75.33 | 335.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.730384E+09 | 25571.27 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 964372.21 | 16033.68 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.731348E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.730384E+09 | 25571.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.682232E+10 | 10964.23 | 03-JAN-12:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.590832E+10 | 10891.48 | 28-FEB-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.427808E+10 | 10934.82 | 06-MAR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.228383E+10 | 10923.10 | 24-APR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.856021E+09 | 10948.98 | 05-MAY-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29671192.42 | 8723.79 | 02-JUN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111276E+09 | 11112.17 | 20-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.615234E+09 | 11046.50 | 17-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279338E+10 | 10954.46 | 13-NOV-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.476107E+10 | 10920.54 | 04-DEC-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.682232E+10 | 11112.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.204476E+10 | 8508.46 | 01-JAN-22:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144048E+10 | 8508.46 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.437748E+09 | 8508.46 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131260E+09 | 8508.46 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.240008E+09 | 8508.46 | 16-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.866061E+09 | 8508.46 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.516031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204476E+10 | 8508.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.361533E+10 | 7909.12 | 04-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.305166E+10 | 7883.37 | 24-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114034E+10 | 7885.38 | 21-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.272486E+09 | 7885.41 | 25-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 618471.88 | 2456.53 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.506154E+09 | 7877.93 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164712E+10 | 7887.39 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102337E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.361533E+10 | 7909.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.222702E+10 | 8586.54 | 01-JAN-22:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169957E+10 | 8586.54 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.492879E+09 | 8586.54 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143990E+09 | 8586.54 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 782977.97 | 1899.16 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.334154E+09 | 8586.54 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.102737E+10 | 8586.54 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.592577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.222702E+10 | 8586.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.251531E+10 | 24633.57 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112839E+10 | 24633.57 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85427056.17 | 24633.57 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9202672.23 | 24633.57 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272585E+09 | 24633.57 | 20-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.582433E+09 | 24633.57 | 04-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.459335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.251531E+10 | 24633.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.212163E+10 | 12104.48 | 27-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138356E+10 | 12087.99 | 16-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380899E+09 | 12070.32 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121294E+09 | 11980.58 | 21-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74867.83 | 499.12 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86509.96 | 75.47 | 28-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.388581E+09 | 12056.12 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.111196E+10 | 12110.00 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212163E+10 | 12110.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.218242E+10 | 8825.12 | 01-JAN-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151048E+10 | 8825.12 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.446898E+09 | 8825.12 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126927E+09 | 8825.12 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3678779.85 | 3185.56 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.518969E+09 | 8825.12 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128743E+10 | 8825.12 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.607681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.218242E+10 | 8825.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.336959E+10 | 8637.80 | 13-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.261493E+10 | 8625.26 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.714744E+09 | 8632.41 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144608E+09 | 8611.33 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2946342.44 | 2400.60 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.785695E+09 | 8656.94 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191463E+10 | 8626.59 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.954714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.336959E+10 | 8656.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.230515E+10 | 8901.61 | 01-JAN-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172652E+10 | 8901.61 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.512817E+09 | 8901.61 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141329E+09 | 8901.61 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 500847.91 | 1571.32 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4839665.32 | 2772.16 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.626178E+09 | 8901.61 | 15-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141890E+10 | 8901.61 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.673623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.230515E+10 | 8901.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.627862E+10 | 31734.93 | 23-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.465135E+10 | 31695.20 | 24-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122295E+10 | 31726.50 | 21-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.371280E+09 | 31614.61 | 04-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 179929.28 | 1199.53 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 373967.98 | 1003.63 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.175230E+10 | 31737.76 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.370330E+10 | 31647.73 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.627862E+10 | 31737.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.380124E+10 | 13586.05 | 23-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.286228E+10 | 13561.14 | 24-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123900E+10 | 13608.15 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.483525E+09 | 13543.54 | 03-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15749489.36 | 11182.86 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49209810.75 | 13418.12 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116074E+10 | 13560.84 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.250395E+10 | 13593.41 | 30-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.380124E+10 | 13608.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.333213E+10 | 10875.85 | 13-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.256285E+10 | 10847.78 | 16-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102632E+10 | 10886.58 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.365504E+09 | 10848.69 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4864743.68 | 4723.64 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57912350.97 | 9273.12 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112778E+10 | 10884.38 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.232763E+10 | 10907.51 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.333213E+10 | 10907.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.542618E+10 | 10057.42 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.457904E+10 | 10020.61 | 24-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182964E+10 | 10019.22 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.526372E+09 | 10022.47 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10462887.69 | 9967.21 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89939502.54 | 9948.99 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.188704E+10 | 10044.42 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383807E+10 | 10026.68 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.542618E+10 | 10057.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.365014E+10 | 11423.18 | 01-JAN-02:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299627E+10 | 11423.18 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126468E+10 | 11423.18 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.451235E+09 | 11423.18 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17254321.64 | 7036.77 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 125221.78 | 41.28 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90453980.21 | 9210.74 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141290E+10 | 11423.18 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.266777E+10 | 11423.18 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.365014E+10 | 11423.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.933384E+10 | 25466.88 | 02-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.937104E+10 | 25397.49 | 06-FEB-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.416154E+10 | 13726.75 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.526680E+09 | 6940.34 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 63141.52 | 224.55 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32957832.01 | 4061.34 | 28-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237881E+10 | 14064.59 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.626914E+10 | 13864.28 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.937104E+10 | 25466.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103629E+11 | 23451.63 | 02-JAN-08:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104795E+11 | 25745.50 | 06-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.532949E+10 | 15330.06 | 23-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103327E+10 | 8134.17 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2800015.16 | 1824.16 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122564E+09 | 5165.36 | 28-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333051E+10 | 15409.26 | 24-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.776214E+10 | 15738.84 | 22-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.384231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104795E+11 | 25745.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.109944E+11 | 24359.45 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108647E+11 | 25206.10 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.548892E+10 | 17835.81 | 23-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125056E+10 | 9617.76 | 03-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7946324.63 | 3199.96 | 01-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.225540E+09 | 6928.01 | 28-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.357367E+10 | 17284.66 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.813399E+10 | 18015.03 | 22-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.109944E+11 | 25206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.436525E+09 | 0.287914E+09 | 21949.60 | 27-MAR-16:00 | 17196.58 | 0.00 |
April | 0.00 | 0.00 | 0.386519E+10 | 0.339501E+10 | 38379.90 | 07-APR-15:50 | 38379.90 | 0.00 |
May | 0.00 | 0.00 | 0.157491E+11 | 0.130900E+11 | 74742.72 | 30-MAY-14:00 | 74742.72 | 0.00 |
June | 0.00 | 0.00 | 0.558415E+11 | 0.429341E+11 | 90798.67 | 19-JUN-12:03 | 67065.89 | 0.00 |
July | 0.00 | 0.00 | 0.796705E+11 | 0.585887E+11 | 96578.47 | 10-JUL-06:03 | 85118.52 | 0.00 |
August | 0.00 | 0.00 | 0.820188E+11 | 0.648440E+11 | 114769.66 | 17-AUG-06:03 | 71827.96 | 0.00 |
September | 0.00 | 0.00 | 0.426499E+11 | 0.340507E+11 | 81978.76 | 07-SEP-11:10 | 50065.68 | 0.00 |
October | 0.00 | 0.00 | 0.182158E+11 | 0.128625E+11 | 64491.88 | 05-OCT-12:30 | 44702.42 | 0.00 |
November | 0.00 | 0.00 | 0.397543E+09 | 0.316894E+09 | 9857.36 | 03-NOV-14:00 | 9857.36 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.298845E+12 | 0.230370E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.820188E+11 | 0.648440E+11 | 114769.66 | 85118.52 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.416154E+09 | 0.279718E+09 | 20527.93 | 27-MAR-16:00 | 16217.10 | 0.00 |
April | 0.00 | 0.00 | 0.387728E+10 | 0.342537E+10 | 39458.79 | 07-APR-14:30 | 39458.79 | 0.00 |
May | 0.00 | 0.00 | 0.149752E+11 | 0.126970E+11 | 74561.11 | 30-MAY-14:00 | 74561.11 | 0.00 |
June | 0.00 | 0.00 | 0.508910E+11 | 0.390071E+11 | 92690.00 | 19-JUN-06:03 | 64694.65 | 0.00 |
July | 0.00 | 0.00 | 0.722691E+11 | 0.525940E+11 | 107336.91 | 22-JUL-05:03 | 61353.87 | 0.00 |
August | 0.00 | 0.00 | 0.723638E+11 | 0.568283E+11 | 99435.75 | 05-AUG-05:03 | 65508.12 | 0.00 |
September | 0.00 | 0.00 | 0.358543E+11 | 0.282340E+11 | 79293.46 | 01-SEP-05:03 | 56104.38 | 0.00 |
October | 0.00 | 0.00 | 0.152092E+11 | 0.104587E+11 | 54424.39 | 04-OCT-14:30 | 42794.61 | 0.00 |
November | 0.00 | 0.00 | 0.361919E+09 | 0.295846E+09 | 8232.99 | 04-NOV-12:30 | 6668.68 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.266218E+12 | 0.203820E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.723638E+11 | 0.568283E+11 | 107336.91 | 74561.11 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 167525.54 | 160876.38 | 279.21 | 15-JAN-10:20 | 268.13 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.433811E+09 | 0.285913E+09 | 21661.08 | 27-MAR-16:00 | 16549.92 | 0.00 |
April | 0.00 | 0.00 | 0.412568E+10 | 0.360746E+10 | 44796.47 | 07-APR-14:30 | 44796.47 | 0.00 |
May | 0.00 | 0.00 | 0.157941E+11 | 0.134559E+11 | 84470.95 | 30-MAY-14:00 | 84470.95 | 0.00 |
June | 0.00 | 0.00 | 0.539758E+11 | 0.418584E+11 | 94112.66 | 19-JUN-13:50 | 77733.25 | 0.00 |
July | 0.00 | 0.00 | 0.772098E+11 | 0.575168E+11 | 115567.43 | 22-JUL-05:03 | 62105.54 | 0.00 |
August | 0.00 | 0.00 | 0.767431E+11 | 0.613340E+11 | 105652.78 | 05-AUG-05:03 | 68652.57 | 0.00 |
September | 0.00 | 0.00 | 0.365133E+11 | 0.286243E+11 | 83012.98 | 01-SEP-14:10 | 83012.98 | 0.00 |
October | 0.00 | 0.00 | 0.147499E+11 | 0.100349E+11 | 57511.05 | 04-OCT-14:00 | 47418.09 | 0.00 |
November | 0.00 | 0.00 | 0.323565E+09 | 0.251285E+09 | 8313.02 | 04-NOV-12:30 | 6493.23 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.279869E+12 | 0.216969E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.772098E+11 | 0.613340E+11 | 115567.43 | 84470.95 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 1880.27 | 6600.52 | 31-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1908.76 | 6609.41 | 09-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1991.26 | 6553.81 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1771.27 | 6258.80 | 04-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1719.50 | 5924.72 | 01-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1646.00 | 5481.23 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1438.10 | 5118.25 | 07-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1559.94 | 4997.79 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1499.37 | 5229.11 | 27-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1588.42 | 5640.55 | 30-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1726.74 | 6062.36 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1760.53 | 6408.82 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 1706.37 | ||||
Minimum of Months | 0.00 | 0.00 | 1438.10 | 4997.79 | ||
Maximum of Months | 0.00 | 0.00 | 1991.26 | 6609.41 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139578E+10 | 0.30 | 2483.34 | 02-JAN-05:01 | 0.79 |
February | 0.121610E+10 | 0.29 | 1511.48 | 01-FEB-06:01 | 0.62 |
March | 0.152743E+10 | 0.31 | 2394.53 | 31-MAR-07:05 | 0.77 |
April | 0.177728E+10 | 0.32 | 4276.58 | 10-APR-05:03 | 1.06 |
May | 0.273570E+10 | 0.38 | 8250.73 | 30-MAY-15:10 | 1.59 |
June | 0.445774E+10 | 0.50 | 9752.08 | 19-JUN-06:03 | 1.76 |
July | 0.558759E+10 | 0.55 | 10776.81 | 10-JUL-04:02 | 1.88 |
August | 0.617747E+10 | 0.59 | 10776.81 | 03-AUG-06:03 | 1.88 |
September | 0.404714E+10 | 0.47 | 9935.84 | 05-SEP-07:10 | 1.79 |
October | 0.317263E+10 | 0.40 | 6477.72 | 05-OCT-15:50 | 1.36 |
November | 0.157875E+10 | 0.30 | 2891.64 | 02-NOV-12:07 | 0.85 |
December | 0.130786E+10 | 0.28 | 1511.48 | 01-DEC-07:01 | 0.62 |
Annual Sum or Average | 0.349815E+11 | 0.39 | |||
Minimum of Months | 0.121610E+10 | 0.28 | 1511.48 | 0.62 | |
Maximum of Months | 0.617747E+10 | 0.59 | 10776.81 | 1.88 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140488E+10 | 0.31 | 2410.16 | 02-JAN-05:01 | 0.83 |
February | 0.122383E+10 | 0.30 | 2410.16 | 01-FEB-07:01 | 0.83 |
March | 0.146488E+10 | 0.31 | 2410.16 | 01-MAR-07:01 | 0.83 |
April | 0.162773E+10 | 0.32 | 4554.90 | 10-APR-15:20 | 1.20 |
May | 0.255222E+10 | 0.40 | 9117.43 | 30-MAY-14:20 | 1.84 |
June | 0.420284E+10 | 0.52 | 8306.04 | 19-JUN-10:50 | 1.73 |
July | 0.521594E+10 | 0.57 | 9459.20 | 10-JUL-04:02 | 1.88 |
August | 0.581439E+10 | 0.61 | 9459.20 | 14-AUG-09:50 | 1.88 |
September | 0.325659E+10 | 0.44 | 8634.42 | 05-SEP-09:10 | 1.77 |
October | 0.232114E+10 | 0.37 | 5776.88 | 04-OCT-15:50 | 1.38 |
November | 0.130671E+10 | 0.29 | 2410.16 | 20-NOV-07:01 | 0.83 |
December | 0.127321E+10 | 0.29 | 2410.16 | 06-DEC-07:01 | 0.83 |
Annual Sum or Average | 0.316644E+11 | 0.39 | |||
Minimum of Months | 0.122383E+10 | 0.29 | 2410.16 | 0.83 | |
Maximum of Months | 0.581439E+10 | 0.61 | 9459.20 | 1.88 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159996E+10 | 0.33 | 2293.99 | 05-JAN-07:02 | 0.73 |
February | 0.136755E+10 | 0.32 | 2293.99 | 07-FEB-07:02 | 0.73 |
March | 0.143997E+10 | 0.30 | 2293.99 | 10-MAR-07:01 | 0.72 |
April | 0.153174E+10 | 0.29 | 3958.37 | 10-APR-15:20 | 0.98 |
May | 0.232520E+10 | 0.35 | 8983.27 | 30-MAY-14:10 | 1.62 |
June | 0.379610E+10 | 0.44 | 8730.91 | 19-JUN-13:40 | 1.58 |
July | 0.479542E+10 | 0.49 | 10482.49 | 10-JUL-04:02 | 1.78 |
August | 0.530033E+10 | 0.52 | 9720.25 | 14-AUG-14:50 | 1.69 |
September | 0.278195E+10 | 0.37 | 7745.22 | 05-SEP-15:10 | 1.47 |
October | 0.192370E+10 | 0.31 | 4994.96 | 04-OCT-15:40 | 1.12 |
November | 0.128781E+10 | 0.27 | 2293.99 | 15-NOV-07:01 | 0.72 |
December | 0.133994E+10 | 0.28 | 2293.99 | 04-DEC-06:01 | 0.72 |
Annual Sum or Average | 0.294897E+11 | 0.36 | |||
Minimum of Months | 0.128781E+10 | 0.27 | 2293.99 | 0.72 | |
Maximum of Months | 0.530033E+10 | 0.52 | 10482.49 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:03 | 0.22 | 0.22 | 57.41 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 56.64 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 56.20 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:02 | 0.22 | 0.22 | 55.53 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 56.10 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.62 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 56.94 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 56.10 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 56.59 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.51 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 56.48 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 56.52 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.53 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.51 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.22 | 57.22 | 1880.27 | 6600.52 | 31-JAN-12:08 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.07 | 57.07 | 1908.76 | 6609.41 | 09-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.62 | 56.62 | 1991.26 | 6553.81 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.01 | 56.01 | 1771.27 | 6258.80 | 04-APR-11:10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.65 | 56.65 | 1719.50 | 5924.72 | 01-MAY-11:08 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.03 | 57.03 | 1646.00 | 5481.23 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.29 | 57.29 | 1438.10 | 5118.25 | 07-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.53 | 56.53 | 1559.94 | 4997.79 | 31-AUG-11:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.91 | 56.91 | 1499.37 | 5229.11 | 27-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.88 | 56.88 | 1588.42 | 5640.55 | 30-OCT-11:06 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.91 | 56.91 | 1726.74 | 6062.36 | 30-NOV-12:13 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.92 | 56.92 | 1760.53 | 6408.82 | 29-DEC-12:10 |
Annual Sum or Average | 0.00 | 1706.37 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.01 | 56.01 | 1438.10 | 4997.79 | ||
Maximum of Months | 0.00 | 0.00 | 57.29 | 57.29 | 1991.26 | 6609.41 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.168356E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133171E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.798630E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.556845E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.745133E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.175120E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.243202E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.257102E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.140489E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.800800E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.555955E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.960948E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.155927E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.555955E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.257102E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.138990E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.958771E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.370985E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.313020E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.621249E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.160667E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.221692E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.230238E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.116087E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.588182E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.399616E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.758857E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.126874E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.313020E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.230238E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.240883E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.190193E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.813194E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.475461E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.625191E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.164633E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.229683E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.236236E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.113695E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.569953E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.871624E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.163807E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.167467E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.475461E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.240883E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139578E+10 | 0.00 | 0.247737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121610E+10 | 0.00 | 0.214720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152743E+10 | 0.436525E+09 | 0.105106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177728E+10 | 0.386519E+10 | 0.335825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.273570E+10 | 0.157491E+11 | 0.857485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.445774E+10 | 0.558415E+11 | 29671192.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.558759E+10 | 0.796705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.617747E+10 | 0.820188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.404714E+10 | 0.426499E+11 | 0.111276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317263E+10 | 0.182158E+11 | 0.648192E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157875E+10 | 0.397543E+09 | 0.625250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130786E+10 | 0.00 | 0.145708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349815E+11 | 0.298845E+12 | 0.825844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.617747E+10 | 0.820188E+11 | 0.247737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140488E+10 | 0.00 | 0.228570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122383E+10 | 0.00 | 0.188433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146488E+10 | 0.416154E+09 | 0.747027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162773E+10 | 0.387728E+10 | 0.157663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.255222E+10 | 0.149752E+11 | 3375730.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.420284E+10 | 0.508910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.521594E+10 | 0.722691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.581439E+10 | 0.723638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.325659E+10 | 0.358543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.232114E+10 | 0.152092E+11 | 0.134115E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130671E+10 | 0.361919E+09 | 0.592252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127321E+10 | 0.00 | 0.140775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316644E+11 | 0.266218E+12 | 0.708848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.581439E+10 | 0.723638E+11 | 0.228570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159996E+10 | 167525.54 | 0.334828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136755E+10 | 0.00 | 0.285165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143997E+10 | 0.433811E+09 | 0.120715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153174E+10 | 0.412568E+10 | 0.344847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232520E+10 | 0.157941E+11 | 56457696.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.379610E+10 | 0.539758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.479542E+10 | 0.772098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.530033E+10 | 0.767431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.278195E+10 | 0.365133E+11 | 125221.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192370E+10 | 0.147499E+11 | 0.513430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128781E+10 | 0.323565E+09 | 0.109144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133994E+10 | 0.00 | 0.231747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294897E+11 | 0.279869E+12 | 0.112178E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.530033E+10 | 0.772098E+11 | 0.334828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.139578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152743E+10 | 0.00 | 0.00 | 0.00 | 0.109833E+09 | 0.634904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177728E+10 | 0.00 | 0.00 | 0.00 | 0.959600E+09 | 0.283157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.273570E+10 | 0.00 | 0.00 | 0.00 | 0.385821E+10 | 0.857422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.445774E+10 | 0.00 | 0.00 | 0.00 | 0.130246E+11 | 29671192.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.558759E+10 | 0.00 | 0.00 | 0.00 | 0.187326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.617747E+10 | 0.00 | 0.00 | 0.00 | 0.195328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.404714E+10 | 0.00 | 0.00 | 0.00 | 0.989047E+10 | 0.111276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317263E+10 | 0.00 | 0.00 | 0.00 | 0.422014E+10 | 0.615234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157875E+10 | 0.00 | 0.00 | 0.00 | 0.107100E+09 | 0.387370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130786E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349815E+11 | 0.00 | 0.00 | 0.00 | 0.704353E+11 | 0.505103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.617747E+10 | 0.00 | 0.00 | 0.00 | 0.195328E+11 | 0.154398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140488E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146488E+10 | 0.00 | 0.00 | 0.00 | 0.104184E+09 | 0.214079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162773E+10 | 0.00 | 0.00 | 0.00 | 0.959115E+09 | 0.543361E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.255222E+10 | 0.00 | 0.00 | 0.00 | 0.365969E+10 | 575715.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.420284E+10 | 0.00 | 0.00 | 0.00 | 0.118638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.521594E+10 | 0.00 | 0.00 | 0.00 | 0.169533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.581439E+10 | 0.00 | 0.00 | 0.00 | 0.172094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.325659E+10 | 0.00 | 0.00 | 0.00 | 0.835215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.232114E+10 | 0.00 | 0.00 | 0.00 | 0.354913E+10 | 11551297.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130671E+10 | 0.00 | 0.00 | 0.00 | 97439673.12 | 0.259201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.316644E+11 | 0.00 | 0.00 | 0.00 | 0.627482E+11 | 0.324616E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.581439E+10 | 0.00 | 0.00 | 0.00 | 0.172094E+11 | 0.124941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.159996E+10 | 0.00 | 0.00 | 0.00 | 47150.77 | 0.224883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143997E+10 | 0.00 | 0.00 | 0.00 | 0.109370E+09 | 0.658260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153174E+10 | 0.00 | 0.00 | 0.00 | 0.102496E+10 | 0.219792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232520E+10 | 0.00 | 0.00 | 0.00 | 0.387819E+10 | 48511371.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.379610E+10 | 0.00 | 0.00 | 0.00 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.479542E+10 | 0.00 | 0.00 | 0.00 | 0.181729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.530033E+10 | 0.00 | 0.00 | 0.00 | 0.183233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.278195E+10 | 0.00 | 0.00 | 0.00 | 0.858738E+10 | 125221.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.192370E+10 | 0.00 | 0.00 | 0.00 | 0.348794E+10 | 0.287890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128781E+10 | 0.00 | 0.00 | 0.00 | 87658511.53 | 0.734077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294897E+11 | 0.00 | 0.00 | 0.00 | 0.663390E+11 | 0.716386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.530033E+10 | 0.00 | 0.00 | 0.00 | 0.183233E+11 | 0.224883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.105206E+11 | 0.00 | 0.00 | 3937664.95 | 0.00 | 0.587789E+09 | 0.336008E+10 | 0.00 | 0.28 |
February | 0.960371E+10 | 0.00 | 0.00 | 5929941.46 | 0.00 | 876426.66 | 0.470216E+10 | 0.00 | 0.29 |
March | 0.596851E+10 | 0.00 | 0.00 | 21133497.51 | 0.00 | 0.00 | 0.104808E+11 | 0.00 | 0.39 |
April | 0.293606E+10 | 11312333.19 | 0.00 | 25316416.66 | 0.00 | 0.00 | 0.125285E+11 | 0.00 | 0.57 |
May | 0.111177E+10 | 0.105945E+09 | 0.00 | 34881265.09 | 0.00 | 0.00 | 0.148198E+11 | 0.00 | 0.90 |
June | 0.342565E+09 | 0.342738E+10 | 0.00 | 14372399.72 | 85606294.11 | 0.00 | 0.316347E+10 | 0.00 | 0.63 |
July | 15799787.52 | 0.813160E+10 | 0.00 | 1082618.22 | 0.223961E+09 | 0.00 | 0.128411E+09 | 0.00 | 0.30 |
August | 0.166986E+09 | 0.633832E+10 | 0.00 | 12013561.68 | 0.179952E+09 | 0.00 | 0.147694E+10 | 0.00 | 0.53 |
September | 0.792945E+09 | 0.209364E+10 | 0.00 | 23908587.58 | 43027707.66 | 0.00 | 0.747882E+10 | 0.00 | 0.77 |
October | 0.154668E+10 | 0.171441E+09 | 0.00 | 38731135.93 | 53467.52 | 0.00 | 0.146370E+11 | 0.00 | 0.85 |
November | 0.355602E+10 | 0.00 | 0.00 | 24591088.53 | 0.00 | 0.00 | 0.129442E+11 | 0.00 | 0.47 |
December | 0.706259E+10 | 0.00 | 0.00 | 12626417.70 | 0.00 | 0.00 | 0.746333E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.436242E+11 | 0.202796E+11 | 0.00 | 0.218525E+09 | 0.532601E+09 | 0.588665E+09 | 0.931835E+11 | 0.00 | 0.53 |
Minimum of Months | 15799787.52 | 0.00 | 0.00 | 1082618.22 | 0.00 | 0.00 | 0.128411E+09 | 0.00 | 0.28 |
Maximum of Months | 0.105206E+11 | 0.813160E+10 | 0.00 | 38731135.93 | 0.223961E+09 | 0.587789E+09 | 0.148198E+11 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149219E+10 | 0.00 | 0.00 | 0.28 |
February | 0.128071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613204E+09 | 0.00 | 0.00 | 0.28 |
March | 0.130452E+11 | 0.00 | 0.00 | 298612.28 | 0.00 | 19436319.74 | 0.524482E+09 | 0.00 | 0.33 |
April | 0.745061E+10 | 3540787.15 | 0.00 | 5581848.96 | 1396211.17 | 2635202.59 | 0.377262E+10 | 0.00 | 0.41 |
May | 0.356005E+10 | 91469069.62 | 0.00 | 14713445.69 | 0.00 | 0.00 | 0.739587E+10 | 0.00 | 0.61 |
June | 0.366635E+09 | 0.269524E+10 | 0.00 | 9035432.11 | 79558836.99 | 0.00 | 0.203900E+10 | 0.00 | 0.45 |
July | 23301255.54 | 0.690885E+10 | 0.00 | 813815.64 | 0.209816E+09 | 0.00 | 86597207.93 | 0.00 | 0.25 |
August | 0.163745E+09 | 0.550817E+10 | 0.00 | 8089021.34 | 0.174949E+09 | 0.00 | 0.955464E+09 | 0.00 | 0.41 |
September | 0.134068E+10 | 0.175340E+10 | 0.00 | 11731066.90 | 42072858.96 | 0.00 | 0.397874E+10 | 0.00 | 0.52 |
October | 0.348101E+10 | 0.155954E+09 | 0.00 | 13741769.10 | 3929732.78 | 0.00 | 0.617757E+10 | 0.00 | 0.52 |
November | 0.985512E+10 | 0.00 | 0.00 | 1629911.34 | 0.00 | 86657409.03 | 0.175044E+10 | 0.00 | 0.33 |
December | 0.128624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121716E+09 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.773025E+11 | 0.171166E+11 | 0.00 | 65634923.34 | 0.511723E+09 | 0.233584E+10 | 0.266808E+11 | 0.00 | 0.39 |
Minimum of Months | 23301255.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.130452E+11 | 0.690885E+10 | 0.00 | 14713445.69 | 0.209816E+09 | 0.149219E+10 | 0.739587E+10 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.919815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381214E+10 | 0.00 | 0.00 | 0.27 |
February | 0.950370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307586E+10 | 0.00 | 0.00 | 0.27 |
March | 0.121895E+11 | 0.00 | 0.00 | 203530.17 | 0.00 | 0.577499E+09 | 0.367916E+09 | 0.00 | 0.33 |
April | 0.799412E+10 | 355060.69 | 0.00 | 4331381.96 | 2436947.16 | 98402234.90 | 0.292775E+10 | 0.00 | 0.42 |
May | 0.487263E+10 | 75260953.33 | 0.00 | 12577384.91 | 0.00 | 0.00 | 0.636863E+10 | 0.00 | 0.63 |
June | 0.589217E+09 | 0.257382E+10 | 0.00 | 8425842.90 | 79648536.23 | 0.00 | 0.205801E+10 | 0.00 | 0.48 |
July | 13315666.19 | 0.662415E+10 | 0.00 | 976408.27 | 0.199430E+09 | 0.00 | 85456252.83 | 0.00 | 0.25 |
August | 0.188686E+09 | 0.526875E+10 | 0.00 | 7599693.56 | 0.163543E+09 | 0.00 | 0.900640E+09 | 0.00 | 0.43 |
September | 0.193762E+10 | 0.167476E+10 | 0.00 | 8365499.88 | 93401711.00 | 0.00 | 0.310953E+10 | 0.00 | 0.51 |
October | 0.495478E+10 | 98196054.25 | 0.00 | 7841992.35 | 18013744.48 | 0.00 | 0.379361E+10 | 0.00 | 0.50 |
November | 0.963917E+10 | 0.00 | 0.00 | 226819.84 | 0.00 | 0.854185E+09 | 0.429885E+09 | 0.00 | 0.33 |
December | 0.100711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203101E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.711520E+11 | 0.163153E+11 | 0.00 | 50548553.83 | 0.556474E+09 | 0.104491E+11 | 0.200414E+11 | 0.00 | 0.39 |
Minimum of Months | 13315666.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.121895E+11 | 0.662415E+10 | 0.00 | 12577384.91 | 0.199430E+09 | 0.381214E+10 | 0.636863E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.350389E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258495E+10 | 0.00 | 0.00 | 0.28 |
February | 0.414393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241557E+10 | 0.00 | 0.00 | 0.29 |
March | 0.163027E+10 | 0.00 | 0.00 | 4930.30 | 0.00 | 0.115125E+10 | 22836889.93 | 0.00 | 0.33 |
April | 0.162936E+10 | 422894.92 | 0.00 | 933372.18 | 196531.00 | 0.283388E+09 | 0.446573E+09 | 0.00 | 0.43 |
May | 0.109484E+10 | 24044102.49 | 0.00 | 3373844.32 | 0.00 | 4161329.95 | 0.149660E+10 | 0.00 | 0.71 |
June | 0.130295E+09 | 0.813524E+09 | 0.00 | 2436177.61 | 15637094.55 | 0.00 | 0.557045E+09 | 0.00 | 0.64 |
July | 3791361.33 | 0.219757E+10 | 0.00 | 305383.99 | 23941311.40 | 0.00 | 22202357.47 | 0.00 | 0.38 |
August | 47994463.29 | 0.172733E+10 | 0.00 | 2060311.82 | 24924410.98 | 0.00 | 0.231882E+09 | 0.00 | 0.59 |
September | 0.513490E+09 | 0.428309E+09 | 0.00 | 1842070.70 | 26367608.15 | 0.00 | 0.612714E+09 | 0.00 | 0.57 |
October | 0.128543E+10 | 20682675.75 | 0.00 | 1133221.11 | 6596048.44 | 46183405.92 | 0.485337E+09 | 0.00 | 0.50 |
November | 0.129597E+10 | 0.00 | 0.00 | 2381.87 | 0.00 | 0.103223E+10 | 13789572.00 | 0.00 | 0.33 |
December | 0.445189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216659E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.884141E+10 | 0.521189E+10 | 0.00 | 12091693.90 | 97663004.52 | 0.968433E+10 | 0.388898E+10 | 0.00 | 0.45 |
Minimum of Months | 3791361.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.163027E+10 | 0.219757E+10 | 0.00 | 3373844.32 | 26367608.15 | 0.258495E+10 | 0.149660E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.590778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189540E+10 | 0.00 | 0.00 | 0.38 |
February | 0.878474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151792E+10 | 0.00 | 0.00 | 0.39 |
March | 0.160744E+10 | 0.00 | 0.00 | 246209.30 | 0.00 | 0.649829E+09 | 0.258266E+09 | 0.00 | 0.47 |
April | 0.122082E+10 | 1221431.67 | 0.00 | 1923034.17 | 0.00 | 0.209707E+09 | 0.972021E+09 | 0.00 | 0.72 |
May | 0.913123E+09 | 25393476.75 | 0.00 | 4458520.32 | 0.00 | 433560.92 | 0.187866E+10 | 0.00 | 1.18 |
June | 86775399.02 | 0.666802E+09 | 0.00 | 2804466.83 | 29640346.44 | 0.00 | 0.673085E+09 | 0.00 | 0.95 |
July | 1460844.28 | 0.184060E+10 | 0.00 | 358323.75 | 25540213.22 | 0.00 | 33349308.45 | 0.00 | 0.53 |
August | 31247159.92 | 0.157384E+10 | 0.00 | 2291521.63 | 18398334.92 | 0.00 | 0.292137E+09 | 0.00 | 0.92 |
September | 0.374842E+09 | 0.354993E+09 | 0.00 | 2732119.03 | 38908175.71 | 0.00 | 0.826298E+09 | 0.00 | 0.90 |
October | 0.838893E+09 | 18015132.04 | 0.00 | 2155779.78 | 7027787.92 | 25406019.97 | 0.931172E+09 | 0.00 | 0.82 |
November | 0.135215E+10 | 0.00 | 0.00 | 60757.32 | 0.00 | 0.640732E+09 | 75532412.76 | 0.00 | 0.46 |
December | 0.850080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144468E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.874608E+10 | 0.448087E+10 | 0.00 | 17030732.13 | 0.119515E+09 | 0.638410E+10 | 0.594052E+10 | 0.00 | 0.68 |
Minimum of Months | 1460844.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.160744E+10 | 0.184060E+10 | 0.00 | 4458520.32 | 38908175.71 | 0.189540E+10 | 0.187866E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.999210E+09 | 0.00 | 0.00 | 869581.46 | 0.00 | 0.176616E+10 | 0.535128E+09 | 0.00 | 0.32 |
February | 0.111955E+10 | 0.00 | 0.00 | 1345276.86 | 0.00 | 0.142774E+10 | 0.772392E+09 | 0.00 | 0.34 |
March | 0.161588E+10 | 0.00 | 0.00 | 3617464.43 | 0.00 | 0.628121E+09 | 0.189898E+10 | 0.00 | 0.51 |
April | 0.137861E+10 | 1406985.58 | 0.00 | 3949626.53 | 0.00 | 0.265588E+09 | 0.191283E+10 | 0.00 | 0.69 |
May | 0.118952E+10 | 29987576.36 | 0.00 | 5405627.67 | 249361.98 | 8043289.10 | 0.225181E+10 | 0.00 | 0.94 |
June | 0.158681E+09 | 0.910561E+09 | 0.00 | 2945274.24 | 24206354.34 | 0.00 | 0.674012E+09 | 0.00 | 0.75 |
July | 5161488.65 | 0.250687E+10 | 0.00 | 374441.81 | 28152415.46 | 0.00 | 22332799.67 | 0.00 | 0.44 |
August | 50067386.60 | 0.228179E+10 | 0.00 | 3382828.33 | 25852243.78 | 0.00 | 0.362084E+09 | 0.00 | 0.84 |
September | 0.422843E+09 | 0.640786E+09 | 0.00 | 6225738.71 | 23968449.28 | 0.00 | 0.169193E+10 | 0.00 | 1.03 |
October | 0.740681E+09 | 61634140.01 | 0.00 | 8204996.79 | 1788383.45 | 21061158.67 | 0.327707E+10 | 0.00 | 1.14 |
November | 0.134394E+10 | 0.00 | 0.00 | 2622743.57 | 0.00 | 0.603355E+09 | 0.135220E+10 | 0.00 | 0.50 |
December | 0.108912E+10 | 0.00 | 0.00 | 1160698.81 | 0.00 | 0.139827E+10 | 0.601216E+09 | 0.00 | 0.32 |
Annual Sum or Average | 0.101133E+11 | 0.643303E+10 | 0.00 | 40104299.22 | 0.104217E+09 | 0.611835E+10 | 0.153520E+11 | 0.00 | 0.65 |
Minimum of Months | 5161488.65 | 0.00 | 0.00 | 374441.81 | 0.00 | 0.00 | 22332799.67 | 0.00 | 0.32 |
Maximum of Months | 0.161588E+10 | 0.250687E+10 | 0.00 | 8204996.79 | 28152415.46 | 0.176616E+10 | 0.327707E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.641802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205656E+10 | 0.00 | 0.00 | 0.42 |
February | 0.695367E+09 | 0.00 | 0.00 | 40114.87 | 0.00 | 0.184366E+10 | 71128055.21 | 0.00 | 0.42 |
March | 0.149155E+10 | 0.00 | 0.00 | 876182.08 | 0.00 | 0.816806E+09 | 0.537316E+09 | 0.00 | 0.54 |
April | 0.136064E+10 | 97205.72 | 0.00 | 2312848.66 | 495700.53 | 0.256266E+09 | 0.107978E+10 | 0.00 | 0.80 |
May | 0.111151E+10 | 22859857.90 | 0.00 | 4187071.09 | 549997.28 | 7921366.10 | 0.167693E+10 | 0.00 | 1.19 |
June | 0.130716E+09 | 0.693016E+09 | 0.00 | 2497544.72 | 30098826.93 | 0.00 | 0.533329E+09 | 0.00 | 0.95 |
July | 4644033.56 | 0.186196E+10 | 0.00 | 306453.76 | 22821721.88 | 0.00 | 14285108.22 | 0.00 | 0.52 |
August | 53659544.28 | 0.161458E+10 | 0.00 | 2034062.64 | 23096455.46 | 0.00 | 0.199450E+09 | 0.00 | 0.91 |
September | 0.490579E+09 | 0.387493E+09 | 0.00 | 2601864.87 | 39780527.08 | 0.00 | 0.712683E+09 | 0.00 | 0.94 |
October | 0.111732E+10 | 28997394.40 | 0.00 | 2112955.72 | 4912679.36 | 41919757.80 | 0.881133E+09 | 0.00 | 0.90 |
November | 0.128843E+10 | 0.00 | 0.00 | 179704.22 | 0.00 | 0.841984E+09 | 0.133802E+09 | 0.00 | 0.51 |
December | 0.688173E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179542E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.907439E+10 | 0.460900E+10 | 0.00 | 17148802.62 | 0.121756E+09 | 0.766054E+10 | 0.583983E+10 | 0.00 | 0.71 |
Minimum of Months | 4644033.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.149155E+10 | 0.186196E+10 | 0.00 | 4187071.09 | 39780527.08 | 0.205656E+10 | 0.167693E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.626675E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251118E+10 | 0.00 | 0.00 | 0.29 |
February | 0.573311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245405E+10 | 0.00 | 0.00 | 0.29 |
March | 0.206492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908653E+09 | 0.00 | 0.00 | 0.33 |
April | 0.202058E+10 | 589893.84 | 0.00 | 130965.76 | 998614.35 | 0.182527E+09 | 0.122132E+09 | 0.00 | 0.39 |
May | 0.148088E+10 | 17830289.18 | 0.00 | 1326663.48 | 0.00 | 336828.43 | 0.629164E+09 | 0.00 | 0.56 |
June | 0.160048E+09 | 0.594612E+09 | 0.00 | 1575808.41 | 26324329.57 | 0.00 | 0.360116E+09 | 0.00 | 0.47 |
July | 9843371.98 | 0.166585E+10 | 0.00 | 176636.22 | 34215250.10 | 0.00 | 15176514.37 | 0.00 | 0.28 |
August | 75334273.87 | 0.136991E+10 | 0.00 | 1686854.02 | 25568309.16 | 0.00 | 0.187990E+09 | 0.00 | 0.46 |
September | 0.477077E+09 | 0.356966E+09 | 0.00 | 2153161.03 | 9030305.56 | 0.00 | 0.693349E+09 | 0.00 | 0.55 |
October | 0.134833E+10 | 24958346.68 | 0.00 | 1652774.95 | 831058.36 | 0.00 | 0.744399E+09 | 0.00 | 0.52 |
November | 0.213897E+10 | 0.00 | 0.00 | 13735.28 | 0.00 | 0.444327E+09 | 28710997.39 | 0.00 | 0.34 |
December | 0.134356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152850E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.123195E+11 | 0.403072E+10 | 0.00 | 8716599.14 | 96967867.09 | 0.802958E+10 | 0.278104E+10 | 0.00 | 0.40 |
Minimum of Months | 9843371.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.213897E+10 | 0.166585E+10 | 0.00 | 2153161.03 | 34215250.10 | 0.251118E+10 | 0.744399E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.783170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151014E+10 | 0.00 | 0.00 | 0.33 |
February | 0.924272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129474E+10 | 0.00 | 0.00 | 0.33 |
March | 0.180134E+10 | 0.00 | 0.00 | 105764.04 | 0.00 | 0.328886E+09 | 93821822.98 | 0.00 | 0.39 |
April | 0.122701E+10 | 2194503.85 | 0.00 | 1294359.80 | 0.00 | 93832992.57 | 0.637780E+09 | 0.00 | 0.55 |
May | 0.807843E+09 | 21374877.45 | 0.00 | 3019020.94 | 0.00 | 0.00 | 0.124607E+10 | 0.00 | 0.89 |
June | 70990988.17 | 0.522548E+09 | 0.00 | 2133082.77 | 20665216.09 | 0.00 | 0.515316E+09 | 0.00 | 0.73 |
July | 3111442.48 | 0.147640E+10 | 0.00 | 234503.95 | 22774091.42 | 0.00 | 26376932.03 | 0.00 | 0.41 |
August | 49472285.15 | 0.131365E+10 | 0.00 | 2042170.41 | 16027043.24 | 0.00 | 0.250949E+09 | 0.00 | 0.76 |
September | 0.248859E+09 | 0.319293E+09 | 0.00 | 3105315.80 | 7480102.42 | 0.00 | 0.938133E+09 | 0.00 | 0.86 |
October | 0.663671E+09 | 24617731.16 | 0.00 | 3353442.70 | 111552.25 | 0.00 | 0.134258E+10 | 0.00 | 0.83 |
November | 0.139114E+10 | 0.00 | 0.00 | 448234.78 | 0.00 | 0.230541E+09 | 0.356032E+09 | 0.00 | 0.41 |
December | 0.131913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.821566E+09 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.929001E+10 | 0.368007E+10 | 0.00 | 15735895.19 | 67058005.41 | 0.427971E+10 | 0.540705E+10 | 0.00 | 0.57 |
Minimum of Months | 3111442.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.180134E+10 | 0.147640E+10 | 0.00 | 3353442.70 | 22774091.42 | 0.151014E+10 | 0.134258E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.593374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351284E+10 | 0.00 | 0.00 | 0.37 |
February | 0.643365E+09 | 0.00 | 0.00 | 19819.03 | 0.00 | 0.332971E+10 | 28965210.18 | 0.00 | 0.37 |
March | 0.135423E+10 | 0.00 | 0.00 | 171600.35 | 0.00 | 0.214598E+10 | 0.143296E+09 | 0.00 | 0.40 |
April | 0.139229E+10 | 4264991.03 | 0.00 | 757196.22 | 0.00 | 0.104957E+10 | 0.335582E+09 | 0.00 | 0.49 |
May | 0.152168E+10 | 28649214.98 | 0.00 | 1224617.54 | 185029.02 | 0.335326E+09 | 0.461222E+09 | 0.00 | 0.63 |
June | 0.212499E+09 | 0.732568E+09 | 0.00 | 1350089.74 | 53438192.25 | 18365260.66 | 0.291302E+09 | 0.00 | 0.52 |
July | 12073470.20 | 0.227151E+10 | 0.00 | 191545.16 | 48499753.23 | 0.00 | 12228116.98 | 0.00 | 0.37 |
August | 91811902.18 | 0.227962E+10 | 0.00 | 2562988.72 | 29889904.23 | 0.00 | 0.242285E+09 | 0.00 | 0.73 |
September | 0.397918E+09 | 0.581293E+09 | 0.00 | 4854787.38 | 24531656.98 | 44931037.11 | 0.129661E+10 | 0.00 | 0.88 |
October | 0.740764E+09 | 66483486.55 | 0.00 | 6209154.69 | 861759.23 | 0.245202E+09 | 0.249500E+10 | 0.00 | 0.97 |
November | 0.140769E+10 | 0.00 | 0.00 | 880706.44 | 0.00 | 0.136384E+10 | 0.580534E+09 | 0.00 | 0.45 |
December | 0.989126E+09 | 0.00 | 0.00 | 90924.09 | 0.00 | 0.254480E+10 | 66635029.30 | 0.00 | 0.34 |
Annual Sum or Average | 0.935683E+10 | 0.596439E+10 | 0.00 | 18313429.35 | 0.157406E+09 | 0.145906E+11 | 0.595366E+10 | 0.00 | 0.54 |
Minimum of Months | 12073470.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.152168E+10 | 0.227962E+10 | 0.00 | 6209154.69 | 53438192.25 | 0.351284E+10 | 0.249500E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.745564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162332E+10 | 0.00 | 0.00 | 0.34 |
February | 0.802239E+09 | 0.00 | 0.00 | 2193.15 | 0.00 | 0.147623E+10 | 10511179.88 | 0.00 | 0.34 |
March | 0.174342E+10 | 0.00 | 0.00 | 346412.08 | 0.00 | 0.362464E+09 | 0.206143E+09 | 0.00 | 0.41 |
April | 0.132162E+10 | 949982.89 | 0.00 | 1281970.49 | 466202.15 | 97123393.13 | 0.591794E+09 | 0.00 | 0.57 |
May | 0.905258E+09 | 19886904.90 | 0.00 | 2566777.17 | 0.00 | 257394.60 | 0.103588E+10 | 0.00 | 0.85 |
June | 96257312.24 | 0.593710E+09 | 0.00 | 1792251.22 | 8019912.84 | 0.00 | 0.392866E+09 | 0.00 | 0.73 |
July | 7100748.16 | 0.153492E+10 | 0.00 | 145015.00 | 13527510.25 | 0.00 | 11094367.74 | 0.00 | 0.40 |
August | 53088417.86 | 0.139660E+10 | 0.00 | 1753994.79 | 13914498.27 | 0.00 | 0.172131E+09 | 0.00 | 0.74 |
September | 0.311595E+09 | 0.352711E+09 | 0.00 | 2680335.02 | 3780748.77 | 0.00 | 0.767162E+09 | 0.00 | 0.83 |
October | 0.749521E+09 | 33811690.47 | 0.00 | 3060621.59 | 73223.47 | 0.00 | 0.122880E+10 | 0.00 | 0.83 |
November | 0.155312E+10 | 0.00 | 0.00 | 266859.35 | 0.00 | 0.289691E+09 | 0.196518E+09 | 0.00 | 0.42 |
December | 0.123164E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964178E+09 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.952043E+10 | 0.393259E+10 | 0.00 | 13896429.86 | 39782095.74 | 0.481327E+10 | 0.461290E+10 | 0.00 | 0.57 |
Minimum of Months | 7100748.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.174342E+10 | 0.153492E+10 | 0.00 | 3060621.59 | 13914498.27 | 0.162332E+10 | 0.122880E+10 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.673136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233638E+10 | 0.00 | 0.00 | 0.28 |
February | 0.809490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209265E+10 | 0.00 | 0.00 | 0.28 |
March | 0.228420E+10 | 0.00 | 0.00 | 10588.34 | 0.00 | 0.566975E+09 | 24804464.49 | 0.00 | 0.33 |
April | 0.183016E+10 | 1274933.65 | 0.00 | 933441.32 | 0.00 | 78179483.14 | 0.456912E+09 | 0.00 | 0.42 |
May | 0.939217E+09 | 30184398.07 | 0.00 | 3686667.93 | 0.00 | 0.00 | 0.153803E+10 | 0.00 | 0.69 |
June | 82902379.99 | 0.883271E+09 | 0.00 | 2417314.27 | 10476634.06 | 0.00 | 0.528799E+09 | 0.00 | 0.61 |
July | 4554604.10 | 0.233427E+10 | 0.00 | 228420.10 | 28429163.70 | 0.00 | 22576440.38 | 0.00 | 0.38 |
August | 46697408.66 | 0.184560E+10 | 0.00 | 1957380.75 | 21905119.82 | 0.00 | 0.217809E+09 | 0.00 | 0.56 |
September | 0.461774E+09 | 0.462060E+09 | 0.00 | 2218291.90 | 10276115.93 | 0.00 | 0.679372E+09 | 0.00 | 0.58 |
October | 0.122889E+10 | 37634792.31 | 0.00 | 1650991.98 | 2009020.53 | 554880.69 | 0.686953E+09 | 0.00 | 0.51 |
November | 0.186236E+10 | 0.00 | 0.00 | 24812.38 | 0.00 | 0.581648E+09 | 25860167.54 | 0.00 | 0.33 |
December | 0.114189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161025E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.113653E+11 | 0.559429E+10 | 0.00 | 13127908.97 | 73096054.05 | 0.726664E+10 | 0.418111E+10 | 0.00 | 0.44 |
Minimum of Months | 4554604.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.228420E+10 | 0.233427E+10 | 0.00 | 3686667.93 | 28429163.70 | 0.233638E+10 | 0.153803E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.936362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170164E+10 | 0.00 | 0.00 | 0.39 |
February | 0.121186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134489E+10 | 0.00 | 0.00 | 0.40 |
March | 0.198853E+10 | 0.00 | 0.00 | 389078.68 | 0.00 | 0.315001E+09 | 0.339069E+09 | 0.00 | 0.48 |
April | 0.140702E+10 | 1885803.94 | 0.00 | 2029707.18 | 0.00 | 59343375.98 | 0.990176E+09 | 0.00 | 0.71 |
May | 0.838891E+09 | 28821395.21 | 0.00 | 4455293.20 | 0.00 | 0.00 | 0.184801E+10 | 0.00 | 1.14 |
June | 66968342.81 | 0.712616E+09 | 0.00 | 2581518.18 | 15331929.55 | 0.00 | 0.625152E+09 | 0.00 | 0.88 |
July | 4088511.27 | 0.191599E+10 | 0.00 | 268663.90 | 25596477.68 | 0.00 | 30749371.00 | 0.00 | 0.52 |
August | 39717210.86 | 0.162373E+10 | 0.00 | 2208713.09 | 20235072.53 | 0.00 | 0.280079E+09 | 0.00 | 0.87 |
September | 0.366581E+09 | 0.369785E+09 | 0.00 | 2970393.94 | 21048109.27 | 0.00 | 0.865491E+09 | 0.00 | 0.89 |
October | 0.857881E+09 | 32283703.91 | 0.00 | 2639783.90 | 1811531.08 | 784242.93 | 0.110958E+10 | 0.00 | 0.83 |
November | 0.163943E+10 | 0.00 | 0.00 | 214045.71 | 0.00 | 0.400622E+09 | 0.187735E+09 | 0.00 | 0.47 |
December | 0.129112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117639E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.106484E+11 | 0.468511E+10 | 0.00 | 17757197.78 | 84023120.10 | 0.499867E+10 | 0.627604E+10 | 0.00 | 0.66 |
Minimum of Months | 4088511.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.198853E+10 | 0.191599E+10 | 0.00 | 4455293.20 | 25596477.68 | 0.170164E+10 | 0.184801E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.133689E+10 | 0.00 | 0.00 | 1231061.36 | 0.00 | 0.128756E+10 | 0.718890E+09 | 0.00 | 0.32 |
February | 0.144209E+10 | 0.00 | 0.00 | 1739350.74 | 0.00 | 0.102276E+10 | 0.989876E+09 | 0.00 | 0.34 |
March | 0.184495E+10 | 0.00 | 0.00 | 4128151.65 | 0.00 | 0.295864E+09 | 0.197767E+10 | 0.00 | 0.50 |
April | 0.145667E+10 | 3518207.80 | 0.00 | 4009731.42 | 0.00 | 67647327.29 | 0.184431E+10 | 0.00 | 0.66 |
May | 0.923490E+09 | 39254645.37 | 0.00 | 5455182.33 | 0.00 | 0.00 | 0.220736E+10 | 0.00 | 0.89 |
June | 0.108657E+09 | 0.100947E+10 | 0.00 | 2735801.18 | 10247544.14 | 0.00 | 0.592376E+09 | 0.00 | 0.70 |
July | 7099112.52 | 0.270247E+10 | 0.00 | 249830.92 | 27109545.00 | 0.00 | 19849971.76 | 0.00 | 0.43 |
August | 48610784.92 | 0.248727E+10 | 0.00 | 3007361.91 | 21369658.09 | 0.00 | 0.303016E+09 | 0.00 | 0.79 |
September | 0.331728E+09 | 0.699596E+09 | 0.00 | 6407982.28 | 7573179.93 | 0.00 | 0.164890E+10 | 0.00 | 1.01 |
October | 0.665476E+09 | 0.106550E+09 | 0.00 | 9137892.28 | 22067.57 | 0.00 | 0.348090E+10 | 0.00 | 1.14 |
November | 0.149680E+10 | 0.00 | 0.00 | 3596522.54 | 0.00 | 0.262194E+09 | 0.179666E+10 | 0.00 | 0.52 |
December | 0.148762E+10 | 0.00 | 0.00 | 1687711.71 | 0.00 | 0.887025E+09 | 0.895869E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.111501E+11 | 0.704814E+10 | 0.00 | 43386580.32 | 66321994.73 | 0.382305E+10 | 0.164757E+11 | 0.00 | 0.64 |
Minimum of Months | 7099112.52 | 0.00 | 0.00 | 249830.92 | 0.00 | 0.00 | 19849971.76 | 0.00 | 0.32 |
Maximum of Months | 0.184495E+10 | 0.270247E+10 | 0.00 | 9137892.28 | 27109545.00 | 0.128756E+10 | 0.348090E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.892063E+09 | 0.00 | 0.00 | 3664.48 | 0.00 | 0.180526E+10 | 12583016.52 | 0.00 | 0.40 |
February | 0.100339E+10 | 0.00 | 0.00 | 73487.71 | 0.00 | 0.154427E+10 | 82357166.47 | 0.00 | 0.41 |
March | 0.190908E+10 | 0.00 | 0.00 | 988775.20 | 0.00 | 0.373005E+09 | 0.533424E+09 | 0.00 | 0.52 |
April | 0.149263E+10 | 1110476.94 | 0.00 | 2268942.57 | 71563.92 | 79221676.85 | 0.993235E+09 | 0.00 | 0.75 |
May | 0.883448E+09 | 30655777.90 | 0.00 | 4121126.92 | 0.00 | 316220.80 | 0.165159E+10 | 0.00 | 1.11 |
June | 0.105921E+09 | 0.784636E+09 | 0.00 | 2199545.96 | 8877120.34 | 0.00 | 0.455901E+09 | 0.00 | 0.89 |
July | 7096402.06 | 0.201851E+10 | 0.00 | 178438.67 | 12597814.66 | 0.00 | 12189706.66 | 0.00 | 0.51 |
August | 51594916.46 | 0.176561E+10 | 0.00 | 1770395.34 | 10519738.19 | 0.00 | 0.173490E+09 | 0.00 | 0.86 |
September | 0.425333E+09 | 0.426719E+09 | 0.00 | 2570425.79 | 13231047.73 | 0.00 | 0.709346E+09 | 0.00 | 0.90 |
October | 0.105052E+10 | 50793655.32 | 0.00 | 2436876.30 | 304053.21 | 510387.85 | 0.988917E+09 | 0.00 | 0.87 |
November | 0.161519E+10 | 0.00 | 0.00 | 265843.82 | 0.00 | 0.507417E+09 | 0.189978E+09 | 0.00 | 0.49 |
December | 0.121597E+10 | 0.00 | 0.00 | 1049.42 | 0.00 | 0.130755E+10 | 4572810.56 | 0.00 | 0.40 |
Annual Sum or Average | 0.106522E+11 | 0.507804E+10 | 0.00 | 16878572.17 | 45601338.04 | 0.561755E+10 | 0.580758E+10 | 0.00 | 0.68 |
Minimum of Months | 7096402.06 | 0.00 | 0.00 | 1049.42 | 0.00 | 0.00 | 4572810.56 | 0.00 | 0.40 |
Maximum of Months | 0.190908E+10 | 0.201851E+10 | 0.00 | 4121126.92 | 13231047.73 | 0.180526E+10 | 0.165159E+10 | 0.00 | 1.11 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.136440E+12 | 0.160625E+11 | 0.00 | 0.134110E+12 | 0.767301E+10 |
February | 0.210359E+12 | 0.153158E+11 | 0.00 | 0.138913E+12 | 0.767880E+10 |
March | 0.339264E+12 | 0.133789E+11 | 0.00 | 0.177346E+12 | 0.535486E+10 |
April | 0.357284E+12 | 0.837215E+10 | 0.00 | 0.187307E+12 | 0.155144E+11 |
May | 0.452616E+12 | 0.470875E+10 | 0.00 | 0.191098E+12 | 0.579171E+11 |
June | 0.435335E+12 | -0.119625E+10 | 0.00 | 0.332029E+11 | 0.198264E+12 |
July | 0.426902E+12 | -0.623347E+10 | 0.00 | -0.440365E+11 | 0.283008E+12 |
August | 0.414398E+12 | -0.446182E+10 | 0.00 | -0.955581E+10 | 0.286191E+12 |
September | 0.296003E+12 | 0.744789E+09 | 0.00 | 0.923385E+11 | 0.141847E+12 |
October | 0.291555E+12 | 0.614445E+10 | 0.00 | 0.197115E+12 | 0.595273E+11 |
November | 0.147112E+12 | 0.120883E+11 | 0.00 | 0.180023E+12 | 0.369597E+10 |
December | 0.110690E+12 | 0.141879E+11 | 0.00 | 0.148739E+12 | 0.554132E+10 |
Annual Sum or Average | 0.361796E+13 | 0.791119E+11 | 0.00 | 0.142660E+13 | 0.107221E+13 |
Minimum of Months | 0.110690E+12 | -0.623347E+10 | 0.00 | -0.440365E+11 | 0.369597E+10 |