Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 08:35:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1674.00 | 336.00 | 336.00 |
Net Site Energy | 1674.00 | 336.00 | 336.00 |
Total Source Energy | 5104.57 | 1024.57 | 1024.57 |
Net Source Energy | 5104.57 | 1024.57 | 1024.57 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 14.44 | 0.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 505.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 202.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 79.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 10.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 93.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1579.43 | 94.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 14.44 | 0.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 505.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 202.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 49.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 79.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 10.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 93.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 14.44 | 0.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 505.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 202.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 49.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 79.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 10.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 93.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 120.33 | 18.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 146.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 317.02 | 18.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 120.33 | 18.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 146.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 317.02 | 18.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1579.434 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1579.434 | 100.00 |
Total On-Site and Utility Electric Sources | 1579.434 | 100.00 |
Total Electricity End Uses | 1579.434 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 106.88 | 99.73 |
Air to Air Heat Recovery for Heating | 0.29 | 0.27 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 107.17 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 74.83 |
Time Setpoint Not Met During Occupied Cooling | 302.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1439.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.9322 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.9322 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.9322 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 30-AUG-15:00 | 05-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 06-JAN-12:09 |
Heating | 0.00 | 10614.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71749.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 16818.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42072.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 827.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13343.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 907.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 6560.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 145720.01 | 17174.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 10614.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 71749.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 16818.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 827.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13343.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 907.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 6560.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 45.72 | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1600.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 641.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 157.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 252.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 32.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 101.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5002.07 | 102.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 9.18 | 0.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 321.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 128.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 50.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 6.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1003.99 | 20.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 9.18 | 0.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 321.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 128.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 50.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 6.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1003.99 | 20.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.71 | 0.276972 | 0.283000 | 0.765766 | 0.738592 | 0.500000 | 0.001376 |
CORE_MID VAV BOX COMPONENT | 1.95 | 0.384886 | 0.372000 | 0.724363 | 1.00 | 0.500000 | 0.000990 |
CORE_TOP VAV BOX COMPONENT | 2.08 | 0.361070 | 0.367000 | 0.761764 | 0.962853 | 0.500000 | 0.001055 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.639568 | 0.247029 | 0.251000 | 0.160531 | 0.658744 | 0.500000 | 0.001542 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.643616 | 0.155406 | 0.200000 | 0.128723 | 0.414416 | 0.500000 | 0.002452 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.782706 | 0.201853 | 0.205000 | 0.160455 | 0.538275 | 0.500000 | 0.001888 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.712769 | 0.140319 | 0.200000 | 0.142554 | 0.374185 | 0.500000 | 0.002715 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.550143 | 0.287183 | 0.293000 | 0.161192 | 0.765822 | 0.500000 | 0.001327 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.575143 | 0.173908 | 0.200000 | 0.115029 | 0.463754 | 0.500000 | 0.002191 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.677048 | 0.233354 | 0.238000 | 0.161137 | 0.622277 | 0.500000 | 0.001633 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.597278 | 0.167452 | 0.200000 | 0.119456 | 0.446538 | 0.500000 | 0.002275 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.547782 | 0.288421 | 0.279000 | 0.152831 | 0.769122 | 0.500000 | 0.001321 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.614839 | 0.162680 | 0.200000 | 0.122968 | 0.433812 | 0.500000 | 0.002342 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.685430 | 0.230500 | 0.223000 | 0.152851 | 0.614667 | 0.500000 | 0.001653 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.639148 | 0.156482 | 0.200000 | 0.127830 | 0.417285 | 0.500000 | 0.002435 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25554.56 |
CORE_MID VAV BOX REHEAT COIL | 24172.87 |
CORE_TOP VAV BOX REHEAT COIL | 25420.98 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 10787.83 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7059.48 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 10749.26 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 7039.73 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6802.48 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4520.10 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6769.15 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4499.10 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 7881.01 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 5201.75 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 7841.23 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 5181.68 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.55 | 1.32 | 5.11 | 1.32 | 4.61 | 4.61 | 0.300000 | 0.286717 | 4.61 |
PACU_VAV_MID | 2.22 | 1.28 | 4.43 | 1.28 | 3.86 | 3.86 | 0.300000 | 0.331818 | 3.86 |
PACU_VAV_TOP | 2.43 | 1.35 | 4.85 | 1.82 | 4.55 | 4.55 | 0.300000 | 0.399937 | 4.55 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.61 |
PACU_VAV_MID_OA_CONTROLLER | 3.86 |
PACU_VAV_TOP_OA_CONTROLLER | 4.55 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.61 | 113387.02 | 0.704592 | 1.54 | 37791.89 | 0.704592 |
PACU_VAV_MID COOLING COIL | 3.86 | 95854.85 | 0.701083 | 1.29 | 31948.42 | 0.701083 |
PACU_VAV_TOP COOLING COIL | 4.55 | 112225.65 | 0.703862 | 1.52 | 37404.81 | 0.703862 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 10006.42 |
PACU_VAV_MID HEATING COIL | 11480.52 |
PACU_VAV_TOP HEATING COIL | 10158.79 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.61 |
PACU_VAV_MID FAN | 3.86 |
PACU_VAV_TOP FAN | 4.55 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_MID OA HEAT RECOVERY | 1.20 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 30.766 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.029 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.013 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.375 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7377 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7531 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4931 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
39 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
40 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
41 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
42 | 7 | -0.27613173E-12 | 0.13648587E-14 | -0.80406974E-13 | 0.78369587E-16 |
43 | 6 | 0.25651297E-07 | 0.27955499E-09 | 0.59014154E-08 | -0.11905989E-12 |
44 | 5 | -0.17465063E-03 | 0.24416492E-05 | -0.90019538E-04 | 0.58421144E-08 |
45 | 4 | 0.27387862 | 0.12098825E-02 | 0.93122264E-01 | -0.31012301E-04 |
46 | 3 | -6.9041115 | 0.38080793E-01 | -2.2314619 | 0.27235146E-01 |
47 | 2 | 39.676056 | 0.13726811 | 14.823303 | -0.32003278 |
48 | 1 | -79.629469 | 0.62686726E-01 | -28.745292 | 1.0590931 |
49 | 0 | 46.824345 | 0.12759187E-02 | 16.300942 | |
50 | 7 | -0.27182421E-12 | 0.13107754E-14 | -0.81108189E-13 | 0.79120162E-16 |
51 | 6 | 0.25844325E-07 | 0.27588229E-09 | 0.59440225E-08 | -0.12008605E-12 |
52 | 5 | -0.17564658E-03 | 0.24062150E-05 | -0.90521036E-04 | 0.58837691E-08 |
53 | 4 | 0.27506755 | 0.11908598E-02 | 0.93548701E-01 | -0.31177608E-04 |
54 | 3 | -6.9277136 | 0.37441415E-01 | -2.2384615 | 0.27350651E-01 |
55 | 2 | 39.753961 | 0.13483533 | 14.852153 | -0.32090009 |
56 | 1 | -79.689237 | 0.61525268E-01 | -28.771196 | 1.0603666 |
57 | 0 | 46.824344 | 0.12512697E-02 | 16.300293 | |
58 | 6 | 0.21465343E-07 | 0.35044740E-09 | 0.49771822E-08 | -0.96989815E-13 |
59 | 5 | -0.15274237E-03 | 0.31655188E-05 | -0.78941554E-04 | 0.49363227E-08 |
60 | 4 | 0.24727258 | 0.16154212E-02 | 0.83601931E-01 | -0.27359285E-04 |
61 | 3 | -6.3748395 | 0.52179222E-01 | -2.0745682 | 0.24648141E-01 |
62 | 2 | 37.927790 | 0.19236366 | 14.173893 | -0.30057625 |
63 | 1 | -78.286849 | 0.89555956E-01 | -28.161423 | 1.0304865 |
64 | 0 | 46.824354 | 0.18576719E-02 | 16.316151 | |
65 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
66 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
67 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
68 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
69 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
70 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
71 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
72 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
73 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
74 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
75 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
76 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
77 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
78 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
79 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
80 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
81 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
82 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
83 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
84 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
85 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
86 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
87 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
88 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
89 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
90 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
91 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
92 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
93 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
94 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
95 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
96 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.4547_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.4547_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.584 | 2.584 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.60743E-002 | 0.16139 | 0.61671 | 0.61671 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.12075 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.384E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.394E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.384E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.394E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.424E-004 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.424E-004 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.550E-005 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3464E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3804E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6415E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.6694E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2984E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3199E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4264E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4410E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.8916E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4091E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6788E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5912E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4101E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4784E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8057E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0496E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3484E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.3921E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6437E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.6823E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3006E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3298E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4263E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4409E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3099E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4267E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1189E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2533E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1970E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0594E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2668E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5265E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7979E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8111E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6333E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6429E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4246E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4283E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8320E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8371E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3747E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4072E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0141E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0403E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7667E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7859E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4263E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4409E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1750E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2536E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7020E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6688E-003 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6131E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.8521E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8057E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0496E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3740E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4063E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0130E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0378E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7648E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7790E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4264E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4410E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2204E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9373E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8140E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6674E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1280E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5822E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2668E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5265E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1164E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1422E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8095E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8350E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.7868E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8012E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8321E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8372E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.3433E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.2292E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.1227E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4564E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.8784E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1624E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.1564E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4627E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1520E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3372E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9762E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1724E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.0773E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9934E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.1886E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4843E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.4847E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6432E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.9821E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3074E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8897E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.9971E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1564E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4627E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1003E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8717E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.7166E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6153E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0443E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5384E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.1887E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4843E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.3431E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.2288E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.1224E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4559E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.8780E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1620E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.1562E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4625E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1520E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3371E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9762E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1722E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.0771E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9932E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.1884E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4841E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.4848E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6432E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.9822E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3073E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8896E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.9963E-003 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1562E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4625E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1003E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8716E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.7166E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6152E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0442E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5382E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.1884E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4842E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37528.48362 | 37528.48362 | 2.70589 | 2.70589 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 3228.37160 | 3228.37160 | 0.13684 | 0.42469 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27042.91039 | 27042.91039 | 1.94721 | 1.94721 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 9381.55674 | 9381.55674 | 0.39547 | 0.42469 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28544.47570 | 28544.47570 | 2.07565 | 2.07565 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 33.74200 | 1.65361E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 17746.69706 | 17746.69706 | 0.75269 | 0.75269 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8795.29037 | 8795.29037 | 0.63957 | 0.63957 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 7587.56641 | 7587.56641 | 0.32327 | 0.32327 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8851.01928 | 8851.01928 | 0.64362 | 0.64362 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 31.29300 | 1.65315E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 4964.57945 | 4964.57945 | 0.21154 | 0.21154 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 10763.74875 | 10763.74875 | 0.78271 | 0.78271 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 7560.55768 | 7560.55768 | 0.32211 | 0.32211 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 9802.02041 | 9802.02041 | 0.71277 | 0.71277 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 4950.75276 | 4950.75276 | 0.21095 | 0.21095 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7565.58844 | 7565.58844 | 0.55014 | 0.55014 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 4795.05758 | 4795.05758 | 0.20384 | 0.20384 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7909.43829 | 7909.43829 | 0.57514 | 0.57514 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 31.09550 | 1.65311E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 3185.10162 | 3185.10162 | 0.13545 | 0.13545 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9310.82132 | 9310.82132 | 0.67705 | 0.67705 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 4771.73674 | 4771.73674 | 0.20284 | 0.20284 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 8213.85668 | 8213.85668 | 0.59728 | 0.59728 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 32.39900 | 1.65335E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 3170.40854 | 3170.40854 | 0.13482 | 0.13482 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7533.06976 | 7533.06976 | 0.54778 | 0.54778 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 5550.38027 | 5550.38027 | 0.23616 | 0.23616 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 8455.30605 | 8455.30605 | 0.61484 | 0.61484 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 30.89800 | 1.65307E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 3662.62023 | 3662.62023 | 0.15588 | 0.15588 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 9426.03016 | 9426.03016 | 0.68543 | 0.68543 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 5522.53305 | 5522.53305 | 0.23497 | 0.23497 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 8789.60915 | 8789.60915 | 0.63915 | 0.63915 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 32.66233 | 1.65340E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 3648.56674 | 3648.56674 | 0.15527 | 0.15527 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 76684.91 | 4.61284 | 4.61284 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 10921.62 | 1.10165 | 1.10165 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 66302.74 | 3.86007 | 3.86007 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 11733.28 | 1.20697 | 1.20697 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 75548.57 | 4.55214 | 4.55214 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 11834.40 | 1.82057 | 1.82057 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.70589 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27697 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76577 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73859 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37559E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25554.55951 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.94721 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38489 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.37200 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.72436 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.89903E-004 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24172.87483 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.07565 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36107 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36700 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76176 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96285 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05520E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25420.98447 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63957 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24703 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16053 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65874 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54233E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10787.82570 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64362 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15541 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12872 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41442 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45164E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7059.47558 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78271 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20185 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20500 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16045 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53828 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.88751E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10749.25591 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71277 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14032 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14255 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37418 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71524E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7039.73139 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55014 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28718 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16119 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76582 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.32668E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6802.48373 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57514 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17391 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11503 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46375 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.19082E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4520.09648 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67705 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23335 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23800 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16114 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62228 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.63271E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6769.14779 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59728 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16745 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11946 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44654 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27528E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4499.09947 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.54778 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28842 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27900 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15283 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76912 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.32099E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7881.00516 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61484 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16268 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12297 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43381 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34203E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5201.74662 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68543 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23050 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22300 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15285 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61467 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.65293E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7841.23169 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63915 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15648 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12783 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41729 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43478E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5181.67887 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.55275 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.32258 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.10550 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.32258 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.61284 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.61284 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.28672 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.21721 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.28084 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.43441 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.28084 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.86007 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 3.86007 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.33182 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.42715 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35403 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.85431 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.82057 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.55214 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.55214 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.39994 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.61284 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 3.86007 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.55214 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.61284 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.61284 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 113387.02264 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70459 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.53746 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37791.89465 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70459 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 10006.41926 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.61284 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.86007 |
158 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 3.86007 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 95854.84843 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.28656 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31948.42098 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
165 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 11480.52226 |
166 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 3.86007 |
167 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.55214 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.55214 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 112225.65071 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70386 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.51723 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37404.80938 |
173 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70386 |
174 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 10158.78578 |
175 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.55214 |
176 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
177 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
179 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
180 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 113165.69 | 386137.35 | 11.63 | 2.97 | 3.33 | 3.52 | 3.64 | 10.13 | 11.37 | 12.00 | 12.41 | 5.3308 | 4.2246 | 2.8451 | 1.2203 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 95698.29 | 326536.13 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 4.4609 | 3.5313 | 2.3763 | 1.0245 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 112016.99 | 382217.82 | 11.63 | 2.97 | 3.33 | 3.52 | 3.64 | 10.13 | 11.38 | 12.00 | 12.42 | 5.2607 | 4.1713 | 2.8113 | 1.2047 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_NORTH_0.25 | N/A | 2.584 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_EAST_0.25 | N/A | 2.584 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | N/A | 2.584 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.4547_SHGC_WEST_0.25 | N/A | 2.584 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2066915905 | 0.2604503079 | Pass | Pass | 0.2391393970 | 0.4241826020 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.1976035884E-002 | 9.4224897702E-002 | Pass | Pass | 0.2622908103 | 0.9611173659 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.6688547769E-002 | 4.7291971221E-002 | Pass | Pass | 0.2454664840 | 0.6329831538 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.2056791712E-002 | 4.9632189173E-002 | Pass | Pass | 0.3553605620 | 1.1173943051 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1592051470 | 0.2367448590 | Pass | Pass | 0.1894477717 | 0.3902888326 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1496542029 | 0.2289254828 | Pass | Pass | 0.1825413655 | 0.3838809462 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1482577984 | 0.2223627744 | Pass | Pass | 0.1829502640 | 0.3832958223 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2181152431 | 0.2855841451 | Pass | Pass | 0.1835137221 | 0.3853718615 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3172178514 | 0.5471446728 | Pass | Pass | 0.2032223228 | 0.4190488585 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2176518564 | 0.3406446334 | Pass | Pass | 0.1834049755 | 0.3820624663 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1765501771 | 0.2273167896 | Pass | Pass | 0.2382616351 | 0.4233987964 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2311718758 | 0.2738223993 | Pass | Pass | 0.2391277060 | 0.4244964992 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3320233108 | 0.5119910908 | Pass | Pass | 0.2649498752 | 0.4586353744 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2189244609 | 0.2862568650 | Pass | Pass | 0.2382882673 | 0.4227876709 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1500157847 | 0.2215463648 | Pass | Pass | 0.1892279339 | 0.3892979540 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2205901536 | 0.2895430793 | Pass | Pass | 0.2000203231 | 0.4081387301 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3087323809 | 0.5151573169 | Pass | Pass | 0.2040798649 | 0.4113944253 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2094974088 | 0.3174923865 | Pass | Pass | 0.1895220002 | 0.3879757560 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3135.63 | -36.1 | 0.00 | 137.62 | 2506.52 | 5743.67 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4547_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4547_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.584 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.4547_SHGC_EAST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.4547_SHGC_EAST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.4547_SHGC_WEST_0.25 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.4547_SHGC_WEST_0.25 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.584 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.4547_SHGC_NORTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.4547_SHGC_EAST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.4547_SHGC_SOUTH_0.25 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.4547_SHGC_WEST_0.25 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.584 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.584 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 177.99 | 2.584 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.584 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.74 | 0.0000 | Y | 5.94 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.51 | 0.0000 | Y | 3.73 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.23 | 0.0000 | Y | 5.82 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.56 | 0.0000 | Y | 3.74 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.63 | 0.0000 | Y | 5.92 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.45 | 0.0000 | Y | 3.72 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.18 | 0.0000 | Y | 5.81 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.48 | 0.0000 | Y | 3.72 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.74 | 0.0000 | Y | 5.94 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.51 | 0.0000 | Y | 3.73 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.23 | 0.0000 | Y | 5.82 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.56 | 0.0000 | Y | 3.74 |
Interior Lighting Total | 5.9322 | 4982.19 | 29555.08 | 202.63 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 41.73 | 41.73 | 3.33 | |
EXTERIOR_LIGHTS_B | 408.47 | AstronomicalClock | - | 83.73 | 62.73 | 4.81 | |
EXTERIOR_LIGHTS_C | 4724.13 | AstronomicalClock | - | 83.73 | 47.05 | 41.72 | |
Exterior Lighting Total | 5557.43 | 49.86 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 113387.02 | 79891.61 | 33495.41 | 0.70 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 95854.85 | 67202.23 | 28652.62 | 0.70 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 112225.65 | 78991.42 | 33234.23 | 0.70 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 113165.7 | 2.97 | 10.13 | N/A | N/A | 11.63 | |
PACU_VAV_MID COOLING COIL | 95698.3 | 2.97 | 10.14 | N/A | N/A | 11.65 | |
PACU_VAV_TOP COOLING COIL | 112017.0 | 2.97 | 10.13 | N/A | N/A | 11.63 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25554.56 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24172.87 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 25420.98 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10787.83 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7059.48 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10749.26 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7039.73 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6802.48 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4520.10 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6769.15 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4499.10 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7881.01 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5201.75 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7841.23 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5181.68 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 10006.42 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 11480.52 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 10158.79 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.61 | 10097.56 | 2189.01 | 1.00 | 1.14 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 3.86 | 8449.75 | 2189.01 | 1.00 | 1.15 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.55 | 9964.68 | 2189.01 | 1.00 | 1.14 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 113165.69 | 2.97 | 10.13 | 11.63 | 5.3308 | 3.33 | 11.37 | 4.2246 | 3.52 | 12.00 | 2.8451 | 3.64 | 12.41 | 1.2203 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 95698.29 | 2.97 | 10.14 | 11.65 | 4.4609 | 3.34 | 11.39 | 3.5313 | 3.52 | 12.03 | 2.3763 | 3.64 | 12.43 | 1.0245 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 112016.99 | 2.97 | 10.13 | 11.63 | 5.2607 | 3.33 | 11.38 | 4.1713 | 3.52 | 12.00 | 2.8113 | 3.64 | 12.42 | 1.2047 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37528.48 | 37528.48 | 38.16 | 2.706 | 2.706 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 28.05 | 0.01653 | 0.425 | 0.00 |
CORE_MID | 27042.91 | 27042.91 | 27.50 | 1.947 | 1.947 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.05 | 0.01653 | 0.425 | 0.00 |
CORE_TOP | 28544.48 | 28544.48 | 29.02 | 2.076 | 2.076 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00892 | 33.74 | 0.01654 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8795.29 | 8795.29 | 42.42 | 0.640 | 0.640 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00885 | 33.82 | 0.01654 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8851.02 | 8851.02 | 67.43 | 0.644 | 0.644 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00873 | 31.29 | 0.01653 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 10763.75 | 10763.75 | 51.91 | 0.783 | 0.783 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00879 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9802.02 | 9802.02 | 74.68 | 0.713 | 0.713 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00870 | 32.79 | 0.01653 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7565.59 | 7565.59 | 36.49 | 0.550 | 0.550 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00888 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7909.44 | 7909.44 | 60.26 | 0.575 | 0.575 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00873 | 31.10 | 0.01653 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9310.82 | 9310.82 | 44.91 | 0.677 | 0.677 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00880 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 8213.86 | 8213.86 | 62.58 | 0.597 | 0.597 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 24.00 | 24.00 | 0.00872 | 32.40 | 0.01653 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7533.07 | 7533.07 | 36.33 | 0.548 | 0.548 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00890 | 33.90 | 0.01654 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 8455.31 | 8455.31 | 64.42 | 0.615 | 0.615 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 24.00 | 24.00 | 0.00873 | 30.90 | 0.01653 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9426.03 | 9426.03 | 45.46 | 0.685 | 0.685 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00882 | 33.83 | 0.01654 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8789.61 | 8789.61 | 66.97 | 0.639 | 0.639 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00872 | 32.66 | 0.01653 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 3228.37 | 3228.37 | 3.28 | 0.137 | 0.425 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
CORE_MID | 9381.56 | 9381.56 | 9.54 | 0.395 | 0.425 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
CORE_TOP | 17746.70 | 17746.70 | 18.04 | 0.753 | 0.753 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 7587.57 | 7587.57 | 36.60 | 0.323 | 0.323 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 4964.58 | 4964.58 | 37.82 | 0.212 | 0.212 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 7560.56 | 7560.56 | 36.46 | 0.322 | 0.322 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 4950.75 | 4950.75 | 37.72 | 0.211 | 0.211 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 4795.06 | 4795.06 | 23.13 | 0.204 | 0.204 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 3185.10 | 3185.10 | 24.27 | 0.135 | 0.135 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 4771.74 | 4771.74 | 23.01 | 0.203 | 0.203 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 3170.41 | 3170.41 | 24.15 | 0.135 | 0.135 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 5550.38 | 5550.38 | 26.77 | 0.236 | 0.236 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 3662.62 | 3662.62 | 27.90 | 0.156 | 0.156 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 4.60 | 0.00526 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 5522.53 | 5522.53 | 26.64 | 0.235 | 0.235 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 4.60 | 0.00526 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 3648.57 | 3648.57 | 27.80 | 0.155 | 0.155 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 4.60 | 0.00526 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.61 | 4.61 | 1.10 | 1.10 | 4.6128 | 1.3226 | 4.6128 | 0.2867 | 0.3000 |
PACU_VAV_MID | 3.86 | 3.86 | 1.21 | 1.21 | 3.8601 | 1.2808 | 3.8601 | 0.3318 | 0.3000 |
PACU_VAV_TOP | 4.55 | 4.55 | 1.82 | 1.82 | 4.5521 | 1.8206 | 4.5521 | 0.3999 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25554.560 | 25554.560 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25554.56 | 14172.46 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00799959 | 51.6718 | 3228.37 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24172.875 | 24172.875 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24172.87 | 14172.46 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 9381.56 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 25420.984 | 25420.984 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25420.98 | 25118.22 | 0.752691 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 17746.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 10787.826 | 10787.826 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10787.83 | 10787.83 | 0.323267 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00793568 | 51.2649 | 7587.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7059.476 | 7059.476 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7059.48 | 7059.48 | 0.211544 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00793662 | 51.2709 | 4964.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 10749.256 | 10749.256 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10749.26 | 10749.26 | 0.322112 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00793523 | 51.2621 | 7560.56 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 7039.731 | 7039.731 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7039.73 | 7039.73 | 0.210952 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00793629 | 51.2688 | 4950.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 6802.484 | 6802.484 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6802.48 | 6802.48 | 0.203843 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00789504 | 51.0058 | 4795.06 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4520.096 | 4520.096 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4520.10 | 4520.10 | 0.135449 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00789801 | 51.0248 | 3185.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 6769.148 | 6769.148 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6769.15 | 6769.15 | 0.202844 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00789427 | 51.0009 | 4771.74 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4499.099 | 4499.099 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4499.10 | 4499.10 | 0.134820 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00789707 | 51.0188 | 3170.41 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 7881.005 | 7881.005 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7881.01 | 7881.01 | 0.236162 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00788942 | 50.9701 | 5550.38 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 5201.747 | 5201.747 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5201.75 | 5201.75 | 0.155875 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00789311 | 50.9936 | 3662.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 7841.232 | 7841.232 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7841.23 | 7841.23 | 0.234970 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00788825 | 50.9626 | 5522.53 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 5181.679 | 5181.679 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5181.68 | 5181.68 | 0.155274 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00789226 | 50.9882 | 3648.57 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 113387.023 | 79891.613 | 4.612840 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 116822.53 | 84093.43 | 4.612840 | 26.57 | 19.15 | 0.01083347 | 11.02 | 11.02 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 25.9096 | 24.00 | 0.00883580 | 47.5027 | 63357.56 | 0.00 | 116917.24 | 81232.22 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 10006.419 | 10006.419 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10006.42 | 10006.42 | 1.383852 | 6.82 | 6.19 | 0.00562237 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 86.3655 | 21.00 | 0.00791326 | 51.1219 | 19150.68 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 95854.848 | 67202.226 | 3.860075 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 100102.71 | 69062.67 | 3.860075 | 27.08 | 19.66 | 0.01128589 | 11.03 | 11.03 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 30.9624 | 24.00 | 0.00891354 | 47.9149 | 52812.23 | 0.00 | 98839.22 | 68363.72 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 11480.522 | 11480.522 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11480.52 | 11480.52 | 1.158022 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 103.2078 | 21.00 | 0.00792718 | 51.2106 | 27765.66 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 112225.651 | 78991.425 | 4.552136 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 115847.12 | 82949.47 | 4.552136 | 26.56 | 19.18 | 0.01087725 | 11.03 | 11.03 | 0.00850000 | 33.74 | 0.01653608 | 25.09 | 26.2551 | 24.00 | 0.00885529 | 47.6061 | 62435.18 | 0.00 | 115719.71 | 80349.02 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 10158.786 | 10158.786 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10158.79 | 10158.79 | 1.365641 | 6.65 | 6.07 | 0.00559488 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 87.5171 | 21.00 | 0.00796276 | 51.4372 | 27826.61 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25554.560 | 25554.560 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25554.56 | 14172.46 | 1.0000 | 0.51097426 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25554.56 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.82 | 0.00799959 | 21.00 | 0.00799959 | 51.6718 | 3228.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24172.875 | 24172.875 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24172.87 | 14172.46 | 1.0000 | 0.51097426 | 0.424691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24172.87 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 9381.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 25420.984 | 25420.984 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25420.98 | 25118.22 | 1.0000 | 0.90561304 | 0.752691 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25420.98 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 17746.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 10787.826 | 10787.826 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10787.83 | 10787.83 | 1.0000 | 0.38894452 | 0.323267 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10787.83 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00793568 | 21.00 | 0.00793568 | 51.2649 | 7587.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7059.476 | 7059.476 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7059.48 | 7059.48 | 1.0000 | 0.25452250 | 0.211544 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7059.48 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00793662 | 21.00 | 0.00793662 | 51.2709 | 4964.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 10749.256 | 10749.256 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10749.26 | 10749.26 | 1.0000 | 0.38755392 | 0.322112 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10749.26 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00793523 | 21.00 | 0.00793523 | 51.2621 | 7560.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7039.731 | 7039.731 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7039.73 | 7039.73 | 1.0000 | 0.25381064 | 0.210952 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7039.73 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00793629 | 21.00 | 0.00793629 | 51.2688 | 4950.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 6802.484 | 6802.484 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6802.48 | 6802.48 | 1.0000 | 0.24525691 | 0.203843 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6802.48 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00789504 | 21.00 | 0.00789504 | 51.0058 | 4795.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4520.096 | 4520.096 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4520.10 | 4520.10 | 1.0000 | 0.16296766 | 0.135449 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4520.10 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00789801 | 21.00 | 0.00789801 | 51.0248 | 3185.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 6769.148 | 6769.148 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6769.15 | 6769.15 | 1.0000 | 0.24405501 | 0.202844 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6769.15 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00789427 | 21.00 | 0.00789427 | 51.0009 | 4771.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4499.099 | 4499.099 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4499.10 | 4499.10 | 1.0000 | 0.16221064 | 0.134820 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4499.10 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00789707 | 21.00 | 0.00789707 | 51.0188 | 3170.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7881.005 | 7881.005 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7881.01 | 7881.01 | 1.0000 | 0.28414194 | 0.236162 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7881.01 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00788942 | 21.00 | 0.00788942 | 50.9701 | 5550.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5201.747 | 5201.747 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5201.75 | 5201.75 | 1.0000 | 0.18754389 | 0.155875 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5201.75 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00789311 | 21.00 | 0.00789311 | 50.9936 | 3662.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 7841.232 | 7841.232 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7841.23 | 7841.23 | 1.0000 | 0.28270795 | 0.234970 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7841.23 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00788825 | 21.00 | 0.00788825 | 50.9626 | 5522.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5181.679 | 5181.679 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5181.68 | 5181.68 | 1.0000 | 0.18682037 | 0.155274 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5181.68 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00789226 | 21.00 | 0.00789226 | 50.9882 | 3648.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 113387.023 | 79891.613 | 4.612840 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.9789 | 1004.8586 | 1.2032 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.612840 | 5.55001630 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 116822.53 | 84093.43 | 1.0303 | 5.55001630 | 4.612840 | 26.57 | 19.15 | 0.01083347 | 54324.8 | 11.02 | 11.02 | 0.00850000 | 32510.5 | -999.0 | -999.00 | -999.00 | -999.00 | 10097.557 | 106724.97 | 33.90 | 0.01653638 | 25.13 | 1.19517000 | 25.9096 | 24.00 | 0.00883580 | 24.00 | 0.00883580 | 47.5027 | 63357.56 | 0.00 | 116917.24 | 81232.22 | 5.33083261 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.74 | 11.72 | 0.00856006 | 33390.1 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10006.419 | 10006.419 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.612840 | 5.55001630 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10006.42 | 10006.42 | 1.0000 | 1.66500489 | 1.383852 | 6.82 | 6.19 | 0.00562237 | 20984.7 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10006.42 | 4.60 | 0.00525715 | 4.60 | 1.19517000 | 86.3655 | 20.88 | 0.00793582 | 21.00 | 0.00791326 | 51.1219 | 19150.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 95854.848 | 67202.226 | 3.860075 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.95314 | 1025.8199 | 1004.8586 | 1.2032 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.860075 | 4.64431415 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 100102.71 | 69062.67 | 1.0443 | 4.64431415 | 3.860075 | 27.08 | 19.66 | 0.01128589 | 56004.7 | 11.03 | 11.03 | 0.00850000 | 32512.0 | -999.0 | -999.00 | -999.00 | -999.00 | 8449.746 | 91652.96 | 33.90 | 0.01653638 | 25.13 | 1.19517000 | 30.9624 | 24.00 | 0.00891354 | 24.00 | 0.00891354 | 47.9149 | 52812.23 | 0.00 | 98839.22 | 68363.72 | 4.46089885 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.63 | 0.00850611 | 33165.6 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11480.522 | 11480.522 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.860075 | 4.64431415 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11480.52 | 11480.52 | 1.0000 | 1.39329425 | 1.158022 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11480.52 | 4.60 | 0.00525715 | 4.60 | 1.19517000 | 103.2078 | 20.90 | 0.00792894 | 21.00 | 0.00792718 | 51.2106 | 27765.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 112225.651 | 78991.425 | 4.552136 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0603 | 1004.8586 | 1.2032 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.552136 | 5.47697983 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | Sensible | 115847.12 | 82949.47 | 1.0323 | 5.47697983 | 4.552136 | 26.56 | 19.18 | 0.01087725 | 54432.6 | 11.03 | 11.03 | 0.00850000 | 32510.7 | -999.0 | -999.00 | -999.00 | -999.00 | 9964.677 | 105882.44 | 33.74 | 0.01653608 | 25.09 | 1.19517000 | 26.2551 | 24.00 | 0.00885529 | 24.00 | 0.00885529 | 47.6061 | 62435.18 | 0.00 | 115719.71 | 80349.02 | 5.26068053 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.70 | 11.69 | 0.00854849 | 33325.3 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10158.786 | 10158.786 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.552136 | 5.47697983 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10158.79 | 10158.79 | 1.0000 | 1.64309395 | 1.365641 | 6.65 | 6.07 | 0.00559488 | 20741.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10158.79 | 4.60 | 0.00525715 | 4.60 | 1.19517000 | 87.5171 | 21.00 | 0.00796276 | 21.00 | 0.00796276 | 51.4372 | 27826.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.61 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 3.86 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 4.55 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 3932.00 | 785.67 | 0.00 |
CORE_MID | 2620.00 | 1929.00 | 0.17 |
CORE_TOP | 2714.17 | 2293.17 | 64.50 |
PERIMETER_TOP_ZN_3 | 3457.50 | 2382.33 | 377.00 |
PERIMETER_TOP_ZN_2 | 3588.17 | 2237.50 | 433.50 |
PERIMETER_TOP_ZN_1 | 3873.33 | 1689.33 | 327.50 |
PERIMETER_TOP_ZN_4 | 3415.33 | 2342.50 | 417.00 |
PERIMETER_BOT_ZN_3 | 3184.83 | 2257.67 | 71.00 |
PERIMETER_BOT_ZN_2 | 3667.50 | 1773.50 | 107.50 |
PERIMETER_BOT_ZN_1 | 4135.17 | 2159.33 | 898.50 |
PERIMETER_BOT_ZN_4 | 3577.50 | 1793.33 | 83.33 |
PERIMETER_MID_ZN_3 | 3388.67 | 2134.00 | 134.50 |
PERIMETER_MID_ZN_2 | 2893.33 | 1779.33 | 215.33 |
PERIMETER_MID_ZN_1 | 3976.17 | 1363.83 | 164.67 |
PERIMETER_MID_ZN_4 | 3449.17 | 1979.50 | 180.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4869.33 | 3578.17 | 1439.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 4.83 | 0.00 | 4.33 |
PERIMETER_TOP_ZN_2 | 0.17 | 42.83 | 0.17 | 42.33 |
PERIMETER_TOP_ZN_1 | 0.00 | 40.83 | 0.00 | 39.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 33.17 | 0.00 | 22.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 19.00 | 0.00 | 19.00 |
PERIMETER_BOT_ZN_1 | 74.67 | 206.33 | 74.67 | 205.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 16.50 | 0.00 | 12.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 26.33 | 0.00 | 26.33 |
PERIMETER_MID_ZN_1 | 0.00 | 32.17 | 0.00 | 31.67 |
PERIMETER_MID_ZN_4 | 0.00 | 23.50 | 0.00 | 16.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 74.83 | 317.00 | 74.83 | 302.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.99 | 52.94 | 2698.04 | 0.596 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.99 | 52.94 | 2698.04 | 0.485 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.99 | 52.94 | 2698.04 | 0.483 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.572 | 0.016 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.761 | 0.017 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.743 | 0.016 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.794 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.515 | 0.009 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.660 | 0.009 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.701 | 1.248 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.661 | 0.009 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.573 | 0.014 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.700 | 0.015 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.761 | 0.014 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.775 | 0.014 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.99 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.94 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.58 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.64 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.99 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.94 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.58 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.64 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 111.05 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 9393539.28 | 0.00 | 9393539.28 | 0.00 | 9393539.28 | 13393058.27 | 5923.61 | 389.56 | 2446.83 | 6.81 |
CORE_MID | 7646216.78 | 0.00 | 7646216.78 | 0.00 | 7646216.78 | 13393058.27 | 7171.72 | 249.04 | 1339.23 | 2.67 |
CORE_TOP | 7617682.42 | 0.00 | 7617682.42 | 0.00 | 7617682.42 | 13393058.27 | 7450.40 | 94.67 | 1214.93 | 3.58 |
PERIMETER_TOP_ZN_3 | 1902209.63 | 0.00 | 1902209.63 | 105547.40 | 2007757.03 | 2823374.22 | 5352.17 | 119.38 | 3288.45 | 3.58 |
PERIMETER_TOP_ZN_2 | 1601031.40 | 0.00 | 1601031.40 | 70364.51 | 1671395.91 | 1787429.43 | 4299.91 | 2.54 | 4457.55 | 3.58 |
PERIMETER_TOP_ZN_1 | 2468283.18 | 0.00 | 2468283.18 | 105547.40 | 2573830.59 | 2823374.22 | 5015.66 | 90.85 | 3653.49 | 3.58 |
PERIMETER_TOP_ZN_4 | 1671498.03 | 0.00 | 1671498.03 | 70364.51 | 1741862.54 | 1787312.18 | 4311.82 | 8.51 | 4439.67 | 3.58 |
PERIMETER_BOT_ZN_3 | 1715157.94 | 0.00 | 1715157.94 | 56119.35 | 1771277.29 | 2823374.22 | 6230.06 | 416.33 | 2113.61 | 6.81 |
PERIMETER_BOT_ZN_2 | 1389950.80 | 0.00 | 1389950.80 | 37412.68 | 1427363.47 | 1787429.43 | 4495.87 | 77.90 | 4186.23 | 6.81 |
PERIMETER_BOT_ZN_1 | 2326699.14 | 0.00 | 2326699.14 | 4154684.95 | 6481384.09 | 2823374.22 | 4811.87 | 302.72 | 3645.41 | 6.81 |
PERIMETER_BOT_ZN_4 | 1391776.20 | 0.00 | 1391776.20 | 37412.68 | 1429188.87 | 1787312.18 | 4879.65 | 122.59 | 3757.76 | 6.81 |
PERIMETER_MID_ZN_3 | 1903241.77 | 0.00 | 1903241.77 | 87860.39 | 1991102.16 | 2823374.22 | 4966.01 | 332.10 | 3461.89 | 2.67 |
PERIMETER_MID_ZN_2 | 1595609.56 | 0.00 | 1595609.56 | 58573.24 | 1654182.80 | 1787429.43 | 4286.91 | 5.79 | 4467.30 | 911.67 |
PERIMETER_MID_ZN_1 | 2524254.75 | 0.00 | 2524254.75 | 87860.39 | 2612115.14 | 2823374.22 | 4588.48 | 306.72 | 3864.79 | 2.67 |
PERIMETER_MID_ZN_4 | 1630361.54 | 0.00 | 1630361.54 | 58573.24 | 1688934.78 | 1787312.18 | 4316.69 | 19.33 | 4423.98 | 2.67 |
Total Facility | 46777512.42 | 0.00 | 46777512.42 | 4930320.74 | 51707833.16 | 67843644.98 | 7551.25 | 1076.72 | 4507.00 | 917.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.4382 | 0.0000 | 0.4382 | 0.0000 | 0.4382 | 0.4247 | 3113.42 | 389.56 | 2440.02 |
CORE_MID | 0.3571 | 0.0000 | 0.3571 | 0.0000 | 0.3571 | 0.4247 | 4357.39 | 249.04 | 1336.57 |
CORE_TOP | 0.3557 | 0.0000 | 0.3557 | 0.0000 | 0.3557 | 0.4247 | 4636.24 | 94.67 | 1212.09 |
PERIMETER_TOP_ZN_3 | 0.0888 | 0.0000 | 0.0888 | 0.0025 | 0.0914 | 0.0895 | 2538.00 | 119.38 | 3285.62 |
PERIMETER_TOP_ZN_2 | 0.0748 | 0.0000 | 0.0748 | 0.0017 | 0.0765 | 0.0567 | 1485.74 | 2.54 | 4454.72 |
PERIMETER_TOP_ZN_1 | 0.1153 | 0.0000 | 0.1153 | 0.0025 | 0.1178 | 0.0895 | 2201.49 | 90.85 | 3650.66 |
PERIMETER_TOP_ZN_4 | 0.0780 | 0.0000 | 0.0780 | 0.0017 | 0.0797 | 0.0567 | 1497.65 | 8.51 | 4436.84 |
PERIMETER_BOT_ZN_3 | 0.0800 | 0.0000 | 0.0800 | 0.0013 | 0.0813 | 0.0895 | 3419.86 | 416.33 | 2106.81 |
PERIMETER_BOT_ZN_2 | 0.0648 | 0.0000 | 0.0648 | 0.0009 | 0.0657 | 0.0567 | 1685.67 | 77.90 | 4179.43 |
PERIMETER_BOT_ZN_1 | 0.1086 | 0.0000 | 0.1086 | 0.1929 | 0.3015 | 0.0895 | 2001.67 | 302.72 | 3638.61 |
PERIMETER_BOT_ZN_4 | 0.0649 | 0.0000 | 0.0649 | 0.0009 | 0.0658 | 0.0567 | 2069.45 | 122.59 | 3750.96 |
PERIMETER_MID_ZN_3 | 0.0889 | 0.0000 | 0.0889 | 0.0021 | 0.0910 | 0.0895 | 2151.68 | 332.10 | 3459.22 |
PERIMETER_MID_ZN_2 | 0.0687 | 0.0000 | 0.0687 | 0.0015 | 0.0702 | 0.0567 | 1469.91 | 2.95 | 3561.14 |
PERIMETER_MID_ZN_1 | 0.1179 | 0.0000 | 0.1179 | 0.0021 | 0.1200 | 0.0895 | 1774.15 | 306.72 | 3862.13 |
PERIMETER_MID_ZN_4 | 0.0761 | 0.0000 | 0.0761 | 0.0014 | 0.0775 | 0.0567 | 1502.35 | 19.33 | 4421.31 |
Total Facility | 2.1778 | 0.0000 | 2.1778 | 0.2116 | 2.3894 | 2.1513 | 4736.14 | 1076.72 | 4499.25 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 23476122.96 | 0.00 | 23476122.96 | 22614548.33 | 4276.07 | 0.00 | 4483.93 | 6.81 |
PACU_VAV_MID | 22148034.51 | 0.00 | 22148034.51 | 22614548.33 | 4276.85 | 0.00 | 4483.15 | 2.67 |
PACU_VAV_TOP | 22091579.37 | 0.00 | 22091579.37 | 22614548.33 | 4292.50 | 1.43 | 4466.07 | 3.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.0952 | 0.0000 | 1.0952 | 0.7171 | 1465.88 | 0.00 | 4477.12 |
PACU_VAV_MID | 1.0344 | 0.0000 | 1.0344 | 0.7171 | 1462.51 | 0.00 | 4480.49 |
PACU_VAV_TOP | 1.0315 | 0.0000 | 1.0315 | 0.7171 | 1478.34 | 1.43 | 4463.24 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 1360.94 | 0.00 | 0.00 | 0.00 | 3122.99 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 1313.43 | 0.00 | 0.00 | 0.00 | 3169.73 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 1239.62 | 0.00 | 0.00 | 0.00 | 3234.27 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.1870 | 0.0000 | 0.0000 | 0.0000 | 1.1362 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 1.8992 | 0.0000 | 0.0000 | 0.0000 | 1.1547 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 1.9627 | 0.0000 | 0.0000 | 0.0000 | 1.1455 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 827 |
Defaulted Fields | 545 |
Fields with Defaults | 2238 |
Autosized Fields | 150 |
Autosizable Fields | 203 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1579.43 | 12346.62 | 06-AUG-17:20 | 145720.01 | 30-AUG-16:00 |
Electricity:Building | 908.07 | 12175.61 | 28-MAY-17:10 | 66392.18 | 25-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 284.50 | 4029.56 | 01-JAN-00:10 | 22405.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 908.07 | 12175.61 | 28-MAY-17:10 | 66392.18 | 25-OCT-07:10 |
InteriorLights:Electricity | 202.63 | 934.27 | 01-JAN-09:50 | 20527.47 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 202.63 | 934.27 | 01-JAN-09:50 | 20527.47 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 202.63 | 934.27 | 01-JAN-09:50 | 20527.47 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 202.63 | 934.27 | 01-JAN-09:50 | 20527.47 | 25-OCT-07:10 |
Electricity:Zone:CORE_MID | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.27 | 409.68 | 26-MAR-17:10 | 2243.06 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.94 | 23.57 | 01-JAN-09:50 | 807.82 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.94 | 23.57 | 01-JAN-09:50 | 807.82 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.13 | 259.34 | 28-MAY-17:10 | 1409.60 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.73 | 14.92 | 01-JAN-07:50 | 501.02 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.73 | 14.92 | 01-JAN-07:50 | 501.02 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.16 | 409.67 | 12-MAR-17:10 | 2237.94 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.82 | 23.57 | 01-JAN-07:50 | 802.71 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.82 | 23.57 | 01-JAN-07:50 | 802.71 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.14 | 259.34 | 12-MAR-17:10 | 1423.60 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.74 | 14.92 | 01-JAN-09:40 | 515.04 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.74 | 14.92 | 01-JAN-09:40 | 515.04 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.25 | 409.68 | 26-MAR-17:10 | 2239.36 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.92 | 23.57 | 01-JAN-09:40 | 804.12 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.92 | 23.57 | 01-JAN-09:40 | 804.12 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.12 | 259.34 | 28-MAY-17:10 | 1407.27 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.72 | 14.92 | 01-JAN-07:50 | 498.70 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.72 | 14.92 | 01-JAN-07:50 | 498.70 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.14 | 409.67 | 12-MAR-17:10 | 2233.95 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.81 | 23.57 | 01-JAN-07:50 | 798.72 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.81 | 23.57 | 01-JAN-07:50 | 798.72 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.13 | 259.34 | 12-MAR-17:10 | 1421.88 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.72 | 14.92 | 01-JAN-09:40 | 513.32 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.72 | 14.92 | 01-JAN-09:40 | 513.32 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.27 | 409.68 | 26-MAR-17:10 | 2243.06 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.94 | 23.57 | 01-JAN-09:50 | 807.81 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.94 | 23.57 | 01-JAN-09:50 | 807.81 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.13 | 259.34 | 28-MAY-17:10 | 1409.59 | 12-DEC-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.73 | 14.92 | 01-JAN-07:50 | 501.02 | 12-DEC-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.73 | 14.92 | 01-JAN-07:50 | 501.02 | 12-DEC-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.16 | 409.67 | 12-MAR-17:10 | 2237.94 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.82 | 23.57 | 01-JAN-07:50 | 802.70 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.82 | 23.57 | 01-JAN-07:50 | 802.70 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.14 | 259.34 | 12-MAR-17:10 | 1423.60 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.74 | 14.92 | 01-JAN-09:40 | 515.03 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.74 | 14.92 | 01-JAN-09:40 | 515.03 | 25-OCT-07:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 621.49 | 168.34 | 01-JAN-00:10 | 86828.17 | 30-AUG-16:00 |
ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 834.20 | 25-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 834.20 | 25-OCT-07:20 |
ElectricityPurchased:Facility | 1579.43 | 12346.62 | 06-AUG-17:20 | 145720.01 | 30-AUG-16:00 |
ElectricityPurchased:Plant | 1579.43 | 12346.62 | 06-AUG-17:20 | 145720.01 | 30-AUG-16:00 |
Cogeneration:ElectricityPurchased | 1579.43 | 12346.62 | 06-AUG-17:20 | 145720.01 | 30-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 1579.43 | 12346.62 | 06-AUG-17:20 | 145720.01 | 30-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1579.43 | 12346.62 | 06-AUG-17:20 | 145720.01 | 30-AUG-16:00 |
ElectricityNet:Plant | 1579.43 | 12346.62 | 06-AUG-17:20 | 145720.01 | 30-AUG-16:00 |
Cogeneration:ElectricityNet | 1579.43 | 12346.62 | 06-AUG-17:20 | 145720.01 | 30-AUG-16:00 |
General:Cogeneration:ElectricityNet | 1579.43 | 12346.62 | 06-AUG-17:20 | 145720.01 | 30-AUG-16:00 |
Heating:Electricity | 14.44 | 0.00 | 01-JAN-00:10 | 81587.44 | 06-FEB-07:10 |
General:Heating:Electricity | 14.44 | 0.00 | 01-JAN-00:10 | 81587.44 | 06-FEB-07:10 |
Fans:Electricity | 79.58 | 0.00 | 01-JAN-00:10 | 13414.70 | 10-OCT-13:40 |
General:Fans:Electricity | 79.58 | 0.00 | 01-JAN-00:10 | 13414.70 | 10-OCT-13:40 |
ExteriorLights:Electricity | 49.86 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 49.86 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 505.46 | 0.00 | 01-JAN-00:10 | 72587.65 | 21-JUL-16:00 |
General:Cooling:Electricity | 505.46 | 0.00 | 01-JAN-00:10 | 72587.65 | 21-JUL-16:00 |
HeatRecovery:Electricity | 10.36 | 0.00 | 01-JAN-00:10 | 907.56 | 04-JAN-21:10 |
General:HeatRecovery:Electricity | 10.36 | 0.00 | 01-JAN-00:10 | 907.56 | 04-JAN-21:10 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 03-JAN-07:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 03-JAN-07:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 03-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 5.69 | 0.00 | 01-JAN-00:10 | 576.82 | 25-OCT-07:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 94.56 | 1156.00 | 04-JAN-18:10 | 17174.77 | 05-JAN-07:20 |
NaturalGas:HVAC | 0.59 | 0.00 | 01-JAN-00:10 | 12382.75 | 05-JAN-08:00 |
Heating:NaturalGas | 0.59 | 0.00 | 01-JAN-00:10 | 12382.75 | 05-JAN-08:00 |
General:Heating:NaturalGas | 0.59 | 0.00 | 01-JAN-00:10 | 12382.75 | 05-JAN-08:00 |
NaturalGas:Plant | 93.98 | 1156.00 | 04-JAN-18:10 | 8988.50 | 23-JAN-12:10 |
WaterSystems:NaturalGas | 93.98 | 1156.00 | 04-JAN-18:10 | 8988.50 | 23-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 93.98 | 1156.00 | 04-JAN-18:10 | 8988.50 | 23-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3603.85 | 0.00 | 01-JAN-00:10 | 425968.08 | 06-OCT-14:00 |
EnergyTransfer:Building | 1442.57 | 0.00 | 01-JAN-00:10 | 153800.47 | 10-OCT-13:40 |
EnergyTransfer:Zone:CORE_BOTTOM | 279.75 | 0.00 | 01-JAN-00:10 | 26203.56 | 22-MAY-08:00 |
Heating:EnergyTransfer | 8.53 | 0.00 | 01-JAN-00:10 | 53726.42 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 8.53 | 0.00 | 01-JAN-00:10 | 53726.42 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1434.04 | 0.00 | 01-JAN-00:10 | 153800.47 | 10-OCT-13:40 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 279.75 | 0.00 | 01-JAN-00:10 | 26203.56 | 22-MAY-08:00 |
General:Cooling:EnergyTransfer | 1434.04 | 0.00 | 01-JAN-00:10 | 153800.47 | 10-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 279.75 | 0.00 | 01-JAN-00:10 | 26203.56 | 22-MAY-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.82 | 0.00 | 01-JAN-00:10 | 9905.76 | 18-JUL-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.95 | 0.00 | 01-JAN-00:10 | 6329.11 | 21-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 2.95 | 0.00 | 01-JAN-00:10 | 6329.11 | 21-DEC-07:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.87 | 0.00 | 01-JAN-00:10 | 9905.76 | 18-JUL-14:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 50.87 | 0.00 | 01-JAN-00:10 | 9905.76 | 18-JUL-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 28.70 | 0.00 | 01-JAN-00:10 | 4442.04 | 10-OCT-14:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.71 | 0.00 | 01-JAN-00:10 | 2056.97 | 31-DEC-12:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.71 | 0.00 | 01-JAN-00:10 | 2056.97 | 31-DEC-12:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 27.99 | 0.00 | 01-JAN-00:10 | 4442.04 | 10-OCT-14:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 27.99 | 0.00 | 01-JAN-00:10 | 4442.04 | 10-OCT-14:10 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.59 | 0.00 | 01-JAN-00:10 | 4783.41 | 10-OCT-15:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.46 | 0.00 | 01-JAN-00:10 | 1520.28 | 15-JAN-12:40 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.46 | 0.00 | 01-JAN-00:10 | 1520.28 | 15-JAN-12:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.13 | 0.00 | 01-JAN-00:10 | 4783.41 | 10-OCT-15:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.13 | 0.00 | 01-JAN-00:10 | 4783.41 | 10-OCT-15:10 |
EnergyTransfer:Zone:CORE_MID | 200.59 | 0.00 | 01-JAN-00:10 | 18203.78 | 10-OCT-08:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1809.64 | 13-MAR-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 1809.64 | 13-MAR-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 200.59 | 0.00 | 01-JAN-00:10 | 18203.78 | 10-OCT-08:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 200.59 | 0.00 | 01-JAN-00:10 | 18203.78 | 10-OCT-08:00 |
EnergyTransfer:Zone:CORE_TOP | 206.56 | 0.00 | 01-JAN-00:10 | 19864.73 | 05-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.17 | 0.00 | 01-JAN-00:10 | 9060.76 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.17 | 0.00 | 01-JAN-00:10 | 9060.76 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 206.38 | 0.00 | 01-JAN-00:10 | 19864.73 | 05-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 206.38 | 0.00 | 01-JAN-00:10 | 19864.73 | 05-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.38 | 0.00 | 01-JAN-00:10 | 7283.99 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.79 | 0.00 | 01-JAN-00:10 | 6016.52 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.79 | 0.00 | 01-JAN-00:10 | 6016.52 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 53.59 | 0.00 | 01-JAN-00:10 | 7283.99 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 53.59 | 0.00 | 01-JAN-00:10 | 7283.99 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 46.63 | 0.00 | 01-JAN-00:10 | 7282.43 | 12-JUN-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.37 | 0.00 | 01-JAN-00:10 | 3694.71 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.37 | 0.00 | 01-JAN-00:10 | 3694.71 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 46.26 | 0.00 | 01-JAN-00:10 | 7282.43 | 12-JUN-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 46.26 | 0.00 | 01-JAN-00:10 | 7282.43 | 12-JUN-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 70.48 | 0.00 | 01-JAN-00:10 | 11188.64 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.44 | 0.00 | 01-JAN-00:10 | 5007.79 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.44 | 0.00 | 01-JAN-00:10 | 5007.79 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 70.04 | 0.00 | 01-JAN-00:10 | 11188.64 | 06-NOV-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 70.04 | 0.00 | 01-JAN-00:10 | 11188.64 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 46.45 | 0.00 | 01-JAN-00:10 | 8315.60 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.45 | 0.00 | 01-JAN-00:10 | 3478.79 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.45 | 0.00 | 01-JAN-00:10 | 3478.79 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.99 | 0.00 | 01-JAN-00:10 | 8315.60 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 45.99 | 0.00 | 01-JAN-00:10 | 8315.60 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 51.96 | 0.00 | 01-JAN-00:10 | 6692.37 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.05 | 0.00 | 01-JAN-00:10 | 2134.78 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.05 | 0.00 | 01-JAN-00:10 | 2134.78 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 51.91 | 0.00 | 01-JAN-00:10 | 6692.37 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 51.91 | 0.00 | 01-JAN-00:10 | 6692.37 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 44.10 | 0.00 | 01-JAN-00:10 | 6493.59 | 11-SEP-09:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1148.74 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1148.74 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 44.08 | 0.00 | 01-JAN-00:10 | 6493.59 | 11-SEP-09:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 44.08 | 0.00 | 01-JAN-00:10 | 6493.59 | 11-SEP-09:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 75.11 | 0.00 | 01-JAN-00:10 | 11793.71 | 30-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.82 | 0.00 | 01-JAN-00:10 | 5986.26 | 05-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.82 | 0.00 | 01-JAN-00:10 | 5986.26 | 05-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 73.29 | 0.00 | 01-JAN-00:10 | 11793.71 | 30-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 73.29 | 0.00 | 01-JAN-00:10 | 11793.71 | 30-AUG-16:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 42.90 | 0.00 | 01-JAN-00:10 | 6909.21 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1050.64 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1050.64 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 42.88 | 0.00 | 01-JAN-00:10 | 6909.21 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 42.88 | 0.00 | 01-JAN-00:10 | 6909.21 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 51.93 | 0.00 | 01-JAN-00:10 | 6571.30 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.11 | 0.00 | 01-JAN-00:10 | 2913.97 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.11 | 0.00 | 01-JAN-00:10 | 2913.97 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 51.83 | 0.00 | 01-JAN-00:10 | 6571.30 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 51.83 | 0.00 | 01-JAN-00:10 | 6571.30 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 44.04 | 0.00 | 01-JAN-00:10 | 6919.28 | 12-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.06 | 0.00 | 01-JAN-00:10 | 1737.26 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.06 | 0.00 | 01-JAN-00:10 | 1737.26 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 43.99 | 0.00 | 01-JAN-00:10 | 6919.28 | 12-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 43.99 | 0.00 | 01-JAN-00:10 | 6919.28 | 12-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 67.87 | 0.00 | 01-JAN-00:10 | 10023.57 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 2198.13 | 21-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 2198.13 | 21-DEC-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 67.82 | 0.00 | 01-JAN-00:10 | 10023.57 | 06-NOV-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 67.82 | 0.00 | 01-JAN-00:10 | 10023.57 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 43.72 | 0.00 | 01-JAN-00:10 | 7607.80 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 1546.58 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 1546.58 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 43.66 | 0.00 | 01-JAN-00:10 | 7607.80 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 43.66 | 0.00 | 01-JAN-00:10 | 7607.80 | 30-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 38.26 | 0.00 | 01-JAN-00:10 | 4953.79 | 23-JAN-12:40 |
PlantLoopHeatingDemand:Plant | 38.26 | 0.00 | 01-JAN-00:10 | 4953.79 | 23-JAN-12:40 |
WaterSystems:PlantLoopHeatingDemand | 38.26 | 0.00 | 01-JAN-00:10 | 4953.79 | 23-JAN-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 38.26 | 0.00 | 01-JAN-00:10 | 4953.79 | 23-JAN-12:40 |
EnergyTransfer:HVAC | 2123.01 | 0.00 | 01-JAN-00:10 | 280118.97 | 06-OCT-14:00 |
HeatingCoils:EnergyTransfer | 14.90 | 0.00 | 01-JAN-00:10 | 83593.63 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 2000.94 | 0.00 | 01-JAN-00:10 | 257847.79 | 06-OCT-14:00 |
HeatRecoveryForHeating:EnergyTransfer | 0.29 | 0.00 | 01-JAN-00:10 | 5630.46 | 20-DEC-08:00 |
HeatRecoveryForCooling:EnergyTransfer | 106.88 | 0.00 | 01-JAN-00:10 | 26302.55 | 07-OCT-13:00 |
EnergyTransfer:Plant | 38.26 | 0.00 | 01-JAN-00:10 | 4953.79 | 23-JAN-12:40 |
WaterSystems:EnergyTransfer | 38.26 | 0.00 | 01-JAN-00:10 | 4953.79 | 23-JAN-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 38.26 | 0.00 | 01-JAN-00:10 | 4953.79 | 23-JAN-12:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -279.751 | 0.000 | 0.000 | 32.758 | 48.333 | 236.167 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -37.507 |
CORE_MID | 0.000 | 0.000 | 0.002 | -200.587 | 0.000 | 0.000 | 33.381 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 3.446 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
CORE_TOP | 0.000 | 0.000 | 0.173 | -206.383 | 0.000 | 0.000 | 33.889 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 8.564 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.788 | -53.589 | 0.000 | 0.000 | 7.202 | 5.942 | 24.333 | 22.052 | 0.000 | 0.121 | 6.638 | 0.000 | -13.006 | 0.000 | -0.480 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.367 | -46.259 | 0.000 | 0.000 | 4.503 | 3.729 | 15.404 | 31.358 | 0.000 | 0.076 | 0.000 | 0.000 | -8.260 | 0.000 | -0.335 | -0.583 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.441 | -70.034 | 0.000 | 0.000 | 7.038 | 5.825 | 24.332 | 54.026 | 0.000 | 0.112 | 0.001 | 0.000 | -12.890 | 0.000 | -0.542 | -8.307 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.454 | -45.992 | 0.000 | 0.000 | 4.568 | 3.735 | 15.403 | 30.908 | 0.000 | 0.079 | 0.000 | 0.000 | -8.742 | 0.000 | -0.338 | -0.075 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.050 | -51.913 | 0.000 | 0.000 | 7.139 | 5.918 | 24.333 | 22.223 | 0.000 | 0.069 | 6.363 | 0.000 | -13.902 | 0.000 | -0.278 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.017 | -44.081 | 0.000 | 0.000 | 4.441 | 3.720 | 15.404 | 31.423 | 0.000 | 0.041 | 0.002 | 0.000 | -9.118 | 0.000 | -0.200 | -1.645 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.820 | -73.289 | 0.000 | 0.000 | 7.043 | 5.812 | 24.332 | 54.356 | 0.000 | 10.643 | 0.003 | 0.000 | -14.073 | 0.000 | -12.366 | -4.279 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.016 | -42.881 | 0.000 | 0.000 | 4.481 | 3.725 | 15.403 | 30.950 | 0.000 | 0.041 | 0.002 | 0.000 | -9.645 | 0.000 | -0.202 | -1.889 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.108 | -51.826 | 0.000 | 0.000 | 7.124 | 5.942 | 24.333 | 22.025 | 0.000 | 0.103 | 6.567 | 0.000 | -13.940 | 0.000 | -0.435 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.057 | -43.987 | 0.000 | 0.000 | 3.304 | 3.729 | 15.404 | 31.340 | 0.000 | 0.064 | 0.001 | 0.000 | -8.783 | 0.000 | -0.301 | -0.827 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.052 | -67.818 | 0.000 | 0.000 | 6.980 | 5.825 | 24.332 | 54.036 | 0.000 | 0.095 | 0.001 | 0.000 | -13.686 | 0.000 | -0.484 | -9.332 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.063 | -43.657 | 0.000 | 0.000 | 4.510 | 3.735 | 15.403 | 30.877 | 0.000 | 0.065 | 0.003 | 0.000 | -9.345 | 0.000 | -0.305 | -1.348 |
TOPFLOOR_PLENUM | 2.950 | -50.872 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.129 | 48.531 | 0.000 | 0.000 | 0.000 | -0.737 | 0.000 |
MIDFLOOR_PLENUM | 0.711 | -27.987 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.149 | 27.887 | 0.000 | 0.000 | 0.000 | -0.760 | 0.000 |
FIRSTFLOOR_PLENUM | 0.460 | -33.130 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.114 | 33.185 | 0.000 | 0.000 | 0.000 | -0.629 | 0.000 |
Total Facility | 4.121 | -111.989 | 4.406 | -1322.048 | 0.000 | 0.000 | 168.360 | 202.635 | 705.434 | 415.574 | 0.000 | 11.900 | 141.193 | 0.000 | -135.392 | 0.000 | -18.390 | -65.796 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 01-MAY-04:03 | 0.00 | 0.00 | 0.00 | -41476.20 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 36601.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 11-OCT-04:03 | 0.00 | 0.00 | 0.00 | -29563.32 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 26652.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 10-OCT-04:02 | 0.00 | 0.00 | 0.00 | -32156.18 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 29245.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 23-JUL-14:43 | 0.00 | 0.00 | 0.00 | -10717.02 | 0.00 | 0.00 | 27.21 | 23.57 | 478.42 | 3284.79 | 0.00 | 38.10 | 6864.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 28-MAY-09:02 | 0.00 | 0.00 | 0.00 | -11302.37 | 0.00 | 0.00 | 15.91 | 14.92 | 302.86 | 6400.99 | 0.00 | 17.60 | 4550.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-DEC-12:42 | 0.00 | 0.00 | 0.00 | -14682.29 | 0.00 | 0.00 | 23.78 | 23.57 | 478.41 | 11907.53 | 0.00 | 0.00 | 2256.01 | 0.00 | -0.00 | 0.00 | -7.01 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-APR-16:42 | 0.00 | 0.00 | 0.00 | -12897.99 | 0.00 | 0.00 | 14.93 | 14.92 | 302.86 | 6577.32 | 0.00 | 0.00 | 5991.06 | 0.00 | -0.00 | 0.00 | -3.11 | 0.00 |
PERIMETER_BOT_ZN_3 | 10-JUL-04:03 | 0.00 | 0.00 | 0.00 | -7742.64 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 7402.00 | 0.00 | -272.85 | 0.00 | -0.17 | 0.00 |
PERIMETER_BOT_ZN_2 | 03-SEP-10:22 | 0.00 | 0.00 | 0.00 | -10297.52 | 0.00 | 0.00 | 16.00 | 14.92 | 302.86 | 5285.88 | 0.00 | 4.91 | 4672.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-12:22 | 0.00 | 0.00 | 0.00 | -12761.93 | 0.00 | 0.00 | 24.01 | 23.57 | 478.41 | 9078.61 | 0.00 | 29.68 | 3127.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 03-SEP-17:02 | 0.00 | 0.00 | 0.00 | -10908.82 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 5833.41 | 0.00 | 9.51 | 4806.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 26-JUN-04:03 | 0.00 | 0.00 | 0.00 | -7791.56 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 7536.45 | 0.00 | -358.55 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 03-SEP-09:02 | 0.00 | 0.00 | 0.00 | -11152.53 | 0.00 | 0.00 | 15.52 | 14.92 | 302.86 | 7249.20 | 0.00 | 5.20 | 3564.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-12:22 | 0.00 | 0.00 | 0.00 | -13038.90 | 0.00 | 0.00 | 23.42 | 23.57 | 478.41 | 9023.62 | 0.00 | 43.07 | 3446.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 03-SEP-17:02 | 0.00 | 0.00 | 0.00 | -11747.23 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 5790.79 | 0.00 | 14.00 | 5683.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 18-JUL-14:50 | 0.00 | -9905.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 | 9887.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-JUL-06:03 | 0.00 | -4461.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 | 4460.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 05-JUL-06:03 | 0.00 | -4921.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 4921.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 05-JUL-04:02 | 0.00 | 8036.29 | 0.00 | -193116.19 | 0.00 | 0.00 | 0.00 | 2375.34 | 14333.92 | 0.00 | 0.00 | 0.00 | 171781.04 | 0.00 | -3407.45 | 0.00 | -2.95 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 13-MAR-06:01 | 0.00 | 0.00 | 16286.80 | 0.00 | 0.00 | 0.00 | 887.13 | 1406.75 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21606.60 |
CORE_TOP | 09-FEB-07:02 | 0.00 | 0.00 | 17764.25 | 0.00 | 0.00 | 0.00 | 895.32 | 1406.75 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23092.24 |
PERIMETER_TOP_ZN_3 | 21-DEC-06:01 | 0.00 | 0.00 | 8573.03 | 0.00 | 0.00 | 0.00 | 106.56 | 98.85 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2367.45 | 0.00 | -28.00 | -7020.89 |
PERIMETER_TOP_ZN_2 | 07-FEB-06:03 | 0.00 | 0.00 | 5194.91 | 0.00 | 0.00 | 0.00 | 63.55 | 62.58 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1076.67 | 0.00 | -17.09 | -4631.10 |
PERIMETER_TOP_ZN_1 | 06-FEB-06:01 | 0.00 | 0.00 | 8212.26 | 0.00 | 0.00 | 0.00 | 105.49 | 98.85 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1966.71 | 0.00 | -14.52 | -7073.25 |
PERIMETER_TOP_ZN_4 | 21-JAN-06:03 | 0.00 | 0.00 | 5156.75 | 0.00 | 0.00 | 0.00 | 63.59 | 62.58 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1682.63 | 0.00 | -30.51 | -3973.59 |
PERIMETER_BOT_ZN_3 | 22-DEC-07:03 | 0.00 | 0.00 | 4734.65 | 0.00 | 0.00 | 0.00 | 190.32 | 296.56 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1397.02 | 0.00 | -6.84 | -4455.55 |
PERIMETER_BOT_ZN_2 | 22-DEC-07:03 | 0.00 | 0.00 | 3156.04 | 0.00 | 0.00 | 0.00 | 120.72 | 187.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -933.75 | 0.00 | -4.56 | -2930.01 |
PERIMETER_BOT_ZN_1 | 21-DEC-07:10 | 0.00 | 0.00 | 6215.64 | 0.00 | 0.00 | 0.00 | 193.30 | 296.56 | 637.88 | 0.00 | 0.00 | 0.00 | 14003.90 | 0.00 | -2677.75 | 0.00 | -18669.52 | 0.00 |
PERIMETER_BOT_ZN_4 | 07-JAN-07:03 | 0.00 | 0.00 | 3139.18 | 0.00 | 0.00 | 0.00 | 60.32 | 62.58 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1488.93 | 0.00 | -7.37 | -2169.58 |
PERIMETER_MID_ZN_3 | 06-FEB-06:01 | 0.00 | 0.00 | 5684.21 | 0.00 | 0.00 | 0.00 | 100.36 | 98.85 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2175.69 | 0.00 | -12.99 | -4332.62 |
PERIMETER_MID_ZN_2 | 10-JAN-07:04 | 0.00 | 0.00 | 3605.09 | 0.00 | 0.00 | 0.00 | 122.37 | 187.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1588.16 | 0.00 | -18.58 | -2712.27 |
PERIMETER_MID_ZN_1 | 25-JAN-07:02 | 0.00 | 0.00 | 5437.22 | 0.00 | 0.00 | 0.00 | 189.90 | 296.56 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1741.39 | 0.00 | -18.32 | -4801.85 |
PERIMETER_MID_ZN_4 | 10-JAN-06:01 | 0.00 | 0.00 | 3731.86 | 0.00 | 0.00 | 0.00 | 62.17 | 62.58 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1568.80 | 0.00 | -15.75 | -2675.86 |
TOPFLOOR_PLENUM | 21-DEC-07:03 | 8299.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -44.29 | -8255.50 |
MIDFLOOR_PLENUM | 31-DEC-12:23 | 3316.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3324.62 |
FIRSTFLOOR_PLENUM | 04-DEC-06:02 | 5220.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -55.28 | -5165.40 |
Total Facility | 06-FEB-07:01 | -3564.71 | 9052.54 | 82135.32 | -9052.54 | 0.00 | 0.00 | 4508.57 | 7126.03 | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21548.70 | 0.00 | -21233.21 | -68522.11 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.1055 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.6128 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.4344 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.8601 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.8543 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5521 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.5527 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3226 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.2172 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.2808 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.4272 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3540 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7059 | 2.7059 | 0.7658 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9472 | 1.9472 | 0.7244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0757 | 2.0757 | 0.7618 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6396 | 0.6396 | 0.1605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6436 | 0.6436 | 0.1287 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7827 | 0.7827 | 0.1605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7128 | 0.7128 | 0.1426 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5501 | 0.5501 | 0.1612 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5751 | 0.5751 | 0.1150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6770 | 0.6770 | 0.1611 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5973 | 0.5973 | 0.1195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5478 | 0.5478 | 0.1528 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6148 | 0.6148 | 0.1230 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6854 | 0.6854 | 0.1529 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6391 | 0.6391 | 0.1278 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.1055 | 4.6128 | 5.1055 | 1.3226 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.4344 | 3.8601 | 4.4344 | 1.2808 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.8543 | 4.5521 | 4.8543 | 1.3540 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3529 | 1.3529 | 0.7658 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9736 | 0.9736 | 0.7244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0378 | 1.0378 | 0.7618 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3198 | 0.3198 | 0.1605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3218 | 0.3218 | 0.1287 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3914 | 0.3914 | 0.1605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3564 | 0.3564 | 0.1426 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2751 | 0.2751 | 0.1612 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2876 | 0.2876 | 0.1150 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3385 | 0.3385 | 0.1611 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2986 | 0.2986 | 0.1195 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2739 | 0.2739 | 0.1528 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3074 | 0.3074 | 0.1230 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3427 | 0.3427 | 0.1529 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3196 | 0.3196 | 0.1278 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.5527 | 1.3226 | 1.3226 | 1.3226 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.2172 | 1.2808 | 1.2808 | 1.2808 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.4272 | 1.3540 | 1.3540 | 1.3540 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 74.83 |
Number of hours cooling loads not met | 302.00 |
Number of hours not met | 376.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 14.44 | 81587.44 | 0.59 | 12382.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 505.46 | 72587.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 202.63 | 20527.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 49.86 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.66 | 834.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 79.58 | 13414.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 10.36 | 907.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 93.98 | 8988.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1579.43 |
Natural Gas | 0.00 | 94.56 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1674.00 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 40.67 |
Space Heating | 2.90 |
Space Cooling | 101.45 |
Fans (All) | 15.97 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 317.02 |
Subtotal | 317.02 |
Natural Gas [MJ/m2] | |
Space Heating | 0.12 |
Service Water Heating | 18.86 |
Miscellaneous (All) | 18.98 |
Subtotal | 18.98 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.10 |
Space Heating | 0.90 |
Space Cooling | 30.20 |
Fans (All) | 4.75 |
Service Water Heating | 5.61 |
Receptacle Equipment | 42.14 |
Miscellaneous | 4.29 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8732.00 | 28.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8691.33 | 68.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8614.67 | 145.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8625.67 | 134.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8604.83 | 155.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8670.83 | 89.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8673.17 | 86.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8666.17 | 93.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8699.33 | 60.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8623.67 | 136.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8623.00 | 137.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8604.50 | 155.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8490.83 | 269.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8490.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 269.17 | 0.00 | 0.00 | 0.00 |
Average | 8672.62 | 87.38 | 0.00 | 0.00 | 0.00 |
Sum | 156107.17 | 1572.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128293.67 | 10.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24902.17 | 6.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 10.33 | 0.00 | 0.00 | 0.00 |
Average | 34142.38 | 0.95 | 0.00 | 0.00 | 0.00 |
Sum | 614562.83 | 17.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8308.17 | 451.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7946.00 | 814.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7848.50 | 911.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7877.33 | 882.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7830.17 | 929.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8280.50 | 479.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8049.17 | 710.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7237.00 | 1523.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8019.33 | 740.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8086.50 | 673.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7969.00 | 791.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8004.50 | 755.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7935.67 | 824.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8172.83 | 587.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8655.17 | 104.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8677.00 | 83.00 | 0.00 | 0.00 | 0.00 |
Min | 7237.00 | 2.50 | 0.00 | 0.00 | 0.00 |
Max | 8757.50 | 1523.00 | 0.00 | 0.00 | 0.00 |
Average | 8133.87 | 626.13 | 0.00 | 0.00 | 0.00 |
Sum | 146409.67 | 11270.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128163.00 | 141.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128300.00 | 4.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128298.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24906.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24906.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 19719.83 | 5189.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24907.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24907.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128300.00 | 5189.17 | 0.00 | 0.00 | 0.00 |
Average | 33846.19 | 297.14 | 0.00 | 0.00 | 0.00 |
Sum | 609231.50 | 5348.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185478E+11 | 40380.58 | 02-JAN-05:03 | 16.83 | 15.69 | 0.197306E+10 | 2606.69 | 05-JAN-14:09 | 14.17 | 9.63 |
February | 0.169206E+11 | 39146.06 | 03-FEB-06:03 | 18.90 | 18.50 | 0.179336E+10 | 2606.61 | 27-FEB-10:09 | 21.37 | 19.24 |
March | 0.207351E+11 | 39565.18 | 01-MAR-06:03 | 15.52 | 13.84 | 0.214410E+10 | 2606.65 | 23-MAR-09:09 | 16.78 | 14.63 |
April | 0.213294E+11 | 39823.87 | 22-APR-05:03 | 20.00 | 18.87 | 0.191468E+10 | 2606.70 | 10-APR-13:00 | 20.00 | 18.87 |
May | 0.266861E+11 | 41473.27 | 01-MAY-04:03 | 26.10 | 23.70 | 0.207565E+10 | 2606.54 | 22-MAY-13:30 | 25.30 | 23.68 |
June | 0.268000E+11 | 40977.36 | 20-JUN-04:03 | 24.50 | 23.30 | 0.206888E+10 | 2606.54 | 01-JUN-13:20 | 24.50 | 23.30 |
July | 0.265259E+11 | 40619.04 | 11-JUL-04:03 | 24.60 | 23.70 | 0.192246E+10 | 2606.54 | 03-JUL-13:30 | 24.60 | 23.70 |
August | 0.284191E+11 | 40679.32 | 29-AUG-04:03 | 23.07 | 22.97 | 0.215849E+10 | 2606.54 | 25-AUG-13:30 | 23.07 | 22.97 |
September | 0.259817E+11 | 40689.80 | 01-SEP-04:03 | 23.77 | 23.15 | 0.191559E+10 | 2606.54 | 18-SEP-13:30 | 28.85 | 26.16 |
October | 0.261417E+11 | 40578.98 | 12-OCT-04:03 | 21.92 | 21.33 | 0.199219E+10 | 2606.69 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.220556E+11 | 39404.56 | 14-NOV-06:03 | 15.42 | 11.91 | 0.196845E+10 | 2606.63 | 24-NOV-10:09 | 20.68 | 16.28 |
December | 0.196061E+11 | 39774.54 | 16-DEC-06:03 | 20.83 | 19.18 | 0.190946E+10 | 2606.65 | 08-DEC-10:00 | 20.83 | 19.18 |
Annual Sum or Average | 0.279749E+12 | 0.238363E+11 | ||||||||
Minimum of Months | 0.169206E+11 | 39146.06 | 15.42 | 11.91 | 0.179336E+10 | 2606.54 | 14.17 | 9.63 | ||
Maximum of Months | 0.284191E+11 | 41473.27 | 26.10 | 23.70 | 0.215849E+10 | 2606.70 | 28.85 | 26.16 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151411E+10 | 5266.96 | 19-JAN-15:00 | 25.00 | 21.54 | 0.00 | 0.00 | 01-JAN-00:10 | 25.00 | 21.54 |
February | 0.186436E+10 | 6187.04 | 27-FEB-15:00 | 26.10 | 20.43 | 0.00 | 0.00 | 01-FEB-00:10 | 26.10 | 20.43 |
March | 0.245358E+10 | 6166.43 | 29-MAR-14:50 | 26.83 | 21.36 | 0.00 | 0.00 | 01-MAR-00:10 | 26.83 | 21.36 |
April | 0.386499E+10 | 8770.75 | 28-APR-15:10 | 33.12 | 23.52 | 0.00 | 0.00 | 01-APR-00:10 | 33.12 | 23.52 |
May | 0.628590E+10 | 9495.42 | 10-MAY-15:00 | 32.80 | 23.10 | 0.00 | 0.00 | 01-MAY-00:10 | 32.80 | 23.10 |
June | 0.695660E+10 | 9519.95 | 28-JUN-14:30 | 33.60 | 26.19 | 0.00 | 0.00 | 01-JUN-00:10 | 33.60 | 26.19 |
July | 0.663243E+10 | 9905.76 | 18-JUL-14:50 | 35.00 | 25.65 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.65 |
August | 0.670454E+10 | 9605.62 | 03-AUG-15:20 | 35.17 | 24.83 | 0.00 | 0.00 | 01-AUG-00:10 | 35.17 | 24.83 |
September | 0.519009E+10 | 8963.38 | 01-SEP-14:00 | 32.20 | 22.62 | 0.00 | 0.00 | 01-SEP-00:10 | 32.20 | 22.62 |
October | 0.506209E+10 | 9141.25 | 05-OCT-15:00 | 34.00 | 24.05 | 0.00 | 0.00 | 01-OCT-00:10 | 34.00 | 24.05 |
November | 0.255580E+10 | 7363.64 | 02-NOV-14:20 | 29.40 | 24.36 | 0.00 | 0.00 | 01-NOV-00:10 | 29.40 | 24.36 |
December | 0.178795E+10 | 6449.13 | 15-DEC-15:10 | 28.83 | 21.51 | 0.00 | 0.00 | 01-DEC-00:10 | 28.83 | 21.51 |
Annual Sum or Average | 0.508724E+11 | 0.00 | ||||||||
Minimum of Months | 0.151411E+10 | 5266.96 | 25.00 | 20.43 | 0.00 | 0.00 | 25.00 | 20.43 | ||
Maximum of Months | 0.695660E+10 | 9905.76 | 35.17 | 26.19 | 0.00 | 0.00 | 35.17 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.740892E+09 | 2930.81 | 04-JAN-07:01 | 1.17 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.17 | -1.3 |
February | 0.880218E+09 | 2538.80 | 13-FEB-07:01 | 4.08 | 0.66 | 0.00 | 0.00 | 01-FEB-00:10 | 4.08 | 0.66 |
March | 0.118095E+10 | 3110.64 | 09-MAR-07:01 | 1.18 | -2.3 | 0.00 | 0.00 | 01-MAR-00:10 | 1.18 | -2.3 |
April | 0.187841E+10 | 3093.05 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.350868E+10 | 3873.67 | 22-MAY-06:03 | 26.10 | 22.55 | 0.00 | 0.00 | 01-MAY-00:10 | 26.10 | 22.55 |
June | 0.370119E+10 | 3777.63 | 12-JUN-16:00 | 33.30 | 21.04 | 0.00 | 0.00 | 01-JUN-00:10 | 33.30 | 21.04 |
July | 0.371126E+10 | 4462.07 | 05-JUL-06:03 | 26.10 | 25.13 | 0.00 | 0.00 | 01-JUL-00:10 | 26.10 | 25.13 |
August | 0.380777E+10 | 4069.88 | 28-AUG-15:30 | 33.00 | 24.29 | 0.00 | 0.00 | 01-AUG-00:10 | 33.00 | 24.29 |
September | 0.312869E+10 | 4217.08 | 05-SEP-06:03 | 22.82 | 22.82 | 0.00 | 0.00 | 01-SEP-00:10 | 22.82 | 22.82 |
October | 0.303510E+10 | 4442.04 | 10-OCT-14:10 | 30.83 | 22.61 | 0.00 | 0.00 | 01-OCT-00:10 | 30.83 | 22.61 |
November | 0.143727E+10 | 3147.53 | 06-NOV-16:20 | 27.73 | 20.09 | 0.00 | 0.00 | 01-NOV-00:10 | 27.73 | 20.09 |
December | 0.976911E+09 | 2448.75 | 15-DEC-16:00 | 28.00 | 21.24 | 0.00 | 0.00 | 01-DEC-00:10 | 28.00 | 21.24 |
Annual Sum or Average | 0.279873E+11 | 0.00 | ||||||||
Minimum of Months | 0.740892E+09 | 2448.75 | 1.17 | -2.3 | 0.00 | 0.00 | 1.17 | -2.3 | ||
Maximum of Months | 0.380777E+10 | 4462.07 | 33.30 | 25.55 | 0.00 | 0.00 | 33.30 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109021E+10 | 3329.66 | 03-JAN-07:08 | 2.33 | 0.16 | 0.00 | 0.00 | 01-JAN-00:10 | 2.33 | 0.16 |
February | 0.119950E+10 | 2910.68 | 17-FEB-07:01 | 1.28 | -1.4 | 0.00 | 0.00 | 01-FEB-00:10 | 1.28 | -1.4 |
March | 0.157855E+10 | 3071.69 | 09-MAR-07:09 | 1.18 | -2.3 | 0.00 | 0.00 | 01-MAR-00:10 | 1.18 | -2.3 |
April | 0.222051E+10 | 3367.27 | 28-APR-16:00 | 32.20 | 25.55 | 0.00 | 0.00 | 01-APR-00:10 | 32.20 | 25.55 |
May | 0.377164E+10 | 4280.04 | 22-MAY-06:03 | 26.10 | 22.55 | 0.00 | 0.00 | 01-MAY-00:10 | 26.10 | 22.55 |
June | 0.397415E+10 | 4118.71 | 19-JUN-12:20 | 29.63 | 24.68 | 0.00 | 0.00 | 01-JUN-00:10 | 29.63 | 24.68 |
July | 0.404462E+10 | 4921.56 | 05-JUL-06:03 | 26.10 | 25.13 | 0.00 | 0.00 | 01-JUL-00:10 | 26.10 | 25.13 |
August | 0.438311E+10 | 4622.47 | 14-AUG-12:20 | 29.77 | 25.46 | 0.00 | 0.00 | 01-AUG-00:10 | 29.77 | 25.46 |
September | 0.369752E+10 | 4909.25 | 05-SEP-06:03 | 22.82 | 22.82 | 0.00 | 0.00 | 01-SEP-00:10 | 22.82 | 22.82 |
October | 0.366787E+10 | 4783.41 | 10-OCT-15:10 | 30.00 | 22.39 | 0.00 | 0.00 | 01-OCT-00:10 | 30.00 | 22.39 |
November | 0.207567E+10 | 3849.62 | 06-NOV-17:00 | 26.60 | 19.72 | 0.00 | 0.00 | 01-NOV-00:10 | 26.60 | 19.72 |
December | 0.142681E+10 | 3189.03 | 18-DEC-07:09 | 2.50 | 0.21 | 0.00 | 0.00 | 01-DEC-00:10 | 2.50 | 0.21 |
Annual Sum or Average | 0.331302E+11 | 0.00 | ||||||||
Minimum of Months | 0.109021E+10 | 2910.68 | 1.18 | -2.3 | 0.00 | 0.00 | 1.18 | -2.3 | ||
Maximum of Months | 0.438311E+10 | 4921.56 | 32.20 | 25.55 | 0.00 | 0.00 | 32.20 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130149E+11 | 25692.10 | 02-JAN-06:03 | 16.00 | 15.39 | 0.180946E+10 | 2606.58 | 02-JAN-10:30 | 22.00 | 18.46 |
February | 0.119987E+11 | 13418.40 | 28-FEB-17:00 | 23.80 | 20.44 | 0.167722E+10 | 2606.65 | 27-FEB-10:09 | 23.80 | 20.44 |
March | 0.146330E+11 | 22182.55 | 27-MAR-05:03 | 19.82 | 18.59 | 0.203810E+10 | 2606.62 | 27-MAR-09:09 | 22.38 | 20.64 |
April | 0.152248E+11 | 28697.75 | 24-APR-05:03 | 20.08 | 20.03 | 0.188878E+10 | 2606.64 | 10-APR-13:00 | 20.08 | 20.03 |
May | 0.197450E+11 | 28806.17 | 17-MAY-05:03 | 22.38 | 20.70 | 0.206761E+10 | 2606.54 | 15-MAY-09:09 | 22.38 | 20.70 |
June | 0.198727E+11 | 28951.34 | 07-JUN-05:03 | 21.10 | 18.90 | 0.206221E+10 | 2606.54 | 26-JUN-09:09 | 27.48 | 24.72 |
July | 0.199762E+11 | 29076.53 | 11-JUL-04:03 | 24.60 | 23.70 | 0.191584E+10 | 2606.55 | 14-JUL-09:09 | 24.08 | 23.26 |
August | 0.206618E+11 | 28765.05 | 17-AUG-05:03 | 22.65 | 22.15 | 0.215188E+10 | 2606.54 | 17-AUG-09:09 | 26.28 | 23.28 |
September | 0.188060E+11 | 28804.27 | 25-SEP-04:03 | 23.72 | 22.35 | 0.190671E+10 | 2606.54 | 08-SEP-09:09 | 23.72 | 22.35 |
October | 0.185122E+11 | 29562.94 | 11-OCT-04:03 | 23.03 | 22.27 | 0.198028E+10 | 2606.68 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.147327E+11 | 28789.19 | 06-NOV-06:03 | 18.80 | 17.70 | 0.192386E+10 | 2606.60 | 13-NOV-14:09 | 23.30 | 17.20 |
December | 0.134084E+11 | 20560.03 | 11-DEC-06:03 | 20.83 | 20.26 | 0.179162E+10 | 2606.61 | 18-DEC-14:09 | 16.17 | 10.34 |
Annual Sum or Average | 0.200586E+12 | 0.232136E+11 | ||||||||
Minimum of Months | 0.119987E+11 | 13418.40 | 16.00 | 15.39 | 0.167722E+10 | 2606.54 | 16.17 | 10.34 | ||
Maximum of Months | 0.206618E+11 | 29562.94 | 24.60 | 23.70 | 0.215188E+10 | 2606.68 | 27.48 | 24.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120648E+11 | 19026.80 | 02-JAN-06:03 | 16.00 | 15.39 | 0.169927E+10 | 2606.62 | 02-JAN-10:09 | 20.67 | 17.79 |
February | 0.116493E+11 | 14184.76 | 27-FEB-17:00 | 24.40 | 20.28 | 0.159894E+10 | 2606.53 | 23-FEB-14:09 | 24.40 | 20.28 |
March | 0.144337E+11 | 14723.26 | 29-MAR-16:00 | 26.60 | 21.18 | 0.195605E+10 | 2606.57 | 30-MAR-09:00 | 24.40 | 20.28 |
April | 0.157794E+11 | 24693.25 | 24-APR-05:03 | 20.08 | 20.03 | 0.185422E+10 | 2606.65 | 10-APR-13:00 | 20.08 | 20.03 |
May | 0.212349E+11 | 31095.23 | 08-MAY-04:03 | 24.32 | 22.06 | 0.206612E+10 | 2606.56 | 12-MAY-09:09 | 26.88 | 22.17 |
June | 0.216096E+11 | 31218.64 | 19-JUN-04:03 | 25.50 | 24.30 | 0.206173E+10 | 2606.60 | 07-JUN-09:09 | 25.50 | 24.30 |
July | 0.217152E+11 | 31211.14 | 31-JUL-04:03 | 24.40 | 23.27 | 0.191568E+10 | 2606.55 | 14-JUL-09:09 | 24.40 | 23.27 |
August | 0.221093E+11 | 30668.21 | 29-AUG-05:03 | 22.68 | 22.68 | 0.215021E+10 | 2606.55 | 17-AUG-09:09 | 22.68 | 22.68 |
September | 0.196731E+11 | 31638.25 | 05-SEP-04:02 | 22.72 | 22.72 | 0.190232E+10 | 2606.57 | 28-SEP-09:09 | 24.68 | 22.58 |
October | 0.190124E+11 | 32152.09 | 10-OCT-04:02 | 22.00 | 19.97 | 0.196442E+10 | 2606.68 | 02-OCT-09:09 | 22.00 | 19.97 |
November | 0.144340E+11 | 16786.45 | 03-NOV-05:03 | 22.28 | 21.91 | 0.185023E+10 | 2606.65 | 06-NOV-10:09 | 24.08 | 20.08 |
December | 0.126673E+11 | 15073.30 | 15-DEC-16:40 | 28.00 | 21.24 | 0.168627E+10 | 2606.52 | 12-DEC-14:09 | 28.00 | 21.24 |
Annual Sum or Average | 0.206383E+12 | 0.227055E+11 | ||||||||
Minimum of Months | 0.116493E+11 | 14184.76 | 16.00 | 15.39 | 0.159894E+10 | 2606.52 | 20.08 | 17.79 | ||
Maximum of Months | 0.221093E+11 | 32152.09 | 28.00 | 24.30 | 0.215021E+10 | 2606.68 | 28.00 | 24.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.196773E+10 | 3759.27 | 02-JAN-14:10 | 26.17 | 18.43 | 0.343753E+09 | 549.47 | 02-JAN-14:09 | 26.17 | 18.43 |
February | 0.222834E+10 | 3773.10 | 28-FEB-15:00 | 25.00 | 20.38 | 0.327124E+09 | 549.48 | 28-FEB-10:00 | 25.00 | 20.38 |
March | 0.299322E+10 | 4822.12 | 30-MAR-13:30 | 28.55 | 22.55 | 0.400311E+09 | 549.48 | 24-MAR-13:00 | 28.55 | 22.55 |
April | 0.390845E+10 | 5879.39 | 28-APR-15:10 | 33.12 | 23.52 | 0.387037E+09 | 549.49 | 12-APR-13:00 | 33.12 | 23.52 |
May | 0.635319E+10 | 9335.59 | 22-MAY-04:02 | 26.10 | 22.31 | 0.437313E+09 | 549.48 | 26-MAY-13:00 | 28.30 | 24.27 |
June | 0.689340E+10 | 9327.53 | 05-JUN-04:03 | 25.22 | 22.37 | 0.436219E+09 | 549.48 | 07-JUN-09:09 | 26.78 | 22.12 |
July | 0.674881E+10 | 10717.17 | 23-JUL-14:43 | 31.97 | 24.85 | 0.405823E+09 | 549.48 | 11-JUL-13:00 | 31.97 | 24.85 |
August | 0.670512E+10 | 9821.46 | 20-AUG-16:42 | 30.33 | 24.49 | 0.454782E+09 | 549.47 | 25-AUG-13:00 | 28.30 | 24.28 |
September | 0.541044E+10 | 10593.86 | 10-SEP-16:12 | 33.90 | 26.90 | 0.402570E+09 | 549.48 | 28-SEP-09:09 | 24.68 | 22.58 |
October | 0.498725E+10 | 6482.05 | 07-OCT-05:03 | 26.17 | 26.04 | 0.412390E+09 | 549.50 | 02-OCT-09:50 | 26.17 | 26.04 |
November | 0.308379E+10 | 4823.81 | 02-NOV-14:00 | 29.40 | 24.47 | 0.380481E+09 | 549.49 | 06-NOV-10:30 | 24.65 | 20.15 |
December | 0.231029E+10 | 4233.81 | 15-DEC-15:00 | 29.00 | 21.56 | 0.340471E+09 | 549.47 | 11-DEC-14:00 | 29.00 | 21.56 |
Annual Sum or Average | 0.535900E+11 | 0.472828E+10 | ||||||||
Minimum of Months | 0.196773E+10 | 3759.27 | 25.00 | 18.43 | 0.327124E+09 | 549.47 | 24.65 | 18.43 | ||
Maximum of Months | 0.689340E+10 | 10717.17 | 33.90 | 26.90 | 0.454782E+09 | 549.50 | 33.12 | 26.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186517E+10 | 3973.86 | 19-JAN-10:30 | 23.85 | 21.17 | 0.227849E+09 | 347.87 | 02-JAN-10:30 | 23.85 | 21.17 |
February | 0.205106E+10 | 4246.85 | 27-FEB-10:40 | 22.17 | 19.29 | 0.217350E+09 | 347.87 | 27-FEB-10:09 | 22.17 | 19.29 |
March | 0.279075E+10 | 5244.66 | 26-MAR-09:35 | 24.77 | 20.03 | 0.266203E+09 | 347.88 | 06-MAR-10:09 | 24.77 | 20.03 |
April | 0.371940E+10 | 11183.50 | 23-APR-08:43 | 24.03 | 20.36 | 0.250004E+09 | 347.88 | 10-APR-13:00 | 24.03 | 20.36 |
May | 0.546525E+10 | 11300.56 | 28-MAY-09:02 | 29.08 | 24.49 | 0.276975E+09 | 347.86 | 09-MAY-09:30 | 29.08 | 24.49 |
June | 0.573714E+10 | 11183.65 | 04-JUN-11:23 | 28.60 | 23.34 | 0.276169E+09 | 347.87 | 07-JUN-09:09 | 26.78 | 22.12 |
July | 0.563316E+10 | 11267.32 | 30-JUL-09:13 | 29.60 | 25.25 | 0.256951E+09 | 347.86 | 24-JUL-09:30 | 29.60 | 25.25 |
August | 0.553368E+10 | 11290.95 | 06-AUG-10:02 | 30.17 | 26.87 | 0.287822E+09 | 347.86 | 25-AUG-13:00 | 28.30 | 24.28 |
September | 0.449515E+10 | 11258.39 | 10-SEP-09:32 | 33.77 | 27.16 | 0.254879E+09 | 347.86 | 21-SEP-09:09 | 22.98 | 21.00 |
October | 0.431567E+10 | 8923.19 | 09-OCT-09:53 | 29.00 | 22.62 | 0.262345E+09 | 347.88 | 02-OCT-09:00 | 29.00 | 22.62 |
November | 0.268012E+10 | 5068.13 | 02-NOV-10:00 | 27.70 | 24.03 | 0.250669E+09 | 347.87 | 06-NOV-10:09 | 24.08 | 20.08 |
December | 0.197297E+10 | 3290.61 | 16-DEC-10:20 | 24.67 | 21.43 | 0.222929E+09 | 347.87 | 08-DEC-10:00 | 24.67 | 21.43 |
Annual Sum or Average | 0.462595E+11 | 0.305014E+10 | ||||||||
Minimum of Months | 0.186517E+10 | 3290.61 | 22.17 | 19.29 | 0.217350E+09 | 347.86 | 22.17 | 19.29 | ||
Maximum of Months | 0.573714E+10 | 11300.56 | 33.77 | 27.16 | 0.287822E+09 | 347.88 | 29.60 | 25.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.416448E+10 | 14123.68 | 01-JAN-14:12 | 25.67 | 18.12 | 0.390513E+09 | 549.50 | 05-JAN-14:09 | 14.17 | 9.63 |
February | 0.420922E+10 | 13980.69 | 26-FEB-13:32 | 26.43 | 19.30 | 0.357374E+09 | 549.50 | 09-FEB-14:00 | 26.43 | 19.30 |
March | 0.430660E+10 | 12764.08 | 26-MAR-15:02 | 24.18 | 19.83 | 0.420004E+09 | 549.50 | 24-MAR-13:00 | 24.18 | 19.83 |
April | 0.484082E+10 | 9390.38 | 23-APR-15:23 | 28.25 | 21.80 | 0.390133E+09 | 549.51 | 10-APR-13:00 | 28.25 | 21.80 |
May | 0.650490E+10 | 11912.18 | 29-MAY-14:13 | 32.40 | 23.19 | 0.437125E+09 | 549.48 | 26-MAY-13:50 | 32.40 | 23.19 |
June | 0.668103E+10 | 10470.09 | 25-JUN-13:43 | 32.70 | 24.38 | 0.435940E+09 | 549.48 | 07-JUN-09:09 | 32.70 | 24.38 |
July | 0.671127E+10 | 12970.56 | 23-JUL-14:43 | 31.97 | 24.85 | 0.405688E+09 | 549.48 | 14-JUL-13:00 | 31.97 | 24.85 |
August | 0.742561E+10 | 13065.80 | 06-AUG-14:43 | 31.50 | 24.70 | 0.454897E+09 | 549.48 | 25-AUG-13:00 | 28.30 | 24.28 |
September | 0.670956E+10 | 13838.41 | 24-SEP-13:23 | 31.35 | 25.17 | 0.403337E+09 | 549.48 | 20-SEP-13:00 | 31.35 | 25.17 |
October | 0.775613E+10 | 14099.60 | 09-OCT-13:12 | 31.00 | 23.42 | 0.416753E+09 | 558.29 | 10-OCT-13:09 | 31.00 | 22.17 |
November | 0.587800E+10 | 14554.62 | 11-NOV-12:52 | 26.60 | 22.72 | 0.404563E+09 | 572.22 | 06-NOV-14:09 | 26.60 | 22.72 |
December | 0.484751E+10 | 14680.82 | 10-DEC-12:42 | 27.00 | 20.34 | 0.376336E+09 | 554.99 | 15-DEC-14:39 | 29.00 | 21.74 |
Annual Sum or Average | 0.700351E+11 | 0.489266E+10 | ||||||||
Minimum of Months | 0.416448E+10 | 9390.38 | 24.18 | 18.12 | 0.357374E+09 | 549.48 | 14.17 | 9.63 | ||
Maximum of Months | 0.775613E+10 | 14680.82 | 32.70 | 25.17 | 0.454897E+09 | 572.22 | 32.70 | 25.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.195760E+10 | 8073.11 | 01-JAN-16:53 | 24.00 | 19.35 | 0.222303E+09 | 347.84 | 02-JAN-14:00 | 27.00 | 18.67 |
February | 0.223369E+10 | 11408.92 | 26-FEB-17:33 | 23.67 | 19.48 | 0.208155E+09 | 347.83 | 28-FEB-14:00 | 25.00 | 20.38 |
March | 0.282233E+10 | 6246.94 | 06-MAR-16:30 | 25.55 | 21.32 | 0.251266E+09 | 347.84 | 24-MAR-13:00 | 25.50 | 16.44 |
April | 0.379844E+10 | 12897.78 | 23-APR-16:42 | 27.28 | 21.76 | 0.240924E+09 | 347.85 | 12-APR-13:00 | 27.28 | 21.76 |
May | 0.508185E+10 | 12583.01 | 29-MAY-16:52 | 30.60 | 23.80 | 0.275670E+09 | 347.84 | 12-MAY-09:09 | 30.60 | 23.80 |
June | 0.541692E+10 | 12444.42 | 11-JUN-16:52 | 33.30 | 21.96 | 0.275196E+09 | 347.84 | 01-JUN-13:39 | 33.30 | 21.96 |
July | 0.519659E+10 | 11623.39 | 23-JUL-14:43 | 31.97 | 24.85 | 0.256118E+09 | 347.84 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.541272E+10 | 11697.10 | 06-AUG-17:23 | 25.50 | 23.74 | 0.286936E+09 | 347.84 | 07-AUG-13:00 | 24.00 | 22.63 |
September | 0.450857E+10 | 12692.06 | 17-SEP-15:52 | 32.20 | 25.55 | 0.253163E+09 | 347.84 | 07-SEP-13:00 | 32.20 | 25.55 |
October | 0.440625E+10 | 12682.68 | 09-OCT-16:32 | 28.00 | 21.42 | 0.258762E+09 | 347.85 | 17-OCT-13:20 | 22.33 | 15.56 |
November | 0.291375E+10 | 6482.83 | 06-NOV-16:00 | 28.30 | 20.26 | 0.238833E+09 | 347.84 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.224457E+10 | 5764.93 | 15-DEC-15:40 | 28.33 | 21.35 | 0.217606E+09 | 347.84 | 01-DEC-14:00 | 28.33 | 21.35 |
Annual Sum or Average | 0.459933E+11 | 0.298493E+10 | ||||||||
Minimum of Months | 0.195760E+10 | 5764.93 | 23.67 | 19.35 | 0.208155E+09 | 347.83 | 22.20 | 15.14 | ||
Maximum of Months | 0.541692E+10 | 12897.78 | 33.30 | 25.55 | 0.286936E+09 | 347.85 | 33.30 | 25.55 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259166E+10 | 3348.41 | 02-JAN-13:30 | 26.00 | 18.64 | 0.357161E+09 | 549.49 | 02-JAN-10:50 | 26.00 | 18.64 |
February | 0.237607E+10 | 2822.88 | 28-FEB-15:00 | 25.00 | 20.38 | 0.332490E+09 | 549.47 | 01-FEB-14:39 | 25.00 | 20.38 |
March | 0.292121E+10 | 3582.40 | 30-MAR-13:30 | 28.55 | 22.55 | 0.403493E+09 | 549.47 | 30-MAR-13:00 | 27.70 | 22.30 |
April | 0.324994E+10 | 4166.92 | 28-APR-15:10 | 33.12 | 23.52 | 0.386461E+09 | 549.48 | 18-APR-13:00 | 33.12 | 23.52 |
May | 0.523093E+10 | 7365.97 | 22-MAY-04:02 | 26.10 | 22.31 | 0.436496E+09 | 549.48 | 30-MAY-09:09 | 27.98 | 24.19 |
June | 0.580934E+10 | 5648.89 | 19-JUN-14:00 | 31.70 | 25.12 | 0.435748E+09 | 549.48 | 01-JUN-13:09 | 31.70 | 25.12 |
July | 0.607837E+10 | 7742.93 | 10-JUL-04:03 | 25.40 | 23.80 | 0.405490E+09 | 549.48 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.661391E+10 | 7353.58 | 14-AUG-04:02 | 26.10 | 24.05 | 0.455172E+09 | 549.48 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.556908E+10 | 7295.15 | 05-SEP-04:02 | 22.72 | 22.72 | 0.403790E+09 | 549.48 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.518906E+10 | 6072.14 | 07-OCT-05:03 | 26.17 | 26.04 | 0.417653E+09 | 549.50 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.339609E+10 | 4379.31 | 03-NOV-14:00 | 29.40 | 23.47 | 0.398021E+09 | 549.48 | 06-NOV-10:09 | 24.08 | 20.08 |
December | 0.288737E+10 | 3787.93 | 15-DEC-14:10 | 29.00 | 22.01 | 0.359704E+09 | 549.48 | 11-DEC-10:20 | 29.00 | 22.01 |
Annual Sum or Average | 0.519130E+11 | 0.479168E+10 | ||||||||
Minimum of Months | 0.237607E+10 | 2822.88 | 22.72 | 18.64 | 0.332490E+09 | 549.47 | 22.17 | 15.50 | ||
Maximum of Months | 0.661391E+10 | 7742.93 | 33.12 | 26.04 | 0.455172E+09 | 549.50 | 33.12 | 25.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211802E+10 | 3631.74 | 19-JAN-10:30 | 23.85 | 21.17 | 0.243893E+09 | 347.88 | 02-JAN-10:09 | 23.85 | 21.17 |
February | 0.200030E+10 | 3611.90 | 27-FEB-10:30 | 21.90 | 19.28 | 0.225298E+09 | 347.87 | 09-FEB-10:00 | 21.90 | 19.28 |
March | 0.256135E+10 | 3908.94 | 29-MAR-10:30 | 23.55 | 20.55 | 0.272403E+09 | 347.87 | 23-MAR-09:09 | 23.55 | 20.55 |
April | 0.309644E+10 | 7395.51 | 23-APR-08:43 | 24.03 | 20.36 | 0.251968E+09 | 347.88 | 10-APR-13:00 | 24.03 | 20.36 |
May | 0.463035E+10 | 7819.28 | 29-MAY-09:43 | 28.72 | 23.10 | 0.277046E+09 | 347.86 | 09-MAY-09:30 | 28.72 | 23.10 |
June | 0.494455E+10 | 7976.48 | 04-JUN-11:23 | 28.60 | 23.34 | 0.276219E+09 | 347.86 | 12-JUN-09:30 | 29.45 | 22.56 |
July | 0.510533E+10 | 9311.18 | 30-JUL-09:13 | 29.60 | 25.25 | 0.257144E+09 | 347.86 | 24-JUL-09:30 | 29.60 | 25.25 |
August | 0.544409E+10 | 9896.40 | 06-AUG-10:02 | 30.17 | 26.87 | 0.288449E+09 | 347.86 | 22-AUG-09:30 | 30.80 | 26.32 |
September | 0.456562E+10 | 10295.45 | 03-SEP-10:22 | 30.55 | 24.83 | 0.256112E+09 | 347.86 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.445399E+10 | 10200.16 | 09-OCT-09:42 | 28.68 | 22.57 | 0.265385E+09 | 347.88 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.291003E+10 | 4723.92 | 06-NOV-09:50 | 23.53 | 19.90 | 0.259864E+09 | 347.87 | 10-NOV-10:09 | 22.75 | 18.16 |
December | 0.225104E+10 | 3196.14 | 16-DEC-10:20 | 24.67 | 21.43 | 0.238497E+09 | 347.87 | 08-DEC-10:00 | 24.67 | 21.43 |
Annual Sum or Average | 0.440811E+11 | 0.311228E+10 | ||||||||
Minimum of Months | 0.200030E+10 | 3196.14 | 21.90 | 19.28 | 0.225298E+09 | 347.86 | 21.90 | 15.50 | ||
Maximum of Months | 0.544409E+10 | 10295.45 | 30.55 | 26.87 | 0.288449E+09 | 347.88 | 30.80 | 26.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363424E+10 | 12119.38 | 01-JAN-13:52 | 26.00 | 17.88 | 0.382446E+09 | 549.90 | 19-JAN-14:09 | 25.00 | 21.54 |
February | 0.354510E+10 | 11708.60 | 26-FEB-15:23 | 25.80 | 20.01 | 0.350834E+09 | 565.49 | 02-FEB-13:09 | 25.80 | 20.01 |
March | 0.353688E+10 | 9459.39 | 06-MAR-13:00 | 27.20 | 21.71 | 0.408093E+09 | 549.49 | 03-MAR-14:00 | 27.20 | 21.71 |
April | 0.429241E+10 | 10430.77 | 28-APR-16:10 | 32.02 | 25.39 | 0.385705E+09 | 594.87 | 28-APR-12:09 | 32.02 | 25.39 |
May | 0.695175E+10 | 10669.63 | 19-MAY-12:00 | 32.20 | 23.63 | 0.439112E+09 | 614.26 | 19-MAY-12:09 | 32.30 | 23.64 |
June | 0.744762E+10 | 10828.71 | 28-JUN-12:00 | 32.80 | 25.51 | 0.438556E+09 | 623.07 | 28-JUN-12:09 | 32.80 | 25.64 |
July | 0.763207E+10 | 11373.00 | 21-JUL-16:10 | 35.45 | 25.77 | 0.409044E+09 | 654.02 | 20-JUL-12:09 | 35.45 | 25.77 |
August | 0.902465E+10 | 11867.37 | 30-AUG-16:20 | 35.83 | 23.47 | 0.459659E+09 | 646.83 | 10-AUG-12:09 | 35.83 | 23.47 |
September | 0.778619E+10 | 11876.74 | 03-SEP-15:42 | 32.28 | 24.61 | 0.406233E+09 | 633.06 | 01-SEP-12:09 | 32.28 | 24.61 |
October | 0.871220E+10 | 12761.78 | 09-OCT-12:22 | 31.00 | 23.23 | 0.424211E+09 | 654.01 | 06-OCT-12:09 | 31.00 | 23.23 |
November | 0.606738E+10 | 12275.83 | 11-NOV-14:32 | 26.43 | 22.96 | 0.409330E+09 | 614.04 | 02-NOV-12:09 | 26.43 | 22.96 |
December | 0.465979E+10 | 12060.10 | 10-DEC-16:12 | 26.33 | 20.05 | 0.373997E+09 | 585.41 | 15-DEC-13:09 | 28.17 | 22.92 |
Annual Sum or Average | 0.732903E+11 | 0.488722E+10 | ||||||||
Minimum of Months | 0.353688E+10 | 9459.39 | 25.80 | 17.88 | 0.350834E+09 | 549.49 | 25.00 | 20.01 | ||
Maximum of Months | 0.902465E+10 | 12761.78 | 35.83 | 25.77 | 0.459659E+09 | 654.02 | 35.83 | 25.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222155E+10 | 4348.33 | 19-JAN-16:30 | 24.50 | 20.73 | 0.236249E+09 | 347.85 | 02-JAN-10:09 | 24.50 | 20.73 |
February | 0.211837E+10 | 8087.48 | 26-FEB-17:23 | 23.85 | 19.57 | 0.218239E+09 | 347.84 | 28-FEB-10:39 | 21.63 | 19.43 |
March | 0.246878E+10 | 4661.95 | 06-MAR-16:40 | 25.37 | 21.25 | 0.261725E+09 | 347.84 | 27-MAR-09:39 | 22.93 | 20.66 |
April | 0.303601E+10 | 7788.51 | 29-APR-17:42 | 27.47 | 23.28 | 0.247271E+09 | 347.84 | 18-APR-13:00 | 27.47 | 23.28 |
May | 0.419904E+10 | 8395.93 | 29-MAY-16:23 | 31.70 | 23.61 | 0.276431E+09 | 347.84 | 30-MAY-09:30 | 28.35 | 24.32 |
June | 0.457980E+10 | 10524.71 | 11-JUN-16:33 | 32.93 | 21.68 | 0.275986E+09 | 347.84 | 26-JUN-09:09 | 27.48 | 24.72 |
July | 0.461953E+10 | 7871.71 | 03-JUL-04:02 | 26.60 | 24.69 | 0.256886E+09 | 347.84 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.527055E+10 | 8797.78 | 06-AUG-17:23 | 25.50 | 23.74 | 0.288355E+09 | 347.84 | 07-AUG-09:09 | 27.50 | 25.10 |
September | 0.449433E+10 | 10907.99 | 03-SEP-17:02 | 30.90 | 24.81 | 0.255918E+09 | 347.84 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.443882E+10 | 10579.31 | 09-OCT-16:22 | 28.00 | 21.50 | 0.265143E+09 | 347.85 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.295429E+10 | 6016.27 | 06-NOV-16:30 | 27.45 | 20.00 | 0.255059E+09 | 347.84 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.248059E+10 | 5314.71 | 10-DEC-16:12 | 26.33 | 20.05 | 0.234503E+09 | 347.84 | 11-DEC-10:09 | 23.33 | 21.75 |
Annual Sum or Average | 0.428817E+11 | 0.307176E+10 | ||||||||
Minimum of Months | 0.211837E+10 | 4348.33 | 23.85 | 19.57 | 0.218239E+09 | 347.84 | 21.63 | 15.14 | ||
Maximum of Months | 0.527055E+10 | 10907.99 | 32.93 | 24.81 | 0.288355E+09 | 347.85 | 28.35 | 25.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236377E+10 | 3817.98 | 02-JAN-13:30 | 26.00 | 18.64 | 0.356461E+09 | 549.48 | 02-JAN-10:09 | 26.00 | 18.64 |
February | 0.239465E+10 | 3515.03 | 28-FEB-15:00 | 25.00 | 20.38 | 0.338298E+09 | 549.48 | 28-FEB-10:09 | 25.00 | 20.38 |
March | 0.306196E+10 | 4462.93 | 30-MAR-13:30 | 28.55 | 22.55 | 0.413783E+09 | 549.49 | 27-MAR-09:09 | 28.55 | 22.55 |
April | 0.371941E+10 | 5091.61 | 28-APR-15:10 | 33.12 | 23.52 | 0.394273E+09 | 549.49 | 10-APR-13:00 | 33.12 | 23.52 |
May | 0.587798E+10 | 7491.80 | 19-MAY-05:03 | 25.00 | 23.46 | 0.437499E+09 | 549.48 | 30-MAY-09:30 | 28.35 | 24.32 |
June | 0.630761E+10 | 7791.70 | 26-JUN-04:03 | 25.00 | 23.68 | 0.436291E+09 | 549.48 | 01-JUN-13:09 | 25.00 | 23.68 |
July | 0.618761E+10 | 7711.68 | 23-JUL-14:43 | 31.97 | 24.85 | 0.405782E+09 | 549.47 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.622662E+10 | 7480.10 | 07-AUG-05:03 | 24.17 | 23.42 | 0.455042E+09 | 549.47 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.512862E+10 | 7596.15 | 05-SEP-04:02 | 22.72 | 22.72 | 0.403394E+09 | 549.48 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.479957E+10 | 7464.87 | 07-OCT-05:03 | 26.17 | 26.04 | 0.416235E+09 | 549.50 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.315889E+10 | 4371.56 | 03-NOV-14:00 | 29.40 | 23.47 | 0.394246E+09 | 549.48 | 06-NOV-10:09 | 24.08 | 20.08 |
December | 0.260006E+10 | 3869.64 | 15-DEC-15:00 | 29.00 | 21.56 | 0.355163E+09 | 549.48 | 11-DEC-10:09 | 29.00 | 21.56 |
Annual Sum or Average | 0.518267E+11 | 0.480647E+10 | ||||||||
Minimum of Months | 0.236377E+10 | 3515.03 | 22.72 | 18.64 | 0.338298E+09 | 549.47 | 22.17 | 15.50 | ||
Maximum of Months | 0.630761E+10 | 7791.70 | 33.12 | 26.04 | 0.455042E+09 | 549.50 | 33.12 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204387E+10 | 4139.83 | 19-JAN-10:00 | 23.00 | 20.89 | 0.173085E+09 | 338.71 | 18-JAN-11:20 | 23.00 | 20.89 |
February | 0.211713E+10 | 4260.22 | 27-FEB-10:00 | 21.10 | 19.21 | 0.163237E+09 | 338.72 | 09-FEB-11:09 | 21.10 | 19.21 |
March | 0.280881E+10 | 5239.65 | 26-MAR-09:20 | 24.03 | 19.81 | 0.198507E+09 | 338.72 | 06-MAR-08:20 | 24.03 | 19.81 |
April | 0.352622E+10 | 11034.16 | 23-APR-09:12 | 24.97 | 20.75 | 0.185614E+09 | 338.74 | 18-APR-14:20 | 24.97 | 20.75 |
May | 0.499921E+10 | 11061.98 | 14-MAY-09:42 | 28.80 | 23.66 | 0.204851E+09 | 338.74 | 16-MAY-07:19 | 26.67 | 23.47 |
June | 0.519715E+10 | 10190.24 | 11-JUN-08:13 | 25.93 | 21.07 | 0.203992E+09 | 338.74 | 26-JUN-07:19 | 25.77 | 23.98 |
July | 0.510441E+10 | 10692.82 | 30-JUL-09:13 | 29.60 | 25.25 | 0.190415E+09 | 338.74 | 10-JUL-07:19 | 29.60 | 25.25 |
August | 0.506538E+10 | 10674.07 | 06-AUG-10:02 | 30.17 | 26.87 | 0.212609E+09 | 338.73 | 30-AUG-07:19 | 26.63 | 23.73 |
September | 0.418906E+10 | 11150.19 | 03-SEP-09:02 | 29.92 | 24.32 | 0.188796E+09 | 338.73 | 11-SEP-07:19 | 25.87 | 24.34 |
October | 0.408675E+10 | 11073.85 | 09-OCT-09:42 | 28.68 | 22.57 | 0.194922E+09 | 338.73 | 17-OCT-12:20 | 21.33 | 14.79 |
November | 0.271934E+10 | 5117.75 | 06-NOV-09:30 | 23.00 | 19.64 | 0.187875E+09 | 338.74 | 06-NOV-08:30 | 23.00 | 19.64 |
December | 0.212971E+10 | 3539.88 | 16-DEC-10:00 | 24.00 | 21.18 | 0.169511E+09 | 338.72 | 01-DEC-11:20 | 24.00 | 21.18 |
Annual Sum or Average | 0.439870E+11 | 0.227341E+10 | ||||||||
Minimum of Months | 0.204387E+10 | 3539.88 | 21.10 | 19.21 | 0.163237E+09 | 338.71 | 21.10 | 14.79 | ||
Maximum of Months | 0.519715E+10 | 11150.19 | 30.17 | 26.87 | 0.212609E+09 | 338.74 | 29.60 | 25.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.452977E+10 | 12377.90 | 01-JAN-14:12 | 25.67 | 18.12 | 0.400738E+09 | 562.67 | 19-JAN-14:09 | 25.00 | 21.54 |
February | 0.433321E+10 | 12236.54 | 26-FEB-13:32 | 26.43 | 19.30 | 0.365837E+09 | 556.26 | 27-FEB-14:20 | 25.70 | 20.08 |
March | 0.434157E+10 | 11239.39 | 26-MAR-14:13 | 27.93 | 20.14 | 0.431354E+09 | 549.50 | 24-MAR-13:00 | 27.93 | 20.14 |
April | 0.459858E+10 | 7016.66 | 28-APR-14:00 | 32.70 | 23.02 | 0.396465E+09 | 549.51 | 10-APR-13:00 | 32.70 | 23.02 |
May | 0.600841E+10 | 9190.76 | 22-MAY-04:02 | 26.10 | 22.31 | 0.437455E+09 | 549.47 | 03-MAY-13:00 | 26.10 | 22.31 |
June | 0.610230E+10 | 8187.88 | 05-JUN-04:03 | 25.22 | 22.37 | 0.436132E+09 | 549.48 | 01-JUN-13:09 | 25.22 | 22.37 |
July | 0.614900E+10 | 9047.10 | 10-JUL-04:03 | 25.40 | 23.80 | 0.405708E+09 | 549.47 | 12-JUL-13:00 | 23.90 | 21.88 |
August | 0.687773E+10 | 9318.68 | 27-AUG-15:13 | 32.67 | 23.88 | 0.455206E+09 | 549.48 | 25-AUG-13:09 | 32.67 | 23.88 |
September | 0.632900E+10 | 12027.58 | 03-SEP-15:42 | 32.28 | 24.61 | 0.404120E+09 | 549.48 | 20-SEP-13:00 | 26.60 | 22.72 |
October | 0.743210E+10 | 13038.59 | 09-OCT-12:22 | 31.00 | 23.23 | 0.419518E+09 | 569.99 | 10-OCT-13:09 | 31.00 | 22.17 |
November | 0.599463E+10 | 12805.84 | 11-NOV-13:42 | 26.18 | 22.83 | 0.411097E+09 | 586.03 | 06-NOV-14:09 | 26.18 | 22.83 |
December | 0.512235E+10 | 12367.15 | 10-DEC-11:32 | 26.67 | 20.77 | 0.386660E+09 | 567.67 | 15-DEC-14:39 | 29.00 | 21.74 |
Annual Sum or Average | 0.678186E+11 | 0.495029E+10 | ||||||||
Minimum of Months | 0.433321E+10 | 7016.66 | 25.22 | 18.12 | 0.365837E+09 | 549.47 | 23.90 | 20.08 | ||
Maximum of Months | 0.743210E+10 | 13038.59 | 32.70 | 24.61 | 0.455206E+09 | 586.03 | 32.70 | 23.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216570E+10 | 6974.00 | 01-JAN-16:53 | 24.00 | 19.35 | 0.230157E+09 | 347.84 | 02-JAN-10:00 | 24.00 | 19.35 |
February | 0.226917E+10 | 10134.65 | 26-FEB-17:33 | 23.67 | 19.48 | 0.215730E+09 | 347.84 | 28-FEB-10:00 | 22.20 | 19.62 |
March | 0.278929E+10 | 6104.43 | 26-MAR-15:32 | 25.33 | 20.03 | 0.260422E+09 | 347.84 | 27-MAR-09:50 | 23.12 | 20.66 |
April | 0.353171E+10 | 11414.61 | 23-APR-16:32 | 27.37 | 21.80 | 0.247308E+09 | 347.85 | 10-APR-13:00 | 27.37 | 21.80 |
May | 0.465511E+10 | 11306.05 | 29-MAY-16:52 | 30.60 | 23.80 | 0.276483E+09 | 347.84 | 30-MAY-09:30 | 28.35 | 24.32 |
June | 0.492171E+10 | 11066.72 | 11-JUN-16:52 | 33.30 | 21.96 | 0.275887E+09 | 347.84 | 26-JUN-09:09 | 27.48 | 24.72 |
July | 0.471434E+10 | 9139.01 | 22-JUL-17:06 | 34.63 | 26.60 | 0.256624E+09 | 347.84 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.498740E+10 | 9547.83 | 06-AUG-17:23 | 25.50 | 23.74 | 0.287720E+09 | 347.84 | 07-AUG-09:09 | 27.50 | 25.10 |
September | 0.418963E+10 | 11746.59 | 03-SEP-17:02 | 30.90 | 24.81 | 0.254845E+09 | 347.84 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.415188E+10 | 11357.15 | 09-OCT-16:22 | 28.00 | 21.50 | 0.262536E+09 | 347.85 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.288991E+10 | 6825.95 | 11-NOV-15:43 | 26.18 | 22.87 | 0.247917E+09 | 347.84 | 06-NOV-10:09 | 26.18 | 22.87 |
December | 0.239181E+10 | 6420.52 | 10-DEC-16:12 | 26.33 | 20.05 | 0.226527E+09 | 347.84 | 01-DEC-14:00 | 26.33 | 20.05 |
Annual Sum or Average | 0.436577E+11 | 0.304215E+10 | ||||||||
Minimum of Months | 0.216570E+10 | 6104.43 | 23.67 | 19.35 | 0.215730E+09 | 347.84 | 22.17 | 15.50 | ||
Maximum of Months | 0.498740E+10 | 11746.59 | 34.63 | 26.60 | 0.287720E+09 | 347.85 | 28.35 | 25.10 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.853280E+09 | 8024.91 | 10-JAN-07:03 | 3.17 |
February | 0.462434E+09 | 7864.46 | 06-FEB-07:03 | 3.90 |
March | 0.507029E+09 | 5406.48 | 13-MAR-06:02 | 5.92 |
April | 0.126292E+09 | 3530.86 | 11-APR-05:03 | 10.63 |
May | 16039249.92 | 4502.84 | 30-MAY-04:02 | 25.60 |
June | 15710851.37 | 3582.51 | 16-JUN-05:03 | 24.50 |
July | 13034972.62 | 3645.65 | 10-JUL-04:03 | 25.40 |
August | 14116888.66 | 4040.64 | 31-AUG-05:03 | 24.13 |
September | 14246771.16 | 4609.86 | 11-SEP-04:02 | 24.83 |
October | 69839313.80 | 4311.29 | 10-OCT-04:02 | 22.00 |
November | 0.221704E+09 | 3783.87 | 15-NOV-06:02 | 7.70 |
December | 0.635796E+09 | 8299.80 | 21-DEC-07:03 | 0.50 |
Annual Sum or Average | 0.294952E+10 | |||
Minimum of Months | 13034972.62 | 3530.86 | 0.50 | |
Maximum of Months | 0.853280E+09 | 8299.80 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241261E+09 | 2763.72 | 15-JAN-12:33 | 21.33 |
February | 0.145516E+09 | 2637.06 | 19-FEB-12:43 | 22.10 |
March | 78942708.89 | 2121.35 | 05-MAR-11:57 | 26.60 |
April | 9386587.75 | 1969.35 | 02-APR-15:08 | 18.72 |
May | 10834756.14 | 2226.16 | 22-MAY-04:02 | 26.10 |
June | 8212360.07 | 1913.84 | 23-JUN-05:03 | 25.60 |
July | 8872542.01 | 2289.23 | 13-JUL-05:03 | 26.93 |
August | 8437827.29 | 1970.53 | 14-AUG-04:02 | 26.10 |
September | 12494399.76 | 1919.03 | 29-SEP-05:03 | 23.80 |
October | 15884185.09 | 2164.62 | 29-OCT-12:13 | 22.33 |
November | 35244304.09 | 2533.16 | 26-NOV-11:02 | 16.97 |
December | 0.136289E+09 | 3315.88 | 31-DEC-12:23 | 23.00 |
Annual Sum or Average | 0.711376E+09 | |||
Minimum of Months | 8212360.07 | 1913.84 | 16.97 | |
Maximum of Months | 0.241261E+09 | 3315.88 | 26.93 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111083E+09 | 4052.03 | 04-JAN-06:02 | 1.83 |
February | 64649944.10 | 3599.22 | 03-FEB-06:03 | 18.90 |
March | 54824391.93 | 3829.35 | 20-MAR-05:03 | 12.10 |
April | 13818765.08 | 3742.39 | 03-APR-05:03 | 12.28 |
May | 16819265.15 | 2934.79 | 01-MAY-04:03 | 26.10 |
June | 17094137.41 | 2625.58 | 20-JUN-04:03 | 24.50 |
July | 16757691.40 | 2899.28 | 07-JUL-04:03 | 25.50 |
August | 20538101.02 | 3299.39 | 23-AUG-04:03 | 26.38 |
September | 22916324.80 | 3355.54 | 07-SEP-04:03 | 25.60 |
October | 25558848.54 | 4234.73 | 30-OCT-05:03 | 16.00 |
November | 28437017.47 | 4750.53 | 15-NOV-06:02 | 7.70 |
December | 67134552.19 | 5220.58 | 04-DEC-06:02 | 5.83 |
Annual Sum or Average | 0.459633E+09 | |||
Minimum of Months | 13818765.08 | 2625.58 | 1.83 | |
Maximum of Months | 0.111083E+09 | 5220.58 | 26.38 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 |
February | 898916.50 | 14981.94 | 06-FEB-07:01 | 3.90 |
March | 1085785.55 | 16286.78 | 13-MAR-06:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 1984702.05 | |||
Minimum of Months | 0.00 | 0.00 | 3.90 | |
Maximum of Months | 1085785.55 | 16286.78 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66173912.71 | 17431.63 | 26-JAN-07:03 | 7.00 |
February | 53755028.34 | 17764.22 | 09-FEB-07:02 | 9.90 |
March | 19003245.20 | 16287.87 | 13-MAR-06:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 1090327.89 | 9086.07 | 16-NOV-07:02 | 9.77 |
December | 32774951.96 | 17446.77 | 27-DEC-07:03 | 12.17 |
Annual Sum or Average | 0.172797E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.92 | |
Maximum of Months | 66173912.71 | 17764.22 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317364E+09 | 8528.62 | 10-JAN-06:01 | 3.00 |
February | 0.156410E+09 | 8461.57 | 06-FEB-06:01 | 2.88 |
March | 0.115521E+09 | 8079.02 | 13-MAR-05:02 | 6.68 |
April | 1019668.79 | 6599.49 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 475167.16 | 2375.84 | 28-OCT-06:03 | 10.00 |
November | 13082874.29 | 7591.04 | 15-NOV-07:02 | 7.80 |
December | 0.183645E+09 | 8573.06 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.787517E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.317364E+09 | 8573.06 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136978E+09 | 5130.90 | 04-JAN-06:02 | 1.83 |
February | 63674387.59 | 5194.99 | 07-FEB-06:03 | 8.62 |
March | 63639882.44 | 5120.56 | 09-MAR-06:02 | 1.10 |
April | 765426.66 | 4774.21 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 507680.74 | 2538.40 | 28-OCT-06:03 | 10.00 |
November | 4968427.40 | 4901.79 | 24-NOV-07:03 | 13.08 |
December | 96896028.99 | 5096.40 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.367430E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.136978E+09 | 5194.99 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161243E+09 | 8036.78 | 10-JAN-06:01 | 3.00 |
February | 81505200.91 | 8212.24 | 06-FEB-06:01 | 2.88 |
March | 87135111.96 | 7457.32 | 13-MAR-05:02 | 6.68 |
April | 632201.74 | 5127.47 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 195536.66 | 977.68 | 28-OCT-06:03 | 10.00 |
November | 4993479.72 | 7072.94 | 15-NOV-07:02 | 7.80 |
December | 0.104856E+09 | 8094.47 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.440561E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.161243E+09 | 8212.24 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180887E+09 | 5156.97 | 21-JAN-06:03 | 1.00 |
February | 88331109.15 | 5018.08 | 06-FEB-06:13 | 3.07 |
March | 68371496.82 | 5147.10 | 11-MAR-06:03 | 6.60 |
April | 613947.54 | 4863.52 | 11-APR-06:02 | 8.87 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 513696.71 | 2568.48 | 28-OCT-06:03 | 10.00 |
November | 9037622.73 | 4833.72 | 24-NOV-07:03 | 13.08 |
December | 0.105900E+09 | 5033.06 | 21-DEC-06:13 | 0.67 |
Annual Sum or Average | 0.453654E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.67 | |
Maximum of Months | 0.180887E+09 | 5156.97 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17730608.56 | 4676.26 | 23-JAN-07:03 | 6.17 |
February | 14857280.32 | 4619.85 | 09-FEB-07:02 | 9.90 |
March | 10892912.36 | 4656.58 | 09-MAR-07:02 | 1.18 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 6261207.63 | 4734.61 | 22-DEC-07:03 | 10.33 |
Annual Sum or Average | 49742008.88 | |||
Minimum of Months | 0.00 | 0.00 | 1.18 | |
Maximum of Months | 17730608.56 | 4734.61 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5355508.52 | 3028.73 | 14-JAN-07:03 | 7.02 |
February | 3927662.40 | 2932.65 | 07-FEB-07:03 | 7.88 |
March | 3758213.98 | 2945.08 | 09-MAR-07:01 | 1.18 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 3531773.84 | 3156.02 | 22-DEC-07:03 | 10.33 |
Annual Sum or Average | 16573158.74 | |||
Minimum of Months | 0.00 | 0.00 | 1.18 | |
Maximum of Months | 5355508.52 | 3156.02 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479566E+09 | 5986.26 | 05-JAN-08:00 | 0.00 |
February | 0.288815E+09 | 5997.78 | 17-FEB-07:10 | 1.28 |
March | 0.431575E+09 | 5894.99 | 09-MAR-07:10 | 1.18 |
April | 84977637.50 | 4631.31 | 12-APR-06:50 | 15.22 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 10146040.28 | 3230.14 | 27-OCT-06:07 | 14.83 |
November | 0.115981E+09 | 4583.01 | 27-NOV-07:08 | 14.08 |
December | 0.408819E+09 | 6215.71 | 21-DEC-07:10 | 0.50 |
Annual Sum or Average | 0.181988E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.479566E+09 | 6215.71 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5320977.27 | 3139.18 | 07-JAN-07:03 | 4.83 |
February | 4397735.84 | 3119.06 | 13-FEB-07:01 | 4.08 |
March | 3823975.74 | 3046.17 | 10-MAR-07:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 2731440.18 | 2694.51 | 30-DEC-07:03 | 6.00 |
Annual Sum or Average | 16274129.03 | |||
Minimum of Months | 0.00 | 0.00 | 4.08 | |
Maximum of Months | 5320977.27 | 3139.18 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43470207.89 | 5555.17 | 10-JAN-06:01 | 3.00 |
February | 25274424.01 | 5684.25 | 06-FEB-06:01 | 2.88 |
March | 14134821.06 | 5440.54 | 13-MAR-06:01 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 399148.63 | 3326.24 | 16-NOV-07:02 | 9.77 |
December | 24233168.94 | 5572.02 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.107512E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 43470207.89 | 5684.25 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20485253.11 | 3605.14 | 10-JAN-07:04 | 3.17 |
February | 10921333.36 | 3570.98 | 06-FEB-06:03 | 2.88 |
March | 8733911.43 | 3518.95 | 23-MAR-06:02 | 8.12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 258734.57 | 2156.12 | 16-NOV-07:02 | 9.77 |
December | 16471149.37 | 3596.72 | 27-DEC-07:03 | 12.17 |
Annual Sum or Average | 56870381.84 | |||
Minimum of Months | 0.00 | 0.00 | 2.88 | |
Maximum of Months | 20485253.11 | 3605.14 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 20265025.69 | 5437.21 | 25-JAN-07:02 | 9.00 |
February | 10223915.96 | 5329.92 | 14-FEB-07:02 | 9.50 |
March | 8739972.81 | 5229.63 | 10-MAR-07:02 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 12979383.62 | 5126.40 | 20-DEC-07:03 | 1.83 |
Annual Sum or Average | 52208298.09 | |||
Minimum of Months | 0.00 | 0.00 | 1.83 | |
Maximum of Months | 20265025.69 | 5437.21 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 25950164.49 | 3731.91 | 10-JAN-06:01 | 3.00 |
February | 13428580.40 | 3436.18 | 07-FEB-07:03 | 7.88 |
March | 8552895.37 | 3531.42 | 15-MAR-06:02 | 8.90 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 445458.87 | 3296.54 | 16-NOV-07:02 | 9.77 |
December | 15036497.95 | 3570.08 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 63413597.09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 25950164.49 | 3731.91 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.537659E+09 | 754.18 | 31-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.466447E+09 | 776.10 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.534374E+09 | 724.50 | 27-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.462750E+09 | 741.23 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.482395E+09 | 583.52 | 23-MAY-07:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.473031E+09 | 457.09 | 27-JUN-11:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.448652E+09 | 490.80 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.507204E+09 | 601.75 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.469071E+09 | 722.72 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.501073E+09 | 807.82 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.527650E+09 | 780.47 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.531792E+09 | 802.06 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.594210E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.448652E+09 | 457.09 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.537659E+09 | 807.82 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.330863E+09 | 455.99 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.290070E+09 | 475.16 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.332897E+09 | 429.27 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.292090E+09 | 452.74 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.307564E+09 | 360.15 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.302883E+09 | 289.76 | 27-JUN-13:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.286128E+09 | 294.72 | 14-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.321617E+09 | 309.16 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.295521E+09 | 426.98 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.313754E+09 | 500.68 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.326495E+09 | 498.59 | 21-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.328796E+09 | 501.02 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.372868E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.286128E+09 | 289.76 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.332897E+09 | 501.02 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.502299E+09 | 734.61 | 31-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.447454E+09 | 763.85 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.524278E+09 | 717.81 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.463969E+09 | 743.83 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.488464E+09 | 604.70 | 23-MAY-07:19 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.480531E+09 | 478.86 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.453635E+09 | 565.71 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.509928E+09 | 625.92 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.466321E+09 | 720.71 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.491878E+09 | 802.71 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.497756E+09 | 760.68 | 21-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.498019E+09 | 794.88 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.582453E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.447454E+09 | 478.86 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.524278E+09 | 802.71 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.328281E+09 | 483.08 | 31-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.289483E+09 | 494.64 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.337570E+09 | 473.35 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.295306E+09 | 479.04 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.309252E+09 | 412.52 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.303645E+09 | 361.44 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.287606E+09 | 390.15 | 14-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.324519E+09 | 441.97 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.299388E+09 | 473.73 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.315950E+09 | 515.04 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.322064E+09 | 503.14 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.322305E+09 | 508.01 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.373537E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.287606E+09 | 361.44 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.337570E+09 | 515.04 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.533778E+09 | 748.07 | 31-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.464091E+09 | 771.01 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.531942E+09 | 716.84 | 27-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.461623E+09 | 734.49 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.481661E+09 | 569.52 | 23-MAY-07:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.472382E+09 | 452.98 | 27-JUN-11:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.447733E+09 | 487.74 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.506224E+09 | 588.19 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.467684E+09 | 715.02 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.499442E+09 | 804.12 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.524134E+09 | 775.37 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.527717E+09 | 798.18 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.591841E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.447733E+09 | 452.98 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.533778E+09 | 804.12 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.329732E+09 | 450.98 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.289126E+09 | 471.74 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.332100E+09 | 423.78 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.291507E+09 | 448.32 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.306971E+09 | 353.53 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.302331E+09 | 287.76 | 27-JUN-13:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.285656E+09 | 292.14 | 14-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.321066E+09 | 307.26 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.294965E+09 | 421.26 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.313151E+09 | 498.25 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.325339E+09 | 496.26 | 21-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.327583E+09 | 498.70 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.371953E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.285656E+09 | 287.76 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.332100E+09 | 498.70 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.501788E+09 | 727.39 | 31-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.446907E+09 | 758.06 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.522962E+09 | 709.77 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.462879E+09 | 737.23 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.487241E+09 | 591.81 | 23-MAY-07:19 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.479499E+09 | 475.41 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.452682E+09 | 550.86 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.509022E+09 | 613.73 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.465412E+09 | 712.89 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.490987E+09 | 798.72 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.496850E+09 | 754.57 | 21-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.496269E+09 | 790.58 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.581250E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.446907E+09 | 475.41 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.522962E+09 | 798.72 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.326972E+09 | 480.21 | 31-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.288590E+09 | 492.19 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.336441E+09 | 470.13 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.294497E+09 | 476.04 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.308500E+09 | 407.27 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.302979E+09 | 354.41 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.286925E+09 | 383.98 | 14-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.323757E+09 | 437.34 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.298510E+09 | 470.54 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.315064E+09 | 513.32 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.321088E+09 | 500.95 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.321239E+09 | 506.04 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.372456E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.286925E+09 | 354.41 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.336441E+09 | 513.32 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.537658E+09 | 754.17 | 31-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.466446E+09 | 776.09 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.534373E+09 | 724.49 | 27-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.462749E+09 | 741.22 | 14-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.482395E+09 | 583.50 | 23-MAY-07:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.473031E+09 | 457.08 | 27-JUN-11:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.448651E+09 | 490.79 | 14-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.507204E+09 | 601.73 | 21-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.469069E+09 | 722.71 | 26-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.501071E+09 | 807.81 | 25-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.527648E+09 | 780.47 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.531790E+09 | 802.05 | 12-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.594208E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.448651E+09 | 457.08 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.537658E+09 | 807.81 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.330863E+09 | 455.99 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.290070E+09 | 475.15 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.332896E+09 | 429.27 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.292089E+09 | 452.73 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.307564E+09 | 360.15 | 30-MAY-15:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.302883E+09 | 289.76 | 27-JUN-13:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.286128E+09 | 294.71 | 14-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.321617E+09 | 309.16 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.295521E+09 | 426.97 | 26-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.313754E+09 | 500.68 | 25-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.326494E+09 | 498.59 | 21-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.328796E+09 | 501.02 | 12-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.372867E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.286128E+09 | 289.76 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.332896E+09 | 501.02 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.502299E+09 | 734.60 | 31-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.447454E+09 | 763.84 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.524278E+09 | 717.79 | 27-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.463969E+09 | 743.82 | 14-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.488459E+09 | 604.68 | 23-MAY-07:19 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.480530E+09 | 478.85 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.453634E+09 | 565.69 | 14-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.509927E+09 | 625.91 | 21-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.466320E+09 | 720.69 | 26-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.491877E+09 | 802.70 | 25-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.497756E+09 | 760.67 | 21-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.498018E+09 | 794.87 | 12-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.582452E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.447454E+09 | 478.85 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.524278E+09 | 802.70 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.328281E+09 | 483.07 | 31-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.289483E+09 | 494.64 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.337570E+09 | 473.34 | 27-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.295306E+09 | 479.03 | 14-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.309251E+09 | 412.51 | 24-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.303645E+09 | 361.43 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.287606E+09 | 390.14 | 14-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.324518E+09 | 441.97 | 23-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.299380E+09 | 473.73 | 26-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.315949E+09 | 515.03 | 25-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.322064E+09 | 503.14 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.322304E+09 | 508.00 | 12-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.373536E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.287606E+09 | 361.43 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.337570E+09 | 515.03 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.537659E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 799696.88 | 95058557.42 |
February | 0.901968E+09 | 0.466447E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 957386.48 | 73286704.52 |
March | 0.107774E+10 | 0.534374E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2698743.39 | 79487105.22 |
April | 0.956342E+09 | 0.462750E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4031170.37 | 36452308.55 |
May | 0.103597E+10 | 0.482395E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16752019.19 | 6540298.46 |
June | 0.103308E+10 | 0.473031E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14999631.68 | 5037139.43 |
July | 0.959235E+09 | 0.448652E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20848792.27 | 2169807.83 |
August | 0.107774E+10 | 0.507204E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20369524.14 | 6542112.25 |
September | 0.956342E+09 | 0.469071E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18989178.05 | 9761920.85 |
October | 0.994195E+09 | 0.501073E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16131971.69 | 31386616.26 |
November | 0.984487E+09 | 0.527650E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2374196.72 | 49259969.06 |
December | 0.959235E+09 | 0.531792E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1610636.44 | 85198591.55 |
Annual Sum or Average | 0.119305E+11 | 0.594210E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120563E+09 | 0.480181E+09 |
Minimum of Months | 0.901968E+09 | 0.448652E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 799696.88 | 2169807.83 |
Maximum of Months | 0.107774E+10 | 0.537659E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20848792.27 | 95058557.42 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.330863E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 332178.88 | 66100786.46 |
February | 0.571020E+09 | 0.290070E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 483303.10 | 51374575.38 |
March | 0.682301E+09 | 0.332897E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1314689.54 | 55682967.02 |
April | 0.605444E+09 | 0.292090E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2515694.99 | 25918161.72 |
May | 0.655854E+09 | 0.307564E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10686513.81 | 4589190.46 |
June | 0.654023E+09 | 0.302883E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9876440.44 | 3408659.33 |
July | 0.607275E+09 | 0.286128E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13532783.45 | 1572326.45 |
August | 0.682301E+09 | 0.321617E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13278434.08 | 4429691.36 |
September | 0.605444E+09 | 0.295521E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12009508.12 | 6648313.16 |
October | 0.629407E+09 | 0.313754E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9841468.30 | 21970876.27 |
November | 0.623262E+09 | 0.326495E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1192918.76 | 34915090.94 |
December | 0.607275E+09 | 0.328796E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795004.01 | 58629573.65 |
Annual Sum or Average | 0.755301E+10 | 0.372868E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75858937.47 | 0.335240E+09 |
Minimum of Months | 0.571020E+09 | 0.286128E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 332178.88 | 1572326.45 |
Maximum of Months | 0.682301E+09 | 0.332897E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13532783.45 | 66100786.46 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.502299E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201753.53 | 0.110248E+09 |
February | 0.901968E+09 | 0.447454E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 467751.51 | 84254211.17 |
March | 0.107774E+10 | 0.524278E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1558831.03 | 85414298.89 |
April | 0.956342E+09 | 0.463969E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3646593.11 | 38932496.16 |
May | 0.103597E+10 | 0.488464E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16772776.73 | 6524810.34 |
June | 0.103308E+10 | 0.480531E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15284632.05 | 4854206.85 |
July | 0.959235E+09 | 0.453635E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21033828.31 | 2137000.88 |
August | 0.107774E+10 | 0.509928E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20013950.00 | 6701124.27 |
September | 0.956342E+09 | 0.466321E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17552068.46 | 10644653.66 |
October | 0.994195E+09 | 0.491878E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13075880.67 | 36913319.92 |
November | 0.984487E+09 | 0.497756E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1293077.48 | 57718396.47 |
December | 0.959235E+09 | 0.498019E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 813037.59 | 98065054.01 |
Annual Sum or Average | 0.119305E+11 | 0.582453E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111714E+09 | 0.542408E+09 |
Minimum of Months | 0.901968E+09 | 0.447454E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201753.53 | 2137000.88 |
Maximum of Months | 0.107774E+10 | 0.524278E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21033828.31 | 0.110248E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.328281E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 414048.89 | 66567840.29 |
February | 0.570983E+09 | 0.289483E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 549960.49 | 51346031.35 |
March | 0.682256E+09 | 0.337570E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1673308.88 | 54944371.16 |
April | 0.605404E+09 | 0.295306E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2463916.68 | 26392891.07 |
May | 0.655811E+09 | 0.309252E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11368278.22 | 4726900.33 |
June | 0.653980E+09 | 0.303645E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9910520.59 | 3708117.88 |
July | 0.607235E+09 | 0.287606E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13929252.60 | 1706637.57 |
August | 0.682256E+09 | 0.324519E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13620745.22 | 4926565.98 |
September | 0.605404E+09 | 0.299388E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12377690.08 | 7056321.54 |
October | 0.629366E+09 | 0.315950E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10366139.23 | 22729646.30 |
November | 0.623221E+09 | 0.322064E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1523841.78 | 34208176.54 |
December | 0.607235E+09 | 0.322305E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 925708.38 | 59330179.02 |
Annual Sum or Average | 0.755252E+10 | 0.373537E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79123411.03 | 0.337644E+09 |
Minimum of Months | 0.570983E+09 | 0.287606E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 414048.89 | 1706637.57 |
Maximum of Months | 0.682256E+09 | 0.337570E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13929252.60 | 66567840.29 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.533778E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 416685.74 | 56508605.46 |
February | 0.901968E+09 | 0.464091E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 554167.07 | 43107489.12 |
March | 0.107774E+10 | 0.531942E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1625527.05 | 44239519.07 |
April | 0.956342E+09 | 0.461623E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2490171.92 | 19195837.45 |
May | 0.103597E+10 | 0.481661E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9746893.98 | 2344564.62 |
June | 0.103308E+10 | 0.472382E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8720243.73 | 2169545.13 |
July | 0.959235E+09 | 0.447733E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12139854.38 | 912476.02 |
August | 0.107774E+10 | 0.506224E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11270721.12 | 3627870.24 |
September | 0.956342E+09 | 0.467684E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10582079.94 | 5757803.36 |
October | 0.994195E+09 | 0.499442E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9002474.40 | 18572091.94 |
November | 0.984487E+09 | 0.524134E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1174818.09 | 30211583.12 |
December | 0.959235E+09 | 0.527717E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 797442.48 | 51503515.28 |
Annual Sum or Average | 0.119305E+11 | 0.591841E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68521079.90 | 0.278151E+09 |
Minimum of Months | 0.901968E+09 | 0.447733E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 416685.74 | 912476.02 |
Maximum of Months | 0.107774E+10 | 0.533778E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12139854.38 | 56508605.46 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.329732E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 148520.17 | 40297657.89 |
February | 0.571020E+09 | 0.289126E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 266290.73 | 30809256.75 |
March | 0.682301E+09 | 0.332100E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 710820.05 | 31802032.37 |
April | 0.605444E+09 | 0.291507E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1409829.99 | 14196361.32 |
May | 0.655854E+09 | 0.306971E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5787591.78 | 1994702.96 |
June | 0.654023E+09 | 0.302331E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5486056.68 | 1656483.46 |
July | 0.607275E+09 | 0.285656E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7377108.40 | 832982.41 |
August | 0.682301E+09 | 0.321066E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7077791.18 | 2720820.82 |
September | 0.605444E+09 | 0.294965E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6358015.25 | 4301580.63 |
October | 0.629407E+09 | 0.313151E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5238194.94 | 13464852.40 |
November | 0.623262E+09 | 0.325339E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 591938.62 | 21751036.08 |
December | 0.607275E+09 | 0.327583E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 397924.83 | 36093965.90 |
Annual Sum or Average | 0.755301E+10 | 0.371953E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40850082.63 | 0.199922E+09 |
Minimum of Months | 0.571020E+09 | 0.285656E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 148520.17 | 832982.41 |
Maximum of Months | 0.682301E+09 | 0.332100E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7377108.40 | 40297657.89 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.501788E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35151512.84 | 0.316960E+10 |
February | 0.901968E+09 | 0.446907E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59504820.19 | 0.196681E+10 |
March | 0.107774E+10 | 0.522962E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158059E+09 | 0.206137E+10 |
April | 0.956342E+09 | 0.462879E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528249E+09 | 0.644455E+09 |
May | 0.103597E+10 | 0.487241E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171505E+10 | 13001557.39 |
June | 0.103308E+10 | 0.479499E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203680E+10 | 14432125.96 |
July | 0.959235E+09 | 0.452682E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178275E+10 | 9463295.43 |
August | 0.107774E+10 | 0.509022E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192518E+10 | 25945325.70 |
September | 0.956342E+09 | 0.465412E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988866E+09 | 78611150.17 |
October | 0.994195E+09 | 0.490987E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100831E+10 | 0.442888E+09 |
November | 0.984487E+09 | 0.496850E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277313E+09 | 0.140663E+10 |
December | 0.959235E+09 | 0.496269E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127999E+09 | 0.253244E+10 |
Annual Sum or Average | 0.119305E+11 | 0.581250E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106432E+11 | 0.123656E+11 |
Minimum of Months | 0.901968E+09 | 0.446907E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35151512.84 | 9463295.43 |
Maximum of Months | 0.107774E+10 | 0.522962E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203680E+10 | 0.316960E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.326972E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 159336.97 | 40415433.89 |
February | 0.570983E+09 | 0.288590E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 260715.50 | 30736812.48 |
March | 0.682256E+09 | 0.336441E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 800276.97 | 31584376.56 |
April | 0.605404E+09 | 0.294497E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1309864.06 | 14543704.46 |
May | 0.655811E+09 | 0.308500E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6095990.68 | 1994438.75 |
June | 0.653980E+09 | 0.302979E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5400820.60 | 1838683.55 |
July | 0.607235E+09 | 0.286925E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7443409.96 | 875952.89 |
August | 0.682256E+09 | 0.323757E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7185605.72 | 2961831.11 |
September | 0.605404E+09 | 0.298510E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6372060.03 | 4555819.44 |
October | 0.629366E+09 | 0.315064E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5306509.99 | 14028593.81 |
November | 0.623221E+09 | 0.321088E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 647455.08 | 21554526.08 |
December | 0.607235E+09 | 0.321239E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 420078.44 | 36584498.99 |
Annual Sum or Average | 0.755252E+10 | 0.372456E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41402124.00 | 0.201675E+09 |
Minimum of Months | 0.570983E+09 | 0.286925E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 159336.97 | 875952.89 |
Maximum of Months | 0.682256E+09 | 0.336441E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7443409.96 | 40415433.89 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.537658E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 612332.64 | 86565595.23 |
February | 0.901968E+09 | 0.466446E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 763752.77 | 67057321.36 |
March | 0.107774E+10 | 0.534373E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2237477.32 | 71308038.60 |
April | 0.956342E+09 | 0.462749E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3462981.59 | 32207302.13 |
May | 0.103597E+10 | 0.482395E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14270889.92 | 5416203.78 |
June | 0.103308E+10 | 0.473031E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12935269.50 | 4227757.89 |
July | 0.959235E+09 | 0.448651E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18004212.54 | 1778774.57 |
August | 0.107774E+10 | 0.507204E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17424957.34 | 5539024.46 |
September | 0.956342E+09 | 0.469069E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16104662.97 | 8723412.13 |
October | 0.994195E+09 | 0.501071E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13651548.60 | 28393951.65 |
November | 0.984487E+09 | 0.527648E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1893906.61 | 45532078.18 |
December | 0.959235E+09 | 0.531790E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1272840.44 | 77922345.19 |
Annual Sum or Average | 0.119305E+11 | 0.594208E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102635E+09 | 0.434672E+09 |
Minimum of Months | 0.901968E+09 | 0.448651E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 612332.64 | 1778774.57 |
Maximum of Months | 0.107774E+10 | 0.537658E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18004212.54 | 86565595.23 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.330863E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 263614.35 | 59855175.33 |
February | 0.421807E+09 | 0.290070E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 407794.97 | 46641964.46 |
March | 0.502994E+09 | 0.332896E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1124533.38 | 49369583.11 |
April | 0.447140E+09 | 0.292089E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2176776.47 | 22609819.84 |
May | 0.484071E+09 | 0.307564E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9033149.70 | 3810424.36 |
June | 0.482240E+09 | 0.302883E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8474630.64 | 2863114.93 |
July | 0.448971E+09 | 0.286128E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11562459.66 | 1295628.40 |
August | 0.502994E+09 | 0.321617E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11296045.83 | 3746625.78 |
September | 0.447140E+09 | 0.295521E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10116007.99 | 5929192.76 |
October | 0.465148E+09 | 0.313754E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8355736.14 | 19668592.21 |
November | 0.460569E+09 | 0.326494E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1003767.19 | 31755222.56 |
December | 0.448971E+09 | 0.328796E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 669820.34 | 53240526.27 |
Annual Sum or Average | 0.557719E+10 | 0.372867E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64484336.65 | 0.300786E+09 |
Minimum of Months | 0.421807E+09 | 0.286128E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 263614.35 | 1295628.40 |
Maximum of Months | 0.502994E+09 | 0.332896E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11562459.66 | 59855175.33 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.502299E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 165809.95 | 98835324.51 |
February | 0.901968E+09 | 0.447454E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 395090.08 | 75931547.33 |
March | 0.107774E+10 | 0.524278E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1296161.45 | 75892497.53 |
April | 0.956342E+09 | 0.463969E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3126108.92 | 34126281.23 |
May | 0.103597E+10 | 0.488459E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14247858.45 | 5405415.62 |
June | 0.103308E+10 | 0.480530E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13178809.06 | 4082368.28 |
July | 0.959235E+09 | 0.453634E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18141453.76 | 1756216.35 |
August | 0.107774E+10 | 0.509927E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17028055.53 | 5676417.58 |
September | 0.956342E+09 | 0.466320E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14694841.12 | 9474000.35 |
October | 0.994195E+09 | 0.491877E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10984168.41 | 32786183.30 |
November | 0.984487E+09 | 0.497756E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1074062.85 | 51944106.33 |
December | 0.959235E+09 | 0.498018E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 683438.74 | 88218600.23 |
Annual Sum or Average | 0.119305E+11 | 0.582452E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95015858.30 | 0.484129E+09 |
Minimum of Months | 0.901968E+09 | 0.447454E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 165809.95 | 1756216.35 |
Maximum of Months | 0.107774E+10 | 0.524278E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18141453.76 | 98835324.51 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.328281E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 292516.69 | 60288985.23 |
February | 0.570983E+09 | 0.289483E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 416837.70 | 46769337.39 |
March | 0.682256E+09 | 0.337570E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1314927.19 | 49139164.69 |
April | 0.605404E+09 | 0.295306E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2006882.59 | 23327628.46 |
May | 0.655811E+09 | 0.309251E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9387255.42 | 3960862.44 |
June | 0.653980E+09 | 0.303645E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8310423.32 | 3142299.83 |
July | 0.607235E+09 | 0.287606E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11622103.28 | 1438600.08 |
August | 0.682256E+09 | 0.324518E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11439313.49 | 4199609.56 |
September | 0.605404E+09 | 0.299380E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10147224.96 | 6388506.84 |
October | 0.629366E+09 | 0.315949E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8459402.50 | 20546576.17 |
November | 0.623221E+09 | 0.322064E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1153580.81 | 31430998.44 |
December | 0.607235E+09 | 0.322304E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 713222.88 | 53945746.42 |
Annual Sum or Average | 0.755252E+10 | 0.373536E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65263690.84 | 0.304578E+09 |
Minimum of Months | 0.570983E+09 | 0.287606E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 292516.69 | 1438600.08 |
Maximum of Months | 0.682256E+09 | 0.337570E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11622103.28 | 60288985.23 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255856.12 | 0.128517E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506445.20 | 98957890.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1883457.60 | 0.101941E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3463315.64 | 45266928.35 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16265399.51 | 5594612.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14959005.37 | 4750841.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22135799.44 | 1614499.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20185834.81 | 6664977.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18076145.12 | 11298740.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13677655.24 | 40680826.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1334067.80 | 67922993.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 916397.96 | 0.115419E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113659E+09 | 0.628629E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255856.12 | 1614499.16 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22135799.44 | 0.128517E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549029.44 | 0.153512E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 920913.45 | 0.119010E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2907899.06 | 0.124745E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4558492.59 | 56203707.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20938417.12 | 7253910.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19138083.76 | 6205089.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28388704.73 | 2105474.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26231436.56 | 8168321.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23576759.48 | 13656402.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18066270.06 | 49359233.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2067912.74 | 81640426.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1482568.59 | 0.137772E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148826E+09 | 0.759632E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549029.44 | 2105474.17 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28388704.73 | 0.153512E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122409.10 | 0.149500E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233710.69 | 0.116246E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1291531.28 | 0.124109E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2651003.41 | 58024964.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18192731.26 | 6607588.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17194400.25 | 5409549.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25583445.41 | 1877668.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24615687.94 | 7381943.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22051985.15 | 11843573.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14586284.26 | 46657169.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1305442.06 | 76817535.24 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 847725.44 | 0.132631E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128676E+09 | 0.737106E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122409.10 | 1877668.09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25583445.41 | 0.149500E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 754.18 | 31-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.98 | 16-JAN-15:00 | 186.47 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 776.10 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 20-FEB-15:00 | 255.76 | 05-FEB-07:55 |
March | 1306.65 | 01-MAR-10:09 | 724.50 | 27-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.96 | 05-MAR-12:33 | 240.20 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 741.23 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.25 | 29-APR-17:02 | 142.28 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 583.52 | 23-MAY-07:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.40 | 21-MAY-13:50 | 33.19 | 14-MAY-11:53 |
June | 1306.65 | 01-JUN-09:09 | 457.09 | 27-JUN-11:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.00 | 10-JUN-17:02 | 41.62 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 490.80 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.50 | 16-JUL-15:00 | 26.24 | 31-JUL-02:20 |
August | 1306.65 | 01-AUG-09:09 | 601.75 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.89 | 20-AUG-13:53 | 58.91 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 722.72 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.57 | 09-SEP-23:00 | 66.38 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 807.82 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.18 | 09-OCT-14:00 | 107.39 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 780.47 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.91 | 05-NOV-13:00 | 167.63 | 12-NOV-07:00 |
December | 1306.65 | 01-DEC-10:09 | 802.06 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.41 | 10-DEC-11:00 | 234.92 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 457.09 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.98 | 26.24 | |||||
Maximum of Months | 1306.65 | 807.82 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 126.18 | 255.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 455.99 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 16-JAN-15:00 | 123.40 | 21-JAN-06:00 |
February | 827.22 | 01-FEB-10:09 | 475.16 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.59 | 20-FEB-15:00 | 185.11 | 05-FEB-10:00 |
March | 827.22 | 01-MAR-10:09 | 429.27 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.40 | 05-MAR-13:07 | 161.22 | 20-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 452.74 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.60 | 29-APR-17:30 | 97.20 | 01-APR-18:00 |
May | 827.22 | 01-MAY-09:09 | 360.15 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.07 | 21-MAY-13:50 | 27.52 | 14-MAY-11:53 |
June | 827.22 | 01-JUN-09:09 | 289.76 | 27-JUN-13:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.20 | 10-JUN-17:02 | 27.14 | 06-JUN-22:00 |
July | 827.22 | 03-JUL-09:09 | 294.72 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.94 | 22-JUL-18:50 | 29.06 | 30-JUL-11:10 |
August | 827.22 | 01-AUG-09:09 | 309.16 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.84 | 20-AUG-14:10 | 39.31 | 25-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 426.98 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.98 | 09-SEP-23:00 | 44.71 | 05-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 500.68 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.42 | 09-OCT-14:00 | 72.42 | 29-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 498.59 | 21-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.07 | 05-NOV-13:00 | 130.28 | 12-NOV-08:40 |
December | 827.22 | 01-DEC-10:09 | 501.02 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.24 | 10-DEC-14:50 | 156.41 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 289.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.14 | |||||
Maximum of Months | 827.22 | 501.02 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 84.42 | 185.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 734.61 | 31-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 | 19-JAN-12:10 | 214.18 | 22-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 763.85 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 | 02-FEB-13:00 | 266.68 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 717.81 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.93 | 26-MAR-13:50 | 247.79 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 743.83 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.86 | 29-APR-17:02 | 152.57 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 604.70 | 23-MAY-07:19 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.77 | 21-MAY-13:50 | 35.32 | 14-MAY-11:53 |
June | 1306.65 | 01-JUN-09:09 | 478.86 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.39 | 10-JUN-17:02 | 41.54 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 565.71 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.97 | 22-JUL-18:50 | 26.76 | 31-JUL-02:70 |
August | 1306.65 | 01-AUG-09:09 | 625.92 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.16 | 20-AUG-14:10 | 59.38 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 720.71 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.00 | 09-SEP-23:00 | 68.16 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 802.71 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.25 | 09-OCT-13:56 | 116.18 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 760.68 | 21-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.28 | 07-NOV-13:00 | 192.40 | 12-NOV-10:53 |
December | 1306.65 | 01-DEC-10:09 | 794.88 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.53 | 13-DEC-14:00 | 239.34 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 478.86 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 | 26.76 | |||||
Maximum of Months | 1306.65 | 802.71 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 110.25 | 266.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 483.08 | 31-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.31 | 16-JAN-13:00 | 130.78 | 22-JAN-17:00 |
February | 827.17 | 01-FEB-10:09 | 494.64 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 26-FEB-12:00 | 170.43 | 05-FEB-07:55 |
March | 827.17 | 01-MAR-10:09 | 473.35 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.60 | 05-MAR-12:23 | 163.80 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 479.04 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 | 23-APR-13:33 | 106.63 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 412.52 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.01 | 21-MAY-13:50 | 26.73 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 361.44 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.98 | 10-JUN-17:08 | 29.35 | 06-JUN-22:00 |
July | 827.17 | 03-JUL-09:09 | 390.15 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.44 | 16-JUL-13:00 | 19.43 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 441.97 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.00 | 20-AUG-13:53 | 40.95 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 473.73 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.94 | 09-SEP-23:00 | 44.60 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 515.04 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.42 | 09-OCT-12:00 | 74.87 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 503.14 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 05-NOV-12:50 | 112.87 | 12-NOV-07:00 |
December | 827.17 | 01-DEC-10:09 | 508.01 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 | 10-DEC-11:00 | 157.01 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 361.44 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 | 19.43 | |||||
Maximum of Months | 827.17 | 515.04 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 89.42 | 170.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 748.07 | 31-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.97 | 16-JAN-15:00 | 113.16 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 771.01 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.14 | 20-FEB-15:20 | 160.14 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 716.84 | 27-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.05 | 05-MAR-12:50 | 134.18 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 734.49 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 | 29-APR-17:02 | 76.25 | 01-APR-21:00 |
May | 1306.65 | 01-MAY-09:09 | 569.52 | 23-MAY-07:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.06 | 07-MAY-13:53 | 12.51 | 14-MAY-12:00 |
June | 1306.65 | 01-JUN-09:09 | 452.98 | 27-JUN-11:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 | 10-JUN-17:02 | 22.09 | 06-JUN-22:10 |
July | 1306.65 | 03-JUL-09:09 | 487.74 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.81 | 22-JUL-18:50 | 12.59 | 31-JUL-02:40 |
August | 1306.65 | 01-AUG-09:09 | 588.19 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.49 | 20-AUG-13:53 | 34.20 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 715.02 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.61 | 09-SEP-17:02 | 35.60 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 804.12 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.35 | 09-OCT-13:50 | 67.68 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 775.37 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.49 | 05-NOV-13:00 | 97.90 | 12-NOV-08:00 |
December | 1306.65 | 01-DEC-10:09 | 798.18 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.53 | 10-DEC-15:00 | 145.89 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 452.98 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.97 | 12.51 | |||||
Maximum of Months | 1306.65 | 804.12 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 73.35 | 160.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 450.98 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 16-JAN-15:00 | 75.55 | 22-JAN-08:00 |
February | 827.22 | 01-FEB-10:09 | 471.74 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 | 20-FEB-15:20 | 113.02 | 05-FEB-08:00 |
March | 827.22 | 01-MAR-10:09 | 423.78 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 | 05-MAR-12:50 | 92.29 | 20-MAR-22:00 |
April | 827.22 | 03-APR-09:09 | 448.32 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 | 29-APR-17:30 | 53.01 | 01-APR-21:00 |
May | 827.22 | 01-MAY-09:09 | 353.53 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.26 | 07-MAY-14:00 | 14.97 | 14-MAY-12:00 |
June | 827.22 | 01-JUN-09:09 | 287.76 | 27-JUN-13:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.07 | 10-JUN-17:02 | 15.12 | 06-JUN-22:10 |
July | 827.22 | 03-JUL-09:09 | 292.14 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 | 22-JUL-18:50 | 12.31 | 30-JUL-11:10 |
August | 827.22 | 01-AUG-09:09 | 307.26 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.26 | 20-AUG-13:53 | 23.66 | 25-AUG-24:00 |
September | 827.22 | 01-SEP-09:09 | 421.26 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.43 | 09-SEP-17:02 | 26.02 | 05-SEP-03:00 |
October | 827.22 | 02-OCT-09:09 | 498.25 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.17 | 09-OCT-13:50 | 46.58 | 29-OCT-02:00 |
November | 827.22 | 01-NOV-09:09 | 496.26 | 21-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 | 05-NOV-13:00 | 74.89 | 12-NOV-08:30 |
December | 827.22 | 01-DEC-10:09 | 498.70 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 10-DEC-15:00 | 98.85 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 287.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 | 12.31 | |||||
Maximum of Months | 827.22 | 498.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 44.17 | 113.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 727.39 | 31-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2496.44 | 02-JAN-13:00 | 25035.31 | 05-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 758.06 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4557.86 | 02-FEB-13:00 | 24380.54 | 17-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 709.77 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5246.49 | 30-MAR-12:00 | 24760.15 | 09-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 737.23 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9194.72 | 28-APR-16:03 | 14363.07 | 11-APR-06:02 |
May | 1306.65 | 01-MAY-09:09 | 591.81 | 23-MAY-07:19 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10101.98 | 25-MAY-16:03 | 1407.36 | 02-MAY-06:10 |
June | 1306.65 | 01-JUN-09:09 | 475.41 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10591.76 | 28-JUN-16:03 | 1906.43 | 07-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 550.86 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13164.94 | 21-JUL-16:02 | 1407.25 | 13-JUL-11:10 |
August | 1306.65 | 01-AUG-09:09 | 613.73 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13542.66 | 30-AUG-16:01 | 2347.92 | 16-AUG-17:00 |
September | 1306.65 | 01-SEP-09:09 | 712.89 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9376.28 | 06-SEP-16:03 | 3862.72 | 07-SEP-17:00 |
October | 1306.65 | 02-OCT-09:09 | 798.72 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9104.82 | 06-OCT-11:02 | 9468.60 | 27-OCT-06:02 |
November | 1306.65 | 01-NOV-09:09 | 754.57 | 21-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5483.96 | 02-NOV-11:03 | 16998.58 | 15-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 790.58 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4688.09 | 13-DEC-13:00 | 25510.20 | 21-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 475.41 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2496.44 | 1407.25 | |||||
Maximum of Months | 1306.65 | 798.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13542.66 | 25510.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 480.21 | 31-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 | 16-JAN-12:53 | 76.19 | 21-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 492.19 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 | 26-FEB-13:32 | 107.32 | 05-FEB-08:00 |
March | 827.17 | 01-MAR-10:09 | 470.13 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 | 05-MAR-12:43 | 92.85 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 476.04 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 23-APR-14:28 | 54.72 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 407.27 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.78 | 28-MAY-10:00 | 11.49 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 354.41 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.56 | 10-JUN-17:10 | 16.61 | 06-JUN-21:20 |
July | 827.17 | 03-JUL-09:09 | 383.98 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.92 | 16-JUL-13:00 | 10.39 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 437.34 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.18 | 20-AUG-13:53 | 24.33 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 470.54 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 09-SEP-17:10 | 25.89 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 513.32 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.44 | 09-OCT-11:50 | 47.82 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 500.95 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 11-NOV-12:00 | 67.29 | 12-NOV-08:00 |
December | 827.17 | 01-DEC-10:09 | 506.04 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 | 10-DEC-11:00 | 99.11 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 354.41 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 6.37 | 10.39 | |||||
Maximum of Months | 827.17 | 513.32 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.44 | 107.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 754.17 | 31-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.15 | 16-JAN-15:00 | 170.11 | 21-JAN-06:00 |
February | 1306.65 | 01-FEB-10:09 | 776.09 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 | 20-FEB-15:00 | 239.56 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 724.49 | 27-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.17 | 05-MAR-12:53 | 211.63 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 741.22 | 14-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.30 | 29-APR-17:02 | 122.24 | 01-APR-21:00 |
May | 1306.65 | 01-MAY-09:09 | 583.50 | 23-MAY-07:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.31 | 07-MAY-14:00 | 23.24 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 457.08 | 27-JUN-11:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.16 | 10-JUN-17:02 | 35.96 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 490.79 | 14-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.70 | 22-JUL-18:50 | 21.77 | 31-JUL-02:20 |
August | 1306.65 | 01-AUG-09:09 | 601.73 | 21-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.28 | 20-AUG-13:53 | 51.44 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 722.71 | 26-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.85 | 09-SEP-17:02 | 56.29 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 807.81 | 25-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.77 | 09-OCT-13:50 | 99.51 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 780.47 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.15 | 11-NOV-12:32 | 149.12 | 12-NOV-08:00 |
December | 1306.65 | 01-DEC-10:09 | 802.05 | 12-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.91 | 10-DEC-15:00 | 216.80 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 457.08 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.15 | 21.77 | |||||
Maximum of Months | 1306.65 | 807.81 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 110.77 | 239.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 455.99 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 16-JAN-15:00 | 112.46 | 21-JAN-06:00 |
February | 805.43 | 01-FEB-08:09 | 475.15 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 20-FEB-15:00 | 172.56 | 05-FEB-10:00 |
March | 805.43 | 01-MAR-08:09 | 429.27 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 | 05-MAR-13:00 | 141.36 | 20-MAR-22:00 |
April | 805.43 | 03-APR-07:10 | 452.73 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.70 | 29-APR-17:30 | 82.55 | 01-APR-21:00 |
May | 805.43 | 01-MAY-07:10 | 360.15 | 30-MAY-15:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.48 | 21-MAY-14:10 | 17.51 | 14-MAY-12:00 |
June | 805.43 | 01-JUN-07:10 | 289.76 | 27-JUN-13:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.70 | 10-JUN-17:02 | 23.44 | 06-JUN-22:10 |
July | 805.43 | 03-JUL-07:10 | 294.71 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.80 | 22-JUL-18:50 | 21.51 | 30-JUL-11:10 |
August | 805.43 | 01-AUG-07:10 | 309.16 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.06 | 20-AUG-13:53 | 34.25 | 25-AUG-24:00 |
September | 805.43 | 01-SEP-07:10 | 426.97 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.54 | 09-SEP-17:02 | 38.04 | 05-SEP-03:00 |
October | 805.43 | 02-OCT-07:10 | 500.68 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.30 | 09-OCT-13:50 | 66.90 | 29-OCT-02:00 |
November | 805.43 | 01-NOV-07:10 | 498.59 | 21-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 | 05-NOV-13:00 | 115.75 | 12-NOV-08:40 |
December | 805.43 | 01-DEC-08:09 | 501.02 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.19 | 10-DEC-15:00 | 143.91 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 289.76 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.46 | 17.51 | |||||
Maximum of Months | 805.43 | 501.02 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 69.30 | 172.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 734.60 | 31-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 19-JAN-12:10 | 180.16 | 22-JAN-17:00 |
February | 1306.65 | 01-FEB-10:09 | 763.84 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 02-FEB-13:00 | 249.10 | 05-FEB-08:00 |
March | 1306.65 | 01-MAR-10:09 | 717.79 | 27-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.60 | 26-MAR-14:00 | 216.95 | 20-MAR-22:00 |
April | 1306.65 | 03-APR-09:09 | 743.82 | 14-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.98 | 29-APR-17:02 | 127.59 | 01-APR-18:00 |
May | 1306.65 | 01-MAY-09:09 | 604.68 | 23-MAY-07:19 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.27 | 07-MAY-14:00 | 23.49 | 09-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 478.85 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.22 | 10-JUN-17:02 | 35.84 | 06-JUN-22:00 |
July | 1306.65 | 03-JUL-09:09 | 565.69 | 14-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.04 | 22-JUL-18:50 | 22.21 | 31-JUL-02:20 |
August | 1306.65 | 01-AUG-09:09 | 625.91 | 21-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.89 | 20-AUG-13:53 | 51.81 | 25-AUG-24:00 |
September | 1306.65 | 01-SEP-09:09 | 720.69 | 26-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.14 | 09-SEP-17:02 | 57.94 | 05-SEP-03:00 |
October | 1306.65 | 02-OCT-09:09 | 802.70 | 25-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.70 | 09-OCT-13:58 | 106.34 | 29-OCT-02:00 |
November | 1306.65 | 01-NOV-09:09 | 760.67 | 21-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 | 07-NOV-13:00 | 166.80 | 12-NOV-11:00 |
December | 1306.65 | 01-DEC-10:09 | 794.87 | 12-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.64 | 13-DEC-14:00 | 221.20 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 478.85 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 22.21 | |||||
Maximum of Months | 1306.65 | 802.70 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 90.70 | 249.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 483.07 | 31-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 | 16-JAN-13:03 | 113.28 | 21-JAN-06:00 |
February | 827.17 | 01-FEB-10:09 | 494.64 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 | 26-FEB-13:13 | 159.64 | 05-FEB-08:00 |
March | 827.17 | 01-MAR-10:09 | 473.34 | 27-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 05-MAR-12:47 | 143.86 | 20-MAR-22:00 |
April | 827.17 | 03-APR-09:09 | 479.03 | 14-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.04 | 23-APR-13:33 | 89.27 | 01-APR-18:00 |
May | 827.17 | 01-MAY-09:09 | 412.51 | 24-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.60 | 21-MAY-14:10 | 19.27 | 06-MAY-20:00 |
June | 827.17 | 01-JUN-09:09 | 361.43 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.18 | 10-JUN-17:08 | 25.29 | 06-JUN-22:00 |
July | 827.17 | 03-JUL-09:09 | 390.14 | 14-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.98 | 16-JUL-13:00 | 16.38 | 31-JUL-02:00 |
August | 827.17 | 01-AUG-09:09 | 441.97 | 23-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.57 | 20-AUG-13:53 | 35.65 | 25-AUG-24:00 |
September | 827.17 | 01-SEP-09:09 | 473.73 | 26-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.99 | 09-SEP-17:08 | 38.08 | 05-SEP-03:00 |
October | 827.17 | 02-OCT-09:09 | 515.03 | 25-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.18 | 09-OCT-11:50 | 68.89 | 29-OCT-02:00 |
November | 827.17 | 01-NOV-09:09 | 503.14 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 11-NOV-12:32 | 100.24 | 12-NOV-07:05 |
December | 827.17 | 01-DEC-10:09 | 508.00 | 12-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 | 10-DEC-11:00 | 144.53 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 361.43 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 | 16.38 | |||||
Maximum of Months | 827.17 | 515.03 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 72.18 | 159.64 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.81 | 16-JAN-15:00 | 244.16 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 20-FEB-14:55 | 350.39 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.99 | 05-MAR-12:53 | 300.12 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.88 | 29-APR-17:02 | 170.46 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.07 | 07-MAY-13:53 | 28.02 | 14-MAY-12:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.56 | 10-JUN-17:02 | 46.35 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.38 | 22-JUL-18:53 | 23.42 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.85 | 20-AUG-13:53 | 68.76 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.56 | 09-SEP-17:02 | 67.37 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.89 | 09-OCT-14:00 | 145.81 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.29 | 05-NOV-13:00 | 209.72 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.70 | 10-DEC-15:00 | 321.84 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 23.42 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.89 | 350.39 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.27 | 16-JAN-14:53 | 303.97 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 | 20-FEB-15:00 | 427.38 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.48 | 05-MAR-13:00 | 377.69 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.29 | 29-APR-17:02 | 212.52 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.27 | 07-MAY-14:00 | 36.74 | 14-MAY-11:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.10 | 10-JUN-17:02 | 58.94 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.11 | 22-JUL-18:53 | 30.92 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.22 | 20-AUG-13:53 | 86.80 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.44 | 09-SEP-17:02 | 87.82 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.63 | 09-OCT-14:00 | 175.45 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 05-NOV-13:00 | 263.59 | 12-NOV-07:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 10-DEC-15:00 | 386.48 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 30.92 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.63 | 427.38 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 | 16-JAN-15:00 | 276.88 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 | 02-FEB-13:00 | 376.59 | 05-FEB-08:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.44 | 26-MAR-14:00 | 367.37 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.07 | 29-APR-17:02 | 233.31 | 01-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 | 07-MAY-14:00 | 77.24 | 14-MAY-11:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.97 | 10-JUN-17:02 | 59.93 | 18-JUN-13:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.63 | 02-JUL-10:53 | 56.87 | 30-JUL-11:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.07 | 20-AUG-13:53 | 82.68 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.92 | 09-SEP-23:00 | 90.35 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.56 | 09-OCT-11:42 | 158.03 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.58 | 07-NOV-22:03 | 249.71 | 12-NOV-11:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 10-DEC-11:05 | 360.71 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 | 56.87 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.92 | 376.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 40380.58 | 02-JAN-05:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 39146.06 | 03-FEB-06:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39565.18 | 01-MAR-06:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39823.87 | 22-APR-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41473.27 | 01-MAY-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40977.36 | 20-JUN-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40619.04 | 11-JUL-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40679.32 | 29-AUG-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 40689.80 | 01-SEP-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40578.98 | 12-OCT-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39404.56 | 14-NOV-06:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39774.54 | 16-DEC-06:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 39146.06 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41473.27 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5266.96 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.63 |
February | 6187.04 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 | 0.00 |
March | 6166.43 | 29-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 0.00 |
April | 8770.75 | 28-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 0.00 |
May | 9495.42 | 10-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 | 0.00 |
June | 9519.95 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.43 | 0.00 |
July | 9905.76 | 18-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 | 0.00 |
August | 9605.62 | 03-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 | 0.00 |
September | 8963.38 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 | 0.00 |
October | 9141.25 | 05-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 |
November | 7363.64 | 02-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.25 | 0.00 |
December | 6449.13 | 15-DEC-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5266.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9905.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.19 | 4.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2930.81 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 |
February | 2538.80 | 13-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.56 |
March | 3110.64 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.92 |
April | 3093.05 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 0.00 |
May | 3873.67 | 22-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 0.00 |
June | 3777.63 | 12-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 | 0.00 |
July | 4462.07 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 | 0.00 |
August | 4069.88 | 28-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.46 | 0.00 |
September | 4217.08 | 05-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 |
October | 4442.04 | 10-OCT-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.68 | 0.00 |
November | 3147.53 | 06-NOV-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 0.00 |
December | 2448.75 | 15-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2448.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4462.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.68 | 72.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3329.66 | 03-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.69 |
February | 2910.68 | 17-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.06 |
March | 3071.69 | 09-MAR-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.59 |
April | 3367.27 | 28-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 | 0.00 |
May | 4280.04 | 22-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.21 | 0.00 |
June | 4118.71 | 19-JUN-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 0.00 |
July | 4921.56 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 | 0.00 |
August | 4622.47 | 14-AUG-12:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 | 0.00 |
September | 4909.25 | 05-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
October | 4783.41 | 10-OCT-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.88 | 0.00 |
November | 3849.62 | 06-NOV-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3189.03 | 18-DEC-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2910.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4921.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.88 | 57.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 25692.10 | 02-JAN-06:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13418.40 | 28-FEB-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22182.55 | 27-MAR-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 28697.75 | 24-APR-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28806.17 | 17-MAY-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28951.34 | 07-JUN-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 29076.53 | 11-JUL-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28765.05 | 17-AUG-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28804.27 | 25-SEP-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29562.94 | 11-OCT-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28789.19 | 06-NOV-06:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20560.03 | 11-DEC-06:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 13418.40 | 0.00 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29562.94 | 6035.01 | 4220.20 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19026.80 | 02-JAN-06:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14184.76 | 27-FEB-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14723.26 | 29-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 24693.25 | 24-APR-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31095.23 | 08-MAY-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31218.64 | 19-JUN-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31211.14 | 31-JUL-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30668.21 | 29-AUG-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 31638.25 | 05-SEP-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32152.09 | 10-OCT-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16786.45 | 03-NOV-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15073.30 | 15-DEC-16:40 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14184.76 | 0.00 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32152.09 | 6035.01 | 4220.20 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3759.27 | 02-JAN-14:10 | 1306.65 | 455.60 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.92 | 0.00 |
February | 3773.10 | 28-FEB-15:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.58 | 0.00 |
March | 4822.12 | 30-MAR-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 0.00 |
April | 5879.39 | 28-APR-15:10 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.29 | 0.00 |
May | 9335.59 | 22-MAY-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
June | 9327.53 | 05-JUN-04:03 | 0.00 | 395.41 | 2059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.80 |
July | 10717.17 | 23-JUL-14:43 | 267.84 | 94.29 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 38.10 | 0.00 |
August | 9821.46 | 20-AUG-16:42 | 267.84 | 94.29 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 32.04 | 0.00 |
September | 10593.86 | 10-SEP-16:12 | 401.76 | 141.44 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 33.56 | 0.00 |
October | 6482.05 | 07-OCT-05:03 | 535.68 | 395.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 0.00 |
November | 4823.81 | 02-NOV-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 0.00 |
December | 4233.81 | 15-DEC-15:00 | 1306.65 | 452.65 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3759.27 | 0.00 | 94.29 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10717.17 | 1306.65 | 494.26 | 2870.49 | 0.00 | 0.00 | 0.00 | 0.00 | 38.10 | 4.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3973.86 | 19-JAN-10:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
February | 4246.85 | 27-FEB-10:40 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 |
March | 5244.66 | 26-MAR-09:35 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 |
April | 11183.50 | 23-APR-08:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 |
May | 11300.56 | 28-MAY-09:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 | 0.00 |
June | 11183.65 | 04-JUN-11:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 0.00 |
July | 11267.32 | 30-JUL-09:13 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 15.19 | 0.00 |
August | 11290.95 | 06-AUG-10:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 | 0.00 |
September | 11258.39 | 10-SEP-09:32 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 35.99 | 0.00 |
October | 8923.19 | 09-OCT-09:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 31.24 | 0.00 |
November | 5068.13 | 02-NOV-10:00 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 | 0.00 |
December | 3290.61 | 16-DEC-10:20 | 261.23 | 89.55 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3290.61 | 169.56 | 59.70 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11300.56 | 827.22 | 268.66 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 35.99 | 14.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14123.68 | 01-JAN-14:12 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 |
February | 13980.69 | 26-FEB-13:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.77 |
March | 12764.08 | 26-MAR-15:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.42 |
April | 9390.38 | 23-APR-15:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 0.00 |
May | 11912.18 | 29-MAY-14:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 14.57 | 0.00 |
June | 10470.09 | 25-JUN-13:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 | 0.00 |
July | 12970.56 | 23-JUL-14:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 39.29 | 0.00 |
August | 13065.80 | 06-AUG-14:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 27.39 | 0.00 |
September | 13838.41 | 24-SEP-13:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 40.69 | 0.00 |
October | 14099.60 | 09-OCT-13:12 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 73.54 | 0.00 |
November | 14554.62 | 11-NOV-12:52 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 |
December | 14680.82 | 10-DEC-12:42 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9390.38 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14680.82 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 73.54 | 28.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8073.11 | 01-JAN-16:53 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 |
February | 11408.92 | 26-FEB-17:33 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 |
March | 6246.94 | 06-MAR-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 0.00 |
April | 12897.78 | 23-APR-16:42 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
May | 12583.01 | 29-MAY-16:52 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 | 0.00 |
June | 12444.42 | 11-JUN-16:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 18.92 | 0.00 |
July | 11623.39 | 23-JUL-14:43 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 26.60 | 0.00 |
August | 11697.10 | 06-AUG-17:23 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
September | 12692.06 | 17-SEP-15:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 37.54 | 0.00 |
October | 12682.68 | 09-OCT-16:32 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 3.63 | 0.00 |
November | 6482.83 | 06-NOV-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 0.00 |
December | 5764.93 | 15-DEC-15:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5764.93 | 0.00 | 59.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12897.78 | 805.38 | 268.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 37.54 | 10.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3348.41 | 02-JAN-13:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
February | 2822.88 | 28-FEB-15:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 | 0.00 |
March | 3582.40 | 30-MAR-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 | 0.00 |
April | 4166.92 | 28-APR-15:10 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 | 0.00 |
May | 7365.97 | 22-MAY-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 | 0.00 |
June | 5648.89 | 19-JUN-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 | 0.00 |
July | 7742.93 | 10-JUL-04:03 | 0.00 | 395.41 | 2059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
August | 7353.58 | 14-AUG-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 0.00 |
September | 7295.15 | 05-SEP-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.90 |
October | 6072.14 | 07-OCT-05:03 | 535.68 | 395.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 | 0.00 |
November | 4379.31 | 03-NOV-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 0.00 |
December | 3787.93 | 15-DEC-14:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2822.88 | 0.00 | 395.41 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7742.93 | 1306.65 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 | 25.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3631.74 | 19-JAN-10:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 |
February | 3611.90 | 27-FEB-10:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
March | 3908.94 | 29-MAR-10:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
April | 7395.51 | 23-APR-08:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 |
May | 7819.28 | 29-MAY-09:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 0.00 |
June | 7976.48 | 04-JUN-11:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 0.00 |
July | 9311.18 | 30-JUL-09:13 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 0.00 |
August | 9896.40 | 06-AUG-10:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 | 0.00 |
September | 10295.45 | 03-SEP-10:22 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 0.00 |
October | 10200.16 | 09-OCT-09:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 | 0.00 |
November | 4723.92 | 06-NOV-09:50 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
December | 3196.14 | 16-DEC-10:20 | 261.23 | 89.55 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3196.14 | 169.56 | 59.70 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10295.45 | 827.22 | 268.66 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 | 6.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12119.38 | 01-JAN-13:52 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 |
February | 11708.60 | 26-FEB-15:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 |
March | 9459.39 | 06-MAR-13:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3837.95 | 0.00 |
April | 10430.77 | 28-APR-16:10 | 1205.27 | 707.27 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 8265.93 | 0.00 |
May | 10669.63 | 19-MAY-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8130.28 | 0.00 |
June | 10828.71 | 28-JUN-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8682.70 | 0.00 |
July | 11373.00 | 21-JUL-16:10 | 2410.55 | 1414.54 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 10992.70 | 0.00 |
August | 11867.37 | 30-AUG-16:20 | 1607.03 | 943.02 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 10634.40 | 0.00 |
September | 11876.74 | 03-SEP-15:42 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 25.92 | 0.00 |
October | 12761.78 | 09-OCT-12:22 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 29.68 | 0.00 |
November | 12275.83 | 11-NOV-14:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 |
December | 12060.10 | 10-DEC-16:12 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9459.39 | 267.84 | 94.29 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12761.78 | 2410.55 | 1414.54 | 4784.12 | 0.00 | 0.00 | 0.00 | 0.00 | 10992.70 | 5.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4348.33 | 19-JAN-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | 0.00 |
February | 8087.48 | 26-FEB-17:23 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
March | 4661.95 | 06-MAR-16:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 | 0.00 |
April | 7788.51 | 29-APR-17:42 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 | 0.00 |
May | 8395.93 | 29-MAY-16:23 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 | 0.00 |
June | 10524.71 | 11-JUN-16:33 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 8.53 | 0.00 |
July | 7871.71 | 03-JUL-04:02 | 0.00 | 312.89 | 1629.46 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | 0.00 |
August | 8797.78 | 06-AUG-17:23 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 |
September | 10907.99 | 03-SEP-17:02 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 0.00 |
October | 10579.31 | 09-OCT-16:22 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 4.05 | 0.00 |
November | 6016.27 | 06-NOV-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | 0.00 |
December | 5314.71 | 10-DEC-16:12 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4348.33 | 0.00 | 59.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10907.99 | 805.38 | 312.89 | 1629.46 | 0.00 | 0.00 | 0.00 | 0.00 | 11.02 | 5.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3817.98 | 02-JAN-13:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.92 | 0.00 |
February | 3515.03 | 28-FEB-15:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 3.06 | 0.00 |
March | 4462.93 | 30-MAR-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 | 0.00 |
April | 5091.61 | 28-APR-15:10 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 0.00 |
May | 7491.80 | 19-MAY-05:03 | 535.68 | 395.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
June | 7791.70 | 26-JUN-04:03 | 0.00 | 395.41 | 2059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7711.68 | 23-JUL-14:43 | 267.84 | 94.29 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 34.28 | 0.00 |
August | 7480.10 | 07-AUG-05:03 | 535.68 | 395.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 |
September | 7596.15 | 05-SEP-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 |
October | 7464.87 | 07-OCT-05:03 | 535.68 | 395.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 | 0.00 |
November | 4371.56 | 03-NOV-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 0.00 |
December | 3869.64 | 15-DEC-15:00 | 1306.65 | 452.65 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3515.03 | 0.00 | 94.29 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7791.70 | 1306.65 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 34.28 | 40.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4139.83 | 19-JAN-10:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 |
February | 4260.22 | 27-FEB-10:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 5239.65 | 26-MAR-09:20 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
April | 11034.16 | 23-APR-09:12 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 |
May | 11061.98 | 14-MAY-09:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 0.00 |
June | 10190.24 | 11-JUN-08:13 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.72 |
July | 10692.82 | 30-JUL-09:13 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 | 0.00 |
August | 10674.07 | 06-AUG-10:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | 0.00 |
September | 11150.19 | 03-SEP-09:02 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 | 0.00 |
October | 11073.85 | 09-OCT-09:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 0.00 |
November | 5117.75 | 06-NOV-09:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 |
December | 3539.88 | 16-DEC-10:00 | 254.35 | 89.55 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3539.88 | 169.56 | 59.70 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11150.19 | 805.43 | 268.66 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 | 9.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12377.90 | 01-JAN-14:12 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 |
February | 12236.54 | 26-FEB-13:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 |
March | 11239.39 | 26-MAR-14:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 7.77 | 0.00 |
April | 7016.66 | 28-APR-14:00 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 | 0.00 |
May | 9190.76 | 22-MAY-04:02 | 0.00 | 494.26 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 | 0.00 |
June | 8187.88 | 05-JUN-04:03 | 0.00 | 395.41 | 2059.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 |
July | 9047.10 | 10-JUL-04:03 | 0.00 | 395.41 | 2059.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
August | 9318.68 | 27-AUG-15:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 45.37 | 0.00 |
September | 12027.58 | 03-SEP-15:42 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 39.69 | 0.00 |
October | 13038.59 | 09-OCT-12:22 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 43.07 | 0.00 |
November | 12805.84 | 11-NOV-13:42 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 |
December | 12367.15 | 10-DEC-11:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7016.66 | 0.00 | 94.29 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13038.59 | 1306.65 | 494.26 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 45.37 | 15.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6974.00 | 01-JAN-16:53 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 |
February | 10134.65 | 26-FEB-17:33 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 |
March | 6104.43 | 26-MAR-15:32 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 |
April | 11414.61 | 23-APR-16:32 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
May | 11306.05 | 29-MAY-16:52 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 14.68 | 0.00 |
June | 11066.72 | 11-JUN-16:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 | 0.00 |
July | 9139.01 | 22-JUL-17:06 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 | 0.00 |
August | 9547.83 | 06-AUG-17:23 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 |
September | 11746.59 | 03-SEP-17:02 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 0.00 |
October | 11357.15 | 09-OCT-16:22 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 4.85 | 0.00 |
November | 6825.95 | 11-NOV-15:43 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.30 |
December | 6420.52 | 10-DEC-16:12 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6104.43 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11746.59 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.27 | 8.81 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.105338E+12 | 107054.69 | 10-JAN-07:10 | 0.873256E+10 | 17174.77 | 05-JAN-07:19 |
February | 0.997457E+11 | 119828.94 | 06-FEB-07:10 | 0.772361E+10 | 15969.50 | 17-FEB-07:40 |
March | 0.115460E+12 | 109504.93 | 30-MAR-12:00 | 0.864305E+10 | 16242.22 | 09-MAR-07:40 |
April | 0.119105E+12 | 132105.67 | 28-APR-15:00 | 0.772991E+10 | 8847.48 | 03-APR-11:50 |
May | 0.152097E+12 | 133868.06 | 30-MAY-12:00 | 0.784776E+10 | 8758.94 | 03-MAY-11:09 |
June | 0.155427E+12 | 137981.12 | 28-JUN-15:09 | 0.745697E+10 | 8666.61 | 02-JUN-11:39 |
July | 0.155574E+12 | 144568.56 | 21-JUL-15:50 | 0.725626E+10 | 8615.99 | 05-JUL-11:09 |
August | 0.164582E+12 | 145720.01 | 30-AUG-15:00 | 0.765577E+10 | 8636.89 | 30-AUG-11:20 |
September | 0.144836E+12 | 137417.49 | 06-SEP-15:00 | 0.732563E+10 | 8706.63 | 29-SEP-11:50 |
October | 0.142728E+12 | 140902.87 | 05-OCT-15:09 | 0.783672E+10 | 8806.03 | 31-OCT-11:50 |
November | 0.115683E+12 | 126083.32 | 02-NOV-15:09 | 0.792451E+10 | 8897.57 | 30-NOV-12:30 |
December | 0.108858E+12 | 115451.87 | 15-DEC-13:00 | 0.843008E+10 | 16574.25 | 20-DEC-07:40 |
Annual Sum or Average | 0.157943E+13 | 0.945628E+11 | ||||
Minimum of Months | 0.997457E+11 | 107054.69 | 0.725626E+10 | 8615.99 | ||
Maximum of Months | 0.164582E+12 | 145720.01 | 0.873256E+10 | 17174.77 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.171889E+11 | 0.506860E+10 | 0.593559E+11 | 0.979873E+09 | 0.423904E+10 | 1312252.65 | 0.484326E+10 | 0.132944E+11 | 0.00 | 0.00 | 0.367060E+09 | 0.00 | 0.00 |
February | 0.154498E+11 | 0.424626E+10 | 0.537310E+11 | 0.886722E+09 | 0.398907E+10 | 1186778.30 | 0.258653E+10 | 0.183703E+11 | 0.00 | 0.00 | 0.484880E+09 | 0.00 | 0.00 |
March | 0.182220E+11 | 0.429518E+10 | 0.617796E+11 | 0.102613E+10 | 0.471391E+10 | 1343621.24 | 0.283884E+10 | 0.220462E+11 | 0.00 | 0.00 | 0.536729E+09 | 0.00 | 0.00 |
April | 0.161864E+11 | 0.377602E+10 | 0.572952E+11 | 0.943668E+09 | 0.526489E+10 | 1267813.82 | 0.186620E+09 | 0.345471E+11 | 0.00 | 0.00 | 0.903744E+09 | 0.00 | 0.00 |
May | 0.173291E+11 | 0.354386E+10 | 0.605677E+11 | 0.100275E+10 | 0.828703E+10 | 1327936.95 | 0.00 | 0.601437E+11 | 0.00 | 0.00 | 0.122193E+10 | 0.00 | 0.00 |
June | 0.171860E+11 | 0.325185E+10 | 0.594895E+11 | 0.987070E+09 | 0.881167E+10 | 1296568.36 | 0.00 | 0.644776E+11 | 0.00 | 0.00 | 0.122193E+10 | 0.00 | 0.00 |
July | 0.161335E+11 | 0.348759E+10 | 0.583622E+11 | 0.959107E+09 | 0.880834E+10 | 1299182.41 | 0.00 | 0.666618E+11 | 0.00 | 0.00 | 0.115986E+10 | 0.00 | 0.00 |
August | 0.180270E+11 | 0.375885E+10 | 0.617796E+11 | 0.102599E+10 | 0.960576E+10 | 1343621.24 | 0.00 | 0.691129E+11 | 0.00 | 0.00 | 0.127094E+10 | 0.00 | 0.00 |
September | 0.162348E+11 | 0.397533E+10 | 0.572729E+11 | 0.943461E+09 | 0.782589E+10 | 1267813.82 | 0.00 | 0.574229E+11 | 0.00 | 0.00 | 0.115986E+10 | 0.00 | 0.00 |
October | 0.169624E+11 | 0.450408E+10 | 0.593671E+11 | 0.979838E+09 | 0.814048E+10 | 1312252.65 | 48794950.18 | 0.517562E+11 | 0.00 | 0.00 | 0.967636E+09 | 0.00 | 0.00 |
November | 0.169719E+11 | 0.477559E+10 | 0.580818E+11 | 0.961670E+09 | 0.531642E+10 | 1278270.02 | 0.419072E+09 | 0.285737E+11 | 0.00 | 0.00 | 0.581698E+09 | 0.00 | 0.00 |
December | 0.167431E+11 | 0.517864E+10 | 0.583511E+11 | 0.959421E+09 | 0.457500E+10 | 1299182.41 | 0.351200E+10 | 0.190570E+11 | 0.00 | 0.00 | 0.480143E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.202635E+12 | 0.498619E+11 | 0.705434E+12 | 0.116557E+11 | 0.795775E+11 | 15535293.87 | 0.144351E+11 | 0.505464E+12 | 0.00 | 0.00 | 0.103564E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154498E+11 | 0.325185E+10 | 0.537310E+11 | 0.886722E+09 | 0.398907E+10 | 1186778.30 | 0.00 | 0.132944E+11 | 0.00 | 0.00 | 0.367060E+09 | 0.00 | 0.00 |
Maximum of Months | 0.182220E+11 | 0.517864E+10 | 0.617796E+11 | 0.102613E+10 | 0.960576E+10 | 1343621.24 | 0.484326E+10 | 0.691129E+11 | 0.00 | 0.00 | 0.127094E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.261371E+09 | 0.00 | 0.847119E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 80134450.20 | 0.00 | 0.764347E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 56295318.64 | 0.00 | 0.858675E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.772991E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.784776E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.745697E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.725626E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.765577E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.732563E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.783672E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.792451E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.189390E+09 | 0.00 | 0.824069E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.587191E+09 | 0.00 | 0.939756E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.725626E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.261371E+09 | 0.00 | 0.858675E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 19911.40 | 31-JAN-08:09 | 5557.43 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 833.39 | 31-JAN-08:20 | 6810.78 | 19-JAN-15:30 | 0.73 | 03-JAN-07:10 | 69023.89 | 10-JAN-07:10 |
February | 20173.07 | 01-FEB-08:09 | 5557.43 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 833.73 | 01-FEB-08:20 | 7522.05 | 27-FEB-16:10 | 0.73 | 06-FEB-07:10 | 81587.44 | 06-FEB-07:10 |
March | 19670.93 | 27-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 833.07 | 27-MAR-07:19 | 6704.21 | 29-MAR-15:20 | 0.73 | 09-MAR-07:10 | 64842.96 | 13-MAR-06:10 |
April | 19890.33 | 14-APR-07:10 | 5557.43 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 833.36 | 14-APR-07:19 | 9962.36 | 28-APR-15:30 | 0.73 | 01-APR-05:30 | 14850.95 | 11-APR-06:10 |
May | 18329.01 | 23-MAY-07:30 | 5557.43 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 831.29 | 23-MAY-07:40 | 10896.13 | 04-MAY-15:00 | 0.73 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 17331.21 | 16-JUN-07:10 | 5557.43 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 829.97 | 16-JUN-07:19 | 11510.24 | 12-JUN-15:00 | 0.73 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 17858.04 | 14-JUL-07:10 | 5557.43 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 830.67 | 14-JUL-07:19 | 12656.40 | 05-JUL-15:09 | 0.73 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 18515.28 | 21-AUG-07:10 | 5557.43 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 831.54 | 21-AUG-07:19 | 13343.01 | 30-AUG-15:00 | 0.73 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 19668.55 | 26-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 833.07 | 26-SEP-07:19 | 12388.55 | 11-SEP-14:30 | 0.73 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 20527.47 | 25-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 834.20 | 25-OCT-07:19 | 13414.70 | 10-OCT-13:39 | 0.73 | 01-OCT-05:10 | 5359.90 | 28-OCT-06:10 |
November | 20173.04 | 21-NOV-16:00 | 5557.43 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 833.68 | 01-NOV-07:19 | 10297.81 | 06-NOV-15:39 | 0.73 | 01-NOV-05:10 | 26380.48 | 16-NOV-07:10 |
December | 20466.01 | 12-DEC-08:09 | 5557.43 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 834.12 | 12-DEC-08:20 | 8671.31 | 15-DEC-15:30 | 0.73 | 04-DEC-08:09 | 71429.03 | 21-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 17331.21 | 5557.43 | 45864.70 | 829.97 | 6704.21 | 0.73 | 0.00 | |||||||
Maximum of Months | 20527.47 | 5557.43 | 45864.70 | 834.20 | 13414.70 | 0.73 | 81587.44 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 39404.69 | 19-JAN-14:00 | 0.00 | 0.00 | 907.56 | 04-JAN-21:10 | 0.00 | 0.00 |
February | 39942.90 | 24-FEB-13:00 | 0.00 | 0.00 | 907.56 | 01-FEB-12:09 | 0.00 | 0.00 |
March | 42666.94 | 30-MAR-12:00 | 0.00 | 0.00 | 907.56 | 06-MAR-07:10 | 0.00 | 0.00 |
April | 61705.99 | 28-APR-15:00 | 0.00 | 0.00 | 907.56 | 04-APR-07:10 | 0.00 | 0.00 |
May | 62658.04 | 30-MAY-12:00 | 0.00 | 0.00 | 907.56 | 01-MAY-16:10 | 0.00 | 0.00 |
June | 67123.39 | 28-JUN-13:00 | 0.00 | 0.00 | 907.56 | 02-JUN-12:09 | 0.00 | 0.00 |
July | 72587.65 | 21-JUL-15:00 | 0.00 | 0.00 | 907.56 | 01-JUL-16:10 | 0.00 | 0.00 |
August | 71855.73 | 03-AUG-15:50 | 0.00 | 0.00 | 907.56 | 01-AUG-16:19 | 0.00 | 0.00 |
September | 64790.48 | 06-SEP-15:00 | 0.00 | 0.00 | 907.56 | 02-SEP-16:10 | 0.00 | 0.00 |
October | 68281.97 | 06-OCT-12:09 | 0.00 | 0.00 | 907.56 | 03-OCT-11:09 | 0.00 | 0.00 |
November | 55339.91 | 02-NOV-15:09 | 0.00 | 0.00 | 907.56 | 02-NOV-11:09 | 0.00 | 0.00 |
December | 46515.14 | 15-DEC-13:00 | 0.00 | 0.00 | 907.56 | 11-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 39404.69 | 0.00 | 0.00 | 907.56 | 0.00 | 0.00 | ||
Maximum of Months | 72587.65 | 0.00 | 0.00 | 907.56 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 107054.69 | 10-JAN-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 3369.01 | 0.73 | 69023.89 | 0.00 | 0.00 |
February | 119828.94 | 06-FEB-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 3579.71 | 0.73 | 81587.44 | 0.00 | 0.00 |
March | 109504.93 | 30-MAR-12:00 | 16818.70 | 42402.18 | 0.00 | 828.07 | 5880.76 | 0.73 | 0.00 | 42666.94 | 0.00 |
April | 132105.67 | 28-APR-15:00 | 16818.70 | 42072.41 | 0.00 | 827.95 | 9772.34 | 0.73 | 0.00 | 61705.99 | 0.00 |
May | 133868.06 | 30-MAY-12:00 | 16818.70 | 42402.18 | 0.00 | 828.07 | 10252.79 | 0.73 | 0.00 | 62658.04 | 0.00 |
June | 137981.12 | 28-JUN-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 10870.88 | 0.73 | 0.00 | 66482.90 | 0.00 |
July | 144568.56 | 21-JUL-15:50 | 16818.70 | 42072.41 | 0.00 | 827.95 | 11569.44 | 0.73 | 0.00 | 72371.78 | 0.00 |
August | 145720.01 | 30-AUG-15:00 | 16818.70 | 42072.41 | 0.00 | 827.95 | 13343.01 | 0.73 | 0.00 | 71749.66 | 0.00 |
September | 137417.49 | 06-SEP-15:00 | 16818.70 | 42072.41 | 0.00 | 827.95 | 11999.67 | 0.73 | 0.00 | 64790.48 | 0.00 |
October | 140902.87 | 05-OCT-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 13149.81 | 0.73 | 0.00 | 67125.72 | 0.00 |
November | 126083.32 | 02-NOV-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 10116.07 | 0.73 | 0.00 | 55339.91 | 0.00 |
December | 115451.87 | 15-DEC-13:00 | 16818.70 | 42402.18 | 0.00 | 828.07 | 7979.51 | 0.73 | 0.00 | 46515.14 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 107054.69 | 7126.03 | 21098.80 | 0.00 | 243.52 | 3369.01 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 145720.01 | 16818.70 | 42402.18 | 5557.43 | 828.07 | 13343.01 | 0.73 | 81587.44 | 72371.78 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 12382.75 | 05-JAN-07:00 | 0.00 | 8988.50 | 23-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 8617.91 | 17-FEB-07:19 | 0.00 | 8972.88 | 13-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 8492.56 | 09-MAR-07:19 | 0.00 | 8941.74 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 8847.48 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 8758.94 | 03-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 8666.61 | 02-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8615.99 | 05-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8636.89 | 30-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8706.63 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 8806.03 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 8897.57 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 10345.11 | 21-DEC-07:19 | 0.00 | 8964.81 | 28-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8615.99 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 12382.75 | 0.00 | 8988.50 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.29 | 0.67 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.46 | 0.67 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.43 | 1.33 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.50 | 1.33 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.83 | 27.43 | 4.33 | 27.43 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.50 | 1.33 | 27.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.90 | 1.00 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.83 | 8.17 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.64 | 6.33 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.71 | 9.33 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.62 | 6.00 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.82 | 6.83 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.62 | 4.67 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Annual Sum or Average | 0.17 | 19.40 | 0.17 | 19.40 | 42.83 | 27.66 | 42.33 | 27.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.40 | 0.17 | 19.40 | 9.67 | 27.90 | 9.33 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.94 | 3.00 | 27.94 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.78 | 1.33 | 27.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.44 | 1.17 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.38 | 2.50 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.42 | 0.83 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.42 | 1.67 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.50 | 3.50 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.82 | 7.00 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.98 | 8.17 | 28.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.75 | 5.50 | 27.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.89 | 4.00 | 27.89 |
Annual Sum or Average | 0.00 | 0.00 | 40.83 | 27.76 | 39.00 | 27.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.98 | 8.17 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.39 | 0.33 | 27.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.79 | 0.33 | 27.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.43 | 0.33 | 27.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.79 | 1.67 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.09 | 2.83 | 28.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.05 | 2.67 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.67 | 4.67 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.74 | 2.33 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.12 | 3.50 | 28.15 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.95 | 3.33 | 27.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.36 | 0.33 | 27.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 33.17 | 27.90 | 22.33 | 27.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.12 | 4.67 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.45 | 0.50 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.65 | 3.33 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.57 | 1.17 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.57 | 4.17 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.49 | 2.33 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.63 | 5.33 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.58 | 2.17 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.00 | 27.59 | 19.00 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.65 | 5.33 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.17 | 18.10 | 19.17 | 18.10 | 2.83 | 18.77 | 2.83 | 19.36 |
February | 11.50 | 18.53 | 11.50 | 18.53 | 1.00 | 18.88 | 1.00 | 19.21 |
March | 17.00 | 18.64 | 17.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
April | 3.00 | 19.60 | 3.00 | 19.60 | 2.67 | 21.23 | 2.67 | 22.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 24.94 | 26.50 | 24.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 25.01 | 31.83 | 25.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 25.39 | 26.67 | 25.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 25.37 | 32.33 | 25.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 25.76 | 17.67 | 25.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 | 25.55 | 42.83 | 25.54 |
November | 4.83 | 19.60 | 4.83 | 19.60 | 16.33 | 23.52 | 16.33 | 24.41 |
December | 19.17 | 18.75 | 19.17 | 18.75 | 5.17 | 19.73 | 5.17 | 20.51 |
Annual Sum or Average | 74.67 | 18.61 | 74.67 | 18.61 | 206.33 | 22.58 | 205.83 | 23.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 | 0.00 | 18.64 |
Maximum of Months | 19.17 | 19.60 | 19.17 | 19.60 | 43.33 | 25.76 | 42.83 | 25.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.42 | 0.67 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.75 | 1.17 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.69 | 1.67 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.46 | 1.50 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.45 | 1.17 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.82 | 3.00 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.68 | 2.67 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.50 | 27.66 | 12.00 | 27.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.82 | 3.00 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.74 | 1.17 | 27.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.90 | 4.67 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.67 | 3.00 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.70 | 5.83 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.58 | 2.83 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.77 | 5.33 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.62 | 3.33 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 26.33 | 27.72 | 26.33 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.90 | 5.83 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.84 | 3.17 | 27.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.60 | 1.67 | 27.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.65 | 6.00 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.83 | 7.83 | 27.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.00 | 8.00 | 27.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.81 | 4.33 | 27.81 |
Annual Sum or Average | 0.00 | 0.00 | 32.17 | 27.56 | 31.67 | 27.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.84 | 8.00 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.64 | 0.33 | 27.64 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.67 | 1.33 | 27.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.92 | 1.83 | 27.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.83 | 2.50 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.54 | 2.67 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.55 | 1.33 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.95 | 3.00 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.82 | 2.83 | 27.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.50 | 27.77 | 16.17 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.95 | 3.00 | 27.99 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 255.67 | 23.58 | 79.83 | 23.79 | 0.00 | 23.79 |
February | 159.67 | 23.63 | 142.33 | 23.99 | 0.00 | 23.99 |
March | 160.50 | 23.55 | 159.50 | 24.01 | 0.00 | 24.01 |
April | 15.67 | 23.70 | 296.00 | 24.52 | 0.00 | 24.52 |
May | 0.00 | 0.00 | 488.50 | 24.36 | 0.00 | 24.36 |
June | 0.00 | 0.00 | 482.33 | 24.32 | 0.00 | 24.32 |
July | 0.00 | 0.00 | 484.67 | 24.35 | 0.00 | 24.35 |
August | 0.00 | 0.00 | 511.17 | 24.32 | 0.00 | 24.32 |
September | 0.00 | 0.00 | 479.67 | 24.32 | 0.00 | 24.32 |
October | 7.50 | 23.73 | 422.67 | 24.41 | 0.00 | 24.41 |
November | 39.17 | 23.71 | 241.17 | 24.39 | 0.00 | 24.39 |
December | 147.50 | 23.55 | 144.17 | 24.03 | 0.00 | 24.03 |
Annual Sum or Average | 785.67 | 23.59 | 3932.00 | 24.25 | 0.00 | 24.25 |
Minimum of Months | 0.00 | 0.00 | 79.83 | 23.79 | 0.00 | 23.79 |
Maximum of Months | 255.67 | 23.73 | 511.17 | 24.52 | 0.00 | 24.52 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 419.00 | 22.58 | 34.17 | 22.71 | 0.00 | 22.71 |
February | 338.33 | 22.72 | 54.17 | 22.92 | 0.17 | 22.92 |
March | 346.33 | 22.85 | 85.33 | 23.13 | 0.00 | 23.13 |
April | 145.33 | 23.28 | 167.33 | 23.87 | 0.00 | 23.87 |
May | 6.17 | 23.28 | 351.00 | 24.29 | 0.00 | 24.29 |
June | 0.50 | 23.33 | 355.33 | 24.28 | 0.00 | 24.28 |
July | 4.17 | 23.27 | 377.50 | 24.29 | 0.00 | 24.29 |
August | 0.83 | 23.34 | 394.33 | 24.27 | 0.00 | 24.27 |
September | 8.33 | 23.26 | 331.83 | 24.27 | 0.00 | 24.27 |
October | 54.00 | 23.37 | 301.33 | 24.20 | 0.00 | 24.20 |
November | 241.33 | 23.24 | 105.17 | 23.56 | 0.00 | 23.56 |
December | 364.67 | 22.77 | 62.50 | 22.99 | 0.00 | 22.99 |
Annual Sum or Average | 1929.00 | 22.85 | 2620.00 | 23.69 | 0.17 | 23.69 |
Minimum of Months | 0.50 | 22.58 | 34.17 | 22.71 | 0.00 | 22.71 |
Maximum of Months | 419.00 | 23.37 | 394.33 | 24.29 | 0.17 | 24.29 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 450.00 | 21.91 | 38.83 | 21.94 | 19.00 | 21.89 |
February | 379.50 | 22.18 | 56.17 | 22.24 | 20.33 | 22.16 |
March | 396.17 | 22.45 | 74.83 | 22.63 | 11.50 | 22.56 |
April | 197.17 | 23.08 | 153.33 | 23.62 | 0.00 | 23.62 |
May | 4.00 | 23.23 | 393.17 | 24.28 | 0.00 | 24.28 |
June | 2.33 | 23.32 | 414.17 | 24.26 | 0.00 | 24.26 |
July | 3.33 | 23.24 | 418.00 | 24.30 | 0.00 | 24.30 |
August | 3.00 | 23.30 | 415.83 | 24.27 | 0.00 | 24.27 |
September | 24.83 | 23.27 | 336.17 | 24.22 | 0.00 | 24.22 |
October | 86.83 | 23.04 | 284.17 | 24.02 | 0.00 | 24.02 |
November | 329.50 | 22.78 | 72.17 | 23.03 | 0.00 | 23.03 |
December | 416.50 | 22.18 | 57.33 | 22.31 | 13.67 | 22.26 |
Annual Sum or Average | 2293.17 | 22.39 | 2714.17 | 23.36 | 64.50 | 23.32 |
Minimum of Months | 2.33 | 21.91 | 38.83 | 21.94 | 0.00 | 21.89 |
Maximum of Months | 450.00 | 23.32 | 418.00 | 24.30 | 20.33 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 456.83 | 21.39 | 144.50 | 21.32 | 116.67 | 21.17 |
February | 388.67 | 21.69 | 105.67 | 21.68 | 61.83 | 21.48 |
March | 393.33 | 22.03 | 120.83 | 22.17 | 47.00 | 22.00 |
April | 208.33 | 22.96 | 198.17 | 23.60 | 8.67 | 23.64 |
May | 11.17 | 26.28 | 471.83 | 24.45 | 10.50 | 24.49 |
June | 6.17 | 25.13 | 477.33 | 24.41 | 3.17 | 24.43 |
July | 13.33 | 26.50 | 479.83 | 24.56 | 12.50 | 24.62 |
August | 7.00 | 25.82 | 486.83 | 24.41 | 5.33 | 24.43 |
September | 30.67 | 24.11 | 407.67 | 24.38 | 8.50 | 24.42 |
October | 111.17 | 23.14 | 340.33 | 24.07 | 12.83 | 24.12 |
November | 338.50 | 22.28 | 100.00 | 22.58 | 14.67 | 22.51 |
December | 417.17 | 21.65 | 124.50 | 21.70 | 75.33 | 21.54 |
Annual Sum or Average | 2382.33 | 22.05 | 3457.50 | 23.20 | 377.00 | 23.09 |
Minimum of Months | 6.17 | 21.39 | 100.00 | 21.32 | 3.17 | 21.17 |
Maximum of Months | 456.83 | 26.50 | 486.83 | 24.56 | 116.67 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 440.00 | 21.68 | 120.67 | 21.71 | 76.00 | 21.53 |
February | 347.50 | 21.91 | 121.00 | 22.09 | 45.00 | 21.91 |
March | 313.83 | 22.07 | 165.83 | 22.55 | 37.17 | 22.39 |
April | 153.00 | 22.96 | 266.33 | 23.88 | 13.17 | 23.94 |
May | 40.33 | 26.68 | 467.50 | 24.66 | 39.00 | 24.81 |
June | 24.67 | 26.43 | 469.33 | 24.54 | 21.50 | 24.64 |
July | 47.00 | 26.63 | 469.33 | 24.76 | 44.50 | 24.93 |
August | 31.67 | 26.23 | 478.33 | 24.54 | 26.67 | 24.65 |
September | 63.67 | 25.03 | 401.50 | 24.58 | 33.17 | 24.73 |
October | 117.50 | 23.68 | 353.33 | 24.29 | 30.17 | 24.42 |
November | 267.00 | 22.39 | 147.17 | 22.98 | 10.17 | 22.92 |
December | 391.33 | 21.83 | 127.83 | 22.01 | 57.00 | 21.86 |
Annual Sum or Average | 2237.50 | 22.48 | 3588.17 | 23.54 | 433.50 | 23.53 |
Minimum of Months | 24.67 | 21.68 | 120.67 | 21.71 | 10.17 | 21.53 |
Maximum of Months | 440.00 | 26.68 | 478.33 | 24.76 | 76.00 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 304.00 | 22.06 | 151.17 | 22.55 | 56.50 | 22.42 |
February | 259.17 | 22.20 | 165.83 | 22.78 | 35.83 | 22.64 |
March | 289.17 | 22.15 | 176.50 | 22.66 | 39.17 | 22.49 |
April | 170.00 | 22.98 | 237.83 | 23.81 | 9.17 | 23.86 |
May | 15.33 | 26.32 | 464.33 | 24.47 | 14.00 | 24.53 |
June | 7.67 | 24.77 | 463.17 | 24.40 | 3.17 | 24.42 |
July | 15.00 | 26.31 | 474.17 | 24.56 | 13.33 | 24.62 |
August | 18.83 | 26.44 | 484.00 | 24.49 | 17.17 | 24.56 |
September | 46.83 | 25.58 | 422.33 | 24.61 | 30.50 | 24.74 |
October | 95.67 | 24.60 | 393.50 | 24.57 | 44.17 | 24.75 |
November | 198.00 | 22.90 | 235.17 | 23.82 | 17.50 | 23.91 |
December | 269.67 | 22.17 | 205.33 | 22.97 | 47.00 | 22.89 |
Annual Sum or Average | 1689.33 | 22.69 | 3873.33 | 23.83 | 327.50 | 23.82 |
Minimum of Months | 7.67 | 22.06 | 151.17 | 22.55 | 3.17 | 22.42 |
Maximum of Months | 304.00 | 26.44 | 484.00 | 24.61 | 56.50 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 426.17 | 21.53 | 138.50 | 21.57 | 95.83 | 21.41 |
February | 352.17 | 21.71 | 128.50 | 21.90 | 58.17 | 21.72 |
March | 354.00 | 21.89 | 145.67 | 22.23 | 44.67 | 22.07 |
April | 208.00 | 22.89 | 221.17 | 23.69 | 17.33 | 23.79 |
May | 35.67 | 25.12 | 439.17 | 24.48 | 19.83 | 24.56 |
June | 25.17 | 25.42 | 441.83 | 24.48 | 15.50 | 24.56 |
July | 33.50 | 25.94 | 446.33 | 24.62 | 26.17 | 24.73 |
August | 27.33 | 24.96 | 460.83 | 24.44 | 14.17 | 24.50 |
September | 66.67 | 24.16 | 382.83 | 24.40 | 21.17 | 24.51 |
October | 122.50 | 23.40 | 335.67 | 24.15 | 25.33 | 24.27 |
November | 311.50 | 22.16 | 132.00 | 22.72 | 11.83 | 22.68 |
December | 379.83 | 21.63 | 142.83 | 21.89 | 67.00 | 21.74 |
Annual Sum or Average | 2342.50 | 22.20 | 3415.33 | 23.33 | 417.00 | 23.27 |
Minimum of Months | 25.17 | 21.53 | 128.50 | 21.57 | 11.83 | 21.41 |
Maximum of Months | 426.17 | 25.94 | 460.83 | 24.62 | 95.83 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 452.33 | 21.91 | 36.33 | 21.96 | 14.50 | 21.92 |
February | 396.83 | 22.09 | 56.00 | 22.13 | 25.17 | 22.04 |
March | 424.17 | 22.29 | 61.67 | 22.42 | 11.67 | 22.37 |
April | 244.67 | 23.02 | 136.17 | 23.45 | 2.00 | 23.46 |
May | 12.00 | 26.09 | 438.50 | 24.37 | 11.00 | 24.42 |
June | 2.33 | 23.42 | 459.17 | 24.32 | 0.00 | 24.32 |
July | 0.00 | 0.00 | 480.17 | 24.43 | 0.00 | 24.43 |
August | 0.00 | 0.00 | 507.00 | 24.36 | 0.00 | 24.36 |
September | 0.00 | 0.00 | 453.83 | 24.38 | 0.00 | 24.38 |
October | 60.33 | 23.37 | 377.83 | 24.24 | 1.00 | 24.24 |
November | 273.00 | 22.95 | 112.50 | 23.30 | 0.00 | 23.30 |
December | 392.00 | 22.27 | 65.67 | 22.49 | 5.67 | 22.47 |
Annual Sum or Average | 2257.67 | 22.38 | 3184.83 | 23.49 | 71.00 | 23.46 |
Minimum of Months | 0.00 | 0.00 | 36.33 | 21.96 | 0.00 | 21.92 |
Maximum of Months | 452.33 | 26.09 | 507.00 | 24.43 | 25.17 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.67 | 22.45 | 59.50 | 22.68 | 3.33 | 22.66 |
February | 320.50 | 22.50 | 81.67 | 22.76 | 7.17 | 22.71 |
March | 307.83 | 22.53 | 130.00 | 23.02 | 6.67 | 22.98 |
April | 134.67 | 23.11 | 255.00 | 23.96 | 3.83 | 23.98 |
May | 23.33 | 26.70 | 469.83 | 24.58 | 23.17 | 24.67 |
June | 6.50 | 25.96 | 475.83 | 24.43 | 4.67 | 24.46 |
July | 15.67 | 26.98 | 486.50 | 24.63 | 15.67 | 24.70 |
August | 8.67 | 27.00 | 509.67 | 24.49 | 8.67 | 24.53 |
September | 18.00 | 27.00 | 465.17 | 24.60 | 18.00 | 24.69 |
October | 51.00 | 24.27 | 409.33 | 24.49 | 13.00 | 24.55 |
November | 167.83 | 23.19 | 211.50 | 23.86 | 0.00 | 23.86 |
December | 315.83 | 22.49 | 113.50 | 22.94 | 3.33 | 22.92 |
Annual Sum or Average | 1773.50 | 22.83 | 3667.50 | 23.91 | 107.50 | 23.94 |
Minimum of Months | 6.50 | 22.45 | 59.50 | 22.68 | 0.00 | 22.66 |
Maximum of Months | 403.67 | 27.00 | 509.67 | 24.63 | 23.17 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 295.50 | 22.18 | 151.67 | 22.82 | 37.83 | 22.74 |
February | 248.00 | 22.24 | 164.67 | 22.98 | 22.00 | 22.88 |
March | 319.83 | 22.04 | 163.33 | 22.58 | 42.17 | 22.49 |
April | 214.67 | 22.94 | 225.17 | 23.62 | 39.67 | 23.63 |
May | 115.50 | 24.32 | 477.67 | 24.35 | 115.50 | 24.35 |
June | 109.33 | 24.19 | 477.67 | 24.33 | 108.17 | 24.31 |
July | 126.33 | 24.30 | 488.83 | 24.46 | 126.33 | 24.44 |
August | 115.83 | 24.35 | 513.33 | 24.47 | 115.83 | 24.45 |
September | 111.50 | 24.49 | 480.00 | 24.52 | 111.50 | 24.51 |
October | 109.83 | 24.60 | 440.33 | 24.70 | 80.33 | 24.77 |
November | 138.67 | 23.32 | 313.83 | 24.23 | 42.83 | 24.28 |
December | 254.33 | 22.41 | 238.67 | 23.36 | 56.33 | 23.35 |
Annual Sum or Average | 2159.33 | 23.04 | 4135.17 | 23.95 | 898.50 | 23.96 |
Minimum of Months | 109.33 | 22.04 | 151.67 | 22.58 | 22.00 | 22.49 |
Maximum of Months | 319.83 | 24.60 | 513.33 | 24.70 | 126.33 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 383.00 | 22.23 | 60.67 | 22.49 | 4.17 | 22.47 |
February | 317.33 | 22.33 | 94.50 | 22.65 | 14.50 | 22.57 |
March | 331.67 | 22.40 | 107.17 | 22.79 | 9.00 | 22.74 |
April | 166.50 | 23.15 | 223.00 | 23.90 | 4.67 | 23.93 |
May | 16.00 | 26.36 | 448.50 | 24.47 | 15.00 | 24.54 |
June | 8.17 | 25.71 | 463.00 | 24.43 | 5.33 | 24.46 |
July | 3.17 | 27.11 | 481.33 | 24.52 | 3.17 | 24.54 |
August | 2.33 | 27.08 | 510.33 | 24.44 | 2.33 | 24.45 |
September | 11.50 | 26.99 | 461.50 | 24.54 | 11.50 | 24.60 |
October | 43.83 | 24.27 | 417.00 | 24.46 | 11.33 | 24.52 |
November | 197.00 | 23.08 | 191.50 | 23.70 | 0.00 | 23.70 |
December | 312.83 | 22.41 | 119.00 | 22.94 | 2.33 | 22.92 |
Annual Sum or Average | 1793.33 | 22.64 | 3577.50 | 23.81 | 83.33 | 23.82 |
Minimum of Months | 2.33 | 22.23 | 60.67 | 22.49 | 0.00 | 22.47 |
Maximum of Months | 383.00 | 27.11 | 510.33 | 24.54 | 15.00 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 440.17 | 21.75 | 68.17 | 21.81 | 34.83 | 21.73 |
February | 368.67 | 22.09 | 83.17 | 22.17 | 33.50 | 22.03 |
March | 375.83 | 22.40 | 96.33 | 22.61 | 16.50 | 22.53 |
April | 170.50 | 23.28 | 215.00 | 23.83 | 7.50 | 23.87 |
May | 9.17 | 26.35 | 483.83 | 24.42 | 9.17 | 24.45 |
June | 0.00 | 0.00 | 487.17 | 24.37 | 0.00 | 24.37 |
July | 2.67 | 26.57 | 485.00 | 24.48 | 2.67 | 24.50 |
August | 0.83 | 26.57 | 500.17 | 24.36 | 0.83 | 24.37 |
September | 2.17 | 24.52 | 426.00 | 24.39 | 0.67 | 24.39 |
October | 79.00 | 23.33 | 361.83 | 24.18 | 7.17 | 24.21 |
November | 288.50 | 22.71 | 100.17 | 23.08 | 0.00 | 23.08 |
December | 396.50 | 22.07 | 81.83 | 22.25 | 21.67 | 22.17 |
Annual Sum or Average | 2134.00 | 22.32 | 3388.67 | 23.49 | 134.50 | 23.45 |
Minimum of Months | 0.00 | 0.00 | 68.17 | 21.81 | 0.00 | 21.73 |
Maximum of Months | 440.17 | 26.57 | 500.17 | 24.48 | 34.83 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 365.67 | 21.99 | 65.17 | 22.12 | 26.33 | 22.02 |
February | 287.83 | 22.21 | 71.67 | 22.43 | 16.17 | 22.33 |
March | 266.83 | 22.32 | 110.17 | 22.83 | 12.33 | 22.75 |
April | 128.17 | 23.24 | 214.17 | 24.05 | 11.33 | 24.13 |
May | 28.00 | 26.81 | 392.33 | 24.72 | 28.00 | 24.85 |
June | 13.33 | 26.67 | 397.00 | 24.57 | 12.33 | 24.64 |
July | 26.83 | 26.86 | 400.67 | 24.79 | 26.50 | 24.91 |
August | 14.67 | 26.65 | 403.17 | 24.57 | 13.67 | 24.65 |
September | 32.83 | 25.93 | 339.17 | 24.73 | 24.00 | 24.86 |
October | 86.83 | 24.00 | 298.00 | 24.47 | 24.33 | 24.59 |
November | 213.67 | 22.73 | 119.00 | 23.37 | 0.33 | 23.38 |
December | 314.67 | 22.11 | 82.83 | 22.39 | 20.00 | 22.30 |
Annual Sum or Average | 1779.33 | 22.67 | 2893.33 | 23.77 | 215.33 | 23.80 |
Minimum of Months | 13.33 | 21.99 | 65.17 | 22.12 | 0.33 | 22.02 |
Maximum of Months | 365.67 | 26.86 | 403.17 | 24.79 | 28.00 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 260.67 | 22.44 | 134.17 | 23.14 | 19.83 | 23.13 |
February | 217.83 | 22.58 | 167.00 | 23.30 | 15.00 | 23.26 |
March | 255.33 | 22.49 | 160.67 | 23.12 | 10.83 | 23.05 |
April | 129.83 | 23.29 | 259.83 | 24.03 | 7.50 | 24.07 |
May | 9.00 | 26.36 | 475.83 | 24.43 | 9.00 | 24.46 |
June | 0.00 | 0.00 | 476.00 | 24.36 | 0.00 | 24.36 |
July | 2.83 | 26.52 | 482.17 | 24.48 | 2.83 | 24.49 |
August | 2.50 | 26.95 | 499.83 | 24.40 | 2.50 | 24.42 |
September | 23.50 | 26.91 | 438.33 | 24.62 | 23.33 | 24.73 |
October | 72.83 | 25.09 | 416.50 | 24.65 | 38.17 | 24.81 |
November | 153.50 | 23.41 | 262.67 | 24.19 | 14.83 | 24.29 |
December | 236.00 | 22.64 | 203.17 | 23.54 | 20.83 | 23.58 |
Annual Sum or Average | 1363.83 | 22.96 | 3976.17 | 24.06 | 164.67 | 24.10 |
Minimum of Months | 0.00 | 0.00 | 134.17 | 23.12 | 0.00 | 23.05 |
Maximum of Months | 260.67 | 26.95 | 499.83 | 24.65 | 38.17 | 24.81 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 400.67 | 21.89 | 81.17 | 22.08 | 29.50 | 21.99 |
February | 322.33 | 22.11 | 101.00 | 22.43 | 21.50 | 22.32 |
March | 322.17 | 22.25 | 128.83 | 22.70 | 15.83 | 22.61 |
April | 158.17 | 23.23 | 247.83 | 23.97 | 13.17 | 24.05 |
May | 16.17 | 26.63 | 454.67 | 24.50 | 16.00 | 24.57 |
June | 14.33 | 26.19 | 457.50 | 24.47 | 11.50 | 24.53 |
July | 16.67 | 26.54 | 464.67 | 24.57 | 15.33 | 24.64 |
August | 6.33 | 26.24 | 479.00 | 24.42 | 5.17 | 24.45 |
September | 29.50 | 25.08 | 413.83 | 24.49 | 14.67 | 24.57 |
October | 81.50 | 23.83 | 365.33 | 24.33 | 20.67 | 24.43 |
November | 265.83 | 22.64 | 144.33 | 23.24 | 0.50 | 23.25 |
December | 345.83 | 22.00 | 111.00 | 22.45 | 16.33 | 22.38 |
Annual Sum or Average | 1979.50 | 22.46 | 3449.17 | 23.65 | 180.17 | 23.65 |
Minimum of Months | 6.33 | 21.89 | 81.17 | 22.08 | 0.50 | 21.99 |
Maximum of Months | 400.67 | 26.63 | 479.00 | 24.57 | 29.50 | 24.64 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.93095 | 34.82189 | 0.29191 | 7.18112 |
February | 454.00000 | 24.01270 | 38.94077 | 0.34196 | 7.88606 |
March | 514.00000 | 24.03741 | 38.55040 | 0.35493 | 8.07821 |
April | 485.00000 | 24.32056 | 42.86308 | 0.46890 | 9.89840 |
May | 508.00000 | 24.34618 | 46.70330 | -0.3259 | 7.65742 |
June | 496.00000 | 24.31147 | 46.75303 | -0.3317 | 7.66654 |
July | 497.00000 | 24.34664 | 46.37734 | -0.3220 | 7.57591 |
August | 514.00000 | 24.31676 | 46.94090 | -0.3224 | 7.55396 |
September | 485.00000 | 24.31338 | 46.39141 | -0.3343 | 7.67399 |
October | 502.00000 | 24.35551 | 43.78131 | 0.50982 | 10.72536 |
November | 489.00000 | 24.23805 | 39.69809 | 0.43137 | 9.16413 |
December | 497.00000 | 24.04862 | 37.55657 | 0.35132 | 8.06746 |
Annual Sum or Average | 5943.00000 | 24.21576 | 42.47201 | 0.09004 | 8.25769 |
Minimum of Months | 454.00000 | 23.93095 | 34.82189 | -0.3343 | 7.18112 |
Maximum of Months | 514.00000 | 24.35551 | 46.94090 | 0.50982 | 10.72536 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.82703 | 38.21312 | 0.04203 | 6.10082 |
February | 454.00000 | 23.05790 | 41.76068 | 0.12465 | 6.51391 |
March | 514.00000 | 23.25817 | 41.15450 | 0.17626 | 6.69413 |
April | 485.00000 | 23.88803 | 44.87408 | 0.36779 | 8.18833 |
May | 508.00000 | 24.13902 | 47.55177 | -0.4048 | 8.75628 |
June | 496.00000 | 24.13443 | 47.58591 | -0.4015 | 8.67456 |
July | 497.00000 | 24.16526 | 47.49173 | -0.3907 | 8.55786 |
August | 514.00000 | 24.15045 | 48.00139 | -0.3920 | 8.53306 |
September | 485.00000 | 24.10027 | 47.84597 | -0.4159 | 8.97192 |
October | 502.00000 | 24.09482 | 45.30773 | 0.44218 | 9.46707 |
November | 489.00000 | 23.67513 | 41.86144 | 0.29130 | 7.30303 |
December | 497.00000 | 23.12671 | 40.67546 | 0.13749 | 6.58849 |
Annual Sum or Average | 5943.00000 | 23.72202 | 44.37665 | -0.0375 | 7.87003 |
Minimum of Months | 454.00000 | 22.82703 | 38.21312 | -0.4159 | 6.10082 |
Maximum of Months | 514.00000 | 24.16526 | 48.00139 | 0.44218 | 9.46707 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.12590 | 39.10819 | -0.1300 | 7.06605 |
February | 454.00000 | 22.46393 | 42.34795 | -0.0189 | 7.02091 |
March | 514.00000 | 22.82010 | 41.52439 | 0.07045 | 6.78144 |
April | 485.00000 | 23.69672 | 44.53873 | 0.32391 | 7.82120 |
May | 508.00000 | 24.15079 | 47.97897 | -0.3809 | 8.38916 |
June | 496.00000 | 24.17360 | 47.78755 | -0.3675 | 8.12912 |
July | 497.00000 | 24.20850 | 47.52033 | -0.3587 | 8.05727 |
August | 514.00000 | 24.16291 | 48.26622 | -0.3704 | 8.20192 |
September | 485.00000 | 24.06687 | 48.05935 | -0.4155 | 9.01766 |
October | 502.00000 | 23.96315 | 45.46753 | 0.41609 | 9.27910 |
November | 489.00000 | 23.17904 | 42.42842 | 0.17214 | 6.66593 |
December | 497.00000 | 22.47884 | 41.49903 | -0.0213 | 6.91032 |
Annual Sum or Average | 5943.00000 | 23.46404 | 44.72682 | -0.0915 | 7.78282 |
Minimum of Months | 454.00000 | 22.12590 | 39.10819 | -0.4155 | 6.66593 |
Maximum of Months | 514.00000 | 24.20850 | 48.26622 | 0.41609 | 9.27910 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.62449 | 41.99328 | -0.2663 | 9.18270 |
February | 454.00000 | 22.01369 | 44.43249 | -0.1347 | 8.82011 |
March | 514.00000 | 22.50005 | 43.34969 | -0.0106 | 7.89041 |
April | 485.00000 | 23.62674 | 46.09521 | 0.31963 | 8.41992 |
May | 508.00000 | 24.36145 | 48.86495 | -0.2673 | 7.25004 |
June | 496.00000 | 24.37750 | 48.07277 | -0.2453 | 6.95509 |
July | 497.00000 | 24.48397 | 48.27276 | -0.2141 | 6.98088 |
August | 514.00000 | 24.34901 | 49.20396 | -0.2613 | 7.17599 |
September | 485.00000 | 24.27967 | 49.37991 | -0.3152 | 8.03184 |
October | 502.00000 | 23.99625 | 47.45966 | 0.44525 | 10.49800 |
November | 489.00000 | 22.80930 | 44.64605 | 0.08542 | 7.19994 |
December | 497.00000 | 22.02061 | 44.52133 | -0.1386 | 8.42269 |
Annual Sum or Average | 5943.00000 | 23.37948 | 46.36948 | -0.0841 | 8.06266 |
Minimum of Months | 454.00000 | 21.62449 | 41.99328 | -0.3152 | 6.95509 |
Maximum of Months | 514.00000 | 24.48397 | 49.37991 | 0.44525 | 10.49800 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.00096 | 41.09910 | -0.1512 | 8.35372 |
February | 454.00000 | 22.41385 | 43.33727 | -0.0146 | 8.27960 |
March | 514.00000 | 22.90155 | 42.05635 | 0.11212 | 8.59800 |
April | 485.00000 | 23.82507 | 45.05236 | 0.40609 | 10.01865 |
May | 508.00000 | 24.41645 | 48.35832 | -0.1882 | 7.23117 |
June | 496.00000 | 24.40129 | 47.72765 | -0.1800 | 6.81628 |
July | 497.00000 | 24.52351 | 47.82135 | -0.1447 | 7.06216 |
August | 514.00000 | 24.36809 | 48.80344 | -0.2024 | 7.05711 |
September | 485.00000 | 24.32800 | 48.86326 | -0.2504 | 8.20482 |
October | 502.00000 | 24.09597 | 46.73207 | 0.50377 | 12.03243 |
November | 489.00000 | 23.19757 | 43.46966 | 0.20066 | 7.93666 |
December | 497.00000 | 22.31574 | 43.68533 | -0.0496 | 8.33878 |
Annual Sum or Average | 5943.00000 | 23.57340 | 45.59848 | 0.00270 | 8.32366 |
Minimum of Months | 454.00000 | 22.00096 | 41.09910 | -0.2504 | 6.81628 |
Maximum of Months | 514.00000 | 24.52351 | 48.86326 | 0.50377 | 12.03243 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.96992 | 38.36969 | 0.09391 | 9.49704 |
February | 454.00000 | 23.09240 | 41.16529 | 0.15877 | 9.50924 |
March | 514.00000 | 23.06375 | 41.46779 | 0.14500 | 8.82249 |
April | 485.00000 | 23.80383 | 45.25863 | 0.37884 | 9.51788 |
May | 508.00000 | 24.35678 | 48.85125 | -0.2651 | 7.33280 |
June | 496.00000 | 24.35383 | 48.19643 | -0.2600 | 7.12040 |
July | 497.00000 | 24.47006 | 48.32709 | -0.2201 | 7.05934 |
August | 514.00000 | 24.37207 | 48.98019 | -0.2343 | 7.07933 |
September | 485.00000 | 24.38694 | 48.72357 | -0.2410 | 7.85618 |
October | 502.00000 | 24.31277 | 45.86944 | 0.57211 | 13.55657 |
November | 489.00000 | 23.76809 | 41.29781 | 0.36155 | 10.41307 |
December | 497.00000 | 23.18921 | 40.98606 | 0.18423 | 10.21920 |
Annual Sum or Average | 5943.00000 | 23.84930 | 44.81808 | 0.05430 | 8.98978 |
Minimum of Months | 454.00000 | 22.96992 | 38.36969 | -0.2651 | 7.05934 |
Maximum of Months | 514.00000 | 24.47006 | 48.98019 | 0.57211 | 13.55657 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.93384 | 40.88409 | -0.1691 | 8.96932 |
February | 454.00000 | 22.25079 | 43.37129 | -0.0494 | 9.08451 |
March | 514.00000 | 22.59575 | 42.57085 | 0.04115 | 8.48281 |
April | 485.00000 | 23.62401 | 45.60455 | 0.36128 | 9.77240 |
May | 508.00000 | 24.29069 | 48.88047 | -0.2480 | 7.58952 |
June | 496.00000 | 24.32655 | 48.09398 | -0.2200 | 7.27520 |
July | 497.00000 | 24.42122 | 48.23217 | -0.1987 | 7.26990 |
August | 514.00000 | 24.30869 | 49.07378 | -0.2279 | 7.21075 |
September | 485.00000 | 24.20941 | 49.23984 | -0.2904 | 8.54045 |
October | 502.00000 | 23.98098 | 47.02133 | 0.47904 | 11.53988 |
November | 489.00000 | 22.88743 | 43.84087 | 0.13524 | 7.96101 |
December | 497.00000 | 22.23581 | 43.46211 | -0.0623 | 8.77172 |
Annual Sum or Average | 5943.00000 | 23.43014 | 45.87247 | -0.0382 | 8.53067 |
Minimum of Months | 454.00000 | 21.93384 | 40.88409 | -0.2904 | 7.21075 |
Maximum of Months | 514.00000 | 24.42122 | 49.23984 | 0.47904 | 11.53988 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.10741 | 40.40806 | -0.1293 | 7.03136 |
February | 454.00000 | 22.31795 | 44.27273 | -0.0526 | 7.07340 |
March | 514.00000 | 22.58638 | 43.62615 | 0.01273 | 6.76585 |
April | 485.00000 | 23.54016 | 46.94794 | 0.28293 | 7.43939 |
May | 508.00000 | 24.25136 | 48.65224 | -0.3489 | 7.99107 |
June | 496.00000 | 24.29164 | 47.84974 | -0.3171 | 7.44515 |
July | 497.00000 | 24.41262 | 47.57513 | -0.2679 | 7.03908 |
August | 514.00000 | 24.35885 | 47.99943 | -0.2727 | 7.01130 |
September | 485.00000 | 24.34438 | 47.80797 | -0.3031 | 7.37958 |
October | 502.00000 | 24.20076 | 45.89888 | 0.48616 | 10.52892 |
November | 489.00000 | 23.42929 | 43.30353 | 0.23804 | 7.09463 |
December | 497.00000 | 22.64040 | 42.56390 | 0.02507 | 6.89521 |
Annual Sum or Average | 5943.00000 | 23.54762 | 45.58328 | -0.0550 | 7.47806 |
Minimum of Months | 454.00000 | 22.10741 | 40.40806 | -0.3489 | 6.76585 |
Maximum of Months | 514.00000 | 24.41262 | 48.65224 | 0.48616 | 10.52892 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.79650 | 39.26621 | 0.04857 | 6.77387 |
February | 454.00000 | 22.96763 | 42.90400 | 0.11822 | 7.11499 |
March | 514.00000 | 23.21383 | 42.07829 | 0.18246 | 7.78334 |
April | 485.00000 | 23.93576 | 45.44139 | 0.40998 | 9.42046 |
May | 508.00000 | 24.41848 | 47.94542 | -0.2366 | 7.22985 |
June | 496.00000 | 24.38807 | 47.37951 | -0.2301 | 6.82416 |
July | 497.00000 | 24.53916 | 47.05938 | -0.1726 | 6.70170 |
August | 514.00000 | 24.44186 | 47.58735 | -0.1935 | 6.60345 |
September | 485.00000 | 24.47967 | 47.27498 | -0.2119 | 7.10835 |
October | 502.00000 | 24.36779 | 45.19047 | 0.56038 | 12.42585 |
November | 489.00000 | 23.88700 | 42.03246 | 0.36914 | 8.68682 |
December | 497.00000 | 23.10037 | 41.71818 | 0.14727 | 7.40944 |
Annual Sum or Average | 5943.00000 | 23.88338 | 44.66836 | 0.06451 | 7.84089 |
Minimum of Months | 454.00000 | 22.79650 | 39.26621 | -0.2366 | 6.60345 |
Maximum of Months | 514.00000 | 24.53916 | 47.94542 | 0.56038 | 12.42585 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.11524 | 38.62196 | 0.18901 | 9.25123 |
February | 454.00000 | 23.21827 | 43.66743 | 0.23590 | 9.17922 |
March | 514.00000 | 22.88320 | 44.22286 | 0.13993 | 8.61186 |
April | 485.00000 | 23.66829 | 49.89399 | 0.36085 | 8.97624 |
May | 508.00000 | 24.32233 | 56.30681 | -0.2708 | 7.03395 |
June | 496.00000 | 24.34222 | 56.29728 | -0.2533 | 6.74673 |
July | 497.00000 | 24.49093 | 56.53303 | -0.1851 | 6.32721 |
August | 514.00000 | 24.49697 | 56.63256 | -0.1496 | 6.13674 |
September | 485.00000 | 24.51567 | 55.54082 | -0.1483 | 6.40999 |
October | 502.00000 | 24.56446 | 49.43879 | 0.66500 | 15.52644 |
November | 489.00000 | 24.14253 | 43.49141 | 0.49884 | 11.90758 |
December | 497.00000 | 23.44446 | 41.67825 | 0.30102 | 10.64917 |
Annual Sum or Average | 5943.00000 | 23.93707 | 49.40480 | 0.11313 | 8.88921 |
Minimum of Months | 454.00000 | 22.88320 | 38.62196 | -0.2708 | 6.13674 |
Maximum of Months | 514.00000 | 24.56446 | 56.63256 | 0.66500 | 15.52644 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.69013 | 39.18930 | 0.02562 | 7.02731 |
February | 454.00000 | 22.87401 | 42.84744 | 0.09942 | 7.52509 |
March | 514.00000 | 23.02936 | 42.52857 | 0.13637 | 7.42169 |
April | 485.00000 | 23.87356 | 45.77330 | 0.39292 | 9.26012 |
May | 508.00000 | 24.32012 | 48.43873 | -0.2882 | 7.54801 |
June | 496.00000 | 24.36175 | 47.64847 | -0.2558 | 7.11060 |
July | 497.00000 | 24.48421 | 47.37492 | -0.2126 | 6.83592 |
August | 514.00000 | 24.42229 | 47.74717 | -0.2074 | 6.60624 |
September | 485.00000 | 24.44357 | 47.45861 | -0.2281 | 7.08482 |
October | 502.00000 | 24.35301 | 45.30534 | 0.55592 | 12.22238 |
November | 489.00000 | 23.74787 | 42.26919 | 0.33781 | 8.35844 |
December | 497.00000 | 23.08620 | 41.44910 | 0.14971 | 7.57506 |
Annual Sum or Average | 5943.00000 | 23.81250 | 44.85007 | 0.04058 | 7.87955 |
Minimum of Months | 454.00000 | 22.69013 | 39.18930 | -0.2882 | 6.60624 |
Maximum of Months | 514.00000 | 24.48421 | 48.43873 | 0.55592 | 12.22238 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.02992 | 41.43913 | -0.1488 | 7.61272 |
February | 454.00000 | 22.43802 | 44.10971 | -0.0223 | 7.53216 |
March | 514.00000 | 22.84255 | 43.11739 | 0.07771 | 7.19116 |
April | 485.00000 | 23.82369 | 46.25938 | 0.36371 | 8.49448 |
May | 508.00000 | 24.35922 | 48.26227 | -0.2905 | 7.33076 |
June | 496.00000 | 24.36057 | 47.62790 | -0.2759 | 7.07347 |
July | 497.00000 | 24.45849 | 47.99424 | -0.2442 | 7.01243 |
August | 514.00000 | 24.34632 | 48.66155 | -0.2833 | 7.21746 |
September | 485.00000 | 24.31275 | 48.95048 | -0.3182 | 7.77429 |
October | 502.00000 | 24.12470 | 47.05972 | 0.46858 | 10.41891 |
November | 489.00000 | 23.24880 | 44.04390 | 0.19264 | 6.99656 |
December | 497.00000 | 22.46390 | 43.85412 | -0.0188 | 7.30635 |
Annual Sum or Average | 5943.00000 | 23.57465 | 45.95830 | -0.0428 | 7.66247 |
Minimum of Months | 454.00000 | 22.02992 | 41.43913 | -0.3182 | 6.99656 |
Maximum of Months | 514.00000 | 24.45849 | 48.95048 | 0.46858 | 10.41891 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.32914 | 40.27473 | -0.0642 | 7.48875 |
February | 385.00000 | 22.70008 | 42.62587 | 0.05297 | 7.44973 |
March | 433.00000 | 23.07488 | 41.58309 | 0.15103 | 8.05022 |
April | 410.00000 | 23.95436 | 45.13990 | 0.41944 | 9.85459 |
May | 430.00000 | 24.49699 | 47.37888 | -0.2111 | 7.44643 |
June | 418.00000 | 24.46300 | 46.85163 | -0.2144 | 7.03754 |
July | 422.00000 | 24.59919 | 47.13838 | -0.1705 | 7.19657 |
August | 433.00000 | 24.43959 | 47.96211 | -0.2272 | 7.21820 |
September | 410.00000 | 24.42765 | 48.08629 | -0.2554 | 8.19033 |
October | 427.00000 | 24.23920 | 46.19680 | 0.51475 | 11.91877 |
November | 417.00000 | 23.47505 | 42.55171 | 0.26125 | 7.91661 |
December | 422.00000 | 22.63961 | 42.84136 | 0.03378 | 7.65199 |
Annual Sum or Average | 5034.00000 | 23.74210 | 44.89522 | 0.02342 | 8.11994 |
Minimum of Months | 385.00000 | 22.32914 | 40.27473 | -0.2554 | 7.03754 |
Maximum of Months | 433.00000 | 24.59919 | 48.08629 | 0.51475 | 11.91877 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.35993 | 37.62456 | 0.20079 | 8.87816 |
February | 454.00000 | 23.47304 | 40.79096 | 0.25715 | 9.02673 |
March | 514.00000 | 23.37030 | 41.17185 | 0.22304 | 8.33636 |
April | 485.00000 | 23.98455 | 45.38332 | 0.41784 | 9.53061 |
May | 508.00000 | 24.36163 | 48.22123 | -0.2866 | 7.35404 |
June | 496.00000 | 24.34047 | 47.74731 | -0.2892 | 7.21956 |
July | 497.00000 | 24.44813 | 48.03702 | -0.2491 | 7.06961 |
August | 514.00000 | 24.37627 | 48.40662 | -0.2558 | 7.06637 |
September | 485.00000 | 24.43070 | 48.24417 | -0.2437 | 7.55336 |
October | 502.00000 | 24.41783 | 45.45578 | 0.58732 | 13.44749 |
November | 489.00000 | 24.06374 | 40.87394 | 0.43610 | 10.67834 |
December | 497.00000 | 23.56159 | 40.33826 | 0.28417 | 9.85114 |
Annual Sum or Average | 5943.00000 | 24.01832 | 44.38281 | 0.08777 | 8.82659 |
Minimum of Months | 454.00000 | 23.35993 | 37.62456 | -0.2892 | 7.06637 |
Maximum of Months | 514.00000 | 24.44813 | 48.40662 | 0.58732 | 13.44749 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35508 | 40.39960 | -0.0508 | 7.71295 |
February | 454.00000 | 22.70318 | 43.08039 | 0.06625 | 8.01366 |
March | 514.00000 | 22.96600 | 42.36468 | 0.13329 | 7.83677 |
April | 485.00000 | 23.88884 | 45.71886 | 0.41688 | 9.88685 |
May | 508.00000 | 24.33870 | 48.21331 | -0.2589 | 7.38493 |
June | 496.00000 | 24.35812 | 47.56450 | -0.2388 | 7.12688 |
July | 497.00000 | 24.44899 | 47.88757 | -0.2151 | 7.07712 |
August | 514.00000 | 24.34452 | 48.49004 | -0.2411 | 7.02977 |
September | 485.00000 | 24.31070 | 48.72818 | -0.2769 | 7.90559 |
October | 502.00000 | 24.16422 | 46.60505 | 0.51137 | 11.59841 |
November | 489.00000 | 23.34044 | 43.29484 | 0.24321 | 7.84487 |
December | 497.00000 | 22.67761 | 42.93271 | 0.05551 | 7.86923 |
Annual Sum or Average | 5943.00000 | 23.66404 | 45.45418 | 0.01067 | 8.10267 |
Minimum of Months | 454.00000 | 22.35508 | 40.39960 | -0.2769 | 7.02977 |
Maximum of Months | 514.00000 | 24.44899 | 48.72818 | 0.51137 | 11.59841 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.197542E+11 | 0.487543E+10 | 251.40 | 0.136737E+11 | 0.608050E+10 | 0.00 | 1.00 | 02-JAN-05:03 | 0.00 | 01-JAN-00:10 | 64473.87 | 19-JAN-13:10 | 59440.90 | 02-JAN-05:03 | 31975.48 | 20-JAN-06:03 | 15112.65 | 19-JAN-13:10 | 0.00 |
February | 0.269705E+11 | 0.661308E+10 | 289.65 | 0.175205E+11 | 0.944998E+10 | 0.00 | 1.00 | 01-FEB-13:10 | 0.00 | 01-FEB-00:10 | 64212.81 | 24-FEB-13:05 | 49729.89 | 27-FEB-06:03 | 21039.01 | 23-FEB-06:03 | 15838.19 | 24-FEB-13:05 | 0.00 |
March | 0.321711E+11 | 0.793067E+10 | 350.43 | 0.219851E+11 | 0.101860E+11 | 0.00 | 1.00 | 06-MAR-06:03 | 0.00 | 01-MAR-00:10 | 69013.55 | 28-MAR-12:00 | 50996.17 | 27-MAR-05:03 | 28839.11 | 29-MAR-05:03 | 17016.94 | 30-MAR-12:00 | 0.00 |
April | 0.503481E+11 | 0.123941E+11 | 394.75 | 0.356531E+11 | 0.146950E+11 | 0.00 | 1.00 | 01-APR-05:03 | 0.00 | 01-APR-00:10 | 80927.15 | 28-APR-16:00 | 54960.34 | 28-APR-15:10 | 29277.51 | 28-APR-17:00 | 22000.54 | 28-APR-16:00 | 0.00 |
May | 0.871696E+11 | 0.221721E+11 | 449.39 | 0.587983E+11 | 0.283713E+11 | 0.00 | 1.00 | 01-MAY-04:03 | 0.00 | 01-MAY-00:10 | 126029.28 | 22-MAY-04:02 | 75843.41 | 22-MAY-04:02 | 50185.87 | 22-MAY-04:02 | 29775.19 | 22-MAY-04:02 | 0.00 |
June | 0.930379E+11 | 0.239594E+11 | 450.69 | 0.622549E+11 | 0.307830E+11 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 92862.33 | 05-JUN-12:03 | 67750.72 | 05-JUN-04:03 | 40062.86 | 29-JUN-17:00 | 25446.83 | 29-JUN-12:04 | 0.00 |
July | 0.973146E+11 | 0.250173E+11 | 453.28 | 0.623885E+11 | 0.349260E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 103698.21 | 05-JUL-12:02 | 80036.76 | 05-JUL-04:02 | 38776.86 | 12-JUL-12:02 | 27951.11 | 05-JUL-12:04 | 0.00 |
August | 0.104073E+12 | 0.266189E+11 | 469.28 | 0.680603E+11 | 0.360125E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 99282.42 | 07-AUG-12:02 | 79190.91 | 14-AUG-04:02 | 40723.19 | 09-AUG-17:00 | 26575.77 | 03-AUG-16:00 | 0.00 |
September | 0.888251E+11 | 0.220077E+11 | 449.27 | 0.575601E+11 | 0.312650E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 100212.23 | 05-SEP-12:02 | 80072.98 | 05-SEP-04:02 | 38611.70 | 05-SEP-12:02 | 25585.19 | 05-SEP-12:02 | 0.00 |
October | 0.793325E+11 | 0.198379E+11 | 444.81 | 0.547156E+11 | 0.246169E+11 | 0.00 | 1.00 | 01-OCT-15:53 | 0.00 | 01-OCT-00:10 | 102324.92 | 06-OCT-12:02 | 79702.88 | 10-OCT-04:02 | 44892.69 | 24-OCT-12:03 | 26994.49 | 06-OCT-12:02 | 0.00 |
November | 0.443175E+11 | 0.108604E+11 | 388.24 | 0.313881E+11 | 0.129294E+11 | 0.00 | 1.00 | 01-NOV-07:05 | 0.00 | 01-NOV-00:10 | 86533.89 | 07-NOV-13:05 | 58164.72 | 03-NOV-05:03 | 34885.39 | 03-NOV-17:00 | 21451.34 | 07-NOV-13:05 | 0.00 |
December | 0.289957E+11 | 0.711894E+10 | 291.75 | 0.197585E+11 | 0.923720E+10 | 0.00 | 1.00 | 08-DEC-11:40 | 0.00 | 01-DEC-00:10 | 75691.76 | 14-DEC-13:05 | 53396.26 | 16-DEC-06:03 | 29086.55 | 12-DEC-14:00 | 18636.80 | 14-DEC-13:05 | 0.00 |
Annual Sum or Average | 0.752310E+12 | 0.189406E+12 | 4682.93 | 0.503757E+12 | 0.248553E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.197542E+11 | 0.487543E+10 | 251.40 | 0.136737E+11 | 0.608050E+10 | 0.00 | 1.00 | 0.00 | 64212.81 | 49729.89 | 21039.01 | 15112.65 | 0.00 | ||||||
Maximum of Months | 0.104073E+12 | 0.266189E+11 | 469.28 | 0.680603E+11 | 0.360125E+11 | 0.00 | 1.00 | 0.00 | 126029.28 | 80072.98 | 50185.87 | 29775.19 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.162951E+11 | 0.402508E+10 | 249.23 | 0.113807E+11 | 0.491436E+10 | 0.00 | 1.00 | 01-JAN-16:53 | 0.00 | 01-JAN-00:10 | 49839.80 | 19-JAN-16:30 | 35617.81 | 19-JAN-15:40 | 18558.94 | 31-JAN-16:30 | 11616.35 | 19-JAN-16:30 | 0.00 |
February | 0.226962E+11 | 0.556407E+10 | 292.14 | 0.151400E+11 | 0.755619E+10 | 0.00 | 1.00 | 01-FEB-13:40 | 0.00 | 01-FEB-00:10 | 50494.64 | 27-FEB-16:50 | 37849.11 | 27-FEB-15:30 | 17190.95 | 24-FEB-10:50 | 11793.64 | 27-FEB-16:50 | 0.00 |
March | 0.268076E+11 | 0.661122E+10 | 354.86 | 0.190916E+11 | 0.771603E+10 | 0.00 | 1.00 | 06-MAR-09:40 | 0.00 | 01-MAR-00:10 | 49682.75 | 07-MAR-14:50 | 35511.49 | 29-MAR-15:20 | 19920.57 | 07-MAR-16:00 | 11557.56 | 07-MAR-14:50 | 0.00 |
April | 0.413694E+11 | 0.102017E+11 | 398.91 | 0.303378E+11 | 0.110316E+11 | 0.00 | 1.00 | 04-APR-13:40 | 0.00 | 01-APR-00:10 | 58485.51 | 28-APR-16:00 | 44821.28 | 28-APR-15:30 | 23559.73 | 24-APR-11:00 | 16318.99 | 28-APR-16:00 | 0.00 |
May | 0.641176E+11 | 0.165436E+11 | 449.53 | 0.485528E+11 | 0.155649E+11 | 0.00 | 1.00 | 01-MAY-04:03 | 0.00 | 01-MAY-00:10 | 94851.15 | 22-MAY-04:02 | 66434.39 | 30-MAY-04:02 | 28464.01 | 22-MAY-04:02 | 22664.76 | 22-MAY-04:02 | 0.00 |
June | 0.660738E+11 | 0.173402E+11 | 449.37 | 0.503615E+11 | 0.157123E+11 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 68138.52 | 17-JUN-05:03 | 65993.97 | 05-JUN-04:03 | 24171.25 | 29-JUN-21:00 | 17429.56 | 28-JUN-14:30 | 0.00 |
July | 0.676900E+11 | 0.177614E+11 | 452.89 | 0.499763E+11 | 0.177137E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 73967.83 | 03-JUL-04:02 | 67433.53 | 05-JUL-04:02 | 26786.19 | 31-JUL-12:50 | 18785.17 | 21-JUL-15:50 | 0.00 |
August | 0.703787E+11 | 0.183026E+11 | 461.72 | 0.518606E+11 | 0.185181E+11 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 76270.40 | 16-AUG-05:03 | 66649.63 | 28-AUG-04:02 | 27496.28 | 07-AUG-15:00 | 19259.93 | 30-AUG-16:00 | 0.00 |
September | 0.628236E+11 | 0.157244E+11 | 436.28 | 0.445448E+11 | 0.182788E+11 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 85544.97 | 05-SEP-04:02 | 67075.81 | 11-SEP-04:02 | 25919.42 | 01-SEP-17:00 | 19645.77 | 05-SEP-04:02 | 0.00 |
October | 0.563432E+11 | 0.142439E+11 | 429.88 | 0.423119E+11 | 0.140313E+11 | 0.00 | 1.00 | 01-OCT-14:32 | 0.00 | 01-OCT-00:10 | 76324.45 | 07-OCT-05:03 | 67372.95 | 10-OCT-04:02 | 24880.17 | 24-OCT-06:40 | 18439.39 | 05-OCT-15:00 | 0.00 |
November | 0.336737E+11 | 0.831125E+10 | 381.97 | 0.245011E+11 | 0.917264E+10 | 0.00 | 1.00 | 01-NOV-07:00 | 0.00 | 01-NOV-00:10 | 57446.67 | 02-NOV-15:20 | 45084.75 | 06-NOV-15:40 | 23133.89 | 02-NOV-08:20 | 14930.46 | 02-NOV-15:00 | 0.00 |
December | 0.228246E+11 | 0.561292E+10 | 287.11 | 0.159222E+11 | 0.690242E+10 | 0.00 | 1.00 | 08-DEC-14:20 | 0.00 | 01-DEC-00:10 | 53024.32 | 12-DEC-16:30 | 41107.24 | 15-DEC-15:40 | 21718.22 | 14-DEC-11:10 | 12927.12 | 15-DEC-15:10 | 0.00 |
Annual Sum or Average | 0.551094E+12 | 0.140242E+12 | 4643.88 | 0.403981E+12 | 0.147112E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.162951E+11 | 0.402508E+10 | 249.23 | 0.113807E+11 | 0.491436E+10 | 0.00 | 1.00 | 0.00 | 49682.75 | 35511.49 | 17190.95 | 11557.56 | 0.00 | ||||||
Maximum of Months | 0.703787E+11 | 0.183026E+11 | 461.72 | 0.518606E+11 | 0.185181E+11 | 0.00 | 1.00 | 0.00 | 94851.15 | 67433.53 | 28464.01 | 22664.76 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.176413E+11 | 0.439386E+10 | 246.01 | 0.120001E+11 | 0.564118E+10 | 0.00 | 1.00 | 01-JAN-16:12 | 0.00 | 01-JAN-00:10 | 59518.08 | 19-JAN-15:00 | 41871.76 | 01-JAN-16:53 | 19660.77 | 19-JAN-14:40 | 13966.26 | 19-JAN-15:00 | 0.00 |
February | 0.250743E+11 | 0.619314E+10 | 291.15 | 0.165114E+11 | 0.856295E+10 | 0.00 | 1.00 | 01-FEB-14:20 | 0.00 | 01-FEB-00:10 | 58712.61 | 27-FEB-15:30 | 44181.65 | 27-FEB-15:30 | 17166.63 | 24-FEB-16:00 | 14032.63 | 27-FEB-15:30 | 0.00 |
March | 0.302603E+11 | 0.750434E+10 | 354.40 | 0.208773E+11 | 0.938302E+10 | 0.00 | 1.00 | 06-MAR-10:20 | 0.00 | 01-MAR-00:10 | 59658.49 | 29-MAR-15:00 | 43854.44 | 29-MAR-15:00 | 21621.13 | 07-MAR-11:40 | 15150.00 | 30-MAR-13:00 | 0.00 |
April | 0.482131E+11 | 0.119513E+11 | 399.79 | 0.342385E+11 | 0.139746E+11 | 0.00 | 1.00 | 04-APR-13:30 | 0.00 | 01-APR-00:10 | 86432.40 | 28-APR-16:00 | 61155.13 | 28-APR-15:20 | 26606.46 | 28-APR-16:00 | 23386.46 | 28-APR-16:00 | 0.00 |
May | 0.842371E+11 | 0.214280E+11 | 449.72 | 0.574644E+11 | 0.267727E+11 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 109328.77 | 22-MAY-04:02 | 78982.82 | 22-MAY-04:02 | 30345.95 | 22-MAY-04:02 | 26147.06 | 22-MAY-04:02 | 0.00 |
June | 0.901944E+11 | 0.231779E+11 | 450.44 | 0.610618E+11 | 0.291327E+11 | 0.00 | 1.00 | 01-JUN-07:30 | 0.00 | 01-JUN-00:10 | 91053.47 | 28-JUN-14:30 | 70791.78 | 05-JUN-04:03 | 32884.12 | 29-JUN-15:00 | 25488.52 | 28-JUN-14:00 | 0.00 |
July | 0.932513E+11 | 0.238831E+11 | 460.09 | 0.600485E+11 | 0.332028E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 93598.54 | 05-JUL-13:50 | 78498.42 | 24-JUL-04:02 | 34240.04 | 22-JUL-10:10 | 26988.37 | 21-JUL-16:00 | 0.00 |
August | 0.949687E+11 | 0.241914E+11 | 462.76 | 0.614301E+11 | 0.335387E+11 | 0.00 | 1.00 | 01-AUG-05:03 | 0.00 | 01-AUG-00:10 | 91693.47 | 14-AUG-13:30 | 77759.39 | 28-AUG-04:02 | 35230.27 | 09-AUG-17:10 | 26408.73 | 03-AUG-15:50 | 0.00 |
September | 0.795184E+11 | 0.196908E+11 | 439.61 | 0.504011E+11 | 0.291173E+11 | 0.00 | 1.00 | 01-SEP-05:03 | 0.00 | 01-SEP-00:10 | 89245.00 | 11-SEP-14:00 | 75075.07 | 11-SEP-04:02 | 33619.62 | 18-SEP-10:00 | 23635.71 | 01-SEP-15:00 | 0.00 |
October | 0.706756E+11 | 0.176743E+11 | 430.13 | 0.477227E+11 | 0.229529E+11 | 0.00 | 1.00 | 01-OCT-14:53 | 0.00 | 01-OCT-00:10 | 96034.15 | 06-OCT-14:00 | 67322.69 | 05-OCT-15:00 | 38699.94 | 07-OCT-08:00 | 25004.56 | 06-OCT-14:00 | 0.00 |
November | 0.379570E+11 | 0.940197E+10 | 380.06 | 0.258109E+11 | 0.121460E+11 | 0.00 | 1.00 | 01-NOV-09:30 | 0.00 | 01-NOV-00:10 | 79985.68 | 02-NOV-14:00 | 55342.88 | 02-NOV-15:00 | 27221.34 | 03-NOV-16:10 | 20382.04 | 02-NOV-14:40 | 0.00 |
December | 0.255460E+11 | 0.632510E+10 | 287.08 | 0.170079E+11 | 0.853808E+10 | 0.00 | 1.00 | 08-DEC-14:00 | 0.00 | 01-DEC-00:10 | 65510.38 | 15-DEC-15:00 | 50405.11 | 15-DEC-15:00 | 26415.31 | 12-DEC-15:00 | 16730.52 | 15-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.697538E+12 | 0.175815E+12 | 4651.25 | 0.464575E+12 | 0.232963E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.176413E+11 | 0.439386E+10 | 246.01 | 0.120001E+11 | 0.564118E+10 | 0.00 | 1.00 | 0.00 | 58712.61 | 41871.76 | 17166.63 | 13966.26 | 0.00 | ||||||
Maximum of Months | 0.949687E+11 | 0.241914E+11 | 462.76 | 0.614301E+11 | 0.335387E+11 | 0.00 | 1.00 | 0.00 | 109328.77 | 78982.82 | 38699.94 | 26988.37 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.49 | 0.00 | 284.49 | 232.33 | 921.80 | 0.00 | 0.00 | 0.00 |
February | 335.63 | 0.00 | 335.63 | 309.66 | 768.96 | 0.00 | 0.00 | 0.00 |
March | 389.36 | 0.00 | 389.36 | 430.92 | 663.43 | 0.00 | 0.00 | 0.00 |
April | 459.53 | 1.89 | 457.64 | 648.95 | 424.51 | 0.00 | 0.00 | 0.00 |
May | 520.51 | 19.04 | 501.47 | 1056.03 | 125.85 | 0.00 | 0.00 | 0.00 |
June | 591.93 | 40.99 | 550.94 | 1245.85 | 109.22 | 0.00 | 0.00 | 0.00 |
July | 574.43 | 21.88 | 552.54 | 1198.31 | 73.47 | 0.00 | 0.00 | 0.00 |
August | 514.41 | 4.05 | 510.36 | 1084.24 | 102.09 | 0.00 | 0.00 | 0.00 |
September | 444.33 | 0.03 | 444.30 | 864.43 | 140.79 | 0.00 | 0.00 | 0.00 |
October | 386.12 | 0.00 | 386.12 | 703.39 | 268.38 | 0.00 | 0.00 | 0.00 |
November | 293.12 | 0.00 | 293.12 | 342.49 | 590.09 | 0.00 | 0.00 | 0.00 |
December | 264.47 | 0.00 | 264.47 | 246.76 | 782.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 421.95 | 7.35 | 414.61 | 699.27 | 412.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 264.47 | 0.00 | 264.47 | 232.33 | 73.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 591.93 | 40.99 | 552.54 | 1245.85 | 921.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 488.11 | 248.55 | 239.56 | 606.54 | 569.98 | 0.00 | 0.00 | 0.00 |
February | 543.52 | 262.40 | 281.13 | 707.60 | 479.25 | 0.00 | 0.00 | 0.00 |
March | 639.36 | 308.35 | 331.02 | 887.11 | 418.44 | 0.00 | 0.00 | 0.00 |
April | 701.63 | 317.33 | 384.30 | 1091.82 | 278.33 | 0.00 | 0.00 | 0.00 |
May | 723.19 | 313.59 | 409.60 | 1335.08 | 84.17 | 0.00 | 0.00 | 0.00 |
June | 733.43 | 290.86 | 442.58 | 1399.93 | 72.93 | 0.00 | 0.00 | 0.00 |
July | 707.14 | 258.77 | 448.36 | 1350.99 | 48.04 | 0.00 | 0.00 | 0.00 |
August | 651.60 | 224.03 | 427.58 | 1247.92 | 68.34 | 0.00 | 0.00 | 0.00 |
September | 577.20 | 198.44 | 378.76 | 1055.02 | 92.96 | 0.00 | 0.00 | 0.00 |
October | 570.39 | 240.70 | 329.69 | 995.28 | 174.39 | 0.00 | 0.00 | 0.00 |
November | 505.00 | 257.62 | 247.38 | 722.14 | 372.43 | 0.00 | 0.00 | 0.00 |
December | 397.61 | 180.11 | 217.50 | 514.61 | 497.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 603.39 | 258.28 | 345.11 | 994.37 | 261.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 397.61 | 180.11 | 217.50 | 514.61 | 48.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 733.43 | 317.33 | 448.36 | 1399.93 | 569.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1644.39 | 1172.73 | 471.66 | 2382.52 | 870.44 | 0.00 | 0.00 | 0.00 |
February | 1491.37 | 965.33 | 526.03 | 2209.68 | 744.05 | 0.00 | 0.00 | 0.00 |
March | 952.12 | 429.69 | 522.43 | 1451.66 | 660.73 | 0.00 | 0.00 | 0.00 |
April | 705.70 | 165.36 | 540.34 | 1181.68 | 441.51 | 0.00 | 0.00 | 0.00 |
May | 539.21 | 22.92 | 516.29 | 1106.29 | 129.18 | 0.00 | 0.00 | 0.00 |
June | 532.65 | 4.96 | 527.68 | 1124.92 | 112.41 | 0.00 | 0.00 | 0.00 |
July | 557.59 | 10.25 | 547.34 | 1169.73 | 71.41 | 0.00 | 0.00 | 0.00 |
August | 655.98 | 78.74 | 577.24 | 1384.30 | 106.84 | 0.00 | 0.00 | 0.00 |
September | 787.06 | 207.42 | 579.64 | 1535.41 | 150.31 | 0.00 | 0.00 | 0.00 |
October | 1221.13 | 636.09 | 585.04 | 2195.13 | 284.89 | 0.00 | 0.00 | 0.00 |
November | 1553.97 | 1069.92 | 484.05 | 2432.31 | 587.05 | 0.00 | 0.00 | 0.00 |
December | 1606.77 | 1153.89 | 452.87 | 2413.75 | 767.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1018.17 | 490.67 | 527.50 | 1713.17 | 408.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 532.65 | 4.96 | 452.87 | 1106.29 | 71.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1644.39 | 1172.73 | 585.04 | 2432.31 | 870.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.18 | 280.74 | 238.44 | 689.03 | 601.44 | 0.00 | 0.00 | 0.00 |
February | 587.83 | 297.52 | 290.31 | 806.93 | 507.80 | 0.00 | 0.00 | 0.00 |
March | 579.36 | 256.47 | 322.89 | 820.63 | 439.84 | 0.00 | 0.00 | 0.00 |
April | 719.59 | 331.02 | 388.56 | 1139.68 | 293.53 | 0.00 | 0.00 | 0.00 |
May | 598.42 | 194.94 | 403.48 | 1140.37 | 92.30 | 0.00 | 0.00 | 0.00 |
June | 664.78 | 233.10 | 431.68 | 1288.86 | 81.23 | 0.00 | 0.00 | 0.00 |
July | 606.82 | 168.32 | 438.50 | 1182.43 | 53.10 | 0.00 | 0.00 | 0.00 |
August | 613.57 | 187.82 | 425.75 | 1195.93 | 74.86 | 0.00 | 0.00 | 0.00 |
September | 564.99 | 193.82 | 371.17 | 1046.54 | 100.38 | 0.00 | 0.00 | 0.00 |
October | 578.44 | 249.94 | 328.50 | 1030.90 | 188.35 | 0.00 | 0.00 | 0.00 |
November | 495.79 | 249.16 | 246.63 | 746.28 | 395.38 | 0.00 | 0.00 | 0.00 |
December | 476.91 | 253.61 | 223.29 | 666.49 | 512.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 583.47 | 240.80 | 342.67 | 980.09 | 277.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 476.91 | 168.32 | 223.29 | 666.49 | 53.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 719.59 | 331.02 | 438.50 | 1288.86 | 601.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.83 | 0.00 | 94.83 | 73.38 | 336.03 | 0.00 | 0.00 | 0.00 |
February | 111.87 | 0.00 | 111.87 | 102.43 | 274.95 | 0.00 | 0.00 | 0.00 |
March | 129.78 | 0.00 | 129.78 | 147.04 | 229.20 | 0.00 | 0.00 | 0.00 |
April | 153.17 | 0.63 | 152.54 | 223.66 | 139.41 | 0.00 | 0.00 | 0.00 |
May | 173.49 | 6.35 | 167.15 | 361.24 | 36.37 | 0.00 | 0.00 | 0.00 |
June | 197.30 | 13.66 | 183.64 | 423.99 | 32.22 | 0.00 | 0.00 | 0.00 |
July | 191.47 | 7.29 | 184.17 | 406.37 | 22.79 | 0.00 | 0.00 | 0.00 |
August | 171.46 | 1.35 | 170.11 | 363.38 | 35.77 | 0.00 | 0.00 | 0.00 |
September | 148.10 | 0.01 | 148.09 | 289.52 | 51.80 | 0.00 | 0.00 | 0.00 |
October | 128.70 | 0.00 | 128.70 | 233.45 | 98.47 | 0.00 | 0.00 | 0.00 |
November | 97.70 | 0.00 | 97.70 | 107.98 | 222.17 | 0.00 | 0.00 | 0.00 |
December | 88.15 | 0.00 | 88.15 | 76.73 | 291.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.64 | 2.45 | 138.20 | 234.88 | 146.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.15 | 0.00 | 88.15 | 73.38 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.30 | 13.66 | 184.17 | 423.99 | 336.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.83 | 0.00 | 94.83 | 73.38 | 336.05 | 0.00 | 0.00 | 0.00 |
February | 111.88 | 0.00 | 111.88 | 102.44 | 274.97 | 0.00 | 0.00 | 0.00 |
March | 129.79 | 0.00 | 129.79 | 147.05 | 229.21 | 0.00 | 0.00 | 0.00 |
April | 153.18 | 0.63 | 152.55 | 223.67 | 139.42 | 0.00 | 0.00 | 0.00 |
May | 173.50 | 6.35 | 167.16 | 361.26 | 36.38 | 0.00 | 0.00 | 0.00 |
June | 197.31 | 13.66 | 183.65 | 424.02 | 32.23 | 0.00 | 0.00 | 0.00 |
July | 191.48 | 7.29 | 184.18 | 406.40 | 22.79 | 0.00 | 0.00 | 0.00 |
August | 171.47 | 1.35 | 170.12 | 363.41 | 35.77 | 0.00 | 0.00 | 0.00 |
September | 148.11 | 0.01 | 148.10 | 289.54 | 51.80 | 0.00 | 0.00 | 0.00 |
October | 128.71 | 0.00 | 128.71 | 233.47 | 98.48 | 0.00 | 0.00 | 0.00 |
November | 97.71 | 0.00 | 97.71 | 107.99 | 222.18 | 0.00 | 0.00 | 0.00 |
December | 88.16 | 0.00 | 88.16 | 76.73 | 291.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.65 | 2.45 | 138.20 | 234.90 | 146.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.16 | 0.00 | 88.16 | 73.38 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.31 | 13.66 | 184.18 | 424.02 | 336.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 94.83 | 0.00 | 94.83 | 73.38 | 336.05 | 0.00 | 0.00 | 0.00 |
February | 111.88 | 0.00 | 111.88 | 102.44 | 274.97 | 0.00 | 0.00 | 0.00 |
March | 129.79 | 0.00 | 129.79 | 147.05 | 229.21 | 0.00 | 0.00 | 0.00 |
April | 153.18 | 0.63 | 152.55 | 223.67 | 139.42 | 0.00 | 0.00 | 0.00 |
May | 173.50 | 6.35 | 167.16 | 361.26 | 36.38 | 0.00 | 0.00 | 0.00 |
June | 197.31 | 13.66 | 183.65 | 424.02 | 32.23 | 0.00 | 0.00 | 0.00 |
July | 191.48 | 7.29 | 184.18 | 406.40 | 22.79 | 0.00 | 0.00 | 0.00 |
August | 171.47 | 1.35 | 170.12 | 363.41 | 35.77 | 0.00 | 0.00 | 0.00 |
September | 148.11 | 0.01 | 148.10 | 289.54 | 51.80 | 0.00 | 0.00 | 0.00 |
October | 128.71 | 0.00 | 128.71 | 233.47 | 98.48 | 0.00 | 0.00 | 0.00 |
November | 97.71 | 0.00 | 97.71 | 107.99 | 222.18 | 0.00 | 0.00 | 0.00 |
December | 88.16 | 0.00 | 88.16 | 76.73 | 291.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 140.65 | 2.45 | 138.20 | 234.90 | 146.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.16 | 0.00 | 88.16 | 73.38 | 22.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 197.31 | 13.66 | 184.18 | 424.02 | 336.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.54 | 239.09 | 230.45 | 568.54 | 615.66 | 0.00 | 0.00 | 0.00 |
February | 522.85 | 252.42 | 270.43 | 673.91 | 507.66 | 0.00 | 0.00 | 0.00 |
March | 615.04 | 296.62 | 318.42 | 858.11 | 430.68 | 0.00 | 0.00 | 0.00 |
April | 674.93 | 305.25 | 369.68 | 1063.37 | 275.04 | 0.00 | 0.00 | 0.00 |
May | 695.68 | 301.66 | 394.02 | 1302.32 | 77.13 | 0.00 | 0.00 | 0.00 |
June | 705.53 | 279.79 | 425.74 | 1363.52 | 67.04 | 0.00 | 0.00 | 0.00 |
July | 680.23 | 248.93 | 431.31 | 1311.53 | 48.48 | 0.00 | 0.00 | 0.00 |
August | 626.82 | 215.50 | 411.31 | 1204.97 | 74.07 | 0.00 | 0.00 | 0.00 |
September | 555.24 | 190.89 | 364.35 | 1017.84 | 105.62 | 0.00 | 0.00 | 0.00 |
October | 548.69 | 231.55 | 317.15 | 957.55 | 191.68 | 0.00 | 0.00 | 0.00 |
November | 485.79 | 247.82 | 237.97 | 681.41 | 413.41 | 0.00 | 0.00 | 0.00 |
December | 382.48 | 173.26 | 209.23 | 480.93 | 545.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 580.43 | 248.45 | 331.98 | 958.51 | 278.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.48 | 173.26 | 209.23 | 480.93 | 48.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 705.53 | 305.25 | 431.31 | 1363.52 | 615.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.57 | 9.45 | 9.11 | 22.48 | 24.34 | 0.00 | 0.00 | 0.00 |
February | 20.67 | 9.98 | 10.69 | 26.65 | 20.07 | 0.00 | 0.00 | 0.00 |
March | 24.32 | 11.73 | 12.59 | 33.93 | 17.03 | 0.00 | 0.00 | 0.00 |
April | 26.69 | 12.07 | 14.62 | 42.04 | 10.87 | 0.00 | 0.00 | 0.00 |
May | 27.51 | 11.93 | 15.58 | 51.49 | 3.05 | 0.00 | 0.00 | 0.00 |
June | 27.90 | 11.06 | 16.83 | 53.91 | 2.65 | 0.00 | 0.00 | 0.00 |
July | 26.90 | 9.84 | 17.05 | 51.86 | 1.92 | 0.00 | 0.00 | 0.00 |
August | 24.78 | 8.52 | 16.26 | 47.64 | 2.93 | 0.00 | 0.00 | 0.00 |
September | 21.95 | 7.55 | 14.41 | 40.24 | 4.18 | 0.00 | 0.00 | 0.00 |
October | 21.69 | 9.16 | 12.54 | 37.86 | 7.58 | 0.00 | 0.00 | 0.00 |
November | 19.21 | 9.80 | 9.41 | 26.94 | 16.35 | 0.00 | 0.00 | 0.00 |
December | 15.12 | 6.85 | 8.27 | 19.02 | 21.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.95 | 9.82 | 13.13 | 37.90 | 11.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 15.12 | 6.85 | 8.27 | 19.02 | 1.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.90 | 12.07 | 17.05 | 53.91 | 24.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 548.15 | 390.92 | 157.22 | 795.82 | 325.94 | 0.00 | 0.00 | 0.00 |
February | 497.14 | 321.79 | 175.35 | 740.19 | 273.88 | 0.00 | 0.00 | 0.00 |
March | 317.38 | 143.24 | 174.15 | 492.00 | 230.31 | 0.00 | 0.00 | 0.00 |
April | 235.24 | 55.12 | 180.12 | 402.66 | 146.87 | 0.00 | 0.00 | 0.00 |
May | 179.74 | 7.64 | 172.10 | 376.57 | 38.06 | 0.00 | 0.00 | 0.00 |
June | 177.55 | 1.65 | 175.90 | 381.96 | 33.15 | 0.00 | 0.00 | 0.00 |
July | 185.87 | 3.42 | 182.45 | 395.09 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 218.67 | 26.25 | 192.42 | 462.04 | 38.77 | 0.00 | 0.00 | 0.00 |
September | 262.36 | 69.14 | 193.22 | 513.12 | 57.75 | 0.00 | 0.00 | 0.00 |
October | 407.06 | 212.04 | 195.02 | 731.79 | 108.67 | 0.00 | 0.00 | 0.00 |
November | 518.01 | 356.65 | 161.35 | 808.69 | 226.05 | 0.00 | 0.00 | 0.00 |
December | 535.61 | 384.64 | 150.96 | 804.49 | 290.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 339.40 | 163.56 | 175.84 | 574.55 | 148.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 177.55 | 1.65 | 150.96 | 376.57 | 22.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 548.15 | 390.92 | 195.02 | 808.69 | 325.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 548.15 | 390.92 | 157.22 | 795.82 | 325.94 | 0.00 | 0.00 | 0.00 |
February | 497.14 | 321.79 | 175.35 | 740.19 | 273.88 | 0.00 | 0.00 | 0.00 |
March | 317.38 | 143.24 | 174.15 | 492.00 | 230.31 | 0.00 | 0.00 | 0.00 |
April | 235.24 | 55.12 | 180.12 | 402.66 | 146.87 | 0.00 | 0.00 | 0.00 |
May | 179.74 | 7.64 | 172.10 | 376.57 | 38.06 | 0.00 | 0.00 | 0.00 |
June | 177.55 | 1.65 | 175.90 | 381.96 | 33.15 | 0.00 | 0.00 | 0.00 |
July | 185.87 | 3.42 | 182.45 | 395.09 | 22.67 | 0.00 | 0.00 | 0.00 |
August | 218.67 | 26.25 | 192.42 | 462.04 | 38.77 | 0.00 | 0.00 | 0.00 |
September | 262.36 | 69.14 | 193.22 | 513.12 | 57.75 | 0.00 | 0.00 | 0.00 |
October | 407.06 | 212.04 | 195.02 | 731.79 | 108.67 | 0.00 | 0.00 | 0.00 |
November | 518.01 | 356.65 | 161.35 | 808.69 | 226.05 | 0.00 | 0.00 | 0.00 |
December | 535.61 | 384.64 | 150.96 | 804.49 | 290.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 339.40 | 163.56 | 175.84 | 574.55 | 148.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 177.55 | 1.65 | 150.96 | 376.57 | 22.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 548.15 | 390.92 | 195.02 | 808.69 | 325.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 548.11 | 390.90 | 157.21 | 795.77 | 325.92 | 0.00 | 0.00 | 0.00 |
February | 497.11 | 321.77 | 175.34 | 740.15 | 273.87 | 0.00 | 0.00 | 0.00 |
March | 317.36 | 143.23 | 174.14 | 491.97 | 230.30 | 0.00 | 0.00 | 0.00 |
April | 235.23 | 55.12 | 180.11 | 402.64 | 146.86 | 0.00 | 0.00 | 0.00 |
May | 179.73 | 7.64 | 172.09 | 376.55 | 38.06 | 0.00 | 0.00 | 0.00 |
June | 177.54 | 1.65 | 175.89 | 381.94 | 33.15 | 0.00 | 0.00 | 0.00 |
July | 185.86 | 3.42 | 182.44 | 395.07 | 22.66 | 0.00 | 0.00 | 0.00 |
August | 218.65 | 26.24 | 192.41 | 462.01 | 38.77 | 0.00 | 0.00 | 0.00 |
September | 262.35 | 69.14 | 193.21 | 513.09 | 57.74 | 0.00 | 0.00 | 0.00 |
October | 407.03 | 212.02 | 195.01 | 731.74 | 108.66 | 0.00 | 0.00 | 0.00 |
November | 517.97 | 356.63 | 161.34 | 808.63 | 226.03 | 0.00 | 0.00 | 0.00 |
December | 535.57 | 384.62 | 150.95 | 804.44 | 290.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 339.38 | 163.55 | 175.83 | 574.51 | 148.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 177.54 | 1.65 | 150.95 | 376.55 | 22.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 548.11 | 390.90 | 195.01 | 808.63 | 325.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 499.43 | 270.06 | 229.37 | 653.72 | 648.29 | 0.00 | 0.00 | 0.00 |
February | 565.47 | 286.20 | 279.26 | 772.87 | 538.92 | 0.00 | 0.00 | 0.00 |
March | 557.32 | 246.71 | 310.61 | 793.56 | 453.67 | 0.00 | 0.00 | 0.00 |
April | 692.21 | 318.43 | 373.78 | 1107.89 | 291.70 | 0.00 | 0.00 | 0.00 |
May | 575.66 | 187.52 | 388.14 | 1111.22 | 83.19 | 0.00 | 0.00 | 0.00 |
June | 639.49 | 224.23 | 415.25 | 1253.92 | 74.71 | 0.00 | 0.00 | 0.00 |
July | 583.73 | 161.92 | 421.82 | 1147.34 | 52.35 | 0.00 | 0.00 | 0.00 |
August | 590.23 | 180.68 | 409.55 | 1153.23 | 80.21 | 0.00 | 0.00 | 0.00 |
September | 543.50 | 186.45 | 357.05 | 1006.47 | 112.84 | 0.00 | 0.00 | 0.00 |
October | 556.43 | 240.43 | 316.00 | 988.65 | 205.70 | 0.00 | 0.00 | 0.00 |
November | 476.93 | 239.68 | 237.24 | 704.04 | 439.88 | 0.00 | 0.00 | 0.00 |
December | 458.76 | 243.96 | 214.80 | 629.08 | 564.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 561.27 | 231.64 | 329.64 | 944.08 | 294.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.76 | 161.92 | 214.80 | 629.08 | 52.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 692.21 | 318.43 | 421.82 | 1253.92 | 648.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 19.75 | 10.68 | 9.07 | 25.85 | 25.63 | 0.00 | 0.00 | 0.00 |
February | 22.36 | 11.32 | 11.04 | 30.56 | 21.31 | 0.00 | 0.00 | 0.00 |
March | 22.04 | 9.75 | 12.28 | 31.38 | 17.94 | 0.00 | 0.00 | 0.00 |
April | 27.37 | 12.59 | 14.78 | 43.80 | 11.53 | 0.00 | 0.00 | 0.00 |
May | 22.76 | 7.41 | 15.35 | 43.94 | 3.29 | 0.00 | 0.00 | 0.00 |
June | 25.28 | 8.87 | 16.42 | 49.58 | 2.95 | 0.00 | 0.00 | 0.00 |
July | 23.08 | 6.40 | 16.68 | 45.36 | 2.07 | 0.00 | 0.00 | 0.00 |
August | 23.34 | 7.14 | 16.19 | 45.60 | 3.17 | 0.00 | 0.00 | 0.00 |
September | 21.49 | 7.37 | 14.12 | 39.79 | 4.46 | 0.00 | 0.00 | 0.00 |
October | 22.00 | 9.51 | 12.49 | 39.09 | 8.13 | 0.00 | 0.00 | 0.00 |
November | 18.86 | 9.48 | 9.38 | 27.84 | 17.39 | 0.00 | 0.00 | 0.00 |
December | 18.14 | 9.65 | 8.49 | 24.87 | 22.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.19 | 9.16 | 13.03 | 37.33 | 11.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 18.14 | 6.40 | 8.49 | 24.87 | 2.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.37 | 12.59 | 16.68 | 49.58 | 25.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.49 | 0.00 | 284.49 | 219.18 | 995.47 | 0.00 | 0.00 | 0.00 |
February | 335.63 | 0.00 | 335.63 | 296.96 | 833.36 | 0.00 | 0.00 | 0.00 |
March | 389.36 | 0.00 | 389.36 | 421.90 | 711.26 | 0.00 | 0.00 | 0.00 |
April | 459.53 | 1.89 | 457.64 | 646.42 | 447.52 | 0.00 | 0.00 | 0.00 |
May | 520.51 | 19.04 | 501.47 | 1065.70 | 126.31 | 0.00 | 0.00 | 0.00 |
June | 591.93 | 40.99 | 550.94 | 1258.30 | 108.66 | 0.00 | 0.00 | 0.00 |
July | 574.43 | 21.88 | 552.54 | 1211.50 | 73.44 | 0.00 | 0.00 | 0.00 |
August | 514.41 | 4.05 | 510.36 | 1093.95 | 103.21 | 0.00 | 0.00 | 0.00 |
September | 444.33 | 0.03 | 444.30 | 871.31 | 147.54 | 0.00 | 0.00 | 0.00 |
October | 386.12 | 0.00 | 386.12 | 704.34 | 285.33 | 0.00 | 0.00 | 0.00 |
November | 293.12 | 0.00 | 293.12 | 328.98 | 644.70 | 0.00 | 0.00 | 0.00 |
December | 264.47 | 0.00 | 264.47 | 233.57 | 851.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 421.95 | 7.35 | 414.61 | 698.41 | 442.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 264.47 | 0.00 | 264.47 | 219.18 | 73.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 591.93 | 40.99 | 552.54 | 1258.30 | 995.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 488.11 | 248.55 | 239.56 | 592.95 | 611.92 | 0.00 | 0.00 | 0.00 |
February | 543.52 | 262.40 | 281.13 | 696.38 | 515.35 | 0.00 | 0.00 | 0.00 |
March | 639.36 | 308.35 | 331.02 | 882.02 | 444.69 | 0.00 | 0.00 | 0.00 |
April | 701.63 | 317.33 | 384.30 | 1092.22 | 290.82 | 0.00 | 0.00 | 0.00 |
May | 723.19 | 313.59 | 409.60 | 1343.06 | 84.52 | 0.00 | 0.00 | 0.00 |
June | 733.43 | 290.86 | 442.58 | 1409.19 | 72.44 | 0.00 | 0.00 | 0.00 |
July | 707.14 | 258.77 | 448.36 | 1360.54 | 48.24 | 0.00 | 0.00 | 0.00 |
August | 651.60 | 224.03 | 427.58 | 1255.42 | 68.95 | 0.00 | 0.00 | 0.00 |
September | 577.20 | 198.44 | 378.76 | 1060.55 | 97.18 | 0.00 | 0.00 | 0.00 |
October | 570.39 | 240.70 | 329.69 | 997.49 | 184.15 | 0.00 | 0.00 | 0.00 |
November | 505.00 | 257.62 | 247.38 | 712.84 | 401.72 | 0.00 | 0.00 | 0.00 |
December | 397.61 | 180.11 | 217.50 | 503.78 | 536.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 603.39 | 258.28 | 345.11 | 993.80 | 278.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 397.61 | 180.11 | 217.50 | 503.78 | 48.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 733.43 | 317.33 | 448.36 | 1409.19 | 611.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1644.39 | 1172.73 | 471.66 | 2367.82 | 932.95 | 0.00 | 0.00 | 0.00 |
February | 1491.37 | 965.33 | 526.03 | 2196.21 | 798.39 | 0.00 | 0.00 | 0.00 |
March | 952.12 | 429.69 | 522.43 | 1444.86 | 703.89 | 0.00 | 0.00 | 0.00 |
April | 705.70 | 165.36 | 540.34 | 1181.96 | 463.93 | 0.00 | 0.00 | 0.00 |
May | 539.21 | 22.92 | 516.29 | 1116.10 | 129.92 | 0.00 | 0.00 | 0.00 |
June | 532.65 | 4.96 | 527.68 | 1136.93 | 111.81 | 0.00 | 0.00 | 0.00 |
July | 557.59 | 10.25 | 547.34 | 1182.89 | 71.57 | 0.00 | 0.00 | 0.00 |
August | 655.98 | 78.74 | 577.24 | 1394.91 | 107.98 | 0.00 | 0.00 | 0.00 |
September | 787.06 | 207.42 | 579.64 | 1543.36 | 156.79 | 0.00 | 0.00 | 0.00 |
October | 1221.13 | 636.09 | 585.04 | 2200.01 | 299.05 | 0.00 | 0.00 | 0.00 |
November | 1553.97 | 1069.92 | 484.05 | 2422.99 | 629.11 | 0.00 | 0.00 | 0.00 |
December | 1606.77 | 1153.89 | 452.87 | 2401.93 | 825.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1018.17 | 490.67 | 527.50 | 1713.46 | 433.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 532.65 | 4.96 | 452.87 | 1116.10 | 71.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1644.39 | 1172.73 | 585.04 | 2422.99 | 932.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 519.18 | 280.74 | 238.44 | 679.99 | 647.85 | 0.00 | 0.00 | 0.00 |
February | 587.83 | 297.52 | 290.31 | 798.04 | 548.77 | 0.00 | 0.00 | 0.00 |
March | 579.36 | 256.47 | 322.89 | 815.24 | 470.84 | 0.00 | 0.00 | 0.00 |
April | 719.59 | 331.02 | 388.56 | 1138.25 | 309.53 | 0.00 | 0.00 | 0.00 |
May | 598.42 | 194.94 | 403.48 | 1145.85 | 93.27 | 0.00 | 0.00 | 0.00 |
June | 664.78 | 233.10 | 431.68 | 1296.14 | 81.41 | 0.00 | 0.00 | 0.00 |
July | 606.82 | 168.32 | 438.50 | 1189.95 | 53.99 | 0.00 | 0.00 | 0.00 |
August | 613.57 | 187.82 | 425.75 | 1202.06 | 75.91 | 0.00 | 0.00 | 0.00 |
September | 564.99 | 193.82 | 371.17 | 1049.70 | 105.54 | 0.00 | 0.00 | 0.00 |
October | 578.44 | 249.94 | 328.50 | 1031.22 | 199.52 | 0.00 | 0.00 | 0.00 |
November | 495.79 | 249.16 | 246.63 | 737.56 | 429.74 | 0.00 | 0.00 | 0.00 |
December | 476.91 | 253.61 | 223.29 | 657.40 | 555.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 583.47 | 240.80 | 342.67 | 979.09 | 296.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 476.91 | 168.32 | 223.29 | 657.40 | 53.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 719.59 | 331.02 | 438.50 | 1296.14 | 647.85 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761979E+09 | 0.00 | 0.761979E+09 | 0.622264E+09 | 0.246896E+10 |
February | 0.811956E+09 | 0.00 | 0.811956E+09 | 0.749139E+09 | 0.186028E+10 |
March | 0.104286E+10 | 0.00 | 0.104286E+10 | 0.115417E+10 | 0.177693E+10 |
April | 0.119110E+10 | 4888705.04 | 0.118621E+10 | 0.168208E+10 | 0.110033E+10 |
May | 0.139412E+10 | 50993845.67 | 0.134313E+10 | 0.282847E+10 | 0.337066E+09 |
June | 0.153427E+10 | 0.106237E+09 | 0.142804E+10 | 0.322925E+10 | 0.283100E+09 |
July | 0.153854E+10 | 58615712.59 | 0.147993E+10 | 0.320955E+10 | 0.196794E+09 |
August | 0.137779E+10 | 10836527.32 | 0.136696E+10 | 0.290404E+10 | 0.273440E+09 |
September | 0.115171E+10 | 88704.64 | 0.115163E+10 | 0.224061E+10 | 0.364918E+09 |
October | 0.103418E+10 | 0.00 | 0.103418E+10 | 0.188396E+10 | 0.718834E+09 |
November | 0.759779E+09 | 0.00 | 0.759779E+09 | 0.887746E+09 | 0.152952E+10 |
December | 0.708346E+09 | 0.00 | 0.708346E+09 | 0.660932E+09 | 0.209569E+10 |
Annual Sum or Average | 0.133067E+11 | 0.231660E+09 | 0.130750E+11 | 0.220522E+11 | 0.130059E+11 |
Minimum of Months | 0.708346E+09 | 0.00 | 0.708346E+09 | 0.622264E+09 | 0.196794E+09 |
Maximum of Months | 0.153854E+10 | 0.106237E+09 | 0.147993E+10 | 0.322925E+10 | 0.246896E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130735E+10 | 0.665704E+09 | 0.641643E+09 | 0.162455E+10 | 0.152662E+10 |
February | 0.131489E+10 | 0.634794E+09 | 0.680100E+09 | 0.171184E+10 | 0.115939E+10 |
March | 0.171247E+10 | 0.825875E+09 | 0.886595E+09 | 0.237604E+10 | 0.112075E+10 |
April | 0.181862E+10 | 0.822507E+09 | 0.996108E+09 | 0.283000E+10 | 0.721423E+09 |
May | 0.193699E+10 | 0.839912E+09 | 0.109707E+10 | 0.357587E+10 | 0.225432E+09 |
June | 0.190106E+10 | 0.753906E+09 | 0.114716E+10 | 0.362863E+10 | 0.189042E+09 |
July | 0.189399E+10 | 0.693097E+09 | 0.120089E+10 | 0.361849E+10 | 0.128671E+09 |
August | 0.174525E+10 | 0.600030E+09 | 0.114522E+10 | 0.334242E+10 | 0.183031E+09 |
September | 0.149610E+10 | 0.514354E+09 | 0.981751E+09 | 0.273461E+10 | 0.240945E+09 |
October | 0.152774E+10 | 0.644700E+09 | 0.883041E+09 | 0.266576E+10 | 0.467081E+09 |
November | 0.130896E+10 | 0.667751E+09 | 0.641211E+09 | 0.187178E+10 | 0.965347E+09 |
December | 0.106496E+10 | 0.482400E+09 | 0.582556E+09 | 0.137832E+10 | 0.133202E+10 |
Annual Sum or Average | 0.190284E+11 | 0.814503E+10 | 0.108834E+11 | 0.313583E+11 | 0.825975E+10 |
Minimum of Months | 0.106496E+10 | 0.482400E+09 | 0.582556E+09 | 0.137832E+10 | 0.128671E+09 |
Maximum of Months | 0.193699E+10 | 0.839912E+09 | 0.120089E+10 | 0.362863E+10 | 0.152662E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.440433E+10 | 0.314104E+10 | 0.126328E+10 | 0.638135E+10 | 0.233139E+10 |
February | 0.360791E+10 | 0.233534E+10 | 0.127258E+10 | 0.534567E+10 | 0.180000E+10 |
March | 0.255016E+10 | 0.115089E+10 | 0.139927E+10 | 0.388811E+10 | 0.176970E+10 |
April | 0.182918E+10 | 0.428620E+09 | 0.140056E+10 | 0.306292E+10 | 0.114439E+10 |
May | 0.144421E+10 | 61376736.89 | 0.138284E+10 | 0.296310E+10 | 0.346007E+09 |
June | 0.138062E+10 | 12868600.70 | 0.136775E+10 | 0.291581E+10 | 0.291364E+09 |
July | 0.149346E+10 | 27449430.67 | 0.146601E+10 | 0.313301E+10 | 0.191264E+09 |
August | 0.175697E+10 | 0.210889E+09 | 0.154608E+10 | 0.370771E+10 | 0.286170E+09 |
September | 0.204007E+10 | 0.537642E+09 | 0.150242E+10 | 0.397979E+10 | 0.389615E+09 |
October | 0.327068E+10 | 0.170371E+10 | 0.156697E+10 | 0.587944E+10 | 0.763038E+09 |
November | 0.402789E+10 | 0.277324E+10 | 0.125465E+10 | 0.630455E+10 | 0.152164E+10 |
December | 0.430356E+10 | 0.309058E+10 | 0.121298E+10 | 0.646498E+10 | 0.205572E+10 |
Annual Sum or Average | 0.321090E+11 | 0.154737E+11 | 0.166354E+11 | 0.540265E+11 | 0.128903E+11 |
Minimum of Months | 0.138062E+10 | 12868600.70 | 0.121298E+10 | 0.291581E+10 | 0.191264E+09 |
Maximum of Months | 0.440433E+10 | 0.314104E+10 | 0.156697E+10 | 0.646498E+10 | 0.233139E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139057E+10 | 0.751943E+09 | 0.638629E+09 | 0.184549E+10 | 0.161089E+10 |
February | 0.142207E+10 | 0.719764E+09 | 0.702310E+09 | 0.195212E+10 | 0.122846E+10 |
March | 0.155177E+10 | 0.686928E+09 | 0.864841E+09 | 0.219799E+10 | 0.117807E+10 |
April | 0.186517E+10 | 0.858009E+09 | 0.100716E+10 | 0.295404E+10 | 0.760820E+09 |
May | 0.160281E+10 | 0.522117E+09 | 0.108069E+10 | 0.305436E+10 | 0.247229E+09 |
June | 0.172310E+10 | 0.604199E+09 | 0.111890E+10 | 0.334071E+10 | 0.210545E+09 |
July | 0.162530E+10 | 0.450831E+09 | 0.117447E+10 | 0.316701E+10 | 0.142225E+09 |
August | 0.164338E+10 | 0.503060E+09 | 0.114032E+10 | 0.320318E+10 | 0.200510E+09 |
September | 0.146446E+10 | 0.502379E+09 | 0.962082E+09 | 0.271263E+10 | 0.260190E+09 |
October | 0.154928E+10 | 0.669427E+09 | 0.879857E+09 | 0.276117E+10 | 0.504474E+09 |
November | 0.128508E+10 | 0.645830E+09 | 0.639254E+09 | 0.193436E+10 | 0.102484E+10 |
December | 0.127734E+10 | 0.679273E+09 | 0.598072E+09 | 0.178514E+10 | 0.137389E+10 |
Annual Sum or Average | 0.184003E+11 | 0.759376E+10 | 0.108066E+11 | 0.309082E+11 | 0.874214E+10 |
Minimum of Months | 0.127734E+10 | 0.450831E+09 | 0.598072E+09 | 0.178514E+10 | 0.142225E+09 |
Maximum of Months | 0.186517E+10 | 0.858009E+09 | 0.117447E+10 | 0.334071E+10 | 0.161089E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253981E+09 | 0.00 | 0.253981E+09 | 0.196530E+09 | 0.900029E+09 |
February | 0.270639E+09 | 0.00 | 0.270639E+09 | 0.247804E+09 | 0.665167E+09 |
March | 0.347604E+09 | 0.00 | 0.347604E+09 | 0.393829E+09 | 0.613889E+09 |
April | 0.397016E+09 | 1629491.25 | 0.395386E+09 | 0.579722E+09 | 0.361357E+09 |
May | 0.464686E+09 | 16997144.35 | 0.447689E+09 | 0.967537E+09 | 97424615.67 |
June | 0.511400E+09 | 35410494.83 | 0.475990E+09 | 0.109898E+10 | 83522934.27 |
July | 0.512824E+09 | 19537646.45 | 0.493286E+09 | 0.108843E+10 | 61037232.63 |
August | 0.459243E+09 | 3612004.87 | 0.455631E+09 | 0.973288E+09 | 95803885.56 |
September | 0.383886E+09 | 29566.81 | 0.383857E+09 | 0.750444E+09 | 0.134265E+09 |
October | 0.344709E+09 | 0.00 | 0.344709E+09 | 0.625276E+09 | 0.263741E+09 |
November | 0.253248E+09 | 0.00 | 0.253248E+09 | 0.279892E+09 | 0.575862E+09 |
December | 0.236104E+09 | 0.00 | 0.236104E+09 | 0.205509E+09 | 0.781843E+09 |
Annual Sum or Average | 0.443534E+10 | 77216348.57 | 0.435812E+10 | 0.740724E+10 | 0.463394E+10 |
Minimum of Months | 0.236104E+09 | 0.00 | 0.236104E+09 | 0.196530E+09 | 61037232.63 |
Maximum of Months | 0.512824E+09 | 35410494.83 | 0.493286E+09 | 0.109898E+10 | 0.900029E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253997E+09 | 0.00 | 0.253997E+09 | 0.196542E+09 | 0.900086E+09 |
February | 0.270656E+09 | 0.00 | 0.270656E+09 | 0.247820E+09 | 0.665209E+09 |
March | 0.347626E+09 | 0.00 | 0.347626E+09 | 0.393854E+09 | 0.613928E+09 |
April | 0.397041E+09 | 1629594.23 | 0.395411E+09 | 0.579759E+09 | 0.361380E+09 |
May | 0.464715E+09 | 16998218.54 | 0.447717E+09 | 0.967599E+09 | 97430772.75 |
June | 0.511433E+09 | 35412732.72 | 0.476020E+09 | 0.109905E+10 | 83528212.78 |
July | 0.512856E+09 | 19538881.20 | 0.493317E+09 | 0.108850E+10 | 61041090.08 |
August | 0.459272E+09 | 3612233.15 | 0.455660E+09 | 0.973350E+09 | 95809940.21 |
September | 0.383911E+09 | 29568.68 | 0.383881E+09 | 0.750491E+09 | 0.134274E+09 |
October | 0.344731E+09 | 0.00 | 0.344731E+09 | 0.625315E+09 | 0.263758E+09 |
November | 0.253264E+09 | 0.00 | 0.253264E+09 | 0.279910E+09 | 0.575899E+09 |
December | 0.236119E+09 | 0.00 | 0.236119E+09 | 0.205522E+09 | 0.781892E+09 |
Annual Sum or Average | 0.443562E+10 | 77221228.52 | 0.435840E+10 | 0.740771E+10 | 0.463423E+10 |
Minimum of Months | 0.236119E+09 | 0.00 | 0.236119E+09 | 0.196542E+09 | 61041090.08 |
Maximum of Months | 0.512856E+09 | 35412732.72 | 0.493317E+09 | 0.109905E+10 | 0.900086E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253997E+09 | 0.00 | 0.253997E+09 | 0.196542E+09 | 0.900086E+09 |
February | 0.270656E+09 | 0.00 | 0.270656E+09 | 0.247820E+09 | 0.665209E+09 |
March | 0.347626E+09 | 0.00 | 0.347626E+09 | 0.393854E+09 | 0.613928E+09 |
April | 0.397041E+09 | 1629594.23 | 0.395411E+09 | 0.579759E+09 | 0.361380E+09 |
May | 0.464715E+09 | 16998218.54 | 0.447717E+09 | 0.967599E+09 | 97430772.75 |
June | 0.511433E+09 | 35412732.72 | 0.476020E+09 | 0.109905E+10 | 83528212.78 |
July | 0.512856E+09 | 19538881.20 | 0.493317E+09 | 0.108850E+10 | 61041090.08 |
August | 0.459272E+09 | 3612233.15 | 0.455660E+09 | 0.973350E+09 | 95809940.21 |
September | 0.383911E+09 | 29568.68 | 0.383881E+09 | 0.750491E+09 | 0.134274E+09 |
October | 0.344731E+09 | 0.00 | 0.344731E+09 | 0.625315E+09 | 0.263758E+09 |
November | 0.253264E+09 | 0.00 | 0.253264E+09 | 0.279910E+09 | 0.575899E+09 |
December | 0.236119E+09 | 0.00 | 0.236119E+09 | 0.205522E+09 | 0.781892E+09 |
Annual Sum or Average | 0.443562E+10 | 77221228.52 | 0.435840E+10 | 0.740771E+10 | 0.463423E+10 |
Minimum of Months | 0.236119E+09 | 0.00 | 0.236119E+09 | 0.196542E+09 | 61041090.08 |
Maximum of Months | 0.512856E+09 | 35412732.72 | 0.493317E+09 | 0.109905E+10 | 0.900086E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125761E+10 | 0.640378E+09 | 0.617235E+09 | 0.152279E+10 | 0.164898E+10 |
February | 0.126487E+10 | 0.610643E+09 | 0.654228E+09 | 0.163033E+10 | 0.122813E+10 |
March | 0.164732E+10 | 0.794455E+09 | 0.852868E+09 | 0.229837E+10 | 0.115354E+10 |
April | 0.174943E+10 | 0.791215E+09 | 0.958216E+09 | 0.275625E+10 | 0.712911E+09 |
May | 0.186330E+10 | 0.807957E+09 | 0.105534E+10 | 0.348814E+10 | 0.206578E+09 |
June | 0.182874E+10 | 0.725224E+09 | 0.110352E+10 | 0.353424E+10 | 0.173776E+09 |
July | 0.182194E+10 | 0.666728E+09 | 0.115521E+10 | 0.351279E+10 | 0.129841E+09 |
August | 0.167886E+10 | 0.577202E+09 | 0.110166E+10 | 0.322739E+10 | 0.198386E+09 |
September | 0.143919E+10 | 0.494786E+09 | 0.944404E+09 | 0.263824E+10 | 0.273761E+09 |
October | 0.146962E+10 | 0.620173E+09 | 0.849450E+09 | 0.256470E+10 | 0.513398E+09 |
November | 0.125917E+10 | 0.642347E+09 | 0.616819E+09 | 0.176621E+10 | 0.107156E+10 |
December | 0.102444E+10 | 0.464047E+09 | 0.560395E+09 | 0.128814E+10 | 0.146047E+10 |
Annual Sum or Average | 0.183045E+11 | 0.783515E+10 | 0.104693E+11 | 0.302276E+11 | 0.877133E+10 |
Minimum of Months | 0.102444E+10 | 0.464047E+09 | 0.560395E+09 | 0.128814E+10 | 0.129841E+09 |
Maximum of Months | 0.186330E+10 | 0.807957E+09 | 0.115521E+10 | 0.353424E+10 | 0.164898E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 49724850.57 | 25319950.09 | 24404900.48 | 60209715.47 | 65199131.28 |
February | 50011880.55 | 24144275.60 | 25867604.96 | 64461633.92 | 48559042.33 |
March | 65133652.97 | 31412021.60 | 33721631.37 | 90875647.54 | 45610040.18 |
April | 69170926.76 | 31283934.76 | 37886992.00 | 0.108980E+09 | 28187875.54 |
May | 73673144.82 | 31945900.23 | 41727244.59 | 0.137918E+09 | 8167924.00 |
June | 72306781.48 | 28674702.02 | 43632079.46 | 0.139741E+09 | 6870936.04 |
July | 72037862.60 | 26361828.29 | 45676034.31 | 0.138893E+09 | 5133784.04 |
August | 66380665.20 | 22822050.68 | 43558614.53 | 0.127608E+09 | 7843993.67 |
September | 56904259.66 | 19563386.03 | 37340873.63 | 0.104314E+09 | 10824269.54 |
October | 58107539.85 | 24521062.88 | 33586476.97 | 0.101406E+09 | 20299282.12 |
November | 49786275.52 | 25397803.41 | 24388472.11 | 69834188.88 | 42368576.87 |
December | 40505509.57 | 18347996.93 | 22157512.64 | 50931737.54 | 57745511.73 |
Annual Sum or Average | 0.723743E+09 | 0.309795E+09 | 0.413948E+09 | 0.119517E+10 | 0.346810E+09 |
Minimum of Months | 40505509.57 | 18347996.93 | 22157512.64 | 50931737.54 | 5133784.04 |
Maximum of Months | 73673144.82 | 31945900.23 | 45676034.31 | 0.139741E+09 | 65199131.28 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146815E+10 | 0.104705E+10 | 0.421106E+09 | 0.213153E+10 | 0.873001E+09 |
February | 0.120268E+10 | 0.778472E+09 | 0.424204E+09 | 0.179068E+10 | 0.662576E+09 |
March | 0.850080E+09 | 0.383642E+09 | 0.466438E+09 | 0.131778E+10 | 0.616868E+09 |
April | 0.609744E+09 | 0.142878E+09 | 0.466866E+09 | 0.104370E+10 | 0.380692E+09 |
May | 0.481418E+09 | 20459581.48 | 0.460958E+09 | 0.100861E+10 | 0.101940E+09 |
June | 0.460218E+09 | 4289673.87 | 0.455928E+09 | 0.990040E+09 | 85918004.07 |
July | 0.497833E+09 | 9150109.50 | 0.488682E+09 | 0.105822E+10 | 60707892.66 |
August | 0.585674E+09 | 70298483.53 | 0.515375E+09 | 0.123754E+10 | 0.103838E+09 |
September | 0.680042E+09 | 0.179220E+09 | 0.500822E+09 | 0.133001E+10 | 0.149675E+09 |
October | 0.109026E+10 | 0.567923E+09 | 0.522338E+09 | 0.196002E+10 | 0.291062E+09 |
November | 0.134267E+10 | 0.924443E+09 | 0.418228E+09 | 0.209611E+10 | 0.585910E+09 |
December | 0.143457E+10 | 0.103023E+10 | 0.404337E+09 | 0.215475E+10 | 0.779036E+09 |
Annual Sum or Average | 0.107033E+11 | 0.515805E+10 | 0.554528E+10 | 0.181190E+11 | 0.469122E+10 |
Minimum of Months | 0.460218E+09 | 4289673.87 | 0.404337E+09 | 0.990040E+09 | 60707892.66 |
Maximum of Months | 0.146815E+10 | 0.104705E+10 | 0.522338E+09 | 0.215475E+10 | 0.873001E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146815E+10 | 0.104705E+10 | 0.421106E+09 | 0.213153E+10 | 0.873001E+09 |
February | 0.120268E+10 | 0.778472E+09 | 0.424204E+09 | 0.179068E+10 | 0.662576E+09 |
March | 0.850080E+09 | 0.383642E+09 | 0.466438E+09 | 0.131778E+10 | 0.616868E+09 |
April | 0.609744E+09 | 0.142878E+09 | 0.466866E+09 | 0.104370E+10 | 0.380692E+09 |
May | 0.481418E+09 | 20459581.48 | 0.460958E+09 | 0.100861E+10 | 0.101940E+09 |
June | 0.460218E+09 | 4289673.87 | 0.455928E+09 | 0.990040E+09 | 85918004.07 |
July | 0.497833E+09 | 9150109.50 | 0.488682E+09 | 0.105822E+10 | 60707892.66 |
August | 0.585674E+09 | 70298483.53 | 0.515375E+09 | 0.123754E+10 | 0.103838E+09 |
September | 0.680042E+09 | 0.179220E+09 | 0.500822E+09 | 0.133001E+10 | 0.149675E+09 |
October | 0.109026E+10 | 0.567923E+09 | 0.522338E+09 | 0.196002E+10 | 0.291062E+09 |
November | 0.134267E+10 | 0.924443E+09 | 0.418228E+09 | 0.209611E+10 | 0.585910E+09 |
December | 0.143457E+10 | 0.103023E+10 | 0.404337E+09 | 0.215475E+10 | 0.779036E+09 |
Annual Sum or Average | 0.107033E+11 | 0.515805E+10 | 0.554528E+10 | 0.181190E+11 | 0.469122E+10 |
Minimum of Months | 0.460218E+09 | 4289673.87 | 0.404337E+09 | 0.990040E+09 | 60707892.66 |
Maximum of Months | 0.146815E+10 | 0.104705E+10 | 0.522338E+09 | 0.215475E+10 | 0.873001E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.146806E+10 | 0.104698E+10 | 0.421079E+09 | 0.213140E+10 | 0.872945E+09 |
February | 0.120260E+10 | 0.778422E+09 | 0.424177E+09 | 0.179056E+10 | 0.662534E+09 |
March | 0.850026E+09 | 0.383618E+09 | 0.466408E+09 | 0.131770E+10 | 0.616829E+09 |
April | 0.609705E+09 | 0.142869E+09 | 0.466836E+09 | 0.104363E+10 | 0.380668E+09 |
May | 0.481387E+09 | 20458288.55 | 0.460929E+09 | 0.100855E+10 | 0.101934E+09 |
June | 0.460189E+09 | 4289402.79 | 0.455899E+09 | 0.989977E+09 | 85912574.54 |
July | 0.497801E+09 | 9149531.27 | 0.488652E+09 | 0.105815E+10 | 60704056.26 |
August | 0.585637E+09 | 70294041.06 | 0.515343E+09 | 0.123746E+10 | 0.103831E+09 |
September | 0.679999E+09 | 0.179209E+09 | 0.500791E+09 | 0.132992E+10 | 0.149666E+09 |
October | 0.109019E+10 | 0.567887E+09 | 0.522305E+09 | 0.195989E+10 | 0.291044E+09 |
November | 0.134259E+10 | 0.924385E+09 | 0.418202E+09 | 0.209598E+10 | 0.585873E+09 |
December | 0.143448E+10 | 0.103016E+10 | 0.404312E+09 | 0.215462E+10 | 0.778987E+09 |
Annual Sum or Average | 0.107027E+11 | 0.515773E+10 | 0.554493E+10 | 0.181178E+11 | 0.469093E+10 |
Minimum of Months | 0.460189E+09 | 4289402.79 | 0.404312E+09 | 0.989977E+09 | 60704056.26 |
Maximum of Months | 0.146806E+10 | 0.104698E+10 | 0.522305E+09 | 0.215462E+10 | 0.872945E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.133767E+10 | 0.723336E+09 | 0.614336E+09 | 0.175093E+10 | 0.173639E+10 |
February | 0.136797E+10 | 0.692380E+09 | 0.675594E+09 | 0.186973E+10 | 0.130375E+10 |
March | 0.149274E+10 | 0.660794E+09 | 0.831943E+09 | 0.212546E+10 | 0.121511E+10 |
April | 0.179421E+10 | 0.825366E+09 | 0.968844E+09 | 0.287166E+10 | 0.756087E+09 |
May | 0.154184E+10 | 0.502253E+09 | 0.103958E+10 | 0.297628E+10 | 0.222822E+09 |
June | 0.165755E+10 | 0.581212E+09 | 0.107634E+10 | 0.325016E+10 | 0.193652E+09 |
July | 0.156347E+10 | 0.433679E+09 | 0.112979E+10 | 0.307305E+10 | 0.140220E+09 |
August | 0.158086E+10 | 0.483922E+09 | 0.109694E+10 | 0.308881E+10 | 0.214824E+09 |
September | 0.140875E+10 | 0.483266E+09 | 0.925484E+09 | 0.260878E+10 | 0.292486E+09 |
October | 0.149034E+10 | 0.643958E+09 | 0.846386E+09 | 0.264799E+10 | 0.550955E+09 |
November | 0.123620E+10 | 0.621260E+09 | 0.614937E+09 | 0.182487E+10 | 0.114016E+10 |
December | 0.122875E+10 | 0.653431E+09 | 0.575321E+09 | 0.168492E+10 | 0.151147E+10 |
Annual Sum or Average | 0.177004E+11 | 0.730486E+10 | 0.103955E+11 | 0.297726E+11 | 0.927792E+10 |
Minimum of Months | 0.122875E+10 | 0.433679E+09 | 0.575321E+09 | 0.168492E+10 | 0.140220E+09 |
Maximum of Months | 0.179421E+10 | 0.825366E+09 | 0.112979E+10 | 0.325016E+10 | 0.173639E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 52890172.70 | 28599946.46 | 24290226.24 | 69229864.66 | 68655100.35 |
February | 54088313.58 | 27376006.88 | 26712306.70 | 73927208.87 | 51549119.71 |
March | 59021292.72 | 26127100.62 | 32894192.10 | 84038674.70 | 48044160.64 |
April | 70941275.25 | 32634136.86 | 38307138.39 | 0.113542E+09 | 29894977.49 |
May | 60962658.31 | 19858574.75 | 41104083.56 | 0.117679E+09 | 8810159.37 |
June | 65537918.32 | 22980537.38 | 42557380.94 | 0.128508E+09 | 7656826.12 |
July | 61818000.86 | 17147236.82 | 44670764.05 | 0.121505E+09 | 5544171.48 |
August | 62505810.51 | 19133761.31 | 43372049.20 | 0.122128E+09 | 8493913.35 |
September | 55700552.25 | 19107846.40 | 36592705.85 | 0.103149E+09 | 11564606.49 |
October | 58926733.32 | 25461453.85 | 33465279.47 | 0.104699E+09 | 21784235.42 |
November | 48877967.62 | 24563975.37 | 24313992.25 | 72153681.89 | 45080820.04 |
December | 48583588.46 | 25835971.82 | 22747616.64 | 66620198.77 | 59762166.79 |
Annual Sum or Average | 0.699854E+09 | 0.288827E+09 | 0.411028E+09 | 0.117718E+10 | 0.366840E+09 |
Minimum of Months | 48583588.46 | 17147236.82 | 22747616.64 | 66620198.77 | 5544171.48 |
Maximum of Months | 70941275.25 | 32634136.86 | 44670764.05 | 0.128508E+09 | 68655100.35 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761979E+09 | 0.00 | 0.761979E+09 | 0.587063E+09 | 0.266626E+10 |
February | 0.811956E+09 | 0.00 | 0.811956E+09 | 0.718406E+09 | 0.201608E+10 |
March | 0.104286E+10 | 0.00 | 0.104286E+10 | 0.113003E+10 | 0.190503E+10 |
April | 0.119110E+10 | 4888705.04 | 0.118621E+10 | 0.167552E+10 | 0.115998E+10 |
May | 0.139412E+10 | 50993845.67 | 0.134313E+10 | 0.285438E+10 | 0.338318E+09 |
June | 0.153427E+10 | 0.106237E+09 | 0.142804E+10 | 0.326151E+10 | 0.281640E+09 |
July | 0.153854E+10 | 58615712.59 | 0.147993E+10 | 0.324489E+10 | 0.196707E+09 |
August | 0.137779E+10 | 10836527.32 | 0.136696E+10 | 0.293003E+10 | 0.276441E+09 |
September | 0.115171E+10 | 88704.64 | 0.115163E+10 | 0.225844E+10 | 0.382435E+09 |
October | 0.103418E+10 | 0.00 | 0.103418E+10 | 0.188650E+10 | 0.764215E+09 |
November | 0.759779E+09 | 0.00 | 0.759779E+09 | 0.852728E+09 | 0.167105E+10 |
December | 0.708346E+09 | 0.00 | 0.708346E+09 | 0.625601E+09 | 0.228173E+10 |
Annual Sum or Average | 0.133067E+11 | 0.231660E+09 | 0.130750E+11 | 0.220251E+11 | 0.139399E+11 |
Minimum of Months | 0.708346E+09 | 0.00 | 0.708346E+09 | 0.587063E+09 | 0.196707E+09 |
Maximum of Months | 0.153854E+10 | 0.106237E+09 | 0.147993E+10 | 0.326151E+10 | 0.266626E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.130735E+10 | 0.665704E+09 | 0.641643E+09 | 0.158816E+10 | 0.163897E+10 |
February | 0.131489E+10 | 0.634794E+09 | 0.680100E+09 | 0.168469E+10 | 0.124673E+10 |
March | 0.171247E+10 | 0.825875E+09 | 0.886595E+09 | 0.236240E+10 | 0.119105E+10 |
April | 0.181862E+10 | 0.822507E+09 | 0.996108E+09 | 0.283103E+10 | 0.753815E+09 |
May | 0.193699E+10 | 0.839912E+09 | 0.109707E+10 | 0.359724E+10 | 0.226372E+09 |
June | 0.190106E+10 | 0.753906E+09 | 0.114716E+10 | 0.365262E+10 | 0.187756E+09 |
July | 0.189399E+10 | 0.693097E+09 | 0.120089E+10 | 0.364406E+10 | 0.129218E+09 |
August | 0.174525E+10 | 0.600030E+09 | 0.114522E+10 | 0.336252E+10 | 0.184663E+09 |
September | 0.149610E+10 | 0.514354E+09 | 0.981751E+09 | 0.274896E+10 | 0.251902E+09 |
October | 0.152774E+10 | 0.644700E+09 | 0.883041E+09 | 0.267167E+10 | 0.493234E+09 |
November | 0.130896E+10 | 0.667751E+09 | 0.641211E+09 | 0.184768E+10 | 0.104127E+10 |
December | 0.106496E+10 | 0.482400E+09 | 0.582556E+09 | 0.134932E+10 | 0.143828E+10 |
Annual Sum or Average | 0.190284E+11 | 0.814503E+10 | 0.108834E+11 | 0.313403E+11 | 0.878325E+10 |
Minimum of Months | 0.106496E+10 | 0.482400E+09 | 0.582556E+09 | 0.134932E+10 | 0.129218E+09 |
Maximum of Months | 0.193699E+10 | 0.839912E+09 | 0.120089E+10 | 0.365262E+10 | 0.163897E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.440433E+10 | 0.314104E+10 | 0.126328E+10 | 0.634197E+10 | 0.249882E+10 |
February | 0.360791E+10 | 0.233534E+10 | 0.127258E+10 | 0.531306E+10 | 0.193146E+10 |
March | 0.255016E+10 | 0.115089E+10 | 0.139927E+10 | 0.386990E+10 | 0.188531E+10 |
April | 0.182918E+10 | 0.428620E+09 | 0.140056E+10 | 0.306363E+10 | 0.120250E+10 |
May | 0.144421E+10 | 61376736.89 | 0.138284E+10 | 0.298937E+10 | 0.347978E+09 |
June | 0.138062E+10 | 12868600.70 | 0.136775E+10 | 0.294693E+10 | 0.289804E+09 |
July | 0.149346E+10 | 27449430.67 | 0.146601E+10 | 0.316824E+10 | 0.191698E+09 |
August | 0.175697E+10 | 0.210889E+09 | 0.154608E+10 | 0.373613E+10 | 0.289216E+09 |
September | 0.204007E+10 | 0.537642E+09 | 0.150242E+10 | 0.400038E+10 | 0.406409E+09 |
October | 0.327068E+10 | 0.170371E+10 | 0.156697E+10 | 0.589250E+10 | 0.800969E+09 |
November | 0.402789E+10 | 0.277324E+10 | 0.125465E+10 | 0.628038E+10 | 0.163065E+10 |
December | 0.430356E+10 | 0.309058E+10 | 0.121298E+10 | 0.643333E+10 | 0.221164E+10 |
Annual Sum or Average | 0.321090E+11 | 0.154737E+11 | 0.166354E+11 | 0.540358E+11 | 0.136865E+11 |
Minimum of Months | 0.138062E+10 | 12868600.70 | 0.121298E+10 | 0.294693E+10 | 0.191698E+09 |
Maximum of Months | 0.440433E+10 | 0.314104E+10 | 0.156697E+10 | 0.643333E+10 | 0.249882E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139057E+10 | 0.751943E+09 | 0.638629E+09 | 0.182130E+10 | 0.173521E+10 |
February | 0.142207E+10 | 0.719764E+09 | 0.702310E+09 | 0.193062E+10 | 0.132757E+10 |
March | 0.155177E+10 | 0.686928E+09 | 0.864841E+09 | 0.218354E+10 | 0.126110E+10 |
April | 0.186517E+10 | 0.858009E+09 | 0.100716E+10 | 0.295034E+10 | 0.802310E+09 |
May | 0.160281E+10 | 0.522117E+09 | 0.108069E+10 | 0.306904E+10 | 0.249821E+09 |
June | 0.172310E+10 | 0.604199E+09 | 0.111890E+10 | 0.335960E+10 | 0.211017E+09 |
July | 0.162530E+10 | 0.450831E+09 | 0.117447E+10 | 0.318715E+10 | 0.144605E+09 |
August | 0.164338E+10 | 0.503060E+09 | 0.114032E+10 | 0.321959E+10 | 0.203316E+09 |
September | 0.146446E+10 | 0.502379E+09 | 0.962082E+09 | 0.272083E+10 | 0.273559E+09 |
October | 0.154928E+10 | 0.669427E+09 | 0.879857E+09 | 0.276203E+10 | 0.534384E+09 |
November | 0.128508E+10 | 0.645830E+09 | 0.639254E+09 | 0.191177E+10 | 0.111389E+10 |
December | 0.127734E+10 | 0.679273E+09 | 0.598072E+09 | 0.176079E+10 | 0.148867E+10 |
Annual Sum or Average | 0.184003E+11 | 0.759376E+10 | 0.108066E+11 | 0.308766E+11 | 0.934546E+10 |
Minimum of Months | 0.127734E+10 | 0.450831E+09 | 0.598072E+09 | 0.176079E+10 | 0.144605E+09 |
Maximum of Months | 0.186517E+10 | 0.858009E+09 | 0.117447E+10 | 0.335960E+10 | 0.173521E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 232.33 | 921.80 | 284.49 | 0.00 | 284.49 | 0.00 | 0.00 |
February | 309.66 | 768.96 | 335.63 | 0.00 | 335.63 | 0.00 | 0.00 |
March | 430.92 | 663.43 | 389.36 | 0.00 | 389.36 | 0.00 | 0.00 |
April | 648.95 | 424.51 | 459.53 | 1.89 | 457.64 | 0.00 | 0.00 |
May | 1056.03 | 125.85 | 520.51 | 19.04 | 501.47 | 0.00 | 0.00 |
June | 1245.85 | 109.22 | 591.93 | 40.99 | 550.94 | 0.00 | 0.00 |
July | 1198.31 | 73.47 | 574.43 | 21.88 | 552.54 | 0.00 | 0.00 |
August | 1084.24 | 102.09 | 514.41 | 4.05 | 510.36 | 0.00 | 0.00 |
September | 864.43 | 140.79 | 444.33 | 0.03 | 444.30 | 0.00 | 0.00 |
October | 703.39 | 268.38 | 386.12 | 0.00 | 386.12 | 0.00 | 0.00 |
November | 342.49 | 590.09 | 293.12 | 0.00 | 293.12 | 0.00 | 0.00 |
December | 246.76 | 782.44 | 264.47 | 0.00 | 264.47 | 0.00 | 0.00 |
Annual Sum or Average | 699.27 | 412.41 | 421.95 | 7.35 | 414.61 | 0.00 | 0.00 |
Minimum of Months | 232.33 | 73.47 | 264.47 | 0.00 | 264.47 | 0.00 | 0.00 |
Maximum of Months | 1245.85 | 921.80 | 591.93 | 40.99 | 552.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 606.54 | 569.98 | 488.11 | 248.55 | 239.56 | 0.00 | 0.00 |
February | 707.60 | 479.25 | 543.52 | 262.40 | 281.13 | 0.00 | 0.00 |
March | 887.11 | 418.44 | 639.36 | 308.35 | 331.02 | 0.00 | 0.00 |
April | 1091.82 | 278.33 | 701.63 | 317.33 | 384.30 | 0.00 | 0.00 |
May | 1335.08 | 84.17 | 723.19 | 313.59 | 409.60 | 0.00 | 0.00 |
June | 1399.93 | 72.93 | 733.43 | 290.86 | 442.58 | 0.00 | 0.00 |
July | 1350.99 | 48.04 | 707.14 | 258.77 | 448.36 | 0.00 | 0.00 |
August | 1247.92 | 68.34 | 651.60 | 224.03 | 427.58 | 0.00 | 0.00 |
September | 1055.02 | 92.96 | 577.20 | 198.44 | 378.76 | 0.00 | 0.00 |
October | 995.28 | 174.39 | 570.39 | 240.70 | 329.69 | 0.00 | 0.00 |
November | 722.14 | 372.43 | 505.00 | 257.62 | 247.38 | 0.00 | 0.00 |
December | 514.61 | 497.32 | 397.61 | 180.11 | 217.50 | 0.00 | 0.00 |
Annual Sum or Average | 994.37 | 261.92 | 603.39 | 258.28 | 345.11 | 0.00 | 0.00 |
Minimum of Months | 514.61 | 48.04 | 397.61 | 180.11 | 217.50 | 0.00 | 0.00 |
Maximum of Months | 1399.93 | 569.98 | 733.43 | 317.33 | 448.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2382.52 | 870.44 | 1644.39 | 1172.73 | 471.66 | 0.00 | 0.00 |
February | 2209.68 | 744.05 | 1491.37 | 965.33 | 526.03 | 0.00 | 0.00 |
March | 1451.66 | 660.73 | 952.12 | 429.69 | 522.43 | 0.00 | 0.00 |
April | 1181.68 | 441.51 | 705.70 | 165.36 | 540.34 | 0.00 | 0.00 |
May | 1106.29 | 129.18 | 539.21 | 22.92 | 516.29 | 0.00 | 0.00 |
June | 1124.92 | 112.41 | 532.65 | 4.96 | 527.68 | 0.00 | 0.00 |
July | 1169.73 | 71.41 | 557.59 | 10.25 | 547.34 | 0.00 | 0.00 |
August | 1384.30 | 106.84 | 655.98 | 78.74 | 577.24 | 0.00 | 0.00 |
September | 1535.41 | 150.31 | 787.06 | 207.42 | 579.64 | 0.00 | 0.00 |
October | 2195.13 | 284.89 | 1221.13 | 636.09 | 585.04 | 0.00 | 0.00 |
November | 2432.31 | 587.05 | 1553.97 | 1069.92 | 484.05 | 0.00 | 0.00 |
December | 2413.75 | 767.52 | 1606.77 | 1153.89 | 452.87 | 0.00 | 0.00 |
Annual Sum or Average | 1713.17 | 408.75 | 1018.17 | 490.67 | 527.50 | 0.00 | 0.00 |
Minimum of Months | 1106.29 | 71.41 | 532.65 | 4.96 | 452.87 | 0.00 | 0.00 |
Maximum of Months | 2432.31 | 870.44 | 1644.39 | 1172.73 | 585.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 689.03 | 601.44 | 519.18 | 280.74 | 238.44 | 0.00 | 0.00 |
February | 806.93 | 507.80 | 587.83 | 297.52 | 290.31 | 0.00 | 0.00 |
March | 820.63 | 439.84 | 579.36 | 256.47 | 322.89 | 0.00 | 0.00 |
April | 1139.68 | 293.53 | 719.59 | 331.02 | 388.56 | 0.00 | 0.00 |
May | 1140.37 | 92.30 | 598.42 | 194.94 | 403.48 | 0.00 | 0.00 |
June | 1288.86 | 81.23 | 664.78 | 233.10 | 431.68 | 0.00 | 0.00 |
July | 1182.43 | 53.10 | 606.82 | 168.32 | 438.50 | 0.00 | 0.00 |
August | 1195.93 | 74.86 | 613.57 | 187.82 | 425.75 | 0.00 | 0.00 |
September | 1046.54 | 100.38 | 564.99 | 193.82 | 371.17 | 0.00 | 0.00 |
October | 1030.90 | 188.35 | 578.44 | 249.94 | 328.50 | 0.00 | 0.00 |
November | 746.28 | 395.38 | 495.79 | 249.16 | 246.63 | 0.00 | 0.00 |
December | 666.49 | 512.95 | 476.91 | 253.61 | 223.29 | 0.00 | 0.00 |
Annual Sum or Average | 980.09 | 277.21 | 583.47 | 240.80 | 342.67 | 0.00 | 0.00 |
Minimum of Months | 666.49 | 53.10 | 476.91 | 168.32 | 223.29 | 0.00 | 0.00 |
Maximum of Months | 1288.86 | 601.44 | 719.59 | 331.02 | 438.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 220.14 | 1008.14 | 284.49 | 0.00 | 284.49 | 0.00 | 0.00 |
February | 307.31 | 824.89 | 335.63 | 0.00 | 335.63 | 0.00 | 0.00 |
March | 441.14 | 687.63 | 389.36 | 0.00 | 389.36 | 0.00 | 0.00 |
April | 671.00 | 418.26 | 459.53 | 1.89 | 457.64 | 0.00 | 0.00 |
May | 1083.76 | 109.13 | 520.50 | 19.04 | 501.46 | 0.00 | 0.00 |
June | 1272.02 | 96.67 | 591.92 | 40.99 | 550.94 | 0.00 | 0.00 |
July | 1219.17 | 68.37 | 574.42 | 21.88 | 552.54 | 0.00 | 0.00 |
August | 1090.20 | 107.31 | 514.41 | 4.05 | 510.36 | 0.00 | 0.00 |
September | 868.61 | 155.41 | 444.33 | 0.03 | 444.30 | 0.00 | 0.00 |
October | 700.38 | 295.42 | 386.12 | 0.00 | 386.12 | 0.00 | 0.00 |
November | 323.96 | 666.54 | 293.12 | 0.00 | 293.12 | 0.00 | 0.00 |
December | 230.19 | 875.76 | 264.46 | 0.00 | 264.46 | 0.00 | 0.00 |
Annual Sum or Average | 704.68 | 440.84 | 421.95 | 7.35 | 414.60 | 0.00 | 0.00 |
Minimum of Months | 220.14 | 68.37 | 264.46 | 0.00 | 264.46 | 0.00 | 0.00 |
Maximum of Months | 1272.02 | 1008.14 | 591.92 | 40.99 | 552.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 591.02 | 640.00 | 488.10 | 248.54 | 239.56 | 0.00 | 0.00 |
February | 700.56 | 527.73 | 543.52 | 262.40 | 281.12 | 0.00 | 0.00 |
March | 892.04 | 447.71 | 639.36 | 308.34 | 331.01 | 0.00 | 0.00 |
April | 1105.41 | 285.92 | 701.62 | 317.32 | 384.30 | 0.00 | 0.00 |
May | 1353.81 | 80.18 | 723.18 | 313.58 | 409.60 | 0.00 | 0.00 |
June | 1417.43 | 69.69 | 733.43 | 290.86 | 442.57 | 0.00 | 0.00 |
July | 1363.38 | 50.39 | 707.13 | 258.77 | 448.36 | 0.00 | 0.00 |
August | 1252.61 | 77.00 | 651.60 | 224.02 | 427.58 | 0.00 | 0.00 |
September | 1058.09 | 109.79 | 577.20 | 198.44 | 378.76 | 0.00 | 0.00 |
October | 995.41 | 199.26 | 570.39 | 240.70 | 329.69 | 0.00 | 0.00 |
November | 708.35 | 429.76 | 505.00 | 257.62 | 247.38 | 0.00 | 0.00 |
December | 499.95 | 566.84 | 397.61 | 180.11 | 217.50 | 0.00 | 0.00 |
Annual Sum or Average | 996.41 | 289.13 | 603.38 | 258.27 | 345.11 | 0.00 | 0.00 |
Minimum of Months | 499.95 | 50.39 | 397.61 | 180.11 | 217.50 | 0.00 | 0.00 |
Maximum of Months | 1417.43 | 640.00 | 733.43 | 317.32 | 448.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2387.42 | 977.80 | 1644.40 | 1172.75 | 471.66 | 0.00 | 0.00 |
February | 2220.54 | 821.63 | 1491.38 | 965.35 | 526.04 | 0.00 | 0.00 |
March | 1475.98 | 690.92 | 952.13 | 429.70 | 522.43 | 0.00 | 0.00 |
April | 1207.96 | 440.61 | 705.71 | 165.36 | 540.34 | 0.00 | 0.00 |
May | 1129.70 | 114.18 | 539.21 | 22.92 | 516.30 | 0.00 | 0.00 |
June | 1145.86 | 99.44 | 532.65 | 4.96 | 527.68 | 0.00 | 0.00 |
July | 1185.26 | 68.00 | 557.60 | 10.25 | 547.35 | 0.00 | 0.00 |
August | 1386.10 | 116.30 | 655.98 | 78.74 | 577.25 | 0.00 | 0.00 |
September | 1539.33 | 173.23 | 787.07 | 207.43 | 579.64 | 0.00 | 0.00 |
October | 2195.31 | 326.00 | 1221.14 | 636.10 | 585.04 | 0.00 | 0.00 |
November | 2426.00 | 678.12 | 1553.99 | 1069.93 | 484.05 | 0.00 | 0.00 |
December | 2413.43 | 872.56 | 1606.78 | 1153.91 | 452.88 | 0.00 | 0.00 |
Annual Sum or Average | 1723.61 | 446.26 | 1018.18 | 490.67 | 527.51 | 0.00 | 0.00 |
Minimum of Months | 1129.70 | 68.00 | 532.65 | 4.96 | 452.88 | 0.00 | 0.00 |
Maximum of Months | 2426.00 | 977.80 | 1644.40 | 1172.75 | 585.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 679.57 | 673.92 | 519.18 | 280.74 | 238.44 | 0.00 | 0.00 |
February | 803.43 | 560.23 | 587.82 | 297.52 | 290.31 | 0.00 | 0.00 |
March | 824.93 | 471.61 | 579.36 | 256.47 | 322.89 | 0.00 | 0.00 |
April | 1151.70 | 303.23 | 719.58 | 331.02 | 388.56 | 0.00 | 0.00 |
May | 1155.15 | 86.48 | 598.42 | 194.93 | 403.48 | 0.00 | 0.00 |
June | 1303.50 | 77.67 | 664.77 | 233.10 | 431.67 | 0.00 | 0.00 |
July | 1192.71 | 54.42 | 606.81 | 168.32 | 438.49 | 0.00 | 0.00 |
August | 1198.83 | 83.38 | 613.56 | 187.82 | 425.74 | 0.00 | 0.00 |
September | 1046.27 | 117.30 | 564.99 | 193.82 | 371.17 | 0.00 | 0.00 |
October | 1027.74 | 213.84 | 578.43 | 249.93 | 328.50 | 0.00 | 0.00 |
November | 731.88 | 457.27 | 495.78 | 249.16 | 246.62 | 0.00 | 0.00 |
December | 653.95 | 586.63 | 476.90 | 253.61 | 223.29 | 0.00 | 0.00 |
Annual Sum or Average | 981.41 | 305.83 | 583.47 | 240.79 | 342.67 | 0.00 | 0.00 |
Minimum of Months | 653.95 | 54.42 | 476.90 | 168.32 | 223.29 | 0.00 | 0.00 |
Maximum of Months | 1303.50 | 673.92 | 719.58 | 331.02 | 438.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 219.18 | 995.47 | 284.49 | 0.00 | 284.49 | 0.00 | 0.00 |
February | 296.96 | 833.36 | 335.63 | 0.00 | 335.63 | 0.00 | 0.00 |
March | 421.90 | 711.26 | 389.36 | 0.00 | 389.36 | 0.00 | 0.00 |
April | 646.42 | 447.52 | 459.53 | 1.89 | 457.64 | 0.00 | 0.00 |
May | 1065.70 | 126.31 | 520.51 | 19.04 | 501.47 | 0.00 | 0.00 |
June | 1258.30 | 108.66 | 591.93 | 40.99 | 550.94 | 0.00 | 0.00 |
July | 1211.50 | 73.44 | 574.43 | 21.88 | 552.54 | 0.00 | 0.00 |
August | 1093.95 | 103.21 | 514.41 | 4.05 | 510.36 | 0.00 | 0.00 |
September | 871.31 | 147.54 | 444.33 | 0.03 | 444.30 | 0.00 | 0.00 |
October | 704.34 | 285.33 | 386.12 | 0.00 | 386.12 | 0.00 | 0.00 |
November | 328.98 | 644.70 | 293.12 | 0.00 | 293.12 | 0.00 | 0.00 |
December | 233.57 | 851.90 | 264.47 | 0.00 | 264.47 | 0.00 | 0.00 |
Annual Sum or Average | 698.41 | 442.03 | 421.95 | 7.35 | 414.61 | 0.00 | 0.00 |
Minimum of Months | 219.18 | 73.44 | 264.47 | 0.00 | 264.47 | 0.00 | 0.00 |
Maximum of Months | 1258.30 | 995.47 | 591.93 | 40.99 | 552.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 592.95 | 611.92 | 488.11 | 248.55 | 239.56 | 0.00 | 0.00 |
February | 696.38 | 515.35 | 543.52 | 262.40 | 281.13 | 0.00 | 0.00 |
March | 882.02 | 444.69 | 639.36 | 308.35 | 331.02 | 0.00 | 0.00 |
April | 1092.22 | 290.82 | 701.63 | 317.33 | 384.30 | 0.00 | 0.00 |
May | 1343.06 | 84.52 | 723.19 | 313.59 | 409.60 | 0.00 | 0.00 |
June | 1409.19 | 72.44 | 733.43 | 290.86 | 442.58 | 0.00 | 0.00 |
July | 1360.54 | 48.24 | 707.14 | 258.77 | 448.36 | 0.00 | 0.00 |
August | 1255.42 | 68.95 | 651.60 | 224.03 | 427.58 | 0.00 | 0.00 |
September | 1060.55 | 97.18 | 577.20 | 198.44 | 378.76 | 0.00 | 0.00 |
October | 997.49 | 184.15 | 570.39 | 240.70 | 329.69 | 0.00 | 0.00 |
November | 712.84 | 401.72 | 505.00 | 257.62 | 247.38 | 0.00 | 0.00 |
December | 503.78 | 536.99 | 397.61 | 180.11 | 217.50 | 0.00 | 0.00 |
Annual Sum or Average | 993.80 | 278.51 | 603.39 | 258.28 | 345.11 | 0.00 | 0.00 |
Minimum of Months | 503.78 | 48.24 | 397.61 | 180.11 | 217.50 | 0.00 | 0.00 |
Maximum of Months | 1409.19 | 611.92 | 733.43 | 317.33 | 448.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2367.82 | 932.95 | 1644.39 | 1172.73 | 471.66 | 0.00 | 0.00 |
February | 2196.21 | 798.39 | 1491.37 | 965.33 | 526.03 | 0.00 | 0.00 |
March | 1444.86 | 703.89 | 952.12 | 429.69 | 522.43 | 0.00 | 0.00 |
April | 1181.96 | 463.93 | 705.70 | 165.36 | 540.34 | 0.00 | 0.00 |
May | 1116.10 | 129.92 | 539.21 | 22.92 | 516.29 | 0.00 | 0.00 |
June | 1136.93 | 111.81 | 532.65 | 4.96 | 527.68 | 0.00 | 0.00 |
July | 1182.89 | 71.57 | 557.59 | 10.25 | 547.34 | 0.00 | 0.00 |
August | 1394.91 | 107.98 | 655.98 | 78.74 | 577.24 | 0.00 | 0.00 |
September | 1543.36 | 156.79 | 787.06 | 207.42 | 579.64 | 0.00 | 0.00 |
October | 2200.01 | 299.05 | 1221.13 | 636.09 | 585.04 | 0.00 | 0.00 |
November | 2422.99 | 629.11 | 1553.97 | 1069.92 | 484.05 | 0.00 | 0.00 |
December | 2401.93 | 825.73 | 1606.77 | 1153.89 | 452.87 | 0.00 | 0.00 |
Annual Sum or Average | 1713.46 | 433.99 | 1018.17 | 490.67 | 527.50 | 0.00 | 0.00 |
Minimum of Months | 1116.10 | 71.57 | 532.65 | 4.96 | 452.87 | 0.00 | 0.00 |
Maximum of Months | 2422.99 | 932.95 | 1644.39 | 1172.73 | 585.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 679.99 | 647.85 | 519.18 | 280.74 | 238.44 | 0.00 | 0.00 |
February | 798.04 | 548.77 | 587.83 | 297.52 | 290.31 | 0.00 | 0.00 |
March | 815.24 | 470.84 | 579.36 | 256.47 | 322.89 | 0.00 | 0.00 |
April | 1138.25 | 309.53 | 719.59 | 331.02 | 388.56 | 0.00 | 0.00 |
May | 1145.85 | 93.27 | 598.42 | 194.94 | 403.48 | 0.00 | 0.00 |
June | 1296.14 | 81.41 | 664.78 | 233.10 | 431.68 | 0.00 | 0.00 |
July | 1189.95 | 53.99 | 606.82 | 168.32 | 438.50 | 0.00 | 0.00 |
August | 1202.06 | 75.91 | 613.57 | 187.82 | 425.75 | 0.00 | 0.00 |
September | 1049.70 | 105.54 | 564.99 | 193.82 | 371.17 | 0.00 | 0.00 |
October | 1031.22 | 199.52 | 578.44 | 249.94 | 328.50 | 0.00 | 0.00 |
November | 737.56 | 429.74 | 495.79 | 249.16 | 246.63 | 0.00 | 0.00 |
December | 657.40 | 555.81 | 476.91 | 253.61 | 223.29 | 0.00 | 0.00 |
Annual Sum or Average | 979.09 | 296.34 | 583.47 | 240.80 | 342.67 | 0.00 | 0.00 |
Minimum of Months | 657.40 | 53.99 | 476.91 | 168.32 | 223.29 | 0.00 | 0.00 |
Maximum of Months | 1296.14 | 647.85 | 719.59 | 331.02 | 438.50 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.622264E+09 | 0.246896E+10 | 0.761979E+09 | 0.00 | 0.761979E+09 | 0.00 | 0.00 |
February | 0.749139E+09 | 0.186028E+10 | 0.811956E+09 | 0.00 | 0.811956E+09 | 0.00 | 0.00 |
March | 0.115417E+10 | 0.177693E+10 | 0.104286E+10 | 0.00 | 0.104286E+10 | 0.00 | 0.00 |
April | 0.168208E+10 | 0.110033E+10 | 0.119110E+10 | 4888705.04 | 0.118621E+10 | 0.00 | 0.00 |
May | 0.282847E+10 | 0.337066E+09 | 0.139412E+10 | 50993845.67 | 0.134313E+10 | 0.00 | 0.00 |
June | 0.322925E+10 | 0.283100E+09 | 0.153427E+10 | 0.106237E+09 | 0.142804E+10 | 0.00 | 0.00 |
July | 0.320955E+10 | 0.196794E+09 | 0.153854E+10 | 58615712.59 | 0.147993E+10 | 0.00 | 0.00 |
August | 0.290404E+10 | 0.273440E+09 | 0.137779E+10 | 10836527.32 | 0.136696E+10 | 0.00 | 0.00 |
September | 0.224061E+10 | 0.364918E+09 | 0.115171E+10 | 88704.64 | 0.115163E+10 | 0.00 | 0.00 |
October | 0.188396E+10 | 0.718834E+09 | 0.103418E+10 | 0.00 | 0.103418E+10 | 0.00 | 0.00 |
November | 0.887746E+09 | 0.152952E+10 | 0.759779E+09 | 0.00 | 0.759779E+09 | 0.00 | 0.00 |
December | 0.660932E+09 | 0.209569E+10 | 0.708346E+09 | 0.00 | 0.708346E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.220522E+11 | 0.130059E+11 | 0.133067E+11 | 0.231660E+09 | 0.130750E+11 | 0.00 | 0.00 |
Minimum of Months | 0.622264E+09 | 0.196794E+09 | 0.708346E+09 | 0.00 | 0.708346E+09 | 0.00 | 0.00 |
Maximum of Months | 0.322925E+10 | 0.246896E+10 | 0.153854E+10 | 0.106237E+09 | 0.147993E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.162455E+10 | 0.152662E+10 | 0.130735E+10 | 0.665704E+09 | 0.641643E+09 | 0.00 | 0.00 |
February | 0.171184E+10 | 0.115939E+10 | 0.131489E+10 | 0.634794E+09 | 0.680100E+09 | 0.00 | 0.00 |
March | 0.237604E+10 | 0.112075E+10 | 0.171247E+10 | 0.825875E+09 | 0.886595E+09 | 0.00 | 0.00 |
April | 0.283000E+10 | 0.721423E+09 | 0.181862E+10 | 0.822507E+09 | 0.996108E+09 | 0.00 | 0.00 |
May | 0.357587E+10 | 0.225432E+09 | 0.193699E+10 | 0.839912E+09 | 0.109707E+10 | 0.00 | 0.00 |
June | 0.362863E+10 | 0.189042E+09 | 0.190106E+10 | 0.753906E+09 | 0.114716E+10 | 0.00 | 0.00 |
July | 0.361849E+10 | 0.128671E+09 | 0.189399E+10 | 0.693097E+09 | 0.120089E+10 | 0.00 | 0.00 |
August | 0.334242E+10 | 0.183031E+09 | 0.174525E+10 | 0.600030E+09 | 0.114522E+10 | 0.00 | 0.00 |
September | 0.273461E+10 | 0.240945E+09 | 0.149610E+10 | 0.514354E+09 | 0.981751E+09 | 0.00 | 0.00 |
October | 0.266576E+10 | 0.467081E+09 | 0.152774E+10 | 0.644700E+09 | 0.883041E+09 | 0.00 | 0.00 |
November | 0.187178E+10 | 0.965347E+09 | 0.130896E+10 | 0.667751E+09 | 0.641211E+09 | 0.00 | 0.00 |
December | 0.137832E+10 | 0.133202E+10 | 0.106496E+10 | 0.482400E+09 | 0.582556E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.313583E+11 | 0.825975E+10 | 0.190284E+11 | 0.814503E+10 | 0.108834E+11 | 0.00 | 0.00 |
Minimum of Months | 0.137832E+10 | 0.128671E+09 | 0.106496E+10 | 0.482400E+09 | 0.582556E+09 | 0.00 | 0.00 |
Maximum of Months | 0.362863E+10 | 0.152662E+10 | 0.193699E+10 | 0.839912E+09 | 0.120089E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.638135E+10 | 0.233139E+10 | 0.440433E+10 | 0.314104E+10 | 0.126328E+10 | 0.00 | 0.00 |
February | 0.534567E+10 | 0.180000E+10 | 0.360791E+10 | 0.233534E+10 | 0.127258E+10 | 0.00 | 0.00 |
March | 0.388811E+10 | 0.176970E+10 | 0.255016E+10 | 0.115089E+10 | 0.139927E+10 | 0.00 | 0.00 |
April | 0.306292E+10 | 0.114439E+10 | 0.182918E+10 | 0.428620E+09 | 0.140056E+10 | 0.00 | 0.00 |
May | 0.296310E+10 | 0.346007E+09 | 0.144421E+10 | 61376736.89 | 0.138284E+10 | 0.00 | 0.00 |
June | 0.291581E+10 | 0.291364E+09 | 0.138062E+10 | 12868600.70 | 0.136775E+10 | 0.00 | 0.00 |
July | 0.313301E+10 | 0.191264E+09 | 0.149346E+10 | 27449430.67 | 0.146601E+10 | 0.00 | 0.00 |
August | 0.370771E+10 | 0.286170E+09 | 0.175697E+10 | 0.210889E+09 | 0.154608E+10 | 0.00 | 0.00 |
September | 0.397979E+10 | 0.389615E+09 | 0.204007E+10 | 0.537642E+09 | 0.150242E+10 | 0.00 | 0.00 |
October | 0.587944E+10 | 0.763038E+09 | 0.327068E+10 | 0.170371E+10 | 0.156697E+10 | 0.00 | 0.00 |
November | 0.630455E+10 | 0.152164E+10 | 0.402789E+10 | 0.277324E+10 | 0.125465E+10 | 0.00 | 0.00 |
December | 0.646498E+10 | 0.205572E+10 | 0.430356E+10 | 0.309058E+10 | 0.121298E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.540265E+11 | 0.128903E+11 | 0.321090E+11 | 0.154737E+11 | 0.166354E+11 | 0.00 | 0.00 |
Minimum of Months | 0.291581E+10 | 0.191264E+09 | 0.138062E+10 | 12868600.70 | 0.121298E+10 | 0.00 | 0.00 |
Maximum of Months | 0.646498E+10 | 0.233139E+10 | 0.440433E+10 | 0.314104E+10 | 0.156697E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.184549E+10 | 0.161089E+10 | 0.139057E+10 | 0.751943E+09 | 0.638629E+09 | 0.00 | 0.00 |
February | 0.195212E+10 | 0.122846E+10 | 0.142207E+10 | 0.719764E+09 | 0.702310E+09 | 0.00 | 0.00 |
March | 0.219799E+10 | 0.117807E+10 | 0.155177E+10 | 0.686928E+09 | 0.864841E+09 | 0.00 | 0.00 |
April | 0.295404E+10 | 0.760820E+09 | 0.186517E+10 | 0.858009E+09 | 0.100716E+10 | 0.00 | 0.00 |
May | 0.305436E+10 | 0.247229E+09 | 0.160281E+10 | 0.522117E+09 | 0.108069E+10 | 0.00 | 0.00 |
June | 0.334071E+10 | 0.210545E+09 | 0.172310E+10 | 0.604199E+09 | 0.111890E+10 | 0.00 | 0.00 |
July | 0.316701E+10 | 0.142225E+09 | 0.162530E+10 | 0.450831E+09 | 0.117447E+10 | 0.00 | 0.00 |
August | 0.320318E+10 | 0.200510E+09 | 0.164338E+10 | 0.503060E+09 | 0.114032E+10 | 0.00 | 0.00 |
September | 0.271263E+10 | 0.260190E+09 | 0.146446E+10 | 0.502379E+09 | 0.962082E+09 | 0.00 | 0.00 |
October | 0.276117E+10 | 0.504474E+09 | 0.154928E+10 | 0.669427E+09 | 0.879857E+09 | 0.00 | 0.00 |
November | 0.193436E+10 | 0.102484E+10 | 0.128508E+10 | 0.645830E+09 | 0.639254E+09 | 0.00 | 0.00 |
December | 0.178514E+10 | 0.137389E+10 | 0.127734E+10 | 0.679273E+09 | 0.598072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.309082E+11 | 0.874214E+10 | 0.184003E+11 | 0.759376E+10 | 0.108066E+11 | 0.00 | 0.00 |
Minimum of Months | 0.178514E+10 | 0.142225E+09 | 0.127734E+10 | 0.450831E+09 | 0.598072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.334071E+10 | 0.161089E+10 | 0.186517E+10 | 0.858009E+09 | 0.117447E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.589615E+09 | 0.270020E+10 | 0.761975E+09 | 0.00 | 0.761975E+09 | 0.00 | 0.00 |
February | 0.743443E+09 | 0.199558E+10 | 0.811951E+09 | 0.00 | 0.811951E+09 | 0.00 | 0.00 |
March | 0.118154E+10 | 0.184174E+10 | 0.104286E+10 | 0.00 | 0.104286E+10 | 0.00 | 0.00 |
April | 0.173924E+10 | 0.108412E+10 | 0.119110E+10 | 4888679.71 | 0.118621E+10 | 0.00 | 0.00 |
May | 0.290273E+10 | 0.292286E+09 | 0.139412E+10 | 50993581.43 | 0.134312E+10 | 0.00 | 0.00 |
June | 0.329707E+10 | 0.250579E+09 | 0.153427E+10 | 0.106236E+09 | 0.142803E+10 | 0.00 | 0.00 |
July | 0.326543E+10 | 0.183119E+09 | 0.153854E+10 | 58615408.86 | 0.147992E+10 | 0.00 | 0.00 |
August | 0.291999E+10 | 0.287424E+09 | 0.137779E+10 | 10836471.17 | 0.136695E+10 | 0.00 | 0.00 |
September | 0.225143E+10 | 0.402813E+09 | 0.115171E+10 | 88704.18 | 0.115162E+10 | 0.00 | 0.00 |
October | 0.187591E+10 | 0.791256E+09 | 0.103417E+10 | 0.00 | 0.103417E+10 | 0.00 | 0.00 |
November | 0.839711E+09 | 0.172766E+10 | 0.759775E+09 | 0.00 | 0.759775E+09 | 0.00 | 0.00 |
December | 0.616552E+09 | 0.234563E+10 | 0.708343E+09 | 0.00 | 0.708343E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.222227E+11 | 0.139024E+11 | 0.133066E+11 | 0.231659E+09 | 0.130749E+11 | 0.00 | 0.00 |
Minimum of Months | 0.589615E+09 | 0.183119E+09 | 0.708343E+09 | 0.00 | 0.708343E+09 | 0.00 | 0.00 |
Maximum of Months | 0.329707E+10 | 0.270020E+10 | 0.153854E+10 | 0.106236E+09 | 0.147992E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.158300E+10 | 0.171418E+10 | 0.130734E+10 | 0.665697E+09 | 0.641640E+09 | 0.00 | 0.00 |
February | 0.169479E+10 | 0.127669E+10 | 0.131488E+10 | 0.634787E+09 | 0.680096E+09 | 0.00 | 0.00 |
March | 0.238925E+10 | 0.119915E+10 | 0.171246E+10 | 0.825867E+09 | 0.886590E+09 | 0.00 | 0.00 |
April | 0.286523E+10 | 0.741099E+09 | 0.181860E+10 | 0.822499E+09 | 0.996103E+09 | 0.00 | 0.00 |
May | 0.362605E+10 | 0.214746E+09 | 0.193697E+10 | 0.839903E+09 | 0.109707E+10 | 0.00 | 0.00 |
June | 0.367399E+10 | 0.180647E+09 | 0.190105E+10 | 0.753899E+09 | 0.114715E+10 | 0.00 | 0.00 |
July | 0.365169E+10 | 0.134974E+09 | 0.189398E+10 | 0.693090E+09 | 0.120089E+10 | 0.00 | 0.00 |
August | 0.335500E+10 | 0.206230E+09 | 0.174524E+10 | 0.600024E+09 | 0.114522E+10 | 0.00 | 0.00 |
September | 0.274256E+10 | 0.284585E+09 | 0.149609E+10 | 0.514349E+09 | 0.981745E+09 | 0.00 | 0.00 |
October | 0.266611E+10 | 0.533697E+09 | 0.152773E+10 | 0.644694E+09 | 0.883036E+09 | 0.00 | 0.00 |
November | 0.183604E+10 | 0.111393E+10 | 0.130895E+10 | 0.667744E+09 | 0.641208E+09 | 0.00 | 0.00 |
December | 0.133907E+10 | 0.151821E+10 | 0.106495E+10 | 0.482395E+09 | 0.582552E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.314228E+11 | 0.911814E+10 | 0.190282E+11 | 0.814495E+10 | 0.108833E+11 | 0.00 | 0.00 |
Minimum of Months | 0.133907E+10 | 0.134974E+09 | 0.106495E+10 | 0.482395E+09 | 0.582552E+09 | 0.00 | 0.00 |
Maximum of Months | 0.367399E+10 | 0.171418E+10 | 0.193697E+10 | 0.839903E+09 | 0.120089E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.639447E+10 | 0.261895E+10 | 0.440437E+10 | 0.314108E+10 | 0.126329E+10 | 0.00 | 0.00 |
February | 0.537192E+10 | 0.198769E+10 | 0.360795E+10 | 0.233537E+10 | 0.127259E+10 | 0.00 | 0.00 |
March | 0.395325E+10 | 0.185056E+10 | 0.255019E+10 | 0.115090E+10 | 0.139928E+10 | 0.00 | 0.00 |
April | 0.313103E+10 | 0.114205E+10 | 0.182919E+10 | 0.428625E+09 | 0.140057E+10 | 0.00 | 0.00 |
May | 0.302578E+10 | 0.305814E+09 | 0.144422E+10 | 61377451.51 | 0.138285E+10 | 0.00 | 0.00 |
June | 0.297006E+10 | 0.257749E+09 | 0.138062E+10 | 12868750.53 | 0.136776E+10 | 0.00 | 0.00 |
July | 0.317459E+10 | 0.182120E+09 | 0.149347E+10 | 27449750.27 | 0.146602E+10 | 0.00 | 0.00 |
August | 0.371253E+10 | 0.311507E+09 | 0.175698E+10 | 0.210891E+09 | 0.154609E+10 | 0.00 | 0.00 |
September | 0.398993E+10 | 0.449016E+09 | 0.204008E+10 | 0.537648E+09 | 0.150244E+10 | 0.00 | 0.00 |
October | 0.587992E+10 | 0.873169E+09 | 0.327071E+10 | 0.170373E+10 | 0.156698E+10 | 0.00 | 0.00 |
November | 0.628820E+10 | 0.175769E+10 | 0.402793E+10 | 0.277327E+10 | 0.125466E+10 | 0.00 | 0.00 |
December | 0.646412E+10 | 0.233706E+10 | 0.430361E+10 | 0.309062E+10 | 0.121299E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.543558E+11 | 0.140734E+11 | 0.321093E+11 | 0.154738E+11 | 0.166355E+11 | 0.00 | 0.00 |
Minimum of Months | 0.297006E+10 | 0.182120E+09 | 0.138062E+10 | 12868750.53 | 0.121299E+10 | 0.00 | 0.00 |
Maximum of Months | 0.646412E+10 | 0.261895E+10 | 0.440437E+10 | 0.314108E+10 | 0.156698E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.182016E+10 | 0.180504E+10 | 0.139056E+10 | 0.751936E+09 | 0.638626E+09 | 0.00 | 0.00 |
February | 0.194366E+10 | 0.135530E+10 | 0.142206E+10 | 0.719756E+09 | 0.702306E+09 | 0.00 | 0.00 |
March | 0.220950E+10 | 0.126315E+10 | 0.155176E+10 | 0.686921E+09 | 0.864837E+09 | 0.00 | 0.00 |
April | 0.298520E+10 | 0.785982E+09 | 0.186515E+10 | 0.858000E+09 | 0.100715E+10 | 0.00 | 0.00 |
May | 0.309396E+10 | 0.231632E+09 | 0.160280E+10 | 0.522112E+09 | 0.108069E+10 | 0.00 | 0.00 |
June | 0.337866E+10 | 0.201309E+09 | 0.172309E+10 | 0.604193E+09 | 0.111890E+10 | 0.00 | 0.00 |
July | 0.319455E+10 | 0.145765E+09 | 0.162529E+10 | 0.450827E+09 | 0.117446E+10 | 0.00 | 0.00 |
August | 0.321093E+10 | 0.223317E+09 | 0.164337E+10 | 0.503055E+09 | 0.114032E+10 | 0.00 | 0.00 |
September | 0.271193E+10 | 0.304050E+09 | 0.146445E+10 | 0.502374E+09 | 0.962076E+09 | 0.00 | 0.00 |
October | 0.275269E+10 | 0.572739E+09 | 0.154927E+10 | 0.669420E+09 | 0.879852E+09 | 0.00 | 0.00 |
November | 0.189703E+10 | 0.118524E+10 | 0.128507E+10 | 0.645824E+09 | 0.639251E+09 | 0.00 | 0.00 |
December | 0.175155E+10 | 0.157123E+10 | 0.127733E+10 | 0.679267E+09 | 0.598068E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.309498E+11 | 0.964476E+10 | 0.184002E+11 | 0.759368E+10 | 0.108065E+11 | 0.00 | 0.00 |
Minimum of Months | 0.175155E+10 | 0.145765E+09 | 0.127733E+10 | 0.450827E+09 | 0.598068E+09 | 0.00 | 0.00 |
Maximum of Months | 0.337866E+10 | 0.180504E+10 | 0.186515E+10 | 0.858000E+09 | 0.117446E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.587063E+09 | 0.266626E+10 | 0.761979E+09 | 0.00 | 0.761979E+09 | 0.00 | 0.00 |
February | 0.718406E+09 | 0.201608E+10 | 0.811956E+09 | 0.00 | 0.811956E+09 | 0.00 | 0.00 |
March | 0.113003E+10 | 0.190503E+10 | 0.104286E+10 | 0.00 | 0.104286E+10 | 0.00 | 0.00 |
April | 0.167552E+10 | 0.115998E+10 | 0.119110E+10 | 4888705.04 | 0.118621E+10 | 0.00 | 0.00 |
May | 0.285438E+10 | 0.338318E+09 | 0.139412E+10 | 50993845.67 | 0.134313E+10 | 0.00 | 0.00 |
June | 0.326151E+10 | 0.281640E+09 | 0.153427E+10 | 0.106237E+09 | 0.142804E+10 | 0.00 | 0.00 |
July | 0.324489E+10 | 0.196707E+09 | 0.153854E+10 | 58615712.59 | 0.147993E+10 | 0.00 | 0.00 |
August | 0.293003E+10 | 0.276441E+09 | 0.137779E+10 | 10836527.32 | 0.136696E+10 | 0.00 | 0.00 |
September | 0.225844E+10 | 0.382435E+09 | 0.115171E+10 | 88704.64 | 0.115163E+10 | 0.00 | 0.00 |
October | 0.188650E+10 | 0.764215E+09 | 0.103418E+10 | 0.00 | 0.103418E+10 | 0.00 | 0.00 |
November | 0.852728E+09 | 0.167105E+10 | 0.759779E+09 | 0.00 | 0.759779E+09 | 0.00 | 0.00 |
December | 0.625601E+09 | 0.228173E+10 | 0.708346E+09 | 0.00 | 0.708346E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.220251E+11 | 0.139399E+11 | 0.133067E+11 | 0.231660E+09 | 0.130750E+11 | 0.00 | 0.00 |
Minimum of Months | 0.587063E+09 | 0.196707E+09 | 0.708346E+09 | 0.00 | 0.708346E+09 | 0.00 | 0.00 |
Maximum of Months | 0.326151E+10 | 0.266626E+10 | 0.153854E+10 | 0.106237E+09 | 0.147993E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.158816E+10 | 0.163897E+10 | 0.130735E+10 | 0.665704E+09 | 0.641643E+09 | 0.00 | 0.00 |
February | 0.168469E+10 | 0.124673E+10 | 0.131489E+10 | 0.634794E+09 | 0.680100E+09 | 0.00 | 0.00 |
March | 0.236240E+10 | 0.119105E+10 | 0.171247E+10 | 0.825875E+09 | 0.886595E+09 | 0.00 | 0.00 |
April | 0.283103E+10 | 0.753815E+09 | 0.181862E+10 | 0.822507E+09 | 0.996108E+09 | 0.00 | 0.00 |
May | 0.359724E+10 | 0.226372E+09 | 0.193699E+10 | 0.839912E+09 | 0.109707E+10 | 0.00 | 0.00 |
June | 0.365262E+10 | 0.187756E+09 | 0.190106E+10 | 0.753906E+09 | 0.114716E+10 | 0.00 | 0.00 |
July | 0.364406E+10 | 0.129218E+09 | 0.189399E+10 | 0.693097E+09 | 0.120089E+10 | 0.00 | 0.00 |
August | 0.336252E+10 | 0.184663E+09 | 0.174525E+10 | 0.600030E+09 | 0.114522E+10 | 0.00 | 0.00 |
September | 0.274896E+10 | 0.251902E+09 | 0.149610E+10 | 0.514354E+09 | 0.981751E+09 | 0.00 | 0.00 |
October | 0.267167E+10 | 0.493234E+09 | 0.152774E+10 | 0.644700E+09 | 0.883041E+09 | 0.00 | 0.00 |
November | 0.184768E+10 | 0.104127E+10 | 0.130896E+10 | 0.667751E+09 | 0.641211E+09 | 0.00 | 0.00 |
December | 0.134932E+10 | 0.143828E+10 | 0.106496E+10 | 0.482400E+09 | 0.582556E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.313403E+11 | 0.878325E+10 | 0.190284E+11 | 0.814503E+10 | 0.108834E+11 | 0.00 | 0.00 |
Minimum of Months | 0.134932E+10 | 0.129218E+09 | 0.106496E+10 | 0.482400E+09 | 0.582556E+09 | 0.00 | 0.00 |
Maximum of Months | 0.365262E+10 | 0.163897E+10 | 0.193699E+10 | 0.839912E+09 | 0.120089E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.634197E+10 | 0.249882E+10 | 0.440433E+10 | 0.314104E+10 | 0.126328E+10 | 0.00 | 0.00 |
February | 0.531306E+10 | 0.193146E+10 | 0.360791E+10 | 0.233534E+10 | 0.127258E+10 | 0.00 | 0.00 |
March | 0.386990E+10 | 0.188531E+10 | 0.255016E+10 | 0.115089E+10 | 0.139927E+10 | 0.00 | 0.00 |
April | 0.306363E+10 | 0.120250E+10 | 0.182918E+10 | 0.428620E+09 | 0.140056E+10 | 0.00 | 0.00 |
May | 0.298937E+10 | 0.347978E+09 | 0.144421E+10 | 61376736.89 | 0.138284E+10 | 0.00 | 0.00 |
June | 0.294693E+10 | 0.289804E+09 | 0.138062E+10 | 12868600.70 | 0.136775E+10 | 0.00 | 0.00 |
July | 0.316824E+10 | 0.191698E+09 | 0.149346E+10 | 27449430.67 | 0.146601E+10 | 0.00 | 0.00 |
August | 0.373613E+10 | 0.289216E+09 | 0.175697E+10 | 0.210889E+09 | 0.154608E+10 | 0.00 | 0.00 |
September | 0.400038E+10 | 0.406409E+09 | 0.204007E+10 | 0.537642E+09 | 0.150242E+10 | 0.00 | 0.00 |
October | 0.589250E+10 | 0.800969E+09 | 0.327068E+10 | 0.170371E+10 | 0.156697E+10 | 0.00 | 0.00 |
November | 0.628038E+10 | 0.163065E+10 | 0.402789E+10 | 0.277324E+10 | 0.125465E+10 | 0.00 | 0.00 |
December | 0.643333E+10 | 0.221164E+10 | 0.430356E+10 | 0.309058E+10 | 0.121298E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.540358E+11 | 0.136865E+11 | 0.321090E+11 | 0.154737E+11 | 0.166354E+11 | 0.00 | 0.00 |
Minimum of Months | 0.294693E+10 | 0.191698E+09 | 0.138062E+10 | 12868600.70 | 0.121298E+10 | 0.00 | 0.00 |
Maximum of Months | 0.643333E+10 | 0.249882E+10 | 0.440433E+10 | 0.314104E+10 | 0.156697E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.182130E+10 | 0.173521E+10 | 0.139057E+10 | 0.751943E+09 | 0.638629E+09 | 0.00 | 0.00 |
February | 0.193062E+10 | 0.132757E+10 | 0.142207E+10 | 0.719764E+09 | 0.702310E+09 | 0.00 | 0.00 |
March | 0.218354E+10 | 0.126110E+10 | 0.155177E+10 | 0.686928E+09 | 0.864841E+09 | 0.00 | 0.00 |
April | 0.295034E+10 | 0.802310E+09 | 0.186517E+10 | 0.858009E+09 | 0.100716E+10 | 0.00 | 0.00 |
May | 0.306904E+10 | 0.249821E+09 | 0.160281E+10 | 0.522117E+09 | 0.108069E+10 | 0.00 | 0.00 |
June | 0.335960E+10 | 0.211017E+09 | 0.172310E+10 | 0.604199E+09 | 0.111890E+10 | 0.00 | 0.00 |
July | 0.318715E+10 | 0.144605E+09 | 0.162530E+10 | 0.450831E+09 | 0.117447E+10 | 0.00 | 0.00 |
August | 0.321959E+10 | 0.203316E+09 | 0.164338E+10 | 0.503060E+09 | 0.114032E+10 | 0.00 | 0.00 |
September | 0.272083E+10 | 0.273559E+09 | 0.146446E+10 | 0.502379E+09 | 0.962082E+09 | 0.00 | 0.00 |
October | 0.276203E+10 | 0.534384E+09 | 0.154928E+10 | 0.669427E+09 | 0.879857E+09 | 0.00 | 0.00 |
November | 0.191177E+10 | 0.111389E+10 | 0.128508E+10 | 0.645830E+09 | 0.639254E+09 | 0.00 | 0.00 |
December | 0.176079E+10 | 0.148867E+10 | 0.127734E+10 | 0.679273E+09 | 0.598072E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.308766E+11 | 0.934546E+10 | 0.184003E+11 | 0.759376E+10 | 0.108066E+11 | 0.00 | 0.00 |
Minimum of Months | 0.176079E+10 | 0.144605E+09 | 0.127734E+10 | 0.450831E+09 | 0.598072E+09 | 0.00 | 0.00 |
Maximum of Months | 0.335960E+10 | 0.173521E+10 | 0.186517E+10 | 0.858009E+09 | 0.117447E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.434373E+10 | -0.364133E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -702405182.2 | 58.99 | 0.00 | 0.00 |
February | 0.391541E+10 | -0.328269E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -632723238.8 | 58.98 | 0.00 | 0.00 |
March | 0.443589E+10 | -0.373659E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -699308847.2 | 58.98 | 0.00 | 0.00 |
April | 0.382577E+10 | -0.315635E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669414572.5 | 58.98 | 0.00 | 0.00 |
May | 0.383823E+10 | -0.314854E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689690443.5 | 58.98 | 0.00 | 0.00 |
June | 0.360097E+10 | -0.293264E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668326516.0 | 58.98 | 0.00 | 0.00 |
July | 0.336361E+10 | -0.267426E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689350479.4 | 58.98 | 0.00 | 0.00 |
August | 0.368039E+10 | -0.299022E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690174544.0 | 58.98 | 0.00 | 0.00 |
September | 0.349978E+10 | -0.283164E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668134859.3 | 58.98 | 0.00 | 0.00 |
October | 0.382871E+10 | -0.313887E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689840895.2 | 58.98 | 0.00 | 0.00 |
November | 0.398283E+10 | -0.331197E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -670859015.8 | 58.98 | 0.00 | 0.00 |
December | 0.415384E+10 | -0.345529E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -698553868.6 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.464692E+11 | -0.383004E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.816878E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.336361E+10 | -0.373659E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -702405182.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.443589E+10 | -0.267426E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -632723238.8 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 6955.26 | 36.26 | 297.00 | 293.00 | 1255.73 | 24.66 | 146.83 | 273.33 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2950.26 | 26.50 | 165.33 | 276.17 | 1036.41 | 19.98 | 65.67 | 254.00 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1330.83 | 17.10 | 0.00 | 311.00 | 788.58 | 19.84 | 48.50 | 269.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:00 | 1044.61 | 16.33 | 0.00 | 314.33 | 608.21 | 19.00 | 22.33 | 268.17 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 929.30 | 16.50 | 0.00 | 338.00 | 526.81 | 19.23 | 8.00 | 279.17 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:19 | 880.60 | 16.13 | 0.00 | 338.17 | 501.92 | 18.86 | 2.50 | 281.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:10 | 977.23 | 16.51 | 0.00 | 349.00 | 540.23 | 19.22 | 13.50 | 293.67 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1142.89 | 16.86 | 0.00 | 339.17 | 620.38 | 19.53 | 38.67 | 293.17 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:30 | 1353.53 | 17.03 | 0.00 | 309.17 | 725.40 | 19.73 | 80.67 | 269.33 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2319.63 | 19.91 | 39.33 | 309.83 | 992.19 | 20.96 | 138.17 | 277.17 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:30 | 7020.98 | 35.66 | 296.00 | 284.00 | 1123.20 | 22.26 | 102.67 | 263.67 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 7084.97 | 37.06 | 279.17 | 281.33 | 1606.76 | 26.63 | 144.33 | 262.00 |
Annual Sum or Average | 4027.67 | 0.51 | 2644.97 | 22.00 | 1076.83 | 3743.17 | 830.23 | 20.65 | 811.83 | 3284.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 880.60 | 16.13 | 0.00 | 276.17 | 501.92 | 18.86 | 2.50 | 254.00 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 7084.97 | 37.06 | 297.00 | 349.00 | 1606.76 | 26.63 | 146.83 | 293.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-07:49 | 1660.07 | 18.52 | 81.33 | 252.00 | 930.93 | 21.68 | 72.33 | 189.83 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 1831.23 | 18.43 | 71.83 | 244.83 | 1012.52 | 21.71 | 64.17 | 202.67 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1940.14 | 19.00 | 74.33 | 301.67 | 1015.20 | 20.37 | 47.83 | 244.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-07:19 | 1963.24 | 17.50 | 76.50 | 311.00 | 1074.03 | 20.78 | 68.00 | 270.33 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2290.98 | 19.96 | 105.83 | 345.67 | 900.53 | 19.83 | 49.17 | 290.50 |
June | 394.00 | 0.51 | 0.48 | 01-JUN-06:19 | 2044.85 | 19.41 | 113.67 | 345.50 | 848.90 | 19.61 | 54.00 | 295.67 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 1971.91 | 19.69 | 112.00 | 354.50 | 841.04 | 19.85 | 53.67 | 295.00 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:49 | 1806.90 | 19.40 | 102.50 | 337.67 | 946.35 | 21.15 | 75.50 | 289.67 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-06:49 | 1701.35 | 18.25 | 80.50 | 301.83 | 885.84 | 21.07 | 66.00 | 258.33 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-06:49 | 1782.42 | 19.05 | 79.00 | 289.50 | 904.94 | 20.43 | 48.50 | 248.83 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-07:00 | 1494.52 | 19.15 | 81.67 | 246.50 | 769.01 | 20.57 | 55.50 | 203.17 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1568.70 | 18.70 | 75.83 | 235.50 | 869.49 | 21.38 | 61.67 | 180.00 |
Annual Sum or Average | 4027.67 | 0.52 | 1850.93 | 18.95 | 1055.00 | 3566.17 | 914.85 | 20.66 | 716.33 | 2968.17 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1494.52 | 17.50 | 71.83 | 235.50 | 769.01 | 19.61 | 47.83 | 180.00 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2290.98 | 19.96 | 113.67 | 354.50 | 1074.03 | 21.71 | 75.50 | 295.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.57 | 0.48 | 01-JAN-09:39 | 435.34 | 12.94 | 0.00 | 218.67 | 286.35 | 16.03 | 0.00 | 83.17 |
February | 295.50 | 0.54 | 0.48 | 01-FEB-11:00 | 502.42 | 14.14 | 0.00 | 228.67 | 331.48 | 17.16 | 0.00 | 138.83 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:00 | 592.23 | 15.31 | 0.00 | 290.17 | 376.50 | 18.10 | 0.00 | 189.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:09 | 710.28 | 15.87 | 0.00 | 319.17 | 436.60 | 18.53 | 0.00 | 260.83 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:10 | 879.57 | 17.00 | 0.00 | 358.50 | 509.80 | 19.84 | 12.67 | 305.33 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:30 | 1024.61 | 17.03 | 0.50 | 365.67 | 554.98 | 22.22 | 97.17 | 330.50 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 1008.72 | 18.12 | 23.17 | 368.83 | 551.29 | 20.76 | 66.50 | 326.67 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 880.18 | 16.66 | 0.00 | 345.50 | 498.44 | 19.32 | 2.67 | 299.50 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:40 | 733.86 | 15.80 | 0.00 | 306.17 | 425.39 | 18.44 | 0.00 | 236.17 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-08:09 | 624.60 | 15.43 | 0.00 | 285.50 | 386.89 | 18.27 | 0.00 | 211.33 |
November | 308.00 | 0.56 | 0.48 | 01-NOV-10:20 | 446.73 | 13.49 | 0.00 | 215.33 | 295.65 | 16.60 | 0.00 | 97.50 |
December | 282.83 | 0.56 | 0.48 | 01-DEC-09:30 | 435.02 | 13.15 | 0.00 | 210.33 | 288.11 | 16.32 | 0.00 | 70.83 |
Annual Sum or Average | 4027.67 | 0.53 | 711.45 | 15.57 | 23.67 | 3512.50 | 421.74 | 18.64 | 179.00 | 2549.83 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 435.02 | 12.94 | 0.00 | 210.33 | 286.35 | 16.03 | 0.00 | 70.83 | |
Maximum of Months | 394.00 | 0.57 | 0.48 | 1024.61 | 18.12 | 23.17 | 368.83 | 554.98 | 22.22 | 97.17 | 330.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-09:39 | 1860.55 | 18.76 | 83.83 | 255.00 | 1104.03 | 22.41 | 81.50 | 197.33 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 1723.34 | 19.26 | 79.00 | 251.17 | 897.84 | 20.45 | 51.17 | 213.50 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1835.76 | 18.19 | 68.83 | 297.00 | 984.53 | 21.07 | 56.67 | 240.50 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:39 | 2059.85 | 17.96 | 82.00 | 313.67 | 1116.35 | 19.48 | 53.00 | 273.83 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-08:09 | 1746.93 | 13.36 | 0.00 | 342.33 | 762.90 | 17.27 | 0.00 | 289.67 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:30 | 1849.80 | 13.28 | 0.00 | 346.00 | 774.99 | 17.11 | 0.00 | 294.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:30 | 1705.32 | 13.84 | 3.67 | 353.67 | 748.22 | 17.39 | 0.00 | 298.00 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:00 | 1759.96 | 16.45 | 59.00 | 338.83 | 803.14 | 17.67 | 5.50 | 290.17 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-08:09 | 1612.38 | 18.27 | 80.00 | 301.83 | 839.46 | 19.79 | 51.67 | 259.17 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:20 | 2110.65 | 21.06 | 105.50 | 296.50 | 865.14 | 21.03 | 53.50 | 251.33 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-10:09 | 1653.63 | 18.70 | 80.00 | 251.50 | 919.80 | 21.54 | 66.67 | 202.17 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-09:30 | 1771.62 | 19.96 | 85.00 | 254.83 | 997.82 | 22.93 | 74.00 | 189.00 |
Annual Sum or Average | 4027.67 | 0.52 | 1807.62 | 17.21 | 726.83 | 3602.33 | 892.54 | 19.64 | 493.67 | 2999.50 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1612.38 | 13.28 | 0.00 | 251.17 | 748.22 | 17.11 | 0.00 | 189.00 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2110.65 | 21.06 | 105.50 | 353.67 | 1116.35 | 22.93 | 81.50 | 298.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 6830.19 | 36.04 | 297.00 | 292.67 | 1159.53 | 22.22 | 92.17 | 272.17 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2828.86 | 24.54 | 165.17 | 273.33 | 996.63 | 19.35 | 36.33 | 259.33 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1254.97 | 13.52 | 0.00 | 309.00 | 735.64 | 17.56 | 0.00 | 262.17 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 994.25 | 12.95 | 0.00 | 311.67 | 576.87 | 16.82 | 0.00 | 264.50 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 888.75 | 12.99 | 0.00 | 333.67 | 503.91 | 16.93 | 0.00 | 273.00 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:19 | 842.93 | 12.63 | 0.00 | 334.33 | 481.04 | 16.54 | 0.00 | 273.33 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:10 | 934.91 | 12.90 | 0.00 | 347.00 | 516.41 | 16.79 | 0.00 | 285.67 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1090.54 | 13.28 | 0.00 | 337.33 | 589.39 | 17.12 | 0.00 | 287.33 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:40 | 1286.82 | 13.38 | 0.00 | 307.67 | 683.85 | 17.23 | 0.00 | 264.17 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2218.98 | 16.53 | 39.33 | 308.00 | 922.39 | 18.37 | 5.67 | 273.50 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:39 | 6900.21 | 35.28 | 293.83 | 283.00 | 1034.65 | 19.53 | 46.00 | 261.67 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 6900.80 | 35.18 | 263.33 | 277.00 | 1503.48 | 24.39 | 110.83 | 259.50 |
Annual Sum or Average | 4027.67 | 0.52 | 2564.23 | 19.20 | 1058.67 | 3714.67 | 780.82 | 18.38 | 291.00 | 3236.33 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 842.93 | 12.63 | 0.00 | 273.33 | 481.04 | 16.54 | 0.00 | 259.33 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 6900.80 | 36.04 | 297.00 | 347.00 | 1503.48 | 24.39 | 110.83 | 287.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-07:49 | 1611.38 | 18.09 | 81.33 | 246.33 | 894.00 | 21.47 | 72.33 | 187.17 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 1779.27 | 17.98 | 71.83 | 241.00 | 974.06 | 21.51 | 64.33 | 199.67 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1880.02 | 18.58 | 74.33 | 298.50 | 964.82 | 20.17 | 47.83 | 239.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 1898.84 | 17.09 | 76.50 | 308.33 | 1028.86 | 20.61 | 68.00 | 266.17 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2223.41 | 19.57 | 105.83 | 343.17 | 853.19 | 19.67 | 49.17 | 286.50 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:19 | 1990.92 | 19.03 | 113.67 | 343.17 | 805.88 | 19.45 | 54.00 | 289.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 1910.79 | 19.17 | 110.33 | 350.83 | 798.46 | 19.68 | 53.67 | 290.50 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1713.92 | 17.52 | 83.50 | 333.67 | 905.86 | 20.98 | 75.50 | 286.17 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-06:49 | 1650.16 | 17.82 | 80.50 | 299.67 | 846.99 | 20.88 | 66.17 | 252.83 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:49 | 1723.70 | 18.61 | 79.00 | 286.83 | 862.26 | 20.22 | 48.50 | 245.17 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-07:00 | 1445.58 | 18.71 | 81.67 | 243.00 | 732.68 | 20.35 | 55.50 | 198.67 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1526.17 | 18.26 | 75.83 | 232.50 | 837.03 | 21.16 | 61.67 | 175.17 |
Annual Sum or Average | 4027.67 | 0.52 | 1791.62 | 18.38 | 1034.33 | 3527.00 | 873.44 | 20.47 | 716.67 | 2917.17 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1445.58 | 17.09 | 71.83 | 232.50 | 732.68 | 19.45 | 47.83 | 175.17 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2223.41 | 19.57 | 113.67 | 350.83 | 1028.86 | 21.51 | 75.50 | 290.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.57 | 0.48 | 01-JAN-09:50 | 416.55 | 9.64 | 0.00 | 208.33 | 276.73 | 13.83 | 0.00 | 71.17 |
February | 295.50 | 0.55 | 0.48 | 01-FEB-11:00 | 481.06 | 10.88 | 0.00 | 221.33 | 320.58 | 15.07 | 0.00 | 128.33 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:00 | 567.70 | 12.16 | 0.00 | 285.83 | 363.85 | 16.21 | 0.00 | 176.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 680.86 | 12.66 | 0.00 | 316.00 | 421.14 | 16.58 | 0.00 | 252.17 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 841.32 | 13.42 | 0.00 | 355.33 | 492.92 | 18.84 | 27.50 | 301.17 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:30 | 982.19 | 13.36 | 0.00 | 364.33 | 531.01 | 20.25 | 59.17 | 326.33 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 963.83 | 13.37 | 0.00 | 365.17 | 527.26 | 18.53 | 24.50 | 321.00 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 842.46 | 13.16 | 0.00 | 344.17 | 477.74 | 17.06 | 0.00 | 294.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:40 | 702.84 | 12.41 | 0.00 | 303.17 | 408.68 | 16.26 | 0.00 | 225.50 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-08:20 | 597.83 | 12.15 | 0.00 | 281.33 | 372.84 | 16.20 | 0.00 | 200.33 |
November | 308.00 | 0.56 | 0.48 | 01-NOV-10:20 | 427.42 | 10.13 | 0.00 | 207.17 | 285.76 | 14.39 | 0.00 | 82.67 |
December | 282.83 | 0.56 | 0.48 | 01-DEC-10:09 | 415.85 | 9.77 | 0.00 | 200.33 | 278.28 | 14.05 | 0.00 | 56.33 |
Annual Sum or Average | 4027.67 | 0.53 | 681.04 | 12.05 | 0.00 | 3452.50 | 405.81 | 16.62 | 111.17 | 2435.33 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 415.85 | 9.64 | 0.00 | 200.33 | 276.73 | 13.83 | 0.00 | 56.33 | |
Maximum of Months | 394.00 | 0.57 | 0.48 | 982.19 | 13.42 | 0.00 | 365.17 | 531.01 | 20.25 | 59.17 | 326.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-09:39 | 1812.65 | 18.41 | 83.83 | 251.67 | 1066.45 | 22.31 | 81.50 | 191.67 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 1662.50 | 18.91 | 79.00 | 248.17 | 853.88 | 20.33 | 51.17 | 207.67 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1781.89 | 17.79 | 68.83 | 293.00 | 940.66 | 20.94 | 56.67 | 235.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:50 | 1996.11 | 17.57 | 82.00 | 310.00 | 1069.83 | 19.32 | 53.00 | 269.33 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-08:09 | 1687.50 | 12.86 | 0.00 | 338.50 | 725.28 | 17.06 | 0.00 | 284.00 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:40 | 1797.31 | 12.80 | 0.00 | 342.83 | 736.58 | 16.90 | 0.00 | 291.33 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:30 | 1649.94 | 13.35 | 3.67 | 350.33 | 711.78 | 17.18 | 0.00 | 292.50 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:00 | 1698.65 | 16.02 | 59.00 | 335.83 | 764.20 | 17.48 | 5.50 | 286.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-08:09 | 1560.99 | 17.67 | 77.00 | 299.33 | 801.48 | 19.64 | 51.67 | 254.00 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:30 | 1970.28 | 18.90 | 84.00 | 292.67 | 822.30 | 20.90 | 53.50 | 247.83 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-10:09 | 1604.67 | 18.32 | 80.00 | 247.00 | 883.50 | 21.43 | 66.67 | 196.00 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-09:39 | 1721.60 | 19.62 | 85.00 | 249.17 | 958.31 | 22.84 | 74.00 | 184.83 |
Annual Sum or Average | 4027.67 | 0.52 | 1745.41 | 16.63 | 702.33 | 3558.50 | 852.65 | 19.49 | 493.67 | 2940.33 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1560.99 | 12.80 | 0.00 | 247.00 | 711.78 | 16.90 | 0.00 | 184.83 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 1996.11 | 19.62 | 85.00 | 350.33 | 1069.83 | 22.84 | 81.50 | 292.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.51 | 0.48 | 01-JAN-07:49 | 6830.18 | 36.04 | 297.00 | 292.67 | 1159.47 | 22.22 | 92.17 | 272.17 |
February | 295.50 | 0.51 | 0.48 | 01-FEB-11:39 | 2828.82 | 24.54 | 165.17 | 273.33 | 996.57 | 19.35 | 36.33 | 259.33 |
March | 296.00 | 0.51 | 0.48 | 02-MAR-12:39 | 1254.93 | 13.52 | 0.00 | 309.00 | 735.59 | 17.56 | 0.00 | 262.17 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 994.21 | 12.95 | 0.00 | 311.67 | 576.84 | 16.82 | 0.00 | 264.50 |
May | 353.67 | 0.52 | 0.48 | 01-MAY-07:40 | 888.72 | 12.99 | 0.00 | 333.67 | 503.88 | 16.93 | 0.00 | 273.00 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:19 | 842.90 | 12.63 | 0.00 | 334.33 | 481.01 | 16.54 | 0.00 | 273.33 |
July | 390.00 | 0.52 | 0.48 | 01-JUL-07:10 | 934.88 | 12.90 | 0.00 | 347.00 | 516.38 | 16.79 | 0.00 | 285.67 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:30 | 1090.49 | 13.28 | 0.00 | 337.33 | 589.35 | 17.12 | 0.00 | 287.33 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:40 | 1286.75 | 13.38 | 0.00 | 307.67 | 683.80 | 17.23 | 0.00 | 264.17 |
October | 330.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2218.92 | 16.54 | 39.33 | 308.00 | 922.32 | 18.37 | 5.67 | 273.50 |
November | 308.00 | 0.51 | 0.48 | 01-NOV-08:39 | 6900.19 | 35.28 | 293.83 | 283.00 | 1034.59 | 19.53 | 46.00 | 261.67 |
December | 282.83 | 0.50 | 0.48 | 01-DEC-07:49 | 6900.79 | 35.18 | 263.33 | 277.00 | 1503.42 | 24.39 | 110.83 | 259.50 |
Annual Sum or Average | 4027.67 | 0.52 | 2564.19 | 19.20 | 1058.67 | 3714.67 | 780.77 | 18.38 | 291.00 | 3236.33 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 842.90 | 12.63 | 0.00 | 273.33 | 481.01 | 16.54 | 0.00 | 259.33 | |
Maximum of Months | 394.00 | 0.53 | 0.48 | 6900.79 | 36.04 | 297.00 | 347.00 | 1503.42 | 24.39 | 110.83 | 287.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-07:49 | 1611.39 | 18.09 | 81.33 | 246.33 | 893.97 | 21.47 | 72.33 | 187.17 |
February | 295.50 | 0.53 | 0.48 | 01-FEB-11:39 | 1779.27 | 17.98 | 71.83 | 241.00 | 974.03 | 21.51 | 64.33 | 199.67 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1880.01 | 18.58 | 74.33 | 298.50 | 964.79 | 20.17 | 47.83 | 239.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-07:19 | 1898.82 | 17.09 | 76.50 | 308.33 | 1028.82 | 20.61 | 68.00 | 266.17 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-06:40 | 2223.39 | 19.57 | 105.83 | 343.17 | 853.14 | 19.67 | 49.17 | 286.50 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-06:19 | 1990.89 | 19.03 | 113.67 | 343.17 | 805.84 | 19.45 | 54.00 | 289.83 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-06:30 | 1910.75 | 19.17 | 110.33 | 350.83 | 798.41 | 19.69 | 53.67 | 290.50 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-06:00 | 1713.89 | 17.52 | 83.50 | 333.67 | 905.81 | 20.98 | 75.50 | 286.17 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-06:49 | 1650.13 | 17.82 | 80.50 | 299.67 | 846.94 | 20.88 | 66.17 | 252.83 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-06:49 | 1723.69 | 18.61 | 79.00 | 286.83 | 862.22 | 20.22 | 48.50 | 245.17 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-07:00 | 1445.58 | 18.72 | 81.67 | 243.00 | 732.65 | 20.35 | 55.50 | 198.67 |
December | 282.83 | 0.54 | 0.48 | 01-DEC-07:49 | 1526.18 | 18.26 | 75.83 | 232.67 | 837.00 | 21.16 | 61.67 | 175.17 |
Annual Sum or Average | 4027.67 | 0.52 | 1791.61 | 18.38 | 1034.33 | 3527.17 | 873.40 | 20.47 | 716.67 | 2917.17 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1445.58 | 17.09 | 71.83 | 232.67 | 732.65 | 19.45 | 47.83 | 175.17 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 2223.39 | 19.57 | 113.67 | 350.83 | 1028.82 | 21.51 | 75.50 | 290.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.57 | 0.48 | 01-JAN-09:50 | 416.55 | 9.64 | 0.00 | 208.33 | 276.72 | 13.83 | 0.00 | 71.17 |
February | 295.50 | 0.55 | 0.48 | 01-FEB-11:00 | 481.06 | 10.88 | 0.00 | 221.33 | 320.56 | 15.07 | 0.00 | 128.33 |
March | 296.00 | 0.53 | 0.48 | 02-MAR-12:00 | 567.70 | 12.16 | 0.00 | 285.83 | 363.84 | 16.21 | 0.00 | 176.33 |
April | 347.33 | 0.53 | 0.48 | 01-APR-08:09 | 680.85 | 12.66 | 0.00 | 316.00 | 421.12 | 16.58 | 0.00 | 252.17 |
May | 353.67 | 0.50 | 0.48 | 01-MAY-07:19 | 841.30 | 13.42 | 0.00 | 355.33 | 492.89 | 18.85 | 27.50 | 300.83 |
June | 394.00 | 0.50 | 0.48 | 01-JUN-06:30 | 982.16 | 13.36 | 0.00 | 364.33 | 530.97 | 20.25 | 59.17 | 326.17 |
July | 390.00 | 0.50 | 0.48 | 01-JUL-06:49 | 963.80 | 13.37 | 0.00 | 365.17 | 527.22 | 18.53 | 24.50 | 321.00 |
August | 380.83 | 0.51 | 0.48 | 01-AUG-07:19 | 842.44 | 13.16 | 0.00 | 344.17 | 477.70 | 17.06 | 0.00 | 293.83 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-07:40 | 702.82 | 12.42 | 0.00 | 303.17 | 408.65 | 16.26 | 0.00 | 225.50 |
October | 330.00 | 0.52 | 0.48 | 01-OCT-08:20 | 597.83 | 12.15 | 0.00 | 281.33 | 372.82 | 16.20 | 0.00 | 200.33 |
November | 308.00 | 0.56 | 0.48 | 01-NOV-10:20 | 427.42 | 10.13 | 0.00 | 207.17 | 285.75 | 14.39 | 0.00 | 82.50 |
December | 282.83 | 0.56 | 0.48 | 01-DEC-10:09 | 415.86 | 9.77 | 0.00 | 200.33 | 278.26 | 14.06 | 0.00 | 56.33 |
Annual Sum or Average | 4027.67 | 0.53 | 681.03 | 12.06 | 0.00 | 3452.50 | 405.79 | 16.62 | 111.17 | 2434.50 | ||
Minimum of Months | 282.83 | 0.50 | 0.48 | 415.86 | 9.64 | 0.00 | 200.33 | 276.72 | 13.83 | 0.00 | 56.33 | |
Maximum of Months | 394.00 | 0.57 | 0.48 | 982.16 | 13.42 | 0.00 | 365.17 | 530.97 | 20.25 | 59.17 | 326.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.54 | 0.48 | 01-JAN-09:39 | 1812.65 | 18.41 | 83.83 | 251.67 | 1066.42 | 22.31 | 81.50 | 191.67 |
February | 295.50 | 0.52 | 0.48 | 01-FEB-11:50 | 1662.50 | 18.91 | 79.00 | 248.17 | 853.85 | 20.33 | 51.17 | 207.67 |
March | 296.00 | 0.52 | 0.48 | 02-MAR-12:39 | 1781.88 | 17.79 | 68.83 | 293.00 | 940.62 | 20.94 | 56.67 | 235.17 |
April | 347.33 | 0.52 | 0.48 | 01-APR-08:50 | 1996.09 | 17.58 | 82.00 | 310.00 | 1069.79 | 19.32 | 53.00 | 269.33 |
May | 353.67 | 0.51 | 0.48 | 01-MAY-08:09 | 1687.47 | 12.86 | 0.00 | 338.50 | 725.23 | 17.06 | 0.00 | 284.00 |
June | 394.00 | 0.52 | 0.48 | 01-JUN-07:40 | 1797.28 | 12.80 | 0.00 | 342.83 | 736.53 | 16.90 | 0.00 | 291.33 |
July | 390.00 | 0.51 | 0.48 | 01-JUL-07:30 | 1649.89 | 13.35 | 3.67 | 350.33 | 711.73 | 17.18 | 0.00 | 292.50 |
August | 380.83 | 0.52 | 0.48 | 01-AUG-07:00 | 1698.61 | 16.02 | 59.00 | 335.83 | 764.15 | 17.48 | 5.50 | 286.00 |
September | 342.17 | 0.52 | 0.48 | 01-SEP-08:09 | 1560.96 | 17.67 | 77.00 | 299.33 | 801.43 | 19.64 | 51.67 | 254.00 |
October | 330.00 | 0.51 | 0.48 | 01-OCT-08:30 | 1970.27 | 18.90 | 84.00 | 292.67 | 822.26 | 20.91 | 53.50 | 247.67 |
November | 308.00 | 0.53 | 0.48 | 01-NOV-10:09 | 1604.67 | 18.32 | 80.00 | 247.00 | 883.47 | 21.43 | 66.67 | 196.00 |
December | 282.83 | 0.52 | 0.48 | 01-DEC-09:39 | 1721.60 | 19.62 | 85.00 | 249.17 | 958.29 | 22.84 | 74.00 | 184.83 |
Annual Sum or Average | 4027.67 | 0.52 | 1745.39 | 16.63 | 702.33 | 3558.50 | 852.61 | 19.49 | 493.67 | 2940.17 | ||
Minimum of Months | 282.83 | 0.51 | 0.48 | 1560.96 | 12.80 | 0.00 | 247.00 | 711.73 | 16.90 | 0.00 | 184.83 | |
Maximum of Months | 394.00 | 0.54 | 0.48 | 1996.09 | 19.62 | 85.00 | 350.33 | 1069.79 | 22.84 | 81.50 | 292.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.788985E+09 | 6769.15 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.505557E+09 | 6769.15 | 03-FEB-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.796982E+09 | 6769.15 | 02-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162511E+09 | 6769.15 | 03-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24667585.37 | 4835.77 | 27-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207255E+09 | 6769.15 | 09-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.686799E+09 | 6769.15 | 01-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.796982E+09 | 6769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 30911976.93 | 4520.10 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20825564.64 | 4520.10 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51049914.07 | 4520.10 | 10-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27437386.86 | 4520.10 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130225E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51049914.07 | 4520.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142874E+09 | 6802.48 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107418E+09 | 6802.48 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107869E+09 | 6802.48 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61109077.65 | 6802.48 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142874E+09 | 6802.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 49683399.34 | 4499.10 | 05-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 38566916.16 | 4499.10 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 59607420.88 | 4499.10 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 26876498.77 | 4499.10 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59607420.88 | 4499.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9850067.90 | 24172.87 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 25280493.84 | 24172.87 | 13-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35130561.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25280493.84 | 24172.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 91133371.94 | 7841.23 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43321706.89 | 7841.23 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80571859.31 | 7841.23 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 61621151.50 | 7841.23 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91133371.94 | 7841.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.144968E+09 | 5201.75 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57488379.17 | 5201.75 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82395794.84 | 5201.75 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 477896.35 | 3384.40 | 16-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118795E+09 | 5201.75 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.404125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.144968E+09 | 5201.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.271530E+09 | 7881.01 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127002E+09 | 7881.01 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107303E+09 | 7881.01 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2323333.13 | 4853.63 | 16-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170301E+09 | 7881.01 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.678459E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.271530E+09 | 7881.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.204742E+09 | 5181.68 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 97942664.27 | 5181.68 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94979163.09 | 5181.68 | 09-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3519060.15 | 4715.29 | 16-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135418E+09 | 5181.68 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.204742E+09 | 5181.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.626588E+09 | 25420.98 | 04-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358070E+09 | 25420.98 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.298702E+09 | 25420.98 | 10-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8070015.94 | 16617.58 | 16-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.444474E+09 | 25420.98 | 20-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.626588E+09 | 25420.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.394340E+09 | 10749.26 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.207489E+09 | 10749.26 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.267869E+09 | 10749.26 | 03-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4738644.57 | 7330.16 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3029218.83 | 2577.88 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20781075.34 | 10749.26 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299519E+09 | 10749.26 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.394340E+09 | 10749.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.452004E+09 | 7059.48 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.210193E+09 | 7059.48 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216399E+09 | 7059.48 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3747847.08 | 7059.48 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3549096.00 | 3818.55 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30492862.70 | 7059.48 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.370965E+09 | 7059.48 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.452004E+09 | 7059.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.959781E+09 | 10665.06 | 12-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.465160E+09 | 10670.07 | 10-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350136E+09 | 10628.64 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6896196.15 | 9431.07 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7726843.88 | 3974.78 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 71447940.66 | 10663.95 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.624363E+09 | 10642.53 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.959781E+09 | 10670.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.685715E+09 | 7039.73 | 03-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.337644E+09 | 7039.73 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.299697E+09 | 7039.73 | 03-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8726482.50 | 7039.73 | 11-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9822206.10 | 3985.97 | 28-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74704498.93 | 7039.73 | 13-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.484325E+09 | 7039.73 | 04-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.685715E+09 | 7039.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 25489297.07 | 3315.81 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5778346.39 | 1965.45 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5422982.05 | 1648.54 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18185431.38 | 3061.37 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54876056.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25489297.07 | 3315.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1141148.23 | 2784.48 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 459848.22 | 2125.97 | 17-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 214015.43 | 2409.90 | 09-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 391360.43 | 2348.42 | 21-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2206372.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1141148.23 | 2784.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182466E+09 | 6590.39 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57869365.55 | 5555.11 | 17-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39399257.44 | 5379.94 | 09-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132935E+09 | 6628.59 | 21-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182466E+09 | 6628.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.197542E+11 | 0.136737E+11 | 64473.87 | 19-JAN-13:10 | 39903.42 | 0.00 |
February | 0.00 | 0.00 | 0.269705E+11 | 0.175205E+11 | 64212.81 | 24-FEB-13:05 | 43192.81 | 0.00 |
March | 0.00 | 0.00 | 0.321711E+11 | 0.219851E+11 | 69013.55 | 28-MAR-12:00 | 43874.24 | 0.00 |
April | 0.00 | 0.00 | 0.503481E+11 | 0.356531E+11 | 80927.15 | 28-APR-16:00 | 54056.08 | 0.00 |
May | 0.00 | 0.00 | 0.871696E+11 | 0.587983E+11 | 126029.28 | 22-MAY-04:02 | 75843.41 | 0.00 |
June | 0.00 | 0.00 | 0.930379E+11 | 0.622549E+11 | 92862.33 | 05-JUN-12:03 | 57605.28 | 0.00 |
July | 0.00 | 0.00 | 0.973146E+11 | 0.623885E+11 | 103698.21 | 05-JUL-12:02 | 64985.69 | 0.00 |
August | 0.00 | 0.00 | 0.104073E+12 | 0.680603E+11 | 99282.42 | 07-AUG-12:02 | 61186.53 | 0.00 |
September | 0.00 | 0.00 | 0.888251E+11 | 0.575601E+11 | 100212.23 | 05-SEP-12:02 | 61600.54 | 0.00 |
October | 0.00 | 0.00 | 0.793325E+11 | 0.547156E+11 | 102324.92 | 06-OCT-12:02 | 60695.87 | 0.00 |
November | 0.00 | 0.00 | 0.443175E+11 | 0.313881E+11 | 86533.89 | 07-NOV-13:05 | 52737.30 | 0.00 |
December | 0.00 | 0.00 | 0.289957E+11 | 0.197585E+11 | 75691.76 | 14-DEC-13:05 | 46757.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.752310E+12 | 0.503757E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.197542E+11 | 0.136737E+11 | 64212.81 | 39903.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104073E+12 | 0.680603E+11 | 126029.28 | 75843.41 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.162951E+11 | 0.113807E+11 | 49839.80 | 19-JAN-16:30 | 33740.82 | 0.00 |
February | 0.00 | 0.00 | 0.226962E+11 | 0.151400E+11 | 50494.64 | 27-FEB-16:50 | 35995.34 | 0.00 |
March | 0.00 | 0.00 | 0.268076E+11 | 0.190916E+11 | 49682.75 | 07-MAR-14:50 | 29840.15 | 0.00 |
April | 0.00 | 0.00 | 0.413694E+11 | 0.303378E+11 | 58485.51 | 28-APR-16:00 | 44364.94 | 0.00 |
May | 0.00 | 0.00 | 0.641176E+11 | 0.485528E+11 | 94851.15 | 22-MAY-04:02 | 66387.14 | 0.00 |
June | 0.00 | 0.00 | 0.660738E+11 | 0.503615E+11 | 68138.52 | 17-JUN-05:03 | 62565.96 | 0.00 |
July | 0.00 | 0.00 | 0.676900E+11 | 0.499763E+11 | 73967.83 | 03-JUL-04:02 | 66933.72 | 0.00 |
August | 0.00 | 0.00 | 0.703787E+11 | 0.518606E+11 | 76270.40 | 16-AUG-05:03 | 57832.02 | 0.00 |
September | 0.00 | 0.00 | 0.628236E+11 | 0.445448E+11 | 85544.97 | 05-SEP-04:02 | 67053.88 | 0.00 |
October | 0.00 | 0.00 | 0.563432E+11 | 0.423119E+11 | 76324.45 | 07-OCT-05:03 | 63468.39 | 0.00 |
November | 0.00 | 0.00 | 0.336737E+11 | 0.245011E+11 | 57446.67 | 02-NOV-15:20 | 44323.17 | 0.00 |
December | 0.00 | 0.00 | 0.228246E+11 | 0.159222E+11 | 53024.32 | 12-DEC-16:30 | 33119.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.551094E+12 | 0.403981E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.162951E+11 | 0.113807E+11 | 49682.75 | 29840.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.703787E+11 | 0.518606E+11 | 94851.15 | 67053.88 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.176413E+11 | 0.120001E+11 | 59518.08 | 19-JAN-15:00 | 39894.02 | 0.00 |
February | 0.00 | 0.00 | 0.250743E+11 | 0.165114E+11 | 58712.61 | 27-FEB-15:30 | 44181.65 | 0.00 |
March | 0.00 | 0.00 | 0.302603E+11 | 0.208773E+11 | 59658.49 | 29-MAR-15:00 | 43854.44 | 0.00 |
April | 0.00 | 0.00 | 0.482131E+11 | 0.342385E+11 | 86432.40 | 28-APR-16:00 | 59825.95 | 0.00 |
May | 0.00 | 0.00 | 0.842371E+11 | 0.574644E+11 | 109328.77 | 22-MAY-04:02 | 78982.82 | 0.00 |
June | 0.00 | 0.00 | 0.901944E+11 | 0.610618E+11 | 91053.47 | 28-JUN-14:30 | 63318.16 | 0.00 |
July | 0.00 | 0.00 | 0.932513E+11 | 0.600485E+11 | 93598.54 | 05-JUL-13:50 | 63776.74 | 0.00 |
August | 0.00 | 0.00 | 0.949687E+11 | 0.614301E+11 | 91693.47 | 14-AUG-13:30 | 60385.09 | 0.00 |
September | 0.00 | 0.00 | 0.795184E+11 | 0.504011E+11 | 89245.00 | 11-SEP-14:00 | 60884.25 | 0.00 |
October | 0.00 | 0.00 | 0.706756E+11 | 0.477227E+11 | 96034.15 | 06-OCT-14:00 | 60386.44 | 0.00 |
November | 0.00 | 0.00 | 0.379570E+11 | 0.258109E+11 | 79985.68 | 02-NOV-14:00 | 54187.03 | 0.00 |
December | 0.00 | 0.00 | 0.255460E+11 | 0.170079E+11 | 65510.38 | 15-DEC-15:00 | 50405.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.697538E+12 | 0.464575E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.176413E+11 | 0.120001E+11 | 58712.61 | 39894.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.949687E+11 | 0.614301E+11 | 109328.77 | 78982.82 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1513.57 | 5214.15 | 23-JAN-12:07 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1510.33 | 5206.27 | 03-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1552.24 | 5068.34 | 01-MAR-12:05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1370.93 | 4781.90 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1331.62 | 4503.80 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1288.90 | 4198.76 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1151.19 | 4009.41 | 05-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1274.15 | 4082.72 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1246.05 | 4314.65 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1325.64 | 4637.53 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1432.58 | 4930.33 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1442.45 | 5150.01 | 26-DEC-12:09 |
Annual Sum or Average | 0.00 | 1369.21 | ||||
Minimum of Months | 0.00 | 0.00 | 1151.19 | 4009.41 | ||
Maximum of Months | 0.00 | 0.00 | 1552.24 | 5214.15 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153621E+10 | 0.29 | 5396.54 | 02-JAN-05:03 | 1.21 |
February | 0.143085E+10 | 0.29 | 4044.14 | 03-FEB-06:03 | 1.01 |
March | 0.171165E+10 | 0.31 | 4044.14 | 01-MAR-06:03 | 1.01 |
April | 0.189484E+10 | 0.32 | 4044.14 | 06-APR-05:03 | 1.01 |
May | 0.301115E+10 | 0.40 | 9070.52 | 22-MAY-04:02 | 1.66 |
June | 0.322829E+10 | 0.43 | 6923.45 | 05-JUN-04:03 | 1.41 |
July | 0.331712E+10 | 0.42 | 10093.52 | 03-JUL-04:02 | 1.78 |
August | 0.381514E+10 | 0.46 | 10093.52 | 07-AUG-04:02 | 1.79 |
September | 0.313244E+10 | 0.42 | 10093.52 | 05-SEP-04:02 | 1.78 |
October | 0.323146E+10 | 0.41 | 10093.52 | 10-OCT-04:02 | 1.79 |
November | 0.211860E+10 | 0.34 | 5288.71 | 03-NOV-05:03 | 1.19 |
December | 0.172394E+10 | 0.30 | 4425.16 | 16-DEC-06:03 | 1.06 |
Annual Sum or Average | 0.301517E+11 | 0.37 | |||
Minimum of Months | 0.143085E+10 | 0.29 | 4044.14 | 1.01 | |
Maximum of Months | 0.381514E+10 | 0.46 | 10093.52 | 1.79 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135549E+10 | 0.29 | 2288.68 | 02-JAN-06:03 | 0.80 |
February | 0.127664E+10 | 0.30 | 2498.33 | 27-FEB-15:30 | 0.85 |
March | 0.149375E+10 | 0.32 | 2141.83 | 29-MAR-15:20 | 0.78 |
April | 0.167174E+10 | 0.33 | 3407.49 | 28-APR-05:03 | 1.01 |
May | 0.261656E+10 | 0.41 | 8446.37 | 30-MAY-04:02 | 1.79 |
June | 0.275268E+10 | 0.43 | 8446.37 | 05-JUN-04:03 | 1.78 |
July | 0.272786E+10 | 0.41 | 8446.37 | 03-JUL-04:02 | 1.78 |
August | 0.289341E+10 | 0.43 | 8446.37 | 05-AUG-05:03 | 1.78 |
September | 0.238225E+10 | 0.39 | 8446.37 | 05-SEP-04:02 | 1.78 |
October | 0.251000E+10 | 0.39 | 8446.37 | 07-OCT-05:03 | 1.78 |
November | 0.163680E+10 | 0.32 | 3382.74 | 06-NOV-16:00 | 1.01 |
December | 0.143658E+10 | 0.30 | 2821.26 | 15-DEC-15:40 | 0.91 |
Annual Sum or Average | 0.247538E+11 | 0.36 | |||
Minimum of Months | 0.127664E+10 | 0.29 | 2141.83 | 0.78 | |
Maximum of Months | 0.289341E+10 | 0.43 | 8446.37 | 1.79 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134733E+10 | 0.28 | 2127.61 | 19-JAN-15:30 | 0.71 |
February | 0.128158E+10 | 0.29 | 2419.62 | 27-FEB-15:40 | 0.76 |
March | 0.150851E+10 | 0.30 | 2227.22 | 29-MAR-15:20 | 0.73 |
April | 0.169831E+10 | 0.31 | 3566.23 | 28-APR-15:30 | 0.94 |
May | 0.265932E+10 | 0.38 | 9960.69 | 22-MAY-04:02 | 1.78 |
June | 0.283070E+10 | 0.41 | 8021.59 | 05-JUN-04:03 | 1.55 |
July | 0.276336E+10 | 0.39 | 9960.69 | 03-JUL-04:02 | 1.78 |
August | 0.289722E+10 | 0.40 | 9960.69 | 07-AUG-04:02 | 1.78 |
September | 0.231120E+10 | 0.37 | 9872.85 | 11-SEP-04:02 | 1.77 |
October | 0.239902E+10 | 0.36 | 5512.33 | 07-OCT-05:03 | 1.23 |
November | 0.156101E+10 | 0.30 | 3335.26 | 02-NOV-15:00 | 0.91 |
December | 0.141447E+10 | 0.28 | 2779.74 | 15-DEC-15:10 | 0.82 |
Annual Sum or Average | 0.246721E+11 | 0.34 | |||
Minimum of Months | 0.128158E+10 | 0.28 | 2127.61 | 0.71 | |
Maximum of Months | 0.289722E+10 | 0.41 | 9960.69 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:10 | 0.22 | 0.22 | 56.99 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:03 | 0.22 | 0.22 | 56.94 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:03 | 0.22 | 0.22 | 57.17 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:03 | 0.22 | 0.22 | 56.69 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 56.57 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 57.19 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 56.93 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 57.07 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 56.95 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.97 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 56.94 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:02 | 0.22 | 0.22 | 56.16 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 56.16 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.97 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.09 | 57.09 | 1513.57 | 5214.15 | 23-JAN-12:07 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.30 | 57.30 | 1510.33 | 5206.27 | 03-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.51 | 57.51 | 1552.24 | 5068.34 | 01-MAR-12:05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.87 | 57.87 | 1370.93 | 4781.90 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.77 | 56.77 | 1331.62 | 4503.80 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.42 | 57.42 | 1288.90 | 4198.76 | 02-JUN-11:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.14 | 57.14 | 1151.19 | 4009.41 | 05-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.28 | 57.28 | 1274.15 | 4082.72 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.17 | 57.17 | 1246.05 | 4314.65 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.43 | 56.43 | 1325.64 | 4637.53 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.92 | 57.92 | 1432.58 | 4930.33 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.46 | 56.46 | 1442.45 | 5150.01 | 26-DEC-12:09 |
Annual Sum or Average | 0.00 | 1369.21 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.43 | 56.43 | 1151.19 | 4009.41 | ||
Maximum of Months | 0.00 | 0.00 | 57.92 | 57.92 | 1552.24 | 5214.15 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.742410E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.871629E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.106578E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.144514E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.251832E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.271877E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.283344E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.304341E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.251401E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.230941E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.131863E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.964510E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.223455E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.742410E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.304341E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.609295E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.717632E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.849550E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.118735E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.191602E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.200929E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.204892E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.211960E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.181066E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.167539E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.995438E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.753563E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.166927E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.609295E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.211960E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.885962E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.905328E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.104456E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.136737E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.240873E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.260086E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.266465E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.270886E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.220020E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.200975E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.111685E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.996322E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.209094E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.885962E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.270886E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153621E+10 | 0.197542E+11 | 0.103794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143085E+10 | 0.269705E+11 | 0.678145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171165E+10 | 0.321711E+11 | 0.102093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189484E+10 | 0.503481E+11 | 0.162511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.301115E+10 | 0.871696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.322829E+10 | 0.930379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.331712E+10 | 0.973146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.381514E+10 | 0.104073E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.313244E+10 | 0.888251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323146E+10 | 0.793325E+11 | 24667585.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211860E+10 | 0.443175E+11 | 0.207255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172394E+10 | 0.289957E+11 | 0.820407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301517E+11 | 0.752310E+12 | 0.395186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143085E+10 | 0.197542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.381514E+10 | 0.104073E+12 | 0.103794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135549E+10 | 0.162951E+11 | 0.713514E+09 | 0.116500E+09 | 0.523097E+09 | 0.00 | 0.00 | 0.00 |
February | 0.127664E+10 | 0.226962E+11 | 0.336065E+09 | 38700908.27 | 0.886787E+09 | 0.00 | 0.00 | 0.00 |
March | 0.149375E+10 | 0.268076E+11 | 0.390744E+09 | 28062973.78 | 0.160901E+10 | 0.00 | 0.00 | 0.00 |
April | 0.167174E+10 | 0.413694E+11 | 0.00 | 0.00 | 0.357563E+10 | 0.00 | 0.00 | 0.00 |
May | 0.261656E+10 | 0.641176E+11 | 0.00 | 0.00 | 0.148374E+11 | 0.00 | 0.00 | 0.00 |
June | 0.275268E+10 | 0.660738E+11 | 0.00 | 0.00 | 0.179558E+11 | 0.00 | 0.00 | 0.00 |
July | 0.272786E+10 | 0.676900E+11 | 0.00 | 0.00 | 0.195812E+11 | 0.00 | 0.00 | 0.00 |
August | 0.289341E+10 | 0.703787E+11 | 0.00 | 0.00 | 0.192653E+11 | 0.00 | 0.00 | 0.00 |
September | 0.238225E+10 | 0.628236E+11 | 0.00 | 0.00 | 0.130572E+11 | 0.00 | 0.00 | 0.00 |
October | 0.251000E+10 | 0.563432E+11 | 0.00 | 0.00 | 0.110249E+11 | 0.00 | 0.00 | 0.00 |
November | 0.163680E+10 | 0.336737E+11 | 6320289.63 | 0.00 | 0.293192E+10 | 0.00 | 0.00 | 0.00 |
December | 0.143658E+10 | 0.228246E+11 | 0.486527E+09 | 0.105945E+09 | 0.162911E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247538E+11 | 0.551094E+12 | 0.193317E+10 | 0.289209E+09 | 0.106877E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127664E+10 | 0.162951E+11 | 0.00 | 0.00 | 0.523097E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.289341E+10 | 0.703787E+11 | 0.713514E+09 | 0.116500E+09 | 0.195812E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134733E+10 | 0.176413E+11 | 0.330090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128158E+10 | 0.250743E+11 | 0.163642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150851E+10 | 0.302603E+11 | 0.147220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169831E+10 | 0.482131E+11 | 24109170.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265932E+10 | 0.842371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.283070E+10 | 0.901944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.276336E+10 | 0.932513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.289722E+10 | 0.949687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231120E+10 | 0.795184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.239902E+10 | 0.706756E+11 | 24127364.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156101E+10 | 0.379570E+11 | 0.205496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141447E+10 | 0.255460E+11 | 0.235658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246721E+11 | 0.697538E+12 | 0.901984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128158E+10 | 0.176413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.289722E+10 | 0.949687E+11 | 0.330090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153621E+10 | 0.00 | 0.00 | 0.00 | 0.487543E+10 | 0.101245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143085E+10 | 0.00 | 0.00 | 0.00 | 0.661308E+10 | 0.672367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171165E+10 | 0.00 | 0.00 | 0.00 | 0.793067E+10 | 0.101551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189484E+10 | 0.00 | 0.00 | 0.00 | 0.123941E+11 | 0.162511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.301115E+10 | 0.00 | 0.00 | 0.00 | 0.221721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.322829E+10 | 0.00 | 0.00 | 0.00 | 0.239594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.331712E+10 | 0.00 | 0.00 | 0.00 | 0.250173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.381514E+10 | 0.00 | 0.00 | 0.00 | 0.266189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.313244E+10 | 0.00 | 0.00 | 0.00 | 0.220077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.323146E+10 | 0.00 | 0.00 | 0.00 | 0.198379E+11 | 24667585.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211860E+10 | 0.00 | 0.00 | 0.00 | 0.108604E+11 | 0.207255E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172394E+10 | 0.00 | 0.00 | 0.00 | 0.711894E+10 | 0.802222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.301517E+11 | 0.00 | 0.00 | 0.00 | 0.189406E+12 | 0.389698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143085E+10 | 0.00 | 0.00 | 0.00 | 0.487543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.381514E+10 | 0.00 | 0.00 | 0.00 | 0.266189E+11 | 0.101551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135549E+10 | 0.00 | 0.00 | 0.00 | 0.402508E+10 | 0.712373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127664E+10 | 0.00 | 0.00 | 0.00 | 0.556407E+10 | 0.335605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149375E+10 | 0.00 | 0.00 | 0.00 | 0.661122E+10 | 0.390530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167174E+10 | 0.00 | 0.00 | 0.00 | 0.102017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.261656E+10 | 0.00 | 0.00 | 0.00 | 0.165436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.275268E+10 | 0.00 | 0.00 | 0.00 | 0.173402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.272786E+10 | 0.00 | 0.00 | 0.00 | 0.177614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.289341E+10 | 0.00 | 0.00 | 0.00 | 0.183026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238225E+10 | 0.00 | 0.00 | 0.00 | 0.157244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251000E+10 | 0.00 | 0.00 | 0.00 | 0.142439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163680E+10 | 0.00 | 0.00 | 0.00 | 0.831125E+10 | 6320289.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143658E+10 | 0.00 | 0.00 | 0.00 | 0.561292E+10 | 0.486135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247538E+11 | 0.00 | 0.00 | 0.00 | 0.140242E+12 | 0.193096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127664E+10 | 0.00 | 0.00 | 0.00 | 0.402508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.289341E+10 | 0.00 | 0.00 | 0.00 | 0.183026E+11 | 0.712373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134733E+10 | 0.00 | 0.00 | 0.00 | 0.439386E+10 | 0.311843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128158E+10 | 0.00 | 0.00 | 0.00 | 0.619314E+10 | 0.157856E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150851E+10 | 0.00 | 0.00 | 0.00 | 0.750434E+10 | 0.143280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.169831E+10 | 0.00 | 0.00 | 0.00 | 0.119513E+11 | 24109170.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265932E+10 | 0.00 | 0.00 | 0.00 | 0.214280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.283070E+10 | 0.00 | 0.00 | 0.00 | 0.231779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.276336E+10 | 0.00 | 0.00 | 0.00 | 0.238831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.289722E+10 | 0.00 | 0.00 | 0.00 | 0.241914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231120E+10 | 0.00 | 0.00 | 0.00 | 0.196908E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.239902E+10 | 0.00 | 0.00 | 0.00 | 0.176743E+11 | 24127364.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156101E+10 | 0.00 | 0.00 | 0.00 | 0.940197E+10 | 0.205496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141447E+10 | 0.00 | 0.00 | 0.00 | 0.632510E+10 | 0.222365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246721E+11 | 0.00 | 0.00 | 0.00 | 0.175815E+12 | 0.860717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128158E+10 | 0.00 | 0.00 | 0.00 | 0.439386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.289722E+10 | 0.00 | 0.00 | 0.00 | 0.241914E+11 | 0.311843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.342329E+10 | 0.140993E+10 | 0.00 | 20908733.93 | 53893948.29 | 0.00 | 0.840064E+10 | 0.00 | 0.50 |
February | 0.180251E+10 | 0.179162E+10 | 0.00 | 13906132.33 | 0.106854E+09 | 0.00 | 0.465643E+10 | 0.00 | 0.49 |
March | 0.160385E+10 | 0.281629E+10 | 0.00 | 19446659.48 | 0.112440E+09 | 0.00 | 0.715205E+10 | 0.00 | 0.56 |
April | 0.345247E+09 | 0.513379E+10 | 0.00 | 8771264.31 | 0.176411E+09 | 0.00 | 0.179198E+10 | 0.00 | 0.44 |
May | 0.00 | 0.133203E+11 | 0.00 | 0.00 | 0.309639E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.144333E+11 | 0.00 | 0.00 | 0.319099E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.155200E+11 | 0.00 | 0.00 | 0.518767E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.154756E+11 | 0.00 | 0.00 | 0.338173E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.126771E+11 | 0.00 | 0.00 | 0.443236E+09 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 0.266930E+09 | 0.938360E+10 | 0.00 | 8017771.73 | 0.305079E+09 | 0.00 | 0.186553E+10 | 0.00 | 0.38 |
November | 0.865954E+09 | 0.372097E+10 | 0.00 | 19806858.04 | 58489346.75 | 0.00 | 0.514715E+10 | 0.00 | 0.56 |
December | 0.250891E+10 | 0.275643E+10 | 0.00 | 20545863.31 | 0.107573E+09 | 0.00 | 0.750960E+10 | 0.00 | 0.51 |
Annual Sum or Average | 0.108167E+11 | 0.984389E+11 | 0.00 | 0.111403E+09 | 0.284965E+10 | 0.00 | 0.365234E+11 | 0.00 | 0.41 |
Minimum of Months | 0.00 | 0.140993E+10 | 0.00 | 0.00 | 53893948.29 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.342329E+10 | 0.155200E+11 | 0.00 | 20908733.93 | 0.518767E+09 | 0.00 | 0.840064E+10 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.763914E+10 | 0.535180E+09 | 0.00 | 1871867.49 | 0.517173E+09 | 0.00 | 0.115076E+10 | 0.00 | 0.39 |
February | 0.418036E+10 | 0.690397E+09 | 0.00 | 914121.02 | 0.541860E+09 | 607863.08 | 0.680000E+09 | 0.00 | 0.39 |
March | 0.444400E+10 | 0.108499E+10 | 0.00 | 2818770.54 | 0.631538E+09 | 641839.65 | 0.197639E+10 | 0.00 | 0.43 |
April | 0.823280E+09 | 0.210892E+10 | 0.00 | 2912717.41 | 0.808475E+09 | 0.00 | 0.749438E+09 | 0.00 | 0.34 |
May | 0.00 | 0.526897E+10 | 0.00 | 0.00 | 0.192171E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.549327E+10 | 0.00 | 0.00 | 0.117615E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.616162E+10 | 0.00 | 0.00 | 0.251580E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.649091E+10 | 0.00 | 0.00 | 0.129431E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.623156E+10 | 0.00 | 0.00 | 0.347363E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.516616E+09 | 0.409777E+10 | 0.00 | 3537879.08 | 0.269272E+09 | 0.00 | 0.100509E+10 | 0.00 | 0.31 |
November | 0.228819E+10 | 0.175871E+10 | 0.00 | 4410885.32 | 0.431879E+09 | 0.00 | 0.169486E+10 | 0.00 | 0.40 |
December | 0.597697E+10 | 0.121580E+10 | 0.00 | 1640759.62 | 0.629149E+09 | 0.00 | 0.116302E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.258685E+11 | 0.411381E+11 | 0.00 | 18107000.49 | 0.486751E+10 | 1249702.73 | 0.841956E+10 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.535180E+09 | 0.00 | 0.00 | 0.117615E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.763914E+10 | 0.649091E+10 | 0.00 | 4410885.32 | 0.808475E+09 | 641839.65 | 0.197639E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.774354E+10 | 0.489249E+09 | 0.00 | 367238.95 | 0.853015E+09 | 94652612.56 | 0.467301E+09 | 0.00 | 0.40 |
February | 0.419080E+10 | 0.771368E+09 | 0.00 | 254504.12 | 0.969694E+09 | 60255977.36 | 0.317065E+09 | 0.00 | 0.38 |
March | 0.512432E+10 | 0.148988E+10 | 0.00 | 1064855.42 | 0.973199E+09 | 30124213.30 | 0.916259E+09 | 0.00 | 0.43 |
April | 0.102799E+10 | 0.313217E+10 | 0.00 | 2175128.70 | 0.133405E+10 | 0.00 | 0.540424E+09 | 0.00 | 0.34 |
May | 0.00 | 0.114509E+11 | 0.00 | 0.00 | 0.437308E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.128952E+11 | 0.00 | 0.00 | 0.346912E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.142376E+11 | 0.00 | 0.00 | 0.666363E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.144932E+11 | 0.00 | 0.00 | 0.420003E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.108573E+11 | 0.00 | 0.00 | 0.144638E+10 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.587242E+09 | 0.839810E+10 | 0.00 | 2367570.52 | 0.669394E+09 | 0.00 | 0.727762E+09 | 0.00 | 0.30 |
November | 0.266314E+10 | 0.235651E+10 | 0.00 | 2073061.72 | 0.120169E+10 | 723533.77 | 0.900093E+09 | 0.00 | 0.40 |
December | 0.632217E+10 | 0.134586E+10 | 74424.02 | 359102.28 | 0.123485E+10 | 57473046.06 | 0.236345E+09 | 19193.37 | 0.39 |
Annual Sum or Average | 0.276592E+11 | 0.819172E+11 | 74424.02 | 8661461.71 | 0.105529E+11 | 0.243229E+09 | 0.410525E+10 | 19193.37 | 0.33 |
Minimum of Months | 0.00 | 0.489249E+09 | 0.00 | 0.00 | 0.346912E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.774354E+10 | 0.144932E+11 | 74424.02 | 2367570.52 | 0.144638E+10 | 94652612.56 | 0.916259E+09 | 19193.37 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136455E+10 | 0.130379E+09 | 95135.13 | 17075.74 | 0.164924E+09 | 0.388031E+09 | 4702600.29 | 501.28 | 0.40 |
February | 0.786728E+09 | 0.182729E+09 | 4739.74 | 14944.28 | 0.208013E+09 | 0.148490E+09 | 32034356.36 | 6342.02 | 0.39 |
March | 0.105931E+10 | 0.400925E+09 | 0.00 | 193741.41 | 0.194136E+09 | 0.144594E+09 | 77659159.55 | 0.00 | 0.45 |
April | 0.236127E+09 | 0.899974E+09 | 0.00 | 604288.24 | 0.240561E+09 | 817224.78 | 0.103984E+09 | 0.00 | 0.39 |
May | 0.00 | 0.352328E+10 | 0.00 | 0.00 | 42733938.42 | 0.00 | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.429451E+10 | 0.00 | 0.00 | 41952979.50 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.474654E+10 | 0.00 | 0.00 | 59358400.89 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.453920E+10 | 0.00 | 0.00 | 53428864.14 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.323315E+10 | 0.00 | 0.00 | 0.172540E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 0.156991E+09 | 0.240396E+10 | 0.00 | 452202.85 | 0.113383E+09 | 399908.12 | 0.126188E+09 | 0.00 | 0.36 |
November | 0.627653E+09 | 0.633289E+09 | 841574.90 | 330196.04 | 0.212466E+09 | 15478722.27 | 0.108942E+09 | 10964.83 | 0.42 |
December | 0.113110E+10 | 0.340075E+09 | 1079997.61 | 32991.03 | 0.248716E+09 | 0.260555E+09 | 7278445.83 | 18968.33 | 0.40 |
Annual Sum or Average | 0.536246E+10 | 0.253280E+11 | 2021447.38 | 1645439.59 | 0.175221E+10 | 0.958366E+09 | 0.460789E+09 | 36776.47 | 0.39 |
Minimum of Months | 0.00 | 0.130379E+09 | 0.00 | 0.00 | 41952979.50 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.136455E+10 | 0.474654E+10 | 1079997.61 | 604288.24 | 0.248716E+09 | 0.388031E+09 | 0.126188E+09 | 18968.33 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119167E+10 | 0.131019E+09 | 75647.22 | 27077.84 | 0.117988E+09 | 0.183282E+09 | 34397271.94 | 1039.50 | 0.51 |
February | 0.630684E+09 | 0.219707E+09 | 3444.95 | 149994.25 | 0.129315E+09 | 61559573.00 | 83832818.92 | 4683.91 | 0.51 |
March | 0.665962E+09 | 0.464700E+09 | 0.00 | 777812.43 | 0.104040E+09 | 93473568.48 | 0.292322E+09 | 0.00 | 0.61 |
April | 0.121576E+09 | 0.933519E+09 | 0.00 | 1009139.65 | 0.153538E+09 | 659325.31 | 0.228331E+09 | 0.00 | 0.59 |
May | 0.00 | 0.301097E+10 | 0.00 | 0.00 | 37141613.53 | 0.00 | 0.00 | 0.00 | 0.50 |
June | 0.00 | 0.354615E+10 | 0.00 | 0.00 | 32855868.31 | 0.00 | 0.00 | 0.00 | 0.53 |
July | 0.00 | 0.397007E+10 | 0.00 | 0.00 | 56860681.26 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.373854E+10 | 0.00 | 0.00 | 53311477.01 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.265868E+10 | 0.00 | 0.00 | 0.171329E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.111630E+09 | 0.207774E+10 | 0.00 | 480383.70 | 99747932.47 | 320669.06 | 0.122426E+09 | 0.00 | 0.49 |
November | 0.406966E+09 | 0.576205E+09 | 383647.17 | 644873.03 | 0.151221E+09 | 3552947.89 | 0.205580E+09 | 5920.87 | 0.55 |
December | 0.913424E+09 | 0.297343E+09 | 384781.84 | 124928.02 | 0.168812E+09 | 0.153041E+09 | 56478315.41 | 9636.21 | 0.50 |
Annual Sum or Average | 0.404191E+10 | 0.216246E+11 | 847521.18 | 3214208.93 | 0.127616E+10 | 0.495889E+09 | 0.102337E+10 | 21280.48 | 0.52 |
Minimum of Months | 0.00 | 0.131019E+09 | 0.00 | 0.00 | 32855868.31 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.119167E+10 | 0.397007E+10 | 384781.84 | 1009139.65 | 0.171329E+09 | 0.183282E+09 | 0.292322E+09 | 9636.21 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.819074E+09 | 0.368130E+09 | 0.00 | 3835895.87 | 94096891.41 | 0.184119E+09 | 0.141127E+10 | 0.00 | 0.59 |
February | 0.473607E+09 | 0.590495E+09 | 4166.22 | 2186504.21 | 0.112338E+09 | 74356126.05 | 0.711623E+09 | 2647.83 | 0.57 |
March | 0.759814E+09 | 0.690611E+09 | 0.00 | 2092082.34 | 0.118310E+09 | 0.123141E+09 | 0.660481E+09 | 0.00 | 0.58 |
April | 0.190273E+09 | 0.116249E+10 | 0.00 | 1209558.52 | 0.212109E+09 | 409966.35 | 0.215567E+09 | 0.00 | 0.47 |
May | 0.00 | 0.357028E+10 | 0.00 | 0.00 | 47347954.70 | 0.00 | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.411288E+10 | 0.00 | 0.00 | 50044236.23 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.467444E+10 | 0.00 | 0.00 | 69552018.49 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.497707E+10 | 0.00 | 0.00 | 57199019.75 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.405977E+10 | 0.00 | 0.00 | 0.135072E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.120095E+09 | 0.364072E+10 | 0.00 | 1215430.67 | 57041491.36 | 399716.95 | 0.264738E+09 | 0.00 | 0.55 |
November | 0.321389E+09 | 0.130047E+10 | 81814.54 | 3714034.70 | 0.118100E+09 | 4419165.26 | 0.918821E+09 | 5978.52 | 0.71 |
December | 0.761015E+09 | 0.905271E+09 | 247870.28 | 3734233.85 | 0.124550E+09 | 0.123314E+09 | 0.100961E+10 | 12038.72 | 0.63 |
Annual Sum or Average | 0.344527E+10 | 0.300526E+11 | 333851.03 | 17987740.17 | 0.119576E+10 | 0.510159E+09 | 0.519211E+10 | 20665.07 | 0.50 |
Minimum of Months | 0.00 | 0.368130E+09 | 0.00 | 0.00 | 47347954.70 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.819074E+09 | 0.497707E+10 | 247870.28 | 3835895.87 | 0.212109E+09 | 0.184119E+09 | 0.141127E+10 | 12038.72 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108674E+10 | 0.132605E+09 | 83945.23 | 371249.84 | 0.150745E+09 | 0.276697E+09 | 0.208323E+09 | 981.02 | 0.57 |
February | 0.629636E+09 | 0.208280E+09 | 3517.80 | 377366.16 | 0.178678E+09 | 0.110363E+09 | 0.133319E+09 | 4802.12 | 0.58 |
March | 0.778871E+09 | 0.323616E+09 | 0.00 | 1079791.96 | 0.184007E+09 | 0.122735E+09 | 0.327963E+09 | 0.00 | 0.68 |
April | 0.183918E+09 | 0.854929E+09 | 0.00 | 927927.08 | 0.237209E+09 | 536717.47 | 0.166152E+09 | 0.00 | 0.60 |
May | 0.00 | 0.272791E+10 | 0.00 | 0.00 | 83194550.70 | 0.00 | 0.00 | 0.00 | 0.46 |
June | 0.00 | 0.327244E+10 | 0.00 | 0.00 | 35560947.85 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.354840E+10 | 0.00 | 0.00 | 59732336.88 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.358300E+10 | 0.00 | 0.00 | 93503671.85 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.253517E+10 | 0.00 | 0.00 | 0.254540E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.154193E+09 | 0.197583E+10 | 0.00 | 477048.90 | 0.144757E+09 | 355123.11 | 0.110824E+09 | 0.00 | 0.51 |
November | 0.488864E+09 | 0.544733E+09 | 419012.06 | 749140.76 | 0.218923E+09 | 15821082.31 | 0.214347E+09 | 7931.69 | 0.62 |
December | 0.945683E+09 | 0.317857E+09 | 963839.96 | 404002.64 | 0.230971E+09 | 0.188388E+09 | 0.129822E+09 | 12187.10 | 0.58 |
Annual Sum or Average | 0.426791E+10 | 0.200248E+11 | 1470315.06 | 4386527.34 | 0.187182E+10 | 0.714896E+09 | 0.129075E+10 | 25901.94 | 0.54 |
Minimum of Months | 0.00 | 0.132605E+09 | 0.00 | 0.00 | 35560947.85 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.108674E+10 | 0.358300E+10 | 963839.96 | 1079791.96 | 0.254540E+09 | 0.276697E+09 | 0.327963E+09 | 12187.10 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.196360E+10 | 0.115287E+09 | 0.00 | 22612.29 | 0.118176E+09 | 45496122.47 | 64351053.62 | 0.00 | 0.41 |
February | 0.107704E+10 | 0.143122E+09 | 0.00 | 12746.03 | 0.150410E+09 | 35121242.08 | 37151208.60 | 0.00 | 0.40 |
March | 0.138731E+10 | 0.260198E+09 | 0.00 | 26205.13 | 0.211467E+09 | 37820982.24 | 22594553.46 | 0.00 | 0.44 |
April | 0.278471E+09 | 0.606316E+09 | 0.00 | 248901.27 | 0.291000E+09 | 0.00 | 49691738.97 | 0.00 | 0.33 |
May | 0.00 | 0.261120E+10 | 0.00 | 0.00 | 61402446.80 | 0.00 | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.320936E+10 | 0.00 | 0.00 | 48492987.22 | 0.00 | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.369977E+10 | 0.00 | 0.00 | 70292814.79 | 0.00 | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.372812E+10 | 0.00 | 0.00 | 45071116.78 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.281538E+10 | 0.00 | 0.00 | 60660464.12 | 0.00 | 0.00 | 0.00 | 0.28 |
October | 0.155857E+09 | 0.203285E+10 | 0.00 | 717578.31 | 60635454.47 | 0.00 | 0.186116E+09 | 0.00 | 0.34 |
November | 0.735184E+09 | 0.588187E+09 | 0.00 | 609648.06 | 71902500.49 | 0.00 | 0.205401E+09 | 0.00 | 0.42 |
December | 0.166212E+10 | 0.337754E+09 | 0.00 | 61175.33 | 0.143244E+09 | 14719294.96 | 20913524.26 | 0.00 | 0.41 |
Annual Sum or Average | 0.725958E+10 | 0.201475E+11 | 0.00 | 1698866.41 | 0.133275E+10 | 0.133158E+09 | 0.586219E+09 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.115287E+09 | 0.00 | 0.00 | 45071116.78 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.196360E+10 | 0.372812E+10 | 0.00 | 717578.31 | 0.291000E+09 | 45496122.47 | 0.205401E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119458E+10 | 0.132161E+09 | 0.00 | 256953.57 | 55262743.34 | 9932745.11 | 0.281618E+09 | 0.00 | 0.47 |
February | 0.655469E+09 | 0.172771E+09 | 0.00 | 239042.04 | 75020019.71 | 7621056.21 | 0.162354E+09 | 0.00 | 0.47 |
March | 0.771117E+09 | 0.361645E+09 | 0.00 | 733631.30 | 72197456.30 | 18821787.62 | 0.273374E+09 | 0.00 | 0.54 |
April | 0.122703E+09 | 0.745895E+09 | 0.00 | 807545.32 | 0.103025E+09 | 0.00 | 0.178848E+09 | 0.00 | 0.48 |
May | 0.00 | 0.233425E+10 | 0.00 | 0.00 | 34061110.85 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.273576E+10 | 0.00 | 0.00 | 31063936.59 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.316920E+10 | 0.00 | 0.00 | 46041955.32 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.308436E+10 | 0.00 | 0.00 | 29016285.69 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.232439E+10 | 0.00 | 0.00 | 39931160.55 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 86911463.80 | 0.176335E+10 | 0.00 | 756941.57 | 33133454.37 | 0.00 | 0.186696E+09 | 0.00 | 0.45 |
November | 0.353970E+09 | 0.520896E+09 | 0.00 | 1408591.68 | 33247706.63 | 0.00 | 0.397081E+09 | 0.00 | 0.55 |
December | 0.986631E+09 | 0.301310E+09 | 0.00 | 514609.79 | 68775337.57 | 8357883.72 | 0.233427E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.417138E+10 | 0.176460E+11 | 0.00 | 4717315.27 | 0.620776E+09 | 44733472.66 | 0.171340E+10 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.132161E+09 | 0.00 | 0.00 | 29016285.69 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.119458E+10 | 0.316920E+10 | 0.00 | 1408591.68 | 0.103025E+09 | 18821787.62 | 0.397081E+09 | 0.00 | 0.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127035E+10 | 0.348105E+09 | 268452.43 | 1477949.77 | 41188461.58 | 0.503112E+09 | 0.665209E+09 | 3372.80 | 0.52 |
February | 0.787006E+09 | 0.525854E+09 | 684928.00 | 672060.56 | 38686396.51 | 0.294052E+09 | 0.217429E+09 | 2092.45 | 0.51 |
March | 0.100385E+10 | 0.615759E+09 | 29968.90 | 610057.84 | 90825120.56 | 0.471591E+09 | 0.171520E+09 | 96.62 | 0.52 |
April | 0.235719E+09 | 0.103703E+10 | 1941981.11 | 519736.62 | 0.212950E+09 | 75668810.80 | 62106883.62 | 7121.83 | 0.42 |
May | 0.00 | 0.336174E+10 | 0.00 | 0.00 | 73666950.88 | 0.00 | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.400889E+10 | 0.00 | 0.00 | 56884283.70 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.459750E+10 | 0.00 | 0.00 | 67693602.96 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.501898E+10 | 0.00 | 0.00 | 46447958.26 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.396518E+10 | 0.00 | 0.00 | 71263720.27 | 0.00 | 0.00 | 0.00 | 0.39 |
October | 0.156179E+09 | 0.346527E+10 | 0.00 | 1084321.30 | 45143993.79 | 15191580.83 | 0.214527E+09 | 0.00 | 0.53 |
November | 0.395890E+09 | 0.120681E+10 | 1933.66 | 3352607.50 | 46835588.13 | 0.131503E+09 | 0.798806E+09 | 3465.97 | 0.69 |
December | 0.102291E+10 | 0.860446E+09 | 34471.55 | 2394179.11 | 60844118.75 | 0.466819E+09 | 0.645744E+09 | 408.54 | 0.61 |
Annual Sum or Average | 0.487191E+10 | 0.290116E+11 | 2961735.66 | 10110912.69 | 0.852430E+09 | 0.195794E+10 | 0.277534E+10 | 16558.21 | 0.48 |
Minimum of Months | 0.00 | 0.348105E+09 | 0.00 | 0.00 | 38686396.51 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.127035E+10 | 0.501898E+10 | 1941981.11 | 3352607.50 | 0.212950E+09 | 0.503112E+09 | 0.798806E+09 | 7121.83 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125713E+10 | 0.154038E+09 | 0.00 | 540698.21 | 50470957.71 | 13143613.20 | 0.290366E+09 | 0.00 | 0.50 |
February | 0.724559E+09 | 0.206790E+09 | 0.00 | 325868.44 | 68511676.00 | 12641838.94 | 0.125011E+09 | 0.00 | 0.50 |
March | 0.867533E+09 | 0.276041E+09 | 0.00 | 737393.73 | 0.105378E+09 | 21294222.97 | 0.226677E+09 | 0.00 | 0.55 |
April | 0.167551E+09 | 0.736741E+09 | 0.00 | 556176.48 | 0.110788E+09 | 0.00 | 0.101870E+09 | 0.00 | 0.47 |
May | 0.00 | 0.212542E+10 | 0.00 | 0.00 | 28443375.04 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.253746E+10 | 0.00 | 0.00 | 19119707.90 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.283695E+10 | 0.00 | 0.00 | 28968428.91 | 0.00 | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.301136E+10 | 0.00 | 0.00 | 19828431.64 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.228667E+10 | 0.00 | 0.00 | 27719453.74 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 0.102004E+09 | 0.172947E+10 | 0.00 | 749480.55 | 26796852.23 | 0.00 | 0.169959E+09 | 0.00 | 0.45 |
November | 0.453157E+09 | 0.533527E+09 | 0.00 | 1156069.76 | 29863899.45 | 0.00 | 0.313590E+09 | 0.00 | 0.56 |
December | 0.109010E+10 | 0.360611E+09 | 0.00 | 568143.76 | 54355183.93 | 8255707.95 | 0.199708E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.466204E+10 | 0.167951E+11 | 0.00 | 4633830.93 | 0.570244E+09 | 55335383.06 | 0.142718E+10 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.154038E+09 | 0.00 | 0.00 | 19119707.90 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.125713E+10 | 0.301136E+10 | 0.00 | 1156069.76 | 0.110788E+09 | 21294222.97 | 0.313590E+09 | 0.00 | 0.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168358E+10 | 0.110781E+09 | 0.00 | 35285.71 | 0.119184E+09 | 97370109.50 | 64267637.42 | 0.00 | 0.40 |
February | 0.926944E+09 | 0.150750E+09 | 0.00 | 45254.37 | 0.123059E+09 | 38773569.77 | 56485224.29 | 0.00 | 0.39 |
March | 0.118211E+10 | 0.281510E+09 | 0.00 | 215494.33 | 0.116675E+09 | 39648375.28 | 0.122035E+09 | 0.00 | 0.44 |
April | 0.236220E+09 | 0.576801E+09 | 0.00 | 572839.75 | 0.121856E+09 | 0.00 | 0.100563E+09 | 0.00 | 0.39 |
May | 0.00 | 0.157124E+10 | 0.00 | 0.00 | 18380494.00 | 0.00 | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.178846E+10 | 0.00 | 0.00 | 15820866.07 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.201225E+10 | 0.00 | 0.00 | 26050222.07 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.197364E+10 | 0.00 | 0.00 | 17689618.37 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.171014E+10 | 0.00 | 0.00 | 38125236.71 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.158830E+09 | 0.112043E+10 | 0.00 | 566645.32 | 44146183.84 | 0.00 | 0.152933E+09 | 0.00 | 0.37 |
November | 0.688516E+09 | 0.388238E+09 | 0.00 | 479672.01 | 0.110793E+09 | 211090.09 | 0.144886E+09 | 0.00 | 0.41 |
December | 0.142867E+10 | 0.253298E+09 | 0.00 | 52401.82 | 0.153363E+09 | 59091054.94 | 15971197.44 | 0.00 | 0.39 |
Annual Sum or Average | 0.630487E+10 | 0.119375E+11 | 0.00 | 1967593.31 | 0.905142E+09 | 0.235094E+09 | 0.657142E+09 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.110781E+09 | 0.00 | 0.00 | 15820866.07 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.168358E+10 | 0.201225E+10 | 0.00 | 572839.75 | 0.153363E+09 | 97370109.50 | 0.152933E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129202E+10 | 98497892.05 | 0.00 | 125074.36 | 94918741.70 | 49954688.24 | 0.149124E+09 | 0.00 | 0.51 |
February | 0.659245E+09 | 0.162121E+09 | 0.00 | 222398.53 | 84660511.70 | 19361906.27 | 0.152142E+09 | 0.00 | 0.52 |
March | 0.776879E+09 | 0.303492E+09 | 0.00 | 878098.47 | 71908422.25 | 38591981.91 | 0.319488E+09 | 0.00 | 0.61 |
April | 0.132527E+09 | 0.560331E+09 | 0.00 | 969899.54 | 94988525.38 | 0.00 | 0.233533E+09 | 0.00 | 0.59 |
May | 0.00 | 0.131943E+10 | 0.00 | 0.00 | 14788943.88 | 0.00 | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.145170E+10 | 0.00 | 0.00 | 14511623.34 | 0.00 | 0.00 | 0.00 | 0.53 |
July | 0.00 | 0.164832E+10 | 0.00 | 0.00 | 20426688.95 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.158972E+10 | 0.00 | 0.00 | 15297287.24 | 0.00 | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.134613E+10 | 0.00 | 0.00 | 61510595.62 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.108104E+09 | 0.942388E+09 | 0.00 | 562626.14 | 42899346.23 | 0.00 | 0.153018E+09 | 0.00 | 0.49 |
November | 0.421502E+09 | 0.336908E+09 | 0.00 | 842025.50 | 88881313.08 | 169843.07 | 0.286529E+09 | 0.00 | 0.55 |
December | 0.103891E+10 | 0.191420E+09 | 0.00 | 284102.93 | 0.126653E+09 | 40730557.97 | 0.139772E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.442918E+10 | 0.995045E+10 | 0.00 | 3884225.48 | 0.731445E+09 | 0.148809E+09 | 0.143361E+10 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 98497892.05 | 0.00 | 0.00 | 14511623.34 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.129202E+10 | 0.164832E+10 | 0.00 | 969899.54 | 0.126653E+09 | 49954688.24 | 0.319488E+09 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.936439E+09 | 0.288391E+09 | 0.00 | 4600092.55 | 54516018.57 | 37168724.78 | 0.170959E+10 | 0.00 | 0.62 |
February | 0.545728E+09 | 0.437444E+09 | 0.00 | 2552937.23 | 51460700.79 | 20973042.00 | 0.800616E+09 | 0.00 | 0.60 |
March | 0.872221E+09 | 0.458326E+09 | 0.00 | 2212468.19 | 70179474.94 | 27776124.30 | 0.702648E+09 | 0.00 | 0.58 |
April | 0.199645E+09 | 0.709007E+09 | 0.00 | 1089817.44 | 0.102060E+09 | 0.00 | 0.191578E+09 | 0.00 | 0.47 |
May | 0.00 | 0.158604E+10 | 0.00 | 0.00 | 18382878.37 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.171182E+10 | 0.00 | 0.00 | 16133109.61 | 0.00 | 0.00 | 0.00 | 0.39 |
July | 0.00 | 0.198828E+10 | 0.00 | 0.00 | 25577115.95 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.215801E+10 | 0.00 | 0.00 | 15830731.05 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.207825E+10 | 0.00 | 0.00 | 25541062.27 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.123558E+09 | 0.164406E+10 | 0.00 | 1355689.67 | 23691115.10 | 0.00 | 0.291405E+09 | 0.00 | 0.56 |
November | 0.354069E+09 | 0.733584E+09 | 0.00 | 4003712.56 | 57684565.27 | 0.00 | 0.103227E+10 | 0.00 | 0.73 |
December | 0.889174E+09 | 0.558129E+09 | 0.00 | 4374604.20 | 72729648.26 | 27916074.55 | 0.121246E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.392083E+10 | 0.143513E+11 | 0.00 | 20189321.84 | 0.533787E+09 | 0.113834E+09 | 0.594057E+10 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.288391E+09 | 0.00 | 0.00 | 15830731.05 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.936439E+09 | 0.215801E+10 | 0.00 | 4600092.55 | 0.102060E+09 | 37168724.78 | 0.170959E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124452E+10 | 0.116557E+09 | 0.00 | 558359.87 | 96999485.34 | 78759564.00 | 0.250244E+09 | 0.00 | 0.54 |
February | 0.693109E+09 | 0.174263E+09 | 0.00 | 444990.62 | 93644954.94 | 28563399.70 | 0.156461E+09 | 0.00 | 0.56 |
March | 0.878803E+09 | 0.237790E+09 | 0.00 | 1055822.67 | 96997292.44 | 29894982.02 | 0.304319E+09 | 0.00 | 0.64 |
April | 0.183329E+09 | 0.527820E+09 | 0.00 | 820084.47 | 0.112247E+09 | 0.00 | 0.136150E+09 | 0.00 | 0.58 |
May | 0.00 | 0.123187E+10 | 0.00 | 0.00 | 8826822.80 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 0.00 | 0.135832E+10 | 0.00 | 0.00 | 13976907.80 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.152656E+10 | 0.00 | 0.00 | 9541072.93 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.157873E+10 | 0.00 | 0.00 | 15084640.26 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.133483E+10 | 0.00 | 0.00 | 74189401.09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 0.131256E+09 | 0.922382E+09 | 0.00 | 548962.70 | 39243088.99 | 0.00 | 0.140332E+09 | 0.00 | 0.51 |
November | 0.528545E+09 | 0.319661E+09 | 0.00 | 850516.22 | 0.110083E+09 | 417284.76 | 0.229704E+09 | 0.00 | 0.59 |
December | 0.109214E+10 | 0.235072E+09 | 0.00 | 514537.29 | 0.118646E+09 | 37651426.44 | 0.163585E+09 | 0.00 | 0.56 |
Annual Sum or Average | 0.475171E+10 | 0.956386E+10 | 0.00 | 4793273.85 | 0.789479E+09 | 0.175287E+09 | 0.138079E+10 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.116557E+09 | 0.00 | 0.00 | 8826822.80 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.124452E+10 | 0.157873E+10 | 0.00 | 1055822.67 | 0.118646E+09 | 78759564.00 | 0.304319E+09 | 0.00 | 0.64 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.234091E+12 | 0.366445E+10 | 0.00 | 0.142627E+12 | 0.670372E+11 |
February | 0.245603E+12 | 0.209042E+10 | 0.00 | 0.101057E+12 | 0.931273E+11 |
March | 0.270589E+12 | 0.188543E+10 | 0.00 | 0.115191E+12 | 0.111296E+12 |
April | 0.299682E+12 | -0.122086E+10 | 0.00 | 0.264972E+11 | 0.174478E+12 |
May | 0.294620E+12 | -0.703904E+10 | 0.00 | -0.752588E+11 | 0.295668E+12 |
June | 0.292152E+12 | -0.744233E+10 | 0.00 | -0.859655E+11 | 0.313784E+12 |
July | 0.302421E+12 | -0.877262E+10 | 0.00 | -0.958955E+11 | 0.324918E+12 |
August | 0.282082E+12 | -0.918472E+10 | 0.00 | -0.959190E+11 | 0.338533E+12 |
September | 0.244609E+12 | -0.731838E+10 | 0.00 | -0.765404E+11 | 0.288590E+12 |
October | 0.254932E+12 | -0.528715E+10 | 0.00 | -0.274146E+11 | 0.258108E+12 |
November | 0.204579E+12 | 90256378.29 | 0.00 | 0.777294E+11 | 0.144522E+12 |
December | 0.210274E+12 | 0.240646E+10 | 0.00 | 0.131515E+12 | 0.964611E+11 |
Annual Sum or Average | 0.313563E+13 | -0.361281E+11 | 0.00 | 0.137624E+12 | 0.250652E+13 |
Minimum of Months | 0.204579E+12 | -0.918472E+10 | 0.00 | -0.959190E+11 | 0.670372E+11 |
Maximum of Months | 0.302421E+12 | 0.366445E+10 | 0.00 | 0.142627E+12 | 0.338533E+12 |