Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2023-10-16 08:35:20
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1782.06 | 357.69 | 357.69 |
Net Site Energy | 1782.06 | 357.69 | 357.69 |
Total Source Energy | 5455.82 | 1095.06 | 1095.06 |
Net Source Energy | 5455.82 | 1095.06 | 1095.06 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 1.34 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 615.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 202.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 49.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 88.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 16.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 90.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1691.82 | 90.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 1.34 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 615.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 202.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 49.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 88.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 16.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 90.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 1.34 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 615.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 202.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 49.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 88.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 16.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 90.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 141.63 | 18.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 339.57 | 18.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 141.63 | 18.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 339.57 | 18.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1691.822 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1691.822 | 100.00 |
Total On-Site and Utility Electric Sources | 1691.822 | 100.00 |
Total Electricity End Uses | 1691.822 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 142.73 | 99.83 |
Air to Air Heat Recovery for Heating | 0.24 | 0.17 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 142.97 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 20.00 |
Time Setpoint Not Met During Occupied Cooling | 489.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1332.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.9322 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.9322 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.9322 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 28-JUL-15:30 | 04-FEB-06:00 | - | - | - | - | - | - | - | - | - | - | 24-JAN-12:09 |
Heating | 0.00 | 2487.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 71361.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 16818.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42072.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 827.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12732.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 907.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7798.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 144721.22 | 10285.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 2487.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 71361.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 16818.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 7527.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 57.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 827.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 12732.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 907.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 7798.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 4.26 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1949.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 642.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 157.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 280.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 52.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 97.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5358.00 | 97.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 391.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 128.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 56.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 10.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1075.43 | 19.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 391.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 128.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 56.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 10.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 19.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1075.43 | 19.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.70 | 0.277603 | 0.282000 | 0.761326 | 0.740274 | 0.500000 | 0.001372 |
CORE_MID VAV BOX COMPONENT | 1.94 | 0.385454 | 0.370000 | 0.719408 | 1.00 | 0.500000 | 0.000988 |
CORE_TOP VAV BOX COMPONENT | 2.11 | 0.355122 | 0.360000 | 0.759749 | 0.946993 | 0.500000 | 0.001073 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.648841 | 0.243498 | 0.247000 | 0.160264 | 0.649329 | 0.500000 | 0.001565 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.612849 | 0.163208 | 0.200000 | 0.122570 | 0.435221 | 0.500000 | 0.002334 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.664569 | 0.237735 | 0.241000 | 0.160161 | 0.633961 | 0.500000 | 0.001603 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.693683 | 0.144180 | 0.200000 | 0.138737 | 0.384480 | 0.500000 | 0.002643 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.543385 | 0.290755 | 0.295000 | 0.160298 | 0.775346 | 0.500000 | 0.001310 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.542551 | 0.184355 | 0.200000 | 0.108510 | 0.491613 | 0.500000 | 0.002067 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.552374 | 0.286023 | 0.290000 | 0.160189 | 0.762727 | 0.500000 | 0.001332 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.568170 | 0.176030 | 0.200000 | 0.113634 | 0.469414 | 0.500000 | 0.002164 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.551704 | 0.286370 | 0.275000 | 0.151719 | 0.763654 | 0.500000 | 0.001330 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.580366 | 0.172343 | 0.200000 | 0.116073 | 0.459581 | 0.500000 | 0.002211 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.561833 | 0.281207 | 0.270000 | 0.151695 | 0.749886 | 0.500000 | 0.001355 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.612876 | 0.163190 | 0.200000 | 0.122575 | 0.435173 | 0.500000 | 0.002335 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25397.36 |
CORE_MID VAV BOX REHEAT COIL | 23998.97 |
CORE_TOP VAV BOX REHEAT COIL | 25344.73 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 9094.82 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 5947.68 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 9081.41 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 5952.31 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5347.45 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3619.83 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5343.79 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3790.76 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 6439.27 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 4247.55 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 6419.62 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 4256.08 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.45 | 1.30 | 4.91 | 1.30 | 4.52 | 4.52 | 0.300000 | 0.288448 | 4.52 |
PACU_VAV_MID | 2.13 | 1.26 | 4.25 | 1.26 | 3.77 | 3.77 | 0.300000 | 0.334165 | 3.77 |
PACU_VAV_TOP | 2.37 | 1.34 | 4.73 | 1.55 | 4.50 | 4.50 | 0.300000 | 0.343575 | 4.50 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.52 |
PACU_VAV_MID_OA_CONTROLLER | 3.77 |
PACU_VAV_TOP_OA_CONTROLLER | 4.50 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.52 | 112257.05 | 0.701083 | 1.51 | 37415.28 | 0.701083 |
PACU_VAV_MID COOLING COIL | 3.77 | 93742.04 | 0.701083 | 1.26 | 31244.22 | 0.701083 |
PACU_VAV_TOP COOLING COIL | 4.50 | 111670.81 | 0.701083 | 1.50 | 37219.88 | 0.701083 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 4352.77 |
PACU_VAV_MID HEATING COIL | 5611.74 |
PACU_VAV_TOP HEATING COIL | 4396.85 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.52 |
PACU_VAV_MID FAN | 3.77 |
PACU_VAV_TOP FAN | 4.50 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
PACU_VAV_MID OA HEAT RECOVERY | 1.20 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.30 | 23.60 | 20.30 | 19.40 | 20.90 | 21.60 | 24.10 | 26.40 | 27.70 | 28.10 | 28.00 | 27.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Miami Intl Ap FL USA TMY3 WMO#=722020 | 25.82 | -80.30 | -5.00 | 11.00 | 101193 | 1.2027 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.49 | 8.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 30.766 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 1.029 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 1.013 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 6 | 0.167 | 1.375 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7377 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7531 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4931 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 7 | -0.27613173E-12 | 0.13648587E-14 | -0.80406974E-13 | 0.78369587E-16 |
43 | 6 | 0.25651297E-07 | 0.27955499E-09 | 0.59014154E-08 | -0.11905989E-12 |
44 | 5 | -0.17465063E-03 | 0.24416492E-05 | -0.90019538E-04 | 0.58421144E-08 |
45 | 4 | 0.27387862 | 0.12098825E-02 | 0.93122264E-01 | -0.31012301E-04 |
46 | 3 | -6.9041115 | 0.38080793E-01 | -2.2314619 | 0.27235146E-01 |
47 | 2 | 39.676056 | 0.13726811 | 14.823303 | -0.32003278 |
48 | 1 | -79.629469 | 0.62686726E-01 | -28.745292 | 1.0590931 |
49 | 0 | 46.824345 | 0.12759187E-02 | 16.300942 | |
50 | 7 | -0.27182421E-12 | 0.13107754E-14 | -0.81108189E-13 | 0.79120162E-16 |
51 | 6 | 0.25844325E-07 | 0.27588229E-09 | 0.59440225E-08 | -0.12008605E-12 |
52 | 5 | -0.17564658E-03 | 0.24062150E-05 | -0.90521036E-04 | 0.58837691E-08 |
53 | 4 | 0.27506755 | 0.11908598E-02 | 0.93548701E-01 | -0.31177608E-04 |
54 | 3 | -6.9277136 | 0.37441415E-01 | -2.2384615 | 0.27350651E-01 |
55 | 2 | 39.753961 | 0.13483533 | 14.852153 | -0.32090009 |
56 | 1 | -79.689237 | 0.61525268E-01 | -28.771196 | 1.0603666 |
57 | 0 | 46.824344 | 0.12512697E-02 | 16.300293 | |
58 | 6 | 0.21465343E-07 | 0.35044740E-09 | 0.49771822E-08 | -0.96989815E-13 |
59 | 5 | -0.15274237E-03 | 0.31655188E-05 | -0.78941554E-04 | 0.49363227E-08 |
60 | 4 | 0.24727258 | 0.16154212E-02 | 0.83601931E-01 | -0.27359285E-04 |
61 | 3 | -6.3748395 | 0.52179222E-01 | -2.0745682 | 0.24648141E-01 |
62 | 2 | 37.927790 | 0.19236366 | 14.173893 | -0.30057625 |
63 | 1 | -78.286849 | 0.89555956E-01 | -28.161423 | 1.0304865 |
64 | 0 | 46.824354 | 0.18576719E-02 | 16.316151 | |
65 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
66 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
67 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
68 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
69 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
70 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
71 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
72 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
73 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
74 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
75 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
76 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
77 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
78 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
79 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
80 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
81 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
82 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
83 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
84 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
85 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
86 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
87 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
88 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
89 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
90 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
91 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
92 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
93 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
94 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
95 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
96 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
97 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
98 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
99 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
100 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
101 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
102 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
103 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
104 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
105 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 35 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
2 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 36 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
3 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 37 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 | ||
4 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 38 | 1 | VerySmooth | 2.864 | 2.864 | 1.000 | 0.231 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.92411E-002 | 0.14129 | 0.63052 | 0.63052 | 0.23000 | 0.16588 | 0.25006 | 0.00000 | 0.84000 | 0.84000 | 0.10752 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.384E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.394E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.384E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.394E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1.950E-002 | 9.403E-005 | 1.424E-004 | 0.123 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1.300E-002 | 9.902E-005 | 1.424E-004 | 0.130 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.424E-004 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.424E-004 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 2.888E-002 | 1.739E-005 | 1.550E-005 | 5.135E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7820E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8134E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0181E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0440E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9027E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9225E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2338E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2473E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9819E-002 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9661E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6264E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0903E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7783E-002 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2064E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5814E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.6580E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7834E-003 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8215E-003 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0196E-003 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0529E-003 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9043E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9295E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2337E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2471E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7688E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1328E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5537E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9561E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6705E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8025E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0059E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4048E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3729E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3849E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1982E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2069E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0433E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0466E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6073E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6119E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1651E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1945E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8406E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8642E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6063E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6230E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2337E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2471E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9738E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1336E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5484E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.7639E-003 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4472E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.1489E-003 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5814E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6580E-003 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1646E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1937E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8399E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8624E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6050E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6181E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2338E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2473E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9988E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7894E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6379E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5481E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8922E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4574E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0059E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4048E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8886E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9115E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6164E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6388E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5770E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5899E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6074E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6120E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.2659E-002 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.7015E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.8654E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.8619E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1668E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8283E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 2.9043E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.3460E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6315E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0551E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.4316E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.8870E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.5673E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7457E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 2.9340E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.3660E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2577E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4896E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8055E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1881E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.6998E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.0138E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.9043E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3460E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.8879E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7286E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.5473E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4993E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.8151E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4168E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9340E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.3660E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.2657E-002 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.7011E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.8651E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.8615E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1664E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8280E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 2.9041E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.3459E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6314E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0550E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.4315E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.8869E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.5671E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7455E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 2.9337E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.3658E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2578E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4895E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8056E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1880E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.6997E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.0130E-003 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.9041E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3459E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.8880E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7285E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.5473E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4993E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.8150E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4167E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9338E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.3659E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37430.29457 | 37430.29457 | 2.69974 | 2.69974 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 2148.78687 | 2148.78687 | 9.14512E-002 | 0.42469 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 26993.82390 | 26993.82390 | 1.94435 | 1.94435 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 28.24200 | 1.71578E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 7776.26676 | 7776.26676 | 0.32658 | 0.42469 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 29012.22646 | 29012.22646 | 2.11041 | 2.11041 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.13300 | 1.71671E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 15184.68382 | 15184.68382 | 0.64347 | 0.64347 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8919.53645 | 8919.53645 | 0.64884 | 0.64884 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 6401.02876 | 6401.02876 | 0.27263 | 0.27263 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 8424.79785 | 8424.79785 | 0.61285 | 0.61285 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 30.82150 | 1.71627E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 4185.49988 | 4185.49988 | 0.17829 | 0.17829 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 9135.75154 | 9135.75154 | 0.66457 | 0.66457 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 6391.63927 | 6391.63927 | 0.27223 | 0.27223 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 9536.03067 | 9536.03067 | 0.69368 | 0.69368 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 4188.73321 | 4188.73321 | 0.17843 | 0.17843 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 7469.93786 | 7469.93786 | 0.54338 | 0.54338 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.92700 | 1.71648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 3616.91095 | 3616.91095 | 0.15348 | 0.15348 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 7458.51788 | 7458.51788 | 0.54255 | 0.54255 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 30.82150 | 1.71627E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 2402.04986 | 2402.04986 | 0.10196 | 0.10196 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 7593.52427 | 7593.52427 | 0.55237 | 0.55237 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 3605.01328 | 3605.01328 | 0.15297 | 0.15297 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 7810.71622 | 7810.71622 | 0.56817 | 0.56817 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 32.03867 | 1.71650E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 2409.82328 | 2409.82328 | 0.10230 | 0.10230 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7584.22775 | 7584.22775 | 0.55170 | 0.55170 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 31.81533 | 1.71646E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 4541.23834 | 4541.23834 | 0.19303 | 0.19303 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 7978.28649 | 7978.28649 | 0.58037 | 0.58037 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 30.46417 | 1.71620E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 2994.59560 | 2994.59560 | 0.12733 | 0.12733 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 7723.47525 | 7723.47525 | 0.56183 | 0.56183 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.20000 | 1.71672E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 4527.49169 | 4527.49169 | 0.19244 | 0.19244 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 8425.21369 | 8425.21369 | 0.61288 | 0.61288 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26200 | 1.71654E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 3000.55944 | 3000.55944 | 0.12758 | 0.12758 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70000 | 6.99286E-003 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 73205.54 | 4.52059 | 4.52059 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 4635.14 | 0.93541 | 0.93541 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 63239.78 | 3.77499 | 3.77499 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 5277.61 | 1.06507 | 1.06507 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73628.07 | 4.49698 | 4.49698 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 5906.44 | 1.54505 | 1.54505 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.69974 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27760 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28200 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.76133 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74027 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37247E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25397.35821 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.94435 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38545 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.37000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.71941 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.88446E-004 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 23998.97495 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11041 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35512 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.75975 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94699 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07287E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 25344.73003 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64884 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24350 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24700 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16026 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64933 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.56469E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9094.82191 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61285 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16321 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12257 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43522 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33445E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5947.68431 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66457 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23774 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24100 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16016 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63396 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60262E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9081.41265 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69368 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14418 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13874 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38448 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64253E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5952.30760 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.54338 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29075 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29500 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16030 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77535 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.31038E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5347.45226 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.54255 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18435 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.10851 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49161 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06667E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3619.82759 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55237 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28602 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16019 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76273 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33206E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 5343.78811 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56817 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17603 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11363 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46941 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16440E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 3790.75752 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55170 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28637 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27500 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15172 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76365 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33045E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6439.27377 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.58037 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17234 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.11607 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45958 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.21071E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4247.54950 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56183 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28121 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15170 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74989 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35487E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6419.61996 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61288 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16319 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12258 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43517 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33470E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 4256.07857 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.45311 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30396 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.90622 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30396 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.52059 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.52059 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.28845 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.12556 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.26147 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.25112 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.26147 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.77499 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 3.77499 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.33416 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.36518 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34148 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.73036 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 1.54505 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.49698 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.49698 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.34358 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.52059 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 3.77499 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.49698 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.52059 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.52059 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 112257.05213 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.50671 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37415.27548 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 4352.77431 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.52059 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.77499 |
158 | HeatExchanger:AirToAir:SensibleAndLatent | PACU_VAV_MID OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.19517 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 3.77499 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 93742.04352 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.25820 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 31244.22311 |
164 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
165 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 5611.73917 |
166 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 3.77499 |
167 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.49698 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.49698 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 111670.80620 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.70108 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.49884 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 37219.87971 |
173 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.70108 |
174 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 4396.84633 |
175 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.49698 |
176 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
177 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
179 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
180 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 112073.71 | 382411.37 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 5.2224 | 4.1340 | 2.7819 | 1.1996 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 93588.94 | 319338.72 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 4.3610 | 3.4522 | 2.3231 | 1.0017 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 111488.42 | 380414.28 | 11.65 | 2.97 | 3.34 | 3.52 | 3.64 | 10.14 | 11.39 | 12.03 | 12.43 | 5.1951 | 4.1124 | 2.7674 | 1.1933 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.375 | 1.140 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.029 | 0.892 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_NORTH_0.23 | N/A | 2.864 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_EAST_0.23 | N/A | 2.864 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | N/A | 2.864 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.013 | 0.880 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5037_SHGC_WEST_0.23 | N/A | 2.864 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2101458038 | 0.2625372201 | Pass | Pass | 0.2385895443 | 0.4240639028 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.7578249514E-002 | 9.2069088417E-002 | Pass | Pass | 0.2055489616 | 0.4401071550 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.8571457357E-002 | 4.7480356041E-002 | Pass | Pass | 0.2085331431 | 0.3941153512 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.5097035418E-002 | 5.1478348112E-002 | Pass | Pass | 0.3429825340 | 1.0276374164 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1603743771 | 0.2383774760 | Pass | Pass | 0.1960155979 | 0.3956737719 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1439790169 | 0.2184396432 | Pass | Pass | 0.1877423160 | 0.3886373106 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1472929038 | 0.2193341791 | Pass | Pass | 0.1879227716 | 0.3878458533 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2217922946 | 0.3097471426 | Pass | Pass | 0.1895811605 | 0.3898960374 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2468785616 | 0.3946553367 | Pass | Pass | 0.2200140721 | 0.4297633265 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1930111723 | 0.2923571879 | Pass | Pass | 0.1881197997 | 0.3867782132 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1881183428 | 0.2373157183 | Pass | Pass | 0.2374041259 | 0.4230377038 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2477611007 | 0.3219401132 | Pass | Pass | 0.2416278448 | 0.4255299053 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2709867352 | 0.3963648742 | Pass | Pass | 0.2682169660 | 0.4525706159 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2140119634 | 0.2737083856 | Pass | Pass | 0.2376874535 | 0.4226275696 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1568956760 | 0.2299057973 | Pass | Pass | 0.1950847447 | 0.3943788279 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2232257454 | 0.3118132225 | Pass | Pass | 0.1968251638 | 0.3932592886 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2394743263 | 0.3782134535 | Pass | Pass | 0.2190495593 | 0.4235280947 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1968698187 | 0.2918002513 | Pass | Pass | 0.1952551853 | 0.3935195860 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3002.18 | -58.1 | 0.00 | -1155.1 | 3098.66 | 4887.65 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 65.00 | 29 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 38.00 | 14 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 391.00 | 83 | |||
Sep | 0.00 | 0 | |||
Oct | 225.00 | 40 | |||
Nov | 0.00 | 0 | |||
Dec | 5.00 | 10 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.140 | 1.375 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.304 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.892 | 1.029 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.320 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.880 | 1.013 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5037_SHGC_EAST_0.23 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5037_SHGC_WEST_0.23 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.864 | 0.231 | 0.231 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5037_SHGC_EAST_0.23 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5037_SHGC_WEST_0.23 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 2.864 | 0.231 | 0.231 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5037_SHGC_NORTH_0.23 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5037_SHGC_EAST_0.23 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5037_SHGC_SOUTH_0.23 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5037_SHGC_WEST_0.23 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 2.864 | 0.231 | 0.231 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 2.864 | 0.231 | 0.231 | |||||||||||||||||
North Total or Average | 177.99 | 2.864 | 0.231 | 0.231 | |||||||||||||||||
Non-North Total or Average | 415.31 | 2.864 | 0.231 | 0.231 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.79 | 0.0000 | Y | 5.95 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.59 | 0.0000 | Y | 3.74 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.29 | 0.0000 | Y | 5.84 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.60 | 0.0000 | Y | 3.74 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.68 | 0.0000 | Y | 5.93 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.53 | 0.0000 | Y | 3.73 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.24 | 0.0000 | Y | 5.83 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.53 | 0.0000 | Y | 3.73 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.79 | 0.0000 | Y | 5.95 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.59 | 0.0000 | Y | 3.74 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.29 | 0.0000 | Y | 5.84 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.60 | 0.0000 | Y | 3.74 |
Interior Lighting Total | 5.9322 | 4982.19 | 29555.08 | 202.77 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 41.82 | 41.82 | 3.34 | |
EXTERIOR_LIGHTS_B | 408.47 | AstronomicalClock | - | 83.82 | 62.82 | 4.82 | |
EXTERIOR_LIGHTS_C | 4724.13 | AstronomicalClock | - | 83.82 | 46.78 | 41.48 | |
Exterior Lighting Total | 5557.43 | 49.63 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 112257.05 | 78701.54 | 33555.52 | 0.70 | 3.40 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 93742.04 | 65720.97 | 28021.07 | 0.70 | 3.40 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 111670.81 | 78290.53 | 33380.28 | 0.70 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 112073.7 | 2.97 | 10.14 | N/A | N/A | 11.65 | |
PACU_VAV_MID COOLING COIL | 93588.9 | 2.97 | 10.14 | N/A | N/A | 11.65 | |
PACU_VAV_TOP COOLING COIL | 111488.4 | 2.97 | 10.14 | N/A | N/A | 11.65 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 25397.36 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 23998.97 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 25344.73 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9094.82 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5947.68 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9081.41 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5952.31 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5347.45 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3619.83 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5343.79 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3790.76 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6439.27 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4247.55 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6419.62 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4256.08 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 4352.77 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 5611.74 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 4396.85 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.52 | 9895.62 | 2189.01 | 1.00 | 1.14 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1314.72 | 3.77 | 8263.50 | 2189.01 | 1.00 | 1.15 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1314.72 | 4.50 | 9843.95 | 2189.01 | 1.00 | 1.14 | General | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 112073.71 | 2.97 | 10.14 | 11.65 | 5.2224 | 3.34 | 11.39 | 4.1340 | 3.52 | 12.03 | 2.7819 | 3.64 | 12.43 | 1.1996 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 93588.94 | 2.97 | 10.14 | 11.65 | 4.3610 | 3.34 | 11.39 | 3.4522 | 3.52 | 12.03 | 2.3231 | 3.64 | 12.43 | 1.0017 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 111488.42 | 2.97 | 10.14 | 11.65 | 5.1951 | 3.34 | 11.39 | 4.1124 | 3.52 | 12.03 | 2.7674 | 3.64 | 12.43 | 1.1933 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37430.29 | 37430.29 | 38.06 | 2.700 | 2.700 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 28.24 | 0.01716 | 0.425 | 0.00 |
CORE_MID | 26993.82 | 26993.82 | 27.45 | 1.944 | 1.944 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.24 | 0.01716 | 0.425 | 0.00 |
CORE_TOP | 29012.23 | 29012.23 | 29.50 | 2.110 | 2.110 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00891 | 33.13 | 0.01717 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8919.54 | 8919.54 | 43.02 | 0.649 | 0.649 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00889 | 32.26 | 0.01717 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 8424.80 | 8424.80 | 64.18 | 0.613 | 0.613 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00876 | 30.82 | 0.01716 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 9135.75 | 9135.75 | 44.06 | 0.665 | 0.665 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00888 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 9536.03 | 9536.03 | 72.65 | 0.694 | 0.694 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00873 | 32.26 | 0.01717 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 7469.94 | 7469.94 | 36.03 | 0.543 | 0.543 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00890 | 31.93 | 0.01716 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7458.52 | 7458.52 | 56.82 | 0.543 | 0.543 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 24.00 | 24.00 | 0.00876 | 30.82 | 0.01716 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 7593.52 | 7593.52 | 36.62 | 0.552 | 0.552 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00890 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7810.72 | 7810.72 | 59.51 | 0.568 | 0.568 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00875 | 32.04 | 0.01717 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7584.23 | 7584.23 | 36.58 | 0.552 | 0.552 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00893 | 31.82 | 0.01716 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7978.29 | 7978.29 | 60.78 | 0.580 | 0.580 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00877 | 30.46 | 0.01716 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 7723.48 | 7723.48 | 37.25 | 0.562 | 0.562 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00893 | 33.20 | 0.01717 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 8425.21 | 8425.21 | 64.19 | 0.613 | 0.613 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00875 | 32.26 | 0.01717 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 2148.79 | 2148.79 | 2.18 | 0.091 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
CORE_MID | 7776.27 | 7776.27 | 7.91 | 0.327 | 0.425 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
CORE_TOP | 15184.68 | 15184.68 | 15.44 | 0.643 | 0.643 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 8.70 | 0.00699 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 6401.03 | 6401.03 | 30.87 | 0.273 | 0.273 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 4185.50 | 4185.50 | 31.89 | 0.178 | 0.178 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 6391.64 | 6391.64 | 30.83 | 0.272 | 0.272 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 4188.73 | 4188.73 | 31.91 | 0.178 | 0.178 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 3616.91 | 3616.91 | 17.44 | 0.153 | 0.153 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 2402.05 | 2402.05 | 18.30 | 0.102 | 0.102 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 3605.01 | 3605.01 | 17.39 | 0.153 | 0.153 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 2409.82 | 2409.82 | 18.36 | 0.102 | 0.102 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 4541.24 | 4541.24 | 21.90 | 0.193 | 0.193 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 2994.60 | 2994.60 | 22.81 | 0.127 | 0.127 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 8.70 | 0.00699 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 4527.49 | 4527.49 | 21.84 | 0.192 | 0.192 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 8.70 | 0.00699 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 3000.56 | 3000.56 | 22.86 | 0.128 | 0.128 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 8.70 | 0.00699 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.52 | 4.52 | 0.94 | 0.94 | 4.5206 | 1.3040 | 4.5206 | 0.2884 | 0.3000 |
PACU_VAV_MID | 3.77 | 3.77 | 1.07 | 1.07 | 3.7750 | 1.2615 | 3.7750 | 0.3342 | 0.3000 |
PACU_VAV_TOP | 4.50 | 4.50 | 1.55 | 1.55 | 4.4970 | 1.5451 | 4.4970 | 0.3436 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25397.358 | 25397.358 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25397.36 | 14167.42 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00799672 | 51.6351 | 2148.79 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 23998.975 | 23998.975 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23998.97 | 14167.42 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 7776.27 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 25344.730 | 25344.730 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25344.73 | 21465.73 | 0.643470 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00800000 | 51.6560 | 15184.68 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 9094.822 | 9094.822 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9094.82 | 9094.82 | 0.272632 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00793846 | 51.2643 | 6401.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 5947.684 | 5947.684 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5947.68 | 5947.68 | 0.178291 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00793944 | 51.2705 | 4185.50 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 9081.413 | 9081.413 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9081.41 | 9081.41 | 0.272230 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00793834 | 51.2635 | 6391.64 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 5952.308 | 5952.308 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5952.31 | 5952.31 | 0.178430 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00793947 | 51.2707 | 4188.73 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5347.452 | 5347.452 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5347.45 | 5120.12 | 0.153484 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00790440 | 51.0470 | 3616.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 3619.828 | 3619.828 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3619.83 | 3401.49 | 0.101965 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00790443 | 51.0473 | 2402.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5343.788 | 5343.788 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5343.79 | 5103.14 | 0.152975 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00790408 | 51.0450 | 3605.01 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3790.758 | 3790.758 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3790.76 | 3412.57 | 0.102297 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00790476 | 51.0494 | 2409.82 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 6439.274 | 6439.274 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6439.27 | 6439.27 | 0.193028 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00789549 | 50.9905 | 4541.24 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 4247.549 | 4247.549 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4247.55 | 4247.55 | 0.127327 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00789728 | 51.0018 | 2994.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 6419.620 | 6419.620 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6419.62 | 6419.62 | 0.192438 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00789501 | 50.9873 | 4527.49 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 4256.079 | 4256.079 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4256.08 | 4256.08 | 0.127583 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 0.0000 | 21.00 | 0.00789757 | 51.0037 | 3000.56 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 112257.052 | 78701.536 | 4.520591 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 116726.73 | 81269.26 | 4.520591 | 26.48 | 19.32 | 0.01110220 | 11.03 | 11.03 | 0.00850000 | 33.20 | 0.01716721 | 25.32 | 26.4384 | 24.00 | 0.00885914 | 47.6096 | 60855.64 | 0.00 | 115752.09 | 80050.13 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 4352.774 | 4352.774 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4352.77 | 4352.77 | 1.356177 | 10.14 | 9.48 | 0.00710605 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 88.1278 | 21.00 | 0.00791840 | 51.1363 | 14182.58 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 93742.044 | 65720.974 | 3.774992 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 98916.95 | 65739.22 | 3.774992 | 26.90 | 19.82 | 0.01159273 | 11.03 | 11.03 | 0.00850000 | 33.00 | 0.01716683 | 25.27 | 31.6602 | 24.00 | 0.00894568 | 48.0683 | 51028.13 | 0.00 | 96660.63 | 66847.14 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 5611.739 | 5611.739 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5611.74 | 5611.74 | 1.132498 | 8.70 | 8.70 | 0.00699286 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 105.5340 | 21.00 | 0.00793120 | 51.2179 | 22840.15 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 111670.806 | 78290.528 | 4.496983 | -999.0 | -999.000 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 116177.40 | 80873.56 | 4.496983 | 26.38 | 19.28 | 0.01108553 | 11.03 | 11.03 | 0.00850000 | 32.93 | 0.01716670 | 25.26 | 26.5771 | 24.00 | 0.00887739 | 47.7065 | 61677.88 | 0.00 | 115147.59 | 79632.08 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 4396.846 | 4396.846 | -999.0 | -999.0 | -999.000 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4396.85 | 4396.85 | 1.349095 | 10.10 | 9.47 | 0.00710547 | 12.80 | 11.58 | 0.00800000 | 8.70 | 0.00699286 | 8.70 | 88.5905 | 21.00 | 0.00797983 | 51.5276 | 27775.95 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 25397.358 | 25397.358 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25397.36 | 14167.42 | 1.0000 | 0.51079251 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25397.36 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.87 | 0.00799672 | 21.00 | 0.00799672 | 51.6351 | 2148.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 23998.975 | 23998.975 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23998.97 | 14167.42 | 1.0000 | 0.51079251 | 0.424691 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23998.97 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.56 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 7776.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 25344.730 | 25344.730 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25344.73 | 21465.73 | 1.0000 | 0.77392584 | 0.643470 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25344.73 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6560 | 15184.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 9094.822 | 9094.822 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9094.82 | 9094.82 | 1.0000 | 0.32790492 | 0.272632 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9094.82 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00793846 | 21.00 | 0.00793846 | 51.2643 | 6401.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 5947.684 | 5947.684 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5947.68 | 5947.68 | 1.0000 | 0.21443795 | 0.178291 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5947.68 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00793944 | 21.00 | 0.00793944 | 51.2705 | 4185.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9081.413 | 9081.413 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9081.41 | 9081.41 | 1.0000 | 0.32742146 | 0.272230 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9081.41 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00793834 | 21.00 | 0.00793834 | 51.2635 | 6391.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 5952.308 | 5952.308 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5952.31 | 5952.31 | 1.0000 | 0.21460464 | 0.178430 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5952.31 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00793947 | 21.00 | 0.00793947 | 51.2707 | 4188.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 5347.452 | 5347.452 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5347.45 | 5120.12 | 1.0000 | 0.18460092 | 0.153484 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5347.45 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00790440 | 21.00 | 0.00790440 | 51.0470 | 3616.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 3619.828 | 3619.828 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3619.83 | 3401.49 | 1.0000 | 0.12263722 | 0.101965 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3619.83 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00790443 | 21.00 | 0.00790443 | 51.0473 | 2402.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 5343.788 | 5343.788 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5343.79 | 5103.14 | 1.0000 | 0.18398882 | 0.152975 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5343.79 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00790408 | 21.00 | 0.00790408 | 51.0450 | 3605.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 3790.758 | 3790.758 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3790.76 | 3412.57 | 1.0000 | 0.12303698 | 0.102297 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3790.76 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.86 | 0.00790476 | 21.00 | 0.00790476 | 51.0494 | 2409.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 6439.274 | 6439.274 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6439.27 | 6439.27 | 1.0000 | 0.23216173 | 0.193028 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6439.27 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00789549 | 21.00 | 0.00789549 | 50.9905 | 4541.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 4247.549 | 4247.549 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4247.55 | 4247.55 | 1.0000 | 0.15314125 | 0.127327 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4247.55 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00789728 | 21.00 | 0.00789728 | 51.0018 | 2994.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 6419.620 | 6419.620 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6419.62 | 6419.62 | 1.0000 | 0.23145313 | 0.192438 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6419.62 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.92 | 0.00789501 | 21.00 | 0.00789501 | 50.9873 | 4527.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 4256.079 | 4256.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4256.08 | 4256.08 | 1.0000 | 0.15344876 | 0.127583 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4256.08 | 8.70 | 0.00699286 | 8.70 | 0.00000000 | 0.0000 | 20.91 | 0.00789757 | 21.00 | 0.00789757 | 51.0037 | 3000.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 112257.052 | 78701.536 | 4.520591 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.99288 | 1025.4784 | 1004.8586 | 1.2027 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.520591 | 5.43709139 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | Sensible | 116726.73 | 81269.26 | 1.0398 | 5.43709139 | 4.520591 | 26.48 | 19.32 | 0.01110220 | 54923.6 | 11.03 | 11.03 | 0.00850000 | 32510.8 | -999.0 | -999.00 | -999.00 | -999.00 | 9895.624 | 106831.10 | 33.20 | 0.01716721 | 25.32 | 1.19517000 | 26.4384 | 24.00 | 0.00885914 | 24.00 | 0.00885914 | 47.6096 | 60855.64 | 0.00 | 115752.09 | 80050.13 | 5.22236738 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.62 | 0.00850428 | 33157.7 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4352.774 | 4352.774 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.520591 | 5.43709139 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4352.77 | 4352.77 | 1.0000 | 1.63112742 | 1.356177 | 10.14 | 9.48 | 0.00710605 | 28099.2 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4352.77 | 8.70 | 0.00699286 | 8.70 | 1.19517000 | 88.1278 | 20.87 | 0.00794630 | 21.00 | 0.00791840 | 51.1363 | 14182.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 93742.044 | 65720.974 | 3.774992 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.93959 | 1026.3903 | 1004.8586 | 1.2027 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.774992 | 4.54032997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 98916.95 | 65739.22 | 1.0552 | 4.54032997 | 3.774992 | 26.90 | 19.82 | 0.01159273 | 56599.1 | 11.03 | 11.03 | 0.00850000 | 32512.4 | -999.0 | -999.00 | -999.00 | -999.00 | 8263.499 | 90653.45 | 33.00 | 0.01716683 | 25.27 | 1.19517000 | 31.6602 | 24.00 | 0.00894568 | 24.00 | 0.00894568 | 48.0683 | 51028.13 | 0.00 | 96660.63 | 66847.14 | 4.36102126 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.62 | 0.00850428 | 33157.7 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5611.739 | 5611.739 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_MID FAN | Fan:VariableVolume | 3.774992 | 4.54032997 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5611.74 | 5611.74 | 1.0000 | 1.36209899 | 1.132498 | 8.70 | 8.70 | 0.00699286 | 26343.9 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5611.74 | 8.70 | 0.00699286 | 8.70 | 1.19517000 | 105.5340 | 20.77 | 0.00793754 | 21.00 | 0.00793120 | 51.2179 | 22840.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 111670.806 | 78290.528 | 4.496983 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.99971 | 1025.4474 | 1004.8586 | 1.2027 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.496983 | 5.40869698 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | Sensible | 116177.40 | 80873.56 | 1.0404 | 5.40869698 | 4.496983 | 26.38 | 19.28 | 0.01108553 | 54773.8 | 11.03 | 11.03 | 0.00850000 | 32510.7 | -999.0 | -999.00 | -999.00 | -999.00 | 9843.946 | 106333.45 | 32.93 | 0.01716670 | 25.26 | 1.19517000 | 26.5771 | 24.00 | 0.00887739 | 24.00 | 0.00887739 | 47.7065 | 61677.88 | 0.00 | 115147.59 | 79632.08 | 5.19509434 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.65 | 11.62 | 0.00850428 | 33157.7 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 4396.846 | 4396.846 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2027 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.496983 | 5.40869698 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | unknown | unknown | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4396.85 | 4396.85 | 1.0000 | 1.62260910 | 1.349095 | 10.10 | 9.47 | 0.00710547 | 28056.1 | 12.80 | 11.58 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 4396.85 | 8.70 | 0.00699286 | 8.70 | 1.19517000 | 88.5905 | 21.00 | 0.00797983 | 21.00 | 0.00797983 | 51.5276 | 27775.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 5039.50 | 92.17 | 0.00 |
CORE_MID | 3669.00 | 799.17 | 0.00 |
CORE_TOP | 3579.67 | 1292.83 | 0.00 |
PERIMETER_TOP_ZN_3 | 4061.67 | 1478.33 | 180.67 |
PERIMETER_TOP_ZN_2 | 4323.83 | 1365.17 | 327.00 |
PERIMETER_TOP_ZN_1 | 4569.00 | 1120.83 | 318.83 |
PERIMETER_TOP_ZN_4 | 4049.67 | 1564.50 | 273.33 |
PERIMETER_BOT_ZN_3 | 4318.50 | 992.00 | 30.67 |
PERIMETER_BOT_ZN_2 | 4796.50 | 668.83 | 148.67 |
PERIMETER_BOT_ZN_1 | 5089.83 | 1372.67 | 954.00 |
PERIMETER_BOT_ZN_4 | 4737.00 | 748.67 | 120.00 |
PERIMETER_MID_ZN_3 | 4284.17 | 1067.00 | 73.33 |
PERIMETER_MID_ZN_2 | 3676.33 | 954.33 | 207.83 |
PERIMETER_MID_ZN_1 | 4817.33 | 721.83 | 209.00 |
PERIMETER_MID_ZN_4 | 4376.50 | 1086.00 | 182.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5390.00 | 2802.17 | 1332.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 6.83 | 0.00 | 5.83 |
PERIMETER_TOP_ZN_2 | 0.00 | 40.67 | 0.00 | 40.50 |
PERIMETER_TOP_ZN_1 | 0.00 | 54.33 | 0.00 | 53.83 |
PERIMETER_TOP_ZN_4 | 0.00 | 33.83 | 0.00 | 25.33 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 19.67 | 0.00 | 19.67 |
PERIMETER_BOT_ZN_1 | 20.00 | 389.17 | 20.00 | 389.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 20.17 | 0.00 | 15.50 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 23.83 | 0.00 | 23.83 |
PERIMETER_MID_ZN_1 | 0.00 | 82.83 | 0.00 | 82.83 |
PERIMETER_MID_ZN_4 | 0.00 | 23.83 | 0.00 | 18.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 20.00 | 501.67 | 20.00 | 489.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 0.504 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.449 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.444 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 0.547 | 0.022 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.720 | 0.023 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 0.677 | 0.022 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.733 | 0.023 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 0.467 | 0.012 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.605 | 0.012 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 0.628 | 1.244 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.594 | 0.012 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 0.550 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.675 | 0.020 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 0.685 | 0.018 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.721 | 0.019 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.96 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.93 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.57 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.63 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.93 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.96 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.93 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.57 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.63 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.93 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 110.86 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 8242923.57 | 0.00 | 8242923.57 | 0.00 | 8242923.57 | 13393058.27 | 5692.16 | 1258.80 | 1809.04 | 212.47 |
CORE_MID | 7234451.96 | 0.00 | 7234451.96 | 0.00 | 7234451.96 | 13393058.27 | 7371.88 | 1285.63 | 102.49 | 120.93 |
CORE_TOP | 7179173.94 | 0.00 | 7179173.94 | 0.00 | 7179173.94 | 13393058.27 | 8127.23 | 606.63 | 26.14 | 129.56 |
PERIMETER_TOP_ZN_3 | 1850250.49 | 0.00 | 1850250.49 | 134708.35 | 1984958.84 | 2823374.22 | 5418.29 | 734.30 | 2607.42 | 129.56 |
PERIMETER_TOP_ZN_2 | 1540732.10 | 0.00 | 1540732.10 | 89805.02 | 1630537.12 | 1787429.43 | 3645.96 | 5.67 | 5108.37 | 129.56 |
PERIMETER_TOP_ZN_1 | 2279585.04 | 0.00 | 2279585.04 | 134708.35 | 2414293.38 | 2823374.22 | 4768.68 | 610.88 | 3380.44 | 129.56 |
PERIMETER_TOP_ZN_4 | 1574936.02 | 0.00 | 1574936.02 | 89805.02 | 1664741.04 | 1787312.18 | 3671.79 | 17.49 | 5070.73 | 129.56 |
PERIMETER_BOT_ZN_3 | 1611910.40 | 0.00 | 1611910.40 | 71624.30 | 1683534.70 | 2823374.22 | 6358.47 | 1315.07 | 1086.45 | 212.47 |
PERIMETER_BOT_ZN_2 | 1311864.47 | 0.00 | 1311864.47 | 47749.25 | 1359613.72 | 1787429.43 | 3974.69 | 136.37 | 4648.94 | 212.47 |
PERIMETER_BOT_ZN_1 | 2141353.75 | 0.00 | 2141353.75 | 4131458.82 | 6272812.57 | 2823374.22 | 4286.66 | 1144.35 | 3328.99 | 212.47 |
PERIMETER_BOT_ZN_4 | 1293251.80 | 0.00 | 1293251.80 | 47749.25 | 1341001.04 | 1787312.18 | 4500.57 | 177.64 | 4081.79 | 212.47 |
PERIMETER_MID_ZN_3 | 1857850.29 | 0.00 | 1857850.29 | 112134.81 | 1969985.11 | 2823374.22 | 4707.20 | 1353.07 | 2699.73 | 120.93 |
PERIMETER_MID_ZN_2 | 1530478.43 | 0.00 | 1530478.43 | 74756.09 | 1605234.52 | 1787429.43 | 3680.91 | 12.03 | 5067.06 | 1029.93 |
PERIMETER_MID_ZN_1 | 2304195.55 | 0.00 | 2304195.55 | 112134.81 | 2416330.37 | 2823374.22 | 3969.52 | 1230.04 | 3560.44 | 120.93 |
PERIMETER_MID_ZN_4 | 1543564.99 | 0.00 | 1543564.99 | 74756.09 | 1618321.08 | 1787312.18 | 3747.29 | 28.51 | 4984.19 | 120.93 |
Total Facility | 43496522.78 | 0.00 | 43496522.78 | 5121390.16 | 48617912.95 | 67843644.98 | 8483.40 | 2443.44 | 5361.77 | 1176.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.3695 | 0.0000 | 0.3695 | 0.0000 | 0.3695 | 0.4247 | 3079.58 | 1070.99 | 1792.43 |
CORE_MID | 0.3295 | 0.0000 | 0.3295 | 0.0000 | 0.3295 | 0.4247 | 4634.82 | 1208.86 | 99.32 |
CORE_TOP | 0.3265 | 0.0000 | 0.3265 | 0.0000 | 0.3265 | 0.4247 | 5313.85 | 604.05 | 25.10 |
PERIMETER_TOP_ZN_3 | 0.0845 | 0.0000 | 0.0845 | 0.0034 | 0.0879 | 0.0895 | 2609.24 | 730.37 | 2603.38 |
PERIMETER_TOP_ZN_2 | 0.0705 | 0.0000 | 0.0705 | 0.0022 | 0.0728 | 0.0567 | 958.02 | 5.46 | 4979.52 |
PERIMETER_TOP_ZN_1 | 0.1046 | 0.0000 | 0.1046 | 0.0034 | 0.1080 | 0.0895 | 1959.35 | 608.37 | 3375.28 |
PERIMETER_TOP_ZN_4 | 0.0718 | 0.0000 | 0.0718 | 0.0022 | 0.0741 | 0.0567 | 984.03 | 17.44 | 4941.53 |
PERIMETER_BOT_ZN_3 | 0.0722 | 0.0000 | 0.0722 | 0.0018 | 0.0740 | 0.0895 | 3728.81 | 1127.74 | 1086.45 |
PERIMETER_BOT_ZN_2 | 0.0592 | 0.0000 | 0.0592 | 0.0012 | 0.0604 | 0.0567 | 1356.43 | 134.01 | 4452.56 |
PERIMETER_BOT_ZN_1 | 0.0969 | 0.0000 | 0.0969 | 0.1915 | 0.2884 | 0.0895 | 1662.11 | 957.49 | 3323.40 |
PERIMETER_BOT_ZN_4 | 0.0581 | 0.0000 | 0.0581 | 0.0012 | 0.0593 | 0.0567 | 1887.99 | 176.31 | 3878.70 |
PERIMETER_MID_ZN_3 | 0.0850 | 0.0000 | 0.0850 | 0.0028 | 0.0878 | 0.0895 | 1972.59 | 1273.19 | 2697.22 |
PERIMETER_MID_ZN_2 | 0.0661 | 0.0000 | 0.0661 | 0.0020 | 0.0681 | 0.0567 | 966.92 | 5.94 | 4061.13 |
PERIMETER_MID_ZN_1 | 0.1059 | 0.0000 | 0.1059 | 0.0028 | 0.1087 | 0.0895 | 1235.57 | 1151.04 | 3556.38 |
PERIMETER_MID_ZN_4 | 0.0706 | 0.0000 | 0.0706 | 0.0019 | 0.0725 | 0.0567 | 1050.63 | 28.39 | 4863.98 |
Total Facility | 1.9711 | 0.0000 | 1.9711 | 0.2164 | 2.1875 | 2.1513 | 5667.16 | 2236.16 | 5094.19 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 21122019.37 | 0.00 | 21122019.37 | 22614548.33 | 3564.92 | 0.00 | 5195.08 | 212.47 |
PACU_VAV_MID | 20932829.29 | 0.00 | 20932829.29 | 22614548.33 | 3650.72 | 0.00 | 5109.28 | 120.93 |
PACU_VAV_TOP | 20866474.51 | 0.00 | 20866474.51 | 22614548.33 | 3636.43 | 0.00 | 5123.57 | 129.56 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 0.9489 | 0.0000 | 0.9489 | 0.7171 | 960.40 | 0.00 | 4982.60 |
PACU_VAV_MID | 0.9565 | 0.0000 | 0.9565 | 0.7171 | 954.65 | 0.00 | 4988.35 |
PACU_VAV_TOP | 0.9518 | 0.0000 | 0.9518 | 0.7171 | 948.99 | 0.00 | 4994.01 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5195.08 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5109.28 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5123.57 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1319 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1397 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.1327 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 827 |
Defaulted Fields | 545 |
Fields with Defaults | 2238 |
Autosized Fields | 150 |
Autosizable Fields | 203 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1691.82 | 12347.22 | 09-JUL-17:30 | 144721.22 | 28-JUL-15:30 |
Electricity:Building | 908.21 | 12175.61 | 09-JUL-17:10 | 67242.49 | 27-SEP-07:10 |
Electricity:Zone:CORE_BOTTOM | 284.50 | 4029.56 | 01-JAN-00:10 | 22405.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 908.21 | 12175.61 | 09-JUL-17:10 | 67242.49 | 27-SEP-07:10 |
InteriorLights:Electricity | 202.77 | 934.27 | 01-JAN-10:10 | 21377.78 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 202.77 | 934.27 | 01-JAN-10:10 | 21377.78 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity | 202.77 | 934.27 | 01-JAN-10:10 | 21377.78 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 202.77 | 934.27 | 01-JAN-10:10 | 21377.78 | 27-SEP-07:10 |
Electricity:Zone:CORE_MID | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.29 | 409.68 | 16-APR-17:10 | 2324.90 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.95 | 23.57 | 01-JAN-10:10 | 889.66 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 5.95 | 23.57 | 01-JAN-10:10 | 889.66 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.14 | 259.34 | 09-JUL-17:10 | 1471.80 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.74 | 14.92 | 01-JAN-07:50 | 563.23 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.74 | 14.92 | 01-JAN-07:50 | 563.23 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.17 | 409.67 | 23-APR-17:10 | 2324.89 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.84 | 23.57 | 01-JAN-07:40 | 889.66 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.84 | 23.57 | 01-JAN-07:40 | 889.66 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.15 | 259.34 | 12-MAR-17:10 | 1471.76 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.74 | 14.92 | 01-JAN-10:10 | 563.19 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.74 | 14.92 | 01-JAN-10:10 | 563.19 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.26 | 409.68 | 09-APR-17:10 | 2324.90 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.93 | 23.57 | 01-JAN-10:10 | 889.66 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 5.93 | 23.57 | 01-JAN-10:10 | 889.66 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.13 | 259.34 | 09-JUL-17:10 | 1471.80 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.73 | 14.92 | 01-JAN-07:40 | 563.23 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.73 | 14.92 | 01-JAN-07:40 | 563.23 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.16 | 409.67 | 19-MAR-17:10 | 2324.89 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.83 | 23.57 | 01-JAN-07:40 | 889.66 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.83 | 23.57 | 01-JAN-07:40 | 889.66 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.13 | 259.34 | 12-MAR-17:10 | 1471.76 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.73 | 14.92 | 01-JAN-10:10 | 563.19 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.73 | 14.92 | 01-JAN-10:10 | 563.19 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.29 | 409.68 | 16-APR-17:10 | 2324.90 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.95 | 23.57 | 01-JAN-10:10 | 889.66 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 5.95 | 23.57 | 01-JAN-10:10 | 889.66 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.14 | 259.34 | 09-JUL-17:10 | 1471.80 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.74 | 14.92 | 01-JAN-07:50 | 563.23 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.74 | 14.92 | 01-JAN-07:50 | 563.23 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.17 | 409.67 | 23-APR-17:10 | 2324.89 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.84 | 23.57 | 01-JAN-07:40 | 889.66 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.84 | 23.57 | 01-JAN-07:40 | 889.66 | 27-SEP-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.15 | 259.34 | 12-MAR-17:10 | 1471.76 | 27-SEP-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.74 | 14.92 | 01-JAN-10:10 | 563.19 | 27-SEP-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.74 | 14.92 | 01-JAN-10:10 | 563.19 | 27-SEP-07:10 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 733.97 | 168.34 | 01-JAN-00:10 | 85829.38 | 28-JUL-15:30 |
ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 835.33 | 27-SEP-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 835.33 | 27-SEP-07:20 |
ElectricityPurchased:Facility | 1691.82 | 12347.22 | 09-JUL-17:30 | 144721.22 | 28-JUL-15:30 |
ElectricityPurchased:Plant | 1691.82 | 12347.22 | 09-JUL-17:30 | 144721.22 | 28-JUL-15:30 |
Cogeneration:ElectricityPurchased | 1691.82 | 12347.22 | 09-JUL-17:30 | 144721.22 | 28-JUL-15:30 |
General:Cogeneration:ElectricityPurchased | 1691.82 | 12347.22 | 09-JUL-17:30 | 144721.22 | 28-JUL-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1691.82 | 12347.22 | 09-JUL-17:30 | 144721.22 | 28-JUL-15:30 |
ElectricityNet:Plant | 1691.82 | 12347.22 | 09-JUL-17:30 | 144721.22 | 28-JUL-15:30 |
Cogeneration:ElectricityNet | 1691.82 | 12347.22 | 09-JUL-17:30 | 144721.22 | 28-JUL-15:30 |
General:Cogeneration:ElectricityNet | 1691.82 | 12347.22 | 09-JUL-17:30 | 144721.22 | 28-JUL-15:30 |
Heating:Electricity | 1.34 | 0.00 | 01-JAN-00:10 | 27441.73 | 04-FEB-07:10 |
General:Heating:Electricity | 1.34 | 0.00 | 01-JAN-00:10 | 27441.73 | 04-FEB-07:10 |
Fans:Electricity | 88.64 | 0.00 | 01-JAN-00:10 | 13282.93 | 31-JUL-14:30 |
General:Fans:Electricity | 88.64 | 0.00 | 01-JAN-00:10 | 13282.93 | 31-JUL-14:30 |
ExteriorLights:Electricity | 49.63 | 0.00 | 01-JAN-07:20 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 49.63 | 0.00 | 01-JAN-07:20 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 615.63 | 0.00 | 01-JAN-00:10 | 71361.11 | 28-JUL-15:30 |
General:Cooling:Electricity | 615.63 | 0.00 | 01-JAN-00:10 | 71361.11 | 28-JUL-15:30 |
HeatRecovery:Electricity | 16.69 | 0.00 | 01-JAN-00:10 | 907.56 | 01-JAN-08:20 |
General:HeatRecovery:Electricity | 16.69 | 0.00 | 01-JAN-00:10 | 907.56 | 01-JAN-08:20 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 01-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 01-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 01-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 5.70 | 0.00 | 01-JAN-00:10 | 600.72 | 27-SEP-07:20 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 90.24 | 1156.00 | 16-MAR-07:10 | 10285.79 | 04-FEB-07:00 |
NaturalGas:HVAC | 0.01 | 0.00 | 01-JAN-00:10 | 2487.39 | 04-FEB-07:00 |
Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 2487.39 | 04-FEB-07:00 |
General:Heating:NaturalGas | 0.01 | 0.00 | 01-JAN-00:10 | 2487.39 | 04-FEB-07:00 |
NaturalGas:Plant | 90.22 | 1156.00 | 16-MAR-07:10 | 8808.78 | 24-JAN-12:10 |
WaterSystems:NaturalGas | 90.22 | 1156.00 | 16-MAR-07:10 | 8808.78 | 24-JAN-12:10 |
Water Heater:WaterSystems:NaturalGas | 90.22 | 1156.00 | 16-MAR-07:10 | 8808.78 | 24-JAN-12:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 24-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4236.19 | 0.00 | 01-JAN-00:10 | 424078.97 | 31-JUL-14:00 |
EnergyTransfer:Building | 1573.57 | 0.00 | 01-JAN-00:10 | 152220.13 | 31-JUL-14:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 300.16 | 0.00 | 01-JAN-00:10 | 26908.42 | 02-OCT-08:00 |
Heating:EnergyTransfer | 1.99 | 0.00 | 01-JAN-00:10 | 17010.73 | 04-FEB-07:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 1.99 | 0.00 | 01-JAN-00:10 | 17010.73 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 1571.58 | 0.00 | 01-JAN-00:10 | 152220.13 | 31-JUL-14:30 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 300.16 | 0.00 | 01-JAN-00:10 | 26908.42 | 02-OCT-08:00 |
General:Cooling:EnergyTransfer | 1571.58 | 0.00 | 01-JAN-00:10 | 152220.13 | 31-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 300.16 | 0.00 | 01-JAN-00:10 | 26908.42 | 02-OCT-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 62.61 | 0.00 | 01-JAN-00:10 | 10610.78 | 28-JUL-15:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.12 | 0.00 | 01-JAN-00:10 | 3987.73 | 04-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.12 | 0.00 | 01-JAN-00:10 | 3987.73 | 04-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 61.50 | 0.00 | 01-JAN-00:10 | 10610.78 | 28-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 61.50 | 0.00 | 01-JAN-00:10 | 10610.78 | 28-JUL-15:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 33.05 | 0.00 | 01-JAN-00:10 | 4240.02 | 31-JUL-14:30 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.15 | 0.00 | 01-JAN-00:10 | 1525.67 | 05-FEB-13:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 0.15 | 0.00 | 01-JAN-00:10 | 1525.67 | 05-FEB-13:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 32.90 | 0.00 | 01-JAN-00:10 | 4240.02 | 31-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 32.90 | 0.00 | 01-JAN-00:10 | 4240.02 | 31-JUL-14:30 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 39.49 | 0.00 | 01-JAN-00:10 | 4615.78 | 31-JUL-15:10 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.24 | 0.00 | 01-JAN-00:10 | 1312.20 | 05-FEB-15:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 0.24 | 0.00 | 01-JAN-00:10 | 1312.20 | 05-FEB-15:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 39.25 | 0.00 | 01-JAN-00:10 | 4615.78 | 31-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 39.25 | 0.00 | 01-JAN-00:10 | 4615.78 | 31-JUL-15:10 |
EnergyTransfer:Zone:CORE_MID | 213.32 | 0.00 | 01-JAN-00:10 | 18208.94 | 02-OCT-07:40 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 213.32 | 0.00 | 01-JAN-00:10 | 18208.94 | 02-OCT-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 213.32 | 0.00 | 01-JAN-00:10 | 18208.94 | 02-OCT-07:40 |
EnergyTransfer:Zone:CORE_TOP | 223.93 | 0.00 | 01-JAN-00:10 | 20173.83 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 1449.45 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 1449.45 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 223.93 | 0.00 | 01-JAN-00:10 | 20173.83 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 223.93 | 0.00 | 01-JAN-00:10 | 20173.83 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 60.66 | 0.00 | 01-JAN-00:10 | 7290.35 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2835.81 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.04 | 0.00 | 01-JAN-00:10 | 2835.81 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 60.61 | 0.00 | 01-JAN-00:10 | 7290.35 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 60.61 | 0.00 | 01-JAN-00:10 | 7290.35 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.90 | 0.00 | 01-JAN-00:10 | 7123.71 | 25-JUL-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1530.89 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1530.89 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.88 | 0.00 | 01-JAN-00:10 | 7123.71 | 25-JUL-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.88 | 0.00 | 01-JAN-00:10 | 7123.71 | 25-JUL-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 76.42 | 0.00 | 01-JAN-00:10 | 9868.98 | 02-JAN-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2516.66 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2516.66 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 76.40 | 0.00 | 01-JAN-00:10 | 9868.98 | 02-JAN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 76.40 | 0.00 | 01-JAN-00:10 | 9868.98 | 02-JAN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.80 | 0.00 | 01-JAN-00:10 | 7650.90 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 1761.53 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 1761.53 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.77 | 0.00 | 01-JAN-00:10 | 7650.90 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.77 | 0.00 | 01-JAN-00:10 | 7650.90 | 17-MAY-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 58.75 | 0.00 | 01-JAN-00:10 | 6455.40 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 58.75 | 0.00 | 01-JAN-00:10 | 6455.40 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 58.75 | 0.00 | 01-JAN-00:10 | 6455.40 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 49.31 | 0.00 | 01-JAN-00:10 | 6295.78 | 12-JUN-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 49.31 | 0.00 | 01-JAN-00:10 | 6295.78 | 12-JUN-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 49.31 | 0.00 | 01-JAN-00:10 | 6295.78 | 12-JUN-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 82.67 | 0.00 | 01-JAN-00:10 | 9739.00 | 27-JUL-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.35 | 0.00 | 01-JAN-00:10 | 3870.42 | 16-MAR-07:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.35 | 0.00 | 01-JAN-00:10 | 3870.42 | 16-MAR-07:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 82.32 | 0.00 | 01-JAN-00:10 | 9739.00 | 27-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 82.32 | 0.00 | 01-JAN-00:10 | 9739.00 | 27-JUL-16:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 47.73 | 0.00 | 01-JAN-00:10 | 6243.73 | 01-SEP-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 47.73 | 0.00 | 01-JAN-00:10 | 6243.73 | 01-SEP-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 47.73 | 0.00 | 01-JAN-00:10 | 6243.73 | 01-SEP-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 57.11 | 0.00 | 01-JAN-00:10 | 6436.49 | 31-JUL-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1030.10 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1030.10 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 57.11 | 0.00 | 01-JAN-00:10 | 6436.49 | 31-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 57.11 | 0.00 | 01-JAN-00:10 | 6436.49 | 31-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.39 | 0.00 | 01-JAN-00:10 | 6597.73 | 12-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 593.48 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 593.48 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.39 | 0.00 | 01-JAN-00:10 | 6597.73 | 12-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 47.39 | 0.00 | 01-JAN-00:10 | 6597.73 | 12-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 72.22 | 0.00 | 01-JAN-00:10 | 8626.51 | 02-JAN-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 895.54 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 895.54 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 72.22 | 0.00 | 01-JAN-00:10 | 8626.51 | 02-JAN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 72.22 | 0.00 | 01-JAN-00:10 | 8626.51 | 02-JAN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.04 | 0.00 | 01-JAN-00:10 | 6916.89 | 17-MAY-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 793.84 | 04-FEB-07:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 793.84 | 04-FEB-07:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.04 | 0.00 | 01-JAN-00:10 | 6916.89 | 17-MAY-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 47.04 | 0.00 | 01-JAN-00:10 | 6916.89 | 17-MAY-16:00 |
PlantLoopHeatingDemand:Facility | 35.28 | 0.00 | 01-JAN-00:10 | 4408.35 | 17-JAN-13:00 |
PlantLoopHeatingDemand:Plant | 35.28 | 0.00 | 01-JAN-00:10 | 4408.35 | 17-JAN-13:00 |
WaterSystems:PlantLoopHeatingDemand | 35.28 | 0.00 | 01-JAN-00:10 | 4408.35 | 17-JAN-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 35.28 | 0.00 | 01-JAN-00:10 | 4408.35 | 17-JAN-13:00 |
EnergyTransfer:HVAC | 2627.35 | 0.00 | 01-JAN-00:10 | 271319.95 | 21-AUG-12:10 |
HeatingCoils:EnergyTransfer | 1.35 | 0.00 | 01-JAN-00:10 | 28672.09 | 04-FEB-07:10 |
CoolingCoils:EnergyTransfer | 2483.03 | 0.00 | 01-JAN-00:10 | 252793.81 | 21-AUG-12:10 |
HeatRecoveryForHeating:EnergyTransfer | 0.24 | 0.00 | 01-JAN-00:10 | 6165.42 | 21-FEB-17:30 |
HeatRecoveryForCooling:EnergyTransfer | 142.73 | 0.00 | 01-JAN-00:10 | 23012.43 | 22-JUL-15:00 |
EnergyTransfer:Plant | 35.28 | 0.00 | 01-JAN-00:10 | 4408.35 | 17-JAN-13:00 |
WaterSystems:EnergyTransfer | 35.28 | 0.00 | 01-JAN-00:10 | 4408.35 | 17-JAN-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 35.28 | 0.00 | 01-JAN-00:10 | 4408.35 | 17-JAN-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -300.160 | 0.000 | 0.000 | 32.698 | 48.333 | 236.167 | 0.000 | 0.000 | 0.000 | 0.002 | 0.000 | 0.000 | 0.000 | 0.000 | -17.038 |
CORE_MID | 0.000 | 0.000 | 0.000 | -213.318 | 0.000 | 0.000 | 32.897 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 16.663 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_TOP | 0.000 | 0.000 | 0.001 | -223.929 | 0.000 | 0.000 | 33.164 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 27.006 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.044 | -60.613 | 0.000 | 0.000 | 7.016 | 5.954 | 24.333 | 23.258 | 0.000 | 0.195 | 8.230 | 0.000 | -8.125 | 0.000 | -0.291 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.021 | -50.875 | 0.000 | 0.000 | 4.404 | 3.741 | 15.404 | 30.789 | 0.000 | 0.124 | 1.800 | 0.000 | -5.204 | 0.000 | -0.204 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.020 | -76.401 | 0.000 | 0.000 | 6.938 | 5.840 | 24.332 | 47.865 | 0.000 | 0.182 | 0.001 | 0.000 | -8.259 | 0.000 | -0.331 | -0.187 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.031 | -50.769 | 0.000 | 0.000 | 4.461 | 3.742 | 15.403 | 29.915 | 0.000 | 0.126 | 2.929 | 0.000 | -5.632 | 0.000 | -0.207 | -0.000 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -58.749 | 0.000 | 0.000 | 6.955 | 5.930 | 24.333 | 23.406 | 0.000 | 0.109 | 7.076 | 0.000 | -8.889 | 0.000 | -0.172 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -49.311 | 0.000 | 0.000 | 4.373 | 3.731 | 15.404 | 30.895 | 0.000 | 0.067 | 0.878 | 0.000 | -5.911 | 0.000 | -0.125 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.354 | -82.313 | 0.000 | 0.000 | 6.873 | 5.828 | 24.332 | 48.035 | 0.000 | 11.246 | 0.042 | 0.000 | -9.292 | 0.000 | -5.106 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -47.729 | 0.000 | 0.000 | 4.389 | 3.731 | 15.403 | 29.941 | 0.000 | 0.066 | 0.724 | 0.000 | -6.398 | 0.000 | -0.128 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.001 | -57.105 | 0.000 | 0.000 | 6.962 | 5.954 | 24.333 | 23.358 | 0.000 | 0.166 | 5.360 | 0.000 | -8.761 | 0.000 | -0.268 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.001 | -47.392 | 0.000 | 0.000 | 3.240 | 3.741 | 15.404 | 30.894 | 0.000 | 0.106 | 0.001 | 0.000 | -5.559 | 0.000 | -0.186 | -0.248 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.001 | -72.220 | 0.000 | 0.000 | 6.900 | 5.840 | 24.332 | 48.026 | 0.000 | 0.155 | 0.000 | 0.000 | -8.801 | 0.000 | -0.299 | -3.933 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.001 | -47.038 | 0.000 | 0.000 | 4.415 | 3.742 | 15.403 | 29.963 | 0.000 | 0.104 | 0.000 | 0.000 | -6.062 | 0.000 | -0.190 | -0.339 |
TOPFLOOR_PLENUM | 1.118 | -61.496 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.208 | 60.602 | 0.000 | 0.000 | 0.000 | -0.432 | -0.000 |
MIDFLOOR_PLENUM | 0.154 | -32.895 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.242 | 32.962 | 0.000 | 0.000 | 0.000 | -0.463 | -0.000 |
FIRSTFLOOR_PLENUM | 0.239 | -39.254 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.183 | 39.218 | 0.000 | 0.000 | 0.000 | -0.387 | -0.000 |
Total Facility | 1.512 | -133.645 | 0.474 | -1437.921 | 0.000 | 0.000 | 165.684 | 202.773 | 705.434 | 396.346 | 0.000 | 13.279 | 203.495 | 0.000 | -86.893 | 0.000 | -8.789 | -21.747 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | -42485.59 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 37611.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | -30385.02 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 27474.05 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 05-SEP-04:02 | 0.00 | 0.00 | 0.00 | -32716.57 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 29805.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 30-JUL-14:23 | 0.00 | 0.00 | 0.00 | -10969.02 | 0.00 | 0.00 | 27.14 | 23.57 | 478.42 | 2932.75 | 0.00 | 51.70 | 7455.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24-SEP-09:43 | 0.00 | 0.00 | 0.00 | -10787.85 | 0.00 | 0.00 | 15.94 | 14.92 | 302.86 | 4698.60 | 0.00 | 10.41 | 5745.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 20-FEB-14:32 | 0.00 | 0.00 | 0.00 | -12579.81 | 0.00 | 0.00 | 23.83 | 23.57 | 478.41 | 8199.08 | 0.00 | 0.00 | 3881.87 | 0.00 | -0.00 | 0.00 | -26.96 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-MAY-16:42 | 0.00 | 0.00 | 0.00 | -11977.73 | 0.00 | 0.00 | 13.74 | 14.92 | 302.86 | 5624.88 | 0.00 | 64.83 | 5956.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 05-JUL-04:03 | 0.00 | 0.00 | 0.00 | -7519.59 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 7244.34 | 0.00 | -338.14 | 0.00 | -0.27 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-11:12 | 0.00 | 0.00 | 0.00 | -9687.14 | 0.00 | 0.00 | 16.34 | 14.92 | 302.86 | 3299.44 | 0.00 | 13.41 | 6040.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-DEC-13:23 | 0.00 | 0.00 | 0.00 | -10103.12 | 0.00 | 0.00 | 25.78 | 23.57 | 478.41 | 7902.68 | 0.00 | 7.83 | 1664.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 17-SEP-17:12 | 0.00 | 0.00 | 0.00 | -10113.61 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 3732.60 | 0.00 | 20.08 | 6101.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 05-JUN-04:03 | 0.00 | 0.00 | 0.00 | -7883.65 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 7664.78 | 0.00 | -394.28 | 0.00 | -0.50 | 0.00 |
PERIMETER_MID_ZN_2 | 23-JUL-08:32 | 0.00 | 0.00 | 0.00 | -10474.61 | 0.00 | 0.00 | 15.84 | 14.92 | 302.86 | 6406.88 | 0.00 | 9.66 | 3724.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 10-DEC-13:32 | 0.00 | 0.00 | 0.00 | -10332.08 | 0.00 | 0.00 | 25.44 | 23.57 | 478.41 | 7925.73 | 0.00 | 12.21 | 1866.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 17-SEP-17:12 | 0.00 | 0.00 | 0.00 | -10865.86 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 3706.31 | 0.00 | 30.91 | 6869.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 28-JUL-15:30 | 0.00 | -10610.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 10591.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 25-SEP-06:03 | 0.00 | -4670.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4673.70 | 0.00 | -0.00 | 0.00 | -3.67 | 0.00 |
FIRSTFLOOR_PLENUM | 31-JUL-12:10 | 0.00 | -4863.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 4846.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 25-SEP-04:02 | 0.00 | 8202.97 | 0.00 | -189672.47 | 0.00 | 0.00 | 0.00 | 2375.34 | 14333.92 | 0.00 | 0.00 | 0.00 | 168961.62 | 0.00 | -4047.58 | 0.00 | -153.79 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 04-FEB-07:03 | 0.00 | 0.00 | 5797.83 | 0.00 | 0.00 | 0.00 | 443.81 | 468.92 | 3025.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9736.48 |
PERIMETER_TOP_ZN_3 | 21-MAR-06:02 | 0.00 | 0.00 | 6219.99 | 0.00 | 0.00 | 0.00 | 190.75 | 296.56 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1697.88 | 0.00 | -17.93 | -5629.38 |
PERIMETER_TOP_ZN_2 | 16-MAR-06:03 | 0.00 | 0.00 | 4140.54 | 0.00 | 0.00 | 0.00 | 122.37 | 187.74 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1431.65 | 0.00 | -33.20 | -3389.62 |
PERIMETER_TOP_ZN_1 | 16-MAR-06:01 | 0.00 | 0.00 | 6032.19 | 0.00 | 0.00 | 0.00 | 193.30 | 296.56 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2162.54 | 0.00 | -47.91 | -4949.48 |
PERIMETER_TOP_ZN_4 | 03-FEB-07:02 | 0.00 | 0.00 | 4145.07 | 0.00 | 0.00 | 0.00 | 120.88 | 185.47 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1023.97 | 0.00 | -28.90 | -3802.35 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 16-MAR-07:00 | 0.00 | 0.00 | 3870.22 | 0.00 | 0.00 | 0.00 | 215.20 | 222.34 | 637.88 | 0.00 | 0.00 | 0.00 | 10639.42 | 0.00 | -1578.29 | 0.00 | -14006.77 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-FEB-07:03 | 0.00 | 0.00 | 3915.49 | 0.00 | 0.00 | 0.00 | 95.64 | 97.44 | 637.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2327.91 | 0.00 | -46.78 | -2371.76 |
PERIMETER_MID_ZN_2 | 04-FEB-07:03 | 0.00 | 0.00 | 2373.88 | 0.00 | 0.00 | 0.00 | 61.10 | 59.89 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -213.95 | 0.00 | -30.90 | -2653.84 |
PERIMETER_MID_ZN_1 | 04-FEB-07:03 | 0.00 | 0.00 | 3582.17 | 0.00 | 0.00 | 0.00 | 94.58 | 96.28 | 637.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1864.82 | 0.00 | -47.47 | -2498.62 |
PERIMETER_MID_ZN_4 | 04-FEB-07:03 | 0.00 | 0.00 | 2276.65 | 0.00 | 0.00 | 0.00 | 61.10 | 61.83 | 403.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1543.85 | 0.00 | -30.77 | -1228.76 |
TOPFLOOR_PLENUM | 16-OCT-05:03 | 4943.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -12.30 | -4931.00 |
MIDFLOOR_PLENUM | 05-FEB-13:03 | 2482.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -37.88 | -2444.92 |
FIRSTFLOOR_PLENUM | 15-DEC-06:02 | 4849.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -68.01 | -4781.56 |
Total Facility | 04-FEB-07:03 | -22641.47 | 23312.68 | 36977.77 | -23312.68 | 0.00 | 0.00 | 2159.26 | 2352.69 | 17966.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17739.46 | 0.00 | -672.84 | -18402.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 4.9062 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.5206 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 4.2511 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.7750 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 4.7304 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.4970 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.4531 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3040 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.1256 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.2615 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.3652 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3415 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6997 | 2.6997 | 0.7613 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9443 | 1.9443 | 0.7194 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1104 | 2.1104 | 0.7597 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6488 | 0.6488 | 0.1603 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6128 | 0.6128 | 0.1226 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6646 | 0.6646 | 0.1602 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6937 | 0.6937 | 0.1387 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5434 | 0.5434 | 0.1603 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5426 | 0.5426 | 0.1085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5524 | 0.5524 | 0.1602 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5682 | 0.5682 | 0.1136 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5517 | 0.5517 | 0.1517 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5804 | 0.5804 | 0.1161 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5618 | 0.5618 | 0.1517 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6129 | 0.6129 | 0.1226 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 4.9062 | 4.5206 | 4.9062 | 1.3040 | 0.0000 | 1.0000 |
PACU_VAV_MID | 4.2511 | 3.7750 | 4.2511 | 1.2615 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 4.7304 | 4.4970 | 4.7304 | 1.3415 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3499 | 1.3499 | 0.7613 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9722 | 0.9722 | 0.7194 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0552 | 1.0552 | 0.7597 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3244 | 0.3244 | 0.1603 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3064 | 0.3064 | 0.1226 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3323 | 0.3323 | 0.1602 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3468 | 0.3468 | 0.1387 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2717 | 0.2717 | 0.1603 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2713 | 0.2713 | 0.1085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2762 | 0.2762 | 0.1602 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2841 | 0.2841 | 0.1136 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2759 | 0.2759 | 0.1517 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2902 | 0.2902 | 0.1161 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2809 | 0.2809 | 0.1517 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3064 | 0.3064 | 0.1226 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.4531 | 1.3040 | 1.3040 | 1.3040 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.1256 | 1.2615 | 1.2615 | 1.2615 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.3652 | 1.3415 | 1.3415 | 1.3415 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Miami Intl Ap FL USA TMY3 WMO#=722020 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 20.00 |
Number of hours cooling loads not met | 489.17 |
Number of hours not met | 509.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 1.34 | 27441.73 | 0.01 | 2487.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 615.63 | 71361.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 202.77 | 21377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 49.63 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.66 | 835.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 88.64 | 13282.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 16.69 | 907.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 90.22 | 8808.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1691.82 |
Natural Gas | 0.00 | 90.24 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 1782.06 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 40.70 |
Space Heating | 0.27 |
Space Cooling | 123.57 |
Fans (All) | 17.79 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 339.57 |
Subtotal | 339.57 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 18.11 |
Miscellaneous (All) | 18.11 |
Subtotal | 18.11 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.38 |
Space Heating | 0.08 |
Space Cooling | 34.55 |
Fans (All) | 4.97 |
Service Water Heating | 5.06 |
Receptacle Equipment | 39.59 |
Miscellaneous | 4.38 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8600.00 | 160.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8729.17 | 30.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8587.17 | 172.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8449.33 | 310.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8410.00 | 350.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8363.00 | 397.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8734.00 | 26.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8456.50 | 303.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8446.67 | 313.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8361.33 | 398.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8639.67 | 120.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8481.83 | 278.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8481.50 | 278.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8388.83 | 371.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8271.83 | 488.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8271.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 488.17 | 0.00 | 0.00 | 0.00 |
Average | 8536.76 | 223.24 | 0.00 | 0.00 | 0.00 |
Sum | 153661.67 | 4018.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128259.67 | 44.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128303.67 | 0.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128301.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24860.67 | 48.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128303.67 | 48.33 | 0.00 | 0.00 | 0.00 |
Average | 34138.00 | 5.33 | 0.00 | 0.00 | 0.00 |
Sum | 614484.00 | 96.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 7876.33 | 883.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8707.50 | 52.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8648.33 | 111.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7007.83 | 1752.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6878.67 | 1881.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6813.83 | 1946.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6857.67 | 1902.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7487.00 | 1273.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7039.83 | 1720.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6069.00 | 2691.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6990.67 | 1769.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7264.50 | 1495.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7078.00 | 1682.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7042.00 | 1718.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7021.33 | 1738.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7283.67 | 1476.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8323.17 | 436.83 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8331.83 | 428.17 | 0.00 | 0.00 | 0.00 |
Min | 6069.00 | 52.50 | 0.00 | 0.00 | 0.00 |
Max | 8707.50 | 2691.00 | 0.00 | 0.00 | 0.00 |
Average | 7373.40 | 1386.60 | 0.00 | 0.00 | 0.00 |
Sum | 132721.17 | 24958.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128001.67 | 302.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128294.33 | 9.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128274.00 | 30.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24899.50 | 9.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24899.33 | 9.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 19635.83 | 5273.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24904.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24904.00 | 5.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128294.33 | 5273.17 | 0.00 | 0.00 | 0.00 |
Average | 33829.78 | 313.56 | 0.00 | 0.00 | 0.00 |
Sum | 608936.00 | 5644.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:20
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1A
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_MIAMI
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.420 |
February | 20.868 |
March | 21.567 |
April | 24.112 |
May | 26.413 |
June | 27.683 |
July | 28.127 |
August | 27.974 |
September | 27.493 |
October | 26.347 |
November | 23.587 |
December | 20.295 |
Annual Sum or Average | 24.507 |
Minimum of Months | 19.420 |
Maximum of Months | 28.127 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224753E+11 | 42484.11 | 02-JAN-05:02 | 18.48 | 18.43 | 0.198980E+10 | 2606.71 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.206022E+11 | 41386.84 | 13-FEB-05:03 | 20.10 | 19.25 | 0.180505E+10 | 2606.69 | 23-FEB-10:09 | 23.07 | 17.34 |
March | 0.245281E+11 | 41418.75 | 06-MAR-05:03 | 22.80 | 22.08 | 0.215700E+10 | 2606.65 | 01-MAR-10:09 | 22.80 | 22.08 |
April | 0.238574E+11 | 39717.80 | 29-APR-05:03 | 22.80 | 20.23 | 0.191560E+10 | 2606.65 | 20-APR-09:09 | 22.80 | 20.23 |
May | 0.267767E+11 | 41323.26 | 22-MAY-04:03 | 22.70 | 20.80 | 0.207591E+10 | 2606.54 | 30-MAY-13:20 | 26.33 | 24.24 |
June | 0.269789E+11 | 41051.39 | 19-JUN-04:02 | 24.40 | 22.82 | 0.206929E+10 | 2606.54 | 05-JUN-13:30 | 24.40 | 22.82 |
July | 0.267895E+11 | 41011.75 | 06-JUL-04:03 | 23.90 | 22.27 | 0.192228E+10 | 2606.54 | 14-JUL-13:30 | 28.90 | 25.45 |
August | 0.283591E+11 | 40741.51 | 29-AUG-04:03 | 23.80 | 23.12 | 0.215864E+10 | 2606.55 | 07-AUG-13:30 | 23.80 | 23.12 |
September | 0.264501E+11 | 41199.33 | 06-SEP-04:03 | 23.22 | 22.55 | 0.191633E+10 | 2606.54 | 11-SEP-13:30 | 29.20 | 24.70 |
October | 0.267794E+11 | 40679.06 | 16-OCT-04:03 | 21.78 | 20.54 | 0.199339E+10 | 2606.55 | 10-OCT-13:30 | 21.78 | 20.54 |
November | 0.243993E+11 | 41465.60 | 13-NOV-05:03 | 12.70 | 7.90 | 0.197390E+10 | 2606.69 | 27-NOV-10:00 | 22.20 | 16.63 |
December | 0.221634E+11 | 40394.08 | 26-DEC-05:03 | 22.43 | 21.04 | 0.191921E+10 | 2606.64 | 15-DEC-14:09 | 22.43 | 21.04 |
Annual Sum or Average | 0.300159E+12 | 0.238964E+11 | ||||||||
Minimum of Months | 0.206022E+11 | 39717.80 | 12.70 | 7.90 | 0.180505E+10 | 2606.54 | 21.70 | 15.05 | ||
Maximum of Months | 0.283591E+11 | 42484.11 | 24.40 | 23.12 | 0.215864E+10 | 2606.71 | 29.20 | 25.45 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245420E+10 | 7226.77 | 02-JAN-15:00 | 28.90 | 23.37 | 0.00 | 0.00 | 01-JAN-00:10 | 28.90 | 23.37 |
February | 0.305377E+10 | 7152.83 | 22-FEB-15:20 | 27.80 | 14.51 | 0.00 | 0.00 | 01-FEB-00:10 | 27.80 | 14.51 |
March | 0.410905E+10 | 8367.94 | 27-MAR-15:00 | 27.80 | 22.40 | 0.00 | 0.00 | 01-MAR-00:10 | 27.80 | 22.40 |
April | 0.526624E+10 | 9225.37 | 13-APR-14:00 | 28.90 | 24.03 | 0.00 | 0.00 | 01-APR-00:10 | 28.90 | 24.03 |
May | 0.665617E+10 | 10245.72 | 22-MAY-13:30 | 34.15 | 23.50 | 0.00 | 0.00 | 01-MAY-00:10 | 34.15 | 23.50 |
June | 0.692846E+10 | 9660.40 | 09-JUN-13:40 | 30.93 | 24.93 | 0.00 | 0.00 | 01-JUN-00:10 | 30.93 | 24.93 |
July | 0.764767E+10 | 10610.78 | 28-JUL-15:30 | 35.00 | 25.05 | 0.00 | 0.00 | 01-JUL-00:10 | 35.00 | 25.05 |
August | 0.694644E+10 | 10170.49 | 23-AUG-14:00 | 32.20 | 25.37 | 0.00 | 0.00 | 01-AUG-00:10 | 32.20 | 25.37 |
September | 0.642846E+10 | 9885.44 | 18-SEP-14:00 | 31.10 | 24.95 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 24.95 |
October | 0.544771E+10 | 9525.06 | 06-OCT-13:10 | 29.82 | 23.71 | 0.00 | 0.00 | 01-OCT-00:10 | 29.82 | 23.71 |
November | 0.390222E+10 | 7676.62 | 10-NOV-14:10 | 28.90 | 24.10 | 0.00 | 0.00 | 01-NOV-00:10 | 28.90 | 24.10 |
December | 0.265612E+10 | 6623.88 | 08-DEC-14:40 | 27.40 | 22.79 | 0.00 | 0.00 | 01-DEC-00:10 | 27.40 | 22.79 |
Annual Sum or Average | 0.614965E+11 | 0.00 | ||||||||
Minimum of Months | 0.245420E+10 | 6623.88 | 27.40 | 14.51 | 0.00 | 0.00 | 27.40 | 14.51 | ||
Maximum of Months | 0.764767E+10 | 10610.78 | 35.00 | 25.37 | 0.00 | 0.00 | 35.00 | 25.37 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139920E+10 | 3260.68 | 02-JAN-16:20 | 25.40 | 20.54 | 0.00 | 0.00 | 01-JAN-00:10 | 25.40 | 20.54 |
February | 0.156879E+10 | 2800.03 | 21-FEB-17:00 | 25.60 | 14.07 | 0.00 | 0.00 | 01-FEB-00:10 | 25.60 | 14.07 |
March | 0.213426E+10 | 3225.75 | 27-MAR-16:00 | 27.20 | 22.19 | 0.00 | 0.00 | 01-MAR-00:10 | 27.20 | 22.19 |
April | 0.259756E+10 | 3409.07 | 17-APR-15:50 | 31.78 | 20.21 | 0.00 | 0.00 | 01-APR-00:10 | 31.78 | 20.21 |
May | 0.338226E+10 | 4404.80 | 30-MAY-06:03 | 23.40 | 22.58 | 0.00 | 0.00 | 01-MAY-00:10 | 23.40 | 22.58 |
June | 0.364210E+10 | 4202.84 | 19-JUN-06:03 | 24.50 | 22.74 | 0.00 | 0.00 | 01-JUN-00:10 | 24.50 | 22.74 |
July | 0.380379E+10 | 4445.67 | 31-JUL-06:03 | 26.20 | 24.14 | 0.00 | 0.00 | 01-JUL-00:10 | 26.20 | 24.14 |
August | 0.374736E+10 | 4359.82 | 21-AUG-06:03 | 27.38 | 24.48 | 0.00 | 0.00 | 01-AUG-00:10 | 27.38 | 24.48 |
September | 0.348964E+10 | 4670.13 | 25-SEP-06:03 | 24.40 | 23.65 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 23.65 |
October | 0.324856E+10 | 4404.61 | 02-OCT-06:03 | 26.70 | 24.92 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 24.92 |
November | 0.232911E+10 | 3487.51 | 06-NOV-16:30 | 27.80 | 20.19 | 0.00 | 0.00 | 01-NOV-00:10 | 27.80 | 20.19 |
December | 0.155281E+10 | 2902.37 | 11-DEC-15:50 | 24.08 | 17.65 | 0.00 | 0.00 | 01-DEC-00:10 | 24.08 | 17.65 |
Annual Sum or Average | 0.328954E+11 | 0.00 | ||||||||
Minimum of Months | 0.139920E+10 | 2800.03 | 23.40 | 14.07 | 0.00 | 0.00 | 23.40 | 14.07 | ||
Maximum of Months | 0.380379E+10 | 4670.13 | 31.78 | 24.92 | 0.00 | 0.00 | 31.78 | 24.92 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207850E+10 | 4059.11 | 02-JAN-16:10 | 25.50 | 20.58 | 0.00 | 0.00 | 01-JAN-00:10 | 25.50 | 20.58 |
February | 0.211057E+10 | 3437.61 | 21-FEB-17:00 | 25.60 | 14.07 | 0.00 | 0.00 | 01-FEB-00:10 | 25.60 | 14.07 |
March | 0.267620E+10 | 3627.43 | 27-MAR-16:00 | 27.20 | 22.19 | 0.00 | 0.00 | 01-MAR-00:10 | 27.20 | 22.19 |
April | 0.297152E+10 | 3759.56 | 17-APR-16:00 | 31.70 | 20.29 | 0.00 | 0.00 | 01-APR-00:10 | 31.70 | 20.29 |
May | 0.379753E+10 | 4538.21 | 22-MAY-12:10 | 33.48 | 23.09 | 0.00 | 0.00 | 01-MAY-00:10 | 33.48 | 23.09 |
June | 0.404459E+10 | 4425.38 | 05-JUN-06:03 | 25.28 | 24.00 | 0.00 | 0.00 | 01-JUN-00:10 | 25.28 | 24.00 |
July | 0.420075E+10 | 4863.45 | 31-JUL-12:10 | 32.93 | 25.13 | 0.00 | 0.00 | 01-JUL-00:10 | 32.93 | 25.13 |
August | 0.429927E+10 | 4581.54 | 28-AUG-06:03 | 25.68 | 24.72 | 0.00 | 0.00 | 01-AUG-00:10 | 25.68 | 24.72 |
September | 0.401071E+10 | 4708.92 | 05-SEP-06:03 | 22.38 | 21.49 | 0.00 | 0.00 | 01-SEP-00:10 | 22.38 | 21.49 |
October | 0.387766E+10 | 4742.50 | 02-OCT-06:03 | 26.70 | 24.92 | 0.00 | 0.00 | 01-OCT-00:10 | 26.70 | 24.92 |
November | 0.303903E+10 | 3986.56 | 06-NOV-16:10 | 27.80 | 20.07 | 0.00 | 0.00 | 01-NOV-00:10 | 27.80 | 20.07 |
December | 0.214785E+10 | 3484.56 | 11-DEC-16:10 | 23.72 | 17.48 | 0.00 | 0.00 | 01-DEC-00:10 | 23.72 | 17.48 |
Annual Sum or Average | 0.392542E+11 | 0.00 | ||||||||
Minimum of Months | 0.207850E+10 | 3437.61 | 22.38 | 14.07 | 0.00 | 0.00 | 22.38 | 14.07 | ||
Maximum of Months | 0.429927E+10 | 4863.45 | 33.48 | 25.13 | 0.00 | 0.00 | 33.48 | 25.13 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149082E+11 | 30384.96 | 02-JAN-05:02 | 18.48 | 18.43 | 0.194866E+10 | 2606.59 | 05-JAN-10:09 | 19.60 | 17.07 |
February | 0.140581E+11 | 29179.71 | 13-FEB-06:03 | 20.60 | 19.45 | 0.177758E+10 | 2606.67 | 23-FEB-10:09 | 23.07 | 17.34 |
March | 0.169935E+11 | 28820.12 | 28-MAR-05:03 | 21.60 | 19.81 | 0.213229E+10 | 2606.64 | 01-MAR-10:09 | 21.60 | 19.81 |
April | 0.172788E+11 | 29089.15 | 18-APR-05:03 | 18.30 | 14.73 | 0.190336E+10 | 2606.65 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.194756E+11 | 29589.29 | 22-MAY-04:03 | 22.70 | 20.80 | 0.206802E+10 | 2606.54 | 09-MAY-09:09 | 22.70 | 20.80 |
June | 0.198476E+11 | 28343.09 | 05-JUN-04:03 | 25.60 | 23.64 | 0.206368E+10 | 2606.54 | 05-JUN-13:50 | 24.13 | 21.79 |
July | 0.200240E+11 | 28894.97 | 24-JUL-04:03 | 24.32 | 23.63 | 0.191689E+10 | 2606.54 | 10-JUL-09:09 | 24.32 | 23.63 |
August | 0.206041E+11 | 28996.60 | 14-AUG-04:03 | 22.88 | 22.36 | 0.215235E+10 | 2606.54 | 07-AUG-13:30 | 22.88 | 22.36 |
September | 0.193060E+11 | 29308.79 | 05-SEP-04:02 | 23.30 | 21.69 | 0.191025E+10 | 2606.54 | 05-SEP-13:09 | 25.73 | 23.35 |
October | 0.191401E+11 | 29927.52 | 16-OCT-04:03 | 21.78 | 20.54 | 0.198571E+10 | 2606.59 | 18-OCT-09:09 | 26.70 | 18.84 |
November | 0.166767E+11 | 30047.26 | 06-NOV-05:03 | 21.10 | 19.63 | 0.196117E+10 | 2606.65 | 13-NOV-10:09 | 19.68 | 13.91 |
December | 0.150049E+11 | 28369.71 | 04-DEC-06:03 | 17.20 | 15.50 | 0.187742E+10 | 2606.61 | 04-DEC-10:09 | 21.88 | 17.23 |
Annual Sum or Average | 0.213318E+12 | 0.236974E+11 | ||||||||
Minimum of Months | 0.140581E+11 | 28343.09 | 17.20 | 14.73 | 0.177758E+10 | 2606.54 | 19.60 | 13.91 | ||
Maximum of Months | 0.206041E+11 | 30384.96 | 25.60 | 23.64 | 0.215235E+10 | 2606.67 | 26.70 | 23.63 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145598E+11 | 25234.47 | 02-JAN-06:03 | 19.32 | 19.04 | 0.187177E+10 | 2606.59 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.140822E+11 | 20525.89 | 13-FEB-06:03 | 20.60 | 19.45 | 0.173673E+10 | 2606.60 | 16-FEB-10:00 | 25.60 | 20.01 |
March | 0.174203E+11 | 31225.53 | 06-MAR-06:03 | 22.80 | 22.00 | 0.209328E+10 | 2606.63 | 02-MAR-14:09 | 22.80 | 22.00 |
April | 0.183076E+11 | 31532.58 | 17-APR-05:03 | 18.90 | 16.76 | 0.189433E+10 | 2606.65 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.211550E+11 | 32459.99 | 22-MAY-04:03 | 22.70 | 20.80 | 0.206570E+10 | 2606.55 | 08-MAY-09:09 | 22.70 | 20.80 |
June | 0.217659E+11 | 32355.68 | 19-JUN-04:02 | 24.40 | 22.82 | 0.206350E+10 | 2606.54 | 05-JUN-13:09 | 24.40 | 22.82 |
July | 0.221478E+11 | 32121.01 | 24-JUL-04:03 | 24.32 | 23.63 | 0.191721E+10 | 2606.53 | 25-JUL-13:09 | 32.30 | 25.97 |
August | 0.222618E+11 | 31674.30 | 07-AUG-04:03 | 25.68 | 24.34 | 0.215066E+10 | 2606.54 | 07-AUG-13:00 | 27.20 | 24.31 |
September | 0.207416E+11 | 32716.49 | 05-SEP-04:02 | 23.30 | 21.69 | 0.190836E+10 | 2606.54 | 11-SEP-13:00 | 27.80 | 24.12 |
October | 0.198260E+11 | 32110.38 | 10-OCT-04:02 | 24.32 | 22.47 | 0.198010E+10 | 2606.64 | 18-OCT-09:39 | 26.70 | 19.01 |
November | 0.168198E+11 | 31638.54 | 06-NOV-06:03 | 21.02 | 19.85 | 0.193928E+10 | 2606.58 | 14-NOV-14:20 | 23.90 | 15.88 |
December | 0.148414E+11 | 31007.00 | 26-DEC-06:03 | 20.32 | 18.04 | 0.180959E+10 | 2606.61 | 04-DEC-10:00 | 20.32 | 18.04 |
Annual Sum or Average | 0.223929E+12 | 0.234305E+11 | ||||||||
Minimum of Months | 0.140822E+11 | 20525.89 | 18.90 | 16.76 | 0.173673E+10 | 2606.53 | 20.32 | 15.88 | ||
Maximum of Months | 0.222618E+11 | 32716.49 | 25.68 | 24.34 | 0.215066E+10 | 2606.65 | 32.30 | 25.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304816E+10 | 4747.40 | 02-JAN-15:00 | 28.90 | 23.37 | 0.383461E+09 | 549.48 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.320522E+10 | 4752.88 | 17-FEB-14:10 | 26.70 | 21.67 | 0.361668E+09 | 549.48 | 27-FEB-14:00 | 26.10 | 16.72 |
March | 0.412441E+10 | 5305.44 | 27-MAR-15:00 | 27.80 | 22.40 | 0.433951E+09 | 549.49 | 02-MAR-14:09 | 27.80 | 22.40 |
April | 0.478347E+10 | 6337.61 | 17-APR-15:20 | 32.03 | 19.94 | 0.399346E+09 | 549.49 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.626208E+10 | 9459.20 | 30-MAY-04:02 | 25.40 | 24.11 | 0.437200E+09 | 549.47 | 22-MAY-13:00 | 25.40 | 24.11 |
June | 0.685859E+10 | 10310.05 | 25-JUN-15:13 | 29.63 | 24.46 | 0.436565E+09 | 549.48 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.704358E+10 | 10969.60 | 30-JUL-14:23 | 33.60 | 24.88 | 0.405974E+09 | 549.47 | 14-JUL-13:00 | 33.60 | 24.88 |
August | 0.670671E+10 | 10734.41 | 06-AUG-14:13 | 32.03 | 25.28 | 0.454942E+09 | 549.48 | 07-AUG-13:00 | 27.20 | 24.31 |
September | 0.603439E+10 | 9660.06 | 24-SEP-15:43 | 30.60 | 24.69 | 0.403697E+09 | 549.48 | 11-SEP-13:00 | 30.60 | 24.69 |
October | 0.524430E+10 | 9352.82 | 02-OCT-04:02 | 26.70 | 25.03 | 0.418404E+09 | 549.49 | 18-OCT-09:39 | 26.70 | 19.01 |
November | 0.410564E+10 | 5405.86 | 03-NOV-14:00 | 29.40 | 24.47 | 0.407071E+09 | 549.48 | 14-NOV-14:20 | 23.90 | 15.88 |
December | 0.319781E+10 | 4579.08 | 08-DEC-14:10 | 27.70 | 22.74 | 0.372673E+09 | 549.48 | 01-DEC-10:09 | 27.70 | 22.74 |
Annual Sum or Average | 0.606144E+11 | 0.491495E+10 | ||||||||
Minimum of Months | 0.304816E+10 | 4579.08 | 25.40 | 19.94 | 0.361668E+09 | 549.47 | 23.90 | 15.88 | ||
Maximum of Months | 0.704358E+10 | 10969.60 | 33.60 | 25.28 | 0.454942E+09 | 549.49 | 33.60 | 24.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257859E+10 | 8085.55 | 01-JAN-10:02 | 25.28 | 21.21 | 0.254738E+09 | 347.88 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.282370E+10 | 4358.08 | 28-FEB-10:20 | 24.40 | 16.22 | 0.234669E+09 | 347.88 | 23-FEB-10:39 | 24.40 | 16.22 |
March | 0.375011E+10 | 5952.85 | 27-MAR-10:30 | 25.85 | 21.67 | 0.283468E+09 | 347.87 | 29-MAR-09:09 | 24.60 | 20.06 |
April | 0.440608E+10 | 10695.86 | 16-APR-08:53 | 25.00 | 21.54 | 0.254138E+09 | 347.88 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.521720E+10 | 7188.05 | 30-MAY-04:02 | 25.40 | 24.11 | 0.276825E+09 | 347.86 | 31-MAY-09:39 | 30.53 | 23.99 |
June | 0.546153E+10 | 10747.37 | 04-JUN-08:23 | 28.90 | 25.06 | 0.276435E+09 | 347.86 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.566811E+10 | 10771.03 | 16-JUL-08:53 | 29.40 | 23.81 | 0.257213E+09 | 347.86 | 14-JUL-13:00 | 29.40 | 23.81 |
August | 0.543528E+10 | 10726.54 | 20-AUG-09:43 | 29.90 | 25.36 | 0.288035E+09 | 347.86 | 07-AUG-13:00 | 29.90 | 25.36 |
September | 0.501738E+10 | 10788.28 | 24-SEP-09:43 | 29.40 | 24.69 | 0.255786E+09 | 347.86 | 14-SEP-09:39 | 29.40 | 24.69 |
October | 0.451894E+10 | 10631.35 | 09-OCT-09:02 | 28.48 | 24.21 | 0.265309E+09 | 347.87 | 18-OCT-09:39 | 26.70 | 19.01 |
November | 0.342091E+10 | 5153.44 | 07-NOV-09:50 | 25.32 | 21.18 | 0.260463E+09 | 347.87 | 13-NOV-10:00 | 21.10 | 14.86 |
December | 0.257764E+10 | 4329.84 | 08-DEC-10:30 | 26.65 | 22.70 | 0.241914E+09 | 347.87 | 04-DEC-10:00 | 26.65 | 22.70 |
Annual Sum or Average | 0.508755E+11 | 0.314899E+10 | ||||||||
Minimum of Months | 0.257764E+10 | 4329.84 | 24.40 | 16.22 | 0.234669E+09 | 347.86 | 21.10 | 14.86 | ||
Maximum of Months | 0.566811E+10 | 10788.28 | 29.90 | 25.36 | 0.288035E+09 | 347.88 | 30.53 | 25.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.551823E+10 | 12362.75 | 01-JAN-13:22 | 26.65 | 21.70 | 0.407742E+09 | 596.30 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.532934E+10 | 12579.55 | 20-FEB-14:32 | 26.50 | 17.84 | 0.373295E+09 | 579.04 | 21-FEB-14:39 | 25.93 | 14.05 |
March | 0.589789E+10 | 11752.44 | 26-MAR-14:02 | 27.80 | 22.29 | 0.443426E+09 | 551.63 | 01-MAR-14:30 | 27.80 | 22.29 |
April | 0.558862E+10 | 8921.76 | 16-APR-15:32 | 30.97 | 21.01 | 0.400068E+09 | 549.49 | 21-APR-09:09 | 25.50 | 18.66 |
May | 0.624935E+10 | 9653.54 | 30-MAY-04:02 | 25.40 | 24.11 | 0.436911E+09 | 549.47 | 22-MAY-13:00 | 25.40 | 24.11 |
June | 0.655218E+10 | 9491.18 | 12-JUN-04:02 | 25.60 | 24.44 | 0.436317E+09 | 549.48 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.688196E+10 | 11403.28 | 30-JUL-13:02 | 32.88 | 25.38 | 0.405787E+09 | 549.47 | 14-JUL-13:00 | 32.88 | 25.38 |
August | 0.718298E+10 | 11337.83 | 20-AUG-11:43 | 32.12 | 26.12 | 0.455015E+09 | 549.48 | 07-AUG-13:00 | 32.12 | 26.12 |
September | 0.733156E+10 | 11816.60 | 24-SEP-11:43 | 31.10 | 25.02 | 0.404218E+09 | 557.69 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.763128E+10 | 12103.52 | 15-OCT-12:02 | 27.98 | 21.58 | 0.421067E+09 | 572.79 | 25-OCT-13:30 | 30.30 | 22.44 |
November | 0.659031E+10 | 12142.89 | 19-NOV-12:13 | 26.70 | 21.28 | 0.415222E+09 | 594.32 | 07-NOV-14:09 | 26.70 | 21.28 |
December | 0.564859E+10 | 12085.57 | 25-DEC-14:23 | 26.40 | 23.55 | 0.393036E+09 | 595.13 | 04-DEC-14:39 | 26.40 | 23.55 |
Annual Sum or Average | 0.764023E+11 | 0.499210E+10 | ||||||||
Minimum of Months | 0.532934E+10 | 8921.76 | 25.40 | 17.84 | 0.373295E+09 | 549.47 | 25.40 | 14.05 | ||
Maximum of Months | 0.763128E+10 | 12579.55 | 32.88 | 26.12 | 0.455015E+09 | 596.30 | 32.88 | 26.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.274498E+10 | 5031.12 | 03-JAN-15:40 | 26.70 | 20.74 | 0.240110E+09 | 347.84 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.295015E+10 | 11443.30 | 19-FEB-15:43 | 27.20 | 21.86 | 0.225945E+09 | 347.84 | 27-FEB-14:00 | 26.10 | 16.72 |
March | 0.391851E+10 | 11825.93 | 12-MAR-15:53 | 24.40 | 18.35 | 0.272071E+09 | 347.84 | 02-MAR-14:09 | 24.40 | 18.35 |
April | 0.441448E+10 | 11975.77 | 09-APR-16:32 | 26.87 | 18.50 | 0.250948E+09 | 347.85 | 17-APR-09:09 | 22.15 | 19.68 |
May | 0.515958E+10 | 11978.75 | 29-MAY-16:42 | 31.97 | 24.40 | 0.275687E+09 | 347.84 | 22-MAY-13:00 | 31.97 | 24.40 |
June | 0.511130E+10 | 11718.13 | 25-JUN-16:33 | 29.23 | 24.32 | 0.275659E+09 | 347.84 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.546750E+10 | 11929.49 | 09-JUL-16:52 | 30.00 | 25.18 | 0.256430E+09 | 347.84 | 14-JUL-13:00 | 28.90 | 26.06 |
August | 0.541403E+10 | 11856.11 | 20-AUG-16:22 | 30.60 | 24.86 | 0.287400E+09 | 347.84 | 07-AUG-13:00 | 30.60 | 24.86 |
September | 0.476934E+10 | 11934.79 | 10-SEP-15:52 | 31.10 | 24.95 | 0.254667E+09 | 347.84 | 11-SEP-13:00 | 27.80 | 24.12 |
October | 0.442541E+10 | 11831.68 | 09-OCT-15:02 | 30.40 | 24.10 | 0.263634E+09 | 347.85 | 18-OCT-09:39 | 26.70 | 19.01 |
November | 0.350045E+10 | 9234.57 | 05-NOV-15:32 | 27.80 | 24.02 | 0.255201E+09 | 347.84 | 14-NOV-14:00 | 23.90 | 15.88 |
December | 0.289472E+10 | 8039.99 | 03-DEC-16:12 | 24.23 | 17.00 | 0.233910E+09 | 347.84 | 01-DEC-10:20 | 24.23 | 17.00 |
Annual Sum or Average | 0.507704E+11 | 0.309166E+10 | ||||||||
Minimum of Months | 0.274498E+10 | 5031.12 | 24.23 | 17.00 | 0.225945E+09 | 347.84 | 22.15 | 15.88 | ||
Maximum of Months | 0.546750E+10 | 11978.75 | 31.97 | 25.18 | 0.287400E+09 | 347.85 | 31.97 | 26.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.333682E+10 | 4391.70 | 02-JAN-15:00 | 28.90 | 23.37 | 0.401513E+09 | 549.48 | 20-JAN-14:09 | 18.98 | 12.27 |
February | 0.322066E+10 | 4068.08 | 17-FEB-14:10 | 26.70 | 21.67 | 0.370282E+09 | 549.48 | 21-FEB-10:50 | 21.32 | 15.77 |
March | 0.385762E+10 | 4320.54 | 06-MAR-14:10 | 24.90 | 22.15 | 0.439939E+09 | 549.48 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.421095E+10 | 5066.45 | 17-APR-15:20 | 32.03 | 19.94 | 0.400643E+09 | 549.50 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.558336E+10 | 7389.93 | 30-MAY-04:02 | 25.40 | 24.11 | 0.437175E+09 | 549.47 | 22-MAY-13:00 | 25.40 | 24.11 |
June | 0.615244E+10 | 7260.14 | 12-JUN-04:02 | 25.60 | 24.44 | 0.436302E+09 | 549.48 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.649680E+10 | 7520.37 | 05-JUL-04:03 | 25.60 | 23.23 | 0.405720E+09 | 549.47 | 19-JUL-13:00 | 27.80 | 25.31 |
August | 0.653725E+10 | 7448.34 | 01-AUG-04:03 | 28.30 | 24.97 | 0.455246E+09 | 549.48 | 07-AUG-13:39 | 28.13 | 24.58 |
September | 0.601462E+10 | 7399.46 | 11-SEP-04:02 | 27.20 | 24.31 | 0.404210E+09 | 549.48 | 11-SEP-13:00 | 27.80 | 24.12 |
October | 0.546593E+10 | 7339.53 | 30-OCT-04:02 | 26.28 | 24.93 | 0.419905E+09 | 549.48 | 10-OCT-13:09 | 26.28 | 24.93 |
November | 0.436997E+10 | 4864.38 | 03-NOV-13:50 | 29.40 | 24.41 | 0.413433E+09 | 549.49 | 14-NOV-10:09 | 22.30 | 16.07 |
December | 0.350308E+10 | 4325.78 | 01-DEC-14:10 | 26.10 | 19.79 | 0.390743E+09 | 549.48 | 04-DEC-10:09 | 21.88 | 17.23 |
Annual Sum or Average | 0.587495E+11 | 0.497511E+10 | ||||||||
Minimum of Months | 0.322066E+10 | 4068.08 | 24.90 | 19.79 | 0.370282E+09 | 549.47 | 18.98 | 12.27 | ||
Maximum of Months | 0.653725E+10 | 7520.37 | 32.03 | 24.97 | 0.455246E+09 | 549.50 | 28.13 | 25.31 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280102E+10 | 8535.93 | 01-JAN-10:32 | 26.13 | 21.45 | 0.262801E+09 | 347.88 | 27-JAN-10:00 | 21.70 | 15.05 |
February | 0.280428E+10 | 4219.11 | 28-FEB-10:10 | 24.40 | 16.25 | 0.238916E+09 | 347.88 | 23-FEB-10:09 | 24.40 | 16.25 |
March | 0.352000E+10 | 5154.87 | 27-MAR-10:30 | 25.85 | 21.67 | 0.286063E+09 | 347.88 | 01-MAR-10:09 | 25.85 | 21.67 |
April | 0.395748E+10 | 8223.34 | 16-APR-08:43 | 24.82 | 21.56 | 0.255216E+09 | 347.88 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.472115E+10 | 7998.43 | 07-MAY-09:23 | 27.50 | 21.81 | 0.277129E+09 | 347.86 | 31-MAY-09:30 | 30.25 | 24.04 |
June | 0.495806E+10 | 9334.26 | 04-JUN-08:23 | 28.90 | 25.06 | 0.276520E+09 | 347.86 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.525457E+10 | 9687.88 | 23-JUL-11:12 | 33.13 | 24.74 | 0.257357E+09 | 347.86 | 17-JUL-09:30 | 33.13 | 24.74 |
August | 0.530099E+10 | 9333.85 | 20-AUG-10:23 | 30.85 | 25.86 | 0.288507E+09 | 347.86 | 07-AUG-13:00 | 30.85 | 25.86 |
September | 0.499811E+10 | 9408.22 | 24-SEP-09:43 | 29.40 | 24.69 | 0.256328E+09 | 347.86 | 14-SEP-09:39 | 29.40 | 24.69 |
October | 0.465584E+10 | 9361.08 | 09-OCT-08:53 | 28.30 | 24.27 | 0.266343E+09 | 347.86 | 26-OCT-13:00 | 21.70 | 20.88 |
November | 0.360942E+10 | 4920.74 | 07-NOV-09:30 | 24.75 | 21.38 | 0.262902E+09 | 347.88 | 13-NOV-10:09 | 19.68 | 13.91 |
December | 0.273031E+10 | 4121.70 | 08-DEC-10:30 | 26.65 | 22.70 | 0.252326E+09 | 347.87 | 15-DEC-10:39 | 13.53 | 9.85 |
Annual Sum or Average | 0.493112E+11 | 0.318041E+10 | ||||||||
Minimum of Months | 0.273031E+10 | 4121.70 | 24.40 | 16.25 | 0.238916E+09 | 347.86 | 13.53 | 9.85 | ||
Maximum of Months | 0.530099E+10 | 9687.88 | 33.13 | 25.86 | 0.288507E+09 | 347.88 | 33.13 | 25.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.538748E+10 | 10036.21 | 01-JAN-12:32 | 26.83 | 21.44 | 0.412464E+09 | 631.06 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.533220E+10 | 9909.11 | 20-FEB-12:43 | 24.32 | 17.38 | 0.377012E+09 | 596.95 | 22-FEB-13:09 | 27.20 | 14.13 |
March | 0.545454E+10 | 8353.29 | 13-MAR-16:10 | 29.32 | 22.34 | 0.441736E+09 | 565.53 | 13-MAR-12:09 | 29.32 | 22.34 |
April | 0.550586E+10 | 8777.13 | 17-APR-16:10 | 31.60 | 20.14 | 0.401269E+09 | 610.74 | 13-APR-12:09 | 31.60 | 20.14 |
May | 0.682335E+10 | 9527.95 | 22-MAY-12:00 | 33.30 | 23.06 | 0.440028E+09 | 681.47 | 22-MAY-12:09 | 33.48 | 23.09 |
June | 0.728338E+10 | 8792.08 | 09-JUN-12:00 | 31.10 | 24.24 | 0.439434E+09 | 619.93 | 09-JUN-12:09 | 31.02 | 24.35 |
July | 0.786713E+10 | 9739.00 | 27-JUL-16:50 | 34.50 | 24.87 | 0.411481E+09 | 690.36 | 31-JUL-12:09 | 32.93 | 25.13 |
August | 0.863595E+10 | 9616.35 | 23-AUG-12:00 | 33.30 | 23.92 | 0.462787E+09 | 686.88 | 23-AUG-12:09 | 33.40 | 24.17 |
September | 0.839338E+10 | 9685.08 | 24-SEP-11:43 | 31.10 | 25.02 | 0.414939E+09 | 668.64 | 11-SEP-12:09 | 31.10 | 25.02 |
October | 0.870045E+10 | 9930.13 | 29-OCT-11:32 | 30.60 | 24.98 | 0.434675E+09 | 676.96 | 03-OCT-12:09 | 30.60 | 24.98 |
November | 0.733927E+10 | 9941.51 | 19-NOV-12:02 | 26.70 | 21.28 | 0.423961E+09 | 637.41 | 08-NOV-13:09 | 26.70 | 21.28 |
December | 0.559210E+10 | 10103.40 | 10-DEC-13:23 | 28.60 | 23.26 | 0.397697E+09 | 616.07 | 04-DEC-14:39 | 28.60 | 23.26 |
Annual Sum or Average | 0.823151E+11 | 0.505748E+10 | ||||||||
Minimum of Months | 0.533220E+10 | 8353.29 | 24.32 | 17.38 | 0.377012E+09 | 565.53 | 26.70 | 14.13 | ||
Maximum of Months | 0.870045E+10 | 10103.40 | 34.50 | 25.02 | 0.462787E+09 | 690.36 | 33.48 | 25.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.270796E+10 | 4611.74 | 02-JAN-16:30 | 25.30 | 20.50 | 0.257284E+09 | 347.84 | 20-JAN-14:00 | 19.40 | 12.60 |
February | 0.275410E+10 | 9915.51 | 20-FEB-17:23 | 25.85 | 17.65 | 0.236349E+09 | 347.85 | 23-FEB-10:39 | 23.87 | 17.94 |
March | 0.349869E+10 | 5698.41 | 27-MAR-16:00 | 27.20 | 22.19 | 0.281716E+09 | 347.84 | 23-MAR-09:00 | 27.20 | 22.19 |
April | 0.386249E+10 | 8955.17 | 01-APR-17:42 | 27.30 | 23.73 | 0.254838E+09 | 347.85 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.458436E+10 | 9968.57 | 29-MAY-16:31 | 32.23 | 24.43 | 0.277026E+09 | 347.84 | 22-MAY-13:00 | 32.23 | 24.43 |
June | 0.452960E+10 | 7878.84 | 10-JUN-17:06 | 30.60 | 24.10 | 0.276316E+09 | 347.84 | 26-JUN-13:00 | 26.70 | 23.11 |
July | 0.497899E+10 | 9523.94 | 09-JUL-16:52 | 30.00 | 25.18 | 0.257112E+09 | 347.84 | 10-JUL-09:09 | 25.37 | 23.57 |
August | 0.521893E+10 | 9906.24 | 13-AUG-16:12 | 30.40 | 25.65 | 0.288478E+09 | 347.84 | 07-AUG-13:00 | 30.40 | 25.65 |
September | 0.466227E+10 | 10114.15 | 17-SEP-17:12 | 30.73 | 24.63 | 0.256207E+09 | 347.84 | 11-SEP-13:00 | 30.73 | 24.63 |
October | 0.448440E+10 | 9831.56 | 09-OCT-16:53 | 28.90 | 23.69 | 0.266267E+09 | 347.84 | 26-OCT-13:00 | 21.70 | 20.88 |
November | 0.353975E+10 | 5711.57 | 07-NOV-16:30 | 28.05 | 22.28 | 0.262245E+09 | 347.85 | 14-NOV-10:09 | 22.30 | 16.07 |
December | 0.290824E+10 | 7029.10 | 10-DEC-15:23 | 28.60 | 22.59 | 0.249528E+09 | 347.84 | 04-DEC-10:09 | 28.60 | 22.59 |
Annual Sum or Average | 0.477298E+11 | 0.316337E+10 | ||||||||
Minimum of Months | 0.270796E+10 | 4611.74 | 25.30 | 17.65 | 0.236349E+09 | 347.84 | 19.40 | 12.60 | ||
Maximum of Months | 0.521893E+10 | 10114.15 | 32.23 | 25.65 | 0.288478E+09 | 347.85 | 32.23 | 25.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312325E+10 | 4446.52 | 02-JAN-15:00 | 28.90 | 23.37 | 0.398040E+09 | 549.48 | 19-JAN-14:00 | 25.00 | 18.53 |
February | 0.317684E+10 | 4310.05 | 17-FEB-14:10 | 26.70 | 21.67 | 0.369969E+09 | 549.49 | 23-FEB-10:50 | 24.13 | 18.14 |
March | 0.398325E+10 | 4648.46 | 28-MAR-13:30 | 27.20 | 20.57 | 0.442131E+09 | 549.48 | 22-MAR-13:00 | 27.20 | 20.57 |
April | 0.445725E+10 | 6622.58 | 13-APR-05:03 | 24.40 | 22.09 | 0.401753E+09 | 549.50 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.574049E+10 | 7456.09 | 30-MAY-05:03 | 24.22 | 22.51 | 0.437542E+09 | 549.47 | 22-MAY-13:00 | 24.22 | 22.51 |
June | 0.624081E+10 | 7885.66 | 05-JUN-04:03 | 25.60 | 23.64 | 0.436535E+09 | 549.48 | 05-JUN-13:50 | 24.13 | 21.79 |
July | 0.635258E+10 | 7763.15 | 17-JUL-04:03 | 26.02 | 23.69 | 0.405880E+09 | 549.47 | 10-JUL-09:09 | 26.02 | 23.69 |
August | 0.618380E+10 | 7800.08 | 01-AUG-04:03 | 28.30 | 24.97 | 0.455161E+09 | 549.48 | 07-AUG-13:30 | 28.60 | 24.70 |
September | 0.558281E+10 | 7880.72 | 05-SEP-04:02 | 23.30 | 21.69 | 0.404050E+09 | 549.48 | 11-SEP-13:00 | 27.80 | 24.12 |
October | 0.501707E+10 | 7611.65 | 10-OCT-04:02 | 24.32 | 22.47 | 0.419537E+09 | 549.48 | 18-OCT-09:09 | 26.70 | 18.84 |
November | 0.402042E+10 | 6824.20 | 21-NOV-06:03 | 25.50 | 21.33 | 0.411934E+09 | 549.48 | 15-NOV-10:20 | 25.50 | 21.33 |
December | 0.322798E+10 | 4200.32 | 01-DEC-14:10 | 26.10 | 19.79 | 0.385744E+09 | 549.49 | 04-DEC-10:09 | 21.88 | 17.23 |
Annual Sum or Average | 0.571066E+11 | 0.496828E+10 | ||||||||
Minimum of Months | 0.312325E+10 | 4200.32 | 23.30 | 19.79 | 0.369969E+09 | 549.47 | 21.88 | 17.23 | ||
Maximum of Months | 0.635258E+10 | 7885.66 | 28.90 | 24.97 | 0.455161E+09 | 549.50 | 28.60 | 24.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262131E+10 | 4770.26 | 02-JAN-10:00 | 24.40 | 20.57 | 0.190749E+09 | 338.73 | 27-JAN-11:20 | 22.07 | 15.40 |
February | 0.275939E+10 | 4689.92 | 28-FEB-09:50 | 24.22 | 16.33 | 0.174737E+09 | 338.72 | 28-FEB-11:20 | 24.80 | 16.42 |
March | 0.360229E+10 | 5619.44 | 27-MAR-10:20 | 25.57 | 21.63 | 0.209823E+09 | 338.73 | 17-MAR-10:30 | 25.57 | 21.63 |
April | 0.407284E+10 | 10110.74 | 16-APR-08:43 | 24.82 | 21.56 | 0.188289E+09 | 338.72 | 18-APR-10:20 | 20.97 | 14.26 |
May | 0.474314E+10 | 9876.96 | 07-MAY-09:23 | 27.50 | 21.81 | 0.204758E+09 | 338.72 | 18-MAY-07:19 | 27.07 | 21.97 |
June | 0.491574E+10 | 10131.44 | 04-JUN-08:23 | 28.90 | 25.06 | 0.204206E+09 | 338.72 | 09-JUN-12:20 | 30.93 | 24.45 |
July | 0.506551E+10 | 10474.75 | 23-JUL-08:32 | 30.20 | 24.97 | 0.190635E+09 | 338.72 | 17-JUL-07:10 | 30.20 | 24.97 |
August | 0.494368E+10 | 10050.69 | 20-AUG-09:02 | 29.50 | 24.78 | 0.212793E+09 | 338.72 | 31-AUG-07:19 | 27.60 | 23.99 |
September | 0.458049E+10 | 10124.73 | 24-SEP-09:43 | 29.40 | 24.69 | 0.189398E+09 | 338.72 | 11-SEP-07:10 | 29.40 | 24.69 |
October | 0.423578E+10 | 10052.16 | 09-OCT-09:02 | 28.48 | 24.21 | 0.196680E+09 | 338.73 | 17-OCT-07:30 | 24.45 | 18.70 |
November | 0.328712E+10 | 5294.94 | 07-NOV-09:30 | 24.75 | 21.38 | 0.193437E+09 | 338.73 | 13-NOV-11:20 | 21.83 | 15.41 |
December | 0.256553E+10 | 4234.05 | 08-DEC-10:00 | 26.10 | 22.56 | 0.182008E+09 | 338.72 | 06-DEC-08:09 | 26.10 | 22.56 |
Annual Sum or Average | 0.473928E+11 | 0.233751E+10 | ||||||||
Minimum of Months | 0.256553E+10 | 4234.05 | 24.22 | 16.33 | 0.174737E+09 | 338.72 | 20.97 | 14.26 | ||
Maximum of Months | 0.506551E+10 | 10474.75 | 30.20 | 25.06 | 0.212793E+09 | 338.73 | 30.93 | 24.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.560959E+10 | 10228.09 | 01-JAN-12:53 | 27.20 | 21.55 | 0.416315E+09 | 618.35 | 02-JAN-14:39 | 28.90 | 23.86 |
February | 0.522089E+10 | 10281.02 | 20-FEB-12:43 | 24.32 | 17.38 | 0.379006E+09 | 599.11 | 21-FEB-14:30 | 25.85 | 14.25 |
March | 0.569277E+10 | 9849.62 | 26-MAR-14:02 | 27.80 | 22.29 | 0.449138E+09 | 570.27 | 01-MAR-14:30 | 27.80 | 22.29 |
April | 0.519892E+10 | 7100.34 | 13-APR-05:03 | 24.40 | 22.09 | 0.402341E+09 | 549.50 | 20-APR-09:09 | 24.40 | 17.53 |
May | 0.572516E+10 | 7570.24 | 30-MAY-05:03 | 24.22 | 22.51 | 0.437427E+09 | 549.47 | 22-MAY-13:00 | 24.22 | 22.51 |
June | 0.595961E+10 | 7890.34 | 26-JUN-04:03 | 25.60 | 24.44 | 0.436364E+09 | 549.48 | 05-JUN-13:50 | 25.60 | 24.44 |
July | 0.620306E+10 | 9420.01 | 30-JUL-13:02 | 32.88 | 25.38 | 0.405752E+09 | 549.47 | 10-JUL-09:09 | 32.88 | 25.38 |
August | 0.661705E+10 | 9107.94 | 06-AUG-14:13 | 32.03 | 25.28 | 0.455274E+09 | 550.99 | 31-AUG-13:09 | 31.70 | 24.44 |
September | 0.676872E+10 | 9890.78 | 24-SEP-11:43 | 31.10 | 25.02 | 0.404781E+09 | 567.64 | 29-SEP-13:09 | 31.10 | 24.17 |
October | 0.719191E+10 | 10185.93 | 15-OCT-12:02 | 27.98 | 21.58 | 0.423798E+09 | 585.96 | 25-OCT-13:20 | 30.20 | 22.36 |
November | 0.636931E+10 | 10222.28 | 19-NOV-12:02 | 26.70 | 21.28 | 0.419907E+09 | 613.12 | 07-NOV-14:09 | 26.70 | 21.28 |
December | 0.566402E+10 | 10331.79 | 10-DEC-13:32 | 28.70 | 23.18 | 0.400907E+09 | 616.36 | 04-DEC-14:39 | 28.70 | 23.18 |
Annual Sum or Average | 0.722210E+11 | 0.503101E+10 | ||||||||
Minimum of Months | 0.519892E+10 | 7100.34 | 24.22 | 17.38 | 0.379006E+09 | 549.47 | 24.22 | 14.25 | ||
Maximum of Months | 0.719191E+10 | 10331.79 | 32.88 | 25.38 | 0.455274E+09 | 618.35 | 32.88 | 25.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269906E+10 | 4801.30 | 03-JAN-15:30 | 26.70 | 20.80 | 0.250423E+09 | 347.84 | 10-JAN-14:00 | 22.20 | 16.63 |
February | 0.281510E+10 | 10658.87 | 20-FEB-16:42 | 26.70 | 17.88 | 0.232767E+09 | 347.84 | 01-FEB-14:39 | 26.70 | 17.88 |
March | 0.369267E+10 | 10193.23 | 12-MAR-15:53 | 24.40 | 18.35 | 0.278674E+09 | 347.84 | 22-MAR-13:00 | 23.30 | 17.73 |
April | 0.403976E+10 | 10724.84 | 02-APR-17:03 | 25.32 | 18.00 | 0.253920E+09 | 347.85 | 20-APR-09:20 | 24.40 | 17.64 |
May | 0.469074E+10 | 10644.90 | 29-MAY-16:42 | 31.97 | 24.40 | 0.276686E+09 | 347.84 | 23-MAY-13:00 | 31.97 | 24.40 |
June | 0.461245E+10 | 9997.13 | 10-JUN-17:06 | 30.60 | 24.10 | 0.276135E+09 | 347.84 | 05-JUN-13:50 | 30.60 | 24.10 |
July | 0.488948E+10 | 10579.85 | 09-JUL-16:52 | 30.00 | 25.18 | 0.256831E+09 | 347.84 | 10-JUL-09:09 | 25.37 | 23.57 |
August | 0.495379E+10 | 10765.20 | 13-AUG-16:12 | 30.40 | 25.65 | 0.288020E+09 | 347.84 | 28-AUG-09:09 | 22.80 | 22.12 |
September | 0.435318E+10 | 10866.27 | 17-SEP-17:12 | 30.73 | 24.63 | 0.255618E+09 | 347.84 | 11-SEP-13:00 | 30.73 | 24.63 |
October | 0.414470E+10 | 10461.56 | 09-OCT-15:02 | 30.40 | 24.10 | 0.265343E+09 | 347.84 | 18-OCT-09:09 | 26.70 | 18.84 |
November | 0.332806E+10 | 7586.71 | 05-NOV-15:32 | 27.80 | 24.02 | 0.259734E+09 | 347.84 | 29-NOV-10:09 | 26.10 | 24.59 |
December | 0.282038E+10 | 9106.46 | 10-DEC-15:32 | 28.50 | 22.56 | 0.242896E+09 | 347.84 | 13-DEC-14:00 | 21.70 | 13.99 |
Annual Sum or Average | 0.470394E+11 | 0.313705E+10 | ||||||||
Minimum of Months | 0.269906E+10 | 4801.30 | 24.40 | 17.88 | 0.232767E+09 | 347.84 | 21.70 | 13.99 | ||
Maximum of Months | 0.495379E+10 | 10866.27 | 31.97 | 25.65 | 0.288020E+09 | 347.85 | 31.97 | 24.63 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294655E+09 | 4941.82 | 02-JAN-06:03 | 19.32 |
February | 0.184717E+09 | 4279.08 | 04-FEB-06:03 | 5.50 |
March | 0.194815E+09 | 4347.08 | 16-MAR-05:02 | 6.70 |
April | 38820638.04 | 4923.84 | 17-APR-05:03 | 18.90 |
May | 17454404.32 | 4348.79 | 30-MAY-04:02 | 25.40 |
June | 14381871.58 | 4075.11 | 19-JUN-04:02 | 24.40 |
July | 18320329.72 | 4868.70 | 31-JUL-04:02 | 26.10 |
August | 14302578.26 | 4111.27 | 31-AUG-05:03 | 25.60 |
September | 16322204.35 | 4923.23 | 05-SEP-04:02 | 23.30 |
October | 20937373.19 | 4943.92 | 16-OCT-05:03 | 22.20 |
November | 69937648.03 | 4590.26 | 06-NOV-06:03 | 21.02 |
December | 0.233705E+09 | 4175.85 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 0.111837E+10 | |||
Minimum of Months | 14302578.26 | 4075.11 | 5.50 | |
Maximum of Months | 0.294655E+09 | 4943.92 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27322909.84 | 2055.30 | 22-JAN-16:33 | 20.40 |
February | 15301100.46 | 2482.63 | 05-FEB-13:03 | 21.20 |
March | 8779403.83 | 1933.04 | 05-MAR-11:13 | 27.23 |
April | 10251775.48 | 1746.94 | 12-APR-05:03 | 24.50 |
May | 9405428.13 | 1803.99 | 10-MAY-05:03 | 25.00 |
June | 7664711.45 | 1864.71 | 22-JUN-05:03 | 24.90 |
July | 8639731.44 | 1621.55 | 03-JUL-04:02 | 25.00 |
August | 9316492.72 | 2084.90 | 28-AUG-04:02 | 26.10 |
September | 9668793.85 | 2158.75 | 18-SEP-04:02 | 27.80 |
October | 10929940.72 | 2055.97 | 30-OCT-04:02 | 26.28 |
November | 11682688.59 | 2277.71 | 13-NOV-06:03 | 12.20 |
December | 25399044.73 | 2132.59 | 24-DEC-11:23 | 26.95 |
Annual Sum or Average | 0.154362E+09 | |||
Minimum of Months | 7664711.45 | 1621.55 | 12.20 | |
Maximum of Months | 27322909.84 | 2482.63 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22149384.90 | 4490.19 | 25-JAN-06:02 | 9.40 |
February | 19517297.14 | 4141.07 | 03-FEB-06:03 | 11.02 |
March | 18856166.32 | 4425.36 | 16-MAR-05:02 | 6.70 |
April | 16515345.67 | 2861.52 | 29-APR-05:03 | 22.80 |
May | 19002722.06 | 3167.61 | 01-MAY-04:03 | 21.02 |
June | 15578325.58 | 2939.41 | 28-JUN-04:03 | 27.62 |
July | 17905464.96 | 2992.56 | 12-JUL-04:03 | 26.93 |
August | 20856457.46 | 3325.12 | 18-AUG-04:03 | 27.70 |
September | 21574226.96 | 3439.91 | 22-SEP-04:03 | 27.80 |
October | 23022691.10 | 3336.04 | 04-OCT-04:03 | 26.10 |
November | 20625919.90 | 4512.85 | 13-NOV-05:03 | 12.70 |
December | 23768077.44 | 4849.69 | 15-DEC-06:02 | 7.80 |
Annual Sum or Average | 0.239372E+09 | |||
Minimum of Months | 15578325.58 | 2861.52 | 6.70 | |
Maximum of Months | 23768077.44 | 4849.69 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74836.42 | 623.64 | 26-JAN-07:02 | 10.68 |
February | 869670.86 | 5797.81 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 944507.28 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 869670.86 | 5797.81 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 12097931.46 | 6111.92 | 25-JAN-07:02 | 9.50 |
February | 14971609.06 | 6063.35 | 04-FEB-07:03 | 5.28 |
March | 4793287.98 | 6220.01 | 21-MAR-06:02 | 10.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 710764.99 | 6019.23 | 27-NOV-07:02 | 10.37 |
December | 11114878.06 | 6121.27 | 15-DEC-07:01 | 7.88 |
Annual Sum or Average | 43688471.54 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 14971609.06 | 6220.01 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5797771.91 | 3985.58 | 10-JAN-07:03 | 13.07 |
February | 5029171.00 | 3536.63 | 04-FEB-07:03 | 5.28 |
March | 2623386.03 | 4140.55 | 16-MAR-06:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 388456.10 | 3884.56 | 27-NOV-07:02 | 10.37 |
December | 6712345.17 | 4090.51 | 15-DEC-07:03 | 7.88 |
Annual Sum or Average | 20551130.21 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 6712345.17 | 4140.55 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4844209.80 | 6013.14 | 25-JAN-07:02 | 9.50 |
February | 6078805.74 | 5965.14 | 04-FEB-07:03 | 5.28 |
March | 3075911.04 | 6032.21 | 16-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 35611.94 | 356.12 | 27-NOV-07:02 | 10.37 |
December | 6365999.93 | 6028.01 | 15-DEC-07:01 | 7.88 |
Annual Sum or Average | 20400538.45 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 6365999.93 | 6032.21 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9015741.19 | 4113.32 | 10-JAN-07:03 | 13.07 |
February | 10328110.83 | 4145.07 | 03-FEB-07:02 | 10.60 |
March | 3141289.88 | 4019.77 | 16-MAR-06:03 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 722135.65 | 3648.74 | 27-NOV-07:02 | 10.37 |
December | 7732764.56 | 3872.49 | 15-DEC-07:03 | 7.88 |
Annual Sum or Average | 30940042.10 | |||
Minimum of Months | 0.00 | 0.00 | 6.70 | |
Maximum of Months | 10328110.83 | 4145.07 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121867E+09 | 3720.09 | 17-JAN-07:50 | 12.88 |
February | 38579771.00 | 3571.30 | 24-FEB-08:62 | 13.63 |
March | 91723428.71 | 3870.42 | 16-MAR-07:00 | 6.70 |
April | 6087698.39 | 3405.47 | 19-APR-06:08 | 15.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 22303559.95 | 3735.83 | 13-NOV-07:30 | 12.50 |
December | 73829850.61 | 3541.44 | 15-DEC-07:10 | 7.88 |
Annual Sum or Average | 0.354392E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.70 | |
Maximum of Months | 0.121867E+09 | 3870.42 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16.65 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 16.65 | |
Maximum of Months | 0.00 | 0.00 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 137887.12 | 1178.20 | 25-JAN-07:02 | 9.50 |
February | 625663.46 | 3915.52 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 763550.58 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 625663.46 | 3915.52 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 325494.16 | 1970.41 | 25-JAN-07:02 | 9.50 |
February | 356085.19 | 2373.90 | 04-FEB-07:03 | 5.28 |
March | 67187.54 | 783.85 | 16-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 225297.35 | 1447.21 | 15-DEC-07:01 | 7.88 |
Annual Sum or Average | 974064.23 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 356085.19 | 2373.90 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 20.40 |
February | 537324.62 | 3582.16 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.10 |
Annual Sum or Average | 537324.62 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 537324.62 | 3582.16 | 28.60 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 313258.43 | 1616.70 | 25-JAN-07:02 | 9.50 |
February | 493530.84 | 2276.67 | 04-FEB-07:03 | 5.28 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.32 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.57 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 26.68 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 28.60 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 27.05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 27.93 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 |
December | 298390.69 | 1872.25 | 15-DEC-07:01 | 7.88 |
Annual Sum or Average | 1105179.96 | |||
Minimum of Months | 0.00 | 0.00 | 5.28 | |
Maximum of Months | 493530.84 | 2276.67 | 28.60 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.542201E+09 | 772.65 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.466483E+09 | 666.87 | 07-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.530347E+09 | 707.09 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.460813E+09 | 664.46 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.485117E+09 | 496.64 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.482333E+09 | 767.92 | 15-JUN-07:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.449909E+09 | 492.64 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.508088E+09 | 663.99 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.470605E+09 | 889.66 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.506983E+09 | 777.02 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.521442E+09 | 752.75 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.530134E+09 | 841.95 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.595446E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.449909E+09 | 492.64 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.542201E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332710E+09 | 493.25 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.291170E+09 | 429.12 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330429E+09 | 359.26 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.292414E+09 | 377.63 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.309966E+09 | 309.01 | 25-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.308662E+09 | 476.94 | 15-JUN-07:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.287552E+09 | 306.31 | 05-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.322171E+09 | 381.23 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.297512E+09 | 563.23 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.314516E+09 | 472.44 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.324747E+09 | 485.40 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.328959E+09 | 533.33 | 15-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.374081E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.287552E+09 | 306.31 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.332710E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.504179E+09 | 746.92 | 04-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.448299E+09 | 586.73 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.520237E+09 | 671.26 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.462007E+09 | 670.48 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.492038E+09 | 579.94 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.492666E+09 | 782.00 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.456447E+09 | 573.17 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.510861E+09 | 679.14 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.467746E+09 | 889.66 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.490481E+09 | 761.28 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.495922E+09 | 705.79 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.499200E+09 | 838.91 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.584008E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.448299E+09 | 573.17 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.520237E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.329664E+09 | 463.14 | 04-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.288563E+09 | 425.49 | 07-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.334937E+09 | 460.45 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.292637E+09 | 446.83 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.311363E+09 | 397.02 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.310846E+09 | 502.86 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.289026E+09 | 393.33 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.325440E+09 | 448.75 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.298997E+09 | 563.19 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.318793E+09 | 496.46 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.320220E+09 | 460.43 | 24-NOV-08:09 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.321610E+09 | 529.69 | 15-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.374209E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.288563E+09 | 393.33 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.334937E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.538352E+09 | 767.36 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.463918E+09 | 656.33 | 07-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.528001E+09 | 697.10 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.459895E+09 | 654.03 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.484482E+09 | 493.91 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.480408E+09 | 762.48 | 15-JUN-07:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.449098E+09 | 489.69 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.507162E+09 | 653.51 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.469082E+09 | 889.66 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.504546E+09 | 771.91 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.518448E+09 | 746.39 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.526389E+09 | 839.83 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.592978E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.449098E+09 | 489.69 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.538352E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.331609E+09 | 490.73 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.290095E+09 | 424.34 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.329710E+09 | 350.68 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.291828E+09 | 369.70 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.309359E+09 | 307.65 | 25-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.307993E+09 | 473.90 | 15-JUN-07:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.286938E+09 | 304.86 | 05-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.321717E+09 | 373.86 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.296888E+09 | 563.23 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.313875E+09 | 468.79 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.323596E+09 | 482.54 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.327675E+09 | 532.26 | 15-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.373128E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.286938E+09 | 304.86 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.331609E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.503390E+09 | 740.12 | 04-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.447557E+09 | 572.33 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.518923E+09 | 658.35 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.461161E+09 | 660.39 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.490760E+09 | 565.78 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.491156E+09 | 777.13 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.455371E+09 | 558.69 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.509922E+09 | 669.51 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.466749E+09 | 889.66 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.489771E+09 | 755.25 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.495188E+09 | 696.64 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.498124E+09 | 836.61 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.582807E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.447557E+09 | 558.69 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.518923E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.328289E+09 | 459.06 | 04-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.287695E+09 | 420.02 | 07-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.333831E+09 | 455.49 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.291901E+09 | 442.69 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.310560E+09 | 391.11 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.309982E+09 | 500.71 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.288254E+09 | 387.27 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.324610E+09 | 444.68 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.298163E+09 | 563.19 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.317680E+09 | 494.06 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.319299E+09 | 456.76 | 24-NOV-08:09 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.320486E+09 | 528.44 | 15-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.373075E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.287695E+09 | 387.27 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.333831E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.542200E+09 | 772.64 | 04-JAN-16:00 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.466482E+09 | 666.87 | 07-FEB-08:09 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.530346E+09 | 707.10 | 15-MAR-07:10 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.460812E+09 | 664.44 | 12-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.485117E+09 | 496.63 | 25-MAY-07:10 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.482332E+09 | 767.91 | 15-JUN-07:30 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.449908E+09 | 492.64 | 05-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.508087E+09 | 663.97 | 28-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.470593E+09 | 889.66 | 27-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.506982E+09 | 777.01 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.521441E+09 | 752.74 | 29-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.530132E+09 | 841.94 | 15-DEC-16:00 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.595443E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.449908E+09 | 492.64 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.542200E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.332709E+09 | 493.25 | 04-JAN-16:00 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.291169E+09 | 429.11 | 13-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330425E+09 | 359.26 | 02-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.292414E+09 | 377.63 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.309966E+09 | 309.01 | 25-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.308654E+09 | 476.94 | 15-JUN-07:30 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.287551E+09 | 306.31 | 05-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.322171E+09 | 381.23 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.297511E+09 | 563.23 | 27-SEP-07:10 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.314516E+09 | 472.43 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.324746E+09 | 485.39 | 29-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.328958E+09 | 533.32 | 15-DEC-16:00 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.374079E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.287551E+09 | 306.31 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.332709E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.504178E+09 | 746.91 | 04-JAN-16:00 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.448299E+09 | 586.72 | 08-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.520236E+09 | 671.27 | 15-MAR-07:10 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.462007E+09 | 670.47 | 12-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.492037E+09 | 579.92 | 25-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.492664E+09 | 781.99 | 15-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.456446E+09 | 573.15 | 05-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.510860E+09 | 679.13 | 28-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.467745E+09 | 889.66 | 27-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.490481E+09 | 761.27 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.495921E+09 | 705.79 | 29-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.499199E+09 | 838.90 | 15-DEC-16:00 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.584007E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.448299E+09 | 573.15 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.520236E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.329664E+09 | 463.14 | 04-JAN-16:00 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.288563E+09 | 425.50 | 07-FEB-08:09 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.334937E+09 | 460.46 | 15-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.292637E+09 | 446.83 | 12-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.311362E+09 | 397.01 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.310845E+09 | 502.85 | 15-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.289025E+09 | 393.31 | 05-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.325432E+09 | 448.74 | 28-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.298997E+09 | 563.19 | 27-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.318792E+09 | 496.45 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.320219E+09 | 460.42 | 24-NOV-08:09 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.321609E+09 | 529.69 | 15-DEC-16:00 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.374208E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.288563E+09 | 393.31 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.334937E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.542201E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2770939.35 | 44157232.21 |
February | 0.901968E+09 | 0.466483E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4380177.22 | 60161647.57 |
March | 0.107774E+10 | 0.530347E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4699056.11 | 54540800.39 |
April | 0.956342E+09 | 0.460813E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10449400.64 | 24005491.70 |
May | 0.103597E+10 | 0.485117E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24008915.86 | 9749550.38 |
June | 0.103308E+10 | 0.482333E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28231360.26 | 3180413.15 |
July | 0.959235E+09 | 0.449909E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26570405.62 | 2909529.21 |
August | 0.107774E+10 | 0.508088E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31320112.35 | 1627348.53 |
September | 0.956342E+09 | 0.470605E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29510163.01 | 2941278.74 |
October | 0.994195E+09 | 0.506983E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19612719.32 | 6064547.35 |
November | 0.984487E+09 | 0.521442E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9539023.16 | 37653884.11 |
December | 0.959235E+09 | 0.530134E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3709957.76 | 43939114.55 |
Annual Sum or Average | 0.119305E+11 | 0.595446E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194802E+09 | 0.290931E+09 |
Minimum of Months | 0.901968E+09 | 0.449909E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2770939.35 | 1627348.53 |
Maximum of Months | 0.107774E+10 | 0.542201E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31320112.35 | 60161647.57 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.332710E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1276531.54 | 31498691.65 |
February | 0.571020E+09 | 0.291170E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2583851.37 | 42283191.33 |
March | 0.682301E+09 | 0.330429E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2874491.90 | 38260231.69 |
April | 0.605444E+09 | 0.292414E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5993696.45 | 16889002.58 |
May | 0.655854E+09 | 0.309966E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15692592.73 | 6711617.84 |
June | 0.654023E+09 | 0.308662E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18675393.82 | 2172022.68 |
July | 0.607275E+09 | 0.287552E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17289209.41 | 2012720.47 |
August | 0.682301E+09 | 0.322171E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20408089.85 | 1107563.62 |
September | 0.605444E+09 | 0.297512E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19022522.23 | 2045100.17 |
October | 0.629407E+09 | 0.314516E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12369313.48 | 4229533.05 |
November | 0.623262E+09 | 0.324747E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6089967.40 | 26831920.72 |
December | 0.607275E+09 | 0.328959E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2206770.06 | 30237650.84 |
Annual Sum or Average | 0.755301E+10 | 0.374081E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124482E+09 | 0.204279E+09 |
Minimum of Months | 0.571020E+09 | 0.287552E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1276531.54 | 1107563.62 |
Maximum of Months | 0.682301E+09 | 0.332710E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20408089.85 | 42283191.33 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.504179E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1407839.14 | 52692657.55 |
February | 0.901968E+09 | 0.448299E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3009130.17 | 69405755.83 |
March | 0.107774E+10 | 0.520237E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3865563.63 | 59793484.37 |
April | 0.956342E+09 | 0.462007E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8991108.36 | 25213263.57 |
May | 0.103597E+10 | 0.492038E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24210874.74 | 9698353.45 |
June | 0.103308E+10 | 0.492666E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28710644.02 | 3077191.84 |
July | 0.959235E+09 | 0.456447E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26941332.84 | 2820763.52 |
August | 0.107774E+10 | 0.510861E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30957414.16 | 1652424.06 |
September | 0.956342E+09 | 0.467746E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27856418.54 | 3183241.82 |
October | 0.994195E+09 | 0.490481E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16604586.42 | 7302039.68 |
November | 0.984487E+09 | 0.495922E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7321151.98 | 44923181.06 |
December | 0.959235E+09 | 0.499200E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2039619.60 | 51607238.88 |
Annual Sum or Average | 0.119305E+11 | 0.584008E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181916E+09 | 0.331370E+09 |
Minimum of Months | 0.901968E+09 | 0.448299E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1407839.14 | 1652424.06 |
Maximum of Months | 0.107774E+10 | 0.520237E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30957414.16 | 69405755.83 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.329664E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1828561.01 | 30354873.21 |
February | 0.570983E+09 | 0.288563E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2650649.46 | 42264557.40 |
March | 0.682256E+09 | 0.334937E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3163738.70 | 39183431.85 |
April | 0.605404E+09 | 0.292637E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6510201.78 | 18439855.49 |
May | 0.655811E+09 | 0.311363E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15793429.61 | 7400626.52 |
June | 0.653980E+09 | 0.310846E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18608849.92 | 2211316.47 |
July | 0.607235E+09 | 0.289026E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17573927.19 | 2114413.11 |
August | 0.682256E+09 | 0.325440E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20224170.70 | 1162100.92 |
September | 0.605404E+09 | 0.298997E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18937083.12 | 2134868.47 |
October | 0.629366E+09 | 0.318793E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12391619.41 | 4593081.95 |
November | 0.623221E+09 | 0.320220E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6229430.96 | 26062040.39 |
December | 0.607235E+09 | 0.321610E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2302265.84 | 30595674.71 |
Annual Sum or Average | 0.755252E+10 | 0.374209E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126214E+09 | 0.206517E+09 |
Minimum of Months | 0.570983E+09 | 0.288563E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1828561.01 | 1162100.92 |
Maximum of Months | 0.682256E+09 | 0.334937E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20224170.70 | 42264557.40 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.538352E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1376544.11 | 27605924.56 |
February | 0.901968E+09 | 0.463918E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2455430.55 | 36358797.31 |
March | 0.107774E+10 | 0.528001E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2777170.88 | 30548438.24 |
April | 0.956342E+09 | 0.459895E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6271086.15 | 12598887.68 |
May | 0.103597E+10 | 0.484482E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13683508.64 | 4618316.92 |
June | 0.103308E+10 | 0.480408E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16087175.48 | 1369266.74 |
July | 0.959235E+09 | 0.449098E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15189000.57 | 1436740.69 |
August | 0.107774E+10 | 0.507162E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17299732.33 | 856037.09 |
September | 0.956342E+09 | 0.469082E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16405390.28 | 1687168.90 |
October | 0.994195E+09 | 0.504546E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10948866.64 | 3641583.16 |
November | 0.984487E+09 | 0.518448E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5048923.54 | 23327441.94 |
December | 0.959235E+09 | 0.526389E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1945757.56 | 27815957.07 |
Annual Sum or Average | 0.119305E+11 | 0.592978E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109489E+09 | 0.171865E+09 |
Minimum of Months | 0.901968E+09 | 0.449098E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1376544.11 | 856037.09 |
Maximum of Months | 0.107774E+10 | 0.538352E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17299732.33 | 36358797.31 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.331609E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617020.35 | 19945885.24 |
February | 0.571020E+09 | 0.290095E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1402028.90 | 26163210.94 |
March | 0.682301E+09 | 0.329710E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1556941.89 | 22488443.43 |
April | 0.605444E+09 | 0.291828E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3323650.18 | 9613463.54 |
May | 0.655854E+09 | 0.309359E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8519012.65 | 3610543.35 |
June | 0.654023E+09 | 0.307993E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10192169.14 | 1056737.82 |
July | 0.607275E+09 | 0.286938E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9405405.55 | 1159167.86 |
August | 0.682301E+09 | 0.321717E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10847183.91 | 645014.43 |
September | 0.605444E+09 | 0.296888E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10091285.52 | 1291644.91 |
October | 0.629407E+09 | 0.313875E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6560307.48 | 2829318.23 |
November | 0.623262E+09 | 0.323596E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3062771.00 | 16840164.89 |
December | 0.607275E+09 | 0.327675E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1099493.34 | 19488325.88 |
Annual Sum or Average | 0.755301E+10 | 0.373128E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66677269.91 | 0.125132E+09 |
Minimum of Months | 0.571020E+09 | 0.286938E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 617020.35 | 645014.43 |
Maximum of Months | 0.682301E+09 | 0.331609E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10847183.91 | 26163210.94 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.503390E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101702E+09 | 0.147920E+10 |
February | 0.901968E+09 | 0.447557E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224807E+09 | 0.653613E+09 |
March | 0.107774E+10 | 0.518923E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273861E+09 | 0.932228E+09 |
April | 0.956342E+09 | 0.461161E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652218E+09 | 0.210524E+09 |
May | 0.103597E+10 | 0.490760E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141123E+10 | 30746276.24 |
June | 0.103308E+10 | 0.491156E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161409E+10 | 4533264.80 |
July | 0.959235E+09 | 0.455371E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180200E+10 | 7341694.65 |
August | 0.107774E+10 | 0.509922E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193107E+10 | 15966235.19 |
September | 0.956342E+09 | 0.466749E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139541E+10 | 18039895.20 |
October | 0.994195E+09 | 0.489771E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110383E+10 | 59924330.68 |
November | 0.984487E+09 | 0.495188E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608357E+09 | 0.378812E+09 |
December | 0.959235E+09 | 0.498124E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127632E+09 | 0.131546E+10 |
Annual Sum or Average | 0.119305E+11 | 0.582807E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112462E+11 | 0.510639E+10 |
Minimum of Months | 0.901968E+09 | 0.447557E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101702E+09 | 4533264.80 |
Maximum of Months | 0.107774E+10 | 0.518923E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193107E+10 | 0.147920E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.328289E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 748791.56 | 19518014.30 |
February | 0.570983E+09 | 0.287695E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1250680.49 | 26377926.27 |
March | 0.682256E+09 | 0.333831E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1560607.79 | 23356452.61 |
April | 0.605404E+09 | 0.291901E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3335345.09 | 10475622.33 |
May | 0.655811E+09 | 0.310560E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8307440.36 | 4003357.96 |
June | 0.653980E+09 | 0.309982E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10078296.04 | 1067412.27 |
July | 0.607235E+09 | 0.288254E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9395071.29 | 1202539.81 |
August | 0.682256E+09 | 0.324610E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10582547.94 | 683710.23 |
September | 0.605404E+09 | 0.298163E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9900665.30 | 1325947.02 |
October | 0.629366E+09 | 0.317680E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6426014.84 | 3040736.76 |
November | 0.623221E+09 | 0.319299E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3036318.76 | 16634294.09 |
December | 0.607235E+09 | 0.320486E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1050915.32 | 19945605.48 |
Annual Sum or Average | 0.755252E+10 | 0.373075E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65672694.79 | 0.127632E+09 |
Minimum of Months | 0.570983E+09 | 0.287695E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 748791.56 | 683710.23 |
Maximum of Months | 0.682256E+09 | 0.333831E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10582547.94 | 26377926.27 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.542200E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2125180.01 | 41476678.41 |
February | 0.901968E+09 | 0.466482E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3672181.89 | 56041869.86 |
March | 0.107774E+10 | 0.530346E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4001201.23 | 49796885.42 |
April | 0.956342E+09 | 0.460812E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9124627.27 | 21504823.52 |
May | 0.103597E+10 | 0.485117E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20423791.07 | 8471616.77 |
June | 0.103308E+10 | 0.482332E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24173524.20 | 2534230.35 |
July | 0.959235E+09 | 0.449908E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22997515.39 | 2399975.82 |
August | 0.107774E+10 | 0.508087E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26754444.88 | 1361261.97 |
September | 0.956342E+09 | 0.470593E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25257232.32 | 2587562.75 |
October | 0.994195E+09 | 0.506982E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16754601.91 | 5629443.95 |
November | 0.984487E+09 | 0.521441E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7804228.24 | 34939784.98 |
December | 0.959235E+09 | 0.530132E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2988037.38 | 41161019.82 |
Annual Sum or Average | 0.119305E+11 | 0.595443E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166077E+09 | 0.267905E+09 |
Minimum of Months | 0.901968E+09 | 0.449908E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2125180.01 | 1361261.97 |
Maximum of Months | 0.107774E+10 | 0.542200E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26754444.88 | 56041869.86 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.332709E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1046742.69 | 29044078.89 |
February | 0.421807E+09 | 0.291169E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2231789.28 | 38882797.72 |
March | 0.502994E+09 | 0.330425E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2478214.75 | 34401643.16 |
April | 0.447140E+09 | 0.292414E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5256646.66 | 14981905.84 |
May | 0.484071E+09 | 0.309966E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13314966.84 | 5834300.80 |
June | 0.482240E+09 | 0.308654E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15892565.57 | 1742108.16 |
July | 0.448971E+09 | 0.287551E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14813487.51 | 1689830.33 |
August | 0.502994E+09 | 0.322171E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17344556.43 | 928061.66 |
September | 0.447140E+09 | 0.297511E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16117194.19 | 1791789.17 |
October | 0.465148E+09 | 0.314516E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10547623.82 | 3886964.33 |
November | 0.460569E+09 | 0.324746E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5029039.38 | 24542168.71 |
December | 0.448971E+09 | 0.328958E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1814480.96 | 27974648.95 |
Annual Sum or Average | 0.557719E+10 | 0.374079E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105887E+09 | 0.185700E+09 |
Minimum of Months | 0.421807E+09 | 0.287551E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1046742.69 | 928061.66 |
Maximum of Months | 0.502994E+09 | 0.332709E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17344556.43 | 38882797.72 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.504178E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1098090.71 | 48020384.99 |
February | 0.901968E+09 | 0.448299E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2464563.75 | 63249309.81 |
March | 0.107774E+10 | 0.520236E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3267890.14 | 53849037.16 |
April | 0.956342E+09 | 0.462007E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7865180.26 | 22413764.84 |
May | 0.103597E+10 | 0.492037E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20561705.69 | 8433500.81 |
June | 0.103308E+10 | 0.492664E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24594796.69 | 2452448.51 |
July | 0.959235E+09 | 0.456446E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23308603.01 | 2326406.13 |
August | 0.107774E+10 | 0.510860E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26352410.36 | 1383414.47 |
September | 0.956342E+09 | 0.467745E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23536364.81 | 2778697.20 |
October | 0.994195E+09 | 0.490481E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13862544.31 | 6660395.05 |
November | 0.984487E+09 | 0.495921E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5964589.98 | 40745645.01 |
December | 0.959235E+09 | 0.499199E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1630795.91 | 47005955.22 |
Annual Sum or Average | 0.119305E+11 | 0.584007E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154508E+09 | 0.299319E+09 |
Minimum of Months | 0.901968E+09 | 0.448299E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1098090.71 | 1383414.47 |
Maximum of Months | 0.107774E+10 | 0.520236E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26352410.36 | 63249309.81 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.329664E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1307146.15 | 28465613.97 |
February | 0.570983E+09 | 0.288563E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2013463.47 | 39186658.88 |
March | 0.682256E+09 | 0.334937E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2496436.77 | 35641826.30 |
April | 0.605404E+09 | 0.292637E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5296580.72 | 16459633.20 |
May | 0.655811E+09 | 0.311362E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13056549.29 | 6478318.10 |
June | 0.653980E+09 | 0.310845E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15617820.85 | 1793996.21 |
July | 0.607235E+09 | 0.289025E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14804318.92 | 1806778.16 |
August | 0.682256E+09 | 0.325432E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16939258.31 | 984844.75 |
September | 0.605404E+09 | 0.298997E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15765997.18 | 1883461.32 |
October | 0.629366E+09 | 0.318792E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10245549.79 | 4244189.76 |
November | 0.623221E+09 | 0.320219E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4940511.03 | 24188734.48 |
December | 0.607235E+09 | 0.321609E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1736033.79 | 28558380.73 |
Annual Sum or Average | 0.755252E+10 | 0.374208E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104220E+09 | 0.189692E+09 |
Minimum of Months | 0.570983E+09 | 0.288563E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1307146.15 | 984844.75 |
Maximum of Months | 0.682256E+09 | 0.334937E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16939258.31 | 39186658.88 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1311855.33 | 62770228.58 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2414072.61 | 82969703.37 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3142126.02 | 71875754.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8363040.03 | 29375745.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22615518.52 | 9606261.39 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29535007.01 | 2487872.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27575213.40 | 2489261.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31939092.28 | 1646977.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29497972.81 | 3266650.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17372027.11 | 7344923.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7064098.15 | 51162890.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2396255.97 | 61668385.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183226E+09 | 0.386665E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1311855.33 | 1646977.89 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31939092.28 | 82969703.37 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2369191.25 | 74240183.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3612753.56 | 98836536.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4493275.98 | 87257413.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11192585.40 | 36011609.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29348430.20 | 11906107.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37922540.18 | 3372690.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35347684.05 | 3304283.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41657113.22 | 2056106.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38388684.41 | 3971821.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23231499.13 | 8735797.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10365414.85 | 61280820.54 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3690016.85 | 72173425.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241619E+09 | 0.463147E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2369191.25 | 2056106.54 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41657113.22 | 98836536.87 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1190244.65 | 69379204.66 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1157955.76 | 91463438.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1549615.54 | 82489609.55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5808492.11 | 35018715.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25390521.40 | 10500057.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35691262.44 | 3908704.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30840735.94 | 3443409.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39699880.09 | 2209315.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34688788.27 | 2910767.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20937225.84 | 5977978.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9357287.03 | 57084053.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1909079.41 | 68044174.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208221E+09 | 0.432429E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1157955.76 | 2209315.69 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39699880.09 | 91463438.76 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 772.65 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.54 | 15-JAN-14:10 | 131.35 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 666.87 | 07-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.28 | 20-FEB-15:00 | 224.33 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 707.09 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.69 | 05-MAR-13:50 | 227.48 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 664.46 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.70 | 15-APR-17:02 | 74.23 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 496.64 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.21 | 29-MAY-16:08 | 50.20 | 25-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 767.92 | 15-JUN-07:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.36 | 17-JUN-18:17 | 55.33 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 492.64 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.04 | 30-JUL-15:50 | 44.12 | 02-JUL-15:57 |
August | 1306.65 | 01-AUG-09:09 | 663.99 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.72 | 13-AUG-13:00 | 63.41 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 889.66 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.90 | 17-SEP-13:43 | 25.02 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 777.02 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.43 | 29-OCT-12:00 | 45.31 | 01-OCT-07:00 |
November | 1306.65 | 01-NOV-09:09 | 752.75 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.65 | 19-NOV-11:05 | 224.10 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 841.95 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.30 | 10-DEC-14:40 | 206.82 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 492.64 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 34.28 | 25.02 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 127.21 | 227.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 493.25 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.79 | 29-JAN-12:00 | 91.64 | 08-JAN-10:00 |
February | 827.22 | 01-FEB-10:09 | 429.12 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 19-FEB-15:50 | 149.16 | 04-FEB-05:00 |
March | 827.22 | 01-MAR-10:09 | 359.26 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 | 05-MAR-13:50 | 153.28 | 16-MAR-02:00 |
April | 827.22 | 03-APR-09:09 | 377.63 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.82 | 15-APR-17:02 | 49.75 | 18-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 309.01 | 25-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.19 | 29-MAY-16:10 | 33.76 | 07-MAY-19:00 |
June | 827.22 | 01-JUN-09:09 | 476.94 | 15-JUN-07:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.04 | 17-JUN-18:13 | 36.44 | 18-JUN-20:00 |
July | 827.22 | 03-JUL-09:09 | 306.31 | 05-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.10 | 30-JUL-15:50 | 31.62 | 02-JUL-15:57 |
August | 827.22 | 01-AUG-09:09 | 381.23 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.88 | 20-AUG-11:48 | 42.93 | 14-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 563.23 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.94 | 17-SEP-16:50 | 17.26 | 19-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 472.44 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 | 29-OCT-14:20 | 30.53 | 01-OCT-07:00 |
November | 827.22 | 01-NOV-09:09 | 485.40 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 22-NOV-22:03 | 175.50 | 11-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 533.33 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.14 | 10-DEC-14:40 | 137.86 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 306.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 18.91 | 17.26 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 88.19 | 175.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 746.92 | 04-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 | 29-JAN-12:00 | 137.59 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 586.73 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.37 | 02-FEB-14:00 | 230.03 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 671.26 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.31 | 05-MAR-13:50 | 235.10 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 670.48 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.97 | 15-APR-17:02 | 75.36 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 579.94 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.59 | 29-MAY-16:08 | 50.24 | 25-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 782.00 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.45 | 17-JUN-17:40 | 55.47 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 573.17 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.36 | 30-JUL-15:50 | 43.84 | 02-JUL-15:57 |
August | 1306.65 | 01-AUG-09:09 | 679.14 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 | 13-AUG-13:00 | 64.05 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 889.66 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.00 | 17-SEP-16:48 | 27.15 | 03-SEP-14:10 |
October | 1306.65 | 02-OCT-09:09 | 761.28 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.29 | 29-OCT-14:00 | 48.06 | 16-OCT-04:55 |
November | 1306.65 | 01-NOV-09:09 | 705.79 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.15 | 22-NOV-22:03 | 251.70 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 838.91 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 39.63 | 10-DEC-14:58 | 212.54 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 573.17 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 | 27.15 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 127.59 | 251.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 463.14 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 | 15-JAN-12:10 | 88.66 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 425.49 | 07-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 19-FEB-13:10 | 150.07 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 460.45 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.43 | 05-MAR-13:50 | 155.81 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 446.83 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.19 | 16-APR-13:00 | 51.93 | 18-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 397.02 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.44 | 29-MAY-16:04 | 35.52 | 07-MAY-19:00 |
June | 827.17 | 01-JUN-09:09 | 502.86 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.08 | 11-JUN-12:00 | 37.88 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 393.33 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.21 | 30-JUL-15:50 | 29.31 | 02-JUL-15:57 |
August | 827.17 | 01-AUG-09:09 | 448.75 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.34 | 13-AUG-12:40 | 44.49 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 563.19 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.76 | 17-SEP-13:02 | 19.07 | 19-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 496.46 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.80 | 29-OCT-12:20 | 31.41 | 01-OCT-07:00 |
November | 827.17 | 01-NOV-09:09 | 460.43 | 24-NOV-08:09 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.77 | 19-NOV-11:05 | 148.98 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 529.69 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.23 | 10-DEC-13:23 | 137.86 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 393.33 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 19.07 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 80.44 | 155.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 767.36 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.34 | 15-JAN-14:00 | 78.50 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 656.33 | 07-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 20-FEB-14:50 | 139.61 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 697.10 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 | 26-MAR-15:00 | 133.73 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 654.03 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.01 | 15-APR-17:02 | 42.09 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 493.91 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.36 | 29-MAY-16:00 | 24.04 | 25-MAY-04:00 |
June | 1306.65 | 01-JUN-09:09 | 762.48 | 15-JUN-07:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.17 | 17-JUN-17:50 | 25.24 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 489.69 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.07 | 30-JUL-15:50 | 21.70 | 02-JUL-15:57 |
August | 1306.65 | 01-AUG-09:09 | 653.51 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.96 | 13-AUG-13:00 | 33.01 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 889.66 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.20 | 17-SEP-14:00 | 14.01 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 771.91 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.06 | 29-OCT-13:40 | 23.76 | 16-OCT-04:45 |
November | 1306.65 | 01-NOV-09:09 | 746.39 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.43 | 23-NOV-12:00 | 135.03 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 839.83 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.47 | 10-DEC-14:50 | 129.17 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 489.69 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 14.01 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 74.36 | 139.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 490.73 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 | 29-JAN-12:30 | 53.68 | 24-JAN-03:00 |
February | 827.22 | 01-FEB-10:09 | 424.34 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.97 | 19-FEB-16:00 | 93.82 | 04-FEB-05:00 |
March | 827.22 | 01-MAR-10:09 | 350.68 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 | 05-MAR-14:40 | 91.85 | 16-MAR-02:00 |
April | 827.22 | 03-APR-09:09 | 369.70 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.53 | 15-APR-17:02 | 29.26 | 18-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 307.65 | 25-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.93 | 29-MAY-16:00 | 18.73 | 07-MAY-19:00 |
June | 827.22 | 01-JUN-09:09 | 473.90 | 15-JUN-07:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.60 | 17-JUN-17:50 | 17.41 | 18-JUN-20:00 |
July | 827.22 | 03-JUL-09:09 | 304.86 | 05-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.52 | 30-JUL-15:50 | 16.66 | 02-JUL-15:57 |
August | 827.22 | 01-AUG-09:09 | 373.86 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.66 | 13-AUG-13:00 | 23.32 | 14-AUG-03:00 |
September | 827.22 | 01-SEP-09:09 | 563.23 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.36 | 17-SEP-14:00 | 10.26 | 19-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 468.79 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.61 | 29-OCT-14:20 | 16.87 | 16-OCT-04:45 |
November | 827.22 | 01-NOV-09:09 | 482.54 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 23-NOV-12:00 | 102.41 | 11-NOV-09:00 |
December | 827.22 | 01-DEC-10:09 | 532.26 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 | 10-DEC-14:50 | 87.19 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 304.86 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 | 10.26 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 47.93 | 102.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 740.12 | 04-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2865.55 | 23-JAN-17:10 | 14700.48 | 25-JAN-07:02 |
February | 1306.65 | 01-FEB-10:09 | 572.33 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4055.08 | 02-FEB-13:00 | 13411.29 | 03-FEB-07:02 |
March | 1306.65 | 01-MAR-10:09 | 658.35 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6016.91 | 13-MAR-16:03 | 17415.06 | 16-MAR-06:01 |
April | 1306.65 | 03-APR-09:09 | 660.39 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8571.94 | 17-APR-16:03 | 7446.02 | 19-APR-06:03 |
May | 1306.65 | 01-MAY-09:09 | 565.78 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9795.18 | 22-MAY-16:02 | 2653.91 | 01-MAY-06:05 |
June | 1306.65 | 01-JUN-09:09 | 777.13 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8169.44 | 09-JUN-16:03 | 875.25 | 13-JUN-17:00 |
July | 1306.65 | 03-JUL-09:09 | 558.69 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12224.56 | 27-JUL-16:02 | 1386.46 | 14-JUL-17:00 |
August | 1306.65 | 01-AUG-09:09 | 669.51 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10062.65 | 08-AUG-11:02 | 2076.67 | 28-AUG-12:00 |
September | 1306.65 | 01-SEP-09:09 | 889.66 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8693.56 | 08-SEP-16:03 | 2066.30 | 05-SEP-06:03 |
October | 1306.65 | 02-OCT-09:09 | 755.25 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7397.70 | 03-OCT-11:02 | 2485.39 | 31-OCT-06:05 |
November | 1306.65 | 01-NOV-09:09 | 696.64 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4585.48 | 03-NOV-16:05 | 14491.37 | 27-NOV-07:02 |
December | 1306.65 | 01-DEC-10:09 | 836.61 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3405.59 | 08-DEC-12:05 | 16851.00 | 15-DEC-07:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 558.69 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 2865.55 | 875.25 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 12224.56 | 17415.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 459.06 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 | 29-JAN-12:30 | 54.68 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 420.02 | 07-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 | 19-FEB-13:32 | 94.24 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 455.49 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.46 | 05-MAR-14:40 | 93.60 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 442.69 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.71 | 16-APR-13:00 | 30.14 | 18-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 391.11 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.29 | 29-MAY-15:54 | 18.75 | 07-MAY-19:00 |
June | 827.17 | 01-JUN-09:09 | 500.71 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.82 | 11-JUN-12:10 | 18.33 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 387.27 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 30-JUL-15:50 | 15.73 | 02-JUL-15:57 |
August | 827.17 | 01-AUG-09:09 | 444.68 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.38 | 13-AUG-12:20 | 24.47 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 563.19 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.34 | 17-SEP-13:20 | 11.23 | 19-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 494.06 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 29-OCT-12:20 | 17.91 | 16-OCT-04:45 |
November | 827.17 | 01-NOV-09:09 | 456.76 | 24-NOV-08:09 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 | 23-NOV-12:00 | 91.12 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 528.44 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 | 10-DEC-13:42 | 87.75 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 387.27 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 | 11.23 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 43.29 | 94.24 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 772.64 | 04-JAN-16:00 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.03 | 15-JAN-14:10 | 118.83 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 666.87 | 07-FEB-08:09 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 | 20-FEB-14:50 | 208.78 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 707.10 | 15-MAR-07:10 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.28 | 05-MAR-14:00 | 205.78 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 664.44 | 12-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.23 | 15-APR-17:02 | 65.94 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 496.63 | 25-MAY-07:10 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.46 | 29-MAY-16:10 | 43.67 | 25-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 767.91 | 15-JUN-07:30 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.82 | 25-JUN-14:00 | 43.52 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 492.64 | 05-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.66 | 30-JUL-15:50 | 30.72 | 02-JUL-15:27 |
August | 1306.65 | 01-AUG-09:09 | 663.97 | 28-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.99 | 13-AUG-12:20 | 51.42 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 889.66 | 27-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.06 | 17-SEP-14:00 | 20.82 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 777.01 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.12 | 29-OCT-14:00 | 39.20 | 16-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 752.74 | 29-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 | 19-NOV-14:10 | 202.80 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 841.94 | 15-DEC-16:00 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.33 | 10-DEC-15:00 | 192.35 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 492.64 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 | 20.82 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 106.46 | 208.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 493.25 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 | 15-JAN-14:50 | 82.89 | 08-JAN-10:00 |
February | 805.43 | 01-FEB-08:09 | 429.11 | 13-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.18 | 19-FEB-15:50 | 138.64 | 04-FEB-05:00 |
March | 805.43 | 01-MAR-08:09 | 359.26 | 02-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | 05-MAR-14:00 | 138.08 | 16-MAR-02:00 |
April | 805.43 | 03-APR-07:10 | 377.63 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.21 | 15-APR-17:02 | 44.11 | 18-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 309.01 | 25-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.23 | 29-MAY-16:10 | 28.72 | 25-MAY-04:55 |
June | 805.43 | 01-JUN-07:10 | 476.94 | 15-JUN-07:30 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.65 | 17-JUN-17:37 | 28.82 | 18-JUN-20:00 |
July | 805.43 | 03-JUL-07:10 | 306.31 | 05-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.61 | 30-JUL-15:50 | 23.89 | 02-JUL-15:27 |
August | 805.43 | 01-AUG-07:10 | 381.23 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.78 | 13-AUG-13:00 | 34.88 | 14-AUG-03:00 |
September | 805.43 | 01-SEP-07:10 | 563.23 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.57 | 17-SEP-16:40 | 14.33 | 19-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 472.43 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.55 | 29-OCT-14:20 | 25.93 | 16-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 485.39 | 29-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.60 | 22-NOV-22:03 | 157.18 | 11-NOV-09:00 |
December | 805.43 | 01-DEC-08:09 | 533.32 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.20 | 10-DEC-15:00 | 128.00 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 306.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 18.18 | 14.33 | |||||
Maximum of Months | 805.43 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 73.23 | 157.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 746.91 | 04-JAN-16:00 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 15.53 | 07-JAN-13:00 | 123.73 | 24-JAN-03:00 |
February | 1306.65 | 01-FEB-10:09 | 586.72 | 08-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.74 | 02-FEB-14:00 | 213.12 | 04-FEB-05:00 |
March | 1306.65 | 01-MAR-10:09 | 671.27 | 15-MAR-07:10 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.37 | 05-MAR-14:00 | 211.59 | 16-MAR-02:00 |
April | 1306.65 | 03-APR-09:09 | 670.47 | 12-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.42 | 15-APR-17:02 | 66.85 | 18-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 579.92 | 25-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.93 | 29-MAY-16:10 | 43.67 | 25-MAY-04:55 |
June | 1306.65 | 01-JUN-09:09 | 781.99 | 15-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.59 | 17-JUN-17:37 | 43.58 | 18-JUN-20:00 |
July | 1306.65 | 03-JUL-09:09 | 573.15 | 05-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.35 | 30-JUL-15:50 | 30.35 | 02-JUL-15:27 |
August | 1306.65 | 01-AUG-09:09 | 679.13 | 28-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.38 | 13-AUG-12:20 | 51.95 | 14-AUG-03:00 |
September | 1306.65 | 01-SEP-09:09 | 889.66 | 27-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.16 | 17-SEP-16:40 | 22.29 | 19-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 761.27 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.23 | 29-OCT-14:00 | 42.48 | 16-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 705.79 | 29-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.26 | 22-NOV-22:03 | 226.27 | 11-NOV-09:00 |
December | 1306.65 | 01-DEC-10:09 | 838.90 | 15-DEC-16:00 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 10-DEC-15:00 | 197.02 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 573.15 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 15.53 | 22.29 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 106.93 | 226.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 463.14 | 04-JAN-16:00 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.93 | 15-JAN-12:10 | 80.11 | 24-JAN-03:00 |
February | 827.17 | 01-FEB-10:09 | 425.50 | 07-FEB-08:09 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 19-FEB-13:10 | 139.47 | 04-FEB-05:00 |
March | 827.17 | 01-MAR-10:09 | 460.46 | 15-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.32 | 05-MAR-14:00 | 140.46 | 16-MAR-02:00 |
April | 827.17 | 03-APR-09:09 | 446.83 | 12-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.05 | 16-APR-12:57 | 45.97 | 18-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 397.01 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.28 | 29-MAY-16:04 | 28.79 | 25-MAY-04:55 |
June | 827.17 | 01-JUN-09:09 | 502.85 | 15-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 11-JUN-12:00 | 30.19 | 18-JUN-20:00 |
July | 827.17 | 03-JUL-09:09 | 393.31 | 05-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.17 | 30-JUL-15:50 | 21.69 | 02-JUL-15:27 |
August | 827.17 | 01-AUG-09:09 | 448.74 | 28-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.12 | 13-AUG-13:00 | 36.46 | 14-AUG-03:00 |
September | 827.17 | 01-SEP-09:09 | 563.19 | 27-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 17-SEP-13:20 | 15.79 | 19-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 496.45 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.97 | 29-OCT-12:20 | 27.30 | 16-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 460.42 | 24-NOV-08:09 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 | 23-NOV-12:10 | 134.88 | 11-NOV-09:00 |
December | 827.17 | 01-DEC-10:09 | 529.69 | 15-DEC-16:00 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 10-DEC-14:00 | 128.17 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 393.31 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 15.79 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 67.28 | 140.46 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 | 29-JAN-11:53 | 169.62 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.18 | 19-FEB-15:43 | 306.05 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.21 | 05-MAR-13:53 | 295.77 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 15-APR-17:02 | 92.18 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.64 | 29-MAY-16:00 | 49.23 | 25-MAY-04:07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.80 | 25-JUN-13:53 | 45.80 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.27 | 30-JUL-15:50 | 37.25 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.49 | 13-AUG-12:53 | 59.41 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.67 | 17-SEP-14:00 | 23.32 | 04-SEP-24:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.98 | 29-OCT-14:00 | 55.37 | 16-OCT-04:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.99 | 04-NOV-17:03 | 279.08 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.92 | 10-DEC-15:00 | 280.32 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.18 | 23.32 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.64 | 306.05 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.03 | 29-JAN-11:53 | 204.77 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 | 19-FEB-14:10 | 377.29 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.75 | 05-MAR-14:00 | 371.47 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.25 | 15-APR-17:02 | 117.16 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.24 | 29-MAY-15:51 | 64.54 | 25-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.33 | 25-JUN-14:00 | 61.76 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.35 | 30-JUL-15:50 | 47.19 | 02-JUL-16:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.29 | 13-AUG-12:53 | 76.08 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.28 | 17-SEP-14:00 | 30.22 | 04-SEP-24:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.34 | 29-OCT-14:00 | 69.39 | 16-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.72 | 04-NOV-17:03 | 347.69 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.42 | 10-DEC-14:40 | 344.40 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.73 | 30.22 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.24 | 377.29 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.80 | 29-JAN-12:00 | 192.35 | 24-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 02-FEB-14:00 | 323.16 | 04-FEB-05:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 05-MAR-13:53 | 329.90 | 16-MAR-02:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.26 | 15-APR-17:02 | 101.95 | 18-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.94 | 29-MAY-15:51 | 77.57 | 28-MAY-18:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.94 | 16-JUN-21:03 | 77.27 | 18-JUN-20:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.58 | 29-JUL-18:00 | 77.11 | 02-JUL-15:57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.64 | 13-AUG-13:00 | 86.35 | 14-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.32 | 21-SEP-21:03 | 49.18 | 03-SEP-14:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.97 | 29-OCT-11:20 | 65.83 | 01-OCT-07:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.65 | 22-NOV-22:03 | 330.43 | 11-NOV-09:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.11 | 10-DEC-10:00 | 294.00 | 15-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 49.18 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.94 | 330.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 42484.11 | 02-JAN-05:02 | 0.00 | 2344.59 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41386.84 | 13-FEB-05:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41418.75 | 06-MAR-05:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39717.80 | 29-APR-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41323.26 | 22-MAY-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41051.39 | 19-JUN-04:02 | 0.00 | 2344.59 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41011.75 | 06-JUL-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 40741.51 | 29-AUG-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41199.33 | 06-SEP-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 40679.06 | 16-OCT-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 41465.60 | 13-NOV-05:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 40394.08 | 26-DEC-05:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 39717.80 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 42484.11 | 2541.06 | 2344.59 | 22028.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7226.77 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 | 0.00 |
February | 7152.83 | 22-FEB-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 0.00 |
March | 8367.94 | 27-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 0.00 |
April | 9225.37 | 13-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.90 | 0.00 |
May | 10245.72 | 22-MAY-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.43 | 0.00 |
June | 9660.40 | 09-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 0.00 |
July | 10610.78 | 28-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 |
August | 10170.49 | 23-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 0.00 |
September | 9885.44 | 18-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 | 0.00 |
October | 9525.06 | 06-OCT-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 0.00 |
November | 7676.62 | 10-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.18 | 0.00 |
December | 6623.88 | 08-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6623.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 0.00 | |
Maximum of Months | 10610.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.43 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3260.68 | 02-JAN-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 | 0.00 |
February | 2800.03 | 21-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 | 0.00 |
March | 3225.75 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.66 | 0.00 |
April | 3409.07 | 17-APR-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 0.00 |
May | 4404.80 | 30-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 |
June | 4202.84 | 19-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 |
July | 4445.67 | 31-JUL-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 0.00 |
August | 4359.82 | 21-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.36 | 0.00 |
September | 4670.13 | 25-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 |
October | 4404.61 | 02-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 | 0.00 |
November | 3487.51 | 06-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 0.00 |
December | 2902.37 | 11-DEC-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2800.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4670.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 4.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4059.11 | 02-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 | 0.00 |
February | 3437.61 | 21-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 0.00 |
March | 3627.43 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | 0.00 |
April | 3759.56 | 17-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.23 | 0.00 |
May | 4538.21 | 22-MAY-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 | 0.00 |
June | 4425.38 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4863.45 | 31-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 | 0.00 |
August | 4581.54 | 28-AUG-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 | 0.00 |
September | 4708.92 | 05-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 |
October | 4742.50 | 02-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.11 | 0.00 |
November | 3986.56 | 06-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 0.00 |
December | 3484.56 | 11-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3437.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4863.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 | 5.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 30384.96 | 02-JAN-05:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29179.71 | 13-FEB-06:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 28820.12 | 28-MAR-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29089.15 | 18-APR-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29589.29 | 22-MAY-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 28343.09 | 05-JUN-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 28894.97 | 24-JUL-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28996.60 | 14-AUG-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29308.79 | 05-SEP-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29927.52 | 16-OCT-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30047.26 | 06-NOV-05:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28369.71 | 04-DEC-06:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 28343.09 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30384.96 | 2541.06 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 25234.47 | 02-JAN-06:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20525.89 | 13-FEB-06:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31225.53 | 06-MAR-06:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31532.58 | 17-APR-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32459.99 | 22-MAY-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 32355.68 | 19-JUN-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32121.01 | 24-JUL-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31674.30 | 07-AUG-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32716.49 | 05-SEP-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32110.38 | 10-OCT-04:02 | 0.00 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31638.54 | 06-NOV-06:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31007.00 | 26-DEC-06:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 20525.89 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32716.49 | 2541.06 | 2344.59 | 12210.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4747.40 | 02-JAN-15:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 0.00 |
February | 4752.88 | 17-FEB-14:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.92 | 0.00 |
March | 5305.44 | 27-MAR-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.80 | 0.00 |
April | 6337.61 | 17-APR-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 19.98 | 0.00 |
May | 9459.20 | 30-MAY-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 |
June | 10310.05 | 25-JUN-15:13 | 267.84 | 94.29 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 15.34 | 0.00 |
July | 10969.60 | 30-JUL-14:23 | 267.84 | 94.29 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 0.00 |
August | 10734.41 | 06-AUG-14:13 | 267.84 | 94.29 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 61.70 | 0.00 |
September | 9660.06 | 24-SEP-15:43 | 267.84 | 94.29 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 36.68 | 0.00 |
October | 9352.82 | 02-OCT-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 | 0.00 |
November | 5405.86 | 03-NOV-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.65 | 0.00 |
December | 4579.08 | 08-DEC-14:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4579.08 | 0.00 | 94.29 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10969.60 | 1306.65 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 61.70 | 3.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8085.55 | 01-JAN-10:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 |
February | 4358.08 | 28-FEB-10:20 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 0.00 |
March | 5952.85 | 27-MAR-10:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 | 0.00 |
April | 10695.86 | 16-APR-08:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 |
May | 7188.05 | 30-MAY-04:02 | 0.00 | 312.91 | 1629.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 |
June | 10747.37 | 04-JUN-08:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 | 0.00 |
July | 10771.03 | 16-JUL-08:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.04 | 0.00 |
August | 10726.54 | 20-AUG-09:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 23.87 | 0.00 |
September | 10788.28 | 24-SEP-09:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.41 | 0.00 |
October | 10631.35 | 09-OCT-09:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 7.38 | 0.00 |
November | 5153.44 | 07-NOV-09:50 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 |
December | 4329.84 | 08-DEC-10:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4329.84 | 0.00 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10788.28 | 827.22 | 312.91 | 1629.47 | 0.00 | 0.00 | 0.00 | 0.00 | 23.87 | 13.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12362.75 | 01-JAN-13:22 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 |
February | 12579.55 | 20-FEB-14:32 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.96 |
March | 11752.44 | 26-MAR-14:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 6.15 | 0.00 |
April | 8921.76 | 16-APR-15:32 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 27.34 | 0.00 |
May | 9653.54 | 30-MAY-04:02 | 0.00 | 494.26 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 |
June | 9491.18 | 12-JUN-04:02 | 0.00 | 494.26 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 |
July | 11403.28 | 30-JUL-13:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 69.27 | 0.00 |
August | 11337.83 | 20-AUG-11:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 73.07 | 0.00 |
September | 11816.60 | 24-SEP-11:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 47.90 | 0.00 |
October | 12103.52 | 15-OCT-12:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 0.00 |
November | 12142.89 | 19-NOV-12:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.09 |
December | 12085.57 | 25-DEC-14:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8921.76 | 0.00 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12579.55 | 334.80 | 494.26 | 2574.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.07 | 26.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5031.12 | 03-JAN-15:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 0.00 |
February | 11443.30 | 19-FEB-15:43 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | 0.00 |
March | 11825.93 | 12-MAR-15:53 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 |
April | 11975.77 | 09-APR-16:32 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
May | 11978.75 | 29-MAY-16:42 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 | 0.00 |
June | 11718.13 | 25-JUN-16:33 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 5.88 | 0.00 |
July | 11929.49 | 09-JUL-16:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 24.98 | 0.00 |
August | 11856.11 | 20-AUG-16:22 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 | 0.00 |
September | 11934.79 | 10-SEP-15:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 36.96 | 0.00 |
October | 11831.68 | 09-OCT-15:02 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 13.48 | 0.00 |
November | 9234.57 | 05-NOV-15:32 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 0.00 |
December | 8039.99 | 03-DEC-16:12 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5031.12 | 169.55 | 59.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11978.75 | 805.38 | 268.64 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 | 19.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4391.70 | 02-JAN-15:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 | 0.00 |
February | 4068.08 | 17-FEB-14:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 0.00 |
March | 4320.54 | 06-MAR-14:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 0.00 |
April | 5066.45 | 17-APR-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 0.00 |
May | 7389.93 | 30-MAY-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 |
June | 7260.14 | 12-JUN-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
July | 7520.37 | 05-JUL-04:03 | 0.00 | 395.41 | 2059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
August | 7448.34 | 01-AUG-04:03 | 0.00 | 395.41 | 2059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 | 0.00 |
September | 7399.46 | 11-SEP-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | 0.00 |
October | 7339.53 | 30-OCT-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 | 0.00 |
November | 4864.38 | 03-NOV-13:50 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 0.00 |
December | 4325.78 | 01-DEC-14:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4068.08 | 0.00 | 395.41 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7520.37 | 1306.65 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 | 1.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8535.93 | 01-JAN-10:32 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.88 |
February | 4219.11 | 28-FEB-10:10 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 | 0.00 |
March | 5154.87 | 27-MAR-10:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 | 0.00 |
April | 8223.34 | 16-APR-08:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 |
May | 7998.43 | 07-MAY-09:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2.61 | 0.00 |
June | 9334.26 | 04-JUN-08:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 0.00 |
July | 9687.88 | 23-JUL-11:12 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 | 0.00 |
August | 9333.85 | 20-AUG-10:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 0.00 |
September | 9408.22 | 24-SEP-09:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 0.00 |
October | 9361.08 | 09-OCT-08:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 0.00 |
November | 4920.74 | 07-NOV-09:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 | 0.00 |
December | 4121.70 | 08-DEC-10:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4121.70 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9687.88 | 827.22 | 268.66 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 6.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10036.21 | 01-JAN-12:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 |
February | 9909.11 | 20-FEB-12:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.36 |
March | 8353.29 | 13-MAR-16:10 | 1205.27 | 707.27 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 5227.76 | 0.00 |
April | 8777.13 | 17-APR-16:10 | 1607.03 | 943.02 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 7146.04 | 0.00 |
May | 9527.95 | 22-MAY-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7933.11 | 0.00 |
June | 8792.08 | 09-JUN-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6699.59 | 0.00 |
July | 9739.00 | 27-JUL-16:50 | 401.76 | 235.76 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 8997.27 | 0.00 |
August | 9616.35 | 23-AUG-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 7846.28 | 0.00 |
September | 9685.08 | 24-SEP-11:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 | 0.00 |
October | 9930.13 | 29-OCT-11:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 22.08 | 0.00 |
November | 9941.51 | 19-NOV-12:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.64 |
December | 10103.40 | 10-DEC-13:23 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8353.29 | 267.84 | 94.29 | 797.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10103.40 | 1607.03 | 943.02 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 8997.27 | 29.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4611.74 | 02-JAN-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 | 0.00 |
February | 9915.51 | 20-FEB-17:23 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.54 |
March | 5698.41 | 27-MAR-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 0.00 |
April | 8955.17 | 01-APR-17:42 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 | 0.00 |
May | 9968.57 | 29-MAY-16:31 | 296.72 | 104.46 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 0.00 |
June | 7878.84 | 10-JUN-17:06 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 0.00 |
July | 9523.94 | 09-JUL-16:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 14.56 | 0.00 |
August | 9906.24 | 13-AUG-16:12 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 17.22 | 0.00 |
September | 10114.15 | 17-SEP-17:12 | 0.00 | 74.61 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.08 | 0.00 |
October | 9831.56 | 09-OCT-16:53 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 | 0.00 |
November | 5711.57 | 07-NOV-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 0.00 |
December | 7029.10 | 10-DEC-15:23 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 10.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4611.74 | 0.00 | 59.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10114.15 | 805.38 | 268.64 | 2119.99 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 | 4.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4446.52 | 02-JAN-15:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 0.00 |
February | 4310.05 | 17-FEB-14:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 10.86 | 0.00 |
March | 4648.46 | 28-MAR-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 0.00 |
April | 6622.58 | 13-APR-05:03 | 535.68 | 395.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 |
May | 7456.09 | 30-MAY-05:03 | 535.68 | 395.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 |
June | 7885.66 | 05-JUN-04:03 | 0.00 | 395.41 | 2059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
July | 7763.15 | 17-JUL-04:03 | 0.00 | 395.41 | 2059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.85 | 0.00 |
August | 7800.08 | 01-AUG-04:03 | 0.00 | 395.41 | 2059.22 | 0.00 | 0.00 | 0.00 | 0.00 | 17.63 | 0.00 |
September | 7880.72 | 05-SEP-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7611.65 | 10-OCT-04:02 | 0.00 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
November | 6824.20 | 21-NOV-06:03 | 535.68 | 395.41 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 0.00 |
December | 4200.32 | 01-DEC-14:10 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4200.32 | 0.00 | 395.41 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7885.66 | 1306.65 | 494.26 | 2574.02 | 0.00 | 0.00 | 0.00 | 0.00 | 17.63 | 1.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4770.26 | 02-JAN-10:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 0.00 |
February | 4689.92 | 28-FEB-09:50 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 | 0.00 |
March | 5619.44 | 27-MAR-10:20 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 |
April | 10110.74 | 16-APR-08:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.18 |
May | 9876.96 | 07-MAY-09:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 | 0.00 |
June | 10131.44 | 04-JUN-08:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 4.66 | 0.00 |
July | 10474.75 | 23-JUL-08:32 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9.66 | 0.00 |
August | 10050.69 | 20-AUG-09:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 | 0.00 |
September | 10124.73 | 24-SEP-09:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 9.20 | 0.00 |
October | 10052.16 | 09-OCT-09:02 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 6.05 | 0.00 |
November | 5294.94 | 07-NOV-09:30 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 | 0.00 |
December | 4234.05 | 08-DEC-10:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4234.05 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10474.75 | 805.43 | 268.66 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 18.11 | 11.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10228.09 | 01-JAN-12:53 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
February | 10281.02 | 20-FEB-12:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.69 |
March | 9849.62 | 26-MAR-14:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 6.65 | 0.00 |
April | 7100.34 | 13-APR-05:03 | 535.68 | 395.41 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
May | 7570.24 | 30-MAY-05:03 | 535.68 | 395.41 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.89 |
June | 7890.34 | 26-JUN-04:03 | 0.00 | 395.41 | 2059.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
July | 9420.01 | 30-JUL-13:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 62.15 | 0.00 |
August | 9107.94 | 06-AUG-14:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 52.13 | 0.00 |
September | 9890.78 | 24-SEP-11:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 42.14 | 0.00 |
October | 10185.93 | 15-OCT-12:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 0.00 |
November | 10222.28 | 19-NOV-12:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.15 |
December | 10331.79 | 10-DEC-13:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7100.34 | 0.00 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10331.79 | 535.68 | 395.41 | 2551.53 | 0.00 | 0.00 | 0.00 | 0.00 | 62.15 | 50.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4801.30 | 03-JAN-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 0.00 |
February | 10658.87 | 20-FEB-16:42 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 |
March | 10193.23 | 12-MAR-15:53 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 |
April | 10724.84 | 02-APR-17:03 | 0.00 | 59.69 | 977.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 |
May | 10644.90 | 29-MAY-16:42 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 55.62 | 0.00 |
June | 9997.13 | 10-JUN-17:06 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 | 0.00 |
July | 10579.85 | 09-JUL-16:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 | 0.00 |
August | 10765.20 | 13-AUG-16:12 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 | 0.00 |
September | 10866.27 | 17-SEP-17:12 | 0.00 | 74.61 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.91 | 0.00 |
October | 10461.56 | 09-OCT-15:02 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 11.27 | 0.00 |
November | 7586.71 | 05-NOV-15:32 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 | 0.00 |
December | 9106.46 | 10-DEC-15:32 | 169.55 | 59.69 | 1211.42 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4801.30 | 0.00 | 59.69 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10866.27 | 805.38 | 268.64 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 55.62 | 16.03 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.119799E+12 | 126393.08 | 02-JAN-13:00 | 0.795718E+10 | 8808.78 | 24-JAN-12:09 |
February | 0.112147E+12 | 111517.48 | 17-FEB-13:00 | 0.718906E+10 | 10285.79 | 04-FEB-06:00 |
March | 0.131445E+12 | 120861.76 | 27-MAR-15:20 | 0.809133E+10 | 8769.98 | 02-MAR-12:50 |
April | 0.130602E+12 | 127319.71 | 14-APR-15:09 | 0.737600E+10 | 8710.97 | 03-APR-11:30 |
May | 0.151745E+12 | 137831.69 | 22-MAY-12:00 | 0.756826E+10 | 8657.11 | 01-MAY-11:09 |
June | 0.157729E+12 | 134185.09 | 26-JUN-12:30 | 0.727487E+10 | 8599.51 | 05-JUN-11:09 |
July | 0.160780E+12 | 144721.22 | 28-JUL-15:30 | 0.714440E+10 | 8574.50 | 03-JUL-11:20 |
August | 0.167461E+12 | 141566.11 | 21-AUG-15:00 | 0.752548E+10 | 8595.24 | 30-AUG-11:20 |
September | 0.154356E+12 | 138788.26 | 18-SEP-15:30 | 0.716431E+10 | 8646.74 | 29-SEP-11:20 |
October | 0.150764E+12 | 136721.97 | 02-OCT-15:09 | 0.757566E+10 | 8704.44 | 31-OCT-11:50 |
November | 0.134412E+12 | 124290.74 | 10-NOV-13:00 | 0.757107E+10 | 8757.84 | 30-NOV-12:20 |
December | 0.120582E+12 | 117910.77 | 08-DEC-16:10 | 0.779808E+10 | 8799.53 | 29-DEC-12:20 |
Annual Sum or Average | 0.169182E+13 | 0.902357E+11 | ||||
Minimum of Months | 0.112147E+12 | 111517.48 | 0.714440E+10 | 8574.50 | ||
Maximum of Months | 0.167461E+12 | 144721.22 | 0.809133E+10 | 10285.79 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.172175E+11 | 0.502192E+10 | 0.593559E+11 | 0.979903E+09 | 0.512080E+10 | 1312252.65 | 0.407392E+09 | 0.303622E+11 | 0.00 | 0.00 | 0.133170E+10 | 0.00 | 0.00 |
February | 0.154524E+11 | 0.419958E+10 | 0.537310E+11 | 0.886710E+09 | 0.507598E+10 | 1186778.30 | 0.256973E+09 | 0.313272E+11 | 0.00 | 0.00 | 0.121576E+10 | 0.00 | 0.00 |
March | 0.181827E+11 | 0.426300E+10 | 0.617796E+11 | 0.102610E+10 | 0.621917E+10 | 1343621.24 | 0.249984E+09 | 0.383065E+11 | 0.00 | 0.00 | 0.141706E+10 | 0.00 | 0.00 |
April | 0.161682E+11 | 0.376543E+10 | 0.572952E+11 | 0.943635E+09 | 0.663729E+10 | 1267813.82 | 11612686.53 | 0.444059E+11 | 0.00 | 0.00 | 0.137352E+10 | 0.00 | 0.00 |
May | 0.173615E+11 | 0.355719E+10 | 0.605677E+11 | 0.100276E+10 | 0.843747E+10 | 1327936.95 | 0.00 | 0.593679E+11 | 0.00 | 0.00 | 0.144888E+10 | 0.00 | 0.00 |
June | 0.172872E+11 | 0.331854E+10 | 0.594895E+11 | 0.987143E+09 | 0.888415E+10 | 1296568.36 | 0.00 | 0.663085E+11 | 0.00 | 0.00 | 0.145287E+10 | 0.00 | 0.00 |
July | 0.161540E+11 | 0.349518E+10 | 0.583622E+11 | 0.959118E+09 | 0.934244E+10 | 1299182.41 | 0.00 | 0.709891E+11 | 0.00 | 0.00 | 0.147669E+10 | 0.00 | 0.00 |
August | 0.180369E+11 | 0.376926E+10 | 0.617796E+11 | 0.102599E+10 | 0.961695E+10 | 1343621.24 | 0.00 | 0.717261E+11 | 0.00 | 0.00 | 0.150533E+10 | 0.00 | 0.00 |
September | 0.162483E+11 | 0.394424E+10 | 0.572729E+11 | 0.943461E+09 | 0.883232E+10 | 1267813.82 | 0.00 | 0.656814E+11 | 0.00 | 0.00 | 0.143185E+10 | 0.00 | 0.00 |
October | 0.169858E+11 | 0.446173E+10 | 0.593671E+11 | 0.979848E+09 | 0.850170E+10 | 1312252.65 | 0.00 | 0.590546E+11 | 0.00 | 0.00 | 0.141211E+10 | 0.00 | 0.00 |
November | 0.169378E+11 | 0.472891E+10 | 0.580818E+11 | 0.961634E+09 | 0.671004E+10 | 1278270.02 | 50037688.78 | 0.456360E+11 | 0.00 | 0.00 | 0.130470E+10 | 0.00 | 0.00 |
December | 0.167409E+11 | 0.510862E+10 | 0.583511E+11 | 0.959414E+09 | 0.526641E+10 | 1299182.41 | 0.367574E+09 | 0.324636E+11 | 0.00 | 0.00 | 0.132258E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.202773E+12 | 0.496336E+11 | 0.705434E+12 | 0.116557E+11 | 0.886447E+11 | 15535293.87 | 0.134357E+10 | 0.615629E+12 | 0.00 | 0.00 | 0.166931E+11 | 0.00 | 0.00 |
Minimum of Months | 0.154524E+11 | 0.331854E+10 | 0.537310E+11 | 0.886710E+09 | 0.507598E+10 | 1186778.30 | 0.00 | 0.303622E+11 | 0.00 | 0.00 | 0.121576E+10 | 0.00 | 0.00 |
Maximum of Months | 0.181827E+11 | 0.510862E+10 | 0.617796E+11 | 0.102610E+10 | 0.961695E+10 | 1343621.24 | 0.407392E+09 | 0.717261E+11 | 0.00 | 0.00 | 0.150533E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.795718E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 12084726.56 | 0.00 | 0.717698E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.809133E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.737600E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.756826E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.727487E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.714440E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.752548E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.716431E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.757566E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.757107E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.779808E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12084726.56 | 0.00 | 0.902236E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.714440E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 12084726.56 | 0.00 | 0.809133E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 20069.79 | 04-JAN-16:00 | 5557.43 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 831.82 | 04-JAN-16:00 | 10296.81 | 02-JAN-14:00 | 0.73 | 01-JAN-06:10 | 21054.76 | 26-JAN-07:10 |
February | 18550.25 | 08-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 830.86 | 07-FEB-08:20 | 9251.13 | 21-FEB-16:19 | 0.73 | 01-FEB-06:30 | 27441.73 | 04-FEB-07:10 |
March | 19025.44 | 14-MAR-07:10 | 5557.43 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 832.21 | 14-MAR-07:19 | 10434.22 | 27-MAR-15:30 | 0.73 | 01-MAR-06:30 | 18245.21 | 16-MAR-06:10 |
April | 19106.18 | 12-APR-07:10 | 5557.43 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 832.32 | 12-APR-07:19 | 10603.70 | 17-APR-15:20 | 0.73 | 01-APR-05:10 | 4133.59 | 19-APR-06:19 |
May | 17967.09 | 25-MAY-07:10 | 5557.43 | 01-MAY-05:10 | 45864.70 | 01-MAY-07:10 | 830.81 | 25-MAY-07:19 | 12205.64 | 22-MAY-12:00 | 0.73 | 01-MAY-05:10 | 0.00 | 01-MAY-00:10 |
June | 20172.16 | 15-JUN-07:10 | 5557.43 | 01-JUN-05:10 | 45864.70 | 01-JUN-07:10 | 833.73 | 15-JUN-07:19 | 11260.99 | 26-JUN-12:30 | 0.73 | 01-JUN-05:10 | 0.00 | 01-JUN-00:10 |
July | 17910.26 | 05-JUL-07:10 | 5557.43 | 01-JUL-05:10 | 45864.70 | 03-JUL-07:10 | 830.74 | 05-JUL-07:19 | 13282.93 | 31-JUL-14:30 | 0.73 | 01-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 19148.35 | 28-AUG-07:10 | 5557.43 | 01-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 832.38 | 28-AUG-07:19 | 12410.88 | 21-AUG-15:09 | 0.73 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 21377.78 | 27-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 835.33 | 27-SEP-07:19 | 12534.26 | 18-SEP-13:50 | 0.73 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
October | 20164.97 | 31-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 833.72 | 31-OCT-07:19 | 12491.21 | 02-OCT-15:09 | 0.73 | 01-OCT-05:10 | 0.00 | 01-OCT-00:10 |
November | 19757.53 | 29-NOV-16:00 | 5557.43 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 832.84 | 24-NOV-08:20 | 10645.11 | 06-NOV-15:30 | 0.73 | 01-NOV-05:10 | 9489.43 | 27-NOV-07:10 |
December | 20885.47 | 15-DEC-16:00 | 5557.43 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 833.25 | 29-DEC-08:39 | 8778.45 | 08-DEC-16:10 | 0.73 | 01-DEC-06:10 | 19718.03 | 21-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 17910.26 | 5557.43 | 45864.70 | 830.74 | 8778.45 | 0.73 | 0.00 | |||||||
Maximum of Months | 21377.78 | 5557.43 | 45864.70 | 835.33 | 13282.93 | 0.73 | 27441.73 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 55419.50 | 02-JAN-13:00 | 0.00 | 0.00 | 907.56 | 01-JAN-08:20 | 0.00 | 0.00 |
February | 42676.05 | 17-FEB-13:00 | 0.00 | 0.00 | 907.56 | 01-FEB-06:10 | 0.00 | 0.00 |
March | 49844.17 | 27-MAR-15:09 | 0.00 | 0.00 | 907.56 | 01-MAR-06:10 | 0.00 | 0.00 |
April | 56816.66 | 14-APR-14:00 | 0.00 | 0.00 | 907.56 | 01-APR-05:19 | 0.00 | 0.00 |
May | 64668.82 | 22-MAY-12:00 | 0.00 | 0.00 | 907.56 | 01-MAY-05:19 | 0.00 | 0.00 |
June | 61966.87 | 26-JUN-12:30 | 0.00 | 0.00 | 907.56 | 01-JUN-04:19 | 0.00 | 0.00 |
July | 71361.11 | 28-JUL-15:30 | 0.00 | 0.00 | 907.56 | 01-JUL-05:19 | 0.00 | 0.00 |
August | 68577.65 | 21-AUG-15:00 | 0.00 | 0.00 | 907.56 | 01-AUG-04:19 | 0.00 | 0.00 |
September | 65692.33 | 18-SEP-15:30 | 0.00 | 0.00 | 907.56 | 01-SEP-04:19 | 0.00 | 0.00 |
October | 64971.01 | 02-OCT-13:00 | 0.00 | 0.00 | 907.56 | 01-OCT-10:50 | 0.00 | 0.00 |
November | 54527.77 | 03-NOV-13:00 | 0.00 | 0.00 | 907.56 | 01-NOV-05:19 | 0.00 | 0.00 |
December | 48054.01 | 08-DEC-15:00 | 0.00 | 0.00 | 907.56 | 01-DEC-06:19 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 42676.05 | 0.00 | 0.00 | 907.56 | 0.00 | 0.00 | ||
Maximum of Months | 71361.11 | 0.00 | 0.00 | 907.56 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 126393.08 | 02-JAN-13:00 | 16818.70 | 42402.18 | 0.00 | 828.07 | 10016.35 | 0.73 | 0.00 | 55419.50 | 0.00 |
February | 111517.48 | 17-FEB-13:00 | 16818.70 | 42402.18 | 0.00 | 828.07 | 7884.20 | 0.73 | 0.00 | 42676.05 | 0.00 |
March | 120861.76 | 27-MAR-15:20 | 16818.70 | 42072.41 | 0.00 | 827.95 | 10413.33 | 0.73 | 0.00 | 49821.08 | 0.00 |
April | 127319.71 | 14-APR-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 9956.05 | 0.73 | 0.00 | 56736.32 | 0.00 |
May | 137831.69 | 22-MAY-12:00 | 16818.70 | 42402.18 | 0.00 | 828.07 | 12205.64 | 0.73 | 0.00 | 64668.82 | 0.00 |
June | 134185.09 | 26-JUN-12:30 | 16818.70 | 42402.18 | 0.00 | 828.07 | 11260.99 | 0.73 | 0.00 | 61966.87 | 0.00 |
July | 144721.22 | 28-JUL-15:30 | 16818.70 | 42072.41 | 0.00 | 827.95 | 12732.76 | 0.73 | 0.00 | 71361.11 | 0.00 |
August | 141566.11 | 21-AUG-15:00 | 16818.70 | 42072.41 | 0.00 | 827.95 | 12361.12 | 0.73 | 0.00 | 68577.65 | 0.00 |
September | 138788.26 | 18-SEP-15:30 | 16818.70 | 42072.41 | 0.00 | 827.95 | 12468.59 | 0.73 | 0.00 | 65692.33 | 0.00 |
October | 136721.97 | 02-OCT-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 12491.21 | 0.73 | 0.00 | 63603.41 | 0.00 |
November | 124290.74 | 10-NOV-13:00 | 16818.70 | 42402.18 | 0.00 | 828.07 | 9591.54 | 0.73 | 0.00 | 53741.97 | 0.00 |
December | 117910.77 | 08-DEC-16:10 | 17585.64 | 42072.41 | 0.00 | 828.77 | 8778.45 | 0.73 | 0.00 | 47737.21 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 111517.48 | 16818.70 | 42072.41 | 0.00 | 827.95 | 7884.20 | 0.73 | 0.00 | 42676.05 | 0.00 | |
Maximum of Months | 144721.22 | 17585.64 | 42402.18 | 0.00 | 828.77 | 12732.76 | 0.73 | 0.00 | 71361.11 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 8808.78 | 24-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 2487.39 | 04-FEB-06:00 | 0.00 | 8801.78 | 03-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 8769.98 | 02-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 8710.97 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 8657.11 | 01-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 8599.51 | 05-JUN-11:09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 8574.50 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 8595.24 | 30-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 8646.74 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 8704.44 | 31-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 8757.84 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 8799.53 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8574.50 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 2487.39 | 0.00 | 8808.78 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.43 | 0.83 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.31 | 0.50 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.42 | 2.83 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.43 | 1.67 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.83 | 27.41 | 5.83 | 27.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.43 | 2.83 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.36 | 0.33 | 27.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.39 | 0.17 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.62 | 3.33 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.48 | 3.83 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.65 | 5.67 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.78 | 13.00 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.63 | 5.67 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.58 | 7.17 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.69 | 1.33 | 27.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.67 | 27.66 | 40.50 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.78 | 13.00 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.48 | 6.83 | 26.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.33 | 4.67 | 27.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.48 | 1.33 | 27.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.45 | 1.00 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.44 | 1.00 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.43 | 3.67 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.58 | 2.50 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.73 | 6.17 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.82 | 8.00 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.10 | 11.17 | 26.10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 26.77 | 7.50 | 26.77 |
Annual Sum or Average | 0.00 | 0.00 | 54.33 | 27.04 | 53.83 | 27.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.82 | 11.17 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.00 | 1.33 | 28.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.78 | 0.67 | 27.75 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.87 | 3.00 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.90 | 2.17 | 27.92 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.81 | 1.83 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.90 | 5.17 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.00 | 2.83 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.87 | 4.00 | 27.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.77 | 3.50 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.40 | 0.33 | 27.40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.50 | 0.50 | 27.50 |
Annual Sum or Average | 0.00 | 0.00 | 33.83 | 27.87 | 25.33 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.00 | 5.17 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.39 | 0.50 | 27.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.46 | 1.33 | 27.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.57 | 1.83 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.61 | 6.83 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.44 | 2.50 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.46 | 4.33 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.56 | 1.33 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
Annual Sum or Average | 0.00 | 0.00 | 19.67 | 27.52 | 19.67 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.61 | 6.83 | 27.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 19.80 | 5.33 | 19.80 | 12.33 | 23.08 | 12.33 | 24.07 |
February | 2.17 | 19.78 | 2.17 | 19.78 | 14.17 | 24.07 | 14.17 | 24.63 |
March | 6.00 | 19.23 | 6.00 | 19.23 | 1.17 | 19.72 | 1.17 | 20.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 24.99 | 7.50 | 24.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 25.09 | 25.17 | 25.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 25.06 | 31.17 | 25.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 | 25.50 | 37.17 | 25.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 | 25.33 | 45.00 | 25.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 63.33 | 25.34 | 63.33 | 25.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | 25.30 | 83.67 | 25.30 |
November | 0.83 | 20.25 | 0.83 | 20.25 | 52.50 | 25.02 | 52.50 | 25.10 |
December | 5.67 | 19.56 | 5.67 | 19.56 | 15.83 | 23.13 | 15.83 | 24.07 |
Annual Sum or Average | 20.00 | 19.58 | 20.00 | 19.58 | 389.17 | 24.77 | 389.00 | 25.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 19.72 | 1.17 | 20.14 |
Maximum of Months | 6.00 | 20.25 | 6.00 | 20.25 | 83.83 | 25.50 | 83.67 | 25.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.61 | 1.17 | 27.61 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.50 | 0.33 | 27.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.59 | 1.83 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.70 | 0.83 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 0.83 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.64 | 2.67 | 27.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.62 | 2.33 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.64 | 3.00 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.52 | 2.50 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 20.17 | 27.60 | 15.50 | 27.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.70 | 3.00 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.57 | 0.50 | 27.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.59 | 2.67 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.48 | 1.50 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.67 | 2.67 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.73 | 7.83 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.51 | 3.00 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.61 | 3.50 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.59 | 1.50 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.17 | 27.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
Annual Sum or Average | 0.00 | 0.00 | 23.83 | 27.62 | 23.83 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.73 | 7.83 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 25.86 | 12.17 | 25.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.85 | 10.00 | 25.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.50 | 27.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.36 | 0.67 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.55 | 4.83 | 27.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 26.21 | 14.33 | 26.21 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 25.30 | 27.00 | 25.30 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 25.86 | 13.33 | 25.86 |
Annual Sum or Average | 0.00 | 0.00 | 82.83 | 25.86 | 82.83 | 25.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.55 | 27.00 | 27.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.73 | 1.50 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.75 | 0.33 | 27.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.74 | 2.50 | 27.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.69 | 1.67 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.61 | 1.17 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.72 | 3.33 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.77 | 2.33 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.74 | 3.00 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.64 | 2.67 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.52 | 0.17 | 27.52 |
Annual Sum or Average | 0.00 | 0.00 | 23.83 | 27.71 | 18.67 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.77 | 3.33 | 27.79 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.33 | 23.73 | 278.00 | 24.49 | 0.00 | 24.49 |
February | 22.67 | 23.59 | 275.83 | 24.41 | 0.00 | 24.41 |
March | 19.50 | 23.74 | 339.33 | 24.42 | 0.00 | 24.42 |
April | 0.00 | 0.00 | 407.33 | 24.39 | 0.00 | 24.39 |
May | 0.00 | 0.00 | 502.50 | 24.37 | 0.00 | 24.37 |
June | 0.00 | 0.00 | 495.17 | 24.33 | 0.00 | 24.33 |
July | 0.00 | 0.00 | 497.00 | 24.34 | 0.00 | 24.34 |
August | 0.00 | 0.00 | 512.00 | 24.33 | 0.00 | 24.33 |
September | 0.00 | 0.00 | 485.00 | 24.34 | 0.00 | 24.34 |
October | 0.00 | 0.00 | 499.33 | 24.40 | 0.00 | 24.40 |
November | 0.00 | 0.00 | 454.17 | 24.44 | 0.00 | 24.44 |
December | 23.67 | 23.60 | 293.83 | 24.46 | 0.00 | 24.46 |
Annual Sum or Average | 92.17 | 23.66 | 5039.50 | 24.39 | 0.00 | 24.39 |
Minimum of Months | 0.00 | 0.00 | 275.83 | 24.33 | 0.00 | 24.33 |
Maximum of Months | 26.33 | 23.74 | 512.00 | 24.49 | 0.00 | 24.49 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 224.17 | 23.24 | 134.83 | 23.65 | 0.00 | 23.65 |
February | 150.50 | 23.18 | 172.83 | 23.81 | 0.00 | 23.81 |
March | 136.17 | 23.28 | 223.67 | 23.92 | 0.00 | 23.92 |
April | 40.50 | 23.31 | 272.50 | 24.20 | 0.00 | 24.20 |
May | 5.83 | 23.22 | 385.33 | 24.29 | 0.00 | 24.29 |
June | 0.33 | 23.35 | 414.00 | 24.26 | 0.00 | 24.26 |
July | 0.50 | 23.30 | 423.33 | 24.27 | 0.00 | 24.27 |
August | 3.83 | 23.22 | 421.33 | 24.25 | 0.00 | 24.25 |
September | 0.00 | 0.00 | 397.17 | 24.28 | 0.00 | 24.28 |
October | 7.00 | 23.25 | 386.50 | 24.34 | 0.00 | 24.34 |
November | 42.67 | 23.32 | 300.67 | 24.27 | 0.00 | 24.27 |
December | 187.67 | 23.16 | 136.83 | 23.67 | 0.00 | 23.67 |
Annual Sum or Average | 799.17 | 23.22 | 3669.00 | 24.12 | 0.00 | 24.12 |
Minimum of Months | 0.00 | 0.00 | 134.83 | 23.65 | 0.00 | 23.65 |
Maximum of Months | 224.17 | 23.35 | 423.33 | 24.34 | 0.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 342.33 | 22.86 | 81.17 | 23.12 | 0.00 | 23.12 |
February | 228.67 | 22.87 | 135.33 | 23.39 | 0.00 | 23.39 |
March | 195.50 | 23.01 | 198.83 | 23.63 | 0.00 | 23.63 |
April | 77.67 | 23.22 | 276.67 | 24.03 | 0.00 | 24.03 |
May | 11.83 | 23.25 | 412.00 | 24.25 | 0.00 | 24.25 |
June | 0.00 | 0.00 | 441.83 | 24.27 | 0.00 | 24.27 |
July | 0.83 | 23.28 | 451.33 | 24.30 | 0.00 | 24.30 |
August | 6.33 | 22.92 | 437.50 | 24.24 | 0.00 | 24.24 |
September | 2.00 | 23.27 | 409.17 | 24.28 | 0.00 | 24.28 |
October | 26.83 | 23.20 | 369.67 | 24.28 | 0.00 | 24.28 |
November | 107.17 | 23.08 | 258.33 | 23.95 | 0.00 | 23.95 |
December | 293.67 | 22.77 | 107.83 | 23.16 | 0.00 | 23.16 |
Annual Sum or Average | 1292.83 | 22.92 | 3579.67 | 23.92 | 0.00 | 23.92 |
Minimum of Months | 0.00 | 0.00 | 81.17 | 23.12 | 0.00 | 23.12 |
Maximum of Months | 342.33 | 23.28 | 451.33 | 24.30 | 0.00 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 359.00 | 22.44 | 89.50 | 22.74 | 7.50 | 22.70 |
February | 242.67 | 22.66 | 157.00 | 23.19 | 17.17 | 23.17 |
March | 223.00 | 22.85 | 237.50 | 23.55 | 21.17 | 23.59 |
April | 86.00 | 23.49 | 324.17 | 24.14 | 8.83 | 24.18 |
May | 17.83 | 25.72 | 477.33 | 24.45 | 13.67 | 24.50 |
June | 16.50 | 26.60 | 492.00 | 24.49 | 16.50 | 24.55 |
July | 23.17 | 26.71 | 489.50 | 24.62 | 23.17 | 24.71 |
August | 21.50 | 26.17 | 490.83 | 24.47 | 20.67 | 24.54 |
September | 14.17 | 25.70 | 456.83 | 24.47 | 10.17 | 24.52 |
October | 40.83 | 24.30 | 418.83 | 24.43 | 16.50 | 24.48 |
November | 128.17 | 23.24 | 284.50 | 23.96 | 13.50 | 24.02 |
December | 305.50 | 22.43 | 143.67 | 22.96 | 11.83 | 22.94 |
Annual Sum or Average | 1478.33 | 22.96 | 4061.67 | 23.99 | 180.67 | 24.03 |
Minimum of Months | 14.17 | 22.43 | 89.50 | 22.74 | 7.50 | 22.70 |
Maximum of Months | 359.00 | 26.71 | 492.00 | 24.62 | 23.17 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 272.50 | 22.50 | 145.00 | 23.13 | 6.83 | 23.12 |
February | 194.67 | 22.80 | 206.33 | 23.52 | 14.33 | 23.53 |
March | 165.83 | 23.08 | 283.33 | 23.84 | 21.67 | 23.88 |
April | 88.33 | 24.11 | 358.50 | 24.38 | 25.50 | 24.50 |
May | 35.83 | 26.30 | 471.50 | 24.58 | 32.50 | 24.70 |
June | 35.50 | 26.72 | 491.33 | 24.60 | 35.50 | 24.73 |
July | 57.00 | 26.84 | 488.50 | 24.82 | 57.00 | 25.01 |
August | 45.67 | 26.01 | 490.00 | 24.56 | 37.33 | 24.70 |
September | 42.17 | 26.35 | 457.17 | 24.66 | 37.83 | 24.80 |
October | 53.50 | 25.05 | 429.00 | 24.57 | 31.00 | 24.68 |
November | 98.67 | 23.36 | 324.83 | 24.11 | 14.17 | 24.18 |
December | 275.50 | 22.46 | 178.33 | 23.16 | 13.33 | 23.16 |
Annual Sum or Average | 1365.17 | 23.50 | 4323.83 | 24.21 | 327.00 | 24.31 |
Minimum of Months | 35.50 | 22.46 | 145.00 | 23.13 | 6.83 | 23.12 |
Maximum of Months | 275.50 | 26.84 | 491.33 | 24.82 | 57.00 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 220.00 | 22.93 | 229.67 | 23.75 | 19.17 | 23.84 |
February | 163.83 | 23.30 | 240.33 | 23.97 | 28.50 | 24.07 |
March | 160.67 | 23.23 | 292.00 | 23.95 | 26.67 | 24.02 |
April | 85.00 | 23.81 | 340.00 | 24.29 | 15.67 | 24.37 |
May | 21.67 | 25.39 | 467.67 | 24.45 | 14.67 | 24.51 |
June | 15.50 | 26.57 | 488.50 | 24.46 | 15.50 | 24.52 |
July | 24.83 | 26.70 | 488.00 | 24.60 | 24.83 | 24.70 |
August | 26.50 | 26.30 | 490.83 | 24.50 | 25.50 | 24.59 |
September | 34.50 | 26.47 | 461.17 | 24.64 | 31.00 | 24.77 |
October | 64.50 | 25.99 | 449.17 | 24.76 | 51.50 | 24.94 |
November | 98.00 | 24.32 | 378.00 | 24.50 | 35.00 | 24.65 |
December | 205.83 | 23.10 | 243.67 | 23.88 | 30.83 | 24.02 |
Annual Sum or Average | 1120.83 | 23.79 | 4569.00 | 24.33 | 318.83 | 24.44 |
Minimum of Months | 15.50 | 22.93 | 229.67 | 23.75 | 14.67 | 23.84 |
Maximum of Months | 220.00 | 26.70 | 490.83 | 24.76 | 51.50 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 328.50 | 22.25 | 122.17 | 22.76 | 6.83 | 22.73 |
February | 241.33 | 22.65 | 172.67 | 23.30 | 24.17 | 23.34 |
March | 206.83 | 22.82 | 263.67 | 23.65 | 26.67 | 23.72 |
April | 113.33 | 23.78 | 331.83 | 24.26 | 26.50 | 24.39 |
May | 38.50 | 25.14 | 443.83 | 24.50 | 22.83 | 24.60 |
June | 23.50 | 26.28 | 468.83 | 24.50 | 20.83 | 24.59 |
July | 34.33 | 26.29 | 471.50 | 24.63 | 29.50 | 24.75 |
August | 37.33 | 25.44 | 476.67 | 24.48 | 25.83 | 24.58 |
September | 39.17 | 25.39 | 435.67 | 24.54 | 24.67 | 24.65 |
October | 73.17 | 24.54 | 408.33 | 24.50 | 33.67 | 24.63 |
November | 140.33 | 23.09 | 290.67 | 23.94 | 16.17 | 24.01 |
December | 288.17 | 22.32 | 163.83 | 23.02 | 15.67 | 23.04 |
Annual Sum or Average | 1564.50 | 23.07 | 4049.67 | 24.03 | 273.33 | 24.12 |
Minimum of Months | 23.50 | 22.25 | 122.17 | 22.76 | 6.83 | 22.73 |
Maximum of Months | 328.50 | 26.29 | 476.67 | 24.63 | 33.67 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 269.33 | 23.02 | 126.33 | 23.41 | 0.00 | 23.41 |
February | 192.67 | 23.04 | 168.50 | 23.59 | 1.00 | 23.60 |
March | 208.00 | 23.10 | 222.33 | 23.70 | 11.50 | 23.73 |
April | 60.50 | 23.51 | 305.17 | 24.15 | 3.50 | 24.17 |
May | 2.33 | 25.94 | 479.33 | 24.37 | 2.33 | 24.38 |
June | 7.83 | 26.33 | 495.50 | 24.39 | 7.83 | 24.42 |
July | 0.00 | 0.00 | 496.33 | 24.45 | 0.00 | 24.45 |
August | 0.67 | 26.48 | 514.00 | 24.37 | 0.67 | 24.37 |
September | 0.00 | 0.00 | 484.17 | 24.40 | 0.00 | 24.40 |
October | 0.00 | 0.00 | 474.67 | 24.41 | 0.00 | 24.41 |
November | 37.17 | 23.57 | 373.33 | 24.25 | 3.83 | 24.27 |
December | 213.50 | 23.01 | 178.83 | 23.61 | 0.00 | 23.61 |
Annual Sum or Average | 992.00 | 23.12 | 4318.50 | 24.13 | 30.67 | 24.14 |
Minimum of Months | 0.00 | 0.00 | 126.33 | 23.41 | 0.00 | 23.41 |
Maximum of Months | 269.33 | 26.48 | 514.00 | 24.45 | 11.50 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 148.50 | 23.19 | 223.67 | 23.93 | 1.67 | 23.95 |
February | 103.50 | 23.26 | 244.83 | 24.02 | 2.83 | 24.03 |
March | 98.00 | 23.49 | 304.33 | 24.14 | 13.50 | 24.18 |
April | 28.67 | 24.42 | 388.00 | 24.44 | 9.17 | 24.49 |
May | 8.67 | 26.79 | 492.67 | 24.49 | 8.67 | 24.53 |
June | 20.33 | 26.71 | 496.00 | 24.53 | 20.33 | 24.61 |
July | 33.33 | 26.89 | 497.00 | 24.73 | 33.33 | 24.86 |
August | 18.83 | 26.81 | 514.00 | 24.53 | 18.83 | 24.61 |
September | 23.50 | 26.84 | 485.00 | 24.63 | 23.50 | 24.73 |
October | 10.00 | 26.88 | 494.17 | 24.56 | 10.00 | 24.61 |
November | 21.17 | 24.40 | 428.83 | 24.40 | 6.83 | 24.44 |
December | 154.33 | 23.07 | 228.00 | 23.88 | 0.00 | 23.88 |
Annual Sum or Average | 668.83 | 23.93 | 4796.50 | 24.39 | 148.67 | 24.45 |
Minimum of Months | 8.67 | 23.07 | 223.67 | 23.88 | 0.00 | 23.88 |
Maximum of Months | 154.33 | 26.89 | 514.00 | 24.73 | 33.33 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 136.00 | 23.19 | 318.00 | 24.17 | 31.83 | 24.22 |
February | 93.33 | 23.25 | 310.50 | 24.24 | 28.00 | 24.29 |
March | 150.17 | 23.07 | 331.67 | 23.93 | 48.17 | 23.93 |
April | 68.00 | 23.62 | 371.67 | 24.24 | 35.00 | 24.24 |
May | 92.83 | 24.26 | 492.33 | 24.38 | 92.83 | 24.37 |
June | 135.67 | 24.41 | 495.83 | 24.41 | 135.67 | 24.41 |
July | 109.33 | 24.54 | 496.67 | 24.55 | 109.33 | 24.55 |
August | 124.67 | 24.57 | 514.00 | 24.55 | 124.67 | 24.55 |
September | 120.83 | 24.95 | 485.00 | 24.74 | 120.83 | 24.78 |
October | 107.83 | 25.28 | 500.00 | 24.88 | 107.83 | 24.94 |
November | 93.50 | 24.58 | 458.00 | 24.67 | 83.50 | 24.69 |
December | 140.50 | 23.39 | 316.17 | 24.24 | 36.33 | 24.33 |
Annual Sum or Average | 1372.67 | 24.06 | 5089.83 | 24.45 | 954.00 | 24.48 |
Minimum of Months | 68.00 | 23.07 | 310.50 | 23.93 | 28.00 | 23.93 |
Maximum of Months | 150.17 | 25.28 | 514.00 | 24.88 | 135.67 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 191.00 | 23.09 | 191.17 | 23.72 | 0.00 | 23.72 |
February | 130.00 | 23.23 | 231.17 | 23.98 | 6.50 | 24.03 |
March | 123.33 | 23.32 | 304.67 | 24.08 | 14.00 | 24.12 |
April | 32.83 | 24.71 | 385.83 | 24.46 | 13.33 | 24.53 |
May | 9.33 | 26.73 | 485.67 | 24.50 | 9.33 | 24.54 |
June | 15.00 | 26.62 | 494.33 | 24.47 | 15.00 | 24.53 |
July | 14.50 | 26.86 | 495.00 | 24.59 | 14.50 | 24.66 |
August | 13.50 | 26.78 | 514.00 | 24.51 | 13.50 | 24.56 |
September | 14.50 | 26.86 | 483.00 | 24.57 | 14.50 | 24.63 |
October | 12.67 | 26.84 | 491.17 | 24.58 | 12.67 | 24.63 |
November | 28.67 | 23.95 | 412.67 | 24.37 | 6.33 | 24.40 |
December | 163.33 | 23.09 | 248.33 | 23.91 | 0.33 | 23.91 |
Annual Sum or Average | 748.67 | 23.65 | 4737.00 | 24.34 | 120.00 | 24.39 |
Minimum of Months | 9.33 | 23.09 | 191.17 | 23.72 | 0.00 | 23.72 |
Maximum of Months | 191.00 | 26.86 | 514.00 | 24.59 | 15.00 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 302.33 | 22.88 | 113.00 | 23.25 | 0.00 | 23.25 |
February | 192.83 | 22.99 | 183.83 | 23.58 | 7.67 | 23.60 |
March | 181.67 | 23.18 | 254.50 | 23.82 | 16.67 | 23.87 |
April | 39.50 | 23.90 | 352.00 | 24.26 | 7.17 | 24.30 |
May | 3.50 | 26.27 | 488.67 | 24.40 | 3.50 | 24.42 |
June | 8.50 | 26.48 | 494.67 | 24.43 | 8.50 | 24.46 |
July | 0.83 | 26.80 | 494.83 | 24.48 | 0.83 | 24.48 |
August | 9.17 | 26.03 | 500.33 | 24.40 | 9.17 | 24.43 |
September | 0.33 | 26.36 | 473.17 | 24.40 | 0.33 | 24.41 |
October | 10.00 | 25.47 | 444.00 | 24.45 | 7.00 | 24.48 |
November | 74.83 | 23.66 | 323.00 | 24.19 | 11.50 | 24.25 |
December | 243.50 | 22.79 | 162.17 | 23.39 | 1.00 | 23.39 |
Annual Sum or Average | 1067.00 | 23.12 | 4284.17 | 24.12 | 73.33 | 24.14 |
Minimum of Months | 0.33 | 22.79 | 113.00 | 23.25 | 0.00 | 23.25 |
Maximum of Months | 302.33 | 26.80 | 500.33 | 24.48 | 16.67 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 214.50 | 22.86 | 128.50 | 23.52 | 2.83 | 23.55 |
February | 146.33 | 23.08 | 173.33 | 23.79 | 9.83 | 23.83 |
March | 127.50 | 23.35 | 232.50 | 24.04 | 18.17 | 24.11 |
April | 54.00 | 24.50 | 303.50 | 24.54 | 19.50 | 24.65 |
May | 15.67 | 26.79 | 396.33 | 24.62 | 15.67 | 24.70 |
June | 23.50 | 26.75 | 414.67 | 24.63 | 23.50 | 24.74 |
July | 36.67 | 26.90 | 417.33 | 24.84 | 36.67 | 25.00 |
August | 26.00 | 26.63 | 415.17 | 24.63 | 26.00 | 24.74 |
September | 22.00 | 26.83 | 392.67 | 24.70 | 22.00 | 24.80 |
October | 22.17 | 26.02 | 366.50 | 24.69 | 17.83 | 24.78 |
November | 61.00 | 23.82 | 285.50 | 24.35 | 13.00 | 24.42 |
December | 205.00 | 22.73 | 150.33 | 23.48 | 2.83 | 23.51 |
Annual Sum or Average | 954.33 | 23.67 | 3676.33 | 24.36 | 207.83 | 24.45 |
Minimum of Months | 15.67 | 22.73 | 128.50 | 23.48 | 2.83 | 23.51 |
Maximum of Months | 214.50 | 26.90 | 417.33 | 24.84 | 36.67 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 160.67 | 23.42 | 262.50 | 24.17 | 16.17 | 24.27 |
February | 107.83 | 23.63 | 269.17 | 24.28 | 19.00 | 24.38 |
March | 108.00 | 23.53 | 315.50 | 24.16 | 20.00 | 24.23 |
April | 33.00 | 24.14 | 369.17 | 24.38 | 8.17 | 24.42 |
May | 3.33 | 26.15 | 482.33 | 24.40 | 3.33 | 24.42 |
June | 8.67 | 26.44 | 492.17 | 24.40 | 8.67 | 24.44 |
July | 1.67 | 26.92 | 493.33 | 24.46 | 1.67 | 24.47 |
August | 13.83 | 26.30 | 501.17 | 24.44 | 13.83 | 24.49 |
September | 22.00 | 26.86 | 475.83 | 24.60 | 22.00 | 24.69 |
October | 41.17 | 26.74 | 469.00 | 24.78 | 39.83 | 24.93 |
November | 57.33 | 25.18 | 405.83 | 24.67 | 32.17 | 24.81 |
December | 164.33 | 23.56 | 281.33 | 24.22 | 24.17 | 24.36 |
Annual Sum or Average | 721.83 | 24.08 | 4817.33 | 24.43 | 209.00 | 24.51 |
Minimum of Months | 1.67 | 23.42 | 262.50 | 24.16 | 1.67 | 24.23 |
Maximum of Months | 164.33 | 26.92 | 501.17 | 24.78 | 39.83 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 270.33 | 22.74 | 150.17 | 23.32 | 0.00 | 23.32 |
February | 179.67 | 23.01 | 201.33 | 23.73 | 15.00 | 23.81 |
March | 149.83 | 23.14 | 293.17 | 23.95 | 19.50 | 24.01 |
April | 60.83 | 24.40 | 366.50 | 24.43 | 21.33 | 24.53 |
May | 13.50 | 26.72 | 471.67 | 24.50 | 13.50 | 24.56 |
June | 17.00 | 26.64 | 485.50 | 24.47 | 17.00 | 24.54 |
July | 20.17 | 26.79 | 487.83 | 24.58 | 20.17 | 24.67 |
August | 20.83 | 26.55 | 492.33 | 24.50 | 20.83 | 24.58 |
September | 16.50 | 26.82 | 457.83 | 24.54 | 16.50 | 24.62 |
October | 32.00 | 25.55 | 440.67 | 24.57 | 21.83 | 24.66 |
November | 79.50 | 23.51 | 333.83 | 24.22 | 12.33 | 24.27 |
December | 225.83 | 22.70 | 195.67 | 23.50 | 4.33 | 23.53 |
Annual Sum or Average | 1086.00 | 23.39 | 4376.50 | 24.22 | 182.33 | 24.29 |
Minimum of Months | 13.50 | 22.70 | 150.17 | 23.32 | 0.00 | 23.32 |
Maximum of Months | 270.33 | 26.82 | 492.33 | 24.58 | 21.83 | 24.67 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.29882 | 40.98892 | 0.45458 | 9.62999 |
February | 454.00000 | 24.29504 | 41.90300 | 0.46203 | 9.81403 |
March | 514.00000 | 24.29460 | 42.57696 | 0.47189 | 9.95143 |
April | 485.00000 | 24.32270 | 45.71445 | 0.50700 | 10.58902 |
May | 508.00000 | 24.36029 | 47.69661 | -0.3132 | 7.49341 |
June | 496.00000 | 24.32709 | 48.14290 | -0.3129 | 7.46294 |
July | 497.00000 | 24.33958 | 47.98470 | -0.3093 | 7.39855 |
August | 514.00000 | 24.32380 | 48.12996 | -0.3125 | 7.44168 |
September | 485.00000 | 24.34245 | 47.89989 | -0.3084 | 7.41324 |
October | 502.00000 | 24.39739 | 47.33681 | 0.55022 | 11.60846 |
November | 489.00000 | 24.41135 | 46.26068 | 0.53480 | 11.27164 |
December | 497.00000 | 24.28237 | 42.74394 | 0.46325 | 9.76955 |
Annual Sum or Average | 5943.00000 | 24.33307 | 45.63556 | 0.15417 | 9.14371 |
Minimum of Months | 454.00000 | 24.28237 | 40.98892 | -0.3132 | 7.39855 |
Maximum of Months | 514.00000 | 24.41135 | 48.14290 | 0.55022 | 11.60846 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.75424 | 43.29883 | 0.31891 | 7.61273 |
February | 454.00000 | 23.82315 | 44.49106 | 0.34953 | 8.14496 |
March | 514.00000 | 23.91080 | 44.52627 | 0.37737 | 8.37694 |
April | 485.00000 | 24.03762 | 47.29481 | 0.43751 | 9.20934 |
May | 508.00000 | 24.15212 | 48.37691 | -0.3960 | 8.63379 |
June | 496.00000 | 24.17051 | 48.76067 | -0.3805 | 8.36723 |
July | 497.00000 | 24.18314 | 48.58488 | -0.3752 | 8.27987 |
August | 514.00000 | 24.15654 | 48.78424 | -0.3854 | 8.42897 |
September | 485.00000 | 24.17377 | 48.57762 | -0.3809 | 8.39742 |
October | 502.00000 | 24.20127 | 47.86594 | 0.49076 | 10.28374 |
November | 489.00000 | 24.11251 | 47.34646 | 0.45152 | 9.52978 |
December | 497.00000 | 23.74275 | 44.92933 | 0.32965 | 7.77225 |
Annual Sum or Average | 5943.00000 | 24.03610 | 46.91454 | 0.06674 | 8.58715 |
Minimum of Months | 454.00000 | 23.74275 | 43.29883 | -0.3960 | 7.61273 |
Maximum of Months | 514.00000 | 24.20127 | 48.78424 | 0.49076 | 10.28374 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.24495 | 43.41796 | 0.19326 | 6.76944 |
February | 454.00000 | 23.48746 | 43.96698 | 0.26521 | 7.58713 |
March | 514.00000 | 23.68477 | 44.33536 | 0.32515 | 7.99795 |
April | 485.00000 | 23.96893 | 47.02861 | 0.42821 | 9.11676 |
May | 508.00000 | 24.15178 | 48.81866 | -0.3738 | 8.31357 |
June | 496.00000 | 24.20995 | 49.07988 | -0.3444 | 7.84850 |
July | 497.00000 | 24.24691 | 48.77031 | -0.3296 | 7.66041 |
August | 514.00000 | 24.16274 | 49.27035 | -0.3619 | 8.12273 |
September | 485.00000 | 24.18217 | 49.01428 | -0.3586 | 8.08421 |
October | 502.00000 | 24.14561 | 48.60149 | 0.48868 | 10.29270 |
November | 489.00000 | 23.90454 | 48.01653 | 0.40706 | 8.89395 |
December | 497.00000 | 23.29394 | 45.18093 | 0.22095 | 7.07189 |
Annual Sum or Average | 5943.00000 | 23.89275 | 47.14223 | 0.04408 | 8.14832 |
Minimum of Months | 454.00000 | 23.24495 | 43.41796 | -0.3738 | 6.76944 |
Maximum of Months | 514.00000 | 24.24691 | 49.27035 | 0.48868 | 10.29270 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.90990 | 46.14211 | 0.11655 | 7.17049 |
February | 454.00000 | 23.30854 | 46.39582 | 0.23196 | 8.08589 |
March | 514.00000 | 23.56386 | 46.98776 | 0.31101 | 8.77501 |
April | 485.00000 | 24.05881 | 48.55532 | 0.46784 | 10.15964 |
May | 508.00000 | 24.35878 | 50.11635 | -0.2607 | 7.31986 |
June | 496.00000 | 24.41139 | 49.92394 | -0.2209 | 6.90109 |
July | 497.00000 | 24.50621 | 49.05371 | -0.1885 | 6.86228 |
August | 514.00000 | 24.35721 | 50.14157 | -0.2518 | 7.20165 |
September | 485.00000 | 24.38677 | 49.81326 | -0.2530 | 7.27134 |
October | 502.00000 | 24.30149 | 50.23681 | 0.54652 | 11.83952 |
November | 489.00000 | 23.88681 | 50.06918 | 0.41702 | 9.53148 |
December | 497.00000 | 23.07168 | 48.30306 | 0.17637 | 7.69178 |
Annual Sum or Average | 5943.00000 | 23.93049 | 48.82562 | 0.08896 | 8.23082 |
Minimum of Months | 454.00000 | 22.90990 | 46.14211 | -0.2607 | 6.86228 |
Maximum of Months | 514.00000 | 24.50621 | 50.23681 | 0.54652 | 11.83952 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.28594 | 45.01021 | 0.22620 | 8.26742 |
February | 454.00000 | 23.56455 | 45.44846 | 0.32032 | 8.94850 |
March | 514.00000 | 23.80455 | 45.95893 | 0.40264 | 9.88561 |
April | 485.00000 | 24.18191 | 47.76482 | 0.54031 | 12.12283 |
May | 508.00000 | 24.38255 | 49.75643 | -0.2007 | 7.11893 |
June | 496.00000 | 24.43695 | 49.66782 | -0.1657 | 6.78614 |
July | 497.00000 | 24.57035 | 48.65328 | -0.1166 | 7.10217 |
August | 514.00000 | 24.38145 | 49.83581 | -0.1955 | 7.09248 |
September | 485.00000 | 24.44568 | 49.30454 | -0.1807 | 7.17181 |
October | 502.00000 | 24.35818 | 49.69610 | 0.59633 | 13.29155 |
November | 489.00000 | 23.99688 | 49.46434 | 0.46969 | 10.55372 |
December | 497.00000 | 23.22315 | 47.75421 | 0.23113 | 8.41123 |
Annual Sum or Average | 5943.00000 | 24.05562 | 48.20922 | 0.15845 | 8.88829 |
Minimum of Months | 454.00000 | 23.22315 | 45.01021 | -0.2007 | 6.78614 |
Maximum of Months | 514.00000 | 24.57035 | 49.83581 | 0.59633 | 13.29155 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.70074 | 43.06255 | 0.34691 | 10.12459 |
February | 454.00000 | 23.87094 | 44.15087 | 0.40689 | 10.66603 |
March | 514.00000 | 23.87467 | 45.50128 | 0.41657 | 10.32752 |
April | 485.00000 | 24.15495 | 48.01508 | 0.50600 | 11.17003 |
May | 508.00000 | 24.34433 | 50.18623 | -0.2664 | 7.43681 |
June | 496.00000 | 24.38283 | 50.12376 | -0.2397 | 7.03734 |
July | 497.00000 | 24.48241 | 49.18679 | -0.2014 | 6.96286 |
August | 514.00000 | 24.37074 | 49.98626 | -0.2346 | 7.14088 |
September | 485.00000 | 24.46230 | 49.24765 | -0.1901 | 7.20298 |
October | 502.00000 | 24.48750 | 48.99905 | 0.63601 | 14.49514 |
November | 489.00000 | 24.28211 | 48.05567 | 0.55724 | 12.84175 |
December | 497.00000 | 23.74912 | 45.43615 | 0.38052 | 10.83275 |
Annual Sum or Average | 5943.00000 | 24.18160 | 47.68555 | 0.17369 | 9.67249 |
Minimum of Months | 454.00000 | 23.70074 | 43.06255 | -0.2664 | 6.96286 |
Maximum of Months | 514.00000 | 24.48750 | 50.18623 | 0.63601 | 14.49514 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.91109 | 45.55420 | 0.14336 | 7.68977 |
February | 454.00000 | 23.33326 | 45.82226 | 0.26980 | 9.04785 |
March | 514.00000 | 23.60295 | 46.28754 | 0.35957 | 9.90024 |
April | 485.00000 | 24.06606 | 48.15382 | 0.51282 | 11.67904 |
May | 508.00000 | 24.31303 | 50.03878 | -0.2267 | 7.51875 |
June | 496.00000 | 24.35651 | 50.09910 | -0.2083 | 7.08170 |
July | 497.00000 | 24.45882 | 49.14748 | -0.1639 | 7.09448 |
August | 514.00000 | 24.33336 | 50.05423 | -0.2125 | 7.22552 |
September | 485.00000 | 24.35538 | 49.76367 | -0.2222 | 7.54856 |
October | 502.00000 | 24.27676 | 50.01667 | 0.57464 | 12.83790 |
November | 489.00000 | 23.83567 | 49.80266 | 0.43434 | 10.19486 |
December | 497.00000 | 23.09277 | 47.63034 | 0.20945 | 8.54086 |
Annual Sum or Average | 5943.00000 | 23.91484 | 48.54627 | 0.12047 | 8.85558 |
Minimum of Months | 454.00000 | 22.91109 | 45.55420 | -0.2267 | 7.08170 |
Maximum of Months | 514.00000 | 24.45882 | 50.09910 | 0.57464 | 12.83790 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.50676 | 44.90430 | 0.26370 | 7.31460 |
February | 454.00000 | 23.64344 | 45.59013 | 0.30878 | 7.96034 |
March | 514.00000 | 23.70033 | 46.56904 | 0.33251 | 8.27095 |
April | 485.00000 | 24.05944 | 48.34686 | 0.44826 | 9.49846 |
May | 508.00000 | 24.33160 | 49.55817 | -0.3028 | 7.47451 |
June | 496.00000 | 24.35779 | 49.48059 | -0.2688 | 7.02201 |
July | 497.00000 | 24.44512 | 48.65004 | -0.2337 | 6.73442 |
August | 514.00000 | 24.36781 | 49.26944 | -0.2633 | 6.99399 |
September | 485.00000 | 24.40193 | 48.89919 | -0.2591 | 6.98382 |
October | 502.00000 | 24.37860 | 49.00593 | 0.55901 | 11.87597 |
November | 489.00000 | 24.17234 | 48.68460 | 0.48288 | 10.23960 |
December | 497.00000 | 23.66467 | 46.64062 | 0.31965 | 8.02078 |
Annual Sum or Average | 5943.00000 | 24.08819 | 47.98087 | 0.11311 | 8.19589 |
Minimum of Months | 454.00000 | 23.50676 | 44.90430 | -0.3028 | 6.73442 |
Maximum of Months | 514.00000 | 24.44512 | 49.55817 | 0.55901 | 11.87597 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.93438 | 43.74140 | 0.38595 | 9.06139 |
February | 454.00000 | 23.99288 | 44.55108 | 0.41732 | 9.41909 |
March | 514.00000 | 24.04897 | 45.33340 | 0.44771 | 9.95815 |
April | 485.00000 | 24.30333 | 47.25955 | 0.54585 | 11.81100 |
May | 508.00000 | 24.42433 | 49.10066 | -0.2214 | 6.94422 |
June | 496.00000 | 24.44286 | 49.12111 | -0.1949 | 6.68628 |
July | 497.00000 | 24.58427 | 48.12873 | -0.1398 | 6.70789 |
August | 514.00000 | 24.44909 | 48.89458 | -0.1887 | 6.66171 |
September | 485.00000 | 24.52401 | 48.34426 | -0.1663 | 6.69203 |
October | 502.00000 | 24.50747 | 48.41458 | 0.62529 | 13.75959 |
November | 489.00000 | 24.32415 | 48.13948 | 0.54580 | 11.66812 |
December | 497.00000 | 23.89237 | 46.11989 | 0.39060 | 9.16321 |
Annual Sum or Average | 5943.00000 | 24.28714 | 47.27890 | 0.20136 | 9.03360 |
Minimum of Months | 454.00000 | 23.89237 | 43.74140 | -0.2214 | 6.66171 |
Maximum of Months | 514.00000 | 24.58427 | 49.12111 | 0.62529 | 13.75959 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.08220 | 44.77959 | 0.47968 | 11.52654 |
February | 454.00000 | 24.14546 | 46.45588 | 0.49954 | 11.58915 |
March | 514.00000 | 23.91584 | 48.60521 | 0.44905 | 10.71638 |
April | 485.00000 | 24.17366 | 52.01737 | 0.52144 | 11.20070 |
May | 508.00000 | 24.38715 | 56.45586 | -0.2404 | 6.81173 |
June | 496.00000 | 24.41050 | 58.85033 | -0.2004 | 6.33957 |
July | 497.00000 | 24.55835 | 56.84978 | -0.1513 | 6.18249 |
August | 514.00000 | 24.54500 | 57.90858 | -0.1361 | 6.18585 |
September | 485.00000 | 24.69359 | 55.93609 | -0.0769 | 6.25731 |
October | 502.00000 | 24.79419 | 53.93909 | 0.74563 | 17.44688 |
November | 489.00000 | 24.59548 | 52.43076 | 0.67559 | 15.46975 |
December | 497.00000 | 24.09926 | 47.12529 | 0.50336 | 12.08836 |
Annual Sum or Average | 5943.00000 | 24.36712 | 52.65638 | 0.25277 | 10.13144 |
Minimum of Months | 454.00000 | 23.91584 | 44.77959 | -0.2404 | 6.18249 |
Maximum of Months | 514.00000 | 24.79419 | 58.85033 | 0.74563 | 17.44688 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.76500 | 44.15014 | 0.34289 | 8.33298 |
February | 454.00000 | 23.92635 | 44.70719 | 0.39895 | 9.43510 |
March | 514.00000 | 24.01489 | 45.43457 | 0.43750 | 9.97711 |
April | 485.00000 | 24.29512 | 47.39713 | 0.54040 | 11.68477 |
May | 508.00000 | 24.42316 | 49.22952 | -0.2280 | 7.04892 |
June | 496.00000 | 24.40406 | 49.48234 | -0.2271 | 6.86247 |
July | 497.00000 | 24.52523 | 48.47642 | -0.1717 | 6.61999 |
August | 514.00000 | 24.44644 | 49.00133 | -0.1929 | 6.66131 |
September | 485.00000 | 24.49867 | 48.63526 | -0.1902 | 6.81201 |
October | 502.00000 | 24.50111 | 48.55513 | 0.61868 | 13.59463 |
November | 489.00000 | 24.29267 | 48.24574 | 0.53557 | 11.46769 |
December | 497.00000 | 23.90252 | 45.87110 | 0.39718 | 9.36953 |
Annual Sum or Average | 5943.00000 | 24.25128 | 47.44836 | 0.18593 | 8.97752 |
Minimum of Months | 454.00000 | 23.76500 | 44.15014 | -0.2280 | 6.61999 |
Maximum of Months | 514.00000 | 24.52523 | 49.48234 | 0.61868 | 13.59463 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.36138 | 45.90914 | 0.22896 | 7.21478 |
February | 454.00000 | 23.60658 | 46.76496 | 0.30734 | 8.17958 |
March | 514.00000 | 23.78349 | 47.03909 | 0.36104 | 8.78788 |
April | 485.00000 | 24.14773 | 48.56436 | 0.47980 | 10.13508 |
May | 508.00000 | 24.37126 | 49.46315 | -0.2817 | 7.34378 |
June | 496.00000 | 24.39220 | 49.40223 | -0.2539 | 7.02258 |
July | 497.00000 | 24.47286 | 48.62939 | -0.2283 | 6.85263 |
August | 514.00000 | 24.35961 | 49.47159 | -0.2750 | 7.22555 |
September | 485.00000 | 24.38790 | 49.19726 | -0.2748 | 7.23680 |
October | 502.00000 | 24.35031 | 49.30241 | 0.54524 | 11.63477 |
November | 489.00000 | 24.08055 | 49.24724 | 0.45648 | 9.83362 |
December | 497.00000 | 23.46861 | 47.94969 | 0.27314 | 7.77637 |
Annual Sum or Average | 5943.00000 | 24.06788 | 48.42013 | 0.10908 | 8.26609 |
Minimum of Months | 454.00000 | 23.36138 | 45.90914 | -0.2817 | 6.85263 |
Maximum of Months | 514.00000 | 24.47286 | 49.47159 | 0.54524 | 11.63477 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.57719 | 44.54015 | 0.29276 | 8.37651 |
February | 385.00000 | 23.77215 | 45.62708 | 0.36285 | 9.00913 |
March | 433.00000 | 23.93373 | 46.05421 | 0.41979 | 9.83495 |
April | 410.00000 | 24.29499 | 47.53156 | 0.53929 | 11.94089 |
May | 430.00000 | 24.46692 | 48.93480 | -0.2227 | 7.27523 |
June | 418.00000 | 24.50465 | 48.99602 | -0.1947 | 6.99443 |
July | 422.00000 | 24.65117 | 47.96337 | -0.1456 | 7.18482 |
August | 433.00000 | 24.46640 | 48.96860 | -0.2163 | 7.19504 |
September | 410.00000 | 24.53760 | 48.52950 | -0.1987 | 7.26310 |
October | 427.00000 | 24.47139 | 48.61121 | 0.59241 | 13.12158 |
November | 417.00000 | 24.17314 | 48.43057 | 0.49227 | 10.76308 |
December | 422.00000 | 23.52000 | 47.29011 | 0.29693 | 8.48138 |
Annual Sum or Average | 5034.00000 | 24.19940 | 47.63345 | 0.16636 | 8.94859 |
Minimum of Months | 385.00000 | 23.52000 | 44.54015 | -0.2227 | 6.99443 |
Maximum of Months | 433.00000 | 24.65117 | 48.99602 | 0.59241 | 13.12158 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.03518 | 42.97029 | 0.43251 | 10.59200 |
February | 454.00000 | 24.11656 | 44.52859 | 0.46837 | 11.01109 |
March | 514.00000 | 24.05333 | 45.53206 | 0.45562 | 10.37139 |
April | 485.00000 | 24.24182 | 47.99013 | 0.51588 | 11.04941 |
May | 508.00000 | 24.36268 | 49.51828 | -0.2854 | 7.41315 |
June | 496.00000 | 24.36521 | 49.59748 | -0.2714 | 7.16147 |
July | 497.00000 | 24.45147 | 48.75236 | -0.2401 | 6.94773 |
August | 514.00000 | 24.37833 | 49.28871 | -0.2572 | 7.13398 |
September | 485.00000 | 24.47927 | 48.58082 | -0.2101 | 7.07192 |
October | 502.00000 | 24.56101 | 47.99349 | 0.63641 | 14.32391 |
November | 489.00000 | 24.45255 | 47.27370 | 0.58884 | 13.21829 |
December | 497.00000 | 24.04836 | 45.19037 | 0.45447 | 11.17673 |
Annual Sum or Average | 5943.00000 | 24.29596 | 47.28531 | 0.18751 | 9.77335 |
Minimum of Months | 454.00000 | 24.03518 | 42.97029 | -0.2854 | 6.94773 |
Maximum of Months | 514.00000 | 24.56101 | 49.59748 | 0.63641 | 14.32391 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.40286 | 45.37046 | 0.26221 | 7.82641 |
February | 454.00000 | 23.68982 | 46.18142 | 0.35484 | 9.24387 |
March | 514.00000 | 23.87124 | 46.32562 | 0.41701 | 9.98109 |
April | 485.00000 | 24.22409 | 48.08251 | 0.53597 | 11.74773 |
May | 508.00000 | 24.37892 | 49.29120 | -0.2350 | 7.23052 |
June | 496.00000 | 24.38136 | 49.50729 | -0.2302 | 7.01125 |
July | 497.00000 | 24.47770 | 48.61094 | -0.1910 | 6.89268 |
August | 514.00000 | 24.37789 | 49.29683 | -0.2262 | 7.04418 |
September | 485.00000 | 24.41278 | 49.06873 | -0.2306 | 7.25197 |
October | 502.00000 | 24.38608 | 48.99988 | 0.58325 | 12.78871 |
November | 489.00000 | 24.08969 | 48.95877 | 0.48412 | 10.59533 |
December | 497.00000 | 23.52559 | 47.33333 | 0.31177 | 8.68832 |
Annual Sum or Average | 5943.00000 | 24.10387 | 48.09511 | 0.15058 | 8.84855 |
Minimum of Months | 454.00000 | 23.40286 | 45.37046 | -0.2350 | 6.89268 |
Maximum of Months | 514.00000 | 24.47770 | 49.50729 | 0.58325 | 12.78871 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.479696E+11 | 0.116073E+11 | 414.28 | 0.349097E+11 | 0.130599E+11 | 0.00 | 1.00 | 01-JAN-09:13 | 0.00 | 01-JAN-00:10 | 87913.89 | 14-JAN-06:03 | 56695.81 | 14-JAN-06:03 | 31218.08 | 14-JAN-06:03 | 21135.67 | 02-JAN-14:00 | 0.00 |
February | 0.487341E+11 | 0.117413E+11 | 377.35 | 0.359025E+11 | 0.128317E+11 | 0.00 | 1.00 | 01-FEB-11:10 | 0.00 | 01-FEB-00:10 | 83166.65 | 11-FEB-06:03 | 51131.25 | 11-FEB-06:03 | 32035.40 | 11-FEB-06:03 | 19109.41 | 11-FEB-06:03 | 0.00 |
March | 0.588131E+11 | 0.141378E+11 | 438.32 | 0.422058E+11 | 0.166073E+11 | 0.00 | 1.00 | 01-MAR-14:30 | 0.00 | 01-MAR-00:10 | 88467.27 | 06-MAR-05:03 | 51753.25 | 27-MAR-15:40 | 38786.49 | 06-MAR-05:03 | 20215.24 | 06-MAR-05:03 | 0.00 |
April | 0.666427E+11 | 0.162491E+11 | 426.69 | 0.470632E+11 | 0.195795E+11 | 0.00 | 1.00 | 01-APR-05:03 | 0.00 | 01-APR-00:10 | 78585.82 | 14-APR-15:10 | 56842.10 | 17-APR-15:20 | 26681.17 | 13-APR-12:02 | 20608.83 | 14-APR-15:10 | 0.00 |
May | 0.889511E+11 | 0.221134E+11 | 449.07 | 0.589121E+11 | 0.300390E+11 | 0.00 | 1.00 | 01-MAY-04:03 | 0.00 | 01-MAY-00:10 | 110925.80 | 30-MAY-04:02 | 77074.67 | 30-MAY-04:02 | 36769.58 | 31-MAY-04:03 | 26152.39 | 30-MAY-04:02 | 0.00 |
June | 0.100187E+12 | 0.249298E+11 | 446.57 | 0.620427E+11 | 0.381447E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 117927.07 | 19-JUN-04:02 | 76514.90 | 12-JUN-04:02 | 44254.69 | 19-JUN-04:02 | 27197.78 | 19-JUN-04:02 | 0.00 |
July | 0.105454E+12 | 0.268207E+11 | 455.68 | 0.654616E+11 | 0.399924E+11 | 0.00 | 1.00 | 01-JUL-04:03 | 0.00 | 01-JUL-00:10 | 111642.14 | 03-JUL-04:02 | 77837.20 | 31-JUL-04:02 | 36747.65 | 12-JUL-12:02 | 26529.55 | 31-JUL-04:02 | 0.00 |
August | 0.109838E+12 | 0.276815E+11 | 467.10 | 0.678799E+11 | 0.419585E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 110763.36 | 28-AUG-04:02 | 78481.01 | 21-AUG-04:02 | 40241.72 | 21-AUG-12:03 | 27323.72 | 01-AUG-04:03 | 0.00 |
September | 0.100788E+12 | 0.251778E+11 | 447.67 | 0.627117E+11 | 0.380767E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 112632.64 | 19-SEP-04:03 | 78815.30 | 11-SEP-04:02 | 38463.12 | 22-SEP-07:10 | 27612.91 | 22-SEP-04:03 | 0.00 |
October | 0.928167E+11 | 0.229034E+11 | 446.44 | 0.604983E+11 | 0.323184E+11 | 0.00 | 1.00 | 01-OCT-10:13 | 0.00 | 01-OCT-00:10 | 116944.58 | 02-OCT-06:03 | 78437.53 | 02-OCT-06:03 | 41488.59 | 04-OCT-07:10 | 28274.15 | 02-OCT-06:03 | 0.00 |
November | 0.737577E+11 | 0.177689E+11 | 413.36 | 0.488432E+11 | 0.249145E+11 | 0.00 | 1.00 | 01-NOV-04:03 | 0.00 | 01-NOV-00:10 | 99839.91 | 04-NOV-05:03 | 65487.36 | 04-NOV-05:03 | 36492.79 | 30-NOV-06:03 | 23417.27 | 04-NOV-05:03 | 0.00 |
December | 0.511897E+11 | 0.123336E+11 | 412.54 | 0.359346E+11 | 0.152551E+11 | 0.00 | 1.00 | 01-DEC-05:03 | 0.00 | 01-DEC-00:10 | 92349.73 | 26-DEC-05:03 | 57835.51 | 11-DEC-05:03 | 35299.57 | 26-DEC-05:03 | 21181.10 | 26-DEC-05:03 | 0.00 |
Annual Sum or Average | 0.945143E+12 | 0.233465E+12 | 5195.08 | 0.622365E+12 | 0.322778E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.479696E+11 | 0.116073E+11 | 377.35 | 0.349097E+11 | 0.128317E+11 | 0.00 | 1.00 | 0.00 | 78585.82 | 51131.25 | 26681.17 | 19109.41 | 0.00 | ||||||
Maximum of Months | 0.109838E+12 | 0.276815E+11 | 467.10 | 0.678799E+11 | 0.419585E+11 | 0.00 | 1.00 | 0.00 | 117927.07 | 78815.30 | 44254.69 | 28274.15 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.366839E+11 | 0.892174E+10 | 407.60 | 0.266700E+11 | 0.100140E+11 | 0.00 | 1.00 | 01-JAN-09:33 | 0.00 | 01-JAN-00:10 | 57232.16 | 02-JAN-14:00 | 44501.05 | 02-JAN-15:10 | 21547.89 | 14-JAN-06:03 | 14685.67 | 02-JAN-14:00 | 0.00 |
February | 0.381572E+11 | 0.920264E+10 | 371.15 | 0.284263E+11 | 0.973097E+10 | 0.00 | 1.00 | 01-FEB-14:20 | 0.00 | 01-FEB-00:10 | 61085.03 | 13-FEB-06:03 | 41340.48 | 21-FEB-16:20 | 27635.22 | 13-FEB-06:03 | 14019.21 | 13-FEB-06:03 | 0.00 |
March | 0.468742E+11 | 0.112684E+11 | 433.72 | 0.345113E+11 | 0.123630E+11 | 0.00 | 1.00 | 01-MAR-14:40 | 0.00 | 01-MAR-00:10 | 73027.21 | 06-MAR-06:03 | 45736.26 | 14-MAR-05:03 | 31114.97 | 06-MAR-05:03 | 16733.31 | 06-MAR-06:03 | 0.00 |
April | 0.520310E+11 | 0.127083E+11 | 420.40 | 0.390068E+11 | 0.130242E+11 | 0.00 | 1.00 | 01-APR-05:03 | 0.00 | 01-APR-00:10 | 83350.29 | 13-APR-05:03 | 57998.33 | 13-APR-05:03 | 25351.96 | 13-APR-05:03 | 19342.37 | 13-APR-05:03 | 0.00 |
May | 0.645048E+11 | 0.162035E+11 | 443.46 | 0.471526E+11 | 0.173522E+11 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 98448.82 | 30-MAY-04:02 | 64553.42 | 30-MAY-04:02 | 33895.41 | 30-MAY-04:02 | 23135.31 | 30-MAY-04:02 | 0.00 |
June | 0.691136E+11 | 0.175352E+11 | 444.68 | 0.492236E+11 | 0.198901E+11 | 0.00 | 1.00 | 01-JUN-04:03 | 0.00 | 01-JUN-00:10 | 104687.16 | 19-JUN-04:02 | 64486.72 | 12-JUN-04:02 | 42334.91 | 19-JUN-04:02 | 24063.13 | 19-JUN-04:02 | 0.00 |
July | 0.707335E+11 | 0.184559E+11 | 451.98 | 0.509103E+11 | 0.198232E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 99291.51 | 03-JUL-04:02 | 65524.05 | 31-JUL-04:02 | 35560.59 | 03-JUL-04:02 | 23398.59 | 31-JUL-04:02 | 0.00 |
August | 0.723344E+11 | 0.186518E+11 | 460.74 | 0.514733E+11 | 0.208611E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 98551.16 | 28-AUG-04:02 | 66027.76 | 21-AUG-04:02 | 33663.17 | 28-AUG-04:02 | 23446.14 | 28-AUG-04:02 | 0.00 |
September | 0.682334E+11 | 0.173645E+11 | 438.25 | 0.479788E+11 | 0.202545E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 91021.75 | 25-SEP-05:03 | 65893.59 | 11-SEP-04:02 | 29920.24 | 20-SEP-05:03 | 21425.76 | 19-SEP-04:03 | 0.00 |
October | 0.636567E+11 | 0.159383E+11 | 432.21 | 0.463167E+11 | 0.173399E+11 | 0.00 | 1.00 | 01-OCT-10:35 | 0.00 | 01-OCT-00:10 | 103588.46 | 02-OCT-04:02 | 64754.31 | 02-OCT-04:02 | 38834.15 | 02-OCT-04:02 | 24785.49 | 02-OCT-04:02 | 0.00 |
November | 0.517137E+11 | 0.125850E+11 | 399.33 | 0.371301E+11 | 0.145836E+11 | 0.00 | 1.00 | 01-NOV-05:03 | 0.00 | 01-NOV-00:10 | 86684.04 | 04-NOV-05:03 | 59152.55 | 21-NOV-06:03 | 31424.75 | 04-NOV-05:03 | 20306.94 | 04-NOV-05:03 | 0.00 |
December | 0.389455E+11 | 0.943765E+10 | 404.81 | 0.278192E+11 | 0.111263E+11 | 0.00 | 1.00 | 01-DEC-06:03 | 0.00 | 01-DEC-00:10 | 74288.43 | 09-DEC-06:03 | 47706.72 | 09-DEC-06:03 | 28020.94 | 11-DEC-05:03 | 17366.47 | 09-DEC-06:03 | 0.00 |
Annual Sum or Average | 0.672982E+12 | 0.168273E+12 | 5108.33 | 0.486619E+12 | 0.186363E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.366839E+11 | 0.892174E+10 | 371.15 | 0.266700E+11 | 0.973097E+10 | 0.00 | 1.00 | 0.00 | 57232.16 | 41340.48 | 21547.89 | 14019.21 | 0.00 | ||||||
Maximum of Months | 0.723344E+11 | 0.186518E+11 | 460.74 | 0.514733E+11 | 0.208611E+11 | 0.00 | 1.00 | 0.00 | 104687.16 | 66027.76 | 42334.91 | 24785.49 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.400082E+11 | 0.983311E+10 | 405.89 | 0.276247E+11 | 0.123835E+11 | 0.00 | 1.00 | 01-JAN-10:02 | 0.00 | 01-JAN-00:10 | 78043.66 | 02-JAN-14:00 | 53763.22 | 02-JAN-15:00 | 26395.16 | 02-JAN-14:00 | 19598.16 | 02-JAN-14:00 | 0.00 |
February | 0.426927E+11 | 0.103832E+11 | 369.40 | 0.305041E+11 | 0.121886E+11 | 0.00 | 1.00 | 02-FEB-09:50 | 0.00 | 01-FEB-00:10 | 63916.64 | 19-FEB-15:43 | 48445.62 | 22-FEB-16:00 | 24357.84 | 11-FEB-16:00 | 15524.96 | 19-FEB-15:43 | 0.00 |
March | 0.533744E+11 | 0.129003E+11 | 434.31 | 0.376032E+11 | 0.157712E+11 | 0.00 | 1.00 | 01-MAR-15:20 | 0.00 | 01-MAR-00:10 | 81481.80 | 06-MAR-06:03 | 55115.44 | 27-MAR-15:00 | 34823.58 | 06-MAR-06:03 | 18669.13 | 06-MAR-06:03 | 0.00 |
April | 0.631990E+11 | 0.154485E+11 | 421.99 | 0.446484E+11 | 0.185506E+11 | 0.00 | 1.00 | 01-APR-13:00 | 0.00 | 01-APR-00:10 | 83065.16 | 13-APR-05:03 | 59547.98 | 17-APR-15:00 | 28765.24 | 13-APR-05:03 | 21145.75 | 14-APR-15:00 | 0.00 |
May | 0.847888E+11 | 0.210510E+11 | 446.54 | 0.561310E+11 | 0.286578E+11 | 0.00 | 1.00 | 01-MAY-05:03 | 0.00 | 01-MAY-00:10 | 111981.87 | 30-MAY-04:02 | 74300.60 | 30-MAY-04:02 | 37681.27 | 30-MAY-04:02 | 26376.05 | 30-MAY-04:02 | 0.00 |
June | 0.961744E+11 | 0.238435E+11 | 448.56 | 0.595137E+11 | 0.366607E+11 | 0.00 | 1.00 | 01-JUN-05:03 | 0.00 | 01-JUN-00:10 | 107403.29 | 12-JUN-04:02 | 76254.67 | 12-JUN-04:02 | 43396.74 | 19-JUN-04:02 | 25441.66 | 12-JUN-04:02 | 0.00 |
July | 0.101551E+12 | 0.257125E+11 | 456.54 | 0.632188E+11 | 0.383322E+11 | 0.00 | 1.00 | 01-JUL-05:03 | 0.00 | 01-JUL-00:10 | 109517.14 | 31-JUL-04:02 | 76794.87 | 30-JUL-14:23 | 37957.47 | 03-JUL-04:02 | 28747.46 | 30-JUL-14:23 | 0.00 |
August | 0.101233E+12 | 0.253928E+11 | 462.18 | 0.619995E+11 | 0.392333E+11 | 0.00 | 1.00 | 01-AUG-04:03 | 0.00 | 01-AUG-00:10 | 112359.80 | 21-AUG-04:02 | 77866.25 | 21-AUG-04:02 | 36996.20 | 20-AUG-11:43 | 27653.72 | 06-AUG-14:13 | 0.00 |
September | 0.929018E+11 | 0.231391E+11 | 441.68 | 0.571701E+11 | 0.357317E+11 | 0.00 | 1.00 | 01-SEP-04:03 | 0.00 | 01-SEP-00:10 | 110850.75 | 18-SEP-04:02 | 77981.39 | 11-SEP-04:02 | 38706.26 | 19-SEP-04:03 | 27392.75 | 18-SEP-04:02 | 0.00 |
October | 0.819090E+11 | 0.202129E+11 | 431.04 | 0.524783E+11 | 0.294307E+11 | 0.00 | 1.00 | 01-OCT-10:30 | 0.00 | 01-OCT-00:10 | 124311.17 | 02-OCT-04:02 | 72232.01 | 02-OCT-04:02 | 52079.17 | 02-OCT-04:02 | 29626.66 | 02-OCT-04:02 | 0.00 |
November | 0.631895E+11 | 0.152822E+11 | 398.82 | 0.403592E+11 | 0.228303E+11 | 0.00 | 1.00 | 01-NOV-09:40 | 0.00 | 01-NOV-00:10 | 88671.58 | 04-NOV-05:03 | 54194.85 | 10-NOV-14:40 | 36084.17 | 30-NOV-06:03 | 20740.02 | 04-NOV-05:03 | 0.00 |
December | 0.438816E+11 | 0.106924E+11 | 404.58 | 0.293176E+11 | 0.145640E+11 | 0.00 | 1.00 | 01-DEC-11:30 | 0.00 | 01-DEC-00:10 | 78535.65 | 11-DEC-06:03 | 48957.56 | 08-DEC-15:30 | 30568.93 | 11-DEC-06:03 | 18033.52 | 11-DEC-06:03 | 0.00 |
Annual Sum or Average | 0.864903E+12 | 0.213891E+12 | 5121.54 | 0.560569E+12 | 0.304335E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.400082E+11 | 0.983311E+10 | 369.40 | 0.276247E+11 | 0.121886E+11 | 0.00 | 1.00 | 0.00 | 63916.64 | 48445.62 | 24357.84 | 15524.96 | 0.00 | ||||||
Maximum of Months | 0.101551E+12 | 0.257125E+11 | 462.18 | 0.632188E+11 | 0.392333E+11 | 0.00 | 1.00 | 0.00 | 124311.17 | 77981.39 | 52079.17 | 29626.66 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 263.46 | 0.00 | 263.46 | 304.51 | 574.07 | 0.00 | 0.00 | 0.00 |
February | 311.85 | 0.00 | 311.85 | 445.56 | 479.63 | 0.00 | 0.00 | 0.00 |
March | 371.90 | 0.00 | 371.90 | 523.66 | 402.92 | 0.00 | 0.00 | 0.00 |
April | 416.73 | 1.87 | 414.86 | 721.26 | 262.32 | 0.00 | 0.00 | 0.00 |
May | 475.88 | 21.29 | 454.60 | 990.03 | 137.27 | 0.00 | 0.00 | 0.00 |
June | 508.35 | 36.60 | 471.74 | 1139.87 | 62.63 | 0.00 | 0.00 | 0.00 |
July | 514.43 | 25.21 | 489.22 | 1208.28 | 91.66 | 0.00 | 0.00 | 0.00 |
August | 455.28 | 4.19 | 451.09 | 1021.91 | 58.73 | 0.00 | 0.00 | 0.00 |
September | 403.89 | 0.03 | 403.85 | 940.86 | 100.10 | 0.00 | 0.00 | 0.00 |
October | 338.36 | 0.00 | 338.36 | 696.87 | 155.51 | 0.00 | 0.00 | 0.00 |
November | 294.20 | 0.00 | 294.20 | 498.63 | 296.00 | 0.00 | 0.00 | 0.00 |
December | 260.59 | 0.00 | 260.59 | 341.50 | 482.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 384.94 | 7.47 | 377.47 | 737.49 | 257.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 260.59 | 0.00 | 260.59 | 304.51 | 58.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 514.43 | 36.60 | 489.22 | 1208.28 | 574.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 422.91 | 202.60 | 220.31 | 626.49 | 362.95 | 0.00 | 0.00 | 0.00 |
February | 488.32 | 226.04 | 262.27 | 778.53 | 302.64 | 0.00 | 0.00 | 0.00 |
March | 596.20 | 281.86 | 314.34 | 945.50 | 250.78 | 0.00 | 0.00 | 0.00 |
April | 647.03 | 288.70 | 358.33 | 1143.73 | 175.16 | 0.00 | 0.00 | 0.00 |
May | 612.11 | 243.76 | 368.36 | 1184.45 | 88.00 | 0.00 | 0.00 | 0.00 |
June | 604.16 | 232.05 | 372.11 | 1230.58 | 41.03 | 0.00 | 0.00 | 0.00 |
July | 620.78 | 223.87 | 396.92 | 1307.21 | 62.00 | 0.00 | 0.00 | 0.00 |
August | 567.65 | 189.81 | 377.84 | 1165.25 | 38.43 | 0.00 | 0.00 | 0.00 |
September | 547.25 | 197.83 | 349.42 | 1137.54 | 67.32 | 0.00 | 0.00 | 0.00 |
October | 503.73 | 216.93 | 286.79 | 972.12 | 102.95 | 0.00 | 0.00 | 0.00 |
November | 408.84 | 163.02 | 245.82 | 711.58 | 187.15 | 0.00 | 0.00 | 0.00 |
December | 330.25 | 116.60 | 213.66 | 504.08 | 309.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 529.19 | 215.11 | 314.08 | 976.33 | 165.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 330.25 | 116.60 | 213.66 | 504.08 | 38.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 647.03 | 288.70 | 396.92 | 1307.21 | 362.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1238.22 | 804.44 | 433.78 | 2009.40 | 568.68 | 0.00 | 0.00 | 0.00 |
February | 1120.15 | 648.15 | 472.01 | 1918.66 | 482.76 | 0.00 | 0.00 | 0.00 |
March | 860.02 | 363.61 | 496.41 | 1490.76 | 402.56 | 0.00 | 0.00 | 0.00 |
April | 584.80 | 102.55 | 482.25 | 1115.93 | 273.46 | 0.00 | 0.00 | 0.00 |
May | 468.62 | 10.14 | 458.49 | 979.34 | 133.43 | 0.00 | 0.00 | 0.00 |
June | 446.79 | 0.84 | 445.95 | 1007.95 | 63.52 | 0.00 | 0.00 | 0.00 |
July | 478.39 | 4.43 | 473.96 | 1130.43 | 91.36 | 0.00 | 0.00 | 0.00 |
August | 542.96 | 45.82 | 497.14 | 1225.01 | 59.57 | 0.00 | 0.00 | 0.00 |
September | 695.06 | 170.33 | 524.74 | 1552.11 | 105.85 | 0.00 | 0.00 | 0.00 |
October | 955.85 | 448.45 | 507.39 | 1890.42 | 172.97 | 0.00 | 0.00 | 0.00 |
November | 1087.54 | 606.97 | 480.58 | 1935.77 | 306.49 | 0.00 | 0.00 | 0.00 |
December | 1193.30 | 752.66 | 440.63 | 1981.62 | 493.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 804.52 | 328.45 | 476.06 | 1517.78 | 261.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 446.79 | 0.84 | 433.78 | 979.34 | 59.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1238.22 | 804.44 | 524.74 | 2009.40 | 568.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 379.91 | 163.79 | 216.13 | 576.00 | 382.05 | 0.00 | 0.00 | 0.00 |
February | 475.07 | 215.00 | 260.07 | 789.71 | 328.21 | 0.00 | 0.00 | 0.00 |
March | 591.61 | 270.16 | 321.45 | 976.53 | 279.21 | 0.00 | 0.00 | 0.00 |
April | 651.19 | 301.52 | 349.67 | 1169.20 | 191.42 | 0.00 | 0.00 | 0.00 |
May | 593.64 | 228.52 | 365.12 | 1165.41 | 101.09 | 0.00 | 0.00 | 0.00 |
June | 503.00 | 141.09 | 361.90 | 1051.93 | 46.26 | 0.00 | 0.00 | 0.00 |
July | 562.14 | 173.91 | 388.24 | 1206.30 | 66.24 | 0.00 | 0.00 | 0.00 |
August | 560.87 | 182.78 | 378.08 | 1155.04 | 44.66 | 0.00 | 0.00 | 0.00 |
September | 478.45 | 141.08 | 337.37 | 1015.15 | 70.02 | 0.00 | 0.00 | 0.00 |
October | 475.97 | 185.55 | 290.42 | 931.43 | 113.90 | 0.00 | 0.00 | 0.00 |
November | 392.62 | 144.02 | 248.61 | 703.49 | 204.25 | 0.00 | 0.00 | 0.00 |
December | 393.33 | 175.85 | 217.47 | 632.38 | 323.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.04 | 193.56 | 311.49 | 948.60 | 178.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.91 | 141.08 | 216.13 | 576.00 | 44.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 651.19 | 301.52 | 388.24 | 1206.30 | 382.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.82 | 0.00 | 87.82 | 96.13 | 218.01 | 0.00 | 0.00 | 0.00 |
February | 103.94 | 0.00 | 103.94 | 146.74 | 176.03 | 0.00 | 0.00 | 0.00 |
March | 123.96 | 0.00 | 123.96 | 177.94 | 141.26 | 0.00 | 0.00 | 0.00 |
April | 138.90 | 0.62 | 138.28 | 246.67 | 87.65 | 0.00 | 0.00 | 0.00 |
May | 158.62 | 7.10 | 151.52 | 336.49 | 44.59 | 0.00 | 0.00 | 0.00 |
June | 169.44 | 12.20 | 157.24 | 387.43 | 19.45 | 0.00 | 0.00 | 0.00 |
July | 171.47 | 8.40 | 163.07 | 408.96 | 30.07 | 0.00 | 0.00 | 0.00 |
August | 151.75 | 1.40 | 150.36 | 342.37 | 21.03 | 0.00 | 0.00 | 0.00 |
September | 134.62 | 0.01 | 134.61 | 315.74 | 36.20 | 0.00 | 0.00 | 0.00 |
October | 112.78 | 0.00 | 112.78 | 232.57 | 58.11 | 0.00 | 0.00 | 0.00 |
November | 98.06 | 0.00 | 98.06 | 163.52 | 113.57 | 0.00 | 0.00 | 0.00 |
December | 86.86 | 0.00 | 86.86 | 108.33 | 185.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.31 | 2.49 | 125.82 | 247.39 | 93.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.86 | 0.00 | 86.86 | 96.13 | 19.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.47 | 12.20 | 163.07 | 408.96 | 218.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.82 | 0.00 | 87.82 | 96.14 | 218.02 | 0.00 | 0.00 | 0.00 |
February | 103.95 | 0.00 | 103.95 | 146.75 | 176.04 | 0.00 | 0.00 | 0.00 |
March | 123.97 | 0.00 | 123.97 | 177.95 | 141.27 | 0.00 | 0.00 | 0.00 |
April | 138.91 | 0.62 | 138.29 | 246.68 | 87.66 | 0.00 | 0.00 | 0.00 |
May | 158.63 | 7.10 | 151.53 | 336.52 | 44.59 | 0.00 | 0.00 | 0.00 |
June | 169.45 | 12.20 | 157.25 | 387.45 | 19.45 | 0.00 | 0.00 | 0.00 |
July | 171.48 | 8.40 | 163.08 | 408.99 | 30.07 | 0.00 | 0.00 | 0.00 |
August | 151.76 | 1.40 | 150.37 | 342.39 | 21.03 | 0.00 | 0.00 | 0.00 |
September | 134.63 | 0.01 | 134.62 | 315.76 | 36.20 | 0.00 | 0.00 | 0.00 |
October | 112.79 | 0.00 | 112.79 | 232.59 | 58.11 | 0.00 | 0.00 | 0.00 |
November | 98.07 | 0.00 | 98.07 | 163.53 | 113.58 | 0.00 | 0.00 | 0.00 |
December | 86.87 | 0.00 | 86.87 | 108.33 | 185.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.32 | 2.49 | 125.83 | 247.40 | 93.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.87 | 0.00 | 86.87 | 96.14 | 19.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.48 | 12.20 | 163.08 | 408.99 | 218.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.82 | 0.00 | 87.82 | 96.14 | 218.02 | 0.00 | 0.00 | 0.00 |
February | 103.95 | 0.00 | 103.95 | 146.75 | 176.04 | 0.00 | 0.00 | 0.00 |
March | 123.97 | 0.00 | 123.97 | 177.95 | 141.27 | 0.00 | 0.00 | 0.00 |
April | 138.91 | 0.62 | 138.29 | 246.68 | 87.66 | 0.00 | 0.00 | 0.00 |
May | 158.63 | 7.10 | 151.53 | 336.52 | 44.59 | 0.00 | 0.00 | 0.00 |
June | 169.45 | 12.20 | 157.25 | 387.45 | 19.45 | 0.00 | 0.00 | 0.00 |
July | 171.48 | 8.40 | 163.08 | 408.99 | 30.07 | 0.00 | 0.00 | 0.00 |
August | 151.76 | 1.40 | 150.37 | 342.39 | 21.03 | 0.00 | 0.00 | 0.00 |
September | 134.63 | 0.01 | 134.62 | 315.76 | 36.20 | 0.00 | 0.00 | 0.00 |
October | 112.79 | 0.00 | 112.79 | 232.59 | 58.11 | 0.00 | 0.00 | 0.00 |
November | 98.07 | 0.00 | 98.07 | 163.53 | 113.58 | 0.00 | 0.00 | 0.00 |
December | 86.87 | 0.00 | 86.87 | 108.33 | 185.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 128.32 | 2.49 | 125.83 | 247.40 | 93.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 86.87 | 0.00 | 86.87 | 96.14 | 19.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 171.48 | 12.20 | 163.08 | 408.99 | 218.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 406.82 | 194.89 | 211.93 | 590.33 | 406.11 | 0.00 | 0.00 | 0.00 |
February | 469.74 | 217.44 | 252.30 | 745.87 | 329.64 | 0.00 | 0.00 | 0.00 |
March | 573.52 | 271.13 | 302.38 | 917.78 | 263.93 | 0.00 | 0.00 | 0.00 |
April | 622.41 | 277.72 | 344.70 | 1114.97 | 179.56 | 0.00 | 0.00 | 0.00 |
May | 588.83 | 234.48 | 354.34 | 1154.16 | 88.78 | 0.00 | 0.00 | 0.00 |
June | 581.18 | 223.23 | 357.95 | 1197.08 | 40.21 | 0.00 | 0.00 | 0.00 |
July | 597.17 | 215.35 | 381.82 | 1268.73 | 63.92 | 0.00 | 0.00 | 0.00 |
August | 546.06 | 182.59 | 363.47 | 1123.71 | 44.03 | 0.00 | 0.00 | 0.00 |
September | 526.44 | 190.31 | 336.13 | 1097.42 | 74.22 | 0.00 | 0.00 | 0.00 |
October | 484.56 | 208.68 | 275.88 | 937.06 | 118.22 | 0.00 | 0.00 | 0.00 |
November | 393.29 | 156.82 | 236.47 | 679.81 | 212.83 | 0.00 | 0.00 | 0.00 |
December | 317.69 | 112.16 | 205.53 | 473.20 | 349.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 509.06 | 206.93 | 302.13 | 942.40 | 180.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 317.69 | 112.16 | 205.53 | 473.20 | 40.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 622.41 | 277.72 | 381.82 | 1268.73 | 406.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.09 | 7.71 | 8.38 | 23.34 | 16.06 | 0.00 | 0.00 | 0.00 |
February | 18.57 | 8.60 | 9.98 | 29.49 | 13.03 | 0.00 | 0.00 | 0.00 |
March | 22.68 | 10.72 | 11.96 | 36.29 | 10.44 | 0.00 | 0.00 | 0.00 |
April | 24.61 | 10.98 | 13.63 | 44.08 | 7.10 | 0.00 | 0.00 | 0.00 |
May | 23.28 | 9.27 | 14.01 | 45.63 | 3.51 | 0.00 | 0.00 | 0.00 |
June | 22.98 | 8.83 | 14.15 | 47.33 | 1.59 | 0.00 | 0.00 | 0.00 |
July | 23.61 | 8.51 | 15.10 | 50.16 | 2.53 | 0.00 | 0.00 | 0.00 |
August | 21.59 | 7.22 | 14.37 | 44.43 | 1.74 | 0.00 | 0.00 | 0.00 |
September | 20.81 | 7.52 | 13.29 | 43.39 | 2.93 | 0.00 | 0.00 | 0.00 |
October | 19.16 | 8.25 | 10.91 | 37.05 | 4.67 | 0.00 | 0.00 | 0.00 |
November | 15.55 | 6.20 | 9.35 | 26.88 | 8.41 | 0.00 | 0.00 | 0.00 |
December | 12.56 | 4.43 | 8.13 | 18.71 | 13.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.13 | 8.18 | 11.95 | 37.26 | 7.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.56 | 4.43 | 8.13 | 18.71 | 1.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.61 | 10.98 | 15.10 | 50.16 | 16.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 412.75 | 268.16 | 144.60 | 668.37 | 220.66 | 0.00 | 0.00 | 0.00 |
February | 373.40 | 216.06 | 157.34 | 641.48 | 182.44 | 0.00 | 0.00 | 0.00 |
March | 286.68 | 121.21 | 165.48 | 503.88 | 144.33 | 0.00 | 0.00 | 0.00 |
April | 194.94 | 34.18 | 160.75 | 379.02 | 93.47 | 0.00 | 0.00 | 0.00 |
May | 156.21 | 3.38 | 152.83 | 331.60 | 44.15 | 0.00 | 0.00 | 0.00 |
June | 148.94 | 0.28 | 148.65 | 341.14 | 19.84 | 0.00 | 0.00 | 0.00 |
July | 159.47 | 1.48 | 157.99 | 380.18 | 30.49 | 0.00 | 0.00 | 0.00 |
August | 180.99 | 15.27 | 165.72 | 406.82 | 22.63 | 0.00 | 0.00 | 0.00 |
September | 231.69 | 56.78 | 174.92 | 515.56 | 40.46 | 0.00 | 0.00 | 0.00 |
October | 318.63 | 149.49 | 169.14 | 628.37 | 70.06 | 0.00 | 0.00 | 0.00 |
November | 362.53 | 202.33 | 160.20 | 644.19 | 122.14 | 0.00 | 0.00 | 0.00 |
December | 397.78 | 250.90 | 146.88 | 660.35 | 192.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 268.18 | 109.49 | 158.69 | 507.74 | 98.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 148.94 | 0.28 | 144.60 | 331.60 | 19.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.75 | 268.16 | 174.92 | 668.37 | 220.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 412.75 | 268.16 | 144.60 | 668.37 | 220.66 | 0.00 | 0.00 | 0.00 |
February | 373.40 | 216.06 | 157.34 | 641.48 | 182.44 | 0.00 | 0.00 | 0.00 |
March | 286.68 | 121.21 | 165.48 | 503.88 | 144.33 | 0.00 | 0.00 | 0.00 |
April | 194.94 | 34.18 | 160.75 | 379.02 | 93.47 | 0.00 | 0.00 | 0.00 |
May | 156.21 | 3.38 | 152.83 | 331.60 | 44.15 | 0.00 | 0.00 | 0.00 |
June | 148.94 | 0.28 | 148.65 | 341.14 | 19.84 | 0.00 | 0.00 | 0.00 |
July | 159.47 | 1.48 | 157.99 | 380.18 | 30.49 | 0.00 | 0.00 | 0.00 |
August | 180.99 | 15.27 | 165.72 | 406.82 | 22.63 | 0.00 | 0.00 | 0.00 |
September | 231.69 | 56.78 | 174.92 | 515.56 | 40.46 | 0.00 | 0.00 | 0.00 |
October | 318.63 | 149.49 | 169.14 | 628.37 | 70.06 | 0.00 | 0.00 | 0.00 |
November | 362.53 | 202.33 | 160.20 | 644.19 | 122.14 | 0.00 | 0.00 | 0.00 |
December | 397.78 | 250.90 | 146.88 | 660.35 | 192.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 268.18 | 109.49 | 158.69 | 507.74 | 98.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 148.94 | 0.28 | 144.60 | 331.60 | 19.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.75 | 268.16 | 174.92 | 668.37 | 220.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 412.73 | 268.14 | 144.59 | 668.32 | 220.64 | 0.00 | 0.00 | 0.00 |
February | 373.37 | 216.04 | 157.33 | 641.44 | 182.43 | 0.00 | 0.00 | 0.00 |
March | 286.67 | 121.20 | 165.47 | 503.84 | 144.32 | 0.00 | 0.00 | 0.00 |
April | 194.93 | 34.18 | 160.74 | 379.00 | 93.46 | 0.00 | 0.00 | 0.00 |
May | 156.20 | 3.38 | 152.82 | 331.58 | 44.15 | 0.00 | 0.00 | 0.00 |
June | 148.93 | 0.28 | 148.64 | 341.12 | 19.84 | 0.00 | 0.00 | 0.00 |
July | 159.46 | 1.48 | 157.98 | 380.15 | 30.49 | 0.00 | 0.00 | 0.00 |
August | 180.98 | 15.27 | 165.71 | 406.79 | 22.62 | 0.00 | 0.00 | 0.00 |
September | 231.68 | 56.77 | 174.91 | 515.53 | 40.46 | 0.00 | 0.00 | 0.00 |
October | 318.61 | 149.48 | 169.13 | 628.33 | 70.05 | 0.00 | 0.00 | 0.00 |
November | 362.50 | 202.32 | 160.19 | 644.15 | 122.14 | 0.00 | 0.00 | 0.00 |
December | 397.75 | 250.88 | 146.87 | 660.31 | 192.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 268.16 | 109.48 | 158.68 | 507.71 | 98.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 148.93 | 0.28 | 144.59 | 331.58 | 19.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 412.73 | 268.14 | 174.91 | 668.32 | 220.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 365.46 | 157.55 | 207.91 | 541.35 | 429.90 | 0.00 | 0.00 | 0.00 |
February | 457.00 | 206.82 | 250.18 | 754.43 | 357.91 | 0.00 | 0.00 | 0.00 |
March | 569.10 | 259.88 | 309.22 | 943.92 | 295.00 | 0.00 | 0.00 | 0.00 |
April | 626.42 | 290.05 | 336.37 | 1134.02 | 195.50 | 0.00 | 0.00 | 0.00 |
May | 571.06 | 219.83 | 351.23 | 1131.82 | 101.54 | 0.00 | 0.00 | 0.00 |
June | 483.86 | 135.73 | 348.14 | 1022.55 | 44.32 | 0.00 | 0.00 | 0.00 |
July | 540.76 | 167.29 | 373.47 | 1168.82 | 68.00 | 0.00 | 0.00 | 0.00 |
August | 539.53 | 175.83 | 363.70 | 1112.60 | 50.59 | 0.00 | 0.00 | 0.00 |
September | 460.25 | 135.71 | 324.54 | 977.92 | 77.76 | 0.00 | 0.00 | 0.00 |
October | 457.86 | 178.49 | 279.37 | 895.34 | 129.09 | 0.00 | 0.00 | 0.00 |
November | 377.69 | 138.54 | 239.15 | 670.49 | 232.28 | 0.00 | 0.00 | 0.00 |
December | 378.36 | 169.16 | 209.20 | 596.11 | 368.28 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 485.83 | 186.19 | 299.64 | 913.32 | 195.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 365.46 | 135.71 | 207.91 | 541.35 | 44.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 626.42 | 290.05 | 373.47 | 1168.82 | 429.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 14.45 | 6.23 | 8.22 | 21.40 | 17.00 | 0.00 | 0.00 | 0.00 |
February | 18.07 | 8.18 | 9.89 | 29.83 | 14.15 | 0.00 | 0.00 | 0.00 |
March | 22.50 | 10.28 | 12.23 | 37.32 | 11.66 | 0.00 | 0.00 | 0.00 |
April | 24.77 | 11.47 | 13.30 | 44.84 | 7.73 | 0.00 | 0.00 | 0.00 |
May | 22.58 | 8.69 | 13.89 | 44.75 | 4.01 | 0.00 | 0.00 | 0.00 |
June | 19.13 | 5.37 | 13.76 | 40.43 | 1.75 | 0.00 | 0.00 | 0.00 |
July | 21.38 | 6.61 | 14.77 | 46.21 | 2.69 | 0.00 | 0.00 | 0.00 |
August | 21.33 | 6.95 | 14.38 | 43.99 | 2.00 | 0.00 | 0.00 | 0.00 |
September | 18.20 | 5.37 | 12.83 | 38.67 | 3.07 | 0.00 | 0.00 | 0.00 |
October | 18.10 | 7.06 | 11.05 | 35.40 | 5.10 | 0.00 | 0.00 | 0.00 |
November | 14.93 | 5.48 | 9.46 | 26.51 | 9.18 | 0.00 | 0.00 | 0.00 |
December | 14.96 | 6.69 | 8.27 | 23.57 | 14.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 19.21 | 7.36 | 11.85 | 36.11 | 7.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 14.45 | 5.37 | 8.22 | 21.40 | 1.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.77 | 11.47 | 14.77 | 46.21 | 17.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 263.46 | 0.00 | 263.46 | 291.05 | 633.77 | 0.00 | 0.00 | 0.00 |
February | 311.85 | 0.00 | 311.85 | 437.65 | 522.60 | 0.00 | 0.00 | 0.00 |
March | 371.90 | 0.00 | 371.90 | 521.80 | 433.43 | 0.00 | 0.00 | 0.00 |
April | 416.73 | 1.87 | 414.86 | 727.13 | 275.40 | 0.00 | 0.00 | 0.00 |
May | 475.88 | 21.29 | 454.60 | 1000.83 | 140.58 | 0.00 | 0.00 | 0.00 |
June | 508.35 | 36.60 | 471.74 | 1154.86 | 62.20 | 0.00 | 0.00 | 0.00 |
July | 514.43 | 25.21 | 489.22 | 1224.96 | 91.22 | 0.00 | 0.00 | 0.00 |
August | 455.28 | 4.19 | 451.09 | 1032.31 | 60.03 | 0.00 | 0.00 | 0.00 |
September | 403.89 | 0.03 | 403.85 | 952.88 | 103.93 | 0.00 | 0.00 | 0.00 |
October | 338.36 | 0.00 | 338.36 | 702.11 | 166.09 | 0.00 | 0.00 | 0.00 |
November | 294.20 | 0.00 | 294.20 | 494.95 | 325.14 | 0.00 | 0.00 | 0.00 |
December | 260.59 | 0.00 | 260.59 | 330.24 | 532.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 384.94 | 7.47 | 377.47 | 740.69 | 277.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 260.59 | 0.00 | 260.59 | 291.05 | 60.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 514.43 | 36.60 | 489.22 | 1224.96 | 633.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 422.91 | 202.60 | 220.31 | 617.15 | 395.03 | 0.00 | 0.00 | 0.00 |
February | 488.32 | 226.04 | 262.27 | 773.96 | 326.27 | 0.00 | 0.00 | 0.00 |
March | 596.20 | 281.86 | 314.34 | 946.43 | 266.56 | 0.00 | 0.00 | 0.00 |
April | 647.03 | 288.70 | 358.33 | 1150.31 | 182.91 | 0.00 | 0.00 | 0.00 |
May | 612.11 | 243.76 | 368.36 | 1193.73 | 90.46 | 0.00 | 0.00 | 0.00 |
June | 604.16 | 232.05 | 372.11 | 1241.64 | 40.84 | 0.00 | 0.00 | 0.00 |
July | 620.78 | 223.87 | 396.92 | 1319.16 | 61.94 | 0.00 | 0.00 | 0.00 |
August | 567.65 | 189.81 | 377.84 | 1173.42 | 39.33 | 0.00 | 0.00 | 0.00 |
September | 547.25 | 197.83 | 349.42 | 1146.64 | 69.56 | 0.00 | 0.00 | 0.00 |
October | 503.73 | 216.93 | 286.79 | 977.20 | 109.24 | 0.00 | 0.00 | 0.00 |
November | 408.84 | 163.02 | 245.82 | 709.92 | 203.35 | 0.00 | 0.00 | 0.00 |
December | 330.25 | 116.60 | 213.66 | 497.00 | 337.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 529.19 | 215.11 | 314.08 | 979.65 | 176.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 330.25 | 116.60 | 213.66 | 497.00 | 39.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 647.03 | 288.70 | 396.92 | 1319.16 | 395.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1238.22 | 804.44 | 433.78 | 1998.89 | 616.61 | 0.00 | 0.00 | 0.00 |
February | 1120.15 | 648.15 | 472.01 | 1914.18 | 518.97 | 0.00 | 0.00 | 0.00 |
March | 860.02 | 363.61 | 496.41 | 1492.33 | 428.85 | 0.00 | 0.00 | 0.00 |
April | 584.80 | 102.55 | 482.25 | 1123.96 | 286.32 | 0.00 | 0.00 | 0.00 |
May | 468.62 | 10.14 | 458.49 | 990.61 | 137.75 | 0.00 | 0.00 | 0.00 |
June | 446.79 | 0.84 | 445.95 | 1022.46 | 63.39 | 0.00 | 0.00 | 0.00 |
July | 478.39 | 4.43 | 473.96 | 1147.05 | 91.09 | 0.00 | 0.00 | 0.00 |
August | 542.96 | 45.82 | 497.14 | 1236.18 | 60.97 | 0.00 | 0.00 | 0.00 |
September | 695.06 | 170.33 | 524.74 | 1565.45 | 109.54 | 0.00 | 0.00 | 0.00 |
October | 955.85 | 448.45 | 507.39 | 1897.41 | 182.45 | 0.00 | 0.00 | 0.00 |
November | 1087.54 | 606.97 | 480.58 | 1934.50 | 330.45 | 0.00 | 0.00 | 0.00 |
December | 1193.30 | 752.66 | 440.63 | 1975.22 | 535.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 804.52 | 328.45 | 476.06 | 1522.90 | 279.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 446.79 | 0.84 | 433.78 | 990.61 | 60.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1238.22 | 804.44 | 524.74 | 1998.89 | 616.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 379.91 | 163.79 | 216.13 | 566.58 | 421.23 | 0.00 | 0.00 | 0.00 |
February | 475.07 | 215.00 | 260.07 | 784.23 | 356.62 | 0.00 | 0.00 | 0.00 |
March | 591.61 | 270.16 | 321.45 | 975.68 | 299.40 | 0.00 | 0.00 | 0.00 |
April | 651.19 | 301.52 | 349.67 | 1172.72 | 200.76 | 0.00 | 0.00 | 0.00 |
May | 593.64 | 228.52 | 365.12 | 1172.16 | 104.16 | 0.00 | 0.00 | 0.00 |
June | 503.00 | 141.09 | 361.90 | 1060.43 | 46.34 | 0.00 | 0.00 | 0.00 |
July | 562.14 | 173.91 | 388.24 | 1215.88 | 66.71 | 0.00 | 0.00 | 0.00 |
August | 560.87 | 182.78 | 378.08 | 1161.18 | 45.73 | 0.00 | 0.00 | 0.00 |
September | 478.45 | 141.08 | 337.37 | 1021.98 | 73.18 | 0.00 | 0.00 | 0.00 |
October | 475.97 | 185.55 | 290.42 | 934.33 | 121.45 | 0.00 | 0.00 | 0.00 |
November | 392.62 | 144.02 | 248.61 | 700.52 | 223.84 | 0.00 | 0.00 | 0.00 |
December | 393.33 | 175.85 | 217.47 | 624.72 | 356.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 505.04 | 193.56 | 311.49 | 950.12 | 192.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.91 | 141.08 | 216.13 | 566.58 | 45.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 651.19 | 301.52 | 388.24 | 1215.88 | 421.23 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.705648E+09 | 0.00 | 0.705648E+09 | 0.815599E+09 | 0.153758E+10 |
February | 0.754417E+09 | 0.00 | 0.754417E+09 | 0.107791E+10 | 0.116031E+10 |
March | 0.996092E+09 | 0.00 | 0.996092E+09 | 0.140256E+10 | 0.107918E+10 |
April | 0.108016E+10 | 4852206.98 | 0.107531E+10 | 0.186951E+10 | 0.679944E+09 |
May | 0.127461E+10 | 57016092.10 | 0.121759E+10 | 0.265169E+10 | 0.367675E+09 |
June | 0.131763E+10 | 94873460.95 | 0.122276E+10 | 0.295454E+10 | 0.162345E+09 |
July | 0.137784E+10 | 67517062.26 | 0.131033E+10 | 0.323626E+10 | 0.245500E+09 |
August | 0.121941E+10 | 11215237.28 | 0.120820E+10 | 0.273707E+10 | 0.157312E+09 |
September | 0.104687E+10 | 82817.23 | 0.104679E+10 | 0.243872E+10 | 0.259454E+09 |
October | 0.906255E+09 | 0.00 | 0.906255E+09 | 0.186650E+10 | 0.416505E+09 |
November | 0.762575E+09 | 0.00 | 0.762575E+09 | 0.129245E+10 | 0.767239E+09 |
December | 0.697974E+09 | 0.00 | 0.697974E+09 | 0.914684E+09 | 0.129145E+10 |
Annual Sum or Average | 0.121395E+11 | 0.235557E+09 | 0.119039E+11 | 0.232575E+11 | 0.812450E+10 |
Minimum of Months | 0.697974E+09 | 0.00 | 0.697974E+09 | 0.815599E+09 | 0.157312E+09 |
Maximum of Months | 0.137784E+10 | 94873460.95 | 0.131033E+10 | 0.323626E+10 | 0.153758E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113271E+10 | 0.542638E+09 | 0.590074E+09 | 0.167799E+10 | 0.972137E+09 |
February | 0.118134E+10 | 0.546841E+09 | 0.634495E+09 | 0.188342E+10 | 0.732158E+09 |
March | 0.159686E+10 | 0.754923E+09 | 0.841933E+09 | 0.253244E+10 | 0.671685E+09 |
April | 0.167709E+10 | 0.748308E+09 | 0.928782E+09 | 0.296455E+10 | 0.454006E+09 |
May | 0.163948E+10 | 0.652877E+09 | 0.986603E+09 | 0.317243E+10 | 0.235688E+09 |
June | 0.156599E+10 | 0.601486E+09 | 0.964508E+09 | 0.318966E+10 | 0.106344E+09 |
July | 0.166271E+10 | 0.599606E+09 | 0.106310E+10 | 0.350124E+10 | 0.166062E+09 |
August | 0.152040E+10 | 0.508389E+09 | 0.101201E+10 | 0.312100E+10 | 0.102940E+09 |
September | 0.141848E+10 | 0.512786E+09 | 0.905698E+09 | 0.294851E+10 | 0.174486E+09 |
October | 0.134918E+10 | 0.581037E+09 | 0.768141E+09 | 0.260372E+10 | 0.275737E+09 |
November | 0.105971E+10 | 0.422547E+09 | 0.637165E+09 | 0.184440E+10 | 0.485087E+09 |
December | 0.884551E+09 | 0.312288E+09 | 0.572263E+09 | 0.135012E+10 | 0.827672E+09 |
Annual Sum or Average | 0.166885E+11 | 0.678373E+10 | 0.990478E+10 | 0.307895E+11 | 0.520400E+10 |
Minimum of Months | 0.884551E+09 | 0.312288E+09 | 0.572263E+09 | 0.135012E+10 | 0.102940E+09 |
Maximum of Months | 0.167709E+10 | 0.754923E+09 | 0.106310E+10 | 0.350124E+10 | 0.972137E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.331645E+10 | 0.215462E+10 | 0.116183E+10 | 0.538198E+10 | 0.152317E+10 |
February | 0.270988E+10 | 0.156799E+10 | 0.114188E+10 | 0.464162E+10 | 0.116790E+10 |
March | 0.230349E+10 | 0.973894E+09 | 0.132960E+10 | 0.399284E+10 | 0.107820E+10 |
April | 0.151581E+10 | 0.265813E+09 | 0.124999E+10 | 0.289249E+10 | 0.708803E+09 |
May | 0.125516E+10 | 27155028.65 | 0.122801E+10 | 0.262308E+10 | 0.357388E+09 |
June | 0.115809E+10 | 2185492.69 | 0.115590E+10 | 0.261260E+10 | 0.164657E+09 |
July | 0.128133E+10 | 11876747.67 | 0.126945E+10 | 0.302773E+10 | 0.244699E+09 |
August | 0.145427E+10 | 0.122718E+09 | 0.133155E+10 | 0.328106E+10 | 0.159542E+09 |
September | 0.180160E+10 | 0.441485E+09 | 0.136012E+10 | 0.402306E+10 | 0.274363E+09 |
October | 0.256014E+10 | 0.120114E+10 | 0.135901E+10 | 0.506330E+10 | 0.463292E+09 |
November | 0.281891E+10 | 0.157326E+10 | 0.124565E+10 | 0.501751E+10 | 0.794429E+09 |
December | 0.319613E+10 | 0.201594E+10 | 0.118020E+10 | 0.530758E+10 | 0.132282E+10 |
Annual Sum or Average | 0.253713E+11 | 0.103581E+11 | 0.150132E+11 | 0.478648E+11 | 0.825926E+10 |
Minimum of Months | 0.115809E+10 | 2185492.69 | 0.114188E+10 | 0.261260E+10 | 0.159542E+09 |
Maximum of Months | 0.331645E+10 | 0.215462E+10 | 0.136012E+10 | 0.538198E+10 | 0.152317E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101756E+10 | 0.438682E+09 | 0.578874E+09 | 0.154275E+10 | 0.102328E+10 |
February | 0.114929E+10 | 0.520118E+09 | 0.629171E+09 | 0.191048E+10 | 0.794007E+09 |
March | 0.158456E+10 | 0.723592E+09 | 0.860969E+09 | 0.261553E+10 | 0.747831E+09 |
April | 0.168788E+10 | 0.781541E+09 | 0.906338E+09 | 0.303056E+10 | 0.496154E+09 |
May | 0.159001E+10 | 0.612079E+09 | 0.977933E+09 | 0.312143E+10 | 0.270753E+09 |
June | 0.130377E+10 | 0.365718E+09 | 0.938050E+09 | 0.272659E+10 | 0.119894E+09 |
July | 0.150565E+10 | 0.465799E+09 | 0.103985E+10 | 0.323095E+10 | 0.177413E+09 |
August | 0.150222E+10 | 0.489571E+09 | 0.101265E+10 | 0.309366E+10 | 0.119630E+09 |
September | 0.124014E+10 | 0.365677E+09 | 0.874462E+09 | 0.263127E+10 | 0.181494E+09 |
October | 0.127483E+10 | 0.496968E+09 | 0.777865E+09 | 0.249475E+10 | 0.305065E+09 |
November | 0.101768E+10 | 0.373290E+09 | 0.644391E+09 | 0.182345E+10 | 0.529418E+09 |
December | 0.105349E+10 | 0.471004E+09 | 0.582481E+09 | 0.169376E+10 | 0.867281E+09 |
Annual Sum or Average | 0.159271E+11 | 0.610404E+10 | 0.982303E+10 | 0.299152E+11 | 0.563222E+10 |
Minimum of Months | 0.101756E+10 | 0.365677E+09 | 0.578874E+09 | 0.154275E+10 | 0.119630E+09 |
Maximum of Months | 0.168788E+10 | 0.781541E+09 | 0.103985E+10 | 0.323095E+10 | 0.102328E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.235205E+09 | 0.00 | 0.235205E+09 | 0.257488E+09 | 0.583918E+09 |
February | 0.251460E+09 | 0.00 | 0.251460E+09 | 0.354983E+09 | 0.425849E+09 |
March | 0.332015E+09 | 0.00 | 0.332015E+09 | 0.476587E+09 | 0.378352E+09 |
April | 0.360037E+09 | 1617325.81 | 0.358420E+09 | 0.639367E+09 | 0.227196E+09 |
May | 0.424849E+09 | 19004464.85 | 0.405844E+09 | 0.901266E+09 | 0.119430E+09 |
June | 0.439190E+09 | 31622990.76 | 0.407567E+09 | 0.100421E+10 | 50408934.98 |
July | 0.459260E+09 | 22504622.63 | 0.436755E+09 | 0.109537E+10 | 80531333.64 |
August | 0.406451E+09 | 3738235.55 | 0.402713E+09 | 0.916991E+09 | 56321788.08 |
September | 0.348940E+09 | 27604.44 | 0.348913E+09 | 0.818409E+09 | 93822139.50 |
October | 0.302071E+09 | 0.00 | 0.302071E+09 | 0.622928E+09 | 0.155643E+09 |
November | 0.254180E+09 | 0.00 | 0.254180E+09 | 0.423832E+09 | 0.294369E+09 |
December | 0.232647E+09 | 0.00 | 0.232647E+09 | 0.290143E+09 | 0.496900E+09 |
Annual Sum or Average | 0.404630E+10 | 78515244.04 | 0.396779E+10 | 0.780157E+10 | 0.296274E+10 |
Minimum of Months | 0.232647E+09 | 0.00 | 0.232647E+09 | 0.257488E+09 | 50408934.98 |
Maximum of Months | 0.459260E+09 | 31622990.76 | 0.436755E+09 | 0.109537E+10 | 0.583918E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.235220E+09 | 0.00 | 0.235220E+09 | 0.257504E+09 | 0.583955E+09 |
February | 0.251476E+09 | 0.00 | 0.251476E+09 | 0.355006E+09 | 0.425876E+09 |
March | 0.332036E+09 | 0.00 | 0.332036E+09 | 0.476617E+09 | 0.378376E+09 |
April | 0.360060E+09 | 1617428.02 | 0.358442E+09 | 0.639407E+09 | 0.227211E+09 |
May | 0.424876E+09 | 19005665.90 | 0.405870E+09 | 0.901323E+09 | 0.119438E+09 |
June | 0.439218E+09 | 31624989.28 | 0.407593E+09 | 0.100427E+10 | 50412120.74 |
July | 0.459289E+09 | 22506044.89 | 0.436783E+09 | 0.109544E+10 | 80536423.09 |
August | 0.406477E+09 | 3738471.80 | 0.402739E+09 | 0.917049E+09 | 56325347.52 |
September | 0.348962E+09 | 27606.18 | 0.348935E+09 | 0.818461E+09 | 93828068.90 |
October | 0.302090E+09 | 0.00 | 0.302090E+09 | 0.622968E+09 | 0.155653E+09 |
November | 0.254196E+09 | 0.00 | 0.254196E+09 | 0.423859E+09 | 0.294387E+09 |
December | 0.232662E+09 | 0.00 | 0.232662E+09 | 0.290161E+09 | 0.496932E+09 |
Annual Sum or Average | 0.404656E+10 | 78520206.08 | 0.396804E+10 | 0.780207E+10 | 0.296293E+10 |
Minimum of Months | 0.232662E+09 | 0.00 | 0.232662E+09 | 0.257504E+09 | 50412120.74 |
Maximum of Months | 0.459289E+09 | 31624989.28 | 0.436783E+09 | 0.109544E+10 | 0.583955E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.235220E+09 | 0.00 | 0.235220E+09 | 0.257504E+09 | 0.583955E+09 |
February | 0.251476E+09 | 0.00 | 0.251476E+09 | 0.355006E+09 | 0.425876E+09 |
March | 0.332036E+09 | 0.00 | 0.332036E+09 | 0.476617E+09 | 0.378376E+09 |
April | 0.360060E+09 | 1617428.02 | 0.358442E+09 | 0.639407E+09 | 0.227211E+09 |
May | 0.424876E+09 | 19005665.90 | 0.405870E+09 | 0.901323E+09 | 0.119438E+09 |
June | 0.439218E+09 | 31624989.28 | 0.407593E+09 | 0.100427E+10 | 50412120.74 |
July | 0.459289E+09 | 22506044.89 | 0.436783E+09 | 0.109544E+10 | 80536423.09 |
August | 0.406477E+09 | 3738471.80 | 0.402739E+09 | 0.917049E+09 | 56325347.52 |
September | 0.348962E+09 | 27606.18 | 0.348935E+09 | 0.818461E+09 | 93828068.90 |
October | 0.302090E+09 | 0.00 | 0.302090E+09 | 0.622968E+09 | 0.155653E+09 |
November | 0.254196E+09 | 0.00 | 0.254196E+09 | 0.423859E+09 | 0.294387E+09 |
December | 0.232662E+09 | 0.00 | 0.232662E+09 | 0.290161E+09 | 0.496932E+09 |
Annual Sum or Average | 0.404656E+10 | 78520206.08 | 0.396804E+10 | 0.780207E+10 | 0.296293E+10 |
Minimum of Months | 0.232662E+09 | 0.00 | 0.232662E+09 | 0.257504E+09 | 50412120.74 |
Maximum of Months | 0.459289E+09 | 31624989.28 | 0.436783E+09 | 0.109544E+10 | 0.583955E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108962E+10 | 0.521993E+09 | 0.567627E+09 | 0.158114E+10 | 0.108773E+10 |
February | 0.113639E+10 | 0.526037E+09 | 0.610358E+09 | 0.180442E+10 | 0.797456E+09 |
March | 0.153611E+10 | 0.726202E+09 | 0.809905E+09 | 0.245817E+10 | 0.706911E+09 |
April | 0.161329E+10 | 0.719838E+09 | 0.893451E+09 | 0.289000E+10 | 0.465426E+09 |
May | 0.157711E+10 | 0.628039E+09 | 0.949072E+09 | 0.309130E+10 | 0.237793E+09 |
June | 0.150642E+10 | 0.578602E+09 | 0.927817E+09 | 0.310282E+10 | 0.104231E+09 |
July | 0.159946E+10 | 0.576794E+09 | 0.102266E+10 | 0.339816E+10 | 0.171210E+09 |
August | 0.146256E+10 | 0.489047E+09 | 0.973516E+09 | 0.300974E+10 | 0.117937E+09 |
September | 0.136452E+10 | 0.493277E+09 | 0.871244E+09 | 0.284453E+10 | 0.192381E+09 |
October | 0.129785E+10 | 0.558932E+09 | 0.738921E+09 | 0.250983E+10 | 0.316646E+09 |
November | 0.101940E+10 | 0.406471E+09 | 0.612926E+09 | 0.176206E+10 | 0.551647E+09 |
December | 0.850901E+09 | 0.300407E+09 | 0.550493E+09 | 0.126743E+10 | 0.936448E+09 |
Annual Sum or Average | 0.160536E+11 | 0.652564E+10 | 0.952799E+10 | 0.297196E+11 | 0.568582E+10 |
Minimum of Months | 0.850901E+09 | 0.300407E+09 | 0.550493E+09 | 0.126743E+10 | 0.104231E+09 |
Maximum of Months | 0.161329E+10 | 0.726202E+09 | 0.102266E+10 | 0.339816E+10 | 0.108773E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 43082607.93 | 20639133.49 | 22443474.44 | 62516711.19 | 43008021.26 |
February | 44932024.40 | 20799013.87 | 24133010.53 | 71345015.99 | 31530710.22 |
March | 60736276.27 | 28713356.61 | 32022919.65 | 97193979.64 | 27950612.32 |
April | 63787996.33 | 28461760.40 | 35326235.93 | 0.114268E+09 | 18402540.11 |
May | 62357528.58 | 24832080.32 | 37525448.26 | 0.122227E+09 | 9402127.44 |
June | 59562457.55 | 22877406.23 | 36685051.31 | 0.122683E+09 | 4121207.72 |
July | 63241050.20 | 22805900.03 | 40435150.17 | 0.134360E+09 | 6769496.97 |
August | 57828463.28 | 19336497.66 | 38491965.62 | 0.119002E+09 | 4663141.84 |
September | 53951956.05 | 19503739.54 | 34448216.51 | 0.112470E+09 | 7606575.63 |
October | 51315915.13 | 22099657.39 | 29216257.73 | 99236562.30 | 12519884.03 |
November | 40306075.43 | 16071515.19 | 24234560.24 | 69670170.55 | 21811625.14 |
December | 33643842.11 | 11877837.65 | 21766004.47 | 50112954.23 | 37026327.56 |
Annual Sum or Average | 0.634746E+09 | 0.258018E+09 | 0.376728E+09 | 0.117509E+10 | 0.224812E+09 |
Minimum of Months | 33643842.11 | 11877837.65 | 21766004.47 | 50112954.23 | 4121207.72 |
Maximum of Months | 63787996.33 | 28713356.61 | 40435150.17 | 0.134360E+09 | 43008021.26 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110552E+10 | 0.718231E+09 | 0.387288E+09 | 0.179015E+10 | 0.591004E+09 |
February | 0.903320E+09 | 0.522682E+09 | 0.380638E+09 | 0.155188E+10 | 0.441361E+09 |
March | 0.767853E+09 | 0.324642E+09 | 0.443211E+09 | 0.134958E+10 | 0.386582E+09 |
April | 0.505283E+09 | 88607141.84 | 0.416676E+09 | 0.982426E+09 | 0.242268E+09 |
May | 0.418399E+09 | 9051972.29 | 0.409347E+09 | 0.888165E+09 | 0.118254E+09 |
June | 0.386040E+09 | 728521.39 | 0.385311E+09 | 0.884227E+09 | 51421586.75 |
July | 0.427122E+09 | 3959045.38 | 0.423163E+09 | 0.101826E+10 | 81671509.84 |
August | 0.484770E+09 | 40907501.38 | 0.443862E+09 | 0.108962E+10 | 60600102.93 |
September | 0.600551E+09 | 0.147166E+09 | 0.453385E+09 | 0.133634E+10 | 0.104881E+09 |
October | 0.853407E+09 | 0.400392E+09 | 0.453015E+09 | 0.168303E+10 | 0.187644E+09 |
November | 0.939667E+09 | 0.524438E+09 | 0.415229E+09 | 0.166973E+10 | 0.316597E+09 |
December | 0.106541E+10 | 0.672001E+09 | 0.393410E+09 | 0.176869E+10 | 0.515079E+09 |
Annual Sum or Average | 0.845734E+10 | 0.345281E+10 | 0.500453E+10 | 0.160121E+11 | 0.309736E+10 |
Minimum of Months | 0.386040E+09 | 728521.39 | 0.380638E+09 | 0.884227E+09 | 51421586.75 |
Maximum of Months | 0.110552E+10 | 0.718231E+09 | 0.453385E+09 | 0.179015E+10 | 0.591004E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110552E+10 | 0.718231E+09 | 0.387288E+09 | 0.179015E+10 | 0.591004E+09 |
February | 0.903320E+09 | 0.522682E+09 | 0.380638E+09 | 0.155188E+10 | 0.441361E+09 |
March | 0.767853E+09 | 0.324642E+09 | 0.443211E+09 | 0.134958E+10 | 0.386582E+09 |
April | 0.505283E+09 | 88607141.84 | 0.416676E+09 | 0.982426E+09 | 0.242268E+09 |
May | 0.418399E+09 | 9051972.29 | 0.409347E+09 | 0.888165E+09 | 0.118254E+09 |
June | 0.386040E+09 | 728521.39 | 0.385311E+09 | 0.884227E+09 | 51421586.75 |
July | 0.427122E+09 | 3959045.38 | 0.423163E+09 | 0.101826E+10 | 81671509.84 |
August | 0.484770E+09 | 40907501.38 | 0.443862E+09 | 0.108962E+10 | 60600102.93 |
September | 0.600551E+09 | 0.147166E+09 | 0.453385E+09 | 0.133634E+10 | 0.104881E+09 |
October | 0.853407E+09 | 0.400392E+09 | 0.453015E+09 | 0.168303E+10 | 0.187644E+09 |
November | 0.939667E+09 | 0.524438E+09 | 0.415229E+09 | 0.166973E+10 | 0.316597E+09 |
December | 0.106541E+10 | 0.672001E+09 | 0.393410E+09 | 0.176869E+10 | 0.515079E+09 |
Annual Sum or Average | 0.845734E+10 | 0.345281E+10 | 0.500453E+10 | 0.160121E+11 | 0.309736E+10 |
Minimum of Months | 0.386040E+09 | 728521.39 | 0.380638E+09 | 0.884227E+09 | 51421586.75 |
Maximum of Months | 0.110552E+10 | 0.718231E+09 | 0.453385E+09 | 0.179015E+10 | 0.591004E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.110545E+10 | 0.718185E+09 | 0.387263E+09 | 0.179004E+10 | 0.590967E+09 |
February | 0.903263E+09 | 0.522648E+09 | 0.380614E+09 | 0.155178E+10 | 0.441334E+09 |
March | 0.767804E+09 | 0.324621E+09 | 0.443183E+09 | 0.134950E+10 | 0.386557E+09 |
April | 0.505251E+09 | 88601542.37 | 0.416650E+09 | 0.982364E+09 | 0.242253E+09 |
May | 0.418373E+09 | 9051400.25 | 0.409322E+09 | 0.888109E+09 | 0.118246E+09 |
June | 0.386015E+09 | 728475.35 | 0.385287E+09 | 0.884172E+09 | 51418337.20 |
July | 0.427095E+09 | 3958795.19 | 0.423136E+09 | 0.101820E+10 | 81666348.66 |
August | 0.484739E+09 | 40904916.26 | 0.443834E+09 | 0.108955E+10 | 60596273.35 |
September | 0.600513E+09 | 0.147157E+09 | 0.453356E+09 | 0.133625E+10 | 0.104875E+09 |
October | 0.853353E+09 | 0.400367E+09 | 0.452986E+09 | 0.168292E+10 | 0.187632E+09 |
November | 0.939608E+09 | 0.524405E+09 | 0.415203E+09 | 0.166963E+10 | 0.316577E+09 |
December | 0.106534E+10 | 0.671958E+09 | 0.393385E+09 | 0.176858E+10 | 0.515046E+09 |
Annual Sum or Average | 0.845681E+10 | 0.345259E+10 | 0.500422E+10 | 0.160111E+11 | 0.309717E+10 |
Minimum of Months | 0.386015E+09 | 728475.35 | 0.380614E+09 | 0.884172E+09 | 51418337.20 |
Maximum of Months | 0.110545E+10 | 0.718185E+09 | 0.453356E+09 | 0.179004E+10 | 0.590967E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.978846E+09 | 0.421993E+09 | 0.556854E+09 | 0.144994E+10 | 0.115145E+10 |
February | 0.110557E+10 | 0.500330E+09 | 0.605237E+09 | 0.182512E+10 | 0.865850E+09 |
March | 0.152428E+10 | 0.696063E+09 | 0.828217E+09 | 0.252819E+10 | 0.790118E+09 |
April | 0.162367E+10 | 0.751807E+09 | 0.871860E+09 | 0.293939E+10 | 0.506735E+09 |
May | 0.152952E+10 | 0.588792E+09 | 0.940732E+09 | 0.303147E+10 | 0.271977E+09 |
June | 0.125417E+10 | 0.351804E+09 | 0.902366E+09 | 0.265044E+10 | 0.114871E+09 |
July | 0.144837E+10 | 0.448078E+09 | 0.100029E+10 | 0.313055E+10 | 0.182135E+09 |
August | 0.144508E+10 | 0.470945E+09 | 0.974130E+09 | 0.297999E+10 | 0.135495E+09 |
September | 0.119296E+10 | 0.351765E+09 | 0.841197E+09 | 0.253477E+10 | 0.201545E+09 |
October | 0.122634E+10 | 0.478061E+09 | 0.748274E+09 | 0.239808E+10 | 0.345767E+09 |
November | 0.978966E+09 | 0.359089E+09 | 0.619877E+09 | 0.173791E+10 | 0.602083E+09 |
December | 0.101341E+10 | 0.453085E+09 | 0.560323E+09 | 0.159662E+10 | 0.986394E+09 |
Annual Sum or Average | 0.153212E+11 | 0.587181E+10 | 0.944936E+10 | 0.288025E+11 | 0.615442E+10 |
Minimum of Months | 0.978846E+09 | 0.351765E+09 | 0.556854E+09 | 0.144994E+10 | 0.114871E+09 |
Maximum of Months | 0.162367E+10 | 0.751807E+09 | 0.100029E+10 | 0.313055E+10 | 0.115145E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 38702592.59 | 16685150.37 | 22017442.22 | 57329104.99 | 45527256.64 |
February | 43713004.00 | 19782531.41 | 23930472.59 | 72163272.36 | 34234907.83 |
March | 60268509.44 | 27521619.53 | 32746889.91 | 99962145.67 | 31240528.19 |
April | 64198186.84 | 29725692.95 | 34472493.89 | 0.116221E+09 | 20035823.23 |
May | 60475831.89 | 23280236.02 | 37195595.87 | 0.119861E+09 | 10753715.99 |
June | 49588650.15 | 13909975.94 | 35678674.21 | 0.104796E+09 | 4541897.47 |
July | 57267110.83 | 17716544.51 | 39550566.31 | 0.123779E+09 | 7201446.78 |
August | 57136847.33 | 18620697.35 | 38516149.99 | 0.117826E+09 | 5357339.12 |
September | 47168516.07 | 13908419.27 | 33260096.81 | 0.100222E+09 | 7968892.68 |
October | 48488061.51 | 18902044.66 | 29586016.85 | 94817851.57 | 13671272.40 |
November | 38707331.76 | 14197998.40 | 24509333.36 | 68715194.00 | 23805773.13 |
December | 40069125.42 | 17914518.48 | 22154606.94 | 63128615.12 | 39001088.31 |
Annual Sum or Average | 0.605784E+09 | 0.232165E+09 | 0.373618E+09 | 0.113882E+10 | 0.243340E+09 |
Minimum of Months | 38702592.59 | 13908419.27 | 22017442.22 | 57329104.99 | 4541897.47 |
Maximum of Months | 64198186.84 | 29725692.95 | 39550566.31 | 0.123779E+09 | 45527256.64 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.705648E+09 | 0.00 | 0.705648E+09 | 0.779554E+09 | 0.169748E+10 |
February | 0.754417E+09 | 0.00 | 0.754417E+09 | 0.105877E+10 | 0.126428E+10 |
March | 0.996092E+09 | 0.00 | 0.996092E+09 | 0.139759E+10 | 0.116091E+10 |
April | 0.108016E+10 | 4852206.98 | 0.107531E+10 | 0.188472E+10 | 0.713830E+09 |
May | 0.127461E+10 | 57016092.10 | 0.121759E+10 | 0.268062E+10 | 0.376541E+09 |
June | 0.131763E+10 | 94873460.95 | 0.122276E+10 | 0.299339E+10 | 0.161218E+09 |
July | 0.137784E+10 | 67517062.26 | 0.131033E+10 | 0.328095E+10 | 0.244320E+09 |
August | 0.121941E+10 | 11215237.28 | 0.120820E+10 | 0.276493E+10 | 0.160775E+09 |
September | 0.104687E+10 | 82817.23 | 0.104679E+10 | 0.246986E+10 | 0.269392E+09 |
October | 0.906255E+09 | 0.00 | 0.906255E+09 | 0.188054E+10 | 0.444868E+09 |
November | 0.762575E+09 | 0.00 | 0.762575E+09 | 0.128291E+10 | 0.842761E+09 |
December | 0.697974E+09 | 0.00 | 0.697974E+09 | 0.884508E+09 | 0.142508E+10 |
Annual Sum or Average | 0.121395E+11 | 0.235557E+09 | 0.119039E+11 | 0.233583E+11 | 0.876145E+10 |
Minimum of Months | 0.697974E+09 | 0.00 | 0.697974E+09 | 0.779554E+09 | 0.160775E+09 |
Maximum of Months | 0.137784E+10 | 94873460.95 | 0.131033E+10 | 0.328095E+10 | 0.169748E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113271E+10 | 0.542638E+09 | 0.590074E+09 | 0.165298E+10 | 0.105805E+10 |
February | 0.118134E+10 | 0.546841E+09 | 0.634495E+09 | 0.187236E+10 | 0.789309E+09 |
March | 0.159686E+10 | 0.754923E+09 | 0.841933E+09 | 0.253493E+10 | 0.713957E+09 |
April | 0.167709E+10 | 0.748308E+09 | 0.928782E+09 | 0.298159E+10 | 0.474106E+09 |
May | 0.163948E+10 | 0.652877E+09 | 0.986603E+09 | 0.319728E+10 | 0.242294E+09 |
June | 0.156599E+10 | 0.601486E+09 | 0.964508E+09 | 0.321833E+10 | 0.105861E+09 |
July | 0.166271E+10 | 0.599606E+09 | 0.106310E+10 | 0.353324E+10 | 0.165911E+09 |
August | 0.152040E+10 | 0.508389E+09 | 0.101201E+10 | 0.314288E+10 | 0.105331E+09 |
September | 0.141848E+10 | 0.512786E+09 | 0.905698E+09 | 0.297208E+10 | 0.180288E+09 |
October | 0.134918E+10 | 0.581037E+09 | 0.768141E+09 | 0.261732E+10 | 0.292584E+09 |
November | 0.105971E+10 | 0.422547E+09 | 0.637165E+09 | 0.184010E+10 | 0.527086E+09 |
December | 0.884551E+09 | 0.312288E+09 | 0.572263E+09 | 0.133116E+10 | 0.904269E+09 |
Annual Sum or Average | 0.166885E+11 | 0.678373E+10 | 0.990478E+10 | 0.308943E+11 | 0.555905E+10 |
Minimum of Months | 0.884551E+09 | 0.312288E+09 | 0.572263E+09 | 0.133116E+10 | 0.105331E+09 |
Maximum of Months | 0.167709E+10 | 0.754923E+09 | 0.106310E+10 | 0.353324E+10 | 0.105805E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.331645E+10 | 0.215462E+10 | 0.116183E+10 | 0.535384E+10 | 0.165153E+10 |
February | 0.270988E+10 | 0.156799E+10 | 0.114188E+10 | 0.463078E+10 | 0.125549E+10 |
March | 0.230349E+10 | 0.973894E+09 | 0.132960E+10 | 0.399705E+10 | 0.114862E+10 |
April | 0.151581E+10 | 0.265813E+09 | 0.124999E+10 | 0.291331E+10 | 0.742150E+09 |
May | 0.125516E+10 | 27155028.65 | 0.122801E+10 | 0.265326E+10 | 0.368940E+09 |
June | 0.115809E+10 | 2185492.69 | 0.115590E+10 | 0.265022E+10 | 0.164298E+09 |
July | 0.128133E+10 | 11876747.67 | 0.126945E+10 | 0.307225E+10 | 0.243984E+09 |
August | 0.145427E+10 | 0.122718E+09 | 0.133155E+10 | 0.331098E+10 | 0.163301E+09 |
September | 0.180160E+10 | 0.441485E+09 | 0.136012E+10 | 0.405765E+10 | 0.283916E+09 |
October | 0.256014E+10 | 0.120114E+10 | 0.135901E+10 | 0.508203E+10 | 0.488683E+09 |
November | 0.281891E+10 | 0.157326E+10 | 0.124565E+10 | 0.501422E+10 | 0.856532E+09 |
December | 0.319613E+10 | 0.201594E+10 | 0.118020E+10 | 0.529042E+10 | 0.143334E+10 |
Annual Sum or Average | 0.253713E+11 | 0.103581E+11 | 0.150132E+11 | 0.480260E+11 | 0.880078E+10 |
Minimum of Months | 0.115809E+10 | 2185492.69 | 0.114188E+10 | 0.265022E+10 | 0.163301E+09 |
Maximum of Months | 0.331645E+10 | 0.215462E+10 | 0.136012E+10 | 0.535384E+10 | 0.165153E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101756E+10 | 0.438682E+09 | 0.578874E+09 | 0.151752E+10 | 0.112823E+10 |
February | 0.114929E+10 | 0.520118E+09 | 0.629171E+09 | 0.189720E+10 | 0.862733E+09 |
March | 0.158456E+10 | 0.723592E+09 | 0.860969E+09 | 0.261326E+10 | 0.801904E+09 |
April | 0.168788E+10 | 0.781541E+09 | 0.906338E+09 | 0.303968E+10 | 0.520364E+09 |
May | 0.159001E+10 | 0.612079E+09 | 0.977933E+09 | 0.313952E+10 | 0.278983E+09 |
June | 0.130377E+10 | 0.365718E+09 | 0.938050E+09 | 0.274865E+10 | 0.120115E+09 |
July | 0.150565E+10 | 0.465799E+09 | 0.103985E+10 | 0.325661E+10 | 0.178681E+09 |
August | 0.150222E+10 | 0.489571E+09 | 0.101265E+10 | 0.311010E+10 | 0.122495E+09 |
September | 0.124014E+10 | 0.365677E+09 | 0.874462E+09 | 0.264896E+10 | 0.189671E+09 |
October | 0.127483E+10 | 0.496968E+09 | 0.777865E+09 | 0.250250E+10 | 0.325279E+09 |
November | 0.101768E+10 | 0.373290E+09 | 0.644391E+09 | 0.181574E+10 | 0.580195E+09 |
December | 0.105349E+10 | 0.471004E+09 | 0.582481E+09 | 0.167324E+10 | 0.953809E+09 |
Annual Sum or Average | 0.159271E+11 | 0.610404E+10 | 0.982303E+10 | 0.299630E+11 | 0.606246E+10 |
Minimum of Months | 0.101756E+10 | 0.365677E+09 | 0.578874E+09 | 0.151752E+10 | 0.120115E+09 |
Maximum of Months | 0.168788E+10 | 0.781541E+09 | 0.103985E+10 | 0.325661E+10 | 0.112823E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 304.51 | 574.07 | 263.46 | 0.00 | 263.46 | 0.00 | 0.00 |
February | 445.56 | 479.63 | 311.85 | 0.00 | 311.85 | 0.00 | 0.00 |
March | 523.66 | 402.92 | 371.90 | 0.00 | 371.90 | 0.00 | 0.00 |
April | 721.26 | 262.32 | 416.73 | 1.87 | 414.86 | 0.00 | 0.00 |
May | 990.03 | 137.27 | 475.88 | 21.29 | 454.60 | 0.00 | 0.00 |
June | 1139.87 | 62.63 | 508.35 | 36.60 | 471.74 | 0.00 | 0.00 |
July | 1208.28 | 91.66 | 514.43 | 25.21 | 489.22 | 0.00 | 0.00 |
August | 1021.91 | 58.73 | 455.28 | 4.19 | 451.09 | 0.00 | 0.00 |
September | 940.86 | 100.10 | 403.89 | 0.03 | 403.85 | 0.00 | 0.00 |
October | 696.87 | 155.51 | 338.36 | 0.00 | 338.36 | 0.00 | 0.00 |
November | 498.63 | 296.00 | 294.20 | 0.00 | 294.20 | 0.00 | 0.00 |
December | 341.50 | 482.17 | 260.59 | 0.00 | 260.59 | 0.00 | 0.00 |
Annual Sum or Average | 737.49 | 257.63 | 384.94 | 7.47 | 377.47 | 0.00 | 0.00 |
Minimum of Months | 304.51 | 58.73 | 260.59 | 0.00 | 260.59 | 0.00 | 0.00 |
Maximum of Months | 1208.28 | 574.07 | 514.43 | 36.60 | 489.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 626.49 | 362.95 | 422.91 | 202.60 | 220.31 | 0.00 | 0.00 |
February | 778.53 | 302.64 | 488.32 | 226.04 | 262.27 | 0.00 | 0.00 |
March | 945.50 | 250.78 | 596.20 | 281.86 | 314.34 | 0.00 | 0.00 |
April | 1143.73 | 175.16 | 647.03 | 288.70 | 358.33 | 0.00 | 0.00 |
May | 1184.45 | 88.00 | 612.11 | 243.76 | 368.36 | 0.00 | 0.00 |
June | 1230.58 | 41.03 | 604.16 | 232.05 | 372.11 | 0.00 | 0.00 |
July | 1307.21 | 62.00 | 620.78 | 223.87 | 396.92 | 0.00 | 0.00 |
August | 1165.25 | 38.43 | 567.65 | 189.81 | 377.84 | 0.00 | 0.00 |
September | 1137.54 | 67.32 | 547.25 | 197.83 | 349.42 | 0.00 | 0.00 |
October | 972.12 | 102.95 | 503.73 | 216.93 | 286.79 | 0.00 | 0.00 |
November | 711.58 | 187.15 | 408.84 | 163.02 | 245.82 | 0.00 | 0.00 |
December | 504.08 | 309.02 | 330.25 | 116.60 | 213.66 | 0.00 | 0.00 |
Annual Sum or Average | 976.33 | 165.02 | 529.19 | 215.11 | 314.08 | 0.00 | 0.00 |
Minimum of Months | 504.08 | 38.43 | 330.25 | 116.60 | 213.66 | 0.00 | 0.00 |
Maximum of Months | 1307.21 | 362.95 | 647.03 | 288.70 | 396.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2009.40 | 568.68 | 1238.22 | 804.44 | 433.78 | 0.00 | 0.00 |
February | 1918.66 | 482.76 | 1120.15 | 648.15 | 472.01 | 0.00 | 0.00 |
March | 1490.76 | 402.56 | 860.02 | 363.61 | 496.41 | 0.00 | 0.00 |
April | 1115.93 | 273.46 | 584.80 | 102.55 | 482.25 | 0.00 | 0.00 |
May | 979.34 | 133.43 | 468.62 | 10.14 | 458.49 | 0.00 | 0.00 |
June | 1007.95 | 63.52 | 446.79 | 0.84 | 445.95 | 0.00 | 0.00 |
July | 1130.43 | 91.36 | 478.39 | 4.43 | 473.96 | 0.00 | 0.00 |
August | 1225.01 | 59.57 | 542.96 | 45.82 | 497.14 | 0.00 | 0.00 |
September | 1552.11 | 105.85 | 695.06 | 170.33 | 524.74 | 0.00 | 0.00 |
October | 1890.42 | 172.97 | 955.85 | 448.45 | 507.39 | 0.00 | 0.00 |
November | 1935.77 | 306.49 | 1087.54 | 606.97 | 480.58 | 0.00 | 0.00 |
December | 1981.62 | 493.89 | 1193.30 | 752.66 | 440.63 | 0.00 | 0.00 |
Annual Sum or Average | 1517.78 | 261.90 | 804.52 | 328.45 | 476.06 | 0.00 | 0.00 |
Minimum of Months | 979.34 | 59.57 | 446.79 | 0.84 | 433.78 | 0.00 | 0.00 |
Maximum of Months | 2009.40 | 568.68 | 1238.22 | 804.44 | 524.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 576.00 | 382.05 | 379.91 | 163.79 | 216.13 | 0.00 | 0.00 |
February | 789.71 | 328.21 | 475.07 | 215.00 | 260.07 | 0.00 | 0.00 |
March | 976.53 | 279.21 | 591.61 | 270.16 | 321.45 | 0.00 | 0.00 |
April | 1169.20 | 191.42 | 651.19 | 301.52 | 349.67 | 0.00 | 0.00 |
May | 1165.41 | 101.09 | 593.64 | 228.52 | 365.12 | 0.00 | 0.00 |
June | 1051.93 | 46.26 | 503.00 | 141.09 | 361.90 | 0.00 | 0.00 |
July | 1206.30 | 66.24 | 562.14 | 173.91 | 388.24 | 0.00 | 0.00 |
August | 1155.04 | 44.66 | 560.87 | 182.78 | 378.08 | 0.00 | 0.00 |
September | 1015.15 | 70.02 | 478.45 | 141.08 | 337.37 | 0.00 | 0.00 |
October | 931.43 | 113.90 | 475.97 | 185.55 | 290.42 | 0.00 | 0.00 |
November | 703.49 | 204.25 | 392.62 | 144.02 | 248.61 | 0.00 | 0.00 |
December | 632.38 | 323.81 | 393.33 | 175.85 | 217.47 | 0.00 | 0.00 |
Annual Sum or Average | 948.60 | 178.60 | 505.04 | 193.56 | 311.49 | 0.00 | 0.00 |
Minimum of Months | 576.00 | 44.66 | 379.91 | 141.08 | 216.13 | 0.00 | 0.00 |
Maximum of Months | 1206.30 | 382.05 | 651.19 | 301.52 | 388.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 288.42 | 654.06 | 263.46 | 0.00 | 263.46 | 0.00 | 0.00 |
February | 440.23 | 528.11 | 311.84 | 0.00 | 311.84 | 0.00 | 0.00 |
March | 533.83 | 423.80 | 371.90 | 0.00 | 371.90 | 0.00 | 0.00 |
April | 740.04 | 262.97 | 416.73 | 1.87 | 414.85 | 0.00 | 0.00 |
May | 1009.53 | 133.78 | 475.88 | 21.29 | 454.59 | 0.00 | 0.00 |
June | 1162.33 | 58.35 | 508.34 | 36.60 | 471.74 | 0.00 | 0.00 |
July | 1226.95 | 90.20 | 514.43 | 25.21 | 489.22 | 0.00 | 0.00 |
August | 1027.14 | 63.09 | 455.27 | 4.19 | 451.09 | 0.00 | 0.00 |
September | 947.27 | 108.60 | 403.88 | 0.03 | 403.85 | 0.00 | 0.00 |
October | 697.75 | 174.34 | 338.36 | 0.00 | 338.36 | 0.00 | 0.00 |
November | 490.57 | 340.72 | 294.20 | 0.00 | 294.20 | 0.00 | 0.00 |
December | 324.99 | 556.59 | 260.59 | 0.00 | 260.59 | 0.00 | 0.00 |
Annual Sum or Average | 742.19 | 281.86 | 384.94 | 7.47 | 377.47 | 0.00 | 0.00 |
Minimum of Months | 288.42 | 58.35 | 260.59 | 0.00 | 260.59 | 0.00 | 0.00 |
Maximum of Months | 1226.95 | 654.06 | 514.43 | 36.60 | 489.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 613.67 | 422.17 | 422.90 | 202.60 | 220.31 | 0.00 | 0.00 |
February | 775.36 | 342.67 | 488.31 | 226.04 | 262.27 | 0.00 | 0.00 |
March | 954.07 | 274.37 | 596.19 | 281.85 | 314.34 | 0.00 | 0.00 |
April | 1159.05 | 186.66 | 647.02 | 288.70 | 358.32 | 0.00 | 0.00 |
May | 1199.79 | 92.29 | 612.11 | 243.75 | 368.35 | 0.00 | 0.00 |
June | 1244.41 | 41.80 | 604.16 | 232.05 | 372.11 | 0.00 | 0.00 |
July | 1318.89 | 66.45 | 620.78 | 223.86 | 396.92 | 0.00 | 0.00 |
August | 1168.14 | 45.77 | 567.65 | 189.81 | 377.84 | 0.00 | 0.00 |
September | 1140.82 | 77.16 | 547.25 | 197.83 | 349.42 | 0.00 | 0.00 |
October | 974.12 | 122.90 | 503.72 | 216.93 | 286.79 | 0.00 | 0.00 |
November | 706.69 | 221.24 | 408.84 | 163.02 | 245.82 | 0.00 | 0.00 |
December | 491.91 | 363.45 | 330.25 | 116.59 | 213.66 | 0.00 | 0.00 |
Annual Sum or Average | 979.66 | 187.42 | 529.19 | 215.11 | 314.08 | 0.00 | 0.00 |
Minimum of Months | 491.91 | 41.80 | 330.25 | 116.59 | 213.66 | 0.00 | 0.00 |
Maximum of Months | 1318.89 | 422.17 | 647.02 | 288.70 | 396.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2005.05 | 661.95 | 1238.23 | 804.45 | 433.78 | 0.00 | 0.00 |
February | 1924.41 | 547.31 | 1120.16 | 648.15 | 472.01 | 0.00 | 0.00 |
March | 1511.60 | 432.99 | 860.03 | 363.61 | 496.42 | 0.00 | 0.00 |
April | 1137.04 | 280.40 | 584.81 | 102.55 | 482.25 | 0.00 | 0.00 |
May | 994.79 | 132.45 | 468.63 | 10.14 | 458.49 | 0.00 | 0.00 |
June | 1023.39 | 59.51 | 446.80 | 0.84 | 445.95 | 0.00 | 0.00 |
July | 1140.50 | 91.48 | 478.40 | 4.43 | 473.96 | 0.00 | 0.00 |
August | 1220.42 | 67.88 | 542.97 | 45.82 | 497.15 | 0.00 | 0.00 |
September | 1546.66 | 121.39 | 695.07 | 170.33 | 524.74 | 0.00 | 0.00 |
October | 1885.07 | 210.17 | 955.86 | 448.46 | 507.40 | 0.00 | 0.00 |
November | 1932.52 | 366.42 | 1087.55 | 606.98 | 480.58 | 0.00 | 0.00 |
December | 1981.01 | 576.91 | 1193.31 | 752.67 | 440.64 | 0.00 | 0.00 |
Annual Sum or Average | 1523.19 | 294.64 | 804.52 | 328.46 | 476.07 | 0.00 | 0.00 |
Minimum of Months | 994.79 | 59.51 | 446.80 | 0.84 | 433.78 | 0.00 | 0.00 |
Maximum of Months | 2005.05 | 661.95 | 1238.23 | 804.45 | 524.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 562.75 | 446.90 | 379.91 | 163.78 | 216.13 | 0.00 | 0.00 |
February | 784.26 | 372.06 | 475.07 | 214.99 | 260.07 | 0.00 | 0.00 |
March | 981.24 | 306.66 | 591.60 | 270.16 | 321.45 | 0.00 | 0.00 |
April | 1178.86 | 203.23 | 651.18 | 301.52 | 349.67 | 0.00 | 0.00 |
May | 1176.57 | 105.56 | 593.64 | 228.52 | 365.12 | 0.00 | 0.00 |
June | 1062.98 | 46.07 | 502.99 | 141.09 | 361.90 | 0.00 | 0.00 |
July | 1215.03 | 70.69 | 562.14 | 173.91 | 388.23 | 0.00 | 0.00 |
August | 1156.59 | 52.59 | 560.86 | 182.78 | 378.08 | 0.00 | 0.00 |
September | 1016.59 | 80.83 | 478.45 | 141.08 | 337.37 | 0.00 | 0.00 |
October | 930.74 | 134.20 | 475.96 | 185.54 | 290.42 | 0.00 | 0.00 |
November | 697.00 | 241.47 | 392.62 | 144.01 | 248.61 | 0.00 | 0.00 |
December | 619.68 | 382.84 | 393.32 | 175.85 | 217.47 | 0.00 | 0.00 |
Annual Sum or Average | 949.43 | 202.87 | 505.04 | 193.56 | 311.48 | 0.00 | 0.00 |
Minimum of Months | 562.75 | 46.07 | 379.91 | 141.08 | 216.13 | 0.00 | 0.00 |
Maximum of Months | 1215.03 | 446.90 | 651.18 | 301.52 | 388.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 291.05 | 633.77 | 263.46 | 0.00 | 263.46 | 0.00 | 0.00 |
February | 437.65 | 522.60 | 311.85 | 0.00 | 311.85 | 0.00 | 0.00 |
March | 521.80 | 433.43 | 371.90 | 0.00 | 371.90 | 0.00 | 0.00 |
April | 727.13 | 275.40 | 416.73 | 1.87 | 414.86 | 0.00 | 0.00 |
May | 1000.83 | 140.58 | 475.88 | 21.29 | 454.60 | 0.00 | 0.00 |
June | 1154.86 | 62.20 | 508.35 | 36.60 | 471.74 | 0.00 | 0.00 |
July | 1224.96 | 91.22 | 514.43 | 25.21 | 489.22 | 0.00 | 0.00 |
August | 1032.31 | 60.03 | 455.28 | 4.19 | 451.09 | 0.00 | 0.00 |
September | 952.88 | 103.93 | 403.89 | 0.03 | 403.85 | 0.00 | 0.00 |
October | 702.11 | 166.09 | 338.36 | 0.00 | 338.36 | 0.00 | 0.00 |
November | 494.95 | 325.14 | 294.20 | 0.00 | 294.20 | 0.00 | 0.00 |
December | 330.24 | 532.06 | 260.59 | 0.00 | 260.59 | 0.00 | 0.00 |
Annual Sum or Average | 740.69 | 277.82 | 384.94 | 7.47 | 377.47 | 0.00 | 0.00 |
Minimum of Months | 291.05 | 60.03 | 260.59 | 0.00 | 260.59 | 0.00 | 0.00 |
Maximum of Months | 1224.96 | 633.77 | 514.43 | 36.60 | 489.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 617.15 | 395.03 | 422.91 | 202.60 | 220.31 | 0.00 | 0.00 |
February | 773.96 | 326.27 | 488.32 | 226.04 | 262.27 | 0.00 | 0.00 |
March | 946.43 | 266.56 | 596.20 | 281.86 | 314.34 | 0.00 | 0.00 |
April | 1150.31 | 182.91 | 647.03 | 288.70 | 358.33 | 0.00 | 0.00 |
May | 1193.73 | 90.46 | 612.11 | 243.76 | 368.36 | 0.00 | 0.00 |
June | 1241.64 | 40.84 | 604.16 | 232.05 | 372.11 | 0.00 | 0.00 |
July | 1319.16 | 61.94 | 620.78 | 223.87 | 396.92 | 0.00 | 0.00 |
August | 1173.42 | 39.33 | 567.65 | 189.81 | 377.84 | 0.00 | 0.00 |
September | 1146.64 | 69.56 | 547.25 | 197.83 | 349.42 | 0.00 | 0.00 |
October | 977.20 | 109.24 | 503.73 | 216.93 | 286.79 | 0.00 | 0.00 |
November | 709.92 | 203.35 | 408.84 | 163.02 | 245.82 | 0.00 | 0.00 |
December | 497.00 | 337.62 | 330.25 | 116.60 | 213.66 | 0.00 | 0.00 |
Annual Sum or Average | 979.65 | 176.28 | 529.19 | 215.11 | 314.08 | 0.00 | 0.00 |
Minimum of Months | 497.00 | 39.33 | 330.25 | 116.60 | 213.66 | 0.00 | 0.00 |
Maximum of Months | 1319.16 | 395.03 | 647.03 | 288.70 | 396.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1998.89 | 616.61 | 1238.22 | 804.44 | 433.78 | 0.00 | 0.00 |
February | 1914.18 | 518.97 | 1120.15 | 648.15 | 472.01 | 0.00 | 0.00 |
March | 1492.33 | 428.85 | 860.02 | 363.61 | 496.41 | 0.00 | 0.00 |
April | 1123.96 | 286.32 | 584.80 | 102.55 | 482.25 | 0.00 | 0.00 |
May | 990.61 | 137.75 | 468.62 | 10.14 | 458.49 | 0.00 | 0.00 |
June | 1022.46 | 63.39 | 446.79 | 0.84 | 445.95 | 0.00 | 0.00 |
July | 1147.05 | 91.09 | 478.39 | 4.43 | 473.96 | 0.00 | 0.00 |
August | 1236.18 | 60.97 | 542.96 | 45.82 | 497.14 | 0.00 | 0.00 |
September | 1565.45 | 109.54 | 695.06 | 170.33 | 524.74 | 0.00 | 0.00 |
October | 1897.41 | 182.45 | 955.85 | 448.45 | 507.39 | 0.00 | 0.00 |
November | 1934.50 | 330.45 | 1087.54 | 606.97 | 480.58 | 0.00 | 0.00 |
December | 1975.22 | 535.15 | 1193.30 | 752.66 | 440.63 | 0.00 | 0.00 |
Annual Sum or Average | 1522.90 | 279.07 | 804.52 | 328.45 | 476.06 | 0.00 | 0.00 |
Minimum of Months | 990.61 | 60.97 | 446.79 | 0.84 | 433.78 | 0.00 | 0.00 |
Maximum of Months | 1998.89 | 616.61 | 1238.22 | 804.44 | 524.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 566.58 | 421.23 | 379.91 | 163.79 | 216.13 | 0.00 | 0.00 |
February | 784.23 | 356.62 | 475.07 | 215.00 | 260.07 | 0.00 | 0.00 |
March | 975.68 | 299.40 | 591.61 | 270.16 | 321.45 | 0.00 | 0.00 |
April | 1172.72 | 200.76 | 651.19 | 301.52 | 349.67 | 0.00 | 0.00 |
May | 1172.16 | 104.16 | 593.64 | 228.52 | 365.12 | 0.00 | 0.00 |
June | 1060.43 | 46.34 | 503.00 | 141.09 | 361.90 | 0.00 | 0.00 |
July | 1215.88 | 66.71 | 562.14 | 173.91 | 388.24 | 0.00 | 0.00 |
August | 1161.18 | 45.73 | 560.87 | 182.78 | 378.08 | 0.00 | 0.00 |
September | 1021.98 | 73.18 | 478.45 | 141.08 | 337.37 | 0.00 | 0.00 |
October | 934.33 | 121.45 | 475.97 | 185.55 | 290.42 | 0.00 | 0.00 |
November | 700.52 | 223.84 | 392.62 | 144.02 | 248.61 | 0.00 | 0.00 |
December | 624.72 | 356.11 | 393.33 | 175.85 | 217.47 | 0.00 | 0.00 |
Annual Sum or Average | 950.12 | 192.24 | 505.04 | 193.56 | 311.49 | 0.00 | 0.00 |
Minimum of Months | 566.58 | 45.73 | 379.91 | 141.08 | 216.13 | 0.00 | 0.00 |
Maximum of Months | 1215.88 | 421.23 | 651.19 | 301.52 | 388.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.815599E+09 | 0.153758E+10 | 0.705648E+09 | 0.00 | 0.705648E+09 | 0.00 | 0.00 |
February | 0.107791E+10 | 0.116031E+10 | 0.754417E+09 | 0.00 | 0.754417E+09 | 0.00 | 0.00 |
March | 0.140256E+10 | 0.107918E+10 | 0.996092E+09 | 0.00 | 0.996092E+09 | 0.00 | 0.00 |
April | 0.186951E+10 | 0.679944E+09 | 0.108016E+10 | 4852206.98 | 0.107531E+10 | 0.00 | 0.00 |
May | 0.265169E+10 | 0.367675E+09 | 0.127461E+10 | 57016092.10 | 0.121759E+10 | 0.00 | 0.00 |
June | 0.295454E+10 | 0.162345E+09 | 0.131763E+10 | 94873460.95 | 0.122276E+10 | 0.00 | 0.00 |
July | 0.323626E+10 | 0.245500E+09 | 0.137784E+10 | 67517062.26 | 0.131033E+10 | 0.00 | 0.00 |
August | 0.273707E+10 | 0.157312E+09 | 0.121941E+10 | 11215237.28 | 0.120820E+10 | 0.00 | 0.00 |
September | 0.243872E+10 | 0.259454E+09 | 0.104687E+10 | 82817.23 | 0.104679E+10 | 0.00 | 0.00 |
October | 0.186650E+10 | 0.416505E+09 | 0.906255E+09 | 0.00 | 0.906255E+09 | 0.00 | 0.00 |
November | 0.129245E+10 | 0.767239E+09 | 0.762575E+09 | 0.00 | 0.762575E+09 | 0.00 | 0.00 |
December | 0.914684E+09 | 0.129145E+10 | 0.697974E+09 | 0.00 | 0.697974E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.232575E+11 | 0.812450E+10 | 0.121395E+11 | 0.235557E+09 | 0.119039E+11 | 0.00 | 0.00 |
Minimum of Months | 0.815599E+09 | 0.157312E+09 | 0.697974E+09 | 0.00 | 0.697974E+09 | 0.00 | 0.00 |
Maximum of Months | 0.323626E+10 | 0.153758E+10 | 0.137784E+10 | 94873460.95 | 0.131033E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.167799E+10 | 0.972137E+09 | 0.113271E+10 | 0.542638E+09 | 0.590074E+09 | 0.00 | 0.00 |
February | 0.188342E+10 | 0.732158E+09 | 0.118134E+10 | 0.546841E+09 | 0.634495E+09 | 0.00 | 0.00 |
March | 0.253244E+10 | 0.671685E+09 | 0.159686E+10 | 0.754923E+09 | 0.841933E+09 | 0.00 | 0.00 |
April | 0.296455E+10 | 0.454006E+09 | 0.167709E+10 | 0.748308E+09 | 0.928782E+09 | 0.00 | 0.00 |
May | 0.317243E+10 | 0.235688E+09 | 0.163948E+10 | 0.652877E+09 | 0.986603E+09 | 0.00 | 0.00 |
June | 0.318966E+10 | 0.106344E+09 | 0.156599E+10 | 0.601486E+09 | 0.964508E+09 | 0.00 | 0.00 |
July | 0.350124E+10 | 0.166062E+09 | 0.166271E+10 | 0.599606E+09 | 0.106310E+10 | 0.00 | 0.00 |
August | 0.312100E+10 | 0.102940E+09 | 0.152040E+10 | 0.508389E+09 | 0.101201E+10 | 0.00 | 0.00 |
September | 0.294851E+10 | 0.174486E+09 | 0.141848E+10 | 0.512786E+09 | 0.905698E+09 | 0.00 | 0.00 |
October | 0.260372E+10 | 0.275737E+09 | 0.134918E+10 | 0.581037E+09 | 0.768141E+09 | 0.00 | 0.00 |
November | 0.184440E+10 | 0.485087E+09 | 0.105971E+10 | 0.422547E+09 | 0.637165E+09 | 0.00 | 0.00 |
December | 0.135012E+10 | 0.827672E+09 | 0.884551E+09 | 0.312288E+09 | 0.572263E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.307895E+11 | 0.520400E+10 | 0.166885E+11 | 0.678373E+10 | 0.990478E+10 | 0.00 | 0.00 |
Minimum of Months | 0.135012E+10 | 0.102940E+09 | 0.884551E+09 | 0.312288E+09 | 0.572263E+09 | 0.00 | 0.00 |
Maximum of Months | 0.350124E+10 | 0.972137E+09 | 0.167709E+10 | 0.754923E+09 | 0.106310E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.538198E+10 | 0.152317E+10 | 0.331645E+10 | 0.215462E+10 | 0.116183E+10 | 0.00 | 0.00 |
February | 0.464162E+10 | 0.116790E+10 | 0.270988E+10 | 0.156799E+10 | 0.114188E+10 | 0.00 | 0.00 |
March | 0.399284E+10 | 0.107820E+10 | 0.230349E+10 | 0.973894E+09 | 0.132960E+10 | 0.00 | 0.00 |
April | 0.289249E+10 | 0.708803E+09 | 0.151581E+10 | 0.265813E+09 | 0.124999E+10 | 0.00 | 0.00 |
May | 0.262308E+10 | 0.357388E+09 | 0.125516E+10 | 27155028.65 | 0.122801E+10 | 0.00 | 0.00 |
June | 0.261260E+10 | 0.164657E+09 | 0.115809E+10 | 2185492.69 | 0.115590E+10 | 0.00 | 0.00 |
July | 0.302773E+10 | 0.244699E+09 | 0.128133E+10 | 11876747.67 | 0.126945E+10 | 0.00 | 0.00 |
August | 0.328106E+10 | 0.159542E+09 | 0.145427E+10 | 0.122718E+09 | 0.133155E+10 | 0.00 | 0.00 |
September | 0.402306E+10 | 0.274363E+09 | 0.180160E+10 | 0.441485E+09 | 0.136012E+10 | 0.00 | 0.00 |
October | 0.506330E+10 | 0.463292E+09 | 0.256014E+10 | 0.120114E+10 | 0.135901E+10 | 0.00 | 0.00 |
November | 0.501751E+10 | 0.794429E+09 | 0.281891E+10 | 0.157326E+10 | 0.124565E+10 | 0.00 | 0.00 |
December | 0.530758E+10 | 0.132282E+10 | 0.319613E+10 | 0.201594E+10 | 0.118020E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.478648E+11 | 0.825926E+10 | 0.253713E+11 | 0.103581E+11 | 0.150132E+11 | 0.00 | 0.00 |
Minimum of Months | 0.261260E+10 | 0.159542E+09 | 0.115809E+10 | 2185492.69 | 0.114188E+10 | 0.00 | 0.00 |
Maximum of Months | 0.538198E+10 | 0.152317E+10 | 0.331645E+10 | 0.215462E+10 | 0.136012E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.154275E+10 | 0.102328E+10 | 0.101756E+10 | 0.438682E+09 | 0.578874E+09 | 0.00 | 0.00 |
February | 0.191048E+10 | 0.794007E+09 | 0.114929E+10 | 0.520118E+09 | 0.629171E+09 | 0.00 | 0.00 |
March | 0.261553E+10 | 0.747831E+09 | 0.158456E+10 | 0.723592E+09 | 0.860969E+09 | 0.00 | 0.00 |
April | 0.303056E+10 | 0.496154E+09 | 0.168788E+10 | 0.781541E+09 | 0.906338E+09 | 0.00 | 0.00 |
May | 0.312143E+10 | 0.270753E+09 | 0.159001E+10 | 0.612079E+09 | 0.977933E+09 | 0.00 | 0.00 |
June | 0.272659E+10 | 0.119894E+09 | 0.130377E+10 | 0.365718E+09 | 0.938050E+09 | 0.00 | 0.00 |
July | 0.323095E+10 | 0.177413E+09 | 0.150565E+10 | 0.465799E+09 | 0.103985E+10 | 0.00 | 0.00 |
August | 0.309366E+10 | 0.119630E+09 | 0.150222E+10 | 0.489571E+09 | 0.101265E+10 | 0.00 | 0.00 |
September | 0.263127E+10 | 0.181494E+09 | 0.124014E+10 | 0.365677E+09 | 0.874462E+09 | 0.00 | 0.00 |
October | 0.249475E+10 | 0.305065E+09 | 0.127483E+10 | 0.496968E+09 | 0.777865E+09 | 0.00 | 0.00 |
November | 0.182345E+10 | 0.529418E+09 | 0.101768E+10 | 0.373290E+09 | 0.644391E+09 | 0.00 | 0.00 |
December | 0.169376E+10 | 0.867281E+09 | 0.105349E+10 | 0.471004E+09 | 0.582481E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.299152E+11 | 0.563222E+10 | 0.159271E+11 | 0.610404E+10 | 0.982303E+10 | 0.00 | 0.00 |
Minimum of Months | 0.154275E+10 | 0.119630E+09 | 0.101756E+10 | 0.365677E+09 | 0.578874E+09 | 0.00 | 0.00 |
Maximum of Months | 0.323095E+10 | 0.102328E+10 | 0.168788E+10 | 0.781541E+09 | 0.103985E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.772496E+09 | 0.175183E+10 | 0.705644E+09 | 0.00 | 0.705644E+09 | 0.00 | 0.00 |
February | 0.106500E+10 | 0.127760E+10 | 0.754413E+09 | 0.00 | 0.754413E+09 | 0.00 | 0.00 |
March | 0.142982E+10 | 0.113510E+10 | 0.996087E+09 | 0.00 | 0.996087E+09 | 0.00 | 0.00 |
April | 0.191818E+10 | 0.681618E+09 | 0.108016E+10 | 4852181.84 | 0.107530E+10 | 0.00 | 0.00 |
May | 0.270391E+10 | 0.358305E+09 | 0.127460E+10 | 57015796.66 | 0.121758E+10 | 0.00 | 0.00 |
June | 0.301275E+10 | 0.151233E+09 | 0.131763E+10 | 94872969.33 | 0.122275E+10 | 0.00 | 0.00 |
July | 0.328625E+10 | 0.241604E+09 | 0.137784E+10 | 67516712.40 | 0.131032E+10 | 0.00 | 0.00 |
August | 0.275109E+10 | 0.168972E+09 | 0.121941E+10 | 11215179.16 | 0.120819E+10 | 0.00 | 0.00 |
September | 0.245533E+10 | 0.281478E+09 | 0.104687E+10 | 82816.80 | 0.104678E+10 | 0.00 | 0.00 |
October | 0.186886E+10 | 0.466949E+09 | 0.906251E+09 | 0.00 | 0.906251E+09 | 0.00 | 0.00 |
November | 0.127155E+10 | 0.883144E+09 | 0.762571E+09 | 0.00 | 0.762571E+09 | 0.00 | 0.00 |
December | 0.870466E+09 | 0.149076E+10 | 0.697971E+09 | 0.00 | 0.697971E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.234057E+11 | 0.888860E+10 | 0.121394E+11 | 0.235556E+09 | 0.119039E+11 | 0.00 | 0.00 |
Minimum of Months | 0.772496E+09 | 0.151233E+09 | 0.697971E+09 | 0.00 | 0.697971E+09 | 0.00 | 0.00 |
Maximum of Months | 0.328625E+10 | 0.175183E+10 | 0.137784E+10 | 94872969.33 | 0.131032E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.164365E+10 | 0.113074E+10 | 0.113270E+10 | 0.542632E+09 | 0.590071E+09 | 0.00 | 0.00 |
February | 0.187576E+10 | 0.828987E+09 | 0.118133E+10 | 0.546836E+09 | 0.634491E+09 | 0.00 | 0.00 |
March | 0.255537E+10 | 0.734861E+09 | 0.159684E+10 | 0.754915E+09 | 0.841928E+09 | 0.00 | 0.00 |
April | 0.300427E+10 | 0.483829E+09 | 0.167708E+10 | 0.748300E+09 | 0.928777E+09 | 0.00 | 0.00 |
May | 0.321353E+10 | 0.247195E+09 | 0.163947E+10 | 0.652871E+09 | 0.986597E+09 | 0.00 | 0.00 |
June | 0.322551E+10 | 0.108352E+09 | 0.156598E+10 | 0.601480E+09 | 0.964502E+09 | 0.00 | 0.00 |
July | 0.353252E+10 | 0.177980E+09 | 0.166270E+10 | 0.599600E+09 | 0.106310E+10 | 0.00 | 0.00 |
August | 0.312874E+10 | 0.122601E+09 | 0.152039E+10 | 0.508384E+09 | 0.101201E+10 | 0.00 | 0.00 |
September | 0.295700E+10 | 0.199988E+09 | 0.141847E+10 | 0.512781E+09 | 0.905693E+09 | 0.00 | 0.00 |
October | 0.260907E+10 | 0.329166E+09 | 0.134917E+10 | 0.581031E+09 | 0.768137E+09 | 0.00 | 0.00 |
November | 0.183173E+10 | 0.573459E+09 | 0.105970E+10 | 0.422543E+09 | 0.637161E+09 | 0.00 | 0.00 |
December | 0.131754E+10 | 0.973475E+09 | 0.884544E+09 | 0.312285E+09 | 0.572259E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.308947E+11 | 0.591063E+10 | 0.166884E+11 | 0.678366E+10 | 0.990472E+10 | 0.00 | 0.00 |
Minimum of Months | 0.131754E+10 | 0.108352E+09 | 0.884544E+09 | 0.312285E+09 | 0.572259E+09 | 0.00 | 0.00 |
Maximum of Months | 0.353252E+10 | 0.113074E+10 | 0.167708E+10 | 0.754915E+09 | 0.106310E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.537034E+10 | 0.177298E+10 | 0.331649E+10 | 0.215465E+10 | 0.116184E+10 | 0.00 | 0.00 |
February | 0.465554E+10 | 0.132406E+10 | 0.270990E+10 | 0.156801E+10 | 0.114189E+10 | 0.00 | 0.00 |
March | 0.404866E+10 | 0.115972E+10 | 0.230351E+10 | 0.973905E+09 | 0.132960E+10 | 0.00 | 0.00 |
April | 0.294721E+10 | 0.726789E+09 | 0.151582E+10 | 0.265816E+09 | 0.125000E+10 | 0.00 | 0.00 |
May | 0.266444E+10 | 0.354754E+09 | 0.125517E+10 | 27155344.83 | 0.122802E+10 | 0.00 | 0.00 |
June | 0.265263E+10 | 0.154262E+09 | 0.115809E+10 | 2185518.13 | 0.115591E+10 | 0.00 | 0.00 |
July | 0.305473E+10 | 0.245009E+09 | 0.128134E+10 | 11876885.95 | 0.126946E+10 | 0.00 | 0.00 |
August | 0.326878E+10 | 0.181796E+09 | 0.145428E+10 | 0.122720E+09 | 0.133156E+10 | 0.00 | 0.00 |
September | 0.400893E+10 | 0.314638E+09 | 0.180162E+10 | 0.441490E+09 | 0.136013E+10 | 0.00 | 0.00 |
October | 0.504897E+10 | 0.562919E+09 | 0.256017E+10 | 0.120115E+10 | 0.135902E+10 | 0.00 | 0.00 |
November | 0.500910E+10 | 0.949772E+09 | 0.281894E+10 | 0.157328E+10 | 0.124566E+10 | 0.00 | 0.00 |
December | 0.530595E+10 | 0.154520E+10 | 0.319617E+10 | 0.201596E+10 | 0.118020E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.480353E+11 | 0.929189E+10 | 0.253715E+11 | 0.103582E+11 | 0.150133E+11 | 0.00 | 0.00 |
Minimum of Months | 0.265263E+10 | 0.154262E+09 | 0.115809E+10 | 2185518.13 | 0.114189E+10 | 0.00 | 0.00 |
Maximum of Months | 0.537034E+10 | 0.177298E+10 | 0.331649E+10 | 0.215465E+10 | 0.136013E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150727E+10 | 0.119698E+10 | 0.101755E+10 | 0.438678E+09 | 0.578871E+09 | 0.00 | 0.00 |
February | 0.189728E+10 | 0.900085E+09 | 0.114928E+10 | 0.520112E+09 | 0.629167E+09 | 0.00 | 0.00 |
March | 0.262815E+10 | 0.821359E+09 | 0.158455E+10 | 0.723585E+09 | 0.860964E+09 | 0.00 | 0.00 |
April | 0.305561E+10 | 0.526771E+09 | 0.168787E+10 | 0.781533E+09 | 0.906333E+09 | 0.00 | 0.00 |
May | 0.315133E+10 | 0.282731E+09 | 0.159000E+10 | 0.612072E+09 | 0.977927E+09 | 0.00 | 0.00 |
June | 0.275523E+10 | 0.119413E+09 | 0.130376E+10 | 0.365714E+09 | 0.938045E+09 | 0.00 | 0.00 |
July | 0.325433E+10 | 0.189337E+09 | 0.150564E+10 | 0.465795E+09 | 0.103984E+10 | 0.00 | 0.00 |
August | 0.309781E+10 | 0.140853E+09 | 0.150221E+10 | 0.489566E+09 | 0.101265E+10 | 0.00 | 0.00 |
September | 0.263499E+10 | 0.209514E+09 | 0.124013E+10 | 0.365673E+09 | 0.874457E+09 | 0.00 | 0.00 |
October | 0.249290E+10 | 0.359438E+09 | 0.127482E+10 | 0.496963E+09 | 0.777860E+09 | 0.00 | 0.00 |
November | 0.180662E+10 | 0.625888E+09 | 0.101767E+10 | 0.373287E+09 | 0.644387E+09 | 0.00 | 0.00 |
December | 0.165975E+10 | 0.102539E+10 | 0.105348E+10 | 0.471000E+09 | 0.582477E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.299413E+11 | 0.639776E+10 | 0.159270E+11 | 0.610398E+10 | 0.982298E+10 | 0.00 | 0.00 |
Minimum of Months | 0.150727E+10 | 0.119413E+09 | 0.101755E+10 | 0.365673E+09 | 0.578871E+09 | 0.00 | 0.00 |
Maximum of Months | 0.325433E+10 | 0.119698E+10 | 0.168787E+10 | 0.781533E+09 | 0.103984E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.779554E+09 | 0.169748E+10 | 0.705648E+09 | 0.00 | 0.705648E+09 | 0.00 | 0.00 |
February | 0.105877E+10 | 0.126428E+10 | 0.754417E+09 | 0.00 | 0.754417E+09 | 0.00 | 0.00 |
March | 0.139759E+10 | 0.116091E+10 | 0.996092E+09 | 0.00 | 0.996092E+09 | 0.00 | 0.00 |
April | 0.188472E+10 | 0.713830E+09 | 0.108016E+10 | 4852206.98 | 0.107531E+10 | 0.00 | 0.00 |
May | 0.268062E+10 | 0.376541E+09 | 0.127461E+10 | 57016092.10 | 0.121759E+10 | 0.00 | 0.00 |
June | 0.299339E+10 | 0.161218E+09 | 0.131763E+10 | 94873460.95 | 0.122276E+10 | 0.00 | 0.00 |
July | 0.328095E+10 | 0.244320E+09 | 0.137784E+10 | 67517062.26 | 0.131033E+10 | 0.00 | 0.00 |
August | 0.276493E+10 | 0.160775E+09 | 0.121941E+10 | 11215237.28 | 0.120820E+10 | 0.00 | 0.00 |
September | 0.246986E+10 | 0.269392E+09 | 0.104687E+10 | 82817.23 | 0.104679E+10 | 0.00 | 0.00 |
October | 0.188054E+10 | 0.444868E+09 | 0.906255E+09 | 0.00 | 0.906255E+09 | 0.00 | 0.00 |
November | 0.128291E+10 | 0.842761E+09 | 0.762575E+09 | 0.00 | 0.762575E+09 | 0.00 | 0.00 |
December | 0.884508E+09 | 0.142508E+10 | 0.697974E+09 | 0.00 | 0.697974E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.233583E+11 | 0.876145E+10 | 0.121395E+11 | 0.235557E+09 | 0.119039E+11 | 0.00 | 0.00 |
Minimum of Months | 0.779554E+09 | 0.160775E+09 | 0.697974E+09 | 0.00 | 0.697974E+09 | 0.00 | 0.00 |
Maximum of Months | 0.328095E+10 | 0.169748E+10 | 0.137784E+10 | 94873460.95 | 0.131033E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165298E+10 | 0.105805E+10 | 0.113271E+10 | 0.542638E+09 | 0.590074E+09 | 0.00 | 0.00 |
February | 0.187236E+10 | 0.789309E+09 | 0.118134E+10 | 0.546841E+09 | 0.634495E+09 | 0.00 | 0.00 |
March | 0.253493E+10 | 0.713957E+09 | 0.159686E+10 | 0.754923E+09 | 0.841933E+09 | 0.00 | 0.00 |
April | 0.298159E+10 | 0.474106E+09 | 0.167709E+10 | 0.748308E+09 | 0.928782E+09 | 0.00 | 0.00 |
May | 0.319728E+10 | 0.242294E+09 | 0.163948E+10 | 0.652877E+09 | 0.986603E+09 | 0.00 | 0.00 |
June | 0.321833E+10 | 0.105861E+09 | 0.156599E+10 | 0.601486E+09 | 0.964508E+09 | 0.00 | 0.00 |
July | 0.353324E+10 | 0.165911E+09 | 0.166271E+10 | 0.599606E+09 | 0.106310E+10 | 0.00 | 0.00 |
August | 0.314288E+10 | 0.105331E+09 | 0.152040E+10 | 0.508389E+09 | 0.101201E+10 | 0.00 | 0.00 |
September | 0.297208E+10 | 0.180288E+09 | 0.141848E+10 | 0.512786E+09 | 0.905698E+09 | 0.00 | 0.00 |
October | 0.261732E+10 | 0.292584E+09 | 0.134918E+10 | 0.581037E+09 | 0.768141E+09 | 0.00 | 0.00 |
November | 0.184010E+10 | 0.527086E+09 | 0.105971E+10 | 0.422547E+09 | 0.637165E+09 | 0.00 | 0.00 |
December | 0.133116E+10 | 0.904269E+09 | 0.884551E+09 | 0.312288E+09 | 0.572263E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.308943E+11 | 0.555905E+10 | 0.166885E+11 | 0.678373E+10 | 0.990478E+10 | 0.00 | 0.00 |
Minimum of Months | 0.133116E+10 | 0.105331E+09 | 0.884551E+09 | 0.312288E+09 | 0.572263E+09 | 0.00 | 0.00 |
Maximum of Months | 0.353324E+10 | 0.105805E+10 | 0.167709E+10 | 0.754923E+09 | 0.106310E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.535384E+10 | 0.165153E+10 | 0.331645E+10 | 0.215462E+10 | 0.116183E+10 | 0.00 | 0.00 |
February | 0.463078E+10 | 0.125549E+10 | 0.270988E+10 | 0.156799E+10 | 0.114188E+10 | 0.00 | 0.00 |
March | 0.399705E+10 | 0.114862E+10 | 0.230349E+10 | 0.973894E+09 | 0.132960E+10 | 0.00 | 0.00 |
April | 0.291331E+10 | 0.742150E+09 | 0.151581E+10 | 0.265813E+09 | 0.124999E+10 | 0.00 | 0.00 |
May | 0.265326E+10 | 0.368940E+09 | 0.125516E+10 | 27155028.65 | 0.122801E+10 | 0.00 | 0.00 |
June | 0.265022E+10 | 0.164298E+09 | 0.115809E+10 | 2185492.69 | 0.115590E+10 | 0.00 | 0.00 |
July | 0.307225E+10 | 0.243984E+09 | 0.128133E+10 | 11876747.67 | 0.126945E+10 | 0.00 | 0.00 |
August | 0.331098E+10 | 0.163301E+09 | 0.145427E+10 | 0.122718E+09 | 0.133155E+10 | 0.00 | 0.00 |
September | 0.405765E+10 | 0.283916E+09 | 0.180160E+10 | 0.441485E+09 | 0.136012E+10 | 0.00 | 0.00 |
October | 0.508203E+10 | 0.488683E+09 | 0.256014E+10 | 0.120114E+10 | 0.135901E+10 | 0.00 | 0.00 |
November | 0.501422E+10 | 0.856532E+09 | 0.281891E+10 | 0.157326E+10 | 0.124565E+10 | 0.00 | 0.00 |
December | 0.529042E+10 | 0.143334E+10 | 0.319613E+10 | 0.201594E+10 | 0.118020E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.480260E+11 | 0.880078E+10 | 0.253713E+11 | 0.103581E+11 | 0.150132E+11 | 0.00 | 0.00 |
Minimum of Months | 0.265022E+10 | 0.163301E+09 | 0.115809E+10 | 2185492.69 | 0.114188E+10 | 0.00 | 0.00 |
Maximum of Months | 0.535384E+10 | 0.165153E+10 | 0.331645E+10 | 0.215462E+10 | 0.136012E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.151752E+10 | 0.112823E+10 | 0.101756E+10 | 0.438682E+09 | 0.578874E+09 | 0.00 | 0.00 |
February | 0.189720E+10 | 0.862733E+09 | 0.114929E+10 | 0.520118E+09 | 0.629171E+09 | 0.00 | 0.00 |
March | 0.261326E+10 | 0.801904E+09 | 0.158456E+10 | 0.723592E+09 | 0.860969E+09 | 0.00 | 0.00 |
April | 0.303968E+10 | 0.520364E+09 | 0.168788E+10 | 0.781541E+09 | 0.906338E+09 | 0.00 | 0.00 |
May | 0.313952E+10 | 0.278983E+09 | 0.159001E+10 | 0.612079E+09 | 0.977933E+09 | 0.00 | 0.00 |
June | 0.274865E+10 | 0.120115E+09 | 0.130377E+10 | 0.365718E+09 | 0.938050E+09 | 0.00 | 0.00 |
July | 0.325661E+10 | 0.178681E+09 | 0.150565E+10 | 0.465799E+09 | 0.103985E+10 | 0.00 | 0.00 |
August | 0.311010E+10 | 0.122495E+09 | 0.150222E+10 | 0.489571E+09 | 0.101265E+10 | 0.00 | 0.00 |
September | 0.264896E+10 | 0.189671E+09 | 0.124014E+10 | 0.365677E+09 | 0.874462E+09 | 0.00 | 0.00 |
October | 0.250250E+10 | 0.325279E+09 | 0.127483E+10 | 0.496968E+09 | 0.777865E+09 | 0.00 | 0.00 |
November | 0.181574E+10 | 0.580195E+09 | 0.101768E+10 | 0.373290E+09 | 0.644391E+09 | 0.00 | 0.00 |
December | 0.167324E+10 | 0.953809E+09 | 0.105349E+10 | 0.471004E+09 | 0.582481E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.299630E+11 | 0.606246E+10 | 0.159271E+11 | 0.610404E+10 | 0.982303E+10 | 0.00 | 0.00 |
Minimum of Months | 0.151752E+10 | 0.120115E+09 | 0.101756E+10 | 0.365677E+09 | 0.578874E+09 | 0.00 | 0.00 |
Maximum of Months | 0.325661E+10 | 0.112823E+10 | 0.168788E+10 | 0.781541E+09 | 0.103985E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.42 | 15.96 | 13.59 | 3.30 | 9.49 | 57.21 | 169.93 | 0.03 |
February | 20.87 | 16.70 | 13.89 | 5.53 | 11.19 | 68.99 | 182.59 | 0.00 |
March | 21.57 | 17.63 | 15.09 | 5.59 | 12.13 | 85.97 | 199.13 | 0.00 |
April | 24.11 | 19.68 | 17.40 | 4.69 | 15.31 | 97.05 | 212.67 | 0.01 |
May | 26.41 | 22.40 | 20.67 | 5.05 | 18.50 | 110.67 | 177.92 | 0.00 |
June | 27.68 | 24.06 | 22.67 | 3.87 | 20.33 | 120.35 | 147.07 | 0.00 |
July | 28.13 | 24.25 | 22.77 | 2.86 | 20.30 | 124.71 | 163.26 | 0.00 |
August | 27.97 | 24.38 | 23.03 | 3.45 | 20.36 | 120.27 | 145.14 | 0.08 |
September | 27.49 | 23.91 | 22.56 | 3.39 | 20.13 | 107.67 | 134.94 | 0.00 |
October | 26.35 | 22.68 | 21.10 | 3.72 | 17.49 | 81.44 | 160.40 | 0.04 |
November | 23.59 | 20.24 | 18.46 | 4.39 | 14.74 | 70.67 | 140.11 | 0.00 |
December | 20.30 | 17.47 | 15.75 | 3.70 | 12.21 | 59.50 | 147.31 | 0.00 |
Annual Sum or Average | 24.51 | 20.80 | 18.94 | 4.12 | 16.04 | 92.16 | 164.97 | 0.01 |
Minimum of Months | 19.42 | 15.96 | 13.59 | 2.86 | 9.49 | 57.21 | 134.94 | 0.00 |
Maximum of Months | 28.13 | 24.38 | 23.03 | 5.59 | 20.36 | 124.71 | 212.67 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.90 | 02-JAN-14:20 | 24.35 | 22.57 | 2.37 | 19.46 | 142.33 | 666.50 |
February | 29.40 | 11-FEB-13:00 | 24.15 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 29.40 | 13-MAR-15:00 | 22.41 | 19.40 | 6.20 | 21.27 | 178.00 | 499.00 |
April | 32.20 | 17-APR-14:00 | 19.76 | 12.80 | 5.20 | 21.27 | 367.00 | 219.50 |
May | 34.40 | 22-MAY-12:00 | 23.24 | 18.30 | 5.70 | 25.99 | 382.50 | 457.50 |
June | 32.20 | 11-JUN-12:00 | 23.83 | 20.60 | 3.60 | 23.15 | 181.50 | 762.50 |
July | 35.60 | 29-JUL-15:00 | 24.39 | 20.00 | 3.60 | 25.66 | 281.50 | 374.50 |
August | 33.90 | 23-AUG-12:00 | 25.44 | 22.20 | 5.70 | 24.50 | 261.50 | 640.00 |
September | 32.20 | 08-SEP-14:00 | 23.42 | 20.00 | 2.10 | 21.61 | 221.50 | 576.00 |
October | 32.20 | 09-OCT-10:00 | 23.83 | 20.60 | 3.10 | 25.16 | 286.50 | 457.50 |
November | 30.00 | 17-NOV-14:00 | 22.20 | 18.90 | 4.10 | 19.35 | 178.50 | 412.50 |
December | 28.90 | 10-DEC-14:20 | 22.91 | 20.40 | 7.87 | 19.82 | 162.67 | 585.17 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.90 | 19.76 | 12.80 | 2.10 | 19.35 | 142.33 | 219.50 | |
Maximum of Months | 35.60 | 25.44 | 22.57 | 7.87 | 25.99 | 382.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 25-JAN-04:00 | 4.59 | -1.7 | 3.10 | -7.3 | 0.00 | 0.00 |
February | 5.00 | 04-FEB-06:00 | 1.99 | -2.8 | 5.70 | -11.9 | 0.00 | 0.00 |
March | 6.70 | 16-MAR-04:00 | 4.49 | 1.70 | 4.60 | -9.2 | 0.00 | 0.00 |
April | 14.40 | 02-APR-05:49 | 13.38 | 12.70 | 1.60 | 0.69 | 0.00 | 0.00 |
May | 20.60 | 01-MAY-04:00 | 19.45 | 18.90 | 1.00 | 7.95 | 0.00 | 0.00 |
June | 22.80 | 05-JUN-14:00 | 20.57 | 19.40 | 2.10 | 18.46 | 245.00 | 55.00 |
July | 22.80 | 02-JUL-15:00 | 21.59 | 21.10 | 4.60 | 20.92 | 155.00 | 8.50 |
August | 22.20 | 12-AUG-06:00 | 21.85 | 21.70 | 2.60 | 20.40 | 65.50 | 0.00 |
September | 22.20 | 05-SEP-05:00 | 21.37 | 21.10 | 2.60 | 13.54 | 0.00 | 0.00 |
October | 21.10 | 28-OCT-02:00 | 20.29 | 20.00 | 2.60 | 8.54 | 0.00 | 0.00 |
November | 10.00 | 27-NOV-02:00 | 8.82 | 7.80 | 3.10 | -4.6 | 0.00 | 0.00 |
December | 7.80 | 15-DEC-05:40 | 5.61 | 3.13 | 6.37 | -7.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.00 | 1.99 | -2.8 | 1.00 | -11.9 | 0.00 | 0.00 | |
Maximum of Months | 22.80 | 21.85 | 21.70 | 6.37 | 20.92 | 245.00 | 55.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.83 | 02-JAN-13:00 | 28.90 | 23.30 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 24.15 | 11-FEB-13:00 | 29.40 | 22.20 | 4.60 | 20.75 | 178.50 | 682.00 |
March | 23.83 | 14-MAR-09:00 | 26.70 | 22.80 | 11.30 | 19.52 | 243.50 | 478.00 |
April | 24.58 | 01-APR-15:00 | 28.30 | 23.30 | 3.60 | 16.30 | 93.50 | 759.50 |
May | 26.05 | 28-MAY-14:00 | 28.90 | 25.00 | 5.20 | 25.66 | 289.00 | 98.50 |
June | 26.06 | 28-JUN-11:00 | 28.90 | 25.00 | 1.50 | 22.98 | 404.50 | 373.50 |
July | 26.39 | 12-JUL-10:00 | 30.60 | 25.00 | 4.60 | 23.82 | 287.50 | 574.00 |
August | 26.46 | 21-AUG-15:00 | 32.20 | 24.40 | 3.60 | 24.50 | 205.50 | 366.00 |
September | 26.31 | 22-SEP-16:00 | 30.00 | 25.00 | 6.20 | 28.91 | 54.00 | 21.00 |
October | 26.52 | 01-OCT-11:00 | 29.40 | 25.60 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 25.31 | 04-NOV-13:00 | 27.80 | 24.40 | 2.10 | 26.48 | 199.00 | 3.00 |
December | 24.31 | 24-DEC-14:00 | 27.20 | 23.30 | 2.10 | 23.66 | 201.50 | 114.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.83 | 26.70 | 22.20 | 1.50 | 16.30 | 54.00 | 0.00 | |
Maximum of Months | 26.52 | 32.20 | 25.60 | 11.30 | 28.91 | 404.50 | 759.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.30 | 02-JAN-13:00 | 28.90 | 24.83 | 1.50 | 19.87 | 151.00 | 613.50 |
February | 22.80 | 11-FEB-16:19 | 27.60 | 24.09 | 5.70 | 18.94 | 101.33 | 565.33 |
March | 22.80 | 14-MAR-09:20 | 25.57 | 23.60 | 9.63 | 22.18 | 176.17 | 527.17 |
April | 23.30 | 01-APR-14:00 | 27.80 | 24.57 | 5.70 | 15.76 | 108.00 | 831.00 |
May | 25.00 | 28-MAY-12:00 | 27.80 | 25.74 | 6.70 | 22.98 | 249.50 | 244.50 |
June | 25.00 | 06-JUN-18:00 | 27.20 | 25.59 | 3.60 | 23.99 | 17.50 | 0.00 |
July | 25.00 | 12-JUL-03:00 | 27.20 | 25.59 | 1.50 | 19.70 | 0.00 | 0.00 |
August | 25.60 | 21-AUG-11:00 | 28.90 | 26.35 | 2.60 | 23.15 | 567.00 | 173.50 |
September | 25.00 | 22-SEP-00:00 | 27.80 | 25.31 | 3.60 | 20.92 | 0.00 | 0.00 |
October | 25.60 | 01-OCT-11:00 | 29.40 | 26.52 | 6.20 | 28.43 | 283.50 | 0.00 |
November | 24.40 | 05-NOV-01:19 | 26.10 | 24.93 | 2.03 | 16.37 | 0.00 | 0.00 |
December | 23.90 | 24-DEC-08:00 | 23.90 | 23.90 | 2.60 | 17.75 | 168.50 | 167.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.80 | 23.90 | 23.60 | 1.50 | 15.76 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 29.40 | 26.52 | 9.63 | 28.43 | 567.00 | 831.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.73 | 28.77 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.06 | 35.04 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 26.11 | 42.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.63 | 49.05 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 29.20 | 48.15 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 30.41 | 45.99 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.58 | 45.60 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 29.50 | 40.49 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 27.97 | 35.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 26.40 | 29.31 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.21 | 26.63 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 27.83 | 39.80 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.73 | 26.63 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 30.92 | 49.88 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.392902E+10 | -0.323743E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691592038.3 | 58.98 | 0.00 | 0.00 |
February | 0.353917E+10 | -0.291424E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -624927891.0 | 58.98 | 0.00 | 0.00 |
March | 0.403454E+10 | -0.334256E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691973931.1 | 58.98 | 0.00 | 0.00 |
April | 0.353784E+10 | -0.286919E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -668645426.3 | 58.98 | 0.00 | 0.00 |
May | 0.361404E+10 | -0.292467E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689373856.0 | 58.98 | 0.00 | 0.00 |
June | 0.345566E+10 | -0.278813E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667526175.6 | 58.98 | 0.00 | 0.00 |
July | 0.326965E+10 | -0.258041E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689243387.6 | 58.98 | 0.00 | 0.00 |
August | 0.357813E+10 | -0.288802E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690112498.1 | 58.98 | 0.00 | 0.00 |
September | 0.336704E+10 | -0.269986E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -667175124.3 | 58.98 | 0.00 | 0.00 |
October | 0.362041E+10 | -0.293225E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -688152346.9 | 58.97 | 0.00 | 0.00 |
November | 0.369474E+10 | -0.302848E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -666264475.5 | 58.98 | 0.00 | 0.00 |
December | 0.379682E+10 | -0.310500E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -691814569.7 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.434371E+11 | -0.353103E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.812680E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.326965E+10 | -0.334256E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -691973931.1 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.403454E+10 | -0.258041E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -624927891.0 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 5872.02 | 35.26 | 274.17 | 287.50 | 1116.26 | 24.26 | 128.00 | 265.33 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:30 | 2119.73 | 24.07 | 134.33 | 273.17 | 861.72 | 19.58 | 60.83 | 240.83 |
March | 362.67 | 0.51 | 0.48 | 01-MAR-07:00 | 1277.89 | 17.21 | 5.67 | 315.00 | 706.70 | 19.63 | 47.17 | 277.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:39 | 984.30 | 16.57 | 0.00 | 315.50 | 560.64 | 19.22 | 6.17 | 265.67 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-07:30 | 842.11 | 16.01 | 0.00 | 332.17 | 472.46 | 18.68 | 0.17 | 262.33 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:30 | 795.89 | 15.29 | 0.00 | 309.33 | 441.96 | 17.98 | 0.33 | 243.50 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:10 | 891.64 | 16.22 | 0.00 | 340.33 | 496.66 | 18.93 | 1.67 | 278.17 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1063.98 | 16.78 | 0.00 | 332.83 | 581.60 | 19.44 | 18.67 | 282.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 1287.54 | 17.01 | 0.00 | 307.67 | 685.70 | 19.70 | 69.00 | 262.83 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-08:20 | 1723.82 | 18.88 | 30.50 | 310.50 | 853.04 | 20.60 | 107.00 | 274.17 |
November | 314.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3294.03 | 29.69 | 236.83 | 285.83 | 964.84 | 23.57 | 169.00 | 263.50 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 5540.26 | 34.49 | 267.00 | 270.50 | 1304.21 | 25.63 | 155.17 | 255.00 |
Annual Sum or Average | 4111.50 | 0.52 | 1975.90 | 20.75 | 948.50 | 3680.33 | 726.25 | 20.38 | 763.17 | 3170.83 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 795.89 | 15.29 | 0.00 | 270.50 | 441.96 | 17.98 | 0.17 | 240.83 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 5872.02 | 35.26 | 274.17 | 340.33 | 1304.21 | 25.63 | 169.00 | 282.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:40 | 1742.27 | 19.03 | 82.33 | 248.17 | 957.08 | 22.09 | 74.00 | 195.83 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:00 | 1900.54 | 20.31 | 99.00 | 245.50 | 705.73 | 19.78 | 45.50 | 194.67 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:19 | 1748.27 | 18.20 | 85.50 | 306.00 | 902.29 | 19.75 | 54.67 | 254.50 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 2091.23 | 19.30 | 99.67 | 308.50 | 1113.81 | 20.79 | 70.67 | 258.00 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:19 | 1914.94 | 18.63 | 103.00 | 338.83 | 793.74 | 19.08 | 49.67 | 277.50 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-06:10 | 1858.14 | 18.81 | 111.00 | 324.50 | 773.38 | 19.08 | 53.00 | 263.83 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:19 | 1835.22 | 19.20 | 114.83 | 347.33 | 784.07 | 19.51 | 54.00 | 289.67 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:49 | 1801.06 | 19.29 | 95.00 | 332.50 | 810.59 | 19.86 | 46.67 | 278.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-06:49 | 1738.88 | 18.31 | 84.00 | 297.00 | 919.52 | 21.45 | 74.33 | 247.83 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:10 | 1718.41 | 18.81 | 81.33 | 288.00 | 928.17 | 21.43 | 66.00 | 244.67 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1392.77 | 19.02 | 84.00 | 255.50 | 699.75 | 20.19 | 51.67 | 203.83 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1512.76 | 19.71 | 85.17 | 238.33 | 616.50 | 19.64 | 34.50 | 176.33 |
Annual Sum or Average | 4111.50 | 0.52 | 1781.54 | 19.02 | 1124.83 | 3530.17 | 836.48 | 20.17 | 674.67 | 2885.17 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1392.77 | 18.20 | 81.33 | 238.33 | 616.50 | 19.08 | 34.50 | 176.33 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 2091.23 | 20.31 | 114.83 | 347.33 | 1113.81 | 22.09 | 74.33 | 289.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.57 | 0.48 | 01-JAN-10:09 | 434.69 | 12.97 | 0.00 | 213.00 | 278.60 | 16.01 | 0.00 | 68.50 |
February | 304.33 | 0.55 | 0.48 | 01-FEB-09:39 | 497.53 | 13.89 | 0.00 | 229.17 | 309.47 | 16.75 | 0.00 | 110.83 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-10:30 | 597.03 | 15.15 | 0.00 | 291.33 | 363.46 | 17.90 | 0.00 | 197.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:39 | 714.70 | 16.17 | 0.00 | 321.67 | 428.49 | 18.79 | 0.00 | 255.33 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:49 | 858.09 | 17.78 | 26.67 | 358.83 | 476.66 | 19.32 | 2.17 | 296.17 |
June | 388.17 | 0.51 | 0.48 | 01-JUN-06:19 | 917.38 | 19.32 | 64.17 | 347.33 | 503.16 | 20.60 | 53.50 | 290.17 |
July | 403.83 | 0.50 | 0.48 | 01-JUL-06:40 | 956.98 | 16.97 | 0.00 | 363.67 | 529.34 | 20.74 | 40.17 | 315.50 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:30 | 861.02 | 16.69 | 0.00 | 342.67 | 490.05 | 19.35 | 0.33 | 287.33 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:30 | 722.59 | 15.77 | 0.00 | 304.00 | 415.98 | 18.43 | 0.00 | 226.00 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 570.16 | 14.78 | 0.00 | 275.50 | 351.30 | 17.57 | 0.00 | 174.00 |
November | 314.83 | 0.55 | 0.48 | 01-NOV-08:30 | 503.54 | 14.04 | 0.00 | 231.50 | 303.93 | 16.89 | 0.00 | 105.17 |
December | 282.67 | 0.55 | 0.48 | 01-DEC-09:20 | 476.28 | 13.72 | 0.00 | 216.67 | 295.66 | 16.71 | 0.00 | 74.50 |
Annual Sum or Average | 4111.50 | 0.53 | 694.33 | 15.79 | 90.83 | 3495.33 | 404.40 | 18.41 | 96.17 | 2401.17 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 434.69 | 12.97 | 0.00 | 213.00 | 278.60 | 16.01 | 0.00 | 68.50 | |
Maximum of Months | 403.83 | 0.57 | 0.48 | 956.98 | 19.32 | 64.17 | 363.67 | 529.34 | 20.74 | 53.50 | 315.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-10:09 | 1489.90 | 17.97 | 72.33 | 247.67 | 848.44 | 21.28 | 65.83 | 182.83 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:39 | 1421.47 | 18.14 | 70.50 | 249.33 | 721.22 | 19.48 | 46.00 | 194.33 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-10:20 | 1714.85 | 18.15 | 86.00 | 300.17 | 872.76 | 19.70 | 55.83 | 249.67 |
April | 357.50 | 0.51 | 0.48 | 01-APR-09:09 | 1850.26 | 17.92 | 80.50 | 320.33 | 1019.98 | 19.62 | 51.83 | 273.33 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-08:09 | 1675.22 | 12.89 | 0.00 | 334.83 | 887.10 | 16.75 | 0.00 | 282.00 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-08:20 | 1429.17 | 12.57 | 0.00 | 319.50 | 638.66 | 16.34 | 0.00 | 260.67 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:30 | 1618.04 | 13.56 | 3.67 | 343.33 | 720.85 | 17.19 | 0.00 | 291.50 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:09 | 1720.63 | 16.61 | 56.83 | 328.33 | 900.72 | 17.61 | 5.50 | 279.67 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-08:09 | 1429.12 | 17.95 | 79.00 | 301.00 | 737.81 | 19.71 | 51.50 | 249.50 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 1691.23 | 18.55 | 83.33 | 281.83 | 921.51 | 21.94 | 76.33 | 240.33 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:30 | 1353.00 | 18.58 | 81.83 | 257.17 | 712.87 | 21.21 | 67.17 | 204.17 |
December | 282.67 | 0.51 | 0.48 | 01-DEC-09:20 | 1551.92 | 19.89 | 81.83 | 250.50 | 838.01 | 22.51 | 66.83 | 196.67 |
Annual Sum or Average | 4111.50 | 0.52 | 1584.40 | 16.68 | 695.83 | 3534.00 | 817.08 | 19.25 | 486.83 | 2904.67 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1353.00 | 12.57 | 0.00 | 247.67 | 638.66 | 16.34 | 0.00 | 182.83 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1850.26 | 19.89 | 86.00 | 343.33 | 1019.98 | 22.51 | 76.33 | 291.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 5760.03 | 35.02 | 274.17 | 285.83 | 1034.17 | 21.84 | 81.00 | 262.67 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:30 | 2028.87 | 21.78 | 132.67 | 272.17 | 796.99 | 16.69 | 0.00 | 237.00 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:00 | 1210.83 | 13.60 | 5.67 | 311.50 | 661.46 | 17.25 | 0.00 | 272.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:39 | 938.32 | 13.18 | 0.00 | 313.83 | 533.00 | 17.06 | 0.00 | 259.00 |
May | 389.00 | 0.53 | 0.48 | 01-MAY-07:40 | 805.86 | 12.47 | 0.00 | 328.50 | 452.20 | 16.34 | 0.00 | 254.00 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:30 | 762.03 | 11.67 | 0.00 | 304.33 | 423.10 | 15.56 | 0.00 | 234.67 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:10 | 852.88 | 12.62 | 0.00 | 337.67 | 474.97 | 16.53 | 0.00 | 270.50 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1015.60 | 13.28 | 0.00 | 329.50 | 553.39 | 17.12 | 0.00 | 273.83 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 1224.82 | 13.28 | 0.00 | 305.33 | 646.93 | 17.15 | 0.00 | 255.83 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-11:39 | 1639.09 | 15.42 | 30.50 | 310.00 | 795.47 | 18.10 | 9.17 | 268.67 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:10 | 3196.89 | 28.60 | 235.17 | 283.17 | 897.24 | 21.09 | 71.33 | 260.83 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 5420.86 | 33.89 | 264.33 | 269.67 | 1220.41 | 23.27 | 92.50 | 254.33 |
Annual Sum or Average | 4111.50 | 0.52 | 1909.26 | 17.91 | 942.50 | 3651.50 | 682.35 | 17.95 | 254.00 | 3104.00 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 762.03 | 11.67 | 0.00 | 269.67 | 423.10 | 15.56 | 0.00 | 234.67 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 5760.03 | 35.02 | 274.17 | 337.67 | 1220.41 | 23.27 | 92.50 | 273.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:49 | 1692.59 | 18.51 | 81.67 | 243.67 | 921.66 | 21.88 | 74.00 | 189.83 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:00 | 1747.58 | 17.58 | 75.33 | 240.00 | 670.19 | 19.57 | 45.50 | 190.83 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:30 | 1686.77 | 17.66 | 84.50 | 302.17 | 859.91 | 19.53 | 54.67 | 249.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 1950.95 | 17.25 | 80.67 | 304.00 | 1069.79 | 20.61 | 70.67 | 250.00 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:19 | 1860.14 | 18.24 | 103.00 | 334.33 | 754.24 | 18.90 | 49.67 | 273.00 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-06:10 | 1812.16 | 18.43 | 111.00 | 322.00 | 735.34 | 18.92 | 53.00 | 256.33 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:30 | 1782.95 | 18.81 | 114.83 | 344.50 | 744.54 | 19.34 | 54.00 | 284.17 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:49 | 1737.46 | 18.90 | 94.83 | 329.00 | 771.19 | 19.68 | 46.83 | 272.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-06:49 | 1687.12 | 17.89 | 84.00 | 293.67 | 880.35 | 21.26 | 74.50 | 244.17 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:19 | 1664.33 | 18.38 | 81.33 | 285.17 | 888.68 | 21.23 | 66.00 | 240.17 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1338.91 | 18.27 | 80.67 | 252.00 | 666.46 | 19.95 | 51.67 | 198.33 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1427.43 | 18.20 | 75.17 | 233.33 | 587.26 | 19.38 | 34.50 | 173.33 |
Annual Sum or Average | 4111.50 | 0.53 | 1710.43 | 18.18 | 1067.00 | 3483.83 | 798.26 | 19.97 | 675.00 | 2821.83 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1338.91 | 17.25 | 75.17 | 233.33 | 587.26 | 18.90 | 34.50 | 173.33 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1950.95 | 18.90 | 114.83 | 344.50 | 1069.79 | 21.88 | 74.50 | 284.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.57 | 0.48 | 01-JAN-10:09 | 416.03 | 9.57 | 0.00 | 203.00 | 268.94 | 13.72 | 0.00 | 55.17 |
February | 304.33 | 0.55 | 0.48 | 01-FEB-09:39 | 476.71 | 10.45 | 0.00 | 221.83 | 298.62 | 14.52 | 0.00 | 98.50 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-10:30 | 572.15 | 11.84 | 0.00 | 287.00 | 350.38 | 15.85 | 0.00 | 187.50 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:50 | 684.66 | 12.89 | 0.00 | 319.17 | 412.50 | 16.84 | 0.00 | 243.50 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:40 | 816.15 | 13.04 | 1.33 | 353.00 | 461.53 | 18.10 | 25.67 | 290.50 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-06:30 | 868.34 | 14.32 | 32.17 | 336.00 | 480.51 | 18.28 | 32.67 | 283.33 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:40 | 915.24 | 13.26 | 0.00 | 361.83 | 505.80 | 18.47 | 26.17 | 308.33 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:40 | 823.56 | 13.24 | 0.00 | 339.00 | 469.44 | 17.15 | 0.00 | 279.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:30 | 691.67 | 12.29 | 0.00 | 300.67 | 399.21 | 16.16 | 0.00 | 219.17 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 545.32 | 11.51 | 0.00 | 271.33 | 338.17 | 15.50 | 0.00 | 160.83 |
November | 314.83 | 0.55 | 0.48 | 01-NOV-08:30 | 481.80 | 10.46 | 0.00 | 224.83 | 292.41 | 14.54 | 0.00 | 94.17 |
December | 282.67 | 0.55 | 0.48 | 01-DEC-09:30 | 455.44 | 10.19 | 0.00 | 208.00 | 284.70 | 14.35 | 0.00 | 59.67 |
Annual Sum or Average | 4111.50 | 0.53 | 663.13 | 12.07 | 33.50 | 3425.67 | 388.66 | 16.29 | 84.50 | 2280.17 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 416.03 | 9.57 | 0.00 | 203.00 | 268.94 | 13.72 | 0.00 | 55.17 | |
Maximum of Months | 403.83 | 0.57 | 0.48 | 915.24 | 14.32 | 32.17 | 361.83 | 505.80 | 18.47 | 32.67 | 308.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-10:09 | 1447.89 | 17.60 | 72.33 | 242.17 | 817.04 | 21.17 | 65.83 | 175.17 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:39 | 1372.90 | 17.78 | 70.50 | 246.00 | 686.79 | 19.35 | 46.17 | 187.83 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-10:20 | 1663.60 | 17.76 | 85.83 | 297.17 | 830.85 | 19.54 | 55.83 | 243.67 |
April | 357.50 | 0.51 | 0.48 | 01-APR-09:09 | 1787.01 | 17.51 | 80.50 | 318.33 | 975.40 | 19.45 | 51.83 | 267.17 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-08:09 | 1618.22 | 12.40 | 0.00 | 332.33 | 849.53 | 16.53 | 0.00 | 274.17 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-08:30 | 1387.18 | 12.07 | 0.00 | 315.83 | 607.51 | 16.11 | 0.00 | 254.83 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:40 | 1566.94 | 13.07 | 3.67 | 340.67 | 685.44 | 16.97 | 0.00 | 285.33 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:09 | 1656.72 | 16.18 | 56.83 | 325.17 | 860.96 | 17.42 | 5.50 | 272.83 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-08:20 | 1383.41 | 17.57 | 78.83 | 298.50 | 703.66 | 19.56 | 51.50 | 242.33 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 1639.01 | 18.17 | 83.33 | 278.83 | 884.41 | 21.82 | 76.33 | 235.17 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:39 | 1309.04 | 18.20 | 81.67 | 253.83 | 680.70 | 20.99 | 65.67 | 198.00 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-09:30 | 1503.70 | 19.53 | 81.83 | 247.00 | 770.02 | 21.09 | 54.83 | 189.00 |
Annual Sum or Average | 4111.50 | 0.52 | 1533.38 | 16.26 | 695.33 | 3495.83 | 778.46 | 18.99 | 473.50 | 2825.50 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1309.04 | 12.07 | 0.00 | 242.17 | 607.51 | 16.11 | 0.00 | 175.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1787.01 | 19.53 | 85.83 | 340.67 | 975.40 | 21.82 | 76.33 | 285.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.51 | 0.48 | 01-JAN-07:40 | 5760.00 | 35.02 | 274.17 | 285.83 | 1034.11 | 21.84 | 81.00 | 262.67 |
February | 304.33 | 0.51 | 0.48 | 01-FEB-08:30 | 2028.82 | 21.78 | 132.67 | 272.17 | 796.93 | 16.69 | 0.00 | 237.00 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:00 | 1210.78 | 13.60 | 5.67 | 311.50 | 661.41 | 17.25 | 0.00 | 272.67 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:39 | 938.29 | 13.18 | 0.00 | 313.83 | 532.96 | 17.07 | 0.00 | 259.00 |
May | 389.00 | 0.53 | 0.48 | 01-MAY-07:40 | 805.83 | 12.47 | 0.00 | 328.50 | 452.17 | 16.34 | 0.00 | 254.00 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-07:30 | 762.00 | 11.67 | 0.00 | 304.33 | 423.07 | 15.56 | 0.00 | 234.67 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:10 | 852.85 | 12.63 | 0.00 | 337.67 | 474.94 | 16.53 | 0.00 | 270.33 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-07:40 | 1015.55 | 13.28 | 0.00 | 329.50 | 553.35 | 17.13 | 0.00 | 273.83 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:19 | 1224.76 | 13.28 | 0.00 | 305.33 | 646.88 | 17.15 | 0.00 | 255.83 |
October | 323.50 | 0.51 | 0.48 | 02-OCT-11:39 | 1639.03 | 15.42 | 30.50 | 310.00 | 795.41 | 18.10 | 9.17 | 268.67 |
November | 314.83 | 0.51 | 0.48 | 01-NOV-07:10 | 3196.84 | 28.60 | 235.17 | 283.17 | 897.17 | 21.09 | 71.33 | 260.83 |
December | 282.67 | 0.50 | 0.48 | 01-DEC-08:39 | 5420.84 | 33.89 | 264.33 | 269.67 | 1220.34 | 23.27 | 92.50 | 254.33 |
Annual Sum or Average | 4111.50 | 0.52 | 1909.22 | 17.91 | 942.50 | 3651.50 | 682.31 | 17.95 | 254.00 | 3103.83 | ||
Minimum of Months | 282.67 | 0.50 | 0.48 | 762.00 | 11.67 | 0.00 | 269.67 | 423.07 | 15.56 | 0.00 | 234.67 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 5760.00 | 35.02 | 274.17 | 337.67 | 1220.34 | 23.27 | 92.50 | 273.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-07:49 | 1692.59 | 18.52 | 81.67 | 243.67 | 921.64 | 21.88 | 74.00 | 189.83 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-07:00 | 1747.57 | 17.58 | 75.33 | 240.00 | 670.15 | 19.57 | 45.50 | 190.83 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-07:30 | 1686.76 | 17.66 | 84.50 | 302.17 | 859.87 | 19.53 | 54.67 | 249.17 |
April | 357.50 | 0.52 | 0.48 | 01-APR-06:00 | 1950.93 | 17.25 | 80.67 | 304.00 | 1069.75 | 20.61 | 70.67 | 250.00 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-06:19 | 1860.11 | 18.24 | 103.00 | 334.33 | 754.20 | 18.90 | 49.67 | 272.83 |
June | 388.17 | 0.53 | 0.48 | 01-JUN-06:10 | 1812.13 | 18.43 | 111.00 | 322.00 | 735.30 | 18.92 | 53.00 | 256.33 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-06:30 | 1782.92 | 18.81 | 114.83 | 344.50 | 744.49 | 19.34 | 54.00 | 284.17 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-06:49 | 1737.42 | 18.90 | 94.83 | 329.00 | 771.14 | 19.68 | 46.83 | 272.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-06:49 | 1687.08 | 17.89 | 84.00 | 293.67 | 880.30 | 21.26 | 74.50 | 244.17 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-07:19 | 1664.32 | 18.38 | 81.33 | 285.17 | 888.64 | 21.23 | 66.00 | 240.17 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-06:00 | 1338.90 | 18.27 | 80.67 | 252.00 | 666.43 | 19.95 | 51.67 | 198.33 |
December | 282.67 | 0.53 | 0.48 | 01-DEC-08:39 | 1427.43 | 18.20 | 75.17 | 233.33 | 587.23 | 19.38 | 34.50 | 173.33 |
Annual Sum or Average | 4111.50 | 0.53 | 1710.41 | 18.18 | 1067.00 | 3483.83 | 798.22 | 19.97 | 675.00 | 2821.67 | ||
Minimum of Months | 282.67 | 0.52 | 0.48 | 1338.90 | 17.25 | 75.17 | 233.33 | 587.23 | 18.90 | 34.50 | 173.33 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1950.93 | 18.90 | 114.83 | 344.50 | 1069.75 | 21.88 | 74.50 | 284.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.57 | 0.48 | 01-JAN-10:09 | 416.04 | 9.57 | 0.00 | 203.00 | 268.93 | 13.72 | 0.00 | 55.17 |
February | 304.33 | 0.55 | 0.48 | 01-FEB-09:39 | 476.71 | 10.45 | 0.00 | 221.83 | 298.60 | 14.52 | 0.00 | 98.50 |
March | 362.67 | 0.53 | 0.48 | 01-MAR-10:30 | 572.15 | 11.84 | 0.00 | 287.00 | 350.37 | 15.85 | 0.00 | 187.33 |
April | 357.50 | 0.52 | 0.48 | 01-APR-08:50 | 684.64 | 12.89 | 0.00 | 319.17 | 412.48 | 16.84 | 0.00 | 243.50 |
May | 389.00 | 0.51 | 0.48 | 01-MAY-06:40 | 816.13 | 13.04 | 1.33 | 353.00 | 461.50 | 18.10 | 25.67 | 290.50 |
June | 388.17 | 0.52 | 0.48 | 01-JUN-06:30 | 868.30 | 14.32 | 32.17 | 336.00 | 480.47 | 18.28 | 32.67 | 283.33 |
July | 403.83 | 0.51 | 0.48 | 01-JUL-06:40 | 915.21 | 13.26 | 0.00 | 361.83 | 505.76 | 18.47 | 26.17 | 308.33 |
August | 348.33 | 0.51 | 0.48 | 01-AUG-07:40 | 823.53 | 13.25 | 0.00 | 339.00 | 469.41 | 17.16 | 0.00 | 279.50 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-07:30 | 691.65 | 12.29 | 0.00 | 300.67 | 399.18 | 16.16 | 0.00 | 219.17 |
October | 323.50 | 0.54 | 0.48 | 02-OCT-11:39 | 545.32 | 11.52 | 0.00 | 271.33 | 338.15 | 15.50 | 0.00 | 160.83 |
November | 314.83 | 0.55 | 0.48 | 01-NOV-08:30 | 481.80 | 10.46 | 0.00 | 224.83 | 292.39 | 14.54 | 0.00 | 94.17 |
December | 282.67 | 0.55 | 0.48 | 01-DEC-09:30 | 455.43 | 10.19 | 0.00 | 208.00 | 284.69 | 14.35 | 0.00 | 59.67 |
Annual Sum or Average | 4111.50 | 0.53 | 663.11 | 12.07 | 33.50 | 3425.67 | 388.63 | 16.29 | 84.50 | 2280.00 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 416.04 | 9.57 | 0.00 | 203.00 | 268.93 | 13.72 | 0.00 | 55.17 | |
Maximum of Months | 403.83 | 0.57 | 0.48 | 915.21 | 14.32 | 32.17 | 361.83 | 505.76 | 18.47 | 32.67 | 308.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 287.00 | 0.54 | 0.48 | 01-JAN-10:09 | 1447.89 | 17.60 | 72.33 | 242.17 | 817.01 | 21.17 | 65.83 | 175.17 |
February | 304.33 | 0.53 | 0.48 | 01-FEB-09:39 | 1372.89 | 17.78 | 70.50 | 246.00 | 686.76 | 19.35 | 46.17 | 187.83 |
March | 362.67 | 0.52 | 0.48 | 01-MAR-10:20 | 1663.58 | 17.76 | 85.83 | 297.17 | 830.81 | 19.55 | 55.83 | 243.67 |
April | 357.50 | 0.51 | 0.48 | 01-APR-09:09 | 1787.00 | 17.52 | 80.50 | 318.33 | 975.36 | 19.45 | 51.83 | 267.17 |
May | 389.00 | 0.52 | 0.48 | 01-MAY-08:09 | 1618.19 | 12.40 | 0.00 | 332.33 | 849.49 | 16.53 | 0.00 | 274.17 |
June | 388.17 | 0.54 | 0.48 | 01-JUN-08:30 | 1387.14 | 12.08 | 0.00 | 315.83 | 607.47 | 16.11 | 0.00 | 254.83 |
July | 403.83 | 0.52 | 0.48 | 01-JUL-07:40 | 1566.90 | 13.07 | 3.67 | 340.67 | 685.39 | 16.97 | 0.00 | 285.33 |
August | 348.33 | 0.52 | 0.48 | 01-AUG-08:09 | 1656.69 | 16.18 | 56.83 | 325.17 | 860.91 | 17.43 | 5.50 | 272.83 |
September | 349.67 | 0.52 | 0.48 | 01-SEP-08:20 | 1383.37 | 17.57 | 78.83 | 298.50 | 703.61 | 19.56 | 51.50 | 242.33 |
October | 323.50 | 0.53 | 0.48 | 02-OCT-11:39 | 1638.99 | 18.18 | 83.33 | 278.83 | 884.37 | 21.82 | 76.33 | 235.17 |
November | 314.83 | 0.53 | 0.48 | 01-NOV-08:39 | 1309.03 | 18.20 | 81.67 | 253.83 | 680.66 | 20.99 | 65.67 | 198.00 |
December | 282.67 | 0.52 | 0.48 | 01-DEC-09:30 | 1503.70 | 19.54 | 81.83 | 247.00 | 769.99 | 21.09 | 54.83 | 189.00 |
Annual Sum or Average | 4111.50 | 0.52 | 1533.36 | 16.26 | 695.33 | 3495.83 | 778.42 | 18.99 | 473.50 | 2825.50 | ||
Minimum of Months | 282.67 | 0.51 | 0.48 | 1309.03 | 12.08 | 0.00 | 242.17 | 607.47 | 16.11 | 0.00 | 175.17 | |
Maximum of Months | 403.83 | 0.54 | 0.48 | 1787.00 | 19.54 | 85.83 | 340.67 | 975.36 | 21.82 | 76.33 | 285.33 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.216125E+09 | 5343.79 | 09-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 76552905.86 | 5343.79 | 03-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162930E+09 | 5343.79 | 01-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11612686.53 | 5004.68 | 19-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 37356306.75 | 5343.79 | 13-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137823E+09 | 5343.79 | 12-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.642401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.216125E+09 | 5343.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 469439.47 | 456.13 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 469439.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 469439.47 | 456.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45286.52 | 27.61 | 04-FEB-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 45286.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 45286.52 | 27.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2130342.10 | 5112.87 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2130342.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2130342.10 | 5112.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 773313.40 | 3126.03 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1602569.30 | 4247.55 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 630302.82 | 1942.44 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2576451.64 | 2606.99 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5582637.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2576451.64 | 4247.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2231571.42 | 2690.33 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7575854.03 | 6439.27 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 667441.54 | 791.48 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1233913.00 | 1109.22 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11708779.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7575854.03 | 6439.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3109815.32 | 2837.55 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7844602.99 | 4256.08 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 909672.97 | 1221.62 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4331161.41 | 3096.81 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16195252.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7844602.99 | 4256.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 4956742.06 | 8138.34 | 26-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15573130.34 | 13301.60 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7718455.43 | 5448.08 | 21-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28248327.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15573130.34 | 13301.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 22253730.29 | 9081.41 | 25-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23545799.83 | 9081.41 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16142009.21 | 9081.41 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 195488.76 | 1954.89 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34457403.21 | 9081.41 | 15-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96594431.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34457403.21 | 9081.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 26451480.71 | 5947.68 | 23-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17359177.63 | 5947.68 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13084029.23 | 5947.68 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 990038.25 | 5947.68 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 44441736.89 | 5947.68 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44441736.89 | 5947.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 63665196.21 | 9094.82 | 23-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 53257537.95 | 9094.82 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26382185.57 | 9094.82 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5317946.48 | 9094.82 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 65609973.67 | 9094.82 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 65609973.67 | 9094.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 67824448.98 | 5952.31 | 10-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51016277.33 | 5952.31 | 04-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29238408.41 | 5952.31 | 16-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6177908.55 | 5952.31 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 69381376.17 | 5952.31 | 13-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69381376.17 | 5952.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9667781.24 | 1989.91 | 04-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 9667781.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9667781.24 | 1989.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.479696E+11 | 0.349097E+11 | 87913.89 | 14-JAN-06:03 | 56695.81 | 0.00 |
February | 0.00 | 0.00 | 0.487341E+11 | 0.359025E+11 | 83166.65 | 11-FEB-06:03 | 51131.25 | 0.00 |
March | 0.00 | 0.00 | 0.588131E+11 | 0.422058E+11 | 88467.27 | 06-MAR-05:03 | 49680.78 | 0.00 |
April | 0.00 | 0.00 | 0.666427E+11 | 0.470632E+11 | 78585.82 | 14-APR-15:10 | 53600.23 | 0.00 |
May | 0.00 | 0.00 | 0.889511E+11 | 0.589121E+11 | 110925.80 | 30-MAY-04:02 | 77074.67 | 0.00 |
June | 0.00 | 0.00 | 0.100187E+12 | 0.620427E+11 | 117927.07 | 19-JUN-04:02 | 73672.39 | 0.00 |
July | 0.00 | 0.00 | 0.105454E+12 | 0.654616E+11 | 111642.14 | 03-JUL-04:02 | 76297.41 | 0.00 |
August | 0.00 | 0.00 | 0.109838E+12 | 0.678799E+11 | 110763.36 | 28-AUG-04:02 | 77732.79 | 0.00 |
September | 0.00 | 0.00 | 0.100788E+12 | 0.627117E+11 | 112632.64 | 19-SEP-04:03 | 77241.30 | 0.00 |
October | 0.00 | 0.00 | 0.928167E+11 | 0.604983E+11 | 116944.58 | 02-OCT-06:03 | 78437.53 | 0.00 |
November | 0.00 | 0.00 | 0.737577E+11 | 0.488432E+11 | 99839.91 | 04-NOV-05:03 | 65487.36 | 0.00 |
December | 0.00 | 0.00 | 0.511897E+11 | 0.359346E+11 | 92349.73 | 26-DEC-05:03 | 57050.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.945143E+12 | 0.622365E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.479696E+11 | 0.349097E+11 | 78585.82 | 49680.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109838E+12 | 0.678799E+11 | 117927.07 | 78437.53 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.366839E+11 | 0.266700E+11 | 57232.16 | 02-JAN-14:00 | 43447.10 | 0.00 |
February | 0.00 | 0.00 | 0.381572E+11 | 0.284263E+11 | 61085.03 | 13-FEB-06:03 | 33449.82 | 0.00 |
March | 0.00 | 0.00 | 0.468742E+11 | 0.345113E+11 | 73027.21 | 06-MAR-06:03 | 43842.67 | 0.00 |
April | 0.00 | 0.00 | 0.520310E+11 | 0.390068E+11 | 83350.29 | 13-APR-05:03 | 57998.33 | 0.00 |
May | 0.00 | 0.00 | 0.645048E+11 | 0.471526E+11 | 98448.82 | 30-MAY-04:02 | 64553.42 | 0.00 |
June | 0.00 | 0.00 | 0.691136E+11 | 0.492236E+11 | 104687.16 | 19-JUN-04:02 | 62352.25 | 0.00 |
July | 0.00 | 0.00 | 0.707335E+11 | 0.509103E+11 | 99291.51 | 03-JUL-04:02 | 63730.91 | 0.00 |
August | 0.00 | 0.00 | 0.723344E+11 | 0.514733E+11 | 98551.16 | 28-AUG-04:02 | 64887.99 | 0.00 |
September | 0.00 | 0.00 | 0.682334E+11 | 0.479788E+11 | 91021.75 | 25-SEP-05:03 | 63499.68 | 0.00 |
October | 0.00 | 0.00 | 0.636567E+11 | 0.463167E+11 | 103588.46 | 02-OCT-04:02 | 64754.31 | 0.00 |
November | 0.00 | 0.00 | 0.517137E+11 | 0.371301E+11 | 86684.04 | 04-NOV-05:03 | 55259.29 | 0.00 |
December | 0.00 | 0.00 | 0.389455E+11 | 0.278192E+11 | 74288.43 | 09-DEC-06:03 | 47706.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.672982E+12 | 0.486619E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.366839E+11 | 0.266700E+11 | 57232.16 | 33449.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.723344E+11 | 0.514733E+11 | 104687.16 | 64887.99 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.400082E+11 | 0.276247E+11 | 78043.66 | 02-JAN-14:00 | 51648.50 | 0.00 |
February | 0.00 | 0.00 | 0.426927E+11 | 0.305041E+11 | 63916.64 | 19-FEB-15:43 | 44615.91 | 0.00 |
March | 0.00 | 0.00 | 0.533744E+11 | 0.376032E+11 | 81481.80 | 06-MAR-06:03 | 46658.21 | 0.00 |
April | 0.00 | 0.00 | 0.631990E+11 | 0.446484E+11 | 83065.16 | 13-APR-05:03 | 54299.91 | 0.00 |
May | 0.00 | 0.00 | 0.847888E+11 | 0.561310E+11 | 111981.87 | 30-MAY-04:02 | 74300.60 | 0.00 |
June | 0.00 | 0.00 | 0.961744E+11 | 0.595137E+11 | 107403.29 | 12-JUN-04:02 | 76254.67 | 0.00 |
July | 0.00 | 0.00 | 0.101551E+12 | 0.632188E+11 | 109517.14 | 31-JUL-04:02 | 74075.98 | 0.00 |
August | 0.00 | 0.00 | 0.101233E+12 | 0.619995E+11 | 112359.80 | 21-AUG-04:02 | 77866.25 | 0.00 |
September | 0.00 | 0.00 | 0.929018E+11 | 0.571701E+11 | 110850.75 | 18-SEP-04:02 | 77723.77 | 0.00 |
October | 0.00 | 0.00 | 0.819090E+11 | 0.524783E+11 | 124311.17 | 02-OCT-04:02 | 72232.01 | 0.00 |
November | 0.00 | 0.00 | 0.631895E+11 | 0.403592E+11 | 88671.58 | 04-NOV-05:03 | 53442.63 | 0.00 |
December | 0.00 | 0.00 | 0.438816E+11 | 0.293176E+11 | 78535.65 | 11-DEC-06:03 | 47966.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.864903E+12 | 0.560569E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.400082E+11 | 0.276247E+11 | 63916.64 | 44615.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101551E+12 | 0.632188E+11 | 124311.17 | 77866.25 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 1362.78 | 4649.93 | 25-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 1359.05 | 4635.82 | 03-FEB-12:17 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1405.56 | 4528.97 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1260.76 | 4336.25 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1248.08 | 4160.85 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1233.98 | 3968.40 | 02-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1116.90 | 3873.92 | 05-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1236.32 | 3960.37 | 31-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1196.16 | 4106.52 | 29-SEP-11:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1248.46 | 4323.33 | 30-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1323.77 | 4495.15 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1311.84 | 4618.46 | 20-DEC-12:10 |
Annual Sum or Average | 0.00 | 1274.85 | ||||
Minimum of Months | 0.00 | 0.00 | 1116.90 | 3873.92 | ||
Maximum of Months | 0.00 | 0.00 | 1405.56 | 4649.93 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205221E+10 | 0.33 | 5793.03 | 14-JAN-06:03 | 1.27 |
February | 0.198854E+10 | 0.34 | 4431.92 | 11-FEB-06:03 | 1.08 |
March | 0.235953E+10 | 0.36 | 4131.56 | 29-MAR-05:03 | 1.03 |
April | 0.245305E+10 | 0.37 | 4843.15 | 24-APR-05:03 | 1.14 |
May | 0.317676E+10 | 0.41 | 9891.67 | 30-MAY-04:02 | 1.78 |
June | 0.335294E+10 | 0.44 | 9891.67 | 12-JUN-04:02 | 1.78 |
July | 0.354870E+10 | 0.44 | 9891.67 | 03-JUL-04:02 | 1.78 |
August | 0.379460E+10 | 0.46 | 9891.67 | 01-AUG-04:03 | 1.78 |
September | 0.346357E+10 | 0.45 | 9891.67 | 05-SEP-04:02 | 1.78 |
October | 0.339741E+10 | 0.43 | 9891.67 | 10-OCT-04:02 | 1.78 |
November | 0.273966E+10 | 0.38 | 7356.92 | 04-NOV-05:03 | 1.48 |
December | 0.208135E+10 | 0.33 | 6082.40 | 11-DEC-05:03 | 1.31 |
Annual Sum or Average | 0.344083E+11 | 0.40 | |||
Minimum of Months | 0.198854E+10 | 0.33 | 4131.56 | 1.03 | |
Maximum of Months | 0.379460E+10 | 0.46 | 9891.67 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157095E+10 | 0.31 | 3285.88 | 02-JAN-15:10 | 1.01 |
February | 0.157121E+10 | 0.33 | 2974.78 | 21-FEB-16:30 | 0.95 |
March | 0.195052E+10 | 0.35 | 4430.09 | 14-MAR-05:03 | 1.20 |
April | 0.208124E+10 | 0.37 | 7404.15 | 13-APR-05:03 | 1.66 |
May | 0.260607E+10 | 0.41 | 8260.19 | 15-MAY-05:03 | 1.78 |
June | 0.273354E+10 | 0.43 | 8260.19 | 03-JUN-05:03 | 1.78 |
July | 0.284362E+10 | 0.43 | 8260.19 | 01-JUL-05:03 | 1.78 |
August | 0.290142E+10 | 0.44 | 8260.19 | 01-AUG-04:03 | 1.78 |
September | 0.269108E+10 | 0.42 | 8260.19 | 05-SEP-04:02 | 1.78 |
October | 0.261644E+10 | 0.40 | 8260.19 | 30-OCT-04:02 | 1.78 |
November | 0.204627E+10 | 0.35 | 7544.77 | 21-NOV-06:03 | 1.68 |
December | 0.162431E+10 | 0.32 | 4883.21 | 11-DEC-06:03 | 1.28 |
Annual Sum or Average | 0.272367E+11 | 0.38 | |||
Minimum of Months | 0.157095E+10 | 0.31 | 2974.78 | 0.95 | |
Maximum of Months | 0.290142E+10 | 0.44 | 8260.19 | 1.78 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149764E+10 | 0.29 | 3186.63 | 02-JAN-15:00 | 0.89 |
February | 0.151623E+10 | 0.31 | 2905.67 | 21-FEB-16:20 | 0.85 |
March | 0.190912E+10 | 0.33 | 3908.52 | 06-MAR-06:03 | 1.00 |
April | 0.210299E+10 | 0.35 | 5012.88 | 13-APR-05:03 | 1.17 |
May | 0.265464E+10 | 0.38 | 9790.34 | 30-MAY-04:02 | 1.78 |
June | 0.279767E+10 | 0.40 | 9840.01 | 12-JUN-04:02 | 1.78 |
July | 0.295012E+10 | 0.40 | 9840.01 | 10-JUL-04:02 | 1.78 |
August | 0.292093E+10 | 0.41 | 9840.01 | 21-AUG-04:02 | 1.78 |
September | 0.267768E+10 | 0.39 | 9840.01 | 11-SEP-04:02 | 1.78 |
October | 0.248785E+10 | 0.36 | 8912.49 | 02-OCT-04:02 | 1.67 |
November | 0.192410E+10 | 0.32 | 4603.51 | 04-NOV-05:03 | 1.11 |
December | 0.156075E+10 | 0.30 | 4242.93 | 11-DEC-06:03 | 1.05 |
Annual Sum or Average | 0.269997E+11 | 0.35 | |||
Minimum of Months | 0.149764E+10 | 0.29 | 2905.67 | 0.85 | |
Maximum of Months | 0.295012E+10 | 0.41 | 9840.01 | 1.78 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:10 | 0.22 | 0.22 | 57.40 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:03 | 0.22 | 0.22 | 56.82 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:03 | 0.22 | 0.22 | 56.62 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:03 | 0.22 | 0.22 | 57.01 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 57.02 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 57.33 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 57.83 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 57.42 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 57.37 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.09 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:03 | 0.22 | 0.22 | 56.98 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:03 | 0.22 | 0.22 | 56.97 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 56.62 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.83 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.24 | 58.24 | 1362.78 | 4649.93 | 25-JAN-12:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.14 | 57.14 | 1359.05 | 4635.82 | 03-FEB-12:17 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.92 | 56.92 | 1405.56 | 4528.97 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.01 | 58.01 | 1260.76 | 4336.25 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.92 | 57.92 | 1248.08 | 4160.85 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.54 | 57.54 | 1233.98 | 3968.40 | 02-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.03 | 58.03 | 1116.90 | 3873.92 | 05-JUL-11:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 58.27 | 58.27 | 1236.32 | 3960.37 | 31-AUG-11:13 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.23 | 58.23 | 1196.16 | 4106.52 | 29-SEP-11:15 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.61 | 56.61 | 1248.46 | 4323.33 | 30-OCT-11:07 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.23 | 57.23 | 1323.77 | 4495.15 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.24 | 57.24 | 1311.84 | 4618.46 | 20-DEC-12:10 |
Annual Sum or Average | 0.00 | 1274.85 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.61 | 56.61 | 1116.90 | 3873.92 | ||
Maximum of Months | 0.00 | 0.00 | 58.27 | 58.27 | 1405.56 | 4649.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.138757E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.138069E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.166603E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.187138E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.252902E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.282827E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.303694E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.314761E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.286413E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.263009E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.205459E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.145528E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.268516E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.138069E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.314761E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.104988E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.107930E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.132212E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.147895E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.188096E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.202688E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.212995E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.215532E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.200556E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.185547E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.146313E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.110701E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195545E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.104988E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.215532E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.115159E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.120602E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.148942E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.175515E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.237056E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.266412E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.286626E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.283138E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.258168E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.227007E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172190E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.124747E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.241556E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115159E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.286626E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.205221E+10 | 0.479696E+11 | 0.216125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198854E+10 | 0.487341E+11 | 77067631.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235953E+10 | 0.588131E+11 | 0.162930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.245305E+10 | 0.666427E+11 | 11612686.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.317676E+10 | 0.889511E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.335294E+10 | 0.100187E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.354870E+10 | 0.105454E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.379460E+10 | 0.109838E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346357E+10 | 0.100788E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.339741E+10 | 0.928167E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.273966E+10 | 0.737577E+11 | 37356306.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208135E+10 | 0.511897E+11 | 0.137823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344083E+11 | 0.945143E+12 | 0.642915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.198854E+10 | 0.479696E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.379460E+10 | 0.109838E+12 | 0.216125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157095E+10 | 0.366839E+11 | 6114700.14 | 0.00 | 0.199341E+10 | 0.00 | 0.00 | 0.00 |
February | 0.157121E+10 | 0.381572E+11 | 19153368.41 | 0.216402E+09 | 0.227901E+10 | 0.00 | 0.00 | 0.00 |
March | 0.195052E+10 | 0.468742E+11 | 2207417.33 | 20176173.89 | 0.324144E+10 | 0.00 | 0.00 | 0.00 |
April | 0.208124E+10 | 0.520310E+11 | 0.00 | 0.00 | 0.645202E+10 | 0.00 | 0.00 | 0.00 |
May | 0.260607E+10 | 0.645048E+11 | 0.00 | 0.00 | 0.143228E+11 | 0.00 | 0.00 | 0.00 |
June | 0.273354E+10 | 0.691136E+11 | 0.00 | 0.00 | 0.205495E+11 | 0.00 | 0.00 | 0.00 |
July | 0.284362E+10 | 0.707335E+11 | 0.00 | 0.00 | 0.235928E+11 | 0.00 | 0.00 | 0.00 |
August | 0.290142E+10 | 0.723344E+11 | 0.00 | 0.00 | 0.231940E+11 | 0.00 | 0.00 | 0.00 |
September | 0.269108E+10 | 0.682334E+11 | 0.00 | 0.00 | 0.193669E+11 | 0.00 | 0.00 | 0.00 |
October | 0.261644E+10 | 0.636567E+11 | 0.00 | 0.00 | 0.151397E+11 | 0.00 | 0.00 | 0.00 |
November | 0.204627E+10 | 0.517137E+11 | 0.00 | 1905947.87 | 0.940849E+10 | 0.00 | 0.00 | 0.00 |
December | 0.162431E+10 | 0.389455E+11 | 8141526.05 | 0.00 | 0.318889E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272367E+11 | 0.672982E+12 | 35617011.95 | 0.238484E+09 | 0.142729E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157095E+10 | 0.366839E+11 | 0.00 | 0.00 | 0.199341E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.290142E+10 | 0.723344E+11 | 19153368.41 | 0.216402E+09 | 0.235928E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149764E+10 | 0.400082E+11 | 0.185152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151623E+10 | 0.426927E+11 | 0.170420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190912E+10 | 0.533744E+11 | 84846632.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210299E+10 | 0.631990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265464E+10 | 0.847888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.279767E+10 | 0.961744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.295012E+10 | 0.101551E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292093E+10 | 0.101233E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.267768E+10 | 0.929018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248785E+10 | 0.819090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192410E+10 | 0.631895E+11 | 12681382.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156075E+10 | 0.438816E+11 | 0.221609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269997E+11 | 0.864903E+12 | 0.674708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149764E+10 | 0.400082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.295012E+10 | 0.101551E+12 | 0.221609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.205221E+10 | 0.00 | 0.00 | 0.00 | 0.116073E+11 | 0.216125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198854E+10 | 0.00 | 0.00 | 0.00 | 0.117413E+11 | 77067631.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.235953E+10 | 0.00 | 0.00 | 0.00 | 0.141378E+11 | 0.162930E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.245305E+10 | 0.00 | 0.00 | 0.00 | 0.162491E+11 | 11612686.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.317676E+10 | 0.00 | 0.00 | 0.00 | 0.221134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.335294E+10 | 0.00 | 0.00 | 0.00 | 0.249298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.354870E+10 | 0.00 | 0.00 | 0.00 | 0.268207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.379460E+10 | 0.00 | 0.00 | 0.00 | 0.276815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.346357E+10 | 0.00 | 0.00 | 0.00 | 0.251778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.339741E+10 | 0.00 | 0.00 | 0.00 | 0.229034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.273966E+10 | 0.00 | 0.00 | 0.00 | 0.177689E+11 | 37356306.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.208135E+10 | 0.00 | 0.00 | 0.00 | 0.123336E+11 | 0.137823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344083E+11 | 0.00 | 0.00 | 0.00 | 0.233465E+12 | 0.642915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.198854E+10 | 0.00 | 0.00 | 0.00 | 0.116073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.379460E+10 | 0.00 | 0.00 | 0.00 | 0.276815E+11 | 0.216125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157095E+10 | 0.00 | 0.00 | 0.00 | 0.892174E+10 | 6114700.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157121E+10 | 0.00 | 0.00 | 0.00 | 0.920264E+10 | 19153368.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.195052E+10 | 0.00 | 0.00 | 0.00 | 0.112684E+11 | 2207417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.208124E+10 | 0.00 | 0.00 | 0.00 | 0.127083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.260607E+10 | 0.00 | 0.00 | 0.00 | 0.162035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.273354E+10 | 0.00 | 0.00 | 0.00 | 0.175352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.284362E+10 | 0.00 | 0.00 | 0.00 | 0.184559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.290142E+10 | 0.00 | 0.00 | 0.00 | 0.186518E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.269108E+10 | 0.00 | 0.00 | 0.00 | 0.173645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.261644E+10 | 0.00 | 0.00 | 0.00 | 0.159383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204627E+10 | 0.00 | 0.00 | 0.00 | 0.125850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162431E+10 | 0.00 | 0.00 | 0.00 | 0.943765E+10 | 8141526.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272367E+11 | 0.00 | 0.00 | 0.00 | 0.168273E+12 | 35617011.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157095E+10 | 0.00 | 0.00 | 0.00 | 0.892174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.290142E+10 | 0.00 | 0.00 | 0.00 | 0.186518E+11 | 19153368.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149764E+10 | 0.00 | 0.00 | 0.00 | 0.983311E+10 | 0.185152E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151623E+10 | 0.00 | 0.00 | 0.00 | 0.103832E+11 | 0.160752E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190912E+10 | 0.00 | 0.00 | 0.00 | 0.129003E+11 | 84846632.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210299E+10 | 0.00 | 0.00 | 0.00 | 0.154485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.265464E+10 | 0.00 | 0.00 | 0.00 | 0.210510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.279767E+10 | 0.00 | 0.00 | 0.00 | 0.238435E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.295012E+10 | 0.00 | 0.00 | 0.00 | 0.257125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.292093E+10 | 0.00 | 0.00 | 0.00 | 0.253928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.267768E+10 | 0.00 | 0.00 | 0.00 | 0.231391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248785E+10 | 0.00 | 0.00 | 0.00 | 0.202129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192410E+10 | 0.00 | 0.00 | 0.00 | 0.152822E+11 | 12681382.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156075E+10 | 0.00 | 0.00 | 0.00 | 0.106924E+11 | 0.221609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269997E+11 | 0.00 | 0.00 | 0.00 | 0.213891E+12 | 0.665040E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149764E+10 | 0.00 | 0.00 | 0.00 | 0.983311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.295012E+10 | 0.00 | 0.00 | 0.00 | 0.257125E+11 | 0.221609E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.306586E+09 | 0.320598E+10 | 0.00 | 19048280.90 | 0.502803E+09 | 0.00 | 0.261070E+10 | 0.00 | 0.38 |
February | 0.201865E+09 | 0.371810E+10 | 0.00 | 12062355.48 | 0.559049E+09 | 0.00 | 0.131917E+10 | 0.00 | 0.37 |
March | 0.198252E+09 | 0.506179E+10 | 0.00 | 15030049.43 | 0.835993E+09 | 0.00 | 0.202328E+10 | 0.00 | 0.39 |
April | 30969251.34 | 0.667927E+10 | 0.00 | 3768180.74 | 0.147398E+10 | 0.00 | 0.314244E+09 | 0.00 | 0.37 |
May | 0.00 | 0.118401E+11 | 0.00 | 0.00 | 0.216160E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.156323E+11 | 0.00 | 0.00 | 0.253790E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.157098E+11 | 0.00 | 0.00 | 0.394489E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
August | 0.00 | 0.169716E+11 | 0.00 | 0.00 | 0.287104E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.145400E+11 | 0.00 | 0.00 | 0.342034E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.00 | 0.119424E+11 | 0.00 | 0.00 | 0.265722E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
November | 0.151293E+09 | 0.886420E+10 | 0.00 | 4188242.71 | 0.126113E+10 | 0.00 | 0.288066E+09 | 0.00 | 0.35 |
December | 0.189931E+09 | 0.362673E+10 | 0.00 | 17399584.59 | 0.114038E+10 | 0.00 | 0.229420E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.107890E+10 | 0.117792E+12 | 0.00 | 71496693.85 | 0.233663E+11 | 0.00 | 0.884965E+10 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.320598E+10 | 0.00 | 0.00 | 0.502803E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.306586E+09 | 0.169716E+11 | 0.00 | 19048280.90 | 0.394489E+10 | 0.00 | 0.261070E+10 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.119328E+10 | 0.129897E+10 | 0.00 | 4370446.85 | 0.104046E+10 | 0.00 | 0.103678E+10 | 0.00 | 0.30 |
February | 0.644369E+09 | 0.160935E+10 | 0.00 | 4375436.21 | 0.103724E+10 | 0.00 | 0.609783E+09 | 0.00 | 0.30 |
March | 0.713340E+09 | 0.260768E+10 | 0.00 | 4542331.47 | 0.992730E+09 | 0.00 | 0.101354E+10 | 0.00 | 0.32 |
April | 32680236.69 | 0.306287E+10 | 0.00 | 2045094.85 | 0.109176E+10 | 0.00 | 0.251860E+09 | 0.00 | 0.31 |
May | 0.00 | 0.489702E+10 | 0.00 | 0.00 | 0.135422E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.617890E+10 | 0.00 | 0.00 | 0.145059E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.598157E+10 | 0.00 | 0.00 | 0.194879E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.664437E+10 | 0.00 | 0.00 | 0.149984E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.633855E+10 | 0.00 | 0.00 | 0.171918E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.504769E+10 | 0.00 | 0.00 | 0.136993E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
November | 0.182912E+09 | 0.380563E+10 | 0.00 | 1519461.05 | 0.948206E+09 | 0.00 | 0.130792E+09 | 0.00 | 0.30 |
December | 0.778970E+09 | 0.152913E+10 | 0.00 | 5121946.30 | 0.131051E+10 | 0.00 | 0.109319E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.354556E+10 | 0.490017E+11 | 0.00 | 21974716.73 | 0.157634E+11 | 0.00 | 0.413595E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.129897E+10 | 0.00 | 0.00 | 0.948206E+09 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.119328E+10 | 0.664437E+10 | 0.00 | 5121946.30 | 0.194879E+10 | 0.00 | 0.109319E+10 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131417E+10 | 0.138637E+10 | 0.00 | 1868914.52 | 0.204559E+10 | 205379.05 | 0.507904E+09 | 0.00 | 0.30 |
February | 0.660414E+09 | 0.183636E+10 | 0.00 | 2894634.50 | 0.192160E+10 | 967817.19 | 0.380849E+09 | 0.00 | 0.30 |
March | 0.903808E+09 | 0.305884E+10 | 0.00 | 2971399.63 | 0.200227E+10 | 0.00 | 0.624330E+09 | 0.00 | 0.31 |
April | 40259129.49 | 0.468877E+10 | 0.00 | 1838923.38 | 0.222257E+10 | 0.00 | 0.203091E+09 | 0.00 | 0.31 |
May | 0.00 | 0.992745E+10 | 0.00 | 0.00 | 0.260888E+10 | 0.00 | 0.00 | 0.00 | 0.31 |
June | 0.00 | 0.138684E+11 | 0.00 | 0.00 | 0.295515E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.141094E+11 | 0.00 | 0.00 | 0.423224E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.151711E+11 | 0.00 | 0.00 | 0.335830E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.130400E+11 | 0.00 | 0.00 | 0.361858E+10 | 0.00 | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.984675E+10 | 0.00 | 0.00 | 0.329326E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
November | 0.214238E+09 | 0.630611E+10 | 0.00 | 701139.51 | 0.284983E+10 | 0.00 | 42585790.04 | 0.00 | 0.30 |
December | 0.989150E+09 | 0.170100E+10 | 0.00 | 2476638.42 | 0.273228E+10 | 0.00 | 0.488319E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.412204E+10 | 0.949405E+11 | 0.00 | 12751649.96 | 0.338405E+11 | 1173196.24 | 0.224708E+10 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.138637E+10 | 0.00 | 0.00 | 0.192160E+10 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.131417E+10 | 0.151711E+11 | 0.00 | 2971399.63 | 0.423224E+10 | 967817.19 | 0.624330E+09 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.330585E+09 | 0.355746E+09 | 0.00 | 197370.46 | 0.405254E+09 | 7989620.85 | 43816364.74 | 0.00 | 0.31 |
February | 0.142665E+09 | 0.549851E+09 | 76052.41 | 612475.88 | 0.332579E+09 | 18711330.79 | 62179608.16 | 563.23 | 0.32 |
March | 0.235930E+09 | 0.873888E+09 | 0.00 | 522071.66 | 0.351095E+09 | 5278435.94 | 80488881.52 | 0.00 | 0.35 |
April | 9684227.89 | 0.135726E+10 | 0.00 | 430415.42 | 0.394730E+09 | 0.00 | 46247107.32 | 0.00 | 0.37 |
May | 0.00 | 0.313113E+10 | 0.00 | 0.00 | 0.424459E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.465547E+10 | 0.00 | 0.00 | 0.484951E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.498774E+10 | 0.00 | 0.00 | 0.640623E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.484258E+10 | 0.00 | 0.00 | 0.540959E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.402034E+10 | 0.00 | 0.00 | 0.636277E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 0.00 | 0.273656E+10 | 0.00 | 0.00 | 0.609540E+09 | 0.00 | 0.00 | 0.00 | 0.36 |
November | 45256136.50 | 0.177408E+10 | 0.00 | 163149.36 | 0.444998E+09 | 449617.68 | 9477632.59 | 0.00 | 0.33 |
December | 0.250881E+09 | 0.473355E+09 | 69821.85 | 290418.88 | 0.530660E+09 | 8179391.27 | 50854396.48 | 3090.70 | 0.31 |
Annual Sum or Average | 0.101500E+10 | 0.297580E+11 | 145874.26 | 2215901.66 | 0.579612E+10 | 40608396.53 | 0.293064E+09 | 3653.93 | 0.38 |
Minimum of Months | 0.00 | 0.355746E+09 | 0.00 | 0.00 | 0.332579E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.330585E+09 | 0.498774E+10 | 76052.41 | 612475.88 | 0.640623E+09 | 18711330.79 | 80488881.52 | 3090.70 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164648E+09 | 0.377900E+09 | 0.00 | 622581.23 | 0.248029E+09 | 2410314.11 | 0.132987E+09 | 0.00 | 0.39 |
February | 0.105351E+09 | 0.527979E+09 | 58397.19 | 757289.43 | 0.222129E+09 | 9111675.17 | 70187951.51 | 198.54 | 0.43 |
March | 88572057.34 | 0.850218E+09 | 0.00 | 1170967.35 | 0.225535E+09 | 2333945.81 | 0.206365E+09 | 0.00 | 0.49 |
April | 5622845.32 | 0.136860E+10 | 0.00 | 482003.41 | 0.249618E+09 | 0.00 | 49309942.76 | 0.00 | 0.54 |
May | 0.00 | 0.265350E+10 | 0.00 | 0.00 | 0.282693E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.00 | 0.376678E+10 | 0.00 | 0.00 | 0.320333E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.411903E+10 | 0.00 | 0.00 | 0.403081E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.396153E+10 | 0.00 | 0.00 | 0.399134E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.347529E+10 | 0.00 | 0.00 | 0.392269E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.246984E+10 | 0.00 | 0.00 | 0.397829E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 32358452.69 | 0.150005E+10 | 0.00 | 187843.22 | 0.318046E+09 | 118196.49 | 10293705.70 | 0.00 | 0.43 |
December | 0.159643E+09 | 0.434259E+09 | 194441.61 | 369804.20 | 0.383908E+09 | 5668171.54 | 72886394.97 | 3612.21 | 0.39 |
Annual Sum or Average | 0.556194E+09 | 0.255050E+11 | 252838.80 | 3590488.85 | 0.384261E+10 | 19642303.12 | 0.542030E+09 | 3810.75 | 0.50 |
Minimum of Months | 0.00 | 0.377900E+09 | 0.00 | 0.00 | 0.222129E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.164648E+09 | 0.411903E+10 | 194441.61 | 1170967.35 | 0.403081E+09 | 9111675.17 | 0.206365E+09 | 3612.21 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159101E+09 | 0.900190E+09 | 0.00 | 3427302.55 | 0.233583E+09 | 2841988.98 | 0.493658E+09 | 0.00 | 0.49 |
February | 91535383.65 | 0.104103E+10 | 0.00 | 2402937.64 | 0.211215E+09 | 12968005.58 | 0.250290E+09 | 0.00 | 0.48 |
March | 0.142282E+09 | 0.128601E+10 | 0.00 | 2275003.92 | 0.259373E+09 | 4803754.93 | 0.315019E+09 | 0.00 | 0.47 |
April | 9243664.68 | 0.163522E+10 | 0.00 | 583613.08 | 0.355773E+09 | 0.00 | 60699319.83 | 0.00 | 0.42 |
May | 0.00 | 0.308147E+10 | 0.00 | 0.00 | 0.442257E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.437787E+10 | 0.00 | 0.00 | 0.514985E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.481428E+10 | 0.00 | 0.00 | 0.663062E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.516956E+10 | 0.00 | 0.00 | 0.518500E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.506184E+10 | 0.00 | 0.00 | 0.493051E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.424589E+10 | 0.00 | 0.00 | 0.364512E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 27310884.02 | 0.296913E+10 | 0.00 | 861261.74 | 0.250899E+09 | 90072.96 | 46224327.58 | 0.00 | 0.50 |
December | 0.129291E+09 | 0.126024E+10 | 0.00 | 2631401.45 | 0.278424E+09 | 5098483.17 | 0.384579E+09 | 0.00 | 0.48 |
Annual Sum or Average | 0.558765E+09 | 0.358427E+11 | 0.00 | 12181520.39 | 0.458563E+10 | 25802305.63 | 0.155047E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.900190E+09 | 0.00 | 0.00 | 0.211215E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.159101E+09 | 0.516956E+10 | 0.00 | 3427302.55 | 0.663062E+09 | 12968005.58 | 0.493658E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234036E+09 | 0.292801E+09 | 0.00 | 635048.52 | 0.365226E+09 | 6777626.84 | 0.122521E+09 | 0.00 | 0.43 |
February | 0.105948E+09 | 0.458589E+09 | 65835.48 | 883006.58 | 0.306658E+09 | 15774852.79 | 0.100134E+09 | 488.91 | 0.46 |
March | 0.173264E+09 | 0.784635E+09 | 0.00 | 1172687.32 | 0.297446E+09 | 5039502.28 | 0.157438E+09 | 0.00 | 0.52 |
April | 8763192.15 | 0.128343E+10 | 0.00 | 450434.51 | 0.327247E+09 | 0.00 | 52109764.97 | 0.00 | 0.54 |
May | 0.00 | 0.254438E+10 | 0.00 | 0.00 | 0.387938E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.343550E+10 | 0.00 | 0.00 | 0.446167E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
July | 0.00 | 0.383673E+10 | 0.00 | 0.00 | 0.561491E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.387290E+10 | 0.00 | 0.00 | 0.520297E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.318286E+10 | 0.00 | 0.00 | 0.535812E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.227145E+10 | 0.00 | 0.00 | 0.535821E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 38149052.05 | 0.141004E+10 | 0.00 | 182104.24 | 0.447851E+09 | 284466.54 | 12366311.27 | 0.00 | 0.45 |
December | 0.187480E+09 | 0.447061E+09 | 218720.50 | 560739.65 | 0.443258E+09 | 7600801.57 | 88154901.54 | 5056.07 | 0.44 |
Annual Sum or Average | 0.747641E+09 | 0.238204E+11 | 284555.98 | 3884020.83 | 0.517521E+10 | 35477250.03 | 0.532725E+09 | 5544.98 | 0.51 |
Minimum of Months | 0.00 | 0.292801E+09 | 0.00 | 0.00 | 0.297446E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.234036E+09 | 0.387290E+10 | 218720.50 | 1172687.32 | 0.561491E+09 | 15774852.79 | 0.157438E+09 | 5056.07 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.358557E+09 | 0.417024E+09 | 0.00 | 411481.92 | 0.227296E+09 | 0.00 | 85537968.15 | 0.00 | 0.29 |
February | 0.183002E+09 | 0.521037E+09 | 0.00 | 614904.04 | 0.230083E+09 | 0.00 | 63685998.71 | 0.00 | 0.29 |
March | 0.269537E+09 | 0.729851E+09 | 0.00 | 375240.72 | 0.314141E+09 | 0.00 | 59693640.10 | 0.00 | 0.30 |
April | 14523883.67 | 0.113502E+10 | 0.00 | 343182.67 | 0.390393E+09 | 0.00 | 37976034.55 | 0.00 | 0.31 |
May | 0.00 | 0.245183E+10 | 0.00 | 0.00 | 0.495610E+09 | 0.00 | 0.00 | 0.00 | 0.34 |
June | 0.00 | 0.359995E+10 | 0.00 | 0.00 | 0.578675E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.392041E+10 | 0.00 | 0.00 | 0.839612E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.396570E+10 | 0.00 | 0.00 | 0.630668E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.337485E+10 | 0.00 | 0.00 | 0.722155E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.00 | 0.241287E+10 | 0.00 | 0.00 | 0.615697E+09 | 0.00 | 0.00 | 0.00 | 0.33 |
November | 55781862.82 | 0.163237E+10 | 0.00 | 306009.26 | 0.308637E+09 | 0.00 | 16246739.94 | 0.00 | 0.30 |
December | 0.271158E+09 | 0.535550E+09 | 0.00 | 626417.04 | 0.364677E+09 | 0.00 | 0.104515E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.115256E+10 | 0.246965E+11 | 0.00 | 2677235.67 | 0.571764E+10 | 0.00 | 0.367655E+09 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.417024E+09 | 0.00 | 0.00 | 0.227296E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.358557E+09 | 0.396570E+10 | 0.00 | 626417.04 | 0.839612E+09 | 0.00 | 0.104515E+09 | 0.00 | 0.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.153916E+09 | 0.418236E+09 | 0.00 | 1259928.68 | 94951405.87 | 0.00 | 0.189914E+09 | 0.00 | 0.36 |
February | 82342986.60 | 0.500727E+09 | 0.00 | 1178612.05 | 0.105834E+09 | 0.00 | 0.111401E+09 | 0.00 | 0.38 |
March | 82916876.58 | 0.753854E+09 | 0.00 | 1416352.16 | 0.135698E+09 | 0.00 | 0.211133E+09 | 0.00 | 0.42 |
April | 6469736.07 | 0.117114E+10 | 0.00 | 474187.93 | 0.195704E+09 | 0.00 | 46201314.21 | 0.00 | 0.45 |
May | 0.00 | 0.212267E+10 | 0.00 | 0.00 | 0.293816E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.302199E+10 | 0.00 | 0.00 | 0.299836E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.342926E+10 | 0.00 | 0.00 | 0.354770E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.336407E+10 | 0.00 | 0.00 | 0.302947E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.298492E+10 | 0.00 | 0.00 | 0.350575E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.215311E+10 | 0.00 | 0.00 | 0.350815E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 31228809.68 | 0.134267E+10 | 0.00 | 409457.41 | 0.191446E+09 | 0.00 | 24181765.92 | 0.00 | 0.38 |
December | 0.129664E+09 | 0.467044E+09 | 0.00 | 955294.03 | 0.221104E+09 | 0.00 | 0.143923E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.486539E+09 | 0.217297E+11 | 0.00 | 5693832.26 | 0.289750E+10 | 0.00 | 0.726753E+09 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.418236E+09 | 0.00 | 0.00 | 94951405.87 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.153916E+09 | 0.342926E+10 | 0.00 | 1416352.16 | 0.354770E+09 | 0.00 | 0.211133E+09 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212336E+09 | 0.900033E+09 | 8132.44 | 2564710.97 | 0.105987E+09 | 58961300.02 | 0.332084E+09 | 556.50 | 0.43 |
February | 0.127945E+09 | 0.991261E+09 | 36835.44 | 2672680.10 | 0.131880E+09 | 26912113.57 | 0.183828E+09 | 244.21 | 0.44 |
March | 0.203646E+09 | 0.121678E+10 | 0.00 | 1335917.20 | 0.214325E+09 | 59438254.03 | 0.129673E+09 | 0.00 | 0.41 |
April | 16025529.68 | 0.157685E+10 | 0.00 | 349388.61 | 0.358981E+09 | 1632499.42 | 38718781.32 | 0.00 | 0.39 |
May | 0.00 | 0.292687E+10 | 0.00 | 0.00 | 0.508979E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.418676E+10 | 0.00 | 0.00 | 0.561802E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.466991E+10 | 0.00 | 0.00 | 0.814138E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.522770E+10 | 0.00 | 0.00 | 0.534607E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.491568E+10 | 0.00 | 0.00 | 0.518409E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.416873E+10 | 0.00 | 0.00 | 0.343105E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
November | 32210298.84 | 0.284323E+10 | 0.00 | 1015329.24 | 0.213990E+09 | 11910149.74 | 47382696.44 | 0.00 | 0.47 |
December | 0.168809E+09 | 0.124413E+10 | 827691.30 | 1807753.24 | 0.180264E+09 | 46542485.55 | 0.277184E+09 | 7041.28 | 0.43 |
Annual Sum or Average | 0.760970E+09 | 0.348679E+11 | 872659.18 | 9745779.36 | 0.448647E+10 | 0.205397E+09 | 0.100887E+10 | 7841.99 | 0.44 |
Minimum of Months | 0.00 | 0.900033E+09 | 0.00 | 0.00 | 0.105987E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.212336E+09 | 0.522770E+10 | 827691.30 | 2672680.10 | 0.814138E+09 | 59438254.03 | 0.332084E+09 | 7041.28 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.202305E+09 | 0.371231E+09 | 0.00 | 945680.36 | 0.120229E+09 | 0.00 | 0.151814E+09 | 0.00 | 0.35 |
February | 0.112206E+09 | 0.479928E+09 | 0.00 | 1035696.23 | 0.113895E+09 | 0.00 | 88794531.53 | 0.00 | 0.37 |
March | 0.149654E+09 | 0.739311E+09 | 0.00 | 1087695.37 | 0.147127E+09 | 0.00 | 0.128552E+09 | 0.00 | 0.42 |
April | 7624148.72 | 0.118645E+10 | 0.00 | 417529.95 | 0.179027E+09 | 0.00 | 43023046.05 | 0.00 | 0.44 |
May | 0.00 | 0.212371E+10 | 0.00 | 0.00 | 0.274321E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.275048E+10 | 0.00 | 0.00 | 0.349836E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.321575E+10 | 0.00 | 0.00 | 0.438941E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.334720E+10 | 0.00 | 0.00 | 0.325904E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.279815E+10 | 0.00 | 0.00 | 0.376389E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.00 | 0.209298E+10 | 0.00 | 0.00 | 0.334630E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
November | 37603400.76 | 0.133552E+10 | 0.00 | 314393.75 | 0.192757E+09 | 0.00 | 16659644.95 | 0.00 | 0.38 |
December | 0.151459E+09 | 0.499738E+09 | 0.00 | 960882.36 | 0.219164E+09 | 0.00 | 0.141611E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.660851E+09 | 0.209404E+11 | 0.00 | 4761878.02 | 0.307222E+10 | 0.00 | 0.570454E+09 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.371231E+09 | 0.00 | 0.00 | 0.113895E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.202305E+09 | 0.334720E+10 | 0.00 | 1087695.37 | 0.438941E+09 | 0.00 | 0.151814E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.394812E+09 | 0.292304E+09 | 0.00 | 314160.44 | 0.215182E+09 | 262461.19 | 66943118.25 | 0.00 | 0.31 |
February | 0.184681E+09 | 0.397299E+09 | 0.00 | 692423.64 | 0.202354E+09 | 2004076.49 | 76790138.39 | 0.00 | 0.32 |
March | 0.277321E+09 | 0.640691E+09 | 0.00 | 527246.77 | 0.201799E+09 | 0.00 | 78450563.39 | 0.00 | 0.35 |
April | 12111585.61 | 0.787736E+09 | 0.00 | 404151.40 | 0.212295E+09 | 0.00 | 50873109.17 | 0.00 | 0.37 |
May | 0.00 | 0.144672E+10 | 0.00 | 0.00 | 0.256510E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.200584E+10 | 0.00 | 0.00 | 0.264862E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 0.00 | 0.202676E+10 | 0.00 | 0.00 | 0.357492E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.205660E+10 | 0.00 | 0.00 | 0.263337E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 0.00 | 0.182766E+10 | 0.00 | 0.00 | 0.340201E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 0.00 | 0.129241E+10 | 0.00 | 0.00 | 0.291994E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
November | 51980931.32 | 0.911068E+09 | 0.00 | 241442.83 | 0.207065E+09 | 0.00 | 13631531.33 | 0.00 | 0.33 |
December | 0.304024E+09 | 0.343005E+09 | 0.00 | 450951.77 | 0.284145E+09 | 0.00 | 81199384.52 | 0.00 | 0.31 |
Annual Sum or Average | 0.122493E+10 | 0.140281E+11 | 0.00 | 2630376.85 | 0.309724E+10 | 2266537.68 | 0.367888E+09 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.292304E+09 | 0.00 | 0.00 | 0.201799E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.394812E+09 | 0.205660E+10 | 0.00 | 692423.64 | 0.357492E+09 | 2004076.49 | 81199384.52 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195517E+09 | 0.261160E+09 | 0.00 | 846498.82 | 0.150853E+09 | 200797.31 | 0.183728E+09 | 0.00 | 0.40 |
February | 0.126060E+09 | 0.349932E+09 | 0.00 | 939808.95 | 0.147958E+09 | 375855.89 | 94005064.33 | 0.00 | 0.44 |
March | 0.105389E+09 | 0.593985E+09 | 0.00 | 1323841.56 | 0.129599E+09 | 117888.21 | 0.249170E+09 | 0.00 | 0.49 |
April | 8532752.13 | 0.751252E+09 | 0.00 | 459635.63 | 0.146915E+09 | 0.00 | 53590154.01 | 0.00 | 0.53 |
May | 0.00 | 0.118304E+10 | 0.00 | 0.00 | 0.188885E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.00 | 0.159374E+10 | 0.00 | 0.00 | 0.182106E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.166540E+10 | 0.00 | 0.00 | 0.216668E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.165697E+10 | 0.00 | 0.00 | 0.178366E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.153881E+10 | 0.00 | 0.00 | 0.220934E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.109971E+10 | 0.00 | 0.00 | 0.215613E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 32996029.95 | 0.759977E+09 | 0.00 | 295574.75 | 0.150154E+09 | 0.00 | 21422246.91 | 0.00 | 0.43 |
December | 0.185594E+09 | 0.276012E+09 | 0.00 | 506179.91 | 0.226245E+09 | 165728.28 | 0.115150E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.654088E+09 | 0.117300E+11 | 0.00 | 4371539.62 | 0.215430E+10 | 860269.68 | 0.717066E+09 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.261160E+09 | 0.00 | 0.00 | 0.129599E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.195517E+09 | 0.166540E+10 | 0.00 | 1323841.56 | 0.226245E+09 | 375855.89 | 0.249170E+09 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198511E+09 | 0.611990E+09 | 0.00 | 3826861.92 | 0.107285E+09 | 0.00 | 0.584066E+09 | 0.00 | 0.50 |
February | 0.129809E+09 | 0.694916E+09 | 0.00 | 2762126.32 | 0.110932E+09 | 293257.92 | 0.252619E+09 | 0.00 | 0.49 |
March | 0.161108E+09 | 0.894225E+09 | 0.00 | 2384465.55 | 0.130967E+09 | 0.00 | 0.336919E+09 | 0.00 | 0.47 |
April | 13574467.38 | 0.916374E+09 | 0.00 | 540124.86 | 0.196705E+09 | 0.00 | 62585317.16 | 0.00 | 0.42 |
May | 0.00 | 0.143336E+10 | 0.00 | 0.00 | 0.255753E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.189439E+10 | 0.00 | 0.00 | 0.272675E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.196456E+10 | 0.00 | 0.00 | 0.359228E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.220016E+10 | 0.00 | 0.00 | 0.245276E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.226930E+10 | 0.00 | 0.00 | 0.269832E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.189924E+10 | 0.00 | 0.00 | 0.199375E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 32009943.55 | 0.144520E+10 | 0.00 | 997162.79 | 0.119368E+09 | 0.00 | 55704860.11 | 0.00 | 0.50 |
December | 0.159193E+09 | 0.756394E+09 | 0.00 | 2999388.77 | 0.164101E+09 | 0.00 | 0.486700E+09 | 0.00 | 0.50 |
Annual Sum or Average | 0.694206E+09 | 0.169801E+11 | 0.00 | 13510130.21 | 0.243150E+10 | 293257.92 | 0.177859E+10 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.611990E+09 | 0.00 | 0.00 | 0.107285E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.198511E+09 | 0.226930E+10 | 0.00 | 3826861.92 | 0.359228E+09 | 293257.92 | 0.584066E+09 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.271437E+09 | 0.221674E+09 | 0.00 | 747732.26 | 0.192074E+09 | 212045.51 | 0.142407E+09 | 0.00 | 0.42 |
February | 0.138523E+09 | 0.335383E+09 | 0.00 | 963188.89 | 0.159446E+09 | 1872658.69 | 0.100047E+09 | 0.00 | 0.44 |
March | 0.192718E+09 | 0.556052E+09 | 0.00 | 1153000.68 | 0.153442E+09 | 124492.04 | 0.150770E+09 | 0.00 | 0.50 |
April | 11047061.13 | 0.722848E+09 | 0.00 | 428308.52 | 0.167549E+09 | 0.00 | 52814934.71 | 0.00 | 0.53 |
May | 0.00 | 0.118317E+10 | 0.00 | 0.00 | 0.193946E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 0.00 | 0.148478E+10 | 0.00 | 0.00 | 0.211966E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
July | 0.00 | 0.159448E+10 | 0.00 | 0.00 | 0.252867E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.167660E+10 | 0.00 | 0.00 | 0.192346E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.146167E+10 | 0.00 | 0.00 | 0.236799E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.00 | 0.105453E+10 | 0.00 | 0.00 | 0.235455E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
November | 41371159.79 | 0.717275E+09 | 0.00 | 240911.01 | 0.179657E+09 | 0.00 | 15079302.75 | 0.00 | 0.43 |
December | 0.222285E+09 | 0.302627E+09 | 0.00 | 684668.73 | 0.228205E+09 | 293425.48 | 0.111851E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.877381E+09 | 0.113111E+11 | 0.00 | 4217810.08 | 0.240375E+10 | 2502621.72 | 0.572969E+09 | 0.00 | 0.50 |
Minimum of Months | 0.00 | 0.221674E+09 | 0.00 | 0.00 | 0.153442E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.271437E+09 | 0.167660E+10 | 0.00 | 1153000.68 | 0.252867E+09 | 1872658.69 | 0.150770E+09 | 0.00 | 0.57 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:20
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.201286E+12 | 0.411904E+09 | 0.00 | -0.105109E+11 | 0.155024E+12 |
February | 0.213640E+12 | -806676856.3 | 0.00 | -0.187705E+11 | 0.160914E+12 |
March | 0.286912E+12 | -0.148879E+10 | 0.00 | -0.342927E+11 | 0.197368E+12 |
April | 0.304663E+12 | -0.328896E+10 | 0.00 | -0.629359E+11 | 0.226279E+12 |
May | 0.289657E+12 | -0.725685E+10 | 0.00 | -0.120106E+12 | 0.297613E+12 |
June | 0.259823E+12 | -0.859628E+10 | 0.00 | -0.159130E+12 | 0.331784E+12 |
July | 0.283806E+12 | -0.841682E+10 | 0.00 | -0.172453E+12 | 0.348728E+12 |
August | 0.307864E+12 | -0.951601E+10 | 0.00 | -0.174978E+12 | 0.355132E+12 |
September | 0.238077E+12 | -0.794487E+10 | 0.00 | -0.157517E+12 | 0.327605E+12 |
October | 0.239749E+12 | -0.676762E+10 | 0.00 | -0.131162E+12 | 0.297437E+12 |
November | 0.181615E+12 | -0.395254E+10 | 0.00 | -0.791401E+11 | 0.234297E+12 |
December | 0.195086E+12 | -464566195.8 | 0.00 | -0.340964E+11 | 0.166480E+12 |
Annual Sum or Average | 0.300218E+13 | -0.580881E+11 | 0.00 | -0.115509E+13 | 0.309866E+13 |
Minimum of Months | 0.181615E+12 | -0.951601E+10 | 0.00 | -0.174978E+12 | 0.155024E+12 |
Maximum of Months | 0.307864E+12 | 0.411904E+09 | 0.00 | -0.105109E+11 | 0.355132E+12 |