Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29

Tabular Output Report in Format: HTML

Building: OfficeSmall

Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2023-10-16 08:29:54


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 206.18 403.36 403.36
Net Site Energy 206.18 403.36 403.36
Total Source Energy 652.96 1277.42 1277.42
Net Source Energy 652.96 1277.42 1277.42


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 511.16
Net Conditioned Building Area 511.16
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 38.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 42.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 20.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 27.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 23.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 206.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 38.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 42.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 20.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 27.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 23.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.16
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 38.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 42.88 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 20.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 52.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 27.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 23.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.31
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 124.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 175.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 103.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 403.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 124.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 175.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11
Other 103.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 403.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.11


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 206.176 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 206.176 100.00
     
Total On-Site and Utility Electric Sources 206.176 100.00
Total Electricity End Uses 206.176 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 58.31 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 58.31 100.00
Total Water End Uses 58.31 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 235.33
Time Not Comfortable Based on Simple ASHRAE 55-2004 831.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

| Environment |

ZoneCoolingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneHeatingSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ZoneElectricSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

SpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

PeakSpaceGainsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

SpaceGainComponentsAtCoolingPeakMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

ComfortReportSimple55Monthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

OccupantComfortDataSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

DXReportMonthly

| PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

WindowReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowEnergyReportMonthly

| PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR | PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 | PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |

WindowZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

WindowEnergyZoneSummaryMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_ZN_1_DAYLCTRL | PERIMETER_ZN_2_DAYLCTRL | PERIMETER_ZN_3_DAYLCTRL | PERIMETER_ZN_4_DAYLCTRL |

CoilReportMonthly

| PSZ-AC:1 HEATING COIL | PSZ-AC:2 HEATING COIL | PSZ-AC:3 HEATING COIL | PSZ-AC:4 HEATING COIL | PSZ-AC:5 HEATING COIL | PSZ-AC:1_SUPPHEATCOIL | PSZ-AC:2_SUPPHEATCOIL | PSZ-AC:3_SUPPHEATCOIL | PSZ-AC:4_SUPPHEATCOIL | PSZ-AC:5_SUPPHEATCOIL | PSZ-AC:1 HP COOLING COIL | PSZ-AC:2 HP COOLING COIL | PSZ-AC:3 HP COOLING COIL | PSZ-AC:4 HP COOLING COIL | PSZ-AC:5 HP COOLING COIL |

PlantLoopDemandReportMonthly

| SWHSYS1 |

FanReportMonthly

| PSZ-AC:1 FAN | PSZ-AC:2 FAN | PSZ-AC:3 FAN | PSZ-AC:4 FAN | PSZ-AC:5 FAN |

PumpReportMonthly

| SWHSYS1 PUMP |

CondLoopDemandReportMonthly

| SWHSYS1 |

ZoneTemperatureOscillationReportMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 | ATTIC |

AirLoopSystemEnergyAndWaterUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentLoadsMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

AirLoopSystemComponentEnergyUseMonthly

| PSZ-AC:1 | PSZ-AC:2 | PSZ-AC:3 | PSZ-AC:4 | PSZ-AC:5 |

MechanicalVentilationLoadsMonthly

| CORE_ZN | PERIMETER_ZN_1 | PERIMETER_ZN_2 | PERIMETER_ZN_3 | PERIMETER_ZN_4 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:29
RunPeriod RUNPERIOD 1
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Above Ground Wall Area [m2] 281.51 84.45 56.30 84.45 56.30
Window Opening Area [m2] 59.65 16.72 11.15 20.63 11.15
Gross Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80
Above Ground Window-Wall Ratio [%] 21.19 19.80 19.80 24.43 19.80


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 598.76
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
CORE_ZN 149.66 Yes Yes 456.46 1.00 0.00 0.00 0.00 0.00 9.0375 18.58 6.7800
PERIMETER_ZN_1 113.45 Yes Yes 346.02 1.00 84.45 0.00 20.63 20.63 9.0375 18.58 6.7800
PERIMETER_ZN_2 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 9.0375 18.58 6.7800
PERIMETER_ZN_3 113.45 Yes Yes 346.02 1.00 84.45 0.00 16.72 16.72 9.0375 18.58 6.7800
PERIMETER_ZN_4 67.30 Yes Yes 205.26 1.00 56.30 0.00 11.15 11.15 9.0375 18.58 6.7800
ATTIC 567.98 No No 720.19 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
Total 511.16     1559.03   281.51 0.00 59.65 59.65 9.0375 18.58 6.7800
Conditioned Total 511.16     1559.03   281.51 0.00 59.65 59.65 9.0375 18.58 6.7800
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 567.98     720.19   0.00 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
CORE_ZN 149.66 Yes Yes 1.00 CORE_ZN GENERAL CORE_ZN 9.0375 18.58 6.7800  
PERIMETER_ZN_1 113.45 Yes Yes 1.00 PERIMETER_ZN_1 GENERAL PERIMETER_ZN_1 9.0375 18.58 6.7800  
PERIMETER_ZN_2 67.30 Yes Yes 1.00 PERIMETER_ZN_2 GENERAL PERIMETER_ZN_2 9.0375 18.58 6.7800  
PERIMETER_ZN_3 113.45 Yes Yes 1.00 PERIMETER_ZN_3 GENERAL PERIMETER_ZN_3 9.0375 18.58 6.7800  
PERIMETER_ZN_4 67.30 Yes Yes 1.00 PERIMETER_ZN_4 GENERAL PERIMETER_ZN_4 9.0375 18.58 6.7800  
ATTIC 567.98 No No 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
Total 511.16             9.0375 9.29 6.7800  
Conditioned Total 511.16             9.0375 9.29 6.7800  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 567.98             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 511.16 511.16 0.00 567.98 9.0375 18.58 6.7800
Total 511.16 511.16 0.00 567.98      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 28-JUN-15:39 27-MAR-06:10 - - - - - - - - - - 02-JAN-12:09
Heating 0.00 2200.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 8851.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2821.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2312.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 2721.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 20172.61 2200.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 2200.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 8851.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2821.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2312.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 2721.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 122.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 135.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 167.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 87.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 74.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 652.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 1.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 239.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 265.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 128.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 327.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 170.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 145.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1277.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 1.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 239.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 265.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 128.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 327.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 170.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 145.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1277.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
CORE_ZN DIRECT AIR 0.375212
PERIMETER_ZN_1 DIRECT AIR 0.475200
PERIMETER_ZN_2 DIRECT AIR 0.341223
PERIMETER_ZN_3 DIRECT AIR 0.473239
PERIMETER_ZN_4 DIRECT AIR 0.399650
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
PSZ-AC:1 0.375212 0.375212 0.375212 0.375212 0.375212 0.375212 1.00 1.000000 0.375212
PSZ-AC:2 0.475200 0.475200 0.475200 0.475200 0.475200 0.475200 1.00 1.00 0.475200
PSZ-AC:3 0.341223 0.341223 0.341223 0.341223 0.341223 0.341223 1.00 1.00 0.341223
PSZ-AC:4 0.473239 0.473239 0.473239 0.473239 0.473239 0.473239 1.00 1.000000 0.473239
PSZ-AC:5 0.399650 0.399650 0.399650 0.399650 0.399650 0.399650 1.00 1.00 0.399650
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
PSZ-AC:1_OA_CONTROLLER 0.375212 0.064622
PSZ-AC:2_OA_CONTROLLER 0.475200 0.048988
PSZ-AC:3_OA_CONTROLLER 0.341223 0.029060
PSZ-AC:4_OA_CONTROLLER 0.473239 0.048988
PSZ-AC:5_OA_CONTROLLER 0.399650 0.029060
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Total Cooling Capacity [W] Design Size Gross Rated Sensible Heat Ratio
PSZ-AC:1 HP COOLING COIL 0.375212 6839.78 0.800861
PSZ-AC:2 HP COOLING COIL 0.475200 8243.41 0.800834
PSZ-AC:3 HP COOLING COIL 0.341223 5648.45 0.800655
PSZ-AC:4 HP COOLING COIL 0.473239 8212.91 0.800684
PSZ-AC:5 HP COOLING COIL 0.399650 6615.63 0.800655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Maximum Supply Air Temperature from Supplemental Heater [C] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
PSZ-AC:1_UNITARY_PACKAGE_DX 0.375212 0.375212 0.375212 0.375212 6839.78 6839.78 40.00 2804.01 1.00
PSZ-AC:2_UNITARY_PACKAGE_DX 0.475200 0.475200 0.475200 0.475200 8243.41 8243.41 40.00 3998.47 1.00
PSZ-AC:3_UNITARY_PACKAGE_DX 0.341223 0.341223 0.341223 0.341223 5648.45 5648.45 40.00 2479.02 1.00
PSZ-AC:4_UNITARY_PACKAGE_DX 0.473239 0.473239 0.473239 0.473239 8212.91 8212.91 40.00 3953.66 1.00
PSZ-AC:5_UNITARY_PACKAGE_DX 0.399650 0.399650 0.399650 0.399650 6615.63 6615.63 40.00 2467.68 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
PSZ-AC:1 FAN 0.375212
PSZ-AC:2 FAN 0.475200
PSZ-AC:3 FAN 0.341223
PSZ-AC:4 FAN 0.473239
PSZ-AC:5 FAN 0.399650
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [m3/s] Design Size Gross Rated Heating Capacity [W]
PSZ-AC:1 HEATING COIL 0.375212 6839.78
PSZ-AC:2 HEATING COIL 0.475200 8243.41
PSZ-AC:3 HEATING COIL 0.341223 5648.45
PSZ-AC:4 HEATING COIL 0.473239 8212.91
PSZ-AC:5 HEATING COIL 0.399650 6615.63
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [W]
PSZ-AC:1_SUPPHEATCOIL 2804.01
PSZ-AC:2_SUPPHEATCOIL 3998.47
PSZ-AC:3_SUPPHEATCOIL 2479.02
PSZ-AC:4_SUPPHEATCOIL 3953.66
PSZ-AC:5_SUPPHEATCOIL 2467.68
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000004 0.000486
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
SWHSYS1 PUMP 0.000004 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST |
PERIMETER_ZN_2_WALL_EAST ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_3_WALL_NORTH ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_EAST | ATTIC_SOFFIT_NORTH |
PERIMETER_ZN_4_WALL_WEST ATTIC_SOFFIT_WEST | ATTIC_SOFFIT_SOUTH | ATTIC_SOFFIT_NORTH |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_ZN_1_WALL_SOUTH PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 | PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 | PERIMETER_ZN_1_WALL_SOUTH_DOOR |
PERIMETER_ZN_2_WALL_EAST PERIMETER_ZN_2_WALL_EAST_WINDOW_4 | PERIMETER_ZN_2_WALL_EAST_WINDOW_3 | PERIMETER_ZN_2_WALL_EAST_WINDOW_2 | PERIMETER_ZN_2_WALL_EAST_WINDOW_1 |
PERIMETER_ZN_3_WALL_NORTH PERIMETER_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 | PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 |
PERIMETER_ZN_4_WALL_WEST PERIMETER_ZN_4_WALL_WEST_WINDOW_4 | PERIMETER_ZN_4_WALL_WEST_WINDOW_3 | PERIMETER_ZN_4_WALL_WEST_WINDOW_2 | PERIMETER_ZN_4_WALL_WEST_WINDOW_1 |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Version

Version ID
1 22.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 20.90 15.40 11.90 14.80 12.70 15.40 23.30 26.30 31.20 30.40 29.80 27.80


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 32.17 -110.88 -7.00 809.00 91976 1.0932


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.66 19.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeSmall 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 6 71 23


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CORE_ZN 0.0 0.00 0.00 0.00 13.85 9.23 1.53 1 1 1 5.00 22.69 5.00 13.46 0.00 3.05 3.05 456.46 TARP TARP 149.66 0.00 0.00 0.00 6 0 0 Yes
2 PERIMETER_ZN_1 0.0 0.00 0.00 0.00 13.85 2.21 1.53 1 1 1 0.00 27.69 0.00 5.00 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.82 20.63 6 7 0 Yes
3 PERIMETER_ZN_2 0.0 0.00 0.00 0.00 25.64 9.23 1.53 1 1 1 22.69 27.69 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
4 PERIMETER_ZN_3 0.0 0.00 0.00 0.00 13.85 16.25 1.53 1 1 1 0.00 27.69 13.46 18.46 0.00 3.05 3.05 346.02 TARP TARP 113.45 84.45 63.83 16.72 6 8 0 Yes
5 PERIMETER_ZN_4 0.0 0.00 0.00 0.00 2.05 9.23 1.53 1 1 1 0.00 5.00 0.00 18.46 0.00 3.05 3.05 205.27 TARP TARP 67.30 56.30 45.15 11.15 6 4 0 Yes
6 ATTIC 0.0 0.00 0.00 0.00 13.85 9.23 3.70 1 1 1 -0.60 28.29 -0.60 19.06 3.05 6.33 1.64 720.19 TARP TARP 567.98 0.00 0.00 0.00 13 0 0 No


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 CORE_ZN 149.66 8.1 18.581 5.382E-002 9.038 6.780 0.000 0.000 0.000 0.000 15.818 No
2 PERIMETER_ZN_1 113.45 6.1 18.581 5.382E-002 9.038 6.780 0.000 0.000 0.000 0.000 15.818 No
3 PERIMETER_ZN_2 67.30 3.6 18.581 5.382E-002 9.038 6.780 0.000 0.000 0.000 0.000 15.818 No
4 PERIMETER_ZN_3 113.45 6.1 18.581 5.382E-002 9.038 6.780 0.000 0.000 0.000 0.000 15.818 No
5 PERIMETER_ZN_4 67.30 3.6 18.581 5.382E-002 9.038 6.780 0.000 0.000 0.000 0.000 15.818 No
6 ATTIC 567.98 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 CORE_ZN BLDG_OCC_SCH_WO_SB CORE_ZN 149.66 8.1 8.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 8
2 PERIMETER_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_1 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
3 PERIMETER_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_ZN_2 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4
4 PERIMETER_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_3 113.45 6.1 6.1 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 6
5 PERIMETER_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_ZN_4 67.30 3.6 3.6 5.382E-002 18.581 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 4


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 CORE_ZN_LIGHTS LTG_SCH_OFFICE CORE_ZN 149.66 8.1 1352.531 9.038 167.923 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1352.531
2 PERIMETER_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_1 113.45 6.1 1025.306 9.038 167.923 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1025.306
3 PERIMETER_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_2 67.30 3.6 608.225 9.038 167.923 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 608.225
4 PERIMETER_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_3 113.45 6.1 1025.306 9.038 167.923 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1025.306
5 PERIMETER_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_ZN_4 67.30 3.6 608.225 9.038 167.923 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 608.225


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 CORE_ZN_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_ZN 149.66 8.1 1014.677 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 1014.677
2 PERIMETER_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_1 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
3 PERIMETER_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_2 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294
4 PERIMETER_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_3 113.45 6.1 769.191 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 769.191
5 PERIMETER_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_ZN_4 67.30 3.6 456.294 6.780 125.977 0.000 0.000 0.000 1.000 MiscPlug 0.000 456.294


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_ZN_1 7 0
2 PERIMETER_ZN_2 4 0
3 PERIMETER_ZN_3 6 0
4 PERIMETER_ZN_4 4 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_ZN_1 0  
2 PERIMETER_ZN_2 0  
3 PERIMETER_ZN_3 0  
4 PERIMETER_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 0.1514 11722.8 0.981 0.4606


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_ZN_1_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_1 113.45 6.1 8.659E-002 7.632E-004 1.025E-003 0.901 0.000 0.000 0.224 0.000
2 PERIMETER_ZN_1_DOOR_INFILTRATION INFIL_DOOR_OPENING_SCH PERIMETER_ZN_1 113.45 6.1 0.130 1.144E-003 1.537E-003 1.350 1.000 0.000 0.000 0.000
3 PERIMETER_ZN_2_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_2 67.30 3.6 5.772E-002 8.577E-004 1.025E-003 1.012 0.000 0.000 0.224 0.000
4 PERIMETER_ZN_3_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_3 113.45 6.1 8.659E-002 7.632E-004 9.800E-004 0.901 0.000 0.000 0.224 0.000
5 PERIMETER_ZN_4_INFILTRATION INFIL_QUARTER_ON_SCH PERIMETER_ZN_4 67.30 3.6 5.772E-002 8.577E-004 1.025E-003 1.012 0.000 0.000 0.224 0.000
6 ATTIC_INFILTRATION ALWAYS_ON ATTIC 567.98 0.0 0.200 3.523E-004 3.052E-004 1.000 1.000 0.000 0.000 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CORE_ZN Mixing/Well-Stirred
2 PERIMETER_ZN_1 Mixing/Well-Stirred
3 PERIMETER_ZN_2 Mixing/Well-Stirred
4 PERIMETER_ZN_3 Mixing/Well-Stirred
5 PERIMETER_ZN_4 Mixing/Well-Stirred
6 ATTIC Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.2000
2 Zone CORE_ZN 1.2000
3 Zone PERIMETER_ZN_1 1.2000
4 Zone PERIMETER_ZN_2 1.2000
5 Zone PERIMETER_ZN_3 1.2000
6 Zone PERIMETER_ZN_4 1.2000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.1137E-003
2 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.2367E-003
3 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 1.1972E-003
4 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 1.3064E-003
5 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 8.0846E-004
6 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 9.0105E-004
7 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT1 3.9490E-004
8 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 PERIMETER_ZN_1_DAYLREFPT2 4.4114E-004
9 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 6.4949E-003
10 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 5.8564E-003
11 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 6.3827E-003
12 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 6.0605E-003
13 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 6.3012E-003
14 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 4.3709E-003
15 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT1 3.3709E-003
16 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 PERIMETER_ZN_1_DAYLREFPT2 1.8142E-003
17 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 6.5804E-003
18 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 6.5610E-003
19 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 6.6909E-003
20 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 7.0182E-003
21 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 5.8881E-003
22 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 4.4264E-003
23 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT1 2.8006E-003
24 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 PERIMETER_ZN_1_DAYLREFPT2 1.6773E-003
25 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.1141E-003
26 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.2495E-003
27 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 1.1991E-003
28 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 1.3244E-003
29 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 8.0923E-004
30 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 9.0596E-004
31 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT1 3.9164E-004
32 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 PERIMETER_ZN_1_DAYLREFPT2 4.3398E-004
33 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.0627E-003
34 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.0771E-003
35 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 1.1542E-003
36 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 1.1669E-003
37 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 7.6889E-004
38 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 7.7883E-004
39 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT1 3.6914E-004
40 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 PERIMETER_ZN_1_DAYLREFPT2 3.7405E-004
41 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.0590E-003
42 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.0618E-003
43 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 1.1510E-003
44 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 1.1534E-003
45 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 7.6628E-004
46 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 7.6814E-004
47 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT1 3.6767E-004
48 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 PERIMETER_ZN_1_DAYLREFPT2 3.6863E-004
49 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.7019E-003
50 Clear Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.0749E-003
51 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.7969E-003
52 Clear Turbid Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 2.1677E-003
53 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 1.2633E-003
54 Intermediate Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 1.4966E-003
55 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT1 6.2630E-004
56 Overcast Sky 12/21 PERIMETER_ZN_1_DAYLCTRL PERIMETER_ZN_1 PERIMETER_ZN_1_WALL_SOUTH_DOOR PERIMETER_ZN_1_DAYLREFPT2 7.0214E-004
57 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 8.7445E-004
58 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 9.6751E-004
59 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 8.0894E-004
60 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 8.7786E-004
61 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 7.5183E-004
62 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 7.8563E-004
63 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT1 6.1908E-004
64 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_4 PERIMETER_ZN_2_DAYLREFPT2 6.6168E-004
65 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.3282E-003
66 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.6205E-003
67 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.6932E-003
68 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 2.1789E-003
69 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 2.4296E-003
70 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.9553E-003
71 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT1 3.0319E-003
72 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_3 PERIMETER_ZN_2_DAYLREFPT2 1.9280E-003
73 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 9.5502E-003
74 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 4.4265E-003
75 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 1.0016E-002
76 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 4.2277E-003
77 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 7.9264E-003
78 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 3.8175E-003
79 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT1 3.6144E-003
80 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_2 PERIMETER_ZN_2_DAYLREFPT2 2.0693E-003
81 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 1.0114E-003
82 Clear Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.2670E-003
83 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 9.7867E-004
84 Clear Turbid Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 1.2448E-003
85 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 8.2612E-004
86 Intermediate Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 9.6796E-004
87 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT1 6.2223E-004
88 Overcast Sky 12/21 PERIMETER_ZN_2_DAYLCTRL PERIMETER_ZN_2 PERIMETER_ZN_2_WALL_EAST_WINDOW_1 PERIMETER_ZN_2_DAYLREFPT2 6.6881E-004
89 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 4.2332E-004
90 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 5.0300E-004
91 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.4144E-004
92 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.0344E-004
93 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 2.8433E-004
94 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 3.2685E-004
95 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT1 3.9068E-004
96 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 PERIMETER_ZN_3_DAYLREFPT2 4.3116E-004
97 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.6224E-003
98 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 2.1601E-003
99 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.0699E-003
100 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.6515E-003
101 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.0277E-003
102 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.1813E-003
103 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT1 2.5564E-003
104 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 PERIMETER_ZN_3_DAYLREFPT2 1.6125E-003
105 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.6469E-003
106 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 2.5808E-003
107 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.8128E-003
108 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.9386E-003
109 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 2.4960E-003
110 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.2443E-003
111 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT1 3.7002E-003
112 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 PERIMETER_ZN_3_DAYLREFPT2 1.8862E-003
113 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 4.3335E-004
114 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 5.3116E-004
115 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.4846E-004
116 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.2265E-004
117 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 2.8732E-004
118 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 3.3068E-004
119 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT1 3.9723E-004
120 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 PERIMETER_ZN_3_DAYLREFPT2 4.4551E-004
121 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.8508E-004
122 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.9740E-004
123 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.1033E-004
124 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.1990E-004
125 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 2.5741E-004
126 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 2.6352E-004
127 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT1 3.6983E-004
128 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 PERIMETER_ZN_3_DAYLREFPT2 3.7529E-004
129 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.8148E-004
130 Clear Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.8396E-004
131 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.0746E-004
132 Clear Turbid Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.0941E-004
133 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 2.5533E-004
134 Intermediate Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 2.5661E-004
135 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT1 3.6816E-004
136 Overcast Sky 12/21 PERIMETER_ZN_3_DAYLCTRL PERIMETER_ZN_3 PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 PERIMETER_ZN_3_DAYLREFPT2 3.6920E-004
137 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 8.9674E-004
138 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.0867E-003
139 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 8.3559E-004
140 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 1.0212E-003
141 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 7.4407E-004
142 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 8.6695E-004
143 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT1 6.2325E-004
144 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_4 PERIMETER_ZN_4_DAYLREFPT2 6.6949E-004
145 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 7.2130E-003
146 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.5824E-003
147 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 7.1352E-003
148 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.2540E-003
149 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 6.7742E-003
150 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 3.2592E-003
151 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT1 3.5992E-003
152 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_3 PERIMETER_ZN_4_DAYLREFPT2 2.0426E-003
153 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.3166E-003
154 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.5476E-003
155 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.6116E-003
156 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 2.0510E-003
157 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 2.1998E-003
158 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.7185E-003
159 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT1 3.0289E-003
160 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_2 PERIMETER_ZN_4_DAYLREFPT2 1.9056E-003
161 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 7.8631E-004
162 Clear Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 8.8301E-004
163 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.9873E-004
164 Clear Turbid Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.6932E-004
165 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.7284E-004
166 Intermediate Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 7.0340E-004
167 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT1 6.1999E-004
168 Overcast Sky 12/21 PERIMETER_ZN_4_DAYLCTRL PERIMETER_ZN_4 PERIMETER_ZN_4_WALL_WEST_WINDOW_1 PERIMETER_ZN_4_DAYLREFPT2 6.6233E-004


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 CORE_ZN Cooling 3868.78244 4642.53893 0.31268 0.37521 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 39.64733 5.62931E-003 149.65740 8.05449 6.46221E-002 0.00000
2 CORE_ZN Heating 812.16764 974.60116 3.85691E-002 6.46221E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 149.65740 8.05449 6.46221E-002 0.00000
3 PERIMETER_ZN_1 Cooling 4899.88750 5879.86500 0.39600 0.47520 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 40.13500 5.63007E-003 113.45000 6.10582 4.89877E-002 0.00000
4 PERIMETER_ZN_1 Heating 2443.43046 2932.11656 0.11603 0.13924 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 113.45000 6.10582 4.89877E-002 0.00000
5 PERIMETER_ZN_2 Cooling 3518.47117 4222.16541 0.28435 0.34122 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 37.40850 5.62583E-003 67.30000 3.62205 2.90601E-002 0.00000
6 PERIMETER_ZN_2 Heating 1540.02687 1848.03225 7.31317E-002 8.77581E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 67.30000 3.62205 2.90601E-002 0.00000
7 PERIMETER_ZN_3 Cooling 4879.67267 5855.60720 0.39437 0.47324 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 40.13500 5.63007E-003 113.45000 6.10582 4.89877E-002 0.00000
8 PERIMETER_ZN_3 Heating 2405.54471 2886.65365 0.11423 0.13708 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 113.45000 6.10582 4.89877E-002 0.00000
9 PERIMETER_ZN_4 Cooling 4120.92333 4945.10800 0.33304 0.39965 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 38.05133 5.62683E-003 67.30000 3.62205 2.90601E-002 0.00000
10 PERIMETER_ZN_4 Heating 1530.44171 1836.53005 7.26766E-002 8.72119E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50000 4.31558E-003 67.30000 3.62205 2.90601E-002 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 PSZ-AC:1 Cooling Sensible 5689.37 0.37521 0.37521 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 PSZ-AC:1 Heating Sensible 2804.01 6.46221E-002 6.46221E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00
3 PSZ-AC:2 Cooling Sensible 6663.15 0.47520 0.47520 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 PSZ-AC:2 Heating Sensible 3998.47 0.13924 0.13924 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
5 PSZ-AC:3 Cooling Sensible 4588.43 0.34122 0.34122 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 PSZ-AC:3 Heating Sensible 2479.02 8.77581E-002 8.77581E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
7 PSZ-AC:4 Cooling Sensible 6639.27 0.47324 0.47324 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 PSZ-AC:4 Heating Sensible 3953.66 0.13708 0.13708 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
9 PSZ-AC:5 Cooling Sensible 5320.71 0.39965 0.39965 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 PSZ-AC:5 Heating Sensible 2467.68 8.72119E-002 8.72119E-002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat CORE_ZN DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.37521
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_1 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.47520
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_2 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.34122
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_3 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.47324
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat PERIMETER_ZN_4 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.39965
6 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.37521
7 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.37521
8 AirLoopHVAC PSZ-AC:1 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.37521
9 AirLoopHVAC PSZ-AC:1 Adjusted Heating Design Air Flow Rate [m3/s] 0.37521
10 AirLoopHVAC PSZ-AC:1 Adjusted Cooling Design Air Flow Rate [m3/s] 0.37521
11 AirLoopHVAC PSZ-AC:1 Adjusted Main Design Air Flow Rate [m3/s] 0.37521
12 AirLoopHVAC PSZ-AC:1 User Heating Air Flow Ratio [] 1.00000
13 AirLoopHVAC PSZ-AC:1 Calculated Heating Air Flow Ratio [] 1.00000
14 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.47520
15 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.47520
16 AirLoopHVAC PSZ-AC:2 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.47520
17 AirLoopHVAC PSZ-AC:2 Adjusted Heating Design Air Flow Rate [m3/s] 0.47520
18 AirLoopHVAC PSZ-AC:2 Adjusted Cooling Design Air Flow Rate [m3/s] 0.47520
19 AirLoopHVAC PSZ-AC:2 Adjusted Main Design Air Flow Rate [m3/s] 0.47520
20 AirLoopHVAC PSZ-AC:2 User Heating Air Flow Ratio [] 1.00000
21 AirLoopHVAC PSZ-AC:2 Calculated Heating Air Flow Ratio [] 1.00000
22 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.34122
23 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.34122
24 AirLoopHVAC PSZ-AC:3 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.34122
25 AirLoopHVAC PSZ-AC:3 Adjusted Heating Design Air Flow Rate [m3/s] 0.34122
26 AirLoopHVAC PSZ-AC:3 Adjusted Cooling Design Air Flow Rate [m3/s] 0.34122
27 AirLoopHVAC PSZ-AC:3 Adjusted Main Design Air Flow Rate [m3/s] 0.34122
28 AirLoopHVAC PSZ-AC:3 User Heating Air Flow Ratio [] 1.00000
29 AirLoopHVAC PSZ-AC:3 Calculated Heating Air Flow Ratio [] 1.00000
30 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.47324
31 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.47324
32 AirLoopHVAC PSZ-AC:4 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.47324
33 AirLoopHVAC PSZ-AC:4 Adjusted Heating Design Air Flow Rate [m3/s] 0.47324
34 AirLoopHVAC PSZ-AC:4 Adjusted Cooling Design Air Flow Rate [m3/s] 0.47324
35 AirLoopHVAC PSZ-AC:4 Adjusted Main Design Air Flow Rate [m3/s] 0.47324
36 AirLoopHVAC PSZ-AC:4 User Heating Air Flow Ratio [] 1.00000
37 AirLoopHVAC PSZ-AC:4 Calculated Heating Air Flow Ratio [] 1.00000
38 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.39965
39 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.39965
40 AirLoopHVAC PSZ-AC:5 Sum of Air Terminal Maximum Flow Rates [m3/s] 0.39965
41 AirLoopHVAC PSZ-AC:5 Adjusted Heating Design Air Flow Rate [m3/s] 0.39965
42 AirLoopHVAC PSZ-AC:5 Adjusted Cooling Design Air Flow Rate [m3/s] 0.39965
43 AirLoopHVAC PSZ-AC:5 Adjusted Main Design Air Flow Rate [m3/s] 0.39965
44 AirLoopHVAC PSZ-AC:5 User Heating Air Flow Ratio [] 1.00000
45 AirLoopHVAC PSZ-AC:5 Calculated Heating Air Flow Ratio [] 1.00000
46 AirLoopHVAC PSZ-AC:1 Design Supply Air Flow Rate [m3/s] 0.37521
47 AirLoopHVAC PSZ-AC:2 Design Supply Air Flow Rate [m3/s] 0.47520
48 AirLoopHVAC PSZ-AC:3 Design Supply Air Flow Rate [m3/s] 0.34122
49 AirLoopHVAC PSZ-AC:4 Design Supply Air Flow Rate [m3/s] 0.47324
50 AirLoopHVAC PSZ-AC:5 Design Supply Air Flow Rate [m3/s] 0.39965
51 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.37521
52 Controller:OutdoorAir PSZ-AC:1_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 6.46221E-002
53 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.37521
54 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6839.78039
55 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80086
56 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.37521
57 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.37521
58 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.37521
59 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.37521
60 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6839.78039
61 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6839.78039
62 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
63 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2804.01417
64 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:1_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
65 Fan:OnOff PSZ-AC:1 FAN Design Size Maximum Flow Rate [m3/s] 0.37521
66 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.37521
67 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6839.78039
68 Coil:Heating:Fuel PSZ-AC:1_SUPPHEATCOIL Design Size Nominal Capacity [W] 2804.01417
69 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.47520
70 Controller:OutdoorAir PSZ-AC:2_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
71 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.47520
72 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 8243.40582
73 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80083
74 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.47520
75 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.47520
76 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.47520
77 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.47520
78 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 8243.40582
79 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 8243.40582
80 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
81 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3998.46532
82 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:2_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
83 Fan:OnOff PSZ-AC:2 FAN Design Size Maximum Flow Rate [m3/s] 0.47520
84 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.47520
85 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL Design Size Gross Rated Heating Capacity [W] 8243.40582
86 Coil:Heating:Fuel PSZ-AC:2_SUPPHEATCOIL Design Size Nominal Capacity [W] 3998.46532
87 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.34122
88 Controller:OutdoorAir PSZ-AC:3_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
89 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.34122
90 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 5648.45467
91 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
92 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.34122
93 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.34122
94 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.34122
95 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.34122
96 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 5648.45467
97 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 5648.45467
98 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
99 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2479.01944
100 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:3_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
101 Fan:OnOff PSZ-AC:3 FAN Design Size Maximum Flow Rate [m3/s] 0.34122
102 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.34122
103 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL Design Size Gross Rated Heating Capacity [W] 5648.45467
104 Coil:Heating:Fuel PSZ-AC:3_SUPPHEATCOIL Design Size Nominal Capacity [W] 2479.01944
105 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.47324
106 Controller:OutdoorAir PSZ-AC:4_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 4.89877E-002
107 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.47324
108 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 8212.91029
109 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80068
110 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.47324
111 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.47324
112 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.47324
113 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.47324
114 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 8212.91029
115 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 8212.91029
116 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
117 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 3953.66463
118 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:4_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
119 Fan:OnOff PSZ-AC:4 FAN Design Size Maximum Flow Rate [m3/s] 0.47324
120 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.47324
121 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL Design Size Gross Rated Heating Capacity [W] 8212.91029
122 Coil:Heating:Fuel PSZ-AC:4_SUPPHEATCOIL Design Size Nominal Capacity [W] 3953.66463
123 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.39965
124 Controller:OutdoorAir PSZ-AC:5_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 2.90601E-002
125 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.39965
126 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Total Cooling Capacity [W] 6615.62646
127 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL Design Size Gross Rated Sensible Heat Ratio 0.80066
128 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate [m3/s] 0.39965
129 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Heating Operation [m3/s] 0.39965
130 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate During Cooling Operation [m3/s] 0.39965
131 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.39965
132 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Heating Capacity [W] 6615.62646
133 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Nominal Cooling Capacity [W] 6615.62646
134 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Maximum Supply Air Temperature from Supplemental Heater [C] 40.00000
135 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Supplemental Heating Coil Nominal Capacity [W] 2467.68479
136 AirLoopHVAC:UnitaryHeatPump:AirToAir PSZ-AC:5_UNITARY_PACKAGE_DX Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
137 Fan:OnOff PSZ-AC:5 FAN Design Size Maximum Flow Rate [m3/s] 0.39965
138 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.39965
139 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL Design Size Gross Rated Heating Capacity [W] 6615.62646
140 Coil:Heating:Fuel PSZ-AC:5_SUPPHEATCOIL Design Size Nominal Capacity [W] 2467.68479
141 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.04800E-006
142 PlantLoop SWHSYS1 Plant Loop Volume [m3] 4.85760E-004
143 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.04800E-006
144 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 1.72991E-008


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {W} Standard Rated Net COP {W/W} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed PSZ-AC:1 HP COOLING COIL 6545.3 3.35 11.44 11.98 11.33 11.28
2 Coil:Cooling:DX:SingleSpeed PSZ-AC:2 HP COOLING COIL 7870.8 3.32 11.33 11.85 11.21 11.12
3 Coil:Cooling:DX:SingleSpeed PSZ-AC:3 HP COOLING COIL 5381.0 3.29 11.22 11.74 11.10 10.96
4 Coil:Cooling:DX:SingleSpeed PSZ-AC:4 HP COOLING COIL 7841.8 3.32 11.33 11.86 11.22 11.12
5 Coil:Cooling:DX:SingleSpeed PSZ-AC:5 HP COOLING COIL 6302.4 3.29 11.22 11.74 11.10 10.96


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {W} Low Temperature Heating (net) Rating Capacity {W} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed PSZ-AC:1 HEATING COIL 7138.2 3962.6 7.37 4
2 Coil:Heating:DX:SingleSpeed PSZ-AC:2 HEATING COIL 8620.9 4793.5 7.35 4
3 Coil:Heating:DX:SingleSpeed PSZ-AC:3 HEATING COIL 5919.2 3296.6 7.33 4
4 Coil:Heating:DX:SingleSpeed PSZ-AC:4 HEATING COIL 8588.8 4775.6 7.35 4
5 Coil:Heating:DX:SingleSpeed PSZ-AC:5 HEATING COIL 6932.7 3861.1 7.32 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CORE_ZN RunPeriod: RUNPERIOD 1 1.6653629106E-002 8.0137355579E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 PERIMETER_ZN_1 RunPeriod: RUNPERIOD 1 8.1005130289E-002 5.3214929041E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 PERIMETER_ZN_2 RunPeriod: RUNPERIOD 1 4.2711307539E-002 3.2655824299E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 PERIMETER_ZN_3 RunPeriod: RUNPERIOD 1 3.4477379592E-002 2.0323619841E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 PERIMETER_ZN_4 RunPeriod: RUNPERIOD 1 6.6215070943E-002 4.7530660144E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 ATTIC RunPeriod: RUNPERIOD 1 0.4967989686 0.4845969450 Pass Pass 0.0000000000 0.0000000000 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 1126.35 32.25 0.00 45.48 195.77 1399.86



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 0.50 0.00 0.50 Wetbulb [C] 2.10 140.00
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 40.80 13.30 18.50 Wetbulb [C] 4.80 310.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 3.00 2      
Feb 34.00 28      
Mar 40.00 18      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 81.00 18      
Aug 71.00 20      
Sep 27.00 12      
Oct 9.00 6      
Nov 35.00 14      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.82 180.00 90.00 S
PERIMETER_ZN_1_FLOOR PERIMETER_ZN_1_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 135.00 180.00  
PERIMETER_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 90.00 90.00 E
PERIMETER_ZN_2_FLOOR PERIMETER_ZN_2_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 270.00 180.00  
PERIMETER_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.977 1.144 84.45 63.83 0.00 90.00 N
PERIMETER_ZN_3_FLOOR PERIMETER_ZN_3_FLOOR_FFACTOR 1.00 0.308 0.324 113.45 113.45 180.00 180.00  
PERIMETER_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.977 1.144 56.30 45.15 270.00 90.00 W
PERIMETER_ZN_4_FLOOR PERIMETER_ZN_4_FLOOR_FFACTOR 1.00 0.346 0.366 67.30 67.30 90.00 180.00  
ATTIC_SOFFIT_WEST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 270.00 180.00  
ATTIC_SOFFIT_SOUTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 225.00 180.00  
ATTIC_SOFFIT_EAST EXT_SOFFIT_FLOOR 0.30 3.082 7.547 11.44 11.44 45.00 180.00  
ATTIC_SOFFIT_NORTH EXT_SOFFIT_FLOOR 0.30 3.082 7.547 16.97 16.97 315.00 180.00  
ATTIC_ROOF_NORTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 0.00 18.45  
ATTIC_ROOF_WEST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 270.00 18.45  
ATTIC_ROOF_EAST ATTICROOFDECK 0.30 2.858 4.706 101.87 101.87 90.00 18.45  
ATTIC_ROOF_SOUTH ATTICROOFDECK 0.30 2.858 4.706 197.51 197.51 180.00 18.45  


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
CORE_ZN_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
CORE_ZN_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
CORE_ZN_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
CORE_ZN_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
CORE_ZN_FLOOR CORE_ZN_FLOOR_FFACTOR 1.00 0.006 0.006 149.66 149.66 270.00 180.00  
CORE_ZN_CEILING NONRES_ROOF 0.30 0.151 0.158 149.66 149.66 270.00 0.00  
PERIMETER_ZN_1_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_1_WALL_NORTH INT_WALL 0.30 2.511 6.299 53.95 53.95 0.00 90.00 N
PERIMETER_ZN_1_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 45.00 0.00  
PERIMETER_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 315.00 90.00 N
PERIMETER_ZN_2_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_2_WALL_WEST INT_WALL 0.30 2.511 6.299 25.80 25.80 270.00 90.00 W
PERIMETER_ZN_2_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 270.00 0.00  
PERIMETER_ZN_3_WALL_SOUTH INT_WALL 0.30 2.511 6.299 53.95 53.95 180.00 90.00 S
PERIMETER_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 21.57 21.57 225.00 90.00 W
PERIMETER_ZN_3_WALL_EAST INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_3_CEILING NONRES_ROOF 0.30 0.151 0.158 113.45 113.45 180.00 0.00  
PERIMETER_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 21.57 21.57 135.00 90.00 S
PERIMETER_ZN_4_WALL_NORTH INT_WALL 0.30 2.511 6.299 21.57 21.57 45.00 90.00 E
PERIMETER_ZN_4_WALL_EAST INT_WALL 0.30 2.511 6.299 25.80 25.80 90.00 90.00 E
PERIMETER_ZN_4_CEILING NONRES_ROOF 0.30 0.151 0.158 67.30 67.30 90.00 0.00  
ATTIC_FLOOR_PERIMETER_SOUTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 180.00 180.00  
ATTIC_FLOOR_PERIMETER_WEST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 315.00 180.00  
ATTIC_FLOOR_PERIMETER_EAST NONRES_ROOF_FLOOR 0.30 0.151 0.158 67.30 67.30 135.00 180.00  
ATTIC_FLOOR_CORE NONRES_ROOF_FLOOR 0.30 0.151 0.158 149.66 149.66 270.00 180.00  
ATTIC_FLOOR_PERIMETER_NORTH NONRES_ROOF_FLOOR 0.30 0.151 0.158 113.45 113.45 315.00 180.00  
CORE_ZN_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 299.31   0.00 90.00 N
PERIMETER_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N
PERIMETER_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 226.90   0.00 90.00 N
PERIMETER_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 134.60   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 WINDOW_U_0.5047_SHGC_SOUTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_1_WALL_SOUTH_DOOR WINDOW_U_0.5047_SHGC_SOUTH_0.25   3.91 0.00 0.00 3.91 3.91 2.869 0.251 0.251             No PERIMETER_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 WINDOW_U_0.5047_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 WINDOW_U_0.5047_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 WINDOW_U_0.5047_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 WINDOW_U_0.5047_SHGC_EAST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 WINDOW_U_0.5047_SHGC_NORTH_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 WINDOW_U_0.5047_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 WINDOW_U_0.5047_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 WINDOW_U_0.5047_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 WINDOW_U_0.5047_SHGC_WEST_0.25   2.79 0.00 0.00 2.79 2.79 2.869 0.251 0.251             No PERIMETER_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             59.65 2.869 0.251 0.251                      
North Total or Average             16.72 2.869 0.251 0.251                      
Non-North Total or Average             42.93 2.869 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_ZN_3_WALL_NORTH
PERIMETER_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_ZN_3_WALL_NORTH


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6 0.86 0.83 0.83 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_1_WALL_SOUTH_DOOR 1.00 1.00 1.00 0.00 0.00 0.00 1.00 1.00 1.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_4 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_3 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_2 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00
PERIMETER_ZN_2_WALL_EAST_WINDOW_1 1.00 0.00 0.00 1.00 0.00 0.00 1.00 0.15 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_1 0.00 0.00 0.00 0.05 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3_WALL_NORTH_WINDOW_6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_4 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_3 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_2 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00
PERIMETER_ZN_4_WALL_WEST_WINDOW_1 0.00 0.00 0.89 0.00 0.00 0.76 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
CORE_ZN_LIGHTS CORE_ZN CORE_ZN GENERAL 9.0375 149.66 1352.53 LightsWired LTG_SCH_OFFICE 54.48 168.00 53.53 0.0000 Y 13.59
PERIMETER_ZN_1_LIGHTS PERIMETER_ZN_1 PERIMETER_ZN_1 GENERAL 9.0375 113.45 1025.31 LightsWired LTG_SCH_OFFICE 54.48 168.00 46.15 0.0000 Y 8.88
PERIMETER_ZN_2_LIGHTS PERIMETER_ZN_2 PERIMETER_ZN_2 GENERAL 9.0375 67.30 608.22 LightsWired LTG_SCH_OFFICE 54.48 168.00 47.52 0.0000 Y 5.43
PERIMETER_ZN_3_LIGHTS PERIMETER_ZN_3 PERIMETER_ZN_3 GENERAL 9.0375 113.45 1025.31 LightsWired LTG_SCH_OFFICE 54.48 168.00 49.45 0.0000 Y 9.52
PERIMETER_ZN_4_LIGHTS PERIMETER_ZN_4 PERIMETER_ZN_4 GENERAL 9.0375 67.30 608.22 LightsWired LTG_SCH_OFFICE 54.48 168.00 47.84 0.0000 Y 5.46
Interior Lighting Total       9.0375 511.16 4619.59               42.88


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_ZN_1_DAYLREFPT1 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.24 1025.31 245.97
PERIMETER_ZN_1_DAYLREFPT2 PERIMETER_ZN_1 PERIMETER_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 1025.31 0.00
PERIMETER_ZN_2_DAYLREFPT1 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.24 608.22 145.91
PERIMETER_ZN_2_DAYLREFPT2 PERIMETER_ZN_2 PERIMETER_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 608.22 0.00
PERIMETER_ZN_3_DAYLREFPT1 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.24 1025.31 245.97
PERIMETER_ZN_3_DAYLREFPT2 PERIMETER_ZN_3 PERIMETER_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 1025.31 0.00
PERIMETER_ZN_4_DAYLREFPT1 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.24 608.22 145.91
PERIMETER_ZN_4_DAYLREFPT2 PERIMETER_ZN_4 PERIMETER_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 608.22 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 66.70 AstronomicalClock -   41.79 41.79 0.52
EXTERIOR_LIGHTS_B 1507.70 AstronomicalClock -   83.79 71.19 20.15
Exterior Lighting Total 1574.40           20.67



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6839.78 5477.72 1362.06 0.80 4.12    
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   8243.41 6601.60 1641.81 0.80 4.12    
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   5648.45 4522.46 1125.99 0.80 4.12    
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   8212.91 6575.94 1636.97 0.80 4.12    
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed   6615.63 5296.84 1318.79 0.80 4.12    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
PSZ-AC:1 HP COOLING COIL   6545.3 3.35 11.44 11.98 11.33 11.28
PSZ-AC:2 HP COOLING COIL   7870.8 3.32 11.33 11.85 11.21 11.12
PSZ-AC:3 HP COOLING COIL   5381.0 3.29 11.22 11.74 11.10 10.96
PSZ-AC:4 HP COOLING COIL   7841.8 3.32 11.33 11.86 11.22 11.12
PSZ-AC:5 HP COOLING COIL   6302.4 3.29 11.22 11.74 11.10 10.96
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed 7138.2 3962.6 7.37 4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed 8620.9 4793.5 7.35 4
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed 5919.2 3296.6 7.33 4
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed 8588.8 4775.6 7.35 4
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed 6932.7 3861.1 7.32 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed   6839.78 3.36
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel   2804.01 0.80
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed   8243.41 3.36
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel   3998.47 0.80
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed   5648.45 3.36
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel   2479.02 0.80
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed   8212.91 3.36
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel   3953.66 0.80
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed   6615.63 3.36
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel   2467.68 0.80
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
PSZ-AC:1 FAN Fan:OnOff 0.56 622.50 0.38 420.28 1120.11 1.00 1.75 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00
PSZ-AC:2 FAN Fan:OnOff 0.56 622.50 0.48 532.28 1120.11 1.00 1.63 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:3 FAN Fan:OnOff 0.56 622.50 0.34 382.21 1120.11 1.00 1.81 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00
PSZ-AC:4 FAN Fan:OnOff 0.56 622.50 0.47 530.08 1120.11 1.00 1.63 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00
PSZ-AC:5 FAN Fan:OnOff 0.56 622.50 0.40 447.65 1120.11 1.00 1.72 General TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 0.00 0.000004 0.00 0.00 0.30 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.15 11722.84 1.00 0.98 0.46



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 3868.78 4642.54 31.02 0.313 0.375 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 23.89 23.89 0.00896 39.65 0.00563 0.065 0.00
PERIMETER_ZN_1 4899.89 5879.87 51.83 0.396 0.475 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 23.89 23.89 0.00862 40.13 0.00563 0.049 0.00
PERIMETER_ZN_2 3518.47 4222.17 62.74 0.284 0.341 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 23.89 23.89 0.00858 37.41 0.00563 0.029 0.00
PERIMETER_ZN_3 4879.67 5855.61 51.61 0.394 0.473 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 23.89 23.89 0.00862 40.13 0.00563 0.049 0.00
PERIMETER_ZN_4 4120.92 4945.11 73.48 0.333 0.400 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 23.89 23.89 0.00857 38.05 0.00563 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
CORE_ZN 812.17 974.60 6.51 0.039 0.065 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00800 0.50 0.00432 0.065 0.00
PERIMETER_ZN_1 2443.43 2932.12 25.85 0.116 0.139 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00770 0.50 0.00432 0.049 0.00
PERIMETER_ZN_2 1540.03 1848.03 27.46 0.073 0.088 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00768 0.50 0.00432 0.029 0.00
PERIMETER_ZN_3 2405.54 2886.65 25.44 0.114 0.137 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00769 0.50 0.00432 0.049 0.00
PERIMETER_ZN_4 1530.44 1836.53 27.29 0.073 0.087 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 21.11 21.11 0.00768 0.50 0.00432 0.029 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
PSZ-AC:1 0.38 0.38 0.06 0.06 0.3752 0.3752 0.3752 1.0000 1.0000
PSZ-AC:2 0.48 0.48 0.14 0.14 0.4752 0.4752 0.4752 1.0000 1.0000
PSZ-AC:3 0.34 0.34 0.09 0.09 0.3412 0.3412 0.3412 1.0000 1.0000
PSZ-AC:4 0.47 0.47 0.14 0.14 0.4732 0.4732 0.4732 1.0000 1.0000
PSZ-AC:5 0.40 0.40 0.09 0.09 0.3996 0.3996 0.3996 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6839.780 5477.717 0.375212 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 5995.45 5995.45 0.375212 27.61 16.53 0.00838853 12.80 11.12 0.00838853 39.65 0.00562931 18.22 17.2228 23.89 0.00896673 44.0804 3840.02 0.00 6838.61 5209.22
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:1 6839.780 6839.780 0.375212 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 6839.78 6839.78 0.375212 17.56 12.02 0.00736544 40.00 20.06 0.00800000 0.50 0.00431558 0.50 17.2228 21.11 0.00800000 46.6350 811.45 0.00 6848.77 6848.77
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:1 2804.014 2804.014 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 2804.01 2804.01 0.375212 17.56 12.02 0.00736544 40.00 20.06 0.00800000 0.50 0.00431558 0.50 17.2228 21.11 0.00800000 46.6350 811.45 0.00 -999.00 -999.00
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 8243.406 6601.599 0.475200 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 7084.28 7084.28 0.475200 26.57 16.12 0.00831159 12.80 11.05 0.00831159 40.13 0.00563007 18.37 10.3089 23.89 0.00862006 42.3982 4891.41 0.00 8241.99 6276.90
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:2 8243.406 8243.406 0.475200 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 8243.41 8243.41 0.475200 18.98 12.56 0.00734724 40.00 20.06 0.00800000 0.50 0.00431558 0.50 10.3089 21.11 0.00769569 44.8844 2443.43 0.00 8254.24 8254.24
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:2 3998.465 3998.465 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3998.47 3998.47 0.475200 18.98 12.56 0.00734724 40.00 20.06 0.00800000 0.50 0.00431558 0.50 10.3089 21.11 0.00769569 44.8844 2443.43 0.00 -999.00 -999.00
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 5648.455 4522.465 0.341223 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 5007.65 5007.65 0.341223 26.05 15.96 0.00833103 12.80 11.07 0.00833103 37.41 0.00562583 17.52 8.5165 23.89 0.00858329 42.2195 3514.03 0.00 5647.49 4299.75
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:3 5648.455 5648.455 0.341223 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 5648.45 5648.45 0.341223 19.35 12.74 0.00739314 40.00 20.06 0.00800000 0.50 0.00431558 0.50 8.5165 21.11 0.00767964 44.7922 1540.03 0.00 5655.88 5655.88
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:3 2479.019 2479.019 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2479.02 2479.02 0.341223 19.35 12.74 0.00739314 40.00 20.06 0.00800000 0.50 0.00431558 0.50 8.5165 21.11 0.00767964 44.7922 1540.03 0.00 -999.00 -999.00
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 8212.910 6575.945 0.473239 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 7058.45 7058.45 0.473239 26.58 16.12 0.00831074 12.80 11.05 0.00831074 40.13 0.00563007 18.37 10.3516 23.89 0.00862051 42.4004 4872.53 0.00 8211.50 6252.62
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:4 8212.910 8212.910 0.473239 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 8212.91 8212.91 0.473239 18.98 12.55 0.00734186 40.00 20.06 0.00800000 0.50 0.00431558 0.50 10.3516 21.11 0.00769129 44.8591 2405.54 0.00 8223.70 8223.70
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:4 3953.665 3953.665 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 3953.66 3953.66 0.473239 18.98 12.55 0.00734186 40.00 20.06 0.00800000 0.50 0.00431558 0.50 10.3516 21.11 0.00769129 44.8591 2405.54 0.00 -999.00 -999.00
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 6615.626 5296.836 0.399650 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 5814.66 5814.66 0.399650 25.92 15.94 0.00835767 12.80 11.09 0.00835767 38.05 0.00562683 17.72 7.2714 23.89 0.00857183 42.1639 4115.01 0.00 6614.49 5035.99
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoopHVAC PSZ-AC:5 6615.626 6615.626 0.399650 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 6615.63 6615.63 0.399650 19.61 12.88 0.00743333 40.00 20.06 0.00800000 0.50 0.00431558 0.50 7.2714 21.11 0.00767781 44.7816 1530.44 0.00 6624.32 6624.32
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoopHVAC PSZ-AC:5 2467.685 2467.685 -999.0 -999.0 -999.000 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 2467.68 2467.68 0.399650 19.61 12.88 0.00743333 40.00 20.06 0.00800000 0.50 0.00431558 0.50 7.2714 21.11 0.00767781 44.7816 1530.44 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
PSZ-AC:1 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6839.780 5477.717 0.375212 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.4339 1004.8586 1.0932 PSZ-AC:1 FAN Fan:OnOff 0.375212 0.41017938   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 Sensible 5995.45 5995.45 0.8766 0.41017938 0.375212 27.61 16.53 0.00838853 49150.8 12.80 11.12 0.00838853 34040.8 -999.0 -999.00 -999.00 -999.00 420.278 5575.18 39.65 0.00562931 18.22 0.06462207 17.2228 23.89 0.00896262 23.89 0.00896673 44.0804 3840.02 0.00 6838.61 5209.22 0.39398039 26.67 19.44 0.01118466 55322.4 13.74 13.51 0.00956314 37964.7
PSZ-AC:1 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6839.780 6839.780 0.375212 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:1 FAN Fan:OnOff 0.375212 0.41017938   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 6839.78 6839.78 1.0000 0.41017938 0.375212 17.56 12.02 0.00736544 36306.3 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6839.78 0.50 0.00431558 0.50 0.06462207 17.2228 21.11 0.00800000 21.11 0.00800000 46.6350 811.45 0.00 6848.77 6848.77 0.40293138 21.11 15.56 0.00875166 43444.1 37.76 21.06 0.00875166 60441.5
PSZ-AC:1_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:1 CORE_ZN Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2804.014 2804.014 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:1 FAN Fan:OnOff 0.375212 0.41017938   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 00:10:00 Sensible 2804.01 2804.01 1.0000 0.41017938 0.375212 17.56 12.02 0.00736544 36306.3 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2804.01 0.50 0.00431558 0.50 0.06462207 17.2228 21.11 0.00800000 21.11 0.00800000 46.6350 811.45 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:2 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8243.406 6601.599 0.475200 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.2908 1004.8586 1.0932 PSZ-AC:2 FAN Fan:OnOff 0.475200 0.51948580   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 Sensible 7084.28 7084.28 0.8594 0.51948580 0.475200 26.57 16.12 0.00831159 47894.6 12.80 11.05 0.00831159 33846.5 -999.0 -999.00 -999.00 -999.00 532.275 6552.01 40.13 0.00563007 18.37 0.04898771 10.3089 23.89 0.00861980 23.89 0.00862006 42.3982 4891.41 0.00 8241.99 6276.90 0.49897004 26.67 19.44 0.01118466 55322.4 14.37 13.83 0.00964055 38804.4
PSZ-AC:2 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 8243.406 8243.406 0.475200 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:2 FAN Fan:OnOff 0.475200 0.51948580   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 8243.41 8243.41 1.0000 0.51948580 0.475200 18.98 12.56 0.00734724 37711.0 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8243.41 0.50 0.00431558 0.50 0.04898771 10.3089 21.11 0.00769569 21.11 0.00769569 44.8844 2443.43 0.00 8254.24 8254.24 0.51030633 21.11 15.56 0.00875166 43444.1 36.95 20.82 0.00875166 59619.2
PSZ-AC:2_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:2 PERIMETER_ZN_1 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3998.465 3998.465 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:2 FAN Fan:OnOff 0.475200 0.51948580   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3998.47 3998.47 1.0000 0.51948580 0.475200 18.98 12.56 0.00734724 37711.0 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3998.47 0.50 0.00431558 0.50 0.04898771 10.3089 21.11 0.00769569 21.11 0.00769569 44.8844 2443.43 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:3 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 5648.455 4522.465 0.341223 -999.0 -999.000 -999.0000 1.02154 1.00000 1020.3270 1004.8586 1.0932 PSZ-AC:3 FAN Fan:OnOff 0.341223 0.37302317   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 Sensible 5007.65 5007.65 0.8866 0.37302317 0.341223 26.05 15.96 0.00833103 47410.2 12.80 11.07 0.00833103 33895.6 -999.0 -999.00 -999.00 -999.00 382.207 4625.44 37.41 0.00562583 17.52 0.02906014 8.5165 23.89 0.00858286 23.89 0.00858329 42.2195 3514.03 0.00 5647.49 4299.75 0.35829157 26.67 19.44 0.01118466 55322.4 14.93 14.12 0.00970984 39560.1
PSZ-AC:3 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 5648.455 5648.455 0.341223 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:3 FAN Fan:OnOff 0.341223 0.37302317   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 5648.45 5648.45 1.0000 0.37302317 0.341223 19.35 12.74 0.00739314 38203.6 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 5648.45 0.50 0.00431558 0.50 0.02906014 8.5165 21.11 0.00767964 21.11 0.00767964 44.7922 1540.03 0.00 5655.88 5655.88 0.36643174 21.11 15.56 0.00875166 43444.1 36.23 20.60 0.00875166 58879.1
PSZ-AC:3_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:3 PERIMETER_ZN_2 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2479.019 2479.019 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:3 FAN Fan:OnOff 0.341223 0.37302317   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2479.02 2479.02 1.0000 0.37302317 0.341223 19.35 12.74 0.00739314 38203.6 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2479.02 0.50 0.00431558 0.50 0.02906014 8.5165 21.11 0.00767964 21.11 0.00767964 44.7922 1540.03 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:4 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 8212.910 6575.945 0.473239 -999.0 -999.000 -999.0000 1.00000 1.00000 1020.2893 1004.8586 1.0932 PSZ-AC:4 FAN Fan:OnOff 0.473239 0.51734262   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 Sensible 7058.45 7058.45 0.8594 0.51734262 0.473239 26.58 16.12 0.00831074 47899.5 12.80 11.05 0.00831074 33844.4 -999.0 -999.00 -999.00 -999.00 530.079 6528.37 40.13 0.00563007 18.37 0.04898771 10.3516 23.89 0.00862028 23.89 0.00862051 42.4004 4872.53 0.00 8211.50 6252.62 0.49691150 26.67 19.44 0.01118466 55322.4 14.36 13.83 0.00963905 38797.3
PSZ-AC:4 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 8212.910 8212.910 0.473239 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:4 FAN Fan:OnOff 0.473239 0.51734262   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 8212.91 8212.91 1.0000 0.51734262 0.473239 18.98 12.55 0.00734186 37688.3 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8212.91 0.50 0.00431558 0.50 0.04898771 10.3516 21.11 0.00769129 21.11 0.00769129 44.8591 2405.54 0.00 8223.70 8223.70 0.50820102 21.11 15.56 0.00875166 43444.1 36.96 20.82 0.00875166 59626.1
PSZ-AC:4_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:4 PERIMETER_ZN_3 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 3953.665 3953.665 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:4 FAN Fan:OnOff 0.473239 0.51734262   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 3953.66 3953.66 1.0000 0.51734262 0.473239 18.98 12.55 0.00734186 37688.3 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 3953.66 0.50 0.00431558 0.50 0.04898771 10.3516 21.11 0.00769129 21.11 0.00769129 44.8591 2405.54 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
PSZ-AC:5 HP COOLING COIL Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident CoolingDesignCapacity N/A Yes Yes unknown No 6615.626 5296.836 0.399650 -999.0 -999.000 -999.0000 1.02173 1.00000 1020.3765 1004.8586 1.0932 PSZ-AC:5 FAN Fan:OnOff 0.399650 0.43689506   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 5814.66 5814.66 0.8789 0.43689506 0.399650 25.92 15.94 0.00835767 47354.0 12.80 11.09 0.00835767 33962.8 -999.0 -999.00 -999.00 -999.00 447.651 5367.01 38.05 0.00562683 17.72 0.02906014 7.2714 23.89 0.00857181 23.89 0.00857183 42.1639 4115.01 0.00 6614.49 5035.99 0.41964101 26.67 19.44 0.01118466 55322.4 14.93 14.12 0.00970984 39560.1
PSZ-AC:5 HEATING COIL Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes Yes unknown No 6615.626 6615.626 0.399650 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:5 FAN Fan:OnOff 0.399650 0.43689506   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 6615.63 6615.63 1.0000 0.43689506 0.399650 19.61 12.88 0.00743333 38566.9 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6615.63 0.50 0.00431558 0.50 0.02906014 7.2714 21.11 0.00767781 21.11 0.00767781 44.7816 1530.44 0.00 6624.32 6624.32 0.42917499 21.11 15.56 0.00875166 43444.1 36.23 20.60 0.00875166 58879.1
PSZ-AC:5_SUPPHEATCOIL Coil:Heating:Fuel AirLoop AirLoopHVAC PSZ-AC:5 PERIMETER_ZN_4 Non-Coincident HeatingDesignCapacity N/A Yes No unknown No 2467.685 2467.685 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.0932 PSZ-AC:5 FAN Fan:OnOff 0.399650 0.43689506   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 unknown unknown TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 Sensible 2467.68 2467.68 1.0000 0.43689506 0.399650 19.61 12.88 0.00743333 38566.9 40.00 20.06 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 2467.68 0.50 0.00431558 0.50 0.02906014 7.2714 21.11 0.00767781 21.11 0.00767781 44.7816 1530.44 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
CORE_ZN 2424.50 1207.33 400.67
PERIMETER_ZN_1 2112.50 1597.50 552.00
PERIMETER_ZN_2 1761.33 1815.33 570.17
PERIMETER_ZN_3 1913.50 2305.33 586.67
PERIMETER_ZN_4 2153.50 2141.67 742.83
ATTIC 0.00 0.00 0.00
Facility 2757.33 2569.50 831.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
CORE_ZN 0.00 197.17 0.00 194.50
PERIMETER_ZN_1 0.00 70.00 0.00 52.33
PERIMETER_ZN_2 0.00 52.50 0.00 3.50
PERIMETER_ZN_3 0.00 10.33 0.00 1.00
PERIMETER_ZN_4 0.00 57.83 0.00 7.50
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 343.17 0.00 235.33
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.398 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.397 0.430 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.371 0.097 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.397 0.078 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.398 0.088 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
CORE_ZN 4.75 8.05 456.46 0.000 0.000 0.000 0.000
PERIMETER_ZN_1 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_2 1.93 3.62 205.26 0.000 0.000 0.000 0.000
PERIMETER_ZN_3 3.60 6.11 346.02 0.000 0.000 0.000 0.000
PERIMETER_ZN_4 2.13 3.62 205.26 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
CORE_ZN PSZ-AC:1 4.75 8.05 456.46 149.66 0.0646 0.065
PERIMETER_ZN_1 PSZ-AC:2 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_2 PSZ-AC:3 1.93 3.62 205.26 67.30 0.0291 0.029
PERIMETER_ZN_3 PSZ-AC:4 3.60 6.11 346.02 113.45 0.0490 0.049
PERIMETER_ZN_4 PSZ-AC:5 2.13 3.62 205.26 67.30 0.0291 0.029
Total Facility   16.00 27.51 1559.03 511.16 0.2207 0.221


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
CORE_ZN 762943.97 0.00 762943.97 0.00 762943.97 2037921.45 5483.98 3276.02 0.00 25.05
PERIMETER_ZN_1 582469.54 0.00 582469.54 830031.74 1412501.28 1544876.42 5483.71 3276.29 0.00 176.10
PERIMETER_ZN_2 347478.53 0.00 347478.53 211253.15 558731.68 916440.58 5482.71 3277.29 0.00 1036.12
PERIMETER_ZN_3 580927.93 0.00 580927.93 316879.72 897807.66 1544876.42 5483.68 3276.32 0.00 130.32
PERIMETER_ZN_4 348243.08 0.00 348243.08 211253.15 559496.22 916440.58 5481.73 3278.27 0.00 260.61
Total Facility 2622063.05 0.00 2622063.05 1569417.76 4191480.81 6960555.45 5484.00 3279.80 0.00 1214.24


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
CORE_ZN 0.0494 0.0000 0.0494 0.0000 0.0494 0.0646 1008.00 3276.00 0.00
PERIMETER_ZN_1 0.0375 0.0000 0.0375 0.0406 0.0780 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_2 0.0208 0.0000 0.0208 0.0054 0.0261 0.0291 1008.00 2520.00 0.00
PERIMETER_ZN_3 0.0375 0.0000 0.0375 0.0073 0.0448 0.0490 1008.00 3276.00 0.00
PERIMETER_ZN_4 0.0223 0.0000 0.0223 0.0049 0.0272 0.0291 1007.69 3276.31 0.00
Total Facility 0.1674 0.0000 0.1674 0.0582 0.2255 0.2207 1008.00 3276.31 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
PSZ-AC:1 911774.20 0.00 911774.20 2037921.45 5483.87 0.06 3276.07 23.38
PSZ-AC:2 696093.97 0.00 696093.97 1544876.42 5482.85 0.16 3276.99 173.19
PSZ-AC:3 415262.41 0.00 415262.41 916440.58 5481.26 0.20 3278.54 1022.84
PSZ-AC:4 694251.64 0.00 694251.64 1544876.42 5483.41 0.06 3276.54 126.59
PSZ-AC:5 416176.11 0.00 416176.11 916440.58 5479.88 0.04 3280.08 244.34


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
PSZ-AC:1 0.0591 0.0000 0.0591 0.0646 1008.00 0.00 3276.00
PSZ-AC:2 0.0448 0.0000 0.0448 0.0490 1008.00 0.00 3276.00
PSZ-AC:3 0.0248 0.0000 0.0248 0.0291 1008.00 0.00 2520.00
PSZ-AC:4 0.0448 0.0000 0.0448 0.0490 1008.00 0.00 3276.00
PSZ-AC:5 0.0266 0.0000 0.0266 0.0291 1007.49 0.00 3276.51


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
PSZ-AC:1 0.00 3299.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:2 0.00 3449.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:3 0.00 3542.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:4 0.00 3402.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PSZ-AC:5 0.00 3583.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
PSZ-AC:1 0.0000 0.0772 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:2 0.0000 0.0585 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:3 0.0000 0.0347 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:4 0.0000 0.0585 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
PSZ-AC:5 0.0000 0.0342 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Surfaces by Class

Total Outdoors
Wall 20 4
Floor 14 8
Roof 9 4
Internal Mass 5 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 21 21
Door 2 2
Glass Door 1 1
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 5
Conditioned Zones 5
Unconditioned Zones 1
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 523
Defaulted Fields 365
Fields with Defaults 1332
Autosized Fields 115
Autosizable Fields 137
Autocalculated Fields 90
Autocalculatable Fields 156



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 206.18 1803.03 03-SEP-11:30 20172.61 28-JUN-15:40
Electricity:Building 95.68 1231.03 03-SEP-11:30 6704.58 28-NOV-16:30
Electricity:Zone:CORE_ZN 29.05 392.60 01-JAN-00:10 1962.98 02-JAN-08:10
Electricity:SpaceType:GENERAL 95.68 1231.03 03-SEP-11:30 6704.58 28-NOV-16:30
InteriorLights:Electricity 42.88 537.90 03-SEP-11:30 3238.93 28-NOV-16:30
InteriorLights:Electricity:Zone:CORE_ZN 13.59 189.67 01-JAN-00:10 948.30 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 42.88 537.90 03-SEP-11:30 3238.93 28-NOV-16:30
LightsWired:InteriorLights:Electricity 42.88 537.90 03-SEP-11:30 3238.93 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:CORE_ZN 13.59 189.67 01-JAN-00:10 948.30 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 42.88 537.90 03-SEP-11:30 3238.93 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_1 20.60 263.12 01-JAN-08:00 1488.06 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_1 8.88 109.29 01-JAN-08:00 718.87 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_1 8.88 109.29 01-JAN-08:00 718.87 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_2 12.38 156.09 01-JAN-08:20 882.74 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_2 5.43 64.83 01-JAN-08:20 426.44 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_2 5.43 64.83 01-JAN-08:20 426.44 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_3 21.24 263.12 14-MAY-16:20 1488.06 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_3 9.52 109.29 14-MAY-16:20 718.87 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_3 9.52 109.29 14-MAY-16:20 718.87 28-NOV-16:30
Electricity:Zone:PERIMETER_ZN_4 12.41 156.09 01-JAN-14:10 882.74 28-NOV-16:30
InteriorLights:Electricity:Zone:PERIMETER_ZN_4 5.46 64.83 01-JAN-14:10 426.44 28-NOV-16:30
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_ZN_4 5.46 64.83 01-JAN-14:10 426.44 28-NOV-16:30
InteriorEquipment:Electricity 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_ZN 15.46 202.94 01-JAN-00:10 1014.68 02-JAN-08:10
InteriorEquipment:Electricity:SpaceType:GENERAL 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_ZN 15.46 202.94 01-JAN-00:10 1014.68 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 52.80 693.13 01-JAN-00:10 3465.65 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_1 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_2 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_3 11.72 153.84 01-JAN-00:10 769.19 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_ZN_4 6.95 91.26 01-JAN-00:10 456.29 02-JAN-08:10
ElectricityPurchased:Facility 206.18 1803.03 03-SEP-11:30 20172.61 28-JUN-15:40
ElectricityPurchased:Plant 206.18 1803.03 03-SEP-11:30 20172.61 28-JUN-15:40
Cogeneration:ElectricityPurchased 206.18 1803.03 03-SEP-11:30 20172.61 28-JUN-15:40
General:Cogeneration:ElectricityPurchased 206.18 1803.03 03-SEP-11:30 20172.61 28-JUN-15:40
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 206.18 1803.03 03-SEP-11:30 20172.61 28-JUN-15:40
ElectricityNet:Plant 206.18 1803.03 03-SEP-11:30 20172.61 28-JUN-15:40
Cogeneration:ElectricityNet 206.18 1803.03 03-SEP-11:30 20172.61 28-JUN-15:40
General:Cogeneration:ElectricityNet 206.18 1803.03 03-SEP-11:30 20172.61 28-JUN-15:40
ExteriorLights:Electricity 20.67 0.00 01-JAN-07:30 1574.40 01-JAN-06:10
General:ExteriorLights:Electricity 20.67 0.00 01-JAN-07:30 1574.40 01-JAN-06:10
Electricity:HVAC 66.38 0.00 01-JAN-00:20 11179.15 28-JUN-16:00
Fans:Electricity 27.54 0.00 01-JAN-00:10 2312.49 02-JAN-06:10
General:Fans:Electricity 27.54 0.00 01-JAN-00:10 2312.49 02-JAN-06:10
Cooling:Electricity 38.60 0.00 01-JAN-00:10 8866.66 28-JUN-16:00
General:Cooling:Electricity 38.60 0.00 01-JAN-00:10 8866.66 28-JUN-16:00
Heating:Electricity 0.23 0.00 01-JAN-00:20 4346.61 02-JAN-07:10
General:Heating:Electricity 0.23 0.00 01-JAN-00:20 4346.61 02-JAN-07:10
Electricity:Plant 23.45 572.00 23-FEB-15:30 2787.77 20-JAN-12:20
WaterSystems:Electricity 23.45 572.00 20-JAN-10:50 2787.77 20-JAN-12:20
Water Heater:WaterSystems:Electricity 23.45 572.00 20-JAN-10:50 2787.77 20-JAN-12:20
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 20-JAN-10:30
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 20-JAN-10:30


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 0.00 0.00 01-JAN-00:10 2200.93 27-MAR-06:10
NaturalGas:HVAC 0.00 0.00 01-JAN-00:10 2200.93 27-MAR-06:10
Heating:NaturalGas 0.00 0.00 01-JAN-00:10 2200.93 27-MAR-06:10
General:Heating:NaturalGas 0.00 0.00 01-JAN-00:10 2200.93 27-MAR-06:10


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:Water 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 06-MAR-13:00
MainsWater:Facility 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterSystems:MainsWater 58.31 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 06-MAR-13:00
WaterUse:WaterSystems:Water 29.16 0.00 01-JAN-00:10 0.00 25-JAN-12:10
WaterUse:WaterSystems:MainsWater 29.16 0.00 01-JAN-00:10 0.00 25-JAN-12:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 285.93 0.00 01-JAN-00:10 62233.24 14-AUG-07:10
EnergyTransfer:Building 128.36 0.00 01-JAN-00:10 27898.81 18-SEP-07:20
EnergyTransfer:Zone:CORE_ZN 32.30 0.00 01-JAN-00:10 6430.67 10-OCT-07:10
Heating:EnergyTransfer 2.68 0.00 01-JAN-00:10 12022.04 02-JAN-07:10
Heating:EnergyTransfer:Zone:CORE_ZN 0.44 0.00 01-JAN-00:10 1450.49 28-JUN-17:10
General:Heating:EnergyTransfer 2.68 0.00 01-JAN-00:10 12022.04 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:CORE_ZN 0.44 0.00 01-JAN-00:10 1450.49 28-JUN-17:10
Cooling:EnergyTransfer 125.68 0.00 01-JAN-00:10 27898.81 18-SEP-07:20
Cooling:EnergyTransfer:Zone:CORE_ZN 31.86 0.00 01-JAN-00:10 6430.67 10-OCT-07:10
General:Cooling:EnergyTransfer 125.68 0.00 01-JAN-00:10 27898.81 18-SEP-07:20
General:Cooling:EnergyTransfer:Zone:CORE_ZN 31.86 0.00 01-JAN-00:10 6430.67 10-OCT-07:10
EnergyTransfer:Zone:PERIMETER_ZN_1 33.71 0.00 01-JAN-00:10 6885.33 10-OCT-11:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.65 0.00 01-JAN-00:10 3638.26 27-MAR-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_1 0.65 0.00 01-JAN-00:10 3638.26 27-MAR-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 33.06 0.00 01-JAN-00:10 6885.33 10-OCT-11:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_1 33.06 0.00 01-JAN-00:10 6885.33 10-OCT-11:10
EnergyTransfer:Zone:PERIMETER_ZN_2 19.89 0.00 01-JAN-00:10 4757.40 05-JUN-07:20
Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.40 0.00 01-JAN-00:10 1980.71 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_2 0.40 0.00 01-JAN-00:10 1980.71 02-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 19.49 0.00 01-JAN-00:10 4757.40 05-JUN-07:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_2 19.49 0.00 01-JAN-00:10 4757.40 05-JUN-07:20
EnergyTransfer:Zone:PERIMETER_ZN_3 24.11 0.00 01-JAN-00:10 6597.58 14-AUG-07:10
Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.74 0.00 01-JAN-00:10 4226.62 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_3 0.74 0.00 01-JAN-00:10 4226.62 02-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 23.37 0.00 01-JAN-00:10 6597.58 14-AUG-07:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_3 23.37 0.00 01-JAN-00:10 6597.58 14-AUG-07:10
EnergyTransfer:Zone:PERIMETER_ZN_4 18.36 0.00 01-JAN-00:10 4614.99 14-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.45 0.00 01-JAN-00:10 1901.52 02-JAN-07:10
General:Heating:EnergyTransfer:Zone:PERIMETER_ZN_4 0.45 0.00 01-JAN-00:10 1901.52 02-JAN-07:10
Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 17.90 0.00 01-JAN-00:10 4614.99 14-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_ZN_4 17.90 0.00 01-JAN-00:10 4614.99 14-AUG-16:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
PlantLoopHeatingDemand:Facility 0.00 -0.00 24-JAN-07:10 77.04 02-JAN-07:10
PlantLoopHeatingDemand:Plant 0.00 -0.00 24-JAN-07:10 77.04 02-JAN-07:10
WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 24-JAN-07:10 77.04 02-JAN-07:10
General:WaterSystems:PlantLoopHeatingDemand 0.00 -0.00 24-JAN-07:10 77.04 02-JAN-07:10
EnergyTransfer:HVAC 157.56 0.00 01-JAN-00:10 36200.22 05-SEP-07:10
CoolingCoils:EnergyTransfer 157.25 0.00 01-JAN-00:10 36200.22 05-SEP-07:10
HeatingCoils:EnergyTransfer 0.32 0.00 01-JAN-00:10 13289.91 02-JAN-07:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Plant 0.00 -0.00 24-JAN-07:10 77.04 02-JAN-07:10
WaterSystems:EnergyTransfer 0.00 -0.00 24-JAN-07:10 77.04 02-JAN-07:10
WaterUse:WaterSystems:EnergyTransfer 0.00 -0.00 24-JAN-07:10 77.04 02-JAN-07:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
CORE_ZN 0.000 0.000 0.439 -31.859 0.000 0.000 4.895 13.590 15.459 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -2.523
PERIMETER_ZN_1 0.000 0.000 0.648 -33.059 0.000 0.000 3.750 8.883 11.719 20.138 0.000 2.432 0.000 0.000 -7.657 0.000 -4.213 -2.641
PERIMETER_ZN_2 0.000 0.000 0.403 -19.490 0.000 0.000 1.625 5.425 6.952 10.310 0.000 0.311 0.000 0.000 -3.836 0.000 -1.251 -0.450
PERIMETER_ZN_3 0.000 0.000 0.739 -23.369 0.000 0.000 3.789 9.517 11.719 5.945 0.000 0.496 0.001 0.000 -5.899 0.000 -1.761 -1.176
PERIMETER_ZN_4 0.000 0.000 0.453 -17.904 0.000 0.000 2.229 5.463 6.952 9.949 0.000 0.297 0.000 0.000 -4.239 0.000 -1.284 -1.914
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 13.251 27.128 0.000 0.000 0.000 -40.379 -0.001
Total Facility 0.000 0.000 2.680 -125.681 0.000 0.000 16.289 42.878 52.800 46.342 0.000 16.787 27.130 0.000 -21.631 0.000 -48.888 -8.704


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 12-OCT-07:02 0.00 0.00 0.00 -7051.35 0.00 0.00 500.39 948.30 1014.68 0.00 0.00 0.00 4587.99 0.00 -0.00 0.00 0.00 0.00
PERIMETER_ZN_1 10-OCT-06:01 0.00 0.00 0.00 -7811.29 0.00 0.00 64.29 335.47 384.60 0.00 0.00 0.00 9190.18 0.00 -645.98 0.00 -1517.27 0.00
PERIMETER_ZN_2 10-OCT-06:01 0.00 0.00 0.00 -5258.59 0.00 0.00 38.70 199.00 228.15 0.00 0.00 0.00 5154.54 0.00 -336.81 0.00 -24.98 0.00
PERIMETER_ZN_3 10-OCT-06:01 0.00 0.00 0.00 -7736.98 0.00 0.00 70.69 335.47 384.60 0.00 0.00 0.00 7450.59 0.00 -469.30 0.00 -35.07 0.00
PERIMETER_ZN_4 16-JUL-19:12 0.00 0.00 0.00 -6140.43 0.00 0.00 0.00 83.62 91.26 226.32 0.00 0.00 5759.56 0.00 -0.00 0.00 -20.33 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 10-OCT-06:01 0.00 0.00 0.00 -33855.14 0.00 0.00 296.63 1511.48 1732.82 0.00 0.00 873.35 32830.31 0.00 -1787.22 0.00 -1602.23 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
CORE_ZN 02-JAN-08:62 0.00 0.00 5682.38 0.00 0.00 0.00 697.55 948.30 1014.68 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -8342.91
PERIMETER_ZN_1 27-MAR-06:02 0.00 0.00 9807.18 0.00 0.00 0.00 117.05 335.47 384.60 0.00 0.00 0.00 0.00 0.00 -895.06 0.00 -2791.33 -6957.91
PERIMETER_ZN_2 27-MAR-06:02 0.00 0.00 5769.64 0.00 0.00 0.00 69.88 199.00 228.15 0.00 0.00 0.00 0.00 0.00 -472.60 0.00 -60.16 -5733.91
PERIMETER_ZN_3 02-JAN-06:02 0.00 0.00 10289.60 0.00 0.00 0.00 67.18 183.71 384.60 0.00 0.00 0.00 0.00 0.00 -500.16 0.00 -116.41 -10308.53
PERIMETER_ZN_4 02-JAN-07:02 0.00 0.00 5713.75 0.00 0.00 0.00 71.90 199.00 228.15 0.00 0.00 0.00 0.00 0.00 -333.06 0.00 -26.72 -5853.03
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 27-MAR-06:02 -998.13 998.13 30769.90 -998.13 0.00 0.00 511.77 1511.48 1732.82 0.00 0.00 973.71 0.00 0.00 -2496.64 0.00 -2998.38 -29006.54



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3752 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3752 0.1722 1.0000 Not calculated 0.0646 0.1722    
PSZ-AC:2 0.4752 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4752 0.1031 1.0000 Not calculated 0.0490 0.1031    
PSZ-AC:3 0.3412 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3412 0.0852 1.0000 Not calculated 0.0291 0.0852    
PSZ-AC:4 0.4732 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4732 0.1035 1.0000 Not calculated 0.0490 0.1035    
PSZ-AC:5 0.3996 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3996 0.0727 1.0000 Not calculated 0.0291 0.0727    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
PSZ-AC:1 0.3752 0.0000 8.0545 1.0000 Calculated from schedules 0.0646 0.3752 1.0000 1.0000 Not calculated 0.0646 0.1722    
PSZ-AC:2 0.4752 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4752 1.0000 1.0000 Not calculated 0.0490 0.1031    
PSZ-AC:3 0.3412 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3412 1.0000 1.0000 Not calculated 0.0291 0.0852    
PSZ-AC:4 0.4732 0.0000 6.1058 1.0000 Calculated from schedules 0.0490 0.4732 1.0000 1.0000 Not calculated 0.0490 0.1035    
PSZ-AC:5 0.3996 0.0000 3.6221 1.0000 Calculated from schedules 0.0291 0.3996 1.0000 1.0000 Not calculated 0.0291 0.0727    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
CORE_ZN PSZ-AC:1 0.000000 8.0545 0.000432 149.66 0.0646 1.0000 0.0646 1.000 0.0646
PERIMETER_ZN_1 PSZ-AC:2 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_2 PSZ-AC:3 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291
PERIMETER_ZN_3 PSZ-AC:4 0.000000 6.1058 0.000432 113.45 0.0490 1.0000 0.0490 1.000 0.0490
PERIMETER_ZN_4 PSZ-AC:5 0.000000 3.6221 0.000432 67.30 0.0291 1.0000 0.0291 1.000 0.0291


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
PSZ-AC:1 0.000000 8.05 0.000432 149.6574 0.0646 0.0646 0.0646
PSZ-AC:2 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:3 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291
PSZ-AC:4 0.000000 6.11 0.000432 113.4500 0.0490 0.0490 0.0490
PSZ-AC:5 0.000000 3.62 0.000432 67.3000 0.0291 0.0291 0.0291


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3752 0.3752 0.3752 No 0.0646 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4752 0.4752 0.4752 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3412 0.3412 0.3412 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4732 0.4732 0.4732 No 0.0490 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3996 0.3996 0.3996 No 0.0291 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3752 0.3752 0.3752 0.3752 0.0646 1.0000
PSZ-AC:2 0.4752 0.4752 0.4752 0.4752 0.0490 1.0000
PSZ-AC:3 0.3412 0.3412 0.3412 0.3412 0.0291 1.0000
PSZ-AC:4 0.4732 0.4732 0.4732 0.4732 0.0490 1.0000
PSZ-AC:5 0.3996 0.3996 0.3996 0.3996 0.0291 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
CORE_ZN PSZ-AC:1 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3752 0.3752 0.3752 No 0.0646 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_1 PSZ-AC:2 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4752 0.4752 0.4752 No 0.0490 0.3518 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_2 PSZ-AC:3 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3412 0.3412 0.3412 No 0.0291 0.3311 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_3 PSZ-AC:4 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4732 0.4732 0.4732 No 0.0490 0.3574 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_ZN_4 PSZ-AC:5 AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.3996 0.3996 0.3996 No 0.0291 0.3332 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
PSZ-AC:1 0.3752 0.3752 0.3752 0.3752 0.0646 1.0000
PSZ-AC:2 0.4752 0.4752 0.4752 0.4752 0.0490 1.0000
PSZ-AC:3 0.3412 0.3412 0.3412 0.3412 0.0291 1.0000
PSZ-AC:4 0.4732 0.4732 0.4732 0.4732 0.0490 1.0000
PSZ-AC:5 0.3996 0.3996 0.3996 0.3996 0.0291 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Total gross floor area [m2] 511.16
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
CORE_ZN 149.66 149.66 0.00 82.16
PERIMETER_ZN_1 113.45 113.45 0.00 82.16
PERIMETER_ZN_2 67.30 67.30 0.00 67.66
PERIMETER_ZN_3 113.45 113.45 0.00 82.16
PERIMETER_ZN_4 67.30 67.30 0.00 82.16
ATTIC 567.98 0.00 567.98 0.00
Totals 511.16 511.16 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 235.33
Number of hours not met 235.33


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.23 4346.61 0.00 2200.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 38.60 8866.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 42.88 3238.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 20.67 1574.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 52.80 3465.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 27.54 2312.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 23.45 2787.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 52.80 206.18
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 52.80 206.18


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 83.88
Space Heating 0.45
Space Cooling 75.52
Fans (All) 53.88
Service Water Heating 45.88
Receptacle Equipment 103.29
Miscellaneous (All) 403.35
Subtotal 403.35


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 20.80
Space Heating 0.11
Space Cooling 18.72
Fans (All) 13.36
Service Water Heating 11.38
Receptacle Equipment 25.61
Miscellaneous 10.03


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
LTG_SCH_OFFICE 2841. 8760.
BLDG_EQUIP_SCH 4310. 8760.
BLDG_OCC_SCH 2512. 4420.
BLDG_OCC_SCH_W_SB 1854. 3640.
BLDG_OCC_SCH_WO_SB 2533. 4420.
BINARY OCCUPANCY 4420. 4420.
INFIL_QUARTER_ON_SCH 5991. 8760.
INFIL_DOOR_OPENING_SCH 1154. 3380.
BLDG_SWH_SCH 2064. 3900.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6200. 8760.
ALWAYS_OFF 0. 0.
HVACOPERATIONSCHD_W_SB 2600. 2600.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 3120. 3120.
MINOA_SCHED 8760. 8760.
WORK_EFF_SCH 0. 0.
CORE_ZN WATER EQUIPMENT LATENT FRACT SCHED 438. 8760.
CORE_ZN WATER EQUIPMENT SENSIBLE FRACT SCHED 1752. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 3120. 3120.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_SCH_YES_OPTIMUM CORE_ZN DUAL SP CONTROL January 21.11 365 15.56 365
CLGSETP_SCH_YES_OPTIMUM CORE_ZN DUAL SP CONTROL July 23.89 365 29.44 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 6630.17 2129.83 0.00 0.00 0.00
PERIMETER_ZN_1 6867.17 1892.83 0.00 0.00 0.00
PERIMETER_ZN_2 6775.17 1984.83 0.00 0.00 0.00
PERIMETER_ZN_3 7030.67 1729.33 0.00 0.00 0.00
PERIMETER_ZN_4 6603.17 2156.83 0.00 0.00 0.00
ATTIC 5332.00 943.33 874.50 1306.33 303.83
Min 5332.00 943.33 0.00 0.00 0.00
Max 7030.67 2156.83 874.50 1306.33 303.83
Average 6539.72 1806.17 145.75 217.72 50.64
Sum 39238.33 10837.00 874.50 1306.33 303.83


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
CORE_ZN 17892.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_2 4788.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_3 13356.00 0.00 0.00 0.00 0.00
PERIMETER_ZN_4 6804.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17892.00 0.00 0.00 0.00 0.00
Average 9366.00 0.00 0.00 0.00 0.00
Sum 56196.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 7009.00 1751.00 0.00 0.00 0.00
PERIMETER_ZN_1 7447.00 1313.00 0.00 0.00 0.00
PERIMETER_ZN_2 7460.67 1299.33 0.00 0.00 0.00
PERIMETER_ZN_3 7511.17 1248.83 0.00 0.00 0.00
PERIMETER_ZN_4 7427.33 1332.67 0.00 0.00 0.00
ATTIC 5481.00 1499.67 434.00 364.00 981.33
Min 5481.00 1248.83 0.00 0.00 0.00
Max 7511.17 1751.00 434.00 364.00 981.33
Average 7056.03 1407.42 72.33 60.67 163.56
Sum 42336.17 8444.50 434.00 364.00 981.33


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CORE_ZN 17862.33 29.67 0.00 0.00 0.00
PERIMETER_ZN_1 13325.17 30.83 0.00 0.00 0.00
PERIMETER_ZN_2 4787.50 0.50 0.00 0.00 0.00
PERIMETER_ZN_3 13330.83 25.17 0.00 0.00 0.00
PERIMETER_ZN_4 6803.50 0.50 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 17862.33 30.83 0.00 0.00 0.00
Average 9351.56 14.44 0.00 0.00 0.00
Sum 56109.33 86.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 08:29:54

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_ZN_4 0.00 0.00 8760.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 5840.00 0.00
Sum 0.00 0.00 35040.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
CORE_ZN 0.00 0.00 0.00 0.00
PERIMETER_ZN_1 0.00 0.00 13356.00 0.00
PERIMETER_ZN_2 0.00 0.00 4788.00 0.00
PERIMETER_ZN_3 0.00 0.00 13356.00 0.00
PERIMETER_ZN_4 0.00 0.00 6804.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 13356.00 0.00
Average 0.00 0.00 6384.00 0.00
Sum 0.00 0.00 38304.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICESMALL

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.827
February 12.716
March 15.425
April 23.310
May 26.312
June 31.196
July 30.423
August 29.815
September 27.754
October 20.869
November 15.431
December 11.863
   
Annual Sum or Average 21.705
Minimum of Months 11.863
Maximum of Months 31.196



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.142884E+10 4544.14 27-JAN-08:63 11.83 5.09 0.295151E+09 427.44 27-JAN-08:09 11.83 5.09
February 0.105265E+10 2669.79 10-FEB-08:63 17.00 8.89 0.267016E+09 415.13 10-FEB-08:09 17.00 8.89
March 0.155501E+10 6565.51 21-MAR-07:03 16.15 9.27 0.325482E+09 455.42 21-MAR-07:10 16.15 9.27
April 0.261127E+10 6818.43 07-APR-07:02 12.40 6.89 0.288473E+09 469.21 26-APR-07:10 21.50 10.77
May 0.336835E+10 6776.65 22-MAY-06:02 16.67 6.50 0.318433E+09 469.21 15-MAY-07:10 16.67 6.50
June 0.403318E+10 6849.90 26-JUN-05:02 22.17 10.13 0.325775E+09 469.22 30-JUN-07:10 29.33 19.12
July 0.378149E+10 6998.50 03-JUL-05:02 20.33 7.70 0.301940E+09 469.23 17-JUL-07:10 27.33 20.24
August 0.416078E+10 6727.63 23-AUG-06:01 22.00 12.48 0.341737E+09 469.23 16-AUG-07:10 22.00 12.48
September 0.356533E+10 6661.04 28-SEP-06:02 21.10 12.33 0.296155E+09 469.25 25-SEP-07:10 21.10 12.33
October 0.295149E+10 7051.26 12-OCT-07:02 8.67 3.88 0.303910E+09 469.23 02-OCT-07:10 8.67 3.88
November 0.203365E+10 6719.83 06-NOV-08:62 12.67 4.88 0.299894E+09 469.23 03-NOV-07:10 12.67 4.88
December 0.131751E+10 4043.56 26-DEC-08:62 8.83 3.32 0.281675E+09 416.70 26-DEC-08:09 8.83 3.32
                     
Annual Sum or Average 0.318595E+11         0.364564E+10        
Minimum of Months 0.105265E+10 2669.79   8.67 3.32 0.267016E+09 415.13   8.67 3.32
Maximum of Months 0.416078E+10 7051.26   22.17 12.48 0.341737E+09 469.25   29.33 20.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.207468E+10 5388.37 30-JAN-14:40 24.67 9.55 0.222438E+09 305.00 09-JAN-11:00 24.67 9.55
February 0.753564E+09 3569.28 01-FEB-15:30 15.50 6.96 0.196016E+09 305.14 17-FEB-10:50 16.83 13.03
March 0.920044E+09 3293.37 20-MAR-14:30 27.70 14.31 0.237765E+09 305.29 23-MAR-07:49 16.37 10.32
April 0.212111E+10 7132.45 26-APR-07:02 21.50 10.77 0.216970E+09 355.69 25-APR-07:10 21.50 10.77
May 0.264101E+10 7342.37 08-MAY-06:01 20.50 9.41 0.240715E+09 355.69 11-MAY-07:10 23.17 12.09
June 0.394225E+10 7540.16 19-JUN-05:02 22.17 10.17 0.243795E+09 355.70 30-JUN-07:10 29.33 19.12
July 0.404988E+10 7501.20 31-JUL-05:02 25.83 15.57 0.221705E+09 355.71 10-JUL-07:10 25.83 15.57
August 0.456156E+10 7654.60 21-AUG-05:02 24.67 16.53 0.254986E+09 355.72 28-AUG-07:10 29.17 20.16
September 0.423510E+10 7610.69 27-SEP-06:02 19.90 13.92 0.223510E+09 355.70 15-SEP-07:10 19.90 13.92
October 0.355655E+10 7811.31 10-OCT-06:01 16.50 11.11 0.230800E+09 355.72 02-OCT-07:10 16.50 11.11
November 0.259336E+10 7173.95 01-NOV-07:02 19.83 14.36 0.225748E+09 351.86 01-NOV-07:10 19.83 14.36
December 0.160987E+10 5606.15 26-DEC-13:55 23.00 10.16 0.209661E+09 305.00 13-DEC-11:30 23.00 10.16
                     
Annual Sum or Average 0.330590E+11         0.272411E+10        
Minimum of Months 0.753564E+09 3293.37   15.50 6.96 0.196016E+09 305.00   16.37 9.55
Maximum of Months 0.456156E+10 7811.31   27.70 16.53 0.254986E+09 355.72   29.33 20.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.465077E+09 1257.69 31-JAN-16:13 29.00 10.73 95033268.20 181.56 20-JAN-09:50 29.00 10.73
February 0.204058E+09 900.29 23-FEB-11:04 15.83 10.67 84665428.85 183.75 17-FEB-13:09 15.83 10.67
March 0.447410E+09 1466.43 23-MAR-10:43 23.43 10.94 0.103700E+09 181.04 01-MAR-09:00 23.43 10.94
April 0.155306E+10 5025.12 17-APR-07:02 17.67 10.67 95442228.47 211.00 06-APR-07:10 17.67 10.67
May 0.209717E+10 5103.24 30-MAY-06:01 18.67 9.89 0.105890E+09 211.00 12-MAY-07:10 18.67 9.89
June 0.304071E+10 5071.49 19-JUN-05:02 22.17 10.17 0.107291E+09 211.00 19-JUN-07:10 28.50 12.43
July 0.298975E+10 5248.46 30-JUL-09:02 29.50 18.97 97502454.74 211.02 17-JUL-07:10 29.50 18.97
August 0.317689E+10 5151.64 21-AUG-05:02 24.67 16.53 0.111994E+09 211.01 11-AUG-07:10 24.67 16.53
September 0.253739E+10 5170.76 10-SEP-09:42 31.13 19.29 97110464.71 211.03 25-SEP-07:10 23.48 17.89
October 0.174493E+10 5258.57 10-OCT-06:01 16.50 11.11 99956513.17 211.02 02-OCT-07:10 16.50 11.11
November 0.887593E+09 4959.49 02-NOV-07:02 16.50 11.83 97929078.27 211.00 01-NOV-07:10 16.50 11.83
December 0.345831E+09 1146.07 26-DEC-13:55 23.00 10.16 89496413.64 180.93 13-DEC-11:39 23.00 10.16
                     
Annual Sum or Average 0.194899E+11         0.118601E+10        
Minimum of Months 0.204058E+09 900.29   15.83 9.89 84665428.85 180.93   15.83 9.89
Maximum of Months 0.317689E+10 5258.57   31.13 19.29 0.111994E+09 211.03   29.50 18.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.375685E+09 1542.92 27-JAN-16:27 26.50 9.48 0.213766E+09 311.65 04-JAN-14:20 26.50 9.48
February 0.125280E+09 859.96 01-FEB-15:57 16.00 7.03 0.187914E+09 305.18 27-FEB-15:20 17.33 9.62
March 0.417830E+09 1863.17 17-MAR-15:55 26.60 14.13 0.234196E+09 306.48 06-MAR-16:19 26.60 14.13
April 0.166005E+10 7390.02 17-APR-07:02 17.67 10.67 0.217350E+09 355.69 26-APR-07:10 21.50 10.77
May 0.247166E+10 7490.47 30-MAY-06:01 18.67 9.89 0.241161E+09 355.69 04-MAY-07:10 18.67 9.89
June 0.379715E+10 7530.55 19-JUN-05:02 22.17 10.17 0.243698E+09 355.69 19-JUN-07:10 28.50 12.43
July 0.386242E+10 7482.58 31-JUL-05:02 25.83 15.57 0.221393E+09 355.72 17-JUL-07:10 25.83 15.57
August 0.406686E+10 7626.13 21-AUG-05:02 24.67 16.53 0.253995E+09 355.71 28-AUG-07:10 29.17 20.16
September 0.334594E+10 7638.42 27-SEP-06:02 19.90 13.92 0.220597E+09 355.70 27-SEP-07:10 20.13 13.97
October 0.200857E+10 7736.95 10-OCT-06:01 16.50 11.11 0.227829E+09 355.72 02-OCT-07:10 16.50 11.11
November 0.952387E+09 7357.64 01-NOV-07:02 19.83 14.36 0.223100E+09 349.99 01-NOV-07:10 19.83 14.36
December 0.285640E+09 1380.95 22-DEC-16:35 24.33 9.71 0.200302E+09 306.40 21-DEC-10:00 24.33 9.71
                     
Annual Sum or Average 0.233695E+11         0.268530E+10        
Minimum of Months 0.125280E+09 859.96   16.00 7.03 0.187914E+09 305.18   16.50 9.48
Maximum of Months 0.406686E+10 7736.95   26.60 16.53 0.253995E+09 355.72   29.17 20.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.490230E+09 2204.85 31-JAN-16:55 29.00 10.73 0.130157E+09 181.47 19-JAN-09:30 29.00 10.73
February 0.184818E+09 1544.76 22-FEB-16:33 20.33 11.40 0.114225E+09 182.91 08-FEB-14:09 20.33 11.40
March 0.383803E+09 1891.88 16-MAR-15:57 28.80 13.95 0.141433E+09 183.69 17-MAR-07:10 14.37 9.61
April 0.135452E+10 5711.54 17-APR-07:02 17.67 10.67 0.130485E+09 212.14 05-APR-07:10 17.67 10.67
May 0.186959E+10 5858.29 30-MAY-06:01 18.67 9.89 0.144292E+09 211.00 12-MAY-07:10 18.67 9.89
June 0.281562E+10 5803.59 12-JUN-06:01 21.53 11.06 0.145241E+09 211.00 19-JUN-07:10 28.50 12.43
July 0.269549E+10 6140.81 16-JUL-19:12 29.33 19.93 0.131738E+09 211.01 10-JUL-07:10 29.33 19.93
August 0.288941E+10 5939.71 14-AUG-05:02 26.00 16.58 0.151272E+09 211.02 28-AUG-07:10 29.17 20.16
September 0.237993E+10 5935.47 27-SEP-06:02 19.90 13.92 0.131500E+09 211.01 27-SEP-07:10 20.13 13.97
October 0.156674E+10 6045.93 10-OCT-06:01 16.50 11.11 0.136252E+09 211.02 02-OCT-07:10 16.50 11.11
November 0.911434E+09 5739.04 02-NOV-07:02 16.50 11.83 0.133822E+09 211.00 01-NOV-07:10 16.50 11.83
December 0.362482E+09 2305.50 26-DEC-16:23 23.00 10.75 0.121819E+09 183.75 08-DEC-13:30 23.00 10.75
                     
Annual Sum or Average 0.179041E+11         0.161224E+10        
Minimum of Months 0.184818E+09 1544.76   16.50 9.89 0.114225E+09 181.47   14.37 9.61
Maximum of Months 0.288941E+10 6140.81   29.33 19.93 0.151272E+09 212.14   29.33 20.16



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27 1.81 0.00 0.00 01-JAN-00:10 4.27 1.81
February 0.00 0.00 01-FEB-00:10 11.90 4.43 0.00 0.00 01-FEB-00:10 11.90 4.43
March 0.00 0.00 01-MAR-00:10 11.85 8.83 0.00 0.00 01-MAR-00:10 11.85 8.83
April 0.00 0.00 01-APR-00:10 15.28 7.34 0.00 0.00 01-APR-00:10 15.28 7.34
May 0.00 0.00 01-MAY-00:10 19.10 7.18 0.00 0.00 01-MAY-00:10 19.10 7.18
June 0.00 0.00 01-JUN-00:10 25.83 11.09 0.00 0.00 01-JUN-00:10 25.83 11.09
July 0.00 0.00 01-JUL-00:05 27.73 14.60 0.00 0.00 01-JUL-00:10 27.73 14.60
August 0.00 0.00 01-AUG-00:10 29.40 18.35 0.00 0.00 01-AUG-00:10 29.40 18.35
September 0.00 0.00 01-SEP-00:10 26.22 16.66 0.00 0.00 01-SEP-00:10 26.22 16.66
October 0.00 0.00 01-OCT-00:10 25.15 15.51 0.00 0.00 01-OCT-00:10 25.15 15.51
November 0.00 0.00 01-NOV-00:10 17.23 10.27 0.00 0.00 01-NOV-00:10 17.23 10.27
December 0.00 0.00 01-DEC-00:10 9.20 2.98 0.00 0.00 01-DEC-00:10 9.20 2.98
                     
Annual Sum or Average 0.00         0.00        
Minimum of Months 0.00 0.00   4.27 1.81 0.00 0.00   4.27 1.81
Maximum of Months 0.00 0.00   29.40 18.35 0.00 0.00   29.40 18.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 10497967.49 5682.24 02-JAN-08:62 7.00
February 3184.88 19.36 09-FEB-18:03 18.67
March 12874202.87 647.83 20-MAR-17:12 28.27
April 42324595.27 1091.56 14-APR-17:01 34.83
May 63741220.35 1216.57 31-MAY-17:01 36.83
June 88921496.37 1562.77 28-JUN-17:01 41.83
July 64405903.70 1381.09 20-JUL-17:01 39.00
August 67822896.85 1496.96 25-AUG-17:01 40.67
September 55562286.61 1236.05 07-SEP-17:01 37.02
October 29003758.32 1003.36 06-OCT-17:01 33.67
November 3263444.27 448.65 01-NOV-17:02 25.67
December 142843.58 135.52 21-DEC-18:02 20.50
         
Annual Sum or Average 0.438564E+09      
Minimum of Months 3184.88 19.36   7.00
Maximum of Months 88921496.37 5682.24   41.83



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 22720931.99 7144.06 02-JAN-07:02 6.00
February 47123804.95 4339.61 13-FEB-07:03 8.33
March 92839406.72 9807.11 27-MAR-06:02 1.97
April 57793023.17 935.83 14-APR-17:22 34.50
May 86366450.67 1044.00 31-MAY-17:23 36.50
June 85714629.20 1267.17 28-JUN-17:11 41.67
July 60183295.48 1162.53 20-JUL-17:11 39.00
August 66535034.75 1197.25 25-AUG-17:11 40.33
September 51586834.52 1019.04 07-SEP-17:11 36.83
October 31423284.01 844.97 03-OCT-17:23 33.50
November 11488358.49 436.13 02-NOV-17:23 24.50
December 33896982.89 3056.07 20-DEC-08:62 7.00
         
Annual Sum or Average 0.647672E+09      
Minimum of Months 11488358.49 436.13   1.97
Maximum of Months 92839406.72 9807.11   41.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 36902390.52 4897.21 02-JAN-07:02 6.00
February 22618738.28 1527.67 13-FEB-08:63 10.17
March 33935902.22 5769.63 27-MAR-06:02 1.97
April 35056384.03 626.64 14-APR-17:22 34.50
May 47631397.23 682.77 31-MAY-17:23 36.50
June 53145832.39 828.87 28-JUN-17:11 41.67
July 38197683.80 752.46 20-JUL-17:11 39.00
August 43340060.91 787.23 25-AUG-17:11 40.33
September 38302075.77 687.52 07-SEP-17:11 36.83
October 26720329.80 586.54 04-OCT-17:23 33.50
November 13787223.01 340.96 02-NOV-17:23 24.50
December 12987036.26 2094.66 07-DEC-07:03 1.33
         
Annual Sum or Average 0.402625E+09      
Minimum of Months 12987036.26 340.96   1.33
Maximum of Months 53145832.39 5769.63   41.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.109972E+09 10289.63 02-JAN-06:02 4.33
February 54125521.54 4505.89 27-FEB-08:62 8.50
March 89630842.92 9633.62 27-MAR-06:02 1.97
April 51670714.43 955.09 14-APR-17:22 34.50
May 70418589.52 1042.74 31-MAY-17:23 36.50
June 82996881.82 1304.77 28-JUN-17:11 41.67
July 60073930.62 1177.19 20-JUL-17:11 39.00
August 67307279.40 1240.32 25-AUG-17:11 40.33
September 56775503.09 1069.03 07-SEP-17:11 36.83
October 36985813.79 888.29 04-OCT-17:23 33.50
November 16443042.18 1546.29 24-NOV-08:62 7.33
December 42197443.91 6359.29 18-DEC-07:03 3.33
         
Annual Sum or Average 0.738598E+09      
Minimum of Months 16443042.18 888.29   1.97
Maximum of Months 0.109972E+09 10289.63   41.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 57559441.75 5713.75 02-JAN-07:02 6.00
February 57520600.31 2161.25 13-FEB-08:63 10.17
March 71890367.45 5559.41 27-MAR-06:02 1.97
April 35715301.37 631.11 14-APR-17:22 34.50
May 39266987.75 699.13 31-MAY-17:23 36.50
June 23407805.19 836.72 28-JUN-17:11 41.67
July 28581136.96 781.36 18-JUL-17:23 38.00
August 27647303.27 791.13 25-AUG-17:11 40.33
September 30982511.60 694.60 07-SEP-17:11 36.83
October 27399155.33 638.81 03-OCT-17:23 33.50
November 20172828.86 495.65 01-NOV-07:04 19.83
December 32897673.96 2079.64 18-DEC-08:63 5.83
         
Annual Sum or Average 0.453041E+09      
Minimum of Months 20172828.86 495.65   1.97
Maximum of Months 71890367.45 5713.75   41.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 4.27
February 0.00 0.00 01-FEB-00:10 11.90
March 0.00 0.00 01-MAR-00:10 11.85
April 0.00 0.00 01-APR-00:10 15.28
May 0.00 0.00 01-MAY-00:10 19.10
June 0.00 0.00 01-JUN-00:10 25.83
July 0.00 0.00 01-JUL-00:05 27.73
August 0.00 0.00 01-AUG-00:10 29.40
September 0.00 0.00 01-SEP-00:10 26.22
October 0.00 0.00 01-OCT-00:10 25.15
November 0.00 0.00 01-NOV-00:10 17.23
December 0.00 0.00 01-DEC-00:10 9.20
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   4.27
Maximum of Months 0.00 0.00   29.40



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.114206E+10 948.30 02-JAN-08:09 0.129836E+10 1014.68 02-JAN-08:09
February 0.103251E+10 948.30 01-FEB-08:09 0.117388E+10 1014.68 01-FEB-08:09
March 0.120245E+10 948.30 01-MAR-08:09 0.137025E+10 1014.68 01-MAR-08:09
April 0.109548E+10 948.30 03-APR-07:10 0.124598E+10 1014.68 03-APR-07:10
May 0.117226E+10 948.30 01-MAY-07:10 0.133431E+10 1014.68 01-MAY-07:10
June 0.115587E+10 948.30 01-JUN-07:10 0.131568E+10 1014.68 01-JUN-07:10
July 0.111187E+10 948.30 03-JUL-07:10 0.126352E+10 1014.68 03-JUL-07:10
August 0.120245E+10 948.30 01-AUG-07:10 0.137025E+10 1014.68 01-AUG-07:10
September 0.109548E+10 948.30 01-SEP-07:10 0.124379E+10 1014.68 01-SEP-07:10
October 0.114206E+10 948.30 02-OCT-07:10 0.129946E+10 1014.68 02-OCT-07:10
November 0.112568E+10 948.30 01-NOV-07:10 0.128083E+10 1014.68 01-NOV-07:10
December 0.111187E+10 948.30 01-DEC-08:09 0.126242E+10 1014.68 01-DEC-08:09
             
Annual Sum or Average 0.135900E+11     0.154587E+11    
Minimum of Months 0.103251E+10 948.30   0.117388E+10 1014.68  
Maximum of Months 0.120245E+10 948.30   0.137025E+10 1014.68  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.735735E+09 707.90 20-JAN-16:00 0.984244E+09 769.19 02-JAN-08:09
February 0.672983E+09 703.18 10-FEB-08:09 0.889874E+09 769.19 01-FEB-08:09
March 0.774799E+09 696.50 21-MAR-07:10 0.103874E+10 769.19 01-MAR-08:09
April 0.708069E+09 673.00 04-APR-07:10 0.944536E+09 769.19 03-APR-07:10
May 0.779209E+09 659.50 05-MAY-07:10 0.101149E+10 769.19 01-MAY-07:10
June 0.782123E+09 663.30 22-JUN-07:10 0.997370E+09 769.19 01-JUN-07:10
July 0.741414E+09 676.22 27-JUL-07:10 0.957827E+09 769.19 03-JUL-07:10
August 0.799251E+09 701.19 04-AUG-07:10 0.103874E+10 769.19 01-AUG-07:10
September 0.706016E+09 675.43 19-SEP-07:10 0.942874E+09 769.19 01-SEP-07:10
October 0.732111E+09 680.58 27-OCT-07:10 0.985075E+09 769.19 02-OCT-07:10
November 0.728051E+09 718.87 28-NOV-16:30 0.970953E+09 769.19 01-NOV-07:10
December 0.723184E+09 718.87 01-DEC-16:30 0.956997E+09 769.19 01-DEC-08:09
             
Annual Sum or Average 0.888295E+10     0.117187E+11    
Minimum of Months 0.672983E+09 659.50   0.889874E+09 769.19  
Maximum of Months 0.799251E+09 718.87   0.103874E+10 769.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.465021E+09 421.00 20-JAN-16:00 0.583867E+09 456.29 02-JAN-08:09
February 0.418480E+09 417.25 10-FEB-08:09 0.527885E+09 456.29 01-FEB-08:09
March 0.476328E+09 409.35 09-MAR-16:00 0.616194E+09 456.29 01-MAR-08:09
April 0.431129E+09 391.00 03-APR-15:00 0.560311E+09 456.29 03-APR-07:10
May 0.460700E+09 390.05 05-MAY-15:00 0.600030E+09 456.29 01-MAY-07:10
June 0.455081E+09 393.23 02-JUN-15:00 0.591653E+09 456.29 01-JUN-07:10
July 0.437046E+09 400.85 13-JUL-15:00 0.568196E+09 456.29 03-JUL-07:10
August 0.475525E+09 415.70 04-AUG-07:10 0.616194E+09 456.29 01-AUG-07:10
September 0.433309E+09 399.77 29-SEP-14:30 0.559325E+09 456.29 01-SEP-07:10
October 0.459044E+09 410.89 31-OCT-15:00 0.584359E+09 456.29 02-OCT-07:10
November 0.458518E+09 426.44 28-NOV-16:30 0.575982E+09 456.29 01-NOV-07:10
December 0.455270E+09 426.44 01-DEC-16:30 0.567703E+09 456.29 01-DEC-08:09
             
Annual Sum or Average 0.542545E+10     0.695170E+10    
Minimum of Months 0.418480E+09 390.05   0.527885E+09 456.29  
Maximum of Months 0.476328E+09 426.44   0.616194E+09 456.29  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.827561E+09 709.81 20-JAN-08:09 0.984244E+09 769.19 02-JAN-08:09
February 0.739487E+09 705.71 10-FEB-08:09 0.889874E+09 769.19 01-FEB-08:09
March 0.843110E+09 700.77 21-MAR-07:10 0.103874E+10 769.19 01-MAR-08:09
April 0.754526E+09 675.24 04-APR-07:10 0.944536E+09 769.19 03-APR-07:10
May 0.793878E+09 663.73 26-MAY-08:30 0.101149E+10 769.19 01-MAY-07:10
June 0.779694E+09 651.95 12-JUN-09:30 0.997370E+09 769.19 01-JUN-07:10
July 0.750179E+09 673.88 28-JUL-12:39 0.957827E+09 769.19 03-JUL-07:10
August 0.830120E+09 702.07 04-AUG-07:10 0.103874E+10 769.19 01-AUG-07:10
September 0.760890E+09 693.49 29-SEP-07:10 0.942874E+09 769.19 01-SEP-07:10
October 0.818346E+09 705.20 31-OCT-07:10 0.985075E+09 769.19 02-OCT-07:10
November 0.811371E+09 718.87 28-NOV-16:30 0.970953E+09 769.19 01-NOV-07:10
December 0.807829E+09 718.87 01-DEC-16:30 0.956997E+09 769.19 01-DEC-08:09
             
Annual Sum or Average 0.951699E+10     0.117187E+11    
Minimum of Months 0.739487E+09 651.95   0.889874E+09 769.19  
Maximum of Months 0.843110E+09 718.87   0.103874E+10 769.19  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.465708E+09 421.55 20-JAN-08:09 0.583867E+09 456.29 02-JAN-08:09
February 0.420021E+09 419.04 03-FEB-08:09 0.527885E+09 456.29 01-FEB-08:09
March 0.479834E+09 418.47 21-MAR-07:10 0.616194E+09 456.29 01-MAR-08:09
April 0.435267E+09 410.71 04-APR-07:10 0.560311E+09 456.29 03-APR-07:10
May 0.465042E+09 403.80 05-MAY-07:10 0.600030E+09 456.29 01-MAY-07:10
June 0.458855E+09 402.98 27-JUN-07:10 0.591653E+09 456.29 01-JUN-07:10
July 0.443977E+09 408.29 27-JUL-07:10 0.568196E+09 456.29 03-JUL-07:10
August 0.483710E+09 417.11 04-AUG-07:10 0.616194E+09 456.29 01-AUG-07:10
September 0.436433E+09 414.00 29-SEP-07:10 0.559325E+09 456.29 01-SEP-07:10
October 0.462454E+09 419.93 27-OCT-07:10 0.584359E+09 456.29 02-OCT-07:10
November 0.456083E+09 426.44 28-NOV-16:30 0.575982E+09 456.29 01-NOV-07:10
December 0.455225E+09 426.44 01-DEC-16:30 0.567703E+09 456.29 01-DEC-08:09
             
Annual Sum or Average 0.546261E+10     0.695170E+10    
Minimum of Months 0.420021E+09 402.98   0.527885E+09 456.29  
Maximum of Months 0.483710E+09 426.44   0.616194E+09 456.29  



Table of Contents

Report: SpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.711734E+09 0.114206E+10 0.129836E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.643949E+09 0.103251E+10 0.117388E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.779518E+09 0.120245E+10 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.677841E+09 0.109548E+10 0.124598E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.745626E+09 0.117226E+10 0.133431E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.745626E+09 0.115587E+10 0.131568E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.677841E+09 0.111187E+10 0.126352E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.779518E+09 0.120245E+10 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.677841E+09 0.109548E+10 0.124379E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.711734E+09 0.114206E+10 0.129946E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.711734E+09 0.112568E+10 0.128083E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.677841E+09 0.111187E+10 0.126242E+10 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.854080E+10 0.135900E+11 0.154587E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.643949E+09 0.103251E+10 0.117388E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.779518E+09 0.120245E+10 0.137025E+10 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.735735E+09 0.984244E+09 0.00 0.00 0.00 0.00 6746026.92 0.606514E+09
February 0.488155E+09 0.672983E+09 0.889874E+09 0.00 0.00 0.00 0.00 0.00 0.614426E+09
March 0.590925E+09 0.774799E+09 0.103874E+10 0.00 0.00 0.00 0.00 20791731.96 0.595061E+09
April 0.513848E+09 0.708069E+09 0.944536E+09 0.00 0.00 0.00 0.00 0.182620E+09 0.223142E+09
May 0.565233E+09 0.779209E+09 0.101149E+10 0.00 0.00 0.00 0.00 0.333233E+09 0.141056E+09
June 0.565233E+09 0.782123E+09 0.997370E+09 0.00 0.00 0.00 0.00 0.555067E+09 52571735.40
July 0.513848E+09 0.741414E+09 0.957827E+09 0.00 0.00 0.00 0.00 0.443502E+09 48780761.70
August 0.590925E+09 0.799251E+09 0.103874E+10 0.00 0.00 0.00 0.00 0.446152E+09 72058263.48
September 0.513848E+09 0.706016E+09 0.942874E+09 0.00 0.00 0.00 0.00 0.299281E+09 0.130398E+09
October 0.539540E+09 0.732111E+09 0.985075E+09 0.00 0.00 0.00 0.00 0.128602E+09 0.397307E+09
November 0.539540E+09 0.728051E+09 0.970953E+09 0.00 0.00 0.00 0.00 15012795.33 0.587485E+09
December 0.513848E+09 0.723184E+09 0.956997E+09 0.00 0.00 0.00 0.00 755609.77 0.743935E+09
                   
Annual Sum or Average 0.647448E+10 0.888295E+10 0.117187E+11 0.00 0.00 0.00 0.00 0.243176E+10 0.421273E+10
Minimum of Months 0.488155E+09 0.672983E+09 0.889874E+09 0.00 0.00 0.00 0.00 0.00 48780761.70
Maximum of Months 0.590925E+09 0.799251E+09 0.103874E+10 0.00 0.00 0.00 0.00 0.555067E+09 0.743935E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.234287E+09 0.465021E+09 0.583867E+09 0.00 0.00 0.00 0.00 522945.98 0.178107E+09
February 0.211974E+09 0.418480E+09 0.527885E+09 0.00 0.00 0.00 0.00 0.00 0.137321E+09
March 0.256600E+09 0.476328E+09 0.616194E+09 0.00 0.00 0.00 0.00 1353178.39 0.179648E+09
April 0.223130E+09 0.431129E+09 0.560311E+09 0.00 0.00 0.00 0.00 20148953.68 77500483.92
May 0.245443E+09 0.460700E+09 0.600030E+09 0.00 0.00 0.00 0.00 40224856.74 52877927.50
June 0.245443E+09 0.455081E+09 0.591653E+09 0.00 0.00 0.00 0.00 84178536.43 23588673.43
July 0.223130E+09 0.437046E+09 0.568196E+09 0.00 0.00 0.00 0.00 71155286.49 27705498.46
August 0.256600E+09 0.475525E+09 0.616194E+09 0.00 0.00 0.00 0.00 49469569.58 33537746.84
September 0.223130E+09 0.433309E+09 0.559325E+09 0.00 0.00 0.00 0.00 31663606.12 55452389.38
October 0.234287E+09 0.459044E+09 0.584359E+09 0.00 0.00 0.00 0.00 11181751.99 0.126301E+09
November 0.234287E+09 0.458518E+09 0.575982E+09 0.00 0.00 0.00 0.00 1009996.99 0.179446E+09
December 0.223130E+09 0.455270E+09 0.567703E+09 0.00 0.00 0.00 0.00 84057.97 0.179602E+09
                   
Annual Sum or Average 0.281144E+10 0.542545E+10 0.695170E+10 0.00 0.00 0.00 0.00 0.310993E+09 0.125109E+10
Minimum of Months 0.211974E+09 0.418480E+09 0.527885E+09 0.00 0.00 0.00 0.00 0.00 23588673.43
Maximum of Months 0.256600E+09 0.476328E+09 0.616194E+09 0.00 0.00 0.00 0.00 84178536.43 0.179648E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.539540E+09 0.827561E+09 0.984244E+09 0.00 0.00 0.00 0.00 1718302.43 0.247497E+09
February 0.488155E+09 0.739487E+09 0.889874E+09 0.00 0.00 0.00 0.00 0.00 0.196283E+09
March 0.590925E+09 0.843110E+09 0.103874E+10 0.00 0.00 0.00 0.00 2531672.78 0.255897E+09
April 0.513848E+09 0.754526E+09 0.944536E+09 0.00 0.00 0.00 0.00 37500169.09 0.105310E+09
May 0.565233E+09 0.793878E+09 0.101149E+10 0.00 0.00 0.00 0.00 68958268.40 72426332.47
June 0.565233E+09 0.779694E+09 0.997370E+09 0.00 0.00 0.00 0.00 0.127602E+09 33565216.15
July 0.513848E+09 0.750179E+09 0.957827E+09 0.00 0.00 0.00 0.00 0.108828E+09 39522018.32
August 0.590925E+09 0.830120E+09 0.103874E+10 0.00 0.00 0.00 0.00 76800957.69 45960772.52
September 0.513848E+09 0.760890E+09 0.942874E+09 0.00 0.00 0.00 0.00 49919504.20 77945615.10
October 0.539540E+09 0.818346E+09 0.985075E+09 0.00 0.00 0.00 0.00 19442542.98 0.176071E+09
November 0.539540E+09 0.811371E+09 0.970953E+09 0.00 0.00 0.00 0.00 2604029.55 0.255396E+09
December 0.513848E+09 0.807829E+09 0.956997E+09 0.00 0.00 0.00 0.00 447636.84 0.254977E+09
                   
Annual Sum or Average 0.647448E+10 0.951699E+10 0.117187E+11 0.00 0.00 0.00 0.00 0.496353E+09 0.176085E+10
Minimum of Months 0.488155E+09 0.739487E+09 0.889874E+09 0.00 0.00 0.00 0.00 0.00 33565216.15
Maximum of Months 0.590925E+09 0.843110E+09 0.103874E+10 0.00 0.00 0.00 0.00 0.127602E+09 0.255897E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.320062E+09 0.465708E+09 0.583867E+09 0.00 0.00 0.00 0.00 652188.65 0.182564E+09
February 0.289580E+09 0.420021E+09 0.527885E+09 0.00 0.00 0.00 0.00 0.00 0.138010E+09
March 0.350544E+09 0.479834E+09 0.616194E+09 0.00 0.00 0.00 0.00 1366803.43 0.182812E+09
April 0.304821E+09 0.435267E+09 0.560311E+09 0.00 0.00 0.00 0.00 17968029.45 84500509.19
May 0.335303E+09 0.465042E+09 0.600030E+09 0.00 0.00 0.00 0.00 37200501.57 56743480.46
June 0.335303E+09 0.458855E+09 0.591653E+09 0.00 0.00 0.00 0.00 79833647.64 25224601.26
July 0.304821E+09 0.443977E+09 0.568196E+09 0.00 0.00 0.00 0.00 69303106.62 28812761.09
August 0.350544E+09 0.483710E+09 0.616194E+09 0.00 0.00 0.00 0.00 48014015.12 34196239.15
September 0.304821E+09 0.436433E+09 0.559325E+09 0.00 0.00 0.00 0.00 30201191.29 57153660.34
October 0.320062E+09 0.462454E+09 0.584359E+09 0.00 0.00 0.00 0.00 11230245.84 0.129818E+09
November 0.320062E+09 0.456083E+09 0.575982E+09 0.00 0.00 0.00 0.00 1099553.22 0.183601E+09
December 0.304821E+09 0.455225E+09 0.567703E+09 0.00 0.00 0.00 0.00 86852.52 0.180657E+09
                   
Annual Sum or Average 0.384075E+10 0.546261E+10 0.695170E+10 0.00 0.00 0.00 0.00 0.296956E+09 0.128409E+10
Minimum of Months 0.289580E+09 0.420021E+09 0.527885E+09 0.00 0.00 0.00 0.00 0.00 25224601.26
Maximum of Months 0.350544E+09 0.483710E+09 0.616194E+09 0.00 0.00 0.00 0.00 79833647.64 0.183601E+09



Table of Contents

Report: SpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.139185E+10 0.235199E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.794331E+09 0.239344E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.930475E+09 0.319442E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.120782E+10 0.438693E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.130059E+10 0.466988E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.108673E+10 0.469332E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.767210E+09 0.421809E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.964913E+09 0.393906E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.840159E+09 0.316030E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.133079E+10 0.290663E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.114879E+10 0.236746E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.148708E+10 0.209729E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.132508E+11 0.403788E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.767210E+09 0.209729E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.148708E+10 0.469332E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 966.54 02-JAN-08:09 948.30 02-JAN-08:09 1014.68 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 966.54 01-FEB-08:09 948.30 01-FEB-08:09 1014.68 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 966.54 01-MAR-08:09 948.30 01-MAR-08:09 1014.68 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 966.54 03-APR-07:10 948.30 03-APR-07:10 1014.68 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 966.54 01-MAY-07:10 948.30 01-MAY-07:10 1014.68 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 966.54 01-JUN-07:10 948.30 01-JUN-07:10 1014.68 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 966.54 03-JUL-07:10 948.30 03-JUL-07:10 1014.68 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 966.54 01-AUG-07:10 948.30 01-AUG-07:10 1014.68 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 966.54 01-SEP-07:10 948.30 01-SEP-07:10 1014.68 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 966.54 02-OCT-07:10 948.30 02-OCT-07:10 1014.68 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 966.54 01-NOV-07:10 948.30 01-NOV-07:10 1014.68 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 966.54 01-DEC-08:09 948.30 01-DEC-08:09 1014.68 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 966.54   948.30   1014.68   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 966.54   948.30   1014.68   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 707.90 20-JAN-16:00 769.19 02-JAN-08:09 0.00 0.00 0.00 0.00 631.86 31-JAN-17:10 2497.48 12-JAN-07:03
February 732.70 01-FEB-08:09 703.18 10-FEB-08:09 769.19 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2596.75 01-FEB-07:03
March 732.70 01-MAR-08:09 696.50 21-MAR-07:10 769.19 01-MAR-08:09 0.00 0.00 0.00 0.00 695.22 20-MAR-17:00 2827.40 27-MAR-06:10
April 732.70 03-APR-07:10 673.00 04-APR-07:10 769.19 03-APR-07:10 0.00 0.00 0.00 0.00 1552.44 14-APR-16:10 1939.89 21-APR-06:05
May 732.70 01-MAY-07:10 659.50 05-MAY-07:10 769.19 01-MAY-07:10 0.00 0.00 0.00 0.00 1846.19 31-MAY-16:10 1705.95 01-MAY-06:03
June 732.70 01-JUN-07:10 663.30 22-JUN-07:10 769.19 01-JUN-07:10 0.00 0.00 0.00 0.00 2487.67 28-JUN-16:03 949.85 21-JUN-06:02
July 732.70 03-JUL-07:10 676.22 27-JUL-07:10 769.19 03-JUL-07:10 0.00 0.00 0.00 0.00 2164.27 20-JUL-17:00 666.63 03-JUL-06:01
August 732.70 01-AUG-07:10 701.19 04-AUG-07:10 769.19 01-AUG-07:10 0.00 0.00 0.00 0.00 2353.50 25-AUG-16:03 942.61 24-AUG-06:02
September 732.70 01-SEP-07:10 675.43 19-SEP-07:10 769.19 01-SEP-07:10 0.00 0.00 0.00 0.00 1936.38 08-SEP-16:03 1298.04 22-SEP-06:03
October 732.70 02-OCT-07:10 680.58 27-OCT-07:10 769.19 02-OCT-07:10 0.00 0.00 0.00 0.00 1491.00 03-OCT-16:05 2678.06 25-OCT-06:03
November 732.70 01-NOV-07:10 718.87 28-NOV-16:30 769.19 01-NOV-07:10 0.00 0.00 0.00 0.00 550.53 01-NOV-16:10 2615.11 24-NOV-07:03
December 732.70 01-DEC-08:09 718.87 01-DEC-16:30 769.19 01-DEC-08:09 0.00 0.00 0.00 0.00 49.66 21-DEC-14:55 3263.42 05-DEC-07:03
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   659.50   769.19   0.00 0.00 0.00 0.00 0.00   666.63  
Maximum of Months 732.70   718.87   769.19   0.00 0.00 0.00 0.00 2487.67   3263.42  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 421.00 20-JAN-16:00 456.29 02-JAN-08:09 0.00 0.00 0.00 0.00 10.69 31-JAN-14:00 255.13 01-JAN-01:00
February 434.65 01-FEB-08:09 417.25 10-FEB-08:09 456.29 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 349.71 02-FEB-23:00
March 434.65 01-MAR-08:09 409.35 09-MAR-16:00 456.29 01-MAR-08:09 0.00 0.00 0.00 0.00 22.78 15-MAR-12:55 295.34 28-MAR-04:00
April 434.65 03-APR-07:10 391.00 03-APR-15:00 456.29 03-APR-07:10 0.00 0.00 0.00 0.00 108.84 30-APR-14:53 224.31 16-APR-09:00
May 434.65 01-MAY-07:10 390.05 05-MAY-15:00 456.29 01-MAY-07:10 0.00 0.00 0.00 0.00 154.37 31-MAY-18:10 150.24 23-MAY-05:00
June 434.65 01-JUN-07:10 393.23 02-JUN-15:00 456.29 01-JUN-07:10 0.00 0.00 0.00 0.00 263.13 30-JUN-18:10 107.49 13-JUN-06:00
July 434.65 03-JUL-07:10 400.85 13-JUL-15:00 456.29 03-JUL-07:10 0.00 0.00 0.00 0.00 280.09 22-JUL-17:47 178.77 17-JUL-19:52
August 434.65 01-AUG-07:10 415.70 04-AUG-07:10 456.29 01-AUG-07:10 0.00 0.00 0.00 0.00 257.47 13-AUG-15:58 233.39 05-AUG-17:01
September 434.65 01-SEP-07:10 399.77 29-SEP-14:30 456.29 01-SEP-07:10 0.00 0.00 0.00 0.00 152.29 17-SEP-12:20 173.17 03-SEP-05:00
October 434.65 02-OCT-07:10 410.89 31-OCT-15:00 456.29 02-OCT-07:10 0.00 0.00 0.00 0.00 102.08 01-OCT-14:10 371.93 22-OCT-13:52
November 434.65 01-NOV-07:10 426.44 28-NOV-16:30 456.29 01-NOV-07:10 0.00 0.00 0.00 0.00 18.37 19-NOV-14:55 324.73 29-NOV-02:00
December 434.65 01-DEC-08:09 426.44 01-DEC-16:30 456.29 01-DEC-08:09 0.00 0.00 0.00 0.00 6.65 25-DEC-14:00 267.22 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   390.05   456.29   0.00 0.00 0.00 0.00 0.00   107.49  
Maximum of Months 434.65   426.44   456.29   0.00 0.00 0.00 0.00 280.09   371.93  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 732.70 02-JAN-08:09 709.81 20-JAN-08:09 769.19 02-JAN-08:09 0.00 0.00 0.00 0.00 53.20 16-JAN-11:53 346.40 01-JAN-01:00
February 732.70 01-FEB-08:09 705.71 10-FEB-08:09 769.19 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 506.25 02-FEB-23:00
March 732.70 01-MAR-08:09 700.77 21-MAR-07:10 769.19 01-MAR-08:09 0.00 0.00 0.00 0.00 34.70 18-MAR-17:02 430.30 28-MAR-04:00
April 732.70 03-APR-07:10 675.24 04-APR-07:10 769.19 03-APR-07:10 0.00 0.00 0.00 0.00 225.90 30-APR-14:53 261.52 21-APR-06:00
May 732.70 01-MAY-07:10 663.73 26-MAY-08:30 769.19 01-MAY-07:10 0.00 0.00 0.00 0.00 234.32 31-MAY-18:10 222.88 23-MAY-05:00
June 732.70 01-JUN-07:10 651.95 12-JUN-09:30 769.19 01-JUN-07:10 0.00 0.00 0.00 0.00 397.10 30-JUN-18:10 154.13 13-JUN-06:00
July 732.70 03-JUL-07:10 673.88 28-JUL-12:39 769.19 03-JUL-07:10 0.00 0.00 0.00 0.00 420.13 22-JUL-17:50 255.82 17-JUL-19:52
August 732.70 01-AUG-07:10 702.07 04-AUG-07:10 769.19 01-AUG-07:10 0.00 0.00 0.00 0.00 386.21 13-AUG-15:58 325.32 05-AUG-17:01
September 732.70 01-SEP-07:10 693.49 29-SEP-07:10 769.19 01-SEP-07:10 0.00 0.00 0.00 0.00 228.55 17-SEP-12:35 252.04 03-SEP-05:00
October 732.70 02-OCT-07:10 705.20 31-OCT-07:10 769.19 02-OCT-07:10 0.00 0.00 0.00 0.00 157.13 01-OCT-14:07 503.27 22-OCT-13:52
November 732.70 01-NOV-07:10 718.87 28-NOV-16:30 769.19 01-NOV-07:10 0.00 0.00 0.00 0.00 77.58 19-NOV-14:55 471.48 29-NOV-02:00
December 732.70 01-DEC-08:09 718.87 01-DEC-16:30 769.19 01-DEC-08:09 0.00 0.00 0.00 0.00 32.46 25-DEC-14:00 392.59 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 732.70   651.95   769.19   0.00 0.00 0.00 0.00 0.00   154.13  
Maximum of Months 732.70   718.87   769.19   0.00 0.00 0.00 0.00 420.13   506.25  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 434.65 02-JAN-08:09 421.55 20-JAN-08:09 456.29 02-JAN-08:09 0.00 0.00 0.00 0.00 21.13 16-JAN-11:53 263.58 01-JAN-01:00
February 434.65 01-FEB-08:09 419.04 03-FEB-08:09 456.29 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 361.96 02-FEB-23:00
March 434.65 01-MAR-08:09 418.47 21-MAR-07:10 456.29 01-MAR-08:09 0.00 0.00 0.00 0.00 22.78 15-MAR-12:55 299.84 28-MAR-04:00
April 434.65 03-APR-07:10 410.71 04-APR-07:10 456.29 03-APR-07:10 0.00 0.00 0.00 0.00 123.14 30-APR-13:00 235.01 26-APR-18:02
May 434.65 01-MAY-07:10 403.80 05-MAY-07:10 456.29 01-MAY-07:10 0.00 0.00 0.00 0.00 128.75 31-MAY-18:16 156.20 23-MAY-05:00
June 434.65 01-JUN-07:10 402.98 27-JUN-07:10 456.29 01-JUN-07:10 0.00 0.00 0.00 0.00 258.43 30-JUN-18:08 109.04 13-JUN-06:00
July 434.65 03-JUL-07:10 408.29 27-JUL-07:10 456.29 03-JUL-07:10 0.00 0.00 0.00 0.00 280.09 22-JUL-17:50 180.75 17-JUL-19:52
August 434.65 01-AUG-07:10 417.11 04-AUG-07:10 456.29 01-AUG-07:10 0.00 0.00 0.00 0.00 257.47 13-AUG-15:55 233.20 05-AUG-17:01
September 434.65 01-SEP-07:10 414.00 29-SEP-07:10 456.29 01-SEP-07:10 0.00 0.00 0.00 0.00 153.10 17-SEP-11:55 171.85 03-SEP-05:00
October 434.65 02-OCT-07:10 419.93 27-OCT-07:10 456.29 02-OCT-07:10 0.00 0.00 0.00 0.00 105.09 01-OCT-14:07 346.64 22-OCT-13:52
November 434.65 01-NOV-07:10 426.44 28-NOV-16:30 456.29 01-NOV-07:10 0.00 0.00 0.00 0.00 27.20 19-NOV-13:00 326.45 29-NOV-02:00
December 434.65 01-DEC-08:09 426.44 01-DEC-16:30 456.29 01-DEC-08:09 0.00 0.00 0.00 0.00 9.32 25-DEC-14:00 267.69 07-DEC-02:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 434.65   402.98   456.29   0.00 0.00 0.00 0.00 0.00   109.04  
Maximum of Months 434.65   426.44   456.29   0.00 0.00 0.00 0.00 280.09   361.96  



Table of Contents

Report: PeakSpaceGainsMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1736.12 28-JAN-07:53 4635.75 09-JAN-13:10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1401.81 02-FEB-06:00 5694.15 28-FEB-13:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1456.91 26-MAR-07:12 6167.67 26-MAR-12:50
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1656.08 22-APR-06:42 6447.10 27-APR-12:50
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1693.15 14-MAY-06:32 6293.64 27-MAY-12:50
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1474.01 16-JUN-06:01 6156.36 25-JUN-12:50
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1599.84 03-JUL-06:01 6157.40 27-JUL-13:20
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1597.16 25-AUG-06:33 5960.06 07-AUG-13:40
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1686.20 17-SEP-04:55 5592.79 07-SEP-13:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1575.72 14-OCT-01:00 5439.88 26-OCT-12:40
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1509.54 27-NOV-08:62 5102.45 14-NOV-13:10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1832.01 21-DEC-07:05 4258.51 14-DEC-13:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1401.81   4258.51  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1832.01   6447.10  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 4544.14 27-JAN-08:63 2899.62 2844.90 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
February 2669.79 10-FEB-08:63 2899.62 2844.90 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
March 6565.51 21-MAR-07:03 3866.15 3793.20 4058.71 0.00 0.00 0.00 0.00 0.00 0.00
April 6818.43 07-APR-07:02 4832.69 4741.50 5073.39 0.00 0.00 0.00 0.00 0.00 0.00
May 6776.65 22-MAY-06:02 1217.84 2655.21 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
June 6849.90 26-JUN-05:02 637.92 1454.08 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
July 6998.50 03-JUL-05:02 637.92 1454.08 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
August 6727.63 23-AUG-06:01 1420.81 3097.74 3551.37 0.00 0.00 0.00 0.00 0.00 0.00
September 6661.04 28-SEP-06:02 1217.84 2655.21 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
October 7051.26 12-OCT-07:02 4832.69 4741.50 5073.39 0.00 0.00 0.00 0.00 0.00 0.00
November 6719.83 06-NOV-08:62 4832.69 4741.50 5073.39 0.00 0.00 0.00 0.00 0.00 0.00
December 4043.56 26-DEC-08:62 3866.15 3793.20 4058.71 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2669.79   637.92 1454.08 3044.03 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7051.26   4832.69 4741.50 5073.39 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5388.37 30-JAN-14:40 732.70 546.42 769.19 0.00 0.00 0.00 0.00 18.87 0.00
February 3569.28 01-FEB-15:30 1465.40 1092.83 1538.38 0.00 0.00 0.00 0.00 0.00 194.63
March 3293.37 20-MAR-14:30 732.70 546.42 769.19 0.00 0.00 0.00 0.00 88.56 0.00
April 7132.45 26-APR-07:02 3663.49 3110.81 3845.96 0.00 0.00 0.00 0.00 0.00 72.59
May 7342.37 08-MAY-06:01 1077.07 2253.05 2692.17 0.00 0.00 0.00 0.00 0.00 847.03
June 7540.16 19-JUN-05:02 483.58 1102.29 2307.57 0.00 0.00 0.00 0.00 0.00 200.80
July 7501.20 31-JUL-05:02 483.58 1102.29 2307.57 0.00 0.00 0.00 0.00 0.00 88.78
August 7654.60 21-AUG-05:02 483.58 1102.29 2307.57 0.00 0.00 0.00 0.00 0.00 112.67
September 7610.69 27-SEP-06:02 923.20 2012.82 2307.57 0.00 0.00 0.00 0.00 0.00 898.75
October 7811.31 10-OCT-06:01 1077.07 2348.29 2692.17 0.00 0.00 0.00 0.00 0.00 1517.27
November 7173.95 01-NOV-07:02 3663.49 3453.98 3845.96 0.00 0.00 0.00 0.00 0.00 109.64
December 5606.15 26-DEC-13:55 1465.40 1092.83 1538.38 0.00 0.00 0.00 0.00 0.00 20.55
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3293.37   483.58 546.42 769.19 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7811.31   3663.49 3453.98 3845.96 0.00 0.00 0.00 0.00 88.56 1517.27



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1257.69 31-JAN-16:13 1303.94 1181.92 1368.88 0.00 0.00 0.00 0.00 8.97 0.00
February 900.29 23-FEB-11:04 2173.23 1620.70 2281.47 0.00 0.00 0.00 0.00 0.00 21.70
March 1466.43 23-MAR-10:43 1738.59 1296.56 1825.18 0.00 0.00 0.00 0.00 0.00 2.84
April 5025.12 17-APR-07:02 2173.23 1620.70 2281.47 0.00 0.00 0.00 0.00 0.00 15.55
May 5103.24 30-MAY-06:01 638.93 1058.85 1597.03 0.00 0.00 0.00 0.00 0.00 18.28
June 5071.49 19-JUN-05:02 286.87 653.89 1368.88 0.00 0.00 0.00 0.00 0.00 56.39
July 5248.46 30-JUL-09:02 0.00 388.98 547.55 0.00 0.00 0.00 0.00 0.00 0.85
August 5151.64 21-AUG-05:02 286.87 653.89 1368.88 0.00 0.00 0.00 0.00 0.00 27.10
September 5170.76 10-SEP-09:42 0.00 388.98 547.55 0.00 0.00 0.00 0.00 13.18 0.00
October 5258.57 10-OCT-06:01 638.93 1393.03 1597.03 0.00 0.00 0.00 0.00 0.00 24.98
November 4959.49 02-NOV-07:02 2173.23 2045.19 2281.47 0.00 0.00 0.00 0.00 0.00 16.77
December 1146.07 26-DEC-13:55 869.29 779.56 912.59 0.00 0.00 0.00 0.00 0.00 1.59
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 900.29   0.00 388.98 547.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5258.57   2173.23 2045.19 2281.47 0.00 0.00 0.00 0.00 13.18 56.39



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1542.92 27-JAN-16:27 2198.10 1964.62 2307.57 0.00 0.00 0.00 0.00 7.74 0.00
February 859.96 01-FEB-15:57 2198.10 1990.71 2307.57 0.00 0.00 0.00 0.00 0.00 21.57
March 1863.17 17-MAR-15:55 2930.79 2448.69 3076.76 0.00 0.00 0.00 0.00 14.01 0.00
April 7390.02 17-APR-07:02 3663.49 3222.68 3845.95 0.00 0.00 0.00 0.00 0.00 23.22
May 7490.47 30-MAY-06:01 1077.07 2101.79 2692.17 0.00 0.00 0.00 0.00 0.00 25.27
June 7530.55 19-JUN-05:02 483.58 1102.29 2307.57 0.00 0.00 0.00 0.00 0.00 83.41
July 7482.58 31-JUL-05:02 483.58 1102.29 2307.57 0.00 0.00 0.00 0.00 0.00 36.12
August 7626.13 21-AUG-05:02 483.58 1102.29 2307.57 0.00 0.00 0.00 0.00 0.00 38.84
September 7638.42 27-SEP-06:02 923.20 2012.82 2307.57 0.00 0.00 0.00 0.00 0.00 29.96
October 7736.95 10-OCT-06:01 1077.07 2348.29 2692.17 0.00 0.00 0.00 0.00 0.00 35.07
November 7357.64 01-NOV-07:02 3663.49 3512.47 3845.95 0.00 0.00 0.00 0.00 0.00 12.69
December 1380.95 22-DEC-16:35 2930.79 2750.62 3076.76 0.00 0.00 0.00 0.00 0.88 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 859.96   483.58 1102.29 2307.57 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7736.95   3663.49 3512.47 3845.95 0.00 0.00 0.00 0.00 14.01 83.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2204.85 31-JAN-16:55 1738.59 1296.56 1825.18 0.00 0.00 0.00 0.00 8.97 0.00
February 1544.76 22-FEB-16:33 1738.59 1296.56 1825.18 0.00 0.00 0.00 0.00 0.00 15.50
March 1891.88 16-MAR-15:57 1303.94 972.42 1368.88 0.00 0.00 0.00 0.00 16.74 0.00
April 5711.54 17-APR-07:02 2173.23 2015.94 2281.47 0.00 0.00 0.00 0.00 0.00 14.86
May 5858.29 30-MAY-06:01 638.93 1345.70 1597.03 0.00 0.00 0.00 0.00 0.00 17.85
June 5803.59 12-JUN-06:01 638.93 1349.39 1597.03 0.00 0.00 0.00 0.00 0.00 11.69
July 6140.81 16-JUL-19:12 0.00 501.74 547.55 0.00 0.00 0.00 0.00 0.00 20.33
August 5939.71 14-AUG-05:02 286.87 653.89 1368.88 0.00 0.00 0.00 0.00 0.00 19.34
September 5935.47 27-SEP-06:02 547.65 1194.03 1368.88 0.00 0.00 0.00 0.00 0.00 20.59
October 6045.93 10-OCT-06:01 638.93 1393.03 1597.03 0.00 0.00 0.00 0.00 0.00 24.91
November 5739.04 02-NOV-07:02 2173.23 2097.66 2281.47 0.00 0.00 0.00 0.00 0.00 16.77
December 2305.50 26-DEC-16:23 1303.94 972.42 1368.88 0.00 0.00 0.00 0.00 0.00 1.97
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1544.76   0.00 501.74 547.55 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6140.81   2173.23 2097.66 2281.47 0.00 0.00 0.00 0.00 16.74 24.91



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 786.20 0.00
February 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 962.13 0.00
March 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 979.60 0.00
April 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1234.66 0.00
May 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1049.41 0.00
June 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1230.10 0.00
July 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 685.43 0.00
August 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 606.95 0.00
September 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 686.15 0.00
October 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 494.76 0.00
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1306.19 0.00
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1054.08 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 494.76 0.00
Maximum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 1306.19 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.157836E+11 15279.72 31-JAN-16:40 593049.69 988.42 02-JAN-06:10
February 0.135345E+11 13460.73 22-FEB-16:10 0.00 0.00 01-FEB-00:10
March 0.159166E+11 14856.20 16-MAR-15:30 1320557.61 2200.93 27-MAR-06:10
April 0.161129E+11 17469.38 14-APR-15:30 0.00 0.00 01-APR-00:10
May 0.179817E+11 17960.45 31-MAY-15:30 0.00 0.00 01-MAY-00:10
June 0.196877E+11 20172.61 28-JUN-15:39 0.00 0.00 01-JUN-00:10
July 0.191335E+11 19722.47 10-JUL-14:50 0.00 0.00 01-JUL-00:10
August 0.208151E+11 19979.11 28-AUG-13:30 0.00 0.00 01-AUG-00:10
September 0.184688E+11 19493.49 08-SEP-15:09 0.00 0.00 01-SEP-00:10
October 0.174766E+11 19127.06 02-OCT-14:20 0.00 0.00 01-OCT-00:10
November 0.161026E+11 16419.73 01-NOV-15:30 0.00 0.00 01-NOV-00:10
December 0.151626E+11 14673.92 26-DEC-16:40 205345.56 250.73 07-DEC-07:10
             
Annual Sum or Average 0.206176E+12     2118952.86    
Minimum of Months 0.135345E+11 13460.73   0.00 0.00  
Maximum of Months 0.208151E+11 20172.61   1320557.61 2200.93  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [J] COGENERATION:ELECTRICITY []
January 0.363609E+10 0.207736E+10 0.443459E+10 0.00 0.227272E+10 0.01 41355126.52 0.126792E+10 0.00 0.00 0.00 0.205357E+10 0.00
February 0.328349E+10 0.176620E+10 0.400939E+10 0.00 0.205627E+10 0.00 17911261.34 0.546680E+09 0.00 0.00 0.00 0.185460E+10 0.00
March 0.377652E+10 0.179114E+10 0.468012E+10 0.00 0.248916E+10 0.00 51932243.65 0.106076E+10 0.00 0.00 0.00 0.206695E+10 0.00
April 0.342447E+10 0.156524E+10 0.425568E+10 0.00 0.216575E+10 0.00 0.00 0.277626E+10 0.00 0.00 0.00 0.192548E+10 0.00
May 0.367109E+10 0.147279E+10 0.455735E+10 0.00 0.238722E+10 0.00 0.00 0.391676E+10 0.00 0.00 0.00 0.197645E+10 0.00
June 0.363162E+10 0.136498E+10 0.449372E+10 0.00 0.244044E+10 0.00 0.00 0.586553E+10 0.00 0.00 0.00 0.189139E+10 0.00
July 0.348449E+10 0.143312E+10 0.431556E+10 0.00 0.224440E+10 0.00 0.00 0.575292E+10 0.00 0.00 0.00 0.190300E+10 0.00
August 0.379106E+10 0.155214E+10 0.468012E+10 0.00 0.255220E+10 0.00 0.00 0.629135E+10 0.00 0.00 0.00 0.194819E+10 0.00
September 0.343213E+10 0.165876E+10 0.424819E+10 0.00 0.220847E+10 0.00 0.00 0.504627E+10 0.00 0.00 0.00 0.187494E+10 0.00
October 0.361402E+10 0.188938E+10 0.443833E+10 0.00 0.228615E+10 0.00 0.00 0.327181E+10 0.00 0.00 0.00 0.197690E+10 0.00
November 0.357970E+10 0.197522E+10 0.437470E+10 0.00 0.227272E+10 0.00 11952021.29 0.192981E+10 0.00 0.00 0.00 0.195855E+10 0.00
December 0.355338E+10 0.212365E+10 0.431182E+10 0.00 0.216487E+10 0.00 0.108554E+09 0.877320E+09 0.00 0.00 0.00 0.202304E+10 0.00
                           
Annual Sum or Average 0.428780E+11 0.206700E+11 0.527996E+11 0.00 0.275404E+11 0.01 0.231705E+09 0.386034E+11 0.00 0.00 0.00 0.234531E+11 0.00
Minimum of Months 0.328349E+10 0.136498E+10 0.400939E+10 0.00 0.205627E+10 0.00 0.00 0.546680E+09 0.00 0.00 0.00 0.185460E+10 0.00
Maximum of Months 0.379106E+10 0.212365E+10 0.468012E+10 0.00 0.255220E+10 0.01 0.108554E+09 0.629135E+10 0.00 0.00 0.00 0.206695E+10 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 593049.69 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 1320557.61 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 205345.56 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 2118952.86 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 1320557.61 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 3206.88 20-JAN-16:00 1574.40 01-JAN-06:10 3465.65 02-JAN-08:09 0.00 2312.49 02-JAN-06:10 0.00 20-JAN-10:30 4346.61 02-JAN-07:10
February 3193.26 10-FEB-08:09 1574.40 01-FEB-06:10 3465.65 01-FEB-08:09 0.00 2312.49 01-FEB-06:10 0.00 01-FEB-00:10 1467.64 13-FEB-07:10
March 3170.28 21-MAR-07:10 1574.40 01-MAR-06:10 3465.65 01-MAR-08:09 0.00 2312.49 01-MAR-06:10 0.00 01-MAR-00:10 2928.50 27-MAR-06:10
April 3044.51 06-APR-07:10 1574.40 01-APR-05:10 3465.65 03-APR-07:10 0.00 2312.49 03-APR-05:10 0.00 01-APR-00:10 0.00 01-APR-00:10
May 3056.45 26-MAY-08:30 1574.40 01-MAY-05:10 3465.65 01-MAY-07:10 0.00 2312.49 01-MAY-05:10 0.00 01-MAY-00:10 0.00 01-MAY-00:10
June 2987.45 07-JUN-12:30 1574.40 01-JUN-05:10 3465.65 01-JUN-07:10 0.00 2312.49 01-JUN-05:10 0.00 01-JUN-00:10 0.00 01-JUN-00:10
July 3080.34 13-JUL-15:00 1574.40 01-JUL-05:10 3465.65 03-JUL-07:10 0.00 2312.49 03-JUL-05:19 0.00 01-JUL-00:10 0.00 01-JUL-00:10
August 3184.38 04-AUG-07:10 1574.40 01-AUG-05:10 3465.65 01-AUG-07:10 0.00 2312.49 01-AUG-05:10 0.00 01-AUG-00:10 0.00 01-AUG-00:10
September 3126.81 29-SEP-07:10 1574.40 01-SEP-05:10 3465.65 01-SEP-07:10 0.00 2312.49 01-SEP-05:10 0.00 01-SEP-00:10 0.00 01-SEP-00:10
October 3158.63 27-OCT-07:10 1574.40 01-OCT-05:10 3465.65 02-OCT-07:10 0.00 2312.49 02-OCT-05:19 0.00 01-OCT-00:10 0.00 01-OCT-00:10
November 3238.93 28-NOV-16:30 1574.40 01-NOV-05:10 3465.65 01-NOV-07:10 0.00 2312.49 01-NOV-05:10 0.00 01-NOV-00:10 250.00 23-NOV-01:39
December 3238.93 01-DEC-16:30 1574.40 01-DEC-06:10 3465.65 01-DEC-08:09 0.00 2312.49 01-DEC-06:10 0.00 01-DEC-00:10 2339.52 07-DEC-07:10
                           
Annual Sum or Average             0.00            
Minimum of Months 2987.45   1574.40   3465.65   0.00 2312.49   0.00   0.00  
Maximum of Months 3238.93   1574.40   3465.65   0.00 2312.49   0.00   4346.61  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY [] HUMIDIFIER:ELECTRICITY [] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY {Maximum} [W] WATERSYSTEMS:ELECTRICITY {TIMESTAMP} COGENERATION:ELECTRICITY []
January 3876.93 31-JAN-16:30 0.00 0.00 0.00 2787.77 20-JAN-12:20 0.00
February 2056.49 22-FEB-16:30 0.00 0.00 0.00 2787.46 02-FEB-12:09 0.00
March 3523.42 16-MAR-15:00 0.00 0.00 0.00 2783.40 01-MAR-12:20 0.00
April 6100.86 14-APR-15:00 0.00 0.00 0.00 2773.68 03-APR-11:20 0.00
May 6724.15 31-MAY-15:00 0.00 0.00 0.00 2763.36 01-MAY-11:30 0.00
June 8866.66 28-JUN-15:00 0.00 0.00 0.00 2752.94 01-JUN-11:09 0.00
July 8480.93 31-JUL-15:00 0.00 0.00 0.00 2745.81 03-JUL-11:20 0.00
August 8611.48 14-AUG-15:30 0.00 0.00 0.00 2748.60 30-AUG-11:09 0.00
September 8198.86 08-SEP-15:00 0.00 0.00 0.00 2756.67 28-SEP-11:09 0.00
October 7854.49 02-OCT-14:09 0.00 0.00 0.00 2768.49 31-OCT-11:00 0.00
November 5059.89 01-NOV-14:00 0.00 0.00 0.00 2778.89 30-NOV-12:20 0.00
December 3271.28 22-DEC-16:30 0.00 0.00 0.00 2785.63 29-DEC-12:09 0.00
                 
Annual Sum or Average     0.00 0.00 0.00     0.00
Minimum of Months 2056.49   0.00 0.00 0.00 2745.81   0.00
Maximum of Months 8866.66   0.00 0.00 0.00 2787.77   0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY [] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY []
January 15279.72 31-JAN-16:40 2879.43 3465.65 0.00 0.00 2312.49 0.00 0.00 3871.21 0.00
February 13460.73 22-FEB-16:10 2887.98 3465.65 0.00 0.00 2312.49 0.00 0.00 2045.69 0.00
March 14856.20 16-MAR-15:30 2834.15 3465.65 0.00 0.00 2312.49 0.00 0.00 3498.65 0.00
April 17469.38 14-APR-15:30 2891.29 3465.65 0.00 0.00 2312.49 0.00 0.00 6061.66 0.00
May 17960.45 31-MAY-15:30 2887.45 3465.65 0.00 0.00 2312.49 0.00 0.00 6568.72 0.00
June 20172.61 28-JUN-15:39 2821.49 3465.65 0.00 0.00 2312.49 0.00 0.00 8851.21 0.00
July 19722.47 10-JUL-14:50 2837.60 3465.65 0.00 0.00 2312.49 0.00 0.00 8401.96 0.00
August 19979.11 28-AUG-13:30 3038.01 3465.65 0.00 0.00 2312.49 0.00 0.00 8457.19 0.00
September 19493.49 08-SEP-15:09 2832.56 3465.65 0.00 0.00 2312.49 0.00 0.00 8158.03 0.00
October 19127.06 02-OCT-14:20 2792.96 3465.65 0.00 0.00 2312.49 0.00 0.00 7844.66 0.00
November 16419.73 01-NOV-15:30 2876.09 3465.65 0.00 0.00 2312.49 0.00 0.00 5028.02 0.00
December 14673.92 26-DEC-16:40 2915.10 3465.65 0.00 0.00 2312.49 0.00 0.00 3231.81 0.00
                       
Annual Sum or Average           0.00         0.00
Minimum of Months 13460.73   2792.96 3465.65 0.00 0.00 2312.49 0.00 0.00 2045.69 0.00
Maximum of Months 20172.61   3038.01 3465.65 0.00 0.00 2312.49 0.00 0.00 8851.21 0.00



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [] COGENERATION:NATURALGAS []
January 0.00 0.00 988.42 02-JAN-06:10 0.00 0.00 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00
March 0.00 0.00 2200.93 27-MAR-06:10 0.00 0.00 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00
December 0.00 0.00 250.73 07-DEC-07:10 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00     0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00   0.00 0.00 0.00
Maximum of Months 0.00 0.00 2200.93   0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 24.51 0.33 24.51
June 0.00 0.00 0.00 0.00 34.33 24.82 34.17 24.81
July 0.00 0.00 0.00 0.00 76.33 24.87 75.33 24.83
August 0.00 0.00 0.00 0.00 46.67 24.86 46.67 24.86
September 0.00 0.00 0.00 0.00 29.83 25.17 28.33 25.04
October 0.00 0.00 0.00 0.00 9.67 24.62 9.67 24.62
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   197.17 24.89 194.50 24.86
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 76.33 25.17 75.33 25.04



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 7.17 25.02 6.67 24.84
July 0.00 0.00 0.00 0.00 5.00 27.51 2.33 26.58
August 0.00 0.00 0.00 0.00 10.83 26.71 6.83 25.91
September 0.00 0.00 0.00 0.00 28.50 25.85 22.33 25.32
October 0.00 0.00 0.00 0.00 18.50 26.02 14.17 25.47
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   70.00 26.06 52.33 25.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 28.50 27.51 22.33 26.58



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 12.00 30.05 0.33 29.90
July 0.00 0.00 0.00 0.00 16.50 30.10 0.33 30.00
August 0.00 0.00 0.00 0.00 17.17 29.06 2.50 28.49
September 0.00 0.00 0.00 0.00 6.17 29.89 0.33 29.62
October 0.00 0.00 0.00 0.00 0.67 30.05 0.00 30.05
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   52.50 29.72 3.50 29.41
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 17.17 30.10 2.50 30.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.67 30.06 0.00 30.06
July 0.00 0.00 0.00 0.00 4.00 29.63 0.33 29.24
August 0.00 0.00 0.00 0.00 3.67 29.39 0.50 28.81
September 0.00 0.00 0.00 0.00 1.00 29.11 0.17 28.44
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   10.33 29.56 1.00 29.12
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 4.00 30.06 0.50 30.06



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.50 30.09 0.00 30.09
May 0.00 0.00 0.00 0.00 3.50 30.21 0.00 30.21
June 0.00 0.00 0.00 0.00 17.17 30.34 5.67 30.31
July 0.00 0.00 0.00 0.00 15.50 30.45 1.17 30.43
August 0.00 0.00 0.00 0.00 11.50 30.48 0.67 30.46
September 0.00 0.00 0.00 0.00 8.00 30.23 0.00 30.23
October 0.00 0.00 0.00 0.00 1.67 30.12 0.00 30.12
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   57.83 30.37 7.50 30.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 17.17 30.48 5.67 30.46



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 154.83 23.61 42.83 23.85 3.67 23.79
February 191.17 23.71 7.00 23.73 0.00 23.73
March 160.00 23.80 71.17 24.21 0.00 24.21
April 4.67 23.89 217.00 25.44 0.00 25.44
May 2.83 27.74 239.50 25.79 2.83 25.81
June 68.50 28.07 367.67 25.91 68.50 26.21
July 111.17 27.82 340.00 26.17 111.17 26.49
August 108.67 27.68 389.83 25.93 108.67 26.25
September 76.67 27.73 340.00 25.83 76.67 26.12
October 30.67 26.80 240.00 25.55 23.33 25.72
November 61.67 24.05 156.83 24.68 5.83 24.70
December 236.50 23.80 12.67 23.88 0.00 23.88
             
Annual Sum or Average 1207.33 25.07 2424.50 25.32 400.67 25.56
Minimum of Months 2.83 23.61 7.00 23.73 0.00 23.73
Maximum of Months 236.50 28.07 389.83 26.17 111.17 26.49



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 135.33 23.18 64.17 23.57 5.83 23.48
February 238.17 22.99 12.67 22.85 11.50 22.73
March 301.83 23.16 38.33 23.10 21.00 22.93
April 77.83 23.80 97.50 25.24 0.00 25.24
May 33.50 23.99 123.00 26.29 0.00 26.29
June 90.50 28.58 274.33 26.75 90.50 27.12
July 119.17 28.16 334.83 26.25 119.17 26.65
August 127.33 28.09 381.83 26.17 127.33 26.55
September 111.83 28.22 340.00 26.24 111.83 26.64
October 77.50 26.00 235.83 25.66 39.83 25.96
November 73.17 23.71 166.50 24.40 11.00 24.43
December 211.33 23.24 43.50 23.25 14.00 23.09
             
Annual Sum or Average 1597.50 24.78 2112.50 25.20 552.00 25.49
Minimum of Months 33.50 22.99 12.67 22.85 0.00 22.73
Maximum of Months 301.83 28.58 381.83 26.75 127.33 27.12



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 286.00 23.34 13.50 23.21 13.50 23.08
February 266.00 22.93 16.67 22.78 16.67 22.64
March 272.33 23.16 24.50 23.05 17.67 22.90
April 22.17 24.07 116.67 25.86 0.00 25.86
May 4.83 28.29 178.50 26.45 4.83 26.49
June 108.83 28.69 294.50 26.79 108.83 27.19
July 116.67 28.40 280.00 26.68 116.67 27.07
August 130.17 28.21 321.50 26.54 130.17 26.91
September 106.00 28.11 279.83 26.43 106.00 26.79
October 79.00 25.34 151.50 25.59 27.33 25.86
November 145.50 23.73 60.33 24.00 4.67 23.98
December 277.83 23.09 23.83 22.89 23.83 22.72
             
Annual Sum or Average 1815.33 24.63 1761.33 25.16 570.17 25.45
Minimum of Months 4.83 22.93 13.50 22.78 0.00 22.64
Maximum of Months 286.00 28.69 321.50 26.79 130.17 27.19



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 357.00 23.08 29.83 22.88 29.83 22.72
February 323.00 22.63 23.67 22.46 23.67 22.30
March 363.83 23.05 32.00 22.88 28.67 22.72
April 95.83 23.95 84.67 25.08 0.00 25.08
May 18.00 23.94 136.50 26.46 0.17 26.47
June 106.33 28.70 305.50 26.68 106.33 27.10
July 114.00 28.31 336.67 26.26 114.00 26.67
August 121.83 28.05 383.17 26.08 121.83 26.46
September 88.83 27.99 338.33 25.92 88.83 26.28
October 135.17 24.40 144.83 24.94 18.33 25.13
November 241.50 23.60 49.83 23.71 6.50 23.69
December 340.00 22.80 48.50 22.53 48.50 22.33
             
Annual Sum or Average 2305.33 24.11 1913.50 24.66 586.67 24.88
Minimum of Months 18.00 22.63 23.67 22.46 0.00 22.30
Maximum of Months 363.83 28.70 383.17 26.68 121.83 27.10



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 277.67 23.37 21.00 23.29 14.50 23.17
February 304.33 22.98 20.33 22.82 20.33 22.67
March 315.17 23.25 50.17 23.32 20.83 23.17
April 100.33 26.22 148.33 26.55 47.33 26.91
May 86.00 28.47 191.33 27.40 78.50 27.73
June 115.67 29.34 325.67 26.97 115.67 27.46
July 122.83 28.67 336.83 26.52 122.83 26.97
August 135.17 28.54 385.33 26.41 135.17 26.85
September 112.33 28.58 340.00 26.35 112.33 26.80
October 110.83 25.62 199.83 25.71 40.67 26.05
November 160.83 23.81 104.17 24.22 6.33 24.23
December 300.50 23.13 30.50 22.94 28.33 22.77
             
Annual Sum or Average 2141.67 24.98 2153.50 25.34 742.83 25.71
Minimum of Months 86.00 22.98 20.33 22.82 6.33 22.67
Maximum of Months 315.17 29.34 385.33 27.40 135.17 27.73



Table of Contents

Report: ComfortReportSimple55Monthly

For: ATTIC

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 294.00000 0.00000 0.00000 0.00000 0.00000
February 266.00000 0.00000 0.00000 0.00000 0.00000
March 322.00000 0.00000 0.00000 0.00000 0.00000
April 280.00000 0.00000 0.00000 0.00000 0.00000
May 308.00000 0.00000 0.00000 0.00000 0.00000
June 308.00000 0.00000 0.00000 0.00000 0.00000
July 280.00000 0.00000 0.00000 0.00000 0.00000
August 322.00000 0.00000 0.00000 0.00000 0.00000
September 280.00000 0.00000 0.00000 0.00000 0.00000
October 294.00000 0.00000 0.00000 0.00000 0.00000
November 294.00000 0.00000 0.00000 0.00000 0.00000
December 280.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 3528.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 266.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 322.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV [] ZONE THERMAL COMFORT FANGER MODEL PPD []
January 357.00000 0.00000 0.00000 0.00000 0.00000
February 323.00000 0.00000 0.00000 0.00000 0.00000
March 391.00000 0.00000 0.00000 0.00000 0.00000
April 340.00000 0.00000 0.00000 0.00000 0.00000
May 374.00000 0.00000 0.00000 0.00000 0.00000
June 374.00000 0.00000 0.00000 0.00000 0.00000
July 340.00000 0.00000 0.00000 0.00000 0.00000
August 391.00000 0.00000 0.00000 0.00000 0.00000
September 340.00000 0.00000 0.00000 0.00000 0.00000
October 357.00000 0.00000 0.00000 0.00000 0.00000
November 357.00000 0.00000 0.00000 0.00000 0.00000
December 340.00000 0.00000 0.00000 0.00000 0.00000
           
Annual Sum or Average 4284.00000 0.00000 0.00000 0.00000 0.00000
Minimum of Months 323.00000 0.00000 0.00000 0.00000 0.00000
Maximum of Months 391.00000 0.00000 0.00000 0.00000 0.00000



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.146111E+10 0.326380E+09 193.71 0.142775E+10 33355923.90 0.00 0.70 27-JAN-08:63 0.00 01-JAN-00:10 4306.22 27-JAN-08:63 4306.22 27-JAN-08:63 502.14 09-JAN-10:52 886.21 27-JAN-08:63 0.00
February 0.937636E+09 0.207596E+09 178.06 0.828414E+09 0.109222E+09 0.00 0.45 10-FEB-08:63 0.00 01-FEB-00:10 2699.31 10-FEB-08:63 2699.31 10-FEB-08:63 489.35 17-FEB-12:00 580.74 10-FEB-08:63 0.00
March 0.161964E+10 0.363323E+09 222.82 0.153464E+10 84999364.35 0.00 1.00 17-MAR-07:03 0.00 01-MAR-00:10 6695.44 17-MAR-07:03 6665.75 21-MAR-07:03 544.59 06-MAR-14:11 1315.22 17-MAR-07:03 0.00
April 0.302896E+10 0.708365E+09 216.27 0.302479E+10 4175359.60 0.00 1.00 03-APR-07:02 0.00 01-APR-00:10 6792.73 26-APR-06:03 6792.73 26-APR-06:03 133.05 07-APR-11:00 1371.89 25-APR-07:02 0.00
May 0.404770E+10 0.978113E+09 242.62 0.404770E+10 8779.89 0.00 1.00 01-MAY-06:03 0.00 01-MAY-00:10 6815.69 11-MAY-06:02 6815.69 11-MAY-06:02 13.00 11-MAY-09:40 1543.90 31-MAY-16:00 0.00
June 0.502759E+10 0.128677E+10 258.41 0.501179E+10 15804553.66 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 7011.73 20-JUN-05:03 7011.73 20-JUN-05:03 806.57 30-JUN-07:40 1792.68 28-JUN-15:57 0.00
July 0.511773E+10 0.123679E+10 247.09 0.460887E+10 0.508857E+09 0.00 1.00 03-JUL-05:02 0.00 01-JUL-00:05 7555.40 14-JUL-06:02 7023.62 03-JUL-05:02 2700.26 14-JUL-06:15 1770.53 19-JUL-13:30 0.00
August 0.570143E+10 0.137796E+10 280.60 0.509946E+10 0.601972E+09 0.00 1.00 01-AUG-05:03 0.00 01-AUG-00:10 7395.24 10-AUG-06:01 6989.34 14-AUG-05:02 2236.41 04-AUG-07:10 1739.70 25-AUG-16:00 0.00
September 0.473433E+10 0.110654E+10 235.79 0.423986E+10 0.494469E+09 0.00 1.00 01-SEP-06:01 0.00 01-SEP-00:10 7413.36 05-SEP-05:01 7002.47 18-SEP-05:02 1957.65 14-SEP-07:10 1714.80 08-SEP-15:00 0.00
October 0.338452E+10 0.767395E+09 226.62 0.323930E+10 0.145222E+09 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 7301.88 03-OCT-06:02 7059.83 02-OCT-05:02 1766.51 03-OCT-06:15 1648.86 02-OCT-13:57 0.00
November 0.222065E+10 0.486441E+09 214.37 0.205567E+10 0.164981E+09 0.00 1.00 01-NOV-07:02 0.00 01-NOV-00:10 7195.30 14-NOV-08:62 6666.02 20-NOV-08:62 2402.65 14-NOV-08:04 1400.22 14-NOV-08:62 0.00
December 0.109038E+10 0.241466E+09 189.88 0.108049E+10 9883474.36 0.00 0.58 26-DEC-08:62 0.00 01-DEC-00:10 3507.51 26-DEC-08:62 3507.51 26-DEC-08:62 303.75 13-DEC-11:35 735.39 26-DEC-08:62 0.00
                                       
Annual Sum or Average 0.383717E+11 0.908713E+10 2706.24 0.361987E+11 0.217295E+10 0.00                         0.00
Minimum of Months 0.937636E+09 0.207596E+09 178.06 0.828414E+09 8779.89 0.00 0.45   0.00   2699.31   2699.31   13.00   580.74   0.00
Maximum of Months 0.570143E+10 0.137796E+10 280.60 0.509946E+10 0.601972E+09 0.00 1.00   0.00   7555.40   7059.83   2700.26   1792.68   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.229293E+10 0.500787E+09 193.81 0.228741E+10 5516211.44 0.00 0.80 30-JAN-14:40 0.00 01-JAN-00:10 5961.12 30-JAN-14:40 5961.12 30-JAN-14:40 473.05 09-JAN-11:02 1325.61 31-JAN-16:00 0.00
February 0.807909E+09 0.177778E+09 136.77 0.787338E+09 20570936.12 0.00 0.51 01-FEB-15:30 0.00 01-FEB-00:10 3646.14 01-FEB-15:30 3646.14 01-FEB-15:30 297.70 16-FEB-11:55 775.51 01-FEB-15:30 0.00
March 0.115071E+10 0.263941E+09 174.40 0.114588E+10 4823591.52 0.00 0.57 16-MAR-15:20 0.00 01-MAR-00:10 4037.54 16-MAR-15:30 4037.54 16-MAR-15:30 140.83 06-MAR-16:15 984.95 16-MAR-15:30 0.00
April 0.262028E+10 0.640609E+09 199.09 0.262028E+10 0.00 0.00 1.00 24-APR-07:02 0.00 01-APR-00:10 7971.79 26-APR-07:02 7971.79 26-APR-07:02 0.00 05-APR-09:21 1642.40 25-APR-07:02 0.00
May 0.334336E+10 0.853401E+09 225.52 0.334336E+10 0.00 0.00 1.00 02-MAY-07:02 0.00 01-MAY-00:10 8006.72 08-MAY-06:01 8006.72 08-MAY-06:01 0.00 10-MAY-09:10 1721.82 31-MAY-16:07 0.00
June 0.490857E+10 0.132120E+10 274.15 0.490121E+10 7352978.25 0.00 1.00 01-JUN-07:02 0.00 01-JUN-00:10 8248.46 19-JUN-05:02 8248.46 19-JUN-05:02 682.65 30-JUN-07:14 2118.86 28-JUN-16:17 0.00
July 0.530616E+10 0.133817E+10 281.23 0.489726E+10 0.408905E+09 0.00 1.00 03-JUL-06:01 0.00 01-JUL-00:05 9278.36 14-JUL-06:02 8374.62 31-JUL-05:02 3849.03 14-JUL-06:03 2074.54 19-JUL-13:45 0.00
August 0.597439E+10 0.150394E+10 307.50 0.551392E+10 0.460478E+09 0.00 1.00 01-AUG-06:01 0.00 01-AUG-00:10 8971.80 10-AUG-06:01 8507.28 14-AUG-05:02 3036.51 04-AUG-07:13 2105.05 27-AUG-16:32 0.00
September 0.536144E+10 0.129233E+10 278.79 0.496019E+10 0.401246E+09 0.00 1.00 01-SEP-06:01 0.00 01-SEP-00:10 9017.46 11-SEP-05:01 8346.30 27-SEP-06:02 2723.31 05-SEP-07:06 2056.07 09-SEP-13:52 0.00
October 0.407080E+10 0.934906E+09 244.47 0.398901E+10 81795556.21 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 8867.32 03-OCT-06:02 8569.21 02-OCT-05:02 2334.79 03-OCT-07:06 1974.28 02-OCT-14:00 0.00
November 0.291001E+10 0.631098E+09 206.96 0.282102E+10 88985002.40 0.00 1.00 01-NOV-07:02 0.00 01-NOV-00:10 8276.10 01-NOV-07:02 7901.76 01-NOV-07:02 1256.84 14-NOV-13:05 1643.41 01-NOV-14:55 0.00
December 0.165726E+10 0.357302E+09 171.45 0.165573E+10 1520963.49 0.00 0.81 26-DEC-13:55 0.00 01-DEC-00:10 6089.32 26-DEC-13:55 6089.32 26-DEC-13:55 184.51 13-DEC-10:53 1273.70 26-DEC-14:00 0.00
                                       
Annual Sum or Average 0.404038E+11 0.981546E+10 2694.16 0.389226E+11 0.148119E+10 0.00                         0.00
Minimum of Months 0.807909E+09 0.177778E+09 136.77 0.787338E+09 0.00 0.00 0.51   0.00   3646.14   3646.14   0.00   775.51   0.00
Maximum of Months 0.597439E+10 0.150394E+10 307.50 0.551392E+10 0.460478E+09 0.00 1.00   0.00   9278.36   8569.21   3849.03   2118.86   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.639683E+09 0.146806E+09 181.31 0.637293E+09 2390179.29 0.00 0.39 31-JAN-16:13 0.00 01-JAN-00:10 1803.02 31-JAN-16:20 1803.02 31-JAN-16:20 182.96 09-JAN-10:00 457.25 31-JAN-16:13 0.00
February 0.273160E+09 61762588.10 143.04 0.263305E+09 9855081.17 0.00 0.22 23-FEB-11:02 0.00 01-FEB-00:10 1068.34 23-FEB-11:02 1021.89 23-FEB-11:04 139.79 16-FEB-11:13 238.78 23-FEB-11:02 0.00
March 0.635502E+09 0.147226E+09 194.33 0.633349E+09 2152917.78 0.00 0.39 20-MAR-15:32 0.00 01-MAR-00:10 1884.63 20-MAR-15:13 1884.63 20-MAR-15:13 81.29 06-MAR-16:15 466.07 20-MAR-15:55 0.00
April 0.190315E+10 0.458481E+09 210.61 0.190315E+10 -0.0 0.00 1.00 03-APR-07:02 0.00 01-APR-00:10 5545.64 25-APR-06:02 5545.64 25-APR-06:02 0.00 14-APR-10:13 1124.86 25-APR-07:02 0.00
May 0.258164E+10 0.645407E+09 247.83 0.258164E+10 -0.0 0.00 1.00 01-MAY-07:02 0.00 01-MAY-00:10 5571.76 30-MAY-06:01 5571.76 30-MAY-06:01 0.00 02-MAY-16:37 1123.64 10-MAY-07:02 0.00
June 0.369913E+10 0.984197E+09 324.90 0.369612E+10 3005480.14 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 5668.75 18-JUN-08:42 5668.75 18-JUN-08:42 320.02 30-JUN-08:10 1398.13 18-JUN-12:42 0.00
July 0.378621E+10 0.958259E+09 336.01 0.357548E+10 0.210733E+09 0.00 1.00 02-JUL-09:22 0.00 01-JUL-00:05 6347.25 14-JUL-06:02 5827.47 30-JUL-09:02 2546.85 14-JUL-06:03 1432.78 16-JUL-14:41 0.00
August 0.405208E+10 0.102478E+10 327.28 0.382299E+10 0.229094E+09 0.00 1.00 01-AUG-06:01 0.00 01-AUG-00:10 6163.95 10-AUG-06:01 5847.00 14-AUG-05:02 1813.18 10-AUG-06:03 1443.12 27-AUG-16:53 0.00
September 0.322499E+10 0.786686E+09 278.22 0.302497E+10 0.200022E+09 0.00 1.00 01-SEP-06:01 0.00 01-SEP-00:10 6186.31 11-SEP-05:01 5829.66 10-SEP-10:22 1441.93 12-SEP-06:03 1346.38 10-SEP-11:02 0.00
October 0.209495E+10 0.492666E+09 229.85 0.205439E+10 40556136.06 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 6071.69 03-OCT-06:02 5869.55 02-OCT-05:02 1361.01 03-OCT-07:13 1250.60 02-OCT-11:00 0.00
November 0.111854E+10 0.252743E+09 208.92 0.107780E+10 40744663.10 0.00 1.00 01-NOV-07:02 0.00 01-NOV-00:10 6032.56 13-NOV-08:62 5611.31 01-NOV-07:02 2156.54 13-NOV-08:62 1167.22 13-NOV-08:62 0.00
December 0.420736E+09 95145310.37 160.83 0.419979E+09 756969.04 0.00 0.33 22-DEC-15:10 0.00 01-DEC-00:10 1524.48 22-DEC-15:15 1524.48 22-DEC-15:15 70.80 13-DEC-10:00 364.68 22-DEC-15:10 0.00
                                       
Annual Sum or Average 0.244298E+11 0.605416E+10 2843.13 0.236905E+11 0.739310E+09 0.00                         0.00
Minimum of Months 0.273160E+09 61762588.10 143.04 0.263305E+09 -0.0 0.00 0.22   0.00   1068.34   1021.89   0.00   238.78   0.00
Maximum of Months 0.405208E+10 0.102478E+10 336.01 0.382299E+10 0.229094E+09 0.00 1.00   0.00   6347.25   5869.55   2546.85   1443.12   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.563007E+09 0.131257E+09 142.14 0.560380E+09 2626360.91 0.00 0.35 31-JAN-17:00 0.00 01-JAN-00:10 2321.57 31-JAN-16:42 2321.57 31-JAN-16:42 149.32 09-JAN-11:53 592.23 31-JAN-16:55 0.00
February 0.155569E+09 35317452.70 73.89 0.143608E+09 11960442.25 0.00 0.18 16-FEB-15:55 0.00 01-FEB-00:10 1267.90 16-FEB-15:55 1170.11 22-FEB-16:00 192.82 16-FEB-13:13 285.27 16-FEB-15:55 0.00
March 0.615706E+09 0.144879E+09 149.16 0.611357E+09 4349228.91 0.00 0.37 16-MAR-15:53 0.00 01-MAR-00:10 2595.20 16-MAR-15:57 2595.20 16-MAR-15:57 114.13 17-MAR-10:50 651.88 16-MAR-15:57 0.00
April 0.215767E+10 0.533224E+09 203.67 0.215767E+10 0.00 0.00 1.00 05-APR-07:02 0.00 01-APR-00:10 8042.54 17-APR-07:02 8042.54 17-APR-07:02 0.00 18-APR-10:38 1635.42 25-APR-07:02 0.00
May 0.318319E+10 0.812409E+09 239.09 0.318319E+10 0.00 0.00 1.00 01-MAY-07:02 0.00 01-MAY-00:10 8030.96 30-MAY-06:01 8030.96 30-MAY-06:01 0.00 04-MAY-10:15 1633.95 10-MAY-07:02 0.00
June 0.476804E+10 0.128349E+10 283.40 0.476225E+10 5797984.68 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 8221.15 19-JUN-05:02 8221.15 19-JUN-05:02 463.32 30-JUN-08:10 2036.90 28-JUN-15:00 0.00
July 0.506324E+10 0.128372E+10 285.04 0.471254E+10 0.350698E+09 0.00 1.00 02-JUL-18:42 0.00 01-JUL-00:05 9235.07 14-JUL-06:02 8345.11 31-JUL-05:02 3742.23 14-JUL-06:03 2038.18 23-JUL-13:02 0.00
August 0.540580E+10 0.137334E+10 304.27 0.501542E+10 0.390381E+09 0.00 1.00 01-AUG-06:01 0.00 01-AUG-00:10 8941.16 10-AUG-06:01 8471.43 14-AUG-05:02 2686.07 10-AUG-06:03 2095.77 27-AUG-16:53 0.00
September 0.438478E+10 0.107287E+10 246.93 0.405360E+10 0.331183E+09 0.00 1.00 01-SEP-06:01 0.00 01-SEP-00:10 8971.51 11-SEP-05:01 8316.55 27-SEP-06:02 2366.15 05-SEP-06:13 1835.93 10-SEP-15:22 0.00
October 0.250109E+10 0.599244E+09 220.34 0.242980E+10 71288139.64 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 8829.00 03-OCT-06:02 8509.34 02-OCT-05:02 2102.28 03-OCT-07:13 1793.06 02-OCT-14:00 0.00
November 0.125163E+10 0.285845E+09 194.28 0.117961E+10 72025812.58 0.00 1.00 01-NOV-07:02 0.00 01-NOV-00:10 8755.01 13-NOV-08:62 8147.62 01-NOV-07:02 3191.04 13-NOV-08:62 1695.32 13-NOV-08:62 0.00
December 0.327287E+09 74879552.22 104.13 0.326387E+09 899789.00 0.00 0.29 22-DEC-15:35 0.00 01-DEC-00:10 1950.15 22-DEC-16:00 1950.15 22-DEC-16:00 74.52 13-DEC-11:55 465.79 22-DEC-14:55 0.00
                                       
Annual Sum or Average 0.303770E+11 0.763048E+10 2446.34 0.291358E+11 0.124121E+10 0.00                         0.00
Minimum of Months 0.155569E+09 35317452.70 73.89 0.143608E+09 0.00 0.00 0.18   0.00   1267.90   1170.11   0.00   285.27   0.00
Maximum of Months 0.540580E+10 0.137334E+10 304.27 0.501542E+10 0.390381E+09 0.00 1.00   0.00   9235.07   8509.34   3742.23   2095.77   0.00



Table of Contents

Report: DXReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.708742E+09 0.162687E+09 169.59 0.705672E+09 3070217.56 0.00 0.51 31-JAN-17:00 0.00 01-JAN-00:10 2815.29 31-JAN-16:55 2815.29 31-JAN-16:55 140.21 09-JAN-11:43 699.94 31-JAN-16:55 0.00
February 0.285355E+09 64226531.18 114.40 0.271908E+09 13447109.46 0.00 0.33 22-FEB-16:23 0.00 01-FEB-00:10 1928.17 22-FEB-16:23 1877.12 22-FEB-16:33 147.34 16-FEB-10:52 423.51 22-FEB-16:23 0.00
March 0.606049E+09 0.141390E+09 170.77 0.601354E+09 4694949.76 0.00 0.44 16-MAR-15:53 0.00 01-MAR-00:10 2497.28 16-MAR-15:57 2497.28 16-MAR-15:57 136.14 06-MAR-15:20 620.78 16-MAR-15:57 0.00
April 0.176062E+10 0.435585E+09 219.75 0.176062E+10 0.00 0.00 1.00 04-APR-07:02 0.00 01-APR-00:10 6493.61 17-APR-07:02 6493.61 17-APR-07:02 0.00 18-APR-09:33 1317.68 25-APR-07:02 0.00
May 0.243091E+10 0.627429E+09 271.36 0.243091E+10 -0.0 0.00 1.00 01-MAY-07:02 0.00 01-MAY-00:10 6532.90 30-MAY-06:01 6532.90 30-MAY-06:01 0.00 11-MAY-08:48 1533.65 07-MAY-17:12 0.00
June 0.358585E+10 0.989872E+09 357.32 0.358205E+10 3802327.37 0.00 1.00 01-JUN-06:02 0.00 01-JUN-00:10 6570.50 05-JUN-05:02 6570.50 05-JUN-05:02 288.25 30-JUN-08:10 1702.90 28-JUN-18:42 0.00
July 0.358504E+10 0.935991E+09 340.49 0.335853E+10 0.226517E+09 0.00 1.00 01-JUL-18:12 0.00 01-JUL-00:05 7435.71 14-JUL-06:02 6911.08 16-JUL-18:32 2957.16 14-JUL-06:03 1673.98 22-JUL-16:03 0.00
August 0.387799E+10 0.101133E+10 342.65 0.362683E+10 0.251158E+09 0.00 1.00 01-AUG-06:01 0.00 01-AUG-00:10 7221.39 10-AUG-06:01 6852.37 14-AUG-05:02 2025.52 10-AUG-06:01 1694.11 27-AUG-16:42 0.00
September 0.315088E+10 0.787844E+09 284.77 0.293529E+10 0.215588E+09 0.00 1.00 01-SEP-06:01 0.00 01-SEP-00:10 7247.62 11-SEP-05:01 6736.02 27-SEP-06:02 1580.58 05-SEP-07:12 1550.84 04-SEP-16:42 0.00
October 0.198335E+10 0.477595E+09 238.88 0.193690E+10 46450354.34 0.00 1.00 02-OCT-05:02 0.00 01-OCT-00:10 7108.47 03-OCT-06:02 6876.35 02-OCT-05:02 1473.52 03-OCT-07:02 1424.01 02-OCT-05:02 0.00
November 0.120844E+10 0.273683E+09 205.83 0.115627E+10 52172663.60 0.00 1.00 01-NOV-07:02 0.00 01-NOV-00:10 7081.84 13-NOV-08:62 6575.25 01-NOV-07:02 2444.95 13-NOV-08:62 1368.87 13-NOV-08:62 0.00
December 0.481323E+09 0.108527E+09 141.58 0.480403E+09 920099.11 0.00 0.48 22-DEC-16:23 0.00 01-DEC-00:10 2747.63 22-DEC-16:27 2747.63 22-DEC-16:27 64.58 13-DEC-11:55 624.40 22-DEC-16:27 0.00
                                       
Annual Sum or Average 0.236646E+11 0.601616E+10 2857.40 0.228467E+11 0.817821E+09 0.00                         0.00
Minimum of Months 0.285355E+09 64226531.18 114.40 0.271908E+09 -0.0 0.00 0.33   0.00   1928.17   1877.12   0.00   423.51   0.00
Maximum of Months 0.387799E+10 0.101133E+10 357.32 0.362683E+10 0.251158E+09 0.00 1.00   0.00   7435.71   6911.08   2957.16   1702.90   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.15 53.28 0.00 0.00 0.00
February 62.57 42.65 19.92 87.69 47.60 0.00 0.00 0.00
March 46.21 22.67 23.54 68.48 42.97 0.00 0.00 0.00
April 30.35 7.28 23.07 54.48 27.31 0.00 0.00 0.00
May 22.19 0.00 22.19 43.69 19.95 0.00 0.00 0.00
June 22.10 0.00 22.10 58.53 10.32 0.00 0.00 0.00
July 21.06 0.06 21.00 51.99 9.42 0.00 0.00 0.00
August 21.44 1.70 19.74 52.96 11.49 0.00 0.00 0.00
September 36.81 13.52 23.28 75.14 16.96 0.00 0.00 0.00
October 70.66 48.89 21.78 116.68 38.81 0.00 0.00 0.00
November 84.94 65.44 19.50 127.71 51.51 0.00 0.00 0.00
December 92.57 73.61 18.96 134.87 64.47 0.00 0.00 0.00
                 
Annual Sum or Average 50.86 29.62 21.24 85.50 32.79 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.69 9.42 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.15 64.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.15 53.28 0.00 0.00 0.00
February 62.57 42.65 19.92 87.69 47.60 0.00 0.00 0.00
March 46.20 22.66 23.54 68.46 42.97 0.00 0.00 0.00
April 30.20 7.21 22.99 54.09 27.31 0.00 0.00 0.00
May 22.19 0.00 22.19 43.68 19.95 0.00 0.00 0.00
June 22.10 0.00 22.10 58.53 10.32 0.00 0.00 0.00
July 21.06 0.06 21.00 51.99 9.42 0.00 0.00 0.00
August 21.41 1.68 19.73 52.90 11.49 0.00 0.00 0.00
September 36.71 13.49 23.22 74.93 16.96 0.00 0.00 0.00
October 70.66 48.89 21.77 116.68 38.81 0.00 0.00 0.00
November 84.94 65.44 19.50 127.71 51.51 0.00 0.00 0.00
December 92.57 73.61 18.96 134.87 64.47 0.00 0.00 0.00
                 
Annual Sum or Average 50.84 29.61 21.22 85.44 32.79 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.68 9.42 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.15 64.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.15 53.28 0.00 0.00 0.00
February 62.57 42.65 19.92 87.69 47.60 0.00 0.00 0.00
March 46.20 22.66 23.54 68.46 42.97 0.00 0.00 0.00
April 30.20 7.21 22.99 54.09 27.31 0.00 0.00 0.00
May 22.19 0.00 22.19 43.68 19.95 0.00 0.00 0.00
June 22.10 0.00 22.10 58.53 10.32 0.00 0.00 0.00
July 21.06 0.06 21.00 51.99 9.42 0.00 0.00 0.00
August 21.41 1.68 19.73 52.90 11.49 0.00 0.00 0.00
September 36.71 13.49 23.22 74.91 16.96 0.00 0.00 0.00
October 70.66 48.89 21.77 116.68 38.81 0.00 0.00 0.00
November 84.94 65.44 19.50 127.71 51.51 0.00 0.00 0.00
December 92.57 73.61 18.96 134.87 64.47 0.00 0.00 0.00
                 
Annual Sum or Average 50.84 29.61 21.22 85.44 32.79 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.68 9.42 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.15 64.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.15 53.28 0.00 0.00 0.00
February 62.57 42.65 19.92 87.69 47.60 0.00 0.00 0.00
March 46.20 22.66 23.54 68.46 42.97 0.00 0.00 0.00
April 30.20 7.21 22.99 54.09 27.31 0.00 0.00 0.00
May 22.19 0.00 22.19 43.68 19.95 0.00 0.00 0.00
June 22.10 0.00 22.10 58.53 10.32 0.00 0.00 0.00
July 21.06 0.06 21.00 51.99 9.42 0.00 0.00 0.00
August 21.41 1.68 19.73 52.90 11.49 0.00 0.00 0.00
September 36.71 13.49 23.22 74.91 16.96 0.00 0.00 0.00
October 70.66 48.89 21.77 116.68 38.81 0.00 0.00 0.00
November 84.94 65.44 19.50 127.71 51.51 0.00 0.00 0.00
December 92.57 73.61 18.96 134.87 64.47 0.00 0.00 0.00
                 
Annual Sum or Average 50.84 29.61 21.22 85.44 32.79 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.68 9.42 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.15 64.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.15 53.28 0.00 0.00 0.00
February 62.57 42.65 19.92 87.69 47.60 0.00 0.00 0.00
March 46.20 22.66 23.54 68.46 42.97 0.00 0.00 0.00
April 30.20 7.21 22.99 54.09 27.31 0.00 0.00 0.00
May 22.19 0.00 22.19 43.68 19.95 0.00 0.00 0.00
June 22.10 0.00 22.10 58.53 10.32 0.00 0.00 0.00
July 21.06 0.06 21.00 51.99 9.42 0.00 0.00 0.00
August 21.41 1.68 19.73 52.90 11.49 0.00 0.00 0.00
September 36.72 13.49 23.23 74.92 16.94 0.00 0.00 0.00
October 70.66 48.89 21.77 116.68 38.81 0.00 0.00 0.00
November 84.94 65.44 19.50 127.71 51.51 0.00 0.00 0.00
December 92.57 73.61 18.96 134.87 64.47 0.00 0.00 0.00
                 
Annual Sum or Average 50.84 29.61 21.22 85.44 32.79 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.68 9.42 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.15 64.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 99.63 79.88 19.75 153.15 53.28 0.00 0.00 0.00
February 62.57 42.65 19.92 87.69 47.60 0.00 0.00 0.00
March 46.21 22.67 23.54 68.47 42.95 0.00 0.00 0.00
April 30.33 7.28 23.05 54.41 27.27 0.00 0.00 0.00
May 22.19 0.00 22.19 43.69 19.95 0.00 0.00 0.00
June 22.10 0.00 22.10 58.53 10.32 0.00 0.00 0.00
July 21.06 0.06 21.00 51.99 9.42 0.00 0.00 0.00
August 21.44 1.70 19.74 52.97 11.49 0.00 0.00 0.00
September 36.83 13.53 23.29 75.13 16.89 0.00 0.00 0.00
October 70.66 48.89 21.78 116.68 38.81 0.00 0.00 0.00
November 84.94 65.44 19.50 127.71 51.51 0.00 0.00 0.00
December 92.57 73.61 18.96 134.87 64.47 0.00 0.00 0.00
                 
Annual Sum or Average 50.86 29.62 21.24 85.49 32.78 0.00 0.00 0.00
Minimum of Months 21.06 0.00 18.96 43.69 9.42 0.00 0.00 0.00
Maximum of Months 99.63 79.88 23.54 153.15 64.47 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 139.85 111.91 27.94 214.27 74.67 0.00 0.00 0.00
February 88.12 59.75 28.37 123.22 66.40 0.00 0.00 0.00
March 73.11 37.97 35.14 111.00 60.02 0.00 0.00 0.00
April 52.48 17.82 34.66 96.85 38.67 0.00 0.00 0.00
May 33.10 1.14 31.96 64.58 28.46 0.00 0.00 0.00
June 31.38 0.00 31.38 81.25 14.87 0.00 0.00 0.00
July 30.42 0.43 29.99 73.56 13.44 0.00 0.00 0.00
August 36.06 6.54 29.52 86.60 16.40 0.00 0.00 0.00
September 59.91 24.70 35.21 120.94 24.01 0.00 0.00 0.00
October 102.35 71.10 31.25 168.61 54.63 0.00 0.00 0.00
November 119.35 91.69 27.66 178.86 72.09 0.00 0.00 0.00
December 129.97 103.13 26.85 188.80 90.20 0.00 0.00 0.00
                 
Annual Sum or Average 74.66 43.83 30.83 125.80 46.08 0.00 0.00 0.00
Minimum of Months 30.42 0.00 26.85 64.58 13.44 0.00 0.00 0.00
Maximum of Months 139.85 111.91 35.21 214.27 90.20 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.75 23.73 14.02 49.28 47.05 0.00 0.00 0.00
February 36.85 21.25 15.60 43.04 45.00 0.00 0.00 0.00
March 45.69 23.56 22.13 61.18 39.58 0.00 0.00 0.00
April 65.00 38.40 26.60 106.38 25.20 0.00 0.00 0.00
May 66.94 39.23 27.71 116.37 19.11 0.00 0.00 0.00
June 69.70 42.67 27.02 137.91 9.93 0.00 0.00 0.00
July 58.53 32.62 25.90 114.86 9.31 0.00 0.00 0.00
August 55.90 31.62 24.28 110.26 11.41 0.00 0.00 0.00
September 45.93 22.08 23.85 85.70 15.66 0.00 0.00 0.00
October 47.00 28.60 18.40 71.15 35.88 0.00 0.00 0.00
November 36.35 21.91 14.44 45.29 47.87 0.00 0.00 0.00
December 33.25 20.18 13.08 37.17 59.62 0.00 0.00 0.00
                 
Annual Sum or Average 49.97 28.86 21.11 81.73 30.41 0.00 0.00 0.00
Minimum of Months 33.25 20.18 13.08 37.17 9.31 0.00 0.00 0.00
Maximum of Months 69.70 42.67 27.71 137.91 59.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.75 23.73 14.02 49.28 47.05 0.00 0.00 0.00
February 36.85 21.25 15.60 43.04 45.00 0.00 0.00 0.00
March 45.69 23.56 22.13 61.18 39.58 0.00 0.00 0.00
April 65.00 38.40 26.60 106.38 25.20 0.00 0.00 0.00
May 66.94 39.23 27.71 116.37 19.11 0.00 0.00 0.00
June 69.70 42.67 27.02 137.91 9.93 0.00 0.00 0.00
July 58.52 32.62 25.90 114.86 9.31 0.00 0.00 0.00
August 55.89 31.62 24.28 110.26 11.41 0.00 0.00 0.00
September 45.93 22.08 23.85 85.70 15.66 0.00 0.00 0.00
October 47.00 28.60 18.40 71.15 35.88 0.00 0.00 0.00
November 36.35 21.91 14.44 45.29 47.87 0.00 0.00 0.00
December 33.25 20.18 13.08 37.17 59.61 0.00 0.00 0.00
                 
Annual Sum or Average 49.97 28.86 21.11 81.73 30.41 0.00 0.00 0.00
Minimum of Months 33.25 20.18 13.08 37.17 9.31 0.00 0.00 0.00
Maximum of Months 69.70 42.67 27.71 137.91 59.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.75 23.73 14.02 49.28 47.05 0.00 0.00 0.00
February 36.85 21.25 15.60 43.04 45.00 0.00 0.00 0.00
March 45.69 23.56 22.13 61.18 39.58 0.00 0.00 0.00
April 65.00 38.40 26.60 106.38 25.20 0.00 0.00 0.00
May 66.94 39.23 27.71 116.37 19.11 0.00 0.00 0.00
June 69.70 42.67 27.02 137.91 9.93 0.00 0.00 0.00
July 58.52 32.62 25.90 114.86 9.31 0.00 0.00 0.00
August 55.89 31.62 24.28 110.26 11.41 0.00 0.00 0.00
September 45.93 22.08 23.85 85.70 15.66 0.00 0.00 0.00
October 47.00 28.60 18.40 71.15 35.88 0.00 0.00 0.00
November 36.35 21.91 14.44 45.29 47.87 0.00 0.00 0.00
December 33.25 20.18 13.08 37.17 59.61 0.00 0.00 0.00
                 
Annual Sum or Average 49.97 28.86 21.11 81.73 30.41 0.00 0.00 0.00
Minimum of Months 33.25 20.18 13.08 37.17 9.31 0.00 0.00 0.00
Maximum of Months 69.70 42.67 27.71 137.91 59.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 37.78 23.75 14.03 49.36 47.05 0.00 0.00 0.00
February 36.85 21.25 15.60 43.04 45.00 0.00 0.00 0.00
March 45.69 23.56 22.13 61.18 39.58 0.00 0.00 0.00
April 65.00 38.40 26.60 106.38 25.20 0.00 0.00 0.00
May 66.94 39.23 27.71 116.37 19.11 0.00 0.00 0.00
June 69.70 42.67 27.02 137.91 9.93 0.00 0.00 0.00
July 58.53 32.62 25.90 114.86 9.31 0.00 0.00 0.00
August 55.90 31.62 24.28 110.26 11.41 0.00 0.00 0.00
September 45.93 22.08 23.85 85.70 15.66 0.00 0.00 0.00
October 47.00 28.60 18.40 71.15 35.88 0.00 0.00 0.00
November 36.37 21.92 14.44 45.32 47.87 0.00 0.00 0.00
December 33.29 20.20 13.09 37.26 59.60 0.00 0.00 0.00
                 
Annual Sum or Average 49.97 28.86 21.11 81.75 30.41 0.00 0.00 0.00
Minimum of Months 33.29 20.20 13.09 37.26 9.31 0.00 0.00 0.00
Maximum of Months 69.70 42.67 27.71 137.91 59.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 10.52 48.55 0.00 0.00 0.00
February 13.17 0.00 13.17 7.37 46.41 0.00 0.00 0.00
March 17.53 0.00 17.53 18.34 41.14 0.00 0.00 0.00
April 21.71 0.22 21.49 36.54 25.42 0.00 0.00 0.00
May 24.98 1.79 23.20 47.67 18.30 0.00 0.00 0.00
June 28.63 4.75 23.88 70.83 9.73 0.00 0.00 0.00
July 24.54 2.35 22.20 58.78 9.03 0.00 0.00 0.00
August 20.15 0.47 19.68 50.30 10.95 0.00 0.00 0.00
September 18.89 0.01 18.88 41.05 15.79 0.00 0.00 0.00
October 14.80 0.00 14.80 20.38 37.25 0.00 0.00 0.00
November 12.26 0.00 12.26 9.01 49.73 0.00 0.00 0.00
December 10.93 0.00 10.93 5.65 62.39 0.00 0.00 0.00
                 
Annual Sum or Average 18.30 0.80 17.50 31.48 31.17 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 5.65 9.03 0.00 0.00 0.00
Maximum of Months 28.63 4.75 23.88 70.83 62.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 10.52 48.55 0.00 0.00 0.00
February 13.17 0.00 13.17 7.37 46.41 0.00 0.00 0.00
March 17.53 0.00 17.53 18.34 41.14 0.00 0.00 0.00
April 21.66 0.20 21.46 36.53 25.52 0.00 0.00 0.00
May 24.85 1.71 23.14 47.33 18.31 0.00 0.00 0.00
June 28.53 4.69 23.84 70.56 9.73 0.00 0.00 0.00
July 24.45 2.29 22.15 58.52 9.03 0.00 0.00 0.00
August 20.06 0.43 19.64 50.09 10.95 0.00 0.00 0.00
September 18.89 0.01 18.88 41.05 15.79 0.00 0.00 0.00
October 14.80 0.00 14.80 20.38 37.25 0.00 0.00 0.00
November 12.26 0.00 12.26 9.01 49.73 0.00 0.00 0.00
December 10.93 0.00 10.93 5.65 62.39 0.00 0.00 0.00
                 
Annual Sum or Average 18.26 0.78 17.48 31.39 31.17 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 5.65 9.03 0.00 0.00 0.00
Maximum of Months 28.53 4.69 23.84 70.56 62.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 10.52 48.55 0.00 0.00 0.00
February 13.17 0.00 13.17 7.37 46.41 0.00 0.00 0.00
March 17.53 0.00 17.53 18.34 41.14 0.00 0.00 0.00
April 21.66 0.20 21.46 36.53 25.53 0.00 0.00 0.00
May 24.85 1.71 23.14 47.33 18.31 0.00 0.00 0.00
June 28.53 4.69 23.84 70.56 9.73 0.00 0.00 0.00
July 24.45 2.29 22.15 58.52 9.03 0.00 0.00 0.00
August 20.06 0.43 19.63 50.09 10.96 0.00 0.00 0.00
September 18.88 0.00 18.88 41.05 15.79 0.00 0.00 0.00
October 14.80 0.00 14.80 20.38 37.25 0.00 0.00 0.00
November 12.26 0.00 12.26 9.01 49.73 0.00 0.00 0.00
December 10.93 0.00 10.93 5.65 62.39 0.00 0.00 0.00
                 
Annual Sum or Average 18.26 0.78 17.48 31.39 31.18 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 5.65 9.03 0.00 0.00 0.00
Maximum of Months 28.53 4.69 23.84 70.56 62.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 10.52 48.55 0.00 0.00 0.00
February 13.17 0.00 13.17 7.37 46.41 0.00 0.00 0.00
March 17.53 0.00 17.53 18.34 41.14 0.00 0.00 0.00
April 21.66 0.20 21.46 36.53 25.53 0.00 0.00 0.00
May 24.85 1.71 23.14 47.33 18.31 0.00 0.00 0.00
June 28.53 4.69 23.84 70.56 9.73 0.00 0.00 0.00
July 24.45 2.29 22.15 58.52 9.03 0.00 0.00 0.00
August 20.06 0.43 19.63 50.09 10.96 0.00 0.00 0.00
September 18.88 0.00 18.88 41.05 15.80 0.00 0.00 0.00
October 14.80 0.00 14.80 20.38 37.25 0.00 0.00 0.00
November 12.26 0.00 12.26 9.01 49.73 0.00 0.00 0.00
December 10.93 0.00 10.93 5.65 62.39 0.00 0.00 0.00
                 
Annual Sum or Average 18.26 0.78 17.48 31.39 31.18 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 5.65 9.03 0.00 0.00 0.00
Maximum of Months 28.53 4.69 23.84 70.56 62.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 10.52 48.55 0.00 0.00 0.00
February 13.17 0.00 13.17 7.37 46.41 0.00 0.00 0.00
March 17.53 0.00 17.53 18.34 41.14 0.00 0.00 0.00
April 21.66 0.20 21.46 36.55 25.53 0.00 0.00 0.00
May 24.85 1.71 23.14 47.33 18.31 0.00 0.00 0.00
June 28.53 4.69 23.84 70.56 9.73 0.00 0.00 0.00
July 24.45 2.29 22.15 58.52 9.03 0.00 0.00 0.00
August 20.06 0.43 19.64 50.09 10.96 0.00 0.00 0.00
September 18.89 0.00 18.88 41.05 15.80 0.00 0.00 0.00
October 14.80 0.00 14.80 20.38 37.25 0.00 0.00 0.00
November 12.26 0.00 12.26 9.01 49.73 0.00 0.00 0.00
December 10.93 0.00 10.93 5.65 62.39 0.00 0.00 0.00
                 
Annual Sum or Average 18.26 0.78 17.48 31.39 31.18 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 5.65 9.03 0.00 0.00 0.00
Maximum of Months 28.53 4.69 23.84 70.56 62.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 11.76 0.00 11.76 10.52 48.55 0.00 0.00 0.00
February 13.17 0.00 13.17 7.37 46.41 0.00 0.00 0.00
March 17.53 0.00 17.53 18.34 41.14 0.00 0.00 0.00
April 21.72 0.22 21.50 36.66 25.53 0.00 0.00 0.00
May 25.00 1.78 23.21 47.69 18.31 0.00 0.00 0.00
June 28.63 4.75 23.88 70.81 9.73 0.00 0.00 0.00
July 24.52 2.33 22.19 58.70 9.03 0.00 0.00 0.00
August 20.13 0.46 19.67 50.25 10.96 0.00 0.00 0.00
September 18.89 0.00 18.88 41.06 15.80 0.00 0.00 0.00
October 14.80 0.00 14.80 20.38 37.25 0.00 0.00 0.00
November 12.26 0.00 12.26 9.01 49.73 0.00 0.00 0.00
December 10.93 0.00 10.93 5.65 62.39 0.00 0.00 0.00
                 
Annual Sum or Average 18.30 0.80 17.50 31.48 31.18 0.00 0.00 0.00
Minimum of Months 10.93 0.00 10.93 5.65 9.03 0.00 0.00 0.00
Maximum of Months 28.63 4.75 23.88 70.81 62.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.61 24.68 14.93 58.18 52.33 0.00 0.00 0.00
February 31.48 15.28 16.20 37.42 47.56 0.00 0.00 0.00
March 41.41 19.78 21.63 57.26 42.51 0.00 0.00 0.00
April 63.49 35.86 27.64 107.28 29.39 0.00 0.00 0.00
May 63.22 34.85 28.36 113.50 22.66 0.00 0.00 0.00
June 67.36 38.96 28.40 135.66 12.24 0.00 0.00 0.00
July 48.43 22.16 26.28 98.74 10.58 0.00 0.00 0.00
August 46.50 22.97 23.52 95.47 12.61 0.00 0.00 0.00
September 40.59 16.88 23.70 78.26 17.34 0.00 0.00 0.00
October 42.35 24.18 18.17 66.91 39.56 0.00 0.00 0.00
November 39.49 23.94 15.55 54.98 52.43 0.00 0.00 0.00
December 31.82 18.17 13.65 40.86 64.71 0.00 0.00 0.00
                 
Annual Sum or Average 46.36 24.84 21.52 78.88 33.61 0.00 0.00 0.00
Minimum of Months 31.48 15.28 13.65 37.42 10.58 0.00 0.00 0.00
Maximum of Months 67.36 38.96 28.40 135.66 64.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.58 24.66 14.92 58.10 52.33 0.00 0.00 0.00
February 31.48 15.28 16.20 37.42 47.56 0.00 0.00 0.00
March 41.40 19.78 21.62 57.26 42.51 0.00 0.00 0.00
April 63.49 35.86 27.64 107.28 29.39 0.00 0.00 0.00
May 63.22 34.85 28.36 113.50 22.66 0.00 0.00 0.00
June 67.36 38.96 28.40 135.66 12.24 0.00 0.00 0.00
July 48.43 22.16 26.27 98.74 10.58 0.00 0.00 0.00
August 46.50 22.97 23.52 95.47 12.60 0.00 0.00 0.00
September 40.59 16.88 23.70 78.25 17.34 0.00 0.00 0.00
October 42.35 24.18 18.17 66.90 39.55 0.00 0.00 0.00
November 39.47 23.93 15.55 54.94 52.43 0.00 0.00 0.00
December 31.78 18.14 13.64 40.76 64.71 0.00 0.00 0.00
                 
Annual Sum or Average 46.36 24.84 21.52 78.86 33.61 0.00 0.00 0.00
Minimum of Months 31.48 15.28 13.64 37.42 10.58 0.00 0.00 0.00
Maximum of Months 67.36 38.96 28.40 135.66 64.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.58 24.66 14.92 58.10 52.33 0.00 0.00 0.00
February 31.48 15.28 16.20 37.42 47.56 0.00 0.00 0.00
March 41.40 19.78 21.62 57.26 42.51 0.00 0.00 0.00
April 63.49 35.86 27.64 107.28 29.39 0.00 0.00 0.00
May 63.22 34.85 28.36 113.50 22.66 0.00 0.00 0.00
June 67.36 38.96 28.40 135.66 12.24 0.00 0.00 0.00
July 48.43 22.16 26.27 98.74 10.58 0.00 0.00 0.00
August 46.50 22.97 23.52 95.47 12.60 0.00 0.00 0.00
September 40.59 16.88 23.70 78.25 17.34 0.00 0.00 0.00
October 42.35 24.18 18.17 66.90 39.55 0.00 0.00 0.00
November 39.47 23.93 15.55 54.94 52.43 0.00 0.00 0.00
December 31.78 18.14 13.64 40.76 64.71 0.00 0.00 0.00
                 
Annual Sum or Average 46.36 24.84 21.52 78.86 33.61 0.00 0.00 0.00
Minimum of Months 31.48 15.28 13.64 37.42 10.58 0.00 0.00 0.00
Maximum of Months 67.36 38.96 28.40 135.66 64.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 39.58 24.66 14.92 58.10 52.33 0.00 0.00 0.00
February 31.48 15.28 16.20 37.42 47.56 0.00 0.00 0.00
March 41.41 19.78 21.63 57.26 42.51 0.00 0.00 0.00
April 63.49 35.86 27.64 107.28 29.39 0.00 0.00 0.00
May 63.22 34.85 28.36 113.50 22.66 0.00 0.00 0.00
June 67.36 38.96 28.40 135.66 12.24 0.00 0.00 0.00
July 48.43 22.16 26.28 98.74 10.58 0.00 0.00 0.00
August 46.50 22.97 23.52 95.47 12.61 0.00 0.00 0.00
September 40.59 16.88 23.70 78.26 17.34 0.00 0.00 0.00
October 42.35 24.18 18.17 66.90 39.56 0.00 0.00 0.00
November 39.47 23.93 15.55 54.94 52.43 0.00 0.00 0.00
December 31.78 18.14 13.64 40.76 64.71 0.00 0.00 0.00
                 
Annual Sum or Average 46.36 24.84 21.52 78.86 33.61 0.00 0.00 0.00
Minimum of Months 31.48 15.28 13.64 37.42 10.58 0.00 0.00 0.00
Maximum of Months 67.36 38.96 28.40 135.66 64.71 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266843E+09 0.213943E+09 52899745.93 0.410199E+09 0.142700E+09
February 0.151368E+09 0.103176E+09 48191558.41 0.212147E+09 0.115149E+09
March 0.123774E+09 60715423.36 63058201.87 0.183420E+09 0.115081E+09
April 78673348.58 18865663.10 59807685.48 0.141203E+09 70782880.12
May 59442718.63 949.91 59441768.72 0.117008E+09 53433524.25
June 57289639.04 0.15 57289638.89 0.151721E+09 26744740.94
July 56408208.06 171573.11 56236634.95 0.139253E+09 25228300.20
August 57423213.63 4540325.02 52882888.61 0.141852E+09 30765513.30
September 95401199.54 35049197.75 60352001.79 0.194769E+09 43966078.44
October 0.189259E+09 0.130936E+09 58323328.64 0.312523E+09 0.103952E+09
November 0.220167E+09 0.169633E+09 50534722.99 0.331016E+09 0.133508E+09
December 0.247928E+09 0.197151E+09 50777148.14 0.361242E+09 0.172670E+09
           
Annual Sum or Average 0.160398E+10 0.934182E+09 0.669795E+09 0.269635E+10 0.103398E+10
Minimum of Months 56408208.06 0.15 48191558.41 0.117008E+09 25228300.20
Maximum of Months 0.266843E+09 0.213943E+09 63058201.87 0.410199E+09 0.172670E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266842E+09 0.213943E+09 52898608.98 0.410200E+09 0.142697E+09
February 0.151366E+09 0.103176E+09 48189778.08 0.212146E+09 0.115148E+09
March 0.123736E+09 60693913.88 63041699.24 0.183353E+09 0.115100E+09
April 78267668.14 18687090.55 59580577.59 0.140211E+09 70780081.61
May 59435708.34 0.00 59435708.34 0.116996E+09 53430681.57
June 57287929.29 0.00 57287929.29 0.151721E+09 26742836.59
July 56404281.07 170394.54 56233886.53 0.139247E+09 25226975.70
August 57357018.90 4512755.83 52844263.06 0.141689E+09 30763984.90
September 95164159.81 34966468.63 60197691.18 0.194223E+09 43964535.65
October 0.189258E+09 0.130936E+09 58321795.39 0.312522E+09 0.103949E+09
November 0.220166E+09 0.169633E+09 50533289.02 0.331015E+09 0.133506E+09
December 0.247927E+09 0.197151E+09 50775918.50 0.361242E+09 0.172667E+09
           
Annual Sum or Average 0.160321E+10 0.933870E+09 0.669341E+09 0.269457E+10 0.103397E+10
Minimum of Months 56404281.07 0.00 48189778.08 0.116996E+09 25226975.70
Maximum of Months 0.266842E+09 0.213943E+09 63041699.24 0.410200E+09 0.172667E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266842E+09 0.213943E+09 52898608.98 0.410200E+09 0.142697E+09
February 0.151366E+09 0.103176E+09 48189778.08 0.212146E+09 0.115148E+09
March 0.123736E+09 60693913.88 63041699.24 0.183353E+09 0.115100E+09
April 78267668.14 18687090.55 59580577.59 0.140211E+09 70780081.61
May 59435708.34 0.00 59435708.34 0.116996E+09 53430681.57
June 57287929.29 0.00 57287929.29 0.151721E+09 26742836.59
July 56404281.07 170394.54 56233886.53 0.139247E+09 25226975.70
August 57356485.00 4512244.25 52844240.74 0.141687E+09 30763984.90
September 95141249.64 34963755.66 60177493.99 0.194177E+09 43964835.27
October 0.189258E+09 0.130936E+09 58321795.39 0.312522E+09 0.103949E+09
November 0.220166E+09 0.169633E+09 50533289.02 0.331015E+09 0.133506E+09
December 0.247927E+09 0.197151E+09 50775918.50 0.361242E+09 0.172667E+09
           
Annual Sum or Average 0.160319E+10 0.933866E+09 0.669321E+09 0.269452E+10 0.103398E+10
Minimum of Months 56404281.07 0.00 48189778.08 0.116996E+09 25226975.70
Maximum of Months 0.266842E+09 0.213943E+09 63041699.24 0.410200E+09 0.172667E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266842E+09 0.213943E+09 52898608.98 0.410200E+09 0.142697E+09
February 0.151366E+09 0.103176E+09 48189778.08 0.212146E+09 0.115148E+09
March 0.123736E+09 60693913.88 63041699.24 0.183353E+09 0.115100E+09
April 78267668.14 18687090.55 59580577.59 0.140211E+09 70780081.61
May 59435708.34 0.00 59435708.34 0.116996E+09 53430681.57
June 57287929.29 0.00 57287929.29 0.151721E+09 26742836.59
July 56404281.07 170394.54 56233886.53 0.139247E+09 25226975.70
August 57356485.83 4512245.09 52844240.74 0.141687E+09 30763970.82
September 95141642.97 34963761.71 60177881.26 0.194173E+09 43960601.40
October 0.189258E+09 0.130936E+09 58321795.39 0.312522E+09 0.103949E+09
November 0.220166E+09 0.169633E+09 50533289.02 0.331015E+09 0.133506E+09
December 0.247927E+09 0.197151E+09 50775918.50 0.361242E+09 0.172667E+09
           
Annual Sum or Average 0.160319E+10 0.933866E+09 0.669321E+09 0.269451E+10 0.103397E+10
Minimum of Months 56404281.07 0.00 48189778.08 0.116996E+09 25226975.70
Maximum of Months 0.266842E+09 0.213943E+09 63041699.24 0.410200E+09 0.172667E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_5

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266842E+09 0.213943E+09 52898608.98 0.410200E+09 0.142697E+09
February 0.151366E+09 0.103176E+09 48189778.08 0.212146E+09 0.115148E+09
March 0.123736E+09 60693913.88 63041699.24 0.183353E+09 0.115100E+09
April 78267668.14 18687090.55 59580577.59 0.140211E+09 70780081.61
May 59435708.34 0.00 59435708.34 0.116996E+09 53430681.57
June 57287929.29 0.00 57287929.29 0.151721E+09 26742836.59
July 56404281.07 170394.54 56233886.53 0.139247E+09 25226975.70
August 57357113.83 4512873.09 52844240.74 0.141688E+09 30762742.95
September 95170505.55 34967401.67 60203103.89 0.194182E+09 43910170.08
October 0.189258E+09 0.130936E+09 58321795.39 0.312522E+09 0.103949E+09
November 0.220166E+09 0.169633E+09 50533289.02 0.331015E+09 0.133506E+09
December 0.247927E+09 0.197151E+09 50775918.50 0.361242E+09 0.172667E+09
           
Annual Sum or Average 0.160322E+10 0.933871E+09 0.669347E+09 0.269452E+10 0.103392E+10
Minimum of Months 56404281.07 0.00 48189778.08 0.116996E+09 25226975.70
Maximum of Months 0.266842E+09 0.213943E+09 63041699.24 0.410200E+09 0.172667E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_WINDOW_6

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.266843E+09 0.213943E+09 52899745.87 0.410199E+09 0.142700E+09
February 0.151368E+09 0.103176E+09 48191558.32 0.212147E+09 0.115149E+09
March 0.123777E+09 60716572.78 63060794.87 0.183383E+09 0.115036E+09
April 78623562.49 18878481.13 59745081.35 0.141036E+09 70688341.55
May 59442469.92 955.41 59441514.51 0.117007E+09 53433524.10
June 57289638.97 0.17 57289638.81 0.151721E+09 26744740.84
July 56408473.20 172071.49 56236401.71 0.139255E+09 25228300.13
August 57432644.12 4549795.93 52882848.19 0.141882E+09 30762509.05
September 95454789.18 35079705.88 60375083.30 0.194730E+09 43788811.19
October 0.189259E+09 0.130936E+09 58323328.56 0.312523E+09 0.103952E+09
November 0.220167E+09 0.169633E+09 50534722.92 0.331016E+09 0.133508E+09
December 0.247928E+09 0.197151E+09 50777148.08 0.361242E+09 0.172670E+09
           
Annual Sum or Average 0.160399E+10 0.934237E+09 0.669758E+09 0.269614E+10 0.103366E+10
Minimum of Months 56408473.20 0.17 48191558.32 0.117007E+09 25228300.13
Maximum of Months 0.266843E+09 0.213943E+09 63060794.87 0.410199E+09 0.172670E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_1_WALL_SOUTH_DOOR

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.374564E+09 0.299737E+09 74826647.49 0.573897E+09 0.199999E+09
February 0.213185E+09 0.144551E+09 68634130.43 0.298083E+09 0.160623E+09
March 0.195807E+09 0.101695E+09 94111665.67 0.297314E+09 0.160766E+09
April 0.136040E+09 46192476.64 89847367.99 0.251039E+09 0.100232E+09
May 88652969.90 3040335.41 85612634.49 0.172971E+09 76232025.64
June 81336276.40 0.00 81336276.40 0.210597E+09 38532499.39
July 81470509.01 1151108.36 80319400.65 0.197025E+09 36001810.09
August 96586500.72 17512319.26 79074181.45 0.231961E+09 43914503.43
September 0.155285E+09 64030085.40 91254515.35 0.313475E+09 62246463.71
October 0.274137E+09 0.190426E+09 83711190.32 0.451611E+09 0.146326E+09
November 0.309357E+09 0.237657E+09 71699602.02 0.463617E+09 0.186860E+09
December 0.348122E+09 0.276211E+09 71911026.45 0.505678E+09 0.241593E+09
           
Annual Sum or Average 0.235454E+10 0.138220E+10 0.972339E+09 0.396727E+10 0.145333E+10
Minimum of Months 81336276.40 0.00 68634130.43 0.172971E+09 36001810.09
Maximum of Months 0.374564E+09 0.299737E+09 94111665.67 0.573897E+09 0.241593E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101108E+09 63546576.21 37561711.42 0.132001E+09 0.126024E+09
February 89156448.25 51412224.00 37744224.25 0.104120E+09 0.108857E+09
March 0.122373E+09 63100302.53 59272519.05 0.163865E+09 0.106001E+09
April 0.168483E+09 99526921.43 68956237.73 0.275742E+09 65312336.67
May 0.179285E+09 0.105070E+09 74215161.27 0.311672E+09 51186308.52
June 0.180654E+09 0.110610E+09 70044833.64 0.357453E+09 25736967.29
July 0.156754E+09 87380273.63 69373964.48 0.307631E+09 24936061.89
August 0.149710E+09 84678567.99 65031464.34 0.295329E+09 30549788.62
September 0.119057E+09 57233808.13 61823508.39 0.222141E+09 40599424.01
October 0.125883E+09 76611304.13 49271407.80 0.190562E+09 96101699.84
November 94227627.53 56799513.76 37428113.76 0.117389E+09 0.124090E+09
December 89065440.69 54042000.93 35023439.76 99559602.95 0.159674E+09
           
Annual Sum or Average 0.157576E+10 0.910011E+09 0.665747E+09 0.257747E+10 0.959070E+09
Minimum of Months 89065440.69 51412224.00 35023439.76 99559602.95 24936061.89
Maximum of Months 0.180654E+09 0.110610E+09 74215161.27 0.357453E+09 0.159674E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101107E+09 63546576.21 37560574.53 0.132001E+09 0.126021E+09
February 89154668.02 51412224.00 37742444.02 0.104118E+09 0.108856E+09
March 0.122370E+09 63100302.53 59269968.56 0.163863E+09 0.105999E+09
April 0.168481E+09 99526921.43 68954415.81 0.275742E+09 65309728.81
May 0.179283E+09 0.105070E+09 74213239.31 0.311672E+09 51183576.20
June 0.180653E+09 0.110610E+09 70043124.14 0.357454E+09 25735117.41
July 0.156752E+09 87380273.63 69371691.73 0.307630E+09 24934775.76
August 0.149708E+09 84678567.99 65029386.82 0.295328E+09 30548204.06
September 0.119055E+09 57233808.13 61820918.36 0.222139E+09 40597698.66
October 0.125881E+09 76611304.13 49269874.63 0.190562E+09 96098842.52
November 94226193.63 56799513.76 37426679.87 0.117389E+09 0.124088E+09
December 89064211.12 54042000.93 35022210.18 99559489.43 0.159671E+09
           
Annual Sum or Average 0.157574E+10 0.910011E+09 0.665725E+09 0.257746E+10 0.959044E+09
Minimum of Months 89064211.12 51412224.00 35022210.18 99559489.43 24934775.76
Maximum of Months 0.180653E+09 0.110610E+09 74213239.31 0.357454E+09 0.159671E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101107E+09 63546576.21 37560574.53 0.132001E+09 0.126021E+09
February 89154668.02 51412224.00 37742444.02 0.104118E+09 0.108856E+09
March 0.122370E+09 63100302.53 59269968.56 0.163863E+09 0.105999E+09
April 0.168481E+09 99526921.43 68954415.81 0.275742E+09 65309728.81
May 0.179283E+09 0.105070E+09 74213239.31 0.311672E+09 51183576.20
June 0.180653E+09 0.110610E+09 70043124.14 0.357454E+09 25735117.41
July 0.156752E+09 87380273.63 69371691.73 0.307630E+09 24934775.76
August 0.149708E+09 84678567.99 65029386.82 0.295328E+09 30548204.06
September 0.119055E+09 57233808.13 61820918.36 0.222139E+09 40597698.66
October 0.125881E+09 76611304.13 49269874.63 0.190562E+09 96098842.52
November 94226193.63 56799513.76 37426679.87 0.117389E+09 0.124088E+09
December 89064211.12 54042000.93 35022210.18 99559489.43 0.159671E+09
           
Annual Sum or Average 0.157574E+10 0.910011E+09 0.665725E+09 0.257746E+10 0.959044E+09
Minimum of Months 89064211.12 51412224.00 35022210.18 99559489.43 24934775.76
Maximum of Months 0.180653E+09 0.110610E+09 74213239.31 0.357454E+09 0.159671E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_2_WALL_EAST_WINDOW_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.101188E+09 63601417.01 37586602.01 0.132218E+09 0.126024E+09
February 89159587.76 51414048.25 37745539.50 0.104127E+09 0.108856E+09
March 0.122373E+09 63100302.53 59272541.23 0.163865E+09 0.106001E+09
April 0.168483E+09 99526921.43 68956237.82 0.275742E+09 65312336.81
May 0.179285E+09 0.105070E+09 74215161.37 0.311672E+09 51186308.66
June 0.180654E+09 0.110610E+09 70044833.73 0.357453E+09 25736967.39
July 0.156754E+09 87380273.63 69373964.60 0.307631E+09 24936061.95
August 0.149710E+09 84678567.99 65031464.45 0.295329E+09 30549788.70
September 0.119057E+09 57233808.13 61823508.53 0.222141E+09 40599424.10
October 0.125887E+09 76614337.36 49272597.49 0.190574E+09 96101699.99
November 94264143.10 56824711.01 37439432.09 0.117477E+09 0.124078E+09
December 89170266.74 54108356.13 35061910.61 99799207.87 0.159630E+09
           
Annual Sum or Average 0.157599E+10 0.910162E+09 0.665824E+09 0.257803E+10 0.959013E+09
Minimum of Months 89159587.76 51414048.25 35061910.61 99799207.87 24936061.95
Maximum of Months 0.180654E+09 0.110610E+09 74215161.37 0.357453E+09 0.159630E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31501559.87 0.00 31501559.87 28183600.69 0.130037E+09
February 31868350.37 0.00 31868350.37 17819595.31 0.112277E+09
March 46953321.85 0.00 46953321.85 49124892.58 0.110187E+09
April 56265071.89 559685.93 55705385.96 94705311.61 65883879.98
May 66916377.60 4787855.16 62128522.44 0.127684E+09 49025848.81
June 74209000.56 12320373.92 61888626.63 0.183581E+09 25217689.08
July 65740615.29 6290286.77 59450328.52 0.157428E+09 24184307.78
August 53958378.82 1247610.05 52710768.78 0.134712E+09 29335184.38
September 48959657.22 13027.65 48946629.57 0.106398E+09 40918514.75
October 39637540.76 0.00 39637540.76 54575831.55 99775774.03
November 31780795.03 0.00 31780795.03 23359345.68 0.128892E+09
December 29273396.86 0.00 29273396.86 15125868.40 0.167107E+09
           
Annual Sum or Average 0.577064E+09 25218839.47 0.551845E+09 0.992698E+09 0.982841E+09
Minimum of Months 29273396.86 0.00 29273396.86 15125868.40 24184307.78
Maximum of Months 74209000.56 12320373.92 62128522.44 0.183581E+09 0.167107E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31500422.93 0.00 31500422.93 28183565.45 0.130033E+09
February 31866570.04 0.00 31866570.04 17818215.01 0.112276E+09
March 46950771.23 0.00 46950771.23 49122463.44 0.110185E+09
April 56151870.26 523541.79 55628328.48 94682782.55 66138448.60
May 66569867.44 4591312.98 61978554.46 0.126781E+09 49046143.42
June 73957358.79 12156471.89 61800886.91 0.182900E+09 25215779.24
July 65473566.69 6141638.73 59331927.96 0.156727E+09 24182969.35
August 53740238.93 1148599.77 52591639.15 0.134156E+09 29341092.30
September 48955498.28 12975.89 48942522.38 0.106395E+09 40919354.72
October 39636007.51 0.00 39636007.51 54575327.30 99772628.71
November 31779361.06 0.00 31779361.06 23358662.21 0.128889E+09
December 29272167.22 0.00 29272167.22 15125598.94 0.167104E+09
           
Annual Sum or Average 0.575854E+09 24574541.05 0.551279E+09 0.989826E+09 0.983103E+09
Minimum of Months 29272167.22 0.00 29272167.22 15125598.94 24182969.35
Maximum of Months 73957358.79 12156471.89 61978554.46 0.182900E+09 0.167104E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31500422.93 0.00 31500422.93 28183565.45 0.130033E+09
February 31866570.04 0.00 31866570.04 17818215.01 0.112276E+09
March 46950771.23 0.00 46950771.23 49122463.44 0.110185E+09
April 56133467.93 517640.06 55615827.87 94680391.87 66183508.52
May 66569867.44 4591312.98 61978554.46 0.126781E+09 49046143.42
June 73957358.79 12156471.89 61800886.91 0.182900E+09 25215779.24
July 65473566.69 6141638.73 59331927.96 0.156727E+09 24182969.35
August 53738527.70 1148515.99 52590011.72 0.134156E+09 29344728.57
September 48949849.07 12582.69 48937266.37 0.106397E+09 40931577.56
October 39636007.51 0.00 39636007.51 54575327.30 99772628.71
November 31779361.06 0.00 31779361.06 23358662.21 0.128889E+09
December 29272167.22 0.00 29272167.22 15125598.94 0.167104E+09
           
Annual Sum or Average 0.575828E+09 24568162.34 0.551260E+09 0.989825E+09 0.983164E+09
Minimum of Months 29272167.22 0.00 29272167.22 15125598.94 24182969.35
Maximum of Months 73957358.79 12156471.89 61978554.46 0.182900E+09 0.167104E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31500422.93 0.00 31500422.93 28183565.45 0.130033E+09
February 31866570.04 0.00 31866570.04 17818215.01 0.112276E+09
March 46950771.23 0.00 46950771.23 49122463.44 0.110185E+09
April 56133467.93 517640.06 55615827.87 94680391.87 66183508.52
May 66569867.44 4591312.98 61978554.46 0.126781E+09 49046143.42
June 73957358.79 12156471.89 61800886.91 0.182900E+09 25215779.24
July 65473566.69 6141638.73 59331927.96 0.156727E+09 24182969.35
August 53738296.02 1148501.29 52589794.72 0.134159E+09 29348175.42
September 48947750.21 12469.82 48935280.39 0.106403E+09 40943044.78
October 39636007.51 0.00 39636007.51 54575327.30 99772628.71
November 31779361.06 0.00 31779361.06 23358662.21 0.128889E+09
December 29272167.22 0.00 29272167.22 15125598.94 0.167104E+09
           
Annual Sum or Average 0.575826E+09 24568034.77 0.551258E+09 0.989835E+09 0.983179E+09
Minimum of Months 29272167.22 0.00 29272167.22 15125598.94 24182969.35
Maximum of Months 73957358.79 12156471.89 61978554.46 0.182900E+09 0.167104E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_5

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31500422.93 0.00 31500422.93 28183565.45 0.130033E+09
February 31866570.04 0.00 31866570.04 17818215.01 0.112276E+09
March 46950771.23 0.00 46950771.23 49122463.44 0.110185E+09
April 56154979.71 523295.75 55631683.97 94727076.44 66180909.30
May 66569867.44 4591312.98 61978554.46 0.126781E+09 49046143.42
June 73957358.79 12156471.89 61800886.91 0.182900E+09 25215779.24
July 65473566.69 6141638.73 59331927.96 0.156727E+09 24182969.35
August 53739799.30 1148571.05 52591228.25 0.134163E+09 29349307.86
September 48950782.79 12737.91 48938044.88 0.106412E+09 40945762.25
October 39636007.51 0.00 39636007.51 54575327.30 99772628.71
November 31779361.06 0.00 31779361.06 23358662.21 0.128889E+09
December 29272167.22 0.00 29272167.22 15125598.94 0.167104E+09
           
Annual Sum or Average 0.575852E+09 24574028.30 0.551278E+09 0.989894E+09 0.983180E+09
Minimum of Months 29272167.22 0.00 29272167.22 15125598.94 24182969.35
Maximum of Months 73957358.79 12156471.89 61978554.46 0.182900E+09 0.167104E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_3_WALL_NORTH_WINDOW_6

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 31501559.81 0.00 31501559.81 28183600.69 0.130037E+09
February 31868350.28 0.00 31868350.28 17819595.24 0.112277E+09
March 46953321.72 0.00 46953321.72 49124892.45 0.110187E+09
April 56287489.68 557361.15 55730128.53 95013124.21 66173272.52
May 66948930.02 4780076.94 62168853.07 0.127730E+09 49048930.97
June 74203775.61 12305919.54 61897856.07 0.183530E+09 25217688.98
July 65676652.37 6235417.07 59441235.31 0.157210E+09 24184089.64
August 53911080.70 1218754.64 52692326.06 0.134581E+09 29349561.49
September 48954337.80 12776.48 48941561.33 0.106416E+09 40947576.16
October 39637540.68 0.00 39637540.68 54575831.52 99775773.87
November 31780794.96 0.00 31780794.96 23359345.64 0.128892E+09
December 29273396.80 0.00 29273396.80 15125868.39 0.167107E+09
           
Annual Sum or Average 0.576997E+09 25110305.81 0.551887E+09 0.992668E+09 0.983197E+09
Minimum of Months 29273396.80 0.00 29273396.80 15125868.39 24184089.64
Maximum of Months 74203775.61 12305919.54 62168853.07 0.183530E+09 0.167107E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106098E+09 66107369.58 39990520.20 0.155829E+09 0.140155E+09
February 76164350.99 36975538.40 39188812.60 90533657.38 0.115050E+09
March 0.110899E+09 52976548.59 57922865.93 0.153377E+09 0.113850E+09
April 0.164575E+09 92940014.96 71635344.90 0.278069E+09 76179605.13
May 0.169319E+09 93350428.99 75968144.53 0.304011E+09 60699261.41
June 0.174606E+09 0.100989E+09 73617114.44 0.351635E+09 31730227.79
July 0.129728E+09 59351700.54 70376487.55 0.264474E+09 28341192.43
August 0.124543E+09 61535883.24 63006732.73 0.255709E+09 33762764.20
September 0.105206E+09 43765069.40 61440446.58 0.202838E+09 44946750.91
October 0.113435E+09 64756536.42 48677982.55 0.179199E+09 0.105945E+09
November 0.102353E+09 62042530.21 40310121.32 0.142509E+09 0.135901E+09
December 85219470.46 48660570.40 36558900.06 0.109444E+09 0.173308E+09
           
Annual Sum or Average 0.146214E+10 0.783451E+09 0.678693E+09 0.248763E+10 0.105987E+10
Minimum of Months 76164350.99 36975538.40 36558900.06 90533657.38 28341192.43
Maximum of Months 0.174606E+09 0.100989E+09 75968144.53 0.351635E+09 0.173308E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106021E+09 66056046.72 39965012.30 0.155622E+09 0.140152E+09
February 76159040.40 36973544.43 39185495.97 90523949.58 0.115049E+09
March 0.110897E+09 52976548.59 57920288.66 0.153374E+09 0.113848E+09
April 0.164574E+09 92940014.96 71633522.99 0.278069E+09 76176626.81
May 0.169317E+09 93350428.99 75966222.57 0.304011E+09 60696190.96
June 0.174604E+09 0.100989E+09 73615404.93 0.351635E+09 31728065.49
July 0.129726E+09 59351700.54 70374214.80 0.264472E+09 28339711.70
August 0.124541E+09 61535883.24 63004655.21 0.255708E+09 33760938.01
September 0.105203E+09 43765069.40 61437856.55 0.202835E+09 44944866.72
October 0.113428E+09 64753215.96 48674917.00 0.179186E+09 0.105942E+09
November 0.102310E+09 62016171.25 40293511.99 0.142402E+09 0.135902E+09
December 85114323.13 48593588.74 36520734.39 0.109174E+09 0.173314E+09
           
Annual Sum or Average 0.146189E+10 0.783301E+09 0.678592E+09 0.248701E+10 0.105985E+10
Minimum of Months 76159040.40 36973544.43 36520734.39 90523949.58 28339711.70
Maximum of Months 0.174604E+09 0.100989E+09 75966222.57 0.351635E+09 0.173314E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106021E+09 66056046.72 39965012.30 0.155622E+09 0.140152E+09
February 76159040.40 36973544.43 39185495.97 90523949.58 0.115049E+09
March 0.110897E+09 52976548.59 57920288.66 0.153374E+09 0.113848E+09
April 0.164574E+09 92940014.96 71633522.99 0.278069E+09 76176626.81
May 0.169317E+09 93350428.99 75966222.57 0.304011E+09 60696190.96
June 0.174604E+09 0.100989E+09 73615404.93 0.351635E+09 31728065.49
July 0.129726E+09 59351700.54 70374214.80 0.264472E+09 28339711.70
August 0.124541E+09 61535883.24 63004655.21 0.255708E+09 33760938.01
September 0.105203E+09 43765069.40 61437856.55 0.202835E+09 44944866.72
October 0.113428E+09 64753215.96 48674917.00 0.179186E+09 0.105942E+09
November 0.102310E+09 62016171.25 40293511.99 0.142402E+09 0.135902E+09
December 85114323.13 48593588.74 36520734.39 0.109174E+09 0.173314E+09
           
Annual Sum or Average 0.146189E+10 0.783301E+09 0.678592E+09 0.248701E+10 0.105985E+10
Minimum of Months 76159040.40 36973544.43 36520734.39 90523949.58 28339711.70
Maximum of Months 0.174604E+09 0.100989E+09 75966222.57 0.351635E+09 0.173314E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_ZN_4_WALL_WEST_WINDOW_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106022E+09 66056046.72 39966149.25 0.155622E+09 0.140155E+09
February 76160820.73 36973544.43 39187276.29 90525435.93 0.115050E+09
March 0.110899E+09 52976548.59 57922839.28 0.153377E+09 0.113850E+09
April 0.164575E+09 92940014.96 71635344.99 0.278069E+09 76179605.28
May 0.169319E+09 93350428.99 75968144.63 0.304011E+09 60699261.57
June 0.174606E+09 0.100989E+09 73617114.53 0.351635E+09 31730227.90
July 0.129728E+09 59351700.54 70376487.67 0.264474E+09 28341192.51
August 0.124543E+09 61535883.24 63006732.83 0.255709E+09 33762764.29
September 0.105206E+09 43765069.40 61440446.72 0.202838E+09 44946751.01
October 0.113430E+09 64753215.96 48676450.25 0.179186E+09 0.105945E+09
November 0.102311E+09 62016171.25 40294945.97 0.142403E+09 0.135905E+09
December 85115552.77 48593588.74 36521964.03 0.109174E+09 0.173318E+09
           
Annual Sum or Average 0.146192E+10 0.783301E+09 0.678614E+09 0.248702E+10 0.105988E+10
Minimum of Months 76160820.73 36973544.43 36521964.03 90525435.93 28341192.51
Maximum of Months 0.174606E+09 0.100989E+09 75968144.63 0.351635E+09 0.173318E+09



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 1133.17 394.33 737.61 591.17 146.44 0.00 0.00
February 649.37 351.98 463.54 315.65 147.89 0.00 0.00
March 521.76 317.82 350.32 173.95 176.37 0.00 0.00
April 422.10 202.47 233.95 61.22 172.73 0.00 0.00
May 326.67 148.15 166.25 1.14 165.11 0.00 0.00
June 432.45 76.77 163.99 0.00 163.99 0.00 0.00
July 385.50 69.95 156.77 0.81 155.96 0.00 0.00
August 404.14 85.31 164.60 16.67 147.93 0.00 0.00
September 570.87 125.68 280.39 105.72 174.67 0.00 0.00
October 868.71 287.49 526.32 364.41 161.90 0.00 0.00
November 945.10 381.13 628.99 484.36 144.64 0.00 0.00
December 998.03 477.00 685.37 544.77 140.59 0.00 0.00
               
Annual Sum or Average 638.56 242.79 379.73 221.53 158.21 0.00 0.00
Minimum of Months 326.67 69.95 156.77 0.00 140.59 0.00 0.00
Maximum of Months 1133.17 477.00 737.61 591.17 176.37 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 197.22 188.21 151.03 94.92 56.10 0.00 0.00
February 172.16 179.99 147.41 85.01 62.41 0.00 0.00
March 244.72 158.30 182.75 94.24 88.52 0.00 0.00
April 425.53 100.79 260.00 153.59 106.41 0.00 0.00
May 465.46 76.44 267.75 156.91 110.83 0.00 0.00
June 551.63 39.72 278.79 170.69 108.09 0.00 0.00
July 459.42 37.24 234.10 130.50 103.60 0.00 0.00
August 441.05 45.62 223.58 126.46 97.12 0.00 0.00
September 342.81 62.65 183.73 88.32 95.40 0.00 0.00
October 284.60 143.52 188.00 114.41 73.58 0.00 0.00
November 181.19 191.49 145.43 87.66 57.76 0.00 0.00
December 148.77 238.44 133.05 80.73 52.32 0.00 0.00
               
Annual Sum or Average 326.94 121.64 199.87 115.43 84.44 0.00 0.00
Minimum of Months 148.77 37.24 133.05 80.73 52.32 0.00 0.00
Maximum of Months 551.63 238.44 278.79 170.69 110.83 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 63.14 291.30 70.57 0.00 70.57 0.00 0.00
February 44.19 278.46 79.04 0.00 79.04 0.00 0.00
March 110.04 246.83 105.18 0.00 105.18 0.00 0.00
April 219.32 153.06 130.06 1.23 128.83 0.00 0.00
May 284.70 109.86 149.40 10.43 138.97 0.00 0.00
June 423.89 58.37 171.39 28.26 143.13 0.00 0.00
July 351.53 54.17 146.85 13.85 133.00 0.00 0.00
August 300.90 65.73 120.53 2.64 117.89 0.00 0.00
September 246.30 94.76 113.32 0.03 113.29 0.00 0.00
October 122.26 223.51 88.79 0.00 88.79 0.00 0.00
November 54.07 298.36 73.56 0.00 73.56 0.00 0.00
December 33.88 374.34 65.57 0.00 65.57 0.00 0.00
               
Annual Sum or Average 188.51 187.04 109.63 4.71 104.92 0.00 0.00
Minimum of Months 33.88 54.17 65.57 0.00 65.57 0.00 0.00
Maximum of Months 423.89 374.34 171.39 28.26 143.13 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 232.49 209.31 158.36 98.67 59.69 0.00 0.00
February 149.68 190.23 125.93 61.13 64.79 0.00 0.00
March 229.06 170.03 165.62 79.12 86.50 0.00 0.00
April 429.12 117.56 253.97 143.43 110.55 0.00 0.00
May 454.02 90.65 252.86 139.41 113.45 0.00 0.00
June 542.65 48.96 269.45 155.85 113.61 0.00 0.00
July 394.97 42.32 193.74 88.64 105.10 0.00 0.00
August 381.88 50.42 185.99 91.90 94.09 0.00 0.00
September 313.02 69.36 162.35 67.54 94.81 0.00 0.00
October 267.61 158.22 169.40 96.71 72.69 0.00 0.00
November 219.80 209.73 157.90 95.71 62.19 0.00 0.00
December 163.14 258.83 127.15 72.60 54.56 0.00 0.00
               
Annual Sum or Average 315.47 134.43 185.43 99.36 86.08 0.00 0.00
Minimum of Months 149.68 42.32 125.93 61.13 54.56 0.00 0.00
Maximum of Months 542.65 258.83 269.45 155.85 113.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.303509E+10 0.105619E+10 0.197562E+10 0.158340E+10 0.392221E+09 0.00 0.00
February 0.157096E+10 0.851510E+09 0.112139E+10 0.763609E+09 0.357776E+09 0.00 0.00
March 0.139749E+10 0.851246E+09 0.938300E+09 0.465903E+09 0.472397E+09 0.00 0.00
April 0.109410E+10 0.524798E+09 0.606407E+09 0.158685E+09 0.447722E+09 0.00 0.00
May 0.874965E+09 0.396815E+09 0.445281E+09 3042240.72 0.442239E+09 0.00 0.00
June 0.112092E+10 0.198986E+09 0.425067E+09 0.32 0.425067E+09 0.00 0.00
July 0.103252E+10 0.187362E+09 0.419904E+09 2176331.11 0.417728E+09 0.00 0.00
August 0.108244E+10 0.228489E+09 0.440869E+09 44652558.49 0.396217E+09 0.00 0.00
September 0.147969E+10 0.325758E+09 0.726758E+09 0.274020E+09 0.452738E+09 0.00 0.00
October 0.232674E+10 0.770023E+09 0.140969E+10 0.976042E+09 0.433645E+09 0.00 0.00
November 0.244971E+10 0.987899E+09 0.163035E+10 0.125545E+10 0.374902E+09 0.00 0.00
December 0.267313E+10 0.127760E+10 0.183569E+10 0.145912E+10 0.376569E+09 0.00 0.00
               
Annual Sum or Average 0.201377E+11 0.765667E+10 0.119753E+11 0.698610E+10 0.498922E+10 0.00 0.00
Minimum of Months 0.874965E+09 0.187362E+09 0.419904E+09 0.32 0.357776E+09 0.00 0.00
Maximum of Months 0.303509E+10 0.127760E+10 0.197562E+10 0.158340E+10 0.472397E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.528221E+09 0.504091E+09 0.404511E+09 0.254241E+09 0.150269E+09 0.00 0.00
February 0.416482E+09 0.435426E+09 0.356625E+09 0.205651E+09 0.150975E+09 0.00 0.00
March 0.655456E+09 0.424001E+09 0.489486E+09 0.252401E+09 0.237085E+09 0.00 0.00
April 0.110297E+10 0.261244E+09 0.673929E+09 0.398108E+09 0.275821E+09 0.00 0.00
May 0.124669E+10 0.204740E+09 0.717137E+09 0.420281E+09 0.296857E+09 0.00 0.00
June 0.142981E+10 0.102944E+09 0.722614E+09 0.442438E+09 0.280176E+09 0.00 0.00
July 0.123052E+10 99741675.35 0.627012E+09 0.349521E+09 0.277491E+09 0.00 0.00
August 0.118131E+10 0.122196E+09 0.598836E+09 0.338714E+09 0.260122E+09 0.00 0.00
September 0.888560E+09 0.162394E+09 0.476224E+09 0.228935E+09 0.247289E+09 0.00 0.00
October 0.762260E+09 0.384401E+09 0.503532E+09 0.306448E+09 0.197084E+09 0.00 0.00
November 0.469644E+09 0.496344E+09 0.376944E+09 0.227223E+09 0.149721E+09 0.00 0.00
December 0.398474E+09 0.638644E+09 0.356364E+09 0.216234E+09 0.140130E+09 0.00 0.00
               
Annual Sum or Average 0.103104E+11 0.383617E+10 0.630322E+10 0.364020E+10 0.266302E+10 0.00 0.00
Minimum of Months 0.398474E+09 99741675.35 0.356364E+09 0.205651E+09 0.140130E+09 0.00 0.00
Maximum of Months 0.142981E+10 0.638644E+09 0.722614E+09 0.442438E+09 0.296857E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.169101E+09 0.780207E+09 0.189005E+09 0.00 0.189005E+09 0.00 0.00
February 0.106912E+09 0.673656E+09 0.191203E+09 0.00 0.191203E+09 0.00 0.00
March 0.294740E+09 0.661116E+09 0.281710E+09 0.00 0.281710E+09 0.00 0.00
April 0.568478E+09 0.396733E+09 0.337126E+09 3199164.74 0.333927E+09 0.00 0.00
May 0.762536E+09 0.294258E+09 0.400145E+09 27933184.01 0.372212E+09 0.00 0.00
June 0.109871E+10 0.151298E+09 0.444242E+09 73252181.00 0.370990E+09 0.00 0.00
July 0.941546E+09 0.145100E+09 0.393312E+09 37092258.76 0.356219E+09 0.00 0.00
August 0.805924E+09 0.176064E+09 0.322826E+09 7060552.78 0.315766E+09 0.00 0.00
September 0.638421E+09 0.245606E+09 0.293718E+09 76570.44 0.293641E+09 0.00 0.00
October 0.327453E+09 0.598642E+09 0.237819E+09 0.00 0.237819E+09 0.00 0.00
November 0.140153E+09 0.773340E+09 0.190679E+09 0.00 0.190679E+09 0.00 0.00
December 90754132.56 0.100263E+10 0.175635E+09 0.00 0.175635E+09 0.00 0.00
               
Annual Sum or Average 0.594473E+10 0.589865E+10 0.345742E+10 0.148614E+09 0.330881E+10 0.00 0.00
Minimum of Months 90754132.56 0.145100E+09 0.175635E+09 0.00 0.175635E+09 0.00 0.00
Maximum of Months 0.109871E+10 0.100263E+10 0.444242E+09 73252181.00 0.372212E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.622695E+09 0.560614E+09 0.424162E+09 0.264276E+09 0.159887E+09 0.00 0.00
February 0.362107E+09 0.460197E+09 0.304643E+09 0.147896E+09 0.156747E+09 0.00 0.00
March 0.613503E+09 0.455395E+09 0.443592E+09 0.211906E+09 0.231686E+09 0.00 0.00
April 0.111228E+10 0.304712E+09 0.658298E+09 0.371760E+09 0.286538E+09 0.00 0.00
May 0.121605E+10 0.242791E+09 0.677270E+09 0.373402E+09 0.303869E+09 0.00 0.00
June 0.140654E+10 0.126917E+09 0.698421E+09 0.403956E+09 0.294465E+09 0.00 0.00
July 0.105789E+10 0.113362E+09 0.518908E+09 0.237407E+09 0.281501E+09 0.00 0.00
August 0.102284E+10 0.135047E+09 0.498166E+09 0.246144E+09 0.252023E+09 0.00 0.00
September 0.811346E+09 0.179783E+09 0.420817E+09 0.175060E+09 0.245757E+09 0.00 0.00
October 0.716757E+09 0.423774E+09 0.453720E+09 0.259016E+09 0.194704E+09 0.00 0.00
November 0.569715E+09 0.543611E+09 0.409283E+09 0.248091E+09 0.161192E+09 0.00 0.00
December 0.436956E+09 0.693244E+09 0.340564E+09 0.194441E+09 0.146122E+09 0.00 0.00
               
Annual Sum or Average 0.994867E+10 0.423945E+10 0.584785E+10 0.313335E+10 0.271449E+10 0.00 0.00
Minimum of Months 0.362107E+09 0.113362E+09 0.304643E+09 0.147896E+09 0.146122E+09 0.00 0.00
Maximum of Months 0.140654E+10 0.693244E+09 0.698421E+09 0.403956E+09 0.303869E+09 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 14.83 7.47 -0.8 2.99 -0.8 34.08 283.26 0.00
February 12.72 9.35 6.24 2.64 2.53 52.02 191.85 0.02
March 15.42 8.67 1.96 3.53 3.02 74.19 207.67 0.01
April 23.31 10.14 -4.1 3.42 6.81 72.47 350.22 0.00
May 26.31 11.07 -4.9 3.62 8.60 75.22 359.64 0.00
June 31.20 14.28 0.18 3.69 15.53 67.31 396.02 0.00
July 30.42 17.99 9.86 3.72 19.28 82.46 278.62 0.02
August 29.82 18.15 11.14 3.33 18.26 71.82 270.19 0.02
September 27.75 17.59 11.45 3.72 17.29 82.54 200.28 0.01
October 20.87 10.99 1.63 3.42 6.03 49.01 269.00 0.00
November 15.43 8.80 1.49 3.02 1.83 40.49 251.35 0.01
December 11.86 4.25 -5.9 2.21 -4.3 34.74 244.35 0.00
                 
Annual Sum or Average 21.70 11.57 2.33 3.28 7.86 61.39 275.62 0.01
Minimum of Months 11.86 4.25 -5.9 2.21 -4.3 34.08 191.85 0.00
Maximum of Months 31.20 18.15 11.45 3.72 19.28 82.54 396.02 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 29.00 31-JAN-15:00 10.73 -14.0 2.10 7.75 109.00 697.00
February 22.00 18-FEB-14:09 14.42 9.67 5.20 14.10 264.00 225.33
March 28.80 16-MAR-15:20 13.79 1.47 3.77 14.35 156.17 666.17
April 35.00 14-APR-14:00 14.57 -4.0 1.50 19.70 150.00 819.50
May 37.00 15-MAY-16:00 15.57 -2.0 4.60 20.75 127.50 679.00
June 42.00 16-JUN-15:00 16.74 -5.0 5.70 25.49 135.00 753.50
July 40.00 12-JUL-13:00 19.40 7.00 2.10 27.95 147.00 3.00
August 41.00 25-AUG-14:09 17.27 -0.7 3.43 25.74 162.33 768.67
September 38.30 08-SEP-14:00 19.81 10.00 3.00 25.82 142.00 699.00
October 37.00 01-OCT-12:00 19.01 9.00 4.10 27.14 262.50 136.00
November 29.00 01-NOV-14:00 16.20 8.00 2.60 16.49 73.50 907.50
December 26.00 21-DEC-14:00 10.90 -5.0 2.60 7.35 68.50 756.50
                 
Annual Sum or Average                
Minimum of Months 22.00   10.73 -14.0 1.50 7.35 68.50 3.00
Maximum of Months 42.00   19.81 10.00 5.70 27.95 264.00 907.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.50 01-JAN-07:00 -1.2 -3.3 3.30 -16.2 17.50 352.00
February 5.00 01-FEB-04:00 3.59 2.00 3.10 -10.7 0.00 0.00
March 0.50 26-MAR-03:00 -2.4 -6.7 2.50 -17.0 0.00 0.00
April 8.00 21-APR-03:00 0.42 -14.0 1.00 -11.7 0.00 0.00
May 12.00 01-MAY-03:00 3.97 -7.0 2.60 -6.2 0.00 0.00
June 18.00 21-JUN-04:00 8.24 -2.0 1.50 3.48 0.00 0.00
July 18.00 01-JUL-05:00 6.53 -9.0 3.10 -1.2 16.00 325.00
August 17.00 05-AUG-17:00 15.02 14.00 5.70 11.46 29.00 0.00
September 16.60 22-SEP-05:00 13.83 12.20 3.00 4.92 0.00 0.00
October 5.00 25-OCT-05:00 0.48 -6.0 3.10 -12.7 0.00 0.00
November 0.00 23-NOV-05:00 -2.5 -6.0 2.10 -17.3 0.00 0.00
December -1.1 07-DEC-04:00 -5.6 -16.0 3.10 -20.8 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -1.1   -5.6 -16.0 1.00 -20.8 0.00 0.00
Maximum of Months 18.00   15.02 14.00 5.70 11.46 29.00 352.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.66 08-JAN-15:00 18.00 16.00 4.60 11.46 102.00 332.00
February 14.73 18-FEB-17:00 16.00 14.00 6.20 10.50 0.00 0.00
March 15.18 17-MAR-10:00 25.50 8.30 2.50 18.46 167.50 459.00
April 15.71 11-APR-14:00 33.00 3.00 2.10 15.94 178.50 758.00
May 15.57 15-MAY-16:00 37.00 -2.0 4.60 20.75 127.50 679.00
June 23.18 17-JUN-15:00 41.00 16.00 3.60 31.13 257.00 9.00
July 23.11 13-JUL-17:00 26.00 22.00 4.60 22.13 79.00 56.50
August 22.19 16-AUG-10:00 35.00 17.00 2.10 24.33 140.50 837.00
September 22.23 01-SEP-11:00 34.40 17.20 4.60 23.82 193.50 725.50
October 21.53 01-OCT-17:00 32.00 17.00 2.10 25.33 30.50 1.50
November 18.59 12-NOV-14:00 20.00 18.00 3.10 15.39 115.00 0.00
December 12.06 12-DEC-12:00 20.00 6.00 1.50 12.60 182.50 6.00
                 
Annual Sum or Average                
Minimum of Months 12.06   16.00 -2.0 1.50 10.50 0.00 0.00
Maximum of Months 23.18   41.00 22.00 6.20 31.13 257.00 837.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.00 08-JAN-15:00 18.00 16.66 4.60 11.46 102.00 332.00
February 14.00 18-FEB-17:00 16.00 14.73 6.20 10.50 0.00 0.00
March 13.30 06-MAR-10:00 14.40 13.70 6.10 10.69 254.50 82.00
April 8.00 15-APR-20:00 23.00 14.00 6.20 7.75 0.00 0.00
May 9.00 26-MAY-02:00 21.00 13.75 3.60 16.30 0.00 0.00
June 16.00 17-JUN-15:00 41.00 23.18 3.60 31.13 257.00 9.00
July 22.00 13-JUL-17:00 26.00 23.11 4.60 22.13 79.00 56.50
August 20.00 09-AUG-17:00 25.00 21.44 5.10 19.17 35.00 0.00
September 20.50 02-SEP-22:10 22.62 21.05 3.18 20.17 0.00 0.00
October 19.00 03-OCT-02:00 23.00 20.15 2.10 10.30 0.00 0.00
November 18.00 12-NOV-14:00 20.00 18.59 3.10 15.39 115.00 0.00
December 10.00 12-DEC-23:00 12.00 10.87 1.50 7.55 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 8.00   12.00 10.87 1.50 7.55 0.00 0.00
Maximum of Months 22.00   41.00 23.18 6.20 31.13 257.00 332.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 18.65 31.23 0.00
February 18.00 13.00 16.00 19.06 29.93 0.00
March 18.00 13.00 16.00 20.99 39.76 0.00
April 18.00 13.00 16.00 24.03 60.89 0.00
May 18.00 13.00 16.00 27.32 65.75 0.00
June 18.00 13.00 16.00 29.99 69.24 0.00
July 18.00 13.00 16.00 31.31 56.42 0.00
August 18.00 13.00 16.00 30.91 52.05 0.00
September 18.00 13.00 16.00 28.91 42.71 0.00
October 18.00 13.00 16.00 25.85 39.20 0.00
November 18.00 13.00 16.00 22.56 30.64 0.00
December 18.00 13.00 16.00 19.93 27.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 24.99 45.50 0.00
Minimum of Months 18.00 13.00 16.00 18.65 27.41 0.00
Maximum of Months 18.00 13.00 16.00 31.31 69.24 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.522586E+09 -410142403.5 0.00 0.00 744.00 0.00 -112443910.5 58.98 0.00 0.00
February 0.470214E+09 -367457912.0 0.00 0.00 672.00 0.00 -102755619.9 58.99 0.00 0.00
March 0.534744E+09 -422742177.6 0.00 0.00 744.00 0.00 -112002200.4 58.99 0.00 0.00
April 0.442471E+09 -338554370.4 0.00 0.00 720.00 0.00 -103916341.8 58.99 0.00 0.00
May 0.444285E+09 -338336854.7 0.00 0.00 744.00 0.00 -105947873.4 58.99 0.00 0.00
June 0.408808E+09 -308471348.9 0.00 0.00 720.00 0.00 -100337127.7 58.99 0.00 0.00
July 0.370271E+09 -267760552.4 0.00 0.00 744.00 0.00 -102510889.9 58.99 0.00 0.00
August 0.416793E+09 -312727107.4 0.00 0.00 744.00 0.00 -104065615.7 58.99 0.00 0.00
September 0.392221E+09 -291921870.1 0.00 0.00 720.00 0.00 -100298821.7 58.99 0.00 0.00
October 0.443827E+09 -337247617.0 0.00 0.00 744.00 0.00 -106579215.2 58.98 0.00 0.00
November 0.476780E+09 -370178039.0 0.00 0.00 720.00 0.00 -106602222.7 58.99 0.00 0.00
December 0.490396E+09 -377846442.2 0.00 0.00 744.00 0.00 -112549095.5 58.99 0.00 0.00
                     
Annual Sum or Average 0.541340E+10 -0.414339E+10 0.00 0.00 8760.00 0.00 -0.127001E+10 58.99 0.00 0.00
Minimum of Months 0.370271E+09 -422742177.6 0.00 0.00 672.00 0.00 -112549095.5 58.98 0.00 0.00
Maximum of Months 0.534744E+09 -267760552.4 0.00 0.00 744.00 0.00 -100298821.7 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.77 0.76 01-JAN-07:00 2239.94 28.67 180.00 278.17 533.36 20.82 136.17 230.83
February 241.00 0.78 0.76 01-FEB-07:49 2605.50 28.68 148.50 202.50 439.26 20.85 117.33 148.00
March 344.33 0.81 0.76 01-MAR-07:40 404.36 16.53 2.33 218.83 312.33 20.63 176.67 151.50
April 380.33 0.82 0.76 01-APR-12:30 299.54 15.90 0.00 107.00 226.25 20.05 101.67 29.33
May 403.17 0.85 0.76 03-MAY-11:20 233.29 15.29 0.00 20.67 176.27 19.55 37.50 0.00
June 418.17 0.87 0.76 04-JUN-12:20 195.90 14.33 0.00 2.17 151.14 18.65 8.00 0.00
July 399.50 0.85 0.76 01-JUL-12:09 224.31 14.89 0.00 18.50 168.61 19.13 58.50 0.00
August 361.83 0.84 0.76 01-AUG-09:09 253.77 15.42 0.00 59.67 190.45 19.66 68.50 5.17
September 350.17 0.81 0.76 01-SEP-07:49 371.21 16.38 0.00 201.00 279.24 20.54 180.33 110.67
October 348.00 0.79 0.76 01-OCT-07:40 719.17 17.31 22.67 258.17 388.56 20.59 142.83 199.83
November 288.50 0.78 0.76 01-NOV-07:49 2050.86 27.23 157.00 245.50 542.80 23.50 154.00 216.17
December 290.67 0.77 0.76 01-DEC-07:40 1833.36 28.05 161.67 260.83 626.84 24.35 175.50 239.67
                         
Annual Sum or Average 4135.50 0.82     831.18 19.10 672.17 1873.00 316.06 20.52 1357.00 1331.17
Minimum of Months 241.00 0.77 0.76   195.90 14.33 0.00 2.17 151.14 18.65 8.00 0.00
Maximum of Months 418.17 0.87 0.76   2605.50 28.68 180.00 278.17 626.84 24.35 180.33 239.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.86 0.76 01-JAN-08:20 917.48 18.94 59.17 89.67 684.44 20.33 75.17 79.50
February 241.00 0.85 0.76 01-FEB-08:20 1017.70 18.92 45.33 80.33 862.09 20.74 62.33 70.00
March 344.33 0.85 0.76 01-MAR-07:00 303.13 15.38 1.17 111.33 255.49 14.98 2.33 86.50
April 380.33 0.85 0.76 01-APR-07:10 306.12 14.63 0.00 116.33 275.84 14.48 0.00 105.67
May 403.17 0.84 0.76 01-MAY-06:30 306.85 14.15 0.00 131.50 282.62 14.02 0.00 120.67
June 418.17 0.85 0.76 01-JUN-06:19 283.00 13.22 0.00 125.00 264.30 13.13 0.00 117.50
July 399.50 0.85 0.76 01-JUL-06:19 289.23 13.93 0.00 121.67 260.59 13.61 0.00 111.50
August 361.83 0.85 0.76 01-AUG-06:49 295.00 14.44 0.00 116.00 264.20 14.19 0.00 103.33
September 350.17 0.85 0.76 01-SEP-06:00 299.67 15.46 0.17 108.00 249.80 14.91 0.00 82.50
October 348.00 0.86 0.76 01-OCT-07:40 361.77 15.21 9.33 109.17 277.90 14.81 7.33 89.50
November 288.50 0.86 0.76 01-NOV-08:09 859.77 19.25 58.67 78.67 488.63 18.83 54.33 69.33
December 290.67 0.86 0.76 01-DEC-07:00 1291.47 21.90 86.67 89.67 702.67 20.90 76.50 69.67
                         
Annual Sum or Average 4135.50 0.85     500.29 15.94 260.50 1277.33 378.74 15.85 278.00 1105.67
Minimum of Months 241.00 0.84 0.76   283.00 13.22 0.00 78.67 249.80 13.13 0.00 69.33
Maximum of Months 418.17 0.86 0.76   1291.47 21.90 86.67 131.50 862.09 20.90 76.50 120.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.93 0.87 23-JAN-14:30 102.60 0.00 0.00 0.00 82.22 0.00 0.00 0.00
February 241.00 0.92 0.85 14-FEB-14:30 128.57 0.00 0.00 0.00 96.05 0.00 0.00 0.00
March 344.33 0.90 0.76 14-MAR-14:30 149.96 0.00 0.00 0.00 108.08 0.00 0.00 0.00
April 380.33 0.88 0.76 07-APR-15:30 182.91 0.00 0.00 0.00 132.13 0.00 0.00 0.00
May 403.17 0.86 0.76 01-MAY-17:30 213.03 0.00 0.00 1.17 152.14 0.00 0.00 1.50
June 418.17 0.86 0.76 01-JUN-17:10 217.45 0.00 0.00 6.83 217.45 0.00 0.00 48.83
July 399.50 0.86 0.76 02-JUL-17:19 217.34 0.00 0.00 4.50 151.18 0.00 0.00 0.00
August 361.83 0.88 0.76 02-AUG-16:19 184.10 0.00 0.00 0.00 130.67 0.00 0.00 0.00
September 350.17 0.89 0.76 03-SEP-11:30 172.09 0.00 0.00 0.67 122.22 0.00 0.00 0.00
October 348.00 0.92 0.80 07-OCT-09:30 120.34 0.00 0.00 0.00 91.58 0.00 0.00 0.00
November 288.50 0.93 0.85 03-NOV-14:30 112.01 0.00 0.00 0.00 86.75 0.00 0.00 0.00
December 290.67 0.93 0.87 31-DEC-12:30 103.50 0.00 0.00 0.00 81.81 0.00 0.00 0.00
                         
Annual Sum or Average 4135.50 0.90     164.13 0.00 0.00 13.17 125.62 0.00 0.00 50.33
Minimum of Months 241.00 0.86 0.76   102.60 0.00 0.00 0.00 81.81 0.00 0.00 0.00
Maximum of Months 418.17 0.93 0.87   217.45 0.00 0.00 6.83 217.45 0.00 0.00 48.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 309.83 0.86 0.76 01-JAN-14:09 1352.24 20.62 88.00 99.83 756.19 19.67 78.67 83.33
February 241.00 0.86 0.76 01-FEB-14:09 844.55 18.13 44.83 74.67 389.27 17.48 38.17 60.17
March 344.33 0.85 0.76 02-MAR-12:20 288.13 15.21 0.33 110.17 234.96 14.65 0.00 75.33
April 380.33 0.85 0.76 01-APR-14:09 317.73 14.66 0.00 127.17 285.67 14.47 0.00 113.83
May 403.17 0.85 0.76 01-MAY-13:39 302.52 14.22 0.00 119.83 277.26 14.04 0.00 111.83
June 418.17 0.85 0.76 01-JUN-13:00 288.78 13.36 0.00 124.67 270.65 13.25 0.00 115.83
July 399.50 0.86 0.76 01-JUL-13:00 266.79 14.00 0.00 98.67 235.51 13.65 0.00 83.00
August 361.83 0.86 0.76 01-AUG-13:09 267.10 14.22 0.00 90.83 234.75 13.87 0.00 77.83
September 350.17 0.85 0.76 01-SEP-13:09 287.44 15.40 1.00 102.33 260.99 15.06 5.50 74.17
October 348.00 0.86 0.76 01-OCT-11:20 361.46 15.11 8.17 101.00 606.32 17.38 59.17 84.00
November 288.50 0.85 0.76 01-NOV-12:09 899.69 18.96 56.17 93.17 617.04 19.25 64.33 81.50
December 290.67 0.86 0.76 01-DEC-13:09 819.96 19.58 66.83 87.33 481.40 18.92 61.67 67.00
                         
Annual Sum or Average 4135.50 0.86     486.72 15.82 265.33 1229.67 372.86 15.69 307.50 1027.83
Minimum of Months 241.00 0.85 0.76   266.79 13.36 0.00 74.67 234.75 13.25 0.00 60.17
Maximum of Months 418.17 0.86 0.76   1352.24 20.62 88.00 127.17 756.19 19.67 78.67 115.83



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HEATING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 4167826.72 6589.31 02-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 4167826.72     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 4167826.72 6589.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HEATING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 13123150.00 7693.49 02-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 35298370.41 4784.02 13-FEB-07:03 0.00 0.00 0.00 0.00 0.00
March 60664883.24 6726.79 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 42412156.52 3799.65 05-DEC-08:62 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.151499E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 60664883.24 7693.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HEATING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 10807344.70 5271.65 02-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 1280366.10 1800.26 13-FEB-08:63 0.00 0.00 0.00 0.00 0.00
March 4346278.09 4609.26 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 2931615.03 2562.67 07-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 19365603.93     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 10807344.70 5271.65   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HEATING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 51181832.37 7912.15 02-JAN-08:62 0.00 0.00 0.00 0.00 0.00
February 13238075.73 5134.09 27-FEB-08:62 0.00 0.00 0.00 0.00 0.00
March 22867493.44 6701.91 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 298501.21 1990.01 24-NOV-08:62 0.00 0.00 0.00 0.00 0.00
December 25293804.43 7022.60 18-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.112880E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 51181832.37 7912.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HEATING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 13221307.44 6174.30 02-JAN-07:02 0.00 0.00 0.00 0.00 0.00
February 3229570.86 2453.06 13-FEB-08:63 0.00 0.00 0.00 0.00 0.00
March 5460485.70 5398.49 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 5288190.35 2504.88 18-DEC-08:63 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 27199554.34     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 13221307.44 6174.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 399846.53 3998.47 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 399846.53     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 399846.53 3998.47   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 180858.63 1808.59 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 180858.63     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 180858.63 1808.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 474439.76 3953.66 02-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 395366.46 3953.66 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 164276.45 802.33 07-DEC-07:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1034082.67     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 474439.76 3953.66   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5_SUPPHEATCOIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 80374.46 803.74 27-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 80374.46     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 80374.46 803.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:1 HP COOLING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.146111E+10 0.142775E+10 4306.22 27-JAN-08:63 4306.22 0.00
February 0.00 0.00 0.937636E+09 0.828414E+09 2699.31 10-FEB-08:63 2699.31 0.00
March 0.00 0.00 0.161964E+10 0.153464E+10 6695.44 17-MAR-07:03 6495.32 0.00
April 0.00 0.00 0.302896E+10 0.302479E+10 6792.73 26-APR-06:03 6792.73 0.00
May 0.00 0.00 0.404770E+10 0.404770E+10 6815.69 11-MAY-06:02 6815.69 0.00
June 0.00 0.00 0.502759E+10 0.501179E+10 7011.73 20-JUN-05:03 7011.73 0.00
July 0.00 0.00 0.511773E+10 0.460887E+10 7555.40 14-JUL-06:02 5019.72 0.00
August 0.00 0.00 0.570143E+10 0.509946E+10 7395.24 10-AUG-06:01 5522.97 0.00
September 0.00 0.00 0.473433E+10 0.423986E+10 7413.36 05-SEP-05:01 6163.93 0.00
October 0.00 0.00 0.338452E+10 0.323930E+10 7301.88 03-OCT-06:02 5802.79 0.00
November 0.00 0.00 0.222065E+10 0.205567E+10 7195.30 14-NOV-08:62 4842.54 0.00
December 0.00 0.00 0.109038E+10 0.108049E+10 3507.51 26-DEC-08:62 3507.51 0.00
                 
Annual Sum or Average 0.00 0.00 0.383717E+11 0.361987E+11       0.00
Minimum of Months 0.00 0.00 0.937636E+09 0.828414E+09 2699.31   2699.31 0.00
Maximum of Months 0.00 0.00 0.570143E+10 0.509946E+10 7555.40   7011.73 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:2 HP COOLING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.229293E+10 0.228741E+10 5961.12 30-JAN-14:40 5961.12 0.00
February 0.00 0.00 0.807909E+09 0.787338E+09 3646.14 01-FEB-15:30 3646.14 0.00
March 0.00 0.00 0.115071E+10 0.114588E+10 4037.54 16-MAR-15:30 4037.54 0.00
April 0.00 0.00 0.262028E+10 0.262028E+10 7971.79 26-APR-07:02 7971.79 0.00
May 0.00 0.00 0.334336E+10 0.334336E+10 8006.72 08-MAY-06:01 8006.72 0.00
June 0.00 0.00 0.490857E+10 0.490121E+10 8248.46 19-JUN-05:02 8248.46 0.00
July 0.00 0.00 0.530616E+10 0.489726E+10 9278.36 14-JUL-06:02 5535.72 0.00
August 0.00 0.00 0.597439E+10 0.551392E+10 8971.80 10-AUG-06:01 6376.43 0.00
September 0.00 0.00 0.536144E+10 0.496019E+10 9017.46 11-SEP-05:01 7189.40 0.00
October 0.00 0.00 0.407080E+10 0.398901E+10 8867.32 03-OCT-06:02 6936.70 0.00
November 0.00 0.00 0.291001E+10 0.282102E+10 8276.10 01-NOV-07:02 7901.76 0.00
December 0.00 0.00 0.165726E+10 0.165573E+10 6089.32 26-DEC-13:55 6089.32 0.00
                 
Annual Sum or Average 0.00 0.00 0.404038E+11 0.389226E+11       0.00
Minimum of Months 0.00 0.00 0.807909E+09 0.787338E+09 3646.14   3646.14 0.00
Maximum of Months 0.00 0.00 0.597439E+10 0.551392E+10 9278.36   8248.46 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:3 HP COOLING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.639683E+09 0.637293E+09 1803.02 31-JAN-16:20 1803.02 0.00
February 0.00 0.00 0.273160E+09 0.263305E+09 1068.34 23-FEB-11:02 1021.69 0.00
March 0.00 0.00 0.635502E+09 0.633349E+09 1884.63 20-MAR-15:13 1884.63 0.00
April 0.00 0.00 0.190315E+10 0.190315E+10 5545.64 25-APR-06:02 5545.64 0.00
May 0.00 0.00 0.258164E+10 0.258164E+10 5571.76 30-MAY-06:01 5571.76 0.00
June 0.00 0.00 0.369913E+10 0.369612E+10 5668.75 18-JUN-08:42 5668.75 0.00
July 0.00 0.00 0.378621E+10 0.357548E+10 6347.25 14-JUL-06:02 3879.64 0.00
August 0.00 0.00 0.405208E+10 0.382299E+10 6163.95 10-AUG-06:01 4447.04 0.00
September 0.00 0.00 0.322499E+10 0.302497E+10 6186.31 11-SEP-05:01 4912.70 0.00
October 0.00 0.00 0.209495E+10 0.205439E+10 6071.69 03-OCT-06:02 4792.42 0.00
November 0.00 0.00 0.111854E+10 0.107780E+10 6032.56 13-NOV-08:62 3876.01 0.00
December 0.00 0.00 0.420736E+09 0.419979E+09 1524.48 22-DEC-15:15 1524.48 0.00
                 
Annual Sum or Average 0.00 0.00 0.244298E+11 0.236905E+11       0.00
Minimum of Months 0.00 0.00 0.273160E+09 0.263305E+09 1068.34   1021.69 0.00
Maximum of Months 0.00 0.00 0.405208E+10 0.382299E+10 6347.25   5668.75 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:4 HP COOLING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.563007E+09 0.560380E+09 2321.57 31-JAN-16:42 2321.57 0.00
February 0.00 0.00 0.155569E+09 0.143608E+09 1267.90 16-FEB-15:55 1154.92 0.00
March 0.00 0.00 0.615706E+09 0.611357E+09 2595.20 16-MAR-15:57 2595.20 0.00
April 0.00 0.00 0.215767E+10 0.215767E+10 8042.54 17-APR-07:02 8042.54 0.00
May 0.00 0.00 0.318319E+10 0.318319E+10 8030.96 30-MAY-06:01 8030.96 0.00
June 0.00 0.00 0.476804E+10 0.476225E+10 8221.15 19-JUN-05:02 8221.15 0.00
July 0.00 0.00 0.506324E+10 0.471254E+10 9235.07 14-JUL-06:02 5593.90 0.00
August 0.00 0.00 0.540580E+10 0.501542E+10 8941.16 10-AUG-06:01 6374.68 0.00
September 0.00 0.00 0.438478E+10 0.405360E+10 8971.51 11-SEP-05:01 7032.89 0.00
October 0.00 0.00 0.250109E+10 0.242980E+10 8829.00 03-OCT-06:02 6927.59 0.00
November 0.00 0.00 0.125163E+10 0.117961E+10 8755.01 13-NOV-08:62 5563.97 0.00
December 0.00 0.00 0.327287E+09 0.326387E+09 1950.15 22-DEC-16:00 1950.15 0.00
                 
Annual Sum or Average 0.00 0.00 0.303770E+11 0.291358E+11       0.00
Minimum of Months 0.00 0.00 0.155569E+09 0.143608E+09 1267.90   1154.92 0.00
Maximum of Months 0.00 0.00 0.540580E+10 0.501542E+10 9235.07   8221.15 0.00



Table of Contents

Report: CoilReportMonthly

For: PSZ-AC:5 HP COOLING COIL

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.708742E+09 0.705672E+09 2815.29 31-JAN-16:55 2815.29 0.00
February 0.00 0.00 0.285355E+09 0.271908E+09 1928.17 22-FEB-16:23 1873.85 0.00
March 0.00 0.00 0.606049E+09 0.601354E+09 2497.28 16-MAR-15:57 2497.28 0.00
April 0.00 0.00 0.176062E+10 0.176062E+10 6493.61 17-APR-07:02 6493.61 0.00
May 0.00 0.00 0.243091E+10 0.243091E+10 6532.90 30-MAY-06:01 6532.90 0.00
June 0.00 0.00 0.358585E+10 0.358205E+10 6570.50 05-JUN-05:02 6570.50 0.00
July 0.00 0.00 0.358504E+10 0.335853E+10 7435.71 14-JUL-06:02 4557.05 0.00
August 0.00 0.00 0.387799E+10 0.362683E+10 7221.39 10-AUG-06:01 5195.87 0.00
September 0.00 0.00 0.315088E+10 0.293529E+10 7247.62 11-SEP-05:01 5725.01 0.00
October 0.00 0.00 0.198335E+10 0.193690E+10 7108.47 03-OCT-06:02 5650.50 0.00
November 0.00 0.00 0.120844E+10 0.115627E+10 7081.84 13-NOV-08:62 4636.90 0.00
December 0.00 0.00 0.481323E+09 0.480403E+09 2747.63 22-DEC-16:27 2747.63 0.00
                 
Annual Sum or Average 0.00 0.00 0.236646E+11 0.228467E+11       0.00
Minimum of Months 0.00 0.00 0.285355E+09 0.271908E+09 1928.17   1873.85 0.00
Maximum of Months 0.00 0.00 0.387799E+10 0.362683E+10 7435.71   6570.50 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 164.86 513.97 23-JAN-12:13
February 0.00 0.00 01-FEB-00:10 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:05 0.00 0.00 01-JUL-00:05
August 0.00 0.00 01-AUG-00:10 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 0.00     14.00    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   164.86 513.97  



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:1 FAN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.413049E+09 0.37 420.28 02-JAN-06:02 1.01
February 0.373711E+09 0.37 420.28 01-FEB-06:05 1.01
March 0.452387E+09 0.40 420.28 01-MAR-06:10 1.01
April 0.393380E+09 0.36 420.28 03-APR-05:10 1.01
May 0.432718E+09 0.39 420.28 01-MAY-05:10 1.01
June 0.433318E+09 0.40 420.28 01-JUN-05:10 1.01
July 0.395251E+09 0.36 420.28 03-JUL-05:02 1.00
August 0.454749E+09 0.42 420.28 01-AUG-05:03 1.00
September 0.394515E+09 0.37 420.28 01-SEP-05:10 1.00
October 0.413049E+09 0.37 420.28 02-OCT-05:02 1.00
November 0.413049E+09 0.38 420.28 01-NOV-05:10 1.01
December 0.393380E+09 0.35 420.28 01-DEC-06:10 1.01
           
Annual Sum or Average 0.496256E+10 0.38      
Minimum of Months 0.373711E+09 0.35 420.28   1.00
Maximum of Months 0.454749E+09 0.42 420.28   1.01



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:2 FAN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.523120E+09 0.37 532.28 02-JAN-06:02 1.01
February 0.473299E+09 0.37 532.28 01-FEB-06:05 1.01
March 0.572941E+09 0.41 532.28 01-MAR-06:10 1.01
April 0.498210E+09 0.37 532.28 03-APR-05:10 1.02
May 0.548031E+09 0.39 532.28 01-MAY-05:10 1.02
June 0.554069E+09 0.44 532.28 01-JUN-05:10 1.01
July 0.510883E+09 0.42 532.28 03-JUL-05:02 1.02
August 0.586053E+09 0.46 532.28 01-AUG-05:03 1.00
September 0.515061E+09 0.44 532.28 01-SEP-05:10 1.00
October 0.531817E+09 0.41 532.28 02-OCT-05:02 1.00
November 0.523120E+09 0.38 532.28 01-NOV-05:10 1.01
December 0.498590E+09 0.36 532.28 01-DEC-06:10 1.01
           
Annual Sum or Average 0.633519E+10 0.40      
Minimum of Months 0.473299E+09 0.36 532.28   1.00
Maximum of Months 0.586053E+09 0.46 532.28   1.02



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:3 FAN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.375633E+09 0.37 382.21 02-JAN-06:02 1.01
February 0.339858E+09 0.37 382.21 01-FEB-06:05 1.01
March 0.411407E+09 0.41 382.21 01-MAR-06:10 1.01
April 0.357746E+09 0.37 382.21 03-APR-05:10 1.02
May 0.394400E+09 0.40 382.21 01-MAY-05:10 1.02
June 0.411117E+09 0.51 382.21 01-JUN-05:10 1.01
July 0.381038E+09 0.50 382.21 02-JUL-09:22 1.02
August 0.427983E+09 0.49 382.21 01-AUG-05:03 1.00
September 0.368152E+09 0.44 382.21 01-SEP-05:10 1.00
October 0.377000E+09 0.38 382.21 02-OCT-05:02 1.00
November 0.375633E+09 0.38 382.21 01-NOV-05:10 1.01
December 0.357746E+09 0.35 382.21 01-DEC-06:10 1.01
           
Annual Sum or Average 0.457771E+10 0.41      
Minimum of Months 0.339858E+09 0.35 382.21   1.00
Maximum of Months 0.427983E+09 0.51 382.21   1.02



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:4 FAN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.520962E+09 0.37 530.08 02-JAN-06:02 1.01
February 0.471346E+09 0.37 530.08 01-FEB-06:05 1.01
March 0.570577E+09 0.41 530.08 01-MAR-06:10 1.01
April 0.496154E+09 0.37 530.08 03-APR-05:10 1.02
May 0.545770E+09 0.39 530.08 01-MAY-05:10 1.02
June 0.554623E+09 0.45 530.08 01-JUN-05:10 1.01
July 0.510408E+09 0.42 530.08 02-JUL-18:42 1.02
August 0.581284E+09 0.46 530.08 01-AUG-05:03 1.00
September 0.500536E+09 0.39 530.08 01-SEP-05:10 1.00
October 0.521713E+09 0.37 530.08 02-OCT-05:02 1.00
November 0.520962E+09 0.38 530.08 01-NOV-05:10 1.01
December 0.496154E+09 0.35 530.08 01-DEC-06:10 1.01
           
Annual Sum or Average 0.629049E+10 0.39      
Minimum of Months 0.471346E+09 0.35 530.08   1.00
Maximum of Months 0.581284E+09 0.46 530.08   1.02



Table of Contents

Report: FanReportMonthly

For: PSZ-AC:5 FAN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.439952E+09 0.37 447.65 02-JAN-06:02 1.01
February 0.398051E+09 0.37 447.65 01-FEB-06:05 1.01
March 0.481852E+09 0.41 447.65 01-MAR-06:10 1.01
April 0.420263E+09 0.37 447.65 03-APR-05:10 1.02
May 0.466303E+09 0.42 447.65 01-MAY-05:10 1.02
June 0.487315E+09 0.54 447.65 01-JUN-05:10 1.01
July 0.446818E+09 0.50 447.65 01-JUL-18:12 1.02
August 0.502131E+09 0.50 447.65 01-AUG-05:03 1.00
September 0.430207E+09 0.43 447.65 01-SEP-05:10 1.00
October 0.442576E+09 0.39 447.65 02-OCT-05:02 1.00
November 0.439952E+09 0.38 447.65 01-NOV-05:10 1.01
December 0.419001E+09 0.35 447.65 01-DEC-06:10 1.01
           
Annual Sum or Average 0.537442E+10 0.42      
Minimum of Months 0.398051E+09 0.35 447.65   1.00
Maximum of Months 0.502131E+09 0.54 447.65   1.02



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.01 0.00 0.00 02-JAN-07:02 0.00 0.00 43.79 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00 18.53 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 18.53 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 0.00 18.53 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 0.00 18.53 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 18.53 0.00
July 0.00 0.00 0.00 01-JUL-00:05 0.00 0.00 18.53 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 0.00 18.53 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00 18.53 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00 18.53 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00 18.53 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00 18.53 0.00
                 
Annual Sum or Average 0.01 0.00            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 18.53 0.00
Maximum of Months 0.01 0.00 0.00   0.00 0.00 43.79 0.00



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 48.89 48.89 164.86 513.97 23-JAN-12:13
February 0.00 0.00 01-FEB-00:10 18.53 18.53 0.00 0.00 01-FEB-00:10
March 0.00 0.00 01-MAR-00:10 18.53 18.53 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:10 18.53 18.53 0.00 0.00 01-APR-00:10
May 0.00 0.00 01-MAY-00:10 18.53 18.53 0.00 0.00 01-MAY-00:10
June 0.00 0.00 01-JUN-00:10 18.53 18.53 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:05 18.53 18.53 0.00 0.00 01-JUL-00:05
August 0.00 0.00 01-AUG-00:10 18.53 18.53 0.00 0.00 01-AUG-00:10
September 0.00 0.00 01-SEP-00:10 18.53 18.53 0.00 0.00 01-SEP-00:10
October 0.00 0.00 01-OCT-00:10 18.53 18.53 0.00 0.00 01-OCT-00:10
November 0.00 0.00 01-NOV-00:10 18.53 18.53 0.00 0.00 01-NOV-00:10
December 0.00 0.00 01-DEC-00:10 18.53 18.53 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 0.00         14.00    
Minimum of Months 0.00 0.00   18.53 18.53 0.00 0.00  
Maximum of Months 0.00 0.00   48.89 48.89 164.86 513.97  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: ATTIC

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.740856E+09 0.00 0.00
February 0.00 0.00 0.00 0.581307E+09 0.00 0.00
March 0.00 0.00 0.00 0.816700E+09 0.00 0.00
April 0.00 0.00 0.00 0.110174E+10 0.00 0.00
May 0.00 0.00 0.00 0.141083E+10 0.00 0.00
June 0.00 0.00 0.00 0.172008E+10 0.00 0.00
July 0.00 0.00 0.00 0.163204E+10 0.00 0.00
August 0.00 0.00 0.00 0.183271E+10 0.00 0.00
September 0.00 0.00 0.00 0.150106E+10 0.00 0.00
October 0.00 0.00 0.00 0.118044E+10 0.00 0.00
November 0.00 0.00 0.00 0.899670E+09 0.00 0.00
December 0.00 0.00 0.00 0.638024E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.140555E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.581307E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.183271E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.102839E+10 0.00 0.00
February 0.00 0.00 0.00 0.663084E+09 0.00 0.00
March 0.00 0.00 0.00 0.859122E+09 0.00 0.00
April 0.00 0.00 0.00 0.113882E+10 0.00 0.00
May 0.00 0.00 0.00 0.140143E+10 0.00 0.00
June 0.00 0.00 0.00 0.187527E+10 0.00 0.00
July 0.00 0.00 0.00 0.184905E+10 0.00 0.00
August 0.00 0.00 0.00 0.209000E+10 0.00 0.00
September 0.00 0.00 0.00 0.180739E+10 0.00 0.00
October 0.00 0.00 0.00 0.146672E+10 0.00 0.00
November 0.00 0.00 0.00 0.115440E+10 0.00 0.00
December 0.00 0.00 0.00 0.875252E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.162089E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.663084E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.209000E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.526148E+09 0.00 0.00
February 0.00 0.00 0.00 0.402047E+09 0.00 0.00
March 0.00 0.00 0.00 0.561166E+09 0.00 0.00
April 0.00 0.00 0.00 0.816227E+09 0.00 0.00
May 0.00 0.00 0.00 0.103981E+10 0.00 0.00
June 0.00 0.00 0.00 0.139531E+10 0.00 0.00
July 0.00 0.00 0.00 0.133930E+10 0.00 0.00
August 0.00 0.00 0.00 0.145276E+10 0.00 0.00
September 0.00 0.00 0.00 0.115484E+10 0.00 0.00
October 0.00 0.00 0.00 0.869665E+09 0.00 0.00
November 0.00 0.00 0.00 0.628556E+09 0.00 0.00
December 0.00 0.00 0.00 0.457138E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.106430E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.402047E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.145276E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.668820E+09 0.00 0.00
February 0.00 0.00 0.00 0.511058E+09 0.00 0.00
March 0.00 0.00 0.00 0.724447E+09 0.00 0.00
April 0.00 0.00 0.00 0.102938E+10 0.00 0.00
May 0.00 0.00 0.00 0.135818E+10 0.00 0.00
June 0.00 0.00 0.00 0.183811E+10 0.00 0.00
July 0.00 0.00 0.00 0.179413E+10 0.00 0.00
August 0.00 0.00 0.00 0.195463E+10 0.00 0.00
September 0.00 0.00 0.00 0.157340E+10 0.00 0.00
October 0.00 0.00 0.00 0.112096E+10 0.00 0.00
November 0.00 0.00 0.00 0.807089E+09 0.00 0.00
December 0.00 0.00 0.00 0.583347E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.139635E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.511058E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.195463E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.607122E+09 0.00 0.00
February 0.00 0.00 0.00 0.463361E+09 0.00 0.00
March 0.00 0.00 0.00 0.626171E+09 0.00 0.00
April 0.00 0.00 0.00 0.855849E+09 0.00 0.00
May 0.00 0.00 0.00 0.109373E+10 0.00 0.00
June 0.00 0.00 0.00 0.147719E+10 0.00 0.00
July 0.00 0.00 0.00 0.138281E+10 0.00 0.00
August 0.00 0.00 0.00 0.151346E+10 0.00 0.00
September 0.00 0.00 0.00 0.121805E+10 0.00 0.00
October 0.00 0.00 0.00 0.920171E+09 0.00 0.00
November 0.00 0.00 0.00 0.713814E+09 0.00 0.00
December 0.00 0.00 0.00 0.532635E+09 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.00 0.114044E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.463361E+09 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.151346E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.413049E+09 0.146111E+10 4167826.72 0.00 0.00 0.00 0.00 0.00
February 0.373711E+09 0.937636E+09 0.00 0.00 0.00 0.00 0.00 0.00
March 0.452387E+09 0.161964E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.393380E+09 0.302896E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.432718E+09 0.404770E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.433318E+09 0.502759E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.395251E+09 0.511773E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.454749E+09 0.570143E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.394515E+09 0.473433E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.413049E+09 0.338452E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.413049E+09 0.222065E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.393380E+09 0.109038E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.496256E+10 0.383717E+11 4167826.72 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.373711E+09 0.937636E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.454749E+09 0.570143E+10 4167826.72 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.523120E+09 0.229293E+10 13123150.00 0.00 0.00 0.00 0.00 0.00
February 0.473299E+09 0.807909E+09 35298370.41 0.00 0.00 0.00 0.00 0.00
March 0.572941E+09 0.115071E+10 61064729.77 0.00 0.00 0.00 0.00 0.00
April 0.498210E+09 0.262028E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.548031E+09 0.334336E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.554069E+09 0.490857E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.510883E+09 0.530616E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.586053E+09 0.597439E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.515061E+09 0.536144E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.531817E+09 0.407080E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.523120E+09 0.291001E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.498590E+09 0.165726E+10 42412156.52 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.633519E+10 0.404038E+11 0.151898E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.473299E+09 0.807909E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.586053E+09 0.597439E+10 61064729.77 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.375633E+09 0.639683E+09 10807344.70 0.00 0.00 0.00 0.00 0.00
February 0.339858E+09 0.273160E+09 1280366.10 0.00 0.00 0.00 0.00 0.00
March 0.411407E+09 0.635502E+09 4527136.72 0.00 0.00 0.00 0.00 0.00
April 0.357746E+09 0.190315E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.394400E+09 0.258164E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.411117E+09 0.369913E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.381038E+09 0.378621E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.427983E+09 0.405208E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.368152E+09 0.322499E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377000E+09 0.209495E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.375633E+09 0.111854E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.357746E+09 0.420736E+09 2931615.03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.457771E+10 0.244298E+11 19546462.55 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.339858E+09 0.273160E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.427983E+09 0.405208E+10 10807344.70 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.520962E+09 0.563007E+09 51656272.13 0.00 0.00 0.00 0.00 0.00
February 0.471346E+09 0.155569E+09 13238075.73 0.00 0.00 0.00 0.00 0.00
March 0.570577E+09 0.615706E+09 23262859.90 0.00 0.00 0.00 0.00 0.00
April 0.496154E+09 0.215767E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.545770E+09 0.318319E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.554623E+09 0.476804E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.510408E+09 0.506324E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.581284E+09 0.540580E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.500536E+09 0.438478E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.521713E+09 0.250109E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.520962E+09 0.125163E+10 298501.21 0.00 0.00 0.00 0.00 0.00
December 0.496154E+09 0.327287E+09 25458080.89 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.629049E+10 0.303770E+11 0.113914E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.471346E+09 0.155569E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.581284E+09 0.540580E+10 51656272.13 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.439952E+09 0.708742E+09 13221307.44 0.00 0.00 0.00 0.00 0.00
February 0.398051E+09 0.285355E+09 3229570.86 0.00 0.00 0.00 0.00 0.00
March 0.481852E+09 0.606049E+09 5540860.16 0.00 0.00 0.00 0.00 0.00
April 0.420263E+09 0.176062E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.466303E+09 0.243091E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.487315E+09 0.358585E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.446818E+09 0.358504E+10 0.00 0.00 0.00 0.00 0.00 0.00
August 0.502131E+09 0.387799E+10 0.00 0.00 0.00 0.00 0.00 0.00
September 0.430207E+09 0.315088E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.442576E+09 0.198335E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.439952E+09 0.120844E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.419001E+09 0.481323E+09 5288190.35 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.537442E+10 0.236646E+11 27279928.80 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.398051E+09 0.285355E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.502131E+09 0.387799E+10 13221307.44 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.413049E+09 0.00 0.00 1427266.36 0.326380E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.373711E+09 0.00 0.00 0.00 0.207596E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.452387E+09 0.00 0.00 990000.00 0.363323E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.393380E+09 0.00 0.00 0.00 0.708365E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.432718E+09 0.00 0.00 0.00 0.978113E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.433318E+09 0.00 0.00 0.00 0.128677E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.395251E+09 0.00 0.00 0.00 0.123679E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.454749E+09 0.00 0.00 0.00 0.137796E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.394515E+09 0.00 0.00 0.00 0.110654E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.413049E+09 0.00 0.00 0.00 0.767395E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.413049E+09 0.00 0.00 180000.00 0.486441E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.393380E+09 0.00 0.00 3178939.25 0.241466E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.496256E+10 0.00 0.00 5776205.61 0.908713E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.373711E+09 0.00 0.00 0.00 0.207596E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.454749E+09 0.00 0.00 3178939.25 0.137796E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.523120E+09 0.00 0.00 4484553.16 0.500787E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.473299E+09 0.00 0.00 12007106.63 0.177778E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.572941E+09 0.00 0.00 22239512.25 0.263941E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.498210E+09 0.00 0.00 0.00 0.640609E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.548031E+09 0.00 0.00 0.00 0.853401E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.554069E+09 0.00 0.00 0.00 0.132120E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.510883E+09 0.00 0.00 0.00 0.133817E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.586053E+09 0.00 0.00 0.00 0.150394E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.515061E+09 0.00 0.00 0.00 0.129233E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.531817E+09 0.00 0.00 0.00 0.934906E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.523120E+09 0.00 0.00 180000.00 0.631098E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.498590E+09 0.00 0.00 19359115.48 0.357302E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.633519E+10 0.00 0.00 58270287.52 0.981546E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.473299E+09 0.00 0.00 0.00 0.177778E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.586053E+09 0.00 0.00 22239512.25 0.150394E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.375633E+09 0.00 0.00 3709387.38 0.146806E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.339858E+09 0.00 0.00 426371.84 61762588.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.411407E+09 0.00 0.00 2532458.44 0.147226E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.357746E+09 0.00 0.00 0.00 0.458481E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.394400E+09 0.00 0.00 0.00 0.645407E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.411117E+09 0.00 0.00 0.00 0.984197E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.381038E+09 0.00 0.00 0.00 0.958259E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.427983E+09 0.00 0.00 0.00 0.102478E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.368152E+09 0.00 0.00 0.00 0.786686E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377000E+09 0.00 0.00 0.00 0.492666E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.375633E+09 0.00 0.00 180000.00 0.252743E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.357746E+09 0.00 0.00 4246890.94 95145310.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.457771E+10 0.00 0.00 11095108.60 0.605416E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.339858E+09 0.00 0.00 0.00 61762588.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.427983E+09 0.00 0.00 4246890.94 0.102478E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.520962E+09 0.00 0.00 16601373.98 0.131257E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.471346E+09 0.00 0.00 4394542.45 35317452.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.570577E+09 0.00 0.00 8991255.85 0.144879E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.496154E+09 0.00 0.00 0.00 0.533224E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.545770E+09 0.00 0.00 0.00 0.812409E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.554623E+09 0.00 0.00 0.00 0.128349E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.510408E+09 0.00 0.00 0.00 0.128372E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.581284E+09 0.00 0.00 0.00 0.137334E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.500536E+09 0.00 0.00 0.00 0.107287E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.521713E+09 0.00 0.00 0.00 0.599244E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.520962E+09 0.00 0.00 282021.29 0.285845E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.496154E+09 0.00 0.00 12312806.11 74879552.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.629049E+10 0.00 0.00 42581999.69 0.763048E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.471346E+09 0.00 0.00 0.00 35317452.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.581284E+09 0.00 0.00 16601373.98 0.137334E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: PSZ-AC:5

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.439952E+09 0.00 0.00 4482545.65 0.162687E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.398051E+09 0.00 0.00 1083240.41 64226531.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.481852E+09 0.00 0.00 2929017.11 0.141390E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.420263E+09 0.00 0.00 0.00 0.435585E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.466303E+09 0.00 0.00 0.00 0.627429E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.487315E+09 0.00 0.00 0.00 0.989872E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.446818E+09 0.00 0.00 0.00 0.935991E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.502131E+09 0.00 0.00 0.00 0.101133E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.430207E+09 0.00 0.00 0.00 0.787844E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.442576E+09 0.00 0.00 0.00 0.477595E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.439952E+09 0.00 0.00 180000.00 0.273683E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.419001E+09 0.00 0.00 5106592.99 0.108527E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.537442E+10 0.00 0.00 13781396.16 0.601616E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.398051E+09 0.00 0.00 0.00 64226531.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.502131E+09 0.00 0.00 5106592.99 0.101133E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_ZN

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.348765E+09 0.00 0.00 7749445.76 0.00 2879791.68 0.623427E+09 0.00 0.19
February 0.314607E+09 0.00 0.00 5011887.75 0.00 0.00 0.719695E+09 0.00 0.19
March 0.341768E+09 0.00 0.00 7832190.49 0.00 0.00 0.689988E+09 0.00 0.21
April 0.131030E+09 1125527.26 0.00 16215661.56 79335.57 0.00 0.364932E+09 0.00 0.19
May 94767382.39 15457472.87 0.00 18906161.59 1539480.36 0.00 0.234395E+09 0.00 0.20
June 28825524.37 0.145490E+09 0.00 15173661.53 13851032.02 0.00 0.109083E+09 0.00 0.21
July 2236040.50 0.426241E+09 0.00 5421118.42 32365936.21 0.00 37945531.23 0.00 0.18
August 12650368.15 0.501041E+09 0.00 2922495.01 27496941.18 0.00 40035752.08 0.00 0.21
September 23092471.37 0.293930E+09 0.00 5374412.11 16982306.51 0.00 45751024.96 0.00 0.19
October 0.165007E+09 64783322.38 0.00 13241942.00 3312794.10 0.00 0.451801E+09 0.00 0.19
November 0.256865E+09 729084.48 0.00 10923135.80 0.00 0.00 0.572683E+09 0.00 0.20
December 0.400035E+09 0.00 0.00 6736610.08 0.00 0.00 0.797696E+09 0.00 0.18
                   
Annual Sum or Average 0.211965E+10 0.144880E+10 0.00 0.115509E+09 95627825.94 2879791.68 0.468743E+10 0.00 0.20
Minimum of Months 2236040.50 0.00 0.00 2922495.01 0.00 0.00 37945531.23 0.00 0.18
Maximum of Months 0.400035E+09 0.501041E+09 0.00 18906161.59 32365936.21 2879791.68 0.797696E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_1

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.173006E+09 383725.89 0.00 10434876.36 0.00 5759700.27 0.228962E+09 0.00 0.19
February 0.228186E+09 0.00 0.00 3512232.95 0.00 21686066.28 0.269234E+09 0.00 0.19
March 0.225908E+09 3763696.61 0.00 3373781.11 528679.44 29826400.22 0.177619E+09 0.00 0.21
April 72564579.57 76283708.11 0.00 4804097.09 8305756.76 0.00 61618738.72 0.00 0.19
May 51529948.10 0.163387E+09 0.00 3606401.58 19270528.72 0.00 14018088.04 0.00 0.20
June 17866487.31 0.366570E+09 0.00 841892.59 34871770.79 0.00 7017340.56 0.00 0.21
July 3144956.38 0.463774E+09 0.00 473984.57 32948109.85 0.00 4914390.68 0.00 0.19
August 12233885.95 0.521330E+09 0.00 782579.09 29299456.60 0.00 7739656.69 0.00 0.21
September 16070171.96 0.337516E+09 0.00 1269306.59 20558998.32 0.00 13188725.23 0.00 0.19
October 95752926.71 95439219.40 0.00 9162914.11 5468345.26 0.00 0.146790E+09 0.00 0.19
November 0.140399E+09 6326488.33 0.00 11639072.84 190455.51 0.00 0.211187E+09 0.00 0.20
December 0.229408E+09 0.00 0.00 8169439.37 0.00 25593767.59 0.303641E+09 0.00 0.18
                   
Annual Sum or Average 0.126607E+10 0.203477E+10 0.00 58070578.23 0.151442E+09 82865934.36 0.144593E+10 0.00 0.20
Minimum of Months 3144956.38 0.00 0.00 473984.57 0.00 0.00 4914390.68 0.00 0.18
Maximum of Months 0.229408E+09 0.521330E+09 0.00 11639072.84 34871770.79 29826400.22 0.303641E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_2

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.115474E+09 80955.53 0.00 2586158.23 0.00 4955465.55 0.129970E+09 0.00 0.19
February 0.154415E+09 0.00 0.00 1046848.14 0.00 1066093.10 0.164546E+09 0.00 0.19
March 0.137836E+09 1800979.97 0.00 2054134.00 59704.88 3419652.37 0.129047E+09 0.00 0.21
April 38987844.48 43807725.86 0.00 5251554.44 2381057.94 0.00 47242098.70 0.00 0.19
May 21099297.37 91678696.02 0.00 4088745.28 7349377.64 0.00 19785953.86 0.00 0.20
June 8882961.37 0.221977E+09 0.00 1100217.25 16794724.26 0.00 6797540.54 0.00 0.22
July 1554377.16 0.306781E+09 0.00 452599.74 20427587.69 0.00 3002872.21 0.00 0.19
August 4835248.58 0.341971E+09 0.00 562877.83 18090072.51 0.00 6579073.45 0.00 0.22
September 7561014.34 0.224298E+09 0.00 785419.49 12690407.65 0.00 9307818.02 0.00 0.19
October 54769292.82 60883758.68 0.00 4987596.77 2835593.59 0.00 93473878.75 0.00 0.19
November 83089479.93 4784270.65 0.00 4357096.32 163537.67 0.00 0.134122E+09 0.00 0.20
December 0.171748E+09 53890.33 0.00 1800158.94 0.00 1565732.66 0.164521E+09 0.00 0.18
                   
Annual Sum or Average 0.800252E+09 0.129812E+10 0.00 29073406.41 80792063.83 11006943.67 0.908395E+09 0.00 0.20
Minimum of Months 1554377.16 0.00 0.00 452599.74 0.00 0.00 3002872.21 0.00 0.18
Maximum of Months 0.171748E+09 0.341971E+09 0.00 5251554.44 20427587.69 4955465.55 0.164546E+09 0.00 0.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_3

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.254449E+09 0.00 0.00 1640952.02 0.00 20793685.94 0.180150E+09 0.00 0.19
February 0.403540E+09 0.00 0.00 431439.50 0.00 10343731.81 0.147060E+09 0.00 0.19
March 0.307941E+09 312196.44 0.00 1716186.17 22513.16 17214039.58 0.163176E+09 0.00 0.21
April 76209749.96 45951995.06 0.00 5440167.71 3305152.78 0.00 87294481.71 0.00 0.19
May 40539331.71 0.110101E+09 0.00 4695410.34 10694144.92 0.00 34854742.61 0.00 0.20
June 15976089.55 0.318398E+09 0.00 1360348.09 26073109.67 0.00 11538767.46 0.00 0.21
July 2838366.88 0.471102E+09 0.00 539787.70 33516545.72 0.00 4911507.35 0.00 0.19
August 10283528.55 0.527759E+09 0.00 842990.71 30002265.38 0.00 9737647.45 0.00 0.21
September 13705355.43 0.335379E+09 0.00 1169830.76 20696037.17 0.00 15230173.27 0.00 0.19
October 0.102238E+09 83845374.52 0.00 5561502.58 4610600.86 0.00 0.174687E+09 0.00 0.19
November 0.169962E+09 3499623.82 0.00 4272744.18 288953.83 118235.14 0.233551E+09 0.00 0.20
December 0.400824E+09 0.00 0.00 1094442.50 0.00 21546849.71 0.174668E+09 0.00 0.18
                   
Annual Sum or Average 0.179851E+10 0.189635E+10 0.00 28765802.26 0.129209E+09 70016542.18 0.123686E+10 0.00 0.20
Minimum of Months 2838366.88 0.00 0.00 431439.50 0.00 0.00 4911507.35 0.00 0.18
Maximum of Months 0.403540E+09 0.527759E+09 0.00 5561502.58 33516545.72 21546849.71 0.233551E+09 0.00 0.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_ZN_4

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.140957E+09 0.00 0.00 2621909.84 0.00 6472488.59 0.132153E+09 0.00 0.19
February 0.202644E+09 0.00 0.00 958349.34 0.00 2847066.81 0.132164E+09 0.00 0.19
March 0.174864E+09 221190.39 0.00 1719088.73 3757.47 4590683.48 0.116208E+09 0.00 0.21
April 45570173.93 28490842.18 0.00 4215694.02 713427.33 0.00 55702643.33 0.00 0.19
May 24320790.45 67753609.41 0.00 3135915.77 3390554.40 0.00 22384381.97 0.00 0.20
June 9584914.40 0.203431E+09 0.00 884967.03 6595070.47 0.00 6852740.55 0.00 0.22
July 1148437.50 0.295218E+09 0.00 413645.48 16062531.74 0.00 3479305.93 0.00 0.19
August 4513831.58 0.331246E+09 0.00 647807.72 12377796.69 0.00 7223410.68 0.00 0.22
September 8053838.39 0.209986E+09 0.00 746872.28 9147756.51 0.00 9186436.68 0.00 0.19
October 57973982.98 52275360.15 0.00 4465087.20 2160248.60 0.00 0.108301E+09 0.00 0.19
November 94478515.61 3341486.09 0.00 4348718.31 112097.21 0.00 0.144551E+09 0.00 0.20
December 0.200438E+09 1193.57 0.00 1875509.62 0.00 6304702.21 0.155671E+09 0.00 0.18
                   
Annual Sum or Average 0.964548E+09 0.119196E+10 0.00 26033565.35 50563240.43 20214941.09 0.893877E+09 0.00 0.20
Minimum of Months 1148437.50 0.00 0.00 413645.48 0.00 0.00 3479305.93 0.00 0.18
Maximum of Months 0.202644E+09 0.331246E+09 0.00 4465087.20 16062531.74 6472488.59 0.155671E+09 0.00 0.22



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 08:29:54

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.585625E+11 0.217115E+10 0.00 0.768624E+10 0.688220E+10
February 0.651432E+11 0.240329E+10 0.00 0.745430E+10 0.297117E+10
March 0.918064E+11 0.359706E+10 0.00 0.743975E+10 0.564721E+10
April 0.126874E+12 0.359532E+10 0.00 0.362729E+10 0.142469E+11
May 0.133843E+12 0.340748E+10 0.00 0.215437E+10 0.195036E+11
June 0.139911E+12 0.310126E+10 0.00 -385317420.6 0.278547E+11
July 0.124959E+12 0.271271E+10 0.00 -0.194588E+10 0.286113E+11
August 0.110449E+12 0.238741E+10 0.00 -0.191704E+10 0.313031E+11
September 0.891386E+11 0.207238E+10 0.00 -603969562.9 0.259027E+11
October 0.779353E+11 0.233384E+10 0.00 0.469339E+10 0.173065E+11
November 0.615606E+11 0.234763E+10 0.00 0.730124E+10 0.106507E+11
December 0.461660E+11 0.212464E+10 0.00 0.997636E+10 0.488697E+10
           
Annual Sum or Average 0.112635E+13 0.322542E+11 0.00 0.454807E+11 0.195767E+12
Minimum of Months 0.461660E+11 0.207238E+10 0.00 -0.194588E+10 0.297117E+10
Maximum of Months 0.139911E+12 0.359706E+10 0.00 0.997636E+10 0.313031E+11