Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2023-10-16 08:35:22
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2130.62 | 427.65 | 427.65 |
Net Site Energy | 2130.62 | 427.65 | 427.65 |
Total Source Energy | 6018.77 | 1208.06 | 1208.06 |
Net Source Energy | 6018.77 | 1208.06 | 1208.06 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 639.08 | 223.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 210.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 54.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 88.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 25.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 126.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1780.69 | 349.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 639.08 | 223.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 45.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 210.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 54.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 88.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 25.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 126.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 639.08 | 223.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 45.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 210.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 54.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 88.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 25.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 126.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 53.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 155.05 | 70.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 357.41 | 70.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 53.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 155.05 | 70.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 149.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 357.41 | 70.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1780.692 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1780.692 | 100.00 |
Total On-Site and Utility Electric Sources | 1780.692 | 100.00 |
Total Electricity End Uses | 1780.692 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 0.19 | 0.04 |
Air to Air Heat Recovery for Heating | 454.26 | 99.96 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 454.45 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1209.83 |
Time Setpoint Not Met During Occupied Cooling | 41.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3488.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.9322 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.9322 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.9322 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-08:09 | 12-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 190552.26 | 199286.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 21377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 45864.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 816.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8262.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 272878.57 | 207548.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 190552.26 | 199286.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 21377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 816.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 5986.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8262.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 2023.96 | 242.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 142.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 667.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 174.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 279.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 80.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 136.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5639.45 | 379.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 406.24 | 48.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 134.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 56.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 16.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1131.92 | 76.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 406.24 | 48.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 134.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 34.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 56.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 16.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1131.92 | 76.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.80 | 0.268096 | 0.277000 | 0.774345 | 0.714923 | 0.500000 | 0.001421 |
CORE_MID VAV BOX COMPONENT | 2.04 | 0.367412 | 0.368000 | 0.750654 | 0.979766 | 0.500000 | 0.001037 |
CORE_TOP VAV BOX COMPONENT | 2.01 | 0.373500 | 0.385000 | 0.772531 | 0.995999 | 0.500000 | 0.001020 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.680420 | 0.232197 | 0.277000 | 0.188476 | 0.619192 | 0.500000 | 0.001641 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.784645 | 0.127474 | 0.200000 | 0.156929 | 0.339931 | 0.500000 | 0.002989 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.25 | 0.126795 | 0.200000 | 0.249208 | 0.338120 | 0.500000 | 0.003005 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.822501 | 0.121599 | 0.200000 | 0.164500 | 0.324264 | 0.500000 | 0.003133 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.526934 | 0.299832 | 0.330000 | 0.173888 | 0.799552 | 0.500000 | 0.001271 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.639578 | 0.156387 | 0.200000 | 0.127916 | 0.417032 | 0.500000 | 0.002436 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.00 | 0.157767 | 0.200000 | 0.200285 | 0.420711 | 0.500000 | 0.002415 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.675965 | 0.147959 | 0.200000 | 0.135193 | 0.394558 | 0.500000 | 0.002575 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.561624 | 0.281312 | 0.282000 | 0.158378 | 0.750165 | 0.500000 | 0.001354 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.777141 | 0.128705 | 0.200000 | 0.155428 | 0.343213 | 0.500000 | 0.002960 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.17 | 0.135239 | 0.200000 | 0.233649 | 0.360636 | 0.500000 | 0.002817 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.770733 | 0.129766 | 0.200000 | 0.154147 | 0.346044 | 0.500000 | 0.002936 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25460.10 |
CORE_MID VAV BOX REHEAT COIL | 27489.80 |
CORE_TOP VAV BOX REHEAT COIL | 50723.19 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22371.90 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14613.80 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22269.46 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14556.57 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17325.33 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11429.16 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17260.86 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11386.89 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 16580.96 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 10902.91 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16491.79 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 10858.22 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.82 | 1.41 | 5.64 | 2.20 | 4.85 | 4.85 | 0.300000 | 0.453864 | 4.85 |
PACU_VAV_MID | 2.66 | 1.45 | 5.32 | 2.50 | 4.32 | 4.32 | 0.300000 | 0.579532 | 4.32 |
PACU_VAV_TOP | 2.77 | 1.53 | 5.54 | 3.79 | 4.77 | 4.77 | 0.300000 | 0.794343 | 4.77 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.85 |
PACU_VAV_MID_OA_CONTROLLER | 4.32 |
PACU_VAV_TOP_OA_CONTROLLER | 4.77 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT OA HEAT RECOVERY | 1.20 |
PACU_VAV_MID OA HEAT RECOVERY | 1.20 |
PACU_VAV_TOP OA HEAT RECOVERY | 1.20 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.85 | 80300.05 | 0.800655 | 1.62 | 26764.01 | 0.800655 |
PACU_VAV_MID COOLING COIL | 4.32 | 71517.55 | 0.800655 | 1.44 | 23836.80 | 0.800655 |
PACU_VAV_TOP COOLING COIL | 4.77 | 78931.18 | 0.800655 | 1.59 | 26307.76 | 0.800655 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 76044.32 |
PACU_VAV_MID HEATING COIL | 77310.06 |
PACU_VAV_TOP HEATING COIL | 77090.78 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.85 |
PACU_VAV_MID FAN | 4.32 |
PACU_VAV_TOP FAN | 4.77 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 30.766 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7380 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.7231 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.058 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1861 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1962 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1861 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1962 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.121 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.149 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7112 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.298 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.019 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.298 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.019 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
39 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
40 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
41 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
42 | 7 | -0.30753051E-12 | 0.12442160E-14 | -0.97997307E-13 | 0.16181277E-15 |
43 | 6 | 0.29129207E-07 | 0.20858330E-09 | 0.66690616E-08 | -0.13765882E-12 |
44 | 5 | -0.19242924E-03 | 0.17796139E-05 | -0.98946217E-04 | 0.65913253E-08 |
45 | 4 | 0.29485983 | 0.86373027E-03 | 0.10065932 | -0.33954172E-04 |
46 | 3 | -7.3200506 | 0.26691581E-01 | -2.3548546 | 0.29272310E-01 |
47 | 2 | 41.048314 | 0.94673972E-01 | 15.330469 | -0.33531364 |
48 | 1 | -80.681549 | 0.42633475E-01 | -29.200290 | 1.0815124 |
49 | 0 | 46.824338 | 0.85589067E-03 | 16.289835 | |
50 | 7 | -0.31002685E-12 | 0.12243056E-14 | -0.98925303E-13 | 0.16187377E-15 |
51 | 6 | 0.29304991E-07 | 0.20474050E-09 | 0.67078600E-08 | -0.13860400E-12 |
52 | 5 | -0.19331904E-03 | 0.17449135E-05 | -0.99391612E-04 | 0.66291231E-08 |
53 | 4 | 0.29589700 | 0.84606238E-03 | 0.10103252 | -0.34100928E-04 |
54 | 3 | -7.3405816 | 0.26122989E-01 | -2.3609475 | 0.29372952E-01 |
55 | 2 | 41.116015 | 0.92586303E-01 | 15.355437 | -0.33606772 |
56 | 1 | -80.733416 | 0.41665486E-01 | -29.222668 | 1.0826177 |
57 | 0 | 46.824337 | 0.83590844E-03 | 16.289304 | |
58 | 7 | -0.27887678E-12 | 0.13864078E-14 | -0.80166063E-13 | 0.13964816E-15 |
59 | 6 | 0.25302967E-07 | 0.28609859E-09 | 0.58245251E-08 | -0.11721010E-12 |
60 | 5 | -0.17285039E-03 | 0.25051735E-05 | -0.89112604E-04 | 0.57669208E-08 |
61 | 4 | 0.27172525 | 0.12441479E-02 | 0.92350123E-01 | -0.30713339E-04 |
62 | 3 | -6.8613536 | 0.39236887E-01 | -2.2187821 | 0.27025925E-01 |
63 | 2 | 39.534911 | 0.14168039 | 14.771016 | -0.31846148 |
64 | 1 | -79.521172 | 0.64798402E-01 | -28.698336 | 1.0567855 |
65 | 0 | 46.824345 | 0.13208371E-02 | 16.302124 | |
66 | 7 | -0.22718025E-08 | -0.85076432E-15 | 0.54602610E-14 | -0.81699313E-16 |
67 | 6 | 0.52504722E-05 | 0.35612887E-08 | 0.31909185E-02 | -0.26768099E-04 |
68 | 5 | -0.37481041E-03 | 0.21076474E-05 | -0.22378418 | 0.19566764E-02 |
69 | 4 | 0.86040017E-02 | 0.95918289E-04 | 4.8305385 | -0.45274525E-01 |
70 | 3 | -0.75502230E-01 | 0.76254733E-03 | -38.027025 | 0.39871575 |
71 | 2 | 0.26802071 | 0.12683646E-02 | 116.49487 | -1.4180853 |
72 | 1 | -0.38680241 | 0.38624458E-03 | -143.91373 | 2.0491456 |
73 | 0 | 0.18857406 | 0.93873709E-05 | 60.838472 | |
74 | 7 | -0.21518248E-08 | -0.72352508E-15 | 0.47198691E-14 | -0.69590188E-16 |
75 | 6 | 0.55239907E-05 | 0.37570600E-08 | 0.31901221E-02 | -0.26761418E-04 |
76 | 5 | -0.39518120E-03 | 0.22239456E-05 | -0.22373891 | 0.19562768E-02 |
77 | 4 | 0.90771213E-02 | 0.10121852E-03 | 4.8297846 | -0.45267278E-01 |
78 | 3 | -0.79671013E-01 | 0.80474906E-03 | -38.022767 | 0.39866868 |
79 | 2 | 0.28284274 | 0.13386367E-02 | 116.48658 | -1.4179745 |
80 | 1 | -0.40820825 | 0.40769430E-03 | -143.90886 | 2.0490654 |
81 | 0 | 0.19901349 | 0.99021926E-05 | 60.838472 | |
82 | 7 | -0.22718025E-08 | -0.85076409E-15 | 0.54602611E-14 | -0.81699316E-16 |
83 | 6 | 0.52504722E-05 | 0.35612887E-08 | 0.31909185E-02 | -0.26768099E-04 |
84 | 5 | -0.37481041E-03 | 0.21076474E-05 | -0.22378418 | 0.19566764E-02 |
85 | 4 | 0.86040017E-02 | 0.95918289E-04 | 4.8305385 | -0.45274525E-01 |
86 | 3 | -0.75502230E-01 | 0.76254733E-03 | -38.027025 | 0.39871575 |
87 | 2 | 0.26802071 | 0.12683646E-02 | 116.49487 | -1.4180853 |
88 | 1 | -0.38680241 | 0.38624458E-03 | -143.91373 | 2.0491456 |
89 | 0 | 0.18857406 | 0.93873709E-05 | 60.838472 | |
90 | 7 | -0.21516764E-08 | -0.72282083E-15 | 0.50090186E-14 | -0.71315031E-16 |
91 | 6 | 0.55243484E-05 | 0.37573175E-08 | 0.31901211E-02 | -0.26761409E-04 |
92 | 5 | -0.39520780E-03 | 0.22240973E-05 | -0.22373885 | 0.19562763E-02 |
93 | 4 | 0.90777390E-02 | 0.10122544E-03 | 4.8297836 | -0.45267268E-01 |
94 | 3 | -0.79676455E-01 | 0.80480411E-03 | -38.022761 | 0.39866862 |
95 | 2 | 0.28286209 | 0.13387285E-02 | 116.48657 | -1.4179743 |
96 | 1 | -0.40823619 | 0.40772215E-03 | -143.90885 | 2.0490653 |
97 | 0 | 0.19902711 | 0.99029315E-05 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.2619_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 1.487 | 1.487 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.2619_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 1.487 | 1.487 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.2619_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 1.487 | 1.487 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.2619_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 1.487 | 1.487 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.47794E-002 | 0.31435 | 0.49157 | 0.49157 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.00644E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.47794E-002 | 0.31435 | 0.49157 | 0.49157 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.00644E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.47794E-002 | 0.31435 | 0.49157 | 0.49157 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.00644E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.47794E-002 | 0.31435 | 0.49157 | 0.49157 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 9.00644E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.384E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.394E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.384E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.394E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.424E-004 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.424E-004 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.550E-005 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2243E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2310E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4465E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4525E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1240E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1639E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8098E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8318E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1295 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.2040E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1502 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1112 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2056E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.7096E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4403E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6646E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2248E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2349E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.4472E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4572E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1272E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1787E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.8095E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.8316E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.8421E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.5602E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.2154E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7988E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.0662E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6157E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1638E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4129E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.6344E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.6644E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8821E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.9052E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6940E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7019E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4471E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4545E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0019E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.0673E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2342E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.2920E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3840E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4221E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8095E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8316E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.2394E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0483E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1954E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4196E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6000E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4886E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4403E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6646E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0012E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.0706E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2320E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.2888E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3811E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4107E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8098E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.8318E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.3925E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0038E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7705E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6023E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7460E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9366E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1639E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4130E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9113E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9981E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4526E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5564E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8874E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9107E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4472E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4547E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1406 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1091 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1630 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1310 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.9310E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.6792E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.9898E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3127E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.4444E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.3370E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.7984E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.5651E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.8472E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4967E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0404E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3467E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8225E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.8323E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7183E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.1002E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0996E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0732E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.9898E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3127E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.1234E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8560E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5351E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4753E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5795E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8482E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0404E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3467E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1407 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1091 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1630 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1310 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.9308E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.6788E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.9894E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3125E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.4448E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.3367E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.7989E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.5649E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.8470E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4964E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0400E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3464E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8229E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.8321E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7186E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.1001E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0994E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0730E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.9894E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3125E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.1236E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8558E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5353E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4751E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5792E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8479E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0400E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3465E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 38196.67864 | 38196.67864 | 2.79547 | 2.79547 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 10699.11766 | 10699.11766 | 0.46584 | 0.46584 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27906.78932 | 27906.78932 | 2.03982 | 2.03982 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 19402.29711 | 19402.29711 | 0.83608 | 0.83608 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 27187.91957 | 27187.91957 | 2.00657 | 2.00657 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 26.89000 | 7.00637E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 35675.43832 | 35675.43832 | 1.54270 | 1.54270 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 7962.46377 | 7962.46377 | 0.58765 | 0.58765 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 21.53500 | 6.99833E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15700.94798 | 15700.94798 | 0.68042 | 0.68042 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10631.78745 | 10631.78745 | 0.78464 | 0.78464 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 22.36800 | 6.99957E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10255.59616 | 10255.59616 | 0.44447 | 0.44447 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 16883.61155 | 16883.61155 | 1.24604 | 1.24604 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15629.19623 | 15629.19623 | 0.67730 | 0.67730 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11144.72372 | 11144.72372 | 0.82250 | 0.82250 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10215.50510 | 10215.50510 | 0.44272 | 0.44272 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6703.63082 | 6703.63082 | 0.49475 | 0.49475 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 12165.10257 | 12165.10257 | 0.52693 | 0.52693 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8666.12130 | 8666.12130 | 0.63958 | 0.63958 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 22.65700 | 7.00000E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 8024.27229 | 8024.27229 | 0.34761 | 0.34761 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 13569.05204 | 13569.05204 | 1.00143 | 1.00143 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 12119.94467 | 12119.94467 | 0.52497 | 0.52497 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9159.14707 | 9159.14707 | 0.67596 | 0.67596 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 23.04800 | 7.00058E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7994.66851 | 7994.66851 | 0.34632 | 0.34632 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7609.79885 | 7609.79885 | 0.56162 | 0.56162 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11644.43958 | 11644.43958 | 0.50429 | 0.50429 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10530.10394 | 10530.10394 | 0.77714 | 0.77714 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 22.07900 | 6.99914E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7656.13206 | 7656.13206 | 0.33160 | 0.33160 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 15829.43071 | 15829.43071 | 1.16824 | 1.16824 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 27.40000 | 7.00714E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11581.98484 | 11581.98484 | 0.50158 | 0.50158 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10443.26860 | 10443.26860 | 0.77073 | 0.77073 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.44200 | 7.00266E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7624.82584 | 7624.82584 | 0.33024 | 0.33024 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 69473.11 | 4.85093 | 4.85093 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 77809.93 | 2.20166 | 2.20166 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 62359.52 | 4.32038 | 4.32038 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 77640.07 | 2.50380 | 2.50380 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 68082.57 | 4.76823 | 4.76823 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 77857.65 | 3.78761 | 3.78761 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.79547 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26810 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77435 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71492 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42113E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25460.10120 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.03982 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36741 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36800 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75065 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97977 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.03698E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 27489.80327 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00657 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37350 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.38500 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77253 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99600 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02008E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 50723.18659 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68042 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23220 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27700 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18848 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61919 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64085E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22371.89774 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78464 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12747 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15693 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33993 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.98885E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14613.80205 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24604 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12679 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24921 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33812 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00485E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22269.45996 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82250 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12160 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16450 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32426 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.13325E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14556.56676 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52693 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29983 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17389 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79955 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27071E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17325.33339 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.63958 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15639 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12792 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41703 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43626E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11429.15983 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00143 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15777 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20029 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42071 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.41496E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17260.85660 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67596 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14796 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13519 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39456 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57503E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11386.89419 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56162 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28131 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28200 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15838 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75017 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35437E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16580.95954 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77714 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12870 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15543 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34321 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96026E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10902.91309 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16824 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13524 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23365 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36064 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81724E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16491.78961 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77073 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12977 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15415 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34604 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93605E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10858.21700 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.81969 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41163 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.63937 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.20166 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.85093 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.85093 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.45386 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.65878 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45226 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.31756 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.50380 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.32038 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.32038 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.57953 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.77009 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53165 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.54018 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.78761 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.76823 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.76823 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.79434 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.85093 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.32038 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.76823 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.85093 |
149 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_BOT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.85093 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 80300.05006 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.61681 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 26764.00669 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
156 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 76044.31649 |
157 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.85093 |
158 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.32038 |
159 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.32038 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 71517.55174 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.43998 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 23836.80000 |
165 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
166 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 77310.05508 |
167 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.32038 |
168 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.76823 |
169 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_TOP OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.76823 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 78931.17802 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80066 |
173 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.58925 |
174 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 26307.76163 |
175 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80066 |
176 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 77090.78346 |
177 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.76823 |
178 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
179 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
180 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
181 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
182 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 78918.29 | 269280.37 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 5.5234 | 4.3688 | 2.9277 | 1.2201 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 70286.91 | 239828.90 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 4.9193 | 3.8910 | 2.6075 | 1.0867 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 77572.97 | 264689.96 | 10.81 | 2.80 | 3.09 | 3.26 | 3.43 | 9.54 | 10.55 | 11.11 | 11.69 | 5.4292 | 4.2944 | 2.8778 | 1.1993 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.058 | 0.913 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.058 | 0.913 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.058 | 0.913 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.058 | 0.913 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.723 | 0.652 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.723 | 0.652 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.723 | 0.652 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.723 | 0.652 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.665 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.665 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.665 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.665 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.058 | 0.913 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_NORTH_0.4 | N/A | 1.487 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.058 | 0.913 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_EAST_0.4 | N/A | 1.487 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.058 | 0.913 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_SOUTH_0.4 | N/A | 1.487 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.058 | 0.913 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_WEST_0.4 | N/A | 1.487 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.665 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_NORTH_0.4 | N/A | 1.487 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_NORTH_0.4 | N/A | 1.487 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_NORTH_0.4 | N/A | 1.487 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.186 | 0.178 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.665 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_EAST_0.4 | N/A | 1.487 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_EAST_0.4 | N/A | 1.487 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.196 | 0.187 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.665 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_SOUTH_0.4 | N/A | 1.487 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_SOUTH_0.4 | N/A | 1.487 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_SOUTH_0.4 | N/A | 1.487 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.186 | 0.178 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.738 | 0.665 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_WEST_0.4 | N/A | 1.487 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_WEST_0.4 | N/A | 1.487 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.196 | 0.187 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.723 | 0.652 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_NORTH_0.4 | N/A | 1.487 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.723 | 0.652 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_EAST_0.4 | N/A | 1.487 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.723 | 0.652 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_SOUTH_0.4 | N/A | 1.487 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.723 | 0.652 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.2619_SHGC_WEST_0.4 | N/A | 1.487 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 1.8389391688E-002 | 1.1966103570E-002 | Pass | Pass | 0.4851155918 | 0.4922178458 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2441486622 | 0.1466509711 | Pass | Pass | 0.4825346596 | 0.4923215846 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1061641478 | 7.1113675332E-002 | Pass | Pass | 0.4830191934 | 0.4818643387 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1022784217 | 5.9301963312E-002 | Pass | Pass | 0.4819700136 | 0.4797833083 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 8.1838652362E-002 | 7.1192302766E-002 | Pass | Pass | 1.0176750382 | 1.4980280307 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2081327915 | 0.1957970913 | Pass | Pass | 0.6668572388 | 0.6385024679 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6870497431 | 0.5686726660 | Pass | Pass | 0.6142183143 | 0.5679470447 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7069695584 | 0.6532150491 | Pass | Pass | 0.6157979865 | 0.6232894373 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6685868243 | 0.6286300329 | Pass | Pass | 0.6344814524 | 0.6442806299 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7036400946 | 0.6581200227 | Pass | Pass | 0.6209666958 | 0.6285568483 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5612434061 | 0.4549635952 | Pass | Pass | 0.6258830724 | 0.5809784063 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5844606573 | 0.5387924718 | Pass | Pass | 0.6529570899 | 0.6657709352 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5440316337 | 0.5094519589 | Pass | Pass | 0.6562936148 | 0.6668535239 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5823880149 | 0.5445245374 | Pass | Pass | 0.6590878104 | 0.6701820090 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4998899473 | 0.4424797860 | Pass | Pass | 0.7105165912 | 0.5851643743 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5602746164 | 0.5305380680 | Pass | Pass | 0.6883223834 | 0.6410339839 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5357261007 | 0.4970027135 | Pass | Pass | 0.7087667797 | 0.6643393542 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5574534797 | 0.5283485887 | Pass | Pass | 0.6881434628 | 0.6418638495 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2406.68 | 136.91 | 0.00 | 2476.57 | 272.66 | 5292.82 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.913 | 1.058 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.913 | 1.058 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.913 | 1.058 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.913 | 1.058 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.652 | 0.723 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.652 | 0.723 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.652 | 0.723 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.652 | 0.723 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.665 | 0.738 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.665 | 0.738 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.665 | 0.738 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.665 | 0.738 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.913 | 1.058 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.913 | 1.058 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.913 | 1.058 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.913 | 1.058 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.665 | 0.738 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.181 | 0.186 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.665 | 0.738 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.190 | 0.196 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.665 | 0.738 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.181 | 0.186 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.665 | 0.738 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.190 | 0.196 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.652 | 0.723 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.652 | 0.723 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.652 | 0.723 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.652 | 0.723 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.2619_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.487 | 0.401 | 0.401 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.2619_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.487 | 0.401 | 0.401 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.2619_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.487 | 0.401 | 0.401 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.2619_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.487 | 0.401 | 0.401 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.2619_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.487 | 0.401 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.2619_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.487 | 0.401 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.2619_SHGC_NORTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.487 | 0.401 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.2619_SHGC_EAST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.487 | 0.401 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.2619_SHGC_EAST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 1.487 | 0.401 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.2619_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.487 | 0.401 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.2619_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.487 | 0.401 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.2619_SHGC_SOUTH_0.4 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.487 | 0.401 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.2619_SHGC_WEST_0.4 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.487 | 0.401 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.2619_SHGC_WEST_0.4 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 1.487 | 0.401 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.2619_SHGC_NORTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.487 | 0.401 | 0.401 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.2619_SHGC_EAST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.487 | 0.401 | 0.401 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.2619_SHGC_SOUTH_0.4 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.487 | 0.401 | 0.401 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.2619_SHGC_WEST_0.4 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.487 | 0.401 | 0.401 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 1.487 | 0.401 | 0.401 | |||||||||||||||||
North Total or Average | 177.99 | 1.487 | 0.401 | 0.401 | |||||||||||||||||
Non-North Total or Average | 415.31 | 1.487 | 0.401 | 0.401 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 29.67 | 0.0000 | Y | 6.85 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 29.18 | 0.0000 | Y | 4.27 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 28.54 | 0.0000 | Y | 6.59 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 29.11 | 0.0000 | Y | 4.25 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 29.55 | 0.0000 | Y | 6.82 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 29.10 | 0.0000 | Y | 4.25 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 28.45 | 0.0000 | Y | 6.57 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 29.02 | 0.0000 | Y | 4.24 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 29.67 | 0.0000 | Y | 6.85 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 29.18 | 0.0000 | Y | 4.27 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 28.54 | 0.0000 | Y | 6.59 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 29.11 | 0.0000 | Y | 4.25 |
Interior Lighting Total | 5.9322 | 4982.19 | 29555.08 | 210.81 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 44.84 | 44.84 | 3.58 | |
EXTERIOR_LIGHTS_B | 408.47 | AstronomicalClock | - | 83.06 | 63.95 | 4.90 | |
EXTERIOR_LIGHTS_C | 4724.13 | AstronomicalClock | - | 83.06 | 52.41 | 46.47 | |
Exterior Lighting Total | 5557.43 | 54.95 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 80300.05 | 64292.66 | 16007.39 | 0.80 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 71517.55 | 57260.90 | 14256.65 | 0.80 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 78931.18 | 63196.66 | 15734.52 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 78918.3 | 2.80 | 9.54 | N/A | N/A | 10.81 | |
PACU_VAV_MID COOLING COIL | 70286.9 | 2.80 | 9.54 | N/A | N/A | 10.81 | |
PACU_VAV_TOP COOLING COIL | 77573.0 | 2.80 | 9.54 | N/A | N/A | 10.81 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25460.10 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 27489.80 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 50723.19 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22371.90 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14613.80 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22269.46 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14556.57 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17325.33 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11429.16 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17260.86 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11386.89 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16580.96 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10902.91 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16491.79 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10858.22 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 76044.32 | 0.81 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 77310.06 | 0.81 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 77090.78 | 0.81 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.85 | 11149.67 | 2298.46 | 1.00 | 1.14 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.32 | 9994.70 | 2313.39 | 1.00 | 1.14 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.77 | 10959.60 | 2298.46 | 1.00 | 1.14 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 78918.29 | 2.80 | 9.54 | 10.81 | 5.5234 | 3.09 | 10.55 | 4.3688 | 3.26 | 11.11 | 2.9277 | 3.43 | 11.69 | 1.2201 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 70286.91 | 2.80 | 9.54 | 10.81 | 4.9193 | 3.09 | 10.55 | 3.8910 | 3.26 | 11.11 | 2.6075 | 3.43 | 11.69 | 1.0867 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 77572.97 | 2.80 | 9.54 | 10.81 | 5.4292 | 3.09 | 10.55 | 4.2944 | 3.26 | 11.11 | 2.8778 | 3.43 | 11.69 | 1.1993 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 38196.68 | 38196.68 | 38.84 | 2.795 | 2.795 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00882 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_MID | 27906.79 | 27906.79 | 28.37 | 2.040 | 2.040 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 19.85 | 0.00700 | 0.425 | 0.00 |
CORE_TOP | 27187.92 | 27187.92 | 27.64 | 2.007 | 2.007 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00894 | 26.89 | 0.00701 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 7962.46 | 7962.46 | 38.40 | 0.588 | 0.588 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:50:00 | 24.00 | 24.00 | 0.00880 | 21.54 | 0.00700 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10631.79 | 10631.79 | 81.00 | 0.785 | 0.785 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00864 | 22.37 | 0.00700 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 16883.61 | 16883.61 | 81.43 | 1.246 | 1.246 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00864 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11144.72 | 11144.72 | 84.91 | 0.823 | 0.823 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00864 | 24.70 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6703.63 | 6703.63 | 32.33 | 0.495 | 0.495 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00887 | 21.38 | 0.00700 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8666.12 | 8666.12 | 66.02 | 0.640 | 0.640 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00868 | 22.66 | 0.00700 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 13569.05 | 13569.05 | 65.44 | 1.001 | 1.001 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00868 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9159.15 | 9159.15 | 69.78 | 0.676 | 0.676 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.00 | 24.00 | 0.00867 | 23.05 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7609.80 | 7609.80 | 36.70 | 0.562 | 0.562 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00882 | 21.38 | 0.00700 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10530.10 | 10530.10 | 80.22 | 0.777 | 0.777 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00865 | 22.08 | 0.00700 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 15829.43 | 15829.43 | 76.35 | 1.168 | 1.168 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00865 | 27.40 | 0.00701 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10443.27 | 10443.27 | 79.57 | 0.771 | 0.771 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00865 | 24.44 | 0.00700 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 10699.12 | 10699.12 | 10.88 | 0.466 | 0.466 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_MID | 19402.30 | 19402.30 | 19.73 | 0.836 | 0.836 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
CORE_TOP | 35675.44 | 35675.44 | 36.27 | 1.543 | 1.543 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15700.95 | 15700.95 | 75.73 | 0.680 | 0.680 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10255.60 | 10255.60 | 78.13 | 0.444 | 0.444 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15629.20 | 15629.20 | 75.38 | 0.677 | 0.677 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10215.51 | 10215.51 | 77.83 | 0.443 | 0.443 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 12165.10 | 12165.10 | 58.67 | 0.527 | 0.527 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8024.27 | 8024.27 | 61.13 | 0.348 | 0.348 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 12119.94 | 12119.94 | 58.45 | 0.525 | 0.525 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7994.67 | 7994.67 | 60.91 | 0.346 | 0.346 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11644.44 | 11644.44 | 56.16 | 0.504 | 0.504 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7656.13 | 7656.13 | 58.33 | 0.332 | 0.332 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11581.98 | 11581.98 | 55.86 | 0.502 | 0.502 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7624.83 | 7624.83 | 58.09 | 0.330 | 0.330 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.85 | 4.85 | 2.20 | 2.20 | 4.8509 | 2.2017 | 4.8509 | 0.4539 | 0.3000 |
PACU_VAV_MID | 4.32 | 4.32 | 2.50 | 2.50 | 4.3204 | 2.5038 | 4.3204 | 0.5795 | 0.3000 |
PACU_VAV_TOP | 4.77 | 4.77 | 3.79 | 3.79 | 4.7682 | 3.7876 | 4.7682 | 0.7943 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25460.101 | 25460.101 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 25460.10 | 15316.63 | 0.465841 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 10699.12 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 27489.803 | 27489.803 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 27489.80 | 27489.80 | 0.836077 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 19402.30 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 50723.187 | 50723.187 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 50723.19 | 50723.19 | 1.542698 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 35675.44 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22371.898 | 22371.898 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22371.90 | 22371.90 | 0.680420 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799140 | 50.8592 | 15700.95 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14613.802 | 14613.802 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14613.80 | 14613.80 | 0.444465 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799123 | 50.8581 | 10255.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22269.460 | 22269.460 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22269.46 | 22269.46 | 0.677305 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799136 | 50.8589 | 15629.20 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14556.567 | 14556.567 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14556.57 | 14556.57 | 0.442724 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799119 | 50.8579 | 10215.51 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17325.333 | 17325.333 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17325.33 | 17325.33 | 0.526934 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799392 | 50.8749 | 12165.10 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11429.160 | 11429.160 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11429.16 | 11429.16 | 0.347607 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799390 | 50.8748 | 8024.27 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17260.857 | 17260.857 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17260.86 | 17260.86 | 0.524973 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799389 | 50.8747 | 12119.94 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11386.894 | 11386.894 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11386.89 | 11386.89 | 0.346322 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799388 | 50.8747 | 7994.67 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 16580.960 | 16580.960 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16580.96 | 16580.96 | 0.504294 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799007 | 50.8508 | 11644.44 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 10902.913 | 10902.913 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10902.91 | 10902.91 | 0.331602 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799000 | 50.8504 | 7656.13 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 16491.790 | 16491.790 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16491.79 | 16491.79 | 0.501582 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799001 | 50.8504 | 11581.98 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 10858.217 | 10858.217 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10858.22 | 10858.22 | 0.330242 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798995 | 50.8501 | 7624.83 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 80300.050 | 64292.657 | 4.850926 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 81567.17 | 81567.17 | 4.850926 | 24.84 | 16.41 | 0.00836132 | 10.90 | 10.90 | 0.00836132 | 27.40 | 0.00700714 | 16.15 | 24.6380 | 24.00 | 0.00880478 | 46.6405 | 65646.01 | 0.00 | 82800.13 | 64652.51 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 76044.316 | 76044.316 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76044.32 | 76044.32 | 1.455278 | -31.07 | -31.07 | 0.00148079 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 82.1266 | 18.11 | 0.00798863 | 60.8604 | 21333.94 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 71517.552 | 57260.904 | 4.320375 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 72646.09 | 72646.09 | 4.320375 | 24.94 | 16.42 | 0.00833198 | 10.89 | 10.89 | 0.00833198 | 27.40 | 0.00700714 | 16.15 | 27.6636 | 24.00 | 0.00884005 | 46.8247 | 58420.73 | 0.00 | 73744.20 | 57581.40 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 77310.055 | 77310.055 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 77310.06 | 77310.06 | 1.296113 | -37.27 | -37.27 | 0.00068120 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 92.2119 | 17.60 | 0.00797567 | 62.7325 | 23661.09 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 78931.178 | 63196.663 | 4.768232 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 80176.70 | 80176.70 | 4.768232 | 24.86 | 16.41 | 0.00835428 | 10.90 | 10.90 | 0.00835428 | 27.40 | 0.00700714 | 16.15 | 25.0653 | 24.00 | 0.00880840 | 46.6593 | 64233.69 | 0.00 | 81388.64 | 63550.38 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 77090.783 | 77090.783 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 77090.78 | 77090.78 | 1.430470 | -32.44 | -32.44 | 0.00136712 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 83.5509 | 15.60 | 0.00797880 | 71.2696 | 27345.91 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25460.101 | 25460.101 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 25460.10 | 15316.63 | 1.0000 | 0.55222620 | 0.465841 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25460.10 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 10699.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 27489.803 | 27489.803 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 27489.80 | 27489.80 | 1.0000 | 0.99111801 | 0.836077 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27489.80 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 19402.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 50723.187 | 50723.187 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 50723.19 | 50723.19 | 1.0000 | 1.82877496 | 1.542698 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50723.19 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 35675.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 22371.898 | 22371.898 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22371.90 | 22371.90 | 1.0000 | 0.80659692 | 0.680420 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22371.90 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00799140 | 21.00 | 0.00799140 | 50.8592 | 15700.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 14613.802 | 14613.802 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14613.80 | 14613.80 | 1.0000 | 0.52688636 | 0.444465 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14613.80 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00799123 | 21.00 | 0.00799123 | 50.8581 | 10255.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 22269.460 | 22269.460 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22269.46 | 22269.46 | 1.0000 | 0.80290363 | 0.677305 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22269.46 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00799136 | 21.00 | 0.00799136 | 50.8589 | 15629.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 14556.567 | 14556.567 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14556.57 | 14556.57 | 1.0000 | 0.52482280 | 0.442724 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14556.57 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00799119 | 21.00 | 0.00799119 | 50.8579 | 10215.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17325.333 | 17325.333 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17325.33 | 17325.33 | 1.0000 | 0.62464798 | 0.526934 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17325.33 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00799392 | 21.00 | 0.00799392 | 50.8749 | 12165.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11429.160 | 11429.160 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11429.16 | 11429.16 | 1.0000 | 0.41206720 | 0.347607 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11429.16 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00799390 | 21.00 | 0.00799390 | 50.8748 | 8024.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 17260.857 | 17260.857 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17260.86 | 17260.86 | 1.0000 | 0.62232333 | 0.524973 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17260.86 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00799389 | 21.00 | 0.00799389 | 50.8747 | 12119.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11386.894 | 11386.894 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11386.89 | 11386.89 | 1.0000 | 0.41054335 | 0.346322 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11386.89 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00799388 | 21.00 | 0.00799388 | 50.8747 | 7994.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16580.960 | 16580.960 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16580.96 | 16580.96 | 1.0000 | 0.59781030 | 0.504294 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16580.96 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00799007 | 21.00 | 0.00799007 | 50.8508 | 11644.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10902.913 | 10902.913 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10902.91 | 10902.91 | 1.0000 | 0.39309388 | 0.331602 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10902.91 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00799000 | 21.00 | 0.00799000 | 50.8504 | 7656.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16491.790 | 16491.790 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16491.79 | 16491.79 | 1.0000 | 0.59459537 | 0.501582 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16491.79 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00799001 | 21.00 | 0.00799001 | 50.8504 | 11581.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 10858.217 | 10858.217 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10858.22 | 10858.22 | 1.0000 | 0.39148241 | 0.330242 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10858.22 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798995 | 21.00 | 0.00798995 | 50.8501 | 7624.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 80300.050 | 64292.657 | 4.850926 | -999.0 | -999.000 | -999.0000 | 1.02321 | 1.00000 | 1020.3833 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.850926 | 5.75047832 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 81567.17 | 81567.17 | 1.0158 | 5.75047832 | 4.850926 | 24.84 | 16.41 | 0.00836132 | 46255.3 | 10.90 | 10.90 | 0.00836132 | 32033.2 | -999.0 | -999.00 | -999.00 | -999.00 | 11149.667 | 70417.51 | 27.40 | 0.00700714 | 16.15 | 1.19517000 | 24.6380 | 24.00 | 0.00880478 | 24.00 | 0.00880478 | 46.6405 | 65646.01 | 0.00 | 82800.13 | 64652.51 | 5.52337790 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 76044.316 | 76044.316 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.850926 | 5.75047832 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 76044.32 | 76044.32 | 1.0000 | 1.72514350 | 1.455278 | -31.07 | -31.07 | 0.00148079 | -27599.4 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76044.32 | -41.90 | 0.00006450 | -41.90 | 1.19517000 | 82.1266 | 18.71 | 0.00798849 | 18.11 | 0.00798863 | 60.8604 | 21333.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 71517.552 | 57260.904 | 4.320375 | -999.0 | -999.000 | -999.0000 | 1.01508 | 1.00000 | 1020.3287 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.320375 | 5.12154265 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 72646.09 | 72646.09 | 1.0158 | 5.12154265 | 4.320375 | 24.94 | 16.42 | 0.00833198 | 46286.4 | 10.89 | 10.89 | 0.00833198 | 31946.5 | -999.0 | -999.00 | -999.00 | -999.00 | 9994.698 | 62651.39 | 27.40 | 0.00700714 | 16.15 | 1.19517000 | 27.6636 | 24.00 | 0.00884005 | 24.00 | 0.00884005 | 46.8247 | 58420.73 | 0.00 | 73744.20 | 57581.40 | 4.91928043 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 77310.055 | 77310.055 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.320375 | 5.12154265 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 77310.06 | 77310.06 | 1.0000 | 1.53646279 | 1.296113 | -37.27 | -37.27 | 0.00068120 | -35797.6 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 77310.06 | -41.90 | 0.00006450 | -41.90 | 1.19517000 | 92.2119 | 17.50 | 0.00798298 | 17.60 | 0.00797567 | 62.7325 | 23661.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 78931.178 | 63196.663 | 4.768232 | -999.0 | -999.000 | -999.0000 | 1.02192 | 1.00000 | 1020.3702 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.768232 | 5.65245013 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 80176.70 | 80176.70 | 1.0158 | 5.65245013 | 4.768232 | 24.86 | 16.41 | 0.00835428 | 46256.2 | 10.90 | 10.90 | 0.00835428 | 32015.4 | -999.0 | -999.00 | -999.00 | -999.00 | 10959.599 | 69217.10 | 27.40 | 0.00700714 | 16.15 | 1.19517000 | 25.0653 | 24.00 | 0.00880840 | 24.00 | 0.00880840 | 46.6593 | 64233.69 | 0.00 | 81388.64 | 63550.38 | 5.42922107 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.23 | 14.40 | 0.00989645 | 40331.5 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 77090.783 | 77090.783 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.768232 | 5.65245013 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 77090.78 | 77090.78 | 1.0000 | 1.69573504 | 1.430470 | -32.44 | -32.44 | 0.00136712 | -29262.2 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 77090.78 | -41.90 | 0.00006450 | -41.90 | 1.19517000 | 83.5509 | 15.60 | 0.00798355 | 15.60 | 0.00797880 | 71.2696 | 27345.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.85 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.32 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.77 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2083.33 | 3835.17 | 1259.17 |
CORE_MID | 2779.33 | 4400.50 | 2310.33 |
CORE_TOP | 3247.00 | 4673.17 | 2892.67 |
PERIMETER_TOP_ZN_3 | 3845.00 | 4697.00 | 3328.33 |
PERIMETER_TOP_ZN_2 | 4065.17 | 4337.00 | 3118.67 |
PERIMETER_TOP_ZN_1 | 3865.67 | 4357.00 | 2931.33 |
PERIMETER_TOP_ZN_4 | 3921.83 | 4661.67 | 3225.33 |
PERIMETER_BOT_ZN_3 | 3555.83 | 4856.83 | 3224.83 |
PERIMETER_BOT_ZN_2 | 3874.17 | 4234.00 | 2935.50 |
PERIMETER_BOT_ZN_1 | 3673.33 | 4659.17 | 2960.33 |
PERIMETER_BOT_ZN_4 | 3675.67 | 4614.33 | 3062.00 |
PERIMETER_MID_ZN_3 | 3650.17 | 4468.83 | 3044.67 |
PERIMETER_MID_ZN_2 | 3317.33 | 3586.67 | 2472.50 |
PERIMETER_MID_ZN_1 | 3678.17 | 4082.00 | 2623.50 |
PERIMETER_MID_ZN_4 | 3758.00 | 4395.33 | 2971.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5124.33 | 5195.00 | 3488.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 1.83 | 0.17 | 1.67 | 0.00 |
CORE_MID | 6.50 | 0.00 | 5.00 | 0.00 |
CORE_TOP | 42.67 | 0.00 | 33.33 | 0.00 |
PERIMETER_TOP_ZN_3 | 404.50 | 0.17 | 227.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 234.83 | 7.83 | 63.33 | 7.83 |
PERIMETER_TOP_ZN_1 | 195.50 | 12.50 | 47.83 | 12.33 |
PERIMETER_TOP_ZN_4 | 236.33 | 11.33 | 66.67 | 3.33 |
PERIMETER_BOT_ZN_3 | 289.50 | 0.17 | 234.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 67.17 | 4.83 | 16.50 | 4.50 |
PERIMETER_BOT_ZN_1 | 1177.33 | 5.17 | 1113.17 | 5.00 |
PERIMETER_BOT_ZN_4 | 71.67 | 2.33 | 18.83 | 0.50 |
PERIMETER_MID_ZN_3 | 159.00 | 2.17 | 103.00 | 0.00 |
PERIMETER_MID_ZN_2 | 73.33 | 11.00 | 18.00 | 9.67 |
PERIMETER_MID_ZN_1 | 54.00 | 13.50 | 10.50 | 13.33 |
PERIMETER_MID_ZN_4 | 74.67 | 12.50 | 20.33 | 4.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1445.33 | 57.33 | 1209.83 | 41.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.809 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.622 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.600 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.773 | 0.013 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 1.207 | 0.014 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 1.237 | 0.013 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 1.075 | 0.014 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.655 | 0.007 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 1.023 | 0.008 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 1.046 | 1.337 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.869 | 0.008 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.726 | 0.011 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 1.112 | 0.013 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 1.235 | 0.011 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 1.057 | 0.012 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.84 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.92 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.56 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.61 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.92 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.84 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.92 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.56 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.61 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.92 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.30 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 12924276.22 | 0.00 | 12924276.22 | 0.00 | 12924276.22 | 13393058.27 | 6562.01 | 25.05 | 2172.95 | 468.23 |
CORE_MID | 9965596.71 | 0.00 | 9965596.71 | 0.00 | 9965596.71 | 13393058.27 | 6864.14 | 17.95 | 1877.91 | 358.21 |
CORE_TOP | 9570760.23 | 0.00 | 9570760.23 | 0.00 | 9570760.23 | 13393058.27 | 6919.92 | 18.87 | 1821.22 | 85.79 |
PERIMETER_TOP_ZN_3 | 2596492.88 | 0.00 | 2596492.88 | 92601.61 | 2689094.49 | 2823374.22 | 4216.56 | 24.44 | 4519.01 | 85.79 |
PERIMETER_TOP_ZN_2 | 2558133.15 | 0.00 | 2558133.15 | 61734.03 | 2619867.18 | 1787429.43 | 4161.69 | 0.94 | 4597.36 | 85.79 |
PERIMETER_TOP_ZN_1 | 4141943.19 | 0.00 | 4141943.19 | 92601.61 | 4234544.79 | 2823374.22 | 4160.77 | 1.62 | 4597.61 | 85.79 |
PERIMETER_TOP_ZN_4 | 2290572.21 | 0.00 | 2290572.21 | 61734.03 | 2352306.24 | 1787312.18 | 4157.45 | 1.67 | 4600.88 | 85.79 |
PERIMETER_BOT_ZN_3 | 2226420.54 | 0.00 | 2226420.54 | 49235.47 | 2275656.01 | 2823374.22 | 5066.32 | 146.09 | 3547.59 | 468.23 |
PERIMETER_BOT_ZN_2 | 2182515.38 | 0.00 | 2182515.38 | 32823.45 | 2215338.83 | 1787429.43 | 4204.10 | 22.61 | 4533.28 | 468.23 |
PERIMETER_BOT_ZN_1 | 3551859.23 | 0.00 | 3551859.23 | 4542235.54 | 8094094.77 | 2823374.22 | 4199.40 | 19.65 | 4540.95 | 468.23 |
PERIMETER_BOT_ZN_4 | 1864644.59 | 0.00 | 1864644.59 | 32823.45 | 1897468.04 | 1787312.18 | 4187.90 | 10.75 | 4561.35 | 468.23 |
PERIMETER_MID_ZN_3 | 2446913.81 | 0.00 | 2446913.81 | 77083.48 | 2523997.30 | 2823374.22 | 6138.78 | 60.98 | 2560.24 | 358.18 |
PERIMETER_MID_ZN_2 | 2602223.72 | 0.00 | 2602223.72 | 51388.68 | 2653612.40 | 1787429.43 | 4122.14 | 2.92 | 4634.94 | 1267.14 |
PERIMETER_MID_ZN_1 | 4148250.59 | 0.00 | 4148250.59 | 77083.48 | 4225334.07 | 2823374.22 | 4126.69 | 1.33 | 4631.98 | 358.18 |
PERIMETER_MID_ZN_4 | 2260917.47 | 0.00 | 2260917.47 | 51388.68 | 2312306.15 | 1787312.18 | 4122.69 | 3.48 | 4633.83 | 358.14 |
Total Facility | 65331519.92 | 0.00 | 65331519.92 | 5222733.51 | 70554253.43 | 67843644.98 | 7028.99 | 321.91 | 4706.96 | 1498.85 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.5925 | 0.0000 | 0.5925 | 0.0000 | 0.5925 | 0.4247 | 3810.78 | 24.10 | 2108.12 |
CORE_MID | 0.4565 | 0.0000 | 0.4565 | 0.0000 | 0.4565 | 0.4247 | 4112.11 | 17.28 | 1813.61 |
CORE_TOP | 0.4403 | 0.0000 | 0.4403 | 0.0000 | 0.4403 | 0.4247 | 4157.78 | 18.03 | 1767.19 |
PERIMETER_TOP_ZN_3 | 0.1196 | 0.0000 | 0.1196 | 0.0021 | 0.1217 | 0.0895 | 1456.85 | 24.21 | 4461.93 |
PERIMETER_TOP_ZN_2 | 0.1181 | 0.0000 | 0.1181 | 0.0014 | 0.1195 | 0.0567 | 1402.29 | 0.94 | 4539.77 |
PERIMETER_TOP_ZN_1 | 0.1913 | 0.0000 | 0.1913 | 0.0021 | 0.1934 | 0.0895 | 1401.36 | 1.62 | 4540.02 |
PERIMETER_TOP_ZN_4 | 0.1053 | 0.0000 | 0.1053 | 0.0014 | 0.1067 | 0.0567 | 1398.05 | 1.67 | 4543.28 |
PERIMETER_BOT_ZN_3 | 0.1015 | 0.0000 | 0.1015 | 0.0011 | 0.1027 | 0.0895 | 2315.78 | 146.09 | 3481.13 |
PERIMETER_BOT_ZN_2 | 0.1001 | 0.0000 | 0.1001 | 0.0007 | 0.1009 | 0.0567 | 1454.48 | 22.53 | 4465.99 |
PERIMETER_BOT_ZN_1 | 0.1631 | 0.0000 | 0.1631 | 0.2111 | 0.3742 | 0.0895 | 1449.78 | 19.57 | 4473.66 |
PERIMETER_BOT_ZN_4 | 0.0851 | 0.0000 | 0.0851 | 0.0007 | 0.0859 | 0.0567 | 1438.32 | 10.73 | 4493.95 |
PERIMETER_MID_ZN_3 | 0.1123 | 0.0000 | 0.1123 | 0.0017 | 0.1140 | 0.0895 | 3387.44 | 60.54 | 2495.02 |
PERIMETER_MID_ZN_2 | 0.1089 | 0.0000 | 0.1089 | 0.0012 | 0.1102 | 0.0567 | 1372.83 | 2.92 | 3658.25 |
PERIMETER_MID_ZN_1 | 0.1910 | 0.0000 | 0.1910 | 0.0017 | 0.1927 | 0.0895 | 1377.38 | 1.33 | 4564.29 |
PERIMETER_MID_ZN_4 | 0.1035 | 0.0000 | 0.1035 | 0.0012 | 0.1047 | 0.0567 | 1373.39 | 3.48 | 4566.14 |
Total Facility | 2.9893 | 0.0000 | 2.9893 | 0.2265 | 3.2157 | 2.1513 | 4238.56 | 319.14 | 4600.77 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 31969376.02 | 0.00 | 31969376.02 | 22614548.33 | 4151.04 | 2.33 | 4606.63 | 468.20 |
PACU_VAV_MID | 30106314.80 | 0.00 | 30106314.80 | 22614548.33 | 4118.90 | 2.75 | 4638.35 | 356.89 |
PACU_VAV_TOP | 29732497.68 | 0.00 | 29732497.68 | 22614548.33 | 4154.18 | 1.47 | 4604.35 | 85.68 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.4649 | 0.0000 | 1.4649 | 0.7171 | 1401.42 | 2.33 | 4539.25 |
PACU_VAV_MID | 1.3814 | 0.0000 | 1.3814 | 0.7171 | 1369.59 | 2.75 | 4570.66 |
PACU_VAV_TOP | 1.3696 | 0.0000 | 1.3696 | 0.7171 | 1394.78 | 1.47 | 4546.75 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 2838.63 | 0.00 | 0.00 | 0.00 | 2479.02 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 2608.31 | 0.00 | 0.00 | 0.00 | 2619.96 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2161.18 | 0.00 | 0.00 | 0.00 | 2627.90 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.4913 | 0.0000 | 0.0000 | 0.0000 | 1.1300 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.3696 | 0.0000 | 0.0000 | 0.0000 | 1.0979 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.5195 | 0.0000 | 0.0000 | 0.0000 | 1.1083 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 831 |
Defaulted Fields | 545 |
Fields with Defaults | 2290 |
Autosized Fields | 152 |
Autosizable Fields | 205 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1780.69 | 12344.18 | 09-APR-17:10 | 272878.57 | 02-JAN-08:10 |
Electricity:Building | 916.24 | 12175.61 | 09-APR-17:10 | 67242.49 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 284.50 | 4029.56 | 01-JAN-00:10 | 22405.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 916.24 | 12175.61 | 09-APR-17:10 | 67242.49 | 02-JAN-08:10 |
InteriorLights:Electricity | 210.81 | 934.27 | 19-FEB-11:10 | 21377.78 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 210.81 | 934.27 | 19-FEB-11:10 | 21377.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 210.81 | 934.27 | 19-FEB-11:10 | 21377.78 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 210.81 | 934.27 | 19-FEB-11:10 | 21377.78 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 31.18 | 409.68 | 09-APR-17:10 | 2324.90 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.85 | 23.57 | 19-FEB-11:10 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.85 | 23.57 | 19-FEB-11:10 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.67 | 259.34 | 09-APR-17:10 | 1471.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.27 | 14.92 | 05-FEB-10:00 | 563.23 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 4.27 | 14.92 | 05-FEB-10:00 | 563.23 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.92 | 409.67 | 12-MAR-17:10 | 2324.89 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.59 | 23.57 | 16-JAN-11:40 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 6.59 | 23.57 | 16-JAN-11:40 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.66 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.25 | 14.92 | 05-FEB-13:20 | 563.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 4.25 | 14.92 | 05-FEB-13:20 | 563.19 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 31.16 | 409.68 | 02-APR-17:10 | 2324.90 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.82 | 23.57 | 19-FEB-10:50 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.82 | 23.57 | 19-FEB-10:50 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.66 | 259.34 | 09-APR-17:10 | 1471.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.25 | 14.92 | 29-JAN-11:30 | 563.23 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 4.25 | 14.92 | 29-JAN-11:30 | 563.23 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.90 | 409.67 | 12-MAR-17:10 | 2324.89 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 23.57 | 15-JAN-12:30 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 6.57 | 23.57 | 15-JAN-12:30 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.64 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.24 | 14.92 | 05-FEB-12:30 | 563.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 4.24 | 14.92 | 05-FEB-12:30 | 563.19 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 31.18 | 409.68 | 09-APR-17:10 | 2324.90 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.85 | 23.57 | 19-FEB-11:10 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.85 | 23.57 | 19-FEB-11:10 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.67 | 259.34 | 09-APR-17:10 | 1471.80 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.27 | 14.92 | 05-FEB-10:00 | 563.23 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 4.27 | 14.92 | 05-FEB-10:00 | 563.23 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.92 | 409.67 | 12-MAR-17:10 | 2324.89 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.59 | 23.57 | 16-JAN-11:40 | 889.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 6.59 | 23.57 | 16-JAN-11:40 | 889.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.66 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.25 | 14.92 | 05-FEB-13:20 | 563.19 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 4.25 | 14.92 | 05-FEB-13:20 | 563.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 809.48 | 168.57 | 10-JUN-18:20 | 225862.55 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 11.67 | 168.34 | 01-JAN-00:10 | 835.33 | 12-JAN-08:30 |
Transformer:ExteriorEquipment:Electricity | 11.67 | 168.34 | 01-JAN-00:10 | 835.33 | 12-JAN-08:30 |
ElectricityPurchased:Facility | 1780.69 | 12344.18 | 09-APR-17:10 | 272878.57 | 02-JAN-08:10 |
ElectricityPurchased:Plant | 1780.69 | 12344.18 | 09-APR-17:10 | 272878.57 | 02-JAN-08:10 |
Cogeneration:ElectricityPurchased | 1780.69 | 12344.18 | 09-APR-17:10 | 272878.57 | 02-JAN-08:10 |
General:Cogeneration:ElectricityPurchased | 1780.69 | 12344.18 | 09-APR-17:10 | 272878.57 | 02-JAN-08:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1780.69 | 12344.18 | 09-APR-17:10 | 272878.57 | 02-JAN-08:10 |
ElectricityNet:Plant | 1780.69 | 12344.18 | 09-APR-17:10 | 272878.57 | 02-JAN-08:10 |
Cogeneration:ElectricityNet | 1780.69 | 12344.18 | 09-APR-17:10 | 272878.57 | 02-JAN-08:10 |
General:Cogeneration:ElectricityNet | 1780.69 | 12344.18 | 09-APR-17:10 | 272878.57 | 02-JAN-08:10 |
Heating:Electricity | 639.08 | 0.00 | 01-JAN-00:40 | 216624.51 | 02-JAN-06:20 |
General:Heating:Electricity | 639.08 | 0.00 | 01-JAN-00:40 | 216624.51 | 02-JAN-06:20 |
Fans:Electricity | 88.28 | 0.00 | 01-JAN-00:40 | 24674.61 | 12-JUL-15:10 |
General:Fans:Electricity | 88.28 | 0.00 | 01-JAN-00:40 | 24674.61 | 12-JUL-15:10 |
ExteriorLights:Electricity | 54.95 | 0.00 | 01-JAN-11:20 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 54.95 | 0.00 | 01-JAN-11:20 | 5557.43 | 01-JAN-06:10 |
HeatRecovery:Electricity | 25.33 | 0.00 | 01-JAN-00:10 | 2722.67 | 06-JAN-18:30 |
General:HeatRecovery:Electricity | 25.33 | 0.00 | 01-JAN-00:10 | 2722.67 | 06-JAN-18:30 |
Cooling:Electricity | 45.13 | 0.00 | 01-JAN-00:10 | 43567.01 | 30-JUN-14:30 |
General:Cooling:Electricity | 45.13 | 0.00 | 01-JAN-00:10 | 43567.01 | 30-JUN-14:30 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 5.92 | 0.00 | 01-JAN-00:10 | 600.72 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 349.92 | 1156.00 | 12-JAN-22:10 | 207548.76 | 12-JAN-07:30 |
NaturalGas:HVAC | 223.55 | 0.00 | 01-JAN-00:40 | 199286.53 | 12-JAN-07:30 |
Heating:NaturalGas | 223.55 | 0.00 | 01-JAN-00:40 | 199286.53 | 12-JAN-07:30 |
General:Heating:NaturalGas | 223.55 | 0.00 | 01-JAN-00:40 | 199286.53 | 12-JAN-07:30 |
NaturalGas:Plant | 126.37 | 1156.00 | 04-JAN-05:20 | 13393.85 | 30-JAN-12:30 |
WaterSystems:NaturalGas | 126.37 | 1156.00 | 04-JAN-05:20 | 13393.85 | 30-JAN-12:30 |
Water Heater:WaterSystems:NaturalGas | 126.37 | 1156.00 | 04-JAN-05:20 | 13393.85 | 30-JAN-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2787.28 | 0.00 | 01-JAN-00:40 | 559459.37 | 27-FEB-07:10 |
EnergyTransfer:Building | 1263.59 | 0.00 | 01-JAN-00:40 | 218646.18 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 176.28 | 0.00 | 01-JAN-00:40 | 24803.44 | 24-JUL-08:00 |
Heating:EnergyTransfer | 579.57 | 0.00 | 01-JAN-00:40 | 218646.18 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.69 | 0.00 | 01-JAN-00:20 | 20503.71 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 579.57 | 0.00 | 01-JAN-00:40 | 218646.18 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 1.69 | 0.00 | 01-JAN-00:20 | 20503.71 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 684.02 | 0.00 | 01-JAN-00:40 | 143560.68 | 12-JUL-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 174.59 | 0.00 | 01-JAN-00:40 | 24803.44 | 24-JUL-08:00 |
General:Cooling:EnergyTransfer | 684.02 | 0.00 | 01-JAN-00:40 | 143560.68 | 12-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 174.59 | 0.00 | 01-JAN-00:40 | 24803.44 | 24-JUL-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 83.92 | 0.00 | 01-JAN-00:40 | 18076.40 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 69.64 | 0.00 | 01-JAN-00:40 | 18076.40 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 69.64 | 0.00 | 01-JAN-00:40 | 18076.40 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.28 | 0.00 | 01-JAN-00:10 | 7711.66 | 21-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 14.28 | 0.00 | 01-JAN-00:10 | 7711.66 | 21-JUL-14:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 36.33 | 0.00 | 01-JAN-00:40 | 10898.57 | 02-JAN-07:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.15 | 0.00 | 01-JAN-00:40 | 10898.57 | 02-JAN-07:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 26.15 | 0.00 | 01-JAN-00:40 | 10898.57 | 02-JAN-07:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.18 | 0.00 | 01-JAN-00:10 | 4070.24 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.18 | 0.00 | 01-JAN-00:10 | 4070.24 | 12-JUL-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 33.65 | 0.00 | 01-JAN-00:40 | 8762.80 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.33 | 0.00 | 01-JAN-00:40 | 8762.80 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 18.33 | 0.00 | 01-JAN-00:40 | 8762.80 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.32 | 0.00 | 01-JAN-00:10 | 4411.01 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.32 | 0.00 | 01-JAN-00:10 | 4411.01 | 12-JUL-16:00 |
EnergyTransfer:Zone:CORE_MID | 118.09 | 0.00 | 01-JAN-00:40 | 24081.96 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 11.96 | 0.00 | 01-JAN-00:40 | 24081.96 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 11.96 | 0.00 | 01-JAN-00:40 | 24081.96 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 106.13 | 0.00 | 01-JAN-00:20 | 16676.94 | 24-JUL-07:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 106.13 | 0.00 | 01-JAN-00:20 | 16676.94 | 24-JUL-07:50 |
EnergyTransfer:Zone:CORE_TOP | 129.25 | 0.00 | 01-JAN-00:40 | 26614.64 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 40.61 | 0.00 | 01-JAN-00:40 | 26614.64 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 40.61 | 0.00 | 01-JAN-00:40 | 26614.64 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 88.64 | 0.00 | 01-JAN-00:20 | 16887.63 | 12-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 88.64 | 0.00 | 01-JAN-00:20 | 16887.63 | 12-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 67.92 | 0.00 | 01-JAN-00:40 | 9800.09 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 49.03 | 0.00 | 01-JAN-00:40 | 9800.09 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 49.03 | 0.00 | 01-JAN-00:40 | 9800.09 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 18.89 | 0.00 | 01-JAN-00:10 | 5634.34 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 18.89 | 0.00 | 01-JAN-00:10 | 5634.34 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.84 | 0.00 | 01-JAN-00:40 | 9852.01 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.14 | 0.00 | 01-JAN-00:40 | 9824.94 | 27-NOV-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 30.14 | 0.00 | 01-JAN-00:40 | 9824.94 | 27-NOV-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.70 | 0.00 | 01-JAN-00:20 | 9852.01 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.70 | 0.00 | 01-JAN-00:20 | 9852.01 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 78.90 | 0.00 | 01-JAN-00:40 | 15494.09 | 27-NOV-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 40.49 | 0.00 | 01-JAN-00:40 | 15494.09 | 27-NOV-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 40.49 | 0.00 | 01-JAN-00:40 | 15494.09 | 27-NOV-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.40 | 0.00 | 01-JAN-00:20 | 14097.09 | 10-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 38.40 | 0.00 | 01-JAN-00:20 | 14097.09 | 10-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.05 | 0.00 | 01-JAN-00:40 | 10220.57 | 27-NOV-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.91 | 0.00 | 01-JAN-00:40 | 10220.57 | 27-NOV-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 31.91 | 0.00 | 01-JAN-00:40 | 10220.57 | 27-NOV-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 18.14 | 0.00 | 01-JAN-00:20 | 7896.72 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 18.14 | 0.00 | 01-JAN-00:20 | 7896.72 | 11-JUL-17:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 50.91 | 0.00 | 01-JAN-00:40 | 7455.63 | 27-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 34.98 | 0.00 | 01-JAN-00:40 | 7455.63 | 27-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 34.98 | 0.00 | 01-JAN-00:40 | 7455.63 | 27-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 15.93 | 0.00 | 01-JAN-00:10 | 4681.30 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 15.93 | 0.00 | 01-JAN-00:10 | 4681.30 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 41.55 | 0.00 | 01-JAN-00:40 | 8004.41 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.83 | 0.00 | 01-JAN-00:40 | 8004.41 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.83 | 0.00 | 01-JAN-00:40 | 8004.41 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 19.72 | 0.00 | 01-JAN-00:20 | 7357.91 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 19.72 | 0.00 | 01-JAN-00:20 | 7357.91 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 112.98 | 0.00 | 01-JAN-00:40 | 24894.48 | 12-JAN-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 91.38 | 0.00 | 01-JAN-00:40 | 24894.48 | 12-JAN-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 91.38 | 0.00 | 01-JAN-00:40 | 24894.48 | 12-JAN-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 21.60 | 0.00 | 01-JAN-00:20 | 12527.17 | 21-JUL-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 21.60 | 0.00 | 01-JAN-00:20 | 12527.17 | 21-JUL-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 38.28 | 0.00 | 01-JAN-00:40 | 8386.22 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.36 | 0.00 | 01-JAN-00:40 | 8386.22 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 23.36 | 0.00 | 01-JAN-00:40 | 8386.22 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 0.00 | 01-JAN-00:20 | 6163.49 | 31-JUL-18:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 14.92 | 0.00 | 01-JAN-00:20 | 6163.49 | 31-JUL-18:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 48.74 | 0.00 | 01-JAN-00:40 | 7869.88 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.61 | 0.00 | 01-JAN-00:40 | 7869.88 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.61 | 0.00 | 01-JAN-00:40 | 7869.88 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 20.13 | 0.00 | 01-JAN-00:10 | 6140.59 | 11-JUL-06:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 20.13 | 0.00 | 01-JAN-00:10 | 6140.59 | 11-JUL-06:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 42.21 | 0.00 | 01-JAN-00:40 | 9643.88 | 07-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 18.08 | 0.00 | 01-JAN-00:40 | 8437.57 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 18.08 | 0.00 | 01-JAN-00:40 | 8437.57 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 24.13 | 0.00 | 01-JAN-00:20 | 9643.88 | 07-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 24.13 | 0.00 | 01-JAN-00:20 | 9643.88 | 07-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 63.72 | 0.00 | 01-JAN-00:40 | 13611.06 | 10-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 22.72 | 0.00 | 01-JAN-00:40 | 12595.86 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 22.72 | 0.00 | 01-JAN-00:40 | 12595.86 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 41.00 | 0.00 | 01-JAN-00:20 | 13611.06 | 10-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 41.00 | 0.00 | 01-JAN-00:20 | 13611.06 | 10-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 37.97 | 0.00 | 01-JAN-00:40 | 8387.66 | 27-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 18.67 | 0.00 | 01-JAN-00:40 | 8387.66 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 18.67 | 0.00 | 01-JAN-00:40 | 8387.66 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 19.30 | 0.00 | 01-JAN-00:20 | 7506.98 | 11-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 19.30 | 0.00 | 01-JAN-00:20 | 7506.98 | 11-JUL-17:40 |
PlantLoopHeatingDemand:Facility | 64.03 | 0.00 | 01-JAN-00:10 | 7551.91 | 25-JAN-12:30 |
PlantLoopHeatingDemand:Plant | 64.03 | 0.00 | 01-JAN-00:10 | 7551.91 | 25-JAN-12:30 |
WaterSystems:PlantLoopHeatingDemand | 64.03 | 0.00 | 01-JAN-00:10 | 7551.91 | 25-JAN-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 64.03 | 0.00 | 01-JAN-00:10 | 7551.91 | 25-JAN-12:30 |
EnergyTransfer:HVAC | 1459.66 | 0.00 | 01-JAN-00:40 | 348470.57 | 27-FEB-07:10 |
HeatingCoils:EnergyTransfer | 820.16 | 0.00 | 01-JAN-00:40 | 348470.57 | 27-FEB-07:10 |
HeatRecoveryForHeating:EnergyTransfer | 454.26 | 0.00 | 01-JAN-00:10 | 99466.60 | 07-NOV-07:20 |
HeatRecoveryForCooling:EnergyTransfer | 0.19 | 0.00 | 01-JAN-00:10 | 11869.69 | 29-JUL-16:00 |
CoolingCoils:EnergyTransfer | 185.05 | 0.00 | 01-JAN-00:10 | 179527.73 | 30-JUN-12:30 |
EnergyTransfer:Plant | 64.03 | 0.00 | 01-JAN-00:10 | 7551.91 | 25-JAN-12:30 |
WaterSystems:EnergyTransfer | 64.03 | 0.00 | 01-JAN-00:10 | 7551.91 | 25-JAN-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 64.03 | 0.00 | 01-JAN-00:10 | 7551.91 | 25-JAN-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 1.687 | -174.589 | 0.000 | 0.000 | 34.549 | 48.333 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -146.146 |
CORE_MID | 0.000 | 0.000 | 11.957 | -106.134 | 0.000 | 0.000 | 35.971 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -105.551 |
CORE_TOP | 0.000 | 0.000 | 40.608 | -88.638 | 0.000 | 0.000 | 36.508 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -152.235 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 49.027 | -18.891 | 0.000 | 0.000 | 7.800 | 6.851 | 24.333 | 13.644 | 0.000 | 0.001 | 0.001 | 0.000 | -43.825 | 0.000 | -2.109 | -36.832 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 30.143 | -22.700 | 0.000 | 0.000 | 4.874 | 4.266 | 15.404 | 30.857 | 0.000 | 0.001 | 0.000 | 0.000 | -27.925 | 0.000 | -1.423 | -33.497 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 40.495 | -38.403 | 0.000 | 0.000 | 7.677 | 6.590 | 24.332 | 60.642 | 0.000 | 0.001 | 0.000 | 0.000 | -40.074 | 0.000 | -2.167 | -59.093 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 31.912 | -18.141 | 0.000 | 0.000 | 4.945 | 4.254 | 15.403 | 21.552 | 0.000 | 0.001 | 0.000 | 0.000 | -28.682 | 0.000 | -1.429 | -29.815 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 34.976 | -15.930 | 0.000 | 0.000 | 7.802 | 6.822 | 24.333 | 13.895 | 0.000 | 0.001 | 0.000 | 0.000 | -44.400 | 0.000 | -1.138 | -26.360 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 21.827 | -19.724 | 0.000 | 0.000 | 4.846 | 4.254 | 15.404 | 30.938 | 0.000 | 0.000 | 0.000 | 0.000 | -28.485 | 0.000 | -0.779 | -28.281 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 91.376 | -21.604 | 0.000 | 0.000 | 8.180 | 6.569 | 24.332 | 61.354 | 0.000 | 0.127 | 0.000 | 0.000 | -39.765 | 0.000 | -103.202 | -27.368 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 23.360 | -14.920 | 0.000 | 0.000 | 4.909 | 4.241 | 15.403 | 21.673 | 0.000 | 0.000 | 0.000 | 0.000 | -29.198 | 0.000 | -0.777 | -24.693 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 28.608 | -20.133 | 0.000 | 0.000 | 7.712 | 6.851 | 24.333 | 13.375 | 0.000 | 0.001 | 0.001 | 0.000 | -45.187 | 0.000 | -1.821 | -13.740 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 18.079 | -24.132 | 0.000 | 0.000 | 3.583 | 4.266 | 15.404 | 30.676 | 0.000 | 0.001 | 0.000 | 0.000 | -28.735 | 0.000 | -1.224 | -17.918 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 22.722 | -41.000 | 0.000 | 0.000 | 7.598 | 6.590 | 24.332 | 60.352 | 0.000 | 0.001 | 0.000 | 0.000 | -41.363 | 0.000 | -1.868 | -37.364 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 18.673 | -19.299 | 0.000 | 0.000 | 4.895 | 4.254 | 15.403 | 21.399 | 0.000 | 0.001 | 0.000 | 0.000 | -29.555 | 0.000 | -1.231 | -14.539 |
TOPFLOOR_PLENUM | 69.642 | -14.282 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -3.191 | -52.170 |
MIDFLOOR_PLENUM | 26.152 | -10.176 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -3.066 | -12.910 |
FIRSTFLOOR_PLENUM | 18.328 | -15.322 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -2.431 | -0.575 |
Total Facility | 114.121 | -39.780 | 465.448 | -644.239 | 0.000 | 0.000 | 181.848 | 210.807 | 705.434 | 380.359 | 0.000 | 0.138 | 0.005 | 0.000 | -427.193 | 0.000 | -127.857 | -819.088 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 14-AUG-04:03 | 0.00 | 0.00 | 0.00 | -42109.92 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 37235.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JUL-04:03 | 0.00 | 0.00 | 0.00 | -31029.83 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 28118.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-06:01 | 0.00 | 0.00 | 0.00 | -25716.65 | 0.00 | 0.00 | 723.79 | 1406.75 | 3025.92 | 0.00 | 0.00 | 0.00 | 20560.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 11-JUL-06:02 | 0.00 | 0.00 | 0.00 | -9536.15 | 0.00 | 0.00 | 144.48 | 141.46 | 637.89 | 4423.19 | 0.00 | 0.00 | 4200.45 | 0.00 | -0.00 | 0.00 | -11.32 | 0.00 |
PERIMETER_TOP_ZN_2 | 14-MAY-09:12 | 0.00 | 0.00 | 0.00 | -14245.78 | 0.00 | 0.00 | 14.42 | 14.92 | 302.86 | 10871.77 | 0.00 | 0.00 | 3115.02 | 0.00 | -0.00 | 0.00 | -73.21 | 0.00 |
PERIMETER_TOP_ZN_1 | 14-MAY-12:32 | 0.00 | 0.00 | 0.00 | -22235.24 | 0.00 | 0.00 | 23.05 | 23.57 | 478.41 | 15253.06 | 0.00 | 0.00 | 6544.88 | 0.00 | -0.00 | 0.00 | -87.73 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-18:32 | 0.00 | 0.00 | 0.00 | -14115.17 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 8928.92 | 0.00 | 0.00 | 5026.11 | 0.00 | -0.00 | 0.00 | -99.20 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUL-06:02 | 0.00 | 0.00 | 0.00 | -7231.68 | 0.00 | 0.00 | 144.48 | 141.46 | 637.89 | 4461.90 | 0.00 | 0.00 | 1852.03 | 0.00 | -0.00 | 0.00 | -6.07 | 0.00 |
PERIMETER_BOT_ZN_2 | 14-MAY-09:12 | 0.00 | 0.00 | 0.00 | -10976.84 | 0.00 | 0.00 | 16.70 | 14.92 | 302.86 | 10972.23 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -36.17 | -293.70 |
PERIMETER_BOT_ZN_1 | 27-AUG-13:52 | 0.00 | 0.00 | 0.00 | -17811.08 | 0.00 | 0.00 | 24.90 | 23.57 | 478.41 | 14589.88 | 0.00 | 0.00 | 2720.41 | 0.00 | -0.00 | 0.00 | -26.10 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-AUG-17:52 | 0.00 | 0.00 | 0.00 | -11344.29 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 8202.66 | 0.00 | 0.00 | 2911.30 | 0.00 | -0.00 | 0.00 | -29.02 | 0.00 |
PERIMETER_MID_ZN_3 | 07-JUN-04:02 | 0.00 | 0.00 | 0.00 | -9039.97 | 0.00 | 0.00 | 0.00 | 47.15 | 514.80 | 8204.24 | 0.00 | 0.00 | 346.21 | 0.00 | -0.00 | 0.00 | -72.43 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-10:02 | 0.00 | 0.00 | 0.00 | -13272.59 | 0.00 | 0.00 | 13.75 | 14.92 | 302.86 | 9327.00 | 0.00 | 0.00 | 3626.46 | 0.00 | -0.00 | 0.00 | -12.41 | 0.00 |
PERIMETER_MID_ZN_1 | 27-AUG-13:12 | 0.00 | 0.00 | 0.00 | -21505.92 | 0.00 | 0.00 | 22.50 | 23.57 | 478.41 | 16074.42 | 0.00 | 0.00 | 4942.39 | 0.00 | -0.00 | 0.00 | -35.38 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-16:42 | 0.00 | 0.00 | 0.00 | -13649.46 | 0.00 | 0.00 | 14.73 | 14.92 | 302.86 | 9753.23 | 0.00 | 0.00 | 3649.73 | 0.00 | -0.00 | 0.00 | -86.01 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:30 | 0.00 | -7712.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 | 7710.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 12-JUL-16:00 | 0.00 | -4070.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 | 4069.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 12-JAN-17:10 | 0.00 | -5638.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5638.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-06:01 | 0.00 | -6052.19 | 0.00 | -158356.19 | 0.00 | 0.00 | 3616.78 | 5614.68 | 21098.80 | 26411.50 | 0.00 | 0.00 | 119114.46 | 0.00 | 0.00 | 0.00 | -11447.85 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 24316.41 | 0.00 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29190.97 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 27246.82 | 0.00 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -30157.79 |
CORE_TOP | 01-JAN-22:42 | 0.00 | 0.00 | 29571.41 | 0.00 | 0.00 | 0.00 | 0.00 | 234.43 | 1831.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -31637.38 |
PERIMETER_TOP_ZN_3 | 27-FEB-04:52 | 0.00 | 0.00 | 10816.18 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3719.84 | 0.00 | 0.00 | -7660.57 |
PERIMETER_TOP_ZN_2 | 27-FEB-04:52 | 0.00 | 0.00 | 12223.51 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2477.73 | 0.00 | 0.00 | -10102.96 |
PERIMETER_TOP_ZN_1 | 27-FEB-04:52 | 0.00 | 0.00 | 19243.27 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3734.14 | 0.00 | 0.00 | -16073.35 |
PERIMETER_TOP_ZN_4 | 27-FEB-04:52 | 0.00 | 0.00 | 12773.23 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2478.90 | 0.00 | 0.00 | -10651.52 |
PERIMETER_BOT_ZN_3 | 27-FEB-04:52 | 0.00 | 0.00 | 8125.33 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3788.33 | 0.00 | 0.00 | -4901.22 |
PERIMETER_BOT_ZN_2 | 27-FEB-04:52 | 0.00 | 0.00 | 9685.08 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2524.78 | 0.00 | 0.00 | -7517.49 |
PERIMETER_BOT_ZN_1 | 12-JAN-07:10 | 0.00 | 0.00 | 26213.62 | 0.00 | 0.00 | 0.00 | 228.69 | 296.56 | 637.88 | 0.00 | 0.00 | 0.00 | 30260.16 | 0.00 | -3990.58 | 0.00 | -53646.33 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-FEB-04:52 | 0.00 | 0.00 | 10205.39 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2525.91 | 0.00 | 0.00 | -8036.66 |
PERIMETER_MID_ZN_3 | 27-FEB-04:52 | 0.00 | 0.00 | 8592.10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3808.32 | 0.00 | 0.00 | -5348.00 |
PERIMETER_MID_ZN_2 | 27-FEB-04:52 | 0.00 | 0.00 | 11307.93 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2536.50 | 0.00 | 0.00 | -9128.61 |
PERIMETER_MID_ZN_1 | 27-FEB-04:52 | 0.00 | 0.00 | 16957.77 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3827.49 | 0.00 | 0.00 | -13694.50 |
PERIMETER_MID_ZN_4 | 27-FEB-04:52 | 0.00 | 0.00 | 11252.87 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2537.87 | 0.00 | 0.00 | -9072.17 |
TOPFLOOR_PLENUM | 12-JAN-06:05 | 19129.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19129.47 |
MIDFLOOR_PLENUM | 02-JAN-07:04 | 11624.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -69.39 | -11554.70 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 9687.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -53.54 | -9634.13 |
Total Facility | 02-JAN-05:01 | 18530.70 | 0.00 | 216467.78 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.34 | 14333.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23353.50 | 0.00 | -1165.78 | -227188.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.6394 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8509 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.3176 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.3204 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.5402 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.7682 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.8197 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4116 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.6588 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4523 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7701 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.5316 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7955 | 2.7955 | 0.7743 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0398 | 2.0398 | 0.7507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0066 | 2.0066 | 0.7725 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6804 | 0.6804 | 0.1885 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7846 | 0.7846 | 0.1569 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2460 | 1.2460 | 0.2492 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8225 | 0.8225 | 0.1645 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5269 | 0.5269 | 0.1739 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6396 | 0.6396 | 0.1279 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0014 | 1.0014 | 0.2003 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6760 | 0.6760 | 0.1352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5616 | 0.5616 | 0.1584 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7771 | 0.7771 | 0.1554 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1682 | 1.1682 | 0.2336 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7707 | 0.7707 | 0.1541 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.6394 | 4.8509 | 5.6394 | 1.4116 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.3176 | 4.3204 | 5.3176 | 1.4523 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.5402 | 4.7682 | 5.5402 | 1.5316 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3977 | 1.3977 | 0.7743 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0199 | 1.0199 | 0.7507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0033 | 1.0033 | 0.7725 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3402 | 0.3402 | 0.1885 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3923 | 0.3923 | 0.1569 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6230 | 0.6230 | 0.2492 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4113 | 0.4113 | 0.1645 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2635 | 0.2635 | 0.1739 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3198 | 0.3198 | 0.1279 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5007 | 0.5007 | 0.2003 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3380 | 0.3380 | 0.1352 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2808 | 0.2808 | 0.1584 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3886 | 0.3886 | 0.1554 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5841 | 0.5841 | 0.2336 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3854 | 0.3854 | 0.1541 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.8197 | 1.4116 | 1.4116 | 1.4116 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.6588 | 1.4523 | 1.4523 | 1.4523 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7701 | 1.5316 | 1.5316 | 1.5316 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 1209.83 |
Number of hours cooling loads not met | 41.00 |
Number of hours not met | 1250.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 639.08 | 216624.51 | 223.55 | 199286.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 45.13 | 43567.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 210.81 | 21377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 54.95 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.67 | 835.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 88.28 | 24674.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 25.33 | 2722.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 126.37 | 13393.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1780.69 |
Natural Gas | 0.00 | 349.92 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 2130.62 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 42.31 |
Space Heating | 128.27 |
Space Cooling | 9.06 |
Fans (All) | 17.72 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 357.41 |
Subtotal | 357.41 |
Natural Gas [MJ/m2] | |
Space Heating | 44.87 |
Service Water Heating | 25.36 |
Miscellaneous (All) | 70.23 |
Subtotal | 70.23 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.89 |
Space Heating | 40.49 |
Space Cooling | 2.12 |
Fans (All) | 4.14 |
Service Water Heating | 5.93 |
Receptacle Equipment | 33.11 |
Miscellaneous | 4.32 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8747.50 | 12.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8751.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8752.17 | 7.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8746.83 | 13.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8746.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 14.00 | 0.00 | 0.00 | 0.00 |
Average | 8754.77 | 5.23 | 0.00 | 0.00 | 0.00 |
Sum | 157585.83 | 94.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8716.67 | 43.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8750.50 | 9.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8754.33 | 5.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8744.83 | 15.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8716.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 43.33 | 0.00 | 0.00 | 0.00 |
Average | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
Sum | 157542.00 | 138.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128280.33 | 23.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128301.67 | 2.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 23.67 | 0.00 | 0.00 | 0.00 |
Average | 34141.89 | 1.44 | 0.00 | 0.00 | 0.00 |
Sum | 614554.00 | 26.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:22
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.750445E+10 | 6854.64 | 27-JAN-17:00 | -12.2 | -12.5 | 0.156908E+10 | 2321.88 | 27-JAN-14:09 | -12.2 | -12.5 |
February | 0.815882E+10 | 7408.94 | 10-FEB-17:00 | -0.6 | -2.2 | 0.149475E+10 | 2474.87 | 10-FEB-14:09 | -0.6 | -2.2 |
March | 0.997444E+10 | 9486.63 | 23-MAR-08:00 | -3.3 | -5.1 | 0.194118E+10 | 2606.57 | 24-MAR-13:30 | -6.4 | -7.6 |
April | 0.130073E+11 | 23671.09 | 28-APR-05:02 | -1.5 | -2.2 | 0.187446E+10 | 2608.82 | 24-APR-09:30 | -1.5 | -2.2 |
May | 0.209582E+11 | 40179.51 | 16-MAY-05:02 | 3.30 | 1.49 | 0.207367E+10 | 2606.66 | 19-MAY-13:39 | 13.87 | 8.18 |
June | 0.244548E+11 | 41523.75 | 12-JUN-04:02 | 7.38 | 5.98 | 0.207063E+10 | 2606.70 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.238997E+11 | 41747.86 | 24-JUL-04:03 | 12.80 | 12.43 | 0.192523E+10 | 2607.02 | 19-JUL-09:09 | 12.80 | 12.43 |
August | 0.242308E+11 | 42117.46 | 14-AUG-04:03 | 11.60 | 10.40 | 0.215983E+10 | 2606.65 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.161149E+11 | 39709.81 | 05-SEP-05:02 | 5.00 | 4.09 | 0.190762E+10 | 2608.55 | 29-SEP-09:20 | -3.9 | -4.4 |
October | 0.104620E+11 | 15766.15 | 04-OCT-07:20 | 7.80 | 2.92 | 0.189332E+10 | 2607.81 | 18-OCT-13:50 | -1.7 | -2.5 |
November | 0.797761E+10 | 7331.94 | 03-NOV-16:00 | -11.1 | -11.5 | 0.162993E+10 | 2445.58 | 03-NOV-13:09 | -11.1 | -11.5 |
December | 0.784588E+10 | 6611.18 | 21-DEC-16:20 | -16.3 | -16.8 | 0.150584E+10 | 2256.57 | 22-DEC-14:09 | -23.7 | -24.0 |
Annual Sum or Average | 0.174589E+12 | 0.220455E+11 | ||||||||
Minimum of Months | 0.750445E+10 | 6611.18 | -16.3 | -16.8 | 0.149475E+10 | 2256.57 | -23.7 | -24.0 | ||
Maximum of Months | 0.244548E+11 | 42117.46 | 12.80 | 12.43 | 0.215983E+10 | 2608.82 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 8217332.28 | 825.91 | 22-MAR-17:09 | 5.13 | 1.52 | 0.00 | 0.00 | 01-MAR-00:10 | 5.13 | 1.52 |
April | 0.649790E+09 | 3314.30 | 21-APR-15:40 | 14.23 | 5.51 | 0.00 | 0.00 | 01-APR-00:10 | 14.23 | 5.51 |
May | 0.234704E+10 | 6526.30 | 31-MAY-14:40 | 20.73 | 10.55 | 0.00 | 0.00 | 01-MAY-00:10 | 20.73 | 10.55 |
June | 0.420783E+10 | 7609.47 | 29-JUN-14:50 | 26.02 | 16.10 | 0.00 | 0.00 | 01-JUN-00:10 | 26.02 | 16.10 |
July | 0.414743E+10 | 7711.66 | 21-JUL-14:30 | 26.95 | 14.56 | 0.00 | 0.00 | 01-JUL-00:10 | 26.95 | 14.56 |
August | 0.257434E+10 | 6502.17 | 10-AUG-15:20 | 22.40 | 12.08 | 0.00 | 0.00 | 01-AUG-00:10 | 22.40 | 12.08 |
September | 0.342766E+09 | 2255.37 | 07-SEP-16:10 | 16.83 | 8.75 | 0.00 | 0.00 | 01-SEP-00:10 | 16.83 | 8.75 |
October | 4918917.78 | 732.25 | 03-OCT-16:10 | 11.60 | 6.16 | 0.00 | 0.00 | 01-OCT-00:10 | 11.60 | 6.16 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:05 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.142823E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.420783E+10 | 7711.66 | 26.95 | 16.10 | 0.00 | 0.00 | 26.95 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7607833.43 | 2572.14 | 11-JAN-05:01 | -27.4 | -27.5 | 0.00 | 0.00 | 01-JAN-00:10 | -27.4 | -27.5 |
February | 7044857.87 | 2563.13 | 25-FEB-05:01 | -24.4 | -24.9 | 0.00 | 0.00 | 01-FEB-00:10 | -24.4 | -24.9 |
March | 13478557.93 | 2595.66 | 02-MAR-05:01 | -26.7 | -27.1 | 0.00 | 0.00 | 01-MAR-00:10 | -26.7 | -27.1 |
April | 0.255121E+09 | 2304.30 | 14-APR-06:01 | -5.8 | -7.0 | 0.00 | 0.00 | 01-APR-00:10 | -5.8 | -7.0 |
May | 0.148546E+10 | 2916.91 | 31-MAY-16:00 | 22.20 | 10.79 | 0.00 | 0.00 | 01-MAY-00:10 | 22.20 | 10.79 |
June | 0.307457E+10 | 3797.00 | 30-JUN-14:30 | 27.75 | 17.00 | 0.00 | 0.00 | 01-JUN-00:10 | 27.75 | 17.00 |
July | 0.296822E+10 | 4070.24 | 12-JUL-16:00 | 25.00 | 13.76 | 0.00 | 0.00 | 01-JUL-00:10 | 25.00 | 13.76 |
August | 0.201835E+10 | 3427.97 | 11-AUG-16:00 | 25.60 | 14.77 | 0.00 | 0.00 | 01-AUG-00:10 | 25.60 | 14.77 |
September | 0.298299E+09 | 1178.61 | 22-SEP-06:02 | 2.70 | 1.41 | 0.00 | 0.00 | 01-SEP-00:10 | 2.70 | 1.41 |
October | 35805113.92 | 1634.94 | 05-OCT-06:01 | -0.6 | -1.4 | 0.00 | 0.00 | 01-OCT-00:10 | -0.6 | -1.4 |
November | 4691187.20 | 2185.33 | 29-NOV-05:11 | -28.9 | -29.1 | 0.00 | 0.00 | 01-NOV-00:10 | -28.9 | -29.1 |
December | 7418780.73 | 2639.90 | 28-DEC-05:01 | -28.2 | -28.4 | 0.00 | 0.00 | 01-DEC-00:10 | -28.2 | -28.4 |
Annual Sum or Average | 0.101761E+11 | 0.00 | ||||||||
Minimum of Months | 4691187.20 | 1178.61 | -28.9 | -29.1 | 0.00 | 0.00 | -28.9 | -29.1 | ||
Maximum of Months | 0.307457E+10 | 4070.24 | 27.75 | 17.00 | 0.00 | 0.00 | 27.75 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310651E+09 | 5638.22 | 12-JAN-17:10 | -35.8 | -35.9 | 0.00 | 0.00 | 01-JAN-00:10 | -35.8 | -35.9 |
February | 0.244689E+09 | 4318.77 | 17-FEB-07:09 | -23.3 | -23.5 | 0.00 | 0.00 | 01-FEB-00:10 | -23.3 | -23.5 |
March | 0.361184E+09 | 5620.74 | 31-MAR-06:09 | -25.6 | -26.1 | 0.00 | 0.00 | 01-MAR-00:10 | -25.6 | -26.1 |
April | 0.696509E+09 | 4136.59 | 03-APR-06:09 | -21.5 | -22.1 | 0.00 | 0.00 | 01-APR-00:10 | -21.5 | -22.1 |
May | 0.217707E+10 | 3389.71 | 16-MAY-06:08 | 3.30 | 1.56 | 0.00 | 0.00 | 01-MAY-00:10 | 3.30 | 1.56 |
June | 0.343600E+10 | 3870.06 | 12-JUN-12:10 | 19.08 | 10.88 | 0.00 | 0.00 | 01-JUN-00:10 | 19.08 | 10.88 |
July | 0.348364E+10 | 4718.48 | 24-JUL-06:07 | 14.18 | 13.06 | 0.00 | 0.00 | 01-JUL-00:10 | 14.18 | 13.06 |
August | 0.286546E+10 | 3990.99 | 28-AUG-06:07 | 5.87 | 5.03 | 0.00 | 0.00 | 01-AUG-00:10 | 5.87 | 5.03 |
September | 0.800934E+09 | 3033.41 | 15-SEP-06:06 | -0.5 | -0.7 | 0.00 | 0.00 | 01-SEP-00:10 | -0.5 | -0.7 |
October | 0.253174E+09 | 3720.57 | 27-OCT-06:10 | -18.4 | -18.8 | 0.00 | 0.00 | 01-OCT-00:10 | -18.4 | -18.8 |
November | 0.333266E+09 | 4440.89 | 09-NOV-07:10 | -26.7 | -26.9 | 0.00 | 0.00 | 01-NOV-00:10 | -26.7 | -26.9 |
December | 0.359511E+09 | 4598.59 | 15-DEC-07:10 | -33.4 | -33.5 | 0.00 | 0.00 | 01-DEC-00:10 | -33.4 | -33.5 |
Annual Sum or Average | 0.153221E+11 | 0.00 | ||||||||
Minimum of Months | 0.244689E+09 | 3033.41 | -35.8 | -35.9 | 0.00 | 0.00 | -35.8 | -35.9 | ||
Maximum of Months | 0.348364E+10 | 5638.22 | 19.08 | 13.06 | 0.00 | 0.00 | 19.08 | 13.06 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251479E+10 | 5248.83 | 20-JAN-17:00 | -11.1 | -11.2 | 0.145488E+10 | 1989.49 | 20-JAN-14:00 | -11.1 | -11.2 |
February | 0.352960E+10 | 5871.51 | 09-FEB-16:30 | -0.8 | -1.5 | 0.134338E+10 | 2161.36 | 09-FEB-14:00 | -0.8 | -1.5 |
March | 0.601108E+10 | 6482.68 | 22-MAR-16:00 | 5.60 | 2.61 | 0.167395E+10 | 2283.14 | 23-MAR-13:00 | -1.7 | -4.1 |
April | 0.880730E+10 | 10646.20 | 28-APR-16:00 | 12.20 | 5.13 | 0.171328E+10 | 2606.59 | 28-APR-09:09 | 12.20 | 5.13 |
May | 0.142728E+11 | 27396.74 | 15-MAY-05:02 | 6.88 | 1.81 | 0.205627E+10 | 2606.65 | 16-MAY-09:09 | 5.97 | 4.63 |
June | 0.172804E+11 | 29333.19 | 15-JUN-05:03 | 10.00 | 8.53 | 0.206516E+10 | 2606.64 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.167290E+11 | 31026.97 | 24-JUL-04:03 | 12.80 | 12.43 | 0.191948E+10 | 2606.89 | 19-JUL-09:09 | 12.80 | 12.43 |
August | 0.157120E+11 | 30447.13 | 01-AUG-05:02 | 10.00 | 9.66 | 0.214947E+10 | 2606.64 | 30-AUG-09:09 | 4.18 | 0.71 |
September | 0.960607E+10 | 11149.47 | 01-SEP-16:00 | 15.60 | 10.82 | 0.180002E+10 | 2606.65 | 01-SEP-09:09 | 15.60 | 10.82 |
October | 0.629239E+10 | 6988.54 | 05-OCT-16:00 | 11.10 | 5.87 | 0.159454E+10 | 2433.00 | 04-OCT-13:00 | 11.10 | 5.87 |
November | 0.309008E+10 | 5417.57 | 02-NOV-16:00 | -8.9 | -9.4 | 0.145067E+10 | 2034.11 | 02-NOV-13:00 | -8.9 | -9.4 |
December | 0.228876E+10 | 5023.77 | 21-DEC-17:00 | -16.7 | -17.3 | 0.140232E+10 | 1943.84 | 21-DEC-14:00 | -16.7 | -17.3 |
Annual Sum or Average | 0.106134E+12 | 0.206234E+11 | ||||||||
Minimum of Months | 0.228876E+10 | 5023.77 | -16.7 | -17.3 | 0.134338E+10 | 1943.84 | -16.7 | -17.3 | ||
Maximum of Months | 0.172804E+11 | 31026.97 | 15.60 | 12.43 | 0.214947E+10 | 2606.89 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.859643E+09 | 4903.43 | 06-JAN-21:03 | -5.7 | -6.4 | 0.144656E+10 | 1929.07 | 30-JAN-10:09 | -25.5 | -25.9 |
February | 0.166513E+10 | 5624.97 | 09-FEB-15:50 | 0.50 | -0.6 | 0.131708E+10 | 2060.63 | 09-FEB-14:00 | 0.50 | -0.6 |
March | 0.387552E+10 | 6483.52 | 22-MAR-16:00 | 5.60 | 2.61 | 0.160536E+10 | 2196.83 | 22-MAR-13:00 | 5.60 | 2.61 |
April | 0.747505E+10 | 10078.82 | 28-APR-16:00 | 12.20 | 5.13 | 0.160999E+10 | 2606.50 | 21-APR-13:50 | 12.20 | 5.13 |
May | 0.132601E+11 | 15297.43 | 31-MAY-16:00 | 22.20 | 10.79 | 0.202343E+10 | 2606.64 | 19-MAY-13:00 | 22.20 | 10.79 |
June | 0.169269E+11 | 20457.78 | 05-JUN-05:02 | 10.68 | 8.83 | 0.205881E+10 | 2606.62 | 27-JUN-09:09 | 13.90 | 13.18 |
July | 0.162355E+11 | 25717.38 | 24-JUL-06:01 | 14.18 | 13.06 | 0.191303E+10 | 2606.83 | 19-JUL-09:09 | 14.18 | 13.06 |
August | 0.143750E+11 | 18133.69 | 03-AUG-05:03 | 14.90 | 13.04 | 0.212394E+10 | 2606.63 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.808556E+10 | 9811.20 | 01-SEP-16:00 | 15.60 | 10.82 | 0.166057E+10 | 2606.55 | 01-SEP-13:30 | 15.60 | 10.82 |
October | 0.396693E+10 | 6664.19 | 03-OCT-16:00 | 11.70 | 6.37 | 0.149902E+10 | 2297.20 | 04-OCT-13:00 | 11.10 | 4.80 |
November | 0.108100E+10 | 4844.24 | 02-NOV-20:03 | -9.4 | -9.7 | 0.143361E+10 | 1929.11 | 27-NOV-10:09 | -27.2 | -27.4 |
December | 0.831791E+09 | 4801.24 | 19-DEC-21:03 | -6.5 | -7.3 | 0.139519E+10 | 1928.99 | 04-DEC-10:09 | -6.5 | -7.3 |
Annual Sum or Average | 0.886382E+11 | 0.200866E+11 | ||||||||
Minimum of Months | 0.831791E+09 | 4801.24 | -9.4 | -9.7 | 0.131708E+10 | 1928.99 | -27.2 | -27.4 | ||
Maximum of Months | 0.169269E+11 | 25717.38 | 22.20 | 13.06 | 0.212394E+10 | 2606.83 | 22.20 | 13.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10818020.52 | 1126.75 | 06-JAN-21:03 | -5.7 | -6.4 | 0.301474E+09 | 406.73 | 03-JAN-14:00 | -5.7 | -6.4 |
February | 12688780.38 | 1137.64 | 10-FEB-21:03 | -6.1 | -6.6 | 0.274186E+09 | 406.70 | 27-FEB-14:30 | -28.6 | -28.8 |
March | 78140306.69 | 1337.13 | 22-MAR-15:40 | 5.60 | 2.48 | 0.330830E+09 | 418.78 | 22-MAR-13:00 | 5.60 | 2.48 |
April | 0.116627E+10 | 1884.70 | 28-APR-16:00 | 12.20 | 5.13 | 0.314826E+09 | 531.13 | 28-APR-13:00 | 12.20 | 5.13 |
May | 0.309440E+10 | 7801.50 | 31-MAY-05:02 | 12.07 | 7.63 | 0.417579E+09 | 549.50 | 19-MAY-13:00 | 12.07 | 7.63 |
June | 0.497460E+10 | 9527.75 | 13-JUN-06:02 | 13.27 | 9.79 | 0.434632E+09 | 549.50 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.464015E+10 | 9536.65 | 11-JUL-06:02 | 16.38 | 12.49 | 0.403135E+09 | 549.54 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.336664E+10 | 4495.02 | 02-AUG-15:30 | 22.75 | 14.69 | 0.436691E+09 | 549.49 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.133854E+10 | 1896.94 | 01-SEP-16:00 | 15.60 | 10.82 | 0.320683E+09 | 537.50 | 01-SEP-13:00 | 15.60 | 10.82 |
October | 0.186121E+09 | 1382.24 | 04-OCT-15:30 | 10.55 | 4.70 | 0.306181E+09 | 432.88 | 04-OCT-13:00 | 10.55 | 4.70 |
November | 10154652.26 | 1112.56 | 02-NOV-20:03 | -9.4 | -9.7 | 0.299245E+09 | 406.71 | 17-NOV-10:09 | -25.0 | -25.3 |
December | 12455503.09 | 1106.38 | 23-DEC-16:03 | -3.1 | -4.1 | 0.290863E+09 | 406.78 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.188910E+11 | 0.413033E+10 | ||||||||
Minimum of Months | 10154652.26 | 1106.38 | -9.4 | -9.7 | 0.274186E+09 | 406.70 | -28.6 | -28.8 | ||
Maximum of Months | 0.497460E+10 | 9536.65 | 22.75 | 14.69 | 0.436691E+09 | 549.54 | 17.80 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11569792.42 | 928.75 | 06-JAN-21:03 | -5.7 | -6.4 | 0.192507E+09 | 257.50 | 03-JAN-14:00 | -5.7 | -6.4 |
February | 18468568.63 | 939.51 | 10-FEB-21:03 | -6.1 | -6.6 | 0.174876E+09 | 257.49 | 27-FEB-14:30 | -28.6 | -28.8 |
March | 0.410795E+09 | 1528.26 | 22-MAR-10:40 | 2.43 | 0.50 | 0.215284E+09 | 333.76 | 22-MAR-09:00 | 2.43 | 0.50 |
April | 0.157503E+10 | 4971.92 | 22-APR-09:30 | 9.15 | 3.96 | 0.221106E+09 | 347.87 | 13-APR-09:00 | 9.15 | 3.96 |
May | 0.443262E+10 | 14246.12 | 14-MAY-09:12 | 15.37 | 8.02 | 0.273192E+09 | 348.26 | 31-MAY-09:00 | 17.20 | 9.87 |
June | 0.531536E+10 | 12068.22 | 04-JUN-09:43 | 17.43 | 11.50 | 0.275288E+09 | 348.35 | 08-JUN-09:30 | 16.15 | 10.27 |
July | 0.522117E+10 | 13456.64 | 23-JUL-09:42 | 20.63 | 14.69 | 0.255602E+09 | 348.59 | 07-JUL-09:50 | 20.63 | 14.69 |
August | 0.395238E+10 | 10589.65 | 11-AUG-06:02 | 10.97 | 7.10 | 0.283954E+09 | 348.24 | 10-AUG-09:00 | 10.97 | 7.10 |
September | 0.144314E+10 | 3626.98 | 09-SEP-09:45 | 6.32 | 4.70 | 0.214503E+09 | 347.88 | 08-SEP-13:09 | 6.32 | 4.70 |
October | 0.295472E+09 | 1514.63 | 03-OCT-10:05 | 4.27 | 2.93 | 0.196327E+09 | 333.58 | 03-OCT-09:00 | 4.27 | 2.93 |
November | 11120774.89 | 916.99 | 02-NOV-20:03 | -9.4 | -9.7 | 0.190704E+09 | 257.49 | 30-NOV-14:30 | -25.6 | -25.8 |
December | 12639266.37 | 912.94 | 23-DEC-16:03 | -3.1 | -4.1 | 0.185580E+09 | 257.54 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.226998E+11 | 0.267893E+10 | ||||||||
Minimum of Months | 11120774.89 | 912.94 | -9.4 | -9.7 | 0.174876E+09 | 257.49 | -28.6 | -28.8 | ||
Maximum of Months | 0.531536E+10 | 14246.12 | 20.63 | 14.69 | 0.283954E+09 | 348.59 | 20.63 | 14.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35096420.20 | 1595.78 | 25-JAN-13:22 | -19.8 | -20.0 | 0.304138E+09 | 406.72 | 03-JAN-14:00 | -19.8 | -20.0 |
February | 0.367779E+09 | 3016.00 | 15-FEB-14:00 | -8.3 | -9.2 | 0.282905E+09 | 549.48 | 15-FEB-14:50 | -7.4 | -8.7 |
March | 0.145871E+10 | 6704.97 | 31-MAR-14:00 | -11.1 | -13.1 | 0.364902E+09 | 550.22 | 15-MAR-13:20 | -11.1 | -13.1 |
April | 0.399783E+10 | 12070.90 | 20-APR-14:10 | 14.32 | 6.25 | 0.354994E+09 | 549.49 | 26-APR-13:00 | 10.60 | 4.23 |
May | 0.638648E+10 | 22233.10 | 14-MAY-12:32 | 18.53 | 9.40 | 0.417753E+09 | 549.62 | 12-MAY-13:20 | 18.53 | 9.40 |
June | 0.756335E+10 | 16896.36 | 18-JUN-13:13 | 15.20 | 11.37 | 0.430270E+09 | 549.50 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.749212E+10 | 22017.32 | 23-JUL-13:42 | 25.00 | 15.26 | 0.399302E+09 | 549.92 | 12-JUL-13:00 | 25.00 | 15.26 |
August | 0.692057E+10 | 20281.15 | 27-AUG-13:22 | 18.60 | 13.91 | 0.438800E+09 | 549.80 | 25-AUG-13:00 | 18.60 | 13.91 |
September | 0.311104E+10 | 9418.12 | 07-SEP-14:30 | 15.85 | 8.58 | 0.343747E+09 | 550.34 | 28-SEP-13:50 | 5.40 | 1.60 |
October | 0.959372E+09 | 7863.62 | 03-OCT-13:30 | 10.85 | 6.24 | 0.321357E+09 | 549.48 | 13-OCT-13:00 | 1.10 | -2.4 |
November | 90664002.98 | 2202.59 | 08-NOV-14:00 | -13.3 | -14.1 | 0.302271E+09 | 497.92 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 20846577.39 | 1453.87 | 23-DEC-16:03 | -3.1 | -4.1 | 0.293171E+09 | 406.77 | 22-DEC-10:50 | -3.1 | -4.1 |
Annual Sum or Average | 0.384039E+11 | 0.425361E+10 | ||||||||
Minimum of Months | 20846577.39 | 1453.87 | -19.8 | -20.0 | 0.282905E+09 | 406.72 | -19.8 | -20.0 | ||
Maximum of Months | 0.756335E+10 | 22233.10 | 25.00 | 15.26 | 0.438800E+09 | 550.34 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12838503.65 | 972.59 | 06-JAN-21:03 | -5.7 | -6.4 | 0.192493E+09 | 257.48 | 03-JAN-14:00 | -5.7 | -6.4 |
February | 18281281.94 | 982.68 | 10-FEB-21:03 | -6.1 | -6.6 | 0.174850E+09 | 257.48 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.215026E+09 | 1405.88 | 29-MAR-16:00 | -6.1 | -9.1 | 0.211068E+09 | 294.99 | 22-MAR-15:50 | -6.1 | -9.1 |
April | 0.163853E+10 | 6179.89 | 20-APR-18:10 | 12.02 | 5.14 | 0.204789E+09 | 339.46 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.310738E+10 | 14114.89 | 14-MAY-18:32 | 16.70 | 9.14 | 0.256822E+09 | 347.85 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.441724E+10 | 12762.41 | 10-JUN-17:05 | 21.20 | 10.81 | 0.271857E+09 | 347.85 | 28-JUN-13:00 | 17.80 | 14.79 |
July | 0.399997E+10 | 11686.65 | 08-JUL-18:33 | 20.00 | 15.32 | 0.251700E+09 | 347.86 | 11-JUL-13:09 | 25.50 | 15.91 |
August | 0.325408E+10 | 11025.10 | 27-AUG-18:42 | 19.60 | 11.80 | 0.270943E+09 | 347.84 | 01-AUG-09:00 | 19.60 | 11.80 |
September | 0.125716E+10 | 3797.88 | 08-SEP-16:00 | 14.40 | 9.03 | 0.202802E+09 | 338.68 | 07-SEP-15:09 | 14.40 | 9.03 |
October | 0.194680E+09 | 1408.41 | 03-OCT-15:10 | 12.62 | 6.83 | 0.194257E+09 | 299.25 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 12160180.73 | 959.89 | 02-NOV-20:03 | -9.4 | -9.7 | 0.190695E+09 | 257.47 | 17-NOV-10:09 | -25.0 | -25.3 |
December | 13503782.05 | 955.12 | 23-DEC-16:03 | -3.1 | -4.1 | 0.185567E+09 | 257.51 | 22-DEC-10:50 | -3.1 | -4.1 |
Annual Sum or Average | 0.181409E+11 | 0.260784E+10 | ||||||||
Minimum of Months | 12160180.73 | 955.12 | -9.4 | -9.7 | 0.174850E+09 | 257.47 | -28.5 | -28.7 | ||
Maximum of Months | 0.441724E+10 | 14114.89 | 21.20 | 15.32 | 0.271857E+09 | 347.86 | 25.50 | 15.91 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14097228.09 | 1025.55 | 21-JAN-16:03 | -5.6 | -5.8 | 0.296570E+09 | 406.71 | 11-JAN-14:30 | -5.6 | -5.8 |
February | 11957709.69 | 1041.97 | 10-FEB-21:03 | -6.1 | -6.6 | 0.270140E+09 | 406.69 | 24-FEB-10:00 | -24.4 | -24.9 |
March | 31110403.47 | 1063.36 | 23-MAR-20:03 | -2.9 | -4.9 | 0.330305E+09 | 406.68 | 03-MAR-14:09 | -2.9 | -4.9 |
April | 0.857468E+09 | 1489.80 | 28-APR-16:00 | 12.20 | 5.13 | 0.304982E+09 | 481.68 | 28-APR-13:00 | 12.20 | 5.13 |
May | 0.232162E+10 | 2364.85 | 31-MAY-16:00 | 22.20 | 10.79 | 0.402756E+09 | 549.48 | 22-MAY-13:00 | 22.20 | 10.79 |
June | 0.359581E+10 | 7076.24 | 13-JUN-06:02 | 13.27 | 9.79 | 0.432902E+09 | 549.50 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.376407E+10 | 7231.91 | 11-JUL-06:02 | 16.38 | 12.49 | 0.403304E+09 | 549.54 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.311499E+10 | 3680.02 | 02-AUG-15:40 | 22.93 | 14.75 | 0.444724E+09 | 549.49 | 07-AUG-09:09 | 11.78 | 11.34 |
September | 0.172621E+10 | 1917.92 | 05-SEP-05:02 | 5.00 | 4.09 | 0.342675E+09 | 538.52 | 01-SEP-13:00 | 5.00 | 4.09 |
October | 0.451436E+09 | 1370.99 | 06-OCT-15:00 | 10.60 | 4.90 | 0.311008E+09 | 459.04 | 06-OCT-13:00 | 10.60 | 4.90 |
November | 14248452.60 | 1048.80 | 02-NOV-20:03 | -9.4 | -9.7 | 0.299717E+09 | 406.70 | 30-NOV-14:39 | -25.7 | -26.0 |
December | 27245622.19 | 1028.75 | 23-DEC-16:03 | -3.1 | -4.1 | 0.289642E+09 | 406.75 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.159303E+11 | 0.412872E+10 | ||||||||
Minimum of Months | 11957709.69 | 1025.55 | -9.4 | -9.7 | 0.270140E+09 | 406.68 | -25.7 | -26.0 | ||
Maximum of Months | 0.376407E+10 | 7231.91 | 22.93 | 14.75 | 0.444724E+09 | 549.54 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12177202.54 | 750.04 | 21-JAN-16:03 | -5.6 | -5.8 | 0.192671E+09 | 257.50 | 03-JAN-14:00 | -5.6 | -5.8 |
February | 13905637.20 | 837.51 | 09-FEB-07:03 | -0.3 | -0.7 | 0.175010E+09 | 257.49 | 27-FEB-14:30 | -28.6 | -28.8 |
March | 0.270646E+09 | 1193.93 | 31-MAR-09:40 | -16.7 | -17.8 | 0.213940E+09 | 328.00 | 31-MAR-09:50 | -16.4 | -17.6 |
April | 0.119269E+10 | 3248.96 | 22-APR-08:40 | 7.20 | 2.77 | 0.219841E+09 | 348.21 | 24-APR-09:30 | 1.15 | -3.1 |
May | 0.342662E+10 | 10977.04 | 14-MAY-09:12 | 15.37 | 8.02 | 0.274237E+09 | 347.88 | 19-MAY-09:09 | 12.15 | 6.94 |
June | 0.425712E+10 | 8643.78 | 13-JUN-06:02 | 13.27 | 9.79 | 0.275215E+09 | 348.10 | 13-JUN-09:30 | 20.25 | 11.95 |
July | 0.453643E+10 | 9210.30 | 09-JUL-06:42 | 14.53 | 12.37 | 0.256508E+09 | 348.31 | 07-JUL-09:50 | 14.53 | 12.37 |
August | 0.379643E+10 | 8543.84 | 11-AUG-06:02 | 10.97 | 7.10 | 0.286915E+09 | 348.20 | 11-AUG-09:09 | 16.97 | 10.66 |
September | 0.165883E+10 | 6726.05 | 10-SEP-09:23 | 11.95 | 6.71 | 0.233455E+09 | 347.88 | 08-SEP-13:09 | 11.95 | 6.71 |
October | 0.530948E+09 | 1713.74 | 03-OCT-09:35 | 2.97 | 2.01 | 0.202503E+09 | 347.87 | 03-OCT-09:00 | 3.90 | 2.68 |
November | 10740872.48 | 784.02 | 02-NOV-06:03 | -10.7 | -11.1 | 0.191081E+09 | 257.49 | 30-NOV-14:30 | -25.6 | -25.8 |
December | 17561523.10 | 751.53 | 23-DEC-16:03 | -3.1 | -4.1 | 0.185824E+09 | 257.52 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.197241E+11 | 0.270720E+10 | ||||||||
Minimum of Months | 10740872.48 | 750.04 | -16.7 | -17.8 | 0.175010E+09 | 257.49 | -28.6 | -28.8 | ||
Maximum of Months | 0.453643E+10 | 10977.04 | 15.37 | 12.37 | 0.286915E+09 | 348.31 | 20.25 | 12.37 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14685328.86 | 1173.29 | 21-JAN-16:03 | -5.6 | -5.8 | 0.222987E+09 | 406.61 | 19-JAN-10:09 | -5.6 | -5.8 |
February | 70810947.94 | 1378.16 | 18-FEB-13:30 | -14.4 | -15.8 | 0.230026E+09 | 406.61 | 07-FEB-10:09 | -14.4 | -15.8 |
March | 0.135105E+09 | 1689.49 | 11-MAR-13:40 | -3.7 | -5.7 | 0.299608E+09 | 428.82 | 22-MAR-14:50 | 5.60 | 2.17 |
April | 0.144886E+10 | 6778.66 | 22-APR-14:00 | 15.60 | 7.03 | 0.317045E+09 | 549.50 | 26-APR-13:00 | 10.60 | 4.23 |
May | 0.302021E+10 | 16831.79 | 14-MAY-12:32 | 18.53 | 9.40 | 0.388778E+09 | 549.51 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.447690E+10 | 9187.22 | 30-JUN-12:00 | 25.60 | 18.33 | 0.414666E+09 | 549.54 | 29-JUN-13:30 | 25.60 | 18.33 |
July | 0.529087E+10 | 15612.23 | 23-JUL-14:02 | 25.10 | 15.30 | 0.390690E+09 | 549.53 | 21-JUL-13:30 | 25.10 | 15.30 |
August | 0.475035E+10 | 17812.21 | 27-AUG-13:52 | 19.40 | 14.21 | 0.425798E+09 | 549.59 | 10-AUG-13:30 | 19.40 | 14.21 |
September | 0.193205E+10 | 7887.24 | 09-SEP-14:00 | 13.90 | 8.84 | 0.328063E+09 | 549.52 | 08-SEP-13:09 | 13.90 | 8.84 |
October | 0.432969E+09 | 3823.45 | 03-OCT-14:00 | 11.70 | 6.58 | 0.293954E+09 | 549.50 | 03-OCT-13:09 | 11.70 | 6.58 |
November | 17775382.27 | 1200.34 | 04-NOV-15:02 | -9.4 | -11.1 | 0.238037E+09 | 406.59 | 02-NOV-09:09 | -9.4 | -11.1 |
December | 13351395.31 | 1160.32 | 30-DEC-16:03 | -10.0 | -10.6 | 0.200990E+09 | 395.78 | 19-DEC-16:00 | -10.0 | -10.6 |
Annual Sum or Average | 0.216039E+11 | 0.375064E+10 | ||||||||
Minimum of Months | 13351395.31 | 1160.32 | -14.4 | -15.8 | 0.200990E+09 | 395.78 | -14.4 | -15.8 | ||
Maximum of Months | 0.529087E+10 | 17812.21 | 25.60 | 18.33 | 0.425798E+09 | 549.59 | 25.60 | 18.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13136424.87 | 790.56 | 21-JAN-16:03 | -5.6 | -5.8 | 0.192664E+09 | 257.48 | 03-JAN-14:00 | -5.6 | -5.8 |
February | 11208533.10 | 803.96 | 11-FEB-16:03 | -0.2 | -2.0 | 0.174959E+09 | 257.47 | 27-FEB-14:30 | -28.6 | -28.8 |
March | 0.101416E+09 | 1046.65 | 31-MAR-17:00 | -9.4 | -11.7 | 0.210381E+09 | 268.41 | 29-MAR-15:00 | -9.4 | -11.7 |
April | 0.121171E+10 | 4475.31 | 21-APR-18:20 | 14.03 | 5.87 | 0.204751E+09 | 338.67 | 28-APR-15:00 | 12.20 | 5.13 |
May | 0.219130E+10 | 4397.07 | 10-MAY-18:30 | 18.30 | 8.86 | 0.257318E+09 | 347.84 | 15-MAY-13:09 | 15.10 | 7.31 |
June | 0.333158E+10 | 11331.56 | 11-JUN-16:42 | 18.90 | 11.02 | 0.273055E+09 | 347.85 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.325357E+10 | 6163.49 | 31-JUL-18:30 | 25.00 | 14.57 | 0.254345E+09 | 347.85 | 07-JUL-13:09 | 25.00 | 14.57 |
August | 0.294602E+10 | 11343.05 | 27-AUG-17:52 | 20.60 | 12.18 | 0.282063E+09 | 347.85 | 01-AUG-09:00 | 20.60 | 12.18 |
September | 0.146249E+10 | 3172.68 | 02-SEP-17:33 | 16.70 | 10.34 | 0.219553E+09 | 347.83 | 01-SEP-13:00 | 16.70 | 10.34 |
October | 0.366775E+09 | 1200.19 | 03-OCT-15:20 | 12.43 | 6.74 | 0.197252E+09 | 307.15 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 11799164.46 | 808.53 | 02-NOV-20:03 | -9.4 | -9.7 | 0.191070E+09 | 257.47 | 28-NOV-14:50 | -25.5 | -25.7 |
December | 18774271.82 | 792.87 | 23-DEC-16:03 | -3.1 | -4.1 | 0.185810E+09 | 257.50 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.149198E+11 | 0.264322E+10 | ||||||||
Minimum of Months | 11208533.10 | 790.56 | -9.4 | -11.7 | 0.174959E+09 | 257.47 | -28.6 | -28.8 | ||
Maximum of Months | 0.333158E+10 | 11343.05 | 25.00 | 14.57 | 0.282063E+09 | 347.85 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12838453.95 | 953.12 | 06-JAN-21:03 | -5.7 | -6.4 | 0.302929E+09 | 406.72 | 03-JAN-14:00 | -5.7 | -6.4 |
February | 19336658.03 | 974.41 | 08-FEB-21:03 | -0.7 | -2.6 | 0.275461E+09 | 406.71 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.186408E+09 | 1202.99 | 22-MAR-15:40 | 5.60 | 2.48 | 0.332772E+09 | 440.76 | 22-MAR-13:00 | 5.60 | 2.48 |
April | 0.135970E+10 | 2108.91 | 28-APR-16:00 | 12.20 | 5.13 | 0.332371E+09 | 549.47 | 28-APR-13:00 | 12.20 | 5.13 |
May | 0.319845E+10 | 7764.45 | 31-MAY-06:03 | 14.08 | 8.75 | 0.431020E+09 | 549.50 | 19-MAY-13:00 | 14.08 | 8.75 |
June | 0.508099E+10 | 9040.24 | 07-JUN-04:02 | 5.87 | 4.55 | 0.435942E+09 | 549.51 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.471321E+10 | 8839.69 | 07-JUL-04:42 | 14.72 | 11.40 | 0.405203E+09 | 549.55 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.352138E+10 | 7435.59 | 02-AUG-06:02 | 11.28 | 10.30 | 0.448877E+09 | 549.49 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.160958E+10 | 2284.43 | 01-SEP-16:00 | 15.60 | 10.82 | 0.348906E+09 | 549.47 | 01-SEP-13:00 | 15.60 | 10.82 |
October | 0.406207E+09 | 1317.09 | 04-OCT-15:30 | 10.55 | 4.70 | 0.311637E+09 | 471.72 | 04-OCT-13:00 | 10.55 | 4.70 |
November | 11762045.06 | 962.11 | 02-NOV-20:03 | -9.4 | -9.7 | 0.300724E+09 | 406.71 | 17-NOV-10:00 | -25.0 | -25.3 |
December | 13015750.04 | 950.27 | 23-DEC-16:03 | -3.1 | -4.1 | 0.292482E+09 | 406.77 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.201329E+11 | 0.421832E+10 | ||||||||
Minimum of Months | 11762045.06 | 950.27 | -9.4 | -9.7 | 0.275461E+09 | 406.71 | -28.5 | -28.7 | ||
Maximum of Months | 0.508099E+10 | 9040.24 | 15.60 | 11.40 | 0.448877E+09 | 549.55 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15296317.09 | 923.32 | 21-JAN-16:03 | -5.6 | -5.8 | 0.141637E+09 | 250.71 | 10-JAN-16:00 | -5.6 | -5.8 |
February | 43972114.97 | 1032.81 | 09-FEB-11:35 | -2.2 | -2.5 | 0.128776E+09 | 254.01 | 09-FEB-11:50 | -2.0 | -2.3 |
March | 0.593593E+09 | 2094.02 | 31-MAR-10:10 | -15.9 | -17.2 | 0.160393E+09 | 338.72 | 31-MAR-10:30 | -15.6 | -16.9 |
April | 0.189630E+10 | 5648.10 | 22-APR-09:20 | 8.87 | 3.75 | 0.166221E+09 | 339.16 | 28-APR-07:40 | 4.67 | 1.87 |
May | 0.463327E+10 | 13128.05 | 14-MAY-09:22 | 15.55 | 8.14 | 0.202797E+09 | 339.59 | 12-MAY-08:00 | 15.55 | 8.14 |
June | 0.528105E+10 | 10601.44 | 04-JUN-10:13 | 17.97 | 11.85 | 0.203588E+09 | 339.42 | 08-JUN-08:20 | 14.07 | 9.39 |
July | 0.518337E+10 | 13273.16 | 23-JUL-10:02 | 21.38 | 14.90 | 0.189969E+09 | 339.73 | 31-JUL-10:30 | 18.85 | 11.80 |
August | 0.413193E+10 | 10365.87 | 10-AUG-06:02 | 10.78 | 7.96 | 0.210730E+09 | 339.51 | 10-AUG-10:30 | 18.60 | 11.60 |
September | 0.182360E+10 | 9623.61 | 10-SEP-09:23 | 11.95 | 6.71 | 0.165868E+09 | 338.97 | 28-SEP-10:00 | 2.20 | -0.8 |
October | 0.503891E+09 | 1956.80 | 03-OCT-10:05 | 4.27 | 2.93 | 0.146921E+09 | 338.95 | 03-OCT-10:00 | 6.10 | 4.15 |
November | 12240969.83 | 931.52 | 02-NOV-20:03 | -9.4 | -9.7 | 0.140322E+09 | 250.71 | 07-NOV-09:20 | -23.7 | -23.9 |
December | 13596675.76 | 921.06 | 23-DEC-16:03 | -3.1 | -4.1 | 0.136572E+09 | 250.71 | 27-DEC-13:50 | -23.8 | -24.0 |
Annual Sum or Average | 0.241321E+11 | 0.199379E+10 | ||||||||
Minimum of Months | 12240969.83 | 921.06 | -15.9 | -17.2 | 0.128776E+09 | 250.71 | -23.8 | -24.0 | ||
Maximum of Months | 0.528105E+10 | 13273.16 | 21.38 | 14.90 | 0.210730E+09 | 339.73 | 18.85 | 11.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76733061.71 | 1719.01 | 25-JAN-13:30 | -19.8 | -20.0 | 0.304785E+09 | 433.55 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.534916E+09 | 3785.84 | 15-FEB-13:40 | -8.7 | -9.6 | 0.286871E+09 | 549.49 | 09-FEB-14:50 | -8.7 | -9.6 |
March | 0.185415E+10 | 7632.95 | 31-MAR-13:30 | -11.4 | -13.3 | 0.372244E+09 | 549.49 | 06-MAR-14:00 | -11.4 | -13.3 |
April | 0.453115E+10 | 15883.25 | 23-APR-13:13 | 10.00 | 3.85 | 0.365133E+09 | 549.70 | 26-APR-09:50 | 4.22 | -0.3 |
May | 0.659181E+10 | 17134.95 | 21-MAY-15:02 | 15.68 | 7.35 | 0.427369E+09 | 550.26 | 12-MAY-13:50 | 15.68 | 7.35 |
June | 0.752930E+10 | 20042.22 | 04-JUN-14:52 | 19.40 | 11.69 | 0.433804E+09 | 549.54 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.742757E+10 | 20238.34 | 23-JUL-13:22 | 25.00 | 15.26 | 0.403448E+09 | 549.93 | 12-JUL-13:00 | 25.00 | 15.26 |
August | 0.713133E+10 | 21508.84 | 27-AUG-13:12 | 18.33 | 13.81 | 0.448222E+09 | 549.79 | 25-AUG-13:00 | 18.33 | 13.81 |
September | 0.376336E+10 | 9824.98 | 09-SEP-13:30 | 13.35 | 8.71 | 0.362877E+09 | 549.52 | 08-SEP-13:09 | 13.35 | 8.71 |
October | 0.137492E+10 | 8494.81 | 03-OCT-13:30 | 10.85 | 6.24 | 0.329927E+09 | 549.49 | 04-OCT-13:09 | 11.60 | 5.09 |
November | 0.164497E+09 | 2271.45 | 08-NOV-13:50 | -13.4 | -14.2 | 0.303755E+09 | 533.95 | 08-NOV-14:09 | -13.4 | -14.2 |
December | 21125253.33 | 1390.43 | 23-DEC-16:03 | -3.1 | -4.1 | 0.293619E+09 | 406.74 | 22-DEC-10:50 | -3.1 | -4.1 |
Annual Sum or Average | 0.410009E+11 | 0.433205E+10 | ||||||||
Minimum of Months | 21125253.33 | 1390.43 | -19.8 | -20.0 | 0.286871E+09 | 406.74 | -18.9 | -19.2 | ||
Maximum of Months | 0.752930E+10 | 21508.84 | 25.00 | 15.26 | 0.448222E+09 | 550.26 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15246911.07 | 915.86 | 06-JAN-21:03 | -5.7 | -6.4 | 0.192747E+09 | 257.47 | 03-JAN-14:00 | -5.7 | -6.4 |
February | 36598872.76 | 937.08 | 08-FEB-21:03 | -0.7 | -2.6 | 0.175111E+09 | 257.47 | 27-FEB-14:39 | -28.5 | -28.7 |
March | 0.328982E+09 | 1425.06 | 31-MAR-16:50 | -9.4 | -11.7 | 0.212431E+09 | 309.85 | 31-MAR-15:00 | -9.4 | -11.7 |
April | 0.191206E+10 | 6751.74 | 22-APR-17:08 | 14.13 | 6.18 | 0.212540E+09 | 347.80 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.321950E+10 | 12206.42 | 21-MAY-17:03 | 16.10 | 7.44 | 0.266405E+09 | 347.85 | 19-MAY-13:00 | 16.10 | 7.44 |
June | 0.441456E+10 | 13648.83 | 11-JUN-16:42 | 18.90 | 11.02 | 0.274494E+09 | 347.86 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.398609E+10 | 11487.96 | 08-JUL-18:33 | 20.00 | 15.32 | 0.254918E+09 | 347.88 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.336165E+10 | 13314.07 | 27-AUG-17:52 | 20.60 | 12.18 | 0.280103E+09 | 347.85 | 01-AUG-09:00 | 20.60 | 12.18 |
September | 0.161832E+10 | 4869.88 | 02-SEP-17:20 | 16.70 | 10.26 | 0.215683E+09 | 347.84 | 01-SEP-13:00 | 16.70 | 10.26 |
October | 0.378950E+09 | 1411.97 | 03-OCT-15:10 | 12.62 | 6.83 | 0.196755E+09 | 314.03 | 03-OCT-15:20 | 12.43 | 6.74 |
November | 14267275.84 | 924.22 | 02-NOV-20:03 | -9.4 | -9.7 | 0.190947E+09 | 257.47 | 27-NOV-14:50 | -23.9 | -24.2 |
December | 13451181.09 | 913.35 | 23-DEC-16:03 | -3.1 | -4.1 | 0.185833E+09 | 257.49 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.192997E+11 | 0.265797E+10 | ||||||||
Minimum of Months | 13451181.09 | 913.35 | -9.4 | -11.7 | 0.175111E+09 | 257.47 | -28.5 | -28.7 | ||
Maximum of Months | 0.441456E+10 | 13648.83 | 20.60 | 15.32 | 0.280103E+09 | 347.88 | 25.00 | 15.96 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.948972E+09 | 24316.42 | 02-JAN-05:01 | -15.6 |
February | 0.227413E+09 | 20701.26 | 22-FEB-06:03 | -30.0 |
March | 25128494.19 | 20760.88 | 06-MAR-06:01 | -21.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8.08 |
October | 3259119.61 | 18493.75 | 30-OCT-06:02 | -15.1 |
November | 0.150134E+09 | 20500.71 | 14-NOV-06:01 | -15.6 |
December | 0.331651E+09 | 20877.82 | 04-DEC-06:12 | -19.4 |
Annual Sum or Average | 0.168656E+10 | |||
Minimum of Months | 0.00 | 0.00 | -30.0 | |
Maximum of Months | 0.948972E+09 | 24316.42 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138951E+11 | 19129.46 | 12-JAN-06:05 | -38.3 |
February | 0.104621E+11 | 18548.22 | 27-FEB-06:09 | -35.9 |
March | 0.735069E+10 | 17544.09 | 01-MAR-06:13 | -28.5 |
April | 0.227908E+10 | 14930.24 | 03-APR-05:13 | -21.3 |
May | 0.420403E+09 | 5759.72 | 31-MAY-05:02 | 12.07 |
June | 0.104927E+09 | 7308.46 | 05-JUN-05:02 | 10.68 |
July | 97894421.37 | 6226.17 | 10-JUL-05:03 | 9.78 |
August | 0.336620E+09 | 4700.70 | 31-AUG-05:02 | -1.2 |
September | 0.148209E+10 | 7815.86 | 25-SEP-06:01 | -1.8 |
October | 0.557053E+10 | 14958.51 | 30-OCT-05:13 | -14.6 |
November | 0.128558E+11 | 17913.58 | 28-NOV-06:12 | -27.6 |
December | 0.147868E+11 | 18139.30 | 15-DEC-06:12 | -33.0 |
Annual Sum or Average | 0.696420E+11 | |||
Minimum of Months | 97894421.37 | 4700.70 | -38.3 | |
Maximum of Months | 0.147868E+11 | 19129.46 | 12.07 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.542202E+10 | 11624.10 | 02-JAN-07:04 | -14.4 |
February | 0.391204E+10 | 10750.59 | 21-FEB-07:03 | -23.2 |
March | 0.290908E+10 | 8121.38 | 06-MAR-07:02 | -20.9 |
April | 0.101096E+10 | 4779.81 | 23-APR-12:32 | 10.00 |
May | 64872022.59 | 4162.00 | 21-MAY-16:23 | 16.10 |
June | 22214668.50 | 3370.88 | 11-JUN-16:42 | 18.90 |
July | 25656899.62 | 3433.85 | 23-JUL-12:02 | 24.08 |
August | 39910133.07 | 4474.11 | 27-AUG-16:32 | 20.93 |
September | 0.548869E+09 | 3706.46 | 10-SEP-09:23 | 11.95 |
October | 0.222159E+10 | 8223.96 | 30-OCT-06:02 | -15.1 |
November | 0.464632E+10 | 10890.97 | 13-NOV-07:03 | -17.1 |
December | 0.532777E+10 | 10689.03 | 04-DEC-07:03 | -19.4 |
Annual Sum or Average | 0.261513E+11 | |||
Minimum of Months | 22214668.50 | 3370.88 | -23.2 | |
Maximum of Months | 0.542202E+10 | 11624.10 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403217E+10 | 9687.68 | 02-JAN-07:01 | -14.4 |
February | 0.292990E+10 | 6905.41 | 21-FEB-07:01 | -23.2 |
March | 0.205524E+10 | 4595.99 | 06-MAR-07:01 | -20.9 |
April | 0.540344E+09 | 3269.93 | 03-APR-07:55 | -17.8 |
May | 21177109.40 | 4493.38 | 25-MAY-05:02 | 4.87 |
June | 20948540.94 | 4116.83 | 07-JUN-04:02 | 5.87 |
July | 25813919.34 | 4158.68 | 06-JUL-05:03 | 8.77 |
August | 26634142.19 | 4798.36 | 30-AUG-05:02 | 0.00 |
September | 0.227544E+09 | 5310.81 | 05-SEP-05:02 | 5.00 |
October | 0.151169E+10 | 4591.87 | 30-OCT-06:01 | -15.1 |
November | 0.320413E+10 | 6976.27 | 13-NOV-07:01 | -17.1 |
December | 0.373147E+10 | 7078.48 | 04-DEC-07:01 | -19.4 |
Annual Sum or Average | 0.183271E+11 | |||
Minimum of Months | 20948540.94 | 3269.93 | -23.2 | |
Maximum of Months | 0.403217E+10 | 9687.68 | 8.77 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358192E+10 | 27246.83 | 02-JAN-05:01 | -15.6 |
February | 0.186969E+10 | 26521.55 | 21-FEB-05:11 | -23.0 |
March | 0.484007E+09 | 24623.03 | 06-MAR-06:01 | -21.1 |
April | 34577094.58 | 22944.20 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 838553.46 | 13975.89 | 25-SEP-06:01 | -1.8 |
October | 0.301145E+09 | 24538.57 | 30-OCT-05:01 | -14.5 |
November | 0.229909E+10 | 26347.34 | 13-NOV-05:01 | -20.2 |
December | 0.338534E+10 | 26439.07 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.119566E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.0 | |
Maximum of Months | 0.358192E+10 | 27246.83 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.999768E+10 | 29571.34 | 01-JAN-22:42 | -15.0 |
February | 0.624584E+10 | 29523.39 | 27-FEB-04:52 | -36.1 |
March | 0.320201E+10 | 28847.19 | 06-MAR-05:01 | -20.2 |
April | 0.530078E+09 | 27120.98 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 97260329.11 | 24423.05 | 25-SEP-05:01 | -1.2 |
October | 0.226884E+10 | 28800.08 | 30-OCT-04:01 | -14.4 |
November | 0.811930E+10 | 29400.66 | 13-NOV-05:01 | -20.2 |
December | 0.101468E+11 | 29285.89 | 04-DEC-04:52 | -20.0 |
Annual Sum or Average | 0.406078E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.101468E+11 | 29571.34 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105075E+11 | 10584.24 | 29-JAN-09:42 | -26.0 |
February | 0.782019E+10 | 10816.18 | 27-FEB-04:52 | -36.1 |
March | 0.522423E+10 | 10306.14 | 06-MAR-04:53 | -20.0 |
April | 0.108488E+10 | 10008.74 | 03-APR-03:53 | -21.1 |
May | 1355530.11 | 6247.75 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 4998086.13 | 7935.62 | 31-AUG-06:01 | -1.5 |
September | 0.394634E+09 | 9078.22 | 25-SEP-05:01 | -1.2 |
October | 0.368463E+10 | 10222.99 | 30-OCT-03:53 | -14.4 |
November | 0.940267E+10 | 10623.81 | 27-NOV-02:32 | -26.1 |
December | 0.109020E+11 | 10577.67 | 03-DEC-23:32 | -22.2 |
Annual Sum or Average | 0.490271E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.109020E+11 | 10816.18 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.698230E+10 | 11925.70 | 29-JAN-09:42 | -26.0 |
February | 0.465923E+10 | 12223.51 | 27-FEB-04:52 | -36.1 |
March | 0.230366E+10 | 11566.05 | 13-MAR-04:01 | -23.9 |
April | 0.451462E+09 | 11075.35 | 04-APR-04:01 | -10.3 |
May | 334228.68 | 2228.19 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 1867048.68 | 8965.09 | 31-AUG-06:01 | -1.5 |
September | 0.168011E+09 | 10312.67 | 25-SEP-05:01 | -1.2 |
October | 0.201248E+10 | 11355.41 | 31-OCT-04:11 | -18.0 |
November | 0.619600E+10 | 11965.72 | 27-NOV-02:32 | -26.1 |
December | 0.736738E+10 | 11905.90 | 03-DEC-23:32 | -22.2 |
Annual Sum or Average | 0.301427E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.736738E+10 | 12223.51 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.966067E+10 | 18817.66 | 29-JAN-09:42 | -26.0 |
February | 0.563606E+10 | 19243.27 | 27-FEB-04:52 | -36.1 |
March | 0.299181E+10 | 18179.80 | 01-MAR-05:01 | -28.3 |
April | 0.660098E+09 | 17412.63 | 03-APR-04:01 | -21.1 |
May | 3517246.09 | 8179.90 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 4085154.02 | 14208.14 | 31-AUG-06:01 | -1.5 |
September | 0.251929E+09 | 16253.78 | 25-SEP-05:01 | -1.2 |
October | 0.252876E+10 | 17926.25 | 31-OCT-04:11 | -18.0 |
November | 0.800315E+10 | 18896.12 | 27-NOV-02:32 | -26.1 |
December | 0.107546E+11 | 18824.91 | 03-DEC-23:32 | -22.2 |
Annual Sum or Average | 0.404947E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.107546E+11 | 19243.27 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.706897E+10 | 12449.30 | 29-JAN-09:42 | -26.0 |
February | 0.503668E+10 | 12773.23 | 27-FEB-04:52 | -36.1 |
March | 0.306742E+10 | 12093.08 | 13-MAR-04:01 | -23.9 |
April | 0.582457E+09 | 11524.27 | 04-APR-04:01 | -10.3 |
May | 2987295.08 | 5315.90 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 3606046.88 | 9158.04 | 31-AUG-06:01 | -1.5 |
September | 0.241811E+09 | 10815.98 | 25-SEP-05:01 | -1.2 |
October | 0.233805E+10 | 11877.36 | 31-OCT-04:11 | -18.0 |
November | 0.618731E+10 | 12505.69 | 27-NOV-02:32 | -26.1 |
December | 0.738302E+10 | 12438.03 | 03-DEC-23:32 | -22.2 |
Annual Sum or Average | 0.319123E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.738302E+10 | 12773.23 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.810670E+10 | 8098.51 | 01-JAN-19:22 | -14.4 |
February | 0.649202E+10 | 8125.34 | 27-FEB-04:52 | -36.1 |
March | 0.469270E+10 | 7830.41 | 01-MAR-05:11 | -28.3 |
April | 0.858151E+09 | 7616.13 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 35159099.66 | 6237.44 | 25-SEP-06:01 | -1.8 |
October | 0.144823E+10 | 7449.28 | 30-OCT-04:01 | -14.4 |
November | 0.579030E+10 | 7810.64 | 13-NOV-04:22 | -20.3 |
December | 0.755242E+10 | 7848.63 | 03-DEC-23:32 | -22.2 |
Annual Sum or Average | 0.349757E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.810670E+10 | 8125.34 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.568325E+10 | 9609.93 | 01-JAN-21:22 | -15.0 |
February | 0.401237E+10 | 9685.10 | 27-FEB-04:52 | -36.1 |
March | 0.183653E+10 | 9368.36 | 01-MAR-05:11 | -28.3 |
April | 0.246748E+09 | 8781.43 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 14122938.11 | 7470.90 | 25-SEP-06:01 | -1.8 |
October | 0.750377E+09 | 8917.93 | 30-OCT-04:01 | -14.4 |
November | 0.393979E+10 | 9336.81 | 13-NOV-05:01 | -20.2 |
December | 0.534398E+10 | 9343.06 | 03-DEC-23:32 | -22.2 |
Annual Sum or Average | 0.218272E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.568325E+10 | 9685.10 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180128E+11 | 26214.10 | 12-JAN-07:10 | -38.3 |
February | 0.130450E+11 | 24604.17 | 27-FEB-07:10 | -34.9 |
March | 0.107038E+11 | 22802.61 | 01-MAR-07:10 | -28.8 |
April | 0.374602E+10 | 20109.97 | 03-APR-06:10 | -21.5 |
May | 0.123622E+10 | 12975.82 | 04-MAY-06:10 | 4.18 |
June | 0.448061E+09 | 11800.67 | 02-JUN-06:10 | 7.15 |
July | 0.357795E+09 | 11695.78 | 17-JUL-06:05 | 8.48 |
August | 0.794652E+09 | 13731.42 | 31-AUG-06:10 | -1.5 |
September | 0.235299E+10 | 15352.62 | 28-SEP-06:10 | -2.8 |
October | 0.712034E+10 | 19430.41 | 31-OCT-07:00 | -19.4 |
November | 0.154173E+11 | 22649.18 | 29-NOV-07:10 | -28.9 |
December | 0.181412E+11 | 24203.54 | 15-DEC-07:10 | -33.4 |
Annual Sum or Average | 0.913762E+11 | |||
Minimum of Months | 0.357795E+09 | 11695.78 | -38.3 | |
Maximum of Months | 0.181412E+11 | 26214.10 | 8.48 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.577151E+10 | 10126.69 | 01-JAN-21:22 | -15.0 |
February | 0.439034E+10 | 10205.41 | 27-FEB-04:52 | -36.1 |
March | 0.265493E+10 | 9887.35 | 01-MAR-05:11 | -28.3 |
April | 0.295245E+09 | 8660.10 | 04-APR-05:01 | -11.6 |
May | 453799.86 | 2071.68 | 27-MAY-06:03 | 0.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 20277110.40 | 7888.12 | 25-SEP-06:01 | -1.8 |
October | 0.929285E+09 | 9445.66 | 30-OCT-04:01 | -14.4 |
November | 0.393740E+10 | 9848.34 | 13-NOV-05:01 | -20.2 |
December | 0.536028E+10 | 9782.36 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.233597E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.577151E+10 | 10205.41 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.681046E+10 | 8559.90 | 01-JAN-19:22 | -14.4 |
February | 0.463713E+10 | 8592.10 | 27-FEB-04:52 | -36.1 |
March | 0.267354E+10 | 8205.71 | 01-MAR-05:11 | -28.3 |
April | 0.352689E+09 | 7923.46 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 54794758.94 | 6817.94 | 30-SEP-05:01 | -4.5 |
October | 0.158054E+10 | 8158.13 | 23-OCT-04:01 | -11.1 |
November | 0.559080E+10 | 8436.74 | 13-NOV-04:22 | -20.3 |
December | 0.690820E+10 | 8383.24 | 11-DEC-03:12 | -21.1 |
Annual Sum or Average | 0.286081E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.690820E+10 | 8592.10 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462938E+10 | 11166.51 | 01-JAN-19:22 | -14.4 |
February | 0.274083E+10 | 11307.93 | 27-FEB-04:52 | -36.1 |
March | 0.108823E+10 | 10868.45 | 01-MAR-05:11 | -28.3 |
April | 0.142368E+09 | 10257.01 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 30091778.97 | 8673.33 | 28-SEP-06:01 | -2.8 |
October | 0.892284E+09 | 10653.74 | 23-OCT-04:01 | -11.1 |
November | 0.377278E+10 | 11024.36 | 13-NOV-05:01 | -20.2 |
December | 0.478291E+10 | 11041.03 | 11-DEC-05:11 | -19.0 |
Annual Sum or Average | 0.180789E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.478291E+10 | 11307.93 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.604268E+10 | 16855.32 | 01-JAN-19:22 | -14.4 |
February | 0.304116E+10 | 16957.77 | 27-FEB-04:52 | -36.1 |
March | 0.128141E+10 | 16298.32 | 01-MAR-05:11 | -28.3 |
April | 0.180699E+09 | 14549.33 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 36822551.69 | 13149.17 | 28-SEP-06:01 | -2.8 |
October | 0.988040E+09 | 15957.51 | 30-OCT-04:01 | -14.4 |
November | 0.445836E+10 | 16633.50 | 13-NOV-05:01 | -20.2 |
December | 0.669251E+10 | 16675.23 | 11-DEC-05:11 | -19.0 |
Annual Sum or Average | 0.227217E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.669251E+10 | 16957.77 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460857E+10 | 11116.10 | 01-JAN-20:02 | -14.5 |
February | 0.296202E+10 | 11252.87 | 27-FEB-04:52 | -36.1 |
March | 0.150515E+10 | 10818.67 | 01-MAR-05:11 | -28.3 |
April | 0.176547E+09 | 9907.41 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 16.35 |
September | 36950323.50 | 8648.32 | 28-SEP-06:01 | -2.8 |
October | 0.101093E+10 | 10630.85 | 23-OCT-04:01 | -11.1 |
November | 0.367135E+10 | 10974.06 | 13-NOV-05:01 | -20.2 |
December | 0.470107E+10 | 10992.25 | 11-DEC-05:11 | -19.0 |
Annual Sum or Average | 0.186726E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.470107E+10 | 11252.87 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.802300E+09 | 889.66 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.611945E+09 | 889.66 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.565431E+09 | 889.66 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.436714E+09 | 583.15 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.450367E+09 | 447.76 | 08-MAY-14:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.437514E+09 | 424.37 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.416993E+09 | 464.06 | 26-JUL-14:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.483193E+09 | 476.17 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.481226E+09 | 851.72 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.606403E+09 | 889.66 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.751257E+09 | 889.66 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.807293E+09 | 889.66 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.685064E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.416993E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.807293E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.492271E+09 | 563.23 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.369307E+09 | 563.23 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.350580E+09 | 563.23 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.276618E+09 | 291.58 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.290390E+09 | 268.66 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.281469E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.267837E+09 | 282.50 | 26-JUL-14:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.308606E+09 | 302.19 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.300088E+09 | 493.12 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.367568E+09 | 563.23 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.454386E+09 | 563.23 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.506680E+09 | 563.23 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426580E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.267837E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.506680E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.748972E+09 | 889.66 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.555934E+09 | 889.66 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.541985E+09 | 889.66 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.438537E+09 | 582.01 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.457880E+09 | 424.37 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.444989E+09 | 424.37 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.423122E+09 | 454.61 | 25-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.485631E+09 | 457.60 | 18-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.467259E+09 | 821.81 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.562262E+09 | 889.66 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.679104E+09 | 889.66 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.784094E+09 | 889.66 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.658977E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.423122E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.784094E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.496456E+09 | 563.19 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.365033E+09 | 563.19 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.349773E+09 | 563.19 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.278881E+09 | 417.84 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.285735E+09 | 282.45 | 23-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.278113E+09 | 291.21 | 27-JUN-07:30 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.264613E+09 | 300.46 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.305330E+09 | 300.55 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.299646E+09 | 540.46 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.367016E+09 | 563.19 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.455390E+09 | 563.19 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.508463E+09 | 563.19 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.425445E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.264613E+09 | 282.45 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.508463E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.799666E+09 | 889.66 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.606635E+09 | 889.66 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.562374E+09 | 889.66 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.435636E+09 | 568.62 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.449716E+09 | 442.99 | 08-MAY-14:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.436881E+09 | 424.37 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.416159E+09 | 460.65 | 26-JUL-14:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.482535E+09 | 472.54 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.478376E+09 | 849.36 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.601378E+09 | 889.66 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.746714E+09 | 889.66 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.806408E+09 | 889.66 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.682248E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.416159E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.806408E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.490705E+09 | 563.23 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.367543E+09 | 563.23 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.349543E+09 | 563.23 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.276192E+09 | 288.90 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.289948E+09 | 268.66 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.281100E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.267452E+09 | 268.66 | 03-JUL-07:10 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.308130E+09 | 300.12 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.299174E+09 | 487.99 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.366163E+09 | 563.23 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.452232E+09 | 563.23 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.505978E+09 | 563.23 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.425416E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.267452E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.505978E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.745749E+09 | 889.66 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.553796E+09 | 889.66 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.541046E+09 | 889.66 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.437672E+09 | 567.42 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.457133E+09 | 424.37 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.444271E+09 | 424.37 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.422423E+09 | 449.79 | 25-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.484851E+09 | 452.74 | 18-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.466260E+09 | 817.21 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.560152E+09 | 889.66 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.675345E+09 | 889.66 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.780571E+09 | 889.66 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.656927E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.422423E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.780571E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.494891E+09 | 563.19 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.363350E+09 | 563.19 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.348673E+09 | 563.19 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.278117E+09 | 412.67 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.285387E+09 | 268.64 | 01-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.277815E+09 | 288.72 | 27-JUN-07:30 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.264267E+09 | 298.38 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.304588E+09 | 298.48 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.298649E+09 | 539.23 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.364980E+09 | 563.19 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.452846E+09 | 563.19 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.507874E+09 | 563.19 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.424144E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.264267E+09 | 268.64 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.507874E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.802299E+09 | 889.66 | 02-JAN-08:09 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.611943E+09 | 889.66 | 01-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.565429E+09 | 889.66 | 01-MAR-08:09 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.436710E+09 | 583.13 | 04-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.450367E+09 | 447.75 | 08-MAY-14:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.437514E+09 | 424.37 | 01-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.416992E+09 | 464.06 | 26-JUL-14:30 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.483191E+09 | 476.16 | 18-AUG-15:00 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.481224E+09 | 851.73 | 28-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.606399E+09 | 889.66 | 03-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.751255E+09 | 889.66 | 01-NOV-07:10 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.807293E+09 | 889.66 | 01-DEC-08:09 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.685062E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.416992E+09 | 424.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.807293E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.492271E+09 | 563.23 | 02-JAN-08:09 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.369307E+09 | 563.23 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.350579E+09 | 563.23 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.276618E+09 | 291.58 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.290390E+09 | 268.66 | 01-MAY-07:10 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.281469E+09 | 268.66 | 01-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.267837E+09 | 282.50 | 26-JUL-14:30 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.308606E+09 | 302.18 | 18-AUG-15:00 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.300088E+09 | 493.13 | 28-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.367567E+09 | 563.23 | 03-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.454378E+09 | 563.23 | 01-NOV-07:10 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.506680E+09 | 563.23 | 01-DEC-08:09 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.426579E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.267837E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.506680E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.748972E+09 | 889.66 | 02-JAN-08:09 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.555934E+09 | 889.66 | 01-FEB-08:09 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.541984E+09 | 889.66 | 01-MAR-08:09 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.438537E+09 | 581.99 | 04-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.457876E+09 | 424.37 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.444989E+09 | 424.37 | 01-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.423122E+09 | 454.60 | 25-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.485629E+09 | 457.59 | 18-AUG-15:00 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.467258E+09 | 821.82 | 28-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.562262E+09 | 889.66 | 03-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.679092E+09 | 889.66 | 01-NOV-07:10 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.784096E+09 | 889.66 | 01-DEC-08:09 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.658975E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.423122E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.784096E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.496455E+09 | 563.19 | 02-JAN-08:09 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.365032E+09 | 563.19 | 01-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.349773E+09 | 563.19 | 01-MAR-08:09 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.278881E+09 | 417.83 | 04-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.285735E+09 | 282.45 | 23-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.278113E+09 | 291.20 | 27-JUN-07:30 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.264612E+09 | 300.45 | 25-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.305330E+09 | 300.55 | 07-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.299626E+09 | 540.46 | 29-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.367014E+09 | 563.19 | 03-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.455389E+09 | 563.19 | 01-NOV-07:10 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.508463E+09 | 563.19 | 01-DEC-08:09 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.425442E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.264612E+09 | 282.45 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.508463E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.802300E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235506E+09 |
February | 0.901968E+09 | 0.611945E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189009E+09 |
March | 0.107774E+10 | 0.565431E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277741E+09 |
April | 0.956342E+09 | 0.436714E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310138E+09 |
May | 0.103597E+10 | 0.450367E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191013E+09 |
June | 0.103308E+10 | 0.437514E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251973.60 | 0.115851E+09 |
July | 0.959235E+09 | 0.416993E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 815023.93 | 85589584.21 |
August | 0.107774E+10 | 0.483193E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114933.31 | 98915625.35 |
September | 0.956342E+09 | 0.481226E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111065E+09 |
October | 0.994195E+09 | 0.606403E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237115E+09 |
November | 0.984487E+09 | 0.751257E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86460768.24 |
December | 0.959235E+09 | 0.807293E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170659E+09 |
Annual Sum or Average | 0.119305E+11 | 0.685064E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1181930.84 | 0.210906E+10 |
Minimum of Months | 0.901968E+09 | 0.416993E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85589584.21 |
Maximum of Months | 0.107774E+10 | 0.807293E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 815023.93 | 0.310138E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.492271E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157144E+09 |
February | 0.571020E+09 | 0.369307E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126121E+09 |
March | 0.682301E+09 | 0.350580E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186734E+09 |
April | 0.605444E+09 | 0.276618E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212496E+09 |
May | 0.655854E+09 | 0.290390E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130961E+09 |
June | 0.654023E+09 | 0.281469E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167985.62 | 77563942.46 |
July | 0.607275E+09 | 0.267837E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 541856.46 | 57788916.76 |
August | 0.682301E+09 | 0.308606E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76947.10 | 67102306.80 |
September | 0.605444E+09 | 0.300088E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76344937.11 |
October | 0.629407E+09 | 0.367568E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158937E+09 |
November | 0.623262E+09 | 0.454386E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57636460.17 |
December | 0.607275E+09 | 0.506680E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113827E+09 |
Annual Sum or Average | 0.755301E+10 | 0.426580E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 786789.18 | 0.142266E+10 |
Minimum of Months | 0.571020E+09 | 0.267837E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57636460.17 |
Maximum of Months | 0.682301E+09 | 0.506680E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 541856.46 | 0.212496E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.748972E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236074E+09 |
February | 0.901968E+09 | 0.555934E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190392E+09 |
March | 0.107774E+10 | 0.541985E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286240E+09 |
April | 0.956342E+09 | 0.438537E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331916E+09 |
May | 0.103597E+10 | 0.457880E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197921E+09 |
June | 0.103308E+10 | 0.444989E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251965.47 | 0.116433E+09 |
July | 0.959235E+09 | 0.423122E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 736104.99 | 87116528.47 |
August | 0.107774E+10 | 0.485631E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114624.94 | 0.102863E+09 |
September | 0.956342E+09 | 0.467259E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117613E+09 |
October | 0.994195E+09 | 0.562262E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242698E+09 |
November | 0.984487E+09 | 0.679104E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86685713.14 |
December | 0.959235E+09 | 0.784094E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170922E+09 |
Annual Sum or Average | 0.119305E+11 | 0.658977E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1102695.40 | 0.216688E+10 |
Minimum of Months | 0.901968E+09 | 0.423122E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86685713.14 |
Maximum of Months | 0.107774E+10 | 0.784094E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 736104.99 | 0.331916E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.496456E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157149E+09 |
February | 0.570983E+09 | 0.365033E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126105E+09 |
March | 0.682256E+09 | 0.349773E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186376E+09 |
April | 0.605404E+09 | 0.278881E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217619E+09 |
May | 0.655811E+09 | 0.285735E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132021E+09 |
June | 0.653980E+09 | 0.278113E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 167987.67 | 78416692.81 |
July | 0.607235E+09 | 0.264613E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 443114.79 | 58416471.80 |
August | 0.682256E+09 | 0.305330E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76510.12 | 67602963.37 |
September | 0.605404E+09 | 0.299646E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75670745.24 |
October | 0.629366E+09 | 0.367016E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158414E+09 |
November | 0.623221E+09 | 0.455390E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57654545.87 |
December | 0.607235E+09 | 0.508463E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113827E+09 |
Annual Sum or Average | 0.755252E+10 | 0.425445E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 687612.58 | 0.142927E+10 |
Minimum of Months | 0.570983E+09 | 0.264613E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57654545.87 |
Maximum of Months | 0.682256E+09 | 0.508463E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 443114.79 | 0.217619E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.799666E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126184E+09 |
February | 0.901968E+09 | 0.606635E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101087E+09 |
March | 0.107774E+10 | 0.562374E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149904E+09 |
April | 0.956342E+09 | 0.435636E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165768E+09 |
May | 0.103597E+10 | 0.449716E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98848924.38 |
June | 0.103308E+10 | 0.436881E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138831.40 | 59980686.29 |
July | 0.959235E+09 | 0.416159E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509708.99 | 44842266.59 |
August | 0.107774E+10 | 0.482535E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67656.19 | 54135832.36 |
September | 0.956342E+09 | 0.478376E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63601350.38 |
October | 0.994195E+09 | 0.601378E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134528E+09 |
November | 0.984487E+09 | 0.746714E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47210084.18 |
December | 0.959235E+09 | 0.806408E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92042934.73 |
Annual Sum or Average | 0.119305E+11 | 0.682248E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 716196.57 | 0.113813E+10 |
Minimum of Months | 0.901968E+09 | 0.416159E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44842266.59 |
Maximum of Months | 0.107774E+10 | 0.806408E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 509708.99 | 0.165768E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.490705E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84175538.57 |
February | 0.571020E+09 | 0.367543E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67509421.10 |
March | 0.682301E+09 | 0.349543E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101210E+09 |
April | 0.605444E+09 | 0.276192E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115929E+09 |
May | 0.655854E+09 | 0.289948E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71259330.79 |
June | 0.654023E+09 | 0.281100E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92558.62 | 41539717.95 |
July | 0.607275E+09 | 0.267452E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 276850.93 | 31470623.58 |
August | 0.682301E+09 | 0.308130E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43314.98 | 37619918.04 |
September | 0.605444E+09 | 0.299174E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44592850.57 |
October | 0.629407E+09 | 0.366163E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90833598.59 |
November | 0.623262E+09 | 0.452232E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31398279.33 |
December | 0.607275E+09 | 0.505978E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61270225.81 |
Annual Sum or Average | 0.755301E+10 | 0.425416E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 412724.53 | 0.778809E+09 |
Minimum of Months | 0.571020E+09 | 0.267452E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31398279.33 |
Maximum of Months | 0.682301E+09 | 0.505978E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 276850.93 | 0.115929E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.745749E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146725E+11 |
February | 0.901968E+09 | 0.553796E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116250E+11 |
March | 0.107774E+10 | 0.541046E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128225E+11 |
April | 0.956342E+09 | 0.437672E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722573E+10 |
May | 0.103597E+10 | 0.457133E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433735E+10 |
June | 0.103308E+10 | 0.444271E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45442146.70 | 0.253262E+10 |
July | 0.959235E+09 | 0.422423E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66204143.44 | 0.194785E+10 |
August | 0.107774E+10 | 0.484851E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15476162.66 | 0.363957E+10 |
September | 0.956342E+09 | 0.466260E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557807E+10 |
October | 0.994195E+09 | 0.560152E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932455E+10 |
November | 0.984487E+09 | 0.675345E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145928E+11 |
December | 0.959235E+09 | 0.780571E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149038E+11 |
Annual Sum or Average | 0.119305E+11 | 0.656927E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127122E+09 | 0.103202E+12 |
Minimum of Months | 0.901968E+09 | 0.422423E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194785E+10 |
Maximum of Months | 0.107774E+10 | 0.780571E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66204143.44 | 0.149038E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.494891E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84173043.27 |
February | 0.570983E+09 | 0.363350E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67450415.35 |
March | 0.682256E+09 | 0.348673E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100611E+09 |
April | 0.605404E+09 | 0.278117E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118226E+09 |
May | 0.655811E+09 | 0.285387E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70064613.23 |
June | 0.653980E+09 | 0.277815E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92557.27 | 41610954.87 |
July | 0.607235E+09 | 0.264267E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 252513.41 | 31230371.27 |
August | 0.682256E+09 | 0.304588E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43316.76 | 37591293.50 |
September | 0.605404E+09 | 0.298649E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43747521.65 |
October | 0.629366E+09 | 0.364980E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89973106.53 |
November | 0.623221E+09 | 0.452846E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31418382.91 |
December | 0.607235E+09 | 0.507874E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61268143.39 |
Annual Sum or Average | 0.755252E+10 | 0.424144E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 388387.44 | 0.777365E+09 |
Minimum of Months | 0.570983E+09 | 0.264267E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31230371.27 |
Maximum of Months | 0.682256E+09 | 0.507874E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 252513.41 | 0.118226E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.802299E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198346E+09 |
February | 0.901968E+09 | 0.611943E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159832E+09 |
March | 0.107774E+10 | 0.565429E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238824E+09 |
April | 0.956342E+09 | 0.436710E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271940E+09 |
May | 0.103597E+10 | 0.450367E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166863E+09 |
June | 0.103308E+10 | 0.437514E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 213544.34 | 99745957.01 |
July | 0.959235E+09 | 0.416992E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 696085.40 | 73571630.92 |
August | 0.107774E+10 | 0.483191E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98603.33 | 86669595.54 |
September | 0.956342E+09 | 0.481224E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99811056.64 |
October | 0.994195E+09 | 0.606399E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207658E+09 |
November | 0.984487E+09 | 0.751255E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73302205.17 |
December | 0.959235E+09 | 0.807293E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144060E+09 |
Annual Sum or Average | 0.119305E+11 | 0.685062E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1008233.07 | 0.182062E+10 |
Minimum of Months | 0.901968E+09 | 0.416992E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73302205.17 |
Maximum of Months | 0.107774E+10 | 0.807293E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 696085.40 | 0.271940E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.492271E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132189E+09 |
February | 0.421807E+09 | 0.369307E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106591E+09 |
March | 0.502994E+09 | 0.350579E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160808E+09 |
April | 0.447140E+09 | 0.276618E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185542E+09 |
May | 0.484071E+09 | 0.290390E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113106E+09 |
June | 0.482240E+09 | 0.281469E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142360.16 | 66375524.05 |
July | 0.448971E+09 | 0.267837E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 475353.39 | 49331430.71 |
August | 0.502994E+09 | 0.308606E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66243.20 | 58165645.85 |
September | 0.447140E+09 | 0.300088E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67882417.37 |
October | 0.465148E+09 | 0.367567E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139288E+09 |
November | 0.460569E+09 | 0.454378E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48779488.41 |
December | 0.448971E+09 | 0.506680E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95904120.47 |
Annual Sum or Average | 0.557719E+10 | 0.426579E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 683956.74 | 0.122396E+10 |
Minimum of Months | 0.421807E+09 | 0.267837E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48779488.41 |
Maximum of Months | 0.502994E+09 | 0.506680E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 475353.39 | 0.185542E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.748972E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198849E+09 |
February | 0.901968E+09 | 0.555934E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161643E+09 |
March | 0.107774E+10 | 0.541984E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247189E+09 |
April | 0.956342E+09 | 0.438537E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289241E+09 |
May | 0.103597E+10 | 0.457876E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171479E+09 |
June | 0.103308E+10 | 0.444989E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 213536.41 | 0.100049E+09 |
July | 0.959235E+09 | 0.423122E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 638320.10 | 74704131.51 |
August | 0.107774E+10 | 0.485629E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98450.07 | 89334755.31 |
September | 0.956342E+09 | 0.467258E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104403E+09 |
October | 0.994195E+09 | 0.562262E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213581E+09 |
November | 0.984487E+09 | 0.679092E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73677421.56 |
December | 0.959235E+09 | 0.784096E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144230E+09 |
Annual Sum or Average | 0.119305E+11 | 0.658975E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 950306.58 | 0.186838E+10 |
Minimum of Months | 0.901968E+09 | 0.423122E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73677421.56 |
Maximum of Months | 0.107774E+10 | 0.784096E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 638320.10 | 0.289241E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.496455E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132196E+09 |
February | 0.570983E+09 | 0.365032E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106528E+09 |
March | 0.682256E+09 | 0.349773E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160401E+09 |
April | 0.605404E+09 | 0.278881E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189840E+09 |
May | 0.655811E+09 | 0.285735E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114543E+09 |
June | 0.653980E+09 | 0.278113E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 142367.55 | 67350341.92 |
July | 0.607235E+09 | 0.264612E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 379102.48 | 50103976.64 |
August | 0.682256E+09 | 0.305330E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65738.19 | 58942021.08 |
September | 0.605404E+09 | 0.299626E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67454487.76 |
October | 0.629366E+09 | 0.367014E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138697E+09 |
November | 0.623221E+09 | 0.455389E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48820693.54 |
December | 0.607235E+09 | 0.508463E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95908928.79 |
Annual Sum or Average | 0.755252E+10 | 0.425442E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 587208.22 | 0.123079E+10 |
Minimum of Months | 0.570983E+09 | 0.264612E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48820693.54 |
Maximum of Months | 0.682256E+09 | 0.508463E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 379102.48 | 0.189840E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258286E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209982E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320063E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370462E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221820E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146269.77 | 0.129900E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573033.55 | 96058307.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35334.10 | 0.116522E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137635E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284464E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97634469.04 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188360E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 754637.42 | 0.243119E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96058307.72 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573033.55 | 0.370462E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328334E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267077E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404850E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466312E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282638E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183901.68 | 0.166425E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767014.08 | 0.122753E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47097.09 | 0.147290E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169119E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349531E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122792E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239022E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 998012.84 | 0.306614E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122753E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767014.08 | 0.466312E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344720E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279253E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418397E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481929E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297317E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115423.54 | 0.179045E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512931.91 | 0.133385E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8798.10 | 0.154194E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170745E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354471E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127161E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250397E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637153.54 | 0.319101E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127161E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 512931.91 | 0.481929E+09 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1062.95 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 889.66 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 625.54 | 25-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 889.66 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 459.67 | 14-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 583.15 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 673.51 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 447.76 | 08-MAY-14:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 320.13 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 30-JUN-15:00 | 309.63 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 464.06 | 26-JUL-14:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 21-JUL-16:00 | 236.96 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 476.17 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 11-AUG-16:00 | 246.43 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 851.72 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 188.43 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 889.66 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 390.60 | 21-OCT-04:05 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 335.05 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 362.36 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.43 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 1062.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 708.63 | 28-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 563.23 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 416.90 | 25-FEB-00:53 |
March | 827.22 | 01-MAR-10:09 | 563.23 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 306.58 | 14-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 291.58 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 449.10 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 268.66 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 214.41 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.69 | 30-JUN-15:00 | 206.17 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 282.50 | 26-JUL-14:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.77 | 29-JUL-19:57 | 159.18 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 302.19 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 11-AUG-16:00 | 163.96 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 493.12 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 127.48 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 563.23 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 263.17 | 21-OCT-04:05 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 223.37 | 10-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 241.57 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.48 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 24.77 | 708.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1062.95 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 889.66 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 626.25 | 25-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 889.66 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 501.25 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 582.01 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 740.95 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 424.37 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 324.30 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 30-JUN-15:00 | 306.91 | 24-JUN-21:00 |
July | 1306.65 | 03-JUL-09:09 | 454.61 | 25-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 21-JUL-16:00 | 241.97 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 457.60 | 18-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.35 | 11-AUG-16:00 | 247.68 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 821.81 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 192.84 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 889.66 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 393.61 | 21-OCT-04:05 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 335.04 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 362.36 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.84 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 1062.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 708.63 | 28-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 563.19 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 416.75 | 25-FEB-00:53 |
March | 827.17 | 01-MAR-10:09 | 563.19 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 306.68 | 14-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 417.84 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 550.32 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 282.45 | 23-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 214.34 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 291.21 | 27-JUN-07:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.69 | 30-JUN-15:00 | 203.63 | 24-JUN-21:00 |
July | 827.17 | 03-JUL-09:09 | 300.46 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 | 21-JUL-16:00 | 161.37 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 300.55 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.57 | 11-AUG-16:00 | 163.51 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 540.46 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 125.25 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 563.19 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 263.24 | 21-OCT-04:05 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 223.36 | 10-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 241.57 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 282.45 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.25 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 | 708.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 564.43 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 889.66 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 334.58 | 25-FEB-01:00 |
March | 1306.65 | 01-MAR-10:09 | 889.66 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 244.31 | 14-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 568.62 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 358.85 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 442.99 | 08-MAY-14:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 172.07 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 | 30-JUN-15:00 | 171.55 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 460.65 | 26-JUL-14:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.88 | 29-JUL-20:00 | 122.92 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 472.54 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 11-AUG-16:00 | 139.91 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 849.36 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 109.66 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 889.66 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 217.64 | 21-OCT-04:03 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 183.85 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 192.42 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.66 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.88 | 564.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 376.29 | 28-JAN-24:00 |
February | 827.22 | 01-FEB-10:09 | 563.23 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 223.06 | 25-FEB-01:00 |
March | 827.22 | 01-MAR-10:09 | 563.23 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 163.13 | 14-MAR-21:03 |
April | 827.22 | 03-APR-09:09 | 288.90 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 241.79 | 01-APR-18:55 |
May | 827.22 | 01-MAY-09:09 | 268.66 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 119.37 | 26-MAY-02:00 |
June | 827.22 | 01-JUN-09:09 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 30-JUN-15:00 | 115.37 | 25-JUN-06:00 |
July | 827.22 | 03-JUL-09:09 | 268.66 | 03-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 21-JUL-16:00 | 84.52 | 04-JUL-17:00 |
August | 827.22 | 01-AUG-09:09 | 300.12 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 11-AUG-16:00 | 94.86 | 30-AUG-01:00 |
September | 827.22 | 01-SEP-09:09 | 487.99 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 76.56 | 04-SEP-14:00 |
October | 827.22 | 02-OCT-09:09 | 563.23 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 145.22 | 21-OCT-04:03 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 122.10 | 10-NOV-02:00 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 128.28 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.56 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 376.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 79055.05 | 12-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 889.66 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 72724.33 | 27-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 889.66 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 65123.44 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 567.42 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 57021.39 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 424.37 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 22063.51 | 16-MAY-06:03 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2557.13 | 21-JUN-17:00 | 17825.67 | 02-JUN-06:05 |
July | 1306.65 | 03-JUL-09:09 | 449.79 | 25-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6004.15 | 21-JUL-16:10 | 16480.31 | 05-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 452.74 | 18-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1948.54 | 11-AUG-16:10 | 28474.49 | 31-AUG-06:01 |
September | 1306.65 | 01-SEP-09:09 | 817.21 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 31657.67 | 29-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 889.66 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 52323.80 | 27-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 65674.49 | 28-NOV-12:01 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 72722.15 | 15-DEC-12:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16480.31 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6004.15 | 79055.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 376.29 | 28-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 563.19 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 223.06 | 25-FEB-01:00 |
March | 827.17 | 01-MAR-10:09 | 563.19 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 163.06 | 14-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 412.67 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 284.78 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 268.64 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 115.32 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 288.72 | 27-JUN-07:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.22 | 30-JUN-15:00 | 114.03 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 298.38 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 21-JUL-16:00 | 85.00 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 298.48 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 11-AUG-16:00 | 94.51 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 539.23 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 74.79 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 563.19 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 144.59 | 21-OCT-04:03 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 122.31 | 10-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 128.28 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.79 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 376.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 884.25 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 889.66 | 01-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 527.75 | 25-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 889.66 | 01-MAR-08:09 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 383.98 | 14-MAR-21:03 |
April | 1306.65 | 03-APR-09:09 | 583.13 | 04-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 579.69 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 447.75 | 08-MAY-14:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 282.88 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 30-JUN-15:00 | 279.77 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 464.06 | 26-JUL-14:30 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.21 | 21-JUL-16:00 | 203.57 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 476.16 | 18-AUG-15:00 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 | 11-AUG-16:00 | 218.83 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 851.73 | 28-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 172.25 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 889.66 | 03-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 333.54 | 21-OCT-04:03 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 01-NOV-07:10 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 284.50 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-08:09 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 299.25 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.25 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 30.21 | 884.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 563.23 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 589.50 | 28-JAN-24:00 |
February | 805.43 | 01-FEB-08:09 | 563.23 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 351.39 | 25-FEB-00:53 |
March | 805.43 | 01-MAR-08:09 | 563.23 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 256.11 | 14-MAR-21:03 |
April | 805.43 | 03-APR-07:10 | 291.58 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 386.87 | 01-APR-18:55 |
May | 805.43 | 01-MAY-07:10 | 268.66 | 01-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 188.91 | 26-MAY-02:00 |
June | 805.43 | 01-JUN-07:10 | 268.66 | 01-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 | 30-JUN-15:00 | 186.04 | 25-JUN-06:00 |
July | 805.43 | 03-JUL-07:10 | 282.50 | 26-JUL-14:30 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 | 29-JUL-20:00 | 136.71 | 04-JUL-17:00 |
August | 805.43 | 01-AUG-07:10 | 302.18 | 18-AUG-15:00 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 11-AUG-16:00 | 145.23 | 30-AUG-01:00 |
September | 805.43 | 01-SEP-07:10 | 493.13 | 28-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 116.29 | 04-SEP-14:00 |
October | 805.43 | 02-OCT-07:10 | 563.23 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 221.98 | 21-OCT-04:03 |
November | 805.43 | 01-NOV-07:10 | 563.23 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 188.96 | 10-NOV-02:00 |
December | 805.43 | 01-DEC-08:09 | 563.23 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 198.68 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.29 | |||||
Maximum of Months | 805.43 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 | 589.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-08:09 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 884.25 | 28-JAN-24:00 |
February | 1306.65 | 01-FEB-10:09 | 889.66 | 01-FEB-08:09 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 531.12 | 25-FEB-00:53 |
March | 1306.65 | 01-MAR-10:09 | 889.66 | 01-MAR-08:09 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 436.90 | 12-MAR-15:00 |
April | 1306.65 | 03-APR-09:09 | 581.99 | 04-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 633.89 | 01-APR-18:55 |
May | 1306.65 | 01-MAY-09:09 | 424.37 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 285.80 | 26-MAY-02:00 |
June | 1306.65 | 01-JUN-09:09 | 424.37 | 01-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.18 | 30-JUN-15:00 | 276.39 | 25-JUN-06:00 |
July | 1306.65 | 03-JUL-09:09 | 454.60 | 25-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.21 | 21-JUL-16:00 | 207.60 | 04-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 457.59 | 18-AUG-15:00 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 | 11-AUG-16:00 | 219.41 | 30-AUG-01:00 |
September | 1306.65 | 01-SEP-09:09 | 821.82 | 28-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 175.70 | 04-SEP-14:00 |
October | 1306.65 | 02-OCT-09:09 | 889.66 | 03-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 342.45 | 22-OCT-17:55 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 01-NOV-07:10 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 286.69 | 10-NOV-02:00 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-08:09 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 300.00 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.70 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 30.21 | 884.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-08:09 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 589.50 | 28-JAN-24:00 |
February | 827.17 | 01-FEB-10:09 | 563.19 | 01-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 350.85 | 25-FEB-00:53 |
March | 827.17 | 01-MAR-10:09 | 563.19 | 01-MAR-08:09 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 256.16 | 14-MAR-21:03 |
April | 827.17 | 03-APR-09:09 | 417.83 | 04-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 468.57 | 01-APR-18:55 |
May | 827.17 | 01-MAY-09:09 | 282.45 | 23-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 189.20 | 26-MAY-02:00 |
June | 827.17 | 01-JUN-09:09 | 291.20 | 27-JUN-07:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 | 30-JUN-15:00 | 183.33 | 25-JUN-06:00 |
July | 827.17 | 03-JUL-09:09 | 300.45 | 25-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 | 21-JUL-16:00 | 138.61 | 04-JUL-17:00 |
August | 827.17 | 01-AUG-09:09 | 300.55 | 07-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 11-AUG-16:00 | 145.26 | 30-AUG-01:00 |
September | 827.17 | 01-SEP-09:09 | 540.46 | 29-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 114.62 | 04-SEP-14:00 |
October | 827.17 | 02-OCT-09:09 | 563.19 | 03-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 221.64 | 21-OCT-04:03 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 01-NOV-07:10 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 189.31 | 10-NOV-02:00 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-08:09 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 198.88 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 282.45 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.62 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 | 589.50 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1191.50 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 710.54 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 502.71 | 25-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 794.16 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 379.71 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 | 30-JUN-15:00 | 369.35 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 29-JUL-17:03 | 251.23 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 | 11-AUG-16:00 | 296.96 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 227.36 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 466.24 | 21-OCT-04:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 388.62 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 404.64 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.36 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 1191.50 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1505.22 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 912.12 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 632.94 | 14-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1003.04 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 485.00 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.10 | 30-JUN-15:00 | 462.82 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.56 | 29-JUL-17:03 | 318.40 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | 11-AUG-16:00 | 375.76 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 272.22 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 575.88 | 21-OCT-04:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 491.96 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 518.06 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.22 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.56 | 1505.22 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1556.18 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 945.57 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 682.23 | 14-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1103.35 | 01-APR-18:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 476.97 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.09 | 30-JUN-15:00 | 466.29 | 24-JUN-21:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.73 | 21-JUL-16:00 | 367.87 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.28 | 11-AUG-16:00 | 364.95 | 30-AUG-01:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 292.12 | 04-SEP-14:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 575.38 | 21-OCT-04:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 500.84 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 537.92 | 28-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.12 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.73 | 1556.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6854.64 | 27-JAN-17:00 | 6035.01 | 4220.20 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7408.94 | 10-FEB-17:00 | 6035.01 | 4220.20 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9486.63 | 23-MAR-08:00 | 6035.01 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23671.09 | 28-APR-05:02 | 3811.58 | 2813.51 | 29937.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40179.51 | 16-MAY-05:02 | 3176.32 | 2344.59 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41523.75 | 12-JUN-04:02 | 0.00 | 2344.59 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41747.86 | 24-JUL-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 42117.46 | 14-AUG-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 39709.81 | 05-SEP-05:02 | 3176.32 | 2344.59 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15766.15 | 04-OCT-07:20 | 12070.02 | 8440.40 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7331.94 | 03-NOV-16:00 | 6035.01 | 4220.20 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6611.18 | 21-DEC-16:20 | 6035.01 | 4220.20 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 6611.18 | 0.00 | 1875.67 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42117.46 | 12070.02 | 8440.40 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.06 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.09 |
March | 825.91 | 22-MAR-17:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.60 |
April | 3314.30 | 21-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.18 |
May | 6526.30 | 31-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.31 |
June | 7609.47 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 | 0.00 |
July | 7711.66 | 21-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 | 0.00 |
August | 6502.17 | 10-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 |
September | 2255.37 | 07-SEP-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 |
October | 732.25 | 03-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.64 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.81 |
December | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7711.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 | 307.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2572.14 | 11-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2563.13 | 25-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.29 |
March | 2595.66 | 02-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.99 |
April | 2304.30 | 14-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 |
May | 2916.91 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
June | 3797.00 | 30-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 | 0.00 |
July | 4070.24 | 12-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 | 0.00 |
August | 3427.97 | 11-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.89 | 0.00 |
September | 1178.61 | 22-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.16 |
October | 1634.94 | 05-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 |
November | 2185.33 | 29-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2639.90 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1178.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4070.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.10 | 642.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5638.22 | 12-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4318.77 | 17-FEB-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5620.74 | 31-MAR-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4136.59 | 03-APR-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.11 |
May | 3389.71 | 16-MAY-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.81 |
June | 3870.06 | 12-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 |
July | 4718.48 | 24-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.56 |
August | 3990.99 | 28-AUG-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.87 |
September | 3033.41 | 15-SEP-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 |
October | 3720.57 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.50 |
November | 4440.89 | 09-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4598.59 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3033.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5638.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5248.83 | 20-JAN-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5871.51 | 09-FEB-16:30 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6482.68 | 22-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10646.20 | 28-APR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27396.74 | 15-MAY-05:02 | 3176.32 | 2344.59 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29333.19 | 15-JUN-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 31026.97 | 24-JUL-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30447.13 | 01-AUG-05:02 | 3176.32 | 2344.59 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11149.47 | 01-SEP-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6988.54 | 05-OCT-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5417.57 | 02-NOV-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5023.77 | 21-DEC-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5023.77 | 0.00 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31026.97 | 6035.01 | 4220.20 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 4903.43 | 06-JAN-21:03 | 2541.06 | 3751.34 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5624.97 | 09-FEB-15:50 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6483.52 | 22-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10078.82 | 28-APR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15297.43 | 31-MAY-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20457.78 | 05-JUN-05:02 | 3176.32 | 2344.59 | 15129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 25717.38 | 24-JUL-06:01 | 8893.70 | 9847.27 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18133.69 | 03-AUG-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9811.20 | 01-SEP-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6664.19 | 03-OCT-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4844.24 | 02-NOV-20:03 | 2541.06 | 3751.34 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4801.24 | 19-DEC-21:03 | 2541.06 | 3751.34 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 4801.24 | 2541.06 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25717.38 | 8893.70 | 9847.27 | 21181.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1126.75 | 06-JAN-21:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.22 |
February | 1137.64 | 10-FEB-21:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 |
March | 1337.13 | 22-MAR-15:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1884.70 | 28-APR-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.65 |
May | 7801.50 | 31-MAY-05:02 | 669.60 | 235.76 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 |
June | 9527.75 | 13-JUN-06:02 | 1607.03 | 848.74 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 |
July | 9536.65 | 11-JUL-06:02 | 1339.19 | 707.29 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.32 |
August | 4495.02 | 02-AUG-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 |
September | 1896.94 | 01-SEP-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.49 |
October | 1382.24 | 04-OCT-15:30 | 1272.23 | 477.94 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.38 |
November | 1112.56 | 02-NOV-20:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1106.38 | 23-DEC-16:03 | 535.68 | 593.09 | 2232.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1106.38 | 535.68 | 235.76 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9536.65 | 1607.03 | 848.74 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 928.75 | 06-JAN-21:03 | 339.13 | 500.65 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.07 |
February | 939.51 | 10-FEB-21:03 | 339.13 | 500.65 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 |
March | 1528.26 | 22-MAR-10:40 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.10 |
April | 4971.92 | 22-APR-09:30 | 261.23 | 89.55 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 |
May | 14246.12 | 14-MAY-09:12 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.21 |
June | 12068.22 | 04-JUN-09:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.80 |
July | 13456.64 | 23-JUL-09:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.57 |
August | 10589.65 | 11-AUG-06:02 | 1017.38 | 537.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 |
September | 3626.98 | 09-SEP-09:45 | 522.45 | 179.11 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 |
October | 1514.63 | 03-OCT-10:05 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 |
November | 916.99 | 02-NOV-20:03 | 339.13 | 500.65 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 912.94 | 23-DEC-16:03 | 339.13 | 375.47 | 1413.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 912.94 | 169.56 | 59.70 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14246.12 | 1610.86 | 537.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1595.78 | 25-JAN-13:22 | 6361.16 | 2121.83 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 |
February | 3016.00 | 15-FEB-14:00 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6704.97 | 31-MAR-14:00 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.32 |
April | 12070.90 | 20-APR-14:10 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 |
May | 22233.10 | 14-MAY-12:32 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.73 |
June | 16896.36 | 18-JUN-13:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.67 |
July | 22017.32 | 23-JUL-13:42 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
August | 20281.15 | 27-AUG-13:22 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.61 |
September | 9418.12 | 07-SEP-14:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.94 |
October | 7863.62 | 03-OCT-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.12 |
November | 2202.59 | 08-NOV-14:00 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.54 |
December | 1453.87 | 23-DEC-16:03 | 535.68 | 593.09 | 2232.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1453.87 | 267.84 | 94.29 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22233.10 | 6361.16 | 2121.83 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 972.59 | 06-JAN-21:03 | 339.11 | 500.62 | 1615.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.06 |
February | 982.68 | 10-FEB-21:03 | 339.11 | 500.62 | 1615.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 |
March | 1405.88 | 29-MAR-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.92 |
April | 6179.89 | 20-APR-18:10 | 169.55 | 179.10 | 807.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 |
May | 14114.89 | 14-MAY-18:32 | 0.00 | 74.61 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.20 |
June | 12762.41 | 10-JUN-17:05 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 |
July | 11686.65 | 08-JUL-18:33 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.98 |
August | 11025.10 | 27-AUG-18:42 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.96 |
September | 3797.88 | 08-SEP-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 |
October | 1408.41 | 03-OCT-15:10 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 |
November | 959.89 | 02-NOV-20:03 | 339.11 | 500.62 | 1615.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 955.12 | 23-DEC-16:03 | 339.11 | 375.45 | 1413.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 955.12 | 0.00 | 59.69 | 807.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14114.89 | 805.38 | 500.62 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1025.55 | 21-JAN-16:03 | 535.68 | 593.09 | 2232.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1041.97 | 10-FEB-21:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 |
March | 1063.36 | 23-MAR-20:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 |
April | 1489.80 | 28-APR-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 |
May | 2364.85 | 31-MAY-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 |
June | 7076.24 | 13-JUN-06:02 | 1607.03 | 848.74 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
July | 7231.91 | 11-JUL-06:02 | 1339.19 | 707.29 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.07 |
August | 3680.02 | 02-AUG-15:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 1917.92 | 05-SEP-05:02 | 669.60 | 494.26 | 3189.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 |
October | 1370.99 | 06-OCT-15:00 | 1272.23 | 478.45 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.14 |
November | 1048.80 | 02-NOV-20:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1028.75 | 23-DEC-16:03 | 535.68 | 593.09 | 2232.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1025.55 | 535.68 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7231.91 | 1607.03 | 848.74 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 750.04 | 21-JAN-16:03 | 339.13 | 375.47 | 1413.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 837.51 | 09-FEB-07:03 | 1695.64 | 1877.44 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 |
March | 1193.93 | 31-MAR-09:40 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.07 |
April | 3248.96 | 22-APR-08:40 | 254.35 | 89.55 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 |
May | 10977.04 | 14-MAY-09:12 | 254.35 | 89.54 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 |
June | 8643.78 | 13-JUN-06:02 | 1017.38 | 537.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.89 |
July | 9210.30 | 09-JUL-06:42 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 |
August | 8543.84 | 11-AUG-06:02 | 1017.38 | 537.32 | 2422.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.10 |
September | 6726.05 | 10-SEP-09:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.64 |
October | 1713.74 | 03-OCT-09:35 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 |
November | 784.02 | 02-NOV-06:03 | 1695.64 | 1877.44 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 751.53 | 23-DEC-16:03 | 339.13 | 375.47 | 1413.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 750.04 | 169.56 | 59.70 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10977.04 | 1695.64 | 1877.44 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1173.29 | 21-JAN-16:03 | 535.68 | 593.09 | 2232.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1378.16 | 18-FEB-13:30 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.36 |
March | 1689.49 | 11-MAR-13:40 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 |
April | 6778.66 | 22-APR-14:00 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 |
May | 16831.79 | 14-MAY-12:32 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.44 |
June | 9187.22 | 30-JUN-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 1950.31 | 0.00 |
July | 15612.23 | 23-JUL-14:02 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 |
August | 17812.21 | 27-AUG-13:52 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.10 |
September | 7887.24 | 09-SEP-14:00 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 |
October | 3823.45 | 03-OCT-14:00 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2274.31 |
November | 1200.34 | 04-NOV-15:02 | 535.68 | 408.45 | 2232.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.84 |
December | 1160.32 | 30-DEC-16:03 | 535.68 | 593.09 | 2232.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1160.32 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17812.21 | 1306.65 | 593.09 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 1950.31 | 2274.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 790.56 | 21-JAN-16:03 | 339.11 | 375.45 | 1413.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 803.96 | 11-FEB-16:03 | 339.11 | 357.70 | 1413.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 |
March | 1046.65 | 31-MAR-17:00 | 254.33 | 149.24 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.75 |
April | 4475.31 | 21-APR-18:20 | 84.78 | 89.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 |
May | 4397.07 | 10-MAY-18:30 | 84.78 | 89.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 |
June | 11331.56 | 11-JUN-16:42 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.36 |
July | 6163.49 | 31-JUL-18:30 | 84.78 | 89.55 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
August | 11343.05 | 27-AUG-17:52 | 0.00 | 74.61 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.02 |
September | 3172.68 | 02-SEP-17:33 | 127.16 | 44.77 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 |
October | 1200.19 | 03-OCT-15:20 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.26 |
November | 808.53 | 02-NOV-20:03 | 339.11 | 500.62 | 1615.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 792.87 | 23-DEC-16:03 | 339.11 | 375.45 | 1413.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 790.56 | 0.00 | 44.77 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11343.05 | 805.38 | 500.62 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 48.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 953.12 | 06-JAN-21:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.80 |
February | 974.41 | 08-FEB-21:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 |
March | 1202.99 | 22-MAR-15:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2108.91 | 28-APR-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 |
May | 7764.45 | 31-MAY-06:03 | 1071.35 | 565.83 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 |
June | 9040.24 | 07-JUN-04:02 | 0.00 | 235.76 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.43 |
July | 8839.69 | 07-JUL-04:42 | 0.00 | 188.61 | 2059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.39 |
August | 7435.59 | 02-AUG-06:02 | 1607.03 | 848.74 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.76 |
September | 2284.43 | 01-SEP-16:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 |
October | 1317.09 | 04-OCT-15:30 | 1272.23 | 477.94 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 |
November | 962.11 | 02-NOV-20:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 950.27 | 23-DEC-16:03 | 535.68 | 593.09 | 2232.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 950.27 | 0.00 | 188.61 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9040.24 | 1607.03 | 848.74 | 3827.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 923.32 | 21-JAN-16:03 | 339.13 | 375.47 | 1413.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1032.81 | 09-FEB-11:35 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.34 |
March | 2094.02 | 31-MAR-10:10 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 |
April | 5648.10 | 22-APR-09:20 | 0.00 | 89.55 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 |
May | 13128.05 | 14-MAY-09:22 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.46 |
June | 10601.44 | 04-JUN-10:13 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.97 |
July | 13273.16 | 23-JUL-10:02 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 |
August | 10365.87 | 10-AUG-06:02 | 847.82 | 447.77 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 |
September | 9623.61 | 10-SEP-09:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.31 |
October | 1956.80 | 03-OCT-10:05 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.40 |
November | 931.52 | 02-NOV-20:03 | 339.13 | 500.65 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 921.06 | 23-DEC-16:03 | 339.13 | 375.47 | 1413.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 921.06 | 0.00 | 59.70 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13273.16 | 1610.86 | 537.32 | 2019.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1719.01 | 25-JAN-13:30 | 6361.16 | 2121.83 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.73 |
February | 3785.84 | 15-FEB-13:40 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7632.95 | 31-MAR-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.98 |
April | 15883.25 | 23-APR-13:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.02 |
May | 17134.95 | 21-MAY-15:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.02 |
June | 20042.22 | 04-JUN-14:52 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.33 |
July | 20238.34 | 23-JUL-13:22 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 |
August | 21508.84 | 27-AUG-13:12 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.38 |
September | 9824.98 | 09-SEP-13:30 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.64 |
October | 8494.81 | 03-OCT-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.99 |
November | 2271.45 | 08-NOV-13:50 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 |
December | 1390.43 | 23-DEC-16:03 | 535.68 | 593.09 | 2232.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1390.43 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21508.84 | 6361.16 | 2121.83 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 915.86 | 06-JAN-21:03 | 339.11 | 500.62 | 1615.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 |
February | 937.08 | 08-FEB-21:03 | 339.11 | 500.62 | 1615.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.06 |
March | 1425.06 | 31-MAR-16:50 | 254.33 | 149.24 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.65 |
April | 6751.74 | 22-APR-17:08 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.55 |
May | 12206.42 | 21-MAY-17:03 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.76 |
June | 13648.83 | 11-JUN-16:42 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.01 |
July | 11487.96 | 08-JUL-18:33 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.58 |
August | 13314.07 | 27-AUG-17:52 | 0.00 | 74.61 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.66 |
September | 4869.88 | 02-SEP-17:20 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.07 |
October | 1411.97 | 03-OCT-15:10 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 |
November | 924.22 | 02-NOV-20:03 | 339.11 | 500.62 | 1615.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 913.35 | 23-DEC-16:03 | 339.11 | 375.45 | 1413.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 913.35 | 0.00 | 59.69 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13648.83 | 805.38 | 500.62 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.55 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.240258E+12 | 272878.57 | 02-JAN-08:09 | 0.656908E+11 | 207548.76 | 12-JAN-07:30 |
February | 0.185158E+12 | 254819.62 | 27-FEB-07:10 | 0.425823E+11 | 187060.02 | 27-FEB-08:09 |
March | 0.160980E+12 | 227528.02 | 06-MAR-07:10 | 0.221857E+11 | 165342.17 | 01-MAR-07:19 |
April | 0.100327E+12 | 182604.08 | 03-APR-06:10 | 0.110325E+11 | 28028.09 | 03-APR-06:19 |
May | 0.936102E+11 | 99708.05 | 31-MAY-15:00 | 0.110889E+11 | 13332.29 | 04-MAY-11:20 |
June | 0.105486E+12 | 127747.49 | 30-JUN-12:30 | 0.106298E+11 | 12722.74 | 01-JUN-11:30 |
July | 0.108246E+12 | 127912.33 | 11-JUL-15:00 | 0.101212E+11 | 11646.84 | 03-JUL-11:39 |
August | 0.104151E+12 | 122740.17 | 11-AUG-15:50 | 0.106203E+11 | 10847.45 | 03-AUG-11:30 |
September | 0.923397E+11 | 115920.29 | 25-SEP-06:10 | 0.988878E+10 | 11241.48 | 25-SEP-15:00 |
October | 0.137503E+12 | 213525.32 | 30-OCT-06:10 | 0.125217E+11 | 26052.13 | 31-OCT-07:10 |
November | 0.211354E+12 | 250532.42 | 27-NOV-07:10 | 0.589506E+11 | 164753.61 | 29-NOV-07:40 |
December | 0.241280E+12 | 247461.85 | 04-DEC-07:10 | 0.846113E+11 | 186545.80 | 15-DEC-07:40 |
Annual Sum or Average | 0.178069E+13 | 0.349924E+12 | ||||
Minimum of Months | 0.923397E+11 | 99708.05 | 0.988878E+10 | 10847.45 | ||
Maximum of Months | 0.241280E+12 | 272878.57 | 0.846113E+11 | 207548.76 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.197094E+11 | 0.863647E+10 | 0.593559E+11 | 0.982958E+09 | 0.661219E+10 | 1312252.65 | 0.141439E+12 | 2132491.00 | 0.00 | 0.00 | 0.351878E+10 | 0.00 | 0.00 |
February | 0.166699E+11 | 0.594683E+10 | 0.537310E+11 | 0.888122E+09 | 0.556339E+10 | 1186778.30 | 0.991291E+11 | 3292422.14 | 0.00 | 0.00 | 0.322473E+10 | 0.00 | 0.00 |
March | 0.184575E+11 | 0.464097E+10 | 0.617796E+11 | 0.102635E+10 | 0.522103E+10 | 1343621.24 | 0.660297E+11 | 10191657.72 | 0.00 | 0.00 | 0.381282E+10 | 0.00 | 0.00 |
April | 0.159368E+11 | 0.286957E+10 | 0.572952E+11 | 0.943532E+09 | 0.511811E+10 | 1267813.82 | 0.159474E+11 | 24363578.28 | 0.00 | 0.00 | 0.219084E+10 | 0.00 | 0.00 |
May | 0.170203E+11 | 0.174062E+10 | 0.605677E+11 | 0.100260E+10 | 0.848815E+10 | 1327936.95 | 0.170099E+10 | 0.281876E+10 | 0.00 | 0.00 | 0.269680E+09 | 0.00 | 0.00 |
June | 0.168329E+11 | 0.926888E+09 | 0.594895E+11 | 0.986915E+09 | 0.126947E+11 | 1296568.36 | 0.596074E+09 | 0.137740E+11 | 0.00 | 0.00 | 0.183508E+09 | 0.00 | 0.00 |
July | 0.158239E+11 | 0.131211E+10 | 0.583622E+11 | 0.958967E+09 | 0.124877E+11 | 1299182.41 | 0.476693E+09 | 0.185341E+11 | 0.00 | 0.00 | 0.289420E+09 | 0.00 | 0.00 |
August | 0.177860E+11 | 0.238496E+10 | 0.617796E+11 | 0.102587E+10 | 0.101467E+11 | 1343621.24 | 0.108508E+10 | 0.978285E+10 | 0.00 | 0.00 | 0.158514E+09 | 0.00 | 0.00 |
September | 0.162866E+11 | 0.374902E+10 | 0.572729E+11 | 0.943502E+09 | 0.498936E+10 | 1267813.82 | 0.732715E+10 | 0.160700E+09 | 0.00 | 0.00 | 0.160929E+10 | 0.00 | 0.00 |
October | 0.177976E+11 | 0.568164E+10 | 0.593671E+11 | 0.980716E+09 | 0.455744E+10 | 1312252.65 | 0.459183E+11 | 13147724.94 | 0.00 | 0.00 | 0.318562E+10 | 0.00 | 0.00 |
November | 0.189640E+11 | 0.757987E+10 | 0.580818E+11 | 0.964096E+09 | 0.579865E+10 | 1278270.02 | 0.116551E+12 | 1798029.49 | 0.00 | 0.00 | 0.341096E+10 | 0.00 | 0.00 |
December | 0.195223E+11 | 0.948343E+10 | 0.583511E+11 | 0.962817E+09 | 0.659931E+10 | 1299182.41 | 0.142879E+12 | 1286339.51 | 0.00 | 0.00 | 0.347957E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.210807E+12 | 0.549524E+11 | 0.705434E+12 | 0.116664E+11 | 0.882767E+11 | 15535293.87 | 0.639079E+12 | 0.451267E+11 | 0.00 | 0.00 | 0.253337E+11 | 0.00 | 0.00 |
Minimum of Months | 0.158239E+11 | 0.926888E+09 | 0.537310E+11 | 0.888122E+09 | 0.455744E+10 | 1186778.30 | 0.476693E+09 | 1286339.51 | 0.00 | 0.00 | 0.158514E+09 | 0.00 | 0.00 |
Maximum of Months | 0.197094E+11 | 0.948343E+10 | 0.617796E+11 | 0.102635E+10 | 0.126947E+11 | 1343621.24 | 0.142879E+12 | 0.185341E+11 | 0.00 | 0.00 | 0.381282E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.547339E+11 | 0.00 | 0.109569E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.326597E+11 | 0.00 | 0.992258E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.107409E+11 | 0.00 | 0.114449E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.501161E+09 | 0.00 | 0.105313E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 18311704.13 | 0.00 | 0.110706E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.106298E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.101212E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 7025246.36 | 0.00 | 0.106133E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 81093812.69 | 0.00 | 0.980769E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.223297E+10 | 0.00 | 0.102887E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.486302E+11 | 0.00 | 0.103204E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.739496E+11 | 0.00 | 0.106616E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.223555E+12 | 0.00 | 0.126369E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.980769E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.739496E+11 | 0.00 | 0.114449E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21377.78 | 02-JAN-08:09 | 5557.43 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 835.33 | 12-JAN-08:30 | 8006.41 | 02-JAN-06:19 | 0.73 | 02-JAN-06:10 | 216624.51 | 02-JAN-06:19 |
February | 21377.78 | 01-FEB-08:09 | 5557.43 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 835.33 | 09-FEB-08:20 | 7497.84 | 27-FEB-07:10 | 0.73 | 01-FEB-07:10 | 210572.61 | 27-FEB-07:10 |
March | 21377.78 | 01-MAR-08:09 | 5557.43 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 835.33 | 01-MAR-08:20 | 6182.69 | 06-MAR-07:10 | 0.73 | 01-MAR-07:10 | 184596.16 | 06-MAR-07:10 |
April | 18247.32 | 04-APR-07:10 | 5557.43 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 831.19 | 04-APR-07:19 | 9403.97 | 21-APR-15:00 | 0.73 | 03-APR-06:10 | 141038.99 | 03-APR-06:10 |
May | 16884.10 | 08-MAY-14:30 | 3195.36 | 01-MAY-21:10 | 45864.70 | 01-MAY-07:10 | 829.33 | 23-MAY-07:19 | 17566.37 | 31-MAY-15:09 | 0.73 | 01-MAY-05:10 | 18239.87 | 03-MAY-06:10 |
June | 16883.91 | 27-JUN-07:30 | 3195.36 | 01-JUN-22:49 | 45864.70 | 01-JUN-07:10 | 829.38 | 27-JUN-07:40 | 22261.35 | 20-JUN-15:30 | 0.73 | 01-JUN-05:10 | 14714.13 | 02-JUN-06:10 |
July | 17043.79 | 25-JUL-07:10 | 3195.36 | 11-JUL-22:00 | 45864.70 | 03-JUL-07:10 | 829.59 | 25-JUL-07:19 | 24674.61 | 12-JUL-15:09 | 0.73 | 01-JUL-05:19 | 14752.40 | 05-JUL-06:19 |
August | 17209.35 | 18-AUG-15:00 | 5557.43 | 24-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 829.58 | 07-AUG-07:19 | 22384.68 | 11-AUG-15:50 | 0.73 | 30-AUG-07:10 | 26380.88 | 31-AUG-06:10 |
September | 20768.42 | 28-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 834.52 | 28-SEP-07:19 | 7736.65 | 08-SEP-15:30 | 0.73 | 08-SEP-07:10 | 75277.75 | 25-SEP-06:10 |
October | 21377.78 | 03-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 835.33 | 11-OCT-07:19 | 5664.41 | 30-OCT-06:10 | 0.73 | 03-OCT-06:10 | 171014.60 | 30-OCT-06:10 |
November | 21377.78 | 01-NOV-07:10 | 5557.43 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 835.33 | 01-NOV-07:19 | 7249.31 | 27-NOV-07:10 | 0.73 | 01-NOV-06:10 | 206533.94 | 27-NOV-07:10 |
December | 21377.78 | 01-DEC-08:09 | 5557.43 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 835.33 | 01-DEC-08:20 | 7101.89 | 11-DEC-06:10 | 0.73 | 01-DEC-07:10 | 203709.88 | 04-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 16883.91 | 3195.36 | 45864.70 | 829.33 | 5664.41 | 0.73 | 14714.13 | |||||||
Maximum of Months | 21377.78 | 5557.43 | 45864.70 | 835.33 | 24674.61 | 0.73 | 216624.51 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 444.36 | 07-JAN-07:10 | 0.00 | 0.00 | 2722.67 | 06-JAN-18:30 | 0.00 | 0.00 |
February | 478.58 | 11-FEB-07:10 | 0.00 | 0.00 | 2722.67 | 02-FEB-07:30 | 0.00 | 0.00 |
March | 623.93 | 18-MAR-06:10 | 0.00 | 0.00 | 2722.67 | 01-MAR-08:50 | 0.00 | 0.00 |
April | 1490.04 | 22-APR-13:00 | 0.00 | 0.00 | 2722.67 | 01-APR-15:09 | 0.00 | 0.00 |
May | 23443.06 | 31-MAY-15:00 | 0.00 | 0.00 | 2722.67 | 01-MAY-20:40 | 0.00 | 0.00 |
June | 43567.01 | 30-JUN-14:30 | 0.00 | 0.00 | 2722.67 | 20-JUN-15:50 | 0.00 | 0.00 |
July | 41820.43 | 11-JUL-15:00 | 0.00 | 0.00 | 2722.67 | 29-JUL-16:10 | 0.00 | 0.00 |
August | 37913.04 | 11-AUG-15:50 | 0.00 | 0.00 | 2722.67 | 30-AUG-06:19 | 0.00 | 0.00 |
September | 5887.27 | 07-SEP-15:00 | 0.00 | 0.00 | 2722.67 | 08-SEP-06:19 | 0.00 | 0.00 |
October | 464.13 | 21-OCT-06:10 | 0.00 | 0.00 | 2722.67 | 02-OCT-17:10 | 0.00 | 0.00 |
November | 446.61 | 04-NOV-06:10 | 0.00 | 0.00 | 2722.67 | 01-NOV-06:30 | 0.00 | 0.00 |
December | 401.08 | 23-DEC-07:10 | 0.00 | 0.00 | 2722.67 | 02-DEC-17:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 401.08 | 0.00 | 0.00 | 2722.67 | 0.00 | 0.00 | ||
Maximum of Months | 43567.01 | 0.00 | 0.00 | 2722.67 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 272878.57 | 02-JAN-08:09 | 21377.78 | 45864.70 | 5557.43 | 816.58 | 5986.42 | 0.73 | 190552.26 | 0.00 | 0.00 |
February | 254819.62 | 27-FEB-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 7497.84 | 0.73 | 210572.61 | 0.00 | 0.00 |
March | 227528.02 | 06-MAR-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 6182.69 | 0.73 | 184596.16 | 0.00 | 0.00 |
April | 182604.08 | 03-APR-06:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 4815.92 | 0.73 | 141038.99 | 0.00 | 0.00 |
May | 99708.05 | 31-MAY-15:00 | 16818.70 | 42072.41 | 0.00 | 827.95 | 16545.20 | 0.73 | 0.00 | 23443.06 | 0.00 |
June | 127747.49 | 30-JUN-12:30 | 16818.70 | 42402.18 | 0.00 | 828.07 | 21619.08 | 0.73 | 0.00 | 43356.07 | 0.00 |
July | 127912.33 | 11-JUL-15:00 | 16818.70 | 42072.41 | 0.00 | 827.95 | 23649.44 | 0.73 | 0.00 | 41820.43 | 0.00 |
August | 122740.17 | 11-AUG-15:50 | 16818.70 | 42072.41 | 0.00 | 827.95 | 22384.68 | 0.73 | 0.00 | 37913.04 | 0.00 |
September | 115920.29 | 25-SEP-06:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 3636.45 | 0.73 | 75277.75 | 256.92 | 0.00 |
October | 213525.32 | 30-OCT-06:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 5664.41 | 0.73 | 171014.60 | 97.13 | 0.00 |
November | 250532.42 | 27-NOV-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 7249.31 | 0.73 | 206533.94 | 0.00 | 0.00 |
December | 247461.85 | 04-DEC-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 7002.80 | 0.73 | 203709.88 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 99708.05 | 7126.03 | 21098.80 | 0.00 | 243.52 | 3636.45 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 272878.57 | 21377.78 | 45864.70 | 5557.43 | 828.07 | 23649.44 | 0.73 | 210572.61 | 43356.07 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 199286.53 | 12-JAN-07:30 | 0.00 | 13393.85 | 30-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 178152.22 | 27-FEB-08:09 | 0.00 | 13372.85 | 22-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 158003.49 | 01-MAR-07:30 | 0.00 | 13368.34 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 19732.76 | 03-APR-06:19 | 0.00 | 13327.28 | 26-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 2222.02 | 04-MAY-06:19 | 0.00 | 13332.29 | 04-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 12722.74 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 11646.84 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 1827.72 | 30-AUG-08:39 | 0.00 | 10847.45 | 03-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 2792.55 | 30-SEP-06:10 | 0.00 | 10652.76 | 27-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 17707.91 | 31-OCT-06:00 | 0.00 | 11491.23 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 157793.32 | 29-NOV-07:30 | 0.00 | 12468.78 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 178628.42 | 15-DEC-07:30 | 0.00 | 13359.52 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10652.76 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 199286.53 | 0.00 | 13393.85 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.42 | 1.67 | 19.54 | 0.00 | 19.54 | 0.00 | 19.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.19 | 0.00 | 26.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.83 | 19.42 | 1.67 | 19.54 | 0.17 | 19.84 | 0.00 | 19.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.42 | 1.67 | 19.54 | 0.17 | 26.19 | 0.00 | 26.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 18.88 | 2.50 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
February | 0.83 | 18.86 | 0.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
March | 0.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.41 | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
November | 0.83 | 19.28 | 0.83 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 1.17 | 18.14 | 0.67 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
Annual Sum or Average | 6.50 | 18.82 | 5.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.42 | 2.50 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.00 | 18.85 | 8.50 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 8.33 | 18.81 | 6.33 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
March | 2.00 | 18.98 | 1.67 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
April | 0.17 | 19.32 | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.50 | 18.89 | 1.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
November | 9.33 | 18.95 | 7.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 10.33 | 18.84 | 8.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Annual Sum or Average | 42.67 | 18.87 | 33.33 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.00 | 19.32 | 8.50 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 91.83 | 16.67 | 52.50 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
February | 74.17 | 16.55 | 40.33 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
March | 33.50 | 17.59 | 18.67 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
April | 3.83 | 17.75 | 2.00 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.23 | 0.00 | 26.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15.67 | 16.79 | 7.00 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
November | 84.50 | 16.64 | 49.50 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
December | 101.00 | 16.79 | 57.00 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
Annual Sum or Average | 404.50 | 16.76 | 227.00 | 17.24 | 0.17 | 17.24 | 0.00 | 17.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.00 | 17.75 | 57.00 | 18.38 | 0.17 | 26.23 | 0.00 | 26.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.67 | 14.70 | 17.00 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
February | 41.67 | 14.90 | 10.50 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
March | 13.33 | 15.43 | 0.83 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
April | 1.33 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.01 | 2.67 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.58 | 1.17 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.88 | 3.83 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9.17 | 15.28 | 1.00 | 15.23 | 0.00 | 15.23 | 0.00 | 15.23 |
November | 52.33 | 14.87 | 17.33 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
December | 61.33 | 14.83 | 16.67 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
Annual Sum or Average | 234.83 | 14.88 | 63.33 | 14.88 | 7.83 | 15.21 | 7.83 | 15.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.33 | 15.82 | 17.33 | 15.82 | 3.83 | 28.01 | 3.83 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.33 | 14.77 | 15.00 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
February | 32.17 | 14.97 | 5.00 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
March | 8.83 | 15.64 | 0.33 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
April | 0.50 | 16.87 | 0.00 | 16.87 | 1.00 | 23.98 | 1.00 | 25.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.81 | 3.67 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.77 | 2.67 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.14 | 3.33 | 28.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.10 | 1.50 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
October | 6.50 | 15.32 | 0.83 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
November | 41.33 | 14.97 | 11.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
December | 55.83 | 14.86 | 15.67 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
Annual Sum or Average | 195.50 | 14.93 | 47.83 | 14.93 | 12.50 | 15.56 | 12.33 | 16.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.77 | 0.00 | 14.77 |
Maximum of Months | 55.83 | 16.87 | 15.67 | 16.87 | 3.67 | 28.14 | 3.67 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.33 | 14.70 | 17.50 | 14.69 | 0.00 | 14.69 | 0.00 | 14.69 |
February | 43.00 | 14.81 | 11.83 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
March | 13.50 | 15.38 | 1.33 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
April | 0.83 | 16.02 | 0.00 | 16.02 | 0.50 | 20.38 | 0.17 | 21.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.72 | 0.67 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.91 | 1.00 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.61 | 1.00 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.90 | 0.50 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10.17 | 15.27 | 1.83 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
November | 51.50 | 14.87 | 17.67 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
December | 61.00 | 14.80 | 16.50 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
Annual Sum or Average | 236.33 | 14.85 | 66.67 | 14.84 | 11.33 | 15.31 | 3.33 | 15.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 61.00 | 16.02 | 17.67 | 16.02 | 3.67 | 27.91 | 1.00 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 99.33 | 18.47 | 81.50 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
February | 77.33 | 18.36 | 61.83 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
March | 24.67 | 19.16 | 21.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
April | 2.17 | 19.32 | 1.83 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.23 | 0.00 | 26.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.83 | 19.04 | 0.67 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
November | 31.83 | 18.92 | 25.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
December | 53.33 | 18.91 | 42.17 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 289.50 | 18.64 | 234.67 | 18.95 | 0.17 | 18.95 | 0.00 | 18.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.33 | 19.32 | 81.50 | 19.51 | 0.17 | 26.23 | 0.00 | 26.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.17 | 15.20 | 10.67 | 15.23 | 0.00 | 15.23 | 0.00 | 15.23 |
February | 16.67 | 15.76 | 4.00 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
March | 2.50 | 16.96 | 0.33 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
April | 0.17 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.58 | 2.00 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.50 | 2.17 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
October | 0.17 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
November | 7.33 | 15.72 | 0.17 | 15.70 | 0.00 | 15.70 | 0.00 | 15.70 |
December | 12.17 | 15.88 | 1.33 | 15.96 | 0.00 | 15.96 | 0.00 | 15.96 |
Annual Sum or Average | 67.17 | 15.59 | 16.50 | 15.67 | 4.83 | 16.32 | 4.50 | 16.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 28.17 | 17.11 | 10.67 | 17.24 | 2.50 | 27.58 | 2.17 | 27.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 267.83 | 15.36 | 242.50 | 15.37 | 0.00 | 15.37 | 0.00 | 15.37 |
February | 159.50 | 15.40 | 149.33 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
March | 111.67 | 15.03 | 109.00 | 15.02 | 0.00 | 15.02 | 0.00 | 15.02 |
April | 42.17 | 16.97 | 42.17 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
May | 13.00 | 19.52 | 13.00 | 19.52 | 0.83 | 19.76 | 0.83 | 19.99 |
June | 0.17 | 20.40 | 0.17 | 20.40 | 0.33 | 23.87 | 0.33 | 25.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.70 | 2.33 | 27.70 |
August | 4.00 | 18.78 | 4.00 | 18.78 | 1.50 | 20.21 | 1.33 | 21.16 |
September | 32.00 | 18.58 | 32.00 | 18.58 | 0.17 | 18.60 | 0.17 | 18.62 |
October | 72.83 | 16.04 | 72.67 | 16.04 | 0.00 | 16.04 | 0.00 | 16.04 |
November | 198.83 | 15.29 | 192.33 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
December | 275.33 | 15.33 | 256.00 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
Annual Sum or Average | 1177.33 | 15.56 | 1113.17 | 15.57 | 5.17 | 15.59 | 5.00 | 15.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 0.00 | 15.02 |
Maximum of Months | 275.33 | 20.40 | 256.00 | 20.40 | 2.33 | 27.70 | 2.33 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.00 | 15.11 | 11.83 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
February | 19.33 | 15.34 | 5.00 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
March | 2.67 | 16.83 | 0.33 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.45 | 0.33 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.17 | 27.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.00 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
November | 7.17 | 15.74 | 0.17 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
December | 12.33 | 15.81 | 1.50 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
Annual Sum or Average | 71.67 | 15.43 | 18.83 | 15.42 | 2.33 | 15.72 | 0.50 | 15.78 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.00 | 16.98 | 11.83 | 17.11 | 1.00 | 27.54 | 0.33 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.67 | 17.00 | 34.00 | 17.37 | 0.00 | 17.37 | 0.00 | 17.37 |
February | 29.67 | 17.42 | 18.67 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
March | 8.17 | 18.93 | 6.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
April | 0.50 | 18.57 | 0.33 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.28 | 0.00 | 26.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.34 | 0.00 | 26.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.33 | 19.09 | 1.83 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
November | 28.17 | 18.00 | 18.50 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
December | 37.50 | 17.88 | 23.67 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
Annual Sum or Average | 159.00 | 17.60 | 103.00 | 18.04 | 2.17 | 18.11 | 0.00 | 18.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 52.67 | 19.09 | 34.00 | 19.36 | 1.50 | 26.34 | 0.00 | 26.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.17 | 15.07 | 11.00 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
February | 11.33 | 15.15 | 1.50 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
March | 1.50 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
April | 0.17 | 17.10 | 0.00 | 17.10 | 0.17 | 22.21 | 0.17 | 23.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.96 | 3.00 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.20 | 1.50 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.70 | 3.67 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.40 | 0.67 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.51 | 0.67 | 27.51 |
October | 0.50 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
November | 12.17 | 15.38 | 2.17 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
December | 16.50 | 15.38 | 3.33 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
Annual Sum or Average | 73.33 | 15.25 | 18.00 | 15.20 | 11.00 | 16.54 | 9.67 | 17.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 0.00 | 15.04 |
Maximum of Months | 31.17 | 17.10 | 11.00 | 17.10 | 4.17 | 27.96 | 3.67 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.33 | 15.17 | 7.33 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
February | 7.33 | 15.40 | 1.50 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
March | 1.17 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.68 | 1.17 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.82 | 3.83 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.77 | 2.50 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.04 | 3.33 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.93 | 2.00 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.45 | 0.50 | 27.45 |
October | 0.33 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
November | 7.67 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
December | 14.17 | 15.50 | 1.67 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
Annual Sum or Average | 54.00 | 15.40 | 10.50 | 15.35 | 13.50 | 17.52 | 13.33 | 19.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 0.00 | 15.14 |
Maximum of Months | 23.33 | 16.97 | 7.33 | 16.97 | 3.83 | 28.04 | 3.83 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.67 | 15.07 | 11.83 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
February | 12.83 | 15.13 | 3.00 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
March | 1.50 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.71 | 0.17 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.70 | 1.00 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.81 | 1.17 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.54 | 1.17 | 27.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.83 | 0.50 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.50 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
November | 11.83 | 15.39 | 2.17 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
December | 16.33 | 15.38 | 3.33 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
Annual Sum or Average | 74.67 | 15.24 | 20.33 | 15.19 | 12.50 | 16.64 | 4.00 | 17.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 31.67 | 16.85 | 11.83 | 16.85 | 4.00 | 27.83 | 1.17 | 27.82 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.99 | 357.17 | 20.82 | 357.17 | 20.75 |
February | 454.00 | 21.51 | 200.50 | 21.25 | 200.50 | 21.12 |
March | 514.00 | 22.42 | 65.33 | 22.26 | 65.33 | 22.14 |
April | 451.83 | 23.56 | 1.00 | 23.55 | 1.00 | 23.55 |
May | 183.67 | 24.01 | 21.33 | 24.21 | 0.00 | 24.21 |
June | 0.00 | 0.00 | 184.67 | 24.95 | 0.00 | 24.95 |
July | 0.00 | 0.00 | 350.17 | 24.64 | 0.00 | 24.64 |
August | 28.83 | 24.00 | 227.17 | 24.68 | 0.00 | 24.68 |
September | 212.83 | 23.79 | 40.83 | 24.10 | 0.00 | 24.10 |
October | 502.00 | 23.14 | 6.33 | 23.11 | 6.33 | 23.08 |
November | 489.00 | 21.56 | 234.67 | 21.34 | 234.67 | 21.23 |
December | 497.00 | 21.06 | 394.17 | 20.95 | 394.17 | 20.90 |
Annual Sum or Average | 3835.17 | 22.23 | 2083.33 | 22.28 | 1259.17 | 22.01 |
Minimum of Months | 0.00 | 0.00 | 1.00 | 20.82 | 0.00 | 20.75 |
Maximum of Months | 514.00 | 24.01 | 394.17 | 24.95 | 394.17 | 24.95 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.31 | 491.83 | 20.30 | 491.83 | 20.29 |
February | 454.00 | 20.56 | 371.50 | 20.48 | 371.50 | 20.45 |
March | 514.00 | 21.12 | 285.67 | 20.98 | 285.67 | 20.91 |
April | 483.33 | 22.59 | 52.67 | 22.42 | 52.67 | 22.28 |
May | 394.33 | 23.76 | 1.17 | 23.77 | 0.00 | 23.77 |
June | 36.83 | 23.83 | 112.00 | 24.54 | 0.00 | 24.54 |
July | 0.83 | 23.67 | 242.33 | 24.53 | 0.00 | 24.53 |
August | 95.50 | 23.70 | 113.50 | 24.26 | 0.00 | 24.26 |
September | 431.67 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
October | 502.00 | 21.43 | 154.00 | 21.25 | 154.00 | 21.14 |
November | 489.00 | 20.50 | 458.17 | 20.47 | 458.17 | 20.46 |
December | 497.00 | 20.36 | 496.50 | 20.36 | 496.50 | 20.36 |
Annual Sum or Average | 4400.50 | 21.52 | 2779.33 | 21.37 | 2310.33 | 21.15 |
Minimum of Months | 0.83 | 20.31 | 0.00 | 20.30 | 0.00 | 20.29 |
Maximum of Months | 514.00 | 23.83 | 496.50 | 24.54 | 496.50 | 24.54 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.97 | 502.00 | 19.97 | 502.00 | 19.97 |
February | 454.00 | 20.10 | 437.67 | 20.08 | 437.67 | 20.08 |
March | 514.00 | 20.59 | 425.17 | 20.51 | 425.17 | 20.48 |
April | 485.00 | 21.87 | 153.67 | 21.54 | 153.67 | 21.33 |
May | 431.83 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
June | 102.67 | 23.71 | 77.00 | 24.07 | 0.00 | 24.07 |
July | 30.33 | 23.41 | 204.83 | 24.33 | 0.00 | 24.33 |
August | 183.83 | 23.31 | 72.50 | 23.67 | 0.00 | 23.67 |
September | 481.50 | 22.28 | 46.50 | 22.14 | 46.50 | 22.02 |
October | 502.00 | 20.65 | 341.67 | 20.50 | 341.67 | 20.44 |
November | 489.00 | 20.01 | 489.00 | 20.01 | 489.00 | 20.01 |
December | 497.00 | 19.96 | 497.00 | 19.96 | 497.00 | 19.96 |
Annual Sum or Average | 4673.17 | 21.12 | 3247.00 | 20.91 | 2892.67 | 20.70 |
Minimum of Months | 30.33 | 19.96 | 0.00 | 19.96 | 0.00 | 19.96 |
Maximum of Months | 514.00 | 23.71 | 502.00 | 24.33 | 502.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.56 | 502.00 | 19.56 | 502.00 | 19.56 |
February | 454.00 | 19.67 | 454.00 | 19.67 | 454.00 | 19.67 |
March | 514.00 | 20.05 | 507.00 | 20.04 | 507.00 | 20.04 |
April | 485.00 | 21.01 | 266.67 | 20.71 | 266.67 | 20.56 |
May | 424.67 | 23.14 | 6.00 | 23.11 | 6.00 | 23.08 |
June | 61.83 | 23.56 | 145.33 | 24.23 | 0.00 | 24.23 |
July | 41.00 | 23.38 | 295.67 | 24.30 | 0.00 | 24.30 |
August | 242.17 | 22.90 | 80.50 | 23.22 | 4.83 | 23.18 |
September | 484.33 | 21.42 | 144.50 | 21.20 | 144.50 | 21.06 |
October | 502.00 | 20.08 | 457.33 | 20.03 | 457.33 | 20.01 |
November | 489.00 | 19.58 | 489.00 | 19.58 | 489.00 | 19.58 |
December | 497.00 | 19.52 | 497.00 | 19.52 | 497.00 | 19.52 |
Annual Sum or Average | 4697.00 | 20.60 | 3845.00 | 20.52 | 3328.33 | 20.31 |
Minimum of Months | 41.00 | 19.52 | 6.00 | 19.52 | 0.00 | 19.52 |
Maximum of Months | 514.00 | 23.56 | 507.00 | 24.30 | 507.00 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 502.00 | 19.65 | 502.00 | 19.65 |
February | 454.00 | 19.78 | 453.00 | 19.77 | 453.00 | 19.77 |
March | 514.00 | 20.35 | 440.17 | 20.24 | 440.17 | 20.20 |
April | 444.50 | 21.62 | 195.17 | 21.25 | 191.33 | 21.03 |
May | 221.83 | 23.20 | 102.50 | 23.63 | 7.83 | 23.69 |
June | 62.83 | 23.59 | 277.33 | 24.24 | 3.33 | 24.27 |
July | 58.50 | 24.15 | 372.67 | 24.45 | 14.83 | 24.54 |
August | 160.83 | 22.98 | 209.83 | 23.71 | 2.50 | 23.69 |
September | 430.50 | 21.62 | 109.00 | 21.45 | 100.17 | 21.27 |
October | 502.00 | 20.22 | 417.50 | 20.12 | 417.50 | 20.08 |
November | 489.00 | 19.67 | 489.00 | 19.67 | 489.00 | 19.67 |
December | 497.00 | 19.62 | 497.00 | 19.62 | 497.00 | 19.62 |
Annual Sum or Average | 4337.00 | 20.63 | 4065.17 | 20.78 | 3118.67 | 20.54 |
Minimum of Months | 58.50 | 19.62 | 102.50 | 19.62 | 2.50 | 19.62 |
Maximum of Months | 514.00 | 24.15 | 502.00 | 24.45 | 502.00 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.68 | 502.00 | 19.68 | 502.00 | 19.68 |
February | 454.00 | 20.03 | 418.00 | 19.94 | 418.00 | 19.91 |
March | 487.17 | 20.74 | 358.00 | 20.46 | 358.00 | 20.35 |
April | 356.50 | 21.60 | 198.00 | 21.50 | 153.00 | 21.24 |
May | 268.67 | 22.79 | 107.67 | 23.26 | 15.00 | 23.27 |
June | 123.17 | 23.41 | 234.83 | 24.07 | 8.50 | 24.14 |
July | 110.17 | 23.53 | 319.67 | 24.26 | 13.17 | 24.34 |
August | 198.67 | 22.90 | 223.00 | 23.68 | 10.17 | 23.69 |
September | 382.33 | 21.63 | 144.33 | 21.70 | 95.83 | 21.50 |
October | 488.33 | 20.44 | 378.67 | 20.29 | 376.17 | 20.22 |
November | 489.00 | 19.73 | 484.50 | 19.71 | 484.50 | 19.71 |
December | 497.00 | 19.63 | 497.00 | 19.63 | 497.00 | 19.63 |
Annual Sum or Average | 4357.00 | 20.79 | 3865.67 | 20.90 | 2931.33 | 20.65 |
Minimum of Months | 110.17 | 19.63 | 107.67 | 19.63 | 8.50 | 19.63 |
Maximum of Months | 502.00 | 23.53 | 502.00 | 24.26 | 502.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 502.00 | 19.65 | 502.00 | 19.65 |
February | 454.00 | 19.77 | 452.33 | 19.76 | 452.33 | 19.76 |
March | 514.00 | 20.20 | 475.33 | 20.14 | 475.33 | 20.12 |
April | 425.33 | 21.23 | 223.00 | 20.96 | 210.17 | 20.78 |
May | 335.17 | 22.69 | 53.33 | 22.87 | 11.00 | 22.81 |
June | 124.50 | 23.28 | 195.00 | 24.05 | 4.33 | 24.09 |
July | 107.17 | 23.21 | 296.50 | 24.12 | 4.17 | 24.15 |
August | 254.83 | 22.74 | 159.00 | 23.33 | 6.83 | 23.30 |
September | 456.67 | 21.42 | 135.83 | 21.25 | 129.67 | 21.10 |
October | 502.00 | 20.12 | 443.50 | 20.06 | 443.50 | 20.03 |
November | 489.00 | 19.67 | 489.00 | 19.67 | 489.00 | 19.67 |
December | 497.00 | 19.62 | 497.00 | 19.62 | 497.00 | 19.62 |
Annual Sum or Average | 4661.67 | 20.66 | 3921.83 | 20.67 | 3225.33 | 20.45 |
Minimum of Months | 107.17 | 19.62 | 53.33 | 19.62 | 4.17 | 19.62 |
Maximum of Months | 514.00 | 23.28 | 502.00 | 24.12 | 502.00 | 24.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.55 | 502.00 | 19.55 | 502.00 | 19.55 |
February | 454.00 | 19.64 | 454.00 | 19.64 | 454.00 | 19.64 |
March | 514.00 | 20.15 | 514.00 | 20.15 | 514.00 | 20.15 |
April | 485.00 | 20.83 | 319.83 | 20.67 | 319.83 | 20.60 |
May | 508.00 | 22.86 | 0.00 | 22.86 | 0.00 | 22.86 |
June | 158.17 | 23.66 | 58.33 | 23.86 | 0.00 | 23.86 |
July | 40.67 | 23.45 | 215.33 | 24.29 | 0.00 | 24.29 |
August | 222.00 | 23.29 | 57.33 | 23.55 | 0.00 | 23.55 |
September | 485.00 | 22.13 | 53.50 | 21.99 | 53.50 | 21.87 |
October | 502.00 | 20.58 | 395.50 | 20.49 | 395.50 | 20.46 |
November | 489.00 | 19.80 | 489.00 | 19.80 | 489.00 | 19.80 |
December | 497.00 | 19.64 | 497.00 | 19.64 | 497.00 | 19.64 |
Annual Sum or Average | 4856.83 | 20.83 | 3555.83 | 20.62 | 3224.83 | 20.43 |
Minimum of Months | 40.67 | 19.55 | 0.00 | 19.55 | 0.00 | 19.55 |
Maximum of Months | 514.00 | 23.66 | 514.00 | 24.29 | 514.00 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 502.00 | 19.74 | 502.00 | 19.74 |
February | 454.00 | 19.86 | 454.00 | 19.86 | 454.00 | 19.86 |
March | 514.00 | 20.44 | 470.17 | 20.38 | 470.17 | 20.36 |
April | 468.17 | 21.81 | 183.83 | 21.47 | 180.50 | 21.27 |
May | 244.00 | 23.43 | 55.50 | 23.74 | 0.83 | 23.75 |
June | 65.83 | 23.56 | 224.17 | 24.26 | 0.00 | 24.26 |
July | 23.00 | 24.63 | 389.17 | 24.55 | 8.17 | 24.60 |
August | 91.00 | 23.48 | 251.50 | 24.17 | 0.00 | 24.17 |
September | 384.00 | 22.49 | 49.67 | 22.57 | 25.67 | 22.46 |
October | 502.00 | 20.84 | 308.17 | 20.66 | 308.17 | 20.59 |
November | 489.00 | 19.85 | 489.00 | 19.85 | 489.00 | 19.85 |
December | 497.00 | 19.74 | 497.00 | 19.74 | 497.00 | 19.74 |
Annual Sum or Average | 4234.00 | 20.84 | 3874.17 | 20.97 | 2935.50 | 20.71 |
Minimum of Months | 23.00 | 19.74 | 49.67 | 19.74 | 0.00 | 19.74 |
Maximum of Months | 514.00 | 24.63 | 502.00 | 24.55 | 502.00 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 17.10 | 502.00 | 17.10 | 502.00 | 17.10 |
February | 454.00 | 18.21 | 448.33 | 18.19 | 448.33 | 18.19 |
March | 514.00 | 19.26 | 456.33 | 19.12 | 456.33 | 19.07 |
April | 432.00 | 21.14 | 169.17 | 20.84 | 155.50 | 20.57 |
May | 373.33 | 22.34 | 45.83 | 22.53 | 13.50 | 22.44 |
June | 189.50 | 22.75 | 131.50 | 23.52 | 0.33 | 23.52 |
July | 105.83 | 22.67 | 295.50 | 24.09 | 6.33 | 24.13 |
August | 209.67 | 22.53 | 208.83 | 23.54 | 7.50 | 23.55 |
September | 393.83 | 21.66 | 99.67 | 21.77 | 54.33 | 21.54 |
October | 499.00 | 20.16 | 330.17 | 19.86 | 330.17 | 19.73 |
November | 489.00 | 17.61 | 489.00 | 17.61 | 489.00 | 17.61 |
December | 497.00 | 16.78 | 497.00 | 16.78 | 497.00 | 16.78 |
Annual Sum or Average | 4659.17 | 19.57 | 3673.33 | 19.48 | 2960.33 | 19.11 |
Minimum of Months | 105.83 | 16.78 | 45.83 | 16.78 | 0.33 | 16.78 |
Maximum of Months | 514.00 | 22.75 | 502.00 | 24.09 | 502.00 | 24.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 502.00 | 19.74 | 502.00 | 19.74 |
February | 454.00 | 19.83 | 454.00 | 19.83 | 454.00 | 19.83 |
March | 514.00 | 20.26 | 498.00 | 20.25 | 498.00 | 20.24 |
April | 458.67 | 21.55 | 196.83 | 21.24 | 195.50 | 21.07 |
May | 411.83 | 22.98 | 7.33 | 23.02 | 0.83 | 23.02 |
June | 126.33 | 23.43 | 151.00 | 24.05 | 0.17 | 24.06 |
July | 59.33 | 23.33 | 286.17 | 24.28 | 0.33 | 24.29 |
August | 154.00 | 23.22 | 164.33 | 23.87 | 0.00 | 23.87 |
September | 446.17 | 22.27 | 47.00 | 22.17 | 42.17 | 22.05 |
October | 502.00 | 20.62 | 383.00 | 20.52 | 383.00 | 20.48 |
November | 489.00 | 19.85 | 489.00 | 19.85 | 489.00 | 19.85 |
December | 497.00 | 19.74 | 497.00 | 19.74 | 497.00 | 19.74 |
Annual Sum or Average | 4614.33 | 20.89 | 3675.67 | 20.83 | 3062.00 | 20.60 |
Minimum of Months | 59.33 | 19.74 | 7.33 | 19.74 | 0.00 | 19.74 |
Maximum of Months | 514.00 | 23.43 | 502.00 | 24.28 | 502.00 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.73 | 502.00 | 19.73 | 502.00 | 19.73 |
February | 454.00 | 19.85 | 454.00 | 19.85 | 454.00 | 19.85 |
March | 514.00 | 20.33 | 480.83 | 20.30 | 480.83 | 20.29 |
April | 485.00 | 21.64 | 179.83 | 21.30 | 179.83 | 21.10 |
May | 385.17 | 23.65 | 1.00 | 23.65 | 0.00 | 23.65 |
June | 16.33 | 23.89 | 175.67 | 24.57 | 0.00 | 24.57 |
July | 3.67 | 23.61 | 327.50 | 24.51 | 0.00 | 24.51 |
August | 141.67 | 23.32 | 101.33 | 23.80 | 0.00 | 23.80 |
September | 479.00 | 22.23 | 57.33 | 22.06 | 57.33 | 21.92 |
October | 502.00 | 20.49 | 384.67 | 20.38 | 384.67 | 20.33 |
November | 489.00 | 19.76 | 489.00 | 19.76 | 489.00 | 19.76 |
December | 497.00 | 19.71 | 497.00 | 19.71 | 497.00 | 19.71 |
Annual Sum or Average | 4468.83 | 20.84 | 3650.17 | 20.79 | 3044.67 | 20.56 |
Minimum of Months | 3.67 | 19.71 | 1.00 | 19.71 | 0.00 | 19.71 |
Maximum of Months | 514.00 | 23.89 | 502.00 | 24.57 | 502.00 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.57 | 427.00 | 19.57 | 427.00 | 19.57 |
February | 385.00 | 19.77 | 381.83 | 19.76 | 381.83 | 19.76 |
March | 433.00 | 20.55 | 349.33 | 20.42 | 349.33 | 20.37 |
April | 367.83 | 21.91 | 113.83 | 21.65 | 105.67 | 21.42 |
May | 187.17 | 23.53 | 101.00 | 23.99 | 7.50 | 24.07 |
June | 34.83 | 23.95 | 226.67 | 24.47 | 3.50 | 24.51 |
July | 25.83 | 25.25 | 324.67 | 24.70 | 13.50 | 24.78 |
August | 110.00 | 23.26 | 189.83 | 24.02 | 0.50 | 24.03 |
September | 350.83 | 22.09 | 57.67 | 22.14 | 38.17 | 22.00 |
October | 426.17 | 20.53 | 306.50 | 20.38 | 306.50 | 20.32 |
November | 417.00 | 19.58 | 417.00 | 19.58 | 417.00 | 19.58 |
December | 422.00 | 19.53 | 422.00 | 19.53 | 422.00 | 19.53 |
Annual Sum or Average | 3586.67 | 20.71 | 3317.33 | 20.89 | 2472.50 | 20.63 |
Minimum of Months | 25.83 | 19.53 | 57.67 | 19.53 | 0.50 | 19.53 |
Maximum of Months | 433.00 | 25.25 | 427.00 | 24.70 | 427.00 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.83 | 498.33 | 19.82 | 498.33 | 19.82 |
February | 454.00 | 20.34 | 399.83 | 20.21 | 399.83 | 20.17 |
March | 470.17 | 21.01 | 314.83 | 20.75 | 312.33 | 20.63 |
April | 336.83 | 22.08 | 145.83 | 22.08 | 93.33 | 21.83 |
May | 237.33 | 23.29 | 104.83 | 23.76 | 6.83 | 23.83 |
June | 76.17 | 23.78 | 258.67 | 24.31 | 7.50 | 24.37 |
July | 55.83 | 24.21 | 351.67 | 24.49 | 13.00 | 24.57 |
August | 135.17 | 23.32 | 248.00 | 24.07 | 6.50 | 24.12 |
September | 345.83 | 22.21 | 98.50 | 22.48 | 31.50 | 22.36 |
October | 482.67 | 20.93 | 282.50 | 20.71 | 279.17 | 20.60 |
November | 489.00 | 19.93 | 478.17 | 19.90 | 478.17 | 19.90 |
December | 497.00 | 19.77 | 497.00 | 19.77 | 497.00 | 19.77 |
Annual Sum or Average | 4082.00 | 20.99 | 3678.17 | 21.17 | 2623.50 | 20.90 |
Minimum of Months | 55.83 | 19.77 | 98.50 | 19.77 | 6.50 | 19.77 |
Maximum of Months | 502.00 | 24.21 | 498.33 | 24.49 | 498.33 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.78 | 502.00 | 19.78 | 502.00 | 19.78 |
February | 454.00 | 19.91 | 450.67 | 19.90 | 450.67 | 19.90 |
March | 514.00 | 20.47 | 442.67 | 20.39 | 442.67 | 20.36 |
April | 415.83 | 21.74 | 157.83 | 21.49 | 143.17 | 21.28 |
May | 298.33 | 23.19 | 45.00 | 23.42 | 0.50 | 23.43 |
June | 67.67 | 23.61 | 213.83 | 24.35 | 3.67 | 24.38 |
July | 44.50 | 23.55 | 331.67 | 24.37 | 3.17 | 24.39 |
August | 167.00 | 23.09 | 179.83 | 23.78 | 1.67 | 23.80 |
September | 444.00 | 22.05 | 64.50 | 21.96 | 53.67 | 21.84 |
October | 502.00 | 20.50 | 384.00 | 20.39 | 384.00 | 20.35 |
November | 489.00 | 19.79 | 489.00 | 19.79 | 489.00 | 19.79 |
December | 497.00 | 19.75 | 497.00 | 19.75 | 497.00 | 19.75 |
Annual Sum or Average | 4395.33 | 20.82 | 3758.00 | 20.88 | 2971.17 | 20.65 |
Minimum of Months | 44.50 | 19.75 | 45.00 | 19.75 | 0.50 | 19.75 |
Maximum of Months | 514.00 | 23.61 | 502.00 | 24.37 | 502.00 | 24.39 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.99452 | 15.50247 | -0.6526 | 15.34658 |
February | 454.00000 | 21.50887 | 16.68511 | -0.5067 | 11.68824 |
March | 514.00000 | 22.42265 | 17.62128 | -0.2756 | 7.51670 |
April | 485.00000 | 23.67576 | 16.77690 | 0.06172 | 5.82957 |
May | 508.00000 | 24.27673 | 21.16278 | -0.5831 | 12.39953 |
June | 496.00000 | 24.37783 | 32.96366 | -0.4301 | 9.35387 |
July | 497.00000 | 24.45310 | 41.13986 | -0.3484 | 8.13046 |
August | 514.00000 | 24.36526 | 36.32024 | -0.4197 | 9.21559 |
September | 485.00000 | 24.15143 | 27.65906 | -0.6242 | 13.95985 |
October | 502.00000 | 23.13970 | 22.75668 | -0.0564 | 5.95168 |
November | 489.00000 | 21.56291 | 15.46388 | -0.5058 | 11.17310 |
December | 497.00000 | 21.06007 | 12.90650 | -0.6476 | 14.38136 |
Annual Sum or Average | 5943.00000 | 23.01092 | 23.15027 | -0.4153 | 10.39659 |
Minimum of Months | 454.00000 | 20.99452 | 12.90650 | -0.6526 | 5.82957 |
Maximum of Months | 514.00000 | 24.45310 | 41.13986 | 0.06172 | 15.34658 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.30536 | 18.55148 | -0.8142 | 20.49249 |
February | 454.00000 | 20.56430 | 20.07840 | -0.7215 | 17.28487 |
March | 514.00000 | 21.12363 | 20.75606 | -0.5560 | 12.13988 |
April | 485.00000 | 22.59431 | 18.75010 | -0.1762 | 7.15746 |
May | 508.00000 | 23.90276 | 22.37054 | -0.7162 | 16.27217 |
June | 496.00000 | 24.20334 | 33.91743 | -0.5030 | 10.58862 |
July | 497.00000 | 24.25513 | 42.24675 | -0.4287 | 9.17272 |
August | 514.00000 | 24.11195 | 37.71025 | -0.5257 | 11.28737 |
September | 485.00000 | 23.18231 | 30.78817 | -0.9505 | 25.69399 |
October | 502.00000 | 21.43282 | 26.71776 | -0.4363 | 9.93182 |
November | 489.00000 | 20.49968 | 19.22147 | -0.7527 | 17.84845 |
December | 497.00000 | 20.36078 | 15.28332 | -0.8216 | 20.23076 |
Annual Sum or Average | 5943.00000 | 22.22571 | 25.59272 | -0.6159 | 14.79969 |
Minimum of Months | 454.00000 | 20.30536 | 15.28332 | -0.9505 | 7.15746 |
Maximum of Months | 514.00000 | 24.25513 | 42.24675 | -0.1762 | 25.69399 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.96978 | 19.40781 | -0.9334 | 25.50157 |
February | 454.00000 | 20.10397 | 21.34431 | -0.8651 | 22.97528 |
March | 514.00000 | 20.58980 | 21.54617 | -0.7146 | 16.99905 |
April | 485.00000 | 21.87209 | 19.42606 | -0.3585 | 9.92424 |
May | 508.00000 | 23.58296 | 22.95568 | -0.8295 | 20.55238 |
June | 496.00000 | 24.09728 | 34.00229 | -0.5397 | 11.41654 |
July | 497.00000 | 24.14466 | 42.37484 | -0.4688 | 9.91550 |
August | 514.00000 | 23.85695 | 38.34316 | -0.6215 | 14.07560 |
September | 485.00000 | 22.29150 | 32.57724 | -1.2613 | 39.48191 |
October | 502.00000 | 20.64984 | 28.19297 | -0.6512 | 15.39111 |
November | 489.00000 | 20.01392 | 20.41844 | -0.9082 | 24.37629 |
December | 497.00000 | 19.96073 | 16.08510 | -0.9572 | 26.19641 |
Annual Sum or Average | 5943.00000 | 21.77735 | 26.44396 | -0.7576 | 19.66416 |
Minimum of Months | 454.00000 | 19.96073 | 16.08510 | -1.2613 | 9.91550 |
Maximum of Months | 514.00000 | 24.14466 | 42.37484 | -0.3585 | 39.48191 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.55645 | 19.73617 | -1.1448 | 34.38219 |
February | 454.00000 | 19.67185 | 21.96277 | -1.0730 | 31.48360 |
March | 514.00000 | 20.05043 | 22.42820 | -0.9222 | 24.95947 |
April | 485.00000 | 21.01247 | 20.43482 | -0.5806 | 15.06218 |
May | 508.00000 | 23.29669 | 23.63977 | -0.9174 | 24.35479 |
June | 496.00000 | 24.14285 | 33.99641 | -0.4894 | 10.49643 |
July | 497.00000 | 24.19391 | 42.35308 | -0.4242 | 9.32951 |
August | 514.00000 | 23.54308 | 39.48914 | -0.7192 | 17.94413 |
September | 485.00000 | 21.42414 | 34.72441 | -1.5681 | 54.42695 |
October | 502.00000 | 20.08011 | 29.18751 | -0.8508 | 22.32503 |
November | 489.00000 | 19.58500 | 20.93074 | -1.1228 | 33.45667 |
December | 497.00000 | 19.51771 | 16.23405 | -1.1808 | 35.86596 |
Annual Sum or Average | 5943.00000 | 21.35768 | 27.14667 | -0.9137 | 26.06700 |
Minimum of Months | 454.00000 | 19.51771 | 16.23405 | -1.5681 | 9.32951 |
Maximum of Months | 514.00000 | 24.19391 | 42.35308 | -0.4242 | 54.42695 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65372 | 19.83617 | -1.1261 | 33.51151 |
February | 454.00000 | 19.77623 | 21.90716 | -1.0325 | 29.79034 |
March | 514.00000 | 20.34774 | 22.02435 | -0.7992 | 20.85906 |
April | 485.00000 | 21.84075 | 19.28177 | -0.3446 | 11.75606 |
May | 508.00000 | 23.76580 | 22.11003 | -0.6459 | 16.80258 |
June | 496.00000 | 24.18225 | 33.56980 | -0.3775 | 9.15126 |
July | 497.00000 | 24.29873 | 41.67143 | -0.2853 | 8.40238 |
August | 514.00000 | 23.81062 | 38.30582 | -0.5441 | 13.42847 |
September | 485.00000 | 21.94667 | 33.64286 | -1.3538 | 45.24305 |
October | 502.00000 | 20.22119 | 28.92383 | -0.7959 | 20.59001 |
November | 489.00000 | 19.66583 | 20.97247 | -1.1060 | 32.68976 |
December | 497.00000 | 19.61620 | 16.44343 | -1.1647 | 35.09268 |
Annual Sum or Average | 5943.00000 | 21.61192 | 26.60654 | -0.7950 | 22.98994 |
Minimum of Months | 454.00000 | 19.61620 | 16.44343 | -1.3538 | 8.40238 |
Maximum of Months | 514.00000 | 24.29873 | 41.67143 | -0.2853 | 45.24305 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.67724 | 19.36424 | -1.1017 | 32.55749 |
February | 454.00000 | 20.02887 | 21.08052 | -0.9330 | 26.31632 |
March | 514.00000 | 20.90632 | 20.72789 | -0.6409 | 18.31412 |
April | 485.00000 | 22.31516 | 17.88538 | -0.2051 | 11.64535 |
May | 508.00000 | 23.48711 | 22.19997 | -0.7551 | 21.59080 |
June | 496.00000 | 24.03426 | 33.69439 | -0.4485 | 11.14244 |
July | 497.00000 | 24.12507 | 41.95835 | -0.3628 | 10.04701 |
August | 514.00000 | 23.72264 | 38.06520 | -0.5565 | 15.19159 |
September | 485.00000 | 22.21946 | 32.31180 | -1.2402 | 41.29088 |
October | 502.00000 | 20.54020 | 27.78296 | -0.7002 | 18.53272 |
November | 489.00000 | 19.72514 | 20.41629 | -1.0614 | 30.99556 |
December | 497.00000 | 19.63111 | 16.01450 | -1.1535 | 34.61648 |
Annual Sum or Average | 5943.00000 | 21.71726 | 26.01208 | -0.7611 | 22.60479 |
Minimum of Months | 454.00000 | 19.63111 | 16.01450 | -1.2402 | 10.04701 |
Maximum of Months | 514.00000 | 24.12507 | 41.95835 | -0.2051 | 41.29088 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65352 | 19.74082 | -1.1294 | 33.63244 |
February | 454.00000 | 19.76699 | 21.78451 | -1.0493 | 30.42943 |
March | 514.00000 | 20.19767 | 22.05233 | -0.8702 | 23.18630 |
April | 485.00000 | 21.59456 | 19.42109 | -0.4075 | 13.42094 |
May | 508.00000 | 23.22858 | 23.38977 | -0.8847 | 24.88365 |
June | 496.00000 | 24.02295 | 34.37047 | -0.4718 | 11.48385 |
July | 497.00000 | 24.04477 | 42.76999 | -0.4247 | 10.45590 |
August | 514.00000 | 23.47155 | 39.45719 | -0.6888 | 17.99065 |
September | 485.00000 | 21.59184 | 34.15051 | -1.4876 | 51.23157 |
October | 502.00000 | 20.12185 | 28.96620 | -0.8363 | 21.85567 |
November | 489.00000 | 19.66868 | 20.86230 | -1.1058 | 32.67918 |
December | 497.00000 | 19.61668 | 16.38235 | -1.1655 | 35.12067 |
Annual Sum or Average | 5943.00000 | 21.43127 | 27.00140 | -0.8747 | 25.43496 |
Minimum of Months | 454.00000 | 19.61668 | 16.38235 | -1.4876 | 10.45590 |
Maximum of Months | 514.00000 | 24.04477 | 42.76999 | -0.4075 | 51.23157 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.54946 | 16.84602 | -1.1417 | 33.97222 |
February | 454.00000 | 19.64200 | 18.65218 | -1.0943 | 32.07283 |
March | 514.00000 | 20.15093 | 20.24496 | -0.9240 | 24.41615 |
April | 485.00000 | 20.82619 | 20.51798 | -0.6433 | 15.10948 |
May | 508.00000 | 22.85980 | 24.87072 | -1.0967 | 31.23273 |
June | 496.00000 | 24.00317 | 35.03514 | -0.5862 | 12.56969 |
July | 497.00000 | 24.15132 | 42.98231 | -0.4708 | 9.97799 |
August | 514.00000 | 23.76928 | 39.22176 | -0.6558 | 15.11514 |
September | 485.00000 | 22.13256 | 32.66710 | -1.3060 | 41.49511 |
October | 502.00000 | 20.57658 | 26.74193 | -0.6924 | 16.25164 |
November | 489.00000 | 19.79757 | 17.51207 | -1.0407 | 29.45603 |
December | 497.00000 | 19.64052 | 14.13012 | -1.1272 | 33.14695 |
Annual Sum or Average | 5943.00000 | 21.44281 | 25.85730 | -0.8962 | 24.47983 |
Minimum of Months | 454.00000 | 19.54946 | 14.13012 | -1.3060 | 9.97799 |
Maximum of Months | 514.00000 | 24.15132 | 42.98231 | -0.4708 | 41.49511 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73935 | 17.05098 | -1.1093 | 32.49474 |
February | 454.00000 | 19.86097 | 18.91368 | -1.0347 | 29.41413 |
March | 514.00000 | 20.44383 | 20.37209 | -0.8012 | 19.99522 |
April | 485.00000 | 21.90672 | 19.57048 | -0.3468 | 10.60739 |
May | 508.00000 | 23.88290 | 22.42319 | -0.6568 | 16.00068 |
June | 496.00000 | 24.19212 | 34.00909 | -0.4257 | 9.60693 |
July | 497.00000 | 24.39741 | 41.77711 | -0.2865 | 7.89637 |
August | 514.00000 | 24.12311 | 37.67453 | -0.4512 | 10.31531 |
September | 485.00000 | 22.91454 | 31.36398 | -1.0149 | 30.03809 |
October | 502.00000 | 20.83807 | 26.73328 | -0.6110 | 14.38830 |
November | 489.00000 | 19.85031 | 17.86590 | -1.0326 | 29.10505 |
December | 497.00000 | 19.73792 | 14.48495 | -1.1163 | 32.66231 |
Annual Sum or Average | 5943.00000 | 21.84189 | 25.25052 | -0.7377 | 20.10187 |
Minimum of Months | 454.00000 | 19.73792 | 14.48495 | -1.1163 | 7.89637 |
Maximum of Months | 514.00000 | 24.39741 | 41.77711 | -0.2865 | 32.66231 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 17.09656 | 14.95052 | -1.6085 | 52.72037 |
February | 454.00000 | 18.20961 | 16.03464 | -1.3153 | 40.66184 |
March | 514.00000 | 19.25572 | 16.49353 | -0.9921 | 28.09478 |
April | 485.00000 | 21.53265 | 16.84152 | -0.3598 | 12.29431 |
May | 508.00000 | 22.92266 | 22.68177 | -0.9479 | 27.59377 |
June | 496.00000 | 23.70799 | 34.54047 | -0.5881 | 14.31941 |
July | 497.00000 | 23.99317 | 42.40092 | -0.4271 | 11.21356 |
August | 514.00000 | 23.61205 | 37.93552 | -0.5717 | 15.21229 |
September | 485.00000 | 22.24417 | 29.92603 | -1.1553 | 36.99428 |
October | 502.00000 | 20.18126 | 23.32515 | -0.7158 | 19.18049 |
November | 489.00000 | 17.60829 | 14.80826 | -1.4491 | 46.13010 |
December | 497.00000 | 16.78184 | 12.53294 | -1.6898 | 55.81524 |
Annual Sum or Average | 5943.00000 | 20.61685 | 23.61613 | -0.9821 | 29.90249 |
Minimum of Months | 454.00000 | 16.78184 | 12.53294 | -1.6898 | 11.21356 |
Maximum of Months | 514.00000 | 23.99317 | 42.40092 | -0.3598 | 55.81524 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73763 | 16.94500 | -1.1129 | 32.64207 |
February | 454.00000 | 19.82751 | 18.75034 | -1.0567 | 30.34703 |
March | 514.00000 | 20.26472 | 20.32324 | -0.8795 | 22.72456 |
April | 485.00000 | 21.69297 | 19.58698 | -0.3986 | 11.32579 |
May | 508.00000 | 23.22675 | 24.07401 | -0.9331 | 25.33934 |
June | 496.00000 | 24.06083 | 34.82324 | -0.5129 | 11.54482 |
July | 497.00000 | 24.17032 | 42.92739 | -0.4214 | 9.58017 |
August | 514.00000 | 23.92508 | 38.70674 | -0.5564 | 12.78564 |
September | 485.00000 | 22.43205 | 32.11019 | -1.1846 | 36.61021 |
October | 502.00000 | 20.61893 | 26.84478 | -0.6776 | 15.88464 |
November | 489.00000 | 19.85171 | 17.70673 | -1.0331 | 29.12237 |
December | 497.00000 | 19.73758 | 14.41848 | -1.1173 | 32.70072 |
Annual Sum or Average | 5943.00000 | 21.64529 | 25.67240 | -0.8216 | 22.46209 |
Minimum of Months | 454.00000 | 19.73758 | 14.41848 | -1.1846 | 9.58017 |
Maximum of Months | 514.00000 | 24.17032 | 42.92739 | -0.3986 | 36.61021 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73259 | 19.64507 | -1.0511 | 30.26623 |
February | 454.00000 | 19.85339 | 21.55119 | -0.9776 | 27.38188 |
March | 514.00000 | 20.32961 | 22.29329 | -0.8090 | 20.17974 |
April | 485.00000 | 21.64299 | 20.26945 | -0.4089 | 11.03244 |
May | 508.00000 | 23.76908 | 23.02313 | -0.7592 | 17.93032 |
June | 496.00000 | 24.25740 | 33.83759 | -0.4495 | 9.57479 |
July | 497.00000 | 24.34177 | 42.14139 | -0.3733 | 8.37042 |
August | 514.00000 | 23.93755 | 38.69403 | -0.5842 | 13.19344 |
September | 485.00000 | 22.25548 | 33.45077 | -1.2656 | 39.91694 |
October | 502.00000 | 20.48914 | 28.60900 | -0.7040 | 17.01360 |
November | 489.00000 | 19.75612 | 20.77819 | -1.0216 | 29.02307 |
December | 497.00000 | 19.71362 | 16.32950 | -1.0786 | 31.24232 |
Annual Sum or Average | 5943.00000 | 21.69131 | 26.77256 | -0.7880 | 21.16231 |
Minimum of Months | 454.00000 | 19.71362 | 16.32950 | -1.2656 | 8.37042 |
Maximum of Months | 514.00000 | 24.34177 | 42.14139 | -0.3733 | 39.91694 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.57243 | 18.91617 | -1.0890 | 31.98371 |
February | 385.00000 | 19.76510 | 20.50082 | -0.9870 | 27.75713 |
March | 433.00000 | 20.54542 | 20.83826 | -0.7228 | 17.76460 |
April | 410.00000 | 22.18118 | 18.22367 | -0.2504 | 9.68523 |
May | 430.00000 | 23.98739 | 21.49942 | -0.5820 | 14.60466 |
June | 418.00000 | 24.30818 | 33.30920 | -0.3586 | 8.77136 |
July | 422.00000 | 24.46186 | 41.42833 | -0.2540 | 7.94811 |
August | 433.00000 | 24.01470 | 37.50875 | -0.4856 | 11.61195 |
September | 410.00000 | 22.49046 | 31.69604 | -1.1512 | 36.32969 |
October | 427.00000 | 20.53289 | 27.34423 | -0.6829 | 16.52942 |
November | 417.00000 | 19.58149 | 20.03437 | -1.0610 | 30.78887 |
December | 422.00000 | 19.52937 | 15.77235 | -1.1215 | 33.23465 |
Annual Sum or Average | 5034.00000 | 21.76194 | 25.63336 | -0.7266 | 20.49112 |
Minimum of Months | 385.00000 | 19.52937 | 15.77235 | -1.1512 | 7.94811 |
Maximum of Months | 433.00000 | 24.46186 | 41.42833 | -0.2504 | 36.32969 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82745 | 18.78433 | -1.0156 | 28.80445 |
February | 454.00000 | 20.33587 | 20.04186 | -0.8188 | 21.84964 |
March | 514.00000 | 21.28639 | 19.96761 | -0.5135 | 14.56180 |
April | 485.00000 | 22.77651 | 17.37052 | -0.0722 | 9.46475 |
May | 508.00000 | 23.83231 | 21.69650 | -0.6352 | 16.47893 |
June | 496.00000 | 24.18953 | 33.46846 | -0.3996 | 9.59238 |
July | 497.00000 | 24.29924 | 41.69185 | -0.3073 | 8.54922 |
August | 514.00000 | 24.01782 | 37.41407 | -0.4523 | 11.58645 |
September | 485.00000 | 22.83809 | 30.88994 | -1.0023 | 30.61052 |
October | 502.00000 | 21.04719 | 26.61150 | -0.5394 | 13.84030 |
November | 489.00000 | 19.92803 | 19.55699 | -0.9587 | 26.54455 |
December | 497.00000 | 19.77441 | 15.61247 | -1.0641 | 30.60209 |
Annual Sum or Average | 5943.00000 | 22.02847 | 25.31617 | -0.6463 | 18.47076 |
Minimum of Months | 454.00000 | 19.77441 | 15.61247 | -1.0641 | 8.54922 |
Maximum of Months | 514.00000 | 24.29924 | 41.69185 | -0.0722 | 30.61052 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78402 | 19.30089 | -1.0470 | 30.03749 |
February | 454.00000 | 19.90706 | 20.98304 | -0.9646 | 26.80398 |
March | 514.00000 | 20.46605 | 21.49799 | -0.7620 | 18.89596 |
April | 485.00000 | 22.09486 | 18.93511 | -0.2640 | 10.20237 |
May | 508.00000 | 23.64701 | 22.83975 | -0.7414 | 18.72949 |
June | 496.00000 | 24.18715 | 34.10548 | -0.4191 | 9.84146 |
July | 497.00000 | 24.23503 | 42.45451 | -0.3628 | 8.82489 |
August | 514.00000 | 23.84429 | 38.67135 | -0.5605 | 13.37145 |
September | 485.00000 | 22.23810 | 32.70939 | -1.2378 | 39.35001 |
October | 502.00000 | 20.50089 | 28.01459 | -0.6980 | 16.80909 |
November | 489.00000 | 19.79095 | 20.27163 | -1.0173 | 28.82030 |
December | 497.00000 | 19.75154 | 16.11166 | -1.0776 | 31.18187 |
Annual Sum or Average | 5943.00000 | 21.72075 | 26.38270 | -0.7605 | 20.97876 |
Minimum of Months | 454.00000 | 19.75154 | 16.11166 | -1.2378 | 8.82489 |
Maximum of Months | 514.00000 | 24.23503 | 42.45451 | -0.2640 | 39.35001 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 4662947.58 | 1345334.48 | 1.44 | 4662767.44 | 180.14 | 0.00 | 0.26 | 20-JAN-07:01 | 0.00 | 01-JAN-00:02 | 5903.60 | 20-JAN-07:01 | 5903.60 | 20-JAN-07:01 | 3.00 | 19-JAN-17:11 | 1644.29 | 20-JAN-07:01 | 0.00 |
February | 7490166.97 | 2181418.40 | 4.32 | 7439214.59 | 50952.38 | 0.00 | 0.27 | 08-FEB-07:01 | 0.00 | 01-FEB-00:10 | 6108.55 | 08-FEB-07:01 | 6108.55 | 08-FEB-07:01 | 27.65 | 09-FEB-13:13 | 1697.86 | 08-FEB-07:01 | 0.00 |
March | 24211556.99 | 7116182.55 | 15.13 | 24016549.77 | 195007.22 | 0.00 | 0.25 | 07-MAR-07:01 | 0.00 | 01-MAR-00:10 | 5750.79 | 07-MAR-07:01 | 5750.79 | 07-MAR-07:01 | 99.40 | 21-MAR-17:12 | 1604.21 | 07-MAR-07:01 | 0.00 |
April | 33837041.97 | 9902770.28 | 17.19 | 33802157.08 | 34884.89 | 0.00 | 0.27 | 14-APR-07:05 | 0.00 | 01-APR-00:10 | 6130.52 | 14-APR-07:05 | 6130.52 | 14-APR-07:05 | 20.18 | 29-APR-08:50 | 1703.59 | 14-APR-07:05 | 0.00 |
May | 0.337895E+10 | 0.886291E+09 | 133.38 | 0.337287E+10 | 6081696.68 | 0.00 | 1.00 | 31-MAY-15:10 | 0.00 | 01-MAY-00:10 | 32700.32 | 31-MAY-16:00 | 32700.32 | 31-MAY-16:00 | 348.02 | 31-MAY-20:00 | 7465.49 | 31-MAY-16:00 | 0.00 |
June | 0.184551E+11 | 0.453875E+10 | 310.66 | 0.176653E+11 | 0.789827E+09 | 0.00 | 1.00 | 12-JUN-13:20 | 0.00 | 01-JUN-00:10 | 57983.68 | 30-JUN-11:40 | 51644.08 | 20-JUN-16:00 | 12443.02 | 30-JUN-06:02 | 13981.01 | 30-JUN-12:30 | 0.00 |
July | 0.262712E+11 | 0.630542E+10 | 328.06 | 0.241945E+11 | 0.207664E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 59508.40 | 11-JUL-16:00 | 56924.55 | 12-JUL-16:00 | 28530.29 | 03-JUL-15:00 | 14351.73 | 11-JUL-16:00 | 0.00 |
August | 0.141661E+11 | 0.345733E+10 | 240.54 | 0.130925E+11 | 0.107361E+10 | 0.00 | 1.00 | 01-AUG-15:10 | 0.00 | 01-AUG-00:10 | 55652.26 | 11-AUG-15:50 | 55652.26 | 11-AUG-15:50 | 7135.02 | 03-AUG-12:40 | 13183.15 | 11-AUG-15:50 | 0.00 |
September | 0.203965E+09 | 58472754.88 | 29.72 | 0.190915E+09 | 13050249.48 | 0.00 | 0.36 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 8358.01 | 07-SEP-16:00 | 8358.01 | 07-SEP-16:00 | 616.43 | 02-SEP-15:02 | 2271.56 | 07-SEP-16:00 | 0.00 |
October | 31287807.91 | 9185460.70 | 17.07 | 29976407.65 | 1311400.26 | 0.00 | 0.15 | 30-OCT-06:01 | 0.00 | 01-OCT-00:10 | 3399.14 | 30-OCT-06:01 | 3399.14 | 30-OCT-06:01 | 134.80 | 02-OCT-07:30 | 971.32 | 30-OCT-06:01 | 0.00 |
November | 4067433.11 | 1184252.04 | 1.73 | 4067433.11 | -0.0 | 0.00 | 0.21 | 16-NOV-07:01 | 0.00 | 01-NOV-00:10 | 4809.70 | 16-NOV-07:01 | 4809.70 | 16-NOV-07:01 | 0.00 | 01-NOV-12:40 | 1354.59 | 16-NOV-07:01 | 0.00 |
December | 2978113.63 | 861606.01 | 0.66 | 2978113.63 | 0.00 | 0.00 | 0.23 | 21-DEC-07:01 | 0.00 | 01-DEC-00:05 | 5138.67 | 21-DEC-07:01 | 5138.67 | 21-DEC-07:01 | 0.00 | 29-DEC-07:01 | 1442.39 | 21-DEC-07:01 | 0.00 |
Annual Sum or Average | 0.625839E+11 | 0.152780E+11 | 1099.89 | 0.586231E+11 | 0.396081E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 2978113.63 | 861606.01 | 0.66 | 2978113.63 | -0.0 | 0.00 | 0.15 | 0.00 | 3399.14 | 3399.14 | 0.00 | 971.32 | 0.00 | ||||||
Maximum of Months | 0.262712E+11 | 0.630542E+10 | 328.06 | 0.241945E+11 | 0.207664E+10 | 0.00 | 1.00 | 0.00 | 59508.40 | 56924.55 | 28530.29 | 14351.73 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2665327.45 | 758104.54 | 0.32 | 2665327.45 | -0.0 | 0.00 | 0.24 | 20-JAN-07:01 | 0.00 | 01-JAN-00:02 | 4731.99 | 20-JAN-07:01 | 4731.99 | 20-JAN-07:01 | 0.00 | 21-JAN-07:03 | 1325.88 | 20-JAN-07:01 | 0.00 |
February | 3459803.83 | 979187.50 | 0.43 | 3459290.77 | 513.06 | 0.00 | 0.29 | 09-FEB-07:01 | 0.00 | 01-FEB-00:10 | 5865.43 | 09-FEB-07:01 | 5865.43 | 09-FEB-07:01 | 5.99 | 09-FEB-07:11 | 1622.47 | 09-FEB-07:01 | 0.00 |
March | 7082184.76 | 1996537.82 | 1.48 | 7077422.53 | 4762.23 | 0.00 | 0.33 | 24-MAR-06:01 | 0.00 | 01-MAR-00:10 | 6857.10 | 24-MAR-06:01 | 6857.10 | 24-MAR-06:01 | 7.88 | 22-MAR-06:12 | 1875.82 | 24-MAR-06:01 | 0.00 |
April | 20363148.53 | 5918102.01 | 11.72 | 20362868.87 | 279.65 | 0.00 | 0.34 | 06-APR-06:01 | 0.00 | 01-APR-00:10 | 6963.43 | 06-APR-06:01 | 6963.43 | 06-APR-06:01 | 1.72 | 18-APR-12:03 | 1902.66 | 06-APR-06:01 | 0.00 |
May | 0.373914E+10 | 0.966332E+09 | 147.02 | 0.373588E+10 | 3251867.43 | 0.00 | 1.00 | 12-MAY-12:50 | 0.00 | 01-MAY-00:10 | 33831.26 | 31-MAY-16:00 | 33831.26 | 31-MAY-16:00 | 370.06 | 31-MAY-06:03 | 7721.34 | 31-MAY-16:00 | 0.00 |
June | 0.186360E+11 | 0.454012E+10 | 320.92 | 0.178888E+11 | 0.747255E+09 | 0.00 | 1.00 | 09-JUN-12:05 | 0.00 | 01-JUN-00:10 | 57938.08 | 30-JUN-12:10 | 51503.83 | 30-JUN-14:30 | 11015.40 | 30-JUN-11:40 | 14043.84 | 30-JUN-14:30 | 0.00 |
July | 0.251148E+11 | 0.601239E+10 | 340.52 | 0.231533E+11 | 0.196151E+10 | 0.00 | 1.00 | 03-JUL-14:30 | 0.00 | 01-JUL-00:10 | 56178.92 | 11-JUL-15:30 | 52732.67 | 12-JUL-16:00 | 28425.03 | 03-JUL-15:00 | 13474.19 | 11-JUL-16:00 | 0.00 |
August | 0.129099E+11 | 0.314812E+10 | 246.87 | 0.119291E+11 | 0.980780E+09 | 0.00 | 1.00 | 01-AUG-13:00 | 0.00 | 01-AUG-00:10 | 50863.75 | 11-AUG-15:20 | 50863.75 | 11-AUG-15:20 | 6418.54 | 04-AUG-10:50 | 11917.06 | 11-AUG-15:40 | 0.00 |
September | 0.185761E+09 | 53123558.48 | 26.71 | 0.175464E+09 | 10297304.46 | 0.00 | 0.34 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 6970.13 | 07-SEP-16:00 | 6970.13 | 07-SEP-16:00 | 520.59 | 02-SEP-15:02 | 1904.35 | 07-SEP-16:00 | 0.00 |
October | 7912137.14 | 2237731.96 | 1.76 | 7871537.10 | 40600.04 | 0.00 | 0.32 | 13-OCT-06:01 | 0.00 | 01-OCT-00:10 | 6501.36 | 13-OCT-06:01 | 6501.36 | 13-OCT-06:01 | 34.48 | 10-OCT-06:12 | 1785.59 | 13-OCT-06:01 | 0.00 |
November | 2161184.24 | 613777.46 | 0.20 | 2161184.24 | -0.0 | 0.00 | 0.23 | 02-NOV-06:01 | 0.00 | 01-NOV-00:10 | 4551.73 | 02-NOV-06:01 | 4551.73 | 02-NOV-06:01 | 0.00 | 16-NOV-07:01 | 1278.00 | 02-NOV-06:01 | 0.00 |
December | 1408942.77 | 405860.25 | 0.38 | 1408942.77 | -0.0 | 0.00 | 0.19 | 23-DEC-07:03 | 0.00 | 01-DEC-00:05 | 3796.28 | 23-DEC-07:03 | 3796.28 | 23-DEC-07:03 | 0.00 | 20-DEC-07:01 | 1075.19 | 23-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.606306E+11 | 0.147330E+11 | 1098.34 | 0.569275E+11 | 0.370314E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 1408942.77 | 405860.25 | 0.20 | 1408942.77 | -0.0 | 0.00 | 0.19 | 0.00 | 3796.28 | 3796.28 | 0.00 | 1075.19 | 0.00 | ||||||
Maximum of Months | 0.251148E+11 | 0.601239E+10 | 340.52 | 0.231533E+11 | 0.196151E+10 | 0.00 | 1.00 | 0.00 | 57938.08 | 52732.67 | 28425.03 | 14043.84 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 98743.27 | 29051.98 | 0.05 | 98743.27 | 0.00 | 0.00 | 0.04 | 19-JAN-07:01 | 0.00 | 01-JAN-00:02 | 824.85 | 19-JAN-07:01 | 824.85 | 19-JAN-07:01 | 0.00 | 19-JAN-07:01 | 242.13 | 19-JAN-07:01 | 0.00 |
February | 454683.33 | 131816.23 | 0.12 | 453533.48 | 1149.86 | 0.00 | 0.16 | 09-FEB-07:01 | 0.00 | 01-FEB-00:10 | 3421.42 | 09-FEB-07:01 | 3421.42 | 09-FEB-07:01 | 13.41 | 09-FEB-07:14 | 976.86 | 09-FEB-07:01 | 0.00 |
March | 3669060.36 | 1078937.35 | 3.50 | 3617317.08 | 51743.28 | 0.00 | 0.17 | 23-MAR-06:01 | 0.00 | 01-MAR-00:10 | 3593.38 | 23-MAR-06:01 | 3593.38 | 23-MAR-06:01 | 29.10 | 22-MAR-11:50 | 1024.11 | 23-MAR-06:01 | 0.00 |
April | 29087469.14 | 8542705.99 | 21.90 | 29077422.65 | 10046.49 | 0.00 | 0.21 | 19-APR-06:01 | 0.00 | 01-APR-00:10 | 4653.88 | 19-APR-06:01 | 4653.88 | 19-APR-06:01 | 15.94 | 18-APR-12:20 | 1311.71 | 19-APR-06:01 | 0.00 |
May | 0.371303E+10 | 0.966141E+09 | 145.32 | 0.370798E+10 | 5052773.01 | 0.00 | 1.00 | 31-MAY-14:10 | 0.00 | 01-MAY-00:10 | 36172.44 | 31-MAY-16:00 | 36172.44 | 31-MAY-16:00 | 357.12 | 31-MAY-20:00 | 8256.23 | 31-MAY-16:00 | 0.00 |
June | 0.191581E+11 | 0.469518E+10 | 317.41 | 0.183768E+11 | 0.781285E+09 | 0.00 | 1.00 | 12-JUN-13:10 | 0.00 | 01-JUN-00:10 | 63931.90 | 30-JUN-12:30 | 57992.57 | 29-JUN-14:30 | 11693.04 | 30-JUN-11:50 | 15673.57 | 30-JUN-14:30 | 0.00 |
July | 0.258197E+11 | 0.621630E+10 | 338.65 | 0.238143E+11 | 0.200542E+10 | 0.00 | 1.00 | 03-JUL-14:40 | 0.00 | 01-JUL-00:10 | 59288.55 | 21-JUL-14:30 | 59288.55 | 21-JUL-14:30 | 28415.95 | 03-JUL-15:00 | 14623.08 | 21-JUL-14:50 | 0.00 |
August | 0.129374E+11 | 0.317741E+10 | 242.51 | 0.118763E+11 | 0.106114E+10 | 0.00 | 1.00 | 02-AUG-12:10 | 0.00 | 01-AUG-00:10 | 54197.39 | 11-AUG-15:50 | 54197.39 | 11-AUG-15:50 | 6532.10 | 03-AUG-14:40 | 12838.90 | 11-AUG-15:50 | 0.00 |
September | 0.170994E+09 | 49103863.81 | 26.96 | 0.158930E+09 | 12064085.13 | 0.00 | 0.28 | 07-SEP-16:00 | 0.00 | 01-SEP-00:10 | 6167.46 | 07-SEP-16:00 | 6167.46 | 07-SEP-16:00 | 584.15 | 02-SEP-15:02 | 1711.37 | 07-SEP-16:00 | 0.00 |
October | 5947465.60 | 1724532.28 | 2.35 | 5767061.10 | 180404.50 | 0.00 | 0.20 | 05-OCT-06:01 | 0.00 | 01-OCT-00:10 | 4403.14 | 05-OCT-06:01 | 4403.14 | 05-OCT-06:01 | 89.50 | 03-OCT-06:01 | 1244.28 | 05-OCT-06:01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 64016.28 | 18873.24 | 0.04 | 64016.28 | -0.0 | 0.00 | 0.02 | 23-DEC-07:03 | 0.00 | 01-DEC-00:05 | 426.78 | 23-DEC-07:03 | 426.78 | 23-DEC-07:03 | 0.00 | 01-DEC-00:05 | 125.82 | 23-DEC-07:03 | 0.00 |
Annual Sum or Average | 0.618386E+11 | 0.151157E+11 | 1098.81 | 0.579734E+11 | 0.386520E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.258197E+11 | 0.621630E+10 | 338.65 | 0.238143E+11 | 0.200542E+10 | 0.00 | 1.00 | 0.00 | 63931.90 | 59288.55 | 28415.95 | 15673.57 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.48 | 0.00 | 36.48 | 0.00 | 2685.61 | 0.00 | 0.00 | 0.00 |
February | 161.26 | 0.00 | 161.26 | 0.00 | 2394.01 | 0.00 | 0.00 | 0.00 |
March | 431.30 | 0.00 | 431.30 | 41.66 | 1756.29 | 0.00 | 0.00 | 0.00 |
April | 779.35 | 16.18 | 763.16 | 341.63 | 927.81 | 0.00 | 0.00 | 0.00 |
May | 1192.41 | 186.56 | 1005.85 | 953.82 | 423.26 | 0.00 | 0.00 | 0.00 |
June | 1558.03 | 344.60 | 1213.42 | 1561.61 | 199.44 | 0.00 | 0.00 | 0.00 |
July | 1307.22 | 210.43 | 1096.79 | 1340.58 | 242.67 | 0.00 | 0.00 | 0.00 |
August | 834.66 | 45.12 | 789.54 | 704.04 | 399.47 | 0.00 | 0.00 | 0.00 |
September | 466.49 | 0.41 | 466.08 | 197.17 | 778.92 | 0.00 | 0.00 | 0.00 |
October | 227.02 | 0.00 | 227.02 | 21.50 | 1478.81 | 0.00 | 0.00 | 0.00 |
November | 70.45 | 0.00 | 70.45 | 0.00 | 2624.17 | 0.00 | 0.00 | 0.00 |
December | 11.07 | 0.00 | 11.07 | 0.00 | 2829.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 591.75 | 67.24 | 524.52 | 432.66 | 1389.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.07 | 0.00 | 11.07 | 0.00 | 199.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1558.03 | 344.60 | 1213.42 | 1561.61 | 2829.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.49 | 19.59 | 43.90 | 5.79 | 1737.51 | 0.00 | 0.00 | 0.00 |
February | 353.15 | 168.09 | 185.07 | 193.50 | 1442.99 | 0.00 | 0.00 | 0.00 |
March | 1010.87 | 512.52 | 498.35 | 882.31 | 1050.43 | 0.00 | 0.00 | 0.00 |
April | 1390.14 | 704.41 | 685.73 | 1325.78 | 574.82 | 0.00 | 0.00 | 0.00 |
May | 2022.20 | 1141.06 | 881.14 | 2263.31 | 306.97 | 0.00 | 0.00 | 0.00 |
June | 1858.92 | 868.19 | 990.73 | 2147.38 | 152.70 | 0.00 | 0.00 | 0.00 |
July | 1766.08 | 857.41 | 908.67 | 2091.08 | 174.76 | 0.00 | 0.00 | 0.00 |
August | 1398.44 | 681.60 | 716.84 | 1586.34 | 270.59 | 0.00 | 0.00 | 0.00 |
September | 864.39 | 379.00 | 485.39 | 833.76 | 491.61 | 0.00 | 0.00 | 0.00 |
October | 455.79 | 182.76 | 273.03 | 341.29 | 896.40 | 0.00 | 0.00 | 0.00 |
November | 96.27 | 33.16 | 63.10 | 8.24 | 1684.26 | 0.00 | 0.00 | 0.00 |
December | 13.69 | 3.15 | 10.54 | 0.00 | 1876.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 944.73 | 464.63 | 480.10 | 978.48 | 885.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.69 | 3.15 | 10.54 | 0.00 | 152.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2022.20 | 1141.06 | 990.73 | 2263.31 | 1876.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 440.54 | 291.23 | 149.31 | 266.85 | 2411.38 | 0.00 | 0.00 | 0.00 |
February | 1515.33 | 1056.92 | 458.41 | 1327.79 | 1928.21 | 0.00 | 0.00 | 0.00 |
March | 2596.40 | 1763.21 | 833.19 | 2617.13 | 1470.10 | 0.00 | 0.00 | 0.00 |
April | 3160.54 | 1968.32 | 1192.22 | 3539.09 | 964.65 | 0.00 | 0.00 | 0.00 |
May | 2597.01 | 1343.51 | 1253.50 | 2984.68 | 532.86 | 0.00 | 0.00 | 0.00 |
June | 2368.32 | 966.63 | 1401.69 | 2794.59 | 288.71 | 0.00 | 0.00 | 0.00 |
July | 2283.82 | 991.98 | 1291.84 | 2761.37 | 306.91 | 0.00 | 0.00 | 0.00 |
August | 2371.89 | 1308.06 | 1063.83 | 2827.47 | 447.33 | 0.00 | 0.00 | 0.00 |
September | 1920.85 | 1159.03 | 761.82 | 2093.10 | 757.95 | 0.00 | 0.00 | 0.00 |
October | 1385.89 | 881.81 | 504.08 | 1309.84 | 1246.28 | 0.00 | 0.00 | 0.00 |
November | 744.48 | 521.37 | 223.11 | 511.93 | 2241.69 | 0.00 | 0.00 | 0.00 |
December | 132.20 | 93.47 | 38.74 | 24.31 | 2689.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1792.59 | 1027.19 | 765.40 | 1922.96 | 1270.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 132.20 | 93.47 | 38.74 | 24.31 | 288.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3160.54 | 1968.32 | 1401.69 | 3539.09 | 2689.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.45 | 5.76 | 27.69 | 0.00 | 1772.06 | 0.00 | 0.00 | 0.00 |
February | 197.96 | 68.19 | 129.76 | 42.54 | 1500.31 | 0.00 | 0.00 | 0.00 |
March | 596.51 | 256.08 | 340.43 | 356.58 | 1075.16 | 0.00 | 0.00 | 0.00 |
April | 1419.34 | 736.68 | 682.66 | 1403.55 | 619.37 | 0.00 | 0.00 | 0.00 |
May | 1380.27 | 629.96 | 750.31 | 1439.59 | 326.13 | 0.00 | 0.00 | 0.00 |
June | 1512.43 | 646.30 | 866.13 | 1706.66 | 178.54 | 0.00 | 0.00 | 0.00 |
July | 1264.93 | 479.46 | 785.47 | 1441.04 | 192.86 | 0.00 | 0.00 | 0.00 |
August | 1039.46 | 440.80 | 598.66 | 1127.46 | 284.28 | 0.00 | 0.00 | 0.00 |
September | 628.72 | 263.46 | 365.26 | 540.68 | 503.80 | 0.00 | 0.00 | 0.00 |
October | 245.38 | 73.26 | 172.12 | 99.41 | 935.09 | 0.00 | 0.00 | 0.00 |
November | 97.77 | 35.08 | 62.69 | 11.18 | 1680.16 | 0.00 | 0.00 | 0.00 |
December | 8.78 | 0.87 | 7.91 | 0.00 | 1882.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.90 | 303.64 | 400.26 | 683.39 | 909.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.78 | 0.87 | 7.91 | 0.00 | 178.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1512.43 | 736.68 | 866.13 | 1706.66 | 1882.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.16 | 0.00 | 12.16 | 0.00 | 898.55 | 0.00 | 0.00 | 0.00 |
February | 53.75 | 0.00 | 53.75 | 0.00 | 797.62 | 0.00 | 0.00 | 0.00 |
March | 143.76 | 0.00 | 143.76 | 14.51 | 585.93 | 0.00 | 0.00 | 0.00 |
April | 259.77 | 5.39 | 254.38 | 120.94 | 307.65 | 0.00 | 0.00 | 0.00 |
May | 397.45 | 62.18 | 335.27 | 331.28 | 136.46 | 0.00 | 0.00 | 0.00 |
June | 519.32 | 114.86 | 404.46 | 531.48 | 63.88 | 0.00 | 0.00 | 0.00 |
July | 435.72 | 70.14 | 365.58 | 452.96 | 79.90 | 0.00 | 0.00 | 0.00 |
August | 278.21 | 15.04 | 263.17 | 234.34 | 136.95 | 0.00 | 0.00 | 0.00 |
September | 155.49 | 0.14 | 155.35 | 60.89 | 279.78 | 0.00 | 0.00 | 0.00 |
October | 75.67 | 0.00 | 75.67 | 5.75 | 519.61 | 0.00 | 0.00 | 0.00 |
November | 23.48 | 0.00 | 23.48 | 0.00 | 893.11 | 0.00 | 0.00 | 0.00 |
December | 3.69 | 0.00 | 3.69 | 0.00 | 953.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.24 | 22.41 | 174.83 | 146.86 | 469.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.69 | 0.00 | 3.69 | 0.00 | 63.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 519.32 | 114.86 | 404.46 | 531.48 | 953.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.16 | 0.00 | 12.16 | 0.00 | 898.61 | 0.00 | 0.00 | 0.00 |
February | 53.75 | 0.00 | 53.75 | 0.00 | 797.67 | 0.00 | 0.00 | 0.00 |
March | 143.77 | 0.00 | 143.77 | 14.51 | 585.96 | 0.00 | 0.00 | 0.00 |
April | 259.79 | 5.39 | 254.39 | 120.94 | 307.67 | 0.00 | 0.00 | 0.00 |
May | 397.48 | 62.19 | 335.29 | 331.30 | 136.47 | 0.00 | 0.00 | 0.00 |
June | 519.35 | 114.87 | 404.48 | 531.51 | 63.88 | 0.00 | 0.00 | 0.00 |
July | 435.75 | 70.14 | 365.60 | 452.99 | 79.91 | 0.00 | 0.00 | 0.00 |
August | 278.22 | 15.04 | 263.18 | 234.36 | 136.96 | 0.00 | 0.00 | 0.00 |
September | 155.50 | 0.14 | 155.36 | 60.89 | 279.80 | 0.00 | 0.00 | 0.00 |
October | 75.67 | 0.00 | 75.67 | 5.75 | 519.64 | 0.00 | 0.00 | 0.00 |
November | 23.48 | 0.00 | 23.48 | 0.00 | 893.16 | 0.00 | 0.00 | 0.00 |
December | 3.69 | 0.00 | 3.69 | 0.00 | 953.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.25 | 22.41 | 174.84 | 146.87 | 469.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.69 | 0.00 | 3.69 | 0.00 | 63.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 519.35 | 114.87 | 404.48 | 531.51 | 953.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.16 | 0.00 | 12.16 | 0.00 | 898.61 | 0.00 | 0.00 | 0.00 |
February | 53.75 | 0.00 | 53.75 | 0.00 | 797.67 | 0.00 | 0.00 | 0.00 |
March | 143.77 | 0.00 | 143.77 | 14.51 | 585.96 | 0.00 | 0.00 | 0.00 |
April | 259.79 | 5.39 | 254.39 | 120.94 | 307.67 | 0.00 | 0.00 | 0.00 |
May | 397.48 | 62.19 | 335.29 | 331.30 | 136.47 | 0.00 | 0.00 | 0.00 |
June | 519.35 | 114.87 | 404.48 | 531.51 | 63.88 | 0.00 | 0.00 | 0.00 |
July | 435.75 | 70.14 | 365.60 | 452.99 | 79.91 | 0.00 | 0.00 | 0.00 |
August | 278.22 | 15.04 | 263.18 | 234.36 | 136.96 | 0.00 | 0.00 | 0.00 |
September | 155.50 | 0.14 | 155.36 | 60.89 | 279.80 | 0.00 | 0.00 | 0.00 |
October | 75.67 | 0.00 | 75.67 | 5.75 | 519.64 | 0.00 | 0.00 | 0.00 |
November | 23.48 | 0.00 | 23.48 | 0.00 | 893.16 | 0.00 | 0.00 | 0.00 |
December | 3.69 | 0.00 | 3.69 | 0.00 | 953.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.25 | 22.41 | 174.84 | 146.87 | 469.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3.69 | 0.00 | 3.69 | 0.00 | 63.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 519.35 | 114.87 | 404.48 | 531.51 | 953.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 61.08 | 18.85 | 42.23 | 5.73 | 1679.58 | 0.00 | 0.00 | 0.00 |
February | 339.72 | 161.69 | 178.02 | 187.11 | 1391.30 | 0.00 | 0.00 | 0.00 |
March | 972.41 | 493.02 | 479.39 | 855.17 | 1018.77 | 0.00 | 0.00 | 0.00 |
April | 1337.25 | 677.61 | 659.64 | 1285.87 | 563.34 | 0.00 | 0.00 | 0.00 |
May | 1945.27 | 1097.65 | 847.62 | 2189.55 | 301.03 | 0.00 | 0.00 | 0.00 |
June | 1788.20 | 835.16 | 953.04 | 2080.23 | 146.80 | 0.00 | 0.00 | 0.00 |
July | 1698.89 | 824.79 | 874.10 | 2019.13 | 172.45 | 0.00 | 0.00 | 0.00 |
August | 1345.24 | 655.67 | 689.57 | 1525.29 | 275.13 | 0.00 | 0.00 | 0.00 |
September | 831.51 | 364.58 | 466.93 | 786.79 | 518.97 | 0.00 | 0.00 | 0.00 |
October | 438.45 | 175.81 | 262.64 | 321.38 | 915.68 | 0.00 | 0.00 | 0.00 |
November | 92.60 | 31.90 | 60.70 | 7.73 | 1653.18 | 0.00 | 0.00 | 0.00 |
December | 13.17 | 3.03 | 10.14 | 0.00 | 1821.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 908.79 | 446.95 | 461.84 | 943.73 | 868.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.17 | 3.03 | 10.14 | 0.00 | 146.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1945.27 | 1097.65 | 953.04 | 2189.55 | 1821.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2.41 | 0.75 | 1.67 | 0.23 | 66.41 | 0.00 | 0.00 | 0.00 |
February | 13.43 | 6.39 | 7.04 | 7.40 | 55.01 | 0.00 | 0.00 | 0.00 |
March | 38.45 | 19.49 | 18.95 | 33.81 | 40.28 | 0.00 | 0.00 | 0.00 |
April | 52.87 | 26.79 | 26.08 | 50.84 | 22.27 | 0.00 | 0.00 | 0.00 |
May | 76.91 | 43.40 | 33.51 | 86.57 | 11.90 | 0.00 | 0.00 | 0.00 |
June | 70.70 | 33.02 | 37.68 | 82.25 | 5.80 | 0.00 | 0.00 | 0.00 |
July | 67.17 | 32.61 | 34.56 | 79.83 | 6.82 | 0.00 | 0.00 | 0.00 |
August | 53.19 | 25.92 | 27.27 | 60.31 | 10.88 | 0.00 | 0.00 | 0.00 |
September | 32.88 | 14.42 | 18.46 | 31.11 | 20.52 | 0.00 | 0.00 | 0.00 |
October | 17.34 | 6.95 | 10.38 | 12.71 | 36.21 | 0.00 | 0.00 | 0.00 |
November | 3.66 | 1.26 | 2.40 | 0.31 | 65.37 | 0.00 | 0.00 | 0.00 |
December | 0.52 | 0.12 | 0.40 | 0.00 | 72.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.93 | 17.67 | 18.26 | 37.31 | 34.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.52 | 0.12 | 0.40 | 0.00 | 5.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 76.91 | 43.40 | 37.68 | 86.57 | 72.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 146.85 | 97.08 | 49.77 | 93.43 | 773.15 | 0.00 | 0.00 | 0.00 |
February | 505.13 | 352.32 | 152.81 | 452.55 | 627.35 | 0.00 | 0.00 | 0.00 |
March | 865.49 | 587.76 | 277.74 | 890.42 | 485.07 | 0.00 | 0.00 | 0.00 |
April | 1053.55 | 656.13 | 397.42 | 1193.44 | 329.07 | 0.00 | 0.00 | 0.00 |
May | 865.70 | 447.85 | 417.84 | 1008.52 | 178.72 | 0.00 | 0.00 | 0.00 |
June | 789.46 | 322.22 | 467.24 | 943.13 | 95.45 | 0.00 | 0.00 | 0.00 |
July | 761.30 | 330.67 | 430.62 | 927.41 | 104.31 | 0.00 | 0.00 | 0.00 |
August | 790.66 | 436.04 | 354.62 | 947.33 | 157.36 | 0.00 | 0.00 | 0.00 |
September | 640.30 | 386.36 | 253.95 | 697.64 | 273.11 | 0.00 | 0.00 | 0.00 |
October | 461.98 | 293.95 | 168.03 | 436.67 | 434.43 | 0.00 | 0.00 | 0.00 |
November | 248.17 | 173.80 | 74.37 | 175.95 | 735.63 | 0.00 | 0.00 | 0.00 |
December | 44.07 | 31.16 | 12.91 | 10.23 | 862.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 597.55 | 342.41 | 255.14 | 648.52 | 420.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.07 | 31.16 | 12.91 | 10.23 | 95.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1053.55 | 656.13 | 467.24 | 1193.44 | 862.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 146.85 | 97.08 | 49.77 | 93.43 | 773.15 | 0.00 | 0.00 | 0.00 |
February | 505.13 | 352.32 | 152.81 | 452.55 | 627.35 | 0.00 | 0.00 | 0.00 |
March | 865.49 | 587.76 | 277.74 | 890.42 | 485.07 | 0.00 | 0.00 | 0.00 |
April | 1053.55 | 656.13 | 397.42 | 1193.44 | 329.07 | 0.00 | 0.00 | 0.00 |
May | 865.70 | 447.85 | 417.84 | 1008.52 | 178.72 | 0.00 | 0.00 | 0.00 |
June | 789.46 | 322.22 | 467.24 | 943.13 | 95.45 | 0.00 | 0.00 | 0.00 |
July | 761.30 | 330.67 | 430.62 | 927.41 | 104.31 | 0.00 | 0.00 | 0.00 |
August | 790.66 | 436.04 | 354.62 | 947.33 | 157.36 | 0.00 | 0.00 | 0.00 |
September | 640.30 | 386.36 | 253.95 | 697.64 | 273.11 | 0.00 | 0.00 | 0.00 |
October | 461.98 | 293.95 | 168.03 | 436.67 | 434.43 | 0.00 | 0.00 | 0.00 |
November | 248.17 | 173.80 | 74.37 | 175.95 | 735.63 | 0.00 | 0.00 | 0.00 |
December | 44.07 | 31.16 | 12.91 | 10.23 | 862.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 597.55 | 342.41 | 255.14 | 648.52 | 420.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.07 | 31.16 | 12.91 | 10.23 | 95.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1053.55 | 656.13 | 467.24 | 1193.44 | 862.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 146.84 | 97.07 | 49.77 | 93.42 | 773.11 | 0.00 | 0.00 | 0.00 |
February | 505.09 | 352.30 | 152.80 | 452.53 | 627.31 | 0.00 | 0.00 | 0.00 |
March | 865.44 | 587.72 | 277.72 | 890.36 | 485.04 | 0.00 | 0.00 | 0.00 |
April | 1053.48 | 656.09 | 397.39 | 1193.36 | 329.05 | 0.00 | 0.00 | 0.00 |
May | 865.64 | 447.82 | 417.82 | 1008.46 | 178.71 | 0.00 | 0.00 | 0.00 |
June | 789.41 | 322.20 | 467.21 | 943.07 | 95.45 | 0.00 | 0.00 | 0.00 |
July | 761.25 | 330.65 | 430.60 | 927.36 | 104.30 | 0.00 | 0.00 | 0.00 |
August | 790.61 | 436.01 | 354.60 | 947.27 | 157.35 | 0.00 | 0.00 | 0.00 |
September | 640.26 | 386.33 | 253.93 | 697.60 | 273.09 | 0.00 | 0.00 | 0.00 |
October | 461.95 | 293.93 | 168.02 | 436.64 | 434.40 | 0.00 | 0.00 | 0.00 |
November | 248.15 | 173.79 | 74.37 | 175.94 | 735.59 | 0.00 | 0.00 | 0.00 |
December | 44.07 | 31.15 | 12.91 | 10.23 | 862.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 597.51 | 342.39 | 255.12 | 648.48 | 420.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 44.07 | 31.15 | 12.91 | 10.23 | 95.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1053.48 | 656.09 | 467.21 | 1193.36 | 862.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 32.18 | 5.54 | 26.63 | 0.00 | 1713.09 | 0.00 | 0.00 | 0.00 |
February | 190.42 | 65.60 | 124.83 | 41.79 | 1446.02 | 0.00 | 0.00 | 0.00 |
March | 573.82 | 246.34 | 327.48 | 349.48 | 1039.26 | 0.00 | 0.00 | 0.00 |
April | 1365.35 | 708.65 | 656.69 | 1364.01 | 608.59 | 0.00 | 0.00 | 0.00 |
May | 1327.76 | 605.99 | 721.77 | 1402.07 | 314.02 | 0.00 | 0.00 | 0.00 |
June | 1454.90 | 621.71 | 833.18 | 1656.95 | 170.09 | 0.00 | 0.00 | 0.00 |
July | 1216.81 | 461.22 | 755.59 | 1394.92 | 187.09 | 0.00 | 0.00 | 0.00 |
August | 999.91 | 424.03 | 575.89 | 1082.56 | 288.04 | 0.00 | 0.00 | 0.00 |
September | 604.80 | 253.44 | 351.36 | 508.55 | 527.49 | 0.00 | 0.00 | 0.00 |
October | 236.04 | 70.47 | 165.57 | 91.49 | 950.10 | 0.00 | 0.00 | 0.00 |
November | 94.05 | 33.75 | 60.31 | 10.44 | 1649.98 | 0.00 | 0.00 | 0.00 |
December | 8.45 | 0.84 | 7.61 | 0.00 | 1828.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 677.12 | 292.08 | 385.04 | 661.11 | 890.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.45 | 0.84 | 7.61 | 0.00 | 170.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1454.90 | 708.65 | 833.18 | 1656.95 | 1828.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1.27 | 0.22 | 1.05 | 0.00 | 67.73 | 0.00 | 0.00 | 0.00 |
February | 7.53 | 2.59 | 4.94 | 1.65 | 57.17 | 0.00 | 0.00 | 0.00 |
March | 22.69 | 9.74 | 12.95 | 13.82 | 41.09 | 0.00 | 0.00 | 0.00 |
April | 53.98 | 28.02 | 25.97 | 53.93 | 24.06 | 0.00 | 0.00 | 0.00 |
May | 52.50 | 23.96 | 28.54 | 55.44 | 12.42 | 0.00 | 0.00 | 0.00 |
June | 57.53 | 24.58 | 32.94 | 65.51 | 6.73 | 0.00 | 0.00 | 0.00 |
July | 48.11 | 18.24 | 29.88 | 55.15 | 7.40 | 0.00 | 0.00 | 0.00 |
August | 39.54 | 16.77 | 22.77 | 42.80 | 11.39 | 0.00 | 0.00 | 0.00 |
September | 23.91 | 10.02 | 13.89 | 20.11 | 20.86 | 0.00 | 0.00 | 0.00 |
October | 9.33 | 2.79 | 6.55 | 3.62 | 37.57 | 0.00 | 0.00 | 0.00 |
November | 3.72 | 1.33 | 2.38 | 0.41 | 65.24 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 0.03 | 0.30 | 0.00 | 72.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 26.77 | 11.55 | 15.22 | 26.14 | 35.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.33 | 0.03 | 0.30 | 0.00 | 6.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.53 | 28.02 | 32.94 | 65.51 | 72.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 36.48 | 0.00 | 36.48 | 0.00 | 2733.53 | 0.00 | 0.00 | 0.00 |
February | 161.26 | 0.00 | 161.26 | 0.00 | 2447.12 | 0.00 | 0.00 | 0.00 |
March | 431.30 | 0.00 | 431.30 | 38.43 | 1816.13 | 0.00 | 0.00 | 0.00 |
April | 779.35 | 16.18 | 763.16 | 322.54 | 983.65 | 0.00 | 0.00 | 0.00 |
May | 1192.41 | 186.56 | 1005.85 | 929.89 | 443.93 | 0.00 | 0.00 | 0.00 |
June | 1558.03 | 344.60 | 1213.42 | 1554.23 | 206.58 | 0.00 | 0.00 | 0.00 |
July | 1307.22 | 210.43 | 1096.79 | 1332.81 | 251.69 | 0.00 | 0.00 | 0.00 |
August | 834.66 | 45.12 | 789.54 | 688.67 | 421.24 | 0.00 | 0.00 | 0.00 |
September | 466.49 | 0.41 | 466.08 | 176.74 | 843.14 | 0.00 | 0.00 | 0.00 |
October | 227.02 | 0.00 | 227.02 | 16.75 | 1552.14 | 0.00 | 0.00 | 0.00 |
November | 70.45 | 0.00 | 70.45 | 0.00 | 2680.73 | 0.00 | 0.00 | 0.00 |
December | 11.07 | 0.00 | 11.07 | 0.00 | 2879.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 591.75 | 67.24 | 524.52 | 424.13 | 1432.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 11.07 | 0.00 | 11.07 | 0.00 | 206.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1558.03 | 344.60 | 1213.42 | 1554.23 | 2879.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.49 | 19.59 | 43.90 | 5.64 | 1767.88 | 0.00 | 0.00 | 0.00 |
February | 353.15 | 168.09 | 185.07 | 190.48 | 1475.48 | 0.00 | 0.00 | 0.00 |
March | 1010.87 | 512.52 | 498.35 | 873.63 | 1086.49 | 0.00 | 0.00 | 0.00 |
April | 1390.14 | 704.41 | 685.73 | 1311.47 | 604.73 | 0.00 | 0.00 | 0.00 |
May | 2022.20 | 1141.06 | 881.14 | 2255.08 | 318.98 | 0.00 | 0.00 | 0.00 |
June | 1858.92 | 868.19 | 990.73 | 2144.83 | 157.37 | 0.00 | 0.00 | 0.00 |
July | 1766.08 | 857.41 | 908.67 | 2088.46 | 180.33 | 0.00 | 0.00 | 0.00 |
August | 1398.44 | 681.60 | 716.84 | 1580.27 | 282.40 | 0.00 | 0.00 | 0.00 |
September | 864.39 | 379.00 | 485.39 | 818.75 | 525.81 | 0.00 | 0.00 | 0.00 |
October | 455.79 | 182.76 | 273.03 | 333.34 | 941.12 | 0.00 | 0.00 | 0.00 |
November | 96.27 | 33.16 | 63.10 | 7.88 | 1720.04 | 0.00 | 0.00 | 0.00 |
December | 13.69 | 3.15 | 10.54 | 0.00 | 1907.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 944.73 | 464.63 | 480.10 | 972.74 | 911.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.69 | 3.15 | 10.54 | 0.00 | 157.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2022.20 | 1141.06 | 990.73 | 2255.08 | 1907.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 440.54 | 291.23 | 149.31 | 263.84 | 2456.36 | 0.00 | 0.00 | 0.00 |
February | 1515.33 | 1056.92 | 458.41 | 1316.78 | 1978.11 | 0.00 | 0.00 | 0.00 |
March | 2596.40 | 1763.21 | 833.19 | 2602.15 | 1524.96 | 0.00 | 0.00 | 0.00 |
April | 3160.54 | 1968.32 | 1192.22 | 3524.08 | 1013.66 | 0.00 | 0.00 | 0.00 |
May | 2597.01 | 1343.51 | 1253.50 | 2976.04 | 559.92 | 0.00 | 0.00 | 0.00 |
June | 2368.32 | 966.63 | 1401.69 | 2791.82 | 300.29 | 0.00 | 0.00 | 0.00 |
July | 2283.82 | 991.98 | 1291.84 | 2757.95 | 319.13 | 0.00 | 0.00 | 0.00 |
August | 2371.89 | 1308.06 | 1063.83 | 2820.13 | 469.79 | 0.00 | 0.00 | 0.00 |
September | 1920.85 | 1159.03 | 761.82 | 2072.99 | 810.48 | 0.00 | 0.00 | 0.00 |
October | 1385.89 | 881.81 | 504.08 | 1292.03 | 1311.51 | 0.00 | 0.00 | 0.00 |
November | 744.48 | 521.37 | 223.11 | 505.65 | 2295.01 | 0.00 | 0.00 | 0.00 |
December | 132.20 | 93.47 | 38.74 | 23.87 | 2737.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1792.59 | 1027.19 | 765.40 | 1913.76 | 1311.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 132.20 | 93.47 | 38.74 | 23.87 | 300.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3160.54 | 1968.32 | 1401.69 | 3524.08 | 2737.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.45 | 5.76 | 27.69 | 0.00 | 1802.31 | 0.00 | 0.00 | 0.00 |
February | 197.96 | 68.19 | 129.76 | 41.66 | 1533.66 | 0.00 | 0.00 | 0.00 |
March | 596.51 | 256.08 | 340.43 | 352.18 | 1112.77 | 0.00 | 0.00 | 0.00 |
April | 1419.34 | 736.68 | 682.66 | 1392.50 | 653.06 | 0.00 | 0.00 | 0.00 |
May | 1380.27 | 629.96 | 750.31 | 1430.46 | 343.60 | 0.00 | 0.00 | 0.00 |
June | 1512.43 | 646.30 | 866.13 | 1703.81 | 185.72 | 0.00 | 0.00 | 0.00 |
July | 1264.93 | 479.46 | 785.47 | 1437.60 | 200.74 | 0.00 | 0.00 | 0.00 |
August | 1039.46 | 440.80 | 598.66 | 1119.79 | 299.46 | 0.00 | 0.00 | 0.00 |
September | 628.72 | 263.46 | 365.26 | 527.53 | 541.21 | 0.00 | 0.00 | 0.00 |
October | 245.38 | 73.26 | 172.12 | 94.60 | 981.41 | 0.00 | 0.00 | 0.00 |
November | 97.77 | 35.08 | 62.69 | 10.74 | 1715.72 | 0.00 | 0.00 | 0.00 |
December | 8.78 | 0.87 | 7.91 | 0.00 | 1913.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 703.90 | 303.64 | 400.26 | 678.57 | 937.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 8.78 | 0.87 | 7.91 | 0.00 | 185.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1512.43 | 736.68 | 866.13 | 1703.81 | 1913.33 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97708504.74 | 0.00 | 97708504.74 | 0.00 | 0.719313E+10 |
February | 0.390120E+09 | 0.00 | 0.390120E+09 | 0.00 | 0.579159E+10 |
March | 0.115520E+10 | 0.00 | 0.115520E+10 | 0.111590E+09 | 0.470405E+10 |
April | 0.202007E+10 | 41949790.24 | 0.197812E+10 | 0.885509E+09 | 0.240489E+10 |
May | 0.319376E+10 | 0.499680E+09 | 0.269408E+10 | 0.255471E+10 | 0.113365E+10 |
June | 0.403840E+10 | 0.893210E+09 | 0.314519E+10 | 0.404770E+10 | 0.516950E+09 |
July | 0.350125E+10 | 0.563609E+09 | 0.293764E+10 | 0.359061E+10 | 0.649969E+09 |
August | 0.223555E+10 | 0.120851E+09 | 0.211470E+10 | 0.188569E+10 | 0.106995E+10 |
September | 0.120915E+10 | 1071841.51 | 0.120807E+10 | 0.511074E+09 | 0.201897E+10 |
October | 0.608042E+09 | 0.00 | 0.608042E+09 | 57573969.40 | 0.396084E+10 |
November | 0.182610E+09 | 0.00 | 0.182610E+09 | 0.00 | 0.680184E+10 |
December | 29639659.08 | 0.00 | 29639659.08 | 0.00 | 0.757870E+10 |
Annual Sum or Average | 0.186615E+11 | 0.212037E+10 | 0.165411E+11 | 0.136445E+11 | 0.438245E+11 |
Minimum of Months | 29639659.08 | 0.00 | 29639659.08 | 0.00 | 0.516950E+09 |
Maximum of Months | 0.403840E+10 | 0.893210E+09 | 0.314519E+10 | 0.404770E+10 | 0.757870E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170062E+09 | 52471550.32 | 0.117591E+09 | 15501003.19 | 0.465375E+10 |
February | 0.854344E+09 | 0.406635E+09 | 0.447709E+09 | 0.468123E+09 | 0.349087E+10 |
March | 0.270751E+10 | 0.137273E+10 | 0.133478E+10 | 0.236318E+10 | 0.281348E+10 |
April | 0.360324E+10 | 0.182584E+10 | 0.177740E+10 | 0.343641E+10 | 0.148993E+10 |
May | 0.541625E+10 | 0.305622E+10 | 0.236004E+10 | 0.606205E+10 | 0.822176E+09 |
June | 0.481831E+10 | 0.225035E+10 | 0.256796E+10 | 0.556602E+10 | 0.395788E+09 |
July | 0.473027E+10 | 0.229649E+10 | 0.243378E+10 | 0.560074E+10 | 0.468076E+09 |
August | 0.374559E+10 | 0.182559E+10 | 0.192000E+10 | 0.424886E+10 | 0.724757E+09 |
September | 0.224050E+10 | 0.982359E+09 | 0.125814E+10 | 0.216110E+10 | 0.127424E+10 |
October | 0.122079E+10 | 0.489516E+09 | 0.731272E+09 | 0.914107E+09 | 0.240092E+10 |
November | 0.249524E+09 | 85961234.00 | 0.163563E+09 | 21353157.93 | 0.436560E+10 |
December | 36671077.03 | 8439139.61 | 28231937.42 | 0.00 | 0.502513E+10 |
Annual Sum or Average | 0.297931E+11 | 0.146526E+11 | 0.151405E+11 | 0.308574E+11 | 0.279247E+11 |
Minimum of Months | 36671077.03 | 8439139.61 | 28231937.42 | 0.00 | 0.395788E+09 |
Maximum of Months | 0.541625E+10 | 0.305622E+10 | 0.256796E+10 | 0.606205E+10 | 0.502513E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117993E+10 | 0.780028E+09 | 0.399904E+09 | 0.714742E+09 | 0.645863E+10 |
February | 0.366588E+10 | 0.255691E+10 | 0.110897E+10 | 0.321218E+10 | 0.466472E+10 |
March | 0.695419E+10 | 0.472258E+10 | 0.223161E+10 | 0.700971E+10 | 0.393753E+10 |
April | 0.819212E+10 | 0.510188E+10 | 0.309024E+10 | 0.917331E+10 | 0.250036E+10 |
May | 0.695583E+10 | 0.359846E+10 | 0.335737E+10 | 0.799416E+10 | 0.142721E+10 |
June | 0.613867E+10 | 0.250550E+10 | 0.363317E+10 | 0.724357E+10 | 0.748327E+09 |
July | 0.611699E+10 | 0.265693E+10 | 0.346006E+10 | 0.739605E+10 | 0.822022E+09 |
August | 0.635288E+10 | 0.350352E+10 | 0.284936E+10 | 0.757310E+10 | 0.119813E+10 |
September | 0.497885E+10 | 0.300420E+10 | 0.197465E+10 | 0.542531E+10 | 0.196460E+10 |
October | 0.371197E+10 | 0.236185E+10 | 0.135013E+10 | 0.350826E+10 | 0.333804E+10 |
November | 0.192969E+10 | 0.135139E+10 | 0.578293E+09 | 0.132692E+10 | 0.581046E+10 |
December | 0.354090E+09 | 0.250338E+09 | 0.103752E+09 | 65101313.73 | 0.720380E+10 |
Annual Sum or Average | 0.565311E+11 | 0.323936E+11 | 0.241375E+11 | 0.606424E+11 | 0.400738E+11 |
Minimum of Months | 0.354090E+09 | 0.250338E+09 | 0.103752E+09 | 65101313.73 | 0.748327E+09 |
Maximum of Months | 0.819212E+10 | 0.510188E+10 | 0.363317E+10 | 0.917331E+10 | 0.720380E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89590715.39 | 15434927.31 | 74155788.08 | 0.00 | 0.474629E+10 |
February | 0.478894E+09 | 0.164969E+09 | 0.313925E+09 | 0.102919E+09 | 0.362956E+10 |
March | 0.159769E+10 | 0.685885E+09 | 0.911805E+09 | 0.955053E+09 | 0.287970E+10 |
April | 0.367893E+10 | 0.190947E+10 | 0.176947E+10 | 0.363801E+10 | 0.160540E+10 |
May | 0.369690E+10 | 0.168727E+10 | 0.200963E+10 | 0.385579E+10 | 0.873513E+09 |
June | 0.392023E+10 | 0.167521E+10 | 0.224502E+10 | 0.442366E+10 | 0.462763E+09 |
July | 0.338798E+10 | 0.128418E+10 | 0.210380E+10 | 0.385968E+10 | 0.516562E+09 |
August | 0.278408E+10 | 0.118063E+10 | 0.160345E+10 | 0.301978E+10 | 0.761417E+09 |
September | 0.162964E+10 | 0.682893E+09 | 0.946743E+09 | 0.140143E+10 | 0.130584E+10 |
October | 0.657221E+09 | 0.196223E+09 | 0.460998E+09 | 0.266247E+09 | 0.250454E+10 |
November | 0.253423E+09 | 90929198.28 | 0.162494E+09 | 28968658.28 | 0.435499E+10 |
December | 23518703.94 | 2330467.50 | 21188236.44 | 0.00 | 0.504150E+10 |
Annual Sum or Average | 0.221981E+11 | 0.957543E+10 | 0.126227E+11 | 0.215515E+11 | 0.286821E+11 |
Minimum of Months | 23518703.94 | 2330467.50 | 21188236.44 | 0.00 | 0.462763E+09 |
Maximum of Months | 0.392023E+10 | 0.190947E+10 | 0.224502E+10 | 0.442366E+10 | 0.504150E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32567960.65 | 0.00 | 32567960.65 | 0.00 | 0.240668E+10 |
February | 0.130034E+09 | 0.00 | 0.130034E+09 | 0.00 | 0.192959E+10 |
March | 0.385047E+09 | 0.00 | 0.385047E+09 | 38858571.96 | 0.156935E+10 |
April | 0.673325E+09 | 13982601.84 | 0.659342E+09 | 0.313464E+09 | 0.797437E+09 |
May | 0.106454E+10 | 0.166552E+09 | 0.897983E+09 | 0.887300E+09 | 0.365506E+09 |
June | 0.134607E+10 | 0.297723E+09 | 0.104835E+10 | 0.137759E+10 | 0.165571E+09 |
July | 0.116703E+10 | 0.187861E+09 | 0.979166E+09 | 0.121321E+10 | 0.214012E+09 |
August | 0.745147E+09 | 40281597.95 | 0.704866E+09 | 0.627668E+09 | 0.366800E+09 |
September | 0.403030E+09 | 357263.60 | 0.402672E+09 | 0.157818E+09 | 0.725191E+09 |
October | 0.202671E+09 | 0.00 | 0.202671E+09 | 15413157.89 | 0.139172E+10 |
November | 60867197.34 | 0.00 | 60867197.34 | 0.00 | 0.231494E+10 |
December | 9879418.92 | 0.00 | 9879418.92 | 0.00 | 0.255250E+10 |
Annual Sum or Average | 0.622020E+10 | 0.706757E+09 | 0.551344E+10 | 0.463133E+10 | 0.147993E+11 |
Minimum of Months | 9879418.92 | 0.00 | 9879418.92 | 0.00 | 0.165571E+09 |
Maximum of Months | 0.134607E+10 | 0.297723E+09 | 0.104835E+10 | 0.137759E+10 | 0.255250E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32570018.89 | 0.00 | 32570018.89 | 0.00 | 0.240683E+10 |
February | 0.130042E+09 | 0.00 | 0.130042E+09 | 0.00 | 0.192971E+10 |
March | 0.385071E+09 | 0.00 | 0.385071E+09 | 38861027.76 | 0.156945E+10 |
April | 0.673367E+09 | 13983485.51 | 0.659384E+09 | 0.313484E+09 | 0.797487E+09 |
May | 0.106460E+10 | 0.166563E+09 | 0.898040E+09 | 0.887356E+09 | 0.365529E+09 |
June | 0.134616E+10 | 0.297741E+09 | 0.104841E+10 | 0.137768E+10 | 0.165582E+09 |
July | 0.116710E+10 | 0.187873E+09 | 0.979228E+09 | 0.121329E+10 | 0.214025E+09 |
August | 0.745194E+09 | 40284143.68 | 0.704910E+09 | 0.627708E+09 | 0.366823E+09 |
September | 0.403055E+09 | 357286.18 | 0.402698E+09 | 0.157828E+09 | 0.725237E+09 |
October | 0.202684E+09 | 0.00 | 0.202684E+09 | 15414131.98 | 0.139181E+10 |
November | 60871044.04 | 0.00 | 60871044.04 | 0.00 | 0.231508E+10 |
December | 9880043.28 | 0.00 | 9880043.28 | 0.00 | 0.255266E+10 |
Annual Sum or Average | 0.622059E+10 | 0.706802E+09 | 0.551379E+10 | 0.463162E+10 | 0.148002E+11 |
Minimum of Months | 9880043.28 | 0.00 | 9880043.28 | 0.00 | 0.165582E+09 |
Maximum of Months | 0.134616E+10 | 0.297741E+09 | 0.104841E+10 | 0.137768E+10 | 0.255266E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 32570018.89 | 0.00 | 32570018.89 | 0.00 | 0.240683E+10 |
February | 0.130042E+09 | 0.00 | 0.130042E+09 | 0.00 | 0.192971E+10 |
March | 0.385071E+09 | 0.00 | 0.385071E+09 | 38861027.76 | 0.156945E+10 |
April | 0.673367E+09 | 13983485.51 | 0.659384E+09 | 0.313484E+09 | 0.797487E+09 |
May | 0.106460E+10 | 0.166563E+09 | 0.898040E+09 | 0.887356E+09 | 0.365529E+09 |
June | 0.134616E+10 | 0.297741E+09 | 0.104841E+10 | 0.137768E+10 | 0.165582E+09 |
July | 0.116710E+10 | 0.187873E+09 | 0.979228E+09 | 0.121329E+10 | 0.214025E+09 |
August | 0.745194E+09 | 40284143.68 | 0.704910E+09 | 0.627708E+09 | 0.366823E+09 |
September | 0.403055E+09 | 357286.18 | 0.402698E+09 | 0.157828E+09 | 0.725237E+09 |
October | 0.202684E+09 | 0.00 | 0.202684E+09 | 15414131.98 | 0.139181E+10 |
November | 60871044.04 | 0.00 | 60871044.04 | 0.00 | 0.231508E+10 |
December | 9880043.28 | 0.00 | 9880043.28 | 0.00 | 0.255266E+10 |
Annual Sum or Average | 0.622059E+10 | 0.706802E+09 | 0.551379E+10 | 0.463162E+10 | 0.148002E+11 |
Minimum of Months | 9880043.28 | 0.00 | 9880043.28 | 0.00 | 0.165582E+09 |
Maximum of Months | 0.134616E+10 | 0.297741E+09 | 0.104841E+10 | 0.137768E+10 | 0.255266E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163593E+09 | 50475273.29 | 0.113117E+09 | 15351934.58 | 0.449858E+10 |
February | 0.821841E+09 | 0.391164E+09 | 0.430677E+09 | 0.452659E+09 | 0.336583E+10 |
March | 0.260451E+10 | 0.132050E+10 | 0.128400E+10 | 0.229047E+10 | 0.272869E+10 |
April | 0.346616E+10 | 0.175637E+10 | 0.170979E+10 | 0.333298E+10 | 0.146017E+10 |
May | 0.521020E+10 | 0.293994E+10 | 0.227026E+10 | 0.586448E+10 | 0.806291E+09 |
June | 0.463501E+10 | 0.216473E+10 | 0.247027E+10 | 0.539196E+10 | 0.380517E+09 |
July | 0.455032E+10 | 0.220912E+10 | 0.234120E+10 | 0.540804E+10 | 0.461897E+09 |
August | 0.360309E+10 | 0.175613E+10 | 0.184696E+10 | 0.408534E+10 | 0.736910E+09 |
September | 0.215526E+10 | 0.944985E+09 | 0.121028E+10 | 0.203936E+10 | 0.134516E+10 |
October | 0.117435E+10 | 0.470893E+09 | 0.703453E+09 | 0.860781E+09 | 0.245255E+10 |
November | 0.240031E+09 | 82690843.92 | 0.157341E+09 | 20044637.47 | 0.428505E+10 |
December | 35275982.59 | 8118073.04 | 27157909.55 | 0.00 | 0.488001E+10 |
Annual Sum or Average | 0.286596E+11 | 0.140951E+11 | 0.145645E+11 | 0.297615E+11 | 0.274017E+11 |
Minimum of Months | 35275982.59 | 8118073.04 | 27157909.55 | 0.00 | 0.380517E+09 |
Maximum of Months | 0.521020E+10 | 0.293994E+10 | 0.247027E+10 | 0.586448E+10 | 0.488001E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 6468300.30 | 1995746.86 | 4472553.44 | 607001.67 | 0.177870E+09 |
February | 32494870.98 | 15466278.76 | 17028592.22 | 17897740.98 | 0.133082E+09 |
March | 0.102980E+09 | 52211428.51 | 50768392.55 | 90563292.18 | 0.107890E+09 |
April | 0.137049E+09 | 69445426.46 | 67603518.72 | 0.131783E+09 | 57734002.63 |
May | 0.206007E+09 | 0.116243E+09 | 89763951.97 | 0.231876E+09 | 31880007.77 |
June | 0.183264E+09 | 85591524.55 | 97672421.35 | 0.213193E+09 | 15045301.04 |
July | 0.179915E+09 | 87346596.12 | 92568763.09 | 0.213829E+09 | 18262974.85 |
August | 0.142463E+09 | 69435992.07 | 73027023.66 | 0.161531E+09 | 29136742.61 |
September | 85217228.39 | 37363855.42 | 47853372.97 | 80634282.67 | 53186532.16 |
October | 46432564.91 | 18618675.74 | 27813889.17 | 34034488.35 | 96971543.10 |
November | 9490627.23 | 3269521.52 | 6221105.71 | 792546.92 | 0.169427E+09 |
December | 1394780.59 | 320981.30 | 1073799.29 | 0.00 | 0.192951E+09 |
Annual Sum or Average | 0.113318E+10 | 0.557309E+09 | 0.575867E+09 | 0.117674E+10 | 0.108344E+10 |
Minimum of Months | 1394780.59 | 320981.30 | 1073799.29 | 0.00 | 15045301.04 |
Maximum of Months | 0.206007E+09 | 0.116243E+09 | 97672421.35 | 0.231876E+09 | 0.192951E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.393323E+09 | 0.260018E+09 | 0.133306E+09 | 0.250243E+09 | 0.207082E+10 |
February | 0.122200E+10 | 0.852330E+09 | 0.369670E+09 | 0.109482E+10 | 0.151769E+10 |
March | 0.231814E+10 | 0.157424E+10 | 0.743892E+09 | 0.238490E+10 | 0.129922E+10 |
April | 0.273079E+10 | 0.170068E+10 | 0.103011E+10 | 0.309340E+10 | 0.852957E+09 |
May | 0.231868E+10 | 0.119953E+10 | 0.111916E+10 | 0.270123E+10 | 0.478688E+09 |
June | 0.204629E+10 | 0.835195E+09 | 0.121109E+10 | 0.244459E+10 | 0.247410E+09 |
July | 0.203906E+10 | 0.885673E+09 | 0.115339E+10 | 0.248399E+10 | 0.279372E+09 |
August | 0.211769E+10 | 0.116788E+10 | 0.949815E+09 | 0.253732E+10 | 0.421475E+09 |
September | 0.165967E+10 | 0.100143E+10 | 0.658235E+09 | 0.180829E+10 | 0.707897E+09 |
October | 0.123736E+10 | 0.787308E+09 | 0.450056E+09 | 0.116957E+10 | 0.116358E+10 |
November | 0.643250E+09 | 0.450480E+09 | 0.192770E+09 | 0.456068E+09 | 0.190676E+10 |
December | 0.118034E+09 | 83448652.49 | 34585089.26 | 27401630.40 | 0.230950E+10 |
Annual Sum or Average | 0.188443E+11 | 0.107982E+11 | 0.804607E+10 | 0.204518E+11 | 0.132554E+11 |
Minimum of Months | 0.118034E+09 | 83448652.49 | 34585089.26 | 27401630.40 | 0.247410E+09 |
Maximum of Months | 0.273079E+10 | 0.170068E+10 | 0.121109E+10 | 0.309340E+10 | 0.230950E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.393323E+09 | 0.260018E+09 | 0.133306E+09 | 0.250243E+09 | 0.207082E+10 |
February | 0.122200E+10 | 0.852330E+09 | 0.369670E+09 | 0.109482E+10 | 0.151769E+10 |
March | 0.231814E+10 | 0.157424E+10 | 0.743892E+09 | 0.238490E+10 | 0.129922E+10 |
April | 0.273079E+10 | 0.170068E+10 | 0.103011E+10 | 0.309340E+10 | 0.852957E+09 |
May | 0.231868E+10 | 0.119953E+10 | 0.111916E+10 | 0.270123E+10 | 0.478688E+09 |
June | 0.204629E+10 | 0.835195E+09 | 0.121109E+10 | 0.244459E+10 | 0.247410E+09 |
July | 0.203906E+10 | 0.885673E+09 | 0.115339E+10 | 0.248399E+10 | 0.279372E+09 |
August | 0.211769E+10 | 0.116788E+10 | 0.949815E+09 | 0.253732E+10 | 0.421475E+09 |
September | 0.165967E+10 | 0.100143E+10 | 0.658235E+09 | 0.180829E+10 | 0.707897E+09 |
October | 0.123736E+10 | 0.787308E+09 | 0.450056E+09 | 0.116957E+10 | 0.116358E+10 |
November | 0.643250E+09 | 0.450480E+09 | 0.192770E+09 | 0.456068E+09 | 0.190676E+10 |
December | 0.118034E+09 | 83448652.49 | 34585089.26 | 27401630.40 | 0.230950E+10 |
Annual Sum or Average | 0.188443E+11 | 0.107982E+11 | 0.804607E+10 | 0.204518E+11 | 0.132554E+11 |
Minimum of Months | 0.118034E+09 | 83448652.49 | 34585089.26 | 27401630.40 | 0.247410E+09 |
Maximum of Months | 0.273079E+10 | 0.170068E+10 | 0.121109E+10 | 0.309340E+10 | 0.230950E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.393299E+09 | 0.260001E+09 | 0.133297E+09 | 0.250228E+09 | 0.207069E+10 |
February | 0.122192E+10 | 0.852276E+09 | 0.369646E+09 | 0.109475E+10 | 0.151759E+10 |
March | 0.231799E+10 | 0.157415E+10 | 0.743845E+09 | 0.238475E+10 | 0.129914E+10 |
April | 0.273062E+10 | 0.170058E+10 | 0.103004E+10 | 0.309320E+10 | 0.852903E+09 |
May | 0.231853E+10 | 0.119945E+10 | 0.111908E+10 | 0.270106E+10 | 0.478657E+09 |
June | 0.204616E+10 | 0.835142E+09 | 0.121101E+10 | 0.244444E+10 | 0.247395E+09 |
July | 0.203893E+10 | 0.885617E+09 | 0.115331E+10 | 0.248383E+10 | 0.279354E+09 |
August | 0.211756E+10 | 0.116780E+10 | 0.949755E+09 | 0.253716E+10 | 0.421449E+09 |
September | 0.165956E+10 | 0.100137E+10 | 0.658193E+09 | 0.180817E+10 | 0.707852E+09 |
October | 0.123729E+10 | 0.787258E+09 | 0.450028E+09 | 0.116950E+10 | 0.116350E+10 |
November | 0.643209E+09 | 0.450451E+09 | 0.192758E+09 | 0.456040E+09 | 0.190664E+10 |
December | 0.118026E+09 | 83443379.01 | 34582903.68 | 27399898.77 | 0.230936E+10 |
Annual Sum or Average | 0.188431E+11 | 0.107975E+11 | 0.804556E+10 | 0.204505E+11 | 0.132545E+11 |
Minimum of Months | 0.118026E+09 | 83443379.01 | 34582903.68 | 27399898.77 | 0.247395E+09 |
Maximum of Months | 0.273062E+10 | 0.170058E+10 | 0.121101E+10 | 0.309320E+10 | 0.230936E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 86182469.88 | 14847709.94 | 71334759.94 | 0.00 | 0.458835E+10 |
February | 0.460676E+09 | 0.158693E+09 | 0.301983E+09 | 0.101100E+09 | 0.349821E+10 |
March | 0.153691E+10 | 0.659790E+09 | 0.877119E+09 | 0.936060E+09 | 0.278356E+10 |
April | 0.353898E+10 | 0.183682E+10 | 0.170215E+10 | 0.353550E+10 | 0.157746E+10 |
May | 0.355626E+10 | 0.162308E+10 | 0.193318E+10 | 0.375532E+10 | 0.841079E+09 |
June | 0.377110E+10 | 0.161148E+10 | 0.215961E+10 | 0.429482E+10 | 0.440873E+09 |
July | 0.325910E+10 | 0.123532E+10 | 0.202377E+10 | 0.373616E+10 | 0.501104E+09 |
August | 0.267817E+10 | 0.113571E+10 | 0.154245E+10 | 0.289953E+10 | 0.771484E+09 |
September | 0.156764E+10 | 0.656913E+09 | 0.910727E+09 | 0.131815E+10 | 0.136727E+10 |
October | 0.632218E+09 | 0.188758E+09 | 0.443461E+09 | 0.245047E+09 | 0.254475E+10 |
November | 0.243782E+09 | 87469823.09 | 0.156312E+09 | 27067266.63 | 0.427674E+10 |
December | 22623995.26 | 2241805.53 | 20382189.73 | 0.00 | 0.489650E+10 |
Annual Sum or Average | 0.213536E+11 | 0.921114E+10 | 0.121425E+11 | 0.208487E+11 | 0.280874E+11 |
Minimum of Months | 22623995.26 | 2241805.53 | 20382189.73 | 0.00 | 0.440873E+09 |
Maximum of Months | 0.377110E+10 | 0.183682E+10 | 0.215961E+10 | 0.429482E+10 | 0.489650E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 3407568.05 | 587063.18 | 2820504.87 | 0.00 | 0.181419E+09 |
February | 18214650.45 | 6274550.47 | 11940099.99 | 3997384.36 | 0.138316E+09 |
March | 60767861.53 | 26087431.10 | 34680430.43 | 37010775.66 | 0.110059E+09 |
April | 0.139928E+09 | 72626104.47 | 67301434.43 | 0.139790E+09 | 62371178.63 |
May | 0.140611E+09 | 64175033.93 | 76436079.73 | 0.148481E+09 | 33255510.11 |
June | 0.149105E+09 | 63716306.96 | 85388989.40 | 0.169813E+09 | 17431734.82 |
July | 0.128861E+09 | 48843474.48 | 80017972.56 | 0.147724E+09 | 19813206.18 |
August | 0.105892E+09 | 44904978.07 | 60987105.46 | 0.114644E+09 | 30503779.25 |
September | 61982903.64 | 25973651.54 | 36009252.10 | 52118224.62 | 54060467.96 |
October | 24997278.80 | 7463277.52 | 17534001.28 | 9688896.30 | 0.100617E+09 |
November | 9638890.07 | 3458466.84 | 6180423.24 | 1070203.15 | 0.169098E+09 |
December | 894529.98 | 88638.68 | 805891.29 | 0.00 | 0.193603E+09 |
Annual Sum or Average | 0.844301E+09 | 0.364199E+09 | 0.480102E+09 | 0.824338E+09 | 0.111055E+10 |
Minimum of Months | 894529.98 | 88638.68 | 805891.29 | 0.00 | 17431734.82 |
Maximum of Months | 0.149105E+09 | 72626104.47 | 85388989.40 | 0.169813E+09 | 0.193603E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 97708504.74 | 0.00 | 97708504.74 | 0.00 | 0.732149E+10 |
February | 0.390120E+09 | 0.00 | 0.390120E+09 | 0.00 | 0.592007E+10 |
March | 0.115520E+10 | 0.00 | 0.115520E+10 | 0.102941E+09 | 0.486433E+10 |
April | 0.202007E+10 | 41949790.24 | 0.197812E+10 | 0.836029E+09 | 0.254961E+10 |
May | 0.319376E+10 | 0.499680E+09 | 0.269408E+10 | 0.249063E+10 | 0.118903E+10 |
June | 0.403840E+10 | 0.893210E+09 | 0.314519E+10 | 0.402858E+10 | 0.535457E+09 |
July | 0.350125E+10 | 0.563609E+09 | 0.293764E+10 | 0.356980E+10 | 0.674133E+09 |
August | 0.223555E+10 | 0.120851E+09 | 0.211470E+10 | 0.184453E+10 | 0.112825E+10 |
September | 0.120915E+10 | 1071841.51 | 0.120807E+10 | 0.458100E+09 | 0.218541E+10 |
October | 0.608042E+09 | 0.00 | 0.608042E+09 | 44859791.61 | 0.415724E+10 |
November | 0.182610E+09 | 0.00 | 0.182610E+09 | 0.00 | 0.694846E+10 |
December | 29639659.08 | 0.00 | 29639659.08 | 0.00 | 0.771319E+10 |
Annual Sum or Average | 0.186615E+11 | 0.212037E+10 | 0.165411E+11 | 0.133755E+11 | 0.451867E+11 |
Minimum of Months | 29639659.08 | 0.00 | 29639659.08 | 0.00 | 0.535457E+09 |
Maximum of Months | 0.403840E+10 | 0.893210E+09 | 0.314519E+10 | 0.402858E+10 | 0.771319E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170062E+09 | 52471550.32 | 0.117591E+09 | 15115822.99 | 0.473509E+10 |
February | 0.854344E+09 | 0.406635E+09 | 0.447709E+09 | 0.460812E+09 | 0.356947E+10 |
March | 0.270751E+10 | 0.137273E+10 | 0.133478E+10 | 0.233992E+10 | 0.291004E+10 |
April | 0.360324E+10 | 0.182584E+10 | 0.177740E+10 | 0.339933E+10 | 0.156747E+10 |
May | 0.541625E+10 | 0.305622E+10 | 0.236004E+10 | 0.604002E+10 | 0.854343E+09 |
June | 0.481831E+10 | 0.225035E+10 | 0.256796E+10 | 0.555941E+10 | 0.407897E+09 |
July | 0.473027E+10 | 0.229649E+10 | 0.243378E+10 | 0.559373E+10 | 0.483006E+09 |
August | 0.374559E+10 | 0.182559E+10 | 0.192000E+10 | 0.423261E+10 | 0.756393E+09 |
September | 0.224050E+10 | 0.982359E+09 | 0.125814E+10 | 0.212219E+10 | 0.136289E+10 |
October | 0.122079E+10 | 0.489516E+09 | 0.731272E+09 | 0.892823E+09 | 0.252069E+10 |
November | 0.249524E+09 | 85961234.00 | 0.163563E+09 | 20425878.53 | 0.445835E+10 |
December | 36671077.03 | 8439139.61 | 28231937.42 | 0.00 | 0.510889E+10 |
Annual Sum or Average | 0.297931E+11 | 0.146526E+11 | 0.151405E+11 | 0.306764E+11 | 0.287345E+11 |
Minimum of Months | 36671077.03 | 8439139.61 | 28231937.42 | 0.00 | 0.407897E+09 |
Maximum of Months | 0.541625E+10 | 0.305622E+10 | 0.256796E+10 | 0.604002E+10 | 0.510889E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117993E+10 | 0.780028E+09 | 0.399904E+09 | 0.706681E+09 | 0.657910E+10 |
February | 0.366588E+10 | 0.255691E+10 | 0.110897E+10 | 0.318555E+10 | 0.478543E+10 |
March | 0.695419E+10 | 0.472258E+10 | 0.223161E+10 | 0.696959E+10 | 0.408446E+10 |
April | 0.819212E+10 | 0.510188E+10 | 0.309024E+10 | 0.913442E+10 | 0.262742E+10 |
May | 0.695583E+10 | 0.359846E+10 | 0.335737E+10 | 0.797101E+10 | 0.149970E+10 |
June | 0.613867E+10 | 0.250550E+10 | 0.363317E+10 | 0.723641E+10 | 0.778346E+09 |
July | 0.611699E+10 | 0.265693E+10 | 0.346006E+10 | 0.738689E+10 | 0.854748E+09 |
August | 0.635288E+10 | 0.350352E+10 | 0.284936E+10 | 0.755345E+10 | 0.125828E+10 |
September | 0.497885E+10 | 0.300420E+10 | 0.197465E+10 | 0.537319E+10 | 0.210075E+10 |
October | 0.371197E+10 | 0.236185E+10 | 0.135013E+10 | 0.346056E+10 | 0.351274E+10 |
November | 0.192969E+10 | 0.135139E+10 | 0.578293E+09 | 0.131064E+10 | 0.594867E+10 |
December | 0.354090E+09 | 0.250338E+09 | 0.103752E+09 | 63933215.46 | 0.733331E+10 |
Annual Sum or Average | 0.565311E+11 | 0.323936E+11 | 0.241375E+11 | 0.603523E+11 | 0.413630E+11 |
Minimum of Months | 0.354090E+09 | 0.250338E+09 | 0.103752E+09 | 63933215.46 | 0.778346E+09 |
Maximum of Months | 0.819212E+10 | 0.510188E+10 | 0.363317E+10 | 0.913442E+10 | 0.733331E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89590715.39 | 15434927.31 | 74155788.08 | 0.00 | 0.482731E+10 |
February | 0.478894E+09 | 0.164969E+09 | 0.313925E+09 | 0.100789E+09 | 0.371024E+10 |
March | 0.159769E+10 | 0.685885E+09 | 0.911805E+09 | 0.943273E+09 | 0.298044E+10 |
April | 0.367893E+10 | 0.190947E+10 | 0.176947E+10 | 0.360936E+10 | 0.169272E+10 |
May | 0.369690E+10 | 0.168727E+10 | 0.200963E+10 | 0.383135E+10 | 0.920286E+09 |
June | 0.392023E+10 | 0.167521E+10 | 0.224502E+10 | 0.441628E+10 | 0.481395E+09 |
July | 0.338798E+10 | 0.128418E+10 | 0.210380E+10 | 0.385046E+10 | 0.537668E+09 |
August | 0.278408E+10 | 0.118063E+10 | 0.160345E+10 | 0.299925E+10 | 0.802074E+09 |
September | 0.162964E+10 | 0.682893E+09 | 0.946743E+09 | 0.136736E+10 | 0.140281E+10 |
October | 0.657221E+09 | 0.196223E+09 | 0.460998E+09 | 0.253372E+09 | 0.262860E+10 |
November | 0.253423E+09 | 90929198.28 | 0.162494E+09 | 27850407.27 | 0.444716E+10 |
December | 23518703.94 | 2330467.50 | 21188236.44 | 0.00 | 0.512466E+10 |
Annual Sum or Average | 0.221981E+11 | 0.957543E+10 | 0.126227E+11 | 0.213993E+11 | 0.295554E+11 |
Minimum of Months | 23518703.94 | 2330467.50 | 21188236.44 | 0.00 | 0.481395E+09 |
Maximum of Months | 0.392023E+10 | 0.190947E+10 | 0.224502E+10 | 0.441628E+10 | 0.512466E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2685.61 | 36.48 | 0.00 | 36.48 | 0.00 | 0.00 |
February | 0.00 | 2394.01 | 161.26 | 0.00 | 161.26 | 0.00 | 0.00 |
March | 41.66 | 1756.29 | 431.30 | 0.00 | 431.30 | 0.00 | 0.00 |
April | 341.63 | 927.81 | 779.35 | 16.18 | 763.16 | 0.00 | 0.00 |
May | 953.82 | 423.26 | 1192.41 | 186.56 | 1005.85 | 0.00 | 0.00 |
June | 1561.61 | 199.44 | 1558.03 | 344.60 | 1213.42 | 0.00 | 0.00 |
July | 1340.58 | 242.67 | 1307.22 | 210.43 | 1096.79 | 0.00 | 0.00 |
August | 704.04 | 399.47 | 834.66 | 45.12 | 789.54 | 0.00 | 0.00 |
September | 197.17 | 778.92 | 466.49 | 0.41 | 466.08 | 0.00 | 0.00 |
October | 21.50 | 1478.81 | 227.02 | 0.00 | 227.02 | 0.00 | 0.00 |
November | 0.00 | 2624.17 | 70.45 | 0.00 | 70.45 | 0.00 | 0.00 |
December | 0.00 | 2829.56 | 11.07 | 0.00 | 11.07 | 0.00 | 0.00 |
Annual Sum or Average | 432.66 | 1389.67 | 591.75 | 67.24 | 524.52 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 199.44 | 11.07 | 0.00 | 11.07 | 0.00 | 0.00 |
Maximum of Months | 1561.61 | 2829.56 | 1558.03 | 344.60 | 1213.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.79 | 1737.51 | 63.49 | 19.59 | 43.90 | 0.00 | 0.00 |
February | 193.50 | 1442.99 | 353.15 | 168.09 | 185.07 | 0.00 | 0.00 |
March | 882.31 | 1050.43 | 1010.87 | 512.52 | 498.35 | 0.00 | 0.00 |
April | 1325.78 | 574.82 | 1390.14 | 704.41 | 685.73 | 0.00 | 0.00 |
May | 2263.31 | 306.97 | 2022.20 | 1141.06 | 881.14 | 0.00 | 0.00 |
June | 2147.38 | 152.70 | 1858.92 | 868.19 | 990.73 | 0.00 | 0.00 |
July | 2091.08 | 174.76 | 1766.08 | 857.41 | 908.67 | 0.00 | 0.00 |
August | 1586.34 | 270.59 | 1398.44 | 681.60 | 716.84 | 0.00 | 0.00 |
September | 833.76 | 491.61 | 864.39 | 379.00 | 485.39 | 0.00 | 0.00 |
October | 341.29 | 896.40 | 455.79 | 182.76 | 273.03 | 0.00 | 0.00 |
November | 8.24 | 1684.26 | 96.27 | 33.16 | 63.10 | 0.00 | 0.00 |
December | 0.00 | 1876.17 | 13.69 | 3.15 | 10.54 | 0.00 | 0.00 |
Annual Sum or Average | 978.48 | 885.49 | 944.73 | 464.63 | 480.10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 152.70 | 13.69 | 3.15 | 10.54 | 0.00 | 0.00 |
Maximum of Months | 2263.31 | 1876.17 | 2022.20 | 1141.06 | 990.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 266.85 | 2411.38 | 440.54 | 291.23 | 149.31 | 0.00 | 0.00 |
February | 1327.79 | 1928.21 | 1515.33 | 1056.92 | 458.41 | 0.00 | 0.00 |
March | 2617.13 | 1470.10 | 2596.40 | 1763.21 | 833.19 | 0.00 | 0.00 |
April | 3539.09 | 964.65 | 3160.54 | 1968.32 | 1192.22 | 0.00 | 0.00 |
May | 2984.68 | 532.86 | 2597.01 | 1343.51 | 1253.50 | 0.00 | 0.00 |
June | 2794.59 | 288.71 | 2368.32 | 966.63 | 1401.69 | 0.00 | 0.00 |
July | 2761.37 | 306.91 | 2283.82 | 991.98 | 1291.84 | 0.00 | 0.00 |
August | 2827.47 | 447.33 | 2371.89 | 1308.06 | 1063.83 | 0.00 | 0.00 |
September | 2093.10 | 757.95 | 1920.85 | 1159.03 | 761.82 | 0.00 | 0.00 |
October | 1309.84 | 1246.28 | 1385.89 | 881.81 | 504.08 | 0.00 | 0.00 |
November | 511.93 | 2241.69 | 744.48 | 521.37 | 223.11 | 0.00 | 0.00 |
December | 24.31 | 2689.59 | 132.20 | 93.47 | 38.74 | 0.00 | 0.00 |
Annual Sum or Average | 1922.96 | 1270.73 | 1792.59 | 1027.19 | 765.40 | 0.00 | 0.00 |
Minimum of Months | 24.31 | 288.71 | 132.20 | 93.47 | 38.74 | 0.00 | 0.00 |
Maximum of Months | 3539.09 | 2689.59 | 3160.54 | 1968.32 | 1401.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1772.06 | 33.45 | 5.76 | 27.69 | 0.00 | 0.00 |
February | 42.54 | 1500.31 | 197.96 | 68.19 | 129.76 | 0.00 | 0.00 |
March | 356.58 | 1075.16 | 596.51 | 256.08 | 340.43 | 0.00 | 0.00 |
April | 1403.55 | 619.37 | 1419.34 | 736.68 | 682.66 | 0.00 | 0.00 |
May | 1439.59 | 326.13 | 1380.27 | 629.96 | 750.31 | 0.00 | 0.00 |
June | 1706.66 | 178.54 | 1512.43 | 646.30 | 866.13 | 0.00 | 0.00 |
July | 1441.04 | 192.86 | 1264.93 | 479.46 | 785.47 | 0.00 | 0.00 |
August | 1127.46 | 284.28 | 1039.46 | 440.80 | 598.66 | 0.00 | 0.00 |
September | 540.68 | 503.80 | 628.72 | 263.46 | 365.26 | 0.00 | 0.00 |
October | 99.41 | 935.09 | 245.38 | 73.26 | 172.12 | 0.00 | 0.00 |
November | 11.18 | 1680.16 | 97.77 | 35.08 | 62.69 | 0.00 | 0.00 |
December | 0.00 | 1882.28 | 8.78 | 0.87 | 7.91 | 0.00 | 0.00 |
Annual Sum or Average | 683.39 | 909.50 | 703.90 | 303.64 | 400.26 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 178.54 | 8.78 | 0.87 | 7.91 | 0.00 | 0.00 |
Maximum of Months | 1706.66 | 1882.28 | 1512.43 | 736.68 | 866.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2695.77 | 36.48 | 0.00 | 36.48 | 0.00 | 0.00 |
February | 0.00 | 2392.95 | 161.26 | 0.00 | 161.26 | 0.00 | 0.00 |
March | 43.53 | 1757.85 | 431.30 | 0.00 | 431.30 | 0.00 | 0.00 |
April | 362.82 | 923.00 | 779.34 | 16.18 | 763.16 | 0.00 | 0.00 |
May | 993.88 | 409.41 | 1192.41 | 186.56 | 1005.85 | 0.00 | 0.00 |
June | 1594.50 | 191.64 | 1558.02 | 344.60 | 1213.42 | 0.00 | 0.00 |
July | 1358.94 | 239.72 | 1307.21 | 210.43 | 1096.78 | 0.00 | 0.00 |
August | 703.06 | 410.86 | 834.65 | 45.12 | 789.53 | 0.00 | 0.00 |
September | 182.67 | 839.38 | 466.49 | 0.41 | 466.08 | 0.00 | 0.00 |
October | 17.26 | 1558.89 | 227.02 | 0.00 | 227.02 | 0.00 | 0.00 |
November | 0.00 | 2679.44 | 70.45 | 0.00 | 70.45 | 0.00 | 0.00 |
December | 0.00 | 2859.11 | 11.07 | 0.00 | 11.07 | 0.00 | 0.00 |
Annual Sum or Average | 440.59 | 1407.91 | 591.75 | 67.24 | 524.51 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 191.64 | 11.07 | 0.00 | 11.07 | 0.00 | 0.00 |
Maximum of Months | 1594.50 | 2859.11 | 1558.02 | 344.60 | 1213.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.96 | 1745.99 | 63.49 | 19.59 | 43.90 | 0.00 | 0.00 |
February | 194.51 | 1446.31 | 353.15 | 168.08 | 185.06 | 0.00 | 0.00 |
March | 888.98 | 1059.06 | 1010.86 | 512.51 | 498.35 | 0.00 | 0.00 |
April | 1336.71 | 585.61 | 1390.13 | 704.41 | 685.72 | 0.00 | 0.00 |
May | 2276.12 | 312.94 | 2022.18 | 1141.05 | 881.13 | 0.00 | 0.00 |
June | 2162.48 | 152.61 | 1858.90 | 868.18 | 990.72 | 0.00 | 0.00 |
July | 2098.96 | 179.27 | 1766.07 | 857.40 | 908.66 | 0.00 | 0.00 |
August | 1585.60 | 286.01 | 1398.43 | 681.59 | 716.84 | 0.00 | 0.00 |
September | 817.90 | 539.49 | 864.38 | 378.99 | 485.39 | 0.00 | 0.00 |
October | 334.09 | 951.88 | 455.79 | 182.76 | 273.02 | 0.00 | 0.00 |
November | 8.04 | 1718.55 | 96.27 | 33.16 | 63.10 | 0.00 | 0.00 |
December | 0.00 | 1894.03 | 13.69 | 3.15 | 10.54 | 0.00 | 0.00 |
Annual Sum or Average | 981.04 | 903.26 | 944.72 | 464.63 | 480.10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 152.61 | 13.69 | 3.15 | 10.54 | 0.00 | 0.00 |
Maximum of Months | 2276.12 | 1894.03 | 2022.18 | 1141.05 | 990.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 280.28 | 2319.41 | 440.54 | 291.23 | 149.31 | 0.00 | 0.00 |
February | 1357.63 | 1882.01 | 1515.34 | 1056.93 | 458.41 | 0.00 | 0.00 |
March | 2671.21 | 1455.19 | 2596.42 | 1763.23 | 833.20 | 0.00 | 0.00 |
April | 3580.24 | 987.20 | 3160.57 | 1968.34 | 1192.23 | 0.00 | 0.00 |
May | 3025.51 | 536.15 | 2597.03 | 1343.53 | 1253.51 | 0.00 | 0.00 |
June | 2829.33 | 286.35 | 2368.34 | 966.64 | 1401.70 | 0.00 | 0.00 |
July | 2782.18 | 312.91 | 2283.84 | 992.00 | 1291.85 | 0.00 | 0.00 |
August | 2841.92 | 472.07 | 2371.92 | 1308.08 | 1063.84 | 0.00 | 0.00 |
September | 2092.88 | 819.31 | 1920.87 | 1159.04 | 761.83 | 0.00 | 0.00 |
October | 1309.98 | 1303.26 | 1385.91 | 881.82 | 504.08 | 0.00 | 0.00 |
November | 527.85 | 2206.85 | 744.49 | 521.38 | 223.11 | 0.00 | 0.00 |
December | 30.69 | 2586.75 | 132.20 | 93.47 | 38.74 | 0.00 | 0.00 |
Annual Sum or Average | 1945.53 | 1260.95 | 1792.61 | 1027.21 | 765.40 | 0.00 | 0.00 |
Minimum of Months | 30.69 | 286.35 | 132.20 | 93.47 | 38.74 | 0.00 | 0.00 |
Maximum of Months | 3580.24 | 2586.75 | 3160.57 | 1968.34 | 1401.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1780.83 | 33.45 | 5.76 | 27.69 | 0.00 | 0.00 |
February | 43.44 | 1503.20 | 197.95 | 68.19 | 129.76 | 0.00 | 0.00 |
March | 363.30 | 1080.35 | 596.50 | 256.08 | 340.43 | 0.00 | 0.00 |
April | 1417.94 | 632.65 | 1419.33 | 736.67 | 682.66 | 0.00 | 0.00 |
May | 1457.51 | 326.44 | 1380.26 | 629.95 | 750.31 | 0.00 | 0.00 |
June | 1722.47 | 176.82 | 1512.42 | 646.30 | 866.13 | 0.00 | 0.00 |
July | 1450.07 | 194.49 | 1264.92 | 479.45 | 785.47 | 0.00 | 0.00 |
August | 1125.36 | 299.43 | 1039.45 | 440.79 | 598.66 | 0.00 | 0.00 |
September | 528.65 | 548.35 | 628.71 | 263.46 | 365.25 | 0.00 | 0.00 |
October | 95.11 | 987.67 | 245.38 | 73.26 | 172.12 | 0.00 | 0.00 |
November | 10.86 | 1715.21 | 97.77 | 35.08 | 62.69 | 0.00 | 0.00 |
December | 0.00 | 1900.43 | 8.78 | 0.87 | 7.91 | 0.00 | 0.00 |
Annual Sum or Average | 687.25 | 925.86 | 703.89 | 303.63 | 400.26 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 176.82 | 8.78 | 0.87 | 7.91 | 0.00 | 0.00 |
Maximum of Months | 1722.47 | 1900.43 | 1512.42 | 736.67 | 866.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 2733.53 | 36.48 | 0.00 | 36.48 | 0.00 | 0.00 |
February | 0.00 | 2447.12 | 161.26 | 0.00 | 161.26 | 0.00 | 0.00 |
March | 38.43 | 1816.13 | 431.30 | 0.00 | 431.30 | 0.00 | 0.00 |
April | 322.54 | 983.65 | 779.35 | 16.18 | 763.16 | 0.00 | 0.00 |
May | 929.89 | 443.93 | 1192.41 | 186.56 | 1005.85 | 0.00 | 0.00 |
June | 1554.23 | 206.58 | 1558.03 | 344.60 | 1213.42 | 0.00 | 0.00 |
July | 1332.81 | 251.69 | 1307.22 | 210.43 | 1096.79 | 0.00 | 0.00 |
August | 688.67 | 421.24 | 834.66 | 45.12 | 789.54 | 0.00 | 0.00 |
September | 176.74 | 843.14 | 466.49 | 0.41 | 466.08 | 0.00 | 0.00 |
October | 16.75 | 1552.14 | 227.02 | 0.00 | 227.02 | 0.00 | 0.00 |
November | 0.00 | 2680.73 | 70.45 | 0.00 | 70.45 | 0.00 | 0.00 |
December | 0.00 | 2879.77 | 11.07 | 0.00 | 11.07 | 0.00 | 0.00 |
Annual Sum or Average | 424.13 | 1432.86 | 591.75 | 67.24 | 524.52 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 206.58 | 11.07 | 0.00 | 11.07 | 0.00 | 0.00 |
Maximum of Months | 1554.23 | 2879.77 | 1558.03 | 344.60 | 1213.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.64 | 1767.88 | 63.49 | 19.59 | 43.90 | 0.00 | 0.00 |
February | 190.48 | 1475.48 | 353.15 | 168.09 | 185.07 | 0.00 | 0.00 |
March | 873.63 | 1086.49 | 1010.87 | 512.52 | 498.35 | 0.00 | 0.00 |
April | 1311.47 | 604.73 | 1390.14 | 704.41 | 685.73 | 0.00 | 0.00 |
May | 2255.08 | 318.98 | 2022.20 | 1141.06 | 881.14 | 0.00 | 0.00 |
June | 2144.83 | 157.37 | 1858.92 | 868.19 | 990.73 | 0.00 | 0.00 |
July | 2088.46 | 180.33 | 1766.08 | 857.41 | 908.67 | 0.00 | 0.00 |
August | 1580.27 | 282.40 | 1398.44 | 681.60 | 716.84 | 0.00 | 0.00 |
September | 818.75 | 525.81 | 864.39 | 379.00 | 485.39 | 0.00 | 0.00 |
October | 333.34 | 941.12 | 455.79 | 182.76 | 273.03 | 0.00 | 0.00 |
November | 7.88 | 1720.04 | 96.27 | 33.16 | 63.10 | 0.00 | 0.00 |
December | 0.00 | 1907.44 | 13.69 | 3.15 | 10.54 | 0.00 | 0.00 |
Annual Sum or Average | 972.74 | 911.17 | 944.73 | 464.63 | 480.10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 157.37 | 13.69 | 3.15 | 10.54 | 0.00 | 0.00 |
Maximum of Months | 2255.08 | 1907.44 | 2022.20 | 1141.06 | 990.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 263.84 | 2456.36 | 440.54 | 291.23 | 149.31 | 0.00 | 0.00 |
February | 1316.78 | 1978.11 | 1515.33 | 1056.92 | 458.41 | 0.00 | 0.00 |
March | 2602.15 | 1524.96 | 2596.40 | 1763.21 | 833.19 | 0.00 | 0.00 |
April | 3524.08 | 1013.66 | 3160.54 | 1968.32 | 1192.22 | 0.00 | 0.00 |
May | 2976.04 | 559.92 | 2597.01 | 1343.51 | 1253.50 | 0.00 | 0.00 |
June | 2791.82 | 300.29 | 2368.32 | 966.63 | 1401.69 | 0.00 | 0.00 |
July | 2757.95 | 319.13 | 2283.82 | 991.98 | 1291.84 | 0.00 | 0.00 |
August | 2820.13 | 469.79 | 2371.89 | 1308.06 | 1063.83 | 0.00 | 0.00 |
September | 2072.99 | 810.48 | 1920.85 | 1159.03 | 761.82 | 0.00 | 0.00 |
October | 1292.03 | 1311.51 | 1385.89 | 881.81 | 504.08 | 0.00 | 0.00 |
November | 505.65 | 2295.01 | 744.48 | 521.37 | 223.11 | 0.00 | 0.00 |
December | 23.87 | 2737.94 | 132.20 | 93.47 | 38.74 | 0.00 | 0.00 |
Annual Sum or Average | 1913.76 | 1311.61 | 1792.59 | 1027.19 | 765.40 | 0.00 | 0.00 |
Minimum of Months | 23.87 | 300.29 | 132.20 | 93.47 | 38.74 | 0.00 | 0.00 |
Maximum of Months | 3524.08 | 2737.94 | 3160.54 | 1968.32 | 1401.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1802.31 | 33.45 | 5.76 | 27.69 | 0.00 | 0.00 |
February | 41.66 | 1533.66 | 197.96 | 68.19 | 129.76 | 0.00 | 0.00 |
March | 352.18 | 1112.77 | 596.51 | 256.08 | 340.43 | 0.00 | 0.00 |
April | 1392.50 | 653.06 | 1419.34 | 736.68 | 682.66 | 0.00 | 0.00 |
May | 1430.46 | 343.60 | 1380.27 | 629.96 | 750.31 | 0.00 | 0.00 |
June | 1703.81 | 185.72 | 1512.43 | 646.30 | 866.13 | 0.00 | 0.00 |
July | 1437.60 | 200.74 | 1264.93 | 479.46 | 785.47 | 0.00 | 0.00 |
August | 1119.79 | 299.46 | 1039.46 | 440.80 | 598.66 | 0.00 | 0.00 |
September | 527.53 | 541.21 | 628.72 | 263.46 | 365.26 | 0.00 | 0.00 |
October | 94.60 | 981.41 | 245.38 | 73.26 | 172.12 | 0.00 | 0.00 |
November | 10.74 | 1715.72 | 97.77 | 35.08 | 62.69 | 0.00 | 0.00 |
December | 0.00 | 1913.33 | 8.78 | 0.87 | 7.91 | 0.00 | 0.00 |
Annual Sum or Average | 678.57 | 937.19 | 703.90 | 303.64 | 400.26 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 185.72 | 8.78 | 0.87 | 7.91 | 0.00 | 0.00 |
Maximum of Months | 1703.81 | 1913.33 | 1512.43 | 736.68 | 866.13 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.719313E+10 | 97708504.74 | 0.00 | 97708504.74 | 0.00 | 0.00 |
February | 0.00 | 0.579159E+10 | 0.390120E+09 | 0.00 | 0.390120E+09 | 0.00 | 0.00 |
March | 0.111590E+09 | 0.470405E+10 | 0.115520E+10 | 0.00 | 0.115520E+10 | 0.00 | 0.00 |
April | 0.885509E+09 | 0.240489E+10 | 0.202007E+10 | 41949790.24 | 0.197812E+10 | 0.00 | 0.00 |
May | 0.255471E+10 | 0.113365E+10 | 0.319376E+10 | 0.499680E+09 | 0.269408E+10 | 0.00 | 0.00 |
June | 0.404770E+10 | 0.516950E+09 | 0.403840E+10 | 0.893210E+09 | 0.314519E+10 | 0.00 | 0.00 |
July | 0.359061E+10 | 0.649969E+09 | 0.350125E+10 | 0.563609E+09 | 0.293764E+10 | 0.00 | 0.00 |
August | 0.188569E+10 | 0.106995E+10 | 0.223555E+10 | 0.120851E+09 | 0.211470E+10 | 0.00 | 0.00 |
September | 0.511074E+09 | 0.201897E+10 | 0.120915E+10 | 1071841.51 | 0.120807E+10 | 0.00 | 0.00 |
October | 57573969.40 | 0.396084E+10 | 0.608042E+09 | 0.00 | 0.608042E+09 | 0.00 | 0.00 |
November | 0.00 | 0.680184E+10 | 0.182610E+09 | 0.00 | 0.182610E+09 | 0.00 | 0.00 |
December | 0.00 | 0.757870E+10 | 29639659.08 | 0.00 | 29639659.08 | 0.00 | 0.00 |
Annual Sum or Average | 0.136445E+11 | 0.438245E+11 | 0.186615E+11 | 0.212037E+10 | 0.165411E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.516950E+09 | 29639659.08 | 0.00 | 29639659.08 | 0.00 | 0.00 |
Maximum of Months | 0.404770E+10 | 0.757870E+10 | 0.403840E+10 | 0.893210E+09 | 0.314519E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 15501003.19 | 0.465375E+10 | 0.170062E+09 | 52471550.32 | 0.117591E+09 | 0.00 | 0.00 |
February | 0.468123E+09 | 0.349087E+10 | 0.854344E+09 | 0.406635E+09 | 0.447709E+09 | 0.00 | 0.00 |
March | 0.236318E+10 | 0.281348E+10 | 0.270751E+10 | 0.137273E+10 | 0.133478E+10 | 0.00 | 0.00 |
April | 0.343641E+10 | 0.148993E+10 | 0.360324E+10 | 0.182584E+10 | 0.177740E+10 | 0.00 | 0.00 |
May | 0.606205E+10 | 0.822176E+09 | 0.541625E+10 | 0.305622E+10 | 0.236004E+10 | 0.00 | 0.00 |
June | 0.556602E+10 | 0.395788E+09 | 0.481831E+10 | 0.225035E+10 | 0.256796E+10 | 0.00 | 0.00 |
July | 0.560074E+10 | 0.468076E+09 | 0.473027E+10 | 0.229649E+10 | 0.243378E+10 | 0.00 | 0.00 |
August | 0.424886E+10 | 0.724757E+09 | 0.374559E+10 | 0.182559E+10 | 0.192000E+10 | 0.00 | 0.00 |
September | 0.216110E+10 | 0.127424E+10 | 0.224050E+10 | 0.982359E+09 | 0.125814E+10 | 0.00 | 0.00 |
October | 0.914107E+09 | 0.240092E+10 | 0.122079E+10 | 0.489516E+09 | 0.731272E+09 | 0.00 | 0.00 |
November | 21353157.93 | 0.436560E+10 | 0.249524E+09 | 85961234.00 | 0.163563E+09 | 0.00 | 0.00 |
December | 0.00 | 0.502513E+10 | 36671077.03 | 8439139.61 | 28231937.42 | 0.00 | 0.00 |
Annual Sum or Average | 0.308574E+11 | 0.279247E+11 | 0.297931E+11 | 0.146526E+11 | 0.151405E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.395788E+09 | 36671077.03 | 8439139.61 | 28231937.42 | 0.00 | 0.00 |
Maximum of Months | 0.606205E+10 | 0.502513E+10 | 0.541625E+10 | 0.305622E+10 | 0.256796E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.714742E+09 | 0.645863E+10 | 0.117993E+10 | 0.780028E+09 | 0.399904E+09 | 0.00 | 0.00 |
February | 0.321218E+10 | 0.466472E+10 | 0.366588E+10 | 0.255691E+10 | 0.110897E+10 | 0.00 | 0.00 |
March | 0.700971E+10 | 0.393753E+10 | 0.695419E+10 | 0.472258E+10 | 0.223161E+10 | 0.00 | 0.00 |
April | 0.917331E+10 | 0.250036E+10 | 0.819212E+10 | 0.510188E+10 | 0.309024E+10 | 0.00 | 0.00 |
May | 0.799416E+10 | 0.142721E+10 | 0.695583E+10 | 0.359846E+10 | 0.335737E+10 | 0.00 | 0.00 |
June | 0.724357E+10 | 0.748327E+09 | 0.613867E+10 | 0.250550E+10 | 0.363317E+10 | 0.00 | 0.00 |
July | 0.739605E+10 | 0.822022E+09 | 0.611699E+10 | 0.265693E+10 | 0.346006E+10 | 0.00 | 0.00 |
August | 0.757310E+10 | 0.119813E+10 | 0.635288E+10 | 0.350352E+10 | 0.284936E+10 | 0.00 | 0.00 |
September | 0.542531E+10 | 0.196460E+10 | 0.497885E+10 | 0.300420E+10 | 0.197465E+10 | 0.00 | 0.00 |
October | 0.350826E+10 | 0.333804E+10 | 0.371197E+10 | 0.236185E+10 | 0.135013E+10 | 0.00 | 0.00 |
November | 0.132692E+10 | 0.581046E+10 | 0.192969E+10 | 0.135139E+10 | 0.578293E+09 | 0.00 | 0.00 |
December | 65101313.73 | 0.720380E+10 | 0.354090E+09 | 0.250338E+09 | 0.103752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.606424E+11 | 0.400738E+11 | 0.565311E+11 | 0.323936E+11 | 0.241375E+11 | 0.00 | 0.00 |
Minimum of Months | 65101313.73 | 0.748327E+09 | 0.354090E+09 | 0.250338E+09 | 0.103752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.917331E+10 | 0.720380E+10 | 0.819212E+10 | 0.510188E+10 | 0.363317E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.474629E+10 | 89590715.39 | 15434927.31 | 74155788.08 | 0.00 | 0.00 |
February | 0.102919E+09 | 0.362956E+10 | 0.478894E+09 | 0.164969E+09 | 0.313925E+09 | 0.00 | 0.00 |
March | 0.955053E+09 | 0.287970E+10 | 0.159769E+10 | 0.685885E+09 | 0.911805E+09 | 0.00 | 0.00 |
April | 0.363801E+10 | 0.160540E+10 | 0.367893E+10 | 0.190947E+10 | 0.176947E+10 | 0.00 | 0.00 |
May | 0.385579E+10 | 0.873513E+09 | 0.369690E+10 | 0.168727E+10 | 0.200963E+10 | 0.00 | 0.00 |
June | 0.442366E+10 | 0.462763E+09 | 0.392023E+10 | 0.167521E+10 | 0.224502E+10 | 0.00 | 0.00 |
July | 0.385968E+10 | 0.516562E+09 | 0.338798E+10 | 0.128418E+10 | 0.210380E+10 | 0.00 | 0.00 |
August | 0.301978E+10 | 0.761417E+09 | 0.278408E+10 | 0.118063E+10 | 0.160345E+10 | 0.00 | 0.00 |
September | 0.140143E+10 | 0.130584E+10 | 0.162964E+10 | 0.682893E+09 | 0.946743E+09 | 0.00 | 0.00 |
October | 0.266247E+09 | 0.250454E+10 | 0.657221E+09 | 0.196223E+09 | 0.460998E+09 | 0.00 | 0.00 |
November | 28968658.28 | 0.435499E+10 | 0.253423E+09 | 90929198.28 | 0.162494E+09 | 0.00 | 0.00 |
December | 0.00 | 0.504150E+10 | 23518703.94 | 2330467.50 | 21188236.44 | 0.00 | 0.00 |
Annual Sum or Average | 0.215515E+11 | 0.286821E+11 | 0.221981E+11 | 0.957543E+10 | 0.126227E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.462763E+09 | 23518703.94 | 2330467.50 | 21188236.44 | 0.00 | 0.00 |
Maximum of Months | 0.442366E+10 | 0.504150E+10 | 0.392023E+10 | 0.190947E+10 | 0.224502E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.722035E+10 | 97707998.43 | 0.00 | 97707998.43 | 0.00 | 0.00 |
February | 0.00 | 0.578901E+10 | 0.390118E+09 | 0.00 | 0.390118E+09 | 0.00 | 0.00 |
March | 0.116581E+09 | 0.470824E+10 | 0.115519E+10 | 0.00 | 0.115519E+10 | 0.00 | 0.00 |
April | 0.940432E+09 | 0.239241E+10 | 0.202006E+10 | 41949572.86 | 0.197811E+10 | 0.00 | 0.00 |
May | 0.266201E+10 | 0.109656E+10 | 0.319374E+10 | 0.499678E+09 | 0.269406E+10 | 0.00 | 0.00 |
June | 0.413295E+10 | 0.496734E+09 | 0.403838E+10 | 0.893206E+09 | 0.314518E+10 | 0.00 | 0.00 |
July | 0.363979E+10 | 0.642062E+09 | 0.350123E+10 | 0.563606E+09 | 0.293762E+10 | 0.00 | 0.00 |
August | 0.188308E+10 | 0.110045E+10 | 0.223554E+10 | 0.120850E+09 | 0.211469E+10 | 0.00 | 0.00 |
September | 0.473473E+09 | 0.217566E+10 | 0.120914E+10 | 1071835.96 | 0.120807E+10 | 0.00 | 0.00 |
October | 46241421.85 | 0.417534E+10 | 0.608039E+09 | 0.00 | 0.608039E+09 | 0.00 | 0.00 |
November | 0.00 | 0.694510E+10 | 0.182609E+09 | 0.00 | 0.182609E+09 | 0.00 | 0.00 |
December | 0.00 | 0.765783E+10 | 29639505.49 | 0.00 | 29639505.49 | 0.00 | 0.00 |
Annual Sum or Average | 0.138946E+11 | 0.443997E+11 | 0.186614E+11 | 0.212036E+10 | 0.165410E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.496734E+09 | 29639505.49 | 0.00 | 29639505.49 | 0.00 | 0.00 |
Maximum of Months | 0.413295E+10 | 0.765783E+10 | 0.403838E+10 | 0.893206E+09 | 0.314518E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 15958936.25 | 0.467645E+10 | 0.170061E+09 | 52471020.15 | 0.117590E+09 | 0.00 | 0.00 |
February | 0.470557E+09 | 0.349891E+10 | 0.854336E+09 | 0.406630E+09 | 0.447706E+09 | 0.00 | 0.00 |
March | 0.238104E+10 | 0.283658E+10 | 0.270749E+10 | 0.137271E+10 | 0.133477E+10 | 0.00 | 0.00 |
April | 0.346476E+10 | 0.151791E+10 | 0.360321E+10 | 0.182582E+10 | 0.177739E+10 | 0.00 | 0.00 |
May | 0.609636E+10 | 0.838171E+09 | 0.541621E+10 | 0.305619E+10 | 0.236002E+10 | 0.00 | 0.00 |
June | 0.560515E+10 | 0.395562E+09 | 0.481827E+10 | 0.225032E+10 | 0.256795E+10 | 0.00 | 0.00 |
July | 0.562187E+10 | 0.480160E+09 | 0.473023E+10 | 0.229647E+10 | 0.243376E+10 | 0.00 | 0.00 |
August | 0.424688E+10 | 0.766046E+09 | 0.374556E+10 | 0.182557E+10 | 0.191998E+10 | 0.00 | 0.00 |
September | 0.211999E+10 | 0.139835E+10 | 0.224048E+10 | 0.982349E+09 | 0.125813E+10 | 0.00 | 0.00 |
October | 0.894815E+09 | 0.254952E+10 | 0.122078E+10 | 0.489511E+09 | 0.731267E+09 | 0.00 | 0.00 |
November | 20837184.39 | 0.445448E+10 | 0.249522E+09 | 85960365.44 | 0.163562E+09 | 0.00 | 0.00 |
December | 0.00 | 0.507296E+10 | 36670763.18 | 8439054.34 | 28231708.84 | 0.00 | 0.00 |
Annual Sum or Average | 0.309382E+11 | 0.284851E+11 | 0.297928E+11 | 0.146524E+11 | 0.151404E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.395562E+09 | 36670763.18 | 8439054.34 | 28231708.84 | 0.00 | 0.00 |
Maximum of Months | 0.609636E+10 | 0.507296E+10 | 0.541621E+10 | 0.305619E+10 | 0.256795E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.750714E+09 | 0.621232E+10 | 0.117995E+10 | 0.780037E+09 | 0.399908E+09 | 0.00 | 0.00 |
February | 0.328439E+10 | 0.455297E+10 | 0.366592E+10 | 0.255694E+10 | 0.110899E+10 | 0.00 | 0.00 |
March | 0.715456E+10 | 0.389757E+10 | 0.695426E+10 | 0.472263E+10 | 0.223163E+10 | 0.00 | 0.00 |
April | 0.927999E+10 | 0.255882E+10 | 0.819220E+10 | 0.510194E+10 | 0.309026E+10 | 0.00 | 0.00 |
May | 0.810352E+10 | 0.143603E+10 | 0.695590E+10 | 0.359850E+10 | 0.335739E+10 | 0.00 | 0.00 |
June | 0.733363E+10 | 0.742216E+09 | 0.613873E+10 | 0.250553E+10 | 0.363320E+10 | 0.00 | 0.00 |
July | 0.745180E+10 | 0.838098E+09 | 0.611705E+10 | 0.265696E+10 | 0.346008E+10 | 0.00 | 0.00 |
August | 0.761181E+10 | 0.126440E+10 | 0.635295E+10 | 0.350356E+10 | 0.284938E+10 | 0.00 | 0.00 |
September | 0.542475E+10 | 0.212365E+10 | 0.497890E+10 | 0.300424E+10 | 0.197466E+10 | 0.00 | 0.00 |
October | 0.350864E+10 | 0.349065E+10 | 0.371201E+10 | 0.236187E+10 | 0.135014E+10 | 0.00 | 0.00 |
November | 0.136818E+10 | 0.572016E+10 | 0.192971E+10 | 0.135141E+10 | 0.578299E+09 | 0.00 | 0.00 |
December | 82203159.57 | 0.692836E+10 | 0.354094E+09 | 0.250341E+09 | 0.103753E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.613542E+11 | 0.397652E+11 | 0.565317E+11 | 0.323940E+11 | 0.241377E+11 | 0.00 | 0.00 |
Minimum of Months | 82203159.57 | 0.742216E+09 | 0.354094E+09 | 0.250341E+09 | 0.103753E+09 | 0.00 | 0.00 |
Maximum of Months | 0.927999E+10 | 0.692836E+10 | 0.819220E+10 | 0.510194E+10 | 0.363320E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.476977E+10 | 89590037.93 | 15434773.11 | 74155264.82 | 0.00 | 0.00 |
February | 0.105098E+09 | 0.363653E+10 | 0.478890E+09 | 0.164967E+09 | 0.313923E+09 | 0.00 | 0.00 |
March | 0.973070E+09 | 0.289362E+10 | 0.159768E+10 | 0.685878E+09 | 0.911800E+09 | 0.00 | 0.00 |
April | 0.367529E+10 | 0.163983E+10 | 0.367890E+10 | 0.190945E+10 | 0.176945E+10 | 0.00 | 0.00 |
May | 0.390380E+10 | 0.874335E+09 | 0.369688E+10 | 0.168726E+10 | 0.200962E+10 | 0.00 | 0.00 |
June | 0.446463E+10 | 0.458305E+09 | 0.392020E+10 | 0.167520E+10 | 0.224500E+10 | 0.00 | 0.00 |
July | 0.388388E+10 | 0.520917E+09 | 0.338796E+10 | 0.128417E+10 | 0.210379E+10 | 0.00 | 0.00 |
August | 0.301417E+10 | 0.801988E+09 | 0.278406E+10 | 0.118062E+10 | 0.160344E+10 | 0.00 | 0.00 |
September | 0.137027E+10 | 0.142133E+10 | 0.162962E+10 | 0.682886E+09 | 0.946737E+09 | 0.00 | 0.00 |
October | 0.254736E+09 | 0.264537E+10 | 0.657216E+09 | 0.196221E+09 | 0.460995E+09 | 0.00 | 0.00 |
November | 28137469.78 | 0.444584E+10 | 0.253421E+09 | 90928289.93 | 0.162493E+09 | 0.00 | 0.00 |
December | 0.00 | 0.509010E+10 | 23518525.23 | 2330444.22 | 21188081.02 | 0.00 | 0.00 |
Annual Sum or Average | 0.216731E+11 | 0.291979E+11 | 0.221979E+11 | 0.957534E+10 | 0.126226E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.458305E+09 | 23518525.23 | 2330444.22 | 21188081.02 | 0.00 | 0.00 |
Maximum of Months | 0.446463E+10 | 0.509010E+10 | 0.392020E+10 | 0.190945E+10 | 0.224500E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.732149E+10 | 97708504.74 | 0.00 | 97708504.74 | 0.00 | 0.00 |
February | 0.00 | 0.592007E+10 | 0.390120E+09 | 0.00 | 0.390120E+09 | 0.00 | 0.00 |
March | 0.102941E+09 | 0.486433E+10 | 0.115520E+10 | 0.00 | 0.115520E+10 | 0.00 | 0.00 |
April | 0.836029E+09 | 0.254961E+10 | 0.202007E+10 | 41949790.24 | 0.197812E+10 | 0.00 | 0.00 |
May | 0.249063E+10 | 0.118903E+10 | 0.319376E+10 | 0.499680E+09 | 0.269408E+10 | 0.00 | 0.00 |
June | 0.402858E+10 | 0.535457E+09 | 0.403840E+10 | 0.893210E+09 | 0.314519E+10 | 0.00 | 0.00 |
July | 0.356980E+10 | 0.674133E+09 | 0.350125E+10 | 0.563609E+09 | 0.293764E+10 | 0.00 | 0.00 |
August | 0.184453E+10 | 0.112825E+10 | 0.223555E+10 | 0.120851E+09 | 0.211470E+10 | 0.00 | 0.00 |
September | 0.458100E+09 | 0.218541E+10 | 0.120915E+10 | 1071841.51 | 0.120807E+10 | 0.00 | 0.00 |
October | 44859791.61 | 0.415724E+10 | 0.608042E+09 | 0.00 | 0.608042E+09 | 0.00 | 0.00 |
November | 0.00 | 0.694846E+10 | 0.182610E+09 | 0.00 | 0.182610E+09 | 0.00 | 0.00 |
December | 0.00 | 0.771319E+10 | 29639659.08 | 0.00 | 29639659.08 | 0.00 | 0.00 |
Annual Sum or Average | 0.133755E+11 | 0.451867E+11 | 0.186615E+11 | 0.212037E+10 | 0.165411E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.535457E+09 | 29639659.08 | 0.00 | 29639659.08 | 0.00 | 0.00 |
Maximum of Months | 0.402858E+10 | 0.771319E+10 | 0.403840E+10 | 0.893210E+09 | 0.314519E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 15115822.99 | 0.473509E+10 | 0.170062E+09 | 52471550.32 | 0.117591E+09 | 0.00 | 0.00 |
February | 0.460812E+09 | 0.356947E+10 | 0.854344E+09 | 0.406635E+09 | 0.447709E+09 | 0.00 | 0.00 |
March | 0.233992E+10 | 0.291004E+10 | 0.270751E+10 | 0.137273E+10 | 0.133478E+10 | 0.00 | 0.00 |
April | 0.339933E+10 | 0.156747E+10 | 0.360324E+10 | 0.182584E+10 | 0.177740E+10 | 0.00 | 0.00 |
May | 0.604002E+10 | 0.854343E+09 | 0.541625E+10 | 0.305622E+10 | 0.236004E+10 | 0.00 | 0.00 |
June | 0.555941E+10 | 0.407897E+09 | 0.481831E+10 | 0.225035E+10 | 0.256796E+10 | 0.00 | 0.00 |
July | 0.559373E+10 | 0.483006E+09 | 0.473027E+10 | 0.229649E+10 | 0.243378E+10 | 0.00 | 0.00 |
August | 0.423261E+10 | 0.756393E+09 | 0.374559E+10 | 0.182559E+10 | 0.192000E+10 | 0.00 | 0.00 |
September | 0.212219E+10 | 0.136289E+10 | 0.224050E+10 | 0.982359E+09 | 0.125814E+10 | 0.00 | 0.00 |
October | 0.892823E+09 | 0.252069E+10 | 0.122079E+10 | 0.489516E+09 | 0.731272E+09 | 0.00 | 0.00 |
November | 20425878.53 | 0.445835E+10 | 0.249524E+09 | 85961234.00 | 0.163563E+09 | 0.00 | 0.00 |
December | 0.00 | 0.510889E+10 | 36671077.03 | 8439139.61 | 28231937.42 | 0.00 | 0.00 |
Annual Sum or Average | 0.306764E+11 | 0.287345E+11 | 0.297931E+11 | 0.146526E+11 | 0.151405E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.407897E+09 | 36671077.03 | 8439139.61 | 28231937.42 | 0.00 | 0.00 |
Maximum of Months | 0.604002E+10 | 0.510889E+10 | 0.541625E+10 | 0.305622E+10 | 0.256796E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.706681E+09 | 0.657910E+10 | 0.117993E+10 | 0.780028E+09 | 0.399904E+09 | 0.00 | 0.00 |
February | 0.318555E+10 | 0.478543E+10 | 0.366588E+10 | 0.255691E+10 | 0.110897E+10 | 0.00 | 0.00 |
March | 0.696959E+10 | 0.408446E+10 | 0.695419E+10 | 0.472258E+10 | 0.223161E+10 | 0.00 | 0.00 |
April | 0.913442E+10 | 0.262742E+10 | 0.819212E+10 | 0.510188E+10 | 0.309024E+10 | 0.00 | 0.00 |
May | 0.797101E+10 | 0.149970E+10 | 0.695583E+10 | 0.359846E+10 | 0.335737E+10 | 0.00 | 0.00 |
June | 0.723641E+10 | 0.778346E+09 | 0.613867E+10 | 0.250550E+10 | 0.363317E+10 | 0.00 | 0.00 |
July | 0.738689E+10 | 0.854748E+09 | 0.611699E+10 | 0.265693E+10 | 0.346006E+10 | 0.00 | 0.00 |
August | 0.755345E+10 | 0.125828E+10 | 0.635288E+10 | 0.350352E+10 | 0.284936E+10 | 0.00 | 0.00 |
September | 0.537319E+10 | 0.210075E+10 | 0.497885E+10 | 0.300420E+10 | 0.197465E+10 | 0.00 | 0.00 |
October | 0.346056E+10 | 0.351274E+10 | 0.371197E+10 | 0.236185E+10 | 0.135013E+10 | 0.00 | 0.00 |
November | 0.131064E+10 | 0.594867E+10 | 0.192969E+10 | 0.135139E+10 | 0.578293E+09 | 0.00 | 0.00 |
December | 63933215.46 | 0.733331E+10 | 0.354090E+09 | 0.250338E+09 | 0.103752E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.603523E+11 | 0.413630E+11 | 0.565311E+11 | 0.323936E+11 | 0.241375E+11 | 0.00 | 0.00 |
Minimum of Months | 63933215.46 | 0.778346E+09 | 0.354090E+09 | 0.250338E+09 | 0.103752E+09 | 0.00 | 0.00 |
Maximum of Months | 0.913442E+10 | 0.733331E+10 | 0.819212E+10 | 0.510188E+10 | 0.363317E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.482731E+10 | 89590715.39 | 15434927.31 | 74155788.08 | 0.00 | 0.00 |
February | 0.100789E+09 | 0.371024E+10 | 0.478894E+09 | 0.164969E+09 | 0.313925E+09 | 0.00 | 0.00 |
March | 0.943273E+09 | 0.298044E+10 | 0.159769E+10 | 0.685885E+09 | 0.911805E+09 | 0.00 | 0.00 |
April | 0.360936E+10 | 0.169272E+10 | 0.367893E+10 | 0.190947E+10 | 0.176947E+10 | 0.00 | 0.00 |
May | 0.383135E+10 | 0.920286E+09 | 0.369690E+10 | 0.168727E+10 | 0.200963E+10 | 0.00 | 0.00 |
June | 0.441628E+10 | 0.481395E+09 | 0.392023E+10 | 0.167521E+10 | 0.224502E+10 | 0.00 | 0.00 |
July | 0.385046E+10 | 0.537668E+09 | 0.338798E+10 | 0.128418E+10 | 0.210380E+10 | 0.00 | 0.00 |
August | 0.299925E+10 | 0.802074E+09 | 0.278408E+10 | 0.118063E+10 | 0.160345E+10 | 0.00 | 0.00 |
September | 0.136736E+10 | 0.140281E+10 | 0.162964E+10 | 0.682893E+09 | 0.946743E+09 | 0.00 | 0.00 |
October | 0.253372E+09 | 0.262860E+10 | 0.657221E+09 | 0.196223E+09 | 0.460998E+09 | 0.00 | 0.00 |
November | 27850407.27 | 0.444716E+10 | 0.253423E+09 | 90929198.28 | 0.162494E+09 | 0.00 | 0.00 |
December | 0.00 | 0.512466E+10 | 23518703.94 | 2330467.50 | 21188236.44 | 0.00 | 0.00 |
Annual Sum or Average | 0.213993E+11 | 0.295554E+11 | 0.221981E+11 | 0.957543E+10 | 0.126227E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.481395E+09 | 23518703.94 | 2330467.50 | 21188236.44 | 0.00 | 0.00 |
Maximum of Months | 0.441628E+10 | 0.512466E+10 | 0.392023E+10 | 0.190947E+10 | 0.224502E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.635293E+10 | -0.557598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -776949427.1 | 58.99 | 0.00 | 0.00 |
February | 0.575796E+10 | -0.506755E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -690409446.8 | 58.99 | 0.00 | 0.00 |
March | 0.674318E+10 | -0.600009E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -743093658.6 | 58.99 | 0.00 | 0.00 |
April | 0.608743E+10 | -0.539882E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -688617609.8 | 58.98 | 0.00 | 0.00 |
May | 0.644227E+10 | -0.574804E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694234723.4 | 58.98 | 0.00 | 0.00 |
June | 0.616994E+10 | -0.550141E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668530990.0 | 58.99 | 0.00 | 0.00 |
July | 0.567558E+10 | -0.498724E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688340608.8 | 58.98 | 0.00 | 0.00 |
August | 0.607278E+10 | -0.538190E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690885157.9 | 58.98 | 0.00 | 0.00 |
September | 0.550345E+10 | -0.482756E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -675885486.7 | 58.98 | 0.00 | 0.00 |
October | 0.581013E+10 | -0.508461E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -725524657.9 | 58.98 | 0.00 | 0.00 |
November | 0.591801E+10 | -0.518040E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -737614117.9 | 58.98 | 0.00 | 0.00 |
December | 0.611212E+10 | -0.533733E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -774783537.1 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.726458E+11 | -0.640909E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.855487E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.550345E+10 | -0.600009E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -776949427.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.674318E+10 | -0.482756E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -668530990.0 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.63 | 0.48 | 10-JAN-11:09 | 515.77 | 9.66 | 2.83 | 55.00 | 402.58 | 14.84 | 6.00 | 33.50 |
February | 205.83 | 0.55 | 0.48 | 01-FEB-11:00 | 1715.74 | 21.49 | 76.00 | 163.33 | 2037.80 | 35.66 | 190.67 | 149.67 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5228.02 | 31.57 | 270.67 | 293.33 | 4649.62 | 33.57 | 283.33 | 275.00 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:49 | 7485.50 | 30.17 | 283.67 | 371.50 | 1436.41 | 20.47 | 220.67 | 323.33 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-06:10 | 3614.04 | 20.16 | 114.67 | 436.50 | 1037.71 | 19.18 | 215.50 | 374.33 |
June | 583.50 | 0.55 | 0.48 | 01-JUN-05:40 | 1704.34 | 16.07 | 0.00 | 458.00 | 945.99 | 18.91 | 229.17 | 384.00 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-05:10 | 2048.26 | 16.73 | 15.67 | 454.50 | 967.94 | 18.96 | 232.00 | 378.67 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:00 | 5336.88 | 25.58 | 240.00 | 394.17 | 1101.70 | 19.57 | 192.67 | 336.17 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 4308.84 | 29.68 | 268.67 | 310.67 | 1475.04 | 21.16 | 165.17 | 266.33 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-07:00 | 2319.93 | 28.91 | 204.17 | 227.17 | 1995.50 | 32.84 | 232.83 | 202.67 |
November | 135.83 | 0.57 | 0.48 | 01-NOV-10:09 | 629.67 | 11.14 | 0.00 | 104.00 | 719.84 | 29.28 | 94.17 | 79.50 |
December | 71.17 | 0.81 | 0.48 | 08-DEC-12:09 | 147.05 | 4.59 | 0.00 | 1.50 | 104.16 | 8.97 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 3490.35 | 22.31 | 1476.33 | 3269.67 | 1465.22 | 22.41 | 2062.17 | 2803.17 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 147.05 | 4.59 | 0.00 | 1.50 | 104.16 | 8.97 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.81 | 0.48 | 7485.50 | 31.57 | 283.67 | 458.00 | 4649.62 | 35.66 | 283.33 | 384.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.74 | 0.48 | 23-JAN-11:09 | 243.65 | 8.93 | 1.67 | 22.00 | 150.81 | 12.31 | 2.00 | 8.33 |
February | 205.83 | 0.60 | 0.48 | 02-FEB-10:20 | 810.72 | 15.78 | 45.33 | 129.17 | 555.70 | 20.88 | 73.67 | 83.17 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:20 | 1905.42 | 18.11 | 82.67 | 267.50 | 1300.59 | 21.68 | 119.00 | 218.67 |
April | 421.83 | 0.52 | 0.48 | 01-APR-06:00 | 2614.77 | 20.05 | 109.67 | 371.67 | 1660.95 | 23.45 | 154.00 | 328.50 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-04:40 | 3564.77 | 21.10 | 179.83 | 446.17 | 1865.68 | 22.69 | 157.00 | 396.50 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-03:00 | 3020.44 | 19.60 | 167.83 | 478.33 | 1358.82 | 21.53 | 146.67 | 416.00 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-03:00 | 3033.10 | 19.80 | 172.17 | 463.00 | 1590.06 | 21.61 | 153.50 | 402.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:00 | 2477.71 | 19.81 | 142.50 | 395.33 | 1272.69 | 21.52 | 125.17 | 338.50 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:30 | 1848.93 | 18.34 | 103.17 | 285.17 | 1000.09 | 20.46 | 109.00 | 231.00 |
October | 265.50 | 0.56 | 0.48 | 01-OCT-07:49 | 966.76 | 16.93 | 70.50 | 197.00 | 601.86 | 19.99 | 77.67 | 132.50 |
November | 135.83 | 0.67 | 0.48 | 01-NOV-10:09 | 332.85 | 14.62 | 33.83 | 54.00 | 197.75 | 17.54 | 34.67 | 11.50 |
December | 71.17 | 0.90 | 0.67 | 04-DEC-11:30 | 82.47 | 4.93 | 0.00 | 0.00 | 48.62 | 7.57 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 2334.14 | 18.59 | 1109.17 | 3109.33 | 1259.66 | 21.06 | 1152.33 | 2566.83 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 82.47 | 4.93 | 0.00 | 0.00 | 48.62 | 7.57 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.67 | 3564.77 | 21.10 | 179.83 | 478.33 | 1865.68 | 23.45 | 157.00 | 416.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.82 | 0.53 | 31-JAN-11:30 | 142.12 | 6.35 | 0.00 | 0.83 | 83.26 | 9.32 | 0.00 | 0.00 |
February | 205.83 | 0.65 | 0.48 | 19-FEB-10:50 | 312.77 | 10.62 | 0.00 | 75.50 | 185.34 | 13.67 | 0.00 | 8.67 |
March | 329.50 | 0.55 | 0.48 | 01-MAR-10:20 | 576.11 | 14.05 | 0.00 | 253.67 | 343.03 | 16.99 | 0.00 | 150.00 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:09 | 756.61 | 16.41 | 0.00 | 385.83 | 471.82 | 19.34 | 4.67 | 306.83 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:49 | 916.79 | 19.49 | 104.33 | 491.17 | 563.80 | 22.98 | 158.33 | 449.33 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:00 | 1121.79 | 20.86 | 149.83 | 525.83 | 652.16 | 22.81 | 199.50 | 485.17 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-03:00 | 1018.78 | 20.52 | 136.83 | 508.00 | 572.16 | 21.59 | 140.83 | 441.67 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-05:40 | 785.43 | 18.15 | 62.17 | 411.17 | 449.27 | 18.81 | 24.83 | 329.83 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:00 | 564.63 | 14.15 | 0.00 | 278.50 | 327.01 | 16.93 | 0.00 | 144.67 |
October | 265.50 | 0.60 | 0.48 | 01-OCT-08:39 | 395.17 | 12.09 | 0.00 | 152.33 | 219.76 | 14.93 | 0.00 | 8.17 |
November | 135.83 | 0.77 | 0.51 | 06-NOV-13:30 | 190.26 | 8.06 | 0.00 | 8.33 | 109.77 | 11.31 | 0.00 | 0.00 |
December | 71.17 | 0.93 | 0.80 | 04-DEC-11:30 | 56.00 | 2.23 | 0.00 | 0.00 | 33.20 | 4.60 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 744.92 | 16.47 | 453.17 | 3091.17 | 436.97 | 18.80 | 528.17 | 2324.33 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 56.00 | 2.23 | 0.00 | 0.00 | 33.20 | 4.60 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.93 | 0.80 | 1121.79 | 20.86 | 149.83 | 525.83 | 652.16 | 22.98 | 199.50 | 485.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.76 | 0.48 | 23-JAN-13:30 | 205.66 | 8.32 | 1.33 | 14.50 | 124.79 | 11.74 | 1.83 | 3.17 |
February | 205.83 | 0.59 | 0.48 | 04-FEB-12:20 | 657.39 | 15.90 | 44.50 | 132.17 | 432.54 | 21.08 | 64.33 | 67.00 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-10:20 | 1468.49 | 17.93 | 74.17 | 277.83 | 929.53 | 21.37 | 91.00 | 229.50 |
April | 421.83 | 0.52 | 0.48 | 01-APR-09:39 | 3056.96 | 21.64 | 139.50 | 372.00 | 1543.47 | 22.06 | 115.50 | 326.83 |
May | 545.00 | 0.52 | 0.48 | 01-MAY-06:00 | 2391.50 | 18.30 | 117.67 | 463.00 | 1196.15 | 19.47 | 56.50 | 408.50 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-05:49 | 2550.62 | 17.71 | 110.67 | 489.67 | 1289.47 | 19.17 | 53.33 | 424.50 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-05:19 | 2203.03 | 17.67 | 114.33 | 481.33 | 1141.33 | 19.06 | 56.50 | 412.67 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-06:40 | 1993.02 | 18.75 | 114.17 | 407.17 | 1213.68 | 20.94 | 95.33 | 348.17 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-07:30 | 1551.81 | 19.08 | 100.00 | 302.00 | 974.19 | 22.26 | 102.50 | 235.17 |
October | 265.50 | 0.55 | 0.48 | 01-OCT-08:00 | 768.48 | 16.66 | 67.00 | 198.00 | 462.86 | 20.11 | 65.17 | 104.17 |
November | 135.83 | 0.67 | 0.48 | 01-NOV-12:50 | 320.23 | 14.17 | 33.83 | 51.33 | 216.84 | 19.30 | 45.17 | 18.33 |
December | 71.17 | 0.91 | 0.75 | 04-DEC-11:30 | 71.87 | 4.16 | 0.00 | 0.00 | 41.90 | 6.81 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 1899.58 | 17.68 | 917.17 | 3189.00 | 1030.33 | 19.90 | 747.17 | 2578.00 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 71.87 | 4.16 | 0.00 | 0.00 | 41.90 | 6.81 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.91 | 0.75 | 3056.96 | 21.64 | 139.50 | 489.67 | 1543.47 | 22.26 | 115.50 | 424.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.64 | 0.48 | 10-JAN-11:20 | 454.21 | 4.61 | 0.00 | 50.83 | 366.18 | 10.83 | 5.83 | 31.00 |
February | 205.83 | 0.55 | 0.48 | 01-FEB-12:09 | 1111.43 | 8.51 | 0.00 | 160.83 | 1891.87 | 33.21 | 170.50 | 144.67 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5026.73 | 30.69 | 265.17 | 292.00 | 4524.36 | 33.10 | 278.33 | 273.67 |
April | 421.83 | 0.53 | 0.48 | 01-APR-07:00 | 7329.35 | 29.06 | 283.67 | 366.83 | 1323.91 | 17.78 | 9.83 | 319.00 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-06:40 | 3508.98 | 17.43 | 114.50 | 431.67 | 964.62 | 16.64 | 1.00 | 367.50 |
June | 583.50 | 0.55 | 0.48 | 01-JUN-05:40 | 1611.23 | 12.35 | 0.00 | 452.50 | 884.95 | 16.27 | 0.00 | 377.50 |
July | 562.83 | 0.55 | 0.48 | 01-JUL-05:10 | 1952.43 | 13.09 | 15.67 | 449.33 | 904.13 | 16.29 | 0.00 | 372.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-06:10 | 5222.59 | 23.87 | 237.00 | 390.00 | 1021.38 | 16.79 | 3.00 | 331.00 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 4148.36 | 28.49 | 260.50 | 307.50 | 1390.41 | 18.44 | 32.33 | 262.17 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-07:00 | 2148.70 | 24.90 | 169.17 | 222.83 | 1900.56 | 31.73 | 223.33 | 199.17 |
November | 135.83 | 0.58 | 0.48 | 01-NOV-10:09 | 572.05 | 6.36 | 0.00 | 98.67 | 578.27 | 21.18 | 56.00 | 67.33 |
December | 71.17 | 0.83 | 0.50 | 08-DEC-12:09 | 133.90 | 1.29 | 0.00 | 0.17 | 97.14 | 5.02 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 3343.90 | 19.14 | 1345.67 | 3223.17 | 1379.68 | 19.79 | 780.17 | 2745.00 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 133.90 | 1.29 | 0.00 | 0.17 | 97.14 | 5.02 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.83 | 0.50 | 7329.35 | 30.69 | 283.67 | 452.50 | 4524.36 | 33.21 | 278.33 | 377.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.74 | 0.48 | 23-JAN-11:20 | 232.96 | 8.36 | 1.67 | 19.17 | 143.69 | 11.91 | 1.67 | 7.00 |
February | 205.83 | 0.61 | 0.48 | 02-FEB-10:30 | 778.26 | 15.33 | 45.33 | 125.50 | 472.88 | 18.46 | 50.83 | 76.33 |
March | 329.50 | 0.55 | 0.48 | 01-MAR-09:20 | 1833.02 | 17.69 | 82.17 | 264.17 | 1237.02 | 21.39 | 111.50 | 214.50 |
April | 421.83 | 0.52 | 0.48 | 01-APR-06:00 | 2530.19 | 19.63 | 109.67 | 367.50 | 1596.28 | 23.25 | 140.00 | 324.17 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-04:40 | 3360.68 | 19.34 | 149.83 | 442.00 | 1795.39 | 22.52 | 145.50 | 392.33 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-03:00 | 2937.63 | 19.22 | 167.33 | 474.00 | 1299.17 | 21.37 | 136.17 | 410.33 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-03:00 | 2936.96 | 19.33 | 169.83 | 459.17 | 1528.91 | 21.44 | 143.67 | 396.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:00 | 2311.85 | 18.06 | 115.33 | 391.50 | 1216.15 | 21.33 | 117.17 | 333.33 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:30 | 1787.37 | 17.94 | 103.00 | 282.33 | 954.86 | 20.23 | 99.67 | 225.00 |
October | 265.50 | 0.57 | 0.48 | 01-OCT-07:00 | 931.45 | 16.51 | 70.50 | 192.83 | 576.69 | 19.77 | 76.00 | 126.33 |
November | 135.83 | 0.68 | 0.48 | 01-NOV-10:09 | 319.48 | 14.16 | 33.83 | 50.83 | 188.89 | 17.28 | 34.50 | 10.00 |
December | 71.17 | 0.90 | 0.68 | 04-DEC-11:30 | 78.56 | 4.49 | 0.00 | 0.00 | 46.13 | 7.27 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 2237.44 | 17.83 | 1048.50 | 3069.00 | 1204.35 | 20.74 | 1056.67 | 2515.50 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 78.56 | 4.49 | 0.00 | 0.00 | 46.13 | 7.27 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.68 | 3360.68 | 19.63 | 169.83 | 474.00 | 1795.39 | 23.25 | 145.50 | 410.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.83 | 0.54 | 31-JAN-11:30 | 134.59 | 2.89 | 0.00 | 0.50 | 79.13 | 6.50 | 0.00 | 0.00 |
February | 205.83 | 0.66 | 0.48 | 19-FEB-11:09 | 297.30 | 6.87 | 0.00 | 64.50 | 176.96 | 10.96 | 0.00 | 4.67 |
March | 329.50 | 0.56 | 0.48 | 01-MAR-10:30 | 549.75 | 10.54 | 0.00 | 246.83 | 328.99 | 14.61 | 0.00 | 136.67 |
April | 421.83 | 0.52 | 0.48 | 01-APR-08:09 | 716.08 | 13.12 | 0.00 | 378.50 | 453.87 | 17.34 | 0.00 | 297.17 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:49 | 876.87 | 16.72 | 103.50 | 488.17 | 538.08 | 20.34 | 107.00 | 438.50 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-04:19 | 1062.36 | 17.03 | 122.83 | 517.67 | 609.71 | 20.07 | 101.33 | 476.50 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-03:00 | 940.39 | 15.86 | 91.67 | 501.33 | 553.05 | 19.76 | 93.33 | 436.00 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-05:40 | 751.33 | 15.15 | 61.33 | 408.00 | 450.19 | 18.78 | 65.00 | 323.83 |
September | 356.33 | 0.56 | 0.48 | 01-SEP-06:00 | 539.44 | 10.58 | 0.00 | 274.00 | 313.55 | 14.55 | 0.00 | 129.50 |
October | 265.50 | 0.61 | 0.48 | 01-OCT-08:50 | 377.43 | 8.14 | 0.00 | 143.17 | 210.14 | 12.17 | 0.00 | 5.50 |
November | 135.83 | 0.78 | 0.52 | 06-NOV-13:30 | 180.59 | 4.19 | 0.00 | 6.67 | 104.47 | 8.33 | 0.00 | 0.00 |
December | 71.17 | 0.93 | 0.81 | 04-DEC-11:30 | 52.86 | 0.31 | 0.00 | 0.00 | 31.46 | 2.40 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 705.08 | 12.91 | 379.33 | 3029.33 | 419.29 | 16.65 | 366.67 | 2248.33 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 52.86 | 0.31 | 0.00 | 0.00 | 31.46 | 2.40 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.93 | 0.81 | 1062.36 | 17.03 | 122.83 | 517.67 | 609.71 | 20.34 | 107.00 | 476.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.77 | 0.48 | 23-JAN-13:30 | 196.90 | 7.98 | 1.33 | 13.33 | 119.12 | 11.73 | 1.83 | 2.83 |
February | 205.83 | 0.59 | 0.48 | 04-FEB-12:30 | 632.62 | 15.56 | 44.50 | 127.00 | 415.07 | 21.01 | 64.33 | 63.33 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-10:30 | 1418.11 | 17.57 | 74.00 | 274.67 | 892.17 | 21.25 | 90.83 | 224.17 |
April | 421.83 | 0.52 | 0.48 | 01-APR-09:39 | 2975.21 | 21.27 | 139.50 | 369.17 | 1482.46 | 21.92 | 113.00 | 323.67 |
May | 545.00 | 0.52 | 0.48 | 01-MAY-06:00 | 2324.83 | 17.90 | 117.67 | 458.83 | 1145.45 | 19.30 | 56.50 | 403.83 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-05:49 | 2482.61 | 17.28 | 110.50 | 484.83 | 1238.80 | 18.98 | 53.33 | 418.67 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-05:19 | 2127.80 | 17.26 | 114.33 | 477.33 | 1091.89 | 18.88 | 56.17 | 407.33 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-06:49 | 1888.49 | 18.35 | 114.17 | 402.67 | 1163.04 | 20.79 | 94.33 | 339.83 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-07:30 | 1504.41 | 18.72 | 100.00 | 298.33 | 939.16 | 22.13 | 102.00 | 228.33 |
October | 265.50 | 0.56 | 0.48 | 01-OCT-09:09 | 742.21 | 16.31 | 66.83 | 194.17 | 442.90 | 19.68 | 62.33 | 97.17 |
November | 135.83 | 0.69 | 0.48 | 01-NOV-12:50 | 306.10 | 13.88 | 33.83 | 47.17 | 192.29 | 17.03 | 34.17 | 13.83 |
December | 71.17 | 0.92 | 0.77 | 04-DEC-11:30 | 68.59 | 3.97 | 0.00 | 0.00 | 39.82 | 6.89 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 1837.82 | 17.30 | 916.67 | 3147.50 | 987.84 | 19.66 | 728.83 | 2523.00 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 68.59 | 3.97 | 0.00 | 0.00 | 39.82 | 6.89 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.77 | 2975.21 | 21.27 | 139.50 | 484.83 | 1482.46 | 22.13 | 113.00 | 418.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.64 | 0.48 | 10-JAN-11:20 | 454.24 | 4.61 | 0.00 | 50.83 | 366.17 | 10.84 | 5.83 | 31.00 |
February | 205.83 | 0.55 | 0.48 | 01-FEB-12:09 | 1111.49 | 8.52 | 0.00 | 160.83 | 1891.84 | 33.21 | 170.50 | 144.67 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:20 | 5026.77 | 30.69 | 265.17 | 292.00 | 4524.29 | 33.10 | 278.33 | 273.67 |
April | 421.83 | 0.53 | 0.48 | 01-APR-07:00 | 7329.34 | 29.06 | 283.67 | 366.83 | 1323.83 | 17.78 | 9.83 | 319.00 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-06:40 | 3508.93 | 17.43 | 114.50 | 431.67 | 964.55 | 16.64 | 1.00 | 367.50 |
June | 583.50 | 0.55 | 0.48 | 01-JUN-05:40 | 1611.17 | 12.35 | 0.00 | 452.50 | 884.89 | 16.27 | 0.00 | 377.50 |
July | 562.83 | 0.55 | 0.48 | 01-JUL-05:10 | 1952.36 | 13.09 | 15.67 | 449.33 | 904.06 | 16.29 | 0.00 | 372.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-06:10 | 5222.54 | 23.87 | 237.00 | 390.00 | 1021.30 | 16.79 | 3.00 | 331.00 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 4148.37 | 28.49 | 260.50 | 307.50 | 1390.34 | 18.45 | 32.33 | 262.17 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-07:00 | 2148.72 | 24.90 | 169.17 | 222.83 | 1900.52 | 31.73 | 223.33 | 199.17 |
November | 135.83 | 0.58 | 0.48 | 01-NOV-10:09 | 572.08 | 6.36 | 0.00 | 98.67 | 578.26 | 21.18 | 56.00 | 67.33 |
December | 71.17 | 0.83 | 0.50 | 08-DEC-12:09 | 133.92 | 1.29 | 0.00 | 0.17 | 97.13 | 5.03 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 3343.87 | 19.14 | 1345.67 | 3223.17 | 1379.62 | 19.80 | 780.17 | 2745.00 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 133.92 | 1.29 | 0.00 | 0.17 | 97.13 | 5.03 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.83 | 0.50 | 7329.34 | 30.69 | 283.67 | 452.50 | 4524.29 | 33.21 | 278.33 | 377.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.74 | 0.48 | 23-JAN-11:20 | 232.96 | 8.36 | 1.67 | 19.17 | 143.68 | 11.92 | 1.67 | 7.00 |
February | 205.83 | 0.61 | 0.48 | 02-FEB-10:30 | 778.26 | 15.34 | 45.33 | 125.50 | 472.86 | 18.46 | 50.83 | 76.33 |
March | 329.50 | 0.55 | 0.48 | 01-MAR-09:20 | 1833.03 | 17.69 | 82.17 | 264.17 | 1236.98 | 21.39 | 111.50 | 214.50 |
April | 421.83 | 0.52 | 0.48 | 01-APR-06:00 | 2530.21 | 19.63 | 109.67 | 367.50 | 1596.23 | 23.25 | 140.00 | 324.17 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-04:40 | 3360.69 | 19.34 | 149.83 | 442.00 | 1795.34 | 22.52 | 145.50 | 392.33 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-03:00 | 2937.62 | 19.22 | 167.33 | 474.00 | 1299.11 | 21.37 | 136.17 | 410.33 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-03:00 | 2936.95 | 19.33 | 169.83 | 459.17 | 1528.85 | 21.44 | 143.67 | 396.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:00 | 2311.84 | 18.06 | 115.33 | 391.50 | 1216.10 | 21.33 | 117.17 | 333.33 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:30 | 1787.37 | 17.94 | 103.00 | 282.33 | 954.82 | 20.23 | 99.67 | 225.00 |
October | 265.50 | 0.57 | 0.48 | 01-OCT-07:00 | 931.44 | 16.51 | 70.50 | 192.83 | 576.67 | 19.77 | 76.00 | 126.33 |
November | 135.83 | 0.68 | 0.48 | 01-NOV-10:09 | 319.48 | 14.16 | 33.83 | 50.83 | 188.88 | 17.28 | 34.50 | 10.00 |
December | 71.17 | 0.90 | 0.68 | 04-DEC-11:30 | 78.56 | 4.49 | 0.00 | 0.00 | 46.13 | 7.27 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 2237.44 | 17.83 | 1048.50 | 3069.00 | 1204.31 | 20.74 | 1056.67 | 2515.50 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 78.56 | 4.49 | 0.00 | 0.00 | 46.13 | 7.27 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.90 | 0.68 | 3360.69 | 19.63 | 169.83 | 474.00 | 1795.34 | 23.25 | 145.50 | 410.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.83 | 0.54 | 31-JAN-11:30 | 134.59 | 2.90 | 0.00 | 0.50 | 79.12 | 6.50 | 0.00 | 0.00 |
February | 205.83 | 0.66 | 0.48 | 19-FEB-11:09 | 297.30 | 6.88 | 0.00 | 64.50 | 176.95 | 10.96 | 0.00 | 4.67 |
March | 329.50 | 0.56 | 0.48 | 01-MAR-10:30 | 549.74 | 10.54 | 0.00 | 246.83 | 328.97 | 14.61 | 0.00 | 136.67 |
April | 421.83 | 0.52 | 0.48 | 01-APR-08:09 | 716.08 | 13.13 | 0.00 | 378.50 | 453.84 | 17.34 | 0.00 | 297.17 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:49 | 876.87 | 16.72 | 103.50 | 488.17 | 538.06 | 20.34 | 107.00 | 438.50 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-04:19 | 1062.35 | 17.03 | 122.83 | 517.67 | 609.67 | 20.07 | 101.33 | 476.50 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-03:00 | 940.38 | 15.86 | 91.67 | 501.33 | 553.02 | 19.76 | 93.33 | 436.00 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-05:40 | 751.32 | 15.15 | 61.33 | 408.00 | 450.16 | 18.78 | 65.00 | 323.83 |
September | 356.33 | 0.56 | 0.48 | 01-SEP-06:00 | 539.43 | 10.58 | 0.00 | 274.00 | 313.53 | 14.55 | 0.00 | 129.50 |
October | 265.50 | 0.61 | 0.48 | 01-OCT-08:50 | 377.42 | 8.15 | 0.00 | 143.17 | 210.12 | 12.17 | 0.00 | 5.50 |
November | 135.83 | 0.78 | 0.52 | 06-NOV-13:30 | 180.58 | 4.19 | 0.00 | 6.67 | 104.46 | 8.33 | 0.00 | 0.00 |
December | 71.17 | 0.93 | 0.81 | 04-DEC-11:30 | 52.86 | 0.31 | 0.00 | 0.00 | 31.46 | 2.40 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 705.07 | 12.91 | 379.33 | 3029.33 | 419.26 | 16.65 | 366.67 | 2248.33 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 52.86 | 0.31 | 0.00 | 0.00 | 31.46 | 2.40 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.93 | 0.81 | 1062.35 | 17.03 | 122.83 | 517.67 | 609.67 | 20.34 | 107.00 | 476.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.77 | 0.48 | 23-JAN-13:30 | 196.90 | 7.98 | 1.33 | 13.33 | 119.11 | 11.73 | 1.83 | 2.83 |
February | 205.83 | 0.59 | 0.48 | 04-FEB-12:30 | 632.62 | 15.57 | 44.50 | 127.00 | 415.06 | 21.01 | 64.33 | 63.33 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-10:30 | 1418.11 | 17.57 | 74.00 | 274.67 | 892.14 | 21.25 | 90.83 | 224.17 |
April | 421.83 | 0.52 | 0.48 | 01-APR-09:39 | 2975.23 | 21.28 | 139.50 | 369.17 | 1482.41 | 21.93 | 113.17 | 323.67 |
May | 545.00 | 0.52 | 0.48 | 01-MAY-06:00 | 2324.83 | 17.90 | 117.67 | 458.83 | 1145.40 | 19.30 | 56.50 | 403.83 |
June | 583.50 | 0.53 | 0.48 | 01-JUN-05:49 | 2482.60 | 17.28 | 110.50 | 484.83 | 1238.75 | 18.98 | 53.33 | 418.67 |
July | 562.83 | 0.53 | 0.48 | 01-JUL-05:19 | 2127.78 | 17.26 | 114.33 | 477.33 | 1091.84 | 18.88 | 56.17 | 407.33 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-06:49 | 1888.48 | 18.36 | 114.17 | 402.67 | 1163.00 | 20.79 | 94.33 | 339.83 |
September | 356.33 | 0.54 | 0.48 | 01-SEP-07:30 | 1504.40 | 18.72 | 100.00 | 298.33 | 939.13 | 22.13 | 102.00 | 228.33 |
October | 265.50 | 0.56 | 0.48 | 01-OCT-09:09 | 742.20 | 16.31 | 66.83 | 194.17 | 442.88 | 19.68 | 62.33 | 97.17 |
November | 135.83 | 0.69 | 0.48 | 01-NOV-12:50 | 306.10 | 13.88 | 33.83 | 47.17 | 192.28 | 17.03 | 34.17 | 13.83 |
December | 71.17 | 0.92 | 0.77 | 04-DEC-11:30 | 68.59 | 3.97 | 0.00 | 0.00 | 39.82 | 6.89 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 1837.81 | 17.30 | 916.67 | 3147.50 | 987.80 | 19.66 | 729.00 | 2523.00 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 68.59 | 3.97 | 0.00 | 0.00 | 39.82 | 6.89 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.92 | 0.77 | 2975.23 | 21.28 | 139.50 | 484.83 | 1482.41 | 22.13 | 113.17 | 418.67 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.259452E+10 | 25460.10 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.944262E+09 | 25460.10 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151392E+09 | 25460.10 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9207188.32 | 25460.10 | 30-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.809283E+09 | 25460.10 | 06-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183876E+10 | 25460.10 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.634742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.259452E+10 | 25460.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190684E+11 | 14772.11 | 19-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143495E+11 | 14771.66 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122269E+11 | 14701.01 | 21-MAR-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.459808E+10 | 14693.31 | 07-APR-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159077E+10 | 15058.12 | 11-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.596074E+09 | 15278.61 | 16-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.476693E+09 | 15089.30 | 05-JUL-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.102798E+10 | 15191.56 | 25-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.303027E+10 | 14841.31 | 05-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.847507E+10 | 14740.69 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166692E+11 | 14756.45 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189663E+11 | 14763.65 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.476693E+09 | 14693.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190684E+11 | 15278.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.710870E+10 | 9415.62 | 23-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.521009E+10 | 9419.67 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286143E+10 | 9393.93 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.530212E+09 | 9366.95 | 04-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 65161910.84 | 9340.16 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140262E+10 | 9374.53 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.516074E+10 | 9406.85 | 07-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.673744E+10 | 9413.46 | 26-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.710870E+10 | 9419.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.994659E+10 | 7774.17 | 19-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.808872E+10 | 7774.99 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.643280E+10 | 7742.67 | 22-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160274E+10 | 7734.45 | 06-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1728308.12 | 726.41 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184729E+09 | 7742.21 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255460E+10 | 7751.19 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.744932E+10 | 7769.75 | 15-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.942966E+10 | 7774.06 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.994659E+10 | 7774.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.723505E+10 | 9943.43 | 20-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.565697E+10 | 9955.46 | 08-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.391220E+10 | 9928.29 | 13-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.642590E+09 | 9868.38 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8777968.07 | 2943.89 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.125950E+09 | 9871.15 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177489E+10 | 9907.79 | 30-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.520056E+10 | 9941.98 | 07-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677392E+10 | 9947.92 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.313309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.723505E+10 | 9955.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.831403E+10 | 27489.80 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.509916E+10 | 27489.80 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225306E+10 | 27489.80 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.236949E+09 | 27489.80 | 01-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3768295.87 | 18626.12 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143218E+10 | 27489.80 | 10-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.622098E+10 | 27489.80 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.832048E+10 | 27489.80 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.832048E+10 | 27489.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.813595E+10 | 16491.79 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.458021E+10 | 16491.79 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239383E+10 | 16491.79 | 01-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.439912E+09 | 16491.79 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164154E+09 | 16491.79 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.206822E+10 | 16491.79 | 03-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.638538E+10 | 16491.79 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.880793E+10 | 16491.79 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.329756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.880793E+10 | 16491.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.606029E+10 | 10902.91 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.399923E+10 | 10902.91 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206290E+10 | 10902.91 | 01-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.365352E+09 | 10902.91 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137990E+09 | 10902.91 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.180342E+10 | 10902.91 | 03-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.514482E+10 | 10902.91 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.619476E+10 | 10902.91 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.619476E+10 | 10902.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.847761E+10 | 8319.88 | 24-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.604601E+10 | 8314.19 | 04-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.406382E+10 | 8330.85 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.687492E+09 | 8318.61 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.210145E+09 | 8299.04 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261549E+10 | 8335.78 | 20-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.713321E+10 | 8318.94 | 07-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.861534E+10 | 8312.69 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.861534E+10 | 8335.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.602824E+10 | 10858.22 | 01-JAN-00:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421814E+10 | 10858.22 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268975E+10 | 10858.22 | 01-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453238E+09 | 10858.22 | 01-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 192561.88 | 65.76 | 27-MAY-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.203372E+09 | 10858.22 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.201268E+10 | 10858.22 | 03-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.502948E+10 | 10858.22 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.610006E+10 | 10858.22 | 01-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.610006E+10 | 10858.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164984E+11 | 29658.20 | 27-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113224E+11 | 29663.23 | 10-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.729544E+10 | 29655.20 | 22-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149830E+10 | 29619.26 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.517150E+09 | 29671.33 | 27-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.563134E+10 | 29730.71 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142497E+11 | 29646.31 | 03-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167456E+11 | 29720.12 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.737584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167456E+11 | 29730.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120766E+11 | 18282.54 | 24-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.752065E+10 | 18286.99 | 14-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.454968E+10 | 18320.45 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120050E+10 | 18194.91 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35355150.37 | 10468.22 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17304852.23 | 18054.39 | 31-AUG-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.668690E+09 | 18316.70 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.410063E+10 | 18323.30 | 20-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102677E+11 | 18281.48 | 14-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132138E+11 | 18276.44 | 30-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132138E+11 | 18323.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.856704E+10 | 11512.70 | 24-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.603255E+10 | 11515.58 | 14-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.351387E+10 | 11537.30 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.817815E+09 | 11497.94 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7306072.87 | 3236.52 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5357409.34 | 11369.36 | 31-AUG-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.439381E+09 | 11536.14 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.316013E+10 | 11538.66 | 20-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.769909E+10 | 11512.06 | 14-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.898265E+10 | 11508.91 | 30-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.392252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.898265E+10 | 11538.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126282E+11 | 10061.00 | 18-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.959151E+10 | 10070.12 | 09-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.710266E+10 | 10060.29 | 21-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178510E+10 | 10052.35 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21893675.39 | 8002.27 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16924740.27 | 9912.88 | 30-AUG-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.897224E+09 | 10061.20 | 27-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.524412E+10 | 10080.74 | 03-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113949E+11 | 10059.60 | 13-NOV-03:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131267E+11 | 10077.47 | 20-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.618093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131267E+11 | 10080.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.869921E+10 | 12068.14 | 24-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.646965E+10 | 12071.15 | 14-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.452001E+10 | 12093.80 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108910E+10 | 12010.56 | 05-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34972789.45 | 6802.33 | 27-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17504745.02 | 11636.54 | 31-AUG-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.679166E+09 | 12092.50 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.363373E+10 | 12095.28 | 20-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.773665E+10 | 12067.46 | 14-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.902536E+10 | 12058.30 | 22-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.902536E+10 | 12095.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131477E+11 | 55215.90 | 12-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.760937E+10 | 52213.14 | 27-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219454E+10 | 43802.87 | 01-MAR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73542927.56 | 4151.18 | 03-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7247447.34 | 2201.93 | 04-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1924903.38 | 5372.41 | 30-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45310315.24 | 7853.38 | 22-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.154290E+09 | 4956.64 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.113549E+11 | 43512.60 | 29-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184335E+11 | 49375.83 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.530223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184335E+11 | 55215.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.129475E+11 | 54429.03 | 12-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.758660E+10 | 47373.32 | 27-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.234737E+10 | 42559.95 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 59592109.97 | 7061.23 | 06-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5395268.57 | 2252.87 | 17-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2659662.13 | 1480.46 | 30-AUG-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6275550.46 | 3208.37 | 25-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.351638E+09 | 6796.95 | 13-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115585E+11 | 42477.25 | 29-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178948E+11 | 47945.54 | 15-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.527603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178948E+11 | 54429.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182392E+11 | 55469.65 | 12-JAN-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112584E+11 | 49346.51 | 27-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.415818E+10 | 45141.62 | 01-MAR-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.272806E+09 | 8795.28 | 03-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2189764.44 | 1197.41 | 11-MAY-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1105884.03 | 2676.73 | 31-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14100122.58 | 3643.44 | 23-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.130278E+10 | 7559.19 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164771E+11 | 44645.21 | 30-NOV-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235709E+11 | 50262.13 | 15-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.752967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.235709E+11 | 55469.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4662947.58 | 4662767.44 | 5903.60 | 20-JAN-07:01 | 5903.60 | 0.00 |
February | 0.00 | 0.00 | 7490166.97 | 7439214.59 | 6108.55 | 08-FEB-07:01 | 6108.55 | 0.00 |
March | 0.00 | 0.00 | 24211556.99 | 24016549.77 | 5750.79 | 07-MAR-07:01 | 5750.79 | 0.00 |
April | 0.00 | 0.00 | 33837041.97 | 33802157.08 | 6130.52 | 14-APR-07:05 | 6130.52 | 0.00 |
May | 0.00 | 0.00 | 0.337895E+10 | 0.337287E+10 | 32700.32 | 31-MAY-16:00 | 32700.32 | 0.00 |
June | 0.00 | 0.00 | 0.184551E+11 | 0.176653E+11 | 57983.68 | 30-JUN-11:40 | 46535.76 | 0.00 |
July | 0.00 | 0.00 | 0.262712E+11 | 0.241945E+11 | 59508.40 | 11-JUL-16:00 | 56071.51 | 0.00 |
August | 0.00 | 0.00 | 0.141661E+11 | 0.130925E+11 | 55652.26 | 11-AUG-15:50 | 55652.26 | 0.00 |
September | 0.00 | 0.00 | 0.203965E+09 | 0.190915E+09 | 8358.01 | 07-SEP-16:00 | 8358.01 | 0.00 |
October | 0.00 | 0.00 | 31287807.91 | 29976407.65 | 3399.14 | 30-OCT-06:01 | 3399.14 | 0.00 |
November | 0.00 | 0.00 | 4067433.11 | 4067433.11 | 4809.70 | 16-NOV-07:01 | 4809.70 | 0.00 |
December | 0.00 | 0.00 | 2978113.63 | 2978113.63 | 5138.67 | 21-DEC-07:01 | 5138.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.625839E+11 | 0.586231E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2978113.63 | 2978113.63 | 3399.14 | 3399.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.262712E+11 | 0.241945E+11 | 59508.40 | 56071.51 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2665327.45 | 2665327.45 | 4731.99 | 20-JAN-07:01 | 4731.99 | 0.00 |
February | 0.00 | 0.00 | 3459803.83 | 3459290.77 | 5865.43 | 09-FEB-07:01 | 5865.43 | 0.00 |
March | 0.00 | 0.00 | 7082184.76 | 7077422.53 | 6857.10 | 24-MAR-06:01 | 6857.10 | 0.00 |
April | 0.00 | 0.00 | 20363148.53 | 20362868.87 | 6963.43 | 06-APR-06:01 | 6963.43 | 0.00 |
May | 0.00 | 0.00 | 0.373914E+10 | 0.373588E+10 | 33831.26 | 31-MAY-16:00 | 33831.26 | 0.00 |
June | 0.00 | 0.00 | 0.186360E+11 | 0.178888E+11 | 57938.08 | 30-JUN-12:10 | 50792.49 | 0.00 |
July | 0.00 | 0.00 | 0.251148E+11 | 0.231533E+11 | 56178.92 | 11-JUL-15:30 | 52412.79 | 0.00 |
August | 0.00 | 0.00 | 0.129099E+11 | 0.119291E+11 | 50863.75 | 11-AUG-15:20 | 50863.75 | 0.00 |
September | 0.00 | 0.00 | 0.185761E+09 | 0.175464E+09 | 6970.13 | 07-SEP-16:00 | 6970.13 | 0.00 |
October | 0.00 | 0.00 | 7912137.14 | 7871537.10 | 6501.36 | 13-OCT-06:01 | 6501.36 | 0.00 |
November | 0.00 | 0.00 | 2161184.24 | 2161184.24 | 4551.73 | 02-NOV-06:01 | 4551.73 | 0.00 |
December | 0.00 | 0.00 | 1408942.77 | 1408942.77 | 3796.28 | 23-DEC-07:03 | 3796.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.606306E+11 | 0.569275E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1408942.77 | 1408942.77 | 3796.28 | 3796.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.251148E+11 | 0.231533E+11 | 57938.08 | 52412.79 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 98743.27 | 98743.27 | 824.85 | 19-JAN-07:01 | 824.85 | 0.00 |
February | 0.00 | 0.00 | 454683.33 | 453533.48 | 3421.42 | 09-FEB-07:01 | 3421.42 | 0.00 |
March | 0.00 | 0.00 | 3669060.36 | 3617317.08 | 3593.38 | 23-MAR-06:01 | 3593.38 | 0.00 |
April | 0.00 | 0.00 | 29087469.14 | 29077422.65 | 4653.88 | 19-APR-06:01 | 4653.88 | 0.00 |
May | 0.00 | 0.00 | 0.371303E+10 | 0.370798E+10 | 36172.44 | 31-MAY-16:00 | 36172.44 | 0.00 |
June | 0.00 | 0.00 | 0.191581E+11 | 0.183768E+11 | 63931.90 | 30-JUN-12:30 | 56679.17 | 0.00 |
July | 0.00 | 0.00 | 0.258197E+11 | 0.238143E+11 | 59288.55 | 21-JUL-14:30 | 59288.55 | 0.00 |
August | 0.00 | 0.00 | 0.129374E+11 | 0.118763E+11 | 54197.39 | 11-AUG-15:50 | 54197.39 | 0.00 |
September | 0.00 | 0.00 | 0.170994E+09 | 0.158930E+09 | 6167.46 | 07-SEP-16:00 | 6167.46 | 0.00 |
October | 0.00 | 0.00 | 5947465.60 | 5767061.10 | 4403.14 | 05-OCT-06:01 | 4403.14 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 64016.28 | 64016.28 | 426.78 | 23-DEC-07:03 | 426.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.618386E+11 | 0.579734E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.258197E+11 | 0.238143E+11 | 63931.90 | 59288.55 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 2233.59 | 7810.30 | 03-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2246.75 | 7810.26 | 27-FEB-12:18 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2395.72 | 7810.26 | 01-MAR-12:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2233.95 | 7809.75 | 04-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2299.46 | 7802.35 | 02-MAY-11:09 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 2278.06 | 7590.64 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2013.01 | 7270.98 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2165.23 | 7072.14 | 03-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 2014.89 | 7049.68 | 29-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 2050.60 | 7254.54 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 2151.54 | 7534.37 | 30-NOV-12:14 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 2143.07 | 7809.22 | 29-DEC-12:14 |
Annual Sum or Average | 0.00 | 2185.16 | ||||
Minimum of Months | 0.00 | 0.00 | 2013.01 | 7049.68 | ||
Maximum of Months | 0.00 | 0.00 | 2395.72 | 7810.30 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.226344E+10 | 0.42 | 2817.05 | 02-JAN-05:01 | 0.83 |
February | 0.188309E+10 | 0.40 | 2817.05 | 01-FEB-07:01 | 0.84 |
March | 0.167944E+10 | 0.34 | 2817.05 | 01-MAR-07:01 | 0.84 |
April | 0.165658E+10 | 0.31 | 2770.04 | 28-APR-05:02 | 0.83 |
May | 0.286199E+10 | 0.39 | 5858.76 | 11-MAY-06:03 | 1.28 |
June | 0.417019E+10 | 0.48 | 8117.01 | 22-JUN-06:02 | 1.56 |
July | 0.441679E+10 | 0.48 | 8412.73 | 12-JUL-15:10 | 1.60 |
August | 0.389606E+10 | 0.45 | 8064.87 | 11-AUG-15:50 | 1.55 |
September | 0.194287E+10 | 0.33 | 4470.83 | 01-SEP-05:02 | 1.08 |
October | 0.145627E+10 | 0.29 | 2817.05 | 30-OCT-06:01 | 0.84 |
November | 0.180626E+10 | 0.35 | 2817.05 | 06-NOV-07:01 | 0.84 |
December | 0.223853E+10 | 0.42 | 2817.05 | 01-DEC-07:01 | 0.84 |
Annual Sum or Average | 0.302715E+11 | 0.39 | |||
Minimum of Months | 0.145627E+10 | 0.29 | 2770.04 | 0.83 | |
Maximum of Months | 0.441679E+10 | 0.48 | 8412.73 | 1.60 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193490E+10 | 0.40 | 2871.41 | 02-JAN-05:01 | 0.90 |
February | 0.163809E+10 | 0.38 | 2871.41 | 01-FEB-06:01 | 0.90 |
March | 0.159543E+10 | 0.33 | 2871.41 | 01-MAR-06:01 | 0.90 |
April | 0.173573E+10 | 0.33 | 3615.17 | 21-APR-15:50 | 1.03 |
May | 0.300349E+10 | 0.43 | 6279.10 | 31-MAY-14:50 | 1.44 |
June | 0.448754E+10 | 0.54 | 7909.72 | 30-JUN-12:10 | 1.65 |
July | 0.425329E+10 | 0.50 | 8389.07 | 12-JUL-12:10 | 1.72 |
August | 0.337226E+10 | 0.45 | 7733.56 | 11-AUG-15:20 | 1.63 |
September | 0.154858E+10 | 0.31 | 2708.41 | 08-SEP-15:30 | 0.87 |
October | 0.141393E+10 | 0.30 | 2871.41 | 10-OCT-06:01 | 0.90 |
November | 0.170655E+10 | 0.37 | 2871.41 | 01-NOV-05:01 | 0.90 |
December | 0.186407E+10 | 0.38 | 2871.41 | 01-DEC-06:01 | 0.91 |
Annual Sum or Average | 0.285538E+11 | 0.39 | |||
Minimum of Months | 0.141393E+10 | 0.30 | 2708.41 | 0.87 | |
Maximum of Months | 0.448754E+10 | 0.54 | 8389.07 | 1.72 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.241385E+10 | 0.45 | 2765.66 | 01-JAN-00:42 | 0.83 |
February | 0.204221E+10 | 0.43 | 2765.66 | 01-FEB-05:11 | 0.83 |
March | 0.194616E+10 | 0.38 | 2765.66 | 01-MAR-05:01 | 0.84 |
April | 0.172581E+10 | 0.32 | 3103.86 | 21-APR-16:00 | 0.89 |
May | 0.262268E+10 | 0.38 | 6432.52 | 31-MAY-15:00 | 1.37 |
June | 0.403698E+10 | 0.48 | 7823.38 | 20-JUN-15:30 | 1.54 |
July | 0.381762E+10 | 0.45 | 8126.60 | 12-JUL-15:20 | 1.58 |
August | 0.287838E+10 | 0.39 | 7152.96 | 11-AUG-15:30 | 1.46 |
September | 0.149791E+10 | 0.30 | 2765.66 | 25-SEP-05:01 | 0.83 |
October | 0.168724E+10 | 0.33 | 2765.66 | 03-OCT-06:01 | 0.83 |
November | 0.228584E+10 | 0.45 | 2765.66 | 01-NOV-05:01 | 0.83 |
December | 0.249672E+10 | 0.46 | 2765.66 | 01-DEC-05:01 | 0.84 |
Annual Sum or Average | 0.294514E+11 | 0.40 | |||
Minimum of Months | 0.149791E+10 | 0.30 | 2765.66 | 0.83 | |
Maximum of Months | 0.403698E+10 | 0.48 | 8126.60 | 1.58 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:02 | 0.22 | 0.22 | 57.26 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 55.31 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 54.83 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:01 | 0.22 | 0.22 | 54.81 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:02 | 0.22 | 0.22 | 55.99 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 55.21 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 55.62 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:02 | 0.22 | 0.22 | 55.88 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:02 | 0.22 | 0.22 | 56.21 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 56.70 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:01 | 0.22 | 0.22 | 56.35 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 55.20 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 54.81 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.26 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.29 | 57.29 | 2233.59 | 7810.30 | 03-JAN-12:18 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55.93 | 55.93 | 2246.75 | 7810.26 | 27-FEB-12:18 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 55.43 | 55.43 | 2395.72 | 7810.26 | 01-MAR-12:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.36 | 55.36 | 2233.95 | 7809.75 | 04-APR-11:08 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.27 | 57.27 | 2299.46 | 7802.35 | 02-MAY-11:09 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 55.82 | 55.82 | 2278.06 | 7590.64 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.26 | 56.26 | 2013.01 | 7270.98 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.38 | 56.38 | 2165.23 | 7072.14 | 03-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.72 | 56.72 | 2014.89 | 7049.68 | 29-SEP-11:08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 54.73 | 54.73 | 2050.60 | 7254.54 | 31-OCT-11:08 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.83 | 56.83 | 2151.54 | 7534.37 | 30-NOV-12:14 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 55.68 | 55.68 | 2143.07 | 7809.22 | 29-DEC-12:14 |
Annual Sum or Average | 0.00 | 2185.16 | ||||||
Minimum of Months | 0.00 | 0.00 | 54.73 | 54.73 | 2013.01 | 7049.68 | ||
Maximum of Months | 0.00 | 0.00 | 57.29 | 57.29 | 2395.72 | 7810.30 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.482180E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.361348E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.272713E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.904010E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.534956E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.930502E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.111989E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.838138E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.540746E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.156818E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.370966E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.459855E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.259070E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.534956E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.482180E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.389518E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.255818E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.150608E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.392459E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.397001E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.902765E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.102657E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.652037E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.232113E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.113482E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.316210E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.399030E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.198496E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.232113E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.399030E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.608833E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.429791E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.289289E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.812517E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.368834E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.873215E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.100339E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.611288E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.474862E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.234589E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.536339E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.635909E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.314916E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.368834E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.635909E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.226344E+10 | 4662947.58 | 0.591009E+11 | 0.264188E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188309E+10 | 7490166.97 | 0.418589E+11 | 0.221419E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167944E+10 | 24211556.99 | 0.277793E+11 | 0.248769E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165658E+10 | 33837041.97 | 0.744716E+10 | 0.657656E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.286199E+10 | 0.337895E+10 | 0.160852E+10 | 0.223358E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.417019E+10 | 0.184551E+11 | 0.596074E+09 | 54800799.32 | 5340892.12 | 0.00 | 0.00 | 0.00 |
July | 0.441679E+10 | 0.262712E+11 | 0.476693E+09 | 0.130466E+09 | 62208143.31 | 0.00 | 0.00 | 0.00 |
August | 0.389606E+10 | 0.141661E+11 | 0.102991E+10 | 54345432.78 | 54561.44 | 0.00 | 0.00 | 0.00 |
September | 0.194287E+10 | 0.203965E+09 | 0.345143E+10 | 0.229215E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145627E+10 | 31287807.91 | 0.143707E+11 | 0.159179E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180626E+10 | 4067433.11 | 0.466440E+11 | 0.255617E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223853E+10 | 2978113.63 | 0.621796E+11 | 0.232971E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302715E+11 | 0.625839E+11 | 0.266543E+12 | 0.147546E+12 | 67603596.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145627E+10 | 2978113.63 | 0.476693E+09 | 54345432.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.441679E+10 | 0.262712E+11 | 0.621796E+11 | 0.264188E+11 | 62208143.31 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.193490E+10 | 2665327.45 | 0.499637E+11 | 0.259046E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163809E+10 | 3459803.83 | 0.315294E+11 | 0.223855E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159543E+10 | 7082184.76 | 0.158107E+11 | 0.262660E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173573E+10 | 20363148.53 | 0.224253E+10 | 0.789323E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.300349E+10 | 0.373914E+10 | 5587830.45 | 0.351768E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.448754E+10 | 0.186360E+11 | 0.00 | 68572976.92 | 6563402.36 | 0.00 | 0.00 | 0.00 |
July | 0.425329E+10 | 0.251148E+11 | 0.00 | 0.168546E+09 | 62545336.05 | 0.00 | 0.00 | 0.00 |
August | 0.337226E+10 | 0.129099E+11 | 2659662.13 | 0.181752E+09 | 22659.86 | 0.00 | 0.00 | 0.00 |
September | 0.154858E+10 | 0.185761E+09 | 0.725705E+09 | 0.390350E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141393E+10 | 7912137.14 | 0.102836E+11 | 0.178317E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170655E+10 | 2161184.24 | 0.414723E+11 | 0.254900E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186407E+10 | 1408942.77 | 0.559334E+11 | 0.224778E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285538E+11 | 0.606306E+11 | 0.207970E+12 | 0.152923E+12 | 69131398.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141393E+10 | 1408942.77 | 0.00 | 68572976.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.448754E+10 | 0.251148E+11 | 0.559334E+11 | 0.262660E+11 | 62545336.05 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.241385E+10 | 98743.27 | 0.767087E+11 | 0.255900E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204221E+10 | 454683.33 | 0.521952E+11 | 0.224047E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194616E+10 | 3669060.36 | 0.311398E+11 | 0.261790E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172581E+10 | 29087469.14 | 0.666362E+10 | 0.835984E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.262268E+10 | 0.371303E+10 | 0.101717E+09 | 0.516278E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.403698E+10 | 0.191581E+11 | 0.00 | 37376588.14 | 6509061.67 | 0.00 | 0.00 | 0.00 |
July | 0.381762E+10 | 0.258197E+11 | 0.00 | 0.114349E+09 | 44956478.56 | 0.00 | 0.00 | 0.00 |
August | 0.287838E+10 | 0.129374E+11 | 58197630.90 | 0.288740E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149791E+10 | 0.170994E+09 | 0.321571E+10 | 0.463575E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168724E+10 | 5947465.60 | 0.230727E+11 | 0.183502E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228584E+10 | 0.00 | 0.678252E+11 | 0.251077E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249672E+10 | 64016.28 | 0.846650E+11 | 0.222110E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294514E+11 | 0.618386E+11 | 0.345646E+12 | 0.153795E+12 | 51465540.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149791E+10 | 0.00 | 0.00 | 37376588.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.403698E+10 | 0.258197E+11 | 0.846650E+11 | 0.261790E+11 | 44956478.56 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.226344E+10 | 0.00 | 0.00 | 0.00 | 1345334.48 | 0.459532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188309E+10 | 0.00 | 0.00 | 0.00 | 2181418.40 | 0.342496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167944E+10 | 0.00 | 0.00 | 0.00 | 7116182.55 | 0.255847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165658E+10 | 0.00 | 0.00 | 0.00 | 9902770.28 | 0.737362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.286199E+10 | 0.00 | 0.00 | 0.00 | 0.886291E+09 | 0.160127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.417019E+10 | 0.00 | 0.00 | 0.00 | 0.453875E+10 | 0.596074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.441679E+10 | 0.00 | 0.00 | 0.00 | 0.630542E+10 | 0.476693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.389606E+10 | 0.00 | 0.00 | 0.00 | 0.345733E+10 | 0.102798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.194287E+10 | 0.00 | 0.00 | 0.00 | 58472754.88 | 0.340611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145627E+10 | 0.00 | 0.00 | 0.00 | 9185460.70 | 0.142164E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180626E+10 | 0.00 | 0.00 | 0.00 | 1184252.04 | 0.352891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.223853E+10 | 0.00 | 0.00 | 0.00 | 861606.01 | 0.437461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.302715E+11 | 0.00 | 0.00 | 0.00 | 0.152780E+11 | 0.213521E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145627E+10 | 0.00 | 0.00 | 0.00 | 861606.01 | 0.476693E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.441679E+10 | 0.00 | 0.00 | 0.00 | 0.630542E+10 | 0.459532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.193490E+10 | 0.00 | 0.00 | 0.00 | 758104.54 | 0.370161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163809E+10 | 0.00 | 0.00 | 0.00 | 979187.50 | 0.239428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159543E+10 | 0.00 | 0.00 | 0.00 | 1996537.82 | 0.134634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.173573E+10 | 0.00 | 0.00 | 0.00 | 5918102.01 | 0.218294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.300349E+10 | 0.00 | 0.00 | 0.00 | 0.966332E+09 | 192561.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.448754E+10 | 0.00 | 0.00 | 0.00 | 0.454012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.425329E+10 | 0.00 | 0.00 | 0.00 | 0.601239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.337226E+10 | 0.00 | 0.00 | 0.00 | 0.314812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154858E+10 | 0.00 | 0.00 | 0.00 | 53123558.48 | 0.719430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141393E+10 | 0.00 | 0.00 | 0.00 | 2237731.96 | 0.993198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170655E+10 | 0.00 | 0.00 | 0.00 | 613777.46 | 0.299139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.186407E+10 | 0.00 | 0.00 | 0.00 | 405860.25 | 0.380386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285538E+11 | 0.00 | 0.00 | 0.00 | 0.147330E+11 | 0.155209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.141393E+10 | 0.00 | 0.00 | 0.00 | 405860.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.448754E+10 | 0.00 | 0.00 | 0.00 | 0.601239E+10 | 0.380386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.241385E+10 | 0.00 | 0.00 | 0.00 | 29051.98 | 0.584695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204221E+10 | 0.00 | 0.00 | 0.00 | 131816.23 | 0.409368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.194616E+10 | 0.00 | 0.00 | 0.00 | 1078937.35 | 0.269817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172581E+10 | 0.00 | 0.00 | 0.00 | 8542705.99 | 0.639081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.262268E+10 | 0.00 | 0.00 | 0.00 | 0.966141E+09 | 99527688.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.403698E+10 | 0.00 | 0.00 | 0.00 | 0.469518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.381762E+10 | 0.00 | 0.00 | 0.00 | 0.621630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.287838E+10 | 0.00 | 0.00 | 0.00 | 0.317741E+10 | 57091746.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149791E+10 | 0.00 | 0.00 | 0.00 | 49103863.81 | 0.320161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168724E+10 | 0.00 | 0.00 | 0.00 | 1724532.28 | 0.217699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.249672E+10 | 0.00 | 0.00 | 0.00 | 18873.24 | 0.610942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294514E+11 | 0.00 | 0.00 | 0.00 | 0.151157E+11 | 0.270349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.403698E+10 | 0.00 | 0.00 | 0.00 | 0.621630E+10 | 0.610942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111282E+10 | 0.00 | 0.00 | 0.26 |
February | 0.101896E+11 | 0.00 | 0.00 | 5800.35 | 0.00 | 0.640298E+09 | 35120391.66 | 0.00 | 0.27 |
March | 0.873849E+10 | 0.00 | 0.00 | 2589550.31 | 0.00 | 91949045.21 | 0.178121E+10 | 0.00 | 0.29 |
April | 0.377415E+10 | 0.00 | 0.00 | 21628596.72 | 0.00 | 0.00 | 0.107450E+11 | 0.00 | 0.39 |
May | 0.160834E+10 | 0.00 | 0.00 | 42655644.81 | 0.00 | 0.00 | 0.222622E+11 | 0.00 | 0.86 |
June | 0.134950E+10 | 5581976.53 | 0.00 | 46154712.33 | 0.00 | 0.00 | 0.193684E+11 | 0.00 | 1.16 |
July | 0.150236E+10 | 59433831.69 | 0.00 | 42308173.49 | 9349215.06 | 0.00 | 0.148561E+11 | 0.00 | 1.07 |
August | 0.122913E+10 | 258394.16 | 0.00 | 49225261.52 | 0.00 | 0.00 | 0.215861E+11 | 0.00 | 1.05 |
September | 0.230311E+10 | 0.00 | 0.00 | 32619806.64 | 0.00 | 0.00 | 0.162907E+11 | 0.00 | 0.53 |
October | 0.555580E+10 | 0.00 | 0.00 | 10048326.10 | 0.00 | 1056327.95 | 0.501490E+10 | 0.00 | 0.30 |
November | 0.117228E+11 | 0.00 | 0.00 | 405.87 | 0.00 | 0.516402E+09 | 8162289.54 | 0.00 | 0.26 |
December | 0.142887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103367E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.738753E+11 | 65274202.38 | 0.00 | 0.247236E+09 | 9349215.06 | 0.339620E+10 | 0.111948E+12 | 0.00 | 0.56 |
Minimum of Months | 0.122913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.142887E+11 | 59433831.69 | 0.00 | 49225261.52 | 9349215.06 | 0.111282E+10 | 0.222622E+11 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.636441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677431E+10 | 0.00 | 0.00 | 0.26 |
February | 0.620933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437878E+10 | 0.00 | 0.00 | 0.27 |
March | 0.882146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117717E+10 | 0.00 | 0.00 | 0.29 |
April | 0.826684E+10 | 0.00 | 0.00 | 2970086.15 | 0.00 | 36363201.97 | 0.265963E+10 | 0.00 | 0.31 |
May | 0.377581E+10 | 0.00 | 0.00 | 20889608.02 | 0.00 | 0.00 | 0.128215E+11 | 0.00 | 0.60 |
June | 0.214466E+10 | 4655400.25 | 0.00 | 28912355.35 | 0.00 | 0.00 | 0.126167E+11 | 0.00 | 0.82 |
July | 0.205057E+10 | 39233245.93 | 0.00 | 26529125.29 | 8581367.82 | 0.00 | 0.942712E+10 | 0.00 | 0.76 |
August | 0.215034E+10 | 245718.13 | 0.00 | 26292314.00 | 0.00 | 0.00 | 0.126431E+11 | 0.00 | 0.69 |
September | 0.706777E+10 | 0.00 | 0.00 | 5660553.72 | 0.00 | 262689.01 | 0.460135E+10 | 0.00 | 0.36 |
October | 0.824044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437070E+09 | 0.00 | 0.00 | 0.27 |
November | 0.739326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528595E+10 | 0.00 | 0.00 | 0.26 |
December | 0.839641E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724745E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.708813E+11 | 44134364.31 | 0.00 | 0.111254E+09 | 8581367.82 | 0.253373E+11 | 0.547693E+11 | 0.00 | 0.43 |
Minimum of Months | 0.205057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.882146E+10 | 39233245.93 | 0.00 | 28912355.35 | 8581367.82 | 0.724745E+10 | 0.128215E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101976E+11 | 0.00 | 0.00 | 0.25 |
February | 0.254558E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658906E+10 | 0.00 | 0.00 | 0.25 |
March | 0.559056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325381E+10 | 0.00 | 0.00 | 0.27 |
April | 0.838720E+10 | 0.00 | 0.00 | 966965.14 | 0.00 | 0.417402E+09 | 0.118906E+10 | 0.00 | 0.31 |
May | 0.508517E+10 | 0.00 | 0.00 | 15819304.03 | 0.00 | 0.00 | 0.103929E+11 | 0.00 | 0.57 |
June | 0.235079E+10 | 10815087.69 | 0.00 | 25998844.55 | 0.00 | 0.00 | 0.120389E+11 | 0.00 | 0.81 |
July | 0.251880E+10 | 35462944.06 | 0.00 | 22727214.22 | 7162639.61 | 0.00 | 0.837496E+10 | 0.00 | 0.75 |
August | 0.343675E+10 | 547875.90 | 0.00 | 18684255.37 | 0.00 | 0.00 | 0.968994E+10 | 0.00 | 0.65 |
September | 0.858680E+10 | 0.00 | 0.00 | 858108.62 | 0.00 | 0.109653E+09 | 0.137335E+10 | 0.00 | 0.34 |
October | 0.559679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191253E+10 | 0.00 | 0.00 | 0.26 |
November | 0.158947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947957E+10 | 0.00 | 0.00 | 0.25 |
December | 0.677688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128904E+11 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.475699E+11 | 46825907.65 | 0.00 | 85054691.94 | 7162639.61 | 0.448500E+11 | 0.430591E+11 | 0.00 | 0.41 |
Minimum of Months | 0.677688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.858680E+10 | 35462944.06 | 0.00 | 25998844.55 | 7162639.61 | 0.128904E+11 | 0.120389E+11 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 25044843.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390307E+10 | 0.00 | 0.00 | 0.37 |
February | 27655810.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282559E+10 | 0.00 | 0.00 | 0.34 |
March | 0.238538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217127E+10 | 0.00 | 0.00 | 0.34 |
April | 0.181742E+10 | 0.00 | 0.00 | 36731.24 | 0.00 | 0.539468E+09 | 87153832.06 | 0.00 | 0.35 |
May | 0.157738E+10 | 0.00 | 0.00 | 3255145.89 | 0.00 | 3540315.85 | 0.211390E+10 | 0.00 | 0.65 |
June | 0.448994E+09 | 4099786.82 | 0.00 | 8727656.58 | 0.00 | 0.00 | 0.361312E+10 | 0.00 | 1.12 |
July | 0.548243E+09 | 11351481.63 | 0.00 | 7061668.19 | 1489885.02 | 0.00 | 0.237584E+10 | 0.00 | 1.01 |
August | 0.122790E+10 | 133666.68 | 0.00 | 3837958.83 | 0.00 | 8476420.50 | 0.185195E+10 | 0.00 | 0.75 |
September | 0.202003E+10 | 0.00 | 0.00 | 22666.66 | 0.00 | 0.398045E+09 | 36450690.08 | 0.00 | 0.39 |
October | 0.400215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149295E+10 | 0.00 | 0.00 | 0.31 |
November | 21783941.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359356E+10 | 0.00 | 0.00 | 0.35 |
December | 32295395.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468972E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.838550E+10 | 15584935.13 | 0.00 | 22941827.38 | 1489885.02 | 0.196257E+11 | 0.100784E+11 | 0.00 | 0.53 |
Minimum of Months | 21783941.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.202003E+10 | 11351481.63 | 0.00 | 8727656.58 | 1489885.02 | 0.468972E+10 | 0.361312E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 21654463.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270803E+10 | 0.00 | 0.00 | 0.41 |
February | 54177435.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197859E+10 | 0.00 | 0.00 | 0.41 |
March | 0.649483E+09 | 0.00 | 0.00 | 9793.19 | 0.00 | 0.123028E+10 | 11590178.70 | 0.00 | 0.43 |
April | 0.120185E+10 | 0.00 | 0.00 | 1420158.79 | 0.00 | 0.228541E+09 | 0.820099E+09 | 0.00 | 0.51 |
May | 0.740562E+09 | 0.00 | 0.00 | 8031926.12 | 0.00 | 144877.41 | 0.433818E+10 | 0.00 | 1.38 |
June | 0.359133E+09 | 3048900.74 | 0.00 | 9721634.60 | 0.00 | 0.00 | 0.434240E+10 | 0.00 | 1.89 |
July | 0.415723E+09 | 8682284.25 | 0.00 | 9367327.60 | 1166108.34 | 0.00 | 0.307579E+10 | 0.00 | 1.80 |
August | 0.634770E+09 | 111293.37 | 0.00 | 6304694.40 | 0.00 | 885225.28 | 0.306091E+10 | 0.00 | 1.33 |
September | 0.156027E+10 | 0.00 | 0.00 | 744010.45 | 0.00 | 0.144282E+09 | 0.414016E+09 | 0.00 | 0.53 |
October | 0.527970E+09 | 0.00 | 0.00 | 2691.74 | 0.00 | 0.100838E+10 | 5821569.92 | 0.00 | 0.40 |
November | 18138730.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252120E+10 | 0.00 | 0.00 | 0.41 |
December | 26889749.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318912E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.621062E+10 | 11842478.36 | 0.00 | 35602236.90 | 1166108.34 | 0.130095E+11 | 0.160688E+11 | 0.00 | 0.83 |
Minimum of Months | 18138730.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.156027E+10 | 8682284.25 | 0.00 | 9721634.60 | 1166108.34 | 0.318912E+10 | 0.434240E+10 | 0.00 | 1.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 84168043.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401664E+10 | 0.00 | 0.00 | 0.40 |
February | 0.426593E+09 | 0.00 | 0.00 | 65510.12 | 0.00 | 0.267979E+10 | 37578284.53 | 0.00 | 0.40 |
March | 0.951601E+09 | 0.00 | 0.00 | 1716006.07 | 0.00 | 0.154989E+10 | 0.710138E+09 | 0.00 | 0.46 |
April | 0.126756E+10 | 0.00 | 0.00 | 6758621.31 | 0.00 | 0.318241E+09 | 0.372192E+10 | 0.00 | 0.75 |
May | 0.154143E+10 | 0.00 | 0.00 | 11417078.85 | 0.00 | 5803317.20 | 0.596018E+10 | 0.00 | 1.37 |
June | 0.976095E+09 | 5646944.02 | 0.00 | 12333839.51 | 0.00 | 0.00 | 0.509835E+10 | 0.00 | 1.73 |
July | 0.106085E+10 | 21592129.79 | 0.00 | 11656658.85 | 1170422.77 | 0.00 | 0.331957E+10 | 0.00 | 1.62 |
August | 0.128249E+10 | 176865.56 | 0.00 | 11189376.97 | 0.00 | 10537159.42 | 0.472405E+10 | 0.00 | 1.52 |
September | 0.187614E+10 | 0.00 | 0.00 | 3671978.67 | 0.00 | 0.248596E+09 | 0.208558E+10 | 0.00 | 0.67 |
October | 0.984252E+09 | 0.00 | 0.00 | 730209.64 | 0.00 | 0.125614E+10 | 0.339322E+09 | 0.00 | 0.42 |
November | 0.156388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371514E+10 | 0.00 | 0.00 | 0.40 |
December | 42701808.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482429E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.106503E+11 | 27415939.38 | 0.00 | 59539279.98 | 1170422.77 | 0.186251E+11 | 0.259967E+11 | 0.00 | 0.85 |
Minimum of Months | 42701808.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.187614E+10 | 21592129.79 | 0.00 | 12333839.51 | 1170422.77 | 0.482429E+10 | 0.596018E+10 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22751052.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277947E+10 | 0.00 | 0.00 | 0.43 |
February | 50849616.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208675E+10 | 0.00 | 0.00 | 0.43 |
March | 0.449431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153696E+10 | 0.00 | 0.00 | 0.45 |
April | 0.123811E+10 | 0.00 | 0.00 | 1959917.44 | 0.00 | 0.338388E+09 | 0.103246E+10 | 0.00 | 0.60 |
May | 0.137693E+10 | 0.00 | 0.00 | 4131476.67 | 0.00 | 5066859.08 | 0.227893E+10 | 0.00 | 1.06 |
June | 0.652279E+09 | 4547432.66 | 0.00 | 7066475.22 | 0.00 | 0.00 | 0.266106E+10 | 0.00 | 1.58 |
July | 0.741876E+09 | 13885437.09 | 0.00 | 5280186.30 | 855622.54 | 0.00 | 0.155959E+10 | 0.00 | 1.37 |
August | 0.116151E+10 | 135018.59 | 0.00 | 3911511.44 | 0.00 | 7189746.43 | 0.164586E+10 | 0.00 | 1.15 |
September | 0.160976E+10 | 0.00 | 0.00 | 498918.46 | 0.00 | 0.279862E+09 | 0.321268E+09 | 0.00 | 0.56 |
October | 0.432799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118013E+10 | 0.00 | 0.00 | 0.42 |
November | 19013842.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259043E+10 | 0.00 | 0.00 | 0.42 |
December | 28187059.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323891E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.778349E+10 | 18567888.33 | 0.00 | 22848485.53 | 855622.54 | 0.140432E+11 | 0.949918E+10 | 0.00 | 0.74 |
Minimum of Months | 19013842.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.160976E+10 | 13885437.09 | 0.00 | 7066475.22 | 855622.54 | 0.323891E+10 | 0.266106E+10 | 0.00 | 1.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 69376663.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370218E+10 | 0.00 | 0.00 | 0.34 |
February | 54507590.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299301E+10 | 0.00 | 0.00 | 0.34 |
March | 99303270.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251385E+10 | 0.00 | 0.00 | 0.33 |
April | 0.174172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814765E+09 | 0.00 | 0.00 | 0.33 |
May | 0.240586E+10 | 0.00 | 0.00 | 548294.99 | 0.00 | 0.00 | 0.625481E+09 | 0.00 | 0.51 |
June | 0.596337E+09 | 877383.97 | 0.00 | 5477528.93 | 0.00 | 0.00 | 0.237659E+10 | 0.00 | 0.81 |
July | 0.618220E+09 | 9718270.12 | 0.00 | 5503728.74 | 2099474.31 | 0.00 | 0.183533E+10 | 0.00 | 0.80 |
August | 0.115657E+10 | 42894.78 | 0.00 | 3670571.81 | 0.00 | 0.00 | 0.178988E+10 | 0.00 | 0.67 |
September | 0.255080E+10 | 0.00 | 0.00 | 25808.98 | 0.00 | 0.103700E+09 | 82984107.01 | 0.00 | 0.37 |
October | 0.101188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118935E+10 | 0.00 | 0.00 | 0.29 |
November | 56683800.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322812E+10 | 0.00 | 0.00 | 0.31 |
December | 0.162668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427415E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.105239E+11 | 10638548.86 | 0.00 | 15225933.46 | 2099474.31 | 0.188191E+11 | 0.671027E+10 | 0.00 | 0.46 |
Minimum of Months | 54507590.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.255080E+10 | 9718270.12 | 0.00 | 5503728.74 | 2099474.31 | 0.427415E+10 | 0.237659E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 54577051.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271201E+10 | 0.00 | 0.00 | 0.39 |
February | 66699262.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211358E+10 | 0.00 | 0.00 | 0.38 |
March | 0.501443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135962E+10 | 0.00 | 0.00 | 0.37 |
April | 0.117730E+10 | 0.00 | 0.00 | 843471.06 | 0.00 | 0.271405E+09 | 0.538979E+09 | 0.00 | 0.40 |
May | 0.602017E+09 | 0.00 | 0.00 | 6182406.24 | 0.00 | 0.00 | 0.335722E+10 | 0.00 | 1.07 |
June | 0.292035E+09 | 1132067.07 | 0.00 | 7746023.50 | 0.00 | 0.00 | 0.341676E+10 | 0.00 | 1.51 |
July | 0.297177E+09 | 10054633.99 | 0.00 | 8202518.99 | 1187181.36 | 0.00 | 0.266919E+10 | 0.00 | 1.53 |
August | 0.437839E+09 | 31554.27 | 0.00 | 6800508.20 | 0.00 | 0.00 | 0.313250E+10 | 0.00 | 1.25 |
September | 0.126722E+10 | 0.00 | 0.00 | 1409540.23 | 0.00 | 24465323.78 | 0.934630E+09 | 0.00 | 0.47 |
October | 0.887327E+09 | 0.00 | 0.00 | 30058.89 | 0.00 | 0.717153E+09 | 13573365.97 | 0.00 | 0.34 |
November | 41736587.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230735E+10 | 0.00 | 0.00 | 0.35 |
December | 0.109726E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304269E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.573510E+10 | 11218255.33 | 0.00 | 31214527.12 | 1187181.36 | 0.125483E+11 | 0.140628E+11 | 0.00 | 0.71 |
Minimum of Months | 41736587.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.126722E+10 | 10054633.99 | 0.00 | 8202518.99 | 1187181.36 | 0.304269E+10 | 0.341676E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 58232107.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705733E+10 | 0.00 | 0.00 | 0.65 |
February | 0.141687E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509576E+10 | 0.00 | 0.00 | 0.59 |
March | 0.263935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403879E+10 | 0.00 | 0.00 | 0.53 |
April | 0.143499E+10 | 0.00 | 0.00 | 825170.53 | 0.00 | 0.171135E+10 | 0.637639E+09 | 0.00 | 0.49 |
May | 0.211148E+10 | 0.00 | 0.00 | 2670878.92 | 0.00 | 0.659055E+09 | 0.160205E+10 | 0.00 | 0.77 |
June | 0.137775E+10 | 1961045.79 | 0.00 | 5356682.44 | 0.00 | 0.250208E+09 | 0.199912E+10 | 0.00 | 1.06 |
July | 0.111018E+10 | 20586011.43 | 0.00 | 7140909.57 | 1453257.77 | 0.219030E+09 | 0.168409E+10 | 0.00 | 1.13 |
August | 0.152938E+10 | 63653.67 | 0.00 | 6271618.02 | 0.00 | 0.439157E+09 | 0.230432E+10 | 0.00 | 1.11 |
September | 0.183888E+10 | 0.00 | 0.00 | 1248248.88 | 0.00 | 0.127754E+10 | 0.891346E+09 | 0.00 | 0.55 |
October | 0.643492E+09 | 0.00 | 0.00 | 124814.96 | 0.00 | 0.276307E+10 | 85136702.97 | 0.00 | 0.46 |
November | 68492486.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665478E+10 | 0.00 | 0.00 | 0.64 |
December | 74811353.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859831E+10 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.106533E+11 | 22610710.89 | 0.00 | 23638323.32 | 1453257.77 | 0.387644E+11 | 0.920371E+10 | 0.00 | 0.72 |
Minimum of Months | 58232107.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219030E+09 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.211148E+10 | 20586011.43 | 0.00 | 7140909.57 | 1453257.77 | 0.859831E+10 | 0.230432E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 58135818.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277883E+10 | 0.00 | 0.00 | 0.40 |
February | 50376320.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227334E+10 | 0.00 | 0.00 | 0.40 |
March | 0.237451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174640E+10 | 0.00 | 0.00 | 0.39 |
April | 0.132084E+10 | 0.00 | 0.00 | 908411.47 | 0.00 | 0.334069E+09 | 0.501342E+09 | 0.00 | 0.44 |
May | 0.140729E+10 | 0.00 | 0.00 | 1991787.88 | 0.00 | 438550.10 | 0.125569E+10 | 0.00 | 0.75 |
June | 0.572024E+09 | 648125.28 | 0.00 | 5069946.67 | 0.00 | 0.00 | 0.190603E+10 | 0.00 | 1.17 |
July | 0.570966E+09 | 13062652.04 | 0.00 | 4371722.26 | 1269136.63 | 0.00 | 0.131181E+10 | 0.00 | 1.08 |
August | 0.707949E+09 | 41392.32 | 0.00 | 4211665.24 | 0.00 | 0.00 | 0.179931E+10 | 0.00 | 0.99 |
September | 0.173858E+10 | 0.00 | 0.00 | 549407.70 | 0.00 | 57405084.29 | 0.399725E+09 | 0.00 | 0.47 |
October | 0.813064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894809E+09 | 0.00 | 0.00 | 0.36 |
November | 47299735.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237017E+10 | 0.00 | 0.00 | 0.37 |
December | 0.116913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308390E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.764089E+10 | 13752169.63 | 0.00 | 17102941.22 | 1269136.63 | 0.135394E+11 | 0.717392E+10 | 0.00 | 0.60 |
Minimum of Months | 47299735.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.173858E+10 | 13062652.04 | 0.00 | 5069946.67 | 1269136.63 | 0.308390E+10 | 0.190603E+10 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 34321741.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353872E+10 | 0.00 | 0.00 | 0.31 |
February | 73460499.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260887E+10 | 0.00 | 0.00 | 0.30 |
March | 0.440960E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183771E+10 | 0.00 | 0.00 | 0.30 |
April | 0.178263E+10 | 0.00 | 0.00 | 175557.95 | 0.00 | 0.300640E+09 | 0.211211E+09 | 0.00 | 0.31 |
May | 0.941217E+09 | 0.00 | 0.00 | 4846562.52 | 0.00 | 0.00 | 0.275940E+10 | 0.00 | 0.65 |
June | 0.283368E+09 | 1549715.62 | 0.00 | 9803843.88 | 0.00 | 0.00 | 0.389471E+10 | 0.00 | 1.13 |
July | 0.345498E+09 | 12288479.59 | 0.00 | 8115818.58 | 1509700.85 | 0.00 | 0.266178E+10 | 0.00 | 1.00 |
August | 0.705487E+09 | 59752.73 | 0.00 | 5416650.34 | 0.00 | 0.00 | 0.249492E+10 | 0.00 | 0.76 |
September | 0.197917E+10 | 0.00 | 0.00 | 263422.89 | 0.00 | 0.107092E+09 | 0.319645E+09 | 0.00 | 0.35 |
October | 0.770080E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109117E+10 | 0.00 | 0.00 | 0.28 |
November | 33115455.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319567E+10 | 0.00 | 0.00 | 0.30 |
December | 40236082.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413212E+10 | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.742955E+10 | 13897947.94 | 0.00 | 28621856.16 | 1509700.85 | 0.168120E+11 | 0.123417E+11 | 0.00 | 0.50 |
Minimum of Months | 33115455.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.197917E+10 | 12288479.59 | 0.00 | 9803843.88 | 1509700.85 | 0.413212E+10 | 0.389471E+10 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 35783049.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282366E+10 | 0.00 | 0.00 | 0.42 |
February | 0.147987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212271E+10 | 0.00 | 0.00 | 0.42 |
March | 0.939754E+09 | 0.00 | 0.00 | 64935.37 | 0.00 | 0.112220E+10 | 50430616.02 | 0.00 | 0.45 |
April | 0.133804E+10 | 0.00 | 0.00 | 1946345.81 | 0.00 | 0.164104E+09 | 0.111299E+10 | 0.00 | 0.55 |
May | 0.698825E+09 | 0.00 | 0.00 | 8645581.94 | 0.00 | 0.00 | 0.467705E+10 | 0.00 | 1.43 |
June | 0.298793E+09 | 1702642.71 | 0.00 | 9887378.57 | 0.00 | 0.00 | 0.439933E+10 | 0.00 | 1.86 |
July | 0.324734E+09 | 9708344.19 | 0.00 | 9556275.84 | 1387412.01 | 0.00 | 0.318982E+10 | 0.00 | 1.76 |
August | 0.562527E+09 | 50877.70 | 0.00 | 7099771.02 | 0.00 | 0.00 | 0.343119E+10 | 0.00 | 1.36 |
September | 0.171750E+10 | 0.00 | 0.00 | 1205438.29 | 0.00 | 65988705.71 | 0.751840E+09 | 0.00 | 0.57 |
October | 0.895133E+09 | 0.00 | 0.00 | 33579.33 | 0.00 | 0.894039E+09 | 16251641.59 | 0.00 | 0.42 |
November | 32811765.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269036E+10 | 0.00 | 0.00 | 0.42 |
December | 40539109.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331036E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.703243E+10 | 11461864.60 | 0.00 | 38439306.18 | 1387412.01 | 0.131934E+11 | 0.176289E+11 | 0.00 | 0.84 |
Minimum of Months | 32811765.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.171750E+10 | 9708344.19 | 0.00 | 9887378.57 | 1387412.01 | 0.331036E+10 | 0.467705E+10 | 0.00 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204329E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406085E+10 | 0.00 | 0.00 | 0.40 |
February | 0.742991E+09 | 0.00 | 0.00 | 193143.44 | 0.00 | 0.259237E+10 | 72948449.22 | 0.00 | 0.41 |
March | 0.132334E+10 | 0.00 | 0.00 | 2616807.84 | 0.00 | 0.130625E+10 | 0.889920E+09 | 0.00 | 0.47 |
April | 0.145555E+10 | 0.00 | 0.00 | 7878053.00 | 0.00 | 0.195362E+09 | 0.405807E+10 | 0.00 | 0.78 |
May | 0.133649E+10 | 0.00 | 0.00 | 12124819.97 | 0.00 | 0.00 | 0.618776E+10 | 0.00 | 1.39 |
June | 0.783924E+09 | 3306927.20 | 0.00 | 12785171.33 | 0.00 | 0.00 | 0.511762E+10 | 0.00 | 1.70 |
July | 0.786388E+09 | 25132116.83 | 0.00 | 12106203.41 | 1238057.80 | 0.00 | 0.342246E+10 | 0.00 | 1.56 |
August | 0.100457E+10 | 79349.97 | 0.00 | 12530023.38 | 0.00 | 0.00 | 0.511391E+10 | 0.00 | 1.53 |
September | 0.203956E+10 | 0.00 | 0.00 | 4962319.25 | 0.00 | 72409603.98 | 0.273411E+10 | 0.00 | 0.72 |
October | 0.138066E+10 | 0.00 | 0.00 | 1100338.88 | 0.00 | 0.103680E+10 | 0.509874E+09 | 0.00 | 0.43 |
November | 0.320444E+09 | 0.00 | 0.00 | 8987.93 | 0.00 | 0.373796E+10 | 10346194.74 | 0.00 | 0.40 |
December | 60854041.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495574E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.114391E+11 | 28518394.00 | 0.00 | 66305868.43 | 1238057.80 | 0.179577E+11 | 0.281170E+11 | 0.00 | 0.85 |
Minimum of Months | 60854041.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.203956E+10 | 25132116.83 | 0.00 | 12785171.33 | 1238057.80 | 0.495574E+10 | 0.618776E+10 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 35694948.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280238E+10 | 0.00 | 0.00 | 0.42 |
February | 0.119590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214953E+10 | 0.00 | 0.00 | 0.42 |
March | 0.692110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140130E+10 | 0.00 | 0.00 | 0.44 |
April | 0.137426E+10 | 0.00 | 0.00 | 2206092.33 | 0.00 | 0.215498E+09 | 0.117761E+10 | 0.00 | 0.60 |
May | 0.103482E+10 | 0.00 | 0.00 | 4862187.33 | 0.00 | 0.00 | 0.263538E+10 | 0.00 | 1.06 |
June | 0.506007E+09 | 1007862.85 | 0.00 | 7506353.53 | 0.00 | 0.00 | 0.275724E+10 | 0.00 | 1.55 |
July | 0.530571E+09 | 15014086.11 | 0.00 | 5691529.39 | 912202.22 | 0.00 | 0.173019E+10 | 0.00 | 1.32 |
August | 0.821827E+09 | 61352.61 | 0.00 | 4824426.37 | 0.00 | 0.00 | 0.203481E+10 | 0.00 | 1.14 |
September | 0.184257E+10 | 0.00 | 0.00 | 768922.82 | 0.00 | 93232780.36 | 0.514504E+09 | 0.00 | 0.56 |
October | 0.797240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992750E+09 | 0.00 | 0.00 | 0.42 |
November | 38773116.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265944E+10 | 0.00 | 0.00 | 0.42 |
December | 40079534.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327958E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.783354E+10 | 16083301.57 | 0.00 | 25859511.77 | 912202.22 | 0.135937E+11 | 0.108497E+11 | 0.00 | 0.73 |
Minimum of Months | 35694948.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.184257E+10 | 15014086.11 | 0.00 | 7506353.53 | 912202.22 | 0.327958E+10 | 0.275724E+10 | 0.00 | 1.55 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:22
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.637411E+10 | 0.184242E+11 | 0.00 | 0.182338E+12 | 0.104090E+11 |
February | 0.497012E+11 | 0.147646E+11 | 0.00 | 0.160841E+12 | 0.622004E+10 |
March | 0.211081E+12 | 0.174540E+11 | 0.00 | 0.193912E+12 | 0.208592E+10 |
April | 0.357976E+12 | 0.117966E+11 | 0.00 | 0.206648E+12 | 0.202872E+09 |
May | 0.433859E+12 | 0.708649E+10 | 0.00 | 0.263374E+12 | 0.136534E+11 |
June | 0.442682E+12 | 0.403836E+10 | 0.00 | 0.224546E+12 | 0.700233E+11 |
July | 0.402199E+12 | 0.313839E+10 | 0.00 | 0.232685E+12 | 0.957398E+11 |
August | 0.304817E+12 | 0.513233E+10 | 0.00 | 0.236891E+12 | 0.497976E+11 |
September | 0.148919E+12 | 0.749253E+10 | 0.00 | 0.219666E+12 | 0.736828E+09 |
October | 0.686873E+11 | 0.133316E+11 | 0.00 | 0.184397E+12 | 0.482559E+09 |
November | 0.899355E+10 | 0.165806E+11 | 0.00 | 0.185080E+12 | 0.924776E+10 |
December | -0.158645E+11 | 0.176753E+11 | 0.00 | 0.186193E+12 | 0.140562E+11 |
Annual Sum or Average | 0.240668E+13 | 0.136915E+12 | 0.00 | 0.247657E+13 | 0.272655E+12 |
Minimum of Months | -0.158645E+11 | 0.313839E+10 | 0.00 | 0.160841E+12 | 0.202872E+09 |
Maximum of Months | 0.442682E+12 | 0.184242E+11 | 0.00 | 0.263374E+12 | 0.957398E+11 |