Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:35:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1531.98 | 307.49 | 307.49 |
Net Site Energy | 1531.98 | 307.49 | 307.49 |
Total Source Energy | 4601.43 | 923.58 | 923.58 |
Net Source Energy | 4601.43 | 923.58 | 923.58 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 28.07 | 20.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 293.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 202.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 120.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 99.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1411.79 | 120.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 28.07 | 20.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 293.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 202.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 49.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 120.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 99.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 28.07 | 20.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 293.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 202.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 49.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 120.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 99.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 88.79 | 24.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 283.37 | 24.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 88.79 | 24.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 283.37 | 24.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1411.788 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1411.788 | 100.00 |
Total On-Site and Utility Electric Sources | 1411.788 | 100.00 |
Total Electricity End Uses | 1411.788 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 122.50 |
Time Setpoint Not Met During Occupied Cooling | 318.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1610.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.9322 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.9322 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.9322 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 20-JUL-15:09 | 27-DEC-07:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 0.00 | 46067.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73716.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 16818.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42072.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 827.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 33449.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8105.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 166885.61 | 54172.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 46067.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 73716.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 16818.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 827.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 33449.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8105.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 88.90 | 22.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 930.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 642.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 156.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 381.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 107.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4471.13 | 130.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 17.84 | 4.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 76.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 21.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 897.42 | 26.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 17.84 | 4.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 186.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 76.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 21.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 897.42 | 26.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.11 | 0.240972 | 0.255000 | 0.793085 | 0.642591 | 0.500000 | 0.001581 |
CORE_MID VAV BOX COMPONENT | 2.25 | 0.333199 | 0.339000 | 0.762503 | 0.888530 | 0.500000 | 0.001143 |
CORE_TOP VAV BOX COMPONENT | 2.45 | 0.305425 | 0.326000 | 0.799942 | 0.814467 | 0.500000 | 0.001247 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.810213 | 0.195000 | 0.208000 | 0.168524 | 0.520001 | 0.500000 | 0.001954 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.719713 | 0.138975 | 0.200000 | 0.143943 | 0.370599 | 0.500000 | 0.002742 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.898143 | 0.175909 | 0.200000 | 0.179629 | 0.469092 | 0.500000 | 0.002166 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.823949 | 0.121385 | 0.200000 | 0.164790 | 0.323694 | 0.500000 | 0.003139 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.652300 | 0.242207 | 0.256000 | 0.166989 | 0.645885 | 0.500000 | 0.001573 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.621439 | 0.160952 | 0.200000 | 0.124288 | 0.429205 | 0.500000 | 0.002367 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.729374 | 0.216613 | 0.229000 | 0.167027 | 0.577634 | 0.500000 | 0.001759 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.658418 | 0.151902 | 0.200000 | 0.131684 | 0.405073 | 0.500000 | 0.002508 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.687766 | 0.229717 | 0.234000 | 0.160937 | 0.612579 | 0.500000 | 0.001659 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.681495 | 0.146768 | 0.200000 | 0.136299 | 0.391382 | 0.500000 | 0.002596 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.773713 | 0.204199 | 0.208000 | 0.160932 | 0.544531 | 0.500000 | 0.001866 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.728986 | 0.137198 | 0.200000 | 0.145797 | 0.365861 | 0.500000 | 0.002777 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 22972.30 |
CORE_MID VAV BOX REHEAT COIL | 22086.48 |
CORE_TOP VAV BOX REHEAT COIL | 33728.46 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 14572.62 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9519.49 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 14480.51 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9465.52 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9943.16 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6591.54 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9863.71 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6539.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 10989.77 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 7239.09 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 10901.21 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 7190.17 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.89 | 1.38 | 5.77 | 1.56 | 5.30 | 5.30 | 0.300000 | 0.294438 | 5.30 |
PACU_VAV_MID | 2.56 | 1.37 | 5.12 | 1.89 | 4.58 | 4.58 | 0.300000 | 0.411834 | 4.58 |
PACU_VAV_TOP | 2.85 | 1.46 | 5.71 | 2.82 | 5.47 | 5.47 | 0.300000 | 0.515839 | 5.47 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.30 |
PACU_VAV_MID_OA_CONTROLLER | 4.58 |
PACU_VAV_TOP_OA_CONTROLLER | 5.47 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.30 | 95750.05 | 0.800152 | 1.77 | 31913.49 | 0.800152 |
PACU_VAV_MID COOLING COIL | 4.58 | 85174.17 | 0.800225 | 1.53 | 28388.55 | 0.800225 |
PACU_VAV_TOP COOLING COIL | 5.47 | 98306.17 | 0.800788 | 1.82 | 32765.45 | 0.800788 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 19522.58 |
PACU_VAV_MID HEATING COIL | 21352.85 |
PACU_VAV_TOP HEATING COIL | 18733.39 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.30 |
PACU_VAV_MID FAN | 4.58 |
PACU_VAV_TOP FAN | 5.47 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 30.766 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.9320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.9163 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.269 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8390 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8573 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5538 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27971961E-12 | 0.14534712E-14 | -0.84678956E-13 | 0.82684317E-16 |
43 | 6 | 0.26817376E-07 | 0.25687399E-09 | 0.61588016E-08 | -0.12527087E-12 |
44 | 5 | -0.18065003E-03 | 0.22251366E-05 | -0.93037841E-04 | 0.60936178E-08 |
45 | 4 | 0.28101542 | 0.10946024E-02 | 0.95683253E-01 | -0.32007147E-04 |
46 | 3 | -7.0457283 | 0.34231649E-01 | -2.2734647 | 0.27928366E-01 |
47 | 2 | 40.143429 | 0.12270019 | 14.996275 | -0.32523640 |
48 | 1 | -79.987958 | 0.55761501E-01 | -28.900564 | 1.0667320 |
49 | 0 | 46.824342 | 0.11295401E-02 | 16.297084 | |
50 | 7 | -0.28233695E-12 | 0.14433069E-14 | -0.85363548E-13 | 0.83491456E-16 |
51 | 6 | 0.27004714E-07 | 0.25312183E-09 | 0.62001510E-08 | -0.12627076E-12 |
52 | 5 | -0.18161011E-03 | 0.21898175E-05 | -0.93520278E-04 | 0.61339935E-08 |
53 | 4 | 0.28215201 | 0.10760039E-02 | 0.96091377E-01 | -0.32166146E-04 |
54 | 3 | -7.0682688 | 0.33616209E-01 | -2.2801509 | 0.28038740E-01 |
55 | 2 | 40.217804 | 0.12038787 | 15.023777 | -0.32606455 |
56 | 1 | -80.044990 | 0.54668782E-01 | -28.925243 | 1.0679473 |
57 | 0 | 46.824342 | 0.11065724E-02 | 16.296477 | |
58 | 6 | 0.22748378E-07 | 0.33059726E-09 | 0.52605359E-08 | -0.10371465E-12 |
59 | 5 | -0.15952455E-03 | 0.29533519E-05 | -0.82380770E-04 | 0.52144884E-08 |
60 | 4 | 0.25560578 | 0.14926938E-02 | 0.86578981E-01 | -0.28493712E-04 |
61 | 3 | -6.5408460 | 0.47808585E-01 | -2.1237636 | 0.25458881E-01 |
62 | 2 | 38.476406 | 0.17496760 | 14.378110 | -0.30668036 |
63 | 1 | -78.708466 | 0.80951212E-01 | -28.345189 | 1.0394692 |
64 | 0 | 46.824351 | 0.16689207E-02 | 16.311239 | |
65 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
66 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
67 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
68 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
69 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
70 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
71 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
72 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
73 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
74 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
75 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
76 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
77 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
78 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
79 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
80 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
81 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
82 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
83 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
84 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
85 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
86 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
87 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
88 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
89 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
90 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
91 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
92 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
93 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
94 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
95 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
96 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.4237_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.408 | 2.408 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.408 | 2.408 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.4237_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.408 | 2.408 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.408 | 2.408 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.98522E-002 | 0.16139 | 0.62038 | 0.62038 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.98522E-002 | 0.16139 | 0.62038 | 0.62038 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.98522E-002 | 0.16139 | 0.62038 | 0.62038 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.98522E-002 | 0.16139 | 0.62038 | 0.62038 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12245 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.384E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.394E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.384E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.394E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.424E-004 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.424E-004 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.550E-005 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9748E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0136E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4344E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4676E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5081E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5349E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4264E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4410E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.8825E-002 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1631E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.9549E-002 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5454E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.7940E-002 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7412E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8057E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0496E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9746E-003 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0143E-003 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4342E-003 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.4683E-003 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5080E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5354E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4263E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4409E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8344E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2455E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5360E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0268E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8445E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9254E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2668E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5265E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5074E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5219E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2707E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2812E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2101E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2137E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8320E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8371E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4475E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4803E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0579E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0837E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7986E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8165E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4263E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4409E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2669E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3239E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7575E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0121E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6766E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.1147E-003 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8057E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0496E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4476E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4804E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0579E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0837E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7985E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8161E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4264E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4410E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7407E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2015E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4220E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9730E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7581E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8857E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2668E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5265E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4564E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4930E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2084E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2471E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1632E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1804E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8321E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8372E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.7312E-002 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.0475E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.6119E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4917E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.1358E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4507E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.1564E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4627E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6900E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1650E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.4103E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9571E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7348E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.8661E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.1886E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4843E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5806E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7225E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0397E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3580E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.9567E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0311E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1564E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4627E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5999E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1238E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.3006E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9069E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6516E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8286E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1887E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4843E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.7313E-002 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.0471E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.6119E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4911E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.1355E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4503E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.1562E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4625E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6900E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1649E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.4103E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9570E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7346E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.8660E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.1884E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4841E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5807E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7225E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0398E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3579E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.9566E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0310E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1562E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4625E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6000E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1236E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.3006E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9067E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6514E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8284E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1884E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4842E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37425.60117 | 37425.60117 | 3.11014 | 3.11014 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 5652.90566 | 5652.90566 | 0.27493 | 0.42469 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27097.74031 | 27097.74031 | 2.24927 | 2.24927 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.48000 | 6.85626E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 12952.08721 | 12952.08721 | 0.63211 | 0.63211 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29289.87936 | 29289.87936 | 2.45381 | 2.45381 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 23750.30915 | 23750.30915 | 1.16443 | 1.16443 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9671.31944 | 9671.31944 | 0.81021 | 0.81021 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 37.84000 | 6.87107E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 10234.35279 | 10234.35279 | 0.50310 | 0.50310 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8591.08706 | 8591.08706 | 0.71971 | 0.71971 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6684.99504 | 6684.99504 | 0.32865 | 0.32865 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 10720.93143 | 10720.93143 | 0.89814 | 0.89814 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 10169.84397 | 10169.84397 | 0.49992 | 0.49992 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 9835.35325 | 9835.35325 | 0.82395 | 0.82395 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6647.19755 | 6647.19755 | 0.32678 | 0.32678 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7786.30432 | 7786.30432 | 0.65230 | 0.65230 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 6990.96228 | 6990.96228 | 0.34327 | 0.34327 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7417.97443 | 7417.97443 | 0.62144 | 0.62144 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 33.48500 | 6.86412E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 4633.67178 | 4633.67178 | 0.22756 | 0.22756 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 8706.31873 | 8706.31873 | 0.72937 | 0.72937 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 6935.32438 | 6935.32438 | 0.34053 | 0.34053 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 7859.37876 | 7859.37876 | 0.65842 | 0.65842 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 36.45333 | 6.86884E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 4596.86928 | 4596.86928 | 0.22575 | 0.22575 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 8209.67495 | 8209.67495 | 0.68777 | 0.68777 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 7724.61946 | 7724.61946 | 0.37941 | 0.37941 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8134.86804 | 8134.86804 | 0.68149 | 0.68149 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 32.79167 | 6.86302E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5087.60040 | 5087.60040 | 0.24992 | 0.24992 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9235.61778 | 9235.61778 | 0.77371 | 0.77371 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 7662.59857 | 7662.59857 | 0.37635 | 0.37635 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 8701.76979 | 8701.76979 | 0.72899 | 0.72899 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 36.62667 | 6.86912E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5053.33952 | 5053.33952 | 0.24823 | 0.24823 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20000 | 2.80840E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 79964.54 | 5.30437 | 5.30437 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 22519.51 | 1.56181 | 1.56181 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 71325.63 | 4.57955 | 4.57955 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 22347.16 | 1.88601 | 1.88601 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 81648.00 | 5.47239 | 5.47239 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 22395.87 | 2.82287 | 2.82287 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.11014 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24097 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25500 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79309 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64259 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.58110E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22972.30211 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.24927 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33320 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76250 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88853 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14346E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22086.47541 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.45381 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30543 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32600 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.79994 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81447 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24744E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 33728.46049 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81021 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19500 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20800 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16852 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52000 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.95384E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14572.62181 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71971 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13897 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14394 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37060 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74151E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9519.48775 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89814 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17591 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17963 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46909 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16589E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14480.51432 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82395 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12139 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16479 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32369 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.13877E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9465.52056 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65230 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24221 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16699 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64589 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57303E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9943.15619 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62144 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16095 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12429 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42920 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36717E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6591.54227 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72937 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21661 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22900 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16703 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57763 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.75890E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9863.71311 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65842 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15190 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13168 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40507 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.50819E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6538.99517 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68777 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22972 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23400 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16094 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61258 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.65856E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10989.77284 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68149 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14677 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13630 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39138 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59593E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7239.08701 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77371 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20420 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20800 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16093 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54453 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.86583E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10901.21486 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.72899 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13720 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14580 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36586 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77701E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7190.16729 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.88583 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.38307 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.77167 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.56181 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.30437 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.30437 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.29444 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.56062 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36647 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.12123 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.88601 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.57955 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.57955 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.41183 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.85291 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45683 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.70583 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.82287 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.47239 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.47239 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.51584 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.30437 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.57955 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.47239 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.30437 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.30437 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 95750.04734 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80015 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.76794 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31913.49078 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80015 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 19522.57853 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.30437 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.57955 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.57955 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 85174.17170 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80023 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.52636 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28388.55143 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80023 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 21352.84968 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.57955 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.47239 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.47239 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 98306.17373 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80079 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.82395 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32765.44771 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80079 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 18733.39468 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.47239 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 94473.53 | 322357.07 | 11.28 | 2.84 | 3.23 | 3.40 | 3.57 | 9.69 | 11.02 | 11.62 | 12.18 | 5.3207 | 4.2257 | 2.8386 | 1.1600 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 84146.08 | 287118.36 | 11.34 | 2.85 | 3.25 | 3.42 | 3.59 | 9.73 | 11.08 | 11.68 | 12.26 | 4.5937 | 3.6622 | 2.4635 | 0.9914 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 96975.15 | 330892.93 | 11.27 | 2.84 | 3.23 | 3.40 | 3.57 | 9.68 | 11.01 | 11.61 | 12.17 | 5.4893 | 4.3589 | 2.9270 | 1.1975 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_EAST_0.25 | N/A | 2.408 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.269 | 1.067 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_WEST_0.25 | N/A | 2.408 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_EAST_0.25 | N/A | 2.408 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_EAST_0.25 | N/A | 2.408 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.932 | 0.818 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_WEST_0.25 | N/A | 2.408 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_WEST_0.25 | N/A | 2.408 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_NORTH_0.25 | N/A | 2.408 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_EAST_0.25 | N/A | 2.408 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | N/A | 2.408 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.916 | 0.806 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4237_SHGC_WEST_0.25 | N/A | 2.408 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 6.3045818528E-002 | 0.1362357972 | Pass | Pass | 9.1797788356E-002 | 0.2867701886 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.4133806054E-002 | 7.8486554734E-002 | Pass | Pass | 6.1105335391E-002 | 0.3000366569 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.1910555851E-002 | 2.4247422030E-002 | Pass | Pass | 0.1569587509 | 0.5585434866 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2118840357E-002 | 2.9033602579E-002 | Pass | Pass | 3.3651102455 | 30.8864681112 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.8230581364E-002 | 0.1011413147 | Pass | Pass | 7.6971380457E-002 | 0.2651996454 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.5331759341E-002 | 8.2811606472E-002 | Pass | Pass | 4.8720710202E-002 | 0.2132836182 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.6845152614E-002 | 6.1453268685E-002 | Pass | Pass | 4.8550073502E-002 | 0.2124310893 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.3713942703E-002 | 0.1106693493 | Pass | Pass | 4.8843762793E-002 | 0.2149151862 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1503317357 | 0.1601590363 | Pass | Pass | 5.5823271772E-002 | 0.2399744383 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1054136012 | 0.1474036630 | Pass | Pass | 4.6469458150E-002 | 0.2050164556 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.4942353973E-002 | 8.2188263485E-002 | Pass | Pass | 9.1239156598E-002 | 0.2859422422 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.2346276418E-002 | 0.1194322917 | Pass | Pass | 9.2125674133E-002 | 0.2881094429 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1317012757 | 0.1959557894 | Pass | Pass | 9.2017991267E-002 | 0.2884425837 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.8420055524E-002 | 0.1462650473 | Pass | Pass | 8.9298809523E-002 | 0.2806140545 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.4562014018E-002 | 7.8571373873E-002 | Pass | Pass | 7.6754881936E-002 | 0.2643059202 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.0705180156E-002 | 0.1302017419 | Pass | Pass | 7.7537785489E-002 | 0.2672992897 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1460243913 | 0.1668816591 | Pass | Pass | 8.7340126379E-002 | 0.2949387410 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.9162729359E-002 | 0.1594167756 | Pass | Pass | 7.4687277652E-002 | 0.2586229540 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3318.95 | 28.17 | 0.00 | 1232.84 | 1400.82 | 5980.80 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.067 | 1.269 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.818 | 0.932 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.806 | 0.916 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.408 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4237_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.408 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.408 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4237_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.408 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.4237_SHGC_EAST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.4237_SHGC_EAST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.4237_SHGC_WEST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.4237_SHGC_WEST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.408 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4237_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.408 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4237_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.408 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4237_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.408 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4237_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.408 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.408 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 177.99 | 2.408 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.408 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.96 | 0.0000 | Y | 5.99 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.80 | 0.0000 | Y | 3.77 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.34 | 0.0000 | Y | 5.85 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.49 | 0.0000 | Y | 3.73 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.86 | 0.0000 | Y | 5.97 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.74 | 0.0000 | Y | 3.76 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.30 | 0.0000 | Y | 5.84 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.42 | 0.0000 | Y | 3.72 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.96 | 0.0000 | Y | 5.99 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.80 | 0.0000 | Y | 3.77 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.34 | 0.0000 | Y | 5.85 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.49 | 0.0000 | Y | 3.73 |
Interior Lighting Total | 5.9322 | 4982.19 | 29555.08 | 202.97 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 41.77 | 41.77 | 3.33 | |
EXTERIOR_LIGHTS_B | 408.47 | AstronomicalClock | - | 83.77 | 62.77 | 4.81 | |
EXTERIOR_LIGHTS_C | 4724.13 | AstronomicalClock | - | 83.77 | 46.49 | 41.22 | |
Exterior Lighting Total | 5557.43 | 49.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 95750.05 | 76614.64 | 19135.41 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 85174.17 | 68158.54 | 17015.63 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 98306.17 | 78722.43 | 19583.74 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 94473.5 | 2.84 | 9.69 | N/A | N/A | 11.28 | |
PACU_VAV_MID COOLING COIL | 84146.1 | 2.85 | 9.73 | N/A | N/A | 11.34 | |
PACU_VAV_TOP COOLING COIL | 96975.1 | 2.84 | 9.68 | N/A | N/A | 11.27 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 22972.30 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 22086.48 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 33728.46 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14572.62 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9519.49 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14480.51 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9465.52 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9943.16 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6591.54 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9863.71 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6539.00 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10989.77 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7239.09 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10901.21 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7190.17 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 19522.58 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 21352.85 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 18733.39 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.30 | 11536.40 | 2174.89 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.58 | 10024.69 | 2189.01 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.47 | 11901.84 | 2174.89 | 1.00 | 1.14 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 94473.53 | 2.84 | 9.69 | 11.28 | 5.3207 | 3.23 | 11.02 | 4.2257 | 3.40 | 11.62 | 2.8386 | 3.57 | 12.18 | 1.1600 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 84146.08 | 2.85 | 9.73 | 11.34 | 4.5937 | 3.25 | 11.08 | 3.6622 | 3.42 | 11.68 | 2.4635 | 3.59 | 12.26 | 0.9914 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96975.15 | 2.84 | 9.68 | 11.27 | 5.4893 | 3.23 | 11.01 | 4.3589 | 3.40 | 11.61 | 2.9270 | 3.57 | 12.17 | 1.1975 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37425.60 | 37425.60 | 38.05 | 3.110 | 3.110 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 28.48 | 0.00686 | 0.425 | 0.00 |
CORE_MID | 27097.74 | 27097.74 | 27.55 | 2.249 | 2.249 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.48 | 0.00686 | 0.425 | 0.00 |
CORE_TOP | 29289.88 | 29289.88 | 29.78 | 2.454 | 2.454 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00891 | 37.84 | 0.00687 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9671.32 | 9671.32 | 46.65 | 0.810 | 0.810 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00875 | 37.84 | 0.00687 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8591.09 | 8591.09 | 65.45 | 0.720 | 0.720 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00867 | 33.48 | 0.00686 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10720.93 | 10720.93 | 51.71 | 0.898 | 0.898 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00872 | 38.10 | 0.00687 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9835.35 | 9835.35 | 74.93 | 0.824 | 0.824 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00865 | 36.63 | 0.00687 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7786.30 | 7786.30 | 37.55 | 0.652 | 0.652 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00881 | 37.97 | 0.00687 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7417.97 | 7417.97 | 56.51 | 0.621 | 0.621 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00871 | 33.48 | 0.00686 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 8706.32 | 8706.32 | 41.99 | 0.729 | 0.729 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00878 | 37.99 | 0.00687 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7859.38 | 7859.38 | 59.88 | 0.658 | 0.658 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00870 | 36.45 | 0.00687 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 8209.67 | 8209.67 | 39.60 | 0.688 | 0.688 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00879 | 37.97 | 0.00687 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8134.87 | 8134.87 | 61.97 | 0.681 | 0.681 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00869 | 32.79 | 0.00686 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9235.62 | 9235.62 | 44.54 | 0.774 | 0.774 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00876 | 37.99 | 0.00687 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8701.77 | 8701.77 | 66.30 | 0.729 | 0.729 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00867 | 36.63 | 0.00687 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 5652.91 | 5652.91 | 5.75 | 0.275 | 0.425 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
CORE_MID | 12952.09 | 12952.09 | 13.17 | 0.632 | 0.632 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
CORE_TOP | 23750.31 | 23750.31 | 24.15 | 1.164 | 1.164 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 10234.35 | 10234.35 | 49.36 | 0.503 | 0.503 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 6685.00 | 6685.00 | 50.93 | 0.329 | 0.329 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10169.84 | 10169.84 | 49.05 | 0.500 | 0.500 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 6647.20 | 6647.20 | 50.64 | 0.327 | 0.327 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00795 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6990.96 | 6990.96 | 33.72 | 0.343 | 0.343 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00794 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 4633.67 | 4633.67 | 35.30 | 0.228 | 0.228 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00794 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 6935.32 | 6935.32 | 33.45 | 0.341 | 0.341 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00794 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 4596.87 | 4596.87 | 35.02 | 0.226 | 0.226 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00794 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7724.62 | 7724.62 | 37.26 | 0.379 | 0.379 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 5087.60 | 5087.60 | 38.76 | 0.250 | 0.250 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -5.20 | 0.00281 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7662.60 | 7662.60 | 36.96 | 0.376 | 0.376 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -5.20 | 0.00281 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 5053.34 | 5053.34 | 38.50 | 0.248 | 0.248 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -5.20 | 0.00281 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.30 | 5.30 | 1.56 | 1.56 | 5.3044 | 1.5618 | 5.3044 | 0.2944 | 0.3000 |
PACU_VAV_MID | 4.58 | 4.58 | 1.89 | 1.89 | 4.5796 | 1.8860 | 4.5796 | 0.4118 | 0.3000 |
PACU_VAV_TOP | 5.47 | 5.47 | 2.82 | 2.82 | 5.4724 | 2.8229 | 5.4724 | 0.5158 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 22972.302 | 22972.302 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22972.30 | 12301.49 | 0.424691 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 5652.91 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 22086.475 | 22086.475 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22086.48 | 18309.54 | 0.632110 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 12952.09 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 33728.460 | 33728.460 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 33728.46 | 33728.46 | 1.164426 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 23750.31 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 14572.622 | 14572.622 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14572.62 | 14572.62 | 0.503098 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00795058 | 44.5797 | 10234.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 9519.488 | 9519.488 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9519.49 | 9519.49 | 0.328646 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00794996 | 44.5763 | 6685.00 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 14480.514 | 14480.514 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14480.51 | 14480.51 | 0.499919 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00795017 | 44.5774 | 10169.84 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9465.521 | 9465.521 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9465.52 | 9465.52 | 0.326783 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00794960 | 44.5743 | 6647.20 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9943.156 | 9943.156 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9943.16 | 9943.16 | 0.343273 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00793713 | 44.5053 | 6990.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6591.542 | 6591.542 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6591.54 | 6591.54 | 0.227563 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00794020 | 44.5223 | 4633.67 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9863.713 | 9863.713 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9863.71 | 9863.71 | 0.340530 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00793593 | 44.4986 | 6935.32 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6538.995 | 6538.995 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6539.00 | 6539.00 | 0.225749 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00793908 | 44.5161 | 4596.87 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 10989.773 | 10989.773 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10989.77 | 10989.77 | 0.379406 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00792824 | 44.4562 | 7724.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 7239.087 | 7239.087 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7239.09 | 7239.09 | 0.249919 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00793086 | 44.4706 | 5087.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 10901.215 | 10901.215 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10901.21 | 10901.21 | 0.376348 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00792685 | 44.4485 | 7662.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 7190.167 | 7190.167 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7190.17 | 7190.17 | 0.248230 | 12.80 | 10.33 | 0.00800000 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00792972 | 44.4644 | 5053.34 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 95750.047 | 76614.639 | 5.304365 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 89819.04 | 89819.04 | 5.304365 | 27.18 | 15.90 | 0.00837709 | 10.76 | 9.88 | 0.00837709 | 38.10 | 0.00687148 | 18.17 | 22.5318 | 24.00 | 0.00881553 | 41.1384 | 63256.63 | 0.00 | 98731.15 | 72424.69 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 19522.579 | 19522.579 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 19522.58 | 19522.58 | 1.591310 | 1.11 | 0.23 | 0.00407658 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 75.1061 | 20.73 | 0.00786430 | 44.8485 | 18516.33 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 85174.172 | 68158.540 | 4.579553 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 79898.26 | 79898.26 | 4.579553 | 27.69 | 16.04 | 0.00834174 | 10.75 | 9.83 | 0.00834174 | 38.10 | 0.00687148 | 18.17 | 26.0980 | 24.00 | 0.00886330 | 41.3581 | 54482.06 | 0.00 | 87826.00 | 64438.63 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 21352.850 | 21352.850 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21352.85 | 21352.85 | 1.373866 | -2.01 | -2.34 | 0.00346373 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 86.9932 | 19.60 | 0.00781733 | 47.8049 | 22845.10 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 98306.174 | 78722.435 | 5.472393 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 92216.84 | 92216.84 | 5.472393 | 27.10 | 15.87 | 0.00837929 | 10.76 | 9.88 | 0.00837929 | 38.10 | 0.00687148 | 18.17 | 21.8400 | 24.00 | 0.00880357 | 41.0832 | 64966.60 | 0.00 | 101366.86 | 74414.72 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 18733.395 | 18733.395 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18733.39 | 18733.39 | 1.641718 | 1.93 | 0.86 | 0.00420534 | 12.80 | 10.33 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 72.8000 | 18.85 | 0.00794420 | 50.8802 | 24605.94 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 22972.302 | 22972.302 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22972.30 | 12301.49 | 1.0000 | 0.44351838 | 0.424691 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22972.30 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.66 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 5652.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 22086.475 | 22086.475 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22086.48 | 18309.54 | 1.0000 | 0.66013274 | 0.632110 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22086.48 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 12952.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 33728.460 | 33728.460 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 33728.46 | 33728.46 | 1.0000 | 1.21604670 | 1.164426 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33728.46 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 23750.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14572.622 | 14572.622 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14572.62 | 14572.62 | 1.0000 | 0.52540165 | 0.503098 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14572.62 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00795058 | 21.00 | 0.00795058 | 44.5797 | 10234.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9519.488 | 9519.488 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9519.49 | 9519.49 | 1.0000 | 0.34321583 | 0.328646 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9519.49 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00794996 | 21.00 | 0.00794996 | 44.5763 | 6685.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14480.514 | 14480.514 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14480.51 | 14480.51 | 1.0000 | 0.52208080 | 0.499919 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14480.51 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00795017 | 21.00 | 0.00795017 | 44.5774 | 10169.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9465.521 | 9465.521 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9465.52 | 9465.52 | 1.0000 | 0.34127010 | 0.326783 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9465.52 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00794960 | 21.00 | 0.00794960 | 44.5743 | 6647.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9943.156 | 9943.156 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9943.16 | 9943.16 | 1.0000 | 0.35849079 | 0.343273 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9943.16 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00793713 | 21.00 | 0.00793713 | 44.5053 | 6990.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6591.542 | 6591.542 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6591.54 | 6591.54 | 1.0000 | 0.23765162 | 0.227563 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6591.54 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00794020 | 21.00 | 0.00794020 | 44.5223 | 4633.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9863.713 | 9863.713 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9863.71 | 9863.71 | 1.0000 | 0.35562654 | 0.340530 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9863.71 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00793593 | 21.00 | 0.00793593 | 44.4986 | 6935.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 6538.995 | 6538.995 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6539.00 | 6539.00 | 1.0000 | 0.23575708 | 0.225749 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6539.00 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00793908 | 21.00 | 0.00793908 | 44.5161 | 4596.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10989.773 | 10989.773 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10989.77 | 10989.77 | 1.0000 | 0.39622553 | 0.379406 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10989.77 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00792824 | 21.00 | 0.00792824 | 44.4562 | 7724.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7239.087 | 7239.087 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7239.09 | 7239.09 | 1.0000 | 0.26099821 | 0.249919 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7239.09 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00793086 | 21.00 | 0.00793086 | 44.4706 | 5087.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10901.215 | 10901.215 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10901.21 | 10901.21 | 1.0000 | 0.39303266 | 0.376348 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10901.21 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00792685 | 21.00 | 0.00792685 | 44.4485 | 7662.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7190.167 | 7190.167 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7190.17 | 7190.17 | 1.0000 | 0.25923446 | 0.248230 | 12.80 | 10.33 | 0.00800000 | 33059.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7190.17 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 20.95 | 0.00792972 | 21.00 | 0.00792972 | 44.4644 | 5053.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 95750.047 | 76614.639 | 5.304365 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4126 | 1004.8586 | 1.0443 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.304365 | 5.53951690 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 89819.04 | 89819.04 | 0.9381 | 5.53951690 | 5.304365 | 27.18 | 15.90 | 0.00837709 | 48684.4 | 10.76 | 9.88 | 0.00837709 | 31929.3 | -999.0 | -999.00 | -999.00 | -999.00 | 11536.402 | 78282.64 | 38.10 | 0.00687148 | 18.17 | 1.19517000 | 22.5318 | 24.00 | 0.00881553 | 24.00 | 0.00881553 | 41.1384 | 63256.63 | 0.00 | 98731.15 | 72424.69 | 5.32074786 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.35 | 13.06 | 0.00924618 | 36766.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19522.579 | 19522.579 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.304365 | 5.53951690 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 19522.58 | 19522.58 | 1.0000 | 1.66185507 | 1.591310 | 1.11 | 0.23 | 0.00407658 | 11318.4 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19522.58 | -5.20 | 0.00280840 | -5.20 | 1.19517000 | 75.1061 | 20.14 | 0.00790273 | 20.73 | 0.00786430 | 44.8485 | 18516.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 85174.172 | 68158.540 | 4.579553 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3469 | 1004.8586 | 1.0443 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.579553 | 4.78257207 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 79898.26 | 79898.26 | 0.9381 | 4.78257207 | 4.579553 | 27.69 | 16.04 | 0.00834174 | 49116.8 | 10.75 | 9.83 | 0.00834174 | 31826.5 | -999.0 | -999.00 | -999.00 | -999.00 | 10024.691 | 69873.57 | 38.10 | 0.00687148 | 18.17 | 1.19517000 | 26.0980 | 24.00 | 0.00886330 | 24.00 | 0.00886330 | 41.3581 | 54482.06 | 0.00 | 87826.00 | 64438.63 | 4.59369663 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.94 | 12.84 | 0.00918852 | 36203.6 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 21352.850 | 21352.850 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.579553 | 4.78257207 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:50:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21352.85 | 21352.85 | 1.0000 | 1.43477162 | 1.373866 | -2.01 | -2.34 | 0.00346373 | 6629.5 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21352.85 | -5.20 | 0.00280840 | -5.20 | 1.19517000 | 86.9932 | 19.32 | 0.00784680 | 19.60 | 0.00781733 | 47.8049 | 22845.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 98306.174 | 78722.435 | 5.472393 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.4167 | 1004.8586 | 1.0443 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.472393 | 5.71499345 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 92216.84 | 92216.84 | 0.9381 | 5.71499345 | 5.472393 | 27.10 | 15.87 | 0.00837929 | 48604.6 | 10.76 | 9.88 | 0.00837929 | 31934.9 | -999.0 | -999.00 | -999.00 | -999.00 | 11901.843 | 80314.99 | 38.10 | 0.00687148 | 18.17 | 1.19517000 | 21.8400 | 24.00 | 0.00880357 | 24.00 | 0.00880357 | 41.0832 | 64966.60 | 0.00 | 101366.86 | 74414.72 | 5.48929441 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.40 | 13.09 | 0.00925958 | 36856.1 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 18733.395 | 18733.395 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.472393 | 5.71499345 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18733.39 | 18733.39 | 1.0000 | 1.71449803 | 1.641718 | 1.93 | 0.86 | 0.00420534 | 12468.0 | 12.80 | 10.33 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18733.39 | -5.20 | 0.00280840 | -5.20 | 1.19517000 | 72.8000 | 21.00 | 0.00794420 | 18.85 | 0.00794420 | 50.8802 | 24605.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.30 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.58 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.47 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2371.50 | 2175.00 | 36.17 |
CORE_MID | 2047.33 | 2919.33 | 99.33 |
CORE_TOP | 2297.17 | 3142.33 | 377.33 |
PERIMETER_TOP_ZN_3 | 3137.67 | 3366.33 | 1194.17 |
PERIMETER_TOP_ZN_2 | 3139.33 | 3051.83 | 958.33 |
PERIMETER_TOP_ZN_1 | 2995.83 | 2549.83 | 719.00 |
PERIMETER_TOP_ZN_4 | 3214.33 | 3189.67 | 1125.83 |
PERIMETER_BOT_ZN_3 | 2504.50 | 3326.50 | 595.83 |
PERIMETER_BOT_ZN_2 | 2683.00 | 2855.83 | 371.50 |
PERIMETER_BOT_ZN_1 | 2595.17 | 2744.17 | 416.67 |
PERIMETER_BOT_ZN_4 | 2681.67 | 2914.17 | 418.50 |
PERIMETER_MID_ZN_3 | 2603.00 | 3217.83 | 618.33 |
PERIMETER_MID_ZN_2 | 2398.83 | 2548.33 | 541.83 |
PERIMETER_MID_ZN_1 | 2750.67 | 2245.50 | 363.50 |
PERIMETER_MID_ZN_4 | 2819.50 | 3004.00 | 653.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4244.67 | 3975.00 | 1610.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 3.83 | 0.00 | 0.17 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.33 | 0.00 | 0.33 |
PERIMETER_TOP_ZN_3 | 0.67 | 15.67 | 0.00 | 10.50 |
PERIMETER_TOP_ZN_2 | 0.67 | 60.00 | 0.00 | 56.17 |
PERIMETER_TOP_ZN_1 | 0.33 | 48.17 | 0.00 | 43.67 |
PERIMETER_TOP_ZN_4 | 0.50 | 51.50 | 0.00 | 31.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 32.50 | 0.00 | 32.00 |
PERIMETER_BOT_ZN_1 | 122.50 | 173.67 | 122.50 | 172.67 |
PERIMETER_BOT_ZN_4 | 0.00 | 36.33 | 0.00 | 23.50 |
PERIMETER_MID_ZN_3 | 0.00 | 2.17 | 0.00 | 1.33 |
PERIMETER_MID_ZN_2 | 0.00 | 42.50 | 0.00 | 41.83 |
PERIMETER_MID_ZN_1 | 0.00 | 34.67 | 0.00 | 33.83 |
PERIMETER_MID_ZN_4 | 0.00 | 44.00 | 0.00 | 27.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 123.33 | 357.17 | 122.50 | 318.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 1.020 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.695 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.686 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.760 | 0.019 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 1.238 | 0.020 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 1.173 | 0.019 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 1.202 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.687 | 0.010 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 1.079 | 0.011 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.956 | 1.268 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.997 | 0.011 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.754 | 0.016 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 1.147 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 1.168 | 0.016 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 1.141 | 0.017 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 22.03 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.94 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 22.03 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.58 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.94 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.24 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 16378731.76 | 0.00 | 16378731.76 | 0.00 | 16378731.76 | 13393058.27 | 5232.93 | 201.50 | 3325.57 | 97.50 |
CORE_MID | 11090969.93 | 0.00 | 11090969.93 | 0.00 | 11090969.93 | 13393058.27 | 6119.27 | 32.54 | 2608.19 | 46.50 |
CORE_TOP | 10936350.22 | 0.00 | 10936350.22 | 0.00 | 10936350.22 | 13393058.27 | 6120.23 | 21.37 | 2618.40 | 47.37 |
PERIMETER_TOP_ZN_3 | 2549912.93 | 0.00 | 2549912.93 | 127813.82 | 2677726.76 | 2823374.22 | 4706.21 | 36.97 | 4016.82 | 47.37 |
PERIMETER_TOP_ZN_2 | 2622194.10 | 0.00 | 2622194.10 | 85208.70 | 2707402.80 | 1787429.43 | 4034.65 | 1.80 | 4723.55 | 47.37 |
PERIMETER_TOP_ZN_1 | 3923078.21 | 0.00 | 3923078.21 | 127813.82 | 4050892.03 | 2823374.22 | 4092.10 | 26.77 | 4641.13 | 47.37 |
PERIMETER_TOP_ZN_4 | 2554116.73 | 0.00 | 2554116.73 | 85208.70 | 2639325.43 | 1787312.18 | 4064.93 | 14.42 | 4680.65 | 47.37 |
PERIMETER_BOT_ZN_3 | 2342082.07 | 0.00 | 2342082.07 | 67958.23 | 2410040.29 | 2823374.22 | 5550.35 | 192.01 | 3017.64 | 97.50 |
PERIMETER_BOT_ZN_2 | 2310215.55 | 0.00 | 2310215.55 | 45305.21 | 2355520.76 | 1787429.43 | 4149.11 | 57.14 | 4553.76 | 97.50 |
PERIMETER_BOT_ZN_1 | 3235160.29 | 0.00 | 3235160.29 | 4260618.50 | 7495778.79 | 2823374.22 | 4468.31 | 153.49 | 4138.20 | 97.50 |
PERIMETER_BOT_ZN_4 | 2143044.59 | 0.00 | 2143044.59 | 45305.21 | 2188349.80 | 1787312.18 | 4292.85 | 64.13 | 4403.02 | 97.50 |
PERIMETER_MID_ZN_3 | 2530399.25 | 0.00 | 2530399.25 | 106395.42 | 2636794.67 | 2823374.22 | 4700.33 | 54.77 | 4004.90 | 46.50 |
PERIMETER_MID_ZN_2 | 2582463.54 | 0.00 | 2582463.54 | 70929.85 | 2653393.39 | 1787429.43 | 3999.35 | 2.19 | 4758.47 | 955.50 |
PERIMETER_MID_ZN_1 | 3907210.13 | 0.00 | 3907210.13 | 106395.42 | 4013605.55 | 2823374.22 | 4520.97 | 35.17 | 4203.86 | 46.50 |
PERIMETER_MID_ZN_4 | 2425324.50 | 0.00 | 2425324.50 | 70929.85 | 2496254.36 | 1787312.18 | 4017.73 | 16.21 | 4726.06 | 46.50 |
Total Facility | 71531253.78 | 0.00 | 71531253.78 | 5199882.74 | 76731136.52 | 67843644.98 | 6327.40 | 534.85 | 4911.42 | 1033.97 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7504 | 0.0000 | 0.7504 | 0.0000 | 0.7504 | 0.4247 | 2513.43 | 201.50 | 3228.07 |
CORE_MID | 0.5118 | 0.0000 | 0.5118 | 0.0000 | 0.5118 | 0.4247 | 3348.77 | 32.54 | 2561.69 |
CORE_TOP | 0.5056 | 0.0000 | 0.5056 | 0.0000 | 0.5056 | 0.4247 | 3342.02 | 21.37 | 2579.60 |
PERIMETER_TOP_ZN_3 | 0.1180 | 0.0000 | 0.1180 | 0.0030 | 0.1210 | 0.0895 | 1928.00 | 36.97 | 3978.03 |
PERIMETER_TOP_ZN_2 | 0.1216 | 0.0000 | 0.1216 | 0.0020 | 0.1236 | 0.0567 | 1256.44 | 1.80 | 4684.75 |
PERIMETER_TOP_ZN_1 | 0.1821 | 0.0000 | 0.1821 | 0.0030 | 0.1852 | 0.0895 | 1313.89 | 26.77 | 4602.34 |
PERIMETER_TOP_ZN_4 | 0.1182 | 0.0000 | 0.1182 | 0.0020 | 0.1202 | 0.0567 | 1286.73 | 14.42 | 4641.86 |
PERIMETER_BOT_ZN_3 | 0.1068 | 0.0000 | 0.1068 | 0.0016 | 0.1084 | 0.0895 | 2830.85 | 192.01 | 2920.14 |
PERIMETER_BOT_ZN_2 | 0.1059 | 0.0000 | 0.1059 | 0.0011 | 0.1070 | 0.0567 | 1429.61 | 57.14 | 4456.26 |
PERIMETER_BOT_ZN_1 | 0.1485 | 0.0000 | 0.1485 | 0.1976 | 0.3460 | 0.0895 | 1748.81 | 153.49 | 4040.70 |
PERIMETER_BOT_ZN_4 | 0.0980 | 0.0000 | 0.0980 | 0.0011 | 0.0990 | 0.0567 | 1573.35 | 64.13 | 4305.52 |
PERIMETER_MID_ZN_3 | 0.1170 | 0.0000 | 0.1170 | 0.0025 | 0.1195 | 0.0895 | 1929.83 | 54.77 | 3958.40 |
PERIMETER_MID_ZN_2 | 0.1127 | 0.0000 | 0.1127 | 0.0018 | 0.1145 | 0.0567 | 1228.35 | 2.19 | 3803.47 |
PERIMETER_MID_ZN_1 | 0.1813 | 0.0000 | 0.1813 | 0.0025 | 0.1838 | 0.0895 | 1750.47 | 35.17 | 4157.36 |
PERIMETER_MID_ZN_4 | 0.1121 | 0.0000 | 0.1121 | 0.0017 | 0.1138 | 0.0567 | 1247.23 | 16.21 | 4679.56 |
Total Facility | 3.2900 | 0.0000 | 3.2900 | 0.2198 | 3.5098 | 2.1513 | 3530.53 | 534.85 | 4795.03 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 28802674.56 | 0.00 | 28802674.56 | 22614548.33 | 3987.41 | 2.36 | 4770.23 | 97.50 |
PACU_VAV_MID | 24578828.72 | 0.00 | 24578828.72 | 22614548.33 | 4017.00 | 2.26 | 4740.73 | 46.50 |
PACU_VAV_TOP | 24632562.33 | 0.00 | 24632562.33 | 22614548.33 | 4043.82 | 2.06 | 4714.12 | 47.37 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.3192 | 0.0000 | 1.3192 | 0.7171 | 1267.91 | 2.36 | 4672.73 |
PACU_VAV_MID | 1.1362 | 0.0000 | 1.1362 | 0.7171 | 1246.50 | 2.26 | 4694.23 |
PACU_VAV_TOP | 1.1403 | 0.0000 | 1.1403 | 0.7171 | 1265.61 | 2.06 | 4675.33 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.22 | 3042.10 | 0.00 | 0.00 | 0.00 | 1815.06 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.25 | 2801.81 | 0.00 | 0.00 | 0.00 | 2033.10 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.08 | 2808.71 | 0.00 | 0.00 | 0.00 | 2026.86 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.1432 | 0.0000 | 0.0000 | 0.0000 | 0.8426 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 1.8171 | 0.0000 | 0.0000 | 0.0000 | 0.8585 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 1.8317 | 0.0000 | 0.0000 | 0.0000 | 0.8484 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 825 |
Defaulted Fields | 545 |
Fields with Defaults | 2230 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1411.79 | 12347.42 | 23-JUL-17:10 | 166885.61 | 20-JUL-15:10 |
Electricity:Building | 908.40 | 12178.84 | 23-JUL-17:10 | 66126.74 | 13-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 284.50 | 4029.56 | 01-JAN-00:10 | 22405.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 908.40 | 12178.84 | 23-JUL-17:10 | 66126.74 | 13-OCT-07:10 |
InteriorLights:Electricity | 202.97 | 934.27 | 01-JAN-09:20 | 21377.78 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 202.97 | 934.27 | 01-JAN-09:20 | 21377.78 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity | 202.97 | 934.27 | 01-JAN-09:20 | 21377.78 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 202.97 | 934.27 | 01-JAN-09:20 | 21377.78 | 22-NOV-17:00 |
Electricity:Zone:CORE_MID | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.33 | 409.68 | 07-MAY-17:10 | 2324.90 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.99 | 23.57 | 01-JAN-09:20 | 889.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.99 | 23.57 | 01-JAN-09:20 | 889.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.17 | 260.46 | 23-JUL-17:10 | 1471.80 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.77 | 14.92 | 01-JAN-08:10 | 563.23 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.77 | 14.92 | 01-JAN-08:10 | 563.23 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.18 | 409.67 | 21-MAY-17:10 | 2324.89 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.85 | 23.57 | 01-JAN-08:20 | 889.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.85 | 23.57 | 01-JAN-08:20 | 889.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.13 | 259.34 | 12-MAR-17:10 | 1471.76 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.73 | 14.92 | 01-JAN-09:20 | 563.19 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.73 | 14.92 | 01-JAN-09:20 | 563.19 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.30 | 409.68 | 30-APR-17:10 | 2324.90 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.97 | 23.57 | 01-JAN-09:20 | 889.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.97 | 23.57 | 01-JAN-09:20 | 889.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.17 | 260.34 | 23-JUL-17:10 | 1471.80 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.76 | 14.92 | 01-JAN-08:10 | 563.23 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.76 | 14.92 | 01-JAN-08:10 | 563.23 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.17 | 409.67 | 19-MAR-17:10 | 2324.89 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.84 | 23.57 | 01-JAN-08:20 | 889.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.84 | 23.57 | 01-JAN-08:20 | 889.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.12 | 259.34 | 12-MAR-17:10 | 1471.76 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.72 | 14.92 | 01-JAN-09:20 | 563.19 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.72 | 14.92 | 01-JAN-09:20 | 563.19 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.33 | 409.68 | 07-MAY-17:10 | 2324.90 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.99 | 23.57 | 01-JAN-09:20 | 889.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.99 | 23.57 | 01-JAN-09:20 | 889.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.17 | 260.46 | 23-JUL-17:10 | 1471.80 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.77 | 14.92 | 01-JAN-08:10 | 563.23 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.77 | 14.92 | 01-JAN-08:10 | 563.23 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.18 | 409.67 | 21-MAY-17:10 | 2324.89 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.85 | 23.57 | 01-JAN-08:20 | 889.66 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.85 | 23.57 | 01-JAN-08:20 | 889.66 | 22-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.13 | 259.34 | 12-MAR-17:10 | 1471.76 | 22-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.73 | 14.92 | 01-JAN-09:20 | 563.19 | 22-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.73 | 14.92 | 01-JAN-09:20 | 563.19 | 22-NOV-17:00 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 454.00 | 168.34 | 01-JAN-00:10 | 107993.77 | 20-JUL-15:10 |
ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 833.85 | 13-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 833.85 | 13-OCT-07:20 |
ElectricityPurchased:Facility | 1411.79 | 12347.42 | 23-JUL-17:10 | 166885.61 | 20-JUL-15:10 |
ElectricityPurchased:Plant | 1411.79 | 12347.42 | 23-JUL-17:10 | 166885.61 | 20-JUL-15:10 |
Cogeneration:ElectricityPurchased | 1411.79 | 12347.42 | 23-JUL-17:10 | 166885.61 | 20-JUL-15:10 |
General:Cogeneration:ElectricityPurchased | 1411.79 | 12347.42 | 23-JUL-17:10 | 166885.61 | 20-JUL-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1411.79 | 12347.42 | 23-JUL-17:10 | 166885.61 | 20-JUL-15:10 |
ElectricityNet:Plant | 1411.79 | 12347.42 | 23-JUL-17:10 | 166885.61 | 20-JUL-15:10 |
Cogeneration:ElectricityNet | 1411.79 | 12347.42 | 23-JUL-17:10 | 166885.61 | 20-JUL-15:10 |
General:Cogeneration:ElectricityNet | 1411.79 | 12347.42 | 23-JUL-17:10 | 166885.61 | 20-JUL-15:10 |
Heating:Electricity | 28.07 | 0.00 | 01-JAN-00:10 | 85850.00 | 27-DEC-07:10 |
General:Heating:Electricity | 28.07 | 0.00 | 01-JAN-00:10 | 85850.00 | 27-DEC-07:10 |
Fans:Electricity | 120.40 | 0.00 | 01-JAN-00:10 | 33449.55 | 20-JUL-15:00 |
General:Fans:Electricity | 120.40 | 0.00 | 01-JAN-00:10 | 33449.55 | 20-JUL-15:00 |
ExteriorLights:Electricity | 49.37 | 0.00 | 01-JAN-07:20 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 49.37 | 0.00 | 01-JAN-07:20 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 293.87 | 0.00 | 01-JAN-00:10 | 73716.27 | 20-JUL-15:10 |
General:Cooling:Electricity | 293.87 | 0.00 | 01-JAN-00:10 | 73716.27 | 20-JUL-15:10 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-08:10 |
WIRED_LTG_ELECTRICITY | 5.70 | 0.00 | 01-JAN-00:10 | 600.72 | 22-NOV-17:10 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 120.20 | 1156.00 | 09-JAN-06:10 | 54172.78 | 27-DEC-07:30 |
NaturalGas:HVAC | 20.73 | 0.00 | 01-JAN-00:10 | 46507.56 | 27-DEC-07:20 |
Heating:NaturalGas | 20.73 | 0.00 | 01-JAN-00:10 | 46507.56 | 27-DEC-07:20 |
General:Heating:NaturalGas | 20.73 | 0.00 | 01-JAN-00:10 | 46507.56 | 27-DEC-07:20 |
NaturalGas:Plant | 99.47 | 1156.00 | 09-JAN-06:10 | 9222.10 | 03-FEB-12:10 |
WaterSystems:NaturalGas | 99.47 | 1156.00 | 09-JAN-06:10 | 9222.10 | 03-FEB-12:10 |
Water Heater:WaterSystems:NaturalGas | 99.47 | 1156.00 | 09-JAN-06:10 | 9222.10 | 03-FEB-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2431.40 | 0.00 | 01-JAN-00:10 | 422428.37 | 20-JUL-15:00 |
EnergyTransfer:Building | 1241.25 | 0.00 | 01-JAN-00:10 | 159765.65 | 03-JUL-14:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 251.28 | 0.00 | 01-JAN-00:10 | 26991.71 | 05-SEP-08:00 |
Heating:EnergyTransfer | 29.01 | 0.00 | 01-JAN-00:10 | 76355.28 | 27-DEC-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 29.01 | 0.00 | 01-JAN-00:10 | 76355.28 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1212.24 | 0.00 | 01-JAN-00:10 | 159765.65 | 03-JUL-14:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 251.28 | 0.00 | 01-JAN-00:10 | 26991.71 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 1212.24 | 0.00 | 01-JAN-00:10 | 159765.65 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 251.28 | 0.00 | 01-JAN-00:10 | 26991.71 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 55.29 | 0.00 | 01-JAN-00:10 | 11554.94 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.34 | 0.00 | 01-JAN-00:10 | 8188.79 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 8.34 | 0.00 | 01-JAN-00:10 | 8188.79 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 46.94 | 0.00 | 01-JAN-00:10 | 11554.94 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 46.94 | 0.00 | 01-JAN-00:10 | 11554.94 | 03-JUL-13:00 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 27.14 | 0.00 | 01-JAN-00:10 | 5238.50 | 03-JUL-14:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.54 | 0.00 | 01-JAN-00:10 | 2636.07 | 04-DEC-11:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.54 | 0.00 | 01-JAN-00:10 | 2636.07 | 04-DEC-11:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 23.60 | 0.00 | 01-JAN-00:10 | 5238.50 | 03-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 23.60 | 0.00 | 01-JAN-00:10 | 5238.50 | 03-JUL-14:50 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 30.48 | 0.00 | 01-JAN-00:10 | 5363.75 | 19-JUN-12:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 1.66 | 0.00 | 01-JAN-00:10 | 2608.57 | 27-DEC-08:30 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 1.66 | 0.00 | 01-JAN-00:10 | 2608.57 | 27-DEC-08:30 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 28.81 | 0.00 | 01-JAN-00:10 | 5363.75 | 19-JUN-12:20 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 28.81 | 0.00 | 01-JAN-00:10 | 5363.75 | 19-JUN-12:20 |
EnergyTransfer:Zone:CORE_MID | 166.15 | 0.00 | 01-JAN-00:10 | 18223.81 | 19-JUN-07:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1972.01 | 17-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1972.01 | 17-JAN-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 166.14 | 0.00 | 01-JAN-00:10 | 18223.81 | 19-JUN-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 166.14 | 0.00 | 01-JAN-00:10 | 18223.81 | 19-JUN-07:40 |
EnergyTransfer:Zone:CORE_TOP | 165.22 | 0.00 | 01-JAN-00:10 | 20420.73 | 03-JUL-13:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.63 | 0.00 | 01-JAN-00:10 | 14473.12 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.63 | 0.00 | 01-JAN-00:10 | 14473.12 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 164.59 | 0.00 | 01-JAN-00:10 | 20420.73 | 03-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 164.59 | 0.00 | 01-JAN-00:10 | 20420.73 | 03-JUL-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 43.23 | 0.00 | 01-JAN-00:10 | 7565.11 | 03-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.74 | 0.00 | 01-JAN-00:10 | 7316.96 | 04-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.74 | 0.00 | 01-JAN-00:10 | 7316.96 | 04-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.49 | 0.00 | 01-JAN-00:10 | 7565.11 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.49 | 0.00 | 01-JAN-00:10 | 7565.11 | 03-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 41.96 | 0.00 | 01-JAN-00:10 | 7963.67 | 03-JUL-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.16 | 0.00 | 01-JAN-00:10 | 4905.73 | 04-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.16 | 0.00 | 01-JAN-00:10 | 4905.73 | 04-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.80 | 0.00 | 01-JAN-00:10 | 7963.67 | 03-JUL-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 40.80 | 0.00 | 01-JAN-00:10 | 7963.67 | 03-JUL-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 62.42 | 0.00 | 01-JAN-00:10 | 10938.49 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.40 | 0.00 | 01-JAN-00:10 | 7053.67 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.40 | 0.00 | 01-JAN-00:10 | 7053.67 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 61.02 | 0.00 | 01-JAN-00:10 | 10938.49 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 61.02 | 0.00 | 01-JAN-00:10 | 10938.49 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 42.46 | 0.00 | 01-JAN-00:10 | 8806.73 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.57 | 0.00 | 01-JAN-00:10 | 4750.39 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 1.57 | 0.00 | 01-JAN-00:10 | 4750.39 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 40.89 | 0.00 | 01-JAN-00:10 | 8806.73 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 40.89 | 0.00 | 01-JAN-00:10 | 8806.73 | 15-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.65 | 0.00 | 01-JAN-00:10 | 6399.13 | 03-JUL-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.34 | 0.00 | 01-JAN-00:10 | 2820.25 | 03-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.34 | 0.00 | 01-JAN-00:10 | 2820.25 | 03-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.32 | 0.00 | 01-JAN-00:10 | 6399.13 | 03-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 37.32 | 0.00 | 01-JAN-00:10 | 6399.13 | 03-JUL-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 37.93 | 0.00 | 01-JAN-00:10 | 6959.05 | 03-JUL-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.09 | 0.00 | 01-JAN-00:10 | 1897.05 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.09 | 0.00 | 01-JAN-00:10 | 1897.05 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 37.84 | 0.00 | 01-JAN-00:10 | 6959.05 | 03-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 37.84 | 0.00 | 01-JAN-00:10 | 6959.05 | 03-JUL-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 61.35 | 0.00 | 01-JAN-00:10 | 11409.94 | 03-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 6.27 | 0.00 | 01-JAN-00:10 | 10067.60 | 27-DEC-07:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 6.27 | 0.00 | 01-JAN-00:10 | 10067.60 | 27-DEC-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 55.08 | 0.00 | 01-JAN-00:10 | 11409.94 | 03-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 55.08 | 0.00 | 01-JAN-00:10 | 11409.94 | 03-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 37.02 | 0.00 | 01-JAN-00:10 | 7260.87 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.12 | 0.00 | 01-JAN-00:10 | 1868.59 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.12 | 0.00 | 01-JAN-00:10 | 1868.59 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 36.90 | 0.00 | 01-JAN-00:10 | 7260.87 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 36.90 | 0.00 | 01-JAN-00:10 | 7260.87 | 07-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.77 | 0.00 | 01-JAN-00:10 | 6714.26 | 03-JUL-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.46 | 0.00 | 01-JAN-00:10 | 3981.51 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.46 | 0.00 | 01-JAN-00:10 | 3981.51 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.31 | 0.00 | 01-JAN-00:10 | 6714.26 | 03-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 40.31 | 0.00 | 01-JAN-00:10 | 6714.26 | 03-JUL-14:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 40.00 | 0.00 | 01-JAN-00:10 | 7509.63 | 30-MAY-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.21 | 0.00 | 01-JAN-00:10 | 2725.58 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.21 | 0.00 | 01-JAN-00:10 | 2725.58 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 39.79 | 0.00 | 01-JAN-00:10 | 7509.63 | 30-MAY-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 39.79 | 0.00 | 01-JAN-00:10 | 7509.63 | 30-MAY-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 60.82 | 0.00 | 01-JAN-00:10 | 9645.40 | 03-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.19 | 0.00 | 01-JAN-00:10 | 3806.39 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.19 | 0.00 | 01-JAN-00:10 | 3806.39 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 60.63 | 0.00 | 01-JAN-00:10 | 9645.40 | 03-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 60.63 | 0.00 | 01-JAN-00:10 | 9645.40 | 03-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 40.08 | 0.00 | 01-JAN-00:10 | 8038.52 | 15-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.27 | 0.00 | 01-JAN-00:10 | 2665.44 | 27-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.27 | 0.00 | 01-JAN-00:10 | 2665.44 | 27-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 39.82 | 0.00 | 01-JAN-00:10 | 8038.52 | 15-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 39.82 | 0.00 | 01-JAN-00:10 | 8038.52 | 15-JUN-16:00 |
PlantLoopHeatingDemand:Facility | 42.69 | 0.00 | 01-JAN-00:10 | 5649.04 | 27-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 42.69 | 0.00 | 01-JAN-00:10 | 5649.04 | 27-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 42.69 | 0.00 | 01-JAN-00:10 | 5649.04 | 27-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 42.69 | 0.00 | 01-JAN-00:10 | 5649.04 | 27-JAN-12:10 |
EnergyTransfer:HVAC | 1147.46 | 0.00 | 01-JAN-00:10 | 327730.89 | 20-JUL-15:00 |
HeatingCoils:EnergyTransfer | 44.65 | 0.00 | 01-JAN-00:10 | 121986.34 | 27-DEC-07:10 |
CoolingCoils:EnergyTransfer | 1102.80 | 0.00 | 01-JAN-00:10 | 327730.89 | 20-JUL-15:00 |
EnergyTransfer:Plant | 42.69 | 0.00 | 01-JAN-00:10 | 5649.04 | 27-JAN-12:10 |
WaterSystems:EnergyTransfer | 42.69 | 0.00 | 01-JAN-00:10 | 5649.04 | 27-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 42.69 | 0.00 | 01-JAN-00:10 | 5649.04 | 27-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -251.280 | 0.000 | 0.000 | 32.729 | 48.333 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -65.950 |
CORE_MID | 0.000 | 0.000 | 0.004 | -166.141 | 0.000 | 0.000 | 33.285 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -30.905 |
CORE_TOP | 0.000 | 0.000 | 0.629 | -164.589 | 0.000 | 0.000 | 33.956 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -33.754 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.741 | -40.494 | 0.000 | 0.000 | 7.322 | 5.994 | 24.333 | 17.527 | 0.000 | 0.124 | 4.894 | 0.000 | -21.598 | 0.000 | -0.842 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.164 | -40.796 | 0.000 | 0.000 | 4.548 | 3.771 | 15.404 | 34.973 | 0.000 | 0.081 | 0.002 | 0.000 | -13.522 | 0.000 | -0.581 | -5.042 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.405 | -61.014 | 0.000 | 0.000 | 7.081 | 5.850 | 24.332 | 59.726 | 0.000 | 0.121 | 0.001 | 0.000 | -20.856 | 0.000 | -0.918 | -15.726 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 1.571 | -40.890 | 0.000 | 0.000 | 4.622 | 3.726 | 15.403 | 35.250 | 0.000 | 0.079 | 0.000 | 0.000 | -14.483 | 0.000 | -0.586 | -4.693 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.336 | -37.316 | 0.000 | 0.000 | 7.273 | 5.971 | 24.333 | 17.801 | 0.000 | 0.073 | 4.676 | 0.000 | -22.675 | 0.000 | -0.472 | -0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.095 | -37.835 | 0.000 | 0.000 | 4.486 | 3.762 | 15.404 | 35.065 | 0.000 | 0.044 | 0.002 | 0.000 | -14.558 | 0.000 | -0.335 | -6.128 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 6.272 | -55.080 | 0.000 | 0.000 | 7.160 | 5.840 | 24.332 | 60.239 | 0.000 | 7.579 | 0.002 | 0.000 | -22.329 | 0.000 | -24.140 | -9.874 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.120 | -36.903 | 0.000 | 0.000 | 4.545 | 3.715 | 15.403 | 35.395 | 0.000 | 0.043 | 0.000 | 0.000 | -15.609 | 0.000 | -0.338 | -6.371 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.458 | -40.309 | 0.000 | 0.000 | 7.219 | 5.994 | 24.333 | 17.402 | 0.000 | 0.106 | 8.698 | 0.000 | -23.144 | 0.000 | -0.757 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.211 | -39.786 | 0.000 | 0.000 | 3.326 | 3.771 | 15.404 | 34.835 | 0.000 | 0.069 | 0.000 | 0.000 | -14.383 | 0.000 | -0.519 | -2.927 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.193 | -60.628 | 0.000 | 0.000 | 6.999 | 5.850 | 24.332 | 59.544 | 0.000 | 0.102 | 0.002 | 0.000 | -22.176 | 0.000 | -0.817 | -13.400 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.268 | -39.816 | 0.000 | 0.000 | 4.556 | 3.726 | 15.403 | 35.166 | 0.000 | 0.066 | 0.000 | 0.000 | -15.458 | 0.000 | -0.525 | -3.385 |
TOPFLOOR_PLENUM | 8.344 | -46.942 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.148 | 39.738 | 0.000 | 0.000 | 0.000 | -1.288 | -0.001 |
MIDFLOOR_PLENUM | 3.538 | -23.602 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.163 | 21.227 | 0.000 | 0.000 | 0.000 | -1.326 | -0.000 |
FIRSTFLOOR_PLENUM | 1.663 | -28.813 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.126 | 28.101 | 0.000 | 0.000 | 0.000 | -1.077 | -0.000 |
Total Facility | 13.545 | -99.357 | 15.465 | -1112.877 | 0.000 | 0.000 | 169.105 | 202.971 | 705.434 | 442.924 | 0.000 | 8.925 | 107.345 | 0.000 | -220.792 | 0.000 | -34.522 | -198.155 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-JUL-04:02 | 0.00 | 0.00 | 0.00 | -42214.69 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 37340.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-04:02 | 0.00 | 0.00 | 0.00 | -31215.17 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 28304.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JUL-04:03 | 0.00 | 0.00 | 0.00 | -32816.85 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 29905.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JUL-16:22 | 0.00 | 0.00 | 0.00 | -11741.75 | 0.00 | 0.00 | 26.03 | 23.57 | 478.42 | 2969.31 | 0.00 | 48.63 | 8195.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 21-MAY-10:02 | 0.00 | 0.00 | 0.00 | -11114.40 | 0.00 | 0.00 | 15.48 | 14.92 | 302.86 | 4947.74 | 0.00 | 0.13 | 5833.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 29-OCT-12:22 | 0.00 | 0.00 | 0.00 | -14363.99 | 0.00 | 0.00 | 23.93 | 23.57 | 478.41 | 11743.71 | 0.00 | 0.00 | 2141.97 | 0.00 | -0.00 | 0.00 | -47.61 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-JUN-17:12 | 0.00 | 0.00 | 0.00 | -12903.17 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 7584.64 | 0.00 | 18.45 | 5040.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 07-AUG-06:03 | 0.00 | 0.00 | 0.00 | -7512.65 | 0.00 | 0.00 | 144.47 | 162.01 | 637.89 | 326.15 | 0.00 | 0.42 | 6241.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-09:32 | 0.00 | 0.00 | 0.00 | -9879.74 | 0.00 | 0.00 | 15.63 | 14.92 | 302.86 | 6152.00 | 0.00 | 4.24 | 3390.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-14:22 | 0.00 | 0.00 | 0.00 | -11748.69 | 0.00 | 0.00 | 24.18 | 23.57 | 478.41 | 8246.63 | 0.00 | 18.88 | 2957.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-AUG-17:52 | 0.00 | 0.00 | 0.00 | -10430.27 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 3500.90 | 0.00 | 13.57 | 6656.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-AUG-16:51 | 0.00 | 0.00 | 0.00 | -9787.04 | 0.00 | 0.00 | 28.45 | 23.57 | 478.42 | 2032.78 | 0.00 | 60.84 | 7162.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-08:52 | 0.00 | 0.00 | 0.00 | -11107.23 | 0.00 | 0.00 | 14.57 | 14.92 | 302.86 | 7053.77 | 0.00 | 0.27 | 3720.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 22-OCT-13:12 | 0.00 | 0.00 | 0.00 | -12414.35 | 0.00 | 0.00 | 24.40 | 23.57 | 478.41 | 9664.34 | 0.00 | 0.00 | 2225.26 | 0.00 | -0.00 | 0.00 | -1.63 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:01 | 0.00 | 0.00 | 0.00 | -11606.73 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 7771.18 | 0.00 | 17.12 | 3559.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 03-JUL-13:00 | 0.00 | -11555.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 11538.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 03-JUL-14:50 | 0.00 | -5238.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 | 5226.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 03-JUL-12:09 | 0.00 | -6715.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 6713.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-06:03 | 0.00 | -10734.43 | 0.00 | -176955.68 | 0.00 | 0.00 | 3484.23 | 5905.56 | 21098.80 | 20921.34 | 0.00 | 2667.79 | 133612.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 04-DEC-07:01 | 0.00 | 0.00 | 16208.97 | 0.00 | 0.00 | 0.00 | 893.12 | 1406.75 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21534.76 |
CORE_TOP | 04-DEC-06:01 | 0.00 | 0.00 | 27689.71 | 0.00 | 0.00 | 0.00 | 493.73 | 468.92 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31678.27 |
PERIMETER_TOP_ZN_3 | 04-DEC-05:02 | 0.00 | 0.00 | 9979.10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2143.66 | 0.00 | -9.55 | -8439.55 |
PERIMETER_TOP_ZN_2 | 04-DEC-05:02 | 0.00 | 0.00 | 8785.66 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1424.53 | 0.00 | -6.45 | -7743.16 |
PERIMETER_TOP_ZN_1 | 04-DEC-05:02 | 0.00 | 0.00 | 10812.90 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2185.08 | 0.00 | -9.84 | -9231.64 |
PERIMETER_TOP_ZN_4 | 04-DEC-05:02 | 0.00 | 0.00 | 8799.13 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1449.91 | 0.00 | -6.56 | -7731.13 |
PERIMETER_BOT_ZN_3 | 02-MAR-06:01 | 0.00 | 0.00 | 7015.44 | 0.00 | 0.00 | 0.00 | 100.00 | 98.85 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2874.94 | 0.00 | -14.86 | -4962.38 |
PERIMETER_BOT_ZN_2 | 27-DEC-06:01 | 0.00 | 0.00 | 5263.15 | 0.00 | 0.00 | 0.00 | 63.15 | 62.58 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1938.54 | 0.00 | -11.44 | -3842.70 |
PERIMETER_BOT_ZN_1 | 27-DEC-07:10 | 0.00 | 0.00 | 10627.08 | 0.00 | 0.00 | 0.00 | 193.30 | 296.56 | 637.88 | 0.00 | 0.00 | 0.00 | 11280.93 | 0.00 | -2946.38 | 0.00 | -20089.37 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-DEC-06:01 | 0.00 | 0.00 | 5249.51 | 0.00 | 0.00 | 0.00 | 63.07 | 62.58 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1905.36 | 0.00 | -11.45 | -3862.16 |
PERIMETER_MID_ZN_3 | 27-DEC-06:01 | 0.00 | 0.00 | 7691.22 | 0.00 | 0.00 | 0.00 | 103.61 | 98.85 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2752.04 | 0.00 | -25.74 | -5753.79 |
PERIMETER_MID_ZN_2 | 27-DEC-06:01 | 0.00 | 0.00 | 6128.33 | 0.00 | 0.00 | 0.00 | 65.98 | 62.58 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1862.28 | 0.00 | -17.14 | -4781.27 |
PERIMETER_MID_ZN_1 | 27-DEC-06:01 | 0.00 | 0.00 | 8584.23 | 0.00 | 0.00 | 0.00 | 103.20 | 98.85 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2822.97 | 0.00 | -25.93 | -6575.27 |
PERIMETER_MID_ZN_4 | 27-DEC-06:01 | 0.00 | 0.00 | 5986.64 | 0.00 | 0.00 | 0.00 | 65.84 | 62.58 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1828.36 | 0.00 | -17.17 | -4673.34 |
TOPFLOOR_PLENUM | 27-DEC-07:02 | 10270.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -40.38 | -10230.00 |
MIDFLOOR_PLENUM | 08-OCT-15:23 | 3978.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.40 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4000.34 |
FIRSTFLOOR_PLENUM | 13-NOV-06:02 | 5250.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -42.80 | -5207.40 |
Total Facility | 04-DEC-07:01 | 4767.91 | 5949.80 | 125507.59 | -5949.80 | 0.00 | 0.00 | 4501.98 | 6085.83 | 21098.80 | 9770.17 | 0.00 | 0.00 | 0.00 | 0.00 | -10791.33 | 0.00 | -23906.53 | -137034.42 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.7717 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.3044 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.1212 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5796 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.7058 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.4724 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8858 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3831 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5606 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3665 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.8529 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4568 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1101 | 3.1101 | 0.7931 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2493 | 2.2493 | 0.7625 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4538 | 2.4538 | 0.7999 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8102 | 0.8102 | 0.1685 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7197 | 0.7197 | 0.1439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8981 | 0.8981 | 0.1796 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8239 | 0.8239 | 0.1648 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6523 | 0.6523 | 0.1670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6214 | 0.6214 | 0.1243 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7294 | 0.7294 | 0.1670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6584 | 0.6584 | 0.1317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6878 | 0.6878 | 0.1609 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6815 | 0.6815 | 0.1363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7737 | 0.7737 | 0.1609 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7290 | 0.7290 | 0.1458 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.7717 | 5.3044 | 5.7717 | 1.3831 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.1212 | 4.5796 | 5.1212 | 1.3665 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.7058 | 5.4724 | 5.7058 | 1.4568 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5551 | 1.5551 | 0.7931 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1246 | 1.1246 | 0.7625 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2269 | 1.2269 | 0.7999 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4051 | 0.4051 | 0.1685 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3599 | 0.3599 | 0.1439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4491 | 0.4491 | 0.1796 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4120 | 0.4120 | 0.1648 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3262 | 0.3262 | 0.1670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3107 | 0.3107 | 0.1243 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3647 | 0.3647 | 0.1670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3292 | 0.3292 | 0.1317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3439 | 0.3439 | 0.1609 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3407 | 0.3407 | 0.1363 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3869 | 0.3869 | 0.1609 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3645 | 0.3645 | 0.1458 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8858 | 1.3831 | 1.3831 | 1.3831 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5606 | 1.3665 | 1.3665 | 1.3665 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.8529 | 1.4568 | 1.4568 | 1.4568 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 122.50 |
Number of hours cooling loads not met | 318.50 |
Number of hours not met | 441.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 28.07 | 85850.00 | 20.73 | 46507.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 293.87 | 73716.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 202.97 | 21377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 49.37 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.66 | 833.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 120.40 | 33449.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 99.47 | 9222.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1411.79 |
Natural Gas | 0.00 | 120.20 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1531.98 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 40.74 |
Space Heating | 5.63 |
Space Cooling | 58.98 |
Fans (All) | 24.17 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 283.37 |
Subtotal | 283.37 |
Natural Gas [MJ/m2] | |
Space Heating | 4.16 |
Service Water Heating | 19.97 |
Miscellaneous (All) | 24.13 |
Subtotal | 24.13 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 13.25 |
Space Heating | 3.19 |
Space Cooling | 19.18 |
Fans (All) | 7.86 |
Service Water Heating | 6.49 |
Receptacle Equipment | 46.05 |
Miscellaneous | 3.98 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8690.50 | 69.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8716.17 | 43.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8686.33 | 73.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8713.17 | 46.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8733.33 | 26.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8713.83 | 46.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8701.00 | 59.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8727.83 | 32.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8701.17 | 58.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8536.83 | 223.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8536.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 223.17 | 0.00 | 0.00 | 0.00 |
Average | 8720.16 | 39.84 | 0.00 | 0.00 | 0.00 |
Sum | 156962.83 | 717.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128302.33 | 1.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24907.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 2.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.13 | 0.20 | 0.00 | 0.00 | 0.00 |
Sum | 614576.33 | 3.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8515.33 | 244.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8590.17 | 169.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8672.50 | 87.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8632.83 | 127.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8557.33 | 202.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8599.50 | 160.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8564.17 | 195.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8649.67 | 110.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8567.33 | 192.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8572.17 | 187.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8555.33 | 204.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8607.83 | 152.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8532.50 | 227.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8566.17 | 193.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8538.00 | 222.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8396.83 | 363.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8676.00 | 84.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8698.33 | 61.67 | 0.00 | 0.00 | 0.00 |
Min | 8396.83 | 61.67 | 0.00 | 0.00 | 0.00 |
Max | 8698.33 | 363.17 | 0.00 | 0.00 | 0.00 |
Average | 8582.89 | 177.11 | 0.00 | 0.00 | 0.00 |
Sum | 154492.00 | 3188.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128189.00 | 115.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128231.00 | 73.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128234.00 | 70.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24900.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24900.33 | 8.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14011.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24907.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14014.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24714.83 | 194.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14014.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24906.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10132.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24906.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14014.00 | 2.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128234.00 | 194.17 | 0.00 | 0.00 | 0.00 |
Average | 34115.87 | 27.46 | 0.00 | 0.00 | 0.00 |
Sum | 614085.67 | 494.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:18
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138829E+11 | 18271.51 | 12-JAN-08:02 | 5.05 | 2.36 | 0.197698E+10 | 2608.75 | 23-JAN-10:20 | 5.97 | 4.15 |
February | 0.137966E+11 | 18967.57 | 23-FEB-06:03 | 10.60 | 5.29 | 0.179815E+10 | 2606.78 | 13-FEB-10:09 | 10.60 | 5.29 |
March | 0.178386E+11 | 24037.65 | 17-MAR-05:03 | 3.72 | -1.9 | 0.215360E+10 | 2606.62 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.204089E+11 | 37698.53 | 29-APR-05:03 | 17.70 | 12.15 | 0.191665E+10 | 2606.68 | 27-APR-09:09 | 17.70 | 12.15 |
May | 0.249945E+11 | 40133.32 | 30-MAY-04:03 | 25.00 | 11.58 | 0.207637E+10 | 2606.70 | 08-MAY-09:09 | 25.00 | 11.58 |
June | 0.265611E+11 | 40905.97 | 05-JUN-04:03 | 22.93 | 14.00 | 0.207053E+10 | 2606.66 | 12-JUN-09:00 | 30.00 | 13.95 |
July | 0.261212E+11 | 42211.10 | 05-JUL-04:02 | 19.08 | 16.04 | 0.192452E+10 | 2717.75 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.279529E+11 | 40975.79 | 14-AUG-04:03 | 17.70 | 16.58 | 0.216014E+10 | 2606.66 | 30-AUG-09:00 | 25.00 | 16.34 |
September | 0.249944E+11 | 41517.03 | 05-SEP-04:02 | 16.60 | 15.64 | 0.191838E+10 | 2606.66 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.231897E+11 | 39093.48 | 25-OCT-05:02 | 7.12 | 5.46 | 0.199337E+10 | 2606.73 | 17-OCT-09:00 | 7.12 | 5.46 |
November | 0.181413E+11 | 38986.28 | 13-NOV-06:02 | 2.30 | 0.06 | 0.197000E+10 | 2606.62 | 09-NOV-10:00 | 2.30 | 0.06 |
December | 0.133977E+11 | 18836.39 | 12-DEC-08:03 | 1.28 | -2.3 | 0.190659E+10 | 2606.61 | 04-DEC-10:09 | 1.28 | -2.3 |
Annual Sum or Average | 0.251280E+12 | 0.238653E+11 | ||||||||
Minimum of Months | 0.133977E+11 | 18271.51 | 1.28 | -2.3 | 0.179815E+10 | 2606.61 | 1.28 | -2.3 | ||
Maximum of Months | 0.279529E+11 | 42211.10 | 25.00 | 16.58 | 0.216014E+10 | 2717.75 | 30.00 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.413513E+09 | 2555.62 | 12-JAN-15:10 | 18.90 | 10.04 | 0.00 | 0.00 | 01-JAN-00:10 | 18.90 | 10.04 |
February | 0.794867E+09 | 3998.06 | 22-FEB-14:30 | 21.95 | 7.96 | 0.00 | 0.00 | 01-FEB-00:10 | 21.95 | 7.96 |
March | 0.172813E+10 | 5403.50 | 16-MAR-14:30 | 22.80 | 9.03 | 0.00 | 0.00 | 01-MAR-00:10 | 22.80 | 9.03 |
April | 0.380439E+10 | 8744.43 | 28-APR-14:40 | 28.90 | 14.03 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 14.03 |
May | 0.618980E+10 | 10672.59 | 30-MAY-14:20 | 34.40 | 17.58 | 0.00 | 0.00 | 01-MAY-00:10 | 34.40 | 17.58 |
June | 0.842771E+10 | 11214.46 | 15-JUN-14:40 | 38.13 | 15.82 | 0.00 | 0.00 | 01-JUN-00:10 | 38.13 | 15.82 |
July | 0.787089E+10 | 11554.94 | 03-JUL-13:00 | 36.70 | 18.58 | 0.00 | 0.00 | 01-JUL-00:10 | 36.70 | 18.58 |
August | 0.727358E+10 | 11111.42 | 07-AUG-15:00 | 35.00 | 18.74 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 18.74 |
September | 0.583025E+10 | 9742.67 | 19-SEP-15:10 | 33.40 | 16.39 | 0.00 | 0.00 | 01-SEP-00:10 | 33.40 | 16.39 |
October | 0.319921E+10 | 8827.65 | 03-OCT-14:30 | 32.25 | 19.38 | 0.00 | 0.00 | 01-OCT-00:10 | 32.25 | 19.38 |
November | 0.113666E+10 | 4666.01 | 03-NOV-15:30 | 23.60 | 13.51 | 0.00 | 0.00 | 01-NOV-00:10 | 23.60 | 13.51 |
December | 0.274062E+09 | 1672.26 | 09-DEC-13:30 | 17.50 | 7.28 | 0.00 | 0.00 | 01-DEC-00:10 | 17.50 | 7.28 |
Annual Sum or Average | 0.469431E+11 | 0.00 | ||||||||
Minimum of Months | 0.274062E+09 | 1672.26 | 17.50 | 7.28 | 0.00 | 0.00 | 17.50 | 7.28 | ||
Maximum of Months | 0.842771E+10 | 11554.94 | 38.13 | 19.38 | 0.00 | 0.00 | 38.13 | 19.38 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144855E+09 | 1826.60 | 05-JAN-07:01 | -0.9 | -5.5 | 0.00 | 0.00 | 01-JAN-00:10 | -0.9 | -5.5 |
February | 0.217469E+09 | 2194.19 | 09-FEB-07:01 | 0.78 | -2.4 | 0.00 | 0.00 | 01-FEB-00:10 | 0.78 | -2.4 |
March | 0.477194E+09 | 2125.06 | 30-MAR-06:01 | -0.1 | -3.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -3.7 |
April | 0.160297E+10 | 3048.54 | 21-APR-15:50 | 31.28 | 14.93 | 0.00 | 0.00 | 01-APR-00:10 | 31.28 | 14.93 |
May | 0.316556E+10 | 4740.50 | 30-MAY-16:00 | 33.90 | 17.46 | 0.00 | 0.00 | 01-MAY-00:10 | 33.90 | 17.46 |
June | 0.438004E+10 | 4997.22 | 19-JUN-07:10 | 24.50 | 16.82 | 0.00 | 0.00 | 01-JUN-00:10 | 24.50 | 16.82 |
July | 0.423460E+10 | 5238.50 | 03-JUL-14:50 | 37.30 | 18.89 | 0.00 | 0.00 | 01-JUL-00:10 | 37.30 | 18.89 |
August | 0.403863E+10 | 5078.30 | 07-AUG-15:00 | 35.00 | 18.74 | 0.00 | 0.00 | 01-AUG-00:10 | 35.00 | 18.74 |
September | 0.313368E+10 | 4461.16 | 05-SEP-15:30 | 31.10 | 19.25 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 19.25 |
October | 0.171738E+10 | 3684.02 | 05-OCT-16:00 | 31.10 | 17.21 | 0.00 | 0.00 | 01-OCT-00:10 | 31.10 | 17.21 |
November | 0.391572E+09 | 1924.35 | 10-NOV-16:00 | 15.00 | 9.95 | 0.00 | 0.00 | 01-NOV-00:10 | 15.00 | 9.95 |
December | 97887176.14 | 1564.91 | 14-DEC-07:01 | 2.30 | 1.51 | 0.00 | 0.00 | 01-DEC-00:10 | 2.30 | 1.51 |
Annual Sum or Average | 0.236018E+11 | 0.00 | ||||||||
Minimum of Months | 97887176.14 | 1564.91 | -0.9 | -5.5 | 0.00 | 0.00 | -0.9 | -5.5 | ||
Maximum of Months | 0.438004E+10 | 5238.50 | 37.30 | 19.25 | 0.00 | 0.00 | 37.30 | 19.25 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.331763E+09 | 2535.34 | 05-JAN-07:01 | -0.9 | -5.5 | 0.00 | 0.00 | 01-JAN-00:10 | -0.9 | -5.5 |
February | 0.519032E+09 | 2580.77 | 09-FEB-07:01 | 0.78 | -2.4 | 0.00 | 0.00 | 01-FEB-00:10 | 0.78 | -2.4 |
March | 0.991947E+09 | 2921.77 | 30-MAR-06:01 | -0.1 | -3.7 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -3.7 |
April | 0.208843E+10 | 3240.48 | 21-APR-15:50 | 31.28 | 14.93 | 0.00 | 0.00 | 01-APR-00:10 | 31.28 | 14.93 |
May | 0.351016E+10 | 5304.65 | 30-MAY-12:07 | 31.20 | 15.49 | 0.00 | 0.00 | 01-MAY-00:10 | 31.20 | 15.49 |
June | 0.454463E+10 | 6012.78 | 05-JUN-12:07 | 34.68 | 16.27 | 0.00 | 0.00 | 01-JUN-00:10 | 34.68 | 16.27 |
July | 0.449991E+10 | 6715.62 | 03-JUL-12:09 | 35.78 | 18.54 | 0.00 | 0.00 | 01-JUL-00:10 | 35.78 | 18.54 |
August | 0.456167E+10 | 5473.76 | 01-AUG-12:08 | 30.92 | 20.18 | 0.00 | 0.00 | 01-AUG-00:10 | 30.92 | 20.18 |
September | 0.387667E+10 | 5399.94 | 05-SEP-06:15 | 17.43 | 15.20 | 0.00 | 0.00 | 01-SEP-00:10 | 17.43 | 15.20 |
October | 0.262316E+10 | 4058.40 | 05-OCT-17:10 | 28.22 | 17.73 | 0.00 | 0.00 | 01-OCT-00:10 | 28.22 | 17.73 |
November | 0.102375E+10 | 2728.41 | 10-NOV-15:40 | 15.20 | 10.03 | 0.00 | 0.00 | 01-NOV-00:10 | 15.20 | 10.03 |
December | 0.241890E+09 | 2094.58 | 21-DEC-07:01 | 0.60 | -2.5 | 0.00 | 0.00 | 01-DEC-00:10 | 0.60 | -2.5 |
Annual Sum or Average | 0.288130E+11 | 0.00 | ||||||||
Minimum of Months | 0.241890E+09 | 2094.58 | -0.9 | -5.5 | 0.00 | 0.00 | -0.9 | -5.5 | ||
Maximum of Months | 0.456167E+10 | 6715.62 | 35.78 | 20.18 | 0.00 | 0.00 | 35.78 | 20.18 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.817152E+10 | 8222.45 | 04-JAN-17:00 | 11.70 | 2.84 | 0.182701E+10 | 2606.54 | 13-JAN-14:20 | 17.97 | 8.78 |
February | 0.828078E+10 | 10213.03 | 22-FEB-17:00 | 21.70 | 8.09 | 0.171494E+10 | 2606.60 | 23-FEB-10:09 | 13.48 | 7.26 |
March | 0.108856E+11 | 11849.82 | 16-MAR-16:00 | 22.20 | 8.37 | 0.210474E+10 | 2606.62 | 22-MAR-09:09 | 15.15 | 5.68 |
April | 0.136626E+11 | 21450.81 | 29-APR-05:03 | 17.70 | 12.15 | 0.190545E+10 | 2606.66 | 27-APR-09:09 | 17.70 | 12.15 |
May | 0.175181E+11 | 29143.03 | 30-MAY-04:03 | 25.00 | 11.58 | 0.207259E+10 | 2606.68 | 08-MAY-09:09 | 25.00 | 11.58 |
June | 0.193589E+11 | 29777.87 | 12-JUN-04:03 | 17.93 | 6.78 | 0.206837E+10 | 2606.65 | 12-JUN-09:39 | 28.70 | 13.17 |
July | 0.191382E+11 | 30867.45 | 05-JUL-04:02 | 19.08 | 16.04 | 0.192190E+10 | 2668.16 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.196484E+11 | 30385.19 | 14-AUG-04:03 | 17.70 | 16.58 | 0.215754E+10 | 2606.65 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.169374E+11 | 31215.21 | 05-SEP-04:02 | 16.60 | 15.64 | 0.191498E+10 | 2606.65 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.145840E+11 | 28960.51 | 06-OCT-05:03 | 13.22 | 11.60 | 0.198255E+10 | 2606.69 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.101809E+11 | 13384.47 | 10-NOV-16:50 | 14.50 | 9.32 | 0.190521E+10 | 2606.61 | 01-NOV-09:09 | 14.50 | 9.32 |
December | 0.777476E+10 | 6979.62 | 15-DEC-17:00 | 15.00 | 5.87 | 0.173424E+10 | 2576.71 | 01-DEC-14:00 | 15.00 | 5.87 |
Annual Sum or Average | 0.166141E+12 | 0.233095E+11 | ||||||||
Minimum of Months | 0.777476E+10 | 6979.62 | 11.70 | 2.84 | 0.171494E+10 | 2576.71 | 13.48 | 5.68 | ||
Maximum of Months | 0.196484E+11 | 31215.21 | 25.00 | 16.58 | 0.215754E+10 | 2668.16 | 28.70 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.700628E+10 | 7325.99 | 12-JAN-16:50 | 17.98 | 9.87 | 0.168019E+10 | 2544.19 | 04-JAN-14:00 | 17.98 | 9.87 |
February | 0.748448E+10 | 9631.34 | 22-FEB-15:40 | 22.60 | 8.36 | 0.160200E+10 | 2606.53 | 07-FEB-14:09 | 22.60 | 8.36 |
March | 0.101842E+11 | 12930.93 | 16-MAR-16:00 | 22.20 | 8.37 | 0.201189E+10 | 2606.57 | 09-MAR-14:09 | 22.20 | 8.37 |
April | 0.135424E+11 | 16251.41 | 28-APR-15:40 | 28.50 | 13.78 | 0.188434E+10 | 2606.66 | 27-APR-09:09 | 28.50 | 13.78 |
May | 0.182593E+11 | 31605.97 | 22-MAY-05:03 | 17.98 | 13.97 | 0.206804E+10 | 2606.66 | 08-MAY-09:09 | 17.98 | 13.97 |
June | 0.210835E+11 | 32496.16 | 05-JUN-04:03 | 22.93 | 14.00 | 0.206841E+10 | 2606.65 | 12-JUN-09:00 | 30.00 | 13.95 |
July | 0.207242E+11 | 32809.69 | 17-JUL-04:03 | 20.60 | 20.13 | 0.192278E+10 | 2676.44 | 20-JUL-15:30 | 25.25 | 22.87 |
August | 0.206008E+11 | 31814.78 | 14-AUG-05:03 | 17.30 | 16.19 | 0.215638E+10 | 2606.65 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.169565E+11 | 31674.95 | 18-SEP-05:03 | 18.30 | 13.86 | 0.190973E+10 | 2606.64 | 11-SEP-09:50 | 18.30 | 13.86 |
October | 0.135358E+11 | 29242.38 | 02-OCT-04:02 | 24.82 | 15.04 | 0.195617E+10 | 2606.66 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.879862E+10 | 13134.37 | 10-NOV-15:00 | 15.60 | 10.20 | 0.179738E+10 | 2606.58 | 09-NOV-10:00 | 15.60 | 10.20 |
December | 0.641325E+10 | 6745.52 | 15-DEC-17:00 | 15.00 | 5.87 | 0.158044E+10 | 2475.65 | 01-DEC-14:00 | 15.00 | 5.87 |
Annual Sum or Average | 0.164589E+12 | 0.226377E+11 | ||||||||
Minimum of Months | 0.641325E+10 | 6745.52 | 15.00 | 5.87 | 0.158044E+10 | 2475.65 | 15.00 | 5.87 | ||
Maximum of Months | 0.210835E+11 | 32809.69 | 28.50 | 20.13 | 0.215638E+10 | 2676.44 | 30.00 | 22.87 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.796086E+09 | 1414.22 | 12-JAN-14:30 | 18.60 | 9.87 | 0.323618E+09 | 507.83 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.108347E+10 | 1852.19 | 22-FEB-15:00 | 22.20 | 8.00 | 0.310151E+09 | 549.46 | 07-FEB-14:00 | 22.20 | 8.00 |
March | 0.179873E+10 | 3087.73 | 22-MAR-14:40 | 24.07 | 8.96 | 0.397385E+09 | 549.48 | 16-MAR-13:00 | 24.07 | 8.96 |
April | 0.312830E+10 | 5379.44 | 21-APR-15:20 | 31.83 | 15.27 | 0.388113E+09 | 549.50 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.514424E+10 | 8307.06 | 21-MAY-15:22 | 34.40 | 18.05 | 0.435161E+09 | 549.50 | 16-MAY-09:00 | 34.40 | 18.05 |
June | 0.684306E+10 | 11680.32 | 18-JUN-15:42 | 37.12 | 16.83 | 0.436591E+09 | 549.50 | 27-JUN-09:50 | 25.50 | 15.70 |
July | 0.652052E+10 | 11741.78 | 02-JUL-16:22 | 38.05 | 18.71 | 0.406195E+09 | 561.00 | 20-JUL-14:00 | 24.40 | 22.82 |
August | 0.590173E+10 | 10263.62 | 06-AUG-15:42 | 36.10 | 18.28 | 0.454588E+09 | 549.50 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.440586E+10 | 5813.74 | 20-SEP-14:30 | 33.30 | 17.76 | 0.400270E+09 | 549.50 | 26-SEP-13:20 | 25.97 | 15.08 |
October | 0.285901E+10 | 6353.66 | 02-OCT-04:02 | 24.82 | 15.04 | 0.400078E+09 | 549.50 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.139578E+10 | 2533.77 | 09-NOV-15:40 | 23.30 | 12.89 | 0.350919E+09 | 549.47 | 09-NOV-14:09 | 23.30 | 12.89 |
December | 0.617240E+09 | 1256.98 | 08-DEC-15:30 | 17.20 | 7.54 | 0.305755E+09 | 480.75 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.404940E+11 | 0.460882E+10 | ||||||||
Minimum of Months | 0.617240E+09 | 1256.98 | 17.20 | 7.54 | 0.305755E+09 | 480.75 | 17.20 | 7.54 | ||
Maximum of Months | 0.684306E+10 | 11741.78 | 38.05 | 18.71 | 0.454588E+09 | 561.00 | 34.40 | 22.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.943888E+09 | 1277.44 | 04-JAN-10:30 | 10.00 | 3.23 | 0.217545E+09 | 347.32 | 04-JAN-10:39 | 10.20 | 3.29 |
February | 0.122073E+10 | 2638.36 | 21-FEB-10:30 | 18.35 | 7.04 | 0.212932E+09 | 347.87 | 24-FEB-10:20 | 7.77 | 2.42 |
March | 0.208642E+10 | 3807.29 | 16-MAR-10:10 | 19.18 | 7.83 | 0.269479E+09 | 347.87 | 06-MAR-10:09 | 19.18 | 7.83 |
April | 0.360795E+10 | 10135.88 | 30-APR-10:53 | 25.00 | 12.86 | 0.252940E+09 | 347.89 | 05-APR-09:00 | 25.00 | 12.86 |
May | 0.522432E+10 | 11114.56 | 21-MAY-10:02 | 27.77 | 13.68 | 0.276674E+09 | 348.23 | 17-MAY-09:50 | 27.77 | 13.68 |
June | 0.634050E+10 | 10872.13 | 18-JUN-09:42 | 31.13 | 16.72 | 0.276633E+09 | 348.20 | 27-JUN-09:00 | 25.60 | 15.68 |
July | 0.591773E+10 | 10943.73 | 02-JUL-09:42 | 30.73 | 19.96 | 0.257438E+09 | 348.29 | 03-JUL-09:00 | 32.20 | 18.73 |
August | 0.564361E+10 | 10924.28 | 06-AUG-09:42 | 30.22 | 17.70 | 0.287976E+09 | 348.18 | 09-AUG-09:39 | 29.43 | 19.02 |
September | 0.459518E+10 | 10827.84 | 03-SEP-10:02 | 26.10 | 19.11 | 0.255065E+09 | 348.34 | 11-SEP-09:00 | 25.60 | 12.20 |
October | 0.293563E+10 | 6350.40 | 01-OCT-10:53 | 27.80 | 14.50 | 0.258749E+09 | 347.89 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.148356E+10 | 4294.96 | 10-NOV-09:20 | 18.67 | 11.91 | 0.236944E+09 | 347.87 | 09-NOV-10:00 | 18.67 | 11.91 |
December | 0.796688E+09 | 1153.52 | 01-DEC-10:30 | 13.05 | 5.08 | 0.202182E+09 | 321.47 | 01-DEC-10:39 | 13.33 | 5.28 |
Annual Sum or Average | 0.407962E+11 | 0.300455E+10 | ||||||||
Minimum of Months | 0.796688E+09 | 1153.52 | 10.00 | 3.23 | 0.202182E+09 | 321.47 | 7.77 | 2.42 | ||
Maximum of Months | 0.634050E+10 | 11114.56 | 31.13 | 19.96 | 0.287976E+09 | 348.34 | 32.20 | 19.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288384E+10 | 8545.74 | 12-JAN-14:30 | 18.60 | 9.87 | 0.383086E+09 | 549.53 | 12-JAN-14:39 | 18.70 | 9.92 |
February | 0.296999E+10 | 13417.42 | 20-FEB-14:23 | 22.75 | 8.67 | 0.351674E+09 | 549.66 | 22-FEB-14:09 | 21.78 | 7.94 |
March | 0.377840E+10 | 8184.91 | 16-MAR-13:30 | 22.50 | 9.16 | 0.424003E+09 | 549.68 | 16-MAR-13:00 | 22.80 | 9.34 |
April | 0.463291E+10 | 11876.82 | 16-APR-13:43 | 29.72 | 13.75 | 0.391890E+09 | 549.78 | 21-APR-13:39 | 32.03 | 15.02 |
May | 0.566629E+10 | 12079.53 | 21-MAY-13:23 | 34.45 | 17.50 | 0.434332E+09 | 549.50 | 05-MAY-13:00 | 34.45 | 17.50 |
June | 0.678937E+10 | 12481.97 | 18-JUN-15:42 | 37.12 | 16.83 | 0.436291E+09 | 549.50 | 12-JUN-09:00 | 37.12 | 16.83 |
July | 0.672815E+10 | 12990.07 | 02-JUL-15:42 | 38.22 | 18.83 | 0.406013E+09 | 557.96 | 20-JUL-14:00 | 24.40 | 22.82 |
August | 0.720717E+10 | 13399.89 | 27-AUG-12:43 | 34.22 | 16.72 | 0.454666E+09 | 550.17 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.718366E+10 | 13710.54 | 17-SEP-11:43 | 31.02 | 15.63 | 0.401984E+09 | 549.87 | 15-SEP-13:00 | 31.02 | 15.63 |
October | 0.630232E+10 | 14360.35 | 29-OCT-12:22 | 23.60 | 11.63 | 0.410543E+09 | 560.58 | 03-OCT-13:39 | 23.60 | 11.63 |
November | 0.430994E+10 | 13684.64 | 11-NOV-12:32 | 17.93 | 8.04 | 0.389062E+09 | 549.83 | 08-NOV-14:50 | 17.93 | 8.04 |
December | 0.256296E+10 | 6672.92 | 07-DEC-14:10 | 15.68 | 6.76 | 0.366445E+09 | 549.49 | 01-DEC-14:09 | 15.68 | 6.76 |
Annual Sum or Average | 0.610150E+11 | 0.484999E+10 | ||||||||
Minimum of Months | 0.256296E+10 | 6672.92 | 15.68 | 6.76 | 0.351674E+09 | 549.49 | 15.68 | 6.76 | ||
Maximum of Months | 0.720717E+10 | 14360.35 | 38.22 | 18.83 | 0.454666E+09 | 560.58 | 37.12 | 22.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.986509E+09 | 3125.99 | 12-JAN-15:30 | 18.90 | 10.10 | 0.214077E+09 | 347.83 | 12-JAN-14:00 | 18.90 | 10.10 |
February | 0.124515E+10 | 4457.22 | 21-FEB-16:50 | 22.30 | 7.87 | 0.199896E+09 | 347.84 | 22-FEB-14:00 | 22.20 | 8.00 |
March | 0.224186E+10 | 5727.42 | 14-MAR-16:00 | 24.40 | 10.33 | 0.250261E+09 | 347.84 | 09-MAR-14:09 | 24.40 | 10.33 |
April | 0.357582E+10 | 12526.81 | 16-APR-17:02 | 29.90 | 11.43 | 0.242345E+09 | 347.85 | 26-APR-13:00 | 26.70 | 13.80 |
May | 0.512621E+10 | 12898.47 | 29-MAY-16:42 | 32.88 | 16.50 | 0.273574E+09 | 347.85 | 03-MAY-13:00 | 32.88 | 16.50 |
June | 0.611763E+10 | 12903.23 | 25-JUN-17:12 | 31.50 | 16.72 | 0.275994E+09 | 347.85 | 12-JUN-09:00 | 31.50 | 16.72 |
July | 0.573188E+10 | 12815.83 | 09-JUL-16:32 | 32.97 | 19.28 | 0.256767E+09 | 347.85 | 03-JUL-09:09 | 32.97 | 19.28 |
August | 0.547420E+10 | 12865.53 | 06-AUG-17:02 | 36.02 | 18.72 | 0.286933E+09 | 347.85 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.460748E+10 | 12460.13 | 17-SEP-15:42 | 32.80 | 15.93 | 0.251993E+09 | 347.85 | 26-SEP-13:20 | 25.97 | 15.08 |
October | 0.323767E+10 | 11168.68 | 08-OCT-15:32 | 26.30 | 17.27 | 0.249961E+09 | 347.85 | 02-OCT-09:09 | 26.30 | 17.27 |
November | 0.174904E+10 | 5208.55 | 09-NOV-15:30 | 23.30 | 12.82 | 0.224712E+09 | 347.84 | 08-NOV-14:00 | 23.30 | 12.82 |
December | 0.797180E+09 | 2292.97 | 15-DEC-16:00 | 15.60 | 6.14 | 0.203540E+09 | 347.74 | 15-DEC-14:00 | 15.60 | 6.14 |
Annual Sum or Average | 0.408906E+11 | 0.293005E+10 | ||||||||
Minimum of Months | 0.797180E+09 | 2292.97 | 15.60 | 6.14 | 0.199896E+09 | 347.74 | 15.60 | 6.14 | ||
Maximum of Months | 0.611763E+10 | 12903.23 | 36.02 | 19.28 | 0.286933E+09 | 347.85 | 32.97 | 19.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118065E+10 | 1343.65 | 12-JAN-13:06 | 16.97 | 8.98 | 0.332212E+09 | 502.81 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.117854E+10 | 1672.14 | 20-FEB-15:02 | 23.30 | 8.84 | 0.308981E+09 | 528.35 | 23-FEB-14:50 | 21.28 | 7.21 |
March | 0.161182E+10 | 1462.75 | 22-MAR-14:50 | 23.98 | 8.91 | 0.386905E+09 | 541.19 | 15-MAR-13:00 | 23.98 | 8.91 |
April | 0.225487E+10 | 3467.78 | 21-APR-15:20 | 31.83 | 15.27 | 0.385274E+09 | 549.49 | 27-APR-09:00 | 22.20 | 13.12 |
May | 0.378381E+10 | 4708.16 | 30-MAY-15:30 | 34.15 | 17.61 | 0.434399E+09 | 549.50 | 08-MAY-09:09 | 34.15 | 17.61 |
June | 0.530527E+10 | 5857.62 | 19-JUN-06:03 | 23.07 | 16.06 | 0.435802E+09 | 549.50 | 12-JUN-09:00 | 23.07 | 16.06 |
July | 0.563486E+10 | 7476.92 | 03-JUL-04:02 | 28.72 | 17.94 | 0.405584E+09 | 559.18 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.561877E+10 | 7511.88 | 07-AUG-06:03 | 25.18 | 16.26 | 0.454968E+09 | 549.50 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.459701E+10 | 6019.01 | 05-SEP-06:02 | 17.07 | 15.07 | 0.403273E+09 | 549.49 | 12-SEP-09:20 | 25.17 | 14.97 |
October | 0.316210E+10 | 4961.63 | 03-OCT-14:30 | 32.25 | 19.38 | 0.413900E+09 | 549.50 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.182523E+10 | 2291.68 | 10-NOV-12:00 | 21.10 | 12.09 | 0.375855E+09 | 549.48 | 09-NOV-10:50 | 21.10 | 12.09 |
December | 0.116291E+10 | 1308.53 | 01-DEC-14:10 | 14.22 | 6.46 | 0.320611E+09 | 498.98 | 01-DEC-14:39 | 13.67 | 6.12 |
Annual Sum or Average | 0.373158E+11 | 0.465776E+10 | ||||||||
Minimum of Months | 0.116291E+10 | 1308.53 | 14.22 | 6.46 | 0.308981E+09 | 498.98 | 13.67 | 6.12 | ||
Maximum of Months | 0.563486E+10 | 7511.88 | 34.15 | 19.38 | 0.454968E+09 | 559.18 | 34.15 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110824E+10 | 1361.21 | 04-JAN-10:10 | 9.60 | 3.11 | 0.230662E+09 | 347.86 | 31-JAN-10:09 | 11.88 | 4.56 |
February | 0.117457E+10 | 2293.41 | 21-FEB-10:30 | 18.35 | 7.04 | 0.218182E+09 | 347.87 | 17-FEB-10:09 | 18.35 | 7.04 |
March | 0.167908E+10 | 2743.18 | 31-MAR-09:50 | 18.25 | 6.32 | 0.271659E+09 | 347.87 | 06-MAR-10:09 | 18.25 | 6.32 |
April | 0.274875E+10 | 6004.29 | 30-APR-10:53 | 25.00 | 12.86 | 0.253776E+09 | 347.88 | 27-APR-09:09 | 25.00 | 12.86 |
May | 0.420444E+10 | 9266.17 | 21-MAY-10:02 | 27.77 | 13.68 | 0.276780E+09 | 348.10 | 30-MAY-09:00 | 28.90 | 14.30 |
June | 0.524298E+10 | 7929.31 | 18-JUN-09:42 | 31.13 | 16.72 | 0.276499E+09 | 348.11 | 13-JUN-09:30 | 31.13 | 16.72 |
July | 0.527351E+10 | 9816.17 | 04-JUL-09:32 | 27.57 | 18.80 | 0.257453E+09 | 348.18 | 28-JUL-09:00 | 30.60 | 19.45 |
August | 0.547302E+10 | 9879.33 | 06-AUG-09:32 | 29.83 | 17.77 | 0.288558E+09 | 348.08 | 09-AUG-09:30 | 29.15 | 19.01 |
September | 0.479359E+10 | 9698.08 | 04-SEP-09:42 | 25.63 | 18.58 | 0.256110E+09 | 348.24 | 15-SEP-09:50 | 27.43 | 19.66 |
October | 0.323374E+10 | 5400.08 | 05-OCT-09:10 | 25.37 | 18.00 | 0.264273E+09 | 347.89 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.181614E+10 | 4104.58 | 10-NOV-09:20 | 18.67 | 11.91 | 0.251838E+09 | 347.87 | 09-NOV-10:00 | 18.67 | 11.91 |
December | 0.108716E+10 | 1166.30 | 01-DEC-09:50 | 11.73 | 4.39 | 0.221121E+09 | 347.85 | 01-DEC-10:39 | 13.33 | 5.28 |
Annual Sum or Average | 0.378352E+11 | 0.306691E+10 | ||||||||
Minimum of Months | 0.108716E+10 | 1166.30 | 9.60 | 3.11 | 0.218182E+09 | 347.85 | 11.88 | 4.56 | ||
Maximum of Months | 0.547302E+10 | 9879.33 | 31.13 | 18.80 | 0.288558E+09 | 348.24 | 31.13 | 19.66 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179250E+10 | 7090.22 | 12-JAN-13:06 | 16.97 | 8.98 | 0.364183E+09 | 549.50 | 23-JAN-14:09 | 10.60 | 6.35 |
February | 0.171166E+10 | 10764.00 | 20-FEB-14:23 | 22.75 | 8.67 | 0.331647E+09 | 549.50 | 14-FEB-14:39 | 22.75 | 8.67 |
March | 0.208239E+10 | 5315.95 | 22-MAR-13:10 | 24.90 | 9.24 | 0.400270E+09 | 549.51 | 22-MAR-13:00 | 24.40 | 9.14 |
April | 0.327764E+10 | 9275.70 | 19-APR-12:00 | 30.60 | 14.04 | 0.380794E+09 | 575.77 | 19-APR-12:09 | 30.60 | 14.03 |
May | 0.495698E+10 | 10151.95 | 19-MAY-16:20 | 34.80 | 16.77 | 0.429813E+09 | 622.84 | 19-MAY-12:09 | 34.80 | 16.77 |
June | 0.683967E+10 | 11340.41 | 02-JUN-17:00 | 38.90 | 16.17 | 0.439429E+09 | 689.00 | 15-JUN-12:09 | 36.10 | 14.46 |
July | 0.708744E+10 | 11409.94 | 03-JUL-17:00 | 38.30 | 18.83 | 0.409081E+09 | 689.85 | 03-JUL-12:09 | 38.30 | 18.83 |
August | 0.784686E+10 | 11161.35 | 07-AUG-16:50 | 36.78 | 17.90 | 0.457792E+09 | 668.77 | 07-AUG-12:09 | 36.78 | 17.90 |
September | 0.790209E+10 | 11272.40 | 04-SEP-13:02 | 30.60 | 18.77 | 0.407448E+09 | 642.38 | 19-SEP-12:09 | 31.88 | 16.39 |
October | 0.620866E+10 | 11748.56 | 01-OCT-14:22 | 32.50 | 15.71 | 0.414776E+09 | 618.63 | 03-OCT-12:09 | 30.10 | 18.63 |
November | 0.370728E+10 | 11371.97 | 11-NOV-13:02 | 18.30 | 8.11 | 0.386470E+09 | 558.10 | 09-NOV-14:09 | 18.30 | 8.11 |
December | 0.166829E+10 | 6534.04 | 17-DEC-14:03 | 15.10 | 4.36 | 0.349245E+09 | 549.50 | 05-DEC-14:09 | 15.10 | 4.36 |
Annual Sum or Average | 0.550814E+11 | 0.477095E+10 | ||||||||
Minimum of Months | 0.166829E+10 | 5315.95 | 15.10 | 4.36 | 0.331647E+09 | 549.50 | 10.60 | 4.36 | ||
Maximum of Months | 0.790209E+10 | 11748.56 | 38.90 | 18.83 | 0.457792E+09 | 689.85 | 38.30 | 18.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117626E+10 | 2374.15 | 30-JAN-16:30 | 15.60 | 6.05 | 0.222857E+09 | 347.83 | 12-JAN-14:00 | 15.60 | 6.05 |
February | 0.114513E+10 | 3464.57 | 21-FEB-16:50 | 22.30 | 7.87 | 0.205012E+09 | 347.83 | 22-FEB-14:00 | 22.20 | 8.00 |
March | 0.169845E+10 | 3546.57 | 21-MAR-16:00 | 25.00 | 9.53 | 0.255738E+09 | 347.84 | 09-MAR-14:20 | 25.00 | 9.53 |
April | 0.256786E+10 | 9791.37 | 16-APR-16:51 | 30.00 | 11.43 | 0.247453E+09 | 347.85 | 27-APR-09:00 | 22.20 | 13.12 |
May | 0.400717E+10 | 9999.94 | 29-MAY-17:22 | 31.95 | 15.92 | 0.275682E+09 | 347.85 | 08-MAY-09:09 | 31.95 | 15.92 |
June | 0.495150E+10 | 9982.78 | 04-JUN-16:32 | 35.20 | 17.04 | 0.276253E+09 | 347.85 | 12-JUN-09:00 | 30.00 | 13.95 |
July | 0.500919E+10 | 9982.30 | 04-JUL-15:31 | 34.23 | 18.80 | 0.257107E+09 | 347.85 | 03-JUL-09:09 | 34.23 | 18.80 |
August | 0.522387E+10 | 10430.27 | 27-AUG-17:52 | 33.30 | 16.50 | 0.288417E+09 | 347.85 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.468438E+10 | 10353.91 | 10-SEP-16:32 | 30.77 | 16.63 | 0.255910E+09 | 347.85 | 11-SEP-09:50 | 25.32 | 12.16 |
October | 0.335934E+10 | 10038.89 | 01-OCT-15:42 | 31.88 | 15.58 | 0.263872E+09 | 347.86 | 17-OCT-09:00 | 21.10 | 16.29 |
November | 0.195231E+10 | 4735.43 | 09-NOV-16:10 | 23.22 | 12.98 | 0.244923E+09 | 347.84 | 09-NOV-10:50 | 23.22 | 12.98 |
December | 0.112870E+10 | 2181.28 | 15-DEC-16:10 | 15.50 | 6.10 | 0.214683E+09 | 347.84 | 01-DEC-14:00 | 15.50 | 6.10 |
Annual Sum or Average | 0.369042E+11 | 0.300791E+10 | ||||||||
Minimum of Months | 0.112870E+10 | 2181.28 | 15.50 | 6.05 | 0.205012E+09 | 347.83 | 15.50 | 6.05 | ||
Maximum of Months | 0.522387E+10 | 10430.27 | 35.20 | 18.80 | 0.288417E+09 | 347.86 | 34.23 | 18.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119742E+10 | 1560.19 | 12-JAN-14:30 | 18.60 | 9.87 | 0.338257E+09 | 527.99 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.137048E+10 | 2014.27 | 23-FEB-14:30 | 21.65 | 7.41 | 0.325229E+09 | 549.46 | 23-FEB-14:00 | 21.10 | 7.10 |
March | 0.198528E+10 | 2919.96 | 22-MAR-14:40 | 24.07 | 8.96 | 0.414985E+09 | 549.48 | 22-MAR-13:00 | 24.07 | 8.96 |
April | 0.307864E+10 | 4765.78 | 21-APR-15:20 | 31.83 | 15.27 | 0.395752E+09 | 549.50 | 27-APR-09:09 | 20.87 | 11.97 |
May | 0.486694E+10 | 7852.40 | 30-MAY-06:03 | 25.10 | 11.90 | 0.436656E+09 | 549.50 | 08-MAY-09:09 | 25.10 | 11.90 |
June | 0.626357E+10 | 9772.38 | 18-JUN-15:31 | 37.03 | 16.78 | 0.436646E+09 | 549.50 | 12-JUN-09:39 | 37.03 | 16.78 |
July | 0.598195E+10 | 8582.75 | 02-JUL-16:22 | 38.05 | 18.71 | 0.406095E+09 | 561.14 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.556415E+10 | 9787.07 | 06-AUG-16:51 | 36.10 | 18.82 | 0.455105E+09 | 549.50 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.429352E+10 | 5283.13 | 13-SEP-05:03 | 23.12 | 17.44 | 0.402752E+09 | 549.50 | 11-SEP-09:50 | 23.12 | 17.44 |
October | 0.297177E+10 | 6199.26 | 02-OCT-04:02 | 24.82 | 15.04 | 0.411092E+09 | 549.50 | 02-OCT-09:09 | 22.35 | 16.60 |
November | 0.170913E+10 | 2542.98 | 09-NOV-16:00 | 23.30 | 13.01 | 0.370044E+09 | 549.48 | 10-NOV-10:09 | 19.60 | 12.16 |
December | 0.102636E+10 | 1285.38 | 08-DEC-15:00 | 17.20 | 7.54 | 0.318971E+09 | 506.03 | 08-DEC-14:00 | 17.20 | 7.54 |
Annual Sum or Average | 0.403092E+11 | 0.471158E+10 | ||||||||
Minimum of Months | 0.102636E+10 | 1285.38 | 17.20 | 7.41 | 0.318971E+09 | 506.03 | 17.20 | 7.10 | ||
Maximum of Months | 0.626357E+10 | 9787.07 | 38.05 | 18.82 | 0.455105E+09 | 561.14 | 37.03 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115288E+10 | 1937.82 | 04-JAN-09:50 | 9.32 | 3.11 | 0.167658E+09 | 338.71 | 12-JAN-09:50 | 10.22 | 5.34 |
February | 0.140296E+10 | 3097.24 | 21-FEB-10:00 | 16.70 | 6.62 | 0.162109E+09 | 338.72 | 24-FEB-08:20 | 4.80 | 0.90 |
March | 0.223231E+10 | 4162.22 | 23-MAR-09:00 | 9.40 | 3.78 | 0.201602E+09 | 339.11 | 17-MAR-08:09 | 9.40 | 3.78 |
April | 0.352790E+10 | 10692.12 | 30-APR-08:42 | 19.72 | 12.65 | 0.187682E+09 | 338.85 | 28-APR-08:30 | 19.72 | 12.65 |
May | 0.488562E+10 | 10939.64 | 29-MAY-09:12 | 23.13 | 15.75 | 0.204792E+09 | 342.73 | 30-MAY-07:19 | 25.97 | 12.58 |
June | 0.579453E+10 | 11025.70 | 18-JUN-09:32 | 30.57 | 16.80 | 0.204444E+09 | 343.50 | 05-JUN-07:19 | 30.57 | 16.80 |
July | 0.539978E+10 | 11045.87 | 04-JUL-08:52 | 26.10 | 18.11 | 0.190866E+09 | 343.62 | 21-JUL-10:30 | 24.75 | 21.90 |
August | 0.526020E+10 | 11106.79 | 06-AUG-08:52 | 28.30 | 17.93 | 0.212904E+09 | 339.58 | 07-AUG-10:30 | 31.95 | 18.18 |
September | 0.438902E+10 | 10834.88 | 04-SEP-08:32 | 22.57 | 17.97 | 0.189062E+09 | 338.88 | 05-SEP-10:09 | 25.18 | 18.26 |
October | 0.298082E+10 | 6148.43 | 05-OCT-08:40 | 24.27 | 17.57 | 0.193305E+09 | 339.03 | 05-OCT-08:00 | 25.00 | 17.90 |
November | 0.172799E+10 | 4671.38 | 10-NOV-09:00 | 18.30 | 11.76 | 0.180027E+09 | 338.72 | 10-NOV-08:30 | 18.30 | 11.76 |
December | 0.103178E+10 | 1211.90 | 01-DEC-10:00 | 12.20 | 4.47 | 0.157115E+09 | 338.39 | 01-DEC-09:00 | 12.20 | 4.47 |
Annual Sum or Average | 0.397858E+11 | 0.225157E+10 | ||||||||
Minimum of Months | 0.103178E+10 | 1211.90 | 9.32 | 3.11 | 0.157115E+09 | 338.39 | 4.80 | 0.90 | ||
Maximum of Months | 0.579453E+10 | 11106.79 | 30.57 | 18.11 | 0.212904E+09 | 343.62 | 31.95 | 21.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338137E+10 | 8362.01 | 12-JAN-14:10 | 18.40 | 9.78 | 0.395817E+09 | 549.53 | 04-JAN-14:00 | 18.40 | 9.78 |
February | 0.331376E+10 | 10243.17 | 20-FEB-12:33 | 21.10 | 8.39 | 0.363036E+09 | 549.86 | 22-FEB-14:30 | 21.95 | 7.96 |
March | 0.396978E+10 | 7672.10 | 16-MAR-13:10 | 22.30 | 9.05 | 0.437132E+09 | 549.89 | 22-MAR-13:50 | 24.50 | 9.16 |
April | 0.448472E+10 | 11484.68 | 30-APR-13:23 | 29.40 | 12.42 | 0.398563E+09 | 549.77 | 28-APR-13:00 | 29.40 | 12.42 |
May | 0.529997E+10 | 7683.53 | 29-MAY-13:13 | 31.33 | 16.88 | 0.436578E+09 | 549.51 | 05-MAY-13:00 | 31.33 | 16.88 |
June | 0.618311E+10 | 10979.64 | 18-JUN-15:31 | 37.03 | 16.78 | 0.436552E+09 | 549.50 | 12-JUN-09:00 | 37.03 | 16.78 |
July | 0.612757E+10 | 9322.42 | 02-JUL-15:42 | 38.22 | 18.83 | 0.406105E+09 | 556.15 | 20-JUL-15:20 | 24.97 | 22.86 |
August | 0.675094E+10 | 11373.71 | 27-AUG-11:53 | 33.30 | 15.93 | 0.455412E+09 | 550.14 | 29-AUG-13:00 | 31.70 | 19.58 |
September | 0.688148E+10 | 12219.77 | 17-SEP-12:52 | 31.70 | 15.78 | 0.404075E+09 | 559.82 | 29-SEP-13:39 | 28.13 | 14.71 |
October | 0.633719E+10 | 12413.93 | 22-OCT-13:12 | 25.97 | 14.61 | 0.417581E+09 | 576.61 | 30-OCT-13:20 | 23.30 | 11.27 |
November | 0.478931E+10 | 12246.99 | 11-NOV-13:02 | 18.30 | 8.11 | 0.401044E+09 | 564.13 | 09-NOV-14:09 | 18.30 | 8.11 |
December | 0.310920E+10 | 7081.38 | 07-DEC-13:35 | 15.20 | 6.59 | 0.379867E+09 | 549.53 | 07-DEC-14:39 | 15.93 | 6.87 |
Annual Sum or Average | 0.606284E+11 | 0.493176E+10 | ||||||||
Minimum of Months | 0.310920E+10 | 7081.38 | 15.20 | 6.59 | 0.363036E+09 | 549.50 | 15.93 | 6.87 | ||
Maximum of Months | 0.688148E+10 | 12413.93 | 38.22 | 18.83 | 0.455412E+09 | 576.61 | 37.03 | 22.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126508E+10 | 3152.97 | 12-JAN-15:30 | 18.90 | 10.10 | 0.221624E+09 | 347.83 | 13-JAN-14:00 | 18.30 | 8.81 |
February | 0.144067E+10 | 4383.02 | 21-FEB-16:40 | 22.40 | 7.93 | 0.208082E+09 | 347.84 | 15-FEB-14:00 | 22.40 | 7.93 |
March | 0.232460E+10 | 7904.87 | 26-MAR-16:33 | 22.60 | 9.13 | 0.261439E+09 | 347.84 | 22-MAR-13:00 | 22.60 | 9.13 |
April | 0.340503E+10 | 11284.68 | 30-APR-16:41 | 30.10 | 12.63 | 0.248893E+09 | 347.85 | 27-APR-09:20 | 30.10 | 12.63 |
May | 0.477701E+10 | 11598.74 | 29-MAY-16:31 | 32.97 | 16.56 | 0.275919E+09 | 347.86 | 05-MAY-13:00 | 32.97 | 16.56 |
June | 0.560259E+10 | 11606.77 | 25-JUN-17:01 | 31.60 | 16.78 | 0.276366E+09 | 347.85 | 12-JUN-09:39 | 31.60 | 16.78 |
July | 0.523250E+10 | 11536.64 | 09-JUL-18:22 | 32.25 | 18.53 | 0.257009E+09 | 347.85 | 03-JUL-09:09 | 32.25 | 18.53 |
August | 0.512064E+10 | 11440.70 | 27-AUG-17:52 | 33.30 | 16.50 | 0.287961E+09 | 347.85 | 28-AUG-09:09 | 25.28 | 16.40 |
September | 0.437989E+10 | 11542.13 | 10-SEP-16:32 | 30.77 | 16.63 | 0.254734E+09 | 347.85 | 11-SEP-09:50 | 25.32 | 12.16 |
October | 0.320139E+10 | 11053.89 | 22-OCT-15:52 | 27.20 | 14.77 | 0.258712E+09 | 347.85 | 02-OCT-09:09 | 27.20 | 14.77 |
November | 0.197378E+10 | 5082.93 | 09-NOV-15:30 | 23.30 | 12.82 | 0.235278E+09 | 347.84 | 17-NOV-14:09 | 16.38 | 6.94 |
December | 0.109386E+10 | 2541.46 | 15-DEC-16:00 | 15.60 | 6.14 | 0.210906E+09 | 347.84 | 01-DEC-14:00 | 15.60 | 6.14 |
Annual Sum or Average | 0.398170E+11 | 0.299692E+10 | ||||||||
Minimum of Months | 0.109386E+10 | 2541.46 | 15.60 | 6.14 | 0.208082E+09 | 347.83 | 15.60 | 6.14 | ||
Maximum of Months | 0.560259E+10 | 11606.77 | 33.30 | 18.53 | 0.287961E+09 | 347.86 | 32.97 | 18.53 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 6.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 8.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 6.42 | |
Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168363E+10 | 8709.19 | 27-JAN-07:02 | -4.3 |
February | 0.120276E+10 | 9450.68 | 03-FEB-07:02 | -5.1 |
March | 0.102431E+10 | 8739.11 | 02-MAR-07:02 | -1.6 |
April | 0.426658E+09 | 4412.48 | 16-APR-07:47 | 16.97 |
May | 0.178730E+09 | 5313.40 | 22-MAY-05:03 | 17.98 |
June | 50234431.08 | 4981.70 | 13-JUN-05:03 | 15.18 |
July | 28350058.33 | 5342.87 | 05-JUL-04:02 | 19.08 |
August | 51775102.12 | 4359.92 | 28-AUG-04:03 | 22.12 |
September | 0.190118E+09 | 5695.62 | 05-SEP-04:02 | 16.60 |
October | 0.443503E+09 | 3618.16 | 25-OCT-05:02 | 7.12 |
November | 0.105082E+10 | 7911.63 | 28-NOV-07:01 | 0.87 |
December | 0.201289E+10 | 10270.38 | 27-DEC-07:02 | -4.3 |
Annual Sum or Average | 0.834377E+10 | |||
Minimum of Months | 28350058.33 | 3618.16 | -5.1 | |
Maximum of Months | 0.201289E+10 | 10270.38 | 22.12 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.956757E+09 | 2615.66 | 22-JAN-14:47 | 13.22 |
February | 0.559368E+09 | 3117.70 | 20-FEB-12:33 | 21.10 |
March | 0.320212E+09 | 2477.53 | 26-MAR-16:33 | 22.60 |
April | 31072648.88 | 2280.64 | 16-APR-15:13 | 29.60 |
May | 17358410.84 | 1776.58 | 07-MAY-16:22 | 29.15 |
June | 14115646.11 | 2261.48 | 18-JUN-15:31 | 37.03 |
July | 17062305.65 | 1880.83 | 02-JUL-15:42 | 38.22 |
August | 17509662.77 | 2149.95 | 06-AUG-15:31 | 36.10 |
September | 18391409.71 | 2229.59 | 10-SEP-15:12 | 31.10 |
October | 38623665.26 | 3978.70 | 08-OCT-15:23 | 26.40 |
November | 0.449825E+09 | 3678.99 | 19-NOV-12:33 | 15.73 |
December | 0.109784E+10 | 3219.35 | 17-DEC-14:03 | 15.10 |
Annual Sum or Average | 0.353813E+10 | |||
Minimum of Months | 14115646.11 | 1776.58 | 13.22 | |
Maximum of Months | 0.109784E+10 | 3978.70 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471472E+09 | 3262.69 | 24-JAN-08:04 | 4.97 |
February | 0.201656E+09 | 2652.01 | 03-FEB-08:13 | -1.1 |
March | 81329675.27 | 2912.93 | 17-MAR-05:03 | 3.72 |
April | 18896044.13 | 3909.16 | 11-APR-05:03 | 4.90 |
May | 18116221.18 | 3389.43 | 04-MAY-05:03 | 16.02 |
June | 16487011.82 | 2627.62 | 20-JUN-04:03 | 19.82 |
July | 21553559.97 | 2693.99 | 18-JUL-04:03 | 23.30 |
August | 25133103.41 | 2965.84 | 24-AUG-04:03 | 25.50 |
September | 28343954.83 | 3696.93 | 25-SEP-04:03 | 10.32 |
October | 43809239.00 | 4509.97 | 25-OCT-05:02 | 7.12 |
November | 0.169705E+09 | 5250.13 | 13-NOV-06:02 | 2.30 |
December | 0.565960E+09 | 3645.65 | 04-DEC-08:09 | 0.28 |
Annual Sum or Average | 0.166246E+10 | |||
Minimum of Months | 16487011.82 | 2627.62 | -1.1 | |
Maximum of Months | 0.565960E+09 | 5250.13 | 25.50 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1183208.13 | 11832.08 | 17-JAN-07:02 | 5.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.42 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
December | 2884616.26 | 16208.90 | 04-DEC-07:01 | -0.5 |
Annual Sum or Average | 4067824.39 | |||
Minimum of Months | 0.00 | 0.00 | -0.5 | |
Maximum of Months | 2884616.26 | 16208.90 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168883E+09 | 26363.96 | 17-JAN-06:01 | 4.50 |
February | 48846499.34 | 25471.76 | 02-FEB-07:01 | -4.0 |
March | 11517712.98 | 25466.54 | 02-MAR-07:01 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 53654446.68 | 26374.44 | 28-NOV-06:01 | 1.02 |
December | 0.345671E+09 | 27689.55 | 04-DEC-06:01 | -1.0 |
Annual Sum or Average | 0.628573E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.345671E+09 | 27689.55 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.782919E+09 | 9508.87 | 09-JAN-06:01 | 2.98 |
February | 0.393072E+09 | 9424.34 | 03-FEB-06:01 | -3.7 |
March | 0.169917E+09 | 9473.11 | 02-MAR-06:01 | -3.5 |
April | 4568193.91 | 8210.99 | 12-APR-06:02 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 975918.98 | 5440.38 | 25-OCT-06:02 | 6.88 |
November | 0.277032E+09 | 9476.45 | 27-NOV-06:01 | 3.30 |
December | 0.111224E+10 | 9979.94 | 04-DEC-05:02 | -0.7 |
Annual Sum or Average | 0.274073E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.111224E+10 | 9979.94 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.357739E+09 | 8365.17 | 09-JAN-06:01 | 2.98 |
February | 0.137111E+09 | 8293.77 | 03-FEB-06:01 | -3.7 |
March | 67873543.24 | 8343.09 | 02-MAR-06:01 | -3.5 |
April | 1043654.98 | 3858.10 | 12-APR-06:02 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 960486.38 | 5047.08 | 25-OCT-06:02 | 6.88 |
November | 0.109976E+09 | 8354.13 | 27-NOV-06:01 | 3.30 |
December | 0.488835E+09 | 8786.97 | 04-DEC-05:02 | -0.7 |
Annual Sum or Average | 0.116354E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.488835E+09 | 8786.97 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414904E+09 | 10290.95 | 09-JAN-06:01 | 2.98 |
February | 0.196427E+09 | 10227.12 | 03-FEB-06:01 | -3.7 |
March | 0.105656E+09 | 10243.08 | 02-MAR-06:01 | -3.5 |
April | 4279340.82 | 9053.29 | 12-APR-06:02 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 383491.71 | 3171.88 | 25-OCT-06:02 | 6.88 |
November | 0.129074E+09 | 10354.94 | 27-NOV-06:01 | 3.30 |
December | 0.553969E+09 | 10813.99 | 04-DEC-05:02 | -0.7 |
Annual Sum or Average | 0.140469E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.553969E+09 | 10813.99 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.450302E+09 | 8402.29 | 09-JAN-06:01 | 2.98 |
February | 0.234379E+09 | 8328.35 | 03-FEB-06:01 | -3.7 |
March | 95658210.95 | 8359.50 | 02-MAR-06:01 | -3.5 |
April | 3717907.11 | 6802.82 | 12-APR-06:02 | 3.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 725000.25 | 4081.11 | 25-OCT-06:02 | 6.88 |
November | 0.159545E+09 | 8399.99 | 27-NOV-06:01 | 3.30 |
December | 0.626364E+09 | 8800.65 | 04-DEC-05:02 | -0.7 |
Annual Sum or Average | 0.157069E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.626364E+09 | 8800.65 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103731E+09 | 6950.58 | 28-JAN-06:01 | -3.3 |
February | 74861722.62 | 6991.76 | 03-FEB-06:01 | -3.7 |
March | 38159559.33 | 7015.51 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 4727301.22 | 6760.60 | 28-NOV-07:01 | 0.87 |
December | 0.114536E+09 | 6979.94 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.336016E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.114536E+09 | 7015.51 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33351878.39 | 5111.16 | 28-JAN-07:03 | -2.9 |
February | 15034776.66 | 5143.61 | 09-FEB-07:01 | 0.78 |
March | 9018242.62 | 5238.98 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 791476.63 | 4934.01 | 28-NOV-07:01 | 0.87 |
December | 36725896.10 | 5263.29 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 94922270.40 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 36725896.10 | 5263.29 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126997E+10 | 10086.37 | 27-JAN-07:10 | -4.3 |
February | 0.114573E+10 | 10319.08 | 03-FEB-07:10 | -5.1 |
March | 0.101408E+10 | 9835.07 | 02-MAR-07:10 | -1.6 |
April | 0.340741E+09 | 8623.04 | 12-APR-06:10 | 3.87 |
May | 64276734.68 | 7486.05 | 02-MAY-06:10 | 9.87 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 26964671.72 | 7430.35 | 25-SEP-06:05 | 10.55 |
October | 0.223222E+09 | 7860.72 | 25-OCT-06:10 | 6.88 |
November | 0.715434E+09 | 9220.39 | 28-NOV-07:10 | 0.87 |
December | 0.147215E+10 | 10627.52 | 27-DEC-07:10 | -4.3 |
Annual Sum or Average | 0.627257E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.147215E+10 | 10627.52 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36609032.12 | 5080.48 | 28-JAN-07:03 | -2.9 |
February | 27406046.53 | 5070.04 | 03-FEB-07:02 | -5.1 |
March | 10472891.18 | 5048.70 | 02-MAR-07:02 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 1726657.42 | 4818.32 | 28-NOV-07:01 | 0.87 |
December | 43819109.83 | 5249.63 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.120034E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 43819109.83 | 5249.63 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132257E+09 | 7433.36 | 28-JAN-06:01 | -3.3 |
February | 53972438.24 | 7320.35 | 03-FEB-06:01 | -3.7 |
March | 15274467.91 | 7317.27 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 25349958.01 | 7386.09 | 28-NOV-06:01 | 1.02 |
December | 0.230959E+09 | 7691.30 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.457813E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.230959E+09 | 7691.30 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65943505.81 | 5956.07 | 17-JAN-06:01 | 4.50 |
February | 20636971.51 | 5833.85 | 03-FEB-06:01 | -3.7 |
March | 8917700.51 | 5797.08 | 02-MAR-06:01 | -3.5 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 8484450.33 | 5808.37 | 28-NOV-06:01 | 1.02 |
December | 0.106981E+09 | 6128.43 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.210964E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.7 | |
Maximum of Months | 0.106981E+09 | 6128.43 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 55964572.51 | 8017.89 | 26-JAN-07:01 | 0.60 |
February | 20768362.94 | 7995.31 | 02-FEB-07:01 | -4.0 |
March | 6545964.03 | 7988.87 | 02-MAR-07:01 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 8625870.14 | 7996.25 | 28-NOV-07:01 | 0.87 |
December | 0.100997E+09 | 8584.34 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.192902E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.100997E+09 | 8584.34 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76560014.39 | 5733.46 | 28-JAN-06:01 | -3.3 |
February | 33341701.91 | 5466.94 | 28-FEB-07:02 | 5.18 |
March | 9313318.28 | 5394.64 | 02-MAR-07:01 | -1.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 25.03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 27.63 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 27.32 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.63 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16.02 |
November | 15923636.81 | 5843.19 | 28-NOV-06:01 | 1.02 |
December | 0.132588E+09 | 5986.73 | 27-DEC-06:01 | -3.5 |
Annual Sum or Average | 0.267726E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.5 | |
Maximum of Months | 0.132588E+09 | 5986.73 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554564E+09 | 839.98 | 17-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.480299E+09 | 759.10 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.532536E+09 | 732.98 | 10-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.453776E+09 | 580.10 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.480550E+09 | 468.99 | 23-MAY-12:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.472189E+09 | 424.37 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.447595E+09 | 558.24 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.506793E+09 | 550.45 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.468018E+09 | 607.61 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.511000E+09 | 780.58 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.542214E+09 | 889.66 | 22-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.544314E+09 | 889.66 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.599385E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.447595E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.554564E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.341432E+09 | 532.23 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.299344E+09 | 489.21 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.334349E+09 | 469.82 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.289153E+09 | 309.03 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.307898E+09 | 302.47 | 24-MAY-15:39 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.303229E+09 | 292.46 | 19-JUN-15:00 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.287473E+09 | 311.46 | 03-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.322882E+09 | 314.42 | 16-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293200E+09 | 334.42 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.319093E+09 | 486.35 | 13-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.336504E+09 | 563.23 | 22-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.336858E+09 | 563.23 | 01-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.377141E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.287473E+09 | 292.46 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.341432E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.514241E+09 | 836.59 | 17-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.457381E+09 | 726.40 | 23-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.521985E+09 | 725.45 | 10-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.456523E+09 | 579.55 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.486379E+09 | 472.01 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.479173E+09 | 424.37 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.454994E+09 | 574.78 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.510351E+09 | 564.18 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.462125E+09 | 532.98 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.493422E+09 | 776.20 | 13-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.505925E+09 | 889.66 | 22-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.507703E+09 | 889.66 | 01-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.585020E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.454994E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.521985E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.333518E+09 | 528.01 | 17-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.294233E+09 | 455.28 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.332778E+09 | 445.36 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.288171E+09 | 395.44 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.305019E+09 | 308.81 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.299986E+09 | 295.51 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.284748E+09 | 386.89 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.322431E+09 | 399.19 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.294595E+09 | 392.57 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.316749E+09 | 495.76 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.325278E+09 | 563.19 | 22-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.328787E+09 | 563.19 | 01-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.372629E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.284748E+09 | 295.51 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.333518E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.550693E+09 | 837.77 | 17-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.477505E+09 | 752.02 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.530592E+09 | 725.96 | 10-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.453187E+09 | 565.97 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.480234E+09 | 465.06 | 23-MAY-12:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.471831E+09 | 424.37 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.446999E+09 | 497.31 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.505983E+09 | 495.36 | 17-AUG-07:19 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.466159E+09 | 594.13 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.508689E+09 | 775.73 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.538297E+09 | 889.66 | 22-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.540823E+09 | 889.66 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.597099E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.446999E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.550693E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.340243E+09 | 531.12 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.298420E+09 | 486.54 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.333562E+09 | 466.49 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.288700E+09 | 307.11 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.307483E+09 | 300.77 | 24-MAY-15:39 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.302834E+09 | 290.17 | 19-JUN-15:20 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.286967E+09 | 309.81 | 03-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.322324E+09 | 312.90 | 16-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.292604E+09 | 297.11 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.318257E+09 | 483.49 | 13-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.335266E+09 | 563.23 | 22-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.335774E+09 | 563.23 | 01-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.376243E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.286967E+09 | 290.17 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.340243E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.513620E+09 | 834.18 | 17-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.456568E+09 | 718.88 | 23-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.520974E+09 | 718.01 | 10-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.455703E+09 | 565.40 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.485609E+09 | 468.08 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.478388E+09 | 424.37 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.453857E+09 | 560.71 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.509213E+09 | 549.36 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.461092E+09 | 476.11 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.492746E+09 | 771.10 | 13-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.505135E+09 | 889.66 | 22-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.507291E+09 | 889.66 | 01-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.584020E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.453857E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.520974E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332299E+09 | 526.68 | 17-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.293183E+09 | 451.43 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.331963E+09 | 440.93 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287497E+09 | 389.48 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.304577E+09 | 307.11 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.299528E+09 | 293.30 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.284103E+09 | 380.82 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.321634E+09 | 393.56 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293806E+09 | 386.18 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.316035E+09 | 493.36 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.324034E+09 | 563.19 | 22-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.326595E+09 | 563.19 | 01-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.371525E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.284103E+09 | 293.30 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.332299E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.554563E+09 | 839.98 | 17-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.480298E+09 | 759.10 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.532535E+09 | 732.97 | 10-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.453776E+09 | 580.08 | 20-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.480550E+09 | 468.98 | 23-MAY-12:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.472189E+09 | 424.37 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.447594E+09 | 558.21 | 07-JUL-07:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.506792E+09 | 550.42 | 17-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.468017E+09 | 607.61 | 29-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.510999E+09 | 780.57 | 13-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.542213E+09 | 889.66 | 22-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.544313E+09 | 889.66 | 01-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.599384E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.447594E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.554563E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.341432E+09 | 532.23 | 17-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.299343E+09 | 489.21 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.334349E+09 | 469.81 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.289152E+09 | 309.02 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.307898E+09 | 302.46 | 24-MAY-15:39 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.303229E+09 | 292.45 | 19-JUN-15:00 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.287472E+09 | 311.46 | 03-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.322882E+09 | 314.41 | 16-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.293200E+09 | 334.43 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.319093E+09 | 486.34 | 13-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.336504E+09 | 563.23 | 22-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.336857E+09 | 563.23 | 01-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.377141E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.287472E+09 | 292.45 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.341432E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.514240E+09 | 836.59 | 17-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.457380E+09 | 726.39 | 23-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.521985E+09 | 725.44 | 10-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.456522E+09 | 579.53 | 20-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.486378E+09 | 472.00 | 03-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.479173E+09 | 424.37 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.454994E+09 | 574.75 | 07-JUL-07:30 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.510350E+09 | 564.16 | 17-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.462125E+09 | 532.98 | 18-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.493422E+09 | 776.19 | 13-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.505925E+09 | 889.66 | 22-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.507703E+09 | 889.66 | 01-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.585020E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.454994E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.521985E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.333517E+09 | 528.00 | 17-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.294233E+09 | 455.28 | 13-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.332779E+09 | 445.36 | 10-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.288171E+09 | 395.43 | 20-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.305019E+09 | 308.81 | 03-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.299986E+09 | 295.51 | 29-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.284748E+09 | 386.88 | 07-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.322430E+09 | 399.18 | 24-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.294595E+09 | 392.58 | 18-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.316749E+09 | 495.75 | 13-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.325278E+09 | 563.19 | 22-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.328787E+09 | 563.19 | 01-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.372629E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.284748E+09 | 295.51 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.333517E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.554564E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135907E+09 |
February | 0.901968E+09 | 0.480299E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48688.28 | 0.117355E+09 |
March | 0.107774E+10 | 0.532536E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76613.90 | 0.125339E+09 |
April | 0.956342E+09 | 0.453776E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7966479.10 | 70082184.14 |
May | 0.103597E+10 | 0.480550E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21737065.55 | 40251443.28 |
June | 0.103308E+10 | 0.472189E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33502570.75 | 15265240.10 |
July | 0.959235E+09 | 0.447595E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27738438.58 | 11729437.30 |
August | 0.107774E+10 | 0.506793E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22569492.41 | 15028929.97 |
September | 0.956342E+09 | 0.468018E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7383513.07 | 19770744.18 |
October | 0.994195E+09 | 0.511000E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2867824.02 | 60724549.04 |
November | 0.984487E+09 | 0.542214E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112883E+09 |
December | 0.959235E+09 | 0.544314E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117436E+09 |
Annual Sum or Average | 0.119305E+11 | 0.599385E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123891E+09 | 0.841772E+09 |
Minimum of Months | 0.901968E+09 | 0.447595E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11729437.30 |
Maximum of Months | 0.107774E+10 | 0.554564E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33502570.75 | 0.135907E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.341432E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92765318.96 |
February | 0.571020E+09 | 0.299344E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80676093.96 |
March | 0.682301E+09 | 0.334349E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27455.55 | 88075432.38 |
April | 0.605444E+09 | 0.289153E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4820584.70 | 48861810.32 |
May | 0.655854E+09 | 0.307898E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14306352.21 | 27834515.93 |
June | 0.654023E+09 | 0.303229E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22277423.81 | 10372128.43 |
July | 0.607275E+09 | 0.287473E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18436696.61 | 8056438.61 |
August | 0.682301E+09 | 0.322882E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14788517.91 | 10381075.12 |
September | 0.605444E+09 | 0.293200E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4627608.88 | 14018823.25 |
October | 0.629407E+09 | 0.319093E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1686795.98 | 42148174.81 |
November | 0.623262E+09 | 0.336504E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78200461.62 |
December | 0.607275E+09 | 0.336858E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80095612.70 |
Annual Sum or Average | 0.755301E+10 | 0.377141E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80971435.65 | 0.581486E+09 |
Minimum of Months | 0.571020E+09 | 0.287473E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8056438.61 |
Maximum of Months | 0.682301E+09 | 0.341432E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22277423.81 | 92765318.96 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.514241E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150776E+09 |
February | 0.901968E+09 | 0.457381E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129036E+09 |
March | 0.107774E+10 | 0.521985E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40556.08 | 0.138145E+09 |
April | 0.956342E+09 | 0.456523E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6469444.90 | 73111764.99 |
May | 0.103597E+10 | 0.486379E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21547842.30 | 40077926.35 |
June | 0.103308E+10 | 0.479173E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33950334.93 | 14975587.36 |
July | 0.959235E+09 | 0.454994E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28064886.03 | 11469152.18 |
August | 0.107774E+10 | 0.510351E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22060587.58 | 15329430.05 |
September | 0.956342E+09 | 0.462125E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6565340.95 | 21429049.62 |
October | 0.994195E+09 | 0.493422E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2062567.08 | 67782394.33 |
November | 0.984487E+09 | 0.505925E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125895E+09 |
December | 0.959235E+09 | 0.507703E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129810E+09 |
Annual Sum or Average | 0.119305E+11 | 0.585020E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120762E+09 | 0.917837E+09 |
Minimum of Months | 0.901968E+09 | 0.454994E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11469152.18 |
Maximum of Months | 0.107774E+10 | 0.521985E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33950334.93 | 0.150776E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.333518E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93636511.96 |
February | 0.570983E+09 | 0.294233E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81121833.69 |
March | 0.682256E+09 | 0.332778E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33287.77 | 88520451.07 |
April | 0.605404E+09 | 0.288171E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4359288.77 | 49256798.82 |
May | 0.655811E+09 | 0.305019E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13628835.94 | 28093119.31 |
June | 0.653980E+09 | 0.299986E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21871319.01 | 10793087.97 |
July | 0.607235E+09 | 0.284748E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18231961.15 | 8426899.67 |
August | 0.682256E+09 | 0.322431E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14492758.69 | 10516784.37 |
September | 0.605404E+09 | 0.294595E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4681985.55 | 14159081.93 |
October | 0.629366E+09 | 0.316749E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1527793.01 | 42829207.81 |
November | 0.623221E+09 | 0.325278E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78284396.38 |
December | 0.607235E+09 | 0.328787E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80817901.55 |
Annual Sum or Average | 0.755252E+10 | 0.372629E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78827229.89 | 0.586456E+09 |
Minimum of Months | 0.570983E+09 | 0.284748E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8426899.67 |
Maximum of Months | 0.682256E+09 | 0.333518E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21871319.01 | 93636511.96 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.550693E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78960822.29 |
February | 0.901968E+09 | 0.477505E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84794.13 | 64891787.46 |
March | 0.107774E+10 | 0.530592E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82380.39 | 66065042.36 |
April | 0.956342E+09 | 0.453187E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5135612.72 | 35692347.33 |
May | 0.103597E+10 | 0.480234E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13419098.74 | 19831365.57 |
June | 0.103308E+10 | 0.471831E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19543703.34 | 6953212.59 |
July | 0.959235E+09 | 0.446999E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16066997.52 | 5664794.79 |
August | 0.107774E+10 | 0.505983E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12729515.75 | 8036070.61 |
September | 0.956342E+09 | 0.466159E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4169210.99 | 11211518.08 |
October | 0.994195E+09 | 0.508689E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1681457.57 | 35770520.95 |
November | 0.984487E+09 | 0.538297E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68348201.17 |
December | 0.959235E+09 | 0.540823E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70225118.12 |
Annual Sum or Average | 0.119305E+11 | 0.597099E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72912771.17 | 0.471651E+09 |
Minimum of Months | 0.901968E+09 | 0.446999E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5664794.79 |
Maximum of Months | 0.107774E+10 | 0.550693E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19543703.34 | 78960822.29 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.340243E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54781499.34 |
February | 0.571020E+09 | 0.298420E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.66 | 45878441.35 |
March | 0.682301E+09 | 0.333562E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19046.94 | 48080624.18 |
April | 0.605444E+09 | 0.288700E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2660404.88 | 26390421.64 |
May | 0.655854E+09 | 0.307483E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8087625.48 | 14652134.80 |
June | 0.654023E+09 | 0.302834E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12308872.87 | 5141248.87 |
July | 0.607275E+09 | 0.286967E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10011305.18 | 4247871.06 |
August | 0.682301E+09 | 0.322324E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7905036.12 | 5900582.51 |
September | 0.605444E+09 | 0.292604E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2484503.21 | 8236025.97 |
October | 0.629407E+09 | 0.318257E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 941983.60 | 25282620.57 |
November | 0.623262E+09 | 0.335266E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48111216.23 |
December | 0.607275E+09 | 0.335774E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48720027.35 |
Annual Sum or Average | 0.755301E+10 | 0.376243E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44419129.93 | 0.335423E+09 |
Minimum of Months | 0.571020E+09 | 0.286967E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4247871.06 |
Maximum of Months | 0.682301E+09 | 0.340243E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12308872.87 | 54781499.34 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.513620E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444442E+10 |
February | 0.901968E+09 | 0.456568E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358928E+10 |
March | 0.107774E+10 | 0.520974E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6046305.97 | 0.326158E+10 |
April | 0.956342E+09 | 0.455703E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380110E+09 | 0.140514E+10 |
May | 0.103597E+10 | 0.485609E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103544E+10 | 0.547594E+09 |
June | 0.103308E+10 | 0.478388E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197441E+10 | 0.188954E+09 |
July | 0.959235E+09 | 0.453857E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161980E+10 | 0.129495E+09 |
August | 0.107774E+10 | 0.509213E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138131E+10 | 0.337548E+09 |
September | 0.956342E+09 | 0.461092E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972227E+09 | 0.531611E+09 |
October | 0.994195E+09 | 0.492746E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210013E+09 | 0.159417E+10 |
November | 0.984487E+09 | 0.505135E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336786E+10 |
December | 0.959235E+09 | 0.507291E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474200E+10 |
Annual Sum or Average | 0.119305E+11 | 0.584020E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757936E+10 | 0.241397E+11 |
Minimum of Months | 0.901968E+09 | 0.453857E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129495E+09 |
Maximum of Months | 0.107774E+10 | 0.520974E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197441E+10 | 0.474200E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.332299E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55110112.71 |
February | 0.570983E+09 | 0.293183E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45830429.05 |
March | 0.682256E+09 | 0.331963E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19863.81 | 48367563.86 |
April | 0.605404E+09 | 0.287497E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2320619.55 | 26626095.62 |
May | 0.655811E+09 | 0.304577E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7544023.62 | 14962333.86 |
June | 0.653980E+09 | 0.299528E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11967750.11 | 5403256.38 |
July | 0.607235E+09 | 0.284103E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9777888.88 | 4480834.78 |
August | 0.682256E+09 | 0.321634E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7683696.15 | 6058920.02 |
September | 0.605404E+09 | 0.293806E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2462046.99 | 8372157.55 |
October | 0.629366E+09 | 0.316035E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 869816.34 | 25989966.17 |
November | 0.623221E+09 | 0.324034E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48298557.21 |
December | 0.607235E+09 | 0.326595E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48749681.53 |
Annual Sum or Average | 0.755252E+10 | 0.371525E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42645705.46 | 0.338250E+09 |
Minimum of Months | 0.570983E+09 | 0.284103E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4480834.78 |
Maximum of Months | 0.682256E+09 | 0.332299E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11967750.11 | 55110112.71 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.554563E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123634E+09 |
February | 0.901968E+09 | 0.480298E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42331.94 | 0.105825E+09 |
March | 0.107774E+10 | 0.532535E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58361.52 | 0.111845E+09 |
April | 0.956342E+09 | 0.453776E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6949010.55 | 61649307.29 |
May | 0.103597E+10 | 0.480550E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18876777.78 | 35135415.07 |
June | 0.103308E+10 | 0.472189E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28596073.94 | 12818809.47 |
July | 0.959235E+09 | 0.447594E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23829391.99 | 9745802.54 |
August | 0.107774E+10 | 0.506792E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19163988.27 | 12937217.68 |
September | 0.956342E+09 | 0.468017E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6392586.97 | 17318126.77 |
October | 0.994195E+09 | 0.510999E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2434281.84 | 54696282.08 |
November | 0.984487E+09 | 0.542213E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103879E+09 |
December | 0.959235E+09 | 0.544313E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107420E+09 |
Annual Sum or Average | 0.119305E+11 | 0.599384E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106343E+09 | 0.756903E+09 |
Minimum of Months | 0.901968E+09 | 0.447594E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9745802.54 |
Maximum of Months | 0.107774E+10 | 0.554563E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28596073.94 | 0.123634E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.341432E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84074570.42 |
February | 0.421807E+09 | 0.299343E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72291371.52 |
March | 0.502994E+09 | 0.334349E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24533.62 | 77794934.33 |
April | 0.447140E+09 | 0.289152E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4211337.00 | 42539324.34 |
May | 0.484071E+09 | 0.307898E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12267271.66 | 24161381.67 |
June | 0.482240E+09 | 0.303229E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18918843.10 | 8692774.96 |
July | 0.448971E+09 | 0.287472E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15687945.91 | 6692667.04 |
August | 0.502994E+09 | 0.322882E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12460422.87 | 8909621.84 |
September | 0.447140E+09 | 0.293200E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3982173.92 | 12163314.57 |
October | 0.465148E+09 | 0.319093E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1442431.74 | 37566038.78 |
November | 0.460569E+09 | 0.336504E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71304348.32 |
December | 0.448971E+09 | 0.336857E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73049267.05 |
Annual Sum or Average | 0.557719E+10 | 0.377141E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68994959.83 | 0.519240E+09 |
Minimum of Months | 0.421807E+09 | 0.287472E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6692667.04 |
Maximum of Months | 0.502994E+09 | 0.341432E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18918843.10 | 84074570.42 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.514240E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135670E+09 |
February | 0.901968E+09 | 0.457380E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115107E+09 |
March | 0.107774E+10 | 0.521985E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35535.47 | 0.121852E+09 |
April | 0.956342E+09 | 0.456522E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5589834.73 | 64090884.33 |
May | 0.103597E+10 | 0.486378E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18374345.26 | 35163000.37 |
June | 0.103308E+10 | 0.479173E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28820243.44 | 12625417.30 |
July | 0.959235E+09 | 0.454994E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23856322.47 | 9588545.86 |
August | 0.107774E+10 | 0.510350E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18537657.07 | 13230310.11 |
September | 0.956342E+09 | 0.462125E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5548268.11 | 18725240.82 |
October | 0.994195E+09 | 0.493422E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1719102.06 | 60136950.57 |
November | 0.984487E+09 | 0.505925E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113779E+09 |
December | 0.959235E+09 | 0.507703E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117505E+09 |
Annual Sum or Average | 0.119305E+11 | 0.585020E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102481E+09 | 0.817473E+09 |
Minimum of Months | 0.901968E+09 | 0.454994E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9588545.86 |
Maximum of Months | 0.107774E+10 | 0.521985E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28820243.44 | 0.135670E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.333517E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84718897.62 |
February | 0.570983E+09 | 0.294233E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72779513.40 |
March | 0.682256E+09 | 0.332779E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24721.41 | 78567004.39 |
April | 0.605404E+09 | 0.288171E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3638005.67 | 43267567.68 |
May | 0.655811E+09 | 0.305019E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11449802.45 | 24644412.32 |
June | 0.653980E+09 | 0.299986E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18355520.88 | 9102203.86 |
July | 0.607235E+09 | 0.284748E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15271160.30 | 7052377.93 |
August | 0.682256E+09 | 0.322430E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12063693.85 | 9082703.65 |
September | 0.605404E+09 | 0.294595E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3898005.54 | 12397160.43 |
October | 0.629366E+09 | 0.316749E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1262791.43 | 38444165.89 |
November | 0.623221E+09 | 0.325278E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71531878.02 |
December | 0.607235E+09 | 0.328787E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73530082.17 |
Annual Sum or Average | 0.755252E+10 | 0.372629E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65963701.53 | 0.525118E+09 |
Minimum of Months | 0.570983E+09 | 0.284748E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7052377.93 |
Maximum of Months | 0.682256E+09 | 0.333517E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18355520.88 | 84718897.62 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178782E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151617E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20236.83 | 0.158374E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7318749.75 | 85279014.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22278953.04 | 46934367.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35343328.85 | 16128562.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29340862.96 | 11963010.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22935506.12 | 17089243.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6684882.29 | 24151698.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2459202.36 | 78716665.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151681E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156476E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126382E+09 | 0.107719E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11963010.07 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35343328.85 | 0.178782E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215639E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186442E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37909.07 | 0.197181E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9874685.48 | 0.108590E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28401834.43 | 60663032.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44974139.55 | 21303140.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37332384.11 | 15587549.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29563863.97 | 21846062.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8888252.85 | 30284021.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3431886.71 | 96787192.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183769E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187626E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162505E+09 | 0.132572E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15587549.01 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44974139.55 | 0.215639E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209382E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182087E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198798E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6403068.08 | 0.106989E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24133333.15 | 56740318.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44229279.64 | 20082206.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35349684.38 | 15215035.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28381775.55 | 20460654.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6902327.16 | 29534242.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2655999.13 | 95010459.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174789E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178962E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148055E+09 | 0.128805E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15215035.16 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44229279.64 | 0.209382E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 839.98 | 17-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 382.72 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 759.10 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 20-FEB-16:00 | 495.03 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 732.98 | 10-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.34 | 19-MAR-13:53 | 374.39 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 580.10 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.87 | 01-APR-17:20 | 406.70 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 468.99 | 23-MAY-12:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.66 | 14-MAY-15:30 | 187.84 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.97 | 04-JUN-18:53 | 149.09 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 558.24 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.95 | 02-JUL-21:10 | 74.03 | 04-JUL-19:13 |
August | 1306.65 | 01-AUG-09:09 | 550.45 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.97 | 27-AUG-13:00 | 130.09 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 607.61 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.37 | 10-SEP-15:00 | 72.74 | 23-SEP-17:10 |
October | 1306.65 | 02-OCT-09:09 | 780.58 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.19 | 01-OCT-15:00 | 182.86 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 22-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 220.22 | 26-NOV-14:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 293.72 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.74 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 151.95 | 495.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 532.23 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 254.58 | 25-JAN-23:00 |
February | 827.22 | 01-FEB-10:09 | 489.21 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 330.78 | 09-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 469.82 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 | 22-MAR-13:00 | 258.79 | 19-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 309.03 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.17 | 01-APR-17:20 | 271.24 | 10-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 302.47 | 24-MAY-15:39 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.70 | 14-MAY-15:30 | 123.96 | 04-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 292.46 | 19-JUN-15:00 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.08 | 04-JUN-18:53 | 99.16 | 28-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 311.46 | 03-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.56 | 02-JUL-21:15 | 50.36 | 04-JUL-19:20 |
August | 827.22 | 01-AUG-09:09 | 314.42 | 16-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.36 | 26-AUG-17:50 | 87.62 | 14-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 334.42 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.50 | 10-SEP-15:00 | 58.10 | 24-SEP-10:30 |
October | 827.22 | 02-OCT-09:09 | 486.35 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 | 01-OCT-15:00 | 122.06 | 23-OCT-21:10 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 170.13 | 26-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 197.29 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 292.46 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.36 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 104.56 | 330.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 836.59 | 17-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 388.83 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 726.40 | 23-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 507.26 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 725.45 | 10-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 22-MAR-13:00 | 400.90 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 579.55 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.68 | 01-APR-17:20 | 410.43 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 472.01 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.38 | 14-MAY-15:26 | 188.74 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.20 | 04-JUN-18:53 | 148.20 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 574.78 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.99 | 02-JUL-21:15 | 73.20 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 564.18 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.97 | 26-AUG-18:00 | 132.24 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 532.98 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.65 | 10-SEP-15:26 | 81.65 | 24-SEP-11:00 |
October | 1306.65 | 02-OCT-09:09 | 776.20 | 13-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.71 | 01-OCT-15:00 | 192.87 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 22-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 255.50 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 311.05 | 18-DEC-05:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.20 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 152.99 | 507.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 528.01 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 254.34 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 455.28 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 331.90 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 445.36 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 22-MAR-12:00 | 259.52 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 395.44 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 | 21-APR-15:00 | 272.14 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 308.81 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.90 | 14-MAY-15:24 | 127.24 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 295.51 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.07 | 04-JUN-18:53 | 102.69 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 386.89 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.58 | 02-JUL-21:15 | 58.72 | 04-JUL-19:10 |
August | 827.17 | 01-AUG-09:09 | 399.19 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.75 | 27-AUG-13:00 | 89.77 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 392.57 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.64 | 10-SEP-14:45 | 50.15 | 04-SEP-19:33 |
October | 827.17 | 02-OCT-09:09 | 495.76 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.08 | 01-OCT-14:54 | 125.76 | 23-OCT-21:10 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 154.41 | 26-NOV-17:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 199.29 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 295.51 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.15 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 103.58 | 331.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 837.77 | 17-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 220.83 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 752.02 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 20-FEB-16:00 | 277.65 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 725.96 | 10-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.51 | 22-MAR-12:00 | 204.22 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 565.97 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.61 | 01-APR-17:03 | 224.34 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 465.06 | 23-MAY-12:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.05 | 14-MAY-16:00 | 98.88 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.44 | 04-JUN-19:00 | 76.74 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 497.31 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.70 | 02-JUL-21:20 | 38.54 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 495.36 | 17-AUG-07:19 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.59 | 26-AUG-18:00 | 66.60 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 594.13 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.92 | 10-SEP-15:00 | 40.59 | 24-SEP-07:00 |
October | 1306.65 | 02-OCT-09:09 | 775.73 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.02 | 01-OCT-14:52 | 107.43 | 24-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 22-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 140.71 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 182.83 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.54 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 90.70 | 277.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 531.12 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 148.64 | 25-JAN-23:00 |
February | 827.22 | 01-FEB-10:09 | 486.54 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 20-FEB-15:50 | 189.89 | 09-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 466.49 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 22-MAR-13:00 | 146.77 | 19-MAR-24:00 |
April | 827.22 | 03-APR-09:09 | 307.11 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 | 01-APR-17:03 | 153.95 | 10-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 300.77 | 24-MAY-15:39 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.52 | 14-MAY-16:00 | 67.34 | 04-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 290.17 | 19-JUN-15:20 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.42 | 04-JUN-19:00 | 52.64 | 28-JUN-02:00 |
July | 827.22 | 03-JUL-09:09 | 309.81 | 03-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.02 | 02-JUL-21:15 | 27.57 | 04-JUL-19:13 |
August | 827.22 | 01-AUG-09:09 | 312.90 | 16-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.07 | 26-AUG-17:50 | 47.44 | 14-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 297.11 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.26 | 10-SEP-15:20 | 31.47 | 24-SEP-10:10 |
October | 827.22 | 02-OCT-09:09 | 483.49 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.91 | 01-OCT-14:52 | 73.75 | 24-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 105.97 | 26-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 125.63 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 290.17 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 58.02 | 189.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 834.18 | 17-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 28019.23 | 27-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 718.88 | 23-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 28958.40 | 03-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 718.01 | 10-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 968.83 | 21-MAR-16:10 | 24916.81 | 02-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 565.40 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7165.72 | 19-APR-16:05 | 17982.21 | 12-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 468.08 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10762.12 | 19-MAY-16:03 | 12530.34 | 02-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14682.61 | 02-JUN-16:01 | 5957.66 | 13-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 560.71 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14072.32 | 03-JUL-16:01 | 5725.07 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 549.36 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12765.46 | 07-AUG-16:01 | 6684.05 | 31-AUG-06:02 |
September | 1306.65 | 01-SEP-09:09 | 476.11 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9399.33 | 19-SEP-16:02 | 12870.88 | 25-SEP-06:02 |
October | 1306.65 | 02-OCT-09:09 | 771.10 | 13-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6205.40 | 04-OCT-16:03 | 16346.08 | 25-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 22-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 22556.79 | 17-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 28011.53 | 27-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5725.07 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 14682.61 | 28958.40 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 526.68 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 147.81 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 451.43 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 189.92 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 440.93 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 | 22-MAR-12:00 | 146.69 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 389.48 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 29-APR-17:03 | 154.10 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 307.11 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.70 | 14-MAY-15:35 | 69.67 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 293.30 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.07 | 04-JUN-19:00 | 54.80 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 380.82 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.58 | 02-JUL-21:15 | 31.05 | 04-JUL-19:03 |
August | 827.17 | 01-AUG-09:09 | 393.56 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.58 | 27-AUG-13:00 | 49.01 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 386.18 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 | 10-SEP-15:13 | 27.48 | 24-SEP-07:00 |
October | 827.17 | 02-OCT-09:09 | 493.36 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 | 01-OCT-15:06 | 75.06 | 24-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 97.28 | 26-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 126.84 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 293.30 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 56.58 | 189.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 839.98 | 17-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 343.24 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 759.10 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.78 | 20-FEB-16:00 | 442.92 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 732.97 | 10-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.66 | 19-MAR-14:10 | 337.79 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 580.08 | 20-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.08 | 01-APR-17:03 | 360.65 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 468.98 | 23-MAY-12:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.81 | 14-MAY-16:00 | 167.66 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.41 | 04-JUN-18:53 | 125.46 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 558.21 | 07-JUL-07:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.46 | 02-JUL-21:20 | 60.41 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 550.42 | 17-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.81 | 26-AUG-18:00 | 107.07 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 607.61 | 29-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.11 | 10-SEP-15:00 | 60.61 | 24-SEP-07:00 |
October | 1306.65 | 02-OCT-09:09 | 780.57 | 13-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.05 | 01-OCT-15:00 | 163.23 | 24-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 22-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 210.03 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 276.92 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.41 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 131.46 | 442.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 532.23 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 227.70 | 25-JAN-23:00 |
February | 805.43 | 01-FEB-08:09 | 489.21 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 295.25 | 09-FEB-01:00 |
March | 805.43 | 01-MAR-08:09 | 469.81 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22-MAR-13:00 | 232.42 | 19-MAR-24:00 |
April | 805.43 | 03-APR-07:10 | 309.02 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | 01-APR-17:20 | 240.31 | 10-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 302.46 | 24-MAY-15:39 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.52 | 14-MAY-16:00 | 110.65 | 04-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 292.45 | 19-JUN-15:00 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.61 | 04-JUN-18:53 | 83.46 | 28-JUN-02:00 |
July | 805.43 | 03-JUL-07:10 | 311.46 | 03-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.53 | 02-JUL-21:15 | 40.26 | 18-JUL-21:10 |
August | 805.43 | 01-AUG-07:10 | 314.41 | 16-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.18 | 26-AUG-17:50 | 72.42 | 14-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 334.43 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.01 | 10-SEP-15:20 | 49.24 | 24-SEP-10:10 |
October | 805.43 | 02-OCT-07:10 | 486.34 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.80 | 01-OCT-15:00 | 108.86 | 24-OCT-02:00 |
November | 805.43 | 01-NOV-07:10 | 563.23 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 160.00 | 26-NOV-09:00 |
December | 805.43 | 01-DEC-08:09 | 563.23 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 185.63 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 292.45 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.26 | |||||
Maximum of Months | 805.43 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 91.53 | 295.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 836.59 | 17-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 349.71 | 25-JAN-23:00 |
February | 1306.65 | 01-FEB-10:09 | 726.39 | 23-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 452.46 | 09-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 725.44 | 10-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 22-MAR-13:00 | 359.17 | 19-MAR-24:00 |
April | 1306.65 | 03-APR-09:09 | 579.53 | 20-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 01-APR-17:20 | 363.74 | 10-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 472.00 | 03-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.37 | 14-MAY-16:00 | 168.54 | 04-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.90 | 04-JUN-18:53 | 124.77 | 28-JUN-02:00 |
July | 1306.65 | 03-JUL-09:09 | 574.75 | 07-JUL-07:30 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.16 | 02-JUL-21:15 | 60.54 | 18-JUL-21:10 |
August | 1306.65 | 01-AUG-09:09 | 564.16 | 17-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.16 | 26-AUG-18:00 | 109.36 | 14-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 532.98 | 18-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.13 | 10-SEP-15:15 | 68.75 | 24-SEP-11:00 |
October | 1306.65 | 02-OCT-09:09 | 776.19 | 13-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.77 | 01-OCT-14:56 | 168.07 | 23-OCT-21:10 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 22-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 240.16 | 26-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 290.89 | 18-DEC-05:30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.54 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 133.16 | 452.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 528.00 | 17-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 227.57 | 25-JAN-23:00 |
February | 827.17 | 01-FEB-10:09 | 455.28 | 13-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 296.66 | 09-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 445.36 | 10-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 22-MAR-13:00 | 233.20 | 19-MAR-24:00 |
April | 827.17 | 03-APR-09:09 | 395.43 | 20-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 21-APR-15:00 | 241.34 | 10-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 308.81 | 03-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.23 | 14-MAY-15:59 | 113.56 | 04-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 295.51 | 29-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.65 | 04-JUN-18:53 | 86.30 | 28-JUN-02:00 |
July | 827.17 | 03-JUL-09:09 | 386.88 | 07-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.82 | 02-JUL-21:15 | 49.46 | 04-JUL-18:57 |
August | 827.17 | 01-AUG-09:09 | 399.18 | 24-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.07 | 27-AUG-13:00 | 74.48 | 14-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 392.58 | 18-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 | 10-SEP-15:13 | 40.28 | 04-SEP-19:20 |
October | 827.17 | 02-OCT-09:09 | 495.75 | 13-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.18 | 01-OCT-14:52 | 110.76 | 24-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 22-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 142.85 | 26-NOV-17:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 187.18 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 295.51 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.28 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 87.82 | 296.66 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 487.18 | 25-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 624.35 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.80 | 22-MAR-13:00 | 484.21 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.12 | 01-APR-17:03 | 501.08 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.63 | 14-MAY-16:00 | 227.21 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.08 | 04-JUN-19:00 | 166.73 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.20 | 02-JUL-21:20 | 81.54 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.64 | 27-AUG-13:00 | 139.38 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.60 | 10-SEP-15:00 | 83.80 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.32 | 01-OCT-14:52 | 229.67 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 303.99 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 406.67 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.54 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.20 | 624.35 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 594.06 | 25-JAN-23:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 789.60 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 22-MAR-13:00 | 601.45 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.07 | 01-APR-17:03 | 639.62 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.71 | 14-MAY-16:00 | 287.34 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.10 | 04-JUN-18:53 | 216.30 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.71 | 02-JUL-21:20 | 105.90 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.77 | 27-AUG-13:00 | 182.81 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.52 | 10-SEP-15:00 | 104.46 | 24-SEP-07:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.10 | 01-OCT-15:00 | 288.47 | 24-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 362.57 | 26-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 487.32 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.46 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.71 | 789.60 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 571.63 | 25-JAN-23:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 737.70 | 09-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 549.62 | 19-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.65 | 01-APR-17:03 | 590.85 | 10-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.70 | 19-MAY-22:00 | 260.37 | 04-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.75 | 04-JUN-19:00 | 226.12 | 28-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.30 | 02-JUL-21:30 | 115.50 | 18-JUL-21:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.41 | 26-AUG-18:00 | 198.71 | 14-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.53 | 10-SEP-15:00 | 120.76 | 23-SEP-17:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.85 | 01-OCT-15:00 | 282.18 | 23-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 351.44 | 26-NOV-14:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 436.33 | 18-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.50 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.30 | 737.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18271.51 | 12-JAN-08:02 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18967.57 | 23-FEB-06:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24037.65 | 17-MAR-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37698.53 | 29-APR-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40133.32 | 30-MAY-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40905.97 | 05-JUN-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 42211.10 | 05-JUL-04:02 | 0.00 | 2344.59 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40975.79 | 14-AUG-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41517.03 | 05-SEP-04:02 | 0.00 | 2344.59 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39093.48 | 25-OCT-05:02 | 3176.32 | 2344.59 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38986.28 | 13-NOV-06:02 | 3176.32 | 2344.59 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18836.39 | 12-DEC-08:03 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18271.51 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42211.10 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2555.62 | 12-JAN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 |
February | 3998.06 | 22-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5403.50 | 16-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.21 |
April | 8744.43 | 28-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 0.00 |
May | 10672.59 | 30-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.93 | 0.00 |
June | 11214.46 | 15-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 0.00 |
July | 11554.94 | 03-JUL-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 0.00 |
August | 11111.42 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.20 | 0.00 |
September | 9742.67 | 19-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.05 | 0.00 |
October | 8827.65 | 03-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.91 | 0.00 |
November | 4666.01 | 03-NOV-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 |
December | 1672.26 | 09-DEC-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1672.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11554.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.13 | 29.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1826.60 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.21 |
February | 2194.19 | 09-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.33 |
March | 2125.06 | 30-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.92 |
April | 3048.54 | 21-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 | 0.00 |
May | 4740.50 | 30-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.90 | 0.00 |
June | 4997.22 | 19-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 |
July | 5238.50 | 03-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 | 0.00 |
August | 5078.30 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 | 0.00 |
September | 4461.16 | 05-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 | 0.00 |
October | 3684.02 | 05-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.19 | 0.00 |
November | 1924.35 | 10-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.37 |
December | 1564.91 | 14-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1564.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5238.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 | 74.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2535.34 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.39 |
February | 2580.77 | 09-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 |
March | 2921.77 | 30-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.56 |
April | 3240.48 | 21-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.47 | 0.00 |
May | 5304.65 | 30-MAY-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.07 | 0.00 |
June | 6012.78 | 05-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 | 0.00 |
July | 6715.62 | 03-JUL-12:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.00 |
August | 5473.76 | 01-AUG-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.47 | 0.00 |
September | 5399.94 | 05-SEP-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 |
October | 4058.40 | 05-OCT-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.49 | 0.00 |
November | 2728.41 | 10-NOV-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.82 |
December | 2094.58 | 21-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2094.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6715.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.47 | 59.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8222.45 | 04-JAN-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10213.03 | 22-FEB-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11849.82 | 16-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 21450.81 | 29-APR-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29143.03 | 30-MAY-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29777.87 | 12-JUN-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30867.45 | 05-JUL-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30385.19 | 14-AUG-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31215.21 | 05-SEP-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28960.51 | 06-OCT-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13384.47 | 10-NOV-16:50 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6979.62 | 15-DEC-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6979.62 | 0.00 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31215.21 | 6035.01 | 4220.20 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7325.99 | 12-JAN-16:50 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9631.34 | 22-FEB-15:40 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12930.93 | 16-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16251.41 | 28-APR-15:40 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31605.97 | 22-MAY-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32496.16 | 05-JUN-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32809.69 | 17-JUL-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31814.78 | 14-AUG-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31674.95 | 18-SEP-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29242.38 | 02-OCT-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 13134.37 | 10-NOV-15:00 | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6745.52 | 15-DEC-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6745.52 | 0.00 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32809.69 | 6198.29 | 4220.20 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1414.22 | 12-JAN-14:30 | 1306.65 | 458.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 |
February | 1852.19 | 22-FEB-15:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3087.73 | 22-MAR-14:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 | 0.00 |
April | 5379.44 | 21-APR-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 53.93 | 0.00 |
May | 8307.06 | 21-MAY-15:22 | 401.76 | 141.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 | 0.00 |
June | 11680.32 | 18-JUN-15:42 | 401.76 | 141.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 47.50 | 0.00 |
July | 11741.78 | 02-JUL-16:22 | 401.76 | 141.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 48.63 | 0.00 |
August | 10263.62 | 06-AUG-15:42 | 401.76 | 141.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 33.01 | 0.00 |
September | 5813.74 | 20-SEP-14:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 | 0.00 |
October | 6353.66 | 02-OCT-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 |
November | 2533.77 | 09-NOV-15:40 | 1272.23 | 582.85 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 |
December | 1256.98 | 08-DEC-15:30 | 1272.23 | 483.84 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1256.98 | 0.00 | 141.44 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11741.78 | 1306.65 | 582.85 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 82.71 | 10.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1277.44 | 04-JAN-10:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.48 |
February | 2638.36 | 21-FEB-10:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 |
March | 3807.29 | 16-MAR-10:10 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.86 |
April | 10135.88 | 30-APR-10:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11114.56 | 21-MAY-10:02 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 | 0.00 |
June | 10872.13 | 18-JUN-09:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 16.07 | 0.00 |
July | 10943.73 | 02-JUL-09:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10924.28 | 06-AUG-09:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13.20 | 0.00 |
September | 10827.84 | 03-SEP-10:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 6350.40 | 01-OCT-10:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4294.96 | 10-NOV-09:20 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.49 |
December | 1153.52 | 01-DEC-10:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1153.52 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11114.56 | 827.22 | 268.66 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 16.07 | 31.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8545.74 | 12-JAN-14:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 |
February | 13417.42 | 20-FEB-14:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.27 |
March | 8184.91 | 16-MAR-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 |
April | 11876.82 | 16-APR-13:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 |
May | 12079.53 | 21-MAY-13:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 79.50 | 0.00 |
June | 12481.97 | 18-JUN-15:42 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 47.63 | 0.00 |
July | 12990.07 | 02-JUL-15:42 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 93.80 | 0.00 |
August | 13399.89 | 27-AUG-12:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 80.60 | 0.00 |
September | 13710.54 | 17-SEP-11:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 0.00 |
October | 14360.35 | 29-OCT-12:22 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.61 |
November | 13684.64 | 11-NOV-12:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.64 |
December | 6672.92 | 07-DEC-14:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6672.92 | 267.84 | 94.29 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14360.35 | 1306.65 | 424.37 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 93.80 | 71.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3125.99 | 12-JAN-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 |
February | 4457.22 | 21-FEB-16:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.06 |
March | 5727.42 | 14-MAR-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 0.00 |
April | 12526.81 | 16-APR-17:02 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 8.29 | 0.00 |
May | 12898.47 | 29-MAY-16:42 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 46.71 | 0.00 |
June | 12903.23 | 25-JUN-17:12 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 | 0.00 |
July | 12815.83 | 09-JUL-16:32 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 17.86 | 0.00 |
August | 12865.53 | 06-AUG-17:02 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 | 0.00 |
September | 12460.13 | 17-SEP-15:42 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 24.75 | 0.00 |
October | 11168.68 | 08-OCT-15:32 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 |
November | 5208.55 | 09-NOV-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 |
December | 2292.97 | 15-DEC-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2292.97 | 0.00 | 59.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12903.23 | 805.38 | 268.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 46.71 | 16.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1343.65 | 12-JAN-13:06 | 6361.16 | 2121.83 | 7176.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
February | 1672.14 | 20-FEB-15:02 | 267.84 | 101.68 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 0.00 |
March | 1462.75 | 22-MAR-14:50 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 0.00 |
April | 3467.78 | 21-APR-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.86 | 0.00 |
May | 4708.16 | 30-MAY-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 | 0.00 |
June | 5857.62 | 19-JUN-06:03 | 803.52 | 424.37 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
July | 7476.92 | 03-JUL-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 | 0.00 |
August | 7511.88 | 07-AUG-06:03 | 803.52 | 486.03 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
September | 6019.01 | 05-SEP-06:02 | 1339.19 | 1179.05 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 |
October | 4961.63 | 03-OCT-14:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.99 | 0.00 |
November | 2291.68 | 10-NOV-12:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 |
December | 1308.53 | 01-DEC-14:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1308.53 | 0.00 | 101.68 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7511.88 | 6361.16 | 2121.83 | 7176.23 | 0.00 | 0.00 | 0.00 | 0.00 | 28.86 | 15.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1361.21 | 04-JAN-10:10 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.63 |
February | 2293.41 | 21-FEB-10:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 |
March | 2743.18 | 31-MAR-09:50 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.41 |
April | 6004.29 | 30-APR-10:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9266.17 | 21-MAY-10:02 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 0.00 |
June | 7929.31 | 18-JUN-09:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 0.00 |
July | 9816.17 | 04-JUL-09:32 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 |
August | 9879.33 | 06-AUG-09:32 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 0.00 |
September | 9698.08 | 04-SEP-09:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 |
October | 5400.08 | 05-OCT-09:10 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 0.00 |
November | 4104.58 | 10-NOV-09:20 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 |
December | 1166.30 | 01-DEC-09:50 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1166.30 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9879.33 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 17.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7090.22 | 12-JAN-13:06 | 6361.16 | 2121.83 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1133.88 |
February | 10764.00 | 20-FEB-14:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.19 |
March | 5315.95 | 22-MAR-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 140.39 | 0.00 |
April | 9275.70 | 19-APR-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6179.91 | 0.00 |
May | 10151.95 | 19-MAY-16:20 | 1205.27 | 707.27 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 9325.77 | 0.00 |
June | 11340.41 | 02-JUN-17:00 | 401.76 | 235.76 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11724.10 | 0.00 |
July | 11409.94 | 03-JUL-17:00 | 401.76 | 347.46 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11158.62 | 0.00 |
August | 11161.35 | 07-AUG-16:50 | 401.76 | 235.76 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 9980.99 | 0.00 |
September | 11272.40 | 04-SEP-13:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 0.00 |
October | 11748.56 | 01-OCT-14:22 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 |
November | 11371.97 | 11-NOV-13:02 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.80 |
December | 6534.04 | 17-DEC-14:03 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5315.95 | 200.88 | 70.72 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11748.56 | 6361.16 | 2121.83 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 11724.10 | 1133.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2374.15 | 30-JAN-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 |
February | 3464.57 | 21-FEB-16:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 |
March | 3546.57 | 21-MAR-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 0.00 |
April | 9791.37 | 16-APR-16:51 | 296.72 | 104.46 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 0.00 |
May | 9999.94 | 29-MAY-17:22 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 0.00 |
June | 9982.78 | 04-JUN-16:32 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 | 0.00 |
July | 9982.30 | 04-JUL-15:31 | 296.72 | 104.46 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 8.31 | 0.00 |
August | 10430.27 | 27-AUG-17:52 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 0.00 |
September | 10353.91 | 10-SEP-16:32 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 | 0.00 |
October | 10038.89 | 01-OCT-15:42 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 13.87 | 0.00 |
November | 4735.43 | 09-NOV-16:10 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 |
December | 2181.28 | 15-DEC-16:10 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2181.28 | 0.00 | 74.61 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10430.27 | 805.38 | 268.64 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 8.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1560.19 | 12-JAN-14:30 | 1306.65 | 458.97 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
February | 2014.27 | 23-FEB-14:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.30 |
March | 2919.96 | 22-MAR-14:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 0.00 |
April | 4765.78 | 21-APR-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 45.04 | 0.00 |
May | 7852.40 | 30-MAY-06:03 | 803.52 | 424.37 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
June | 9772.38 | 18-JUN-15:31 | 535.68 | 188.59 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 36.52 | 0.00 |
July | 8582.75 | 02-JUL-16:22 | 401.76 | 141.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 41.01 | 0.00 |
August | 9787.07 | 06-AUG-16:51 | 602.64 | 212.16 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 60.84 | 0.00 |
September | 5283.13 | 13-SEP-05:03 | 535.68 | 395.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 |
October | 6199.26 | 02-OCT-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 |
November | 2542.98 | 09-NOV-16:00 | 1272.23 | 650.79 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 |
December | 1285.38 | 08-DEC-15:00 | 1306.65 | 459.42 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1285.38 | 0.00 | 141.44 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9787.07 | 1306.65 | 650.79 | 4305.74 | 0.00 | 0.00 | 0.00 | 0.00 | 60.84 | 9.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1937.82 | 04-JAN-09:50 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 |
February | 3097.24 | 21-FEB-10:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 |
March | 4162.22 | 23-MAR-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.68 |
April | 10692.12 | 30-APR-08:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.35 |
May | 10939.64 | 29-MAY-09:12 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.47 |
June | 11025.70 | 18-JUN-09:32 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 0.00 |
July | 11045.87 | 04-JUL-08:52 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.15 |
August | 11106.79 | 06-AUG-08:52 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 | 0.00 |
September | 10834.88 | 04-SEP-08:32 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 |
October | 6148.43 | 05-OCT-08:40 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
November | 4671.38 | 10-NOV-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 |
December | 1211.90 | 01-DEC-10:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1211.90 | 211.95 | 74.62 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11106.79 | 805.43 | 268.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 34.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8362.01 | 12-JAN-14:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
February | 10243.17 | 20-FEB-12:33 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.47 |
March | 7672.10 | 16-MAR-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 |
April | 11484.68 | 30-APR-13:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 | 0.00 |
May | 7683.53 | 29-MAY-13:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 43.49 | 0.00 |
June | 10979.64 | 18-JUN-15:31 | 535.68 | 188.59 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 36.58 | 0.00 |
July | 9322.42 | 02-JUL-15:42 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 78.86 | 0.00 |
August | 11373.71 | 27-AUG-11:53 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 47.97 | 0.00 |
September | 12219.77 | 17-SEP-12:52 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 | 0.00 |
October | 12413.93 | 22-OCT-13:12 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 |
November | 12246.99 | 11-NOV-13:02 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 |
December | 7081.38 | 07-DEC-13:35 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7081.38 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12413.93 | 2544.47 | 848.73 | 3827.30 | 0.00 | 0.00 | 0.00 | 0.00 | 78.86 | 68.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3152.97 | 12-JAN-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 |
February | 4383.02 | 21-FEB-16:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
March | 7904.87 | 26-MAR-16:33 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.12 |
April | 11284.68 | 30-APR-16:41 | 296.72 | 104.46 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 | 0.00 |
May | 11598.74 | 29-MAY-16:31 | 339.11 | 119.38 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 | 0.00 |
June | 11606.77 | 25-JUN-17:01 | 0.00 | 119.38 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 0.00 |
July | 11536.64 | 09-JUL-18:22 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 22.16 | 0.00 |
August | 11440.70 | 27-AUG-17:52 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 | 0.00 |
September | 11542.13 | 10-SEP-16:32 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.99 | 0.00 |
October | 11053.89 | 22-OCT-15:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
November | 5082.93 | 09-NOV-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 |
December | 2541.46 | 15-DEC-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2541.46 | 0.00 | 59.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11606.77 | 805.38 | 268.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 | 27.12 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.954696E+11 | 102697.75 | 17-JAN-07:10 | 0.143220E+11 | 51775.63 | 27-JAN-07:30 |
February | 0.855265E+11 | 98925.83 | 03-FEB-07:10 | 0.116306E+11 | 53762.12 | 03-FEB-07:19 |
March | 0.993672E+11 | 92890.77 | 02-MAR-08:09 | 0.112920E+11 | 42311.94 | 02-MAR-07:49 |
April | 0.105475E+12 | 124612.13 | 21-APR-15:09 | 0.840732E+10 | 20006.91 | 12-APR-06:10 |
May | 0.132212E+12 | 144965.56 | 30-MAY-15:00 | 0.834577E+10 | 8941.40 | 01-MAY-11:20 |
June | 0.152821E+12 | 152390.70 | 15-JUN-14:30 | 0.783998E+10 | 8809.81 | 01-JUN-11:09 |
July | 0.154080E+12 | 166885.61 | 20-JUL-15:09 | 0.754725E+10 | 8714.10 | 03-JUL-11:39 |
August | 0.153035E+12 | 148668.91 | 07-AUG-15:00 | 0.793542E+10 | 8720.89 | 31-AUG-11:39 |
September | 0.132294E+12 | 136358.23 | 05-SEP-15:30 | 0.760162E+10 | 8807.32 | 29-SEP-11:39 |
October | 0.111485E+12 | 125709.43 | 03-OCT-13:00 | 0.820760E+10 | 11838.49 | 25-OCT-06:30 |
November | 0.941000E+11 | 94818.07 | 09-NOV-16:10 | 0.100866E+11 | 35722.42 | 28-NOV-07:19 |
December | 0.959218E+11 | 117940.43 | 27-DEC-07:10 | 0.169807E+11 | 54172.78 | 27-DEC-07:30 |
Annual Sum or Average | 0.141179E+13 | 0.120197E+12 | ||||
Minimum of Months | 0.855265E+11 | 92890.77 | 0.754725E+10 | 8714.10 | ||
Maximum of Months | 0.154080E+12 | 166885.61 | 0.169807E+11 | 54172.78 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.173228E+11 | 0.526200E+10 | 0.593559E+11 | 0.979991E+09 | 0.441836E+10 | 1312252.65 | 0.751840E+10 | 0.610890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155623E+11 | 0.434296E+10 | 0.537310E+11 | 0.886819E+09 | 0.433849E+10 | 1186778.30 | 0.433726E+10 | 0.232640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182008E+11 | 0.424766E+10 | 0.617796E+11 | 0.102609E+10 | 0.575388E+10 | 1343621.24 | 0.262594E+10 | 0.573194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161080E+11 | 0.361096E+10 | 0.572952E+11 | 0.943600E+09 | 0.854590E+10 | 1267813.82 | 0.490660E+09 | 0.184794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173070E+11 | 0.331728E+10 | 0.605677E+11 | 0.100272E+10 | 0.135046E+11 | 1327936.95 | 92727691.01 | 0.364187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171704E+11 | 0.302802E+10 | 0.594895E+11 | 0.987054E+09 | 0.177439E+11 | 1296568.36 | 0.00 | 0.544008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161300E+11 | 0.324092E+10 | 0.583622E+11 | 0.959108E+09 | 0.168838E+11 | 1299182.41 | 0.00 | 0.585027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180244E+11 | 0.357044E+10 | 0.617796E+11 | 0.102598E+10 | 0.167301E+11 | 1343621.24 | 0.00 | 0.519033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161972E+11 | 0.385837E+10 | 0.572729E+11 | 0.943423E+09 | 0.131756E+11 | 1267813.82 | 38554715.63 | 0.408069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170147E+11 | 0.456843E+10 | 0.593671E+11 | 0.979844E+09 | 0.922561E+10 | 1312252.65 | 0.312963E+09 | 0.200155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170792E+11 | 0.493231E+10 | 0.580818E+11 | 0.961794E+09 | 0.579430E+10 | 1278270.02 | 0.279886E+10 | 0.445044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168543E+11 | 0.538871E+10 | 0.583511E+11 | 0.959541E+09 | 0.428706E+10 | 1299182.41 | 0.985650E+10 | 0.223338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202971E+12 | 0.493681E+11 | 0.705434E+12 | 0.116560E+11 | 0.120402E+12 | 15535293.87 | 0.280719E+11 | 0.293870E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155623E+11 | 0.302802E+10 | 0.537310E+11 | 0.886819E+09 | 0.428706E+10 | 1186778.30 | 0.00 | 0.223338E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.182008E+11 | 0.538871E+10 | 0.617796E+11 | 0.102609E+10 | 0.177439E+11 | 1343621.24 | 0.985650E+10 | 0.585027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.522912E+10 | 0.00 | 0.909288E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.339382E+10 | 0.00 | 0.823674E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.202075E+10 | 0.00 | 0.927129E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.126482E+09 | 0.00 | 0.828084E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.834577E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.783998E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.754725E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.793542E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.760162E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 25882597.00 | 0.00 | 0.818172E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.172213E+10 | 0.00 | 0.836452E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.820928E+10 | 0.00 | 0.877138E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.207275E+11 | 0.00 | 0.994694E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.754725E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.820928E+10 | 0.00 | 0.927129E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 20863.95 | 17-JAN-16:00 | 5557.43 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 833.06 | 17-JAN-16:00 | 5626.32 | 12-JAN-15:30 | 0.73 | 02-JAN-08:09 | 65404.14 | 27-JAN-07:10 |
February | 19810.64 | 23-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 832.84 | 13-FEB-08:20 | 7657.70 | 21-FEB-16:30 | 0.73 | 01-FEB-07:10 | 67113.69 | 03-FEB-07:10 |
March | 19759.19 | 10-MAR-16:00 | 5557.43 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 832.15 | 22-MAR-07:19 | 11044.33 | 16-MAR-15:30 | 0.73 | 01-MAR-08:09 | 61554.35 | 02-MAR-07:10 |
April | 18216.73 | 20-APR-07:10 | 5557.43 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 831.14 | 20-APR-07:19 | 19047.73 | 21-APR-15:09 | 0.73 | 01-APR-05:10 | 17467.79 | 12-APR-06:10 |
May | 17203.49 | 23-MAY-12:30 | 5557.43 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 829.79 | 03-MAY-07:19 | 26811.85 | 30-MAY-15:00 | 0.73 | 01-MAY-05:19 | 9426.14 | 02-MAY-06:10 |
June | 16897.09 | 29-JUN-07:10 | 3195.36 | 01-JUN-19:10 | 45864.70 | 01-JUN-07:10 | 829.40 | 29-JUN-07:19 | 26721.72 | 19-JUN-14:30 | 0.73 | 01-JUN-05:30 | 0.00 | 01-JUN-00:10 |
July | 18046.67 | 07-JUL-07:30 | 5557.43 | 06-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 830.92 | 07-JUL-07:40 | 33449.55 | 20-JUL-14:00 | 0.73 | 01-JUL-05:19 | 0.00 | 01-JUL-00:10 |
August | 17980.85 | 17-AUG-07:10 | 5557.43 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 830.83 | 17-AUG-07:19 | 24295.26 | 07-AUG-14:00 | 0.73 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 17913.28 | 18-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 830.74 | 18-SEP-07:19 | 20832.40 | 05-SEP-15:30 | 0.73 | 01-SEP-05:19 | 5634.29 | 25-SEP-06:10 |
October | 20262.04 | 13-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 833.85 | 13-OCT-07:19 | 17029.29 | 03-OCT-15:39 | 0.73 | 01-OCT-05:10 | 15526.75 | 25-OCT-06:10 |
November | 21377.78 | 22-NOV-16:00 | 5557.43 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 833.78 | 28-NOV-16:00 | 11612.74 | 10-NOV-15:00 | 0.73 | 27-NOV-08:09 | 59523.72 | 28-NOV-07:10 |
December | 21377.78 | 01-DEC-16:00 | 5557.43 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 833.83 | 11-DEC-16:00 | 4631.42 | 07-DEC-13:00 | 0.73 | 04-DEC-07:10 | 85850.00 | 27-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 16897.09 | 3195.36 | 45864.70 | 829.40 | 4631.42 | 0.73 | 0.00 | |||||||
Maximum of Months | 21377.78 | 5557.43 | 45864.70 | 833.85 | 33449.55 | 0.73 | 85850.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 10252.04 | 03-JAN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16872.90 | 21-FEB-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22205.09 | 21-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45896.61 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59643.75 | 30-MAY-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 69754.94 | 15-JUN-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73716.27 | 20-JUL-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 68626.52 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 55856.04 | 05-SEP-15:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 55495.30 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23067.68 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5055.46 | 20-DEC-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 5055.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73716.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 102697.75 | 17-JAN-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 3271.54 | 0.73 | 65399.70 | 0.00 | 0.00 |
February | 98925.83 | 03-FEB-07:10 | 7126.03 | 21098.80 | 0.00 | 243.52 | 3343.06 | 0.73 | 67113.69 | 0.00 | 0.00 |
March | 92890.77 | 02-MAR-08:09 | 17006.27 | 45864.70 | 0.00 | 814.73 | 3230.15 | 0.73 | 25974.20 | 0.00 | 0.00 |
April | 124612.13 | 21-APR-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 19047.73 | 0.73 | 0.00 | 45844.62 | 0.00 |
May | 144965.56 | 30-MAY-15:00 | 16818.70 | 42072.41 | 0.00 | 827.95 | 26811.85 | 0.73 | 0.00 | 58433.92 | 0.00 |
June | 152390.70 | 15-JUN-14:30 | 16818.70 | 40588.47 | 0.00 | 827.42 | 24654.53 | 0.73 | 0.00 | 69500.84 | 0.00 |
July | 166885.61 | 20-JUL-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 33449.55 | 0.73 | 0.00 | 73716.27 | 0.00 |
August | 148668.91 | 07-AUG-15:00 | 16818.70 | 42072.41 | 0.00 | 827.95 | 20322.60 | 0.73 | 0.00 | 68626.52 | 0.00 |
September | 136358.23 | 05-SEP-15:30 | 16925.53 | 42072.41 | 0.00 | 828.00 | 20832.40 | 0.73 | 0.00 | 55699.17 | 0.00 |
October | 125709.43 | 03-OCT-13:00 | 16818.70 | 40588.47 | 0.00 | 827.42 | 11978.81 | 0.73 | 0.00 | 55495.30 | 0.00 |
November | 94818.07 | 09-NOV-16:10 | 18102.54 | 42072.41 | 0.00 | 829.39 | 11395.88 | 0.73 | 0.00 | 22417.11 | 0.00 |
December | 117940.43 | 27-DEC-07:10 | 7126.03 | 21098.80 | 0.00 | 243.52 | 3621.35 | 0.73 | 85850.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 92890.77 | 7126.03 | 21098.80 | 0.00 | 243.52 | 3230.15 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 166885.61 | 18102.54 | 45864.70 | 5557.43 | 829.39 | 33449.55 | 0.73 | 85850.00 | 73716.27 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 44043.69 | 27-JAN-07:19 | 0.00 | 9221.86 | 26-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 46100.01 | 03-FEB-07:10 | 0.00 | 9222.10 | 03-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 35708.55 | 02-MAR-07:19 | 0.00 | 9176.67 | 03-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 11934.20 | 12-APR-06:10 | 0.00 | 9060.14 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 8941.40 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 8809.81 | 01-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8714.10 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8720.89 | 31-AUG-11:39 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8807.32 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 4348.93 | 25-OCT-06:10 | 0.00 | 8939.82 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 27654.34 | 28-NOV-07:19 | 0.00 | 9082.53 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 46507.56 | 27-DEC-07:19 | 0.00 | 9178.59 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8714.10 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 46507.56 | 0.00 | 9222.10 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.18 | 0.00 | 26.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.18 | 0.00 | 26.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.98 | 0.17 | 25.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.17 | 0.00 | 26.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.17 | 0.00 | 26.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.83 | 26.12 | 0.17 | 26.06 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.18 | 0.17 | 26.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.33 | 24.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 24.57 | 0.33 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.57 | 0.33 | 24.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.36 | 1.00 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.49 | 2.67 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.43 | 4.83 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.45 | 2.00 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
Annual Sum or Average | 0.67 | 17.15 | 0.00 | 17.15 | 15.67 | 27.02 | 10.50 | 27.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.24 | 0.00 | 17.24 | 6.83 | 27.49 | 4.83 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.69 | 2.50 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.74 | 10.50 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.86 | 10.17 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.83 | 15.17 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.85 | 9.67 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.67 | 7.67 | 27.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.42 | 0.50 | 27.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
Annual Sum or Average | 0.67 | 17.12 | 0.00 | 17.12 | 60.00 | 27.68 | 56.17 | 27.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 17.12 | 0.00 | 17.12 | 16.83 | 27.86 | 15.17 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.52 | 1.67 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.53 | 2.50 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.47 | 4.50 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.50 | 3.83 | 27.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.53 | 7.17 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.69 | 6.17 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.83 | 7.17 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.93 | 7.00 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.61 | 3.67 | 27.61 |
December | 0.33 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
Annual Sum or Average | 0.33 | 17.17 | 0.00 | 17.17 | 48.17 | 27.59 | 43.67 | 27.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 17.17 | 0.00 | 17.17 | 8.50 | 27.93 | 7.17 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.44 | 0.50 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.09 | 3.50 | 28.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.27 | 4.67 | 28.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.35 | 4.17 | 28.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.15 | 6.50 | 28.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.30 | 4.50 | 28.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.09 | 4.50 | 28.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.81 | 2.67 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
Annual Sum or Average | 0.50 | 17.13 | 0.00 | 17.13 | 51.50 | 28.08 | 31.00 | 28.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 17.13 | 0.00 | 17.13 | 12.33 | 28.35 | 6.50 | 28.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.47 | 0.83 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.55 | 3.67 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.67 | 4.33 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.62 | 8.67 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.62 | 7.67 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.57 | 6.33 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 32.50 | 27.60 | 32.00 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.67 | 8.67 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.17 | 18.11 | 27.17 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
February | 18.33 | 17.85 | 18.33 | 17.85 | 0.83 | 18.06 | 0.83 | 18.26 |
March | 23.17 | 18.49 | 23.17 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
April | 5.00 | 18.83 | 5.00 | 18.83 | 1.50 | 19.59 | 1.50 | 20.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 24.98 | 9.50 | 24.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 | 25.80 | 33.67 | 25.80 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 25.53 | 30.17 | 25.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 25.54 | 34.50 | 25.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 25.53 | 38.50 | 25.53 |
October | 2.00 | 20.18 | 2.00 | 20.18 | 19.00 | 25.02 | 18.17 | 25.45 |
November | 18.00 | 19.18 | 18.00 | 19.18 | 5.83 | 20.35 | 5.83 | 21.23 |
December | 28.83 | 17.86 | 28.83 | 17.86 | 0.00 | 17.86 | 0.00 | 17.86 |
Annual Sum or Average | 122.50 | 18.31 | 122.50 | 18.31 | 173.67 | 21.36 | 172.67 | 22.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.86 | 0.00 | 17.86 |
Maximum of Months | 28.83 | 20.18 | 28.83 | 20.18 | 38.50 | 25.80 | 38.50 | 25.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.72 | 1.67 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.83 | 3.67 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.91 | 3.17 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.79 | 4.67 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.91 | 3.83 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.77 | 4.17 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.69 | 2.33 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 36.33 | 27.82 | 23.50 | 27.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.91 | 4.67 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.39 | 0.50 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.37 | 0.67 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.17 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 27.35 | 1.33 | 27.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.39 | 0.67 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.69 | 3.17 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.85 | 5.83 | 27.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.82 | 7.67 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.76 | 11.50 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.79 | 7.67 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.74 | 4.83 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.46 | 1.17 | 27.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 42.50 | 27.77 | 41.83 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 27.85 | 11.50 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.67 | 27.28 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.50 | 2.17 | 27.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.42 | 1.33 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.38 | 1.33 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.41 | 3.00 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.48 | 5.67 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.68 | 6.83 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.89 | 6.83 | 27.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.65 | 5.33 | 27.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.28 | 0.50 | 27.28 |
Annual Sum or Average | 0.00 | 0.00 | 34.67 | 27.61 | 33.83 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.89 | 6.83 | 27.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.47 | 0.17 | 27.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.93 | 3.00 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.04 | 4.67 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.16 | 4.00 | 28.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.97 | 5.33 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.13 | 4.00 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.96 | 3.83 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.71 | 2.83 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 44.00 | 28.01 | 27.83 | 28.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.16 | 5.33 | 28.23 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.83 | 23.92 | 0.00 | 23.92 | 0.00 | 23.92 |
February | 388.00 | 24.00 | 4.50 | 24.01 | 0.00 | 24.01 |
March | 412.00 | 23.98 | 4.50 | 24.00 | 0.00 | 24.00 |
April | 136.00 | 24.01 | 60.50 | 24.44 | 0.00 | 24.44 |
May | 19.67 | 24.00 | 205.67 | 24.67 | 0.00 | 24.67 |
June | 0.00 | 0.00 | 333.67 | 24.48 | 0.00 | 24.48 |
July | 28.00 | 24.47 | 495.50 | 24.40 | 28.00 | 24.41 |
August | 0.83 | 24.00 | 500.50 | 24.37 | 0.83 | 24.37 |
September | 7.33 | 25.71 | 429.50 | 24.47 | 7.33 | 24.49 |
October | 6.67 | 24.00 | 283.17 | 24.61 | 0.00 | 24.61 |
November | 231.50 | 23.98 | 54.00 | 24.17 | 0.00 | 24.17 |
December | 472.17 | 23.92 | 0.00 | 23.92 | 0.00 | 23.92 |
Annual Sum or Average | 2175.00 | 23.97 | 2371.50 | 24.25 | 36.17 | 24.26 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.92 | 0.00 | 23.92 |
Maximum of Months | 472.83 | 25.71 | 500.50 | 24.67 | 28.00 | 24.67 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.78 | 0.00 | 22.78 | 0.00 | 22.78 |
February | 454.00 | 23.17 | 0.00 | 23.17 | 0.00 | 23.17 |
March | 508.17 | 23.56 | 0.00 | 23.56 | 0.00 | 23.56 |
April | 265.33 | 23.86 | 14.67 | 23.93 | 0.00 | 23.93 |
May | 56.33 | 23.94 | 162.67 | 24.36 | 0.00 | 24.36 |
June | 4.00 | 24.00 | 307.33 | 24.39 | 0.00 | 24.39 |
July | 62.00 | 24.22 | 493.17 | 24.30 | 62.00 | 24.29 |
August | 12.17 | 24.00 | 484.83 | 24.28 | 12.17 | 24.27 |
September | 26.67 | 24.32 | 396.83 | 24.33 | 19.17 | 24.34 |
October | 122.17 | 23.70 | 179.50 | 24.06 | 4.50 | 24.06 |
November | 409.50 | 23.40 | 6.83 | 23.42 | 0.00 | 23.42 |
December | 497.00 | 22.62 | 1.50 | 22.61 | 1.50 | 22.61 |
Annual Sum or Average | 2919.33 | 23.25 | 2047.33 | 23.70 | 99.33 | 23.71 |
Minimum of Months | 4.00 | 22.62 | 0.00 | 22.61 | 0.00 | 22.61 |
Maximum of Months | 508.17 | 24.32 | 493.17 | 24.39 | 62.00 | 24.39 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.80 | 89.33 | 21.62 | 89.33 | 21.48 |
February | 454.00 | 22.34 | 44.50 | 22.21 | 44.50 | 22.10 |
March | 514.00 | 23.01 | 5.83 | 22.98 | 5.83 | 22.96 |
April | 299.00 | 23.63 | 16.67 | 23.68 | 0.00 | 23.68 |
May | 91.50 | 23.79 | 171.50 | 24.24 | 0.00 | 24.24 |
June | 7.33 | 24.00 | 325.17 | 24.40 | 0.00 | 24.40 |
July | 40.00 | 24.11 | 493.00 | 24.33 | 40.00 | 24.31 |
August | 6.50 | 24.00 | 478.83 | 24.28 | 6.50 | 24.28 |
September | 43.50 | 23.82 | 374.67 | 24.23 | 15.00 | 24.24 |
October | 236.33 | 23.41 | 123.67 | 23.66 | 2.17 | 23.66 |
November | 451.17 | 22.59 | 21.83 | 22.51 | 21.83 | 22.43 |
December | 497.00 | 21.53 | 152.17 | 21.30 | 152.17 | 21.17 |
Annual Sum or Average | 3142.33 | 22.57 | 2297.17 | 23.10 | 377.33 | 22.98 |
Minimum of Months | 6.50 | 21.53 | 5.83 | 21.30 | 0.00 | 21.17 |
Maximum of Months | 514.00 | 24.11 | 493.00 | 24.40 | 152.17 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.85 | 288.17 | 20.66 | 288.17 | 20.57 |
February | 454.00 | 21.43 | 177.83 | 21.17 | 177.83 | 21.02 |
March | 514.00 | 22.25 | 101.00 | 21.98 | 101.00 | 21.78 |
April | 304.83 | 23.17 | 48.17 | 23.24 | 10.17 | 23.17 |
May | 107.50 | 23.66 | 217.83 | 24.27 | 1.67 | 24.29 |
June | 16.33 | 25.56 | 394.67 | 24.55 | 8.67 | 24.60 |
July | 71.83 | 25.09 | 495.83 | 24.59 | 71.83 | 24.65 |
August | 32.83 | 24.49 | 472.83 | 24.39 | 21.50 | 24.42 |
September | 83.33 | 23.49 | 348.00 | 24.17 | 21.50 | 24.17 |
October | 310.67 | 22.87 | 108.83 | 23.20 | 7.33 | 23.21 |
November | 472.00 | 21.65 | 132.67 | 21.38 | 132.67 | 21.20 |
December | 497.00 | 20.61 | 351.83 | 20.46 | 351.83 | 20.40 |
Annual Sum or Average | 3366.33 | 21.92 | 3137.67 | 22.47 | 1194.17 | 22.23 |
Minimum of Months | 16.33 | 20.61 | 48.17 | 20.46 | 1.67 | 20.40 |
Maximum of Months | 514.00 | 25.56 | 495.83 | 24.59 | 351.83 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.25 | 191.17 | 20.96 | 191.17 | 20.80 |
February | 438.17 | 21.96 | 101.50 | 21.66 | 101.50 | 21.45 |
March | 417.33 | 22.51 | 64.00 | 22.32 | 57.17 | 22.12 |
April | 175.17 | 23.29 | 129.83 | 23.90 | 9.83 | 23.90 |
May | 81.50 | 24.71 | 317.50 | 24.64 | 28.00 | 24.80 |
June | 40.17 | 26.52 | 438.17 | 24.71 | 34.33 | 24.86 |
July | 109.33 | 25.75 | 495.50 | 24.81 | 109.33 | 24.96 |
August | 54.50 | 25.72 | 485.50 | 24.57 | 44.00 | 24.71 |
September | 83.83 | 24.89 | 399.33 | 24.53 | 47.67 | 24.68 |
October | 209.83 | 22.67 | 174.83 | 23.49 | 4.50 | 23.49 |
November | 443.00 | 22.09 | 91.33 | 21.88 | 80.17 | 21.68 |
December | 497.00 | 20.97 | 250.67 | 20.72 | 250.67 | 20.60 |
Annual Sum or Average | 3051.83 | 22.32 | 3139.33 | 22.98 | 958.33 | 22.84 |
Minimum of Months | 40.17 | 20.97 | 64.00 | 20.72 | 4.50 | 20.60 |
Maximum of Months | 502.00 | 26.52 | 495.50 | 24.81 | 250.67 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 384.50 | 21.74 | 154.50 | 21.54 | 130.50 | 21.28 |
February | 327.33 | 22.04 | 110.17 | 22.00 | 84.00 | 21.75 |
March | 353.50 | 22.46 | 89.67 | 22.38 | 67.33 | 22.15 |
April | 227.67 | 23.15 | 109.17 | 23.60 | 12.83 | 23.55 |
May | 117.83 | 23.77 | 233.33 | 24.31 | 10.00 | 24.38 |
June | 25.33 | 25.18 | 381.67 | 24.54 | 10.83 | 24.60 |
July | 79.17 | 25.23 | 495.00 | 24.60 | 79.17 | 24.67 |
August | 49.17 | 25.16 | 472.00 | 24.49 | 34.33 | 24.58 |
September | 85.50 | 24.63 | 389.83 | 24.50 | 45.50 | 24.63 |
October | 198.83 | 23.40 | 254.17 | 24.06 | 27.67 | 24.22 |
November | 302.33 | 22.12 | 139.50 | 22.45 | 59.83 | 22.23 |
December | 398.67 | 21.66 | 166.83 | 21.34 | 157.00 | 21.10 |
Annual Sum or Average | 2549.83 | 22.57 | 2995.83 | 23.27 | 719.00 | 23.12 |
Minimum of Months | 25.33 | 21.66 | 89.67 | 21.34 | 10.00 | 21.10 |
Maximum of Months | 398.67 | 25.23 | 495.00 | 24.60 | 157.00 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 488.33 | 21.18 | 235.67 | 20.90 | 235.33 | 20.75 |
February | 423.67 | 21.56 | 164.17 | 21.34 | 156.33 | 21.16 |
March | 416.33 | 22.04 | 113.33 | 21.90 | 96.67 | 21.70 |
April | 257.17 | 22.96 | 115.17 | 23.41 | 19.17 | 23.41 |
May | 132.50 | 23.92 | 271.67 | 24.36 | 23.33 | 24.51 |
June | 40.00 | 25.41 | 391.83 | 24.60 | 20.83 | 24.71 |
July | 83.83 | 25.24 | 491.50 | 24.60 | 83.83 | 24.68 |
August | 63.00 | 24.72 | 463.50 | 24.45 | 37.17 | 24.54 |
September | 104.83 | 23.92 | 369.17 | 24.29 | 43.33 | 24.39 |
October | 270.83 | 22.77 | 177.50 | 23.43 | 11.50 | 23.50 |
November | 413.67 | 21.65 | 136.67 | 21.52 | 114.17 | 21.33 |
December | 495.50 | 21.01 | 284.17 | 20.73 | 284.17 | 20.60 |
Annual Sum or Average | 3189.67 | 22.09 | 3214.33 | 22.72 | 1125.83 | 22.54 |
Minimum of Months | 40.00 | 21.01 | 113.33 | 20.73 | 11.50 | 20.60 |
Maximum of Months | 495.50 | 25.41 | 491.50 | 24.60 | 284.17 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.29 | 144.67 | 21.16 | 144.67 | 21.08 |
February | 454.00 | 21.51 | 134.17 | 21.33 | 134.17 | 21.22 |
March | 514.00 | 22.00 | 65.00 | 21.86 | 65.00 | 21.74 |
April | 417.00 | 23.23 | 3.50 | 23.22 | 2.67 | 23.21 |
May | 159.67 | 23.69 | 135.67 | 24.00 | 0.00 | 24.00 |
June | 11.67 | 23.95 | 317.83 | 24.40 | 0.00 | 24.40 |
July | 42.67 | 24.29 | 495.00 | 24.40 | 42.67 | 24.40 |
August | 8.00 | 24.00 | 494.17 | 24.34 | 8.00 | 24.33 |
September | 36.17 | 23.98 | 392.33 | 24.31 | 17.50 | 24.31 |
October | 225.17 | 23.56 | 143.50 | 23.80 | 2.50 | 23.80 |
November | 459.17 | 22.54 | 8.83 | 22.51 | 8.83 | 22.48 |
December | 497.00 | 21.31 | 169.83 | 21.15 | 169.83 | 21.05 |
Annual Sum or Average | 3326.50 | 22.20 | 2504.50 | 22.80 | 595.83 | 22.65 |
Minimum of Months | 8.00 | 21.29 | 3.50 | 21.15 | 0.00 | 21.05 |
Maximum of Months | 514.00 | 24.29 | 495.00 | 24.40 | 169.83 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.95 | 62.17 | 21.80 | 62.17 | 21.68 |
February | 444.33 | 22.38 | 44.00 | 22.23 | 44.00 | 22.10 |
March | 482.50 | 22.83 | 29.17 | 22.74 | 26.67 | 22.64 |
April | 215.67 | 23.55 | 83.83 | 24.04 | 0.67 | 24.05 |
May | 57.33 | 24.14 | 267.67 | 24.57 | 7.17 | 24.62 |
June | 16.00 | 26.35 | 418.67 | 24.58 | 12.50 | 24.65 |
July | 74.00 | 25.52 | 496.17 | 24.72 | 74.00 | 24.81 |
August | 30.33 | 26.42 | 506.50 | 24.58 | 30.33 | 24.68 |
September | 43.67 | 25.94 | 442.17 | 24.65 | 38.00 | 24.77 |
October | 113.83 | 23.51 | 236.50 | 24.18 | 2.00 | 24.18 |
November | 379.17 | 23.03 | 23.83 | 23.12 | 1.67 | 23.11 |
December | 497.00 | 21.98 | 72.33 | 21.81 | 72.33 | 21.67 |
Annual Sum or Average | 2855.83 | 22.77 | 2683.00 | 23.49 | 371.50 | 23.46 |
Minimum of Months | 16.00 | 21.95 | 23.83 | 21.80 | 0.67 | 21.67 |
Maximum of Months | 502.00 | 26.42 | 506.50 | 24.72 | 74.00 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 407.33 | 21.86 | 68.50 | 21.83 | 42.67 | 21.59 |
February | 380.50 | 22.05 | 59.00 | 22.09 | 33.00 | 21.87 |
March | 456.33 | 22.31 | 63.17 | 22.21 | 43.67 | 22.00 |
April | 318.17 | 23.01 | 53.00 | 23.24 | 7.00 | 23.17 |
May | 163.00 | 23.29 | 139.33 | 23.89 | 0.00 | 23.89 |
June | 32.00 | 23.28 | 309.17 | 24.49 | 3.00 | 24.49 |
July | 89.83 | 24.11 | 493.83 | 24.45 | 89.83 | 24.41 |
August | 47.33 | 24.10 | 494.67 | 24.45 | 42.83 | 24.44 |
September | 72.83 | 24.65 | 430.17 | 24.64 | 53.50 | 24.72 |
October | 108.67 | 23.70 | 302.67 | 24.44 | 31.33 | 24.58 |
November | 260.17 | 22.47 | 109.00 | 23.08 | 16.50 | 22.96 |
December | 408.00 | 21.89 | 72.67 | 21.76 | 53.33 | 21.49 |
Annual Sum or Average | 2744.17 | 22.52 | 2595.17 | 23.37 | 416.67 | 23.28 |
Minimum of Months | 32.00 | 21.86 | 53.00 | 21.76 | 0.00 | 21.49 |
Maximum of Months | 456.33 | 24.65 | 494.67 | 24.64 | 89.83 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.83 | 21.84 | 70.83 | 21.70 | 70.83 | 21.59 |
February | 442.83 | 22.03 | 67.50 | 21.89 | 64.50 | 21.77 |
March | 464.83 | 22.47 | 37.17 | 22.43 | 29.00 | 22.34 |
April | 278.67 | 23.36 | 74.83 | 23.71 | 1.33 | 23.73 |
May | 108.83 | 23.92 | 245.00 | 24.38 | 7.83 | 24.44 |
June | 19.67 | 25.73 | 385.50 | 24.55 | 11.33 | 24.61 |
July | 66.00 | 25.21 | 495.17 | 24.60 | 66.00 | 24.66 |
August | 27.83 | 25.97 | 504.50 | 24.53 | 27.83 | 24.60 |
September | 43.00 | 25.11 | 432.50 | 24.55 | 33.17 | 24.62 |
October | 99.83 | 23.74 | 239.17 | 24.26 | 9.17 | 24.32 |
November | 371.83 | 22.83 | 34.33 | 22.96 | 2.33 | 22.95 |
December | 497.00 | 21.86 | 95.17 | 21.67 | 95.17 | 21.54 |
Annual Sum or Average | 2914.17 | 22.58 | 2681.67 | 23.33 | 418.50 | 23.28 |
Minimum of Months | 19.67 | 21.84 | 34.33 | 21.67 | 1.33 | 21.54 |
Maximum of Months | 497.00 | 25.97 | 504.50 | 24.60 | 95.17 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.40 | 141.83 | 21.23 | 141.83 | 21.12 |
February | 454.00 | 21.97 | 76.17 | 21.79 | 76.17 | 21.66 |
March | 514.00 | 22.72 | 26.00 | 22.63 | 26.00 | 22.54 |
April | 289.00 | 23.53 | 28.17 | 23.61 | 0.00 | 23.61 |
May | 82.50 | 23.86 | 209.50 | 24.37 | 0.00 | 24.37 |
June | 4.00 | 24.99 | 377.83 | 24.52 | 1.17 | 24.53 |
July | 69.67 | 24.38 | 496.67 | 24.48 | 69.67 | 24.47 |
August | 21.17 | 24.21 | 490.33 | 24.37 | 21.17 | 24.36 |
September | 56.17 | 23.84 | 378.50 | 24.27 | 28.17 | 24.26 |
October | 266.50 | 23.38 | 130.83 | 23.64 | 7.00 | 23.64 |
November | 461.83 | 22.32 | 34.33 | 22.20 | 34.33 | 22.10 |
December | 497.00 | 21.18 | 212.83 | 20.99 | 212.83 | 20.89 |
Annual Sum or Average | 3217.83 | 22.34 | 2603.00 | 22.95 | 618.33 | 22.80 |
Minimum of Months | 4.00 | 21.18 | 26.00 | 20.99 | 0.00 | 20.89 |
Maximum of Months | 514.00 | 24.99 | 496.67 | 24.52 | 212.83 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 21.71 | 89.83 | 21.50 | 89.83 | 21.35 |
February | 363.17 | 22.31 | 48.50 | 22.19 | 42.67 | 22.04 |
March | 362.17 | 22.81 | 35.00 | 22.84 | 19.83 | 22.73 |
April | 157.83 | 23.58 | 100.67 | 24.19 | 4.33 | 24.24 |
May | 55.33 | 24.84 | 250.67 | 24.80 | 18.33 | 24.93 |
June | 28.67 | 26.75 | 356.33 | 24.81 | 26.17 | 24.95 |
July | 104.00 | 25.55 | 422.00 | 24.87 | 104.00 | 24.98 |
August | 43.00 | 26.00 | 416.00 | 24.67 | 41.17 | 24.79 |
September | 53.83 | 25.28 | 345.00 | 24.64 | 37.00 | 24.77 |
October | 171.67 | 23.21 | 165.50 | 23.88 | 5.00 | 23.89 |
November | 359.67 | 22.52 | 37.17 | 22.52 | 21.33 | 22.41 |
December | 422.00 | 21.51 | 132.17 | 21.26 | 132.17 | 21.10 |
Annual Sum or Average | 2548.33 | 22.68 | 2398.83 | 23.39 | 541.83 | 23.34 |
Minimum of Months | 28.67 | 21.51 | 35.00 | 21.26 | 4.33 | 21.10 |
Maximum of Months | 427.00 | 26.75 | 422.00 | 24.87 | 132.17 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 355.33 | 22.27 | 78.83 | 22.32 | 46.67 | 22.14 |
February | 305.00 | 22.61 | 53.83 | 22.79 | 24.00 | 22.66 |
March | 337.67 | 22.99 | 35.33 | 23.16 | 10.33 | 23.09 |
April | 199.33 | 23.53 | 91.67 | 23.98 | 0.83 | 23.99 |
May | 82.00 | 23.84 | 226.50 | 24.41 | 1.33 | 24.42 |
June | 11.00 | 24.70 | 373.67 | 24.50 | 2.33 | 24.52 |
July | 81.17 | 24.74 | 495.83 | 24.53 | 81.17 | 24.56 |
August | 32.50 | 25.61 | 493.17 | 24.49 | 32.50 | 24.56 |
September | 61.33 | 25.31 | 419.00 | 24.59 | 46.00 | 24.71 |
October | 148.83 | 24.02 | 285.83 | 24.39 | 28.33 | 24.53 |
November | 268.83 | 22.80 | 107.17 | 23.33 | 16.83 | 23.27 |
December | 362.50 | 22.22 | 89.83 | 22.09 | 73.17 | 21.87 |
Annual Sum or Average | 2245.50 | 23.00 | 2750.67 | 23.75 | 363.50 | 23.71 |
Minimum of Months | 11.00 | 22.22 | 35.33 | 22.09 | 0.83 | 21.87 |
Maximum of Months | 362.50 | 25.61 | 495.83 | 24.59 | 81.17 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 480.83 | 21.67 | 116.83 | 21.48 | 115.00 | 21.34 |
February | 418.67 | 22.08 | 70.50 | 21.96 | 62.83 | 21.82 |
March | 414.00 | 22.60 | 39.33 | 22.65 | 20.67 | 22.57 |
April | 231.67 | 23.41 | 102.33 | 23.85 | 5.33 | 23.90 |
May | 101.17 | 24.27 | 276.67 | 24.51 | 19.33 | 24.63 |
June | 27.50 | 26.05 | 399.33 | 24.61 | 18.67 | 24.71 |
July | 103.00 | 24.95 | 496.00 | 24.58 | 103.00 | 24.63 |
August | 46.50 | 25.29 | 489.67 | 24.49 | 43.67 | 24.56 |
September | 79.50 | 24.46 | 400.00 | 24.42 | 54.17 | 24.48 |
October | 215.17 | 23.36 | 204.00 | 23.88 | 12.83 | 23.95 |
November | 393.33 | 22.27 | 61.33 | 22.30 | 34.00 | 22.19 |
December | 492.67 | 21.56 | 163.50 | 21.30 | 163.50 | 21.14 |
Annual Sum or Average | 3004.00 | 22.54 | 2819.50 | 23.23 | 653.00 | 23.16 |
Minimum of Months | 27.50 | 21.56 | 39.33 | 21.30 | 5.33 | 21.14 |
Maximum of Months | 492.67 | 26.05 | 496.00 | 24.61 | 163.50 | 24.71 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.96994 | 20.41669 | 0.16235 | 5.69275 |
February | 454.00000 | 24.08586 | 17.12749 | 0.17917 | 5.81052 |
March | 514.00000 | 24.19501 | 16.59150 | 0.21679 | 6.12020 |
April | 485.00000 | 24.35256 | 20.51074 | 0.31307 | 7.28016 |
May | 508.00000 | 24.35453 | 29.46371 | -0.4580 | 9.84614 |
June | 496.00000 | 24.35343 | 35.62155 | -0.3956 | 8.69698 |
July | 497.00000 | 24.39921 | 47.75271 | -0.2964 | 7.21618 |
August | 514.00000 | 24.36152 | 45.44714 | -0.3236 | 7.54542 |
September | 485.00000 | 24.40545 | 42.81303 | -0.3336 | 7.84622 |
October | 502.00000 | 24.38130 | 34.54713 | 0.43325 | 9.22800 |
November | 489.00000 | 24.27194 | 21.75554 | 0.28328 | 6.90832 |
December | 497.00000 | 23.95939 | 17.75294 | 0.13946 | 5.55367 |
Annual Sum or Average | 5943.00000 | 24.25839 | 29.24419 | -0.0089 | 7.32441 |
Minimum of Months | 454.00000 | 23.95939 | 16.59150 | -0.4580 | 5.55367 |
Maximum of Months | 514.00000 | 24.40545 | 47.75271 | 0.43325 | 9.84614 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.78255 | 23.22386 | -0.1124 | 5.72423 |
February | 454.00000 | 23.17421 | 19.21333 | -0.0337 | 5.51391 |
March | 514.00000 | 23.57961 | 18.12498 | 0.06756 | 5.43056 |
April | 485.00000 | 24.04889 | 21.55912 | 0.23528 | 6.41043 |
May | 508.00000 | 24.22482 | 30.70720 | -0.5147 | 10.94571 |
June | 496.00000 | 24.27538 | 37.05045 | -0.4332 | 9.27897 |
July | 497.00000 | 24.30367 | 50.66031 | -0.3289 | 7.52892 |
August | 514.00000 | 24.26953 | 48.02388 | -0.3629 | 8.00832 |
September | 485.00000 | 24.27875 | 44.92342 | -0.3919 | 8.59384 |
October | 502.00000 | 24.08635 | 36.15311 | 0.34877 | 7.79332 |
November | 489.00000 | 23.53507 | 23.89163 | 0.09558 | 5.79567 |
December | 497.00000 | 22.61991 | 20.33069 | -0.1717 | 6.14378 |
Annual Sum or Average | 5943.00000 | 23.76899 | 31.24962 | -0.1351 | 7.28016 |
Minimum of Months | 454.00000 | 22.61991 | 18.12498 | -0.5147 | 5.43056 |
Maximum of Months | 514.00000 | 24.30367 | 50.66031 | 0.34877 | 10.94571 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.79991 | 24.33363 | -0.3525 | 8.57747 |
February | 454.00000 | 22.34321 | 19.93389 | -0.2344 | 7.23546 |
March | 514.00000 | 23.00566 | 18.66054 | -0.0701 | 5.99421 |
April | 485.00000 | 23.84173 | 21.51008 | 0.18643 | 6.24862 |
May | 508.00000 | 24.17866 | 30.41719 | -0.5228 | 11.29647 |
June | 496.00000 | 24.29194 | 36.60447 | -0.4104 | 8.92600 |
July | 497.00000 | 24.34288 | 49.39484 | -0.3062 | 7.29566 |
August | 514.00000 | 24.26129 | 46.85750 | -0.3617 | 8.03641 |
September | 485.00000 | 24.20380 | 44.29984 | -0.4187 | 9.17399 |
October | 502.00000 | 23.76835 | 36.48494 | 0.26579 | 6.98880 |
November | 489.00000 | 22.69972 | 25.00208 | -0.1095 | 6.67474 |
December | 497.00000 | 21.52924 | 21.27878 | -0.4405 | 10.14446 |
Annual Sum or Average | 5943.00000 | 23.36304 | 31.31980 | -0.2319 | 8.05796 |
Minimum of Months | 454.00000 | 21.52924 | 18.66054 | -0.5228 | 5.99421 |
Maximum of Months | 514.00000 | 24.34288 | 49.39484 | 0.26579 | 11.29647 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.85440 | 26.45391 | -0.5998 | 13.75530 |
February | 454.00000 | 21.42723 | 22.04708 | -0.4645 | 11.22260 |
March | 514.00000 | 22.24793 | 20.24987 | -0.2561 | 8.21835 |
April | 485.00000 | 23.56337 | 22.25531 | 0.12161 | 6.73426 |
May | 508.00000 | 24.20241 | 30.28307 | -0.4927 | 11.54981 |
June | 496.00000 | 24.41457 | 36.23306 | -0.3173 | 8.01937 |
July | 497.00000 | 24.51765 | 49.27633 | -0.2005 | 6.80796 |
August | 514.00000 | 24.32874 | 46.86551 | -0.3114 | 7.87750 |
September | 485.00000 | 24.14144 | 44.83661 | -0.4282 | 10.24684 |
October | 502.00000 | 23.33277 | 38.35869 | 0.16185 | 6.88851 |
November | 489.00000 | 21.73373 | 27.18956 | -0.3485 | 9.73413 |
December | 497.00000 | 20.60912 | 23.46945 | -0.6875 | 16.38474 |
Annual Sum or Average | 5943.00000 | 22.95935 | 32.37219 | -0.3181 | 9.77604 |
Minimum of Months | 454.00000 | 20.60912 | 20.24987 | -0.6875 | 6.73426 |
Maximum of Months | 514.00000 | 24.51765 | 49.27633 | 0.16185 | 16.38474 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25070 | 25.73274 | -0.4812 | 11.56973 |
February | 454.00000 | 22.05049 | 21.01393 | -0.2901 | 9.18540 |
March | 514.00000 | 22.84201 | 18.82138 | -0.0820 | 7.52902 |
April | 485.00000 | 23.98415 | 21.09691 | 0.27692 | 8.23715 |
May | 508.00000 | 24.36680 | 29.72156 | -0.3473 | 9.69032 |
June | 496.00000 | 24.47994 | 35.94166 | -0.2063 | 7.42026 |
July | 497.00000 | 24.60522 | 48.85141 | -0.0916 | 6.93269 |
August | 514.00000 | 24.39310 | 46.52188 | -0.2042 | 7.41072 |
September | 485.00000 | 24.31341 | 43.97161 | -0.2823 | 8.81491 |
October | 502.00000 | 23.60151 | 37.16696 | 0.26330 | 8.27519 |
November | 489.00000 | 22.28297 | 26.07748 | -0.1939 | 8.38083 |
December | 497.00000 | 20.97177 | 22.90153 | -0.5745 | 13.64122 |
Annual Sum or Average | 5943.00000 | 23.27081 | 31.56644 | -0.1843 | 8.91943 |
Minimum of Months | 454.00000 | 20.97177 | 18.82138 | -0.5745 | 6.93269 |
Maximum of Months | 514.00000 | 24.60522 | 48.85141 | 0.27692 | 13.64122 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35654 | 23.37956 | -0.1950 | 10.18822 |
February | 454.00000 | 22.74068 | 19.40845 | -0.1102 | 9.27565 |
March | 514.00000 | 23.06093 | 18.12751 | -0.0254 | 8.04694 |
April | 485.00000 | 23.80733 | 21.37418 | 0.21100 | 7.86011 |
May | 508.00000 | 24.19129 | 30.19931 | -0.4809 | 11.75129 |
June | 496.00000 | 24.38192 | 36.30518 | -0.3310 | 8.32125 |
July | 497.00000 | 24.49528 | 49.29162 | -0.2025 | 6.97712 |
August | 514.00000 | 24.35556 | 46.57235 | -0.2646 | 7.69724 |
September | 485.00000 | 24.30826 | 43.79260 | -0.2874 | 9.05520 |
October | 502.00000 | 23.90498 | 35.91271 | 0.36458 | 10.10870 |
November | 489.00000 | 23.03033 | 24.03385 | 0.01848 | 9.26611 |
December | 497.00000 | 22.18547 | 20.69730 | -0.2625 | 11.02423 |
Annual Sum or Average | 5943.00000 | 23.57403 | 30.84695 | -0.1315 | 9.13199 |
Minimum of Months | 454.00000 | 22.18547 | 18.12751 | -0.4809 | 6.97712 |
Maximum of Months | 514.00000 | 24.49528 | 49.29162 | 0.36458 | 11.75129 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.26559 | 25.28684 | -0.4835 | 12.43729 |
February | 454.00000 | 21.76784 | 20.95059 | -0.3623 | 10.61937 |
March | 514.00000 | 22.47643 | 19.06635 | -0.1644 | 8.53263 |
April | 485.00000 | 23.60703 | 21.69346 | 0.18608 | 8.23060 |
May | 508.00000 | 24.16667 | 30.15161 | -0.4232 | 11.74075 |
June | 496.00000 | 24.38933 | 36.21181 | -0.2533 | 8.13595 |
July | 497.00000 | 24.48042 | 49.30502 | -0.1478 | 7.15684 |
August | 514.00000 | 24.30828 | 46.81607 | -0.2454 | 8.09225 |
September | 485.00000 | 24.14658 | 44.57100 | -0.3408 | 10.04918 |
October | 502.00000 | 23.43439 | 37.51646 | 0.23349 | 8.39627 |
November | 489.00000 | 22.04898 | 25.80017 | -0.2432 | 9.49027 |
December | 497.00000 | 21.02398 | 22.47206 | -0.5716 | 14.50104 |
Annual Sum or Average | 5943.00000 | 23.10302 | 31.73620 | -0.2343 | 9.77536 |
Minimum of Months | 454.00000 | 21.02398 | 19.06635 | -0.5716 | 7.15684 |
Maximum of Months | 514.00000 | 24.48042 | 49.30502 | 0.23349 | 14.50104 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.29374 | 25.60011 | -0.4684 | 10.11787 |
February | 454.00000 | 21.51317 | 21.87892 | -0.4355 | 9.74860 |
March | 514.00000 | 22.00257 | 20.94786 | -0.3182 | 7.95191 |
April | 485.00000 | 23.35606 | 23.42610 | 0.04763 | 5.91107 |
May | 508.00000 | 24.05767 | 30.91467 | -0.5911 | 13.05588 |
June | 496.00000 | 24.28375 | 36.25142 | -0.4172 | 9.02025 |
July | 497.00000 | 24.41279 | 48.34286 | -0.2756 | 6.98899 |
August | 514.00000 | 24.32942 | 46.09152 | -0.3301 | 7.67368 |
September | 485.00000 | 24.27807 | 43.82628 | -0.3842 | 8.64569 |
October | 502.00000 | 23.85917 | 37.10331 | 0.29047 | 7.19632 |
November | 489.00000 | 22.63068 | 25.87397 | -0.1177 | 6.35642 |
December | 497.00000 | 21.31066 | 22.42392 | -0.4803 | 10.45327 |
Annual Sum or Average | 5943.00000 | 23.12097 | 31.96948 | -0.2901 | 8.59712 |
Minimum of Months | 454.00000 | 21.29374 | 20.94786 | -0.5911 | 5.91107 |
Maximum of Months | 514.00000 | 24.41279 | 48.34286 | 0.29047 | 13.05588 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.95256 | 25.05486 | -0.2961 | 7.88627 |
February | 454.00000 | 22.43501 | 21.05019 | -0.1983 | 7.24799 |
March | 514.00000 | 22.94541 | 19.63209 | -0.0720 | 6.57076 |
April | 485.00000 | 24.05535 | 21.74964 | 0.26072 | 7.42477 |
May | 508.00000 | 24.35516 | 29.87744 | -0.4051 | 9.78124 |
June | 496.00000 | 24.44220 | 35.65227 | -0.2772 | 7.60927 |
July | 497.00000 | 24.59572 | 47.63486 | -0.1388 | 6.60203 |
August | 514.00000 | 24.46127 | 45.51444 | -0.2017 | 6.87685 |
September | 485.00000 | 24.47423 | 42.89766 | -0.2288 | 7.41010 |
October | 502.00000 | 24.14454 | 35.93845 | 0.39725 | 9.01714 |
November | 489.00000 | 23.31083 | 24.67833 | 0.06530 | 6.32779 |
December | 497.00000 | 21.98446 | 21.98138 | -0.3055 | 8.06973 |
Annual Sum or Average | 5943.00000 | 23.60343 | 31.05215 | -0.1172 | 7.57400 |
Minimum of Months | 454.00000 | 21.95256 | 19.63209 | -0.4051 | 6.32779 |
Maximum of Months | 514.00000 | 24.59572 | 47.63486 | 0.39725 | 9.78124 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.39851 | 21.67043 | -0.1264 | 8.41196 |
February | 454.00000 | 22.53780 | 18.74445 | -0.1211 | 8.26524 |
March | 514.00000 | 22.59630 | 18.03944 | -0.1205 | 7.70614 |
April | 485.00000 | 23.52848 | 21.41466 | 0.12301 | 6.95851 |
May | 508.00000 | 23.99121 | 29.83211 | -0.5993 | 13.97298 |
June | 496.00000 | 24.35315 | 35.16157 | -0.4132 | 9.37361 |
July | 497.00000 | 24.50939 | 49.26852 | -0.2393 | 6.85213 |
August | 514.00000 | 24.44413 | 45.99266 | -0.2553 | 7.31379 |
September | 485.00000 | 24.49601 | 42.77830 | -0.2235 | 7.79354 |
October | 502.00000 | 24.23162 | 35.10409 | 0.46440 | 10.98463 |
November | 489.00000 | 23.45350 | 22.57345 | 0.16904 | 8.48476 |
December | 497.00000 | 22.39185 | 18.88820 | -0.1448 | 8.54643 |
Annual Sum or Average | 5943.00000 | 23.58346 | 30.04611 | -0.1253 | 8.73535 |
Minimum of Months | 454.00000 | 22.39185 | 18.03944 | -0.5993 | 6.85213 |
Maximum of Months | 514.00000 | 24.50939 | 49.26852 | 0.46440 | 13.97298 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.88216 | 24.80299 | -0.3114 | 8.34039 |
February | 454.00000 | 22.10900 | 21.18205 | -0.2772 | 8.14097 |
March | 514.00000 | 22.67128 | 19.83974 | -0.1362 | 6.98751 |
April | 485.00000 | 23.82886 | 22.25281 | 0.19946 | 7.11626 |
May | 508.00000 | 24.25413 | 30.16472 | -0.4513 | 10.79835 |
June | 496.00000 | 24.38880 | 35.85928 | -0.3121 | 8.04738 |
July | 497.00000 | 24.51700 | 47.97240 | -0.1794 | 6.67528 |
August | 514.00000 | 24.44121 | 45.67227 | -0.2230 | 7.06190 |
September | 485.00000 | 24.43538 | 43.13947 | -0.2505 | 7.44146 |
October | 502.00000 | 24.18062 | 35.96425 | 0.40877 | 9.22751 |
November | 489.00000 | 23.17295 | 24.57055 | 0.03670 | 6.48029 |
December | 497.00000 | 21.85892 | 21.84442 | -0.3349 | 8.63910 |
Annual Sum or Average | 5943.00000 | 23.48701 | 31.18527 | -0.1528 | 7.91757 |
Minimum of Months | 454.00000 | 21.85892 | 19.83974 | -0.4513 | 6.48029 |
Maximum of Months | 514.00000 | 24.51700 | 47.97240 | 0.40877 | 10.79835 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.40109 | 25.83304 | -0.4393 | 9.82791 |
February | 454.00000 | 21.97218 | 21.59049 | -0.3150 | 8.23568 |
March | 514.00000 | 22.72028 | 19.93488 | -0.1346 | 6.49745 |
April | 485.00000 | 23.80441 | 22.28087 | 0.17779 | 6.35592 |
May | 508.00000 | 24.26139 | 30.52637 | -0.4817 | 10.67228 |
June | 496.00000 | 24.40848 | 36.58555 | -0.3390 | 8.07508 |
July | 497.00000 | 24.49476 | 50.36857 | -0.2210 | 6.69205 |
August | 514.00000 | 24.35256 | 47.89084 | -0.3100 | 7.57065 |
September | 485.00000 | 24.24207 | 45.30173 | -0.3957 | 9.00100 |
October | 502.00000 | 23.71235 | 37.88043 | 0.25606 | 6.99538 |
November | 489.00000 | 22.40862 | 26.38443 | -0.1722 | 7.03181 |
December | 497.00000 | 21.18350 | 22.97878 | -0.5149 | 11.41899 |
Annual Sum or Average | 5943.00000 | 23.25620 | 32.38022 | -0.2409 | 8.19955 |
Minimum of Months | 454.00000 | 21.18350 | 19.93488 | -0.5149 | 6.35592 |
Maximum of Months | 514.00000 | 24.49476 | 50.36857 | 0.25606 | 11.41899 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.71346 | 24.67206 | -0.3526 | 8.89448 |
February | 385.00000 | 22.45368 | 19.80538 | -0.1857 | 7.55930 |
March | 433.00000 | 23.10567 | 18.14323 | -0.0190 | 6.76506 |
April | 410.00000 | 24.14156 | 20.94088 | 0.29870 | 8.12939 |
May | 430.00000 | 24.47891 | 29.60456 | -0.3464 | 9.45289 |
June | 418.00000 | 24.56760 | 35.63171 | -0.2289 | 7.64648 |
July | 422.00000 | 24.70193 | 49.22328 | -0.1023 | 6.96100 |
August | 433.00000 | 24.49722 | 46.78498 | -0.2081 | 7.36656 |
September | 410.00000 | 24.44618 | 43.93622 | -0.2695 | 8.36932 |
October | 427.00000 | 23.88471 | 36.61718 | 0.32311 | 8.41874 |
November | 417.00000 | 22.78060 | 24.73144 | -0.0664 | 6.98098 |
December | 422.00000 | 21.50847 | 21.78428 | -0.4255 | 10.11103 |
Annual Sum or Average | 5034.00000 | 23.52872 | 31.07098 | -0.1322 | 8.05780 |
Minimum of Months | 385.00000 | 21.50847 | 18.14323 | -0.4255 | 6.76506 |
Maximum of Months | 433.00000 | 24.70193 | 49.22328 | 0.32311 | 10.11103 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.89947 | 22.60579 | -0.0430 | 8.07618 |
February | 454.00000 | 23.24083 | 18.82254 | 0.02397 | 7.59809 |
March | 514.00000 | 23.47070 | 17.75109 | 0.07933 | 6.95136 |
April | 485.00000 | 24.04435 | 21.37296 | 0.26358 | 7.51711 |
May | 508.00000 | 24.28521 | 30.39356 | -0.4616 | 10.60263 |
June | 496.00000 | 24.39441 | 36.62506 | -0.3474 | 8.27433 |
July | 497.00000 | 24.49797 | 50.32932 | -0.2166 | 6.81227 |
August | 514.00000 | 24.39815 | 47.53575 | -0.2606 | 7.30637 |
September | 485.00000 | 24.41543 | 44.19916 | -0.2588 | 7.94506 |
October | 502.00000 | 24.20372 | 35.57915 | 0.43832 | 10.43137 |
November | 489.00000 | 23.56441 | 23.29798 | 0.16082 | 8.28664 |
December | 497.00000 | 22.80063 | 19.98356 | -0.0905 | 8.33399 |
Annual Sum or Average | 5943.00000 | 23.85523 | 30.80235 | -0.0610 | 8.18408 |
Minimum of Months | 454.00000 | 22.80063 | 17.75109 | -0.4616 | 6.81227 |
Maximum of Months | 514.00000 | 24.49797 | 50.32932 | 0.43832 | 10.60263 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.78228 | 24.75745 | -0.3309 | 9.08879 |
February | 454.00000 | 22.27378 | 20.61630 | -0.2220 | 8.01457 |
March | 514.00000 | 22.94649 | 18.82338 | -0.0459 | 6.96770 |
April | 485.00000 | 23.90480 | 21.70749 | 0.25055 | 7.80633 |
May | 508.00000 | 24.29000 | 30.29413 | -0.3979 | 10.28318 |
June | 496.00000 | 24.42187 | 36.47218 | -0.2668 | 7.86783 |
July | 497.00000 | 24.50036 | 50.27081 | -0.1590 | 6.82962 |
August | 514.00000 | 24.37612 | 47.72449 | -0.2351 | 7.46545 |
September | 485.00000 | 24.29883 | 44.90353 | -0.2989 | 8.46634 |
October | 502.00000 | 23.84877 | 37.11245 | 0.33184 | 8.55541 |
November | 489.00000 | 22.66635 | 25.13046 | -0.0806 | 7.33126 |
December | 497.00000 | 21.58040 | 22.06992 | -0.4047 | 10.27446 |
Annual Sum or Average | 5943.00000 | 23.41582 | 31.74360 | -0.1552 | 8.24817 |
Minimum of Months | 454.00000 | 21.58040 | 18.82338 | -0.4047 | 6.82962 |
Maximum of Months | 514.00000 | 24.50036 | 50.27081 | 0.33184 | 10.28318 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.847725E+09 | 0.233741E+09 | 48.56 | 0.841076E+09 | 6649541.91 | 0.00 | 0.53 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 15455.25 | 03-JAN-15:00 | 15455.25 | 03-JAN-15:00 | 450.51 | 01-JAN-15:00 | 4018.05 | 03-JAN-15:00 | 0.00 |
February | 0.306479E+10 | 0.808865E+09 | 99.28 | 0.305034E+10 | 14450344.18 | 0.00 | 0.83 | 21-FEB-16:20 | 0.00 | 01-FEB-00:10 | 26178.76 | 21-FEB-16:20 | 26178.76 | 21-FEB-16:20 | 704.07 | 27-FEB-16:20 | 6273.72 | 21-FEB-16:20 | 0.00 |
March | 0.774080E+10 | 0.200231E+10 | 197.33 | 0.772584E+10 | 14955386.10 | 0.00 | 1.00 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 32885.03 | 21-MAR-16:00 | 32885.03 | 21-MAR-16:00 | 407.00 | 25-MAR-11:30 | 7727.28 | 21-MAR-16:00 | 0.00 |
April | 0.240472E+11 | 0.619699E+10 | 326.99 | 0.238998E+11 | 0.147335E+09 | 0.00 | 1.00 | 03-APR-11:50 | 0.00 | 01-APR-00:10 | 52510.68 | 21-APR-15:10 | 52510.68 | 21-APR-15:10 | 3199.30 | 18-APR-21:00 | 14906.26 | 21-APR-15:10 | 0.00 |
May | 0.473762E+11 | 0.124376E+11 | 445.80 | 0.462524E+11 | 0.112381E+10 | 0.00 | 1.00 | 02-MAY-14:30 | 0.00 | 01-MAY-00:10 | 64774.71 | 30-MAY-15:30 | 64774.71 | 30-MAY-15:30 | 13140.59 | 22-MAY-11:10 | 19587.50 | 30-MAY-15:30 | 0.00 |
June | 0.652113E+11 | 0.184715E+11 | 463.25 | 0.630277E+11 | 0.218361E+10 | 0.00 | 1.00 | 01-JUN-07:20 | 0.00 | 01-JUN-00:10 | 73042.57 | 19-JUN-06:03 | 69111.87 | 15-JUN-06:03 | 19118.28 | 19-JUN-18:00 | 23239.73 | 05-JUN-16:00 | 0.00 |
July | 0.769389E+11 | 0.206705E+11 | 472.46 | 0.625224E+11 | 0.144165E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 112381.20 | 20-JUL-14:55 | 82629.85 | 03-JUL-06:03 | 73440.31 | 17-JUL-06:03 | 25277.82 | 20-JUL-15:05 | 0.00 |
August | 0.713783E+11 | 0.188747E+11 | 489.94 | 0.619752E+11 | 0.940311E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 101175.16 | 08-AUG-06:03 | 80343.30 | 07-AUG-06:03 | 56548.76 | 03-AUG-06:03 | 23335.96 | 07-AUG-16:00 | 0.00 |
September | 0.591861E+11 | 0.151936E+11 | 430.87 | 0.517399E+11 | 0.744611E+10 | 0.00 | 1.00 | 01-SEP-06:03 | 0.00 | 01-SEP-00:10 | 90625.83 | 14-SEP-09:50 | 64960.46 | 18-SEP-16:00 | 48009.41 | 22-SEP-06:03 | 20922.26 | 14-SEP-09:50 | 0.00 |
October | 0.306367E+11 | 0.760393E+10 | 345.17 | 0.275291E+11 | 0.310768E+10 | 0.00 | 1.00 | 01-OCT-14:22 | 0.00 | 01-OCT-00:10 | 69516.89 | 04-OCT-10:40 | 65846.22 | 02-OCT-04:02 | 24948.06 | 04-OCT-10:40 | 18836.46 | 03-OCT-14:00 | 0.00 |
November | 0.679992E+10 | 0.173325E+10 | 158.37 | 0.667615E+10 | 0.123773E+09 | 0.00 | 1.00 | 03-NOV-14:30 | 0.00 | 01-NOV-00:10 | 38802.27 | 03-NOV-16:00 | 38802.27 | 03-NOV-16:00 | 2791.40 | 02-NOV-17:00 | 8883.27 | 03-NOV-16:00 | 0.00 |
December | 0.295073E+09 | 84412361.71 | 28.11 | 0.294017E+09 | 1055760.28 | 0.00 | 0.26 | 08-DEC-14:00 | 0.00 | 01-DEC-00:10 | 7085.30 | 08-DEC-14:00 | 7085.30 | 08-DEC-14:00 | 348.13 | 10-DEC-12:50 | 1972.66 | 08-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.393523E+12 | 0.104311E+12 | 3506.13 | 0.355534E+12 | 0.379891E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.295073E+09 | 84412361.71 | 28.11 | 0.294017E+09 | 1055760.28 | 0.00 | 0.26 | 0.00 | 7085.30 | 7085.30 | 348.13 | 1972.66 | 0.00 | ||||||
Maximum of Months | 0.769389E+11 | 0.206705E+11 | 489.94 | 0.630277E+11 | 0.144165E+11 | 0.00 | 1.00 | 0.00 | 112381.20 | 82629.85 | 73440.31 | 25277.82 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.687530E+09 | 0.190763E+09 | 48.33 | 0.680891E+09 | 6638895.30 | 0.00 | 0.47 | 12-JAN-15:00 | 0.00 | 01-JAN-00:10 | 11819.58 | 12-JAN-15:00 | 11819.58 | 12-JAN-15:00 | 425.59 | 12-JAN-17:13 | 3126.48 | 12-JAN-15:00 | 0.00 |
February | 0.284906E+10 | 0.758744E+09 | 107.33 | 0.283550E+10 | 13558732.21 | 0.00 | 0.79 | 21-FEB-16:20 | 0.00 | 01-FEB-00:10 | 21772.37 | 21-FEB-16:20 | 21772.37 | 21-FEB-16:20 | 720.60 | 27-FEB-15:20 | 5283.35 | 21-FEB-16:20 | 0.00 |
March | 0.706992E+10 | 0.183668E+10 | 209.29 | 0.706473E+10 | 5189298.01 | 0.00 | 1.00 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 29066.87 | 21-MAR-16:00 | 29066.87 | 21-MAR-16:00 | 299.25 | 11-MAR-16:00 | 6835.68 | 21-MAR-16:00 | 0.00 |
April | 0.225663E+11 | 0.581892E+10 | 343.49 | 0.224576E+11 | 0.108675E+09 | 0.00 | 1.00 | 03-APR-11:50 | 0.00 | 01-APR-00:10 | 50276.07 | 21-APR-15:00 | 50276.07 | 21-APR-15:00 | 2780.60 | 18-APR-21:00 | 14346.40 | 21-APR-15:00 | 0.00 |
May | 0.429759E+11 | 0.112731E+11 | 446.52 | 0.422453E+11 | 0.730606E+09 | 0.00 | 1.00 | 01-MAY-14:50 | 0.00 | 01-MAY-00:10 | 64664.32 | 30-MAY-06:03 | 64664.32 | 30-MAY-06:03 | 7902.28 | 28-MAY-07:53 | 18699.22 | 30-MAY-14:40 | 0.00 |
June | 0.591047E+11 | 0.167531E+11 | 463.27 | 0.577410E+11 | 0.136371E+10 | 0.00 | 1.00 | 01-JUN-07:30 | 0.00 | 01-JUN-00:10 | 70310.64 | 19-JUN-06:03 | 63559.85 | 15-JUN-14:30 | 16512.47 | 19-JUN-18:00 | 21674.18 | 15-JUN-14:30 | 0.00 |
July | 0.662169E+11 | 0.177639E+11 | 470.34 | 0.553064E+11 | 0.109105E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 99968.37 | 20-JUL-14:55 | 74720.40 | 03-JUL-06:03 | 65472.00 | 17-JUL-06:03 | 22485.81 | 20-JUL-15:05 | 0.00 |
August | 0.586507E+11 | 0.155691E+11 | 479.22 | 0.525337E+11 | 0.611699E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 81637.74 | 05-AUG-05:03 | 68611.31 | 07-AUG-06:03 | 38628.51 | 03-AUG-06:03 | 20935.04 | 07-AUG-16:00 | 0.00 |
September | 0.471915E+11 | 0.121802E+11 | 418.76 | 0.422986E+11 | 0.489289E+10 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 67988.38 | 14-SEP-09:40 | 58115.76 | 18-SEP-15:30 | 31431.16 | 14-SEP-09:40 | 17000.31 | 18-SEP-15:30 | 0.00 |
October | 0.241195E+11 | 0.603729E+10 | 334.97 | 0.219139E+11 | 0.220555E+10 | 0.00 | 1.00 | 01-OCT-13:53 | 0.00 | 01-OCT-00:10 | 59023.01 | 02-OCT-04:02 | 59023.01 | 02-OCT-04:02 | 17425.96 | 04-OCT-10:30 | 16813.78 | 03-OCT-14:00 | 0.00 |
November | 0.542200E+10 | 0.140377E+10 | 159.86 | 0.529494E+10 | 0.127054E+09 | 0.00 | 1.00 | 03-NOV-15:30 | 0.00 | 01-NOV-00:10 | 30985.21 | 09-NOV-15:20 | 30985.21 | 09-NOV-15:20 | 3133.02 | 03-NOV-11:00 | 7075.34 | 09-NOV-15:20 | 0.00 |
December | 0.247546E+09 | 70920591.16 | 27.11 | 0.246962E+09 | 584008.92 | 0.00 | 0.24 | 23-DEC-15:00 | 0.00 | 01-DEC-00:10 | 5631.65 | 23-DEC-15:00 | 5631.65 | 23-DEC-15:00 | 201.04 | 10-DEC-12:50 | 1578.02 | 23-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.337102E+12 | 0.896565E+11 | 3508.49 | 0.310620E+12 | 0.264820E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.247546E+09 | 70920591.16 | 27.11 | 0.246962E+09 | 584008.92 | 0.00 | 0.24 | 0.00 | 5631.65 | 5631.65 | 201.04 | 1578.02 | 0.00 | ||||||
Maximum of Months | 0.662169E+11 | 0.177639E+11 | 479.22 | 0.577410E+11 | 0.109105E+11 | 0.00 | 1.00 | 0.00 | 99968.37 | 74720.40 | 65472.00 | 22485.81 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.664385E+09 | 0.186387E+09 | 47.22 | 0.647862E+09 | 16522695.72 | 0.00 | 0.41 | 03-JAN-14:50 | 0.00 | 01-JAN-00:10 | 11705.64 | 03-JAN-14:50 | 11705.64 | 03-JAN-14:50 | 645.90 | 12-JAN-17:02 | 3144.07 | 03-JAN-14:50 | 0.00 |
February | 0.280991E+10 | 0.758795E+09 | 104.86 | 0.278699E+10 | 22924937.42 | 0.00 | 0.80 | 20-FEB-15:02 | 0.00 | 01-FEB-00:10 | 25433.04 | 20-FEB-15:02 | 25433.04 | 20-FEB-15:02 | 899.31 | 27-FEB-15:00 | 6158.20 | 20-FEB-15:02 | 0.00 |
March | 0.719581E+10 | 0.189295E+10 | 207.92 | 0.717698E+10 | 18824281.38 | 0.00 | 0.97 | 21-MAR-16:00 | 0.00 | 01-MAR-00:10 | 32197.15 | 21-MAR-16:00 | 32197.15 | 21-MAR-16:00 | 415.75 | 15-MAR-09:40 | 7642.13 | 21-MAR-16:00 | 0.00 |
April | 0.248905E+11 | 0.646346E+10 | 342.38 | 0.247088E+11 | 0.181680E+09 | 0.00 | 1.00 | 03-APR-12:00 | 0.00 | 01-APR-00:10 | 59325.27 | 21-APR-14:40 | 59325.27 | 21-APR-14:40 | 3505.03 | 18-APR-21:00 | 16927.53 | 21-APR-14:40 | 0.00 |
May | 0.480775E+11 | 0.127080E+11 | 446.75 | 0.470012E+11 | 0.107639E+10 | 0.00 | 1.00 | 02-MAY-14:50 | 0.00 | 01-MAY-00:10 | 72583.50 | 30-MAY-14:50 | 72583.50 | 30-MAY-14:50 | 10671.42 | 24-MAY-11:00 | 22109.54 | 30-MAY-14:50 | 0.00 |
June | 0.671635E+11 | 0.191762E+11 | 462.22 | 0.652803E+11 | 0.188322E+10 | 0.00 | 1.00 | 01-JUN-08:00 | 0.00 | 01-JUN-00:10 | 76402.71 | 15-JUN-14:40 | 76402.71 | 15-JUN-14:40 | 19077.33 | 19-JUN-18:00 | 26117.65 | 15-JUN-14:40 | 0.00 |
July | 0.742106E+11 | 0.200682E+11 | 471.81 | 0.622122E+11 | 0.119984E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 115381.31 | 20-JUL-14:55 | 83559.54 | 03-JUL-04:02 | 74980.05 | 20-JUL-14:55 | 26115.87 | 21-JUL-10:50 | 0.00 |
August | 0.651789E+11 | 0.174595E+11 | 478.66 | 0.578811E+11 | 0.729780E+10 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 78918.12 | 07-AUG-04:02 | 78918.12 | 07-AUG-04:02 | 36702.31 | 02-AUG-08:30 | 24355.52 | 07-AUG-16:00 | 0.00 |
September | 0.516062E+11 | 0.134331E+11 | 417.00 | 0.458726E+11 | 0.573359E+10 | 0.00 | 1.00 | 01-SEP-07:30 | 0.00 | 01-SEP-00:10 | 77769.40 | 14-SEP-10:00 | 67680.74 | 18-SEP-15:30 | 38079.12 | 14-SEP-10:00 | 19797.72 | 18-SEP-15:30 | 0.00 |
October | 0.251698E+11 | 0.637432E+10 | 330.17 | 0.224934E+11 | 0.267641E+10 | 0.00 | 1.00 | 01-OCT-10:53 | 0.00 | 01-OCT-00:10 | 69122.15 | 03-OCT-14:00 | 61419.12 | 05-OCT-16:00 | 17111.20 | 04-OCT-10:40 | 19845.06 | 03-OCT-14:00 | 0.00 |
November | 0.497619E+10 | 0.131342E+10 | 152.64 | 0.478986E+10 | 0.186336E+09 | 0.00 | 0.95 | 09-NOV-15:00 | 0.00 | 01-NOV-00:10 | 31662.38 | 09-NOV-15:00 | 31662.38 | 09-NOV-15:00 | 2893.17 | 03-NOV-11:40 | 7338.47 | 09-NOV-15:00 | 0.00 |
December | 0.236402E+09 | 68005466.40 | 25.72 | 0.234443E+09 | 1959237.77 | 0.00 | 0.21 | 23-DEC-15:00 | 0.00 | 01-DEC-00:10 | 5686.74 | 23-DEC-15:00 | 5686.74 | 23-DEC-15:00 | 179.12 | 08-DEC-16:20 | 1604.29 | 23-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.372180E+12 | 0.999024E+11 | 3487.34 | 0.341086E+12 | 0.310940E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.236402E+09 | 68005466.40 | 25.72 | 0.234443E+09 | 1959237.77 | 0.00 | 0.21 | 0.00 | 5686.74 | 5686.74 | 179.12 | 1604.29 | 0.00 | ||||||
Maximum of Months | 0.742106E+11 | 0.200682E+11 | 478.66 | 0.652803E+11 | 0.119984E+11 | 0.00 | 1.00 | 0.00 | 115381.31 | 83559.54 | 74980.05 | 26117.65 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 263.16 | 0.00 | 263.16 | 72.04 | 1235.16 | 0.00 | 0.00 | 0.00 |
February | 321.34 | 0.00 | 321.34 | 162.59 | 1120.56 | 0.00 | 0.00 | 0.00 |
March | 420.53 | 0.00 | 420.53 | 309.48 | 962.24 | 0.00 | 0.00 | 0.00 |
April | 485.55 | 3.83 | 481.72 | 564.33 | 574.84 | 0.00 | 0.00 | 0.00 |
May | 575.88 | 41.64 | 534.24 | 928.18 | 342.59 | 0.00 | 0.00 | 0.00 |
June | 612.35 | 75.39 | 536.96 | 1279.41 | 186.49 | 0.00 | 0.00 | 0.00 |
July | 565.93 | 55.09 | 510.84 | 1174.55 | 149.63 | 0.00 | 0.00 | 0.00 |
August | 477.20 | 9.76 | 467.44 | 916.18 | 200.00 | 0.00 | 0.00 | 0.00 |
September | 416.40 | 0.17 | 416.24 | 698.07 | 402.76 | 0.00 | 0.00 | 0.00 |
October | 345.73 | 0.00 | 345.73 | 374.55 | 638.19 | 0.00 | 0.00 | 0.00 |
November | 279.10 | 0.00 | 279.10 | 113.46 | 1072.69 | 0.00 | 0.00 | 0.00 |
December | 261.12 | 0.00 | 261.12 | 52.36 | 1359.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.17 | 15.57 | 403.60 | 555.78 | 684.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 261.12 | 0.00 | 261.12 | 52.36 | 149.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.35 | 75.39 | 536.96 | 1279.41 | 1359.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.23 | 254.54 | 214.69 | 476.45 | 762.66 | 0.00 | 0.00 | 0.00 |
February | 627.78 | 357.83 | 269.95 | 727.35 | 691.04 | 0.00 | 0.00 | 0.00 |
March | 775.10 | 427.06 | 348.05 | 968.48 | 597.83 | 0.00 | 0.00 | 0.00 |
April | 933.96 | 518.14 | 415.82 | 1366.05 | 367.28 | 0.00 | 0.00 | 0.00 |
May | 963.80 | 523.79 | 440.01 | 1576.98 | 228.83 | 0.00 | 0.00 | 0.00 |
June | 964.34 | 536.48 | 427.86 | 1772.74 | 122.02 | 0.00 | 0.00 | 0.00 |
July | 864.80 | 452.10 | 412.70 | 1594.41 | 99.54 | 0.00 | 0.00 | 0.00 |
August | 822.91 | 421.16 | 401.75 | 1465.51 | 132.57 | 0.00 | 0.00 | 0.00 |
September | 815.28 | 465.17 | 350.10 | 1359.94 | 254.61 | 0.00 | 0.00 | 0.00 |
October | 627.00 | 338.38 | 288.62 | 891.84 | 408.14 | 0.00 | 0.00 | 0.00 |
November | 562.05 | 327.21 | 234.84 | 639.99 | 663.11 | 0.00 | 0.00 | 0.00 |
December | 468.82 | 248.39 | 220.43 | 453.95 | 833.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 741.34 | 405.64 | 335.70 | 1109.00 | 428.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.82 | 248.39 | 214.69 | 453.95 | 99.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 964.34 | 536.48 | 440.01 | 1772.74 | 833.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1800.20 | 1363.84 | 436.36 | 2434.53 | 1149.58 | 0.00 | 0.00 | 0.00 |
February | 1669.89 | 1177.25 | 492.65 | 2294.39 | 1051.09 | 0.00 | 0.00 | 0.00 |
March | 1357.13 | 782.52 | 574.62 | 1918.81 | 945.25 | 0.00 | 0.00 | 0.00 |
April | 920.13 | 343.32 | 576.81 | 1460.09 | 600.85 | 0.00 | 0.00 | 0.00 |
May | 650.25 | 91.01 | 559.24 | 1141.76 | 364.67 | 0.00 | 0.00 | 0.00 |
June | 561.00 | 35.60 | 525.41 | 1209.06 | 189.78 | 0.00 | 0.00 | 0.00 |
July | 571.88 | 53.01 | 518.87 | 1221.65 | 154.33 | 0.00 | 0.00 | 0.00 |
August | 728.99 | 192.97 | 536.02 | 1468.65 | 210.73 | 0.00 | 0.00 | 0.00 |
September | 1137.86 | 591.16 | 546.71 | 2087.50 | 412.78 | 0.00 | 0.00 | 0.00 |
October | 1546.02 | 1045.21 | 500.81 | 2439.18 | 640.09 | 0.00 | 0.00 | 0.00 |
November | 1860.49 | 1418.40 | 442.10 | 2628.85 | 1005.12 | 0.00 | 0.00 | 0.00 |
December | 1843.82 | 1384.05 | 459.77 | 2454.92 | 1235.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1218.05 | 703.86 | 514.19 | 1893.90 | 661.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 561.00 | 35.60 | 436.36 | 1141.76 | 154.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1860.49 | 1418.40 | 576.81 | 2628.85 | 1235.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.28 | 278.36 | 215.92 | 554.76 | 804.42 | 0.00 | 0.00 | 0.00 |
February | 557.74 | 296.45 | 261.29 | 665.30 | 737.72 | 0.00 | 0.00 | 0.00 |
March | 760.04 | 407.36 | 352.69 | 990.96 | 640.85 | 0.00 | 0.00 | 0.00 |
April | 873.61 | 471.85 | 401.76 | 1311.96 | 401.83 | 0.00 | 0.00 | 0.00 |
May | 940.96 | 503.45 | 437.50 | 1566.00 | 253.16 | 0.00 | 0.00 | 0.00 |
June | 915.95 | 491.97 | 423.99 | 1709.23 | 136.88 | 0.00 | 0.00 | 0.00 |
July | 812.84 | 403.92 | 408.93 | 1520.71 | 110.13 | 0.00 | 0.00 | 0.00 |
August | 787.20 | 401.18 | 386.01 | 1419.04 | 145.14 | 0.00 | 0.00 | 0.00 |
September | 805.03 | 448.48 | 356.55 | 1378.89 | 282.02 | 0.00 | 0.00 | 0.00 |
October | 693.00 | 404.46 | 288.54 | 1040.96 | 434.53 | 0.00 | 0.00 | 0.00 |
November | 581.67 | 354.17 | 227.50 | 730.69 | 704.25 | 0.00 | 0.00 | 0.00 |
December | 468.74 | 254.63 | 214.11 | 502.19 | 876.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.86 | 393.29 | 331.57 | 1117.77 | 459.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.74 | 254.63 | 214.11 | 502.19 | 110.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 940.96 | 503.45 | 437.50 | 1709.23 | 876.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.71 | 0.00 | 87.71 | 21.26 | 441.36 | 0.00 | 0.00 | 0.00 |
February | 107.11 | 0.00 | 107.11 | 55.48 | 383.97 | 0.00 | 0.00 | 0.00 |
March | 140.17 | 0.00 | 140.17 | 110.93 | 318.44 | 0.00 | 0.00 | 0.00 |
April | 161.84 | 1.28 | 160.57 | 198.79 | 184.56 | 0.00 | 0.00 | 0.00 |
May | 191.95 | 13.88 | 178.07 | 320.15 | 108.35 | 0.00 | 0.00 | 0.00 |
June | 204.11 | 25.13 | 178.98 | 437.24 | 56.77 | 0.00 | 0.00 | 0.00 |
July | 188.63 | 18.36 | 170.27 | 399.65 | 47.23 | 0.00 | 0.00 | 0.00 |
August | 159.06 | 3.25 | 155.81 | 308.53 | 68.04 | 0.00 | 0.00 | 0.00 |
September | 138.79 | 0.06 | 138.74 | 232.32 | 142.56 | 0.00 | 0.00 | 0.00 |
October | 115.24 | 0.00 | 115.24 | 120.63 | 233.59 | 0.00 | 0.00 | 0.00 |
November | 93.03 | 0.00 | 93.03 | 31.76 | 400.55 | 0.00 | 0.00 | 0.00 |
December | 87.03 | 0.00 | 87.03 | 12.89 | 498.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.72 | 5.19 | 134.53 | 188.14 | 239.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.03 | 0.00 | 87.03 | 12.89 | 47.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.11 | 25.13 | 178.98 | 437.24 | 498.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.72 | 0.00 | 87.72 | 21.26 | 441.39 | 0.00 | 0.00 | 0.00 |
February | 107.12 | 0.00 | 107.12 | 55.49 | 384.00 | 0.00 | 0.00 | 0.00 |
March | 140.18 | 0.00 | 140.18 | 110.94 | 318.46 | 0.00 | 0.00 | 0.00 |
April | 161.85 | 1.28 | 160.58 | 198.81 | 184.57 | 0.00 | 0.00 | 0.00 |
May | 191.96 | 13.88 | 178.08 | 320.17 | 108.36 | 0.00 | 0.00 | 0.00 |
June | 204.12 | 25.13 | 178.99 | 437.27 | 56.77 | 0.00 | 0.00 | 0.00 |
July | 188.65 | 18.36 | 170.28 | 399.67 | 47.23 | 0.00 | 0.00 | 0.00 |
August | 159.07 | 3.25 | 155.82 | 308.55 | 68.04 | 0.00 | 0.00 | 0.00 |
September | 138.80 | 0.06 | 138.75 | 232.33 | 142.57 | 0.00 | 0.00 | 0.00 |
October | 115.24 | 0.00 | 115.24 | 120.64 | 233.61 | 0.00 | 0.00 | 0.00 |
November | 93.04 | 0.00 | 93.04 | 31.76 | 400.57 | 0.00 | 0.00 | 0.00 |
December | 87.04 | 0.00 | 87.04 | 12.89 | 498.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.72 | 5.19 | 134.53 | 188.15 | 239.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.04 | 0.00 | 87.04 | 12.89 | 47.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.12 | 25.13 | 178.99 | 437.27 | 498.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.72 | 0.00 | 87.72 | 21.26 | 441.39 | 0.00 | 0.00 | 0.00 |
February | 107.12 | 0.00 | 107.12 | 55.49 | 384.00 | 0.00 | 0.00 | 0.00 |
March | 140.18 | 0.00 | 140.18 | 110.94 | 318.46 | 0.00 | 0.00 | 0.00 |
April | 161.85 | 1.28 | 160.58 | 198.81 | 184.57 | 0.00 | 0.00 | 0.00 |
May | 191.96 | 13.88 | 178.08 | 320.17 | 108.36 | 0.00 | 0.00 | 0.00 |
June | 204.12 | 25.13 | 178.99 | 437.27 | 56.77 | 0.00 | 0.00 | 0.00 |
July | 188.65 | 18.36 | 170.28 | 399.67 | 47.23 | 0.00 | 0.00 | 0.00 |
August | 159.07 | 3.25 | 155.82 | 308.55 | 68.04 | 0.00 | 0.00 | 0.00 |
September | 138.80 | 0.06 | 138.75 | 232.33 | 142.57 | 0.00 | 0.00 | 0.00 |
October | 115.24 | 0.00 | 115.24 | 120.64 | 233.61 | 0.00 | 0.00 | 0.00 |
November | 93.04 | 0.00 | 93.04 | 31.76 | 400.57 | 0.00 | 0.00 | 0.00 |
December | 87.04 | 0.00 | 87.04 | 12.89 | 498.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 139.72 | 5.19 | 134.53 | 188.15 | 239.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 87.04 | 0.00 | 87.04 | 12.89 | 47.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 204.12 | 25.13 | 178.99 | 437.27 | 498.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 451.38 | 244.85 | 206.52 | 448.21 | 801.36 | 0.00 | 0.00 | 0.00 |
February | 603.90 | 344.22 | 259.68 | 699.05 | 701.90 | 0.00 | 0.00 | 0.00 |
March | 745.62 | 410.81 | 334.81 | 944.23 | 588.38 | 0.00 | 0.00 | 0.00 |
April | 898.43 | 498.43 | 400.01 | 1331.98 | 357.15 | 0.00 | 0.00 | 0.00 |
May | 927.13 | 503.86 | 423.27 | 1536.84 | 219.91 | 0.00 | 0.00 | 0.00 |
June | 927.65 | 516.07 | 411.59 | 1724.90 | 114.17 | 0.00 | 0.00 | 0.00 |
July | 831.90 | 434.90 | 397.00 | 1547.57 | 97.07 | 0.00 | 0.00 | 0.00 |
August | 791.60 | 405.13 | 386.47 | 1415.90 | 136.83 | 0.00 | 0.00 | 0.00 |
September | 784.26 | 447.48 | 336.79 | 1308.82 | 267.56 | 0.00 | 0.00 | 0.00 |
October | 603.15 | 325.51 | 277.64 | 851.11 | 438.38 | 0.00 | 0.00 | 0.00 |
November | 540.67 | 314.76 | 225.91 | 596.35 | 725.28 | 0.00 | 0.00 | 0.00 |
December | 450.99 | 238.94 | 212.05 | 416.67 | 895.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 713.14 | 390.20 | 322.93 | 1069.62 | 444.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 450.99 | 238.94 | 206.52 | 416.67 | 97.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 927.65 | 516.07 | 423.27 | 1724.90 | 895.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.85 | 9.68 | 8.17 | 17.72 | 31.69 | 0.00 | 0.00 | 0.00 |
February | 23.88 | 13.61 | 10.27 | 27.64 | 27.75 | 0.00 | 0.00 | 0.00 |
March | 29.48 | 16.24 | 13.24 | 37.33 | 23.26 | 0.00 | 0.00 | 0.00 |
April | 35.52 | 19.71 | 15.82 | 52.67 | 14.12 | 0.00 | 0.00 | 0.00 |
May | 36.66 | 19.92 | 16.74 | 60.77 | 8.70 | 0.00 | 0.00 | 0.00 |
June | 36.68 | 20.40 | 16.27 | 68.20 | 4.51 | 0.00 | 0.00 | 0.00 |
July | 32.89 | 17.20 | 15.70 | 61.19 | 3.84 | 0.00 | 0.00 | 0.00 |
August | 31.30 | 16.02 | 15.28 | 55.98 | 5.41 | 0.00 | 0.00 | 0.00 |
September | 31.01 | 17.69 | 13.32 | 51.75 | 10.58 | 0.00 | 0.00 | 0.00 |
October | 23.85 | 12.87 | 10.98 | 33.65 | 17.33 | 0.00 | 0.00 | 0.00 |
November | 21.38 | 12.45 | 8.93 | 23.58 | 28.68 | 0.00 | 0.00 | 0.00 |
December | 17.83 | 9.45 | 8.38 | 16.47 | 35.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.20 | 15.43 | 12.77 | 42.29 | 17.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.83 | 9.45 | 8.17 | 16.47 | 3.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 36.68 | 20.40 | 16.74 | 68.20 | 35.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 600.09 | 454.63 | 145.46 | 815.89 | 422.74 | 0.00 | 0.00 | 0.00 |
February | 556.65 | 392.43 | 164.22 | 773.95 | 372.95 | 0.00 | 0.00 | 0.00 |
March | 452.39 | 260.85 | 191.54 | 654.74 | 320.39 | 0.00 | 0.00 | 0.00 |
April | 306.72 | 114.44 | 192.27 | 499.73 | 197.17 | 0.00 | 0.00 | 0.00 |
May | 216.76 | 30.34 | 186.42 | 392.18 | 116.41 | 0.00 | 0.00 | 0.00 |
June | 187.01 | 11.87 | 175.14 | 411.19 | 58.21 | 0.00 | 0.00 | 0.00 |
July | 190.63 | 17.67 | 172.96 | 413.22 | 49.63 | 0.00 | 0.00 | 0.00 |
August | 243.00 | 64.32 | 178.68 | 491.65 | 73.68 | 0.00 | 0.00 | 0.00 |
September | 379.30 | 197.06 | 182.24 | 696.45 | 150.52 | 0.00 | 0.00 | 0.00 |
October | 515.36 | 348.42 | 166.94 | 812.65 | 238.40 | 0.00 | 0.00 | 0.00 |
November | 620.18 | 472.81 | 147.37 | 873.21 | 380.16 | 0.00 | 0.00 | 0.00 |
December | 614.63 | 461.37 | 153.26 | 817.14 | 460.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 406.03 | 234.63 | 171.40 | 636.74 | 236.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.01 | 11.87 | 145.46 | 392.18 | 49.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.18 | 472.81 | 192.27 | 873.21 | 460.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 600.09 | 454.63 | 145.46 | 815.89 | 422.74 | 0.00 | 0.00 | 0.00 |
February | 556.65 | 392.43 | 164.22 | 773.95 | 372.95 | 0.00 | 0.00 | 0.00 |
March | 452.39 | 260.85 | 191.54 | 654.74 | 320.39 | 0.00 | 0.00 | 0.00 |
April | 306.72 | 114.44 | 192.27 | 499.73 | 197.17 | 0.00 | 0.00 | 0.00 |
May | 216.76 | 30.34 | 186.42 | 392.18 | 116.41 | 0.00 | 0.00 | 0.00 |
June | 187.01 | 11.87 | 175.14 | 411.19 | 58.21 | 0.00 | 0.00 | 0.00 |
July | 190.63 | 17.67 | 172.96 | 413.22 | 49.63 | 0.00 | 0.00 | 0.00 |
August | 243.00 | 64.32 | 178.68 | 491.65 | 73.68 | 0.00 | 0.00 | 0.00 |
September | 379.30 | 197.06 | 182.24 | 696.45 | 150.52 | 0.00 | 0.00 | 0.00 |
October | 515.36 | 348.42 | 166.94 | 812.65 | 238.40 | 0.00 | 0.00 | 0.00 |
November | 620.18 | 472.81 | 147.37 | 873.21 | 380.16 | 0.00 | 0.00 | 0.00 |
December | 614.63 | 461.37 | 153.26 | 817.14 | 460.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 406.03 | 234.63 | 171.40 | 636.74 | 236.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 187.01 | 11.87 | 145.46 | 392.18 | 49.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.18 | 472.81 | 192.27 | 873.21 | 460.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 600.05 | 454.60 | 145.45 | 815.84 | 422.71 | 0.00 | 0.00 | 0.00 |
February | 556.61 | 392.40 | 164.21 | 773.90 | 372.92 | 0.00 | 0.00 | 0.00 |
March | 452.36 | 260.83 | 191.53 | 654.70 | 320.37 | 0.00 | 0.00 | 0.00 |
April | 306.70 | 114.44 | 192.26 | 499.70 | 197.15 | 0.00 | 0.00 | 0.00 |
May | 216.74 | 30.34 | 186.41 | 392.16 | 116.40 | 0.00 | 0.00 | 0.00 |
June | 186.99 | 11.86 | 175.13 | 411.16 | 58.20 | 0.00 | 0.00 | 0.00 |
July | 190.62 | 17.67 | 172.95 | 413.19 | 49.62 | 0.00 | 0.00 | 0.00 |
August | 242.99 | 64.32 | 178.67 | 491.62 | 73.67 | 0.00 | 0.00 | 0.00 |
September | 379.28 | 197.05 | 182.23 | 696.41 | 150.51 | 0.00 | 0.00 | 0.00 |
October | 515.32 | 348.39 | 166.93 | 812.60 | 238.39 | 0.00 | 0.00 | 0.00 |
November | 620.14 | 472.78 | 147.36 | 873.15 | 380.14 | 0.00 | 0.00 | 0.00 |
December | 614.59 | 461.34 | 153.25 | 817.09 | 460.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 406.00 | 234.61 | 171.39 | 636.70 | 236.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 186.99 | 11.86 | 145.45 | 392.16 | 49.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 620.14 | 472.78 | 192.26 | 873.15 | 460.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 475.48 | 267.77 | 207.70 | 530.17 | 844.89 | 0.00 | 0.00 | 0.00 |
February | 536.53 | 285.17 | 251.35 | 645.39 | 747.37 | 0.00 | 0.00 | 0.00 |
March | 731.13 | 391.86 | 339.27 | 969.30 | 633.28 | 0.00 | 0.00 | 0.00 |
April | 840.37 | 453.90 | 386.48 | 1278.79 | 392.40 | 0.00 | 0.00 | 0.00 |
May | 905.16 | 484.30 | 420.86 | 1525.04 | 245.02 | 0.00 | 0.00 | 0.00 |
June | 881.11 | 473.25 | 407.86 | 1661.31 | 128.37 | 0.00 | 0.00 | 0.00 |
July | 781.92 | 388.55 | 393.37 | 1474.37 | 107.60 | 0.00 | 0.00 | 0.00 |
August | 757.25 | 385.92 | 371.33 | 1370.08 | 150.59 | 0.00 | 0.00 | 0.00 |
September | 774.40 | 431.42 | 342.98 | 1326.40 | 297.23 | 0.00 | 0.00 | 0.00 |
October | 666.64 | 389.07 | 277.57 | 992.47 | 469.98 | 0.00 | 0.00 | 0.00 |
November | 559.54 | 340.70 | 218.84 | 689.13 | 773.19 | 0.00 | 0.00 | 0.00 |
December | 450.91 | 244.95 | 205.96 | 472.39 | 939.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 697.28 | 378.32 | 318.96 | 1079.69 | 476.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 450.91 | 244.95 | 205.96 | 472.39 | 107.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 905.16 | 484.30 | 420.86 | 1661.31 | 939.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.80 | 10.59 | 8.21 | 20.96 | 33.41 | 0.00 | 0.00 | 0.00 |
February | 21.21 | 11.28 | 9.94 | 25.52 | 29.55 | 0.00 | 0.00 | 0.00 |
March | 28.91 | 15.49 | 13.41 | 38.33 | 25.04 | 0.00 | 0.00 | 0.00 |
April | 33.23 | 17.95 | 15.28 | 50.56 | 15.52 | 0.00 | 0.00 | 0.00 |
May | 35.79 | 19.15 | 16.64 | 60.30 | 9.69 | 0.00 | 0.00 | 0.00 |
June | 34.84 | 18.71 | 16.13 | 65.69 | 5.08 | 0.00 | 0.00 | 0.00 |
July | 30.92 | 15.36 | 15.55 | 58.30 | 4.25 | 0.00 | 0.00 | 0.00 |
August | 29.94 | 15.26 | 14.68 | 54.17 | 5.95 | 0.00 | 0.00 | 0.00 |
September | 30.62 | 17.06 | 13.56 | 52.44 | 11.75 | 0.00 | 0.00 | 0.00 |
October | 26.36 | 15.38 | 10.97 | 39.24 | 18.58 | 0.00 | 0.00 | 0.00 |
November | 22.12 | 13.47 | 8.65 | 27.25 | 30.57 | 0.00 | 0.00 | 0.00 |
December | 17.83 | 9.68 | 8.14 | 18.68 | 37.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 27.57 | 14.96 | 12.61 | 42.69 | 18.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 17.83 | 9.68 | 8.14 | 18.68 | 4.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 35.79 | 19.15 | 16.64 | 65.69 | 37.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 263.16 | 0.00 | 263.16 | 59.14 | 1339.76 | 0.00 | 0.00 | 0.00 |
February | 321.34 | 0.00 | 321.34 | 147.90 | 1207.42 | 0.00 | 0.00 | 0.00 |
March | 420.53 | 0.00 | 420.53 | 295.11 | 1027.08 | 0.00 | 0.00 | 0.00 |
April | 485.55 | 3.83 | 481.72 | 560.64 | 605.86 | 0.00 | 0.00 | 0.00 |
May | 575.88 | 41.64 | 534.24 | 931.47 | 353.62 | 0.00 | 0.00 | 0.00 |
June | 612.35 | 75.39 | 536.96 | 1290.03 | 187.93 | 0.00 | 0.00 | 0.00 |
July | 565.93 | 55.09 | 510.84 | 1186.98 | 150.17 | 0.00 | 0.00 | 0.00 |
August | 477.20 | 9.76 | 467.44 | 923.49 | 205.81 | 0.00 | 0.00 | 0.00 |
September | 416.40 | 0.17 | 416.24 | 699.91 | 420.38 | 0.00 | 0.00 | 0.00 |
October | 345.73 | 0.00 | 345.73 | 364.68 | 685.25 | 0.00 | 0.00 | 0.00 |
November | 279.10 | 0.00 | 279.10 | 97.79 | 1175.16 | 0.00 | 0.00 | 0.00 |
December | 261.12 | 0.00 | 261.12 | 39.83 | 1476.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.17 | 15.57 | 403.60 | 551.82 | 733.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 261.12 | 0.00 | 261.12 | 39.83 | 150.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 612.35 | 75.39 | 536.96 | 1290.03 | 1476.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.23 | 254.54 | 214.69 | 460.12 | 823.91 | 0.00 | 0.00 | 0.00 |
February | 627.78 | 357.83 | 269.95 | 711.81 | 739.98 | 0.00 | 0.00 | 0.00 |
March | 775.10 | 427.06 | 348.05 | 957.67 | 631.88 | 0.00 | 0.00 | 0.00 |
April | 933.96 | 518.14 | 415.82 | 1365.35 | 382.41 | 0.00 | 0.00 | 0.00 |
May | 963.80 | 523.79 | 440.01 | 1581.85 | 235.56 | 0.00 | 0.00 | 0.00 |
June | 964.34 | 536.48 | 427.86 | 1781.68 | 123.14 | 0.00 | 0.00 | 0.00 |
July | 864.80 | 452.10 | 412.70 | 1603.89 | 100.14 | 0.00 | 0.00 | 0.00 |
August | 822.91 | 421.16 | 401.75 | 1471.89 | 136.18 | 0.00 | 0.00 | 0.00 |
September | 815.28 | 465.17 | 350.10 | 1362.44 | 263.75 | 0.00 | 0.00 | 0.00 |
October | 627.00 | 338.38 | 288.62 | 886.21 | 433.99 | 0.00 | 0.00 | 0.00 |
November | 562.05 | 327.21 | 234.84 | 623.08 | 718.15 | 0.00 | 0.00 | 0.00 |
December | 468.82 | 248.39 | 220.43 | 434.42 | 900.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 741.34 | 405.64 | 335.70 | 1104.62 | 456.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.82 | 248.39 | 214.69 | 434.42 | 100.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 964.34 | 536.48 | 440.01 | 1781.68 | 900.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1800.20 | 1363.84 | 436.36 | 2414.07 | 1238.35 | 0.00 | 0.00 | 0.00 |
February | 1669.89 | 1177.25 | 492.65 | 2276.47 | 1125.02 | 0.00 | 0.00 | 0.00 |
March | 1357.13 | 782.52 | 574.62 | 1906.44 | 1001.61 | 0.00 | 0.00 | 0.00 |
April | 920.13 | 343.32 | 576.81 | 1459.41 | 631.10 | 0.00 | 0.00 | 0.00 |
May | 650.25 | 91.01 | 559.24 | 1146.46 | 378.69 | 0.00 | 0.00 | 0.00 |
June | 561.00 | 35.60 | 525.41 | 1218.86 | 192.46 | 0.00 | 0.00 | 0.00 |
July | 571.88 | 53.01 | 518.87 | 1233.21 | 155.92 | 0.00 | 0.00 | 0.00 |
August | 728.99 | 192.97 | 536.02 | 1476.91 | 217.40 | 0.00 | 0.00 | 0.00 |
September | 1137.86 | 591.16 | 546.71 | 2091.95 | 429.46 | 0.00 | 0.00 | 0.00 |
October | 1546.02 | 1045.21 | 500.81 | 2432.92 | 678.82 | 0.00 | 0.00 | 0.00 |
November | 1860.49 | 1418.40 | 442.10 | 2606.61 | 1083.06 | 0.00 | 0.00 | 0.00 |
December | 1843.82 | 1384.05 | 459.77 | 2426.23 | 1332.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1218.05 | 703.86 | 514.19 | 1888.14 | 703.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 561.00 | 35.60 | 436.36 | 1146.46 | 155.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1860.49 | 1418.40 | 576.81 | 2606.61 | 1332.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 494.28 | 278.36 | 215.92 | 544.98 | 869.29 | 0.00 | 0.00 | 0.00 |
February | 557.74 | 296.45 | 261.29 | 656.15 | 792.12 | 0.00 | 0.00 | 0.00 |
March | 760.04 | 407.36 | 352.69 | 982.99 | 682.00 | 0.00 | 0.00 | 0.00 |
April | 873.61 | 471.85 | 401.76 | 1310.30 | 422.44 | 0.00 | 0.00 | 0.00 |
May | 940.96 | 503.45 | 437.50 | 1569.70 | 262.62 | 0.00 | 0.00 | 0.00 |
June | 915.95 | 491.97 | 423.99 | 1716.47 | 138.49 | 0.00 | 0.00 | 0.00 |
July | 812.84 | 403.92 | 408.93 | 1528.45 | 111.30 | 0.00 | 0.00 | 0.00 |
August | 787.20 | 401.18 | 386.01 | 1424.22 | 149.67 | 0.00 | 0.00 | 0.00 |
September | 805.03 | 448.48 | 356.55 | 1380.39 | 293.64 | 0.00 | 0.00 | 0.00 |
October | 693.00 | 404.46 | 288.54 | 1034.80 | 464.31 | 0.00 | 0.00 | 0.00 |
November | 581.67 | 354.17 | 227.50 | 719.40 | 765.85 | 0.00 | 0.00 | 0.00 |
December | 468.74 | 254.63 | 214.11 | 490.47 | 948.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.86 | 393.29 | 331.57 | 1115.11 | 490.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 468.74 | 254.63 | 214.11 | 490.47 | 111.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 940.96 | 503.45 | 437.50 | 1716.47 | 948.65 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.704835E+09 | 0.00 | 0.704835E+09 | 0.192946E+09 | 0.330826E+10 |
February | 0.777386E+09 | 0.00 | 0.777386E+09 | 0.393340E+09 | 0.271086E+10 |
March | 0.112635E+10 | 0.00 | 0.112635E+10 | 0.828904E+09 | 0.257725E+10 |
April | 0.125854E+10 | 9915510.00 | 0.124863E+10 | 0.146275E+10 | 0.148997E+10 |
May | 0.154244E+10 | 0.111540E+09 | 0.143090E+10 | 0.248605E+10 | 0.917596E+09 |
June | 0.158721E+10 | 0.195404E+09 | 0.139181E+10 | 0.331623E+10 | 0.483384E+09 |
July | 0.151579E+10 | 0.147550E+09 | 0.136824E+10 | 0.314591E+10 | 0.400761E+09 |
August | 0.127814E+10 | 26134601.93 | 0.125200E+10 | 0.245391E+10 | 0.535684E+09 |
September | 0.107931E+10 | 430684.71 | 0.107888E+10 | 0.180941E+10 | 0.104397E+10 |
October | 0.925999E+09 | 0.00 | 0.925999E+09 | 0.100319E+10 | 0.170934E+10 |
November | 0.723440E+09 | 0.00 | 0.723440E+09 | 0.294089E+09 | 0.278041E+10 |
December | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.140233E+09 | 0.364094E+10 |
Annual Sum or Average | 0.132188E+11 | 0.490975E+09 | 0.127278E+11 | 0.175270E+11 | 0.215984E+11 |
Minimum of Months | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.140233E+09 | 0.400761E+09 |
Maximum of Months | 0.158721E+10 | 0.195404E+09 | 0.143090E+10 | 0.331623E+10 | 0.364094E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125678E+10 | 0.681755E+09 | 0.575023E+09 | 0.127611E+10 | 0.204271E+10 |
February | 0.151873E+10 | 0.865663E+09 | 0.653065E+09 | 0.175961E+10 | 0.167177E+10 |
March | 0.207604E+10 | 0.114383E+10 | 0.932211E+09 | 0.259398E+10 | 0.160124E+10 |
April | 0.242083E+10 | 0.134302E+10 | 0.107781E+10 | 0.354081E+10 | 0.952002E+09 |
May | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.422379E+10 | 0.612909E+09 |
June | 0.249957E+10 | 0.139056E+10 | 0.110902E+10 | 0.459493E+10 | 0.316284E+09 |
July | 0.231629E+10 | 0.121091E+10 | 0.110538E+10 | 0.427048E+10 | 0.266595E+09 |
August | 0.220407E+10 | 0.112802E+10 | 0.107605E+10 | 0.392522E+10 | 0.355074E+09 |
September | 0.211320E+10 | 0.120573E+10 | 0.907468E+09 | 0.352497E+10 | 0.659954E+09 |
October | 0.167936E+10 | 0.906330E+09 | 0.773027E+09 | 0.238869E+10 | 0.109317E+10 |
November | 0.145683E+10 | 0.848120E+09 | 0.608714E+09 | 0.165884E+10 | 0.171877E+10 |
December | 0.125570E+10 | 0.665296E+09 | 0.590403E+09 | 0.121585E+10 | 0.223121E+10 |
Annual Sum or Average | 0.233788E+11 | 0.127921E+11 | 0.105867E+11 | 0.349733E+11 | 0.135217E+11 |
Minimum of Months | 0.125570E+10 | 0.665296E+09 | 0.575023E+09 | 0.121585E+10 | 0.266595E+09 |
Maximum of Months | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.459493E+10 | 0.223121E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.482167E+10 | 0.365291E+10 | 0.116875E+10 | 0.652063E+10 | 0.307904E+10 |
February | 0.403980E+10 | 0.284799E+10 | 0.119181E+10 | 0.555058E+10 | 0.254281E+10 |
March | 0.363495E+10 | 0.209589E+10 | 0.153905E+10 | 0.513933E+10 | 0.253175E+10 |
April | 0.238498E+10 | 0.889894E+09 | 0.149509E+10 | 0.378455E+10 | 0.155741E+10 |
May | 0.174163E+10 | 0.243769E+09 | 0.149786E+10 | 0.305810E+10 | 0.976743E+09 |
June | 0.145412E+10 | 92263465.73 | 0.136185E+10 | 0.313389E+10 | 0.491917E+09 |
July | 0.153172E+10 | 0.141992E+09 | 0.138973E+10 | 0.327207E+10 | 0.413356E+09 |
August | 0.195252E+10 | 0.516841E+09 | 0.143568E+10 | 0.393364E+10 | 0.564412E+09 |
September | 0.294934E+10 | 0.153228E+10 | 0.141706E+10 | 0.541081E+10 | 0.106992E+10 |
October | 0.414086E+10 | 0.279949E+10 | 0.134137E+10 | 0.653310E+10 | 0.171443E+10 |
November | 0.482240E+10 | 0.367648E+10 | 0.114592E+10 | 0.681398E+10 | 0.260527E+10 |
December | 0.493849E+10 | 0.370705E+10 | 0.123144E+10 | 0.657525E+10 | 0.330921E+10 |
Annual Sum or Average | 0.384125E+11 | 0.221969E+11 | 0.162156E+11 | 0.597259E+11 | 0.208563E+11 |
Minimum of Months | 0.145412E+10 | 92263465.73 | 0.114592E+10 | 0.305810E+10 | 0.413356E+09 |
Maximum of Months | 0.493849E+10 | 0.370705E+10 | 0.153905E+10 | 0.681398E+10 | 0.330921E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132388E+10 | 0.745569E+09 | 0.578309E+09 | 0.148587E+10 | 0.215455E+10 |
February | 0.134929E+10 | 0.717176E+09 | 0.632116E+09 | 0.160950E+10 | 0.178468E+10 |
March | 0.203570E+10 | 0.109106E+10 | 0.944638E+09 | 0.265420E+10 | 0.171646E+10 |
April | 0.226439E+10 | 0.122304E+10 | 0.104136E+10 | 0.340060E+10 | 0.104154E+10 |
May | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.419438E+10 | 0.678067E+09 |
June | 0.237414E+10 | 0.127517E+10 | 0.109897E+10 | 0.443032E+10 | 0.354798E+09 |
July | 0.217712E+10 | 0.108185E+10 | 0.109527E+10 | 0.407307E+10 | 0.294977E+09 |
August | 0.210842E+10 | 0.107453E+10 | 0.103389E+10 | 0.380077E+10 | 0.388754E+09 |
September | 0.208664E+10 | 0.116247E+10 | 0.924172E+09 | 0.357407E+10 | 0.731003E+09 |
October | 0.185613E+10 | 0.108329E+10 | 0.772833E+09 | 0.278810E+10 | 0.116385E+10 |
November | 0.150769E+10 | 0.918021E+09 | 0.589669E+09 | 0.189394E+10 | 0.182543E+10 |
December | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.134506E+10 | 0.234879E+10 |
Annual Sum or Average | 0.228591E+11 | 0.124026E+11 | 0.104565E+11 | 0.352499E+11 | 0.144829E+11 |
Minimum of Months | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.134506E+10 | 0.294977E+09 |
Maximum of Months | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.443032E+10 | 0.234879E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234934E+09 | 0.00 | 0.234934E+09 | 56948740.28 | 0.118214E+10 |
February | 0.259117E+09 | 0.00 | 0.259117E+09 | 0.134221E+09 | 0.928912E+09 |
March | 0.375432E+09 | 0.00 | 0.375432E+09 | 0.297123E+09 | 0.852903E+09 |
April | 0.419495E+09 | 3305013.62 | 0.416190E+09 | 0.515273E+09 | 0.478375E+09 |
May | 0.514121E+09 | 37178117.66 | 0.476943E+09 | 0.857498E+09 | 0.290214E+09 |
June | 0.529045E+09 | 65131603.43 | 0.463913E+09 | 0.113333E+10 | 0.147151E+09 |
July | 0.505238E+09 | 49181063.32 | 0.456057E+09 | 0.107042E+10 | 0.126496E+09 |
August | 0.426026E+09 | 8711121.82 | 0.417315E+09 | 0.826366E+09 | 0.182228E+09 |
September | 0.359754E+09 | 143554.78 | 0.359610E+09 | 0.602170E+09 | 0.369505E+09 |
October | 0.308652E+09 | 0.00 | 0.308652E+09 | 0.323090E+09 | 0.625650E+09 |
November | 0.241135E+09 | 0.00 | 0.241135E+09 | 82312920.74 | 0.103822E+10 |
December | 0.233114E+09 | 0.00 | 0.233114E+09 | 34521148.81 | 0.133606E+10 |
Annual Sum or Average | 0.440606E+10 | 0.163650E+09 | 0.424241E+10 | 0.593327E+10 | 0.755785E+10 |
Minimum of Months | 0.233114E+09 | 0.00 | 0.233114E+09 | 34521148.81 | 0.126496E+09 |
Maximum of Months | 0.529045E+09 | 65131603.43 | 0.476943E+09 | 0.113333E+10 | 0.133606E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234949E+09 | 0.00 | 0.234949E+09 | 56952339.34 | 0.118221E+10 |
February | 0.259133E+09 | 0.00 | 0.259133E+09 | 0.134230E+09 | 0.928971E+09 |
March | 0.375456E+09 | 0.00 | 0.375456E+09 | 0.297142E+09 | 0.852957E+09 |
April | 0.419522E+09 | 3305222.50 | 0.416216E+09 | 0.515306E+09 | 0.478406E+09 |
May | 0.514153E+09 | 37180467.25 | 0.476973E+09 | 0.857552E+09 | 0.290233E+09 |
June | 0.529078E+09 | 65135719.64 | 0.463943E+09 | 0.113340E+10 | 0.147161E+09 |
July | 0.505270E+09 | 49184171.48 | 0.456086E+09 | 0.107049E+10 | 0.126504E+09 |
August | 0.426053E+09 | 8711672.35 | 0.417341E+09 | 0.826418E+09 | 0.182239E+09 |
September | 0.359777E+09 | 143563.85 | 0.359633E+09 | 0.602208E+09 | 0.369529E+09 |
October | 0.308671E+09 | 0.00 | 0.308671E+09 | 0.323110E+09 | 0.625689E+09 |
November | 0.241150E+09 | 0.00 | 0.241150E+09 | 82318122.78 | 0.103829E+10 |
December | 0.233129E+09 | 0.00 | 0.233129E+09 | 34523330.49 | 0.133614E+10 |
Annual Sum or Average | 0.440634E+10 | 0.163661E+09 | 0.424268E+10 | 0.593365E+10 | 0.755833E+10 |
Minimum of Months | 0.233129E+09 | 0.00 | 0.233129E+09 | 34523330.49 | 0.126504E+09 |
Maximum of Months | 0.529078E+09 | 65135719.64 | 0.476973E+09 | 0.113340E+10 | 0.133614E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234949E+09 | 0.00 | 0.234949E+09 | 56952339.34 | 0.118221E+10 |
February | 0.259133E+09 | 0.00 | 0.259133E+09 | 0.134230E+09 | 0.928971E+09 |
March | 0.375456E+09 | 0.00 | 0.375456E+09 | 0.297142E+09 | 0.852957E+09 |
April | 0.419522E+09 | 3305222.50 | 0.416216E+09 | 0.515306E+09 | 0.478406E+09 |
May | 0.514153E+09 | 37180467.25 | 0.476973E+09 | 0.857552E+09 | 0.290233E+09 |
June | 0.529078E+09 | 65135719.64 | 0.463943E+09 | 0.113340E+10 | 0.147161E+09 |
July | 0.505270E+09 | 49184171.48 | 0.456086E+09 | 0.107049E+10 | 0.126504E+09 |
August | 0.426053E+09 | 8711672.35 | 0.417341E+09 | 0.826418E+09 | 0.182239E+09 |
September | 0.359777E+09 | 143563.85 | 0.359633E+09 | 0.602208E+09 | 0.369529E+09 |
October | 0.308671E+09 | 0.00 | 0.308671E+09 | 0.323110E+09 | 0.625689E+09 |
November | 0.241150E+09 | 0.00 | 0.241150E+09 | 82318122.78 | 0.103829E+10 |
December | 0.233129E+09 | 0.00 | 0.233129E+09 | 34523330.49 | 0.133614E+10 |
Annual Sum or Average | 0.440634E+10 | 0.163661E+09 | 0.424268E+10 | 0.593365E+10 | 0.755833E+10 |
Minimum of Months | 0.233129E+09 | 0.00 | 0.233129E+09 | 34523330.49 | 0.126504E+09 |
Maximum of Months | 0.529078E+09 | 65135719.64 | 0.476973E+09 | 0.113340E+10 | 0.133614E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120897E+10 | 0.655818E+09 | 0.553149E+09 | 0.120049E+10 | 0.214637E+10 |
February | 0.146095E+10 | 0.832729E+09 | 0.628222E+09 | 0.169115E+10 | 0.169803E+10 |
March | 0.199706E+10 | 0.110031E+10 | 0.896750E+09 | 0.252902E+10 | 0.157593E+10 |
April | 0.232873E+10 | 0.129192E+10 | 0.103681E+10 | 0.345249E+10 | 0.925723E+09 |
May | 0.248323E+10 | 0.134954E+10 | 0.113369E+10 | 0.411626E+10 | 0.589010E+09 |
June | 0.240448E+10 | 0.133765E+10 | 0.106683E+10 | 0.447094E+10 | 0.295929E+09 |
July | 0.222817E+10 | 0.116484E+10 | 0.106333E+10 | 0.414501E+10 | 0.260005E+09 |
August | 0.212023E+10 | 0.108511E+10 | 0.103512E+10 | 0.379235E+10 | 0.366474E+09 |
September | 0.203281E+10 | 0.115986E+10 | 0.872948E+09 | 0.339246E+10 | 0.693506E+09 |
October | 0.161547E+10 | 0.871849E+09 | 0.743621E+09 | 0.227960E+10 | 0.117416E+10 |
November | 0.140141E+10 | 0.815853E+09 | 0.585558E+09 | 0.154573E+10 | 0.187994E+10 |
December | 0.120793E+10 | 0.639985E+09 | 0.567944E+09 | 0.111601E+10 | 0.239926E+10 |
Annual Sum or Average | 0.224894E+11 | 0.123055E+11 | 0.101840E+11 | 0.337315E+11 | 0.140043E+11 |
Minimum of Months | 0.120793E+10 | 0.639985E+09 | 0.553149E+09 | 0.111601E+10 | 0.260005E+09 |
Maximum of Months | 0.248323E+10 | 0.134954E+10 | 0.113369E+10 | 0.447094E+10 | 0.239926E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47801471.59 | 25930449.85 | 21871021.73 | 47466429.02 | 84865549.43 |
February | 57764691.50 | 32925360.09 | 24839331.41 | 66866588.42 | 67138577.87 |
March | 78961971.89 | 43505299.87 | 35456672.03 | 99995293.67 | 62310660.75 |
April | 92076062.01 | 51081373.88 | 40994688.13 | 0.136508E+09 | 36602257.52 |
May | 98184733.25 | 53359468.25 | 44825265.00 | 0.162753E+09 | 23288927.50 |
June | 95071012.79 | 52889535.46 | 42181477.34 | 0.176777E+09 | 11700775.52 |
July | 88099906.73 | 46056860.12 | 42043046.61 | 0.163890E+09 | 10280372.21 |
August | 83831823.54 | 42904122.79 | 40927700.75 | 0.149946E+09 | 14490039.31 |
September | 80375369.77 | 45859786.93 | 34515582.84 | 0.134135E+09 | 27420606.02 |
October | 63874206.72 | 34472109.83 | 29402096.89 | 90133341.06 | 46425285.63 |
November | 55410538.44 | 32258088.28 | 23152450.16 | 61116665.97 | 74331084.18 |
December | 47760413.06 | 25304415.41 | 22455997.65 | 44125839.05 | 94864667.30 |
Annual Sum or Average | 0.889212E+09 | 0.486547E+09 | 0.402665E+09 | 0.133371E+10 | 0.553719E+09 |
Minimum of Months | 47760413.06 | 25304415.41 | 21871021.73 | 44125839.05 | 10280372.21 |
Maximum of Months | 98184733.25 | 53359468.25 | 44825265.00 | 0.176777E+09 | 94864667.30 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160727E+10 | 0.121768E+10 | 0.389596E+09 | 0.218528E+10 | 0.113227E+10 |
February | 0.134664E+10 | 0.949361E+09 | 0.397280E+09 | 0.187233E+10 | 0.902229E+09 |
March | 0.121169E+10 | 0.698654E+09 | 0.513031E+09 | 0.175365E+10 | 0.858123E+09 |
April | 0.795018E+09 | 0.296641E+09 | 0.498376E+09 | 0.129531E+10 | 0.511054E+09 |
May | 0.580558E+09 | 81259067.57 | 0.499299E+09 | 0.105042E+10 | 0.311780E+09 |
June | 0.484718E+09 | 30755494.51 | 0.453962E+09 | 0.106581E+10 | 0.150876E+09 |
July | 0.510587E+09 | 47332300.02 | 0.463255E+09 | 0.110676E+10 | 0.132922E+09 |
August | 0.650858E+09 | 0.172286E+09 | 0.478572E+09 | 0.131683E+10 | 0.197335E+09 |
September | 0.983144E+09 | 0.510777E+09 | 0.472366E+09 | 0.180521E+10 | 0.390138E+09 |
October | 0.138033E+10 | 0.933195E+09 | 0.447135E+09 | 0.217660E+10 | 0.638542E+09 |
November | 0.160752E+10 | 0.122553E+10 | 0.381983E+09 | 0.226335E+10 | 0.985387E+09 |
December | 0.164621E+10 | 0.123572E+10 | 0.410491E+09 | 0.218863E+10 | 0.123254E+10 |
Annual Sum or Average | 0.128045E+11 | 0.739920E+10 | 0.540535E+10 | 0.200802E+11 | 0.744320E+10 |
Minimum of Months | 0.484718E+09 | 30755494.51 | 0.381983E+09 | 0.105042E+10 | 0.132922E+09 |
Maximum of Months | 0.164621E+10 | 0.123572E+10 | 0.513031E+09 | 0.226335E+10 | 0.123254E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160727E+10 | 0.121768E+10 | 0.389596E+09 | 0.218528E+10 | 0.113227E+10 |
February | 0.134664E+10 | 0.949361E+09 | 0.397280E+09 | 0.187233E+10 | 0.902229E+09 |
March | 0.121169E+10 | 0.698654E+09 | 0.513031E+09 | 0.175365E+10 | 0.858123E+09 |
April | 0.795018E+09 | 0.296641E+09 | 0.498376E+09 | 0.129531E+10 | 0.511054E+09 |
May | 0.580558E+09 | 81259067.57 | 0.499299E+09 | 0.105042E+10 | 0.311780E+09 |
June | 0.484718E+09 | 30755494.51 | 0.453962E+09 | 0.106581E+10 | 0.150876E+09 |
July | 0.510587E+09 | 47332300.02 | 0.463255E+09 | 0.110676E+10 | 0.132922E+09 |
August | 0.650858E+09 | 0.172286E+09 | 0.478572E+09 | 0.131683E+10 | 0.197335E+09 |
September | 0.983144E+09 | 0.510777E+09 | 0.472366E+09 | 0.180521E+10 | 0.390138E+09 |
October | 0.138033E+10 | 0.933195E+09 | 0.447135E+09 | 0.217660E+10 | 0.638542E+09 |
November | 0.160752E+10 | 0.122553E+10 | 0.381983E+09 | 0.226335E+10 | 0.985387E+09 |
December | 0.164621E+10 | 0.123572E+10 | 0.410491E+09 | 0.218863E+10 | 0.123254E+10 |
Annual Sum or Average | 0.128045E+11 | 0.739920E+10 | 0.540535E+10 | 0.200802E+11 | 0.744320E+10 |
Minimum of Months | 0.484718E+09 | 30755494.51 | 0.381983E+09 | 0.105042E+10 | 0.132922E+09 |
Maximum of Months | 0.164621E+10 | 0.123572E+10 | 0.513031E+09 | 0.226335E+10 | 0.123254E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160717E+10 | 0.121760E+10 | 0.389571E+09 | 0.218514E+10 | 0.113220E+10 |
February | 0.134656E+10 | 0.949301E+09 | 0.397255E+09 | 0.187221E+10 | 0.902172E+09 |
March | 0.121161E+10 | 0.698610E+09 | 0.512999E+09 | 0.175354E+10 | 0.858069E+09 |
April | 0.794967E+09 | 0.296622E+09 | 0.498345E+09 | 0.129523E+10 | 0.511021E+09 |
May | 0.580521E+09 | 81253932.45 | 0.499267E+09 | 0.105035E+10 | 0.311760E+09 |
June | 0.484687E+09 | 30753550.94 | 0.453934E+09 | 0.106574E+10 | 0.150867E+09 |
July | 0.510555E+09 | 47329308.88 | 0.463226E+09 | 0.110669E+10 | 0.132913E+09 |
August | 0.650817E+09 | 0.172275E+09 | 0.478542E+09 | 0.131675E+10 | 0.197323E+09 |
September | 0.983082E+09 | 0.510745E+09 | 0.472337E+09 | 0.180509E+10 | 0.390114E+09 |
October | 0.138024E+10 | 0.933136E+09 | 0.447107E+09 | 0.217646E+10 | 0.638501E+09 |
November | 0.160742E+10 | 0.122546E+10 | 0.381958E+09 | 0.226321E+10 | 0.985325E+09 |
December | 0.164611E+10 | 0.123565E+10 | 0.410465E+09 | 0.218849E+10 | 0.123246E+10 |
Annual Sum or Average | 0.128037E+11 | 0.739873E+10 | 0.540500E+10 | 0.200789E+11 | 0.744273E+10 |
Minimum of Months | 0.484687E+09 | 30753550.94 | 0.381958E+09 | 0.105035E+10 | 0.132913E+09 |
Maximum of Months | 0.164611E+10 | 0.123565E+10 | 0.512999E+09 | 0.226321E+10 | 0.123246E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.127351E+10 | 0.717204E+09 | 0.556310E+09 | 0.142000E+10 | 0.226294E+10 |
February | 0.129796E+10 | 0.689892E+09 | 0.608071E+09 | 0.156133E+10 | 0.180804E+10 |
March | 0.195826E+10 | 0.104955E+10 | 0.908704E+09 | 0.259617E+10 | 0.169618E+10 |
April | 0.217825E+10 | 0.117651E+10 | 0.100174E+10 | 0.331463E+10 | 0.101710E+10 |
May | 0.242439E+10 | 0.129715E+10 | 0.112724E+10 | 0.408467E+10 | 0.656250E+09 |
June | 0.228383E+10 | 0.122666E+10 | 0.105717E+10 | 0.430613E+10 | 0.332743E+09 |
July | 0.209429E+10 | 0.104069E+10 | 0.105360E+10 | 0.394894E+10 | 0.288184E+09 |
August | 0.202822E+10 | 0.103365E+10 | 0.994564E+09 | 0.366962E+10 | 0.403331E+09 |
September | 0.200726E+10 | 0.111824E+10 | 0.889017E+09 | 0.343803E+10 | 0.770416E+09 |
October | 0.178552E+10 | 0.104208E+10 | 0.743435E+09 | 0.265824E+10 | 0.125881E+10 |
November | 0.145033E+10 | 0.883095E+09 | 0.567238E+09 | 0.178621E+10 | 0.200411E+10 |
December | 0.120771E+10 | 0.656067E+09 | 0.551648E+09 | 0.126524E+10 | 0.251698E+10 |
Annual Sum or Average | 0.219895E+11 | 0.119308E+11 | 0.100587E+11 | 0.340492E+11 | 0.150151E+11 |
Minimum of Months | 0.120771E+10 | 0.656067E+09 | 0.551648E+09 | 0.126524E+10 | 0.288184E+09 |
Maximum of Months | 0.242439E+10 | 0.129715E+10 | 0.112724E+10 | 0.430613E+10 | 0.251698E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 50353474.72 | 28357519.06 | 21995955.65 | 56145448.66 | 89474776.82 |
February | 51320122.74 | 27277605.28 | 24042517.46 | 61733448.09 | 71488414.26 |
March | 77427552.34 | 41498280.99 | 35929271.35 | 0.102650E+09 | 67065369.21 |
April | 86125788.90 | 46517830.12 | 39607958.78 | 0.131057E+09 | 40215179.46 |
May | 95857884.47 | 51288026.21 | 44569858.26 | 0.161504E+09 | 25947485.40 |
June | 90300239.98 | 48500875.85 | 41799364.12 | 0.170260E+09 | 13156325.38 |
July | 82806258.38 | 41147827.36 | 41658431.02 | 0.156137E+09 | 11394519.79 |
August | 80193612.79 | 40869511.51 | 39324101.27 | 0.145093E+09 | 15947330.02 |
September | 79364893.30 | 44214037.10 | 35150856.20 | 0.135936E+09 | 30461538.61 |
October | 70597487.04 | 41202815.88 | 29394671.17 | 0.105104E+09 | 49772016.48 |
November | 57344702.50 | 34916661.65 | 22428040.86 | 70624999.29 | 79240540.21 |
December | 47751822.04 | 25940203.11 | 21811618.93 | 50026273.55 | 99519107.05 |
Annual Sum or Average | 0.869444E+09 | 0.471731E+09 | 0.397713E+09 | 0.134627E+10 | 0.593683E+09 |
Minimum of Months | 47751822.04 | 25940203.11 | 21811618.93 | 50026273.55 | 11394519.79 |
Maximum of Months | 95857884.47 | 51288026.21 | 44569858.26 | 0.170260E+09 | 99519107.05 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.704835E+09 | 0.00 | 0.704835E+09 | 0.158406E+09 | 0.358841E+10 |
February | 0.777386E+09 | 0.00 | 0.777386E+09 | 0.357797E+09 | 0.292099E+10 |
March | 0.112635E+10 | 0.00 | 0.112635E+10 | 0.790415E+09 | 0.275094E+10 |
April | 0.125854E+10 | 9915510.00 | 0.124863E+10 | 0.145318E+10 | 0.157038E+10 |
May | 0.154244E+10 | 0.111540E+09 | 0.143090E+10 | 0.249486E+10 | 0.947123E+09 |
June | 0.158721E+10 | 0.195404E+09 | 0.139181E+10 | 0.334376E+10 | 0.487114E+09 |
July | 0.151579E+10 | 0.147550E+09 | 0.136824E+10 | 0.317919E+10 | 0.402211E+09 |
August | 0.127814E+10 | 26134601.93 | 0.125200E+10 | 0.247346E+10 | 0.551248E+09 |
September | 0.107931E+10 | 430684.71 | 0.107888E+10 | 0.181416E+10 | 0.108963E+10 |
October | 0.925999E+09 | 0.00 | 0.925999E+09 | 0.976767E+09 | 0.183537E+10 |
November | 0.723440E+09 | 0.00 | 0.723440E+09 | 0.253469E+09 | 0.304600E+10 |
December | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.106675E+09 | 0.395438E+10 |
Annual Sum or Average | 0.132188E+11 | 0.490975E+09 | 0.127278E+11 | 0.174021E+11 | 0.231438E+11 |
Minimum of Months | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.106675E+09 | 0.402211E+09 |
Maximum of Months | 0.158721E+10 | 0.195404E+09 | 0.143090E+10 | 0.334376E+10 | 0.395438E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125678E+10 | 0.681755E+09 | 0.575023E+09 | 0.123239E+10 | 0.220677E+10 |
February | 0.151873E+10 | 0.865663E+09 | 0.653065E+09 | 0.172202E+10 | 0.179015E+10 |
March | 0.207604E+10 | 0.114383E+10 | 0.932211E+09 | 0.256502E+10 | 0.169244E+10 |
April | 0.242083E+10 | 0.134302E+10 | 0.107781E+10 | 0.353900E+10 | 0.991212E+09 |
May | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.423682E+10 | 0.630917E+09 |
June | 0.249957E+10 | 0.139056E+10 | 0.110902E+10 | 0.461812E+10 | 0.319179E+09 |
July | 0.231629E+10 | 0.121091E+10 | 0.110538E+10 | 0.429587E+10 | 0.268209E+09 |
August | 0.220407E+10 | 0.112802E+10 | 0.107605E+10 | 0.394232E+10 | 0.364749E+09 |
September | 0.211320E+10 | 0.120573E+10 | 0.907468E+09 | 0.353144E+10 | 0.683630E+09 |
October | 0.167936E+10 | 0.906330E+09 | 0.773027E+09 | 0.237361E+10 | 0.116241E+10 |
November | 0.145683E+10 | 0.848120E+09 | 0.608714E+09 | 0.161502E+10 | 0.186143E+10 |
December | 0.125570E+10 | 0.665296E+09 | 0.590403E+09 | 0.116354E+10 | 0.241234E+10 |
Annual Sum or Average | 0.233788E+11 | 0.127921E+11 | 0.105867E+11 | 0.348352E+11 | 0.143834E+11 |
Minimum of Months | 0.125570E+10 | 0.665296E+09 | 0.575023E+09 | 0.116354E+10 | 0.268209E+09 |
Maximum of Months | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.461812E+10 | 0.241234E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.482167E+10 | 0.365291E+10 | 0.116875E+10 | 0.646585E+10 | 0.331680E+10 |
February | 0.403980E+10 | 0.284799E+10 | 0.119181E+10 | 0.550723E+10 | 0.272165E+10 |
March | 0.363495E+10 | 0.209589E+10 | 0.153905E+10 | 0.510622E+10 | 0.268271E+10 |
April | 0.238498E+10 | 0.889894E+09 | 0.149509E+10 | 0.378279E+10 | 0.163581E+10 |
May | 0.174163E+10 | 0.243769E+09 | 0.149786E+10 | 0.307068E+10 | 0.101429E+10 |
June | 0.145412E+10 | 92263465.73 | 0.136185E+10 | 0.315929E+10 | 0.498848E+09 |
July | 0.153172E+10 | 0.141992E+09 | 0.138973E+10 | 0.330303E+10 | 0.417612E+09 |
August | 0.195252E+10 | 0.516841E+09 | 0.143568E+10 | 0.395576E+10 | 0.582277E+09 |
September | 0.294934E+10 | 0.153228E+10 | 0.141706E+10 | 0.542234E+10 | 0.111316E+10 |
October | 0.414086E+10 | 0.279949E+10 | 0.134137E+10 | 0.651634E+10 | 0.181815E+10 |
November | 0.482240E+10 | 0.367648E+10 | 0.114592E+10 | 0.675633E+10 | 0.280730E+10 |
December | 0.493849E+10 | 0.370705E+10 | 0.123144E+10 | 0.649843E+10 | 0.356773E+10 |
Annual Sum or Average | 0.384125E+11 | 0.221969E+11 | 0.162156E+11 | 0.595443E+11 | 0.221763E+11 |
Minimum of Months | 0.145412E+10 | 92263465.73 | 0.114592E+10 | 0.307068E+10 | 0.417612E+09 |
Maximum of Months | 0.493849E+10 | 0.370705E+10 | 0.153905E+10 | 0.675633E+10 | 0.356773E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132388E+10 | 0.745569E+09 | 0.578309E+09 | 0.145967E+10 | 0.232831E+10 |
February | 0.134929E+10 | 0.717176E+09 | 0.632116E+09 | 0.158737E+10 | 0.191631E+10 |
March | 0.203570E+10 | 0.109106E+10 | 0.944638E+09 | 0.263284E+10 | 0.182667E+10 |
April | 0.226439E+10 | 0.122304E+10 | 0.104136E+10 | 0.339629E+10 | 0.109497E+10 |
May | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.420428E+10 | 0.703396E+09 |
June | 0.237414E+10 | 0.127517E+10 | 0.109897E+10 | 0.444910E+10 | 0.358969E+09 |
July | 0.217712E+10 | 0.108185E+10 | 0.109527E+10 | 0.409380E+10 | 0.298107E+09 |
August | 0.210842E+10 | 0.107453E+10 | 0.103389E+10 | 0.381464E+10 | 0.400877E+09 |
September | 0.208664E+10 | 0.116247E+10 | 0.924172E+09 | 0.357798E+10 | 0.761113E+09 |
October | 0.185613E+10 | 0.108329E+10 | 0.772833E+09 | 0.277162E+10 | 0.124360E+10 |
November | 0.150769E+10 | 0.918021E+09 | 0.589669E+09 | 0.186470E+10 | 0.198507E+10 |
December | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.131368E+10 | 0.254086E+10 |
Annual Sum or Average | 0.228591E+11 | 0.124026E+11 | 0.104565E+11 | 0.351660E+11 | 0.154583E+11 |
Minimum of Months | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.131368E+10 | 0.298107E+09 |
Maximum of Months | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.444910E+10 | 0.254086E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 72.04 | 1235.16 | 263.16 | 0.00 | 263.16 | 0.00 | 0.00 |
February | 162.59 | 1120.56 | 321.34 | 0.00 | 321.34 | 0.00 | 0.00 |
March | 309.48 | 962.24 | 420.53 | 0.00 | 420.53 | 0.00 | 0.00 |
April | 564.33 | 574.84 | 485.55 | 3.83 | 481.72 | 0.00 | 0.00 |
May | 928.18 | 342.59 | 575.88 | 41.64 | 534.24 | 0.00 | 0.00 |
June | 1279.41 | 186.49 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
July | 1174.55 | 149.63 | 565.93 | 55.09 | 510.84 | 0.00 | 0.00 |
August | 916.18 | 200.00 | 477.20 | 9.76 | 467.44 | 0.00 | 0.00 |
September | 698.07 | 402.76 | 416.40 | 0.17 | 416.24 | 0.00 | 0.00 |
October | 374.55 | 638.19 | 345.73 | 0.00 | 345.73 | 0.00 | 0.00 |
November | 113.46 | 1072.69 | 279.10 | 0.00 | 279.10 | 0.00 | 0.00 |
December | 52.36 | 1359.37 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Annual Sum or Average | 555.78 | 684.88 | 419.17 | 15.57 | 403.60 | 0.00 | 0.00 |
Minimum of Months | 52.36 | 149.63 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Maximum of Months | 1279.41 | 1359.37 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 476.45 | 762.66 | 469.23 | 254.54 | 214.69 | 0.00 | 0.00 |
February | 727.35 | 691.04 | 627.78 | 357.83 | 269.95 | 0.00 | 0.00 |
March | 968.48 | 597.83 | 775.10 | 427.06 | 348.05 | 0.00 | 0.00 |
April | 1366.05 | 367.28 | 933.96 | 518.14 | 415.82 | 0.00 | 0.00 |
May | 1576.98 | 228.83 | 963.80 | 523.79 | 440.01 | 0.00 | 0.00 |
June | 1772.74 | 122.02 | 964.34 | 536.48 | 427.86 | 0.00 | 0.00 |
July | 1594.41 | 99.54 | 864.80 | 452.10 | 412.70 | 0.00 | 0.00 |
August | 1465.51 | 132.57 | 822.91 | 421.16 | 401.75 | 0.00 | 0.00 |
September | 1359.94 | 254.61 | 815.28 | 465.17 | 350.10 | 0.00 | 0.00 |
October | 891.84 | 408.14 | 627.00 | 338.38 | 288.62 | 0.00 | 0.00 |
November | 639.99 | 663.11 | 562.05 | 327.21 | 234.84 | 0.00 | 0.00 |
December | 453.95 | 833.04 | 468.82 | 248.39 | 220.43 | 0.00 | 0.00 |
Annual Sum or Average | 1109.00 | 428.77 | 741.34 | 405.64 | 335.70 | 0.00 | 0.00 |
Minimum of Months | 453.95 | 99.54 | 468.82 | 248.39 | 214.69 | 0.00 | 0.00 |
Maximum of Months | 1772.74 | 833.04 | 964.34 | 536.48 | 440.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2434.53 | 1149.58 | 1800.20 | 1363.84 | 436.36 | 0.00 | 0.00 |
February | 2294.39 | 1051.09 | 1669.89 | 1177.25 | 492.65 | 0.00 | 0.00 |
March | 1918.81 | 945.25 | 1357.13 | 782.52 | 574.62 | 0.00 | 0.00 |
April | 1460.09 | 600.85 | 920.13 | 343.32 | 576.81 | 0.00 | 0.00 |
May | 1141.76 | 364.67 | 650.25 | 91.01 | 559.24 | 0.00 | 0.00 |
June | 1209.06 | 189.78 | 561.00 | 35.60 | 525.41 | 0.00 | 0.00 |
July | 1221.65 | 154.33 | 571.88 | 53.01 | 518.87 | 0.00 | 0.00 |
August | 1468.65 | 210.73 | 728.99 | 192.97 | 536.02 | 0.00 | 0.00 |
September | 2087.50 | 412.78 | 1137.86 | 591.16 | 546.71 | 0.00 | 0.00 |
October | 2439.18 | 640.09 | 1546.02 | 1045.21 | 500.81 | 0.00 | 0.00 |
November | 2628.85 | 1005.12 | 1860.49 | 1418.40 | 442.10 | 0.00 | 0.00 |
December | 2454.92 | 1235.52 | 1843.82 | 1384.05 | 459.77 | 0.00 | 0.00 |
Annual Sum or Average | 1893.90 | 661.35 | 1218.05 | 703.86 | 514.19 | 0.00 | 0.00 |
Minimum of Months | 1141.76 | 154.33 | 561.00 | 35.60 | 436.36 | 0.00 | 0.00 |
Maximum of Months | 2628.85 | 1235.52 | 1860.49 | 1418.40 | 576.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 554.76 | 804.42 | 494.28 | 278.36 | 215.92 | 0.00 | 0.00 |
February | 665.30 | 737.72 | 557.74 | 296.45 | 261.29 | 0.00 | 0.00 |
March | 990.96 | 640.85 | 760.04 | 407.36 | 352.69 | 0.00 | 0.00 |
April | 1311.96 | 401.83 | 873.61 | 471.85 | 401.76 | 0.00 | 0.00 |
May | 1566.00 | 253.16 | 940.96 | 503.45 | 437.50 | 0.00 | 0.00 |
June | 1709.23 | 136.88 | 915.95 | 491.97 | 423.99 | 0.00 | 0.00 |
July | 1520.71 | 110.13 | 812.84 | 403.92 | 408.93 | 0.00 | 0.00 |
August | 1419.04 | 145.14 | 787.20 | 401.18 | 386.01 | 0.00 | 0.00 |
September | 1378.89 | 282.02 | 805.03 | 448.48 | 356.55 | 0.00 | 0.00 |
October | 1040.96 | 434.53 | 693.00 | 404.46 | 288.54 | 0.00 | 0.00 |
November | 730.69 | 704.25 | 581.67 | 354.17 | 227.50 | 0.00 | 0.00 |
December | 502.19 | 876.94 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Annual Sum or Average | 1117.77 | 459.25 | 724.86 | 393.29 | 331.57 | 0.00 | 0.00 |
Minimum of Months | 502.19 | 110.13 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Maximum of Months | 1709.23 | 876.94 | 940.96 | 503.45 | 437.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 63.79 | 1324.13 | 263.15 | 0.00 | 263.15 | 0.00 | 0.00 |
February | 166.45 | 1151.97 | 321.34 | 0.00 | 321.34 | 0.00 | 0.00 |
March | 332.81 | 955.35 | 420.53 | 0.00 | 420.53 | 0.00 | 0.00 |
April | 596.41 | 553.70 | 485.55 | 3.83 | 481.72 | 0.00 | 0.00 |
May | 960.50 | 325.07 | 575.88 | 41.64 | 534.23 | 0.00 | 0.00 |
June | 1311.78 | 170.32 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
July | 1199.00 | 141.69 | 565.93 | 55.09 | 510.84 | 0.00 | 0.00 |
August | 925.63 | 204.12 | 477.20 | 9.76 | 467.44 | 0.00 | 0.00 |
September | 696.99 | 427.69 | 416.40 | 0.17 | 416.23 | 0.00 | 0.00 |
October | 361.90 | 700.80 | 345.73 | 0.00 | 345.73 | 0.00 | 0.00 |
November | 95.27 | 1201.70 | 279.10 | 0.00 | 279.10 | 0.00 | 0.00 |
December | 38.67 | 1496.54 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Annual Sum or Average | 564.45 | 719.00 | 419.16 | 15.57 | 403.59 | 0.00 | 0.00 |
Minimum of Months | 38.67 | 141.69 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Maximum of Months | 1311.78 | 1496.54 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 465.93 | 833.05 | 469.22 | 254.54 | 214.69 | 0.00 | 0.00 |
February | 726.69 | 729.65 | 627.78 | 357.83 | 269.95 | 0.00 | 0.00 |
March | 981.56 | 611.65 | 775.10 | 427.05 | 348.05 | 0.00 | 0.00 |
April | 1384.64 | 371.27 | 933.95 | 518.13 | 415.82 | 0.00 | 0.00 |
May | 1597.60 | 228.61 | 963.79 | 523.78 | 440.01 | 0.00 | 0.00 |
June | 1793.10 | 118.68 | 964.33 | 536.47 | 427.86 | 0.00 | 0.00 |
July | 1608.76 | 100.91 | 864.80 | 452.10 | 412.70 | 0.00 | 0.00 |
August | 1471.88 | 142.24 | 822.90 | 421.15 | 401.75 | 0.00 | 0.00 |
September | 1360.57 | 278.14 | 815.27 | 465.17 | 350.10 | 0.00 | 0.00 |
October | 884.76 | 455.71 | 627.00 | 338.38 | 288.61 | 0.00 | 0.00 |
November | 619.92 | 753.96 | 562.05 | 327.20 | 234.84 | 0.00 | 0.00 |
December | 433.14 | 931.20 | 468.82 | 248.39 | 220.43 | 0.00 | 0.00 |
Annual Sum or Average | 1111.91 | 461.63 | 741.33 | 405.63 | 335.70 | 0.00 | 0.00 |
Minimum of Months | 433.14 | 100.91 | 468.82 | 248.39 | 214.69 | 0.00 | 0.00 |
Maximum of Months | 1793.10 | 931.20 | 964.33 | 536.47 | 440.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2447.62 | 1268.20 | 1800.22 | 1363.86 | 436.37 | 0.00 | 0.00 |
February | 2321.79 | 1118.81 | 1669.91 | 1177.26 | 492.65 | 0.00 | 0.00 |
March | 1964.17 | 961.14 | 1357.15 | 782.53 | 574.62 | 0.00 | 0.00 |
April | 1499.17 | 591.48 | 920.14 | 343.33 | 576.81 | 0.00 | 0.00 |
May | 1176.52 | 349.21 | 650.25 | 91.01 | 559.24 | 0.00 | 0.00 |
June | 1233.54 | 174.62 | 561.00 | 35.60 | 525.41 | 0.00 | 0.00 |
July | 1239.63 | 148.88 | 571.88 | 53.01 | 518.87 | 0.00 | 0.00 |
August | 1474.91 | 221.03 | 728.99 | 192.97 | 536.02 | 0.00 | 0.00 |
September | 2089.31 | 451.54 | 1137.87 | 591.17 | 546.71 | 0.00 | 0.00 |
October | 2437.90 | 715.20 | 1546.04 | 1045.22 | 500.81 | 0.00 | 0.00 |
November | 2619.57 | 1140.47 | 1860.51 | 1418.41 | 442.10 | 0.00 | 0.00 |
December | 2451.37 | 1380.51 | 1843.84 | 1384.07 | 459.77 | 0.00 | 0.00 |
Annual Sum or Average | 1910.17 | 708.05 | 1218.06 | 703.87 | 514.20 | 0.00 | 0.00 |
Minimum of Months | 1176.52 | 148.88 | 561.00 | 35.60 | 436.37 | 0.00 | 0.00 |
Maximum of Months | 2619.57 | 1380.51 | 1860.51 | 1418.41 | 576.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 551.13 | 878.29 | 494.28 | 278.36 | 215.91 | 0.00 | 0.00 |
February | 670.91 | 776.92 | 557.74 | 296.45 | 261.29 | 0.00 | 0.00 |
March | 1007.62 | 658.32 | 760.04 | 407.35 | 352.69 | 0.00 | 0.00 |
April | 1329.35 | 407.91 | 873.60 | 471.85 | 401.76 | 0.00 | 0.00 |
May | 1585.34 | 254.70 | 940.95 | 503.45 | 437.50 | 0.00 | 0.00 |
June | 1727.00 | 133.45 | 915.94 | 491.96 | 423.98 | 0.00 | 0.00 |
July | 1532.66 | 111.85 | 812.84 | 403.91 | 408.92 | 0.00 | 0.00 |
August | 1424.25 | 156.54 | 787.19 | 401.18 | 386.01 | 0.00 | 0.00 |
September | 1378.84 | 308.98 | 805.02 | 448.48 | 356.55 | 0.00 | 0.00 |
October | 1031.72 | 488.57 | 692.99 | 404.45 | 288.54 | 0.00 | 0.00 |
November | 716.37 | 803.76 | 581.67 | 354.17 | 227.49 | 0.00 | 0.00 |
December | 491.06 | 976.89 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Annual Sum or Average | 1122.38 | 494.95 | 724.85 | 393.28 | 331.57 | 0.00 | 0.00 |
Minimum of Months | 491.06 | 111.85 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Maximum of Months | 1727.00 | 976.89 | 940.95 | 503.45 | 437.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 59.14 | 1339.76 | 263.16 | 0.00 | 263.16 | 0.00 | 0.00 |
February | 147.90 | 1207.42 | 321.34 | 0.00 | 321.34 | 0.00 | 0.00 |
March | 295.11 | 1027.08 | 420.53 | 0.00 | 420.53 | 0.00 | 0.00 |
April | 560.64 | 605.86 | 485.55 | 3.83 | 481.72 | 0.00 | 0.00 |
May | 931.47 | 353.62 | 575.88 | 41.64 | 534.24 | 0.00 | 0.00 |
June | 1290.03 | 187.93 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
July | 1186.98 | 150.17 | 565.93 | 55.09 | 510.84 | 0.00 | 0.00 |
August | 923.49 | 205.81 | 477.20 | 9.76 | 467.44 | 0.00 | 0.00 |
September | 699.91 | 420.38 | 416.40 | 0.17 | 416.24 | 0.00 | 0.00 |
October | 364.68 | 685.25 | 345.73 | 0.00 | 345.73 | 0.00 | 0.00 |
November | 97.79 | 1175.16 | 279.10 | 0.00 | 279.10 | 0.00 | 0.00 |
December | 39.83 | 1476.40 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Annual Sum or Average | 551.82 | 733.88 | 419.17 | 15.57 | 403.60 | 0.00 | 0.00 |
Minimum of Months | 39.83 | 150.17 | 261.12 | 0.00 | 261.12 | 0.00 | 0.00 |
Maximum of Months | 1290.03 | 1476.40 | 612.35 | 75.39 | 536.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 460.12 | 823.91 | 469.23 | 254.54 | 214.69 | 0.00 | 0.00 |
February | 711.81 | 739.98 | 627.78 | 357.83 | 269.95 | 0.00 | 0.00 |
March | 957.67 | 631.88 | 775.10 | 427.06 | 348.05 | 0.00 | 0.00 |
April | 1365.35 | 382.41 | 933.96 | 518.14 | 415.82 | 0.00 | 0.00 |
May | 1581.85 | 235.56 | 963.80 | 523.79 | 440.01 | 0.00 | 0.00 |
June | 1781.68 | 123.14 | 964.34 | 536.48 | 427.86 | 0.00 | 0.00 |
July | 1603.89 | 100.14 | 864.80 | 452.10 | 412.70 | 0.00 | 0.00 |
August | 1471.89 | 136.18 | 822.91 | 421.16 | 401.75 | 0.00 | 0.00 |
September | 1362.44 | 263.75 | 815.28 | 465.17 | 350.10 | 0.00 | 0.00 |
October | 886.21 | 433.99 | 627.00 | 338.38 | 288.62 | 0.00 | 0.00 |
November | 623.08 | 718.15 | 562.05 | 327.21 | 234.84 | 0.00 | 0.00 |
December | 434.42 | 900.67 | 468.82 | 248.39 | 220.43 | 0.00 | 0.00 |
Annual Sum or Average | 1104.62 | 456.10 | 741.34 | 405.64 | 335.70 | 0.00 | 0.00 |
Minimum of Months | 434.42 | 100.14 | 468.82 | 248.39 | 214.69 | 0.00 | 0.00 |
Maximum of Months | 1781.68 | 900.67 | 964.34 | 536.48 | 440.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2414.07 | 1238.35 | 1800.20 | 1363.84 | 436.36 | 0.00 | 0.00 |
February | 2276.47 | 1125.02 | 1669.89 | 1177.25 | 492.65 | 0.00 | 0.00 |
March | 1906.44 | 1001.61 | 1357.13 | 782.52 | 574.62 | 0.00 | 0.00 |
April | 1459.41 | 631.10 | 920.13 | 343.32 | 576.81 | 0.00 | 0.00 |
May | 1146.46 | 378.69 | 650.25 | 91.01 | 559.24 | 0.00 | 0.00 |
June | 1218.86 | 192.46 | 561.00 | 35.60 | 525.41 | 0.00 | 0.00 |
July | 1233.21 | 155.92 | 571.88 | 53.01 | 518.87 | 0.00 | 0.00 |
August | 1476.91 | 217.40 | 728.99 | 192.97 | 536.02 | 0.00 | 0.00 |
September | 2091.95 | 429.46 | 1137.86 | 591.16 | 546.71 | 0.00 | 0.00 |
October | 2432.92 | 678.82 | 1546.02 | 1045.21 | 500.81 | 0.00 | 0.00 |
November | 2606.61 | 1083.06 | 1860.49 | 1418.40 | 442.10 | 0.00 | 0.00 |
December | 2426.23 | 1332.04 | 1843.82 | 1384.05 | 459.77 | 0.00 | 0.00 |
Annual Sum or Average | 1888.14 | 703.21 | 1218.05 | 703.86 | 514.19 | 0.00 | 0.00 |
Minimum of Months | 1146.46 | 155.92 | 561.00 | 35.60 | 436.36 | 0.00 | 0.00 |
Maximum of Months | 2606.61 | 1332.04 | 1860.49 | 1418.40 | 576.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 544.98 | 869.29 | 494.28 | 278.36 | 215.92 | 0.00 | 0.00 |
February | 656.15 | 792.12 | 557.74 | 296.45 | 261.29 | 0.00 | 0.00 |
March | 982.99 | 682.00 | 760.04 | 407.36 | 352.69 | 0.00 | 0.00 |
April | 1310.30 | 422.44 | 873.61 | 471.85 | 401.76 | 0.00 | 0.00 |
May | 1569.70 | 262.62 | 940.96 | 503.45 | 437.50 | 0.00 | 0.00 |
June | 1716.47 | 138.49 | 915.95 | 491.97 | 423.99 | 0.00 | 0.00 |
July | 1528.45 | 111.30 | 812.84 | 403.92 | 408.93 | 0.00 | 0.00 |
August | 1424.22 | 149.67 | 787.20 | 401.18 | 386.01 | 0.00 | 0.00 |
September | 1380.39 | 293.64 | 805.03 | 448.48 | 356.55 | 0.00 | 0.00 |
October | 1034.80 | 464.31 | 693.00 | 404.46 | 288.54 | 0.00 | 0.00 |
November | 719.40 | 765.85 | 581.67 | 354.17 | 227.50 | 0.00 | 0.00 |
December | 490.47 | 948.65 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Annual Sum or Average | 1115.11 | 490.18 | 724.86 | 393.29 | 331.57 | 0.00 | 0.00 |
Minimum of Months | 490.47 | 111.30 | 468.74 | 254.63 | 214.11 | 0.00 | 0.00 |
Maximum of Months | 1716.47 | 948.65 | 940.96 | 503.45 | 437.50 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.192946E+09 | 0.330826E+10 | 0.704835E+09 | 0.00 | 0.704835E+09 | 0.00 | 0.00 |
February | 0.393340E+09 | 0.271086E+10 | 0.777386E+09 | 0.00 | 0.777386E+09 | 0.00 | 0.00 |
March | 0.828904E+09 | 0.257725E+10 | 0.112635E+10 | 0.00 | 0.112635E+10 | 0.00 | 0.00 |
April | 0.146275E+10 | 0.148997E+10 | 0.125854E+10 | 9915510.00 | 0.124863E+10 | 0.00 | 0.00 |
May | 0.248605E+10 | 0.917596E+09 | 0.154244E+10 | 0.111540E+09 | 0.143090E+10 | 0.00 | 0.00 |
June | 0.331623E+10 | 0.483384E+09 | 0.158721E+10 | 0.195404E+09 | 0.139181E+10 | 0.00 | 0.00 |
July | 0.314591E+10 | 0.400761E+09 | 0.151579E+10 | 0.147550E+09 | 0.136824E+10 | 0.00 | 0.00 |
August | 0.245391E+10 | 0.535684E+09 | 0.127814E+10 | 26134601.93 | 0.125200E+10 | 0.00 | 0.00 |
September | 0.180941E+10 | 0.104397E+10 | 0.107931E+10 | 430684.71 | 0.107888E+10 | 0.00 | 0.00 |
October | 0.100319E+10 | 0.170934E+10 | 0.925999E+09 | 0.00 | 0.925999E+09 | 0.00 | 0.00 |
November | 0.294089E+09 | 0.278041E+10 | 0.723440E+09 | 0.00 | 0.723440E+09 | 0.00 | 0.00 |
December | 0.140233E+09 | 0.364094E+10 | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.175270E+11 | 0.215984E+11 | 0.132188E+11 | 0.490975E+09 | 0.127278E+11 | 0.00 | 0.00 |
Minimum of Months | 0.140233E+09 | 0.400761E+09 | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.00 | 0.00 |
Maximum of Months | 0.331623E+10 | 0.364094E+10 | 0.158721E+10 | 0.195404E+09 | 0.143090E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127611E+10 | 0.204271E+10 | 0.125678E+10 | 0.681755E+09 | 0.575023E+09 | 0.00 | 0.00 |
February | 0.175961E+10 | 0.167177E+10 | 0.151873E+10 | 0.865663E+09 | 0.653065E+09 | 0.00 | 0.00 |
March | 0.259398E+10 | 0.160124E+10 | 0.207604E+10 | 0.114383E+10 | 0.932211E+09 | 0.00 | 0.00 |
April | 0.354081E+10 | 0.952002E+09 | 0.242083E+10 | 0.134302E+10 | 0.107781E+10 | 0.00 | 0.00 |
May | 0.422379E+10 | 0.612909E+09 | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.00 | 0.00 |
June | 0.459493E+10 | 0.316284E+09 | 0.249957E+10 | 0.139056E+10 | 0.110902E+10 | 0.00 | 0.00 |
July | 0.427048E+10 | 0.266595E+09 | 0.231629E+10 | 0.121091E+10 | 0.110538E+10 | 0.00 | 0.00 |
August | 0.392522E+10 | 0.355074E+09 | 0.220407E+10 | 0.112802E+10 | 0.107605E+10 | 0.00 | 0.00 |
September | 0.352497E+10 | 0.659954E+09 | 0.211320E+10 | 0.120573E+10 | 0.907468E+09 | 0.00 | 0.00 |
October | 0.238869E+10 | 0.109317E+10 | 0.167936E+10 | 0.906330E+09 | 0.773027E+09 | 0.00 | 0.00 |
November | 0.165884E+10 | 0.171877E+10 | 0.145683E+10 | 0.848120E+09 | 0.608714E+09 | 0.00 | 0.00 |
December | 0.121585E+10 | 0.223121E+10 | 0.125570E+10 | 0.665296E+09 | 0.590403E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.349733E+11 | 0.135217E+11 | 0.233788E+11 | 0.127921E+11 | 0.105867E+11 | 0.00 | 0.00 |
Minimum of Months | 0.121585E+10 | 0.266595E+09 | 0.125570E+10 | 0.665296E+09 | 0.575023E+09 | 0.00 | 0.00 |
Maximum of Months | 0.459493E+10 | 0.223121E+10 | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.652063E+10 | 0.307904E+10 | 0.482167E+10 | 0.365291E+10 | 0.116875E+10 | 0.00 | 0.00 |
February | 0.555058E+10 | 0.254281E+10 | 0.403980E+10 | 0.284799E+10 | 0.119181E+10 | 0.00 | 0.00 |
March | 0.513933E+10 | 0.253175E+10 | 0.363495E+10 | 0.209589E+10 | 0.153905E+10 | 0.00 | 0.00 |
April | 0.378455E+10 | 0.155741E+10 | 0.238498E+10 | 0.889894E+09 | 0.149509E+10 | 0.00 | 0.00 |
May | 0.305810E+10 | 0.976743E+09 | 0.174163E+10 | 0.243769E+09 | 0.149786E+10 | 0.00 | 0.00 |
June | 0.313389E+10 | 0.491917E+09 | 0.145412E+10 | 92263465.73 | 0.136185E+10 | 0.00 | 0.00 |
July | 0.327207E+10 | 0.413356E+09 | 0.153172E+10 | 0.141992E+09 | 0.138973E+10 | 0.00 | 0.00 |
August | 0.393364E+10 | 0.564412E+09 | 0.195252E+10 | 0.516841E+09 | 0.143568E+10 | 0.00 | 0.00 |
September | 0.541081E+10 | 0.106992E+10 | 0.294934E+10 | 0.153228E+10 | 0.141706E+10 | 0.00 | 0.00 |
October | 0.653310E+10 | 0.171443E+10 | 0.414086E+10 | 0.279949E+10 | 0.134137E+10 | 0.00 | 0.00 |
November | 0.681398E+10 | 0.260527E+10 | 0.482240E+10 | 0.367648E+10 | 0.114592E+10 | 0.00 | 0.00 |
December | 0.657525E+10 | 0.330921E+10 | 0.493849E+10 | 0.370705E+10 | 0.123144E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.597259E+11 | 0.208563E+11 | 0.384125E+11 | 0.221969E+11 | 0.162156E+11 | 0.00 | 0.00 |
Minimum of Months | 0.305810E+10 | 0.413356E+09 | 0.145412E+10 | 92263465.73 | 0.114592E+10 | 0.00 | 0.00 |
Maximum of Months | 0.681398E+10 | 0.330921E+10 | 0.493849E+10 | 0.370705E+10 | 0.153905E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.148587E+10 | 0.215455E+10 | 0.132388E+10 | 0.745569E+09 | 0.578309E+09 | 0.00 | 0.00 |
February | 0.160950E+10 | 0.178468E+10 | 0.134929E+10 | 0.717176E+09 | 0.632116E+09 | 0.00 | 0.00 |
March | 0.265420E+10 | 0.171646E+10 | 0.203570E+10 | 0.109106E+10 | 0.944638E+09 | 0.00 | 0.00 |
April | 0.340060E+10 | 0.104154E+10 | 0.226439E+10 | 0.122304E+10 | 0.104136E+10 | 0.00 | 0.00 |
May | 0.419438E+10 | 0.678067E+09 | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.00 | 0.00 |
June | 0.443032E+10 | 0.354798E+09 | 0.237414E+10 | 0.127517E+10 | 0.109897E+10 | 0.00 | 0.00 |
July | 0.407307E+10 | 0.294977E+09 | 0.217712E+10 | 0.108185E+10 | 0.109527E+10 | 0.00 | 0.00 |
August | 0.380077E+10 | 0.388754E+09 | 0.210842E+10 | 0.107453E+10 | 0.103389E+10 | 0.00 | 0.00 |
September | 0.357407E+10 | 0.731003E+09 | 0.208664E+10 | 0.116247E+10 | 0.924172E+09 | 0.00 | 0.00 |
October | 0.278810E+10 | 0.116385E+10 | 0.185613E+10 | 0.108329E+10 | 0.772833E+09 | 0.00 | 0.00 |
November | 0.189394E+10 | 0.182543E+10 | 0.150769E+10 | 0.918021E+09 | 0.589669E+09 | 0.00 | 0.00 |
December | 0.134506E+10 | 0.234879E+10 | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.352499E+11 | 0.144829E+11 | 0.228591E+11 | 0.124026E+11 | 0.104565E+11 | 0.00 | 0.00 |
Minimum of Months | 0.134506E+10 | 0.294977E+09 | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.00 | 0.00 |
Maximum of Months | 0.443032E+10 | 0.234879E+10 | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.170853E+09 | 0.354656E+10 | 0.704831E+09 | 0.00 | 0.704831E+09 | 0.00 | 0.00 |
February | 0.402681E+09 | 0.278685E+10 | 0.777382E+09 | 0.00 | 0.777382E+09 | 0.00 | 0.00 |
March | 0.891407E+09 | 0.255882E+10 | 0.112634E+10 | 0.00 | 0.112634E+10 | 0.00 | 0.00 |
April | 0.154588E+10 | 0.143519E+10 | 0.125854E+10 | 9915458.62 | 0.124862E+10 | 0.00 | 0.00 |
May | 0.257260E+10 | 0.870680E+09 | 0.154243E+10 | 0.111539E+09 | 0.143089E+10 | 0.00 | 0.00 |
June | 0.340012E+10 | 0.441472E+09 | 0.158720E+10 | 0.195403E+09 | 0.139180E+10 | 0.00 | 0.00 |
July | 0.321140E+10 | 0.379505E+09 | 0.151578E+10 | 0.147549E+09 | 0.136823E+10 | 0.00 | 0.00 |
August | 0.247920E+10 | 0.546706E+09 | 0.127813E+10 | 26134466.51 | 0.125200E+10 | 0.00 | 0.00 |
September | 0.180659E+10 | 0.110856E+10 | 0.107931E+10 | 430682.48 | 0.107888E+10 | 0.00 | 0.00 |
October | 0.969310E+09 | 0.187703E+10 | 0.925994E+09 | 0.00 | 0.925994E+09 | 0.00 | 0.00 |
November | 0.246949E+09 | 0.311480E+10 | 0.723436E+09 | 0.00 | 0.723436E+09 | 0.00 | 0.00 |
December | 0.103568E+09 | 0.400833E+10 | 0.699373E+09 | 0.00 | 0.699373E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.178006E+11 | 0.226745E+11 | 0.132187E+11 | 0.490972E+09 | 0.127278E+11 | 0.00 | 0.00 |
Minimum of Months | 0.103568E+09 | 0.379505E+09 | 0.699373E+09 | 0.00 | 0.699373E+09 | 0.00 | 0.00 |
Maximum of Months | 0.340012E+10 | 0.400833E+10 | 0.158720E+10 | 0.195403E+09 | 0.143089E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124796E+10 | 0.223124E+10 | 0.125677E+10 | 0.681748E+09 | 0.575020E+09 | 0.00 | 0.00 |
February | 0.175802E+10 | 0.176517E+10 | 0.151872E+10 | 0.865654E+09 | 0.653061E+09 | 0.00 | 0.00 |
March | 0.262902E+10 | 0.163824E+10 | 0.207602E+10 | 0.114382E+10 | 0.932206E+09 | 0.00 | 0.00 |
April | 0.358900E+10 | 0.962325E+09 | 0.242081E+10 | 0.134300E+10 | 0.107781E+10 | 0.00 | 0.00 |
May | 0.427901E+10 | 0.612299E+09 | 0.258142E+10 | 0.140290E+10 | 0.117852E+10 | 0.00 | 0.00 |
June | 0.464772E+10 | 0.307630E+09 | 0.249955E+10 | 0.139054E+10 | 0.110901E+10 | 0.00 | 0.00 |
July | 0.430890E+10 | 0.270286E+09 | 0.231627E+10 | 0.121090E+10 | 0.110537E+10 | 0.00 | 0.00 |
August | 0.394229E+10 | 0.380964E+09 | 0.220406E+10 | 0.112801E+10 | 0.107605E+10 | 0.00 | 0.00 |
September | 0.352659E+10 | 0.720927E+09 | 0.211318E+10 | 0.120572E+10 | 0.907464E+09 | 0.00 | 0.00 |
October | 0.236973E+10 | 0.122059E+10 | 0.167934E+10 | 0.906321E+09 | 0.773023E+09 | 0.00 | 0.00 |
November | 0.160684E+10 | 0.195427E+10 | 0.145682E+10 | 0.848111E+09 | 0.608711E+09 | 0.00 | 0.00 |
December | 0.116013E+10 | 0.249413E+10 | 0.125569E+10 | 0.665289E+09 | 0.590400E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.350652E+11 | 0.145581E+11 | 0.233787E+11 | 0.127920E+11 | 0.105866E+11 | 0.00 | 0.00 |
Minimum of Months | 0.116013E+10 | 0.270286E+09 | 0.125569E+10 | 0.665289E+09 | 0.575020E+09 | 0.00 | 0.00 |
Maximum of Months | 0.464772E+10 | 0.249413E+10 | 0.258142E+10 | 0.140290E+10 | 0.117852E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.655571E+10 | 0.339674E+10 | 0.482172E+10 | 0.365295E+10 | 0.116876E+10 | 0.00 | 0.00 |
February | 0.561688E+10 | 0.270663E+10 | 0.403984E+10 | 0.284802E+10 | 0.119182E+10 | 0.00 | 0.00 |
March | 0.526084E+10 | 0.257432E+10 | 0.363498E+10 | 0.209592E+10 | 0.153906E+10 | 0.00 | 0.00 |
April | 0.388585E+10 | 0.153313E+10 | 0.238500E+10 | 0.889904E+09 | 0.149510E+10 | 0.00 | 0.00 |
May | 0.315118E+10 | 0.935319E+09 | 0.174164E+10 | 0.243772E+09 | 0.149786E+10 | 0.00 | 0.00 |
June | 0.319735E+10 | 0.452619E+09 | 0.145412E+10 | 92264539.97 | 0.136186E+10 | 0.00 | 0.00 |
July | 0.332021E+10 | 0.398757E+09 | 0.153173E+10 | 0.141994E+09 | 0.138974E+10 | 0.00 | 0.00 |
August | 0.395041E+10 | 0.591993E+09 | 0.195253E+10 | 0.516847E+09 | 0.143569E+10 | 0.00 | 0.00 |
September | 0.541550E+10 | 0.117039E+10 | 0.294937E+10 | 0.153230E+10 | 0.141707E+10 | 0.00 | 0.00 |
October | 0.652966E+10 | 0.191558E+10 | 0.414090E+10 | 0.279953E+10 | 0.134138E+10 | 0.00 | 0.00 |
November | 0.678992E+10 | 0.295610E+10 | 0.482245E+10 | 0.367653E+10 | 0.114592E+10 | 0.00 | 0.00 |
December | 0.656574E+10 | 0.369755E+10 | 0.493854E+10 | 0.370709E+10 | 0.123145E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.602392E+11 | 0.223291E+11 | 0.384128E+11 | 0.221971E+11 | 0.162157E+11 | 0.00 | 0.00 |
Minimum of Months | 0.315118E+10 | 0.398757E+09 | 0.145412E+10 | 92264539.97 | 0.114592E+10 | 0.00 | 0.00 |
Maximum of Months | 0.678992E+10 | 0.369755E+10 | 0.493854E+10 | 0.370709E+10 | 0.153906E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.147615E+10 | 0.235242E+10 | 0.132387E+10 | 0.745562E+09 | 0.578306E+09 | 0.00 | 0.00 |
February | 0.162307E+10 | 0.187953E+10 | 0.134928E+10 | 0.717169E+09 | 0.632113E+09 | 0.00 | 0.00 |
March | 0.269882E+10 | 0.176324E+10 | 0.203569E+10 | 0.109105E+10 | 0.944633E+09 | 0.00 | 0.00 |
April | 0.344568E+10 | 0.105732E+10 | 0.226438E+10 | 0.122302E+10 | 0.104135E+10 | 0.00 | 0.00 |
May | 0.424618E+10 | 0.682197E+09 | 0.252025E+10 | 0.134844E+10 | 0.117181E+10 | 0.00 | 0.00 |
June | 0.447639E+10 | 0.345899E+09 | 0.237413E+10 | 0.127516E+10 | 0.109897E+10 | 0.00 | 0.00 |
July | 0.410508E+10 | 0.299579E+09 | 0.217710E+10 | 0.108184E+10 | 0.109526E+10 | 0.00 | 0.00 |
August | 0.381471E+10 | 0.419278E+09 | 0.210841E+10 | 0.107452E+10 | 0.103389E+10 | 0.00 | 0.00 |
September | 0.357397E+10 | 0.800878E+09 | 0.208662E+10 | 0.116245E+10 | 0.924168E+09 | 0.00 | 0.00 |
October | 0.276335E+10 | 0.130858E+10 | 0.185611E+10 | 0.108328E+10 | 0.772829E+09 | 0.00 | 0.00 |
November | 0.185684E+10 | 0.208335E+10 | 0.150768E+10 | 0.918012E+09 | 0.589666E+09 | 0.00 | 0.00 |
December | 0.131527E+10 | 0.261650E+10 | 0.125547E+10 | 0.682007E+09 | 0.573460E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.353955E+11 | 0.156088E+11 | 0.228590E+11 | 0.124025E+11 | 0.104565E+11 | 0.00 | 0.00 |
Minimum of Months | 0.131527E+10 | 0.299579E+09 | 0.125547E+10 | 0.682007E+09 | 0.573460E+09 | 0.00 | 0.00 |
Maximum of Months | 0.447639E+10 | 0.261650E+10 | 0.252025E+10 | 0.134844E+10 | 0.117181E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.158406E+09 | 0.358841E+10 | 0.704835E+09 | 0.00 | 0.704835E+09 | 0.00 | 0.00 |
February | 0.357797E+09 | 0.292099E+10 | 0.777386E+09 | 0.00 | 0.777386E+09 | 0.00 | 0.00 |
March | 0.790415E+09 | 0.275094E+10 | 0.112635E+10 | 0.00 | 0.112635E+10 | 0.00 | 0.00 |
April | 0.145318E+10 | 0.157038E+10 | 0.125854E+10 | 9915510.00 | 0.124863E+10 | 0.00 | 0.00 |
May | 0.249486E+10 | 0.947123E+09 | 0.154244E+10 | 0.111540E+09 | 0.143090E+10 | 0.00 | 0.00 |
June | 0.334376E+10 | 0.487114E+09 | 0.158721E+10 | 0.195404E+09 | 0.139181E+10 | 0.00 | 0.00 |
July | 0.317919E+10 | 0.402211E+09 | 0.151579E+10 | 0.147550E+09 | 0.136824E+10 | 0.00 | 0.00 |
August | 0.247346E+10 | 0.551248E+09 | 0.127814E+10 | 26134601.93 | 0.125200E+10 | 0.00 | 0.00 |
September | 0.181416E+10 | 0.108963E+10 | 0.107931E+10 | 430684.71 | 0.107888E+10 | 0.00 | 0.00 |
October | 0.976767E+09 | 0.183537E+10 | 0.925999E+09 | 0.00 | 0.925999E+09 | 0.00 | 0.00 |
November | 0.253469E+09 | 0.304600E+10 | 0.723440E+09 | 0.00 | 0.723440E+09 | 0.00 | 0.00 |
December | 0.106675E+09 | 0.395438E+10 | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.174021E+11 | 0.231438E+11 | 0.132188E+11 | 0.490975E+09 | 0.127278E+11 | 0.00 | 0.00 |
Minimum of Months | 0.106675E+09 | 0.402211E+09 | 0.699376E+09 | 0.00 | 0.699376E+09 | 0.00 | 0.00 |
Maximum of Months | 0.334376E+10 | 0.395438E+10 | 0.158721E+10 | 0.195404E+09 | 0.143090E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123239E+10 | 0.220677E+10 | 0.125678E+10 | 0.681755E+09 | 0.575023E+09 | 0.00 | 0.00 |
February | 0.172202E+10 | 0.179015E+10 | 0.151873E+10 | 0.865663E+09 | 0.653065E+09 | 0.00 | 0.00 |
March | 0.256502E+10 | 0.169244E+10 | 0.207604E+10 | 0.114383E+10 | 0.932211E+09 | 0.00 | 0.00 |
April | 0.353900E+10 | 0.991212E+09 | 0.242083E+10 | 0.134302E+10 | 0.107781E+10 | 0.00 | 0.00 |
May | 0.423682E+10 | 0.630917E+09 | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.00 | 0.00 |
June | 0.461812E+10 | 0.319179E+09 | 0.249957E+10 | 0.139056E+10 | 0.110902E+10 | 0.00 | 0.00 |
July | 0.429587E+10 | 0.268209E+09 | 0.231629E+10 | 0.121091E+10 | 0.110538E+10 | 0.00 | 0.00 |
August | 0.394232E+10 | 0.364749E+09 | 0.220407E+10 | 0.112802E+10 | 0.107605E+10 | 0.00 | 0.00 |
September | 0.353144E+10 | 0.683630E+09 | 0.211320E+10 | 0.120573E+10 | 0.907468E+09 | 0.00 | 0.00 |
October | 0.237361E+10 | 0.116241E+10 | 0.167936E+10 | 0.906330E+09 | 0.773027E+09 | 0.00 | 0.00 |
November | 0.161502E+10 | 0.186143E+10 | 0.145683E+10 | 0.848120E+09 | 0.608714E+09 | 0.00 | 0.00 |
December | 0.116354E+10 | 0.241234E+10 | 0.125570E+10 | 0.665296E+09 | 0.590403E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.348352E+11 | 0.143834E+11 | 0.233788E+11 | 0.127921E+11 | 0.105867E+11 | 0.00 | 0.00 |
Minimum of Months | 0.116354E+10 | 0.268209E+09 | 0.125570E+10 | 0.665296E+09 | 0.575023E+09 | 0.00 | 0.00 |
Maximum of Months | 0.461812E+10 | 0.241234E+10 | 0.258144E+10 | 0.140291E+10 | 0.117853E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.646585E+10 | 0.331680E+10 | 0.482167E+10 | 0.365291E+10 | 0.116875E+10 | 0.00 | 0.00 |
February | 0.550723E+10 | 0.272165E+10 | 0.403980E+10 | 0.284799E+10 | 0.119181E+10 | 0.00 | 0.00 |
March | 0.510622E+10 | 0.268271E+10 | 0.363495E+10 | 0.209589E+10 | 0.153905E+10 | 0.00 | 0.00 |
April | 0.378279E+10 | 0.163581E+10 | 0.238498E+10 | 0.889894E+09 | 0.149509E+10 | 0.00 | 0.00 |
May | 0.307068E+10 | 0.101429E+10 | 0.174163E+10 | 0.243769E+09 | 0.149786E+10 | 0.00 | 0.00 |
June | 0.315929E+10 | 0.498848E+09 | 0.145412E+10 | 92263465.73 | 0.136185E+10 | 0.00 | 0.00 |
July | 0.330303E+10 | 0.417612E+09 | 0.153172E+10 | 0.141992E+09 | 0.138973E+10 | 0.00 | 0.00 |
August | 0.395576E+10 | 0.582277E+09 | 0.195252E+10 | 0.516841E+09 | 0.143568E+10 | 0.00 | 0.00 |
September | 0.542234E+10 | 0.111316E+10 | 0.294934E+10 | 0.153228E+10 | 0.141706E+10 | 0.00 | 0.00 |
October | 0.651634E+10 | 0.181815E+10 | 0.414086E+10 | 0.279949E+10 | 0.134137E+10 | 0.00 | 0.00 |
November | 0.675633E+10 | 0.280730E+10 | 0.482240E+10 | 0.367648E+10 | 0.114592E+10 | 0.00 | 0.00 |
December | 0.649843E+10 | 0.356773E+10 | 0.493849E+10 | 0.370705E+10 | 0.123144E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.595443E+11 | 0.221763E+11 | 0.384125E+11 | 0.221969E+11 | 0.162156E+11 | 0.00 | 0.00 |
Minimum of Months | 0.307068E+10 | 0.417612E+09 | 0.145412E+10 | 92263465.73 | 0.114592E+10 | 0.00 | 0.00 |
Maximum of Months | 0.675633E+10 | 0.356773E+10 | 0.493849E+10 | 0.370705E+10 | 0.153905E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.145967E+10 | 0.232831E+10 | 0.132388E+10 | 0.745569E+09 | 0.578309E+09 | 0.00 | 0.00 |
February | 0.158737E+10 | 0.191631E+10 | 0.134929E+10 | 0.717176E+09 | 0.632116E+09 | 0.00 | 0.00 |
March | 0.263284E+10 | 0.182667E+10 | 0.203570E+10 | 0.109106E+10 | 0.944638E+09 | 0.00 | 0.00 |
April | 0.339629E+10 | 0.109497E+10 | 0.226439E+10 | 0.122304E+10 | 0.104136E+10 | 0.00 | 0.00 |
May | 0.420428E+10 | 0.703396E+09 | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.00 | 0.00 |
June | 0.444910E+10 | 0.358969E+09 | 0.237414E+10 | 0.127517E+10 | 0.109897E+10 | 0.00 | 0.00 |
July | 0.409380E+10 | 0.298107E+09 | 0.217712E+10 | 0.108185E+10 | 0.109527E+10 | 0.00 | 0.00 |
August | 0.381464E+10 | 0.400877E+09 | 0.210842E+10 | 0.107453E+10 | 0.103389E+10 | 0.00 | 0.00 |
September | 0.357798E+10 | 0.761113E+09 | 0.208664E+10 | 0.116247E+10 | 0.924172E+09 | 0.00 | 0.00 |
October | 0.277162E+10 | 0.124360E+10 | 0.185613E+10 | 0.108329E+10 | 0.772833E+09 | 0.00 | 0.00 |
November | 0.186470E+10 | 0.198507E+10 | 0.150769E+10 | 0.918021E+09 | 0.589669E+09 | 0.00 | 0.00 |
December | 0.131368E+10 | 0.254086E+10 | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.351660E+11 | 0.154583E+11 | 0.228591E+11 | 0.124026E+11 | 0.104565E+11 | 0.00 | 0.00 |
Minimum of Months | 0.131368E+10 | 0.298107E+09 | 0.125548E+10 | 0.682014E+09 | 0.573463E+09 | 0.00 | 0.00 |
Maximum of Months | 0.444910E+10 | 0.254086E+10 | 0.252027E+10 | 0.134845E+10 | 0.117181E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.484717E+10 | -0.414208E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -705088574.6 | 58.98 | 0.00 | 0.00 |
February | 0.439498E+10 | -0.376148E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -633495503.6 | 58.98 | 0.00 | 0.00 |
March | 0.498630E+10 | -0.428819E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -698118852.6 | 58.98 | 0.00 | 0.00 |
April | 0.427228E+10 | -0.360292E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669360255.9 | 58.98 | 0.00 | 0.00 |
May | 0.424014E+10 | -0.354967E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690470588.2 | 58.98 | 0.00 | 0.00 |
June | 0.391305E+10 | -0.324553E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667514857.8 | 58.98 | 0.00 | 0.00 |
July | 0.359630E+10 | -0.290771E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688589896.4 | 58.98 | 0.00 | 0.00 |
August | 0.390927E+10 | -0.321912E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690150659.3 | 58.98 | 0.00 | 0.00 |
September | 0.371840E+10 | -0.305236E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666042445.3 | 58.98 | 0.00 | 0.00 |
October | 0.411018E+10 | -0.341988E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690301434.4 | 58.98 | 0.00 | 0.00 |
November | 0.433582E+10 | -0.366332E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -672499182.6 | 58.98 | 0.00 | 0.00 |
December | 0.458533E+10 | -0.388012E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -705203306.7 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.509092E+11 | -0.427324E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.817684E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.359630E+10 | -0.428819E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -705203306.7 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.498630E+10 | -0.290771E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -633495503.6 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.50 | 0.48 | 01-JAN-08:20 | 7847.03 | 36.94 | 265.17 | 274.50 | 1642.64 | 25.90 | 129.67 | 259.17 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-07:00 | 8500.85 | 36.41 | 261.50 | 265.50 | 1187.43 | 21.87 | 86.83 | 238.83 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:19 | 1711.27 | 17.06 | 10.67 | 313.33 | 886.70 | 19.32 | 62.17 | 281.33 |
April | 373.83 | 0.52 | 0.48 | 01-APR-07:10 | 1057.36 | 16.43 | 0.00 | 326.50 | 655.02 | 19.17 | 20.67 | 280.00 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-06:49 | 860.48 | 16.11 | 0.00 | 352.17 | 529.64 | 18.85 | 0.00 | 298.83 |
June | 398.00 | 0.52 | 0.48 | 01-JUN-06:49 | 767.33 | 15.95 | 0.00 | 342.50 | 484.49 | 18.81 | 0.00 | 284.50 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-06:00 | 821.49 | 16.00 | 0.00 | 348.17 | 499.20 | 18.78 | 0.67 | 273.00 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-06:49 | 976.29 | 16.40 | 0.00 | 336.67 | 592.58 | 19.13 | 11.83 | 279.17 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:30 | 1261.73 | 16.82 | 11.00 | 308.83 | 745.91 | 19.10 | 38.50 | 268.50 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-07:10 | 3171.11 | 23.88 | 131.00 | 308.50 | 1055.13 | 20.22 | 67.00 | 276.50 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 8052.28 | 36.92 | 288.33 | 283.83 | 1335.63 | 24.25 | 112.50 | 270.67 |
December | 289.50 | 0.50 | 0.48 | 01-DEC-07:19 | 7120.31 | 37.32 | 284.00 | 273.83 | 1617.86 | 25.93 | 135.00 | 266.67 |
Annual Sum or Average | 4125.67 | 0.51 | 3083.54 | 22.58 | 1251.67 | 3734.33 | 881.31 | 20.62 | 664.83 | 3277.17 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 767.33 | 15.95 | 0.00 | 265.50 | 484.49 | 18.78 | 0.00 | 238.83 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 8500.85 | 37.32 | 288.33 | 352.17 | 1642.64 | 25.93 | 135.00 | 298.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.53 | 0.48 | 01-JAN-08:09 | 2002.92 | 19.52 | 79.83 | 232.67 | 1158.22 | 21.99 | 63.33 | 168.83 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-07:40 | 2548.26 | 21.05 | 89.67 | 236.33 | 929.87 | 20.17 | 41.00 | 180.67 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-06:00 | 2210.57 | 18.11 | 82.50 | 293.33 | 1229.23 | 21.12 | 70.83 | 253.50 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:10 | 2931.20 | 19.79 | 109.83 | 325.83 | 1101.76 | 19.48 | 50.83 | 290.33 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-05:49 | 2252.45 | 17.63 | 87.00 | 354.50 | 1272.46 | 20.58 | 72.67 | 315.67 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-05:49 | 2288.22 | 17.70 | 85.00 | 348.67 | 1305.48 | 20.64 | 70.00 | 308.00 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-05:49 | 2040.22 | 17.56 | 84.17 | 354.17 | 1125.94 | 20.49 | 69.00 | 301.50 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:49 | 2641.13 | 19.49 | 109.50 | 336.33 | 1016.80 | 19.53 | 52.33 | 293.33 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-06:10 | 2534.12 | 19.95 | 111.50 | 302.17 | 974.02 | 19.88 | 57.67 | 263.67 |
October | 318.83 | 0.52 | 0.48 | 01-OCT-06:49 | 2120.10 | 18.41 | 77.67 | 274.00 | 1189.47 | 20.98 | 60.67 | 218.33 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:50 | 1757.64 | 18.67 | 77.50 | 238.00 | 911.58 | 20.00 | 50.67 | 175.83 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-07:10 | 1563.22 | 19.64 | 78.83 | 236.17 | 814.31 | 20.78 | 50.33 | 181.50 |
Annual Sum or Average | 4125.67 | 0.52 | 2262.24 | 18.87 | 1073.00 | 3532.17 | 1098.02 | 20.44 | 709.33 | 2951.17 | ||
Minimum of Months | 268.33 | 0.51 | 0.48 | 1563.22 | 17.56 | 77.50 | 232.67 | 814.31 | 19.48 | 41.00 | 168.83 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 2931.20 | 21.05 | 111.50 | 354.50 | 1305.48 | 21.99 | 72.67 | 315.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.56 | 0.48 | 01-JAN-09:20 | 424.57 | 12.97 | 0.00 | 197.00 | 285.61 | 16.28 | 0.00 | 61.17 |
February | 268.33 | 0.54 | 0.48 | 01-FEB-09:50 | 483.83 | 13.80 | 0.00 | 208.83 | 324.64 | 16.93 | 0.00 | 104.33 |
March | 351.83 | 0.53 | 0.48 | 01-MAR-08:20 | 573.05 | 14.73 | 0.00 | 281.83 | 369.95 | 17.62 | 0.00 | 193.33 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:40 | 680.33 | 16.06 | 0.00 | 343.67 | 437.31 | 18.80 | 0.00 | 281.67 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:10 | 844.14 | 16.91 | 3.00 | 381.00 | 489.67 | 19.52 | 8.33 | 348.83 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-06:10 | 908.17 | 20.23 | 83.17 | 378.17 | 513.83 | 19.87 | 27.67 | 348.00 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-06:10 | 860.32 | 18.38 | 37.17 | 384.00 | 492.33 | 19.71 | 16.17 | 332.83 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:00 | 730.07 | 16.37 | 0.00 | 355.00 | 456.26 | 19.08 | 0.00 | 301.50 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-08:20 | 568.60 | 15.14 | 0.00 | 289.33 | 374.66 | 17.99 | 0.00 | 201.83 |
October | 318.83 | 0.54 | 0.48 | 01-OCT-08:09 | 509.40 | 14.17 | 0.00 | 262.83 | 338.58 | 17.20 | 0.00 | 146.50 |
November | 295.83 | 0.56 | 0.48 | 01-NOV-13:20 | 411.45 | 12.97 | 0.00 | 196.50 | 279.85 | 16.24 | 0.00 | 57.00 |
December | 289.50 | 0.56 | 0.48 | 01-DEC-09:09 | 425.34 | 12.99 | 0.00 | 205.33 | 281.14 | 16.23 | 0.00 | 52.50 |
Annual Sum or Average | 4125.67 | 0.52 | 641.17 | 15.67 | 123.33 | 3483.50 | 398.27 | 18.14 | 52.17 | 2429.50 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 411.45 | 12.97 | 0.00 | 196.50 | 279.85 | 16.23 | 0.00 | 52.50 | |
Maximum of Months | 408.83 | 0.56 | 0.48 | 908.17 | 20.23 | 83.17 | 384.00 | 513.83 | 19.87 | 27.67 | 348.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-09:20 | 1718.70 | 19.91 | 81.17 | 242.33 | 904.33 | 20.90 | 52.33 | 180.67 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-09:50 | 1936.00 | 18.91 | 70.83 | 236.67 | 1097.36 | 22.11 | 61.33 | 188.67 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-08:20 | 2575.25 | 20.29 | 110.33 | 305.67 | 965.73 | 19.76 | 52.50 | 258.50 |
April | 373.83 | 0.51 | 0.48 | 01-APR-08:09 | 2870.05 | 19.78 | 111.83 | 329.33 | 1124.18 | 19.61 | 51.83 | 290.50 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-07:19 | 2146.36 | 12.42 | 0.00 | 364.50 | 1238.15 | 16.68 | 0.00 | 326.67 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-07:19 | 2322.33 | 12.50 | 0.00 | 363.33 | 1272.21 | 16.80 | 0.00 | 316.50 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-07:19 | 2066.22 | 12.84 | 3.67 | 366.67 | 1135.64 | 16.84 | 0.00 | 306.33 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-07:30 | 2069.47 | 16.11 | 57.17 | 337.17 | 1095.26 | 16.93 | 3.67 | 292.00 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-08:30 | 2522.99 | 19.76 | 110.17 | 300.67 | 980.89 | 19.75 | 55.83 | 257.33 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-08:20 | 2122.75 | 19.42 | 86.17 | 289.00 | 1159.62 | 21.91 | 69.00 | 235.17 |
November | 295.83 | 0.52 | 0.48 | 01-NOV-12:39 | 1627.78 | 19.77 | 86.17 | 244.33 | 808.61 | 20.50 | 54.00 | 187.17 |
December | 289.50 | 0.52 | 0.48 | 01-DEC-09:09 | 1795.43 | 21.86 | 105.67 | 245.33 | 722.13 | 21.14 | 51.83 | 183.50 |
Annual Sum or Average | 4125.67 | 0.51 | 2178.06 | 17.45 | 823.17 | 3625.00 | 1057.40 | 19.16 | 452.33 | 3023.00 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1627.78 | 12.42 | 0.00 | 236.67 | 722.13 | 16.68 | 0.00 | 180.67 | |
Maximum of Months | 408.83 | 0.52 | 0.48 | 2870.05 | 21.86 | 111.83 | 366.67 | 1272.21 | 22.11 | 69.00 | 326.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.50 | 0.48 | 01-JAN-08:20 | 7701.95 | 36.63 | 265.17 | 273.67 | 1526.14 | 23.45 | 97.17 | 257.67 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-08:09 | 8374.99 | 36.20 | 261.33 | 264.33 | 1089.80 | 19.19 | 34.67 | 237.50 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:19 | 1622.43 | 13.40 | 10.67 | 310.67 | 820.64 | 16.87 | 1.83 | 276.00 |
April | 373.83 | 0.52 | 0.48 | 01-APR-07:19 | 1001.94 | 13.06 | 0.00 | 323.50 | 617.96 | 17.08 | 0.00 | 275.17 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-06:00 | 822.46 | 12.90 | 0.00 | 347.33 | 507.58 | 16.86 | 0.00 | 293.00 |
June | 398.00 | 0.52 | 0.48 | 01-JUN-06:00 | 735.77 | 12.64 | 0.00 | 339.67 | 467.32 | 16.74 | 0.00 | 277.17 |
July | 400.17 | 0.53 | 0.48 | 01-JUL-07:10 | 785.86 | 12.70 | 0.00 | 344.00 | 479.04 | 16.72 | 0.00 | 265.17 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-06:00 | 928.61 | 13.07 | 0.00 | 333.50 | 562.59 | 17.04 | 0.00 | 274.33 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:30 | 1191.26 | 13.34 | 11.00 | 305.50 | 694.99 | 16.86 | 0.00 | 263.00 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-07:10 | 3053.87 | 21.12 | 128.00 | 306.83 | 970.26 | 17.62 | 13.33 | 273.00 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 7890.63 | 35.70 | 278.33 | 279.83 | 1231.66 | 21.77 | 90.00 | 269.33 |
December | 289.50 | 0.50 | 0.48 | 01-DEC-07:19 | 6972.88 | 37.13 | 284.00 | 272.67 | 1504.12 | 23.48 | 101.33 | 265.17 |
Annual Sum or Average | 4125.67 | 0.51 | 3001.14 | 20.04 | 1238.50 | 3701.50 | 823.10 | 18.34 | 338.33 | 3226.50 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 735.77 | 12.64 | 0.00 | 264.33 | 467.32 | 16.72 | 0.00 | 237.50 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 8374.99 | 37.13 | 284.00 | 347.33 | 1526.14 | 23.48 | 101.33 | 293.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.54 | 0.48 | 01-JAN-08:09 | 1954.29 | 19.07 | 79.83 | 228.33 | 1119.39 | 21.77 | 63.33 | 165.33 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-07:40 | 2488.41 | 20.64 | 89.67 | 233.33 | 884.99 | 19.96 | 41.00 | 178.17 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-06:00 | 2149.27 | 17.67 | 82.33 | 289.50 | 1178.26 | 20.93 | 70.83 | 249.83 |
April | 373.83 | 0.52 | 0.48 | 01-APR-06:10 | 2855.13 | 19.39 | 109.83 | 323.00 | 1043.80 | 19.30 | 50.83 | 285.17 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-05:49 | 2176.52 | 17.22 | 87.00 | 351.50 | 1217.90 | 20.42 | 72.67 | 311.17 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-05:49 | 2223.27 | 17.28 | 85.00 | 346.00 | 1250.17 | 20.48 | 70.00 | 305.33 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-05:49 | 1975.91 | 17.14 | 84.17 | 350.67 | 1074.65 | 20.32 | 69.00 | 296.83 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-05:49 | 2566.77 | 19.10 | 109.50 | 332.50 | 965.84 | 19.35 | 52.33 | 288.83 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-06:10 | 2475.02 | 19.55 | 111.50 | 298.17 | 925.71 | 19.70 | 57.67 | 260.83 |
October | 318.83 | 0.53 | 0.48 | 01-OCT-06:49 | 2061.60 | 17.97 | 77.67 | 271.83 | 1143.67 | 20.78 | 60.67 | 213.33 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:00 | 1694.89 | 17.89 | 73.50 | 233.67 | 870.55 | 19.78 | 50.67 | 169.33 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-07:10 | 1389.55 | 17.48 | 61.83 | 230.50 | 777.40 | 20.55 | 50.33 | 175.50 |
Annual Sum or Average | 4125.67 | 0.52 | 2189.68 | 18.30 | 1051.83 | 3489.00 | 1049.15 | 20.25 | 709.33 | 2899.67 | ||
Minimum of Months | 268.33 | 0.51 | 0.48 | 1389.55 | 17.14 | 61.83 | 228.33 | 777.40 | 19.30 | 41.00 | 165.33 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 2855.13 | 20.64 | 111.50 | 351.50 | 1250.17 | 21.77 | 72.67 | 311.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.56 | 0.48 | 01-JAN-09:20 | 406.44 | 9.50 | 0.00 | 184.83 | 276.44 | 13.93 | 0.00 | 50.83 |
February | 268.33 | 0.55 | 0.48 | 01-FEB-09:00 | 463.79 | 10.50 | 0.00 | 201.33 | 314.56 | 14.79 | 0.00 | 96.00 |
March | 351.83 | 0.53 | 0.48 | 01-MAR-08:20 | 550.66 | 11.48 | 0.00 | 276.83 | 358.66 | 15.62 | 0.00 | 185.17 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:40 | 653.69 | 12.95 | 0.00 | 342.67 | 423.74 | 17.04 | 0.00 | 274.67 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:19 | 811.42 | 13.61 | 3.00 | 380.00 | 472.19 | 17.59 | 0.00 | 344.50 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-06:10 | 873.39 | 17.49 | 83.17 | 377.33 | 496.36 | 17.77 | 1.33 | 345.83 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-05:00 | 826.05 | 15.24 | 37.17 | 382.17 | 502.07 | 19.15 | 37.50 | 333.67 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:00 | 700.59 | 13.14 | 0.00 | 353.00 | 440.90 | 17.22 | 0.00 | 293.50 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-08:30 | 545.86 | 12.03 | 0.00 | 283.50 | 363.23 | 16.16 | 0.00 | 194.00 |
October | 318.83 | 0.54 | 0.48 | 01-OCT-08:20 | 488.71 | 10.94 | 0.00 | 255.67 | 328.17 | 15.16 | 0.00 | 134.33 |
November | 295.83 | 0.57 | 0.48 | 01-NOV-13:20 | 394.33 | 9.54 | 0.00 | 183.50 | 271.28 | 13.97 | 0.00 | 45.50 |
December | 289.50 | 0.57 | 0.48 | 01-DEC-09:20 | 406.60 | 9.54 | 0.00 | 193.67 | 271.53 | 13.89 | 0.00 | 38.83 |
Annual Sum or Average | 4125.67 | 0.53 | 615.55 | 12.46 | 123.33 | 3414.50 | 387.82 | 16.25 | 38.83 | 2336.83 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 394.33 | 9.50 | 0.00 | 183.50 | 271.28 | 13.89 | 0.00 | 38.83 | |
Maximum of Months | 408.83 | 0.57 | 0.48 | 873.39 | 17.49 | 83.17 | 382.17 | 502.07 | 19.15 | 37.50 | 345.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-09:20 | 1666.41 | 19.57 | 81.17 | 237.33 | 862.52 | 20.79 | 52.33 | 175.00 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-09:00 | 1882.67 | 18.53 | 70.83 | 232.83 | 1056.89 | 21.99 | 61.33 | 184.50 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-08:30 | 2516.77 | 19.93 | 110.33 | 301.17 | 919.01 | 19.63 | 52.50 | 254.50 |
April | 373.83 | 0.51 | 0.48 | 01-APR-08:09 | 2803.48 | 19.40 | 111.83 | 325.00 | 1023.78 | 19.45 | 51.83 | 285.67 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-07:30 | 2070.82 | 11.97 | 0.00 | 361.17 | 1187.05 | 16.50 | 0.00 | 322.50 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-07:19 | 2156.27 | 12.04 | 0.00 | 358.33 | 1222.61 | 16.62 | 0.00 | 312.67 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-07:30 | 2002.91 | 12.37 | 3.67 | 361.50 | 1090.13 | 16.64 | 0.00 | 300.83 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-07:30 | 2001.28 | 15.68 | 57.17 | 332.17 | 1046.79 | 16.75 | 3.67 | 287.00 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-08:39 | 2463.84 | 19.38 | 110.17 | 296.83 | 932.97 | 19.61 | 55.83 | 254.17 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-08:20 | 2060.53 | 19.05 | 86.17 | 283.33 | 1110.93 | 21.80 | 69.00 | 232.00 |
November | 295.83 | 0.53 | 0.48 | 01-NOV-12:39 | 1570.23 | 19.05 | 82.33 | 239.00 | 769.60 | 20.39 | 54.00 | 183.67 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-09:09 | 1626.80 | 19.03 | 82.83 | 237.33 | 687.70 | 21.04 | 52.00 | 176.17 |
Annual Sum or Average | 4125.67 | 0.51 | 2098.15 | 16.85 | 796.50 | 3566.00 | 1006.95 | 19.01 | 452.50 | 2968.67 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1570.23 | 11.97 | 0.00 | 232.83 | 687.70 | 16.50 | 0.00 | 175.00 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 2803.48 | 19.93 | 111.83 | 361.50 | 1222.61 | 21.99 | 69.00 | 322.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.50 | 0.48 | 01-JAN-08:20 | 7701.96 | 36.63 | 265.17 | 273.67 | 1526.09 | 23.45 | 97.17 | 257.67 |
February | 268.33 | 0.50 | 0.48 | 01-FEB-08:09 | 8374.97 | 36.21 | 261.33 | 264.33 | 1089.75 | 19.19 | 34.67 | 237.50 |
March | 351.83 | 0.51 | 0.48 | 01-MAR-07:19 | 1622.39 | 13.41 | 10.67 | 310.67 | 820.60 | 16.87 | 1.83 | 276.00 |
April | 373.83 | 0.52 | 0.48 | 01-APR-07:19 | 1001.92 | 13.06 | 0.00 | 323.50 | 617.93 | 17.08 | 0.00 | 275.17 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-06:00 | 822.44 | 12.90 | 0.00 | 347.33 | 507.56 | 16.86 | 0.00 | 293.00 |
June | 398.00 | 0.52 | 0.48 | 01-JUN-06:00 | 735.76 | 12.64 | 0.00 | 339.67 | 467.30 | 16.74 | 0.00 | 276.83 |
July | 400.17 | 0.53 | 0.48 | 01-JUL-07:10 | 785.84 | 12.70 | 0.00 | 344.00 | 479.02 | 16.72 | 0.00 | 265.17 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-06:00 | 928.58 | 13.07 | 0.00 | 333.50 | 562.56 | 17.04 | 0.00 | 274.33 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-07:30 | 1191.23 | 13.35 | 11.00 | 305.50 | 694.96 | 16.86 | 0.00 | 263.00 |
October | 318.83 | 0.50 | 0.48 | 01-OCT-07:10 | 3053.84 | 21.12 | 128.00 | 306.83 | 970.21 | 17.62 | 13.33 | 273.00 |
November | 295.83 | 0.50 | 0.48 | 01-NOV-12:39 | 7890.63 | 35.70 | 278.33 | 279.83 | 1231.61 | 21.77 | 90.00 | 269.33 |
December | 289.50 | 0.50 | 0.48 | 01-DEC-07:19 | 6972.90 | 37.13 | 284.00 | 272.67 | 1504.06 | 23.48 | 101.33 | 265.17 |
Annual Sum or Average | 4125.67 | 0.51 | 3001.12 | 20.04 | 1238.50 | 3701.50 | 823.06 | 18.34 | 338.33 | 3226.17 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 735.76 | 12.64 | 0.00 | 264.33 | 467.30 | 16.72 | 0.00 | 237.50 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 8374.97 | 37.13 | 284.00 | 347.33 | 1526.09 | 23.48 | 101.33 | 293.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.54 | 0.48 | 01-JAN-08:09 | 1954.30 | 19.07 | 79.83 | 228.33 | 1119.36 | 21.77 | 63.33 | 165.33 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-07:40 | 2488.42 | 20.65 | 89.67 | 233.33 | 884.96 | 19.96 | 41.00 | 178.17 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-06:00 | 2149.26 | 17.67 | 82.33 | 289.50 | 1178.22 | 20.94 | 70.83 | 249.83 |
April | 373.83 | 0.52 | 0.48 | 01-APR-06:10 | 2855.13 | 19.39 | 109.83 | 323.00 | 1043.76 | 19.30 | 50.83 | 285.17 |
May | 408.83 | 0.52 | 0.48 | 01-MAY-05:49 | 2176.52 | 17.22 | 87.00 | 351.50 | 1217.86 | 20.42 | 72.67 | 311.17 |
June | 398.00 | 0.51 | 0.48 | 01-JUN-05:49 | 2223.27 | 17.28 | 85.00 | 346.00 | 1250.14 | 20.48 | 70.00 | 305.33 |
July | 400.17 | 0.52 | 0.48 | 01-JUL-05:49 | 1975.91 | 17.14 | 84.17 | 350.67 | 1074.61 | 20.32 | 69.00 | 296.83 |
August | 377.83 | 0.52 | 0.48 | 01-AUG-05:49 | 2566.77 | 19.10 | 109.50 | 332.50 | 965.80 | 19.35 | 52.33 | 288.83 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-06:10 | 2475.02 | 19.55 | 111.50 | 298.33 | 925.68 | 19.70 | 57.67 | 260.67 |
October | 318.83 | 0.53 | 0.48 | 01-OCT-06:49 | 2061.60 | 17.97 | 77.67 | 271.83 | 1143.64 | 20.78 | 60.67 | 213.33 |
November | 295.83 | 0.54 | 0.48 | 01-NOV-12:00 | 1694.90 | 17.89 | 73.50 | 233.67 | 870.53 | 19.78 | 50.67 | 169.33 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-07:10 | 1389.56 | 17.48 | 61.83 | 230.50 | 777.37 | 20.55 | 50.33 | 175.50 |
Annual Sum or Average | 4125.67 | 0.52 | 2189.68 | 18.31 | 1051.83 | 3489.17 | 1049.12 | 20.25 | 709.33 | 2899.50 | ||
Minimum of Months | 268.33 | 0.51 | 0.48 | 1389.56 | 17.14 | 61.83 | 228.33 | 777.37 | 19.30 | 41.00 | 165.33 | |
Maximum of Months | 408.83 | 0.54 | 0.48 | 2855.13 | 20.65 | 111.50 | 351.50 | 1250.14 | 21.77 | 72.67 | 311.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.56 | 0.48 | 01-JAN-09:20 | 406.45 | 9.50 | 0.00 | 185.00 | 276.43 | 13.93 | 0.00 | 50.67 |
February | 268.33 | 0.55 | 0.48 | 01-FEB-09:00 | 463.80 | 10.50 | 0.00 | 201.33 | 314.54 | 14.79 | 0.00 | 96.00 |
March | 351.83 | 0.53 | 0.48 | 01-MAR-08:20 | 550.66 | 11.48 | 0.00 | 276.83 | 358.64 | 15.62 | 0.00 | 185.17 |
April | 373.83 | 0.51 | 0.48 | 01-APR-06:40 | 653.69 | 12.95 | 0.00 | 342.67 | 423.73 | 17.04 | 0.00 | 274.67 |
May | 408.83 | 0.50 | 0.48 | 01-MAY-06:19 | 811.41 | 13.61 | 3.00 | 380.00 | 472.17 | 17.59 | 0.00 | 344.50 |
June | 398.00 | 0.49 | 0.48 | 01-JUN-06:10 | 873.38 | 17.49 | 83.17 | 377.33 | 496.34 | 17.77 | 1.33 | 345.83 |
July | 400.17 | 0.50 | 0.48 | 01-JUL-05:00 | 826.04 | 15.24 | 37.17 | 382.17 | 502.04 | 19.15 | 37.50 | 333.67 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-05:00 | 700.58 | 13.14 | 0.00 | 353.00 | 440.88 | 17.22 | 0.00 | 293.50 |
September | 365.83 | 0.53 | 0.48 | 01-SEP-08:30 | 545.86 | 12.03 | 0.00 | 283.50 | 363.21 | 16.16 | 0.00 | 194.00 |
October | 318.83 | 0.54 | 0.48 | 01-OCT-08:20 | 488.71 | 10.94 | 0.00 | 255.67 | 328.16 | 15.16 | 0.00 | 134.33 |
November | 295.83 | 0.57 | 0.48 | 01-NOV-13:20 | 394.34 | 9.54 | 0.00 | 183.50 | 271.27 | 13.97 | 0.00 | 45.50 |
December | 289.50 | 0.57 | 0.48 | 01-DEC-09:20 | 406.61 | 9.55 | 0.00 | 193.67 | 271.51 | 13.89 | 0.00 | 38.83 |
Annual Sum or Average | 4125.67 | 0.53 | 615.55 | 12.46 | 123.33 | 3414.67 | 387.80 | 16.25 | 38.83 | 2336.67 | ||
Minimum of Months | 268.33 | 0.49 | 0.48 | 394.34 | 9.50 | 0.00 | 183.50 | 271.27 | 13.89 | 0.00 | 38.83 | |
Maximum of Months | 408.83 | 0.57 | 0.48 | 873.38 | 17.49 | 83.17 | 382.17 | 502.04 | 19.15 | 37.50 | 345.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.83 | 0.52 | 0.48 | 01-JAN-09:20 | 1666.42 | 19.57 | 81.17 | 237.33 | 862.49 | 20.80 | 52.33 | 175.00 |
February | 268.33 | 0.52 | 0.48 | 01-FEB-09:00 | 1882.67 | 18.54 | 70.83 | 232.83 | 1056.86 | 21.99 | 61.33 | 184.50 |
March | 351.83 | 0.52 | 0.48 | 01-MAR-08:30 | 2516.76 | 19.93 | 110.33 | 301.17 | 918.98 | 19.63 | 52.50 | 254.50 |
April | 373.83 | 0.51 | 0.48 | 01-APR-08:09 | 2803.48 | 19.40 | 111.83 | 325.00 | 1023.75 | 19.45 | 51.83 | 285.67 |
May | 408.83 | 0.51 | 0.48 | 01-MAY-07:30 | 2070.81 | 11.97 | 0.00 | 361.17 | 1187.02 | 16.50 | 0.00 | 322.50 |
June | 398.00 | 0.50 | 0.48 | 01-JUN-07:19 | 2156.27 | 12.04 | 0.00 | 358.33 | 1222.57 | 16.62 | 0.00 | 312.67 |
July | 400.17 | 0.51 | 0.48 | 01-JUL-07:30 | 2002.90 | 12.37 | 3.67 | 361.50 | 1090.09 | 16.65 | 0.00 | 300.83 |
August | 377.83 | 0.51 | 0.48 | 01-AUG-07:30 | 2001.28 | 15.68 | 57.17 | 332.17 | 1046.75 | 16.75 | 3.67 | 287.00 |
September | 365.83 | 0.52 | 0.48 | 01-SEP-08:39 | 2463.84 | 19.38 | 110.17 | 296.83 | 932.94 | 19.61 | 55.83 | 254.17 |
October | 318.83 | 0.51 | 0.48 | 01-OCT-08:20 | 2060.54 | 19.06 | 86.17 | 283.33 | 1110.90 | 21.80 | 69.00 | 232.00 |
November | 295.83 | 0.53 | 0.48 | 01-NOV-12:39 | 1570.24 | 19.06 | 82.33 | 239.17 | 769.58 | 20.40 | 54.00 | 183.67 |
December | 289.50 | 0.53 | 0.48 | 01-DEC-09:09 | 1626.80 | 19.03 | 82.83 | 237.33 | 687.68 | 21.04 | 52.00 | 176.17 |
Annual Sum or Average | 4125.67 | 0.51 | 2098.15 | 16.85 | 796.50 | 3566.17 | 1006.92 | 19.01 | 452.50 | 2968.67 | ||
Minimum of Months | 268.33 | 0.50 | 0.48 | 1570.24 | 11.97 | 0.00 | 232.83 | 687.68 | 16.50 | 0.00 | 175.00 | |
Maximum of Months | 408.83 | 0.53 | 0.48 | 2803.48 | 19.93 | 111.83 | 361.50 | 1222.57 | 21.99 | 69.00 | 322.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157156E+10 | 9476.78 | 12-JAN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141983E+10 | 9496.03 | 13-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125310E+10 | 9456.29 | 01-MAR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435280E+09 | 9627.44 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92727691.01 | 9634.93 | 12-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 38554715.63 | 9487.84 | 25-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.294491E+09 | 9686.63 | 25-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.893047E+09 | 9620.85 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181106E+10 | 9474.72 | 12-DEC-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.780965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.181106E+10 | 9686.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111570E+09 | 6591.54 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45615514.13 | 6591.54 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28693153.00 | 6591.54 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4194754.15 | 6591.54 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115776E+09 | 6591.54 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305849E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.115776E+09 | 6591.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.354039E+09 | 8443.19 | 17-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.256924E+09 | 8450.44 | 28-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.128261E+09 | 8408.41 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 645454.53 | 788.26 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 19297701.55 | 8400.23 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366352E+09 | 8443.72 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.366352E+09 | 8450.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142042E+09 | 6539.00 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103818E+09 | 6539.00 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43353857.00 | 6539.00 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9065086.54 | 6539.00 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159144E+09 | 6539.00 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.457424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159144E+09 | 6539.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 5304469.74 | 16069.44 | 17-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17589610.67 | 22086.48 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22894080.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17589610.67 | 22086.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138765E+09 | 9974.45 | 17-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48444641.86 | 9914.60 | 15-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20550537.75 | 9917.53 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27367525.13 | 9951.10 | 30-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203466E+09 | 10053.32 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438594E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.203466E+09 | 10053.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.207817E+09 | 7239.09 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 56435588.32 | 7239.09 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24944827.46 | 7239.09 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45260250.82 | 7239.09 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.291716E+09 | 7239.09 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.626174E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.291716E+09 | 7239.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.360321E+09 | 8899.40 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147344E+09 | 8906.58 | 16-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 47602155.47 | 8871.83 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 81654847.94 | 8920.46 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.559208E+09 | 8936.13 | 04-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.559208E+09 | 8936.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.271345E+09 | 7190.17 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120955E+09 | 7190.17 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38925168.27 | 7190.17 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 70424441.20 | 7190.17 | 17-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387920E+09 | 7190.17 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.889569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.387920E+09 | 7190.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.632153E+09 | 31743.08 | 26-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.211392E+09 | 31590.95 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 46986933.72 | 31614.37 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193448E+09 | 31789.31 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106389E+10 | 31859.08 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106389E+10 | 31859.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.678844E+09 | 11694.62 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.348560E+09 | 11634.17 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219257E+09 | 11570.96 | 02-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16738651.27 | 11522.11 | 12-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1957905.29 | 4197.91 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.267823E+09 | 11647.37 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.860787E+09 | 11663.71 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.860787E+09 | 11694.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.681772E+09 | 9372.23 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292179E+09 | 9255.86 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156361E+09 | 9253.76 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1808200.05 | 4939.18 | 12-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4641480.49 | 6465.90 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.252323E+09 | 9333.44 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.900505E+09 | 9346.60 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.228959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.900505E+09 | 9372.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139725E+10 | 10549.31 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.735235E+09 | 10522.88 | 17-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.346869E+09 | 10529.38 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16881051.93 | 10394.16 | 12-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4373647.16 | 6975.67 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527668E+09 | 10507.17 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.187045E+10 | 10531.94 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.187045E+10 | 10549.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.965614E+09 | 9465.52 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.550528E+09 | 9465.52 | 01-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271034E+09 | 9465.52 | 01-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19306939.40 | 8697.10 | 12-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7498569.94 | 5231.62 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.407287E+09 | 9465.52 | 06-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124865E+10 | 9465.52 | 04-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.346991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124865E+10 | 9465.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.780765E+09 | 10409.04 | 27-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.525555E+09 | 11096.97 | 03-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275519E+09 | 8184.66 | 02-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1016445.01 | 1946.29 | 12-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150954E+09 | 6065.53 | 28-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145419E+10 | 11073.56 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145419E+10 | 11096.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146821E+10 | 11375.78 | 27-JAN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.931260E+09 | 12094.85 | 03-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.540259E+09 | 9188.63 | 02-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28744314.11 | 3553.22 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3253295.15 | 1026.99 | 25-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.492272E+09 | 7579.67 | 28-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231827E+10 | 12266.80 | 27-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.578227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.231827E+10 | 12266.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.193432E+10 | 13930.44 | 27-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125824E+10 | 14778.18 | 03-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.800825E+09 | 11719.31 | 02-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71425214.83 | 5347.91 | 12-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17452782.45 | 2600.37 | 25-OCT-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.734474E+09 | 9408.63 | 28-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.279496E+10 | 15067.35 | 27-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.761170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.279496E+10 | 15067.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.847725E+09 | 0.841076E+09 | 15455.25 | 03-JAN-15:00 | 15455.25 | 0.00 |
February | 0.00 | 0.00 | 0.306479E+10 | 0.305034E+10 | 26178.76 | 21-FEB-16:20 | 26178.76 | 0.00 |
March | 0.00 | 0.00 | 0.774080E+10 | 0.772584E+10 | 32885.03 | 21-MAR-16:00 | 32885.03 | 0.00 |
April | 0.00 | 0.00 | 0.240472E+11 | 0.238998E+11 | 52510.68 | 21-APR-15:10 | 52510.68 | 0.00 |
May | 0.00 | 0.00 | 0.473762E+11 | 0.462524E+11 | 64774.71 | 30-MAY-15:30 | 64774.71 | 0.00 |
June | 0.00 | 0.00 | 0.652113E+11 | 0.630277E+11 | 73042.57 | 19-JUN-06:03 | 59192.19 | 0.00 |
July | 0.00 | 0.00 | 0.769389E+11 | 0.625224E+11 | 112381.20 | 20-JUL-14:55 | 39343.94 | 0.00 |
August | 0.00 | 0.00 | 0.713783E+11 | 0.619752E+11 | 101175.16 | 08-AUG-06:03 | 68198.43 | 0.00 |
September | 0.00 | 0.00 | 0.591861E+11 | 0.517399E+11 | 90625.83 | 14-SEP-09:50 | 46700.35 | 0.00 |
October | 0.00 | 0.00 | 0.306367E+11 | 0.275291E+11 | 69516.89 | 04-OCT-10:40 | 44568.83 | 0.00 |
November | 0.00 | 0.00 | 0.679992E+10 | 0.667615E+10 | 38802.27 | 03-NOV-16:00 | 38802.27 | 0.00 |
December | 0.00 | 0.00 | 0.295073E+09 | 0.294017E+09 | 7085.30 | 08-DEC-14:00 | 7085.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.393523E+12 | 0.355534E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.295073E+09 | 0.294017E+09 | 7085.30 | 7085.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.769389E+11 | 0.630277E+11 | 112381.20 | 68198.43 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.687530E+09 | 0.680891E+09 | 11819.58 | 12-JAN-15:00 | 11819.58 | 0.00 |
February | 0.00 | 0.00 | 0.284906E+10 | 0.283550E+10 | 21772.37 | 21-FEB-16:20 | 21772.37 | 0.00 |
March | 0.00 | 0.00 | 0.706992E+10 | 0.706473E+10 | 29066.87 | 21-MAR-16:00 | 29066.87 | 0.00 |
April | 0.00 | 0.00 | 0.225663E+11 | 0.224576E+11 | 50276.07 | 21-APR-15:00 | 50276.07 | 0.00 |
May | 0.00 | 0.00 | 0.429759E+11 | 0.422453E+11 | 64664.32 | 30-MAY-06:03 | 64664.32 | 0.00 |
June | 0.00 | 0.00 | 0.591047E+11 | 0.577410E+11 | 70310.64 | 19-JUN-06:03 | 57678.95 | 0.00 |
July | 0.00 | 0.00 | 0.662169E+11 | 0.553064E+11 | 99968.37 | 20-JUL-14:55 | 35015.50 | 0.00 |
August | 0.00 | 0.00 | 0.586507E+11 | 0.525337E+11 | 81637.74 | 05-AUG-05:03 | 48932.07 | 0.00 |
September | 0.00 | 0.00 | 0.471915E+11 | 0.422986E+11 | 67988.38 | 14-SEP-09:40 | 36557.23 | 0.00 |
October | 0.00 | 0.00 | 0.241195E+11 | 0.219139E+11 | 59023.01 | 02-OCT-04:02 | 59023.01 | 0.00 |
November | 0.00 | 0.00 | 0.542200E+10 | 0.529494E+10 | 30985.21 | 09-NOV-15:20 | 30985.21 | 0.00 |
December | 0.00 | 0.00 | 0.247546E+09 | 0.246962E+09 | 5631.65 | 23-DEC-15:00 | 5631.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.337102E+12 | 0.310620E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.247546E+09 | 0.246962E+09 | 5631.65 | 5631.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.662169E+11 | 0.577410E+11 | 99968.37 | 64664.32 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.664385E+09 | 0.647862E+09 | 11705.64 | 03-JAN-14:50 | 11705.64 | 0.00 |
February | 0.00 | 0.00 | 0.280991E+10 | 0.278699E+10 | 25433.04 | 20-FEB-15:02 | 25433.04 | 0.00 |
March | 0.00 | 0.00 | 0.719581E+10 | 0.717698E+10 | 32197.15 | 21-MAR-16:00 | 32197.15 | 0.00 |
April | 0.00 | 0.00 | 0.248905E+11 | 0.247088E+11 | 59325.27 | 21-APR-14:40 | 59325.27 | 0.00 |
May | 0.00 | 0.00 | 0.480775E+11 | 0.470012E+11 | 72583.50 | 30-MAY-14:50 | 72583.50 | 0.00 |
June | 0.00 | 0.00 | 0.671635E+11 | 0.652803E+11 | 76402.71 | 15-JUN-14:40 | 76402.71 | 0.00 |
July | 0.00 | 0.00 | 0.742106E+11 | 0.622122E+11 | 115381.31 | 20-JUL-14:55 | 40401.26 | 0.00 |
August | 0.00 | 0.00 | 0.651789E+11 | 0.578811E+11 | 78918.12 | 07-AUG-04:02 | 78918.12 | 0.00 |
September | 0.00 | 0.00 | 0.516062E+11 | 0.458726E+11 | 77769.40 | 14-SEP-10:00 | 39690.28 | 0.00 |
October | 0.00 | 0.00 | 0.251698E+11 | 0.224934E+11 | 69122.15 | 03-OCT-14:00 | 61113.10 | 0.00 |
November | 0.00 | 0.00 | 0.497619E+10 | 0.478986E+10 | 31662.38 | 09-NOV-15:00 | 31662.38 | 0.00 |
December | 0.00 | 0.00 | 0.236402E+09 | 0.234443E+09 | 5686.74 | 23-DEC-15:00 | 5686.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.372180E+12 | 0.341086E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.236402E+09 | 0.234443E+09 | 5686.74 | 5686.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.742106E+11 | 0.652803E+11 | 115381.31 | 78918.12 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1699.68 | 5906.99 | 23-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1708.40 | 5908.63 | 03-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1757.99 | 5798.65 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1543.05 | 5434.15 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1480.95 | 5060.85 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1409.52 | 4667.97 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1237.54 | 4379.64 | 03-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1359.85 | 4363.40 | 29-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1331.88 | 4643.39 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1430.48 | 5067.10 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1567.70 | 5491.16 | 30-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1600.49 | 5784.80 | 29-DEC-12:06 |
Annual Sum or Average | 0.00 | 1509.52 | ||||
Minimum of Months | 0.00 | 0.00 | 1237.54 | 4363.40 | ||
Maximum of Months | 0.00 | 0.00 | 1757.99 | 5908.63 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165126E+10 | 0.32 | 2561.85 | 12-JAN-08:02 | 0.83 |
February | 0.165107E+10 | 0.34 | 3103.84 | 21-FEB-16:30 | 0.93 |
March | 0.218748E+10 | 0.37 | 3418.85 | 16-MAR-15:30 | 0.98 |
April | 0.307633E+10 | 0.43 | 6168.58 | 21-APR-15:10 | 1.38 |
May | 0.474981E+10 | 0.54 | 9473.23 | 30-MAY-12:07 | 1.81 |
June | 0.603856E+10 | 0.64 | 11261.98 | 05-JUN-12:20 | 2.01 |
July | 0.589420E+10 | 0.61 | 11531.79 | 03-JUL-04:02 | 2.04 |
August | 0.600306E+10 | 0.63 | 11531.79 | 05-AUG-06:03 | 2.03 |
September | 0.500145E+10 | 0.57 | 9512.42 | 05-SEP-06:02 | 1.80 |
October | 0.386829E+10 | 0.48 | 10979.92 | 02-OCT-06:03 | 1.97 |
November | 0.250502E+10 | 0.39 | 5088.34 | 09-NOV-16:40 | 1.23 |
December | 0.159014E+10 | 0.32 | 2701.38 | 12-DEC-08:03 | 0.86 |
Annual Sum or Average | 0.442167E+11 | 0.47 | |||
Minimum of Months | 0.159014E+10 | 0.32 | 2561.85 | 0.83 | |
Maximum of Months | 0.603856E+10 | 0.64 | 11531.79 | 2.04 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137962E+10 | 0.32 | 1745.57 | 12-JAN-15:40 | 0.74 |
February | 0.135315E+10 | 0.34 | 2502.70 | 21-FEB-16:30 | 0.90 |
March | 0.182600E+10 | 0.37 | 3928.48 | 16-MAR-15:30 | 1.16 |
April | 0.283390E+10 | 0.45 | 6449.50 | 21-APR-14:40 | 1.56 |
May | 0.449914E+10 | 0.57 | 9247.75 | 30-MAY-14:40 | 1.95 |
June | 0.588494E+10 | 0.68 | 10020.68 | 15-JUN-04:03 | 2.07 |
July | 0.555071E+10 | 0.64 | 10020.68 | 20-JUL-14:55 | 2.03 |
August | 0.549690E+10 | 0.64 | 10020.68 | 07-AUG-04:02 | 2.05 |
September | 0.421625E+10 | 0.55 | 7660.04 | 21-SEP-15:50 | 1.72 |
October | 0.283039E+10 | 0.44 | 8923.15 | 02-OCT-04:02 | 1.91 |
November | 0.170202E+10 | 0.36 | 3960.80 | 09-NOV-16:10 | 1.16 |
December | 0.133052E+10 | 0.31 | 2327.54 | 04-DEC-07:01 | 0.86 |
Annual Sum or Average | 0.389035E+11 | 0.47 | |||
Minimum of Months | 0.133052E+10 | 0.31 | 1745.57 | 0.74 | |
Maximum of Months | 0.588494E+10 | 0.68 | 10020.68 | 2.07 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138748E+10 | 0.31 | 2387.21 | 02-JAN-07:01 | 0.79 |
February | 0.133427E+10 | 0.33 | 2387.21 | 01-FEB-07:01 | 0.79 |
March | 0.174041E+10 | 0.35 | 3697.00 | 16-MAR-15:30 | 1.01 |
April | 0.263568E+10 | 0.41 | 6534.21 | 21-APR-15:00 | 1.40 |
May | 0.425568E+10 | 0.51 | 9684.04 | 30-MAY-14:50 | 1.79 |
June | 0.582044E+10 | 0.61 | 9968.81 | 19-JUN-14:30 | 1.82 |
July | 0.543889E+10 | 0.57 | 11897.08 | 03-JUL-04:02 | 2.04 |
August | 0.523018E+10 | 0.57 | 11260.33 | 07-AUG-04:02 | 1.97 |
September | 0.395786E+10 | 0.49 | 7859.17 | 05-SEP-15:30 | 1.56 |
October | 0.252693E+10 | 0.39 | 8081.39 | 02-OCT-04:02 | 1.60 |
November | 0.158726E+10 | 0.33 | 3462.28 | 09-NOV-15:50 | 0.96 |
December | 0.136640E+10 | 0.31 | 2387.21 | 04-DEC-06:01 | 0.79 |
Annual Sum or Average | 0.372815E+11 | 0.43 | |||
Minimum of Months | 0.133427E+10 | 0.31 | 2387.21 | 0.79 | |
Maximum of Months | 0.582044E+10 | 0.61 | 11897.08 | 2.04 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:10 | 0.22 | 0.22 | 56.59 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:02 | 0.22 | 0.22 | 55.96 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:02 | 0.22 | 0.22 | 56.01 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:05 | 0.22 | 0.22 | 56.18 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 56.34 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 57.26 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 57.37 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 57.12 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 57.13 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.25 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 56.96 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:03 | 0.22 | 0.22 | 56.81 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.96 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.37 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 56.69 | 56.69 | 1699.68 | 5906.99 | 23-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.35 | 56.35 | 1708.40 | 5908.63 | 03-FEB-12:08 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.43 | 56.43 | 1757.99 | 5798.65 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.68 | 56.68 | 1543.05 | 5434.15 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.64 | 56.64 | 1480.95 | 5060.85 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.56 | 57.56 | 1409.52 | 4667.97 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.64 | 57.64 | 1237.54 | 4379.64 | 03-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.35 | 57.35 | 1359.85 | 4363.40 | 29-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.40 | 57.40 | 1331.88 | 4643.39 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.68 | 56.68 | 1430.48 | 5067.10 | 31-OCT-11:30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.31 | 57.31 | 1567.70 | 5491.16 | 30-NOV-12:07 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.25 | 57.25 | 1600.49 | 5784.80 | 29-DEC-12:06 |
Annual Sum or Average | 0.00 | 1509.52 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.35 | 56.35 | 1237.54 | 4363.40 | ||
Maximum of Months | 0.00 | 0.00 | 57.64 | 57.64 | 1757.99 | 5908.63 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.406421E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.428612E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.564320E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.970924E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.172801E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.245101E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.265647E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.248778E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.202336E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.117667E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.516387E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.412688E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.158226E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.406421E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.265647E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.255393E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.248507E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.379470E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.865282E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.157723E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.226380E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.233146E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.210660E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.163965E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.886768E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.333050E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.286134E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.131733E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.248507E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.233146E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.592950E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.423096E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.467386E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.915388E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.169637E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.249967E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.255071E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.226897E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.173910E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.891972E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.454922E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.737868E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.152384E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.423096E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.255071E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165126E+10 | 0.847725E+09 | 0.295998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165107E+10 | 0.306479E+10 | 0.235174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218748E+10 | 0.774080E+10 | 0.172893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.307633E+10 | 0.240472E+11 | 0.436942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.474981E+10 | 0.473762E+11 | 92727691.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.603856E+10 | 0.652113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.589420E+10 | 0.769389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.600306E+10 | 0.713783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.500145E+10 | 0.591861E+11 | 38554715.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.386829E+10 | 0.306367E+11 | 0.294491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250502E+10 | 0.679992E+10 | 0.107656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159014E+10 | 0.295073E+09 | 0.390652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.442167E+11 | 0.393523E+12 | 0.128864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159014E+10 | 0.295073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.603856E+10 | 0.769389E+11 | 0.390652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137962E+10 | 0.687530E+09 | 0.245176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135315E+10 | 0.284906E+10 | 0.130444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182600E+10 | 0.706992E+10 | 0.672281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283390E+10 | 0.225663E+11 | 28744314.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.449914E+10 | 0.429759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.588494E+10 | 0.591047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.555071E+10 | 0.662169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.549690E+10 | 0.586507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.421625E+10 | 0.471915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.283039E+10 | 0.241195E+11 | 3253295.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170202E+10 | 0.542200E+10 | 0.716979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133052E+10 | 0.247546E+09 | 0.377817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389035E+11 | 0.337102E+12 | 0.895563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133052E+10 | 0.247546E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.588494E+10 | 0.662169E+11 | 0.377817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138748E+10 | 0.664385E+09 | 0.628995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133427E+10 | 0.280991E+10 | 0.339614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174041E+10 | 0.719581E+10 | 0.184133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263568E+10 | 0.248905E+11 | 0.126160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425568E+10 | 0.480775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.582044E+10 | 0.671635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.543889E+10 | 0.742106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.523018E+10 | 0.651789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.395786E+10 | 0.516062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252693E+10 | 0.251698E+11 | 35924385.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158726E+10 | 0.497619E+10 | 0.238302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136640E+10 | 0.236402E+09 | 0.873923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372815E+11 | 0.372180E+12 | 0.228118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133427E+10 | 0.236402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.582044E+10 | 0.742106E+11 | 0.873923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165126E+10 | 0.00 | 0.00 | 0.00 | 0.233741E+09 | 0.217921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165107E+10 | 0.00 | 0.00 | 0.00 | 0.808865E+09 | 0.182619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218748E+10 | 0.00 | 0.00 | 0.00 | 0.200231E+10 | 0.145341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.307633E+10 | 0.00 | 0.00 | 0.00 | 0.619699E+10 | 0.435925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.474981E+10 | 0.00 | 0.00 | 0.00 | 0.124376E+11 | 92727691.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.603856E+10 | 0.00 | 0.00 | 0.00 | 0.184715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.589420E+10 | 0.00 | 0.00 | 0.00 | 0.206705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.600306E+10 | 0.00 | 0.00 | 0.00 | 0.188747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.500145E+10 | 0.00 | 0.00 | 0.00 | 0.151936E+11 | 38554715.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.386829E+10 | 0.00 | 0.00 | 0.00 | 0.760393E+10 | 0.294491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250502E+10 | 0.00 | 0.00 | 0.00 | 0.173325E+10 | 0.925605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159014E+10 | 0.00 | 0.00 | 0.00 | 84412361.71 | 0.245233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.442167E+11 | 0.00 | 0.00 | 0.00 | 0.104311E+12 | 0.969844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159014E+10 | 0.00 | 0.00 | 0.00 | 84412361.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.603856E+10 | 0.00 | 0.00 | 0.00 | 0.206705E+11 | 0.245233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137962E+10 | 0.00 | 0.00 | 0.00 | 0.190763E+09 | 0.983552E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135315E+10 | 0.00 | 0.00 | 0.00 | 0.758744E+09 | 0.373179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.182600E+10 | 0.00 | 0.00 | 0.00 | 0.183668E+10 | 0.132023E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283390E+10 | 0.00 | 0.00 | 0.00 | 0.581892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.449914E+10 | 0.00 | 0.00 | 0.00 | 0.112731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.588494E+10 | 0.00 | 0.00 | 0.00 | 0.167531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.555071E+10 | 0.00 | 0.00 | 0.00 | 0.177639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.549690E+10 | 0.00 | 0.00 | 0.00 | 0.155691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.421625E+10 | 0.00 | 0.00 | 0.00 | 0.121802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.283039E+10 | 0.00 | 0.00 | 0.00 | 0.603729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170202E+10 | 0.00 | 0.00 | 0.00 | 0.140377E+10 | 0.224707E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133052E+10 | 0.00 | 0.00 | 0.00 | 70920591.16 | 0.145990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.389035E+11 | 0.00 | 0.00 | 0.00 | 0.896565E+11 | 0.317336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133052E+10 | 0.00 | 0.00 | 0.00 | 70920591.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.588494E+10 | 0.00 | 0.00 | 0.00 | 0.177639E+11 | 0.145990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138748E+10 | 0.00 | 0.00 | 0.00 | 0.186387E+09 | 0.435563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133427E+10 | 0.00 | 0.00 | 0.00 | 0.758795E+09 | 0.213789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174041E+10 | 0.00 | 0.00 | 0.00 | 0.189295E+10 | 0.104051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263568E+10 | 0.00 | 0.00 | 0.00 | 0.646346E+10 | 54734842.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.425568E+10 | 0.00 | 0.00 | 0.00 | 0.127080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.582044E+10 | 0.00 | 0.00 | 0.00 | 0.191762E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.543889E+10 | 0.00 | 0.00 | 0.00 | 0.200682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.523018E+10 | 0.00 | 0.00 | 0.00 | 0.174595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.395786E+10 | 0.00 | 0.00 | 0.00 | 0.134331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252693E+10 | 0.00 | 0.00 | 0.00 | 0.637432E+10 | 18471602.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158726E+10 | 0.00 | 0.00 | 0.00 | 0.131342E+10 | 0.164855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136640E+10 | 0.00 | 0.00 | 0.00 | 68005466.40 | 0.594427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372815E+11 | 0.00 | 0.00 | 0.00 | 0.999024E+11 | 0.152001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133427E+10 | 0.00 | 0.00 | 0.00 | 68005466.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.582044E+10 | 0.00 | 0.00 | 0.00 | 0.200682E+11 | 0.594427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239455E+10 | 0.00 | 0.00 | 27217731.25 | 0.00 | 0.00 | 0.136596E+11 | 0.00 | 0.55 |
February | 0.123197E+10 | 0.00 | 0.00 | 26913131.24 | 0.00 | 0.00 | 0.134887E+11 | 0.00 | 0.66 |
March | 0.976501E+09 | 0.00 | 0.00 | 36685459.36 | 0.00 | 0.00 | 0.157396E+11 | 0.00 | 0.85 |
April | 0.663746E+09 | 0.148037E+09 | 0.00 | 34195123.82 | 27724031.20 | 0.00 | 0.103504E+11 | 0.00 | 0.86 |
May | 0.465532E+09 | 0.576663E+09 | 0.00 | 24813822.39 | 0.108099E+09 | 0.00 | 0.476784E+10 | 0.00 | 0.73 |
June | 0.197926E+09 | 0.191108E+10 | 0.00 | 13667395.03 | 0.109061E+09 | 0.00 | 0.117030E+10 | 0.00 | 0.54 |
July | 7141075.56 | 0.650768E+10 | 0.00 | 874337.58 | 0.420985E+09 | 0.00 | 43545573.09 | 0.00 | 0.50 |
August | 96478190.43 | 0.293366E+10 | 0.00 | 12218059.58 | 0.166039E+09 | 0.00 | 0.126789E+10 | 0.00 | 0.68 |
September | 0.337753E+09 | 0.186892E+10 | 0.00 | 19654181.58 | 0.234052E+09 | 0.00 | 0.282449E+10 | 0.00 | 0.70 |
October | 0.705390E+09 | 0.443530E+09 | 0.00 | 36567040.47 | 48582599.47 | 0.00 | 0.122917E+11 | 0.00 | 1.03 |
November | 0.146369E+10 | 0.00 | 0.00 | 37143697.09 | 0.00 | 0.00 | 0.166750E+11 | 0.00 | 0.87 |
December | 0.264664E+10 | 0.00 | 0.00 | 26037709.13 | 0.00 | 0.00 | 0.133878E+11 | 0.00 | 0.51 |
Annual Sum or Average | 0.111873E+11 | 0.143896E+11 | 0.00 | 0.295988E+09 | 0.111454E+10 | 0.00 | 0.105667E+12 | 0.00 | 0.71 |
Minimum of Months | 7141075.56 | 0.00 | 0.00 | 874337.58 | 0.00 | 0.00 | 43545573.09 | 0.00 | 0.50 |
Maximum of Months | 0.264664E+10 | 0.650768E+10 | 0.00 | 37143697.09 | 0.420985E+09 | 0.00 | 0.166750E+11 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.836818E+10 | 0.00 | 0.00 | 1582028.39 | 0.00 | 665814.81 | 0.227466E+10 | 0.00 | 0.36 |
February | 0.592057E+10 | 0.00 | 0.00 | 4511471.25 | 0.00 | 0.00 | 0.358558E+10 | 0.00 | 0.43 |
March | 0.483923E+10 | 0.00 | 0.00 | 10898913.54 | 0.00 | 0.00 | 0.600400E+10 | 0.00 | 0.54 |
April | 0.132215E+10 | 72462202.45 | 0.00 | 18358521.05 | 55125959.75 | 0.00 | 0.599268E+10 | 0.00 | 0.57 |
May | 0.659048E+09 | 0.345480E+09 | 0.00 | 17976026.29 | 0.116399E+09 | 0.00 | 0.315122E+10 | 0.00 | 0.51 |
June | 0.255798E+09 | 0.135636E+10 | 0.00 | 11308393.41 | 0.124525E+09 | 0.00 | 0.947575E+09 | 0.00 | 0.42 |
July | 14762353.13 | 0.440945E+10 | 0.00 | 1545910.66 | 0.412434E+09 | 0.00 | 54205154.97 | 0.00 | 0.40 |
August | 0.115199E+09 | 0.173570E+10 | 0.00 | 10980121.91 | 0.190136E+09 | 0.00 | 0.102171E+10 | 0.00 | 0.51 |
September | 0.381085E+09 | 0.108144E+10 | 0.00 | 14256166.86 | 0.187481E+09 | 0.00 | 0.178445E+10 | 0.00 | 0.50 |
October | 0.128131E+10 | 0.263303E+09 | 0.00 | 18725224.17 | 43264985.19 | 0.00 | 0.671837E+10 | 0.00 | 0.65 |
November | 0.532076E+10 | 0.00 | 0.00 | 9650820.82 | 0.00 | 0.00 | 0.524428E+10 | 0.00 | 0.50 |
December | 0.916940E+10 | 0.00 | 0.00 | 915953.75 | 0.00 | 1925659.06 | 0.157024E+10 | 0.00 | 0.34 |
Annual Sum or Average | 0.376475E+11 | 0.926420E+10 | 0.00 | 0.120710E+09 | 0.112937E+10 | 2591473.87 | 0.383490E+11 | 0.00 | 0.48 |
Minimum of Months | 14762353.13 | 0.00 | 0.00 | 915953.75 | 0.00 | 0.00 | 54205154.97 | 0.00 | 0.34 |
Maximum of Months | 0.916940E+10 | 0.440945E+10 | 0.00 | 18725224.17 | 0.412434E+09 | 1925659.06 | 0.671837E+10 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.908358E+10 | 0.00 | 0.00 | 353872.46 | 0.00 | 0.362768E+09 | 0.588610E+09 | 0.00 | 0.36 |
February | 0.706884E+10 | 0.00 | 0.00 | 1801034.52 | 0.00 | 95889276.90 | 0.187696E+10 | 0.00 | 0.43 |
March | 0.638046E+10 | 0.00 | 0.00 | 6266732.90 | 0.00 | 31857633.72 | 0.396995E+10 | 0.00 | 0.54 |
April | 0.203727E+10 | 44938318.05 | 0.00 | 15815536.89 | 23925375.58 | 0.00 | 0.478241E+10 | 0.00 | 0.58 |
May | 0.925536E+09 | 0.283884E+09 | 0.00 | 17794478.56 | 0.122344E+09 | 0.00 | 0.245860E+10 | 0.00 | 0.53 |
June | 0.227770E+09 | 0.122975E+10 | 0.00 | 11635899.70 | 0.105392E+09 | 0.00 | 0.670487E+09 | 0.00 | 0.41 |
July | 13808326.48 | 0.454127E+10 | 0.00 | 1475592.41 | 0.572844E+09 | 0.00 | 27844489.43 | 0.00 | 0.39 |
August | 0.119188E+09 | 0.189321E+10 | 0.00 | 9631886.88 | 0.230091E+09 | 0.00 | 0.637056E+09 | 0.00 | 0.49 |
September | 0.524018E+09 | 0.117257E+10 | 0.00 | 11049572.25 | 0.330542E+09 | 0.00 | 0.110771E+10 | 0.00 | 0.48 |
October | 0.220869E+10 | 0.298760E+09 | 0.00 | 12414412.17 | 67401511.68 | 0.00 | 0.465395E+10 | 0.00 | 0.63 |
November | 0.661127E+10 | 0.00 | 0.00 | 4464155.85 | 2332244.02 | 81803246.35 | 0.290116E+10 | 0.00 | 0.48 |
December | 0.935218E+10 | 0.00 | 0.00 | 38042.53 | 0.00 | 0.508907E+09 | 0.206072E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.445526E+11 | 0.946437E+10 | 0.00 | 92741217.12 | 0.145487E+10 | 0.108123E+10 | 0.238808E+11 | 0.00 | 0.47 |
Minimum of Months | 13808326.48 | 0.00 | 0.00 | 38042.53 | 0.00 | 0.00 | 27844489.43 | 0.00 | 0.34 |
Maximum of Months | 0.935218E+10 | 0.454127E+10 | 0.00 | 17794478.56 | 0.572844E+09 | 0.508907E+09 | 0.478241E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657651E+09 | 0.00 | 0.00 | 0.36 |
February | 0.149244E+10 | 0.00 | 0.00 | 144334.06 | 0.00 | 0.323865E+09 | 83518375.39 | 0.00 | 0.42 |
March | 0.150968E+10 | 0.00 | 0.00 | 858652.86 | 0.00 | 0.181470E+09 | 0.472659E+09 | 0.00 | 0.54 |
April | 0.665515E+09 | 15599650.39 | 0.00 | 3327346.07 | 3741945.15 | 7225850.18 | 0.750024E+09 | 0.00 | 0.61 |
May | 0.230429E+09 | 95432443.14 | 0.00 | 4756925.02 | 22740638.90 | 0.00 | 0.524915E+09 | 0.00 | 0.64 |
June | 58459702.64 | 0.451796E+09 | 0.00 | 3377966.61 | 17773231.16 | 0.00 | 0.163444E+09 | 0.00 | 0.58 |
July | 4053830.25 | 0.140067E+10 | 0.00 | 425808.86 | 0.114725E+09 | 0.00 | 5717480.73 | 0.00 | 0.53 |
August | 35171310.37 | 0.537517E+09 | 0.00 | 2440234.33 | 48079064.53 | 0.00 | 0.142531E+09 | 0.00 | 0.60 |
September | 0.143198E+09 | 0.294484E+09 | 0.00 | 2523358.19 | 73916803.52 | 0.00 | 0.202213E+09 | 0.00 | 0.53 |
October | 0.755860E+09 | 76333083.01 | 0.00 | 1972300.05 | 14257522.44 | 1681631.60 | 0.609824E+09 | 0.00 | 0.62 |
November | 0.154436E+10 | 0.00 | 0.00 | 339865.54 | 491335.23 | 0.247600E+09 | 0.190678E+09 | 0.00 | 0.46 |
December | 0.122923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936844E+09 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.915076E+10 | 0.287183E+10 | 0.00 | 20166791.59 | 0.295725E+09 | 0.235634E+10 | 0.314552E+10 | 0.00 | 0.52 |
Minimum of Months | 4053830.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.154436E+10 | 0.140067E+10 | 0.00 | 4756925.02 | 0.114725E+09 | 0.936844E+09 | 0.750024E+09 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144834E+10 | 0.00 | 0.00 | 30605.41 | 0.00 | 0.306339E+09 | 56581033.65 | 0.00 | 0.48 |
February | 0.116701E+10 | 0.00 | 0.00 | 530104.51 | 0.00 | 0.104364E+09 | 0.394104E+09 | 0.00 | 0.59 |
March | 0.941777E+09 | 0.00 | 0.00 | 2357502.52 | 0.00 | 74067530.54 | 0.120515E+10 | 0.00 | 0.87 |
April | 0.317972E+09 | 15208584.32 | 0.00 | 5335868.85 | 1967274.61 | 726349.08 | 0.148578E+10 | 0.00 | 1.18 |
May | 0.124743E+09 | 95253028.94 | 0.00 | 6020622.52 | 13708293.10 | 0.00 | 0.897820E+09 | 0.00 | 1.20 |
June | 46261619.50 | 0.375782E+09 | 0.00 | 3524582.57 | 12457610.98 | 0.00 | 0.186161E+09 | 0.00 | 0.91 |
July | 3305376.32 | 0.130961E+10 | 0.00 | 361302.57 | 86532695.77 | 0.00 | 5597991.42 | 0.00 | 0.80 |
August | 27511923.10 | 0.561775E+09 | 0.00 | 2347231.21 | 32231858.08 | 0.00 | 0.143995E+09 | 0.00 | 0.96 |
September | 91487143.23 | 0.400433E+09 | 0.00 | 3092366.32 | 40143255.86 | 0.00 | 0.331758E+09 | 0.00 | 1.00 |
October | 0.484263E+09 | 65760272.63 | 0.00 | 2831838.66 | 10929237.70 | 1090964.85 | 0.101891E+10 | 0.00 | 1.03 |
November | 0.108692E+10 | 0.00 | 0.00 | 1008780.02 | 419666.97 | 0.127245E+09 | 0.576187E+09 | 0.00 | 0.68 |
December | 0.135618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465137E+09 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.709577E+10 | 0.282383E+10 | 0.00 | 27440805.14 | 0.198390E+09 | 0.107897E+10 | 0.630205E+10 | 0.00 | 0.85 |
Minimum of Months | 3305376.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.144834E+10 | 0.130961E+10 | 0.00 | 6020622.52 | 86532695.77 | 0.465137E+09 | 0.148578E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.952607E+09 | 0.00 | 0.00 | 5051502.43 | 0.00 | 0.275327E+09 | 0.255779E+10 | 0.00 | 0.66 |
February | 0.850063E+09 | 0.00 | 0.00 | 4879824.91 | 0.00 | 0.143296E+09 | 0.241903E+10 | 0.00 | 0.79 |
March | 0.931362E+09 | 0.00 | 0.00 | 5848644.07 | 0.00 | 0.114264E+09 | 0.272846E+10 | 0.00 | 0.99 |
April | 0.548234E+09 | 30270011.54 | 0.00 | 6061260.17 | 1725346.25 | 7066949.42 | 0.147682E+10 | 0.00 | 0.88 |
May | 0.269446E+09 | 0.110067E+09 | 0.00 | 5084548.07 | 23859689.39 | 0.00 | 0.564680E+09 | 0.00 | 0.69 |
June | 70969171.42 | 0.442248E+09 | 0.00 | 3208836.77 | 20762344.80 | 0.00 | 0.147544E+09 | 0.00 | 0.56 |
July | 4320942.64 | 0.138253E+10 | 0.00 | 448690.96 | 0.132617E+09 | 0.00 | 5868996.24 | 0.00 | 0.53 |
August | 39900098.87 | 0.623154E+09 | 0.00 | 2973088.70 | 52463628.60 | 0.00 | 0.167679E+09 | 0.00 | 0.70 |
September | 0.108887E+09 | 0.470424E+09 | 0.00 | 4782524.71 | 66022930.18 | 0.00 | 0.410477E+09 | 0.00 | 0.80 |
October | 0.473416E+09 | 0.141798E+09 | 0.00 | 8003211.98 | 6340662.85 | 350917.42 | 0.234119E+10 | 0.00 | 1.32 |
November | 0.851816E+09 | 0.00 | 0.00 | 7121913.03 | 523709.97 | 0.132288E+09 | 0.331920E+10 | 0.00 | 1.11 |
December | 0.988726E+09 | 0.00 | 0.00 | 4393144.09 | 0.00 | 0.330958E+09 | 0.223259E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.608975E+10 | 0.320049E+10 | 0.00 | 57857189.89 | 0.304315E+09 | 0.100355E+10 | 0.183713E+11 | 0.00 | 0.80 |
Minimum of Months | 4320942.64 | 0.00 | 0.00 | 448690.96 | 0.00 | 0.00 | 5868996.24 | 0.00 | 0.53 |
Maximum of Months | 0.988726E+09 | 0.138253E+10 | 0.00 | 8003211.98 | 0.132617E+09 | 0.330958E+09 | 0.331920E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128931E+10 | 0.00 | 0.00 | 424781.99 | 0.00 | 0.496388E+09 | 0.347468E+09 | 0.00 | 0.57 |
February | 0.126029E+10 | 0.00 | 0.00 | 754183.45 | 0.00 | 0.255102E+09 | 0.447767E+09 | 0.00 | 0.70 |
March | 0.128393E+10 | 0.00 | 0.00 | 2332208.27 | 0.00 | 0.144998E+09 | 0.107570E+10 | 0.00 | 1.02 |
April | 0.620633E+09 | 20416487.67 | 0.00 | 4375771.17 | 844917.40 | 8187475.59 | 0.966907E+09 | 0.00 | 1.07 |
May | 0.266850E+09 | 99010515.75 | 0.00 | 4426355.20 | 16384301.98 | 0.00 | 0.417455E+09 | 0.00 | 0.94 |
June | 68520793.45 | 0.417260E+09 | 0.00 | 2645123.30 | 15823471.34 | 0.00 | 0.112982E+09 | 0.00 | 0.76 |
July | 4339701.06 | 0.110538E+10 | 0.00 | 354896.35 | 0.137595E+09 | 0.00 | 4041870.32 | 0.00 | 0.69 |
August | 41765329.30 | 0.446760E+09 | 0.00 | 2149255.04 | 54471399.40 | 0.00 | 0.106745E+09 | 0.00 | 0.83 |
September | 0.132360E+09 | 0.259247E+09 | 0.00 | 3004719.43 | 76204644.65 | 0.00 | 0.229205E+09 | 0.00 | 0.82 |
October | 0.700648E+09 | 78110011.36 | 0.00 | 2925563.60 | 11660383.59 | 1703897.29 | 0.832077E+09 | 0.00 | 1.12 |
November | 0.128797E+10 | 0.00 | 0.00 | 1347830.51 | 480447.39 | 0.211362E+09 | 0.724827E+09 | 0.00 | 0.86 |
December | 0.117984E+10 | 0.00 | 0.00 | 235242.58 | 0.00 | 0.669478E+09 | 0.252654E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.813645E+10 | 0.242618E+10 | 0.00 | 24975930.88 | 0.313465E+09 | 0.178722E+10 | 0.551783E+10 | 0.00 | 0.82 |
Minimum of Months | 4339701.06 | 0.00 | 0.00 | 235242.58 | 0.00 | 0.00 | 4041870.32 | 0.00 | 0.53 |
Maximum of Months | 0.128931E+10 | 0.110538E+10 | 0.00 | 4426355.20 | 0.137595E+09 | 0.669478E+09 | 0.107570E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232249E+09 | 0.00 | 0.00 | 0.37 |
February | 0.184436E+10 | 0.00 | 0.00 | 2079.87 | 0.00 | 0.159151E+09 | 4373736.94 | 0.00 | 0.42 |
March | 0.195959E+10 | 0.00 | 0.00 | 76089.44 | 0.00 | 94152108.27 | 55855782.64 | 0.00 | 0.49 |
April | 0.912202E+09 | 16507063.70 | 0.00 | 1280363.14 | 13070159.33 | 0.00 | 0.316313E+09 | 0.00 | 0.47 |
May | 0.335789E+09 | 0.108105E+09 | 0.00 | 2188984.72 | 19842607.78 | 0.00 | 0.314177E+09 | 0.00 | 0.47 |
June | 0.104051E+09 | 0.428003E+09 | 0.00 | 1819556.26 | 25852150.64 | 0.00 | 0.111116E+09 | 0.00 | 0.46 |
July | 4544097.81 | 0.126694E+10 | 0.00 | 76078.24 | 0.134815E+09 | 0.00 | 3784404.46 | 0.00 | 0.46 |
August | 55037225.13 | 0.583652E+09 | 0.00 | 1669747.35 | 52017884.70 | 0.00 | 0.150476E+09 | 0.00 | 0.58 |
September | 0.179054E+09 | 0.355512E+09 | 0.00 | 2255280.63 | 56538731.28 | 0.00 | 0.264258E+09 | 0.00 | 0.54 |
October | 0.670666E+09 | 80713464.56 | 0.00 | 2700119.26 | 12691369.32 | 0.00 | 0.899022E+09 | 0.00 | 0.64 |
November | 0.183294E+10 | 0.00 | 0.00 | 531556.76 | 0.00 | 11707857.01 | 0.360473E+09 | 0.00 | 0.48 |
December | 0.209889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293662E+09 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.121093E+11 | 0.283943E+10 | 0.00 | 12599855.67 | 0.314828E+09 | 0.790922E+09 | 0.247985E+10 | 0.00 | 0.48 |
Minimum of Months | 4544097.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.211221E+10 | 0.126694E+10 | 0.00 | 2700119.26 | 0.134815E+09 | 0.293662E+09 | 0.899022E+09 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154757E+10 | 0.00 | 0.00 | 84480.61 | 0.00 | 72613450.14 | 0.126682E+09 | 0.00 | 0.43 |
February | 0.117359E+10 | 0.00 | 0.00 | 465907.31 | 0.00 | 25850320.03 | 0.340050E+09 | 0.00 | 0.51 |
March | 0.962047E+09 | 0.00 | 0.00 | 1665789.74 | 0.00 | 16110666.73 | 0.839461E+09 | 0.00 | 0.68 |
April | 0.331424E+09 | 22759707.46 | 0.00 | 3698917.38 | 4341608.99 | 0.00 | 0.111685E+10 | 0.00 | 0.88 |
May | 0.154906E+09 | 0.112833E+09 | 0.00 | 3858193.42 | 9942959.34 | 0.00 | 0.700912E+09 | 0.00 | 0.92 |
June | 69313888.46 | 0.390170E+09 | 0.00 | 2265771.23 | 12778318.42 | 0.00 | 0.147487E+09 | 0.00 | 0.75 |
July | 1574810.47 | 0.121594E+10 | 0.00 | 111765.88 | 69512962.62 | 0.00 | 6717405.84 | 0.00 | 0.70 |
August | 37585280.06 | 0.593800E+09 | 0.00 | 1785703.95 | 23015028.59 | 0.00 | 0.163978E+09 | 0.00 | 0.91 |
September | 99437237.99 | 0.399191E+09 | 0.00 | 3161508.00 | 28055438.61 | 0.00 | 0.440578E+09 | 0.00 | 0.98 |
October | 0.342119E+09 | 70795595.13 | 0.00 | 3949898.05 | 7309373.58 | 0.00 | 0.135993E+10 | 0.00 | 1.06 |
November | 0.931577E+09 | 0.00 | 0.00 | 2111482.91 | 0.00 | 990086.59 | 0.101888E+10 | 0.00 | 0.70 |
December | 0.158441E+10 | 0.00 | 0.00 | 61151.27 | 0.00 | 96574548.85 | 99603505.66 | 0.00 | 0.41 |
Annual Sum or Average | 0.723555E+10 | 0.280549E+10 | 0.00 | 23220569.74 | 0.154956E+09 | 0.212139E+09 | 0.636112E+10 | 0.00 | 0.75 |
Minimum of Months | 1574810.47 | 0.00 | 0.00 | 61151.27 | 0.00 | 0.00 | 6717405.84 | 0.00 | 0.41 |
Maximum of Months | 0.158441E+10 | 0.121594E+10 | 0.00 | 3949898.05 | 69512962.62 | 96574548.85 | 0.135993E+10 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134262E+10 | 0.00 | 0.00 | 1471779.63 | 0.00 | 0.725772E+09 | 0.955708E+09 | 0.00 | 0.50 |
February | 0.123498E+10 | 0.00 | 0.00 | 1384492.13 | 0.00 | 0.604091E+09 | 0.665406E+09 | 0.00 | 0.57 |
March | 0.140634E+10 | 0.00 | 0.00 | 1646041.02 | 0.00 | 0.533504E+09 | 0.611282E+09 | 0.00 | 0.63 |
April | 0.785439E+09 | 50851362.12 | 0.00 | 2749864.52 | 4887298.95 | 0.172084E+09 | 0.434019E+09 | 0.00 | 0.59 |
May | 0.388657E+09 | 0.162572E+09 | 0.00 | 2276167.52 | 19606987.04 | 49130283.68 | 0.219503E+09 | 0.00 | 0.53 |
June | 0.132479E+09 | 0.559941E+09 | 0.00 | 1702728.13 | 27162830.53 | 0.00 | 65567928.81 | 0.00 | 0.50 |
July | 6253582.61 | 0.139849E+10 | 0.00 | 17360.07 | 0.181979E+09 | 0.00 | 535365.02 | 0.00 | 0.50 |
August | 77639497.59 | 0.809942E+09 | 0.00 | 1713382.36 | 55308204.17 | 0.00 | 0.121547E+09 | 0.00 | 0.68 |
September | 0.177105E+09 | 0.602649E+09 | 0.00 | 4007130.86 | 53021122.32 | 17344174.04 | 0.367433E+09 | 0.00 | 0.79 |
October | 0.473660E+09 | 0.168033E+09 | 0.00 | 7545720.48 | 4427302.42 | 0.126352E+09 | 0.193352E+10 | 0.00 | 1.20 |
November | 0.945425E+09 | 0.00 | 0.00 | 5737238.61 | 0.00 | 0.375525E+09 | 0.251581E+10 | 0.00 | 0.97 |
December | 0.127865E+10 | 0.00 | 0.00 | 1343065.18 | 0.00 | 0.866120E+09 | 0.940031E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.824924E+10 | 0.375248E+10 | 0.00 | 31594970.50 | 0.346393E+09 | 0.346992E+10 | 0.883037E+10 | 0.00 | 0.66 |
Minimum of Months | 6253582.61 | 0.00 | 0.00 | 17360.07 | 0.00 | 0.00 | 535365.02 | 0.00 | 0.46 |
Maximum of Months | 0.140634E+10 | 0.139849E+10 | 0.00 | 7545720.48 | 0.181979E+09 | 0.866120E+09 | 0.251581E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150195E+10 | 0.00 | 0.00 | 370161.33 | 0.00 | 0.115921E+09 | 0.285228E+09 | 0.00 | 0.48 |
February | 0.130914E+10 | 0.00 | 0.00 | 434462.08 | 0.00 | 72651365.83 | 0.251095E+09 | 0.00 | 0.55 |
March | 0.131143E+10 | 0.00 | 0.00 | 1301285.16 | 0.00 | 25252681.53 | 0.510550E+09 | 0.00 | 0.72 |
April | 0.538235E+09 | 28396538.50 | 0.00 | 2697847.22 | 3726314.89 | 0.00 | 0.626868E+09 | 0.00 | 0.75 |
May | 0.232929E+09 | 0.130178E+09 | 0.00 | 2340450.80 | 9526267.01 | 0.00 | 0.325493E+09 | 0.00 | 0.71 |
June | 77620788.69 | 0.442267E+09 | 0.00 | 1496056.41 | 11412372.45 | 0.00 | 88299494.10 | 0.00 | 0.63 |
July | 1671265.90 | 0.111266E+10 | 0.00 | 64792.37 | 83144843.66 | 0.00 | 4518617.38 | 0.00 | 0.60 |
August | 39221138.61 | 0.549266E+09 | 0.00 | 1376670.16 | 28475199.91 | 0.00 | 0.118509E+09 | 0.00 | 0.79 |
September | 0.101153E+09 | 0.352316E+09 | 0.00 | 2584701.36 | 34792341.25 | 0.00 | 0.301261E+09 | 0.00 | 0.80 |
October | 0.364683E+09 | 84940290.49 | 0.00 | 3841264.46 | 6532513.01 | 0.00 | 0.114485E+10 | 0.00 | 1.05 |
November | 0.111855E+10 | 0.00 | 0.00 | 1848074.80 | 0.00 | 5123687.48 | 0.935361E+09 | 0.00 | 0.77 |
December | 0.151743E+10 | 0.00 | 0.00 | 312166.50 | 0.00 | 0.129932E+09 | 0.280063E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.811401E+10 | 0.270002E+10 | 0.00 | 18667932.65 | 0.177610E+09 | 0.348880E+09 | 0.487210E+10 | 0.00 | 0.69 |
Minimum of Months | 1671265.90 | 0.00 | 0.00 | 64792.37 | 0.00 | 0.00 | 4518617.38 | 0.00 | 0.45 |
Maximum of Months | 0.151743E+10 | 0.111266E+10 | 0.00 | 3841264.46 | 83144843.66 | 0.129932E+09 | 0.114485E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197268E+10 | 0.00 | 0.00 | 4461.40 | 0.00 | 0.253330E+09 | 19940462.43 | 0.00 | 0.36 |
February | 0.172670E+10 | 0.00 | 0.00 | 186296.48 | 0.00 | 0.105514E+09 | 0.128610E+09 | 0.00 | 0.42 |
March | 0.163001E+10 | 0.00 | 0.00 | 1073275.67 | 0.00 | 30632979.46 | 0.512556E+09 | 0.00 | 0.52 |
April | 0.604052E+09 | 26870953.14 | 0.00 | 3281001.45 | 8265692.47 | 0.00 | 0.831708E+09 | 0.00 | 0.57 |
May | 0.209098E+09 | 0.125546E+09 | 0.00 | 4270109.39 | 20340450.08 | 0.00 | 0.604008E+09 | 0.00 | 0.61 |
June | 79451322.05 | 0.523734E+09 | 0.00 | 3080671.89 | 17701292.26 | 0.00 | 0.207640E+09 | 0.00 | 0.60 |
July | 4690095.32 | 0.136587E+10 | 0.00 | 373820.84 | 87747596.09 | 0.00 | 10734754.00 | 0.00 | 0.55 |
August | 43285101.13 | 0.513166E+09 | 0.00 | 2581385.56 | 37848836.31 | 0.00 | 0.205151E+09 | 0.00 | 0.62 |
September | 0.156700E+09 | 0.288631E+09 | 0.00 | 2621410.80 | 39907365.76 | 0.00 | 0.260623E+09 | 0.00 | 0.53 |
October | 0.667293E+09 | 70614178.85 | 0.00 | 2570395.53 | 9202910.48 | 0.00 | 0.802870E+09 | 0.00 | 0.61 |
November | 0.171083E+10 | 0.00 | 0.00 | 527751.65 | 0.00 | 54923938.56 | 0.312205E+09 | 0.00 | 0.46 |
December | 0.185344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421228E+09 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.106582E+11 | 0.291443E+10 | 0.00 | 20570580.67 | 0.221014E+09 | 0.865630E+09 | 0.389605E+10 | 0.00 | 0.52 |
Minimum of Months | 4690095.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.197268E+10 | 0.136587E+10 | 0.00 | 4270109.39 | 87747596.09 | 0.421228E+09 | 0.831708E+09 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161240E+10 | 0.00 | 0.00 | 131903.96 | 0.00 | 0.144823E+09 | 0.151657E+09 | 0.00 | 0.48 |
February | 0.118688E+10 | 0.00 | 0.00 | 842614.58 | 0.00 | 34963863.64 | 0.545421E+09 | 0.00 | 0.60 |
March | 0.987970E+09 | 0.00 | 0.00 | 2678653.33 | 0.00 | 16133528.76 | 0.132614E+10 | 0.00 | 0.87 |
April | 0.300448E+09 | 26054817.64 | 0.00 | 5329504.61 | 4704834.69 | 0.00 | 0.159227E+10 | 0.00 | 1.12 |
May | 0.126841E+09 | 0.116580E+09 | 0.00 | 5478456.98 | 12663340.21 | 0.00 | 0.964343E+09 | 0.00 | 1.12 |
June | 59986996.93 | 0.420297E+09 | 0.00 | 3439901.93 | 12080604.27 | 0.00 | 0.236120E+09 | 0.00 | 0.92 |
July | 4162427.08 | 0.123521E+10 | 0.00 | 325827.26 | 60579450.55 | 0.00 | 10411951.02 | 0.00 | 0.80 |
August | 38339362.82 | 0.502199E+09 | 0.00 | 2408466.84 | 25562577.71 | 0.00 | 0.202521E+09 | 0.00 | 0.96 |
September | 0.103867E+09 | 0.335126E+09 | 0.00 | 3297135.24 | 25159346.50 | 0.00 | 0.423040E+09 | 0.00 | 0.98 |
October | 0.479936E+09 | 55587613.35 | 0.00 | 3301522.57 | 7161584.83 | 0.00 | 0.115981E+10 | 0.00 | 1.00 |
November | 0.113046E+10 | 0.00 | 0.00 | 1523344.91 | 0.00 | 28520314.23 | 0.792589E+09 | 0.00 | 0.70 |
December | 0.164365E+10 | 0.00 | 0.00 | 41969.60 | 0.00 | 0.222055E+09 | 59242359.60 | 0.00 | 0.45 |
Annual Sum or Average | 0.767495E+10 | 0.269105E+10 | 0.00 | 28799301.84 | 0.147912E+09 | 0.446495E+09 | 0.746357E+10 | 0.00 | 0.83 |
Minimum of Months | 4162427.08 | 0.00 | 0.00 | 41969.60 | 0.00 | 0.00 | 10411951.02 | 0.00 | 0.45 |
Maximum of Months | 0.164365E+10 | 0.123521E+10 | 0.00 | 5478456.98 | 60579450.55 | 0.222055E+09 | 0.159227E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103794E+10 | 0.00 | 0.00 | 6167678.73 | 0.00 | 0.108349E+09 | 0.299925E+10 | 0.00 | 0.71 |
February | 0.901971E+09 | 0.00 | 0.00 | 5645706.54 | 0.00 | 39608302.29 | 0.265488E+10 | 0.00 | 0.83 |
March | 0.938682E+09 | 0.00 | 0.00 | 6398209.87 | 0.00 | 12367498.57 | 0.273881E+10 | 0.00 | 0.97 |
April | 0.483527E+09 | 55861983.19 | 0.00 | 5686135.25 | 3541295.47 | 0.00 | 0.146583E+10 | 0.00 | 0.81 |
May | 0.237960E+09 | 0.150001E+09 | 0.00 | 4466526.62 | 19108455.90 | 0.00 | 0.607688E+09 | 0.00 | 0.65 |
June | 81932532.93 | 0.521918E+09 | 0.00 | 2880398.56 | 18388865.10 | 0.00 | 0.186943E+09 | 0.00 | 0.57 |
July | 5667070.27 | 0.136434E+10 | 0.00 | 382731.01 | 88900069.80 | 0.00 | 9010032.12 | 0.00 | 0.54 |
August | 41412742.55 | 0.612611E+09 | 0.00 | 3050924.06 | 37088276.32 | 0.00 | 0.231638E+09 | 0.00 | 0.71 |
September | 0.117292E+09 | 0.464932E+09 | 0.00 | 4573288.60 | 36970158.72 | 0.00 | 0.454110E+09 | 0.00 | 0.78 |
October | 0.409189E+09 | 0.134273E+09 | 0.00 | 8520945.75 | 4761455.44 | 0.00 | 0.237954E+10 | 0.00 | 1.25 |
November | 0.839109E+09 | 0.00 | 0.00 | 8612557.33 | 0.00 | 18238668.29 | 0.356484E+10 | 0.00 | 1.14 |
December | 0.110880E+10 | 0.00 | 0.00 | 5579166.08 | 0.00 | 0.157238E+09 | 0.272458E+10 | 0.00 | 0.64 |
Annual Sum or Average | 0.620348E+10 | 0.330394E+10 | 0.00 | 61964268.39 | 0.208759E+09 | 0.335802E+09 | 0.200171E+11 | 0.00 | 0.80 |
Minimum of Months | 5667070.27 | 0.00 | 0.00 | 382731.01 | 0.00 | 0.00 | 9010032.12 | 0.00 | 0.54 |
Maximum of Months | 0.110880E+10 | 0.136434E+10 | 0.00 | 8612557.33 | 88900069.80 | 0.157238E+09 | 0.356484E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154152E+10 | 0.00 | 0.00 | 586361.52 | 0.00 | 0.195425E+09 | 0.405884E+09 | 0.00 | 0.55 |
February | 0.136585E+10 | 0.00 | 0.00 | 877574.87 | 0.00 | 88210081.64 | 0.474475E+09 | 0.00 | 0.67 |
March | 0.127262E+10 | 0.00 | 0.00 | 2495988.57 | 0.00 | 23192857.49 | 0.105049E+10 | 0.00 | 0.94 |
April | 0.532905E+09 | 39321191.08 | 0.00 | 4020971.73 | 2167586.99 | 0.00 | 0.955332E+09 | 0.00 | 0.95 |
May | 0.230227E+09 | 0.140695E+09 | 0.00 | 3597903.33 | 11037539.79 | 0.00 | 0.447138E+09 | 0.00 | 0.86 |
June | 74981141.12 | 0.509596E+09 | 0.00 | 2292539.64 | 11411040.83 | 0.00 | 0.142732E+09 | 0.00 | 0.77 |
July | 5547621.33 | 0.111663E+10 | 0.00 | 279799.30 | 78737187.97 | 0.00 | 5842786.65 | 0.00 | 0.69 |
August | 45157169.43 | 0.447817E+09 | 0.00 | 2167838.31 | 31177910.28 | 0.00 | 0.148524E+09 | 0.00 | 0.83 |
September | 0.141455E+09 | 0.262740E+09 | 0.00 | 2808190.76 | 33683737.27 | 0.00 | 0.250383E+09 | 0.00 | 0.78 |
October | 0.550031E+09 | 73349816.40 | 0.00 | 3215526.47 | 6520131.43 | 0.00 | 0.935832E+09 | 0.00 | 1.02 |
November | 0.136777E+10 | 0.00 | 0.00 | 1606016.96 | 0.00 | 37294558.61 | 0.777031E+09 | 0.00 | 0.82 |
December | 0.149725E+10 | 0.00 | 0.00 | 390015.95 | 0.00 | 0.298035E+09 | 0.321370E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.862532E+10 | 0.259015E+10 | 0.00 | 24338727.40 | 0.174735E+09 | 0.642158E+09 | 0.591504E+10 | 0.00 | 0.78 |
Minimum of Months | 5547621.33 | 0.00 | 0.00 | 279799.30 | 0.00 | 0.00 | 5842786.65 | 0.00 | 0.50 |
Maximum of Months | 0.154152E+10 | 0.111663E+10 | 0.00 | 4020971.73 | 78737187.97 | 0.298035E+09 | 0.105049E+10 | 0.00 | 1.02 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:18
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.218598E+12 | 0.675359E+10 | 0.00 | 0.183884E+12 | 0.385635E+10 |
February | 0.221308E+12 | 0.539451E+10 | 0.00 | 0.158409E+12 | 0.117289E+11 |
March | 0.315901E+12 | 0.531817E+10 | 0.00 | 0.196716E+12 | 0.281426E+11 |
April | 0.323182E+12 | 0.233950E+10 | 0.00 | 0.150993E+12 | 0.900086E+11 |
May | 0.334838E+12 | 0.454686E+09 | 0.00 | 0.104105E+12 | 0.174848E+12 |
June | 0.323097E+12 | -0.139929E+10 | 0.00 | 0.156275E+11 | 0.245880E+12 |
July | 0.321362E+12 | -0.286846E+10 | 0.00 | -0.884786E+11 | 0.275869E+12 |
August | 0.300399E+12 | -0.147310E+10 | 0.00 | -0.180278E+11 | 0.247111E+12 |
September | 0.284688E+12 | -437502432.6 | 0.00 | 0.114583E+11 | 0.198791E+12 |
October | 0.265679E+12 | 0.213232E+10 | 0.00 | 0.145657E+12 | 0.999467E+11 |
November | 0.220580E+12 | 0.523060E+10 | 0.00 | 0.202215E+12 | 0.219930E+11 |
December | 0.189315E+12 | 0.672852E+10 | 0.00 | 0.170217E+12 | 0.264422E+10 |
Annual Sum or Average | 0.331895E+13 | 0.281735E+11 | 0.00 | 0.123278E+13 | 0.140082E+13 |
Minimum of Months | 0.189315E+12 | -0.286846E+10 | 0.00 | -0.884786E+11 | 0.264422E+10 |