Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2023-10-16 08:35:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2057.19 | 412.91 | 412.91 |
Net Site Energy | 2057.19 | 412.91 | 412.91 |
Total Source Energy | 5492.19 | 1102.36 | 1102.36 |
Net Source Energy | 5492.19 | 1102.36 | 1102.36 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 371.42 | 375.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 132.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 203.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 91.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 116.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1566.10 | 491.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 371.42 | 375.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 132.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 203.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 50.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 584.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 0.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 91.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Water Heater | 0.00 | 116.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 371.42 | 375.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 132.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 203.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 50.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 705.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 11.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 91.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 116.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 119.50 | 98.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 314.34 | 98.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 50.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 119.50 | 98.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 314.34 | 98.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1566.105 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1566.105 | 100.00 |
Total On-Site and Utility Electric Sources | 1566.105 | 100.00 |
Total Electricity End Uses | 1566.105 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 794.83 |
Time Setpoint Not Met During Occupied Cooling | 102.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3256.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT HEATING COIL | PACU_VAV_MID HEATING COIL | PACU_VAV_TOP HEATING COIL | PACU_VAV_BOT COOLING COIL | PACU_VAV_MID COOLING COIL | PACU_VAV_TOP COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:35 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 593.29 | 177.99 | 118.66 | 177.99 | 118.66 |
Gross Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 24.8342 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 59.33 | 59.33 | 5.9322 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 39.55 | 39.55 | 5.9322 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 593.29 | 593.29 | 5.9322 | 18.58 | 11.3794 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
CORE_BOTTOM | 983.54 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 5.9322 | 18.58 | 24.8342 | |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 1.00 | FIRSTFLOOR_PLENUM | GENERAL | FIRSTFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 1.00 | CORE_MID | GENERAL | CORE_MID | 5.9322 | 18.58 | 8.0700 | |
CORE_TOP | 983.54 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 5.9322 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 5.9322 | 18.58 | 8.0695 | |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 5.9322 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 1.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 5.9322 | 18.58 | 8.0700 | |
Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Conditioned Total | 4982.19 | 5.9322 | 9.29 | 11.3794 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 4982.19 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 4982.19 | 4982.19 | 0.00 | 4982.19 | 5.9322 | 18.58 | 11.3794 |
Total | 4982.19 | 4982.19 | 0.00 | 4982.19 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-07:10 | 02-FEB-08:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-12:09 |
Heating | 201104.60 | 189408.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7126.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 21098.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 243.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7319.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 8600.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 242450.80 | 198009.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 201104.60 | 189408.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 7126.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 15327.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 5727.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 43.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 243.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 7319.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 8600.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 1176.29 | 406.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 644.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 159.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2234.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 36.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 290.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 125.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4959.85 | 532.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 236.10 | 81.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 84.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 58.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 995.52 | 106.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 236.10 | 81.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 84.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 129.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 31.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 448.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 7.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 58.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 25.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 995.52 | 106.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 2.84 | 0.264206 | 0.273000 | 0.774401 | 0.704549 | 0.500000 | 0.001442 |
CORE_MID VAV BOX COMPONENT | 2.05 | 0.365756 | 0.364000 | 0.745858 | 0.975348 | 0.500000 | 0.001042 |
CORE_TOP VAV BOX COMPONENT | 2.17 | 0.345611 | 0.359000 | 0.778489 | 0.921629 | 0.500000 | 0.001102 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.699414 | 0.225891 | 0.247000 | 0.172755 | 0.602377 | 0.500000 | 0.001687 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.800106 | 0.125011 | 0.200000 | 0.160021 | 0.333362 | 0.500000 | 0.003048 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.979482 | 0.161301 | 0.200000 | 0.195896 | 0.430137 | 0.500000 | 0.002362 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.879120 | 0.113767 | 0.200000 | 0.175824 | 0.303380 | 0.500000 | 0.003349 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.526236 | 0.300229 | 0.317000 | 0.166817 | 0.800612 | 0.500000 | 0.001269 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.647352 | 0.154509 | 0.200000 | 0.129470 | 0.412024 | 0.500000 | 0.002466 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.771596 | 0.204759 | 0.211000 | 0.162807 | 0.546025 | 0.500000 | 0.001861 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.691526 | 0.144630 | 0.200000 | 0.138305 | 0.385679 | 0.500000 | 0.002634 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.573816 | 0.275335 | 0.274000 | 0.157225 | 0.734227 | 0.500000 | 0.001384 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.780448 | 0.128160 | 0.200000 | 0.156090 | 0.341759 | 0.500000 | 0.002973 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 0.881584 | 0.179213 | 0.200000 | 0.176317 | 0.477902 | 0.500000 | 0.002126 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.805011 | 0.124241 | 0.200000 | 0.161002 | 0.331309 | 0.500000 | 0.003067 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 24669.71 |
CORE_MID VAV BOX REHEAT COIL | 26564.63 |
CORE_TOP VAV BOX REHEAT COIL | 47195.69 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22280.91 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14428.91 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22043.76 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14575.91 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16764.06 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10942.84 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16577.87 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11065.64 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 17050.36 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 11096.66 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 16843.08 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 11221.81 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.74 | 1.37 | 5.47 | 2.18 | 4.81 | 4.81 | 0.300000 | 0.452690 | 4.81 |
PACU_VAV_MID | 2.54 | 1.40 | 5.09 | 2.60 | 4.25 | 4.25 | 0.300000 | 0.611701 | 4.25 |
PACU_VAV_TOP | 2.76 | 1.48 | 5.53 | 3.78 | 4.95 | 4.95 | 0.300000 | 0.765070 | 4.95 |
Maximum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 4.81 |
PACU_VAV_MID_OA_CONTROLLER | 4.25 |
PACU_VAV_TOP_OA_CONTROLLER | 4.95 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT COOLING COIL | 4.81 | 106196.35 | 0.739865 | 1.60 | 35395.24 | 0.739865 |
PACU_VAV_MID COOLING COIL | 4.25 | 97388.68 | 0.726456 | 1.42 | 32459.65 | 0.726456 |
PACU_VAV_TOP COOLING COIL | 4.95 | 108735.15 | 0.740783 | 1.65 | 36241.43 | 0.740783 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT HEATING COIL | 52075.52 |
PACU_VAV_MID HEATING COIL | 53368.17 |
PACU_VAV_TOP HEATING COIL | 52864.73 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 4.81 |
PACU_VAV_MID FAN | 4.25 |
PACU_VAV_TOP FAN | 4.95 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000054 | 0.726125 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 73.69 | 59.33 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 49.77 | 39.55 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 77.59 | 59.33 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 51.72 | 39.55 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 24.834 | 0.000 | 0.000 | 0.000 | 0.000 | 30.766 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 5.932 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 14.002 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
2 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
3 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 983.54 | 52.9 | 5834.488 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5834.488 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
12 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
13 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 778.667 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.667 |
14 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1229.961 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1229.961 |
15 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 778.616 | 5.932 | 110.212 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 778.616 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 16363.220 | 16.637 | 309.098 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 1963.586 | 11290.622 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_ADD_DF | CORE_BOTTOM | 983.54 | 52.9 | 125.000 | 0.127 | 2.361 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 0.000 | 86.250 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.8230 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.8078 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
10 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 1.150 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
11 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.2198 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2318 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 43 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9811 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
18 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.004 |
20 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
21 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
22 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
23 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6352 |
24 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
25 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
27 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.237 |
28 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
29 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.474 |
30 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
31 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.236 |
32 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
33 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
34 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
39 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
40 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
41 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
42 | 7 | -0.29271718E-12 | 0.39018976E-14 | -0.95409794E-13 | 0.14031862E-15 |
43 | 6 | 0.28119875E-07 | 0.23018622E-09 | 0.64462818E-08 | -0.13223787E-12 |
44 | 5 | -0.18730445E-03 | 0.19766612E-05 | -0.96378477E-04 | 0.63741704E-08 |
45 | 4 | 0.28886303 | 0.96488018E-03 | 0.98502618E-01 | -0.33108066E-04 |
46 | 3 | -7.2012884 | 0.29969116E-01 | -2.3196140 | 0.28690299E-01 |
47 | 2 | 40.656634 | 0.10677685 | 15.185922 | -0.33095131 |
48 | 1 | -80.381403 | 0.48271972E-01 | -29.070695 | 1.0751162 |
49 | 0 | 46.824340 | 0.97281563E-03 | 16.292938 | |
50 | 7 | -0.29698131E-12 | 0.16309180E-14 | -0.96973160E-13 | 0.14287369E-15 |
51 | 6 | 0.28300742E-07 | 0.22637461E-09 | 0.64862022E-08 | -0.13325668E-12 |
52 | 5 | -0.18822477E-03 | 0.19416323E-05 | -0.96839913E-04 | 0.64130988E-08 |
53 | 4 | 0.28994290 | 0.94679318E-03 | 0.98890842E-01 | -0.33260122E-04 |
54 | 3 | -7.2226813 | 0.29380190E-01 | -2.3259615 | 0.28795119E-01 |
55 | 2 | 40.727196 | 0.10459334 | 15.211975 | -0.33173716 |
56 | 1 | -80.435484 | 0.47251308E-01 | -29.094057 | 1.0762686 |
57 | 0 | 46.824339 | 0.95158293E-03 | 16.292375 | |
58 | 7 | -0.28880029E-12 | 0.14052396E-14 | -0.89944031E-13 | 0.19390441E-15 |
59 | 6 | 0.24186151E-07 | 0.30632773E-09 | 0.55779829E-08 | -0.11129316E-12 |
60 | 5 | -0.16705207E-03 | 0.27050648E-05 | -0.86187518E-04 | 0.55256261E-08 |
61 | 4 | 0.26475108 | 0.13534316E-02 | 0.89851259E-01 | -0.29749003E-04 |
62 | 3 | -6.7227801 | 0.42963698E-01 | -2.1776942 | 0.26348129E-01 |
63 | 2 | 39.077370 | 0.15602542 | 14.601354 | -0.31336847 |
64 | 1 | -79.169997 | 0.71710627E-01 | -28.545908 | 1.0493028 |
65 | 0 | 46.824348 | 0.14688112E-02 | 16.306008 | |
66 | 7 | -0.19168505E-08 | -0.51383041E-15 | 0.68469349E-14 | -0.93730203E-16 |
67 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
68 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
69 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
70 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
71 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
72 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
73 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
74 | 7 | -0.18147523E-08 | -0.43765969E-15 | 0.59880535E-14 | -0.82299290E-16 |
75 | 6 | 0.64914511E-05 | 0.44428550E-08 | 0.31873263E-02 | -0.26737964E-04 |
76 | 5 | -0.46689866E-03 | 0.26323880E-05 | -0.22358000 | 0.19548742E-02 |
77 | 4 | 0.10740407E-01 | 0.11982633E-03 | 4.8271378 | -0.45241835E-01 |
78 | 3 | -0.94318369E-01 | 0.95296379E-03 | -38.007814 | 0.39850340 |
79 | 2 | 0.33490849 | 0.15853305E-02 | 116.45748 | -1.4175852 |
80 | 1 | -0.48339250 | 0.48313585E-03 | -143.89172 | 2.0487838 |
81 | 0 | 0.23567793 | 0.11657420E-04 | 60.838472 | |
82 | 7 | -0.19168505E-08 | -0.51383063E-15 | 0.68469351E-14 | -0.93730206E-16 |
83 | 6 | 0.61617009E-05 | 0.42103975E-08 | 0.31882761E-02 | -0.26745931E-04 |
84 | 5 | -0.44250412E-03 | 0.24935927E-05 | -0.22363399 | 0.19553507E-02 |
85 | 4 | 0.10175003E-01 | 0.11350545E-03 | 4.8280370 | -0.45250478E-01 |
86 | 3 | -0.89340535E-01 | 0.90260008E-03 | -38.012894 | 0.39855955 |
87 | 2 | 0.31721614 | 0.15015396E-02 | 116.46736 | -1.4177174 |
88 | 1 | -0.45784565 | 0.45746588E-03 | -143.89754 | 2.0488794 |
89 | 0 | 0.22322007 | 0.11078117E-04 | 60.838472 | |
90 | 7 | -0.18146260E-08 | -0.43662845E-15 | 0.62700332E-14 | -0.82012168E-16 |
91 | 6 | 0.64918823E-05 | 0.44431590E-08 | 0.31873251E-02 | -0.26737954E-04 |
92 | 5 | -0.46693053E-03 | 0.26325692E-05 | -0.22357993 | 0.19548736E-02 |
93 | 4 | 0.10741146E-01 | 0.11983458E-03 | 4.8271366 | -0.45241823E-01 |
94 | 3 | -0.94324870E-01 | 0.95302955E-03 | -38.007807 | 0.39850333 |
95 | 2 | 0.33493160 | 0.15854399E-02 | 116.45746 | -1.4175850 |
96 | 1 | -0.48342587 | 0.48316934E-03 | -143.89172 | 2.0487836 |
97 | 0 | 0.23569420 | 0.11658190E-04 | 60.838472 | |
98 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
99 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
100 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
101 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
102 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
103 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
104 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
105 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
106 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3425_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 1.946 | 1.946 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 1.946 | 1.946 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.3425_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 1.946 | 1.946 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 1.946 | 1.946 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.81926E-002 | 0.29373 | 0.50259 | 0.50259 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11205 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.81926E-002 | 0.29373 | 0.50259 | 0.50259 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11205 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.81926E-002 | 0.29373 | 0.50259 | 0.50259 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11205 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.81926E-002 | 0.29373 | 0.50259 | 0.50259 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11205 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_TOP_ZN_3 | 1 | 0 |
2 | PERIMETER_TOP_ZN_2 | 1 | 0 |
3 | PERIMETER_TOP_ZN_1 | 1 | 0 |
4 | PERIMETER_TOP_ZN_4 | 1 | 0 |
5 | PERIMETER_BOT_ZN_3 | 3 | 0 |
6 | PERIMETER_BOT_ZN_2 | 2 | 0 |
7 | PERIMETER_BOT_ZN_1 | 3 | 0 |
8 | PERIMETER_BOT_ZN_4 | 2 | 0 |
9 | PERIMETER_MID_ZN_3 | 1 | 0 |
10 | PERIMETER_MID_ZN_2 | 1 | 0 |
11 | PERIMETER_MID_ZN_1 | 1 | 0 |
12 | PERIMETER_MID_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_TOP_ZN_3 | 0 | |
2 | PERIMETER_TOP_ZN_2 | 0 | |
3 | PERIMETER_TOP_ZN_1 | 0 | |
4 | PERIMETER_TOP_ZN_4 | 0 | |
5 | PERIMETER_BOT_ZN_3 | 0 | |
6 | PERIMETER_BOT_ZN_2 | 0 | |
7 | PERIMETER_BOT_ZN_1 | 0 | |
8 | PERIMETER_BOT_ZN_4 | 0 | |
9 | PERIMETER_MID_ZN_3 | 0 | |
10 | PERIMETER_MID_ZN_2 | 0 | |
11 | PERIMETER_MID_ZN_1 | 0 | |
12 | PERIMETER_MID_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.3785 | 29307.1 | 1.024 | 0.2440 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.43 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.43 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.215E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.231E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.215E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.231E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 3.119E-002 | 1.504E-004 | 2.278E-004 | 0.197 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 2.080E-002 | 1.584E-004 | 2.278E-004 | 0.208 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.278E-004 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.278E-004 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 4.621E-002 | 2.783E-005 | 2.480E-005 | 8.216E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0341E-002 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0399E-002 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1485E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1536E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8757E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9164E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6395E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6611E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1446 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0075E-002 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1652 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.1419E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1016 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3926E-002 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2271E-002 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5852E-002 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.0342E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0409E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1487E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1547E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.8770E-003 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9234E-003 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.6393E-003 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6609E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5344E-002 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8413E-002 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2435E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5944E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4040E-002 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2291E-002 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9184E-002 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3003E-002 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7806E-004 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8042E-004 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5234E-004 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.5405E-004 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1852E-004 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1911E-004 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2478E-004 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2552E-004 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9126E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9641E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2684E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3100E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8363E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8672E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6393E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6609E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.7392E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2033E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8914E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6815E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7689E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1716E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.2271E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5852E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9124E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.9645E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2679E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.3089E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8351E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8623E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6395E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6611E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6341E-002 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3985E-002 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1116E-002 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0353E-002 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6852E-002 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8882E-002 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9184E-002 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3003E-002 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2289E-004 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2976E-004 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8260E-004 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9021E-004 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7643E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7914E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2479E-004 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2553E-004 |
81 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1423 |
82 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.4965E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1598 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1078 |
85 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1075 |
86 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.4684E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7521E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.2047E-002 |
89 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2800E-002 |
90 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6989E-002 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.0107E-002 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4647E-002 |
93 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2139E-002 |
94 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1261E-002 |
95 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8008E-002 |
96 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2370E-002 |
97 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2263E-002 |
98 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8331E-002 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3273E-002 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2243E-002 |
101 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2034E-002 |
102 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6718E-002 |
103 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7521E-002 |
104 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2047E-002 |
105 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.4144E-002 |
106 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2782E-002 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.9227E-002 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9337E-002 |
109 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.5209E-002 |
110 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8011E-002 |
111 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8008E-002 |
112 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2371E-002 |
113 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1423 |
114 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.4957E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1598 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1078 |
117 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1075 |
118 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.4678E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7517E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.2044E-002 |
121 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.2800E-002 |
122 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6987E-002 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.0107E-002 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4645E-002 |
125 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.2136E-002 |
126 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1258E-002 |
127 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8004E-002 |
128 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2368E-002 |
129 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2265E-002 |
130 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8330E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3275E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2243E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2033E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6716E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7517E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2044E-002 |
137 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.4145E-002 |
138 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2781E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.9228E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9335E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.5207E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8008E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8005E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2369E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 37551.32127 | 37551.32127 | 2.83663 | 2.83663 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
2 | CORE_BOTTOM | Heating | 10081.16718 | 10081.16718 | 0.45315 | 0.45315 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
3 | CORE_MID | Cooling | 27160.20706 | 27160.20706 | 2.04906 | 2.04906 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
4 | CORE_MID | Heating | 18749.67630 | 18749.67630 | 0.83388 | 0.83388 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
5 | CORE_TOP | Cooling | 28467.61786 | 28467.61786 | 2.16849 | 2.16849 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 30.98800 | 1.53647E-002 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
6 | CORE_TOP | Heating | 33200.14353 | 33200.14353 | 1.48151 | 1.48151 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 983.53657 | 52.93867 | 0.42469 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8727.11688 | 8727.11688 | 0.66481 | 0.66481 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 15637.06936 | 15637.06936 | 0.69941 | 0.69941 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 10503.22239 | 10503.22239 | 0.80011 | 0.80011 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.97067 | 1.53554E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 10126.03256 | 10126.03256 | 0.45293 | 0.45293 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 12857.91426 | 12857.91426 | 0.97948 | 0.97948 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 31.02333 | 1.53648E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 15470.95806 | 15470.95806 | 0.69197 | 0.69197 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 11540.47761 | 11540.47761 | 0.87912 | 0.87912 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 10229.00270 | 10229.00270 | 0.45755 | 0.45755 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6756.74819 | 6756.74819 | 0.51470 | 0.51470 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53651E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 11771.40588 | 11771.40588 | 0.52624 | 0.52624 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 8498.19505 | 8498.19505 | 0.64735 | 0.64735 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 26.27100 | 1.53560E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 7683.29771 | 7683.29771 | 0.34350 | 0.34350 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 10129.18891 | 10129.18891 | 0.77160 | 0.77160 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 31.11167 | 1.53649E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 11641.00349 | 11641.00349 | 0.52039 | 0.52039 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 9078.11336 | 9078.11336 | 0.69153 | 0.69153 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 28.39100 | 1.53599E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 7769.30438 | 7769.30438 | 0.34736 | 0.34736 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7532.61355 | 7532.61355 | 0.57382 | 0.57382 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.33100 | 1.53579E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 11972.79766 | 11972.79766 | 0.53522 | 0.53522 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 10245.26404 | 10245.26404 | 0.78045 | 0.78045 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53543E-002 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 7791.59848 | 7791.59848 | 0.34833 | 0.34833 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.26219 | 7.06516 | 5.66790E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 11572.87034 | 11572.87034 | 0.88158 | 0.88158 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 11827.61539 | 11827.61539 | 0.52872 | 0.52872 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 207.33814 | 11.15994 | 8.95286E-002 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 10567.71737 | 10567.71737 | 0.80501 | 0.80501 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53617E-002 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 7879.25456 | 7879.25456 | 0.35226 | 0.35226 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 131.25358 | 7.06470 | 5.66753E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 72132.21 | 4.81365 | 4.81365 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 53203.30 | 2.17909 | 2.17909 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 64740.64 | 4.24785 | 4.24785 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 53672.28 | 2.59842 | 2.59842 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 73639.65 | 4.94513 | 4.94513 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 53779.15 | 3.78338 | 3.78338 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.83663 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26421 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77440 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70455 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44206E-003 |
8 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24669.71475 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.04906 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36576 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36400 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.74586 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97535 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04168E-003 |
16 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 26564.63310 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.16849 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34561 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35900 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.77849 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92163 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10240E-003 |
24 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 47195.68939 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69941 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22589 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24700 |
28 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17276 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60238 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.68665E-003 |
32 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22280.90819 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80011 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12501 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16002 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33336 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04774E-003 |
40 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14428.90882 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.97948 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16130 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19590 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43014 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36204E-003 |
48 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22043.76353 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87912 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11377 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17582 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30338 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34894E-003 |
56 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14575.91278 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52624 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30023 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16682 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80061 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26903E-003 |
64 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16764.06097 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.64735 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15451 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12947 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41202 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.46587E-003 |
72 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 10942.83762 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77160 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20476 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21100 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16281 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54603 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.86072E-003 |
80 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16577.87355 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.69153 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14463 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13831 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38568 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.63431E-003 |
88 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11065.63748 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57382 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27534 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27400 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15723 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73423 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38377E-003 |
96 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 17050.36228 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78045 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12816 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15609 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34176 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.97286E-003 |
104 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11096.66209 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88158 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17921 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17632 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47790 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.12596E-003 |
112 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 16843.08084 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.80501 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12424 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16100 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33131 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.06662E-003 |
120 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11221.81269 |
121 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.73667 |
122 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.37180 |
123 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.47334 |
124 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.17909 |
125 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.81365 |
126 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 4.81365 |
127 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
128 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.45269 |
129 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.54496 |
130 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.39649 |
131 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.08992 |
132 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 2.59842 |
133 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.24785 |
134 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.24785 |
135 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.61170 |
137 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.76331 |
138 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.48299 |
139 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.52662 |
140 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 3.78338 |
141 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.94513 |
142 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 4.94513 |
143 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.76507 |
145 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 4.81365 |
146 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.24785 |
147 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 4.94513 |
148 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.81365 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.81365 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 106196.34754 |
151 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.73987 |
152 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.60439 |
153 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35395.24264 |
154 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.73987 |
155 | Coil:Heating:Fuel | PACU_VAV_BOT HEATING COIL | Design Size Nominal Capacity [W] | 52075.51997 |
156 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 4.81365 |
157 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.24785 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.24785 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 97388.68225 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72646 |
161 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.41581 |
162 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32459.64779 |
163 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72646 |
164 | Coil:Heating:Fuel | PACU_VAV_MID HEATING COIL | Design Size Nominal Capacity [W] | 53368.17225 |
165 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.24785 |
166 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.94513 |
167 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.94513 |
168 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 108735.15211 |
169 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.74078 |
170 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.64821 |
171 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 36241.42620 |
172 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.74078 |
173 | Coil:Heating:Fuel | PACU_VAV_TOP HEATING COIL | Design Size Nominal Capacity [W] | 52864.72690 |
174 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 4.94513 |
175 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
176 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
177 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
178 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 0.72612 |
179 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT COOLING COIL | N/A | N/A | 105607.54 | 360347.90 | 12.48 | 3.19 | 3.58 | 3.77 | 3.93 | 10.87 | 12.20 | 12.85 | 13.42 | 5.3104 | 4.2303 | 2.8477 | 1.1841 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID COOLING COIL | N/A | N/A | 96977.52 | 330901.03 | 12.57 | 3.20 | 3.60 | 3.80 | 3.95 | 10.93 | 12.29 | 12.96 | 13.48 | 4.6862 | 3.7266 | 2.5075 | 1.0575 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP COOLING COIL | N/A | N/A | 108119.59 | 368919.35 | 12.48 | 3.18 | 3.57 | 3.77 | 3.93 | 10.87 | 12.20 | 12.85 | 13.42 | 5.4555 | 4.3446 | 2.9247 | 1.2157 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.150 | 0.981 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.150 | 0.981 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.150 | 0.981 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.150 | 0.981 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.808 | 0.721 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.808 | 0.721 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.808 | 0.721 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.808 | 0.721 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.733 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.733 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.733 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.733 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.150 | 0.981 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.150 | 0.981 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_EAST_0.38 | N/A | 1.946 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.150 | 0.981 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.150 | 0.981 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_WEST_0.38 | N/A | 1.946 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.733 | 73.69 | 136.92 | 73.69 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 19.78 | 19.78 | 19.78 | 0.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.733 | 49.77 | 91.28 | 49.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_EAST_0.38 | N/A | 1.946 | No | 38.05 | 38.05 | 38.05 | 90.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_EAST_0.38 | N/A | 1.946 | No | 1.50 | 1.50 | 1.50 | 90.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.232 | 0.219 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.733 | 73.69 | 136.92 | 73.69 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 19.78 | 19.78 | 19.78 | 180.00 | 90.00 | 15.82 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.220 | 0.209 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.823 | 0.733 | 49.77 | 91.28 | 49.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_WEST_0.38 | N/A | 1.946 | No | 38.05 | 38.05 | 38.05 | 270.00 | 90.00 | 30.84 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_WEST_0.38 | N/A | 1.946 | No | 1.50 | 1.50 | 1.50 | 270.00 | 90.00 | 1.22 | 1.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.232 | 0.219 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.808 | 0.721 | 77.59 | 136.92 | 77.59 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_NORTH_0.38 | N/A | 1.946 | No | 59.33 | 59.33 | 59.33 | 0.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.808 | 0.721 | 51.72 | 91.28 | 51.72 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_EAST_0.38 | N/A | 1.946 | No | 39.55 | 39.55 | 39.55 | 90.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.808 | 0.721 | 77.59 | 136.92 | 77.59 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | N/A | 1.946 | No | 59.33 | 59.33 | 59.33 | 180.00 | 90.00 | 49.91 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.808 | 0.721 | 51.72 | 91.28 | 51.72 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3425_SHGC_WEST_0.38 | N/A | 1.946 | No | 39.55 | 39.55 | 39.55 | 270.00 | 90.00 | 33.27 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.0601056292E-002 | 2.5652638130E-002 | Pass | Pass | 0.4860497935 | 0.4897340959 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1573596656 | 0.1060309629 | Pass | Pass | 0.4944532092 | 0.4762298743 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.4577602528E-002 | 3.9574552750E-002 | Pass | Pass | 0.4964425080 | 0.4656859577 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.9714765725E-002 | 4.1283845890E-002 | Pass | Pass | 0.5006631617 | 0.4688617072 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.7747465494E-003 | 6.6281712237E-003 | Pass | Pass | 1.0086728496 | 2.6408044126 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 9.9805293430E-002 | 0.1001289593 | Pass | Pass | 21.1237493651 | 50.1437464287 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4172684858 | 0.4132020684 | Pass | Pass | 13.8757371322 | 51.7595133281 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4350177991 | 0.4296376793 | Pass | Pass | 41.7293356636 | 124.5149183402 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3948267905 | 0.4035074180 | Pass | Pass | 33.9565815804 | 94.5683789720 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4398006161 | 0.4290887695 | Pass | Pass | 38.3512558426 | 117.2259995372 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3009294881 | 0.2918230588 | Pass | Pass | 25.4181673642 | 83.6970949798 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3117557719 | 0.3033756935 | Pass | Pass | 18.5289810816 | 42.6247696344 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2666702951 | 0.2729011350 | Pass | Pass | 19.0734325078 | 43.5796382817 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3185672402 | 0.3060956641 | Pass | Pass | 18.2857648360 | 41.8999454114 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3053641296 | 0.2908714249 | Pass | Pass | 21.8753964298 | 58.7200594289 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3074575230 | 0.3009551565 | Pass | Pass | 15.0135117514 | 43.5449196135 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2680209047 | 0.2801240472 | Pass | Pass | 16.6947177293 | 47.4946301359 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3122346674 | 0.2998366089 | Pass | Pass | 14.7217007238 | 39.2505814215 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3658.37 | 139.88 | 0.00 | 1639.11 | 796.70 | 6234.06 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.981 | 1.150 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.981 | 1.150 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.981 | 1.150 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.981 | 1.150 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.721 | 0.808 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.721 | 0.808 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.721 | 0.808 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.721 | 0.808 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.733 | 0.823 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.733 | 0.823 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.733 | 0.823 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.733 | 0.823 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.981 | 1.150 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.981 | 1.150 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.981 | 1.150 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.981 | 1.150 | 91.28 | 51.72 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.733 | 0.823 | 136.92 | 73.69 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.733 | 0.823 | 91.28 | 49.77 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.733 | 0.823 | 136.92 | 73.69 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.212 | 0.220 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.733 | 0.823 | 91.28 | 49.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.223 | 0.232 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.721 | 0.808 | 136.92 | 77.59 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.721 | 0.808 | 91.28 | 51.72 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.721 | 0.808 | 136.92 | 77.59 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.721 | 0.808 | 91.28 | 51.72 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_FLOOR | CORE_BOT_ZN_5_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 135.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 315.00 | 180.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_TOP_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 90.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 270.00 | 180.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 0.00 | |
iz-PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 270.00 | 0.00 | |
iz-PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 0.00 | |
iz-PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 90.00 | 0.00 | |
iz-CORE_MID_ZN_5_FLOOR | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 983.54 | 983.54 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 983.54 | 983.54 | 0.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 225.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 315.00 | 0.00 | |
PERIMETER_TOP_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 45.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 135.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 225.00 | 90.00 | W |
iz-CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.26 | 131.26 | 90.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.26 | 131.26 | 270.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 315.00 | 90.00 | N |
iz-CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 111.82 | 111.82 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 207.34 | 207.34 | 180.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 207.34 | 207.34 | 0.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 135.00 | 90.00 | S |
iz-PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.74 | 17.74 | 45.00 | 90.00 | E |
iz-CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 66.19 | 66.19 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 131.25 | 131.25 | 270.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 131.25 | 131.25 | 90.00 | 0.00 | |
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1967.08 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.68 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 414.67 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 262.51 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.946 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3425_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.946 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.946 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3425_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.946 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3425_SHGC_EAST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3425_SHGC_EAST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 19.78 | 0.00 | 0.00 | 19.78 | 19.78 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3425_SHGC_WEST_0.38 | 38.05 | 0.00 | 0.00 | 38.05 | 38.05 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3425_SHGC_WEST_0.38 | 1.50 | 0.00 | 0.00 | 1.50 | 1.50 | 1.946 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3425_SHGC_NORTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.946 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3425_SHGC_EAST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.946 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3425_SHGC_SOUTH_0.38 | 59.33 | 0.00 | 0.00 | 59.33 | 59.33 | 1.946 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3425_SHGC_WEST_0.38 | 39.55 | 0.00 | 0.00 | 39.55 | 39.55 | 1.946 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 593.29 | 1.946 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 177.99 | 1.946 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 415.31 | 1.946 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 5.9322 | 983.54 | 5834.49 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 44.13 | 0.0000 | Y | 48.33 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.09 | 0.0000 | Y | 6.02 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.85 | 0.0000 | Y | 3.78 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.57 | 0.0000 | Y | 5.90 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.77 | 0.0000 | Y | 3.77 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.00 | 0.0000 | Y | 6.00 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.80 | 0.0000 | Y | 3.77 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.51 | 0.0000 | Y | 5.89 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.71 | 0.0000 | Y | 3.76 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 26.09 | 0.0000 | Y | 6.02 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 5.9322 | 131.26 | 778.67 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.85 | 0.0000 | Y | 3.78 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 5.9322 | 207.34 | 1229.96 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.57 | 0.0000 | Y | 5.90 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 5.9322 | 131.25 | 778.62 | LightsWired | LTG_SCH_OFFICE | 45.30 | 168.00 | 25.77 | 0.0000 | Y | 3.77 |
Interior Lighting Total | 5.9322 | 4982.19 | 29555.08 | 203.36 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.67 | 298.62 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.67 | 108.62 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 1229.96 | 471.69 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 1229.96 | 171.58 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.38 | 778.62 | 298.60 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.14 | 778.62 | 108.62 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 424.83 | AstronomicalClock | - | 42.24 | 42.24 | 3.37 | |
EXTERIOR_LIGHTS_B | 408.47 | AstronomicalClock | - | 83.63 | 62.93 | 4.83 | |
EXTERIOR_LIGHTS_C | 4724.13 | AstronomicalClock | - | 83.63 | 47.43 | 42.06 | |
Exterior Lighting Total | 5557.43 | 50.26 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | 106196.35 | 78570.99 | 27625.36 | 0.74 | 3.74 | |||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | 97388.68 | 70748.61 | 26640.07 | 0.73 | 3.74 | |||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | 108735.15 | 80549.19 | 28185.96 | 0.74 | 3.74 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT COOLING COIL | 105607.5 | 3.19 | 10.87 | N/A | N/A | 12.48 | |
PACU_VAV_MID COOLING COIL | 96977.5 | 3.20 | 10.93 | N/A | N/A | 12.57 | |
PACU_VAV_TOP COOLING COIL | 108119.6 | 3.18 | 10.87 | N/A | N/A | 12.48 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 24669.71 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 26564.63 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 47195.69 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22280.91 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14428.91 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22043.76 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14575.91 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16764.06 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10942.84 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16577.87 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11065.64 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 17050.36 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11096.66 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16843.08 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11221.81 | 1.00 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | 52075.52 | 0.80 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | 53368.17 | 0.80 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | 52864.73 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.81 | 11063.99 | 2298.46 | 1.00 | 1.14 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.25 | 9826.93 | 2313.39 | 1.00 | 1.14 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.60 | 1389.42 | 4.95 | 11366.20 | 2298.46 | 1.00 | 1.14 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000054 | 0.73 | 13540.37 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 1.02 | 0.24 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 105607.54 | 3.19 | 10.87 | 12.48 | 5.3104 | 3.58 | 12.20 | 4.2303 | 3.77 | 12.85 | 2.8477 | 3.93 | 13.42 | 1.1841 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 96977.52 | 3.20 | 10.93 | 12.57 | 4.6862 | 3.60 | 12.29 | 3.7266 | 3.80 | 12.96 | 2.5075 | 3.95 | 13.48 | 1.0575 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 108119.59 | 3.18 | 10.87 | 12.48 | 5.4555 | 3.57 | 12.20 | 4.3446 | 3.77 | 12.85 | 2.9247 | 3.93 | 13.42 | 1.2157 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 37551.32 | 37551.32 | 38.18 | 2.837 | 2.837 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00883 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_MID | 27160.21 | 27160.21 | 27.61 | 2.049 | 2.049 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 23.36 | 0.01535 | 0.425 | 0.00 |
CORE_TOP | 28467.62 | 28467.62 | 28.94 | 2.168 | 2.168 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00892 | 30.99 | 0.01536 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 8727.12 | 8727.12 | 42.09 | 0.665 | 0.665 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00897 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10503.22 | 10503.22 | 80.02 | 0.800 | 0.800 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00876 | 25.97 | 0.01536 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 12857.91 | 12857.91 | 62.01 | 0.979 | 0.979 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00883 | 31.02 | 0.01536 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 11540.48 | 11540.48 | 87.93 | 0.879 | 0.879 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00873 | 29.54 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 6756.75 | 6756.75 | 32.59 | 0.515 | 0.515 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00900 | 31.20 | 0.01537 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 8498.20 | 8498.20 | 64.74 | 0.647 | 0.647 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00876 | 26.27 | 0.01536 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 10129.19 | 10129.19 | 48.85 | 0.772 | 0.772 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00884 | 31.11 | 0.01536 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 9078.11 | 9078.11 | 69.16 | 0.692 | 0.692 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00874 | 28.39 | 0.01536 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 7532.61 | 7532.61 | 36.33 | 0.574 | 0.574 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 24.00 | 24.00 | 0.00901 | 27.33 | 0.01536 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 10245.26 | 10245.26 | 78.05 | 0.780 | 0.780 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00875 | 25.37 | 0.01535 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11572.87 | 11572.87 | 55.82 | 0.882 | 0.882 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00884 | 30.85 | 0.01536 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 10567.72 | 10567.72 | 80.51 | 0.805 | 0.805 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00874 | 29.36 | 0.01536 | 0.057 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 10081.17 | 10081.17 | 10.25 | 0.453 | 0.453 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_MID | 18749.68 | 18749.68 | 19.06 | 0.834 | 0.834 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
CORE_TOP | 33200.14 | 33200.14 | 33.76 | 1.482 | 1.482 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 0.425 | 0.00 |
PERIMETER_TOP_ZN_3 | 15637.07 | 15637.07 | 75.42 | 0.699 | 0.699 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_2 | 10126.03 | 10126.03 | 77.14 | 0.453 | 0.453 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_TOP_ZN_1 | 15470.96 | 15470.96 | 74.62 | 0.692 | 0.692 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_TOP_ZN_4 | 10229.00 | 10229.00 | 77.93 | 0.458 | 0.458 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_3 | 11771.41 | 11771.41 | 56.77 | 0.526 | 0.526 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_2 | 7683.30 | 7683.30 | 58.53 | 0.344 | 0.344 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_BOT_ZN_1 | 11641.00 | 11641.00 | 56.15 | 0.520 | 0.520 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_BOT_ZN_4 | 7769.30 | 7769.30 | 59.19 | 0.347 | 0.347 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_3 | 11972.80 | 11972.80 | 57.75 | 0.535 | 0.535 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_2 | 7791.60 | 7791.60 | 59.36 | 0.348 | 0.348 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -26.20 | 0.00036 | 0.057 | 0.00 |
PERIMETER_MID_ZN_1 | 11827.62 | 11827.62 | 57.05 | 0.529 | 0.529 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -26.20 | 0.00036 | 0.090 | 0.00 |
PERIMETER_MID_ZN_4 | 7879.25 | 7879.25 | 60.03 | 0.352 | 0.352 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -26.20 | 0.00036 | 0.057 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 4.81 | 4.81 | 2.18 | 2.18 | 4.8137 | 2.1791 | 4.8137 | 0.4527 | 0.3000 |
PACU_VAV_MID | 4.25 | 4.25 | 2.60 | 2.60 | 4.2479 | 2.5984 | 4.2479 | 0.6117 | 0.3000 |
PACU_VAV_TOP | 4.95 | 4.95 | 3.78 | 3.78 | 4.9451 | 3.7834 | 4.9451 | 0.7651 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 24669.715 | 24669.715 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 24669.71 | 14435.86 | 0.453152 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 10081.17 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 26564.633 | 26564.633 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26564.63 | 26564.63 | 0.833884 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 18749.68 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 47195.689 | 47195.689 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 47195.69 | 47195.69 | 1.481508 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3290 | 33200.14 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22280.908 | 22280.908 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22280.91 | 22280.91 | 0.699414 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00777744 | 47.9776 | 15637.07 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14428.909 | 14428.909 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14428.91 | 14428.91 | 0.452934 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00777112 | 47.9392 | 10126.03 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22043.764 | 22043.764 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22043.76 | 22043.76 | 0.691970 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00777509 | 47.9632 | 15470.96 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14575.913 | 14575.913 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14575.91 | 14575.91 | 0.457549 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00777338 | 47.9530 | 10229.00 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 16764.061 | 16764.061 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16764.06 | 16764.06 | 0.526236 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00783701 | 48.3389 | 11771.41 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10942.838 | 10942.838 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10942.84 | 10942.84 | 0.343504 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00783456 | 48.3240 | 7683.30 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 16577.874 | 16577.874 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16577.87 | 16577.87 | 0.520392 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00783479 | 48.3254 | 11641.00 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11065.637 | 11065.637 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11065.64 | 11065.64 | 0.347359 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00783669 | 48.3370 | 7769.30 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 17050.362 | 17050.362 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17050.36 | 17050.36 | 0.535224 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00775493 | 47.8400 | 11972.80 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 11096.662 | 11096.662 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11096.66 | 11096.66 | 0.348332 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00774989 | 47.8094 | 7791.60 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 16843.081 | 16843.081 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16843.08 | 16843.08 | 0.528717 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00775163 | 47.8199 | 11827.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 11221.813 | 11221.813 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11221.81 | 11221.81 | 0.352261 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00775286 | 47.8275 | 7879.25 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 106196.348 | 78570.986 | 4.813651 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 108651.88 | 81578.86 | 4.813651 | 25.79 | 18.12 | 0.01048020 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 24.8288 | 24.00 | 0.00886618 | 45.5007 | 63175.57 | 0.00 | 109502.69 | 78154.62 |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 52075.520 | 52075.520 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52075.52 | 52075.52 | 1.444095 | -18.45 | -18.45 | 0.00163354 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 82.7625 | 19.34 | 0.00762904 | 52.1699 | 22968.92 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 97388.682 | 70748.614 | 4.247853 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 100278.47 | 73099.76 | 4.247853 | 26.03 | 18.41 | 0.01075401 | 10.83 | 10.83 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 28.1359 | 24.00 | 0.00894437 | 45.8967 | 55667.69 | 0.00 | 100420.80 | 70438.78 |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 53368.172 | 53368.172 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 53368.17 | 53368.17 | 1.274356 | -23.49 | -23.49 | 0.00081129 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 93.7862 | 17.60 | 0.00741454 | 56.5619 | 22092.52 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 108735.152 | 80549.194 | 4.945134 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 111188.44 | 83582.64 | 4.945134 | 25.74 | 18.09 | 0.01046520 | 10.85 | 10.85 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 24.1686 | 24.00 | 0.00889682 | 45.6562 | 64706.42 | 0.00 | 112120.54 | 80102.78 |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 52864.727 | 52864.727 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52864.73 | 52864.73 | 1.483540 | -18.08 | -18.08 | 0.00176630 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 80.5620 | 15.60 | 0.00743660 | 64.4225 | 25011.61 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 24669.715 | 24669.715 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | Sensible | 24669.71 | 14435.86 | 1.0000 | 0.52047085 | 0.453152 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24669.71 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 10081.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 26564.633 | 26564.633 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26564.63 | 26564.63 | 1.0000 | 0.95776190 | 0.833884 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26564.63 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 18749.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 47195.689 | 47195.689 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 47195.69 | 47195.69 | 1.0000 | 1.70159449 | 1.481508 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 47195.69 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 49.3290 | 33200.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 22280.908 | 22280.908 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22280.91 | 22280.91 | 1.0000 | 0.80331639 | 0.699414 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22280.91 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777744 | 21.00 | 0.00777744 | 47.9776 | 15637.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 14428.909 | 14428.909 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14428.91 | 14428.91 | 1.0000 | 0.52022022 | 0.452934 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14428.91 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777112 | 21.00 | 0.00777112 | 47.9392 | 10126.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 22043.764 | 22043.764 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22043.76 | 22043.76 | 1.0000 | 0.79476637 | 0.691970 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22043.76 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777509 | 21.00 | 0.00777509 | 47.9632 | 15470.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 14575.913 | 14575.913 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14575.91 | 14575.91 | 1.0000 | 0.52552030 | 0.457549 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14575.91 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777338 | 21.00 | 0.00777338 | 47.9530 | 10229.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 16764.061 | 16764.061 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16764.06 | 16764.06 | 1.0000 | 0.60441185 | 0.526236 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16764.06 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00783701 | 21.00 | 0.00783701 | 48.3389 | 11771.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 10942.838 | 10942.838 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10942.84 | 10942.84 | 1.0000 | 0.39453332 | 0.343504 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10942.84 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00783456 | 21.00 | 0.00783456 | 48.3240 | 7683.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16577.874 | 16577.874 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16577.87 | 16577.87 | 1.0000 | 0.59769904 | 0.520392 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16577.87 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00783479 | 21.00 | 0.00783479 | 48.3254 | 11641.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11065.637 | 11065.637 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11065.64 | 11065.64 | 1.0000 | 0.39896075 | 0.347359 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11065.64 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00783669 | 21.00 | 0.00783669 | 48.3370 | 7769.30 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 17050.362 | 17050.362 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17050.36 | 17050.36 | 1.0000 | 0.61473416 | 0.535224 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17050.36 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775493 | 21.00 | 0.00775493 | 47.8400 | 11972.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 11096.662 | 11096.662 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11096.66 | 11096.66 | 1.0000 | 0.40007931 | 0.348332 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11096.66 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774989 | 21.00 | 0.00774989 | 47.8094 | 7791.60 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 16843.081 | 16843.081 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16843.08 | 16843.08 | 1.0000 | 0.60726083 | 0.528717 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16843.08 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775163 | 21.00 | 0.00775163 | 47.8199 | 11827.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 11221.813 | 11221.813 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11221.81 | 11221.81 | 1.0000 | 0.40459150 | 0.352261 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11221.81 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00775286 | 21.00 | 0.00775286 | 47.8275 | 7879.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 106196.348 | 78570.986 | 4.813651 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3222 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.813651 | 5.52874708 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 108651.88 | 81578.86 | 1.0231 | 5.52874708 | 4.813651 | 25.79 | 18.12 | 0.01048020 | 52624.6 | 10.85 | 10.85 | 0.00850000 | 32328.2 | -999.0 | -999.00 | -999.00 | -999.00 | 11063.992 | 97587.89 | 31.20 | 0.01536508 | 23.13 | 1.19517000 | 24.8288 | 24.00 | 0.00886618 | 24.00 | 0.00886618 | 45.5007 | 63175.57 | 0.00 | 109502.69 | 78154.62 | 5.31040336 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.26 | 12.25 | 0.00887017 | 34702.0 | |
PACU_VAV_BOT HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52075.520 | 52075.520 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_BOT FAN | Fan:VariableVolume | 4.813651 | 5.52874708 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 52075.52 | 52075.52 | 1.0000 | 1.65862412 | 1.444095 | -18.45 | -18.45 | 0.00163354 | -14504.9 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52075.52 | -26.20 | 0.00036134 | -26.20 | 1.19517000 | 82.7625 | 18.79 | 0.00774174 | 19.34 | 0.00762904 | 52.1699 | 22968.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 97388.682 | 70748.614 | 4.247853 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8312 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.247853 | 4.87889591 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 100278.47 | 73099.76 | 1.0297 | 4.87889591 | 4.247853 | 26.03 | 18.41 | 0.01075401 | 53569.6 | 10.83 | 10.83 | 0.00850000 | 32316.3 | -999.0 | -999.00 | -999.00 | -999.00 | 9826.925 | 90451.55 | 31.20 | 0.01536508 | 23.13 | 1.19517000 | 28.1359 | 24.00 | 0.00894437 | 24.00 | 0.00894437 | 45.8967 | 55667.69 | 0.00 | 100420.80 | 70438.78 | 4.68621640 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.94 | 11.92 | 0.00867618 | 33893.4 | |
PACU_VAV_MID HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 53368.172 | 53368.172 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.247853 | 4.87889591 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 53368.17 | 53368.17 | 1.0000 | 1.46366877 | 1.274356 | -23.49 | -23.49 | 0.00081129 | -21605.7 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53368.17 | -26.20 | 0.00036134 | -26.20 | 1.19517000 | 93.7862 | 17.48 | 0.00760238 | 17.60 | 0.00741454 | 56.5619 | 22092.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 108735.152 | 80549.194 | 4.945134 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2943 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.945134 | 5.67976215 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 111188.44 | 83582.64 | 1.0226 | 5.67976215 | 4.945134 | 25.74 | 18.09 | 0.01046520 | 52542.9 | 10.85 | 10.85 | 0.00850000 | 32328.2 | -999.0 | -999.00 | -999.00 | -999.00 | 11366.200 | 99822.25 | 31.20 | 0.01536508 | 23.13 | 1.19517000 | 24.1686 | 24.00 | 0.00889682 | 24.00 | 0.00889682 | 45.6562 | 64706.42 | 0.00 | 112120.54 | 80102.78 | 5.45545448 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.29 | 12.27 | 0.00888358 | 34770.4 | |
PACU_VAV_TOP HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52864.727 | 52864.727 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | PACU_VAV_TOP FAN | Fan:VariableVolume | 4.945134 | 5.67976215 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 04:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 52864.73 | 52864.73 | 1.0000 | 1.70392865 | 1.483540 | -18.08 | -18.08 | 0.00176630 | -13804.6 | 12.80 | 11.18 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52864.73 | -26.20 | 0.00036134 | -26.20 | 1.19517000 | 80.5620 | 15.60 | 0.00758926 | 15.60 | 0.00743660 | 64.4225 | 25011.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.81 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.25 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 4.95 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | PACU_VAV_MID_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 2526.17 | 3260.50 | 526.67 |
CORE_MID | 3158.17 | 3784.67 | 1548.50 |
CORE_TOP | 3547.17 | 4023.50 | 2103.83 |
PERIMETER_TOP_ZN_3 | 4113.00 | 4208.83 | 2719.33 |
PERIMETER_TOP_ZN_2 | 4087.50 | 4099.33 | 2554.50 |
PERIMETER_TOP_ZN_1 | 3751.17 | 3926.17 | 2199.83 |
PERIMETER_TOP_ZN_4 | 4025.00 | 4226.50 | 2613.33 |
PERIMETER_BOT_ZN_3 | 3782.83 | 4304.50 | 2512.00 |
PERIMETER_BOT_ZN_2 | 3926.17 | 4007.33 | 2303.67 |
PERIMETER_BOT_ZN_1 | 3740.17 | 4368.83 | 2482.00 |
PERIMETER_BOT_ZN_4 | 3853.67 | 4075.00 | 2298.67 |
PERIMETER_MID_ZN_3 | 3936.00 | 3972.50 | 2349.67 |
PERIMETER_MID_ZN_2 | 3337.67 | 3403.33 | 2001.83 |
PERIMETER_MID_ZN_1 | 3591.83 | 3659.17 | 1826.17 |
PERIMETER_MID_ZN_4 | 3868.83 | 3983.17 | 2276.67 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5098.00 | 4918.67 | 3256.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 0.67 | 0.50 | 0.67 | 0.33 |
CORE_MID | 3.00 | 0.00 | 2.50 | 0.00 |
CORE_TOP | 18.17 | 0.00 | 13.33 | 0.00 |
PERIMETER_TOP_ZN_3 | 263.50 | 3.17 | 142.50 | 1.67 |
PERIMETER_TOP_ZN_2 | 141.67 | 19.67 | 31.17 | 19.33 |
PERIMETER_TOP_ZN_1 | 130.83 | 21.67 | 33.50 | 20.50 |
PERIMETER_TOP_ZN_4 | 140.33 | 27.00 | 33.17 | 15.17 |
PERIMETER_BOT_ZN_3 | 173.83 | 0.00 | 136.67 | 0.00 |
PERIMETER_BOT_ZN_2 | 32.17 | 10.17 | 4.33 | 10.17 |
PERIMETER_BOT_ZN_1 | 742.67 | 27.33 | 719.67 | 27.33 |
PERIMETER_BOT_ZN_4 | 31.17 | 17.00 | 5.00 | 9.33 |
PERIMETER_MID_ZN_3 | 124.17 | 0.00 | 77.00 | 0.00 |
PERIMETER_MID_ZN_2 | 49.83 | 19.00 | 6.17 | 19.00 |
PERIMETER_MID_ZN_1 | 38.50 | 19.17 | 7.33 | 19.17 |
PERIMETER_MID_ZN_4 | 52.67 | 25.33 | 9.00 | 14.33 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 959.17 | 123.83 | 794.83 | 102.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.843 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.630 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.635 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.762 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 1.193 | 0.052 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 1.021 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 1.215 | 0.052 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.649 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.962 | 0.028 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.844 | 1.324 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.952 | 0.028 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.717 | 0.041 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 1.089 | 0.046 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 0.973 | 0.041 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 1.138 | 0.043 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.74 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.90 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.54 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.58 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.90 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_MID | PACU_VAV_MID | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
CORE_TOP | PACU_VAV_TOP | 21.74 | 52.94 | 2698.04 | 983.54 | 0.0000 | 0.425 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 2.90 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 2.54 | 7.07 | 360.08 | 131.26 | 0.0000 | 0.057 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 4.58 | 11.16 | 568.77 | 207.34 | 0.0000 | 0.090 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 2.90 | 7.06 | 360.05 | 131.25 | 0.0000 | 0.057 |
Total Facility | 109.75 | 268.17 | 13667.13 | 4982.19 | 0.0000 | 2.151 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
CORE_BOTTOM | 13479309.52 | 0.00 | 13479309.52 | 0.00 | 13479309.52 | 13393058.27 | 6182.70 | 102.29 | 2475.01 | 284.20 |
CORE_MID | 10077814.23 | 0.00 | 10077814.23 | 0.00 | 10077814.23 | 13393058.27 | 6713.67 | 19.31 | 2027.02 | 279.80 |
CORE_TOP | 10136264.91 | 0.00 | 10136264.91 | 0.00 | 10136264.91 | 13393058.27 | 6637.40 | 32.81 | 2089.78 | 92.18 |
PERIMETER_TOP_ZN_3 | 2561301.87 | 0.00 | 2561301.87 | 333884.44 | 2895186.31 | 2823374.22 | 4526.19 | 1099.19 | 3134.61 | 92.12 |
PERIMETER_TOP_ZN_2 | 2534349.24 | 0.00 | 2534349.24 | 222588.29 | 2756937.53 | 1787429.43 | 4091.32 | 0.88 | 4667.80 | 92.12 |
PERIMETER_TOP_ZN_1 | 3419109.23 | 0.00 | 3419109.23 | 333884.44 | 3752993.67 | 2823374.22 | 4106.96 | 1.32 | 4651.72 | 92.12 |
PERIMETER_TOP_ZN_4 | 2593496.22 | 0.00 | 2593496.22 | 222588.29 | 2816084.50 | 1787312.18 | 4088.86 | 3.54 | 4667.60 | 92.12 |
PERIMETER_BOT_ZN_3 | 2207155.91 | 0.00 | 2207155.91 | 177523.80 | 2384679.71 | 2823374.22 | 5376.63 | 661.22 | 2722.16 | 284.20 |
PERIMETER_BOT_ZN_2 | 2059787.07 | 0.00 | 2059787.07 | 118348.49 | 2178135.57 | 1787429.43 | 4152.80 | 16.92 | 4590.29 | 284.20 |
PERIMETER_BOT_ZN_1 | 2865105.87 | 0.00 | 2865105.87 | 4544307.04 | 7409412.90 | 2823374.22 | 5113.91 | 45.31 | 3600.78 | 284.20 |
PERIMETER_BOT_ZN_4 | 2045708.36 | 0.00 | 2045708.36 | 118348.49 | 2164056.85 | 1787312.18 | 4174.84 | 18.09 | 4567.07 | 284.20 |
PERIMETER_MID_ZN_3 | 2413399.14 | 0.00 | 2413399.14 | 277932.54 | 2691331.69 | 2823374.22 | 5927.98 | 38.92 | 2793.10 | 279.78 |
PERIMETER_MID_ZN_2 | 2481594.73 | 0.00 | 2481594.73 | 185287.25 | 2666881.98 | 1787429.43 | 4089.13 | 2.22 | 4668.65 | 1188.78 |
PERIMETER_MID_ZN_1 | 3262915.46 | 0.00 | 3262915.46 | 277932.54 | 3540848.00 | 2823374.22 | 4126.94 | 9.27 | 4623.79 | 279.78 |
PERIMETER_MID_ZN_4 | 2429788.58 | 0.00 | 2429788.58 | 185287.25 | 2615075.83 | 1787312.18 | 4092.13 | 3.66 | 4664.22 | 279.78 |
Total Facility | 64567100.35 | 0.00 | 64567100.35 | 6997912.86 | 71565013.21 | 67843644.98 | 6861.45 | 1507.29 | 4790.81 | 1330.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
CORE_BOTTOM | 0.6177 | 0.0000 | 0.6177 | 0.0000 | 0.6177 | 0.4247 | 3438.49 | 102.29 | 2402.21 |
CORE_MID | 0.4631 | 0.0000 | 0.4631 | 0.0000 | 0.4631 | 0.4247 | 3945.57 | 19.31 | 1978.12 |
CORE_TOP | 0.4665 | 0.0000 | 0.4665 | 0.0000 | 0.4665 | 0.4247 | 3874.06 | 32.81 | 2036.13 |
PERIMETER_TOP_ZN_3 | 0.1181 | 0.0000 | 0.1181 | 0.0077 | 0.1258 | 0.0895 | 1762.85 | 1099.19 | 3080.96 |
PERIMETER_TOP_ZN_2 | 0.1170 | 0.0000 | 0.1170 | 0.0051 | 0.1221 | 0.0567 | 1328.14 | 0.88 | 4613.98 |
PERIMETER_TOP_ZN_1 | 0.1580 | 0.0000 | 0.1580 | 0.0077 | 0.1656 | 0.0895 | 1343.62 | 1.32 | 4598.06 |
PERIMETER_TOP_ZN_4 | 0.1192 | 0.0000 | 0.1192 | 0.0051 | 0.1243 | 0.0567 | 1325.68 | 3.54 | 4613.78 |
PERIMETER_BOT_ZN_3 | 0.1007 | 0.0000 | 0.1007 | 0.0041 | 0.1048 | 0.0895 | 2632.37 | 661.13 | 2649.50 |
PERIMETER_BOT_ZN_2 | 0.0943 | 0.0000 | 0.0943 | 0.0027 | 0.0971 | 0.0567 | 1409.23 | 16.87 | 4516.90 |
PERIMETER_BOT_ZN_1 | 0.1315 | 0.0000 | 0.1315 | 0.2082 | 0.3397 | 0.0895 | 2369.56 | 45.31 | 3528.12 |
PERIMETER_BOT_ZN_4 | 0.0934 | 0.0000 | 0.0934 | 0.0027 | 0.0961 | 0.0567 | 1431.30 | 18.04 | 4493.66 |
PERIMETER_MID_ZN_3 | 0.1111 | 0.0000 | 0.1111 | 0.0064 | 0.1175 | 0.0895 | 3159.89 | 38.92 | 2744.20 |
PERIMETER_MID_ZN_2 | 0.1068 | 0.0000 | 0.1068 | 0.0045 | 0.1113 | 0.0567 | 1321.09 | 2.22 | 3710.69 |
PERIMETER_MID_ZN_1 | 0.1506 | 0.0000 | 0.1506 | 0.0064 | 0.1570 | 0.0895 | 1358.84 | 9.27 | 4574.89 |
PERIMETER_MID_ZN_4 | 0.1116 | 0.0000 | 0.1116 | 0.0043 | 0.1159 | 0.0567 | 1324.09 | 3.64 | 4615.27 |
Total Facility | 2.9596 | 0.0000 | 2.9596 | 0.2648 | 3.2245 | 2.1513 | 4069.94 | 1507.12 | 4688.75 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PACU_VAV_BOT | 29888728.85 | 0.00 | 29888728.85 | 22614548.33 | 4102.07 | 1.86 | 4656.07 | 284.20 |
PACU_VAV_MID | 27261562.84 | 0.00 | 27261562.84 | 22614548.33 | 4094.44 | 1.77 | 4663.79 | 279.35 |
PACU_VAV_TOP | 28025366.69 | 0.00 | 28025366.69 | 22614548.33 | 4091.94 | 2.44 | 4665.62 | 91.29 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PACU_VAV_BOT | 1.3687 | 0.0000 | 1.3687 | 0.7171 | 1358.39 | 1.86 | 4582.74 |
PACU_VAV_MID | 1.2544 | 0.0000 | 1.2544 | 0.7171 | 1326.35 | 1.77 | 4614.88 |
PACU_VAV_TOP | 1.2911 | 0.0000 | 1.2911 | 0.7171 | 1328.76 | 2.44 | 4611.80 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PACU_VAV_BOT | 0.00 | 0.08 | 2725.16 | 0.00 | 0.00 | 0.00 | 2334.98 | 0.00 | 0.00 | 0.00 |
PACU_VAV_MID | 0.00 | 0.08 | 2583.84 | 0.00 | 0.00 | 0.00 | 2513.86 | 0.00 | 0.00 | 0.00 |
PACU_VAV_TOP | 0.00 | 0.00 | 2419.78 | 0.00 | 0.00 | 0.00 | 2446.80 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PACU_VAV_BOT | 0.0000 | 0.0000 | 2.3478 | 0.0000 | 0.0000 | 0.0000 | 1.0305 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_MID | 0.0000 | 0.0000 | 2.1118 | 0.0000 | 0.0000 | 0.0000 | 1.0301 | 0.0000 | 0.0000 | 0.0000 |
PACU_VAV_TOP | 0.0000 | 0.0000 | 2.2137 | 0.0000 | 0.0000 | 0.0000 | 1.0301 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 825 |
Defaulted Fields | 545 |
Fields with Defaults | 2230 |
Autosized Fields | 149 |
Autosizable Fields | 202 |
Autocalculated Fields | 155 |
Autocalculatable Fields | 276 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1566.10 | 12344.18 | 09-APR-17:10 | 242450.80 | 02-JAN-07:10 |
Electricity:Building | 908.80 | 12175.61 | 09-APR-17:10 | 66998.96 | 03-NOV-07:10 |
Electricity:Zone:CORE_BOTTOM | 284.50 | 4029.56 | 01-JAN-00:10 | 22405.39 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 908.80 | 12175.61 | 09-APR-17:10 | 66998.96 | 03-NOV-07:10 |
InteriorLights:Electricity | 203.36 | 934.27 | 01-JAN-10:10 | 21377.78 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 203.36 | 934.27 | 01-JAN-10:10 | 21377.78 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 203.36 | 934.27 | 01-JAN-10:10 | 21377.78 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 203.36 | 934.27 | 01-JAN-10:10 | 21377.78 | 02-JAN-16:40 |
Electricity:Zone:CORE_MID | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 163.76 | 2065.97 | 01-JAN-00:10 | 11028.52 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 48.33 | 234.43 | 01-JAN-00:10 | 4220.20 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 30.36 | 409.68 | 09-APR-17:10 | 2324.90 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.02 | 23.57 | 01-JAN-10:10 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 6.02 | 23.57 | 01-JAN-10:10 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 19.18 | 259.34 | 09-APR-17:10 | 1471.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.78 | 14.92 | 01-JAN-09:40 | 563.23 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 3.78 | 14.92 | 01-JAN-09:40 | 563.23 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 30.24 | 409.67 | 26-MAR-17:10 | 2324.89 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.90 | 23.57 | 01-JAN-09:40 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 5.90 | 23.57 | 01-JAN-09:40 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 19.17 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.77 | 14.92 | 01-JAN-10:00 | 563.19 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 3.77 | 14.92 | 01-JAN-10:00 | 563.19 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 30.34 | 409.68 | 09-APR-17:10 | 2324.90 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.00 | 23.57 | 01-JAN-10:10 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 6.00 | 23.57 | 01-JAN-10:10 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 19.17 | 259.34 | 09-APR-17:10 | 1471.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.77 | 14.92 | 01-JAN-09:40 | 563.23 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 3.77 | 14.92 | 01-JAN-09:40 | 563.23 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 30.22 | 409.67 | 26-MAR-17:10 | 2324.89 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.89 | 23.57 | 01-JAN-09:40 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 5.89 | 23.57 | 01-JAN-09:40 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 19.16 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.76 | 14.92 | 01-JAN-10:00 | 563.19 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 3.76 | 14.92 | 01-JAN-10:00 | 563.19 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 30.36 | 409.68 | 09-APR-17:10 | 2324.90 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.02 | 23.57 | 01-JAN-10:10 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 6.02 | 23.57 | 01-JAN-10:10 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 19.18 | 259.34 | 09-APR-17:10 | 1471.80 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.78 | 14.92 | 01-JAN-09:40 | 563.23 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 3.78 | 14.92 | 01-JAN-09:40 | 563.23 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 30.24 | 409.67 | 26-MAR-17:10 | 2324.89 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.90 | 23.57 | 01-JAN-09:40 | 889.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 5.90 | 23.57 | 01-JAN-09:40 | 889.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 19.17 | 259.34 | 12-MAR-17:10 | 1471.76 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.77 | 14.92 | 01-JAN-10:00 | 563.19 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 3.77 | 14.92 | 01-JAN-10:00 | 563.19 | 02-JAN-16:40 |
InteriorEquipment:Electricity | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 236.17 | 3795.13 | 01-JAN-00:10 | 18185.19 | 02-JAN-08:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 705.43 | 11241.34 | 01-JAN-00:10 | 45864.70 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 584.69 | 9277.75 | 01-JAN-00:10 | 34487.83 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 115.43 | 1831.54 | 01-JAN-00:10 | 6808.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.25 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 24.33 | 386.10 | 01-JAN-00:10 | 1435.24 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 15.40 | 244.42 | 01-JAN-00:10 | 908.57 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 120.10 | 1963.59 | 01-JAN-00:10 | 11290.62 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.64 | 0.00 | 01-JAN-00:10 | 86.25 | 02-JAN-08:10 |
Electricity:HVAC | 607.03 | 168.57 | 14-MAY-17:30 | 208667.81 | 02-JAN-07:10 |
ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 835.01 | 03-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 11.66 | 168.34 | 01-JAN-00:10 | 835.01 | 03-NOV-07:20 |
ElectricityPurchased:Facility | 1566.10 | 12344.18 | 09-APR-17:10 | 242450.80 | 02-JAN-07:10 |
ElectricityPurchased:Plant | 1566.10 | 12344.18 | 09-APR-17:10 | 242450.80 | 02-JAN-07:10 |
Cogeneration:ElectricityPurchased | 1566.10 | 12344.18 | 09-APR-17:10 | 242450.80 | 02-JAN-07:10 |
General:Cogeneration:ElectricityPurchased | 1566.10 | 12344.18 | 09-APR-17:10 | 242450.80 | 02-JAN-07:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1566.10 | 12344.18 | 09-APR-17:10 | 242450.80 | 02-JAN-07:10 |
ElectricityNet:Plant | 1566.10 | 12344.18 | 09-APR-17:10 | 242450.80 | 02-JAN-07:10 |
Cogeneration:ElectricityNet | 1566.10 | 12344.18 | 09-APR-17:10 | 242450.80 | 02-JAN-07:10 |
General:Cogeneration:ElectricityNet | 1566.10 | 12344.18 | 09-APR-17:10 | 242450.80 | 02-JAN-07:10 |
Heating:Electricity | 371.42 | 0.00 | 01-JAN-00:40 | 201104.60 | 02-JAN-07:10 |
General:Heating:Electricity | 371.42 | 0.00 | 01-JAN-00:40 | 201104.60 | 02-JAN-07:10 |
Fans:Electricity | 91.81 | 0.00 | 01-JAN-00:40 | 29055.78 | 03-JUL-15:30 |
General:Fans:Electricity | 91.81 | 0.00 | 01-JAN-00:40 | 29055.78 | 03-JUL-15:30 |
ExteriorLights:Electricity | 50.26 | 0.00 | 01-JAN-08:00 | 5557.43 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 50.26 | 0.00 | 01-JAN-08:00 | 5557.43 | 01-JAN-06:10 |
Cooling:Electricity | 132.15 | 0.00 | 01-JAN-00:10 | 72586.61 | 04-AUG-15:30 |
General:Cooling:Electricity | 132.15 | 0.00 | 01-JAN-00:10 | 72586.61 | 04-AUG-15:30 |
Electricity:Plant | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
General:Pumps:Electricity | 0.02 | 0.00 | 01-JAN-00:10 | 0.73 | 02-JAN-06:10 |
WIRED_LTG_ELECTRICITY | 5.71 | 0.00 | 01-JAN-00:10 | 600.72 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 585.33 | 9277.75 | 01-JAN-00:10 | 34574.08 | 02-JAN-08:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 491.08 | 1156.00 | 06-JAN-05:10 | 198009.07 | 02-FEB-08:10 |
NaturalGas:HVAC | 375.03 | 0.00 | 01-JAN-00:40 | 190421.08 | 02-FEB-07:30 |
Heating:NaturalGas | 375.03 | 0.00 | 01-JAN-00:40 | 190421.08 | 02-FEB-07:30 |
General:Heating:NaturalGas | 375.03 | 0.00 | 01-JAN-00:40 | 190421.08 | 02-FEB-07:30 |
NaturalGas:Plant | 116.05 | 1156.00 | 02-JAN-07:20 | 12041.65 | 17-FEB-12:30 |
WaterSystems:NaturalGas | 116.05 | 1156.00 | 02-JAN-07:20 | 12041.65 | 17-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 116.05 | 1156.00 | 02-JAN-07:20 | 12041.65 | 17-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 2440.38 | 0.00 | 01-JAN-00:40 | 508298.83 | 30-JAN-07:10 |
EnergyTransfer:Building | 1123.58 | 0.00 | 01-JAN-00:40 | 198212.39 | 02-JAN-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 189.90 | 0.00 | 01-JAN-00:40 | 26051.95 | 03-AUG-07:30 |
Heating:EnergyTransfer | 329.72 | 0.00 | 01-JAN-00:40 | 198212.39 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.61 | 0.00 | 01-JAN-00:10 | 19291.16 | 02-JAN-06:10 |
General:Heating:EnergyTransfer | 329.72 | 0.00 | 01-JAN-00:40 | 198212.39 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.61 | 0.00 | 01-JAN-00:10 | 19291.16 | 02-JAN-06:10 |
Cooling:EnergyTransfer | 793.85 | 0.00 | 01-JAN-00:40 | 156988.18 | 04-AUG-15:20 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 189.29 | 0.00 | 01-JAN-00:40 | 26051.95 | 03-AUG-07:30 |
General:Cooling:EnergyTransfer | 793.85 | 0.00 | 01-JAN-00:40 | 156988.18 | 04-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 189.29 | 0.00 | 01-JAN-00:40 | 26051.95 | 03-AUG-07:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 64.69 | 0.00 | 01-JAN-00:40 | 18799.46 | 02-FEB-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 41.33 | 0.00 | 01-JAN-00:40 | 18799.46 | 02-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 41.33 | 0.00 | 01-JAN-00:40 | 18799.46 | 02-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.36 | 0.00 | 01-JAN-00:10 | 10719.74 | 26-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 23.36 | 0.00 | 01-JAN-00:10 | 10719.74 | 26-JUN-13:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 29.68 | 0.00 | 01-JAN-00:40 | 9555.91 | 11-DEC-07:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.31 | 0.00 | 01-JAN-00:40 | 9555.91 | 11-DEC-07:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.31 | 0.00 | 01-JAN-00:40 | 9555.91 | 11-DEC-07:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.37 | 0.00 | 01-JAN-00:10 | 4805.93 | 26-JUN-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 12.37 | 0.00 | 01-JAN-00:10 | 4805.93 | 26-JUN-15:40 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 27.77 | 0.00 | 01-JAN-00:40 | 7829.95 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 11.88 | 0.00 | 01-JAN-00:40 | 7829.95 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 11.88 | 0.00 | 01-JAN-00:40 | 7829.95 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.89 | 0.00 | 01-JAN-00:10 | 5139.00 | 05-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 15.89 | 0.00 | 01-JAN-00:10 | 5139.00 | 05-JUL-12:10 |
EnergyTransfer:Zone:CORE_MID | 126.91 | 0.00 | 01-JAN-00:40 | 23037.17 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 5.60 | 0.00 | 01-JAN-00:20 | 23037.17 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 5.60 | 0.00 | 01-JAN-00:20 | 23037.17 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 121.31 | 0.00 | 01-JAN-00:40 | 17248.76 | 05-JUL-07:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 121.31 | 0.00 | 01-JAN-00:40 | 17248.76 | 05-JUL-07:30 |
EnergyTransfer:Zone:CORE_TOP | 131.05 | 0.00 | 01-JAN-00:40 | 27243.62 | 11-DEC-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 20.85 | 0.00 | 01-JAN-00:40 | 27243.62 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 20.85 | 0.00 | 01-JAN-00:40 | 27243.62 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 110.20 | 0.00 | 01-JAN-00:20 | 19447.70 | 26-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 110.20 | 0.00 | 01-JAN-00:20 | 19447.70 | 26-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 55.14 | 0.00 | 01-JAN-00:40 | 9950.15 | 30-JAN-05:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 31.38 | 0.00 | 01-JAN-00:40 | 9950.15 | 30-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 31.38 | 0.00 | 01-JAN-00:40 | 9950.15 | 30-JAN-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.76 | 0.00 | 01-JAN-00:10 | 7069.87 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 23.76 | 0.00 | 01-JAN-00:10 | 7069.87 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.44 | 0.00 | 01-JAN-00:40 | 9908.65 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 18.28 | 0.00 | 01-JAN-00:40 | 9908.65 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 18.28 | 0.00 | 01-JAN-00:40 | 9908.65 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.17 | 0.00 | 01-JAN-00:20 | 8718.04 | 26-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 25.17 | 0.00 | 01-JAN-00:20 | 8718.04 | 26-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 61.28 | 0.00 | 01-JAN-00:40 | 13138.34 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.03 | 0.00 | 01-JAN-00:40 | 13138.34 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 22.03 | 0.00 | 01-JAN-00:40 | 13138.34 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.25 | 0.00 | 01-JAN-00:20 | 13096.42 | 07-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 39.25 | 0.00 | 01-JAN-00:20 | 13096.42 | 07-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 44.93 | 0.00 | 01-JAN-00:40 | 10615.45 | 02-FEB-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 19.17 | 0.00 | 01-JAN-00:40 | 10615.45 | 02-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 19.17 | 0.00 | 01-JAN-00:40 | 10615.45 | 02-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.76 | 0.00 | 01-JAN-00:20 | 9209.79 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.76 | 0.00 | 01-JAN-00:20 | 9209.79 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 40.50 | 0.00 | 01-JAN-00:40 | 7205.49 | 02-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.09 | 0.00 | 01-JAN-00:40 | 7205.49 | 02-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.09 | 0.00 | 01-JAN-00:40 | 7205.49 | 02-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.41 | 0.00 | 01-JAN-00:20 | 5261.44 | 04-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 20.41 | 0.00 | 01-JAN-00:20 | 5261.44 | 04-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 33.08 | 0.00 | 01-JAN-00:40 | 7755.95 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 11.29 | 0.00 | 01-JAN-00:40 | 7755.95 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 11.29 | 0.00 | 01-JAN-00:40 | 7755.95 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.79 | 0.00 | 01-JAN-00:20 | 6927.90 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 21.79 | 0.00 | 01-JAN-00:20 | 6927.90 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 74.08 | 0.00 | 01-JAN-00:40 | 18545.17 | 02-FEB-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 47.28 | 0.00 | 01-JAN-00:40 | 18545.17 | 02-FEB-08:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 47.28 | 0.00 | 01-JAN-00:40 | 18545.17 | 02-FEB-08:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 26.80 | 0.00 | 01-JAN-00:20 | 11871.33 | 07-SEP-12:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 26.80 | 0.00 | 01-JAN-00:20 | 11871.33 | 07-SEP-12:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 33.52 | 0.00 | 01-JAN-00:40 | 7865.07 | 30-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 11.72 | 0.00 | 01-JAN-00:40 | 7865.07 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 11.72 | 0.00 | 01-JAN-00:40 | 7865.07 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.80 | 0.00 | 01-JAN-00:20 | 7099.32 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 21.80 | 0.00 | 01-JAN-00:20 | 7099.32 | 05-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 42.63 | 0.00 | 01-JAN-00:40 | 7925.27 | 30-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 18.10 | 0.00 | 01-JAN-00:40 | 7925.27 | 30-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 18.10 | 0.00 | 01-JAN-00:40 | 7925.27 | 30-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.53 | 0.00 | 01-JAN-00:20 | 6336.29 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 24.53 | 0.00 | 01-JAN-00:20 | 6336.29 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 36.32 | 0.00 | 01-JAN-00:40 | 8851.94 | 30-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 10.57 | 0.00 | 01-JAN-00:40 | 8851.94 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 10.57 | 0.00 | 01-JAN-00:40 | 8851.94 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 25.75 | 0.00 | 01-JAN-00:20 | 8549.09 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 25.75 | 0.00 | 01-JAN-00:20 | 8549.09 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 51.64 | 0.00 | 01-JAN-00:40 | 11946.13 | 07-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 11.39 | 0.00 | 01-JAN-00:40 | 11008.22 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 11.39 | 0.00 | 01-JAN-00:40 | 11008.22 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.25 | 0.00 | 01-JAN-00:20 | 11946.13 | 07-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 40.25 | 0.00 | 01-JAN-00:20 | 11946.13 | 07-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 37.02 | 0.00 | 01-JAN-00:40 | 8898.92 | 30-JAN-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.84 | 0.00 | 01-JAN-00:40 | 8898.92 | 30-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.84 | 0.00 | 01-JAN-00:40 | 8898.92 | 30-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.17 | 0.00 | 01-JAN-00:20 | 8642.77 | 05-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.17 | 0.00 | 01-JAN-00:20 | 8642.77 | 05-JUL-16:00 |
PlantLoopHeatingDemand:Facility | 55.82 | 0.00 | 01-JAN-00:10 | 7152.33 | 23-FEB-12:30 |
PlantLoopHeatingDemand:Plant | 55.82 | 0.00 | 01-JAN-00:10 | 7152.33 | 23-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 55.82 | 0.00 | 01-JAN-00:10 | 7152.33 | 23-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 55.82 | 0.00 | 01-JAN-00:10 | 7152.33 | 23-FEB-12:30 |
EnergyTransfer:HVAC | 1260.99 | 0.00 | 01-JAN-00:40 | 342582.08 | 04-AUG-07:20 |
HeatingCoils:EnergyTransfer | 671.44 | 0.00 | 01-JAN-00:40 | 323732.52 | 02-FEB-07:10 |
CoolingCoils:EnergyTransfer | 589.54 | 0.00 | 01-JAN-00:10 | 342582.08 | 04-AUG-07:20 |
EnergyTransfer:Plant | 55.82 | 0.00 | 01-JAN-00:10 | 7152.33 | 23-FEB-12:30 |
WaterSystems:EnergyTransfer | 55.82 | 0.00 | 01-JAN-00:10 | 7152.33 | 23-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 55.82 | 0.00 | 01-JAN-00:10 | 7152.33 | 23-FEB-12:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.609 | -189.289 | 0.000 | 0.000 | 33.790 | 48.333 | 236.167 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -129.610 |
CORE_MID | 0.000 | 0.000 | 5.598 | -121.315 | 0.000 | 0.000 | 35.289 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -83.331 |
CORE_TOP | 0.000 | 0.000 | 20.852 | -110.200 | 0.000 | 0.000 | 35.930 | 48.333 | 115.425 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -110.340 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 31.379 | -23.764 | 0.000 | 0.000 | 7.703 | 6.023 | 24.333 | 15.952 | 0.000 | 0.044 | 0.001 | 0.000 | -36.852 | 0.000 | -6.128 | -18.690 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 18.276 | -25.166 | 0.000 | 0.000 | 4.835 | 3.779 | 15.404 | 29.912 | 0.000 | 0.029 | 0.000 | 0.000 | -22.877 | 0.000 | -4.130 | -20.062 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 22.026 | -39.249 | 0.000 | 0.000 | 7.519 | 5.903 | 24.332 | 61.567 | 0.000 | 0.040 | 0.001 | 0.000 | -33.475 | 0.000 | -6.328 | -42.335 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 19.174 | -25.756 | 0.000 | 0.000 | 4.880 | 3.767 | 15.403 | 31.246 | 0.000 | 0.028 | 0.000 | 0.000 | -23.704 | 0.000 | -4.145 | -20.892 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 20.089 | -20.409 | 0.000 | 0.000 | 7.688 | 6.003 | 24.333 | 16.284 | 0.000 | 0.030 | 0.000 | 0.000 | -37.558 | 0.000 | -3.356 | -13.104 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 11.289 | -21.786 | 0.000 | 0.000 | 4.799 | 3.770 | 15.404 | 30.084 | 0.000 | 0.017 | 0.000 | 0.000 | -23.615 | 0.000 | -2.285 | -17.677 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 47.278 | -26.798 | 0.000 | 0.000 | 7.896 | 5.890 | 24.332 | 62.659 | 0.000 | 1.638 | 0.000 | 0.000 | -33.885 | 0.000 | -68.493 | -20.518 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 11.723 | -21.798 | 0.000 | 0.000 | 4.832 | 3.758 | 15.403 | 31.459 | 0.000 | 0.016 | 0.000 | 0.000 | -24.469 | 0.000 | -2.294 | -18.631 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 18.104 | -24.530 | 0.000 | 0.000 | 7.614 | 6.023 | 24.333 | 15.725 | 0.000 | 0.039 | 0.000 | 0.000 | -38.397 | 0.000 | -5.306 | -3.604 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 10.569 | -25.752 | 0.000 | 0.000 | 3.550 | 3.779 | 15.404 | 29.744 | 0.000 | 0.025 | 0.000 | 0.000 | -23.794 | 0.000 | -3.567 | -9.957 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 11.395 | -40.249 | 0.000 | 0.000 | 7.413 | 5.903 | 24.332 | 61.269 | 0.000 | 0.034 | 0.000 | 0.000 | -34.975 | 0.000 | -5.490 | -29.633 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 10.844 | -26.172 | 0.000 | 0.000 | 4.825 | 3.767 | 15.403 | 31.100 | 0.000 | 0.023 | 0.000 | 0.000 | -24.690 | 0.000 | -3.585 | -11.518 |
TOPFLOOR_PLENUM | 41.328 | -23.358 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.035 | 0.000 | 0.000 | 0.000 | 0.000 | -9.221 | -8.784 |
MIDFLOOR_PLENUM | 17.311 | -12.369 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.056 | 3.996 | 0.000 | 0.000 | 0.000 | -8.995 | -0.001 |
FIRSTFLOOR_PLENUM | 11.880 | -15.888 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.044 | 11.189 | 0.000 | 0.000 | 0.000 | -7.224 | -0.000 |
Total Facility | 70.519 | -51.615 | 259.205 | -742.235 | 0.000 | 0.000 | 178.566 | 203.365 | 705.434 | 417.001 | 0.000 | 2.099 | 15.188 | 0.000 | -358.290 | 0.000 | -140.545 | -558.687 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 05-JUL-04:03 | 0.00 | 0.00 | 0.00 | -41487.84 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 36613.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-JUL-04:03 | 0.00 | 0.00 | 0.00 | -30179.48 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 27268.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 03-JUL-04:03 | 0.00 | 0.00 | 0.00 | -32012.22 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 29101.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-18:02 | 0.00 | 0.00 | 0.00 | -10369.08 | 0.00 | 0.00 | 0.00 | 23.57 | 386.10 | 3627.67 | 0.00 | 124.53 | 6207.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-08:52 | 0.00 | 0.00 | 0.00 | -13394.78 | 0.00 | 0.00 | 13.47 | 14.92 | 302.86 | 9991.24 | 0.00 | 0.00 | 3094.18 | 0.00 | -0.00 | 0.00 | -21.89 | 0.00 |
PERIMETER_TOP_ZN_1 | 17-SEP-13:52 | 0.00 | 0.00 | 0.00 | -16405.27 | 0.00 | 0.00 | 22.60 | 23.57 | 478.41 | 11589.19 | 0.00 | 1.20 | 4290.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 23-JUL-15:52 | 0.00 | 0.00 | 0.00 | -15355.10 | 0.00 | 0.00 | 14.29 | 14.92 | 302.86 | 10129.98 | 0.00 | 0.00 | 4911.26 | 0.00 | -0.00 | 0.00 | -18.20 | 0.00 |
PERIMETER_BOT_ZN_3 | 05-JUL-06:03 | 0.00 | 0.00 | 0.00 | -5815.00 | 0.00 | 0.00 | 149.04 | 141.46 | 637.89 | 2658.92 | 0.00 | 0.00 | 2235.23 | 0.00 | -0.00 | 0.00 | -7.53 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-09:21 | 0.00 | 0.00 | 0.00 | -10760.26 | 0.00 | 0.00 | 15.73 | 14.92 | 302.86 | 9148.01 | 0.00 | 0.00 | 1284.78 | 0.00 | -0.00 | 0.00 | -6.04 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-14:22 | 0.00 | 0.00 | 0.00 | -13392.14 | 0.00 | 0.00 | 25.08 | 23.57 | 478.41 | 10533.53 | 0.00 | 0.00 | 2370.50 | 0.00 | -0.00 | 0.00 | -38.96 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-17:21 | 0.00 | 0.00 | 0.00 | -11852.43 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 9756.14 | 0.00 | 8.89 | 1828.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-18:31 | 0.00 | 0.00 | 0.00 | -9307.74 | 0.00 | 0.00 | 0.00 | 23.57 | 386.10 | 3579.53 | 0.00 | 68.64 | 5249.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 25-JUN-08:31 | 0.00 | 0.00 | 0.00 | -14307.52 | 0.00 | 0.00 | 13.82 | 14.92 | 302.86 | 10345.63 | 0.00 | 0.00 | 3682.07 | 0.00 | -0.00 | 0.00 | -51.79 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-13:12 | 0.00 | 0.00 | 0.00 | -14831.28 | 0.00 | 0.00 | 23.04 | 23.57 | 478.41 | 13470.32 | 0.00 | 0.00 | 887.62 | 0.00 | -0.00 | 0.00 | -51.68 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-18:31 | 0.00 | 0.00 | 0.00 | -14373.22 | 0.00 | 0.00 | 0.00 | 14.92 | 244.42 | 6210.13 | 0.00 | 23.63 | 7880.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:50 | 0.00 | -10719.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.73 | 10679.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-JUL-06:15 | 0.00 | -5090.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5114.34 | 0.00 | -0.00 | 0.00 | -23.85 | 0.00 |
FIRSTFLOOR_PLENUM | 26-JUN-12:08 | 0.00 | -5870.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.95 | 5837.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-06:03 | 0.00 | -8411.17 | 0.00 | -157624.92 | 0.00 | 0.00 | 3566.26 | 5666.32 | 21098.80 | 7576.98 | 0.00 | 0.00 | 133895.69 | 0.00 | 0.00 | 0.00 | -5767.96 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 22590.95 | 0.00 | 0.00 | 0.00 | 0.00 | 468.92 | 4405.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27465.51 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 26230.30 | 0.00 | 0.00 | 0.00 | 0.00 | 468.92 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29141.27 |
CORE_TOP | 11-DEC-00:02 | 0.00 | 0.00 | 30673.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.43 | 2442.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -33349.49 |
PERIMETER_TOP_ZN_3 | 29-JAN-19:32 | 0.00 | 0.00 | 10831.71 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3873.72 | 0.00 | -1411.64 | -5981.86 |
PERIMETER_TOP_ZN_2 | 02-FEB-03:12 | 0.00 | 0.00 | 12098.75 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3223.86 | 0.00 | -821.19 | -8410.88 |
PERIMETER_TOP_ZN_1 | 29-JAN-07:32 | 0.00 | 0.00 | 14810.04 | 0.00 | 0.00 | 0.00 | 60.40 | 42.14 | 478.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3523.85 | 0.00 | -1653.09 | -10214.04 |
PERIMETER_TOP_ZN_4 | 02-FEB-03:12 | 0.00 | 0.00 | 13256.39 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3330.11 | 0.00 | -822.42 | -9461.03 |
PERIMETER_BOT_ZN_3 | 29-JAN-19:32 | 0.00 | 0.00 | 7767.09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 386.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3965.54 | 0.00 | -775.12 | -3461.95 |
PERIMETER_BOT_ZN_2 | 29-JAN-19:32 | 0.00 | 0.00 | 9279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 31.29 | 244.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2586.87 | 0.00 | -526.70 | -6441.81 |
PERIMETER_BOT_ZN_1 | 02-FEB-07:10 | 0.00 | 0.00 | 19392.91 | 0.00 | 0.00 | 0.00 | 236.13 | 296.56 | 637.88 | 0.00 | 0.00 | 0.00 | 34856.46 | 0.00 | -4963.36 | 0.00 | -50456.58 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-DEC-01:22 | 0.00 | 0.00 | 9912.78 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2476.89 | 0.00 | -295.26 | -7497.80 |
PERIMETER_MID_ZN_3 | 02-FEB-04:53 | 0.00 | 0.00 | 8445.61 | 0.00 | 0.00 | 0.00 | 0.00 | 49.42 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5155.37 | 0.00 | -768.57 | -3085.90 |
PERIMETER_MID_ZN_2 | 11-DEC-05:11 | 0.00 | 0.00 | 11201.65 | 0.00 | 0.00 | 0.00 | 0.00 | 62.58 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2407.98 | 0.00 | -356.18 | -8825.96 |
PERIMETER_MID_ZN_1 | 11-DEC-05:11 | 0.00 | 0.00 | 12686.26 | 0.00 | 0.00 | 0.00 | 0.00 | 98.85 | 514.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3636.74 | 0.00 | -533.35 | -9129.82 |
PERIMETER_MID_ZN_4 | 30-JAN-04:41 | 0.00 | 0.00 | 11474.40 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 325.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2857.44 | 0.00 | -631.11 | -8343.02 |
TOPFLOOR_PLENUM | 02-FEB-06:10 | 19546.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -271.55 | -19275.37 |
MIDFLOOR_PLENUM | 02-JAN-07:11 | 10077.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -226.69 | -9850.71 |
FIRSTFLOOR_PLENUM | 02-JAN-07:01 | 8850.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -170.34 | -8680.49 |
Total Facility | 02-JAN-05:01 | 13461.06 | 0.00 | 203460.10 | 0.00 | 0.00 | 0.00 | 0.00 | 2375.34 | 14333.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19576.78 | 0.00 | -5506.22 | -208547.42 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 5.4733 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.8137 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.0899 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.2479 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.5266 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 4.9451 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.7367 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3718 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 2.5450 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.3965 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 2.7633 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 1.4830 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000432 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000432 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000432 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000432 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000432 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8366 | 2.8366 | 0.7744 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0491 | 2.0491 | 0.7459 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1685 | 2.1685 | 0.7785 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6994 | 0.6994 | 0.1728 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8001 | 0.8001 | 0.1600 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9795 | 0.9795 | 0.1959 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8791 | 0.8791 | 0.1758 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5262 | 0.5262 | 0.1668 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6474 | 0.6474 | 0.1295 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7716 | 0.7716 | 0.1628 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6915 | 0.6915 | 0.1383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5738 | 0.5738 | 0.1572 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7804 | 0.7804 | 0.1561 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8816 | 0.8816 | 0.1763 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8050 | 0.8050 | 0.1610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 5.4733 | 4.8137 | 5.4733 | 1.3718 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.0899 | 4.2479 | 5.0899 | 1.3965 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.5266 | 4.9451 | 5.5266 | 1.4830 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4183 | 1.4183 | 0.7744 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0245 | 1.0245 | 0.7459 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0842 | 1.0842 | 0.7785 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3497 | 0.3497 | 0.1728 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4001 | 0.4001 | 0.1600 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4897 | 0.4897 | 0.1959 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4396 | 0.4396 | 0.1758 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2631 | 0.2631 | 0.1668 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3237 | 0.3237 | 0.1295 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3858 | 0.3858 | 0.1628 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3458 | 0.3458 | 0.1383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2869 | 0.2869 | 0.1572 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3902 | 0.3902 | 0.1561 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4408 | 0.4408 | 0.1763 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4025 | 0.4025 | 0.1610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.7367 | 1.3718 | 1.3718 | 1.3718 | 0.0000 | 1.0000 |
PACU_VAV_MID | 2.5450 | 1.3965 | 1.3965 | 1.3965 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 2.7633 | 1.4830 | 1.4830 | 1.4830 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 794.83 |
Number of hours cooling loads not met | 102.33 |
Number of hours not met | 897.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 371.42 | 201104.60 | 375.03 | 190421.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 132.15 | 72586.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 203.36 | 21377.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 50.26 | 5557.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 584.69 | 34487.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 120.10 | 11290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 0.64 | 86.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 11.66 | 835.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 91.81 | 29055.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.02 | 0.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 116.05 | 12041.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 705.43 | 1566.10 |
Natural Gas | 0.00 | 491.08 |
Additional | 0.00 | 0.00 |
Total | 705.43 | 2057.19 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 40.82 |
Space Heating | 74.55 |
Space Cooling | 26.52 |
Fans (All) | 18.43 |
Service Water Heating | 0.00 |
Receptacle Equipment | 141.59 |
Miscellaneous (All) | 314.34 |
Subtotal | 314.34 |
Natural Gas [MJ/m2] | |
Space Heating | 75.27 |
Service Water Heating | 23.29 |
Miscellaneous (All) | 98.57 |
Subtotal | 98.57 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.89 |
Space Heating | 36.29 |
Space Cooling | 6.42 |
Fans (All) | 4.46 |
Service Water Heating | 5.64 |
Receptacle Equipment | 34.29 |
Miscellaneous | 3.01 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2362. | 8760. |
BLDG_EQUIP_SCH | 4095. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 2070. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
PERIMETER_MID_ZN_2_MDP_SCH | 1574. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM_STARTSTOP | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8747.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8688.83 | 71.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8698.83 | 61.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8662.50 | 97.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8711.17 | 48.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8735.00 | 25.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8699.67 | 60.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8693.83 | 66.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8706.17 | 53.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8667.50 | 92.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8647.00 | 113.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8647.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 113.00 | 0.00 | 0.00 | 0.00 |
Average | 8720.14 | 39.86 | 0.00 | 0.00 | 0.00 |
Sum | 156962.50 | 717.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
CORE_BOTTOM | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10134.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128304.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Average | 34143.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Sum | 614580.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 8315.67 | 444.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8425.50 | 334.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8523.33 | 236.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8385.67 | 374.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8344.50 | 415.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8345.33 | 414.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8317.67 | 442.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8550.67 | 209.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8421.67 | 338.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8321.83 | 438.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8381.33 | 378.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8368.67 | 391.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8343.17 | 416.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8315.50 | 444.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8278.00 | 482.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8017.33 | 742.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8448.50 | 311.50 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 8467.33 | 292.67 | 0.00 | 0.00 | 0.00 |
Min | 8017.33 | 209.33 | 0.00 | 0.00 | 0.00 |
Max | 8550.67 | 742.67 | 0.00 | 0.00 | 0.00 |
Average | 8365.09 | 394.91 | 0.00 | 0.00 | 0.00 |
Sum | 150571.67 | 7108.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
CORE_BOTTOM | 128039.17 | 264.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 128163.67 | 140.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 128219.00 | 85.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24898.33 | 10.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 24901.33 | 7.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 14016.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 24902.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 14012.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 24007.50 | 901.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 14013.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 24891.17 | 17.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 10132.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 24897.33 | 11.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 14013.00 | 3.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 128219.00 | 901.50 | 0.00 | 0.00 | 0.00 |
Average | 34062.34 | 80.99 | 0.00 | 0.00 | 0.00 |
Sum | 613122.17 | 1457.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:35:21
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 5840.00 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 10134.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 14016.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 24909.00 | 0.00 |
Average | 0.00 | 0.00 | 12759.33 | 0.00 |
Sum | 0.00 | 0.00 | 229668.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2021
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.794106E+10 | 7631.56 | 13-JAN-17:00 | 2.20 | 0.77 | 0.162775E+10 | 2564.91 | 13-JAN-14:09 | 2.20 | 0.77 |
February | 0.801751E+10 | 9002.63 | 24-FEB-17:00 | 7.20 | 5.13 | 0.158245E+10 | 2597.19 | 24-FEB-14:09 | 7.20 | 5.13 |
March | 0.112570E+11 | 15532.97 | 24-MAR-07:20 | 8.30 | 5.13 | 0.204231E+10 | 2606.64 | 28-MAR-09:39 | 9.07 | 5.68 |
April | 0.132854E+11 | 39502.14 | 19-APR-05:02 | 5.40 | 4.35 | 0.187701E+10 | 2606.67 | 13-APR-09:09 | 5.40 | 4.35 |
May | 0.190786E+11 | 36678.03 | 30-MAY-06:02 | 15.18 | 15.13 | 0.207317E+10 | 2606.72 | 09-MAY-13:09 | 15.18 | 15.13 |
June | 0.234782E+11 | 39475.46 | 24-JUN-05:03 | 15.78 | 13.36 | 0.206901E+10 | 2606.69 | 01-JUN-09:00 | 15.78 | 13.36 |
July | 0.244598E+11 | 41493.45 | 05-JUL-04:03 | 18.72 | 18.00 | 0.192428E+10 | 2606.65 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.258358E+11 | 39708.40 | 19-AUG-05:03 | 15.68 | 13.97 | 0.215994E+10 | 2818.52 | 04-AUG-07:40 | 15.68 | 13.97 |
September | 0.213102E+11 | 41171.61 | 11-SEP-04:03 | 20.50 | 17.33 | 0.191517E+10 | 2606.67 | 06-SEP-09:09 | 20.50 | 17.33 |
October | 0.146702E+11 | 18709.57 | 13-OCT-07:02 | 1.65 | 0.38 | 0.197794E+10 | 2608.54 | 24-OCT-09:09 | 6.03 | 2.72 |
November | 0.112006E+11 | 17731.35 | 07-NOV-08:07 | 10.18 | 9.48 | 0.187049E+10 | 2608.54 | 16-NOV-14:39 | 7.60 | 2.84 |
December | 0.875499E+10 | 8899.86 | 07-DEC-16:20 | -5.7 | -8.8 | 0.168478E+10 | 2606.56 | 07-DEC-14:09 | -5.7 | -8.8 |
Annual Sum or Average | 0.189289E+12 | 0.228043E+11 | ||||||||
Minimum of Months | 0.794106E+10 | 7631.56 | -5.7 | -8.8 | 0.158245E+10 | 2564.91 | -5.7 | -8.8 | ||
Maximum of Months | 0.258358E+11 | 41493.45 | 20.50 | 18.00 | 0.215994E+10 | 2818.52 | 21.28 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 11136582.81 | 645.34 | 25-FEB-16:20 | 5.40 | 2.62 | 0.00 | 0.00 | 01-FEB-00:10 | 5.40 | 2.62 |
March | 0.197975E+09 | 1967.86 | 25-MAR-15:05 | 18.72 | 10.45 | 0.00 | 0.00 | 01-MAR-00:10 | 18.72 | 10.45 |
April | 0.121878E+10 | 8195.72 | 18-APR-14:30 | 28.30 | 20.65 | 0.00 | 0.00 | 01-APR-00:10 | 28.30 | 20.65 |
May | 0.273842E+10 | 9344.75 | 31-MAY-14:00 | 29.40 | 19.44 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 19.44 |
June | 0.510030E+10 | 10719.74 | 26-JUN-13:50 | 31.60 | 21.99 | 0.00 | 0.00 | 01-JUN-00:10 | 31.60 | 21.99 |
July | 0.564356E+10 | 10204.82 | 05-JUL-13:50 | 27.12 | 19.90 | 0.00 | 0.00 | 01-JUL-00:10 | 27.12 | 19.90 |
August | 0.518586E+10 | 10597.41 | 04-AUG-15:20 | 33.90 | 25.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.66 |
September | 0.275853E+10 | 9490.55 | 07-SEP-15:00 | 31.70 | 18.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.53 |
October | 0.438405E+09 | 3331.26 | 20-OCT-14:40 | 23.07 | 13.25 | 0.00 | 0.00 | 01-OCT-00:10 | 23.07 | 13.25 |
November | 65762142.23 | 1692.73 | 04-NOV-15:02 | 14.13 | 6.72 | 0.00 | 0.00 | 01-NOV-00:10 | 14.13 | 6.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.233587E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.8 | -3.2 | 0.00 | 0.00 | -2.8 | -3.2 | ||
Maximum of Months | 0.564356E+10 | 10719.74 | 33.90 | 25.66 | 0.00 | 0.00 | 33.90 | 25.66 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11489658.31 | 2648.68 | 05-JAN-05:01 | -21.2 | -21.5 | 0.00 | 0.00 | 01-JAN-00:10 | -21.2 | -21.5 |
February | 14196962.48 | 2246.02 | 01-FEB-05:01 | -30.2 | -30.4 | 0.00 | 0.00 | 01-FEB-00:10 | -30.2 | -30.4 |
March | 72885009.20 | 1704.77 | 30-MAR-06:01 | 1.10 | 0.61 | 0.00 | 0.00 | 01-MAR-00:10 | 1.10 | 0.61 |
April | 0.473631E+09 | 3093.96 | 18-APR-15:20 | 27.20 | 20.26 | 0.00 | 0.00 | 01-APR-00:10 | 27.20 | 20.26 |
May | 0.113196E+10 | 3663.81 | 31-MAY-15:40 | 28.87 | 19.09 | 0.00 | 0.00 | 01-MAY-00:10 | 28.87 | 19.09 |
June | 0.273252E+10 | 4805.93 | 26-JUN-15:40 | 31.50 | 22.02 | 0.00 | 0.00 | 01-JUN-00:10 | 31.50 | 22.02 |
July | 0.316671E+10 | 5091.01 | 05-JUL-06:15 | 19.80 | 18.77 | 0.00 | 0.00 | 01-JUL-00:10 | 19.80 | 18.77 |
August | 0.292256E+10 | 4361.46 | 04-AUG-15:40 | 33.90 | 26.00 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 26.00 |
September | 0.157518E+10 | 4074.47 | 07-SEP-16:00 | 31.70 | 18.53 | 0.00 | 0.00 | 01-SEP-00:10 | 31.70 | 18.53 |
October | 0.195206E+09 | 2089.22 | 13-OCT-06:01 | 0.75 | -0.4 | 0.00 | 0.00 | 01-OCT-00:10 | 0.75 | -0.4 |
November | 66421804.11 | 1840.44 | 25-NOV-05:01 | -15.3 | -15.7 | 0.00 | 0.00 | 01-NOV-00:10 | -15.3 | -15.7 |
December | 5887166.75 | 2086.86 | 28-DEC-05:01 | -17.2 | -17.5 | 0.00 | 0.00 | 01-DEC-00:10 | -17.2 | -17.5 |
Annual Sum or Average | 0.123686E+11 | 0.00 | ||||||||
Minimum of Months | 5887166.75 | 1704.77 | -30.2 | -30.4 | 0.00 | 0.00 | -30.2 | -30.4 | ||
Maximum of Months | 0.316671E+10 | 5091.01 | 33.90 | 26.00 | 0.00 | 0.00 | 33.90 | 26.00 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121312E+09 | 3286.59 | 05-JAN-17:10 | -20.7 | -21.2 | 0.00 | 0.00 | 01-JAN-00:10 | -20.7 | -21.2 |
February | 0.128214E+09 | 4374.82 | 02-FEB-17:10 | -29.6 | -29.9 | 0.00 | 0.00 | 01-FEB-00:10 | -29.6 | -29.9 |
March | 0.225911E+09 | 2719.94 | 21-MAR-06:10 | -7.2 | -8.3 | 0.00 | 0.00 | 01-MAR-00:10 | -7.2 | -8.3 |
April | 0.678041E+09 | 3295.56 | 21-APR-06:01 | 0.50 | 0.01 | 0.00 | 0.00 | 01-APR-00:10 | 0.50 | 0.01 |
May | 0.157768E+10 | 3748.11 | 31-MAY-15:10 | 29.72 | 19.55 | 0.00 | 0.00 | 01-MAY-00:10 | 29.72 | 19.55 |
June | 0.308562E+10 | 5870.94 | 26-JUN-12:08 | 30.68 | 21.60 | 0.00 | 0.00 | 01-JUN-00:10 | 30.68 | 21.60 |
July | 0.360852E+10 | 5364.17 | 05-JUL-06:15 | 19.80 | 18.77 | 0.00 | 0.00 | 01-JUL-00:10 | 19.80 | 18.77 |
August | 0.360190E+10 | 4489.53 | 04-AUG-12:10 | 31.20 | 26.19 | 0.00 | 0.00 | 01-AUG-00:10 | 31.20 | 26.19 |
September | 0.221367E+10 | 4496.60 | 11-SEP-15:30 | 28.05 | 20.01 | 0.00 | 0.00 | 01-SEP-00:10 | 28.05 | 20.01 |
October | 0.381672E+09 | 2207.86 | 26-OCT-06:01 | -0.9 | -2.2 | 0.00 | 0.00 | 01-OCT-00:10 | -0.9 | -2.2 |
November | 0.170103E+09 | 2172.98 | 09-NOV-18:01 | 1.10 | 0.21 | 0.00 | 0.00 | 01-NOV-00:10 | 1.10 | 0.21 |
December | 95797588.76 | 3136.45 | 08-DEC-17:10 | -19.2 | -19.4 | 0.00 | 0.00 | 01-DEC-00:10 | -19.2 | -19.4 |
Annual Sum or Average | 0.158884E+11 | 0.00 | ||||||||
Minimum of Months | 95797588.76 | 2172.98 | -29.6 | -29.9 | 0.00 | 0.00 | -29.6 | -29.9 | ||
Maximum of Months | 0.360852E+10 | 5870.94 | 31.20 | 26.19 | 0.00 | 0.00 | 31.20 | 26.19 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356543E+10 | 6000.58 | 13-JAN-17:00 | 2.20 | 0.77 | 0.147218E+10 | 2221.33 | 13-JAN-14:00 | 2.20 | 0.77 |
February | 0.444471E+10 | 6238.46 | 24-FEB-17:00 | 7.20 | 5.13 | 0.137512E+10 | 2247.20 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.719691E+10 | 7110.50 | 24-MAR-16:00 | 10.60 | 5.50 | 0.177467E+10 | 2510.86 | 24-MAR-13:00 | 10.60 | 5.50 |
April | 0.910877E+10 | 23878.03 | 17-APR-05:03 | 11.42 | 9.68 | 0.172049E+10 | 2606.61 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.130490E+11 | 29381.98 | 30-MAY-05:03 | 14.50 | 14.50 | 0.204025E+10 | 2606.69 | 09-MAY-13:09 | 14.50 | 14.50 |
June | 0.162276E+11 | 30034.95 | 12-JUN-04:03 | 18.22 | 17.50 | 0.205873E+10 | 2606.65 | 01-JUN-09:00 | 18.22 | 17.50 |
July | 0.172040E+11 | 30183.08 | 05-JUL-04:03 | 18.72 | 18.00 | 0.191977E+10 | 2606.64 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.173413E+11 | 29098.21 | 28-AUG-05:03 | 18.40 | 18.00 | 0.215456E+10 | 2671.35 | 04-AUG-07:30 | 18.40 | 18.00 |
September | 0.135491E+11 | 30116.30 | 11-SEP-04:03 | 20.50 | 17.33 | 0.188525E+10 | 2606.67 | 06-SEP-09:09 | 20.50 | 17.33 |
October | 0.877417E+10 | 8344.68 | 20-OCT-13:10 | 21.93 | 12.68 | 0.182151E+10 | 2604.20 | 03-OCT-13:00 | 21.93 | 12.68 |
November | 0.639233E+10 | 7515.97 | 03-NOV-13:30 | 15.85 | 10.76 | 0.162883E+10 | 2531.35 | 03-NOV-15:00 | 15.00 | 9.33 |
December | 0.446118E+10 | 5862.53 | 01-DEC-16:20 | -2.4 | -4.5 | 0.145343E+10 | 2195.12 | 07-DEC-14:00 | -3.3 | -7.2 |
Annual Sum or Average | 0.121315E+12 | 0.213048E+11 | ||||||||
Minimum of Months | 0.356543E+10 | 5862.53 | -2.4 | -4.5 | 0.137512E+10 | 2195.12 | -3.3 | -7.2 | ||
Maximum of Months | 0.173413E+11 | 30183.08 | 21.93 | 18.00 | 0.215456E+10 | 2671.35 | 23.27 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188802E+10 | 5831.52 | 13-JAN-16:40 | 2.77 | 1.17 | 0.145380E+10 | 2128.89 | 13-JAN-14:00 | 2.77 | 1.17 |
February | 0.280528E+10 | 6355.94 | 24-FEB-17:00 | 7.20 | 5.13 | 0.133659E+10 | 2211.62 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.569565E+10 | 7319.20 | 24-MAR-16:00 | 10.60 | 5.50 | 0.168709E+10 | 2465.94 | 24-MAR-13:00 | 10.60 | 5.50 |
April | 0.827445E+10 | 15918.47 | 17-APR-15:30 | 19.40 | 11.54 | 0.164471E+10 | 2606.66 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.128874E+11 | 18062.14 | 30-MAY-05:03 | 14.50 | 14.50 | 0.200352E+10 | 2606.68 | 09-MAY-13:09 | 14.50 | 14.50 |
June | 0.166064E+11 | 31665.59 | 26-JUN-04:03 | 21.60 | 20.40 | 0.203994E+10 | 2606.66 | 09-JUN-09:30 | 21.60 | 20.40 |
July | 0.175867E+11 | 32016.05 | 03-JUL-04:03 | 18.80 | 17.39 | 0.191465E+10 | 2606.68 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.172419E+11 | 30630.18 | 28-AUG-05:03 | 18.40 | 18.00 | 0.214553E+10 | 2606.70 | 08-AUG-09:09 | 18.40 | 18.00 |
September | 0.126158E+11 | 27739.47 | 11-SEP-05:03 | 19.90 | 17.36 | 0.182529E+10 | 2606.71 | 06-SEP-09:39 | 19.90 | 17.36 |
October | 0.758313E+10 | 7732.88 | 20-OCT-13:30 | 22.20 | 12.82 | 0.167419E+10 | 2528.41 | 20-OCT-15:00 | 21.30 | 12.72 |
November | 0.468257E+10 | 7371.63 | 03-NOV-16:00 | 15.00 | 9.33 | 0.153007E+10 | 2466.41 | 03-NOV-15:00 | 15.00 | 9.33 |
December | 0.233310E+10 | 5729.87 | 01-DEC-16:10 | -2.1 | -4.3 | 0.140904E+10 | 2097.78 | 01-DEC-14:00 | -2.1 | -4.3 |
Annual Sum or Average | 0.110200E+12 | 0.206644E+11 | ||||||||
Minimum of Months | 0.188802E+10 | 5729.87 | -2.1 | -4.3 | 0.133659E+10 | 2097.78 | -2.1 | -4.3 | ||
Maximum of Months | 0.175867E+11 | 32016.05 | 22.20 | 20.40 | 0.214553E+10 | 2606.71 | 23.68 | 20.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16043357.45 | 1012.09 | 13-JAN-21:03 | -0.1 | -0.9 | 0.300289E+09 | 406.72 | 18-JAN-14:00 | -17.2 | -17.5 |
February | 44148272.83 | 1149.27 | 24-FEB-16:20 | 7.93 | 5.63 | 0.273844E+09 | 413.57 | 24-FEB-14:00 | 7.93 | 5.63 |
March | 0.459344E+09 | 1513.73 | 28-MAR-15:40 | 16.13 | 10.43 | 0.338991E+09 | 490.96 | 28-MAR-15:50 | 15.87 | 10.36 |
April | 0.135727E+10 | 5367.51 | 18-APR-15:00 | 28.30 | 20.65 | 0.325087E+09 | 549.50 | 18-APR-09:09 | 28.30 | 20.65 |
May | 0.304781E+10 | 5906.71 | 31-MAY-15:00 | 30.00 | 19.70 | 0.411669E+09 | 549.50 | 09-MAY-13:09 | 30.00 | 19.70 |
June | 0.477659E+10 | 10369.97 | 25-JUN-18:02 | 30.82 | 21.76 | 0.426746E+09 | 549.50 | 09-JUN-09:30 | 30.82 | 21.76 |
July | 0.503181E+10 | 8223.61 | 03-JUL-06:03 | 19.08 | 17.92 | 0.403654E+09 | 549.51 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.472146E+10 | 6573.34 | 04-AUG-15:20 | 33.90 | 25.66 | 0.449512E+09 | 549.51 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.283386E+10 | 5845.97 | 11-SEP-14:00 | 28.90 | 20.23 | 0.369665E+09 | 549.51 | 06-SEP-09:39 | 28.90 | 20.23 |
October | 0.103880E+10 | 1644.31 | 20-OCT-13:40 | 22.33 | 12.89 | 0.326876E+09 | 519.15 | 20-OCT-15:00 | 21.30 | 12.72 |
November | 0.424447E+09 | 1487.71 | 03-NOV-15:40 | 15.37 | 9.43 | 0.308631E+09 | 488.57 | 03-NOV-13:00 | 15.37 | 9.43 |
December | 13133311.95 | 1012.68 | 02-DEC-16:03 | 4.95 | 2.78 | 0.292130E+09 | 406.74 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.237647E+11 | 0.422709E+10 | ||||||||
Minimum of Months | 13133311.95 | 1012.09 | -0.1 | -0.9 | 0.273844E+09 | 406.72 | -17.2 | -17.5 | ||
Maximum of Months | 0.503181E+10 | 10369.97 | 33.90 | 25.66 | 0.449512E+09 | 549.51 | 30.82 | 21.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40367251.00 | 929.04 | 13-JAN-21:03 | -0.1 | -0.9 | 0.192490E+09 | 257.49 | 23-JAN-14:30 | -14.2 | -14.6 |
February | 0.136832E+09 | 1370.58 | 24-FEB-10:20 | 4.80 | 1.70 | 0.176219E+09 | 315.00 | 24-FEB-10:30 | 5.00 | 1.88 |
March | 0.687268E+09 | 2256.06 | 28-MAR-09:35 | 9.07 | 5.68 | 0.222206E+09 | 347.88 | 28-MAR-09:50 | 9.53 | 5.99 |
April | 0.157516E+10 | 7306.21 | 18-APR-09:30 | 24.20 | 19.59 | 0.214046E+09 | 347.89 | 18-APR-09:09 | 24.20 | 19.59 |
May | 0.327111E+10 | 10384.52 | 29-MAY-10:23 | 24.45 | 18.61 | 0.267519E+09 | 348.32 | 31-MAY-09:50 | 27.02 | 19.46 |
June | 0.486583E+10 | 13362.46 | 25-JUN-08:42 | 25.73 | 21.05 | 0.269420E+09 | 348.41 | 26-JUN-09:00 | 28.30 | 22.44 |
July | 0.518738E+10 | 13399.90 | 02-JUL-08:52 | 25.60 | 21.00 | 0.256043E+09 | 348.53 | 05-JUL-09:30 | 23.60 | 20.34 |
August | 0.471726E+10 | 11155.12 | 20-AUG-09:53 | 22.80 | 19.05 | 0.285607E+09 | 348.41 | 02-AUG-09:50 | 22.80 | 19.05 |
September | 0.312603E+10 | 11541.55 | 04-SEP-09:32 | 17.57 | 12.97 | 0.240075E+09 | 347.90 | 06-SEP-09:39 | 24.67 | 18.11 |
October | 0.113529E+10 | 2487.93 | 20-OCT-09:50 | 14.70 | 9.97 | 0.213397E+09 | 347.88 | 20-OCT-09:09 | 14.70 | 9.97 |
November | 0.396854E+09 | 1348.39 | 04-NOV-09:40 | 8.13 | 4.42 | 0.194747E+09 | 308.97 | 03-NOV-13:00 | 8.13 | 4.42 |
December | 26987105.23 | 934.07 | 02-DEC-16:03 | 4.95 | 2.78 | 0.185837E+09 | 257.49 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.251664E+11 | 0.271760E+10 | ||||||||
Minimum of Months | 26987105.23 | 929.04 | -0.1 | -0.9 | 0.176219E+09 | 257.49 | -15.6 | -15.9 | ||
Maximum of Months | 0.518738E+10 | 13399.90 | 25.73 | 21.05 | 0.285607E+09 | 348.53 | 28.30 | 22.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.559426E+09 | 3922.75 | 12-JAN-12:40 | 2.03 | 0.42 | 0.322446E+09 | 549.49 | 12-JAN-14:00 | 2.80 | 1.13 |
February | 0.829091E+09 | 7155.67 | 24-FEB-13:50 | 7.62 | 4.99 | 0.298028E+09 | 549.50 | 24-FEB-14:09 | 7.88 | 5.25 |
March | 0.156112E+10 | 7617.59 | 24-MAR-13:40 | 12.93 | 6.50 | 0.370171E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.274127E+10 | 13321.30 | 16-APR-15:12 | 28.50 | 20.39 | 0.343710E+09 | 549.88 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.423433E+10 | 10405.70 | 29-MAY-12:23 | 24.45 | 18.92 | 0.415543E+09 | 549.79 | 30-MAY-13:50 | 26.70 | 19.86 |
June | 0.588271E+10 | 16145.60 | 11-JUN-12:13 | 30.77 | 22.77 | 0.424962E+09 | 550.05 | 26-JUN-13:00 | 31.70 | 22.11 |
July | 0.651556E+10 | 16205.33 | 02-JUL-12:13 | 28.70 | 22.31 | 0.402842E+09 | 550.00 | 05-JUL-13:00 | 27.20 | 19.77 |
August | 0.696232E+10 | 16363.54 | 13-AUG-13:32 | 25.73 | 19.92 | 0.449570E+09 | 550.13 | 21-AUG-13:50 | 29.32 | 21.76 |
September | 0.551558E+10 | 16405.40 | 17-SEP-13:52 | 27.20 | 18.12 | 0.379849E+09 | 560.09 | 07-SEP-13:39 | 27.20 | 18.12 |
October | 0.272972E+10 | 10349.43 | 20-OCT-13:30 | 22.20 | 12.82 | 0.365915E+09 | 549.59 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.108667E+10 | 9109.37 | 03-NOV-13:30 | 15.85 | 10.76 | 0.324344E+09 | 549.49 | 21-NOV-14:30 | -6.4 | -8.1 |
December | 0.632021E+09 | 5198.25 | 01-DEC-13:30 | -0.9 | -3.3 | 0.313882E+09 | 549.49 | 14-DEC-14:00 | 1.70 | 0.50 |
Annual Sum or Average | 0.392498E+11 | 0.441126E+10 | ||||||||
Minimum of Months | 0.559426E+09 | 3922.75 | -0.9 | -3.3 | 0.298028E+09 | 549.49 | -6.4 | -8.1 | ||
Maximum of Months | 0.696232E+10 | 16405.40 | 30.77 | 22.77 | 0.449570E+09 | 560.09 | 31.70 | 22.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 71544332.11 | 1373.98 | 12-JAN-16:00 | 2.80 | 1.13 | 0.192854E+09 | 287.40 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.187795E+09 | 2388.67 | 24-FEB-16:30 | 7.75 | 5.51 | 0.177337E+09 | 338.68 | 24-FEB-16:10 | 7.75 | 5.51 |
March | 0.656827E+09 | 2722.49 | 23-MAR-16:00 | 17.20 | 10.15 | 0.218261E+09 | 338.68 | 24-MAR-15:30 | 11.70 | 6.01 |
April | 0.181471E+10 | 13890.29 | 15-APR-17:05 | 29.72 | 18.80 | 0.208298E+09 | 347.84 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.325844E+10 | 12536.16 | 14-MAY-16:52 | 21.70 | 15.79 | 0.254128E+09 | 347.85 | 08-MAY-13:00 | 21.70 | 15.79 |
June | 0.476962E+10 | 15160.95 | 25-JUN-16:42 | 31.78 | 21.74 | 0.265702E+09 | 347.85 | 09-JUN-09:30 | 31.78 | 21.74 |
July | 0.517380E+10 | 15354.24 | 23-JUL-15:52 | 22.80 | 15.36 | 0.253515E+09 | 347.86 | 25-JUL-09:09 | 23.68 | 19.04 |
August | 0.488345E+10 | 12909.99 | 13-AUG-16:12 | 25.40 | 20.51 | 0.281457E+09 | 347.86 | 30-AUG-13:00 | 23.90 | 18.14 |
September | 0.315674E+10 | 12358.91 | 04-SEP-16:52 | 22.20 | 14.41 | 0.229054E+09 | 347.85 | 06-SEP-09:50 | 25.13 | 18.36 |
October | 0.122761E+10 | 4909.68 | 20-OCT-15:30 | 22.30 | 13.06 | 0.210922E+09 | 347.76 | 20-OCT-13:00 | 22.30 | 13.06 |
November | 0.451283E+09 | 3007.29 | 03-NOV-15:30 | 15.55 | 9.47 | 0.194512E+09 | 338.68 | 03-NOV-15:00 | 15.00 | 9.33 |
December | 0.105091E+09 | 1365.48 | 01-DEC-15:50 | -1.6 | -4.0 | 0.186280E+09 | 286.65 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.257569E+11 | 0.267232E+10 | ||||||||
Minimum of Months | 71544332.11 | 1365.48 | -1.6 | -4.0 | 0.177337E+09 | 286.65 | -1.7 | -4.1 | ||
Maximum of Months | 0.517380E+10 | 15354.24 | 31.78 | 21.74 | 0.281457E+09 | 347.86 | 31.78 | 21.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16484559.38 | 989.34 | 13-JAN-21:03 | -0.1 | -0.9 | 0.298695E+09 | 406.72 | 18-JAN-14:00 | -17.2 | -17.5 |
February | 23991256.78 | 989.17 | 09-FEB-21:03 | 2.80 | 1.60 | 0.272917E+09 | 406.70 | 01-FEB-14:39 | 2.80 | 1.60 |
March | 0.339385E+09 | 1252.86 | 28-MAR-15:30 | 16.40 | 10.50 | 0.335382E+09 | 447.08 | 28-MAR-13:00 | 16.40 | 10.50 |
April | 0.921131E+09 | 2722.32 | 18-APR-15:20 | 27.20 | 20.26 | 0.313766E+09 | 549.48 | 18-APR-13:09 | 27.20 | 20.26 |
May | 0.214012E+10 | 3648.24 | 31-MAY-15:00 | 30.00 | 19.70 | 0.396562E+09 | 549.50 | 05-MAY-13:09 | 30.00 | 19.70 |
June | 0.354796E+10 | 5067.47 | 26-JUN-14:30 | 31.40 | 21.97 | 0.426187E+09 | 549.50 | 20-JUN-13:00 | 31.40 | 21.97 |
July | 0.404646E+10 | 5816.98 | 05-JUL-06:03 | 19.60 | 18.69 | 0.403535E+09 | 549.50 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.416751E+10 | 5314.17 | 04-AUG-07:33 | 25.03 | 24.26 | 0.452274E+09 | 560.41 | 04-AUG-07:40 | 25.03 | 24.26 |
September | 0.291525E+10 | 5144.66 | 11-SEP-14:00 | 28.90 | 20.23 | 0.384498E+09 | 549.50 | 06-SEP-09:09 | 28.90 | 20.23 |
October | 0.156350E+10 | 1555.88 | 02-OCT-15:20 | 17.73 | 14.45 | 0.346959E+09 | 519.85 | 02-OCT-13:00 | 17.73 | 14.45 |
November | 0.708646E+09 | 1454.30 | 03-NOV-15:40 | 15.37 | 9.43 | 0.318527E+09 | 499.56 | 03-NOV-13:00 | 15.37 | 9.43 |
December | 18557083.78 | 987.97 | 02-DEC-16:03 | 4.95 | 2.78 | 0.292857E+09 | 406.70 | 12-DEC-14:30 | -15.9 | -16.3 |
Annual Sum or Average | 0.204090E+11 | 0.424216E+10 | ||||||||
Minimum of Months | 16484559.38 | 987.97 | -0.1 | -0.9 | 0.272917E+09 | 406.70 | -17.2 | -17.5 | ||
Maximum of Months | 0.416751E+10 | 5816.98 | 31.40 | 24.26 | 0.452274E+09 | 560.41 | 31.40 | 24.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36999032.66 | 817.91 | 13-JAN-07:03 | -1.6 | -2.3 | 0.192820E+09 | 257.81 | 13-JAN-10:00 | 2.20 | 0.51 |
February | 89909555.57 | 1014.44 | 24-FEB-10:15 | 4.80 | 1.70 | 0.176168E+09 | 295.91 | 24-FEB-10:30 | 5.00 | 1.88 |
March | 0.523275E+09 | 1222.28 | 28-MAR-10:00 | 10.00 | 6.30 | 0.220186E+09 | 338.02 | 28-MAR-09:00 | 10.00 | 6.30 |
April | 0.108683E+10 | 4761.31 | 18-APR-09:40 | 24.67 | 19.90 | 0.210338E+09 | 347.88 | 18-APR-09:09 | 24.67 | 19.90 |
May | 0.226464E+10 | 5708.81 | 31-MAY-09:30 | 26.65 | 19.56 | 0.266776E+09 | 347.88 | 09-MAY-09:09 | 26.65 | 19.56 |
June | 0.387497E+10 | 8456.31 | 25-JUN-09:22 | 26.95 | 21.50 | 0.271285E+09 | 348.10 | 26-JUN-09:50 | 28.12 | 22.45 |
July | 0.441331E+10 | 10761.83 | 02-JUL-09:21 | 26.15 | 21.26 | 0.256585E+09 | 348.24 | 05-JUL-09:30 | 23.60 | 20.34 |
August | 0.434373E+10 | 8325.44 | 20-AUG-09:43 | 22.43 | 18.94 | 0.287370E+09 | 361.69 | 04-AUG-07:40 | 22.43 | 18.94 |
September | 0.314125E+10 | 7741.62 | 04-SEP-07:42 | 12.75 | 11.43 | 0.249033E+09 | 347.88 | 06-SEP-09:09 | 23.27 | 17.32 |
October | 0.138182E+10 | 2221.31 | 20-OCT-09:50 | 14.70 | 9.97 | 0.233819E+09 | 347.88 | 20-OCT-09:09 | 14.70 | 9.97 |
November | 0.580819E+09 | 1188.91 | 03-NOV-10:50 | 14.13 | 11.31 | 0.202609E+09 | 323.12 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 48867132.20 | 864.77 | 05-DEC-09:30 | -6.4 | -8.4 | 0.186538E+09 | 265.17 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.217864E+11 | 0.275353E+10 | ||||||||
Minimum of Months | 36999032.66 | 817.91 | -6.4 | -8.4 | 0.176168E+09 | 257.81 | -5.9 | -8.1 | ||
Maximum of Months | 0.441331E+10 | 10761.83 | 26.95 | 21.50 | 0.287370E+09 | 361.69 | 28.12 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56631759.48 | 1091.50 | 13-JAN-14:30 | 3.90 | 1.72 | 0.241993E+09 | 422.68 | 13-JAN-14:39 | 3.90 | 1.72 |
February | 0.123883E+09 | 1438.02 | 25-FEB-15:30 | 5.60 | 2.75 | 0.241551E+09 | 493.38 | 24-FEB-14:00 | 5.60 | 2.75 |
March | 0.384795E+09 | 2200.17 | 24-MAR-14:00 | 13.30 | 6.51 | 0.320656E+09 | 549.49 | 24-MAR-13:39 | 13.30 | 6.51 |
April | 0.104992E+10 | 10226.76 | 18-APR-12:00 | 27.80 | 20.94 | 0.309379E+09 | 549.58 | 18-APR-13:30 | 27.75 | 20.64 |
May | 0.220991E+10 | 10503.05 | 31-MAY-12:00 | 29.40 | 19.85 | 0.379530E+09 | 553.55 | 31-MAY-12:09 | 29.50 | 19.82 |
June | 0.419339E+10 | 11239.38 | 26-JUN-12:00 | 30.60 | 21.63 | 0.411086E+09 | 593.98 | 26-JUN-12:09 | 30.68 | 21.60 |
July | 0.526399E+10 | 12563.23 | 30-JUL-13:52 | 27.20 | 19.41 | 0.399342E+09 | 549.65 | 05-JUL-13:09 | 27.20 | 19.41 |
August | 0.623464E+10 | 11736.73 | 04-AUG-16:10 | 33.15 | 26.05 | 0.448383E+09 | 608.52 | 04-AUG-12:09 | 33.15 | 26.05 |
September | 0.478483E+10 | 13392.10 | 04-SEP-14:22 | 21.95 | 14.29 | 0.375339E+09 | 634.12 | 07-SEP-12:09 | 30.78 | 18.58 |
October | 0.169698E+10 | 8165.47 | 30-OCT-12:06 | 16.13 | 9.73 | 0.351216E+09 | 549.55 | 20-OCT-13:00 | 16.13 | 9.73 |
November | 0.670120E+09 | 6599.79 | 04-NOV-13:30 | 14.15 | 6.81 | 0.298968E+09 | 549.49 | 03-NOV-13:09 | 14.15 | 6.81 |
December | 0.129653E+09 | 1407.72 | 02-DEC-12:40 | 5.40 | 2.84 | 0.256919E+09 | 431.39 | 01-DEC-14:39 | 5.40 | 2.84 |
Annual Sum or Average | 0.267987E+11 | 0.403436E+10 | ||||||||
Minimum of Months | 56631759.48 | 1091.50 | 3.90 | 1.72 | 0.241551E+09 | 422.68 | 3.90 | 1.72 | ||
Maximum of Months | 0.623464E+10 | 13392.10 | 33.15 | 26.05 | 0.448383E+09 | 634.12 | 33.15 | 26.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44744737.42 | 1038.31 | 12-JAN-16:00 | 2.80 | 1.13 | 0.193063E+09 | 279.76 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.118800E+09 | 1326.76 | 24-FEB-16:40 | 7.57 | 5.38 | 0.176901E+09 | 332.82 | 24-FEB-16:49 | 7.38 | 5.26 |
March | 0.482704E+09 | 1312.29 | 23-MAR-16:50 | 16.28 | 9.98 | 0.216140E+09 | 325.43 | 23-MAR-15:00 | 16.28 | 9.98 |
April | 0.123411E+10 | 9257.57 | 16-APR-17:01 | 28.03 | 20.22 | 0.207347E+09 | 347.84 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.215650E+10 | 6388.61 | 21-MAY-18:03 | 16.93 | 9.12 | 0.254151E+09 | 347.85 | 31-MAY-13:09 | 29.90 | 19.66 |
June | 0.369709E+10 | 11530.27 | 25-JUN-18:02 | 30.82 | 21.76 | 0.268926E+09 | 347.86 | 20-JUN-13:00 | 30.82 | 21.76 |
July | 0.434190E+10 | 11852.11 | 02-JUL-17:21 | 28.60 | 21.10 | 0.256159E+09 | 347.85 | 19-JUL-09:09 | 21.28 | 16.97 |
August | 0.442127E+10 | 9416.01 | 05-AUG-17:05 | 25.32 | 17.94 | 0.287094E+09 | 347.87 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.305704E+10 | 11673.57 | 04-SEP-17:42 | 20.87 | 14.10 | 0.243794E+09 | 347.85 | 06-SEP-09:09 | 23.27 | 17.32 |
October | 0.150954E+10 | 4172.66 | 11-OCT-16:00 | 17.80 | 11.96 | 0.226787E+09 | 347.83 | 20-OCT-13:00 | 22.60 | 13.03 |
November | 0.637554E+09 | 2575.98 | 03-NOV-15:40 | 15.37 | 9.43 | 0.202781E+09 | 342.36 | 03-NOV-13:00 | 15.37 | 9.43 |
December | 97051446.24 | 1089.72 | 01-DEC-15:50 | -1.6 | -4.0 | 0.187108E+09 | 289.46 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.217983E+11 | 0.272025E+10 | ||||||||
Minimum of Months | 44744737.42 | 1038.31 | -1.6 | -4.0 | 0.176901E+09 | 279.76 | -1.7 | -4.1 | ||
Maximum of Months | 0.442127E+10 | 11852.11 | 30.82 | 21.76 | 0.287094E+09 | 347.87 | 30.82 | 21.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30467168.73 | 943.37 | 13-JAN-21:03 | -0.1 | -0.9 | 0.302166E+09 | 406.71 | 18-JAN-14:00 | -17.2 | -17.5 |
February | 82106763.89 | 1084.26 | 24-FEB-16:30 | 7.75 | 5.51 | 0.275923E+09 | 422.94 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.656275E+09 | 1409.13 | 28-MAR-15:30 | 16.40 | 10.50 | 0.345384E+09 | 503.77 | 24-MAR-13:00 | 16.40 | 10.50 |
April | 0.151978E+10 | 4878.48 | 18-APR-15:00 | 28.30 | 20.65 | 0.337060E+09 | 549.49 | 18-APR-09:09 | 28.30 | 20.65 |
May | 0.302565E+10 | 5279.12 | 31-MAY-15:00 | 30.00 | 19.70 | 0.422729E+09 | 549.50 | 09-MAY-13:09 | 30.00 | 19.70 |
June | 0.461356E+10 | 9307.17 | 25-JUN-18:31 | 29.97 | 21.56 | 0.431846E+09 | 549.89 | 27-JUN-13:20 | 29.60 | 22.39 |
July | 0.488818E+10 | 7734.22 | 05-JUL-06:03 | 19.60 | 18.69 | 0.404908E+09 | 549.75 | 03-JUL-13:00 | 19.60 | 18.69 |
August | 0.467026E+10 | 5839.68 | 04-AUG-15:30 | 33.90 | 25.83 | 0.453166E+09 | 556.26 | 04-AUG-07:30 | 33.90 | 25.83 |
September | 0.298189E+10 | 5568.15 | 11-SEP-13:40 | 28.70 | 20.26 | 0.384531E+09 | 549.50 | 06-SEP-09:09 | 28.70 | 20.26 |
October | 0.141792E+10 | 1699.56 | 20-OCT-13:30 | 22.20 | 12.82 | 0.347100E+09 | 538.24 | 02-OCT-13:00 | 22.20 | 12.82 |
November | 0.626319E+09 | 1494.95 | 03-NOV-13:30 | 15.85 | 10.76 | 0.318475E+09 | 506.34 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 17992379.19 | 938.24 | 02-DEC-16:03 | 4.95 | 2.78 | 0.293360E+09 | 406.70 | 08-DEC-14:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.245304E+11 | 0.431665E+10 | ||||||||
Minimum of Months | 17992379.19 | 938.24 | -0.1 | -0.9 | 0.275923E+09 | 406.70 | -17.2 | -17.5 | ||
Maximum of Months | 0.488818E+10 | 9307.17 | 33.90 | 25.83 | 0.453166E+09 | 556.26 | 33.90 | 25.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 56758676.48 | 1060.06 | 12-JAN-10:00 | -2.8 | -3.3 | 0.141661E+09 | 260.87 | 12-JAN-09:00 | -2.8 | -3.3 |
February | 0.188958E+09 | 1447.68 | 24-FEB-10:00 | 4.40 | 1.36 | 0.130230E+09 | 325.14 | 24-FEB-09:00 | 4.40 | 1.36 |
March | 0.849779E+09 | 2886.52 | 28-MAR-09:00 | 7.20 | 4.38 | 0.165742E+09 | 338.72 | 28-MAR-10:09 | 10.47 | 6.54 |
April | 0.175337E+10 | 7255.13 | 18-APR-09:00 | 22.80 | 18.62 | 0.160390E+09 | 338.73 | 18-APR-07:10 | 22.80 | 18.62 |
May | 0.328686E+10 | 11335.82 | 29-MAY-09:53 | 23.90 | 18.44 | 0.199229E+09 | 338.94 | 31-MAY-08:00 | 26.10 | 19.69 |
June | 0.468040E+10 | 14314.62 | 25-JUN-08:31 | 25.37 | 20.95 | 0.200409E+09 | 339.61 | 26-JUN-07:40 | 24.43 | 21.77 |
July | 0.498417E+10 | 14225.09 | 04-JUL-08:61 | 22.30 | 19.61 | 0.189937E+09 | 339.21 | 05-JUL-08:00 | 22.80 | 20.41 |
August | 0.460072E+10 | 13133.75 | 27-AUG-09:32 | 23.87 | 19.50 | 0.211386E+09 | 349.57 | 04-AUG-07:30 | 23.87 | 19.50 |
September | 0.327011E+10 | 11382.01 | 03-SEP-08:23 | 16.65 | 12.41 | 0.180450E+09 | 338.74 | 05-SEP-07:00 | 15.60 | 12.97 |
October | 0.145320E+10 | 3184.83 | 20-OCT-08:55 | 12.20 | 8.72 | 0.164121E+09 | 338.72 | 20-OCT-10:09 | 15.68 | 10.42 |
November | 0.566890E+09 | 1493.00 | 04-NOV-09:40 | 8.13 | 4.42 | 0.146288E+09 | 318.35 | 03-NOV-10:00 | 8.13 | 4.42 |
December | 60959992.97 | 1088.95 | 05-DEC-09:50 | -6.2 | -8.3 | 0.137089E+09 | 267.57 | 05-DEC-09:00 | -6.1 | -8.3 |
Annual Sum or Average | 0.257522E+11 | 0.202693E+10 | ||||||||
Minimum of Months | 56758676.48 | 1060.06 | -6.2 | -8.3 | 0.130230E+09 | 260.87 | -6.1 | -8.3 | ||
Maximum of Months | 0.498417E+10 | 14314.62 | 25.37 | 20.95 | 0.211386E+09 | 349.57 | 26.10 | 21.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.654130E+09 | 4544.48 | 12-JAN-12:30 | 1.95 | 0.38 | 0.328456E+09 | 549.49 | 31-JAN-14:09 | -20.0 | -20.5 |
February | 0.955050E+09 | 7245.19 | 24-FEB-13:40 | 7.43 | 4.81 | 0.305658E+09 | 549.50 | 24-FEB-14:09 | 7.88 | 5.25 |
March | 0.180968E+10 | 7656.22 | 24-MAR-13:10 | 12.38 | 6.48 | 0.380349E+09 | 549.50 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.290082E+10 | 11653.66 | 16-APR-13:53 | 27.80 | 20.59 | 0.355124E+09 | 549.84 | 18-APR-13:39 | 27.93 | 20.65 |
May | 0.418533E+10 | 9578.17 | 29-MAY-12:33 | 24.63 | 19.18 | 0.425562E+09 | 550.06 | 30-MAY-13:00 | 26.70 | 19.86 |
June | 0.563047E+10 | 14345.04 | 11-JUN-12:02 | 30.68 | 22.67 | 0.430903E+09 | 549.98 | 30-JUN-13:50 | 29.40 | 21.96 |
July | 0.624772E+10 | 14727.06 | 30-JUL-11:43 | 26.42 | 21.31 | 0.404852E+09 | 550.04 | 05-JUL-13:00 | 26.42 | 21.31 |
August | 0.681172E+10 | 14707.93 | 13-AUG-13:32 | 25.73 | 19.92 | 0.453423E+09 | 550.51 | 21-AUG-13:00 | 29.40 | 21.95 |
September | 0.566547E+10 | 14831.25 | 04-SEP-13:12 | 21.30 | 14.06 | 0.392011E+09 | 567.48 | 07-SEP-13:20 | 31.87 | 18.17 |
October | 0.323839E+10 | 10335.61 | 20-OCT-13:10 | 21.93 | 12.68 | 0.383141E+09 | 549.61 | 20-OCT-13:50 | 22.47 | 12.96 |
November | 0.136804E+10 | 9296.60 | 03-NOV-13:10 | 15.68 | 10.94 | 0.338961E+09 | 549.49 | 21-NOV-14:00 | -6.7 | -8.4 |
December | 0.782142E+09 | 5644.39 | 01-DEC-13:30 | -0.9 | -3.3 | 0.319142E+09 | 549.49 | 14-DEC-14:00 | 1.70 | 0.50 |
Annual Sum or Average | 0.402490E+11 | 0.451758E+10 | ||||||||
Minimum of Months | 0.654130E+09 | 4544.48 | -0.9 | -3.3 | 0.305658E+09 | 549.49 | -20.0 | -20.5 | ||
Maximum of Months | 0.681172E+10 | 14831.25 | 30.68 | 22.67 | 0.453423E+09 | 567.48 | 31.87 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 98108473.24 | 1328.18 | 12-JAN-16:00 | 2.80 | 1.13 | 0.193423E+09 | 298.27 | 12-JAN-16:10 | 2.62 | 1.03 |
February | 0.245118E+09 | 2404.54 | 24-FEB-16:40 | 7.57 | 5.38 | 0.178533E+09 | 339.01 | 24-FEB-16:40 | 7.57 | 5.38 |
March | 0.825469E+09 | 2906.45 | 21-MAR-16:00 | -0.6 | -4.1 | 0.221643E+09 | 338.69 | 24-MAR-15:39 | 11.33 | 5.84 |
April | 0.195226E+10 | 12054.88 | 16-APR-16:32 | 28.50 | 20.39 | 0.214122E+09 | 347.84 | 18-APR-09:09 | 23.27 | 18.95 |
May | 0.318315E+10 | 11555.95 | 14-MAY-16:52 | 21.70 | 15.79 | 0.262204E+09 | 347.85 | 09-MAY-13:09 | 21.70 | 15.79 |
June | 0.456602E+10 | 14373.18 | 25-JUN-18:31 | 29.97 | 21.56 | 0.270360E+09 | 347.86 | 20-JUN-13:00 | 29.97 | 21.56 |
July | 0.494738E+10 | 13965.88 | 04-JUL-16:41 | 27.80 | 21.54 | 0.255626E+09 | 347.85 | 05-JUL-09:20 | 23.33 | 20.37 |
August | 0.474684E+10 | 12687.52 | 05-AUG-17:05 | 25.32 | 17.94 | 0.285510E+09 | 347.86 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.323604E+10 | 11577.76 | 04-SEP-17:12 | 21.67 | 14.30 | 0.238310E+09 | 347.86 | 06-SEP-09:09 | 23.27 | 17.32 |
October | 0.158795E+10 | 4893.78 | 11-OCT-16:00 | 17.80 | 11.96 | 0.220095E+09 | 347.83 | 11-OCT-13:00 | 17.80 | 11.96 |
November | 0.644802E+09 | 3178.87 | 03-NOV-15:30 | 15.55 | 9.47 | 0.200025E+09 | 347.30 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 0.138960E+09 | 1334.17 | 01-DEC-15:50 | -1.6 | -4.0 | 0.187467E+09 | 299.68 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.261721E+11 | 0.272732E+10 | ||||||||
Minimum of Months | 98108473.24 | 1328.18 | -1.6 | -4.1 | 0.178533E+09 | 298.27 | -1.7 | -4.1 | ||
Maximum of Months | 0.494738E+10 | 14373.18 | 29.97 | 21.56 | 0.285510E+09 | 347.86 | 29.97 | 21.56 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472759E+09 | 22590.99 | 02-JAN-05:01 | -4.5 |
February | 66629769.84 | 19297.11 | 06-FEB-06:01 | -15.0 |
March | 4171416.74 | 18228.51 | 07-MAR-07:01 | -5.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 15979904.66 | 19702.99 | 27-NOV-06:02 | -9.4 |
December | 49846725.86 | 19192.24 | 11-DEC-06:02 | -22.1 |
Annual Sum or Average | 0.609387E+09 | |||
Minimum of Months | 0.00 | 0.00 | -22.1 | |
Maximum of Months | 0.472759E+09 | 22590.99 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115146E+11 | 18421.16 | 31-JAN-06:09 | -30.6 |
February | 0.734893E+10 | 19546.89 | 02-FEB-06:10 | -36.7 |
March | 0.397110E+10 | 15819.20 | 06-MAR-06:12 | -13.9 |
April | 0.170510E+10 | 12792.48 | 03-APR-05:13 | -7.2 |
May | 0.365191E+09 | 4571.01 | 30-MAY-05:03 | 14.50 |
June | 0.178228E+09 | 6591.20 | 19-JUN-05:03 | 11.78 |
July | 87579216.99 | 5552.44 | 31-JUL-05:03 | 16.88 |
August | 0.151165E+09 | 4010.71 | 14-AUG-05:03 | 15.68 |
September | 0.618915E+09 | 6751.23 | 30-SEP-05:02 | 0.10 |
October | 0.152323E+10 | 7861.93 | 23-OCT-06:01 | -3.0 |
November | 0.489904E+10 | 16433.63 | 28-NOV-06:12 | -18.1 |
December | 0.896504E+10 | 17058.28 | 11-DEC-06:12 | -22.0 |
Annual Sum or Average | 0.413282E+11 | |||
Minimum of Months | 87579216.99 | 4010.71 | -36.7 | |
Maximum of Months | 0.115146E+11 | 19546.89 | 16.88 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462592E+10 | 10077.44 | 02-JAN-07:11 | -6.1 |
February | 0.295177E+10 | 9283.28 | 06-FEB-07:03 | -15.0 |
March | 0.191041E+10 | 7705.76 | 06-MAR-07:11 | -12.6 |
April | 0.779466E+09 | 6222.43 | 03-APR-06:11 | -7.0 |
May | 0.122337E+09 | 3529.44 | 21-MAY-09:02 | 13.58 |
June | 41841764.87 | 3222.69 | 11-JUN-15:21 | 33.05 |
July | 29801343.68 | 2458.07 | 30-JUL-15:42 | 27.70 |
August | 21915137.40 | 3069.15 | 13-AUG-15:32 | 25.77 |
September | 0.174921E+09 | 3457.51 | 04-SEP-15:13 | 22.20 |
October | 0.896459E+09 | 4825.96 | 29-OCT-13:33 | 13.53 |
November | 0.211437E+10 | 9657.51 | 27-NOV-07:11 | -9.4 |
December | 0.364136E+10 | 9840.24 | 11-DEC-07:04 | -21.7 |
Annual Sum or Average | 0.173106E+11 | |||
Minimum of Months | 21915137.40 | 2458.07 | -21.7 | |
Maximum of Months | 0.462592E+10 | 10077.44 | 33.05 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330153E+10 | 8850.82 | 02-JAN-07:01 | -5.9 |
February | 0.209579E+10 | 6240.70 | 06-FEB-07:01 | -15.0 |
March | 0.139904E+10 | 4072.28 | 06-MAR-07:01 | -12.7 |
April | 0.528085E+09 | 4301.50 | 20-APR-05:02 | 2.62 |
May | 45905245.12 | 3911.91 | 08-MAY-05:03 | 12.02 |
June | 18891735.22 | 4293.27 | 02-JUN-05:03 | 7.20 |
July | 26081026.54 | 3311.70 | 10-JUL-04:03 | 17.20 |
August | 26009515.63 | 3254.13 | 19-AUG-05:03 | 15.68 |
September | 63238930.71 | 5133.31 | 25-SEP-05:02 | 2.80 |
October | 0.411020E+09 | 3456.94 | 17-OCT-07:07 | 2.85 |
November | 0.143605E+10 | 5902.86 | 27-NOV-07:01 | -9.4 |
December | 0.252762E+10 | 6023.01 | 11-DEC-07:01 | -21.7 |
Annual Sum or Average | 0.118793E+11 | |||
Minimum of Months | 18891735.22 | 3254.13 | -21.7 | |
Maximum of Months | 0.330153E+10 | 8850.82 | 17.20 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251595E+10 | 26230.32 | 02-JAN-05:01 | -4.5 |
February | 0.101395E+10 | 25064.43 | 06-FEB-05:01 | -14.5 |
March | 0.228150E+09 | 23563.10 | 06-MAR-06:01 | -14.1 |
April | 51223778.12 | 22627.26 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 578829.60 | 9647.16 | 16-OCT-06:01 | -0.4 |
November | 0.544337E+09 | 25065.40 | 27-NOV-05:01 | -9.4 |
December | 0.124359E+10 | 25065.09 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.559778E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.251595E+10 | 26230.32 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.728239E+10 | 30431.57 | 23-JAN-05:11 | -18.0 |
February | 0.404429E+10 | 30139.73 | 06-FEB-05:01 | -14.5 |
March | 0.157811E+10 | 29941.08 | 06-MAR-05:01 | -15.4 |
April | 0.379584E+09 | 28980.04 | 03-APR-04:11 | -6.9 |
May | 1111326.54 | 16669.90 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 10594646.28 | 24509.29 | 29-SEP-06:01 | 0.10 |
October | 0.140569E+09 | 25968.45 | 16-OCT-05:01 | 0.48 |
November | 0.241096E+10 | 30120.83 | 27-NOV-05:01 | -9.4 |
December | 0.500485E+10 | 30672.93 | 11-DEC-00:02 | -21.7 |
Annual Sum or Average | 0.208525E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.7 | |
Maximum of Months | 0.728239E+10 | 30672.93 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.983737E+10 | 10831.84 | 29-JAN-19:32 | -23.7 |
February | 0.603755E+10 | 10797.85 | 02-FEB-03:12 | -35.0 |
March | 0.285710E+10 | 10497.36 | 06-MAR-04:52 | -15.6 |
April | 0.815030E+09 | 10011.07 | 03-APR-04:11 | -6.9 |
May | 18349260.59 | 8176.92 | 02-MAY-05:03 | 2.20 |
June | 279371.65 | 851.78 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 88424132.74 | 8830.12 | 30-SEP-05:01 | 0.10 |
October | 0.584673E+09 | 8966.85 | 28-OCT-05:01 | -1.7 |
November | 0.364704E+10 | 10550.49 | 26-NOV-01:32 | -24.4 |
December | 0.749263E+10 | 10796.15 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.313784E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.983737E+10 | 10831.84 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.591106E+10 | 12084.57 | 29-JAN-19:32 | -23.7 |
February | 0.337853E+10 | 12098.82 | 02-FEB-03:12 | -35.0 |
March | 0.148183E+10 | 11706.21 | 06-MAR-04:52 | -15.6 |
April | 0.430895E+09 | 11285.19 | 03-APR-04:11 | -6.9 |
May | 4353435.26 | 8956.78 | 02-MAY-06:01 | 2.30 |
June | 614488.84 | 1186.25 | 05-JUN-06:03 | 8.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 41860823.65 | 9908.45 | 30-SEP-05:01 | 0.10 |
October | 0.288114E+09 | 10045.72 | 28-OCT-05:01 | -1.7 |
November | 0.218198E+10 | 11772.65 | 26-NOV-01:32 | -24.4 |
December | 0.455634E+10 | 12079.06 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.182756E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.591106E+10 | 12098.82 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.681954E+10 | 14810.23 | 29-JAN-07:32 | -22.6 |
February | 0.383537E+10 | 14744.82 | 02-FEB-03:12 | -35.0 |
March | 0.205249E+10 | 14380.04 | 06-MAR-04:52 | -15.6 |
April | 0.667464E+09 | 13889.66 | 03-APR-04:11 | -6.9 |
May | 19125548.17 | 11075.03 | 02-MAY-06:01 | 2.30 |
June | 844154.60 | 2954.91 | 03-JUN-06:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 65486353.58 | 12158.44 | 30-SEP-05:01 | 0.10 |
October | 0.372961E+09 | 12328.00 | 23-OCT-05:01 | -2.7 |
November | 0.257464E+10 | 14509.80 | 27-NOV-00:52 | -11.7 |
December | 0.561774E+10 | 14799.19 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.220257E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.681954E+10 | 14810.23 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.609618E+10 | 13188.91 | 19-JAN-04:42 | -27.0 |
February | 0.357324E+10 | 13256.45 | 02-FEB-03:12 | -35.0 |
March | 0.167568E+10 | 12754.87 | 06-MAR-04:52 | -15.6 |
April | 0.471212E+09 | 12369.18 | 03-APR-04:11 | -6.9 |
May | 14952865.20 | 9832.62 | 02-MAY-06:01 | 2.30 |
June | 1671900.98 | 2978.58 | 03-JUN-06:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 63078169.94 | 10935.45 | 30-SEP-05:01 | 0.10 |
October | 0.348466E+09 | 10974.48 | 23-OCT-05:01 | -2.7 |
November | 0.225122E+10 | 12873.31 | 26-NOV-01:32 | -24.4 |
December | 0.467810E+10 | 13226.90 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.191738E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.0 | |
Maximum of Months | 0.609618E+10 | 13256.45 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.689062E+10 | 7767.11 | 29-JAN-19:32 | -23.7 |
February | 0.443972E+10 | 7625.73 | 04-FEB-04:42 | -30.7 |
March | 0.218625E+10 | 7340.28 | 06-MAR-05:01 | -15.4 |
April | 0.633449E+09 | 7198.19 | 03-APR-04:01 | -6.8 |
May | 9995085.04 | 6022.29 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 2634465.36 | 5892.21 | 29-SEP-06:01 | 0.10 |
October | 35360324.09 | 6033.63 | 16-OCT-06:01 | -0.4 |
November | 0.157919E+10 | 7493.39 | 27-NOV-00:52 | -11.7 |
December | 0.431172E+10 | 7702.85 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.200889E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.7 | |
Maximum of Months | 0.689062E+10 | 7767.11 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414334E+10 | 9279.67 | 29-JAN-19:32 | -23.7 |
February | 0.237470E+10 | 9191.24 | 02-FEB-05:01 | -36.2 |
March | 0.101139E+10 | 8880.81 | 06-MAR-05:01 | -15.4 |
April | 0.273825E+09 | 8726.87 | 03-APR-04:01 | -6.8 |
May | 514193.81 | 7221.18 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 920708.65 | 5472.80 | 29-SEP-06:01 | 0.10 |
October | 12862892.95 | 7316.84 | 27-OCT-06:01 | 0.25 |
November | 0.895004E+09 | 8843.96 | 27-NOV-05:01 | -9.4 |
December | 0.257682E+10 | 9270.45 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.112894E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.2 | |
Maximum of Months | 0.414334E+10 | 9279.67 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116907E+11 | 18672.47 | 31-JAN-07:10 | -30.5 |
February | 0.803962E+10 | 19393.30 | 02-FEB-07:10 | -36.7 |
March | 0.636866E+10 | 14038.36 | 06-MAR-07:10 | -12.7 |
April | 0.322313E+10 | 13011.10 | 03-APR-06:50 | -6.8 |
May | 0.101232E+10 | 10794.03 | 02-MAY-06:10 | 2.30 |
June | 0.395006E+09 | 9363.13 | 02-JUN-06:10 | 7.30 |
July | 32834369.89 | 8244.41 | 24-JUL-06:05 | 12.35 |
August | 0.131055E+09 | 8831.77 | 07-AUG-06:08 | 8.87 |
September | 0.716976E+09 | 10918.79 | 29-SEP-06:10 | 0.10 |
October | 0.177770E+10 | 11369.53 | 23-OCT-06:10 | -3.0 |
November | 0.497946E+10 | 15308.70 | 28-NOV-07:10 | -17.6 |
December | 0.891042E+10 | 16375.81 | 11-DEC-07:10 | -21.7 |
Annual Sum or Average | 0.472779E+11 | |||
Minimum of Months | 32834369.89 | 8244.41 | -36.7 | |
Maximum of Months | 0.116907E+11 | 19393.30 | 12.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.427430E+10 | 9792.05 | 30-JAN-04:52 | -27.8 |
February | 0.244953E+10 | 9802.48 | 02-FEB-05:01 | -36.2 |
March | 0.114360E+10 | 9461.61 | 06-MAR-05:01 | -15.4 |
April | 0.257159E+09 | 9348.37 | 03-APR-04:01 | -6.8 |
May | 4281412.92 | 7782.79 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 2914775.31 | 7710.76 | 29-SEP-06:01 | 0.10 |
October | 14512159.24 | 7810.42 | 16-OCT-06:01 | -0.4 |
November | 0.935552E+09 | 9426.21 | 27-NOV-05:01 | -9.4 |
December | 0.264154E+10 | 9912.78 | 11-DEC-01:22 | -21.7 |
Annual Sum or Average | 0.117234E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.2 | |
Maximum of Months | 0.427430E+10 | 9912.78 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.640950E+10 | 8411.23 | 30-JAN-04:41 | -27.7 |
February | 0.364205E+10 | 8445.66 | 02-FEB-04:53 | -36.1 |
March | 0.134359E+10 | 8271.53 | 06-MAR-04:52 | -15.6 |
April | 0.275528E+09 | 7894.26 | 03-APR-04:01 | -6.8 |
May | 966261.42 | 6455.28 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 8266808.80 | 6564.65 | 29-SEP-06:01 | 0.10 |
October | 81290683.88 | 6808.74 | 16-OCT-05:01 | 0.48 |
November | 0.189468E+10 | 8188.54 | 26-NOV-04:42 | -25.0 |
December | 0.444830E+10 | 8365.94 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.181042E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.640950E+10 | 8445.66 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380400E+10 | 11192.09 | 30-JAN-04:41 | -27.7 |
February | 0.198748E+10 | 11101.83 | 02-FEB-04:12 | -35.4 |
March | 0.703856E+09 | 10648.54 | 13-MAR-04:01 | -9.4 |
April | 0.151248E+09 | 10526.26 | 03-APR-04:01 | -6.8 |
May | 492188.10 | 7382.82 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 4952763.07 | 8775.70 | 29-SEP-06:01 | 0.10 |
October | 48653991.32 | 8798.05 | 16-OCT-06:01 | -0.4 |
November | 0.114032E+10 | 10705.32 | 24-NOV-05:01 | -14.7 |
December | 0.272762E+10 | 11201.64 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.105686E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.380400E+10 | 11201.64 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.396724E+10 | 12682.06 | 30-JAN-04:41 | -27.7 |
February | 0.196852E+10 | 12591.97 | 02-FEB-04:53 | -36.1 |
March | 0.876594E+09 | 12125.05 | 06-MAR-05:01 | -15.4 |
April | 0.206109E+09 | 11943.94 | 03-APR-04:01 | -6.8 |
May | 1397710.96 | 9832.22 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 6265520.75 | 9998.64 | 29-SEP-06:01 | 0.10 |
October | 50238119.73 | 10024.69 | 16-OCT-06:01 | -0.4 |
November | 0.119376E+10 | 12198.15 | 24-NOV-05:01 | -14.7 |
December | 0.312484E+10 | 12686.25 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.113950E+11 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.396724E+10 | 12686.25 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388252E+10 | 11474.36 | 30-JAN-04:41 | -27.7 |
February | 0.207099E+10 | 11415.30 | 02-FEB-04:12 | -35.4 |
March | 0.765232E+09 | 10902.35 | 13-MAR-04:01 | -9.4 |
April | 0.148664E+09 | 10796.71 | 03-APR-04:01 | -6.8 |
May | 1797538.12 | 8893.51 | 02-MAY-06:01 | 2.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 8028223.53 | 8945.92 | 29-SEP-06:01 | 0.10 |
October | 55278348.98 | 8972.39 | 16-OCT-06:01 | -0.4 |
November | 0.115788E+10 | 10961.25 | 25-NOV-05:01 | -15.3 |
December | 0.275391E+10 | 11462.81 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.108443E+11 | |||
Minimum of Months | 0.00 | 0.00 | -35.4 | |
Maximum of Months | 0.388252E+10 | 11474.36 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.198672E+11 | 18185.19 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.179823E+11 | 18185.19 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.207117E+11 | 18185.19 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.191625E+11 | 18185.19 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.202894E+11 | 18185.19 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.199404E+11 | 18185.19 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.195094E+11 | 18185.19 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.207117E+11 | 18185.19 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.191582E+11 | 18185.19 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.198694E+11 | 18185.19 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.194582E+11 | 18185.19 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.195072E+11 | 18185.19 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.236167E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.179823E+11 | 18185.19 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.207117E+11 | 18185.19 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.403280E+10 | 4220.20 | 02-JAN-08:09 | 0.971303E+10 | 6808.32 | 02-JAN-08:09 |
February | 0.365805E+10 | 4220.20 | 01-FEB-08:09 | 0.879311E+10 | 6808.32 | 01-FEB-08:09 |
March | 0.434679E+10 | 4220.20 | 01-MAR-08:09 | 0.101015E+11 | 6808.32 | 01-MAR-08:09 |
April | 0.388256E+10 | 4220.20 | 03-APR-07:10 | 0.937947E+10 | 6808.32 | 03-APR-07:10 |
May | 0.418979E+10 | 4220.20 | 01-MAY-07:10 | 0.990724E+10 | 6808.32 | 01-MAY-07:10 |
June | 0.416954E+10 | 4220.20 | 01-JUN-07:10 | 0.972788E+10 | 6808.32 | 01-JUN-07:10 |
July | 0.390282E+10 | 4220.20 | 03-JUL-07:10 | 0.955663E+10 | 6808.32 | 03-JUL-07:10 |
August | 0.434679E+10 | 4220.20 | 01-AUG-07:10 | 0.101015E+11 | 6808.32 | 01-AUG-07:10 |
September | 0.388256E+10 | 4220.20 | 01-SEP-07:10 | 0.937507E+10 | 6808.32 | 01-SEP-07:10 |
October | 0.403280E+10 | 4220.20 | 02-OCT-07:10 | 0.971523E+10 | 6808.32 | 02-OCT-07:10 |
November | 0.398554E+10 | 4220.20 | 01-NOV-07:10 | 0.950025E+10 | 6808.32 | 01-NOV-07:10 |
December | 0.390282E+10 | 4220.20 | 01-DEC-08:09 | 0.955443E+10 | 6808.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.483329E+11 | 0.115425E+12 | ||||
Minimum of Months | 0.365805E+10 | 4220.20 | 0.879311E+10 | 6808.32 | ||
Maximum of Months | 0.434679E+10 | 4220.20 | 0.101015E+11 | 6808.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.574566E+09 | 889.66 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.483561E+09 | 761.39 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.524900E+09 | 648.81 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.455513E+09 | 597.13 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.470359E+09 | 452.38 | 09-MAY-15:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.463983E+09 | 487.28 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.438033E+09 | 487.79 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.491937E+09 | 470.08 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.463020E+09 | 600.74 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.509128E+09 | 860.21 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.556701E+09 | 889.66 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.591542E+09 | 889.66 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.602324E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.438033E+09 | 452.38 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.591542E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.354472E+09 | 563.23 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.300451E+09 | 488.42 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330918E+09 | 421.34 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287648E+09 | 312.64 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.300189E+09 | 299.79 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.295776E+09 | 300.18 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.278826E+09 | 300.63 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.313092E+09 | 268.66 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.292810E+09 | 313.02 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.316975E+09 | 511.14 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.346277E+09 | 563.23 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.361621E+09 | 563.23 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.377905E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.278826E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.361621E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.545832E+09 | 889.66 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.463299E+09 | 736.07 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.519470E+09 | 610.08 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.454783E+09 | 591.16 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.473927E+09 | 444.39 | 09-MAY-15:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.468015E+09 | 489.56 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.440989E+09 | 490.22 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.494622E+09 | 463.17 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.460294E+09 | 582.88 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.494213E+09 | 815.54 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.535049E+09 | 889.66 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.552560E+09 | 889.66 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.590305E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.440989E+09 | 444.39 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.552560E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.353264E+09 | 563.19 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.298432E+09 | 455.51 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330734E+09 | 412.33 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287809E+09 | 397.32 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.298380E+09 | 294.14 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.294339E+09 | 312.89 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.278166E+09 | 313.86 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.311923E+09 | 306.70 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.291444E+09 | 403.08 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.319087E+09 | 545.91 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.343613E+09 | 563.19 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.359692E+09 | 563.19 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.376688E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.278166E+09 | 294.14 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.359692E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.571441E+09 | 889.66 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.480970E+09 | 753.73 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.523579E+09 | 637.84 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.454429E+09 | 583.88 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.469872E+09 | 447.51 | 09-MAY-15:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.463533E+09 | 484.11 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.437664E+09 | 484.65 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.491442E+09 | 466.03 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.461707E+09 | 587.54 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.507062E+09 | 858.65 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.553999E+09 | 889.66 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.587026E+09 | 889.66 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.600272E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.437664E+09 | 447.51 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.587026E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.353275E+09 | 563.23 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.299512E+09 | 484.56 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330315E+09 | 416.24 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287185E+09 | 310.92 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.299825E+09 | 298.00 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.295412E+09 | 297.90 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.278532E+09 | 298.49 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.312757E+09 | 268.66 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.292296E+09 | 311.44 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.316210E+09 | 507.92 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.345215E+09 | 563.23 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.359920E+09 | 563.23 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.377045E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.278532E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.359920E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.543815E+09 | 889.66 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.462065E+09 | 728.85 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.518702E+09 | 596.81 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.453920E+09 | 577.59 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.473293E+09 | 424.37 | 01-MAY-07:10 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.467349E+09 | 486.54 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.440449E+09 | 487.23 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.494026E+09 | 458.70 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.459563E+09 | 568.69 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.493408E+09 | 811.33 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.533651E+09 | 889.66 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.550176E+09 | 889.66 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.589042E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.440449E+09 | 424.37 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.550176E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.351956E+09 | 563.19 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.297576E+09 | 451.22 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330056E+09 | 404.91 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287188E+09 | 391.44 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.298050E+09 | 291.77 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.294021E+09 | 311.30 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.277884E+09 | 312.32 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.311538E+09 | 304.87 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.290901E+09 | 397.38 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.318204E+09 | 545.16 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.342568E+09 | 563.19 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.358059E+09 | 563.19 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.375800E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.277884E+09 | 291.77 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.358059E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.574563E+09 | 889.66 | 02-JAN-16:40 | 0.204758E+10 | 1435.25 | 02-JAN-08:09 |
February | 0.483560E+09 | 761.39 | 01-FEB-16:00 | 0.185366E+10 | 1435.25 | 01-FEB-08:09 |
March | 0.524899E+09 | 648.79 | 01-MAR-16:00 | 0.212947E+10 | 1435.25 | 01-MAR-08:09 |
April | 0.455511E+09 | 597.11 | 10-APR-07:10 | 0.197726E+10 | 1435.25 | 03-APR-07:10 |
May | 0.470358E+09 | 452.37 | 09-MAY-15:30 | 0.208852E+10 | 1435.25 | 01-MAY-07:10 |
June | 0.463982E+09 | 487.27 | 13-JUN-07:10 | 0.205071E+10 | 1435.25 | 01-JUN-07:10 |
July | 0.438033E+09 | 487.79 | 20-JUL-07:10 | 0.201461E+10 | 1435.25 | 03-JUL-07:10 |
August | 0.491936E+09 | 470.07 | 31-AUG-07:10 | 0.212947E+10 | 1435.25 | 01-AUG-07:10 |
September | 0.463019E+09 | 600.72 | 21-SEP-07:10 | 0.197634E+10 | 1435.25 | 01-SEP-07:10 |
October | 0.509127E+09 | 860.21 | 31-OCT-07:10 | 0.204804E+10 | 1435.25 | 02-OCT-07:10 |
November | 0.556698E+09 | 889.66 | 06-NOV-16:00 | 0.200273E+10 | 1435.25 | 01-NOV-07:10 |
December | 0.591538E+09 | 889.66 | 01-DEC-16:30 | 0.201415E+10 | 1435.25 | 01-DEC-08:09 |
Annual Sum or Average | 0.602323E+10 | 0.243325E+11 | ||||
Minimum of Months | 0.438033E+09 | 452.37 | 0.185366E+10 | 1435.25 | ||
Maximum of Months | 0.591538E+09 | 889.66 | 0.212947E+10 | 1435.25 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.354471E+09 | 563.23 | 02-JAN-16:40 | 0.129621E+10 | 908.57 | 02-JAN-08:09 |
February | 0.300451E+09 | 488.42 | 01-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330917E+09 | 421.33 | 01-MAR-16:00 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287648E+09 | 312.64 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.300188E+09 | 299.79 | 24-MAY-15:00 | 0.132213E+10 | 908.57 | 01-MAY-07:10 |
June | 0.295776E+09 | 300.17 | 13-JUN-07:10 | 0.129819E+10 | 908.57 | 01-JUN-07:10 |
July | 0.278826E+09 | 300.63 | 31-JUL-15:00 | 0.127534E+10 | 908.57 | 03-JUL-07:10 |
August | 0.313092E+09 | 268.66 | 01-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.292809E+09 | 313.02 | 29-SEP-15:00 | 0.125111E+10 | 908.57 | 01-SEP-07:10 |
October | 0.316974E+09 | 511.14 | 31-OCT-07:10 | 0.129650E+10 | 908.57 | 02-OCT-07:10 |
November | 0.346276E+09 | 563.23 | 06-NOV-16:00 | 0.126781E+10 | 908.57 | 01-NOV-07:10 |
December | 0.361620E+09 | 563.23 | 01-DEC-16:30 | 0.127504E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.377905E+10 | 0.154036E+11 | ||||
Minimum of Months | 0.278826E+09 | 268.66 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.361620E+09 | 563.23 | 0.134804E+10 | 908.57 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.545831E+09 | 889.66 | 02-JAN-16:40 | 0.204757E+10 | 1435.24 | 02-JAN-08:09 |
February | 0.463298E+09 | 736.06 | 14-FEB-16:00 | 0.185364E+10 | 1435.24 | 01-FEB-08:09 |
March | 0.519469E+09 | 610.06 | 01-MAR-16:00 | 0.212945E+10 | 1435.24 | 01-MAR-08:09 |
April | 0.454780E+09 | 591.14 | 10-APR-07:10 | 0.197725E+10 | 1435.24 | 03-APR-07:10 |
May | 0.473927E+09 | 444.38 | 09-MAY-15:30 | 0.208851E+10 | 1435.24 | 01-MAY-07:10 |
June | 0.468014E+09 | 489.56 | 13-JUN-07:10 | 0.205070E+10 | 1435.24 | 01-JUN-07:10 |
July | 0.440989E+09 | 490.22 | 20-JUL-07:10 | 0.201460E+10 | 1435.24 | 03-JUL-07:10 |
August | 0.494622E+09 | 463.16 | 31-AUG-07:10 | 0.212945E+10 | 1435.24 | 01-AUG-07:10 |
September | 0.460293E+09 | 582.86 | 21-SEP-07:10 | 0.197632E+10 | 1435.24 | 01-SEP-07:10 |
October | 0.494212E+09 | 815.54 | 31-OCT-07:10 | 0.204803E+10 | 1435.24 | 02-OCT-07:10 |
November | 0.535048E+09 | 889.66 | 06-NOV-16:00 | 0.200271E+10 | 1435.24 | 01-NOV-07:10 |
December | 0.552559E+09 | 889.66 | 01-DEC-16:30 | 0.201413E+10 | 1435.24 | 01-DEC-08:09 |
Annual Sum or Average | 0.590304E+10 | 0.243324E+11 | ||||
Minimum of Months | 0.440989E+09 | 444.38 | 0.185364E+10 | 1435.24 | ||
Maximum of Months | 0.552559E+09 | 889.66 | 0.212945E+10 | 1435.24 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.353263E+09 | 563.19 | 02-JAN-16:40 | 0.129620E+10 | 908.57 | 02-JAN-08:09 |
February | 0.298431E+09 | 455.50 | 14-FEB-16:00 | 0.117344E+10 | 908.57 | 01-FEB-08:09 |
March | 0.330733E+09 | 412.34 | 14-MAR-07:10 | 0.134804E+10 | 908.57 | 01-MAR-08:09 |
April | 0.287808E+09 | 397.31 | 10-APR-07:10 | 0.125169E+10 | 908.57 | 03-APR-07:10 |
May | 0.298380E+09 | 294.14 | 25-MAY-07:10 | 0.132212E+10 | 908.57 | 01-MAY-07:10 |
June | 0.294339E+09 | 312.88 | 13-JUN-07:10 | 0.129818E+10 | 908.57 | 01-JUN-07:10 |
July | 0.278166E+09 | 313.85 | 20-JUL-07:10 | 0.127533E+10 | 908.57 | 03-JUL-07:10 |
August | 0.311923E+09 | 306.69 | 31-AUG-07:10 | 0.134804E+10 | 908.57 | 01-AUG-07:10 |
September | 0.291444E+09 | 403.06 | 21-SEP-07:10 | 0.125110E+10 | 908.57 | 01-SEP-07:10 |
October | 0.319086E+09 | 545.91 | 31-OCT-07:10 | 0.129649E+10 | 908.57 | 02-OCT-07:10 |
November | 0.343612E+09 | 563.19 | 06-NOV-16:00 | 0.126780E+10 | 908.57 | 01-NOV-07:10 |
December | 0.359691E+09 | 563.19 | 01-DEC-16:30 | 0.127503E+10 | 908.57 | 01-DEC-08:09 |
Annual Sum or Average | 0.376688E+10 | 0.154035E+11 | ||||
Minimum of Months | 0.278166E+09 | 294.14 | 0.117344E+10 | 908.57 | ||
Maximum of Months | 0.359691E+09 | 563.19 | 0.134804E+10 | 908.57 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.198672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.191625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.202894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.199404E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.195094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.191582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.198694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.194582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.195072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.236167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.179823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.207117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.403280E+10 | 0.971303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.388256E+10 | 0.937947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.418979E+10 | 0.990724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.416954E+10 | 0.972788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.390282E+10 | 0.955663E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.388256E+10 | 0.937507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.403280E+10 | 0.971523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.398554E+10 | 0.950025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.390282E+10 | 0.955443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.483329E+11 | 0.115425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.427861E+10 | 0.365805E+10 | 0.879311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.434679E+10 | 0.101015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.574566E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114597E+10 |
February | 0.901968E+09 | 0.483561E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837564E+09 |
March | 0.107774E+10 | 0.524900E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717579E+09 |
April | 0.956342E+09 | 0.455513E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4530694.90 | 0.447199E+09 |
May | 0.103597E+10 | 0.470359E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1409894.56 | 0.255253E+09 |
June | 0.103308E+10 | 0.463983E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18869444.99 | 0.150595E+09 |
July | 0.959235E+09 | 0.438033E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6447057.34 | 0.110362E+09 |
August | 0.107774E+10 | 0.491937E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7115535.32 | 0.148697E+09 |
September | 0.956342E+09 | 0.463020E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5995667.58 | 0.227401E+09 |
October | 0.994195E+09 | 0.509128E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419972E+09 |
November | 0.984487E+09 | 0.556701E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709000E+09 |
December | 0.959235E+09 | 0.591542E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957977E+09 |
Annual Sum or Average | 0.119305E+11 | 0.602324E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 44368294.69 | 0.612757E+10 |
Minimum of Months | 0.901968E+09 | 0.438033E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110362E+09 |
Maximum of Months | 0.107774E+10 | 0.591542E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18869444.99 | 0.114597E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.354472E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765594E+09 |
February | 0.571020E+09 | 0.300451E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.560749E+09 |
March | 0.682301E+09 | 0.330918E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483613E+09 |
April | 0.605444E+09 | 0.287648E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2968926.92 | 0.306894E+09 |
May | 0.655854E+09 | 0.300189E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939804.20 | 0.174785E+09 |
June | 0.654023E+09 | 0.295776E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12400961.12 | 0.101536E+09 |
July | 0.607275E+09 | 0.278826E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4095973.78 | 74846829.59 |
August | 0.682301E+09 | 0.313092E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4690433.68 | 0.100173E+09 |
September | 0.605444E+09 | 0.292810E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3643146.41 | 0.156887E+09 |
October | 0.629407E+09 | 0.316975E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288774E+09 |
November | 0.623262E+09 | 0.346277E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475082E+09 |
December | 0.607275E+09 | 0.361621E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640868E+09 |
Annual Sum or Average | 0.755301E+10 | 0.377905E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28739246.12 | 0.412980E+10 |
Minimum of Months | 0.571020E+09 | 0.278826E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74846829.59 |
Maximum of Months | 0.682301E+09 | 0.361621E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12400961.12 | 0.765594E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.545832E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115997E+10 |
February | 0.901968E+09 | 0.463299E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858609E+09 |
March | 0.107774E+10 | 0.519470E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745538E+09 |
April | 0.956342E+09 | 0.454783E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3369470.15 | 0.469373E+09 |
May | 0.103597E+10 | 0.473927E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1409835.64 | 0.262057E+09 |
June | 0.103308E+10 | 0.468015E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18291435.50 | 0.150643E+09 |
July | 0.959235E+09 | 0.440989E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5962770.22 | 0.111471E+09 |
August | 0.107774E+10 | 0.494622E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6756123.30 | 0.154551E+09 |
September | 0.956342E+09 | 0.460294E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4374880.13 | 0.244254E+09 |
October | 0.994195E+09 | 0.494213E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459691E+09 |
November | 0.984487E+09 | 0.535049E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730942E+09 |
December | 0.959235E+09 | 0.552560E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980548E+09 |
Annual Sum or Average | 0.119305E+11 | 0.590305E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40164514.94 | 0.632765E+10 |
Minimum of Months | 0.901968E+09 | 0.440989E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111471E+09 |
Maximum of Months | 0.107774E+10 | 0.552560E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18291435.50 | 0.115997E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.353264E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766044E+09 |
February | 0.570983E+09 | 0.298432E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563327E+09 |
March | 0.682256E+09 | 0.330734E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485040E+09 |
April | 0.605404E+09 | 0.287809E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2235693.91 | 0.310922E+09 |
May | 0.655811E+09 | 0.298380E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 946426.70 | 0.174724E+09 |
June | 0.653980E+09 | 0.294339E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12366354.59 | 0.102096E+09 |
July | 0.607235E+09 | 0.278166E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4179491.97 | 77280287.63 |
August | 0.682256E+09 | 0.311923E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4707292.63 | 0.103547E+09 |
September | 0.605404E+09 | 0.291444E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3433692.89 | 0.157852E+09 |
October | 0.629366E+09 | 0.319087E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287823E+09 |
November | 0.623221E+09 | 0.343613E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475507E+09 |
December | 0.607235E+09 | 0.359692E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641085E+09 |
Annual Sum or Average | 0.755252E+10 | 0.376688E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27868952.69 | 0.414525E+10 |
Minimum of Months | 0.570983E+09 | 0.278166E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77280287.63 |
Maximum of Months | 0.682256E+09 | 0.359692E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12366354.59 | 0.766044E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.571441E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616580E+09 |
February | 0.901968E+09 | 0.480970E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457061E+09 |
March | 0.107774E+10 | 0.523579E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388648E+09 |
April | 0.956342E+09 | 0.454429E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4343442.90 | 0.236229E+09 |
May | 0.103597E+10 | 0.469872E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 856277.93 | 0.129517E+09 |
June | 0.103308E+10 | 0.463533E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12677018.37 | 78119619.16 |
July | 0.959235E+09 | 0.437664E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4404760.13 | 56813307.69 |
August | 0.107774E+10 | 0.491442E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4079072.70 | 80255600.30 |
September | 0.956342E+09 | 0.461707E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3763457.95 | 0.129773E+09 |
October | 0.994195E+09 | 0.507062E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250415E+09 |
November | 0.984487E+09 | 0.553999E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405207E+09 |
December | 0.959235E+09 | 0.587026E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527392E+09 |
Annual Sum or Average | 0.119305E+11 | 0.600272E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30124029.97 | 0.335601E+10 |
Minimum of Months | 0.901968E+09 | 0.437664E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56813307.69 |
Maximum of Months | 0.107774E+10 | 0.587026E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12677018.37 | 0.616580E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.353275E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412527E+09 |
February | 0.571020E+09 | 0.299512E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306908E+09 |
March | 0.682301E+09 | 0.330315E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263533E+09 |
April | 0.605444E+09 | 0.287185E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2324595.28 | 0.164687E+09 |
May | 0.655854E+09 | 0.299825E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 512742.96 | 93636159.51 |
June | 0.654023E+09 | 0.295412E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7162648.79 | 54968109.81 |
July | 0.607275E+09 | 0.278532E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2342108.24 | 40711558.98 |
August | 0.682301E+09 | 0.312757E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2566970.39 | 56085412.66 |
September | 0.605444E+09 | 0.292296E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1931654.64 | 91942465.94 |
October | 0.629407E+09 | 0.316210E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174712E+09 |
November | 0.623262E+09 | 0.345215E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272008E+09 |
December | 0.607275E+09 | 0.359920E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352932E+09 |
Annual Sum or Average | 0.755301E+10 | 0.377045E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16840720.32 | 0.228465E+10 |
Minimum of Months | 0.571020E+09 | 0.278532E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40711558.98 |
Maximum of Months | 0.682301E+09 | 0.359920E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7162648.79 | 0.412527E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.543815E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128041E+11 |
February | 0.901968E+09 | 0.462065E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.975458E+10 |
March | 0.107774E+10 | 0.518702E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851734E+10 |
April | 0.956342E+09 | 0.453920E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32577670.17 | 0.529688E+10 |
May | 0.103597E+10 | 0.473293E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105222E+09 | 0.296372E+10 |
June | 0.103308E+10 | 0.467349E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395056E+09 | 0.162722E+10 |
July | 0.959235E+09 | 0.440449E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358497E+09 | 0.751713E+09 |
August | 0.107774E+10 | 0.494026E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494952E+09 | 0.116074E+10 |
September | 0.956342E+09 | 0.459563E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251492E+09 | 0.270711E+10 |
October | 0.994195E+09 | 0.493408E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531900E+10 |
November | 0.984487E+09 | 0.533651E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738409E+10 |
December | 0.959235E+09 | 0.550176E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102067E+11 |
Annual Sum or Average | 0.119305E+11 | 0.589042E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163780E+10 | 0.684932E+11 |
Minimum of Months | 0.901968E+09 | 0.440449E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751713E+09 |
Maximum of Months | 0.107774E+10 | 0.550176E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494952E+09 | 0.128041E+11 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.351956E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412599E+09 |
February | 0.570983E+09 | 0.297576E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308052E+09 |
March | 0.682256E+09 | 0.330056E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264050E+09 |
April | 0.605404E+09 | 0.287188E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1479192.80 | 0.168115E+09 |
May | 0.655811E+09 | 0.298050E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 527962.33 | 93142584.66 |
June | 0.653980E+09 | 0.294021E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6952963.93 | 55271545.72 |
July | 0.607235E+09 | 0.277884E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2309500.61 | 42920314.48 |
August | 0.682256E+09 | 0.311538E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2528237.51 | 58552366.73 |
September | 0.605404E+09 | 0.290901E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1749927.39 | 92538247.64 |
October | 0.629366E+09 | 0.318204E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173477E+09 |
November | 0.623221E+09 | 0.342568E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272418E+09 |
December | 0.607235E+09 | 0.358059E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352981E+09 |
Annual Sum or Average | 0.755252E+10 | 0.375800E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15547784.57 | 0.229412E+10 |
Minimum of Months | 0.570983E+09 | 0.277884E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42920314.48 |
Maximum of Months | 0.682256E+09 | 0.358059E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6952963.93 | 0.412599E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.574563E+09 | 0.204758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964516E+09 |
February | 0.901968E+09 | 0.483560E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717945E+09 |
March | 0.107774E+10 | 0.524899E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623359E+09 |
April | 0.956342E+09 | 0.455511E+09 | 0.197726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4296695.18 | 0.394297E+09 |
May | 0.103597E+10 | 0.470358E+09 | 0.208852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1185839.89 | 0.222886E+09 |
June | 0.103308E+10 | 0.463982E+09 | 0.205071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16382808.58 | 0.131384E+09 |
July | 0.959235E+09 | 0.438033E+09 | 0.201461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5740265.26 | 95495378.23 |
August | 0.107774E+10 | 0.491936E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6034359.29 | 0.129660E+09 |
September | 0.956342E+09 | 0.463019E+09 | 0.197634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5120390.93 | 0.203154E+09 |
October | 0.994195E+09 | 0.509127E+09 | 0.204804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383182E+09 |
November | 0.984487E+09 | 0.556698E+09 | 0.200273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621382E+09 |
December | 0.959235E+09 | 0.591538E+09 | 0.201415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818337E+09 |
Annual Sum or Average | 0.119305E+11 | 0.602323E+10 | 0.243325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38760359.14 | 0.530560E+10 |
Minimum of Months | 0.901968E+09 | 0.438033E+09 | 0.185366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95495378.23 |
Maximum of Months | 0.107774E+10 | 0.591538E+09 | 0.212947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16382808.58 | 0.964516E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.354471E+09 | 0.129621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644199E+09 |
February | 0.421807E+09 | 0.300451E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480771E+09 |
March | 0.502994E+09 | 0.330917E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420445E+09 |
April | 0.447140E+09 | 0.287648E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2841540.65 | 0.268888E+09 |
May | 0.484071E+09 | 0.300188E+09 | 0.132213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 790994.15 | 0.151319E+09 |
June | 0.482240E+09 | 0.295776E+09 | 0.129819E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10883611.60 | 88219390.96 |
July | 0.448971E+09 | 0.278826E+09 | 0.127534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3671371.70 | 64374403.08 |
August | 0.502994E+09 | 0.313092E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4042061.12 | 86836165.20 |
September | 0.447140E+09 | 0.292809E+09 | 0.125111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3204484.93 | 0.138494E+09 |
October | 0.465148E+09 | 0.316974E+09 | 0.129650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261516E+09 |
November | 0.460569E+09 | 0.346276E+09 | 0.126781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415554E+09 |
December | 0.448971E+09 | 0.361620E+09 | 0.127504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546827E+09 |
Annual Sum or Average | 0.557719E+10 | 0.377905E+10 | 0.154036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25434064.16 | 0.356744E+10 |
Minimum of Months | 0.421807E+09 | 0.278826E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64374403.08 |
Maximum of Months | 0.502994E+09 | 0.361620E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10883611.60 | 0.644199E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.545831E+09 | 0.204757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982532E+09 |
February | 0.901968E+09 | 0.463298E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739416E+09 |
March | 0.107774E+10 | 0.519469E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649747E+09 |
April | 0.956342E+09 | 0.454780E+09 | 0.197725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2967542.63 | 0.412535E+09 |
May | 0.103597E+10 | 0.473927E+09 | 0.208851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1185667.83 | 0.228346E+09 |
June | 0.103308E+10 | 0.468014E+09 | 0.205070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15598168.51 | 0.131624E+09 |
July | 0.959235E+09 | 0.440989E+09 | 0.201460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5122432.11 | 96693294.75 |
August | 0.107774E+10 | 0.494622E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5685787.18 | 0.134457E+09 |
September | 0.956342E+09 | 0.460293E+09 | 0.197632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3671723.39 | 0.216215E+09 |
October | 0.994195E+09 | 0.494212E+09 | 0.204803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415031E+09 |
November | 0.984487E+09 | 0.535048E+09 | 0.200271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642111E+09 |
December | 0.959235E+09 | 0.552559E+09 | 0.201413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.840870E+09 |
Annual Sum or Average | 0.119305E+11 | 0.590304E+10 | 0.243324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34231321.66 | 0.548958E+10 |
Minimum of Months | 0.901968E+09 | 0.440989E+09 | 0.185364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96693294.75 |
Maximum of Months | 0.107774E+10 | 0.552559E+09 | 0.212945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15598168.51 | 0.982532E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.353263E+09 | 0.129620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.644597E+09 |
February | 0.570983E+09 | 0.298431E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482701E+09 |
March | 0.682256E+09 | 0.330733E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421290E+09 |
April | 0.605404E+09 | 0.287808E+09 | 0.125169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1936299.14 | 0.272857E+09 |
May | 0.655811E+09 | 0.298380E+09 | 0.132212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 797419.18 | 0.152478E+09 |
June | 0.653980E+09 | 0.294339E+09 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10396798.98 | 89162025.96 |
July | 0.607235E+09 | 0.278166E+09 | 0.127533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3541944.08 | 67065150.32 |
August | 0.682256E+09 | 0.311923E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3926931.48 | 90296770.14 |
September | 0.605404E+09 | 0.291444E+09 | 0.125110E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2802807.88 | 0.140041E+09 |
October | 0.629366E+09 | 0.319086E+09 | 0.129649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260818E+09 |
November | 0.623221E+09 | 0.343612E+09 | 0.126780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416265E+09 |
December | 0.607235E+09 | 0.359691E+09 | 0.127503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547036E+09 |
Annual Sum or Average | 0.755252E+10 | 0.376688E+10 | 0.154035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23402200.75 | 0.358461E+10 |
Minimum of Months | 0.570983E+09 | 0.278166E+09 | 0.117344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67065150.32 |
Maximum of Months | 0.682256E+09 | 0.359691E+09 | 0.134804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10396798.98 | 0.644597E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128330E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969020E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851910E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5484099.06 | 0.543103E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1149913.24 | 0.300220E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21012942.80 | 0.174026E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5944254.39 | 0.126836E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5702196.25 | 0.176147E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4754936.10 | 0.283829E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547232E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.860499E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110772E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44048341.85 | 0.722384E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126836E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21012942.80 | 0.128330E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161516E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121188E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106105E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6660532.71 | 0.677160E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1470183.14 | 0.382708E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26393148.01 | 0.222027E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7441122.19 | 0.162236E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7566838.40 | 0.223175E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6763182.99 | 0.351044E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657654E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105180E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137912E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56295007.43 | 0.899502E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162236E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26393148.01 | 0.161516E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168555E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124939E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109096E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3088812.12 | 0.693052E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1027665.02 | 0.400010E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18074556.97 | 0.227724E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3543383.53 | 0.169772E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5617957.61 | 0.230207E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3937063.27 | 0.352196E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649301E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105876E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141412E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35289438.52 | 0.922104E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169772E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18074556.97 | 0.168555E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 18185.19 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 18185.19 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 18185.19 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 18185.19 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 18185.19 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 18185.19 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 18185.19 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 18185.19 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 18185.19 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 18185.19 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 18185.19 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 18185.19 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 18185.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 4220.20 | 02-JAN-08:09 | 6808.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 4220.20 | 01-FEB-08:09 | 6808.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 4220.20 | 01-MAR-08:09 | 6808.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 4220.20 | 03-APR-07:10 | 6808.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 4220.20 | 01-MAY-07:10 | 6808.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 4220.20 | 01-JUN-07:10 | 6808.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 4220.20 | 03-JUL-07:10 | 6808.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 4220.20 | 01-AUG-07:10 | 6808.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 4220.20 | 01-SEP-07:10 | 6808.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 4220.20 | 02-OCT-07:10 | 6808.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 4220.20 | 01-NOV-07:10 | 6808.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 4220.20 | 01-DEC-08:09 | 6808.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2247.57 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 761.39 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1541.38 | 04-FEB-23:00 |
March | 1306.65 | 01-MAR-10:09 | 648.81 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1203.09 | 06-MAR-06:00 |
April | 1306.65 | 03-APR-09:09 | 597.13 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.30 | 15-APR-17:02 | 895.35 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 452.38 | 09-MAY-15:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.46 | 31-MAY-13:00 | 604.48 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 487.28 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.58 | 11-JUN-14:56 | 509.36 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 487.79 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.94 | 02-JUL-15:00 | 235.06 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 470.08 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.64 | 04-AUG-16:40 | 308.60 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 600.74 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.73 | 17-SEP-14:42 | 457.22 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 860.21 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 625.97 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1659.03 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2609.76 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 452.38 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.06 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 241.58 | 2609.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1502.28 | 29-JAN-10:54 |
February | 827.22 | 01-FEB-10:09 | 488.42 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1027.58 | 04-FEB-23:00 |
March | 827.22 | 01-MAR-10:09 | 421.34 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 815.19 | 05-MAR-09:55 |
April | 827.22 | 03-APR-09:09 | 312.64 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.35 | 15-APR-17:02 | 596.90 | 02-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 299.79 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 31-MAY-13:00 | 405.65 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 300.18 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.15 | 11-JUN-14:56 | 339.91 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 300.63 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.68 | 02-JUL-15:38 | 156.53 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 268.66 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.43 | 04-AUG-16:40 | 210.38 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 313.02 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 | 17-SEP-14:42 | 303.48 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 511.14 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 418.33 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1105.49 | 20-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1739.11 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.53 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 166.15 | 1739.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2311.24 | 29-JAN-12:52 |
February | 1306.65 | 01-FEB-10:09 | 736.07 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1543.03 | 04-FEB-22:55 |
March | 1306.65 | 01-MAR-10:09 | 610.08 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1328.27 | 05-MAR-14:15 |
April | 1306.65 | 03-APR-09:09 | 591.16 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.94 | 15-APR-17:10 | 895.35 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 444.39 | 09-MAY-15:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.46 | 31-MAY-13:00 | 614.68 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 489.56 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.53 | 11-JUN-14:56 | 511.20 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 490.22 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.10 | 02-JUL-15:36 | 236.69 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 463.17 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.64 | 04-AUG-16:40 | 325.32 | 06-AUG-13:50 |
September | 1306.65 | 01-SEP-09:09 | 582.88 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.19 | 10-SEP-14:48 | 460.58 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 815.54 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 647.92 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1660.43 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2610.75 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 444.39 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.69 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 239.53 | 2610.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1499.13 | 29-JAN-10:54 |
February | 827.17 | 01-FEB-10:09 | 455.51 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1027.72 | 04-FEB-22:55 |
March | 827.17 | 01-MAR-10:09 | 412.33 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 803.05 | 06-MAR-05:58 |
April | 827.17 | 03-APR-09:09 | 397.32 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.48 | 15-APR-17:07 | 596.90 | 02-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 294.14 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 31-MAY-13:00 | 404.18 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 312.89 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.22 | 11-JUN-14:54 | 335.99 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 313.86 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.28 | 02-JUL-11:00 | 163.65 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 306.70 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.43 | 04-AUG-16:40 | 211.51 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 403.08 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.98 | 17-SEP-12:00 | 322.12 | 24-SEP-17:43 |
October | 827.17 | 02-OCT-09:09 | 545.91 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 420.64 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1105.32 | 20-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1738.59 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 294.14 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.65 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 161.22 | 1738.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1196.60 | 29-JAN-10:54 |
February | 1306.65 | 01-FEB-10:09 | 753.73 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 818.27 | 04-FEB-22:53 |
March | 1306.65 | 01-MAR-10:09 | 637.84 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 651.40 | 12-MAR-16:00 |
April | 1306.65 | 03-APR-09:09 | 583.88 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.93 | 15-APR-17:02 | 491.17 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 447.51 | 09-MAY-15:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.87 | 31-MAY-13:00 | 323.47 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 484.11 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.07 | 18-JUN-16:00 | 289.40 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 484.65 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.18 | 02-JUL-15:30 | 119.93 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 466.03 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.06 | 04-AUG-16:40 | 170.02 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 587.54 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.97 | 17-SEP-15:00 | 264.47 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 858.65 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 390.59 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 887.14 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1410.18 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 447.51 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.93 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 158.93 | 1410.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 563.23 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 806.63 | 29-JAN-10:52 |
February | 827.22 | 01-FEB-10:09 | 484.56 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 545.51 | 04-FEB-22:53 |
March | 827.22 | 01-MAR-10:09 | 416.24 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 443.51 | 05-MAR-09:55 |
April | 827.22 | 03-APR-09:09 | 310.92 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.10 | 15-APR-17:02 | 326.78 | 02-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 298.00 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 | 31-MAY-13:00 | 225.62 | 01-MAY-24:00 |
June | 827.22 | 01-JUN-09:09 | 297.90 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.86 | 18-JUN-16:00 | 199.14 | 02-JUN-05:00 |
July | 827.22 | 03-JUL-09:09 | 298.49 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 | 02-JUL-15:30 | 82.94 | 09-JUL-10:00 |
August | 827.22 | 01-AUG-09:09 | 268.66 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.37 | 04-AUG-16:40 | 117.12 | 06-AUG-09:00 |
September | 827.22 | 01-SEP-09:09 | 311.44 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 | 17-SEP-15:00 | 180.45 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 507.92 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 266.72 | 24-OCT-05:00 |
November | 827.22 | 01-NOV-09:09 | 563.23 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 591.28 | 20-NOV-22:02 |
December | 827.22 | 01-DEC-10:09 | 563.23 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 938.13 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.94 | |||||
Maximum of Months | 827.22 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 97.86 | 938.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 63498.94 | 31-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 728.85 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 73025.02 | 02-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 596.81 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 40488.19 | 06-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 577.59 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4441.70 | 18-APR-12:00 | 34099.01 | 03-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 424.37 | 01-MAY-07:10 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5881.40 | 31-MAY-12:00 | 22280.12 | 02-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 486.54 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8311.64 | 26-JUN-16:05 | 15794.04 | 02-JUN-06:03 |
July | 1306.65 | 03-JUL-09:09 | 487.23 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6679.41 | 26-JUL-16:10 | 11127.70 | 24-JUL-06:03 |
August | 1306.65 | 01-AUG-09:09 | 458.70 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9853.54 | 04-AUG-16:03 | 15361.48 | 07-AUG-06:03 |
September | 1306.65 | 01-SEP-09:09 | 568.69 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7810.67 | 07-SEP-16:03 | 25093.26 | 29-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 811.33 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 29526.29 | 23-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 46485.67 | 28-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 52051.76 | 08-DEC-17:01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11127.70 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 9853.54 | 73025.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 797.63 | 29-JAN-10:54 |
February | 827.17 | 01-FEB-10:09 | 451.22 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 545.51 | 04-FEB-22:53 |
March | 827.17 | 01-MAR-10:09 | 404.91 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 441.53 | 12-MAR-16:00 |
April | 827.17 | 03-APR-09:09 | 391.44 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.02 | 15-APR-17:10 | 324.82 | 02-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 291.77 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 | 31-MAY-13:00 | 220.62 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 311.30 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.65 | 11-JUN-15:07 | 193.82 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 312.32 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.70 | 02-JUL-11:30 | 88.16 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 304.87 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.37 | 04-AUG-16:40 | 121.14 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 397.38 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 17-SEP-11:40 | 180.31 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 545.16 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 266.58 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 591.25 | 20-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 937.00 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 291.77 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.16 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 82.65 | 937.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.25 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1869.64 | 29-JAN-11:00 |
February | 1306.65 | 01-FEB-10:09 | 761.39 | 01-FEB-16:00 | 1435.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1282.09 | 04-FEB-22:53 |
March | 1306.65 | 01-MAR-10:09 | 648.79 | 01-MAR-16:00 | 1435.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1035.06 | 12-MAR-16:00 |
April | 1306.65 | 03-APR-09:09 | 597.11 | 10-APR-07:10 | 1435.25 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.49 | 15-APR-17:02 | 765.03 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 452.37 | 09-MAY-15:30 | 1435.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 | 31-MAY-13:00 | 536.20 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 487.27 | 13-JUN-07:10 | 1435.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.90 | 11-JUN-15:00 | 459.94 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 487.79 | 20-JUL-07:10 | 1435.25 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.31 | 02-JUL-16:00 | 199.52 | 09-JUL-21:00 |
August | 1306.65 | 01-AUG-09:09 | 470.07 | 31-AUG-07:10 | 1435.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.64 | 04-AUG-16:40 | 269.59 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 600.72 | 21-SEP-07:10 | 1435.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 | 17-SEP-15:00 | 405.67 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 860.21 | 31-OCT-07:10 | 1435.25 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 587.07 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1386.39 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2192.74 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 452.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.52 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 197.90 | 2192.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 563.23 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1254.85 | 29-JAN-10:52 |
February | 805.43 | 01-FEB-08:09 | 488.42 | 01-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 854.72 | 04-FEB-22:53 |
March | 805.43 | 01-MAR-08:09 | 421.33 | 01-MAR-16:00 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 730.27 | 05-MAR-09:55 |
April | 805.43 | 03-APR-07:10 | 312.64 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.24 | 15-APR-17:02 | 508.43 | 02-APR-24:00 |
May | 805.43 | 01-MAY-07:10 | 299.79 | 24-MAY-15:00 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 31-MAY-13:00 | 358.73 | 01-MAY-24:00 |
June | 805.43 | 01-JUN-07:10 | 300.17 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.77 | 18-JUN-16:10 | 306.60 | 02-JUN-05:00 |
July | 805.43 | 03-JUL-07:10 | 300.63 | 31-JUL-15:00 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 | 02-JUL-16:00 | 139.47 | 09-JUL-10:00 |
August | 805.43 | 01-AUG-07:10 | 268.66 | 01-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 | 04-AUG-16:40 | 183.47 | 06-AUG-09:00 |
September | 805.43 | 01-SEP-07:10 | 313.02 | 29-SEP-15:00 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.53 | 17-SEP-15:00 | 268.95 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 511.14 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 392.06 | 24-OCT-05:00 |
November | 805.43 | 01-NOV-07:10 | 563.23 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 923.90 | 20-NOV-22:02 |
December | 805.43 | 01-DEC-08:09 | 563.23 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1461.82 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.47 | |||||
Maximum of Months | 805.43 | 563.23 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 144.77 | 1461.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 889.66 | 02-JAN-16:40 | 1435.24 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1992.00 | 29-JAN-13:00 |
February | 1306.65 | 01-FEB-10:09 | 736.06 | 14-FEB-16:00 | 1435.24 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1282.08 | 04-FEB-22:53 |
March | 1306.65 | 01-MAR-10:09 | 610.06 | 01-MAR-16:00 | 1435.24 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1161.02 | 05-MAR-14:00 |
April | 1306.65 | 03-APR-09:09 | 591.14 | 10-APR-07:10 | 1435.24 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.64 | 15-APR-17:10 | 769.04 | 02-APR-24:00 |
May | 1306.65 | 01-MAY-09:09 | 444.38 | 09-MAY-15:30 | 1435.24 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.30 | 31-MAY-13:00 | 544.16 | 01-MAY-24:00 |
June | 1306.65 | 01-JUN-09:09 | 489.56 | 13-JUN-07:10 | 1435.24 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.38 | 11-JUN-15:24 | 461.54 | 02-JUN-05:00 |
July | 1306.65 | 03-JUL-09:09 | 490.22 | 20-JUL-07:10 | 1435.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.34 | 02-JUL-15:56 | 202.08 | 09-JUL-10:00 |
August | 1306.65 | 01-AUG-09:09 | 463.16 | 31-AUG-07:10 | 1435.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.64 | 04-AUG-16:40 | 274.33 | 06-AUG-09:00 |
September | 1306.65 | 01-SEP-09:09 | 582.86 | 21-SEP-07:10 | 1435.24 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | 06-SEP-16:00 | 408.42 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 815.54 | 31-OCT-07:10 | 1435.24 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 605.64 | 24-OCT-05:00 |
November | 1306.65 | 01-NOV-09:09 | 889.66 | 06-NOV-16:00 | 1435.24 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1387.67 | 20-NOV-22:02 |
December | 1306.65 | 01-DEC-10:09 | 889.66 | 01-DEC-16:30 | 1435.24 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2192.74 | 09-DEC-01:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1306.65 | 444.38 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.08 | |||||
Maximum of Months | 1306.65 | 889.66 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 198.38 | 2192.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 563.19 | 02-JAN-16:40 | 908.57 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1246.44 | 29-JAN-10:52 |
February | 827.17 | 01-FEB-10:09 | 455.50 | 14-FEB-16:00 | 908.57 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 854.72 | 04-FEB-22:53 |
March | 827.17 | 01-MAR-10:09 | 412.34 | 14-MAR-07:10 | 908.57 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 698.58 | 12-MAR-16:00 |
April | 827.17 | 03-APR-09:09 | 397.31 | 10-APR-07:10 | 908.57 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.94 | 15-APR-17:07 | 506.94 | 02-APR-24:00 |
May | 827.17 | 01-MAY-09:09 | 294.14 | 25-MAY-07:10 | 908.57 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 31-MAY-13:00 | 358.30 | 01-MAY-24:00 |
June | 827.17 | 01-JUN-09:09 | 312.88 | 13-JUN-07:10 | 908.57 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.52 | 11-JUN-15:24 | 304.11 | 02-JUN-05:00 |
July | 827.17 | 03-JUL-09:09 | 313.85 | 20-JUL-07:10 | 908.57 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 02-JUL-11:20 | 138.72 | 09-JUL-21:00 |
August | 827.17 | 01-AUG-09:09 | 306.69 | 31-AUG-07:10 | 908.57 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 | 04-AUG-16:40 | 184.62 | 06-AUG-09:00 |
September | 827.17 | 01-SEP-09:09 | 403.06 | 21-SEP-07:10 | 908.57 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.95 | 17-SEP-11:40 | 270.14 | 24-SEP-17:43 |
October | 827.17 | 02-OCT-09:09 | 545.91 | 31-OCT-07:10 | 908.57 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 393.73 | 24-OCT-05:00 |
November | 827.17 | 01-NOV-09:09 | 563.19 | 06-NOV-16:00 | 908.57 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 923.82 | 20-NOV-22:02 |
December | 827.17 | 01-DEC-10:09 | 563.19 | 01-DEC-16:30 | 908.57 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1461.82 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 827.17 | 294.14 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.72 | |||||
Maximum of Months | 827.17 | 563.19 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 127.52 | 1461.82 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2496.98 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1732.92 | 04-FEB-22:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1423.76 | 12-MAR-16:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.15 | 15-APR-17:02 | 1106.77 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 | 31-MAY-13:00 | 738.97 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.45 | 11-JUN-14:52 | 638.84 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.50 | 02-JUL-15:10 | 257.32 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.09 | 04-AUG-16:30 | 353.51 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.28 | 17-SEP-14:42 | 558.51 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 856.91 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1820.68 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3028.08 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.32 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.45 | 3028.08 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3125.64 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2193.47 | 04-FEB-22:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1784.47 | 21-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.37 | 15-APR-17:02 | 1329.77 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.58 | 31-MAY-13:00 | 937.86 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.03 | 11-JUN-15:00 | 805.11 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.73 | 02-JUL-15:00 | 325.24 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.92 | 04-AUG-16:30 | 448.75 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.11 | 17-SEP-14:42 | 706.88 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1035.54 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2259.28 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3789.00 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.24 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.03 | 3789.00 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3301.51 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2238.54 | 10-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1824.45 | 12-MAR-16:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.17 | 15-APR-17:02 | 1330.93 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 | 31-MAY-13:00 | 909.65 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.46 | 18-JUN-16:00 | 767.46 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.22 | 25-JUL-21:03 | 352.15 | 09-JUL-21:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.90 | 03-AUG-16:00 | 466.59 | 06-AUG-09:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.26 | 06-SEP-16:00 | 679.96 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 930.49 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2437.19 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3838.56 | 09-DEC-01:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.15 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.46 | 3838.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 7631.56 | 13-JAN-17:00 | 12070.02 | 8440.40 | 28785.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9002.63 | 24-FEB-17:00 | 6035.01 | 4220.20 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15532.97 | 24-MAR-07:20 | 12070.02 | 8440.40 | 36370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39502.14 | 19-APR-05:02 | 3176.32 | 2344.59 | 24947.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36678.03 | 30-MAY-06:02 | 6352.64 | 7033.77 | 43983.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39475.46 | 24-JUN-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 41493.45 | 05-JUL-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 39708.40 | 19-AUG-05:03 | 2541.06 | 1875.67 | 19958.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 41171.61 | 11-SEP-04:03 | 0.00 | 1875.67 | 17622.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 18709.57 | 13-OCT-07:02 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17731.35 | 07-NOV-08:07 | 18105.02 | 12660.61 | 54555.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8899.86 | 07-DEC-16:20 | 12070.02 | 8440.40 | 28785.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 7631.56 | 0.00 | 1875.67 | 14392.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 41493.45 | 60350.08 | 42202.02 | 181851.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.48 |
February | 645.34 | 25-FEB-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.44 |
March | 1967.86 | 25-MAR-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.83 |
April | 8195.72 | 18-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.99 | 0.00 |
May | 9344.75 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.77 | 0.00 |
June | 10719.74 | 26-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.73 | 0.00 |
July | 10204.82 | 05-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 0.00 |
August | 10597.41 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.46 | 0.00 |
September | 9490.55 | 07-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.24 | 0.00 |
October | 3331.26 | 20-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 |
November | 1692.73 | 04-NOV-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.36 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10719.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.46 | 710.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2648.68 | 05-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713.64 |
February | 2246.02 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.90 |
March | 1704.77 | 30-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.18 |
April | 3093.96 | 18-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.35 | 0.00 |
May | 3663.81 | 31-MAY-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.35 | 0.00 |
June | 4805.93 | 26-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.44 | 0.00 |
July | 5091.01 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 |
August | 4361.46 | 04-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.34 | 0.00 |
September | 4074.47 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2089.22 | 13-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.79 |
November | 1840.44 | 25-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1277.27 |
December | 2086.86 | 28-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1704.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5091.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.34 | 1277.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3286.59 | 05-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.93 |
February | 4374.82 | 02-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.10 |
March | 2719.94 | 21-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.86 |
April | 3295.56 | 21-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.69 |
May | 3748.11 | 31-MAY-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.64 | 0.00 |
June | 5870.94 | 26-JUN-12:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.95 | 0.00 |
July | 5364.17 | 05-JUL-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.24 |
August | 4489.53 | 04-AUG-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 | 0.00 |
September | 4496.60 | 11-SEP-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.01 | 0.00 |
October | 2207.86 | 26-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.87 |
November | 2172.98 | 09-NOV-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.90 |
December | 3136.45 | 08-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2172.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5870.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 | 577.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6000.58 | 13-JAN-17:00 | 12070.02 | 8440.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6238.46 | 24-FEB-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7110.50 | 24-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23878.03 | 17-APR-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 29381.98 | 30-MAY-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30034.95 | 12-JUN-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 30183.08 | 05-JUL-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29098.21 | 28-AUG-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 30116.30 | 11-SEP-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8344.68 | 20-OCT-13:10 | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7515.97 | 03-NOV-13:30 | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5862.53 | 01-DEC-16:20 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5862.53 | 0.00 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30183.08 | 12070.02 | 8440.40 | 13616.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5831.52 | 13-JAN-16:40 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6355.94 | 24-FEB-17:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7319.20 | 24-MAR-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15918.47 | 17-APR-15:30 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 18062.14 | 30-MAY-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31665.59 | 26-JUN-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 32016.05 | 03-JUL-04:03 | 0.00 | 1875.67 | 9768.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30630.18 | 28-AUG-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27739.47 | 11-SEP-05:03 | 2541.06 | 1875.67 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7732.88 | 20-OCT-13:30 | 6198.29 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7371.63 | 03-NOV-16:00 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5729.87 | 01-DEC-16:10 | 6035.01 | 4220.20 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 5729.87 | 0.00 | 1875.67 | 6808.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32016.05 | 6198.29 | 4220.20 | 12103.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1012.09 | 13-JAN-21:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.79 |
February | 1149.27 | 24-FEB-16:20 | 1272.23 | 456.13 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.73 |
March | 1513.73 | 28-MAR-15:40 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.14 |
April | 5367.51 | 18-APR-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 46.75 | 0.00 |
May | 5906.71 | 31-MAY-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 28.89 | 0.00 |
June | 10369.97 | 25-JUN-18:02 | 0.00 | 141.44 | 2316.62 | 0.00 | 0.00 | 0.00 | 0.00 | 124.53 | 0.00 |
July | 8223.61 | 03-JUL-06:03 | 1071.35 | 565.83 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.72 |
August | 6573.34 | 04-AUG-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 38.01 | 0.00 |
September | 5845.97 | 11-SEP-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 38.74 | 0.00 |
October | 1644.31 | 20-OCT-13:40 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 |
November | 1487.71 | 03-NOV-15:40 | 1272.23 | 467.72 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.70 |
December | 1012.68 | 02-DEC-16:03 | 401.76 | 392.23 | 1674.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1012.09 | 0.00 | 141.44 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10369.97 | 1306.65 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 124.53 | 107.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 929.04 | 13-JAN-21:03 | 339.13 | 500.65 | 1615.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.70 |
February | 1370.58 | 24-FEB-10:20 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.04 |
March | 2256.06 | 28-MAR-09:35 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.95 |
April | 7306.21 | 18-APR-09:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 | 0.00 |
May | 10384.52 | 29-MAY-10:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.85 |
June | 13362.46 | 25-JUN-08:42 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 |
July | 13399.90 | 02-JUL-08:52 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.89 |
August | 11155.12 | 20-AUG-09:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.15 |
September | 11541.55 | 04-SEP-09:32 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.66 |
October | 2487.93 | 20-OCT-09:50 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.68 |
November | 1348.39 | 04-NOV-09:40 | 522.45 | 179.11 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.02 |
December | 934.07 | 02-DEC-16:03 | 254.35 | 247.84 | 1060.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 929.04 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13399.90 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 | 104.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3922.75 | 12-JAN-12:40 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.13 |
February | 7155.67 | 24-FEB-13:50 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.37 |
March | 7617.59 | 24-MAR-13:40 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.31 |
April | 13321.30 | 16-APR-15:12 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 0.00 |
May | 10405.70 | 29-MAY-12:23 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.24 |
June | 16145.60 | 11-JUN-12:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 85.03 | 0.00 |
July | 16205.33 | 02-JUL-12:13 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 27.62 | 0.00 |
August | 16363.54 | 13-AUG-13:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 |
September | 16405.40 | 17-SEP-13:52 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 | 0.00 |
October | 10349.43 | 20-OCT-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.65 |
November | 9109.37 | 03-NOV-13:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.35 |
December | 5198.25 | 01-DEC-13:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3922.75 | 200.88 | 70.72 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16405.40 | 1306.65 | 424.37 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 85.03 | 128.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1373.98 | 12-JAN-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.61 |
February | 2388.67 | 24-FEB-16:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.46 |
March | 2722.49 | 23-MAR-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 |
April | 13890.29 | 15-APR-17:05 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 78.10 | 0.00 |
May | 12536.16 | 14-MAY-16:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.16 |
June | 15160.95 | 25-JUN-16:42 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 94.72 | 0.00 |
July | 15354.24 | 23-JUL-15:52 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.20 |
August | 12909.99 | 13-AUG-16:12 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.05 |
September | 12358.91 | 04-SEP-16:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 |
October | 4909.68 | 20-OCT-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.08 |
November | 3007.29 | 03-NOV-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.73 |
December | 1365.48 | 01-DEC-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1365.48 | 211.94 | 74.61 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15354.24 | 805.38 | 268.64 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 94.72 | 93.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 989.34 | 13-JAN-21:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.34 |
February | 989.17 | 09-FEB-21:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.35 |
March | 1252.86 | 28-MAR-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 |
April | 2722.32 | 18-APR-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 0.00 |
May | 3648.24 | 31-MAY-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 0.00 |
June | 5067.47 | 26-JUN-14:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 17.62 | 0.00 |
July | 5816.98 | 05-JUL-06:03 | 803.52 | 424.37 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.53 |
August | 5314.17 | 04-AUG-07:33 | 5088.93 | 1697.46 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.80 | 0.00 |
September | 5144.66 | 11-SEP-14:00 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.82 | 0.00 |
October | 1555.88 | 02-OCT-15:20 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 |
November | 1454.30 | 03-NOV-15:40 | 1272.23 | 464.03 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 |
December | 987.97 | 02-DEC-16:03 | 401.76 | 388.92 | 1674.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 987.97 | 401.76 | 388.92 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5816.98 | 5088.93 | 1697.46 | 5740.99 | 0.00 | 0.00 | 0.00 | 0.00 | 20.82 | 69.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 817.91 | 13-JAN-07:03 | 1695.64 | 1877.44 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 |
February | 1014.44 | 24-FEB-10:15 | 1654.44 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.68 |
March | 1222.28 | 28-MAR-10:00 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.06 |
April | 4761.31 | 18-APR-09:40 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | 0.00 |
May | 5708.81 | 31-MAY-09:30 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 0.00 |
June | 8456.31 | 25-JUN-09:22 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 | 0.00 |
July | 10761.83 | 02-JUL-09:21 | 296.74 | 104.47 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
August | 8325.44 | 20-AUG-09:43 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.64 |
September | 7741.62 | 04-SEP-07:42 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.26 |
October | 2221.31 | 20-OCT-09:50 | 827.22 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 |
November | 1188.91 | 03-NOV-10:50 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 |
December | 864.77 | 05-DEC-09:30 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 817.91 | 169.56 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10761.83 | 1695.64 | 1877.44 | 4038.10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 142.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1091.50 | 13-JAN-14:30 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3229.65 |
February | 1438.02 | 25-FEB-15:30 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.48 |
March | 2200.17 | 24-MAR-14:00 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.34 |
April | 10226.76 | 18-APR-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 4441.70 | 0.00 |
May | 10503.05 | 31-MAY-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 5881.40 | 0.00 |
June | 11239.38 | 26-JUN-12:00 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 6421.96 | 0.00 |
July | 12563.23 | 30-JUL-13:52 | 401.76 | 141.44 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2.08 | 0.00 |
August | 11736.73 | 04-AUG-16:10 | 1607.03 | 943.02 | 3189.42 | 0.00 | 0.00 | 0.00 | 0.00 | 8613.35 | 0.00 |
September | 13392.10 | 04-SEP-14:22 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.96 |
October | 8165.47 | 30-OCT-12:06 | 6361.16 | 2121.83 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1424.01 |
November | 6599.79 | 04-NOV-13:30 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.34 |
December | 1407.72 | 02-DEC-12:40 | 137.54 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1091.50 | 133.92 | 70.73 | 558.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13392.10 | 6361.16 | 2121.83 | 7176.19 | 0.00 | 0.00 | 0.00 | 0.00 | 8613.35 | 3229.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1038.31 | 12-JAN-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.97 |
February | 1326.76 | 24-FEB-16:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.32 |
March | 1312.29 | 23-MAR-16:50 | 254.33 | 149.24 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.02 |
April | 9257.57 | 16-APR-17:01 | 0.00 | 104.46 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 18.74 | 0.00 |
May | 6388.61 | 21-MAY-18:03 | 0.00 | 44.77 | 733.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.95 |
June | 11530.27 | 25-JUN-18:02 | 0.00 | 89.54 | 1466.51 | 0.00 | 0.00 | 0.00 | 0.00 | 41.21 | 0.00 |
July | 11852.11 | 02-JUL-17:21 | 0.00 | 134.31 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 | 0.00 |
August | 9416.01 | 05-AUG-17:05 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 |
September | 11673.57 | 04-SEP-17:42 | 0.00 | 74.61 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.15 |
October | 4172.66 | 11-OCT-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.28 |
November | 2575.98 | 03-NOV-15:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.68 |
December | 1089.72 | 01-DEC-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1038.31 | 0.00 | 44.77 | 504.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11852.11 | 805.38 | 268.64 | 2199.77 | 0.00 | 0.00 | 0.00 | 0.00 | 41.21 | 48.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 943.37 | 13-JAN-21:03 | 535.68 | 790.82 | 2551.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.14 |
February | 1084.26 | 24-FEB-16:30 | 1272.23 | 462.49 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.30 |
March | 1409.13 | 28-MAR-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.66 |
April | 4878.48 | 18-APR-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 | 0.00 |
May | 5279.12 | 31-MAY-15:00 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 24.16 | 0.00 |
June | 9307.17 | 25-JUN-18:31 | 0.00 | 165.01 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 | 0.00 |
July | 7734.22 | 05-JUL-06:03 | 803.52 | 424.37 | 1913.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 |
August | 5839.68 | 04-AUG-15:30 | 1272.23 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 | 0.00 |
September | 5568.15 | 11-SEP-13:40 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 31.12 | 0.00 |
October | 1699.56 | 20-OCT-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 |
November | 1494.95 | 03-NOV-13:30 | 1306.65 | 424.37 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.87 |
December | 938.24 | 02-DEC-16:03 | 401.76 | 392.23 | 1674.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 938.24 | 0.00 | 165.01 | 1435.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9307.17 | 1306.65 | 790.82 | 2702.72 | 0.00 | 0.00 | 0.00 | 0.00 | 68.64 | 90.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1060.06 | 12-JAN-10:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.13 |
February | 1447.68 | 24-FEB-10:00 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.61 |
March | 2886.52 | 28-MAR-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.76 |
April | 7255.13 | 18-APR-09:00 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.63 |
May | 11335.82 | 29-MAY-09:53 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.47 |
June | 14314.62 | 25-JUN-08:31 | 296.74 | 104.47 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 |
July | 14225.09 | 04-JUL-08:61 | 296.74 | 104.47 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.84 |
August | 13133.75 | 27-AUG-09:32 | 211.95 | 74.62 | 1514.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 |
September | 11382.01 | 03-SEP-08:23 | 169.56 | 59.70 | 1211.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.97 |
October | 3184.83 | 20-OCT-08:55 | 1610.86 | 537.32 | 1817.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 |
November | 1493.00 | 04-NOV-09:40 | 0.00 | 179.11 | 1009.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.89 |
December | 1088.95 | 05-DEC-09:50 | 805.43 | 268.66 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1060.06 | 0.00 | 59.70 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 14314.62 | 1610.86 | 537.32 | 2120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4544.48 | 12-JAN-12:30 | 687.71 | 424.37 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.38 |
February | 7245.19 | 24-FEB-13:40 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.79 |
March | 7656.22 | 24-MAR-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.42 |
April | 11653.66 | 16-APR-13:53 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 32.61 | 0.00 |
May | 9578.17 | 29-MAY-12:33 | 200.88 | 70.72 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.88 |
June | 14345.04 | 11-JUN-12:02 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 72.44 | 0.00 |
July | 14727.06 | 30-JUL-11:43 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 |
August | 14707.93 | 13-AUG-13:32 | 267.84 | 94.29 | 1913.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.64 |
September | 14831.25 | 04-SEP-13:12 | 334.80 | 117.87 | 2392.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.68 |
October | 10335.61 | 20-OCT-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.98 |
November | 9296.60 | 03-NOV-13:10 | 1306.65 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.55 |
December | 5644.39 | 01-DEC-13:30 | 1272.23 | 424.37 | 1435.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4544.48 | 200.88 | 70.72 | 1275.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14831.25 | 2544.47 | 848.73 | 2870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 72.44 | 107.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1328.18 | 12-JAN-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.29 |
February | 2404.54 | 24-FEB-16:40 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.75 |
March | 2906.45 | 21-MAR-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.53 |
April | 12054.88 | 16-APR-16:32 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 | 0.00 |
May | 11555.95 | 14-MAY-16:52 | 211.94 | 74.61 | 1514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.44 |
June | 14373.18 | 25-JUN-18:31 | 0.00 | 104.46 | 1710.93 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 0.00 |
July | 13965.88 | 04-JUL-16:41 | 339.11 | 119.38 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 0.00 |
August | 12687.52 | 05-AUG-17:05 | 254.33 | 89.54 | 1817.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.65 |
September | 11577.76 | 04-SEP-17:12 | 0.00 | 74.61 | 1222.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.80 |
October | 4893.78 | 11-OCT-16:00 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 |
November | 3178.87 | 03-NOV-15:30 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 |
December | 1334.17 | 01-DEC-15:50 | 805.38 | 268.64 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1328.18 | 0.00 | 74.61 | 908.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14373.18 | 805.38 | 268.64 | 2422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 | 121.53 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.201650E+12 | 242450.80 | 02-JAN-07:10 | 0.121092E+12 | 167691.45 | 31-JAN-07:40 |
February | 0.148968E+12 | 235789.21 | 06-FEB-07:10 | 0.844803E+11 | 198009.07 | 02-FEB-08:09 |
March | 0.129136E+12 | 204026.80 | 06-MAR-07:10 | 0.537620E+11 | 95119.10 | 06-MAR-07:40 |
April | 0.101067E+12 | 175083.74 | 03-APR-06:10 | 0.261438E+11 | 73683.88 | 03-APR-06:30 |
May | 0.999996E+11 | 126003.26 | 31-MAY-15:09 | 0.106431E+11 | 32950.14 | 02-MAY-06:19 |
June | 0.121467E+12 | 151782.02 | 26-JUN-07:49 | 0.949197E+10 | 14623.87 | 03-JUN-06:10 |
July | 0.130232E+12 | 149430.12 | 03-JUL-15:30 | 0.895194E+10 | 9242.22 | 03-JUL-11:20 |
August | 0.134270E+12 | 157957.40 | 04-AUG-15:30 | 0.933606E+10 | 9161.80 | 01-AUG-11:00 |
September | 0.104018E+12 | 131790.34 | 07-SEP-15:00 | 0.100276E+11 | 39487.09 | 29-SEP-06:49 |
October | 0.952492E+11 | 111017.78 | 16-OCT-06:10 | 0.180109E+11 | 52443.67 | 23-OCT-06:10 |
November | 0.127942E+12 | 225550.89 | 27-NOV-07:10 | 0.485825E+11 | 116387.15 | 28-NOV-07:30 |
December | 0.172107E+12 | 235734.74 | 11-DEC-07:10 | 0.905593E+11 | 135643.07 | 11-DEC-08:50 |
Annual Sum or Average | 0.156610E+13 | 0.491081E+12 | ||||
Minimum of Months | 0.952492E+11 | 111017.78 | 0.895194E+10 | 9161.80 | ||
Maximum of Months | 0.201650E+12 | 242450.80 | 0.121092E+12 | 198009.07 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.175752E+11 | 0.589555E+10 | 0.593559E+11 | 0.980281E+09 | 0.618470E+10 | 1312252.65 | 0.111657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156058E+11 | 0.467974E+10 | 0.537310E+11 | 0.886832E+09 | 0.477577E+10 | 1186778.30 | 0.692874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181551E+11 | 0.432235E+10 | 0.617796E+11 | 0.102605E+10 | 0.478814E+10 | 1343621.24 | 0.389520E+11 | 0.111971E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161019E+11 | 0.341932E+10 | 0.572952E+11 | 0.943608E+09 | 0.526267E+10 | 1267813.82 | 0.143916E+11 | 0.365114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171961E+11 | 0.296853E+10 | 0.605677E+11 | 0.100268E+10 | 0.717750E+10 | 1327936.95 | 0.155808E+10 | 0.952765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.170732E+11 | 0.265938E+10 | 0.594895E+11 | 0.987016E+09 | 0.124488E+11 | 1296568.36 | 0.538927E+09 | 0.282691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160150E+11 | 0.283197E+10 | 0.583622E+11 | 0.959047E+09 | 0.138161E+11 | 1299182.41 | 50152687.25 | 0.381961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178733E+11 | 0.327185E+10 | 0.617796E+11 | 0.102590E+10 | 0.138466E+11 | 1343621.24 | 0.180932E+09 | 0.362906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161673E+11 | 0.380427E+10 | 0.572729E+11 | 0.943401E+09 | 0.892849E+10 | 1267813.82 | 0.177841E+10 | 0.151218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170121E+11 | 0.481185E+10 | 0.593671E+11 | 0.979848E+09 | 0.469501E+10 | 1312252.65 | 0.743811E+10 | 0.943976E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172953E+11 | 0.547250E+10 | 0.580818E+11 | 0.962009E+09 | 0.463090E+10 | 1278270.02 | 0.414627E+11 | 34999646.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.172945E+11 | 0.611896E+10 | 0.583511E+11 | 0.960063E+09 | 0.525500E+10 | 1299182.41 | 0.841259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203365E+12 | 0.502563E+11 | 0.705434E+12 | 0.116567E+11 | 0.918096E+11 | 15535293.87 | 0.371421E+12 | 0.132147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156058E+11 | 0.265938E+10 | 0.537310E+11 | 0.886832E+09 | 0.463090E+10 | 1186778.30 | 50152687.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181551E+11 | 0.611896E+10 | 0.617796E+11 | 0.102605E+10 | 0.138466E+11 | 1343621.24 | 0.111657E+12 | 0.381961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.110648E+12 | 0.00 | 0.104440E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.749116E+11 | 0.00 | 0.956864E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.428137E+11 | 0.00 | 0.109482E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.162757E+11 | 0.00 | 0.986802E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.612978E+09 | 0.00 | 0.100301E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 43570539.23 | 0.00 | 0.944840E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.895194E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.933606E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.129014E+10 | 0.00 | 0.873747E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.871065E+10 | 0.00 | 0.930026E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.391135E+11 | 0.00 | 0.946901E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.806094E+11 | 0.00 | 0.994992E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.375029E+12 | 0.00 | 0.116052E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.873747E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.110648E+12 | 0.00 | 0.109482E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 21377.78 | 02-JAN-16:40 | 5557.43 | 01-JAN-06:10 | 45864.70 | 02-JAN-08:09 | 834.18 | 17-JAN-08:20 | 7319.69 | 02-JAN-07:10 | 0.73 | 02-JAN-06:10 | 201104.60 | 02-JAN-07:10 |
February | 19926.46 | 14-FEB-16:00 | 5557.43 | 01-FEB-06:10 | 45864.70 | 01-FEB-08:09 | 832.58 | 22-FEB-08:20 | 6847.96 | 06-FEB-07:10 | 0.73 | 01-FEB-07:10 | 194914.75 | 06-FEB-07:10 |
March | 18757.77 | 01-MAR-16:00 | 5557.43 | 01-MAR-06:10 | 45864.70 | 01-MAR-08:09 | 830.82 | 14-MAR-07:19 | 5838.49 | 06-MAR-07:10 | 0.73 | 01-MAR-07:10 | 170463.60 | 06-MAR-07:10 |
April | 18320.89 | 10-APR-07:10 | 5557.43 | 01-APR-05:10 | 45864.70 | 03-APR-07:10 | 831.28 | 10-APR-07:19 | 19973.04 | 18-APR-15:20 | 0.73 | 03-APR-06:10 | 142628.10 | 03-APR-06:10 |
May | 17001.50 | 09-MAY-15:30 | 3195.36 | 01-MAY-19:10 | 45864.70 | 01-MAY-07:10 | 829.45 | 25-MAY-07:19 | 22007.93 | 31-MAY-15:09 | 0.73 | 02-MAY-07:10 | 40421.65 | 02-MAY-06:10 |
June | 17420.26 | 13-JUN-07:10 | 3195.36 | 01-JUN-19:40 | 45864.70 | 01-JUN-07:10 | 830.09 | 13-JUN-07:19 | 28700.73 | 26-JUN-15:50 | 0.73 | 01-JUN-05:10 | 14287.22 | 05-JUN-06:10 |
July | 17424.55 | 20-JUL-07:10 | 3195.36 | 01-JUL-19:00 | 45864.70 | 03-JUL-07:10 | 830.10 | 20-JUL-07:19 | 29055.78 | 03-JUL-15:30 | 0.73 | 01-JUL-05:19 | 6157.08 | 24-JUL-06:10 |
August | 17176.06 | 31-AUG-07:10 | 5557.43 | 08-AUG-05:10 | 45864.70 | 01-AUG-07:10 | 829.77 | 31-AUG-07:19 | 25651.01 | 04-AUG-15:30 | 0.73 | 01-AUG-05:30 | 10633.80 | 07-AUG-06:19 |
September | 18317.29 | 21-SEP-07:10 | 5557.43 | 01-SEP-05:10 | 45864.70 | 01-SEP-07:10 | 831.28 | 21-SEP-07:19 | 22542.16 | 07-SEP-15:00 | 0.73 | 18-SEP-16:10 | 53798.22 | 30-SEP-06:10 |
October | 20849.25 | 31-OCT-07:10 | 5557.43 | 01-OCT-05:10 | 45864.70 | 02-OCT-07:10 | 834.63 | 31-OCT-07:19 | 7703.49 | 20-OCT-15:09 | 0.73 | 06-OCT-07:10 | 73470.40 | 16-OCT-06:10 |
November | 21377.78 | 06-NOV-16:00 | 5557.43 | 01-NOV-05:10 | 45864.70 | 01-NOV-07:10 | 835.01 | 03-NOV-07:19 | 6458.30 | 27-NOV-07:10 | 0.73 | 09-NOV-17:10 | 185066.09 | 27-NOV-07:10 |
December | 21377.78 | 01-DEC-16:30 | 5557.43 | 01-DEC-06:10 | 45864.70 | 01-DEC-08:09 | 834.51 | 22-DEC-08:20 | 7018.55 | 11-DEC-07:10 | 0.73 | 01-DEC-07:10 | 194689.68 | 11-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 17001.50 | 3195.36 | 45864.70 | 829.45 | 5838.49 | 0.73 | 6157.08 | |||||||
Maximum of Months | 21377.78 | 5557.43 | 45864.70 | 835.01 | 29055.78 | 0.73 | 201104.60 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5728.73 | 25-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42749.91 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44572.76 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 68912.38 | 26-JUN-07:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 64142.06 | 05-JUL-10:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72586.61 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54456.58 | 06-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17206.57 | 20-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2998.14 | 03-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72586.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 242450.80 | 02-JAN-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 7319.69 | 0.73 | 201104.60 | 0.00 | 0.00 |
February | 235789.21 | 06-FEB-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 6847.96 | 0.73 | 194914.75 | 0.00 | 0.00 |
March | 204026.80 | 06-MAR-07:10 | 6381.74 | 21098.80 | 0.00 | 243.44 | 5838.49 | 0.73 | 170463.60 | 0.00 | 0.00 |
April | 175083.74 | 03-APR-06:10 | 6292.35 | 21098.80 | 0.00 | 243.43 | 4820.32 | 0.73 | 142628.10 | 0.00 | 0.00 |
May | 126003.26 | 31-MAY-15:09 | 16818.70 | 42072.41 | 0.00 | 827.95 | 22007.93 | 0.73 | 0.00 | 44275.54 | 0.00 |
June | 151782.02 | 26-JUN-07:49 | 16818.70 | 45864.70 | 0.00 | 829.30 | 19356.21 | 0.73 | 0.00 | 68912.38 | 0.00 |
July | 149430.12 | 03-JUL-15:30 | 16818.70 | 42072.41 | 0.00 | 827.95 | 29055.78 | 0.73 | 0.00 | 60654.56 | 0.00 |
August | 157957.40 | 04-AUG-15:30 | 16818.70 | 42072.41 | 0.00 | 827.95 | 25651.01 | 0.73 | 0.00 | 72586.61 | 0.00 |
September | 131790.34 | 07-SEP-15:00 | 16818.70 | 42072.41 | 0.00 | 827.95 | 22542.16 | 0.73 | 0.00 | 49528.39 | 0.00 |
October | 111017.78 | 16-OCT-06:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 3520.88 | 0.73 | 73470.40 | 0.00 | 0.00 |
November | 225550.89 | 27-NOV-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 6458.30 | 0.73 | 185066.09 | 0.00 | 0.00 |
December | 235734.74 | 11-DEC-07:10 | 7126.03 | 21098.80 | 5557.43 | 243.52 | 7018.55 | 0.73 | 194689.68 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 111017.78 | 6292.35 | 21098.80 | 0.00 | 243.43 | 3520.88 | 0.73 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 242450.80 | 16818.70 | 45864.70 | 5557.43 | 829.30 | 29055.78 | 0.73 | 201104.60 | 72586.61 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 159447.99 | 31-JAN-07:40 | 0.00 | 11937.89 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 190421.08 | 02-FEB-07:30 | 0.00 | 12041.65 | 17-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 86889.79 | 06-MAR-07:40 | 0.00 | 11992.23 | 03-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 65669.08 | 03-APR-06:40 | 0.00 | 11215.55 | 05-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 24754.76 | 02-MAY-06:19 | 0.00 | 10007.77 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 6682.48 | 03-JUN-06:10 | 0.00 | 9394.59 | 01-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 9242.22 | 03-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 9161.80 | 01-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 32426.52 | 29-SEP-06:19 | 0.00 | 9207.19 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 44297.27 | 23-OCT-06:10 | 0.00 | 9350.95 | 31-OCT-11:09 | 0.00 |
November | 0.00 | 0.00 | 108899.14 | 25-NOV-17:00 | 0.00 | 9513.07 | 30-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 129731.77 | 09-DEC-07:30 | 0.00 | 10848.28 | 27-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9161.80 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 190421.08 | 0.00 | 12041.65 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.69 | 0.67 | 19.69 | 0.00 | 19.69 | 0.00 | 19.69 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.09 | 0.33 | 25.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 19.69 | 0.67 | 19.69 | 0.50 | 21.26 | 0.33 | 21.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.69 | 0.67 | 19.69 | 0.33 | 26.17 | 0.33 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.12 | 1.83 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.17 | 19.13 | 0.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.19 | 0.17 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
December | 0.50 | 18.34 | 0.33 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
Annual Sum or Average | 3.00 | 19.00 | 2.50 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.19 | 1.83 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.33 | 18.74 | 6.17 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
February | 3.33 | 18.50 | 2.17 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
March | 0.50 | 18.47 | 0.33 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
April | 0.33 | 17.98 | 0.17 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 19.19 | 1.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
December | 4.00 | 18.76 | 3.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
Annual Sum or Average | 18.17 | 18.72 | 13.33 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.33 | 19.19 | 6.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 111.33 | 16.73 | 62.17 | 17.25 | 0.00 | 17.25 | 0.00 | 17.25 |
February | 56.17 | 16.96 | 32.17 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
March | 13.33 | 16.76 | 5.33 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
April | 2.83 | 16.91 | 1.00 | 17.62 | 0.00 | 17.62 | 0.00 | 17.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.42 | 1.67 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.00 | 27.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24.33 | 16.59 | 12.33 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
December | 55.50 | 16.58 | 29.50 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
Annual Sum or Average | 263.50 | 16.74 | 142.50 | 17.25 | 3.17 | 17.33 | 1.67 | 17.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 111.33 | 16.96 | 62.17 | 17.62 | 2.83 | 27.42 | 1.67 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.67 | 14.89 | 13.83 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
February | 25.50 | 14.94 | 4.83 | 15.08 | 0.00 | 15.08 | 0.00 | 15.08 |
March | 7.67 | 15.43 | 0.33 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
April | 1.83 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.55 | 2.50 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.01 | 5.50 | 28.03 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.99 | 7.17 | 27.99 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.80 | 1.67 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.65 | 2.50 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15.33 | 14.91 | 3.50 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
December | 32.67 | 14.97 | 8.67 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
Annual Sum or Average | 141.67 | 14.95 | 31.17 | 15.05 | 19.67 | 16.36 | 19.33 | 17.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.67 | 15.43 | 13.83 | 15.50 | 7.17 | 28.01 | 7.17 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.17 | 15.46 | 14.50 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
February | 24.33 | 15.88 | 7.00 | 16.43 | 0.00 | 16.43 | 0.00 | 16.43 |
March | 5.83 | 15.73 | 0.67 | 15.87 | 0.00 | 15.87 | 0.00 | 15.87 |
April | 1.67 | 15.73 | 0.17 | 16.06 | 1.83 | 21.94 | 1.67 | 23.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.45 | 0.67 | 27.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.78 | 4.00 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.81 | 4.83 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.60 | 4.00 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.93 | 4.83 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.45 | 0.50 | 27.45 |
November | 14.67 | 15.33 | 4.17 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
December | 29.17 | 15.48 | 7.00 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
Annual Sum or Average | 130.83 | 15.54 | 33.50 | 15.89 | 21.67 | 17.28 | 20.50 | 18.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.53 | 0.00 | 15.53 |
Maximum of Months | 55.17 | 15.88 | 14.50 | 16.43 | 5.17 | 27.93 | 4.83 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.50 | 14.81 | 14.50 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
February | 24.17 | 14.83 | 4.83 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
March | 7.67 | 15.42 | 1.17 | 15.44 | 0.00 | 15.44 | 0.00 | 15.44 |
April | 1.83 | 15.20 | 0.00 | 15.20 | 1.50 | 21.14 | 0.83 | 22.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.92 | 1.67 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.45 | 3.17 | 28.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.25 | 4.83 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.96 | 2.17 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.96 | 2.50 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15.33 | 14.86 | 3.67 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
December | 32.83 | 14.85 | 9.00 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
Annual Sum or Average | 140.33 | 14.87 | 33.17 | 14.91 | 27.00 | 16.70 | 15.17 | 17.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 58.50 | 15.42 | 14.50 | 15.44 | 10.00 | 28.45 | 4.83 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 79.50 | 18.52 | 62.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
February | 59.67 | 18.68 | 47.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
March | 6.00 | 18.72 | 4.67 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
April | 0.50 | 18.87 | 0.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.50 | 19.06 | 4.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 22.67 | 18.73 | 17.67 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
Annual Sum or Average | 173.83 | 18.63 | 136.67 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 79.50 | 19.06 | 62.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.83 | 15.62 | 2.67 | 15.80 | 0.00 | 15.80 | 0.00 | 15.80 |
February | 8.50 | 15.55 | 0.83 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
March | 0.67 | 17.21 | 0.17 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
April | 0.17 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.70 | 2.50 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.69 | 4.33 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.65 | 1.17 | 26.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.49 | 2.17 | 27.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 17.24 | 0.17 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
December | 5.00 | 15.52 | 0.50 | 15.60 | 0.00 | 15.60 | 0.00 | 15.60 |
Annual Sum or Average | 32.17 | 15.68 | 4.33 | 15.85 | 10.17 | 18.39 | 10.17 | 20.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.83 | 17.24 | 2.67 | 17.63 | 4.33 | 27.70 | 4.33 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 211.83 | 15.51 | 199.33 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
February | 130.50 | 15.44 | 124.50 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
March | 86.83 | 16.47 | 86.17 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
April | 50.33 | 17.62 | 50.17 | 17.62 | 0.00 | 17.62 | 0.00 | 17.62 |
May | 13.33 | 19.27 | 13.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
June | 2.33 | 19.67 | 2.33 | 19.67 | 2.50 | 21.66 | 2.50 | 22.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.50 | 2.00 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.58 | 3.33 | 25.58 |
September | 9.33 | 18.97 | 9.33 | 18.97 | 19.00 | 22.32 | 19.00 | 23.42 |
October | 30.67 | 18.57 | 30.67 | 18.57 | 0.50 | 18.64 | 0.50 | 18.71 |
November | 72.33 | 16.59 | 71.67 | 16.59 | 0.00 | 16.59 | 0.00 | 16.59 |
December | 135.17 | 15.86 | 132.17 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
Annual Sum or Average | 742.67 | 16.17 | 719.67 | 16.18 | 27.33 | 16.36 | 27.33 | 16.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.45 | 0.00 | 15.45 |
Maximum of Months | 211.83 | 19.67 | 199.33 | 19.67 | 19.00 | 27.50 | 19.00 | 27.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.50 | 15.56 | 2.83 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
February | 7.50 | 15.56 | 1.17 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
March | 0.67 | 17.27 | 0.17 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 |
April | 0.17 | 17.01 | 0.00 | 17.01 | 0.67 | 25.50 | 0.50 | 26.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.47 | 0.00 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.90 | 2.17 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.85 | 3.17 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.65 | 1.17 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.61 | 2.33 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
December | 5.50 | 15.46 | 0.83 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
Annual Sum or Average | 31.17 | 15.62 | 5.00 | 15.73 | 17.00 | 19.58 | 9.33 | 20.80 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.50 | 17.27 | 2.83 | 17.69 | 7.33 | 27.90 | 3.17 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.83 | 17.67 | 35.17 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 |
February | 30.00 | 17.69 | 19.00 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
March | 3.33 | 17.99 | 2.00 | 18.58 | 0.00 | 18.58 | 0.00 | 18.58 |
April | 0.50 | 18.57 | 0.33 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.17 | 16.89 | 5.67 | 17.42 | 0.00 | 17.42 | 0.00 | 17.42 |
December | 24.33 | 17.21 | 14.83 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
Annual Sum or Average | 124.17 | 17.53 | 77.00 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 54.83 | 18.57 | 35.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.50 | 15.19 | 2.67 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
February | 11.00 | 15.21 | 0.83 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
March | 1.00 | 15.87 | 0.00 | 15.87 | 0.00 | 15.87 | 0.00 | 15.87 |
April | 0.17 | 16.97 | 0.00 | 16.97 | 0.33 | 23.83 | 0.33 | 25.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.64 | 3.17 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.85 | 5.33 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.02 | 5.67 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.77 | 2.00 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.83 | 2.50 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.50 | 15.22 | 1.17 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
December | 10.67 | 15.18 | 1.50 | 15.14 | 0.00 | 15.14 | 0.00 | 15.14 |
Annual Sum or Average | 49.83 | 15.21 | 6.17 | 15.24 | 19.00 | 18.43 | 19.00 | 20.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.50 | 16.97 | 2.67 | 16.97 | 5.67 | 28.02 | 5.67 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.33 | 15.92 | 3.67 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
February | 6.83 | 15.77 | 1.17 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
March | 0.33 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
April | 0.17 | 17.05 | 0.00 | 17.05 | 1.67 | 26.70 | 1.67 | 27.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.41 | 0.33 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.63 | 3.50 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.70 | 4.00 | 27.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.55 | 3.33 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.85 | 5.00 | 27.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.51 | 1.33 | 27.51 |
November | 5.50 | 15.50 | 0.83 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
December | 8.33 | 15.65 | 1.67 | 15.90 | 0.00 | 15.90 | 0.00 | 15.90 |
Annual Sum or Average | 38.50 | 15.79 | 7.33 | 16.07 | 19.17 | 19.49 | 19.17 | 21.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.65 | 0.00 | 15.65 |
Maximum of Months | 17.33 | 17.05 | 3.67 | 17.05 | 5.00 | 27.85 | 5.00 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.50 | 15.18 | 3.50 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
February | 10.83 | 15.27 | 1.17 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
March | 0.83 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
April | 0.17 | 16.95 | 0.00 | 16.95 | 1.50 | 27.00 | 0.83 | 27.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.84 | 1.83 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.27 | 2.83 | 28.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.12 | 4.33 | 28.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.92 | 1.83 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.81 | 2.67 | 27.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.83 | 15.20 | 1.50 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
December | 12.50 | 15.12 | 2.83 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
Annual Sum or Average | 52.67 | 15.21 | 9.00 | 15.21 | 25.33 | 18.95 | 14.33 | 20.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.50 | 16.95 | 3.50 | 16.95 | 9.33 | 28.27 | 4.33 | 28.28 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.39 | 286.67 | 21.15 | 286.67 | 21.04 |
February | 454.00 | 22.13 | 89.83 | 21.91 | 89.83 | 21.75 |
March | 505.50 | 23.05 | 8.17 | 23.01 | 8.17 | 22.98 |
April | 378.17 | 23.51 | 36.67 | 23.60 | 0.00 | 23.60 |
May | 74.17 | 23.88 | 268.17 | 24.38 | 0.00 | 24.38 |
June | 1.00 | 23.69 | 421.00 | 24.36 | 0.00 | 24.36 |
July | 0.00 | 0.00 | 490.17 | 24.41 | 0.00 | 24.41 |
August | 0.50 | 24.80 | 502.17 | 24.35 | 0.50 | 24.35 |
September | 62.83 | 23.85 | 257.83 | 24.44 | 0.00 | 24.44 |
October | 374.50 | 23.88 | 19.17 | 23.93 | 0.00 | 23.93 |
November | 410.83 | 23.01 | 43.33 | 22.85 | 38.50 | 22.70 |
December | 497.00 | 22.09 | 103.00 | 21.88 | 103.00 | 21.74 |
Annual Sum or Average | 3260.50 | 22.70 | 2526.17 | 23.12 | 526.67 | 22.93 |
Minimum of Months | 0.00 | 0.00 | 8.17 | 21.15 | 0.00 | 21.04 |
Maximum of Months | 505.50 | 24.80 | 502.17 | 24.44 | 286.67 | 24.44 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.46 | 464.00 | 20.41 | 464.00 | 20.40 |
February | 454.00 | 20.87 | 308.83 | 20.75 | 308.83 | 20.69 |
March | 514.00 | 21.71 | 159.17 | 21.49 | 159.17 | 21.35 |
April | 417.67 | 22.34 | 60.00 | 22.31 | 37.83 | 22.20 |
May | 199.67 | 23.35 | 160.67 | 23.74 | 0.00 | 23.74 |
June | 43.83 | 23.28 | 341.67 | 24.13 | 0.00 | 24.13 |
July | 0.00 | 0.00 | 462.67 | 24.28 | 0.00 | 24.28 |
August | 0.67 | 24.14 | 455.00 | 24.22 | 0.67 | 24.22 |
September | 169.50 | 23.31 | 168.17 | 23.84 | 0.00 | 23.84 |
October | 497.33 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
November | 489.00 | 21.66 | 182.83 | 21.38 | 182.83 | 21.21 |
December | 497.00 | 20.74 | 395.17 | 20.64 | 395.17 | 20.60 |
Annual Sum or Average | 3784.67 | 21.69 | 3158.17 | 22.03 | 1548.50 | 21.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 20.41 | 0.00 | 20.40 |
Maximum of Months | 514.00 | 24.14 | 464.00 | 24.28 | 464.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 486.33 | 20.04 | 486.33 | 20.03 |
February | 454.00 | 20.37 | 385.50 | 20.29 | 385.50 | 20.26 |
March | 514.00 | 21.14 | 273.67 | 20.93 | 273.67 | 20.83 |
April | 424.00 | 21.76 | 125.50 | 21.60 | 101.83 | 21.41 |
May | 266.83 | 23.09 | 130.33 | 23.43 | 0.00 | 23.43 |
June | 91.17 | 23.03 | 322.33 | 23.96 | 0.00 | 23.96 |
July | 17.00 | 23.40 | 433.33 | 24.23 | 0.00 | 24.23 |
August | 28.83 | 23.34 | 401.67 | 24.13 | 3.00 | 24.13 |
September | 237.67 | 22.75 | 140.50 | 23.27 | 5.50 | 23.23 |
October | 502.00 | 21.81 | 82.83 | 21.64 | 82.83 | 21.50 |
November | 489.00 | 20.84 | 290.17 | 20.59 | 290.17 | 20.47 |
December | 497.00 | 20.20 | 475.00 | 20.17 | 475.00 | 20.16 |
Annual Sum or Average | 4023.50 | 21.21 | 3547.17 | 21.51 | 2103.83 | 21.22 |
Minimum of Months | 17.00 | 20.06 | 82.83 | 20.04 | 0.00 | 20.03 |
Maximum of Months | 514.00 | 23.40 | 486.33 | 24.23 | 486.33 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.51 | 502.00 | 19.51 | 502.00 | 19.51 |
February | 454.00 | 19.73 | 442.67 | 19.71 | 442.67 | 19.71 |
March | 514.00 | 20.51 | 387.17 | 20.38 | 387.17 | 20.33 |
April | 430.17 | 21.00 | 231.17 | 20.87 | 200.33 | 20.68 |
May | 287.17 | 22.58 | 151.33 | 23.04 | 11.33 | 22.98 |
June | 117.50 | 23.06 | 328.17 | 23.99 | 18.50 | 24.06 |
July | 48.33 | 23.91 | 431.83 | 24.29 | 19.17 | 24.33 |
August | 80.33 | 23.23 | 378.17 | 24.01 | 17.33 | 24.02 |
September | 287.33 | 22.15 | 174.33 | 22.68 | 34.67 | 22.53 |
October | 502.00 | 20.94 | 227.33 | 20.70 | 227.33 | 20.57 |
November | 489.00 | 20.09 | 361.83 | 19.90 | 361.83 | 19.82 |
December | 497.00 | 19.65 | 497.00 | 19.65 | 497.00 | 19.65 |
Annual Sum or Average | 4208.83 | 20.67 | 4113.00 | 21.02 | 2719.33 | 20.75 |
Minimum of Months | 48.33 | 19.51 | 151.33 | 19.51 | 11.33 | 19.51 |
Maximum of Months | 514.00 | 23.91 | 502.00 | 24.29 | 502.00 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.65 | 495.67 | 19.65 | 495.67 | 19.64 |
February | 454.00 | 19.90 | 417.17 | 19.84 | 417.17 | 19.82 |
March | 511.50 | 20.73 | 323.00 | 20.51 | 323.00 | 20.41 |
April | 397.67 | 21.24 | 211.83 | 21.23 | 160.67 | 21.00 |
May | 231.33 | 22.78 | 210.17 | 23.54 | 17.67 | 23.59 |
June | 128.83 | 23.39 | 355.33 | 24.13 | 31.17 | 24.28 |
July | 68.00 | 25.31 | 448.83 | 24.56 | 48.17 | 24.71 |
August | 78.33 | 23.68 | 409.00 | 24.14 | 26.33 | 24.20 |
September | 245.50 | 22.28 | 214.00 | 23.12 | 32.17 | 23.07 |
October | 496.17 | 21.21 | 157.33 | 20.96 | 157.33 | 20.81 |
November | 489.00 | 20.19 | 348.17 | 20.01 | 348.17 | 19.93 |
December | 497.00 | 19.76 | 497.00 | 19.76 | 497.00 | 19.76 |
Annual Sum or Average | 4099.33 | 20.86 | 4087.50 | 21.28 | 2554.50 | 21.01 |
Minimum of Months | 68.00 | 19.65 | 157.33 | 19.65 | 17.67 | 19.64 |
Maximum of Months | 511.50 | 25.31 | 497.00 | 24.56 | 497.00 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.83 | 19.98 | 429.83 | 19.79 | 429.83 | 19.72 |
February | 440.83 | 20.34 | 344.83 | 20.11 | 341.83 | 20.01 |
March | 469.33 | 20.95 | 292.00 | 20.73 | 282.33 | 20.59 |
April | 368.50 | 21.26 | 224.83 | 21.33 | 162.33 | 21.11 |
May | 243.33 | 22.55 | 194.33 | 23.30 | 14.33 | 23.27 |
June | 138.00 | 23.16 | 324.00 | 23.99 | 24.17 | 24.10 |
July | 75.50 | 24.35 | 422.67 | 24.40 | 34.33 | 24.51 |
August | 95.33 | 23.82 | 397.00 | 24.20 | 34.00 | 24.29 |
September | 238.00 | 22.57 | 230.83 | 23.37 | 42.17 | 23.37 |
October | 401.33 | 21.44 | 174.00 | 21.44 | 129.33 | 21.23 |
November | 469.83 | 20.58 | 299.17 | 20.33 | 287.50 | 20.17 |
December | 488.33 | 20.21 | 417.67 | 20.01 | 417.67 | 19.93 |
Annual Sum or Average | 3926.17 | 21.11 | 3751.17 | 21.49 | 2199.83 | 21.20 |
Minimum of Months | 75.50 | 19.98 | 174.00 | 19.79 | 14.33 | 19.72 |
Maximum of Months | 497.83 | 24.35 | 429.83 | 24.40 | 429.83 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.67 | 493.33 | 19.65 | 493.33 | 19.65 |
February | 452.17 | 19.98 | 413.00 | 19.91 | 413.00 | 19.88 |
March | 500.67 | 20.65 | 348.67 | 20.48 | 347.33 | 20.41 |
April | 390.17 | 21.08 | 227.17 | 21.11 | 175.83 | 20.91 |
May | 293.50 | 22.41 | 167.00 | 23.04 | 19.83 | 23.03 |
June | 148.33 | 22.92 | 336.00 | 23.91 | 24.00 | 24.01 |
July | 89.50 | 24.26 | 412.67 | 24.39 | 39.67 | 24.52 |
August | 110.00 | 23.32 | 391.50 | 24.04 | 29.67 | 24.11 |
September | 290.00 | 22.16 | 199.17 | 22.86 | 46.00 | 22.83 |
October | 469.50 | 21.00 | 208.33 | 20.81 | 196.83 | 20.66 |
November | 483.67 | 20.14 | 344.17 | 19.96 | 343.83 | 19.88 |
December | 497.00 | 19.76 | 484.00 | 19.74 | 484.00 | 19.73 |
Annual Sum or Average | 4226.50 | 20.83 | 4025.00 | 21.19 | 2613.33 | 20.94 |
Minimum of Months | 89.50 | 19.67 | 167.00 | 19.65 | 19.83 | 19.65 |
Maximum of Months | 502.00 | 24.26 | 493.33 | 24.39 | 493.33 | 24.52 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.60 | 502.00 | 19.60 | 502.00 | 19.60 |
February | 454.00 | 19.91 | 450.33 | 19.90 | 450.33 | 19.90 |
March | 514.00 | 20.52 | 408.67 | 20.44 | 408.67 | 20.41 |
April | 473.17 | 21.03 | 245.67 | 20.84 | 239.67 | 20.72 |
May | 424.33 | 22.54 | 66.50 | 22.66 | 20.00 | 22.62 |
June | 135.17 | 22.93 | 268.17 | 23.77 | 7.33 | 23.78 |
July | 27.33 | 23.71 | 425.00 | 24.20 | 6.83 | 24.21 |
August | 41.17 | 23.52 | 406.67 | 24.09 | 10.33 | 24.10 |
September | 245.33 | 22.74 | 146.50 | 23.27 | 3.50 | 23.25 |
October | 502.00 | 21.70 | 69.83 | 21.57 | 69.83 | 21.47 |
November | 489.00 | 20.72 | 296.50 | 20.48 | 296.50 | 20.37 |
December | 497.00 | 19.95 | 497.00 | 19.95 | 497.00 | 19.95 |
Annual Sum or Average | 4304.50 | 20.95 | 3782.83 | 21.19 | 2512.00 | 20.92 |
Minimum of Months | 27.33 | 19.60 | 66.50 | 19.60 | 3.50 | 19.60 |
Maximum of Months | 514.00 | 23.71 | 502.00 | 24.20 | 502.00 | 24.21 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.81 | 497.83 | 19.81 | 497.83 | 19.80 |
February | 454.00 | 20.14 | 428.67 | 20.10 | 428.67 | 20.09 |
March | 514.00 | 20.79 | 344.50 | 20.62 | 344.50 | 20.55 |
April | 434.67 | 21.38 | 187.50 | 21.24 | 158.67 | 21.05 |
May | 269.17 | 22.78 | 152.00 | 23.46 | 2.50 | 23.46 |
June | 111.83 | 23.30 | 355.67 | 24.12 | 19.17 | 24.19 |
July | 33.67 | 25.97 | 470.33 | 24.56 | 26.83 | 24.67 |
August | 26.33 | 24.65 | 465.00 | 24.30 | 16.67 | 24.34 |
September | 187.83 | 23.03 | 224.50 | 23.85 | 8.67 | 23.89 |
October | 487.83 | 22.22 | 24.50 | 22.14 | 24.50 | 22.07 |
November | 489.00 | 20.87 | 280.67 | 20.62 | 280.67 | 20.51 |
December | 497.00 | 20.06 | 495.00 | 20.06 | 495.00 | 20.06 |
Annual Sum or Average | 4007.33 | 21.13 | 3926.17 | 21.54 | 2303.67 | 21.26 |
Minimum of Months | 26.33 | 19.81 | 24.50 | 19.81 | 2.50 | 19.80 |
Maximum of Months | 514.00 | 25.97 | 497.83 | 24.56 | 497.83 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 17.81 | 489.17 | 17.77 | 489.17 | 17.76 |
February | 454.00 | 18.90 | 399.17 | 18.73 | 399.17 | 18.66 |
March | 507.00 | 20.07 | 345.00 | 19.78 | 345.00 | 19.66 |
April | 433.00 | 20.77 | 237.17 | 20.63 | 204.83 | 20.42 |
May | 392.83 | 22.09 | 95.50 | 22.46 | 19.50 | 22.39 |
June | 214.00 | 22.59 | 270.67 | 23.51 | 58.00 | 23.53 |
July | 140.50 | 23.66 | 425.83 | 24.17 | 102.83 | 24.16 |
August | 127.33 | 23.50 | 446.67 | 24.12 | 90.83 | 24.11 |
September | 220.67 | 22.46 | 233.67 | 23.54 | 27.50 | 23.58 |
October | 421.67 | 21.78 | 78.17 | 21.83 | 39.83 | 21.63 |
November | 462.00 | 20.17 | 280.00 | 19.88 | 267.50 | 19.68 |
December | 493.83 | 18.93 | 439.17 | 18.79 | 437.83 | 18.73 |
Annual Sum or Average | 4368.83 | 20.45 | 3740.17 | 20.72 | 2482.00 | 20.39 |
Minimum of Months | 127.33 | 17.81 | 78.17 | 17.77 | 19.50 | 17.76 |
Maximum of Months | 507.00 | 23.66 | 489.17 | 24.17 | 489.17 | 24.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.81 | 494.50 | 19.80 | 494.50 | 19.80 |
February | 454.00 | 20.20 | 423.50 | 20.15 | 423.50 | 20.13 |
March | 514.00 | 20.77 | 356.67 | 20.61 | 356.67 | 20.55 |
April | 426.00 | 21.34 | 188.67 | 21.24 | 158.83 | 21.05 |
May | 340.33 | 22.58 | 108.67 | 23.00 | 9.17 | 22.96 |
June | 121.33 | 23.04 | 337.17 | 24.00 | 14.50 | 24.06 |
July | 34.00 | 25.77 | 455.83 | 24.55 | 24.67 | 24.66 |
August | 27.83 | 24.36 | 465.33 | 24.30 | 12.00 | 24.33 |
September | 208.33 | 22.87 | 219.83 | 23.68 | 13.83 | 23.72 |
October | 467.00 | 21.99 | 47.50 | 21.94 | 35.67 | 21.86 |
November | 483.17 | 20.82 | 273.33 | 20.57 | 272.67 | 20.45 |
December | 497.00 | 20.07 | 482.67 | 20.05 | 482.67 | 20.04 |
Annual Sum or Average | 4075.00 | 21.10 | 3853.67 | 21.49 | 2298.67 | 21.21 |
Minimum of Months | 27.83 | 19.81 | 47.50 | 19.80 | 9.17 | 19.80 |
Maximum of Months | 514.00 | 25.77 | 494.50 | 24.55 | 494.50 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.66 | 497.67 | 19.66 | 497.67 | 19.65 |
February | 454.00 | 20.01 | 429.17 | 19.98 | 429.17 | 19.97 |
March | 514.00 | 20.80 | 334.83 | 20.62 | 334.83 | 20.54 |
April | 423.00 | 21.42 | 174.50 | 21.32 | 140.67 | 21.13 |
May | 242.00 | 22.98 | 163.00 | 23.45 | 1.83 | 23.44 |
June | 70.67 | 23.11 | 360.67 | 24.12 | 4.17 | 24.14 |
July | 10.67 | 24.49 | 463.17 | 24.36 | 7.33 | 24.36 |
August | 35.83 | 23.72 | 431.00 | 24.17 | 13.00 | 24.18 |
September | 235.33 | 22.63 | 166.83 | 23.28 | 5.83 | 23.24 |
October | 499.00 | 21.60 | 110.67 | 21.39 | 110.67 | 21.25 |
November | 489.00 | 20.60 | 307.50 | 20.34 | 307.50 | 20.23 |
December | 497.00 | 19.89 | 497.00 | 19.89 | 497.00 | 19.89 |
Annual Sum or Average | 3972.50 | 20.91 | 3936.00 | 21.32 | 2349.67 | 21.03 |
Minimum of Months | 10.67 | 19.66 | 110.67 | 19.66 | 1.83 | 19.65 |
Maximum of Months | 514.00 | 24.49 | 497.67 | 24.36 | 497.67 | 24.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.56 | 417.17 | 19.55 | 417.17 | 19.54 |
February | 385.00 | 20.01 | 353.33 | 19.95 | 353.33 | 19.93 |
March | 428.67 | 20.89 | 251.00 | 20.66 | 251.00 | 20.56 |
April | 327.83 | 21.42 | 151.50 | 21.48 | 105.67 | 21.26 |
May | 195.83 | 23.12 | 169.33 | 23.82 | 14.83 | 23.92 |
June | 92.50 | 23.79 | 303.50 | 24.33 | 25.67 | 24.47 |
July | 44.50 | 26.02 | 395.17 | 24.68 | 37.00 | 24.83 |
August | 46.50 | 24.20 | 360.67 | 24.29 | 19.67 | 24.35 |
September | 195.17 | 22.69 | 172.50 | 23.56 | 15.17 | 23.62 |
October | 421.33 | 21.68 | 72.83 | 21.51 | 71.67 | 21.37 |
November | 417.00 | 20.50 | 270.67 | 20.28 | 270.67 | 20.19 |
December | 422.00 | 19.79 | 420.00 | 19.79 | 420.00 | 19.79 |
Annual Sum or Average | 3403.33 | 21.01 | 3337.67 | 21.44 | 2001.83 | 21.17 |
Minimum of Months | 44.50 | 19.56 | 72.83 | 19.55 | 14.83 | 19.54 |
Maximum of Months | 428.67 | 26.02 | 420.00 | 24.68 | 420.00 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.83 | 20.25 | 409.00 | 20.03 | 409.00 | 19.95 |
February | 438.50 | 20.75 | 305.67 | 20.46 | 303.50 | 20.34 |
March | 462.67 | 21.33 | 243.33 | 21.08 | 233.17 | 20.91 |
April | 358.17 | 21.70 | 177.83 | 21.85 | 108.33 | 21.64 |
May | 198.17 | 22.95 | 206.17 | 23.68 | 4.83 | 23.69 |
June | 97.67 | 23.64 | 351.00 | 24.20 | 18.67 | 24.30 |
July | 41.17 | 25.30 | 461.00 | 24.50 | 26.83 | 24.59 |
August | 52.50 | 24.59 | 451.83 | 24.34 | 27.83 | 24.42 |
September | 197.00 | 23.16 | 236.50 | 23.92 | 23.67 | 24.02 |
October | 380.67 | 22.13 | 100.33 | 22.31 | 44.67 | 22.17 |
November | 455.67 | 21.06 | 252.83 | 20.83 | 232.17 | 20.62 |
December | 482.17 | 20.50 | 396.33 | 20.30 | 393.50 | 20.21 |
Annual Sum or Average | 3659.17 | 21.43 | 3591.83 | 21.88 | 1826.17 | 21.58 |
Minimum of Months | 41.17 | 20.25 | 100.33 | 20.03 | 4.83 | 19.95 |
Maximum of Months | 494.83 | 25.30 | 461.00 | 24.50 | 409.00 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 489.50 | 19.77 | 489.50 | 19.76 |
February | 452.00 | 20.24 | 396.50 | 20.15 | 396.50 | 20.11 |
March | 497.67 | 20.92 | 298.67 | 20.73 | 297.50 | 20.63 |
April | 383.33 | 21.47 | 178.83 | 21.56 | 123.33 | 21.37 |
May | 247.50 | 22.80 | 183.00 | 23.45 | 9.83 | 23.49 |
June | 107.67 | 23.34 | 360.33 | 24.13 | 18.67 | 24.22 |
July | 50.33 | 25.28 | 448.33 | 24.52 | 32.00 | 24.64 |
August | 58.83 | 23.95 | 435.67 | 24.24 | 23.17 | 24.29 |
September | 248.33 | 22.63 | 200.50 | 23.39 | 23.50 | 23.43 |
October | 456.67 | 21.53 | 106.50 | 21.42 | 92.83 | 21.29 |
November | 481.83 | 20.59 | 297.33 | 20.37 | 296.17 | 20.27 |
December | 497.00 | 19.99 | 473.67 | 19.95 | 473.67 | 19.94 |
Annual Sum or Average | 3983.17 | 21.06 | 3868.83 | 21.49 | 2276.67 | 21.22 |
Minimum of Months | 50.33 | 19.79 | 106.50 | 19.77 | 9.83 | 19.76 |
Maximum of Months | 502.00 | 25.28 | 489.50 | 24.52 | 489.50 | 24.64 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.39066 | 14.17454 | -0.5605 | 12.89481 |
February | 454.00000 | 22.13165 | 17.88085 | -0.3479 | 8.80237 |
March | 514.00000 | 23.06621 | 22.56700 | -0.0749 | 6.19054 |
April | 485.00000 | 23.67278 | 28.79108 | 0.14468 | 6.29289 |
May | 508.00000 | 24.29550 | 40.89359 | -0.4600 | 10.09871 |
June | 496.00000 | 24.30747 | 47.62756 | -0.3569 | 8.05845 |
July | 497.00000 | 24.40978 | 51.83639 | -0.2818 | 7.11151 |
August | 514.00000 | 24.34439 | 50.89973 | -0.3071 | 7.36226 |
September | 485.00000 | 24.31794 | 37.50474 | -0.4392 | 9.77434 |
October | 502.00000 | 23.99730 | 27.54836 | 0.22551 | 6.28694 |
November | 489.00000 | 23.19347 | 24.26917 | -0.0233 | 6.98218 |
December | 497.00000 | 22.08790 | 16.28477 | -0.3668 | 8.84391 |
Annual Sum or Average | 5943.00000 | 23.44382 | 31.81882 | -0.2372 | 8.22068 |
Minimum of Months | 454.00000 | 21.39066 | 14.17454 | -0.5605 | 6.19054 |
Maximum of Months | 514.00000 | 24.40978 | 51.83639 | 0.22551 | 12.89481 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.45893 | 14.94772 | -0.7845 | 19.29190 |
February | 454.00000 | 20.87407 | 19.07799 | -0.6373 | 14.61325 |
March | 514.00000 | 21.70775 | 24.49943 | -0.3784 | 9.30404 |
April | 485.00000 | 22.58443 | 31.34032 | -0.0944 | 7.19071 |
May | 508.00000 | 23.80475 | 42.88387 | -0.6203 | 13.99925 |
June | 496.00000 | 24.09780 | 49.16872 | -0.4406 | 9.62062 |
July | 497.00000 | 24.24719 | 52.96219 | -0.3505 | 7.88035 |
August | 514.00000 | 24.19125 | 52.08649 | -0.3805 | 8.29119 |
September | 485.00000 | 23.89305 | 39.38634 | -0.6012 | 14.10542 |
October | 502.00000 | 22.77888 | 30.67581 | -0.0575 | 5.76782 |
November | 489.00000 | 21.66304 | 26.68328 | -0.3783 | 10.49875 |
December | 497.00000 | 20.73602 | 17.37667 | -0.6841 | 15.89202 |
Annual Sum or Average | 5943.00000 | 22.59988 | 33.55397 | -0.4497 | 11.34430 |
Minimum of Months | 454.00000 | 20.45893 | 14.94772 | -0.7845 | 5.76782 |
Maximum of Months | 514.00000 | 24.24719 | 52.96219 | -0.0575 | 19.29190 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.05816 | 15.25496 | -0.9140 | 24.68408 |
February | 454.00000 | 20.37353 | 19.68106 | -0.7876 | 19.87310 |
March | 514.00000 | 21.14468 | 25.07763 | -0.5326 | 12.53721 |
April | 485.00000 | 22.04444 | 32.15207 | -0.2293 | 9.20186 |
May | 508.00000 | 23.54162 | 43.44192 | -0.7064 | 17.09442 |
June | 496.00000 | 23.95332 | 49.66475 | -0.4811 | 11.04380 |
July | 497.00000 | 24.17891 | 53.36437 | -0.3652 | 8.20368 |
August | 514.00000 | 24.06950 | 52.56257 | -0.4175 | 9.02270 |
September | 485.00000 | 23.45779 | 40.32970 | -0.7530 | 19.76499 |
October | 502.00000 | 21.81329 | 32.01075 | -0.2941 | 8.04393 |
November | 489.00000 | 20.84135 | 27.53029 | -0.5984 | 15.44762 |
December | 497.00000 | 20.20213 | 17.84206 | -0.8483 | 21.96686 |
Annual Sum or Average | 5943.00000 | 22.15489 | 34.20451 | -0.5758 | 14.68836 |
Minimum of Months | 454.00000 | 20.05816 | 15.25496 | -0.9140 | 8.04393 |
Maximum of Months | 514.00000 | 24.17891 | 53.36437 | -0.2293 | 24.68408 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.51010 | 15.59890 | -1.1484 | 34.72662 |
February | 454.00000 | 19.73032 | 20.50369 | -1.0186 | 29.33938 |
March | 514.00000 | 20.51122 | 26.55489 | -0.7247 | 18.22575 |
April | 485.00000 | 21.36524 | 33.65729 | -0.4032 | 13.27439 |
May | 508.00000 | 23.23314 | 44.46288 | -0.7982 | 21.69037 |
June | 496.00000 | 23.91183 | 50.33430 | -0.4610 | 12.27612 |
July | 497.00000 | 24.22972 | 54.03139 | -0.3145 | 8.13462 |
August | 514.00000 | 23.97414 | 53.51964 | -0.4225 | 9.77646 |
September | 485.00000 | 22.99064 | 42.07653 | -0.9044 | 27.06337 |
October | 502.00000 | 20.94487 | 34.11651 | -0.5120 | 12.35456 |
November | 489.00000 | 20.08556 | 29.10461 | -0.8225 | 22.99348 |
December | 497.00000 | 19.65230 | 18.67714 | -1.0705 | 31.23363 |
Annual Sum or Average | 5943.00000 | 21.69577 | 35.34852 | -0.7142 | 19.99483 |
Minimum of Months | 454.00000 | 19.51010 | 15.59890 | -1.1484 | 8.13462 |
Maximum of Months | 514.00000 | 24.22972 | 54.03139 | -0.3145 | 34.72662 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.65358 | 15.58487 | -1.0970 | 32.51156 |
February | 454.00000 | 19.90047 | 20.22870 | -0.9526 | 26.75937 |
March | 514.00000 | 20.74802 | 25.78981 | -0.6386 | 16.44070 |
April | 485.00000 | 21.80502 | 32.44118 | -0.2709 | 12.51774 |
May | 508.00000 | 23.56216 | 43.28003 | -0.6227 | 17.38797 |
June | 496.00000 | 23.94587 | 49.74874 | -0.3639 | 11.92111 |
July | 497.00000 | 24.34422 | 53.28649 | -0.1849 | 7.86031 |
August | 514.00000 | 24.03215 | 52.86454 | -0.3239 | 8.85283 |
September | 485.00000 | 23.27443 | 40.87619 | -0.7407 | 23.23353 |
October | 502.00000 | 21.24571 | 33.19966 | -0.4178 | 10.51749 |
November | 489.00000 | 20.18635 | 28.70509 | -0.7886 | 21.47042 |
December | 497.00000 | 19.75568 | 18.37064 | -1.0357 | 29.72387 |
Annual Sum or Average | 5943.00000 | 21.88832 | 34.65808 | -0.6171 | 18.17498 |
Minimum of Months | 454.00000 | 19.65358 | 15.58487 | -1.0970 | 7.86031 |
Maximum of Months | 514.00000 | 24.34422 | 53.28649 | -0.1849 | 32.51156 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.01423 | 15.33016 | -0.9497 | 28.32692 |
February | 454.00000 | 20.44660 | 19.53209 | -0.7759 | 22.43225 |
March | 514.00000 | 21.24014 | 24.95487 | -0.5094 | 14.93088 |
April | 485.00000 | 21.99358 | 31.86643 | -0.2228 | 12.93103 |
May | 508.00000 | 23.42488 | 43.56550 | -0.6986 | 19.65149 |
June | 496.00000 | 23.86822 | 50.15225 | -0.4422 | 12.70128 |
July | 497.00000 | 24.24615 | 53.68568 | -0.2648 | 8.48185 |
August | 514.00000 | 24.06343 | 52.74160 | -0.3287 | 9.33528 |
September | 485.00000 | 23.44543 | 40.33619 | -0.6702 | 21.81905 |
October | 502.00000 | 22.03075 | 31.36749 | -0.2157 | 10.22818 |
November | 489.00000 | 20.73991 | 27.86718 | -0.6311 | 18.66845 |
December | 497.00000 | 20.27745 | 17.79191 | -0.8676 | 25.31380 |
Annual Sum or Average | 5943.00000 | 22.16419 | 34.22888 | -0.5463 | 17.00717 |
Minimum of Months | 454.00000 | 20.01423 | 15.33016 | -0.9497 | 8.48185 |
Maximum of Months | 514.00000 | 24.24615 | 53.68568 | -0.2157 | 28.32692 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.66991 | 15.33533 | -1.0978 | 32.59782 |
February | 454.00000 | 19.99756 | 19.82049 | -0.9366 | 26.43752 |
March | 514.00000 | 20.74565 | 25.55800 | -0.6507 | 16.94346 |
April | 485.00000 | 21.70242 | 32.39420 | -0.2887 | 13.29089 |
May | 508.00000 | 23.13688 | 44.27032 | -0.7653 | 22.39943 |
June | 496.00000 | 23.78422 | 50.36092 | -0.4256 | 13.47117 |
July | 497.00000 | 24.19064 | 53.93178 | -0.2418 | 9.00706 |
August | 514.00000 | 23.92958 | 53.36623 | -0.3527 | 9.98411 |
September | 485.00000 | 22.98864 | 41.54359 | -0.8375 | 27.05314 |
October | 502.00000 | 21.19800 | 32.94642 | -0.4302 | 11.79858 |
November | 489.00000 | 20.18854 | 28.46214 | -0.7889 | 21.87048 |
December | 497.00000 | 19.76194 | 18.15953 | -1.0351 | 29.81944 |
Annual Sum or Average | 5943.00000 | 21.79033 | 34.81046 | -0.6519 | 19.47658 |
Minimum of Months | 454.00000 | 19.66991 | 15.33533 | -1.0978 | 9.00706 |
Maximum of Months | 514.00000 | 24.19064 | 53.93178 | -0.2418 | 32.59782 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.60211 | 15.59502 | -1.1031 | 32.39370 |
February | 454.00000 | 19.90530 | 20.51995 | -0.9686 | 26.60725 |
March | 514.00000 | 20.51731 | 26.80495 | -0.7309 | 17.53775 |
April | 485.00000 | 21.09701 | 34.52112 | -0.4881 | 12.51510 |
May | 508.00000 | 22.78753 | 46.30523 | -0.9899 | 27.90570 |
June | 496.00000 | 23.80490 | 50.64867 | -0.5467 | 12.86268 |
July | 497.00000 | 24.16130 | 53.99067 | -0.3786 | 8.43914 |
August | 514.00000 | 24.05528 | 53.03942 | -0.4210 | 9.09963 |
September | 485.00000 | 23.43279 | 40.91402 | -0.7549 | 19.83522 |
October | 502.00000 | 21.70328 | 32.72772 | -0.3056 | 7.96258 |
November | 489.00000 | 20.72041 | 28.35255 | -0.6310 | 16.29250 |
December | 497.00000 | 19.95278 | 18.59817 | -0.9578 | 25.92009 |
Annual Sum or Average | 5943.00000 | 21.82733 | 35.29968 | -0.6880 | 18.05816 |
Minimum of Months | 454.00000 | 19.60211 | 15.59502 | -1.1031 | 7.96258 |
Maximum of Months | 514.00000 | 24.16130 | 53.99067 | -0.3056 | 32.39370 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81079 | 15.93076 | -1.0415 | 29.69194 |
February | 454.00000 | 20.13578 | 20.65297 | -0.8911 | 23.43473 |
March | 514.00000 | 20.79365 | 26.47236 | -0.6347 | 15.24126 |
April | 485.00000 | 21.68323 | 33.35001 | -0.3222 | 11.03625 |
May | 508.00000 | 23.55305 | 44.18449 | -0.6859 | 18.08190 |
June | 496.00000 | 24.02531 | 49.41370 | -0.3926 | 10.80707 |
July | 497.00000 | 24.41584 | 52.74919 | -0.2060 | 7.21689 |
August | 514.00000 | 24.21481 | 52.02219 | -0.2889 | 7.50684 |
September | 485.00000 | 23.84086 | 39.54212 | -0.5544 | 15.32379 |
October | 502.00000 | 22.27830 | 31.83575 | -0.1546 | 6.75890 |
November | 489.00000 | 20.86986 | 28.32607 | -0.5848 | 15.12400 |
December | 497.00000 | 20.06488 | 18.67352 | -0.9218 | 24.45823 |
Annual Sum or Average | 5943.00000 | 22.15677 | 34.55453 | -0.5543 | 15.32878 |
Minimum of Months | 454.00000 | 19.81079 | 15.93076 | -1.0415 | 6.75890 |
Maximum of Months | 514.00000 | 24.41584 | 52.74919 | -0.1546 | 29.69194 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 17.81449 | 14.06015 | -1.3570 | 42.59940 |
February | 454.00000 | 18.89866 | 18.42892 | -1.0590 | 30.70839 |
March | 514.00000 | 20.12310 | 24.12756 | -0.7304 | 20.01744 |
April | 485.00000 | 21.16956 | 31.74394 | -0.4090 | 13.88186 |
May | 508.00000 | 22.64029 | 45.57902 | -0.9709 | 28.51460 |
June | 496.00000 | 23.53563 | 51.88712 | -0.5786 | 15.60386 |
July | 497.00000 | 24.15761 | 55.86089 | -0.3162 | 8.60974 |
August | 514.00000 | 24.09309 | 54.23424 | -0.3181 | 8.68377 |
September | 485.00000 | 23.55282 | 39.26310 | -0.6013 | 19.21254 |
October | 502.00000 | 22.22966 | 29.49866 | -0.1091 | 8.17969 |
November | 489.00000 | 20.44387 | 26.06932 | -0.6163 | 18.67424 |
December | 497.00000 | 18.97622 | 16.55639 | -1.0703 | 31.88666 |
Annual Sum or Average | 5943.00000 | 21.48900 | 34.08700 | -0.6758 | 20.48112 |
Minimum of Months | 454.00000 | 17.81449 | 14.06015 | -1.3570 | 8.17969 |
Maximum of Months | 514.00000 | 24.15761 | 55.86089 | -0.1091 | 42.59940 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81363 | 15.70489 | -1.0454 | 29.89990 |
February | 454.00000 | 20.19920 | 20.30954 | -0.8797 | 23.23282 |
March | 514.00000 | 20.76541 | 26.28346 | -0.6501 | 15.70761 |
April | 485.00000 | 21.70010 | 33.06157 | -0.3110 | 11.15145 |
May | 508.00000 | 23.15458 | 45.09778 | -0.8237 | 22.62086 |
June | 496.00000 | 23.91785 | 49.88613 | -0.4386 | 11.85072 |
July | 497.00000 | 24.38727 | 52.95511 | -0.2225 | 7.40070 |
August | 514.00000 | 24.22581 | 52.12305 | -0.2836 | 7.52040 |
September | 485.00000 | 23.68645 | 39.92987 | -0.6117 | 17.27257 |
October | 502.00000 | 22.13837 | 31.65347 | -0.1832 | 7.31154 |
November | 489.00000 | 20.86462 | 28.08145 | -0.5853 | 15.36668 |
December | 497.00000 | 20.06586 | 18.47322 | -0.9222 | 24.58188 |
Annual Sum or Average | 5943.00000 | 22.09155 | 34.59215 | -0.5779 | 16.10831 |
Minimum of Months | 454.00000 | 19.81363 | 15.70489 | -1.0454 | 7.31154 |
Maximum of Months | 514.00000 | 24.38727 | 52.95511 | -0.1832 | 29.89990 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.66136 | 15.91151 | -1.0622 | 30.87662 |
February | 454.00000 | 20.00972 | 20.52618 | -0.9087 | 24.42532 |
March | 514.00000 | 20.79846 | 26.33747 | -0.6205 | 15.01067 |
April | 485.00000 | 21.77160 | 33.18619 | -0.2886 | 10.37923 |
May | 508.00000 | 23.56438 | 43.81122 | -0.6905 | 17.14923 |
June | 496.00000 | 24.09492 | 49.70657 | -0.4090 | 10.04596 |
July | 497.00000 | 24.31715 | 53.45696 | -0.2940 | 7.43362 |
August | 514.00000 | 24.12990 | 52.85785 | -0.3761 | 8.40771 |
September | 485.00000 | 23.44008 | 41.11923 | -0.7468 | 20.18522 |
October | 502.00000 | 21.61002 | 33.24101 | -0.3285 | 8.68159 |
November | 489.00000 | 20.59972 | 28.52199 | -0.6621 | 17.66023 |
December | 497.00000 | 19.89463 | 18.68438 | -0.9623 | 26.40491 |
Annual Sum or Average | 5943.00000 | 22.00770 | 34.90662 | -0.6103 | 16.31438 |
Minimum of Months | 454.00000 | 19.66136 | 15.91151 | -1.0622 | 7.43362 |
Maximum of Months | 514.00000 | 24.31715 | 53.45696 | -0.2886 | 30.87662 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.56242 | 15.20515 | -1.0687 | 31.25842 |
February | 385.00000 | 20.00514 | 19.53811 | -0.8888 | 23.75345 |
March | 433.00000 | 20.92579 | 25.01123 | -0.5714 | 14.24009 |
April | 410.00000 | 22.03919 | 31.37450 | -0.2029 | 10.81365 |
May | 430.00000 | 23.73985 | 42.53469 | -0.5749 | 15.57986 |
June | 418.00000 | 24.12199 | 48.92786 | -0.3358 | 10.57957 |
July | 422.00000 | 24.46635 | 52.45744 | -0.1767 | 7.61383 |
August | 433.00000 | 24.16095 | 52.11731 | -0.3085 | 8.26602 |
September | 410.00000 | 23.54804 | 39.83567 | -0.6534 | 19.50099 |
October | 427.00000 | 21.72380 | 31.67334 | -0.2868 | 8.23233 |
November | 417.00000 | 20.50346 | 27.24256 | -0.6791 | 17.72272 |
December | 422.00000 | 19.79385 | 17.69787 | -0.9756 | 27.00172 |
Annual Sum or Average | 5034.00000 | 22.06265 | 33.73849 | -0.5582 | 16.15048 |
Minimum of Months | 385.00000 | 19.56242 | 15.20515 | -1.0687 | 7.61383 |
Maximum of Months | 433.00000 | 24.46635 | 52.45744 | -0.1767 | 31.25842 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.30560 | 15.36945 | -0.8410 | 24.06058 |
February | 454.00000 | 20.85979 | 19.33757 | -0.6436 | 17.78817 |
March | 514.00000 | 21.61828 | 24.54886 | -0.3917 | 12.05857 |
April | 485.00000 | 22.39243 | 31.30492 | -0.1126 | 10.45308 |
May | 508.00000 | 23.73690 | 42.88775 | -0.5982 | 15.41736 |
June | 496.00000 | 24.07589 | 49.44572 | -0.3850 | 10.22987 |
July | 497.00000 | 24.36247 | 53.01292 | -0.2389 | 7.49592 |
August | 514.00000 | 24.22121 | 52.06857 | -0.2845 | 7.91199 |
September | 485.00000 | 23.83324 | 39.42552 | -0.5340 | 16.07776 |
October | 502.00000 | 22.68161 | 30.33131 | -0.0406 | 8.07596 |
November | 489.00000 | 21.32542 | 27.17175 | -0.4586 | 14.60714 |
December | 497.00000 | 20.62174 | 17.57067 | -0.7428 | 20.81673 |
Annual Sum or Average | 5943.00000 | 22.51660 | 33.66746 | -0.4380 | 13.70705 |
Minimum of Months | 454.00000 | 20.30560 | 15.36945 | -0.8410 | 7.49592 |
Maximum of Months | 514.00000 | 24.36247 | 53.01292 | -0.0406 | 24.06058 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.79270 | 15.41467 | -1.0194 | 29.17717 |
February | 454.00000 | 20.25518 | 19.70621 | -0.8324 | 22.11083 |
March | 514.00000 | 21.02555 | 25.22934 | -0.5497 | 13.95680 |
April | 485.00000 | 22.06004 | 31.85460 | -0.1855 | 10.72081 |
May | 508.00000 | 23.48406 | 43.56268 | -0.6549 | 17.62039 |
June | 496.00000 | 24.00133 | 49.64042 | -0.3662 | 10.79235 |
July | 497.00000 | 24.32726 | 53.21799 | -0.2105 | 7.81015 |
August | 514.00000 | 24.12288 | 52.61674 | -0.2987 | 8.25511 |
September | 485.00000 | 23.40696 | 40.61178 | -0.6905 | 20.55693 |
October | 502.00000 | 21.76358 | 32.06011 | -0.2678 | 8.64617 |
November | 489.00000 | 20.64958 | 27.85283 | -0.6394 | 16.96619 |
December | 497.00000 | 19.98981 | 17.99845 | -0.9312 | 25.33405 |
Annual Sum or Average | 5943.00000 | 22.08862 | 34.27631 | -0.5518 | 15.93228 |
Minimum of Months | 454.00000 | 19.79270 | 15.41467 | -1.0194 | 7.81015 |
Maximum of Months | 514.00000 | 24.32726 | 53.21799 | -0.1855 | 29.17717 |
Report: DXReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.140983E+09 | 36653806.85 | 11.00 | 0.118528E+09 | 22455150.72 | 0.00 | 0.24 | 25-MAR-15:00 | 0.00 | 01-MAR-00:10 | 7131.00 | 25-MAR-15:00 | 6210.18 | 25-MAR-15:00 | 991.45 | 25-MAR-15:40 | 1814.97 | 25-MAR-15:00 | 0.00 |
April | 0.474701E+10 | 0.111660E+10 | 73.92 | 0.358574E+10 | 0.116128E+10 | 0.00 | 1.00 | 18-APR-09:00 | 0.00 | 01-APR-00:10 | 68612.12 | 18-APR-12:00 | 48789.82 | 18-APR-15:10 | 23847.69 | 18-APR-12:00 | 15464.29 | 18-APR-12:00 | 0.00 |
May | 0.130049E+11 | 0.301861E+10 | 215.74 | 0.965204E+10 | 0.335285E+10 | 0.00 | 1.00 | 05-MAY-14:30 | 0.00 | 01-MAY-00:10 | 69083.15 | 31-MAY-11:10 | 54491.00 | 31-MAY-15:10 | 24096.85 | 30-MAY-10:10 | 15918.31 | 31-MAY-11:10 | 0.00 |
June | 0.419756E+11 | 0.949198E+10 | 346.71 | 0.306480E+11 | 0.113276E+11 | 0.00 | 1.00 | 09-JUN-09:30 | 0.00 | 01-JUN-00:10 | 120096.86 | 26-JUN-06:03 | 66587.94 | 26-JUN-15:50 | 71874.33 | 26-JUN-06:03 | 24772.23 | 26-JUN-06:03 | 0.00 |
July | 0.601230E+11 | 0.131951E+11 | 435.76 | 0.400163E+11 | 0.201067E+11 | 0.00 | 1.00 | 02-JUL-08:62 | 0.00 | 01-JUL-00:10 | 106099.43 | 03-JUL-08:50 | 64711.50 | 03-JUL-15:30 | 63685.38 | 05-JUL-06:03 | 22075.76 | 05-JUL-10:40 | 0.00 |
August | 0.591367E+11 | 0.130590E+11 | 428.34 | 0.403042E+11 | 0.188326E+11 | 0.00 | 1.00 | 01-AUG-06:02 | 0.00 | 01-AUG-00:10 | 124702.80 | 03-AUG-07:10 | 65846.28 | 04-AUG-15:30 | 88854.84 | 04-AUG-07:10 | 25503.16 | 04-AUG-07:25 | 0.00 |
September | 0.235438E+11 | 0.542751E+10 | 240.89 | 0.205790E+11 | 0.296478E+10 | 0.00 | 1.00 | 01-SEP-11:50 | 0.00 | 01-SEP-00:10 | 92042.95 | 11-SEP-09:50 | 62995.22 | 07-SEP-16:00 | 36833.50 | 11-SEP-09:50 | 19443.18 | 11-SEP-09:50 | 0.00 |
October | 0.136758E+10 | 0.334396E+09 | 48.11 | 0.115921E+10 | 0.208365E+09 | 0.00 | 0.84 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 29302.54 | 20-OCT-15:00 | 29302.54 | 20-OCT-15:00 | 4856.50 | 02-OCT-15:00 | 6372.73 | 20-OCT-15:00 | 0.00 |
November | 44943156.65 | 11829059.20 | 5.44 | 39329936.79 | 5613219.86 | 0.00 | 0.13 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3782.51 | 03-NOV-14:00 | 3544.90 | 03-NOV-15:00 | 523.15 | 03-NOV-12:15 | 988.14 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.204084E+12 | 0.456916E+11 | 1805.91 | 0.146102E+12 | 0.579822E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.601230E+11 | 0.131951E+11 | 435.76 | 0.403042E+11 | 0.201067E+11 | 0.00 | 1.00 | 0.00 | 124702.80 | 66587.94 | 88854.84 | 25503.16 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.142430E+09 | 36904556.92 | 11.00 | 0.124626E+09 | 17803558.42 | 0.00 | 0.27 | 25-MAR-15:00 | 0.00 | 01-MAR-00:10 | 7547.76 | 25-MAR-15:00 | 7121.50 | 25-MAR-15:00 | 818.64 | 25-MAR-16:00 | 1904.96 | 25-MAR-15:00 | 0.00 |
April | 0.514164E+10 | 0.119510E+10 | 79.38 | 0.400899E+10 | 0.113265E+10 | 0.00 | 1.00 | 16-APR-15:52 | 0.00 | 01-APR-00:10 | 62141.37 | 18-APR-12:40 | 51339.20 | 18-APR-15:00 | 22207.08 | 18-APR-09:30 | 13946.13 | 18-APR-12:40 | 0.00 |
May | 0.135468E+11 | 0.312892E+10 | 235.56 | 0.100070E+11 | 0.353978E+10 | 0.00 | 1.00 | 05-MAY-12:30 | 0.00 | 01-MAY-00:10 | 63348.40 | 30-MAY-11:00 | 53887.21 | 31-MAY-15:00 | 26833.73 | 30-MAY-10:10 | 14247.80 | 31-MAY-15:00 | 0.00 |
June | 0.400471E+11 | 0.902248E+10 | 348.69 | 0.295165E+11 | 0.105306E+11 | 0.00 | 1.00 | 08-JUN-15:50 | 0.00 | 01-JUN-00:10 | 110136.32 | 26-JUN-06:03 | 61929.98 | 26-JUN-15:30 | 65842.84 | 26-JUN-06:03 | 22717.68 | 26-JUN-06:03 | 0.00 |
July | 0.550189E+11 | 0.120634E+11 | 434.96 | 0.366842E+11 | 0.183347E+11 | 0.00 | 1.00 | 02-JUL-07:52 | 0.00 | 01-JUL-00:10 | 100782.45 | 05-JUL-10:50 | 60015.95 | 03-JUL-15:10 | 59029.09 | 05-JUL-06:03 | 21148.55 | 05-JUL-10:50 | 0.00 |
August | 0.513749E+11 | 0.113666E+11 | 424.17 | 0.351871E+11 | 0.161878E+11 | 0.00 | 1.00 | 01-AUG-07:03 | 0.00 | 01-AUG-00:10 | 114360.25 | 04-AUG-07:10 | 64587.45 | 04-AUG-15:20 | 81362.75 | 04-AUG-07:10 | 23325.70 | 04-AUG-07:15 | 0.00 |
September | 0.205305E+11 | 0.474291E+10 | 237.37 | 0.180153E+11 | 0.251519E+10 | 0.00 | 1.00 | 01-SEP-12:10 | 0.00 | 01-SEP-00:10 | 77875.11 | 11-SEP-09:40 | 60207.47 | 07-SEP-16:00 | 31595.82 | 11-SEP-09:40 | 17361.10 | 06-SEP-14:30 | 0.00 |
October | 0.123465E+10 | 0.303029E+09 | 48.50 | 0.104272E+10 | 0.191935E+09 | 0.00 | 0.77 | 20-OCT-14:50 | 0.00 | 01-OCT-00:10 | 23995.84 | 20-OCT-14:50 | 23995.84 | 20-OCT-14:50 | 4107.88 | 02-OCT-15:00 | 5328.32 | 20-OCT-14:50 | 0.00 |
November | 51034878.16 | 13338779.09 | 5.22 | 43279012.56 | 7755865.60 | 0.00 | 0.18 | 03-NOV-13:30 | 0.00 | 01-NOV-00:10 | 4721.69 | 03-NOV-13:30 | 3952.61 | 03-NOV-13:40 | 861.75 | 03-NOV-13:10 | 1220.34 | 03-NOV-13:30 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.187088E+12 | 0.418726E+11 | 1824.85 | 0.134630E+12 | 0.524581E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.550189E+11 | 0.120634E+11 | 434.96 | 0.366842E+11 | 0.183347E+11 | 0.00 | 1.00 | 0.00 | 114360.25 | 64587.45 | 81362.75 | 23325.70 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
March | 0.147935E+09 | 38412742.14 | 11.00 | 0.126042E+09 | 21892780.91 | 0.00 | 0.26 | 25-MAR-15:00 | 0.00 | 01-MAR-00:10 | 7929.71 | 25-MAR-15:00 | 7238.68 | 25-MAR-15:00 | 960.54 | 25-MAR-15:50 | 2008.79 | 25-MAR-15:00 | 0.00 |
April | 0.577162E+10 | 0.133944E+10 | 79.83 | 0.448333E+10 | 0.128829E+10 | 0.00 | 1.00 | 15-APR-13:50 | 0.00 | 01-APR-00:10 | 74802.88 | 18-APR-15:50 | 58938.91 | 18-APR-15:00 | 22966.04 | 18-APR-15:50 | 16066.72 | 18-APR-15:50 | 0.00 |
May | 0.146001E+11 | 0.338012E+10 | 237.02 | 0.108408E+11 | 0.375929E+10 | 0.00 | 1.00 | 04-MAY-14:50 | 0.00 | 01-MAY-00:10 | 71312.17 | 30-MAY-12:10 | 63324.90 | 31-MAY-15:00 | 25085.36 | 30-MAY-10:00 | 16402.79 | 31-MAY-15:00 | 0.00 |
June | 0.431390E+11 | 0.975467E+10 | 348.71 | 0.322010E+11 | 0.109380E+11 | 0.00 | 1.00 | 08-JUN-15:50 | 0.00 | 01-JUN-00:10 | 122967.98 | 26-JUN-06:03 | 74202.42 | 26-JUN-14:00 | 73762.14 | 26-JUN-06:03 | 25364.46 | 26-JUN-06:03 | 0.00 |
July | 0.588328E+11 | 0.129376E+11 | 434.50 | 0.392437E+11 | 0.195891E+11 | 0.00 | 1.00 | 01-JUL-13:00 | 0.00 | 01-JUL-00:10 | 106016.99 | 06-JUL-15:10 | 69047.97 | 03-JUL-15:20 | 52382.81 | 17-JUL-16:10 | 22307.74 | 06-JUL-15:10 | 0.00 |
August | 0.533239E+11 | 0.118650E+11 | 421.79 | 0.369678E+11 | 0.163561E+11 | 0.00 | 1.00 | 01-AUG-07:35 | 0.00 | 01-AUG-00:10 | 127795.46 | 03-AUG-05:03 | 76457.36 | 04-AUG-15:30 | 87878.51 | 04-AUG-05:03 | 25886.01 | 03-AUG-05:03 | 0.00 |
September | 0.212807E+11 | 0.495136E+10 | 233.85 | 0.185970E+11 | 0.268367E+10 | 0.00 | 1.00 | 01-SEP-13:00 | 0.00 | 01-SEP-00:10 | 77993.51 | 11-SEP-10:00 | 69003.84 | 07-SEP-16:00 | 29739.94 | 11-SEP-10:00 | 19049.89 | 06-SEP-14:00 | 0.00 |
October | 0.123815E+10 | 0.306551E+09 | 47.39 | 0.102430E+10 | 0.213849E+09 | 0.00 | 0.71 | 20-OCT-15:00 | 0.00 | 01-OCT-00:10 | 24443.81 | 20-OCT-15:00 | 24443.81 | 20-OCT-15:00 | 4270.69 | 02-OCT-15:00 | 5512.49 | 20-OCT-15:00 | 0.00 |
November | 37289923.77 | 9831808.18 | 4.33 | 31323742.24 | 5966181.53 | 0.00 | 0.12 | 03-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3461.35 | 03-NOV-14:00 | 2979.24 | 03-NOV-14:30 | 528.93 | 03-NOV-13:30 | 907.11 | 03-NOV-14:00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
Annual Sum or Average | 0.198371E+12 | 0.445830E+11 | 1818.43 | 0.143515E+12 | 0.548562E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Maximum of Months | 0.588328E+11 | 0.129376E+11 | 434.50 | 0.392437E+11 | 0.195891E+11 | 0.00 | 1.00 | 0.00 | 127795.46 | 76457.36 | 87878.51 | 25886.01 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 331.29 | 0.00 | 331.29 | 1.80 | 2625.03 | 0.00 | 0.00 | 0.00 |
February | 420.02 | 0.00 | 420.02 | 28.98 | 2097.36 | 0.00 | 0.00 | 0.00 |
March | 629.48 | 0.00 | 629.48 | 213.30 | 1327.36 | 0.00 | 0.00 | 0.00 |
April | 726.69 | 3.58 | 723.11 | 423.71 | 906.82 | 0.00 | 0.00 | 0.00 |
May | 947.61 | 35.62 | 911.99 | 852.07 | 539.23 | 0.00 | 0.00 | 0.00 |
June | 1107.54 | 100.52 | 1007.02 | 1274.20 | 374.55 | 0.00 | 0.00 | 0.00 |
July | 1038.70 | 69.48 | 969.22 | 1245.16 | 329.59 | 0.00 | 0.00 | 0.00 |
August | 869.70 | 15.41 | 854.28 | 1038.35 | 386.33 | 0.00 | 0.00 | 0.00 |
September | 666.81 | 0.17 | 666.64 | 635.42 | 658.87 | 0.00 | 0.00 | 0.00 |
October | 495.78 | 0.00 | 495.78 | 256.45 | 982.22 | 0.00 | 0.00 | 0.00 |
November | 346.81 | 0.00 | 346.81 | 65.92 | 1544.54 | 0.00 | 0.00 | 0.00 |
December | 224.96 | 0.00 | 224.96 | 0.57 | 2302.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 651.67 | 18.81 | 632.86 | 505.83 | 1168.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 224.96 | 0.00 | 224.96 | 0.57 | 329.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1107.54 | 100.52 | 1007.02 | 1274.20 | 2625.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 473.26 | 194.75 | 278.51 | 210.59 | 1580.87 | 0.00 | 0.00 | 0.00 |
February | 627.31 | 275.84 | 351.47 | 370.50 | 1243.33 | 0.00 | 0.00 | 0.00 |
March | 852.32 | 338.31 | 514.01 | 671.56 | 814.40 | 0.00 | 0.00 | 0.00 |
April | 1046.57 | 458.32 | 588.24 | 1018.22 | 583.37 | 0.00 | 0.00 | 0.00 |
May | 1314.40 | 574.33 | 740.07 | 1482.63 | 363.24 | 0.00 | 0.00 | 0.00 |
June | 1446.47 | 629.91 | 816.55 | 1809.93 | 251.16 | 0.00 | 0.00 | 0.00 |
July | 1462.01 | 674.60 | 787.40 | 1870.79 | 220.85 | 0.00 | 0.00 | 0.00 |
August | 1232.44 | 531.33 | 701.11 | 1581.02 | 257.15 | 0.00 | 0.00 | 0.00 |
September | 1099.23 | 519.44 | 579.79 | 1307.62 | 424.38 | 0.00 | 0.00 | 0.00 |
October | 700.50 | 292.59 | 407.91 | 643.67 | 616.43 | 0.00 | 0.00 | 0.00 |
November | 413.30 | 134.25 | 279.06 | 230.48 | 957.69 | 0.00 | 0.00 | 0.00 |
December | 320.15 | 137.48 | 182.67 | 147.69 | 1420.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 917.09 | 397.33 | 519.76 | 948.52 | 725.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 320.15 | 134.25 | 182.67 | 147.69 | 220.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1462.01 | 674.60 | 816.55 | 1870.79 | 1580.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2060.28 | 1409.89 | 650.39 | 1846.23 | 2143.80 | 0.00 | 0.00 | 0.00 |
February | 2207.55 | 1491.44 | 716.11 | 2064.33 | 1719.95 | 0.00 | 0.00 | 0.00 |
March | 1921.07 | 1011.57 | 909.50 | 1887.60 | 1241.98 | 0.00 | 0.00 | 0.00 |
April | 1730.76 | 809.16 | 921.60 | 1891.57 | 929.28 | 0.00 | 0.00 | 0.00 |
May | 1433.87 | 388.74 | 1045.13 | 1660.14 | 588.94 | 0.00 | 0.00 | 0.00 |
June | 1392.07 | 283.43 | 1108.64 | 1789.57 | 401.19 | 0.00 | 0.00 | 0.00 |
July | 1473.61 | 371.31 | 1102.30 | 1975.23 | 351.41 | 0.00 | 0.00 | 0.00 |
August | 1660.27 | 595.41 | 1064.86 | 2260.65 | 414.14 | 0.00 | 0.00 | 0.00 |
September | 2011.89 | 1060.10 | 951.79 | 2561.06 | 671.40 | 0.00 | 0.00 | 0.00 |
October | 2100.83 | 1317.98 | 782.86 | 2356.55 | 953.12 | 0.00 | 0.00 | 0.00 |
November | 1585.08 | 992.29 | 592.79 | 1516.80 | 1376.12 | 0.00 | 0.00 | 0.00 |
December | 1690.25 | 1280.35 | 409.91 | 1626.87 | 1982.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1769.73 | 914.36 | 855.37 | 1952.28 | 1061.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1392.07 | 283.43 | 409.91 | 1516.80 | 351.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2207.55 | 1491.44 | 1108.64 | 2561.06 | 2143.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.36 | 189.91 | 279.45 | 218.17 | 1619.07 | 0.00 | 0.00 | 0.00 |
February | 688.24 | 339.14 | 349.09 | 456.96 | 1289.43 | 0.00 | 0.00 | 0.00 |
March | 821.61 | 305.68 | 515.93 | 635.81 | 841.77 | 0.00 | 0.00 | 0.00 |
April | 1198.49 | 592.63 | 605.86 | 1240.57 | 608.23 | 0.00 | 0.00 | 0.00 |
May | 1201.95 | 480.15 | 721.80 | 1364.77 | 383.31 | 0.00 | 0.00 | 0.00 |
June | 1410.35 | 611.21 | 799.14 | 1776.88 | 269.80 | 0.00 | 0.00 | 0.00 |
July | 1514.29 | 719.31 | 794.98 | 1959.94 | 241.81 | 0.00 | 0.00 | 0.00 |
August | 1323.87 | 607.57 | 716.30 | 1724.42 | 277.02 | 0.00 | 0.00 | 0.00 |
September | 1071.63 | 508.65 | 562.98 | 1283.33 | 443.44 | 0.00 | 0.00 | 0.00 |
October | 746.76 | 332.00 | 414.76 | 717.95 | 644.50 | 0.00 | 0.00 | 0.00 |
November | 446.98 | 165.29 | 281.69 | 288.07 | 980.33 | 0.00 | 0.00 | 0.00 |
December | 343.75 | 162.05 | 181.70 | 191.17 | 1450.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 937.43 | 417.88 | 519.55 | 990.79 | 751.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 343.75 | 162.05 | 181.70 | 191.17 | 241.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1514.29 | 719.31 | 799.14 | 1959.94 | 1619.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.43 | 0.00 | 110.43 | 0.65 | 877.49 | 0.00 | 0.00 | 0.00 |
February | 140.00 | 0.00 | 140.00 | 9.72 | 704.25 | 0.00 | 0.00 | 0.00 |
March | 209.82 | 0.00 | 209.82 | 76.07 | 443.78 | 0.00 | 0.00 | 0.00 |
April | 242.22 | 1.19 | 241.02 | 152.10 | 296.63 | 0.00 | 0.00 | 0.00 |
May | 315.86 | 11.87 | 303.98 | 300.50 | 170.65 | 0.00 | 0.00 | 0.00 |
June | 369.16 | 33.51 | 335.66 | 435.08 | 121.49 | 0.00 | 0.00 | 0.00 |
July | 346.22 | 23.16 | 323.06 | 422.98 | 107.93 | 0.00 | 0.00 | 0.00 |
August | 289.89 | 5.14 | 284.75 | 349.21 | 130.80 | 0.00 | 0.00 | 0.00 |
September | 222.26 | 0.06 | 222.20 | 209.51 | 234.42 | 0.00 | 0.00 | 0.00 |
October | 165.25 | 0.00 | 165.25 | 78.74 | 358.34 | 0.00 | 0.00 | 0.00 |
November | 115.60 | 0.00 | 115.60 | 19.14 | 547.68 | 0.00 | 0.00 | 0.00 |
December | 74.98 | 0.00 | 74.98 | 0.08 | 787.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.21 | 6.27 | 210.94 | 172.11 | 396.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.98 | 0.00 | 74.98 | 0.08 | 107.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 369.16 | 33.51 | 335.66 | 435.08 | 877.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.43 | 0.00 | 110.43 | 0.65 | 877.54 | 0.00 | 0.00 | 0.00 |
February | 140.01 | 0.00 | 140.01 | 9.72 | 704.30 | 0.00 | 0.00 | 0.00 |
March | 209.83 | 0.00 | 209.83 | 76.08 | 443.81 | 0.00 | 0.00 | 0.00 |
April | 242.23 | 1.19 | 241.04 | 152.11 | 296.65 | 0.00 | 0.00 | 0.00 |
May | 315.88 | 11.87 | 304.00 | 300.52 | 170.66 | 0.00 | 0.00 | 0.00 |
June | 369.19 | 33.51 | 335.68 | 435.10 | 121.50 | 0.00 | 0.00 | 0.00 |
July | 346.24 | 23.16 | 323.08 | 423.00 | 107.93 | 0.00 | 0.00 | 0.00 |
August | 289.90 | 5.14 | 284.77 | 349.23 | 130.81 | 0.00 | 0.00 | 0.00 |
September | 222.27 | 0.06 | 222.22 | 209.52 | 234.44 | 0.00 | 0.00 | 0.00 |
October | 165.26 | 0.00 | 165.26 | 78.75 | 358.36 | 0.00 | 0.00 | 0.00 |
November | 115.60 | 0.00 | 115.60 | 19.14 | 547.71 | 0.00 | 0.00 | 0.00 |
December | 74.99 | 0.00 | 74.99 | 0.08 | 787.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.23 | 6.27 | 210.96 | 172.13 | 396.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.99 | 0.00 | 74.99 | 0.08 | 107.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 369.19 | 33.51 | 335.68 | 435.10 | 877.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.43 | 0.00 | 110.43 | 0.65 | 877.54 | 0.00 | 0.00 | 0.00 |
February | 140.01 | 0.00 | 140.01 | 9.72 | 704.30 | 0.00 | 0.00 | 0.00 |
March | 209.83 | 0.00 | 209.83 | 76.08 | 443.81 | 0.00 | 0.00 | 0.00 |
April | 242.23 | 1.19 | 241.04 | 152.11 | 296.65 | 0.00 | 0.00 | 0.00 |
May | 315.88 | 11.87 | 304.00 | 300.52 | 170.66 | 0.00 | 0.00 | 0.00 |
June | 369.19 | 33.51 | 335.68 | 435.10 | 121.50 | 0.00 | 0.00 | 0.00 |
July | 346.24 | 23.16 | 323.08 | 423.00 | 107.93 | 0.00 | 0.00 | 0.00 |
August | 289.90 | 5.14 | 284.77 | 349.23 | 130.81 | 0.00 | 0.00 | 0.00 |
September | 222.27 | 0.06 | 222.22 | 209.52 | 234.44 | 0.00 | 0.00 | 0.00 |
October | 165.26 | 0.00 | 165.26 | 78.75 | 358.36 | 0.00 | 0.00 | 0.00 |
November | 115.60 | 0.00 | 115.60 | 19.14 | 547.71 | 0.00 | 0.00 | 0.00 |
December | 74.99 | 0.00 | 74.99 | 0.08 | 787.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 217.23 | 6.27 | 210.96 | 172.13 | 396.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 74.99 | 0.00 | 74.99 | 0.08 | 107.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 369.19 | 33.51 | 335.68 | 435.10 | 877.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 455.26 | 187.34 | 267.92 | 205.23 | 1532.16 | 0.00 | 0.00 | 0.00 |
February | 603.44 | 265.34 | 338.10 | 359.97 | 1215.77 | 0.00 | 0.00 | 0.00 |
March | 819.89 | 325.44 | 494.46 | 659.08 | 793.88 | 0.00 | 0.00 | 0.00 |
April | 1006.75 | 440.89 | 565.87 | 1001.56 | 562.11 | 0.00 | 0.00 | 0.00 |
May | 1264.40 | 552.48 | 711.92 | 1449.20 | 347.47 | 0.00 | 0.00 | 0.00 |
June | 1391.44 | 605.95 | 785.49 | 1757.12 | 244.97 | 0.00 | 0.00 | 0.00 |
July | 1406.39 | 648.94 | 757.45 | 1812.01 | 218.09 | 0.00 | 0.00 | 0.00 |
August | 1185.56 | 511.12 | 674.44 | 1526.92 | 259.39 | 0.00 | 0.00 | 0.00 |
September | 1057.41 | 499.68 | 557.73 | 1252.67 | 446.76 | 0.00 | 0.00 | 0.00 |
October | 673.85 | 281.46 | 392.39 | 599.27 | 660.75 | 0.00 | 0.00 | 0.00 |
November | 397.58 | 129.14 | 268.44 | 211.89 | 984.45 | 0.00 | 0.00 | 0.00 |
December | 307.97 | 132.25 | 175.72 | 140.87 | 1405.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 882.20 | 382.22 | 499.99 | 917.66 | 720.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 307.97 | 129.14 | 175.72 | 140.87 | 218.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1406.39 | 648.94 | 785.49 | 1812.01 | 1532.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 18.00 | 7.41 | 10.59 | 8.11 | 60.58 | 0.00 | 0.00 | 0.00 |
February | 23.86 | 10.49 | 13.37 | 14.23 | 48.07 | 0.00 | 0.00 | 0.00 |
March | 32.42 | 12.87 | 19.55 | 26.06 | 31.39 | 0.00 | 0.00 | 0.00 |
April | 39.81 | 17.43 | 22.37 | 39.60 | 22.23 | 0.00 | 0.00 | 0.00 |
May | 49.99 | 21.84 | 28.15 | 57.30 | 13.74 | 0.00 | 0.00 | 0.00 |
June | 55.02 | 23.96 | 31.06 | 69.47 | 9.69 | 0.00 | 0.00 | 0.00 |
July | 55.61 | 25.66 | 29.95 | 71.65 | 8.62 | 0.00 | 0.00 | 0.00 |
August | 46.88 | 20.21 | 26.67 | 60.37 | 10.26 | 0.00 | 0.00 | 0.00 |
September | 41.81 | 19.76 | 22.05 | 49.53 | 17.66 | 0.00 | 0.00 | 0.00 |
October | 26.64 | 11.13 | 15.51 | 23.69 | 26.13 | 0.00 | 0.00 | 0.00 |
November | 15.72 | 5.11 | 10.61 | 8.38 | 38.92 | 0.00 | 0.00 | 0.00 |
December | 12.18 | 5.23 | 6.95 | 5.57 | 55.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 34.88 | 15.11 | 19.77 | 36.28 | 28.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 12.18 | 5.11 | 6.95 | 5.57 | 8.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.61 | 25.66 | 31.06 | 71.65 | 60.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 686.78 | 469.98 | 216.80 | 636.55 | 696.07 | 0.00 | 0.00 | 0.00 |
February | 735.87 | 497.16 | 238.71 | 708.86 | 572.39 | 0.00 | 0.00 | 0.00 |
March | 640.38 | 337.20 | 303.17 | 648.05 | 412.25 | 0.00 | 0.00 | 0.00 |
April | 576.94 | 269.73 | 307.21 | 648.18 | 305.50 | 0.00 | 0.00 | 0.00 |
May | 477.97 | 129.58 | 348.39 | 573.15 | 188.32 | 0.00 | 0.00 | 0.00 |
June | 464.04 | 94.48 | 369.56 | 609.51 | 130.45 | 0.00 | 0.00 | 0.00 |
July | 491.22 | 123.77 | 367.44 | 667.01 | 117.55 | 0.00 | 0.00 | 0.00 |
August | 553.44 | 198.48 | 354.96 | 759.03 | 144.20 | 0.00 | 0.00 | 0.00 |
September | 670.65 | 353.38 | 317.27 | 856.19 | 242.42 | 0.00 | 0.00 | 0.00 |
October | 700.30 | 439.34 | 260.96 | 785.76 | 352.71 | 0.00 | 0.00 | 0.00 |
November | 528.38 | 330.77 | 197.60 | 507.82 | 485.18 | 0.00 | 0.00 | 0.00 |
December | 563.44 | 426.80 | 136.64 | 551.34 | 662.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 589.93 | 304.80 | 285.13 | 662.32 | 358.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 464.04 | 94.48 | 136.64 | 507.82 | 117.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 735.87 | 497.16 | 369.56 | 856.19 | 696.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 686.78 | 469.98 | 216.80 | 636.55 | 696.07 | 0.00 | 0.00 | 0.00 |
February | 735.87 | 497.16 | 238.71 | 708.86 | 572.39 | 0.00 | 0.00 | 0.00 |
March | 640.38 | 337.20 | 303.17 | 648.05 | 412.25 | 0.00 | 0.00 | 0.00 |
April | 576.94 | 269.73 | 307.21 | 648.18 | 305.50 | 0.00 | 0.00 | 0.00 |
May | 477.97 | 129.58 | 348.39 | 573.15 | 188.32 | 0.00 | 0.00 | 0.00 |
June | 464.04 | 94.48 | 369.56 | 609.51 | 130.45 | 0.00 | 0.00 | 0.00 |
July | 491.22 | 123.77 | 367.44 | 667.01 | 117.55 | 0.00 | 0.00 | 0.00 |
August | 553.44 | 198.48 | 354.96 | 759.03 | 144.20 | 0.00 | 0.00 | 0.00 |
September | 670.65 | 353.38 | 317.27 | 856.19 | 242.42 | 0.00 | 0.00 | 0.00 |
October | 700.30 | 439.34 | 260.96 | 785.76 | 352.71 | 0.00 | 0.00 | 0.00 |
November | 528.38 | 330.77 | 197.60 | 507.82 | 485.18 | 0.00 | 0.00 | 0.00 |
December | 563.44 | 426.80 | 136.64 | 551.34 | 662.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 589.93 | 304.80 | 285.13 | 662.32 | 358.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 464.04 | 94.48 | 136.64 | 507.82 | 117.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 735.87 | 497.16 | 369.56 | 856.19 | 696.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 686.74 | 469.95 | 216.79 | 636.51 | 696.03 | 0.00 | 0.00 | 0.00 |
February | 735.83 | 497.13 | 238.70 | 708.82 | 572.36 | 0.00 | 0.00 | 0.00 |
March | 640.34 | 337.18 | 303.16 | 648.01 | 412.22 | 0.00 | 0.00 | 0.00 |
April | 576.90 | 269.71 | 307.19 | 648.14 | 305.48 | 0.00 | 0.00 | 0.00 |
May | 477.94 | 129.58 | 348.37 | 573.12 | 188.31 | 0.00 | 0.00 | 0.00 |
June | 464.01 | 94.47 | 369.53 | 609.47 | 130.44 | 0.00 | 0.00 | 0.00 |
July | 491.19 | 123.77 | 367.42 | 666.97 | 117.54 | 0.00 | 0.00 | 0.00 |
August | 553.40 | 198.46 | 354.94 | 758.98 | 144.19 | 0.00 | 0.00 | 0.00 |
September | 670.61 | 353.36 | 317.25 | 856.14 | 242.41 | 0.00 | 0.00 | 0.00 |
October | 700.26 | 439.31 | 260.94 | 785.71 | 352.69 | 0.00 | 0.00 | 0.00 |
November | 528.34 | 330.75 | 197.59 | 507.78 | 485.15 | 0.00 | 0.00 | 0.00 |
December | 563.40 | 426.77 | 136.63 | 551.30 | 662.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 589.89 | 304.78 | 285.11 | 662.28 | 358.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 464.01 | 94.47 | 136.63 | 507.78 | 117.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 735.83 | 497.13 | 369.53 | 856.14 | 696.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 451.51 | 182.68 | 268.82 | 214.75 | 1567.63 | 0.00 | 0.00 | 0.00 |
February | 662.05 | 326.24 | 335.81 | 447.53 | 1258.82 | 0.00 | 0.00 | 0.00 |
March | 790.36 | 294.05 | 496.30 | 627.98 | 820.00 | 0.00 | 0.00 | 0.00 |
April | 1152.89 | 570.08 | 582.81 | 1215.57 | 590.68 | 0.00 | 0.00 | 0.00 |
May | 1156.23 | 461.88 | 694.35 | 1336.01 | 365.04 | 0.00 | 0.00 | 0.00 |
June | 1356.70 | 587.96 | 768.74 | 1724.08 | 262.73 | 0.00 | 0.00 | 0.00 |
July | 1456.68 | 691.94 | 764.74 | 1895.42 | 240.89 | 0.00 | 0.00 | 0.00 |
August | 1273.50 | 584.45 | 689.05 | 1663.71 | 281.55 | 0.00 | 0.00 | 0.00 |
September | 1030.87 | 489.30 | 541.57 | 1227.90 | 466.19 | 0.00 | 0.00 | 0.00 |
October | 718.35 | 319.37 | 398.98 | 677.16 | 688.99 | 0.00 | 0.00 | 0.00 |
November | 429.98 | 159.01 | 270.97 | 270.03 | 1007.57 | 0.00 | 0.00 | 0.00 |
December | 330.68 | 155.89 | 174.79 | 185.06 | 1434.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 901.77 | 401.98 | 499.79 | 959.62 | 746.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 330.68 | 155.89 | 174.79 | 185.06 | 240.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1456.68 | 691.94 | 768.74 | 1895.42 | 1567.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 17.85 | 7.22 | 10.63 | 8.49 | 61.98 | 0.00 | 0.00 | 0.00 |
February | 26.18 | 12.90 | 13.28 | 17.69 | 49.77 | 0.00 | 0.00 | 0.00 |
March | 31.25 | 11.63 | 19.62 | 24.83 | 32.42 | 0.00 | 0.00 | 0.00 |
April | 45.58 | 22.54 | 23.04 | 48.06 | 23.36 | 0.00 | 0.00 | 0.00 |
May | 45.72 | 18.26 | 27.45 | 52.82 | 14.43 | 0.00 | 0.00 | 0.00 |
June | 53.64 | 23.25 | 30.40 | 68.17 | 10.39 | 0.00 | 0.00 | 0.00 |
July | 57.60 | 27.36 | 30.24 | 74.94 | 9.52 | 0.00 | 0.00 | 0.00 |
August | 50.35 | 23.11 | 27.24 | 65.78 | 11.13 | 0.00 | 0.00 | 0.00 |
September | 40.76 | 19.35 | 21.41 | 48.55 | 18.43 | 0.00 | 0.00 | 0.00 |
October | 28.40 | 12.63 | 15.78 | 26.77 | 27.24 | 0.00 | 0.00 | 0.00 |
November | 17.00 | 6.29 | 10.71 | 10.68 | 39.84 | 0.00 | 0.00 | 0.00 |
December | 13.07 | 6.16 | 6.91 | 7.32 | 56.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.66 | 15.89 | 19.76 | 37.94 | 29.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 13.07 | 6.16 | 6.91 | 7.32 | 9.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 57.60 | 27.36 | 30.40 | 74.94 | 61.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 331.29 | 0.00 | 331.29 | 1.53 | 2676.14 | 0.00 | 0.00 | 0.00 |
February | 420.02 | 0.00 | 420.02 | 25.70 | 2165.00 | 0.00 | 0.00 | 0.00 |
March | 629.48 | 0.00 | 629.48 | 204.48 | 1388.24 | 0.00 | 0.00 | 0.00 |
April | 726.69 | 3.58 | 723.11 | 414.18 | 963.28 | 0.00 | 0.00 | 0.00 |
May | 947.61 | 35.62 | 911.99 | 840.42 | 565.67 | 0.00 | 0.00 | 0.00 |
June | 1107.54 | 100.52 | 1007.02 | 1270.12 | 390.59 | 0.00 | 0.00 | 0.00 |
July | 1038.70 | 69.48 | 969.22 | 1245.05 | 340.38 | 0.00 | 0.00 | 0.00 |
August | 869.70 | 15.41 | 854.28 | 1034.81 | 402.31 | 0.00 | 0.00 | 0.00 |
September | 666.81 | 0.17 | 666.64 | 622.16 | 703.23 | 0.00 | 0.00 | 0.00 |
October | 495.78 | 0.00 | 495.78 | 234.41 | 1063.37 | 0.00 | 0.00 | 0.00 |
November | 346.81 | 0.00 | 346.81 | 56.56 | 1631.61 | 0.00 | 0.00 | 0.00 |
December | 224.96 | 0.00 | 224.96 | 0.19 | 2374.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 651.67 | 18.81 | 632.86 | 498.62 | 1217.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 224.96 | 0.00 | 224.96 | 0.19 | 340.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1107.54 | 100.52 | 1007.02 | 1270.12 | 2676.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 473.26 | 194.75 | 278.51 | 208.07 | 1611.43 | 0.00 | 0.00 | 0.00 |
February | 627.31 | 275.84 | 351.47 | 364.78 | 1284.45 | 0.00 | 0.00 | 0.00 |
March | 852.32 | 338.31 | 514.01 | 662.65 | 851.85 | 0.00 | 0.00 | 0.00 |
April | 1046.57 | 458.32 | 588.24 | 1011.94 | 615.76 | 0.00 | 0.00 | 0.00 |
May | 1314.40 | 574.33 | 740.07 | 1478.69 | 378.52 | 0.00 | 0.00 | 0.00 |
June | 1446.47 | 629.91 | 816.55 | 1809.45 | 261.13 | 0.00 | 0.00 | 0.00 |
July | 1462.01 | 674.60 | 787.40 | 1872.76 | 227.40 | 0.00 | 0.00 | 0.00 |
August | 1232.44 | 531.33 | 701.11 | 1580.72 | 266.49 | 0.00 | 0.00 | 0.00 |
September | 1099.23 | 519.44 | 579.79 | 1300.87 | 448.98 | 0.00 | 0.00 | 0.00 |
October | 700.50 | 292.59 | 407.91 | 625.92 | 663.24 | 0.00 | 0.00 | 0.00 |
November | 413.30 | 134.25 | 279.06 | 220.34 | 1009.48 | 0.00 | 0.00 | 0.00 |
December | 320.15 | 137.48 | 182.67 | 144.36 | 1464.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 917.09 | 397.33 | 519.76 | 943.18 | 754.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 320.15 | 134.25 | 182.67 | 144.36 | 227.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1462.01 | 674.60 | 816.55 | 1872.76 | 1611.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2060.28 | 1409.89 | 650.39 | 1837.36 | 2194.39 | 0.00 | 0.00 | 0.00 |
February | 2207.55 | 1491.44 | 716.11 | 2050.62 | 1784.66 | 0.00 | 0.00 | 0.00 |
March | 1921.07 | 1011.57 | 909.50 | 1875.06 | 1302.01 | 0.00 | 0.00 | 0.00 |
April | 1730.76 | 809.16 | 921.60 | 1883.81 | 984.45 | 0.00 | 0.00 | 0.00 |
May | 1433.87 | 388.74 | 1045.13 | 1654.01 | 618.13 | 0.00 | 0.00 | 0.00 |
June | 1392.07 | 283.43 | 1108.64 | 1787.85 | 420.14 | 0.00 | 0.00 | 0.00 |
July | 1473.61 | 371.31 | 1102.30 | 1976.91 | 364.16 | 0.00 | 0.00 | 0.00 |
August | 1660.27 | 595.41 | 1064.86 | 2260.90 | 431.63 | 0.00 | 0.00 | 0.00 |
September | 2011.89 | 1060.10 | 951.79 | 2551.85 | 712.89 | 0.00 | 0.00 | 0.00 |
October | 2100.83 | 1317.98 | 782.86 | 2333.06 | 1027.66 | 0.00 | 0.00 | 0.00 |
November | 1585.08 | 992.29 | 592.79 | 1495.30 | 1455.35 | 0.00 | 0.00 | 0.00 |
December | 1690.25 | 1280.35 | 409.91 | 1615.81 | 2050.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1769.73 | 914.36 | 855.37 | 1942.82 | 1109.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1392.07 | 283.43 | 409.91 | 1495.30 | 364.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2207.55 | 1491.44 | 1108.64 | 2551.85 | 2194.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.36 | 189.91 | 279.45 | 216.99 | 1650.27 | 0.00 | 0.00 | 0.00 |
February | 688.24 | 339.14 | 349.09 | 453.30 | 1331.21 | 0.00 | 0.00 | 0.00 |
March | 821.61 | 305.68 | 515.93 | 629.79 | 881.10 | 0.00 | 0.00 | 0.00 |
April | 1198.49 | 592.63 | 605.86 | 1235.80 | 643.93 | 0.00 | 0.00 | 0.00 |
May | 1201.95 | 480.15 | 721.80 | 1359.28 | 402.40 | 0.00 | 0.00 | 0.00 |
June | 1410.35 | 611.21 | 799.14 | 1775.44 | 281.97 | 0.00 | 0.00 | 0.00 |
July | 1514.29 | 719.31 | 794.98 | 1960.81 | 250.30 | 0.00 | 0.00 | 0.00 |
August | 1323.87 | 607.57 | 716.30 | 1723.39 | 288.48 | 0.00 | 0.00 | 0.00 |
September | 1071.63 | 508.65 | 562.98 | 1275.32 | 471.15 | 0.00 | 0.00 | 0.00 |
October | 746.76 | 332.00 | 414.76 | 704.10 | 695.06 | 0.00 | 0.00 | 0.00 |
November | 446.98 | 165.29 | 281.69 | 279.52 | 1033.81 | 0.00 | 0.00 | 0.00 |
December | 343.75 | 162.05 | 181.70 | 188.87 | 1495.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 937.43 | 417.88 | 519.55 | 986.18 | 782.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 343.75 | 162.05 | 181.70 | 188.87 | 250.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1514.29 | 719.31 | 799.14 | 1960.81 | 1650.27 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.887339E+09 | 0.00 | 0.887339E+09 | 4826241.59 | 0.703087E+10 |
February | 0.101610E+10 | 0.00 | 0.101610E+10 | 70113219.65 | 0.507393E+10 |
March | 0.168599E+10 | 0.00 | 0.168599E+10 | 0.571312E+09 | 0.355520E+10 |
April | 0.188357E+10 | 9280265.68 | 0.187429E+10 | 0.109826E+10 | 0.235048E+10 |
May | 0.253809E+10 | 95400764.26 | 0.244268E+10 | 0.228220E+10 | 0.144428E+10 |
June | 0.287075E+10 | 0.260558E+09 | 0.261019E+10 | 0.330272E+10 | 0.970837E+09 |
July | 0.278206E+10 | 0.186089E+09 | 0.259597E+10 | 0.333503E+10 | 0.882766E+09 |
August | 0.232940E+10 | 41283426.32 | 0.228811E+10 | 0.278112E+10 | 0.103473E+10 |
September | 0.172837E+10 | 428557.81 | 0.172794E+10 | 0.164701E+10 | 0.170779E+10 |
October | 0.132791E+10 | 0.00 | 0.132791E+10 | 0.686884E+09 | 0.263077E+10 |
November | 0.898922E+09 | 0.00 | 0.898922E+09 | 0.170857E+09 | 0.400345E+10 |
December | 0.602531E+09 | 0.00 | 0.602531E+09 | 1532841.53 | 0.616669E+10 |
Annual Sum or Average | 0.205510E+11 | 0.593040E+09 | 0.199580E+11 | 0.159519E+11 | 0.368518E+11 |
Minimum of Months | 0.602531E+09 | 0.00 | 0.602531E+09 | 1532841.53 | 0.882766E+09 |
Maximum of Months | 0.287075E+10 | 0.260558E+09 | 0.261019E+10 | 0.333503E+10 | 0.703087E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126759E+10 | 0.521614E+09 | 0.745972E+09 | 0.564044E+09 | 0.423420E+10 |
February | 0.151758E+10 | 0.667309E+09 | 0.850272E+09 | 0.896313E+09 | 0.300786E+10 |
March | 0.228285E+10 | 0.906129E+09 | 0.137672E+10 | 0.179871E+10 | 0.218129E+10 |
April | 0.271270E+10 | 0.118797E+10 | 0.152472E+10 | 0.263924E+10 | 0.151209E+10 |
May | 0.352050E+10 | 0.153829E+10 | 0.198220E+10 | 0.397109E+10 | 0.972908E+09 |
June | 0.374924E+10 | 0.163273E+10 | 0.211651E+10 | 0.469134E+10 | 0.651011E+09 |
July | 0.391584E+10 | 0.180685E+10 | 0.210899E+10 | 0.501071E+10 | 0.591529E+09 |
August | 0.330098E+10 | 0.142312E+10 | 0.187786E+10 | 0.423461E+10 | 0.688744E+09 |
September | 0.284920E+10 | 0.134639E+10 | 0.150281E+10 | 0.338936E+10 | 0.110000E+10 |
October | 0.187623E+10 | 0.783685E+09 | 0.109255E+10 | 0.172401E+10 | 0.165104E+10 |
November | 0.107128E+10 | 0.347972E+09 | 0.723311E+09 | 0.597396E+09 | 0.248233E+10 |
December | 0.857486E+09 | 0.368225E+09 | 0.489262E+09 | 0.395569E+09 | 0.380378E+10 |
Annual Sum or Average | 0.289215E+11 | 0.125303E+11 | 0.163912E+11 | 0.299124E+11 | 0.228768E+11 |
Minimum of Months | 0.857486E+09 | 0.347972E+09 | 0.489262E+09 | 0.395569E+09 | 0.591529E+09 |
Maximum of Months | 0.391584E+10 | 0.180685E+10 | 0.211651E+10 | 0.501071E+10 | 0.423420E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.551825E+10 | 0.377626E+10 | 0.174200E+10 | 0.494495E+10 | 0.574196E+10 |
February | 0.534051E+10 | 0.360809E+10 | 0.173242E+10 | 0.499402E+10 | 0.416090E+10 |
March | 0.514539E+10 | 0.270939E+10 | 0.243600E+10 | 0.505574E+10 | 0.332651E+10 |
April | 0.448612E+10 | 0.209734E+10 | 0.238878E+10 | 0.490296E+10 | 0.240868E+10 |
May | 0.384049E+10 | 0.104120E+10 | 0.279928E+10 | 0.444653E+10 | 0.157741E+10 |
June | 0.360826E+10 | 0.734658E+09 | 0.287360E+10 | 0.463856E+10 | 0.103988E+10 |
July | 0.394691E+10 | 0.994514E+09 | 0.295240E+10 | 0.529046E+10 | 0.941208E+09 |
August | 0.444686E+10 | 0.159474E+10 | 0.285211E+10 | 0.605492E+10 | 0.110922E+10 |
September | 0.521482E+10 | 0.274778E+10 | 0.246704E+10 | 0.663827E+10 | 0.174028E+10 |
October | 0.562688E+10 | 0.353007E+10 | 0.209681E+10 | 0.631179E+10 | 0.255285E+10 |
November | 0.410852E+10 | 0.257201E+10 | 0.153651E+10 | 0.393155E+10 | 0.356691E+10 |
December | 0.452717E+10 | 0.342928E+10 | 0.109790E+10 | 0.435740E+10 | 0.530948E+10 |
Annual Sum or Average | 0.558102E+11 | 0.288353E+11 | 0.269748E+11 | 0.615671E+11 | 0.334753E+11 |
Minimum of Months | 0.360826E+10 | 0.734658E+09 | 0.109790E+10 | 0.393155E+10 | 0.941208E+09 |
Maximum of Months | 0.562688E+10 | 0.377626E+10 | 0.295240E+10 | 0.663827E+10 | 0.574196E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125714E+10 | 0.508652E+09 | 0.748485E+09 | 0.584355E+09 | 0.433652E+10 |
February | 0.166498E+10 | 0.820450E+09 | 0.844529E+09 | 0.110548E+10 | 0.311939E+10 |
March | 0.220060E+10 | 0.818743E+09 | 0.138186E+10 | 0.170296E+10 | 0.225458E+10 |
April | 0.310648E+10 | 0.153609E+10 | 0.157038E+10 | 0.321557E+10 | 0.157653E+10 |
May | 0.321931E+10 | 0.128604E+10 | 0.193328E+10 | 0.365540E+10 | 0.102666E+10 |
June | 0.365563E+10 | 0.158426E+10 | 0.207137E+10 | 0.460568E+10 | 0.699329E+09 |
July | 0.405587E+10 | 0.192660E+10 | 0.212927E+10 | 0.524950E+10 | 0.647677E+09 |
August | 0.354585E+10 | 0.162731E+10 | 0.191854E+10 | 0.461868E+10 | 0.741978E+09 |
September | 0.277767E+10 | 0.131842E+10 | 0.145925E+10 | 0.332638E+10 | 0.114941E+10 |
October | 0.200012E+10 | 0.889228E+09 | 0.111089E+10 | 0.192296E+10 | 0.172623E+10 |
November | 0.115858E+10 | 0.428442E+09 | 0.730140E+09 | 0.746670E+09 | 0.254102E+10 |
December | 0.920711E+09 | 0.434035E+09 | 0.486675E+09 | 0.512022E+09 | 0.388492E+10 |
Annual Sum or Average | 0.295629E+11 | 0.131783E+11 | 0.163847E+11 | 0.312456E+11 | 0.237042E+11 |
Minimum of Months | 0.920711E+09 | 0.428442E+09 | 0.486675E+09 | 0.512022E+09 | 0.647677E+09 |
Maximum of Months | 0.405587E+10 | 0.192660E+10 | 0.212927E+10 | 0.524950E+10 | 0.433652E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295766E+09 | 0.00 | 0.295766E+09 | 1740899.03 | 0.235026E+10 |
February | 0.338685E+09 | 0.00 | 0.338685E+09 | 23515942.79 | 0.170372E+10 |
March | 0.561969E+09 | 0.00 | 0.561969E+09 | 0.203749E+09 | 0.118863E+10 |
April | 0.627827E+09 | 3093275.54 | 0.624734E+09 | 0.394255E+09 | 0.768873E+09 |
May | 0.845988E+09 | 31798750.22 | 0.814190E+09 | 0.804856E+09 | 0.457063E+09 |
June | 0.956871E+09 | 86848477.70 | 0.870023E+09 | 0.112772E+10 | 0.314914E+09 |
July | 0.927308E+09 | 62026758.62 | 0.865282E+09 | 0.113290E+10 | 0.289073E+09 |
August | 0.776429E+09 | 13760491.04 | 0.762668E+09 | 0.935321E+09 | 0.350333E+09 |
September | 0.576095E+09 | 142845.85 | 0.575952E+09 | 0.543043E+09 | 0.607621E+09 |
October | 0.442615E+09 | 0.00 | 0.442615E+09 | 0.210904E+09 | 0.959782E+09 |
November | 0.299627E+09 | 0.00 | 0.299627E+09 | 49599239.98 | 0.141958E+10 |
December | 0.200834E+09 | 0.00 | 0.200834E+09 | 216549.19 | 0.210884E+10 |
Annual Sum or Average | 0.685001E+10 | 0.197671E+09 | 0.665234E+10 | 0.542782E+10 | 0.125187E+11 |
Minimum of Months | 0.200834E+09 | 0.00 | 0.200834E+09 | 216549.19 | 0.289073E+09 |
Maximum of Months | 0.956871E+09 | 86848477.70 | 0.870023E+09 | 0.113290E+10 | 0.235026E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295784E+09 | 0.00 | 0.295784E+09 | 1741009.05 | 0.235041E+10 |
February | 0.338707E+09 | 0.00 | 0.338707E+09 | 23517428.96 | 0.170383E+10 |
March | 0.562005E+09 | 0.00 | 0.562005E+09 | 0.203762E+09 | 0.118870E+10 |
April | 0.627867E+09 | 3093471.03 | 0.624773E+09 | 0.394280E+09 | 0.768921E+09 |
May | 0.846042E+09 | 31800759.85 | 0.814241E+09 | 0.804907E+09 | 0.457092E+09 |
June | 0.956932E+09 | 86853966.38 | 0.870078E+09 | 0.112779E+10 | 0.314934E+09 |
July | 0.927367E+09 | 62030678.61 | 0.865336E+09 | 0.113297E+10 | 0.289091E+09 |
August | 0.776478E+09 | 13761360.68 | 0.762717E+09 | 0.935381E+09 | 0.350355E+09 |
September | 0.576131E+09 | 142854.87 | 0.575989E+09 | 0.543077E+09 | 0.607659E+09 |
October | 0.442643E+09 | 0.00 | 0.442643E+09 | 0.210917E+09 | 0.959842E+09 |
November | 0.299645E+09 | 0.00 | 0.299645E+09 | 49602374.57 | 0.141967E+10 |
December | 0.200847E+09 | 0.00 | 0.200847E+09 | 216562.87 | 0.210898E+10 |
Annual Sum or Average | 0.685045E+10 | 0.197683E+09 | 0.665276E+10 | 0.542816E+10 | 0.125195E+11 |
Minimum of Months | 0.200847E+09 | 0.00 | 0.200847E+09 | 216562.87 | 0.289091E+09 |
Maximum of Months | 0.956932E+09 | 86853966.38 | 0.870078E+09 | 0.113297E+10 | 0.235041E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295784E+09 | 0.00 | 0.295784E+09 | 1741009.05 | 0.235041E+10 |
February | 0.338707E+09 | 0.00 | 0.338707E+09 | 23517428.96 | 0.170383E+10 |
March | 0.562005E+09 | 0.00 | 0.562005E+09 | 0.203762E+09 | 0.118870E+10 |
April | 0.627867E+09 | 3093471.03 | 0.624773E+09 | 0.394280E+09 | 0.768921E+09 |
May | 0.846042E+09 | 31800759.85 | 0.814241E+09 | 0.804907E+09 | 0.457092E+09 |
June | 0.956932E+09 | 86853966.38 | 0.870078E+09 | 0.112779E+10 | 0.314934E+09 |
July | 0.927367E+09 | 62030678.61 | 0.865336E+09 | 0.113297E+10 | 0.289091E+09 |
August | 0.776478E+09 | 13761360.68 | 0.762717E+09 | 0.935381E+09 | 0.350355E+09 |
September | 0.576131E+09 | 142854.87 | 0.575989E+09 | 0.543077E+09 | 0.607659E+09 |
October | 0.442643E+09 | 0.00 | 0.442643E+09 | 0.210917E+09 | 0.959842E+09 |
November | 0.299645E+09 | 0.00 | 0.299645E+09 | 49602374.57 | 0.141967E+10 |
December | 0.200847E+09 | 0.00 | 0.200847E+09 | 216562.87 | 0.210898E+10 |
Annual Sum or Average | 0.685045E+10 | 0.197683E+09 | 0.665276E+10 | 0.542816E+10 | 0.125195E+11 |
Minimum of Months | 0.200847E+09 | 0.00 | 0.200847E+09 | 216562.87 | 0.289091E+09 |
Maximum of Months | 0.956932E+09 | 86853966.38 | 0.870078E+09 | 0.113297E+10 | 0.235041E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121936E+10 | 0.501770E+09 | 0.717594E+09 | 0.549689E+09 | 0.410374E+10 |
February | 0.145985E+10 | 0.641921E+09 | 0.817926E+09 | 0.870849E+09 | 0.294120E+10 |
March | 0.219600E+10 | 0.871655E+09 | 0.132435E+10 | 0.176527E+10 | 0.212633E+10 |
April | 0.260950E+10 | 0.114278E+10 | 0.146672E+10 | 0.259605E+10 | 0.145698E+10 |
May | 0.338657E+10 | 0.147977E+10 | 0.190680E+10 | 0.388155E+10 | 0.930656E+09 |
June | 0.360661E+10 | 0.157061E+10 | 0.203599E+10 | 0.455445E+10 | 0.634957E+09 |
July | 0.376687E+10 | 0.173811E+10 | 0.202876E+10 | 0.485330E+10 | 0.584138E+09 |
August | 0.317540E+10 | 0.136898E+10 | 0.180642E+10 | 0.408971E+10 | 0.694750E+09 |
September | 0.274081E+10 | 0.129517E+10 | 0.144564E+10 | 0.324693E+10 | 0.115799E+10 |
October | 0.180485E+10 | 0.753870E+09 | 0.105098E+10 | 0.160510E+10 | 0.176975E+10 |
November | 0.103053E+10 | 0.334733E+09 | 0.695795E+09 | 0.549210E+09 | 0.255170E+10 |
December | 0.824865E+09 | 0.354216E+09 | 0.470650E+09 | 0.377318E+09 | 0.376493E+10 |
Annual Sum or Average | 0.278212E+11 | 0.120536E+11 | 0.157676E+11 | 0.289394E+11 | 0.227171E+11 |
Minimum of Months | 0.824865E+09 | 0.334733E+09 | 0.470650E+09 | 0.377318E+09 | 0.584138E+09 |
Maximum of Months | 0.376687E+10 | 0.173811E+10 | 0.203599E+10 | 0.485330E+10 | 0.410374E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 48212545.43 | 19839521.38 | 28373024.04 | 21734191.94 | 0.162258E+09 |
February | 57721061.80 | 25380990.96 | 32340070.84 | 34432598.70 | 0.116292E+09 |
March | 86828039.34 | 34464465.00 | 52363574.34 | 69797289.47 | 84073288.16 |
April | 0.103177E+09 | 45184413.61 | 57992893.23 | 0.102645E+09 | 57607789.92 |
May | 0.133902E+09 | 58508754.97 | 75393107.64 | 0.153473E+09 | 36797285.98 |
June | 0.142602E+09 | 62100637.47 | 80501364.50 | 0.180079E+09 | 25105638.55 |
July | 0.148939E+09 | 68723297.50 | 80215272.96 | 0.191895E+09 | 23096308.18 |
August | 0.125552E+09 | 54128133.39 | 71424245.58 | 0.161703E+09 | 27469806.09 |
September | 0.108369E+09 | 51209802.76 | 57159273.39 | 0.128381E+09 | 45785932.29 |
October | 71362264.86 | 29807328.99 | 41554935.87 | 63464063.75 | 69974444.70 |
November | 40746180.34 | 13235053.48 | 27511126.87 | 21715266.10 | 0.100892E+09 |
December | 32614426.70 | 14005362.83 | 18609063.87 | 14918818.81 | 0.148862E+09 |
Annual Sum or Average | 0.110003E+10 | 0.476588E+09 | 0.623438E+09 | 0.114424E+10 | 0.898215E+09 |
Minimum of Months | 32614426.70 | 13235053.48 | 18609063.87 | 14918818.81 | 23096308.18 |
Maximum of Months | 0.148939E+09 | 68723297.50 | 80501364.50 | 0.191895E+09 | 0.162258E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183948E+10 | 0.125879E+10 | 0.580683E+09 | 0.170492E+10 | 0.186435E+10 |
February | 0.178023E+10 | 0.120274E+10 | 0.577491E+09 | 0.171487E+10 | 0.138473E+10 |
March | 0.171518E+10 | 0.903158E+09 | 0.812024E+09 | 0.173574E+10 | 0.110417E+10 |
April | 0.149542E+10 | 0.699137E+09 | 0.796280E+09 | 0.168008E+10 | 0.791857E+09 |
May | 0.128020E+10 | 0.347080E+09 | 0.933120E+09 | 0.153513E+10 | 0.504405E+09 |
June | 0.120279E+10 | 0.244894E+09 | 0.957892E+09 | 0.157985E+10 | 0.338120E+09 |
July | 0.131568E+10 | 0.331516E+09 | 0.984160E+09 | 0.178653E+10 | 0.314848E+09 |
August | 0.148233E+10 | 0.531599E+09 | 0.950730E+09 | 0.203298E+10 | 0.386214E+09 |
September | 0.173833E+10 | 0.915955E+09 | 0.822371E+09 | 0.221926E+10 | 0.628358E+09 |
October | 0.187568E+10 | 0.117673E+10 | 0.698956E+09 | 0.210457E+10 | 0.944697E+09 |
November | 0.136955E+10 | 0.857363E+09 | 0.512185E+09 | 0.131626E+10 | 0.125759E+10 |
December | 0.150911E+10 | 0.114313E+10 | 0.365976E+09 | 0.147670E+10 | 0.177572E+10 |
Annual Sum or Average | 0.186040E+11 | 0.961209E+10 | 0.899187E+10 | 0.208869E+11 | 0.112951E+11 |
Minimum of Months | 0.120279E+10 | 0.244894E+09 | 0.365976E+09 | 0.131626E+10 | 0.314848E+09 |
Maximum of Months | 0.187568E+10 | 0.125879E+10 | 0.984160E+09 | 0.221926E+10 | 0.186435E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183948E+10 | 0.125879E+10 | 0.580683E+09 | 0.170492E+10 | 0.186435E+10 |
February | 0.178023E+10 | 0.120274E+10 | 0.577491E+09 | 0.171487E+10 | 0.138473E+10 |
March | 0.171518E+10 | 0.903158E+09 | 0.812024E+09 | 0.173574E+10 | 0.110417E+10 |
April | 0.149542E+10 | 0.699137E+09 | 0.796280E+09 | 0.168008E+10 | 0.791857E+09 |
May | 0.128020E+10 | 0.347080E+09 | 0.933120E+09 | 0.153513E+10 | 0.504405E+09 |
June | 0.120279E+10 | 0.244894E+09 | 0.957892E+09 | 0.157985E+10 | 0.338120E+09 |
July | 0.131568E+10 | 0.331516E+09 | 0.984160E+09 | 0.178653E+10 | 0.314848E+09 |
August | 0.148233E+10 | 0.531599E+09 | 0.950730E+09 | 0.203298E+10 | 0.386214E+09 |
September | 0.173833E+10 | 0.915955E+09 | 0.822371E+09 | 0.221926E+10 | 0.628358E+09 |
October | 0.187568E+10 | 0.117673E+10 | 0.698956E+09 | 0.210457E+10 | 0.944697E+09 |
November | 0.136955E+10 | 0.857363E+09 | 0.512185E+09 | 0.131626E+10 | 0.125759E+10 |
December | 0.150911E+10 | 0.114313E+10 | 0.365976E+09 | 0.147670E+10 | 0.177572E+10 |
Annual Sum or Average | 0.186040E+11 | 0.961209E+10 | 0.899187E+10 | 0.208869E+11 | 0.112951E+11 |
Minimum of Months | 0.120279E+10 | 0.244894E+09 | 0.365976E+09 | 0.131626E+10 | 0.314848E+09 |
Maximum of Months | 0.187568E+10 | 0.125879E+10 | 0.984160E+09 | 0.221926E+10 | 0.186435E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183936E+10 | 0.125871E+10 | 0.580646E+09 | 0.170482E+10 | 0.186424E+10 |
February | 0.178011E+10 | 0.120266E+10 | 0.577455E+09 | 0.171477E+10 | 0.138464E+10 |
March | 0.171507E+10 | 0.903101E+09 | 0.811972E+09 | 0.173563E+10 | 0.110410E+10 |
April | 0.149532E+10 | 0.699093E+09 | 0.796230E+09 | 0.167997E+10 | 0.791807E+09 |
May | 0.128012E+10 | 0.347058E+09 | 0.933061E+09 | 0.153503E+10 | 0.504373E+09 |
June | 0.120271E+10 | 0.244879E+09 | 0.957831E+09 | 0.157975E+10 | 0.338099E+09 |
July | 0.131559E+10 | 0.331495E+09 | 0.984098E+09 | 0.178641E+10 | 0.314828E+09 |
August | 0.148224E+10 | 0.531565E+09 | 0.950670E+09 | 0.203285E+10 | 0.386190E+09 |
September | 0.173822E+10 | 0.915897E+09 | 0.822319E+09 | 0.221912E+10 | 0.628318E+09 |
October | 0.187557E+10 | 0.117665E+10 | 0.698912E+09 | 0.210444E+10 | 0.944637E+09 |
November | 0.136946E+10 | 0.857309E+09 | 0.512153E+09 | 0.131617E+10 | 0.125751E+10 |
December | 0.150901E+10 | 0.114306E+10 | 0.365953E+09 | 0.147661E+10 | 0.177561E+10 |
Annual Sum or Average | 0.186028E+11 | 0.961148E+10 | 0.899130E+10 | 0.208856E+11 | 0.112944E+11 |
Minimum of Months | 0.120271E+10 | 0.244879E+09 | 0.365953E+09 | 0.131617E+10 | 0.314828E+09 |
Maximum of Months | 0.187557E+10 | 0.125871E+10 | 0.984098E+09 | 0.221912E+10 | 0.186424E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120931E+10 | 0.489301E+09 | 0.720012E+09 | 0.575193E+09 | 0.419873E+10 |
February | 0.160164E+10 | 0.789236E+09 | 0.812402E+09 | 0.108266E+10 | 0.304533E+10 |
March | 0.211689E+10 | 0.787594E+09 | 0.132929E+10 | 0.168198E+10 | 0.219628E+10 |
April | 0.298830E+10 | 0.147765E+10 | 0.151064E+10 | 0.315076E+10 | 0.153105E+10 |
May | 0.309684E+10 | 0.123711E+10 | 0.185973E+10 | 0.357838E+10 | 0.977717E+09 |
June | 0.351656E+10 | 0.152398E+10 | 0.199257E+10 | 0.446881E+10 | 0.680992E+09 |
July | 0.390157E+10 | 0.185330E+10 | 0.204827E+10 | 0.507669E+10 | 0.645211E+09 |
August | 0.341095E+10 | 0.156540E+10 | 0.184556E+10 | 0.445608E+10 | 0.754092E+09 |
September | 0.267200E+10 | 0.126827E+10 | 0.140374E+10 | 0.318271E+10 | 0.120836E+10 |
October | 0.192403E+10 | 0.855398E+09 | 0.106863E+10 | 0.181370E+10 | 0.184540E+10 |
November | 0.111451E+10 | 0.412142E+09 | 0.702365E+09 | 0.699908E+09 | 0.261163E+10 |
December | 0.885684E+09 | 0.417523E+09 | 0.468161E+09 | 0.495657E+09 | 0.384330E+10 |
Annual Sum or Average | 0.284383E+11 | 0.126769E+11 | 0.157614E+11 | 0.302625E+11 | 0.235381E+11 |
Minimum of Months | 0.885684E+09 | 0.412142E+09 | 0.468161E+09 | 0.495657E+09 | 0.645211E+09 |
Maximum of Months | 0.390157E+10 | 0.185330E+10 | 0.204827E+10 | 0.507669E+10 | 0.419873E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 47815001.96 | 19346449.31 | 28468552.64 | 22742471.47 | 0.166014E+09 |
February | 63327168.57 | 31205595.62 | 32121572.95 | 42807198.84 | 0.120410E+09 |
March | 83699580.82 | 31140674.80 | 52558906.02 | 66503545.78 | 86838876.29 |
April | 0.118154E+09 | 58424944.15 | 59729314.54 | 0.124578E+09 | 60536465.86 |
May | 0.122446E+09 | 48914030.66 | 73532026.32 | 0.141486E+09 | 38658024.27 |
June | 0.139041E+09 | 60256719.27 | 78784432.75 | 0.176692E+09 | 26925792.22 |
July | 0.154264E+09 | 73277549.93 | 80986627.06 | 0.200727E+09 | 25511041.26 |
August | 0.134866E+09 | 61894250.40 | 72971433.78 | 0.176189E+09 | 29816123.58 |
September | 0.105648E+09 | 50145899.13 | 55502450.23 | 0.125841E+09 | 47777617.90 |
October | 76074104.14 | 33821544.40 | 42252559.74 | 71711883.71 | 72965530.41 |
November | 44066492.34 | 16295684.92 | 27770807.42 | 27673602.00 | 0.103261E+09 |
December | 35019058.09 | 16508418.98 | 18510639.11 | 19597733.16 | 0.151961E+09 |
Annual Sum or Average | 0.112442E+10 | 0.501232E+09 | 0.623189E+09 | 0.119655E+10 | 0.930675E+09 |
Minimum of Months | 35019058.09 | 16295684.92 | 18510639.11 | 19597733.16 | 25511041.26 |
Maximum of Months | 0.154264E+09 | 73277549.93 | 80986627.06 | 0.200727E+09 | 0.166014E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.887339E+09 | 0.00 | 0.887339E+09 | 4087477.42 | 0.716776E+10 |
February | 0.101610E+10 | 0.00 | 0.101610E+10 | 62169659.74 | 0.523756E+10 |
March | 0.168599E+10 | 0.00 | 0.168599E+10 | 0.547685E+09 | 0.371825E+10 |
April | 0.188357E+10 | 9280265.68 | 0.187429E+10 | 0.107356E+10 | 0.249682E+10 |
May | 0.253809E+10 | 95400764.26 | 0.244268E+10 | 0.225099E+10 | 0.151508E+10 |
June | 0.287075E+10 | 0.260558E+09 | 0.261019E+10 | 0.329216E+10 | 0.101240E+10 |
July | 0.278206E+10 | 0.186089E+09 | 0.259597E+10 | 0.333475E+10 | 0.911661E+09 |
August | 0.232940E+10 | 41283426.32 | 0.228811E+10 | 0.277163E+10 | 0.107754E+10 |
September | 0.172837E+10 | 428557.81 | 0.172794E+10 | 0.161264E+10 | 0.182277E+10 |
October | 0.132791E+10 | 0.00 | 0.132791E+10 | 0.627832E+09 | 0.284813E+10 |
November | 0.898922E+09 | 0.00 | 0.898922E+09 | 0.146593E+09 | 0.422914E+10 |
December | 0.602531E+09 | 0.00 | 0.602531E+09 | 519578.31 | 0.636017E+10 |
Annual Sum or Average | 0.205510E+11 | 0.593040E+09 | 0.199580E+11 | 0.157246E+11 | 0.383973E+11 |
Minimum of Months | 0.602531E+09 | 0.00 | 0.602531E+09 | 519578.31 | 0.911661E+09 |
Maximum of Months | 0.287075E+10 | 0.260558E+09 | 0.261019E+10 | 0.333475E+10 | 0.716776E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126759E+10 | 0.521614E+09 | 0.745972E+09 | 0.557285E+09 | 0.431606E+10 |
February | 0.151758E+10 | 0.667309E+09 | 0.850272E+09 | 0.882473E+09 | 0.310734E+10 |
March | 0.228285E+10 | 0.906129E+09 | 0.137672E+10 | 0.177483E+10 | 0.228160E+10 |
April | 0.271270E+10 | 0.118797E+10 | 0.152472E+10 | 0.262295E+10 | 0.159605E+10 |
May | 0.352050E+10 | 0.153829E+10 | 0.198220E+10 | 0.396051E+10 | 0.101383E+10 |
June | 0.374924E+10 | 0.163273E+10 | 0.211651E+10 | 0.469010E+10 | 0.676839E+09 |
July | 0.391584E+10 | 0.180685E+10 | 0.210899E+10 | 0.501599E+10 | 0.609061E+09 |
August | 0.330098E+10 | 0.142312E+10 | 0.187786E+10 | 0.423379E+10 | 0.713776E+09 |
September | 0.284920E+10 | 0.134639E+10 | 0.150281E+10 | 0.337185E+10 | 0.116376E+10 |
October | 0.187623E+10 | 0.783685E+09 | 0.109255E+10 | 0.167646E+10 | 0.177642E+10 |
November | 0.107128E+10 | 0.347972E+09 | 0.723311E+09 | 0.571111E+09 | 0.261656E+10 |
December | 0.857486E+09 | 0.368225E+09 | 0.489262E+09 | 0.386667E+09 | 0.392263E+10 |
Annual Sum or Average | 0.289215E+11 | 0.125303E+11 | 0.163912E+11 | 0.297440E+11 | 0.237939E+11 |
Minimum of Months | 0.857486E+09 | 0.347972E+09 | 0.489262E+09 | 0.386667E+09 | 0.609061E+09 |
Maximum of Months | 0.391584E+10 | 0.180685E+10 | 0.211651E+10 | 0.501599E+10 | 0.431606E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.551825E+10 | 0.377626E+10 | 0.174200E+10 | 0.492118E+10 | 0.587745E+10 |
February | 0.534051E+10 | 0.360809E+10 | 0.173242E+10 | 0.496087E+10 | 0.431744E+10 |
March | 0.514539E+10 | 0.270939E+10 | 0.243600E+10 | 0.502216E+10 | 0.348730E+10 |
April | 0.448612E+10 | 0.209734E+10 | 0.238878E+10 | 0.488284E+10 | 0.255171E+10 |
May | 0.384049E+10 | 0.104120E+10 | 0.279928E+10 | 0.443010E+10 | 0.165560E+10 |
June | 0.360826E+10 | 0.734658E+09 | 0.287360E+10 | 0.463411E+10 | 0.108899E+10 |
July | 0.394691E+10 | 0.994514E+09 | 0.295240E+10 | 0.529495E+10 | 0.975378E+09 |
August | 0.444686E+10 | 0.159474E+10 | 0.285211E+10 | 0.605559E+10 | 0.115607E+10 |
September | 0.521482E+10 | 0.274778E+10 | 0.246704E+10 | 0.661440E+10 | 0.184781E+10 |
October | 0.562688E+10 | 0.353007E+10 | 0.209681E+10 | 0.624886E+10 | 0.275247E+10 |
November | 0.410852E+10 | 0.257201E+10 | 0.153651E+10 | 0.387581E+10 | 0.377227E+10 |
December | 0.452717E+10 | 0.342928E+10 | 0.109790E+10 | 0.432779E+10 | 0.549267E+10 |
Annual Sum or Average | 0.558102E+11 | 0.288353E+11 | 0.269748E+11 | 0.612687E+11 | 0.349752E+11 |
Minimum of Months | 0.360826E+10 | 0.734658E+09 | 0.109790E+10 | 0.387581E+10 | 0.975378E+09 |
Maximum of Months | 0.562688E+10 | 0.377626E+10 | 0.295240E+10 | 0.661440E+10 | 0.587745E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125714E+10 | 0.508652E+09 | 0.748485E+09 | 0.581192E+09 | 0.442008E+10 |
February | 0.166498E+10 | 0.820450E+09 | 0.844529E+09 | 0.109663E+10 | 0.322046E+10 |
March | 0.220060E+10 | 0.818743E+09 | 0.138186E+10 | 0.168683E+10 | 0.235993E+10 |
April | 0.310648E+10 | 0.153609E+10 | 0.157038E+10 | 0.320320E+10 | 0.166907E+10 |
May | 0.321931E+10 | 0.128604E+10 | 0.193328E+10 | 0.364069E+10 | 0.107779E+10 |
June | 0.365563E+10 | 0.158426E+10 | 0.207137E+10 | 0.460194E+10 | 0.730865E+09 |
July | 0.405587E+10 | 0.192660E+10 | 0.212927E+10 | 0.525183E+10 | 0.670394E+09 |
August | 0.354585E+10 | 0.162731E+10 | 0.191854E+10 | 0.461592E+10 | 0.772676E+09 |
September | 0.277767E+10 | 0.131842E+10 | 0.145925E+10 | 0.330564E+10 | 0.122121E+10 |
October | 0.200012E+10 | 0.889228E+09 | 0.111089E+10 | 0.188585E+10 | 0.186165E+10 |
November | 0.115858E+10 | 0.428442E+09 | 0.730140E+09 | 0.724523E+09 | 0.267964E+10 |
December | 0.920711E+09 | 0.434035E+09 | 0.486675E+09 | 0.505857E+09 | 0.400577E+10 |
Annual Sum or Average | 0.295629E+11 | 0.131783E+11 | 0.163847E+11 | 0.311001E+11 | 0.246895E+11 |
Minimum of Months | 0.920711E+09 | 0.428442E+09 | 0.486675E+09 | 0.505857E+09 | 0.670394E+09 |
Maximum of Months | 0.405587E+10 | 0.192660E+10 | 0.212927E+10 | 0.525183E+10 | 0.442008E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.80 | 2625.03 | 331.29 | 0.00 | 331.29 | 0.00 | 0.00 |
February | 28.98 | 2097.36 | 420.02 | 0.00 | 420.02 | 0.00 | 0.00 |
March | 213.30 | 1327.36 | 629.48 | 0.00 | 629.48 | 0.00 | 0.00 |
April | 423.71 | 906.82 | 726.69 | 3.58 | 723.11 | 0.00 | 0.00 |
May | 852.07 | 539.23 | 947.61 | 35.62 | 911.99 | 0.00 | 0.00 |
June | 1274.20 | 374.55 | 1107.54 | 100.52 | 1007.02 | 0.00 | 0.00 |
July | 1245.16 | 329.59 | 1038.70 | 69.48 | 969.22 | 0.00 | 0.00 |
August | 1038.35 | 386.33 | 869.70 | 15.41 | 854.28 | 0.00 | 0.00 |
September | 635.42 | 658.87 | 666.81 | 0.17 | 666.64 | 0.00 | 0.00 |
October | 256.45 | 982.22 | 495.78 | 0.00 | 495.78 | 0.00 | 0.00 |
November | 65.92 | 1544.54 | 346.81 | 0.00 | 346.81 | 0.00 | 0.00 |
December | 0.57 | 2302.38 | 224.96 | 0.00 | 224.96 | 0.00 | 0.00 |
Annual Sum or Average | 505.83 | 1168.56 | 651.67 | 18.81 | 632.86 | 0.00 | 0.00 |
Minimum of Months | 0.57 | 329.59 | 224.96 | 0.00 | 224.96 | 0.00 | 0.00 |
Maximum of Months | 1274.20 | 2625.03 | 1107.54 | 100.52 | 1007.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 210.59 | 1580.87 | 473.26 | 194.75 | 278.51 | 0.00 | 0.00 |
February | 370.50 | 1243.33 | 627.31 | 275.84 | 351.47 | 0.00 | 0.00 |
March | 671.56 | 814.40 | 852.32 | 338.31 | 514.01 | 0.00 | 0.00 |
April | 1018.22 | 583.37 | 1046.57 | 458.32 | 588.24 | 0.00 | 0.00 |
May | 1482.63 | 363.24 | 1314.40 | 574.33 | 740.07 | 0.00 | 0.00 |
June | 1809.93 | 251.16 | 1446.47 | 629.91 | 816.55 | 0.00 | 0.00 |
July | 1870.79 | 220.85 | 1462.01 | 674.60 | 787.40 | 0.00 | 0.00 |
August | 1581.02 | 257.15 | 1232.44 | 531.33 | 701.11 | 0.00 | 0.00 |
September | 1307.62 | 424.38 | 1099.23 | 519.44 | 579.79 | 0.00 | 0.00 |
October | 643.67 | 616.43 | 700.50 | 292.59 | 407.91 | 0.00 | 0.00 |
November | 230.48 | 957.69 | 413.30 | 134.25 | 279.06 | 0.00 | 0.00 |
December | 147.69 | 1420.17 | 320.15 | 137.48 | 182.67 | 0.00 | 0.00 |
Annual Sum or Average | 948.52 | 725.42 | 917.09 | 397.33 | 519.76 | 0.00 | 0.00 |
Minimum of Months | 147.69 | 220.85 | 320.15 | 134.25 | 182.67 | 0.00 | 0.00 |
Maximum of Months | 1870.79 | 1580.87 | 1462.01 | 674.60 | 816.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1846.23 | 2143.80 | 2060.28 | 1409.89 | 650.39 | 0.00 | 0.00 |
February | 2064.33 | 1719.95 | 2207.55 | 1491.44 | 716.11 | 0.00 | 0.00 |
March | 1887.60 | 1241.98 | 1921.07 | 1011.57 | 909.50 | 0.00 | 0.00 |
April | 1891.57 | 929.28 | 1730.76 | 809.16 | 921.60 | 0.00 | 0.00 |
May | 1660.14 | 588.94 | 1433.87 | 388.74 | 1045.13 | 0.00 | 0.00 |
June | 1789.57 | 401.19 | 1392.07 | 283.43 | 1108.64 | 0.00 | 0.00 |
July | 1975.23 | 351.41 | 1473.61 | 371.31 | 1102.30 | 0.00 | 0.00 |
August | 2260.65 | 414.14 | 1660.27 | 595.41 | 1064.86 | 0.00 | 0.00 |
September | 2561.06 | 671.40 | 2011.89 | 1060.10 | 951.79 | 0.00 | 0.00 |
October | 2356.55 | 953.12 | 2100.83 | 1317.98 | 782.86 | 0.00 | 0.00 |
November | 1516.80 | 1376.12 | 1585.08 | 992.29 | 592.79 | 0.00 | 0.00 |
December | 1626.87 | 1982.33 | 1690.25 | 1280.35 | 409.91 | 0.00 | 0.00 |
Annual Sum or Average | 1952.28 | 1061.49 | 1769.73 | 914.36 | 855.37 | 0.00 | 0.00 |
Minimum of Months | 1516.80 | 351.41 | 1392.07 | 283.43 | 409.91 | 0.00 | 0.00 |
Maximum of Months | 2561.06 | 2143.80 | 2207.55 | 1491.44 | 1108.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 218.17 | 1619.07 | 469.36 | 189.91 | 279.45 | 0.00 | 0.00 |
February | 456.96 | 1289.43 | 688.24 | 339.14 | 349.09 | 0.00 | 0.00 |
March | 635.81 | 841.77 | 821.61 | 305.68 | 515.93 | 0.00 | 0.00 |
April | 1240.57 | 608.23 | 1198.49 | 592.63 | 605.86 | 0.00 | 0.00 |
May | 1364.77 | 383.31 | 1201.95 | 480.15 | 721.80 | 0.00 | 0.00 |
June | 1776.88 | 269.80 | 1410.35 | 611.21 | 799.14 | 0.00 | 0.00 |
July | 1959.94 | 241.81 | 1514.29 | 719.31 | 794.98 | 0.00 | 0.00 |
August | 1724.42 | 277.02 | 1323.87 | 607.57 | 716.30 | 0.00 | 0.00 |
September | 1283.33 | 443.44 | 1071.63 | 508.65 | 562.98 | 0.00 | 0.00 |
October | 717.95 | 644.50 | 746.76 | 332.00 | 414.76 | 0.00 | 0.00 |
November | 288.07 | 980.33 | 446.98 | 165.29 | 281.69 | 0.00 | 0.00 |
December | 191.17 | 1450.46 | 343.75 | 162.05 | 181.70 | 0.00 | 0.00 |
Annual Sum or Average | 990.79 | 751.66 | 937.43 | 417.88 | 519.55 | 0.00 | 0.00 |
Minimum of Months | 191.17 | 241.81 | 343.75 | 162.05 | 181.70 | 0.00 | 0.00 |
Maximum of Months | 1959.94 | 1619.07 | 1514.29 | 719.31 | 799.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.95 | 2632.57 | 331.29 | 0.00 | 331.29 | 0.00 | 0.00 |
February | 29.16 | 2112.84 | 420.01 | 0.00 | 420.01 | 0.00 | 0.00 |
March | 228.22 | 1331.41 | 629.47 | 0.00 | 629.47 | 0.00 | 0.00 |
April | 456.33 | 889.94 | 726.68 | 3.58 | 723.10 | 0.00 | 0.00 |
May | 901.53 | 511.96 | 947.61 | 35.62 | 911.99 | 0.00 | 0.00 |
June | 1305.28 | 364.50 | 1107.54 | 100.52 | 1007.01 | 0.00 | 0.00 |
July | 1268.98 | 323.80 | 1038.70 | 69.48 | 969.22 | 0.00 | 0.00 |
August | 1047.67 | 392.41 | 869.69 | 15.41 | 854.28 | 0.00 | 0.00 |
September | 628.55 | 703.29 | 666.80 | 0.17 | 666.64 | 0.00 | 0.00 |
October | 236.24 | 1075.07 | 495.78 | 0.00 | 495.78 | 0.00 | 0.00 |
November | 57.41 | 1643.10 | 346.80 | 0.00 | 346.80 | 0.00 | 0.00 |
December | 0.24 | 2362.15 | 224.96 | 0.00 | 224.96 | 0.00 | 0.00 |
Annual Sum or Average | 516.37 | 1190.95 | 651.67 | 18.81 | 632.86 | 0.00 | 0.00 |
Minimum of Months | 0.24 | 323.80 | 224.96 | 0.00 | 224.96 | 0.00 | 0.00 |
Maximum of Months | 1305.28 | 2632.57 | 1107.54 | 100.52 | 1007.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 213.34 | 1592.74 | 473.26 | 194.75 | 278.51 | 0.00 | 0.00 |
February | 374.21 | 1263.85 | 627.30 | 275.84 | 351.47 | 0.00 | 0.00 |
March | 685.14 | 825.27 | 852.31 | 338.31 | 514.01 | 0.00 | 0.00 |
April | 1041.16 | 584.33 | 1046.56 | 458.32 | 588.24 | 0.00 | 0.00 |
May | 1506.50 | 361.21 | 1314.39 | 574.33 | 740.07 | 0.00 | 0.00 |
June | 1826.59 | 254.65 | 1446.45 | 629.91 | 816.55 | 0.00 | 0.00 |
July | 1883.66 | 226.72 | 1461.99 | 674.59 | 787.40 | 0.00 | 0.00 |
August | 1587.30 | 269.65 | 1232.43 | 531.33 | 701.11 | 0.00 | 0.00 |
September | 1302.20 | 464.42 | 1099.22 | 519.44 | 579.78 | 0.00 | 0.00 |
October | 622.97 | 686.88 | 700.50 | 292.59 | 407.91 | 0.00 | 0.00 |
November | 220.26 | 1023.37 | 413.30 | 134.25 | 279.05 | 0.00 | 0.00 |
December | 146.44 | 1461.24 | 320.15 | 137.48 | 182.67 | 0.00 | 0.00 |
Annual Sum or Average | 953.95 | 748.84 | 917.09 | 397.33 | 519.76 | 0.00 | 0.00 |
Minimum of Months | 146.44 | 226.72 | 320.15 | 134.25 | 182.67 | 0.00 | 0.00 |
Maximum of Months | 1883.66 | 1592.74 | 1461.99 | 674.59 | 816.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1909.60 | 2088.17 | 2060.30 | 1409.91 | 650.39 | 0.00 | 0.00 |
February | 2126.54 | 1717.14 | 2207.58 | 1491.46 | 716.12 | 0.00 | 0.00 |
March | 1944.11 | 1236.72 | 1921.09 | 1011.58 | 909.51 | 0.00 | 0.00 |
April | 1944.49 | 916.48 | 1730.77 | 809.17 | 921.60 | 0.00 | 0.00 |
May | 1719.42 | 564.96 | 1433.88 | 388.75 | 1045.14 | 0.00 | 0.00 |
June | 1828.50 | 391.33 | 1392.08 | 283.44 | 1108.65 | 0.00 | 0.00 |
July | 2000.99 | 352.64 | 1473.62 | 371.31 | 1102.31 | 0.00 | 0.00 |
August | 2277.03 | 432.58 | 1660.28 | 595.42 | 1064.86 | 0.00 | 0.00 |
September | 2568.53 | 727.25 | 2011.91 | 1060.11 | 951.80 | 0.00 | 0.00 |
October | 2357.22 | 1058.11 | 2100.86 | 1317.99 | 782.86 | 0.00 | 0.00 |
November | 1523.41 | 1455.52 | 1585.09 | 992.30 | 592.79 | 0.00 | 0.00 |
December | 1653.98 | 1988.90 | 1690.27 | 1280.36 | 409.91 | 0.00 | 0.00 |
Annual Sum or Average | 1986.91 | 1074.47 | 1769.75 | 914.37 | 855.37 | 0.00 | 0.00 |
Minimum of Months | 1523.41 | 352.64 | 1392.08 | 283.44 | 409.91 | 0.00 | 0.00 |
Maximum of Months | 2568.53 | 2088.17 | 2207.58 | 1491.46 | 1108.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 223.24 | 1629.61 | 469.36 | 189.91 | 279.45 | 0.00 | 0.00 |
February | 465.22 | 1308.59 | 688.23 | 339.14 | 349.09 | 0.00 | 0.00 |
March | 652.81 | 852.42 | 821.60 | 305.68 | 515.92 | 0.00 | 0.00 |
April | 1263.63 | 614.04 | 1198.48 | 592.62 | 605.85 | 0.00 | 0.00 |
May | 1388.84 | 379.47 | 1201.94 | 480.15 | 721.80 | 0.00 | 0.00 |
June | 1792.25 | 273.12 | 1410.34 | 611.20 | 799.14 | 0.00 | 0.00 |
July | 1970.36 | 250.42 | 1514.28 | 719.30 | 794.97 | 0.00 | 0.00 |
August | 1729.49 | 292.68 | 1323.86 | 607.56 | 716.30 | 0.00 | 0.00 |
September | 1276.45 | 484.62 | 1071.63 | 508.65 | 562.98 | 0.00 | 0.00 |
October | 703.93 | 716.24 | 746.75 | 332.00 | 414.76 | 0.00 | 0.00 |
November | 280.70 | 1047.41 | 446.98 | 165.29 | 281.69 | 0.00 | 0.00 |
December | 192.37 | 1491.66 | 343.75 | 162.05 | 181.70 | 0.00 | 0.00 |
Annual Sum or Average | 997.56 | 775.90 | 937.43 | 417.88 | 519.55 | 0.00 | 0.00 |
Minimum of Months | 192.37 | 250.42 | 343.75 | 162.05 | 181.70 | 0.00 | 0.00 |
Maximum of Months | 1970.36 | 1629.61 | 1514.28 | 719.30 | 799.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.53 | 2676.14 | 331.29 | 0.00 | 331.29 | 0.00 | 0.00 |
February | 25.70 | 2165.00 | 420.02 | 0.00 | 420.02 | 0.00 | 0.00 |
March | 204.48 | 1388.24 | 629.48 | 0.00 | 629.48 | 0.00 | 0.00 |
April | 414.18 | 963.28 | 726.69 | 3.58 | 723.11 | 0.00 | 0.00 |
May | 840.42 | 565.67 | 947.61 | 35.62 | 911.99 | 0.00 | 0.00 |
June | 1270.12 | 390.59 | 1107.54 | 100.52 | 1007.02 | 0.00 | 0.00 |
July | 1245.05 | 340.38 | 1038.70 | 69.48 | 969.22 | 0.00 | 0.00 |
August | 1034.81 | 402.31 | 869.70 | 15.41 | 854.28 | 0.00 | 0.00 |
September | 622.16 | 703.23 | 666.81 | 0.17 | 666.64 | 0.00 | 0.00 |
October | 234.41 | 1063.37 | 495.78 | 0.00 | 495.78 | 0.00 | 0.00 |
November | 56.56 | 1631.61 | 346.81 | 0.00 | 346.81 | 0.00 | 0.00 |
December | 0.19 | 2374.61 | 224.96 | 0.00 | 224.96 | 0.00 | 0.00 |
Annual Sum or Average | 498.62 | 1217.57 | 651.67 | 18.81 | 632.86 | 0.00 | 0.00 |
Minimum of Months | 0.19 | 340.38 | 224.96 | 0.00 | 224.96 | 0.00 | 0.00 |
Maximum of Months | 1270.12 | 2676.14 | 1107.54 | 100.52 | 1007.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 208.07 | 1611.43 | 473.26 | 194.75 | 278.51 | 0.00 | 0.00 |
February | 364.78 | 1284.45 | 627.31 | 275.84 | 351.47 | 0.00 | 0.00 |
March | 662.65 | 851.85 | 852.32 | 338.31 | 514.01 | 0.00 | 0.00 |
April | 1011.94 | 615.76 | 1046.57 | 458.32 | 588.24 | 0.00 | 0.00 |
May | 1478.69 | 378.52 | 1314.40 | 574.33 | 740.07 | 0.00 | 0.00 |
June | 1809.45 | 261.13 | 1446.47 | 629.91 | 816.55 | 0.00 | 0.00 |
July | 1872.76 | 227.40 | 1462.01 | 674.60 | 787.40 | 0.00 | 0.00 |
August | 1580.72 | 266.49 | 1232.44 | 531.33 | 701.11 | 0.00 | 0.00 |
September | 1300.87 | 448.98 | 1099.23 | 519.44 | 579.79 | 0.00 | 0.00 |
October | 625.92 | 663.24 | 700.50 | 292.59 | 407.91 | 0.00 | 0.00 |
November | 220.34 | 1009.48 | 413.30 | 134.25 | 279.06 | 0.00 | 0.00 |
December | 144.36 | 1464.54 | 320.15 | 137.48 | 182.67 | 0.00 | 0.00 |
Annual Sum or Average | 943.18 | 754.50 | 917.09 | 397.33 | 519.76 | 0.00 | 0.00 |
Minimum of Months | 144.36 | 227.40 | 320.15 | 134.25 | 182.67 | 0.00 | 0.00 |
Maximum of Months | 1872.76 | 1611.43 | 1462.01 | 674.60 | 816.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1837.36 | 2194.39 | 2060.28 | 1409.89 | 650.39 | 0.00 | 0.00 |
February | 2050.62 | 1784.66 | 2207.55 | 1491.44 | 716.11 | 0.00 | 0.00 |
March | 1875.06 | 1302.01 | 1921.07 | 1011.57 | 909.50 | 0.00 | 0.00 |
April | 1883.81 | 984.45 | 1730.76 | 809.16 | 921.60 | 0.00 | 0.00 |
May | 1654.01 | 618.13 | 1433.87 | 388.74 | 1045.13 | 0.00 | 0.00 |
June | 1787.85 | 420.14 | 1392.07 | 283.43 | 1108.64 | 0.00 | 0.00 |
July | 1976.91 | 364.16 | 1473.61 | 371.31 | 1102.30 | 0.00 | 0.00 |
August | 2260.90 | 431.63 | 1660.27 | 595.41 | 1064.86 | 0.00 | 0.00 |
September | 2551.85 | 712.89 | 2011.89 | 1060.10 | 951.79 | 0.00 | 0.00 |
October | 2333.06 | 1027.66 | 2100.83 | 1317.98 | 782.86 | 0.00 | 0.00 |
November | 1495.30 | 1455.35 | 1585.08 | 992.29 | 592.79 | 0.00 | 0.00 |
December | 1615.81 | 2050.73 | 1690.25 | 1280.35 | 409.91 | 0.00 | 0.00 |
Annual Sum or Average | 1942.82 | 1109.06 | 1769.73 | 914.36 | 855.37 | 0.00 | 0.00 |
Minimum of Months | 1495.30 | 364.16 | 1392.07 | 283.43 | 409.91 | 0.00 | 0.00 |
Maximum of Months | 2551.85 | 2194.39 | 2207.55 | 1491.44 | 1108.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 216.99 | 1650.27 | 469.36 | 189.91 | 279.45 | 0.00 | 0.00 |
February | 453.30 | 1331.21 | 688.24 | 339.14 | 349.09 | 0.00 | 0.00 |
March | 629.79 | 881.10 | 821.61 | 305.68 | 515.93 | 0.00 | 0.00 |
April | 1235.80 | 643.93 | 1198.49 | 592.63 | 605.86 | 0.00 | 0.00 |
May | 1359.28 | 402.40 | 1201.95 | 480.15 | 721.80 | 0.00 | 0.00 |
June | 1775.44 | 281.97 | 1410.35 | 611.21 | 799.14 | 0.00 | 0.00 |
July | 1960.81 | 250.30 | 1514.29 | 719.31 | 794.98 | 0.00 | 0.00 |
August | 1723.39 | 288.48 | 1323.87 | 607.57 | 716.30 | 0.00 | 0.00 |
September | 1275.32 | 471.15 | 1071.63 | 508.65 | 562.98 | 0.00 | 0.00 |
October | 704.10 | 695.06 | 746.76 | 332.00 | 414.76 | 0.00 | 0.00 |
November | 279.52 | 1033.81 | 446.98 | 165.29 | 281.69 | 0.00 | 0.00 |
December | 188.87 | 1495.58 | 343.75 | 162.05 | 181.70 | 0.00 | 0.00 |
Annual Sum or Average | 986.18 | 782.90 | 937.43 | 417.88 | 519.55 | 0.00 | 0.00 |
Minimum of Months | 188.87 | 250.30 | 343.75 | 162.05 | 181.70 | 0.00 | 0.00 |
Maximum of Months | 1960.81 | 1650.27 | 1514.29 | 719.31 | 799.14 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4826241.59 | 0.703087E+10 | 0.887339E+09 | 0.00 | 0.887339E+09 | 0.00 | 0.00 |
February | 70113219.65 | 0.507393E+10 | 0.101610E+10 | 0.00 | 0.101610E+10 | 0.00 | 0.00 |
March | 0.571312E+09 | 0.355520E+10 | 0.168599E+10 | 0.00 | 0.168599E+10 | 0.00 | 0.00 |
April | 0.109826E+10 | 0.235048E+10 | 0.188357E+10 | 9280265.68 | 0.187429E+10 | 0.00 | 0.00 |
May | 0.228220E+10 | 0.144428E+10 | 0.253809E+10 | 95400764.26 | 0.244268E+10 | 0.00 | 0.00 |
June | 0.330272E+10 | 0.970837E+09 | 0.287075E+10 | 0.260558E+09 | 0.261019E+10 | 0.00 | 0.00 |
July | 0.333503E+10 | 0.882766E+09 | 0.278206E+10 | 0.186089E+09 | 0.259597E+10 | 0.00 | 0.00 |
August | 0.278112E+10 | 0.103473E+10 | 0.232940E+10 | 41283426.32 | 0.228811E+10 | 0.00 | 0.00 |
September | 0.164701E+10 | 0.170779E+10 | 0.172837E+10 | 428557.81 | 0.172794E+10 | 0.00 | 0.00 |
October | 0.686884E+09 | 0.263077E+10 | 0.132791E+10 | 0.00 | 0.132791E+10 | 0.00 | 0.00 |
November | 0.170857E+09 | 0.400345E+10 | 0.898922E+09 | 0.00 | 0.898922E+09 | 0.00 | 0.00 |
December | 1532841.53 | 0.616669E+10 | 0.602531E+09 | 0.00 | 0.602531E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.159519E+11 | 0.368518E+11 | 0.205510E+11 | 0.593040E+09 | 0.199580E+11 | 0.00 | 0.00 |
Minimum of Months | 1532841.53 | 0.882766E+09 | 0.602531E+09 | 0.00 | 0.602531E+09 | 0.00 | 0.00 |
Maximum of Months | 0.333503E+10 | 0.703087E+10 | 0.287075E+10 | 0.260558E+09 | 0.261019E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.564044E+09 | 0.423420E+10 | 0.126759E+10 | 0.521614E+09 | 0.745972E+09 | 0.00 | 0.00 |
February | 0.896313E+09 | 0.300786E+10 | 0.151758E+10 | 0.667309E+09 | 0.850272E+09 | 0.00 | 0.00 |
March | 0.179871E+10 | 0.218129E+10 | 0.228285E+10 | 0.906129E+09 | 0.137672E+10 | 0.00 | 0.00 |
April | 0.263924E+10 | 0.151209E+10 | 0.271270E+10 | 0.118797E+10 | 0.152472E+10 | 0.00 | 0.00 |
May | 0.397109E+10 | 0.972908E+09 | 0.352050E+10 | 0.153829E+10 | 0.198220E+10 | 0.00 | 0.00 |
June | 0.469134E+10 | 0.651011E+09 | 0.374924E+10 | 0.163273E+10 | 0.211651E+10 | 0.00 | 0.00 |
July | 0.501071E+10 | 0.591529E+09 | 0.391584E+10 | 0.180685E+10 | 0.210899E+10 | 0.00 | 0.00 |
August | 0.423461E+10 | 0.688744E+09 | 0.330098E+10 | 0.142312E+10 | 0.187786E+10 | 0.00 | 0.00 |
September | 0.338936E+10 | 0.110000E+10 | 0.284920E+10 | 0.134639E+10 | 0.150281E+10 | 0.00 | 0.00 |
October | 0.172401E+10 | 0.165104E+10 | 0.187623E+10 | 0.783685E+09 | 0.109255E+10 | 0.00 | 0.00 |
November | 0.597396E+09 | 0.248233E+10 | 0.107128E+10 | 0.347972E+09 | 0.723311E+09 | 0.00 | 0.00 |
December | 0.395569E+09 | 0.380378E+10 | 0.857486E+09 | 0.368225E+09 | 0.489262E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.299124E+11 | 0.228768E+11 | 0.289215E+11 | 0.125303E+11 | 0.163912E+11 | 0.00 | 0.00 |
Minimum of Months | 0.395569E+09 | 0.591529E+09 | 0.857486E+09 | 0.347972E+09 | 0.489262E+09 | 0.00 | 0.00 |
Maximum of Months | 0.501071E+10 | 0.423420E+10 | 0.391584E+10 | 0.180685E+10 | 0.211651E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.494495E+10 | 0.574196E+10 | 0.551825E+10 | 0.377626E+10 | 0.174200E+10 | 0.00 | 0.00 |
February | 0.499402E+10 | 0.416090E+10 | 0.534051E+10 | 0.360809E+10 | 0.173242E+10 | 0.00 | 0.00 |
March | 0.505574E+10 | 0.332651E+10 | 0.514539E+10 | 0.270939E+10 | 0.243600E+10 | 0.00 | 0.00 |
April | 0.490296E+10 | 0.240868E+10 | 0.448612E+10 | 0.209734E+10 | 0.238878E+10 | 0.00 | 0.00 |
May | 0.444653E+10 | 0.157741E+10 | 0.384049E+10 | 0.104120E+10 | 0.279928E+10 | 0.00 | 0.00 |
June | 0.463856E+10 | 0.103988E+10 | 0.360826E+10 | 0.734658E+09 | 0.287360E+10 | 0.00 | 0.00 |
July | 0.529046E+10 | 0.941208E+09 | 0.394691E+10 | 0.994514E+09 | 0.295240E+10 | 0.00 | 0.00 |
August | 0.605492E+10 | 0.110922E+10 | 0.444686E+10 | 0.159474E+10 | 0.285211E+10 | 0.00 | 0.00 |
September | 0.663827E+10 | 0.174028E+10 | 0.521482E+10 | 0.274778E+10 | 0.246704E+10 | 0.00 | 0.00 |
October | 0.631179E+10 | 0.255285E+10 | 0.562688E+10 | 0.353007E+10 | 0.209681E+10 | 0.00 | 0.00 |
November | 0.393155E+10 | 0.356691E+10 | 0.410852E+10 | 0.257201E+10 | 0.153651E+10 | 0.00 | 0.00 |
December | 0.435740E+10 | 0.530948E+10 | 0.452717E+10 | 0.342928E+10 | 0.109790E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.615671E+11 | 0.334753E+11 | 0.558102E+11 | 0.288353E+11 | 0.269748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.393155E+10 | 0.941208E+09 | 0.360826E+10 | 0.734658E+09 | 0.109790E+10 | 0.00 | 0.00 |
Maximum of Months | 0.663827E+10 | 0.574196E+10 | 0.562688E+10 | 0.377626E+10 | 0.295240E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.584355E+09 | 0.433652E+10 | 0.125714E+10 | 0.508652E+09 | 0.748485E+09 | 0.00 | 0.00 |
February | 0.110548E+10 | 0.311939E+10 | 0.166498E+10 | 0.820450E+09 | 0.844529E+09 | 0.00 | 0.00 |
March | 0.170296E+10 | 0.225458E+10 | 0.220060E+10 | 0.818743E+09 | 0.138186E+10 | 0.00 | 0.00 |
April | 0.321557E+10 | 0.157653E+10 | 0.310648E+10 | 0.153609E+10 | 0.157038E+10 | 0.00 | 0.00 |
May | 0.365540E+10 | 0.102666E+10 | 0.321931E+10 | 0.128604E+10 | 0.193328E+10 | 0.00 | 0.00 |
June | 0.460568E+10 | 0.699329E+09 | 0.365563E+10 | 0.158426E+10 | 0.207137E+10 | 0.00 | 0.00 |
July | 0.524950E+10 | 0.647677E+09 | 0.405587E+10 | 0.192660E+10 | 0.212927E+10 | 0.00 | 0.00 |
August | 0.461868E+10 | 0.741978E+09 | 0.354585E+10 | 0.162731E+10 | 0.191854E+10 | 0.00 | 0.00 |
September | 0.332638E+10 | 0.114941E+10 | 0.277767E+10 | 0.131842E+10 | 0.145925E+10 | 0.00 | 0.00 |
October | 0.192296E+10 | 0.172623E+10 | 0.200012E+10 | 0.889228E+09 | 0.111089E+10 | 0.00 | 0.00 |
November | 0.746670E+09 | 0.254102E+10 | 0.115858E+10 | 0.428442E+09 | 0.730140E+09 | 0.00 | 0.00 |
December | 0.512022E+09 | 0.388492E+10 | 0.920711E+09 | 0.434035E+09 | 0.486675E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.312456E+11 | 0.237042E+11 | 0.295629E+11 | 0.131783E+11 | 0.163847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.512022E+09 | 0.647677E+09 | 0.920711E+09 | 0.428442E+09 | 0.486675E+09 | 0.00 | 0.00 |
Maximum of Months | 0.524950E+10 | 0.433652E+10 | 0.405587E+10 | 0.192660E+10 | 0.212927E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 5222917.13 | 0.705108E+10 | 0.887334E+09 | 0.00 | 0.887334E+09 | 0.00 | 0.00 |
February | 70550800.71 | 0.511139E+10 | 0.101610E+10 | 0.00 | 0.101610E+10 | 0.00 | 0.00 |
March | 0.611272E+09 | 0.356604E+10 | 0.168598E+10 | 0.00 | 0.168598E+10 | 0.00 | 0.00 |
April | 0.118282E+10 | 0.230672E+10 | 0.188356E+10 | 9280217.59 | 0.187428E+10 | 0.00 | 0.00 |
May | 0.241467E+10 | 0.137125E+10 | 0.253807E+10 | 95400269.92 | 0.244267E+10 | 0.00 | 0.00 |
June | 0.338330E+10 | 0.944782E+09 | 0.287073E+10 | 0.260556E+09 | 0.261018E+10 | 0.00 | 0.00 |
July | 0.339884E+10 | 0.867255E+09 | 0.278204E+10 | 0.186088E+09 | 0.259595E+10 | 0.00 | 0.00 |
August | 0.280608E+10 | 0.105104E+10 | 0.232938E+10 | 41283212.39 | 0.228810E+10 | 0.00 | 0.00 |
September | 0.162920E+10 | 0.182294E+10 | 0.172836E+10 | 428555.59 | 0.172793E+10 | 0.00 | 0.00 |
October | 0.632738E+09 | 0.287947E+10 | 0.132790E+10 | 0.00 | 0.132790E+10 | 0.00 | 0.00 |
November | 0.148804E+09 | 0.425891E+10 | 0.898917E+09 | 0.00 | 0.898917E+09 | 0.00 | 0.00 |
December | 649674.93 | 0.632679E+10 | 0.602528E+09 | 0.00 | 0.602528E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.162841E+11 | 0.375576E+11 | 0.205509E+11 | 0.593037E+09 | 0.199579E+11 | 0.00 | 0.00 |
Minimum of Months | 649674.93 | 0.867255E+09 | 0.602528E+09 | 0.00 | 0.602528E+09 | 0.00 | 0.00 |
Maximum of Months | 0.339884E+10 | 0.705108E+10 | 0.287073E+10 | 0.260556E+09 | 0.261018E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.571423E+09 | 0.426600E+10 | 0.126758E+10 | 0.521609E+09 | 0.745967E+09 | 0.00 | 0.00 |
February | 0.905282E+09 | 0.305749E+10 | 0.151757E+10 | 0.667302E+09 | 0.850266E+09 | 0.00 | 0.00 |
March | 0.183507E+10 | 0.221041E+10 | 0.228283E+10 | 0.906120E+09 | 0.137671E+10 | 0.00 | 0.00 |
April | 0.269869E+10 | 0.151459E+10 | 0.271268E+10 | 0.118796E+10 | 0.152472E+10 | 0.00 | 0.00 |
May | 0.403502E+10 | 0.967453E+09 | 0.352047E+10 | 0.153828E+10 | 0.198219E+10 | 0.00 | 0.00 |
June | 0.473453E+10 | 0.660063E+09 | 0.374921E+10 | 0.163271E+10 | 0.211650E+10 | 0.00 | 0.00 |
July | 0.504520E+10 | 0.607235E+09 | 0.391581E+10 | 0.180683E+10 | 0.210897E+10 | 0.00 | 0.00 |
August | 0.425141E+10 | 0.722220E+09 | 0.330095E+10 | 0.142311E+10 | 0.187784E+10 | 0.00 | 0.00 |
September | 0.337531E+10 | 0.120378E+10 | 0.284918E+10 | 0.134638E+10 | 0.150280E+10 | 0.00 | 0.00 |
October | 0.166856E+10 | 0.183973E+10 | 0.187622E+10 | 0.783677E+09 | 0.109254E+10 | 0.00 | 0.00 |
November | 0.570925E+09 | 0.265259E+10 | 0.107127E+10 | 0.347968E+09 | 0.723307E+09 | 0.00 | 0.00 |
December | 0.392237E+09 | 0.391379E+10 | 0.857480E+09 | 0.368221E+09 | 0.489259E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.300837E+11 | 0.236153E+11 | 0.289212E+11 | 0.125302E+11 | 0.163911E+11 | 0.00 | 0.00 |
Minimum of Months | 0.392237E+09 | 0.607235E+09 | 0.857480E+09 | 0.347968E+09 | 0.489259E+09 | 0.00 | 0.00 |
Maximum of Months | 0.504520E+10 | 0.426600E+10 | 0.391581E+10 | 0.180683E+10 | 0.211650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.511466E+10 | 0.559294E+10 | 0.551831E+10 | 0.377630E+10 | 0.174201E+10 | 0.00 | 0.00 |
February | 0.514451E+10 | 0.415411E+10 | 0.534057E+10 | 0.360813E+10 | 0.173244E+10 | 0.00 | 0.00 |
March | 0.520711E+10 | 0.331244E+10 | 0.514544E+10 | 0.270942E+10 | 0.243602E+10 | 0.00 | 0.00 |
April | 0.504012E+10 | 0.237552E+10 | 0.448616E+10 | 0.209737E+10 | 0.238879E+10 | 0.00 | 0.00 |
May | 0.460529E+10 | 0.151318E+10 | 0.384052E+10 | 0.104122E+10 | 0.279930E+10 | 0.00 | 0.00 |
June | 0.473946E+10 | 0.101434E+10 | 0.360828E+10 | 0.734667E+09 | 0.287362E+10 | 0.00 | 0.00 |
July | 0.535946E+10 | 0.944524E+09 | 0.394694E+10 | 0.994526E+09 | 0.295242E+10 | 0.00 | 0.00 |
August | 0.609880E+10 | 0.115862E+10 | 0.444689E+10 | 0.159476E+10 | 0.285213E+10 | 0.00 | 0.00 |
September | 0.665763E+10 | 0.188503E+10 | 0.521487E+10 | 0.274781E+10 | 0.246706E+10 | 0.00 | 0.00 |
October | 0.631358E+10 | 0.283403E+10 | 0.562693E+10 | 0.353011E+10 | 0.209682E+10 | 0.00 | 0.00 |
November | 0.394869E+10 | 0.377270E+10 | 0.410856E+10 | 0.257204E+10 | 0.153652E+10 | 0.00 | 0.00 |
December | 0.443001E+10 | 0.532706E+10 | 0.452722E+10 | 0.342932E+10 | 0.109791E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.626593E+11 | 0.338845E+11 | 0.558107E+11 | 0.288357E+11 | 0.269750E+11 | 0.00 | 0.00 |
Minimum of Months | 0.394869E+10 | 0.944524E+09 | 0.360828E+10 | 0.734667E+09 | 0.109791E+10 | 0.00 | 0.00 |
Maximum of Months | 0.665763E+10 | 0.559294E+10 | 0.562693E+10 | 0.377630E+10 | 0.295242E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.597935E+09 | 0.436475E+10 | 0.125713E+10 | 0.508647E+09 | 0.748480E+09 | 0.00 | 0.00 |
February | 0.112547E+10 | 0.316574E+10 | 0.166497E+10 | 0.820442E+09 | 0.844524E+09 | 0.00 | 0.00 |
March | 0.174848E+10 | 0.228312E+10 | 0.220059E+10 | 0.818735E+09 | 0.138185E+10 | 0.00 | 0.00 |
April | 0.327534E+10 | 0.159159E+10 | 0.310645E+10 | 0.153608E+10 | 0.157037E+10 | 0.00 | 0.00 |
May | 0.371987E+10 | 0.101637E+10 | 0.321929E+10 | 0.128602E+10 | 0.193327E+10 | 0.00 | 0.00 |
June | 0.464550E+10 | 0.707918E+09 | 0.365560E+10 | 0.158424E+10 | 0.207136E+10 | 0.00 | 0.00 |
July | 0.527742E+10 | 0.670722E+09 | 0.405583E+10 | 0.192658E+10 | 0.212926E+10 | 0.00 | 0.00 |
August | 0.463227E+10 | 0.783909E+09 | 0.354582E+10 | 0.162729E+10 | 0.191853E+10 | 0.00 | 0.00 |
September | 0.330855E+10 | 0.125614E+10 | 0.277765E+10 | 0.131841E+10 | 0.145924E+10 | 0.00 | 0.00 |
October | 0.188541E+10 | 0.191837E+10 | 0.200010E+10 | 0.889219E+09 | 0.111088E+10 | 0.00 | 0.00 |
November | 0.727582E+09 | 0.271489E+10 | 0.115857E+10 | 0.428438E+09 | 0.730136E+09 | 0.00 | 0.00 |
December | 0.515255E+09 | 0.399526E+10 | 0.920703E+09 | 0.434031E+09 | 0.486672E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.314591E+11 | 0.244688E+11 | 0.295627E+11 | 0.131781E+11 | 0.163846E+11 | 0.00 | 0.00 |
Minimum of Months | 0.515255E+09 | 0.670722E+09 | 0.920703E+09 | 0.428438E+09 | 0.486672E+09 | 0.00 | 0.00 |
Maximum of Months | 0.527742E+10 | 0.436475E+10 | 0.405583E+10 | 0.192658E+10 | 0.212926E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4087477.42 | 0.716776E+10 | 0.887339E+09 | 0.00 | 0.887339E+09 | 0.00 | 0.00 |
February | 62169659.74 | 0.523756E+10 | 0.101610E+10 | 0.00 | 0.101610E+10 | 0.00 | 0.00 |
March | 0.547685E+09 | 0.371825E+10 | 0.168599E+10 | 0.00 | 0.168599E+10 | 0.00 | 0.00 |
April | 0.107356E+10 | 0.249682E+10 | 0.188357E+10 | 9280265.68 | 0.187429E+10 | 0.00 | 0.00 |
May | 0.225099E+10 | 0.151508E+10 | 0.253809E+10 | 95400764.26 | 0.244268E+10 | 0.00 | 0.00 |
June | 0.329216E+10 | 0.101240E+10 | 0.287075E+10 | 0.260558E+09 | 0.261019E+10 | 0.00 | 0.00 |
July | 0.333475E+10 | 0.911661E+09 | 0.278206E+10 | 0.186089E+09 | 0.259597E+10 | 0.00 | 0.00 |
August | 0.277163E+10 | 0.107754E+10 | 0.232940E+10 | 41283426.32 | 0.228811E+10 | 0.00 | 0.00 |
September | 0.161264E+10 | 0.182277E+10 | 0.172837E+10 | 428557.81 | 0.172794E+10 | 0.00 | 0.00 |
October | 0.627832E+09 | 0.284813E+10 | 0.132791E+10 | 0.00 | 0.132791E+10 | 0.00 | 0.00 |
November | 0.146593E+09 | 0.422914E+10 | 0.898922E+09 | 0.00 | 0.898922E+09 | 0.00 | 0.00 |
December | 519578.31 | 0.636017E+10 | 0.602531E+09 | 0.00 | 0.602531E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.157246E+11 | 0.383973E+11 | 0.205510E+11 | 0.593040E+09 | 0.199580E+11 | 0.00 | 0.00 |
Minimum of Months | 519578.31 | 0.911661E+09 | 0.602531E+09 | 0.00 | 0.602531E+09 | 0.00 | 0.00 |
Maximum of Months | 0.333475E+10 | 0.716776E+10 | 0.287075E+10 | 0.260558E+09 | 0.261019E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.557285E+09 | 0.431606E+10 | 0.126759E+10 | 0.521614E+09 | 0.745972E+09 | 0.00 | 0.00 |
February | 0.882473E+09 | 0.310734E+10 | 0.151758E+10 | 0.667309E+09 | 0.850272E+09 | 0.00 | 0.00 |
March | 0.177483E+10 | 0.228160E+10 | 0.228285E+10 | 0.906129E+09 | 0.137672E+10 | 0.00 | 0.00 |
April | 0.262295E+10 | 0.159605E+10 | 0.271270E+10 | 0.118797E+10 | 0.152472E+10 | 0.00 | 0.00 |
May | 0.396051E+10 | 0.101383E+10 | 0.352050E+10 | 0.153829E+10 | 0.198220E+10 | 0.00 | 0.00 |
June | 0.469010E+10 | 0.676839E+09 | 0.374924E+10 | 0.163273E+10 | 0.211651E+10 | 0.00 | 0.00 |
July | 0.501599E+10 | 0.609061E+09 | 0.391584E+10 | 0.180685E+10 | 0.210899E+10 | 0.00 | 0.00 |
August | 0.423379E+10 | 0.713776E+09 | 0.330098E+10 | 0.142312E+10 | 0.187786E+10 | 0.00 | 0.00 |
September | 0.337185E+10 | 0.116376E+10 | 0.284920E+10 | 0.134639E+10 | 0.150281E+10 | 0.00 | 0.00 |
October | 0.167646E+10 | 0.177642E+10 | 0.187623E+10 | 0.783685E+09 | 0.109255E+10 | 0.00 | 0.00 |
November | 0.571111E+09 | 0.261656E+10 | 0.107128E+10 | 0.347972E+09 | 0.723311E+09 | 0.00 | 0.00 |
December | 0.386667E+09 | 0.392263E+10 | 0.857486E+09 | 0.368225E+09 | 0.489262E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.297440E+11 | 0.237939E+11 | 0.289215E+11 | 0.125303E+11 | 0.163912E+11 | 0.00 | 0.00 |
Minimum of Months | 0.386667E+09 | 0.609061E+09 | 0.857486E+09 | 0.347972E+09 | 0.489262E+09 | 0.00 | 0.00 |
Maximum of Months | 0.501599E+10 | 0.431606E+10 | 0.391584E+10 | 0.180685E+10 | 0.211651E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.492118E+10 | 0.587745E+10 | 0.551825E+10 | 0.377626E+10 | 0.174200E+10 | 0.00 | 0.00 |
February | 0.496087E+10 | 0.431744E+10 | 0.534051E+10 | 0.360809E+10 | 0.173242E+10 | 0.00 | 0.00 |
March | 0.502216E+10 | 0.348730E+10 | 0.514539E+10 | 0.270939E+10 | 0.243600E+10 | 0.00 | 0.00 |
April | 0.488284E+10 | 0.255171E+10 | 0.448612E+10 | 0.209734E+10 | 0.238878E+10 | 0.00 | 0.00 |
May | 0.443010E+10 | 0.165560E+10 | 0.384049E+10 | 0.104120E+10 | 0.279928E+10 | 0.00 | 0.00 |
June | 0.463411E+10 | 0.108899E+10 | 0.360826E+10 | 0.734658E+09 | 0.287360E+10 | 0.00 | 0.00 |
July | 0.529495E+10 | 0.975378E+09 | 0.394691E+10 | 0.994514E+09 | 0.295240E+10 | 0.00 | 0.00 |
August | 0.605559E+10 | 0.115607E+10 | 0.444686E+10 | 0.159474E+10 | 0.285211E+10 | 0.00 | 0.00 |
September | 0.661440E+10 | 0.184781E+10 | 0.521482E+10 | 0.274778E+10 | 0.246704E+10 | 0.00 | 0.00 |
October | 0.624886E+10 | 0.275247E+10 | 0.562688E+10 | 0.353007E+10 | 0.209681E+10 | 0.00 | 0.00 |
November | 0.387581E+10 | 0.377227E+10 | 0.410852E+10 | 0.257201E+10 | 0.153651E+10 | 0.00 | 0.00 |
December | 0.432779E+10 | 0.549267E+10 | 0.452717E+10 | 0.342928E+10 | 0.109790E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.612687E+11 | 0.349752E+11 | 0.558102E+11 | 0.288353E+11 | 0.269748E+11 | 0.00 | 0.00 |
Minimum of Months | 0.387581E+10 | 0.975378E+09 | 0.360826E+10 | 0.734658E+09 | 0.109790E+10 | 0.00 | 0.00 |
Maximum of Months | 0.661440E+10 | 0.587745E+10 | 0.562688E+10 | 0.377626E+10 | 0.295240E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.581192E+09 | 0.442008E+10 | 0.125714E+10 | 0.508652E+09 | 0.748485E+09 | 0.00 | 0.00 |
February | 0.109663E+10 | 0.322046E+10 | 0.166498E+10 | 0.820450E+09 | 0.844529E+09 | 0.00 | 0.00 |
March | 0.168683E+10 | 0.235993E+10 | 0.220060E+10 | 0.818743E+09 | 0.138186E+10 | 0.00 | 0.00 |
April | 0.320320E+10 | 0.166907E+10 | 0.310648E+10 | 0.153609E+10 | 0.157038E+10 | 0.00 | 0.00 |
May | 0.364069E+10 | 0.107779E+10 | 0.321931E+10 | 0.128604E+10 | 0.193328E+10 | 0.00 | 0.00 |
June | 0.460194E+10 | 0.730865E+09 | 0.365563E+10 | 0.158426E+10 | 0.207137E+10 | 0.00 | 0.00 |
July | 0.525183E+10 | 0.670394E+09 | 0.405587E+10 | 0.192660E+10 | 0.212927E+10 | 0.00 | 0.00 |
August | 0.461592E+10 | 0.772676E+09 | 0.354585E+10 | 0.162731E+10 | 0.191854E+10 | 0.00 | 0.00 |
September | 0.330564E+10 | 0.122121E+10 | 0.277767E+10 | 0.131842E+10 | 0.145925E+10 | 0.00 | 0.00 |
October | 0.188585E+10 | 0.186165E+10 | 0.200012E+10 | 0.889228E+09 | 0.111089E+10 | 0.00 | 0.00 |
November | 0.724523E+09 | 0.267964E+10 | 0.115858E+10 | 0.428442E+09 | 0.730140E+09 | 0.00 | 0.00 |
December | 0.505857E+09 | 0.400577E+10 | 0.920711E+09 | 0.434035E+09 | 0.486675E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.311001E+11 | 0.246895E+11 | 0.295629E+11 | 0.131783E+11 | 0.163847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.505857E+09 | 0.670394E+09 | 0.920711E+09 | 0.428442E+09 | 0.486675E+09 | 0.00 | 0.00 |
Maximum of Months | 0.525183E+10 | 0.442008E+10 | 0.405587E+10 | 0.192660E+10 | 0.212927E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.593784E+10 | -0.517005E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -767795121.9 | 58.99 | 0.00 | 0.00 |
February | 0.547060E+10 | -0.479340E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -677196978.3 | 58.98 | 0.00 | 0.00 |
March | 0.634536E+10 | -0.561764E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -727724992.5 | 58.98 | 0.00 | 0.00 |
April | 0.554953E+10 | -0.486068E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -688851823.3 | 58.98 | 0.00 | 0.00 |
May | 0.560196E+10 | -0.490722E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -694736564.9 | 58.98 | 0.00 | 0.00 |
June | 0.521485E+10 | -0.454477E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -670079057.0 | 58.99 | 0.00 | 0.00 |
July | 0.472919E+10 | -0.403983E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -689353030.5 | 58.98 | 0.00 | 0.00 |
August | 0.504117E+10 | -0.435020E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -690969276.1 | 58.99 | 0.00 | 0.00 |
September | 0.463983E+10 | -0.397025E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -669577122.1 | 58.98 | 0.00 | 0.00 |
October | 0.501118E+10 | -0.430730E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -703879198.1 | 58.98 | 0.00 | 0.00 |
November | 0.523062E+10 | -0.452981E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -700808212.2 | 58.98 | 0.00 | 0.00 |
December | 0.553571E+10 | -0.478527E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -750434551.1 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.643078E+11 | -0.558764E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.843141E+10 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.463983E+10 | -0.561764E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -767795121.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.634536E+10 | -0.397025E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -669577122.1 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 6353.25 | 36.85 | 205.17 | 238.17 | 5281.01 | 37.85 | 201.83 | 216.17 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 7570.06 | 37.10 | 222.17 | 252.33 | 2157.71 | 28.50 | 174.33 | 232.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 6916.05 | 29.76 | 259.50 | 322.50 | 1269.92 | 21.04 | 173.83 | 284.00 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:19 | 1994.03 | 17.91 | 0.00 | 339.83 | 1188.16 | 20.70 | 130.50 | 285.50 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:49 | 1541.13 | 17.48 | 0.00 | 386.17 | 859.13 | 20.24 | 154.17 | 336.17 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:00 | 1566.94 | 17.72 | 0.00 | 388.17 | 887.79 | 20.50 | 165.67 | 340.83 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 1626.20 | 18.03 | 0.00 | 397.50 | 930.55 | 20.80 | 183.67 | 350.00 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:19 | 1809.98 | 17.94 | 0.00 | 371.33 | 1014.89 | 20.70 | 200.67 | 333.00 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:30 | 2652.84 | 19.77 | 26.00 | 326.33 | 1289.62 | 21.24 | 175.33 | 293.00 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 6518.73 | 32.72 | 291.67 | 301.33 | 1703.80 | 22.50 | 169.50 | 277.17 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 4533.31 | 32.15 | 229.50 | 242.67 | 2460.62 | 30.51 | 218.67 | 218.83 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-08:09 | 5523.81 | 35.48 | 167.50 | 213.00 | 5099.16 | 38.45 | 177.00 | 172.17 |
Annual Sum or Average | 3807.33 | 0.50 | 3633.36 | 24.34 | 1401.50 | 3779.33 | 1697.11 | 23.82 | 2125.17 | 3338.83 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1541.13 | 17.48 | 0.00 | 213.00 | 859.13 | 20.24 | 130.50 | 172.17 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 7570.06 | 37.10 | 291.67 | 397.50 | 5281.01 | 38.45 | 218.67 | 350.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 1636.73 | 21.09 | 65.67 | 219.67 | 833.26 | 22.03 | 77.00 | 165.00 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 1964.81 | 20.17 | 62.83 | 230.67 | 1123.28 | 23.29 | 77.83 | 189.50 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 2595.67 | 20.65 | 99.50 | 311.33 | 1060.58 | 20.94 | 61.83 | 267.50 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 3043.65 | 20.36 | 77.00 | 340.33 | 1788.44 | 22.19 | 57.33 | 289.67 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3127.69 | 19.82 | 111.83 | 394.33 | 1357.49 | 21.54 | 77.33 | 346.50 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 2859.34 | 19.87 | 95.50 | 397.17 | 1554.76 | 21.71 | 68.33 | 357.83 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 3643.39 | 21.41 | 123.33 | 405.83 | 1568.73 | 22.01 | 70.00 | 367.50 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 2883.70 | 20.16 | 110.00 | 372.67 | 1296.70 | 21.95 | 72.17 | 344.00 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-05:00 | 2908.81 | 21.18 | 95.17 | 321.83 | 1641.24 | 22.86 | 79.00 | 279.17 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 1791.45 | 19.47 | 84.00 | 282.67 | 995.94 | 22.37 | 83.00 | 244.67 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1387.59 | 18.72 | 63.83 | 223.17 | 762.03 | 21.53 | 72.33 | 172.50 |
December | 186.17 | 0.53 | 0.48 | 01-DEC-07:00 | 1286.73 | 20.67 | 63.83 | 182.33 | 663.10 | 21.30 | 58.00 | 107.33 |
Annual Sum or Average | 3807.33 | 0.51 | 2583.66 | 20.29 | 1052.50 | 3682.00 | 1277.07 | 21.95 | 854.17 | 3131.17 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1286.73 | 18.72 | 62.83 | 182.33 | 663.10 | 20.94 | 57.33 | 107.33 | |
Maximum of Months | 428.67 | 0.53 | 0.48 | 3643.39 | 21.41 | 123.33 | 405.83 | 1788.44 | 23.29 | 83.00 | 367.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.55 | 0.48 | 01-JAN-10:09 | 559.32 | 14.21 | 0.00 | 199.00 | 344.57 | 17.32 | 0.00 | 106.00 |
February | 226.83 | 0.54 | 0.48 | 01-FEB-09:30 | 589.33 | 14.59 | 0.00 | 212.50 | 369.62 | 17.65 | 0.00 | 131.67 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:30 | 805.38 | 16.25 | 0.00 | 307.00 | 469.77 | 19.03 | 0.00 | 240.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:30 | 942.76 | 17.29 | 0.00 | 343.50 | 584.30 | 20.03 | 15.83 | 269.50 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1072.40 | 17.69 | 3.17 | 406.67 | 612.51 | 21.36 | 92.50 | 365.50 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1292.71 | 21.05 | 75.33 | 408.33 | 761.93 | 23.50 | 189.67 | 383.83 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:49 | 1220.43 | 19.61 | 30.67 | 417.67 | 722.80 | 22.30 | 165.50 | 387.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1009.48 | 17.61 | 0.00 | 384.33 | 592.25 | 20.32 | 38.67 | 345.83 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:30 | 833.63 | 16.94 | 0.00 | 322.83 | 515.91 | 19.71 | 0.00 | 258.83 |
October | 325.17 | 0.53 | 0.48 | 01-OCT-07:49 | 658.70 | 15.17 | 0.00 | 269.17 | 392.04 | 18.07 | 0.00 | 196.33 |
November | 254.83 | 0.54 | 0.48 | 01-NOV-08:39 | 560.83 | 14.15 | 0.00 | 208.50 | 320.00 | 16.99 | 0.00 | 104.50 |
December | 186.17 | 0.57 | 0.48 | 01-DEC-10:00 | 406.36 | 12.70 | 0.00 | 146.33 | 258.73 | 15.98 | 0.00 | 31.83 |
Annual Sum or Average | 3807.33 | 0.51 | 891.48 | 16.95 | 109.17 | 3625.83 | 529.86 | 19.85 | 502.17 | 2821.83 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 406.36 | 12.70 | 0.00 | 146.33 | 258.73 | 15.98 | 0.00 | 31.83 | |
Maximum of Months | 428.67 | 0.57 | 0.48 | 1292.71 | 21.05 | 75.33 | 417.67 | 761.93 | 23.50 | 189.67 | 387.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:00 | 1691.97 | 20.45 | 67.17 | 217.83 | 1035.05 | 23.64 | 81.17 | 166.17 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-09:30 | 2035.02 | 20.35 | 63.33 | 231.50 | 1080.85 | 21.48 | 54.83 | 191.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:39 | 2210.13 | 20.35 | 93.33 | 313.83 | 1192.50 | 21.94 | 78.83 | 270.33 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 3914.53 | 21.33 | 84.50 | 341.67 | 1640.20 | 21.14 | 39.17 | 281.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-07:10 | 2366.05 | 16.53 | 49.50 | 394.00 | 1282.47 | 18.15 | 0.00 | 353.17 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-06:10 | 2995.63 | 17.02 | 50.33 | 397.00 | 1372.36 | 18.61 | 0.00 | 358.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-06:10 | 3376.24 | 17.52 | 56.00 | 405.33 | 1475.12 | 18.84 | 2.17 | 368.33 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:40 | 2825.33 | 18.99 | 83.83 | 377.33 | 1582.95 | 20.89 | 55.17 | 340.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-07:30 | 2948.91 | 21.39 | 96.67 | 326.00 | 1700.54 | 22.98 | 72.17 | 286.33 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:49 | 1848.30 | 19.55 | 82.17 | 284.00 | 988.99 | 21.24 | 66.83 | 244.00 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:39 | 1433.03 | 18.76 | 68.00 | 226.67 | 801.20 | 21.25 | 65.50 | 177.50 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-10:39 | 1357.23 | 19.60 | 55.00 | 186.50 | 730.95 | 20.68 | 40.83 | 103.17 |
Annual Sum or Average | 3807.33 | 0.51 | 2530.35 | 19.07 | 849.83 | 3701.67 | 1289.87 | 20.64 | 556.67 | 3140.33 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1357.23 | 16.53 | 49.50 | 186.50 | 730.95 | 18.15 | 0.00 | 103.17 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 3914.53 | 21.39 | 96.67 | 405.33 | 1700.54 | 23.64 | 81.17 | 368.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.51 | 0.48 | 01-JAN-09:39 | 6072.18 | 34.27 | 187.83 | 234.83 | 5142.19 | 37.47 | 200.00 | 214.00 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 7352.37 | 35.66 | 211.50 | 248.17 | 2029.03 | 26.49 | 105.50 | 230.50 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:09 | 6779.72 | 28.97 | 244.17 | 320.17 | 1178.09 | 18.22 | 3.50 | 280.83 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:30 | 1877.78 | 14.38 | 0.00 | 338.17 | 1106.71 | 18.36 | 5.17 | 279.83 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:49 | 1465.33 | 13.84 | 0.00 | 383.33 | 811.38 | 17.76 | 0.00 | 332.17 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:00 | 1491.96 | 14.32 | 0.00 | 384.50 | 841.98 | 18.23 | 0.00 | 335.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 1546.09 | 14.64 | 0.00 | 395.00 | 880.69 | 18.57 | 0.33 | 344.83 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1715.18 | 14.40 | 0.00 | 369.17 | 953.19 | 18.32 | 0.00 | 330.00 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:30 | 2521.91 | 16.41 | 26.00 | 325.00 | 1197.33 | 18.79 | 13.17 | 289.00 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 6363.55 | 31.96 | 286.33 | 299.00 | 1601.28 | 19.72 | 30.33 | 274.67 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 4362.85 | 30.70 | 215.50 | 239.83 | 2366.15 | 29.28 | 180.50 | 216.33 |
December | 186.17 | 0.51 | 0.48 | 01-DEC-08:09 | 5347.66 | 34.51 | 164.50 | 211.67 | 4930.75 | 36.92 | 169.00 | 167.00 |
Annual Sum or Average | 3807.33 | 0.51 | 3504.03 | 21.76 | 1335.83 | 3748.83 | 1613.97 | 21.64 | 707.50 | 3294.50 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1465.33 | 13.84 | 0.00 | 211.67 | 811.38 | 17.76 | 0.00 | 167.00 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 7352.37 | 35.66 | 286.33 | 395.00 | 5142.19 | 37.47 | 200.00 | 344.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:39 | 1583.21 | 20.66 | 65.67 | 216.67 | 794.60 | 21.79 | 70.33 | 162.00 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 1905.11 | 19.73 | 62.83 | 227.17 | 1077.84 | 23.08 | 70.67 | 184.17 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 2525.43 | 20.25 | 99.17 | 309.00 | 1009.25 | 20.72 | 52.67 | 263.67 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 2954.02 | 19.96 | 77.00 | 338.17 | 1721.43 | 22.00 | 57.17 | 280.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3044.43 | 19.41 | 111.67 | 391.67 | 1297.19 | 21.37 | 77.50 | 342.50 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 2758.82 | 19.41 | 94.50 | 393.83 | 1487.33 | 21.54 | 68.33 | 353.50 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 3464.77 | 19.77 | 101.83 | 402.83 | 1501.08 | 21.83 | 70.00 | 364.17 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-05:40 | 2790.43 | 19.61 | 107.67 | 371.00 | 1236.02 | 21.77 | 71.83 | 339.17 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-05:00 | 2691.42 | 19.15 | 74.50 | 319.67 | 1563.43 | 22.52 | 72.67 | 273.33 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-06:40 | 1732.11 | 19.03 | 84.00 | 279.83 | 926.71 | 21.10 | 63.83 | 238.83 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1344.12 | 18.28 | 63.33 | 220.17 | 731.78 | 21.30 | 69.50 | 167.00 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-08:09 | 1244.74 | 20.24 | 63.67 | 178.33 | 631.99 | 21.05 | 52.83 | 104.33 |
Annual Sum or Average | 3807.33 | 0.51 | 2486.10 | 19.58 | 1005.83 | 3648.33 | 1218.74 | 21.65 | 797.33 | 3073.00 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1244.74 | 18.28 | 62.83 | 178.33 | 631.99 | 20.72 | 52.67 | 104.33 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 3464.77 | 20.66 | 111.67 | 402.83 | 1721.43 | 23.08 | 77.50 | 364.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.55 | 0.48 | 01-JAN-10:09 | 533.60 | 10.70 | 0.00 | 194.00 | 330.98 | 14.90 | 0.00 | 97.67 |
February | 226.83 | 0.54 | 0.48 | 01-FEB-09:39 | 563.26 | 11.20 | 0.00 | 207.50 | 356.03 | 15.39 | 0.00 | 120.33 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:39 | 771.51 | 12.81 | 0.00 | 304.17 | 451.84 | 16.75 | 0.00 | 233.67 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:30 | 903.39 | 14.25 | 0.00 | 341.33 | 563.95 | 18.22 | 0.33 | 258.00 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1027.95 | 14.21 | 3.17 | 404.33 | 588.51 | 19.27 | 29.67 | 360.50 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1238.18 | 18.36 | 74.50 | 406.83 | 731.75 | 21.69 | 78.00 | 378.83 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:49 | 1169.20 | 16.61 | 30.67 | 415.83 | 695.04 | 20.41 | 44.67 | 381.67 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 966.86 | 14.37 | 0.00 | 382.50 | 569.65 | 18.33 | 0.00 | 340.67 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-06:30 | 797.68 | 13.90 | 0.00 | 319.17 | 497.21 | 17.86 | 0.00 | 251.33 |
October | 325.17 | 0.53 | 0.48 | 01-OCT-07:49 | 630.26 | 11.67 | 0.00 | 264.67 | 377.03 | 15.72 | 0.00 | 185.83 |
November | 254.83 | 0.54 | 0.48 | 01-NOV-08:50 | 536.49 | 10.38 | 0.00 | 202.83 | 306.97 | 14.38 | 0.00 | 90.67 |
December | 186.17 | 0.58 | 0.48 | 01-DEC-11:09 | 387.30 | 8.93 | 0.00 | 133.50 | 248.74 | 13.33 | 0.00 | 25.17 |
Annual Sum or Average | 3807.33 | 0.51 | 853.57 | 13.67 | 108.33 | 3576.67 | 509.61 | 17.73 | 152.67 | 2724.33 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 387.30 | 8.93 | 0.00 | 133.50 | 248.74 | 13.33 | 0.00 | 25.17 | |
Maximum of Months | 428.67 | 0.58 | 0.48 | 1238.18 | 18.36 | 74.50 | 415.83 | 731.75 | 21.69 | 78.00 | 381.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 1639.27 | 20.11 | 67.17 | 215.00 | 996.55 | 23.55 | 80.50 | 160.83 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-09:39 | 1969.32 | 20.00 | 63.33 | 228.50 | 1030.83 | 21.37 | 54.17 | 185.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:39 | 2046.40 | 18.40 | 69.50 | 311.17 | 1144.95 | 21.81 | 76.17 | 266.83 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 3817.92 | 20.97 | 84.50 | 339.17 | 1564.39 | 21.00 | 39.17 | 275.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-07:10 | 2289.68 | 16.09 | 49.33 | 392.17 | 1227.36 | 17.96 | 0.00 | 348.50 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-06:10 | 2903.28 | 16.61 | 50.17 | 394.00 | 1305.39 | 18.43 | 0.00 | 353.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-06:19 | 3268.49 | 17.10 | 56.00 | 402.00 | 1401.14 | 18.67 | 2.17 | 363.83 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:40 | 2636.99 | 18.59 | 83.67 | 374.33 | 1517.80 | 20.74 | 55.00 | 336.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-07:30 | 2865.43 | 21.03 | 96.67 | 324.67 | 1636.46 | 22.84 | 72.17 | 279.67 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:00 | 1785.15 | 19.19 | 82.17 | 281.17 | 942.76 | 21.12 | 65.67 | 240.00 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:50 | 1386.91 | 18.41 | 67.83 | 224.33 | 768.38 | 21.14 | 65.17 | 172.67 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-10:50 | 1314.60 | 19.25 | 55.00 | 181.50 | 698.70 | 20.58 | 40.00 | 98.33 |
Annual Sum or Average | 3807.33 | 0.51 | 2433.77 | 18.55 | 825.33 | 3668.00 | 1233.33 | 20.50 | 550.17 | 3080.83 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1314.60 | 16.09 | 49.33 | 181.50 | 698.70 | 17.96 | 0.00 | 98.33 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 3817.92 | 21.03 | 96.67 | 402.00 | 1636.46 | 23.55 | 80.50 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.51 | 0.48 | 01-JAN-09:39 | 6072.24 | 34.27 | 187.83 | 234.83 | 5142.11 | 37.48 | 200.00 | 214.00 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 7352.38 | 35.67 | 211.50 | 248.17 | 2028.95 | 26.49 | 105.50 | 230.50 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:09 | 6779.65 | 28.97 | 244.17 | 320.17 | 1178.00 | 18.22 | 3.50 | 280.83 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:30 | 1877.71 | 14.38 | 0.00 | 338.17 | 1106.64 | 18.36 | 5.17 | 279.83 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:49 | 1465.26 | 13.84 | 0.00 | 383.33 | 811.32 | 17.76 | 0.00 | 332.17 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:00 | 1491.90 | 14.32 | 0.00 | 384.50 | 841.93 | 18.23 | 0.00 | 335.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 1546.03 | 14.64 | 0.00 | 395.00 | 880.63 | 18.57 | 0.33 | 344.83 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:30 | 1715.11 | 14.40 | 0.00 | 369.17 | 953.12 | 18.32 | 0.00 | 330.00 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:30 | 2521.84 | 16.41 | 26.00 | 325.00 | 1197.25 | 18.79 | 13.17 | 289.00 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 6363.52 | 31.96 | 286.33 | 299.00 | 1601.19 | 19.72 | 30.33 | 274.67 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 4362.86 | 30.70 | 215.50 | 239.83 | 2366.07 | 29.28 | 180.50 | 216.33 |
December | 186.17 | 0.51 | 0.48 | 01-DEC-08:09 | 5347.72 | 34.51 | 164.50 | 211.67 | 4930.70 | 36.92 | 169.00 | 167.00 |
Annual Sum or Average | 3807.33 | 0.51 | 3503.99 | 21.76 | 1335.83 | 3748.83 | 1613.89 | 21.64 | 707.50 | 3294.50 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1465.26 | 13.84 | 0.00 | 211.67 | 811.32 | 17.76 | 0.00 | 167.00 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 7352.38 | 35.67 | 286.33 | 395.00 | 5142.11 | 37.48 | 200.00 | 344.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:39 | 1583.22 | 20.66 | 65.67 | 216.67 | 794.56 | 21.79 | 70.33 | 162.00 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 1905.11 | 19.73 | 62.83 | 227.17 | 1077.81 | 23.08 | 70.67 | 184.17 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 2525.41 | 20.25 | 99.17 | 309.00 | 1009.20 | 20.72 | 52.67 | 263.67 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 2954.02 | 19.96 | 77.00 | 338.17 | 1721.38 | 22.00 | 57.17 | 280.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3044.40 | 19.42 | 111.67 | 391.67 | 1297.13 | 21.37 | 77.50 | 342.50 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 2758.79 | 19.41 | 94.50 | 393.83 | 1487.26 | 21.54 | 68.33 | 353.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 3464.76 | 19.77 | 101.83 | 402.83 | 1501.02 | 21.83 | 70.00 | 364.00 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-05:40 | 2790.41 | 19.61 | 107.67 | 371.00 | 1235.96 | 21.77 | 71.83 | 339.17 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-05:00 | 2691.42 | 19.15 | 74.50 | 319.67 | 1563.38 | 22.52 | 72.67 | 273.33 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-06:40 | 1732.10 | 19.03 | 84.00 | 279.83 | 926.67 | 21.10 | 63.83 | 238.83 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1344.10 | 18.28 | 63.33 | 220.17 | 731.74 | 21.30 | 69.50 | 167.00 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-08:09 | 1244.74 | 20.25 | 63.67 | 178.33 | 631.96 | 21.05 | 52.83 | 104.33 |
Annual Sum or Average | 3807.33 | 0.51 | 2486.08 | 19.59 | 1005.83 | 3648.33 | 1218.69 | 21.65 | 797.33 | 3072.67 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1244.74 | 18.28 | 62.83 | 178.33 | 631.96 | 20.72 | 52.67 | 104.33 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 3464.76 | 20.66 | 111.67 | 402.83 | 1721.38 | 23.08 | 77.50 | 364.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.55 | 0.48 | 01-JAN-10:09 | 533.60 | 10.70 | 0.00 | 194.00 | 330.96 | 14.90 | 0.00 | 97.67 |
February | 226.83 | 0.54 | 0.48 | 01-FEB-09:39 | 563.26 | 11.20 | 0.00 | 207.50 | 356.01 | 15.39 | 0.00 | 120.17 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:39 | 771.49 | 12.81 | 0.00 | 304.17 | 451.81 | 16.76 | 0.00 | 233.67 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:30 | 903.38 | 14.25 | 0.00 | 341.33 | 563.92 | 18.22 | 0.33 | 258.00 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1027.92 | 14.22 | 3.17 | 404.33 | 588.48 | 19.27 | 29.67 | 360.50 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1238.16 | 18.36 | 74.50 | 406.83 | 731.71 | 21.69 | 78.00 | 378.83 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:49 | 1169.18 | 16.61 | 30.67 | 415.83 | 695.00 | 20.41 | 44.67 | 381.67 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 966.84 | 14.37 | 0.00 | 382.50 | 569.62 | 18.33 | 0.00 | 340.67 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-06:30 | 797.67 | 13.90 | 0.00 | 319.17 | 497.18 | 17.86 | 0.00 | 251.33 |
October | 325.17 | 0.53 | 0.48 | 01-OCT-07:49 | 630.25 | 11.67 | 0.00 | 264.67 | 377.01 | 15.72 | 0.00 | 185.83 |
November | 254.83 | 0.54 | 0.48 | 01-NOV-08:50 | 536.48 | 10.38 | 0.00 | 202.83 | 306.95 | 14.39 | 0.00 | 90.67 |
December | 186.17 | 0.58 | 0.48 | 01-DEC-11:09 | 387.30 | 8.94 | 0.00 | 133.50 | 248.73 | 13.33 | 0.00 | 25.17 |
Annual Sum or Average | 3807.33 | 0.51 | 853.55 | 13.67 | 108.33 | 3576.67 | 509.58 | 17.73 | 152.67 | 2724.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 387.30 | 8.94 | 0.00 | 133.50 | 248.73 | 13.33 | 0.00 | 25.17 | |
Maximum of Months | 428.67 | 0.58 | 0.48 | 1238.16 | 18.36 | 74.50 | 415.83 | 731.71 | 21.69 | 78.00 | 381.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.53 | 0.48 | 01-JAN-09:00 | 1639.27 | 20.12 | 67.17 | 215.00 | 996.51 | 23.55 | 80.50 | 160.83 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-09:39 | 1969.32 | 20.00 | 63.33 | 228.50 | 1030.80 | 21.37 | 54.17 | 185.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:39 | 2046.38 | 18.40 | 69.50 | 311.17 | 1144.90 | 21.81 | 76.17 | 266.83 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 3817.91 | 20.97 | 84.50 | 339.17 | 1564.33 | 21.00 | 39.17 | 275.00 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-07:10 | 2289.65 | 16.10 | 49.33 | 392.17 | 1227.30 | 17.96 | 0.00 | 348.50 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-06:10 | 2903.26 | 16.61 | 50.17 | 394.00 | 1305.33 | 18.43 | 0.00 | 353.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-06:19 | 3268.47 | 17.11 | 56.00 | 402.00 | 1401.07 | 18.67 | 2.17 | 363.83 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:40 | 2636.97 | 18.60 | 83.67 | 374.33 | 1517.74 | 20.74 | 55.00 | 336.50 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-07:30 | 2865.43 | 21.03 | 96.67 | 324.67 | 1636.41 | 22.84 | 72.17 | 279.67 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:00 | 1785.14 | 19.19 | 82.17 | 281.17 | 942.71 | 21.12 | 65.83 | 240.00 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:50 | 1386.90 | 18.41 | 67.83 | 224.33 | 768.34 | 21.14 | 65.17 | 172.67 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-10:50 | 1314.60 | 19.25 | 55.00 | 181.50 | 698.68 | 20.58 | 40.00 | 98.33 |
Annual Sum or Average | 3807.33 | 0.51 | 2433.76 | 18.55 | 825.33 | 3668.00 | 1233.28 | 20.50 | 550.33 | 3080.83 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1314.60 | 16.10 | 49.33 | 181.50 | 698.68 | 17.96 | 0.00 | 98.33 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 3817.91 | 21.03 | 96.67 | 402.00 | 1636.41 | 23.55 | 80.50 | 363.83 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142898E+10 | 24669.71 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.382796E+09 | 24669.71 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14251477.45 | 24669.71 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 96526950.61 | 24669.71 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.289791E+09 | 24669.71 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221234E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142898E+10 | 24669.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126648E+11 | 11048.98 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.896127E+10 | 11032.00 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.758315E+10 | 11017.58 | 29-MAR-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.408228E+10 | 11201.78 | 19-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131273E+10 | 11053.49 | 26-MAY-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.511569E+09 | 11285.72 | 01-JUN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 50152687.25 | 10871.14 | 24-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180932E+09 | 11275.72 | 17-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.906913E+09 | 11291.62 | 19-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.222751E+10 | 11040.64 | 03-OCT-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.591047E+10 | 11034.68 | 08-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100816E+11 | 11022.02 | 14-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.544733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 50152687.25 | 10871.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.126648E+11 | 11291.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.537723E+10 | 9236.63 | 11-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.338096E+10 | 9227.58 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175270E+10 | 9213.27 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.631326E+09 | 9194.64 | 12-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1830236.05 | 9153.72 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3523807.00 | 7003.90 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 51033643.57 | 9164.22 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148369E+10 | 9222.28 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.368761E+10 | 9247.66 | 14-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.537723E+10 | 9247.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.860169E+10 | 7535.49 | 02-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.584159E+10 | 7524.54 | 07-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342991E+10 | 7507.06 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129166E+10 | 7517.25 | 12-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37727829.84 | 7483.85 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13047826.53 | 7455.67 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155712E+09 | 7491.08 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237976E+10 | 7500.24 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.580749E+10 | 7517.37 | 14-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.860169E+10 | 7535.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.558467E+10 | 9849.67 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351548E+10 | 9857.25 | 13-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200209E+10 | 9841.98 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.608752E+09 | 9821.92 | 12-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19700624.20 | 9790.78 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16185694.51 | 9786.66 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75516524.99 | 9789.61 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155577E+10 | 9814.62 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.377604E+10 | 9861.82 | 18-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.558467E+10 | 9861.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.623229E+10 | 26564.63 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309666E+10 | 26564.63 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.112987E+10 | 26564.63 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.204052E+09 | 26564.63 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2427185.02 | 14141.14 | 16-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168860E+10 | 26564.63 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.385689E+10 | 26564.63 | 01-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.623229E+10 | 26564.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.519961E+10 | 12612.40 | 17-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.284609E+10 | 12623.81 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150672E+10 | 12570.96 | 07-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.459341E+09 | 12562.11 | 04-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5970179.61 | 12407.00 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19394542.29 | 12401.37 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143013E+09 | 12405.92 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.182882E+10 | 12601.94 | 24-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.430076E+10 | 12585.19 | 14-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.519961E+10 | 12623.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.515402E+10 | 11079.00 | 09-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.306935E+10 | 11073.01 | 16-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143424E+10 | 11049.81 | 03-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.434651E+09 | 11043.49 | 04-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1051033.53 | 9395.48 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20931850.50 | 10978.57 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209410E+09 | 10983.74 | 23-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194279E+10 | 11096.66 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.402567E+10 | 11096.66 | 30-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.515402E+10 | 11096.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.800183E+10 | 8224.07 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.493848E+10 | 8245.54 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.223072E+10 | 8226.21 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.581148E+09 | 8208.73 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4646516.43 | 8075.65 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 27912733.30 | 8204.63 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.260033E+09 | 8200.74 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271281E+10 | 8258.54 | 15-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.589471E+10 | 8213.63 | 30-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.800183E+10 | 8258.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.524509E+10 | 11221.81 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.316274E+10 | 11221.81 | 01-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157908E+10 | 11221.81 | 01-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.443656E+09 | 11221.81 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9558727.03 | 11221.81 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 42174735.30 | 11221.81 | 29-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.253891E+09 | 11221.81 | 13-OCT-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194989E+10 | 11221.81 | 10-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.402375E+10 | 11221.81 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.524509E+10 | 11221.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128387E+11 | 30977.34 | 18-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.797405E+10 | 31002.64 | 10-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.395288E+10 | 31019.31 | 27-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119235E+10 | 31004.25 | 28-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4460835.14 | 21392.66 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69568329.39 | 30521.12 | 30-SEP-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.602031E+09 | 30990.74 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.502435E+10 | 31064.83 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.985361E+10 | 30963.01 | 01-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.415120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128387E+11 | 31064.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.841624E+10 | 13962.86 | 17-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.501023E+10 | 13987.04 | 27-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301881E+10 | 13990.96 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117437E+10 | 13972.00 | 03-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 49234923.60 | 13829.45 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6220916.73 | 4185.12 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144758E+09 | 13898.28 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.703152E+09 | 13982.59 | 23-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.355784E+10 | 13995.65 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.712753E+10 | 13967.73 | 04-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.841624E+10 | 13995.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.741452E+10 | 11369.82 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.460006E+10 | 11405.43 | 25-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.240422E+10 | 11368.18 | 22-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.893079E+09 | 11384.17 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12974513.24 | 11274.26 | 02-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5713490.23 | 2194.17 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112970E+09 | 11288.11 | 25-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.691582E+09 | 11393.89 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.318067E+10 | 11364.73 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.599717E+10 | 11343.02 | 14-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.741452E+10 | 11405.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117946E+11 | 9998.61 | 14-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.761004E+10 | 10014.42 | 08-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.412398E+10 | 10045.91 | 30-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138499E+10 | 10011.22 | 13-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42579418.02 | 9978.69 | 02-MAY-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3269096.29 | 1942.05 | 05-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202321E+09 | 10003.75 | 29-SEP-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116229E+10 | 10023.93 | 31-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.481584E+10 | 10023.79 | 20-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.924335E+10 | 9994.86 | 30-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.403833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117946E+11 | 10045.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.770270E+10 | 12464.29 | 27-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.489764E+10 | 12531.77 | 25-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.278937E+10 | 12448.25 | 03-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.100991E+10 | 12464.99 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 55621449.10 | 12412.39 | 03-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12154856.59 | 4078.94 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.198705E+09 | 12392.85 | 30-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.900505E+09 | 12492.62 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333490E+10 | 12486.96 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.616001E+10 | 12458.70 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.770270E+10 | 12531.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285540E+11 | 44270.06 | 31-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191679E+11 | 51221.54 | 02-FEB-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105487E+11 | 24035.54 | 06-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363626E+10 | 17348.72 | 03-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102211E+09 | 5517.81 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2841593.58 | 913.11 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191446E+09 | 7231.98 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153523E+10 | 10562.04 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.936728E+10 | 29171.59 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203124E+11 | 35440.62 | 11-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.934182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285540E+11 | 51221.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.283302E+11 | 43513.71 | 31-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195266E+11 | 51850.00 | 02-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116482E+11 | 24187.81 | 06-MAR-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.458168E+10 | 18273.24 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169694E+09 | 6580.89 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8348299.04 | 1489.72 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.351272E+09 | 8613.68 | 29-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.252533E+10 | 11911.16 | 23-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104367E+11 | 29404.96 | 28-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210220E+11 | 34916.71 | 09-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.986001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.283302E+11 | 51850.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP HEATING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.316339E+11 | 44619.46 | 31-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212347E+11 | 52864.73 | 02-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.120540E+11 | 24202.59 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.480265E+10 | 19058.47 | 03-APR-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.218478E+09 | 8125.38 | 02-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 23666538.77 | 2968.59 | 03-JUN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.489396E+09 | 10620.30 | 29-SEP-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290796E+10 | 14347.16 | 23-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114869E+11 | 31652.98 | 28-NOV-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231531E+11 | 38271.62 | 09-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108005E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.316339E+11 | 52864.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.140983E+09 | 0.118528E+09 | 7131.00 | 25-MAR-15:00 | 6210.18 | 0.00 |
April | 0.00 | 0.00 | 0.474701E+10 | 0.358574E+10 | 68612.12 | 18-APR-12:00 | 44764.42 | 0.00 |
May | 0.00 | 0.00 | 0.130049E+11 | 0.965204E+10 | 69083.15 | 31-MAY-11:10 | 49516.85 | 0.00 |
June | 0.00 | 0.00 | 0.419756E+11 | 0.306480E+11 | 120096.86 | 26-JUN-06:03 | 48222.53 | 0.00 |
July | 0.00 | 0.00 | 0.601230E+11 | 0.400163E+11 | 106099.43 | 03-JUL-08:50 | 49535.70 | 0.00 |
August | 0.00 | 0.00 | 0.591367E+11 | 0.403042E+11 | 124702.80 | 03-AUG-07:10 | 45112.41 | 0.00 |
September | 0.00 | 0.00 | 0.235438E+11 | 0.205790E+11 | 92042.95 | 11-SEP-09:50 | 55209.45 | 0.00 |
October | 0.00 | 0.00 | 0.136758E+10 | 0.115921E+10 | 29302.54 | 20-OCT-15:00 | 29302.54 | 0.00 |
November | 0.00 | 0.00 | 44943156.65 | 39329936.79 | 3782.51 | 03-NOV-14:00 | 3376.48 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.204084E+12 | 0.146102E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.601230E+11 | 0.403042E+11 | 124702.80 | 55209.45 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.142430E+09 | 0.124626E+09 | 7547.76 | 25-MAR-15:00 | 7121.50 | 0.00 |
April | 0.00 | 0.00 | 0.514164E+10 | 0.400899E+10 | 62141.37 | 18-APR-12:40 | 44778.35 | 0.00 |
May | 0.00 | 0.00 | 0.135468E+11 | 0.100070E+11 | 63348.40 | 30-MAY-11:00 | 39730.72 | 0.00 |
June | 0.00 | 0.00 | 0.400471E+11 | 0.295165E+11 | 110136.32 | 26-JUN-06:03 | 44293.48 | 0.00 |
July | 0.00 | 0.00 | 0.550189E+11 | 0.366842E+11 | 100782.45 | 05-JUL-10:50 | 53164.40 | 0.00 |
August | 0.00 | 0.00 | 0.513749E+11 | 0.351871E+11 | 114360.25 | 04-AUG-07:10 | 32997.50 | 0.00 |
September | 0.00 | 0.00 | 0.205305E+11 | 0.180153E+11 | 77875.11 | 11-SEP-09:40 | 46279.28 | 0.00 |
October | 0.00 | 0.00 | 0.123465E+10 | 0.104272E+10 | 23995.84 | 20-OCT-14:50 | 23995.84 | 0.00 |
November | 0.00 | 0.00 | 51034878.16 | 43279012.56 | 4721.69 | 03-NOV-13:30 | 3924.49 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187088E+12 | 0.134630E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.550189E+11 | 0.366842E+11 | 114360.25 | 53164.40 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP COOLING COIL
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.147935E+09 | 0.126042E+09 | 7929.71 | 25-MAR-15:00 | 7238.68 | 0.00 |
April | 0.00 | 0.00 | 0.577162E+10 | 0.448333E+10 | 74802.88 | 18-APR-15:50 | 51836.84 | 0.00 |
May | 0.00 | 0.00 | 0.146001E+11 | 0.108408E+11 | 71312.17 | 30-MAY-12:10 | 51567.96 | 0.00 |
June | 0.00 | 0.00 | 0.431390E+11 | 0.322010E+11 | 122967.98 | 26-JUN-06:03 | 49205.83 | 0.00 |
July | 0.00 | 0.00 | 0.588328E+11 | 0.392437E+11 | 106016.99 | 06-JUL-15:10 | 54631.52 | 0.00 |
August | 0.00 | 0.00 | 0.533239E+11 | 0.369678E+11 | 127795.46 | 03-AUG-05:03 | 43232.47 | 0.00 |
September | 0.00 | 0.00 | 0.212807E+11 | 0.185970E+11 | 77993.51 | 11-SEP-10:00 | 48253.57 | 0.00 |
October | 0.00 | 0.00 | 0.123815E+10 | 0.102430E+10 | 24443.81 | 20-OCT-15:00 | 24443.81 | 0.00 |
November | 0.00 | 0.00 | 37289923.77 | 31323742.24 | 3461.35 | 03-NOV-14:00 | 2955.79 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198371E+12 | 0.143515E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.588328E+11 | 0.392437E+11 | 127795.46 | 54631.52 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 2082.28 | 7369.66 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2133.80 | 7415.08 | 23-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2252.82 | 7405.50 | 01-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2027.37 | 7200.15 | 03-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 1986.60 | 6842.74 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1909.71 | 6408.79 | 01-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 1660.01 | 5969.12 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1780.87 | 5734.33 | 04-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 1684.84 | 5908.66 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1761.15 | 6271.86 | 31-OCT-11:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1901.14 | 6715.17 | 30-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1937.93 | 7090.95 | 29-DEC-12:14 |
Annual Sum or Average | 0.00 | 1925.34 | ||||
Minimum of Months | 0.00 | 0.00 | 1660.01 | 5734.33 | ||
Maximum of Months | 0.00 | 0.00 | 2252.82 | 7415.08 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.191010E+10 | 0.39 | 2662.87 | 02-JAN-07:01 | 0.84 |
February | 0.148528E+10 | 0.35 | 2662.87 | 01-FEB-07:02 | 0.84 |
March | 0.156870E+10 | 0.33 | 2662.87 | 06-MAR-07:01 | 0.84 |
April | 0.174229E+10 | 0.33 | 5716.67 | 18-APR-15:10 | 1.29 |
May | 0.247852E+10 | 0.37 | 7214.63 | 31-MAY-12:10 | 1.49 |
June | 0.422839E+10 | 0.50 | 10618.07 | 26-JUN-12:08 | 1.90 |
July | 0.495942E+10 | 0.53 | 10474.13 | 05-JUL-12:10 | 1.89 |
August | 0.520427E+10 | 0.55 | 11059.57 | 04-AUG-07:05 | 1.94 |
September | 0.349730E+10 | 0.45 | 8750.07 | 11-SEP-15:50 | 1.68 |
October | 0.174924E+10 | 0.32 | 3292.99 | 20-OCT-15:10 | 0.94 |
November | 0.153328E+10 | 0.32 | 2662.87 | 27-NOV-07:01 | 0.84 |
December | 0.158495E+10 | 0.34 | 2662.87 | 12-DEC-07:02 | 0.84 |
Annual Sum or Average | 0.319418E+11 | 0.40 | |||
Minimum of Months | 0.148528E+10 | 0.32 | 2662.87 | 0.84 | |
Maximum of Months | 0.520427E+10 | 0.55 | 11059.57 | 1.94 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.188932E+10 | 0.41 | 2656.17 | 04-JAN-06:03 | 0.90 |
February | 0.146729E+10 | 0.36 | 2656.17 | 03-FEB-06:03 | 0.90 |
March | 0.151786E+10 | 0.34 | 2656.17 | 13-MAR-05:01 | 0.90 |
April | 0.174521E+10 | 0.34 | 7310.71 | 18-APR-15:00 | 1.63 |
May | 0.239784E+10 | 0.40 | 7639.38 | 30-MAY-15:30 | 1.68 |
June | 0.422445E+10 | 0.53 | 9822.99 | 26-JUN-06:03 | 1.97 |
July | 0.461047E+10 | 0.54 | 9425.54 | 05-JUL-15:20 | 1.92 |
August | 0.454841E+10 | 0.54 | 9822.99 | 04-AUG-07:05 | 1.96 |
September | 0.287340E+10 | 0.43 | 9102.60 | 08-SEP-16:00 | 1.87 |
October | 0.147404E+10 | 0.31 | 2334.24 | 20-OCT-15:00 | 0.83 |
November | 0.143485E+10 | 0.33 | 2656.17 | 13-NOV-06:01 | 0.90 |
December | 0.163323E+10 | 0.36 | 2656.17 | 12-DEC-06:02 | 0.90 |
Annual Sum or Average | 0.298164E+11 | 0.41 | |||
Minimum of Months | 0.143485E+10 | 0.31 | 2334.24 | 0.83 | |
Maximum of Months | 0.461047E+10 | 0.54 | 9822.99 | 1.97 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.238528E+10 | 0.47 | 2635.49 | 19-JAN-07:01 | 0.83 |
February | 0.182320E+10 | 0.41 | 2635.49 | 03-FEB-07:03 | 0.83 |
March | 0.170158E+10 | 0.35 | 2635.49 | 01-MAR-07:01 | 0.82 |
April | 0.177517E+10 | 0.34 | 7154.69 | 18-APR-15:00 | 1.46 |
May | 0.230114E+10 | 0.37 | 7796.30 | 31-MAY-15:00 | 1.54 |
June | 0.399593E+10 | 0.48 | 10824.72 | 26-JUN-15:20 | 1.89 |
July | 0.424617E+10 | 0.48 | 9713.64 | 03-JUL-15:20 | 1.77 |
August | 0.409388E+10 | 0.48 | 10693.79 | 04-AUG-15:30 | 1.88 |
September | 0.255779E+10 | 0.39 | 8855.75 | 08-SEP-15:50 | 1.67 |
October | 0.147173E+10 | 0.30 | 2635.49 | 23-OCT-06:01 | 0.82 |
November | 0.166277E+10 | 0.36 | 2635.49 | 10-NOV-07:01 | 0.82 |
December | 0.203682E+10 | 0.41 | 2635.49 | 11-DEC-07:07 | 0.83 |
Annual Sum or Average | 0.300515E+11 | 0.40 | |||
Minimum of Months | 0.147173E+10 | 0.30 | 2635.49 | 0.82 | |
Maximum of Months | 0.424617E+10 | 0.48 | 10824.72 | 1.89 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1312252.65 | 393675.80 | 0.73 | 01-JAN-06:03 | 0.22 | 0.22 | 57.35 | 0.05 |
February | 1186778.30 | 356033.49 | 0.73 | 01-FEB-06:01 | 0.22 | 0.22 | 55.87 | 0.05 |
March | 1343621.24 | 403086.37 | 0.73 | 01-MAR-06:01 | 0.22 | 0.22 | 56.25 | 0.05 |
April | 1267813.82 | 380344.15 | 0.73 | 01-APR-05:01 | 0.22 | 0.22 | 56.11 | 0.05 |
May | 1327936.95 | 398381.08 | 0.73 | 01-MAY-05:03 | 0.22 | 0.22 | 55.46 | 0.05 |
June | 1296568.36 | 388970.51 | 0.73 | 01-JUN-05:03 | 0.22 | 0.22 | 55.77 | 0.05 |
July | 1299182.41 | 389754.72 | 0.73 | 01-JUL-05:03 | 0.22 | 0.22 | 56.53 | 0.05 |
August | 1343621.24 | 403086.37 | 0.73 | 01-AUG-05:03 | 0.22 | 0.22 | 55.76 | 0.05 |
September | 1267813.82 | 380344.15 | 0.73 | 01-SEP-05:03 | 0.22 | 0.22 | 55.77 | 0.05 |
October | 1312252.65 | 393675.80 | 0.73 | 01-OCT-05:10 | 0.22 | 0.22 | 57.34 | 0.05 |
November | 1278270.02 | 383481.00 | 0.73 | 01-NOV-05:02 | 0.22 | 0.22 | 55.80 | 0.05 |
December | 1299182.41 | 389754.72 | 0.73 | 01-DEC-06:01 | 0.22 | 0.22 | 55.67 | 0.05 |
Annual Sum or Average | 15535293.87 | 4660588.16 | ||||||
Minimum of Months | 1186778.30 | 356033.49 | 0.73 | 0.22 | 0.22 | 55.46 | 0.05 | |
Maximum of Months | 1343621.24 | 403086.37 | 0.73 | 0.22 | 0.22 | 57.35 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.33 | 57.33 | 2082.28 | 7369.66 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.38 | 56.38 | 2133.80 | 7415.08 | 23-FEB-12:09 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.75 | 56.75 | 2252.82 | 7405.50 | 01-MAR-12:09 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.55 | 56.55 | 2027.37 | 7200.15 | 03-APR-11:09 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.21 | 56.21 | 1986.60 | 6842.74 | 01-MAY-11:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.25 | 56.25 | 1909.71 | 6408.79 | 01-JUN-11:13 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.01 | 57.01 | 1660.01 | 5969.12 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.19 | 56.19 | 1780.87 | 5734.33 | 04-AUG-11:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.21 | 56.21 | 1684.84 | 5908.66 | 29-SEP-11:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 55.31 | 55.31 | 1761.15 | 6271.86 | 31-OCT-11:05 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.50 | 56.50 | 1901.14 | 6715.17 | 30-NOV-12:09 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.11 | 56.11 | 1937.93 | 7090.95 | 29-DEC-12:14 |
Annual Sum or Average | 0.00 | 1925.34 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.31 | 55.31 | 1660.01 | 5734.33 | ||
Maximum of Months | 0.00 | 0.00 | 57.33 | 57.33 | 2252.82 | 7415.08 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.355674E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.235674E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.163875E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.947290E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.686911E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.142319E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.182046E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.184442E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.986448E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.459341E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.129713E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.252274E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.195402E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.459341E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.355674E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.317222E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.185806E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.943539E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.506316E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.554798E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.132469E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.166738E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.159150E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.772672E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.264584E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.115711E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.237350E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.161864E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.264584E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.317222E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.505521E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.319152E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180293E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.876930E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.584613E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.137780E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.171838E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.159589E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.823747E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.583784E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.215862E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.404185E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.238113E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.583784E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.505521E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.191010E+10 | 0.00 | 0.622113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148528E+10 | 0.00 | 0.412500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156870E+10 | 0.140983E+09 | 0.253308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174229E+10 | 0.474701E+10 | 0.102503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247852E+10 | 0.130049E+11 | 0.147420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.422839E+10 | 0.419756E+11 | 0.514411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.495942E+10 | 0.601230E+11 | 50152687.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.520427E+10 | 0.591367E+11 | 0.180932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.349730E+10 | 0.235438E+11 | 0.113112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174924E+10 | 0.136758E+10 | 0.404500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153328E+10 | 44943156.65 | 0.207935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158495E+10 | 0.00 | 0.439549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319418E+11 | 0.204084E+12 | 0.211187E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148528E+10 | 0.00 | 50152687.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.520427E+10 | 0.601230E+11 | 0.622113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.188932E+10 | 0.00 | 0.581630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146729E+10 | 0.00 | 0.366400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151786E+10 | 0.142430E+09 | 0.195289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174521E+10 | 0.514164E+10 | 0.670453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239784E+10 | 0.135468E+11 | 0.190920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.422445E+10 | 0.400471E+11 | 8348299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.461047E+10 | 0.550189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.454841E+10 | 0.513749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.287340E+10 | 0.205305E+11 | 0.461686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147404E+10 | 0.123465E+10 | 0.339410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143485E+10 | 51034878.16 | 0.205596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163323E+10 | 0.00 | 0.431238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298164E+11 | 0.187088E+12 | 0.188775E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.461047E+10 | 0.550189E+11 | 0.581630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.238528E+10 | 0.00 | 0.798007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182320E+10 | 0.00 | 0.513268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170158E+10 | 0.147935E+09 | 0.283433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177517E+10 | 0.577162E+10 | 0.104573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.230114E+10 | 0.146001E+11 | 0.383349E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.399593E+10 | 0.431390E+11 | 51024898.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.424617E+10 | 0.588328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409388E+10 | 0.533239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.255779E+10 | 0.212807E+11 | 0.121772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147173E+10 | 0.123815E+10 | 0.696752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166277E+10 | 37289923.77 | 0.314005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203682E+10 | 0.00 | 0.615347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300515E+11 | 0.198371E+12 | 0.271483E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.424617E+10 | 0.588328E+11 | 0.798007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.191010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156870E+10 | 0.00 | 0.00 | 0.00 | 36653806.85 | 0.147821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174229E+10 | 0.00 | 0.00 | 0.00 | 0.111660E+10 | 0.661402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247852E+10 | 0.00 | 0.00 | 0.00 | 0.301861E+10 | 0.137199E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.422839E+10 | 0.00 | 0.00 | 0.00 | 0.949198E+10 | 0.511569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.495942E+10 | 0.00 | 0.00 | 0.00 | 0.131951E+11 | 50152687.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.520427E+10 | 0.00 | 0.00 | 0.00 | 0.130590E+11 | 0.180932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.349730E+10 | 0.00 | 0.00 | 0.00 | 0.542751E+10 | 0.939671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174924E+10 | 0.00 | 0.00 | 0.00 | 0.334396E+09 | 0.250978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153328E+10 | 0.00 | 0.00 | 0.00 | 11829059.20 | 0.114262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319418E+11 | 0.00 | 0.00 | 0.00 | 0.456916E+11 | 0.117768E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50152687.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.520427E+10 | 0.00 | 0.00 | 0.00 | 0.131951E+11 | 0.336573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.188932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151786E+10 | 0.00 | 0.00 | 0.00 | 36904556.92 | 0.788062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.174521E+10 | 0.00 | 0.00 | 0.00 | 0.119510E+10 | 0.212285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.239784E+10 | 0.00 | 0.00 | 0.00 | 0.312892E+10 | 21226456.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.422445E+10 | 0.00 | 0.00 | 0.00 | 0.902248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.461047E+10 | 0.00 | 0.00 | 0.00 | 0.120634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.454841E+10 | 0.00 | 0.00 | 0.00 | 0.113666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.287340E+10 | 0.00 | 0.00 | 0.00 | 0.474291E+10 | 0.110414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147404E+10 | 0.00 | 0.00 | 0.00 | 0.303029E+09 | 0.868774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143485E+10 | 0.00 | 0.00 | 0.00 | 13338779.09 | 0.101229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298164E+11 | 0.00 | 0.00 | 0.00 | 0.418726E+11 | 0.901747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.461047E+10 | 0.00 | 0.00 | 0.00 | 0.120634E+11 | 0.298328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.238528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.182320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170158E+10 | 0.00 | 0.00 | 0.00 | 38412742.14 | 0.162893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177517E+10 | 0.00 | 0.00 | 0.00 | 0.133944E+10 | 0.565469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.230114E+10 | 0.00 | 0.00 | 0.00 | 0.338012E+10 | 0.164871E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.399593E+10 | 0.00 | 0.00 | 0.00 | 0.975467E+10 | 27358359.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.424617E+10 | 0.00 | 0.00 | 0.00 | 0.129376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409388E+10 | 0.00 | 0.00 | 0.00 | 0.118650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.255779E+10 | 0.00 | 0.00 | 0.00 | 0.495136E+10 | 0.728322E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147173E+10 | 0.00 | 0.00 | 0.00 | 0.306551E+09 | 0.405956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.166277E+10 | 0.00 | 0.00 | 0.00 | 9831808.18 | 0.199136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300515E+11 | 0.00 | 0.00 | 0.00 | 0.445830E+11 | 0.163478E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.424617E+10 | 0.00 | 0.00 | 0.00 | 0.129376E+11 | 0.481668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.201083E+11 | 0.00 | 0.00 | 147154.52 | 0.00 | 0.112708E+10 | 0.234447E+09 | 0.00 | 0.27 |
February | 0.160636E+11 | 0.00 | 0.00 | 611642.64 | 0.00 | 0.123840E+09 | 0.115924E+10 | 0.00 | 0.28 |
March | 0.107580E+11 | 0.00 | 0.00 | 10372092.06 | 0.00 | 5663574.14 | 0.647139E+10 | 0.00 | 0.35 |
April | 0.508143E+10 | 0.233433E+09 | 0.00 | 19534680.24 | 33488798.96 | 0.00 | 0.965473E+10 | 0.00 | 0.44 |
May | 0.137019E+10 | 0.281915E+09 | 0.00 | 31675888.42 | 26233262.00 | 0.00 | 0.142945E+11 | 0.00 | 0.83 |
June | 0.526282E+09 | 0.300611E+10 | 0.00 | 26785350.20 | 0.225761E+09 | 0.00 | 0.932636E+10 | 0.00 | 0.92 |
July | 0.501287E+09 | 0.522250E+10 | 0.00 | 17788565.04 | 0.601168E+09 | 0.00 | 0.378476E+10 | 0.00 | 0.92 |
August | 0.732567E+09 | 0.528604E+10 | 0.00 | 25868364.73 | 0.323734E+09 | 0.00 | 0.583094E+10 | 0.00 | 0.99 |
September | 0.125174E+10 | 0.534373E+09 | 0.00 | 33757431.74 | 92661543.61 | 0.00 | 0.139077E+11 | 0.00 | 0.83 |
October | 0.267890E+10 | 0.00 | 0.00 | 26888825.23 | 5755524.74 | 0.00 | 0.141962E+11 | 0.00 | 0.50 |
November | 0.825122E+10 | 0.00 | 0.00 | 13379081.27 | 0.00 | 42068259.73 | 0.850029E+10 | 0.00 | 0.38 |
December | 0.165344E+11 | 0.00 | 0.00 | 1158637.25 | 0.00 | 0.162422E+09 | 0.201800E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.838579E+11 | 0.145644E+11 | 0.00 | 0.207968E+09 | 0.130880E+10 | 0.146108E+10 | 0.893785E+11 | 0.00 | 0.58 |
Minimum of Months | 0.501287E+09 | 0.00 | 0.00 | 147154.52 | 0.00 | 0.00 | 0.234447E+09 | 0.00 | 0.27 |
Maximum of Months | 0.201083E+11 | 0.528604E+10 | 0.00 | 33757431.74 | 0.601168E+09 | 0.112708E+10 | 0.142945E+11 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.138239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780721E+10 | 0.00 | 0.00 | 0.27 |
February | 0.139000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314908E+10 | 0.00 | 0.00 | 0.27 |
March | 0.147654E+11 | 0.00 | 0.00 | 58644.76 | 0.00 | 0.694171E+09 | 0.170230E+09 | 0.00 | 0.31 |
April | 0.909661E+10 | 0.103349E+09 | 0.00 | 3719312.55 | 0.119849E+09 | 97078291.18 | 0.281119E+10 | 0.00 | 0.36 |
May | 0.434942E+10 | 0.206138E+09 | 0.00 | 12168276.76 | 0.118059E+09 | 0.00 | 0.662659E+10 | 0.00 | 0.58 |
June | 0.131802E+10 | 0.228152E+10 | 0.00 | 14960308.01 | 0.256606E+09 | 0.00 | 0.526166E+10 | 0.00 | 0.63 |
July | 0.563491E+09 | 0.400851E+10 | 0.00 | 10790074.62 | 0.535185E+09 | 0.00 | 0.227290E+10 | 0.00 | 0.66 |
August | 0.783071E+09 | 0.383415E+10 | 0.00 | 15334207.82 | 0.339472E+09 | 0.00 | 0.342877E+10 | 0.00 | 0.67 |
September | 0.324965E+10 | 0.385165E+09 | 0.00 | 13827804.15 | 91761577.82 | 0.00 | 0.618860E+10 | 0.00 | 0.54 |
October | 0.949836E+10 | 0.00 | 0.00 | 1319070.00 | 9307137.25 | 490394.30 | 0.198831E+10 | 0.00 | 0.34 |
November | 0.116051E+11 | 0.00 | 0.00 | 241717.80 | 0.00 | 0.169302E+10 | 0.762599E+09 | 0.00 | 0.31 |
December | 0.140957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414520E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.970485E+11 | 0.108188E+11 | 0.00 | 72419416.46 | 0.147024E+10 | 0.175862E+11 | 0.295108E+11 | 0.00 | 0.43 |
Minimum of Months | 0.563491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.147654E+11 | 0.400851E+10 | 0.00 | 15334207.82 | 0.535185E+09 | 0.780721E+10 | 0.662659E+10 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.635614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131661E+11 | 0.00 | 0.00 | 0.25 |
February | 0.794589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765252E+10 | 0.00 | 0.00 | 0.26 |
March | 0.120313E+11 | 0.00 | 0.00 | 28518.68 | 0.00 | 0.266465E+10 | 89254032.80 | 0.00 | 0.30 |
April | 0.907840E+10 | 0.109091E+09 | 0.00 | 2673516.62 | 0.155773E+09 | 0.617286E+09 | 0.182133E+10 | 0.00 | 0.36 |
May | 0.504232E+10 | 0.165629E+09 | 0.00 | 10179655.59 | 80576846.24 | 439673.14 | 0.571215E+10 | 0.00 | 0.59 |
June | 0.196691E+10 | 0.218771E+10 | 0.00 | 12286905.40 | 0.363790E+09 | 0.00 | 0.446599E+10 | 0.00 | 0.66 |
July | 0.832979E+09 | 0.413769E+10 | 0.00 | 8371700.05 | 0.683531E+09 | 0.00 | 0.196512E+10 | 0.00 | 0.71 |
August | 0.109695E+10 | 0.349874E+10 | 0.00 | 12527466.01 | 0.528796E+09 | 0.00 | 0.280545E+10 | 0.00 | 0.69 |
September | 0.482604E+10 | 0.326890E+09 | 0.00 | 8308462.11 | 0.112205E+09 | 30460892.76 | 0.352380E+10 | 0.00 | 0.52 |
October | 0.102513E+11 | 0.00 | 0.00 | 165208.27 | 5402325.27 | 0.269642E+09 | 0.254878E+09 | 0.00 | 0.34 |
November | 0.876207E+10 | 0.00 | 253074.96 | 26478.28 | 0.00 | 0.406316E+10 | 82890177.91 | 163971.41 | 0.30 |
December | 0.740882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908241E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.755990E+11 | 0.104258E+11 | 253074.96 | 54567911.02 | 0.193007E+10 | 0.375466E+11 | 0.207209E+11 | 163971.41 | 0.44 |
Minimum of Months | 0.832979E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.120313E+11 | 0.413769E+10 | 253074.96 | 12527466.01 | 0.683531E+09 | 0.131661E+11 | 0.571215E+10 | 163971.41 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 89946296.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599315E+10 | 0.00 | 0.00 | 0.36 |
February | 0.174617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430665E+10 | 0.00 | 0.00 | 0.33 |
March | 0.106206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235611E+10 | 0.00 | 0.00 | 0.33 |
April | 0.146941E+10 | 43062746.71 | 0.00 | 416588.25 | 25363837.08 | 0.830520E+09 | 0.259777E+09 | 0.00 | 0.39 |
May | 0.132729E+10 | 53055966.86 | 0.00 | 2410911.14 | 16862931.01 | 22503215.27 | 0.111747E+10 | 0.00 | 0.67 |
June | 0.499295E+09 | 0.727160E+09 | 0.00 | 3280177.47 | 73237304.96 | 596093.35 | 0.107704E+10 | 0.00 | 0.87 |
July | 0.193439E+09 | 0.128825E+10 | 0.00 | 2299831.63 | 0.144724E+09 | 0.00 | 0.499356E+09 | 0.00 | 0.92 |
August | 0.314665E+09 | 0.108303E+10 | 0.00 | 2946503.02 | 96456259.48 | 0.00 | 0.608635E+09 | 0.00 | 0.85 |
September | 0.120455E+10 | 99673187.56 | 0.00 | 1537942.38 | 21467452.93 | 94614723.90 | 0.559764E+09 | 0.00 | 0.57 |
October | 0.172789E+10 | 0.00 | 0.00 | 7168.94 | 1198835.22 | 0.658999E+09 | 16585112.80 | 0.00 | 0.35 |
November | 0.777213E+09 | 0.00 | 62452.96 | 0.00 | 0.00 | 0.237944E+10 | 0.00 | 59624.12 | 0.33 |
December | 55752810.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.442165E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.889613E+10 | 0.329424E+10 | 62452.96 | 12899122.83 | 0.379311E+09 | 0.210642E+11 | 0.413862E+10 | 59624.12 | 0.52 |
Minimum of Months | 55752810.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.172789E+10 | 0.128825E+10 | 62452.96 | 3280177.47 | 0.144724E+09 | 0.599315E+10 | 0.111747E+10 | 59624.12 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418341E+10 | 0.00 | 0.00 | 0.41 |
February | 0.399963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299458E+10 | 0.00 | 0.00 | 0.42 |
March | 0.144121E+10 | 0.00 | 0.00 | 87965.83 | 0.00 | 0.154238E+10 | 83693315.51 | 0.00 | 0.47 |
April | 0.133028E+10 | 68780857.38 | 0.00 | 932276.26 | 14986838.53 | 0.592158E+09 | 0.587890E+09 | 0.00 | 0.62 |
May | 0.949406E+09 | 65021041.15 | 0.00 | 3398364.62 | 9358789.09 | 5576094.25 | 0.162558E+10 | 0.00 | 1.10 |
June | 0.470095E+09 | 0.695893E+09 | 0.00 | 3888420.76 | 53242072.62 | 915659.99 | 0.130818E+10 | 0.00 | 1.45 |
July | 0.138821E+09 | 0.118398E+10 | 0.00 | 3220742.67 | 0.111630E+09 | 0.00 | 0.674591E+09 | 0.00 | 1.58 |
August | 0.252496E+09 | 0.990000E+09 | 0.00 | 3751397.51 | 84556726.78 | 0.00 | 0.797315E+09 | 0.00 | 1.39 |
September | 0.917322E+09 | 0.108408E+09 | 0.00 | 2696474.23 | 15199499.78 | 47449215.56 | 0.883228E+09 | 0.00 | 0.97 |
October | 0.179790E+10 | 0.00 | 0.00 | 89010.74 | 1110466.80 | 0.383249E+09 | 42839756.59 | 0.00 | 0.52 |
November | 0.786587E+09 | 0.00 | 55793.47 | 0.00 | 0.00 | 0.191058E+10 | 0.00 | 37072.28 | 0.46 |
December | 0.146751E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345622E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.879874E+10 | 0.311209E+10 | 55793.47 | 18064652.61 | 0.290084E+09 | 0.151165E+11 | 0.600332E+10 | 37072.28 | 0.82 |
Minimum of Months | 0.138821E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.179790E+10 | 0.118398E+10 | 55793.47 | 3888420.76 | 0.111630E+09 | 0.418341E+10 | 0.162558E+10 | 37072.28 | 1.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125625E+10 | 0.00 | 0.00 | 425550.97 | 0.00 | 0.410170E+10 | 0.265691E+09 | 0.00 | 0.34 |
February | 0.134241E+10 | 0.00 | 0.00 | 827898.34 | 0.00 | 0.266653E+10 | 0.434418E+09 | 0.00 | 0.35 |
March | 0.157435E+10 | 0.00 | 0.00 | 1772080.74 | 0.00 | 0.165902E+10 | 0.102810E+10 | 0.00 | 0.43 |
April | 0.142644E+10 | 0.122121E+09 | 0.00 | 2891163.81 | 15851313.15 | 0.699714E+09 | 0.153128E+10 | 0.00 | 0.60 |
May | 0.122742E+10 | 79900781.00 | 0.00 | 4458090.25 | 14201774.70 | 28450901.36 | 0.202737E+10 | 0.00 | 0.91 |
June | 0.612349E+09 | 0.856540E+09 | 0.00 | 3958587.15 | 84653921.81 | 1106740.73 | 0.132753E+10 | 0.00 | 1.06 |
July | 0.239807E+09 | 0.158705E+10 | 0.00 | 3129423.28 | 0.141430E+09 | 0.00 | 0.625707E+09 | 0.00 | 1.16 |
August | 0.320109E+09 | 0.142857E+10 | 0.00 | 5052320.81 | 87120384.75 | 0.00 | 0.106192E+10 | 0.00 | 1.21 |
September | 0.107812E+10 | 0.221067E+09 | 0.00 | 5507571.20 | 9506686.85 | 63482442.11 | 0.169625E+10 | 0.00 | 0.99 |
October | 0.156794E+10 | 594274.97 | 0.00 | 3723232.31 | 900019.70 | 0.349267E+09 | 0.177000E+10 | 0.00 | 0.59 |
November | 0.134585E+10 | 0.00 | 66173.50 | 772546.44 | 0.00 | 0.181659E+10 | 0.452214E+09 | 58756.05 | 0.41 |
December | 0.746277E+09 | 0.00 | 0.00 | 981052.66 | 0.00 | 0.352950E+10 | 0.526862E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.127373E+11 | 0.429585E+10 | 66173.50 | 33499517.97 | 0.353664E+09 | 0.149154E+11 | 0.127473E+11 | 58756.05 | 0.70 |
Minimum of Months | 0.239807E+09 | 0.00 | 0.00 | 425550.97 | 0.00 | 0.00 | 0.265691E+09 | 0.00 | 0.34 |
Maximum of Months | 0.157435E+10 | 0.158705E+10 | 66173.50 | 5507571.20 | 0.141430E+09 | 0.410170E+10 | 0.202737E+10 | 58756.05 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.341791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441452E+10 | 0.00 | 0.00 | 0.45 |
February | 0.536513E+09 | 0.00 | 0.00 | 35702.85 | 0.00 | 0.319987E+10 | 34777769.74 | 0.00 | 0.46 |
March | 0.128452E+10 | 0.00 | 0.00 | 302431.61 | 0.00 | 0.188530E+10 | 0.210623E+09 | 0.00 | 0.52 |
April | 0.135787E+10 | 47226277.35 | 0.00 | 1568375.62 | 25285019.05 | 0.668824E+09 | 0.855742E+09 | 0.00 | 0.71 |
May | 0.134296E+10 | 53959311.59 | 0.00 | 2977125.11 | 17616292.79 | 28631040.46 | 0.127978E+10 | 0.00 | 1.12 |
June | 0.585549E+09 | 0.628712E+09 | 0.00 | 3260042.70 | 64771610.35 | 2373653.27 | 0.104190E+10 | 0.00 | 1.36 |
July | 0.215124E+09 | 0.132784E+10 | 0.00 | 2942363.66 | 85523907.40 | 0.00 | 0.484150E+09 | 0.00 | 1.45 |
August | 0.318264E+09 | 0.967569E+09 | 0.00 | 3626199.90 | 97474317.63 | 0.00 | 0.695539E+09 | 0.00 | 1.40 |
September | 0.123217E+10 | 0.115174E+09 | 0.00 | 2301342.16 | 15759093.61 | 95198549.78 | 0.649872E+09 | 0.00 | 1.00 |
October | 0.163497E+10 | 0.00 | 0.00 | 645553.25 | 1220130.09 | 0.500991E+09 | 0.379210E+09 | 0.00 | 0.60 |
November | 0.917465E+09 | 0.00 | 61692.44 | 62456.87 | 110.33 | 0.201493E+10 | 42259851.89 | 37062.68 | 0.51 |
December | 0.360097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353564E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.101273E+11 | 0.314048E+10 | 61692.44 | 17721593.73 | 0.307650E+09 | 0.163463E+11 | 0.567385E+10 | 37062.68 | 0.84 |
Minimum of Months | 0.215124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.163497E+10 | 0.132784E+10 | 61692.44 | 3626199.90 | 97474317.63 | 0.441452E+10 | 0.127978E+10 | 37062.68 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578369E+10 | 0.00 | 0.00 | 0.34 |
February | 0.121696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432004E+10 | 0.00 | 0.00 | 0.32 |
March | 0.909247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263996E+10 | 0.00 | 0.00 | 0.33 |
April | 0.144961E+10 | 14821449.39 | 0.00 | 20013.21 | 28067273.94 | 0.103296E+10 | 21664266.89 | 0.00 | 0.34 |
May | 0.183390E+10 | 36163324.34 | 0.00 | 298875.20 | 8103238.39 | 24527800.25 | 0.237431E+09 | 0.00 | 0.51 |
June | 0.652299E+09 | 0.512033E+09 | 0.00 | 2062715.07 | 60717620.73 | 0.00 | 0.646209E+09 | 0.00 | 0.63 |
July | 0.244771E+09 | 0.906759E+09 | 0.00 | 1750908.11 | 0.133430E+09 | 0.00 | 0.377001E+09 | 0.00 | 0.69 |
August | 0.372439E+09 | 0.913387E+09 | 0.00 | 2502590.13 | 92956988.71 | 0.00 | 0.556818E+09 | 0.00 | 0.72 |
September | 0.130361E+10 | 98771958.75 | 0.00 | 1734056.08 | 20856764.18 | 9642044.15 | 0.702438E+09 | 0.00 | 0.55 |
October | 0.247300E+10 | 0.00 | 0.00 | 1954.68 | 1239821.87 | 0.106349E+09 | 21841592.92 | 0.00 | 0.36 |
November | 0.135633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190531E+10 | 0.00 | 0.00 | 0.33 |
December | 98620249.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434095E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.109477E+11 | 0.248194E+10 | 0.00 | 8371112.48 | 0.345371E+09 | 0.201634E+11 | 0.256340E+10 | 0.00 | 0.45 |
Minimum of Months | 98620249.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.247300E+10 | 0.913387E+09 | 0.00 | 2502590.13 | 0.133430E+09 | 0.578369E+10 | 0.702438E+09 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189032E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386528E+10 | 0.00 | 0.00 | 0.37 |
February | 0.365713E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279678E+10 | 0.00 | 0.00 | 0.37 |
March | 0.123559E+10 | 0.00 | 0.00 | 6234.31 | 0.00 | 0.146809E+10 | 12270402.16 | 0.00 | 0.40 |
April | 0.122129E+10 | 40086703.08 | 0.00 | 435293.50 | 7662589.36 | 0.541801E+09 | 0.250874E+09 | 0.00 | 0.46 |
May | 0.944844E+09 | 47155471.76 | 0.00 | 1882587.77 | 5460834.86 | 619937.60 | 0.936754E+09 | 0.00 | 0.77 |
June | 0.427739E+09 | 0.567510E+09 | 0.00 | 3117080.95 | 25475909.17 | 0.00 | 0.976438E+09 | 0.00 | 1.10 |
July | 0.144925E+09 | 0.927765E+09 | 0.00 | 2797071.68 | 86322818.52 | 0.00 | 0.565554E+09 | 0.00 | 1.23 |
August | 0.205382E+09 | 0.891048E+09 | 0.00 | 3687442.82 | 60109868.67 | 0.00 | 0.816613E+09 | 0.00 | 1.19 |
September | 0.737779E+09 | 0.110557E+09 | 0.00 | 3275279.88 | 12847513.55 | 1977042.04 | 0.115494E+10 | 0.00 | 0.90 |
October | 0.178592E+10 | 0.00 | 0.00 | 214770.38 | 962253.76 | 33831793.01 | 0.210851E+09 | 0.00 | 0.44 |
November | 0.112864E+10 | 0.00 | 0.00 | 277.09 | 0.00 | 0.134677E+10 | 3632516.96 | 0.00 | 0.39 |
December | 0.308814E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300997E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.869566E+10 | 0.258412E+10 | 0.00 | 15416038.37 | 0.198842E+09 | 0.130651E+11 | 0.492793E+10 | 0.00 | 0.67 |
Minimum of Months | 0.144925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.178592E+10 | 0.927765E+09 | 0.00 | 3687442.82 | 86322818.52 | 0.386528E+10 | 0.115494E+10 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.859003E+10 | 0.00 | 0.00 | 0.50 |
February | 0.296894E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590637E+10 | 0.00 | 0.00 | 0.44 |
March | 0.665232E+09 | 0.00 | 0.00 | 77990.91 | 0.00 | 0.417111E+10 | 64591437.43 | 0.00 | 0.43 |
April | 0.820210E+09 | 90357262.43 | 18227.99 | 326905.74 | 7212107.68 | 0.216565E+10 | 0.179376E+09 | 1722.32 | 0.43 |
May | 0.153999E+10 | 67960106.36 | 0.00 | 557032.72 | 7199091.47 | 0.557434E+09 | 0.206413E+09 | 0.00 | 0.58 |
June | 0.749228E+09 | 0.700571E+09 | 0.00 | 1529603.34 | 64653572.97 | 0.210501E+09 | 0.395455E+09 | 0.00 | 0.69 |
July | 0.296817E+09 | 0.122274E+10 | 0.00 | 1655228.41 | 0.144165E+09 | 21058403.54 | 0.307659E+09 | 0.00 | 0.80 |
August | 0.326996E+09 | 0.136863E+10 | 0.00 | 3654749.79 | 86937722.49 | 83155654.51 | 0.708600E+09 | 0.00 | 0.95 |
September | 0.106518E+10 | 0.240644E+09 | 0.00 | 3743720.21 | 12030398.77 | 0.393948E+09 | 0.996282E+09 | 0.00 | 0.82 |
October | 0.159637E+10 | 829299.14 | 0.00 | 1115253.33 | 568004.09 | 0.988597E+09 | 0.635388E+09 | 0.00 | 0.46 |
November | 0.931161E+09 | 0.00 | 0.00 | 353258.20 | 0.00 | 0.335385E+10 | 0.219163E+09 | 0.00 | 0.44 |
December | 0.352443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.631891E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.885431E+10 | 0.369174E+10 | 18227.99 | 13013742.63 | 0.322766E+09 | 0.327606E+11 | 0.371293E+10 | 1722.32 | 0.58 |
Minimum of Months | 0.213783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21058403.54 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.159637E+10 | 0.136863E+10 | 18227.99 | 3743720.21 | 0.144165E+09 | 0.859003E+10 | 0.996282E+09 | 1722.32 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412700E+10 | 0.00 | 0.00 | 0.40 |
February | 0.393940E+09 | 0.00 | 0.00 | 4137.65 | 0.00 | 0.301157E+10 | 5409671.15 | 0.00 | 0.39 |
March | 0.114686E+10 | 0.00 | 0.00 | 7381.46 | 0.00 | 0.172836E+10 | 23886930.42 | 0.00 | 0.42 |
April | 0.126355E+10 | 28843910.78 | 0.00 | 644794.76 | 14505074.01 | 0.555315E+09 | 0.363155E+09 | 0.00 | 0.50 |
May | 0.127008E+10 | 45274577.33 | 0.00 | 1207663.75 | 6473694.45 | 11165749.30 | 0.563761E+09 | 0.00 | 0.74 |
June | 0.505718E+09 | 0.513987E+09 | 0.00 | 2614673.85 | 31866068.84 | 0.00 | 0.738359E+09 | 0.00 | 1.02 |
July | 0.176167E+09 | 0.103061E+10 | 0.00 | 2310680.01 | 60981688.17 | 0.00 | 0.403369E+09 | 0.00 | 1.10 |
August | 0.246521E+09 | 0.912386E+09 | 0.00 | 3329883.61 | 50536176.83 | 0.00 | 0.688045E+09 | 0.00 | 1.18 |
September | 0.936057E+09 | 0.123818E+09 | 0.00 | 2511241.53 | 10800635.74 | 10940870.69 | 0.862483E+09 | 0.00 | 0.87 |
October | 0.181087E+10 | 0.00 | 0.00 | 700713.86 | 1027916.76 | 54311793.02 | 0.372479E+09 | 0.00 | 0.50 |
November | 0.122754E+10 | 0.00 | 0.00 | 52822.41 | 0.00 | 0.139265E+10 | 35913980.71 | 0.00 | 0.42 |
December | 0.378141E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313808E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.956440E+10 | 0.265492E+10 | 0.00 | 13383992.90 | 0.176191E+09 | 0.140294E+11 | 0.405686E+10 | 0.00 | 0.66 |
Minimum of Months | 0.176167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.181087E+10 | 0.103061E+10 | 0.00 | 3329883.61 | 60981688.17 | 0.412700E+10 | 0.862483E+09 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148655E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552640E+10 | 0.00 | 0.00 | 0.32 |
February | 0.345295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394414E+10 | 0.00 | 0.00 | 0.31 |
March | 0.147154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188363E+10 | 0.00 | 0.00 | 0.31 |
April | 0.173867E+10 | 45127297.36 | 0.00 | 526961.11 | 12781945.19 | 0.483930E+09 | 0.284216E+09 | 0.00 | 0.36 |
May | 0.107274E+10 | 67960688.89 | 0.00 | 2825497.34 | 23221605.44 | 2973091.14 | 0.132149E+10 | 0.00 | 0.64 |
June | 0.374225E+09 | 0.765939E+09 | 0.00 | 3715402.09 | 46574601.68 | 0.00 | 0.117141E+10 | 0.00 | 0.82 |
July | 0.142739E+09 | 0.125639E+10 | 0.00 | 2635080.08 | 0.109210E+09 | 0.00 | 0.528477E+09 | 0.00 | 0.84 |
August | 0.255653E+09 | 0.116856E+10 | 0.00 | 3090345.61 | 70361182.41 | 0.00 | 0.659748E+09 | 0.00 | 0.80 |
September | 0.113089E+10 | 0.121869E+09 | 0.00 | 2015315.71 | 14441311.61 | 23340112.94 | 0.776933E+09 | 0.00 | 0.55 |
October | 0.216609E+10 | 0.00 | 0.00 | 53746.52 | 1961928.64 | 0.176847E+09 | 80918449.55 | 0.00 | 0.34 |
November | 0.118028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193622E+10 | 0.00 | 0.00 | 0.31 |
December | 91523513.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421496E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.101183E+11 | 0.342585E+10 | 0.00 | 14862348.47 | 0.278553E+09 | 0.181924E+11 | 0.482319E+10 | 0.00 | 0.49 |
Minimum of Months | 91523513.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.216609E+10 | 0.125639E+10 | 0.00 | 3715402.09 | 0.109210E+09 | 0.552640E+10 | 0.132149E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445965E+10 | 0.00 | 0.00 | 0.43 |
February | 0.694490E+09 | 0.00 | 0.00 | 52.48 | 0.00 | 0.297277E+10 | 1115129.16 | 0.00 | 0.44 |
March | 0.180189E+10 | 0.00 | 0.00 | 173663.05 | 0.00 | 0.137634E+10 | 0.124083E+09 | 0.00 | 0.49 |
April | 0.162492E+10 | 62360628.73 | 0.00 | 1072014.05 | 8235363.89 | 0.373471E+09 | 0.662251E+09 | 0.00 | 0.62 |
May | 0.897328E+09 | 77146681.15 | 0.00 | 3689068.16 | 15335463.65 | 249372.16 | 0.173515E+10 | 0.00 | 1.09 |
June | 0.456108E+09 | 0.710812E+09 | 0.00 | 3976765.74 | 34775359.19 | 0.00 | 0.130848E+10 | 0.00 | 1.36 |
July | 0.130134E+09 | 0.111996E+10 | 0.00 | 3344503.12 | 93318893.49 | 0.00 | 0.685402E+09 | 0.00 | 1.44 |
August | 0.235315E+09 | 0.101268E+10 | 0.00 | 3759200.33 | 71797836.23 | 0.00 | 0.862645E+09 | 0.00 | 1.31 |
September | 0.983760E+09 | 0.118283E+09 | 0.00 | 3200568.04 | 11837733.19 | 11462689.08 | 0.107990E+10 | 0.00 | 0.98 |
October | 0.215351E+10 | 0.00 | 0.00 | 183195.21 | 1947753.32 | 0.135155E+09 | 0.130088E+09 | 0.00 | 0.54 |
November | 0.117330E+10 | 0.00 | 0.00 | 7843.91 | 0.00 | 0.177797E+10 | 11826497.46 | 0.00 | 0.48 |
December | 0.387075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351258E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.107663E+11 | 0.310125E+10 | 0.00 | 19406874.09 | 0.237248E+09 | 0.146197E+11 | 0.660094E+10 | 0.00 | 0.80 |
Minimum of Months | 0.130134E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.215351E+10 | 0.111996E+10 | 0.00 | 3976765.74 | 93318893.49 | 0.445965E+10 | 0.173515E+10 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140989E+10 | 0.00 | 0.00 | 699793.02 | 0.00 | 0.379504E+10 | 0.434818E+09 | 0.00 | 0.33 |
February | 0.161544E+10 | 0.00 | 0.00 | 1029925.99 | 0.00 | 0.232140E+10 | 0.545969E+09 | 0.00 | 0.34 |
March | 0.182674E+10 | 0.00 | 0.00 | 2271475.94 | 0.00 | 0.128921E+10 | 0.121738E+10 | 0.00 | 0.43 |
April | 0.169905E+10 | 0.126869E+09 | 0.00 | 3102869.55 | 7100015.62 | 0.369937E+09 | 0.151717E+10 | 0.00 | 0.57 |
May | 0.103127E+10 | 0.106759E+09 | 0.00 | 4685156.92 | 18923931.58 | 2940665.50 | 0.210093E+10 | 0.00 | 0.87 |
June | 0.478181E+09 | 0.904675E+09 | 0.00 | 4265439.71 | 52973478.60 | 0.00 | 0.134330E+10 | 0.00 | 0.98 |
July | 0.190858E+09 | 0.152783E+10 | 0.00 | 3066702.77 | 0.115622E+09 | 0.00 | 0.589483E+09 | 0.00 | 1.02 |
August | 0.283088E+09 | 0.153094E+10 | 0.00 | 4829391.02 | 66024049.72 | 0.00 | 0.100205E+10 | 0.00 | 1.11 |
September | 0.953461E+09 | 0.255522E+09 | 0.00 | 5982611.80 | 10649580.78 | 15185626.90 | 0.197517E+10 | 0.00 | 0.97 |
October | 0.169462E+10 | 1812950.65 | 0.00 | 4832397.98 | 963669.34 | 0.119710E+09 | 0.214951E+10 | 0.00 | 0.62 |
November | 0.175876E+10 | 0.00 | 0.00 | 1179643.45 | 0.00 | 0.133692E+10 | 0.624724E+09 | 0.00 | 0.41 |
December | 0.899793E+09 | 0.00 | 0.00 | 1379583.42 | 0.00 | 0.324576E+10 | 0.771911E+09 | 0.00 | 0.34 |
Annual Sum or Average | 0.138412E+11 | 0.445441E+10 | 0.00 | 37324991.58 | 0.272257E+09 | 0.124961E+11 | 0.142724E+11 | 0.00 | 0.67 |
Minimum of Months | 0.190858E+09 | 0.00 | 0.00 | 699793.02 | 0.00 | 0.00 | 0.434818E+09 | 0.00 | 0.33 |
Maximum of Months | 0.182674E+10 | 0.153094E+10 | 0.00 | 5982611.80 | 0.115622E+09 | 0.379504E+10 | 0.214951E+10 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.481522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438354E+10 | 0.00 | 0.00 | 0.45 |
February | 0.851267E+09 | 0.00 | 0.00 | 46716.74 | 0.00 | 0.292196E+10 | 45066996.45 | 0.00 | 0.45 |
March | 0.164237E+10 | 0.00 | 0.00 | 380249.38 | 0.00 | 0.155375E+10 | 0.229490E+09 | 0.00 | 0.51 |
April | 0.163986E+10 | 47752295.24 | 0.00 | 1636282.76 | 15498735.12 | 0.362467E+09 | 0.843503E+09 | 0.00 | 0.67 |
May | 0.114084E+10 | 73376566.02 | 0.00 | 3035273.58 | 22322450.88 | 5186671.48 | 0.133033E+10 | 0.00 | 1.05 |
June | 0.519651E+09 | 0.669649E+09 | 0.00 | 3414081.99 | 39009383.50 | 0.00 | 0.999861E+09 | 0.00 | 1.26 |
July | 0.204117E+09 | 0.125286E+10 | 0.00 | 2676572.42 | 59871038.78 | 0.00 | 0.422604E+09 | 0.00 | 1.27 |
August | 0.291234E+09 | 0.104788E+10 | 0.00 | 3346692.55 | 65339646.52 | 0.00 | 0.661894E+09 | 0.00 | 1.27 |
September | 0.120421E+10 | 0.141810E+09 | 0.00 | 2347607.79 | 9625893.64 | 30564174.97 | 0.755807E+09 | 0.00 | 0.94 |
October | 0.199026E+10 | 0.00 | 0.00 | 865005.21 | 2009054.97 | 0.171749E+09 | 0.436161E+09 | 0.00 | 0.59 |
November | 0.131599E+10 | 0.00 | 0.00 | 78082.35 | 0.00 | 0.170740E+10 | 49937319.47 | 0.00 | 0.50 |
December | 0.491412E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352758E+10 | 0.00 | 0.00 | 0.44 |
Annual Sum or Average | 0.117727E+11 | 0.323333E+10 | 0.00 | 17826564.78 | 0.213676E+09 | 0.146642E+11 | 0.577465E+10 | 0.00 | 0.79 |
Minimum of Months | 0.204117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.199026E+10 | 0.125286E+10 | 0.00 | 3414081.99 | 65339646.52 | 0.438354E+10 | 0.133033E+10 | 0.00 | 1.27 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:35:21
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.214061E+12 | 0.269594E+11 | 0.00 | 0.152268E+12 | 0.221295E+11 |
February | 0.231711E+12 | 0.204777E+11 | 0.00 | 0.139992E+12 | 0.149823E+11 |
March | 0.330675E+12 | 0.182962E+11 | 0.00 | 0.161640E+12 | 0.910607E+10 |
April | 0.382953E+12 | 0.111188E+11 | 0.00 | 0.166937E+12 | 0.225666E+11 |
May | 0.432993E+12 | 0.621643E+10 | 0.00 | 0.197472E+12 | 0.508020E+11 |
June | 0.446384E+12 | 0.123099E+10 | 0.00 | 0.900767E+11 | 0.153439E+12 |
July | 0.448751E+12 | -599656606.3 | 0.00 | 0.229313E+11 | 0.212171E+12 |
August | 0.393195E+12 | 0.463222E+09 | 0.00 | 0.654349E+11 | 0.200126E+12 |
September | 0.283158E+12 | 0.523987E+10 | 0.00 | 0.161004E+12 | 0.807347E+11 |
October | 0.224542E+12 | 0.113537E+11 | 0.00 | 0.184503E+12 | 0.652649E+10 |
November | 0.145643E+12 | 0.167431E+11 | 0.00 | 0.150738E+12 | 0.799097E+10 |
December | 0.124304E+12 | 0.223828E+11 | 0.00 | 0.146117E+12 | 0.161219E+11 |
Annual Sum or Average | 0.365837E+13 | 0.139883E+12 | 0.00 | 0.163911E+13 | 0.796697E+12 |
Minimum of Months | 0.124304E+12 | -599656606.3 | 0.00 | 0.229313E+11 | 0.652649E+10 |
Maximum of Months | 0.448751E+12 | 0.269594E+11 | 0.00 | 0.197472E+12 | 0.212171E+12 |