Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 08:35:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1629.52 | 327.07 | 327.07 |
Net Site Energy | 1629.52 | 327.07 | 327.07 |
Total Source Energy | 4644.36 | 932.19 | 932.19 |
Net Source Energy | 4644.36 | 932.19 | 932.19 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 142.36 | 137.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 156.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 202.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 112.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 110.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1381.64 | 247.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 142.36 | 137.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 156.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 202.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 49.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 112.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 110.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 142.36 | 137.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 156.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 202.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 49.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 112.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 110.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 82.66 | 49.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 277.32 | 49.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 82.66 | 49.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 277.32 | 49.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1381.642 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1381.642 | 100.00 |
Total On-Site and Utility Electric Sources | 1381.642 | 100.00 |
Total Electricity End Uses | 1381.642 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 355.17 |
Time Setpoint Not Met During Occupied Cooling | 194.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2505.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.9322 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.9322 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.9322 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 06-FEB-07:10 | 23-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 03-JAN-12:09 |
Heating | 164237.08 | 103522.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7126.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6205.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7929.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 198912.02 | 111452.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 164237.08 | 103522.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 7126.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 6205.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 7929.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 450.85 | 148.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 495.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 642.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 157.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 357.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 120.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4375.66 | 268.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 90.49 | 29.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 71.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 878.26 | 53.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 90.49 | 29.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 99.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 71.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 24.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 878.26 | 53.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.31 | 0.226107 | 0.243000 | 0.805449 | 0.602952 | 0.500000 | 0.001685 |
CORE_MID VAV BOX COMPONENT | 2.39 | 0.313959 | 0.328000 | 0.782973 | 0.837223 | 0.500000 | 0.001214 |
CORE_TOP VAV BOX COMPONENT | 2.59 | 0.288853 | 0.315000 | 0.817294 | 0.770276 | 0.500000 | 0.001319 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.817214 | 0.193330 | 0.211000 | 0.172432 | 0.515545 | 0.500000 | 0.001971 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.913994 | 0.109434 | 0.200000 | 0.182799 | 0.300000 | 0.500000 | 0.003482 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.12 | 0.141614 | 0.200000 | 0.223129 | 0.377639 | 0.500000 | 0.002690 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.08 | 0.092984 | 0.200000 | 0.215123 | 0.300000 | 0.500000 | 0.004097 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.620992 | 0.254418 | 0.274000 | 0.170152 | 0.678449 | 0.500000 | 0.001498 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.742025 | 0.134796 | 0.200000 | 0.148405 | 0.359455 | 0.500000 | 0.002826 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.867740 | 0.182072 | 0.200000 | 0.173548 | 0.485527 | 0.500000 | 0.002093 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.825466 | 0.121162 | 0.200000 | 0.165093 | 0.323099 | 0.500000 | 0.003145 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.698016 | 0.226344 | 0.237000 | 0.165430 | 0.603584 | 0.500000 | 0.001683 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.896908 | 0.111518 | 0.200000 | 0.179382 | 0.300000 | 0.500000 | 0.003416 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.990331 | 0.159534 | 0.200000 | 0.198066 | 0.425424 | 0.500000 | 0.002388 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.974649 | 0.102617 | 0.200000 | 0.194930 | 0.300000 | 0.500000 | 0.003713 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21836.01 |
CORE_MID VAV BOX REHEAT COIL | 23120.04 |
CORE_TOP VAV BOX REHEAT COIL | 41294.17 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18275.89 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12032.85 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18396.19 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12032.64 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13478.99 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8968.23 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 13592.10 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8968.14 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 13941.14 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 9246.16 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 14037.97 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 9246.07 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 3.19 | 1.46 | 6.37 | 2.09 | 5.68 | 5.68 | 0.300000 | 0.367848 | 5.68 |
PACU_VAV_MID | 2.97 | 1.52 | 5.95 | 2.57 | 5.05 | 5.05 | 0.300000 | 0.508661 | 5.05 |
PACU_VAV_TOP | 3.26 | 1.61 | 6.52 | 3.76 | 5.96 | 5.96 | 0.300000 | 0.631989 | 5.96 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.68 |
PACU_VAV_MID_OA_CONTROLLER | 5.05 |
PACU_VAV_TOP_OA_CONTROLLER | 5.96 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 5.68 | 93961.52 | 0.800655 | 1.89 | 31317.37 | 0.800655 |
PACU_VAV_MID COOLING COIL | 5.05 | 83537.73 | 0.800655 | 1.68 | 27843.13 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 5.96 | 98578.45 | 0.800655 | 1.98 | 32856.20 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 32961.52 |
PACU_VAV_MID HEATING COIL | 34181.06 |
PACU_VAV_TOP HEATING COIL | 33916.69 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.68 |
PACU_VAV_MID FAN | 5.05 |
PACU_VAV_TOP FAN | 5.96 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 30.766 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8662 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.8508 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.198 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2365 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2242 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2366 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9205 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9413 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6010 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.151 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.383 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.150 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29361301E-12 | 0.14012854E-14 | -0.85605344E-13 | 0.14800367E-15 |
43 | 6 | 0.27604353E-07 | 0.24091625E-09 | 0.63325015E-08 | -0.12947724E-12 |
44 | 5 | -0.18467641E-03 | 0.20758097E-05 | -0.95060042E-04 | 0.62631763E-08 |
45 | 4 | 0.28577214 | 0.10163362E-02 | 0.97391765E-01 | -0.32673590E-04 |
46 | 3 | -7.1400386 | 0.31651635E-01 | -2.3014419 | 0.28390242E-01 |
47 | 2 | 40.454589 | 0.11303679 | 15.111294 | -0.32870127 |
48 | 1 | -80.226531 | 0.51206543E-01 | -29.003760 | 1.0718159 |
49 | 0 | 46.824341 | 0.10340301E-02 | 16.294559 | |
50 | 7 | -0.29611882E-12 | 0.13865371E-14 | -0.86632775E-13 | 0.14828224E-15 |
51 | 6 | 0.27787793E-07 | 0.23712375E-09 | 0.63729895E-08 | -0.13045931E-12 |
52 | 5 | -0.18561242E-03 | 0.20406469E-05 | -0.95529752E-04 | 0.63026795E-08 |
53 | 4 | 0.28687424 | 0.99804250E-03 | 0.97787795E-01 | -0.32828381E-04 |
54 | 3 | -7.1618810 | 0.31052249E-01 | -2.3079221 | 0.28497237E-01 |
55 | 2 | 40.526644 | 0.11080299 | 15.137914 | -0.32950368 |
56 | 1 | -80.281767 | 0.50157931E-01 | -29.027638 | 1.0729929 |
57 | 0 | 46.824340 | 0.10121278E-02 | 16.293979 | |
58 | 7 | -0.28014218E-12 | 0.13884632E-14 | -0.87393674E-13 | 0.18804395E-15 |
59 | 6 | 0.23616586E-07 | 0.31618784E-09 | 0.54522364E-08 | -0.10828607E-12 |
60 | 5 | -0.16407885E-03 | 0.28046874E-05 | -0.84685207E-04 | 0.54024401E-08 |
61 | 4 | 0.26115148 | 0.14088028E-02 | 0.88562665E-01 | -0.29253652E-04 |
62 | 3 | -6.6512012 | 0.44876491E-01 | -2.1564742 | 0.25998182E-01 |
63 | 2 | 38.840966 | 0.16346293 | 14.513591 | -0.31073734 |
64 | 1 | -78.988481 | 0.75323239E-01 | -28.467021 | 1.0454353 |
65 | 0 | 46.824349 | 0.15467291E-02 | 16.308047 | |
66 | 7 | -0.18778705E-08 | -0.48456698E-15 | 0.68415356E-14 | -0.90766841E-16 |
67 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
68 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
69 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
70 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
71 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
72 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
73 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
74 | 7 | -0.17777358E-08 | -0.41207670E-15 | 0.60771148E-14 | -0.79247013E-16 |
75 | 6 | 0.66205355E-05 | 0.45347915E-08 | 0.31869553E-02 | -0.26734852E-04 |
76 | 5 | -0.47643654E-03 | 0.26865296E-05 | -0.22355891 | 0.19546881E-02 |
77 | 4 | 0.10961386E-01 | 0.12229770E-03 | 4.8267865 | -0.45238458E-01 |
78 | 3 | -0.96263561E-01 | 0.97262436E-03 | -38.005829 | 0.39848146 |
79 | 2 | 0.34182167 | 0.16181264E-02 | 116.45361 | -1.4175335 |
80 | 1 | -0.49337445 | 0.49308431E-03 | -143.88945 | 2.0487464 |
81 | 0 | 0.24054552 | 0.11921404E-04 | 60.838472 | |
82 | 7 | -0.18778705E-08 | -0.48456747E-15 | 0.68415356E-14 | -0.90766840E-16 |
83 | 6 | 0.62832840E-05 | 0.42957215E-08 | 0.31879255E-02 | -0.26742991E-04 |
84 | 5 | -0.45150393E-03 | 0.25448514E-05 | -0.22361406 | 0.19551748E-02 |
85 | 4 | 0.10383635E-01 | 0.11583744E-03 | 4.8277051 | -0.45247288E-01 |
86 | 3 | -0.91177470E-01 | 0.92119394E-03 | -38.011019 | 0.39853883 |
87 | 2 | 0.32374524 | 0.15324382E-02 | 116.46371 | -1.4176686 |
88 | 1 | -0.46727348 | 0.46697369E-03 | -143.89540 | 2.0488441 |
89 | 0 | 0.22781756 | 0.11275910E-04 | 60.838472 | |
90 | 7 | -0.17776120E-08 | -0.41258204E-15 | 0.60425363E-14 | -0.82023253E-16 |
91 | 6 | 0.66209765E-05 | 0.45351028E-08 | 0.31869540E-02 | -0.26734841E-04 |
92 | 5 | -0.47646911E-03 | 0.26867147E-05 | -0.22355884 | 0.19546874E-02 |
93 | 4 | 0.10962140E-01 | 0.12230614E-03 | 4.8267853 | -0.45238446E-01 |
94 | 3 | -0.96270204E-01 | 0.97269154E-03 | -38.005822 | 0.39848139 |
95 | 2 | 0.34184528 | 0.16182383E-02 | 116.45360 | -1.4175333 |
96 | 1 | -0.49340854 | 0.49311848E-03 | -143.88944 | 2.0487463 |
97 | 0 | 0.24056214 | 0.11922214E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3628_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.3628_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.061 | 2.061 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.62909E-002 | 0.29373 | 0.50042 | 0.50042 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11614 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.215E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.231E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.215E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.231E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.278E-004 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.278E-004 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.480E-005 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0134E-002 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0196E-002 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1193E-002 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1247E-002 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8841E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9277E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6395E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6611E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1424 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8435E-002 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1619 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.9066E-002 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1021 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3950E-002 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2271E-002 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5852E-002 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0133E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0194E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1192E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1244E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8834E-003 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9261E-003 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6393E-003 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6609E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8873E-002 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5106E-002 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4359E-002 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1835E-002 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9412E-002 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0071E-002 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9184E-002 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3003E-002 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3645E-004 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3880E-004 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0036E-004 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0205E-004 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9093E-004 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9149E-004 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2478E-004 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2552E-004 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8664E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9172E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2271E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2674E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8136E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8419E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6393E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6609E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6746E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1661E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8341E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6488E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7310E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1564E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2271E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5852E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8667E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9174E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2274E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2678E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8140E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8429E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6395E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6611E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0278E-002 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5776E-002 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6115E-002 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2675E-002 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0568E-002 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0610E-002 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9184E-002 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3003E-002 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4720E-004 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5462E-004 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1396E-004 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2228E-004 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9859E-004 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0140E-004 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2479E-004 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2553E-004 |
81 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1390 |
82 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.1846E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1551 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1035 |
85 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1076 |
86 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4577E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7521E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.2047E-002 |
89 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6588E-002 |
90 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.3837E-002 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2353E-002 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0730E-002 |
93 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.7679E-002 |
94 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9140E-002 |
95 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8008E-002 |
96 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2370E-002 |
97 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.1578E-002 |
98 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7894E-002 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2666E-002 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1859E-002 |
101 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1631E-002 |
102 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6532E-002 |
103 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7521E-002 |
104 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2047E-002 |
105 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.7945E-002 |
106 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4492E-002 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.4048E-002 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1552E-002 |
109 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.8796E-002 |
110 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9662E-002 |
111 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8008E-002 |
112 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2371E-002 |
113 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1390 |
114 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.1839E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1551 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1035 |
117 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1076 |
118 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4571E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7517E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.2044E-002 |
121 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6589E-002 |
122 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.3835E-002 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2354E-002 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0728E-002 |
125 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.7676E-002 |
126 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9137E-002 |
127 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8004E-002 |
128 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2368E-002 |
129 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.1580E-002 |
130 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7893E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2668E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1858E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1630E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6531E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7517E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2044E-002 |
137 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.7946E-002 |
138 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4491E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.4048E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1550E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.8793E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9659E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8005E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2369E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37325.28247 | 37325.28247 | 3.31460 | 3.31460 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8303.96634 | 8303.96634 | 0.43873 | 0.43873 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 26910.41909 | 26910.41909 | 2.38711 | 2.38711 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 16314.80624 | 16314.80624 | 0.85281 | 0.85281 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28986.33093 | 28986.33093 | 2.59458 | 2.59458 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 33.45600 | 5.47459E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 29045.11292 | 29045.11292 | 1.52319 | 1.52319 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 9130.10429 | 9130.10429 | 0.81721 | 0.81721 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 12826.75020 | 12826.75020 | 0.67413 | 0.67413 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10211.44529 | 10211.44529 | 0.91399 | 0.91399 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.46414E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 8444.51690 | 8444.51690 | 0.44385 | 0.44385 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12464.30642 | 12464.30642 | 1.11565 | 1.11565 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 12911.01543 | 12911.01543 | 0.67857 | 0.67857 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12017.15152 | 12017.15152 | 1.07562 | 1.07562 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 8444.36848 | 8444.36848 | 0.44384 | 0.44384 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6937.77693 | 6937.77693 | 0.62099 | 0.62099 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 9465.76036 | 9465.76036 | 0.49719 | 0.49719 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8290.06292 | 8290.06292 | 0.74203 | 0.74203 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 27.01800 | 5.46476E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 6297.23389 | 6297.23389 | 0.33080 | 0.33080 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 9694.51969 | 9694.51969 | 0.86774 | 0.86774 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 9544.98413 | 9544.98413 | 0.50136 | 0.50136 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9222.29462 | 9222.29462 | 0.82547 | 0.82547 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 30.84133 | 5.47057E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 6297.17021 | 6297.17021 | 0.33080 | 0.33080 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7798.35838 | 7798.35838 | 0.69802 | 0.69802 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 9790.14247 | 9790.14247 | 0.51424 | 0.51424 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10020.52591 | 10020.52591 | 0.89691 | 0.89691 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 6492.34661 | 6492.34661 | 0.34106 | 0.34106 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11064.20071 | 11064.20071 | 0.99033 | 0.99033 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 9857.96081 | 9857.96081 | 0.51781 | 0.51781 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10889.07681 | 10889.07681 | 0.97465 | 0.97465 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 6492.27921 | 6492.27921 | 0.34105 | 0.34105 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 74025.43 | 5.67622 | 5.67622 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 35807.74 | 2.08798 | 2.08798 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 66983.65 | 5.04651 | 5.04651 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 35666.76 | 2.56697 | 2.56697 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 76830.35 | 5.95512 | 5.95512 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 35848.36 | 3.76357 | 3.76357 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.31460 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22611 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80545 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60295 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68504E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21836.00574 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.38711 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31396 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32800 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78297 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83722 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21354E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23120.04191 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.59458 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28885 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.81729 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77028 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.31901E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 41294.17070 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81721 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19333 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21100 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17243 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51555 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97073E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18275.88771 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91399 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10943 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18280 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.48156E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12032.85355 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11565 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14161 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22313 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37764 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69040E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 18396.19430 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07562 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.29842E-002 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21512 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.09747E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12032.64312 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62099 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25442 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27400 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17015 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67845 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49753E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13478.98610 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74203 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13480 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14841 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35946 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82650E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8968.22684 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86774 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18207 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17355 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48553 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09257E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13592.10421 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82547 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12116 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16509 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32310 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14455E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8968.13740 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69802 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22634 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23700 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16543 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60358 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68328E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13941.14209 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89691 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11152 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17938 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.41647E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9246.16058 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99033 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15953 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19807 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42542 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38820E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14037.97342 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97465 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10262 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19493 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.71285E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9246.06585 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.18541 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46265 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.37083 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.08798 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.67622 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.67622 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.36785 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.97351 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.52078 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.94702 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.56697 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.04651 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.04651 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.50866 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.25853 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.61078 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.51706 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.76357 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.95512 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.95512 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.63199 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.67622 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 5.04651 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.95512 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.67622 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.67622 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 93961.51583 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.89188 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31317.37323 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 32961.52051 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.67622 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.04651 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.04651 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 83537.72968 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.68200 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 27843.12530 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 34181.06142 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 5.04651 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.95512 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.95512 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 98578.45010 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.98484 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32856.19742 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 33916.69179 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.95512 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 92344.67 | 315093.10 | 11.70 | 2.92 | 3.35 | 3.53 | 3.69 | 9.95 | 11.44 | 12.06 | 12.59 | 5.3290 | 4.2132 | 2.8244 | 1.1961 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 82100.25 | 280137.69 | 11.70 | 2.92 | 3.35 | 3.53 | 3.69 | 9.95 | 11.44 | 12.06 | 12.59 | 4.7379 | 3.7458 | 2.5111 | 1.0634 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 96882.16 | 330575.65 | 11.70 | 2.92 | 3.35 | 3.53 | 3.69 | 9.95 | 11.44 | 12.06 | 12.59 | 5.5909 | 4.4202 | 2.9632 | 1.2549 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.198 | 1.016 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.237 | 0.224 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.224 | 0.213 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.866 | 0.767 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.237 | 0.224 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_NORTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_EAST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | N/A | 2.061 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3628_SHGC_WEST_0.38 | N/A | 2.061 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.1748867384E-002 | 6.1680159476E-002 | Pass | Pass | 7.4584933644E-003 | 8.6096025230E-002 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1341858437 | 9.7214886070E-002 | Pass | Pass | 0.1163795207 | 0.3146817003 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.9347357087E-002 | 3.5739442752E-002 | Pass | Pass | 4.5608131057E-002 | 0.2147046294 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.9433054628E-002 | 1.9352842614E-002 | Pass | Pass | 1.5632267018E-002 | 0.1383798747 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.3051040938E-002 | 6.2847126065E-002 | Pass | Pass | 3.6405702608E-002 | 0.1840596038 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.4071745724E-002 | 3.3211380869E-002 | Pass | Pass | 0.1170167407 | 0.3215379084 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.6057562616E-002 | 0.1426920410 | Pass | Pass | 5.2089339581 | 28.4073431775 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1080926833 | 0.1303325377 | Pass | Pass | 5.2093761719 | 36.8925741723 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1553296248 | 0.1468998622 | Pass | Pass | 0.2279952904 | 1.1848464053 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1301066976 | 0.1211535483 | Pass | Pass | 8.7214604163 | 55.0394796545 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.4932298009E-002 | 2.8354623158E-002 | Pass | Pass | 7.2183183542E-003 | 8.4669262765E-002 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.7657246122E-002 | 0.1065345103 | Pass | Pass | 7.3624728323E-003 | 8.5516661304E-002 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1090281946 | 0.1195994975 | Pass | Pass | 7.1244922962E-003 | 8.4110748085E-002 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 6.9314659072E-002 | 9.4287366099E-002 | Pass | Pass | 6.9457742760E-003 | 8.3051433070E-002 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.2409586460E-002 | 3.5300108255E-002 | Pass | Pass | 3.7310174571E-002 | 0.1883764805 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.8670327305E-002 | 0.1357409189 | Pass | Pass | 3.6866659097E-002 | 0.1862773148 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1644158550 | 0.1630462078 | Pass | Pass | 3.5008115670E-002 | 0.1831847433 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.0547046956E-002 | 0.1273733503 | Pass | Pass | 3.3470200049E-002 | 0.1708164145 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4199.65 | 83.61 | 0.00 | 1884.61 | 815.27 | 6983.15 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.016 | 1.198 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.216 | 0.224 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.767 | 0.866 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.228 | 0.237 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3628_SHGC_EAST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3628_SHGC_EAST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3628_SHGC_WEST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3628_SHGC_WEST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.061 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3628_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3628_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3628_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3628_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.061 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.061 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 177.99 | 2.061 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.061 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.88 | 0.0000 | Y | 5.97 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.79 | 0.0000 | Y | 3.77 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.41 | 0.0000 | Y | 5.87 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.47 | 0.0000 | Y | 3.72 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.81 | 0.0000 | Y | 5.96 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.74 | 0.0000 | Y | 3.76 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.37 | 0.0000 | Y | 5.86 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.43 | 0.0000 | Y | 3.72 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.88 | 0.0000 | Y | 5.97 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.79 | 0.0000 | Y | 3.77 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.41 | 0.0000 | Y | 5.87 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.47 | 0.0000 | Y | 3.72 |
Interior Lighting Total | 5.9322 | 4982.19 | 29555.08 | 202.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.26 | 42.26 | 3.37 | |
EXTERIOR_LIGHTS_B | 408.47 | AstronomicalClock | - | 83.67 | 62.97 | 4.83 | |
EXTERIOR_LIGHTS_C | 4724.13 | AstronomicalClock | - | 83.67 | 46.88 | 41.57 | |
Exterior Lighting Total | 5557.43 | 49.77 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 93961.52 | 75230.78 | 18730.73 | 0.80 | 3.57 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 83537.73 | 66884.92 | 16652.81 | 0.80 | 3.57 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 98578.45 | 78927.35 | 19651.10 | 0.80 | 3.57 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 92344.7 | 2.92 | 9.95 | N/A | N/A | 11.70 | |
PACU_VAV_MID COOLING COIL | 82100.3 | 2.92 | 9.95 | N/A | N/A | 11.70 | |
PACU_VAV_TOP COOLING COIL | 96882.2 | 2.92 | 9.95 | N/A | N/A | 11.70 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 21836.01 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 23120.04 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 41294.17 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18275.89 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12032.85 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18396.19 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12032.64 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13478.99 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8968.23 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13592.10 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8968.14 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13941.14 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9246.16 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14037.97 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9246.07 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 32961.52 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 34181.06 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 33916.69 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.68 | 12345.13 | 2174.89 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.05 | 11599.22 | 2298.46 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.96 | 12951.73 | 2174.89 | 1.00 | 1.13 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 92344.67 | 2.92 | 9.95 | 11.70 | 5.3290 | 3.35 | 11.44 | 4.2132 | 3.53 | 12.06 | 2.8244 | 3.69 | 12.59 | 1.1961 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 82100.25 | 2.92 | 9.95 | 11.70 | 4.7379 | 3.35 | 11.44 | 3.7458 | 3.53 | 12.06 | 2.5111 | 3.69 | 12.59 | 1.0634 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96882.16 | 2.92 | 9.95 | 11.70 | 5.5909 | 3.35 | 11.44 | 4.4202 | 3.53 | 12.06 | 2.9632 | 3.69 | 12.59 | 1.2549 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37325.28 | 37325.28 | 37.95 | 3.315 | 3.315 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 22.95 | 0.00546 | 0.425 | 0.00 |
CORE_MID | 26910.42 | 26910.42 | 27.36 | 2.387 | 2.387 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 22.95 | 0.00546 | 0.425 | 0.00 |
CORE_TOP | 28986.33 | 28986.33 | 29.47 | 2.595 | 2.595 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00891 | 33.46 | 0.00547 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 9130.10 | 9130.10 | 44.03 | 0.817 | 0.817 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00874 | 33.75 | 0.00548 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10211.45 | 10211.45 | 77.79 | 0.914 | 0.914 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00863 | 26.60 | 0.00546 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12464.31 | 12464.31 | 60.12 | 1.116 | 1.116 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00867 | 33.65 | 0.00547 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 12017.15 | 12017.15 | 91.56 | 1.076 | 1.076 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00861 | 31.83 | 0.00547 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6937.78 | 6937.78 | 33.46 | 0.621 | 0.621 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00883 | 33.75 | 0.00548 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8290.06 | 8290.06 | 63.16 | 0.742 | 0.742 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00868 | 27.02 | 0.00546 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9694.52 | 9694.52 | 46.76 | 0.868 | 0.868 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00874 | 33.65 | 0.00547 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9222.29 | 9222.29 | 70.26 | 0.825 | 0.825 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00866 | 30.84 | 0.00547 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7798.36 | 7798.36 | 37.61 | 0.698 | 0.698 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00878 | 33.75 | 0.00548 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10020.53 | 10020.53 | 76.34 | 0.897 | 0.897 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00864 | 25.76 | 0.00546 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11064.20 | 11064.20 | 53.36 | 0.990 | 0.990 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00870 | 33.41 | 0.00547 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10889.08 | 10889.08 | 82.96 | 0.975 | 0.975 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00863 | 31.83 | 0.00547 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8303.97 | 8303.97 | 8.44 | 0.439 | 0.439 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
CORE_MID | 16314.81 | 16314.81 | 16.59 | 0.853 | 0.853 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
CORE_TOP | 29045.11 | 29045.11 | 29.53 | 1.523 | 1.523 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 12826.75 | 12826.75 | 61.86 | 0.674 | 0.674 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8444.52 | 8444.52 | 64.33 | 0.444 | 0.444 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12911.02 | 12911.02 | 62.27 | 0.679 | 0.679 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 8444.37 | 8444.37 | 64.34 | 0.444 | 0.444 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 9465.76 | 9465.76 | 45.65 | 0.497 | 0.497 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 6297.23 | 6297.23 | 47.97 | 0.331 | 0.331 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 9544.98 | 9544.98 | 46.04 | 0.501 | 0.501 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 6297.17 | 6297.17 | 47.98 | 0.331 | 0.331 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00793 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 9790.14 | 9790.14 | 47.22 | 0.514 | 0.514 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 6492.35 | 6492.35 | 49.46 | 0.341 | 0.341 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -17.90 | 0.00096 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 9857.96 | 9857.96 | 47.55 | 0.518 | 0.518 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -17.90 | 0.00096 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 6492.28 | 6492.28 | 49.46 | 0.341 | 0.341 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -17.90 | 0.00096 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.68 | 5.68 | 2.09 | 2.09 | 5.6762 | 2.0880 | 5.6762 | 0.3678 | 0.3000 |
PACU_VAV_MID | 5.05 | 5.05 | 2.57 | 2.57 | 5.0465 | 2.5670 | 5.0465 | 0.5087 | 0.3000 |
PACU_VAV_TOP | 5.96 | 5.96 | 3.76 | 3.76 | 5.9551 | 3.7636 | 5.9551 | 0.6320 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21836.006 | 21836.006 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21836.01 | 11894.10 | 0.438729 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 8303.97 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 23120.042 | 23120.042 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23120.04 | 23120.04 | 0.852812 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 16314.81 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 41294.171 | 41294.171 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 41294.17 | 41294.17 | 1.523188 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 29045.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 18275.888 | 18275.888 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18275.89 | 18275.89 | 0.674129 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00790831 | 41.5058 | 12826.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12032.854 | 12032.854 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12032.85 | 12032.85 | 0.443847 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00790720 | 41.5001 | 8444.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 18396.194 | 18396.194 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18396.19 | 18396.19 | 0.678567 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00790891 | 41.5090 | 12911.02 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12032.643 | 12032.643 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12032.64 | 12032.64 | 0.443839 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00790720 | 41.5001 | 8444.37 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13478.986 | 13478.986 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13478.99 | 13478.99 | 0.497189 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00792977 | 41.6166 | 9465.76 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 8968.227 | 8968.227 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8968.23 | 8968.23 | 0.330804 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00793104 | 41.6232 | 6297.23 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 13592.104 | 13592.104 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13592.10 | 13592.10 | 0.501362 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00793065 | 41.6211 | 9544.98 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8968.137 | 8968.137 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8968.14 | 8968.14 | 0.330801 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00793104 | 41.6232 | 6297.17 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 13941.142 | 13941.142 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13941.14 | 13941.14 | 0.514237 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00789780 | 41.4513 | 9790.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 9246.161 | 9246.161 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9246.16 | 9246.16 | 0.341056 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00789808 | 41.4527 | 6492.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 14037.973 | 14037.973 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14037.97 | 14037.97 | 0.517808 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00789864 | 41.4556 | 9857.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 9246.066 | 9246.066 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9246.07 | 9246.07 | 0.341053 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00789808 | 41.4527 | 6492.28 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 93961.516 | 75230.782 | 5.676215 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 91487.07 | 91487.07 | 5.676215 | 26.08 | 14.62 | 0.00810640 | 10.62 | 8.97 | 0.00810640 | 33.90 | 0.00547527 | 15.07 | 21.0558 | 24.00 | 0.00880861 | 38.4735 | 63382.62 | 0.00 | 96886.94 | 69013.99 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 32961.521 | 32961.521 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 32961.52 | 32961.52 | 1.702865 | -6.91 | -6.91 | 0.00300781 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 70.1859 | 19.60 | 0.00776038 | 44.4202 | 17811.09 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 83537.730 | 66884.923 | 5.046514 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 81337.79 | 81337.79 | 5.046514 | 26.35 | 14.66 | 0.00804183 | 10.49 | 8.85 | 0.00804183 | 33.90 | 0.00547527 | 15.07 | 23.6831 | 24.00 | 0.00884108 | 38.6132 | 56230.31 | 0.00 | 86138.61 | 61357.80 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 34181.061 | 34181.061 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34181.06 | 34181.06 | 1.513954 | -10.19 | -10.19 | 0.00239963 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 78.9436 | 19.31 | 0.00776034 | 45.2321 | 21361.42 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 98578.450 | 78927.355 | 5.955124 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 95982.42 | 95982.42 | 5.955124 | 25.99 | 14.60 | 0.00811905 | 10.62 | 8.98 | 0.00811905 | 33.90 | 0.00547527 | 15.07 | 20.0696 | 24.00 | 0.00878663 | 38.3786 | 66231.71 | 0.00 | 101647.61 | 72405.10 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 33916.692 | 33916.692 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 33916.69 | 33916.69 | 1.786537 | -6.53 | -6.53 | 0.00323037 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 66.8987 | 17.60 | 0.00778481 | 50.5032 | 23508.79 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 21836.006 | 21836.006 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 21836.01 | 11894.10 | 1.0000 | 0.42883012 | 0.438729 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21836.01 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 21.01 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 8303.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 23120.042 | 23120.042 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23120.04 | 23120.04 | 1.0000 | 0.83357053 | 0.852812 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23120.04 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 16314.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 41294.171 | 41294.171 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 41294.17 | 41294.17 | 1.0000 | 1.48882100 | 1.523188 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41294.17 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 29045.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 18275.888 | 18275.888 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18275.89 | 18275.89 | 1.0000 | 0.65891928 | 0.674129 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18275.89 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790831 | 21.00 | 0.00790831 | 41.5058 | 12826.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 12032.854 | 12032.854 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12032.85 | 12032.85 | 1.0000 | 0.43383278 | 0.443847 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12032.85 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790720 | 21.00 | 0.00790720 | 41.5001 | 8444.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 18396.194 | 18396.194 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18396.19 | 18396.19 | 1.0000 | 0.66325682 | 0.678567 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18396.19 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790891 | 21.00 | 0.00790891 | 41.5090 | 12911.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 12032.643 | 12032.643 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12032.64 | 12032.64 | 1.0000 | 0.43382520 | 0.443839 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12032.64 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00790720 | 21.00 | 0.00790720 | 41.5001 | 8444.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13478.986 | 13478.986 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13478.99 | 13478.99 | 1.0000 | 0.48597168 | 0.497189 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13478.99 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00792977 | 21.00 | 0.00792977 | 41.6166 | 9465.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8968.227 | 8968.227 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8968.23 | 8968.23 | 1.0000 | 0.32334066 | 0.330804 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8968.23 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00793104 | 21.00 | 0.00793104 | 41.6232 | 6297.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 13592.104 | 13592.104 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13592.10 | 13592.10 | 1.0000 | 0.49005004 | 0.501362 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13592.10 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00793065 | 21.00 | 0.00793065 | 41.6211 | 9544.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8968.137 | 8968.137 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8968.14 | 8968.14 | 1.0000 | 0.32333744 | 0.330801 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8968.14 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00793104 | 21.00 | 0.00793104 | 41.6232 | 6297.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 13941.142 | 13941.142 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13941.14 | 13941.14 | 1.0000 | 0.50263426 | 0.514237 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13941.14 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00789780 | 21.00 | 0.00789780 | 41.4513 | 9790.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9246.161 | 9246.161 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9246.16 | 9246.16 | 1.0000 | 0.33336129 | 0.341056 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9246.16 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00789808 | 21.00 | 0.00789808 | 41.4527 | 6492.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14037.973 | 14037.973 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14037.97 | 14037.97 | 1.0000 | 0.50612542 | 0.517808 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14037.97 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00789864 | 21.00 | 0.00789864 | 41.4556 | 9857.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9246.066 | 9246.066 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9246.07 | 9246.07 | 1.0000 | 0.33335787 | 0.341053 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9246.07 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00789808 | 21.00 | 0.00789808 | 41.4527 | 6492.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 93961.516 | 75230.782 | 5.676215 | -999.0 | -999.000 | -999.0000 | 1.07578 | 1.00000 | 1019.9094 | 1004.8586 | 0.9774 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.676215 | 5.54814620 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 91487.07 | 91487.07 | 0.9737 | 5.54814620 | 5.676215 | 26.08 | 14.62 | 0.00810640 | 46877.5 | 10.62 | 8.97 | 0.00810640 | 31103.4 | -999.0 | -999.00 | -999.00 | -999.00 | 12345.134 | 79141.94 | 33.90 | 0.00547527 | 15.07 | 1.19517000 | 21.0558 | 24.00 | 0.00880861 | 24.00 | 0.00880861 | 38.4735 | 63382.62 | 0.00 | 96886.94 | 69013.99 | 5.32903637 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32961.521 | 32961.521 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.676215 | 5.54814620 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 32961.52 | 32961.52 | 1.0000 | 1.66444386 | 1.702865 | -6.91 | -6.91 | 0.00300781 | 542.7 | 12.80 | 9.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32961.52 | -17.90 | 0.00095524 | -17.90 | 1.19517000 | 70.1859 | 18.97 | 0.00783979 | 19.60 | 0.00776038 | 44.4202 | 17811.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 83537.730 | 66884.923 | 5.046514 | -999.0 | -999.000 | -999.0000 | 1.05002 | 1.00000 | 1019.7894 | 1004.8586 | 0.9774 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.046514 | 4.93265284 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 81337.79 | 81337.79 | 0.9737 | 4.93265284 | 5.046514 | 26.35 | 14.66 | 0.00804183 | 46983.5 | 10.49 | 8.85 | 0.00804183 | 30813.9 | -999.0 | -999.00 | -999.00 | -999.00 | 11599.219 | 69738.57 | 33.90 | 0.00547527 | 15.07 | 1.19517000 | 23.6831 | 24.00 | 0.00884108 | 24.00 | 0.00884108 | 38.6132 | 56230.31 | 0.00 | 86138.61 | 61357.80 | 4.73785034 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34181.061 | 34181.061 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_MID FAN | Fan:VariableVolume | 5.046514 | 4.93265284 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 34181.06 | 34181.06 | 1.0000 | 1.47979585 | 1.513954 | -10.19 | -10.19 | 0.00239963 | -4280.2 | 12.80 | 9.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34181.06 | -17.90 | 0.00095524 | -17.90 | 1.19517000 | 78.9436 | 18.73 | 0.00781485 | 19.31 | 0.00776034 | 45.2321 | 21361.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 98578.450 | 78927.355 | 5.955124 | -999.0 | -999.000 | -999.0000 | 1.08174 | 1.00000 | 1019.9329 | 1004.8586 | 0.9774 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.955124 | 5.82076235 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 95982.42 | 95982.42 | 0.9737 | 5.82076235 | 5.955124 | 25.99 | 14.60 | 0.00811905 | 46818.3 | 10.62 | 8.98 | 0.00811905 | 31135.3 | -999.0 | -999.00 | -999.00 | -999.00 | 12951.730 | 83030.69 | 33.90 | 0.00547527 | 15.07 | 1.19517000 | 20.0696 | 24.00 | 0.00878663 | 24.00 | 0.00878663 | 38.3786 | 66231.71 | 0.00 | 101647.61 | 72405.10 | 5.59088624 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.99 | 13.21 | 0.00913394 | 37141.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33916.692 | 33916.692 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.955124 | 5.82076235 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:20:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 33916.69 | 33916.69 | 1.0000 | 1.74622871 | 1.786537 | -6.53 | -6.53 | 0.00323037 | 1479.2 | 12.80 | 9.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33916.69 | -17.90 | 0.00095524 | -17.90 | 1.19517000 | 66.8987 | 16.45 | 0.00782847 | 17.60 | 0.00778481 | 50.5032 | 23508.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.68 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.05 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 5.96 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1314.67 | 3117.50 | 41.67 |
CORE_MID | 1330.00 | 3793.33 | 418.00 |
CORE_TOP | 2044.17 | 4025.33 | 1166.33 |
PERIMETER_TOP_ZN_3 | 3207.50 | 4143.00 | 2144.00 |
PERIMETER_TOP_ZN_2 | 3222.50 | 3761.33 | 1792.33 |
PERIMETER_TOP_ZN_1 | 2989.00 | 3280.00 | 1409.50 |
PERIMETER_TOP_ZN_4 | 3195.67 | 4014.00 | 1946.33 |
PERIMETER_BOT_ZN_3 | 2673.67 | 4192.50 | 1836.00 |
PERIMETER_BOT_ZN_2 | 2807.67 | 3615.17 | 1285.50 |
PERIMETER_BOT_ZN_1 | 2480.00 | 3424.50 | 1087.00 |
PERIMETER_BOT_ZN_4 | 2654.17 | 3822.83 | 1365.33 |
PERIMETER_MID_ZN_3 | 2665.67 | 3978.50 | 1540.67 |
PERIMETER_MID_ZN_2 | 2448.67 | 3129.00 | 1228.67 |
PERIMETER_MID_ZN_1 | 2688.00 | 2976.17 | 957.67 |
PERIMETER_MID_ZN_4 | 2727.67 | 3772.17 | 1392.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4698.50 | 4641.00 | 2505.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 1.00 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.00 | 0.17 | 0.00 |
CORE_TOP | 1.50 | 0.00 | 0.67 | 0.00 |
PERIMETER_TOP_ZN_3 | 62.00 | 6.83 | 26.67 | 5.00 |
PERIMETER_TOP_ZN_2 | 41.00 | 31.50 | 5.67 | 30.67 |
PERIMETER_TOP_ZN_1 | 26.50 | 43.17 | 4.67 | 41.67 |
PERIMETER_TOP_ZN_4 | 41.83 | 29.17 | 8.67 | 19.67 |
PERIMETER_BOT_ZN_3 | 5.83 | 0.00 | 4.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 1.00 | 19.17 | 0.00 | 19.17 |
PERIMETER_BOT_ZN_1 | 340.17 | 91.33 | 339.17 | 90.33 |
PERIMETER_BOT_ZN_4 | 1.00 | 19.50 | 0.00 | 12.83 |
PERIMETER_MID_ZN_3 | 6.83 | 2.50 | 3.67 | 2.17 |
PERIMETER_MID_ZN_2 | 4.17 | 27.83 | 0.50 | 27.83 |
PERIMETER_MID_ZN_1 | 2.33 | 51.50 | 0.33 | 51.17 |
PERIMETER_MID_ZN_4 | 4.67 | 26.17 | 0.67 | 17.83 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 398.33 | 211.33 | 355.17 | 194.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.59 | 52.94 | 2698.04 | 0.975 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.59 | 52.94 | 2698.04 | 0.677 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.59 | 52.94 | 2698.04 | 0.676 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.55 | 11.16 | 568.77 | 0.772 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.88 | 7.07 | 360.08 | 1.435 | 0.035 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.55 | 11.16 | 568.77 | 1.411 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.88 | 7.06 | 360.05 | 1.424 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.55 | 11.16 | 568.77 | 0.663 | 0.018 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.88 | 7.07 | 360.08 | 1.188 | 0.019 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.55 | 11.16 | 568.77 | 1.036 | 1.302 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.88 | 7.06 | 360.05 | 1.093 | 0.019 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.55 | 11.16 | 568.77 | 0.751 | 0.028 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.52 | 7.07 | 360.08 | 1.342 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.55 | 11.16 | 568.77 | 1.368 | 0.028 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.88 | 7.06 | 360.05 | 1.333 | 0.029 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.59 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.59 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.59 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.55 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.88 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.55 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.88 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.55 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.88 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.55 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.88 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.55 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.52 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.55 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.88 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.59 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.59 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.59 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.55 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.88 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.55 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.88 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.55 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.88 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.55 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.88 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.55 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.52 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.55 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.88 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.02 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 15698714.49 | 0.00 | 15698714.49 | 0.00 | 15698714.49 | 13393058.27 | 5609.95 | 68.46 | 3081.59 | 99.36 |
CORE_MID | 10862667.08 | 0.00 | 10862667.08 | 0.00 | 10862667.08 | 13393058.27 | 6460.02 | 28.79 | 2271.19 | 79.11 |
CORE_TOP | 10864759.74 | 0.00 | 10864759.74 | 0.00 | 10864759.74 | 13393058.27 | 6424.21 | 22.52 | 2313.27 | 90.46 |
PERIMETER_TOP_ZN_3 | 2613932.99 | 0.00 | 2613932.99 | 231607.63 | 2845540.61 | 2823374.22 | 5550.43 | 40.33 | 3169.24 | 90.46 |
PERIMETER_TOP_ZN_2 | 3070876.95 | 0.00 | 3070876.95 | 154404.16 | 3225281.10 | 1787429.43 | 4050.32 | 2.25 | 4707.43 | 90.46 |
PERIMETER_TOP_ZN_1 | 4758272.10 | 0.00 | 4758272.10 | 231607.63 | 4989879.73 | 2823374.22 | 4087.33 | 4.32 | 4668.35 | 90.46 |
PERIMETER_TOP_ZN_4 | 3063565.63 | 0.00 | 3063565.63 | 154404.16 | 3217969.78 | 1787312.18 | 4069.68 | 9.11 | 4681.21 | 90.46 |
PERIMETER_BOT_ZN_3 | 2269727.50 | 0.00 | 2269727.50 | 123144.38 | 2392871.89 | 2823374.22 | 6216.53 | 61.01 | 2482.46 | 99.36 |
PERIMETER_BOT_ZN_2 | 2559304.21 | 0.00 | 2559304.21 | 82095.76 | 2641399.97 | 1787429.43 | 4038.78 | 16.33 | 4704.89 | 99.36 |
PERIMETER_BOT_ZN_1 | 3521714.52 | 0.00 | 3521714.52 | 4445819.77 | 7967534.29 | 2823374.22 | 4850.37 | 303.23 | 3606.39 | 99.36 |
PERIMETER_BOT_ZN_4 | 2365751.26 | 0.00 | 2365751.26 | 82095.76 | 2447847.02 | 1787312.18 | 4188.16 | 22.88 | 4548.96 | 99.36 |
PERIMETER_MID_ZN_3 | 2539922.16 | 0.00 | 2539922.16 | 192795.44 | 2732717.60 | 2823374.22 | 5719.14 | 42.18 | 2998.68 | 79.11 |
PERIMETER_MID_ZN_2 | 3043571.37 | 0.00 | 3043571.37 | 128529.52 | 3172100.89 | 1787429.43 | 4011.03 | 4.57 | 4744.40 | 988.11 |
PERIMETER_MID_ZN_1 | 4603461.32 | 0.00 | 4603461.32 | 192795.44 | 4796256.76 | 2823374.22 | 4080.47 | 9.66 | 4669.87 | 79.11 |
PERIMETER_MID_ZN_4 | 2858045.52 | 0.00 | 2858045.52 | 128529.52 | 2986575.03 | 1787312.18 | 4023.46 | 12.02 | 4724.51 | 79.11 |
Total Facility | 74694286.83 | 0.00 | 74694286.83 | 6147829.16 | 80842115.99 | 67843644.98 | 6655.64 | 567.50 | 4903.98 | 1101.03 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.7212 | 0.0000 | 0.7212 | 0.0000 | 0.7212 | 0.4247 | 2876.31 | 68.46 | 2998.23 |
CORE_MID | 0.5015 | 0.0000 | 0.5015 | 0.0000 | 0.5015 | 0.4247 | 3685.40 | 28.79 | 2228.81 |
CORE_TOP | 0.5011 | 0.0000 | 0.5011 | 0.0000 | 0.5011 | 0.4247 | 3654.16 | 22.52 | 2266.32 |
PERIMETER_TOP_ZN_3 | 0.1207 | 0.0000 | 0.1207 | 0.0052 | 0.1260 | 0.0895 | 2780.37 | 40.33 | 3122.30 |
PERIMETER_TOP_ZN_2 | 0.1420 | 0.0000 | 0.1420 | 0.0035 | 0.1455 | 0.0567 | 1280.26 | 2.25 | 4660.48 |
PERIMETER_TOP_ZN_1 | 0.2206 | 0.0000 | 0.2206 | 0.0052 | 0.2258 | 0.0895 | 1317.28 | 4.32 | 4621.40 |
PERIMETER_TOP_ZN_4 | 0.1411 | 0.0000 | 0.1411 | 0.0035 | 0.1446 | 0.0567 | 1299.62 | 9.11 | 4634.27 |
PERIMETER_BOT_ZN_3 | 0.1037 | 0.0000 | 0.1037 | 0.0028 | 0.1065 | 0.0895 | 3482.78 | 61.01 | 2399.21 |
PERIMETER_BOT_ZN_2 | 0.1176 | 0.0000 | 0.1176 | 0.0019 | 0.1194 | 0.0567 | 1306.15 | 16.33 | 4620.52 |
PERIMETER_BOT_ZN_1 | 0.1621 | 0.0000 | 0.1621 | 0.2048 | 0.3670 | 0.0895 | 2116.62 | 303.23 | 3523.14 |
PERIMETER_BOT_ZN_4 | 0.1082 | 0.0000 | 0.1082 | 0.0019 | 0.1100 | 0.0567 | 1455.55 | 22.86 | 4464.58 |
PERIMETER_MID_ZN_3 | 0.1174 | 0.0000 | 0.1174 | 0.0044 | 0.1218 | 0.0895 | 2944.51 | 42.18 | 2956.30 |
PERIMETER_MID_ZN_2 | 0.1328 | 0.0000 | 0.1328 | 0.0031 | 0.1359 | 0.0567 | 1236.45 | 4.55 | 3793.01 |
PERIMETER_MID_ZN_1 | 0.2136 | 0.0000 | 0.2136 | 0.0044 | 0.2180 | 0.0895 | 1305.85 | 9.66 | 4627.49 |
PERIMETER_MID_ZN_4 | 0.1319 | 0.0000 | 0.1319 | 0.0029 | 0.1348 | 0.0567 | 1248.97 | 11.96 | 4682.08 |
Total Facility | 3.4356 | 0.0000 | 3.4356 | 0.2435 | 3.6791 | 2.1513 | 3858.75 | 567.39 | 4791.10 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 25236670.88 | 0.00 | 25236670.88 | 22614548.33 | 4288.22 | 720.37 | 3751.41 | 99.36 |
PACU_VAV_MID | 22841033.29 | 0.00 | 22841033.29 | 22614548.33 | 4093.56 | 21.03 | 4645.41 | 79.11 |
PACU_VAV_TOP | 23284055.87 | 0.00 | 23284055.87 | 22614548.33 | 4094.69 | 24.67 | 4640.64 | 89.75 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.1587 | 0.0000 | 1.1587 | 0.7171 | 1554.58 | 720.37 | 3668.05 |
PACU_VAV_MID | 1.0561 | 0.0000 | 1.0561 | 0.7171 | 1318.93 | 21.03 | 4603.04 |
PACU_VAV_TOP | 1.0753 | 0.0000 | 1.0753 | 0.7171 | 1324.64 | 24.67 | 4593.69 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 2886.82 | 0.00 | 0.00 | 0.00 | 1991.73 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2679.17 | 0.00 | 0.00 | 0.00 | 2213.56 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2744.21 | 0.00 | 0.00 | 0.00 | 2161.58 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 1.9369 | 0.0000 | 0.0000 | 0.0000 | 0.7472 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 1.7670 | 0.0000 | 0.0000 | 0.0000 | 0.7602 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 1.7942 | 0.0000 | 0.0000 | 0.0000 | 0.7537 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 825 |
Defaulted Fields | 545 |
Fields with Defaults | 2230 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1381.64 | 12344.18 | 14-MAY-17:10 | 198912.02 | 06-FEB-07:10 |
Electricity:Building | 908.40 | 12175.61 | 14-MAY-17:10 | 66132.41 | 21-DEC-08:10 |
Electricity:Zone:CORE_BOTTOM | 284.50 | 4029.56 | 01-JAN-00:10 | 22405.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 908.40 | 12175.61 | 14-MAY-17:10 | 66132.41 | 21-DEC-08:10 |
InteriorLights:Electricity | 202.96 | 934.27 | 01-JAN-09:30 | 21377.78 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 202.96 | 934.27 | 01-JAN-09:30 | 21377.78 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 202.96 | 934.27 | 01-JAN-09:30 | 21377.78 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 202.96 | 934.27 | 01-JAN-09:30 | 21377.78 | 02-JAN-16:50 |
Electricity:Zone:CORE_MID | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.31 | 409.68 | 09-APR-17:10 | 2324.90 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.97 | 23.57 | 01-JAN-09:30 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.97 | 23.57 | 01-JAN-09:30 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.17 | 259.34 | 14-MAY-17:10 | 1471.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.77 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.77 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.20 | 409.67 | 26-MAR-17:10 | 2324.89 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.87 | 23.57 | 01-JAN-08:00 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.87 | 23.57 | 01-JAN-08:00 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.13 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.72 | 14.92 | 01-JAN-09:30 | 563.19 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.72 | 14.92 | 01-JAN-09:30 | 563.19 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.29 | 409.68 | 09-APR-17:10 | 2324.90 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.96 | 23.57 | 01-JAN-09:30 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.96 | 23.57 | 01-JAN-09:30 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.17 | 259.34 | 14-MAY-17:10 | 1471.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.76 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.76 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.19 | 409.67 | 26-MAR-17:10 | 2324.89 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.86 | 23.57 | 01-JAN-08:00 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.86 | 23.57 | 01-JAN-08:00 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.12 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.72 | 14.92 | 01-JAN-09:30 | 563.19 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.72 | 14.92 | 01-JAN-09:30 | 563.19 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.31 | 409.68 | 09-APR-17:10 | 2324.90 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.97 | 23.57 | 01-JAN-09:30 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.97 | 23.57 | 01-JAN-09:30 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.17 | 259.34 | 14-MAY-17:10 | 1471.80 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.77 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.77 | 14.92 | 01-JAN-07:50 | 563.23 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.20 | 409.67 | 26-MAR-17:10 | 2324.89 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.87 | 23.57 | 01-JAN-08:00 | 889.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.87 | 23.57 | 01-JAN-08:00 | 889.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.13 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.72 | 14.92 | 01-JAN-09:30 | 563.19 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.72 | 14.92 | 01-JAN-09:30 | 563.19 | 02-JAN-16:50 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 423.46 | 168.34 | 01-JAN-00:10 | 170686.47 | 06-FEB-07:10 |
ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 833.98 | 02-JAN-17:00 |
Transformer:ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 833.98 | 02-JAN-17:00 |
ElectricityPurchased:Facility | 1381.64 | 12344.18 | 14-MAY-17:10 | 198912.02 | 06-FEB-07:10 |
ElectricityPurchased:Plant | 1381.64 | 12344.18 | 14-MAY-17:10 | 198912.02 | 06-FEB-07:10 |
Cogeneration:ElectricityPurchased | 1381.64 | 12344.18 | 14-MAY-17:10 | 198912.02 | 06-FEB-07:10 |
General:Cogeneration:ElectricityPurchased | 1381.64 | 12344.18 | 14-MAY-17:10 | 198912.02 | 06-FEB-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1381.64 | 12344.18 | 14-MAY-17:10 | 198912.02 | 06-FEB-07:10 |
ElectricityNet:Plant | 1381.64 | 12344.18 | 14-MAY-17:10 | 198912.02 | 06-FEB-07:10 |
Cogeneration:ElectricityNet | 1381.64 | 12344.18 | 14-MAY-17:10 | 198912.02 | 06-FEB-07:10 |
General:Cogeneration:ElectricityNet | 1381.64 | 12344.18 | 14-MAY-17:10 | 198912.02 | 06-FEB-07:10 |
Heating:Electricity | 142.36 | 0.00 | 01-JAN-00:10 | 164237.08 | 06-FEB-07:10 |
General:Heating:Electricity | 142.36 | 0.00 | 01-JAN-00:10 | 164237.08 | 06-FEB-07:10 |
Fans:Electricity | 112.87 | 0.00 | 01-JAN-00:10 | 32528.53 | 24-JUL-15:30 |
General:Fans:Electricity | 112.87 | 0.00 | 01-JAN-00:10 | 32528.53 | 24-JUL-15:30 |
ExteriorLights:Electricity | 49.77 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 49.77 | 0.00 | 01-JAN-07:30 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 156.58 | 0.00 | 01-JAN-00:10 | 76338.79 | 26-JUN-15:10 |
General:Cooling:Electricity | 156.58 | 0.00 | 01-JAN-00:10 | 76338.79 | 26-JUN-15:10 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-07:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-07:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-07:10 |
WIRED_LTG_ELECTRICITY | 5.70 | 0.00 | 01-JAN-00:10 | 600.72 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 247.88 | 1156.00 | 10-JAN-06:10 | 111452.60 | 23-DEC-07:20 |
NaturalGas:HVAC | 137.05 | 0.00 | 01-JAN-00:10 | 103522.90 | 23-DEC-07:20 |
Heating:NaturalGas | 137.05 | 0.00 | 01-JAN-00:10 | 103522.90 | 23-DEC-07:20 |
General:Heating:NaturalGas | 137.05 | 0.00 | 01-JAN-00:10 | 103522.90 | 23-DEC-07:20 |
NaturalGas:Plant | 110.83 | 1156.00 | 03-JAN-17:10 | 9794.57 | 07-FEB-12:40 |
WaterSystems:NaturalGas | 110.83 | 1156.00 | 03-JAN-17:10 | 9794.57 | 07-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 110.83 | 1156.00 | 03-JAN-17:10 | 9794.57 | 07-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2045.22 | 0.00 | 01-JAN-00:10 | 395720.85 | 26-JUN-15:20 |
EnergyTransfer:Building | 1110.17 | 0.00 | 01-JAN-00:10 | 165389.55 | 26-JUN-15:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 211.01 | 0.00 | 01-JAN-00:10 | 26404.18 | 05-SEP-08:00 |
Heating:EnergyTransfer | 126.43 | 0.00 | 01-JAN-00:10 | 153400.44 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 3617.53 | 26-DEC-07:10 |
General:Heating:EnergyTransfer | 126.43 | 0.00 | 01-JAN-00:10 | 153400.44 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 3617.53 | 26-DEC-07:10 |
Cooling:EnergyTransfer | 983.74 | 0.00 | 01-JAN-00:10 | 165389.55 | 26-JUN-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 211.01 | 0.00 | 01-JAN-00:10 | 26404.18 | 05-SEP-08:00 |
General:Cooling:EnergyTransfer | 983.74 | 0.00 | 01-JAN-00:10 | 165389.55 | 26-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 211.01 | 0.00 | 01-JAN-00:10 | 26404.18 | 05-SEP-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 54.68 | 0.00 | 01-JAN-00:10 | 14129.42 | 23-DEC-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.32 | 0.00 | 01-JAN-00:10 | 14129.42 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 21.32 | 0.00 | 01-JAN-00:10 | 14129.42 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.36 | 0.00 | 01-JAN-00:10 | 12057.93 | 16-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.36 | 0.00 | 01-JAN-00:10 | 12057.93 | 16-AUG-15:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 25.61 | 0.00 | 01-JAN-00:10 | 6965.20 | 06-FEB-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.00 | 0.00 | 01-JAN-00:10 | 6965.20 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.00 | 0.00 | 01-JAN-00:10 | 6965.20 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.60 | 0.00 | 01-JAN-00:10 | 5197.33 | 17-JUL-10:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 15.60 | 0.00 | 01-JAN-00:10 | 5197.33 | 17-JUL-10:20 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 25.90 | 0.00 | 01-JAN-00:10 | 5332.26 | 17-JUL-15:30 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 6.03 | 0.00 | 01-JAN-00:10 | 4007.05 | 06-FEB-09:10 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 6.03 | 0.00 | 01-JAN-00:10 | 4007.05 | 06-FEB-09:10 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 19.87 | 0.00 | 01-JAN-00:10 | 5332.26 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 19.87 | 0.00 | 01-JAN-00:10 | 5332.26 | 17-JUL-15:30 |
EnergyTransfer:Zone:CORE_MID | 137.05 | 0.00 | 01-JAN-00:10 | 18243.48 | 17-JUL-07:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.66 | 0.00 | 01-JAN-00:10 | 15725.24 | 26-DEC-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.66 | 0.00 | 01-JAN-00:10 | 15725.24 | 26-DEC-07:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 136.39 | 0.00 | 01-JAN-00:10 | 18243.48 | 17-JUL-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 136.39 | 0.00 | 01-JAN-00:10 | 18243.48 | 17-JUL-07:30 |
EnergyTransfer:Zone:CORE_TOP | 134.09 | 0.00 | 01-JAN-00:10 | 26754.71 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 6.39 | 0.00 | 01-JAN-00:10 | 26754.71 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 6.39 | 0.00 | 01-JAN-00:10 | 26754.71 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 127.70 | 0.00 | 01-JAN-00:10 | 20078.39 | 17-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 127.70 | 0.00 | 01-JAN-00:10 | 20078.39 | 17-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.10 | 0.00 | 01-JAN-00:10 | 9000.49 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.40 | 0.00 | 01-JAN-00:10 | 9000.49 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.40 | 0.00 | 01-JAN-00:10 | 9000.49 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.70 | 0.00 | 01-JAN-00:10 | 7722.63 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 28.70 | 0.00 | 01-JAN-00:10 | 7722.63 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 41.38 | 0.00 | 01-JAN-00:10 | 9507.74 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.07 | 0.00 | 01-JAN-00:10 | 8581.02 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.07 | 0.00 | 01-JAN-00:10 | 8581.02 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 34.30 | 0.00 | 01-JAN-00:10 | 9507.74 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 34.30 | 0.00 | 01-JAN-00:10 | 9507.74 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 66.89 | 0.00 | 01-JAN-00:10 | 13345.05 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.66 | 0.00 | 01-JAN-00:10 | 11461.00 | 21-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.66 | 0.00 | 01-JAN-00:10 | 11461.00 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 58.23 | 0.00 | 01-JAN-00:10 | 13345.05 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 58.23 | 0.00 | 01-JAN-00:10 | 13345.05 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 40.90 | 0.00 | 01-JAN-00:10 | 10455.98 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 7.84 | 0.00 | 01-JAN-00:10 | 8567.28 | 23-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 7.84 | 0.00 | 01-JAN-00:10 | 8567.28 | 23-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 33.06 | 0.00 | 01-JAN-00:10 | 10455.98 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 33.06 | 0.00 | 01-JAN-00:10 | 10455.98 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 30.84 | 0.00 | 01-JAN-00:10 | 6462.53 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.79 | 0.00 | 01-JAN-00:10 | 6462.53 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.79 | 0.00 | 01-JAN-00:10 | 6462.53 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 25.04 | 0.00 | 01-JAN-00:10 | 6089.11 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 25.04 | 0.00 | 01-JAN-00:10 | 6089.11 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 33.51 | 0.00 | 01-JAN-00:10 | 7582.56 | 17-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.55 | 0.00 | 01-JAN-00:10 | 5851.99 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.55 | 0.00 | 01-JAN-00:10 | 5851.99 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.96 | 0.00 | 01-JAN-00:10 | 7582.56 | 17-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 30.96 | 0.00 | 01-JAN-00:10 | 7582.56 | 17-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 62.99 | 0.00 | 01-JAN-00:10 | 14017.22 | 21-DEC-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 19.87 | 0.00 | 01-JAN-00:10 | 14017.22 | 21-DEC-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 19.87 | 0.00 | 01-JAN-00:10 | 14017.22 | 21-DEC-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 43.13 | 0.00 | 01-JAN-00:10 | 12056.46 | 26-JUN-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 43.13 | 0.00 | 01-JAN-00:10 | 12056.46 | 26-JUN-16:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 31.04 | 0.00 | 01-JAN-00:10 | 7954.73 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.72 | 0.00 | 01-JAN-00:10 | 5843.30 | 06-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.72 | 0.00 | 01-JAN-00:10 | 5843.30 | 06-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.32 | 0.00 | 01-JAN-00:10 | 7954.73 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 28.32 | 0.00 | 01-JAN-00:10 | 7954.73 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 35.11 | 0.00 | 01-JAN-00:10 | 7214.39 | 06-FEB-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 5.22 | 0.00 | 01-JAN-00:10 | 7214.39 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 5.22 | 0.00 | 01-JAN-00:10 | 7214.39 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 29.89 | 0.00 | 01-JAN-00:10 | 7041.12 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 29.89 | 0.00 | 01-JAN-00:10 | 7041.12 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 37.95 | 0.00 | 01-JAN-00:10 | 9256.23 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.85 | 0.00 | 01-JAN-00:10 | 6081.11 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.85 | 0.00 | 01-JAN-00:10 | 6081.11 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 35.10 | 0.00 | 01-JAN-00:10 | 9256.23 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 35.10 | 0.00 | 01-JAN-00:10 | 9256.23 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 62.73 | 0.00 | 01-JAN-00:10 | 12142.38 | 28-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.08 | 0.00 | 01-JAN-00:10 | 9111.15 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.08 | 0.00 | 01-JAN-00:10 | 9111.15 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 59.64 | 0.00 | 01-JAN-00:10 | 12142.38 | 28-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 59.64 | 0.00 | 01-JAN-00:10 | 12142.38 | 28-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.40 | 0.00 | 01-JAN-00:10 | 9695.85 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.97 | 0.00 | 01-JAN-00:10 | 6126.92 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.97 | 0.00 | 01-JAN-00:10 | 6126.92 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.43 | 0.00 | 01-JAN-00:10 | 9695.85 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.43 | 0.00 | 01-JAN-00:10 | 9695.85 | 16-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 51.76 | 0.00 | 01-JAN-00:10 | 6544.92 | 14-FEB-12:10 |
PlantLoopHeatingDemand:Plant | 51.76 | 0.00 | 01-JAN-00:10 | 6544.92 | 14-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 51.76 | 0.00 | 01-JAN-00:10 | 6544.92 | 14-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 51.76 | 0.00 | 01-JAN-00:10 | 6544.92 | 14-FEB-12:10 |
EnergyTransfer:HVAC | 883.29 | 0.00 | 01-JAN-00:10 | 226183.98 | 26-JUN-15:20 |
HeatingCoils:EnergyTransfer | 252.00 | 0.00 | 01-JAN-00:10 | 224685.59 | 23-DEC-07:10 |
CoolingCoils:EnergyTransfer | 631.29 | 0.00 | 01-JAN-00:10 | 226183.98 | 26-JUN-15:20 |
EnergyTransfer:Plant | 51.76 | 0.00 | 01-JAN-00:10 | 6544.92 | 14-FEB-12:10 |
WaterSystems:EnergyTransfer | 51.76 | 0.00 | 01-JAN-00:10 | 6544.92 | 14-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 51.76 | 0.00 | 01-JAN-00:10 | 6544.92 | 14-FEB-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.004 | -211.005 | 0.000 | 0.000 | 32.918 | 48.333 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -106.417 |
CORE_MID | 0.000 | 0.000 | 0.658 | -136.390 | 0.000 | 0.000 | 34.249 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -62.275 |
CORE_TOP | 0.000 | 0.000 | 6.386 | -127.700 | 0.000 | 0.000 | 35.006 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -77.450 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 13.402 | -28.702 | 0.000 | 0.000 | 7.553 | 5.975 | 24.333 | 19.143 | 0.000 | 0.064 | 0.000 | 0.000 | -32.091 | 0.000 | -2.910 | -6.767 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 7.074 | -34.304 | 0.000 | 0.000 | 4.690 | 3.770 | 15.404 | 42.637 | 0.000 | 0.042 | 0.000 | 0.000 | -20.639 | 0.000 | -1.979 | -16.695 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 8.656 | -58.231 | 0.000 | 0.000 | 7.258 | 5.866 | 24.332 | 88.148 | 0.000 | 0.062 | 0.000 | 0.000 | -31.352 | 0.000 | -3.061 | -41.680 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 7.840 | -33.055 | 0.000 | 0.000 | 4.775 | 3.723 | 15.403 | 39.251 | 0.000 | 0.043 | 0.000 | 0.000 | -21.231 | 0.000 | -1.983 | -14.767 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 5.793 | -25.043 | 0.000 | 0.000 | 7.543 | 5.959 | 24.333 | 19.440 | 0.000 | 0.037 | 0.000 | 0.000 | -33.210 | 0.000 | -1.612 | -3.240 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.548 | -30.957 | 0.000 | 0.000 | 4.645 | 3.763 | 15.404 | 42.763 | 0.000 | 0.023 | 0.001 | 0.000 | -21.838 | 0.000 | -1.122 | -15.227 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 19.865 | -43.125 | 0.000 | 0.000 | 7.442 | 5.858 | 24.332 | 88.859 | 0.000 | 3.466 | 0.001 | 0.000 | -33.234 | 0.000 | -45.499 | -27.964 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 2.719 | -28.320 | 0.000 | 0.000 | 4.713 | 3.716 | 15.403 | 39.390 | 0.000 | 0.023 | 0.000 | 0.000 | -22.441 | 0.000 | -1.123 | -14.080 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 5.221 | -29.893 | 0.000 | 0.000 | 7.468 | 5.975 | 24.333 | 18.910 | 0.000 | 0.055 | 4.387 | 0.000 | -33.895 | 0.000 | -2.561 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.854 | -35.097 | 0.000 | 0.000 | 3.442 | 3.770 | 15.404 | 42.460 | 0.000 | 0.036 | 0.002 | 0.000 | -21.711 | 0.000 | -1.735 | -9.423 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 3.084 | -59.641 | 0.000 | 0.000 | 7.167 | 5.867 | 24.332 | 87.878 | 0.000 | 0.052 | 0.002 | 0.000 | -33.076 | 0.000 | -2.691 | -32.972 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.972 | -33.430 | 0.000 | 0.000 | 4.717 | 3.723 | 15.403 | 39.095 | 0.000 | 0.036 | 0.000 | 0.000 | -22.404 | 0.000 | -1.742 | -8.369 |
TOPFLOOR_PLENUM | 21.321 | -33.360 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.065 | 16.418 | 0.000 | 0.000 | 0.000 | -4.444 | -0.004 |
MIDFLOOR_PLENUM | 10.003 | -15.605 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.080 | 9.945 | 0.000 | 0.000 | 0.000 | -4.424 | -0.001 |
FIRSTFLOOR_PLENUM | 6.032 | -19.872 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.062 | 17.343 | 0.000 | 0.000 | 0.000 | -3.564 | -0.000 |
Total Facility | 37.356 | -68.837 | 89.076 | -914.893 | 0.000 | 0.000 | 173.587 | 202.963 | 705.434 | 567.973 | 0.000 | 4.145 | 48.100 | 0.000 | -327.121 | 0.000 | -80.449 | -437.332 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-SEP-04:02 | 0.00 | 0.00 | 0.00 | -41748.39 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 36873.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-04:02 | 0.00 | 0.00 | 0.00 | -30394.14 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 27483.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JUL-04:03 | 0.00 | 0.00 | 0.00 | -32470.71 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 29559.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-17:21 | 0.00 | 0.00 | 0.00 | -11025.62 | 0.00 | 0.00 | 0.00 | 23.57 | 386.10 | 3221.37 | 0.00 | 105.21 | 7289.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 09-JUL-09:02 | 0.00 | 0.00 | 0.00 | -13605.30 | 0.00 | 0.00 | 14.37 | 14.92 | 302.86 | 9530.04 | 0.00 | 0.00 | 3758.63 | 0.00 | -0.00 | 0.00 | -15.52 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-13:21 | 0.00 | 0.00 | 0.00 | -17392.00 | 0.00 | 0.00 | 21.95 | 23.57 | 478.41 | 15191.24 | 0.00 | 0.00 | 1831.52 | 0.00 | -0.00 | 0.00 | -154.70 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:31 | 0.00 | 0.00 | 0.00 | -15940.55 | 0.00 | 0.00 | 11.23 | 14.92 | 302.86 | 10936.92 | 0.00 | 1.41 | 4673.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 17-JUL-06:03 | 0.00 | 0.00 | 0.00 | -6756.59 | 0.00 | 0.00 | 145.69 | 141.46 | 637.89 | 2592.33 | 0.00 | 0.00 | 3241.97 | 0.00 | -0.00 | 0.00 | -2.74 | 0.00 |
PERIMETER_BOT_ZN_2 | 06-AUG-09:01 | 0.00 | 0.00 | 0.00 | -11095.12 | 0.00 | 0.00 | 15.36 | 14.92 | 302.86 | 10197.64 | 0.00 | 0.00 | 570.74 | 0.00 | -0.00 | 0.00 | -6.40 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-12:31 | 0.00 | 0.00 | 0.00 | -13262.72 | 0.00 | 0.00 | 23.73 | 23.57 | 478.41 | 12774.70 | 0.00 | 5.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -42.70 |
PERIMETER_BOT_ZN_4 | 25-JUN-16:31 | 0.00 | 0.00 | 0.00 | -12202.56 | 0.00 | 0.00 | 13.81 | 14.92 | 302.86 | 10593.54 | 0.00 | 25.40 | 1252.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-11:42 | 0.00 | 0.00 | 0.00 | -9377.29 | 0.00 | 0.00 | 27.65 | 23.57 | 478.42 | 4516.25 | 0.00 | 140.91 | 4190.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-09:01 | 0.00 | 0.00 | 0.00 | -13987.81 | 0.00 | 0.00 | 13.36 | 14.92 | 302.86 | 10116.03 | 0.00 | 0.00 | 3553.52 | 0.00 | -0.00 | 0.00 | -12.89 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-12:41 | 0.00 | 0.00 | 0.00 | -15554.56 | 0.00 | 0.00 | 21.85 | 23.57 | 478.41 | 12769.73 | 0.00 | 27.79 | 2233.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 10-SEP-17:21 | 0.00 | 0.00 | 0.00 | -15034.61 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 7134.64 | 0.00 | 7.24 | 7633.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 16-AUG-15:10 | 0.00 | -12059.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 | 12041.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 17-JUL-10:20 | 0.00 | -5197.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.35 | 5161.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 17-JUL-12:07 | 0.00 | -6477.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 | 6453.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-06:03 | 0.00 | -6350.60 | 0.00 | -159142.02 | 0.00 | 0.00 | 3516.40 | 5640.25 | 21098.80 | 32705.49 | 0.00 | 0.00 | 104160.80 | 0.00 | 0.00 | 0.00 | -1629.13 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 06-FEB-07:01 | 0.00 | 0.00 | 16839.53 | 0.00 | 0.00 | 0.00 | 887.44 | 1406.75 | 8796.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27930.51 |
CORE_MID | 26-DEC-06:01 | 0.00 | 0.00 | 20464.78 | 0.00 | 0.00 | 0.00 | 500.42 | 468.92 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24460.04 |
CORE_TOP | 06-FEB-05:01 | 0.00 | 0.00 | 30756.14 | 0.00 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33667.12 |
PERIMETER_TOP_ZN_3 | 24-DEC-04:12 | 0.00 | 0.00 | 10410.98 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3539.88 | 0.00 | -581.25 | -6725.37 |
PERIMETER_TOP_ZN_2 | 24-DEC-04:12 | 0.00 | 0.00 | 11370.93 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2424.46 | 0.00 | -394.46 | -8827.73 |
PERIMETER_TOP_ZN_1 | 24-DEC-05:32 | 0.00 | 0.00 | 13932.92 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3504.74 | 0.00 | -449.79 | -10413.91 |
PERIMETER_TOP_ZN_4 | 24-DEC-02:52 | 0.00 | 0.00 | 12441.67 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2546.24 | 0.00 | -478.40 | -9692.73 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 7454.13 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2668.13 | 0.00 | -153.70 | -5245.95 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 8831.83 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1769.56 | 0.00 | -103.32 | -7347.43 |
PERIMETER_BOT_ZN_1 | 22-DEC-07:10 | 0.00 | 0.00 | 14456.29 | 0.00 | 0.00 | 0.00 | 208.76 | 296.56 | 637.88 | 0.00 | 0.00 | 0.00 | 19249.92 | 0.00 | -3864.12 | 0.00 | -30985.28 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 8863.29 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1807.97 | 0.00 | -103.34 | -7340.45 |
PERIMETER_MID_ZN_3 | 24-DEC-07:32 | 0.00 | 0.00 | 8482.23 | 0.00 | 0.00 | 0.00 | 58.22 | 46.06 | 478.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3207.93 | 0.00 | -387.53 | -5469.46 |
PERIMETER_MID_ZN_2 | 21-DEC-05:11 | 0.00 | 0.00 | 9151.02 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2915.17 | 0.00 | -235.74 | -6388.58 |
PERIMETER_MID_ZN_1 | 21-DEC-05:11 | 0.00 | 0.00 | 11721.50 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4398.18 | 0.00 | -353.57 | -7583.40 |
PERIMETER_MID_ZN_4 | 21-DEC-05:11 | 0.00 | 0.00 | 9133.49 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2918.16 | 0.00 | -235.87 | -6367.93 |
TOPFLOOR_PLENUM | 23-DEC-06:13 | 16225.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -256.09 | -15969.54 |
MIDFLOOR_PLENUM | 06-FEB-07:11 | 8054.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -122.60 | -7931.51 |
FIRSTFLOOR_PLENUM | 16-OCT-05:02 | 5253.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -44.10 | -5208.98 |
Total Facility | 06-FEB-07:01 | 22627.09 | 0.00 | 159243.52 | 0.00 | 0.00 | 0.00 | 4631.43 | 7126.03 | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29438.89 | 0.00 | -32185.15 | -153102.83 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.3708 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.6762 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.9470 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.0465 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 6.5171 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 5.9551 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 3.1854 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4626 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.9735 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5208 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 3.2585 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.6108 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3146 | 3.3146 | 0.8054 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3871 | 2.3871 | 0.7830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5946 | 2.5946 | 0.8173 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8172 | 0.8172 | 0.1724 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9140 | 0.9140 | 0.1828 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1156 | 1.1156 | 0.2231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0756 | 1.0756 | 0.2151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6210 | 0.6210 | 0.1702 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7420 | 0.7420 | 0.1484 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8677 | 0.8677 | 0.1735 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8255 | 0.8255 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6980 | 0.6980 | 0.1654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8969 | 0.8969 | 0.1794 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9903 | 0.9903 | 0.1981 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9746 | 0.9746 | 0.1949 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.3708 | 5.6762 | 6.3708 | 1.4626 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.9470 | 5.0465 | 5.9470 | 1.5208 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 6.5171 | 5.9551 | 6.5171 | 1.6108 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6573 | 1.6573 | 0.8054 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1936 | 1.1936 | 0.7830 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2973 | 1.2973 | 0.8173 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4086 | 0.4086 | 0.1724 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4570 | 0.4570 | 0.1828 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5578 | 0.5578 | 0.2231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5378 | 0.5378 | 0.2151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3105 | 0.3105 | 0.1702 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3710 | 0.3710 | 0.1484 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4339 | 0.4339 | 0.1735 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4127 | 0.4127 | 0.1651 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3490 | 0.3490 | 0.1654 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4485 | 0.4485 | 0.1794 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4952 | 0.4952 | 0.1981 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4873 | 0.4873 | 0.1949 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 3.1854 | 1.4626 | 1.4626 | 1.4626 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.9735 | 1.5208 | 1.5208 | 1.5208 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 3.2585 | 1.6108 | 1.6108 | 1.6108 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 355.17 |
Number of hours cooling loads not met | 194.00 |
Number of hours not met | 549.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 142.36 | 164237.08 | 137.05 | 103522.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 156.58 | 76338.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 202.96 | 21377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 49.77 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.66 | 833.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 112.87 | 32528.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 110.83 | 9794.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1381.64 |
Natural Gas | 0.00 | 247.88 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1629.52 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 40.74 |
Space Heating | 28.57 |
Space Cooling | 31.43 |
Fans (All) | 22.65 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 277.32 |
Subtotal | 277.32 |
Natural Gas [MJ/m2] | |
Space Heating | 27.51 |
Service Water Heating | 22.24 |
Miscellaneous (All) | 49.75 |
Subtotal | 49.75 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 12.46 |
Space Heating | 17.15 |
Space Cooling | 9.61 |
Fans (All) | 6.93 |
Service Water Heating | 6.80 |
Receptacle Equipment | 43.29 |
Miscellaneous | 3.77 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8740.17 | 19.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8736.50 | 23.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8749.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8743.67 | 16.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8738.67 | 21.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8681.50 | 78.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8681.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 78.50 | 0.00 | 0.00 | 0.00 |
Average | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
Sum | 157443.00 | 237.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8716.33 | 43.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8740.67 | 19.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8745.83 | 14.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8743.17 | 16.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8739.33 | 20.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8716.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 43.67 | 0.00 | 0.00 | 0.00 |
Average | 8748.86 | 11.14 | 0.00 | 0.00 | 0.00 |
Sum | 157479.50 | 200.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128289.33 | 14.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128299.33 | 4.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 14.67 | 0.00 | 0.00 | 0.00 |
Average | 34142.26 | 1.07 | 0.00 | 0.00 | 0.00 |
Sum | 614560.67 | 19.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113299E+11 | 16153.25 | 26-JAN-16:50 | 6.33 | 1.96 | 0.194701E+10 | 2606.65 | 27-JAN-10:20 | 2.33 | 2.17 |
February | 0.102638E+11 | 18707.23 | 23-FEB-08:03 | 1.00 | 0.54 | 0.174962E+10 | 2606.63 | 15-FEB-14:20 | 1.00 | 0.54 |
March | 0.145787E+11 | 29095.68 | 16-MAR-05:03 | 7.83 | 0.85 | 0.213111E+10 | 2606.62 | 02-MAR-10:20 | 7.83 | 0.85 |
April | 0.130516E+11 | 19372.78 | 13-APR-05:02 | 3.00 | 0.64 | 0.189915E+10 | 2609.54 | 14-APR-09:00 | 1.00 | 0.54 |
May | 0.194889E+11 | 35061.21 | 08-MAY-05:03 | 6.00 | 1.12 | 0.207486E+10 | 2608.65 | 02-MAY-09:20 | 6.00 | 1.12 |
June | 0.253759E+11 | 37705.12 | 24-JUN-05:03 | 14.18 | 10.44 | 0.207033E+10 | 2606.71 | 20-JUN-13:00 | 14.18 | 10.44 |
July | 0.247952E+11 | 40678.31 | 17-JUL-04:03 | 19.00 | 9.40 | 0.192426E+10 | 2606.67 | 14-JUL-09:30 | 19.00 | 9.40 |
August | 0.265967E+11 | 39246.65 | 28-AUG-04:03 | 14.17 | 14.06 | 0.216034E+10 | 2606.68 | 29-AUG-09:00 | 22.00 | 14.30 |
September | 0.233701E+11 | 41747.77 | 05-SEP-04:02 | 14.40 | 9.67 | 0.191785E+10 | 2606.89 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.178873E+11 | 35847.57 | 10-OCT-06:01 | 8.33 | 4.27 | 0.198607E+10 | 2606.75 | 03-OCT-13:09 | 8.33 | 4.27 |
November | 0.134897E+11 | 21817.58 | 10-NOV-06:03 | 5.67 | 4.71 | 0.195575E+10 | 2606.63 | 29-NOV-10:39 | -9.0 | -9.0 |
December | 0.107780E+11 | 17299.54 | 05-DEC-08:03 | -0.8 | -3.2 | 0.186023E+10 | 2606.63 | 12-DEC-10:20 | 6.33 | 0.77 |
Annual Sum or Average | 0.211006E+12 | 0.236766E+11 | ||||||||
Minimum of Months | 0.102638E+11 | 16153.25 | -0.8 | -3.2 | 0.174962E+10 | 2606.62 | -9.0 | -9.0 | ||
Maximum of Months | 0.265967E+11 | 41747.77 | 19.00 | 14.06 | 0.216034E+10 | 2609.54 | 22.00 | 14.30 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292406E+09 | 3005.70 | 20-JAN-14:10 | 20.83 | 6.93 | 0.00 | 0.00 | 01-JAN-00:10 | 20.83 | 6.93 |
February | 0.390387E+09 | 3218.70 | 18-FEB-13:50 | 20.00 | 7.73 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 7.73 |
March | 0.126249E+10 | 6760.89 | 14-MAR-14:10 | 23.00 | 7.59 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 7.59 |
April | 0.127921E+10 | 5942.97 | 21-APR-13:30 | 15.50 | 6.04 | 0.00 | 0.00 | 01-APR-00:10 | 15.50 | 6.04 |
May | 0.301096E+10 | 8721.98 | 31-MAY-14:30 | 28.00 | 14.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 14.75 |
June | 0.718840E+10 | 12053.90 | 26-JUN-13:30 | 37.15 | 15.33 | 0.00 | 0.00 | 01-JUN-00:10 | 37.15 | 15.33 |
July | 0.660473E+10 | 10613.93 | 17-JUL-14:00 | 35.00 | 14.93 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 14.93 |
August | 0.668800E+10 | 12057.93 | 16-AUG-15:10 | 36.17 | 16.19 | 0.00 | 0.00 | 01-AUG-00:10 | 36.17 | 16.19 |
September | 0.432749E+10 | 9027.70 | 12-SEP-14:50 | 29.40 | 13.78 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.78 |
October | 0.155036E+10 | 6912.49 | 11-OCT-15:00 | 26.00 | 9.46 | 0.00 | 0.00 | 01-OCT-00:10 | 26.00 | 9.46 |
November | 0.563904E+09 | 3573.79 | 09-NOV-13:10 | 20.00 | 8.90 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 8.90 |
December | 0.202110E+09 | 2162.60 | 17-DEC-14:08 | 17.92 | 5.75 | 0.00 | 0.00 | 01-DEC-00:10 | 17.92 | 5.75 |
Annual Sum or Average | 0.333605E+11 | 0.00 | ||||||||
Minimum of Months | 0.202110E+09 | 2162.60 | 15.50 | 5.75 | 0.00 | 0.00 | 15.50 | 5.75 | ||
Maximum of Months | 0.718840E+10 | 12057.93 | 37.15 | 16.19 | 0.00 | 0.00 | 37.15 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97739576.36 | 2220.67 | 05-JAN-05:01 | -17.0 | -17.0 | 0.00 | 0.00 | 01-JAN-00:10 | -17.0 | -17.0 |
February | 87617122.70 | 1930.23 | 28-FEB-07:01 | -2.7 | -3.1 | 0.00 | 0.00 | 01-FEB-00:10 | -2.7 | -3.1 |
March | 0.362474E+09 | 2342.39 | 15-MAR-16:00 | 19.00 | 5.38 | 0.00 | 0.00 | 01-MAR-00:10 | 19.00 | 5.38 |
April | 0.308637E+09 | 1861.24 | 11-APR-06:01 | -0.5 | -3.2 | 0.00 | 0.00 | 01-APR-00:10 | -0.5 | -3.2 |
May | 0.110723E+10 | 2574.71 | 18-MAY-15:00 | 23.00 | 11.61 | 0.00 | 0.00 | 01-MAY-00:10 | 23.00 | 11.61 |
June | 0.358686E+10 | 5074.97 | 26-JUN-15:20 | 39.20 | 15.68 | 0.00 | 0.00 | 01-JUN-00:10 | 39.20 | 15.68 |
July | 0.354592E+10 | 5197.33 | 17-JUL-10:20 | 34.33 | 14.36 | 0.00 | 0.00 | 01-JUL-00:10 | 34.33 | 14.36 |
August | 0.348796E+10 | 4618.45 | 21-AUG-14:40 | 27.00 | 14.47 | 0.00 | 0.00 | 01-AUG-00:10 | 27.00 | 14.47 |
September | 0.230614E+10 | 4385.17 | 05-SEP-15:40 | 24.60 | 13.98 | 0.00 | 0.00 | 01-SEP-00:10 | 24.60 | 13.98 |
October | 0.508173E+09 | 2866.05 | 11-OCT-16:00 | 24.00 | 8.61 | 0.00 | 0.00 | 01-OCT-00:10 | 24.00 | 8.61 |
November | 0.151019E+09 | 1736.62 | 30-NOV-05:01 | -12.8 | -13.4 | 0.00 | 0.00 | 01-NOV-00:10 | -12.8 | -13.4 |
December | 55155858.64 | 2627.61 | 21-DEC-05:11 | -18.3 | -18.5 | 0.00 | 0.00 | 01-DEC-00:10 | -18.3 | -18.5 |
Annual Sum or Average | 0.156049E+11 | 0.00 | ||||||||
Minimum of Months | 55155858.64 | 1736.62 | -18.3 | -18.5 | 0.00 | 0.00 | -18.3 | -18.5 | ||
Maximum of Months | 0.358686E+10 | 5197.33 | 39.20 | 15.68 | 0.00 | 0.00 | 39.20 | 15.68 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245713E+09 | 2813.44 | 27-JAN-07:01 | -1.7 | -1.7 | 0.00 | 0.00 | 01-JAN-00:10 | -1.7 | -1.7 |
February | 0.216529E+09 | 2559.16 | 28-FEB-07:01 | -2.7 | -3.1 | 0.00 | 0.00 | 01-FEB-00:10 | -2.7 | -3.1 |
March | 0.657080E+09 | 2644.33 | 15-MAR-15:40 | 19.33 | 5.50 | 0.00 | 0.00 | 01-MAR-00:10 | 19.33 | 5.50 |
April | 0.494866E+09 | 2204.19 | 14-APR-17:01 | 2.67 | 0.26 | 0.00 | 0.00 | 01-APR-00:10 | 2.67 | 0.26 |
May | 0.160646E+10 | 2830.74 | 18-MAY-15:10 | 22.33 | 11.65 | 0.00 | 0.00 | 01-MAY-00:10 | 22.33 | 11.65 |
June | 0.394151E+10 | 6395.87 | 26-JUN-12:07 | 36.18 | 15.20 | 0.00 | 0.00 | 01-JUN-00:10 | 36.18 | 15.20 |
July | 0.388014E+10 | 6477.24 | 17-JUL-12:07 | 36.00 | 14.76 | 0.00 | 0.00 | 01-JUL-00:10 | 36.00 | 14.76 |
August | 0.406539E+10 | 4918.80 | 18-AUG-12:07 | 33.83 | 13.78 | 0.00 | 0.00 | 01-AUG-00:10 | 33.83 | 13.78 |
September | 0.308363E+10 | 4809.62 | 05-SEP-06:13 | 14.00 | 7.55 | 0.00 | 0.00 | 01-SEP-00:10 | 14.00 | 7.55 |
October | 0.110985E+10 | 3594.14 | 11-OCT-16:20 | 23.33 | 8.54 | 0.00 | 0.00 | 01-OCT-00:10 | 23.33 | 8.54 |
November | 0.389453E+09 | 2518.88 | 29-NOV-17:10 | -11.3 | -11.3 | 0.00 | 0.00 | 01-NOV-00:10 | -11.3 | -11.3 |
December | 0.181737E+09 | 2835.09 | 19-DEC-17:10 | -17.0 | -17.2 | 0.00 | 0.00 | 01-DEC-00:10 | -17.0 | -17.2 |
Annual Sum or Average | 0.198724E+11 | 0.00 | ||||||||
Minimum of Months | 0.181737E+09 | 2204.19 | -17.0 | -17.2 | 0.00 | 0.00 | -17.0 | -17.2 | ||
Maximum of Months | 0.406539E+10 | 6477.24 | 36.18 | 15.20 | 0.00 | 0.00 | 36.18 | 15.20 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.715289E+10 | 8270.46 | 24-JAN-14:40 | 17.33 | 6.54 | 0.171585E+10 | 2606.53 | 26-JAN-14:20 | 9.00 | 2.97 |
February | 0.631111E+10 | 8035.25 | 27-FEB-13:10 | 14.00 | 4.75 | 0.155256E+10 | 2606.55 | 28-FEB-14:00 | 4.00 | 3.02 |
March | 0.909479E+10 | 13098.56 | 15-MAR-16:00 | 19.00 | 5.38 | 0.195831E+10 | 2606.64 | 17-MAR-09:09 | 6.83 | 6.35 |
April | 0.813292E+10 | 11404.24 | 21-APR-16:00 | 13.00 | 5.24 | 0.175363E+10 | 2606.71 | 13-APR-13:00 | 13.00 | 5.24 |
May | 0.123771E+11 | 17656.36 | 18-MAY-05:03 | 11.67 | 7.89 | 0.203802E+10 | 2606.66 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.177892E+11 | 29736.55 | 26-JUN-04:03 | 13.85 | 9.53 | 0.206680E+10 | 2606.67 | 08-JUN-13:09 | 13.85 | 9.53 |
July | 0.175833E+11 | 30135.71 | 24-JUL-04:03 | 18.00 | 14.77 | 0.192057E+10 | 2606.64 | 11-JUL-09:30 | 18.00 | 14.77 |
August | 0.180831E+11 | 29803.03 | 21-AUG-04:03 | 19.17 | 11.93 | 0.215695E+10 | 2606.65 | 21-AUG-09:09 | 25.33 | 14.07 |
September | 0.151982E+11 | 30393.34 | 05-SEP-04:02 | 14.40 | 9.67 | 0.190959E+10 | 2606.85 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.101925E+11 | 17683.94 | 11-OCT-05:02 | 10.17 | 3.29 | 0.188378E+10 | 2606.63 | 03-OCT-13:09 | 10.17 | 3.29 |
November | 0.794832E+10 | 10779.80 | 08-NOV-16:40 | 14.67 | 6.46 | 0.177190E+10 | 2606.57 | 10-NOV-10:39 | 4.67 | 4.67 |
December | 0.652705E+10 | 7541.96 | 15-DEC-13:30 | 11.50 | 3.22 | 0.161708E+10 | 2543.37 | 04-DEC-14:00 | 11.50 | 3.22 |
Annual Sum or Average | 0.136390E+12 | 0.223451E+11 | ||||||||
Minimum of Months | 0.631111E+10 | 7541.96 | 10.17 | 3.22 | 0.155256E+10 | 2543.37 | 4.00 | 2.97 | ||
Maximum of Months | 0.180831E+11 | 30393.34 | 19.17 | 14.77 | 0.215695E+10 | 2606.85 | 25.33 | 14.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.561726E+10 | 8331.09 | 20-JAN-14:00 | 21.00 | 6.96 | 0.160533E+10 | 2539.11 | 25-JAN-14:00 | 14.00 | 4.48 |
February | 0.510638E+10 | 7190.47 | 26-FEB-13:32 | 17.33 | 4.46 | 0.146742E+10 | 2582.66 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.803610E+10 | 14126.06 | 15-MAR-15:40 | 19.33 | 5.50 | 0.186955E+10 | 2606.56 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.749157E+10 | 12888.92 | 21-APR-14:00 | 15.00 | 5.55 | 0.168380E+10 | 2606.71 | 13-APR-13:00 | 15.00 | 5.55 |
May | 0.120373E+11 | 15461.04 | 18-MAY-15:20 | 21.67 | 11.66 | 0.200307E+10 | 2606.65 | 18-MAY-09:09 | 21.67 | 11.66 |
June | 0.186086E+11 | 23569.73 | 26-JUN-05:03 | 17.07 | 11.32 | 0.206328E+10 | 2606.68 | 08-JUN-13:09 | 17.07 | 11.32 |
July | 0.182043E+11 | 32471.26 | 17-JUL-04:03 | 19.00 | 9.40 | 0.191831E+10 | 2606.64 | 11-JUL-09:30 | 19.00 | 9.40 |
August | 0.184135E+11 | 29150.69 | 21-AUG-05:03 | 19.92 | 12.21 | 0.215254E+10 | 2606.65 | 10-AUG-09:50 | 19.92 | 12.21 |
September | 0.144867E+11 | 30904.81 | 11-SEP-05:03 | 17.88 | 8.62 | 0.189000E+10 | 2606.84 | 05-SEP-09:09 | 17.88 | 8.62 |
October | 0.855867E+10 | 14939.18 | 11-OCT-16:00 | 24.00 | 8.61 | 0.177811E+10 | 2606.59 | 11-OCT-13:09 | 24.00 | 8.61 |
November | 0.630368E+10 | 9813.04 | 08-NOV-16:20 | 16.33 | 7.18 | 0.164727E+10 | 2606.55 | 08-NOV-14:09 | 16.33 | 7.18 |
December | 0.483668E+10 | 7164.70 | 03-DEC-14:32 | 18.00 | 6.62 | 0.150935E+10 | 2453.25 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.127701E+12 | 0.215880E+11 | ||||||||
Minimum of Months | 0.483668E+10 | 7164.70 | 15.00 | 4.46 | 0.146742E+10 | 2453.25 | 9.00 | 3.00 | ||
Maximum of Months | 0.186086E+11 | 32471.26 | 24.00 | 12.21 | 0.215254E+10 | 2606.84 | 24.00 | 12.21 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.458822E+09 | 1676.66 | 20-JAN-14:00 | 21.00 | 6.96 | 0.314707E+09 | 505.56 | 20-JAN-16:19 | 16.00 | 6.84 |
February | 0.425290E+09 | 1437.60 | 26-FEB-13:32 | 17.33 | 4.46 | 0.285765E+09 | 510.02 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.110552E+10 | 3370.78 | 14-MAR-14:40 | 23.00 | 7.59 | 0.369000E+09 | 549.48 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.122745E+10 | 3309.23 | 20-APR-13:30 | 21.50 | 8.83 | 0.338480E+09 | 549.51 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.289056E+10 | 5472.92 | 17-MAY-13:30 | 29.00 | 11.78 | 0.413863E+09 | 549.50 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.585019E+10 | 11025.62 | 25-JUN-17:21 | 32.15 | 14.00 | 0.435229E+09 | 549.98 | 12-JUN-13:09 | 32.15 | 14.00 |
July | 0.567688E+10 | 10934.11 | 09-JUL-13:42 | 34.67 | 13.78 | 0.404744E+09 | 549.67 | 18-JUL-13:30 | 33.00 | 14.80 |
August | 0.519678E+10 | 6572.67 | 16-AUG-14:30 | 36.50 | 16.26 | 0.452375E+09 | 549.50 | 21-AUG-09:09 | 25.33 | 14.07 |
September | 0.354733E+10 | 6256.74 | 11-SEP-14:30 | 28.85 | 13.58 | 0.391723E+09 | 549.53 | 05-SEP-09:09 | 28.85 | 13.58 |
October | 0.134916E+10 | 3831.95 | 11-OCT-14:50 | 26.17 | 9.50 | 0.350246E+09 | 549.48 | 11-OCT-13:09 | 26.17 | 9.50 |
November | 0.659172E+09 | 1946.53 | 09-NOV-13:50 | 20.00 | 8.66 | 0.322447E+09 | 549.48 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.314859E+09 | 1376.95 | 03-DEC-14:32 | 18.00 | 6.62 | 0.298637E+09 | 487.46 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.287020E+11 | 0.437722E+10 | ||||||||
Minimum of Months | 0.314859E+09 | 1376.95 | 17.33 | 4.46 | 0.285765E+09 | 487.46 | 14.00 | 4.75 | ||
Maximum of Months | 0.585019E+10 | 11025.62 | 36.50 | 16.26 | 0.452375E+09 | 549.98 | 33.00 | 14.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.772016E+09 | 2080.76 | 20-JAN-10:10 | 14.67 | 5.12 | 0.208508E+09 | 347.86 | 24-JAN-10:09 | 11.50 | 3.54 |
February | 0.845643E+09 | 3152.64 | 27-FEB-09:30 | 9.50 | 2.73 | 0.195295E+09 | 347.87 | 23-FEB-10:09 | 9.50 | 2.73 |
March | 0.177790E+10 | 7242.62 | 12-MAR-09:02 | 14.17 | 5.14 | 0.251817E+09 | 347.88 | 27-MAR-09:00 | 0.00 | -0.5 |
April | 0.185687E+10 | 6559.41 | 21-APR-09:00 | 12.00 | 5.98 | 0.227801E+09 | 347.89 | 13-APR-13:00 | 12.00 | 5.98 |
May | 0.340688E+10 | 7393.55 | 16-MAY-08:40 | 22.00 | 11.45 | 0.268123E+09 | 347.90 | 17-MAY-09:09 | 25.33 | 11.72 |
June | 0.622505E+10 | 10377.55 | 11-JUN-09:12 | 20.73 | 10.95 | 0.275908E+09 | 348.97 | 29-JUN-09:09 | 28.58 | 13.43 |
July | 0.584475E+10 | 13604.93 | 09-JUL-09:02 | 24.67 | 12.86 | 0.256499E+09 | 348.65 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.601933E+10 | 12930.58 | 06-AUG-09:12 | 25.67 | 15.47 | 0.287089E+09 | 348.51 | 31-AUG-09:50 | 26.67 | 13.56 |
September | 0.422016E+10 | 10513.07 | 04-SEP-09:22 | 25.25 | 13.40 | 0.251243E+09 | 347.92 | 08-SEP-09:20 | 24.97 | 11.66 |
October | 0.179082E+10 | 7080.27 | 01-OCT-08:43 | 12.83 | 7.58 | 0.233000E+09 | 347.87 | 11-OCT-13:09 | 26.17 | 9.50 |
November | 0.967346E+09 | 2993.11 | 07-NOV-09:30 | 14.00 | 4.09 | 0.214024E+09 | 347.87 | 07-NOV-10:00 | 16.00 | 5.55 |
December | 0.577044E+09 | 1619.77 | 03-DEC-14:32 | 18.00 | 6.62 | 0.194205E+09 | 316.86 | 14-DEC-10:09 | 10.50 | 1.74 |
Annual Sum or Average | 0.343038E+11 | 0.286351E+10 | ||||||||
Minimum of Months | 0.577044E+09 | 1619.77 | 9.50 | 2.73 | 0.194205E+09 | 316.86 | 0.00 | -0.5 | ||
Maximum of Months | 0.622505E+10 | 13604.93 | 25.67 | 15.47 | 0.287089E+09 | 348.97 | 31.00 | 14.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348967E+10 | 12374.85 | 20-JAN-13:30 | 21.00 | 6.97 | 0.374116E+09 | 550.06 | 20-JAN-14:09 | 20.83 | 6.93 |
February | 0.326427E+10 | 15440.47 | 26-FEB-12:52 | 18.00 | 4.84 | 0.339892E+09 | 549.60 | 23-FEB-14:50 | 18.00 | 4.84 |
March | 0.395533E+10 | 16646.60 | 12-MAR-13:02 | 18.67 | 5.91 | 0.403808E+09 | 554.57 | 15-MAR-13:30 | 20.50 | 6.02 |
April | 0.268739E+10 | 8893.07 | 21-APR-13:10 | 15.83 | 6.37 | 0.355411E+09 | 549.53 | 13-APR-13:00 | 15.83 | 6.37 |
May | 0.411694E+10 | 7998.15 | 16-MAY-13:10 | 27.17 | 12.14 | 0.413838E+09 | 549.51 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.682660E+10 | 15333.92 | 25-JUN-12:02 | 31.78 | 12.57 | 0.433441E+09 | 550.05 | 30-JUN-13:50 | 35.82 | 14.30 |
July | 0.686154E+10 | 15366.23 | 09-JUL-13:42 | 34.67 | 13.78 | 0.403765E+09 | 549.50 | 11-JUL-09:30 | 25.50 | 13.66 |
August | 0.803008E+10 | 15191.86 | 20-AUG-15:02 | 28.00 | 13.92 | 0.452042E+09 | 560.77 | 31-AUG-13:20 | 30.00 | 11.86 |
September | 0.723029E+10 | 16413.08 | 04-SEP-13:22 | 29.40 | 13.40 | 0.396602E+09 | 596.36 | 28-SEP-13:30 | 30.50 | 11.31 |
October | 0.510865E+10 | 17391.55 | 01-OCT-13:21 | 17.00 | 8.82 | 0.375157E+09 | 576.45 | 10-OCT-13:30 | 24.50 | 8.32 |
November | 0.387818E+10 | 17291.65 | 05-NOV-13:31 | 21.00 | 6.43 | 0.373873E+09 | 555.60 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.278245E+10 | 15544.50 | 03-DEC-12:32 | 16.80 | 6.08 | 0.350128E+09 | 549.54 | 01-DEC-14:39 | 16.80 | 6.08 |
Annual Sum or Average | 0.582314E+11 | 0.467207E+10 | ||||||||
Minimum of Months | 0.268739E+10 | 7998.15 | 15.83 | 4.84 | 0.339892E+09 | 549.50 | 12.83 | 4.84 | ||
Maximum of Months | 0.803008E+10 | 17391.55 | 34.67 | 13.92 | 0.452042E+09 | 596.36 | 35.82 | 14.30 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.885834E+09 | 4334.22 | 20-JAN-16:00 | 18.00 | 7.49 | 0.208621E+09 | 347.83 | 20-JAN-14:00 | 18.00 | 7.49 |
February | 0.926205E+09 | 4755.14 | 17-FEB-16:30 | 13.50 | 6.66 | 0.190535E+09 | 347.84 | 17-FEB-14:00 | 13.50 | 6.66 |
March | 0.188903E+10 | 13865.67 | 12-MAR-16:22 | 18.00 | 5.68 | 0.234484E+09 | 347.84 | 08-MAR-14:00 | 18.00 | 5.68 |
April | 0.180983E+10 | 9293.52 | 08-APR-17:06 | 15.67 | 5.07 | 0.211543E+09 | 347.85 | 19-APR-13:00 | 22.00 | 9.00 |
May | 0.331686E+10 | 8674.82 | 31-MAY-16:00 | 28.00 | 14.86 | 0.254165E+09 | 347.85 | 31-MAY-13:00 | 28.00 | 14.86 |
June | 0.583045E+10 | 15944.97 | 11-JUN-16:31 | 28.17 | 12.60 | 0.272640E+09 | 347.86 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.518602E+10 | 15816.56 | 02-JUL-17:01 | 28.00 | 12.40 | 0.253711E+09 | 347.86 | 11-JUL-09:30 | 25.50 | 13.66 |
August | 0.534040E+10 | 15353.23 | 13-AUG-16:42 | 22.17 | 9.87 | 0.282788E+09 | 347.85 | 21-AUG-09:09 | 25.33 | 14.07 |
September | 0.397807E+10 | 15510.78 | 10-SEP-16:52 | 30.50 | 12.19 | 0.242780E+09 | 347.86 | 01-SEP-13:00 | 30.50 | 12.19 |
October | 0.214698E+10 | 10657.06 | 09-OCT-16:02 | 21.83 | 8.61 | 0.219763E+09 | 347.84 | 11-OCT-13:09 | 26.17 | 9.50 |
November | 0.112072E+10 | 5416.60 | 07-NOV-15:40 | 21.33 | 7.24 | 0.210322E+09 | 347.84 | 06-NOV-14:00 | 21.33 | 7.24 |
December | 0.624682E+09 | 3214.16 | 01-DEC-15:30 | 19.50 | 7.14 | 0.196423E+09 | 347.83 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.330551E+11 | 0.277777E+10 | ||||||||
Minimum of Months | 0.624682E+09 | 3214.16 | 13.50 | 5.07 | 0.190535E+09 | 347.83 | 13.50 | 5.68 | ||
Maximum of Months | 0.583045E+10 | 15944.97 | 30.50 | 14.86 | 0.282788E+09 | 347.86 | 30.50 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.484147E+09 | 1378.69 | 20-JAN-14:10 | 20.83 | 6.93 | 0.313592E+09 | 467.45 | 25-JAN-14:00 | 14.00 | 4.48 |
February | 0.382633E+09 | 1547.11 | 27-FEB-13:05 | 14.00 | 4.75 | 0.283184E+09 | 473.52 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.916037E+09 | 1751.72 | 14-MAR-13:10 | 23.83 | 7.85 | 0.358188E+09 | 546.81 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.108055E+10 | 1390.96 | 20-APR-13:40 | 21.33 | 8.72 | 0.328527E+09 | 541.02 | 20-APR-13:50 | 21.17 | 8.62 |
May | 0.210587E+10 | 3624.61 | 17-MAY-13:30 | 29.00 | 11.78 | 0.412050E+09 | 549.49 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.449098E+10 | 5482.72 | 13-JUN-12:08 | 33.90 | 13.85 | 0.434812E+09 | 549.51 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.448635E+10 | 6756.44 | 17-JUL-06:03 | 22.50 | 11.12 | 0.404301E+09 | 549.99 | 25-JUL-13:09 | 29.33 | 16.42 |
August | 0.442110E+10 | 5172.30 | 18-AUG-14:00 | 35.00 | 13.50 | 0.453331E+09 | 549.50 | 21-AUG-09:09 | 25.33 | 14.07 |
September | 0.354465E+10 | 5590.00 | 11-SEP-14:30 | 28.85 | 13.58 | 0.398662E+09 | 549.54 | 05-SEP-09:09 | 28.85 | 13.58 |
October | 0.166616E+10 | 3101.09 | 11-OCT-14:40 | 26.33 | 9.55 | 0.368435E+09 | 549.47 | 11-OCT-13:09 | 26.33 | 9.55 |
November | 0.968937E+09 | 1758.05 | 07-NOV-15:40 | 21.33 | 7.24 | 0.330775E+09 | 549.48 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.495894E+09 | 1449.10 | 03-DEC-15:02 | 17.67 | 6.57 | 0.301774E+09 | 486.15 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.250433E+11 | 0.438763E+10 | ||||||||
Minimum of Months | 0.382633E+09 | 1378.69 | 14.00 | 4.75 | 0.283184E+09 | 467.45 | 14.00 | 4.48 | ||
Maximum of Months | 0.449098E+10 | 6756.44 | 35.00 | 13.85 | 0.453331E+09 | 549.99 | 29.33 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.767507E+09 | 1395.34 | 20-JAN-10:10 | 14.67 | 5.12 | 0.212090E+09 | 347.86 | 24-JAN-10:09 | 11.50 | 3.54 |
February | 0.756412E+09 | 2541.49 | 27-FEB-08:35 | 7.67 | 2.12 | 0.197019E+09 | 347.87 | 23-FEB-10:09 | 7.67 | 2.12 |
March | 0.142368E+10 | 4176.85 | 15-MAR-09:10 | 14.17 | 4.19 | 0.253525E+09 | 347.87 | 27-MAR-09:00 | 0.00 | -0.5 |
April | 0.151567E+10 | 4418.19 | 21-APR-09:10 | 12.00 | 5.90 | 0.229132E+09 | 347.89 | 13-APR-13:00 | 12.00 | 5.90 |
May | 0.259478E+10 | 5177.23 | 16-MAY-09:00 | 23.00 | 11.65 | 0.269951E+09 | 347.89 | 31-MAY-09:00 | 25.00 | 13.24 |
June | 0.526358E+10 | 8938.70 | 18-JUN-10:12 | 25.33 | 18.24 | 0.276218E+09 | 348.33 | 27-JUN-09:00 | 26.60 | 12.07 |
July | 0.496476E+10 | 10652.80 | 09-JUL-10:22 | 29.00 | 13.30 | 0.256973E+09 | 348.29 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.549878E+10 | 11094.40 | 06-AUG-09:41 | 26.67 | 15.50 | 0.288068E+09 | 348.26 | 31-AUG-09:50 | 26.67 | 13.56 |
September | 0.427920E+10 | 10660.47 | 04-SEP-09:52 | 26.10 | 13.35 | 0.254767E+09 | 348.41 | 08-SEP-09:30 | 25.25 | 11.81 |
October | 0.203837E+10 | 6060.60 | 01-OCT-08:53 | 13.00 | 7.66 | 0.243675E+09 | 347.88 | 03-OCT-13:09 | 12.17 | 8.60 |
November | 0.117399E+10 | 2890.75 | 07-NOV-09:10 | 14.00 | 4.09 | 0.225281E+09 | 347.87 | 07-NOV-10:00 | 16.00 | 5.55 |
December | 0.680618E+09 | 1449.29 | 03-DEC-12:23 | 16.60 | 5.97 | 0.201512E+09 | 331.53 | 18-DEC-10:09 | 3.17 | -0.7 |
Annual Sum or Average | 0.309573E+11 | 0.290821E+10 | ||||||||
Minimum of Months | 0.680618E+09 | 1395.34 | 7.67 | 2.12 | 0.197019E+09 | 331.53 | 0.00 | -0.7 | ||
Maximum of Months | 0.549878E+10 | 11094.40 | 29.00 | 18.24 | 0.288068E+09 | 348.41 | 31.00 | 14.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177752E+10 | 9980.53 | 22-JAN-14:43 | 8.00 | 4.11 | 0.347448E+09 | 549.60 | 23-JAN-14:00 | 19.00 | 5.82 |
February | 0.135380E+10 | 12042.89 | 26-FEB-13:22 | 17.50 | 4.55 | 0.306919E+09 | 549.51 | 16-FEB-14:09 | 17.50 | 4.55 |
March | 0.194225E+10 | 9344.84 | 14-MAR-13:10 | 23.83 | 7.85 | 0.376036E+09 | 549.85 | 14-MAR-13:00 | 23.00 | 7.59 |
April | 0.123813E+10 | 5091.63 | 12-APR-12:08 | 19.33 | 7.40 | 0.329316E+09 | 549.51 | 13-APR-13:39 | 16.00 | 9.74 |
May | 0.222705E+10 | 7442.66 | 16-MAY-12:00 | 27.00 | 11.84 | 0.394296E+09 | 549.51 | 17-MAY-13:00 | 29.00 | 11.64 |
June | 0.593432E+10 | 12093.10 | 26-JUN-16:20 | 38.43 | 15.58 | 0.432382E+09 | 671.57 | 26-JUN-12:09 | 38.43 | 15.58 |
July | 0.595851E+10 | 11854.72 | 17-JUL-12:00 | 36.00 | 14.76 | 0.402800E+09 | 671.43 | 17-JUL-12:09 | 36.00 | 14.76 |
August | 0.745725E+10 | 12345.67 | 06-AUG-13:02 | 30.17 | 15.84 | 0.453193E+09 | 675.37 | 16-AUG-12:09 | 35.17 | 12.78 |
September | 0.700738E+10 | 13262.57 | 04-SEP-12:31 | 29.03 | 13.49 | 0.398824E+09 | 634.92 | 28-SEP-12:09 | 30.08 | 11.35 |
October | 0.402055E+10 | 12618.82 | 09-OCT-13:42 | 22.00 | 8.68 | 0.370605E+09 | 607.89 | 10-OCT-13:50 | 24.83 | 8.58 |
November | 0.258315E+10 | 12239.72 | 05-NOV-13:42 | 21.00 | 6.39 | 0.354681E+09 | 574.08 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.162627E+10 | 12345.69 | 03-DEC-14:23 | 18.00 | 6.62 | 0.322077E+09 | 549.59 | 04-DEC-14:30 | 19.50 | 6.42 |
Annual Sum or Average | 0.431262E+11 | 0.448858E+10 | ||||||||
Minimum of Months | 0.123813E+10 | 5091.63 | 8.00 | 4.11 | 0.306919E+09 | 549.51 | 16.00 | 4.55 | ||
Maximum of Months | 0.745725E+10 | 13262.57 | 38.43 | 15.84 | 0.453193E+09 | 675.37 | 38.43 | 15.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.822879E+09 | 3156.01 | 23-JAN-16:10 | 18.17 | 6.14 | 0.210126E+09 | 347.75 | 25-JAN-14:00 | 14.00 | 4.48 |
February | 0.770432E+09 | 3399.81 | 17-FEB-16:30 | 13.50 | 6.66 | 0.190858E+09 | 347.83 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.138773E+10 | 5409.56 | 13-MAR-16:50 | 22.17 | 6.72 | 0.237317E+09 | 347.84 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.138912E+10 | 6296.98 | 08-APR-17:08 | 15.67 | 5.07 | 0.214070E+09 | 347.84 | 19-APR-13:00 | 22.00 | 9.00 |
May | 0.235907E+10 | 5673.74 | 31-MAY-16:00 | 28.00 | 14.86 | 0.259809E+09 | 347.85 | 10-MAY-13:50 | 28.00 | 14.86 |
June | 0.471291E+10 | 12202.60 | 25-JUN-16:31 | 32.70 | 13.89 | 0.275155E+09 | 347.86 | 20-JUN-13:00 | 32.70 | 13.89 |
July | 0.417703E+10 | 11755.52 | 01-JUL-18:22 | 27.00 | 10.29 | 0.255679E+09 | 347.85 | 11-JUL-09:30 | 25.50 | 13.66 |
August | 0.465003E+10 | 11707.62 | 13-AUG-17:42 | 22.83 | 10.50 | 0.287104E+09 | 347.86 | 15-AUG-13:39 | 25.33 | 13.66 |
September | 0.382147E+10 | 12128.67 | 10-SEP-17:52 | 29.40 | 11.87 | 0.252926E+09 | 347.88 | 05-SEP-09:09 | 29.40 | 11.87 |
October | 0.222393E+10 | 10321.71 | 09-OCT-16:22 | 21.50 | 8.67 | 0.236400E+09 | 347.84 | 04-OCT-13:00 | 21.50 | 8.67 |
November | 0.128273E+10 | 4750.04 | 07-NOV-15:40 | 21.33 | 7.24 | 0.219472E+09 | 347.84 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.723554E+09 | 2595.43 | 04-DEC-15:30 | 18.00 | 5.80 | 0.200198E+09 | 347.83 | 04-DEC-14:00 | 18.00 | 5.80 |
Annual Sum or Average | 0.283209E+11 | 0.283911E+10 | ||||||||
Minimum of Months | 0.723554E+09 | 2595.43 | 13.50 | 5.07 | 0.190858E+09 | 347.75 | 14.00 | 4.48 | ||
Maximum of Months | 0.471291E+10 | 12202.60 | 32.70 | 14.86 | 0.287104E+09 | 347.88 | 32.70 | 14.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.727961E+09 | 1647.16 | 20-JAN-14:40 | 20.33 | 6.84 | 0.321626E+09 | 506.76 | 20-JAN-16:30 | 15.00 | 6.47 |
February | 0.640590E+09 | 1599.08 | 27-FEB-13:10 | 14.00 | 4.75 | 0.291869E+09 | 514.76 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.131242E+10 | 3204.36 | 14-MAR-15:00 | 23.00 | 7.59 | 0.379569E+09 | 549.48 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.141898E+10 | 2937.82 | 20-APR-13:30 | 21.50 | 8.83 | 0.348861E+09 | 549.51 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.295165E+10 | 5090.94 | 17-MAY-13:30 | 29.00 | 11.78 | 0.423163E+09 | 549.50 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.557189E+10 | 7838.25 | 26-JUN-06:03 | 19.77 | 12.60 | 0.435994E+09 | 549.98 | 12-JUN-13:30 | 19.77 | 12.60 |
July | 0.543314E+10 | 9377.16 | 16-JUL-11:42 | 36.00 | 14.35 | 0.405371E+09 | 549.83 | 24-JUL-13:50 | 32.00 | 16.85 |
August | 0.503923E+10 | 5959.96 | 18-AUG-13:50 | 34.67 | 13.33 | 0.454067E+09 | 549.92 | 18-AUG-13:50 | 34.67 | 13.33 |
September | 0.364127E+10 | 5880.35 | 11-SEP-14:30 | 28.85 | 13.58 | 0.398085E+09 | 549.54 | 05-SEP-09:09 | 28.85 | 13.58 |
October | 0.163793E+10 | 3657.49 | 11-OCT-14:40 | 26.33 | 9.55 | 0.366983E+09 | 549.49 | 10-OCT-13:00 | 26.33 | 9.55 |
November | 0.968972E+09 | 2177.89 | 09-NOV-13:40 | 20.00 | 8.72 | 0.332701E+09 | 549.48 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.548965E+09 | 1424.64 | 03-DEC-14:53 | 18.00 | 6.62 | 0.303909E+09 | 507.38 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.298930E+11 | 0.446220E+10 | ||||||||
Minimum of Months | 0.548965E+09 | 1424.64 | 14.00 | 4.75 | 0.291869E+09 | 506.76 | 14.00 | 4.75 | ||
Maximum of Months | 0.557189E+10 | 9377.16 | 36.00 | 14.35 | 0.454067E+09 | 549.98 | 34.67 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100541E+10 | 2773.08 | 20-JAN-09:40 | 12.67 | 4.18 | 0.156858E+09 | 338.71 | 19-JAN-09:39 | 12.67 | 4.18 |
February | 0.106185E+10 | 4225.83 | 27-FEB-09:10 | 9.17 | 2.67 | 0.146411E+09 | 338.72 | 27-FEB-08:20 | 9.17 | 2.67 |
March | 0.199184E+10 | 9491.88 | 12-MAR-09:13 | 14.33 | 5.23 | 0.187005E+09 | 338.73 | 27-MAR-10:09 | 0.33 | -0.4 |
April | 0.202979E+10 | 6854.46 | 21-APR-08:30 | 11.50 | 5.93 | 0.169791E+09 | 338.74 | 13-APR-14:09 | 11.50 | 5.93 |
May | 0.343918E+10 | 8316.37 | 28-MAY-09:13 | 12.67 | 8.79 | 0.199469E+09 | 338.97 | 16-MAY-08:50 | 12.67 | 8.79 |
June | 0.590103E+10 | 12738.86 | 18-JUN-10:12 | 25.33 | 18.24 | 0.203938E+09 | 339.91 | 29-JUN-08:00 | 28.30 | 13.38 |
July | 0.553882E+10 | 13692.66 | 16-JUL-08:21 | 31.50 | 14.54 | 0.190327E+09 | 343.30 | 17-JUL-07:19 | 26.00 | 12.45 |
August | 0.576782E+10 | 13989.14 | 06-AUG-09:01 | 25.33 | 15.45 | 0.212243E+09 | 339.76 | 07-AUG-10:09 | 28.33 | 14.90 |
September | 0.424540E+10 | 13215.89 | 04-SEP-09:12 | 24.97 | 13.41 | 0.186654E+09 | 339.15 | 18-SEP-08:00 | 22.70 | 10.68 |
October | 0.211243E+10 | 10118.85 | 01-OCT-08:53 | 13.00 | 7.66 | 0.174579E+09 | 338.73 | 10-OCT-14:09 | 25.00 | 8.67 |
November | 0.125150E+10 | 3966.82 | 07-NOV-09:10 | 14.00 | 4.09 | 0.161251E+09 | 338.72 | 07-NOV-11:09 | 16.67 | 5.90 |
December | 0.752513E+09 | 1672.84 | 03-DEC-14:53 | 18.00 | 6.62 | 0.146273E+09 | 336.18 | 14-DEC-09:50 | 9.67 | 1.34 |
Annual Sum or Average | 0.350976E+11 | 0.213480E+10 | ||||||||
Minimum of Months | 0.752513E+09 | 1672.84 | 9.17 | 2.67 | 0.146273E+09 | 336.18 | 0.33 | -0.4 | ||
Maximum of Months | 0.590103E+10 | 13989.14 | 31.50 | 18.24 | 0.212243E+09 | 343.30 | 28.33 | 14.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400376E+10 | 13980.67 | 22-JAN-13:53 | 8.00 | 4.11 | 0.383381E+09 | 568.87 | 20-JAN-14:09 | 8.00 | 4.11 |
February | 0.364351E+10 | 14014.85 | 26-FEB-12:52 | 18.00 | 4.84 | 0.348042E+09 | 549.64 | 24-FEB-14:50 | 18.00 | 4.84 |
March | 0.417589E+10 | 13900.87 | 12-MAR-11:13 | 16.67 | 5.83 | 0.413375E+09 | 569.72 | 15-MAR-13:30 | 20.50 | 6.02 |
April | 0.284678E+10 | 8339.82 | 21-APR-13:10 | 15.83 | 6.37 | 0.365736E+09 | 549.81 | 21-APR-13:39 | 15.33 | 5.87 |
May | 0.407781E+10 | 7367.25 | 16-MAY-13:10 | 27.17 | 12.14 | 0.424034E+09 | 549.51 | 10-MAY-13:39 | 27.17 | 12.14 |
June | 0.640821E+10 | 13568.46 | 25-JUN-12:23 | 32.15 | 12.76 | 0.435366E+09 | 550.38 | 30-JUN-13:50 | 35.82 | 14.30 |
July | 0.646474E+10 | 13190.54 | 16-JUL-11:42 | 36.00 | 14.35 | 0.405214E+09 | 549.88 | 31-JUL-13:39 | 26.33 | 17.62 |
August | 0.767405E+10 | 14300.37 | 06-AUG-12:22 | 31.50 | 15.93 | 0.454558E+09 | 569.57 | 31-AUG-13:09 | 30.00 | 11.91 |
September | 0.721431E+10 | 15554.29 | 10-SEP-12:41 | 32.25 | 13.24 | 0.401748E+09 | 612.19 | 28-SEP-13:20 | 30.50 | 11.31 |
October | 0.551226E+10 | 14553.15 | 15-OCT-13:32 | 13.67 | 3.81 | 0.386713E+09 | 598.63 | 10-OCT-13:09 | 13.67 | 3.81 |
November | 0.443074E+10 | 14264.23 | 05-NOV-13:02 | 21.00 | 6.54 | 0.384282E+09 | 580.02 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.319026E+10 | 13900.98 | 17-DEC-13:02 | 18.00 | 5.78 | 0.360874E+09 | 549.60 | 14-DEC-14:39 | 18.00 | 5.78 |
Annual Sum or Average | 0.596423E+11 | 0.476332E+10 | ||||||||
Minimum of Months | 0.284678E+10 | 7367.25 | 8.00 | 3.81 | 0.348042E+09 | 549.51 | 8.00 | 3.81 | ||
Maximum of Months | 0.767405E+10 | 15554.29 | 36.00 | 15.93 | 0.454558E+09 | 612.19 | 35.82 | 17.62 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111865E+10 | 4181.33 | 20-JAN-16:00 | 18.00 | 7.49 | 0.212801E+09 | 347.83 | 24-JAN-14:00 | 17.00 | 6.48 |
February | 0.111067E+10 | 4668.56 | 17-FEB-16:30 | 13.50 | 6.66 | 0.193875E+09 | 347.84 | 17-FEB-14:00 | 13.50 | 6.66 |
March | 0.203215E+10 | 10063.86 | 12-MAR-17:12 | 17.33 | 5.43 | 0.240293E+09 | 347.84 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.194338E+10 | 8771.99 | 08-APR-17:06 | 15.67 | 5.07 | 0.217397E+09 | 347.85 | 13-APR-13:30 | 16.50 | 9.66 |
May | 0.325496E+10 | 8089.01 | 31-MAY-16:00 | 28.00 | 14.86 | 0.262011E+09 | 347.86 | 10-MAY-13:39 | 28.00 | 14.86 |
June | 0.547866E+10 | 14270.03 | 25-JUN-16:21 | 32.70 | 13.84 | 0.274758E+09 | 347.86 | 20-JUN-13:00 | 32.70 | 13.84 |
July | 0.488838E+10 | 14158.46 | 02-JUL-16:42 | 28.00 | 12.40 | 0.255533E+09 | 347.86 | 11-JUL-09:30 | 25.50 | 13.66 |
August | 0.507748E+10 | 13834.55 | 13-AUG-16:22 | 22.50 | 10.02 | 0.286030E+09 | 347.86 | 15-AUG-13:39 | 25.33 | 13.66 |
September | 0.392211E+10 | 15034.63 | 10-SEP-17:21 | 29.95 | 12.03 | 0.249003E+09 | 347.88 | 05-SEP-09:09 | 29.95 | 12.03 |
October | 0.239500E+10 | 10662.16 | 09-OCT-16:22 | 21.50 | 8.67 | 0.228241E+09 | 347.86 | 10-OCT-13:00 | 25.00 | 8.71 |
November | 0.139742E+10 | 5387.56 | 07-NOV-15:30 | 21.50 | 7.27 | 0.215687E+09 | 347.84 | 09-NOV-14:50 | 18.33 | 8.19 |
December | 0.811483E+09 | 3102.21 | 01-DEC-15:30 | 19.50 | 7.14 | 0.199821E+09 | 347.84 | 15-DEC-14:00 | 9.00 | 3.00 |
Annual Sum or Average | 0.334303E+11 | 0.283545E+10 | ||||||||
Minimum of Months | 0.811483E+09 | 3102.21 | 13.50 | 5.07 | 0.193875E+09 | 347.83 | 9.00 | 3.00 | ||
Maximum of Months | 0.547866E+10 | 15034.63 | 32.70 | 14.86 | 0.286030E+09 | 347.88 | 32.70 | 14.86 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.50 |
February | 1160990.64 | 16839.63 | 06-FEB-07:01 | -9.7 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 2879973.94 | 14191.83 | 26-DEC-07:02 | 6.83 |
Annual Sum or Average | 4040964.58 | |||
Minimum of Months | 0.00 | 0.00 | -9.7 | |
Maximum of Months | 2879973.94 | 16839.63 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338837E+10 | 15076.48 | 05-JAN-06:12 | -17.0 |
February | 0.342254E+10 | 14409.63 | 13-FEB-06:13 | -10.7 |
March | 0.239025E+10 | 10975.38 | 20-MAR-05:13 | 0.00 |
April | 0.155572E+10 | 12624.44 | 17-APR-05:13 | -8.0 |
May | 0.467064E+09 | 5827.69 | 02-MAY-06:01 | 0.17 |
June | 0.113485E+09 | 5649.11 | 26-JUN-05:03 | 17.07 |
July | 85238271.91 | 4702.31 | 03-JUL-05:03 | 11.00 |
August | 0.119108E+09 | 5723.88 | 07-AUG-05:03 | 16.17 |
September | 0.348876E+09 | 5490.04 | 11-SEP-05:03 | 17.88 |
October | 0.198903E+10 | 12698.14 | 31-OCT-05:12 | -8.3 |
November | 0.253605E+10 | 13552.27 | 30-NOV-06:13 | -12.0 |
December | 0.490512E+10 | 16225.60 | 23-DEC-06:13 | -22.1 |
Annual Sum or Average | 0.213208E+11 | |||
Minimum of Months | 85238271.91 | 4702.31 | -22.1 | |
Maximum of Months | 0.490512E+10 | 16225.60 | 17.88 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171771E+10 | 5565.95 | 15-JAN-13:33 | 4.67 |
February | 0.172643E+10 | 8054.14 | 06-FEB-07:11 | -9.3 |
March | 0.113653E+10 | 5693.43 | 20-MAR-06:02 | 0.00 |
April | 0.901159E+09 | 4612.24 | 03-APR-06:02 | -7.7 |
May | 0.188202E+09 | 2727.37 | 28-MAY-09:13 | 12.67 |
June | 23385354.93 | 2927.49 | 25-JUN-16:21 | 32.70 |
July | 28857443.81 | 2867.69 | 16-JUL-14:22 | 35.50 |
August | 22820420.72 | 3499.13 | 06-AUG-11:02 | 30.33 |
September | 62974370.12 | 4246.21 | 17-SEP-15:12 | 26.60 |
October | 0.729511E+09 | 5163.64 | 15-OCT-15:32 | 15.00 |
November | 0.137796E+10 | 6051.89 | 12-NOV-12:23 | 5.00 |
December | 0.208745E+10 | 7089.96 | 26-DEC-07:13 | 6.67 |
Annual Sum or Average | 0.100030E+11 | |||
Minimum of Months | 22820420.72 | 2727.37 | -9.3 | |
Maximum of Months | 0.208745E+10 | 8054.14 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101411E+10 | 3431.61 | 30-JAN-08:09 | -2.0 |
February | 0.102764E+10 | 4025.45 | 06-FEB-08:50 | -5.5 |
March | 0.724043E+09 | 3563.75 | 16-MAR-05:03 | 7.83 |
April | 0.550581E+09 | 3961.66 | 24-APR-07:10 | 1.00 |
May | 0.109954E+09 | 4088.65 | 30-MAY-05:03 | 8.17 |
June | 25577944.11 | 3400.04 | 10-JUN-05:03 | 9.77 |
July | 26231434.00 | 2903.70 | 05-JUL-04:03 | 15.00 |
August | 28402896.58 | 3087.91 | 28-AUG-04:03 | 14.17 |
September | 37160886.68 | 4644.80 | 22-SEP-05:02 | -1.7 |
October | 0.406740E+09 | 5253.20 | 16-OCT-05:02 | 1.00 |
November | 0.746037E+09 | 3916.44 | 24-NOV-08:06 | -2.7 |
December | 0.133524E+10 | 4174.83 | 26-DEC-07:02 | 6.83 |
Annual Sum or Average | 0.603172E+10 | |||
Minimum of Months | 25577944.11 | 2903.70 | -5.5 | |
Maximum of Months | 0.133524E+10 | 5253.20 | 15.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 73305999.27 | 18881.36 | 02-JAN-06:01 | -2.8 |
February | 0.220029E+09 | 20250.04 | 06-FEB-06:01 | -10.0 |
March | 57060707.98 | 19364.41 | 20-MAR-05:01 | 0.00 |
April | 36234511.14 | 18514.10 | 03-APR-05:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 13252847.35 | 18037.31 | 31-OCT-06:01 | -9.0 |
November | 20222541.38 | 18035.26 | 01-NOV-06:01 | -2.8 |
December | 0.237655E+09 | 20464.67 | 26-DEC-06:01 | 7.00 |
Annual Sum or Average | 0.657761E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.237655E+09 | 20464.67 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105673E+10 | 28730.43 | 02-JAN-05:01 | -2.2 |
February | 0.137205E+10 | 30756.18 | 06-FEB-05:01 | -10.0 |
March | 0.574969E+09 | 29569.78 | 20-MAR-04:11 | 0.67 |
April | 0.494761E+09 | 28953.15 | 03-APR-04:01 | -8.0 |
May | 21826580.63 | 25137.60 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.399666E+09 | 28547.54 | 30-OCT-04:01 | -10.0 |
November | 0.611477E+09 | 27862.87 | 30-NOV-06:01 | -12.0 |
December | 0.185415E+10 | 30370.77 | 26-DEC-05:01 | 3.67 |
Annual Sum or Average | 0.638563E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.185415E+10 | 30756.18 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235086E+10 | 9766.78 | 02-JAN-05:01 | -2.2 |
February | 0.252444E+10 | 10165.42 | 12-FEB-05:03 | -19.8 |
March | 0.132694E+10 | 10054.84 | 19-MAR-08:13 | -13.0 |
April | 0.750302E+09 | 9897.18 | 03-APR-04:01 | -8.0 |
May | 56592424.91 | 8811.12 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 17364257.33 | 8146.52 | 22-SEP-05:02 | -1.7 |
October | 0.970960E+09 | 9882.03 | 30-OCT-04:01 | -10.0 |
November | 0.165341E+10 | 9805.44 | 27-NOV-05:01 | -7.0 |
December | 0.375120E+10 | 10411.03 | 24-DEC-04:12 | -19.7 |
Annual Sum or Average | 0.134021E+11 | |||
Minimum of Months | 0.00 | 0.00 | -19.8 | |
Maximum of Months | 0.375120E+10 | 10411.03 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114960E+10 | 10686.00 | 02-JAN-05:01 | -2.2 |
February | 0.129066E+10 | 11086.16 | 13-FEB-05:01 | -11.0 |
March | 0.693679E+09 | 10835.48 | 20-MAR-04:11 | 0.67 |
April | 0.396678E+09 | 10908.16 | 03-APR-04:01 | -8.0 |
May | 20920775.34 | 9701.45 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 8168020.86 | 8658.46 | 22-SEP-06:01 | -1.4 |
October | 0.612520E+09 | 10883.16 | 30-OCT-04:01 | -10.0 |
November | 0.859331E+09 | 10825.87 | 27-NOV-05:01 | -7.0 |
December | 0.204229E+10 | 11370.95 | 24-DEC-04:12 | -19.7 |
Annual Sum or Average | 0.707384E+10 | |||
Minimum of Months | 0.00 | 0.00 | -19.7 | |
Maximum of Months | 0.204229E+10 | 11370.95 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120328E+10 | 12968.38 | 05-JAN-05:01 | -17.0 |
February | 0.160533E+10 | 13645.43 | 06-FEB-04:53 | -10.0 |
March | 0.103299E+10 | 13485.38 | 19-MAR-08:13 | -13.0 |
April | 0.676410E+09 | 13400.74 | 03-APR-04:01 | -8.0 |
May | 62398693.41 | 11918.61 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 15272683.97 | 10692.43 | 22-SEP-06:01 | -1.4 |
October | 0.858350E+09 | 13351.82 | 30-OCT-04:01 | -10.0 |
November | 0.982440E+09 | 13090.08 | 01-NOV-04:01 | -3.0 |
December | 0.221988E+10 | 13932.95 | 24-DEC-05:32 | -18.3 |
Annual Sum or Average | 0.865636E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.3 | |
Maximum of Months | 0.221988E+10 | 13932.95 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129103E+10 | 11675.29 | 02-JAN-05:01 | -2.2 |
February | 0.143929E+10 | 12160.86 | 13-FEB-05:01 | -11.0 |
March | 0.807918E+09 | 11882.37 | 20-MAR-04:11 | 0.67 |
April | 0.485512E+09 | 11946.10 | 03-APR-04:01 | -8.0 |
May | 42494850.76 | 10444.13 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 13137549.89 | 9363.09 | 22-SEP-06:01 | -1.4 |
October | 0.625821E+09 | 11933.28 | 30-OCT-04:01 | -10.0 |
November | 0.951010E+09 | 11680.41 | 27-NOV-05:01 | -7.0 |
December | 0.218412E+10 | 12441.66 | 24-DEC-02:52 | -21.0 |
Annual Sum or Average | 0.784034E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.218412E+10 | 12441.66 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126534E+10 | 7070.40 | 02-JAN-05:01 | -2.2 |
February | 0.148138E+10 | 7454.22 | 06-FEB-05:01 | -10.0 |
March | 0.647937E+09 | 6846.18 | 20-MAR-04:02 | 0.83 |
April | 0.284940E+09 | 6894.19 | 03-APR-04:01 | -8.0 |
May | 10119986.91 | 6024.15 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.200756E+09 | 6590.08 | 31-OCT-05:01 | -8.2 |
November | 0.392751E+09 | 6749.74 | 30-NOV-06:01 | -12.0 |
December | 0.151016E+10 | 7189.62 | 26-DEC-05:01 | 3.67 |
Annual Sum or Average | 0.579340E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.151016E+10 | 7454.22 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470500E+09 | 8190.24 | 06-JAN-05:01 | -7.8 |
February | 0.653132E+09 | 8832.13 | 06-FEB-05:01 | -10.0 |
March | 0.277101E+09 | 7872.25 | 20-MAR-05:01 | 0.00 |
April | 0.127014E+09 | 7884.54 | 04-APR-05:01 | -2.2 |
May | 1868360.79 | 7079.44 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.127531E+09 | 7793.94 | 31-OCT-05:01 | -8.2 |
November | 0.186674E+09 | 7966.47 | 30-NOV-06:01 | -12.0 |
December | 0.704402E+09 | 8451.28 | 22-DEC-05:01 | -21.0 |
Annual Sum or Average | 0.254822E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.704402E+09 | 8832.13 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286764E+10 | 13680.07 | 05-JAN-07:10 | -17.0 |
February | 0.319221E+10 | 12497.89 | 06-FEB-07:50 | -8.3 |
March | 0.273174E+10 | 12164.03 | 29-MAR-06:10 | -7.7 |
April | 0.198449E+10 | 11929.14 | 17-APR-06:10 | -7.7 |
May | 0.853230E+09 | 10616.92 | 02-MAY-06:10 | 0.17 |
June | 36977025.66 | 8298.56 | 09-JUN-06:07 | 9.37 |
July | 22527831.85 | 8203.89 | 03-JUL-06:05 | 11.00 |
August | 34901596.80 | 6046.31 | 23-AUG-06:05 | 12.50 |
September | 0.195728E+09 | 10056.90 | 22-SEP-06:10 | -1.4 |
October | 0.196718E+10 | 12329.91 | 30-OCT-06:10 | -10.0 |
November | 0.232869E+10 | 12778.16 | 29-NOV-17:10 | -11.3 |
December | 0.365059E+10 | 14456.59 | 22-DEC-07:10 | -20.0 |
Annual Sum or Average | 0.198659E+11 | |||
Minimum of Months | 22527831.85 | 6046.31 | -20.0 | |
Maximum of Months | 0.365059E+10 | 14456.59 | 12.50 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.512610E+09 | 7845.21 | 05-JAN-06:01 | -17.0 |
February | 0.670719E+09 | 8863.61 | 06-FEB-05:01 | -10.0 |
March | 0.308747E+09 | 7778.90 | 20-MAR-05:01 | 0.00 |
April | 0.163393E+09 | 7780.77 | 04-APR-05:01 | -2.2 |
May | 6265965.55 | 6941.35 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 18.18 |
October | 0.131176E+09 | 7723.77 | 31-OCT-05:01 | -8.2 |
November | 0.177709E+09 | 7858.11 | 30-NOV-06:01 | -12.0 |
December | 0.747998E+09 | 8435.99 | 22-DEC-05:01 | -21.0 |
Annual Sum or Average | 0.271862E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.747998E+09 | 8863.61 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.929727E+09 | 7928.04 | 06-JAN-05:01 | -7.8 |
February | 0.107202E+10 | 8388.79 | 13-FEB-05:01 | -11.0 |
March | 0.394127E+09 | 7835.57 | 20-MAR-04:02 | 0.83 |
April | 0.235538E+09 | 7894.10 | 03-APR-04:01 | -8.0 |
May | 6862790.77 | 6751.66 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 438911.41 | 5629.61 | 22-SEP-06:01 | -1.4 |
October | 0.339114E+09 | 7833.59 | 30-OCT-04:01 | -10.0 |
November | 0.555425E+09 | 7846.86 | 30-NOV-05:01 | -12.8 |
December | 0.168784E+10 | 8482.24 | 24-DEC-07:32 | -17.3 |
Annual Sum or Average | 0.522110E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.3 | |
Maximum of Months | 0.168784E+10 | 8482.24 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453469E+09 | 8623.75 | 06-JAN-05:01 | -7.8 |
February | 0.568643E+09 | 9129.27 | 13-FEB-05:01 | -11.0 |
March | 0.224614E+09 | 8411.88 | 20-MAR-04:02 | 0.83 |
April | 0.130207E+09 | 8607.51 | 03-APR-04:01 | -8.0 |
May | 2057895.38 | 7079.22 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 456319.91 | 5911.14 | 22-SEP-06:01 | -1.4 |
October | 0.241934E+09 | 8503.56 | 30-OCT-04:01 | -10.0 |
November | 0.310303E+09 | 8531.82 | 30-NOV-05:01 | -12.8 |
December | 0.922554E+09 | 9151.02 | 21-DEC-05:11 | -18.3 |
Annual Sum or Average | 0.285424E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.3 | |
Maximum of Months | 0.922554E+09 | 9151.02 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408282E+09 | 11042.44 | 05-JAN-05:01 | -17.0 |
February | 0.665402E+09 | 11634.46 | 06-FEB-05:01 | -10.0 |
March | 0.294497E+09 | 10957.10 | 20-MAR-04:02 | 0.83 |
April | 0.219477E+09 | 11110.69 | 03-APR-04:01 | -8.0 |
May | 8409840.51 | 9508.40 | 02-MAY-06:01 | 0.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 476786.00 | 6294.26 | 22-SEP-06:01 | -1.4 |
October | 0.313305E+09 | 10948.84 | 30-OCT-04:01 | -10.0 |
November | 0.303542E+09 | 10858.97 | 30-NOV-05:01 | -12.8 |
December | 0.870888E+09 | 11721.51 | 21-DEC-05:11 | -18.3 |
Annual Sum or Average | 0.308428E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.3 | |
Maximum of Months | 0.870888E+09 | 11721.51 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.485316E+09 | 8510.67 | 06-JAN-05:01 | -7.8 |
February | 0.595409E+09 | 8974.89 | 13-FEB-05:01 | -11.0 |
March | 0.238642E+09 | 8421.67 | 20-MAR-04:02 | 0.83 |
April | 0.160054E+09 | 8530.55 | 03-APR-04:01 | -8.0 |
May | 5904680.97 | 6965.62 | 03-MAY-06:01 | 2.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 888542.30 | 6988.97 | 22-SEP-06:01 | -1.4 |
October | 0.227865E+09 | 8440.55 | 30-OCT-04:01 | -10.0 |
November | 0.314912E+09 | 8449.59 | 30-NOV-05:01 | -12.8 |
December | 0.942562E+09 | 9133.48 | 21-DEC-05:11 | -18.3 |
Annual Sum or Average | 0.297155E+10 | |||
Minimum of Months | 0.00 | 0.00 | -18.3 | |
Maximum of Months | 0.942562E+09 | 9133.48 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.566691E+09 | 889.66 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.479112E+09 | 840.54 | 06-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.526989E+09 | 695.29 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.453093E+09 | 622.20 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.472862E+09 | 445.76 | 12-MAY-13:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.463157E+09 | 452.88 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.438339E+09 | 424.37 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.498396E+09 | 478.86 | 28-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.459436E+09 | 482.85 | 21-SEP-15:00 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.510919E+09 | 776.12 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.551585E+09 | 889.66 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.554100E+09 | 889.66 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.597468E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.438339E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.566691E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351655E+09 | 563.23 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.300916E+09 | 532.22 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.332833E+09 | 424.86 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287837E+09 | 365.39 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.301613E+09 | 283.96 | 12-MAY-13:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.295905E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.279828E+09 | 268.66 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.317656E+09 | 305.98 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.290918E+09 | 308.94 | 21-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.320352E+09 | 484.53 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.345536E+09 | 563.23 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.345329E+09 | 563.23 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.377038E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.279828E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.351655E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.530666E+09 | 889.66 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.462276E+09 | 839.43 | 06-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.521195E+09 | 688.97 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.454056E+09 | 618.08 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.475980E+09 | 424.37 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.468306E+09 | 458.11 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.442431E+09 | 449.14 | 28-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.500766E+09 | 476.17 | 28-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.457846E+09 | 475.86 | 21-SEP-15:00 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.499604E+09 | 770.12 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.526285E+09 | 889.66 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.526542E+09 | 889.66 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.586595E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.442431E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.530666E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.342848E+09 | 563.19 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.294974E+09 | 530.37 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.329867E+09 | 444.63 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.286094E+09 | 404.84 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.299669E+09 | 291.23 | 19-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.294094E+09 | 296.64 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.278198E+09 | 294.32 | 28-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.314460E+09 | 302.63 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.289801E+09 | 343.99 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.318739E+09 | 491.94 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.336690E+09 | 563.19 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.337700E+09 | 563.19 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.372313E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.278198E+09 | 291.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.342848E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.563684E+09 | 889.66 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.477034E+09 | 838.36 | 06-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.525596E+09 | 686.61 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.452435E+09 | 610.22 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.472433E+09 | 424.37 | 01-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.462852E+09 | 447.93 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.438005E+09 | 424.37 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.498468E+09 | 475.30 | 28-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.458655E+09 | 479.51 | 21-SEP-15:00 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.508963E+09 | 771.08 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.549278E+09 | 889.66 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.551471E+09 | 889.66 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.595888E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.438005E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.563684E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.350731E+09 | 563.23 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.299875E+09 | 531.12 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.332146E+09 | 419.67 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287422E+09 | 357.53 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.301303E+09 | 281.86 | 12-MAY-13:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.295588E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.279526E+09 | 268.66 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.317305E+09 | 304.07 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.290552E+09 | 307.18 | 21-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.319351E+09 | 481.62 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.344576E+09 | 563.23 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.344310E+09 | 563.23 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.376269E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.279526E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.350731E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.530024E+09 | 889.66 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.461491E+09 | 837.19 | 06-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.520737E+09 | 679.93 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.453478E+09 | 605.88 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.475418E+09 | 424.37 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.467729E+09 | 453.48 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.441898E+09 | 444.04 | 28-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.500225E+09 | 472.44 | 28-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.457270E+09 | 472.07 | 21-SEP-15:00 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.498859E+09 | 764.72 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.525061E+09 | 889.66 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.525378E+09 | 889.66 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.585757E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.441898E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.530024E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.341804E+09 | 563.19 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.294255E+09 | 529.17 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.329310E+09 | 440.42 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.285724E+09 | 399.23 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.299378E+09 | 288.70 | 19-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.293876E+09 | 294.33 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.277975E+09 | 291.94 | 28-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.314151E+09 | 300.88 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.289328E+09 | 336.00 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.317876E+09 | 489.40 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.335781E+09 | 563.19 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.336802E+09 | 563.19 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.371626E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.277975E+09 | 288.70 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.341804E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.566691E+09 | 889.66 | 02-JAN-16:49 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.479111E+09 | 840.53 | 06-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.526988E+09 | 695.28 | 21-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.453093E+09 | 622.18 | 03-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.472862E+09 | 445.75 | 12-MAY-13:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.463157E+09 | 452.87 | 16-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.438338E+09 | 424.37 | 03-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.498396E+09 | 478.85 | 28-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.459436E+09 | 482.85 | 21-SEP-15:00 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.510917E+09 | 776.11 | 30-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.551584E+09 | 889.66 | 06-NOV-16:49 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.554099E+09 | 889.66 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.597467E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.438338E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.566691E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351655E+09 | 563.23 | 02-JAN-16:49 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.300916E+09 | 532.22 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.332832E+09 | 424.85 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287837E+09 | 365.37 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.301613E+09 | 283.96 | 12-MAY-13:30 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.295905E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.279827E+09 | 268.66 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.317656E+09 | 305.98 | 28-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.290917E+09 | 308.93 | 21-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.320352E+09 | 484.53 | 30-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.345536E+09 | 563.23 | 06-NOV-16:49 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.345329E+09 | 563.23 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.377037E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.279827E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.351655E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.530783E+09 | 889.66 | 02-JAN-16:49 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.463242E+09 | 839.42 | 06-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.521210E+09 | 688.96 | 21-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.454056E+09 | 618.06 | 03-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.475979E+09 | 424.37 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.468306E+09 | 458.10 | 16-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.442430E+09 | 449.13 | 28-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.500766E+09 | 476.16 | 28-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.457846E+09 | 475.85 | 21-SEP-15:00 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.499603E+09 | 770.11 | 30-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.526284E+09 | 889.66 | 06-NOV-16:49 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.526541E+09 | 889.66 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.586705E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.442430E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.530783E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.342848E+09 | 563.19 | 02-JAN-16:49 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.294974E+09 | 530.36 | 06-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.329867E+09 | 444.62 | 21-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.286094E+09 | 404.83 | 03-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.299669E+09 | 291.23 | 19-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.294094E+09 | 296.63 | 16-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.278198E+09 | 294.32 | 28-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.314459E+09 | 302.63 | 21-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.289801E+09 | 344.00 | 25-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.318739E+09 | 491.94 | 30-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.336689E+09 | 563.19 | 06-NOV-16:49 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.337699E+09 | 563.19 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.372313E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.278198E+09 | 291.23 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.342848E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.566691E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210162E+09 |
February | 0.901968E+09 | 0.479112E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339625E+09 |
March | 0.107774E+10 | 0.526989E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367536E+09 |
April | 0.956342E+09 | 0.453093E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391188E+09 |
May | 0.103597E+10 | 0.472862E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 876988.85 | 0.210574E+09 |
June | 0.103308E+10 | 0.463157E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18794734.61 | 93564410.38 |
July | 0.959235E+09 | 0.438339E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23843419.76 | 92980864.12 |
August | 0.107774E+10 | 0.498396E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12843467.38 | 91684761.07 |
September | 0.956342E+09 | 0.459436E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7139331.86 | 0.132813E+09 |
October | 0.994195E+09 | 0.510919E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124824.41 | 0.281504E+09 |
November | 0.984487E+09 | 0.551585E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241286E+09 |
December | 0.959235E+09 | 0.554100E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2722.36 | 0.456948E+09 |
Annual Sum or Average | 0.119305E+11 | 0.597468E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63625489.21 | 0.290987E+10 |
Minimum of Months | 0.901968E+09 | 0.438339E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91684761.07 |
Maximum of Months | 0.107774E+10 | 0.566691E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23843419.76 | 0.456948E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.351655E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143369E+09 |
February | 0.571020E+09 | 0.300916E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231056E+09 |
March | 0.682301E+09 | 0.332833E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251101E+09 |
April | 0.605444E+09 | 0.287837E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266351E+09 |
May | 0.655854E+09 | 0.301613E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 587382.74 | 0.142112E+09 |
June | 0.654023E+09 | 0.295905E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12407631.62 | 62910272.76 |
July | 0.607275E+09 | 0.279828E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15834153.47 | 63721766.83 |
August | 0.682301E+09 | 0.317656E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8332360.24 | 62430651.13 |
September | 0.605444E+09 | 0.290918E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4558832.15 | 91254806.10 |
October | 0.629407E+09 | 0.320352E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82430.05 | 0.193114E+09 |
November | 0.623262E+09 | 0.345536E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163521E+09 |
December | 0.607275E+09 | 0.345329E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.72 | 0.307905E+09 |
Annual Sum or Average | 0.755301E+10 | 0.377038E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41803158.99 | 0.197885E+10 |
Minimum of Months | 0.571020E+09 | 0.279828E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62430651.13 |
Maximum of Months | 0.682301E+09 | 0.351655E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15834153.47 | 0.307905E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.530666E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230888E+09 |
February | 0.901968E+09 | 0.462276E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361652E+09 |
March | 0.107774E+10 | 0.521195E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387148E+09 |
April | 0.956342E+09 | 0.454056E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.400773E+09 |
May | 0.103597E+10 | 0.475980E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 875832.62 | 0.212771E+09 |
June | 0.103308E+10 | 0.468306E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18697594.69 | 92449057.00 |
July | 0.959235E+09 | 0.442431E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23750644.26 | 92637486.27 |
August | 0.107774E+10 | 0.500766E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12383256.23 | 94937427.28 |
September | 0.956342E+09 | 0.457846E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6095918.54 | 0.141068E+09 |
October | 0.994195E+09 | 0.499604E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109017.52 | 0.300515E+09 |
November | 0.984487E+09 | 0.526285E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260260E+09 |
December | 0.959235E+09 | 0.526542E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485523E+09 |
Annual Sum or Average | 0.119305E+11 | 0.586595E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61912263.85 | 0.306062E+10 |
Minimum of Months | 0.901968E+09 | 0.442431E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92449057.00 |
Maximum of Months | 0.107774E+10 | 0.530666E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23750644.26 | 0.485523E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.342848E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143996E+09 |
February | 0.570983E+09 | 0.294974E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231878E+09 |
March | 0.682256E+09 | 0.329867E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250997E+09 |
April | 0.605404E+09 | 0.286094E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264455E+09 |
May | 0.655811E+09 | 0.299669E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 615692.37 | 0.143302E+09 |
June | 0.653980E+09 | 0.294094E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12674273.35 | 64199082.39 |
July | 0.607235E+09 | 0.278198E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16178177.39 | 62848303.42 |
August | 0.682256E+09 | 0.314460E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8802047.50 | 63616323.05 |
September | 0.605404E+09 | 0.289801E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4630746.08 | 91765198.96 |
October | 0.629366E+09 | 0.318739E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94321.86 | 0.192049E+09 |
November | 0.623221E+09 | 0.336690E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164538E+09 |
December | 0.607235E+09 | 0.337700E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309105E+09 |
Annual Sum or Average | 0.755252E+10 | 0.372313E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42995258.55 | 0.198275E+10 |
Minimum of Months | 0.570983E+09 | 0.278198E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62848303.42 |
Maximum of Months | 0.682256E+09 | 0.342848E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16178177.39 | 0.309105E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.563684E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117796E+09 |
February | 0.901968E+09 | 0.477034E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186109E+09 |
March | 0.107774E+10 | 0.525596E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.19 | 0.201438E+09 |
April | 0.956342E+09 | 0.452435E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216172E+09 |
May | 0.103597E+10 | 0.472433E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 514240.45 | 0.111638E+09 |
June | 0.103308E+10 | 0.462852E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10923241.04 | 48138525.21 |
July | 0.959235E+09 | 0.438005E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14410132.93 | 47642684.33 |
August | 0.107774E+10 | 0.498468E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7374022.48 | 48694514.59 |
September | 0.956342E+09 | 0.458655E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4141193.87 | 75018529.10 |
October | 0.994195E+09 | 0.508963E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68641.97 | 0.163456E+09 |
November | 0.984487E+09 | 0.549278E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138722E+09 |
December | 0.959235E+09 | 0.551471E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2128.68 | 0.256799E+09 |
Annual Sum or Average | 0.119305E+11 | 0.595888E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37434664.60 | 0.161162E+10 |
Minimum of Months | 0.901968E+09 | 0.438005E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47642684.33 |
Maximum of Months | 0.107774E+10 | 0.563684E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14410132.93 | 0.256799E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.350731E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81505231.52 |
February | 0.571020E+09 | 0.299875E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128790E+09 |
March | 0.682301E+09 | 0.332146E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.96 | 0.140545E+09 |
April | 0.605444E+09 | 0.287422E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150991E+09 |
May | 0.655854E+09 | 0.301303E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 322655.84 | 78265137.99 |
June | 0.654023E+09 | 0.295588E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6853666.91 | 34163860.54 |
July | 0.607275E+09 | 0.279526E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8687908.00 | 34593034.38 |
August | 0.682301E+09 | 0.317305E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4500342.16 | 35160652.11 |
September | 0.605444E+09 | 0.290552E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2419225.27 | 53628972.38 |
October | 0.629407E+09 | 0.319351E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45534.14 | 0.113975E+09 |
November | 0.623262E+09 | 0.344576E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95316348.43 |
December | 0.607275E+09 | 0.344310E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175299E+09 |
Annual Sum or Average | 0.755301E+10 | 0.376269E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22829333.29 | 0.112223E+10 |
Minimum of Months | 0.571020E+09 | 0.279526E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34163860.54 |
Maximum of Months | 0.682301E+09 | 0.350731E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8687908.00 | 0.175299E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.530024E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627571E+10 |
February | 0.901968E+09 | 0.461491E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615150E+10 |
March | 0.107774E+10 | 0.520737E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.21 | 0.533050E+10 |
April | 0.956342E+09 | 0.453478E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399496E+10 |
May | 0.103597E+10 | 0.475418E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84592566.19 | 0.258767E+10 |
June | 0.103308E+10 | 0.467729E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110446E+10 | 0.615838E+09 |
July | 0.959235E+09 | 0.441898E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888041E+09 | 0.572410E+09 |
August | 0.107774E+10 | 0.500225E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966855E+09 | 0.868112E+09 |
September | 0.956342E+09 | 0.457270E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414691E+09 | 0.139201E+10 |
October | 0.994195E+09 | 0.498859E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7036385.32 | 0.481597E+10 |
November | 0.984487E+09 | 0.525061E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597290E+10 |
December | 0.959235E+09 | 0.525378E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692156E+10 |
Annual Sum or Average | 0.119305E+11 | 0.585757E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346567E+10 | 0.454991E+11 |
Minimum of Months | 0.901968E+09 | 0.441898E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572410E+09 |
Maximum of Months | 0.107774E+10 | 0.530024E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110446E+10 | 0.692156E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.341804E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81871592.58 |
February | 0.570983E+09 | 0.294255E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129031E+09 |
March | 0.682256E+09 | 0.329310E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 | 0.139952E+09 |
April | 0.605404E+09 | 0.285724E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149576E+09 |
May | 0.655811E+09 | 0.299378E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 339378.79 | 78408947.57 |
June | 0.653980E+09 | 0.293876E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6834012.69 | 35110786.41 |
July | 0.607235E+09 | 0.277975E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8824471.45 | 33992541.72 |
August | 0.682256E+09 | 0.314151E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4719817.51 | 35869047.25 |
September | 0.605404E+09 | 0.289328E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2383147.33 | 54079750.46 |
October | 0.629366E+09 | 0.317876E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45539.15 | 0.113649E+09 |
November | 0.623221E+09 | 0.335781E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95732087.59 |
December | 0.607235E+09 | 0.336802E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175736E+09 |
Annual Sum or Average | 0.755252E+10 | 0.371626E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23146372.13 | 0.112301E+10 |
Minimum of Months | 0.570983E+09 | 0.277975E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33992541.72 |
Maximum of Months | 0.682256E+09 | 0.341804E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8824471.45 | 0.175736E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.566691E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186922E+09 |
February | 0.901968E+09 | 0.479111E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296289E+09 |
March | 0.107774E+10 | 0.526988E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323316E+09 |
April | 0.956342E+09 | 0.453093E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347821E+09 |
May | 0.103597E+10 | 0.472862E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 740651.30 | 0.184117E+09 |
June | 0.103308E+10 | 0.463157E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16042787.06 | 80391013.43 |
July | 0.959235E+09 | 0.438338E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20643792.52 | 79893607.47 |
August | 0.107774E+10 | 0.498396E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10945284.19 | 79493554.32 |
September | 0.956342E+09 | 0.459436E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6099188.92 | 0.117582E+09 |
October | 0.994195E+09 | 0.510917E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104916.96 | 0.251852E+09 |
November | 0.984487E+09 | 0.551584E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214424E+09 |
December | 0.959235E+09 | 0.554099E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 961.36 | 0.398399E+09 |
Annual Sum or Average | 0.119305E+11 | 0.597467E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54577582.31 | 0.256050E+10 |
Minimum of Months | 0.901968E+09 | 0.438338E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79493554.32 |
Maximum of Months | 0.107774E+10 | 0.566691E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20643792.52 | 0.398399E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.351655E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127267E+09 |
February | 0.421807E+09 | 0.300916E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201298E+09 |
March | 0.502994E+09 | 0.332832E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219875E+09 |
April | 0.447140E+09 | 0.287837E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235540E+09 |
May | 0.484071E+09 | 0.301613E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497130.56 | 0.123697E+09 |
June | 0.482240E+09 | 0.295905E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10640710.91 | 53925746.54 |
July | 0.448971E+09 | 0.279827E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13670905.57 | 54570883.62 |
August | 0.502994E+09 | 0.317656E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7047455.40 | 53918080.68 |
September | 0.447140E+09 | 0.290917E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3946445.36 | 80072913.74 |
October | 0.465148E+09 | 0.320352E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69934.34 | 0.171386E+09 |
November | 0.460569E+09 | 0.345536E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144796E+09 |
December | 0.448971E+09 | 0.345329E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.81 | 0.268719E+09 |
Annual Sum or Average | 0.557719E+10 | 0.377037E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35872704.94 | 0.173507E+10 |
Minimum of Months | 0.421807E+09 | 0.279827E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53918080.68 |
Maximum of Months | 0.502994E+09 | 0.351655E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13670905.57 | 0.268719E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.530783E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204668E+09 |
February | 0.901968E+09 | 0.463242E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315943E+09 |
March | 0.107774E+10 | 0.521210E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339750E+09 |
April | 0.956342E+09 | 0.454056E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355791E+09 |
May | 0.103597E+10 | 0.475979E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 738356.20 | 0.186225E+09 |
June | 0.103308E+10 | 0.468306E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15789879.03 | 79904888.34 |
July | 0.959235E+09 | 0.442430E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20163771.58 | 80091966.30 |
August | 0.107774E+10 | 0.500766E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10346507.19 | 82461840.61 |
September | 0.956342E+09 | 0.457846E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5115712.71 | 0.124245E+09 |
October | 0.994195E+09 | 0.499603E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75621.04 | 0.266602E+09 |
November | 0.984487E+09 | 0.526284E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229918E+09 |
December | 0.959235E+09 | 0.526541E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425571E+09 |
Annual Sum or Average | 0.119305E+11 | 0.586705E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52229847.75 | 0.269117E+10 |
Minimum of Months | 0.901968E+09 | 0.442430E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79904888.34 |
Maximum of Months | 0.107774E+10 | 0.530783E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20163771.58 | 0.425571E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.342848E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127828E+09 |
February | 0.570983E+09 | 0.294974E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202096E+09 |
March | 0.682256E+09 | 0.329867E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220059E+09 |
April | 0.605404E+09 | 0.286094E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234511E+09 |
May | 0.655811E+09 | 0.299669E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 503042.09 | 0.125417E+09 |
June | 0.653980E+09 | 0.294094E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10606334.67 | 55446023.87 |
July | 0.607235E+09 | 0.278198E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13630449.52 | 54327395.29 |
August | 0.682256E+09 | 0.314459E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7322888.58 | 55338585.29 |
September | 0.605404E+09 | 0.289801E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3779779.71 | 81215446.15 |
October | 0.629366E+09 | 0.318739E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74770.25 | 0.170988E+09 |
November | 0.623221E+09 | 0.336689E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145663E+09 |
December | 0.607235E+09 | 0.337699E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269597E+09 |
Annual Sum or Average | 0.755252E+10 | 0.372313E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35917264.82 | 0.174249E+10 |
Minimum of Months | 0.570983E+09 | 0.278198E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54327395.29 |
Maximum of Months | 0.682256E+09 | 0.342848E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13630449.52 | 0.269597E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264042E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414315E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453314E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483403E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713589.41 | 0.247658E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18462619.75 | 0.106360E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24838204.33 | 0.105440E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11766313.02 | 0.107319E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6185608.12 | 0.164002E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54343.58 | 0.356174E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302728E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559680E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62020678.21 | 0.356444E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105440E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24838204.33 | 0.559680E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324072E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513856E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562669E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599162E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 941751.40 | 0.312592E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23784287.31 | 0.136902E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31891752.44 | 0.135973E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15358575.52 | 0.136751E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8390154.73 | 0.205151E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85346.30 | 0.438438E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370950E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687084E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80451867.71 | 0.442360E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135973E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31891752.44 | 0.687084E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323055E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.518719E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567567E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601096E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557085.86 | 0.324189E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20165035.62 | 0.138177E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25330377.41 | 0.137895E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12658344.90 | 0.138349E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5906738.53 | 0.202675E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18826.91 | 0.435106E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369155E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687881E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64636409.23 | 0.444386E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137895E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25330377.41 | 0.687881E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 398.30 | 31-JAN-02:00 |
February | 1306.65 | 01-FEB-10:09 | 840.54 | 06-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 517.22 | 05-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 695.29 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1152.72 | 19-MAR-07:00 |
April | 1306.65 | 03-APR-09:09 | 622.20 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 742.97 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 445.76 | 12-MAY-13:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.72 | 17-MAY-14:50 | 413.40 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 452.88 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.14 | 25-JUN-17:24 | 273.25 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 424.37 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.59 | 16-JUL-11:55 | 263.35 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 478.86 | 28-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.57 | 02-AUG-16:00 | 345.54 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 482.85 | 21-SEP-15:00 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 | 10-SEP-15:00 | 281.82 | 21-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 776.12 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 | 11-OCT-14:00 | 611.31 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 639.74 | 01-NOV-04:08 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.80 | 02-DEC-15:00 | 957.85 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.35 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 199.59 | 1152.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 264.77 | 13-JAN-05:04 |
February | 827.22 | 01-FEB-10:09 | 532.22 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 352.06 | 05-FEB-22:55 |
March | 827.22 | 01-MAR-10:09 | 424.86 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 777.29 | 19-MAR-06:55 |
April | 827.22 | 03-APR-09:09 | 365.39 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 495.31 | 15-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 283.96 | 12-MAY-13:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 17-MAY-14:50 | 275.02 | 03-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.20 | 25-JUN-17:30 | 181.63 | 08-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 268.66 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.84 | 16-JUL-11:58 | 187.95 | 02-JUL-09:00 |
August | 827.22 | 01-AUG-09:09 | 305.98 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.71 | 02-AUG-16:00 | 233.25 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 308.94 | 21-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.31 | 10-SEP-15:00 | 187.46 | 21-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 484.53 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 11-OCT-14:00 | 409.44 | 29-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 431.44 | 01-NOV-04:04 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 02-DEC-15:00 | 638.26 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.63 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 136.84 | 777.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 412.67 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 839.43 | 06-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 548.15 | 19-FEB-17:00 |
March | 1306.65 | 01-MAR-10:09 | 688.97 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1165.54 | 19-MAR-06:55 |
April | 1306.65 | 03-APR-09:09 | 618.08 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 742.97 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 424.37 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.72 | 17-MAY-14:50 | 418.68 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 458.11 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.46 | 25-JUN-17:24 | 271.72 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 449.14 | 28-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.64 | 16-JUL-11:58 | 263.27 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 476.17 | 28-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.56 | 02-AUG-16:00 | 374.18 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 475.86 | 21-SEP-15:00 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.65 | 10-SEP-14:55 | 283.75 | 21-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 770.12 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.78 | 11-OCT-14:00 | 627.07 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 639.74 | 01-NOV-04:06 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 959.91 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.27 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 200.64 | 1165.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 266.92 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 530.37 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 352.03 | 05-FEB-22:55 |
March | 827.17 | 01-MAR-10:09 | 444.63 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 777.36 | 19-MAR-06:55 |
April | 827.17 | 03-APR-09:09 | 404.84 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 495.31 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 291.23 | 19-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 17-MAY-14:50 | 281.41 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 296.64 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | 25-JUN-17:47 | 192.55 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 294.32 | 28-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.90 | 16-JUL-12:00 | 180.92 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 302.63 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.75 | 06-AUG-12:00 | 247.52 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 343.99 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.08 | 10-SEP-14:53 | 185.77 | 21-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 491.94 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.69 | 11-OCT-14:00 | 406.57 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 430.16 | 01-NOV-04:04 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 638.42 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 291.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.92 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 140.90 | 777.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 235.52 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 838.36 | 06-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 282.63 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 686.61 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 14-MAR-13:00 | 636.34 | 19-MAR-06:53 |
April | 1306.65 | 03-APR-09:09 | 610.22 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 422.20 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 424.37 | 01-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 17-MAY-14:50 | 235.19 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 447.93 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.78 | 25-JUN-18:00 | 145.97 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 424.37 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.60 | 16-JUL-12:00 | 139.01 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 475.30 | 28-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 | 06-AUG-12:00 | 172.55 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 479.51 | 21-SEP-15:00 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 | 10-SEP-15:00 | 167.16 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 771.08 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.43 | 11-OCT-14:00 | 373.87 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 357.66 | 01-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 | 02-DEC-15:00 | 533.33 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.01 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 110.60 | 636.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 160.20 | 13-JAN-05:00 |
February | 827.22 | 01-FEB-10:09 | 531.12 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 197.70 | 23-FEB-24:00 |
March | 827.22 | 01-MAR-10:09 | 419.67 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 423.22 | 19-MAR-06:53 |
April | 827.22 | 03-APR-09:09 | 357.53 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 285.85 | 15-APR-05:00 |
May | 827.22 | 01-MAY-09:09 | 281.86 | 12-MAY-13:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 | 17-MAY-14:50 | 159.79 | 03-MAY-03:00 |
June | 827.22 | 01-JUN-09:09 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.40 | 25-JUN-18:00 | 101.41 | 08-JUN-23:00 |
July | 827.22 | 03-JUL-09:09 | 268.66 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.83 | 16-JUL-11:58 | 98.24 | 03-JUL-03:00 |
August | 827.22 | 01-AUG-09:09 | 304.07 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 | 02-AUG-16:00 | 123.57 | 27-AUG-18:00 |
September | 827.22 | 01-SEP-09:09 | 307.18 | 21-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.68 | 10-SEP-15:00 | 112.39 | 22-SEP-02:00 |
October | 827.22 | 02-OCT-09:09 | 481.62 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 11-OCT-14:00 | 255.13 | 29-OCT-09:00 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 237.07 | 01-NOV-04:00 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 353.97 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.24 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 72.83 | 423.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 41076.59 | 05-JAN-17:01 |
February | 1306.65 | 01-FEB-10:09 | 837.19 | 06-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 32324.59 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 679.93 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 | 14-MAR-13:00 | 31118.71 | 02-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 605.88 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 30163.20 | 17-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 424.37 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3902.38 | 31-MAY-16:10 | 21005.91 | 02-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 453.48 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13597.12 | 26-JUN-16:02 | 12563.82 | 09-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 444.04 | 28-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10462.93 | 17-JUL-11:02 | 11586.16 | 03-JUL-06:02 |
August | 1306.65 | 01-AUG-09:09 | 472.44 | 28-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11957.00 | 16-AUG-16:02 | 10733.05 | 17-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 472.07 | 21-SEP-15:00 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6272.61 | 12-SEP-16:03 | 23202.42 | 22-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 764.72 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1015.92 | 10-OCT-16:30 | 32903.93 | 30-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 35356.15 | 29-NOV-17:01 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 48384.30 | 21-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10733.05 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 13597.12 | 48384.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 161.52 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 529.17 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 198.20 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 440.42 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 14-MAR-13:00 | 421.98 | 19-MAR-06:53 |
April | 827.17 | 03-APR-09:09 | 399.23 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 281.12 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 288.70 | 19-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 | 17-MAY-14:50 | 163.74 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 294.33 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 25-JUN-17:54 | 106.31 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 291.94 | 28-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.43 | 16-JUL-12:00 | 101.72 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 300.88 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 06-AUG-11:58 | 134.70 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 336.00 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.23 | 10-SEP-14:34 | 111.30 | 22-SEP-02:00 |
October | 827.17 | 02-OCT-09:09 | 489.40 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 11-OCT-14:00 | 251.58 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 236.72 | 01-NOV-04:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 356.27 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 288.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.72 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 76.43 | 421.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 370.22 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 840.53 | 06-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 457.29 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 695.28 | 21-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 969.34 | 19-MAR-06:53 |
April | 1306.65 | 03-APR-09:09 | 622.18 | 03-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 658.53 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 445.75 | 12-MAY-13:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 | 17-MAY-14:50 | 375.84 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 452.87 | 16-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.00 | 25-JUN-17:45 | 234.11 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 424.37 | 03-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.96 | 16-JUL-11:53 | 226.13 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 478.85 | 28-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.29 | 02-AUG-16:00 | 285.69 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 482.85 | 21-SEP-15:00 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.01 | 10-SEP-15:00 | 253.05 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 776.11 | 30-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.42 | 11-OCT-14:00 | 563.86 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 532.77 | 01-NOV-04:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 02-DEC-15:00 | 822.66 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.13 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 161.96 | 969.34 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 563.23 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 246.78 | 13-JAN-05:00 |
February | 805.43 | 01-FEB-08:09 | 532.22 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 307.23 | 23-FEB-24:00 |
March | 805.43 | 01-MAR-08:09 | 424.85 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 642.95 | 19-MAR-06:53 |
April | 805.43 | 03-APR-07:10 | 365.37 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 437.46 | 16-APR-15:00 |
May | 805.43 | 01-MAY-07:10 | 283.96 | 12-MAY-13:30 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 17-MAY-14:50 | 249.77 | 03-MAY-03:00 |
June | 805.43 | 01-JUN-07:10 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.88 | 25-JUN-17:50 | 155.67 | 08-JUN-23:00 |
July | 805.43 | 03-JUL-07:10 | 268.66 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.42 | 16-JUL-11:53 | 153.75 | 02-JUL-08:40 |
August | 805.43 | 01-AUG-07:10 | 305.98 | 28-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.19 | 02-AUG-16:00 | 193.13 | 27-AUG-18:00 |
September | 805.43 | 01-SEP-07:10 | 308.93 | 21-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.77 | 10-SEP-14:50 | 167.89 | 22-SEP-02:00 |
October | 805.43 | 02-OCT-07:10 | 484.53 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 | 11-OCT-14:00 | 377.35 | 29-OCT-09:00 |
November | 805.43 | 01-NOV-07:10 | 563.23 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 359.74 | 01-NOV-04:02 |
December | 805.43 | 01-DEC-08:09 | 563.23 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 02-DEC-15:00 | 545.60 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.75 | |||||
Maximum of Months | 805.43 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 109.42 | 642.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:49 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 383.74 | 13-JAN-05:00 |
February | 1306.65 | 01-FEB-10:09 | 839.42 | 06-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 482.52 | 23-FEB-24:00 |
March | 1306.65 | 01-MAR-10:09 | 688.96 | 21-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 971.91 | 19-MAR-06:53 |
April | 1306.65 | 03-APR-09:09 | 618.06 | 03-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 661.15 | 15-APR-05:00 |
May | 1306.65 | 01-MAY-09:09 | 424.37 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 | 17-MAY-14:50 | 380.20 | 03-MAY-03:00 |
June | 1306.65 | 01-JUN-09:09 | 458.10 | 16-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.22 | 25-JUN-17:50 | 233.22 | 08-JUN-23:00 |
July | 1306.65 | 03-JUL-09:09 | 449.13 | 28-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.03 | 16-JUL-11:53 | 226.58 | 03-JUL-03:00 |
August | 1306.65 | 01-AUG-09:09 | 476.16 | 28-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.29 | 02-AUG-16:00 | 310.93 | 27-AUG-18:00 |
September | 1306.65 | 01-SEP-09:09 | 475.85 | 21-SEP-15:00 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.14 | 10-SEP-14:44 | 254.03 | 22-SEP-02:00 |
October | 1306.65 | 02-OCT-09:09 | 770.11 | 30-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.46 | 11-OCT-14:00 | 576.43 | 29-OCT-09:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:49 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 538.31 | 01-NOV-04:02 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 833.71 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.58 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 162.03 | 971.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:49 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 248.72 | 13-JAN-05:00 |
February | 827.17 | 01-FEB-10:09 | 530.36 | 06-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 312.15 | 23-FEB-24:00 |
March | 827.17 | 01-MAR-10:09 | 444.62 | 21-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 641.59 | 19-MAR-06:53 |
April | 827.17 | 03-APR-09:09 | 404.83 | 03-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 435.60 | 15-APR-05:00 |
May | 827.17 | 01-MAY-09:09 | 291.23 | 19-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 17-MAY-14:50 | 255.13 | 03-MAY-03:00 |
June | 827.17 | 01-JUN-09:09 | 296.63 | 16-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.92 | 25-JUN-17:43 | 164.56 | 08-JUN-23:00 |
July | 827.17 | 03-JUL-09:09 | 294.32 | 28-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.56 | 16-JUL-11:55 | 155.70 | 03-JUL-03:00 |
August | 827.17 | 01-AUG-09:09 | 302.63 | 21-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 | 06-AUG-11:53 | 205.48 | 27-AUG-18:00 |
September | 827.17 | 01-SEP-09:09 | 344.00 | 25-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.80 | 10-SEP-13:24 | 166.89 | 22-SEP-02:00 |
October | 827.17 | 02-OCT-09:09 | 491.94 | 30-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 | 11-OCT-14:00 | 374.89 | 29-OCT-09:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:49 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 359.79 | 01-NOV-04:02 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 548.94 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 291.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.70 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 115.56 | 641.59 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 537.51 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 645.51 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1393.52 | 19-MAR-06:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 935.86 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 | 17-MAY-14:40 | 530.23 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.37 | 25-JUN-18:00 | 308.45 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.47 | 16-JUL-12:00 | 300.22 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 | 06-AUG-12:00 | 365.93 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.85 | 10-SEP-15:00 | 354.00 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 11-OCT-14:00 | 803.69 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 773.99 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1133.29 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.22 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.47 | 1393.52 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 662.26 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 808.53 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1714.33 | 19-MAR-06:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1167.44 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 17-MAY-14:40 | 660.39 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.90 | 25-JUN-18:00 | 395.48 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.50 | 16-JUL-12:00 | 388.65 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.89 | 06-AUG-12:00 | 465.43 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.94 | 10-SEP-15:00 | 445.24 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.01 | 11-OCT-14:00 | 977.19 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 935.57 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1420.50 | 21-DEC-22:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.65 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.50 | 1714.33 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 604.70 | 31-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 821.65 | 19-FEB-17:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1720.60 | 19-MAR-07:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1133.53 | 15-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | 17-MAY-13:00 | 605.19 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.33 | 25-JUN-17:50 | 396.45 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.05 | 16-JUL-12:00 | 384.36 | 03-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.72 | 02-AUG-16:00 | 547.18 | 27-AUG-18:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.08 | 10-SEP-14:40 | 420.76 | 21-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 11-OCT-14:00 | 934.20 | 29-OCT-13:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 891.47 | 01-NOV-03:50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1442.18 | 21-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.36 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.05 | 1720.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16153.25 | 26-JAN-16:50 | 6035.01 | 4220.20 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18707.23 | 23-FEB-08:03 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29095.68 | 16-MAR-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19372.78 | 13-APR-05:02 | 3176.32 | 2344.59 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35061.21 | 08-MAY-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 37705.12 | 24-JUN-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 40678.31 | 17-JUL-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39246.65 | 28-AUG-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41747.77 | 05-SEP-04:02 | 0.00 | 2344.59 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 35847.57 | 10-OCT-06:01 | 10164.22 | 11254.03 | 70374.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21817.58 | 10-NOV-06:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17299.54 | 05-DEC-08:03 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16153.25 | 0.00 | 1875.67 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41747.77 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3005.70 | 20-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 |
February | 3218.70 | 18-FEB-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.02 |
March | 6760.89 | 14-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.39 |
April | 5942.97 | 21-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.09 |
May | 8721.98 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 | 0.00 |
June | 12053.90 | 26-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 | 0.00 |
July | 10613.93 | 17-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.81 | 0.00 |
August | 12057.93 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 | 0.00 |
September | 9027.70 | 12-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.27 | 0.00 |
October | 6912.49 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 | 0.00 |
November | 3573.79 | 09-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 |
December | 2162.60 | 17-DEC-14:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2162.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12057.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.81 | 118.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2220.67 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.99 |
February | 1930.23 | 28-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.93 |
March | 2342.39 | 15-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.78 |
April | 1861.24 | 11-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.41 |
May | 2574.71 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.95 |
June | 5074.97 | 26-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.05 | 0.00 |
July | 5197.33 | 17-JUL-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.35 | 0.00 |
August | 4618.45 | 21-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.35 | 0.00 |
September | 4385.17 | 05-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 |
October | 2866.05 | 11-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.90 |
November | 1736.62 | 30-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.72 |
December | 2627.61 | 21-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 610.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1736.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5197.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.05 | 610.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2813.44 | 27-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.58 |
February | 2559.16 | 28-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.20 |
March | 2644.33 | 15-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 |
April | 2204.19 | 14-APR-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.45 |
May | 2830.74 | 18-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 |
June | 6395.87 | 26-JUN-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.38 | 0.00 |
July | 6477.24 | 17-JUL-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 | 0.00 |
August | 4918.80 | 18-AUG-12:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 | 0.00 |
September | 4809.62 | 05-SEP-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 |
October | 3594.14 | 11-OCT-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
November | 2518.88 | 29-NOV-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.66 |
December | 2835.09 | 19-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2204.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6477.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 | 145.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8270.46 | 24-JAN-14:40 | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8035.25 | 27-FEB-13:10 | 24140.03 | 16880.81 | 27233.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13098.56 | 15-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11404.24 | 21-APR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17656.36 | 18-MAY-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29736.55 | 26-JUN-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30135.71 | 24-JUL-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29803.03 | 21-AUG-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30393.34 | 05-SEP-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17683.94 | 11-OCT-05:02 | 3176.32 | 2344.59 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10779.80 | 08-NOV-16:40 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7541.96 | 15-DEC-13:30 | 12070.02 | 8440.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7541.96 | 0.00 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30393.34 | 24140.03 | 16880.81 | 27233.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8331.09 | 20-JAN-14:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7190.47 | 26-FEB-13:32 | 1588.16 | 1172.15 | 11347.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14126.06 | 15-MAR-15:40 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12888.92 | 21-APR-14:00 | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15461.04 | 18-MAY-15:20 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23569.73 | 26-JUN-05:03 | 1905.79 | 1406.75 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32471.26 | 17-JUL-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29150.69 | 21-AUG-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30904.81 | 11-SEP-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14939.18 | 11-OCT-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9813.04 | 08-NOV-16:20 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7164.70 | 03-DEC-14:32 | 1270.53 | 937.72 | 9077.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7164.70 | 0.00 | 937.72 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32471.26 | 6198.29 | 4220.20 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1676.66 | 20-JAN-14:00 | 1272.23 | 444.50 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
February | 1437.60 | 26-FEB-13:32 | 334.80 | 117.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.26 |
March | 3370.78 | 14-MAR-14:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 |
April | 3309.23 | 20-APR-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.98 |
May | 5472.92 | 17-MAY-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 | 0.00 |
June | 11025.62 | 25-JUN-17:21 | 0.00 | 165.01 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 105.21 | 0.00 |
July | 10934.11 | 09-JUL-13:42 | 334.80 | 117.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 86.26 | 0.00 |
August | 6572.67 | 16-AUG-14:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.91 | 0.00 |
September | 6256.74 | 11-SEP-14:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 | 0.00 |
October | 3831.95 | 11-OCT-14:50 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 | 0.00 |
November | 1946.53 | 09-NOV-13:50 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 |
December | 1376.95 | 03-DEC-14:32 | 267.84 | 103.04 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1376.95 | 0.00 | 103.04 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11025.62 | 1306.65 | 444.50 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 105.21 | 67.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2080.76 | 20-JAN-10:10 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 |
February | 3152.64 | 27-FEB-09:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.88 |
March | 7242.62 | 12-MAR-09:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.94 |
April | 6559.41 | 21-APR-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 |
May | 7393.55 | 16-MAY-08:40 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 |
June | 10377.55 | 11-JUN-09:12 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.82 |
July | 13604.93 | 09-JUL-09:02 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.52 |
August | 12930.58 | 06-AUG-09:12 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 |
September | 10513.07 | 04-SEP-09:22 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 |
October | 7080.27 | 01-OCT-08:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.31 |
November | 2993.11 | 07-NOV-09:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.55 |
December | 1619.77 | 03-DEC-14:32 | 169.56 | 65.06 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1619.77 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | |
Maximum of Months | 13604.93 | 827.22 | 268.66 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12374.85 | 20-JAN-13:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 |
February | 15440.47 | 26-FEB-12:52 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.34 |
March | 16646.60 | 12-MAR-13:02 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.94 |
April | 8893.07 | 21-APR-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.26 |
May | 7998.15 | 16-MAY-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 11.47 | 0.00 |
June | 15333.92 | 25-JUN-12:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 59.67 | 0.00 |
July | 15366.23 | 09-JUL-13:42 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 81.82 | 0.00 |
August | 15191.86 | 20-AUG-15:02 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 0.00 |
September | 16413.08 | 04-SEP-13:22 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 20.47 | 0.00 |
October | 17391.55 | 01-OCT-13:21 | 468.72 | 165.01 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.70 |
November | 17291.65 | 05-NOV-13:31 | 468.72 | 165.01 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 |
December | 15544.50 | 03-DEC-12:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7998.15 | 267.84 | 94.29 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17391.55 | 1306.65 | 424.37 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 81.82 | 282.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4334.22 | 20-JAN-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.62 |
February | 4755.14 | 17-FEB-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.04 |
March | 13865.67 | 12-MAR-16:22 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.20 |
April | 9293.52 | 08-APR-17:06 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.06 |
May | 8674.82 | 31-MAY-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 0.00 |
June | 15944.97 | 11-JUN-16:31 | 296.72 | 104.46 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 0.00 |
July | 15816.56 | 02-JUL-17:01 | 0.00 | 104.46 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 | 0.00 |
August | 15353.23 | 13-AUG-16:42 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.01 |
September | 15510.78 | 10-SEP-16:52 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 0.00 |
October | 10657.06 | 09-OCT-16:02 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 |
November | 5416.60 | 07-NOV-15:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 |
December | 3214.16 | 01-DEC-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3214.16 | 0.00 | 74.61 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15944.97 | 805.38 | 268.64 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 109.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1378.69 | 20-JAN-14:10 | 1306.65 | 444.54 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 |
February | 1547.11 | 27-FEB-13:05 | 5088.93 | 1697.46 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.11 |
March | 1751.72 | 14-MAR-13:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 0.00 |
April | 1390.96 | 20-APR-13:40 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.59 |
May | 3624.61 | 17-MAY-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 | 0.00 |
June | 5482.72 | 13-JUN-12:08 | 6361.16 | 2121.83 | 7176.23 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 0.00 |
July | 6756.44 | 17-JUL-06:03 | 803.52 | 424.37 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 |
August | 5172.30 | 18-AUG-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.03 | 0.00 |
September | 5590.00 | 11-SEP-14:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 0.00 |
October | 3101.09 | 11-OCT-14:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 | 0.00 |
November | 1758.05 | 07-NOV-15:40 | 1272.23 | 573.73 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 |
December | 1449.10 | 03-DEC-15:02 | 267.84 | 122.82 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1378.69 | 267.84 | 122.82 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6756.44 | 6361.16 | 2121.83 | 7176.23 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 | 39.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1395.34 | 20-JAN-10:10 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 |
February | 2541.49 | 27-FEB-08:35 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 |
March | 4176.85 | 15-MAR-09:10 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.13 |
April | 4418.19 | 21-APR-09:10 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 |
May | 5177.23 | 16-MAY-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
June | 8938.70 | 18-JUN-10:12 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
July | 10652.80 | 09-JUL-10:22 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 | 0.00 |
August | 11094.40 | 06-AUG-09:41 | 296.74 | 104.47 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 |
September | 10660.47 | 04-SEP-09:52 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 |
October | 6060.60 | 01-OCT-08:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.26 |
November | 2890.75 | 07-NOV-09:10 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 |
December | 1449.29 | 03-DEC-12:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1395.34 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11094.40 | 1610.86 | 537.32 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 | 86.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9980.53 | 22-JAN-14:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.58 |
February | 12042.89 | 26-FEB-13:22 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.03 |
March | 9344.84 | 14-MAR-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.40 |
April | 5091.63 | 12-APR-12:08 | 5088.93 | 1697.46 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 703.11 |
May | 7442.66 | 16-MAY-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3059.41 | 0.00 |
June | 12093.10 | 26-JUN-16:20 | 1607.03 | 943.02 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 11354.18 | 0.00 |
July | 11854.72 | 17-JUL-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 9339.11 | 0.00 |
August | 12345.67 | 06-AUG-13:02 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 | 0.00 |
September | 13262.57 | 04-SEP-12:31 | 468.72 | 165.01 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 0.00 |
October | 12618.82 | 09-OCT-13:42 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.71 |
November | 12239.72 | 05-NOV-13:42 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.08 |
December | 12345.69 | 03-DEC-14:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5091.63 | 267.84 | 94.29 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13262.57 | 5088.93 | 1697.46 | 5740.95 | 0.00 | 0.00 | 0.00 | 0.00 | 11354.18 | 703.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3156.01 | 23-JAN-16:10 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 |
February | 3399.81 | 17-FEB-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 |
March | 5409.56 | 13-MAR-16:50 | 254.33 | 149.24 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
April | 6296.98 | 08-APR-17:08 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.42 |
May | 5673.74 | 31-MAY-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 0.00 |
June | 12202.60 | 25-JUN-16:31 | 423.88 | 149.23 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 25.40 | 0.00 |
July | 11755.52 | 01-JUL-18:22 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.57 |
August | 11707.62 | 13-AUG-17:42 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 |
September | 12128.67 | 10-SEP-17:52 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 7.02 | 0.00 |
October | 10321.71 | 09-OCT-16:22 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 |
November | 4750.04 | 07-NOV-15:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 |
December | 2595.43 | 04-DEC-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2595.43 | 0.00 | 74.61 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12202.60 | 805.38 | 268.64 | 3028.56 | 0.00 | 0.00 | 0.00 | 0.00 | 25.40 | 57.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1647.16 | 20-JAN-14:40 | 1306.65 | 456.17 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 |
February | 1599.08 | 27-FEB-13:10 | 5088.93 | 1697.46 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.73 |
March | 3204.36 | 14-MAR-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.66 |
April | 2937.82 | 20-APR-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.10 |
May | 5090.94 | 17-MAY-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 | 0.00 |
June | 7838.25 | 26-JUN-06:03 | 803.52 | 424.37 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 |
July | 9377.16 | 16-JUL-11:42 | 334.80 | 117.87 | 2392.08 | 0.00 | 0.00 | 0.00 | 0.00 | 140.91 | 0.00 |
August | 5959.96 | 18-AUG-13:50 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 0.00 |
September | 5880.35 | 11-SEP-14:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 | 0.00 |
October | 3657.49 | 11-OCT-14:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 0.00 |
November | 2177.89 | 09-NOV-13:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.10 |
December | 1424.64 | 03-DEC-14:53 | 267.84 | 120.42 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1424.64 | 267.84 | 117.87 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9377.16 | 5088.93 | 1697.46 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 140.91 | 67.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2773.08 | 20-JAN-09:40 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.65 |
February | 4225.83 | 27-FEB-09:10 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.77 |
March | 9491.88 | 12-MAR-09:13 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.51 |
April | 6854.46 | 21-APR-08:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 |
May | 8316.37 | 28-MAY-09:13 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.87 |
June | 12738.86 | 18-JUN-10:12 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.88 |
July | 13692.66 | 16-JUL-08:21 | 296.74 | 104.47 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 | 0.00 |
August | 13989.14 | 06-AUG-09:01 | 296.74 | 104.47 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.89 |
September | 13215.89 | 04-SEP-09:12 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.86 |
October | 10118.85 | 01-OCT-08:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.70 |
November | 3966.82 | 07-NOV-09:10 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.68 |
December | 1672.84 | 03-DEC-14:53 | 169.56 | 75.60 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1672.84 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13989.14 | 805.43 | 268.66 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 | 136.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13980.67 | 22-JAN-13:53 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.84 |
February | 14014.85 | 26-FEB-12:52 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.82 |
March | 13900.87 | 12-MAR-11:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.04 |
April | 8339.82 | 21-APR-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 |
May | 7367.25 | 16-MAY-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 | 0.00 |
June | 13568.46 | 25-JUN-12:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 45.65 | 0.00 |
July | 13190.54 | 16-JUL-11:42 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 142.73 | 0.00 |
August | 14300.37 | 06-AUG-12:22 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 0.00 |
September | 15554.29 | 10-SEP-12:41 | 468.72 | 165.01 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 27.79 | 0.00 |
October | 14553.15 | 15-OCT-13:32 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.65 |
November | 14264.23 | 05-NOV-13:02 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 |
December | 13900.98 | 17-DEC-13:02 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7367.25 | 267.84 | 94.29 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15554.29 | 1306.65 | 424.37 | 3348.89 | 0.00 | 0.00 | 0.00 | 0.00 | 142.73 | 232.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4181.33 | 20-JAN-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 |
February | 4668.56 | 17-FEB-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 |
March | 10063.86 | 12-MAR-17:12 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.52 |
April | 8771.99 | 08-APR-17:06 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.47 |
May | 8089.01 | 31-MAY-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 0.00 |
June | 14270.03 | 25-JUN-16:21 | 296.72 | 104.46 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 35.49 | 0.00 |
July | 14158.46 | 02-JUL-16:42 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 | 0.00 |
August | 13834.55 | 13-AUG-16:22 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 |
September | 15034.63 | 10-SEP-17:21 | 0.00 | 119.38 | 1955.35 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 0.00 |
October | 10662.16 | 09-OCT-16:22 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 |
November | 5387.56 | 07-NOV-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
December | 3102.21 | 01-DEC-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3102.21 | 0.00 | 59.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15034.63 | 805.38 | 268.64 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 35.49 | 90.47 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.113044E+12 | 166176.53 | 05-JAN-07:10 | 0.344425E+11 | 94274.09 | 05-JAN-07:30 |
February | 0.106422E+12 | 198912.02 | 06-FEB-07:10 | 0.330432E+11 | 66785.67 | 06-FEB-07:40 |
March | 0.110236E+12 | 166896.95 | 20-MAR-06:10 | 0.251553E+11 | 64091.73 | 04-MAR-17:49 |
April | 0.953273E+11 | 160064.55 | 03-APR-06:10 | 0.176744E+11 | 60715.85 | 03-APR-06:19 |
May | 0.101182E+12 | 112924.55 | 31-MAY-15:50 | 0.100053E+11 | 32669.80 | 02-MAY-06:10 |
June | 0.136825E+12 | 165212.22 | 26-JUN-15:09 | 0.901216E+10 | 9210.53 | 01-JUN-11:00 |
July | 0.133514E+12 | 150245.92 | 17-JUL-10:39 | 0.861585E+10 | 9107.84 | 03-JUL-11:09 |
August | 0.138235E+12 | 152923.74 | 16-AUG-15:09 | 0.902485E+10 | 9058.53 | 31-AUG-11:20 |
September | 0.114872E+12 | 133615.70 | 12-SEP-15:50 | 0.899194E+10 | 33841.99 | 22-SEP-06:19 |
October | 0.104428E+12 | 157879.70 | 30-OCT-06:10 | 0.197513E+11 | 70206.60 | 30-OCT-06:40 |
November | 0.104457E+12 | 151578.08 | 30-NOV-07:10 | 0.274340E+11 | 79058.86 | 29-NOV-20:49 |
December | 0.123098E+12 | 190316.16 | 26-DEC-07:10 | 0.447276E+11 | 111452.60 | 23-DEC-07:19 |
Annual Sum or Average | 0.138164E+13 | 0.247878E+12 | ||||
Minimum of Months | 0.953273E+11 | 112924.55 | 0.861585E+10 | 9058.53 | ||
Maximum of Months | 0.138235E+12 | 198912.02 | 0.447276E+11 | 111452.60 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.174685E+11 | 0.564546E+10 | 0.593559E+11 | 0.980161E+09 | 0.513808E+10 | 1312252.65 | 0.238300E+11 | 0.624813E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155823E+11 | 0.454970E+10 | 0.537310E+11 | 0.886832E+09 | 0.485453E+10 | 1186778.30 | 0.265891E+11 | 0.227140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181699E+11 | 0.427159E+10 | 0.617796E+11 | 0.102606E+10 | 0.629279E+10 | 1343621.24 | 0.166368E+11 | 0.205826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160889E+11 | 0.345324E+10 | 0.572952E+11 | 0.943588E+09 | 0.522506E+10 | 1267813.82 | 0.104979E+11 | 0.182209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172182E+11 | 0.309698E+10 | 0.605677E+11 | 0.100268E+10 | 0.831311E+10 | 1327936.95 | 0.169177E+10 | 0.929071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170716E+11 | 0.280700E+10 | 0.594895E+11 | 0.987011E+09 | 0.181050E+11 | 1296568.36 | 57655843.28 | 0.383062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160234E+11 | 0.297733E+10 | 0.583622E+11 | 0.959046E+09 | 0.169809E+11 | 1299182.41 | 30694484.52 | 0.381794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179331E+11 | 0.334495E+10 | 0.617796E+11 | 0.102593E+10 | 0.174094E+11 | 1343621.24 | 59359653.69 | 0.366814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161395E+11 | 0.380744E+10 | 0.572729E+11 | 0.943374E+09 | 0.128562E+11 | 1267813.82 | 0.404295E+09 | 0.234474E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170427E+11 | 0.471849E+10 | 0.593671E+11 | 0.979869E+09 | 0.708198E+10 | 1312252.65 | 0.111942E+11 | 0.404229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172315E+11 | 0.525909E+10 | 0.580818E+11 | 0.961962E+09 | 0.539104E+10 | 1278270.02 | 0.162934E+11 | 0.123709E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169938E+11 | 0.583886E+10 | 0.583511E+11 | 0.959701E+09 | 0.521843E+10 | 1299182.41 | 0.350736E+11 | 0.661181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202963E+12 | 0.497701E+11 | 0.705434E+12 | 0.116562E+11 | 0.112867E+12 | 15535293.87 | 0.142359E+12 | 0.156578E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.155823E+11 | 0.280700E+10 | 0.537310E+11 | 0.886832E+09 | 0.485453E+10 | 1186778.30 | 30694484.52 | 0.227140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181699E+11 | 0.583886E+10 | 0.617796E+11 | 0.102606E+10 | 0.181050E+11 | 1343621.24 | 0.350736E+11 | 0.383062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.245574E+11 | 0.00 | 0.988509E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.240096E+11 | 0.00 | 0.903359E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.148451E+11 | 0.00 | 0.103101E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.835635E+10 | 0.00 | 0.931803E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.498723E+09 | 0.00 | 0.950663E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.901216E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.861585E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.902485E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.508955E+09 | 0.00 | 0.848299E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.107430E+11 | 0.00 | 0.900834E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.183153E+11 | 0.00 | 0.911869E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.352173E+11 | 0.00 | 0.951031E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.137052E+12 | 0.00 | 0.110827E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.848299E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.352173E+11 | 0.00 | 0.103101E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21377.78 | 02-JAN-16:49 | 5557.43 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 833.98 | 02-JAN-16:00 | 7340.27 | 24-JAN-15:00 | 0.73 | 02-JAN-07:10 | 127289.43 | 05-JAN-07:10 |
February | 20881.53 | 06-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 833.15 | 08-FEB-08:20 | 7023.79 | 27-FEB-15:20 | 0.73 | 01-FEB-07:10 | 164237.08 | 06-FEB-07:10 |
March | 19394.68 | 21-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 832.70 | 21-MAR-07:19 | 17593.72 | 15-MAR-15:00 | 0.73 | 01-MAR-07:10 | 133544.24 | 20-MAR-06:10 |
April | 18654.42 | 03-APR-07:10 | 5557.43 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 831.72 | 03-APR-07:19 | 10739.09 | 21-APR-13:30 | 0.73 | 03-APR-06:10 | 127138.22 | 03-APR-06:10 |
May | 16905.29 | 12-MAY-13:30 | 3195.36 | 01-MAY-18:49 | 45864.70 | 01-MAY-07:10 | 829.38 | 19-MAY-07:19 | 18103.62 | 18-MAY-14:30 | 0.73 | 02-MAY-06:10 | 57166.91 | 01-MAY-06:10 |
June | 17077.57 | 16-JUN-07:10 | 3195.36 | 01-JUN-19:19 | 45864.70 | 01-JUN-07:10 | 829.64 | 16-JUN-07:19 | 31591.61 | 27-JUN-15:09 | 0.73 | 25-JUN-15:00 | 9318.77 | 09-JUN-06:19 |
July | 16962.56 | 28-JUL-07:10 | 3195.36 | 01-JUL-19:30 | 45864.70 | 03-JUL-07:10 | 829.49 | 28-JUL-07:19 | 32528.53 | 24-JUL-15:30 | 0.73 | 01-JUL-05:19 | 7166.56 | 03-JUL-06:19 |
August | 17310.50 | 28-AUG-15:00 | 5557.43 | 10-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 829.63 | 21-AUG-07:40 | 28783.32 | 11-AUG-15:09 | 0.73 | 01-AUG-05:30 | 5421.73 | 23-AUG-06:19 |
September | 17326.12 | 21-SEP-15:00 | 5557.43 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 829.86 | 25-SEP-07:19 | 26080.79 | 05-SEP-15:39 | 0.73 | 22-SEP-07:10 | 31006.10 | 22-SEP-06:10 |
October | 20212.84 | 30-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 833.79 | 30-OCT-07:19 | 17664.49 | 11-OCT-15:00 | 0.73 | 23-OCT-06:10 | 119249.58 | 30-OCT-06:10 |
November | 21377.78 | 06-NOV-16:49 | 5557.43 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 833.98 | 06-NOV-16:00 | 9457.39 | 08-NOV-15:30 | 0.73 | 01-NOV-06:10 | 118529.26 | 30-NOV-07:10 |
December | 21377.78 | 01-DEC-16:30 | 5557.43 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 833.98 | 01-DEC-16:40 | 6007.31 | 14-DEC-15:09 | 0.73 | 05-DEC-08:09 | 150826.37 | 26-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 16905.29 | 3195.36 | 45864.70 | 829.38 | 6007.31 | 0.73 | 5421.73 | |||||||
Maximum of Months | 21377.78 | 5557.43 | 45864.70 | 833.98 | 32528.53 | 0.73 | 164237.08 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 14884.15 | 20-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10665.03 | 18-FEB-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23237.31 | 14-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15560.08 | 20-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35116.19 | 31-MAY-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76338.79 | 26-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 63352.11 | 17-JUL-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 65601.83 | 16-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49126.59 | 12-SEP-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34508.35 | 11-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18089.76 | 07-NOV-14:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13958.36 | 01-DEC-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 10665.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76338.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 166176.53 | 05-JAN-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 4860.60 | 0.73 | 127289.43 | 0.00 | 0.00 |
February | 198912.02 | 06-FEB-07:10 | 7126.03 | 21098.80 | 0.00 | 243.52 | 6205.87 | 0.73 | 164237.08 | 0.00 | 0.00 |
March | 166896.95 | 20-MAR-06:10 | 7126.03 | 21098.80 | 0.00 | 243.52 | 4883.64 | 0.73 | 133544.24 | 0.00 | 0.00 |
April | 160064.55 | 03-APR-06:10 | 6806.56 | 21098.80 | 0.00 | 243.49 | 4776.76 | 0.73 | 127138.22 | 0.00 | 0.00 |
May | 112924.55 | 31-MAY-15:50 | 16818.70 | 42072.41 | 0.00 | 827.95 | 18088.58 | 0.73 | 0.00 | 35116.19 | 0.00 |
June | 165212.22 | 26-JUN-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 29153.64 | 0.73 | 0.00 | 76338.79 | 0.00 |
July | 150245.92 | 17-JUL-10:39 | 16818.70 | 41577.77 | 0.00 | 827.77 | 30314.13 | 0.73 | 0.00 | 60706.82 | 0.00 |
August | 152923.74 | 16-AUG-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 27752.24 | 0.73 | 0.00 | 65451.71 | 0.00 |
September | 133615.70 | 12-SEP-15:50 | 16818.70 | 42072.41 | 0.00 | 827.95 | 24769.32 | 0.73 | 0.00 | 49126.59 | 0.00 |
October | 157879.70 | 30-OCT-06:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 4603.62 | 0.73 | 119249.58 | 0.00 | 0.00 |
November | 151578.08 | 30-NOV-07:10 | 7126.03 | 21098.80 | 0.00 | 243.52 | 4579.74 | 0.73 | 118529.26 | 0.00 | 0.00 |
December | 190316.16 | 26-DEC-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 5463.29 | 0.73 | 150826.37 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 112924.55 | 6806.56 | 21098.80 | 0.00 | 243.49 | 4579.74 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 198912.02 | 16818.70 | 42072.41 | 5557.43 | 827.95 | 30314.13 | 0.73 | 164237.08 | 76338.79 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 86095.28 | 05-JAN-07:30 | 0.00 | 9705.00 | 31-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 61159.85 | 11-FEB-17:00 | 0.00 | 9794.57 | 07-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 57013.56 | 04-MAR-17:00 | 0.00 | 9668.50 | 02-MAR-12:20 | 0.00 |
April | 0.00 | 0.00 | 53800.20 | 17-APR-06:19 | 0.00 | 9459.04 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 25620.80 | 02-MAY-06:19 | 0.00 | 9341.68 | 02-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 9210.53 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9107.84 | 03-JUL-11:09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9058.53 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 25882.60 | 22-SEP-06:10 | 0.00 | 9110.83 | 28-SEP-11:09 | 0.00 |
October | 0.00 | 0.00 | 62344.20 | 30-OCT-06:30 | 0.00 | 9238.38 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 71522.28 | 29-NOV-20:00 | 0.00 | 9356.42 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 103522.90 | 23-DEC-07:19 | 0.00 | 9469.40 | 29-DEC-12:09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9058.53 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 103522.90 | 0.00 | 9794.57 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.19 | 0.00 | 26.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.16 | 0.00 | 26.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 26.18 | 0.00 | 26.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.19 | 0.00 | 26.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Annual Sum or Average | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 18.50 | 0.33 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
March | 0.33 | 18.01 | 0.17 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 17.55 | 0.17 | 17.86 | 0.00 | 17.86 | 0.00 | 17.86 |
Annual Sum or Average | 1.50 | 17.97 | 0.67 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.50 | 0.33 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 16.87 | 2.67 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
February | 15.33 | 16.26 | 6.67 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
March | 3.00 | 15.63 | 1.67 | 15.63 | 0.00 | 15.63 | 0.00 | 15.63 |
April | 2.33 | 17.39 | 1.00 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.58 | 1.33 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.56 | 3.50 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.67 | 17.70 | 0.83 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
November | 2.83 | 17.67 | 1.17 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
December | 30.00 | 16.42 | 12.67 | 16.99 | 0.00 | 16.99 | 0.00 | 16.99 |
Annual Sum or Average | 62.00 | 16.52 | 26.67 | 17.01 | 6.83 | 17.76 | 5.00 | 18.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.00 | 17.70 | 12.67 | 18.33 | 4.67 | 27.58 | 3.50 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 16.07 | 0.50 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
February | 11.17 | 15.05 | 2.33 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
March | 3.33 | 15.12 | 1.33 | 15.00 | 0.33 | 15.83 | 0.33 | 16.55 |
April | 1.67 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.82 | 6.83 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 28.03 | 13.67 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.10 | 5.50 | 28.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.72 | 3.83 | 27.72 |
October | 1.33 | 15.48 | 0.00 | 15.48 | 0.33 | 17.88 | 0.33 | 19.47 |
November | 2.00 | 16.12 | 0.00 | 16.12 | 0.00 | 16.12 | 0.00 | 16.12 |
December | 17.00 | 14.94 | 1.50 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
Annual Sum or Average | 41.00 | 15.21 | 5.67 | 15.18 | 31.50 | 20.32 | 30.67 | 22.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 | 0.00 | 14.95 |
Maximum of Months | 17.00 | 16.12 | 2.33 | 16.12 | 14.17 | 28.10 | 13.67 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 16.78 | 0.33 | 17.10 | 0.83 | 19.59 | 0.83 | 21.12 |
February | 7.00 | 15.23 | 1.17 | 15.26 | 1.17 | 16.85 | 1.17 | 18.09 |
March | 2.17 | 15.12 | 1.33 | 14.99 | 1.50 | 18.92 | 1.50 | 21.03 |
April | 1.33 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.65 | 4.33 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.77 | 8.33 | 27.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.89 | 5.17 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.29 | 9.50 | 27.28 |
October | 0.83 | 16.72 | 0.17 | 17.17 | 5.83 | 26.67 | 5.83 | 27.41 |
November | 1.00 | 16.71 | 0.00 | 16.71 | 2.67 | 24.92 | 2.67 | 26.22 |
December | 11.83 | 15.31 | 1.67 | 15.49 | 2.00 | 17.09 | 2.00 | 18.32 |
Annual Sum or Average | 26.50 | 15.52 | 4.67 | 15.62 | 43.17 | 22.67 | 41.67 | 24.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.77 | 0.00 | 15.77 |
Maximum of Months | 11.83 | 16.78 | 1.67 | 17.17 | 10.00 | 27.89 | 9.50 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.50 | 15.99 | 0.67 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
February | 11.17 | 15.05 | 3.17 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
March | 3.83 | 15.11 | 1.67 | 15.00 | 0.83 | 16.70 | 0.67 | 17.77 |
April | 2.17 | 15.61 | 0.00 | 15.61 | 0.17 | 16.50 | 0.17 | 17.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.55 | 1.00 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.60 | 4.00 | 28.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.19 | 6.17 | 28.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.40 | 2.33 | 28.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.21 | 4.00 | 28.23 |
October | 1.50 | 15.43 | 0.00 | 15.43 | 1.50 | 21.81 | 1.33 | 23.80 |
November | 1.67 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
December | 18.00 | 14.94 | 3.17 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
Annual Sum or Average | 41.83 | 15.18 | 8.67 | 15.13 | 29.17 | 19.95 | 19.67 | 21.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 | 0.00 | 14.93 |
Maximum of Months | 18.00 | 16.37 | 3.17 | 16.37 | 8.50 | 28.60 | 6.17 | 28.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.42 | 0.33 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
February | 3.33 | 19.28 | 2.83 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 19.00 | 1.50 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Annual Sum or Average | 5.83 | 19.19 | 4.67 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.42 | 2.83 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.62 | 2.33 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.69 | 9.17 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.80 | 4.17 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.56 | 3.33 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
Annual Sum or Average | 1.00 | 16.86 | 0.00 | 16.86 | 19.17 | 27.14 | 19.17 | 27.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 16.88 | 0.00 | 16.88 | 9.17 | 27.80 | 9.17 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.83 | 17.17 | 50.83 | 17.17 | 0.83 | 17.25 | 0.83 | 17.33 |
February | 53.67 | 17.15 | 53.17 | 17.15 | 1.17 | 17.26 | 1.17 | 17.37 |
March | 45.33 | 17.91 | 45.33 | 17.91 | 1.17 | 18.03 | 1.17 | 18.15 |
April | 35.17 | 18.14 | 35.17 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
May | 10.50 | 19.10 | 10.50 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 25.34 | 14.67 | 25.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 25.30 | 12.83 | 25.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 25.66 | 20.50 | 25.66 |
September | 2.17 | 18.16 | 2.17 | 18.16 | 20.50 | 24.63 | 19.83 | 25.21 |
October | 34.33 | 17.68 | 34.33 | 17.68 | 14.33 | 19.20 | 14.00 | 20.25 |
November | 42.00 | 17.35 | 42.00 | 17.35 | 3.00 | 17.71 | 3.00 | 18.05 |
December | 66.17 | 16.68 | 65.67 | 16.68 | 2.33 | 16.87 | 2.33 | 17.06 |
Annual Sum or Average | 340.17 | 17.41 | 339.17 | 17.41 | 91.33 | 18.42 | 90.33 | 19.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 | 0.00 | 17.06 |
Maximum of Months | 66.17 | 19.10 | 65.67 | 19.10 | 20.50 | 25.66 | 20.50 | 25.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.50 | 0.17 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.03 | 3.17 | 28.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.98 | 2.50 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.02 | 1.83 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.86 | 3.50 | 27.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.90 | 1.50 | 27.90 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
Annual Sum or Average | 1.00 | 16.91 | 0.00 | 16.91 | 19.50 | 27.42 | 12.83 | 27.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 16.93 | 0.00 | 16.93 | 5.67 | 28.03 | 3.50 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
February | 2.00 | 18.65 | 1.33 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
March | 0.17 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 | 0.00 | 17.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.39 | 0.17 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.46 | 2.00 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
December | 4.33 | 17.46 | 2.33 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
Annual Sum or Average | 6.83 | 17.79 | 3.67 | 18.25 | 2.50 | 20.02 | 2.17 | 21.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.33 | 18.65 | 2.33 | 19.07 | 2.00 | 27.46 | 2.00 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
February | 0.83 | 17.12 | 0.17 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
March | 0.17 | 17.17 | 0.00 | 17.17 | 0.67 | 25.57 | 0.67 | 26.50 |
April | 0.17 | 17.23 | 0.00 | 17.23 | 0.17 | 22.26 | 0.17 | 23.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.55 | 0.67 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.78 | 5.50 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.03 | 11.33 | 28.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.16 | 4.50 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.81 | 3.67 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.60 | 1.33 | 27.60 |
November | 0.17 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
December | 2.50 | 15.65 | 0.33 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
Annual Sum or Average | 4.17 | 16.24 | 0.50 | 16.26 | 27.83 | 26.25 | 27.83 | 27.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 0.00 | 15.55 |
Maximum of Months | 2.50 | 17.23 | 0.33 | 17.50 | 11.33 | 28.16 | 11.33 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 17.20 | 0.00 | 17.20 | 2.00 | 26.84 | 2.00 | 27.22 |
February | 0.83 | 17.21 | 0.17 | 17.56 | 2.17 | 24.59 | 2.17 | 25.91 |
March | 0.17 | 17.23 | 0.00 | 17.23 | 1.83 | 27.04 | 1.83 | 27.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.54 | 2.50 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.58 | 6.83 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.75 | 5.00 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.04 | 10.33 | 27.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 26.80 | 11.67 | 26.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.10 | 6.00 | 27.10 |
December | 1.17 | 16.36 | 0.17 | 16.19 | 2.67 | 24.06 | 2.67 | 25.63 |
Annual Sum or Average | 2.33 | 16.79 | 0.33 | 16.83 | 51.50 | 26.78 | 51.17 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 17.23 | 0.17 | 17.56 | 11.67 | 27.75 | 11.67 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
February | 1.17 | 16.53 | 0.17 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
March | 0.17 | 17.16 | 0.00 | 17.16 | 1.00 | 26.24 | 0.67 | 26.80 |
April | 0.33 | 17.20 | 0.00 | 17.20 | 0.17 | 20.78 | 0.17 | 22.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.45 | 0.83 | 27.46 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.46 | 3.67 | 28.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.14 | 4.33 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.25 | 2.33 | 28.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.08 | 3.83 | 28.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.91 | 2.00 | 27.93 |
November | 0.17 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
December | 2.50 | 15.67 | 0.50 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
Annual Sum or Average | 4.67 | 16.21 | 0.67 | 16.19 | 26.17 | 26.13 | 17.83 | 26.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 0.00 | 15.55 |
Maximum of Months | 2.50 | 17.20 | 0.50 | 17.20 | 6.50 | 28.46 | 4.33 | 28.53 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 486.00 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
February | 428.67 | 23.43 | 3.33 | 23.41 | 3.33 | 23.39 |
March | 474.33 | 23.71 | 2.50 | 23.71 | 0.00 | 23.71 |
April | 380.33 | 23.79 | 6.17 | 23.82 | 0.00 | 23.82 |
May | 135.33 | 23.95 | 128.17 | 24.53 | 0.00 | 24.53 |
June | 2.17 | 24.00 | 290.50 | 24.54 | 0.50 | 24.54 |
July | 21.00 | 24.51 | 341.50 | 24.52 | 18.33 | 24.53 |
August | 2.17 | 24.23 | 331.17 | 24.54 | 1.33 | 24.53 |
September | 41.83 | 24.01 | 155.83 | 24.76 | 0.00 | 24.76 |
October | 269.17 | 23.91 | 34.50 | 24.11 | 0.00 | 24.11 |
November | 379.50 | 23.79 | 2.83 | 23.80 | 0.00 | 23.80 |
December | 497.00 | 23.35 | 18.17 | 23.27 | 18.17 | 23.20 |
Annual Sum or Average | 3117.50 | 23.64 | 1314.67 | 23.93 | 41.67 | 23.92 |
Minimum of Months | 2.17 | 23.35 | 0.00 | 23.27 | 0.00 | 23.20 |
Maximum of Months | 497.00 | 24.51 | 341.50 | 24.76 | 18.33 | 24.76 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.07 | 90.00 | 21.86 | 90.00 | 21.70 |
February | 454.00 | 22.13 | 90.17 | 21.88 | 90.17 | 21.70 |
March | 499.00 | 22.62 | 33.50 | 22.50 | 33.50 | 22.39 |
April | 464.00 | 22.78 | 16.83 | 22.71 | 16.83 | 22.65 |
May | 245.50 | 23.54 | 32.00 | 23.66 | 0.00 | 23.66 |
June | 15.83 | 23.94 | 247.33 | 24.35 | 0.00 | 24.35 |
July | 38.50 | 24.23 | 287.83 | 24.36 | 26.83 | 24.36 |
August | 8.00 | 24.00 | 267.33 | 24.42 | 0.00 | 24.42 |
September | 142.33 | 23.78 | 101.67 | 24.21 | 0.00 | 24.21 |
October | 447.83 | 23.23 | 19.17 | 23.16 | 16.50 | 23.08 |
November | 479.33 | 22.58 | 13.50 | 22.53 | 13.50 | 22.48 |
December | 497.00 | 21.77 | 130.67 | 21.50 | 130.67 | 21.32 |
Annual Sum or Average | 3793.33 | 22.59 | 1330.00 | 22.78 | 418.00 | 22.64 |
Minimum of Months | 8.00 | 21.77 | 13.50 | 21.50 | 0.00 | 21.32 |
Maximum of Months | 502.00 | 24.23 | 287.83 | 24.42 | 130.67 | 24.42 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.22 | 221.67 | 20.92 | 221.67 | 20.77 |
February | 454.00 | 21.37 | 194.50 | 21.05 | 194.50 | 20.89 |
March | 510.67 | 22.01 | 118.67 | 21.67 | 118.67 | 21.43 |
April | 471.17 | 22.13 | 98.00 | 21.81 | 98.00 | 21.58 |
May | 310.67 | 23.26 | 24.83 | 23.27 | 5.33 | 23.23 |
June | 31.67 | 23.75 | 251.17 | 24.28 | 0.00 | 24.28 |
July | 46.83 | 24.04 | 297.17 | 24.31 | 28.50 | 24.30 |
August | 30.50 | 23.77 | 255.00 | 24.28 | 0.00 | 24.28 |
September | 192.50 | 23.45 | 83.50 | 23.80 | 0.00 | 23.80 |
October | 489.33 | 22.55 | 68.33 | 22.31 | 68.33 | 22.12 |
November | 489.00 | 21.72 | 141.50 | 21.47 | 141.50 | 21.32 |
December | 497.00 | 20.91 | 289.83 | 20.66 | 289.83 | 20.54 |
Annual Sum or Average | 4025.33 | 21.96 | 2044.17 | 22.02 | 1166.33 | 21.76 |
Minimum of Months | 30.50 | 20.91 | 24.83 | 20.66 | 0.00 | 20.54 |
Maximum of Months | 510.67 | 24.04 | 297.17 | 24.31 | 289.83 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.29 | 370.17 | 20.10 | 370.17 | 20.03 |
February | 454.00 | 20.44 | 335.17 | 20.27 | 335.17 | 20.20 |
March | 514.00 | 21.22 | 251.33 | 20.83 | 251.33 | 20.64 |
April | 468.00 | 21.31 | 186.00 | 20.87 | 186.00 | 20.62 |
May | 310.50 | 22.78 | 74.00 | 22.90 | 20.33 | 22.78 |
June | 40.83 | 23.76 | 329.00 | 24.32 | 5.67 | 24.33 |
July | 67.50 | 24.20 | 357.50 | 24.43 | 43.33 | 24.44 |
August | 71.50 | 23.40 | 283.83 | 24.15 | 5.00 | 24.15 |
September | 231.50 | 23.01 | 104.17 | 23.40 | 10.67 | 23.32 |
October | 497.17 | 21.67 | 168.17 | 21.30 | 168.17 | 21.08 |
November | 489.00 | 20.77 | 310.67 | 20.54 | 310.67 | 20.43 |
December | 497.00 | 20.10 | 437.50 | 20.00 | 437.50 | 19.97 |
Annual Sum or Average | 4143.00 | 21.23 | 3207.50 | 21.36 | 2144.00 | 21.08 |
Minimum of Months | 40.83 | 20.10 | 74.00 | 20.00 | 5.00 | 19.97 |
Maximum of Months | 514.00 | 24.20 | 437.50 | 24.43 | 437.50 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.69 | 293.67 | 20.41 | 293.67 | 20.28 |
February | 439.83 | 20.89 | 253.50 | 20.55 | 253.50 | 20.38 |
March | 450.83 | 21.40 | 201.83 | 21.02 | 194.00 | 20.78 |
April | 392.17 | 21.24 | 182.00 | 20.91 | 160.83 | 20.63 |
May | 221.67 | 22.64 | 155.83 | 23.25 | 13.50 | 23.15 |
June | 46.33 | 25.21 | 396.33 | 24.51 | 27.50 | 24.63 |
July | 98.00 | 25.20 | 419.33 | 24.69 | 78.83 | 24.82 |
August | 69.83 | 24.28 | 374.83 | 24.37 | 24.17 | 24.48 |
September | 160.83 | 23.08 | 195.50 | 23.82 | 16.33 | 23.83 |
October | 405.67 | 21.66 | 158.00 | 21.43 | 138.33 | 21.18 |
November | 477.17 | 21.11 | 225.33 | 20.81 | 225.33 | 20.66 |
December | 497.00 | 20.38 | 366.33 | 20.17 | 366.33 | 20.09 |
Annual Sum or Average | 3761.33 | 21.43 | 3222.50 | 21.77 | 1792.33 | 21.50 |
Minimum of Months | 46.33 | 20.38 | 155.83 | 20.17 | 13.50 | 20.09 |
Maximum of Months | 502.00 | 25.21 | 419.33 | 24.69 | 366.33 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.33 | 21.18 | 244.33 | 21.15 | 189.17 | 20.89 |
February | 335.67 | 21.10 | 233.17 | 21.04 | 182.00 | 20.77 |
March | 387.83 | 21.40 | 217.33 | 21.21 | 183.17 | 20.96 |
April | 384.50 | 21.17 | 183.00 | 20.86 | 161.67 | 20.59 |
May | 269.00 | 22.55 | 125.00 | 22.98 | 20.67 | 22.85 |
June | 84.67 | 23.78 | 319.83 | 24.27 | 15.33 | 24.34 |
July | 102.17 | 24.28 | 357.17 | 24.45 | 55.17 | 24.52 |
August | 90.83 | 23.91 | 340.83 | 24.31 | 21.33 | 24.40 |
September | 166.00 | 23.41 | 225.50 | 24.04 | 28.33 | 24.13 |
October | 339.17 | 21.85 | 233.33 | 22.06 | 143.00 | 21.85 |
November | 340.83 | 21.44 | 230.17 | 21.58 | 155.33 | 21.32 |
December | 408.00 | 20.94 | 279.33 | 20.74 | 254.33 | 20.54 |
Annual Sum or Average | 3280.00 | 21.73 | 2989.00 | 22.15 | 1409.50 | 21.87 |
Minimum of Months | 84.67 | 20.94 | 125.00 | 20.74 | 15.33 | 20.54 |
Maximum of Months | 408.00 | 24.28 | 357.17 | 24.45 | 254.33 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.00 | 20.60 | 317.83 | 20.35 | 317.83 | 20.24 |
February | 423.67 | 20.69 | 280.50 | 20.46 | 276.33 | 20.34 |
March | 447.50 | 21.03 | 247.67 | 20.82 | 231.00 | 20.64 |
April | 414.33 | 21.01 | 202.83 | 20.77 | 179.33 | 20.53 |
May | 297.00 | 22.38 | 136.50 | 22.87 | 23.00 | 22.77 |
June | 103.17 | 23.73 | 328.67 | 24.25 | 23.17 | 24.37 |
July | 124.33 | 23.94 | 354.17 | 24.30 | 55.33 | 24.38 |
August | 113.67 | 23.31 | 322.50 | 24.09 | 16.50 | 24.16 |
September | 237.50 | 22.91 | 171.17 | 23.51 | 26.33 | 23.55 |
October | 422.00 | 21.37 | 202.83 | 21.30 | 167.83 | 21.11 |
November | 456.17 | 20.93 | 252.83 | 20.68 | 251.50 | 20.55 |
December | 491.67 | 20.39 | 378.17 | 20.18 | 378.17 | 20.10 |
Annual Sum or Average | 4014.00 | 21.32 | 3195.67 | 21.59 | 1946.33 | 21.33 |
Minimum of Months | 103.17 | 20.39 | 136.50 | 20.18 | 16.50 | 20.10 |
Maximum of Months | 491.67 | 23.94 | 378.17 | 24.30 | 378.17 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.52 | 360.83 | 20.39 | 360.83 | 20.34 |
February | 454.00 | 20.55 | 345.33 | 20.45 | 345.33 | 20.40 |
March | 514.00 | 21.10 | 270.50 | 20.85 | 270.50 | 20.73 |
April | 485.00 | 21.38 | 161.33 | 21.12 | 161.33 | 20.96 |
May | 403.50 | 22.98 | 29.50 | 22.93 | 16.50 | 22.84 |
June | 43.33 | 23.77 | 234.50 | 24.21 | 3.67 | 24.21 |
July | 54.33 | 23.90 | 294.67 | 24.28 | 32.33 | 24.26 |
August | 52.67 | 23.71 | 238.17 | 24.19 | 4.00 | 24.18 |
September | 198.83 | 23.48 | 97.33 | 23.87 | 0.00 | 23.87 |
October | 498.83 | 22.36 | 68.67 | 22.14 | 68.67 | 21.96 |
November | 489.00 | 21.31 | 179.17 | 21.12 | 179.17 | 21.01 |
December | 497.00 | 20.48 | 393.67 | 20.38 | 393.67 | 20.33 |
Annual Sum or Average | 4192.50 | 21.50 | 2673.67 | 21.55 | 1836.00 | 21.31 |
Minimum of Months | 43.33 | 20.48 | 29.50 | 20.38 | 0.00 | 20.33 |
Maximum of Months | 514.00 | 23.90 | 393.67 | 24.28 | 393.67 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.10 | 237.17 | 20.85 | 237.17 | 20.73 |
February | 449.67 | 21.27 | 224.00 | 20.92 | 224.00 | 20.75 |
March | 484.33 | 21.83 | 162.33 | 21.46 | 158.67 | 21.22 |
April | 427.83 | 21.88 | 118.00 | 21.61 | 109.67 | 21.38 |
May | 238.50 | 23.05 | 102.50 | 23.43 | 9.00 | 23.36 |
June | 14.50 | 25.09 | 398.17 | 24.47 | 9.83 | 24.50 |
July | 52.00 | 25.12 | 430.67 | 24.64 | 49.33 | 24.69 |
August | 26.33 | 25.47 | 409.33 | 24.50 | 17.67 | 24.58 |
September | 82.33 | 23.72 | 227.00 | 24.43 | 5.83 | 24.48 |
October | 371.50 | 22.47 | 94.83 | 22.45 | 62.17 | 22.23 |
November | 469.17 | 21.87 | 112.67 | 21.63 | 111.17 | 21.45 |
December | 497.00 | 20.96 | 291.00 | 20.70 | 291.00 | 20.58 |
Annual Sum or Average | 3615.17 | 21.83 | 2807.67 | 22.23 | 1285.50 | 21.96 |
Minimum of Months | 14.50 | 20.96 | 94.83 | 20.70 | 5.83 | 20.58 |
Maximum of Months | 502.00 | 25.47 | 430.67 | 24.64 | 291.00 | 24.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 398.83 | 21.14 | 161.17 | 20.97 | 127.50 | 20.63 |
February | 370.17 | 20.77 | 187.00 | 20.49 | 165.50 | 20.18 |
March | 435.50 | 21.18 | 185.50 | 20.85 | 173.33 | 20.58 |
April | 452.67 | 21.26 | 150.50 | 20.93 | 145.67 | 20.70 |
May | 383.50 | 22.47 | 48.50 | 22.51 | 23.33 | 22.38 |
June | 83.83 | 23.01 | 251.17 | 24.09 | 7.67 | 24.08 |
July | 84.50 | 23.37 | 321.33 | 24.24 | 40.83 | 24.20 |
August | 61.33 | 23.22 | 359.00 | 24.34 | 15.17 | 24.37 |
September | 102.33 | 23.30 | 255.50 | 24.35 | 20.33 | 24.45 |
October | 302.00 | 21.94 | 173.83 | 22.29 | 85.83 | 22.06 |
November | 333.67 | 21.34 | 169.50 | 21.62 | 85.83 | 21.27 |
December | 416.17 | 20.70 | 217.00 | 20.41 | 196.00 | 20.10 |
Annual Sum or Average | 3424.50 | 21.51 | 2480.00 | 21.97 | 1087.00 | 21.64 |
Minimum of Months | 61.33 | 20.70 | 48.50 | 20.41 | 7.67 | 20.10 |
Maximum of Months | 452.67 | 23.37 | 359.00 | 24.35 | 196.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.67 | 21.06 | 250.17 | 20.81 | 250.17 | 20.68 |
February | 441.83 | 21.08 | 231.17 | 20.80 | 231.17 | 20.67 |
March | 480.83 | 21.49 | 195.00 | 21.19 | 190.33 | 20.99 |
April | 449.50 | 21.62 | 126.33 | 21.37 | 121.33 | 21.18 |
May | 314.00 | 22.85 | 80.17 | 23.15 | 9.83 | 23.09 |
June | 51.83 | 24.22 | 338.50 | 24.41 | 15.00 | 24.47 |
July | 65.67 | 24.09 | 358.67 | 24.38 | 39.33 | 24.39 |
August | 41.33 | 24.08 | 366.67 | 24.38 | 13.17 | 24.42 |
September | 125.17 | 23.59 | 190.83 | 24.29 | 9.67 | 24.37 |
October | 400.83 | 22.40 | 96.33 | 22.35 | 65.67 | 22.17 |
November | 458.67 | 21.72 | 114.33 | 21.51 | 113.67 | 21.36 |
December | 496.50 | 20.91 | 306.00 | 20.67 | 306.00 | 20.56 |
Annual Sum or Average | 3822.83 | 21.74 | 2654.17 | 22.05 | 1365.33 | 21.80 |
Minimum of Months | 41.33 | 20.91 | 80.17 | 20.67 | 9.67 | 20.56 |
Maximum of Months | 496.67 | 24.22 | 366.67 | 24.41 | 306.00 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.73 | 281.33 | 20.50 | 281.33 | 20.39 |
February | 454.00 | 20.81 | 268.67 | 20.58 | 268.67 | 20.48 |
March | 513.33 | 21.59 | 171.67 | 21.22 | 171.67 | 20.99 |
April | 470.83 | 21.84 | 116.67 | 21.50 | 116.67 | 21.28 |
May | 284.67 | 23.20 | 64.67 | 23.36 | 8.67 | 23.30 |
June | 14.50 | 24.03 | 335.83 | 24.38 | 3.50 | 24.39 |
July | 36.17 | 24.30 | 371.83 | 24.46 | 35.00 | 24.45 |
August | 31.67 | 23.78 | 296.83 | 24.31 | 2.33 | 24.31 |
September | 192.67 | 23.38 | 105.83 | 23.85 | 0.50 | 23.84 |
October | 492.67 | 22.26 | 81.83 | 21.99 | 81.83 | 21.79 |
November | 489.00 | 21.28 | 203.33 | 21.05 | 203.33 | 20.93 |
December | 497.00 | 20.47 | 367.17 | 20.31 | 367.17 | 20.25 |
Annual Sum or Average | 3978.50 | 21.58 | 2665.67 | 21.77 | 1540.67 | 21.49 |
Minimum of Months | 14.50 | 20.47 | 64.67 | 20.31 | 0.50 | 20.25 |
Maximum of Months | 513.33 | 24.30 | 371.83 | 24.46 | 367.17 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 421.33 | 20.97 | 202.67 | 20.71 | 202.67 | 20.58 |
February | 365.50 | 21.05 | 186.83 | 20.73 | 184.17 | 20.56 |
March | 379.00 | 21.56 | 136.67 | 21.26 | 126.67 | 21.01 |
April | 339.83 | 21.62 | 115.67 | 21.41 | 96.33 | 21.18 |
May | 185.17 | 22.94 | 127.00 | 23.57 | 6.83 | 23.52 |
June | 27.50 | 25.71 | 330.67 | 24.63 | 20.50 | 24.73 |
July | 72.67 | 25.48 | 352.33 | 24.83 | 65.83 | 24.94 |
August | 43.83 | 24.85 | 308.33 | 24.54 | 19.67 | 24.65 |
September | 133.50 | 23.41 | 159.67 | 24.14 | 9.33 | 24.21 |
October | 341.00 | 21.99 | 105.50 | 21.95 | 76.50 | 21.74 |
November | 397.67 | 21.41 | 144.67 | 21.18 | 141.50 | 21.02 |
December | 422.00 | 20.66 | 278.67 | 20.42 | 278.67 | 20.31 |
Annual Sum or Average | 3129.00 | 21.67 | 2448.67 | 22.08 | 1228.67 | 21.83 |
Minimum of Months | 27.50 | 20.66 | 105.50 | 20.42 | 6.83 | 20.31 |
Maximum of Months | 422.00 | 25.71 | 352.33 | 24.83 | 278.67 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 348.67 | 21.67 | 195.33 | 21.79 | 125.33 | 21.53 |
February | 315.50 | 21.49 | 199.50 | 21.50 | 139.00 | 21.21 |
March | 373.50 | 21.79 | 150.83 | 21.64 | 116.33 | 21.37 |
April | 381.67 | 21.79 | 106.67 | 21.57 | 90.83 | 21.33 |
May | 237.83 | 23.03 | 119.33 | 23.46 | 8.67 | 23.39 |
June | 35.50 | 24.17 | 332.17 | 24.39 | 8.17 | 24.43 |
July | 70.67 | 24.64 | 374.17 | 24.54 | 48.50 | 24.59 |
August | 48.17 | 24.71 | 369.50 | 24.47 | 17.83 | 24.56 |
September | 130.83 | 23.94 | 236.67 | 24.42 | 21.33 | 24.56 |
October | 318.67 | 22.44 | 186.50 | 22.74 | 87.83 | 22.61 |
November | 320.67 | 22.00 | 184.83 | 22.29 | 96.67 | 22.07 |
December | 394.50 | 21.46 | 232.50 | 21.31 | 197.17 | 21.08 |
Annual Sum or Average | 2976.17 | 22.13 | 2688.00 | 22.66 | 957.67 | 22.43 |
Minimum of Months | 35.50 | 21.46 | 106.67 | 21.31 | 8.17 | 21.08 |
Maximum of Months | 394.50 | 24.71 | 374.17 | 24.54 | 197.17 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.50 | 21.00 | 236.67 | 20.74 | 236.50 | 20.60 |
February | 420.00 | 21.02 | 221.83 | 20.77 | 216.00 | 20.62 |
March | 445.33 | 21.41 | 166.50 | 21.17 | 152.17 | 20.96 |
April | 415.00 | 21.55 | 129.67 | 21.38 | 109.00 | 21.17 |
May | 262.00 | 22.80 | 131.33 | 23.34 | 7.17 | 23.30 |
June | 64.17 | 24.37 | 343.67 | 24.42 | 21.17 | 24.53 |
July | 82.67 | 24.37 | 367.67 | 24.43 | 49.83 | 24.49 |
August | 67.83 | 23.88 | 344.67 | 24.32 | 16.50 | 24.38 |
September | 186.67 | 23.30 | 176.17 | 23.96 | 15.50 | 24.06 |
October | 414.83 | 21.94 | 120.67 | 21.95 | 82.50 | 21.78 |
November | 448.17 | 21.38 | 165.50 | 21.16 | 163.00 | 21.02 |
December | 489.00 | 20.74 | 323.33 | 20.50 | 323.33 | 20.40 |
Annual Sum or Average | 3772.17 | 21.65 | 2727.67 | 22.00 | 1392.67 | 21.76 |
Minimum of Months | 64.17 | 20.74 | 120.67 | 20.50 | 7.17 | 20.40 |
Maximum of Months | 489.00 | 24.37 | 367.67 | 24.43 | 323.33 | 24.53 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.52982 | 20.24409 | 0.02916 | 5.63088 |
February | 454.00000 | 23.49390 | 18.36443 | 0.00847 | 5.85488 |
March | 514.00000 | 23.79063 | 18.01533 | 0.09953 | 5.57570 |
April | 485.00000 | 23.93704 | 21.90216 | 0.16001 | 5.87032 |
May | 508.00000 | 24.34647 | 24.62063 | -0.5523 | 12.03082 |
June | 496.00000 | 24.34541 | 32.78138 | -0.4301 | 9.28918 |
July | 497.00000 | 24.39607 | 34.73665 | -0.3999 | 8.75599 |
August | 514.00000 | 24.36833 | 33.25811 | -0.4165 | 9.08664 |
September | 485.00000 | 24.38343 | 24.60539 | -0.4869 | 10.55280 |
October | 502.00000 | 24.20037 | 19.06534 | 0.24005 | 6.54906 |
November | 489.00000 | 23.94495 | 20.62623 | 0.15492 | 5.84214 |
December | 497.00000 | 23.34590 | 15.07014 | -0.0508 | 5.94178 |
Annual Sum or Average | 5943.00000 | 24.01078 | 23.65616 | -0.1388 | 7.59798 |
Minimum of Months | 454.00000 | 23.34590 | 15.07014 | -0.5523 | 5.57570 |
Maximum of Months | 514.00000 | 24.39607 | 34.73665 | 0.24005 | 12.03082 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.07084 | 22.27830 | -0.2997 | 8.18109 |
February | 454.00000 | 22.12549 | 20.23267 | -0.3024 | 8.50920 |
March | 514.00000 | 22.67432 | 20.09178 | -0.1563 | 6.94671 |
April | 485.00000 | 22.84055 | 24.12897 | -0.0902 | 6.48391 |
May | 508.00000 | 23.90601 | 26.09394 | -0.7106 | 16.58032 |
June | 496.00000 | 24.21823 | 33.84792 | -0.4881 | 10.27498 |
July | 497.00000 | 24.26228 | 35.71243 | -0.4594 | 9.70050 |
August | 514.00000 | 24.25194 | 34.23749 | -0.4768 | 10.06190 |
September | 485.00000 | 24.16478 | 25.65825 | -0.5855 | 12.87532 |
October | 502.00000 | 23.35350 | 21.04499 | 0.02944 | 6.21267 |
November | 489.00000 | 22.61270 | 23.16592 | -0.1543 | 6.56110 |
December | 497.00000 | 21.77009 | 16.74055 | -0.4112 | 10.15976 |
Annual Sum or Average | 5943.00000 | 23.19668 | 25.31508 | -0.3428 | 9.39233 |
Minimum of Months | 454.00000 | 21.77009 | 16.74055 | -0.7106 | 6.21267 |
Maximum of Months | 514.00000 | 24.26228 | 35.71243 | 0.02944 | 16.58032 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.21825 | 23.15668 | -0.5198 | 12.71941 |
February | 454.00000 | 21.36665 | 20.92715 | -0.4993 | 12.48626 |
March | 514.00000 | 22.02451 | 20.43437 | -0.3221 | 9.81321 |
April | 485.00000 | 22.18327 | 24.87876 | -0.2510 | 8.82281 |
May | 508.00000 | 23.60503 | 26.35831 | -0.8122 | 20.47382 |
June | 496.00000 | 24.17741 | 33.72904 | -0.4920 | 10.40984 |
July | 497.00000 | 24.23952 | 35.64979 | -0.4588 | 9.74752 |
August | 514.00000 | 24.18404 | 34.28721 | -0.4936 | 10.42152 |
September | 485.00000 | 23.94001 | 25.74430 | -0.6654 | 15.56858 |
October | 502.00000 | 22.59168 | 21.97234 | -0.1632 | 7.56501 |
November | 489.00000 | 21.71891 | 24.38495 | -0.3812 | 9.61294 |
December | 497.00000 | 20.91485 | 17.39004 | -0.6362 | 15.67110 |
Annual Sum or Average | 5943.00000 | 22.69218 | 25.78486 | -0.4746 | 11.94343 |
Minimum of Months | 454.00000 | 20.91485 | 17.39004 | -0.8122 | 7.56501 |
Maximum of Months | 514.00000 | 24.23952 | 35.64979 | -0.1632 | 20.47382 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.28582 | 25.21743 | -0.7842 | 20.49929 |
February | 454.00000 | 20.44348 | 22.79046 | -0.7625 | 19.68300 |
March | 514.00000 | 21.21632 | 22.00475 | -0.5383 | 14.60820 |
April | 485.00000 | 21.40525 | 26.34201 | -0.4425 | 13.33757 |
May | 508.00000 | 23.33105 | 27.49675 | -0.8901 | 24.58507 |
June | 496.00000 | 24.24181 | 33.67163 | -0.4245 | 9.63545 |
July | 497.00000 | 24.33672 | 35.64025 | -0.3829 | 9.18767 |
August | 514.00000 | 24.12344 | 34.96400 | -0.4850 | 10.88269 |
September | 485.00000 | 23.68600 | 26.66532 | -0.7415 | 19.62391 |
October | 502.00000 | 21.69170 | 24.16059 | -0.3927 | 11.30243 |
November | 489.00000 | 20.77168 | 26.45253 | -0.6412 | 15.75944 |
December | 497.00000 | 20.09600 | 18.62056 | -0.8898 | 24.17236 |
Annual Sum or Average | 5943.00000 | 22.15118 | 27.03980 | -0.6135 | 16.07671 |
Minimum of Months | 454.00000 | 20.09600 | 18.62056 | -0.8901 | 9.18767 |
Maximum of Months | 514.00000 | 24.33672 | 35.64025 | -0.3829 | 24.58507 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.69164 | 23.97887 | -0.6574 | 16.83056 |
February | 454.00000 | 20.99564 | 21.41966 | -0.5934 | 16.65466 |
March | 514.00000 | 21.75610 | 20.43082 | -0.3667 | 12.96269 |
April | 485.00000 | 21.79896 | 24.96439 | -0.3041 | 12.62439 |
May | 508.00000 | 23.55032 | 26.39139 | -0.7362 | 19.96452 |
June | 496.00000 | 24.32325 | 33.13368 | -0.2822 | 8.22548 |
July | 497.00000 | 24.45102 | 35.20553 | -0.2398 | 8.50572 |
August | 514.00000 | 24.21045 | 34.21909 | -0.3324 | 9.26024 |
September | 485.00000 | 23.88959 | 25.69276 | -0.5731 | 15.56495 |
October | 502.00000 | 22.18335 | 22.57276 | -0.2438 | 11.06059 |
November | 489.00000 | 21.17998 | 25.02848 | -0.5159 | 13.47259 |
December | 497.00000 | 20.38003 | 17.76985 | -0.7931 | 21.18062 |
Annual Sum or Average | 5943.00000 | 22.46457 | 25.93994 | -0.4688 | 13.83493 |
Minimum of Months | 454.00000 | 20.38003 | 17.76985 | -0.7931 | 8.22548 |
Maximum of Months | 514.00000 | 24.45102 | 35.20553 | -0.2398 | 21.18062 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.00738 | 21.70537 | -0.2903 | 13.42350 |
February | 454.00000 | 21.93519 | 19.79215 | -0.3214 | 14.81369 |
March | 514.00000 | 22.09209 | 19.69768 | -0.2675 | 12.89873 |
April | 485.00000 | 21.78712 | 24.79202 | -0.3166 | 12.95206 |
May | 508.00000 | 23.35992 | 26.80448 | -0.8401 | 23.73383 |
June | 496.00000 | 24.15787 | 33.67290 | -0.4231 | 10.37934 |
July | 497.00000 | 24.29782 | 35.53371 | -0.3596 | 9.67779 |
August | 514.00000 | 24.17390 | 34.38829 | -0.3858 | 10.12055 |
September | 485.00000 | 23.98340 | 25.35591 | -0.5267 | 15.49454 |
October | 502.00000 | 22.64340 | 21.40581 | -0.0905 | 12.06189 |
November | 489.00000 | 22.35015 | 22.76333 | -0.1853 | 12.11685 |
December | 497.00000 | 21.56327 | 16.26267 | -0.4563 | 16.61553 |
Annual Sum or Average | 5943.00000 | 22.87128 | 25.23000 | -0.3726 | 13.68761 |
Minimum of Months | 454.00000 | 21.56327 | 16.26267 | -0.8401 | 9.67779 |
Maximum of Months | 514.00000 | 24.29782 | 35.53371 | -0.0905 | 23.73383 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.72591 | 23.50068 | -0.6530 | 17.75459 |
February | 454.00000 | 20.92299 | 21.12584 | -0.6173 | 17.51593 |
March | 514.00000 | 21.44629 | 20.47226 | -0.4428 | 14.13473 |
April | 485.00000 | 21.46699 | 25.24951 | -0.3883 | 13.53934 |
May | 508.00000 | 23.18236 | 27.06510 | -0.8629 | 25.49041 |
June | 496.00000 | 24.09031 | 33.87935 | -0.3818 | 10.82285 |
July | 497.00000 | 24.15699 | 35.94065 | -0.3702 | 10.27400 |
August | 514.00000 | 24.00595 | 35.04362 | -0.4326 | 11.38572 |
September | 485.00000 | 23.59098 | 26.32512 | -0.6846 | 19.94871 |
October | 502.00000 | 21.84824 | 22.71413 | -0.3118 | 11.93036 |
November | 489.00000 | 21.14816 | 24.66408 | -0.5240 | 14.19264 |
December | 497.00000 | 20.43257 | 17.37937 | -0.7875 | 21.72776 |
Annual Sum or Average | 5943.00000 | 22.26396 | 26.15747 | -0.5375 | 15.71187 |
Minimum of Months | 454.00000 | 20.43257 | 17.37937 | -0.8629 | 10.27400 |
Maximum of Months | 514.00000 | 24.15699 | 35.94065 | -0.3118 | 25.49041 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.52433 | 24.97470 | -0.7127 | 17.03895 |
February | 454.00000 | 20.55345 | 22.72364 | -0.7284 | 17.56745 |
March | 514.00000 | 21.10469 | 22.20627 | -0.5638 | 13.35434 |
April | 485.00000 | 21.38172 | 26.73034 | -0.4487 | 10.83814 |
May | 508.00000 | 23.21293 | 28.34583 | -0.9639 | 26.44573 |
June | 496.00000 | 24.15160 | 33.96306 | -0.5061 | 10.67645 |
July | 497.00000 | 24.23684 | 35.80197 | -0.4624 | 9.88382 |
August | 514.00000 | 24.13749 | 34.82041 | -0.5119 | 10.84076 |
September | 485.00000 | 23.94997 | 26.36307 | -0.6565 | 15.45912 |
October | 502.00000 | 22.37076 | 23.29977 | -0.2079 | 7.65920 |
November | 489.00000 | 21.30953 | 25.62855 | -0.4770 | 10.91219 |
December | 497.00000 | 20.48470 | 18.53465 | -0.7554 | 18.58717 |
Annual Sum or Average | 5943.00000 | 22.29905 | 26.98896 | -0.5824 | 14.09736 |
Minimum of Months | 454.00000 | 20.48470 | 18.53465 | -0.9639 | 7.65920 |
Maximum of Months | 514.00000 | 24.23684 | 35.80197 | -0.2079 | 26.44573 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.09567 | 24.04185 | -0.5450 | 12.91500 |
February | 454.00000 | 21.29928 | 21.59587 | -0.5145 | 13.79703 |
March | 514.00000 | 21.98065 | 20.74651 | -0.3174 | 10.58880 |
April | 485.00000 | 22.16411 | 25.10584 | -0.2267 | 9.25795 |
May | 508.00000 | 23.71645 | 26.70051 | -0.7252 | 18.44579 |
June | 496.00000 | 24.36334 | 32.98157 | -0.3197 | 8.00857 |
July | 497.00000 | 24.49879 | 34.94330 | -0.2727 | 7.90014 |
August | 514.00000 | 24.35469 | 33.66725 | -0.3150 | 8.14588 |
September | 485.00000 | 24.26929 | 25.22836 | -0.4492 | 10.99679 |
October | 502.00000 | 22.99049 | 21.68142 | -0.0291 | 8.05453 |
November | 489.00000 | 21.96285 | 24.28482 | -0.2984 | 9.05543 |
December | 497.00000 | 20.95840 | 17.88691 | -0.6182 | 15.11414 |
Annual Sum or Average | 5943.00000 | 22.81708 | 25.77704 | -0.3854 | 11.01340 |
Minimum of Months | 454.00000 | 20.95840 | 17.88691 | -0.7252 | 7.90014 |
Maximum of Months | 514.00000 | 24.49879 | 34.94330 | -0.0291 | 18.44579 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.85965 | 20.63657 | -0.2615 | 12.09140 |
February | 454.00000 | 21.48214 | 18.84323 | -0.3713 | 14.87701 |
March | 514.00000 | 21.67653 | 19.12740 | -0.3339 | 12.32546 |
April | 485.00000 | 21.47221 | 24.45627 | -0.3702 | 11.09851 |
May | 508.00000 | 22.93519 | 27.12877 | -0.9960 | 28.70350 |
June | 496.00000 | 24.09280 | 33.11957 | -0.5028 | 11.51155 |
July | 497.00000 | 24.24062 | 35.29683 | -0.4285 | 10.14330 |
August | 514.00000 | 24.23678 | 33.39417 | -0.3960 | 9.86556 |
September | 485.00000 | 24.20594 | 24.44520 | -0.4406 | 12.39279 |
October | 502.00000 | 22.93757 | 20.17999 | 0.03327 | 11.14247 |
November | 489.00000 | 22.40218 | 21.32303 | -0.0987 | 11.25460 |
December | 497.00000 | 21.34656 | 14.95536 | -0.4249 | 15.72738 |
Annual Sum or Average | 5943.00000 | 22.75064 | 24.46055 | -0.3835 | 13.43923 |
Minimum of Months | 454.00000 | 21.34656 | 14.95536 | -0.9960 | 9.86556 |
Maximum of Months | 514.00000 | 24.24062 | 35.29683 | 0.03327 | 28.70350 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.08845 | 23.64039 | -0.5477 | 13.40207 |
February | 454.00000 | 21.16180 | 21.40621 | -0.5483 | 14.22003 |
March | 514.00000 | 21.67693 | 20.83168 | -0.3935 | 11.44579 |
April | 485.00000 | 21.81862 | 25.53486 | -0.3150 | 9.83072 |
May | 508.00000 | 23.42583 | 27.33599 | -0.8342 | 22.59515 |
June | 496.00000 | 24.24867 | 33.53515 | -0.3864 | 9.39070 |
July | 497.00000 | 24.28168 | 35.61976 | -0.3837 | 9.12983 |
August | 514.00000 | 24.25983 | 34.33590 | -0.3872 | 9.19470 |
September | 485.00000 | 24.16527 | 25.61700 | -0.5077 | 12.70604 |
October | 502.00000 | 22.80270 | 21.85399 | -0.0674 | 8.08564 |
November | 489.00000 | 21.87650 | 24.07244 | -0.3157 | 9.19740 |
December | 497.00000 | 20.91870 | 17.58592 | -0.6288 | 15.78661 |
Annual Sum or Average | 5943.00000 | 22.65596 | 25.98959 | -0.4427 | 12.08134 |
Minimum of Months | 454.00000 | 20.91870 | 17.58592 | -0.8342 | 8.08564 |
Maximum of Months | 514.00000 | 24.28168 | 35.61976 | -0.0674 | 22.59515 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.72856 | 24.71062 | -0.6411 | 15.46757 |
February | 454.00000 | 20.80555 | 22.37715 | -0.6389 | 15.71451 |
March | 514.00000 | 21.58850 | 21.64575 | -0.4231 | 11.51074 |
April | 485.00000 | 21.89927 | 25.80014 | -0.3094 | 9.65991 |
May | 508.00000 | 23.64976 | 27.10414 | -0.7813 | 19.78882 |
June | 496.00000 | 24.29367 | 33.67758 | -0.4176 | 9.13612 |
July | 497.00000 | 24.38374 | 35.55829 | -0.3775 | 8.66379 |
August | 514.00000 | 24.21921 | 34.74086 | -0.4605 | 9.92623 |
September | 485.00000 | 23.94315 | 26.45276 | -0.6525 | 15.79202 |
October | 502.00000 | 22.29134 | 23.51435 | -0.2284 | 8.32182 |
November | 489.00000 | 21.28274 | 25.77599 | -0.4845 | 11.44246 |
December | 497.00000 | 20.46509 | 18.46800 | -0.7560 | 19.08044 |
Annual Sum or Average | 5943.00000 | 22.47709 | 26.69057 | -0.5135 | 12.85679 |
Minimum of Months | 454.00000 | 20.46509 | 18.46800 | -0.7813 | 8.32182 |
Maximum of Months | 514.00000 | 24.38374 | 35.55829 | -0.2284 | 19.78882 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.01191 | 23.04836 | -0.5535 | 13.51117 |
February | 385.00000 | 21.21811 | 20.63572 | -0.5128 | 14.44662 |
March | 433.00000 | 21.91146 | 19.73419 | -0.3107 | 11.30389 |
April | 410.00000 | 22.06699 | 24.40946 | -0.2303 | 9.96672 |
May | 430.00000 | 23.74651 | 26.20280 | -0.6808 | 17.73715 |
June | 418.00000 | 24.42075 | 32.97259 | -0.2873 | 8.19117 |
July | 422.00000 | 24.57603 | 34.83125 | -0.2370 | 8.36073 |
August | 433.00000 | 24.32805 | 34.04044 | -0.3321 | 9.03907 |
September | 410.00000 | 24.07065 | 25.54889 | -0.5316 | 13.96257 |
October | 427.00000 | 22.50597 | 21.78701 | -0.1476 | 9.33271 |
November | 417.00000 | 21.54443 | 24.00001 | -0.4021 | 10.74845 |
December | 422.00000 | 20.66195 | 17.04736 | -0.6916 | 17.55937 |
Annual Sum or Average | 5034.00000 | 22.68228 | 25.38882 | -0.4092 | 11.99982 |
Minimum of Months | 385.00000 | 20.66195 | 17.04736 | -0.6916 | 8.19117 |
Maximum of Months | 433.00000 | 24.57603 | 34.83125 | -0.1476 | 17.73715 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.50708 | 21.07020 | -0.1424 | 10.64258 |
February | 454.00000 | 22.37105 | 19.21212 | -0.1901 | 12.26223 |
March | 514.00000 | 22.47157 | 19.26616 | -0.1557 | 10.57752 |
April | 485.00000 | 22.29224 | 24.21746 | -0.1842 | 9.46909 |
May | 508.00000 | 23.70179 | 26.44790 | -0.7274 | 18.73730 |
June | 496.00000 | 24.26405 | 33.58216 | -0.4032 | 9.36227 |
July | 497.00000 | 24.39485 | 35.36440 | -0.3427 | 8.74230 |
August | 514.00000 | 24.30367 | 34.10513 | -0.3561 | 8.93824 |
September | 485.00000 | 24.22005 | 25.20813 | -0.4487 | 12.33286 |
October | 502.00000 | 23.12665 | 20.82721 | 0.04601 | 10.20599 |
November | 489.00000 | 22.85137 | 22.05478 | -0.0370 | 10.06743 |
December | 497.00000 | 22.08002 | 15.88616 | -0.3011 | 12.99298 |
Annual Sum or Average | 5943.00000 | 23.22284 | 24.82040 | -0.2713 | 11.19396 |
Minimum of Months | 454.00000 | 22.08002 | 15.88616 | -0.7274 | 8.74230 |
Maximum of Months | 514.00000 | 24.39485 | 35.36440 | 0.04601 | 18.73730 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.15228 | 22.97979 | -0.5152 | 13.46417 |
February | 454.00000 | 21.26282 | 20.71191 | -0.5003 | 14.16005 |
March | 514.00000 | 21.79348 | 20.14876 | -0.3345 | 11.39717 |
April | 485.00000 | 21.92855 | 24.74309 | -0.2631 | 9.98924 |
May | 508.00000 | 23.54784 | 26.72802 | -0.7437 | 20.15594 |
June | 496.00000 | 24.21978 | 33.75777 | -0.3564 | 9.48705 |
July | 497.00000 | 24.27538 | 35.75407 | -0.3472 | 9.06357 |
August | 514.00000 | 24.17377 | 34.73967 | -0.3915 | 9.75065 |
September | 485.00000 | 23.90650 | 26.14536 | -0.5829 | 15.63582 |
October | 502.00000 | 22.36106 | 22.17476 | -0.1666 | 9.25767 |
November | 489.00000 | 21.60847 | 24.05819 | -0.3793 | 10.59643 |
December | 497.00000 | 20.79722 | 17.14292 | -0.6571 | 17.18580 |
Annual Sum or Average | 5943.00000 | 22.59753 | 25.80183 | -0.4361 | 12.50304 |
Minimum of Months | 454.00000 | 20.79722 | 17.14292 | -0.7437 | 9.06357 |
Maximum of Months | 514.00000 | 24.27538 | 35.75407 | -0.1666 | 20.15594 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.748924E+09 | 0.190038E+09 | 24.67 | 0.748588E+09 | 336010.47 | 0.00 | 0.70 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 20719.24 | 20-JAN-14:00 | 20719.24 | 20-JAN-14:00 | 109.10 | 19-JAN-12:30 | 4910.28 | 20-JAN-14:00 | 0.00 |
February | 0.233075E+09 | 61679989.91 | 13.21 | 0.232223E+09 | 851871.95 | 0.00 | 0.43 | 26-FEB-12:42 | 0.00 | 01-FEB-00:10 | 12042.36 | 26-FEB-12:42 | 12042.36 | 26-FEB-12:42 | 238.35 | 18-FEB-16:07 | 3058.72 | 26-FEB-12:42 | 0.00 |
March | 0.282985E+10 | 0.678946E+09 | 73.50 | 0.282941E+10 | 440228.18 | 0.00 | 1.00 | 13-MAR-14:00 | 0.00 | 01-MAR-00:10 | 37190.69 | 14-MAR-13:00 | 37190.69 | 14-MAR-13:00 | 232.35 | 31-MAR-17:40 | 8127.78 | 14-MAR-13:00 | 0.00 |
April | 0.240328E+10 | 0.613332E+09 | 84.37 | 0.236590E+10 | 37385034.54 | 0.00 | 0.72 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 21604.31 | 20-APR-13:00 | 21604.31 | 20-APR-13:00 | 2802.16 | 28-APR-14:00 | 5085.30 | 20-APR-13:00 | 0.00 |
May | 0.129790E+11 | 0.311162E+10 | 216.86 | 0.126662E+11 | 0.312815E+09 | 0.00 | 1.00 | 10-MAY-12:30 | 0.00 | 01-MAY-00:10 | 47049.30 | 17-MAY-13:00 | 47049.30 | 17-MAY-13:00 | 3165.53 | 31-MAY-07:40 | 11671.65 | 17-MAY-13:00 | 0.00 |
June | 0.512927E+11 | 0.129521E+11 | 435.86 | 0.488705E+11 | 0.242226E+10 | 0.00 | 1.00 | 01-JUN-10:30 | 0.00 | 01-JUN-00:10 | 73325.59 | 26-JUN-16:00 | 73325.59 | 26-JUN-16:00 | 18544.52 | 21-JUN-06:03 | 24394.86 | 26-JUN-15:50 | 0.00 |
July | 0.521544E+11 | 0.129689E+11 | 443.00 | 0.480695E+11 | 0.408492E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 71182.60 | 17-JUL-12:07 | 71182.60 | 17-JUL-12:07 | 30365.83 | 31-JUL-15:40 | 21687.29 | 17-JUL-12:07 | 0.00 |
August | 0.515264E+11 | 0.127583E+11 | 436.55 | 0.488715E+11 | 0.265496E+10 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 68801.95 | 16-AUG-16:00 | 68801.95 | 16-AUG-16:00 | 27482.95 | 04-AUG-06:03 | 21625.24 | 16-AUG-16:00 | 0.00 |
September | 0.355121E+11 | 0.851604E+10 | 362.31 | 0.350354E+11 | 0.476713E+09 | 0.00 | 1.00 | 01-SEP-10:10 | 0.00 | 01-SEP-00:10 | 62444.92 | 12-SEP-16:00 | 62444.92 | 12-SEP-16:00 | 8855.98 | 01-SEP-14:00 | 16427.06 | 12-SEP-16:00 | 0.00 |
October | 0.619945E+10 | 0.147224E+10 | 112.24 | 0.618312E+10 | 16328225.68 | 0.00 | 1.00 | 10-OCT-10:20 | 0.00 | 01-OCT-00:10 | 51650.92 | 11-OCT-15:20 | 51650.92 | 11-OCT-15:20 | 1016.78 | 01-OCT-11:32 | 11731.04 | 11-OCT-14:00 | 0.00 |
November | 0.184056E+10 | 0.447611E+09 | 40.86 | 0.184052E+10 | 37482.92 | 0.00 | 0.93 | 07-NOV-15:00 | 0.00 | 01-NOV-00:10 | 29608.24 | 07-NOV-15:00 | 29608.24 | 07-NOV-15:00 | 34.38 | 09-NOV-08:45 | 6566.50 | 07-NOV-15:00 | 0.00 |
December | 0.824985E+09 | 0.211736E+09 | 32.00 | 0.824634E+09 | 350815.95 | 0.00 | 0.65 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 19207.01 | 01-DEC-14:00 | 19207.01 | 01-DEC-14:00 | 122.88 | 03-DEC-15:47 | 4605.64 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.218545E+12 | 0.539825E+11 | 2275.43 | 0.208537E+12 | 0.100074E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.233075E+09 | 61679989.91 | 13.21 | 0.232223E+09 | 37482.92 | 0.00 | 0.43 | 0.00 | 12042.36 | 12042.36 | 34.38 | 3058.72 | 0.00 | ||||||
Maximum of Months | 0.521544E+11 | 0.129689E+11 | 443.00 | 0.488715E+11 | 0.408492E+10 | 0.00 | 1.00 | 0.00 | 73325.59 | 73325.59 | 30365.83 | 24394.86 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.935235E+09 | 0.232802E+09 | 28.50 | 0.935195E+09 | 39677.85 | 0.00 | 0.76 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 20510.58 | 20-JAN-14:00 | 20510.58 | 20-JAN-14:00 | 35.50 | 19-JAN-11:50 | 4774.23 | 20-JAN-14:00 | 0.00 |
February | 0.355406E+09 | 92156602.05 | 17.83 | 0.355212E+09 | 194780.54 | 0.00 | 0.63 | 18-FEB-13:20 | 0.00 | 01-FEB-00:10 | 16326.76 | 18-FEB-13:20 | 16326.76 | 18-FEB-13:20 | 52.12 | 18-FEB-17:10 | 3940.92 | 18-FEB-13:20 | 0.00 |
March | 0.291280E+10 | 0.695785E+09 | 77.83 | 0.291262E+10 | 181622.79 | 0.00 | 1.00 | 13-MAR-13:50 | 0.00 | 01-MAR-00:10 | 34354.71 | 13-MAR-16:00 | 34354.71 | 13-MAR-16:00 | 138.00 | 31-MAR-17:50 | 7469.56 | 13-MAR-16:00 | 0.00 |
April | 0.230555E+10 | 0.584735E+09 | 85.40 | 0.227458E+10 | 30972199.93 | 0.00 | 0.79 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 21381.83 | 20-APR-13:00 | 21381.83 | 20-APR-13:00 | 2537.21 | 28-APR-14:00 | 4940.34 | 20-APR-13:00 | 0.00 |
May | 0.124460E+11 | 0.297209E+10 | 229.14 | 0.121552E+11 | 0.290790E+09 | 0.00 | 1.00 | 04-MAY-15:00 | 0.00 | 01-MAY-00:10 | 44974.73 | 31-MAY-16:00 | 44974.73 | 31-MAY-16:00 | 2787.22 | 31-MAY-07:50 | 10944.54 | 17-MAY-13:30 | 0.00 |
June | 0.476538E+11 | 0.120167E+11 | 434.72 | 0.455080E+11 | 0.214582E+10 | 0.00 | 1.00 | 01-JUN-10:10 | 0.00 | 01-JUN-00:10 | 70796.77 | 26-JUN-15:20 | 70796.77 | 26-JUN-15:20 | 16383.50 | 18-JUN-10:12 | 23892.06 | 26-JUN-15:00 | 0.00 |
July | 0.483237E+11 | 0.120152E+11 | 440.26 | 0.447036E+11 | 0.362011E+10 | 0.00 | 1.00 | 01-JUL-06:03 | 0.00 | 01-JUL-00:10 | 68075.31 | 31-JUL-14:40 | 66580.04 | 17-JUL-10:20 | 30115.71 | 31-JUL-15:50 | 19798.19 | 17-JUL-13:00 | 0.00 |
August | 0.459706E+11 | 0.114032E+11 | 430.01 | 0.437014E+11 | 0.226926E+10 | 0.00 | 1.00 | 01-AUG-12:10 | 0.00 | 01-AUG-00:10 | 66784.82 | 16-AUG-15:10 | 66784.82 | 16-AUG-15:10 | 16770.40 | 21-AUG-16:00 | 20448.30 | 16-AUG-15:10 | 0.00 |
September | 0.303013E+11 | 0.729230E+10 | 356.83 | 0.299007E+11 | 0.400648E+09 | 0.00 | 1.00 | 01-SEP-10:00 | 0.00 | 01-SEP-00:10 | 59148.85 | 12-SEP-15:50 | 59148.85 | 12-SEP-15:50 | 8434.23 | 01-SEP-14:00 | 15430.00 | 12-SEP-15:50 | 0.00 |
October | 0.553179E+10 | 0.131657E+10 | 112.76 | 0.552037E+10 | 11415296.88 | 0.00 | 1.00 | 10-OCT-10:30 | 0.00 | 01-OCT-00:10 | 46957.58 | 11-OCT-15:00 | 46957.58 | 11-OCT-15:00 | 727.67 | 01-OCT-10:13 | 10773.72 | 11-OCT-14:40 | 0.00 |
November | 0.168951E+10 | 0.413837E+09 | 43.83 | 0.168912E+10 | 388111.95 | 0.00 | 0.93 | 07-NOV-15:00 | 0.00 | 01-NOV-00:10 | 26263.60 | 07-NOV-15:00 | 26263.60 | 07-NOV-15:00 | 165.74 | 09-NOV-08:55 | 5827.57 | 07-NOV-15:00 | 0.00 |
December | 0.927467E+09 | 0.234321E+09 | 32.50 | 0.927415E+09 | 51431.69 | 0.00 | 0.75 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 20050.50 | 01-DEC-14:00 | 20050.50 | 01-DEC-14:00 | 44.39 | 03-DEC-15:55 | 4685.52 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.199353E+12 | 0.492697E+11 | 2289.62 | 0.190583E+12 | 0.876987E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.355406E+09 | 92156602.05 | 17.83 | 0.355212E+09 | 39677.85 | 0.00 | 0.63 | 0.00 | 16326.76 | 16326.76 | 35.50 | 3940.92 | 0.00 | ||||||
Maximum of Months | 0.483237E+11 | 0.120167E+11 | 440.26 | 0.455080E+11 | 0.362011E+10 | 0.00 | 1.00 | 0.00 | 70796.77 | 70796.77 | 30115.71 | 23892.06 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.795040E+09 | 0.201974E+09 | 25.17 | 0.795025E+09 | 14522.30 | 0.00 | 0.70 | 20-JAN-14:00 | 0.00 | 01-JAN-00:10 | 21979.22 | 20-JAN-14:00 | 21979.22 | 20-JAN-14:00 | 22.07 | 19-JAN-12:02 | 5199.63 | 20-JAN-14:00 | 0.00 |
February | 0.279097E+09 | 73303852.17 | 13.83 | 0.278297E+09 | 800098.68 | 0.00 | 0.50 | 18-FEB-13:30 | 0.00 | 01-FEB-00:10 | 14870.03 | 18-FEB-13:30 | 14870.03 | 18-FEB-13:30 | 194.24 | 18-FEB-16:03 | 3711.53 | 18-FEB-13:30 | 0.00 |
March | 0.282668E+10 | 0.683527E+09 | 73.17 | 0.282629E+10 | 385716.78 | 0.00 | 1.00 | 13-MAR-14:30 | 0.00 | 01-MAR-00:10 | 36139.09 | 13-MAR-15:50 | 36139.09 | 13-MAR-15:50 | 179.79 | 31-MAR-17:50 | 7859.14 | 13-MAR-15:50 | 0.00 |
April | 0.244452E+10 | 0.624027E+09 | 83.57 | 0.240386E+10 | 40656534.94 | 0.00 | 0.75 | 20-APR-13:00 | 0.00 | 01-APR-00:10 | 23687.93 | 20-APR-13:00 | 23687.93 | 20-APR-13:00 | 2808.07 | 28-APR-14:00 | 5534.43 | 20-APR-13:00 | 0.00 |
May | 0.132961E+11 | 0.320701E+10 | 228.44 | 0.128849E+11 | 0.411224E+09 | 0.00 | 1.00 | 04-MAY-14:50 | 0.00 | 01-MAY-00:10 | 54489.05 | 31-MAY-15:20 | 54489.05 | 31-MAY-15:20 | 3364.22 | 30-MAY-17:10 | 13150.86 | 31-MAY-15:20 | 0.00 |
June | 0.524128E+11 | 0.133375E+11 | 432.92 | 0.500732E+11 | 0.233957E+10 | 0.00 | 1.00 | 01-JUN-10:40 | 0.00 | 01-JUN-00:10 | 83412.49 | 26-JUN-15:10 | 83412.49 | 26-JUN-15:10 | 16616.88 | 22-JUN-13:20 | 28220.75 | 26-JUN-15:00 | 0.00 |
July | 0.525365E+11 | 0.131953E+11 | 440.11 | 0.487429E+11 | 0.379366E+10 | 0.00 | 1.00 | 01-JUL-08:50 | 0.00 | 01-JUL-00:10 | 76175.71 | 17-JUL-14:00 | 76175.71 | 17-JUL-14:00 | 31141.72 | 31-JUL-15:40 | 22761.27 | 17-JUL-13:30 | 0.00 |
August | 0.499443E+11 | 0.125199E+11 | 426.30 | 0.475631E+11 | 0.238117E+10 | 0.00 | 1.00 | 02-AUG-09:50 | 0.00 | 01-AUG-00:10 | 80142.82 | 16-AUG-15:10 | 80142.82 | 16-AUG-15:10 | 16667.52 | 21-AUG-16:00 | 24536.63 | 16-AUG-15:10 | 0.00 |
September | 0.313453E+11 | 0.763904E+10 | 354.77 | 0.308239E+11 | 0.521360E+09 | 0.00 | 1.00 | 01-SEP-10:50 | 0.00 | 01-SEP-00:10 | 67137.58 | 12-SEP-15:50 | 67137.58 | 12-SEP-15:50 | 7834.48 | 01-SEP-14:00 | 17516.25 | 12-SEP-15:50 | 0.00 |
October | 0.517102E+10 | 0.125349E+10 | 106.92 | 0.515145E+10 | 19561679.93 | 0.00 | 1.00 | 10-OCT-12:30 | 0.00 | 01-OCT-00:10 | 52467.02 | 11-OCT-15:00 | 52467.02 | 11-OCT-15:00 | 927.72 | 01-OCT-11:22 | 12073.61 | 11-OCT-14:40 | 0.00 |
November | 0.150073E+10 | 0.375641E+09 | 40.25 | 0.149900E+10 | 1728501.35 | 0.00 | 0.81 | 07-NOV-14:20 | 0.00 | 01-NOV-00:10 | 25997.14 | 07-NOV-14:20 | 25997.14 | 07-NOV-14:20 | 375.36 | 09-NOV-09:20 | 5973.93 | 07-NOV-14:20 | 0.00 |
December | 0.835158E+09 | 0.215123E+09 | 31.17 | 0.834880E+09 | 277577.93 | 0.00 | 0.63 | 01-DEC-14:00 | 0.00 | 01-DEC-00:10 | 19347.41 | 01-DEC-14:00 | 19347.41 | 01-DEC-14:00 | 97.36 | 03-DEC-15:40 | 4667.21 | 01-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.213387E+12 | 0.533258E+11 | 2256.62 | 0.203877E+12 | 0.951040E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.279097E+09 | 73303852.17 | 13.83 | 0.278297E+09 | 14522.30 | 0.00 | 0.50 | 0.00 | 14870.03 | 14870.03 | 22.07 | 3711.53 | 0.00 | ||||||
Maximum of Months | 0.525365E+11 | 0.133375E+11 | 440.11 | 0.500732E+11 | 0.379366E+10 | 0.00 | 1.00 | 0.00 | 83412.49 | 83412.49 | 31141.72 | 28220.75 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 351.98 | 0.00 | 351.98 | 81.99 | 1583.39 | 0.00 | 0.00 | 0.00 |
February | 442.39 | 0.00 | 442.39 | 99.43 | 1616.57 | 0.00 | 0.00 | 0.00 |
March | 601.95 | 0.00 | 601.95 | 297.20 | 1223.40 | 0.00 | 0.00 | 0.00 |
April | 755.96 | 4.19 | 751.77 | 443.42 | 1040.44 | 0.00 | 0.00 | 0.00 |
May | 1032.69 | 34.14 | 998.56 | 957.68 | 639.91 | 0.00 | 0.00 | 0.00 |
June | 1132.42 | 125.55 | 1006.87 | 1508.78 | 365.15 | 0.00 | 0.00 | 0.00 |
July | 1070.96 | 69.33 | 1001.64 | 1442.84 | 345.88 | 0.00 | 0.00 | 0.00 |
August | 852.40 | 20.16 | 832.24 | 1099.02 | 394.24 | 0.00 | 0.00 | 0.00 |
September | 716.02 | 0.17 | 715.85 | 820.26 | 599.44 | 0.00 | 0.00 | 0.00 |
October | 512.84 | 0.00 | 512.84 | 302.48 | 1212.35 | 0.00 | 0.00 | 0.00 |
November | 389.31 | 0.00 | 389.31 | 128.50 | 1433.82 | 0.00 | 0.00 | 0.00 |
December | 329.32 | 0.00 | 329.32 | 68.62 | 1794.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 683.60 | 21.18 | 662.43 | 607.01 | 1017.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.32 | 0.00 | 329.32 | 68.62 | 345.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1132.42 | 125.55 | 1006.87 | 1508.78 | 1794.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.76 | 450.28 | 284.48 | 676.84 | 989.13 | 0.00 | 0.00 | 0.00 |
February | 976.05 | 616.17 | 359.87 | 937.69 | 1030.93 | 0.00 | 0.00 | 0.00 |
March | 1178.06 | 687.15 | 490.91 | 1212.88 | 784.96 | 0.00 | 0.00 | 0.00 |
April | 1208.16 | 588.52 | 619.65 | 1218.82 | 676.47 | 0.00 | 0.00 | 0.00 |
May | 1412.33 | 589.93 | 822.39 | 1614.31 | 430.04 | 0.00 | 0.00 | 0.00 |
June | 1723.18 | 904.62 | 818.56 | 2313.81 | 243.72 | 0.00 | 0.00 | 0.00 |
July | 1566.51 | 745.93 | 820.58 | 2121.25 | 230.77 | 0.00 | 0.00 | 0.00 |
August | 1580.04 | 870.23 | 709.81 | 2127.12 | 262.78 | 0.00 | 0.00 | 0.00 |
September | 1314.67 | 714.17 | 600.51 | 1683.50 | 383.52 | 0.00 | 0.00 | 0.00 |
October | 952.09 | 521.69 | 430.40 | 1013.55 | 790.64 | 0.00 | 0.00 | 0.00 |
November | 741.08 | 418.42 | 322.66 | 716.34 | 921.70 | 0.00 | 0.00 | 0.00 |
December | 641.57 | 369.59 | 271.98 | 564.90 | 1132.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1169.78 | 622.75 | 547.03 | 1352.02 | 654.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 641.57 | 369.59 | 271.98 | 564.90 | 230.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1723.18 | 904.62 | 822.39 | 2313.81 | 1132.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3373.25 | 2774.86 | 598.39 | 3896.21 | 1449.10 | 0.00 | 0.00 | 0.00 |
February | 3235.57 | 2579.60 | 655.97 | 3697.24 | 1518.27 | 0.00 | 0.00 | 0.00 |
March | 2385.51 | 1569.53 | 815.98 | 2762.82 | 1205.46 | 0.00 | 0.00 | 0.00 |
April | 1545.04 | 621.26 | 923.77 | 1640.36 | 1073.36 | 0.00 | 0.00 | 0.00 |
May | 1415.86 | 259.52 | 1156.34 | 1634.07 | 698.54 | 0.00 | 0.00 | 0.00 |
June | 1305.38 | 238.58 | 1066.79 | 1883.47 | 396.99 | 0.00 | 0.00 | 0.00 |
July | 1358.86 | 243.33 | 1115.53 | 1964.20 | 368.39 | 0.00 | 0.00 | 0.00 |
August | 1730.11 | 723.25 | 1006.86 | 2514.30 | 414.80 | 0.00 | 0.00 | 0.00 |
September | 2225.95 | 1242.07 | 983.89 | 3037.32 | 616.89 | 0.00 | 0.00 | 0.00 |
October | 2661.59 | 1888.45 | 773.13 | 3243.78 | 1210.81 | 0.00 | 0.00 | 0.00 |
November | 3242.77 | 2584.96 | 657.81 | 3821.38 | 1381.74 | 0.00 | 0.00 | 0.00 |
December | 3100.93 | 2509.85 | 591.08 | 3508.29 | 1629.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2293.09 | 1429.77 | 863.32 | 2795.16 | 994.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1305.38 | 238.58 | 591.08 | 1634.07 | 368.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3373.25 | 2774.86 | 1156.34 | 3896.21 | 1629.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 781.62 | 495.28 | 286.34 | 766.35 | 1016.25 | 0.00 | 0.00 | 0.00 |
February | 942.52 | 584.08 | 358.44 | 909.85 | 1046.83 | 0.00 | 0.00 | 0.00 |
March | 1103.63 | 608.90 | 494.74 | 1130.35 | 801.14 | 0.00 | 0.00 | 0.00 |
April | 1039.12 | 439.95 | 599.18 | 1020.67 | 694.53 | 0.00 | 0.00 | 0.00 |
May | 1270.08 | 447.75 | 822.33 | 1459.10 | 455.05 | 0.00 | 0.00 | 0.00 |
June | 1553.38 | 747.39 | 805.99 | 2117.24 | 273.09 | 0.00 | 0.00 | 0.00 |
July | 1265.64 | 463.58 | 802.06 | 1731.23 | 249.21 | 0.00 | 0.00 | 0.00 |
August | 1320.97 | 652.57 | 668.39 | 1782.36 | 277.89 | 0.00 | 0.00 | 0.00 |
September | 1171.30 | 561.72 | 609.59 | 1515.88 | 409.22 | 0.00 | 0.00 | 0.00 |
October | 985.37 | 563.21 | 422.16 | 1086.06 | 805.86 | 0.00 | 0.00 | 0.00 |
November | 808.55 | 490.89 | 317.66 | 813.12 | 935.17 | 0.00 | 0.00 | 0.00 |
December | 653.09 | 385.80 | 267.29 | 586.68 | 1138.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1074.94 | 536.12 | 538.83 | 1244.63 | 673.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 653.09 | 385.80 | 267.29 | 586.68 | 249.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1553.38 | 747.39 | 822.33 | 2117.24 | 1138.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.32 | 0.00 | 117.32 | 27.08 | 545.84 | 0.00 | 0.00 | 0.00 |
February | 147.46 | 0.00 | 147.46 | 34.84 | 550.10 | 0.00 | 0.00 | 0.00 |
March | 200.64 | 0.00 | 200.64 | 105.32 | 414.06 | 0.00 | 0.00 | 0.00 |
April | 251.98 | 1.40 | 250.58 | 154.66 | 357.26 | 0.00 | 0.00 | 0.00 |
May | 344.21 | 11.38 | 332.84 | 328.77 | 211.47 | 0.00 | 0.00 | 0.00 |
June | 377.46 | 41.85 | 335.61 | 512.30 | 118.86 | 0.00 | 0.00 | 0.00 |
July | 356.97 | 23.11 | 333.86 | 489.90 | 111.96 | 0.00 | 0.00 | 0.00 |
August | 284.12 | 6.72 | 277.40 | 370.86 | 131.97 | 0.00 | 0.00 | 0.00 |
September | 238.66 | 0.06 | 238.61 | 272.73 | 210.74 | 0.00 | 0.00 | 0.00 |
October | 170.94 | 0.00 | 170.94 | 96.76 | 435.02 | 0.00 | 0.00 | 0.00 |
November | 129.76 | 0.00 | 129.76 | 39.33 | 510.85 | 0.00 | 0.00 | 0.00 |
December | 109.77 | 0.00 | 109.77 | 21.61 | 626.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.86 | 7.06 | 220.80 | 205.47 | 351.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.77 | 0.00 | 109.77 | 21.61 | 111.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 377.46 | 41.85 | 335.61 | 512.30 | 626.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.33 | 0.00 | 117.33 | 27.08 | 545.88 | 0.00 | 0.00 | 0.00 |
February | 147.47 | 0.00 | 147.47 | 34.84 | 550.14 | 0.00 | 0.00 | 0.00 |
March | 200.65 | 0.00 | 200.65 | 105.33 | 414.09 | 0.00 | 0.00 | 0.00 |
April | 251.99 | 1.40 | 250.59 | 154.67 | 357.28 | 0.00 | 0.00 | 0.00 |
May | 344.24 | 11.38 | 332.86 | 328.79 | 211.49 | 0.00 | 0.00 | 0.00 |
June | 377.48 | 41.85 | 335.63 | 512.33 | 118.87 | 0.00 | 0.00 | 0.00 |
July | 356.99 | 23.11 | 333.88 | 489.93 | 111.97 | 0.00 | 0.00 | 0.00 |
August | 284.14 | 6.72 | 277.42 | 370.88 | 131.98 | 0.00 | 0.00 | 0.00 |
September | 238.68 | 0.06 | 238.62 | 272.75 | 210.75 | 0.00 | 0.00 | 0.00 |
October | 170.95 | 0.00 | 170.95 | 96.77 | 435.05 | 0.00 | 0.00 | 0.00 |
November | 129.77 | 0.00 | 129.77 | 39.34 | 510.88 | 0.00 | 0.00 | 0.00 |
December | 109.77 | 0.00 | 109.77 | 21.61 | 626.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.87 | 7.06 | 220.81 | 205.48 | 351.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.77 | 0.00 | 109.77 | 21.61 | 111.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 377.48 | 41.85 | 335.63 | 512.33 | 626.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.33 | 0.00 | 117.33 | 27.08 | 545.88 | 0.00 | 0.00 | 0.00 |
February | 147.47 | 0.00 | 147.47 | 34.84 | 550.14 | 0.00 | 0.00 | 0.00 |
March | 200.65 | 0.00 | 200.65 | 105.33 | 414.09 | 0.00 | 0.00 | 0.00 |
April | 251.99 | 1.40 | 250.59 | 154.67 | 357.28 | 0.00 | 0.00 | 0.00 |
May | 344.24 | 11.38 | 332.86 | 328.79 | 211.49 | 0.00 | 0.00 | 0.00 |
June | 377.48 | 41.85 | 335.63 | 512.33 | 118.87 | 0.00 | 0.00 | 0.00 |
July | 356.99 | 23.11 | 333.88 | 489.93 | 111.97 | 0.00 | 0.00 | 0.00 |
August | 284.14 | 6.72 | 277.42 | 370.88 | 131.98 | 0.00 | 0.00 | 0.00 |
September | 238.68 | 0.06 | 238.62 | 272.75 | 210.75 | 0.00 | 0.00 | 0.00 |
October | 170.95 | 0.00 | 170.95 | 96.77 | 435.05 | 0.00 | 0.00 | 0.00 |
November | 129.77 | 0.00 | 129.77 | 39.34 | 510.88 | 0.00 | 0.00 | 0.00 |
December | 109.77 | 0.00 | 109.77 | 21.61 | 626.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 227.87 | 7.06 | 220.81 | 205.48 | 351.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.77 | 0.00 | 109.77 | 21.61 | 111.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 377.48 | 41.85 | 335.63 | 512.33 | 626.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 706.81 | 433.15 | 273.66 | 648.14 | 998.77 | 0.00 | 0.00 | 0.00 |
February | 938.91 | 592.73 | 346.18 | 906.14 | 1029.03 | 0.00 | 0.00 | 0.00 |
March | 1133.24 | 661.01 | 472.24 | 1177.01 | 787.31 | 0.00 | 0.00 | 0.00 |
April | 1162.20 | 566.13 | 596.08 | 1181.88 | 691.06 | 0.00 | 0.00 | 0.00 |
May | 1358.60 | 567.49 | 791.11 | 1565.82 | 424.23 | 0.00 | 0.00 | 0.00 |
June | 1657.63 | 870.21 | 787.42 | 2241.40 | 239.72 | 0.00 | 0.00 | 0.00 |
July | 1506.92 | 717.55 | 789.36 | 2054.94 | 226.64 | 0.00 | 0.00 | 0.00 |
August | 1519.93 | 837.12 | 682.81 | 2054.15 | 267.20 | 0.00 | 0.00 | 0.00 |
September | 1264.66 | 687.00 | 577.66 | 1617.75 | 402.41 | 0.00 | 0.00 | 0.00 |
October | 915.87 | 501.84 | 414.03 | 967.97 | 835.21 | 0.00 | 0.00 | 0.00 |
November | 712.88 | 402.50 | 310.38 | 678.28 | 962.11 | 0.00 | 0.00 | 0.00 |
December | 617.17 | 355.53 | 261.64 | 537.32 | 1153.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1125.27 | 599.06 | 526.22 | 1304.43 | 666.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 617.17 | 355.53 | 261.64 | 537.32 | 226.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1657.63 | 870.21 | 791.11 | 2241.40 | 1153.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.95 | 17.13 | 10.82 | 25.63 | 39.49 | 0.00 | 0.00 | 0.00 |
February | 37.12 | 23.44 | 13.69 | 35.83 | 40.69 | 0.00 | 0.00 | 0.00 |
March | 44.81 | 26.14 | 18.67 | 46.54 | 31.13 | 0.00 | 0.00 | 0.00 |
April | 45.95 | 22.38 | 23.57 | 46.73 | 27.32 | 0.00 | 0.00 | 0.00 |
May | 53.72 | 22.44 | 31.28 | 61.91 | 16.77 | 0.00 | 0.00 | 0.00 |
June | 65.54 | 34.41 | 31.13 | 88.62 | 9.48 | 0.00 | 0.00 | 0.00 |
July | 59.58 | 28.37 | 31.21 | 81.25 | 8.96 | 0.00 | 0.00 | 0.00 |
August | 60.10 | 33.10 | 27.00 | 81.22 | 10.56 | 0.00 | 0.00 | 0.00 |
September | 50.00 | 27.16 | 22.84 | 63.96 | 15.91 | 0.00 | 0.00 | 0.00 |
October | 36.21 | 19.84 | 16.37 | 38.27 | 33.02 | 0.00 | 0.00 | 0.00 |
November | 28.19 | 15.91 | 12.27 | 26.82 | 38.04 | 0.00 | 0.00 | 0.00 |
December | 24.40 | 14.06 | 10.34 | 21.25 | 45.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44.49 | 23.69 | 20.81 | 51.58 | 26.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.40 | 14.06 | 10.34 | 21.25 | 8.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.54 | 34.41 | 31.28 | 88.62 | 45.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1124.45 | 924.98 | 199.47 | 1303.94 | 520.01 | 0.00 | 0.00 | 0.00 |
February | 1078.56 | 859.89 | 218.66 | 1245.10 | 533.28 | 0.00 | 0.00 | 0.00 |
March | 795.20 | 523.19 | 272.00 | 933.64 | 418.52 | 0.00 | 0.00 | 0.00 |
April | 515.03 | 207.09 | 307.93 | 558.14 | 373.20 | 0.00 | 0.00 | 0.00 |
May | 471.97 | 86.51 | 385.46 | 558.05 | 231.23 | 0.00 | 0.00 | 0.00 |
June | 435.14 | 79.53 | 355.61 | 636.89 | 130.86 | 0.00 | 0.00 | 0.00 |
July | 452.97 | 81.11 | 371.85 | 663.31 | 121.55 | 0.00 | 0.00 | 0.00 |
August | 576.72 | 241.09 | 335.63 | 843.34 | 144.21 | 0.00 | 0.00 | 0.00 |
September | 742.01 | 414.04 | 327.97 | 1014.21 | 224.72 | 0.00 | 0.00 | 0.00 |
October | 887.22 | 629.50 | 257.72 | 1082.48 | 444.26 | 0.00 | 0.00 | 0.00 |
November | 1080.96 | 861.68 | 219.28 | 1277.39 | 504.39 | 0.00 | 0.00 | 0.00 |
December | 1033.68 | 836.64 | 197.03 | 1175.47 | 581.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 764.39 | 476.61 | 287.78 | 939.26 | 351.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.14 | 79.53 | 197.03 | 558.05 | 121.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1124.45 | 924.98 | 385.46 | 1303.94 | 581.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1124.45 | 924.98 | 199.47 | 1303.94 | 520.01 | 0.00 | 0.00 | 0.00 |
February | 1078.56 | 859.89 | 218.66 | 1245.10 | 533.28 | 0.00 | 0.00 | 0.00 |
March | 795.20 | 523.19 | 272.00 | 933.64 | 418.52 | 0.00 | 0.00 | 0.00 |
April | 515.03 | 207.09 | 307.93 | 558.14 | 373.20 | 0.00 | 0.00 | 0.00 |
May | 471.97 | 86.51 | 385.46 | 558.05 | 231.23 | 0.00 | 0.00 | 0.00 |
June | 435.14 | 79.53 | 355.61 | 636.89 | 130.86 | 0.00 | 0.00 | 0.00 |
July | 452.97 | 81.11 | 371.85 | 663.31 | 121.55 | 0.00 | 0.00 | 0.00 |
August | 576.72 | 241.09 | 335.63 | 843.34 | 144.21 | 0.00 | 0.00 | 0.00 |
September | 742.01 | 414.04 | 327.97 | 1014.21 | 224.72 | 0.00 | 0.00 | 0.00 |
October | 887.22 | 629.50 | 257.72 | 1082.48 | 444.26 | 0.00 | 0.00 | 0.00 |
November | 1080.96 | 861.68 | 219.28 | 1277.39 | 504.39 | 0.00 | 0.00 | 0.00 |
December | 1033.68 | 836.64 | 197.03 | 1175.47 | 581.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 764.39 | 476.61 | 287.78 | 939.26 | 351.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.14 | 79.53 | 197.03 | 558.05 | 121.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1124.45 | 924.98 | 385.46 | 1303.94 | 581.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1124.38 | 924.92 | 199.46 | 1303.86 | 519.98 | 0.00 | 0.00 | 0.00 |
February | 1078.49 | 859.84 | 218.65 | 1245.02 | 533.24 | 0.00 | 0.00 | 0.00 |
March | 795.15 | 523.16 | 271.98 | 933.58 | 418.49 | 0.00 | 0.00 | 0.00 |
April | 515.00 | 207.08 | 307.91 | 558.10 | 373.17 | 0.00 | 0.00 | 0.00 |
May | 471.94 | 86.50 | 385.43 | 558.02 | 231.21 | 0.00 | 0.00 | 0.00 |
June | 435.11 | 79.53 | 355.58 | 636.85 | 130.85 | 0.00 | 0.00 | 0.00 |
July | 452.94 | 81.11 | 371.83 | 663.27 | 121.54 | 0.00 | 0.00 | 0.00 |
August | 576.68 | 241.08 | 335.61 | 843.28 | 144.20 | 0.00 | 0.00 | 0.00 |
September | 741.96 | 414.01 | 327.95 | 1014.15 | 224.71 | 0.00 | 0.00 | 0.00 |
October | 887.17 | 629.47 | 257.70 | 1082.41 | 444.23 | 0.00 | 0.00 | 0.00 |
November | 1080.89 | 861.63 | 219.26 | 1277.31 | 504.35 | 0.00 | 0.00 | 0.00 |
December | 1033.61 | 836.59 | 197.02 | 1175.39 | 581.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 764.34 | 476.58 | 287.76 | 939.20 | 351.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 435.11 | 79.53 | 197.02 | 558.02 | 121.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1124.38 | 924.92 | 385.43 | 1303.86 | 581.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 751.89 | 476.43 | 275.45 | 739.05 | 1028.27 | 0.00 | 0.00 | 0.00 |
February | 906.67 | 561.86 | 344.80 | 882.92 | 1046.67 | 0.00 | 0.00 | 0.00 |
March | 1061.65 | 585.73 | 475.92 | 1099.17 | 801.36 | 0.00 | 0.00 | 0.00 |
April | 999.59 | 423.21 | 576.38 | 991.48 | 705.19 | 0.00 | 0.00 | 0.00 |
May | 1221.76 | 430.71 | 791.05 | 1417.16 | 447.97 | 0.00 | 0.00 | 0.00 |
June | 1494.29 | 718.96 | 775.33 | 2049.07 | 268.92 | 0.00 | 0.00 | 0.00 |
July | 1217.49 | 445.94 | 771.55 | 1678.05 | 242.21 | 0.00 | 0.00 | 0.00 |
August | 1270.71 | 627.75 | 642.97 | 1719.96 | 279.91 | 0.00 | 0.00 | 0.00 |
September | 1126.74 | 540.35 | 586.40 | 1453.50 | 428.92 | 0.00 | 0.00 | 0.00 |
October | 947.89 | 541.79 | 406.10 | 1035.01 | 851.18 | 0.00 | 0.00 | 0.00 |
November | 777.79 | 472.21 | 305.58 | 774.78 | 976.31 | 0.00 | 0.00 | 0.00 |
December | 628.24 | 371.12 | 257.12 | 562.60 | 1161.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1034.05 | 515.72 | 518.33 | 1201.55 | 684.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 628.24 | 371.12 | 257.12 | 562.60 | 242.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1494.29 | 718.96 | 791.05 | 2049.07 | 1161.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 29.73 | 18.84 | 10.89 | 29.22 | 40.66 | 0.00 | 0.00 | 0.00 |
February | 35.85 | 22.22 | 13.63 | 34.91 | 41.38 | 0.00 | 0.00 | 0.00 |
March | 41.98 | 23.16 | 18.82 | 43.46 | 31.69 | 0.00 | 0.00 | 0.00 |
April | 39.52 | 16.73 | 22.79 | 39.20 | 27.88 | 0.00 | 0.00 | 0.00 |
May | 48.31 | 17.03 | 31.28 | 56.03 | 17.71 | 0.00 | 0.00 | 0.00 |
June | 59.08 | 28.43 | 30.66 | 81.02 | 10.63 | 0.00 | 0.00 | 0.00 |
July | 48.14 | 17.63 | 30.51 | 66.35 | 9.58 | 0.00 | 0.00 | 0.00 |
August | 50.24 | 24.82 | 25.42 | 68.01 | 11.07 | 0.00 | 0.00 | 0.00 |
September | 44.55 | 21.36 | 23.19 | 57.47 | 16.96 | 0.00 | 0.00 | 0.00 |
October | 37.48 | 21.42 | 16.06 | 40.92 | 33.66 | 0.00 | 0.00 | 0.00 |
November | 30.75 | 18.67 | 12.08 | 30.63 | 38.60 | 0.00 | 0.00 | 0.00 |
December | 24.84 | 14.67 | 10.17 | 22.24 | 45.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.89 | 20.39 | 20.49 | 47.51 | 27.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 24.84 | 14.67 | 10.17 | 22.24 | 9.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 59.08 | 28.43 | 31.28 | 81.02 | 45.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 351.98 | 0.00 | 351.98 | 73.12 | 1678.10 | 0.00 | 0.00 | 0.00 |
February | 442.39 | 0.00 | 442.39 | 91.08 | 1698.94 | 0.00 | 0.00 | 0.00 |
March | 601.95 | 0.00 | 601.95 | 286.99 | 1295.62 | 0.00 | 0.00 | 0.00 |
April | 755.96 | 4.19 | 751.77 | 431.40 | 1117.18 | 0.00 | 0.00 | 0.00 |
May | 1032.69 | 34.14 | 998.56 | 943.52 | 671.00 | 0.00 | 0.00 | 0.00 |
June | 1132.42 | 125.55 | 1006.87 | 1510.93 | 374.66 | 0.00 | 0.00 | 0.00 |
July | 1070.96 | 69.33 | 1001.64 | 1446.03 | 354.44 | 0.00 | 0.00 | 0.00 |
August | 852.40 | 20.16 | 832.24 | 1099.23 | 408.38 | 0.00 | 0.00 | 0.00 |
September | 716.02 | 0.17 | 715.85 | 813.88 | 631.27 | 0.00 | 0.00 | 0.00 |
October | 512.84 | 0.00 | 512.84 | 287.20 | 1295.56 | 0.00 | 0.00 | 0.00 |
November | 389.31 | 0.00 | 389.31 | 115.73 | 1528.41 | 0.00 | 0.00 | 0.00 |
December | 329.32 | 0.00 | 329.32 | 62.43 | 1883.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 683.60 | 21.18 | 662.43 | 599.62 | 1074.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 329.32 | 0.00 | 329.32 | 62.43 | 354.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1132.42 | 125.55 | 1006.87 | 1510.93 | 1883.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 734.76 | 450.28 | 284.48 | 664.00 | 1044.95 | 0.00 | 0.00 | 0.00 |
February | 976.05 | 616.17 | 359.87 | 927.87 | 1080.21 | 0.00 | 0.00 | 0.00 |
March | 1178.06 | 687.15 | 490.91 | 1205.60 | 827.58 | 0.00 | 0.00 | 0.00 |
April | 1208.16 | 588.52 | 619.65 | 1211.29 | 722.72 | 0.00 | 0.00 | 0.00 |
May | 1412.33 | 589.93 | 822.39 | 1607.91 | 448.61 | 0.00 | 0.00 | 0.00 |
June | 1723.18 | 904.62 | 818.56 | 2317.51 | 249.78 | 0.00 | 0.00 | 0.00 |
July | 1566.51 | 745.93 | 820.58 | 2125.05 | 236.41 | 0.00 | 0.00 | 0.00 |
August | 1580.04 | 870.23 | 709.81 | 2129.56 | 271.51 | 0.00 | 0.00 | 0.00 |
September | 1314.67 | 714.17 | 600.51 | 1681.06 | 401.12 | 0.00 | 0.00 | 0.00 |
October | 952.09 | 521.69 | 430.40 | 1005.32 | 839.24 | 0.00 | 0.00 | 0.00 |
November | 741.08 | 418.42 | 322.66 | 703.58 | 977.36 | 0.00 | 0.00 | 0.00 |
December | 641.57 | 369.59 | 271.98 | 554.45 | 1186.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1169.78 | 622.75 | 547.03 | 1346.39 | 688.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 641.57 | 369.59 | 271.98 | 554.45 | 236.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1723.18 | 904.62 | 822.39 | 2317.51 | 1186.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3373.25 | 2774.86 | 598.39 | 3875.87 | 1532.59 | 0.00 | 0.00 | 0.00 |
February | 3235.57 | 2579.60 | 655.97 | 3683.50 | 1595.89 | 0.00 | 0.00 | 0.00 |
March | 2385.51 | 1569.53 | 815.98 | 2753.43 | 1274.78 | 0.00 | 0.00 | 0.00 |
April | 1545.04 | 621.26 | 923.77 | 1629.99 | 1149.89 | 0.00 | 0.00 | 0.00 |
May | 1415.86 | 259.52 | 1156.34 | 1624.65 | 734.65 | 0.00 | 0.00 | 0.00 |
June | 1305.38 | 238.58 | 1066.79 | 1886.78 | 410.27 | 0.00 | 0.00 | 0.00 |
July | 1358.86 | 243.33 | 1115.53 | 1968.07 | 380.03 | 0.00 | 0.00 | 0.00 |
August | 1730.11 | 723.25 | 1006.86 | 2516.66 | 430.73 | 0.00 | 0.00 | 0.00 |
September | 2225.95 | 1242.07 | 983.89 | 3034.62 | 647.63 | 0.00 | 0.00 | 0.00 |
October | 2661.59 | 1888.45 | 773.13 | 3232.46 | 1286.16 | 0.00 | 0.00 | 0.00 |
November | 3242.77 | 2584.96 | 657.81 | 3804.20 | 1465.24 | 0.00 | 0.00 | 0.00 |
December | 3100.93 | 2509.85 | 591.08 | 3489.99 | 1714.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2293.09 | 1429.77 | 863.32 | 2786.58 | 1048.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1305.38 | 238.58 | 591.08 | 1624.65 | 380.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3373.25 | 2774.86 | 1156.34 | 3875.87 | 1714.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 781.62 | 495.28 | 286.34 | 758.07 | 1075.87 | 0.00 | 0.00 | 0.00 |
February | 942.52 | 584.08 | 358.44 | 903.79 | 1099.88 | 0.00 | 0.00 | 0.00 |
March | 1103.63 | 608.90 | 494.74 | 1124.64 | 847.48 | 0.00 | 0.00 | 0.00 |
April | 1039.12 | 439.95 | 599.18 | 1013.65 | 743.89 | 0.00 | 0.00 | 0.00 |
May | 1270.08 | 447.75 | 822.33 | 1451.93 | 478.55 | 0.00 | 0.00 | 0.00 |
June | 1553.38 | 747.39 | 805.99 | 2119.18 | 281.88 | 0.00 | 0.00 | 0.00 |
July | 1265.64 | 463.58 | 802.06 | 1733.38 | 256.96 | 0.00 | 0.00 | 0.00 |
August | 1320.97 | 652.57 | 668.39 | 1782.33 | 288.40 | 0.00 | 0.00 | 0.00 |
September | 1171.30 | 561.72 | 609.59 | 1511.33 | 430.65 | 0.00 | 0.00 | 0.00 |
October | 985.37 | 563.21 | 422.16 | 1077.29 | 857.59 | 0.00 | 0.00 | 0.00 |
November | 808.55 | 490.89 | 317.66 | 803.72 | 993.96 | 0.00 | 0.00 | 0.00 |
December | 653.09 | 385.80 | 267.29 | 580.21 | 1195.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1074.94 | 536.12 | 538.83 | 1239.69 | 710.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 653.09 | 385.80 | 267.29 | 580.21 | 256.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1553.38 | 747.39 | 822.33 | 2119.18 | 1195.17 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.942735E+09 | 0.00 | 0.942735E+09 | 0.219600E+09 | 0.424096E+10 |
February | 0.107024E+10 | 0.00 | 0.107024E+10 | 0.240545E+09 | 0.391082E+10 |
March | 0.161227E+10 | 0.00 | 0.161227E+10 | 0.796025E+09 | 0.327676E+10 |
April | 0.195946E+10 | 10870236.15 | 0.194859E+10 | 0.114936E+10 | 0.269682E+10 |
May | 0.276597E+10 | 91431654.91 | 0.267453E+10 | 0.256505E+10 | 0.171394E+10 |
June | 0.293523E+10 | 0.325418E+09 | 0.260981E+10 | 0.391075E+10 | 0.946481E+09 |
July | 0.286846E+10 | 0.185680E+09 | 0.268278E+10 | 0.386452E+10 | 0.926397E+09 |
August | 0.228308E+10 | 54009907.87 | 0.222907E+10 | 0.294362E+10 | 0.105594E+10 |
September | 0.185592E+10 | 435922.88 | 0.185548E+10 | 0.212611E+10 | 0.155375E+10 |
October | 0.137360E+10 | 0.00 | 0.137360E+10 | 0.810160E+09 | 0.324715E+10 |
November | 0.100910E+10 | 0.00 | 0.100910E+10 | 0.333069E+09 | 0.371647E+10 |
December | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.183781E+09 | 0.480524E+10 |
Annual Sum or Average | 0.215581E+11 | 0.667846E+09 | 0.208902E+11 | 0.191426E+11 | 0.320907E+11 |
Minimum of Months | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.183781E+09 | 0.926397E+09 |
Maximum of Months | 0.293523E+10 | 0.325418E+09 | 0.268278E+10 | 0.391075E+10 | 0.480524E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196798E+10 | 0.120603E+10 | 0.761944E+09 | 0.181285E+10 | 0.264929E+10 |
February | 0.236125E+10 | 0.149064E+10 | 0.870605E+09 | 0.226846E+10 | 0.249402E+10 |
March | 0.315532E+10 | 0.184046E+10 | 0.131485E+10 | 0.324858E+10 | 0.210243E+10 |
April | 0.313156E+10 | 0.152544E+10 | 0.160613E+10 | 0.315919E+10 | 0.175341E+10 |
May | 0.378277E+10 | 0.158007E+10 | 0.220270E+10 | 0.432377E+10 | 0.115182E+10 |
June | 0.446649E+10 | 0.234478E+10 | 0.212171E+10 | 0.599740E+10 | 0.631732E+09 |
July | 0.419574E+10 | 0.199790E+10 | 0.219784E+10 | 0.568155E+10 | 0.618106E+09 |
August | 0.423198E+10 | 0.233082E+10 | 0.190116E+10 | 0.569729E+10 | 0.703826E+09 |
September | 0.340763E+10 | 0.185112E+10 | 0.155652E+10 | 0.436363E+10 | 0.994093E+09 |
October | 0.255007E+10 | 0.139729E+10 | 0.115278E+10 | 0.271469E+10 | 0.211765E+10 |
November | 0.192087E+10 | 0.108454E+10 | 0.836331E+09 | 0.185675E+10 | 0.238906E+10 |
December | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.151302E+10 | 0.303315E+10 |
Annual Sum or Average | 0.368900E+11 | 0.196390E+11 | 0.172510E+11 | 0.426372E+11 | 0.206386E+11 |
Minimum of Months | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.151302E+10 | 0.618106E+09 |
Maximum of Months | 0.446649E+10 | 0.234478E+10 | 0.220270E+10 | 0.599740E+10 | 0.303315E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.903490E+10 | 0.743217E+10 | 0.160273E+10 | 0.104356E+11 | 0.388127E+10 |
February | 0.782749E+10 | 0.624056E+10 | 0.158693E+10 | 0.894437E+10 | 0.367299E+10 |
March | 0.638936E+10 | 0.420383E+10 | 0.218553E+10 | 0.739993E+10 | 0.322872E+10 |
April | 0.400474E+10 | 0.161032E+10 | 0.239442E+10 | 0.425183E+10 | 0.278214E+10 |
May | 0.379223E+10 | 0.695086E+09 | 0.309715E+10 | 0.437668E+10 | 0.187096E+10 |
June | 0.338353E+10 | 0.618411E+09 | 0.276512E+10 | 0.488195E+10 | 0.102899E+10 |
July | 0.363958E+10 | 0.651745E+09 | 0.298784E+10 | 0.526092E+10 | 0.986698E+09 |
August | 0.463392E+10 | 0.193715E+10 | 0.269678E+10 | 0.673430E+10 | 0.111101E+10 |
September | 0.576967E+10 | 0.321943E+10 | 0.255023E+10 | 0.787273E+10 | 0.159898E+10 |
October | 0.712879E+10 | 0.505803E+10 | 0.207076E+10 | 0.868815E+10 | 0.324305E+10 |
November | 0.840526E+10 | 0.670020E+10 | 0.170505E+10 | 0.990501E+10 | 0.358146E+10 |
December | 0.830554E+10 | 0.672238E+10 | 0.158315E+10 | 0.939661E+10 | 0.436554E+10 |
Annual Sum or Average | 0.723150E+11 | 0.450893E+11 | 0.272257E+11 | 0.881481E+11 | 0.313518E+11 |
Minimum of Months | 0.338353E+10 | 0.618411E+09 | 0.158315E+10 | 0.425183E+10 | 0.986698E+09 |
Maximum of Months | 0.903490E+10 | 0.743217E+10 | 0.309715E+10 | 0.104356E+11 | 0.436554E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209349E+10 | 0.132655E+10 | 0.766944E+09 | 0.205259E+10 | 0.272194E+10 |
February | 0.228015E+10 | 0.141302E+10 | 0.867136E+09 | 0.220112E+10 | 0.253249E+10 |
March | 0.295598E+10 | 0.163087E+10 | 0.132510E+10 | 0.302753E+10 | 0.214578E+10 |
April | 0.269341E+10 | 0.114034E+10 | 0.155307E+10 | 0.264558E+10 | 0.180021E+10 |
May | 0.340177E+10 | 0.119925E+10 | 0.220252E+10 | 0.390806E+10 | 0.121881E+10 |
June | 0.402636E+10 | 0.193723E+10 | 0.208913E+10 | 0.548790E+10 | 0.707845E+09 |
July | 0.338988E+10 | 0.124165E+10 | 0.214823E+10 | 0.463693E+10 | 0.667476E+09 |
August | 0.353807E+10 | 0.174785E+10 | 0.179022E+10 | 0.477387E+10 | 0.744299E+09 |
September | 0.303601E+10 | 0.145597E+10 | 0.158004E+10 | 0.392915E+10 | 0.106070E+10 |
October | 0.263923E+10 | 0.150851E+10 | 0.113071E+10 | 0.290890E+10 | 0.215841E+10 |
November | 0.209577E+10 | 0.127239E+10 | 0.823378E+09 | 0.210762E+10 | 0.242396E+10 |
December | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.157136E+10 | 0.304880E+10 |
Annual Sum or Average | 0.338994E+11 | 0.169069E+11 | 0.169924E+11 | 0.392506E+11 | 0.212307E+11 |
Minimum of Months | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.157136E+10 | 0.667476E+09 |
Maximum of Months | 0.402636E+10 | 0.193723E+10 | 0.220252E+10 | 0.548790E+10 | 0.304880E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314230E+09 | 0.00 | 0.314230E+09 | 72520112.54 | 0.146199E+10 |
February | 0.356729E+09 | 0.00 | 0.356729E+09 | 84278801.00 | 0.133081E+10 |
March | 0.537397E+09 | 0.00 | 0.537397E+09 | 0.282085E+09 | 0.110902E+10 |
April | 0.653122E+09 | 3623240.62 | 0.649499E+09 | 0.400888E+09 | 0.926016E+09 |
May | 0.921945E+09 | 30475776.36 | 0.891469E+09 | 0.880588E+09 | 0.566408E+09 |
June | 0.978364E+09 | 0.108467E+09 | 0.869896E+09 | 0.132788E+10 | 0.308096E+09 |
July | 0.956108E+09 | 61890569.91 | 0.894217E+09 | 0.131214E+10 | 0.299884E+09 |
August | 0.760990E+09 | 18002450.85 | 0.742987E+09 | 0.993303E+09 | 0.353462E+09 |
September | 0.618611E+09 | 145300.75 | 0.618466E+09 | 0.706924E+09 | 0.546237E+09 |
October | 0.457844E+09 | 0.00 | 0.457844E+09 | 0.259162E+09 | 0.116516E+10 |
November | 0.336350E+09 | 0.00 | 0.336350E+09 | 0.101955E+09 | 0.132413E+10 |
December | 0.294002E+09 | 0.00 | 0.294002E+09 | 57883883.41 | 0.167830E+10 |
Annual Sum or Average | 0.718569E+10 | 0.222605E+09 | 0.696308E+10 | 0.647961E+10 | 0.110695E+11 |
Minimum of Months | 0.294002E+09 | 0.00 | 0.294002E+09 | 57883883.41 | 0.299884E+09 |
Maximum of Months | 0.978364E+09 | 0.108467E+09 | 0.894217E+09 | 0.132788E+10 | 0.167830E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314250E+09 | 0.00 | 0.314250E+09 | 72524695.69 | 0.146208E+10 |
February | 0.356751E+09 | 0.00 | 0.356751E+09 | 84284127.29 | 0.133089E+10 |
March | 0.537431E+09 | 0.00 | 0.537431E+09 | 0.282103E+09 | 0.110909E+10 |
April | 0.653163E+09 | 3623469.60 | 0.649540E+09 | 0.400914E+09 | 0.926075E+09 |
May | 0.922003E+09 | 30477702.38 | 0.891525E+09 | 0.880643E+09 | 0.566444E+09 |
June | 0.978425E+09 | 0.108474E+09 | 0.869951E+09 | 0.132796E+10 | 0.308115E+09 |
July | 0.956168E+09 | 61894481.29 | 0.894274E+09 | 0.131222E+10 | 0.299903E+09 |
August | 0.761038E+09 | 18003588.58 | 0.743034E+09 | 0.993366E+09 | 0.353484E+09 |
September | 0.618650E+09 | 145309.93 | 0.618505E+09 | 0.706968E+09 | 0.546272E+09 |
October | 0.457873E+09 | 0.00 | 0.457873E+09 | 0.259179E+09 | 0.116523E+10 |
November | 0.336371E+09 | 0.00 | 0.336371E+09 | 0.101962E+09 | 0.132421E+10 |
December | 0.294020E+09 | 0.00 | 0.294020E+09 | 57887541.57 | 0.167840E+10 |
Annual Sum or Average | 0.718614E+10 | 0.222619E+09 | 0.696352E+10 | 0.648002E+10 | 0.110702E+11 |
Minimum of Months | 0.294020E+09 | 0.00 | 0.294020E+09 | 57887541.57 | 0.299903E+09 |
Maximum of Months | 0.978425E+09 | 0.108474E+09 | 0.894274E+09 | 0.132796E+10 | 0.167840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.314250E+09 | 0.00 | 0.314250E+09 | 72524695.69 | 0.146208E+10 |
February | 0.356751E+09 | 0.00 | 0.356751E+09 | 84284127.29 | 0.133089E+10 |
March | 0.537431E+09 | 0.00 | 0.537431E+09 | 0.282103E+09 | 0.110909E+10 |
April | 0.653163E+09 | 3623469.60 | 0.649540E+09 | 0.400914E+09 | 0.926075E+09 |
May | 0.922003E+09 | 30477702.38 | 0.891525E+09 | 0.880643E+09 | 0.566444E+09 |
June | 0.978425E+09 | 0.108474E+09 | 0.869951E+09 | 0.132796E+10 | 0.308115E+09 |
July | 0.956168E+09 | 61894481.29 | 0.894274E+09 | 0.131222E+10 | 0.299903E+09 |
August | 0.761038E+09 | 18003588.58 | 0.743034E+09 | 0.993366E+09 | 0.353484E+09 |
September | 0.618650E+09 | 145309.93 | 0.618505E+09 | 0.706968E+09 | 0.546272E+09 |
October | 0.457873E+09 | 0.00 | 0.457873E+09 | 0.259179E+09 | 0.116523E+10 |
November | 0.336371E+09 | 0.00 | 0.336371E+09 | 0.101962E+09 | 0.132421E+10 |
December | 0.294020E+09 | 0.00 | 0.294020E+09 | 57887541.57 | 0.167840E+10 |
Annual Sum or Average | 0.718614E+10 | 0.222619E+09 | 0.696352E+10 | 0.648002E+10 | 0.110702E+11 |
Minimum of Months | 0.294020E+09 | 0.00 | 0.294020E+09 | 57887541.57 | 0.299903E+09 |
Maximum of Months | 0.978425E+09 | 0.108474E+09 | 0.894274E+09 | 0.132796E+10 | 0.167840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.189311E+10 | 0.116015E+10 | 0.732960E+09 | 0.173598E+10 | 0.267510E+10 |
February | 0.227142E+10 | 0.143393E+10 | 0.837488E+09 | 0.219214E+10 | 0.248943E+10 |
March | 0.303528E+10 | 0.177044E+10 | 0.126484E+10 | 0.315249E+10 | 0.210872E+10 |
April | 0.301243E+10 | 0.146740E+10 | 0.154503E+10 | 0.306344E+10 | 0.179123E+10 |
May | 0.363887E+10 | 0.151996E+10 | 0.211891E+10 | 0.419389E+10 | 0.113626E+10 |
June | 0.429657E+10 | 0.225557E+10 | 0.204100E+10 | 0.580970E+10 | 0.621351E+09 |
July | 0.403612E+10 | 0.192189E+10 | 0.211423E+10 | 0.550396E+10 | 0.607038E+09 |
August | 0.407098E+10 | 0.224214E+10 | 0.182884E+10 | 0.550183E+10 | 0.715657E+09 |
September | 0.327800E+10 | 0.178069E+10 | 0.149730E+10 | 0.419320E+10 | 0.104304E+10 |
October | 0.245305E+10 | 0.134413E+10 | 0.110893E+10 | 0.259261E+10 | 0.223704E+10 |
November | 0.184780E+10 | 0.104328E+10 | 0.804517E+09 | 0.175809E+10 | 0.249380E+10 |
December | 0.165302E+10 | 0.952253E+09 | 0.700767E+09 | 0.143916E+10 | 0.308920E+10 |
Annual Sum or Average | 0.354866E+11 | 0.188918E+11 | 0.165948E+11 | 0.411365E+11 | 0.210079E+11 |
Minimum of Months | 0.165302E+10 | 0.952253E+09 | 0.700767E+09 | 0.143916E+10 | 0.607038E+09 |
Maximum of Months | 0.429657E+10 | 0.225557E+10 | 0.211891E+10 | 0.580970E+10 | 0.308920E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 74851854.85 | 45871280.28 | 28980574.57 | 68639130.02 | 0.105771E+09 |
February | 89809899.69 | 56696393.84 | 33113505.85 | 86675395.25 | 98429771.70 |
March | 0.120012E+09 | 70001719.01 | 50010440.30 | 0.124647E+09 | 83376995.54 |
April | 0.119109E+09 | 58019680.16 | 61089059.77 | 0.121126E+09 | 70823495.23 |
May | 0.143877E+09 | 60097872.24 | 83779611.65 | 0.165823E+09 | 44926536.52 |
June | 0.169883E+09 | 89183388.48 | 80699170.63 | 0.229710E+09 | 24567656.45 |
July | 0.159585E+09 | 75989889.06 | 83594729.67 | 0.217622E+09 | 24001750.93 |
August | 0.160963E+09 | 88652189.02 | 72310777.96 | 0.217537E+09 | 28296416.33 |
September | 0.129609E+09 | 70406958.28 | 59202089.61 | 0.165795E+09 | 41240874.11 |
October | 96991565.62 | 53145510.59 | 43846055.03 | 0.102509E+09 | 88450486.20 |
November | 73060170.97 | 41250305.34 | 31809865.63 | 69513257.16 | 98602499.76 |
December | 65358905.10 | 37651218.26 | 27707686.83 | 56903194.27 | 0.122144E+09 |
Annual Sum or Average | 0.140311E+10 | 0.746966E+09 | 0.656144E+09 | 0.162650E+10 | 0.830632E+09 |
Minimum of Months | 65358905.10 | 37651218.26 | 27707686.83 | 56903194.27 | 24001750.93 |
Maximum of Months | 0.169883E+09 | 89183388.48 | 83779611.65 | 0.229710E+09 | 0.122144E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.301173E+10 | 0.247747E+10 | 0.534257E+09 | 0.349248E+10 | 0.139280E+10 |
February | 0.260925E+10 | 0.208026E+10 | 0.528990E+09 | 0.301214E+10 | 0.129011E+10 |
March | 0.212985E+10 | 0.140132E+10 | 0.728530E+09 | 0.250066E+10 | 0.112097E+10 |
April | 0.133495E+10 | 0.536789E+09 | 0.798162E+09 | 0.144670E+10 | 0.967322E+09 |
May | 0.126411E+10 | 0.231703E+09 | 0.103241E+10 | 0.149469E+10 | 0.619325E+09 |
June | 0.112787E+10 | 0.206144E+09 | 0.921731E+09 | 0.165081E+10 | 0.339194E+09 |
July | 0.121323E+10 | 0.217255E+09 | 0.995973E+09 | 0.177661E+10 | 0.325567E+09 |
August | 0.154469E+10 | 0.645737E+09 | 0.898949E+09 | 0.225879E+10 | 0.386255E+09 |
September | 0.192328E+10 | 0.107318E+10 | 0.850101E+09 | 0.262884E+10 | 0.582485E+09 |
October | 0.237634E+10 | 0.168607E+10 | 0.690272E+09 | 0.289931E+10 | 0.118991E+10 |
November | 0.280184E+10 | 0.223347E+10 | 0.568367E+09 | 0.331100E+10 | 0.130737E+10 |
December | 0.276860E+10 | 0.224087E+10 | 0.527733E+09 | 0.314837E+10 | 0.155681E+10 |
Annual Sum or Average | 0.241057E+11 | 0.150303E+11 | 0.907548E+10 | 0.296204E+11 | 0.110781E+11 |
Minimum of Months | 0.112787E+10 | 0.206144E+09 | 0.527733E+09 | 0.144670E+10 | 0.325567E+09 |
Maximum of Months | 0.301173E+10 | 0.247747E+10 | 0.103241E+10 | 0.349248E+10 | 0.155681E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.301173E+10 | 0.247747E+10 | 0.534257E+09 | 0.349248E+10 | 0.139280E+10 |
February | 0.260925E+10 | 0.208026E+10 | 0.528990E+09 | 0.301214E+10 | 0.129011E+10 |
March | 0.212985E+10 | 0.140132E+10 | 0.728530E+09 | 0.250066E+10 | 0.112097E+10 |
April | 0.133495E+10 | 0.536789E+09 | 0.798162E+09 | 0.144670E+10 | 0.967322E+09 |
May | 0.126411E+10 | 0.231703E+09 | 0.103241E+10 | 0.149469E+10 | 0.619325E+09 |
June | 0.112787E+10 | 0.206144E+09 | 0.921731E+09 | 0.165081E+10 | 0.339194E+09 |
July | 0.121323E+10 | 0.217255E+09 | 0.995973E+09 | 0.177661E+10 | 0.325567E+09 |
August | 0.154469E+10 | 0.645737E+09 | 0.898949E+09 | 0.225879E+10 | 0.386255E+09 |
September | 0.192328E+10 | 0.107318E+10 | 0.850101E+09 | 0.262884E+10 | 0.582485E+09 |
October | 0.237634E+10 | 0.168607E+10 | 0.690272E+09 | 0.289931E+10 | 0.118991E+10 |
November | 0.280184E+10 | 0.223347E+10 | 0.568367E+09 | 0.331100E+10 | 0.130737E+10 |
December | 0.276860E+10 | 0.224087E+10 | 0.527733E+09 | 0.314837E+10 | 0.155681E+10 |
Annual Sum or Average | 0.241057E+11 | 0.150303E+11 | 0.907548E+10 | 0.296204E+11 | 0.110781E+11 |
Minimum of Months | 0.112787E+10 | 0.206144E+09 | 0.527733E+09 | 0.144670E+10 | 0.325567E+09 |
Maximum of Months | 0.301173E+10 | 0.247747E+10 | 0.103241E+10 | 0.349248E+10 | 0.155681E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.301154E+10 | 0.247732E+10 | 0.534224E+09 | 0.349226E+10 | 0.139271E+10 |
February | 0.260908E+10 | 0.208012E+10 | 0.528957E+09 | 0.301195E+10 | 0.129002E+10 |
March | 0.212972E+10 | 0.140123E+10 | 0.728484E+09 | 0.250051E+10 | 0.112089E+10 |
April | 0.133487E+10 | 0.536755E+09 | 0.798112E+09 | 0.144661E+10 | 0.967261E+09 |
May | 0.126403E+10 | 0.231688E+09 | 0.103235E+10 | 0.149460E+10 | 0.619286E+09 |
June | 0.112780E+10 | 0.206131E+09 | 0.921673E+09 | 0.165071E+10 | 0.339173E+09 |
July | 0.121315E+10 | 0.217242E+09 | 0.995910E+09 | 0.177649E+10 | 0.325546E+09 |
August | 0.154459E+10 | 0.645696E+09 | 0.898892E+09 | 0.225865E+10 | 0.386231E+09 |
September | 0.192316E+10 | 0.107311E+10 | 0.850047E+09 | 0.262867E+10 | 0.582448E+09 |
October | 0.237619E+10 | 0.168596E+10 | 0.690228E+09 | 0.289912E+10 | 0.118983E+10 |
November | 0.280166E+10 | 0.223333E+10 | 0.568331E+09 | 0.331079E+10 | 0.130729E+10 |
December | 0.276843E+10 | 0.224073E+10 | 0.527700E+09 | 0.314817E+10 | 0.155671E+10 |
Annual Sum or Average | 0.241042E+11 | 0.150293E+11 | 0.907490E+10 | 0.296185E+11 | 0.110774E+11 |
Minimum of Months | 0.112780E+10 | 0.206131E+09 | 0.527700E+09 | 0.144661E+10 | 0.325546E+09 |
Maximum of Months | 0.301154E+10 | 0.247732E+10 | 0.103235E+10 | 0.349226E+10 | 0.155671E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201385E+10 | 0.127608E+10 | 0.737770E+09 | 0.197948E+10 | 0.275411E+10 |
February | 0.219341E+10 | 0.135926E+10 | 0.834151E+09 | 0.213596E+10 | 0.253211E+10 |
March | 0.284352E+10 | 0.156883E+10 | 0.127469E+10 | 0.294400E+10 | 0.214636E+10 |
April | 0.259095E+10 | 0.109696E+10 | 0.149399E+10 | 0.256993E+10 | 0.182784E+10 |
May | 0.327236E+10 | 0.115362E+10 | 0.211874E+10 | 0.379572E+10 | 0.119983E+10 |
June | 0.387319E+10 | 0.186353E+10 | 0.200966E+10 | 0.531120E+10 | 0.697040E+09 |
July | 0.326092E+10 | 0.119441E+10 | 0.206651E+10 | 0.449450E+10 | 0.648730E+09 |
August | 0.340348E+10 | 0.168136E+10 | 0.172212E+10 | 0.460674E+10 | 0.749706E+09 |
September | 0.292051E+10 | 0.140058E+10 | 0.151994E+10 | 0.376747E+10 | 0.111176E+10 |
October | 0.253882E+10 | 0.145112E+10 | 0.108770E+10 | 0.277216E+10 | 0.227981E+10 |
November | 0.201604E+10 | 0.122398E+10 | 0.792057E+09 | 0.200822E+10 | 0.253059E+10 |
December | 0.168269E+10 | 0.994004E+09 | 0.688682E+09 | 0.150686E+10 | 0.311002E+10 |
Annual Sum or Average | 0.326097E+11 | 0.162637E+11 | 0.163460E+11 | 0.378922E+11 | 0.215879E+11 |
Minimum of Months | 0.168269E+10 | 0.994004E+09 | 0.688682E+09 | 0.150686E+10 | 0.648730E+09 |
Maximum of Months | 0.387319E+10 | 0.186353E+10 | 0.211874E+10 | 0.531120E+10 | 0.311002E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 79625608.84 | 50454911.82 | 29170697.02 | 78266739.29 | 0.108895E+09 |
February | 86725264.41 | 53743742.24 | 32981522.17 | 84453572.98 | 0.100117E+09 |
March | 0.112430E+09 | 62029845.27 | 50400160.88 | 0.116403E+09 | 84865168.22 |
April | 0.102443E+09 | 43372532.56 | 59070836.17 | 0.101612E+09 | 72271233.57 |
May | 0.129386E+09 | 45613048.18 | 83772740.38 | 0.150079E+09 | 47440196.98 |
June | 0.153142E+09 | 73682114.35 | 79459870.66 | 0.209999E+09 | 27560312.13 |
July | 0.128934E+09 | 47225734.30 | 81707949.58 | 0.177708E+09 | 25650180.21 |
August | 0.134570E+09 | 66479171.86 | 68090971.48 | 0.182146E+09 | 29642692.28 |
September | 0.115474E+09 | 55377309.50 | 60096906.40 | 0.148962E+09 | 43957914.36 |
October | 0.100383E+09 | 57375825.15 | 43006691.55 | 0.109608E+09 | 90141579.31 |
November | 79712061.33 | 48394890.12 | 31317171.21 | 79402885.75 | 0.100057E+09 |
December | 66531716.14 | 39301894.90 | 27229821.24 | 59579791.60 | 0.122967E+09 |
Annual Sum or Average | 0.128936E+10 | 0.643051E+09 | 0.646305E+09 | 0.149822E+10 | 0.853566E+09 |
Minimum of Months | 66531716.14 | 39301894.90 | 27229821.24 | 59579791.60 | 25650180.21 |
Maximum of Months | 0.153142E+09 | 73682114.35 | 83772740.38 | 0.209999E+09 | 0.122967E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.942735E+09 | 0.00 | 0.942735E+09 | 0.195837E+09 | 0.449461E+10 |
February | 0.107024E+10 | 0.00 | 0.107024E+10 | 0.220346E+09 | 0.411006E+10 |
March | 0.161227E+10 | 0.00 | 0.161227E+10 | 0.768664E+09 | 0.347019E+10 |
April | 0.195946E+10 | 10870236.15 | 0.194859E+10 | 0.111819E+10 | 0.289574E+10 |
May | 0.276597E+10 | 91431654.91 | 0.267453E+10 | 0.252713E+10 | 0.179720E+10 |
June | 0.293523E+10 | 0.325418E+09 | 0.260981E+10 | 0.391632E+10 | 0.971123E+09 |
July | 0.286846E+10 | 0.185680E+09 | 0.268278E+10 | 0.387304E+10 | 0.949342E+09 |
August | 0.228308E+10 | 54009907.87 | 0.222907E+10 | 0.294417E+10 | 0.109380E+10 |
September | 0.185592E+10 | 435922.88 | 0.185548E+10 | 0.210959E+10 | 0.163626E+10 |
October | 0.137360E+10 | 0.00 | 0.137360E+10 | 0.769237E+09 | 0.347002E+10 |
November | 0.100910E+10 | 0.00 | 0.100910E+10 | 0.299974E+09 | 0.396165E+10 |
December | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.167207E+09 | 0.504472E+10 |
Annual Sum or Average | 0.215581E+11 | 0.667846E+09 | 0.208902E+11 | 0.189097E+11 | 0.338947E+11 |
Minimum of Months | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.167207E+09 | 0.949342E+09 |
Maximum of Months | 0.293523E+10 | 0.325418E+09 | 0.268278E+10 | 0.391632E+10 | 0.504472E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196798E+10 | 0.120603E+10 | 0.761944E+09 | 0.177846E+10 | 0.279880E+10 |
February | 0.236125E+10 | 0.149064E+10 | 0.870605E+09 | 0.224470E+10 | 0.261325E+10 |
March | 0.315532E+10 | 0.184046E+10 | 0.131485E+10 | 0.322908E+10 | 0.221660E+10 |
April | 0.313156E+10 | 0.152544E+10 | 0.160613E+10 | 0.313967E+10 | 0.187328E+10 |
May | 0.378277E+10 | 0.158007E+10 | 0.220270E+10 | 0.430662E+10 | 0.120157E+10 |
June | 0.446649E+10 | 0.234478E+10 | 0.212171E+10 | 0.600698E+10 | 0.647422E+09 |
July | 0.419574E+10 | 0.199790E+10 | 0.219784E+10 | 0.569173E+10 | 0.633204E+09 |
August | 0.423198E+10 | 0.233082E+10 | 0.190116E+10 | 0.570381E+10 | 0.727222E+09 |
September | 0.340763E+10 | 0.185112E+10 | 0.155652E+10 | 0.435730E+10 | 0.103969E+10 |
October | 0.255007E+10 | 0.139729E+10 | 0.115278E+10 | 0.269264E+10 | 0.224783E+10 |
November | 0.192087E+10 | 0.108454E+10 | 0.836331E+09 | 0.182368E+10 | 0.253332E+10 |
December | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.148503E+10 | 0.317885E+10 |
Annual Sum or Average | 0.368900E+11 | 0.196390E+11 | 0.172510E+11 | 0.424597E+11 | 0.217110E+11 |
Minimum of Months | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.148503E+10 | 0.633204E+09 |
Maximum of Months | 0.446649E+10 | 0.234478E+10 | 0.220270E+10 | 0.600698E+10 | 0.317885E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.903490E+10 | 0.743217E+10 | 0.160273E+10 | 0.103811E+11 | 0.410489E+10 |
February | 0.782749E+10 | 0.624056E+10 | 0.158693E+10 | 0.891112E+10 | 0.386078E+10 |
March | 0.638936E+10 | 0.420383E+10 | 0.218553E+10 | 0.737478E+10 | 0.341438E+10 |
April | 0.400474E+10 | 0.161032E+10 | 0.239442E+10 | 0.422493E+10 | 0.298053E+10 |
May | 0.379223E+10 | 0.695086E+09 | 0.309715E+10 | 0.435146E+10 | 0.196769E+10 |
June | 0.338353E+10 | 0.618411E+09 | 0.276512E+10 | 0.489055E+10 | 0.106341E+10 |
July | 0.363958E+10 | 0.651745E+09 | 0.298784E+10 | 0.527128E+10 | 0.101787E+10 |
August | 0.463392E+10 | 0.193715E+10 | 0.269678E+10 | 0.674062E+10 | 0.115366E+10 |
September | 0.576967E+10 | 0.321943E+10 | 0.255023E+10 | 0.786575E+10 | 0.167866E+10 |
October | 0.712879E+10 | 0.505803E+10 | 0.207076E+10 | 0.865783E+10 | 0.344484E+10 |
November | 0.840526E+10 | 0.670020E+10 | 0.170505E+10 | 0.986048E+10 | 0.379789E+10 |
December | 0.830554E+10 | 0.672238E+10 | 0.158315E+10 | 0.934760E+10 | 0.459099E+10 |
Annual Sum or Average | 0.723150E+11 | 0.450893E+11 | 0.272257E+11 | 0.878775E+11 | 0.330756E+11 |
Minimum of Months | 0.338353E+10 | 0.618411E+09 | 0.158315E+10 | 0.422493E+10 | 0.101787E+10 |
Maximum of Months | 0.903490E+10 | 0.743217E+10 | 0.309715E+10 | 0.103811E+11 | 0.459099E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209349E+10 | 0.132655E+10 | 0.766944E+09 | 0.203041E+10 | 0.288161E+10 |
February | 0.228015E+10 | 0.141302E+10 | 0.867136E+09 | 0.218644E+10 | 0.266082E+10 |
March | 0.295598E+10 | 0.163087E+10 | 0.132510E+10 | 0.301224E+10 | 0.226988E+10 |
April | 0.269341E+10 | 0.114034E+10 | 0.155307E+10 | 0.262737E+10 | 0.192816E+10 |
May | 0.340177E+10 | 0.119925E+10 | 0.220252E+10 | 0.388885E+10 | 0.128175E+10 |
June | 0.402636E+10 | 0.193723E+10 | 0.208913E+10 | 0.549291E+10 | 0.730623E+09 |
July | 0.338988E+10 | 0.124165E+10 | 0.214823E+10 | 0.464270E+10 | 0.688238E+09 |
August | 0.353807E+10 | 0.174785E+10 | 0.179022E+10 | 0.477378E+10 | 0.772439E+09 |
September | 0.303601E+10 | 0.145597E+10 | 0.158004E+10 | 0.391737E+10 | 0.111623E+10 |
October | 0.263923E+10 | 0.150851E+10 | 0.113071E+10 | 0.288541E+10 | 0.229697E+10 |
November | 0.209577E+10 | 0.127239E+10 | 0.823378E+09 | 0.208324E+10 | 0.257633E+10 |
December | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.155404E+10 | 0.320114E+10 |
Annual Sum or Average | 0.338994E+11 | 0.169069E+11 | 0.169924E+11 | 0.390948E+11 | 0.224042E+11 |
Minimum of Months | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.155404E+10 | 0.688238E+09 |
Maximum of Months | 0.402636E+10 | 0.193723E+10 | 0.220252E+10 | 0.549291E+10 | 0.320114E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 81.99 | 1583.39 | 351.98 | 0.00 | 351.98 | 0.00 | 0.00 |
February | 99.43 | 1616.57 | 442.39 | 0.00 | 442.39 | 0.00 | 0.00 |
March | 297.20 | 1223.40 | 601.95 | 0.00 | 601.95 | 0.00 | 0.00 |
April | 443.42 | 1040.44 | 755.96 | 4.19 | 751.77 | 0.00 | 0.00 |
May | 957.68 | 639.91 | 1032.69 | 34.14 | 998.56 | 0.00 | 0.00 |
June | 1508.78 | 365.15 | 1132.42 | 125.55 | 1006.87 | 0.00 | 0.00 |
July | 1442.84 | 345.88 | 1070.96 | 69.33 | 1001.64 | 0.00 | 0.00 |
August | 1099.02 | 394.24 | 852.40 | 20.16 | 832.24 | 0.00 | 0.00 |
September | 820.26 | 599.44 | 716.02 | 0.17 | 715.85 | 0.00 | 0.00 |
October | 302.48 | 1212.35 | 512.84 | 0.00 | 512.84 | 0.00 | 0.00 |
November | 128.50 | 1433.82 | 389.31 | 0.00 | 389.31 | 0.00 | 0.00 |
December | 68.62 | 1794.07 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Annual Sum or Average | 607.01 | 1017.59 | 683.60 | 21.18 | 662.43 | 0.00 | 0.00 |
Minimum of Months | 68.62 | 345.88 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Maximum of Months | 1508.78 | 1794.07 | 1132.42 | 125.55 | 1006.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 676.84 | 989.13 | 734.76 | 450.28 | 284.48 | 0.00 | 0.00 |
February | 937.69 | 1030.93 | 976.05 | 616.17 | 359.87 | 0.00 | 0.00 |
March | 1212.88 | 784.96 | 1178.06 | 687.15 | 490.91 | 0.00 | 0.00 |
April | 1218.82 | 676.47 | 1208.16 | 588.52 | 619.65 | 0.00 | 0.00 |
May | 1614.31 | 430.04 | 1412.33 | 589.93 | 822.39 | 0.00 | 0.00 |
June | 2313.81 | 243.72 | 1723.18 | 904.62 | 818.56 | 0.00 | 0.00 |
July | 2121.25 | 230.77 | 1566.51 | 745.93 | 820.58 | 0.00 | 0.00 |
August | 2127.12 | 262.78 | 1580.04 | 870.23 | 709.81 | 0.00 | 0.00 |
September | 1683.50 | 383.52 | 1314.67 | 714.17 | 600.51 | 0.00 | 0.00 |
October | 1013.55 | 790.64 | 952.09 | 521.69 | 430.40 | 0.00 | 0.00 |
November | 716.34 | 921.70 | 741.08 | 418.42 | 322.66 | 0.00 | 0.00 |
December | 564.90 | 1132.45 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Annual Sum or Average | 1352.02 | 654.45 | 1169.78 | 622.75 | 547.03 | 0.00 | 0.00 |
Minimum of Months | 564.90 | 230.77 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Maximum of Months | 2313.81 | 1132.45 | 1723.18 | 904.62 | 822.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3896.21 | 1449.10 | 3373.25 | 2774.86 | 598.39 | 0.00 | 0.00 |
February | 3697.24 | 1518.27 | 3235.57 | 2579.60 | 655.97 | 0.00 | 0.00 |
March | 2762.82 | 1205.46 | 2385.51 | 1569.53 | 815.98 | 0.00 | 0.00 |
April | 1640.36 | 1073.36 | 1545.04 | 621.26 | 923.77 | 0.00 | 0.00 |
May | 1634.07 | 698.54 | 1415.86 | 259.52 | 1156.34 | 0.00 | 0.00 |
June | 1883.47 | 396.99 | 1305.38 | 238.58 | 1066.79 | 0.00 | 0.00 |
July | 1964.20 | 368.39 | 1358.86 | 243.33 | 1115.53 | 0.00 | 0.00 |
August | 2514.30 | 414.80 | 1730.11 | 723.25 | 1006.86 | 0.00 | 0.00 |
September | 3037.32 | 616.89 | 2225.95 | 1242.07 | 983.89 | 0.00 | 0.00 |
October | 3243.78 | 1210.81 | 2661.59 | 1888.45 | 773.13 | 0.00 | 0.00 |
November | 3821.38 | 1381.74 | 3242.77 | 2584.96 | 657.81 | 0.00 | 0.00 |
December | 3508.29 | 1629.91 | 3100.93 | 2509.85 | 591.08 | 0.00 | 0.00 |
Annual Sum or Average | 2795.16 | 994.16 | 2293.09 | 1429.77 | 863.32 | 0.00 | 0.00 |
Minimum of Months | 1634.07 | 368.39 | 1305.38 | 238.58 | 591.08 | 0.00 | 0.00 |
Maximum of Months | 3896.21 | 1629.91 | 3373.25 | 2774.86 | 1156.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 766.35 | 1016.25 | 781.62 | 495.28 | 286.34 | 0.00 | 0.00 |
February | 909.85 | 1046.83 | 942.52 | 584.08 | 358.44 | 0.00 | 0.00 |
March | 1130.35 | 801.14 | 1103.63 | 608.90 | 494.74 | 0.00 | 0.00 |
April | 1020.67 | 694.53 | 1039.12 | 439.95 | 599.18 | 0.00 | 0.00 |
May | 1459.10 | 455.05 | 1270.08 | 447.75 | 822.33 | 0.00 | 0.00 |
June | 2117.24 | 273.09 | 1553.38 | 747.39 | 805.99 | 0.00 | 0.00 |
July | 1731.23 | 249.21 | 1265.64 | 463.58 | 802.06 | 0.00 | 0.00 |
August | 1782.36 | 277.89 | 1320.97 | 652.57 | 668.39 | 0.00 | 0.00 |
September | 1515.88 | 409.22 | 1171.30 | 561.72 | 609.59 | 0.00 | 0.00 |
October | 1086.06 | 805.86 | 985.37 | 563.21 | 422.16 | 0.00 | 0.00 |
November | 813.12 | 935.17 | 808.55 | 490.89 | 317.66 | 0.00 | 0.00 |
December | 586.68 | 1138.29 | 653.09 | 385.80 | 267.29 | 0.00 | 0.00 |
Annual Sum or Average | 1244.63 | 673.22 | 1074.94 | 536.12 | 538.83 | 0.00 | 0.00 |
Minimum of Months | 586.68 | 249.21 | 653.09 | 385.80 | 267.29 | 0.00 | 0.00 |
Maximum of Months | 2117.24 | 1138.29 | 1553.38 | 747.39 | 822.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 81.23 | 1637.60 | 351.98 | 0.00 | 351.98 | 0.00 | 0.00 |
February | 104.52 | 1650.38 | 442.39 | 0.00 | 442.39 | 0.00 | 0.00 |
March | 315.97 | 1242.24 | 601.95 | 0.00 | 601.95 | 0.00 | 0.00 |
April | 464.01 | 1071.82 | 755.96 | 4.19 | 751.77 | 0.00 | 0.00 |
May | 986.36 | 634.44 | 1032.69 | 34.14 | 998.55 | 0.00 | 0.00 |
June | 1536.96 | 356.61 | 1132.41 | 125.55 | 1006.87 | 0.00 | 0.00 |
July | 1469.75 | 335.91 | 1070.95 | 69.32 | 1001.63 | 0.00 | 0.00 |
August | 1112.62 | 395.92 | 852.40 | 20.16 | 832.23 | 0.00 | 0.00 |
September | 818.23 | 632.25 | 716.01 | 0.17 | 715.85 | 0.00 | 0.00 |
October | 290.29 | 1305.12 | 512.84 | 0.00 | 512.84 | 0.00 | 0.00 |
November | 118.01 | 1532.62 | 389.31 | 0.00 | 389.31 | 0.00 | 0.00 |
December | 64.84 | 1879.89 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Annual Sum or Average | 616.43 | 1053.08 | 683.60 | 21.18 | 662.42 | 0.00 | 0.00 |
Minimum of Months | 64.84 | 335.91 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Maximum of Months | 1536.96 | 1879.89 | 1132.41 | 125.55 | 1006.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 673.77 | 1038.26 | 734.75 | 450.28 | 284.48 | 0.00 | 0.00 |
February | 941.97 | 1069.72 | 976.04 | 616.17 | 359.87 | 0.00 | 0.00 |
March | 1223.54 | 818.44 | 1178.05 | 687.14 | 490.91 | 0.00 | 0.00 |
April | 1228.61 | 718.38 | 1208.16 | 588.51 | 619.64 | 0.00 | 0.00 |
May | 1627.73 | 441.00 | 1412.31 | 589.93 | 822.39 | 0.00 | 0.00 |
June | 2330.02 | 249.20 | 1723.17 | 904.61 | 818.56 | 0.00 | 0.00 |
July | 2136.19 | 235.60 | 1566.50 | 745.92 | 820.57 | 0.00 | 0.00 |
August | 2135.37 | 277.76 | 1580.03 | 870.22 | 709.81 | 0.00 | 0.00 |
September | 1681.71 | 418.32 | 1314.66 | 714.16 | 600.50 | 0.00 | 0.00 |
October | 1006.24 | 868.24 | 952.08 | 521.68 | 430.40 | 0.00 | 0.00 |
November | 705.09 | 1000.15 | 741.07 | 418.41 | 322.66 | 0.00 | 0.00 |
December | 558.57 | 1198.98 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Annual Sum or Average | 1356.01 | 692.49 | 1169.77 | 622.74 | 547.02 | 0.00 | 0.00 |
Minimum of Months | 558.57 | 235.60 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Maximum of Months | 2330.02 | 1198.98 | 1723.17 | 904.61 | 822.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3911.74 | 1560.00 | 3373.28 | 2774.89 | 598.39 | 0.00 | 0.00 |
February | 3735.22 | 1599.80 | 3235.60 | 2579.63 | 655.98 | 0.00 | 0.00 |
March | 2800.86 | 1255.54 | 2385.54 | 1569.55 | 815.99 | 0.00 | 0.00 |
April | 1674.38 | 1119.56 | 1545.05 | 621.27 | 923.78 | 0.00 | 0.00 |
May | 1674.13 | 693.67 | 1415.87 | 259.52 | 1156.35 | 0.00 | 0.00 |
June | 1910.62 | 392.58 | 1305.38 | 238.59 | 1066.80 | 0.00 | 0.00 |
July | 1989.89 | 364.65 | 1358.87 | 243.34 | 1115.54 | 0.00 | 0.00 |
August | 2529.96 | 432.62 | 1730.12 | 723.26 | 1006.87 | 0.00 | 0.00 |
September | 3042.57 | 674.16 | 2225.97 | 1242.08 | 983.89 | 0.00 | 0.00 |
October | 3247.36 | 1332.76 | 2661.61 | 1888.47 | 773.14 | 0.00 | 0.00 |
November | 3832.09 | 1513.13 | 3242.80 | 2584.99 | 657.82 | 0.00 | 0.00 |
December | 3526.32 | 1743.70 | 3100.97 | 2509.88 | 591.09 | 0.00 | 0.00 |
Annual Sum or Average | 2817.71 | 1053.83 | 2293.12 | 1429.79 | 863.33 | 0.00 | 0.00 |
Minimum of Months | 1674.13 | 364.65 | 1305.38 | 238.59 | 591.09 | 0.00 | 0.00 |
Maximum of Months | 3911.74 | 1743.70 | 3373.28 | 2774.89 | 1156.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 768.28 | 1068.92 | 781.61 | 495.27 | 286.34 | 0.00 | 0.00 |
February | 917.83 | 1088.06 | 942.52 | 584.08 | 358.44 | 0.00 | 0.00 |
March | 1142.62 | 833.04 | 1103.63 | 608.89 | 494.73 | 0.00 | 0.00 |
April | 1030.69 | 733.07 | 1039.12 | 439.94 | 599.17 | 0.00 | 0.00 |
May | 1473.19 | 465.68 | 1270.07 | 447.74 | 822.32 | 0.00 | 0.00 |
June | 2130.09 | 279.55 | 1553.37 | 747.38 | 805.99 | 0.00 | 0.00 |
July | 1744.40 | 251.78 | 1265.63 | 463.57 | 802.05 | 0.00 | 0.00 |
August | 1787.96 | 290.98 | 1320.96 | 652.57 | 668.39 | 0.00 | 0.00 |
September | 1510.97 | 445.88 | 1171.29 | 561.71 | 609.58 | 0.00 | 0.00 |
October | 1075.93 | 884.84 | 985.37 | 563.21 | 422.16 | 0.00 | 0.00 |
November | 805.41 | 1014.91 | 808.55 | 490.89 | 317.66 | 0.00 | 0.00 |
December | 584.84 | 1207.06 | 653.08 | 385.79 | 267.29 | 0.00 | 0.00 |
Annual Sum or Average | 1249.06 | 711.61 | 1074.93 | 536.11 | 538.82 | 0.00 | 0.00 |
Minimum of Months | 584.84 | 251.78 | 653.08 | 385.79 | 267.29 | 0.00 | 0.00 |
Maximum of Months | 2130.09 | 1207.06 | 1553.37 | 747.38 | 822.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 73.12 | 1678.10 | 351.98 | 0.00 | 351.98 | 0.00 | 0.00 |
February | 91.08 | 1698.94 | 442.39 | 0.00 | 442.39 | 0.00 | 0.00 |
March | 286.99 | 1295.62 | 601.95 | 0.00 | 601.95 | 0.00 | 0.00 |
April | 431.40 | 1117.18 | 755.96 | 4.19 | 751.77 | 0.00 | 0.00 |
May | 943.52 | 671.00 | 1032.69 | 34.14 | 998.56 | 0.00 | 0.00 |
June | 1510.93 | 374.66 | 1132.42 | 125.55 | 1006.87 | 0.00 | 0.00 |
July | 1446.03 | 354.44 | 1070.96 | 69.33 | 1001.64 | 0.00 | 0.00 |
August | 1099.23 | 408.38 | 852.40 | 20.16 | 832.24 | 0.00 | 0.00 |
September | 813.88 | 631.27 | 716.02 | 0.17 | 715.85 | 0.00 | 0.00 |
October | 287.20 | 1295.56 | 512.84 | 0.00 | 512.84 | 0.00 | 0.00 |
November | 115.73 | 1528.41 | 389.31 | 0.00 | 389.31 | 0.00 | 0.00 |
December | 62.43 | 1883.48 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Annual Sum or Average | 599.62 | 1074.79 | 683.60 | 21.18 | 662.43 | 0.00 | 0.00 |
Minimum of Months | 62.43 | 354.44 | 329.32 | 0.00 | 329.32 | 0.00 | 0.00 |
Maximum of Months | 1510.93 | 1883.48 | 1132.42 | 125.55 | 1006.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 664.00 | 1044.95 | 734.76 | 450.28 | 284.48 | 0.00 | 0.00 |
February | 927.87 | 1080.21 | 976.05 | 616.17 | 359.87 | 0.00 | 0.00 |
March | 1205.60 | 827.58 | 1178.06 | 687.15 | 490.91 | 0.00 | 0.00 |
April | 1211.29 | 722.72 | 1208.16 | 588.52 | 619.65 | 0.00 | 0.00 |
May | 1607.91 | 448.61 | 1412.33 | 589.93 | 822.39 | 0.00 | 0.00 |
June | 2317.51 | 249.78 | 1723.18 | 904.62 | 818.56 | 0.00 | 0.00 |
July | 2125.05 | 236.41 | 1566.51 | 745.93 | 820.58 | 0.00 | 0.00 |
August | 2129.56 | 271.51 | 1580.04 | 870.23 | 709.81 | 0.00 | 0.00 |
September | 1681.06 | 401.12 | 1314.67 | 714.17 | 600.51 | 0.00 | 0.00 |
October | 1005.32 | 839.24 | 952.09 | 521.69 | 430.40 | 0.00 | 0.00 |
November | 703.58 | 977.36 | 741.08 | 418.42 | 322.66 | 0.00 | 0.00 |
December | 554.45 | 1186.85 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Annual Sum or Average | 1346.39 | 688.45 | 1169.78 | 622.75 | 547.03 | 0.00 | 0.00 |
Minimum of Months | 554.45 | 236.41 | 641.57 | 369.59 | 271.98 | 0.00 | 0.00 |
Maximum of Months | 2317.51 | 1186.85 | 1723.18 | 904.62 | 822.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3875.87 | 1532.59 | 3373.25 | 2774.86 | 598.39 | 0.00 | 0.00 |
February | 3683.50 | 1595.89 | 3235.57 | 2579.60 | 655.97 | 0.00 | 0.00 |
March | 2753.43 | 1274.78 | 2385.51 | 1569.53 | 815.98 | 0.00 | 0.00 |
April | 1629.99 | 1149.89 | 1545.04 | 621.26 | 923.77 | 0.00 | 0.00 |
May | 1624.65 | 734.65 | 1415.86 | 259.52 | 1156.34 | 0.00 | 0.00 |
June | 1886.78 | 410.27 | 1305.38 | 238.58 | 1066.79 | 0.00 | 0.00 |
July | 1968.07 | 380.03 | 1358.86 | 243.33 | 1115.53 | 0.00 | 0.00 |
August | 2516.66 | 430.73 | 1730.11 | 723.25 | 1006.86 | 0.00 | 0.00 |
September | 3034.62 | 647.63 | 2225.95 | 1242.07 | 983.89 | 0.00 | 0.00 |
October | 3232.46 | 1286.16 | 2661.59 | 1888.45 | 773.13 | 0.00 | 0.00 |
November | 3804.20 | 1465.24 | 3242.77 | 2584.96 | 657.81 | 0.00 | 0.00 |
December | 3489.99 | 1714.08 | 3100.93 | 2509.85 | 591.08 | 0.00 | 0.00 |
Annual Sum or Average | 2786.58 | 1048.82 | 2293.09 | 1429.77 | 863.32 | 0.00 | 0.00 |
Minimum of Months | 1624.65 | 380.03 | 1305.38 | 238.58 | 591.08 | 0.00 | 0.00 |
Maximum of Months | 3875.87 | 1714.08 | 3373.25 | 2774.86 | 1156.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 758.07 | 1075.87 | 781.62 | 495.28 | 286.34 | 0.00 | 0.00 |
February | 903.79 | 1099.88 | 942.52 | 584.08 | 358.44 | 0.00 | 0.00 |
March | 1124.64 | 847.48 | 1103.63 | 608.90 | 494.74 | 0.00 | 0.00 |
April | 1013.65 | 743.89 | 1039.12 | 439.95 | 599.18 | 0.00 | 0.00 |
May | 1451.93 | 478.55 | 1270.08 | 447.75 | 822.33 | 0.00 | 0.00 |
June | 2119.18 | 281.88 | 1553.38 | 747.39 | 805.99 | 0.00 | 0.00 |
July | 1733.38 | 256.96 | 1265.64 | 463.58 | 802.06 | 0.00 | 0.00 |
August | 1782.33 | 288.40 | 1320.97 | 652.57 | 668.39 | 0.00 | 0.00 |
September | 1511.33 | 430.65 | 1171.30 | 561.72 | 609.59 | 0.00 | 0.00 |
October | 1077.29 | 857.59 | 985.37 | 563.21 | 422.16 | 0.00 | 0.00 |
November | 803.72 | 993.96 | 808.55 | 490.89 | 317.66 | 0.00 | 0.00 |
December | 580.21 | 1195.17 | 653.09 | 385.80 | 267.29 | 0.00 | 0.00 |
Annual Sum or Average | 1239.69 | 710.43 | 1074.94 | 536.12 | 538.83 | 0.00 | 0.00 |
Minimum of Months | 580.21 | 256.96 | 653.09 | 385.80 | 267.29 | 0.00 | 0.00 |
Maximum of Months | 2119.18 | 1195.17 | 1553.38 | 747.39 | 822.33 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.219600E+09 | 0.424096E+10 | 0.942735E+09 | 0.00 | 0.942735E+09 | 0.00 | 0.00 |
February | 0.240545E+09 | 0.391082E+10 | 0.107024E+10 | 0.00 | 0.107024E+10 | 0.00 | 0.00 |
March | 0.796025E+09 | 0.327676E+10 | 0.161227E+10 | 0.00 | 0.161227E+10 | 0.00 | 0.00 |
April | 0.114936E+10 | 0.269682E+10 | 0.195946E+10 | 10870236.15 | 0.194859E+10 | 0.00 | 0.00 |
May | 0.256505E+10 | 0.171394E+10 | 0.276597E+10 | 91431654.91 | 0.267453E+10 | 0.00 | 0.00 |
June | 0.391075E+10 | 0.946481E+09 | 0.293523E+10 | 0.325418E+09 | 0.260981E+10 | 0.00 | 0.00 |
July | 0.386452E+10 | 0.926397E+09 | 0.286846E+10 | 0.185680E+09 | 0.268278E+10 | 0.00 | 0.00 |
August | 0.294362E+10 | 0.105594E+10 | 0.228308E+10 | 54009907.87 | 0.222907E+10 | 0.00 | 0.00 |
September | 0.212611E+10 | 0.155375E+10 | 0.185592E+10 | 435922.88 | 0.185548E+10 | 0.00 | 0.00 |
October | 0.810160E+09 | 0.324715E+10 | 0.137360E+10 | 0.00 | 0.137360E+10 | 0.00 | 0.00 |
November | 0.333069E+09 | 0.371647E+10 | 0.100910E+10 | 0.00 | 0.100910E+10 | 0.00 | 0.00 |
December | 0.183781E+09 | 0.480524E+10 | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.191426E+11 | 0.320907E+11 | 0.215581E+11 | 0.667846E+09 | 0.208902E+11 | 0.00 | 0.00 |
Minimum of Months | 0.183781E+09 | 0.926397E+09 | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.00 | 0.00 |
Maximum of Months | 0.391075E+10 | 0.480524E+10 | 0.293523E+10 | 0.325418E+09 | 0.268278E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181285E+10 | 0.264929E+10 | 0.196798E+10 | 0.120603E+10 | 0.761944E+09 | 0.00 | 0.00 |
February | 0.226846E+10 | 0.249402E+10 | 0.236125E+10 | 0.149064E+10 | 0.870605E+09 | 0.00 | 0.00 |
March | 0.324858E+10 | 0.210243E+10 | 0.315532E+10 | 0.184046E+10 | 0.131485E+10 | 0.00 | 0.00 |
April | 0.315919E+10 | 0.175341E+10 | 0.313156E+10 | 0.152544E+10 | 0.160613E+10 | 0.00 | 0.00 |
May | 0.432377E+10 | 0.115182E+10 | 0.378277E+10 | 0.158007E+10 | 0.220270E+10 | 0.00 | 0.00 |
June | 0.599740E+10 | 0.631732E+09 | 0.446649E+10 | 0.234478E+10 | 0.212171E+10 | 0.00 | 0.00 |
July | 0.568155E+10 | 0.618106E+09 | 0.419574E+10 | 0.199790E+10 | 0.219784E+10 | 0.00 | 0.00 |
August | 0.569729E+10 | 0.703826E+09 | 0.423198E+10 | 0.233082E+10 | 0.190116E+10 | 0.00 | 0.00 |
September | 0.436363E+10 | 0.994093E+09 | 0.340763E+10 | 0.185112E+10 | 0.155652E+10 | 0.00 | 0.00 |
October | 0.271469E+10 | 0.211765E+10 | 0.255007E+10 | 0.139729E+10 | 0.115278E+10 | 0.00 | 0.00 |
November | 0.185675E+10 | 0.238906E+10 | 0.192087E+10 | 0.108454E+10 | 0.836331E+09 | 0.00 | 0.00 |
December | 0.151302E+10 | 0.303315E+10 | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.426372E+11 | 0.206386E+11 | 0.368900E+11 | 0.196390E+11 | 0.172510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.151302E+10 | 0.618106E+09 | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.00 | 0.00 |
Maximum of Months | 0.599740E+10 | 0.303315E+10 | 0.446649E+10 | 0.234478E+10 | 0.220270E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104356E+11 | 0.388127E+10 | 0.903490E+10 | 0.743217E+10 | 0.160273E+10 | 0.00 | 0.00 |
February | 0.894437E+10 | 0.367299E+10 | 0.782749E+10 | 0.624056E+10 | 0.158693E+10 | 0.00 | 0.00 |
March | 0.739993E+10 | 0.322872E+10 | 0.638936E+10 | 0.420383E+10 | 0.218553E+10 | 0.00 | 0.00 |
April | 0.425183E+10 | 0.278214E+10 | 0.400474E+10 | 0.161032E+10 | 0.239442E+10 | 0.00 | 0.00 |
May | 0.437668E+10 | 0.187096E+10 | 0.379223E+10 | 0.695086E+09 | 0.309715E+10 | 0.00 | 0.00 |
June | 0.488195E+10 | 0.102899E+10 | 0.338353E+10 | 0.618411E+09 | 0.276512E+10 | 0.00 | 0.00 |
July | 0.526092E+10 | 0.986698E+09 | 0.363958E+10 | 0.651745E+09 | 0.298784E+10 | 0.00 | 0.00 |
August | 0.673430E+10 | 0.111101E+10 | 0.463392E+10 | 0.193715E+10 | 0.269678E+10 | 0.00 | 0.00 |
September | 0.787273E+10 | 0.159898E+10 | 0.576967E+10 | 0.321943E+10 | 0.255023E+10 | 0.00 | 0.00 |
October | 0.868815E+10 | 0.324305E+10 | 0.712879E+10 | 0.505803E+10 | 0.207076E+10 | 0.00 | 0.00 |
November | 0.990501E+10 | 0.358146E+10 | 0.840526E+10 | 0.670020E+10 | 0.170505E+10 | 0.00 | 0.00 |
December | 0.939661E+10 | 0.436554E+10 | 0.830554E+10 | 0.672238E+10 | 0.158315E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.881481E+11 | 0.313518E+11 | 0.723150E+11 | 0.450893E+11 | 0.272257E+11 | 0.00 | 0.00 |
Minimum of Months | 0.425183E+10 | 0.986698E+09 | 0.338353E+10 | 0.618411E+09 | 0.158315E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104356E+11 | 0.436554E+10 | 0.903490E+10 | 0.743217E+10 | 0.309715E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205259E+10 | 0.272194E+10 | 0.209349E+10 | 0.132655E+10 | 0.766944E+09 | 0.00 | 0.00 |
February | 0.220112E+10 | 0.253249E+10 | 0.228015E+10 | 0.141302E+10 | 0.867136E+09 | 0.00 | 0.00 |
March | 0.302753E+10 | 0.214578E+10 | 0.295598E+10 | 0.163087E+10 | 0.132510E+10 | 0.00 | 0.00 |
April | 0.264558E+10 | 0.180021E+10 | 0.269341E+10 | 0.114034E+10 | 0.155307E+10 | 0.00 | 0.00 |
May | 0.390806E+10 | 0.121881E+10 | 0.340177E+10 | 0.119925E+10 | 0.220252E+10 | 0.00 | 0.00 |
June | 0.548790E+10 | 0.707845E+09 | 0.402636E+10 | 0.193723E+10 | 0.208913E+10 | 0.00 | 0.00 |
July | 0.463693E+10 | 0.667476E+09 | 0.338988E+10 | 0.124165E+10 | 0.214823E+10 | 0.00 | 0.00 |
August | 0.477387E+10 | 0.744299E+09 | 0.353807E+10 | 0.174785E+10 | 0.179022E+10 | 0.00 | 0.00 |
September | 0.392915E+10 | 0.106070E+10 | 0.303601E+10 | 0.145597E+10 | 0.158004E+10 | 0.00 | 0.00 |
October | 0.290890E+10 | 0.215841E+10 | 0.263923E+10 | 0.150851E+10 | 0.113071E+10 | 0.00 | 0.00 |
November | 0.210762E+10 | 0.242396E+10 | 0.209577E+10 | 0.127239E+10 | 0.823378E+09 | 0.00 | 0.00 |
December | 0.157136E+10 | 0.304880E+10 | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.392506E+11 | 0.212307E+11 | 0.338994E+11 | 0.169069E+11 | 0.169924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.157136E+10 | 0.667476E+09 | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.00 | 0.00 |
Maximum of Months | 0.548790E+10 | 0.304880E+10 | 0.402636E+10 | 0.193723E+10 | 0.220252E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.217570E+09 | 0.438615E+10 | 0.942730E+09 | 0.00 | 0.942730E+09 | 0.00 | 0.00 |
February | 0.252847E+09 | 0.399259E+10 | 0.107023E+10 | 0.00 | 0.107023E+10 | 0.00 | 0.00 |
March | 0.846292E+09 | 0.332720E+10 | 0.161226E+10 | 0.00 | 0.161226E+10 | 0.00 | 0.00 |
April | 0.120272E+10 | 0.277817E+10 | 0.195945E+10 | 10870179.82 | 0.194858E+10 | 0.00 | 0.00 |
May | 0.264187E+10 | 0.169930E+10 | 0.276595E+10 | 91431181.13 | 0.267452E+10 | 0.00 | 0.00 |
June | 0.398381E+10 | 0.924327E+09 | 0.293521E+10 | 0.325416E+09 | 0.260980E+10 | 0.00 | 0.00 |
July | 0.393659E+10 | 0.899689E+09 | 0.286845E+10 | 0.185680E+09 | 0.268277E+10 | 0.00 | 0.00 |
August | 0.298003E+10 | 0.106043E+10 | 0.228306E+10 | 54009628.00 | 0.222906E+10 | 0.00 | 0.00 |
September | 0.212086E+10 | 0.163878E+10 | 0.185591E+10 | 435920.62 | 0.185547E+10 | 0.00 | 0.00 |
October | 0.777519E+09 | 0.349563E+10 | 0.137359E+10 | 0.00 | 0.137359E+10 | 0.00 | 0.00 |
November | 0.305879E+09 | 0.397255E+10 | 0.100909E+10 | 0.00 | 0.100909E+10 | 0.00 | 0.00 |
December | 0.173659E+09 | 0.503510E+10 | 0.882042E+09 | 0.00 | 0.882042E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.194396E+11 | 0.332099E+11 | 0.215580E+11 | 0.667843E+09 | 0.208901E+11 | 0.00 | 0.00 |
Minimum of Months | 0.173659E+09 | 0.899689E+09 | 0.882042E+09 | 0.00 | 0.882042E+09 | 0.00 | 0.00 |
Maximum of Months | 0.398381E+10 | 0.503510E+10 | 0.293521E+10 | 0.325416E+09 | 0.268277E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180462E+10 | 0.278087E+10 | 0.196796E+10 | 0.120602E+10 | 0.761940E+09 | 0.00 | 0.00 |
February | 0.227882E+10 | 0.258786E+10 | 0.236123E+10 | 0.149063E+10 | 0.870601E+09 | 0.00 | 0.00 |
March | 0.327714E+10 | 0.219210E+10 | 0.315529E+10 | 0.184044E+10 | 0.131485E+10 | 0.00 | 0.00 |
April | 0.318456E+10 | 0.186205E+10 | 0.313154E+10 | 0.152542E+10 | 0.160612E+10 | 0.00 | 0.00 |
May | 0.435971E+10 | 0.118118E+10 | 0.378274E+10 | 0.158006E+10 | 0.220269E+10 | 0.00 | 0.00 |
June | 0.603941E+10 | 0.645919E+09 | 0.446645E+10 | 0.234476E+10 | 0.212170E+10 | 0.00 | 0.00 |
July | 0.572158E+10 | 0.631040E+09 | 0.419571E+10 | 0.199788E+10 | 0.219782E+10 | 0.00 | 0.00 |
August | 0.571936E+10 | 0.743953E+09 | 0.423195E+10 | 0.233079E+10 | 0.190115E+10 | 0.00 | 0.00 |
September | 0.435900E+10 | 0.108428E+10 | 0.340761E+10 | 0.185110E+10 | 0.155651E+10 | 0.00 | 0.00 |
October | 0.269512E+10 | 0.232549E+10 | 0.255005E+10 | 0.139727E+10 | 0.115278E+10 | 0.00 | 0.00 |
November | 0.182760E+10 | 0.259240E+10 | 0.192086E+10 | 0.108453E+10 | 0.836327E+09 | 0.00 | 0.00 |
December | 0.149607E+10 | 0.321134E+10 | 0.171838E+10 | 0.989904E+09 | 0.728474E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.427630E+11 | 0.218385E+11 | 0.368898E+11 | 0.196388E+11 | 0.172509E+11 | 0.00 | 0.00 |
Minimum of Months | 0.149607E+10 | 0.631040E+09 | 0.171838E+10 | 0.989904E+09 | 0.728474E+09 | 0.00 | 0.00 |
Maximum of Months | 0.603941E+10 | 0.321134E+10 | 0.446645E+10 | 0.234476E+10 | 0.220269E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104772E+11 | 0.417832E+10 | 0.903500E+10 | 0.743226E+10 | 0.160274E+10 | 0.00 | 0.00 |
February | 0.903624E+10 | 0.387024E+10 | 0.782757E+10 | 0.624064E+10 | 0.158694E+10 | 0.00 | 0.00 |
March | 0.750184E+10 | 0.336283E+10 | 0.638942E+10 | 0.420388E+10 | 0.218554E+10 | 0.00 | 0.00 |
April | 0.434000E+10 | 0.290191E+10 | 0.400477E+10 | 0.161033E+10 | 0.239444E+10 | 0.00 | 0.00 |
May | 0.448398E+10 | 0.185794E+10 | 0.379226E+10 | 0.695095E+09 | 0.309717E+10 | 0.00 | 0.00 |
June | 0.495234E+10 | 0.101756E+10 | 0.338355E+10 | 0.618419E+09 | 0.276514E+10 | 0.00 | 0.00 |
July | 0.532971E+10 | 0.976679E+09 | 0.363961E+10 | 0.651752E+09 | 0.298786E+10 | 0.00 | 0.00 |
August | 0.677624E+10 | 0.115874E+10 | 0.463396E+10 | 0.193717E+10 | 0.269679E+10 | 0.00 | 0.00 |
September | 0.788635E+10 | 0.174742E+10 | 0.576972E+10 | 0.321947E+10 | 0.255025E+10 | 0.00 | 0.00 |
October | 0.869774E+10 | 0.356965E+10 | 0.712886E+10 | 0.505809E+10 | 0.207077E+10 | 0.00 | 0.00 |
November | 0.993278E+10 | 0.392203E+10 | 0.840535E+10 | 0.670028E+10 | 0.170507E+10 | 0.00 | 0.00 |
December | 0.944490E+10 | 0.467033E+10 | 0.830563E+10 | 0.672246E+10 | 0.158317E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.888593E+11 | 0.332336E+11 | 0.723157E+11 | 0.450899E+11 | 0.272259E+11 | 0.00 | 0.00 |
Minimum of Months | 0.434000E+10 | 0.976679E+09 | 0.338355E+10 | 0.618419E+09 | 0.158317E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104772E+11 | 0.467033E+10 | 0.903500E+10 | 0.743226E+10 | 0.309717E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205775E+10 | 0.286300E+10 | 0.209348E+10 | 0.132654E+10 | 0.766941E+09 | 0.00 | 0.00 |
February | 0.222041E+10 | 0.263223E+10 | 0.228014E+10 | 0.141300E+10 | 0.867133E+09 | 0.00 | 0.00 |
March | 0.306041E+10 | 0.223123E+10 | 0.295595E+10 | 0.163086E+10 | 0.132509E+10 | 0.00 | 0.00 |
April | 0.267154E+10 | 0.190011E+10 | 0.269339E+10 | 0.114033E+10 | 0.155306E+10 | 0.00 | 0.00 |
May | 0.394580E+10 | 0.124727E+10 | 0.340174E+10 | 0.119924E+10 | 0.220251E+10 | 0.00 | 0.00 |
June | 0.552120E+10 | 0.724600E+09 | 0.402633E+10 | 0.193721E+10 | 0.208912E+10 | 0.00 | 0.00 |
July | 0.467220E+10 | 0.674380E+09 | 0.338986E+10 | 0.124164E+10 | 0.214822E+10 | 0.00 | 0.00 |
August | 0.478888E+10 | 0.779349E+09 | 0.353805E+10 | 0.174784E+10 | 0.179021E+10 | 0.00 | 0.00 |
September | 0.391644E+10 | 0.115572E+10 | 0.303599E+10 | 0.145595E+10 | 0.158004E+10 | 0.00 | 0.00 |
October | 0.288177E+10 | 0.236995E+10 | 0.263921E+10 | 0.150850E+10 | 0.113071E+10 | 0.00 | 0.00 |
November | 0.208762E+10 | 0.263065E+10 | 0.209575E+10 | 0.127237E+10 | 0.823375E+09 | 0.00 | 0.00 |
December | 0.156644E+10 | 0.323299E+10 | 0.174922E+10 | 0.103331E+10 | 0.715912E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.393905E+11 | 0.224415E+11 | 0.338991E+11 | 0.169068E+11 | 0.169923E+11 | 0.00 | 0.00 |
Minimum of Months | 0.156644E+10 | 0.674380E+09 | 0.174922E+10 | 0.103331E+10 | 0.715912E+09 | 0.00 | 0.00 |
Maximum of Months | 0.552120E+10 | 0.323299E+10 | 0.402633E+10 | 0.193721E+10 | 0.220251E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195837E+09 | 0.449461E+10 | 0.942735E+09 | 0.00 | 0.942735E+09 | 0.00 | 0.00 |
February | 0.220346E+09 | 0.411006E+10 | 0.107024E+10 | 0.00 | 0.107024E+10 | 0.00 | 0.00 |
March | 0.768664E+09 | 0.347019E+10 | 0.161227E+10 | 0.00 | 0.161227E+10 | 0.00 | 0.00 |
April | 0.111819E+10 | 0.289574E+10 | 0.195946E+10 | 10870236.15 | 0.194859E+10 | 0.00 | 0.00 |
May | 0.252713E+10 | 0.179720E+10 | 0.276597E+10 | 91431654.91 | 0.267453E+10 | 0.00 | 0.00 |
June | 0.391632E+10 | 0.971123E+09 | 0.293523E+10 | 0.325418E+09 | 0.260981E+10 | 0.00 | 0.00 |
July | 0.387304E+10 | 0.949342E+09 | 0.286846E+10 | 0.185680E+09 | 0.268278E+10 | 0.00 | 0.00 |
August | 0.294417E+10 | 0.109380E+10 | 0.228308E+10 | 54009907.87 | 0.222907E+10 | 0.00 | 0.00 |
September | 0.210959E+10 | 0.163626E+10 | 0.185592E+10 | 435922.88 | 0.185548E+10 | 0.00 | 0.00 |
October | 0.769237E+09 | 0.347002E+10 | 0.137360E+10 | 0.00 | 0.137360E+10 | 0.00 | 0.00 |
November | 0.299974E+09 | 0.396165E+10 | 0.100910E+10 | 0.00 | 0.100910E+10 | 0.00 | 0.00 |
December | 0.167207E+09 | 0.504472E+10 | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.189097E+11 | 0.338947E+11 | 0.215581E+11 | 0.667846E+09 | 0.208902E+11 | 0.00 | 0.00 |
Minimum of Months | 0.167207E+09 | 0.949342E+09 | 0.882047E+09 | 0.00 | 0.882047E+09 | 0.00 | 0.00 |
Maximum of Months | 0.391632E+10 | 0.504472E+10 | 0.293523E+10 | 0.325418E+09 | 0.268278E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.177846E+10 | 0.279880E+10 | 0.196798E+10 | 0.120603E+10 | 0.761944E+09 | 0.00 | 0.00 |
February | 0.224470E+10 | 0.261325E+10 | 0.236125E+10 | 0.149064E+10 | 0.870605E+09 | 0.00 | 0.00 |
March | 0.322908E+10 | 0.221660E+10 | 0.315532E+10 | 0.184046E+10 | 0.131485E+10 | 0.00 | 0.00 |
April | 0.313967E+10 | 0.187328E+10 | 0.313156E+10 | 0.152544E+10 | 0.160613E+10 | 0.00 | 0.00 |
May | 0.430662E+10 | 0.120157E+10 | 0.378277E+10 | 0.158007E+10 | 0.220270E+10 | 0.00 | 0.00 |
June | 0.600698E+10 | 0.647422E+09 | 0.446649E+10 | 0.234478E+10 | 0.212171E+10 | 0.00 | 0.00 |
July | 0.569173E+10 | 0.633204E+09 | 0.419574E+10 | 0.199790E+10 | 0.219784E+10 | 0.00 | 0.00 |
August | 0.570381E+10 | 0.727222E+09 | 0.423198E+10 | 0.233082E+10 | 0.190116E+10 | 0.00 | 0.00 |
September | 0.435730E+10 | 0.103969E+10 | 0.340763E+10 | 0.185112E+10 | 0.155652E+10 | 0.00 | 0.00 |
October | 0.269264E+10 | 0.224783E+10 | 0.255007E+10 | 0.139729E+10 | 0.115278E+10 | 0.00 | 0.00 |
November | 0.182368E+10 | 0.253332E+10 | 0.192087E+10 | 0.108454E+10 | 0.836331E+09 | 0.00 | 0.00 |
December | 0.148503E+10 | 0.317885E+10 | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.424597E+11 | 0.217110E+11 | 0.368900E+11 | 0.196390E+11 | 0.172510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.148503E+10 | 0.633204E+09 | 0.171839E+10 | 0.989914E+09 | 0.728478E+09 | 0.00 | 0.00 |
Maximum of Months | 0.600698E+10 | 0.317885E+10 | 0.446649E+10 | 0.234478E+10 | 0.220270E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103811E+11 | 0.410489E+10 | 0.903490E+10 | 0.743217E+10 | 0.160273E+10 | 0.00 | 0.00 |
February | 0.891112E+10 | 0.386078E+10 | 0.782749E+10 | 0.624056E+10 | 0.158693E+10 | 0.00 | 0.00 |
March | 0.737478E+10 | 0.341438E+10 | 0.638936E+10 | 0.420383E+10 | 0.218553E+10 | 0.00 | 0.00 |
April | 0.422493E+10 | 0.298053E+10 | 0.400474E+10 | 0.161032E+10 | 0.239442E+10 | 0.00 | 0.00 |
May | 0.435146E+10 | 0.196769E+10 | 0.379223E+10 | 0.695086E+09 | 0.309715E+10 | 0.00 | 0.00 |
June | 0.489055E+10 | 0.106341E+10 | 0.338353E+10 | 0.618411E+09 | 0.276512E+10 | 0.00 | 0.00 |
July | 0.527128E+10 | 0.101787E+10 | 0.363958E+10 | 0.651745E+09 | 0.298784E+10 | 0.00 | 0.00 |
August | 0.674062E+10 | 0.115366E+10 | 0.463392E+10 | 0.193715E+10 | 0.269678E+10 | 0.00 | 0.00 |
September | 0.786575E+10 | 0.167866E+10 | 0.576967E+10 | 0.321943E+10 | 0.255023E+10 | 0.00 | 0.00 |
October | 0.865783E+10 | 0.344484E+10 | 0.712879E+10 | 0.505803E+10 | 0.207076E+10 | 0.00 | 0.00 |
November | 0.986048E+10 | 0.379789E+10 | 0.840526E+10 | 0.670020E+10 | 0.170505E+10 | 0.00 | 0.00 |
December | 0.934760E+10 | 0.459099E+10 | 0.830554E+10 | 0.672238E+10 | 0.158315E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.878775E+11 | 0.330756E+11 | 0.723150E+11 | 0.450893E+11 | 0.272257E+11 | 0.00 | 0.00 |
Minimum of Months | 0.422493E+10 | 0.101787E+10 | 0.338353E+10 | 0.618411E+09 | 0.158315E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103811E+11 | 0.459099E+10 | 0.903490E+10 | 0.743217E+10 | 0.309715E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.203041E+10 | 0.288161E+10 | 0.209349E+10 | 0.132655E+10 | 0.766944E+09 | 0.00 | 0.00 |
February | 0.218644E+10 | 0.266082E+10 | 0.228015E+10 | 0.141302E+10 | 0.867136E+09 | 0.00 | 0.00 |
March | 0.301224E+10 | 0.226988E+10 | 0.295598E+10 | 0.163087E+10 | 0.132510E+10 | 0.00 | 0.00 |
April | 0.262737E+10 | 0.192816E+10 | 0.269341E+10 | 0.114034E+10 | 0.155307E+10 | 0.00 | 0.00 |
May | 0.388885E+10 | 0.128175E+10 | 0.340177E+10 | 0.119925E+10 | 0.220252E+10 | 0.00 | 0.00 |
June | 0.549291E+10 | 0.730623E+09 | 0.402636E+10 | 0.193723E+10 | 0.208913E+10 | 0.00 | 0.00 |
July | 0.464270E+10 | 0.688238E+09 | 0.338988E+10 | 0.124165E+10 | 0.214823E+10 | 0.00 | 0.00 |
August | 0.477378E+10 | 0.772439E+09 | 0.353807E+10 | 0.174785E+10 | 0.179022E+10 | 0.00 | 0.00 |
September | 0.391737E+10 | 0.111623E+10 | 0.303601E+10 | 0.145597E+10 | 0.158004E+10 | 0.00 | 0.00 |
October | 0.288541E+10 | 0.229697E+10 | 0.263923E+10 | 0.150851E+10 | 0.113071E+10 | 0.00 | 0.00 |
November | 0.208324E+10 | 0.257633E+10 | 0.209577E+10 | 0.127239E+10 | 0.823378E+09 | 0.00 | 0.00 |
December | 0.155404E+10 | 0.320114E+10 | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.390948E+11 | 0.224042E+11 | 0.338994E+11 | 0.169069E+11 | 0.169924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.155404E+10 | 0.688238E+09 | 0.174923E+10 | 0.103332E+10 | 0.715916E+09 | 0.00 | 0.00 |
Maximum of Months | 0.549291E+10 | 0.320114E+10 | 0.402636E+10 | 0.193723E+10 | 0.220252E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.548734E+10 | -0.477004E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -717306881.9 | 58.98 | 0.00 | 0.00 |
February | 0.503691E+10 | -0.438881E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -648103278.2 | 58.99 | 0.00 | 0.00 |
March | 0.582838E+10 | -0.511856E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -709819859.1 | 58.98 | 0.00 | 0.00 |
April | 0.510877E+10 | -0.442526E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -683508428.3 | 58.98 | 0.00 | 0.00 |
May | 0.517835E+10 | -0.448520E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -693158199.4 | 58.99 | 0.00 | 0.00 |
June | 0.486008E+10 | -0.419142E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668659372.6 | 58.99 | 0.00 | 0.00 |
July | 0.445805E+10 | -0.376939E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688665481.7 | 58.98 | 0.00 | 0.00 |
August | 0.479175E+10 | -0.410192E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689831724.6 | 58.98 | 0.00 | 0.00 |
September | 0.443242E+10 | -0.376482E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667598738.3 | 58.99 | 0.00 | 0.00 |
October | 0.477631E+10 | -0.407952E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -696790753.8 | 58.98 | 0.00 | 0.00 |
November | 0.494480E+10 | -0.426184E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -682955181.1 | 58.98 | 0.00 | 0.00 |
December | 0.518136E+10 | -0.446007E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -721286978.2 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.600845E+11 | -0.518168E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.826768E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.443242E+10 | -0.511856E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -721286978.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.582838E+10 | -0.376482E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -648103278.2 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:00 | 9399.41 | 37.37 | 256.83 | 263.33 | 5095.18 | 34.69 | 232.50 | 257.00 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 12764.06 | 38.85 | 241.00 | 260.50 | 2051.05 | 24.43 | 108.17 | 234.00 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:10 | 2447.71 | 17.99 | 10.33 | 323.33 | 1383.38 | 20.44 | 98.67 | 281.33 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 1829.97 | 17.71 | 0.00 | 334.17 | 1066.12 | 20.48 | 115.83 | 288.17 |
May | 415.33 | 0.51 | 0.48 | 01-MAY-06:19 | 1636.41 | 17.79 | 0.00 | 386.00 | 903.50 | 20.55 | 188.67 | 344.33 |
June | 421.50 | 0.51 | 0.48 | 01-JUN-05:00 | 1319.18 | 17.26 | 0.00 | 382.67 | 792.18 | 20.11 | 109.50 | 337.83 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:40 | 1487.93 | 17.41 | 0.00 | 387.67 | 843.51 | 20.20 | 167.67 | 345.83 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:19 | 1594.96 | 17.18 | 0.00 | 363.50 | 975.60 | 19.97 | 115.50 | 324.33 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:30 | 2637.07 | 19.06 | 29.50 | 325.83 | 1216.93 | 20.41 | 132.33 | 296.17 |
October | 262.67 | 0.49 | 0.48 | 01-OCT-06:40 | 12422.75 | 36.13 | 239.67 | 297.50 | 1708.53 | 21.06 | 98.00 | 264.50 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:39 | 10853.54 | 38.43 | 248.33 | 260.00 | 3226.78 | 29.54 | 174.50 | 238.67 |
December | 251.17 | 0.50 | 0.48 | 01-DEC-07:40 | 8778.64 | 37.56 | 233.50 | 251.33 | 7209.95 | 40.38 | 248.33 | 241.83 |
Annual Sum or Average | 3902.00 | 0.50 | 4793.34 | 24.34 | 1259.17 | 3835.83 | 1952.14 | 23.53 | 1789.67 | 3454.00 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1319.18 | 17.18 | 0.00 | 251.33 | 792.18 | 19.97 | 98.00 | 234.00 | |
Maximum of Months | 430.33 | 0.51 | 0.48 | 12764.06 | 38.85 | 256.83 | 387.67 | 7209.95 | 40.38 | 248.33 | 345.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.54 | 0.48 | 01-JAN-07:49 | 2178.26 | 19.86 | 82.50 | 224.00 | 1313.62 | 22.78 | 87.17 | 186.83 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 3496.99 | 22.23 | 84.33 | 240.17 | 2076.51 | 23.18 | 67.83 | 190.83 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-06:49 | 3169.89 | 19.61 | 68.83 | 309.17 | 1849.87 | 22.59 | 64.83 | 265.83 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 3619.83 | 20.82 | 84.83 | 334.17 | 1587.24 | 22.11 | 52.50 | 287.00 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:49 | 2881.50 | 20.73 | 111.50 | 393.33 | 1563.77 | 22.39 | 83.50 | 356.00 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 3442.76 | 20.34 | 109.00 | 394.50 | 1952.92 | 22.10 | 79.67 | 363.67 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-05:10 | 3086.20 | 20.45 | 114.17 | 397.83 | 1663.79 | 22.10 | 84.83 | 362.33 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:49 | 4219.63 | 20.77 | 116.50 | 362.67 | 1681.40 | 21.53 | 69.00 | 329.00 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-05:49 | 3480.91 | 21.22 | 105.50 | 324.83 | 1344.60 | 21.13 | 57.50 | 297.33 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:19 | 3059.38 | 20.28 | 67.67 | 278.83 | 1798.24 | 23.03 | 56.83 | 227.50 |
November | 257.67 | 0.53 | 0.48 | 01-NOV-08:39 | 2160.91 | 20.04 | 69.50 | 231.33 | 1126.31 | 21.07 | 70.33 | 188.67 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-07:49 | 2175.57 | 20.68 | 78.00 | 219.83 | 1362.38 | 23.46 | 87.17 | 178.17 |
Annual Sum or Average | 3902.00 | 0.51 | 3140.24 | 20.58 | 1092.33 | 3710.67 | 1620.81 | 22.22 | 861.17 | 3233.17 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2160.91 | 19.61 | 67.67 | 219.83 | 1126.31 | 21.07 | 52.50 | 178.17 | |
Maximum of Months | 430.33 | 0.54 | 0.48 | 4219.63 | 22.23 | 116.50 | 397.83 | 2076.51 | 23.46 | 87.17 | 363.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.56 | 0.48 | 01-JAN-09:30 | 474.16 | 12.82 | 0.00 | 197.17 | 319.09 | 16.21 | 0.00 | 94.50 |
February | 245.50 | 0.52 | 0.48 | 01-FEB-10:39 | 563.90 | 14.41 | 0.00 | 228.33 | 392.67 | 17.73 | 0.00 | 148.17 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-07:40 | 736.84 | 15.92 | 0.00 | 305.83 | 480.76 | 18.89 | 0.17 | 228.33 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 991.77 | 17.26 | 0.00 | 339.67 | 589.72 | 19.98 | 21.00 | 278.83 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1209.86 | 17.91 | 0.00 | 403.67 | 672.88 | 20.77 | 114.50 | 371.17 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:10 | 1296.32 | 18.08 | 0.00 | 413.83 | 738.58 | 23.47 | 190.00 | 399.00 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:40 | 1240.71 | 17.84 | 0.00 | 413.17 | 689.66 | 21.81 | 151.00 | 385.67 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:00 | 962.19 | 17.14 | 0.00 | 373.83 | 597.74 | 19.90 | 47.50 | 335.67 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:40 | 808.97 | 16.46 | 0.00 | 320.33 | 513.92 | 19.33 | 5.00 | 272.17 |
October | 262.67 | 0.52 | 0.48 | 01-OCT-06:00 | 684.52 | 15.63 | 0.00 | 271.17 | 465.78 | 18.77 | 0.00 | 199.33 |
November | 257.67 | 0.54 | 0.48 | 01-NOV-08:50 | 530.80 | 13.86 | 0.00 | 215.83 | 365.16 | 17.22 | 0.00 | 141.50 |
December | 251.17 | 0.55 | 0.48 | 01-DEC-08:39 | 489.23 | 13.44 | 0.00 | 203.00 | 328.00 | 16.86 | 0.00 | 105.50 |
Annual Sum or Average | 3902.00 | 0.51 | 889.34 | 16.22 | 0.00 | 3685.83 | 539.74 | 19.62 | 529.17 | 2959.83 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 474.16 | 12.82 | 0.00 | 197.17 | 319.09 | 16.21 | 0.00 | 94.50 | |
Maximum of Months | 430.33 | 0.56 | 0.48 | 1296.32 | 18.08 | 0.00 | 413.83 | 738.58 | 23.47 | 190.00 | 399.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.52 | 0.48 | 01-JAN-09:30 | 2396.23 | 20.15 | 83.33 | 238.00 | 1562.06 | 23.73 | 93.00 | 186.50 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 2660.22 | 20.54 | 68.50 | 248.50 | 1405.57 | 21.58 | 52.50 | 196.67 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:40 | 2922.76 | 19.49 | 73.83 | 320.67 | 1776.50 | 23.12 | 74.50 | 275.17 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 2925.36 | 20.45 | 85.17 | 339.50 | 1265.93 | 20.81 | 38.33 | 292.50 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-07:30 | 2469.81 | 17.13 | 53.17 | 388.83 | 1315.60 | 18.43 | 0.50 | 354.17 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-06:10 | 2996.91 | 13.99 | 1.83 | 392.83 | 1668.23 | 18.08 | 0.17 | 366.33 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:40 | 2516.58 | 16.72 | 54.83 | 398.00 | 1371.62 | 18.22 | 0.67 | 365.00 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:30 | 2531.99 | 16.70 | 53.50 | 373.17 | 1483.07 | 18.19 | 7.83 | 345.00 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-07:10 | 2928.79 | 21.27 | 109.83 | 325.83 | 1577.94 | 22.54 | 79.00 | 296.50 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-07:10 | 3801.99 | 22.81 | 92.83 | 288.50 | 1413.46 | 21.93 | 48.17 | 240.67 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:50 | 2492.20 | 20.85 | 77.17 | 242.50 | 1496.73 | 24.10 | 85.67 | 200.33 |
December | 251.17 | 0.52 | 0.48 | 01-DEC-08:39 | 2070.73 | 21.22 | 80.67 | 235.00 | 1157.56 | 22.42 | 71.83 | 185.50 |
Annual Sum or Average | 3902.00 | 0.51 | 2721.08 | 18.83 | 834.67 | 3791.33 | 1463.31 | 20.70 | 552.17 | 3304.33 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2070.73 | 13.99 | 1.83 | 235.00 | 1157.56 | 18.08 | 0.17 | 185.50 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 3801.99 | 22.81 | 109.83 | 398.00 | 1776.50 | 24.10 | 93.00 | 366.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:00 | 9184.67 | 36.94 | 256.50 | 261.83 | 4922.92 | 33.53 | 205.33 | 256.67 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 12497.34 | 37.21 | 228.50 | 256.00 | 1879.90 | 21.78 | 69.33 | 232.67 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:10 | 2339.05 | 14.25 | 9.83 | 323.33 | 1270.25 | 17.92 | 8.83 | 276.83 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 1729.74 | 14.17 | 0.00 | 331.67 | 998.02 | 18.13 | 3.67 | 283.83 |
May | 415.33 | 0.51 | 0.48 | 01-MAY-06:19 | 1558.88 | 14.23 | 0.00 | 382.83 | 856.35 | 18.15 | 0.00 | 340.67 |
June | 421.50 | 0.51 | 0.48 | 01-JUN-05:00 | 1258.21 | 13.93 | 0.00 | 379.00 | 755.55 | 17.97 | 0.00 | 333.67 |
July | 430.33 | 0.52 | 0.48 | 01-JUL-06:40 | 1418.24 | 13.91 | 0.00 | 384.00 | 801.34 | 17.86 | 0.00 | 340.50 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:19 | 1507.71 | 13.74 | 0.00 | 362.33 | 915.97 | 17.73 | 3.33 | 320.33 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:40 | 2514.72 | 15.69 | 29.50 | 323.00 | 1127.78 | 17.94 | 2.33 | 293.33 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:49 | 12237.49 | 35.71 | 239.17 | 295.83 | 1557.37 | 18.19 | 8.33 | 258.83 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:39 | 10616.41 | 38.02 | 247.17 | 258.50 | 3026.36 | 26.97 | 126.33 | 236.00 |
December | 251.17 | 0.50 | 0.48 | 01-DEC-07:49 | 8428.94 | 35.41 | 220.00 | 248.33 | 7032.47 | 40.14 | 247.00 | 240.33 |
Annual Sum or Average | 3902.00 | 0.51 | 4652.39 | 21.68 | 1230.67 | 3806.67 | 1852.83 | 21.34 | 674.50 | 3413.67 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1258.21 | 13.74 | 0.00 | 248.33 | 755.55 | 17.73 | 0.00 | 232.67 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 12497.34 | 38.02 | 256.50 | 384.00 | 7032.47 | 40.14 | 247.00 | 340.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.54 | 0.48 | 01-JAN-07:49 | 2118.66 | 19.44 | 82.50 | 221.83 | 1265.97 | 22.57 | 83.17 | 183.33 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 3083.92 | 19.66 | 66.17 | 236.33 | 2012.75 | 22.98 | 65.17 | 188.67 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-06:00 | 3061.10 | 19.08 | 67.83 | 305.50 | 1777.68 | 22.40 | 62.33 | 259.67 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 3518.28 | 20.42 | 84.83 | 332.00 | 1443.57 | 20.77 | 41.17 | 279.83 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:49 | 2682.14 | 18.64 | 84.50 | 390.50 | 1498.58 | 22.22 | 83.50 | 352.50 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 3331.82 | 19.88 | 108.00 | 392.00 | 1876.54 | 21.94 | 79.67 | 361.17 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-05:10 | 2865.46 | 18.41 | 86.67 | 395.00 | 1594.39 | 21.94 | 84.83 | 358.67 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:49 | 4114.69 | 20.38 | 116.50 | 360.50 | 1601.26 | 21.36 | 69.00 | 325.33 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-05:49 | 3393.61 | 20.81 | 105.50 | 322.50 | 1274.95 | 20.94 | 56.00 | 294.50 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:30 | 2970.53 | 19.85 | 67.67 | 276.50 | 1727.31 | 22.83 | 55.67 | 222.83 |
November | 257.67 | 0.53 | 0.48 | 01-NOV-08:39 | 2092.59 | 19.61 | 69.50 | 228.33 | 1072.81 | 20.85 | 63.00 | 185.17 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-07:49 | 2115.87 | 20.25 | 78.00 | 217.00 | 1303.08 | 23.06 | 81.50 | 173.33 |
Annual Sum or Average | 3902.00 | 0.51 | 3003.63 | 19.66 | 1017.67 | 3678.00 | 1547.63 | 21.94 | 825.00 | 3185.00 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2092.59 | 18.41 | 66.17 | 217.00 | 1072.81 | 20.77 | 41.17 | 173.33 | |
Maximum of Months | 430.33 | 0.54 | 0.48 | 4114.69 | 20.81 | 116.50 | 395.00 | 2012.75 | 23.06 | 84.83 | 361.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.57 | 0.48 | 01-JAN-09:30 | 453.92 | 9.37 | 0.00 | 190.17 | 308.91 | 13.78 | 0.00 | 86.50 |
February | 245.50 | 0.52 | 0.48 | 01-FEB-10:50 | 541.29 | 11.10 | 0.00 | 224.00 | 381.65 | 15.53 | 0.00 | 142.17 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-07:49 | 707.38 | 12.81 | 0.00 | 302.33 | 465.99 | 16.94 | 0.00 | 221.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 951.74 | 14.12 | 0.00 | 337.83 | 568.83 | 18.07 | 0.83 | 271.00 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1160.62 | 14.50 | 0.00 | 402.17 | 646.22 | 18.60 | 3.50 | 367.33 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:10 | 1245.97 | 14.74 | 0.00 | 411.83 | 710.53 | 21.73 | 70.83 | 397.17 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:40 | 1191.47 | 14.42 | 0.00 | 411.50 | 662.49 | 19.80 | 32.67 | 380.83 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 946.89 | 14.00 | 0.00 | 377.00 | 577.90 | 18.05 | 3.00 | 333.00 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:49 | 775.99 | 13.38 | 0.00 | 316.67 | 497.09 | 17.43 | 0.00 | 266.50 |
October | 262.67 | 0.52 | 0.48 | 01-OCT-07:10 | 655.66 | 12.53 | 0.00 | 267.67 | 451.34 | 16.78 | 0.00 | 193.50 |
November | 257.67 | 0.54 | 0.48 | 01-NOV-08:00 | 507.72 | 10.48 | 0.00 | 210.00 | 353.59 | 14.90 | 0.00 | 133.83 |
December | 251.17 | 0.55 | 0.48 | 01-DEC-08:50 | 466.97 | 9.96 | 0.00 | 198.50 | 316.61 | 14.41 | 0.00 | 95.67 |
Annual Sum or Average | 3902.00 | 0.52 | 855.66 | 12.94 | 0.00 | 3649.67 | 520.75 | 17.57 | 110.83 | 2889.00 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 453.92 | 9.37 | 0.00 | 190.17 | 308.91 | 13.78 | 0.00 | 86.50 | |
Maximum of Months | 430.33 | 0.57 | 0.48 | 1245.97 | 14.74 | 0.00 | 411.83 | 710.53 | 21.73 | 70.83 | 397.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.53 | 0.48 | 01-JAN-09:30 | 2335.79 | 19.81 | 83.33 | 233.83 | 1513.26 | 23.65 | 92.17 | 182.00 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 2580.62 | 20.19 | 68.50 | 245.83 | 1341.14 | 21.47 | 52.33 | 193.83 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:49 | 2841.60 | 19.11 | 73.83 | 318.50 | 1712.27 | 23.00 | 74.17 | 269.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 2844.01 | 20.08 | 85.17 | 337.50 | 1205.18 | 20.66 | 38.33 | 288.17 |
May | 415.33 | 0.51 | 0.48 | 01-MAY-07:40 | 2385.11 | 16.70 | 53.17 | 387.17 | 1256.54 | 18.26 | 0.50 | 350.67 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-06:10 | 2901.73 | 13.54 | 1.83 | 390.83 | 1600.22 | 17.90 | 0.00 | 363.50 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:40 | 2433.98 | 16.29 | 54.83 | 394.83 | 1314.33 | 18.04 | 0.50 | 360.83 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:30 | 2427.94 | 16.09 | 50.67 | 372.00 | 1420.88 | 18.02 | 7.83 | 339.67 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-07:10 | 2710.57 | 18.96 | 84.67 | 322.67 | 1517.91 | 22.41 | 78.17 | 294.33 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-07:10 | 3712.20 | 22.47 | 92.83 | 286.83 | 1343.43 | 21.82 | 48.00 | 235.50 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:50 | 2425.62 | 20.51 | 77.17 | 240.00 | 1442.68 | 24.01 | 84.67 | 197.50 |
December | 251.17 | 0.52 | 0.48 | 01-DEC-08:50 | 2009.69 | 20.90 | 80.67 | 234.17 | 1109.55 | 22.33 | 71.33 | 182.83 |
Annual Sum or Average | 3902.00 | 0.51 | 2626.35 | 18.25 | 806.67 | 3764.17 | 1403.24 | 20.56 | 548.00 | 3257.83 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2009.69 | 13.54 | 1.83 | 233.83 | 1109.55 | 17.90 | 0.00 | 182.00 | |
Maximum of Months | 430.33 | 0.53 | 0.48 | 3712.20 | 22.47 | 92.83 | 394.83 | 1712.27 | 24.01 | 92.17 | 363.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.50 | 0.48 | 01-JAN-07:00 | 9186.15 | 36.98 | 256.83 | 262.00 | 4922.86 | 33.53 | 205.33 | 256.67 |
February | 245.50 | 0.49 | 0.48 | 01-FEB-10:39 | 12561.15 | 38.65 | 241.00 | 259.00 | 1879.83 | 21.78 | 69.33 | 232.67 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:10 | 2339.53 | 14.30 | 10.33 | 323.33 | 1270.18 | 17.92 | 8.83 | 276.83 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 1729.67 | 14.17 | 0.00 | 331.67 | 997.96 | 18.13 | 3.67 | 283.83 |
May | 415.33 | 0.51 | 0.48 | 01-MAY-06:19 | 1558.81 | 14.23 | 0.00 | 382.83 | 856.28 | 18.15 | 0.00 | 340.67 |
June | 421.50 | 0.51 | 0.48 | 01-JUN-05:00 | 1258.17 | 13.93 | 0.00 | 379.00 | 755.51 | 17.97 | 0.00 | 333.67 |
July | 430.33 | 0.52 | 0.48 | 01-JUL-06:40 | 1418.19 | 13.92 | 0.00 | 384.00 | 801.28 | 17.87 | 0.00 | 340.50 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-06:19 | 1507.66 | 13.74 | 0.00 | 362.17 | 915.92 | 17.73 | 3.33 | 320.33 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:40 | 2514.66 | 15.69 | 29.50 | 323.00 | 1127.71 | 17.94 | 2.50 | 293.33 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-06:49 | 12237.47 | 35.72 | 239.17 | 295.83 | 1557.29 | 18.19 | 8.33 | 258.83 |
November | 257.67 | 0.50 | 0.48 | 01-NOV-08:39 | 10616.45 | 38.02 | 247.17 | 258.50 | 3026.29 | 26.97 | 126.33 | 236.00 |
December | 251.17 | 0.50 | 0.48 | 01-DEC-07:49 | 8429.01 | 35.41 | 220.00 | 248.33 | 7032.40 | 40.14 | 247.00 | 240.33 |
Annual Sum or Average | 3902.00 | 0.51 | 4656.52 | 21.78 | 1244.00 | 3809.67 | 1852.77 | 21.34 | 674.67 | 3413.67 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 1258.17 | 13.74 | 0.00 | 248.33 | 755.51 | 17.73 | 0.00 | 232.67 | |
Maximum of Months | 430.33 | 0.52 | 0.48 | 12561.15 | 38.65 | 256.83 | 384.00 | 7032.40 | 40.14 | 247.00 | 340.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.54 | 0.48 | 01-JAN-07:49 | 2118.67 | 19.44 | 82.50 | 221.83 | 1265.95 | 22.57 | 83.17 | 183.33 |
February | 245.50 | 0.51 | 0.48 | 01-FEB-10:39 | 3083.94 | 19.66 | 66.17 | 236.33 | 2012.73 | 22.98 | 65.17 | 188.67 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-06:00 | 3061.11 | 19.08 | 67.83 | 305.50 | 1777.65 | 22.40 | 62.33 | 259.67 |
April | 296.67 | 0.51 | 0.48 | 03-APR-09:39 | 3518.27 | 20.42 | 84.83 | 332.00 | 1443.51 | 20.77 | 41.17 | 279.83 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-05:49 | 2682.10 | 18.64 | 84.50 | 390.33 | 1498.52 | 22.23 | 83.50 | 352.50 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-04:00 | 3331.81 | 19.88 | 108.00 | 392.00 | 1876.48 | 21.94 | 79.67 | 361.17 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-05:10 | 2865.43 | 18.41 | 86.67 | 395.00 | 1594.33 | 21.94 | 84.83 | 358.67 |
August | 394.50 | 0.51 | 0.48 | 01-AUG-05:49 | 4114.69 | 20.38 | 116.50 | 360.50 | 1601.21 | 21.36 | 69.00 | 325.33 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-05:49 | 3393.61 | 20.81 | 105.50 | 322.50 | 1274.90 | 20.94 | 56.00 | 294.50 |
October | 262.67 | 0.51 | 0.48 | 01-OCT-06:30 | 2970.55 | 19.85 | 67.67 | 276.50 | 1727.27 | 22.83 | 55.67 | 222.83 |
November | 257.67 | 0.53 | 0.48 | 01-NOV-08:39 | 2092.60 | 19.61 | 69.50 | 228.33 | 1072.78 | 20.85 | 63.00 | 185.17 |
December | 251.17 | 0.53 | 0.48 | 01-DEC-07:49 | 2115.89 | 20.25 | 78.00 | 217.00 | 1303.06 | 23.06 | 81.50 | 173.33 |
Annual Sum or Average | 3902.00 | 0.51 | 3003.63 | 19.66 | 1017.67 | 3677.83 | 1547.59 | 21.94 | 825.00 | 3185.00 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2092.60 | 18.41 | 66.17 | 217.00 | 1072.78 | 20.77 | 41.17 | 173.33 | |
Maximum of Months | 430.33 | 0.54 | 0.48 | 4114.69 | 20.81 | 116.50 | 395.00 | 2012.73 | 23.06 | 84.83 | 361.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.57 | 0.48 | 01-JAN-09:30 | 453.92 | 9.38 | 0.00 | 190.17 | 308.89 | 13.78 | 0.00 | 86.33 |
February | 245.50 | 0.52 | 0.48 | 01-FEB-10:50 | 541.30 | 11.10 | 0.00 | 224.00 | 381.64 | 15.54 | 0.00 | 142.00 |
March | 296.17 | 0.51 | 0.48 | 01-MAR-07:49 | 707.38 | 12.81 | 0.00 | 302.33 | 465.97 | 16.94 | 0.00 | 221.50 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 951.73 | 14.12 | 0.00 | 337.83 | 568.80 | 18.07 | 0.83 | 271.00 |
May | 415.33 | 0.50 | 0.48 | 01-MAY-06:10 | 1160.59 | 14.50 | 0.00 | 402.17 | 646.18 | 18.60 | 3.50 | 367.33 |
June | 421.50 | 0.49 | 0.48 | 01-JUN-05:10 | 1245.97 | 14.74 | 0.00 | 411.83 | 710.50 | 21.73 | 70.83 | 397.17 |
July | 430.33 | 0.50 | 0.48 | 01-JUL-05:40 | 1191.45 | 14.42 | 0.00 | 411.50 | 662.45 | 19.80 | 32.67 | 380.83 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-05:00 | 946.89 | 14.01 | 0.00 | 377.00 | 577.87 | 18.05 | 3.00 | 333.00 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-06:49 | 775.99 | 13.38 | 0.00 | 316.67 | 497.06 | 17.43 | 0.00 | 266.50 |
October | 262.67 | 0.52 | 0.48 | 01-OCT-07:10 | 655.67 | 12.53 | 0.00 | 267.67 | 451.33 | 16.78 | 0.00 | 193.50 |
November | 257.67 | 0.54 | 0.48 | 01-NOV-08:00 | 507.73 | 10.49 | 0.00 | 210.00 | 353.58 | 14.90 | 0.00 | 133.83 |
December | 251.17 | 0.55 | 0.48 | 01-DEC-08:50 | 466.98 | 9.96 | 0.00 | 198.50 | 316.60 | 14.41 | 0.00 | 95.67 |
Annual Sum or Average | 3902.00 | 0.52 | 855.65 | 12.94 | 0.00 | 3649.67 | 520.73 | 17.57 | 110.83 | 2888.67 | ||
Minimum of Months | 245.50 | 0.49 | 0.48 | 453.92 | 9.38 | 0.00 | 190.17 | 308.89 | 13.78 | 0.00 | 86.33 | |
Maximum of Months | 430.33 | 0.57 | 0.48 | 1245.97 | 14.74 | 0.00 | 411.83 | 710.50 | 21.73 | 70.83 | 397.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.53 | 0.48 | 01-JAN-09:30 | 2335.80 | 19.81 | 83.33 | 233.83 | 1513.23 | 23.65 | 92.17 | 182.00 |
February | 245.50 | 0.50 | 0.48 | 01-FEB-10:39 | 2580.63 | 20.19 | 68.50 | 245.83 | 1341.12 | 21.48 | 52.33 | 193.83 |
March | 296.17 | 0.50 | 0.48 | 01-MAR-07:49 | 2841.61 | 19.12 | 73.83 | 318.50 | 1712.23 | 23.00 | 74.17 | 269.00 |
April | 296.67 | 0.50 | 0.48 | 03-APR-09:39 | 2843.99 | 20.08 | 85.17 | 337.50 | 1205.12 | 20.66 | 38.33 | 288.17 |
May | 415.33 | 0.51 | 0.48 | 01-MAY-07:40 | 2385.07 | 16.70 | 53.17 | 387.17 | 1256.48 | 18.26 | 0.50 | 350.67 |
June | 421.50 | 0.50 | 0.48 | 01-JUN-06:10 | 2901.72 | 13.54 | 1.83 | 390.83 | 1600.16 | 17.90 | 0.00 | 363.50 |
July | 430.33 | 0.51 | 0.48 | 01-JUL-06:40 | 2433.94 | 16.29 | 54.83 | 394.83 | 1314.27 | 18.04 | 0.50 | 360.67 |
August | 394.50 | 0.50 | 0.48 | 01-AUG-06:30 | 2427.94 | 16.09 | 50.67 | 372.00 | 1420.83 | 18.02 | 7.83 | 339.67 |
September | 354.00 | 0.51 | 0.48 | 01-SEP-07:10 | 2710.57 | 18.96 | 84.67 | 322.67 | 1517.86 | 22.42 | 78.33 | 294.33 |
October | 262.67 | 0.50 | 0.48 | 01-OCT-07:10 | 3712.21 | 22.47 | 92.83 | 286.83 | 1343.39 | 21.82 | 48.00 | 235.50 |
November | 257.67 | 0.51 | 0.48 | 01-NOV-08:50 | 2425.63 | 20.51 | 77.17 | 240.00 | 1442.65 | 24.01 | 84.67 | 197.50 |
December | 251.17 | 0.52 | 0.48 | 01-DEC-08:50 | 2009.70 | 20.90 | 80.67 | 234.17 | 1109.52 | 22.33 | 71.33 | 182.83 |
Annual Sum or Average | 3902.00 | 0.51 | 2626.34 | 18.25 | 806.67 | 3764.17 | 1403.20 | 20.56 | 548.17 | 3257.67 | ||
Minimum of Months | 245.50 | 0.50 | 0.48 | 2009.70 | 13.54 | 1.83 | 233.83 | 1109.52 | 17.90 | 0.00 | 182.00 | |
Maximum of Months | 430.33 | 0.53 | 0.48 | 3712.21 | 22.47 | 92.83 | 394.83 | 1712.23 | 24.01 | 92.17 | 363.50 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1716118.41 | 21836.01 | 06-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9476395.69 | 21836.01 | 26-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11192514.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9476395.69 | 21836.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.340177E+10 | 10571.06 | 10-JAN-17:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380750E+10 | 10522.54 | 28-FEB-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338368E+10 | 10606.81 | 17-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.248932E+10 | 10557.29 | 14-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109864E+10 | 10774.40 | 08-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 57655843.28 | 10796.86 | 09-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30694484.52 | 10553.69 | 03-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 59359653.69 | 7955.50 | 23-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252448E+09 | 10706.66 | 27-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.235472E+10 | 11445.47 | 12-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277067E+10 | 10585.99 | 10-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.421965E+10 | 10567.55 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 30694484.52 | 7955.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.421965E+10 | 11445.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.908479E+09 | 8968.23 | 30-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107415E+10 | 8956.72 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.600046E+09 | 8968.23 | 20-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.290380E+09 | 8966.23 | 25-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10978523.47 | 8920.66 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259739E+09 | 8950.51 | 25-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.420992E+09 | 8962.66 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121296E+10 | 8942.32 | 13-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.477773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121296E+10 | 8968.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.208588E+10 | 7536.52 | 30-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.230553E+10 | 7530.06 | 22-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123145E+10 | 7532.71 | 25-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.607128E+09 | 7541.48 | 25-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32801504.39 | 7516.24 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.362411E+09 | 7528.25 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.818056E+09 | 7525.37 | 24-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233081E+10 | 7561.84 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.977407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.233081E+10 | 7561.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107060E+10 | 8968.14 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119524E+10 | 8968.14 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.747507E+09 | 8968.14 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.394680E+09 | 8968.14 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24467235.13 | 8968.14 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.286384E+09 | 8968.14 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.470842E+09 | 8968.14 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135829E+10 | 8968.14 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.135829E+10 | 8968.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.337711E+09 | 23120.04 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.685508E+09 | 23120.04 | 02-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234569E+09 | 23120.04 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138853E+09 | 23120.04 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96515374.87 | 23120.04 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 95529397.87 | 23120.04 | 01-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.833428E+09 | 23120.04 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.833428E+09 | 23120.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.708930E+09 | 12066.16 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.999242E+09 | 12066.95 | 06-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.627137E+09 | 11995.47 | 20-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.384761E+09 | 12041.90 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 25590694.40 | 11889.50 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2734683.15 | 8042.32 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.523493E+09 | 11977.63 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.542415E+09 | 12009.17 | 02-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131603E+10 | 12005.48 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.513033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131603E+10 | 12066.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.969147E+09 | 9246.16 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103722E+10 | 9246.16 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.581890E+09 | 9246.16 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.332455E+09 | 9246.16 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11142395.55 | 9246.16 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2175987.73 | 7548.60 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.479999E+09 | 9246.16 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.709716E+09 | 9246.16 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160288E+10 | 9246.16 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.572662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160288E+10 | 9246.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.154438E+10 | 8549.35 | 18-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167503E+10 | 8511.83 | 07-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.784551E+09 | 8543.74 | 20-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.422942E+09 | 8550.12 | 24-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19259256.29 | 8425.68 | 01-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2287215.87 | 7193.10 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.543227E+09 | 8507.62 | 30-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100559E+10 | 8532.87 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.247124E+10 | 8532.21 | 29-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.846851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247124E+10 | 8550.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110647E+10 | 9246.07 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116695E+10 | 9246.07 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687486E+09 | 9246.07 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.403978E+09 | 9246.07 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27575897.93 | 9246.07 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5388807.21 | 9246.07 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.489583E+09 | 9246.07 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.792658E+09 | 9246.07 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173148E+10 | 9246.07 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.641158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173148E+10 | 9246.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.253054E+10 | 31678.04 | 11-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.287026E+10 | 31672.81 | 22-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152046E+10 | 31657.77 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.106157E+10 | 31712.22 | 25-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72664223.51 | 31522.79 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100463E+10 | 31565.92 | 25-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158430E+10 | 31606.26 | 20-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388764E+10 | 31530.72 | 29-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.388764E+10 | 31712.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176714E+10 | 13589.44 | 31-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216471E+10 | 13592.32 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159175E+10 | 13619.81 | 25-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110757E+10 | 13579.95 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114947E+09 | 13550.37 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 33664187.27 | 13407.75 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127651E+10 | 13613.67 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146675E+10 | 13604.62 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296829E+10 | 13568.64 | 06-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.296829E+10 | 13619.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.186127E+10 | 11051.64 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.190877E+10 | 11065.03 | 07-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.117868E+10 | 11076.68 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.722716E+09 | 11092.15 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45927058.49 | 11012.96 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21436733.67 | 10984.37 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.986151E+09 | 11084.35 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144614E+10 | 11055.51 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.291787E+10 | 11046.35 | 16-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.291787E+10 | 11092.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.331770E+10 | 9976.54 | 11-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342084E+10 | 9974.24 | 22-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195379E+10 | 9976.86 | 25-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116304E+10 | 9987.38 | 25-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94231361.75 | 9928.21 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35567839.80 | 9857.73 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139648E+10 | 9972.27 | 25-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242876E+10 | 9984.59 | 13-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.492363E+10 | 9949.94 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.492363E+10 | 9987.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.221995E+10 | 12032.64 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227645E+10 | 12032.64 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151380E+10 | 12032.64 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.978553E+09 | 12032.64 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.113537E+09 | 12032.64 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48591517.61 | 12032.64 | 22-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.113440E+10 | 12032.64 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.174103E+10 | 12032.64 | 01-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.328992E+10 | 12032.64 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.328992E+10 | 12032.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.576872E+10 | 21981.44 | 05-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.566710E+10 | 17286.09 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.331244E+10 | 13733.15 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171767E+10 | 13813.48 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66477231.74 | 5757.88 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 65528412.85 | 5698.03 | 22-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210824E+10 | 15372.64 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.394990E+10 | 17599.76 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.822099E+10 | 27355.54 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.822099E+10 | 27355.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.660812E+10 | 22833.22 | 05-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.644830E+10 | 17554.70 | 06-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409139E+10 | 14921.57 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.233625E+10 | 15254.50 | 17-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137014E+09 | 6878.02 | 02-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143302E+09 | 7262.56 | 22-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.294473E+10 | 17167.88 | 30-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.505594E+10 | 18903.05 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.932654E+10 | 27783.11 | 23-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.932654E+10 | 27783.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.726906E+10 | 25951.55 | 05-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.709231E+10 | 19071.44 | 02-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.447228E+10 | 17013.89 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.263116E+10 | 16510.17 | 17-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195488E+09 | 8569.24 | 02-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198334E+09 | 9657.01 | 22-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.354143E+10 | 18852.03 | 30-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.564640E+10 | 20770.65 | 29-NOV-21:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106263E+11 | 31213.68 | 23-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.416728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106263E+11 | 31213.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.748924E+09 | 0.748588E+09 | 20719.24 | 20-JAN-14:00 | 20719.24 | 0.00 |
February | 0.00 | 0.00 | 0.233075E+09 | 0.232223E+09 | 12042.36 | 26-FEB-12:42 | 12042.36 | 0.00 |
March | 0.00 | 0.00 | 0.282985E+10 | 0.282941E+10 | 37190.69 | 14-MAR-13:00 | 37190.69 | 0.00 |
April | 0.00 | 0.00 | 0.240328E+10 | 0.236590E+10 | 21604.31 | 20-APR-13:00 | 21604.31 | 0.00 |
May | 0.00 | 0.00 | 0.129790E+11 | 0.126662E+11 | 47049.30 | 17-MAY-13:00 | 47049.30 | 0.00 |
June | 0.00 | 0.00 | 0.512927E+11 | 0.488705E+11 | 73325.59 | 26-JUN-16:00 | 73325.59 | 0.00 |
July | 0.00 | 0.00 | 0.521544E+11 | 0.480695E+11 | 71182.60 | 17-JUL-12:07 | 71182.60 | 0.00 |
August | 0.00 | 0.00 | 0.515264E+11 | 0.488715E+11 | 68801.95 | 16-AUG-16:00 | 68801.95 | 0.00 |
September | 0.00 | 0.00 | 0.355121E+11 | 0.350354E+11 | 62444.92 | 12-SEP-16:00 | 62444.92 | 0.00 |
October | 0.00 | 0.00 | 0.619945E+10 | 0.618312E+10 | 51650.92 | 11-OCT-15:20 | 51650.92 | 0.00 |
November | 0.00 | 0.00 | 0.184056E+10 | 0.184052E+10 | 29608.24 | 07-NOV-15:00 | 29608.24 | 0.00 |
December | 0.00 | 0.00 | 0.824985E+09 | 0.824634E+09 | 19207.01 | 01-DEC-14:00 | 19207.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.218545E+12 | 0.208537E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.233075E+09 | 0.232223E+09 | 12042.36 | 12042.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.521544E+11 | 0.488715E+11 | 73325.59 | 73325.59 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.935235E+09 | 0.935195E+09 | 20510.58 | 20-JAN-14:00 | 20510.58 | 0.00 |
February | 0.00 | 0.00 | 0.355406E+09 | 0.355212E+09 | 16326.76 | 18-FEB-13:20 | 16326.76 | 0.00 |
March | 0.00 | 0.00 | 0.291280E+10 | 0.291262E+10 | 34354.71 | 13-MAR-16:00 | 34354.71 | 0.00 |
April | 0.00 | 0.00 | 0.230555E+10 | 0.227458E+10 | 21381.83 | 20-APR-13:00 | 21381.83 | 0.00 |
May | 0.00 | 0.00 | 0.124460E+11 | 0.121552E+11 | 44974.73 | 31-MAY-16:00 | 44974.73 | 0.00 |
June | 0.00 | 0.00 | 0.476538E+11 | 0.455080E+11 | 70796.77 | 26-JUN-15:20 | 70796.77 | 0.00 |
July | 0.00 | 0.00 | 0.483237E+11 | 0.447036E+11 | 68075.31 | 31-JUL-14:40 | 49305.50 | 0.00 |
August | 0.00 | 0.00 | 0.459706E+11 | 0.437014E+11 | 66784.82 | 16-AUG-15:10 | 66784.82 | 0.00 |
September | 0.00 | 0.00 | 0.303013E+11 | 0.299007E+11 | 59148.85 | 12-SEP-15:50 | 59148.85 | 0.00 |
October | 0.00 | 0.00 | 0.553179E+10 | 0.552037E+10 | 46957.58 | 11-OCT-15:00 | 46957.58 | 0.00 |
November | 0.00 | 0.00 | 0.168951E+10 | 0.168912E+10 | 26263.60 | 07-NOV-15:00 | 26263.60 | 0.00 |
December | 0.00 | 0.00 | 0.927467E+09 | 0.927415E+09 | 20050.50 | 01-DEC-14:00 | 20050.50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.199353E+12 | 0.190583E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.355406E+09 | 0.355212E+09 | 16326.76 | 16326.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.483237E+11 | 0.455080E+11 | 70796.77 | 70796.77 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.795040E+09 | 0.795025E+09 | 21979.22 | 20-JAN-14:00 | 21979.22 | 0.00 |
February | 0.00 | 0.00 | 0.279097E+09 | 0.278297E+09 | 14870.03 | 18-FEB-13:30 | 14870.03 | 0.00 |
March | 0.00 | 0.00 | 0.282668E+10 | 0.282629E+10 | 36139.09 | 13-MAR-15:50 | 36139.09 | 0.00 |
April | 0.00 | 0.00 | 0.244452E+10 | 0.240386E+10 | 23687.93 | 20-APR-13:00 | 23687.93 | 0.00 |
May | 0.00 | 0.00 | 0.132961E+11 | 0.128849E+11 | 54489.05 | 31-MAY-15:20 | 54489.05 | 0.00 |
June | 0.00 | 0.00 | 0.524128E+11 | 0.500732E+11 | 83412.49 | 26-JUN-15:10 | 83412.49 | 0.00 |
July | 0.00 | 0.00 | 0.525365E+11 | 0.487429E+11 | 76175.71 | 17-JUL-14:00 | 76175.71 | 0.00 |
August | 0.00 | 0.00 | 0.499443E+11 | 0.475631E+11 | 80142.82 | 16-AUG-15:10 | 80142.82 | 0.00 |
September | 0.00 | 0.00 | 0.313453E+11 | 0.308239E+11 | 67137.58 | 12-SEP-15:50 | 67137.58 | 0.00 |
October | 0.00 | 0.00 | 0.517102E+10 | 0.515145E+10 | 52467.02 | 11-OCT-15:00 | 52467.02 | 0.00 |
November | 0.00 | 0.00 | 0.150073E+10 | 0.149900E+10 | 25997.14 | 07-NOV-14:20 | 25997.14 | 0.00 |
December | 0.00 | 0.00 | 0.835158E+09 | 0.834880E+09 | 19347.41 | 01-DEC-14:00 | 19347.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.213387E+12 | 0.203877E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.279097E+09 | 0.278297E+09 | 14870.03 | 14870.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.525365E+11 | 0.500732E+11 | 83412.49 | 83412.49 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1933.81 | 6793.02 | 30-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1967.07 | 6813.29 | 15-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2067.13 | 6785.84 | 01-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1859.81 | 6571.31 | 03-APR-11:13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1829.29 | 6243.89 | 02-MAY-11:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1773.32 | 5873.70 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1558.71 | 5564.38 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1688.27 | 5416.76 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1605.57 | 5583.40 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1676.21 | 5957.22 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1798.14 | 6298.69 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1816.31 | 6604.73 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1796.83 | ||||
Minimum of Months | 0.00 | 0.00 | 1558.71 | 5416.76 | ||
Maximum of Months | 0.00 | 0.00 | 2067.13 | 6813.29 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165267E+10 | 0.35 | 3142.45 | 24-JAN-16:10 | 0.96 |
February | 0.151432E+10 | 0.35 | 3012.89 | 23-FEB-08:03 | 0.94 |
March | 0.212731E+10 | 0.39 | 5618.10 | 15-MAR-15:40 | 1.35 |
April | 0.178575E+10 | 0.36 | 3008.64 | 12-APR-12:08 | 0.94 |
May | 0.297550E+10 | 0.42 | 5744.97 | 17-MAY-13:00 | 1.36 |
June | 0.616932E+10 | 0.66 | 12323.34 | 26-JUN-12:07 | 2.18 |
July | 0.584638E+10 | 0.62 | 12105.01 | 24-JUL-12:10 | 2.15 |
August | 0.611870E+10 | 0.64 | 10713.62 | 18-AUG-12:07 | 2.00 |
September | 0.490579E+10 | 0.58 | 10171.03 | 06-SEP-12:10 | 1.94 |
October | 0.280405E+10 | 0.42 | 6133.89 | 11-OCT-16:30 | 1.42 |
November | 0.193889E+10 | 0.37 | 4179.92 | 07-NOV-16:30 | 1.13 |
December | 0.161579E+10 | 0.34 | 2888.89 | 26-DEC-07:02 | 0.92 |
Annual Sum or Average | 0.394545E+11 | 0.46 | |||
Minimum of Months | 0.151432E+10 | 0.34 | 2888.89 | 0.92 | |
Maximum of Months | 0.616932E+10 | 0.66 | 12323.34 | 2.18 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.171023E+10 | 0.37 | 3020.33 | 02-JAN-06:01 | 1.03 |
February | 0.161838E+10 | 0.38 | 3020.33 | 02-FEB-07:01 | 1.03 |
March | 0.209672E+10 | 0.42 | 6605.71 | 15-MAR-16:00 | 1.64 |
April | 0.172771E+10 | 0.38 | 3959.83 | 21-APR-13:30 | 1.20 |
May | 0.283573E+10 | 0.46 | 6662.39 | 18-MAY-14:30 | 1.63 |
June | 0.626078E+10 | 0.72 | 11019.13 | 30-JUN-15:10 | 2.24 |
July | 0.588838E+10 | 0.67 | 11440.11 | 17-JUL-10:20 | 2.29 |
August | 0.598548E+10 | 0.68 | 11005.66 | 11-AUG-15:10 | 2.24 |
September | 0.433213E+10 | 0.58 | 10681.91 | 05-SEP-15:40 | 2.19 |
October | 0.225404E+10 | 0.42 | 6789.87 | 10-OCT-16:00 | 1.66 |
November | 0.176993E+10 | 0.38 | 3522.32 | 07-NOV-15:50 | 1.12 |
December | 0.169761E+10 | 0.38 | 3020.33 | 11-DEC-06:01 | 1.03 |
Annual Sum or Average | 0.381771E+11 | 0.49 | |||
Minimum of Months | 0.161838E+10 | 0.37 | 3020.33 | 1.03 | |
Maximum of Months | 0.626078E+10 | 0.72 | 11440.11 | 2.29 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177518E+10 | 0.37 | 2871.80 | 02-JAN-05:01 | 0.89 |
February | 0.172183E+10 | 0.40 | 2871.80 | 01-FEB-06:01 | 0.89 |
March | 0.206876E+10 | 0.41 | 5959.69 | 15-MAR-15:50 | 1.36 |
April | 0.171159E+10 | 0.36 | 3904.85 | 21-APR-13:30 | 1.06 |
May | 0.250188E+10 | 0.40 | 6255.11 | 31-MAY-15:40 | 1.38 |
June | 0.567494E+10 | 0.61 | 11244.15 | 26-JUN-15:10 | 2.00 |
July | 0.524610E+10 | 0.57 | 11193.41 | 24-JUL-15:30 | 1.98 |
August | 0.530521E+10 | 0.57 | 11414.93 | 11-AUG-15:10 | 2.02 |
September | 0.361830E+10 | 0.48 | 9532.68 | 12-SEP-15:50 | 1.80 |
October | 0.202389E+10 | 0.38 | 6419.52 | 11-OCT-16:00 | 1.42 |
November | 0.168222E+10 | 0.36 | 2871.80 | 01-NOV-05:01 | 0.89 |
December | 0.190502E+10 | 0.40 | 2871.80 | 05-DEC-07:01 | 0.89 |
Annual Sum or Average | 0.352349E+11 | 0.44 | |||
Minimum of Months | 0.168222E+10 | 0.36 | 2871.80 | 0.89 | |
Maximum of Months | 0.567494E+10 | 0.61 | 11414.93 | 2.02 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:05 | 0.22 | 0.22 | 56.61 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 55.54 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 56.37 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:05 | 0.22 | 0.22 | 55.14 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:01 | 0.22 | 0.22 | 56.52 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 56.01 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 56.23 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 56.10 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 56.78 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.51 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:01 | 0.22 | 0.22 | 56.76 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 56.82 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.14 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.51 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.50 | 57.50 | 1933.81 | 6793.02 | 30-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.99 | 55.99 | 1967.07 | 6813.29 | 15-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.06 | 57.06 | 2067.13 | 6785.84 | 01-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.80 | 55.80 | 1859.81 | 6571.31 | 03-APR-11:13 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.02 | 57.02 | 1829.29 | 6243.89 | 02-MAY-11:07 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.37 | 57.37 | 1773.32 | 5873.70 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.52 | 57.52 | 1558.71 | 5564.38 | 03-JUL-11:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.50 | 56.50 | 1688.27 | 5416.76 | 31-AUG-11:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.15 | 57.15 | 1605.57 | 5583.40 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.34 | 55.34 | 1676.21 | 5957.22 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.17 | 57.17 | 1798.14 | 6298.69 | 29-NOV-12:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.21 | 57.21 | 1816.31 | 6604.73 | 29-DEC-12:07 |
Annual Sum or Average | 0.00 | 1796.83 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.34 | 55.34 | 1558.71 | 5416.76 | ||
Maximum of Months | 0.00 | 0.00 | 57.52 | 57.52 | 2067.13 | 6813.29 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.930944E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.996014E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.876893E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.618059E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.725401E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.191791E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.188459E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.189364E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.136743E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.753954E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.686706E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.109587E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.137474E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.618059E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.191791E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.660967E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.727449E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.570814E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.399543E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.589138E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.182775E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.179036E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.173886E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.116370E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.570343E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.532968E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.988700E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.115606E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.399543E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.182775E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.136737E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.144362E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.105108E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.736907E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.615019E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.190124E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.184414E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.178251E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.113966E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.907554E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.107248E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.201075E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.158723E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.615019E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.201075E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165267E+10 | 0.748924E+09 | 0.132354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151432E+10 | 0.233075E+09 | 0.140512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212731E+10 | 0.282985E+10 | 0.927511E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178575E+10 | 0.240328E+10 | 0.549917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.297550E+10 | 0.129790E+11 | 0.123337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.616932E+10 | 0.512927E+11 | 57655843.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.584638E+10 | 0.521544E+11 | 30694484.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.611870E+10 | 0.515264E+11 | 59359653.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.490579E+10 | 0.355121E+11 | 0.317976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280405E+10 | 0.619945E+10 | 0.537149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193889E+10 | 0.184056E+10 | 0.843046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161579E+10 | 0.824985E+09 | 0.173522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394545E+11 | 0.218545E+12 | 0.749142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151432E+10 | 0.233075E+09 | 30694484.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.616932E+10 | 0.521544E+11 | 0.173522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.171023E+10 | 0.935235E+09 | 0.112748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161838E+10 | 0.355406E+09 | 0.120123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209672E+10 | 0.291280E+10 | 0.700702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172771E+10 | 0.230555E+10 | 0.401924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283573E+10 | 0.124460E+11 | 0.220582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.626078E+10 | 0.476538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.588838E+10 | 0.483237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.598548E+10 | 0.459706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.433213E+10 | 0.303013E+11 | 0.155889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.225404E+10 | 0.553179E+10 | 0.507754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176993E+10 | 0.168951E+10 | 0.820184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169761E+10 | 0.927467E+09 | 0.172816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.381771E+11 | 0.199353E+12 | 0.652508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161838E+10 | 0.355406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.626078E+10 | 0.483237E+11 | 0.172816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.177518E+10 | 0.795040E+09 | 0.189656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172183E+10 | 0.279097E+09 | 0.197333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206876E+10 | 0.282668E+10 | 0.122308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171159E+10 | 0.244452E+10 | 0.766461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.250188E+10 | 0.132961E+11 | 0.636794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.567494E+10 | 0.524128E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.524610E+10 | 0.525365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.530521E+10 | 0.499443E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.361830E+10 | 0.313453E+11 | 0.337594E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202389E+10 | 0.517102E+10 | 0.933960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168222E+10 | 0.150073E+10 | 0.143134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190502E+10 | 0.835158E+09 | 0.286137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352349E+11 | 0.213387E+12 | 0.111835E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.168222E+10 | 0.279097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.567494E+10 | 0.525365E+11 | 0.286137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165267E+10 | 0.00 | 0.00 | 0.00 | 0.190038E+09 | 0.746673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151432E+10 | 0.00 | 0.00 | 0.00 | 61679989.91 | 0.838414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212731E+10 | 0.00 | 0.00 | 0.00 | 0.678946E+09 | 0.596268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178575E+10 | 0.00 | 0.00 | 0.00 | 0.613332E+09 | 0.378151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.297550E+10 | 0.00 | 0.00 | 0.00 | 0.311162E+10 | 0.116689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.616932E+10 | 0.00 | 0.00 | 0.00 | 0.129521E+11 | 57655843.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.584638E+10 | 0.00 | 0.00 | 0.00 | 0.129689E+11 | 30694484.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.611870E+10 | 0.00 | 0.00 | 0.00 | 0.127583E+11 | 59359653.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.490579E+10 | 0.00 | 0.00 | 0.00 | 0.851604E+10 | 0.252448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280405E+10 | 0.00 | 0.00 | 0.00 | 0.147224E+10 | 0.326325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193889E+10 | 0.00 | 0.00 | 0.00 | 0.447611E+09 | 0.448056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161579E+10 | 0.00 | 0.00 | 0.00 | 0.211736E+09 | 0.913120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.394545E+11 | 0.00 | 0.00 | 0.00 | 0.539825E+11 | 0.440371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151432E+10 | 0.00 | 0.00 | 0.00 | 61679989.91 | 30694484.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.616932E+10 | 0.00 | 0.00 | 0.00 | 0.129689E+11 | 0.913120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.171023E+10 | 0.00 | 0.00 | 0.00 | 0.232802E+09 | 0.466664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161838E+10 | 0.00 | 0.00 | 0.00 | 92156602.05 | 0.556395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.209672E+10 | 0.00 | 0.00 | 0.00 | 0.695785E+09 | 0.291563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172771E+10 | 0.00 | 0.00 | 0.00 | 0.584735E+09 | 0.168299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283573E+10 | 0.00 | 0.00 | 0.00 | 0.297209E+10 | 83568244.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.626078E+10 | 0.00 | 0.00 | 0.00 | 0.120167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.588838E+10 | 0.00 | 0.00 | 0.00 | 0.120152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.598548E+10 | 0.00 | 0.00 | 0.00 | 0.114032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.433213E+10 | 0.00 | 0.00 | 0.00 | 0.729230E+10 | 12586693.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.225404E+10 | 0.00 | 0.00 | 0.00 | 0.131657E+10 | 0.213282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.176993E+10 | 0.00 | 0.00 | 0.00 | 0.413837E+09 | 0.314591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169761E+10 | 0.00 | 0.00 | 0.00 | 0.234321E+09 | 0.795507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.381771E+11 | 0.00 | 0.00 | 0.00 | 0.492697E+11 | 0.281592E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161838E+10 | 0.00 | 0.00 | 0.00 | 92156602.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.626078E+10 | 0.00 | 0.00 | 0.00 | 0.120167E+11 | 0.795507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.177518E+10 | 0.00 | 0.00 | 0.00 | 0.201974E+09 | 0.116966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.172183E+10 | 0.00 | 0.00 | 0.00 | 73303852.17 | 0.126410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206876E+10 | 0.00 | 0.00 | 0.00 | 0.683527E+09 | 0.775848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171159E+10 | 0.00 | 0.00 | 0.00 | 0.624027E+09 | 0.503345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.250188E+10 | 0.00 | 0.00 | 0.00 | 0.320701E+10 | 0.441307E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.567494E+10 | 0.00 | 0.00 | 0.00 | 0.133375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.524610E+10 | 0.00 | 0.00 | 0.00 | 0.131953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.530521E+10 | 0.00 | 0.00 | 0.00 | 0.125199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.361830E+10 | 0.00 | 0.00 | 0.00 | 0.763904E+10 | 0.139260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202389E+10 | 0.00 | 0.00 | 0.00 | 0.125349E+10 | 0.579817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168222E+10 | 0.00 | 0.00 | 0.00 | 0.375641E+09 | 0.866698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190502E+10 | 0.00 | 0.00 | 0.00 | 0.215123E+09 | 0.179874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.352349E+11 | 0.00 | 0.00 | 0.00 | 0.533258E+11 | 0.701626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.168222E+10 | 0.00 | 0.00 | 0.00 | 73303852.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.567494E+10 | 0.00 | 0.00 | 0.00 | 0.133375E+11 | 0.179874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.539028E+10 | 0.00 | 0.00 | 18939654.48 | 0.00 | 0.00 | 0.983055E+10 | 0.00 | 0.41 |
February | 0.566960E+10 | 0.00 | 0.00 | 17552604.62 | 0.00 | 1129636.29 | 0.849145E+10 | 0.00 | 0.38 |
March | 0.350629E+10 | 0.00 | 0.00 | 27360737.39 | 0.00 | 0.00 | 0.135848E+11 | 0.00 | 0.60 |
April | 0.233420E+10 | 0.00 | 0.00 | 24439455.97 | 0.00 | 0.00 | 0.121556E+11 | 0.00 | 0.58 |
May | 0.770589E+09 | 2797360.50 | 0.00 | 37774996.67 | 4749289.79 | 0.00 | 0.157038E+11 | 0.00 | 0.95 |
June | 0.542324E+09 | 0.508129E+09 | 0.00 | 29487770.10 | 99379374.69 | 0.00 | 0.555150E+10 | 0.00 | 0.84 |
July | 0.415324E+09 | 0.648984E+09 | 0.00 | 26116823.70 | 0.152182E+09 | 0.00 | 0.402598E+10 | 0.00 | 0.78 |
August | 0.606406E+09 | 0.503499E+09 | 0.00 | 38185926.98 | 48884213.43 | 0.00 | 0.735901E+10 | 0.00 | 0.90 |
September | 0.676865E+09 | 62996072.71 | 0.00 | 41041313.31 | 28368616.47 | 0.00 | 0.106308E+11 | 0.00 | 0.97 |
October | 0.227343E+10 | 0.00 | 0.00 | 37780496.47 | 0.00 | 0.00 | 0.171520E+11 | 0.00 | 0.75 |
November | 0.343165E+10 | 0.00 | 0.00 | 28749415.17 | 0.00 | 0.00 | 0.131736E+11 | 0.00 | 0.52 |
December | 0.668071E+10 | 0.00 | 0.00 | 16926686.43 | 0.00 | 2215743.69 | 0.873638E+10 | 0.00 | 0.37 |
Annual Sum or Average | 0.322977E+11 | 0.172641E+10 | 0.00 | 0.344356E+09 | 0.333564E+09 | 3345379.98 | 0.126395E+12 | 0.00 | 0.67 |
Minimum of Months | 0.415324E+09 | 0.00 | 0.00 | 16926686.43 | 0.00 | 0.00 | 0.402598E+10 | 0.00 | 0.37 |
Maximum of Months | 0.668071E+10 | 0.648984E+09 | 0.00 | 41041313.31 | 0.152182E+09 | 2215743.69 | 0.171520E+11 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107248E+11 | 0.00 | 0.00 | 905124.92 | 0.00 | 0.193660E+09 | 0.106747E+10 | 0.00 | 0.31 |
February | 0.961901E+10 | 0.00 | 0.00 | 909238.29 | 0.00 | 0.510808E+09 | 0.107031E+10 | 0.00 | 0.30 |
March | 0.868721E+10 | 0.00 | 0.00 | 5646832.21 | 0.00 | 87804545.40 | 0.362272E+10 | 0.00 | 0.42 |
April | 0.705478E+10 | 0.00 | 0.00 | 5087654.67 | 0.00 | 96179536.09 | 0.329285E+10 | 0.00 | 0.40 |
May | 0.262515E+10 | 23614.95 | 0.00 | 17507231.30 | 6404430.66 | 0.00 | 0.807868E+10 | 0.00 | 0.62 |
June | 0.626514E+09 | 0.331392E+09 | 0.00 | 20520694.47 | 82102474.17 | 0.00 | 0.360640E+10 | 0.00 | 0.60 |
July | 0.500954E+09 | 0.449375E+09 | 0.00 | 18041141.94 | 0.144125E+09 | 0.00 | 0.266128E+10 | 0.00 | 0.56 |
August | 0.679892E+09 | 0.339273E+09 | 0.00 | 25688169.94 | 39899528.10 | 0.00 | 0.467817E+10 | 0.00 | 0.62 |
September | 0.114832E+10 | 43143103.00 | 0.00 | 23553142.74 | 37119467.07 | 0.00 | 0.604531E+10 | 0.00 | 0.63 |
October | 0.648477E+10 | 0.00 | 0.00 | 10120137.95 | 0.00 | 72953489.92 | 0.551638E+10 | 0.00 | 0.46 |
November | 0.937753E+10 | 0.00 | 0.00 | 3169506.00 | 0.00 | 60229483.65 | 0.221757E+10 | 0.00 | 0.35 |
December | 0.115467E+11 | 0.00 | 0.00 | 353871.88 | 0.00 | 0.665333E+09 | 0.473622E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.690757E+11 | 0.116321E+10 | 0.00 | 0.131503E+09 | 0.309651E+09 | 0.168697E+10 | 0.423308E+11 | 0.00 | 0.46 |
Minimum of Months | 0.500954E+09 | 0.00 | 0.00 | 353871.88 | 0.00 | 0.00 | 0.473622E+09 | 0.00 | 0.30 |
Maximum of Months | 0.115467E+11 | 0.449375E+09 | 0.00 | 25688169.94 | 0.144125E+09 | 0.665333E+09 | 0.807868E+10 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.914453E+10 | 0.00 | 0.00 | 368662.55 | 0.00 | 0.159018E+10 | 0.497219E+09 | 0.00 | 0.30 |
February | 0.826885E+10 | 0.00 | 0.00 | 309091.32 | 0.00 | 0.181897E+10 | 0.541918E+09 | 0.00 | 0.29 |
March | 0.858910E+10 | 0.00 | 0.00 | 3936168.52 | 0.00 | 0.708388E+09 | 0.268123E+10 | 0.00 | 0.41 |
April | 0.710039E+10 | 0.00 | 0.00 | 3610828.44 | 0.00 | 0.564367E+09 | 0.269434E+10 | 0.00 | 0.40 |
May | 0.342611E+10 | 87971.31 | 0.00 | 15098564.14 | 1493454.93 | 34056921.68 | 0.707488E+10 | 0.00 | 0.63 |
June | 0.904618E+09 | 0.237131E+09 | 0.00 | 21269486.36 | 77920095.83 | 0.00 | 0.321701E+10 | 0.00 | 0.64 |
July | 0.639999E+09 | 0.324363E+09 | 0.00 | 18597121.46 | 0.129234E+09 | 0.00 | 0.224026E+10 | 0.00 | 0.58 |
August | 0.934162E+09 | 0.267595E+09 | 0.00 | 24061280.13 | 34126776.63 | 0.00 | 0.396893E+10 | 0.00 | 0.62 |
September | 0.191414E+10 | 27822979.12 | 0.00 | 18979091.68 | 25147393.20 | 0.00 | 0.455441E+10 | 0.00 | 0.62 |
October | 0.694700E+10 | 0.00 | 0.00 | 4870730.54 | 0.00 | 0.804674E+09 | 0.328646E+10 | 0.00 | 0.44 |
November | 0.893690E+10 | 0.00 | 0.00 | 1225532.43 | 0.00 | 0.899395E+09 | 0.103177E+10 | 0.00 | 0.33 |
December | 0.862845E+10 | 0.00 | 0.00 | 20613.49 | 0.00 | 0.295804E+10 | 0.110264E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.654342E+11 | 0.857001E+09 | 0.00 | 0.112347E+09 | 0.267921E+09 | 0.937808E+10 | 0.318987E+11 | 0.00 | 0.46 |
Minimum of Months | 0.639999E+09 | 0.00 | 0.00 | 20613.49 | 0.00 | 0.00 | 0.110264E+09 | 0.00 | 0.29 |
Maximum of Months | 0.914453E+10 | 0.324363E+09 | 0.00 | 24061280.13 | 0.129234E+09 | 0.295804E+10 | 0.707488E+10 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.919170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164718E+10 | 0.00 | 0.00 | 0.32 |
February | 0.897055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151315E+10 | 0.00 | 0.00 | 0.31 |
March | 0.130525E+10 | 0.00 | 0.00 | 518332.54 | 0.00 | 0.945932E+09 | 0.301475E+09 | 0.00 | 0.41 |
April | 0.123733E+10 | 0.00 | 0.00 | 735672.39 | 0.00 | 0.560414E+09 | 0.448409E+09 | 0.00 | 0.42 |
May | 0.872879E+09 | 37989.88 | 0.00 | 3821347.06 | 315088.15 | 33168246.15 | 0.149427E+10 | 0.00 | 0.72 |
June | 0.203928E+09 | 92517887.71 | 0.00 | 6601297.76 | 13340292.44 | 0.00 | 0.847811E+09 | 0.00 | 0.87 |
July | 0.152921E+09 | 0.121847E+09 | 0.00 | 5484119.61 | 22701117.79 | 0.00 | 0.565334E+09 | 0.00 | 0.77 |
August | 0.274344E+09 | 92617590.11 | 0.00 | 6342600.66 | 6651799.88 | 0.00 | 0.862259E+09 | 0.00 | 0.74 |
September | 0.549955E+09 | 12133861.13 | 0.00 | 4442457.74 | 3938551.60 | 16649708.12 | 0.841001E+09 | 0.00 | 0.67 |
October | 0.136220E+10 | 0.00 | 0.00 | 560764.38 | 0.00 | 0.699303E+09 | 0.304840E+09 | 0.00 | 0.44 |
November | 0.994899E+09 | 0.00 | 0.00 | 107678.06 | 0.00 | 0.131685E+10 | 79161575.92 | 0.00 | 0.34 |
December | 0.658342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232911E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.942827E+10 | 0.319154E+09 | 0.00 | 28614270.21 | 46946849.87 | 0.906176E+10 | 0.574456E+10 | 0.00 | 0.53 |
Minimum of Months | 0.152921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.136220E+10 | 0.121847E+09 | 0.00 | 6601297.76 | 22701117.79 | 0.232911E+10 | 0.149427E+10 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132091E+10 | 0.00 | 0.00 | 92568.41 | 0.00 | 0.112666E+10 | 91137688.48 | 0.00 | 0.51 |
February | 0.122828E+10 | 0.00 | 0.00 | 375653.53 | 0.00 | 0.960683E+09 | 0.243758E+09 | 0.00 | 0.50 |
March | 0.118233E+10 | 0.00 | 0.00 | 2058054.93 | 0.00 | 0.695208E+09 | 0.113921E+10 | 0.00 | 0.80 |
April | 0.101686E+10 | 0.00 | 0.00 | 2298036.47 | 0.00 | 0.437253E+09 | 0.130393E+10 | 0.00 | 0.84 |
May | 0.748407E+09 | 31849.01 | 0.00 | 5030799.24 | 334031.23 | 14789610.28 | 0.212164E+10 | 0.00 | 1.34 |
June | 0.147770E+09 | 76587972.81 | 0.00 | 8468770.55 | 10403755.66 | 0.00 | 0.134528E+10 | 0.00 | 1.66 |
July | 0.132965E+09 | 0.114228E+09 | 0.00 | 7015983.34 | 16004582.21 | 0.00 | 0.714799E+09 | 0.00 | 1.33 |
August | 0.201126E+09 | 81291794.75 | 0.00 | 8921884.66 | 6705640.96 | 0.00 | 0.156655E+10 | 0.00 | 1.57 |
September | 0.486693E+09 | 11609763.86 | 0.00 | 6196177.17 | 4131967.65 | 12122650.74 | 0.134602E+10 | 0.00 | 1.37 |
October | 0.107979E+10 | 0.00 | 0.00 | 1818389.86 | 0.00 | 0.611953E+09 | 0.958905E+09 | 0.00 | 0.80 |
November | 0.126926E+10 | 0.00 | 0.00 | 416087.98 | 0.00 | 0.909386E+09 | 0.277649E+09 | 0.00 | 0.56 |
December | 0.107123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162284E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.988561E+10 | 0.283749E+09 | 0.00 | 42692406.14 | 37579977.72 | 0.639090E+10 | 0.111089E+11 | 0.00 | 0.98 |
Minimum of Months | 0.132965E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.132091E+10 | 0.114228E+09 | 0.00 | 8921884.66 | 16004582.21 | 0.162284E+10 | 0.212164E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104465E+10 | 0.00 | 0.00 | 6437357.95 | 0.00 | 0.962450E+09 | 0.312651E+10 | 0.00 | 0.77 |
February | 0.100336E+10 | 0.00 | 0.00 | 7066181.39 | 0.00 | 0.854216E+09 | 0.327135E+10 | 0.00 | 0.74 |
March | 0.110863E+10 | 0.00 | 0.00 | 7399951.13 | 0.00 | 0.791172E+09 | 0.357596E+10 | 0.00 | 1.03 |
April | 0.122628E+10 | 0.00 | 0.00 | 3981152.41 | 0.00 | 0.534340E+09 | 0.213810E+10 | 0.00 | 0.79 |
May | 0.104852E+10 | 64774.61 | 0.00 | 5902755.37 | 407727.80 | 43694882.38 | 0.236503E+10 | 0.00 | 1.04 |
June | 0.341619E+09 | 0.105802E+09 | 0.00 | 7259072.86 | 16098630.48 | 0.00 | 0.895052E+09 | 0.00 | 1.01 |
July | 0.236636E+09 | 0.172179E+09 | 0.00 | 6275152.42 | 15946875.78 | 0.00 | 0.619983E+09 | 0.00 | 0.92 |
August | 0.355887E+09 | 0.135370E+09 | 0.00 | 10459245.12 | 7745494.14 | 0.00 | 0.134785E+10 | 0.00 | 1.09 |
September | 0.502574E+09 | 25593680.37 | 0.00 | 11075358.51 | 4374820.80 | 20453914.51 | 0.212477E+10 | 0.00 | 1.32 |
October | 0.874257E+09 | 0.00 | 0.00 | 10786487.51 | 0.00 | 0.717087E+09 | 0.429644E+10 | 0.00 | 1.28 |
November | 0.987930E+09 | 0.00 | 0.00 | 7745137.41 | 0.00 | 0.824460E+09 | 0.345770E+10 | 0.00 | 0.91 |
December | 0.116981E+10 | 0.00 | 0.00 | 5169495.92 | 0.00 | 0.140233E+10 | 0.214590E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.990014E+10 | 0.439009E+09 | 0.00 | 89557348.01 | 44573549.00 | 0.615021E+10 | 0.293646E+11 | 0.00 | 0.97 |
Minimum of Months | 0.236636E+09 | 0.00 | 0.00 | 3981152.41 | 0.00 | 0.00 | 0.619983E+09 | 0.00 | 0.68 |
Maximum of Months | 0.122628E+10 | 0.172179E+09 | 0.00 | 11075358.51 | 16098630.48 | 0.140233E+10 | 0.429644E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120989E+10 | 0.00 | 0.00 | 423062.97 | 0.00 | 0.148309E+10 | 0.341866E+09 | 0.00 | 0.62 |
February | 0.118577E+10 | 0.00 | 0.00 | 731790.51 | 0.00 | 0.130191E+10 | 0.474648E+09 | 0.00 | 0.61 |
March | 0.149942E+10 | 0.00 | 0.00 | 2221060.71 | 0.00 | 0.948764E+09 | 0.112859E+10 | 0.00 | 0.98 |
April | 0.141851E+10 | 0.00 | 0.00 | 1955538.10 | 0.00 | 0.570717E+09 | 0.108196E+10 | 0.00 | 0.93 |
May | 0.116960E+10 | 44341.80 | 0.00 | 4141896.60 | 393098.03 | 43780387.73 | 0.166320E+10 | 0.00 | 1.36 |
June | 0.350042E+09 | 0.112410E+09 | 0.00 | 5998918.20 | 9199071.90 | 0.00 | 0.642592E+09 | 0.00 | 1.32 |
July | 0.259326E+09 | 0.122685E+09 | 0.00 | 4269321.50 | 22976157.61 | 0.00 | 0.440048E+09 | 0.00 | 1.15 |
August | 0.400534E+09 | 0.100408E+09 | 0.00 | 6493210.13 | 7510723.66 | 0.00 | 0.713055E+09 | 0.00 | 1.19 |
September | 0.694626E+09 | 15652027.75 | 0.00 | 4909276.61 | 3259555.85 | 23017722.28 | 0.969778E+09 | 0.00 | 1.26 |
October | 0.145413E+10 | 0.00 | 0.00 | 2517528.83 | 0.00 | 0.740104E+09 | 0.111042E+10 | 0.00 | 1.03 |
November | 0.129591E+10 | 0.00 | 0.00 | 708315.07 | 0.00 | 0.120972E+10 | 0.466579E+09 | 0.00 | 0.70 |
December | 0.101229E+10 | 0.00 | 0.00 | 201483.38 | 0.00 | 0.198113E+10 | 0.151365E+09 | 0.00 | 0.59 |
Annual Sum or Average | 0.119500E+11 | 0.351200E+09 | 0.00 | 34571402.62 | 43338607.05 | 0.830224E+10 | 0.918410E+10 | 0.00 | 0.98 |
Minimum of Months | 0.259326E+09 | 0.00 | 0.00 | 201483.38 | 0.00 | 0.00 | 0.151365E+09 | 0.00 | 0.59 |
Maximum of Months | 0.149942E+10 | 0.122685E+09 | 0.00 | 6493210.13 | 22976157.61 | 0.198113E+10 | 0.166320E+10 | 0.00 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161243E+10 | 0.00 | 0.00 | 0.32 |
February | 0.912851E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161092E+10 | 0.00 | 0.00 | 0.31 |
March | 0.152733E+10 | 0.00 | 0.00 | 63038.09 | 0.00 | 0.988494E+09 | 45144860.89 | 0.00 | 0.39 |
April | 0.169042E+10 | 0.00 | 0.00 | 33008.97 | 0.00 | 0.416705E+09 | 64418265.13 | 0.00 | 0.38 |
May | 0.112668E+10 | 470190.62 | 0.00 | 1821693.91 | 1046072.11 | 18411540.76 | 0.737226E+09 | 0.00 | 0.53 |
June | 0.288469E+09 | 0.110101E+09 | 0.00 | 3796343.01 | 20664999.38 | 0.00 | 0.576779E+09 | 0.00 | 0.63 |
July | 0.224206E+09 | 0.137333E+09 | 0.00 | 3290811.37 | 30884128.25 | 0.00 | 0.417551E+09 | 0.00 | 0.60 |
August | 0.302993E+09 | 0.104030E+09 | 0.00 | 4669147.76 | 10173573.68 | 0.00 | 0.759414E+09 | 0.00 | 0.63 |
September | 0.563675E+09 | 15048915.52 | 0.00 | 4216459.17 | 5352044.33 | 0.00 | 0.905161E+09 | 0.00 | 0.65 |
October | 0.171319E+10 | 0.00 | 0.00 | 597374.01 | 0.00 | 0.375034E+09 | 0.341757E+09 | 0.00 | 0.43 |
November | 0.163329E+10 | 0.00 | 0.00 | 64620.72 | 0.00 | 0.780525E+09 | 53566918.39 | 0.00 | 0.34 |
December | 0.104553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183250E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.121107E+11 | 0.366983E+09 | 0.00 | 18552497.01 | 68120817.76 | 0.763502E+10 | 0.390102E+10 | 0.00 | 0.46 |
Minimum of Months | 0.224206E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.171319E+10 | 0.137333E+09 | 0.00 | 4669147.76 | 30884128.25 | 0.183250E+10 | 0.905161E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136492E+10 | 0.00 | 0.00 | 91786.21 | 0.00 | 0.873202E+09 | 68620738.52 | 0.00 | 0.43 |
February | 0.113966E+10 | 0.00 | 0.00 | 328155.66 | 0.00 | 0.830923E+09 | 0.202484E+09 | 0.00 | 0.42 |
March | 0.117345E+10 | 0.00 | 0.00 | 1468483.72 | 0.00 | 0.508974E+09 | 0.811180E+09 | 0.00 | 0.64 |
April | 0.115996E+10 | 0.00 | 0.00 | 1602277.10 | 0.00 | 0.204128E+09 | 0.847316E+09 | 0.00 | 0.65 |
May | 0.636573E+09 | 538202.79 | 0.00 | 3789883.33 | 875063.13 | 4197391.87 | 0.152059E+10 | 0.00 | 0.98 |
June | 0.157343E+09 | 0.104121E+09 | 0.00 | 5932245.60 | 14106257.95 | 0.00 | 0.106466E+10 | 0.00 | 1.29 |
July | 0.136004E+09 | 0.136297E+09 | 0.00 | 4923344.87 | 21882627.01 | 0.00 | 0.628916E+09 | 0.00 | 1.07 |
August | 0.192104E+09 | 0.108833E+09 | 0.00 | 7523717.10 | 7650876.86 | 0.00 | 0.140187E+10 | 0.00 | 1.36 |
September | 0.300247E+09 | 16246954.53 | 0.00 | 6594437.87 | 4231438.97 | 0.00 | 0.157117E+10 | 0.00 | 1.31 |
October | 0.103774E+10 | 0.00 | 0.00 | 2489125.64 | 0.00 | 0.296345E+09 | 0.123907E+10 | 0.00 | 0.75 |
November | 0.137308E+10 | 0.00 | 0.00 | 748058.53 | 0.00 | 0.459252E+09 | 0.397221E+09 | 0.00 | 0.49 |
December | 0.121767E+10 | 0.00 | 0.00 | 4250.90 | 0.00 | 0.117973E+10 | 16689076.45 | 0.00 | 0.42 |
Annual Sum or Average | 0.988875E+10 | 0.366036E+09 | 0.00 | 35495766.52 | 48746263.91 | 0.435675E+10 | 0.976979E+10 | 0.00 | 0.82 |
Minimum of Months | 0.136004E+09 | 0.00 | 0.00 | 4250.90 | 0.00 | 0.00 | 16689076.45 | 0.00 | 0.42 |
Maximum of Months | 0.137308E+10 | 0.136297E+09 | 0.00 | 7523717.10 | 21882627.01 | 0.117973E+10 | 0.157117E+10 | 0.00 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108704E+10 | 0.00 | 0.00 | 2045161.78 | 0.00 | 0.190423E+10 | 0.115854E+10 | 0.00 | 0.55 |
February | 0.907022E+09 | 0.00 | 0.00 | 1805464.62 | 0.00 | 0.197767E+10 | 0.946434E+09 | 0.00 | 0.51 |
March | 0.110164E+10 | 0.00 | 0.00 | 2481312.69 | 0.00 | 0.160390E+10 | 0.112111E+10 | 0.00 | 0.68 |
April | 0.122350E+10 | 0.00 | 0.00 | 771173.30 | 0.00 | 0.115677E+10 | 0.402020E+09 | 0.00 | 0.50 |
May | 0.121839E+10 | 965872.78 | 0.00 | 1945079.71 | 1008431.78 | 0.456792E+09 | 0.469581E+09 | 0.00 | 0.62 |
June | 0.395728E+09 | 0.162524E+09 | 0.00 | 4125237.76 | 18122926.36 | 34571511.33 | 0.409353E+09 | 0.00 | 0.69 |
July | 0.301983E+09 | 0.203705E+09 | 0.00 | 3414786.95 | 29409195.94 | 13510905.48 | 0.315614E+09 | 0.00 | 0.67 |
August | 0.368632E+09 | 0.193888E+09 | 0.00 | 8380642.44 | 5643102.05 | 41086110.62 | 0.863912E+09 | 0.00 | 0.88 |
September | 0.472996E+09 | 35570755.03 | 0.00 | 9755403.40 | 3874052.82 | 0.114642E+09 | 0.166899E+10 | 0.00 | 1.17 |
October | 0.768061E+09 | 0.00 | 0.00 | 8391548.16 | 0.00 | 0.120995E+10 | 0.290533E+10 | 0.00 | 1.01 |
November | 0.961234E+09 | 0.00 | 0.00 | 4308761.36 | 0.00 | 0.143551E+10 | 0.196243E+10 | 0.00 | 0.71 |
December | 0.102090E+10 | 0.00 | 0.00 | 2432009.93 | 0.00 | 0.254375E+10 | 0.974645E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.982713E+10 | 0.596654E+09 | 0.00 | 49856582.10 | 58057708.95 | 0.124924E+11 | 0.131980E+11 | 0.00 | 0.71 |
Minimum of Months | 0.301983E+09 | 0.00 | 0.00 | 771173.30 | 0.00 | 13510905.48 | 0.315614E+09 | 0.00 | 0.50 |
Maximum of Months | 0.122350E+10 | 0.203705E+09 | 0.00 | 9755403.40 | 29409195.94 | 0.254375E+10 | 0.290533E+10 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.135140E+10 | 0.00 | 0.00 | 235678.06 | 0.00 | 0.104828E+10 | 0.196026E+09 | 0.00 | 0.49 |
February | 0.121775E+10 | 0.00 | 0.00 | 349217.62 | 0.00 | 0.983735E+09 | 0.236902E+09 | 0.00 | 0.48 |
March | 0.142198E+10 | 0.00 | 0.00 | 1206160.54 | 0.00 | 0.686796E+09 | 0.580357E+09 | 0.00 | 0.70 |
April | 0.147524E+10 | 0.00 | 0.00 | 983639.62 | 0.00 | 0.282550E+09 | 0.495861E+09 | 0.00 | 0.66 |
May | 0.948400E+09 | 886620.63 | 0.00 | 2622385.42 | 809581.10 | 19607736.97 | 0.101195E+10 | 0.00 | 0.92 |
June | 0.287274E+09 | 0.141135E+09 | 0.00 | 3665692.31 | 10818532.32 | 0.00 | 0.513488E+09 | 0.00 | 0.98 |
July | 0.232451E+09 | 0.145345E+09 | 0.00 | 2697657.95 | 23383077.22 | 0.00 | 0.379629E+09 | 0.00 | 0.88 |
August | 0.288020E+09 | 0.124021E+09 | 0.00 | 4885006.02 | 8663592.35 | 0.00 | 0.692998E+09 | 0.00 | 0.98 |
September | 0.447880E+09 | 19237463.89 | 0.00 | 4913874.85 | 3106608.30 | 0.00 | 0.106804E+10 | 0.00 | 1.10 |
October | 0.131234E+10 | 0.00 | 0.00 | 2508105.83 | 0.00 | 0.341987E+09 | 0.112874E+10 | 0.00 | 0.84 |
November | 0.157091E+10 | 0.00 | 0.00 | 672884.53 | 0.00 | 0.521544E+09 | 0.403941E+09 | 0.00 | 0.56 |
December | 0.129107E+10 | 0.00 | 0.00 | 152397.73 | 0.00 | 0.128403E+10 | 0.118570E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.118447E+11 | 0.430624E+09 | 0.00 | 24892700.47 | 46781391.29 | 0.516853E+10 | 0.682651E+10 | 0.00 | 0.76 |
Minimum of Months | 0.232451E+09 | 0.00 | 0.00 | 152397.73 | 0.00 | 0.00 | 0.118570E+09 | 0.00 | 0.47 |
Maximum of Months | 0.157091E+10 | 0.145345E+09 | 0.00 | 4913874.85 | 23383077.22 | 0.128403E+10 | 0.112874E+10 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128873E+10 | 0.00 | 0.00 | 0.31 |
February | 0.122525E+10 | 0.00 | 0.00 | 972.11 | 0.00 | 0.119572E+10 | 7286219.35 | 0.00 | 0.30 |
March | 0.159066E+10 | 0.00 | 0.00 | 593278.40 | 0.00 | 0.643286E+09 | 0.329351E+09 | 0.00 | 0.41 |
April | 0.151271E+10 | 0.00 | 0.00 | 749088.97 | 0.00 | 0.267220E+09 | 0.422798E+09 | 0.00 | 0.41 |
May | 0.775585E+09 | 891369.81 | 0.00 | 4180378.78 | 794624.07 | 13914381.68 | 0.158323E+10 | 0.00 | 0.70 |
June | 0.150966E+09 | 0.130029E+09 | 0.00 | 5861772.29 | 14251804.90 | 0.00 | 0.890251E+09 | 0.00 | 0.81 |
July | 0.144844E+09 | 0.175850E+09 | 0.00 | 4845696.54 | 25300151.34 | 0.00 | 0.605234E+09 | 0.00 | 0.75 |
August | 0.212290E+09 | 0.123444E+09 | 0.00 | 6208084.05 | 7108839.61 | 0.00 | 0.963994E+09 | 0.00 | 0.73 |
September | 0.487639E+09 | 19080225.37 | 0.00 | 4650329.00 | 5807650.68 | 425730.19 | 0.978358E+09 | 0.00 | 0.67 |
October | 0.154517E+10 | 0.00 | 0.00 | 786294.20 | 0.00 | 0.446963E+09 | 0.403839E+09 | 0.00 | 0.43 |
November | 0.148634E+10 | 0.00 | 0.00 | 156796.80 | 0.00 | 0.864199E+09 | 99684194.73 | 0.00 | 0.34 |
December | 0.105512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182369E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.114748E+11 | 0.449294E+09 | 0.00 | 28032691.15 | 53263070.61 | 0.654414E+10 | 0.628403E+10 | 0.00 | 0.52 |
Minimum of Months | 0.144844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.159066E+10 | 0.175850E+09 | 0.00 | 6208084.05 | 25300151.34 | 0.182369E+10 | 0.158323E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.161301E+10 | 0.00 | 0.00 | 225741.05 | 0.00 | 0.989528E+09 | 0.164169E+09 | 0.00 | 0.53 |
February | 0.143384E+10 | 0.00 | 0.00 | 695314.44 | 0.00 | 0.877572E+09 | 0.367739E+09 | 0.00 | 0.54 |
March | 0.142915E+10 | 0.00 | 0.00 | 2465611.30 | 0.00 | 0.540252E+09 | 0.126939E+10 | 0.00 | 0.83 |
April | 0.129646E+10 | 0.00 | 0.00 | 2554562.09 | 0.00 | 0.227688E+09 | 0.132885E+10 | 0.00 | 0.85 |
May | 0.724263E+09 | 776267.90 | 0.00 | 5259671.92 | 861639.88 | 5243234.42 | 0.217298E+10 | 0.00 | 1.30 |
June | 0.124431E+09 | 0.102690E+09 | 0.00 | 7563311.29 | 13315420.35 | 0.00 | 0.137202E+10 | 0.00 | 1.54 |
July | 0.117656E+09 | 0.152807E+09 | 0.00 | 6227178.34 | 20232723.75 | 0.00 | 0.778271E+09 | 0.00 | 1.26 |
August | 0.195914E+09 | 0.108672E+09 | 0.00 | 8465140.77 | 7178838.03 | 0.00 | 0.161744E+10 | 0.00 | 1.51 |
September | 0.444244E+09 | 17980411.41 | 0.00 | 6335670.84 | 6297447.57 | 452747.32 | 0.152095E+10 | 0.00 | 1.35 |
October | 0.129288E+10 | 0.00 | 0.00 | 2380237.20 | 0.00 | 0.475815E+09 | 0.117323E+10 | 0.00 | 0.84 |
November | 0.161712E+10 | 0.00 | 0.00 | 696999.18 | 0.00 | 0.715332E+09 | 0.369174E+09 | 0.00 | 0.60 |
December | 0.135162E+10 | 0.00 | 0.00 | 34645.36 | 0.00 | 0.153951E+10 | 37385557.19 | 0.00 | 0.52 |
Annual Sum or Average | 0.116406E+11 | 0.382926E+09 | 0.00 | 42904083.77 | 47886069.58 | 0.537139E+10 | 0.121716E+11 | 0.00 | 0.98 |
Minimum of Months | 0.117656E+09 | 0.00 | 0.00 | 34645.36 | 0.00 | 0.00 | 37385557.19 | 0.00 | 0.52 |
Maximum of Months | 0.161712E+10 | 0.152807E+09 | 0.00 | 8465140.77 | 20232723.75 | 0.153951E+10 | 0.217298E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130001E+10 | 0.00 | 0.00 | 7762207.22 | 0.00 | 0.619729E+09 | 0.343141E+10 | 0.00 | 0.79 |
February | 0.107564E+10 | 0.00 | 0.00 | 8176299.36 | 0.00 | 0.656556E+09 | 0.352014E+10 | 0.00 | 0.76 |
March | 0.123719E+10 | 0.00 | 0.00 | 7930591.49 | 0.00 | 0.536868E+09 | 0.348312E+10 | 0.00 | 1.00 |
April | 0.141219E+10 | 0.00 | 0.00 | 4111073.33 | 0.00 | 0.266366E+09 | 0.192015E+10 | 0.00 | 0.76 |
May | 0.877780E+09 | 1527850.71 | 0.00 | 6180190.63 | 876913.51 | 18490138.35 | 0.232647E+10 | 0.00 | 0.97 |
June | 0.267815E+09 | 0.150139E+09 | 0.00 | 6191772.23 | 16246858.93 | 0.00 | 0.846674E+09 | 0.00 | 0.89 |
July | 0.202314E+09 | 0.238955E+09 | 0.00 | 5215827.39 | 19576960.38 | 0.00 | 0.617401E+09 | 0.00 | 0.84 |
August | 0.253520E+09 | 0.196245E+09 | 0.00 | 9586282.95 | 4476154.73 | 0.00 | 0.136201E+10 | 0.00 | 1.03 |
September | 0.447725E+09 | 42455016.49 | 0.00 | 10590077.30 | 5878935.95 | 489513.56 | 0.208346E+10 | 0.00 | 1.26 |
October | 0.101267E+10 | 0.00 | 0.00 | 11904450.47 | 0.00 | 0.490337E+09 | 0.427160E+10 | 0.00 | 1.25 |
November | 0.123875E+10 | 0.00 | 0.00 | 9268735.05 | 0.00 | 0.479299E+09 | 0.374478E+10 | 0.00 | 0.94 |
December | 0.135093E+10 | 0.00 | 0.00 | 6360301.62 | 0.00 | 0.100638E+10 | 0.250740E+10 | 0.00 | 0.70 |
Annual Sum or Average | 0.106765E+11 | 0.629322E+09 | 0.00 | 93277809.03 | 47055823.49 | 0.407452E+10 | 0.301146E+11 | 0.00 | 0.93 |
Minimum of Months | 0.202314E+09 | 0.00 | 0.00 | 4111073.33 | 0.00 | 0.00 | 0.617401E+09 | 0.00 | 0.70 |
Maximum of Months | 0.141219E+10 | 0.238955E+09 | 0.00 | 11904450.47 | 19576960.38 | 0.100638E+10 | 0.427160E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163218E+10 | 0.00 | 0.00 | 512911.39 | 0.00 | 0.107428E+10 | 0.356224E+09 | 0.00 | 0.61 |
February | 0.146898E+10 | 0.00 | 0.00 | 804810.49 | 0.00 | 0.101288E+10 | 0.487240E+09 | 0.00 | 0.60 |
March | 0.173813E+10 | 0.00 | 0.00 | 2250285.33 | 0.00 | 0.632488E+09 | 0.104893E+10 | 0.00 | 0.94 |
April | 0.165985E+10 | 0.00 | 0.00 | 1913487.05 | 0.00 | 0.278515E+09 | 0.932778E+09 | 0.00 | 0.88 |
May | 0.946083E+09 | 1660930.50 | 0.00 | 4295531.40 | 569113.03 | 21342539.37 | 0.167440E+10 | 0.00 | 1.24 |
June | 0.309952E+09 | 0.157832E+09 | 0.00 | 4772260.84 | 9278483.61 | 0.00 | 0.589244E+09 | 0.00 | 1.16 |
July | 0.240872E+09 | 0.185226E+09 | 0.00 | 3362349.84 | 19129528.69 | 0.00 | 0.433993E+09 | 0.00 | 1.04 |
August | 0.333180E+09 | 0.140048E+09 | 0.00 | 5666283.88 | 6883209.63 | 0.00 | 0.723622E+09 | 0.00 | 1.10 |
September | 0.614630E+09 | 24452065.16 | 0.00 | 4722613.03 | 4833412.80 | 3806900.57 | 0.988862E+09 | 0.00 | 1.15 |
October | 0.164455E+10 | 0.00 | 0.00 | 2727805.19 | 0.00 | 0.510135E+09 | 0.108441E+10 | 0.00 | 0.98 |
November | 0.169309E+10 | 0.00 | 0.00 | 829865.27 | 0.00 | 0.815181E+09 | 0.488034E+09 | 0.00 | 0.69 |
December | 0.137348E+10 | 0.00 | 0.00 | 256049.61 | 0.00 | 0.165027E+10 | 0.182902E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.136550E+11 | 0.509219E+09 | 0.00 | 32114253.32 | 40693747.76 | 0.599890E+10 | 0.899063E+10 | 0.00 | 0.92 |
Minimum of Months | 0.240872E+09 | 0.00 | 0.00 | 256049.61 | 0.00 | 0.00 | 0.182902E+09 | 0.00 | 0.58 |
Maximum of Months | 0.173813E+10 | 0.185226E+09 | 0.00 | 5666283.88 | 19129528.69 | 0.165027E+10 | 0.167440E+10 | 0.00 | 1.24 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.250844E+12 | 0.954456E+10 | 0.00 | 0.165287E+12 | 0.801548E+10 |
February | 0.308310E+12 | 0.110254E+11 | 0.00 | 0.152473E+12 | 0.589665E+10 |
March | 0.372397E+12 | 0.106013E+11 | 0.00 | 0.178897E+12 | 0.135966E+11 |
April | 0.384622E+12 | 0.948226E+10 | 0.00 | 0.177400E+12 | 0.106467E+11 |
May | 0.448188E+12 | 0.538846E+10 | 0.00 | 0.199727E+12 | 0.481115E+11 |
June | 0.465868E+12 | 0.105738E+10 | 0.00 | 0.121362E+12 | 0.189666E+12 |
July | 0.435483E+12 | 0.726909E+09 | 0.00 | 0.941735E+11 | 0.191194E+12 |
August | 0.433778E+12 | 0.118556E+10 | 0.00 | 0.962272E+11 | 0.184123E+12 |
September | 0.330859E+12 | 0.298758E+10 | 0.00 | 0.155992E+12 | 0.120708E+12 |
October | 0.294884E+12 | 0.874688E+10 | 0.00 | 0.204918E+12 | 0.230931E+11 |
November | 0.263127E+12 | 0.960559E+10 | 0.00 | 0.181103E+12 | 0.993095E+10 |
December | 0.211294E+12 | 0.132547E+11 | 0.00 | 0.157027E+12 | 0.102922E+11 |
Annual Sum or Average | 0.419965E+13 | 0.836066E+11 | 0.00 | 0.188459E+13 | 0.815274E+12 |
Minimum of Months | 0.211294E+12 | 0.726909E+09 | 0.00 | 0.941735E+11 | 0.589665E+10 |
Maximum of Months | 0.465868E+12 | 0.132547E+11 | 0.00 | 0.204918E+12 | 0.191194E+12 |